Table of Contents

Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.04 00:30

Tabular Output Report in Format: HTML

Building: OutPatientHealthCare

Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470

Simulation Timestamp: 2020-06-04 00:31:20


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 5267.93 1384.84 1384.84
Net Site Energy 5267.93 1384.84 1384.84
Total Source Energy 13078.50 3438.08 3438.08
Net Source Energy 13078.50 3438.08 3438.08


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3804.01
Net Conditioned Building Area 3804.01
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 253.03 1302.26 0.00 0.00 0.00 0.00
Cooling 347.07 0.00 0.00 0.00 0.00 0.00
Interior Lighting 380.82 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 55.34 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1829.40 188.37 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 345.45 0.00 0.00 0.00 0.00 0.00
Pumps 7.47 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 318.66 0.00 0.00 0.00 0.00 118.54
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 240.06 0.00 0.00 0.00 478.84
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 3537.24 1730.69 0.00 0.00 0.00 597.38
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 1302.26 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 253.03 0.00 0.00 0.00 0.00 0.00
Cooling General 347.07 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 380.82 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 55.34 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1190.14 188.37 0.00 0.00 0.00 0.00
  ElevatorLift 636.70 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.57 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 345.45 0.00 0.00 0.00 0.00 0.00
Pumps General 7.47 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 318.66 0.00 0.00 0.00 0.00 118.54
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 240.06 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 478.84
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 114.66 0.00 0.00 0.00 0.00 0.00
HVAC 334.30 405.45 0.00 0.00 0.00 0.16
Other 480.92 49.52 0.00 0.00 0.00 0.00
Total 929.87 454.97 0.00 0.00 0.00 0.16


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 114.66 0.00 0.00 0.00 0.00 0.00
HVAC 334.30 405.45 0.00 0.00 0.00 0.16
Other 480.92 49.52 0.00 0.00 0.00 0.00
Total 929.87 454.97 0.00 0.00 0.00 0.16


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 3537.236 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 3537.236 100.00
     
Total On-Site and Utility Electric Sources 3537.236 100.00
Total Electricity End Uses 3537.236 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 597.38 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 597.38 100.00
Total Water End Uses 597.38 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 2344.50
Time Setpoint Not Met During Occupied Cooling 1786.17
Time Not Comfortable Based on Simple ASHRAE 55-2004 7830.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Meter |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Meter |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Meter |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Meter |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OUTPATIENTHEALTHCARE

| Meter |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Meter |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Meter |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7

| Meter |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS

| Meter |

ZoneCoolingSummaryMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

ZoneHeatingSummaryMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

ZoneElectricSummaryMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

SpaceGainsMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 HUMID | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOCKER ROOM | FLOOR 1 LOUNGE | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI ROOM | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE STATION | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 2 CONFERENCE | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 RECEPTION | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 WORK | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 HUMID | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 OFFICE | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 TREATMENT | FLOOR 3 WORK | FLOOR 1 BIO HAZ | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 IT HALL | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 MED GAS | FLOOR 1 MRI HALL | FLOOR 1 MRI TOILET | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE TOILET | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP TOILET | FLOOR 1 RECEPTION HALL | FLOOR 1 SCRUB | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 3 ELEVATOR HALL | FLOOR 3 JANITOR | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

PeakSpaceGainsMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 HUMID | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOCKER ROOM | FLOOR 1 LOUNGE | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI ROOM | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE STATION | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 2 CONFERENCE | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 RECEPTION | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 WORK | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 HUMID | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 OFFICE | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 TREATMENT | FLOOR 3 WORK | FLOOR 1 BIO HAZ | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 IT HALL | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 MED GAS | FLOOR 1 MRI HALL | FLOOR 1 MRI TOILET | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE TOILET | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP TOILET | FLOOR 1 RECEPTION HALL | FLOOR 1 SCRUB | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 3 ELEVATOR HALL | FLOOR 3 JANITOR | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

SpaceGainComponentsAtCoolingPeakMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

ComfortReportSimple55Monthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

OccupantComfortDataSummaryMonthly

| FLOOR 1 ANESTHESIA PEOPLE | FLOOR 1 CAFE PEOPLE | FLOOR 1 CLEAN PEOPLE | FLOOR 1 CLEAN WORK PEOPLE | FLOOR 1 DICTATION PEOPLE | FLOOR 1 DRESSING ROOM PEOPLE | FLOOR 1 HUMID PEOPLE | FLOOR 1 IT ROOM PEOPLE | FLOOR 1 LOBBY PEOPLE | FLOOR 1 LOCKER ROOM PEOPLE | FLOOR 1 LOUNGE PEOPLE | FLOOR 1 MRI CONTROL ROOM PEOPLE | FLOOR 1 MRI ROOM PEOPLE | FLOOR 1 NOURISHMENT PEOPLE | FLOOR 1 NURSE STATION PEOPLE | FLOOR 1 OFFICE PEOPLE | FLOOR 1 OPERATING ROOM 1 PEOPLE | FLOOR 1 OPERATING ROOM 2 PEOPLE | FLOOR 1 OPERATING ROOM 3 PEOPLE | FLOOR 1 PACU PEOPLE | FLOOR 1 PRE-OP ROOM 1 PEOPLE | FLOOR 1 PRE-OP ROOM 2 PEOPLE | FLOOR 1 PROCEDURE ROOM PEOPLE | FLOOR 1 RECEPTION PEOPLE | FLOOR 1 RECOVERY ROOM PEOPLE | FLOOR 1 SCHEDULING PEOPLE | FLOOR 1 SOIL PEOPLE | FLOOR 1 SOIL HOLD PEOPLE | FLOOR 1 SOIL WORK PEOPLE | FLOOR 1 STEP DOWN PEOPLE | FLOOR 2 CONFERENCE PEOPLE | FLOOR 2 DICTATION PEOPLE | FLOOR 2 EXAM 1 PEOPLE | FLOOR 2 EXAM 2 PEOPLE | FLOOR 2 EXAM 3 PEOPLE | FLOOR 2 EXAM 4 PEOPLE | FLOOR 2 EXAM 5 PEOPLE | FLOOR 2 EXAM 6 PEOPLE | FLOOR 2 EXAM 7 PEOPLE | FLOOR 2 EXAM 8 PEOPLE | FLOOR 2 EXAM 9 PEOPLE | FLOOR 2 LOUNGE PEOPLE | FLOOR 2 NURSE STATION 1 PEOPLE | FLOOR 2 NURSE STATION 2 PEOPLE | FLOOR 2 OFFICE PEOPLE | FLOOR 2 RECEPTION PEOPLE | FLOOR 2 SCHEDULING 1 PEOPLE | FLOOR 2 SCHEDULING 2 PEOPLE | FLOOR 2 WORK PEOPLE | FLOOR 2 X-RAY PEOPLE | FLOOR 3 DRESSING ROOM PEOPLE | FLOOR 3 HUMID PEOPLE | FLOOR 3 LOCKER PEOPLE | FLOOR 3 LOUNGE PEOPLE | FLOOR 3 OFFICE PEOPLE | FLOOR 3 PHYSICAL THERAPY 1 PEOPLE | FLOOR 3 PHYSICAL THERAPY 2 PEOPLE | FLOOR 3 TREATMENT PEOPLE | FLOOR 3 WORK PEOPLE |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| AHU-1_COOLC DXCOIL | AHU-2_COOLC DXCOIL |

WindowReportMonthly

| 78F987 | D8037E | 4A8120 | AAE778 | 3AAD8B | 8128A9 | 9B1541 | CF850A | A6BA23 | D10D28 | 591336 | 38B811 | C044D6 | 1D94BE | 18748E | 137A56 | 8D508E | B2D381 | 1DA13A | 44E54A | 757D10 | E33BAE | 24167A | 2C0938 | 8600DD | A1ED60 | E8D997 | 88E1FC | F83F33 | B1F5EE | F52F3D | 80885D | FEEF06 | 2BE8DE | 513E2A | BA5CD9 | 1AD478 | 27F0AC | 724114 | D538C4 | 5635BC | 831C1D | 9BB95F | C0778D | 7D2D69 | 2EF63B | C417C0 | EB042B | 4C1F71 | D23C8B | B4E4BE | EEF55D | E55A57 | 93D018 | DD9F5D | 15B02B | 820282 | 9BA05A | C639E8 | A2790A | 79FCEE | EDE617 | C61F0D | 7248C5 | 29FA28 | F0B23F | EEC10E | 944FCE | C41399 | 95BA33 | F27282 | 3DB407 | 3DADE2 | DF3E2C | 5031C8 | C087D0 | D2CA75 | B0FB49 | FE9BC9 | 9DF7DE | D0BE44 | 6B5226 | 8F59F7 | 44F571 | 6BD844 | 86D536 | BAF71D | 3833A2 | 2111A1 | 9BC521 | 142781 | E74902 | 93BBC3 | C635A6 |

WindowEnergyReportMonthly

| 78F987 | D8037E | 4A8120 | AAE778 | 3AAD8B | 8128A9 | 9B1541 | CF850A | A6BA23 | D10D28 | 591336 | 38B811 | C044D6 | 1D94BE | 18748E | 137A56 | 8D508E | B2D381 | 1DA13A | 44E54A | 757D10 | E33BAE | 24167A | 2C0938 | 8600DD | A1ED60 | E8D997 | 88E1FC | F83F33 | B1F5EE | F52F3D | 80885D | FEEF06 | 2BE8DE | 513E2A | BA5CD9 | 1AD478 | 27F0AC | 724114 | D538C4 | 5635BC | 831C1D | 9BB95F | C0778D | 7D2D69 | 2EF63B | C417C0 | EB042B | 4C1F71 | D23C8B | B4E4BE | EEF55D | E55A57 | 93D018 | DD9F5D | 15B02B | 820282 | 9BA05A | C639E8 | A2790A | 79FCEE | EDE617 | C61F0D | 7248C5 | 29FA28 | F0B23F | EEC10E | 944FCE | C41399 | 95BA33 | F27282 | 3DB407 | 3DADE2 | DF3E2C | 5031C8 | C087D0 | D2CA75 | B0FB49 | FE9BC9 | 9DF7DE | D0BE44 | 6B5226 | 8F59F7 | 44F571 | 6BD844 | 86D536 | BAF71D | 3833A2 | 2111A1 | 9BC521 | 142781 | E74902 | 93BBC3 | C635A6 |

WindowZoneSummaryMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

WindowEnergyZoneSummaryMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| FLOOR 2 RECEPTION_DAYLCTRL | FLOOR 3 OFFICE_DAYLCTRL | FLOOR 3 LOUNGE_DAYLCTRL | FLOOR 2 OFFICE_DAYLCTRL | FLOOR 2 CONFERENCE_DAYLCTRL |

CoilReportMonthly

| FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL | FLOOR 1 BIO HAZ VAV BOX REHEAT COIL | FLOOR 1 CAFE VAV BOX REHEAT COIL | FLOOR 1 CLEAN VAV BOX REHEAT COIL | FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL | FLOOR 1 DICTATION VAV BOX REHEAT COIL | FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL | FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL | FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL | FLOOR 1 HUMID VAV BOX REHEAT COIL | FLOOR 1 IT HALL VAV BOX REHEAT COIL | FLOOR 1 IT ROOM VAV BOX REHEAT COIL | FLOOR 1 LOBBY VAV BOX REHEAT COIL | FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL | FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL | FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL | FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL | FLOOR 1 LOUNGE VAV BOX REHEAT COIL | FLOOR 1 MED GAS VAV BOX REHEAT COIL | FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL | FLOOR 1 MRI HALL VAV BOX REHEAT COIL | FLOOR 1 MRI ROOM VAV BOX REHEAT COIL | FLOOR 1 MRI TOILET VAV BOX REHEAT COIL | FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL | FLOOR 1 NURSE HALL VAV BOX REHEAT COIL | FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL | FLOOR 1 NURSE STATION VAV BOX REHEAT COIL | FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL | FLOOR 1 OFFICE VAV BOX REHEAT COIL | FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL | FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL | FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL | FLOOR 1 PACU VAV BOX REHEAT COIL | FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL | FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL | FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL | FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL | FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL | FLOOR 1 RECEPTION VAV BOX REHEAT COIL | FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL | FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL | FLOOR 1 SCHEDULING VAV BOX REHEAT COIL | FLOOR 1 SCRUB VAV BOX REHEAT COIL | FLOOR 1 SOIL VAV BOX REHEAT COIL | FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL | FLOOR 1 SOIL WORK VAV BOX REHEAT COIL | FLOOR 1 STEP DOWN VAV BOX REHEAT COIL | FLOOR 1 STERILE HALL VAV BOX REHEAT COIL | FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL | FLOOR 1 STORAGE VAV BOX REHEAT COIL | FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL | FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL | FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL | FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL | FLOOR 1 VESTIBULE VAV BOX REHEAT COIL | AHU-1_HEATC | AHU-2_HEATC | AHU-1_EXTRAWATERHEATC | FLOOR 2 CONFERENCE VAV BOX REHEAT COIL | FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL | FLOOR 2 DICTATION VAV BOX REHEAT COIL | FLOOR 2 EXAM 1 VAV BOX REHEAT COIL | FLOOR 2 EXAM 2 VAV BOX REHEAT COIL | FLOOR 2 EXAM 3 VAV BOX REHEAT COIL | FLOOR 2 EXAM 4 VAV BOX REHEAT COIL | FLOOR 2 EXAM 5 VAV BOX REHEAT COIL | FLOOR 2 EXAM 6 VAV BOX REHEAT COIL | FLOOR 2 EXAM 7 VAV BOX REHEAT COIL | FLOOR 2 EXAM 8 VAV BOX REHEAT COIL | FLOOR 2 EXAM 9 VAV BOX REHEAT COIL | FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL | FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL | FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL | FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL | FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL | FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL | FLOOR 2 JANITOR VAV BOX REHEAT COIL | FLOOR 2 LOUNGE VAV BOX REHEAT COIL | FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL | FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL | FLOOR 2 OFFICE VAV BOX REHEAT COIL | FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL | FLOOR 2 RECEPTION VAV BOX REHEAT COIL | FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL | FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL | FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL | FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL | FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL | FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL | FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL | FLOOR 2 UTILITY VAV BOX REHEAT COIL | FLOOR 2 WORK VAV BOX REHEAT COIL | FLOOR 2 WORK HALL VAV BOX REHEAT COIL | FLOOR 2 WORK TOILET VAV BOX REHEAT COIL | FLOOR 2 X-RAY VAV BOX REHEAT COIL | FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL | FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL | FLOOR 3 HUMID VAV BOX REHEAT COIL | FLOOR 3 JANITOR VAV BOX REHEAT COIL | FLOOR 3 LOCKER VAV BOX REHEAT COIL | FLOOR 3 LOUNGE VAV BOX REHEAT COIL | FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL | FLOOR 3 MECHANICAL VAV BOX REHEAT COIL | FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL | FLOOR 3 OFFICE VAV BOX REHEAT COIL | FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL | FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL | FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL | FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL | FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL | FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL | FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL | FLOOR 3 TREATMENT VAV BOX REHEAT COIL | FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL | FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL | FLOOR 3 UTILITY VAV BOX REHEAT COIL | FLOOR 3 WORK VAV BOX REHEAT COIL | NE STAIR VAV BOX REHEAT COIL | NW ELEVATOR VAV BOX REHEAT COIL | NW STAIR VAV BOX REHEAT COIL | SW STAIR VAV BOX REHEAT COIL | AHU-1_EXTRAELECHEATC | AHU-1_COOLC DXCOIL | AHU-2_COOLC DXCOIL |

PlantLoopDemandReportMonthly

| SWHSYS1 | HEATSYS1 |

FanReportMonthly

| AHU-1_FAN | AHU-2_FAN | FLOOR 1 ANESTHESIA EXHAUST FAN | FLOOR 1 LOBBY TOILET EXHAUST FAN | FLOOR 1 MRI CONTROL ROOM EXHAUST FAN | FLOOR 1 MRI ROOM EXHAUST FAN | FLOOR 1 MRI TOILET EXHAUST FAN | FLOOR 1 NURSE TOILET EXHAUST FAN | FLOOR 1 PRE-OP TOILET EXHAUST FAN | FLOOR 1 SOIL EXHAUST FAN | FLOOR 1 SOIL HOLD EXHAUST FAN | FLOOR 1 SOIL WORK EXHAUST FAN | FLOOR 2 CONFERENCE TOILET EXHAUST FAN | FLOOR 2 RECEPTION TOILET EXHAUST FAN | FLOOR 2 WORK TOILET EXHAUST FAN | FLOOR 2 X-RAY EXHAUST FAN | FLOOR 3 LOUNGE TOILET EXHAUST FAN | FLOOR 3 OFFICE TOILET EXHAUST FAN | FLOOR 3 PHYSICAL THERAPY TOILET EXHAUST FAN |

PumpReportMonthly

| HEATSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 | HEATSYS1 |

ZoneTemperatureOscillationReportMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

AirLoopSystemEnergyAndWaterUseMonthly

| AHU-1 | AHU-2 |

AirLoopSystemComponentLoadsMonthly

| AHU-1 | AHU-2 |

AirLoopSystemComponentEnergyUseMonthly

| AHU-1 | AHU-2 |

MechanicalVentilationLoadsMonthly

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

General

Value
Program Version and Build EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.04 00:30
RunPeriod RUNPERIOD 1
Weather File International Falls Intl Ap MN USA TMY3 WMO#=727470
Latitude [deg] 48.57
Longitude [deg] -93.4
Elevation [m] 359.00
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1553.34 473.81 302.86 473.81 302.86
Above Ground Wall Area [m2] 1553.34 473.81 302.86 473.81 302.86
Window Opening Area [m2] 308.29 97.22 57.97 114.08 39.02
Gross Window-Wall Ratio [%] 19.85 20.52 19.14 24.08 12.88
Above Ground Window-Wall Ratio [%] 19.85 20.52 19.14 24.08 12.88


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1553.34 473.81 302.86 473.81 302.86
Above Ground Wall Area [m2] 1553.34 473.81 302.86 473.81 302.86
Window Opening Area [m2] 308.29 97.22 57.97 114.08 39.02
Gross Window-Wall Ratio [%] 19.85 20.52 19.14 24.08 12.88
Above Ground Window-Wall Ratio [%] 19.85 20.52 19.14 24.08 12.88


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1373.29
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
FLOOR 1 ANESTHESIA 10.03 Yes Yes 30.58 1.00 8.36 0.00 2.23 2.23 15.0695 4.64 21.5300
FLOOR 1 BIO HAZ 5.20 Yes Yes 15.86 1.00 0.00 0.00 0.00 0.00 4.0903   1.0800
FLOOR 1 CAFE 39.02 Yes Yes 118.93 1.00 18.58 0.00 8.92 8.92 4.3056 0.93 10.7600
FLOOR 1 CLEAN 11.71 Yes Yes 35.68 1.00 0.00 0.00 0.00 0.00 15.0695 4.64 21.5300
FLOOR 1 CLEAN WORK 15.33 Yes Yes 46.72 1.00 0.00 0.00 0.00 0.00 15.0695 4.64 21.5300
FLOOR 1 DICTATION 11.71 Yes Yes 35.68 1.00 0.00 0.00 0.00 0.00 7.9653 18.58 11.8400
FLOOR 1 DRESSING ROOM 4.18 Yes Yes 12.74 1.00 8.36 0.00 2.32 2.32 7.9653 18.58 11.8400
FLOOR 1 ELECTRICAL ROOM 9.10 Yes Yes 27.75 1.00 6.50 0.00 0.00 0.00 15.0695   53.8200
FLOOR 1 ELEVATOR PUMP ROOM 8.45 Yes Yes 25.77 1.00 18.58 0.00 0.00 0.00 15.0695   5719.4020
FLOOR 1 HUMID 5.02 Yes Yes 15.29 1.00 0.00 0.00 0.00 0.00 7.9653 18.58 11.8400
FLOOR 1 IT HALL 13.01 Yes Yes 39.64 1.00 0.00 0.00 0.00 0.00 5.2958   4.3100
FLOOR 1 IT ROOM 10.41 Yes Yes 31.71 1.00 0.00 0.00 0.00 0.00 7.9653 18.58 11.8400
FLOOR 1 LOBBY 57.79 Yes Yes 176.13 1.00 20.44 0.00 8.92 8.92 9.0417 9.29 11.8400
FLOOR 1 LOBBY HALL 22.30 Yes Yes 67.96 1.00 0.00 0.00 0.00 0.00 5.2958   4.3100
FLOOR 1 LOBBY TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 0.00 0.00 6.7813   4.3100
FLOOR 1 LOCKER ROOM 61.32 Yes Yes 186.89 1.00 20.44 0.00 5.57 5.57 6.3507 6.19 32.2900
FLOOR 1 LOCKER ROOM HALL 46.08 Yes Yes 140.45 1.00 0.00 0.00 0.00 0.00 5.2958   4.3100
FLOOR 1 LOUNGE 33.45 Yes Yes 101.94 1.00 0.00 0.00 0.00 0.00 6.3507 6.19 32.2900
FLOOR 1 MED GAS 5.20 Yes Yes 15.86 1.00 13.94 0.00 0.00 0.00 4.0903   1.0800
FLOOR 1 MRI CONTROL ROOM 15.61 Yes Yes 47.57 1.00 4.65 0.00 0.00 0.00 10.1181 4.64 107.6400
FLOOR 1 MRI HALL 13.66 Yes Yes 41.63 1.00 0.00 0.00 0.00 0.00 5.2958   4.3100
FLOOR 1 MRI ROOM 40.88 Yes Yes 124.59 1.00 0.00 0.00 0.00 0.00 10.1181 4.64 107.6400
FLOOR 1 MRI TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 0.00 0.00 6.7813   4.3100
FLOOR 1 NOURISHMENT 16.91 Yes Yes 51.54 1.00 0.00 0.00 0.00 0.00 12.5938 4.64 21.5300
FLOOR 1 NURSE HALL 46.08 Yes Yes 140.45 1.00 0.00 0.00 0.00 0.00 5.2958   4.3100
FLOOR 1 NURSE JANITOR 5.02 Yes Yes 15.29 1.00 0.00 0.00 0.00 0.00 4.0903   1.0800
FLOOR 1 NURSE STATION 24.25 Yes Yes 73.91 1.00 0.00 0.00 0.00 0.00 12.5938 4.64 21.5300
FLOOR 1 NURSE TOILET 5.02 Yes Yes 15.29 1.00 0.00 0.00 0.00 0.00 6.7813   4.3100
FLOOR 1 OFFICE 44.87 Yes Yes 136.77 1.00 0.00 0.00 0.00 0.00 7.9653 18.58 11.8400
FLOOR 1 OPERATING ROOM 1 42.74 Yes Yes 130.26 1.00 39.95 0.00 8.92 8.92 24.3264 4.64 118.3600
FLOOR 1 OPERATING ROOM 2 44.59 Yes Yes 135.92 1.00 22.30 0.00 6.69 6.69 24.3264 4.64 118.3600
FLOOR 1 OPERATING ROOM 3 44.22 Yes Yes 134.79 1.00 0.00 0.00 0.00 0.00 24.3264 4.64 118.3600
FLOOR 1 PACU 10.03 Yes Yes 30.58 1.00 0.00 0.00 0.00 0.00 13.4549 4.64 32.2900
FLOOR 1 PRE-OP HALL 49.05 Yes Yes 149.51 1.00 0.00 0.00 0.00 0.00 5.2958   4.3100
FLOOR 1 PRE-OP ROOM 1 17.56 Yes Yes 53.52 1.00 3.72 0.00 0.00 0.00 7.3195 9.29 21.5300
FLOOR 1 PRE-OP ROOM 2 31.40 Yes Yes 95.71 1.00 0.00 0.00 0.00 0.00 7.3195 9.29 21.5300
FLOOR 1 PRE-OP TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 0.00 0.00 6.7813   4.3100
FLOOR 1 PROCEDURE ROOM 26.48 Yes Yes 80.70 1.00 17.65 0.00 5.57 5.57 15.0695 4.64 32.2900
FLOOR 1 RECEPTION 47.29 Yes Yes 144.13 1.00 12.08 0.00 3.34 3.34 9.0417 3.10 11.8400
FLOOR 1 RECEPTION HALL 11.89 Yes Yes 36.25 1.00 0.00 0.00 0.00 0.00 5.2958   4.3100
FLOOR 1 RECOVERY ROOM 50.17 Yes Yes 152.91 1.00 41.81 0.00 8.92 8.92 13.4549 4.64 32.2900
FLOOR 1 SCHEDULING 11.06 Yes Yes 33.70 1.00 6.50 0.00 0.74 0.74 7.9653 18.58 11.8400
FLOOR 1 SCRUB 7.80 Yes Yes 23.79 1.00 0.00 0.00 0.00 0.00 5.2958   4.3100
FLOOR 1 SOIL 11.71 Yes Yes 35.68 1.00 0.00 0.00 0.00 0.00 15.0695 4.64 21.5300
FLOOR 1 SOIL HOLD 5.20 Yes Yes 15.86 1.00 0.00 0.00 0.00 0.00 15.0695 4.64 21.5300
FLOOR 1 SOIL WORK 16.72 Yes Yes 50.97 1.00 0.00 0.00 0.00 0.00 15.0695 4.64 21.5300
FLOOR 1 STEP DOWN 27.87 Yes Yes 84.95 1.00 34.37 0.00 6.69 6.69 13.4549 4.64 32.2900
FLOOR 1 STERILE HALL 57.23 Yes Yes 174.43 1.00 7.43 0.00 2.23 2.23 5.2958   4.3100
FLOOR 1 STERILE STORAGE 36.79 Yes Yes 112.13 1.00 0.00 0.00 0.00 0.00 4.0903   1.0800
FLOOR 1 STORAGE 85.47 Yes Yes 260.51 1.00 58.53 0.00 8.36 8.36 4.0903   1.0800
FLOOR 1 SUB-STERILE 18.21 Yes Yes 55.50 1.00 13.01 0.00 2.97 2.97 5.2958   4.3100
FLOOR 1 UTILITY HALL 23.78 Yes Yes 72.49 1.00 14.86 0.00 0.00 0.00 5.2958   4.3100
FLOOR 1 UTILITY JANITOR 3.90 Yes Yes 11.89 1.00 0.00 0.00 0.00 0.00 4.0903   1.0800
FLOOR 1 UTILITY ROOM 33.45 Yes Yes 101.94 1.00 16.72 0.00 2.23 2.23 4.0903   1.0800
FLOOR 1 VESTIBULE 6.69 Yes Yes 20.39 1.00 7.43 0.00 0.00 0.00 5.2958   4.3100
FLOOR 2 CONFERENCE 31.22 Yes Yes 95.14 1.00 37.16 0.00 8.92 8.92 10.4410 1.86 10.7600
FLOOR 2 CONFERENCE TOILET 5.95 Yes Yes 18.12 1.00 0.00 0.00 0.00 0.00 6.7813   4.3100
FLOOR 2 DICTATION 6.50 Yes Yes 19.82 1.00 0.00 0.00 0.00 0.00 7.9653 18.58 11.8400
FLOOR 2 EXAM 1 33.45 Yes Yes 101.94 1.00 39.02 0.00 8.92 8.92 15.0695 4.64 11.8400
FLOOR 2 EXAM 2 50.17 Yes Yes 152.91 1.00 16.72 0.00 3.72 3.72 15.0695 4.64 11.8400
FLOOR 2 EXAM 3 66.89 Yes Yes 203.88 1.00 22.30 0.00 5.95 5.95 15.0695 4.64 11.8400
FLOOR 2 EXAM 4 7.80 Yes Yes 23.79 1.00 6.50 0.00 2.23 2.23 15.0695 4.64 11.8400
FLOOR 2 EXAM 5 32.52 Yes Yes 99.11 1.00 23.23 0.00 5.95 5.95 15.0695 4.64 11.8400
FLOOR 2 EXAM 6 20.90 Yes Yes 63.71 1.00 13.94 0.00 4.18 4.18 15.0695 4.64 11.8400
FLOOR 2 EXAM 7 73.58 Yes Yes 224.27 1.00 22.30 0.00 5.57 5.57 15.0695 4.64 11.8400
FLOOR 2 EXAM 8 25.08 Yes Yes 76.46 1.00 16.72 0.00 5.57 5.57 15.0695 4.64 11.8400
FLOOR 2 EXAM 9 36.79 Yes Yes 112.13 1.00 11.15 0.00 2.79 2.79 15.0695 4.64 11.8400
FLOOR 2 EXAM HALL 1 16.72 Yes Yes 50.97 1.00 5.57 0.00 0.00 0.00 5.2958   4.3100
FLOOR 2 EXAM HALL 2 16.72 Yes Yes 50.97 1.00 5.57 0.00 0.00 0.00 5.2958   4.3100
FLOOR 2 EXAM HALL 3 16.72 Yes Yes 50.97 1.00 5.57 0.00 0.00 0.00 5.2958   4.3100
FLOOR 2 EXAM HALL 4 18.39 Yes Yes 56.07 1.00 5.57 0.00 0.00 0.00 5.2958   4.3100
FLOOR 2 EXAM HALL 5 18.39 Yes Yes 56.07 1.00 5.57 0.00 0.00 0.00 5.2958   4.3100
FLOOR 2 EXAM HALL 6 18.39 Yes Yes 56.07 1.00 5.57 0.00 0.00 0.00 5.2958   4.3100
FLOOR 2 JANITOR 5.85 Yes Yes 17.84 1.00 14.86 0.00 0.00 0.00 4.0903   1.0800
FLOOR 2 LOUNGE 7.43 Yes Yes 22.65 1.00 0.00 0.00 0.00 0.00 6.3507 6.19 32.2900
FLOOR 2 NURSE STATION 1 13.94 Yes Yes 42.48 1.00 0.00 0.00 0.00 0.00 12.5938 4.64 21.5300
FLOOR 2 NURSE STATION 2 16.72 Yes Yes 50.97 1.00 0.00 0.00 0.00 0.00 12.5938 4.64 21.5300
FLOOR 2 OFFICE 52.03 Yes Yes 158.57 1.00 37.16 0.00 8.92 8.92 7.9653 18.58 11.8400
FLOOR 2 OFFICE HALL 41.25 Yes Yes 125.73 1.00 0.00 0.00 0.00 0.00 5.2958   4.3100
FLOOR 2 RECEPTION 91.42 Yes Yes 278.64 1.00 45.52 0.00 16.72 16.72 9.0417 3.10 11.8400
FLOOR 2 RECEPTION HALL 52.40 Yes Yes 159.71 1.00 6.50 0.00 0.00 0.00 5.2958   4.3100
FLOOR 2 RECEPTION TOILET 11.71 Yes Yes 35.68 1.00 0.00 0.00 0.00 0.00 6.7813   4.3100
FLOOR 2 SCHEDULING 1 30.10 Yes Yes 91.75 1.00 0.00 0.00 0.00 0.00 7.9653 18.58 11.8400
FLOOR 2 SCHEDULING 2 31.77 Yes Yes 96.84 1.00 0.00 0.00 0.00 0.00 7.9653 18.58 11.8400
FLOOR 2 STORAGE 1 5.20 Yes Yes 15.86 1.00 0.00 0.00 0.00 0.00 4.0903   1.0800
FLOOR 2 STORAGE 2 11.15 Yes Yes 33.98 1.00 0.00 0.00 0.00 0.00 4.0903   1.0800
FLOOR 2 STORAGE 3 13.38 Yes Yes 40.78 1.00 0.00 0.00 0.00 0.00 4.0903   1.0800
FLOOR 2 UTILITY 11.71 Yes Yes 35.68 1.00 8.36 0.00 2.23 2.23 4.0903   1.0800
FLOOR 2 WORK 157.01 Yes Yes 478.55 1.00 24.15 0.00 5.57 5.57 7.9653 18.58 9.7803
FLOOR 2 WORK HALL 77.48 Yes Yes 236.16 1.00 5.57 0.00 0.00 0.00 5.2958   4.3100
FLOOR 2 WORK TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 0.00 0.00 6.7813   4.3100
FLOOR 2 X-RAY 83.61 Yes Yes 254.85 1.00 0.00 0.00 0.00 0.00 10.1181 4.64 107.6400
FLOOR 3 DRESSING ROOM 3.90 Yes Yes 11.89 1.00 0.00 0.00 0.00 0.00 7.9653 18.58 11.8400
FLOOR 3 ELEVATOR HALL 34.37 Yes Yes 104.77 1.00 3.72 0.00 0.00 0.00 5.2958   4.3100
FLOOR 3 HUMID 10.03 Yes Yes 30.58 1.00 0.00 0.00 0.00 0.00 7.9653 18.58 11.8400
FLOOR 3 JANITOR 5.85 Yes Yes 17.84 1.00 14.86 0.00 0.00 0.00 4.0903   1.0800
FLOOR 3 LOCKER 11.15 Yes Yes 33.98 1.00 0.00 0.00 0.00 0.00 6.3507 6.19 32.2900
FLOOR 3 LOUNGE 70.51 Yes Yes 214.92 1.00 21.37 0.00 5.57 5.57 6.3507 6.19 32.2900
FLOOR 3 LOUNGE TOILET 17.84 Yes Yes 54.37 1.00 11.15 0.00 4.18 4.18 6.7813   4.3100
FLOOR 3 MECHANICAL 32.52 Yes Yes 99.11 1.00 23.23 0.00 5.95 5.95 15.0695   53.8200
FLOOR 3 MECHANICAL HALL 27.87 Yes Yes 84.95 1.00 0.00 0.00 0.00 0.00 5.2958   4.3100
FLOOR 3 OFFICE 282.05 Yes Yes 859.70 1.00 68.75 0.00 19.51 19.51 7.9653 18.58 11.8400
FLOOR 3 OFFICE HALL 77.48 Yes Yes 236.16 1.00 5.57 0.00 0.00 0.00 5.2958   4.3100
FLOOR 3 OFFICE TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 0.00 0.00 6.7813   4.3100
FLOOR 3 PHYSICAL THERAPY 1 120.77 Yes Yes 368.12 1.00 78.97 0.00 28.99 28.99 9.7952 4.64 16.1500
FLOOR 3 PHYSICAL THERAPY 2 55.00 Yes Yes 167.64 1.00 0.00 0.00 0.00 0.00 9.7952 4.64 16.1500
FLOOR 3 PHYSICAL THERAPY TOILET 7.80 Yes Yes 23.79 1.00 0.00 0.00 0.00 0.00 6.7813   4.3100
FLOOR 3 STORAGE 1 10.03 Yes Yes 30.58 1.00 0.00 0.00 0.00 0.00 4.0903   1.0800
FLOOR 3 STORAGE 2 7.80 Yes Yes 23.79 1.00 0.00 0.00 0.00 0.00 4.0903   1.0800
FLOOR 3 TREATMENT 44.22 Yes Yes 134.79 1.00 0.00 0.00 0.00 0.00 15.0695 4.64 11.8400
FLOOR 3 UNDEVELOPED 1 210.70 Yes Yes 642.23 1.00 66.89 0.00 25.64 25.64 4.0903   11.8400
FLOOR 3 UNDEVELOPED 2 107.02 Yes Yes 326.21 1.00 52.03 0.00 13.38 13.38 4.0903   11.8400
FLOOR 3 UTILITY 20.07 Yes Yes 61.16 1.00 0.00 0.00 0.00 0.00 4.0903   1.0800
FLOOR 3 WORK 53.33 Yes Yes 162.54 1.00 38.09 0.00 8.92 8.92 7.9653 18.58 11.8400
NE STAIR 15.61 Yes Yes 142.72 1.00 97.55 0.00 12.02 12.02 5.2958   4.3100
NW ELEVATOR 13.01 Yes Yes 118.93 1.00 75.25 0.00 0.00 0.00 5.2958   4.3100
NW STAIR 17.84 Yes Yes 163.10 1.00 111.48 0.00 11.15 11.15 5.2958   4.3100
SW STAIR 8.92 Yes Yes 81.55 1.00 55.74 0.00 1.11 1.11 5.2958   4.3100
Total 3804.01     11932.15   1553.34 0.00 308.29 308.29 8.6973 9.08 31.9256
Conditioned Total 3804.01     11932.15   1553.34 0.00 308.29 308.29 8.6973 9.08 31.9256
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 09-JAN-07:19 26-DEC-11:00 - - - 04-JAN-11:00
Heating 128516.87 149041.56 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 26366.16 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 5724.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 86760.32 9905.77 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 15244.37 0.00 0.00 0.00 0.00 0.00
Pumps 585.39 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 28341.85 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 22758.46 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 291538.95 181705.78 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 149041.56 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 26366.16 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 5724.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 62583.90 9905.77 0.00 0.00 0.00 0.00
  ElevatorLift 24082.42 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 94.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 15244.37 0.00 0.00 0.00 0.00 0.00
Pumps General 585.39 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 28341.85 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 22758.46 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 801.34 1411.65 0.00 0.00 0.00
Cooling 1099.16 0.00 0.00 0.00 0.00
Interior Lighting 1206.06 0.00 0.00 0.00 0.00
Exterior Lighting 175.27 0.00 0.00 0.00 0.00
Interior Equipment 5793.73 204.20 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 1094.03 0.00 0.00 0.00 0.00
Pumps 23.65 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 1009.19 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 260.23 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 11202.43 1876.07 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 210.66 371.09 0.00 0.00 0.00
Cooling 288.95 0.00 0.00 0.00 0.00
Interior Lighting 317.05 0.00 0.00 0.00 0.00
Exterior Lighting 46.08 0.00 0.00 0.00 0.00
Interior Equipment 1523.06 53.68 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 287.60 0.00 0.00 0.00 0.00
Pumps 6.22 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 265.30 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 68.41 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 2944.90 493.18 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 210.66 371.09 0.00 0.00 0.00
Cooling 288.95 0.00 0.00 0.00 0.00
Interior Lighting 317.05 0.00 0.00 0.00 0.00
Exterior Lighting 46.08 0.00 0.00 0.00 0.00
Interior Equipment 1523.06 53.68 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 287.60 0.00 0.00 0.00 0.00
Pumps 6.22 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 265.30 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 68.41 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 2944.90 493.18 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
FLOOR 1 ANESTHESIA VAV BOX COMPONENT 0.049076 0.000000 1.00 0.049076 1.00 0.500000 0.002446 0.000014 0.049076 16.00 0.007000
FLOOR 1 BIO HAZ VAV BOX COMPONENT 0.007940 0.499290 0.200000 0.001588 1.00 0.500000 0.000763 0.000004 0.005623 16.00 0.007000
FLOOR 1 CAFE VAV BOX COMPONENT 0.295871 0.100492 0.200000 0.059174 0.478507 0.500000 0.003791 0.000023 0.059174 16.00 0.007000
FLOOR 1 CLEAN VAV BOX COMPONENT 0.050434 0.786000 1.00 0.050434 1.00 0.500000 0.002154 0.000007 0.050434 16.00 0.007000
FLOOR 1 CLEAN WORK VAV BOX COMPONENT 0.062243 0.834009 1.00 0.062243 1.00 0.500000 0.002030 0.000008 0.062243 16.00 0.007000
FLOOR 1 DICTATION VAV BOX COMPONENT 0.037005       1.00 0.500000 0.001581 0.000000 0.003701 16.00 0.007000
FLOOR 1 DRESSING ROOM VAV BOX COMPONENT 0.016056       1.00 0.500000 0.001920 0.000010 0.016056 16.00 0.007000
FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT 0.045333 0.153037 0.200000 0.009067 1.00 0.500000 0.002490 0.000003 0.009067 16.00 0.007000
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT 0.297971 0.021620 0.200000 0.059594 0.475135 0.500000 0.017623 0.000021 0.059594 16.00 0.007000
FLOOR 1 HUMID VAV BOX COMPONENT 0.017798       1.00 0.500000 0.001774 0.000000 0.001780 16.00 0.007000
FLOOR 1 IT HALL VAV BOX COMPONENT 0.024700 0.401251 0.200000 0.004940 1.00 0.500000 0.000950 0.000001 0.004940 16.00 0.007000
FLOOR 1 IT ROOM VAV BOX COMPONENT 0.026949       1.00 0.500000 0.001295 0.000000 0.002695 16.00 0.007000
FLOOR 1 LOBBY VAV BOX COMPONENT 0.273476 0.161011 0.200000 0.054695 0.517691 0.500000 0.002366 0.000043 0.067519 16.00 0.007000
FLOOR 1 LOBBY HALL VAV BOX COMPONENT 0.056540 0.300497 0.200000 0.011308 1.00 0.500000 0.001268 0.000001 0.011308 16.00 0.007000
FLOOR 1 LOBBY TOILET VAV BOX COMPONENT 0.036154 0.000000 1.00 0.036154 1.00 0.500000 0.003603 0.000012 0.036154 16.00 0.007000
FLOOR 1 LOCKER ROOM VAV BOX COMPONENT 0.235645 0.198276 0.200000 0.047129 0.600803 0.500000 0.001922 0.000006 0.047129 16.00 0.007000
FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT 0.085340 0.411449 0.200000 0.017068 1.00 0.500000 0.000926 0.000002 0.017068 16.00 0.007000
FLOOR 1 LOUNGE VAV BOX COMPONENT 0.130592 0.195151 0.200000 0.026118 1.00 0.500000 0.001952 0.000003 0.026118 16.00 0.007000
FLOOR 1 MED GAS VAV BOX COMPONENT 0.029248 0.135542 0.200000 0.005850 1.00 0.500000 0.002811 0.000018 0.029248 16.00 0.007000
FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT 0.143846 0.000000 0.200000 0.028769 0.984223 0.500000 0.004608 0.000004 0.028769 16.00 0.007000
FLOOR 1 MRI HALL VAV BOX COMPONENT 0.033157 0.313858 0.200000 0.006631 1.00 0.500000 0.001214 0.000001 0.006631 16.00 0.007000
FLOOR 1 MRI ROOM VAV BOX COMPONENT 0.367855 0.000000 0.200000 0.073571 0.384869 0.500000 0.004500 0.000010 0.073571 16.00 0.007000
FLOOR 1 MRI TOILET VAV BOX COMPONENT 0.009780 0.000000 1.00 0.009780 1.00 0.500000 0.000975 0.000006 0.009780 16.00 0.007000
FLOOR 1 NOURISHMENT VAV BOX COMPONENT 0.071489 0.180227 0.200000 0.014298 1.00 0.500000 0.002114 0.000002 0.014298 16.00 0.007000
FLOOR 1 NURSE HALL VAV BOX COMPONENT 0.103971 0.337719 0.200000 0.020794 1.00 0.500000 0.001128 0.000003 0.020794 16.00 0.007000
FLOOR 1 NURSE JANITOR VAV BOX COMPONENT 0.012509 0.305610 0.200000 0.002502 1.00 0.500000 0.001247 0.000000 0.002502 16.00 0.007000
FLOOR 1 NURSE STATION VAV BOX COMPONENT 0.097548 0.189411 0.200000 0.019510 1.00 0.500000 0.002011 0.000003 0.019510 16.00 0.007000
FLOOR 1 NURSE TOILET VAV BOX COMPONENT 0.015475 0.000000 1.00 0.015475 1.00 0.500000 0.001542 0.000002 0.015475 16.00 0.007000
FLOOR 1 OFFICE VAV BOX COMPONENT 0.110447       1.00 0.500000 0.001231 0.000001 0.011045 16.00 0.007000
FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT 0.723607       0.600000 0.500000 0.008466 0.000023 0.434164 16.00 0.007000
FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT 0.755069       0.600000 0.500000 0.008466 0.000000 0.453041 16.00 0.007000
FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT 0.748776 1.00 1.00 0.748776 1.00 0.500000 0.008466 0.000041 0.748776 16.00 0.007000
FLOOR 1 PACU VAV BOX COMPONENT 0.050967 1.00 1.00 0.050967 1.00 0.500000 0.002540 0.000007 0.050967 16.00 0.007000
FLOOR 1 PRE-OP HALL VAV BOX COMPONENT 0.100515 0.371867 0.200000 0.020103 1.00 0.500000 0.001025 0.000003 0.020103 16.00 0.007000
FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT 0.089192 1.00 1.00 0.089192 1.00 0.500000 0.002540 0.000012 0.089192 16.00 0.007000
FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT 0.159508 1.00 1.00 0.159508 1.00 0.500000 0.002540 0.000021 0.159508 16.00 0.007000
FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT 0.012429 0.000000 1.00 0.012429 1.00 0.500000 0.001239 0.000008 0.012429 16.00 0.007000
FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT 0.336241 1.00 1.00 0.336241 1.00 0.500000 0.006350 0.000053 0.336241 16.00 0.007000
FLOOR 1 RECEPTION VAV BOX COMPONENT 0.183994 0.195839 0.200000 0.036799 0.769463 0.500000 0.001945 0.000000 0.036799 16.00 0.007000
FLOOR 1 RECEPTION HALL VAV BOX COMPONENT 0.025850 0.350544 0.200000 0.005170 1.00 0.500000 0.001087 0.000001 0.005170 16.00 0.007000
FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT 0.271606 0.938255 0.870000 0.236297 0.870000 0.500000 0.002707 0.000066 0.236297 16.00 0.007000
FLOOR 1 SCHEDULING VAV BOX COMPONENT 0.030110       1.00 0.500000 0.001362 0.000003 0.005031 16.00 0.007000
FLOOR 1 SCRUB VAV BOX COMPONENT 0.017531 0.339205 0.200000 0.003506 1.00 0.500000 0.001123 0.000003 0.005376 16.00 0.007000
FLOOR 1 SOIL VAV BOX COMPONENT 0.050152 0.000000 1.00 0.050152 1.00 0.500000 0.002142 0.000007 0.050152 16.00 0.007000
FLOOR 1 SOIL HOLD VAV BOX COMPONENT 0.019575 0.000000 1.00 0.019575 1.00 0.500000 0.001881 0.000000 0.019575 16.00 0.007000
FLOOR 1 SOIL WORK VAV BOX COMPONENT 0.066618 0.000000 1.00 0.066618 1.00 0.500000 0.001992 0.000009 0.066618 16.00 0.007000
FLOOR 1 STEP DOWN VAV BOX COMPONENT 0.161448 0.876909 0.690000 0.111399 0.876914 0.500000 0.002896 0.000044 0.111399 16.00 0.007000
FLOOR 1 STERILE HALL VAV BOX COMPONENT 0.099998 0.436087 0.200000 0.020000 1.00 0.500000 0.000874 0.000010 0.020000 16.00 0.007000
FLOOR 1 STERILE STORAGE VAV BOX COMPONENT 0.060922 0.460157 0.200000 0.012184 1.00 0.500000 0.000828 0.000002 0.012184 16.00 0.007000
FLOOR 1 STORAGE VAV BOX COMPONENT 0.201576 0.323098 0.200000 0.040315 0.861595 0.500000 0.001179 0.000126 0.201576 16.00 0.007000
FLOOR 1 SUB-STERILE VAV BOX COMPONENT 0.044774 0.309892 0.200000 0.008955 1.00 0.500000 0.001229 0.000023 0.036564 16.00 0.007000
FLOOR 1 UTILITY HALL VAV BOX COMPONENT 0.059516 0.304502 0.200000 0.011903 1.00 0.500000 0.001251 0.000037 0.059516 16.00 0.007000
FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT 0.008735 0.340383 0.200000 0.001747 1.00 0.500000 0.001119 0.000002 0.002535 16.00 0.007000
FLOOR 1 UTILITY ROOM VAV BOX COMPONENT 0.061199 0.416429 0.200000 0.012240 1.00 0.500000 0.000915 0.000038 0.061199 16.00 0.007000
FLOOR 1 VESTIBULE VAV BOX COMPONENT 0.016515 0.308622 0.200000 0.003303 1.00 0.500000 0.001235 0.000010 0.016515 16.00 0.007000
FLOOR 2 CONFERENCE VAV BOX COMPONENT 0.221385 0.107442 0.333000 0.073721 0.639501 0.500000 0.003546        
FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT 0.019566 0.000000 1.00 0.019566 1.00 0.500000 0.001645        
FLOOR 2 DICTATION VAV BOX COMPONENT 0.025827 0.191870 0.163000 0.004210 1.00 0.500000 0.001986        
FLOOR 2 EXAM 1 VAV BOX COMPONENT 0.241227 0.704275 0.510000 0.123026 0.586900 0.500000 0.003606        
FLOOR 2 EXAM 2 VAV BOX COMPONENT 0.254836 1.00 1.00 0.254836 1.00 0.500000 0.002540        
FLOOR 2 EXAM 3 VAV BOX COMPONENT 0.339781 1.00 1.00 0.339781 1.00 0.500000 0.002540        
FLOOR 2 EXAM 4 VAV BOX COMPONENT 0.049462 0.801439 0.640000 0.031656 1.00 0.500000 0.003169        
FLOOR 2 EXAM 5 VAV BOX COMPONENT 0.207175 0.797256 0.690000 0.142951 0.690000 0.500000 0.003186        
FLOOR 2 EXAM 6 VAV BOX COMPONENT 0.106182 1.00 0.940000 0.099811 1.00 0.500000 0.002540        
FLOOR 2 EXAM 7 VAV BOX COMPONENT 0.373759 1.00 1.00 0.373759 1.00 0.500000 0.002540        
FLOOR 2 EXAM 8 VAV BOX COMPONENT 0.127418 1.00 0.930000 0.118499 1.00 0.500000 0.002540        
FLOOR 2 EXAM 9 VAV BOX COMPONENT 0.186879 1.00 1.00 0.186879 1.00 0.500000 0.002540        
FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT 0.055824 0.228263 0.137000 0.007648 1.00 0.500000 0.001669        
FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT 0.055403 0.229997 0.138000 0.007646 1.00 0.500000 0.001657        
FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT 0.053265 0.239229 0.144000 0.007670 1.00 0.500000 0.001593        
FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT 0.054571 0.256855 0.154000 0.008404 1.00 0.500000 0.001483        
FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT 0.057315 0.244560 0.147000 0.008425 1.00 0.500000 0.001558        
FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT 0.056895 0.246365 0.148000 0.008420 1.00 0.500000 0.001546        
FLOOR 2 JANITOR VAV BOX COMPONENT 0.034187 0.130456 0.157000 0.005367 1.00 0.500000 0.002921        
FLOOR 2 LOUNGE VAV BOX COMPONENT 0.038665 0.146473 0.198000 0.007656 1.00 0.500000 0.002601        
FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT 0.063149 0.168154 0.269000 0.016987 1.00 0.500000 0.002266        
FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT 0.075833 0.168034 0.269000 0.020399 1.00 0.500000 0.002267        
FLOOR 2 OFFICE VAV BOX COMPONENT 0.240662 0.164727 0.140000 0.033693 0.588277 0.500000 0.002313        
FLOOR 2 OFFICE HALL VAV BOX COMPONENT 0.132040 0.238046 0.143000 0.018882 1.00 0.500000 0.001601        
FLOOR 2 RECEPTION VAV BOX COMPONENT 0.463475 0.150298 0.316000 0.146458 0.400796 0.500000 0.002535        
FLOOR 2 RECEPTION HALL VAV BOX COMPONENT 0.171486 0.232828 0.140000 0.024008 0.825585 0.500000 0.001636        
FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT 0.035619 0.000000 1.00 0.035619 1.00 0.500000 0.001521        
FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT 0.093387 0.245609 0.209000 0.019518 1.00 0.500000 0.001551        
FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT 0.103259 0.234467 0.199000 0.020549 1.00 0.500000 0.001625        
FLOOR 2 STORAGE 1 VAV BOX COMPONENT 0.016236 0.244176 0.293000 0.004757 1.00 0.500000 0.001560        
FLOOR 2 STORAGE 2 VAV BOX COMPONENT 0.028011 0.303278 0.364000 0.010196 1.00 0.500000 0.001256        
FLOOR 2 STORAGE 3 VAV BOX COMPONENT 0.036313 0.280729 0.337000 0.012237 1.00 0.500000 0.001357        
FLOOR 2 UTILITY VAV BOX COMPONENT 0.053648 0.166266 0.200000 0.010730 1.00 0.500000 0.002292        
FLOOR 2 WORK VAV BOX COMPONENT 0.419804 0.284987 0.242000 0.101593 0.759965 0.500000 0.001337        
FLOOR 2 WORK HALL VAV BOX COMPONENT 0.231967 0.254521 0.153000 0.035491 0.678723 0.500000 0.001497        
FLOOR 2 WORK TOILET VAV BOX COMPONENT 0.018386 0.000000 1.00 0.018386 1.00 0.500000 0.001832        
FLOOR 2 X-RAY VAV BOX COMPONENT 0.843760 0.000000 0.227000 0.191533 0.300000 0.500000 0.005046        
FLOOR 3 DRESSING ROOM VAV BOX COMPONENT 0.017672 0.168244 0.143000 0.002527 1.00 0.500000 0.002265        
FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT 0.077035 0.340015 0.204000 0.015715 1.00 0.500000 0.001121        
FLOOR 3 HUMID VAV BOX COMPONENT 0.042060 0.181777 0.155000 0.006519 1.00 0.500000 0.002096        
FLOOR 3 JANITOR VAV BOX COMPONENT 0.022470 0.198485 0.388000 0.008718 1.00 0.500000 0.001920        
FLOOR 3 LOCKER VAV BOX COMPONENT 0.058070 0.146290 0.197000 0.011440 1.00 0.500000 0.002604        
FLOOR 3 LOUNGE VAV BOX COMPONENT 0.336133 0.159851 0.216000 0.072605 0.426270 0.500000 0.002383        
FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT 0.052635 0.000000 1.00 0.052635 1.00 0.500000 0.001475        
FLOOR 3 MECHANICAL VAV BOX COMPONENT 0.321366 0.077100 0.010000 0.003214 0.440546 0.500000 0.004942        
FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT 0.092755 0.228964 0.137000 0.012707 1.00 0.500000 0.001664        
FLOOR 3 OFFICE VAV BOX COMPONENT 0.738613 0.290984 0.247000 0.182437 0.775959 0.500000 0.001309        
FLOOR 3 OFFICE HALL VAV BOX COMPONENT 0.212195 0.278238 0.167000 0.035437 0.741967 0.500000 0.001369        
FLOOR 3 OFFICE TOILET VAV BOX COMPONENT 0.015025 0.000000 1.00 0.015025 1.00 0.500000 0.001497        
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT 0.720313 0.851703 0.690000 0.497016 0.690000 0.500000 0.002982        
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT 0.279375 1.00 0.830000 0.231882 0.830000 0.500000 0.002540        
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT 0.024455 0.000000 1.00 0.024455 1.00 0.500000 0.001567        
FLOOR 3 STORAGE 1 VAV BOX COMPONENT 0.024527 0.311725 1.00 0.024527 1.00 0.500000 0.001222        
FLOOR 3 STORAGE 2 VAV BOX COMPONENT 0.022129 0.268725 0.322000 0.007125 1.00 0.500000 0.001418        
FLOOR 3 TREATMENT VAV BOX COMPONENT 0.224633 1.00 0.810000 0.181953 0.810000 0.500000 0.002540        
FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT 0.675477 0.237693 0.285000 0.192511 0.633849 0.500000 0.001603        
FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT 0.342417 0.238167 0.286000 0.097931 0.635113 0.500000 0.001600        
FLOOR 3 UTILITY VAV BOX COMPONENT 0.036307 0.421166 0.505000 0.018335 1.00 0.500000 0.000905        
FLOOR 3 WORK VAV BOX COMPONENT 0.292081 0.139121 0.118000 0.034466 0.484715 0.500000 0.002739        
NE STAIR VAV BOX COMPONENT 0.161175 0.073790 0.077000 0.012410 0.878403 0.500000 0.005163        
NW ELEVATOR VAV BOX COMPONENT 0.105667 0.093794 0.076000 0.008031 1.00 0.500000 0.004062        
NW STAIR VAV BOX COMPONENT 0.165150 0.082301 0.086000 0.014203 0.857258 0.500000 0.004629        
SW STAIR VAV BOX COMPONENT 0.080610 0.084307 0.061000 0.004917 1.00 0.500000 0.004519        
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL 656.24 0.000014 12.57
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL 160.43 0.000004 3.45
FLOOR 1 CAFE VAV BOX REHEAT COIL 1070.71 0.000023 21.15
FLOOR 1 CLEAN VAV BOX REHEAT COIL 302.66 0.000007 5.33
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL 373.52 0.000008 6.58
FLOOR 1 DICTATION VAV BOX REHEAT COIL 22.21 0.000000 0.391231
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL 456.74 0.000010 9.82
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL 131.68 0.000003 2.54
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL 936.97 0.000021 18.21
FLOOR 1 HUMID VAV BOX REHEAT COIL 10.68 0.000000 0.188163
FLOOR 1 IT HALL VAV BOX REHEAT COIL 29.65 0.000001 0.522275
FLOOR 1 IT ROOM VAV BOX REHEAT COIL 0.000000 0.000000 1.00
FLOOR 1 LOBBY VAV BOX REHEAT COIL 1943.58 0.000043 41.93
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL 67.86 0.000001 1.20
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL 533.79 0.000012 10.31
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL 282.82 0.000006 4.98
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL 102.42 0.000002 1.80
FLOOR 1 LOUNGE VAV BOX REHEAT COIL 156.74 0.000003 2.76
FLOOR 1 MED GAS VAV BOX REHEAT COIL 831.02 0.000018 17.87
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL 172.64 0.000004 3.04
FLOOR 1 MRI HALL VAV BOX REHEAT COIL 44.47 0.000001 0.789714
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL 441.50 0.000010 7.78
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL 279.51 0.000006 6.02
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL 85.80 0.000002 1.51
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL 135.32 0.000003 2.40
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL 15.01 0.000000 0.264492
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL 117.08 0.000003 2.06
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL 92.87 0.000002 1.64
FLOOR 1 OFFICE VAV BOX REHEAT COIL 66.28 0.000001 1.17
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL 1072.82 0.000023 18.19
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL 0.000000 0.000000 1.00
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL 1850.23 0.000041 31.38
FLOOR 1 PACU VAV BOX REHEAT COIL 305.85 0.000007 5.39
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL 120.64 0.000003 2.13
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL 535.25 0.000012 9.43
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL 957.21 0.000021 16.86
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL 354.49 0.000008 7.63
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL 2409.63 0.000053 43.01
FLOOR 1 RECEPTION VAV BOX REHEAT COIL 0.000000 0.000000 1.00
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL 31.02 0.000001 0.546580
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL 3021.08 0.000066 57.59
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL 143.48 0.000003 3.09
FLOOR 1 SCRUB VAV BOX REHEAT COIL 153.17 0.000003 3.30
FLOOR 1 SOIL VAV BOX REHEAT COIL 300.96 0.000007 5.30
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL 0.000000 0.000000 1.00
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL 399.78 0.000009 7.04
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL 2002.41 0.000044 39.51
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL 436.85 0.000010 8.88
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL 73.12 0.000002 1.29
FLOOR 1 STORAGE VAV BOX REHEAT COIL 5754.65 0.000126 123.88
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL 1044.78 0.000023 22.50
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL 1697.90 0.000037 36.54
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL 72.07 0.000002 1.55
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL 1750.46 0.000038 37.70
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL 471.10 0.000010 10.14
AHU-1_HEATC 92954.51 0.002035 1468.34
AHU-1_EXTRAWATERHEATC 92954.51 0.002035 1468.34
AHU-2_HEATC 115747.63 0.002534 1832.71
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W]
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL 2088.67  
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL 552.56  
FLOOR 2 DICTATION VAV BOX REHEAT COIL 118.89  
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL 3474.26  
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL 7196.58  
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL 9595.44  
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL 893.97  
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL 4036.94  
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL 2818.66  
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL 10554.99  
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL 3346.41  
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL 5277.49  
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL 513.24  
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL 323.56  
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL 335.30  
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL 237.33  
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL 237.93  
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL 283.92  
FLOOR 2 JANITOR VAV BOX REHEAT COIL 661.07  
FLOOR 2 LOUNGE VAV BOX REHEAT COIL 216.20  
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL 479.72  
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL 576.08  
FLOOR 2 OFFICE VAV BOX REHEAT COIL 2682.35  
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL 833.19  
FLOOR 2 RECEPTION VAV BOX REHEAT COIL 4135.99  
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL 677.99  
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL 1005.89  
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL 551.19  
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL 580.30  
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL 134.34  
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL 287.93  
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL 345.59  
FLOOR 2 UTILITY VAV BOX REHEAT COIL 766.16  
FLOOR 2 WORK VAV BOX REHEAT COIL 2868.98  
FLOOR 2 WORK HALL VAV BOX REHEAT COIL 1002.27  
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL 519.23  
FLOOR 2 X-RAY VAV BOX REHEAT COIL 5408.92  
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL 181.82  
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL 1443.69  
FLOOR 3 HUMID VAV BOX REHEAT COIL 394.63  
FLOOR 3 JANITOR VAV BOX REHEAT COIL 634.55  
FLOOR 3 LOCKER VAV BOX REHEAT COIL 403.57  
FLOOR 3 LOUNGE VAV BOX REHEAT COIL 2050.36  
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL 1486.41  
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL 493.80  
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL 1531.87  
FLOOR 3 OFFICE VAV BOX REHEAT COIL 8748.53  
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL 3136.63  
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL 424.31  
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL 14035.79  
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL 6548.36  
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL 690.61  
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL 692.63  
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL 435.45  
FLOOR 3 TREATMENT VAV BOX REHEAT COIL 5138.36  
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL 7691.37  
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL 5047.39  
FLOOR 3 UTILITY VAV BOX REHEAT COIL 892.29  
FLOOR 3 WORK VAV BOX REHEAT COIL 2982.53  
NE STAIR VAV BOX REHEAT COIL 4551.58  
NW ELEVATOR VAV BOX REHEAT COIL 2984.04  
NW STAIR VAV BOX REHEAT COIL 4663.85  
SW STAIR VAV BOX REHEAT COIL 2276.44  
AHU-1_EXTRAELECHEATC 92954.51 10000000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
AHU-1 5.30 4.27 7.10 5.30 7.10 7.10 1.00 0.746282 7.10
AHU-2 6.49 4.32 10.73 4.32 9.20 9.20 1.00 0.469380 9.20
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AHU-1_OA_CONTROLLER 7.10 2.07
AHU-2_OA_CONTROLLER 9.20  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:TwoSpeed

Design Size High Speed Rated Air Flow Rate [m3/s] Design Size High Speed Gross Rated Total Cooling Capacity [W] Design Size High Speed Rated Sensible Heat Ratio Design Size Low Speed Rated Air Flow Rate [m3/s] Design Size Low Speed Gross Rated Total Cooling Capacity [W] Design Size Low Speed Gross Rated Sensible Heat Ratio
AHU-1_COOLC DXCOIL 7.10 176331.53 0.698083 2.37 58771.30 0.698083
AHU-2_COOLC DXCOIL 9.20 220453.16 0.709065 3.07 73477.04 0.709065
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
AHU-1_FAN 7.10
AHU-2_FAN 9.20
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
AHU-1 HUMIDIFIER 0.000045 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s]
AHU-1_HEATC_CONTROLLER 0.002035
AHU-1_EXTRAWATERHEATC_CONTROLLER 0.002035
AHU-2_HEATC_CONTROLLER 0.002534
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000063 0.007580
HEATSYS1 0.002208 0.264946
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000063 8.07
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000063
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
HEATSYS1 PUMP 0.002208 558.50
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 100840.74 100840.74 0.002208
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
5F762C 84418A | 1535AC | B40F89 | 3330D8 | 1775A6 | 38B339 |
84FB73 8E5BB9 | AF0124 |
7F5C82 E7B55F |
C732B0 8E5BB9 | 5507DC |
FE5A3C FB3814 |
F629C1 8E5BB9 | AF0124 |
577FC1 88E360 |
FLOOR 1 MED GAS ROOF 9EC269 | B316F7 | 9621FD | 42CEE1 | F209CC | 155BD6 | C5EA55 | 5E657E | 9C3A6A | C52EE0 | F7D24D | FC22D1 | 68A2D7 | CE3FEF | 5ADC59 | 88E360 | 2E2D0C | AF0124 |
C114C1 8E5BB9 | AF0124 |
ADB8D0 8E5BB9 | AF0124 |
E326E4 E7B55F |
1D96D7 E7B55F |
84418A 5F762C | A5A6A3 | EA6DC8 | 4ABC66 | 8D1BC4 | 1DEE26 | FB3814 | AF0124 | 850EA7 |
1535AC 5F762C | A5A6A3 | EA6DC8 | 4ABC66 | 8D1BC4 | 1DEE26 | FB3814 | AF0124 | 850EA7 |
6D2616 8E5BB9 | AF0124 |
A5A6A3 84418A | 1535AC | B40F89 | 3330D8 | 1775A6 | 38B339 |
EA6DC8 84418A | 1535AC | B40F89 | 3330D8 | 1775A6 | 38B339 |
B40F89 5F762C | A5A6A3 | EA6DC8 | 4ABC66 | 8D1BC4 | 1DEE26 | FB3814 | AF0124 | 850EA7 |
8E5BB9 84FB73 | C732B0 | F629C1 | C114C1 | ADB8D0 | 6D2616 | 9621FD | 42CEE1 | 155BD6 | C5EA55 | 5E657E | 9C3A6A | C52EE0 | F7D24D | FC22D1 | 5ADC59 | 2E2D0C | AF0124 |
FLOOR 1 STORGE ROOF 9EC269 | B316F7 | 9621FD | 42CEE1 | F209CC | 155BD6 | C5EA55 | 5E657E | 9C3A6A | C52EE0 | F7D24D | FC22D1 | 68A2D7 | CE3FEF | 5ADC59 | 88E360 | 2E2D0C | AF0124 |
61E610 E7B55F |
529072 88E360 |
FLOOR 1 UTILITY HALL ROOF 9EC269 | B316F7 | 9621FD | 42CEE1 | F209CC | 155BD6 | C5EA55 | 5E657E | 9C3A6A | C52EE0 | F7D24D | FC22D1 | 68A2D7 | CE3FEF | 5ADC59 | 88E360 | 2E2D0C | AF0124 |
D95F04 E7B55F |
3330D8 5F762C | A5A6A3 | EA6DC8 | 4ABC66 | 8D1BC4 | 1DEE26 | FB3814 | AF0124 | 850EA7 |
208CCF E7B55F |
1775A6 4ABC66 | 8D1BC4 | 1DEE26 | FB3814 | AF0124 | 850EA7 |
B4E619 E7B55F |
9EC269 AF0124 |
B316F7 AF0124 |
9621FD AF0124 |
42CEE1 AF0124 |
F209CC AF0124 |
155BD6 AF0124 |
C5EA55 AF0124 |
5E657E 5507DC |
4B1439 E7B55F |
4ABC66 1775A6 | 38B339 |
5B04CF FB3814 |
8D1BC4 1775A6 | 38B339 |
4B55FA E7B55F |
9C3A6A AF0124 |
C52EE0 5507DC |
1C33AD FB3814 |
F7D24D 5507DC |
FC22D1 5507DC |
68A2D7 AF0124 |
CE3FEF AF0124 |
CE618F E7B55F |
5ADC59 AF0124 |
D4F411 FB3814 |
D22917 E7B55F |
38B339 1DEE26 | FB3814 | AF0124 | 850EA7 |
BE5F2F FB3814 |
1DEE26 38B339 |
C86329 E7B55F |
88E360 577FC1 | 529072 | AF0124 |
E7B55F 7F5C82 | E326E4 | 1D96D7 | 61E610 | D95F04 | 208CCF | B4E619 | 4B1439 | 4B55FA | CE618F | D22917 | C86329 |
FB3814 FE5A3C | 84418A | 1535AC | B40F89 | 3330D8 | 1775A6 | 5B04CF | 1C33AD | D4F411 | 38B339 | BE5F2F | 270BCE |
5507DC C732B0 | 5E657E | C52EE0 | F7D24D | FC22D1 |
2E2D0C 8E5BB9 |
AF0124 84FB73 | F629C1 | C114C1 | ADB8D0 | 84418A | 1535AC | 6D2616 | B40F89 | 8E5BB9 | 3330D8 | 1775A6 | 9EC269 | B316F7 | 9621FD | 42CEE1 | F209CC | 155BD6 | C5EA55 | 9C3A6A | 68A2D7 | CE3FEF | 5ADC59 | 38B339 | 88E360 |
850EA7 84418A | 1535AC | B40F89 | 3330D8 | 1775A6 | 38B339 |
270BCE FB3814 |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
481E71 78F987 |
5F762C D8037E |
84FB73 4A8120 |
E02487 BA05F7 |
FE5A3C AAE778 | F67E1F |
F629C1 3AAD8B | 8128A9 |
E85BB5 7EB6E7 |
C114C1 D18914 |
879583 9B1541 | CF850A |
E326E4 A6BA23 | D10D28 | D4B39B |
1D96D7 591336 | 38B811 | C044D6 |
6D2616 1D94BE | 18748E |
A5A6A3 137A56 |
28B002 8D508E | B2D381 | 1DA13A | 44E54A | D2D3BC | C528DA | EFD3F9 |
EA6DC8 757D10 |
B40F89 E33BAE |
997723 24167A | 2C0938 | 62B5AF |
CEC7BD 8600DD |
8E5BB9 71E924 |
859BC1 A1ED60 | E8D997 | 88E1FC | 3C44F9 | 49526E | 865AE8 |
61E610 F83F33 |
529072 5E66D1 |
D95F04 E14DAE | B1F5EE |
3330D8 84A1D5 |
208CCF F52F3D |
AEF992 80885D |
54D065 FEEF06 |
1775A6 2BE8DE | 513E2A | BA5CD9 |
97F00A 1AD478 |
A497E9 27F0AC |
88A75F 724114 |
B4E619 D538C4 | 5635BC |
9EC269 831C1D |
B316F7 9BB95F | C0778D |
9621FD 7D2D69 | 2EF63B |
42CEE1 C417C0 |
4B1439 EB042B | 4C1F71 | D23C8B | B4E4BE |
4ABC66 EEF55D | E55A57 |
5B04CF 93D018 |
4B55FA DD9F5D |
9C3A6A 15B02B | 820282 |
68A2D7 9BA05A | C639E8 |
CE3FEF A2790A |
CE618F 79FCEE | EDE617 |
5ADC59 C61F0D | 7248C5 | 29FA28 | F0B23F | EEC10E | 944FCE | C41399 |
D22917 95BA33 | F27282 |
C1BC97 3DB407 | 3DADE2 | DF3E2C | 5031C8 |
8DA7DB C087D0 | D2CA75 | B0FB49 |
38B339 FE9BC9 | 9DF7DE | D0BE44 |
BE5F2F 6B5226 |
1DEE26 8F59F7 | 44F571 |
C86329 6BD844 | 86D536 | BAF71D | 3833A2 |
DFC6F0 2111A1 |
88E360 9CB8E5 | 9BC521 | 142781 | E4A528 |
FB3814 24BAF7 |
FCD12D 19E57D |
5507DC EDE769 |
2E2D0C E74902 | 93BBC3 | 1C9872 |
850EA7 C635A6 |
270BCE F402E9 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Version

Version ID
1 9.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 5.40 -2.00 -14.60 -16.90 -11.50 -6.20 4.00 13.40 18.00 19.70 17.90 12.30


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 International Falls Intl Ap MN USA TMY3 WMO#=727470 48.57 -93.40 -6.00 359.00 97086 1.1539


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 3.29 36.60 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OutPatientHealthCare 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance

Adjust Zone Mixing

Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}
Infiltration Zones {MixingSourceZonesOnly
AllZones}
1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 118 1395 117


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 FLOOR 1 ANESTHESIA 0.0 39.32 0.00 0.00 40.69 1.83 1.52 1 1 1 39.32 42.06 0.00 3.66 0.00 3.05 3.05 30.58 TARP DOE-2 10.03 8.36 6.13 2.23 7 1 0 Yes
2 FLOOR 1 BIO HAZ 0.0 39.32 25.91 0.00 41.00 27.13 1.52 1 1 1 39.93 42.06 25.91 28.35 0.00 3.05 3.05 15.86 TARP DOE-2 5.20 0.00 0.00 0.00 6 0 0 Yes
3 FLOOR 1 CAFE 0.0 0.00 19.20 0.00 8.84 12.34 1.52 1 1 1 5.79 11.89 9.14 15.54 0.00 3.05 3.05 118.93 TARP DOE-2 39.02 18.58 9.66 8.92 7 1 0 Yes
4 FLOOR 1 CLEAN 0.0 29.26 8.84 0.00 30.63 10.97 1.52 1 1 1 29.26 32.00 8.84 13.11 0.00 3.05 3.05 35.68 TARP DOE-2 11.71 0.00 0.00 0.00 9 0 0 Yes
5 FLOOR 1 CLEAN WORK 0.0 42.06 9.75 0.00 39.78 11.43 1.52 1 1 1 37.49 42.06 9.75 13.11 0.00 3.05 3.05 46.72 TARP DOE-2 15.33 0.00 0.00 0.00 8 0 0 Yes
6 FLOOR 1 DICTATION 0.0 32.00 8.84 0.00 33.38 10.97 1.52 1 1 1 32.00 34.75 8.84 13.11 0.00 3.05 3.05 35.68 TARP DOE-2 11.71 0.00 0.00 0.00 8 0 0 Yes
7 FLOOR 1 DRESSING ROOM 0.0 15.54 28.35 0.00 14.17 27.58 1.52 1 1 1 12.80 15.54 26.82 28.35 0.00 3.05 3.05 12.74 TARP DOE-2 4.18 8.36 6.04 2.32 6 1 0 Yes
8 FLOOR 1 ELECTRICAL ROOM 0.0 50.60 18.59 0.00 48.46 19.66 1.52 1 1 1 46.33 50.60 18.59 20.73 0.00 3.05 3.05 27.75 TARP DOE-2 9.10 6.50 6.50 0.00 6 0 0 Yes
9 FLOOR 1 ELEVATOR PUMP ROOM 0.0 3.96 28.35 0.00 1.98 27.28 1.52 1 1 1 0.00 3.96 26.21 28.35 0.00 3.05 3.05 25.77 TARP DOE-2 8.45 18.58 16.63 0.00 8 1 0 Yes
10 FLOOR 1 HUMID 0.0 32.00 14.94 0.00 30.63 14.02 1.52 1 1 1 29.26 32.00 13.11 14.94 0.00 3.05 3.05 15.29 TARP DOE-2 5.02 0.00 0.00 0.00 6 0 0 Yes
11 FLOOR 1 IT HALL 0.0 33.53 25.91 0.00 37.80 25.15 1.52 1 1 1 33.53 42.06 24.38 25.91 0.00 3.05 3.05 39.64 TARP DOE-2 13.01 0.00 0.00 0.00 10 0 0 Yes
12 FLOOR 1 IT ROOM 0.0 37.19 28.35 0.00 35.66 27.13 1.52 1 1 1 33.53 37.80 25.91 28.35 0.00 3.05 3.05 31.71 TARP DOE-2 10.41 0.00 0.00 0.00 6 0 0 Yes
13 FLOOR 1 LOBBY 0.0 2.13 24.38 0.00 4.17 20.93 1.52 1 1 1 2.13 6.40 11.58 28.35 0.00 3.05 3.05 176.13 TARP DOE-2 57.79 20.44 9.57 8.92 17 2 0 Yes
14 FLOOR 1 LOBBY HALL 0.0 11.89 19.20 0.00 8.84 17.37 1.52 1 1 1 5.79 11.89 15.54 19.20 0.00 3.05 3.05 67.96 TARP DOE-2 22.30 0.00 0.00 0.00 8 0 0 Yes
15 FLOOR 1 LOBBY TOILET 0.0 0.00 26.21 0.00 1.37 25.30 1.52 1 1 1 0.00 2.74 24.38 26.21 0.00 3.05 3.05 15.29 TARP DOE-2 5.02 5.57 5.57 0.00 7 0 0 Yes
16 FLOOR 1 LOCKER ROOM 0.0 29.87 28.35 0.00 26.52 23.77 1.52 1 1 1 23.16 29.87 19.20 28.35 0.00 3.05 3.05 186.89 TARP DOE-2 61.32 20.44 14.86 5.57 11 2 0 Yes
17 FLOOR 1 LOCKER ROOM HALL 0.0 23.16 19.20 0.00 32.61 17.98 1.52 1 1 1 23.16 42.06 16.76 19.20 0.00 3.05 3.05 140.45 TARP DOE-2 46.08 0.00 0.00 0.00 17 0 0 Yes
18 FLOOR 1 LOUNGE 0.0 29.87 19.20 0.00 31.70 23.77 1.52 1 1 1 29.87 33.53 19.20 28.35 0.00 3.05 3.05 101.94 TARP DOE-2 33.45 0.00 0.00 0.00 9 0 0 Yes
19 FLOOR 1 MED GAS 0.0 44.50 33.22 0.00 43.28 34.29 1.52 1 1 1 42.06 44.50 33.22 35.36 0.00 3.05 3.05 15.86 TARP DOE-2 5.20 13.94 11.98 0.00 6 1 0 Yes
20 FLOOR 1 MRI CONTROL ROOM 0.0 12.80 28.35 0.00 9.60 27.13 1.52 1 1 1 6.40 12.80 25.91 28.35 0.00 3.05 3.05 47.57 TARP DOE-2 15.61 4.65 2.69 0.00 9 1 0 Yes
21 FLOOR 1 MRI HALL 0.0 11.89 25.91 0.00 14.50 25.26 1.52 1 1 1 11.89 17.37 23.77 26.82 0.00 3.05 3.05 41.63 TARP DOE-2 13.66 0.00 0.00 0.00 11 0 0 Yes
22 FLOOR 1 MRI ROOM 0.0 6.71 25.91 0.00 8.84 22.56 1.52 1 1 1 5.79 11.89 19.20 25.91 0.00 3.05 3.05 124.59 TARP DOE-2 40.88 0.00 0.00 0.00 8 0 0 Yes
23 FLOOR 1 MRI TOILET 0.0 17.37 28.35 0.00 16.46 26.97 1.52 1 1 1 15.54 17.37 25.60 28.35 0.00 3.05 3.05 15.29 TARP DOE-2 5.02 5.57 5.57 0.00 7 0 0 Yes
24 FLOOR 1 NOURISHMENT 0.0 27.13 16.76 0.00 28.19 12.80 1.52 1 1 1 27.13 29.26 8.84 16.76 0.00 3.05 3.05 51.54 TARP DOE-2 16.91 0.00 0.00 0.00 12 0 0 Yes
25 FLOOR 1 NURSE HALL 0.0 39.32 3.66 0.00 32.61 4.88 1.52 1 1 1 23.16 42.06 3.66 6.10 0.00 3.05 3.05 140.45 TARP DOE-2 46.08 0.00 0.00 0.00 16 0 0 Yes
26 FLOOR 1 NURSE JANITOR 0.0 29.26 16.76 0.00 30.63 15.85 1.52 1 1 1 29.26 32.00 14.94 16.76 0.00 3.05 3.05 15.29 TARP DOE-2 5.02 0.00 0.00 0.00 7 0 0 Yes
27 FLOOR 1 NURSE STATION 0.0 32.00 8.84 0.00 27.58 7.47 1.52 1 1 1 23.16 32.00 6.10 8.84 0.00 3.05 3.05 73.91 TARP DOE-2 24.25 0.00 0.00 0.00 11 0 0 Yes
28 FLOOR 1 NURSE TOILET 0.0 37.49 8.84 0.00 36.58 7.47 1.52 1 1 1 35.66 37.49 6.10 8.84 0.00 3.05 3.05 15.29 TARP DOE-2 5.02 0.00 0.00 0.00 6 0 0 Yes
29 FLOOR 1 OFFICE 0.0 14.63 15.85 0.00 17.53 20.27 1.52 1 1 1 14.33 20.73 16.76 23.77 0.00 3.05 3.05 136.77 TARP DOE-2 44.87 0.00 0.00 0.00 10 0 0 Yes
30 FLOOR 1 OPERATING ROOM 1 0.0 44.81 0.00 0.00 47.55 3.51 1.52 1 1 1 44.50 50.60 0.00 7.01 0.00 3.05 3.05 130.26 TARP DOE-2 42.74 39.95 29.08 8.92 9 5 0 Yes
31 FLOOR 1 OPERATING ROOM 2 0.0 50.60 11.28 0.00 47.55 14.94 1.52 1 1 1 44.50 50.60 11.28 18.59 0.00 3.05 3.05 135.92 TARP DOE-2 44.59 22.30 15.61 6.69 10 3 0 Yes
32 FLOOR 1 OPERATING ROOM 3 0.0 33.53 19.20 0.00 37.80 21.79 1.52 1 1 1 33.53 42.06 19.20 24.38 0.00 3.05 3.05 134.79 TARP DOE-2 44.22 0.00 0.00 0.00 11 0 0 Yes
33 FLOOR 1 PACU 0.0 35.66 8.84 0.00 33.83 7.47 1.52 1 1 1 32.00 35.66 6.10 8.84 0.00 3.05 3.05 30.58 TARP DOE-2 10.03 0.00 0.00 0.00 7 0 0 Yes
34 FLOOR 1 PRE-OP HALL 0.0 20.73 23.77 0.00 21.95 13.72 1.52 1 1 1 20.73 23.16 3.66 23.77 0.00 3.05 3.05 149.51 TARP DOE-2 49.05 0.00 0.00 0.00 20 0 0 Yes
35 FLOOR 1 PRE-OP ROOM 1 0.0 17.98 13.41 0.00 19.35 11.13 1.52 1 1 1 17.98 20.73 7.92 14.33 0.00 3.05 3.05 53.52 TARP DOE-2 17.56 3.72 3.72 0.00 9 0 0 Yes
36 FLOOR 1 PRE-OP ROOM 2 0.0 24.38 8.84 0.00 25.15 12.80 1.52 1 1 1 23.16 27.13 8.84 16.76 0.00 3.05 3.05 95.71 TARP DOE-2 31.40 0.00 0.00 0.00 11 0 0 Yes
37 FLOOR 1 PRE-OP TOILET 0.0 17.98 5.49 0.00 19.35 4.57 1.52 1 1 1 17.98 20.73 3.66 5.49 0.00 3.05 3.05 15.29 TARP DOE-2 5.02 5.57 5.57 0.00 6 0 0 Yes
38 FLOOR 1 PROCEDURE ROOM 0.0 22.86 28.35 0.00 20.27 26.06 1.52 1 1 1 17.37 23.16 23.77 28.35 0.00 3.05 3.05 80.70 TARP DOE-2 26.48 17.65 12.08 5.57 10 2 0 Yes
39 FLOOR 1 RECEPTION 0.0 9.75 9.14 0.00 13.70 16.13 1.52 1 1 1 11.89 15.85 9.14 23.77 0.00 3.05 3.05 144.13 TARP DOE-2 47.29 12.08 8.73 3.34 13 1 0 Yes
40 FLOOR 1 RECEPTION HALL 0.0 20.73 14.33 0.00 18.29 15.54 1.52 1 1 1 15.85 20.73 14.33 16.76 0.00 3.05 3.05 36.25 TARP DOE-2 11.89 0.00 0.00 0.00 9 0 0 Yes
41 FLOOR 1 RECOVERY ROOM 0.0 20.42 0.00 0.00 32.46 1.83 1.52 1 1 1 25.60 39.32 0.00 3.66 0.00 3.05 3.05 152.91 TARP DOE-2 50.17 41.81 27.03 8.92 9 7 0 Yes
42 FLOOR 1 SCHEDULING 0.0 15.85 9.14 0.00 16.92 11.73 1.52 1 1 1 15.85 17.98 9.14 14.33 0.00 3.05 3.05 33.70 TARP DOE-2 11.06 6.50 5.76 0.74 7 1 0 Yes
43 FLOOR 1 SCRUB 0.0 44.50 11.28 0.00 45.42 9.14 1.52 1 1 1 44.50 46.33 7.01 11.28 0.00 3.05 3.05 23.79 TARP DOE-2 7.80 0.00 0.00 0.00 6 0 0 Yes
44 FLOOR 1 SOIL 0.0 34.75 13.11 0.00 36.12 10.97 1.52 1 1 1 34.75 37.49 8.84 13.11 0.00 3.05 3.05 35.68 TARP DOE-2 11.71 0.00 0.00 0.00 10 0 0 Yes
45 FLOOR 1 SOIL HOLD 0.0 37.19 25.91 0.00 38.86 27.13 1.52 1 1 1 37.80 39.93 25.91 28.35 0.00 3.05 3.05 15.86 TARP DOE-2 5.20 0.00 0.00 0.00 7 0 0 Yes
46 FLOOR 1 SOIL WORK 0.0 42.06 6.10 0.00 39.78 7.92 1.52 1 1 1 37.49 42.06 6.10 9.75 0.00 3.05 3.05 50.97 TARP DOE-2 16.72 0.00 0.00 0.00 10 0 0 Yes
47 FLOOR 1 STEP DOWN 0.0 20.42 0.00 0.00 21.79 1.83 1.52 1 1 1 17.98 25.60 0.00 3.66 0.00 3.05 3.05 84.95 TARP DOE-2 27.87 34.37 25.73 6.69 10 4 0 Yes
48 FLOOR 1 STERILE HALL 0.0 42.06 0.00 0.00 43.28 11.73 1.52 1 1 1 42.06 44.50 0.00 23.47 0.00 3.05 3.05 174.43 TARP DOE-2 57.23 7.43 5.20 2.23 23 1 0 Yes
49 FLOOR 1 STERILE STORAGE 0.0 32.00 13.11 0.00 37.03 14.94 1.52 1 1 1 32.00 42.06 13.11 16.76 0.00 3.05 3.05 112.13 TARP DOE-2 36.79 0.00 0.00 0.00 11 0 0 Yes
50 FLOOR 1 STORAGE 0.0 41.45 35.36 0.00 35.97 31.85 1.52 1 1 1 29.87 42.06 28.35 35.36 0.00 3.05 3.05 260.52 TARP DOE-2 85.47 58.53 41.34 8.36 10 7 0 Yes
51 FLOOR 1 SUB-STERILE 0.0 50.60 7.01 0.00 48.46 9.14 1.52 1 1 1 46.33 50.60 7.01 11.28 0.00 3.05 3.05 55.50 TARP DOE-2 18.21 13.01 10.03 2.97 6 1 0 Yes
52 FLOOR 1 UTILITY HALL 0.0 44.50 28.96 0.00 43.28 28.35 1.52 1 1 1 42.06 44.50 23.47 33.22 0.00 3.05 3.05 72.49 TARP DOE-2 23.78 14.86 7.43 0.00 13 1 0 Yes
53 FLOOR 1 UTILITY JANITOR 0.0 44.50 20.73 0.00 45.42 19.66 1.52 1 1 1 44.50 46.33 18.59 20.73 0.00 3.05 3.05 11.89 TARP DOE-2 3.90 0.00 0.00 0.00 6 0 0 Yes
54 FLOOR 1 UTILITY ROOM 0.0 50.60 20.73 0.00 47.55 23.47 1.52 1 1 1 44.50 50.60 20.73 26.21 0.00 3.05 3.05 101.94 TARP DOE-2 33.45 16.72 12.54 2.23 9 2 0 Yes
55 FLOOR 1 VESTIBULE 0.0 17.98 7.92 0.00 19.35 6.71 1.52 1 1 1 17.98 20.73 5.49 7.92 0.00 3.05 3.05 20.39 TARP DOE-2 6.69 7.43 5.48 0.00 6 1 0 Yes
56 FLOOR 2 CONFERENCE 0.0 50.60 0.00 3.05 46.33 1.83 4.57 1 1 1 42.06 50.60 0.00 3.66 3.05 6.10 3.05 95.14 TARP DOE-2 31.22 37.16 28.24 8.92 9 2 0 Yes
57 FLOOR 2 CONFERENCE TOILET 0.0 44.50 6.10 3.05 43.28 4.88 4.57 1 1 1 42.06 44.50 3.66 6.10 3.05 6.10 3.05 18.12 TARP DOE-2 5.95 0.00 0.00 0.00 6 0 0 Yes
58 FLOOR 2 DICTATION 0.0 42.06 9.14 3.05 41.00 7.62 4.57 1 1 1 39.93 42.06 6.10 9.14 3.05 6.10 3.05 19.82 TARP DOE-2 6.50 0.00 0.00 0.00 6 0 0 Yes
59 FLOOR 2 EXAM 1 0.0 17.98 0.00 3.05 19.81 4.57 4.57 1 1 1 17.98 21.64 0.00 9.14 3.05 6.10 3.05 101.94 TARP DOE-2 33.45 39.02 30.10 8.92 10 4 0 Yes
60 FLOOR 2 EXAM 2 0.0 23.47 0.00 3.05 26.21 4.57 4.57 1 1 1 23.47 28.96 0.00 9.14 3.05 6.10 3.05 152.91 TARP DOE-2 50.17 16.72 13.01 3.72 11 1 0 Yes
61 FLOOR 2 EXAM 3 0.0 30.78 0.00 3.05 34.44 4.57 4.57 1 1 1 30.78 38.10 0.00 9.14 3.05 6.10 3.05 203.88 TARP DOE-2 66.89 22.30 16.35 5.95 16 1 0 Yes
62 FLOOR 2 EXAM 4 0.0 39.93 0.00 3.05 41.00 1.83 4.57 1 1 1 39.93 42.06 0.00 3.66 3.05 6.10 3.05 23.79 TARP DOE-2 7.80 6.50 4.27 2.23 6 1 0 Yes
63 FLOOR 2 EXAM 5 0.0 50.60 18.59 3.05 48.46 22.40 4.57 1 1 1 46.33 50.60 18.59 26.21 3.05 6.10 3.05 99.11 TARP DOE-2 32.52 23.23 17.28 5.95 7 2 0 Yes
64 FLOOR 2 EXAM 6 0.0 44.50 28.35 3.05 42.21 26.06 4.57 1 1 1 39.93 44.50 23.77 28.35 3.05 6.10 3.05 63.71 TARP DOE-2 20.90 13.94 9.75 4.18 10 1 0 Yes
65 FLOOR 2 EXAM 7 0.0 38.10 28.35 3.05 34.44 23.32 4.57 1 1 1 30.78 38.10 18.29 28.35 3.05 6.10 3.05 224.27 TARP DOE-2 73.58 22.30 16.72 5.57 15 2 0 Yes
66 FLOOR 2 EXAM 8 0.0 28.96 28.35 3.05 26.21 26.06 4.57 1 1 1 23.47 28.96 23.77 28.35 3.05 6.10 3.05 76.46 TARP DOE-2 25.08 16.72 11.15 5.57 6 2 0 Yes
67 FLOOR 2 EXAM 9 0.0 21.64 28.35 3.05 19.81 23.32 4.57 1 1 1 17.98 21.64 18.29 28.35 3.05 6.10 3.05 112.13 TARP DOE-2 36.79 11.15 8.36 2.79 8 1 0 Yes
68 FLOOR 2 EXAM HALL 1 0.0 21.64 0.00 3.05 22.56 4.57 4.57 1 1 1 21.64 23.47 0.00 9.14 3.05 6.10 3.05 50.97 TARP DOE-2 16.72 5.57 5.57 0.00 10 0 0 Yes
69 FLOOR 2 EXAM HALL 2 0.0 28.96 0.00 3.05 29.87 4.57 4.57 1 1 1 28.96 30.78 0.00 9.14 3.05 6.10 3.05 50.97 TARP DOE-2 16.72 5.57 5.57 0.00 10 0 0 Yes
70 FLOOR 2 EXAM HALL 3 0.0 38.10 0.00 3.05 39.01 4.57 4.57 1 1 1 38.10 39.93 0.00 9.14 3.05 6.10 3.05 50.97 TARP DOE-2 16.72 5.57 5.57 0.00 12 0 0 Yes
71 FLOOR 2 EXAM HALL 4 0.0 39.93 28.35 3.05 39.01 23.32 4.57 1 1 1 38.10 39.93 18.29 28.35 3.05 6.10 3.05 56.07 TARP DOE-2 18.39 5.57 5.57 0.00 11 0 0 Yes
72 FLOOR 2 EXAM HALL 5 0.0 30.78 28.35 3.05 29.87 23.32 4.57 1 1 1 28.96 30.78 18.29 28.35 3.05 6.10 3.05 56.07 TARP DOE-2 18.39 5.57 5.57 0.00 10 0 0 Yes
73 FLOOR 2 EXAM HALL 6 0.0 23.47 28.35 3.05 22.56 23.32 4.57 1 1 1 21.64 23.47 18.29 28.35 3.05 6.10 3.05 56.07 TARP DOE-2 18.39 5.57 5.57 0.00 11 0 0 Yes
74 FLOOR 2 JANITOR 0.0 0.00 28.35 3.05 1.37 27.28 4.57 1 1 1 0.00 2.74 26.21 28.35 3.05 6.10 3.05 17.84 TARP DOE-2 5.85 14.86 14.86 0.00 6 0 0 Yes
75 FLOOR 2 LOUNGE 0.0 44.50 9.14 3.05 43.28 7.62 4.57 1 1 1 42.06 44.50 6.10 9.14 3.05 6.10 3.05 22.65 TARP DOE-2 7.43 0.00 0.00 0.00 6 0 0 Yes
76 FLOOR 2 NURSE STATION 1 0.0 39.01 21.34 3.05 42.21 19.81 4.57 1 1 1 39.93 44.50 18.29 21.34 3.05 6.10 3.05 42.48 TARP DOE-2 13.94 0.00 0.00 0.00 8 0 0 Yes
77 FLOOR 2 NURSE STATION 2 0.0 23.47 21.34 3.05 26.21 19.81 4.57 1 1 1 23.47 28.96 18.29 21.34 3.05 6.10 3.05 50.97 TARP DOE-2 16.72 0.00 0.00 0.00 7 0 0 Yes
78 FLOOR 2 OFFICE 0.0 50.60 3.66 3.05 48.46 9.75 4.57 1 1 1 46.33 50.60 3.66 15.85 3.05 6.10 3.05 158.57 TARP DOE-2 52.03 37.16 28.24 8.92 9 4 0 Yes
79 FLOOR 2 OFFICE HALL 0.0 46.33 3.66 3.05 45.42 14.94 4.57 1 1 1 44.50 46.33 3.66 26.21 3.05 6.10 3.05 125.73 TARP DOE-2 41.25 0.00 0.00 0.00 21 0 0 Yes
80 FLOOR 2 RECEPTION 0.0 2.13 16.46 3.05 8.91 12.84 4.57 1 1 1 2.13 15.85 9.14 16.46 3.05 6.10 3.05 278.64 TARP DOE-2 91.42 45.52 28.80 16.72 12 3 0 Yes
81 FLOOR 2 RECEPTION HALL 0.0 17.98 9.14 3.05 30.18 10.06 4.57 1 1 1 15.85 44.50 9.14 10.97 3.05 6.10 3.05 159.71 TARP DOE-2 52.40 6.50 6.50 0.00 30 0 0 Yes
82 FLOOR 2 RECEPTION TOILET 0.0 17.98 10.97 3.05 16.92 13.72 4.57 1 1 1 15.85 17.98 10.97 16.46 3.05 6.10 3.05 35.68 TARP DOE-2 11.71 0.00 0.00 0.00 7 0 0 Yes
83 FLOOR 2 SCHEDULING 1 0.0 44.50 16.46 3.05 41.76 13.72 4.57 1 1 1 39.01 44.50 10.97 16.46 3.05 6.10 3.05 91.75 TARP DOE-2 30.10 0.00 0.00 0.00 9 0 0 Yes
84 FLOOR 2 SCHEDULING 2 0.0 23.77 16.46 3.05 20.88 13.72 4.57 1 1 1 17.98 23.77 10.97 16.46 3.05 6.10 3.05 96.84 TARP DOE-2 31.77 0.00 0.00 0.00 9 0 0 Yes
85 FLOOR 2 STORAGE 1 0.0 42.06 3.66 3.05 41.00 4.88 4.57 1 1 1 39.93 42.06 3.66 6.10 3.05 6.10 3.05 15.86 TARP DOE-2 5.20 0.00 0.00 0.00 6 0 0 Yes
86 FLOOR 2 STORAGE 2 0.0 39.01 23.77 3.05 42.21 22.56 4.57 1 1 1 39.93 44.50 21.34 23.77 3.05 6.10 3.05 33.98 TARP DOE-2 11.15 0.00 0.00 0.00 8 0 0 Yes
87 FLOOR 2 STORAGE 3 0.0 23.47 21.34 3.05 26.21 22.56 4.57 1 1 1 23.47 28.96 21.34 23.77 3.05 6.10 3.05 40.78 TARP DOE-2 13.38 0.00 0.00 0.00 6 0 0 Yes
88 FLOOR 2 UTILITY 0.0 50.60 18.59 3.05 48.46 17.22 4.57 1 1 1 46.33 50.60 15.85 18.59 3.05 6.10 3.05 35.68 TARP DOE-2 11.71 8.36 6.13 2.23 6 1 0 Yes
89 FLOOR 2 WORK 0.0 17.98 28.35 3.05 10.11 23.44 4.57 1 1 1 2.13 17.98 18.29 28.35 3.05 6.10 3.05 478.55 TARP DOE-2 157.01 24.15 18.58 5.57 22 2 0 Yes
90 FLOOR 2 WORK HALL 0.0 44.50 16.46 3.05 23.33 17.37 4.57 1 1 1 2.13 44.50 16.46 18.29 3.05 6.10 3.05 236.16 TARP DOE-2 77.48 5.57 5.57 0.00 28 0 0 Yes
91 FLOOR 2 WORK TOILET 0.0 0.00 26.21 3.05 1.37 25.30 4.57 1 1 1 0.00 2.74 24.38 26.21 3.05 6.10 3.05 15.29 TARP DOE-2 5.02 5.57 5.57 0.00 7 0 0 Yes
92 FLOOR 2 X-RAY 0.0 39.01 16.46 3.05 31.39 13.72 4.57 1 1 1 23.77 39.01 10.97 16.46 3.05 6.10 3.05 254.85 TARP DOE-2 83.61 0.00 0.00 0.00 18 0 0 Yes
93 FLOOR 3 DRESSING ROOM 0.0 39.01 10.97 6.10 37.95 11.89 7.62 1 1 1 36.88 39.01 10.97 12.80 6.10 9.14 3.05 11.89 TARP DOE-2 3.90 0.00 0.00 0.00 6 0 0 Yes
94 FLOOR 3 ELEVATOR HALL 0.0 5.79 28.35 6.10 3.83 23.43 7.62 1 1 1 2.13 5.79 18.29 28.35 6.10 9.14 3.05 104.77 TARP DOE-2 34.37 3.72 3.72 0.00 10 0 0 Yes
95 FLOOR 3 HUMID 0.0 35.05 16.46 6.10 35.97 13.72 7.62 1 1 1 35.05 36.88 10.97 16.46 6.10 9.14 3.05 30.58 TARP DOE-2 10.03 0.00 0.00 0.00 7 0 0 Yes
96 FLOOR 3 JANITOR 0.0 0.00 28.35 6.10 1.37 27.28 7.62 1 1 1 0.00 2.74 26.21 28.35 6.10 9.14 3.05 17.84 TARP DOE-2 5.85 14.86 14.86 0.00 6 0 0 Yes
97 FLOOR 3 LOCKER 0.0 37.49 20.42 6.10 35.66 21.95 7.62 1 1 1 33.83 37.49 20.42 23.47 6.10 9.14 3.05 33.98 TARP DOE-2 11.15 0.00 0.00 0.00 6 0 0 Yes
98 FLOOR 3 LOUNGE 0.0 37.49 28.35 6.10 41.00 23.32 7.62 1 1 1 37.49 44.50 18.29 28.35 6.10 9.14 3.05 214.92 TARP DOE-2 70.51 21.37 15.79 5.57 13 2 0 Yes
99 FLOOR 3 LOUNGE TOILET 0.0 33.83 23.47 6.10 35.66 25.91 7.62 1 1 1 33.83 37.49 23.47 28.35 6.10 9.14 3.05 54.37 TARP DOE-2 17.84 11.15 6.97 4.18 6 1 0 Yes
100 FLOOR 3 MECHANICAL 0.0 50.60 18.59 6.10 48.46 22.40 7.62 1 1 1 46.33 50.60 18.59 26.21 6.10 9.14 3.05 99.11 TARP DOE-2 32.52 23.23 17.28 5.95 6 2 0 Yes
101 FLOOR 3 MECHANICAL HALL 0.0 46.33 3.66 6.10 45.42 18.59 7.62 1 1 1 44.50 46.33 10.97 26.21 6.10 9.14 3.05 84.95 TARP DOE-2 27.87 0.00 0.00 0.00 10 0 0 Yes
102 FLOOR 3 OFFICE 0.0 33.83 28.35 6.10 19.81 23.32 7.62 1 1 1 5.79 33.83 18.29 28.35 6.10 9.14 3.05 859.70 TARP DOE-2 282.05 68.75 49.24 19.51 16 7 0 Yes
103 FLOOR 3 OFFICE HALL 0.0 2.13 16.46 6.10 23.32 17.37 7.62 1 1 1 2.13 44.50 16.46 18.29 6.10 9.14 3.05 236.16 TARP DOE-2 77.48 5.57 5.57 0.00 14 0 0 Yes
104 FLOOR 3 OFFICE TOILET 0.0 0.00 24.38 6.10 1.37 25.30 7.62 1 1 1 0.00 2.74 24.38 26.21 6.10 9.14 3.05 15.29 TARP DOE-2 5.02 5.57 5.57 0.00 7 0 0 Yes
105 FLOOR 3 PHYSICAL THERAPY 1 0.0 50.60 0.00 6.10 40.69 3.05 7.62 1 1 1 30.78 50.60 0.00 6.10 6.10 9.14 3.05 368.12 TARP DOE-2 120.77 78.97 49.98 28.99 15 6 0 Yes
106 FLOOR 3 PHYSICAL THERAPY 2 0.0 35.05 10.97 6.10 40.69 8.53 7.62 1 1 1 35.05 46.33 6.10 10.97 6.10 9.14 3.05 167.64 TARP DOE-2 55.00 0.00 0.00 0.00 14 0 0 Yes
107 FLOOR 3 PHYSICAL THERAPY TOILET 0.0 39.01 10.97 6.10 37.95 14.63 7.62 1 1 1 36.88 39.01 12.80 16.46 6.10 9.14 3.05 23.79 TARP DOE-2 7.80 0.00 0.00 0.00 6 0 0 Yes
108 FLOOR 3 STORAGE 1 0.0 39.01 10.97 6.10 41.76 11.89 7.62 1 1 1 39.01 44.50 10.97 12.80 6.10 9.14 3.05 30.58 TARP DOE-2 10.03 0.00 0.00 0.00 6 0 0 Yes
109 FLOOR 3 STORAGE 2 0.0 37.49 18.29 6.10 35.66 19.35 7.62 1 1 1 33.83 37.49 18.29 20.42 6.10 9.14 3.05 23.79 TARP DOE-2 7.80 0.00 0.00 0.00 6 0 0 Yes
110 FLOOR 3 TREATMENT 0.0 30.78 0.00 6.10 32.92 11.28 7.62 1 1 1 30.78 35.05 6.10 16.46 6.10 9.14 3.05 134.79 TARP DOE-2 44.22 0.00 0.00 0.00 9 0 0 Yes
111 FLOOR 3 UNDEVELOPED 1 0.0 17.98 0.00 6.10 24.38 8.23 7.62 1 1 1 17.98 30.78 0.00 16.46 6.10 9.14 3.05 642.23 TARP DOE-2 210.70 66.89 41.25 25.64 14 6 0 Yes
112 FLOOR 3 UNDEVELOPED 2 0.0 2.13 11.58 6.10 9.46 12.65 7.62 1 1 1 2.13 17.98 9.14 16.46 6.10 9.14 3.05 326.21 TARP DOE-2 107.02 52.03 38.65 13.38 10 3 0 Yes
113 FLOOR 3 UTILITY 0.0 39.01 16.46 6.10 41.76 14.63 7.62 1 1 1 39.01 44.50 12.80 16.46 6.10 9.14 3.05 61.16 TARP DOE-2 20.07 0.00 0.00 0.00 6 0 0 Yes
114 FLOOR 3 WORK 0.0 50.60 18.59 6.10 48.46 12.34 7.62 1 1 1 46.33 50.60 6.10 18.59 6.10 9.14 3.05 162.54 TARP DOE-2 53.33 38.09 29.17 8.92 8 4 0 Yes
115 NE STAIR 0.0 51.82 26.21 0.00 48.16 27.28 4.57 1 1 1 44.50 51.82 26.21 28.35 0.00 9.14 9.14 142.72 TARP DOE-2 15.61 97.55 81.62 12.02 13 5 0 Yes
116 NW ELEVATOR 0.0 0.00 24.38 0.00 1.07 21.34 4.57 1 1 1 0.00 2.13 18.29 24.38 0.00 9.14 9.14 118.93 TARP DOE-2 13.01 75.25 71.35 0.00 10 2 0 Yes
117 NW STAIR 0.0 12.80 28.35 0.00 7.62 29.57 4.57 1 1 1 3.96 11.28 28.35 30.78 0.00 9.14 9.14 163.11 TARP DOE-2 17.84 111.48 96.43 11.15 10 4 0 Yes
118 SW STAIR 0.0 0.91 11.58 0.00 3.96 10.36 4.57 1 1 1 2.13 5.79 9.14 11.58 0.00 9.14 9.14 81.55 TARP DOE-2 8.92 55.74 52.68 1.11 10 2 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 FLOOR 1 ANESTHESIA 10.03 2.2 4.645 0.215 15.069 21.530 0.000 0.000 0.000 0.000 36.599 No
2 FLOOR 1 BIO HAZ 5.20 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
3 FLOOR 1 CAFE 39.02 42.0 0.929 1.076 4.306 10.760 0.000 0.000 0.000 0.000 15.066 No
4 FLOOR 1 CLEAN 11.71 2.5 4.645 0.215 15.069 21.530 0.000 0.000 0.000 0.000 36.599 No
5 FLOOR 1 CLEAN WORK 15.33 3.3 4.645 0.215 15.069 21.530 0.000 0.000 0.000 0.000 36.599 No
6 FLOOR 1 DICTATION 11.71 0.6 18.579 5.382E-002 7.965 11.840 0.000 0.000 0.000 0.000 19.805 No
7 FLOOR 1 DRESSING ROOM 4.18 0.2 18.579 5.382E-002 7.965 11.840 0.000 0.000 0.000 0.000 19.805 No
8 FLOOR 1 ELECTRICAL ROOM 9.10 0.0 N/A 0.000 15.069 53.820 0.000 0.000 0.000 0.000 68.889 No
9 FLOOR 1 ELEVATOR PUMP ROOM 8.45 0.0 N/A 0.000 15.069 5719.402 0.000 0.000 0.000 0.000 5734.472 No
10 FLOOR 1 HUMID 5.02 0.3 18.579 5.382E-002 7.965 11.840 0.000 0.000 0.000 0.000 19.805 No
11 FLOOR 1 IT HALL 13.01 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
12 FLOOR 1 IT ROOM 10.41 0.6 18.579 5.382E-002 7.965 11.840 0.000 0.000 0.000 0.000 19.805 No
13 FLOOR 1 LOBBY 57.79 6.2 9.289 0.108 9.042 11.840 0.000 0.000 0.000 0.000 20.882 No
14 FLOOR 1 LOBBY HALL 22.30 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
15 FLOOR 1 LOBBY TOILET 5.02 0.0 N/A 0.000 6.781 4.310 0.000 0.000 0.000 0.000 11.091 No
16 FLOOR 1 LOCKER ROOM 61.32 9.9 6.193 0.161 6.351 32.290 0.000 0.000 0.000 0.000 38.641 No
17 FLOOR 1 LOCKER ROOM HALL 46.08 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
18 FLOOR 1 LOUNGE 33.45 5.4 6.193 0.161 6.351 32.290 0.000 0.000 0.000 0.000 38.641 No
19 FLOOR 1 MED GAS 5.20 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
20 FLOOR 1 MRI CONTROL ROOM 15.61 3.4 4.645 0.215 10.118 107.640 0.000 0.000 0.000 0.000 117.758 No
21 FLOOR 1 MRI HALL 13.66 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
22 FLOOR 1 MRI ROOM 40.88 8.8 4.645 0.215 10.118 107.640 0.000 0.000 0.000 0.000 117.758 No
23 FLOOR 1 MRI TOILET 5.02 0.0 N/A 0.000 6.781 4.310 0.000 0.000 0.000 0.000 11.091 No
24 FLOOR 1 NOURISHMENT 16.91 3.6 4.645 0.215 12.594 21.530 0.000 0.000 0.000 0.000 34.124 No
25 FLOOR 1 NURSE HALL 46.08 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
26 FLOOR 1 NURSE JANITOR 5.02 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
27 FLOOR 1 NURSE STATION 24.25 5.2 4.645 0.215 12.594 21.530 0.000 0.000 0.000 0.000 34.124 No
28 FLOOR 1 NURSE TOILET 5.02 0.0 N/A 0.000 6.781 4.310 0.000 0.000 0.000 0.000 11.091 No
29 FLOOR 1 OFFICE 44.87 2.4 18.579 5.382E-002 7.965 11.840 0.000 0.000 0.000 0.000 19.805 No
30 FLOOR 1 OPERATING ROOM 1 42.74 9.2 4.645 0.215 24.326 43.060 75.300 0.000 0.000 0.000 142.686 No
31 FLOOR 1 OPERATING ROOM 2 44.59 9.6 4.645 0.215 24.326 43.060 75.300 0.000 0.000 0.000 142.686 No
32 FLOOR 1 OPERATING ROOM 3 44.22 9.5 4.645 0.215 24.326 43.060 75.300 0.000 0.000 0.000 142.686 No
33 FLOOR 1 PACU 10.03 2.2 4.645 0.215 13.455 32.290 0.000 0.000 0.000 0.000 45.745 No
34 FLOOR 1 PRE-OP HALL 49.05 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
35 FLOOR 1 PRE-OP ROOM 1 17.56 1.9 9.289 0.108 7.319 21.530 0.000 0.000 0.000 0.000 28.849 No
36 FLOOR 1 PRE-OP ROOM 2 31.40 3.4 9.289 0.108 7.319 21.530 0.000 0.000 0.000 0.000 28.849 No
37 FLOOR 1 PRE-OP TOILET 5.02 0.0 N/A 0.000 6.781 4.310 0.000 0.000 0.000 0.000 11.091 No
38 FLOOR 1 PROCEDURE ROOM 26.48 5.7 4.645 0.215 15.069 32.290 0.000 0.000 0.000 0.000 47.359 No
39 FLOOR 1 RECEPTION 47.29 15.3 3.096 0.323 9.042 11.840 0.000 0.000 0.000 0.000 20.882 No
40 FLOOR 1 RECEPTION HALL 11.89 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
41 FLOOR 1 RECOVERY ROOM 50.17 10.8 4.645 0.215 13.455 32.290 0.000 0.000 0.000 0.000 45.745 No
42 FLOOR 1 SCHEDULING 11.06 0.6 18.579 5.382E-002 7.965 11.840 0.000 0.000 0.000 0.000 19.805 No
43 FLOOR 1 SCRUB 7.80 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
44 FLOOR 1 SOIL 11.71 2.5 4.645 0.215 15.069 21.530 0.000 0.000 0.000 0.000 36.599 No
45 FLOOR 1 SOIL HOLD 5.20 1.1 4.645 0.215 15.069 21.530 0.000 0.000 0.000 0.000 36.599 No
46 FLOOR 1 SOIL WORK 16.72 3.6 4.645 0.215 15.069 21.530 0.000 0.000 0.000 0.000 36.599 No
47 FLOOR 1 STEP DOWN 27.87 6.0 4.645 0.215 13.455 32.290 0.000 0.000 0.000 0.000 45.745 No
48 FLOOR 1 STERILE HALL 57.23 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
49 FLOOR 1 STERILE STORAGE 36.79 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
50 FLOOR 1 STORAGE 85.47 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
51 FLOOR 1 SUB-STERILE 18.21 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
52 FLOOR 1 UTILITY HALL 23.78 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
53 FLOOR 1 UTILITY JANITOR 3.90 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
54 FLOOR 1 UTILITY ROOM 33.45 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
55 FLOOR 1 VESTIBULE 6.69 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
56 FLOOR 2 CONFERENCE 31.22 16.8 1.858 0.538 10.441 10.760 0.000 0.000 0.000 0.000 21.201 No
57 FLOOR 2 CONFERENCE TOILET 5.95 0.0 N/A 0.000 6.781 4.310 0.000 0.000 0.000 0.000 11.091 No
58 FLOOR 2 DICTATION 6.50 0.4 18.579 5.382E-002 7.965 11.840 0.000 0.000 0.000 0.000 19.805 No
59 FLOOR 2 EXAM 1 33.45 7.2 4.645 0.215 15.069 11.840 0.000 0.000 0.000 0.000 26.909 No
60 FLOOR 2 EXAM 2 50.17 10.8 4.645 0.215 15.069 11.840 0.000 0.000 0.000 0.000 26.909 No
61 FLOOR 2 EXAM 3 66.89 14.4 4.645 0.215 15.069 11.840 0.000 0.000 0.000 0.000 26.909 No
62 FLOOR 2 EXAM 4 7.80 1.7 4.645 0.215 15.069 11.840 0.000 0.000 0.000 0.000 26.909 No
63 FLOOR 2 EXAM 5 32.52 7.0 4.645 0.215 15.069 11.840 0.000 0.000 0.000 0.000 26.909 No
64 FLOOR 2 EXAM 6 20.90 4.5 4.645 0.215 15.069 11.840 0.000 0.000 0.000 0.000 26.909 No
65 FLOOR 2 EXAM 7 73.58 15.8 4.645 0.215 15.069 11.840 0.000 0.000 0.000 0.000 26.909 No
66 FLOOR 2 EXAM 8 25.08 5.4 4.645 0.215 15.069 11.840 0.000 0.000 0.000 0.000 26.909 No
67 FLOOR 2 EXAM 9 36.79 7.9 4.645 0.215 15.069 11.840 0.000 0.000 0.000 0.000 26.909 No
68 FLOOR 2 EXAM HALL 1 16.72 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
69 FLOOR 2 EXAM HALL 2 16.72 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
70 FLOOR 2 EXAM HALL 3 16.72 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
71 FLOOR 2 EXAM HALL 4 18.39 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
72 FLOOR 2 EXAM HALL 5 18.39 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
73 FLOOR 2 EXAM HALL 6 18.39 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
74 FLOOR 2 JANITOR 5.85 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
75 FLOOR 2 LOUNGE 7.43 1.2 6.193 0.161 6.351 32.290 0.000 0.000 0.000 0.000 38.641 No
76 FLOOR 2 NURSE STATION 1 13.94 3.0 4.645 0.215 12.594 21.530 0.000 0.000 0.000 0.000 34.124 No
77 FLOOR 2 NURSE STATION 2 16.72 3.6 4.645 0.215 12.594 21.530 0.000 0.000 0.000 0.000 34.124 No
78 FLOOR 2 OFFICE 52.03 2.8 18.579 5.382E-002 7.965 11.840 0.000 0.000 0.000 0.000 19.805 No
79 FLOOR 2 OFFICE HALL 41.25 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
80 FLOOR 2 RECEPTION 91.42 29.5 3.096 0.323 9.042 11.840 0.000 0.000 0.000 0.000 20.882 No
81 FLOOR 2 RECEPTION HALL 52.40 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
82 FLOOR 2 RECEPTION TOILET 11.71 0.0 N/A 0.000 6.781 4.310 0.000 0.000 0.000 0.000 11.091 No
83 FLOOR 2 SCHEDULING 1 30.10 1.6 18.579 5.382E-002 7.965 11.840 0.000 0.000 0.000 0.000 19.805 No
84 FLOOR 2 SCHEDULING 2 31.77 1.7 18.579 5.382E-002 7.965 11.840 0.000 0.000 0.000 0.000 19.805 No
85 FLOOR 2 STORAGE 1 5.20 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
86 FLOOR 2 STORAGE 2 11.15 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
87 FLOOR 2 STORAGE 3 13.38 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
88 FLOOR 2 UTILITY 11.71 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
89 FLOOR 2 WORK 157.01 8.5 18.579 5.382E-002 7.965 9.780 0.000 0.000 0.000 0.000 17.746 No
90 FLOOR 2 WORK HALL 77.48 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
91 FLOOR 2 WORK TOILET 5.02 0.0 N/A 0.000 6.781 4.310 0.000 0.000 0.000 0.000 11.091 No
92 FLOOR 2 X-RAY 83.61 18.0 4.645 0.215 10.118 107.640 0.000 0.000 0.000 0.000 117.758 No
93 FLOOR 3 DRESSING ROOM 3.90 0.2 18.579 5.382E-002 7.965 11.840 0.000 0.000 0.000 0.000 19.805 No
94 FLOOR 3 ELEVATOR HALL 34.37 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
95 FLOOR 3 HUMID 10.03 0.5 18.579 5.382E-002 7.965 11.840 0.000 0.000 0.000 0.000 19.805 No
96 FLOOR 3 JANITOR 5.85 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
97 FLOOR 3 LOCKER 11.15 1.8 6.193 0.161 6.351 32.290 0.000 0.000 0.000 0.000 38.641 No
98 FLOOR 3 LOUNGE 70.51 11.4 6.193 0.161 6.351 32.290 0.000 0.000 0.000 0.000 38.641 No
99 FLOOR 3 LOUNGE TOILET 17.84 0.0 N/A 0.000 6.781 4.310 0.000 0.000 0.000 0.000 11.091 No
100 FLOOR 3 MECHANICAL 32.52 0.0 N/A 0.000 15.069 53.820 0.000 0.000 0.000 0.000 68.889 No
101 FLOOR 3 MECHANICAL HALL 27.87 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
102 FLOOR 3 OFFICE 282.05 15.2 18.579 5.382E-002 7.965 11.840 0.000 0.000 0.000 0.000 19.805 No
103 FLOOR 3 OFFICE HALL 77.48 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
104 FLOOR 3 OFFICE TOILET 5.02 0.0 N/A 0.000 6.781 4.310 0.000 0.000 0.000 0.000 11.091 No
105 FLOOR 3 PHYSICAL THERAPY 1 120.77 26.0 4.645 0.215 9.795 16.150 0.000 0.000 0.000 0.000 25.945 No
106 FLOOR 3 PHYSICAL THERAPY 2 55.00 11.8 4.645 0.215 9.795 16.150 0.000 0.000 0.000 0.000 25.945 No
107 FLOOR 3 PHYSICAL THERAPY TOILET 7.80 0.0 N/A 0.000 6.781 4.310 0.000 0.000 0.000 0.000 11.091 No
108 FLOOR 3 STORAGE 1 10.03 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
109 FLOOR 3 STORAGE 2 7.80 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
110 FLOOR 3 TREATMENT 44.22 9.5 4.645 0.215 15.069 11.840 0.000 0.000 0.000 0.000 26.909 No
111 FLOOR 3 UNDEVELOPED 1 210.70 0.0 N/A 0.000 4.090 11.840 0.000 0.000 0.000 0.000 15.930 No
112 FLOOR 3 UNDEVELOPED 2 107.02 0.0 N/A 0.000 4.090 11.840 0.000 0.000 0.000 0.000 15.930 No
113 FLOOR 3 UTILITY 20.07 0.0 N/A 0.000 4.090 1.080 0.000 0.000 0.000 0.000 5.170 No
114 FLOOR 3 WORK 53.33 2.9 18.579 5.382E-002 7.965 11.840 0.000 0.000 0.000 0.000 19.805 No
115 NE STAIR 15.61 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
116 NW ELEVATOR 13.01 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
117 NW STAIR 17.84 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No
118 SW STAIR 8.92 0.0 N/A 0.000 5.296 4.310 0.000 0.000 0.000 0.000 9.606 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation
1 FLOOR 1 ANESTHESIA PEOPLE BLDG_OCC_SCH FLOOR 1 ANESTHESIA 10.03 2.2 2.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
2 FLOOR 1 CAFE PEOPLE BLDG_OCC_SCH FLOOR 1 CAFE 39.02 42.0 42.0 1.076 0.929 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 38 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
3 FLOOR 1 CLEAN PEOPLE BLDG_OCC_SCH FLOOR 1 CLEAN 11.71 2.5 2.5 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
4 FLOOR 1 CLEAN WORK PEOPLE BLDG_OCC_SCH FLOOR 1 CLEAN WORK 15.33 3.3 3.3 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
5 FLOOR 1 DICTATION PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 1 DICTATION 11.71 0.6 0.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
6 FLOOR 1 DRESSING ROOM PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 1 DRESSING ROOM 4.18 0.2 0.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
7 FLOOR 1 HUMID PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 1 HUMID 5.02 0.3 0.3 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
8 FLOOR 1 IT ROOM PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 1 IT ROOM 10.41 0.6 0.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
9 FLOOR 1 LOBBY PEOPLE BLDG_OCC_SCH FLOOR 1 LOBBY 57.79 6.2 6.2 0.108 9.289 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
10 FLOOR 1 LOCKER ROOM PEOPLE BLDG_OCC_SCH FLOOR 1 LOCKER ROOM 61.32 9.9 9.9 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 9 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
11 FLOOR 1 LOUNGE PEOPLE BLDG_OCC_SCH FLOOR 1 LOUNGE 33.45 5.4 5.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 5 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
12 FLOOR 1 MRI CONTROL ROOM PEOPLE BLDG_OCC_SCH FLOOR 1 MRI CONTROL ROOM 15.61 3.4 3.4 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
13 FLOOR 1 MRI ROOM PEOPLE BLDG_OCC_SCH FLOOR 1 MRI ROOM 40.88 8.8 8.8 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
14 FLOOR 1 NOURISHMENT PEOPLE BLDG_OCC_SCH FLOOR 1 NOURISHMENT 16.91 3.6 3.6 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
15 FLOOR 1 NURSE STATION PEOPLE BLDG_OCC_SCH FLOOR 1 NURSE STATION 24.25 5.2 5.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 5 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
16 FLOOR 1 OFFICE PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 1 OFFICE 44.87 2.4 2.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
17 FLOOR 1 OPERATING ROOM 1 PEOPLE BLDG_OCC_SCH FLOOR 1 OPERATING ROOM 1 42.74 9.2 9.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
18 FLOOR 1 OPERATING ROOM 2 PEOPLE BLDG_OCC_SCH FLOOR 1 OPERATING ROOM 2 44.59 9.6 9.6 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 9 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
19 FLOOR 1 OPERATING ROOM 3 PEOPLE BLDG_OCC_SCH FLOOR 1 OPERATING ROOM 3 44.22 9.5 9.5 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 9 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
20 FLOOR 1 PACU PEOPLE BLDG_OCC_SCH FLOOR 1 PACU 10.03 2.2 2.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
21 FLOOR 1 PRE-OP ROOM 1 PEOPLE BLDG_OCC_SCH FLOOR 1 PRE-OP ROOM 1 17.56 1.9 1.9 0.108 9.289 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
22 FLOOR 1 PRE-OP ROOM 2 PEOPLE BLDG_OCC_SCH FLOOR 1 PRE-OP ROOM 2 31.40 3.4 3.4 0.108 9.289 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
23 FLOOR 1 PROCEDURE ROOM PEOPLE BLDG_OCC_SCH FLOOR 1 PROCEDURE ROOM 26.48 5.7 5.7 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 5 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
24 FLOOR 1 RECEPTION PEOPLE BLDG_OCC_SCH FLOOR 1 RECEPTION 47.29 15.3 15.3 0.323 3.096 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 14 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
25 FLOOR 1 RECOVERY ROOM PEOPLE BLDG_OCC_SCH FLOOR 1 RECOVERY ROOM 50.17 10.8 10.8 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 10 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
26 FLOOR 1 SCHEDULING PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 1 SCHEDULING 11.06 0.6 0.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
27 FLOOR 1 SOIL PEOPLE BLDG_OCC_SCH FLOOR 1 SOIL 11.71 2.5 2.5 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
28 FLOOR 1 SOIL HOLD PEOPLE BLDG_OCC_SCH FLOOR 1 SOIL HOLD 5.20 1.1 1.1 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
29 FLOOR 1 SOIL WORK PEOPLE BLDG_OCC_SCH FLOOR 1 SOIL WORK 16.72 3.6 3.6 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
30 FLOOR 1 STEP DOWN PEOPLE BLDG_OCC_SCH FLOOR 1 STEP DOWN 27.87 6.0 6.0 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 5 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
31 FLOOR 2 CONFERENCE PEOPLE MEETINGROOM_OCC_W_SB_SCH FLOOR 2 CONFERENCE 31.22 16.8 16.8 0.538 1.858 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 15 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
32 FLOOR 2 DICTATION PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 2 DICTATION 6.50 0.4 0.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
33 FLOOR 2 EXAM 1 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 1 33.45 7.2 7.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
34 FLOOR 2 EXAM 2 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 2 50.17 10.8 10.8 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 10 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
35 FLOOR 2 EXAM 3 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 3 66.89 14.4 14.4 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
36 FLOOR 2 EXAM 4 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 4 7.80 1.7 1.7 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
37 FLOOR 2 EXAM 5 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 5 32.52 7.0 7.0 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
38 FLOOR 2 EXAM 6 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 6 20.90 4.5 4.5 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
39 FLOOR 2 EXAM 7 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 7 73.58 15.8 15.8 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 14 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
40 FLOOR 2 EXAM 8 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 8 25.08 5.4 5.4 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 5 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
41 FLOOR 2 EXAM 9 PEOPLE BLDG_OCC_SCH FLOOR 2 EXAM 9 36.79 7.9 7.9 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
42 FLOOR 2 LOUNGE PEOPLE BLDG_OCC_SCH FLOOR 2 LOUNGE 7.43 1.2 1.2 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
43 FLOOR 2 NURSE STATION 1 PEOPLE BLDG_OCC_SCH FLOOR 2 NURSE STATION 1 13.94 3.0 3.0 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
44 FLOOR 2 NURSE STATION 2 PEOPLE BLDG_OCC_SCH FLOOR 2 NURSE STATION 2 16.72 3.6 3.6 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
45 FLOOR 2 OFFICE PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 2 OFFICE 52.03 2.8 2.8 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
46 FLOOR 2 RECEPTION PEOPLE BLDG_OCC_SCH FLOOR 2 RECEPTION 91.42 29.5 29.5 0.323 3.096 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 27 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
47 FLOOR 2 SCHEDULING 1 PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 2 SCHEDULING 1 30.10 1.6 1.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
48 FLOOR 2 SCHEDULING 2 PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 2 SCHEDULING 2 31.77 1.7 1.7 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
49 FLOOR 2 WORK PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 2 WORK 157.01 8.5 8.5 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
50 FLOOR 2 X-RAY PEOPLE BLDG_OCC_SCH FLOOR 2 X-RAY 83.61 18.0 18.0 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 16 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
51 FLOOR 3 DRESSING ROOM PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 3 DRESSING ROOM 3.90 0.2 0.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
52 FLOOR 3 HUMID PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 3 HUMID 10.03 0.5 0.5 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
53 FLOOR 3 LOCKER PEOPLE BLDG_OCC_SCH FLOOR 3 LOCKER 11.15 1.8 1.8 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
54 FLOOR 3 LOUNGE PEOPLE BLDG_OCC_SCH FLOOR 3 LOUNGE 70.51 11.4 11.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 10 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
55 FLOOR 3 OFFICE PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 3 OFFICE 282.05 15.2 15.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 14 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
56 FLOOR 3 PHYSICAL THERAPY 1 PEOPLE BLDG_OCC_SCH FLOOR 3 PHYSICAL THERAPY 1 120.77 26.0 26.0 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 23 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
57 FLOOR 3 PHYSICAL THERAPY 2 PEOPLE BLDG_OCC_SCH FLOOR 3 PHYSICAL THERAPY 2 55.00 11.8 11.8 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
58 FLOOR 3 TREATMENT PEOPLE BLDG_OCC_SCH FLOOR 3 TREATMENT 44.22 9.5 9.5 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 9 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
59 FLOOR 3 WORK PEOPLE OFFICE_OCC_W_SB_SCH FLOOR 3 WORK 53.33 2.9 2.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 FLOOR 1 ANESTHESIA_LIGHTS BLDG_LIGHT_SCH FLOOR 1 ANESTHESIA 10.03 2.2 151.200 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 7.560 136.080
2 FLOOR 1 BIO HAZ_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 1 BIO HAZ 5.20 0.0 21.280 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 0.714 19.152
3 FLOOR 1 CAFE_LIGHTS BLDG_LIGHT_SCH FLOOR 1 CAFE 39.02 42.0 168.000 4.306 4.000 0.000 0.700 0.200 0.100 1.000 LightsWired 8.400 151.200
4 FLOOR 1 CLEAN_LIGHTS BLDG_LIGHT_SCH FLOOR 1 CLEAN 11.71 2.5 176.400 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 8.820 158.760
5 FLOOR 1 CLEAN WORK_LIGHTS BLDG_LIGHT_SCH FLOOR 1 CLEAN WORK 15.33 3.3 231.000 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 11.550 207.900
6 FLOOR 1 DICTATION_LIGHTS BLDG_LIGHT_OFFICE_SCH FLOOR 1 DICTATION 11.71 0.6 93.240 7.965 147.986 0.000 0.700 0.200 0.100 1.000 LightsWired 4.662 83.916
7 FLOOR 1 DRESSING ROOM_LIGHTS BLDG_LIGHT_OFFICE_SCH FLOOR 1 DRESSING ROOM 4.18 0.2 33.300 7.965 147.986 0.000 0.700 0.200 0.100 1.000 LightsWired 1.665 29.970
8 FLOOR 1 ELECTRICAL ROOM_LIGHTS BLDG_LIGHT_SCH FLOOR 1 ELECTRICAL ROOM 9.10 0.0 137.200 15.069 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 6.860 123.480
9 FLOOR 1 ELEVATOR PUMP ROOM_LIGHTS BLDG_LIGHT_SCH FLOOR 1 ELEVATOR PUMP ROOM 8.45 0.0 127.400 15.069 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 6.370 114.660
10 FLOOR 1 HUMID_LIGHTS BLDG_LIGHT_OFFICE_SCH FLOOR 1 HUMID 5.02 0.3 39.960 7.965 147.986 0.000 0.700 0.200 0.100 1.000 LightsWired 1.998 35.964
11 FLOOR 1 IT HALL_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 1 IT HALL 13.01 0.0 68.880 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 3.278 61.992
12 FLOOR 1 IT ROOM_LIGHTS BLDG_LIGHT_OFFICE_SCH FLOOR 1 IT ROOM 10.41 0.6 82.880 7.965 147.986 0.000 0.700 0.200 0.100 1.000 LightsWired 4.144 74.592
13 FLOOR 1 LOBBY_LIGHTS BLDG_LIGHT_LOBBYFLR1_SCH FLOOR 1 LOBBY 57.79 6.2 522.480 9.042 83.992 0.000 0.700 0.200 0.100 1.000 LightsWired 24.818 470.232
14 FLOOR 1 LOBBY HALL_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 1 LOBBY HALL 22.30 0.0 118.080 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 5.620 106.272
15 FLOOR 1 LOBBY TOILET_LIGHTS BLDG_LIGHT_TOILET_SCH FLOOR 1 LOBBY TOILET 5.02 0.0 34.020 6.781 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 1.123 30.618
16 FLOOR 1 LOCKER ROOM_LIGHTS BLDG_LIGHT_LOCKER_SCH FLOOR 1 LOCKER ROOM 61.32 9.9 389.400 6.351 39.330 0.000 0.700 0.200 0.100 1.000 LightsWired 19.470 350.460
17 FLOOR 1 LOCKER ROOM HALL_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 1 LOCKER ROOM HALL 46.08 0.0 244.032 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 11.615 219.629
18 FLOOR 1 LOUNGE_LIGHTS BLDG_LIGHT_LOUNGE_SCH FLOOR 1 LOUNGE 33.45 5.4 212.400 6.351 39.330 0.000 0.700 0.200 0.100 1.000 LightsWired 10.620 191.160
19 FLOOR 1 MED GAS_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 1 MED GAS 5.20 0.0 21.280 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 0.714 19.152
20 FLOOR 1 MRI CONTROL ROOM_LIGHTS BLDG_LIGHT_SCH FLOOR 1 MRI CONTROL ROOM 15.61 3.4 157.920 10.118 46.995 0.000 0.700 0.200 0.100 1.000 LightsWired 7.896 142.128
21 FLOOR 1 MRI HALL_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 1 MRI HALL 13.66 0.0 72.324 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 3.442 65.092
22 FLOOR 1 MRI ROOM_LIGHTS BLDG_LIGHT_EXAM_SCH FLOOR 1 MRI ROOM 40.88 8.8 413.600 10.118 46.995 0.000 0.700 0.200 0.100 1.000 LightsWired 16.130 372.240
23 FLOOR 1 MRI TOILET_LIGHTS BLDG_LIGHT_TOILET_SCH FLOOR 1 MRI TOILET 5.02 0.0 34.020 6.781 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 1.123 30.618
24 FLOOR 1 NOURISHMENT_LIGHTS BLDG_LIGHT_SCH FLOOR 1 NOURISHMENT 16.91 3.6 212.940 12.594 58.494 0.000 0.700 0.200 0.100 1.000 LightsWired 10.647 191.646
25 FLOOR 1 NURSE HALL_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 1 NURSE HALL 46.08 0.0 244.032 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 11.615 219.629
26 FLOOR 1 NURSE JANITOR_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 1 NURSE JANITOR 5.02 0.0 20.520 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 0.689 18.468
27 FLOOR 1 NURSE STATION_LIGHTS BLDG_LIGHT_SCH FLOOR 1 NURSE STATION 24.25 5.2 305.370 12.594 58.494 0.000 0.700 0.200 0.100 1.000 LightsWired 15.269 274.833
28 FLOOR 1 NURSE TOILET_LIGHTS BLDG_LIGHT_TOILET_SCH FLOOR 1 NURSE TOILET 5.02 0.0 34.020 6.781 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 1.123 30.618
29 FLOOR 1 OFFICE_LIGHTS BLDG_LIGHT_OFFICE_SCH FLOOR 1 OFFICE 44.87 2.4 357.420 7.965 147.986 0.000 0.700 0.200 0.100 1.000 LightsWired 17.871 321.678
30 FLOOR 1 OPERATING ROOM 1_LIGHTS BLDG_LIGHT_SCH FLOOR 1 OPERATING ROOM 1 42.74 9.2 1039.600 24.326 112.989 0.000 0.700 0.200 0.100 1.000 LightsWired 51.980 935.640
31 FLOOR 1 OPERATING ROOM 2_LIGHTS BLDG_LIGHT_SCH FLOOR 1 OPERATING ROOM 2 44.59 9.6 1084.800 24.326 112.989 0.000 0.700 0.200 0.100 1.000 LightsWired 54.240 976.320
32 FLOOR 1 OPERATING ROOM 3_LIGHTS BLDG_LIGHT_SCH FLOOR 1 OPERATING ROOM 3 44.22 9.5 1075.760 24.326 112.989 0.000 0.700 0.200 0.100 1.000 LightsWired 53.788 968.184
33 FLOOR 1 PACU_LIGHTS BLDG_LIGHT_SCH FLOOR 1 PACU 10.03 2.2 135.000 13.455 62.494 0.000 0.700 0.200 0.100 1.000 LightsWired 6.750 121.500
34 FLOOR 1 PRE-OP HALL_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 1 PRE-OP HALL 49.05 0.0 259.776 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 12.364 233.798
35 FLOOR 1 PRE-OP ROOM 1_LIGHTS BLDG_LIGHT_SCH FLOOR 1 PRE-OP ROOM 1 17.56 1.9 128.520 7.319 67.993 0.000 0.700 0.200 0.100 1.000 LightsWired 6.426 115.668
36 FLOOR 1 PRE-OP ROOM 2_LIGHTS BLDG_LIGHT_SCH FLOOR 1 PRE-OP ROOM 2 31.40 3.4 229.840 7.319 67.993 0.000 0.700 0.200 0.100 1.000 LightsWired 11.492 206.856
37 FLOOR 1 PRE-OP TOILET_LIGHTS BLDG_LIGHT_TOILET_SCH FLOOR 1 PRE-OP TOILET 5.02 0.0 34.020 6.781 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 1.123 30.618
38 FLOOR 1 PROCEDURE ROOM_LIGHTS BLDG_LIGHT_SCH FLOOR 1 PROCEDURE ROOM 26.48 5.7 399.000 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 19.950 359.100
39 FLOOR 1 RECEPTION_LIGHTS BLDG_LIGHT_SCH FLOOR 1 RECEPTION 47.29 15.3 427.560 9.042 27.997 0.000 0.700 0.200 0.100 1.000 LightsWired 21.378 384.804
40 FLOOR 1 RECEPTION HALL_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 1 RECEPTION HALL 11.89 0.0 62.976 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 2.997 56.678
41 FLOOR 1 RECOVERY ROOM_LIGHTS BLDG_LIGHT_SCH FLOOR 1 RECOVERY ROOM 50.17 10.8 675.000 13.455 62.494 0.000 0.700 0.200 0.100 1.000 LightsWired 33.750 607.500
42 FLOOR 1 SCHEDULING_LIGHTS BLDG_LIGHT_OFFICE_SCH FLOOR 1 SCHEDULING 11.06 0.6 88.060 7.965 147.986 0.000 0.700 0.200 0.100 1.000 LightsWired 4.403 79.254
43 FLOOR 1 SCRUB_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 1 SCRUB 7.80 0.0 41.328 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 1.967 37.195
44 FLOOR 1 SOIL_LIGHTS BLDG_LIGHT_SCH FLOOR 1 SOIL 11.71 2.5 176.400 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 8.820 158.760
45 FLOOR 1 SOIL HOLD_LIGHTS BLDG_LIGHT_SCH FLOOR 1 SOIL HOLD 5.20 1.1 78.400 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 3.920 70.560
46 FLOOR 1 SOIL WORK_LIGHTS BLDG_LIGHT_SCH FLOOR 1 SOIL WORK 16.72 3.6 252.000 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 12.600 226.800
47 FLOOR 1 STEP DOWN_LIGHTS BLDG_LIGHT_SCH FLOOR 1 STEP DOWN 27.87 6.0 375.000 13.455 62.494 0.000 0.700 0.200 0.100 1.000 LightsWired 18.750 337.500
48 FLOOR 1 STERILE HALL_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 1 STERILE HALL 57.23 0.0 303.072 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 14.425 272.765
49 FLOOR 1 STERILE STORAGE_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 1 STERILE STORAGE 36.79 0.0 150.480 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 5.051 135.432
50 FLOOR 1 STORAGE_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 1 STORAGE 85.47 0.0 349.600 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 11.734 314.640
51 FLOOR 1 SUB-STERILE_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 1 SUB-STERILE 18.21 0.0 96.432 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 4.590 86.789
52 FLOOR 1 UTILITY HALL_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 1 UTILITY HALL 23.78 0.0 125.952 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 5.995 113.357
53 FLOOR 1 UTILITY JANITOR_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 1 UTILITY JANITOR 3.90 0.0 15.960 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 0.536 14.364
54 FLOOR 1 UTILITY ROOM_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 1 UTILITY ROOM 33.45 0.0 136.800 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 4.592 123.120
55 FLOOR 1 VESTIBULE_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 1 VESTIBULE 6.69 0.0 35.424 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 1.686 31.882
56 FLOOR 2 CONFERENCE_LIGHTS BLDG_LIGHT_SCH FLOOR 2 CONFERENCE 31.22 16.8 325.920 10.441 19.398 0.000 0.700 0.200 0.100 1.000 LightsWired 16.296 293.328
57 FLOOR 2 CONFERENCE TOILET_LIGHTS BLDG_LIGHT_TOILET_SCH FLOOR 2 CONFERENCE TOILET 5.95 0.0 40.320 6.781 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 1.331 36.288
58 FLOOR 2 DICTATION_LIGHTS BLDG_LIGHT_OFFICE_SCH FLOOR 2 DICTATION 6.50 0.4 51.800 7.965 147.986 0.000 0.700 0.200 0.100 1.000 LightsWired 2.590 46.620
59 FLOOR 2 EXAM 1_LIGHTS BLDG_LIGHT_EXAM_SCH FLOOR 2 EXAM 1 33.45 7.2 504.000 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 19.656 453.600
60 FLOOR 2 EXAM 2_LIGHTS BLDG_LIGHT_EXAM_SCH FLOOR 2 EXAM 2 50.17 10.8 756.000 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 29.484 680.400
61 FLOOR 2 EXAM 3_LIGHTS BLDG_LIGHT_EXAM_SCH FLOOR 2 EXAM 3 66.89 14.4 1008.000 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 39.312 907.200
62 FLOOR 2 EXAM 4_LIGHTS BLDG_LIGHT_EXAM_SCH FLOOR 2 EXAM 4 7.80 1.7 117.600 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 4.586 105.840
63 FLOOR 2 EXAM 5_LIGHTS BLDG_LIGHT_EXAM_SCH FLOOR 2 EXAM 5 32.52 7.0 490.000 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 19.110 441.000
64 FLOOR 2 EXAM 6_LIGHTS BLDG_LIGHT_EXAM_SCH FLOOR 2 EXAM 6 20.90 4.5 315.000 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 12.285 283.500
65 FLOOR 2 EXAM 7_LIGHTS BLDG_LIGHT_EXAM_SCH FLOOR 2 EXAM 7 73.58 15.8 1108.800 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 43.243 997.920
66 FLOOR 2 EXAM 8_LIGHTS BLDG_LIGHT_EXAM_SCH FLOOR 2 EXAM 8 25.08 5.4 378.000 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 14.742 340.200
67 FLOOR 2 EXAM 9_LIGHTS BLDG_LIGHT_EXAM_SCH FLOOR 2 EXAM 9 36.79 7.9 554.400 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 21.622 498.960
68 FLOOR 2 EXAM HALL 1_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 2 EXAM HALL 1 16.72 0.0 88.560 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 4.215 79.704
69 FLOOR 2 EXAM HALL 2_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 2 EXAM HALL 2 16.72 0.0 88.560 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 4.215 79.704
70 FLOOR 2 EXAM HALL 3_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 2 EXAM HALL 3 16.72 0.0 88.560 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 4.215 79.704
71 FLOOR 2 EXAM HALL 4_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 2 EXAM HALL 4 18.39 0.0 97.416 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 4.637 87.674
72 FLOOR 2 EXAM HALL 5_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 2 EXAM HALL 5 18.39 0.0 97.416 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 4.637 87.674
73 FLOOR 2 EXAM HALL 6_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 2 EXAM HALL 6 18.39 0.0 97.416 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 4.637 87.674
74 FLOOR 2 JANITOR_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 2 JANITOR 5.85 0.0 23.940 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 0.804 21.546
75 FLOOR 2 LOUNGE_LIGHTS BLDG_LIGHT_LOUNGE_SCH FLOOR 2 LOUNGE 7.43 1.2 47.200 6.351 39.330 0.000 0.700 0.200 0.100 1.000 LightsWired 2.360 42.480
76 FLOOR 2 NURSE STATION 1_LIGHTS BLDG_LIGHT_SCH FLOOR 2 NURSE STATION 1 13.94 3.0 175.500 12.594 58.494 0.000 0.700 0.200 0.100 1.000 LightsWired 8.775 157.950
77 FLOOR 2 NURSE STATION 2_LIGHTS BLDG_LIGHT_SCH FLOOR 2 NURSE STATION 2 16.72 3.6 210.600 12.594 58.494 0.000 0.700 0.200 0.100 1.000 LightsWired 10.530 189.540
78 FLOOR 2 OFFICE_LIGHTS BLDG_LIGHT_OFFICE_SCH FLOOR 2 OFFICE 52.03 2.8 414.400 7.965 147.986 0.000 0.700 0.200 0.100 1.000 LightsWired 20.720 372.960
79 FLOOR 2 OFFICE HALL_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 2 OFFICE HALL 41.25 0.0 218.448 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 10.397 196.603
80 FLOOR 2 RECEPTION_LIGHTS BLDG_LIGHT_SCH FLOOR 2 RECEPTION 91.42 29.5 826.560 9.042 27.997 0.000 0.700 0.200 0.100 1.000 LightsWired 41.328 743.904
81 FLOOR 2 RECEPTION HALL_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 2 RECEPTION HALL 52.40 0.0 277.488 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 13.207 249.739
82 FLOOR 2 RECEPTION TOILET_LIGHTS BLDG_LIGHT_TOILET_SCH FLOOR 2 RECEPTION TOILET 11.71 0.0 79.380 6.781 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 2.620 71.442
83 FLOOR 2 SCHEDULING 1_LIGHTS BLDG_LIGHT_OFFICE_SCH FLOOR 2 SCHEDULING 1 30.10 1.6 239.760 7.965 147.986 0.000 0.700 0.200 0.100 1.000 LightsWired 11.988 215.784
84 FLOOR 2 SCHEDULING 2_LIGHTS BLDG_LIGHT_OFFICE_SCH FLOOR 2 SCHEDULING 2 31.77 1.7 253.080 7.965 147.986 0.000 0.700 0.200 0.100 1.000 LightsWired 12.654 227.772
85 FLOOR 2 STORAGE 1_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 2 STORAGE 1 5.20 0.0 21.280 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 0.714 19.152
86 FLOOR 2 STORAGE 2_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 2 STORAGE 2 11.15 0.0 45.600 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 1.531 41.040
87 FLOOR 2 STORAGE 3_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 2 STORAGE 3 13.38 0.0 54.720 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 1.837 49.248
88 FLOOR 2 UTILITY_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 2 UTILITY 11.71 0.0 47.880 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 1.607 43.092
89 FLOOR 2 WORK_LIGHTS BLDG_LIGHT_OFFICE_SCH FLOOR 2 WORK 157.01 8.5 1250.600 7.965 147.986 0.000 0.700 0.200 0.100 1.000 LightsWired 62.530 1125.540
90 FLOOR 2 WORK HALL_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 2 WORK HALL 77.48 0.0 410.328 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 19.530 369.295
91 FLOOR 2 WORK TOILET_LIGHTS BLDG_LIGHT_TOILET_SCH FLOOR 2 WORK TOILET 5.02 0.0 34.020 6.781 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 1.123 30.618
92 FLOOR 2 X-RAY_LIGHTS BLDG_LIGHT_EXAM_SCH FLOOR 2 X-RAY 83.61 18.0 846.000 10.118 46.995 0.000 0.700 0.200 0.100 1.000 LightsWired 32.994 761.400
93 FLOOR 3 DRESSING ROOM_LIGHTS BLDG_LIGHT_OFFICE_SCH FLOOR 3 DRESSING ROOM 3.90 0.2 31.080 7.965 147.986 0.000 0.700 0.200 0.100 1.000 LightsWired 1.554 27.972
94 FLOOR 3 ELEVATOR HALL_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 3 ELEVATOR HALL 34.37 0.0 182.040 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 8.664 163.836
95 FLOOR 3 HUMID_LIGHTS BLDG_LIGHT_OFFICE_SCH FLOOR 3 HUMID 10.03 0.5 79.920 7.965 147.986 0.000 0.700 0.200 0.100 1.000 LightsWired 3.996 71.928
96 FLOOR 3 JANITOR_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 3 JANITOR 5.85 0.0 23.940 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 0.804 21.546
97 FLOOR 3 LOCKER_LIGHTS BLDG_LIGHT_LOCKER_SCH FLOOR 3 LOCKER 11.15 1.8 70.800 6.351 39.330 0.000 0.700 0.200 0.100 1.000 LightsWired 3.540 63.720
98 FLOOR 3 LOUNGE_LIGHTS BLDG_LIGHT_LOUNGE_SCH FLOOR 3 LOUNGE 70.51 11.4 447.810 6.351 39.330 0.000 0.700 0.200 0.100 1.000 LightsWired 22.391 403.029
99 FLOOR 3 LOUNGE TOILET_LIGHTS BLDG_LIGHT_TOILET_SCH FLOOR 3 LOUNGE TOILET 17.84 0.0 120.960 6.781 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 3.992 108.864
100 FLOOR 3 MECHANICAL_LIGHTS BLDG_LIGHT_SCH FLOOR 3 MECHANICAL 32.52 0.0 490.000 15.069 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 24.500 441.000
101 FLOOR 3 MECHANICAL HALL_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 3 MECHANICAL HALL 27.87 0.0 147.600 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 7.025 132.840
102 FLOOR 3 OFFICE_LIGHTS BLDG_LIGHT_OFFICE_SCH FLOOR 3 OFFICE 282.05 15.2 2246.640 7.965 147.986 0.000 0.700 0.200 0.100 1.000 LightsWired 112.332 2021.976
103 FLOOR 3 OFFICE HALL_LIGHTS BLDG_LIGHT_CORRIDOR_SCH FLOOR 3 OFFICE HALL 77.48 0.0 410.328 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 19.530 369.295
104 FLOOR 3 OFFICE TOILET_LIGHTS BLDG_LIGHT_TOILET_SCH FLOOR 3 OFFICE TOILET 5.02 0.0 34.020 6.781 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 1.123 30.618
105 FLOOR 3 PHYSICAL THERAPY 1_LIGHTS BLDG_LIGHT_EXAM_SCH FLOOR 3 PHYSICAL THERAPY 1 120.77 26.0 1183.000 9.795 45.496 0.000 0.700 0.200 0.100 1.000 LightsWired 46.137 1064.700
106 FLOOR 3 PHYSICAL THERAPY 2_LIGHTS BLDG_LIGHT_EXAM_SCH FLOOR 3 PHYSICAL THERAPY 2 55.00 11.8 538.720 9.795 45.496 0.000 0.700 0.200 0.100 1.000 LightsWired 21.010 484.848
107 FLOOR 3 PHYSICAL THERAPY TOILET_LIGHTS BLDG_LIGHT_TOILET_SCH FLOOR 3 PHYSICAL THERAPY TOILET 7.80 0.0 52.920 6.781 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 1.746 47.628
108 FLOOR 3 STORAGE 1_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 3 STORAGE 1 10.03 0.0 41.040 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 1.378 36.936
109 FLOOR 3 STORAGE 2_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 3 STORAGE 2 7.80 0.0 31.920 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 1.071 28.728
110 FLOOR 3 TREATMENT_LIGHTS BLDG_LIGHT_SCH FLOOR 3 TREATMENT 44.22 9.5 666.400 15.069 69.993 0.000 0.700 0.200 0.100 1.000 LightsWired 33.320 599.760
111 FLOOR 3 UNDEVELOPED 1_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 3 UNDEVELOPED 1 210.70 0.0 861.840 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 28.928 775.656
112 FLOOR 3 UNDEVELOPED 2_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 3 UNDEVELOPED 2 107.02 0.0 437.760 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 14.693 393.984
113 FLOOR 3 UTILITY_LIGHTS BLDG_LIGHT_STORAGE_SCH FLOOR 3 UTILITY 20.07 0.0 82.080 4.090 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 2.755 73.872
114 FLOOR 3 WORK_LIGHTS BLDG_LIGHT_OFFICE_SCH FLOOR 3 WORK 53.33 2.9 424.760 7.965 147.986 0.000 0.700 0.200 0.100 1.000 LightsWired 21.238 382.284
115 NE STAIR_LIGHTS BLDG_LIGHT_CORRIDOR_SCH NE STAIR 15.61 0.0 82.656 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 3.934 74.390
116 NW ELEVATOR_LIGHTS BLDG_LIGHT_CORRIDOR_SCH NW ELEVATOR 13.01 0.0 68.880 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 3.278 61.992
117 NW STAIR_LIGHTS BLDG_LIGHT_CORRIDOR_SCH NW STAIR 17.84 0.0 94.464 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 4.496 85.018
118 SW STAIR_LIGHTS BLDG_LIGHT_CORRIDOR_SCH SW STAIR 8.92 0.0 47.232 5.296 N/A 0.000 0.700 0.200 0.100 1.000 LightsWired 2.248 42.509


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 FLOOR 1 ANESTHESIA_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 ANESTHESIA 10.03 2.2 216.022 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 64.188 216.022
2 FLOOR 1 BIO HAZ_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 BIO HAZ 5.20 0.0 5.619 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 1.670 5.619
3 FLOOR 1 CAFE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 CAFE 39.02 42.0 419.847 10.760 9.995 0.000 0.500 0.000 0.500 MiscPlug 124.753 419.847
4 FLOOR 1 CLEAN_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 CLEAN 11.71 2.5 252.026 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 74.886 252.026
5 FLOOR 1 CLEAN WORK_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 CLEAN WORK 15.33 3.3 330.033 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 98.066 330.033
6 FLOOR 1 DICTATION_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 DICTATION 11.71 0.6 138.597 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 41.182 138.597
7 FLOOR 1 DRESSING ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 DRESSING ROOM 4.18 0.2 49.499 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 14.708 49.499
8 FLOOR 1 ELECTRICAL ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 ELECTRICAL ROOM 9.10 0.0 490.004 53.820 N/A 0.000 0.500 0.000 0.500 MiscPlug 145.599 490.004
9 FLOOR 1 ELEVATOR PUMP ROOM_ELEVATORS_EQUIP BLDG_ELEVATORS FLOOR 1 ELEVATOR PUMP ROOM 8.45 0.0 48164.835 5697.165 N/A 0.000 0.100 0.900 0.000 ElevatorLift 2408.242 48164.835
10 ELEVATORS_LIGHTS_FAN ELEV_LIGHT_FAN_SCH_ADD_DF FLOOR 1 ELEVATOR PUMP ROOM 8.45 0.0 188.000 22.238 N/A 0.000 0.100 0.900 0.000 ElevatorLightsFan 9.400 188.000
11 FLOOR 1 HUMID_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 HUMID 5.02 0.3 59.399 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 17.650 59.399
12 FLOOR 1 IT HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 IT HALL 13.01 0.0 56.058 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 16.657 56.058
13 FLOOR 1 IT ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 IT ROOM 10.41 0.6 123.197 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 36.606 123.197
14 FLOOR 1 LOBBY_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 LOBBY 57.79 6.2 684.183 11.840 109.986 0.000 0.500 0.000 0.500 MiscPlug 203.297 684.183
15 FLOOR 1 LOBBY HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 LOBBY HALL 22.30 0.0 96.099 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 28.555 96.099
16 FLOOR 1 LOBBY TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 LOBBY TOILET 5.02 0.0 21.622 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 6.425 21.622
17 FLOOR 1 LOCKER ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 LOCKER ROOM 61.32 9.9 1979.894 32.290 199.970 0.000 0.500 0.000 0.500 MiscPlug 588.302 1979.894
18 FLOOR 1 LOCKER ROOM HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 LOCKER ROOM HALL 46.08 0.0 198.604 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 59.013 198.604
19 FLOOR 1 LOUNGE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 LOUNGE 33.45 5.4 1079.942 32.290 199.970 0.000 0.500 0.000 0.500 MiscPlug 320.892 1079.942
20 FLOOR 1 MED GAS_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 MED GAS 5.20 0.0 5.619 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 1.670 5.619
21 FLOOR 1 MRI CONTROL ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 MRI CONTROL ROOM 15.61 3.4 1680.014 107.640 499.956 0.000 0.500 0.000 0.500 MiscPlug 499.196 1680.014
22 FLOOR 1 MRI HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 MRI HALL 13.66 0.0 58.861 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 17.490 58.861
23 FLOOR 1 MRI ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 MRI ROOM 40.88 8.8 4400.037 107.640 499.956 0.000 0.500 0.000 0.500 MiscPlug 1307.419 4400.037
24 FLOOR 1 MRI TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 MRI TOILET 5.02 0.0 21.622 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 6.425 21.622
25 FLOOR 1 NOURISHMENT_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 NOURISHMENT 16.91 3.6 364.037 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 108.169 364.037
26 FLOOR 1 NURSE HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 NURSE HALL 46.08 0.0 198.604 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 59.013 198.604
27 FLOOR 1 NURSE JANITOR_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 NURSE JANITOR 5.02 0.0 5.418 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 1.610 5.418
28 FLOOR 1 NURSE STATION_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 NURSE STATION 24.25 5.2 522.053 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 155.122 522.053
29 FLOOR 1 NURSE TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 NURSE TOILET 5.02 0.0 21.622 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 6.425 21.622
30 FLOOR 1 OFFICE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 OFFICE 44.87 2.4 531.287 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 157.865 531.287
31 FLOOR 1 OPERATING ROOM 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 OPERATING ROOM 1 42.74 9.2 1840.186 43.060 200.001 0.000 0.500 0.000 0.500 MiscPlug 546.790 1840.186
32 FLOOR 1 OPERATING ROOM 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 OPERATING ROOM 2 44.59 9.6 1920.194 43.060 200.001 0.000 0.500 0.000 0.500 MiscPlug 570.563 1920.194
33 FLOOR 1 OPERATING ROOM 3_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 OPERATING ROOM 3 44.22 9.5 1904.193 43.060 200.001 0.000 0.500 0.000 0.500 MiscPlug 565.808 1904.193
34 FLOOR 1 PACU_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 PACU 10.03 2.2 323.983 32.290 149.977 0.000 0.500 0.000 0.500 MiscPlug 96.268 323.983
35 FLOOR 1 PRE-OP HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 PRE-OP HALL 49.05 0.0 211.418 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 62.820 211.418
36 FLOOR 1 PRE-OP ROOM 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 PRE-OP ROOM 1 17.56 1.9 378.038 21.530 200.001 0.000 0.500 0.000 0.500 MiscPlug 112.330 378.038
37 FLOOR 1 PRE-OP ROOM 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 PRE-OP ROOM 2 31.40 3.4 676.068 21.530 200.001 0.000 0.500 0.000 0.500 MiscPlug 200.886 676.068
38 FLOOR 1 PRE-OP TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 PRE-OP TOILET 5.02 0.0 21.622 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 6.425 21.622
39 FLOOR 1 PROCEDURE ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 PROCEDURE ROOM 26.48 5.7 854.954 32.290 149.977 0.000 0.500 0.000 0.500 MiscPlug 254.040 854.954
40 FLOOR 1 RECEPTION_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 RECEPTION 47.29 15.3 559.886 11.840 36.662 0.000 0.500 0.000 0.500 MiscPlug 166.363 559.886
41 FLOOR 1 RECEPTION HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 RECEPTION HALL 11.89 0.0 51.253 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 15.229 51.253
42 FLOOR 1 RECOVERY ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 RECOVERY ROOM 50.17 10.8 1619.913 32.290 149.977 0.000 0.500 0.000 0.500 MiscPlug 481.338 1619.913
43 FLOOR 1 SCHEDULING_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 SCHEDULING 11.06 0.6 130.897 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 38.894 130.897
44 FLOOR 1 SCRUB_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 SCRUB 7.80 0.0 33.635 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 9.994 33.635
45 FLOOR 1 SOIL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 SOIL 11.71 2.5 252.026 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 74.886 252.026
46 FLOOR 1 SOIL HOLD_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 SOIL HOLD 5.20 1.1 112.011 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 33.283 112.011
47 FLOOR 1 SOIL WORK_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 SOIL WORK 16.72 3.6 360.036 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 106.981 360.036
48 FLOOR 1 STEP DOWN_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 STEP DOWN 27.87 6.0 899.952 32.290 149.977 0.000 0.500 0.000 0.500 MiscPlug 267.410 899.952
49 FLOOR 1 STERILE HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 STERILE HALL 57.23 0.0 246.654 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 73.290 246.654
50 FLOOR 1 STERILE STORAGE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 STERILE STORAGE 36.79 0.0 39.733 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 11.806 39.733
51 FLOOR 1 STORAGE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 STORAGE 85.47 0.0 92.309 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 27.428 92.309
52 FLOOR 1 SUB-STERILE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 SUB-STERILE 18.21 0.0 78.481 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 23.320 78.481
53 FLOOR 1 UTILITY HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 UTILITY HALL 23.78 0.0 102.506 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 30.458 102.506
54 FLOOR 1 UTILITY JANITOR_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 UTILITY JANITOR 3.90 0.0 4.214 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 1.252 4.214
55 FLOOR 1 UTILITY ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 UTILITY ROOM 33.45 0.0 36.121 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 10.733 36.121
56 FLOOR 1 VESTIBULE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 1 VESTIBULE 6.69 0.0 28.830 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 8.566 28.830
57 FLOOR 2 CONFERENCE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 CONFERENCE 31.22 16.8 335.878 10.760 19.991 0.000 0.500 0.000 0.500 MiscPlug 99.802 335.878
58 FLOOR 2 CONFERENCE TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 CONFERENCE TOILET 5.95 0.0 25.626 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 7.615 25.626
59 FLOOR 2 DICTATION_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 DICTATION 6.50 0.4 76.998 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 22.879 76.998
60 FLOOR 2 EXAM 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 1 33.45 7.2 395.990 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 117.664 395.990
61 FLOOR 2 EXAM 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 2 50.17 10.8 593.985 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 176.496 593.985
62 FLOOR 2 EXAM 3_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 3 66.89 14.4 791.980 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 235.327 791.980
63 FLOOR 2 EXAM 4_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 4 7.80 1.7 92.398 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 27.455 92.398
64 FLOOR 2 EXAM 5_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 5 32.52 7.0 384.990 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 114.395 384.990
65 FLOOR 2 EXAM 6_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 6 20.90 4.5 247.494 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 73.540 247.494
66 FLOOR 2 EXAM 7_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 7 73.58 15.8 871.178 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 258.860 871.178
67 FLOOR 2 EXAM 8_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 8 25.08 5.4 296.992 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 88.248 296.992
68 FLOOR 2 EXAM 9_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM 9 36.79 7.9 435.589 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 129.430 435.589
69 FLOOR 2 EXAM HALL 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM HALL 1 16.72 0.0 72.074 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 21.416 72.074
70 FLOOR 2 EXAM HALL 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM HALL 2 16.72 0.0 72.074 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 21.416 72.074
71 FLOOR 2 EXAM HALL 3_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM HALL 3 16.72 0.0 72.074 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 21.416 72.074
72 FLOOR 2 EXAM HALL 4_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM HALL 4 18.39 0.0 79.282 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 23.558 79.282
73 FLOOR 2 EXAM HALL 5_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM HALL 5 18.39 0.0 79.282 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 23.558 79.282
74 FLOOR 2 EXAM HALL 6_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 EXAM HALL 6 18.39 0.0 79.282 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 23.558 79.282
75 FLOOR 2 JANITOR_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 JANITOR 5.85 0.0 6.321 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 1.878 6.321
76 FLOOR 2 LOUNGE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 LOUNGE 7.43 1.2 239.987 32.290 199.970 0.000 0.500 0.000 0.500 MiscPlug 71.309 239.987
77 FLOOR 2 NURSE STATION 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 NURSE STATION 1 13.94 3.0 300.030 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 89.150 300.030
78 FLOOR 2 NURSE STATION 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 NURSE STATION 2 16.72 3.6 360.036 21.530 100.000 0.000 0.500 0.000 0.500 MiscPlug 106.981 360.036
79 FLOOR 2 OFFICE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 OFFICE 52.03 2.8 615.984 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 183.032 615.984
80 FLOOR 2 OFFICE HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 OFFICE HALL 41.25 0.0 177.783 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 52.826 177.783
81 FLOOR 2 RECEPTION_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 RECEPTION 91.42 29.5 1082.372 11.840 36.662 0.000 0.500 0.000 0.500 MiscPlug 321.614 1082.372
82 FLOOR 2 RECEPTION HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 RECEPTION HALL 52.40 0.0 225.832 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 67.103 225.832
83 FLOOR 2 RECEPTION TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 RECEPTION TOILET 11.71 0.0 50.452 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 14.991 50.452
84 FLOOR 2 SCHEDULING 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 SCHEDULING 1 30.10 1.6 356.391 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 105.897 356.391
85 FLOOR 2 SCHEDULING 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 SCHEDULING 2 31.77 1.7 376.190 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 111.781 376.190
86 FLOOR 2 STORAGE 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 STORAGE 1 5.20 0.0 5.619 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 1.670 5.619
87 FLOOR 2 STORAGE 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 STORAGE 2 11.15 0.0 12.040 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 3.578 12.040
88 FLOOR 2 STORAGE 3_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 STORAGE 3 13.38 0.0 14.448 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 4.293 14.448
89 FLOOR 2 UTILITY_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 UTILITY 11.71 0.0 12.642 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 3.756 12.642
90 FLOOR 2 WORK_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 WORK 157.01 8.5 1535.561 9.780 181.705 0.000 0.500 0.000 0.500 MiscPlug 456.274 1535.561
91 FLOOR 2 WORK HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 WORK HALL 77.48 0.0 333.944 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 99.227 333.944
92 FLOOR 2 WORK TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 WORK TOILET 5.02 0.0 21.622 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 6.425 21.622
93 FLOOR 2 X-RAY_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 2 X-RAY 83.61 18.0 9000.075 107.640 499.956 0.000 0.500 0.000 0.500 MiscPlug 2674.266 9000.075
94 FLOOR 3 DRESSING ROOM_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 DRESSING ROOM 3.90 0.2 46.199 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 13.727 46.199
95 FLOOR 3 ELEVATOR HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 ELEVATOR HALL 34.37 0.0 148.153 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 44.022 148.153
96 FLOOR 3 HUMID_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 HUMID 10.03 0.5 118.797 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 35.299 118.797
97 FLOOR 3 JANITOR_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 JANITOR 5.85 0.0 6.321 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 1.878 6.321
98 FLOOR 3 LOCKER_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 LOCKER 11.15 1.8 359.981 32.290 199.970 0.000 0.500 0.000 0.500 MiscPlug 106.964 359.981
99 FLOOR 3 LOUNGE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 LOUNGE 70.51 11.4 2276.878 32.290 199.970 0.000 0.500 0.000 0.500 MiscPlug 676.547 2276.878
100 FLOOR 3 LOUNGE TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 LOUNGE TOILET 17.84 0.0 76.879 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 22.844 76.879
101 FLOOR 3 MECHANICAL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 MECHANICAL 32.52 0.0 1750.015 53.820 N/A 0.000 0.500 0.000 0.500 MiscPlug 519.996 1750.015
102 FLOOR 3 MECHANICAL HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 MECHANICAL HALL 27.87 0.0 120.124 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 35.693 120.124
103 FLOOR 3 OFFICE_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 OFFICE 282.05 15.2 3339.515 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 992.297 3339.515
104 FLOOR 3 OFFICE HALL_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 OFFICE HALL 77.48 0.0 333.944 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 99.227 333.944
105 FLOOR 3 OFFICE TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 OFFICE TOILET 5.02 0.0 21.622 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 6.425 21.622
106 FLOOR 3 PHYSICAL THERAPY 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 PHYSICAL THERAPY 1 120.77 26.0 1950.499 16.150 75.012 0.000 0.500 0.000 0.500 MiscPlug 579.568 1950.499
107 FLOOR 3 PHYSICAL THERAPY 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 PHYSICAL THERAPY 2 55.00 11.8 888.227 16.150 75.012 0.000 0.500 0.000 0.500 MiscPlug 263.926 888.227
108 FLOOR 3 PHYSICAL THERAPY TOILET_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 PHYSICAL THERAPY TOILET 7.80 0.0 33.635 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 9.994 33.635
109 FLOOR 3 STORAGE 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 STORAGE 1 10.03 0.0 10.836 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 3.220 10.836
110 FLOOR 3 STORAGE 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 STORAGE 2 7.80 0.0 8.428 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 2.504 8.428
111 FLOOR 3 TREATMENT_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 TREATMENT 44.22 9.5 523.587 11.840 54.993 0.000 0.500 0.000 0.500 MiscPlug 155.578 523.587
112 FLOOR 3 UNDEVELOPED 1_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 UNDEVELOPED 1 210.70 0.0 2494.737 11.840 N/A 0.000 0.500 0.000 0.500 MiscPlug 741.281 2494.737
113 FLOOR 3 UNDEVELOPED 2_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 UNDEVELOPED 2 107.02 0.0 1267.168 11.840 N/A 0.000 0.500 0.000 0.500 MiscPlug 376.524 1267.168
114 FLOOR 3 UTILITY_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 UTILITY 20.07 0.0 21.672 1.080 N/A 0.000 0.500 0.000 0.500 MiscPlug 6.440 21.672
115 FLOOR 3 WORK_PLUGMISC_EQUIP BLDG_EQUIP_SCH FLOOR 3 WORK 53.33 2.9 631.384 11.840 219.973 0.000 0.500 0.000 0.500 MiscPlug 187.608 631.384
116 NE STAIR_PLUGMISC_EQUIP BLDG_EQUIP_SCH NE STAIR 15.61 0.0 67.269 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 19.988 67.269
117 NW ELEVATOR_PLUGMISC_EQUIP BLDG_EQUIP_SCH NW ELEVATOR 13.01 0.0 56.058 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 16.657 56.058
118 NW STAIR_PLUGMISC_EQUIP BLDG_EQUIP_SCH NW STAIR 17.84 0.0 76.879 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 22.844 76.879
119 SW STAIR_PLUGMISC_EQUIP BLDG_EQUIP_SCH SW STAIR 8.92 0.0 38.440 4.310 N/A 0.000 0.500 0.000 0.500 MiscPlug 11.422 38.440


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 FLOOR 1 OPERATING ROOM 1_GASMISC_EQUIP BLDG_EQUIP_SCH_BASE FLOOR 1 OPERATING ROOM 1 42.74 9.2 3217.976 75.300 349.746 0.000 0.000 0.500 0.500 MiscPlug 965.393 3217.976
2 FLOOR 1 OPERATING ROOM 2_GASMISC_EQUIP BLDG_EQUIP_SCH_BASE FLOOR 1 OPERATING ROOM 2 44.59 9.6 3357.888 75.300 349.746 0.000 0.000 0.500 0.500 MiscPlug 1007.366 3357.888
3 FLOOR 1 OPERATING ROOM 3_GASMISC_EQUIP BLDG_EQUIP_SCH_BASE FLOOR 1 OPERATING ROOM 3 44.22 9.5 3329.905 75.300 349.746 0.000 0.000 0.500 0.500 MiscPlug 998.972 3329.905


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.761 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 INT_SLAB_FLOOR 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_CEILING 14 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
7 NONRES_ROOF 18 3 3 0.167 0.1625 0.900 0.900 0.700 0.700 Rough
8 NONRES_EXT_WALL 21 4 7 0.167 0.2903 0.900 0.900 0.700 0.700 Smooth
9 FLOOR1ANESTHESIASLAB_FFACTOR 31 2 7 0.167 0.2507 0.000 0.900 0.000 0.700 MediumRough
10 FLOOR1BIOHAZSLAB_FFACTOR 32 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
11 FLOOR1CAFESLAB_FFACTOR 33 2 7 0.167 0.1409 0.000 0.900 0.000 0.700 MediumRough
12 FLOOR1CLEANSLAB_FFACTOR 34 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
13 FLOOR1CLEANWORKSLAB_FFACTOR 35 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
14 FLOOR1DICTATIONSLAB_FFACTOR 36 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
15 FLOOR1DRESSINGROOMSLAB_FFACTOR 37 2 7 0.167 0.6364 0.000 0.900 0.000 0.700 MediumRough
16 FLOOR1ELECTRICALROOMSLAB_FFACTOR 38 2 7 0.167 0.2137 0.000 0.900 0.000 0.700 MediumRough
17 FLOOR1ELEVATORPUMPROOMSLAB_FFACTOR 39 2 7 0.167 0.7062 0.000 0.900 0.000 0.700 MediumRough
18 FLOOR1HUMIDSLAB_FFACTOR 40 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
19 FLOOR1ITHALLSLAB_FFACTOR 41 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
20 FLOOR1ITROOMSLAB_FFACTOR 42 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
21 FLOOR1LOBBYSLAB_FFACTOR 43 2 7 0.167 0.1041 0.000 0.900 0.000 0.700 MediumRough
22 FLOOR1LOBBYHALLSLAB_FFACTOR 44 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
23 FLOOR1LOBBYTOILETSLAB_FFACTOR 45 2 7 0.167 0.3387 0.000 0.900 0.000 0.700 MediumRough
24 FLOOR1LOCKERROOMSLAB_FFACTOR 46 2 7 0.167 0.9801E-01 0.000 0.900 0.000 0.700 MediumRough
25 FLOOR1LOCKERROOMHALLSLAB_FFACTOR 47 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
26 FLOOR1LOUNGESLAB_FFACTOR 48 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
27 FLOOR1MEDGASSLAB_FFACTOR 49 2 7 0.167 0.8819 0.000 0.900 0.000 0.700 MediumRough
28 FLOOR1MRICONTROLROOMSLAB_FFACTOR 50 2 7 0.167 0.8737E-01 0.000 0.900 0.000 0.700 MediumRough
29 FLOOR1MRIHALLSLAB_FFACTOR 51 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
30 FLOOR1MRIROOMSLAB_FFACTOR 52 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
31 FLOOR1MRITOILETSLAB_FFACTOR 53 2 7 0.167 0.3387 0.000 0.900 0.000 0.700 MediumRough
32 FLOOR1NOURISHMENTSLAB_FFACTOR 54 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
33 FLOOR1NURSEHALLSLAB_FFACTOR 55 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
34 FLOOR1NURSEJANITORSLAB_FFACTOR 56 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
35 FLOOR1NURSESTATIONSLAB_FFACTOR 57 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
36 FLOOR1NURSETOILETSLAB_FFACTOR 58 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
37 FLOOR1OFFICESLAB_FFACTOR 59 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
38 FLOOR1OPERATINGROOM1SLAB_FFACTOR 60 2 7 0.167 0.2826 0.000 0.900 0.000 0.700 MediumRough
39 FLOOR1OPERATINGROOM2SLAB_FFACTOR 61 2 7 0.167 0.1481 0.000 0.900 0.000 0.700 MediumRough
40 FLOOR1OPERATINGROOM3SLAB_FFACTOR 62 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
41 FLOOR1PACUSLAB_FFACTOR 63 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
42 FLOOR1PRE-OPHALLSLAB_FFACTOR 64 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
43 FLOOR1PRE-OPROOM1SLAB_FFACTOR 65 2 7 0.167 0.6189E-01 0.000 0.900 0.000 0.700 MediumRough
44 FLOOR1PRE-OPROOM2SLAB_FFACTOR 66 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
45 FLOOR1PRE-OPTOILETSLAB_FFACTOR 67 2 7 0.167 0.3387 0.000 0.900 0.000 0.700 MediumRough
46 FLOOR1PROCEDUREROOMSLAB_FFACTOR 68 2 7 0.167 0.1990 0.000 0.900 0.000 0.700 MediumRough
47 FLOOR1RECEPTIONSLAB_FFACTOR 69 2 7 0.167 0.7483E-01 0.000 0.900 0.000 0.700 MediumRough
48 FLOOR1RECEPTIONHALLSLAB_FFACTOR 70 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
49 FLOOR1RECOVERYROOMSLAB_FFACTOR 71 2 7 0.167 0.2507 0.000 0.900 0.000 0.700 MediumRough
50 FLOOR1SCHEDULINGSLAB_FFACTOR 72 2 7 0.167 0.1750 0.000 0.900 0.000 0.700 MediumRough
51 FLOOR1SCRUBSLAB_FFACTOR 73 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
52 FLOOR1SOILSLAB_FFACTOR 74 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
53 FLOOR1SOILHOLDSLAB_FFACTOR 75 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
54 FLOOR1SOILWORKSLAB_FFACTOR 76 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
55 FLOOR1STEPDOWNSLAB_FFACTOR 77 2 7 0.167 0.3782 0.000 0.900 0.000 0.700 MediumRough
56 FLOOR1STERILEHALLSLAB_FFACTOR 78 2 7 0.167 0.3784E-01 0.000 0.900 0.000 0.700 MediumRough
57 FLOOR1NURSESTORAGESLAB_FFACTOR 79 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
58 FLOOR1STORAGESLAB_FFACTOR 80 2 7 0.167 0.2046 0.000 0.900 0.000 0.700 MediumRough
59 FLOOR1SUB-STERILESLAB_FFACTOR 81 2 7 0.167 0.2137 0.000 0.900 0.000 0.700 MediumRough
60 FLOOR1UTILITYHALLSLAB_FFACTOR 82 2 7 0.167 0.1862 0.000 0.900 0.000 0.700 MediumRough
61 FLOOR1UTILITYJANITORSLAB_FFACTOR 83 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough
62 FLOOR1UTILITYROOMSLAB_FFACTOR 84 2 7 0.167 0.1481 0.000 0.900 0.000 0.700 MediumRough
63 FLOOR1VESTIBULESLAB_FFACTOR 85 2 7 0.167 0.3387 0.000 0.900 0.000 0.700 MediumRough
64 NESTAIRSLAB_FFACTOR 86 2 7 0.167 0.6657 0.000 0.900 0.000 0.700 MediumRough
65 NWELEVATORSLAB_FFACTOR 87 2 7 0.167 0.6115 0.000 0.900 0.000 0.700 MediumRough
66 NWSTAIRSLAB_FFACTOR 88 2 7 0.167 0.6657 0.000 0.900 0.000 0.700 MediumRough
67 SWSTAIRSLAB_FFACTOR 89 2 7 0.167 0.6657 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.5677
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
9 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
10 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
11 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 6.093
12 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
13 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
14 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
15 NONRES_EXTERIOR_WALL_INSULATION 0.0000 0.000 0.000 0.000 3.210
16 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
17 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 3.911
18 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
19 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 176.9
20 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
21 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 7.019
22 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
23 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 176.9
24 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
25 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 176.9
26 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
27 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 176.9
28 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
29 ~FC_Insulation_7 0.0000 0.000 0.000 0.000 1.494
30 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
31 ~FC_Insulation_8 0.0000 0.000 0.000 0.000 4.602
32 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
33 ~FC_Insulation_9 0.0000 0.000 0.000 0.000 1.339
34 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
35 ~FC_Insulation_10 0.0000 0.000 0.000 0.000 176.9
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_11 0.0000 0.000 0.000 0.000 176.9
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_12 0.0000 0.000 0.000 0.000 176.9
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_13 0.0000 0.000 0.000 0.000 9.530
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
43 ~FC_Insulation_14 0.0000 0.000 0.000 0.000 176.9
44 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
45 ~FC_Insulation_15 0.0000 0.000 0.000 0.000 2.875
46 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
47 ~FC_Insulation_16 0.0000 0.000 0.000 0.000 10.13
48 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
49 ~FC_Insulation_17 0.0000 0.000 0.000 0.000 176.9
50 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
51 ~FC_Insulation_18 0.0000 0.000 0.000 0.000 176.9
52 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
53 ~FC_Insulation_19 0.0000 0.000 0.000 0.000 1.057
54 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
55 ~FC_Insulation_20 0.0000 0.000 0.000 0.000 11.37
56 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
57 ~FC_Insulation_21 0.0000 0.000 0.000 0.000 176.9
58 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
59 ~FC_Insulation_22 0.0000 0.000 0.000 0.000 176.9
60 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
61 ~FC_Insulation_23 0.0000 0.000 0.000 0.000 2.875
62 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
63 ~FC_Insulation_24 0.0000 0.000 0.000 0.000 176.9
64 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
65 ~FC_Insulation_25 0.0000 0.000 0.000 0.000 176.9
66 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
67 ~FC_Insulation_26 0.0000 0.000 0.000 0.000 176.9
68 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
69 ~FC_Insulation_27 0.0000 0.000 0.000 0.000 176.9
70 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
71 ~FC_Insulation_28 0.0000 0.000 0.000 0.000 176.9
72 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
73 ~FC_Insulation_29 0.0000 0.000 0.000 0.000 176.9
74 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
75 ~FC_Insulation_30 0.0000 0.000 0.000 0.000 3.462
76 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
77 ~FC_Insulation_31 0.0000 0.000 0.000 0.000 6.673
78 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
79 ~FC_Insulation_32 0.0000 0.000 0.000 0.000 176.9
80 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
81 ~FC_Insulation_33 0.0000 0.000 0.000 0.000 176.9
82 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
83 ~FC_Insulation_34 0.0000 0.000 0.000 0.000 176.9
84 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
85 ~FC_Insulation_35 0.0000 0.000 0.000 0.000 16.08
86 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
87 ~FC_Insulation_36 0.0000 0.000 0.000 0.000 176.9
88 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
89 ~FC_Insulation_37 0.0000 0.000 0.000 0.000 2.875
90 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
91 ~FC_Insulation_38 0.0000 0.000 0.000 0.000 4.947
92 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
93 ~FC_Insulation_39 0.0000 0.000 0.000 0.000 13.29
94 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
95 ~FC_Insulation_40 0.0000 0.000 0.000 0.000 176.9
96 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
97 ~FC_Insulation_41 0.0000 0.000 0.000 0.000 3.911
98 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
99 ~FC_Insulation_42 0.0000 0.000 0.000 0.000 5.638
100 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
101 ~FC_Insulation_43 0.0000 0.000 0.000 0.000 176.9
102 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
103 ~FC_Insulation_44 0.0000 0.000 0.000 0.000 176.9
104 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
105 ~FC_Insulation_45 0.0000 0.000 0.000 0.000 176.9
106 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
107 ~FC_Insulation_46 0.0000 0.000 0.000 0.000 176.9
108 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
109 ~FC_Insulation_47 0.0000 0.000 0.000 0.000 2.567
110 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
111 ~FC_Insulation_48 0.0000 0.000 0.000 0.000 26.35
112 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
113 ~FC_Insulation_49 0.0000 0.000 0.000 0.000 176.9
114 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
115 ~FC_Insulation_50 0.0000 0.000 0.000 0.000 4.810
116 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
117 ~FC_Insulation_51 0.0000 0.000 0.000 0.000 4.602
118 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
119 ~FC_Insulation_52 0.0000 0.000 0.000 0.000 5.292
120 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
121 ~FC_Insulation_53 0.0000 0.000 0.000 0.000 176.9
122 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
123 ~FC_Insulation_54 0.0000 0.000 0.000 0.000 6.673
124 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
125 ~FC_Insulation_55 0.0000 0.000 0.000 0.000 2.875
126 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
127 ~FC_Insulation_56 0.0000 0.000 0.000 0.000 1.425
128 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
129 ~FC_Insulation_57 0.0000 0.000 0.000 0.000 1.558
130 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
131 ~FC_Insulation_58 0.0000 0.000 0.000 0.000 1.425
132 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
133 ~FC_Insulation_59 0.0000 0.000 0.000 0.000 1.425
134 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1010000 2.1010000 2.1010000  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.7613636 1.7613636 1.7613636  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
21 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
22 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
23 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
24 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
25 2 51.553741 0.22121684 1.2284947 -0.25833933
26 1 -128.86110 0.21944682 -5.1479470 1.1228340
27 0 81.526494 0.16043334E-01 4.4519351  
28 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
29 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
30 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
31 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
32 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
33 2 1.2284947 0.22121684 51.553741 -0.25833933
34 1 -5.1479470 0.21944682 -128.86110 1.1228340
35 0 4.4519351 0.16043334E-01 81.526494  
36 3 -0.63083111E-06 0.74112372E-09 -0.38647046E-05 0.15329585E-16
37 2 0.78415922 0.99752939E-03 1.0633801 -0.74093433E-06
38 1 -22.010056 0.66447931E-01 -6.3131541 0.20386814
39 0 21.355302 0.61958938E-01 5.3791822  
40 7 -0.37770232E-12 0.51790214E-15 -0.12781252E-12 0.55998589E-16
41 6 0.34333646E-07 0.85611267E-10 0.78179037E-08 -0.16618826E-12
42 5 -0.21846269E-03 0.70914283E-06 -0.11192726E-03 0.77079120E-08
43 4 0.32474569 0.33518246E-03 0.11143489 -0.38230638E-04
44 3 -7.9105893 0.10117084E-01 -2.5301860 0.32170091E-01
45 2 42.994418 0.35140113E-01 16.046370 -0.35699651
46 1 -82.171251 0.15534856E-01 -29.841212 1.1132611
47 0 46.824329 0.30626733E-03 16.275140  
48 7 -0.16745635E-08 -0.34336040E-15 0.84355089E-14 -0.11966027E-15
49 6 0.70109463E-05 0.48099747E-08 0.31858354E-02 -0.26725457E-04
50 5 -0.50524852E-03 0.28501127E-05 -0.22349525 0.19541262E-02
51 4 0.11628654E-01 0.12975345E-03 4.8257261 -0.45228265E-01
52 3 -0.10213633 0.10320045E-02 -37.999839 0.39841525
53 2 0.36269187 0.17170067E-02 116.44195 -1.4173776
54 1 -0.52350793 0.52328400E-03 -143.88258 2.0486336
55 0 0.25523951 0.12640358E-04 60.838472  
56 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
57 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
58 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
59 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
60 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
61 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
62 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
63 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
64 0 0.84795330E-02 0.69040512E-07 60.838472  
65 7 -0.30130732E-08 -0.19663079E-14 0.18020900E-14 -0.47182978E-16
66 6 0.40580912E-05 0.26947613E-08 0.31944409E-02 -0.26797647E-04
67 5 -0.28518434E-03 0.15936277E-05 -0.22398436 0.19584433E-02
68 4 0.65167661E-02 0.72485992E-04 4.8338723 -0.45306572E-01
69 3 -0.57091956E-01 0.57601239E-03 -38.045856 0.39892390
70 2 0.20253495 0.95766665E-03 116.53151 -1.4185755
71 1 -0.29220933 0.29151331E-03 -143.93531 2.0495001
72 0 0.14243704 0.70698501E-05 60.838472  
73 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
74 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
75 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
76 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
77 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
78 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
79 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
80 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
81 0 0.84795330E-02 0.69040512E-07 60.838472  
82 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
83 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
84 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
85 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
86 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
87 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
88 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
89 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
90 0 0.84795330E-02 0.69040512E-07 60.838472  
91 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
92 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
93 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
94 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
95 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
96 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
97 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
98 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
99 0 0.84795330E-02 0.69040512E-07 60.838472  
100 7 -0.63354292E-09 -0.34524560E-16 0.25970292E-14 0.43057705E-17
101 6 0.18121931E-04 0.12451397E-07 0.31546183E-02 -0.26463582E-04
102 5 -0.13164637E-02 0.74038195E-05 -0.22172031 0.19384598E-02
103 4 0.30338355E-01 0.33751534E-03 4.7961511 -0.44943982E-01
104 3 -0.26648700 0.26888935E-02 -37.832705 0.39656797
105 2 0.94621804 0.44783110E-02 116.11658 -1.4130256
106 1 -1.3656475 0.13682334E-02 -143.69102 2.0454848
107 0 0.66578928 0.32451875E-04 60.838472  
108 7 -0.19720080E-08 -0.56222426E-15 0.71895331E-14 -0.10475809E-15
109 6 0.59980349E-05 0.40937398E-08 0.31887486E-02 -0.26749895E-04
110 5 -0.43037878E-03 0.24246149E-05 -0.22366084 0.19555878E-02
111 4 0.98938404E-02 0.11035919E-03 4.8284843 -0.45254778E-01
112 3 -0.86864713E-01 0.87756038E-03 -38.015421 0.39858748
113 2 0.30841581 0.14598055E-02 116.47228 -1.4177832
114 1 -0.44513792 0.44476903E-03 -143.90044 2.0489270
115 0 0.21702305 0.10756423E-04 60.838472  
116 7 -0.56662636E-09 -0.32498008E-16 0.28411115E-14 -0.25164316E-17
117 6 0.20224663E-04 0.13863325E-07 0.31487914E-02 -0.26414701E-04
118 5 -0.14691118E-02 0.82524534E-05 -0.22138891 0.19355348E-02
119 4 0.33848916E-01 0.37625138E-03 4.7906274 -0.44890890E-01
120 3 -0.29727753 0.29985150E-02 -37.801482 0.39622288
121 2 1.0554555 0.49943303E-02 116.05578 -1.4122124
122 1 -1.5232347 0.15271081E-02 -143.65522 2.0448964
123 0 0.74259706 0.35868910E-04 60.838472  
124 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
125 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
126 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
127 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
128 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
129 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
130 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
131 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
132 0 0.84795330E-02 0.69040512E-07 60.838472  
133 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
134 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
135 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
136 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
137 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
138 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
139 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
140 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
141 0 0.84795330E-02 0.69040512E-07 60.838472  
142 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
143 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
144 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
145 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
146 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
147 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
148 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
149 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
150 0 0.84795330E-02 0.69040512E-07 60.838472  
151 7 -0.40947066E-08 -0.48955525E-14 0.95226092E-15 -0.40789664E-16
152 6 0.31269961E-05 0.19931420E-08 0.31973038E-02 -0.26821664E-04
153 5 -0.21333598E-03 0.11765416E-05 -0.22414703 0.19598792E-02
154 4 0.48311985E-02 0.53472194E-04 4.8365808 -0.45332608E-01
155 3 -0.42183862E-01 0.42460073E-03 -38.061152 0.39909298
156 2 0.14944710 0.70549263E-03 116.56128 -1.4189737
157 1 -0.21548528 0.21452630E-03 -143.95282 2.0497881
158 0 0.10500555 0.52161482E-05 60.838472  
159 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
160 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
161 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
162 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
163 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
164 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
165 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
166 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
167 0 0.84795330E-02 0.69040512E-07 60.838472  
168 7 -0.12284012E-08 -0.14175971E-15 0.90913404E-14 -0.95703409E-16
169 6 0.94645076E-05 0.65252983E-08 0.31788545E-02 -0.26666895E-04
170 5 -0.68547975E-03 0.38695660E-05 -0.22309841 0.19506234E-02
171 4 0.15796080E-01 0.17623363E-03 4.8191151 -0.45164717E-01
172 3 -0.13878962 0.14022659E-02 -37.962486 0.39800239
173 2 0.49290750 0.23337621E-02 116.36925 -1.4164051
174 1 -0.71149158 0.71162911E-03 -143.83978 2.0479300
175 0 0.34689854 0.17148853E-04 60.838472  
176 7 -0.43515952E-08 -0.58697377E-14 0.18887276E-14 -0.43154944E-16
177 6 0.29796072E-05 0.18778145E-08 0.31977758E-02 -0.26825623E-04
178 5 -0.20164803E-03 0.11079188E-05 -0.22417385 0.19601158E-02
179 4 0.45549943E-02 0.50342701E-04 4.8370272 -0.45336899E-01
180 3 -0.39734490E-01 0.39967219E-03 -38.063673 0.39912084
181 2 0.14071554 0.66396299E-03 116.56618 -1.4190393
182 1 -0.20286005 0.20184195E-03 -143.95571 2.0498355
183 0 0.98844516E-01 0.49107823E-05 60.838472  
184 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
185 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
186 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
187 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
188 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
189 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
190 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
191 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
192 0 0.84795330E-02 0.69040512E-07 60.838472  
193 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
194 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
195 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
196 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
197 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
198 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
199 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
200 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
201 0 0.84795330E-02 0.69040512E-07 60.838472  
202 7 -0.44519219E-09 0.21353915E-16 0.26743827E-14 -0.64240203E-17
203 6 0.25633029E-04 0.17490695E-07 0.31338911E-02 -0.26289704E-04
204 5 -0.18609750E-02 0.10417545E-04 -0.22054135 0.19280540E-02
205 4 0.42849662E-01 0.47529737E-03 4.7764982 -0.44755083E-01
206 3 -0.37616433 0.37901525E-02 -37.721601 0.39534004
207 2 1.3352208 0.63166647E-02 115.90023 -1.4101318
208 1 -1.9267460 0.19322515E-02 -143.56362 2.0433907
209 0 0.93924550 0.45494630E-04 60.838472  
210 7 -0.48870060E-08 -0.82965015E-14 0.59818870E-15 -0.31463760E-16
211 6 0.27285629E-05 0.16760845E-08 0.31986010E-02 -0.26832546E-04
212 5 -0.18138205E-03 0.98813231E-06 -0.22422072 0.19605296E-02
213 4 0.40738709E-02 0.44875976E-04 4.8378074 -0.45344400E-01
214 3 -0.35460872E-01 0.35612997E-03 -38.068078 0.39916953
215 2 0.12547084 0.59137191E-03 116.57475 -1.4191539
216 1 -0.18081065 0.17970674E-03 -143.96075 2.0499184
217 0 0.88082908E-01 0.43607610E-05 60.838472  
218 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
219 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
220 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
221 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
222 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
223 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
224 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
225 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
226 0 0.84795330E-02 0.69040512E-07 60.838472  
227 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
228 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
229 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
230 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
231 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
232 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
233 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
234 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
235 0 0.84795330E-02 0.69040512E-07 60.838472  
236 7 -0.12284012E-08 -0.14175937E-15 0.90913404E-14 -0.95703408E-16
237 6 0.94645076E-05 0.65252983E-08 0.31788545E-02 -0.26666895E-04
238 5 -0.68547975E-03 0.38695660E-05 -0.22309841 0.19506234E-02
239 4 0.15796080E-01 0.17623363E-03 4.8191151 -0.45164717E-01
240 3 -0.13878962 0.14022659E-02 -37.962486 0.39800239
241 2 0.49290750 0.23337621E-02 116.36925 -1.4164051
242 1 -0.71149158 0.71162911E-03 -143.83978 2.0479300
243 0 0.34689854 0.17148853E-04 60.838472  
244 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
245 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
246 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
247 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
248 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
249 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
250 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
251 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
252 0 0.84795330E-02 0.69040512E-07 60.838472  
253 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
254 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
255 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
256 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
257 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
258 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
259 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
260 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
261 0 0.84795330E-02 0.69040512E-07 60.838472  
262 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
263 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
264 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
265 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
266 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
267 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
268 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
269 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
270 0 0.84795330E-02 0.69040512E-07 60.838472  
271 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
272 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
273 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
274 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
275 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
276 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
277 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
278 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
279 0 0.84795330E-02 0.69040512E-07 60.838472  
280 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
281 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
282 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
283 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
284 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
285 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
286 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
287 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
288 0 0.84795330E-02 0.69040512E-07 60.838472  
289 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
290 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
291 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
292 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
293 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
294 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
295 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
296 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
297 0 0.84795330E-02 0.69040512E-07 60.838472  
298 7 -0.14808798E-08 -0.23949551E-15 0.12272327E-13 -0.18246766E-15
299 6 0.78929210E-05 0.54311228E-08 0.31833161E-02 -0.26704323E-04
300 5 -0.57017740E-03 0.32179232E-05 -0.22335205 0.19528622E-02
301 4 0.13131138E-01 0.14653030E-03 4.8233405 -0.45205333E-01
302 3 -0.11535542 0.11655739E-02 -37.986361 0.39826627
303 2 0.40966171 0.19396166E-02 116.41572 -1.4170267
304 1 -0.59132034 0.59108368E-03 -143.86714 2.0483797
305 0 0.28830555 0.14332557E-04 60.838472  
306 7 -0.28643491E-08 -0.16995809E-14 0.24045771E-14 -0.54933304E-16
307 6 0.42456870E-05 0.28327202E-08 0.31938794E-02 -0.26792937E-04
308 5 -0.29940489E-03 0.16755240E-05 -0.22395245 0.19581617E-02
309 4 0.68487419E-02 0.76219176E-04 4.8333410 -0.45301464E-01
310 3 -0.60022801E-01 0.60573315E-03 -38.042855 0.39889073
311 2 0.21296398 0.10071667E-02 116.52567 -1.4184974
312 1 -0.30727654 0.30661253E-03 -143.93187 2.0494436
313 0 0.14978662 0.74369660E-05 60.838472  
314 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
315 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
316 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
317 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
318 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
319 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
320 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
321 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
322 0 0.84795330E-02 0.69040512E-07 60.838472  
323 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
324 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
325 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
326 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
327 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
328 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
329 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
330 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
331 0 0.84795330E-02 0.69040512E-07 60.838472  
332 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
333 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
334 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
335 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
336 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
337 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
338 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
339 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
340 0 0.84795330E-02 0.69040512E-07 60.838472  
341 7 -0.69171128E-08 -0.77577402E-14 -0.10203795E-14 0.73488214E-17
342 6 0.21850465E-05 0.11975428E-08 0.32005764E-02 -0.26849117E-04
343 5 -0.13432513E-03 0.70277424E-06 -0.22433290 0.19615197E-02
344 4 0.29375393E-02 0.31842351E-04 4.8396738 -0.45362343E-01
345 3 -0.25306754E-01 0.25220309E-03 -38.078611 0.39928597
346 2 0.89163248E-01 0.41802523E-03 116.59524 -1.4194280
347 1 -0.12824026 0.12672127E-03 -143.97281 2.0501166
348 0 0.62410937E-01 0.30704220E-05 60.838472  
349 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
350 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
351 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
352 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
353 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
354 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
355 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
356 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
357 0 0.84795330E-02 0.69040512E-07 60.838472  
358 7 -0.12284012E-08 -0.14175932E-15 0.90913404E-14 -0.95703408E-16
359 6 0.94645076E-05 0.65252983E-08 0.31788545E-02 -0.26666895E-04
360 5 -0.68547975E-03 0.38695660E-05 -0.22309841 0.19506234E-02
361 4 0.15796080E-01 0.17623363E-03 4.8191151 -0.45164717E-01
362 3 -0.13878962 0.14022659E-02 -37.962486 0.39800239
363 2 0.49290750 0.23337621E-02 116.36925 -1.4164051
364 1 -0.71149158 0.71162911E-03 -143.83978 2.0479300
365 0 0.34689854 0.17148853E-04 60.838472  
366 7 -0.21207308E-08 -0.69128061E-15 0.45866754E-14 -0.60902148E-16
367 6 0.56000727E-05 0.38109606E-08 0.31899011E-02 -0.26759564E-04
368 5 -0.40083884E-03 0.22562489E-05 -0.22372635 0.19561660E-02
369 4 0.92084614E-02 0.10268861E-03 4.8295754 -0.45265267E-01
370 3 -0.80828076E-01 0.81646647E-03 -38.021585 0.39865561
371 2 0.28695633 0.13581156E-02 116.48428 -1.4179437
372 1 -0.41414885 0.41367783E-03 -143.90750 2.0490431
373 0 0.20191061 0.10030641E-04 60.838472  
374 7 -0.57130047E-08 -0.13239772E-13 0.10905418E-14 -0.28047254E-16
375 6 0.24479969E-05 0.14397793E-08 0.31995727E-02 -0.26840697E-04
376 5 -0.15790103E-03 0.84743722E-06 -0.22427591 0.19610167E-02
377 4 0.35113992E-02 0.38452882E-04 4.8387258 -0.45353229E-01
378 3 -0.30448793E-01 0.30493823E-03 -38.073262 0.39922684
379 2 0.10756931 0.50601438E-03 116.58484 -1.4192888
380 1 -0.15490371 0.15363679E-03 -143.96669 2.0500160
381 0 0.75434867E-01 0.37234106E-05 60.838472  
382 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
383 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
384 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
385 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
386 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
387 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
388 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
389 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
390 0 0.84795330E-02 0.69040512E-07 60.838472  
391 7 -0.16745635E-08 -0.34336014E-15 0.84355089E-14 -0.11966027E-15
392 6 0.70109463E-05 0.48099747E-08 0.31858354E-02 -0.26725457E-04
393 5 -0.50524852E-03 0.28501127E-05 -0.22349525 0.19541262E-02
394 4 0.11628654E-01 0.12975345E-03 4.8257261 -0.45228265E-01
395 3 -0.10213633 0.10320045E-02 -37.999839 0.39841525
396 2 0.36269187 0.17170067E-02 116.44195 -1.4173776
397 1 -0.52350793 0.52328400E-03 -143.88258 2.0486336
398 0 0.25523951 0.12640358E-04 60.838472  
399 7 -0.24181773E-08 -0.10221181E-14 0.55753694E-14 -0.89228560E-16
400 6 0.49546107E-05 0.33478439E-08 0.31917839E-02 -0.26775358E-04
401 5 -0.35271260E-03 0.19813498E-05 -0.22383336 0.19571105E-02
402 4 0.80903338E-02 0.90158653E-04 4.8313577 -0.45282399E-01
403 3 -0.70974666E-01 0.71670983E-03 -38.031653 0.39876690
404 2 0.25192080 0.11919822E-02 116.50387 -1.4182058
405 1 -0.36354954 0.36299642E-03 -143.91904 2.0492327
406 0 0.17723347 0.88027183E-05 60.838472  
407 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
408 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
409 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
410 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
411 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
412 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
413 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
414 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
415 0 0.84795330E-02 0.69040512E-07 60.838472  
416 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
417 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
418 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
419 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
420 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
421 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
422 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
423 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
424 0 0.84795330E-02 0.69040512E-07 60.838472  
425 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
426 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
427 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
428 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
429 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
430 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
431 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
432 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
433 0 0.84795330E-02 0.69040512E-07 60.838472  
434 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
435 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
436 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
437 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
438 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
439 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
440 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
441 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
442 0 0.84795330E-02 0.69040512E-07 60.838472  
443 7 -0.10957602E-08 -0.10446318E-15 0.58604438E-14 -0.67988962E-16
444 6 0.10581855E-04 0.72990064E-08 0.31756983E-02 -0.26640419E-04
445 5 -0.76724133E-03 0.43303693E-05 -0.22291898 0.19490397E-02
446 4 0.17683915E-01 0.19724498E-03 4.8161256 -0.45135981E-01
447 3 -0.15538261 0.15697371E-02 -37.945594 0.39781568
448 2 0.55183826 0.26127204E-02 116.33636 -1.4159652
449 1 -0.79655301 0.79695091E-03 -143.82042 2.0476118
450 0 0.38837024 0.19147965E-04 60.838472  
451 7 -0.11341741E-07 0.17465777E-14 -0.11013965E-13 0.16610245E-15
452 6 0.18605007E-05 0.75608361E-09 0.32024496E-02 -0.26864831E-04
453 5 -0.94515678E-04 0.43724092E-06 -0.22443913 0.19624575E-02
454 4 0.19105981E-02 0.19657251E-04 4.8414387 -0.45379313E-01
455 3 -0.15927185E-01 0.15470923E-03 -38.088559 0.39939597
456 2 0.55338944E-01 0.25485055E-03 116.61457 -1.4196866
457 1 -0.79079009E-01 0.76679519E-04 -143.98418 2.0503034
458 0 0.38357486E-01 0.18329447E-05 60.838472  
459 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
460 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
461 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
462 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
463 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
464 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
465 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
466 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
467 0 0.84795330E-02 0.69040512E-07 60.838472  
468 7 -0.20617138E-08 -0.63827742E-15 0.79901203E-14 -0.11974232E-15
469 6 0.57509578E-05 0.39182634E-08 0.31894635E-02 -0.26755893E-04
470 5 -0.41204887E-03 0.23201804E-05 -0.22370148 0.19559464E-02
471 4 0.94686263E-02 0.10560089E-03 4.8291611 -0.45261284E-01
472 3 -0.83119792E-01 0.83966347E-03 -38.019245 0.39862975
473 2 0.29510348 0.13967212E-02 116.47972 -1.4178828
474 1 -0.42591419 0.42548700E-03 -143.90482 2.0489990
475 0 0.20764828 0.10304016E-04 60.838472  
476 7 -0.19720080E-08 -0.56222455E-15 0.71895331E-14 -0.10475809E-15
477 6 0.59980349E-05 0.40937398E-08 0.31887486E-02 -0.26749895E-04
478 5 -0.43037878E-03 0.24246149E-05 -0.22366084 0.19555878E-02
479 4 0.98938404E-02 0.11035919E-03 4.8284843 -0.45254778E-01
480 3 -0.86864713E-01 0.87756038E-03 -38.015421 0.39858748
481 2 0.30841581 0.14598055E-02 116.47228 -1.4177832
482 1 -0.44513792 0.44476903E-03 -143.90044 2.0489270
483 0 0.21702305 0.10756423E-04 60.838472  
484 7 -0.22694539E-08 -0.84863991E-15 0.55469534E-14 -0.83853025E-16
485 6 0.52555408E-05 0.35649316E-08 0.31909037E-02 -0.26767974E-04
486 5 -0.37518838E-03 0.21098061E-05 -0.22378334 0.19566690E-02
487 4 0.86127835E-02 0.96016712E-04 4.8305245 -0.45274390E-01
488 3 -0.75579620E-01 0.76333077E-03 -38.026946 0.39871488
489 2 0.26829589 0.12696698E-02 116.49471 -1.4180833
490 1 -0.38719983 0.38664225E-03 -143.91364 2.0491441
491 0 0.18876788 0.93971978E-05 60.838472  
492 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
493 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
494 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
495 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
496 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
497 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
498 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
499 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
500 0 0.84795330E-02 0.69040512E-07 60.838472  
501 7 -0.28643491E-08 -0.16995809E-14 0.24045772E-14 -0.54933306E-16
502 6 0.42456870E-05 0.28327202E-08 0.31938794E-02 -0.26792937E-04
503 5 -0.29940489E-03 0.16755240E-05 -0.22395245 0.19581617E-02
504 4 0.68487419E-02 0.76219176E-04 4.8333410 -0.45301464E-01
505 3 -0.60022801E-01 0.60573315E-03 -38.042855 0.39889073
506 2 0.21296398 0.10071667E-02 116.52567 -1.4184974
507 1 -0.30727654 0.30661253E-03 -143.93187 2.0494436
508 0 0.14978662 0.74369660E-05 60.838472  
509 7 -0.12284012E-08 -0.14175855E-15 0.90913404E-14 -0.95703408E-16
510 6 0.94645076E-05 0.65252983E-08 0.31788545E-02 -0.26666895E-04
511 5 -0.68547975E-03 0.38695660E-05 -0.22309841 0.19506234E-02
512 4 0.15796080E-01 0.17623363E-03 4.8191151 -0.45164717E-01
513 3 -0.13878962 0.14022659E-02 -37.962486 0.39800239
514 2 0.49290750 0.23337621E-02 116.36925 -1.4164051
515 1 -0.71149158 0.71162911E-03 -143.83978 2.0479300
516 0 0.34689854 0.17148853E-04 60.838472  
517 7 -0.60380197E-09 -0.32537531E-16 0.26517167E-14 0.11835187E-18
518 6 0.18999490E-04 0.13040612E-07 0.31521841E-02 -0.26443161E-04
519 5 -0.13801921E-02 0.77584874E-05 -0.22158187 0.19372379E-02
520 4 0.31804274E-01 0.35369747E-03 4.7938436 -0.44921804E-01
521 3 -0.27934588 0.28182451E-02 -37.819662 0.39642382
522 2 0.99184117 0.46937988E-02 116.09119 -1.4126859
523 1 -1.4314662 0.14346442E-02 -143.67607 2.0452390
524 0 0.69786981 0.33851636E-04 60.838472  
525 7 -0.66108114E-09 -0.33486930E-16 0.25903973E-14 0.49093329E-17
526 6 0.17379187E-04 0.11958821E-07 0.31566813E-02 -0.26480888E-04
527 5 -0.12624999E-02 0.71026258E-05 -0.22183764 0.19394954E-02
528 4 0.29096691E-01 0.32381118E-03 4.7981065 -0.44962778E-01
529 3 -0.25559347 0.25791697E-02 -37.843758 0.39669013
530 2 0.90756470 0.42960940E-02 116.13810 -1.4133134
531 1 -1.3098814 0.13114524E-02 -143.70369 2.0456931
532 0 0.63860776 0.31506934E-04 60.838472  
533 7 -0.60380197E-09 -0.32537060E-16 0.26517167E-14 0.11835167E-18
534 6 0.18999490E-04 0.13040612E-07 0.31521841E-02 -0.26443161E-04
535 5 -0.13801921E-02 0.77584874E-05 -0.22158187 0.19372379E-02
536 4 0.31804274E-01 0.35369747E-03 4.7938436 -0.44921804E-01
537 3 -0.27934588 0.28182451E-02 -37.819662 0.39642382
538 2 0.99184117 0.46937988E-02 116.09119 -1.4126859
539 1 -1.4314662 0.14346442E-02 -143.67607 2.0452390
540 0 0.69786981 0.33851636E-04 60.838472  
541 7 -0.60380197E-09 -0.32536956E-16 0.26517167E-14 0.11835186E-18
542 6 0.18999490E-04 0.13040612E-07 0.31521841E-02 -0.26443161E-04
543 5 -0.13801921E-02 0.77584874E-05 -0.22158187 0.19372379E-02
544 4 0.31804274E-01 0.35369747E-03 4.7938436 -0.44921804E-01
545 3 -0.27934588 0.28182451E-02 -37.819662 0.39642382
546 2 0.99184117 0.46937988E-02 116.09119 -1.4126859
547 1 -1.4314662 0.14346442E-02 -143.67607 2.0452390
548 0 0.69786981 0.33851636E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.29_SHGC_0.4 30 1 VerySmooth 1.647 0.395 0.315 0.441


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   4.26414E-002 0.31435 0.48879 0.48879 0.44000 0.13397 0.17027 0.00000 0.84000 0.84000 9.85326E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Calculation Method Value {days} Allowable Number Figures in Shadow Overlap {} Polygon Clipping Algorithm Sky Diffuse Modeling Algorithm External Shading Calculation Method Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 AverageOverDaysInFrequency 30 15000 SutherlandHodgman SimpleSkyDiffuseModeling InternalCalculation No No No


Zone/Window Adjacency Daylighting Counts

Zone Name Number of Exterior Windows Number of Exterior Windows in Adjacent Zones
1 FLOOR 2 CONFERENCE 2 0
2 FLOOR 2 OFFICE 4 0
3 FLOOR 2 RECEPTION 3 0
4 FLOOR 3 LOUNGE 2 0
5 FLOOR 3 OFFICE 7 0


Zone/Window Adjacency Daylighting Matrix

Zone Name Number of Adjacent Zones with Windows Adjacent Zone Names - 1st 100 (max)
1 FLOOR 2 CONFERENCE 0  
2 FLOOR 2 OFFICE 0  
3 FLOOR 2 RECEPTION 0  
4 FLOOR 3 LOUNGE 0  
5 FLOOR 3 OFFICE 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.7570 58614.2 0.000 0.0000


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 4161C8 0 0.00 0.00 0.00 0 3.05 2.74 3.14 0.27 0 No No
2 1AD133 0 0.00 0.00 0.00 0 3.05 2.74 3.14 0.27 0 No No
3 330DF9 0 0.00 0.00 0.00 0 3.05 2.74 3.14 0.27 0 No No
4 481E71 0 473.81 134.43 9.14 0 3.05 2.74 3.14 0.27 3 No No
5 78F987 0 473.81 134.43 9.14 0 3.05 2.74 3.14 0.27 2 No No
6 FLOOR 1 ANESTHESIA SLAB 0 0.00 0.00 0.00 0 3.05 2.74 3.14 0.27 0 No No
7 DDCF3E 0 0.00 0.00 0.00 0 3.05 2.74 3.14 0.27 0 No No
8 BE1AE1 0 0.00 0.00 0.00 0 3.05 2.74 3.14 0.27 0 No No
9 FLOOR 1 ANESTHESIA_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.74 3.14 0.27 0 No No
10 70DAD1 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
11 32CC19 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
12 BBEE0B 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
13 F951A6 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
14 FLOOR 1 BIO HAZ SLAB 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
15 F6F6C6 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
16 FLOOR 1 BIO HAZ_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
17 5F762C 0 473.81 134.43 9.14 0 3.05 6.10 6.24 0.48 4 No No
18 D8037E 0 473.81 134.43 9.14 0 3.05 6.10 6.24 0.48 1 No No
19 4507E9 0 0.00 0.00 0.00 0 3.05 6.10 6.24 0.48 0 No No
20 C48E94 0 0.00 0.00 0.00 0 3.05 6.10 6.24 0.48 0 No No
21 6B31A8 0 0.00 0.00 0.00 0 3.05 6.10 6.24 0.48 0 No No
22 368E02 0 0.00 0.00 0.00 0 3.05 6.10 6.24 0.48 0 No No
23 FLOOR 1 CAFE SLAB 0 0.00 0.00 0.00 0 3.05 6.10 6.24 0.48 0 No No
24 4783F2 0 0.00 0.00 0.00 0 3.05 6.10 6.24 0.48 0 No No
25 FLOOR 1 CAFE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.10 6.24 0.48 0 No No
26 EA8FA7 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
27 FE7511 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
28 59E0E4 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
29 7949FA 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
30 FLOOR 1 CLEAN SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
31 EC2478 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
32 1B4EDC 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
33 D1AFC9 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
34 442699 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
35 FLOOR 1 CLEAN_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
36 FD8CF2 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
37 49DA86 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
38 619EE6 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
39 B551AD 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
40 FLOOR 1 CLEAN WORK SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
41 8E9267 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
42 BB097B 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
43 2E1FB7 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
44 FLOOR 1 CLEAN WORK_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.87 -999.00 0 No No
45 94A56A 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
46 4A854B 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
47 8594D3 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
48 86244A 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
49 FLOOR 1 DICTATION SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
50 672F1E 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
51 A7115C 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
52 AF27F8 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
53 FLOOR 1 DICTATION_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
54 256F02 0 0.00 0.00 0.00 0 3.05 2.74 1.96 0.28 0 No No
55 DE027F 0 0.00 0.00 0.00 0 3.05 2.74 1.96 0.28 0 No No
56 84FB73 0 473.81 143.75 9.14 0 3.05 2.74 1.96 0.28 3 No No
57 4A8120 0 473.81 143.75 9.14 0 3.05 2.74 1.96 0.28 2 No No
58 CC17E8 0 0.00 0.00 0.00 0 3.05 2.74 1.96 0.28 0 No No
59 FLOOR 1 DRESSING ROOM SLAB 0 0.00 0.00 0.00 0 3.05 2.74 1.96 0.28 0 No No
60 5DACB5 0 0.00 0.00 0.00 0 3.05 2.74 1.96 0.28 0 No No
61 FLOOR 1 DRESSING ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.74 1.96 0.28 0 No No
62 9879B2 0 0.00 0.00 0.00 0 3.05 2.13 2.84 0.00 0 No No
63 2D53AC 0 0.00 0.00 0.00 0 3.05 2.13 2.84 0.00 0 No No
64 7F5C82 0 302.86 143.75 9.14 0 3.05 2.13 2.84 0.00 0 No No
65 E82152 0 0.00 0.00 0.00 0 3.05 2.13 2.84 0.00 0 No No
66 FLOOR 1 ELECTRICAL ROOM SLAB 0 0.00 0.00 0.00 0 3.05 2.13 2.84 0.00 0 No No
67 D7AC92 0 0.00 0.00 0.00 0 3.05 2.13 2.84 0.00 0 No No
68 FLOOR 1 ELECTRICAL ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.13 2.84 0.00 0 No No
69 F99476 0 0.00 0.00 0.00 0 3.05 6.10 2.77 0.00 0 No No
70 C732B0 0 473.81 143.75 9.14 0 3.05 6.10 2.77 0.00 0 No No
71 9926F7 0 0.00 0.00 0.00 0 3.05 6.10 2.77 0.00 0 No No
72 E02487 0 302.86 110.86 9.14 0 3.05 6.10 2.77 0.00 0 No No
73 BA05F7 0 302.86 110.86 9.14 0 3.05 6.10 2.77 0.00 0 No No
74 B45B50 0 0.00 0.00 0.00 0 3.05 6.10 2.77 0.00 0 No No
75 FLOOR 1 ELEVATOR PUMP ROOM SLAB 0 0.00 0.00 0.00 0 3.05 6.10 2.77 0.00 0 No No
76 DF9D5D 0 0.00 0.00 0.00 0 3.05 6.10 2.77 0.00 0 No No
77 827528 0 0.00 0.00 0.00 0 3.05 6.10 2.77 0.00 0 No No
78 FLOOR 1 ELEVATOR PUMP ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.10 2.77 0.00 0 No No
79 758B3C 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
80 A7F46C 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
81 3F71D3 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
82 8BB36F 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
83 FLOOR 1 HUMID SLAB 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
84 D21333 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
85 FLOOR 1 HUMID_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
86 FEC1E3 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
87 5D9E95 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
88 F4D6DD 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
89 FB87D3 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
90 445A39 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
91 3A6904 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
92 FLOOR 1 IT HALL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
93 FB17DD 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
94 8A2F34 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
95 9A5B84 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
96 FLOOR 1 IT HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.59 -999.00 0 No No
97 2CF0AA 0 0.00 0.00 0.00 0 3.05 0.00 3.10 -999.00 0 No No
98 307901 0 0.00 0.00 0.00 0 3.05 0.00 3.10 -999.00 0 No No
99 FA769A 0 0.00 0.00 0.00 0 3.05 0.00 3.10 -999.00 0 No No
100 319A6B 0 0.00 0.00 0.00 0 3.05 0.00 3.10 -999.00 0 No No
101 FLOOR 1 IT ROOM SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.10 -999.00 0 No No
102 C732D4 0 0.00 0.00 0.00 0 3.05 0.00 3.10 -999.00 0 No No
103 FLOOR 1 IT ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.10 -999.00 0 No No
104 822161 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
105 43A2A2 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
106 6FB351 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
107 8134C2 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
108 102EC4 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
109 BAD27A 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
110 5D8FAF 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
111 46E87C 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
112 3145CA 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
113 73E892 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
114 4418C4 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
115 FE5A3C 0 302.86 110.86 9.14 0 3.05 6.71 5.50 0.44 4 No No
116 AAE778 0 302.86 110.86 9.14 0 3.05 6.71 5.50 0.44 1 No No
117 F67E1F 0 302.86 110.86 9.14 0 3.05 6.71 5.50 0.44 0 No No
118 4911A5 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
119 FLOOR 1 LOBBY SLAB 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
120 D647E0 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
121 BFB8E1 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
122 78FEE8 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
123 FLOOR 1 LOBBY_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 5.50 0.44 0 No No
124 A6D45E 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
125 F7F8BA 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
126 34019D 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
127 72A819 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
128 FLOOR 1 LOBBY HALL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
129 D60B94 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
130 B7E9B3 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
131 690A91 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
132 FLOOR 1 LOBBY HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 4.57 -999.00 0 No No
133 9FF31D 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
134 9D87EC 0 302.86 110.86 9.14 0 3.05 1.83 2.19 0.00 0 No No
135 F23EB6 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
136 7F6FC2 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
137 88CB69 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
138 FLOOR 1 LOBBY TOILET SLAB 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
139 9BB388 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
140 FLOOR 1 LOBBY TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
141 E9F3F6 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
142 A9C27A 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
143 F629C1 0 473.81 143.75 9.14 0 3.05 6.71 7.74 0.27 3 No No
144 3AAD8B 0 473.81 143.75 9.14 0 3.05 6.71 7.74 0.27 2 No No
145 8128A9 0 473.81 143.75 9.14 0 3.05 6.71 7.74 0.27 2 No No
146 962DB5 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
147 92E22C 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
148 FLOOR 1 LOCKER ROOM SLAB 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
149 7B1677 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
150 21C5E8 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
151 FDCEC5 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
152 C1F15F 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
153 1E6611 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
154 FLOOR 1 LOCKER ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 7.74 0.27 0 No No
155 35028C 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
156 852027 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
157 EBFE47 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
158 D9965C 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
159 71783C 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
160 D8C098 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
161 66D163 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
162 8D03E8 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
163 9A0DF2 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
164 FLOOR 1 LOCKER ROOM HALL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
165 1891E7 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
166 BD75DE 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
167 3137C4 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
168 C8F2F1 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
169 6B171C 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
170 86C171 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
171 C605B5 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
172 FLOOR 1 LOCKER ROOM HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
173 18AFE3 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
174 761D33 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
175 9C0202 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
176 29BD5F 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
177 897BAF 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
178 3E6044 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
179 FLOOR 1 LOUNGE SLAB 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
180 7B9EEC 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
181 B04E85 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
182 FLOOR 1 LOUNGE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 5.23 -999.00 0 No No
183 A4B378 0 0.00 0.00 0.00 0 3.05 4.57 2.28 0.00 0 No No
184 72BCFE 0 0.00 0.00 0.00 0 3.05 4.57 2.28 0.00 0 No No
185 E85BB5 0 473.81 143.75 9.14 0 3.05 4.57 2.28 0.00 0 No No
186 7EB6E7 0 473.81 143.75 9.14 0 3.05 4.57 2.28 0.00 0 No No
187 577FC1 0 302.86 143.75 9.14 0 3.05 4.57 2.28 0.00 0 No No
188 FLOOR 1 MED GAS SLAB 0 0.00 0.00 0.00 0 3.05 4.57 2.28 0.00 0 No No
189 FLOOR 1 MED GAS ROOF 0 1373.29 114.97 6.10 0 3.05 4.57 2.28 0.00 0 No No
190 FLOOR 1 MED GAS_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 4.57 2.28 0.00 0 No No
191 F0B690 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
192 D2C53A 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
193 BFD4BB 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
194 C114C1 0 473.81 143.75 9.14 0 3.05 1.52 3.53 0.00 0 No No
195 D18914 0 473.81 143.75 9.14 0 3.05 1.52 3.53 0.00 0 No No
196 92A2CB 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
197 1EC3A0 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
198 E66ECE 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
199 FLOOR 1 MRI CONTROL ROOM SLAB 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
200 290CAB 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
201 FLOOR 1 MRI CONTROL ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.52 3.53 0.00 0 No No
202 824665 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
203 68F53B 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
204 27B0D7 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
205 90FDA9 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
206 91DE28 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
207 A8DB72 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
208 8A30DD 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
209 596DE0 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
210 B92155 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
211 FLOOR 1 MRI HALL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
212 5CB500 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
213 FLOOR 1 MRI HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.20 -999.00 0 No No
214 2FAF44 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
215 A78253 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
216 E5BC3F 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
217 867BBB 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
218 F3084E 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
219 BA91C7 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
220 FLOOR 1 MRI ROOM SLAB 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
221 803791 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
222 FLOOR 1 MRI ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 6.39 -999.00 0 No No
223 ADB8D0 0 473.81 143.75 9.14 0 3.05 1.83 2.19 0.00 0 No No
224 30DB21 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
225 C9D24D 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
226 4ED109 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
227 24139C 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
228 FLOOR 1 MRI TOILET SLAB 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
229 388F10 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
230 FLOOR 1 MRI TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
231 855191 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
232 C0F51F 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
233 A59907 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
234 28DE5A 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
235 58B6B6 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
236 725D3E 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
237 FLOOR 1 NOURISHMENT SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
238 4E5019 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
239 E8F02D 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
240 6ECCF3 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
241 AA1F5C 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
242 F665B1 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
243 FLOOR 1 NOURISHMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.36 -999.00 0 No No
244 6822BB 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
245 825233 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
246 86A28D 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
247 C92A6E 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
248 114EC6 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
249 9EB05A 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
250 7434CD 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
251 344D34 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
252 59CEFB 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
253 FLOOR 1 NURSE HALL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
254 C75191 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
255 92E327 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
256 7F6B1B 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
257 4A49C1 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
258 8F5FFC 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
259 DDBA1E 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
260 FLOOR 1 NURSE HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 4.32 -999.00 0 No No
261 4E3BB5 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
262 415590 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
263 D9F81F 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
264 E1B4BB 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
265 FLOOR 1 NURSE JANITOR SLAB 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
266 2CB843 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
267 E2AB17 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
268 FLOOR 1 NURSE JANITOR_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
269 464A53 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
270 FE5062 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
271 4A07CD 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
272 EE0803 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
273 DFDE4F 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
274 A452BE 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
275 FLOOR 1 NURSE STATION SLAB 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
276 BD4B70 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
277 A0117C 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
278 52F395 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
279 AA2E8F 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
280 FLOOR 1 NURSE STATION_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 4.19 -999.00 0 No No
281 CA6EDA 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
282 5EB34C 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
283 5CD67D 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
284 E5CB03 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
285 FLOOR 1 NURSE TOILET SLAB 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
286 156F92 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
287 FLOOR 1 NURSE TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.19 -999.00 0 No No
288 361D65 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
289 2B5816 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
290 7B67EC 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
291 7E0561 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
292 4E24F1 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
293 8259AE 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
294 FLOOR 1 OFFICE SLAB 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
295 B754EC 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
296 621A74 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
297 28F0DE 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
298 FLOOR 1 OFFICE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 6.69 -999.00 0 No No
299 879583 0 473.81 134.43 9.14 0 3.05 13.11 6.52 0.22 3 No No
300 9B1541 0 473.81 134.43 9.14 0 3.05 13.11 6.52 0.22 2 No No
301 CF850A 0 473.81 134.43 9.14 0 3.05 13.11 6.52 0.22 2 No No
302 83A098 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.22 0 No No
303 E326E4 0 302.86 143.75 9.14 0 3.05 13.11 6.52 0.22 3 No No
304 A6BA23 0 302.86 143.75 9.14 0 3.05 13.11 6.52 0.22 2 No No
305 D10D28 0 302.86 143.75 9.14 0 3.05 13.11 6.52 0.22 2 No No
306 D4B39B 0 302.86 143.75 9.14 0 3.05 13.11 6.52 0.22 0 No No
307 575A7B 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.22 0 No No
308 7E9E26 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.22 0 No No
309 FLOOR 1 OPERATING ROOM 1 SLAB 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.22 0 No No
310 E648BC 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.22 0 No No
311 FFE052 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.22 0 No No
312 611A3F 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.22 0 No No
313 FLOOR 1 OPERATING ROOM 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 6.52 0.22 0 No No
314 9C6F66 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.30 0 No No
315 1D96D7 0 302.86 143.75 9.14 0 3.05 7.32 6.65 0.30 3 No No
316 591336 0 302.86 143.75 9.14 0 3.05 7.32 6.65 0.30 2 No No
317 38B811 0 302.86 143.75 9.14 0 3.05 7.32 6.65 0.30 2 No No
318 C044D6 0 302.86 143.75 9.14 0 3.05 7.32 6.65 0.30 2 No No
319 A2AAC5 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.30 0 No No
320 1747DE 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.30 0 No No
321 F4C599 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.30 0 No No
322 964F72 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.30 0 No No
323 FLOOR 1 OPERATING ROOM 2 SLAB 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.30 0 No No
324 726F67 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.30 0 No No
325 406D70 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.30 0 No No
326 368A44 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.30 0 No No
327 FLOOR 1 OPERATING ROOM 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 7.32 6.65 0.30 0 No No
328 9E12D4 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
329 FD0958 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
330 AE206C 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
331 966665 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
332 52CA89 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
333 FLOOR 1 OPERATING ROOM 3 SLAB 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
334 8F1C77 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
335 18AD08 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
336 69AE66 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
337 CF6C6E 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
338 678B62 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
339 FLOOR 1 OPERATING ROOM 3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 6.45 -999.00 0 No No
340 2B4DBD 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
341 FCD8D2 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
342 F740DF 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
343 446771 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
344 A2F014 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
345 FLOOR 1 PACU SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
346 995832 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
347 FLOOR 1 PACU_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.14 -999.00 0 No No
348 33A280 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
349 BABBB4 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
350 F9B592 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
351 6E46A9 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
352 BA8FF7 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
353 25B45C 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
354 592524 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
355 EAACE4 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
356 3AE420 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
357 414FE2 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
358 DEAC23 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
359 22DAE3 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
360 FLOOR 1 PRE-OP HALL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
361 388CB3 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
362 FB3834 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
363 343C52 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
364 E63CF4 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
365 D6D2A5 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
366 83172E 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
367 8FE324 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
368 FLOOR 1 PRE-OP HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 4.35 -999.00 0 No No
369 4DA0F5 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
370 8F966C 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
371 FA21EE 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
372 5B255F 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
373 84418A 0 302.86 110.86 9.14 0 3.05 1.22 3.84 0.00 0 No No
374 FLOOR 1 PRE-OP ROOM 1 SLAB 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
375 3C43B2 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
376 BC6EE7 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
377 363652 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
378 FLOOR 1 PRE-OP ROOM 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.22 3.84 0.00 0 No No
379 551E65 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
380 8C3884 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
381 9853A2 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
382 7AE5B9 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
383 FLOOR 1 PRE-OP ROOM 2 SLAB 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
384 39AFEA 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
385 CABD0E 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
386 AF38CF 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
387 C0A312 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
388 661D88 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
389 AFFD01 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
390 FLOOR 1 PRE-OP ROOM 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 5.28 -999.00 0 No No
391 2DEB73 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
392 7D08C0 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
393 36E420 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
394 1535AC 0 302.86 110.86 9.14 0 3.05 1.83 2.19 0.00 0 No No
395 FLOOR 1 PRE-OP TOILET SLAB 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
396 97616F 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
397 FLOOR 1 PRE-OP TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
398 95486C 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
399 EAE60F 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
400 6D2616 0 473.81 143.75 9.14 0 3.05 5.79 5.11 0.32 3 No No
401 1D94BE 0 473.81 143.75 9.14 0 3.05 5.79 5.11 0.32 2 No No
402 18748E 0 473.81 143.75 9.14 0 3.05 5.79 5.11 0.32 2 No No
403 704EC3 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
404 E20721 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
405 FA9EF2 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
406 FLOOR 1 PROCEDURE ROOM SLAB 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
407 673317 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
408 E5C1C9 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
409 79376C 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
410 FLOOR 1 PROCEDURE ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 5.79 5.11 0.32 0 No No
411 6EA718 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
412 2730E5 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
413 E608B9 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
414 25AB11 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
415 5A39B1 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
416 234734 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
417 57B162 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
418 7BB928 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
419 A5A6A3 0 473.81 134.43 9.14 0 3.05 3.96 5.09 0.28 3 No No
420 137A56 0 473.81 134.43 9.14 0 3.05 3.96 5.09 0.28 2 No No
421 FLOOR 1 RECEPTION SLAB 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
422 A02892 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
423 9114B7 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
424 700E69 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
425 FLOOR 1 RECEPTION_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.96 5.09 0.28 0 No No
426 11E9BF 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
427 839A66 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
428 FE2C3E 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
429 CD7BAD 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
430 6A1AB7 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
431 FLOOR 1 RECEPTION HALL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
432 68AAF3 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
433 DE014E 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
434 709E99 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
435 FLOOR 1 RECEPTION HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.25 -999.00 0 No No
436 28B002 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 3 No No
437 8D508E 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 2 No No
438 B2D381 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 2 No No
439 1DA13A 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 2 No No
440 44E54A 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 2 No No
441 D2D3BC 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 0 No No
442 C528DA 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 0 No No
443 EFD3F9 0 473.81 134.43 9.14 0 3.05 13.72 5.78 0.21 0 No No
444 F4FE92 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
445 66B6F7 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
446 72C4ED 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
447 FLOOR 1 RECOVERY ROOM SLAB 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
448 C5ECA6 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
449 65D500 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
450 AE5EBC 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
451 2A1A9E 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
452 FLOOR 1 RECOVERY ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.72 5.78 0.21 0 No No
453 EA6DC8 0 473.81 134.43 9.14 0 3.05 2.13 3.02 0.11 3 No No
454 757D10 0 473.81 134.43 9.14 0 3.05 2.13 3.02 0.11 2 No No
455 612A96 0 0.00 0.00 0.00 0 3.05 2.13 3.02 0.11 0 No No
456 BDC047 0 0.00 0.00 0.00 0 3.05 2.13 3.02 0.11 0 No No
457 42E287 0 0.00 0.00 0.00 0 3.05 2.13 3.02 0.11 0 No No
458 FLOOR 1 SCHEDULING SLAB 0 0.00 0.00 0.00 0 3.05 2.13 3.02 0.11 0 No No
459 513564 0 0.00 0.00 0.00 0 3.05 2.13 3.02 0.11 0 No No
460 58F893 0 0.00 0.00 0.00 0 3.05 2.13 3.02 0.11 0 No No
461 FLOOR 1 SCHEDULING_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.13 3.02 0.11 0 No No
462 7816FD 0 0.00 0.00 0.00 0 3.05 0.00 2.56 -999.00 0 No No
463 1B2EF8 0 0.00 0.00 0.00 0 3.05 0.00 2.56 -999.00 0 No No
464 24EAE3 0 0.00 0.00 0.00 0 3.05 0.00 2.56 -999.00 0 No No
465 9DB411 0 0.00 0.00 0.00 0 3.05 0.00 2.56 -999.00 0 No No
466 FLOOR 1 SCRUB SLAB 0 0.00 0.00 0.00 0 3.05 0.00 2.56 -999.00 0 No No
467 7008C0 0 0.00 0.00 0.00 0 3.05 0.00 2.56 -999.00 0 No No
468 FLOOR 1 SCRUB_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.56 -999.00 0 No No
469 762F8C 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
470 5D199F 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
471 ACADA4 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
472 4398AD 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
473 9E478E 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
474 6B967C 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
475 FLOOR 1 SOIL SLAB 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
476 4B54B4 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
477 88D2F8 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
478 7274F6 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
479 FLOOR 1 SOIL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.34 -999.00 0 No No
480 A1087A 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
481 41CE25 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
482 9A776E 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
483 9ABA5B 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
484 FLOOR 1 SOIL HOLD SLAB 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
485 58A74A 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
486 D78A26 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
487 FLOOR 1 SOIL HOLD_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
488 37E2C7 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
489 23683B 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
490 CA9655 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
491 121DFF 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
492 FAE342 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
493 FLOOR 1 SOIL WORK SLAB 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
494 A44272 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
495 B9DDBA 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
496 9EBF3E 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
497 903092 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
498 FLOOR 1 SOIL WORK_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 4.06 -999.00 0 No No
499 5FD018 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
500 809229 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
501 B40F89 0 302.86 110.86 9.14 0 3.05 11.28 4.94 0.19 3 No No
502 E33BAE 0 302.86 110.86 9.14 0 3.05 11.28 4.94 0.19 2 No No
503 997723 0 473.81 134.43 9.14 0 3.05 11.28 4.94 0.19 3 No No
504 24167A 0 473.81 134.43 9.14 0 3.05 11.28 4.94 0.19 2 No No
505 2C0938 0 473.81 134.43 9.14 0 3.05 11.28 4.94 0.19 2 No No
506 62B5AF 0 473.81 134.43 9.14 0 3.05 11.28 4.94 0.19 0 No No
507 CA45DE 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
508 5B693D 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
509 FLOOR 1 STEP DOWN SLAB 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
510 FBDD49 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
511 4284B6 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
512 FCE842 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
513 FLOOR 1 STEP DOWN_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 11.28 4.94 0.19 0 No No
514 829DCE 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
515 E77E00 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
516 CEC7BD 0 473.81 134.43 9.14 0 3.05 2.44 4.42 0.30 3 No No
517 8600DD 0 473.81 134.43 9.14 0 3.05 2.44 4.42 0.30 2 No No
518 8C4FA5 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
519 B3A518 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
520 44686F 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
521 6A2C62 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
522 A809DD 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
523 EE0E68 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
524 88AE01 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
525 2C9CF4 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
526 765EA5 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
527 2B370E 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
528 F30797 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
529 FLOOR 1 STERILE HALL SLAB 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
530 3179A6 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
531 370DB2 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
532 34B3F0 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
533 CEDA0D 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
534 4469CD 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
535 F62393 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
536 340FB5 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
537 CDA7F8 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
538 FLOOR 1 STERILE HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.44 4.42 0.30 0 No No
539 8043B2 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
540 38F548 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
541 96662A 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
542 1003C1 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
543 863C6C 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
544 808817 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
545 EA4B61 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
546 FLOOR 1 NURSE STORAGE SLAB 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
547 C1737B 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
548 D44BF1 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
549 5C05FF 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
550 FLOOR 1 STERILE STORAGE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 5.36 -999.00 0 No No
551 707E04 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
552 8E5BB9 0 302.86 110.86 9.14 0 3.05 19.20 8.90 0.14 3 No No
553 71E924 0 302.86 110.86 9.14 0 3.05 19.20 8.90 0.14 0 No No
554 859BC1 0 473.81 143.75 9.14 0 3.05 19.20 8.90 0.14 3 No No
555 A1ED60 0 473.81 143.75 9.14 0 3.05 19.20 8.90 0.14 2 No No
556 E8D997 0 473.81 143.75 9.14 0 3.05 19.20 8.90 0.14 2 No No
557 88E1FC 0 473.81 143.75 9.14 0 3.05 19.20 8.90 0.14 2 No No
558 3C44F9 0 473.81 143.75 9.14 0 3.05 19.20 8.90 0.14 0 No No
559 49526E 0 473.81 143.75 9.14 0 3.05 19.20 8.90 0.14 0 No No
560 865AE8 0 473.81 143.75 9.14 0 3.05 19.20 8.90 0.14 0 No No
561 891195 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
562 8B4DC1 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
563 19D150 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
564 814856 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
565 5B533A 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
566 FLOOR 1 STORAGE SLAB 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
567 FLOOR 1 STORGE ROOF 0 1373.29 114.97 6.10 0 3.05 19.20 8.90 0.14 0 No No
568 FLOOR 1 STORAGE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 19.20 8.90 0.14 0 No No
569 61E610 0 302.86 143.75 9.14 0 3.05 4.27 4.27 0.23 3 No No
570 F83F33 0 302.86 143.75 9.14 0 3.05 4.27 4.27 0.23 2 No No
571 76F2F2 0 0.00 0.00 0.00 0 3.05 4.27 4.27 0.23 0 No No
572 D61127 0 0.00 0.00 0.00 0 3.05 4.27 4.27 0.23 0 No No
573 196C5F 0 0.00 0.00 0.00 0 3.05 4.27 4.27 0.23 0 No No
574 FLOOR 1 SUB-STERILE SLAB 0 0.00 0.00 0.00 0 3.05 4.27 4.27 0.23 0 No No
575 1875B3 0 0.00 0.00 0.00 0 3.05 4.27 4.27 0.23 0 No No
576 FLOOR 1 SUB-STERILE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 4.27 4.27 0.23 0 No No
577 39E49D 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
578 F43F35 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
579 89BBEB 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
580 87231D 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
581 529072 0 302.86 143.75 9.14 0 3.05 4.88 3.90 0.00 0 No No
582 5E66D1 0 302.86 143.75 9.14 0 3.05 4.88 3.90 0.00 0 No No
583 C1C64E 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
584 1D9EED 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
585 20FB14 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
586 DEFACF 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
587 FLOOR 1 UTILITY HALL SLAB 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
588 FLOOR 1 UTILITY HALL ROOF 0 1373.29 114.97 6.10 0 3.05 4.88 3.90 0.00 0 No No
589 5136E3 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
590 EFCC3C 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
591 FLOOR 1 UTILITY HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 4.88 3.90 0.00 0 No No
592 2E8328 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
593 E321D9 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
594 E89C6C 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
595 816F6D 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
596 FLOOR 1 UTILITY JANITOR SLAB 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
597 5F697A 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
598 FLOOR 1 UTILITY JANITOR_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
599 EC28A9 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.13 0 No No
600 204CB9 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.13 0 No No
601 62475F 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.13 0 No No
602 D95F04 0 302.86 143.75 9.14 0 3.05 5.49 5.78 0.13 3 No No
603 E14DAE 0 302.86 143.75 9.14 0 3.05 5.49 5.78 0.13 0 No No
604 B1F5EE 0 302.86 143.75 9.14 0 3.05 5.49 5.78 0.13 2 No No
605 87BFF9 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.13 0 No No
606 23CCB1 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.13 0 No No
607 FLOOR 1 UTILITY ROOM SLAB 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.13 0 No No
608 7DB101 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.13 0 No No
609 F28371 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.13 0 No No
610 FLOOR 1 UTILITY ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 5.49 5.78 0.13 0 No No
611 231744 0 0.00 0.00 0.00 0 3.05 2.44 2.58 0.00 0 No No
612 3330D8 0 302.86 110.86 9.14 0 3.05 2.44 2.58 0.00 0 No No
613 84A1D5 0 302.86 110.86 9.14 0 3.05 2.44 2.58 0.00 0 No No
614 2FEACD 0 0.00 0.00 0.00 0 3.05 2.44 2.58 0.00 0 No No
615 AA1709 0 0.00 0.00 0.00 0 3.05 2.44 2.58 0.00 0 No No
616 FLOOR 1 VESTIBULE SLAB 0 0.00 0.00 0.00 0 3.05 2.44 2.58 0.00 0 No No
617 C34217 0 0.00 0.00 0.00 0 3.05 2.44 2.58 0.00 0 No No
618 FLOOR 1 VESTIBULE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.44 2.58 0.00 0 No No
619 208CCF 0 302.86 143.75 9.14 0 3.05 12.19 5.12 0.24 3 No No
620 F52F3D 0 302.86 143.75 9.14 0 3.05 12.19 5.12 0.24 2 No No
621 AEF992 0 473.81 134.43 9.14 0 3.05 12.19 5.12 0.24 3 No No
622 80885D 0 473.81 134.43 9.14 0 3.05 12.19 5.12 0.24 2 No No
623 9AC2E9 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.24 0 No No
624 436189 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.24 0 No No
625 B184C1 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.24 0 No No
626 BC8EB7 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.24 0 No No
627 75353D 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.24 0 No No
628 2BD1E8 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.24 0 No No
629 240A7C 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.24 0 No No
630 FLOOR 2 CONFERENCE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 12.19 5.12 0.24 0 No No
631 F6D879 0 0.00 0.00 0.00 0 3.05 0.00 2.44 -999.00 0 No No
632 1701A6 0 0.00 0.00 0.00 0 3.05 0.00 2.44 -999.00 0 No No
633 772842 0 0.00 0.00 0.00 0 3.05 0.00 2.44 -999.00 0 No No
634 3C9825 0 0.00 0.00 0.00 0 3.05 0.00 2.44 -999.00 0 No No
635 C2CE5F 0 0.00 0.00 0.00 0 3.05 0.00 2.44 -999.00 0 No No
636 7149EA 0 0.00 0.00 0.00 0 3.05 0.00 2.44 -999.00 0 No No
637 FLOOR 2 CONFERENCE TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.44 -999.00 0 No No
638 296861 0 0.00 0.00 0.00 0 3.05 0.00 2.51 -999.00 0 No No
639 3D4DE8 0 0.00 0.00 0.00 0 3.05 0.00 2.51 -999.00 0 No No
640 8A5790 0 0.00 0.00 0.00 0 3.05 0.00 2.51 -999.00 0 No No
641 2DB420 0 0.00 0.00 0.00 0 3.05 0.00 2.51 -999.00 0 No No
642 56C7DA 0 0.00 0.00 0.00 0 3.05 0.00 2.51 -999.00 0 No No
643 E1B973 0 0.00 0.00 0.00 0 3.05 0.00 2.51 -999.00 0 No No
644 FLOOR 2 DICTATION_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.51 -999.00 0 No No
645 640E64 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
646 10E44F 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
647 54D065 0 473.81 134.43 9.14 0 3.05 12.80 5.23 0.23 3 No No
648 FEEF06 0 473.81 134.43 9.14 0 3.05 12.80 5.23 0.23 2 No No
649 1775A6 0 302.86 110.86 9.14 0 3.05 12.80 5.23 0.23 3 No No
650 2BE8DE 0 302.86 110.86 9.14 0 3.05 12.80 5.23 0.23 2 No No
651 513E2A 0 302.86 110.86 9.14 0 3.05 12.80 5.23 0.23 2 No No
652 BA5CD9 0 302.86 110.86 9.14 0 3.05 12.80 5.23 0.23 2 No No
653 6E3B28 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
654 14C7EF 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
655 5EBA9B 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
656 F24E0D 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
657 D023D9 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
658 A4BE81 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
659 FLOOR 2 EXAM 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 12.80 5.23 0.23 0 No No
660 4EE021 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
661 6ED237 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
662 97F00A 0 473.81 134.43 9.14 0 3.05 5.49 6.86 0.22 3 No No
663 1AD478 0 473.81 134.43 9.14 0 3.05 5.49 6.86 0.22 2 No No
664 ADD799 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
665 4017DC 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
666 CCAA9D 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
667 4968A2 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
668 4579A7 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
669 FDAEB8 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
670 E3B855 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
671 906F5E 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
672 FLOOR 2 EXAM 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 5.49 6.86 0.22 0 No No
673 DFA4B1 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
674 F23BF4 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
675 A497E9 0 473.81 134.43 9.14 0 3.05 7.32 8.13 0.27 3 No No
676 27F0AC 0 473.81 134.43 9.14 0 3.05 7.32 8.13 0.27 2 No No
677 26E66C 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
678 17C5CF 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
679 BA0A29 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
680 26AF41 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
681 75A3C4 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
682 BEC196 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
683 9B49F5 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
684 EB611D 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
685 C81AED 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
686 BD5B50 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
687 3AEAAB 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
688 D74115 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
689 5065F0 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
690 FLOOR 2 EXAM 3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 7.32 8.13 0.27 0 No No
691 7C84B6 0 0.00 0.00 0.00 0 3.05 2.13 2.70 0.34 0 No No
692 D88779 0 0.00 0.00 0.00 0 3.05 2.13 2.70 0.34 0 No No
693 577E2E 0 0.00 0.00 0.00 0 3.05 2.13 2.70 0.34 0 No No
694 88A75F 0 473.81 134.43 9.14 0 3.05 2.13 2.70 0.34 3 No No
695 724114 0 473.81 134.43 9.14 0 3.05 2.13 2.70 0.34 2 No No
696 4E78E0 0 0.00 0.00 0.00 0 3.05 2.13 2.70 0.34 0 No No
697 C0697F 0 0.00 0.00 0.00 0 3.05 2.13 2.70 0.34 0 No No
698 FLOOR 2 EXAM 4_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.13 2.70 0.34 0 No No
699 83B6E3 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.26 0 No No
700 AC956A 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.26 0 No No
701 B4E619 0 302.86 143.75 9.14 0 3.05 7.62 5.47 0.26 3 No No
702 D538C4 0 302.86 143.75 9.14 0 3.05 7.62 5.47 0.26 2 No No
703 5635BC 0 302.86 143.75 9.14 0 3.05 7.62 5.47 0.26 2 No No
704 BFA29B 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.26 0 No No
705 65AB67 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.26 0 No No
706 C25071 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.26 0 No No
707 31B3DF 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.26 0 No No
708 FLOOR 2 EXAM 5_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.26 0 No No
709 F29458 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
710 1EB5B1 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
711 9EC269 0 473.81 143.75 9.14 0 3.05 4.57 4.57 0.30 3 No No
712 831C1D 0 473.81 143.75 9.14 0 3.05 4.57 4.57 0.30 2 No No
713 47CE83 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
714 A8FC82 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
715 C84AE1 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
716 F67EC8 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
717 10FB67 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
718 1624C5 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
719 917AB5 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
720 FLOOR 2 EXAM 6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 4.57 4.57 0.30 0 No No
721 247258 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
722 B316F7 0 473.81 143.75 9.14 0 3.05 7.32 8.47 0.25 3 No No
723 9BB95F 0 473.81 143.75 9.14 0 3.05 7.32 8.47 0.25 2 No No
724 C0778D 0 473.81 143.75 9.14 0 3.05 7.32 8.47 0.25 2 No No
725 FF8B08 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
726 F976A9 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
727 8D6453 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
728 D1899C 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
729 5620F1 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
730 40E182 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
731 A6147C 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
732 37898A 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
733 F0D8EE 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
734 567037 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
735 6B3E65 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
736 245972 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
737 F17DF7 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
738 FLOOR 2 EXAM 7_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 7.32 8.47 0.25 0 No No
739 D7DC8D 0 0.00 0.00 0.00 0 3.05 5.49 4.99 0.33 0 No No
740 9621FD 0 473.81 143.75 9.14 0 3.05 5.49 4.99 0.33 3 No No
741 7D2D69 0 473.81 143.75 9.14 0 3.05 5.49 4.99 0.33 2 No No
742 2EF63B 0 473.81 143.75 9.14 0 3.05 5.49 4.99 0.33 2 No No
743 6A2DCE 0 0.00 0.00 0.00 0 3.05 5.49 4.99 0.33 0 No No
744 7A03ED 0 0.00 0.00 0.00 0 3.05 5.49 4.99 0.33 0 No No
745 A9A1F6 0 0.00 0.00 0.00 0 3.05 5.49 4.99 0.33 0 No No
746 DA760E 0 0.00 0.00 0.00 0 3.05 5.49 4.99 0.33 0 No No
747 FLOOR 2 EXAM 8_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 5.49 4.99 0.33 0 No No
748 42CEE1 0 473.81 143.75 9.14 0 3.05 3.66 5.36 0.25 3 No No
749 C417C0 0 473.81 143.75 9.14 0 3.05 3.66 5.36 0.25 2 No No
750 35051E 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
751 685FFA 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
752 B51929 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
753 8E5734 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
754 4E920E 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
755 87C477 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
756 5D2769 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
757 FLOOR 2 EXAM 9_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 5.36 0.25 0 No No
758 4979C8 0 473.81 134.43 9.14 0 3.05 1.83 3.05 0.00 0 No No
759 9E6B6C 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
760 DF91E0 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
761 53450D 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
762 DFCCAE 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
763 D4B714 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
764 3AE495 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
765 526C70 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
766 2C31F2 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
767 E26130 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
768 FLOOR 2 EXAM HALL 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
769 42FAB2 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
770 815D63 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
771 6713DA 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
772 8CA0BF 0 473.81 134.43 9.14 0 3.05 1.83 3.05 0.00 0 No No
773 4C8372 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
774 243E09 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
775 C94CC0 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
776 BD39AC 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
777 75EAF8 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
778 E9AEFF 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
779 FLOOR 2 EXAM HALL 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
780 479A9C 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
781 DA6040 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
782 6C95E7 0 473.81 134.43 9.14 0 3.05 1.83 3.05 0.00 0 No No
783 BC25F3 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
784 C08963 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
785 36A02A 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
786 A08A28 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
787 F87FCE 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
788 BAE3F8 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
789 D10995 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
790 D4A2A4 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
791 6C1891 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
792 FLOOR 2 EXAM HALL 3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.05 0.00 0 No No
793 46F148 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
794 F209CC 0 473.81 143.75 9.14 0 3.05 1.83 3.09 0.00 0 No No
795 E7EC3B 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
796 55191F 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
797 3947B8 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
798 3B9E2E 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
799 C2156D 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
800 5CA4CF 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
801 4AA9BC 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
802 D1E495 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
803 4180E7 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
804 FLOOR 2 EXAM HALL 4_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
805 247FD8 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
806 2E6DF0 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
807 14F382 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
808 155BD6 0 473.81 143.75 9.14 0 3.05 1.83 3.09 0.00 0 No No
809 ED8563 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
810 A1BBBE 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
811 E0C60A 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
812 772953 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
813 15A02B 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
814 B9D6E3 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
815 FLOOR 2 EXAM HALL 5_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
816 942718 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
817 D2C12A 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
818 5556EE 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
819 C5EA55 0 473.81 143.75 9.14 0 3.05 1.83 3.09 0.00 0 No No
820 D37566 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
821 E7055D 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
822 EC3BEA 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
823 D2FA45 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
824 98E1BD 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
825 5F9E13 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
826 B4F89F 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
827 FLOOR 2 EXAM HALL 6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.09 0.00 0 No No
828 8177BA 0 302.86 110.86 9.14 0 3.05 4.88 2.40 0.00 0 No No
829 5E657E 0 473.81 143.75 9.14 0 3.05 4.88 2.40 0.00 0 No No
830 4AD319 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
831 E0C0A7 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
832 5B736E 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
833 F6E6D8 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
834 FLOOR 2 JANITOR_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
835 97BB21 0 0.00 0.00 0.00 0 3.05 0.00 2.71 -999.00 0 No No
836 7620CF 0 0.00 0.00 0.00 0 3.05 0.00 2.71 -999.00 0 No No
837 680AA1 0 0.00 0.00 0.00 0 3.05 0.00 2.71 -999.00 0 No No
838 A524F1 0 0.00 0.00 0.00 0 3.05 0.00 2.71 -999.00 0 No No
839 4CDC86 0 0.00 0.00 0.00 0 3.05 0.00 2.71 -999.00 0 No No
840 B352F7 0 0.00 0.00 0.00 0 3.05 0.00 2.71 -999.00 0 No No
841 FLOOR 2 LOUNGE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.71 -999.00 0 No No
842 CBB2D7 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
843 D0731B 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
844 ECDEDB 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
845 ED1D7F 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
846 2805F0 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
847 5A7EAB 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
848 291561 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
849 4E1563 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
850 FLOOR 2 NURSE STATION 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.66 -999.00 0 No No
851 A49FCC 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
852 5DBD9D 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
853 491317 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
854 462370 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
855 9EADD8 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
856 DE8843 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
857 C45BF3 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
858 FLOOR 2 NURSE STATION 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.92 -999.00 0 No No
859 AAF377 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.24 0 No No
860 CE4555 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.24 0 No No
861 A8A4FA 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.24 0 No No
862 4B1439 0 302.86 143.75 9.14 0 3.05 12.19 6.32 0.24 3 No No
863 EB042B 0 302.86 143.75 9.14 0 3.05 12.19 6.32 0.24 2 No No
864 4C1F71 0 302.86 143.75 9.14 0 3.05 12.19 6.32 0.24 2 No No
865 D23C8B 0 302.86 143.75 9.14 0 3.05 12.19 6.32 0.24 2 No No
866 B4E4BE 0 302.86 143.75 9.14 0 3.05 12.19 6.32 0.24 2 No No
867 352740 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.24 0 No No
868 D3CF55 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.24 0 No No
869 64A2F7 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.24 0 No No
870 D1A180 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.24 0 No No
871 9BB582 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.24 0 No No
872 FLOOR 2 OFFICE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 12.19 6.32 0.24 0 No No
873 DFA16C 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
874 2884D1 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
875 CC4EB4 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
876 B2F07D 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
877 AF86E1 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
878 571934 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
879 67A7F3 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
880 24E235 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
881 AB568E 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
882 577A10 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
883 988ACA 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
884 F5AF76 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
885 4EDE0A 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
886 874DF8 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
887 8C822C 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
888 B44BE3 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
889 4F2F27 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
890 909DB9 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
891 30A09C 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
892 BFEF28 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
893 C588CC 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
894 FLOOR 2 OFFICE HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
895 23C13E 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
896 3DE7A6 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
897 4ABC66 0 473.81 134.43 9.14 0 3.05 14.94 8.69 0.37 3 No No
898 EEF55D 0 473.81 134.43 9.14 0 3.05 14.94 8.69 0.37 1 No No
899 E55A57 0 473.81 134.43 9.14 0 3.05 14.94 8.69 0.37 2 No No
900 5B04CF 0 302.86 110.86 9.14 0 3.05 14.94 8.69 0.37 4 No No
901 93D018 0 302.86 110.86 9.14 0 3.05 14.94 8.69 0.37 1 No No
902 FCDEAC 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
903 AB4E10 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
904 E7BF7F 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
905 FA00FE 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
906 14CDC6 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
907 39BFFB 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
908 167608 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
909 C39FCC 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
910 FLOOR 2 RECEPTION_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 14.94 8.69 0.37 0 No No
911 CA9485 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
912 2740BD 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
913 F0AF69 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
914 8D1BC4 0 473.81 134.43 9.14 0 3.05 2.13 3.44 0.00 0 No No
915 9CE650 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
916 EEECA3 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
917 EE34A3 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
918 CFAD9D 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
919 25F524 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
920 D79C57 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
921 93F6DE 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
922 8AA0B7 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
923 1D6CD8 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
924 427B0D 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
925 A72F04 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
926 C51FD6 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
927 3110A1 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
928 F81393 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
929 4FA380 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
930 2FE383 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
931 3F961C 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
932 4B590B 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
933 20B940 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
934 21FC9D 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
935 EB4979 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
936 A5FA3B 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
937 7A3F36 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
938 4DAEA4 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
939 B52A5D 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
940 2C7827 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
941 FLOOR 2 RECEPTION HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.13 3.44 0.00 0 No No
942 2D0A7F 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
943 E63515 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
944 B04C98 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
945 50DB3D 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
946 115AA8 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
947 CFB630 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
948 E9C76F 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
949 FLOOR 2 RECEPTION TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.07 -999.00 0 No No
950 9C568B 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
951 B76374 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
952 24DA9F 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
953 CADDAF 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
954 10830D 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
955 EF47B0 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
956 C3DB37 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
957 F631E4 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
958 93EF1F 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
959 FLOOR 2 SCHEDULING 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 5.49 -999.00 0 No No
960 9FBDA3 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
961 87BFF8 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
962 DB7F62 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
963 969F22 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
964 795751 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
965 6A14D8 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
966 E3963E 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
967 630683 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
968 4EB51A 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
969 FLOOR 2 SCHEDULING 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 5.63 -999.00 0 No No
970 390BCF 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
971 DE64CC 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
972 F6E717 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
973 58AD84 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
974 A3E3D6 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
975 ED1C1D 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
976 FLOOR 2 STORAGE 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.28 -999.00 0 No No
977 A168ED 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
978 ED650B 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
979 8E1DCD 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
980 16E41D 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
981 1C7FB1 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
982 4B217A 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
983 A3F683 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
984 430C7E 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
985 FLOOR 2 STORAGE 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.18 -999.00 0 No No
986 70C0BF 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
987 211EA4 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
988 E0D6E9 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
989 BADB96 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
990 1E3410 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
991 695D6E 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
992 FLOOR 2 STORAGE 3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.38 -999.00 0 No No
993 97B688 0 0.00 0.00 0.00 0 3.05 2.74 3.34 0.27 0 No No
994 290DF3 0 0.00 0.00 0.00 0 3.05 2.74 3.34 0.27 0 No No
995 4B55FA 0 302.86 143.75 9.14 0 3.05 2.74 3.34 0.27 3 No No
996 DD9F5D 0 302.86 143.75 9.14 0 3.05 2.74 3.34 0.27 2 No No
997 4F0CD7 0 0.00 0.00 0.00 0 3.05 2.74 3.34 0.27 0 No No
998 4D50C0 0 0.00 0.00 0.00 0 3.05 2.74 3.34 0.27 0 No No
999 703D3E 0 0.00 0.00 0.00 0 3.05 2.74 3.34 0.27 0 No No
1000 FLOOR 2 UTILITY_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 2.74 3.34 0.27 0 No No
1001 9C3A6A 0 473.81 143.75 9.14 0 3.05 7.92 12.12 0.23 3 No No
1002 15B02B 0 473.81 143.75 9.14 0 3.05 7.92 12.12 0.23 2 No No
1003 820282 0 473.81 143.75 9.14 0 3.05 7.92 12.12 0.23 2 No No
1004 5C7E1E 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1005 B5E37D 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1006 8D1659 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1007 E88E01 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1008 4CE123 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1009 E55935 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1010 C52EE0 0 473.81 143.75 9.14 0 3.05 7.92 12.12 0.23 3 No No
1011 9AB0BF 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1012 1A8E2A 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1013 E21951 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1014 517DFC 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1015 CEC6B4 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1016 1A95D5 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1017 5724CC 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1018 7FA5FF 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1019 E43750 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1020 E9C9E1 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1021 CE626A 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1022 541C9C 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1023 F77E4B 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1024 287E3B 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1025 FLOOR 2 WORK_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 7.92 12.12 0.23 0 No No
1026 830326 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1027 EAD1EA 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1028 1C33AD 0 302.86 110.86 9.14 0 3.05 1.83 3.51 0.00 0 No No
1029 52D809 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1030 450AA9 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1031 29E445 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1032 B0FF3A 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1033 9036B9 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1034 5EE606 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1035 3FBBC8 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1036 B5099E 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1037 7A8E3F 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1038 32BAA7 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1039 738F37 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1040 B94E9A 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1041 83658D 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1042 CAC621 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1043 E90253 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1044 FD4C82 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1045 F5C927 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1046 362FF8 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1047 21F419 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1048 283EC6 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1049 C5B569 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1050 D29B01 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1051 FFE9D0 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1052 7A8C4C 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1053 957242 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1054 FLOOR 2 WORK HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1055 F22E15 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1056 49DA28 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1057 8C4550 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1058 6CC177 0 302.86 110.86 9.14 0 3.05 1.83 2.19 0.00 0 No No
1059 9969B3 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1060 4C4C25 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1061 FC3B6D 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1062 FLOOR 2 WORK TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1063 34B8D8 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1064 E74038 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1065 762874 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1066 637F6F 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1067 C6DCD1 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1068 1BDF58 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1069 15A915 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1070 1CC550 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1071 55622A 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1072 5D03DA 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1073 AE5078 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1074 774CCD 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1075 F6FE66 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1076 1DCC9F 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1077 47890C 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1078 F7E82F 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1079 7FDC1A 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1080 F02E9C 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1081 FLOOR 2 X-RAY_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 8.07 -999.00 0 No No
1082 137A14 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
1083 F2515C 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
1084 71A3C4 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
1085 46292D 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
1086 9AC2BE 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
1087 FLOOR 3 DRESSING ROOM ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 1.97 -999.00 0 No No
1088 FLOOR 3 DRESSING ROOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 1.97 -999.00 0 No No
1089 5EAFB3 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1090 E0CB0D 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1091 FB63A7 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1092 79D0A5 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1093 212961 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1094 C1AD55 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1095 B75832 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1096 F7D24D 0 473.81 143.75 9.14 0 3.05 1.22 5.01 0.00 0 No No
1097 D6F20A 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1098 FLOOR 3 ELEVATOR HALL ROOF 0 1373.29 114.97 6.10 0 3.05 1.22 5.01 0.00 0 No No
1099 FLOOR 3 ELEVATOR HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.22 5.01 0.00 0 No No
1100 C3FB92 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1101 AAD404 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1102 2272E0 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1103 E13FC4 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1104 506DC0 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1105 628387 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1106 FLOOR 3 HUMID ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 2.74 -999.00 0 No No
1107 FLOOR 3 HUMID_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1108 1D53D9 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
1109 FC22D1 0 473.81 143.75 9.14 0 3.05 4.88 2.40 0.00 0 No No
1110 DD2E2D 0 302.86 110.86 9.14 0 3.05 4.88 2.40 0.00 0 No No
1111 C4A89B 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
1112 B840A7 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
1113 FLOOR 3 JANITOR ROOF 0 1373.29 114.97 6.10 0 3.05 4.88 2.40 0.00 0 No No
1114 FLOOR 3 JANITOR_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 4.88 2.40 0.00 0 No No
1115 C86932 0 0.00 0.00 0.00 0 3.05 0.00 3.33 -999.00 0 No No
1116 B1856A 0 0.00 0.00 0.00 0 3.05 0.00 3.33 -999.00 0 No No
1117 AEA170 0 0.00 0.00 0.00 0 3.05 0.00 3.33 -999.00 0 No No
1118 82303C 0 0.00 0.00 0.00 0 3.05 0.00 3.33 -999.00 0 No No
1119 D10EC7 0 0.00 0.00 0.00 0 3.05 0.00 3.33 -999.00 0 No No
1120 FLOOR 3 LOCKER ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 3.33 -999.00 0 No No
1121 FLOOR 3 LOCKER_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.33 -999.00 0 No No
1122 AA26DE 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1123 68A2D7 0 473.81 143.75 9.14 0 3.05 7.01 8.26 0.26 3 No No
1124 9BA05A 0 473.81 143.75 9.14 0 3.05 7.01 8.26 0.26 2 No No
1125 C639E8 0 473.81 143.75 9.14 0 3.05 7.01 8.26 0.26 2 No No
1126 824F52 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1127 D2E9BA 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1128 D197DA 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1129 7C7BE2 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1130 812B32 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1131 3B5B94 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1132 60F383 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1133 F7BE2F 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1134 B29215 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1135 52FA3B 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1136 FLOOR 3 LOUNGE ROOF 0 1373.29 114.97 6.10 0 3.05 7.01 8.26 0.26 0 No No
1137 FLOOR 3 LOUNGE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 7.01 8.26 0.26 0 No No
1138 6D960C 0 0.00 0.00 0.00 0 3.05 3.66 4.18 0.38 0 No No
1139 9AB92B 0 0.00 0.00 0.00 0 3.05 3.66 4.18 0.38 0 No No
1140 CE3FEF 0 473.81 143.75 9.14 0 3.05 3.66 4.18 0.38 3 No No
1141 A2790A 0 473.81 143.75 9.14 0 3.05 3.66 4.18 0.38 2 No No
1142 E0FD95 0 0.00 0.00 0.00 0 3.05 3.66 4.18 0.38 0 No No
1143 B46F2C 0 0.00 0.00 0.00 0 3.05 3.66 4.18 0.38 0 No No
1144 FLOOR 3 LOUNGE TOILET ROOF 0 1373.29 114.97 6.10 0 3.05 3.66 4.18 0.38 0 No No
1145 FLOOR 3 LOUNGE TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.18 0.38 0 No No
1146 6F0E5D 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.26 0 No No
1147 D67C59 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.26 0 No No
1148 6C68C2 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.26 0 No No
1149 CE618F 0 302.86 143.75 9.14 0 3.05 7.62 5.47 0.26 3 No No
1150 79FCEE 0 302.86 143.75 9.14 0 3.05 7.62 5.47 0.26 2 No No
1151 EDE617 0 302.86 143.75 9.14 0 3.05 7.62 5.47 0.26 2 No No
1152 1DC177 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.26 0 No No
1153 FLOOR 3 MECHANICAL ROOF 0 1373.29 114.97 6.10 0 3.05 7.62 5.47 0.26 0 No No
1154 FLOOR 3 MECHANICAL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 7.62 5.47 0.26 0 No No
1155 A11DA8 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1156 BC2C22 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1157 44775D 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1158 CDD69A 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1159 F5E7FE 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1160 4BF787 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1161 98A52C 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1162 6310E5 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1163 2E74E6 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1164 FLOOR 3 MECHANICAL HALL ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 3.27 -999.00 0 No No
1165 FLOOR 3 MECHANICAL HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 3.27 -999.00 0 No No
1166 5FDFAE 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1167 C7B7AA 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1168 B972D4 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1169 5ADC59 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 3 No No
1170 C61F0D 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 2 No No
1171 7248C5 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 2 No No
1172 29FA28 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 2 No No
1173 F0B23F 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 2 No No
1174 EEC10E 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 2 No No
1175 944FCE 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 2 No No
1176 C41399 0 473.81 143.75 9.14 0 3.05 22.56 14.81 0.28 2 No No
1177 7DCAF1 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1178 CBFB94 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1179 A5FC87 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1180 A72B2F 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1181 538FE6 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1182 8A695C 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1183 45A523 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1184 F94215 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1185 C27BD7 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1186 AE8664 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1187 535D54 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1188 FLOOR 3 OFFICE ROOF 0 1373.29 114.97 6.10 0 3.05 22.56 14.81 0.28 0 No No
1189 FLOOR 3 OFFICE_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 22.56 14.81 0.28 0 No No
1190 CC8990 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1191 D4F411 0 302.86 110.86 9.14 0 3.05 1.83 3.51 0.00 0 No No
1192 2F3F2A 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1193 869ED5 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1194 D75504 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1195 E80026 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1196 A03B2E 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1197 133349 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1198 7DCD8A 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1199 D7E6B2 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1200 8646EF 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1201 840387 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1202 14A82B 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1203 FLOOR 3 OFFICE HALL ROOF 0 1373.29 114.97 6.10 0 3.05 1.83 3.51 0.00 0 No No
1204 FLOOR 3 OFFICE HALL_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 3.51 0.00 0 No No
1205 460DA4 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1206 8316C5 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1207 D5E94D 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1208 B35AD6 0 302.86 110.86 9.14 0 3.05 1.83 2.19 0.00 0 No No
1209 D0C6E8 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1210 F07866 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1211 FLOOR 3 OFFICE TOILET ROOF 0 1373.29 114.97 6.10 0 3.05 1.83 2.19 0.00 0 No No
1212 FLOOR 3 OFFICE TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 1.83 2.19 0.00 0 No No
1213 D22917 0 302.86 143.75 9.14 0 3.05 25.91 9.32 0.37 4 No No
1214 95BA33 0 302.86 143.75 9.14 0 3.05 25.91 9.32 0.37 1 No No
1215 F27282 0 302.86 143.75 9.14 0 3.05 25.91 9.32 0.37 1 No No
1216 4497EF 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.37 0 No No
1217 C1BC97 0 473.81 134.43 9.14 0 3.05 25.91 9.32 0.37 4 No No
1218 3DB407 0 473.81 134.43 9.14 0 3.05 25.91 9.32 0.37 1 No No
1219 3DADE2 0 473.81 134.43 9.14 0 3.05 25.91 9.32 0.37 1 No No
1220 DF3E2C 0 473.81 134.43 9.14 0 3.05 25.91 9.32 0.37 1 No No
1221 5031C8 0 473.81 134.43 9.14 0 3.05 25.91 9.32 0.37 1 No No
1222 F3F6EA 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.37 0 No No
1223 BCAAD1 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.37 0 No No
1224 E5720F 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.37 0 No No
1225 8E83C6 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.37 0 No No
1226 D14D65 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.37 0 No No
1227 CDCA72 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.37 0 No No
1228 339B46 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.37 0 No No
1229 7F8407 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.37 0 No No
1230 F69079 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.37 0 No No
1231 A56694 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.37 0 No No
1232 3C8351 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.37 0 No No
1233 FLOOR 3 PHYICAL THERAPY 1 ROOF 0 1373.29 114.97 6.10 0 3.05 25.91 9.32 0.37 0 No No
1234 FLOOR 3 PHYSICAL THERAPY 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 25.91 9.32 0.37 0 No No
1235 958E3F 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1236 27D999 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1237 55BD05 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1238 8BCB23 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1239 5C690E 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1240 E49C43 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1241 EF4AD1 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1242 8FB568 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1243 C271D9 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1244 1EE332 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1245 96623F 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1246 F17575 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1247 317B1B 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1248 FLOOR 3 PHYSICAL THERAPY 2 ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 6.81 -999.00 0 No No
1249 FLOOR 3 PHYSICAL THERAPY 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 6.81 -999.00 0 No No
1250 44D36C 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1251 CD21EC 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1252 BF7411 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1253 EA4A9E 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1254 484FB1 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1255 FLOOR 3 PHYSICAL THERAPY TOILET ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 2.70 -999.00 0 No No
1256 FLOOR 3 PHYSICAL THERAPY TOILET_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1257 D4C22E 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1258 6EC372 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1259 301CE0 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1260 89A685 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1261 137CDB 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1262 FLOOR 3 STORAGE 1 ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 2.74 -999.00 0 No No
1263 FLOOR 3 STORAGE 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.74 -999.00 0 No No
1264 FE5F03 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1265 1F37D7 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1266 AC05CF 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1267 C9F74B 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1268 63B825 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1269 FLOOR 3 STORAGE 2 ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 2.70 -999.00 0 No No
1270 FLOOR 3 STORAGE 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 2.70 -999.00 0 No No
1271 C78153 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1272 D13E00 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1273 2451B7 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1274 624E8A 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1275 D6005B 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1276 2B4713 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1277 25A972 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1278 496A6C 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1279 FLOOR 3 TREATMENT ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 6.05 -999.00 0 No No
1280 FLOOR 3 TREATMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 6.05 -999.00 0 No No
1281 C050FD 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1282 8DA7DB 0 473.81 134.43 9.14 0 3.05 21.95 14.40 0.38 4 No No
1283 C087D0 0 473.81 134.43 9.14 0 3.05 21.95 14.40 0.38 2 No No
1284 D2CA75 0 473.81 134.43 9.14 0 3.05 21.95 14.40 0.38 2 No No
1285 B0FB49 0 473.81 134.43 9.14 0 3.05 21.95 14.40 0.38 1 No No
1286 F8F69A 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1287 4CCA8D 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1288 2336C8 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1289 38B339 0 302.86 110.86 9.14 0 3.05 21.95 14.40 0.38 3 No No
1290 FE9BC9 0 302.86 110.86 9.14 0 3.05 21.95 14.40 0.38 1 No No
1291 9DF7DE 0 302.86 110.86 9.14 0 3.05 21.95 14.40 0.38 1 No No
1292 D0BE44 0 302.86 110.86 9.14 0 3.05 21.95 14.40 0.38 2 No No
1293 F4E5F5 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1294 AA7BE2 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1295 68EB71 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1296 66FE82 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1297 948D7B 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1298 236CCE 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1299 AE769E 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1300 FLOOR 3 UNDEVELOPED 1 ROOF 0 1373.29 114.97 6.10 0 3.05 21.95 14.40 0.38 0 No No
1301 FLOOR 3 UNDEVELOPED 1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 21.95 14.40 0.38 0 No No
1302 BE5F2F 0 302.86 110.86 9.14 0 3.05 17.07 9.24 0.26 3 No No
1303 6B5226 0 302.86 110.86 9.14 0 3.05 17.07 9.24 0.26 2 No No
1304 D5C4E5 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1305 C1B522 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1306 1DEE26 0 473.81 134.43 9.14 0 3.05 17.07 9.24 0.26 3 No No
1307 8F59F7 0 473.81 134.43 9.14 0 3.05 17.07 9.24 0.26 2 No No
1308 44F571 0 473.81 134.43 9.14 0 3.05 17.07 9.24 0.26 2 No No
1309 192E17 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1310 855B07 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1311 9D1FA7 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1312 6F1456 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1313 CDCFEE 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1314 FLOOR 3 UNDEVELOPED 2 ROOF 0 1373.29 114.97 6.10 0 3.05 17.07 9.24 0.26 0 No No
1315 FLOOR 3 UNDEVELOPED 2_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 17.07 9.24 0.26 0 No No
1316 111907 0 0.00 0.00 0.00 0 3.05 0.00 4.39 -999.00 0 No No
1317 CF2803 0 0.00 0.00 0.00 0 3.05 0.00 4.39 -999.00 0 No No
1318 180143 0 0.00 0.00 0.00 0 3.05 0.00 4.39 -999.00 0 No No
1319 2BC70D 0 0.00 0.00 0.00 0 3.05 0.00 4.39 -999.00 0 No No
1320 DF5076 0 0.00 0.00 0.00 0 3.05 0.00 4.39 -999.00 0 No No
1321 FLOOR 3 UTILITY ROOF 0 1373.29 114.97 6.10 0 3.05 0.00 4.39 -999.00 0 No No
1322 FLOOR 3 UTILITY_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 0.00 4.39 -999.00 0 No No
1323 3613B7 0 0.00 0.00 0.00 0 3.05 12.50 6.36 0.23 0 No No
1324 C86329 0 302.86 143.75 9.14 0 3.05 12.50 6.36 0.23 3 No No
1325 6BD844 0 302.86 143.75 9.14 0 3.05 12.50 6.36 0.23 2 No No
1326 86D536 0 302.86 143.75 9.14 0 3.05 12.50 6.36 0.23 2 No No
1327 BAF71D 0 302.86 143.75 9.14 0 3.05 12.50 6.36 0.23 2 No No
1328 3833A2 0 302.86 143.75 9.14 0 3.05 12.50 6.36 0.23 2 No No
1329 E7A265 0 0.00 0.00 0.00 0 3.05 12.50 6.36 0.23 0 No No
1330 4C6DBF 0 0.00 0.00 0.00 0 3.05 12.50 6.36 0.23 0 No No
1331 EFFB3B 0 0.00 0.00 0.00 0 3.05 12.50 6.36 0.23 0 No No
1332 8480E5 0 0.00 0.00 0.00 0 3.05 12.50 6.36 0.23 0 No No
1333 F6DDE6 0 0.00 0.00 0.00 0 3.05 12.50 6.36 0.23 0 No No
1334 FLOOR 3 WORK ROOF 0 1373.29 114.97 6.10 0 3.05 12.50 6.36 0.23 0 No No
1335 FLOOR 3 WORK_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 12.50 6.36 0.23 0 No No
1336 986A05 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.12 0 No No
1337 DFC6F0 0 302.86 143.75 9.14 0 9.14 10.67 3.30 0.12 4 No No
1338 2111A1 0 302.86 143.75 9.14 0 9.14 10.67 3.30 0.12 1 No No
1339 6EE166 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.12 0 No No
1340 A28F01 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.12 0 No No
1341 DE6295 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.12 0 No No
1342 D68874 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.12 0 No No
1343 88E360 0 473.81 143.75 9.14 0 9.14 10.67 3.30 0.12 3 No No
1344 9CB8E5 0 473.81 143.75 9.14 0 9.14 10.67 3.30 0.12 0 No No
1345 9BC521 0 473.81 143.75 9.14 0 9.14 10.67 3.30 0.12 2 No No
1346 142781 0 473.81 143.75 9.14 0 9.14 10.67 3.30 0.12 2 No No
1347 E4A528 0 473.81 143.75 9.14 0 9.14 10.67 3.30 0.12 0 No No
1348 16BE00 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.12 0 No No
1349 60F634 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.12 0 No No
1350 E7B55F 0 473.81 134.43 9.14 0 9.14 10.67 3.30 0.12 4 No No
1351 EEFDE3 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.12 0 No No
1352 NE STAIR SLAB 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.12 0 No No
1353 NE STAIR ROOF 0 1373.29 114.97 6.10 0 9.14 10.67 3.30 0.12 0 No No
1354 NE STAIR_INTERNALMASS_1 0 0.00 0.00 0.00 0 9.14 10.67 3.30 0.12 0 No No
1355 FB3814 0 473.81 134.43 9.14 0 9.14 8.23 3.16 0.00 0 No No
1356 24BAF7 0 473.81 134.43 9.14 0 9.14 8.23 3.16 0.00 0 No No
1357 976E3F 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1358 FCD12D 0 302.86 110.86 9.14 0 9.14 8.23 3.16 0.00 0 No No
1359 19E57D 0 302.86 110.86 9.14 0 9.14 8.23 3.16 0.00 0 No No
1360 D699FF 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1361 F9DFA4 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1362 BDE9D9 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1363 BEDECA 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1364 9BA592 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1365 NW ELEVATOR SLAB 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1366 NW ELEVATOR ROOF 0 1373.29 114.97 6.10 0 9.14 8.23 3.16 0.00 0 No No
1367 NW ELEVATOR_INTERNALMASS_1 0 0.00 0.00 0.00 0 9.14 8.23 3.16 0.00 0 No No
1368 5507DC 0 302.86 110.86 9.14 0 9.14 12.19 3.66 1.00E-001 3 No No
1369 EDE769 0 302.86 110.86 9.14 0 9.14 12.19 3.66 1.00E-001 0 No No
1370 2E2D0C 0 473.81 143.75 9.14 0 9.14 12.19 3.66 1.00E-001 3 No No
1371 E74902 0 473.81 143.75 9.14 0 9.14 12.19 3.66 1.00E-001 2 No No
1372 93BBC3 0 473.81 143.75 9.14 0 9.14 12.19 3.66 1.00E-001 2 No No
1373 1C9872 0 473.81 143.75 9.14 0 9.14 12.19 3.66 1.00E-001 0 No No
1374 FA9233 0 0.00 0.00 0.00 0 9.14 12.19 3.66 1.00E-001 0 No No
1375 AF0124 0 302.86 143.75 9.14 0 9.14 12.19 3.66 1.00E-001 3 No No
1376 74AB49 0 0.00 0.00 0.00 0 9.14 12.19 3.66 1.00E-001 0 No No
1377 DF47AC 0 0.00 0.00 0.00 0 9.14 12.19 3.66 1.00E-001 0 No No
1378 F41621 0 0.00 0.00 0.00 0 9.14 12.19 3.66 1.00E-001 0 No No
1379 7C0F83 0 0.00 0.00 0.00 0 9.14 12.19 3.66 1.00E-001 0 No No
1380 NW STAIR SLAB 0 0.00 0.00 0.00 0 9.14 12.19 3.66 1.00E-001 0 No No
1381 NW STAIR ROOF 0 1373.29 114.97 6.10 0 9.14 12.19 3.66 1.00E-001 0 No No
1382 NW STAIR_INTERNALMASS_1 0 0.00 0.00 0.00 0 9.14 12.19 3.66 1.00E-001 0 No No
1383 8FF821 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No
1384 850EA7 0 473.81 134.43 9.14 0 9.14 6.10 2.93 2.00E-002 4 No No
1385 C635A6 0 473.81 134.43 9.14 0 9.14 6.10 2.93 2.00E-002 1 No No
1386 1068C8 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No
1387 E2AFEB 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No
1388 99468F 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No
1389 17258E 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No
1390 573330 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No
1391 270BCE 0 302.86 110.86 9.14 0 9.14 6.10 2.93 2.00E-002 4 No No
1392 F402E9 0 302.86 110.86 9.14 0 9.14 6.10 2.93 2.00E-002 0 No No
1393 SW STAIR SLAB 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No
1394 SW STAIR ROOF 0 1373.29 114.97 6.10 0 9.14 6.10 2.93 2.00E-002 0 No No
1395 SW STAIR_INTERNALMASS_1 0 0.00 0.00 0.00 0 9.14 6.10 2.93 2.00E-002 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 FLOOR 1 ANESTHESIA_INFILTRATION INFIL_SCH FLOOR 1 ANESTHESIA 10.03 2.2 4.757E-003 4.741E-004 5.690E-004 0.560 0.000 0.000 0.224 0.000
2 FLOOR 1 CAFE_INFILTRATION INFIL_SCH FLOOR 1 CAFE 39.02 42.0 1.057E-002 2.709E-004 5.690E-004 0.320 0.000 0.000 0.224 0.000
3 FLOOR 1 DRESSING ROOM_INFILTRATION INFIL_SCH FLOOR 1 DRESSING ROOM 4.18 0.2 4.757E-003 1.138E-003 5.690E-004 1.344 0.000 0.000 0.224 0.000
4 FLOOR 1 ELECTRICAL ROOM_INFILTRATION INFIL_SCH FLOOR 1 ELECTRICAL ROOM 9.10 0.0 3.700E-003 4.064E-004 5.690E-004 0.480 0.000 0.000 0.224 0.000
5 FLOOR 1 ELEVATOR PUMP ROOM_INFILTRATION INFIL_SCH FLOOR 1 ELEVATOR PUMP ROOM 8.45 0.0 1.057E-002 1.250E-003 5.149E-004 1.477 0.000 0.000 0.224 0.000
6 FLOOR 1 LOBBY_INFILTRATION INFIL_SCH FLOOR 1 LOBBY 57.79 6.2 1.163E-002 2.012E-004 5.194E-004 0.238 0.000 0.000 0.224 0.000
7 FLOOR 1 LOBBY TOILET_INFILTRATION INFIL_SCH FLOOR 1 LOBBY TOILET 5.02 0.0 3.171E-003 6.322E-004 5.690E-004 0.747 0.000 0.000 0.224 0.000
8 FLOOR 1 LOCKER ROOM_INFILTRATION INFIL_SCH FLOOR 1 LOCKER ROOM 61.32 9.9 1.163E-002 1.897E-004 5.690E-004 0.224 0.000 0.000 0.224 0.000
9 FLOOR 1 MED GAS_INFILTRATION INFIL_SCH FLOOR 1 MED GAS 5.20 0.0 5.774E-003 1.110E-003 2.738E-004 1.311 0.000 0.000 0.224 0.000
10 FLOOR 1 MRI TOILET_INFILTRATION INFIL_SCH FLOOR 1 MRI TOILET 5.02 0.0 3.171E-003 6.322E-004 5.690E-004 0.747 0.000 0.000 0.224 0.000
11 FLOOR 1 OPERATING ROOM 1_INFILTRATION INFIL_SCH FLOOR 1 OPERATING ROOM 1 42.74 9.2 2.273E-002 5.319E-004 5.425E-004 0.628 0.000 0.000 0.224 0.000
12 FLOOR 1 OPERATING ROOM 2_INFILTRATION INFIL_SCH FLOOR 1 OPERATING ROOM 2 44.59 9.6 1.269E-002 2.845E-004 5.690E-004 0.336 0.000 0.000 0.224 0.000
13 FLOOR 1 PRE-OP ROOM 1_INFILTRATION INFIL_SCH FLOOR 1 PRE-OP ROOM 1 17.56 1.9 2.114E-003 1.204E-004 5.690E-004 0.142 0.000 0.000 0.224 0.000
14 FLOOR 1 PRE-OP TOILET_INFILTRATION INFIL_SCH FLOOR 1 PRE-OP TOILET 5.02 0.0 3.171E-003 6.322E-004 5.690E-004 0.747 0.000 0.000 0.224 0.000
15 FLOOR 1 PROCEDURE ROOM_INFILTRATION INFIL_SCH FLOOR 1 PROCEDURE ROOM 26.48 5.7 1.004E-002 3.793E-004 5.690E-004 0.448 0.000 0.000 0.224 0.000
16 FLOOR 1 RECEPTION_INFILTRATION INFIL_SCH FLOOR 1 RECEPTION 47.29 15.3 6.872E-003 1.453E-004 5.690E-004 0.172 0.000 0.000 0.224 0.000
17 FLOOR 1 RECOVERY ROOM_INFILTRATION INFIL_SCH FLOOR 1 RECOVERY ROOM 50.17 10.8 2.379E-002 4.741E-004 4.991E-004 0.560 0.000 0.000 0.224 0.000
18 FLOOR 1 SCHEDULING_INFILTRATION INFIL_SCH FLOOR 1 SCHEDULING 11.06 0.6 3.700E-003 3.347E-004 5.690E-004 0.395 0.000 0.000 0.224 0.000
19 FLOOR 1 STEP DOWN_INFILTRATION INFIL_SCH FLOOR 1 STEP DOWN 27.87 6.0 1.956E-002 7.017E-004 5.384E-004 0.829 0.000 0.000 0.224 0.000
20 FLOOR 1 STORAGE_INFILTRATION INFIL_SCH FLOOR 1 STORAGE 85.47 0.0 1.354E-002 1.584E-004 8.858E-005 0.187 0.000 0.000 0.224 0.000
21 FLOOR 1 SUB-STERILE_INFILTRATION INFIL_SCH FLOOR 1 SUB-STERILE 18.21 0.0 7.400E-003 4.064E-004 5.690E-004 0.480 0.000 0.000 0.224 0.000
22 FLOOR 1 UTILITY HALL_INFILTRATION INFIL_SCH FLOOR 1 UTILITY HALL 23.78 0.0 4.698E-003 1.975E-004 1.374E-004 0.233 0.000 0.000 0.224 0.000
23 FLOOR 1 UTILITY ROOM_INFILTRATION INFIL_SCH FLOOR 1 UTILITY ROOM 33.45 0.0 9.514E-003 2.845E-004 5.095E-004 0.336 0.000 0.000 0.224 0.000
24 FLOOR 1 VESTIBULE_INFILTRATION INFIL_SCH FLOOR 1 VESTIBULE 6.69 0.0 4.229E-003 6.322E-004 4.507E-004 0.747 0.000 0.000 0.224 0.000
25 FLOOR 1 VESTIBULE_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH FLOOR 1 VESTIBULE 6.69 0.0 0.777 0.116 8.279E-002 137.167 1.000 0.000 0.000 0.000
26 FLOOR 2 CONFERENCE_INFILTRATION INFIL_SCH FLOOR 2 CONFERENCE 31.22 16.8 2.114E-002 6.773E-004 5.690E-004 0.800 0.000 0.000 0.224 0.000
27 FLOOR 2 EXAM 1_INFILTRATION INFIL_SCH FLOOR 2 EXAM 1 33.45 7.2 2.220E-002 6.638E-004 5.690E-004 0.784 0.000 0.000 0.224 0.000
28 FLOOR 2 EXAM 2_INFILTRATION INFIL_SCH FLOOR 2 EXAM 2 50.17 10.8 9.514E-003 1.897E-004 5.690E-004 0.224 0.000 0.000 0.224 0.000
29 FLOOR 2 EXAM 3_INFILTRATION INFIL_SCH FLOOR 2 EXAM 3 66.89 14.4 1.269E-002 1.897E-004 5.690E-004 0.224 0.000 0.000 0.224 0.000
30 FLOOR 2 EXAM 4_INFILTRATION INFIL_SCH FLOOR 2 EXAM 4 7.80 1.7 3.700E-003 4.741E-004 5.690E-004 0.560 0.000 0.000 0.224 0.000
31 FLOOR 2 EXAM 5_INFILTRATION INFIL_SCH FLOOR 2 EXAM 5 32.52 7.0 1.321E-002 4.064E-004 5.690E-004 0.480 0.000 0.000 0.224 0.000
32 FLOOR 2 EXAM 6_INFILTRATION INFIL_SCH FLOOR 2 EXAM 6 20.90 4.5 7.929E-003 3.793E-004 5.690E-004 0.448 0.000 0.000 0.224 0.000
33 FLOOR 2 EXAM 7_INFILTRATION INFIL_SCH FLOOR 2 EXAM 7 73.58 15.8 1.269E-002 1.724E-004 5.690E-004 0.204 0.000 0.000 0.224 0.000
34 FLOOR 2 EXAM 8_INFILTRATION INFIL_SCH FLOOR 2 EXAM 8 25.08 5.4 9.514E-003 3.793E-004 5.690E-004 0.448 0.000 0.000 0.224 0.000
35 FLOOR 2 EXAM 9_INFILTRATION INFIL_SCH FLOOR 2 EXAM 9 36.79 7.9 6.343E-003 1.724E-004 5.690E-004 0.204 0.000 0.000 0.224 0.000
36 FLOOR 2 JANITOR_INFILTRATION INFIL_SCH FLOOR 2 JANITOR 5.85 0.0 8.457E-003 1.445E-003 5.690E-004 1.707 0.000 0.000 0.224 0.000
37 FLOOR 2 OFFICE_INFILTRATION INFIL_SCH FLOOR 2 OFFICE 52.03 2.8 2.114E-002 4.064E-004 5.690E-004 0.480 0.000 0.000 0.224 0.000
38 FLOOR 2 RECEPTION_INFILTRATION INFIL_SCH FLOOR 2 RECEPTION 91.42 29.5 2.590E-002 2.833E-004 5.690E-004 0.335 0.000 0.000 0.224 0.000
39 FLOOR 2 UTILITY_INFILTRATION INFIL_SCH FLOOR 2 UTILITY 11.71 0.0 4.757E-003 4.064E-004 5.690E-004 0.480 0.000 0.000 0.224 0.000
40 FLOOR 2 WORK_INFILTRATION INFIL_SCH FLOOR 2 WORK 157.01 8.5 1.374E-002 8.753E-005 5.690E-004 0.103 0.000 0.000 0.224 0.000
41 FLOOR 2 WORK TOILET_INFILTRATION INFIL_SCH FLOOR 2 WORK TOILET 5.02 0.0 3.171E-003 6.322E-004 5.690E-004 0.747 0.000 0.000 0.224 0.000
42 FLOOR 3 ELEVATOR HALL_INFILTRATION INFIL_SCH FLOOR 3 ELEVATOR HALL 34.37 0.0 2.114E-005 6.151E-007 5.551E-007 7.265E-004 0.000 0.000 0.224 0.000
43 FLOOR 3 JANITOR_INFILTRATION INFIL_SCH FLOOR 3 JANITOR 5.85 0.0 1.614E-003 2.758E-004 7.793E-005 0.326 0.000 0.000 0.224 0.000
44 FLOOR 3 LOUNGE_INFILTRATION INFIL_SCH FLOOR 3 LOUNGE 70.51 11.4 3.331E-004 4.724E-006 3.625E-006 5.580E-003 0.000 0.000 0.224 0.000
45 FLOOR 3 LOUNGE TOILET_INFILTRATION INFIL_SCH FLOOR 3 LOUNGE TOILET 17.84 0.0 3.482E-004 1.952E-005 1.201E-005 2.306E-002 0.000 0.000 0.224 0.000
46 FLOOR 3 MECHANICAL_INFILTRATION INFIL_SCH FLOOR 3 MECHANICAL 32.52 0.0 8.219E-004 2.528E-005 1.475E-005 2.986E-002 0.000 0.000 0.224 0.000
47 FLOOR 3 OFFICE_INFILTRATION INFIL_SCH FLOOR 3 OFFICE 282.05 15.2 8.644E-004 3.065E-006 2.464E-006 3.620E-003 0.000 0.000 0.224 0.000
48 FLOOR 3 OFFICE HALL_INFILTRATION INFIL_SCH FLOOR 3 OFFICE HALL 77.48 0.0 2.093E-005 2.702E-007 2.520E-007 3.191E-004 0.000 0.000 0.224 0.000
49 FLOOR 3 OFFICE TOILET_INFILTRATION INFIL_SCH FLOOR 3 OFFICE TOILET 5.02 0.0 2.965E-004 5.911E-005 2.800E-005 6.981E-002 0.000 0.000 0.224 0.000
50 FLOOR 3 PHYSICAL THERAPY 1_INFILTRATION INFIL_SCH FLOOR 3 PHYSICAL THERAPY 1 120.77 26.0 2.574E-003 2.132E-005 1.289E-005 2.518E-002 0.000 0.000 0.224 0.000
51 FLOOR 3 UNDEVELOPED 1_INFILTRATION INFIL_SCH FLOOR 3 UNDEVELOPED 1 210.70 0.0 1.088E-003 5.166E-006 3.921E-006 6.101E-003 0.000 0.000 0.224 0.000
52 FLOOR 3 UNDEVELOPED 2_INFILTRATION INFIL_SCH FLOOR 3 UNDEVELOPED 2 107.02 0.0 1.279E-003 1.195E-005 8.040E-006 1.411E-002 0.000 0.000 0.224 0.000
53 FLOOR 3 WORK_INFILTRATION INFIL_SCH FLOOR 3 WORK 53.33 2.9 1.348E-003 2.528E-005 1.475E-005 2.986E-002 0.000 0.000 0.224 0.000
54 NE STAIR_INFILTRATION INFIL_SCH NE STAIR 15.61 0.0 2.039E-002 1.306E-003 1.742E-004 0.514 0.000 0.000 0.224 0.000
55 NW ELEVATOR_INFILTRATION INFIL_SCH NW ELEVATOR 13.01 0.0 1.497E-002 1.151E-003 1.624E-004 0.453 0.000 0.000 0.224 0.000
56 NW STAIR_INFILTRATION INFIL_SCH NW STAIR 17.84 0.0 2.330E-002 1.306E-003 1.749E-004 0.514 0.000 0.000 0.224 0.000
57 SW STAIR_INFILTRATION INFIL_SCH SW STAIR 8.92 0.0 1.165E-002 1.306E-003 1.749E-004 0.514 0.000 0.000 0.224 0.000
58 FLOOR 3 DRESSING ROOM_INFILTRATION INFIL_SCH FLOOR 3 DRESSING ROOM 3.90 0.2 2.220E-003 5.690E-004 5.690E-004 0.672 0.000 0.000 0.224 0.000
59 FLOOR 3 HUMID_INFILTRATION INFIL_SCH FLOOR 3 HUMID 10.03 0.5 5.709E-003 5.690E-004 5.690E-004 0.672 0.000 0.000 0.224 0.000
60 FLOOR 3 LOCKER_INFILTRATION INFIL_SCH FLOOR 3 LOCKER 11.15 1.8 6.343E-003 5.690E-004 5.690E-004 0.672 0.000 0.000 0.224 0.000
61 FLOOR 3 MECHANICAL HALL_INFILTRATION INFIL_SCH FLOOR 3 MECHANICAL HALL 27.87 0.0 1.586E-002 5.690E-004 5.690E-004 0.672 0.000 0.000 0.224 0.000
62 FLOOR 3 PHYSICAL THERAPY 2_INFILTRATION INFIL_SCH FLOOR 3 PHYSICAL THERAPY 2 55.00 11.8 3.129E-002 5.690E-004 5.690E-004 0.672 0.000 0.000 0.224 0.000
63 FLOOR 3 PHYSICAL THERAPY TOILET_INFILTRATION INFIL_SCH FLOOR 3 PHYSICAL THERAPY TOILET 7.80 0.0 4.440E-003 5.690E-004 5.690E-004 0.672 0.000 0.000 0.224 0.000
64 FLOOR 3 STORAGE 1_INFILTRATION INFIL_SCH FLOOR 3 STORAGE 1 10.03 0.0 5.709E-003 5.690E-004 5.690E-004 0.672 0.000 0.000 0.224 0.000
65 FLOOR 3 STORAGE 2_INFILTRATION INFIL_SCH FLOOR 3 STORAGE 2 7.80 0.0 4.440E-003 5.690E-004 5.690E-004 0.672 0.000 0.000 0.224 0.000
66 FLOOR 3 TREATMENT_INFILTRATION INFIL_SCH FLOOR 3 TREATMENT 44.22 9.5 2.516E-002 5.690E-004 5.690E-004 0.672 0.000 0.000 0.224 0.000
67 FLOOR 3 UTILITY_INFILTRATION INFIL_SCH FLOOR 3 UTILITY 20.07 0.0 1.142E-002 5.690E-004 5.690E-004 0.672 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 FLOOR 1 ANESTHESIA Mixing/Well-Stirred
2 FLOOR 1 BIO HAZ Mixing/Well-Stirred
3 FLOOR 1 CAFE Mixing/Well-Stirred
4 FLOOR 1 CLEAN Mixing/Well-Stirred
5 FLOOR 1 CLEAN WORK Mixing/Well-Stirred
6 FLOOR 1 DICTATION Mixing/Well-Stirred
7 FLOOR 1 DRESSING ROOM Mixing/Well-Stirred
8 FLOOR 1 ELECTRICAL ROOM Mixing/Well-Stirred
9 FLOOR 1 ELEVATOR PUMP ROOM Mixing/Well-Stirred
10 FLOOR 1 HUMID Mixing/Well-Stirred
11 FLOOR 1 IT HALL Mixing/Well-Stirred
12 FLOOR 1 IT ROOM Mixing/Well-Stirred
13 FLOOR 1 LOBBY Mixing/Well-Stirred
14 FLOOR 1 LOBBY HALL Mixing/Well-Stirred
15 FLOOR 1 LOBBY TOILET Mixing/Well-Stirred
16 FLOOR 1 LOCKER ROOM Mixing/Well-Stirred
17 FLOOR 1 LOCKER ROOM HALL Mixing/Well-Stirred
18 FLOOR 1 LOUNGE Mixing/Well-Stirred
19 FLOOR 1 MED GAS Mixing/Well-Stirred
20 FLOOR 1 MRI CONTROL ROOM Mixing/Well-Stirred
21 FLOOR 1 MRI HALL Mixing/Well-Stirred
22 FLOOR 1 MRI ROOM Mixing/Well-Stirred
23 FLOOR 1 MRI TOILET Mixing/Well-Stirred
24 FLOOR 1 NOURISHMENT Mixing/Well-Stirred
25 FLOOR 1 NURSE HALL Mixing/Well-Stirred
26 FLOOR 1 NURSE JANITOR Mixing/Well-Stirred
27 FLOOR 1 NURSE STATION Mixing/Well-Stirred
28 FLOOR 1 NURSE TOILET Mixing/Well-Stirred
29 FLOOR 1 OFFICE Mixing/Well-Stirred
30 FLOOR 1 OPERATING ROOM 1 Mixing/Well-Stirred
31 FLOOR 1 OPERATING ROOM 2 Mixing/Well-Stirred
32 FLOOR 1 OPERATING ROOM 3 Mixing/Well-Stirred
33 FLOOR 1 PACU Mixing/Well-Stirred
34 FLOOR 1 PRE-OP HALL Mixing/Well-Stirred
35 FLOOR 1 PRE-OP ROOM 1 Mixing/Well-Stirred
36 FLOOR 1 PRE-OP ROOM 2 Mixing/Well-Stirred
37 FLOOR 1 PRE-OP TOILET Mixing/Well-Stirred
38 FLOOR 1 PROCEDURE ROOM Mixing/Well-Stirred
39 FLOOR 1 RECEPTION Mixing/Well-Stirred
40 FLOOR 1 RECEPTION HALL Mixing/Well-Stirred
41 FLOOR 1 RECOVERY ROOM Mixing/Well-Stirred
42 FLOOR 1 SCHEDULING Mixing/Well-Stirred
43 FLOOR 1 SCRUB Mixing/Well-Stirred
44 FLOOR 1 SOIL Mixing/Well-Stirred
45 FLOOR 1 SOIL HOLD Mixing/Well-Stirred
46 FLOOR 1 SOIL WORK Mixing/Well-Stirred
47 FLOOR 1 STEP DOWN Mixing/Well-Stirred
48 FLOOR 1 STERILE HALL Mixing/Well-Stirred
49 FLOOR 1 STERILE STORAGE Mixing/Well-Stirred
50 FLOOR 1 STORAGE Mixing/Well-Stirred
51 FLOOR 1 SUB-STERILE Mixing/Well-Stirred
52 FLOOR 1 UTILITY HALL Mixing/Well-Stirred
53 FLOOR 1 UTILITY JANITOR Mixing/Well-Stirred
54 FLOOR 1 UTILITY ROOM Mixing/Well-Stirred
55 FLOOR 1 VESTIBULE Mixing/Well-Stirred
56 FLOOR 2 CONFERENCE Mixing/Well-Stirred
57 FLOOR 2 CONFERENCE TOILET Mixing/Well-Stirred
58 FLOOR 2 DICTATION Mixing/Well-Stirred
59 FLOOR 2 EXAM 1 Mixing/Well-Stirred
60 FLOOR 2 EXAM 2 Mixing/Well-Stirred
61 FLOOR 2 EXAM 3 Mixing/Well-Stirred
62 FLOOR 2 EXAM 4 Mixing/Well-Stirred
63 FLOOR 2 EXAM 5 Mixing/Well-Stirred
64 FLOOR 2 EXAM 6 Mixing/Well-Stirred
65 FLOOR 2 EXAM 7 Mixing/Well-Stirred
66 FLOOR 2 EXAM 8 Mixing/Well-Stirred
67 FLOOR 2 EXAM 9 Mixing/Well-Stirred
68 FLOOR 2 EXAM HALL 1 Mixing/Well-Stirred
69 FLOOR 2 EXAM HALL 2 Mixing/Well-Stirred
70 FLOOR 2 EXAM HALL 3 Mixing/Well-Stirred
71 FLOOR 2 EXAM HALL 4 Mixing/Well-Stirred
72 FLOOR 2 EXAM HALL 5 Mixing/Well-Stirred
73 FLOOR 2 EXAM HALL 6 Mixing/Well-Stirred
74 FLOOR 2 JANITOR Mixing/Well-Stirred
75 FLOOR 2 LOUNGE Mixing/Well-Stirred
76 FLOOR 2 NURSE STATION 1 Mixing/Well-Stirred
77 FLOOR 2 NURSE STATION 2 Mixing/Well-Stirred
78 FLOOR 2 OFFICE Mixing/Well-Stirred
79 FLOOR 2 OFFICE HALL Mixing/Well-Stirred
80 FLOOR 2 RECEPTION Mixing/Well-Stirred
81 FLOOR 2 RECEPTION HALL Mixing/Well-Stirred
82 FLOOR 2 RECEPTION TOILET Mixing/Well-Stirred
83 FLOOR 2 SCHEDULING 1 Mixing/Well-Stirred
84 FLOOR 2 SCHEDULING 2 Mixing/Well-Stirred
85 FLOOR 2 STORAGE 1 Mixing/Well-Stirred
86 FLOOR 2 STORAGE 2 Mixing/Well-Stirred
87 FLOOR 2 STORAGE 3 Mixing/Well-Stirred
88 FLOOR 2 UTILITY Mixing/Well-Stirred
89 FLOOR 2 WORK Mixing/Well-Stirred
90 FLOOR 2 WORK HALL Mixing/Well-Stirred
91 FLOOR 2 WORK TOILET Mixing/Well-Stirred
92 FLOOR 2 X-RAY Mixing/Well-Stirred
93 FLOOR 3 DRESSING ROOM Mixing/Well-Stirred
94 FLOOR 3 ELEVATOR HALL Mixing/Well-Stirred
95 FLOOR 3 HUMID Mixing/Well-Stirred
96 FLOOR 3 JANITOR Mixing/Well-Stirred
97 FLOOR 3 LOCKER Mixing/Well-Stirred
98 FLOOR 3 LOUNGE Mixing/Well-Stirred
99 FLOOR 3 LOUNGE TOILET Mixing/Well-Stirred
100 FLOOR 3 MECHANICAL Mixing/Well-Stirred
101 FLOOR 3 MECHANICAL HALL Mixing/Well-Stirred
102 FLOOR 3 OFFICE Mixing/Well-Stirred
103 FLOOR 3 OFFICE HALL Mixing/Well-Stirred
104 FLOOR 3 OFFICE TOILET Mixing/Well-Stirred
105 FLOOR 3 PHYSICAL THERAPY 1 Mixing/Well-Stirred
106 FLOOR 3 PHYSICAL THERAPY 2 Mixing/Well-Stirred
107 FLOOR 3 PHYSICAL THERAPY TOILET Mixing/Well-Stirred
108 FLOOR 3 STORAGE 1 Mixing/Well-Stirred
109 FLOOR 3 STORAGE 2 Mixing/Well-Stirred
110 FLOOR 3 TREATMENT Mixing/Well-Stirred
111 FLOOR 3 UNDEVELOPED 1 Mixing/Well-Stirred
112 FLOOR 3 UNDEVELOPED 2 Mixing/Well-Stirred
113 FLOOR 3 UTILITY Mixing/Well-Stirred
114 FLOOR 3 WORK Mixing/Well-Stirred
115 NE STAIR Mixing/Well-Stirred
116 NW ELEVATOR Mixing/Well-Stirred
117 NW STAIR Mixing/Well-Stirred
118 SW STAIR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 FLOOR 1 ANESTHESIA Cooling 641.39108 641.39108 4.90760E-002 4.90760E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 29.99667 1.27032E-002 10.03353 2.16021 1.52901E-002 0.00000
2 FLOOR 1 ANESTHESIA Heating 362.06062 362.06062 1.59859E-002 1.59859E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 10.03353 2.16021 1.52901E-002 0.00000
3 FLOOR 1 BIO HAZ Cooling 105.66168 105.66168 7.93999E-003 7.93999E-003 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 5.20257 0.00000 3.17129E-003 0.00000
4 FLOOR 1 BIO HAZ Heating 126.69057 126.69057 5.62299E-003 5.62299E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 5.20257 0.00000 3.17129E-003 0.00000
5 FLOOR 1 CAFE Cooling 3862.59274 3862.59274 0.29587 0.29587 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 29.89333 1.27032E-002 39.01928 42.00409 0.18433 0.00000
6 FLOOR 1 CAFE Heating 713.09298 713.09298 3.09705E-002 0.18433 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 39.01928 42.00409 0.18433 0.00000
7 FLOOR 1 CLEAN Cooling 672.34293 672.34293 5.04340E-002 5.04340E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 11.70578 2.52025 1.78385E-002 0.00000
8 FLOOR 1 CLEAN Heating 0.00000 0.00000 0.00000 1.78385E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 11.70578 2.52025 1.78385E-002 0.00000
9 FLOOR 1 CLEAN WORK Cooling 813.52932 813.52932 6.22427E-002 6.22427E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 20.92400 1.27032E-002 15.32900 3.30032 2.33599E-002 0.00000
10 FLOOR 1 CLEAN WORK Heating 0.00000 0.00000 0.00000 2.33599E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 15.32900 3.30032 2.33599E-002 0.00000
11 FLOOR 1 DICTATION Cooling 495.63759 495.63759 3.70051E-002 3.70051E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 11.70578 0.63006 5.05424E-003 0.00000
12 FLOOR 1 DICTATION Heating 0.00000 0.00000 0.00000 5.05424E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 11.70578 0.63006 5.05424E-003 0.00000
13 FLOOR 1 DRESSING ROOM Cooling 131.96169 131.96169 1.00957E-002 1.00957E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 30.10000 1.27032E-002 4.18064 0.22502 1.80509E-003 0.00000
14 FLOOR 1 DRESSING ROOM Heating 360.48864 360.48864 1.60560E-002 1.60560E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 4.18064 0.22502 1.80509E-003 0.00000
15 FLOOR 1 ELECTRICAL ROOM Cooling 592.61684 592.61684 4.53331E-002 4.53331E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 26.93800 1.27032E-002 9.10450 0.00000 0.00000 0.00000
16 FLOOR 1 ELECTRICAL ROOM Heating 77.81415 77.81415 3.44689E-003 3.44689E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 9.10450 0.00000 0.00000 0.00000
17 FLOOR 1 ELEVATOR PUMP ROOM Cooling 3937.66845 3937.66845 0.29797 0.29797 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 8.45418 0.00000 0.00000 0.00000
18 FLOOR 1 ELEVATOR PUMP ROOM Heating 579.89042 579.89042 2.57850E-002 2.57850E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 8.45418 0.00000 0.00000 0.00000
19 FLOOR 1 HUMID Cooling 237.67592 237.67592 1.77976E-002 1.77976E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 5.01676 0.27003 2.16610E-003 0.00000
20 FLOOR 1 HUMID Heating 0.00000 0.00000 0.00000 2.16610E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 5.01676 0.27003 2.16610E-003 0.00000
21 FLOOR 1 IT HALL Cooling 330.48767 330.48767 2.47000E-002 2.47000E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 13.00643 0.00000 3.96411E-003 0.00000
22 FLOOR 1 IT HALL Heating 0.00000 0.00000 0.00000 3.96411E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 13.00643 0.00000 3.96411E-003 0.00000
23 FLOOR 1 IT ROOM Cooling 362.31362 362.31362 2.69488E-002 2.69488E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 10.40514 0.56005 4.49266E-003 0.00000
24 FLOOR 1 IT ROOM Heating 4.01865 4.01865 1.78619E-004 4.49266E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 -32.70000 1.83376E-004 10.40514 0.56005 4.49266E-003 0.00000
25 FLOOR 1 LOBBY Cooling 3574.76059 3574.76059 0.27348 0.27348 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 27.12400 1.27032E-002 57.78569 6.22061 3.22886E-002 0.00000
26 FLOOR 1 LOBBY Heating 1538.96907 1538.96907 6.75185E-002 6.75185E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 57.78569 6.22061 3.22886E-002 0.00000
27 FLOOR 1 LOBBY HALL Cooling 761.27657 761.27657 5.65401E-002 5.65401E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 22.29673 0.00000 6.79562E-003 0.00000
28 FLOOR 1 LOBBY HALL Heating 0.00000 0.00000 0.00000 6.79562E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 22.29673 0.00000 6.79562E-003 0.00000
29 FLOOR 1 LOBBY TOILET Cooling 479.76964 479.76964 3.61542E-002 3.61542E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 5.01676 0.00000 0.00000 0.00000
30 FLOOR 1 LOBBY TOILET Heating 317.03534 317.03534 1.40903E-002 1.40903E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 5.01676 0.00000 0.00000 0.00000
31 FLOOR 1 LOCKER ROOM Cooling 3079.83986 3079.83986 0.23564 0.23564 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 29.79000 1.27032E-002 61.31601 9.90096 4.20479E-002 0.00000
32 FLOOR 1 LOCKER ROOM Heating 0.00000 0.00000 0.00000 4.20479E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 61.31601 9.90096 4.20479E-002 0.00000
33 FLOOR 1 LOCKER ROOM HALL Cooling 1150.12815 1150.12815 8.53396E-002 8.53396E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 46.07991 0.00000 1.40443E-002 0.00000
34 FLOOR 1 LOCKER ROOM HALL Heating 0.00000 0.00000 0.00000 1.40443E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 46.07991 0.00000 1.40443E-002 0.00000
35 FLOOR 1 LOUNGE Cooling 1706.94439 1706.94439 0.13059 0.13059 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 20.92400 1.27032E-002 33.44509 5.40053 2.29352E-002 0.00000
36 FLOOR 1 LOUNGE Heating 0.00000 0.00000 0.00000 2.29352E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 33.44509 5.40053 2.29352E-002 0.00000
37 FLOOR 1 MED GAS Cooling 74.94703 74.94703 5.73350E-003 5.73350E-003 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 30.10000 1.27032E-002 5.20257 0.00000 3.17129E-003 0.00000
38 FLOOR 1 MED GAS Heating 655.63467 655.63467 2.92482E-002 2.92482E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 5.20257 0.00000 3.17129E-003 0.00000
39 FLOOR 1 MRI CONTROL ROOM Cooling 1880.04204 1880.04204 0.14385 0.14385 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 28.86000 1.27032E-002 15.60771 3.36033 2.37847E-002 0.00000
40 FLOOR 1 MRI CONTROL ROOM Heating 0.00000 0.00000 0.00000 2.37847E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 15.60771 3.36033 2.37847E-002 0.00000
41 FLOOR 1 MRI HALL Cooling 446.26060 446.26060 3.31566E-002 3.31566E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 13.65675 0.00000 4.16232E-003 0.00000
42 FLOOR 1 MRI HALL Heating 4.64792 4.64792 2.08243E-004 4.16232E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 -32.70000 1.83376E-004 13.65675 0.00000 4.16232E-003 0.00000
43 FLOOR 1 MRI ROOM Cooling 4808.06975 4808.06975 0.36786 0.36786 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 27.53733 1.27032E-002 40.87734 8.80086 6.22932E-002 0.00000
44 FLOOR 1 MRI ROOM Heating 0.00000 0.00000 0.00000 6.22932E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 40.87734 8.80086 6.22932E-002 0.00000
45 FLOOR 1 MRI TOILET Cooling 129.47270 129.47270 9.73278E-003 9.73278E-003 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 5.01676 0.00000 0.00000 0.00000
46 FLOOR 1 MRI TOILET Heating 220.96734 220.96734 9.77969E-003 9.77969E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 5.01676 0.00000 0.00000 0.00000
47 FLOOR 1 NOURISHMENT Cooling 953.15332 953.15332 7.14886E-002 7.14886E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 16.90835 3.64035 1.37422E-002 0.00000
48 FLOOR 1 NOURISHMENT Heating 0.00000 0.00000 0.00000 1.37422E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 16.90835 3.64035 1.37422E-002 0.00000
49 FLOOR 1 NURSE HALL Cooling 1404.13011 1404.13011 0.10397 0.10397 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 46.07991 0.00000 1.40443E-002 0.00000
50 FLOOR 1 NURSE HALL Heating 10.19426 10.19426 4.56768E-004 1.40443E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 -32.70000 1.83376E-004 46.07991 0.00000 1.40443E-002 0.00000
51 FLOOR 1 NURSE JANITOR Cooling 167.48723 167.48723 1.25087E-002 1.25087E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 5.01676 0.00000 3.05803E-003 0.00000
52 FLOOR 1 NURSE JANITOR Heating 0.00000 0.00000 0.00000 3.05803E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 5.01676 0.00000 3.05803E-003 0.00000
53 FLOOR 1 NURSE STATION Cooling 1274.98157 1274.98157 9.75484E-002 9.75484E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 20.92400 1.27032E-002 24.24769 5.22051 1.97073E-002 0.00000
54 FLOOR 1 NURSE STATION Heating 0.00000 0.00000 0.00000 1.97073E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 24.24769 5.22051 1.97073E-002 0.00000
55 FLOOR 1 NURSE TOILET Cooling 207.29342 207.29342 1.54750E-002 1.54750E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 5.01676 0.00000 0.00000 0.00000
56 FLOOR 1 OFFICE Cooling 1488.51866 1488.51866 0.11045 0.11045 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 44.87217 2.41524 1.93746E-002 0.00000
57 FLOOR 1 OFFICE Heating 0.00000 0.00000 0.00000 1.93746E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 44.87217 2.41524 1.93746E-002 0.00000
58 FLOOR 1 OPERATING ROOM 1 Cooling 6218.49784 6218.49784 0.70415 0.72361 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 24.68533 1.27032E-002 42.73540 9.20090 0.23879 0.00000
59 FLOOR 1 OPERATING ROOM 1 Heating 0.00000 0.00000 0.00000 0.23879 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 42.73540 9.20090 0.23879 0.00000
60 FLOOR 1 OPERATING ROOM 2 Cooling 6636.62727 6636.62727 0.75148 0.75507 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 23.98267 1.27032E-002 44.59346 9.60093 0.24917 0.00000
61 FLOOR 1 OPERATING ROOM 2 Heating 2.83669 2.83669 1.11988E-004 0.24917 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:10:00 -32.70000 1.83376E-004 44.59346 9.60093 0.24917 0.00000
62 FLOOR 1 OPERATING ROOM 3 Cooling 5928.72705 5928.72705 0.65406 0.74878 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 44.22185 9.52093 0.24710 0.00000
63 FLOOR 1 OPERATING ROOM 3 Heating 0.00000 0.00000 0.00000 0.24710 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 44.22185 9.52093 0.24710 0.00000
64 FLOOR 1 PACU Cooling 637.57606 637.57606 4.78765E-002 5.09671E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 10.03353 2.16021 3.22792E-002 0.00000
65 FLOOR 1 PACU Heating 0.00000 0.00000 0.00000 3.22792E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 10.03353 2.16021 3.22792E-002 0.00000
66 FLOOR 1 PRE-OP HALL Cooling 1356.92401 1356.92401 0.10052 0.10052 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 49.05281 0.00000 1.49504E-002 0.00000
67 FLOOR 1 PRE-OP HALL Heating 0.00000 0.00000 0.00000 1.49504E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 49.05281 0.00000 1.49504E-002 0.00000
68 FLOOR 1 PRE-OP ROOM 1 Cooling 751.05089 751.05089 5.60193E-002 8.91925E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 17.55867 1.89018 5.20290E-002 0.00000
69 FLOOR 1 PRE-OP ROOM 1 Heating 0.00000 0.00000 0.00000 5.20290E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 17.55867 1.89018 5.20290E-002 0.00000
70 FLOOR 1 PRE-OP ROOM 2 Cooling 1417.68499 1417.68499 0.10591 0.15951 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 31.40123 3.38033 9.30465E-002 0.00000
71 FLOOR 1 PRE-OP ROOM 2 Heating 0.00000 0.00000 0.00000 9.30465E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 31.40123 3.38033 9.30465E-002 0.00000
72 FLOOR 1 PRE-OP TOILET Cooling 150.14835 150.14835 1.14859E-002 1.14859E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 27.12400 1.27032E-002 5.01676 0.00000 0.00000 0.00000
73 FLOOR 1 PRE-OP TOILET Heating 279.99053 279.99053 1.24292E-002 1.24292E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 5.01676 0.00000 0.00000 0.00000
74 FLOOR 1 PROCEDURE ROOM Cooling 1605.78339 1605.78339 0.12287 0.33624 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.10000 1.27032E-002 26.47737 5.70055 0.10760 0.00000
75 FLOOR 1 PROCEDURE ROOM Heating 397.46892 397.46892 1.73554E-002 0.10760 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 26.47737 5.70055 0.10760 0.00000
76 FLOOR 1 RECEPTION Cooling 2404.31581 2404.31581 0.18399 0.18399 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 29.89333 1.27032E-002 47.28765 15.27149 5.04433E-002 0.00000
77 FLOOR 1 RECEPTION Heating 37.44326 37.44326 1.64392E-003 5.04433E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 -32.70000 1.83376E-004 47.28765 15.27149 5.04433E-002 0.00000
78 FLOOR 1 RECEPTION HALL Cooling 347.66986 347.66986 2.58495E-002 2.58495E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 11.89159 0.00000 3.62433E-003 0.00000
79 FLOOR 1 RECEPTION HALL Heating 0.00000 0.00000 0.00000 3.62433E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 11.89159 0.00000 3.62433E-003 0.00000
80 FLOOR 1 RECOVERY ROOM Cooling 3549.60287 3549.60287 0.27161 0.27161 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 29.99667 1.27032E-002 50.16764 10.80105 0.16140 0.00000
81 FLOOR 1 RECOVERY ROOM Heating 1604.48693 1604.48693 7.06709E-002 0.16140 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 50.16764 10.80105 0.16140 0.00000
82 FLOOR 1 SCHEDULING Cooling 404.77754 404.77754 3.01098E-002 3.01098E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 11.05546 0.59506 4.77345E-003 0.00000
83 FLOOR 1 SCHEDULING Heating 113.50050 113.50050 5.03111E-003 5.03111E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 11.05546 0.59506 4.77345E-003 0.00000
84 FLOOR 1 SCRUB Cooling 233.94623 233.94623 1.75308E-002 1.75308E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 7.80386 0.00000 2.37847E-003 0.00000
85 FLOOR 1 SCRUB Heating 120.90591 120.90591 5.37594E-003 5.37594E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 7.80386 0.00000 2.37847E-003 0.00000
86 FLOOR 1 SOIL Cooling 655.50564 655.50564 5.01519E-002 5.01519E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 20.92400 1.27032E-002 11.70578 2.52025 1.78385E-002 0.00000
87 FLOOR 1 SOIL Heating 0.00000 0.00000 0.00000 1.78385E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 11.70578 2.52025 1.78385E-002 0.00000
88 FLOOR 1 SOIL HOLD Cooling 261.58183 261.58183 1.95750E-002 1.95750E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 5.20257 1.12011 7.92822E-003 0.00000
89 FLOOR 1 SOIL HOLD Heating 2.26420 2.26420 1.00391E-004 7.92822E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 -32.70000 1.83376E-004 5.20257 1.12011 7.92822E-003 0.00000
90 FLOOR 1 SOIL WORK Cooling 870.71738 870.71738 6.66183E-002 6.66183E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 20.92400 1.27032E-002 16.72255 3.60035 2.54836E-002 0.00000
91 FLOOR 1 SOIL WORK Heating 0.00000 0.00000 0.00000 2.54836E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 16.72255 3.60035 2.54836E-002 0.00000
92 FLOOR 1 STEP DOWN Cooling 2109.94049 2109.94049 0.16145 0.16145 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 28.52933 1.27032E-002 27.87091 6.00058 8.96644E-002 0.00000
93 FLOOR 1 STEP DOWN Heating 1334.42031 1334.42031 5.91131E-002 8.96644E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 27.87091 6.00058 8.96644E-002 0.00000
94 FLOOR 1 STERILE HALL Cooling 1344.61284 1344.61284 9.99983E-002 9.99983E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 57.22827 0.00000 1.74421E-002 0.00000
95 FLOOR 1 STERILE HALL Heating 316.83671 316.83671 1.41188E-002 1.74421E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 57.22827 0.00000 1.74421E-002 0.00000
96 FLOOR 1 STERILE STORAGE Cooling 822.30924 822.30924 6.09220E-002 6.09220E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 36.78960 0.00000 2.24255E-002 0.00000
97 FLOOR 1 STERILE STORAGE Heating 0.00000 0.00000 0.00000 2.24255E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 36.78960 0.00000 2.24255E-002 0.00000
98 FLOOR 1 STORAGE Cooling 1039.51385 1039.51385 7.95179E-002 7.95179E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 29.02533 1.27032E-002 85.47080 0.00000 5.20997E-002 0.00000
99 FLOOR 1 STORAGE Heating 4545.33157 4545.33157 0.20158 0.20158 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 85.47080 0.00000 5.20997E-002 0.00000
100 FLOOR 1 SUB-STERILE Cooling 600.77632 600.77632 4.47745E-002 4.47745E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 18.20900 0.00000 5.54976E-003 0.00000
101 FLOOR 1 SUB-STERILE Heating 825.58535 825.58535 3.65637E-002 3.65637E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 18.20900 0.00000 5.54976E-003 0.00000
102 FLOOR 1 UTILITY HALL Cooling 477.31711 477.31711 3.65133E-002 3.65133E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:40:00 22.49467 1.27032E-002 23.78318 0.00000 7.24866E-003 0.00000
103 FLOOR 1 UTILITY HALL Heating 1340.86976 1340.86976 5.95162E-002 5.95162E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 23.78318 0.00000 7.24866E-003 0.00000
104 FLOOR 1 UTILITY JANITOR Cooling 116.39539 116.39539 8.73507E-003 8.73507E-003 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 3.90193 0.00000 2.37847E-003 0.00000
105 FLOOR 1 UTILITY JANITOR Heating 56.85839 56.85839 2.53452E-003 2.53452E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 3.90193 0.00000 2.37847E-003 0.00000
106 FLOOR 1 UTILITY ROOM Cooling 713.17460 713.17460 5.31033E-002 5.31033E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 33.44509 0.00000 2.03869E-002 0.00000
107 FLOOR 1 UTILITY ROOM Heating 1383.51397 1383.51397 6.11993E-002 6.11993E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 33.44509 0.00000 2.03869E-002 0.00000
108 FLOOR 1 VESTIBULE Cooling 214.72713 214.72713 1.64260E-002 1.64260E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 27.53733 1.27032E-002 6.68902 0.00000 2.03869E-003 0.00000
109 FLOOR 1 VESTIBULE Heating 372.10130 372.10130 1.65155E-002 1.65155E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 6.68902 0.00000 2.03869E-003 0.00000
110 FLOOR 2 CONFERENCE Cooling 2449.16195 2449.16195 0.22139 0.22139 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 29.68667 1.27032E-002 31.21542 16.80163 4.91550E-002 0.00000
111 FLOOR 2 CONFERENCE Heating 1667.31645 1667.31645 7.39613E-002 7.39613E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 31.21542 16.80163 4.91550E-002 0.00000
112 FLOOR 2 CONFERENCE TOILET Cooling 223.38887 223.38887 1.95663E-002 1.95663E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 5.94579 0.00000 0.00000 0.00000
113 FLOOR 2 CONFERENCE TOILET Heating 96.36828 96.36828 4.28463E-003 4.28463E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 5.94579 0.00000 0.00000 0.00000
114 FLOOR 2 DICTATION Cooling 293.65247 293.65247 2.58271E-002 2.58271E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 6.50321 0.35003 2.80791E-003 0.00000
115 FLOOR 2 DICTATION Heating 0.00000 0.00000 0.00000 2.80791E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 6.50321 0.35003 2.80791E-003 0.00000
116 FLOOR 2 EXAM 1 Cooling 2669.88695 2669.88695 0.24123 0.24123 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 27.95067 1.27032E-002 33.44509 7.20070 5.09671E-002 0.00000
117 FLOOR 2 EXAM 1 Heating 1697.23417 1697.23417 7.52396E-002 7.52396E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 33.44509 7.20070 5.09671E-002 0.00000
118 FLOOR 2 EXAM 2 Cooling 2393.12874 2393.12874 0.21623 0.25484 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 29.68667 1.27032E-002 50.16764 10.80105 7.64507E-002 0.00000
119 FLOOR 2 EXAM 2 Heating 691.10356 691.10356 3.02619E-002 7.64507E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 50.16764 10.80105 7.64507E-002 0.00000
120 FLOOR 2 EXAM 3 Cooling 3274.75609 3274.75609 0.29589 0.33978 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 29.68667 1.27032E-002 66.89019 14.40140 0.10193 0.00000
121 FLOOR 2 EXAM 3 Heating 924.75119 924.75119 4.04240E-002 0.10193 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 66.89019 14.40140 0.10193 0.00000
122 FLOOR 2 EXAM 4 Cooling 547.43733 547.43733 4.94624E-002 4.94624E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 29.58333 1.27032E-002 7.80386 1.68016 1.18923E-002 0.00000
123 FLOOR 2 EXAM 4 Heating 404.97236 404.97236 1.79622E-002 1.79622E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 7.80386 1.68016 1.18923E-002 0.00000
124 FLOOR 2 EXAM 5 Cooling 2292.88296 2292.88296 0.20717 0.20717 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 23.28000 1.27032E-002 32.51606 7.00068 4.95514E-002 0.00000
125 FLOOR 2 EXAM 5 Heating 1251.23389 1251.23389 5.52883E-002 5.52883E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 32.51606 7.00068 4.95514E-002 0.00000
126 FLOOR 2 EXAM 6 Cooling 954.64042 954.64042 8.62579E-002 0.10618 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 30.10000 1.27032E-002 20.90318 4.50044 3.18545E-002 0.00000
127 FLOOR 2 EXAM 6 Heating 699.46476 699.46476 3.08454E-002 3.18545E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 20.90318 4.50044 3.18545E-002 0.00000
128 FLOOR 2 EXAM 7 Cooling 3037.56642 3037.56642 0.27445 0.37376 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 20.92400 1.27032E-002 73.57921 15.84154 0.11213 0.00000
129 FLOOR 2 EXAM 7 Heating 476.69397 476.69397 2.09319E-002 0.11213 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 73.57921 15.84154 0.11213 0.00000
130 FLOOR 2 EXAM 8 Cooling 1201.97247 1201.97247 0.10861 0.12742 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 30.10000 1.27032E-002 25.08382 5.40053 3.82254E-002 0.00000
131 FLOOR 2 EXAM 8 Heating 749.64121 749.64121 3.29564E-002 3.82254E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 25.08382 5.40053 3.82254E-002 0.00000
132 FLOOR 2 EXAM 9 Cooling 1641.33751 1641.33751 0.14830 0.18688 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 20.92400 1.27032E-002 36.78960 7.92077 5.60639E-002 0.00000
133 FLOOR 2 EXAM 9 Heating 388.53092 388.53092 1.70749E-002 5.60639E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 36.78960 7.92077 5.60639E-002 0.00000
134 FLOOR 2 EXAM HALL 1 Cooling 637.42195 637.42195 5.58241E-002 5.58241E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 16.72255 0.00000 5.09671E-003 0.00000
135 FLOOR 2 EXAM HALL 1 Heating 410.90540 410.90540 1.81742E-002 1.81742E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 16.72255 0.00000 5.09671E-003 0.00000
136 FLOOR 2 EXAM HALL 2 Cooling 632.65826 632.65826 5.54032E-002 5.54032E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 16.72255 0.00000 5.09671E-003 0.00000
137 FLOOR 2 EXAM HALL 2 Heating 257.94100 257.94100 1.14574E-002 1.14574E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 16.72255 0.00000 5.09671E-003 0.00000
138 FLOOR 2 EXAM HALL 3 Cooling 608.73579 608.73579 5.32651E-002 5.32651E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 16.72255 0.00000 5.09671E-003 0.00000
139 FLOOR 2 EXAM HALL 3 Heating 267.41265 267.41265 1.18731E-002 1.18731E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 16.72255 0.00000 5.09671E-003 0.00000
140 FLOOR 2 EXAM HALL 4 Cooling 625.14306 625.14306 5.45710E-002 5.45710E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 18.39480 0.00000 5.60639E-003 0.00000
141 FLOOR 2 EXAM HALL 4 Heating 163.48469 163.48469 7.28254E-003 7.28254E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 18.39480 0.00000 5.60639E-003 0.00000
142 FLOOR 2 EXAM HALL 5 Cooling 655.46350 655.46350 5.73146E-002 5.73146E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 18.39480 0.00000 5.60639E-003 0.00000
143 FLOOR 2 EXAM HALL 5 Heating 165.30378 165.30378 7.36586E-003 7.36586E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 18.39480 0.00000 5.60639E-003 0.00000
144 FLOOR 2 EXAM HALL 6 Cooling 650.87384 650.87384 5.68947E-002 5.68947E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 18.39480 0.00000 5.60639E-003 0.00000
145 FLOOR 2 EXAM HALL 6 Heating 226.11009 226.11009 1.00538E-002 1.00538E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 18.39480 0.00000 5.60639E-003 0.00000
146 FLOOR 2 JANITOR Cooling 386.71593 386.71593 3.41871E-002 3.41871E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 5.85289 0.00000 3.56770E-003 0.00000
147 FLOOR 2 JANITOR Heating 525.52829 525.52829 2.34088E-002 2.34088E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 5.85289 0.00000 3.56770E-003 0.00000
148 FLOOR 2 LOUNGE Cooling 437.59465 437.59465 3.86648E-002 3.86648E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 7.43224 1.20012 5.09671E-003 0.00000
149 FLOOR 2 LOUNGE Heating 0.00000 0.00000 0.00000 5.09671E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 7.43224 1.20012 5.09671E-003 0.00000
150 FLOOR 2 NURSE STATION 1 Cooling 698.97244 698.97244 6.31495E-002 6.31495E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 20.92400 1.27032E-002 13.93546 3.00029 1.13260E-002 0.00000
151 FLOOR 2 NURSE STATION 1 Heating 0.00000 0.00000 0.00000 1.13260E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 13.93546 3.00029 1.13260E-002 0.00000
152 FLOOR 2 NURSE STATION 2 Cooling 860.47009 860.47009 7.58335E-002 7.58335E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 16.72255 3.60035 1.35912E-002 0.00000
153 FLOOR 2 NURSE STATION 2 Heating 0.00000 0.00000 0.00000 1.35912E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 16.72255 3.60035 1.35912E-002 0.00000
154 FLOOR 2 OFFICE Cooling 2663.99058 2663.99058 0.24066 0.24066 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:40:00 22.49467 1.27032E-002 52.02570 2.80027 2.24633E-002 0.00000
155 FLOOR 2 OFFICE Heating 2147.88775 2147.88775 9.49837E-002 9.49837E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 52.02570 2.80027 2.24633E-002 0.00000
156 FLOOR 2 OFFICE HALL Cooling 1509.30747 1509.30747 0.13204 0.13204 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 41.24895 0.00000 1.25719E-002 0.00000
157 FLOOR 2 OFFICE HALL Heating 665.39936 665.39936 2.95039E-002 2.95039E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 41.24895 0.00000 1.25719E-002 0.00000
158 FLOOR 2 RECEPTION Cooling 5128.61541 5128.61541 0.46347 0.46347 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 28.36400 1.27032E-002 91.41659 29.52287 9.75171E-002 0.00000
159 FLOOR 2 RECEPTION Heating 2560.94460 2560.94460 0.11249 0.11249 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 91.41659 29.52287 9.75171E-002 0.00000
160 FLOOR 2 RECEPTION HALL Cooling 1959.24088 1959.24088 0.17149 0.17149 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 52.39731 0.00000 1.59697E-002 0.00000
161 FLOOR 2 RECEPTION HALL Heating 0.00000 0.00000 0.00000 1.59697E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 52.39731 0.00000 1.59697E-002 0.00000
162 FLOOR 2 RECEPTION TOILET Cooling 407.56058 407.56058 3.56194E-002 3.56194E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 11.70578 0.00000 0.00000 0.00000
163 FLOOR 2 RECEPTION TOILET Heating 69.46698 69.46698 3.09982E-003 3.09982E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 11.70578 0.00000 0.00000 0.00000
164 FLOOR 2 SCHEDULING 1 Cooling 1068.57944 1068.57944 9.33867E-002 9.33867E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 30.10058 1.62016 1.29966E-002 0.00000
165 FLOOR 2 SCHEDULING 1 Heating 0.00000 0.00000 0.00000 1.29966E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 30.10058 1.62016 1.29966E-002 0.00000
166 FLOOR 2 SCHEDULING 2 Cooling 1180.22221 1180.22221 0.10326 0.10326 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 31.77284 1.71017 1.37187E-002 0.00000
167 FLOOR 2 SCHEDULING 2 Heating 0.00000 0.00000 0.00000 1.37187E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 31.77284 1.71017 1.37187E-002 0.00000
168 FLOOR 2 STORAGE 1 Cooling 185.25533 185.25533 1.62357E-002 1.62357E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 5.20257 0.00000 3.17129E-003 0.00000
169 FLOOR 2 STORAGE 1 Heating 82.59767 82.59767 3.67676E-003 3.67676E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 5.20257 0.00000 3.17129E-003 0.00000
170 FLOOR 2 STORAGE 2 Cooling 320.68079 320.68079 2.80108E-002 2.80108E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 11.14836 0.00000 6.79562E-003 0.00000
171 FLOOR 2 STORAGE 2 Heating 95.84706 95.84706 4.27167E-003 6.79562E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 11.14836 0.00000 6.79562E-003 0.00000
172 FLOOR 2 STORAGE 3 Cooling 416.66821 416.66821 3.63129E-002 3.63129E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 13.37804 0.00000 8.15474E-003 0.00000
173 FLOOR 2 STORAGE 3 Heating 101.24498 101.24498 4.51424E-003 8.15474E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 13.37804 0.00000 8.15474E-003 0.00000
174 FLOOR 2 UTILITY Cooling 593.89166 593.89166 5.36477E-002 5.36477E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:40:00 22.49467 1.27032E-002 11.70578 0.00000 7.13540E-003 0.00000
175 FLOOR 2 UTILITY Heating 611.67615 611.67615 2.71301E-002 2.71301E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 11.70578 0.00000 7.13540E-003 0.00000
176 FLOOR 2 WORK Cooling 4829.76222 4829.76222 0.41980 0.41980 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 157.00614 8.45082 6.77910E-002 0.00000
177 FLOOR 2 WORK Heating 1305.50612 1305.50612 5.74968E-002 6.77910E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 157.00614 8.45082 6.77910E-002 0.00000
178 FLOOR 2 WORK HALL Cooling 2655.27790 2655.27790 0.23197 0.23197 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 77.48114 0.00000 2.36148E-002 0.00000
179 FLOOR 2 WORK HALL Heating 9.12704 9.12704 4.08956E-004 2.36148E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 -32.70000 1.83376E-004 77.48114 0.00000 2.36148E-002 0.00000
180 FLOOR 2 WORK TOILET Cooling 209.54470 209.54470 1.83863E-002 1.83863E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 5.01676 0.00000 0.00000 0.00000
181 FLOOR 2 WORK TOILET Heating 316.48908 316.48908 1.40654E-002 1.40654E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 5.01676 0.00000 0.00000 0.00000
182 FLOOR 2 X-RAY Cooling 9339.09404 9339.09404 0.84376 0.84376 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 20.92400 1.27032E-002 83.61274 18.00175 0.12742 0.00000
183 FLOOR 2 X-RAY Heating 0.00000 0.00000 0.00000 0.12742 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70000 1.83376E-004 83.61274 18.00175 0.12742 0.00000
184 FLOOR 3 DRESSING ROOM Cooling 200.40988 200.40988 1.76724E-002 1.76724E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 3.90193 0.21002 1.68475E-003 0.00000
185 FLOOR 3 DRESSING ROOM Heating 145.93748 145.93748 6.43821E-003 6.43821E-003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 3.90193 0.21002 1.68475E-003 0.00000
186 FLOOR 3 ELEVATOR HALL Cooling 889.80019 889.80019 7.70350E-002 7.70350E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 34.37412 0.00000 1.04766E-002 0.00000
187 FLOOR 3 ELEVATOR HALL Heating 1159.90971 1159.90971 5.11221E-002 5.11221E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 34.37412 0.00000 1.04766E-002 0.00000
188 FLOOR 3 HUMID Cooling 478.06457 478.06457 4.20600E-002 4.20600E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 10.03353 0.54005 4.33221E-003 0.00000
189 FLOOR 3 HUMID Heating 317.65739 317.65739 1.39740E-002 1.39740E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 10.03353 0.54005 4.33221E-003 0.00000
190 FLOOR 3 JANITOR Cooling 152.63176 152.63176 1.37873E-002 1.37873E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 27.53733 1.27032E-002 5.85289 0.00000 3.56770E-003 0.00000
191 FLOOR 3 JANITOR Heating 504.62254 504.62254 2.24698E-002 2.24698E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 5.85289 0.00000 3.56770E-003 0.00000
192 FLOOR 3 LOCKER Cooling 657.95748 657.95748 5.80698E-002 5.80698E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 11.14836 1.80018 7.64507E-003 0.00000
193 FLOOR 3 LOCKER Heating 325.01735 325.01735 1.42907E-002 1.42907E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 11.14836 1.80018 7.64507E-003 0.00000
194 FLOOR 3 LOUNGE Cooling 3720.42973 3720.42973 0.33613 0.33613 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 30.10000 1.27032E-002 70.51341 11.38611 4.83551E-002 0.00000
195 FLOOR 3 LOUNGE Heating 1237.33156 1237.33156 5.36478E-002 5.36478E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 70.51341 11.38611 4.83551E-002 0.00000
196 FLOOR 3 LOUNGE TOILET Cooling 603.42157 603.42157 5.26346E-002 5.26346E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 17.83738 0.00000 0.00000 0.00000
197 FLOOR 3 LOUNGE TOILET Heating 864.73190 864.73190 3.83102E-002 3.83102E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 17.83738 0.00000 0.00000 0.00000
198 FLOOR 3 MECHANICAL Cooling 3557.75571 3557.75571 0.32137 0.32137 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 23.28000 1.27032E-002 32.51606 0.00000 0.00000 0.00000
199 FLOOR 3 MECHANICAL Heating 398.60734 398.60734 1.74857E-002 1.74857E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 32.51606 0.00000 0.00000 0.00000
200 FLOOR 3 MECHANICAL HALL Cooling 1058.25431 1058.25431 9.27554E-002 9.27554E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 27.87091 0.00000 8.49452E-003 0.00000
201 FLOOR 3 MECHANICAL HALL Heating 1225.98797 1225.98797 5.42446E-002 5.42446E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 27.87091 0.00000 8.49452E-003 0.00000
202 FLOOR 3 OFFICE Cooling 8504.04080 8504.04080 0.73861 0.73861 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 282.05363 15.18148 0.12178 0.00000
203 FLOOR 3 OFFICE Heating 7074.82348 7074.82348 0.30979 0.30979 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 282.05363 15.18148 0.12178 0.00000
204 FLOOR 3 OFFICE HALL Cooling 2435.69746 2435.69746 0.21219 0.21219 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 77.48114 0.00000 2.36148E-002 0.00000
205 FLOOR 3 OFFICE HALL Heating 2521.33396 2521.33396 0.11107 0.11107 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 77.48114 0.00000 2.36148E-002 0.00000
206 FLOOR 3 OFFICE TOILET Cooling 148.13056 148.13056 1.30225E-002 1.30225E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 5.01676 0.00000 0.00000 0.00000
207 FLOOR 3 OFFICE TOILET Heating 338.12480 338.12480 1.50251E-002 1.50251E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 5.01676 0.00000 0.00000 0.00000
208 FLOOR 3 PHYSICAL THERAPY 1 Cooling 7972.16044 7972.16044 0.72031 0.72031 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 29.58333 1.27032E-002 120.77395 26.00253 0.18405 0.00000
209 FLOOR 3 PHYSICAL THERAPY 1 Heating 4771.39758 4771.39758 0.21069 0.21069 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 120.77395 26.00253 0.18405 0.00000
210 FLOOR 3 PHYSICAL THERAPY 2 Cooling 2702.38159 2702.38159 0.24419 0.27938 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 29.99667 1.27032E-002 54.99860 11.84115 8.38126E-002 0.00000
211 FLOOR 3 PHYSICAL THERAPY 2 Heating 1449.94984 1449.94984 6.35880E-002 8.38126E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 54.99860 11.84115 8.38126E-002 0.00000
212 FLOOR 3 PHYSICAL THERAPY TOILET Cooling 279.29486 279.29486 2.44549E-002 2.44549E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 7.80386 0.00000 0.00000 0.00000
213 FLOOR 3 PHYSICAL THERAPY TOILET Heating 280.16413 280.16413 1.23537E-002 1.23537E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 7.80386 0.00000 0.00000 0.00000
214 FLOOR 3 STORAGE 1 Cooling 278.88726 278.88726 2.45266E-002 2.45266E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 10.03353 0.00000 6.11606E-003 0.00000
215 FLOOR 3 STORAGE 1 Heating 408.29461 408.29461 1.80559E-002 1.80559E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 10.03353 0.00000 6.11606E-003 0.00000
216 FLOOR 3 STORAGE 2 Cooling 252.21519 252.21519 2.21287E-002 2.21287E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 7.80386 0.00000 4.75693E-003 0.00000
217 FLOOR 3 STORAGE 2 Heating 348.29522 348.29522 1.54197E-002 1.54197E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 7.80386 0.00000 4.75693E-003 0.00000
218 FLOOR 3 TREATMENT Cooling 2243.21175 2243.21175 0.20270 0.22463 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 30.10000 1.27032E-002 44.22185 9.52093 6.73899E-002 0.00000
219 FLOOR 3 TREATMENT Heating 1109.92626 1109.92626 4.85982E-002 6.73899E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 44.22185 9.52093 6.73899E-002 0.00000
220 FLOOR 3 UNDEVELOPED 1 Cooling 7478.05761 7478.05761 0.67548 0.67548 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 28.69467 1.27032E-002 210.70409 0.00000 0.12844 0.00000
221 FLOOR 3 UNDEVELOPED 1 Heating 6198.53481 6198.53481 0.27236 0.27236 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 210.70409 0.00000 0.12844 0.00000
222 FLOOR 3 UNDEVELOPED 2 Cooling 3790.81707 3790.81707 0.34242 0.34242 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 28.69467 1.27032E-002 107.02430 0.00000 6.52379E-002 0.00000
223 FLOOR 3 UNDEVELOPED 2 Heating 4049.76319 4049.76319 0.17873 0.17873 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 107.02430 0.00000 6.52379E-002 0.00000
224 FLOOR 3 UTILITY Cooling 413.89211 413.89211 3.63066E-002 3.63066E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.81600 1.27032E-002 20.06706 0.00000 1.22321E-002 0.00000
225 FLOOR 3 UTILITY Heating 716.13665 716.13665 3.15966E-002 3.15966E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 20.06706 0.00000 1.22321E-002 0.00000
226 FLOOR 3 WORK Cooling 3233.34041 3233.34041 0.29208 0.29208 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 22.88733 1.27032E-002 53.32634 2.87028 2.30249E-002 0.00000
227 FLOOR 3 WORK Heating 2386.76352 2386.76352 0.10561 0.10561 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 53.32634 2.87028 2.30249E-002 0.00000
228 NE STAIR Cooling 1027.75842 1027.75842 9.28414E-002 9.28414E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 30.10000 1.27032E-002 15.60771 0.00000 4.75693E-003 0.00000
229 NE STAIR Heating 3622.88145 3622.88145 0.16117 0.16117 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 15.60771 0.00000 4.75693E-003 0.00000
230 NW ELEVATOR Cooling 865.17196 865.17196 7.81524E-002 7.81524E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 27.33067 1.27032E-002 13.00643 0.00000 3.96411E-003 0.00000
231 NW ELEVATOR Heating 2379.85223 2379.85223 0.10567 0.10567 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 13.00643 0.00000 3.96411E-003 0.00000
232 NW STAIR Cooling 1047.66111 1047.66111 9.46395E-002 9.46395E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 28.69467 1.27032E-002 17.83738 0.00000 5.43650E-003 0.00000
233 NW STAIR Heating 3715.90707 3715.90707 0.16515 0.16515 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 17.83738 0.00000 5.43650E-003 0.00000
234 SW STAIR Cooling 740.68837 740.68837 6.69090E-002 6.69090E-002 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 28.52933 1.27032E-002 8.91869 0.00000 2.71825E-003 0.00000
235 SW STAIR Heating 1814.15386 1814.15386 8.06102E-002 8.06102E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 8.91869 0.00000 2.71825E-003 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 AHU-1 Cooling Sensible 117750.93 6.91716 6.91716 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 AHU-1 Heating Sensible 114868.53 2.50668 2.50668 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:50:00
3 AHU-2 Cooling Sensible 141302.06 9.20300 9.20300 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 AHU-2 Heating Sensible 142104.78 3.54373 3.54373 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 10:40:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.90760E-002
2 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
3 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
4 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.90760E-002
5 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.44560E-003
8 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.43682E-005
9 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.90760E-002
10 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
11 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ANESTHESIA VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
12 Coil:Heating:Water FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL Design Size Rated Capacity [W] 656.23793
13 Coil:Heating:Water FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.43682E-005
14 Coil:Heating:Water FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 12.56781
15 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.93999E-003
16 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.49929
17 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
18 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.58800E-003
19 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
20 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.63083E-004
22 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.51266E-006
23 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.62299E-003
24 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
25 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 BIO HAZ VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
26 Coil:Heating:Water FLOOR 1 BIO HAZ VAV BOX REHEAT COIL Design Size Rated Capacity [W] 160.43422
27 Coil:Heating:Water FLOOR 1 BIO HAZ VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.51266E-006
28 Coil:Heating:Water FLOOR 1 BIO HAZ VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3.45307
29 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CAFE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.29587
30 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CAFE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10049
31 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CAFE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
32 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CAFE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.91741E-002
33 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CAFE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.47851
34 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CAFE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CAFE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.79134E-003
36 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CAFE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.34429E-005
37 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CAFE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.91741E-002
38 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CAFE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
39 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CAFE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
40 Coil:Heating:Water FLOOR 1 CAFE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1070.71140
41 Coil:Heating:Water FLOOR 1 CAFE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.34429E-005
42 Coil:Heating:Water FLOOR 1 CAFE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 21.14627
43 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.04340E-002
44 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.78600
45 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
46 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.04340E-002
47 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.15423E-003
50 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.62656E-006
51 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.04340E-002
52 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
53 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
54 Coil:Heating:Water FLOOR 1 CLEAN VAV BOX REHEAT COIL Design Size Rated Capacity [W] 302.65521
55 Coil:Heating:Water FLOOR 1 CLEAN VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.62656E-006
56 Coil:Heating:Water FLOOR 1 CLEAN VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 5.33206
57 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.22427E-002
58 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.83401
59 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
60 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.22427E-002
61 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.03023E-003
64 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.17812E-006
65 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.22427E-002
66 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
67 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 CLEAN WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
68 Coil:Heating:Water FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL Design Size Rated Capacity [W] 373.51979
69 Coil:Heating:Water FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.17812E-006
70 Coil:Heating:Water FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6.58052
71 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.70051E-002
72 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
73 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
74 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.58063E-003
75 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.86213E-007
76 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.70051E-003
77 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
78 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DICTATION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
79 Coil:Heating:Water FLOOR 1 DICTATION VAV BOX REHEAT COIL Design Size Rated Capacity [W] 22.20682
80 Coil:Heating:Water FLOOR 1 DICTATION VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.86213E-007
81 Coil:Heating:Water FLOOR 1 DICTATION VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 0.39123
82 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.60560E-002
83 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
84 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
85 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.92028E-003
86 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.00003E-005
87 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.60560E-002
88 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
89 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 DRESSING ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
90 Coil:Heating:Water FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 456.74465
91 Coil:Heating:Water FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.00003E-005
92 Coil:Heating:Water FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 9.82287
93 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.53331E-002
94 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15304
95 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
96 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.06662E-003
97 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
98 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
99 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.48960E-003
100 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.88319E-006
101 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.06662E-003
102 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
103 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
104 Coil:Heating:Water FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 131.68428
105 Coil:Heating:Water FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.88319E-006
106 Coil:Heating:Water FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2.53955
107 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.29797
108 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 2.16199E-002
109 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
110 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.95941E-002
111 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.47513
112 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
113 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.76227E-002
114 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.05148E-005
115 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.95941E-002
116 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
117 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
118 Coil:Heating:Water FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 936.97212
119 Coil:Heating:Water FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.05148E-005
120 Coil:Heating:Water FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 18.20864
121 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.77976E-002
122 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
123 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
124 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.77381E-003
125 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.33844E-007
126 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.77976E-003
127 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
128 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 HUMID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
129 Coil:Heating:Water FLOOR 1 HUMID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10.68038
130 Coil:Heating:Water FLOOR 1 HUMID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.33844E-007
131 Coil:Heating:Water FLOOR 1 HUMID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 0.18816
132 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.47000E-002
133 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.40125
134 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
135 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.94000E-003
136 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
137 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
138 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.49531E-004
139 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.49070E-007
140 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.94000E-003
141 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
142 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
143 Coil:Heating:Water FLOOR 1 IT HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 29.64505
144 Coil:Heating:Water FLOOR 1 IT HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.49070E-007
145 Coil:Heating:Water FLOOR 1 IT HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 0.52227
146 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.69488E-002
147 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
148 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
149 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.29497E-003
150 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 0.00000
151 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.69488E-003
152 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
153 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 IT ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
154 Coil:Heating:Water FLOOR 1 IT ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 0.00000
155 Coil:Heating:Water FLOOR 1 IT ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 0.00000
156 Coil:Heating:Water FLOOR 1 IT ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1.00000
157 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.27348
158 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16101
159 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
160 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.46952E-002
161 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51769
162 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
163 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.36630E-003
164 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.25542E-005
165 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.75185E-002
166 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
167 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
168 Coil:Heating:Water FLOOR 1 LOBBY VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1943.57984
169 Coil:Heating:Water FLOOR 1 LOBBY VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.25542E-005
170 Coil:Heating:Water FLOOR 1 LOBBY VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 41.93201
171 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.65401E-002
172 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30050
173 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
174 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.13080E-002
175 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
176 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
177 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.26790E-003
178 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.48577E-006
179 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.13080E-002
180 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
181 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
182 Coil:Heating:Water FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 67.85963
183 Coil:Heating:Water FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.48577E-006
184 Coil:Heating:Water FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1.19552
185 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.61542E-002
186 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
187 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
188 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.61542E-002
189 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
190 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
191 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.60334E-003
192 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.16871E-005
193 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.61542E-002
194 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
195 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOBBY TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
196 Coil:Heating:Water FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL Design Size Rated Capacity [W] 533.78752
197 Coil:Heating:Water FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.16871E-005
198 Coil:Heating:Water FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 10.30965
199 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.23564
200 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19828
201 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
202 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.71290E-002
203 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.60080
204 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
205 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.92156E-003
206 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.19231E-006
207 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.71290E-002
208 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
209 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
210 Coil:Heating:Water FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 282.82195
211 Coil:Heating:Water FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.19231E-006
212 Coil:Heating:Water FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4.98264
213 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.53396E-002
214 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.41145
215 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
216 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.70679E-002
217 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
218 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
219 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.25996E-004
220 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.24257E-006
221 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.70679E-002
222 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
223 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
224 Coil:Heating:Water FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 102.42494
225 Coil:Heating:Water FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.24257E-006
226 Coil:Heating:Water FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1.80448
227 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.13059
228 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19515
229 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
230 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.61184E-002
231 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
232 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
233 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.95233E-003
234 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.43171E-006
235 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.61184E-002
236 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
237 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 LOUNGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
238 Coil:Heating:Water FLOOR 1 LOUNGE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 156.73684
239 Coil:Heating:Water FLOOR 1 LOUNGE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.43171E-006
240 Coil:Heating:Water FLOOR 1 LOUNGE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2.76133
241 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.92482E-002
242 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13554
243 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
244 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.84964E-003
245 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
246 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
247 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.81094E-003
248 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.81949E-005
249 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.92482E-002
250 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
251 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MED GAS VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
252 Coil:Heating:Water FLOOR 1 MED GAS VAV BOX REHEAT COIL Design Size Rated Capacity [W] 831.01511
253 Coil:Heating:Water FLOOR 1 MED GAS VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.81949E-005
254 Coil:Heating:Water FLOOR 1 MED GAS VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 17.86627
255 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.14385
256 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
257 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
258 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.87691E-002
259 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.98422
260 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
261 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.60816E-003
262 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.78000E-006
263 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.87691E-002
264 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
265 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
266 Coil:Heating:Water FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 172.64410
267 Coil:Heating:Water FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.78000E-006
268 Coil:Heating:Water FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3.04157
269 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.31566E-002
270 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.31386
271 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
272 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.63131E-003
273 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
274 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
275 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.21393E-003
276 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.73761E-007
277 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.63131E-003
278 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
279 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
280 Coil:Heating:Water FLOOR 1 MRI HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 44.47465
281 Coil:Heating:Water FLOOR 1 MRI HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.73761E-007
282 Coil:Heating:Water FLOOR 1 MRI HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 0.78971
283 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.36786
284 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI ROOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
285 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI ROOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
286 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI ROOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.35711E-002
287 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.38487
288 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
289 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.49950E-003
290 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.66656E-006
291 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.35711E-002
292 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
293 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
294 Coil:Heating:Water FLOOR 1 MRI ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 441.50161
295 Coil:Heating:Water FLOOR 1 MRI ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.66656E-006
296 Coil:Heating:Water FLOOR 1 MRI ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7.77820
297 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.77969E-003
298 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
299 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
300 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.77969E-003
301 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
302 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
303 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.74701E-004
304 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.11987E-006
305 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.77969E-003
306 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
307 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 MRI TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
308 Coil:Heating:Water FLOOR 1 MRI TOILET VAV BOX REHEAT COIL Design Size Rated Capacity [W] 279.51325
309 Coil:Heating:Water FLOOR 1 MRI TOILET VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.11987E-006
310 Coil:Heating:Water FLOOR 1 MRI TOILET VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6.01881
311 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.14886E-002
312 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18023
313 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
314 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.42977E-002
315 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
316 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
317 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.11400E-003
318 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.87859E-006
319 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.42977E-002
320 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
321 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NOURISHMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
322 Coil:Heating:Water FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 85.80087
323 Coil:Heating:Water FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.87859E-006
324 Coil:Heating:Water FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1.51161
325 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.10397
326 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33772
327 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
328 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.07941E-002
329 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
330 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
331 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.12816E-003
332 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.96279E-006
333 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.07941E-002
334 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
335 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
336 Coil:Heating:Water FLOOR 1 NURSE HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 135.31984
337 Coil:Heating:Water FLOOR 1 NURSE HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.96279E-006
338 Coil:Heating:Water FLOOR 1 NURSE HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2.39747
339 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.25087E-002
340 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30561
341 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
342 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.50173E-003
343 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
344 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
345 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.24669E-003
346 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.28705E-007
347 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.50173E-003
348 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
349 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
350 Coil:Heating:Water FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15.01296
351 Coil:Heating:Water FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.28705E-007
352 Coil:Heating:Water FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 0.26449
353 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.75484E-002
354 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18941
355 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
356 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.95097E-002
357 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
358 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
359 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.01150E-003
360 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.56339E-006
361 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.95097E-002
362 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
363 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE STATION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
364 Coil:Heating:Water FLOOR 1 NURSE STATION VAV BOX REHEAT COIL Design Size Rated Capacity [W] 117.07794
365 Coil:Heating:Water FLOOR 1 NURSE STATION VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.56339E-006
366 Coil:Heating:Water FLOOR 1 NURSE STATION VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2.06263
367 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.54750E-002
368 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
369 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
370 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.54750E-002
371 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
372 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
373 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.54233E-003
374 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.03328E-006
375 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.54750E-002
376 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
377 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 NURSE TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
378 Coil:Heating:Water FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL Design Size Rated Capacity [W] 92.86599
379 Coil:Heating:Water FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.03328E-006
380 Coil:Heating:Water FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1.63608
381 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.11045
382 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
383 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
384 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.23068E-003
385 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.45117E-006
386 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.10447E-002
387 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
388 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OFFICE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
389 Coil:Heating:Water FLOOR 1 OFFICE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 66.27932
390 Coil:Heating:Water FLOOR 1 OFFICE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.45117E-006
391 Coil:Heating:Water FLOOR 1 OFFICE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1.16768
392 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.72361
393 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.60000
394 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
395 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.46614E-003
396 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.34892E-005
397 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.43416
398 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
399 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
400 Coil:Heating:Water FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1072.82387
401 Coil:Heating:Water FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.34892E-005
402 Coil:Heating:Water FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 18.19449
403 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.75507
404 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.60000
405 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
406 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.46614E-003
407 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 0.00000
408 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.45304
409 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
410 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
411 Coil:Heating:Water FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 0.00000
412 Coil:Heating:Water FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 0.00000
413 Coil:Heating:Water FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1.00000
414 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.74878
415 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
416 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
417 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.74878
418 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
419 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
420 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.46614E-003
421 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.05103E-005
422 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.74878
423 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
424 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
425 Coil:Heating:Water FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1850.23247
426 Coil:Heating:Water FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.05103E-005
427 Coil:Heating:Water FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 31.37890
428 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.09671E-002
429 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
430 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
431 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.09671E-002
432 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
433 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
434 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
435 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.69661E-006
436 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.09671E-002
437 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
438 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PACU VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
439 Coil:Heating:Water FLOOR 1 PACU VAV BOX REHEAT COIL Design Size Rated Capacity [W] 305.85478
440 Coil:Heating:Water FLOOR 1 PACU VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.69661E-006
441 Coil:Heating:Water FLOOR 1 PACU VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 5.38843
442 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.10052
443 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.37187
444 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
445 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.01030E-002
446 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
447 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
448 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.02456E-003
449 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.64135E-006
450 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.01030E-002
451 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
452 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
453 Coil:Heating:Water FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 120.63861
454 Coil:Heating:Water FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.64135E-006
455 Coil:Heating:Water FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2.12536
456 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.91925E-002
457 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
458 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
459 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.91925E-002
460 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
461 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
462 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
463 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.17191E-005
464 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.91925E-002
465 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
466 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
467 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 535.24586
468 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.17191E-005
469 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 9.42975
470 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.15951
471 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
472 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
473 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.15951
474 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
475 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
476 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
477 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.09579E-005
478 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.15951
479 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
480 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
481 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 957.21218
482 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.09579E-005
483 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 16.86378
484 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.24292E-002
485 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
486 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
487 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.24292E-002
488 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
489 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
490 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.23876E-003
491 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.76136E-006
492 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.24292E-002
493 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
494 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
495 Coil:Heating:Water FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL Design Size Rated Capacity [W] 354.48543
496 Coil:Heating:Water FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.76136E-006
497 Coil:Heating:Water FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7.62888
498 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.33624
499 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
500 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
501 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.33624
502 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
503 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
504 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.34960E-003
505 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.27582E-005
506 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.33624
507 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
508 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
509 Coil:Heating:Water FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2409.63098
510 Coil:Heating:Water FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.27582E-005
511 Coil:Heating:Water FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 43.00782
512 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.18399
513 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19584
514 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
515 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.67987E-002
516 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.76946
517 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
518 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.94547E-003
519 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 0.00000
520 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.67987E-002
521 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
522 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
523 Coil:Heating:Water FLOOR 1 RECEPTION VAV BOX REHEAT COIL Design Size Rated Capacity [W] 0.00000
524 Coil:Heating:Water FLOOR 1 RECEPTION VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 0.00000
525 Coil:Heating:Water FLOOR 1 RECEPTION VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1.00000
526 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.58495E-002
527 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.35054
528 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
529 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.16990E-003
530 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
531 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
532 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.08688E-003
533 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.79277E-007
534 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.16990E-003
535 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
536 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECEPTION HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
537 Coil:Heating:Water FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 31.02469
538 Coil:Heating:Water FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.79277E-007
539 Coil:Heating:Water FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 0.54658
540 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.27161
541 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.93825
542 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.87000
543 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23630
544 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.87000
545 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
546 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.70698E-003
547 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.61458E-005
548 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.23630
549 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
550 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
551 Coil:Heating:Water FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3021.08338
552 Coil:Heating:Water FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.61458E-005
553 Coil:Heating:Water FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 57.58647
554 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.01098E-002
555 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
556 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
557 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.36176E-003
558 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.14151E-006
559 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.03111E-003
560 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
561 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCHEDULING VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
562 Coil:Heating:Water FLOOR 1 SCHEDULING VAV BOX REHEAT COIL Design Size Rated Capacity [W] 143.48260
563 Coil:Heating:Water FLOOR 1 SCHEDULING VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.14151E-006
564 Coil:Heating:Water FLOOR 1 SCHEDULING VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3.08785
565 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.75308E-002
566 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33921
567 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
568 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.50616E-003
569 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
570 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
571 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.12321E-003
572 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.35355E-006
573 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.37594E-003
574 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
575 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SCRUB VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
576 Coil:Heating:Water FLOOR 1 SCRUB VAV BOX REHEAT COIL Design Size Rated Capacity [W] 153.16702
577 Coil:Heating:Water FLOOR 1 SCRUB VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.35355E-006
578 Coil:Heating:Water FLOOR 1 SCRUB VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3.29541
579 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.01519E-002
580 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
581 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
582 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.01519E-002
583 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
584 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
585 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.14218E-003
586 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.58949E-006
587 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.01519E-002
588 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
589 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
590 Coil:Heating:Water FLOOR 1 SOIL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 300.96249
591 Coil:Heating:Water FLOOR 1 SOIL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.58949E-006
592 Coil:Heating:Water FLOOR 1 SOIL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 5.30224
593 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.95750E-002
594 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
595 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
596 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.95750E-002
597 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
598 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
599 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.88128E-003
600 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 0.00000
601 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.95750E-002
602 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
603 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL HOLD VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
604 Coil:Heating:Water FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL Design Size Rated Capacity [W] 0.00000
605 Coil:Heating:Water FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 0.00000
606 Coil:Heating:Water FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1.00000
607 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.66183E-002
608 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
609 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
610 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.66183E-002
611 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
612 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
613 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.99187E-003
614 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.75303E-006
615 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.66183E-002
616 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
617 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SOIL WORK VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
618 Coil:Heating:Water FLOOR 1 SOIL WORK VAV BOX REHEAT COIL Design Size Rated Capacity [W] 399.77800
619 Coil:Heating:Water FLOOR 1 SOIL WORK VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.75303E-006
620 Coil:Heating:Water FLOOR 1 SOIL WORK VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7.04313
621 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.16145
622 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.87691
623 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.69000
624 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11140
625 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.87691
626 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
627 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.89636E-003
628 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.38422E-005
629 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.11140
630 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
631 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STEP DOWN VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
632 Coil:Heating:Water FLOOR 1 STEP DOWN VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2002.40700
633 Coil:Heating:Water FLOOR 1 STEP DOWN VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.38422E-005
634 Coil:Heating:Water FLOOR 1 STEP DOWN VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 39.51349
635 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.99983E-002
636 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.43609
637 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
638 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.99997E-002
639 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
640 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
641 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.73680E-004
642 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.56472E-006
643 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.99997E-002
644 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
645 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
646 Coil:Heating:Water FLOOR 1 STERILE HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 436.85002
647 Coil:Heating:Water FLOOR 1 STERILE HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.56472E-006
648 Coil:Heating:Water FLOOR 1 STERILE HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 8.87552
649 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.09220E-002
650 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.46016
651 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
652 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.21844E-002
653 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
654 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
655 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.27979E-004
656 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.60092E-006
657 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.21844E-002
658 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
659 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STERILE STORAGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
660 Coil:Heating:Water FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 73.11887
661 Coil:Heating:Water FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.60092E-006
662 Coil:Heating:Water FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1.28818
663 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.20158
664 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32310
665 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
666 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.03152E-002
667 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.86159
668 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
669 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.17921E-003
670 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.25997E-004
671 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.20158
672 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
673 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 STORAGE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
674 Coil:Heating:Water FLOOR 1 STORAGE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5754.64902
675 Coil:Heating:Water FLOOR 1 STORAGE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.25997E-004
676 Coil:Heating:Water FLOOR 1 STORAGE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 123.87808
677 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.47745E-002
678 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30989
679 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
680 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.95489E-003
681 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
682 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
683 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.22946E-003
684 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.28751E-005
685 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.65637E-002
686 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
687 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 SUB-STERILE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
688 Coil:Heating:Water FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1044.77502
689 Coil:Heating:Water FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.28751E-005
690 Coil:Heating:Water FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 22.49590
691 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.95162E-002
692 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30450
693 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
694 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.19032E-002
695 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
696 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
697 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.25122E-003
698 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.71752E-005
699 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.95162E-002
700 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
701 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY HALL VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
702 Coil:Heating:Water FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1697.90400
703 Coil:Heating:Water FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.71752E-005
704 Coil:Heating:Water FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 36.54333
705 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.73507E-003
706 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34038
707 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
708 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.74701E-003
709 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
710 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
711 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.11933E-003
712 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.57791E-006
713 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.53452E-003
714 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
715 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
716 Coil:Heating:Water FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL Design Size Rated Capacity [W] 72.06809
717 Coil:Heating:Water FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.57791E-006
718 Coil:Heating:Water FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1.54974
719 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.11993E-002
720 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.41643
721 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
722 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.22399E-002
723 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
724 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
725 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.14921E-004
726 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.83258E-005
727 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.11993E-002
728 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
729 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 UTILITY ROOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
730 Coil:Heating:Water FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1750.45686
731 Coil:Heating:Water FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.83258E-005
732 Coil:Heating:Water FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 37.70055
733 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.65155E-002
734 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30862
735 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
736 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.30309E-003
737 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
738 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
739 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.23452E-003
740 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.03145E-005
741 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.65155E-002
742 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.00000
743 AirTerminal:SingleDuct:VAV:Reheat FLOOR 1 VESTIBULE VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
744 Coil:Heating:Water FLOOR 1 VESTIBULE VAV BOX REHEAT COIL Design Size Rated Capacity [W] 471.09713
745 Coil:Heating:Water FLOOR 1 VESTIBULE VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.03145E-005
746 Coil:Heating:Water FLOOR 1 VESTIBULE VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 10.13888
747 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.22139
748 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10744
749 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33300
750 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.37214E-002
751 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.63950
752 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
753 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.54609E-003
754 Coil:Heating:Electric FLOOR 2 CONFERENCE VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 2088.67400
755 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.95663E-002
756 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
757 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
758 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.95663E-002
759 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
760 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
761 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.64539E-003
762 Coil:Heating:Electric FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 552.55516
763 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.58271E-002
764 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19187
765 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.16300
766 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.20983E-003
767 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
768 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
769 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 DICTATION VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.98572E-003
770 Coil:Heating:Electric FLOOR 2 DICTATION VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 118.88585
771 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.24123
772 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.70428
773 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.51000
774 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12303
775 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58690
776 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
777 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.60632E-003
778 Coil:Heating:Electric FLOOR 2 EXAM 1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 3474.26305
779 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.25484
780 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
781 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
782 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.25484
783 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
784 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
785 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
786 Coil:Heating:Electric FLOOR 2 EXAM 2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 7196.58303
787 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.33978
788 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
789 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
790 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.33978
791 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
792 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
793 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
794 Coil:Heating:Electric FLOOR 2 EXAM 3 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 9595.44404
795 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.94624E-002
796 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.80144
797 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.64000
798 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.16560E-002
799 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
800 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
801 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.16910E-003
802 Coil:Heating:Electric FLOOR 2 EXAM 4 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 893.96703
803 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.20717
804 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.79726
805 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.69000
806 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.14295
807 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.69000
808 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
809 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 5 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.18573E-003
810 Coil:Heating:Electric FLOOR 2 EXAM 5 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 4036.93773
811 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.10618
812 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
813 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.94000
814 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.98106E-002
815 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
816 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
817 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
818 Coil:Heating:Electric FLOOR 2 EXAM 6 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 2818.66169
819 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.37376
820 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
821 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
822 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.37376
823 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
824 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
825 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 7 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
826 Coil:Heating:Electric FLOOR 2 EXAM 7 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 10554.98845
827 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.12742
828 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
829 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.93000
830 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11850
831 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
832 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
833 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 8 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
834 Coil:Heating:Electric FLOOR 2 EXAM 8 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 3346.41111
835 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.18688
836 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
837 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
838 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.18688
839 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
840 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
841 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM 9 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
842 Coil:Heating:Electric FLOOR 2 EXAM 9 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 5277.49422
843 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.58241E-002
844 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22826
845 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.13700
846 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.64790E-003
847 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
848 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
849 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.66913E-003
850 Coil:Heating:Electric FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 513.23983
851 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.54032E-002
852 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23000
853 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.13800
854 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.64564E-003
855 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
856 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
857 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.65654E-003
858 Coil:Heating:Electric FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 323.55886
859 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.32651E-002
860 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23923
861 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.14400
862 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.67018E-003
863 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
864 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
865 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.59261E-003
866 Coil:Heating:Electric FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 335.29763
867 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.45710E-002
868 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25686
869 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.15400
870 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.40393E-003
871 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
872 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
873 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.48333E-003
874 Coil:Heating:Electric FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 237.32769
875 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.73146E-002
876 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24456
877 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.14700
878 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.42525E-003
879 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
880 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
881 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.55790E-003
882 Coil:Heating:Electric FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 237.92980
883 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.68947E-002
884 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24636
885 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.14800
886 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.42042E-003
887 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
888 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
889 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.54649E-003
890 Coil:Heating:Electric FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 283.91886
891 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.41871E-002
892 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13046
893 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.15700
894 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.36738E-003
895 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
896 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
897 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 JANITOR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.92053E-003
898 Coil:Heating:Electric FLOOR 2 JANITOR VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 661.06543
899 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.86648E-002
900 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14647
901 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.19800
902 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.65563E-003
903 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
904 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
905 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 LOUNGE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.60115E-003
906 Coil:Heating:Electric FLOOR 2 LOUNGE VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 216.19585
907 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.31495E-002
908 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16815
909 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.26900
910 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.69872E-002
911 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
912 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
913 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.26579E-003
914 Coil:Heating:Electric FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 479.72052
915 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.58335E-002
916 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16803
917 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.26900
918 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.03992E-002
919 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
920 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
921 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.26740E-003
922 Coil:Heating:Electric FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 576.07546
923 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.24066
924 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16473
925 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.14000
926 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.36927E-002
927 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58828
928 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
929 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.31292E-003
930 Coil:Heating:Electric FLOOR 2 OFFICE VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 2682.34985
931 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.13204
932 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23805
933 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.14300
934 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.88818E-002
935 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
936 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
937 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 OFFICE HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.60053E-003
938 Coil:Heating:Electric FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 833.19184
939 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.46347
940 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15030
941 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31600
942 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.14646
943 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.40080
944 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
945 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53496E-003
946 Coil:Heating:Electric FLOOR 2 RECEPTION VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 4135.98605
947 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.17149
948 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23283
949 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.14000
950 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.40080E-002
951 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.82559
952 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
953 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.63640E-003
954 Coil:Heating:Electric FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 677.98889
955 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.56194E-002
956 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
957 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
958 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.56194E-002
959 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
960 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
961 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.52144E-003
962 Coil:Heating:Electric FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 1005.89475
963 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.33867E-002
964 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24561
965 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20900
966 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.95178E-002
967 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
968 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
969 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.55124E-003
970 Coil:Heating:Electric FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 551.18506
971 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.10326
972 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23447
973 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.19900
974 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.05486E-002
975 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
976 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
977 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.62496E-003
978 Coil:Heating:Electric FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 580.29509
979 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.62357E-002
980 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24418
981 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.29300
982 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.75705E-003
983 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
984 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
985 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.56035E-003
986 Coil:Heating:Electric FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 134.33967
987 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.80108E-002
988 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30328
989 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.36400
990 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.01959E-002
991 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
992 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
993 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.25627E-003
994 Coil:Heating:Electric FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 287.93407
995 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.63129E-002
996 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.28073
997 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33700
998 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.22374E-002
999 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1000 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1001 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 STORAGE 3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.35718E-003
1002 Coil:Heating:Electric FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 345.58641
1003 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.36477E-002
1004 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16627
1005 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
1006 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.07295E-002
1007 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1008 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1009 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 UTILITY VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.29151E-003
1010 Coil:Heating:Electric FLOOR 2 UTILITY VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 766.15535
1011 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.41980
1012 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.28499
1013 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24200
1014 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.10159
1015 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.75997
1016 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1017 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.33690E-003
1018 Coil:Heating:Electric FLOOR 2 WORK VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 2868.98292
1019 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.23197
1020 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25452
1021 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.15300
1022 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.54910E-002
1023 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.67872
1024 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1025 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.49693E-003
1026 Coil:Heating:Electric FLOOR 2 WORK HALL VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 1002.26915
1027 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.83863E-002
1028 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
1029 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
1030 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.83863E-002
1031 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1032 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1033 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 WORK TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.83248E-003
1034 Coil:Heating:Electric FLOOR 2 WORK TOILET VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 519.23043
1035 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 X-RAY VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.84376
1036 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 X-RAY VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
1037 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 X-RAY VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22700
1038 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 X-RAY VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.19153
1039 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 X-RAY VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
1040 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 X-RAY VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1041 AirTerminal:SingleDuct:VAV:Reheat FLOOR 2 X-RAY VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.04564E-003
1042 Coil:Heating:Electric FLOOR 2 X-RAY VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 5408.92168
1043 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.76724E-002
1044 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16824
1045 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.14300
1046 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.52715E-003
1047 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1048 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1049 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 DRESSING ROOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.26457E-003
1050 Coil:Heating:Electric FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 181.81575
1051 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.70350E-002
1052 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34002
1053 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20400
1054 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.57151E-002
1055 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1056 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1057 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.12054E-003
1058 Coil:Heating:Electric FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 1443.69196
1059 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.20600E-002
1060 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18178
1061 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.15500
1062 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.51930E-003
1063 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1064 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1065 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 HUMID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.09597E-003
1066 Coil:Heating:Electric FLOOR 3 HUMID VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 394.62579
1067 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.24698E-002
1068 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19848
1069 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.38800
1070 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.71827E-003
1071 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1072 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1073 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 JANITOR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.91955E-003
1074 Coil:Heating:Electric FLOOR 3 JANITOR VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 634.54868
1075 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.80698E-002
1076 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14629
1077 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.19700
1078 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.14397E-002
1079 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1080 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1081 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOCKER VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.60441E-003
1082 Coil:Heating:Electric FLOOR 3 LOCKER VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 403.56937
1083 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.33613
1084 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15985
1085 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.21600
1086 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.26046E-002
1087 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.42627
1088 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1089 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.38347E-003
1090 Coil:Heating:Electric FLOOR 3 LOUNGE VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 2050.36187
1091 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.26346E-002
1092 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
1093 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
1094 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.26346E-002
1095 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1096 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1097 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.47540E-003
1098 Coil:Heating:Electric FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 1486.40572
1099 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.32137
1100 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.70998E-002
1101 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000E-002
1102 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.21366E-003
1103 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.44055
1104 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1105 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.94164E-003
1106 Coil:Heating:Electric FLOOR 3 MECHANICAL VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 493.79825
1107 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.27554E-002
1108 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22896
1109 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.13700
1110 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.27075E-002
1111 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1112 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1113 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.66402E-003
1114 Coil:Heating:Electric FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 1531.87200
1115 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.73861
1116 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.29098
1117 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24700
1118 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.18244
1119 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.77596
1120 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1121 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.30935E-003
1122 Coil:Heating:Electric FLOOR 3 OFFICE VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 8748.53497
1123 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.21219
1124 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27824
1125 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.16700
1126 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.54365E-002
1127 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.74197
1128 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1129 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE HALL VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.36933E-003
1130 Coil:Heating:Electric FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 3136.63034
1131 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.50251E-002
1132 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
1133 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
1134 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.50251E-002
1135 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1136 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1137 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 OFFICE TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.49749E-003
1138 Coil:Heating:Electric FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 424.30987
1139 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.72031
1140 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.85170
1141 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.69000
1142 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.49702
1143 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.69000
1144 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1145 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.98207E-003
1146 Coil:Heating:Electric FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 14035.78672
1147 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.27938
1148 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
1149 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.83000
1150 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23188
1151 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.83000
1152 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1153 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
1154 Coil:Heating:Electric FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 6548.35748
1155 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.44549E-002
1156 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.00000
1157 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
1158 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.44549E-002
1159 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1160 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1161 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.56685E-003
1162 Coil:Heating:Electric FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 690.60787
1163 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.45266E-002
1164 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.31172
1165 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
1166 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.45266E-002
1167 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1168 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1169 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.22223E-003
1170 Coil:Heating:Electric FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 692.63340
1171 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.21287E-002
1172 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.26872
1173 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32200
1174 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.12545E-003
1175 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1176 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1177 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 STORAGE 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.41781E-003
1178 Coil:Heating:Electric FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 435.45454
1179 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.22463
1180 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
1181 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.81000
1182 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.18195
1183 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.81000
1184 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1185 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 TREATMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.53984E-003
1186 Coil:Heating:Electric FLOOR 3 TREATMENT VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 5138.36028
1187 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.67548
1188 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23769
1189 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.28500
1190 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.19251
1191 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.63385
1192 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1193 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.60291E-003
1194 Coil:Heating:Electric FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 7691.37435
1195 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.34242
1196 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23817
1197 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.28600
1198 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.79313E-002
1199 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.63511
1200 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1201 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.59972E-003
1202 Coil:Heating:Electric FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 5047.38783
1203 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.63066E-002
1204 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.42117
1205 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50500
1206 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.83348E-002
1207 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1208 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1209 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 UTILITY VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.04631E-004
1210 Coil:Heating:Electric FLOOR 3 UTILITY VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 892.28990
1211 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.29208
1212 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13912
1213 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11800
1214 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.44656E-002
1215 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.48471
1216 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1217 AirTerminal:SingleDuct:VAV:Reheat FLOOR 3 WORK VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.73862E-003
1218 Coil:Heating:Electric FLOOR 3 WORK VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 2982.52664
1219 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.16117
1220 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.37900E-002
1221 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 7.70000E-002
1222 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.24104E-002
1223 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.87840
1224 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1225 AirTerminal:SingleDuct:VAV:Reheat NE STAIR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.16330E-003
1226 Coil:Heating:Electric NE STAIR VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 4551.58353
1227 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.10567
1228 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.37940E-002
1229 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 7.60000E-002
1230 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.03067E-003
1231 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1232 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1233 AirTerminal:SingleDuct:VAV:Reheat NW ELEVATOR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.06209E-003
1234 Coil:Heating:Electric NW ELEVATOR VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 2984.03612
1235 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.16515
1236 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 8.23014E-002
1237 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 8.60000E-002
1238 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.42029E-002
1239 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.85726
1240 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1241 AirTerminal:SingleDuct:VAV:Reheat NW STAIR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.62932E-003
1242 Coil:Heating:Electric NW STAIR VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 4663.85312
1243 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.06102E-002
1244 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 8.43074E-002
1245 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 6.10000E-002
1246 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.91722E-003
1247 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
1248 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
1249 AirTerminal:SingleDuct:VAV:Reheat SW STAIR VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.51917E-003
1250 Coil:Heating:Electric SW STAIR VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 2276.44056
1251 AirLoopHVAC AHU-1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.29925
1252 AirLoopHVAC AHU-1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.26950
1253 AirLoopHVAC AHU-1 Sum of Air Terminal Maximum Flow Rates [m3/s] 7.10087
1254 AirLoopHVAC AHU-1 Adjusted Heating Design Air Flow Rate [m3/s] 5.29925
1255 AirLoopHVAC AHU-1 Adjusted Cooling Design Air Flow Rate [m3/s] 7.10087
1256 AirLoopHVAC AHU-1 Adjusted Main Design Air Flow Rate [m3/s] 7.10087
1257 AirLoopHVAC AHU-1 User Heating Air Flow Ratio [] 1.00000
1258 AirLoopHVAC AHU-1 Calculated Heating Air Flow Ratio [] 0.74628
1259 AirLoopHVAC AHU-2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.48532
1260 AirLoopHVAC AHU-2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.31971
1261 AirLoopHVAC AHU-2 Sum of Air Terminal Maximum Flow Rates [m3/s] 10.72700
1262 AirLoopHVAC AHU-2 Adjusted Heating Design Air Flow Rate [m3/s] 4.31971
1263 AirLoopHVAC AHU-2 Adjusted Cooling Design Air Flow Rate [m3/s] 9.20300
1264 AirLoopHVAC AHU-2 Adjusted Main Design Air Flow Rate [m3/s] 9.20300
1265 AirLoopHVAC AHU-2 User Heating Air Flow Ratio [] 1.00000
1266 AirLoopHVAC AHU-2 Calculated Heating Air Flow Ratio [] 0.46938
1267 AirLoopHVAC AHU-1 Design Supply Air Flow Rate [m3/s] 7.10087
1268 AirLoopHVAC AHU-2 Design Supply Air Flow Rate [m3/s] 9.20300
1269 Controller:OutdoorAir AHU-1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 7.10087
1270 Controller:OutdoorAir AHU-1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.07098
1271 Coil:Cooling:DX:TwoSpeed AHU-1_COOLC DXCOIL Design Size High Speed Rated Air Flow Rate [m3/s] 7.10087
1272 Coil:Cooling:DX:TwoSpeed AHU-1_COOLC DXCOIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 176331.52997
1273 Coil:Cooling:DX:TwoSpeed AHU-1_COOLC DXCOIL Design Size High Speed Rated Sensible Heat Ratio 0.69808
1274 Coil:Cooling:DX:TwoSpeed AHU-1_COOLC DXCOIL Design Size Low Speed Rated Air Flow Rate [m3/s] 2.36672
1275 Coil:Cooling:DX:TwoSpeed AHU-1_COOLC DXCOIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 58771.29894
1276 Coil:Cooling:DX:TwoSpeed AHU-1_COOLC DXCOIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.69808
1277 Coil:Heating:Water AHU-1_HEATC Design Size Rated Capacity [W] 92954.51419
1278 Coil:Heating:Water AHU-1_HEATC Design Size Maximum Water Flow Rate [m3/s] 2.03521E-003
1279 Coil:Heating:Water AHU-1_HEATC Design Size U-Factor Times Area Value [W/K] 1468.34147
1280 Fan:VariableVolume AHU-1_FAN Design Size Maximum Flow Rate [m3/s] 7.10087
1281 Humidifier:Steam:Electric AHU-1 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 4.47308E-005
1282 Humidifier:Steam:Electric AHU-1 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
1283 Humidifier:Steam:Electric AHU-1 HUMIDIFIER Design Size Rated Power [W] 96450.69782
1284 Humidifier:Steam:Electric AHU-1 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
1285 Coil:Heating:Electric AHU-1_EXTRAELECHEATC Design Size Nominal Capacity [W] 92954.51419
1286 Coil:Heating:Electric AHU-1_EXTRAELECHEATC User-Specified Nominal Capacity [W] 10000000.00000
1287 Coil:Heating:Water AHU-1_EXTRAWATERHEATC Design Size Rated Capacity [W] 92954.51419
1288 Coil:Heating:Water AHU-1_EXTRAWATERHEATC Design Size Maximum Water Flow Rate [m3/s] 2.03521E-003
1289 Coil:Heating:Water AHU-1_EXTRAWATERHEATC Design Size U-Factor Times Area Value [W/K] 1468.34147
1290 Controller:WaterCoil AHU-1_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.03521E-003
1291 Controller:WaterCoil AHU-1_EXTRAWATERHEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.03521E-003
1292 Controller:OutdoorAir AHU-2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.20300
1293 Coil:Cooling:DX:TwoSpeed AHU-2_COOLC DXCOIL Design Size High Speed Rated Air Flow Rate [m3/s] 9.20300
1294 Coil:Cooling:DX:TwoSpeed AHU-2_COOLC DXCOIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 220453.15832
1295 Coil:Cooling:DX:TwoSpeed AHU-2_COOLC DXCOIL Design Size High Speed Rated Sensible Heat Ratio 0.70907
1296 Coil:Cooling:DX:TwoSpeed AHU-2_COOLC DXCOIL Design Size Low Speed Rated Air Flow Rate [m3/s] 3.06736
1297 Coil:Cooling:DX:TwoSpeed AHU-2_COOLC DXCOIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 73477.03767
1298 Coil:Cooling:DX:TwoSpeed AHU-2_COOLC DXCOIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.70907
1299 Coil:Heating:Water AHU-2_HEATC Design Size Rated Capacity [W] 115747.62863
1300 Coil:Heating:Water AHU-2_HEATC Design Size Maximum Water Flow Rate [m3/s] 2.53426E-003
1301 Coil:Heating:Water AHU-2_HEATC Design Size U-Factor Times Area Value [W/K] 1832.70502
1302 Fan:VariableVolume AHU-2_FAN Design Size Maximum Flow Rate [m3/s] 9.20300
1303 Controller:WaterCoil AHU-2_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.53426E-003
1304 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 6.31667E-005
1305 PlantLoop SWHSYS1 Plant Loop Volume [m3] 7.58000E-003
1306 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 6.31667E-005
1307 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 8.06887
1308 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 6.31667E-005
1309 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.20788E-003
1310 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.26495
1311 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.20788E-003
1312 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 558.50037
1313 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 100840.74408
1314 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 100840.74000
1315 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.20788E-003


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL 651.64
2 Coil:Heating:Water FLOOR 1 BIO HAZ VAV BOX REHEAT COIL 159.21
3 Coil:Heating:Water FLOOR 1 CAFE VAV BOX REHEAT COIL 1062.96
4 Coil:Heating:Water FLOOR 1 CLEAN VAV BOX REHEAT COIL 300.27
5 Coil:Heating:Water FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL 370.58
6 Coil:Heating:Water FLOOR 1 DICTATION VAV BOX REHEAT COIL 22.03
7 Coil:Heating:Water FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL 453.27
8 Coil:Heating:Water FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL 130.76
9 Coil:Heating:Water FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL 930.33
10 Coil:Heating:Water FLOOR 1 HUMID VAV BOX REHEAT COIL 10.60
11 Coil:Heating:Water FLOOR 1 IT HALL VAV BOX REHEAT COIL 29.41
12 Coil:Heating:Water FLOOR 1 IT ROOM VAV BOX REHEAT COIL 0.00
13 Coil:Heating:Water FLOOR 1 LOBBY VAV BOX REHEAT COIL 1928.77
14 Coil:Heating:Water FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL 67.33
15 Coil:Heating:Water FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL 530.02
16 Coil:Heating:Water FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL 280.60
17 Coil:Heating:Water FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL 101.62
18 Coil:Heating:Water FLOOR 1 LOUNGE VAV BOX REHEAT COIL 155.50
19 Coil:Heating:Water FLOOR 1 MED GAS VAV BOX REHEAT COIL 824.69
20 Coil:Heating:Water FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL 171.28
21 Coil:Heating:Water FLOOR 1 MRI HALL VAV BOX REHEAT COIL 44.12
22 Coil:Heating:Water FLOOR 1 MRI ROOM VAV BOX REHEAT COIL 438.03
23 Coil:Heating:Water FLOOR 1 MRI TOILET VAV BOX REHEAT COIL 277.38
24 Coil:Heating:Water FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL 85.13
25 Coil:Heating:Water FLOOR 1 NURSE HALL VAV BOX REHEAT COIL 134.25
26 Coil:Heating:Water FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL 14.89
27 Coil:Heating:Water FLOOR 1 NURSE STATION VAV BOX REHEAT COIL 116.16
28 Coil:Heating:Water FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL 92.13
29 Coil:Heating:Water FLOOR 1 OFFICE VAV BOX REHEAT COIL 65.76
30 Coil:Heating:Water FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL 1064.63
31 Coil:Heating:Water FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL 0.00
32 Coil:Heating:Water FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL 1836.11
33 Coil:Heating:Water FLOOR 1 PACU VAV BOX REHEAT COIL 303.45
34 Coil:Heating:Water FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL 119.69
35 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL 531.03
36 Coil:Heating:Water FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL 949.68
37 Coil:Heating:Water FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL 351.79
38 Coil:Heating:Water FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL 2390.54
39 Coil:Heating:Water FLOOR 1 RECEPTION VAV BOX REHEAT COIL 0.00
40 Coil:Heating:Water FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL 30.78
41 Coil:Heating:Water FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL 2996.80
42 Coil:Heating:Water FLOOR 1 SCHEDULING VAV BOX REHEAT COIL 142.39
43 Coil:Heating:Water FLOOR 1 SCRUB VAV BOX REHEAT COIL 152.00
44 Coil:Heating:Water FLOOR 1 SOIL VAV BOX REHEAT COIL 298.59
45 Coil:Heating:Water FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL 0.00
46 Coil:Heating:Water FLOOR 1 SOIL WORK VAV BOX REHEAT COIL 396.63
47 Coil:Heating:Water FLOOR 1 STEP DOWN VAV BOX REHEAT COIL 1987.92
48 Coil:Heating:Water FLOOR 1 STERILE HALL VAV BOX REHEAT COIL 433.65
49 Coil:Heating:Water FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL 72.54
50 Coil:Heating:Water FLOOR 1 STORAGE VAV BOX REHEAT COIL 5710.81
51 Coil:Heating:Water FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL 1036.82
52 Coil:Heating:Water FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL 1684.97
53 Coil:Heating:Water FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL 71.52
54 Coil:Heating:Water FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL 1737.12
55 Coil:Heating:Water FLOOR 1 VESTIBULE VAV BOX REHEAT COIL 467.51
56 Coil:Heating:Water AHU-1_HEATC 78855.15
57 Coil:Heating:Water AHU-1_EXTRAWATERHEATC 78855.15
58 Coil:Heating:Water AHU-2_HEATC 98665.72


VAV DX Cooling Coil Standard Rating Information

DX Coil Type DX Coil Name Fan Type Fan Name Standard Net Cooling Capacity {W} Standard Net Cooling Capacity {Btu/h} IEER {Btu/W-h} COP 100% Capacity {W/W} COP 75% Capacity {W/W} COP 50% Capacity {W/W} COP 25% Capacity {W/W} EER 100% Capacity {Btu/W-h} EER 75% Capacity {Btu/W-h} EER 50% Capacity {Btu/W-h} EER 25% Capacity {Btu/W-h} Supply Air Flow 100% {kg/s} Supply Air Flow 75% {kg/s} Supply Air Flow 50% {kg/s} Supply Air Flow 25% {kg/s}
1 Coil:Cooling:DX:TwoSpeed AHU-1_COOLC DXCOIL N/A N/A 171139.04 583950.65 11.47 3.01 3.27 3.48 3.62 10.25 11.17 11.87 12.35 7.8695 6.2283 4.1745 1.7742
2 Coil:Cooling:DX:TwoSpeed AHU-2_COOLC DXCOIL N/A N/A 213709.81 729208.15 11.40 2.99 3.26 3.46 3.61 10.21 11.11 11.79 12.31 10.1991 8.0804 5.4163 2.2749


Zone Surfaces

Zone Name # Surfaces
1 FLOOR 1 ANESTHESIA 9
2 FLOOR 1 BIO HAZ 7
3 FLOOR 1 CAFE 9
4 FLOOR 1 CLEAN 10
5 FLOOR 1 CLEAN WORK 9
6 FLOOR 1 DICTATION 9
7 FLOOR 1 DRESSING ROOM 8
8 FLOOR 1 ELECTRICAL ROOM 7
9 FLOOR 1 ELEVATOR PUMP ROOM 10
10 FLOOR 1 HUMID 7
11 FLOOR 1 IT HALL 11
12 FLOOR 1 IT ROOM 7
13 FLOOR 1 LOBBY 20
14 FLOOR 1 LOBBY HALL 9
15 FLOOR 1 LOBBY TOILET 8
16 FLOOR 1 LOCKER ROOM 14
17 FLOOR 1 LOCKER ROOM HALL 18
18 FLOOR 1 LOUNGE 10
19 FLOOR 1 MED GAS 8
20 FLOOR 1 MRI CONTROL ROOM 11
21 FLOOR 1 MRI HALL 12
22 FLOOR 1 MRI ROOM 9
23 FLOOR 1 MRI TOILET 8
24 FLOOR 1 NOURISHMENT 13
25 FLOOR 1 NURSE HALL 17
26 FLOOR 1 NURSE JANITOR 8
27 FLOOR 1 NURSE STATION 12
28 FLOOR 1 NURSE TOILET 7
29 FLOOR 1 OFFICE 11
30 FLOOR 1 OPERATING ROOM 1 15
31 FLOOR 1 OPERATING ROOM 2 14
32 FLOOR 1 OPERATING ROOM 3 12
33 FLOOR 1 PACU 8
34 FLOOR 1 PRE-OP HALL 21
35 FLOOR 1 PRE-OP ROOM 1 10
36 FLOOR 1 PRE-OP ROOM 2 12
37 FLOOR 1 PRE-OP TOILET 7
38 FLOOR 1 PROCEDURE ROOM 13
39 FLOOR 1 RECEPTION 15
40 FLOOR 1 RECEPTION HALL 10
41 FLOOR 1 RECOVERY ROOM 17
42 FLOOR 1 SCHEDULING 9
43 FLOOR 1 SCRUB 7
44 FLOOR 1 SOIL 11
45 FLOOR 1 SOIL HOLD 8
46 FLOOR 1 SOIL WORK 11
47 FLOOR 1 STEP DOWN 15
48 FLOOR 1 STERILE HALL 25
49 FLOOR 1 STERILE STORAGE 12
50 FLOOR 1 STORAGE 18
51 FLOOR 1 SUB-STERILE 8
52 FLOOR 1 UTILITY HALL 15
53 FLOOR 1 UTILITY JANITOR 7
54 FLOOR 1 UTILITY ROOM 12
55 FLOOR 1 VESTIBULE 8
56 FLOOR 2 CONFERENCE 12
57 FLOOR 2 CONFERENCE TOILET 7
58 FLOOR 2 DICTATION 7
59 FLOOR 2 EXAM 1 15
60 FLOOR 2 EXAM 2 13
61 FLOOR 2 EXAM 3 18
62 FLOOR 2 EXAM 4 8
63 FLOOR 2 EXAM 5 10
64 FLOOR 2 EXAM 6 12
65 FLOOR 2 EXAM 7 18
66 FLOOR 2 EXAM 8 9
67 FLOOR 2 EXAM 9 10
68 FLOOR 2 EXAM HALL 1 11
69 FLOOR 2 EXAM HALL 2 11
70 FLOOR 2 EXAM HALL 3 13
71 FLOOR 2 EXAM HALL 4 12
72 FLOOR 2 EXAM HALL 5 11
73 FLOOR 2 EXAM HALL 6 12
74 FLOOR 2 JANITOR 7
75 FLOOR 2 LOUNGE 7
76 FLOOR 2 NURSE STATION 1 9
77 FLOOR 2 NURSE STATION 2 8
78 FLOOR 2 OFFICE 14
79 FLOOR 2 OFFICE HALL 22
80 FLOOR 2 RECEPTION 16
81 FLOOR 2 RECEPTION HALL 31
82 FLOOR 2 RECEPTION TOILET 8
83 FLOOR 2 SCHEDULING 1 10
84 FLOOR 2 SCHEDULING 2 10
85 FLOOR 2 STORAGE 1 7
86 FLOOR 2 STORAGE 2 9
87 FLOOR 2 STORAGE 3 7
88 FLOOR 2 UTILITY 8
89 FLOOR 2 WORK 25
90 FLOOR 2 WORK HALL 29
91 FLOOR 2 WORK TOILET 8
92 FLOOR 2 X-RAY 19
93 FLOOR 3 DRESSING ROOM 7
94 FLOOR 3 ELEVATOR HALL 11
95 FLOOR 3 HUMID 8
96 FLOOR 3 JANITOR 7
97 FLOOR 3 LOCKER 7
98 FLOOR 3 LOUNGE 16
99 FLOOR 3 LOUNGE TOILET 8
100 FLOOR 3 MECHANICAL 9
101 FLOOR 3 MECHANICAL HALL 11
102 FLOOR 3 OFFICE 24
103 FLOOR 3 OFFICE HALL 15
104 FLOOR 3 OFFICE TOILET 8
105 FLOOR 3 PHYSICAL THERAPY 1 22
106 FLOOR 3 PHYSICAL THERAPY 2 15
107 FLOOR 3 PHYSICAL THERAPY TOILET 7
108 FLOOR 3 STORAGE 1 7
109 FLOOR 3 STORAGE 2 7
110 FLOOR 3 TREATMENT 10
111 FLOOR 3 UNDEVELOPED 1 21
112 FLOOR 3 UNDEVELOPED 2 14
113 FLOOR 3 UTILITY 7
114 FLOOR 3 WORK 13
115 NE STAIR 19
116 NW ELEVATOR 13
117 NW STAIR 15
118 SW STAIR 13


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 4161C8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 B3A518 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 1AD133 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 114EC6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 330DF9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 66B6F7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 481E71 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   6.13 8.36 6.13 180.00 90.00 2.74 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
5 78F987 Window 481E71 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
6 FLOOR 1 ANESTHESIA SLAB Floor   CTF - ConductionTransferFunction FLOOR1ANESTHESIASLAB_FFACTOR 0.251 0.236   10.03 10.03 10.03 0.00 180.00 2.74 3.66 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
7 DDCF3E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2.23 2.23 2.23 90.00 0.00 3.66 0.61 0.00 A08A28 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BE1AE1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.80 7.80 7.80 270.00 0.00 3.66 2.13 0.00 4E78E0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 FLOOR 1 ANESTHESIA_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   20.07 20.07 20.07 0.00 90.00 20.07 1.00 0.00 FLOOR 1 ANESTHESIA_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
10 70DAD1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 A1087A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
11 32CC19 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 DEFACF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
12 BBEE0B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 19D150 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
13 F951A6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 5D9E95 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 FLOOR 1 BIO HAZ SLAB Floor   CTF - ConductionTransferFunction FLOOR1BIOHAZSLAB_FFACTOR 5.650E-003 5.642E-003   5.20 5.20 5.20 0.00 180.00 2.13 2.44 0.00 FLOOR 1 BIO HAZ SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
15 F6F6C6 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.20 5.20 5.20 0.00 0.00 2.13 2.44 0.00 F67EC8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
16 FLOOR 1 BIO HAZ_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.41 10.41 10.41 0.00 90.00 10.41 1.00 0.00 FLOOR 1 BIO HAZ_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
17 5F762C Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   9.66 18.58 9.66 180.00 90.00 6.10 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.55 0.45 4
18 D8037E Window 5F762C Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 8.92 8.92 8.92 180.00 90.00 3.66 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.55 0.45 4
19 4507E9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 0.00 90.00 6.10 3.05 0.00 A6D45E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 C48E94 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.08 12.08 12.08 270.00 90.00 3.96 3.05 0.00 3145CA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
21 6B31A8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   19.51 19.51 19.51 90.00 90.00 6.40 3.05 0.00 7BB928 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 368E02 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 8FF821 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 FLOOR 1 CAFE SLAB Floor   CTF - ConductionTransferFunction FLOOR1CAFESLAB_FFACTOR 0.141 0.136   39.02 39.02 39.02 90.00 180.00 6.40 6.10 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 4783F2 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   39.02 39.02 39.02 90.00 0.00 6.40 6.10 0.00 39BFFB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 FLOOR 1 CAFE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 FLOOR 1 CAFE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 EA8FA7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 EE0803 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 FE7511 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 8BB36F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 59E0E4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 270.00 90.00 4.27 3.05 0.00 855191 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 7949FA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 90.00 90.00 4.27 3.05 0.00 86244A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 FLOOR 1 CLEAN SLAB Floor   CTF - ConductionTransferFunction FLOOR1CLEANSLAB_FFACTOR 5.650E-003 5.642E-003   11.71 11.71 11.71 90.00 180.00 4.27 2.74 0.00 FLOOR 1 CLEAN SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 EC2478 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.46 0.46 0.46 90.00 0.00 0.30 1.52 0.00 75EAF8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 1B4EDC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.37 0.37 0.37 0.00 0.00 1.22 0.30 0.00 EB611D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
33 D1AFC9 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.85 5.85 5.85 180.00 0.00 2.74 2.13 0.00 1CC550 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
34 442699 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 0.00 0.00 2.74 1.83 0.00 2FE383 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
35 FLOOR 1 CLEAN_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   23.41 23.41 23.41 0.00 90.00 23.41 1.00 0.00 FLOOR 1 CLEAN_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
36 FD8CF2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 808817 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
37 49DA86 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.22 10.22 10.22 270.00 90.00 3.35 3.05 0.00 6B967C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
38 619EE6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.22 10.22 10.22 90.00 90.00 3.35 3.05 0.00 A809DD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
39 B551AD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 121DFF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
40 FLOOR 1 CLEAN WORK SLAB Floor   CTF - ConductionTransferFunction FLOOR1CLEANWORKSLAB_FFACTOR 5.650E-003 5.642E-003   15.33 15.33 15.33 180.00 180.00 4.57 3.35 0.00 FLOOR 1 CLEAN WORK SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
41 8E9267 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.50 6.50 6.50 270.00 0.00 2.13 3.05 0.00 EF47B0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
42 BB097B Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.25 3.25 3.25 180.00 0.00 1.52 2.13 0.00 774CCD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
43 2E1FB7 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.57 5.57 5.57 270.00 0.00 1.22 4.57 0.00 A5FA3B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
44 FLOOR 1 CLEAN WORK_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   30.66 30.66 30.66 0.00 90.00 30.66 1.00 0.00 FLOOR 1 CLEAN WORK_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
45 94A56A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 8043B2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 4A854B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 90.00 90.00 4.27 3.05 0.00 ACADA4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
47 8594D3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 A2F014 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
48 86244A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 270.00 90.00 4.27 3.05 0.00 7949FA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
49 FLOOR 1 DICTATION SLAB Floor   CTF - ConductionTransferFunction FLOOR1DICTATIONSLAB_FFACTOR 5.650E-003 5.642E-003   11.71 11.71 11.71 0.00 180.00 2.74 4.27 0.00 FLOOR 1 DICTATION SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
50 672F1E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.84 0.84 0.84 0.00 0.00 2.74 0.30 0.00 9B49F5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
51 A7115C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.85 5.85 5.85 180.00 0.00 2.74 2.13 0.00 5D03DA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
52 AF27F8 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 0.00 0.00 2.74 1.83 0.00 3F961C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 FLOOR 1 DICTATION_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   23.41 23.41 23.41 0.00 90.00 23.41 1.00 0.00 FLOOR 1 DICTATION_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 256F02 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 90.00 90.00 1.52 3.05 0.00 4ED109 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
55 DE027F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 270.00 90.00 1.52 3.05 0.00 1EC3A0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
56 84FB73 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   6.04 8.36 6.04 0.00 90.00 2.74 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.57 0.43 4
57 4A8120 Window 84FB73 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.32 2.32 2.32 0.00 90.00 1.52 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.56 0.44 4
58 CC17E8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 A8DB72 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 FLOOR 1 DRESSING ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1DRESSINGROOMSLAB_FFACTOR 0.636 0.551   4.18 4.18 4.18 0.00 180.00 2.74 1.52 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
60 5DACB5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.18 4.18 4.18 0.00 0.00 2.74 1.52 0.00 541C9C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
61 FLOOR 1 DRESSING ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   8.36 8.36 8.36 0.00 90.00 8.36 1.00 0.00 FLOOR 1 DRESSING ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
62 9879B2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 2E8328 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 2D53AC Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 964F72 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
64 7F5C82 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 E82152 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 EC28A9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
66 FLOOR 1 ELECTRICAL ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1ELECTRICALROOMSLAB_FFACTOR 0.214 0.203   9.10 9.10 9.10 0.00 180.00 4.27 2.13 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
67 D7AC92 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   9.10 9.10 9.10 0.00 0.00 4.27 2.13 0.00 65AB67 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
68 FLOOR 1 ELECTRICAL ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   18.21 18.21 18.21 0.00 90.00 18.21 1.00 0.00 FLOOR 1 ELECTRICAL ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
69 F99476 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 F23EB6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
70 C732B0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   12.08 12.08 12.08 0.00 90.00 3.96 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.61 0.39 4
71 9926F7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 6FB351 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 E02487 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   4.55 6.50 4.55 270.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 BA05F7 Door E02487 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
74 B45B50 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   3.72 3.72 3.72 180.00 90.00 1.22 3.05 0.00 5D8FAF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 FLOOR 1 ELEVATOR PUMP ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1ELEVATORPUMPROOMSLAB_FFACTOR 0.706 0.603   8.45 8.45 8.45 180.00 180.00 3.96 2.13 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
76 DF9D5D Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.85 5.85 5.85 90.00 0.00 2.13 2.74 0.00 5B736E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
77 827528 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2.60 2.60 2.60 270.00 0.00 2.13 1.22 0.00 1A8E2A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
78 FLOOR 1 ELEVATOR PUMP ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   16.91 16.91 16.91 0.00 90.00 16.91 1.00 0.00 FLOOR 1 ELEVATOR PUMP ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
79 758B3C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 863C6C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 A7F46C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 725D3E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 3F71D3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 E1B4BB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
82 8BB36F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 FE7511 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
83 FLOOR 1 HUMID SLAB Floor   CTF - ConductionTransferFunction FLOOR1HUMIDSLAB_FFACTOR 5.650E-003 5.642E-003   5.02 5.02 5.02 0.00 180.00 2.74 1.83 0.00 FLOOR 1 HUMID SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
84 D21333 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 0.00 0.00 2.74 1.83 0.00 55622A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
85 FLOOR 1 HUMID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 1 HUMID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 FEC1E3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 180.00 90.00 8.53 3.05 0.00 AE206C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
87 5D9E95 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 F951A6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 F4D6DD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 90.00 90.00 1.52 3.05 0.00 20FB14 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
89 FB87D3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 270.00 90.00 1.52 3.05 0.00 3E6044 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 445A39 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 9A776E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 3A6904 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 2CF0AA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 FLOOR 1 IT HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1ITHALLSLAB_FFACTOR 5.650E-003 5.642E-003   13.01 13.01 13.01 180.00 180.00 8.53 1.52 0.00 FLOOR 1 IT HALL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 FB17DD Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.25 3.25 3.25 270.00 0.00 1.52 2.13 0.00 1624C5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 8A2F34 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2.79 2.79 2.79 270.00 0.00 1.52 1.83 0.00 4AA9BC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
95 9A5B84 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.97 6.97 6.97 90.00 0.00 1.52 4.57 0.00 40E182 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
96 FLOOR 1 IT HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   26.01 26.01 26.01 0.00 90.00 26.01 1.00 0.00 FLOOR 1 IT HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
97 2CF0AA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 3A6904 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 307901 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 897BAF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
99 FA769A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 41CE25 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 319A6B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 5B533A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 FLOOR 1 IT ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1ITROOMSLAB_FFACTOR 5.650E-003 5.642E-003   10.41 10.41 10.41 90.00 180.00 2.44 4.27 0.00 FLOOR 1 IT ROOM SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 C732D4 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   10.41 10.41 10.41 90.00 0.00 2.44 4.27 0.00 8D6453 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 FLOOR 1 IT ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   20.81 20.81 20.81 0.00 90.00 20.81 1.00 0.00 FLOOR 1 IT ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 822161 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 FA9233 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 43A2A2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 270.00 90.00 6.10 3.05 0.00 976E3F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 6FB351 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 9926F7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 8134C2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 0.00 90.00 0.61 3.05 0.00 88CB69 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 102EC4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 9FF31D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 BAD27A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 1068C8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
110 5D8FAF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   3.72 3.72 3.72 0.00 90.00 1.22 3.05 0.00 B45B50 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 46E87C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 BFD4BB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
112 3145CA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.08 12.08 12.08 90.00 90.00 3.96 3.05 0.00 C48E94 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
113 73E892 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 180.00 90.00 0.61 3.05 0.00 F3084E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
114 4418C4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 E5BC3F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 FE5A3C Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   9.57 20.44 9.57 270.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.58 0.42 4
116 AAE778 Window FE5A3C Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 8.92 8.92 8.92 270.00 90.00 3.66 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
117 F67E1F Door FE5A3C CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.65 0.35 4
118 4911A5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 72A819 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
119 FLOOR 1 LOBBY SLAB Floor   CTF - ConductionTransferFunction FLOOR1LOBBYSLAB_FFACTOR 0.104 0.102   57.79 57.79 57.79 90.00 180.00 7.60 7.60 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 10
120 D647E0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.69 6.69 6.69 180.00 0.00 3.66 1.83 0.00 CAC621 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
121 BFB8E1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   33.26 33.26 33.26 180.00 0.00 5.77 5.77 0.00 517DFC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
122 78FEE8 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   17.84 17.84 17.84 270.00 0.00 4.88 3.66 0.00 167608 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
123 FLOOR 1 LOBBY_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   115.57 115.57 115.57 0.00 90.00 115.57 1.00 0.00 FLOOR 1 LOBBY_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
124 A6D45E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 180.00 90.00 6.10 3.05 0.00 4507E9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 F7F8BA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 234734 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 34019D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 0.00 90.00 6.10 3.05 0.00 867BBB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
127 72A819 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 4911A5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
128 FLOOR 1 LOBBY HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1LOBBYHALLSLAB_FFACTOR 5.650E-003 5.642E-003   22.30 22.30 22.30 0.00 180.00 6.10 3.66 0.00 FLOOR 1 LOBBY HALL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
129 D60B94 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.15 11.15 11.15 180.00 0.00 6.10 1.83 0.00 E90253 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
130 B7E9B3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.57 5.57 5.57 180.00 0.00 6.10 0.91 0.00 5724CC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
131 690A91 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.57 5.57 5.57 0.00 0.00 6.10 0.91 0.00 FA00FE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
132 FLOOR 1 LOBBY HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   44.59 44.59 44.59 0.00 90.00 44.59 1.00 0.00 FLOOR 1 LOBBY HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
133 9FF31D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 102EC4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 9D87EC Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
135 F23EB6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 F99476 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
136 7F6FC2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 D699FF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
137 88CB69 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 180.00 90.00 0.61 3.05 0.00 8134C2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
138 FLOOR 1 LOBBY TOILET SLAB Floor   CTF - ConductionTransferFunction FLOOR1LOBBYTOILETSLAB_FFACTOR 0.339 0.313   5.02 5.02 5.02 0.00 180.00 2.74 1.83 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
139 9BB388 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 0.00 0.00 2.74 1.83 0.00 4C4C25 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
140 FLOOR 1 LOBBY TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 1 LOBBY TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
141 E9F3F6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 270.00 90.00 4.57 3.05 0.00 704EC3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
142 A9C27A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 180.00 90.00 6.71 3.05 0.00 8D03E8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
143 F629C1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   14.86 20.44 14.86 0.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.57 0.43 4
144 3AAD8B Window F629C1 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.59 0.41 4
145 8128A9 Window F629C1 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
146 962DB5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 90.00 90.00 9.14 3.05 0.00 761D33 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 92E22C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 270.00 90.00 4.57 3.05 0.00 EAACE4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 FLOOR 1 LOCKER ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1LOCKERROOMSLAB_FFACTOR 9.801E-002 9.573E-002   61.32 61.32 61.32 270.00 180.00 9.14 6.71 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
149 7B1677 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   8.36 8.36 8.36 270.00 0.00 9.14 0.91 0.00 772953 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
150 21C5E8 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   25.08 25.08 25.08 180.00 0.00 5.49 4.57 0.00 A9A1F6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
151 FDCEC5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2.79 2.79 2.79 90.00 0.00 9.14 0.30 0.00 EC3BEA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 C1F15F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 180.00 0.00 5.49 2.44 0.00 1E3410 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
153 1E6611 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.71 11.71 11.71 0.00 0.00 5.49 2.13 0.00 9EADD8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
154 FLOOR 1 LOCKER ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   122.63 122.63 122.63 0.00 90.00 122.63 1.00 0.00 FLOOR 1 LOCKER ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
155 35028C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 88AE01 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 852027 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 592524 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
157 EBFE47 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 0.00 90.00 8.53 3.05 0.00 FD0958 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 D9965C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.08 12.08 12.08 180.00 90.00 3.96 3.05 0.00 7AE5B9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
159 71783C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 C0F51F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
160 D8C098 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 4E3BB5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
161 66D163 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 180.00 90.00 10.06 3.05 0.00 1003C1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
162 8D03E8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 A9C27A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
163 9A0DF2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 18AFE3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
164 FLOOR 1 LOCKER ROOM HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1LOCKERROOMHALLSLAB_FFACTOR 5.650E-003 5.642E-003   46.08 46.08 46.08 180.00 180.00 18.90 2.44 0.00 FLOOR 1 LOCKER ROOM HALL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
165 1891E7 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.95 1.95 1.95 270.00 0.00 0.91 2.13 0.00 5A7EAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
166 BD75DE Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   28.80 28.80 28.80 270.00 0.00 1.52 18.90 0.00 FFE9D0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
167 3137C4 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.67 1.67 1.67 270.00 0.00 0.91 1.83 0.00 C2156D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
168 C8F2F1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.69 6.69 6.69 180.00 0.00 7.32 0.91 0.00 37898A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
169 6B171C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.67 1.67 1.67 180.00 0.00 1.83 0.91 0.00 E0C60A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
170 86C171 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 270.00 0.00 0.91 5.49 0.00 DE8843 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
171 C605B5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.28 0.28 0.28 90.00 0.00 0.91 0.30 0.00 5F9E13 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 FLOOR 1 LOCKER ROOM HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   92.16 92.16 92.16 0.00 90.00 92.16 1.00 0.00 FLOOR 1 LOCKER ROOM HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
173 18AFE3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 9A0DF2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
174 761D33 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 270.00 90.00 9.14 3.05 0.00 962DB5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
175 9C0202 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 891195 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
176 29BD5F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   15.79 15.79 15.79 90.00 90.00 5.18 3.05 0.00 9E12D4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 897BAF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 307901 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 3E6044 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 90.00 90.00 1.52 3.05 0.00 FB87D3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
179 FLOOR 1 LOUNGE SLAB Floor   CTF - ConductionTransferFunction FLOOR1LOUNGESLAB_FFACTOR 5.650E-003 5.642E-003   33.45 33.45 33.45 180.00 180.00 3.66 9.14 0.00 FLOOR 1 LOUNGE SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 7B9EEC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   25.08 25.08 25.08 270.00 0.00 9.14 2.74 0.00 A6147C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
181 B04E85 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   8.36 8.36 8.36 90.00 0.00 9.14 0.91 0.00 15A02B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
182 FLOOR 1 LOUNGE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   66.89 66.89 66.89 0.00 90.00 66.89 1.00 0.00 FLOOR 1 LOUNGE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
183 A4B378 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 89BBEB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 72BCFE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 8B4DC1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 E85BB5 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.48 7.43 5.48 0.00 90.00 2.44 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 7EB6E7 Door E85BB5 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 577FC1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.58 0.42 4
188 FLOOR 1 MED GAS SLAB Floor   CTF - ConductionTransferFunction FLOOR1MEDGASSLAB_FFACTOR 0.882 0.726   5.20 5.20 5.20 180.00 180.00 2.44 2.13 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 FLOOR 1 MED GAS ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   5.20 5.20 5.20 180.00 0.00 2.44 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.15 0.85 4
190 FLOOR 1 MED GAS_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.41 10.41 10.41 0.00 90.00 10.41 1.00 0.00 FLOOR 1 MED GAS_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
191 F0B690 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 A78253 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 D2C53A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 90.00 90.00 0.91 3.05 0.00 27B0D7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BFD4BB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 46E87C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 C114C1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   2.69 4.65 2.69 0.00 90.00 1.52 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.67 0.33 4
195 D18914 Door C114C1 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.68 0.32 4
196 92A2CB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 0.00 90.00 4.88 3.05 0.00 74AB49 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
197 1EC3A0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 90.00 90.00 1.52 3.05 0.00 DE027F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
198 E66ECE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 180.00 90.00 0.91 3.05 0.00 90FDA9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
199 FLOOR 1 MRI CONTROL ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1MRICONTROLROOMSLAB_FFACTOR 8.737E-002 8.555E-002   15.61 15.61 15.61 180.00 180.00 6.40 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
200 290CAB Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   15.61 15.61 15.61 90.00 0.00 2.44 6.40 0.00 CEC6B4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
201 FLOOR 1 MRI CONTROL ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   31.22 31.22 31.22 0.00 90.00 31.22 1.00 0.00 FLOOR 1 MRI CONTROL ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
202 824665 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 E20721 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
203 68F53B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 E608B9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
204 27B0D7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 270.00 90.00 0.91 3.05 0.00 D2C53A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
205 90FDA9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 0.00 90.00 0.91 3.05 0.00 E66ECE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
206 91DE28 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 BA91C7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
207 A8DB72 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 CC17E8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
208 8A30DD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   3.72 3.72 3.72 90.00 90.00 1.22 3.05 0.00 24139C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
209 596DE0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 C9D24D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
210 B92155 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 180.00 90.00 3.05 3.05 0.00 4E24F1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
211 FLOOR 1 MRI HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1MRIHALLSLAB_FFACTOR 5.650E-003 5.642E-003   13.66 13.66 13.66 180.00 180.00 3.70 3.70 0.00 FLOOR 1 MRI HALL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 8
212 5CB500 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.66 13.66 13.66 180.00 0.00 3.70 3.70 0.00 1A95D5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 8
213 FLOOR 1 MRI HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   27.31 27.31 27.31 0.00 90.00 27.31 1.00 0.00 FLOOR 1 MRI HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
214 2FAF44 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 90.00 90.00 4.57 3.05 0.00 6EA718 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
215 A78253 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 F0B690 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
216 E5BC3F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 4418C4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
217 867BBB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 180.00 90.00 6.10 3.05 0.00 34019D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
218 F3084E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 0.00 90.00 0.61 3.05 0.00 73E892 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
219 BA91C7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 91DE28 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
220 FLOOR 1 MRI ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1MRIROOMSLAB_FFACTOR 5.650E-003 5.642E-003   40.88 40.88 40.88 90.00 180.00 6.71 6.10 0.00 FLOOR 1 MRI ROOM SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
221 803791 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   40.88 40.88 40.88 90.00 0.00 6.71 6.10 0.00 E43750 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
222 FLOOR 1 MRI ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   81.75 81.75 81.75 0.00 90.00 81.75 1.00 0.00 FLOOR 1 MRI ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
223 ADB8D0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
224 30DB21 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 95486C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 C9D24D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 596DE0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 4ED109 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 270.00 90.00 1.52 3.05 0.00 256F02 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 24139C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   3.72 3.72 3.72 270.00 90.00 1.22 3.05 0.00 8A30DD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 FLOOR 1 MRI TOILET SLAB Floor   CTF - ConductionTransferFunction FLOOR1MRITOILETSLAB_FFACTOR 0.339 0.313   5.02 5.02 5.02 90.00 180.00 2.74 1.83 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
229 388F10 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 90.00 0.00 2.74 1.83 0.00 E21951 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
230 FLOOR 1 MRI TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 1 MRI TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
231 855191 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 90.00 90.00 4.27 3.05 0.00 59E0E4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 C0F51F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 71783C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
233 A59907 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 A452BE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
234 28DE5A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.15 24.15 24.15 270.00 90.00 7.92 3.05 0.00 551E65 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
235 58B6B6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 D9F81F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
236 725D3E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 A7F46C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
237 FLOOR 1 NOURISHMENT SLAB Floor   CTF - ConductionTransferFunction FLOOR1NOURISHMENTSLAB_FFACTOR 5.650E-003 5.642E-003   16.91 16.91 16.91 270.00 180.00 7.92 2.13 0.00 FLOOR 1 NOURISHMENT SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
238 4E5019 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.65 0.65 0.65 180.00 0.00 2.13 0.30 0.00 21F419 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
239 E8F02D Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.56 0.56 0.56 90.00 0.00 0.30 1.83 0.00 E3B855 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
240 6ECCF3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   9.29E-002 9.29E-002 9.29E-002 0.00 0.00 0.30 0.30 0.00 BD39AC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
241 AA1F5C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.90 3.90 3.90 0.00 0.00 2.13 1.83 0.00 4FA380 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
242 F665B1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.71 11.71 11.71 270.00 0.00 5.49 2.13 0.00 C6DCD1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
243 FLOOR 1 NOURISHMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   33.82 33.82 33.82 0.00 90.00 33.82 1.00 0.00 FLOOR 1 NOURISHMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
244 6822BB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 5FD018 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
245 825233 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 23683B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
246 86A28D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 BABBB4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
247 C92A6E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 44686F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
248 114EC6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 1AD133 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
249 9EB05A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 E5CB03 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
250 7434CD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 F740DF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
251 344D34 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.94 26.94 26.94 0.00 90.00 8.84 3.05 0.00 4A07CD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
252 59CEFB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.81 41.81 41.81 180.00 90.00 13.72 3.05 0.00 72C4ED Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
253 FLOOR 1 NURSE HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1NURSEHALLSLAB_FFACTOR 5.650E-003 5.642E-003   46.08 46.08 46.08 270.00 180.00 2.44 18.90 0.00 FLOOR 1 NURSE HALL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
254 C75191 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.74 0.74 0.74 90.00 0.00 2.44 0.30 0.00 526C70 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
255 92E327 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 0.00 0.00 5.49 2.44 0.00 CCAA9D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
256 7F6B1B Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   17.84 17.84 17.84 90.00 0.00 2.44 7.32 0.00 BA0A29 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
257 4A49C1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 90.00 0.00 2.44 1.83 0.00 243E09 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
258 8F5FFC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 0.00 0.00 1.83 2.44 0.00 BAE3F8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
259 DDBA1E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.20 5.20 5.20 270.00 0.00 2.44 2.13 0.00 A3E3D6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
260 FLOOR 1 NURSE HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   92.16 92.16 92.16 0.00 90.00 92.16 1.00 0.00 FLOOR 1 NURSE HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
261 4E3BB5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 D8C098 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
262 415590 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 96662A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
263 D9F81F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 58B6B6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
264 E1B4BB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 3F71D3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
265 FLOOR 1 NURSE JANITOR SLAB Floor   CTF - ConductionTransferFunction FLOOR1NURSEJANITORSLAB_FFACTOR 5.650E-003 5.642E-003   5.02 5.02 5.02 180.00 180.00 2.74 1.83 0.00 FLOOR 1 NURSE JANITOR SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
266 2CB843 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.84 0.84 0.84 180.00 0.00 2.74 0.30 0.00 C5B569 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
267 E2AB17 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.18 4.18 4.18 0.00 0.00 2.74 1.52 0.00 AE5078 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
268 FLOOR 1 NURSE JANITOR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 1 NURSE JANITOR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
269 464A53 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 BA8FF7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
270 FE5062 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 FCD8D2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
271 4A07CD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.94 26.94 26.94 180.00 90.00 8.84 3.05 0.00 344D34 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
272 EE0803 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 EA8FA7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
273 DFDE4F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.08 12.08 12.08 0.00 90.00 3.96 3.05 0.00 8C3884 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
274 A452BE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 A59907 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
275 FLOOR 1 NURSE STATION SLAB Floor   CTF - ConductionTransferFunction FLOOR1NURSESTATIONSLAB_FFACTOR 5.650E-003 5.642E-003   24.25 24.25 24.25 180.00 180.00 8.84 2.74 0.00 FLOOR 1 NURSE STATION SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
276 BD4B70 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.84 0.84 0.84 90.00 0.00 2.74 0.30 0.00 3AE495 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
277 A0117C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   15.05 15.05 15.05 90.00 0.00 2.74 5.49 0.00 4579A7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
278 52F395 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.34 3.34 3.34 270.00 0.00 2.74 1.22 0.00 BD5B50 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
279 AA2E8F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 90.00 0.00 2.74 1.83 0.00 C94CC0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
280 FLOOR 1 NURSE STATION_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   48.50 48.50 48.50 0.00 90.00 48.50 1.00 0.00 FLOOR 1 NURSE STATION_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
281 CA6EDA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 446771 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
282 5EB34C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 9E478E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
283 5CD67D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 FAE342 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
284 E5CB03 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 9EB05A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
285 FLOOR 1 NURSE TOILET SLAB Floor   CTF - ConductionTransferFunction FLOOR1NURSETOILETSLAB_FFACTOR 5.650E-003 5.642E-003   5.02 5.02 5.02 180.00 180.00 1.83 2.74 0.00 FLOOR 1 NURSE TOILET SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
286 156F92 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 180.00 0.00 1.83 2.74 0.00 75A3C4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
287 FLOOR 1 NURSE TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 1 NURSE TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
288 361D65 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.22 10.22 10.22 0.00 90.00 3.35 3.05 0.00 EAE60F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
289 2B5816 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 90.00 90.00 7.01 3.05 0.00 33A280 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
290 7B67EC Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 180.00 90.00 1.52 3.05 0.00 25AB11 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
291 7E0561 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 270.00 90.00 7.01 3.05 0.00 2730E5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
292 4E24F1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 0.00 90.00 3.05 3.05 0.00 B92155 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
293 8259AE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 180.00 90.00 4.88 3.05 0.00 CD7BAD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
294 FLOOR 1 OFFICE SLAB Floor   CTF - ConductionTransferFunction FLOOR1OFFICESLAB_FFACTOR 5.650E-003 5.642E-003   44.87 44.87 44.87 0.00 180.00 6.40 7.01 0.00 FLOOR 1 OFFICE SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
295 B754EC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   9.75 9.75 9.75 0.00 0.00 6.40 1.52 0.00 F5C927 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
296 621A74 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   15.05 15.05 15.05 270.00 0.00 5.49 2.74 0.00 87C477 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
297 28F0DE Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   20.07 20.07 20.07 90.00 0.00 5.49 3.66 0.00 CE626A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
298 FLOOR 1 OFFICE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   89.74 89.74 89.74 0.00 90.00 89.74 1.00 0.00 FLOOR 1 OFFICE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
299 879583 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   14.12 18.58 14.12 180.00 90.00 6.10 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
300 9B1541 Window 879583 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
301 CF850A Window 879583 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
302 83A098 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 270.00 90.00 7.01 3.05 0.00 E77E00 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
303 E326E4 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   14.96 21.37 14.96 90.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
304 A6BA23 Window E326E4 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
305 D10D28 Window E326E4 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
306 D4B39B Door E326E4 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
307 575A7B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 196C5F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
308 7E9E26 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 9DB411 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
309 FLOOR 1 OPERATING ROOM 1 SLAB Floor   CTF - ConductionTransferFunction FLOOR1OPERATINGROOM1SLAB_FFACTOR 0.283 0.264   42.74 42.74 42.74 0.00 180.00 6.10 7.01 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
310 E648BC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   22.30 22.30 22.30 0.00 0.00 6.10 3.66 0.00 2BD1E8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
311 FFE052 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   14.31 14.31 14.31 270.00 0.00 3.35 4.27 0.00 64A2F7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
312 611A3F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.13 6.13 6.13 90.00 0.00 3.35 1.83 0.00 874DF8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
313 FLOOR 1 OPERATING ROOM 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   85.47 85.47 85.47 0.00 90.00 85.47 1.00 0.00 FLOOR 1 OPERATING ROOM 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
314 9C6F66 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 816F6D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
315 1D96D7 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   15.61 22.30 15.61 90.00 90.00 7.32 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
316 591336 Window 1D96D7 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
317 38B811 Window 1D96D7 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
318 C044D6 Window 1D96D7 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
319 A2AAC5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 24EAE3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
320 1747DE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 270.00 90.00 7.32 3.05 0.00 765EA5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
321 F4C599 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 76F2F2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
322 964F72 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 2D53AC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
323 FLOOR 1 OPERATING ROOM 2 SLAB Floor   CTF - ConductionTransferFunction FLOOR1OPERATINGROOM2SLAB_FFACTOR 0.148 0.143   44.59 44.59 44.59 0.00 180.00 6.10 7.32 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
324 726F67 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 180.00 0.00 1.83 7.32 0.00 B44BE3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
325 406D70 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   19.51 19.51 19.51 180.00 0.00 4.27 4.57 0.00 352740 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
326 368A44 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.71 11.71 11.71 180.00 0.00 4.27 2.74 0.00 4D50C0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
327 FLOOR 1 OPERATING ROOM 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   89.19 89.19 89.19 0.00 90.00 89.19 1.00 0.00 FLOOR 1 OPERATING ROOM 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
328 9E12D4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   15.79 15.79 15.79 270.00 90.00 5.18 3.05 0.00 29BD5F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
329 FD0958 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 180.00 90.00 8.53 3.05 0.00 EBFE47 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
330 AE206C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 0.00 90.00 8.53 3.05 0.00 FEC1E3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
331 966665 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 90.00 90.00 0.91 3.05 0.00 1D9EED Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
332 52CA89 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 90.00 90.00 4.27 3.05 0.00 829DCE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
333 FLOOR 1 OPERATING ROOM 3 SLAB Floor   CTF - ConductionTransferFunction FLOOR1OPERATINGROOM3SLAB_FFACTOR 5.650E-003 5.642E-003   44.22 44.22 44.22 0.00 180.00 8.53 5.18 0.00 FLOOR 1 OPERATING ROOM 3 SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
334 8F1C77 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.30 1.30 1.30 180.00 0.00 2.13 0.61 0.00 10FB67 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
335 18AD08 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   9.48 9.48 9.48 270.00 0.00 5.18 1.83 0.00 D1E495 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
336 69AE66 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.20 5.20 5.20 180.00 0.00 2.13 2.44 0.00 A3F683 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
337 CF6C6E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.55 4.55 4.55 0.00 0.00 2.13 2.13 0.00 291561 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
338 678B62 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   23.69 23.69 23.69 90.00 0.00 5.18 4.57 0.00 5620F1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
339 FLOOR 1 OPERATING ROOM 3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   88.44 88.44 88.44 0.00 90.00 88.44 1.00 0.00 FLOOR 1 OPERATING ROOM 3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
340 2B4DBD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 0.00 90.00 0.91 3.05 0.00 762F8C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
341 FCD8D2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 FE5062 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
342 F740DF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 7434CD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
343 446771 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 CA6EDA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
344 A2F014 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 8594D3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
345 FLOOR 1 PACU SLAB Floor   CTF - ConductionTransferFunction FLOOR1PACUSLAB_FFACTOR 5.650E-003 5.642E-003   10.03 10.03 10.03 180.00 180.00 3.66 2.74 0.00 FLOOR 1 PACU SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
346 995832 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   10.03 10.03 10.03 180.00 0.00 3.66 2.74 0.00 BEC196 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
347 FLOOR 1 PACU_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   20.07 20.07 20.07 0.00 90.00 20.07 1.00 0.00 FLOOR 1 PACU_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
348 33A280 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 270.00 90.00 7.01 3.05 0.00 2B5816 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
349 BABBB4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 86A28D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
350 F9B592 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 FA9EF2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
351 6E46A9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 5B693D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
352 BA8FF7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 464A53 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
353 25B45C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.15 24.15 24.15 90.00 90.00 7.92 3.05 0.00 9853A2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
354 592524 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 852027 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
355 EAACE4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 90.00 90.00 4.57 3.05 0.00 92E22C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
356 3AE420 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 FE2C3E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
357 414FE2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   19.51 19.51 19.51 270.00 90.00 6.40 3.05 0.00 5B255F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
358 DEAC23 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 AA1709 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
359 22DAE3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 7D08C0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
360 FLOOR 1 PRE-OP HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1PRE-OPHALLSLAB_FFACTOR 5.650E-003 5.642E-003   49.05 49.05 49.05 180.00 180.00 2.44 20.12 0.00 FLOOR 1 PRE-OP HALL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
361 388CB3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 90.00 0.00 5.49 0.91 0.00 D023D9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
362 FB3834 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   8.36 8.36 8.36 270.00 0.00 5.49 1.52 0.00 DFCCAE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
363 343C52 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 0.00 0.00 2.44 5.49 0.00 630683 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
364 E63CF4 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 0.00 0.00 2.44 1.83 0.00 3110A1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
365 D6D2A5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 270.00 0.00 1.83 2.44 0.00 362FF8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
366 83172E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   8.36 8.36 8.36 270.00 0.00 5.49 1.52 0.00 98E1BD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
367 8FE324 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 90.00 0.00 5.49 0.91 0.00 8E5734 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
368 FLOOR 1 PRE-OP HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   98.11 98.11 98.11 0.00 90.00 98.11 1.00 0.00 FLOOR 1 PRE-OP HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
369 4DA0F5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 231744 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
370 8F966C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   15.79 15.79 15.79 270.00 90.00 5.18 3.05 0.00 42E287 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
371 FA21EE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 6A1AB7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
372 5B255F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   19.51 19.51 19.51 90.00 90.00 6.40 3.05 0.00 414FE2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
373 84418A Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   3.72 3.72 3.72 270.00 90.00 1.22 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.72 0.28 4
374 FLOOR 1 PRE-OP ROOM 1 SLAB Floor   CTF - ConductionTransferFunction FLOOR1PRE-OPROOM1SLAB_FFACTOR 6.189E-002 6.097E-002   17.56 17.56 17.56 90.00 180.00 6.40 2.74 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
375 3C43B2 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   9.20 9.20 9.20 270.00 0.00 3.35 2.74 0.00 6A14D8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
376 BC6EE7 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.34 3.34 3.34 0.00 0.00 2.74 1.22 0.00 F24E0D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
377 363652 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 180.00 0.00 2.74 1.83 0.00 21FC9D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
378 FLOOR 1 PRE-OP ROOM 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   35.12 35.12 35.12 0.00 90.00 35.12 1.00 0.00 FLOOR 1 PRE-OP ROOM 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
379 551E65 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.15 24.15 24.15 90.00 90.00 7.92 3.05 0.00 28DE5A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
380 8C3884 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.08 12.08 12.08 180.00 90.00 3.96 3.05 0.00 DFDE4F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
381 9853A2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.15 24.15 24.15 270.00 90.00 7.92 3.05 0.00 25B45C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
382 7AE5B9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   12.08 12.08 12.08 0.00 90.00 3.96 3.05 0.00 D9965C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
383 FLOOR 1 PRE-OP ROOM 2 SLAB Floor   CTF - ConductionTransferFunction FLOOR1PRE-OPROOM2SLAB_FFACTOR 5.650E-003 5.642E-003   31.40 31.40 31.40 0.00 180.00 3.96 7.92 0.00 FLOOR 1 PRE-OP ROOM 2 SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
384 39AFEA Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   9.29E-002 9.29E-002 9.29E-002 90.00 0.00 0.30 0.30 0.00 D4B714 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
385 CABD0E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.21 1.21 1.21 180.00 0.00 3.96 0.30 0.00 FD4C82 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
386 AF38CF Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.11 1.11 1.11 0.00 0.00 3.66 0.30 0.00 FDAEB8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
387 C0A312 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.25 7.25 7.25 0.00 0.00 3.96 1.83 0.00 F81393 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
388 661D88 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   18.39 18.39 18.39 0.00 0.00 3.35 5.49 0.00 1BDF58 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
389 AFFD01 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.34 3.34 3.34 0.00 0.00 0.61 5.49 0.00 795751 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
390 FLOOR 1 PRE-OP ROOM 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   62.80 62.80 62.80 0.00 90.00 62.80 1.00 0.00 FLOOR 1 PRE-OP ROOM 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
391 2DEB73 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 2FEACD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
392 7D08C0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 22DAE3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
393 36E420 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 CA45DE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
394 1535AC Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.64 0.36 4
395 FLOOR 1 PRE-OP TOILET SLAB Floor   CTF - ConductionTransferFunction FLOOR1PRE-OPTOILETSLAB_FFACTOR 0.339 0.313   5.02 5.02 5.02 270.00 180.00 1.83 2.74 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
396 97616F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 270.00 0.00 1.83 2.74 0.00 14C7EF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
397 FLOOR 1 PRE-OP TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 1 PRE-OP TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
398 95486C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 30DB21 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
399 EAE60F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.22 10.22 10.22 180.00 90.00 3.35 3.05 0.00 361D65 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
400 6D2616 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   12.08 17.65 12.08 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
401 1D94BE Window 6D2616 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
402 18748E Window 6D2616 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
403 704EC3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 90.00 90.00 4.57 3.05 0.00 E9F3F6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
404 E20721 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 824665 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
405 FA9EF2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 F9B592 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
406 FLOOR 1 PROCEDURE ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1PROCEDUREROOMSLAB_FFACTOR 0.199 0.190   26.48 26.48 26.48 270.00 180.00 4.57 5.79 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
407 673317 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.97 6.97 6.97 270.00 0.00 4.57 1.52 0.00 D2FA45 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
408 E5C1C9 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   16.72 16.72 16.72 270.00 0.00 4.57 3.66 0.00 4E920E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
409 79376C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2.79 2.79 2.79 90.00 0.00 4.57 0.61 0.00 E9C9E1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
410 FLOOR 1 PROCEDURE ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   52.95 52.95 52.95 0.00 90.00 52.95 1.00 0.00 FLOOR 1 PROCEDURE ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
411 6EA718 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 270.00 90.00 4.57 3.05 0.00 2FAF44 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
412 2730E5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 90.00 90.00 7.01 3.05 0.00 7E0561 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
413 E608B9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 68F53B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
414 25AB11 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 0.00 90.00 1.52 3.05 0.00 7B67EC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
415 5A39B1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   15.79 15.79 15.79 90.00 90.00 5.18 3.05 0.00 612A96 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
416 234734 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 F7F8BA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
417 57B162 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 11E9BF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
418 7BB928 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   19.51 19.51 19.51 270.00 90.00 6.40 3.05 0.00 6B31A8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
419 A5A6A3 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   8.73 12.08 8.73 180.00 90.00 3.96 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
420 137A56 Window A5A6A3 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 3.34 3.34 3.34 180.00 90.00 2.74 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
421 FLOOR 1 RECEPTION SLAB Floor   CTF - ConductionTransferFunction FLOOR1RECEPTIONSLAB_FFACTOR 7.483E-002 7.350E-002   47.29 47.29 47.29 270.00 180.00 6.88 6.88 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
422 A02892 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.92 4.92 4.92 180.00 0.00 2.22 2.22 0.00 83658D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
423 9114B7 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 90.00 0.00 5.49 2.44 0.00 7FA5FF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
424 700E69 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   28.99 28.99 28.99 270.00 0.00 7.32 3.96 0.00 14CDC6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
425 FLOOR 1 RECEPTION_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   94.58 94.58 94.58 0.00 90.00 94.58 1.00 0.00 FLOOR 1 RECEPTION_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
426 11E9BF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 57B162 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
427 839A66 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 BDC047 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
428 FE2C3E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 3AE420 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
429 CD7BAD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 0.00 90.00 4.88 3.05 0.00 8259AE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
430 6A1AB7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 FA21EE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
431 FLOOR 1 RECEPTION HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1RECEPTIONHALLSLAB_FFACTOR 5.650E-003 5.642E-003   11.89 11.89 11.89 0.00 180.00 4.88 2.44 0.00 FLOOR 1 RECEPTION HALL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
432 68AAF3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.55 4.55 4.55 0.00 0.00 2.13 2.13 0.00 115AA8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
433 DE014E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.85 5.85 5.85 0.00 0.00 2.74 2.13 0.00 E3963E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
434 709E99 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.49 1.49 1.49 180.00 0.00 4.88 0.30 0.00 7A8C4C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
435 FLOOR 1 RECEPTION HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   23.78 23.78 23.78 0.00 90.00 23.78 1.00 0.00 FLOOR 1 RECEPTION HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
436 28B002 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   27.03 41.81 27.03 180.00 90.00 13.72 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
437 8D508E Window 28B002 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
438 B2D381 Window 28B002 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
439 1DA13A Window 28B002 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
440 44E54A Window 28B002 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
441 D2D3BC Door 28B002 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
442 C528DA Door 28B002 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
443 EFD3F9 Door 28B002 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
444 F4FE92 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 809229 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
445 66B6F7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 330DF9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
446 72C4ED Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.81 41.81 41.81 0.00 90.00 13.72 3.05 0.00 59CEFB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
447 FLOOR 1 RECOVERY ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1RECOVERYROOMSLAB_FFACTOR 0.251 0.236   50.17 50.17 50.17 90.00 180.00 3.66 13.72 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
448 C5ECA6 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   12.26 12.26 12.26 90.00 0.00 3.66 3.35 0.00 4017DC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
449 65D500 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   26.76 26.76 26.76 90.00 0.00 3.66 7.32 0.00 17C5CF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
450 AE5EBC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.69 6.69 6.69 90.00 0.00 3.66 1.83 0.00 4C8372 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
451 2A1A9E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 270.00 0.00 3.66 1.22 0.00 F87FCE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
452 FLOOR 1 RECOVERY ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   100.34 100.34 100.34 0.00 90.00 100.34 1.00 0.00 FLOOR 1 RECOVERY ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
453 EA6DC8 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.76 6.50 5.76 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.71 0.29 4
454 757D10 Window EA6DC8 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 0.74 0.74 0.74 180.00 90.00 0.61 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.71 0.29 4
455 612A96 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   15.79 15.79 15.79 270.00 90.00 5.18 3.05 0.00 5A39B1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
456 BDC047 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 839A66 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
457 42E287 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   15.79 15.79 15.79 90.00 90.00 5.18 3.05 0.00 8F966C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
458 FLOOR 1 SCHEDULING SLAB Floor   CTF - ConductionTransferFunction FLOOR1SCHEDULINGSLAB_FFACTOR 0.175 0.168   11.06 11.06 11.06 90.00 180.00 5.18 2.13 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
459 513564 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.90 3.90 3.90 0.00 0.00 2.13 1.83 0.00 C51FD6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
460 58F893 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.15 7.15 7.15 180.00 0.00 2.13 3.35 0.00 CFB630 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
461 FLOOR 1 SCHEDULING_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   22.11 22.11 22.11 0.00 90.00 22.11 1.00 0.00 FLOOR 1 SCHEDULING_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
462 7816FD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 90.00 90.00 4.27 3.05 0.00 D61127 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
463 1B2EF8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 270.00 90.00 4.27 3.05 0.00 2C9CF4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
464 24EAE3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 A2AAC5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
465 9DB411 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 7E9E26 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
466 FLOOR 1 SCRUB SLAB Floor   CTF - ConductionTransferFunction FLOOR1SCRUBSLAB_FFACTOR 5.650E-003 5.642E-003   7.80 7.80 7.80 90.00 180.00 4.27 1.83 0.00 FLOOR 1 SCRUB SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
467 7008C0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.80 7.80 7.80 90.00 0.00 4.27 1.83 0.00 8C822C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
468 FLOOR 1 SCRUB_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   15.61 15.61 15.61 0.00 90.00 15.61 1.00 0.00 FLOOR 1 SCRUB_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
469 762F8C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 180.00 90.00 0.91 3.05 0.00 2B4DBD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
470 5D199F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 90.00 90.00 0.91 3.05 0.00 CA9655 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
471 ACADA4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 270.00 90.00 4.27 3.05 0.00 4A854B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
472 4398AD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 EA4B61 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
473 9E478E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 5EB34C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
474 6B967C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.22 10.22 10.22 90.00 90.00 3.35 3.05 0.00 49DA86 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
475 FLOOR 1 SOIL SLAB Floor   CTF - ConductionTransferFunction FLOOR1SOILSLAB_FFACTOR 5.650E-003 5.642E-003   11.71 11.71 11.71 90.00 180.00 4.27 2.74 0.00 FLOOR 1 SOIL SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
476 4B54B4 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.84 0.84 0.84 0.00 0.00 2.74 0.30 0.00 C81AED Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
477 88D2F8 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.85 5.85 5.85 180.00 0.00 2.74 2.13 0.00 15A915 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
478 7274F6 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 0.00 0.00 2.74 1.83 0.00 4B590B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
479 FLOOR 1 SOIL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   23.41 23.41 23.41 0.00 90.00 23.41 1.00 0.00 FLOOR 1 SOIL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
480 A1087A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 70DAD1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
481 41CE25 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 FA769A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
482 9A776E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 445A39 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
483 9ABA5B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 814856 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
484 FLOOR 1 SOIL HOLD SLAB Floor   CTF - ConductionTransferFunction FLOOR1SOILHOLDSLAB_FFACTOR 5.650E-003 5.642E-003   5.20 5.20 5.20 0.00 180.00 2.13 2.44 0.00 FLOOR 1 SOIL HOLD SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
485 58A74A Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 270.00 0.00 2.44 1.83 0.00 5CA4CF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
486 D78A26 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.74 0.74 0.74 90.00 0.00 2.44 0.30 0.00 D1899C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
487 FLOOR 1 SOIL HOLD_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.41 10.41 10.41 0.00 90.00 10.41 1.00 0.00 FLOOR 1 SOIL HOLD_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
488 37E2C7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 6A2C62 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
489 23683B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 825233 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
490 CA9655 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 270.00 90.00 0.91 3.05 0.00 5D199F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
491 121DFF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 B551AD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
492 FAE342 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 5CD67D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
493 FLOOR 1 SOIL WORK SLAB Floor   CTF - ConductionTransferFunction FLOOR1SOILWORKSLAB_FFACTOR 5.650E-003 5.642E-003   16.72 16.72 16.72 0.00 180.00 4.57 3.66 0.00 FLOOR 1 SOIL WORK SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
494 A44272 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   1.86 1.86 1.86 90.00 0.00 3.05 0.61 0.00 26AF41 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
495 B9DDBA Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.57 5.57 5.57 90.00 0.00 3.05 1.83 0.00 D10995 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
496 9EBF3E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2.79 2.79 2.79 0.00 0.00 4.57 0.61 0.00 EB4979 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
497 903092 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.50 6.50 6.50 0.00 0.00 2.13 3.05 0.00 56C7DA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
498 FLOOR 1 SOIL WORK_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   33.45 33.45 33.45 0.00 90.00 33.45 1.00 0.00 FLOOR 1 SOIL WORK_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
499 5FD018 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 6822BB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
500 809229 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 F4FE92 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
501 B40F89 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   8.92 11.15 8.92 270.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.61 0.39 4
502 E33BAE Window B40F89 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 270.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.61 0.39 4
503 997723 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   16.82 23.23 16.82 180.00 90.00 7.62 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
504 24167A Window 997723 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
505 2C0938 Window 997723 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
506 62B5AF Door 997723 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
507 CA45DE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 36E420 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
508 5B693D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 6E46A9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
509 FLOOR 1 STEP DOWN SLAB Floor   CTF - ConductionTransferFunction FLOOR1STEPDOWNSLAB_FFACTOR 0.378 0.346   27.87 27.87 27.87 270.00 180.00 3.66 7.62 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
510 FBDD49 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 0.00 0.00 3.66 3.66 0.00 5EBA9B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
511 4284B6 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.69 6.69 6.69 90.00 0.00 3.66 1.83 0.00 2C31F2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
512 FCE842 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.80 7.80 7.80 270.00 0.00 3.66 2.13 0.00 4968A2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
513 FLOOR 1 STEP DOWN_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   55.74 55.74 55.74 0.00 90.00 55.74 1.00 0.00 FLOOR 1 STEP DOWN_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
514 829DCE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 270.00 90.00 4.27 3.05 0.00 52CA89 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
515 E77E00 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 90.00 90.00 7.01 3.05 0.00 83A098 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
516 CEC7BD Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.20 7.43 5.20 180.00 90.00 2.44 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
517 8600DD Window CEC7BD Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
518 8C4FA5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 F43F35 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
519 B3A518 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 4161C8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
520 44686F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 C92A6E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
521 6A2C62 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 37E2C7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
522 A809DD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.22 10.22 10.22 270.00 90.00 3.35 3.05 0.00 619EE6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
523 EE0E68 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 38F548 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
524 88AE01 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 35028C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
525 2C9CF4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 90.00 90.00 4.27 3.05 0.00 1B2EF8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
526 765EA5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 90.00 90.00 7.32 3.05 0.00 1747DE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
527 2B370E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 E321D9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
528 F30797 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 87BFF9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
529 FLOOR 1 STERILE HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1STERILEHALLSLAB_FFACTOR 3.784E-002 3.749E-002   57.23 57.23 57.23 270.00 180.00 23.47 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
530 3179A6 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   8.92 8.92 8.92 0.00 0.00 2.44 3.66 0.00 75353D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
531 370DB2 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.20 5.20 5.20 180.00 0.00 2.44 2.13 0.00 4B217A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
532 34B3F0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.43 7.43 7.43 90.00 0.00 3.05 2.44 0.00 4CDC86 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
533 CEDA0D Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.95 5.95 5.95 0.00 0.00 2.44 2.44 0.00 C2CE5F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
534 4469CD Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 90.00 0.00 5.49 2.44 0.00 10830D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
535 F62393 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 90.00 0.00 1.83 2.44 0.00 283EC6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
536 340FB5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 0.00 0.00 2.44 1.83 0.00 20B940 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
537 CDA7F8 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.43 7.43 7.43 270.00 0.00 3.05 2.44 0.00 2805F0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
538 FLOOR 1 STERILE HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   114.46 114.46 114.46 0.00 90.00 114.46 1.00 0.00 FLOOR 1 STERILE HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
539 8043B2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 94A56A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
540 38F548 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 EE0E68 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
541 96662A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 415590 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
542 1003C1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 0.00 90.00 10.06 3.05 0.00 66D163 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
543 863C6C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 758B3C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
544 808817 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 FD8CF2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
545 EA4B61 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 4398AD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
546 FLOOR 1 NURSE STORAGE SLAB Floor   CTF - ConductionTransferFunction FLOOR1NURSESTORAGESLAB_FFACTOR 5.650E-003 5.642E-003   36.79 36.79 36.79 0.00 180.00 10.06 3.66 0.00 FLOOR 1 NURSE STORAGE SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
547 C1737B Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   10.22 10.22 10.22 0.00 0.00 3.05 3.35 0.00 C3DB37 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
548 D44BF1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.07 3.07 3.07 180.00 0.00 10.06 0.30 0.00 D29B01 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
549 5C05FF Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   23.50 23.50 23.50 0.00 0.00 7.01 3.35 0.00 F6FE66 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
550 FLOOR 1 STERILE STORAGE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   73.58 73.58 73.58 0.00 90.00 73.58 1.00 0.00 FLOOR 1 STERILE STORAGE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
551 707E04 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 90.00 90.00 4.88 3.05 0.00 87231D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
552 8E5BB9 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   18.39 21.37 18.39 270.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.69 0.31 4
553 71E924 Door 8E5BB9 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   2.97 2.97 2.97 270.00 90.00 1.22 2.44 4.00E-004 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.65 0.35 4
554 859BC1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   22.95 37.16 22.95 0.00 90.00 12.19 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
555 A1ED60 Window 859BC1 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
556 E8D997 Window 859BC1 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
557 88E1FC Window 859BC1 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
558 3C44F9 Door 859BC1 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
559 49526E Door 859BC1 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
560 865AE8 Door 859BC1 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
561 891195 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 9C0202 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
562 8B4DC1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 72BCFE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
563 19D150 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 BBEE0B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
564 814856 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 9ABA5B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
565 5B533A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 319A6B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
566 FLOOR 1 STORAGE SLAB Floor   CTF - ConductionTransferFunction FLOOR1STORAGESLAB_FFACTOR 0.205 0.195   85.47 85.47 85.47 270.00 180.00 7.01 12.19 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
567 FLOOR 1 STORGE ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   85.47 85.47 85.47 270.00 0.00 7.01 12.19 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.27 0.73 4
568 FLOOR 1 STORAGE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   170.94 170.94 170.94 0.00 90.00 170.94 1.00 0.00 FLOOR 1 STORAGE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
569 61E610 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   10.03 13.01 10.03 90.00 90.00 4.27 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
570 F83F33 Window 61E610 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.97 2.97 2.97 90.00 90.00 2.44 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
571 76F2F2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 F4C599 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
572 D61127 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 270.00 90.00 4.27 3.05 0.00 7816FD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
573 196C5F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 575A7B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
574 FLOOR 1 SUB-STERILE SLAB Floor   CTF - ConductionTransferFunction FLOOR1SUB-STERILESLAB_FFACTOR 0.214 0.203   18.21 18.21 18.21 180.00 180.00 4.27 4.27 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
575 1875B3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   18.21 18.21 18.21 180.00 0.00 4.27 4.27 0.00 D3CF55 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
576 FLOOR 1 SUB-STERILE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   36.42 36.42 36.42 0.00 90.00 36.42 1.00 0.00 FLOOR 1 SUB-STERILE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
577 39E49D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 62475F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
578 F43F35 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 8C4FA5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
579 89BBEB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 A4B378 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
580 87231D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 270.00 90.00 4.88 3.05 0.00 707E04 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
581 529072 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   7.43 14.86 7.43 90.00 90.00 4.88 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.67 0.33 4
582 5E66D1 Door 529072 CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.761 1.761   7.43 7.43 7.43 90.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.66 0.34 4
583 C1C64E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 986A05 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
584 1D9EED Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.79 2.79 2.79 270.00 90.00 0.91 3.05 0.00 966665 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
585 20FB14 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.65 4.65 4.65 270.00 90.00 1.52 3.05 0.00 F4D6DD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
586 DEFACF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 32CC19 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
587 FLOOR 1 UTILITY HALL SLAB Floor   CTF - ConductionTransferFunction FLOOR1UTILITYHALLSLAB_FFACTOR 0.186 0.178   23.78 23.78 23.78 90.00 180.00 9.75 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
588 FLOOR 1 UTILITY HALL ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   11.89 11.89 11.89 180.00 0.00 2.44 4.88 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.32 0.68 4
589 5136E3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   0.74 0.74 0.74 0.00 0.00 2.44 0.30 0.00 1C7FB1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
590 EFCC3C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.15 11.15 11.15 270.00 0.00 4.57 2.44 0.00 C84AE1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
591 FLOOR 1 UTILITY HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   47.57 47.57 47.57 0.00 90.00 47.57 1.00 0.00 FLOOR 1 UTILITY HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
592 2E8328 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 9879B2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
593 E321D9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 2B370E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
594 E89C6C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 23CCB1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
595 816F6D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 9C6F66 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
596 FLOOR 1 UTILITY JANITOR SLAB Floor   CTF - ConductionTransferFunction FLOOR1UTILITYJANITORSLAB_FFACTOR 5.650E-003 5.642E-003   3.90 3.90 3.90 90.00 180.00 2.13 1.83 0.00 FLOOR 1 UTILITY JANITOR SLAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
597 5F697A Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.90 3.90 3.90 90.00 0.00 2.13 1.83 0.00 4F2F27 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
598 FLOOR 1 UTILITY JANITOR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7.80 7.80 7.80 0.00 90.00 7.80 1.00 0.00 FLOOR 1 UTILITY JANITOR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
599 EC28A9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 E82152 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
600 204CB9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 0.00 90.00 6.10 3.05 0.00 A28F01 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
601 62475F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 39E49D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
602 D95F04 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   12.54 16.72 12.54 90.00 90.00 5.49 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.55 0.45 4
603 E14DAE Door D95F04 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.59 0.41 4
604 B1F5EE Window D95F04 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
605 87BFF9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 F30797 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
606 23CCB1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 E89C6C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
607 FLOOR 1 UTILITY ROOM SLAB Floor   CTF - ConductionTransferFunction FLOOR1UTILITYROOMSLAB_FFACTOR 0.148 0.143   33.45 33.45 33.45 180.00 180.00 6.10 5.49 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
608 7DB101 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   10.03 10.03 10.03 270.00 0.00 5.49 1.83 0.00 909DB9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
609 F28371 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   23.41 23.41 23.41 180.00 0.00 4.27 5.49 0.00 C25071 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
610 FLOOR 1 UTILITY ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   66.89 66.89 66.89 0.00 90.00 66.89 1.00 0.00 FLOOR 1 UTILITY ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
611 231744 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 4DA0F5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
612 3330D8 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.48 7.43 5.48 270.00 90.00 2.44 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.69 0.31 4
613 84A1D5 Door 3330D8 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.69 0.31 4
614 2FEACD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 2DEB73 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
615 AA1709 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 DEAC23 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
616 FLOOR 1 VESTIBULE SLAB Floor   CTF - ConductionTransferFunction FLOOR1VESTIBULESLAB_FFACTOR 0.339 0.313   6.69 6.69 6.69 90.00 180.00 2.44 2.74 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
617 C34217 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.69 6.69 6.69 90.00 0.00 2.44 2.74 0.00 6E3B28 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
618 FLOOR 1 VESTIBULE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   13.38 13.38 13.38 0.00 90.00 13.38 1.00 0.00 FLOOR 1 VESTIBULE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
619 208CCF Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   8.92 11.15 8.92 90.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
620 F52F3D Window 208CCF Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
621 AEF992 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   19.32 26.01 19.32 180.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
622 80885D Window AEF992 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 6.69 6.69 6.69 180.00 90.00 5.49 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
623 9AC2E9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 CE4555 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
624 436189 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 7C84B6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
625 B184C1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 CC4EB4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
626 BC8EB7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 3C9825 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
627 75353D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   8.92 8.92 8.92 270.00 180.00 3.66 2.44 0.00 3179A6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
628 2BD1E8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   22.30 22.30 22.30 180.00 180.00 6.10 3.66 0.00 E648BC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
629 240A7C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   31.22 31.22 31.22 180.00 0.00 8.53 3.66 0.00 D14D65 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
630 FLOOR 2 CONFERENCE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   62.43 62.43 62.43 0.00 90.00 62.43 1.00 0.00 FLOOR 2 CONFERENCE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
631 F6D879 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 58AD84 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
632 1701A6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 680AA1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
633 772842 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 577A10 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
634 3C9825 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 BC8EB7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
635 C2CE5F Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.95 5.95 5.95 0.00 180.00 2.44 2.44 0.00 CEDA0D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
636 7149EA Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.95 5.95 5.95 0.00 0.00 2.44 2.44 0.00 CDCA72 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
637 FLOOR 2 CONFERENCE TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   11.89 11.89 11.89 0.00 90.00 11.89 1.00 0.00 FLOOR 2 CONFERENCE TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
638 296861 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 7620CF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
639 3D4DE8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 36A02A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
640 8A5790 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 D79C57 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
641 2DB420 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 DE64CC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
642 56C7DA Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.50 6.50 6.50 90.00 180.00 3.05 2.13 0.00 903092 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
643 E1B973 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.50 6.50 6.50 90.00 0.00 3.05 2.13 0.00 1EE332 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
644 FLOOR 2 DICTATION_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   13.01 13.01 13.01 0.00 90.00 13.01 1.00 0.00 FLOOR 2 DICTATION_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
645 640E64 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 90.00 90.00 9.14 3.05 0.00 9E6B6C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
646 10E44F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 A72F04 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
647 54D065 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   8.92 11.15 8.92 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
648 FEEF06 Window 54D065 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
649 1775A6 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   21.18 27.87 21.18 270.00 90.00 9.14 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
650 2BE8DE Window 1775A6 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 270.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.57 0.43 4
651 513E2A Window 1775A6 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 270.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.68 0.32 4
652 BA5CD9 Window 1775A6 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 270.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.61 0.39 4
653 6E3B28 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.69 6.69 6.69 270.00 180.00 2.44 2.74 0.00 C34217 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
654 14C7EF Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 270.00 180.00 1.83 2.74 0.00 97616F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
655 5EBA9B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 270.00 180.00 3.66 3.66 0.00 FBDD49 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
656 F24E0D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.34 3.34 3.34 270.00 180.00 1.22 2.74 0.00 BC6EE7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
657 D023D9 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 0.00 180.00 0.91 5.49 0.00 388CB3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
658 A4BE81 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   33.45 33.45 33.45 0.00 0.00 3.66 9.14 0.00 F4E5F5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
659 FLOOR 2 EXAM 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   66.89 66.89 66.89 0.00 90.00 66.89 1.00 0.00 FLOOR 2 EXAM 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
660 4EE021 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 90.00 90.00 9.14 3.05 0.00 42FAB2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
661 6ED237 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 270.00 90.00 9.14 3.05 0.00 53450D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
662 97F00A Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   13.01 16.72 13.01 180.00 90.00 5.49 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
663 1AD478 Window 97F00A Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 3.72 3.72 3.72 180.00 90.00 3.05 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
664 ADD799 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 EEECA3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
665 4017DC Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   12.26 12.26 12.26 90.00 180.00 3.66 3.35 0.00 C5ECA6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
666 CCAA9D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 180.00 180.00 5.49 2.44 0.00 92E327 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
667 4968A2 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.80 7.80 7.80 270.00 180.00 3.66 2.13 0.00 FCE842 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
668 4579A7 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   15.05 15.05 15.05 180.00 180.00 5.49 2.74 0.00 A0117C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
669 FDAEB8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.11 1.11 1.11 270.00 180.00 0.30 3.66 0.00 AF38CF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
670 E3B855 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.56 0.56 0.56 90.00 180.00 0.30 1.83 0.00 E8F02D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
671 906F5E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   50.17 50.17 50.17 0.00 0.00 5.49 9.14 0.00 68EB71 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
672 FLOOR 2 EXAM 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   100.34 100.34 100.34 0.00 90.00 100.34 1.00 0.00 FLOOR 2 EXAM 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
673 DFA4B1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 0.00 90.00 7.32 3.05 0.00 CFAD9D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
674 F23BF4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 270.00 90.00 9.14 3.05 0.00 6713DA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
675 A497E9 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   16.35 22.30 16.35 180.00 90.00 7.32 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
676 27F0AC Window A497E9 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 5.95 5.95 5.95 180.00 90.00 4.88 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
677 26E66C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 90.00 90.00 9.14 3.05 0.00 479A9C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
678 17C5CF Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   26.76 26.76 26.76 180.00 180.00 7.32 3.66 0.00 65D500 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
679 BA0A29 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   17.84 17.84 17.84 180.00 180.00 7.32 2.44 0.00 7F6B1B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
680 26AF41 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.86 1.86 1.86 180.00 180.00 0.61 3.05 0.00 A44272 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
681 75A3C4 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 90.00 180.00 2.74 1.83 0.00 156F92 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
682 BEC196 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   10.03 10.03 10.03 90.00 180.00 2.74 3.66 0.00 995832 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
683 9B49F5 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.84 0.84 0.84 90.00 180.00 0.30 2.74 0.00 672F1E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
684 EB611D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.37 0.37 0.37 0.00 180.00 1.22 0.30 0.00 1B4EDC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
685 C81AED Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.84 0.84 0.84 270.00 180.00 0.30 2.74 0.00 4B54B4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
686 BD5B50 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.34 3.34 3.34 180.00 180.00 1.22 2.74 0.00 52F395 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
687 3AEAAB Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.01 13.01 13.01 90.00 0.00 3.05 4.27 0.00 2B4713 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
688 D74115 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   44.59 44.59 44.59 0.00 0.00 7.32 6.10 0.00 7F8407 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
689 5065F0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   9.29 9.29 9.29 270.00 0.00 3.05 3.05 0.00 8FB568 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
690 FLOOR 2 EXAM 3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   133.78 133.78 133.78 0.00 90.00 133.78 1.00 0.00 FLOOR 2 EXAM 3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
691 7C84B6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 436189 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
692 D88779 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 F6E717 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
693 577E2E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 DA6040 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
694 88A75F Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   4.27 6.50 4.27 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
695 724114 Window 88A75F Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 180.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
696 4E78E0 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.80 7.80 7.80 90.00 180.00 3.66 2.13 0.00 BE1AE1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
697 C0697F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.80 7.80 7.80 90.00 0.00 3.66 2.13 0.00 F69079 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
698 FLOOR 2 EXAM 4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   15.61 15.61 15.61 0.00 90.00 15.61 1.00 0.00 FLOOR 2 EXAM 4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
699 83B6E3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 290DF3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
700 AC956A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   23.23 23.23 23.23 270.00 90.00 7.62 3.05 0.00 571934 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
701 B4E619 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   17.28 23.23 17.28 90.00 90.00 7.62 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.54 0.46 4
702 D538C4 Window B4E619 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.97 2.97 2.97 90.00 90.00 2.44 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
703 5635BC Window B4E619 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.97 2.97 2.97 90.00 90.00 2.44 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.54 0.46 4
704 BFA29B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 DE6295 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
705 65AB67 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   9.10 9.10 9.10 180.00 180.00 4.27 2.13 0.00 D7AC92 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
706 C25071 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   23.41 23.41 23.41 0.00 180.00 4.27 5.49 0.00 F28371 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
707 31B3DF Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.52 32.52 32.52 270.00 0.00 7.62 4.27 0.00 1DC177 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
708 FLOOR 2 EXAM 5_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   65.03 65.03 65.03 0.00 90.00 65.03 1.00 0.00 FLOOR 2 EXAM 5_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
709 F29458 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ED650B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
710 1EB5B1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 2884D1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
711 9EC269 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   9.75 13.94 9.75 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
712 831C1D Window 9EC269 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 4.18 4.18 4.18 0.00 90.00 2.74 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
713 47CE83 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 270.00 90.00 4.57 3.05 0.00 3947B8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
714 A8FC82 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 16BE00 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
715 C84AE1 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.15 11.15 11.15 90.00 180.00 4.57 2.44 0.00 EFCC3C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
716 F67EC8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.20 5.20 5.20 90.00 180.00 2.44 2.13 0.00 F6F6C6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
717 10FB67 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.30 1.30 1.30 180.00 180.00 2.13 0.61 0.00 8F1C77 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
718 1624C5 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.25 3.25 3.25 180.00 180.00 2.13 1.52 0.00 FB17DD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
719 917AB5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   20.90 20.90 20.90 90.00 0.00 4.57 4.57 0.00 F7BE2F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
720 FLOOR 2 EXAM 6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   41.81 41.81 41.81 0.00 90.00 41.81 1.00 0.00 FLOOR 2 EXAM 6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
721 247258 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 270.00 90.00 10.06 3.05 0.00 14F382 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
722 B316F7 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   16.72 22.30 16.72 0.00 90.00 7.32 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
723 9BB95F Window B316F7 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
724 C0778D Window B316F7 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
725 FF8B08 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 90.00 90.00 10.06 3.05 0.00 55191F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
726 F976A9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 180.00 90.00 7.32 3.05 0.00 3FBBC8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
727 8D6453 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   10.41 10.41 10.41 0.00 180.00 4.27 2.44 0.00 C732D4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
728 D1899C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.74 0.74 0.74 0.00 180.00 0.30 2.44 0.00 D78A26 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
729 5620F1 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   23.69 23.69 23.69 90.00 180.00 5.18 4.57 0.00 678B62 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
730 40E182 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.97 6.97 6.97 270.00 180.00 1.52 4.57 0.00 9A5B84 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
731 A6147C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   25.08 25.08 25.08 0.00 180.00 2.74 9.14 0.00 7B9EEC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
732 37898A Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.69 6.69 6.69 180.00 180.00 7.32 0.91 0.00 C8F2F1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
733 F0D8EE Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   30.66 30.66 30.66 90.00 0.00 10.06 3.05 0.00 A72B2F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
734 567037 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   6.13 6.13 6.13 180.00 0.00 0.61 10.06 0.00 60F383 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
735 6B3E65 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   17.84 17.84 17.84 90.00 0.00 4.88 3.66 0.00 B46F2C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
736 245972 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.15 11.15 11.15 90.00 0.00 3.05 3.66 0.00 D10EC7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
737 F17DF7 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.80 7.80 7.80 0.00 0.00 3.66 2.13 0.00 63B825 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
738 FLOOR 2 EXAM 7_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   147.16 147.16 147.16 0.00 90.00 147.16 1.00 0.00 FLOOR 2 EXAM 7_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
739 D7DC8D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 90.00 90.00 4.57 3.05 0.00 2E6DF0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
740 9621FD Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   11.15 16.72 11.15 0.00 90.00 5.49 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
741 7D2D69 Window 9621FD Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
742 2EF63B Window 9621FD Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
743 6A2DCE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 270.00 90.00 4.57 3.05 0.00 D37566 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
744 7A03ED Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 BADB96 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
745 A9A1F6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   25.08 25.08 25.08 0.00 180.00 5.49 4.57 0.00 21C5E8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
746 DA760E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   25.08 25.08 25.08 0.00 0.00 5.49 4.57 0.00 8A695C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
747 FLOOR 2 EXAM 8_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   50.17 50.17 50.17 0.00 90.00 50.17 1.00 0.00 FLOOR 2 EXAM 8_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
748 42CEE1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   8.36 11.15 8.36 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
749 C417C0 Window 42CEE1 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
750 35051E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 270.00 90.00 10.06 3.05 0.00 5C7E1E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
751 685FFA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 90.00 90.00 10.06 3.05 0.00 5556EE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
752 B51929 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 32BAA7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
753 8E5734 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 90.00 180.00 5.49 0.91 0.00 8FE324 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
754 4E920E Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   16.72 16.72 16.72 0.00 180.00 3.66 4.57 0.00 E5C1C9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
755 87C477 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   15.05 15.05 15.05 270.00 180.00 5.49 2.74 0.00 621A74 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
756 5D2769 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.79 36.79 36.79 180.00 0.00 3.66 10.06 0.00 AE8664 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
757 FLOOR 2 EXAM 9_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   73.58 73.58 73.58 0.00 90.00 73.58 1.00 0.00 FLOOR 2 EXAM 9_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
758 4979C8 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
759 9E6B6C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 270.00 90.00 9.14 3.05 0.00 640E64 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
760 DF91E0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 9CE650 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
761 53450D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 90.00 90.00 9.14 3.05 0.00 6ED237 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
762 DFCCAE Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   8.36 8.36 8.36 90.00 180.00 5.49 1.52 0.00 FB3834 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
763 D4B714 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   9.29E-002 9.29E-002 9.29E-002 0.00 180.00 0.30 0.30 0.00 39AFEA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
764 3AE495 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.84 0.84 0.84 0.00 180.00 0.30 2.74 0.00 BD4B70 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
765 526C70 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.74 0.74 0.74 0.00 180.00 0.30 2.44 0.00 C75191 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
766 2C31F2 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.69 6.69 6.69 180.00 180.00 1.83 3.66 0.00 4284B6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
767 E26130 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   16.72 16.72 16.72 270.00 0.00 9.14 1.83 0.00 AA7BE2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
768 FLOOR 2 EXAM HALL 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   33.45 33.45 33.45 0.00 90.00 33.45 1.00 0.00 FLOOR 2 EXAM HALL 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
769 42FAB2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 270.00 90.00 9.14 3.05 0.00 4EE021 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
770 815D63 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 EE34A3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
771 6713DA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 90.00 90.00 9.14 3.05 0.00 F23BF4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
772 8CA0BF Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
773 4C8372 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.69 6.69 6.69 180.00 180.00 1.83 3.66 0.00 AE5EBC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
774 243E09 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 180.00 180.00 1.83 2.44 0.00 4A49C1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
775 C94CC0 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 180.00 180.00 1.83 2.74 0.00 AA2E8F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
776 BD39AC Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   9.29E-002 9.29E-002 9.29E-002 270.00 180.00 0.30 0.30 0.00 6ECCF3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
777 75EAF8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.46 0.46 0.46 90.00 180.00 0.30 1.52 0.00 EC2478 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
778 E9AEFF Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   16.72 16.72 16.72 270.00 0.00 9.14 1.83 0.00 948D7B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
779 FLOOR 2 EXAM HALL 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   33.45 33.45 33.45 0.00 90.00 33.45 1.00 0.00 FLOOR 2 EXAM HALL 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
780 479A9C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.87 27.87 27.87 270.00 90.00 9.14 3.05 0.00 26E66C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
781 DA6040 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 577E2E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
782 6C95E7 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
783 BC25F3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 25F524 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
784 C08963 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 390BCF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
785 36A02A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 3D4DE8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
786 A08A28 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2.23 2.23 2.23 180.00 180.00 0.61 3.66 0.00 DDCF3E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
787 F87FCE Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 180.00 180.00 1.22 3.66 0.00 2A1A9E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
788 BAE3F8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 180.00 180.00 1.83 2.44 0.00 8F5FFC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
789 D10995 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.57 5.57 5.57 0.00 180.00 1.83 3.05 0.00 B9DDBA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
790 D4A2A4 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.57 5.57 5.57 180.00 0.00 1.83 3.05 0.00 C271D9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
791 6C1891 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.15 11.15 11.15 270.00 0.00 6.10 1.83 0.00 3C8351 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
792 FLOOR 2 EXAM HALL 3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   33.45 33.45 33.45 0.00 90.00 33.45 1.00 0.00 FLOOR 2 EXAM HALL 3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
793 46F148 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 CBB2D7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
794 F209CC Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
795 E7EC3B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 B5099E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
796 55191F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 270.00 90.00 10.06 3.05 0.00 FF8B08 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
797 3947B8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 90.00 90.00 4.57 3.05 0.00 47CE83 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
798 3B9E2E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 A168ED Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
799 C2156D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.67 1.67 1.67 180.00 180.00 1.83 0.91 0.00 3137C4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
800 5CA4CF Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 0.00 180.00 1.83 2.44 0.00 58A74A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
801 4AA9BC Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2.79 2.79 2.79 0.00 180.00 1.83 1.52 0.00 8A2F34 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
802 D1E495 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   9.48 9.48 9.48 90.00 180.00 5.18 1.83 0.00 18AD08 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
803 4180E7 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   18.39 18.39 18.39 90.00 0.00 10.06 1.83 0.00 52FA3B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
804 FLOOR 2 EXAM HALL 4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   36.79 36.79 36.79 0.00 90.00 36.79 1.00 0.00 FLOOR 2 EXAM HALL 4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
805 247FD8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 5EE606 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
806 2E6DF0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 270.00 90.00 4.57 3.05 0.00 D7DC8D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
807 14F382 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 90.00 90.00 10.06 3.05 0.00 247258 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
808 155BD6 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
809 ED8563 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 E0D6E9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
810 A1BBBE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 462370 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
811 E0C60A Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.67 1.67 1.67 270.00 180.00 0.91 1.83 0.00 6B171C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
812 772953 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   8.36 8.36 8.36 270.00 180.00 9.14 0.91 0.00 7B1677 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
813 15A02B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   8.36 8.36 8.36 0.00 180.00 0.91 9.14 0.00 B04E85 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
814 B9D6E3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   18.39 18.39 18.39 90.00 0.00 10.06 1.83 0.00 538FE6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
815 FLOOR 2 EXAM HALL 5_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   36.79 36.79 36.79 0.00 90.00 36.79 1.00 0.00 FLOOR 2 EXAM HALL 5_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
816 942718 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 7A8E3F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
817 D2C12A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 A49FCC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
818 5556EE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 270.00 90.00 10.06 3.05 0.00 685FFA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
819 C5EA55 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
820 D37566 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 90.00 90.00 4.57 3.05 0.00 6A2DCE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
821 E7055D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 70C0BF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
822 EC3BEA Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2.79 2.79 2.79 90.00 180.00 9.14 0.30 0.00 FDCEC5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
823 D2FA45 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.97 6.97 6.97 270.00 180.00 4.57 1.52 0.00 673317 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
824 98E1BD Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   8.36 8.36 8.36 270.00 180.00 5.49 1.52 0.00 83172E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
825 5F9E13 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.28 0.28 0.28 180.00 180.00 0.30 0.91 0.00 C605B5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
826 B4F89F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   18.39 18.39 18.39 270.00 0.00 10.06 1.83 0.00 F94215 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
827 FLOOR 2 EXAM HALL 6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   36.79 36.79 36.79 0.00 90.00 36.79 1.00 0.00 FLOOR 2 EXAM HALL 6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
828 8177BA Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
829 5E657E Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.57 0.43 4
830 4AD319 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 4CE123 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
831 E0C0A7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 8C4550 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
832 5B736E Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.85 5.85 5.85 180.00 180.00 2.74 2.13 0.00 DF9D5D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
833 F6E6D8 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.85 5.85 5.85 180.00 0.00 2.74 2.13 0.00 B840A7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
834 FLOOR 2 JANITOR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   11.71 11.71 11.71 0.00 90.00 11.71 1.00 0.00 FLOOR 2 JANITOR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
835 97BB21 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 0.00 90.00 2.44 3.05 0.00 93F6DE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
836 7620CF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 296861 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
837 680AA1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 1701A6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
838 A524F1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 988ACA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
839 4CDC86 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.43 7.43 7.43 0.00 180.00 2.44 3.05 0.00 34B3F0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
840 B352F7 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.43 7.43 7.43 0.00 0.00 2.44 3.05 0.00 96623F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
841 FLOOR 2 LOUNGE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   14.86 14.86 14.86 0.00 90.00 14.86 1.00 0.00 FLOOR 2 LOUNGE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
842 CBB2D7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 46F148 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
843 D0731B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 16E41D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
844 ECDEDB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 52D809 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
845 ED1D7F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 24E235 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
846 2805F0 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.43 7.43 7.43 90.00 180.00 3.05 2.44 0.00 CDA7F8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
847 5A7EAB Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.95 1.95 1.95 180.00 180.00 2.13 0.91 0.00 1891E7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
848 291561 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.55 4.55 4.55 0.00 180.00 2.13 2.13 0.00 CF6C6E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
849 4E1563 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.94 13.94 13.94 180.00 0.00 4.57 3.05 0.00 3B5B94 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
850 FLOOR 2 NURSE STATION 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   27.87 27.87 27.87 0.00 90.00 27.87 1.00 0.00 FLOOR 2 NURSE STATION 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
851 A49FCC Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 D2C12A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
852 5DBD9D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 B94E9A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
853 491317 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 211EA4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
854 462370 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 A1BBBE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
855 9EADD8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.71 11.71 11.71 0.00 180.00 5.49 2.13 0.00 1E6611 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
856 DE8843 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 180.00 180.00 5.49 0.91 0.00 86C171 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
857 C45BF3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   16.72 16.72 16.72 270.00 0.00 3.05 5.49 0.00 C27BD7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
858 FLOOR 2 NURSE STATION 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   33.45 33.45 33.45 0.00 90.00 33.45 1.00 0.00 FLOOR 2 NURSE STATION 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
859 AAF377 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   37.16 37.16 37.16 270.00 90.00 12.19 3.05 0.00 DFA16C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
860 CE4555 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 9AC2E9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
861 A8A4FA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 97B688 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
862 4B1439 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   28.24 37.16 28.24 90.00 90.00 12.19 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
863 EB042B Window 4B1439 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
864 4C1F71 Window 4B1439 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
865 D23C8B Window 4B1439 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
866 B4E4BE Window 4B1439 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
867 352740 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   19.51 19.51 19.51 0.00 180.00 4.27 4.57 0.00 406D70 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
868 D3CF55 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   18.21 18.21 18.21 0.00 180.00 4.27 4.27 0.00 1875B3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
869 64A2F7 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   14.31 14.31 14.31 180.00 180.00 4.27 3.35 0.00 FFE052 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
870 D1A180 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   10.41 10.41 10.41 0.00 0.00 4.27 2.44 0.00 8E83C6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
871 9BB582 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   41.62 41.62 41.62 180.00 0.00 4.27 9.75 0.00 8480E5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
872 FLOOR 2 OFFICE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   104.05 104.05 104.05 0.00 90.00 104.05 1.00 0.00 FLOOR 2 OFFICE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
873 DFA16C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   37.16 37.16 37.16 90.00 90.00 12.19 3.05 0.00 AAF377 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
874 2884D1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 1EB5B1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
875 CC4EB4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 B184C1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
876 B2F07D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 6EE166 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
877 AF86E1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 90.00 90.00 2.74 3.05 0.00 4F0CD7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
878 571934 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   23.23 23.23 23.23 90.00 90.00 7.62 3.05 0.00 AC956A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
879 67A7F3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 8E1DCD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
880 24E235 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 ED1D7F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
881 AB568E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 830326 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
882 577A10 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 772842 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
883 988ACA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 A524F1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
884 F5AF76 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 270.00 90.00 5.49 3.05 0.00 24DA9F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
885 4EDE0A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 2740BD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
886 874DF8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.13 6.13 6.13 270.00 180.00 3.35 1.83 0.00 611A3F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
887 8C822C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.80 7.80 7.80 270.00 180.00 4.27 1.83 0.00 7008C0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
888 B44BE3 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 270.00 180.00 7.32 1.83 0.00 726F67 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
889 4F2F27 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.90 3.90 3.90 180.00 180.00 1.83 2.13 0.00 5F697A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
890 909DB9 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   10.03 10.03 10.03 0.00 180.00 1.83 5.49 0.00 7DB101 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
891 30A09C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   8.92 8.92 8.92 90.00 0.00 4.88 1.83 0.00 F17575 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
892 BFEF28 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   27.87 27.87 27.87 90.00 0.00 15.24 1.83 0.00 2E74E6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
893 C588CC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   4.46 4.46 4.46 0.00 0.00 1.83 2.44 0.00 339B46 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
894 FLOOR 2 OFFICE HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   82.50 82.50 82.50 0.00 90.00 82.50 1.00 0.00 FLOOR 2 OFFICE HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
895 23C13E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.81 41.81 41.81 0.00 90.00 13.72 3.05 0.00 EAD1EA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
896 3DE7A6 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 17258E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
897 4ABC66 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   20.62 30.66 20.62 180.00 90.00 10.06 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.57 0.43 4
898 EEF55D Window 4ABC66 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 6.69 6.69 6.69 180.00 90.00 3.66 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.54 0.46 4
899 E55A57 Window 4ABC66 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 3.34 3.34 3.34 180.00 90.00 2.74 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.60 0.40 4
900 5B04CF Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   8.18 14.86 8.18 270.00 90.00 4.88 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
901 93D018 Window 5B04CF Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 6.69 6.69 6.69 270.00 90.00 3.66 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
902 FCDEAC Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 99468F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
903 AB4E10 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 CA9485 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
904 E7BF7F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 90.00 90.00 5.49 3.05 0.00 B04C98 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
905 FA00FE Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.57 5.57 5.57 90.00 180.00 0.91 6.10 0.00 690A91 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
906 14CDC6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   28.99 28.99 28.99 270.00 180.00 7.32 3.96 0.00 700E69 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
907 39BFFB Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   39.02 39.02 39.02 180.00 180.00 6.10 6.40 0.00 4783F2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
908 167608 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   17.84 17.84 17.84 270.00 180.00 4.88 3.66 0.00 78FEE8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
909 C39FCC Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   91.42 91.42 91.42 180.00 0.00 9.56 9.56 0.00 9D1FA7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
910 FLOOR 2 RECEPTION_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   182.83 182.83 182.83 0.00 90.00 182.83 1.00 0.00 FLOOR 2 RECEPTION_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
911 CA9485 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 AB4E10 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
912 2740BD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 4EDE0A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
913 F0AF69 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 B76374 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
914 8D1BC4 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.70 0.30 4
915 9CE650 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 DF91E0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
916 EEECA3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 ADD799 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
917 EE34A3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 815D63 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
918 CFAD9D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 180.00 90.00 7.32 3.05 0.00 DFA4B1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
919 25F524 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 BC25F3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
920 D79C57 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 8A5790 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
921 93F6DE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 97BB21 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
922 8AA0B7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   46.45 46.45 46.45 0.00 90.00 15.24 3.05 0.00 E74038 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
923 1D6CD8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.65 17.65 17.65 0.00 90.00 5.79 3.05 0.00 9FBDA3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
924 427B0D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 E63515 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
925 A72F04 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 10E44F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
926 C51FD6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.90 3.90 3.90 270.00 180.00 1.83 2.13 0.00 513564 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
927 3110A1 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 270.00 180.00 1.83 2.44 0.00 E63CF4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
928 F81393 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.25 7.25 7.25 0.00 180.00 3.96 1.83 0.00 C0A312 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
929 4FA380 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.90 3.90 3.90 270.00 180.00 1.83 2.13 0.00 AA1F5C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
930 2FE383 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 270.00 180.00 1.83 2.74 0.00 442699 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
931 3F961C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 270.00 180.00 1.83 2.74 0.00 AF27F8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
932 4B590B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 270.00 180.00 1.83 2.74 0.00 7274F6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
933 20B940 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 90.00 180.00 1.83 2.44 0.00 340FB5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
934 21FC9D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 90.00 180.00 1.83 2.74 0.00 363652 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
935 EB4979 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2.79 2.79 2.79 270.00 180.00 0.61 4.57 0.00 9EBF3E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
936 A5FA3B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.57 5.57 5.57 90.00 180.00 1.22 4.57 0.00 2E1FB7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
937 7A3F36 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.90 3.90 3.90 90.00 0.00 1.83 2.13 0.00 6F1456 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
938 4DAEA4 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   23.41 23.41 23.41 180.00 0.00 12.80 1.83 0.00 236CCE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
939 B52A5D Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   17.28 17.28 17.28 0.00 0.00 9.45 1.83 0.00 317B1B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
940 2C7827 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.80 7.80 7.80 180.00 0.00 4.27 1.83 0.00 496A6C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
941 FLOOR 2 RECEPTION HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   104.79 104.79 104.79 0.00 90.00 104.79 1.00 0.00 FLOOR 2 RECEPTION HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
942 2D0A7F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 90.00 90.00 5.49 3.05 0.00 87BFF8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
943 E63515 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 427B0D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
944 B04C98 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 270.00 90.00 5.49 3.05 0.00 E7BF7F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
945 50DB3D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 450AA9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
946 115AA8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.55 4.55 4.55 0.00 180.00 2.13 2.13 0.00 68AAF3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
947 CFB630 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.15 7.15 7.15 180.00 180.00 2.13 3.35 0.00 58F893 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
948 E9C76F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.71 11.71 11.71 180.00 0.00 2.13 5.49 0.00 CDCFEE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
949 FLOOR 2 RECEPTION TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   23.41 23.41 23.41 0.00 90.00 23.41 1.00 0.00 FLOOR 2 RECEPTION TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
950 9C568B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 9036B9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
951 B76374 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 F0AF69 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
952 24DA9F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 90.00 90.00 5.49 3.05 0.00 F5AF76 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
953 CADDAF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 270.00 90.00 5.49 3.05 0.00 762874 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
954 10830D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 90.00 180.00 5.49 2.44 0.00 4469CD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
955 EF47B0 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.50 6.50 6.50 180.00 180.00 3.05 2.13 0.00 8E9267 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
956 C3DB37 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   10.22 10.22 10.22 0.00 180.00 3.05 3.35 0.00 C1737B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
957 F631E4 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   10.03 10.03 10.03 0.00 0.00 5.49 1.83 0.00 137CDB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
958 93EF1F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   20.07 20.07 20.07 180.00 0.00 5.49 3.66 0.00 DF5076 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
959 FLOOR 2 SCHEDULING 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   60.20 60.20 60.20 0.00 90.00 60.20 1.00 0.00 FLOOR 2 SCHEDULING 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
960 9FBDA3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.65 17.65 17.65 180.00 90.00 5.79 3.05 0.00 1D6CD8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
961 87BFF8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 270.00 90.00 5.49 3.05 0.00 2D0A7F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
962 DB7F62 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 90.00 90.00 5.49 3.05 0.00 637F6F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
963 969F22 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.65 17.65 17.65 0.00 90.00 5.79 3.05 0.00 29E445 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
964 795751 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.34 3.34 3.34 90.00 180.00 5.49 0.61 0.00 AFFD01 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
965 6A14D8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   9.20 9.20 9.20 180.00 180.00 2.74 3.35 0.00 3C43B2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
966 E3963E Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.85 5.85 5.85 270.00 180.00 2.13 2.74 0.00 DE014E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
967 630683 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 270.00 180.00 5.49 2.44 0.00 343C52 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
968 4EB51A Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   31.77 31.77 31.77 90.00 0.00 5.49 5.79 0.00 66FE82 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
969 FLOOR 2 SCHEDULING 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   63.55 63.55 63.55 0.00 90.00 63.55 1.00 0.00 FLOOR 2 SCHEDULING 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
970 390BCF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 C08963 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
971 DE64CC Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 2DB420 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
972 F6E717 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 D88779 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
973 58AD84 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 F6D879 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
974 A3E3D6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.20 5.20 5.20 270.00 180.00 2.44 2.13 0.00 DDBA1E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
975 ED1C1D Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.20 5.20 5.20 270.00 0.00 2.44 2.13 0.00 A56694 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
976 FLOOR 2 STORAGE 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.41 10.41 10.41 0.00 90.00 10.41 1.00 0.00 FLOOR 2 STORAGE 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
977 A168ED Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 3B9E2E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
978 ED650B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 F29458 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
979 8E1DCD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 67A7F3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
980 16E41D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 D0731B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
981 1C7FB1 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.74 0.74 0.74 0.00 180.00 2.44 0.30 0.00 5136E3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
982 4B217A Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.20 5.20 5.20 90.00 180.00 2.13 2.44 0.00 370DB2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
983 A3F683 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.20 5.20 5.20 0.00 180.00 2.13 2.44 0.00 69AE66 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
984 430C7E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.15 11.15 11.15 270.00 0.00 2.44 4.57 0.00 B29215 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
985 FLOOR 2 STORAGE 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   22.30 22.30 22.30 0.00 90.00 22.30 1.00 0.00 FLOOR 2 STORAGE 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
986 70C0BF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 E7055D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
987 211EA4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 491317 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
988 E0D6E9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 ED8563 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
989 BADB96 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 7A03ED Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
990 1E3410 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 90.00 180.00 2.44 5.49 0.00 C1F15F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
991 695D6E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   13.38 13.38 13.38 90.00 0.00 2.44 5.49 0.00 45A523 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
992 FLOOR 2 STORAGE 3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   26.76 26.76 26.76 0.00 90.00 26.76 1.00 0.00 FLOOR 2 STORAGE 3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
993 97B688 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 A8A4FA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
994 290DF3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 83B6E3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
995 4B55FA Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   6.13 8.36 6.13 90.00 90.00 2.74 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
996 DD9F5D Window 4B55FA Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
997 4F0CD7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 270.00 90.00 2.74 3.05 0.00 AF86E1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
998 4D50C0 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.71 11.71 11.71 270.00 180.00 2.74 4.27 0.00 368A44 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
999 703D3E Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   11.71 11.71 11.71 270.00 0.00 2.74 4.27 0.00 F6DDE6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1000 FLOOR 2 UTILITY_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   23.41 23.41 23.41 0.00 90.00 23.41 1.00 0.00 FLOOR 2 UTILITY_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1001 9C3A6A Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   14.86 20.44 14.86 0.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.57 0.43 4
1002 15B02B Window 9C3A6A Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
1003 820282 Window 9C3A6A Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.59 0.41 4
1004 5C7E1E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 90.00 90.00 10.06 3.05 0.00 35051E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1005 B5E37D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 0.00 90.00 0.61 3.05 0.00 9969B3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1006 8D1659 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 270.00 90.00 6.10 3.05 0.00 BEDECA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1007 E88E01 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   48.31 48.31 48.31 180.00 90.00 15.85 3.05 0.00 738F37 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1008 4CE123 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 4AD319 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1009 E55935 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 0.00 90.00 7.32 3.05 0.00 F41621 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1010 C52EE0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   3.72 3.72 3.72 0.00 90.00 1.22 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.69 0.31 4
1011 9AB0BF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 F22E15 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1012 1A8E2A Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2.60 2.60 2.60 270.00 180.00 2.13 1.22 0.00 827528 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1013 E21951 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 180.00 180.00 1.83 2.74 0.00 388F10 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1014 517DFC Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   33.26 33.26 33.26 270.00 180.00 5.77 5.77 0.00 BFB8E1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 10
1015 CEC6B4 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   15.61 15.61 15.61 0.00 180.00 6.40 2.44 0.00 290CAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1016 1A95D5 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.66 13.66 13.66 270.00 180.00 3.70 3.70 0.00 5CB500 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 8
1017 5724CC Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.57 5.57 5.57 180.00 180.00 6.10 0.91 0.00 B7E9B3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1018 7FA5FF Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 270.00 180.00 5.49 2.44 0.00 9114B7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1019 E43750 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   40.88 40.88 40.88 0.00 180.00 6.10 6.71 0.00 803791 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1020 E9C9E1 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2.79 2.79 2.79 0.00 180.00 0.61 4.57 0.00 79376C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1021 CE626A Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   20.07 20.07 20.07 270.00 180.00 5.49 3.66 0.00 28F0DE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1022 541C9C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.18 4.18 4.18 270.00 180.00 1.52 2.74 0.00 5DACB5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1023 F77E4B Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   34.37 34.37 34.37 90.00 0.00 5.86 5.86 0.00 D6F20A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
1024 287E3B Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   122.63 122.63 122.63 270.00 0.00 10.06 12.19 0.00 535D54 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1025 FLOOR 2 WORK_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   259.39 259.39 259.39 0.00 90.00 259.39 1.00 0.00 FLOOR 2 WORK_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1026 830326 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 AB568E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1027 EAD1EA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.81 41.81 41.81 180.00 90.00 13.72 3.05 0.00 23C13E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1028 1C33AD Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.65 0.35 4
1029 52D809 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ECDEDB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1030 450AA9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 50DB3D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1031 29E445 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.65 17.65 17.65 180.00 90.00 5.79 3.05 0.00 969F22 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1032 B0FF3A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   46.45 46.45 46.45 180.00 90.00 15.24 3.05 0.00 34B8D8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1033 9036B9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 9C568B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1034 5EE606 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 247FD8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1035 3FBBC8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 0.00 90.00 7.32 3.05 0.00 F976A9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1036 B5099E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 E7EC3B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1037 7A8E3F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 942718 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1038 32BAA7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 B51929 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1039 738F37 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   48.31 48.31 48.31 0.00 90.00 15.85 3.05 0.00 E88E01 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1040 B94E9A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 5DBD9D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1041 83658D Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.92 4.92 4.92 270.00 180.00 2.22 2.22 0.00 A02892 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
1042 CAC621 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.69 6.69 6.69 270.00 180.00 1.83 3.66 0.00 D647E0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1043 E90253 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.15 11.15 11.15 270.00 180.00 1.83 6.10 0.00 D60B94 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1044 FD4C82 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.21 1.21 1.21 180.00 180.00 3.96 0.30 0.00 CABD0E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1045 F5C927 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   9.75 9.75 9.75 0.00 180.00 6.40 1.52 0.00 B754EC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1046 362FF8 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 270.00 180.00 1.83 2.44 0.00 D6D2A5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1047 21F419 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.65 0.65 0.65 180.00 180.00 2.13 0.30 0.00 4E5019 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1048 283EC6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 180.00 180.00 2.44 1.83 0.00 F62393 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1049 C5B569 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   0.84 0.84 0.84 180.00 180.00 2.74 0.30 0.00 2CB843 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1050 D29B01 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.07 3.07 3.07 180.00 180.00 10.06 0.30 0.00 D44BF1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1051 FFE9D0 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   28.80 28.80 28.80 270.00 180.00 1.52 18.90 0.00 BD75DE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1052 7A8C4C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   1.49 1.49 1.49 180.00 180.00 4.88 0.30 0.00 709E99 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1053 957242 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   77.48 77.48 77.48 0.00 0.00 42.37 1.83 0.00 14A82B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1054 FLOOR 2 WORK HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   154.96 154.96 154.96 0.00 90.00 154.96 1.00 0.00 FLOOR 2 WORK HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1055 F22E15 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 9AB0BF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1056 49DA28 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 BDE9D9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1057 8C4550 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 E0C0A7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1058 6CC177 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1059 9969B3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 180.00 90.00 0.61 3.05 0.00 B5E37D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1060 4C4C25 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 180.00 180.00 2.74 1.83 0.00 9BB388 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1061 FC3B6D Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   5.02 5.02 5.02 90.00 0.00 1.83 2.74 0.00 F07866 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1062 FLOOR 2 WORK TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 2 WORK TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1063 34B8D8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   46.45 46.45 46.45 0.00 90.00 15.24 3.05 0.00 B0FF3A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1064 E74038 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   46.45 46.45 46.45 180.00 90.00 15.24 3.05 0.00 8AA0B7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1065 762874 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 90.00 90.00 5.49 3.05 0.00 CADDAF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1066 637F6F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 270.00 90.00 5.49 3.05 0.00 DB7F62 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1067 C6DCD1 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.71 11.71 11.71 270.00 180.00 5.49 2.13 0.00 F665B1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1068 1BDF58 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   18.39 18.39 18.39 270.00 180.00 5.49 3.35 0.00 661D88 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1069 15A915 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.85 5.85 5.85 180.00 180.00 2.74 2.13 0.00 88D2F8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1070 1CC550 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.85 5.85 5.85 180.00 180.00 2.74 2.13 0.00 D1AFC9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1071 55622A Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 180.00 180.00 2.74 1.83 0.00 D21333 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1072 5D03DA Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.85 5.85 5.85 180.00 180.00 2.74 2.13 0.00 A7115C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1073 AE5078 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.18 4.18 4.18 270.00 180.00 1.52 2.74 0.00 E2AB17 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1074 774CCD Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.25 3.25 3.25 180.00 180.00 1.52 2.13 0.00 BB097B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1075 F6FE66 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   23.50 23.50 23.50 0.00 180.00 7.01 3.35 0.00 5C05FF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1076 1DCC9F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   38.46 38.46 38.46 90.00 0.00 5.49 7.01 0.00 AE769E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1077 47890C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3.90 3.90 3.90 0.00 0.00 2.13 1.83 0.00 9AC2BE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1078 F7E82F Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   7.80 7.80 7.80 180.00 0.00 2.13 3.66 0.00 484FB1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1079 7FDC1A Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   23.41 23.41 23.41 90.00 0.00 5.49 4.27 0.00 25A972 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1080 F02E9C Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   10.03 10.03 10.03 270.00 0.00 5.49 1.83 0.00 628387 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
1081 FLOOR 2 X-RAY_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   167.23 167.23 167.23 0.00 90.00 167.23 1.00 0.00 FLOOR 2 X-RAY_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1082 137A14 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 CD21EC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1083 F2515C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 AAD404 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1084 71A3C4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 EF4AD1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1085 46292D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 301CE0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1086 9AC2BE Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.90 3.90 3.90 270.00 180.00 1.83 2.13 0.00 47890C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1087 FLOOR 3 DRESSING ROOM ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   3.90 3.90 3.90 270.00 0.00 1.83 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1088 FLOOR 3 DRESSING ROOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7.80 7.80 7.80 0.00 90.00 7.80 1.00 0.00 FLOOR 3 DRESSING ROOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1089 5EAFB3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 DF47AC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1090 E0CB0D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 270.00 90.00 6.10 3.05 0.00 F9DFA4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1091 FB63A7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 0.00 90.00 0.61 3.05 0.00 D0C6E8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1092 79D0A5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 8646EF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1093 212961 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 90.00 90.00 10.06 3.05 0.00 B972D4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1094 C1AD55 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 C4A89B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1095 B75832 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 8316C5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1096 F7D24D Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   3.72 3.72 3.72 0.00 90.00 1.22 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.65 0.35 4
1097 D6F20A Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   34.37 34.37 34.37 270.00 180.00 5.86 5.86 0.00 F77E4B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
1098 FLOOR 3 ELEVATOR HALL ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   34.37 34.37 34.37 0.00 0.00 5.86 5.86 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
1099 FLOOR 3 ELEVATOR HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   68.75 68.75 68.75 0.00 90.00 68.75 1.00 0.00 FLOOR 3 ELEVATOR HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1100 C3FB92 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 55BD05 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1101 AAD404 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 F2515C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1102 2272E0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 270.00 90.00 5.49 3.05 0.00 D6005B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1103 E13FC4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 D75504 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1104 506DC0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 EA4A9E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1105 628387 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   10.03 10.03 10.03 270.00 180.00 5.49 1.83 0.00 F02E9C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1106 FLOOR 3 HUMID ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   10.03 10.03 10.03 270.00 0.00 5.49 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1107 FLOOR 3 HUMID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   20.07 20.07 20.07 0.00 90.00 20.07 1.00 0.00 FLOOR 3 HUMID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1108 1D53D9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 180.00 90.00 2.74 3.05 0.00 460DA4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1109 FC22D1 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.54 0.46 4
1110 DD2E2D Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1111 C4A89B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 C1AD55 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1112 B840A7 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.85 5.85 5.85 0.00 180.00 2.74 2.13 0.00 F6E6D8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1113 FLOOR 3 JANITOR ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   5.85 5.85 5.85 0.00 0.00 2.74 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1114 FLOOR 3 JANITOR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   11.71 11.71 11.71 0.00 90.00 11.71 1.00 0.00 FLOOR 3 JANITOR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1115 C86932 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 812B32 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1116 B1856A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 9AB92B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1117 AEA170 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 1F37D7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1118 82303C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 A5FC87 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1119 D10EC7 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.15 11.15 11.15 0.00 180.00 3.66 3.05 0.00 245972 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1120 FLOOR 3 LOCKER ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   11.15 11.15 11.15 0.00 0.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1121 FLOOR 3 LOCKER_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   22.30 22.30 22.30 0.00 90.00 22.30 1.00 0.00 FLOOR 3 LOCKER_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1122 AA26DE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 180.00 90.00 7.01 3.05 0.00 CC8990 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1123 68A2D7 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   15.79 21.37 15.79 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1124 9BA05A Window 68A2D7 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1125 C639E8 Window 68A2D7 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1126 824F52 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.15 24.15 24.15 90.00 90.00 7.92 3.05 0.00 44775D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1127 D2E9BA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 EEFDE3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1128 D197DA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 AC05CF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1129 7C7BE2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 270.00 90.00 4.88 3.05 0.00 E0FD95 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1130 812B32 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 270.00 90.00 3.05 3.05 0.00 C86932 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1131 3B5B94 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.94 13.94 13.94 180.00 180.00 4.57 3.05 0.00 4E1563 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1132 60F383 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.13 6.13 6.13 90.00 180.00 10.06 0.61 0.00 567037 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1133 F7BE2F Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   20.90 20.90 20.90 90.00 180.00 4.57 4.57 0.00 917AB5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1134 B29215 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.15 11.15 11.15 0.00 180.00 4.57 2.44 0.00 430C7E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1135 52FA3B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   18.39 18.39 18.39 90.00 180.00 10.06 1.83 0.00 4180E7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1136 FLOOR 3 LOUNGE ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   70.51 70.51 70.51 270.00 0.00 10.06 7.01 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1137 FLOOR 3 LOUNGE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   141.03 141.03 141.03 0.00 90.00 141.03 1.00 0.00 FLOOR 3 LOUNGE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1138 6D960C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 270.00 90.00 4.88 3.05 0.00 CBFB94 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1139 9AB92B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 B1856A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1140 CE3FEF Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   6.97 11.15 6.97 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1141 A2790A Window CE3FEF Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 4.18 4.18 4.18 0.00 90.00 2.74 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1142 E0FD95 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 90.00 90.00 4.88 3.05 0.00 7C7BE2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1143 B46F2C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   17.84 17.84 17.84 0.00 180.00 3.66 4.88 0.00 6B3E65 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1144 FLOOR 3 LOUNGE TOILET ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   17.84 17.84 17.84 0.00 0.00 3.66 4.88 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1145 FLOOR 3 LOUNGE TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   35.67 35.67 35.67 0.00 90.00 35.67 1.00 0.00 FLOOR 3 LOUNGE TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1146 6F0E5D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 60F634 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1147 D67C59 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   23.23 23.23 23.23 270.00 90.00 7.62 3.05 0.00 98A52C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1148 6C68C2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 3613B7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1149 CE618F Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   17.28 23.23 17.28 90.00 90.00 7.62 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
1150 79FCEE Window CE618F Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.97 2.97 2.97 90.00 90.00 2.44 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1151 EDE617 Window CE618F Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.97 2.97 2.97 90.00 90.00 2.44 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
1152 1DC177 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.52 32.52 32.52 0.00 180.00 4.27 7.62 0.00 31B3DF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1153 FLOOR 3 MECHANICAL ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   32.52 32.52 32.52 0.00 0.00 4.27 7.62 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1154 FLOOR 3 MECHANICAL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   65.03 65.03 65.03 0.00 90.00 65.03 1.00 0.00 FLOOR 3 MECHANICAL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1155 A11DA8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   23.23 23.23 23.23 90.00 90.00 7.62 3.05 0.00 4C6DBF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1156 BC2C22 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 D68874 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1157 44775D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.15 24.15 24.15 270.00 90.00 7.92 3.05 0.00 824F52 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1158 CDD69A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 5C690E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1159 F5E7FE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CF2803 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1160 4BF787 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 869ED5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1161 98A52C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   23.23 23.23 23.23 90.00 90.00 7.62 3.05 0.00 D67C59 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1162 6310E5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 6EC372 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1163 2E74E6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   27.87 27.87 27.87 90.00 180.00 15.24 1.83 0.00 BFEF28 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1164 FLOOR 3 MECHANICAL HALL ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   27.87 27.87 27.87 0.00 0.00 1.83 15.24 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1165 FLOOR 3 MECHANICAL HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   55.74 55.74 55.74 0.00 90.00 55.74 1.00 0.00 FLOOR 3 MECHANICAL HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1166 5FDFAE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   85.47 85.47 85.47 180.00 90.00 28.04 3.05 0.00 D7E6B2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1167 C7B7AA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 FE5F03 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1168 B972D4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   30.66 30.66 30.66 270.00 90.00 10.06 3.05 0.00 212961 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1169 5ADC59 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   49.24 68.75 49.24 0.00 90.00 22.56 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
1170 C61F0D Window 5ADC59 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1171 7248C5 Window 5ADC59 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.56 0.44 4
1172 29FA28 Window 5ADC59 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1173 F0B23F Window 5ADC59 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1174 EEC10E Window 5ADC59 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1175 944FCE Window 5ADC59 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
1176 C41399 Window 5ADC59 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.79 2.79 2.79 0.00 90.00 1.83 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1177 7DCAF1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 7C0F83 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1178 CBFB94 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 90.00 90.00 4.88 3.05 0.00 6D960C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1179 A5FC87 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   9.29 9.29 9.29 90.00 90.00 3.05 3.05 0.00 82303C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1180 A72B2F Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   30.66 30.66 30.66 90.00 180.00 10.06 3.05 0.00 F0D8EE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1181 538FE6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   18.39 18.39 18.39 90.00 180.00 10.06 1.83 0.00 B9D6E3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1182 8A695C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   25.08 25.08 25.08 0.00 180.00 5.49 4.57 0.00 DA760E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1183 45A523 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.38 13.38 13.38 0.00 180.00 5.49 2.44 0.00 695D6E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1184 F94215 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   18.39 18.39 18.39 0.00 180.00 1.83 10.06 0.00 B4F89F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1185 C27BD7 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   16.72 16.72 16.72 90.00 180.00 3.05 5.49 0.00 C45BF3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1186 AE8664 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.79 36.79 36.79 90.00 180.00 10.06 3.66 0.00 5D2769 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1187 535D54 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   122.63 122.63 122.63 0.00 180.00 12.19 10.06 0.00 287E3B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1188 FLOOR 3 OFFICE ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   282.05 282.05 282.05 180.00 0.00 28.04 10.06 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1189 FLOOR 3 OFFICE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   564.11 564.11 564.11 0.00 90.00 564.11 1.00 0.00 FLOOR 3 OFFICE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1190 CC8990 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   21.37 21.37 21.37 0.00 90.00 7.01 3.05 0.00 AA26DE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1191 D4F411 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.62 0.38 4
1192 2F3F2A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   48.31 48.31 48.31 180.00 90.00 15.85 3.05 0.00 855B07 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1193 869ED5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 4BF787 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1194 D75504 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 E13FC4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1195 E80026 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 D13E00 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1196 A03B2E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 BF7411 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1197 133349 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 111907 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1198 7DCD8A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 C9F74B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1199 D7E6B2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   85.47 85.47 85.47 0.00 90.00 28.04 3.05 0.00 5FDFAE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1200 8646EF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 79D0A5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1201 840387 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   39.02 39.02 39.02 180.00 90.00 12.80 3.05 0.00 4CCA8D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1202 14A82B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   77.48 77.48 77.48 270.00 180.00 1.83 42.37 0.00 957242 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1203 FLOOR 3 OFFICE HALL ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   77.48 77.48 77.48 270.00 0.00 1.83 42.37 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1204 FLOOR 3 OFFICE HALL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   154.96 154.96 154.96 0.00 90.00 154.96 1.00 0.00 FLOOR 3 OFFICE HALL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1205 460DA4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.36 8.36 8.36 0.00 90.00 2.74 3.05 0.00 1D53D9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1206 8316C5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 B75832 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1207 D5E94D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 9BA592 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1208 B35AD6 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1209 D0C6E8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   1.86 1.86 1.86 180.00 90.00 0.61 3.05 0.00 FB63A7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1210 F07866 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.02 5.02 5.02 270.00 180.00 1.83 2.74 0.00 FC3B6D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1211 FLOOR 3 OFFICE TOILET ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   5.02 5.02 5.02 270.00 0.00 1.83 2.74 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1212 FLOOR 3 OFFICE TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   10.03 10.03 10.03 0.00 90.00 10.03 1.00 0.00 FLOOR 3 OFFICE TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1213 D22917 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   11.89 18.58 11.89 90.00 90.00 6.10 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1214 95BA33 Window D22917 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 3.34 3.34 3.34 90.00 90.00 1.83 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1215 F27282 Window D22917 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 3.34 3.34 3.34 90.00 90.00 1.83 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1216 4497EF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 270.00 90.00 6.10 3.05 0.00 C050FD Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1217 C1BC97 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   38.09 60.39 38.09 180.00 90.00 19.81 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1218 3DB407 Window C1BC97 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 5.57 5.57 5.57 180.00 90.00 3.05 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1219 3DADE2 Window C1BC97 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 5.57 5.57 5.57 180.00 90.00 3.05 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1220 DF3E2C Window C1BC97 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 5.57 5.57 5.57 180.00 90.00 3.05 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1221 5031C8 Window C1BC97 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 5.57 5.57 5.57 180.00 90.00 3.05 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1222 F3F6EA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 E7A265 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1223 BCAAD1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   34.37 34.37 34.37 0.00 90.00 11.28 3.05 0.00 958E3F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1224 E5720F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 C78153 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1225 8E83C6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   10.41 10.41 10.41 90.00 180.00 2.44 4.27 0.00 D1A180 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1226 D14D65 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   31.22 31.22 31.22 90.00 180.00 3.66 8.53 0.00 240A7C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1227 CDCA72 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.95 5.95 5.95 90.00 180.00 2.44 2.44 0.00 7149EA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1228 339B46 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   4.46 4.46 4.46 90.00 180.00 2.44 1.83 0.00 C588CC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1229 7F8407 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   44.59 44.59 44.59 270.00 180.00 6.10 7.32 0.00 D74115 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1230 F69079 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.80 7.80 7.80 90.00 180.00 3.66 2.13 0.00 C0697F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1231 A56694 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.20 5.20 5.20 90.00 180.00 2.44 2.13 0.00 ED1C1D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1232 3C8351 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.15 11.15 11.15 90.00 180.00 6.10 1.83 0.00 6C1891 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1233 FLOOR 3 PHYICAL THERAPY 1 ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   120.77 120.77 120.77 180.00 0.00 19.81 6.10 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1234 FLOOR 3 PHYSICAL THERAPY 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   241.55 241.55 241.55 0.00 90.00 241.55 1.00 0.00 FLOOR 3 PHYSICAL THERAPY 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1235 958E3F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   34.37 34.37 34.37 180.00 90.00 11.28 3.05 0.00 BCAAD1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1236 27D999 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 270.00 90.00 4.88 3.05 0.00 2451B7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1237 55BD05 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 C3FB92 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1238 8BCB23 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 90.00 90.00 4.88 3.05 0.00 EFFB3B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1239 5C690E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 0.00 90.00 1.83 3.05 0.00 CDD69A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1240 E49C43 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 D4C22E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1241 EF4AD1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 71A3C4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1242 8FB568 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   9.29 9.29 9.29 180.00 180.00 3.05 3.05 0.00 5065F0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1243 C271D9 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   5.57 5.57 5.57 180.00 180.00 1.83 3.05 0.00 D4A2A4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1244 1EE332 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   6.50 6.50 6.50 180.00 180.00 2.13 3.05 0.00 E1B973 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1245 96623F Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.43 7.43 7.43 180.00 180.00 2.44 3.05 0.00 B352F7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1246 F17575 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   8.92 8.92 8.92 180.00 180.00 1.83 4.88 0.00 30A09C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1247 317B1B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   17.28 17.28 17.28 0.00 180.00 9.45 1.83 0.00 B52A5D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1248 FLOOR 3 PHYSICAL THERAPY 2 ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   55.00 55.00 55.00 90.00 0.00 4.88 11.28 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1249 FLOOR 3 PHYSICAL THERAPY 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   110.00 110.00 110.00 0.00 90.00 110.00 1.00 0.00 FLOOR 3 PHYSICAL THERAPY 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1250 44D36C Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 2BC70D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1251 CD21EC Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 180.00 90.00 2.13 3.05 0.00 137A14 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1252 BF7411 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 A03B2E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1253 EA4A9E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 506DC0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1254 484FB1 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.80 7.80 7.80 90.00 180.00 3.66 2.13 0.00 F7E82F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1255 FLOOR 3 PHYSICAL THERAPY TOILET ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   7.80 7.80 7.80 90.00 0.00 3.66 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1256 FLOOR 3 PHYSICAL THERAPY TOILET_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   15.61 15.61 15.61 0.00 90.00 15.61 1.00 0.00 FLOOR 3 PHYSICAL THERAPY TOILET_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1257 D4C22E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 E49C43 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1258 6EC372 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 90.00 90.00 1.83 3.05 0.00 6310E5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1259 301CE0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 270.00 90.00 1.83 3.05 0.00 46292D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1260 89A685 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 180143 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1261 137CDB Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   10.03 10.03 10.03 180.00 180.00 5.49 1.83 0.00 F631E4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1262 FLOOR 3 STORAGE 1 ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   10.03 10.03 10.03 180.00 0.00 5.49 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1263 FLOOR 3 STORAGE 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   20.07 20.07 20.07 0.00 90.00 20.07 1.00 0.00 FLOOR 3 STORAGE 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1264 FE5F03 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 C7B7AA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1265 1F37D7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 AEA170 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1266 AC05CF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 90.00 90.00 2.13 3.05 0.00 D197DA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1267 C9F74B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 7DCD8A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1268 63B825 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.80 7.80 7.80 180.00 180.00 3.66 2.13 0.00 F17DF7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1269 FLOOR 3 STORAGE 2 ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   7.80 7.80 7.80 180.00 0.00 3.66 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1270 FLOOR 3 STORAGE 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   15.61 15.61 15.61 0.00 90.00 15.61 1.00 0.00 FLOOR 3 STORAGE 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1271 C78153 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 E5720F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1272 D13E00 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 E80026 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1273 2451B7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 90.00 90.00 4.88 3.05 0.00 27D999 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1274 624E8A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 2336C8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1275 D6005B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 90.00 90.00 5.49 3.05 0.00 2272E0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1276 2B4713 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   13.01 13.01 13.01 180.00 180.00 4.27 3.05 0.00 3AEAAB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1277 25A972 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   23.41 23.41 23.41 0.00 180.00 4.27 5.49 0.00 7FDC1A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1278 496A6C Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   7.80 7.80 7.80 270.00 180.00 1.83 4.27 0.00 2C7827 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1279 FLOOR 3 TREATMENT ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   44.22 44.22 44.22 90.00 0.00 10.36 4.27 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1280 FLOOR 3 TREATMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   88.44 88.44 88.44 0.00 90.00 88.44 1.00 0.00 FLOOR 3 TREATMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1281 C050FD Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 90.00 90.00 6.10 3.05 0.00 4497EF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1282 8DA7DB Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   23.41 39.02 23.41 180.00 90.00 12.80 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1283 C087D0 Window 8DA7DB Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 5.57 5.57 5.57 180.00 90.00 3.05 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1284 D2CA75 Window 8DA7DB Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 5.57 5.57 5.57 180.00 90.00 3.05 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1285 B0FB49 Window 8DA7DB Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 4.46 4.46 4.46 180.00 90.00 2.44 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1286 F8F69A Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 270.00 90.00 7.32 3.05 0.00 192E17 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1287 4CCA8D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   39.02 39.02 39.02 0.00 90.00 12.80 3.05 0.00 840387 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1288 2336C8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 624E8A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1289 38B339 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   17.84 27.87 17.84 270.00 90.00 9.14 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.56 0.44 4
1290 FE9BC9 Window 38B339 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 3.34 3.34 3.34 270.00 90.00 1.83 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
1291 9DF7DE Window 38B339 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 3.34 3.34 3.34 270.00 90.00 1.83 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.55 0.45 4
1292 D0BE44 Window 38B339 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 3.34 3.34 3.34 270.00 90.00 1.83 1.83 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.61 0.39 4
1293 F4E5F5 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   33.45 33.45 33.45 180.00 180.00 3.66 9.14 0.00 A4BE81 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1294 AA7BE2 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   16.72 16.72 16.72 180.00 180.00 1.83 9.14 0.00 E26130 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1295 68EB71 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   50.17 50.17 50.17 180.00 180.00 5.49 9.14 0.00 906F5E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1296 66FE82 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   31.77 31.77 31.77 270.00 180.00 5.49 5.79 0.00 4EB51A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1297 948D7B Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   16.72 16.72 16.72 180.00 180.00 1.83 9.14 0.00 E9AEFF Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1298 236CCE Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   23.41 23.41 23.41 0.00 180.00 12.80 1.83 0.00 4DAEA4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1299 AE769E Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   38.46 38.46 38.46 90.00 180.00 5.49 7.01 0.00 1DCC9F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1300 FLOOR 3 UNDEVELOPED 1 ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   210.70 210.70 210.70 0.00 0.00 12.80 16.46 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1301 FLOOR 3 UNDEVELOPED 1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   421.41 421.41 421.41 0.00 90.00 421.41 1.00 0.00 FLOOR 3 UNDEVELOPED 1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1302 BE5F2F Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   10.41 14.86 10.41 270.00 90.00 4.88 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
1303 6B5226 Window BE5F2F Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 4.46 4.46 4.46 270.00 90.00 3.66 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
1304 D5C4E5 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 E2AFEB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1305 C1B522 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 270.00 90.00 2.44 3.05 0.00 573330 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1306 1DEE26 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   28.24 37.16 28.24 180.00 90.00 12.19 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.55 0.45 4
1307 8F59F7 Window 1DEE26 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 4.46 4.46 4.46 180.00 90.00 3.66 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
1308 44F571 Window 1DEE26 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 4.46 4.46 4.46 180.00 90.00 3.66 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.56 0.44 4
1309 192E17 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 90.00 90.00 7.32 3.05 0.00 F8F69A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1310 855B07 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   48.31 48.31 48.31 0.00 90.00 15.85 3.05 0.00 2F3F2A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1311 9D1FA7 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   91.42 91.42 91.42 270.00 180.00 9.56 9.56 0.00 C39FCC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
1312 6F1456 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   3.90 3.90 3.90 180.00 180.00 2.13 1.83 0.00 7A3F36 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1313 CDCFEE Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.71 11.71 11.71 0.00 180.00 2.13 5.49 0.00 E9C76F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1314 FLOOR 3 UNDEVELOPED 2 ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   107.02 107.02 107.02 180.00 0.00 10.35 10.35 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
1315 FLOOR 3 UNDEVELOPED 2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   214.05 214.05 214.05 0.00 90.00 214.05 1.00 0.00 FLOOR 3 UNDEVELOPED 2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1316 111907 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 0.00 90.00 5.49 3.05 0.00 133349 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1317 CF2803 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 F5E7FE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1318 180143 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 89A685 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1319 2BC70D Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 44D36C Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1320 DF5076 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   20.07 20.07 20.07 0.00 180.00 5.49 3.66 0.00 93EF1F Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1321 FLOOR 3 UTILITY ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   20.07 20.07 20.07 0.00 0.00 5.49 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1322 FLOOR 3 UTILITY_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   40.13 40.13 40.13 0.00 90.00 40.13 1.00 0.00 FLOOR 3 UTILITY_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1323 3613B7 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 0.00 90.00 4.27 3.05 0.00 6C68C2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1324 C86329 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   29.17 38.09 29.17 90.00 90.00 12.50 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1325 6BD844 Window C86329 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1326 86D536 Window C86329 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1327 BAF71D Window C86329 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1328 3833A2 Window C86329 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 2.23 2.23 2.23 90.00 90.00 1.83 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1329 E7A265 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 F3F6EA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1330 4C6DBF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   23.23 23.23 23.23 270.00 90.00 7.62 3.05 0.00 A11DA8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1331 EFFB3B Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 270.00 90.00 4.88 3.05 0.00 8BCB23 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1332 8480E5 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   41.62 41.62 41.62 180.00 180.00 4.27 9.75 0.00 9BB582 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1333 F6DDE6 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   11.71 11.71 11.71 0.00 180.00 4.27 2.74 0.00 703D3E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1334 FLOOR 3 WORK ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   53.33 53.33 53.33 90.00 0.00 12.50 4.27 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1335 FLOOR 3 WORK_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   106.65 106.65 106.65 0.00 90.00 106.65 1.00 0.00 FLOOR 3 WORK_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1336 986A05 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 C1C64E Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1337 DFC6F0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   18.77 19.51 18.77 90.00 90.00 2.13 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1338 2111A1 Window DFC6F0 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 0.74 0.74 0.74 90.00 90.00 0.61 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1339 6EE166 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 B2F07D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1340 A28F01 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 180.00 90.00 6.10 3.05 0.00 204CB9 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1341 DE6295 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 BFA29B Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1342 D68874 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 BC2C22 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1343 88E360 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   51.71 66.89 51.71 0.00 90.00 7.32 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
1344 9CB8E5 Door 88E360 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.63 0.37 4
1345 9BC521 Window 88E360 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 5.71 5.71 5.71 0.00 90.00 3.75 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1346 142781 Window 88E360 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 5.57 5.57 5.57 0.00 90.00 3.66 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1347 E4A528 Door 88E360 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
1348 16BE00 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 A8FC82 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1349 60F634 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.01 13.01 13.01 180.00 90.00 4.27 3.05 0.00 6F0E5D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1350 E7B55F Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   11.15 11.15 11.15 180.00 90.00 1.22 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.70 0.30 4
1351 EEFDE3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 270.00 90.00 2.13 3.05 0.00 D2E9BA Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1352 NE STAIR SLAB Floor   CTF - ConductionTransferFunction NESTAIRSLAB_FFACTOR 0.666 0.573   15.61 15.61 15.61 0.00 180.00 7.32 2.13 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1353 NE STAIR ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   15.61 15.61 15.61 0.00 0.00 7.32 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1354 NE STAIR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   31.22 31.22 31.22 0.00 90.00 31.22 1.00 0.00 NE STAIR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1355 FB3814 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   17.56 19.51 17.56 180.00 90.00 2.13 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.68 0.32 4
1356 24BAF7 Door FB3814 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.71 0.29 4
1357 976E3F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 90.00 90.00 6.10 3.05 0.00 43A2A2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1358 FCD12D Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   53.79 55.74 53.79 270.00 90.00 6.10 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1359 19E57D Door FCD12D CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1360 D699FF Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 7F6FC2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1361 F9DFA4 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 90.00 90.00 6.10 3.05 0.00 E0CB0D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1362 BDE9D9 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 49DA28 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1363 BEDECA Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.58 18.58 18.58 90.00 90.00 6.10 3.05 0.00 8D1659 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1364 9BA592 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.50 6.50 6.50 0.00 90.00 2.13 3.05 0.00 D5E94D Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1365 NW ELEVATOR SLAB Floor   CTF - ConductionTransferFunction NWELEVATORSLAB_FFACTOR 0.612 0.532   13.01 13.01 13.01 90.00 180.00 6.10 2.13 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1366 NW ELEVATOR ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   13.01 13.01 13.01 90.00 0.00 6.10 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1367 NW ELEVATOR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   26.01 26.01 26.01 0.00 90.00 26.01 1.00 0.00 NW ELEVATOR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1368 5507DC Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   20.35 22.30 20.35 270.00 90.00 2.44 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.65 0.35 4
1369 EDE769 Door 5507DC CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.68 0.32 4
1370 2E2D0C Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   53.79 66.89 53.79 0.00 90.00 7.32 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1371 E74902 Window 2E2D0C Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 5.57 5.57 5.57 0.00 90.00 3.66 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1372 93BBC3 Window 2E2D0C Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 5.57 5.57 5.57 0.00 90.00 3.66 1.52 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1373 1C9872 Door 2E2D0C CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1374 FA9233 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 822161 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1375 AF0124 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   22.30 22.30 22.30 90.00 90.00 2.44 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.68 0.32 4
1376 74AB49 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   14.86 14.86 14.86 180.00 90.00 4.88 3.05 0.00 92A2CB Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1377 DF47AC Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.57 5.57 5.57 180.00 90.00 1.83 3.05 0.00 5EAFB3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1378 F41621 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.30 22.30 22.30 180.00 90.00 7.32 3.05 0.00 E55935 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1379 7C0F83 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   16.72 16.72 16.72 180.00 90.00 5.49 3.05 0.00 7DCAF1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1380 NW STAIR SLAB Floor   CTF - ConductionTransferFunction NWSTAIRSLAB_FFACTOR 0.666 0.573   17.84 17.84 17.84 270.00 180.00 2.44 7.32 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1381 NW STAIR ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   17.84 17.84 17.84 270.00 0.00 2.44 7.32 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1382 NW STAIR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   35.67 35.67 35.67 0.00 90.00 35.67 1.00 0.00 NW STAIR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
1383 8FF821 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 368E02 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1384 850EA7 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   32.33 33.45 32.33 180.00 90.00 3.66 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.52 0.48 4
1385 C635A6 Window 850EA7 Window5 Detailed Fenestration NONRESWINDOW_U_0.29_SHGC_0.4 N/A 1.647 No 1.11 1.11 1.11 180.00 90.00 0.91 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.53 0.47 4
1386 1068C8 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 BAD27A Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1387 E2AFEB Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 D5C4E5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1388 99468F Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 FCDEAC Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1389 17258E Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 3DE7A6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1390 573330 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 90.00 90.00 2.44 3.05 0.00 C1B522 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
1391 270BCE Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL 0.290 0.278   20.35 22.30 20.35 270.00 90.00 2.44 9.14 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
1392 F402E9 Door 270BCE CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.51 0.49 4
1393 SW STAIR SLAB Floor   CTF - ConductionTransferFunction SWSTAIRSLAB_FFACTOR 0.666 0.573   8.92 8.92 8.92 270.00 180.00 2.44 3.66 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
1394 SW STAIR ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   8.92 8.92 8.92 180.00 0.00 3.66 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
1395 SW STAIR_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   17.84 17.84 17.84 0.00 90.00 17.84 1.00 0.00 SW STAIR_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1
2 VETERANS DAY Holiday InputFile 11/11 1
3 CHRISTMAS Holiday InputFile 12/25 1
4 INDEPENDENCE DAY Holiday InputFile 07/04 1
5 MLK DAY Holiday InputFile 01/16 1
6 PRESIDENTS DAY Holiday InputFile 02/20 1
7 MEMORIAL DAY Holiday InputFile 05/29 1
8 LABOR DAY Holiday InputFile 09/04 1
9 COLUMBUS DAY Holiday InputFile 10/09 1
10 THANKSGIVING Holiday InputFile 11/23 1


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Environment:WarmupDays

NumberofWarmupDays
1 12


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 FLOOR 1 ANESTHESIA RunPeriod: RUNPERIOD 1 3.0906039508E-002 4.6249814214E-002 Pass Pass 0.2265089829 0.5592907736 Pass Pass
2 FLOOR 1 BIO HAZ RunPeriod: RUNPERIOD 1 1.1031304005E-003 2.1643270594E-003 Pass Pass 8.0986718852E-003 7.9357712735E-003 Pass Pass
3 FLOOR 1 CAFE RunPeriod: RUNPERIOD 1 3.6725041286E-002 4.5053075304E-002 Pass Pass 0.3884138237 2.5909992049 Pass Pass
4 FLOOR 1 CLEAN RunPeriod: RUNPERIOD 1 3.8524077883E-002 5.6427400473E-002 Pass Pass 7.9815563441E-002 0.2031735151 Pass Pass
5 FLOOR 1 CLEAN WORK RunPeriod: RUNPERIOD 1 3.1041129399E-002 5.3548973396E-002 Pass Pass 9.5959441244E-002 0.2680620831 Pass Pass
6 FLOOR 1 DICTATION RunPeriod: RUNPERIOD 1 1.5240862337E-002 1.8919722096E-002 Pass Pass 6.4896618514E-002 0.1539347417 Pass Pass
7 FLOOR 1 DRESSING ROOM RunPeriod: RUNPERIOD 1 3.9605938484E-003 8.7919651363E-003 Pass Pass 6.8773122930E-003 6.4781431487E-003 Pass Pass
8 FLOOR 1 ELECTRICAL ROOM RunPeriod: RUNPERIOD 1 2.6903193660E-002 4.2137467708E-002 Pass Pass 8.9812249357E-002 0.2358204665 Pass Pass
9 FLOOR 1 ELEVATOR PUMP ROOM RunPeriod: RUNPERIOD 1 6.5526224802E-002 0.1014975468 Pass Pass 0.1322481220 0.2795410161 Pass Pass
10 FLOOR 1 HUMID RunPeriod: RUNPERIOD 1 1.3882739943E-002 1.7155151120E-002 Pass Pass 5.8666715214E-002 0.1368264437 Pass Pass
11 FLOOR 1 IT HALL RunPeriod: RUNPERIOD 1 7.5025697084E-003 9.8705674499E-003 Pass Pass 0.1579933358 0.4990102914 Pass Pass
12 FLOOR 1 IT ROOM RunPeriod: RUNPERIOD 1 1.9724870019E-002 3.1050995045E-002 Pass Pass 0.2371289233 0.7114985584 Pass Pass
13 FLOOR 1 LOBBY RunPeriod: RUNPERIOD 1 1.3598978390E-002 2.9227933492E-002 Pass Pass 0.4432904681 2.2607805957 Pass Pass
14 FLOOR 1 LOBBY HALL RunPeriod: RUNPERIOD 1 1.6918353494E-002 1.3793994848E-002 Pass Pass 6.5932058080E-002 0.1504225719 Pass Pass
15 FLOOR 1 LOBBY TOILET RunPeriod: RUNPERIOD 1 1.2205832592E-002 2.8822192911E-002 Pass Pass 0.2213656316 0.5892076200 Pass Pass
16 FLOOR 1 LOCKER ROOM RunPeriod: RUNPERIOD 1 2.2814779927E-002 3.7480707278E-002 Pass Pass 9.7239282195E-002 0.2639958446 Pass Pass
17 FLOOR 1 LOCKER ROOM HALL RunPeriod: RUNPERIOD 1 9.3701882835E-003 1.1292416632E-002 Pass Pass 8.9274581620E-002 0.2289164378 Pass Pass
18 FLOOR 1 LOUNGE RunPeriod: RUNPERIOD 1 2.1818982716E-002 3.4947433253E-002 Pass Pass 6.4934276868E-002 0.1555329600 Pass Pass
19 FLOOR 1 MED GAS RunPeriod: RUNPERIOD 1 5.0253129247E-003 1.1535108372E-002 Pass Pass 4.7266276107E-003 5.1561269004E-003 Pass Pass
20 FLOOR 1 MRI CONTROL ROOM RunPeriod: RUNPERIOD 1 4.1776920515E-002 7.6305002980E-002 Pass Pass 4.3503645229E-002 9.9476246584E-002 Pass Pass
21 FLOOR 1 MRI HALL RunPeriod: RUNPERIOD 1 1.1556043297E-002 1.1748414828E-002 Pass Pass 0.1033670859 0.2719433624 Pass Pass
22 FLOOR 1 MRI ROOM RunPeriod: RUNPERIOD 1 4.4623475786E-002 8.3899054940E-002 Pass Pass 3.0615487757E-002 6.7708440820E-002 Pass Pass
23 FLOOR 1 MRI TOILET RunPeriod: RUNPERIOD 1 4.0269469683E-003 1.0002245209E-002 Pass Pass 1.2200220720E-002 1.6071553728E-002 Pass Pass
24 FLOOR 1 NOURISHMENT RunPeriod: RUNPERIOD 1 2.0386718164E-002 2.8732127468E-002 Pass Pass 5.4834631904E-002 0.1268787574 Pass Pass
25 FLOOR 1 NURSE HALL RunPeriod: RUNPERIOD 1 2.1694136573E-002 1.9597880071E-002 Pass Pass 8.2818746014E-002 0.1948140002 Pass Pass
26 FLOOR 1 NURSE JANITOR RunPeriod: RUNPERIOD 1 8.6692568149E-003 1.0107015015E-002 Pass Pass 6.8345047642E-002 0.1634831195 Pass Pass
27 FLOOR 1 NURSE STATION RunPeriod: RUNPERIOD 1 2.2132185202E-002 2.9618726434E-002 Pass Pass 6.1721213441E-002 0.1445041223 Pass Pass
28 FLOOR 1 NURSE TOILET RunPeriod: RUNPERIOD 1 2.1411714118E-002 3.0357398232E-002 Pass Pass 0.1189120055 0.3562138171 Pass Pass
29 FLOOR 1 OFFICE RunPeriod: RUNPERIOD 1 1.5455281466E-002 1.9375600628E-002 Pass Pass 8.2219694189E-002 0.2058648897 Pass Pass
30 FLOOR 1 OPERATING ROOM 1 RunPeriod: RUNPERIOD 1 3.2363503564E-002 6.1673659792E-002 Pass Pass 9.0933979222E-002 0.3898018680 Pass Pass
31 FLOOR 1 OPERATING ROOM 2 RunPeriod: RUNPERIOD 1 5.5206795397E-002 0.1067923343 Pass Pass 9.0215342417E-002 0.3968366312 Pass Pass
32 FLOOR 1 OPERATING ROOM 3 RunPeriod: RUNPERIOD 1 5.3312384378E-002 9.9631115929E-002 Pass Pass 7.9866997896E-002 0.2490311793 Pass Pass
33 FLOOR 1 PACU RunPeriod: RUNPERIOD 1 3.4845389770E-002 6.0120473754E-002 Pass Pass 8.7413855749E-002 0.2365028884 Pass Pass
34 FLOOR 1 PRE-OP HALL RunPeriod: RUNPERIOD 1 1.0967205697E-002 1.1641676883E-002 Pass Pass 0.1079118640 0.2911005636 Pass Pass
35 FLOOR 1 PRE-OP ROOM 1 RunPeriod: RUNPERIOD 1 1.6372034177E-002 2.9676443983E-002 Pass Pass 0.1323033712 0.5074734845 Pass Pass
36 FLOOR 1 PRE-OP ROOM 2 RunPeriod: RUNPERIOD 1 3.4895972821E-002 5.7848492611E-002 Pass Pass 9.4381982261E-002 0.2694451766 Pass Pass
37 FLOOR 1 PRE-OP TOILET RunPeriod: RUNPERIOD 1 4.7132943525E-003 1.2203876984E-002 Pass Pass 4.9580555725E-002 6.3933694220E-002 Pass Pass
38 FLOOR 1 PROCEDURE ROOM RunPeriod: RUNPERIOD 1 1.7373181256E-002 4.8654948714E-002 Pass Pass 0.1873976424 0.3276804494 Pass Pass
39 FLOOR 1 RECEPTION RunPeriod: RUNPERIOD 1 3.1160605286E-002 3.0199083737E-002 Pass Pass 8.1871967631E-002 0.1914161514 Pass Pass
40 FLOOR 1 RECEPTION HALL RunPeriod: RUNPERIOD 1 1.1316556547E-002 1.1677993502E-002 Pass Pass 9.8675620714E-002 0.2559438081 Pass Pass
41 FLOOR 1 RECOVERY ROOM RunPeriod: RUNPERIOD 1 3.1474754432E-002 4.6815824955E-002 Pass Pass 0.4069309484 2.0942506327 Pass Pass
42 FLOOR 1 SCHEDULING RunPeriod: RUNPERIOD 1 1.9124676000E-002 2.7041928188E-002 Pass Pass 0.3156861140 1.0382931809 Pass Pass
43 FLOOR 1 SCRUB RunPeriod: RUNPERIOD 1 7.0549281980E-003 1.0639391696E-002 Pass Pass 0.3212370254 1.0951435362 Pass Pass
44 FLOOR 1 SOIL RunPeriod: RUNPERIOD 1 3.2856261335E-002 5.4009596956E-002 Pass Pass 8.6791271298E-002 0.2431384767 Pass Pass
45 FLOOR 1 SOIL HOLD RunPeriod: RUNPERIOD 1 4.0089004366E-002 5.8096338101E-002 Pass Pass 0.3406440317 1.5206912756 Pass Pass
46 FLOOR 1 SOIL WORK RunPeriod: RUNPERIOD 1 2.9668554989E-002 4.7462590110E-002 Pass Pass 0.1020405990 0.2936258965 Pass Pass
47 FLOOR 1 STEP DOWN RunPeriod: RUNPERIOD 1 1.6192114616E-002 2.8648101421E-002 Pass Pass 0.2463893917 1.2889637435 Pass Pass
48 FLOOR 1 STERILE HALL RunPeriod: RUNPERIOD 1 1.6607158595E-002 2.0042628582E-002 Pass Pass 0.1154800097 0.3096718358 Pass Pass
49 FLOOR 1 STERILE STORAGE RunPeriod: RUNPERIOD 1 8.3023292955E-003 9.3623100610E-003 Pass Pass 7.5835420079E-002 0.1858730613 Pass Pass
50 FLOOR 1 STORAGE RunPeriod: RUNPERIOD 1 3.1030037174E-003 7.4041402718E-003 Pass Pass 4.5460525338E-003 5.4456122386E-003 Pass Pass
51 FLOOR 1 SUB-STERILE RunPeriod: RUNPERIOD 1 1.8257639175E-003 4.5049667931E-003 Pass Pass 2.0250907493E-002 3.5425824812E-002 Pass Pass
52 FLOOR 1 UTILITY HALL RunPeriod: RUNPERIOD 1 2.6089395456E-003 6.2045596766E-003 Pass Pass 5.1764676422E-003 6.1702977598E-003 Pass Pass
53 FLOOR 1 UTILITY JANITOR RunPeriod: RUNPERIOD 1 6.6114353363E-003 1.1002890693E-002 Pass Pass 0.2686573148 0.7127989669 Pass Pass
54 FLOOR 1 UTILITY ROOM RunPeriod: RUNPERIOD 1 1.7143242228E-003 4.2988620159E-003 Pass Pass 1.0087672592E-002 1.7791995778E-002 Pass Pass
55 FLOOR 1 VESTIBULE RunPeriod: RUNPERIOD 1 2.2720981699E-003 5.6062462740E-003 Pass Pass 1.3731454659E-002 1.6515830861E-002 Pass Pass
56 FLOOR 2 CONFERENCE RunPeriod: RUNPERIOD 1 1.7689797129E-002 3.7296617205E-002 Pass Pass 0.2077753760 1.4299177328 Pass Pass
57 FLOOR 2 CONFERENCE TOILET RunPeriod: RUNPERIOD 1 3.6092330444E-003 8.9876972578E-003 Pass Pass 2.9335643511E-002 3.6189990420E-002 Pass Pass
58 FLOOR 2 DICTATION RunPeriod: RUNPERIOD 1 8.9870290781E-003 1.1675011567E-002 Pass Pass 2.5192261142E-003 4.1748520749E-003 Pass Pass
59 FLOOR 2 EXAM 1 RunPeriod: RUNPERIOD 1 1.5480880783E-006 2.1635723248E-006 Pass Pass 9.2920291090E-002 0.2551369887 Pass Pass
60 FLOOR 2 EXAM 2 RunPeriod: RUNPERIOD 1 4.4976914117E-007 6.9774636296E-007 Pass Pass 0.1319804380 0.5680051325 Pass Pass
61 FLOOR 2 EXAM 3 RunPeriod: RUNPERIOD 1 4.8099500188E-007 7.2323879803E-007 Pass Pass 0.1555076380 0.6025381919 Pass Pass
62 FLOOR 2 EXAM 4 RunPeriod: RUNPERIOD 1 2.2322570325E-002 4.3538419833E-002 Pass Pass 0.1313117121 0.3778586970 Pass Pass
63 FLOOR 2 EXAM 5 RunPeriod: RUNPERIOD 1 8.7847087853E-007 1.2416937825E-006 Pass Pass 0.3383408058 1.8764494263 Pass Pass
64 FLOOR 2 EXAM 6 RunPeriod: RUNPERIOD 1 1.2978816900E-006 1.8014315743E-006 Pass Pass 1.1606521422E-002 2.3546216492E-002 Pass Pass
65 FLOOR 2 EXAM 7 RunPeriod: RUNPERIOD 1 7.7214745390E-007 1.0991778000E-006 Pass Pass 0.1309702790 0.5511302847 Pass Pass
66 FLOOR 2 EXAM 8 RunPeriod: RUNPERIOD 1 1.2886174608E-006 1.7968107435E-006 Pass Pass 1.2491914421E-002 2.5350697803E-002 Pass Pass
67 FLOOR 2 EXAM 9 RunPeriod: RUNPERIOD 1 7.7719496246E-007 1.1035241968E-006 Pass Pass 0.2458580431 1.2148937258 Pass Pass
68 FLOOR 2 EXAM HALL 1 RunPeriod: RUNPERIOD 1 1.3689757266E-002 1.7137013477E-002 Pass Pass 0.4879685276 4.6335833975 Pass Pass
69 FLOOR 2 EXAM HALL 2 RunPeriod: RUNPERIOD 1 1.5990012092E-002 1.4689138030E-002 Pass Pass 2.1050116863E-002 5.1176477895E-002 Pass Pass
70 FLOOR 2 EXAM HALL 3 RunPeriod: RUNPERIOD 1 1.9003177042E-002 1.6576705680E-002 Pass Pass 2.6331961580E-002 6.0547155876E-002 Pass Pass
71 FLOOR 2 EXAM HALL 4 RunPeriod: RUNPERIOD 1 5.2967146101E-007 9.8687047417E-007 Pass Pass 0.1531621423 0.6494384124 Pass Pass
72 FLOOR 2 EXAM HALL 5 RunPeriod: RUNPERIOD 1 5.0980792321E-007 9.5355216205E-007 Pass Pass 0.2366631299 1.3028710100 Pass Pass
73 FLOOR 2 EXAM HALL 6 RunPeriod: RUNPERIOD 1 7.4693915492E-007 1.3429451615E-006 Pass Pass 2.7574187507E-002 5.5313260463E-002 Pass Pass
74 FLOOR 2 JANITOR RunPeriod: RUNPERIOD 1 3.7455373362E-006 7.4118689706E-006 Pass Pass 1.3028693996E-002 1.1335219273E-002 Pass Pass
75 FLOOR 2 LOUNGE RunPeriod: RUNPERIOD 1 1.2098023856E-002 3.0937682594E-002 Pass Pass 3.0632752558E-003 9.9171914790E-003 Pass Pass
76 FLOOR 2 NURSE STATION 1 RunPeriod: RUNPERIOD 1 9.4939743287E-003 2.7288891310E-002 Pass Pass 2.9615655336E-003 1.0251219641E-002 Pass Pass
77 FLOOR 2 NURSE STATION 2 RunPeriod: RUNPERIOD 1 9.0523573452E-003 2.7262532975E-002 Pass Pass 2.9005306848E-003 1.0485605750E-002 Pass Pass
78 FLOOR 2 OFFICE RunPeriod: RUNPERIOD 1 1.3745968538E-006 2.7977913253E-006 Pass Pass 3.7124582494E-002 6.3377375207E-002 Pass Pass
79 FLOOR 2 OFFICE HALL RunPeriod: RUNPERIOD 1 5.2493948640E-003 7.6529069225E-003 Pass Pass 3.0133835676E-002 6.8265893266E-002 Pass Pass
80 FLOOR 2 RECEPTION RunPeriod: RUNPERIOD 1 1.1149114291E-002 2.9713125080E-002 Pass Pass 0.1581398983 0.5617935230 Pass Pass
81 FLOOR 2 RECEPTION HALL RunPeriod: RUNPERIOD 1 1.0547495493E-002 6.8430488505E-003 Pass Pass 2.7842355348E-003 1.8472699663E-003 Pass Pass
82 FLOOR 2 RECEPTION TOILET RunPeriod: RUNPERIOD 1 2.2133838740E-003 6.9834546752E-003 Pass Pass 1.8334373850E-002 1.7994022063E-002 Pass Pass
83 FLOOR 2 SCHEDULING 1 RunPeriod: RUNPERIOD 1 7.8701339747E-003 1.4367395655E-002 Pass Pass 2.0161680723E-003 4.4441930855E-003 Pass Pass
84 FLOOR 2 SCHEDULING 2 RunPeriod: RUNPERIOD 1 9.7123343609E-003 1.4457130424E-002 Pass Pass 2.4745086023E-003 4.4049466586E-003 Pass Pass
85 FLOOR 2 STORAGE 1 RunPeriod: RUNPERIOD 1 1.8279024709E-002 2.4476131139E-002 Pass Pass 1.2305975314E-002 1.4722318906E-002 Pass Pass
86 FLOOR 2 STORAGE 2 RunPeriod: RUNPERIOD 1 3.3869116613E-007 6.1379410580E-007 Pass Pass 0.1491672149 0.3861611761 Pass Pass
87 FLOOR 2 STORAGE 3 RunPeriod: RUNPERIOD 1 4.7622169736E-007 8.4644786546E-007 Pass Pass 0.1556534737 0.4288750499 Pass Pass
88 FLOOR 2 UTILITY RunPeriod: RUNPERIOD 1 2.1846178094E-006 3.5501177076E-006 Pass Pass 2.4370649016E-002 4.7111518320E-002 Pass Pass
89 FLOOR 2 WORK RunPeriod: RUNPERIOD 1 1.3619421628E-003 6.3105684286E-003 Pass Pass 0.2248060486 1.9460549759 Pass Pass
90 FLOOR 2 WORK HALL RunPeriod: RUNPERIOD 1 7.5660834225E-003 5.8008036334E-003 Pass Pass 2.2361694063E-003 1.8594627519E-003 Pass Pass
91 FLOOR 2 WORK TOILET RunPeriod: RUNPERIOD 1 1.5483417997E-006 2.4531004993E-006 Pass Pass 1.0518043882E-002 9.2265687795E-003 Pass Pass
92 FLOOR 2 X-RAY RunPeriod: RUNPERIOD 1 2.8248658497E-002 9.4663145311E-002 Pass Pass 4.1912068503E-003 1.7303625836E-002 Pass Pass
93 FLOOR 3 DRESSING ROOM RunPeriod: RUNPERIOD 1 4.2441081507E-003 8.1883007371E-003 Pass Pass 0.2467521065 1.2625781462 Pass Pass
94 FLOOR 3 ELEVATOR HALL RunPeriod: RUNPERIOD 1 2.4923929946E-006 4.3451857679E-006 Pass Pass 8.4706316865E-003 1.1076580064E-002 Pass Pass
95 FLOOR 3 HUMID RunPeriod: RUNPERIOD 1 5.0664267631E-003 9.2974401831E-003 Pass Pass 0.2455393735 1.5187436079 Pass Pass
96 FLOOR 3 JANITOR RunPeriod: RUNPERIOD 1 3.8150199884E-006 6.4326099670E-006 Pass Pass 4.8049096612E-003 3.4806969681E-003 Pass Pass
97 FLOOR 3 LOCKER RunPeriod: RUNPERIOD 1 8.8765268081E-004 3.6703287260E-003 Pass Pass 0.2437751756 1.8958529169 Pass Pass
98 FLOOR 3 LOUNGE RunPeriod: RUNPERIOD 1 3.7677264790E-003 1.4433905716E-002 Pass Pass 0.2820236089 2.3927552498 Pass Pass
99 FLOOR 3 LOUNGE TOILET RunPeriod: RUNPERIOD 1 2.2304717685E-006 3.4498425815E-006 Pass Pass 7.4226570944E-003 6.9914724780E-003 Pass Pass
100 FLOOR 3 MECHANICAL RunPeriod: RUNPERIOD 1 6.8430008297E-002 0.2934254014 Pass Pass 0.8926495357 10.5384984671 Pass Pass
101 FLOOR 3 MECHANICAL HALL RunPeriod: RUNPERIOD 1 3.6327335787E-004 2.2531590363E-003 Pass Pass 0.3010126934 0.8259034481 Pass Pass
102 FLOOR 3 OFFICE RunPeriod: RUNPERIOD 1 1.3906579317E-006 2.9572444070E-006 Pass Pass 1.5421926597E-002 3.2536702702E-002 Pass Pass
103 FLOOR 3 OFFICE HALL RunPeriod: RUNPERIOD 1 1.5159740772E-006 2.6874654040E-006 Pass Pass 0.2559906689 1.8739682236 Pass Pass
104 FLOOR 3 OFFICE TOILET RunPeriod: RUNPERIOD 1 1.9638502560E-006 3.0345545561E-006 Pass Pass 7.2609803059E-003 5.7109218053E-003 Pass Pass
105 FLOOR 3 PHYSICAL THERAPY 1 RunPeriod: RUNPERIOD 1 1.5373700032E-002 3.2695826745E-002 Pass Pass 9.5118082479E-002 0.2711076130 Pass Pass
106 FLOOR 3 PHYSICAL THERAPY 2 RunPeriod: RUNPERIOD 1 7.6216785394E-007 1.1027455670E-006 Pass Pass 0.1699046271 0.4548227033 Pass Pass
107 FLOOR 3 PHYSICAL THERAPY TOILET RunPeriod: RUNPERIOD 1 7.1039840516E-007 1.2629633373E-006 Pass Pass 1.4339147583 13.3984005293 Pass Pass
108 FLOOR 3 STORAGE 1 RunPeriod: RUNPERIOD 1 1.1600691546E-006 1.9967928576E-006 Pass Pass 2.2674541224E-002 1.9994682379E-002 Pass Pass
109 FLOOR 3 STORAGE 2 RunPeriod: RUNPERIOD 1 1.9431156335E-006 3.5209958728E-006 Pass Pass 1.4194095395E-002 1.1126094339E-002 Pass Pass
110 FLOOR 3 TREATMENT RunPeriod: RUNPERIOD 1 5.7486353352E-007 8.5056552522E-007 Pass Pass 0.1791012660 0.4457058281 Pass Pass
111 FLOOR 3 UNDEVELOPED 1 RunPeriod: RUNPERIOD 1 1.6377173188E-002 3.7883341056E-002 Pass Pass 0.1755980856 0.8490521000 Pass Pass
112 FLOOR 3 UNDEVELOPED 2 RunPeriod: RUNPERIOD 1 9.9510785822E-003 2.5218615556E-002 Pass Pass 0.7121557154 6.2330999995 Pass Pass
113 FLOOR 3 UTILITY RunPeriod: RUNPERIOD 1 1.6952190357E-006 3.0968030651E-006 Pass Pass 2.0465705052E-002 1.7647719713E-002 Pass Pass
114 FLOOR 3 WORK RunPeriod: RUNPERIOD 1 1.8389871359E-006 4.3438241416E-006 Pass Pass 0.1399601540 0.6661498690 Pass Pass
115 NE STAIR RunPeriod: RUNPERIOD 1 5.6020761274E-006 9.6983344614E-006 Pass Pass 6.4986838448E-003 6.3460893554E-003 Pass Pass
116 NW ELEVATOR RunPeriod: RUNPERIOD 1 5.1874784521E-006 8.7249341760E-006 Pass Pass 9.9092315162E-003 9.5647553012E-003 Pass Pass
117 NW STAIR RunPeriod: RUNPERIOD 1 5.8544174900E-006 1.0255148034E-005 Pass Pass 4.4918996239E-003 3.2482452165E-003 Pass Pass
118 SW STAIR RunPeriod: RUNPERIOD 1 5.3775094258E-006 7.8317130858E-006 Pass Pass 2.8181506629E-002 2.8067252896E-002 Pass Pass



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB -32.70 0.00 -32.70 Wetbulb [C] 2.40 210.00
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 30.10 12.40 21.10 Wetbulb [C] 4.70 200.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
481E71 NONRES_EXT_WALL 0.30 0.278 0.290 8.36 6.13 180.00 90.00 S
5F762C NONRES_EXT_WALL 0.30 0.278 0.290 18.58 9.66 180.00 90.00 S
84FB73 NONRES_EXT_WALL 0.30 0.278 0.290 8.36 6.04 0.00 90.00 N
7F5C82 NONRES_EXT_WALL 0.30 0.278 0.290 6.50 6.50 90.00 90.00 E
C732B0 NONRES_EXT_WALL 0.30 0.278 0.290 12.08 12.08 0.00 90.00 N
E02487 NONRES_EXT_WALL 0.30 0.278 0.290 6.50 4.55 270.00 90.00 W
FE5A3C NONRES_EXT_WALL 0.30 0.278 0.290 20.44 9.57 270.00 90.00 W
9D87EC NONRES_EXT_WALL 0.30 0.278 0.290 5.57 5.57 270.00 90.00 W
F629C1 NONRES_EXT_WALL 0.30 0.278 0.290 20.44 14.86 0.00 90.00 N
E85BB5 NONRES_EXT_WALL 0.30 0.278 0.290 7.43 5.48 0.00 90.00 N
577FC1 NONRES_EXT_WALL 0.30 0.278 0.290 6.50 6.50 90.00 90.00 E
FLOOR 1 MED GAS ROOF NONRES_ROOF 0.30 0.159 0.163 5.20 5.20 180.00 0.00  
C114C1 NONRES_EXT_WALL 0.30 0.278 0.290 4.65 2.69 0.00 90.00 N
ADB8D0 NONRES_EXT_WALL 0.30 0.278 0.290 5.57 5.57 0.00 90.00 N
879583 NONRES_EXT_WALL 0.30 0.278 0.290 18.58 14.12 180.00 90.00 S
E326E4 NONRES_EXT_WALL 0.30 0.278 0.290 21.37 14.96 90.00 90.00 E
1D96D7 NONRES_EXT_WALL 0.30 0.278 0.290 22.30 15.61 90.00 90.00 E
84418A NONRES_EXT_WALL 0.30 0.278 0.290 3.72 3.72 270.00 90.00 W
1535AC NONRES_EXT_WALL 0.30 0.278 0.290 5.57 5.57 270.00 90.00 W
6D2616 NONRES_EXT_WALL 0.30 0.278 0.290 17.65 12.08 0.00 90.00 N
A5A6A3 NONRES_EXT_WALL 0.30 0.278 0.290 12.08 8.73 180.00 90.00 S
28B002 NONRES_EXT_WALL 0.30 0.278 0.290 41.81 27.03 180.00 90.00 S
EA6DC8 NONRES_EXT_WALL 0.30 0.278 0.290 6.50 5.76 180.00 90.00 S
B40F89 NONRES_EXT_WALL 0.30 0.278 0.290 11.15 8.92 270.00 90.00 W
997723 NONRES_EXT_WALL 0.30 0.278 0.290 23.23 16.82 180.00 90.00 S
CEC7BD NONRES_EXT_WALL 0.30 0.278 0.290 7.43 5.20 180.00 90.00 S
8E5BB9 NONRES_EXT_WALL 0.30 0.278 0.290 21.37 18.39 270.00 90.00 W
859BC1 NONRES_EXT_WALL 0.30 0.278 0.290 37.16 22.95 0.00 90.00 N
FLOOR 1 STORGE ROOF NONRES_ROOF 0.30 0.159 0.163 85.47 85.47 270.00 0.00  
61E610 NONRES_EXT_WALL 0.30 0.278 0.290 13.01 10.03 90.00 90.00 E
529072 NONRES_EXT_WALL 0.30 0.278 0.290 14.86 7.43 90.00 90.00 E
FLOOR 1 UTILITY HALL ROOF NONRES_ROOF 0.30 0.159 0.163 11.89 11.89 180.00 0.00  
D95F04 NONRES_EXT_WALL 0.30 0.278 0.290 16.72 12.54 90.00 90.00 E
3330D8 NONRES_EXT_WALL 0.30 0.278 0.290 7.43 5.48 270.00 90.00 W
208CCF NONRES_EXT_WALL 0.30 0.278 0.290 11.15 8.92 90.00 90.00 E
AEF992 NONRES_EXT_WALL 0.30 0.278 0.290 26.01 19.32 180.00 90.00 S
54D065 NONRES_EXT_WALL 0.30 0.278 0.290 11.15 8.92 180.00 90.00 S
1775A6 NONRES_EXT_WALL 0.30 0.278 0.290 27.87 21.18 270.00 90.00 W
97F00A NONRES_EXT_WALL 0.30 0.278 0.290 16.72 13.01 180.00 90.00 S
A497E9 NONRES_EXT_WALL 0.30 0.278 0.290 22.30 16.35 180.00 90.00 S
88A75F NONRES_EXT_WALL 0.30 0.278 0.290 6.50 4.27 180.00 90.00 S
B4E619 NONRES_EXT_WALL 0.30 0.278 0.290 23.23 17.28 90.00 90.00 E
9EC269 NONRES_EXT_WALL 0.30 0.278 0.290 13.94 9.75 0.00 90.00 N
B316F7 NONRES_EXT_WALL 0.30 0.278 0.290 22.30 16.72 0.00 90.00 N
9621FD NONRES_EXT_WALL 0.30 0.278 0.290 16.72 11.15 0.00 90.00 N
42CEE1 NONRES_EXT_WALL 0.30 0.278 0.290 11.15 8.36 0.00 90.00 N
4979C8 NONRES_EXT_WALL 0.30 0.278 0.290 5.57 5.57 180.00 90.00 S
8CA0BF NONRES_EXT_WALL 0.30 0.278 0.290 5.57 5.57 180.00 90.00 S
6C95E7 NONRES_EXT_WALL 0.30 0.278 0.290 5.57 5.57 180.00 90.00 S
F209CC NONRES_EXT_WALL 0.30 0.278 0.290 5.57 5.57 0.00 90.00 N
155BD6 NONRES_EXT_WALL 0.30 0.278 0.290 5.57 5.57 0.00 90.00 N
C5EA55 NONRES_EXT_WALL 0.30 0.278 0.290 5.57 5.57 0.00 90.00 N
8177BA NONRES_EXT_WALL 0.30 0.278 0.290 6.50 6.50 270.00 90.00 W
5E657E NONRES_EXT_WALL 0.30 0.278 0.290 8.36 8.36 0.00 90.00 N
4B1439 NONRES_EXT_WALL 0.30 0.278 0.290 37.16 28.24 90.00 90.00 E
4ABC66 NONRES_EXT_WALL 0.30 0.278 0.290 30.66 20.62 180.00 90.00 S
5B04CF NONRES_EXT_WALL 0.30 0.278 0.290 14.86 8.18 270.00 90.00 W
8D1BC4 NONRES_EXT_WALL 0.30 0.278 0.290 6.50 6.50 180.00 90.00 S
4B55FA NONRES_EXT_WALL 0.30 0.278 0.290 8.36 6.13 90.00 90.00 E
9C3A6A NONRES_EXT_WALL 0.30 0.278 0.290 20.44 14.86 0.00 90.00 N
C52EE0 NONRES_EXT_WALL 0.30 0.278 0.290 3.72 3.72 0.00 90.00 N
1C33AD NONRES_EXT_WALL 0.30 0.278 0.290 5.57 5.57 270.00 90.00 W
6CC177 NONRES_EXT_WALL 0.30 0.278 0.290 5.57 5.57 270.00 90.00 W
FLOOR 3 DRESSING ROOM ROOF NONRES_ROOF 0.30 0.159 0.163 3.90 3.90 270.00 0.00  
F7D24D NONRES_EXT_WALL 0.30 0.278 0.290 3.72 3.72 0.00 90.00 N
FLOOR 3 ELEVATOR HALL ROOF NONRES_ROOF 0.30 0.159 0.163 34.37 34.37 0.00 0.00  
FLOOR 3 HUMID ROOF NONRES_ROOF 0.30 0.159 0.163 10.03 10.03 270.00 0.00  
FC22D1 NONRES_EXT_WALL 0.30 0.278 0.290 8.36 8.36 0.00 90.00 N
DD2E2D NONRES_EXT_WALL 0.30 0.278 0.290 6.50 6.50 270.00 90.00 W
FLOOR 3 JANITOR ROOF NONRES_ROOF 0.30 0.159 0.163 5.85 5.85 0.00 0.00  
FLOOR 3 LOCKER ROOF NONRES_ROOF 0.30 0.159 0.163 11.15 11.15 0.00 0.00  
68A2D7 NONRES_EXT_WALL 0.30 0.278 0.290 21.37 15.79 0.00 90.00 N
FLOOR 3 LOUNGE ROOF NONRES_ROOF 0.30 0.159 0.163 70.51 70.51 270.00 0.00  
CE3FEF NONRES_EXT_WALL 0.30 0.278 0.290 11.15 6.97 0.00 90.00 N
FLOOR 3 LOUNGE TOILET ROOF NONRES_ROOF 0.30 0.159 0.163 17.84 17.84 0.00 0.00  
CE618F NONRES_EXT_WALL 0.30 0.278 0.290 23.23 17.28 90.00 90.00 E
FLOOR 3 MECHANICAL ROOF NONRES_ROOF 0.30 0.159 0.163 32.52 32.52 0.00 0.00  
FLOOR 3 MECHANICAL HALL ROOF NONRES_ROOF 0.30 0.159 0.163 27.87 27.87 0.00 0.00  
5ADC59 NONRES_EXT_WALL 0.30 0.278 0.290 68.75 49.24 0.00 90.00 N
FLOOR 3 OFFICE ROOF NONRES_ROOF 0.30 0.159 0.163 282.05 282.05 180.00 0.00  
D4F411 NONRES_EXT_WALL 0.30 0.278 0.290 5.57 5.57 270.00 90.00 W
FLOOR 3 OFFICE HALL ROOF NONRES_ROOF 0.30 0.159 0.163 77.48 77.48 270.00 0.00  
B35AD6 NONRES_EXT_WALL 0.30 0.278 0.290 5.57 5.57 270.00 90.00 W
FLOOR 3 OFFICE TOILET ROOF NONRES_ROOF 0.30 0.159 0.163 5.02 5.02 270.00 0.00  
D22917 NONRES_EXT_WALL 0.30 0.278 0.290 18.58 11.89 90.00 90.00 E
C1BC97 NONRES_EXT_WALL 0.30 0.278 0.290 60.39 38.09 180.00 90.00 S
FLOOR 3 PHYICAL THERAPY 1 ROOF NONRES_ROOF 0.30 0.159 0.163 120.77 120.77 180.00 0.00  
FLOOR 3 PHYSICAL THERAPY 2 ROOF NONRES_ROOF 0.30 0.159 0.163 55.00 55.00 90.00 0.00  
FLOOR 3 PHYSICAL THERAPY TOILET ROOF NONRES_ROOF 0.30 0.159 0.163 7.80 7.80 90.00 0.00  
FLOOR 3 STORAGE 1 ROOF NONRES_ROOF 0.30 0.159 0.163 10.03 10.03 180.00 0.00  
FLOOR 3 STORAGE 2 ROOF NONRES_ROOF 0.30 0.159 0.163 7.80 7.80 180.00 0.00  
FLOOR 3 TREATMENT ROOF NONRES_ROOF 0.30 0.159 0.163 44.22 44.22 90.00 0.00  
8DA7DB NONRES_EXT_WALL 0.30 0.278 0.290 39.02 23.41 180.00 90.00 S
38B339 NONRES_EXT_WALL 0.30 0.278 0.290 27.87 17.84 270.00 90.00 W
FLOOR 3 UNDEVELOPED 1 ROOF NONRES_ROOF 0.30 0.159 0.163 210.70 210.70 0.00 0.00  
BE5F2F NONRES_EXT_WALL 0.30 0.278 0.290 14.86 10.41 270.00 90.00 W
1DEE26 NONRES_EXT_WALL 0.30 0.278 0.290 37.16 28.24 180.00 90.00 S
FLOOR 3 UNDEVELOPED 2 ROOF NONRES_ROOF 0.30 0.159 0.163 107.02 107.02 180.00 0.00  
FLOOR 3 UTILITY ROOF NONRES_ROOF 0.30 0.159 0.163 20.07 20.07 0.00 0.00  
C86329 NONRES_EXT_WALL 0.30 0.278 0.290 38.09 29.17 90.00 90.00 E
FLOOR 3 WORK ROOF NONRES_ROOF 0.30 0.159 0.163 53.33 53.33 90.00 0.00  
DFC6F0 NONRES_EXT_WALL 0.30 0.278 0.290 19.51 18.77 90.00 90.00 E
88E360 NONRES_EXT_WALL 0.30 0.278 0.290 66.89 51.71 0.00 90.00 N
E7B55F NONRES_EXT_WALL 0.30 0.278 0.290 11.15 11.15 180.00 90.00 S
NE STAIR ROOF NONRES_ROOF 0.30 0.159 0.163 15.61 15.61 0.00 0.00  
FB3814 NONRES_EXT_WALL 0.30 0.278 0.290 19.51 17.56 180.00 90.00 S
FCD12D NONRES_EXT_WALL 0.30 0.278 0.290 55.74 53.79 270.00 90.00 W
NW ELEVATOR ROOF NONRES_ROOF 0.30 0.159 0.163 13.01 13.01 90.00 0.00  
5507DC NONRES_EXT_WALL 0.30 0.278 0.290 22.30 20.35 270.00 90.00 W
2E2D0C NONRES_EXT_WALL 0.30 0.278 0.290 66.89 53.79 0.00 90.00 N
AF0124 NONRES_EXT_WALL 0.30 0.278 0.290 22.30 22.30 90.00 90.00 E
NW STAIR ROOF NONRES_ROOF 0.30 0.159 0.163 17.84 17.84 270.00 0.00  
850EA7 NONRES_EXT_WALL 0.30 0.278 0.290 33.45 32.33 180.00 90.00 S
270BCE NONRES_EXT_WALL 0.30 0.278 0.290 22.30 20.35 270.00 90.00 W
SW STAIR ROOF NONRES_ROOF 0.30 0.159 0.163 8.92 8.92 180.00 0.00  
FLOOR 1 ANESTHESIA SLAB FLOOR1ANESTHESIASLAB_FFACTOR 1.00   0.251 10.03 10.03 0.00 180.00  
FLOOR 1 CAFE SLAB FLOOR1CAFESLAB_FFACTOR 1.00   0.141 39.02 39.02 90.00 180.00  
FLOOR 1 DRESSING ROOM SLAB FLOOR1DRESSINGROOMSLAB_FFACTOR 1.00   0.636 4.18 4.18 0.00 180.00  
FLOOR 1 ELECTRICAL ROOM SLAB FLOOR1ELECTRICALROOMSLAB_FFACTOR 1.00   0.214 9.10 9.10 0.00 180.00  
FLOOR 1 ELEVATOR PUMP ROOM SLAB FLOOR1ELEVATORPUMPROOMSLAB_FFACTOR 1.00   0.706 8.45 8.45 180.00 180.00  
FLOOR 1 LOBBY SLAB FLOOR1LOBBYSLAB_FFACTOR 1.00   0.104 57.79 57.79 90.00 180.00  
FLOOR 1 LOBBY TOILET SLAB FLOOR1LOBBYTOILETSLAB_FFACTOR 1.00   0.339 5.02 5.02 0.00 180.00  
FLOOR 1 LOCKER ROOM SLAB FLOOR1LOCKERROOMSLAB_FFACTOR 1.00   0.098 61.32 61.32 270.00 180.00  
FLOOR 1 MED GAS SLAB FLOOR1MEDGASSLAB_FFACTOR 1.00   0.882 5.20 5.20 180.00 180.00  
FLOOR 1 MRI CONTROL ROOM SLAB FLOOR1MRICONTROLROOMSLAB_FFACTOR 1.00   0.087 15.61 15.61 180.00 180.00  
FLOOR 1 MRI TOILET SLAB FLOOR1MRITOILETSLAB_FFACTOR 1.00   0.339 5.02 5.02 90.00 180.00  
FLOOR 1 OPERATING ROOM 1 SLAB FLOOR1OPERATINGROOM1SLAB_FFACTOR 1.00   0.283 42.74 42.74 0.00 180.00  
FLOOR 1 OPERATING ROOM 2 SLAB FLOOR1OPERATINGROOM2SLAB_FFACTOR 1.00   0.148 44.59 44.59 0.00 180.00  
FLOOR 1 PRE-OP ROOM 1 SLAB FLOOR1PRE-OPROOM1SLAB_FFACTOR 1.00   0.062 17.56 17.56 90.00 180.00  
FLOOR 1 PRE-OP TOILET SLAB FLOOR1PRE-OPTOILETSLAB_FFACTOR 1.00   0.339 5.02 5.02 270.00 180.00  
FLOOR 1 PROCEDURE ROOM SLAB FLOOR1PROCEDUREROOMSLAB_FFACTOR 1.00   0.199 26.48 26.48 270.00 180.00  
FLOOR 1 RECEPTION SLAB FLOOR1RECEPTIONSLAB_FFACTOR 1.00   0.075 47.29 47.29 270.00 180.00  
FLOOR 1 RECOVERY ROOM SLAB FLOOR1RECOVERYROOMSLAB_FFACTOR 1.00   0.251 50.17 50.17 90.00 180.00  
FLOOR 1 SCHEDULING SLAB FLOOR1SCHEDULINGSLAB_FFACTOR 1.00   0.175 11.06 11.06 90.00 180.00  
FLOOR 1 STEP DOWN SLAB FLOOR1STEPDOWNSLAB_FFACTOR 1.00   0.378 27.87 27.87 270.00 180.00  
FLOOR 1 STERILE HALL SLAB FLOOR1STERILEHALLSLAB_FFACTOR 1.00   0.038 57.23 57.23 270.00 180.00  
FLOOR 1 STORAGE SLAB FLOOR1STORAGESLAB_FFACTOR 1.00   0.205 85.47 85.47 270.00 180.00  
FLOOR 1 SUB-STERILE SLAB FLOOR1SUB-STERILESLAB_FFACTOR 1.00   0.214 18.21 18.21 180.00 180.00  
FLOOR 1 UTILITY HALL SLAB FLOOR1UTILITYHALLSLAB_FFACTOR 1.00   0.186 23.78 23.78 90.00 180.00  
FLOOR 1 UTILITY ROOM SLAB FLOOR1UTILITYROOMSLAB_FFACTOR 1.00   0.148 33.45 33.45 180.00 180.00  
FLOOR 1 VESTIBULE SLAB FLOOR1VESTIBULESLAB_FFACTOR 1.00   0.339 6.69 6.69 90.00 180.00  
NE STAIR SLAB NESTAIRSLAB_FFACTOR 1.00   0.666 15.61 15.61 0.00 180.00  
NW ELEVATOR SLAB NWELEVATORSLAB_FFACTOR 1.00   0.612 13.01 13.01 90.00 180.00  
NW STAIR SLAB NWSTAIRSLAB_FFACTOR 1.00   0.666 17.84 17.84 270.00 180.00  
SW STAIR SLAB SWSTAIRSLAB_FFACTOR 1.00   0.666 8.92 8.92 270.00 180.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
78F987 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 481E71 180.00 90.00 S
D8037E NONRESWINDOW_U_0.29_SHGC_0.4 8.92 0.00 0.00 8.92 8.92 1.647 0.395 0.441     No 5F762C 180.00 90.00 S
4A8120 NONRESWINDOW_U_0.29_SHGC_0.4 2.32 0.00 0.00 2.32 2.32 1.647 0.395 0.441     No 84FB73 0.00 90.00 N
AAE778 NONRESWINDOW_U_0.29_SHGC_0.4 8.92 0.00 0.00 8.92 8.92 1.647 0.395 0.441     No FE5A3C 270.00 90.00 W
3AAD8B NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No F629C1 0.00 90.00 N
8128A9 NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No F629C1 0.00 90.00 N
9B1541 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 879583 180.00 90.00 S
CF850A NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 879583 180.00 90.00 S
A6BA23 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No E326E4 90.00 90.00 E
D10D28 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No E326E4 90.00 90.00 E
591336 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 1D96D7 90.00 90.00 E
38B811 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 1D96D7 90.00 90.00 E
C044D6 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 1D96D7 90.00 90.00 E
1D94BE NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 6D2616 0.00 90.00 N
18748E NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 6D2616 0.00 90.00 N
137A56 NONRESWINDOW_U_0.29_SHGC_0.4 3.34 0.00 0.00 3.34 3.34 1.647 0.395 0.441     No A5A6A3 180.00 90.00 S
8D508E NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 28B002 180.00 90.00 S
B2D381 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 28B002 180.00 90.00 S
1DA13A NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 28B002 180.00 90.00 S
44E54A NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 28B002 180.00 90.00 S
757D10 NONRESWINDOW_U_0.29_SHGC_0.4 0.74 0.00 0.00 0.74 0.74 1.647 0.395 0.441     No EA6DC8 180.00 90.00 S
E33BAE NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No B40F89 270.00 90.00 W
24167A NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 997723 180.00 90.00 S
2C0938 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 997723 180.00 90.00 S
8600DD NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No CEC7BD 180.00 90.00 S
A1ED60 NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 859BC1 0.00 90.00 N
E8D997 NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 859BC1 0.00 90.00 N
88E1FC NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 859BC1 0.00 90.00 N
F83F33 NONRESWINDOW_U_0.29_SHGC_0.4 2.97 0.00 0.00 2.97 2.97 1.647 0.395 0.441     No 61E610 90.00 90.00 E
B1F5EE NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No D95F04 90.00 90.00 E
F52F3D NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 208CCF 90.00 90.00 E
80885D NONRESWINDOW_U_0.29_SHGC_0.4 6.69 0.00 0.00 6.69 6.69 1.647 0.395 0.441     No AEF992 180.00 90.00 S
FEEF06 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 54D065 180.00 90.00 S
2BE8DE NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 1775A6 270.00 90.00 W
513E2A NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 1775A6 270.00 90.00 W
BA5CD9 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 1775A6 270.00 90.00 W
1AD478 NONRESWINDOW_U_0.29_SHGC_0.4 3.72 0.00 0.00 3.72 3.72 1.647 0.395 0.441     No 97F00A 180.00 90.00 S
27F0AC NONRESWINDOW_U_0.29_SHGC_0.4 5.95 0.00 0.00 5.95 5.95 1.647 0.395 0.441     No A497E9 180.00 90.00 S
724114 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 88A75F 180.00 90.00 S
D538C4 NONRESWINDOW_U_0.29_SHGC_0.4 2.97 0.00 0.00 2.97 2.97 1.647 0.395 0.441     No B4E619 90.00 90.00 E
5635BC NONRESWINDOW_U_0.29_SHGC_0.4 2.97 0.00 0.00 2.97 2.97 1.647 0.395 0.441     No B4E619 90.00 90.00 E
831C1D NONRESWINDOW_U_0.29_SHGC_0.4 4.18 0.00 0.00 4.18 4.18 1.647 0.395 0.441     No 9EC269 0.00 90.00 N
9BB95F NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No B316F7 0.00 90.00 N
C0778D NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No B316F7 0.00 90.00 N
7D2D69 NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 9621FD 0.00 90.00 N
2EF63B NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 9621FD 0.00 90.00 N
C417C0 NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 42CEE1 0.00 90.00 N
EB042B NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 4B1439 90.00 90.00 E
4C1F71 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 4B1439 90.00 90.00 E
D23C8B NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 4B1439 90.00 90.00 E
B4E4BE NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 4B1439 90.00 90.00 E
EEF55D NONRESWINDOW_U_0.29_SHGC_0.4 6.69 0.00 0.00 6.69 6.69 1.647 0.395 0.441     No 4ABC66 180.00 90.00 S
E55A57 NONRESWINDOW_U_0.29_SHGC_0.4 3.34 0.00 0.00 3.34 3.34 1.647 0.395 0.441     No 4ABC66 180.00 90.00 S
93D018 NONRESWINDOW_U_0.29_SHGC_0.4 6.69 0.00 0.00 6.69 6.69 1.647 0.395 0.441     No 5B04CF 270.00 90.00 W
DD9F5D NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No 4B55FA 90.00 90.00 E
15B02B NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 9C3A6A 0.00 90.00 N
820282 NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 9C3A6A 0.00 90.00 N
9BA05A NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 68A2D7 0.00 90.00 N
C639E8 NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 68A2D7 0.00 90.00 N
A2790A NONRESWINDOW_U_0.29_SHGC_0.4 4.18 0.00 0.00 4.18 4.18 1.647 0.395 0.441     No CE3FEF 0.00 90.00 N
79FCEE NONRESWINDOW_U_0.29_SHGC_0.4 2.97 0.00 0.00 2.97 2.97 1.647 0.395 0.441     No CE618F 90.00 90.00 E
EDE617 NONRESWINDOW_U_0.29_SHGC_0.4 2.97 0.00 0.00 2.97 2.97 1.647 0.395 0.441     No CE618F 90.00 90.00 E
C61F0D NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 5ADC59 0.00 90.00 N
7248C5 NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 5ADC59 0.00 90.00 N
29FA28 NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 5ADC59 0.00 90.00 N
F0B23F NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 5ADC59 0.00 90.00 N
EEC10E NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 5ADC59 0.00 90.00 N
944FCE NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 5ADC59 0.00 90.00 N
C41399 NONRESWINDOW_U_0.29_SHGC_0.4 2.79 0.00 0.00 2.79 2.79 1.647 0.395 0.441     No 5ADC59 0.00 90.00 N
95BA33 NONRESWINDOW_U_0.29_SHGC_0.4 3.34 0.00 0.00 3.34 3.34 1.647 0.395 0.441     No D22917 90.00 90.00 E
F27282 NONRESWINDOW_U_0.29_SHGC_0.4 3.34 0.00 0.00 3.34 3.34 1.647 0.395 0.441     No D22917 90.00 90.00 E
3DB407 NONRESWINDOW_U_0.29_SHGC_0.4 5.57 0.00 0.00 5.57 5.57 1.647 0.395 0.441     No C1BC97 180.00 90.00 S
3DADE2 NONRESWINDOW_U_0.29_SHGC_0.4 5.57 0.00 0.00 5.57 5.57 1.647 0.395 0.441     No C1BC97 180.00 90.00 S
DF3E2C NONRESWINDOW_U_0.29_SHGC_0.4 5.57 0.00 0.00 5.57 5.57 1.647 0.395 0.441     No C1BC97 180.00 90.00 S
5031C8 NONRESWINDOW_U_0.29_SHGC_0.4 5.57 0.00 0.00 5.57 5.57 1.647 0.395 0.441     No C1BC97 180.00 90.00 S
C087D0 NONRESWINDOW_U_0.29_SHGC_0.4 5.57 0.00 0.00 5.57 5.57 1.647 0.395 0.441     No 8DA7DB 180.00 90.00 S
D2CA75 NONRESWINDOW_U_0.29_SHGC_0.4 5.57 0.00 0.00 5.57 5.57 1.647 0.395 0.441     No 8DA7DB 180.00 90.00 S
B0FB49 NONRESWINDOW_U_0.29_SHGC_0.4 4.46 0.00 0.00 4.46 4.46 1.647 0.395 0.441     No 8DA7DB 180.00 90.00 S
FE9BC9 NONRESWINDOW_U_0.29_SHGC_0.4 3.34 0.00 0.00 3.34 3.34 1.647 0.395 0.441     No 38B339 270.00 90.00 W
9DF7DE NONRESWINDOW_U_0.29_SHGC_0.4 3.34 0.00 0.00 3.34 3.34 1.647 0.395 0.441     No 38B339 270.00 90.00 W
D0BE44 NONRESWINDOW_U_0.29_SHGC_0.4 3.34 0.00 0.00 3.34 3.34 1.647 0.395 0.441     No 38B339 270.00 90.00 W
6B5226 NONRESWINDOW_U_0.29_SHGC_0.4 4.46 0.00 0.00 4.46 4.46 1.647 0.395 0.441     No BE5F2F 270.00 90.00 W
8F59F7 NONRESWINDOW_U_0.29_SHGC_0.4 4.46 0.00 0.00 4.46 4.46 1.647 0.395 0.441     No 1DEE26 180.00 90.00 S
44F571 NONRESWINDOW_U_0.29_SHGC_0.4 4.46 0.00 0.00 4.46 4.46 1.647 0.395 0.441     No 1DEE26 180.00 90.00 S
6BD844 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No C86329 90.00 90.00 E
86D536 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No C86329 90.00 90.00 E
BAF71D NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No C86329 90.00 90.00 E
3833A2 NONRESWINDOW_U_0.29_SHGC_0.4 2.23 0.00 0.00 2.23 2.23 1.647 0.395 0.441     No C86329 90.00 90.00 E
2111A1 NONRESWINDOW_U_0.29_SHGC_0.4 0.74 0.00 0.00 0.74 0.74 1.647 0.395 0.441     No DFC6F0 90.00 90.00 E
9BC521 NONRESWINDOW_U_0.29_SHGC_0.4 5.71 0.00 0.00 5.71 5.71 1.647 0.395 0.441     No 88E360 0.00 90.00 N
142781 NONRESWINDOW_U_0.29_SHGC_0.4 5.57 0.00 0.00 5.57 5.57 1.647 0.395 0.441     No 88E360 0.00 90.00 N
E74902 NONRESWINDOW_U_0.29_SHGC_0.4 5.57 0.00 0.00 5.57 5.57 1.647 0.395 0.441     No 2E2D0C 0.00 90.00 N
93BBC3 NONRESWINDOW_U_0.29_SHGC_0.4 5.57 0.00 0.00 5.57 5.57 1.647 0.395 0.441     No 2E2D0C 0.00 90.00 N
C635A6 NONRESWINDOW_U_0.29_SHGC_0.4 1.11 0.00 0.00 1.11 1.11 1.647 0.395 0.441     No 850EA7 180.00 90.00 S
Total or Average           308.29 1.647 0.395 0.441              
North Total or Average           97.22 1.647 0.395 0.441              
Non-North Total or Average           211.08 1.647 0.395 0.441              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
BA05F7 SWINGING DOOR_CON 1.598 2.101 1.95 E02487
F67E1F SWINGING DOOR_CON 1.598 2.101 1.95 FE5A3C
7EB6E7 SWINGING DOOR_CON 1.598 2.101 1.95 E85BB5
D18914 SWINGING DOOR_CON 1.598 2.101 1.95 C114C1
D4B39B SWINGING DOOR_CON 1.598 2.101 1.95 E326E4
D2D3BC SWINGING DOOR_CON 1.598 2.101 1.95 28B002
C528DA SWINGING DOOR_CON 1.598 2.101 1.95 28B002
EFD3F9 SWINGING DOOR_CON 1.598 2.101 1.95 28B002
62B5AF SWINGING DOOR_CON 1.598 2.101 1.95 997723
71E924 SWINGING DOOR_CON 1.598 2.101 2.97 8E5BB9
3C44F9 SWINGING DOOR_CON 1.598 2.101 1.95 859BC1
49526E SWINGING DOOR_CON 1.598 2.101 1.95 859BC1
865AE8 SWINGING DOOR_CON 1.598 2.101 1.95 859BC1
5E66D1 OVERHEAD DOOR_CON 1.394 1.761 7.43 529072
E14DAE SWINGING DOOR_CON 1.598 2.101 1.95 D95F04
84A1D5 SWINGING DOOR_CON 1.598 2.101 1.95 3330D8
9CB8E5 SWINGING DOOR_CON 1.598 2.101 1.95 88E360
E4A528 SWINGING DOOR_CON 1.598 2.101 1.95 88E360
24BAF7 SWINGING DOOR_CON 1.598 2.101 1.95 FB3814
19E57D SWINGING DOOR_CON 1.598 2.101 1.95 FCD12D
EDE769 SWINGING DOOR_CON 1.598 2.101 1.95 5507DC
1C9872 SWINGING DOOR_CON 1.598 2.101 1.95 2E2D0C
F402E9 SWINGING DOOR_CON 1.598 2.101 1.95 270BCE



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
78F987 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
D8037E 0.00 1.00 1.00 0.57 1.00 1.00 0.35 1.00 1.00
4A8120 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AAE778 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
3AAD8B 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
8128A9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
9B1541 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CF850A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
A6BA23 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
D10D28 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
591336 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
38B811 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
C044D6 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
1D94BE 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
18748E 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
137A56 0.00 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
8D508E 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
B2D381 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
1DA13A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
44E54A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
757D10 0.00 0.00 1.00 0.00 0.45 1.00 0.00 0.53 1.00
E33BAE 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
24167A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
2C0938 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
8600DD 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
A1ED60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
E8D997 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
88E1FC 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F83F33 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
B1F5EE 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F52F3D 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
80885D 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FEEF06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
2BE8DE 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
513E2A 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
BA5CD9 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
1AD478 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
27F0AC 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
724114 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
D538C4 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
5635BC 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
831C1D 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
9BB95F 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
C0778D 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
7D2D69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
2EF63B 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
C417C0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
EB042B 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
4C1F71 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
D23C8B 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
B4E4BE 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
EEF55D 0.18 1.00 1.00 1.00 1.00 1.00 0.35 1.00 1.00
E55A57 0.00 1.00 1.00 0.25 1.00 1.00 0.00 1.00 1.00
93D018 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
DD9F5D 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
15B02B 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
820282 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
9BA05A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
C639E8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
A2790A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
79FCEE 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
EDE617 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
C61F0D 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
7248C5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
29FA28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F0B23F 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
EEC10E 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
944FCE 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
C41399 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
95BA33 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F27282 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
3DB407 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
3DADE2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
DF3E2C 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
5031C8 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
C087D0 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
D2CA75 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
B0FB49 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
FE9BC9 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
9DF7DE 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
D0BE44 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
6B5226 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
8F59F7 1.00 1.00 1.00 1.00 1.00 1.00 0.58 1.00 1.00
44F571 0.55 1.00 1.00 0.93 1.00 1.00 0.00 1.00 1.00
6BD844 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
86D536 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
BAF71D 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
3833A2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
2111A1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
9BC521 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
142781 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
E74902 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
93BBC3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
C635A6 0.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
FLOOR 1 ANESTHESIA_LIGHTS FLOOR 1 ANESTHESIA 15.0695 10.03 151.20 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 2.06
FLOOR 1 BIO HAZ_LIGHTS FLOOR 1 BIO HAZ 4.0903 5.20 21.28 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 0.19
FLOOR 1 CAFE_LIGHTS FLOOR 1 CAFE 4.3056 39.02 168.00 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 2.29
FLOOR 1 CLEAN_LIGHTS FLOOR 1 CLEAN 15.0695 11.71 176.40 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 2.41
FLOOR 1 CLEAN WORK_LIGHTS FLOOR 1 CLEAN WORK 15.0695 15.33 231.00 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 3.15
FLOOR 1 DICTATION_LIGHTS FLOOR 1 DICTATION 7.9653 11.71 93.24 LightsWired BLDG_LIGHT_OFFICE_SCH 64.18 168.00 62.57 0.0000 Y 1.10
FLOOR 1 DRESSING ROOM_LIGHTS FLOOR 1 DRESSING ROOM 7.9653 4.18 33.30 LightsWired BLDG_LIGHT_OFFICE_SCH 64.18 168.00 62.57 0.0000 Y 0.39
FLOOR 1 ELECTRICAL ROOM_LIGHTS FLOOR 1 ELECTRICAL ROOM 15.0695 9.10 137.20 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 1.87
FLOOR 1 ELEVATOR PUMP ROOM_LIGHTS FLOOR 1 ELEVATOR PUMP ROOM 15.0695 8.45 127.40 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 1.74
FLOOR 1 HUMID_LIGHTS FLOOR 1 HUMID 7.9653 5.02 39.96 LightsWired BLDG_LIGHT_OFFICE_SCH 64.18 168.00 62.57 0.0000 Y 0.47
FLOOR 1 IT HALL_LIGHTS FLOOR 1 IT HALL 5.2958 13.01 68.88 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 0.89
FLOOR 1 IT ROOM_LIGHTS FLOOR 1 IT ROOM 7.9653 10.41 82.88 LightsWired BLDG_LIGHT_OFFICE_SCH 64.18 168.00 62.57 0.0000 Y 0.97
FLOOR 1 LOBBY_LIGHTS FLOOR 1 LOBBY 9.0417 57.79 522.48 LightsWired BLDG_LIGHT_LOBBYFLR1_SCH 70.85 168.00 69.05 0.0000 Y 6.77
FLOOR 1 LOBBY HALL_LIGHTS FLOOR 1 LOBBY HALL 5.2958 22.30 118.08 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 1.53
FLOOR 1 LOBBY TOILET_LIGHTS FLOOR 1 LOBBY TOILET 6.7813 5.02 34.02 LightsWired BLDG_LIGHT_TOILET_SCH 49.22 168.00 47.97 0.0000 Y 0.31
FLOOR 1 LOCKER ROOM_LIGHTS FLOOR 1 LOCKER ROOM 6.3507 61.32 389.40 LightsWired BLDG_LIGHT_LOCKER_SCH 74.58 168.00 72.68 0.0000 Y 5.31
FLOOR 1 LOCKER ROOM HALL_LIGHTS FLOOR 1 LOCKER ROOM HALL 5.2958 46.08 244.03 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 3.17
FLOOR 1 LOUNGE_LIGHTS FLOOR 1 LOUNGE 6.3507 33.45 212.40 LightsWired BLDG_LIGHT_LOUNGE_SCH 74.58 168.00 72.68 0.0000 Y 2.90
FLOOR 1 MED GAS_LIGHTS FLOOR 1 MED GAS 4.0903 5.20 21.28 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 0.19
FLOOR 1 MRI CONTROL ROOM_LIGHTS FLOOR 1 MRI CONTROL ROOM 10.1181 15.61 157.92 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 2.15
FLOOR 1 MRI HALL_LIGHTS FLOOR 1 MRI HALL 5.2958 13.66 72.32 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 0.94
FLOOR 1 MRI ROOM_LIGHTS FLOOR 1 MRI ROOM 10.1181 40.88 413.60 LightsWired BLDG_LIGHT_EXAM_SCH 58.17 168.00 56.69 0.0000 Y 4.40
FLOOR 1 MRI TOILET_LIGHTS FLOOR 1 MRI TOILET 6.7813 5.02 34.02 LightsWired BLDG_LIGHT_TOILET_SCH 49.22 168.00 47.97 0.0000 Y 0.31
FLOOR 1 NOURISHMENT_LIGHTS FLOOR 1 NOURISHMENT 12.5938 16.91 212.94 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 2.91
FLOOR 1 NURSE HALL_LIGHTS FLOOR 1 NURSE HALL 5.2958 46.08 244.03 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 3.17
FLOOR 1 NURSE JANITOR_LIGHTS FLOOR 1 NURSE JANITOR 4.0903 5.02 20.52 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 0.19
FLOOR 1 NURSE STATION_LIGHTS FLOOR 1 NURSE STATION 12.5938 24.25 305.37 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 4.17
FLOOR 1 NURSE TOILET_LIGHTS FLOOR 1 NURSE TOILET 6.7813 5.02 34.02 LightsWired BLDG_LIGHT_TOILET_SCH 49.22 168.00 47.97 0.0000 Y 0.31
FLOOR 1 OFFICE_LIGHTS FLOOR 1 OFFICE 7.9653 44.87 357.42 LightsWired BLDG_LIGHT_OFFICE_SCH 64.18 168.00 62.57 0.0000 Y 4.20
FLOOR 1 OPERATING ROOM 1_LIGHTS FLOOR 1 OPERATING ROOM 1 24.3264 42.74 1039.60 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 14.18
FLOOR 1 OPERATING ROOM 2_LIGHTS FLOOR 1 OPERATING ROOM 2 24.3264 44.59 1084.80 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 14.80
FLOOR 1 OPERATING ROOM 3_LIGHTS FLOOR 1 OPERATING ROOM 3 24.3264 44.22 1075.76 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 14.68
FLOOR 1 PACU_LIGHTS FLOOR 1 PACU 13.4549 10.03 135.00 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 1.84
FLOOR 1 PRE-OP HALL_LIGHTS FLOOR 1 PRE-OP HALL 5.2958 49.05 259.78 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 3.37
FLOOR 1 PRE-OP ROOM 1_LIGHTS FLOOR 1 PRE-OP ROOM 1 7.3195 17.56 128.52 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 1.75
FLOOR 1 PRE-OP ROOM 2_LIGHTS FLOOR 1 PRE-OP ROOM 2 7.3195 31.40 229.84 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 3.14
FLOOR 1 PRE-OP TOILET_LIGHTS FLOOR 1 PRE-OP TOILET 6.7813 5.02 34.02 LightsWired BLDG_LIGHT_TOILET_SCH 49.22 168.00 47.97 0.0000 Y 0.31
FLOOR 1 PROCEDURE ROOM_LIGHTS FLOOR 1 PROCEDURE ROOM 15.0695 26.48 399.00 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 5.44
FLOOR 1 RECEPTION_LIGHTS FLOOR 1 RECEPTION 9.0417 47.29 427.56 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 5.83
FLOOR 1 RECEPTION HALL_LIGHTS FLOOR 1 RECEPTION HALL 5.2958 11.89 62.98 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 0.82
FLOOR 1 RECOVERY ROOM_LIGHTS FLOOR 1 RECOVERY ROOM 13.4549 50.17 675.00 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 9.21
FLOOR 1 SCHEDULING_LIGHTS FLOOR 1 SCHEDULING 7.9653 11.06 88.06 LightsWired BLDG_LIGHT_OFFICE_SCH 64.18 168.00 62.57 0.0000 Y 1.03
FLOOR 1 SCRUB_LIGHTS FLOOR 1 SCRUB 5.2958 7.80 41.33 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 0.54
FLOOR 1 SOIL_LIGHTS FLOOR 1 SOIL 15.0695 11.71 176.40 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 2.41
FLOOR 1 SOIL HOLD_LIGHTS FLOOR 1 SOIL HOLD 15.0695 5.20 78.40 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 1.07
FLOOR 1 SOIL WORK_LIGHTS FLOOR 1 SOIL WORK 15.0695 16.72 252.00 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 3.44
FLOOR 1 STEP DOWN_LIGHTS FLOOR 1 STEP DOWN 13.4549 27.87 375.00 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 5.12
FLOOR 1 STERILE HALL_LIGHTS FLOOR 1 STERILE HALL 5.2958 57.23 303.07 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 3.94
FLOOR 1 STERILE STORAGE_LIGHTS FLOOR 1 STERILE STORAGE 4.0903 36.79 150.48 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 1.38
FLOOR 1 STORAGE_LIGHTS FLOOR 1 STORAGE 4.0903 85.47 349.60 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 3.20
FLOOR 1 SUB-STERILE_LIGHTS FLOOR 1 SUB-STERILE 5.2958 18.21 96.43 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 1.25
FLOOR 1 UTILITY HALL_LIGHTS FLOOR 1 UTILITY HALL 5.2958 23.78 125.95 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 1.64
FLOOR 1 UTILITY JANITOR_LIGHTS FLOOR 1 UTILITY JANITOR 4.0903 3.90 15.96 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 0.15
FLOOR 1 UTILITY ROOM_LIGHTS FLOOR 1 UTILITY ROOM 4.0903 33.45 136.80 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 1.25
FLOOR 1 VESTIBULE_LIGHTS FLOOR 1 VESTIBULE 5.2958 6.69 35.42 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 0.46
FLOOR 2 CONFERENCE_LIGHTS FLOOR 2 CONFERENCE 10.4410 31.22 325.92 LightsWired BLDG_LIGHT_SCH 74.58 106.99 25.04 0.0000 Y 1.53
FLOOR 2 CONFERENCE TOILET_LIGHTS FLOOR 2 CONFERENCE TOILET 6.7813 5.95 40.32 LightsWired BLDG_LIGHT_TOILET_SCH 49.22 168.00 47.97 0.0000 Y 0.36
FLOOR 2 DICTATION_LIGHTS FLOOR 2 DICTATION 7.9653 6.50 51.80 LightsWired BLDG_LIGHT_OFFICE_SCH 64.18 168.00 62.57 0.0000 Y 0.61
FLOOR 2 EXAM 1_LIGHTS FLOOR 2 EXAM 1 15.0695 33.45 504.00 LightsWired BLDG_LIGHT_EXAM_SCH 58.17 168.00 56.69 0.0000 Y 5.36
FLOOR 2 EXAM 2_LIGHTS FLOOR 2 EXAM 2 15.0695 50.17 756.00 LightsWired BLDG_LIGHT_EXAM_SCH 58.17 168.00 56.69 0.0000 Y 8.05
FLOOR 2 EXAM 3_LIGHTS FLOOR 2 EXAM 3 15.0695 66.89 1008.00 LightsWired BLDG_LIGHT_EXAM_SCH 58.17 168.00 56.69 0.0000 Y 10.73
FLOOR 2 EXAM 4_LIGHTS FLOOR 2 EXAM 4 15.0695 7.80 117.60 LightsWired BLDG_LIGHT_EXAM_SCH 58.17 168.00 56.69 0.0000 Y 1.25
FLOOR 2 EXAM 5_LIGHTS FLOOR 2 EXAM 5 15.0695 32.52 490.00 LightsWired BLDG_LIGHT_EXAM_SCH 58.17 168.00 56.69 0.0000 Y 5.21
FLOOR 2 EXAM 6_LIGHTS FLOOR 2 EXAM 6 15.0695 20.90 315.00 LightsWired BLDG_LIGHT_EXAM_SCH 58.17 168.00 56.69 0.0000 Y 3.35
FLOOR 2 EXAM 7_LIGHTS FLOOR 2 EXAM 7 15.0695 73.58 1108.80 LightsWired BLDG_LIGHT_EXAM_SCH 58.17 168.00 56.69 0.0000 Y 11.80
FLOOR 2 EXAM 8_LIGHTS FLOOR 2 EXAM 8 15.0695 25.08 378.00 LightsWired BLDG_LIGHT_EXAM_SCH 58.17 168.00 56.69 0.0000 Y 4.02
FLOOR 2 EXAM 9_LIGHTS FLOOR 2 EXAM 9 15.0695 36.79 554.40 LightsWired BLDG_LIGHT_EXAM_SCH 58.17 168.00 56.69 0.0000 Y 5.90
FLOOR 2 EXAM HALL 1_LIGHTS FLOOR 2 EXAM HALL 1 5.2958 16.72 88.56 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 1.15
FLOOR 2 EXAM HALL 2_LIGHTS FLOOR 2 EXAM HALL 2 5.2958 16.72 88.56 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 1.15
FLOOR 2 EXAM HALL 3_LIGHTS FLOOR 2 EXAM HALL 3 5.2958 16.72 88.56 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 1.15
FLOOR 2 EXAM HALL 4_LIGHTS FLOOR 2 EXAM HALL 4 5.2958 18.39 97.42 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 1.27
FLOOR 2 EXAM HALL 5_LIGHTS FLOOR 2 EXAM HALL 5 5.2958 18.39 97.42 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 1.27
FLOOR 2 EXAM HALL 6_LIGHTS FLOOR 2 EXAM HALL 6 5.2958 18.39 97.42 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 1.27
FLOOR 2 JANITOR_LIGHTS FLOOR 2 JANITOR 4.0903 5.85 23.94 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 0.22
FLOOR 2 LOUNGE_LIGHTS FLOOR 2 LOUNGE 6.3507 7.43 47.20 LightsWired BLDG_LIGHT_LOUNGE_SCH 74.58 168.00 72.68 0.0000 Y 0.64
FLOOR 2 NURSE STATION 1_LIGHTS FLOOR 2 NURSE STATION 1 12.5938 13.94 175.50 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 2.39
FLOOR 2 NURSE STATION 2_LIGHTS FLOOR 2 NURSE STATION 2 12.5938 16.72 210.60 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 2.87
FLOOR 2 OFFICE_LIGHTS FLOOR 2 OFFICE 7.9653 52.03 414.40 LightsWired BLDG_LIGHT_OFFICE_SCH 64.18 122.35 23.68 0.0000 Y 1.84
FLOOR 2 OFFICE HALL_LIGHTS FLOOR 2 OFFICE HALL 5.2958 41.25 218.45 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 2.84
FLOOR 2 RECEPTION_LIGHTS FLOOR 2 RECEPTION 9.0417 91.42 826.56 LightsWired BLDG_LIGHT_SCH 74.58 168.00 37.31 0.0000 Y 5.79
FLOOR 2 RECEPTION HALL_LIGHTS FLOOR 2 RECEPTION HALL 5.2958 52.40 277.49 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 3.60
FLOOR 2 RECEPTION TOILET_LIGHTS FLOOR 2 RECEPTION TOILET 6.7813 11.71 79.38 LightsWired BLDG_LIGHT_TOILET_SCH 49.22 168.00 47.97 0.0000 Y 0.71
FLOOR 2 SCHEDULING 1_LIGHTS FLOOR 2 SCHEDULING 1 7.9653 30.10 239.76 LightsWired BLDG_LIGHT_OFFICE_SCH 64.18 168.00 62.57 0.0000 Y 2.82
FLOOR 2 SCHEDULING 2_LIGHTS FLOOR 2 SCHEDULING 2 7.9653 31.77 253.08 LightsWired BLDG_LIGHT_OFFICE_SCH 64.18 168.00 62.57 0.0000 Y 2.97
FLOOR 2 STORAGE 1_LIGHTS FLOOR 2 STORAGE 1 4.0903 5.20 21.28 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 0.19
FLOOR 2 STORAGE 2_LIGHTS FLOOR 2 STORAGE 2 4.0903 11.15 45.60 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 0.42
FLOOR 2 STORAGE 3_LIGHTS FLOOR 2 STORAGE 3 4.0903 13.38 54.72 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 0.50
FLOOR 2 UTILITY_LIGHTS FLOOR 2 UTILITY 4.0903 11.71 47.88 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 0.44
FLOOR 2 WORK_LIGHTS FLOOR 2 WORK 7.9653 157.01 1250.60 LightsWired BLDG_LIGHT_OFFICE_SCH 64.18 168.00 62.57 0.0000 Y 14.69
FLOOR 2 WORK HALL_LIGHTS FLOOR 2 WORK HALL 5.2958 77.48 410.33 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 5.33
FLOOR 2 WORK TOILET_LIGHTS FLOOR 2 WORK TOILET 6.7813 5.02 34.02 LightsWired BLDG_LIGHT_TOILET_SCH 49.22 168.00 47.97 0.0000 Y 0.31
FLOOR 2 X-RAY_LIGHTS FLOOR 2 X-RAY 10.1181 83.61 846.00 LightsWired BLDG_LIGHT_EXAM_SCH 58.17 168.00 56.69 0.0000 Y 9.00
FLOOR 3 DRESSING ROOM_LIGHTS FLOOR 3 DRESSING ROOM 7.9653 3.90 31.08 LightsWired BLDG_LIGHT_OFFICE_SCH 64.18 168.00 62.57 0.0000 Y 0.37
FLOOR 3 ELEVATOR HALL_LIGHTS FLOOR 3 ELEVATOR HALL 5.2958 34.37 182.04 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 2.36
FLOOR 3 HUMID_LIGHTS FLOOR 3 HUMID 7.9653 10.03 79.92 LightsWired BLDG_LIGHT_OFFICE_SCH 64.18 168.00 62.57 0.0000 Y 0.94
FLOOR 3 JANITOR_LIGHTS FLOOR 3 JANITOR 4.0903 5.85 23.94 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 0.22
FLOOR 3 LOCKER_LIGHTS FLOOR 3 LOCKER 6.3507 11.15 70.80 LightsWired BLDG_LIGHT_LOCKER_SCH 74.58 168.00 72.68 0.0000 Y 0.97
FLOOR 3 LOUNGE_LIGHTS FLOOR 3 LOUNGE 6.3507 70.51 447.81 LightsWired BLDG_LIGHT_LOUNGE_SCH 74.58 168.00 49.36 0.0000 Y 4.15
FLOOR 3 LOUNGE TOILET_LIGHTS FLOOR 3 LOUNGE TOILET 6.7813 17.84 120.96 LightsWired BLDG_LIGHT_TOILET_SCH 49.22 168.00 47.97 0.0000 Y 1.09
FLOOR 3 MECHANICAL_LIGHTS FLOOR 3 MECHANICAL 15.0695 32.52 490.00 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 6.69
FLOOR 3 MECHANICAL HALL_LIGHTS FLOOR 3 MECHANICAL HALL 5.2958 27.87 147.60 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 1.92
FLOOR 3 OFFICE_LIGHTS FLOOR 3 OFFICE 7.9653 282.05 2246.64 LightsWired BLDG_LIGHT_OFFICE_SCH 64.18 168.00 49.23 0.0000 Y 20.76
FLOOR 3 OFFICE HALL_LIGHTS FLOOR 3 OFFICE HALL 5.2958 77.48 410.33 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 5.33
FLOOR 3 OFFICE TOILET_LIGHTS FLOOR 3 OFFICE TOILET 6.7813 5.02 34.02 LightsWired BLDG_LIGHT_TOILET_SCH 49.22 168.00 47.97 0.0000 Y 0.31
FLOOR 3 PHYSICAL THERAPY 1_LIGHTS FLOOR 3 PHYSICAL THERAPY 1 9.7952 120.77 1183.00 LightsWired BLDG_LIGHT_EXAM_SCH 58.17 168.00 56.69 0.0000 Y 12.59
FLOOR 3 PHYSICAL THERAPY 2_LIGHTS FLOOR 3 PHYSICAL THERAPY 2 9.7952 55.00 538.72 LightsWired BLDG_LIGHT_EXAM_SCH 58.17 168.00 56.69 0.0000 Y 5.73
FLOOR 3 PHYSICAL THERAPY TOILET_LIGHTS FLOOR 3 PHYSICAL THERAPY TOILET 6.7813 7.80 52.92 LightsWired BLDG_LIGHT_TOILET_SCH 49.22 168.00 47.97 0.0000 Y 0.48
FLOOR 3 STORAGE 1_LIGHTS FLOOR 3 STORAGE 1 4.0903 10.03 41.04 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 0.38
FLOOR 3 STORAGE 2_LIGHTS FLOOR 3 STORAGE 2 4.0903 7.80 31.92 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 0.29
FLOOR 3 TREATMENT_LIGHTS FLOOR 3 TREATMENT 15.0695 44.22 666.40 LightsWired BLDG_LIGHT_SCH 74.58 168.00 72.68 0.0000 Y 9.09
FLOOR 3 UNDEVELOPED 1_LIGHTS FLOOR 3 UNDEVELOPED 1 4.0903 210.70 861.84 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 7.89
FLOOR 3 UNDEVELOPED 2_LIGHTS FLOOR 3 UNDEVELOPED 2 4.0903 107.02 437.76 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 4.01
FLOOR 3 UTILITY_LIGHTS FLOOR 3 UTILITY 4.0903 20.07 82.08 LightsWired BLDG_LIGHT_STORAGE_SCH 50.06 168.00 48.79 0.0000 Y 0.75
FLOOR 3 WORK_LIGHTS FLOOR 3 WORK 7.9653 53.33 424.76 LightsWired BLDG_LIGHT_OFFICE_SCH 64.18 168.00 62.57 0.0000 Y 4.99
NE STAIR_LIGHTS NE STAIR 5.2958 15.61 82.66 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 1.07
NW ELEVATOR_LIGHTS NW ELEVATOR 5.2958 13.01 68.88 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 0.89
NW STAIR_LIGHTS NW STAIR 5.2958 17.84 94.46 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 1.23
SW STAIR_LIGHTS SW STAIR 5.2958 8.92 47.23 LightsWired BLDG_LIGHT_CORRIDOR_SCH 70.99 168.00 69.19 0.0000 Y 0.61
Interior Lighting Total   8.6973 3804.01 33084.72               380.82


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
FLOOR 2 CONFERENCE_DAYLREFPT1 FLOOR 2 CONFERENCE FLOOR 2 CONFERENCE_DAYLCTRL SplitFlux Continuous/Off 0.67 325.92 218.37
FLOOR 2 CONFERENCE_DAYLREFPT2 FLOOR 2 CONFERENCE FLOOR 2 CONFERENCE_DAYLCTRL SplitFlux Continuous/Off 0.33 325.92 107.55
FLOOR 2 OFFICE_DAYLREFPT1 FLOOR 2 OFFICE FLOOR 2 OFFICE_DAYLCTRL SplitFlux Continuous/Off 0.57 414.40 236.21
FLOOR 2 OFFICE_DAYLREFPT2 FLOOR 2 OFFICE FLOOR 2 OFFICE_DAYLCTRL SplitFlux Continuous/Off 0.43 414.40 178.19
FLOOR 2 RECEPTION_DAYLREFPT1 FLOOR 2 RECEPTION FLOOR 2 RECEPTION_DAYLCTRL SplitFlux Continuous/Off 0.23 826.56 190.11
FLOOR 2 RECEPTION_DAYLREFPT2 FLOOR 2 RECEPTION FLOOR 2 RECEPTION_DAYLCTRL SplitFlux Continuous/Off 0.54 826.56 446.34
FLOOR 3 LOUNGE_DAYLREFPT1 FLOOR 3 LOUNGE FLOOR 3 LOUNGE_DAYLCTRL SplitFlux Continuous/Off 0.24 447.81 107.47
FLOOR 3 LOUNGE_DAYLREFPT2 FLOOR 3 LOUNGE FLOOR 3 LOUNGE_DAYLCTRL SplitFlux Continuous/Off 0.24 447.81 107.47
FLOOR 3 OFFICE_DAYLREFPT1 FLOOR 3 OFFICE FLOOR 3 OFFICE_DAYLCTRL SplitFlux Continuous/Off 0.19 2246.64 426.86
FLOOR 3 OFFICE_DAYLREFPT2 FLOOR 3 OFFICE FLOOR 3 OFFICE_DAYLCTRL SplitFlux Continuous/Off 0.19 2246.64 426.86


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 173.80 AstronomicalClock -   42.55 42.55 1.39
EXTERIOR_LIGHTS_B 1402.00 AstronomicalClock -   83.52 63.04 16.59
EXTERIOR_LIGHTS_C 4148.20 AstronomicalClock -   83.52 47.99 37.37
Exterior Lighting Total 5724.00           55.34



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 100840.74 0.80    


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
AHU-1_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed   176331.53 123094.08 53237.45 0.70 3.40    
AHU-2_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed   220453.16 156315.64 64137.51 0.71 3.40    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
AHU-1_COOLC DXCOIL   171139.0 3.01 10.25 N/A 11.47
AHU-2_COOLC DXCOIL   213709.8 2.99 10.21 N/A 11.40
ANSI/AHRI ratings include supply fan

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
AHU-1_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed                
AHU-2_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL Coil:Heating:Water 656.24 651.64 -
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL Coil:Heating:Water 160.43 159.21 -
FLOOR 1 CAFE VAV BOX REHEAT COIL Coil:Heating:Water 1070.71 1062.96 -
FLOOR 1 CLEAN VAV BOX REHEAT COIL Coil:Heating:Water 302.66 300.27 -
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL Coil:Heating:Water 373.52 370.58 -
FLOOR 1 DICTATION VAV BOX REHEAT COIL Coil:Heating:Water 22.21 22.03 -
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL Coil:Heating:Water 456.74 453.27 -
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL Coil:Heating:Water 131.68 130.76 -
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL Coil:Heating:Water 936.97 930.33 -
FLOOR 1 HUMID VAV BOX REHEAT COIL Coil:Heating:Water 10.68 10.60 -
FLOOR 1 IT HALL VAV BOX REHEAT COIL Coil:Heating:Water 29.65 29.41 -
FLOOR 1 IT ROOM VAV BOX REHEAT COIL Coil:Heating:Water 0.00 0.00 -
FLOOR 1 LOBBY VAV BOX REHEAT COIL Coil:Heating:Water 1943.58 1928.77 -
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL Coil:Heating:Water 67.86 67.33 -
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL Coil:Heating:Water 533.79 530.02 -
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL Coil:Heating:Water 282.82 280.60 -
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL Coil:Heating:Water 102.42 101.62 -
FLOOR 1 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Water 156.74 155.50 -
FLOOR 1 MED GAS VAV BOX REHEAT COIL Coil:Heating:Water 831.02 824.69 -
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL Coil:Heating:Water 172.64 171.28 -
FLOOR 1 MRI HALL VAV BOX REHEAT COIL Coil:Heating:Water 44.47 44.12 -
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL Coil:Heating:Water 441.50 438.03 -
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL Coil:Heating:Water 279.51 277.38 -
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL Coil:Heating:Water 85.80 85.13 -
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL Coil:Heating:Water 135.32 134.25 -
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL Coil:Heating:Water 15.01 14.89 -
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL Coil:Heating:Water 117.08 116.16 -
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL Coil:Heating:Water 92.87 92.13 -
FLOOR 1 OFFICE VAV BOX REHEAT COIL Coil:Heating:Water 66.28 65.76 -
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL Coil:Heating:Water 1072.82 1064.63 -
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL Coil:Heating:Water 0.00 0.00 -
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL Coil:Heating:Water 1850.23 1836.11 -
FLOOR 1 PACU VAV BOX REHEAT COIL Coil:Heating:Water 305.85 303.45 -
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL Coil:Heating:Water 120.64 119.69 -
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL Coil:Heating:Water 535.25 531.03 -
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL Coil:Heating:Water 957.21 949.68 -
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL Coil:Heating:Water 354.49 351.79 -
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL Coil:Heating:Water 2409.63 2390.54 -
FLOOR 1 RECEPTION VAV BOX REHEAT COIL Coil:Heating:Water 0.00 0.00 -
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL Coil:Heating:Water 31.02 30.78 -
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL Coil:Heating:Water 3021.08 2996.80 -
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL Coil:Heating:Water 143.48 142.39 -
FLOOR 1 SCRUB VAV BOX REHEAT COIL Coil:Heating:Water 153.17 152.00 -
FLOOR 1 SOIL VAV BOX REHEAT COIL Coil:Heating:Water 300.96 298.59 -
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL Coil:Heating:Water 0.00 0.00 -
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL Coil:Heating:Water 399.78 396.63 -
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL Coil:Heating:Water 2002.41 1987.92 -
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL Coil:Heating:Water 436.85 433.65 -
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL Coil:Heating:Water 73.12 72.54 -
FLOOR 1 STORAGE VAV BOX REHEAT COIL Coil:Heating:Water 5754.65 5710.81 -
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL Coil:Heating:Water 1044.78 1036.82 -
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL Coil:Heating:Water 1697.90 1684.97 -
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL Coil:Heating:Water 72.07 71.52 -
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL Coil:Heating:Water 1750.46 1737.12 -
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL Coil:Heating:Water 471.10 467.51 -
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL Coil:Heating:Electric   2088.67 1.00
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   552.56 1.00
FLOOR 2 DICTATION VAV BOX REHEAT COIL Coil:Heating:Electric   118.89 1.00
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL Coil:Heating:Electric   3474.26 1.00
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL Coil:Heating:Electric   7196.58 1.00
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL Coil:Heating:Electric   9595.44 1.00
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL Coil:Heating:Electric   893.97 1.00
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL Coil:Heating:Electric   4036.94 1.00
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL Coil:Heating:Electric   2818.66 1.00
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL Coil:Heating:Electric   10554.99 1.00
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL Coil:Heating:Electric   3346.41 1.00
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL Coil:Heating:Electric   5277.49 1.00
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL Coil:Heating:Electric   513.24 1.00
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL Coil:Heating:Electric   323.56 1.00
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL Coil:Heating:Electric   335.30 1.00
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL Coil:Heating:Electric   237.33 1.00
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL Coil:Heating:Electric   237.93 1.00
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL Coil:Heating:Electric   283.92 1.00
FLOOR 2 JANITOR VAV BOX REHEAT COIL Coil:Heating:Electric   661.07 1.00
FLOOR 2 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Electric   216.20 1.00
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL Coil:Heating:Electric   479.72 1.00
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL Coil:Heating:Electric   576.08 1.00
FLOOR 2 OFFICE VAV BOX REHEAT COIL Coil:Heating:Electric   2682.35 1.00
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL Coil:Heating:Electric   833.19 1.00
FLOOR 2 RECEPTION VAV BOX REHEAT COIL Coil:Heating:Electric   4135.99 1.00
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL Coil:Heating:Electric   677.99 1.00
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   1005.89 1.00
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL Coil:Heating:Electric   551.19 1.00
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL Coil:Heating:Electric   580.30 1.00
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL Coil:Heating:Electric   134.34 1.00
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL Coil:Heating:Electric   287.93 1.00
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL Coil:Heating:Electric   345.59 1.00
FLOOR 2 UTILITY VAV BOX REHEAT COIL Coil:Heating:Electric   766.16 1.00
FLOOR 2 WORK VAV BOX REHEAT COIL Coil:Heating:Electric   2868.98 1.00
FLOOR 2 WORK HALL VAV BOX REHEAT COIL Coil:Heating:Electric   1002.27 1.00
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   519.23 1.00
FLOOR 2 X-RAY VAV BOX REHEAT COIL Coil:Heating:Electric   5408.92 1.00
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL Coil:Heating:Electric   181.82 1.00
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL Coil:Heating:Electric   1443.69 1.00
FLOOR 3 HUMID VAV BOX REHEAT COIL Coil:Heating:Electric   394.63 1.00
FLOOR 3 JANITOR VAV BOX REHEAT COIL Coil:Heating:Electric   634.55 1.00
FLOOR 3 LOCKER VAV BOX REHEAT COIL Coil:Heating:Electric   403.57 1.00
FLOOR 3 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Electric   2050.36 1.00
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   1486.41 1.00
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL Coil:Heating:Electric   493.80 1.00
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL Coil:Heating:Electric   1531.87 1.00
FLOOR 3 OFFICE VAV BOX REHEAT COIL Coil:Heating:Electric   8748.53 1.00
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL Coil:Heating:Electric   3136.63 1.00
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   424.31 1.00
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL Coil:Heating:Electric   14035.79 1.00
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL Coil:Heating:Electric   6548.36 1.00
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   690.61 1.00
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL Coil:Heating:Electric   692.63 1.00
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL Coil:Heating:Electric   435.45 1.00
FLOOR 3 TREATMENT VAV BOX REHEAT COIL Coil:Heating:Electric   5138.36 1.00
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL Coil:Heating:Electric   7691.37 1.00
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL Coil:Heating:Electric   5047.39 1.00
FLOOR 3 UTILITY VAV BOX REHEAT COIL Coil:Heating:Electric   892.29 1.00
FLOOR 3 WORK VAV BOX REHEAT COIL Coil:Heating:Electric   2982.53 1.00
NE STAIR VAV BOX REHEAT COIL Coil:Heating:Electric   4551.58 1.00
NW ELEVATOR VAV BOX REHEAT COIL Coil:Heating:Electric   2984.04 1.00
NW STAIR VAV BOX REHEAT COIL Coil:Heating:Electric   4663.85 1.00
SW STAIR VAV BOX REHEAT COIL Coil:Heating:Electric   2276.44 1.00
AHU-1_HEATC Coil:Heating:Water 92954.51 78855.15 -
AHU-1_EXTRAELECHEATC Coil:Heating:Electric   10000000.00 1.00
AHU-1_EXTRAWATERHEATC Coil:Heating:Water 92954.51 78855.15 -
AHU-2_HEATC Coil:Heating:Water 115747.63 98665.72 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
FLOOR 1 ANESTHESIA EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.07 54.61 803.55 1.00 3.34 General    
FLOOR 1 LOBBY TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 4.80 General    
FLOOR 1 MRI CONTROL ROOM EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.16 127.44 803.55 1.00 1.94 General    
FLOOR 1 MRI ROOM EXHAUST FAN Fan:ZoneExhaust 0.39 124.50 0.42 134.30 323.38 1.00 2.18 General    
FLOOR 1 MRI TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 4.80 General    
FLOOR 1 NURSE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 4.80 General    
FLOOR 1 PRE-OP TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 4.80 General    
FLOOR 1 SOIL EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.10 79.63 803.55 1.00 2.57 General    
FLOOR 1 SOIL HOLD EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 35.39 803.55 1.00 4.67 General    
FLOOR 1 SOIL WORK EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.14 113.76 803.55 1.00 2.07 General    
FLOOR 2 CONFERENCE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.05 40.45 803.55 1.00 4.20 General    
FLOOR 2 RECEPTION TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.10 79.63 803.55 1.00 2.57 General    
FLOOR 2 WORK TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 4.80 General    
FLOOR 2 X-RAY EXHAUST FAN Fan:ZoneExhaust 0.39 124.50 0.85 274.71 323.38 1.00 1.75 General    
FLOOR 3 LOUNGE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.15 121.35 803.55 1.00 1.99 General    
FLOOR 3 OFFICE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 4.80 General    
FLOOR 3 PHYSICAL THERAPY TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.07 53.09 803.55 1.00 3.41 General    
AHU-1_FAN Fan:VariableVolume 0.61 1389.42 7.10 16216.46 2283.73 1.00 1.13 General INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
AHU-2_FAN Fan:VariableVolume 0.61 1389.42 9.20 21017.15 2283.73 1.00 1.12 General INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000063 8.07 127739.32 0.30 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 179352.00 0.002208 558.50 252957.60 0.91 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.76 58614.20 0.81 0.00 0.00


VAV DX Cooling Standard Rating Details

DX Cooling Coil Type Assocated Fan Net Cooling Capacity [W] COP [W/W] EER [Btu/W-h] IEER [Btu/W-h] Supply Air Flow 100% [kg/s] COP 75% Capacity [W/W] EER 75% Capacity [Btu/W-h] Supply Air Flow 75% [kg/s] COP 50% Capacity [W/W] EER 50% Capacity [Btu/W-h] Supply Air Flow 50% [kg/s] COP 25% Capacity [W/W] EER 25% Capacity [Btu/W-h] Supply Air Flow 25% [kg/s]
AHU-1_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed None 171139.04 3.01 10.25 11.47 7.8695 3.27 11.17 6.2283 3.48 11.87 4.1745 3.62 12.35 1.7742
AHU-2_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed None 213709.81 2.99 10.21 11.40 10.1991 3.26 11.11 8.0804 3.46 11.79 5.4163 3.61 12.31 2.2749
Indoor-coil-only unit ratings per ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2, with supply fan specific power at 365 {W/1000cfm} (773.3 {W/(m3/s)})


Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
FLOOR 1 ANESTHESIA 641.39 641.39 63.92 0.049 0.049 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 22.20 22.20 0.00915 30.00 0.01270 0.015 0.00
FLOOR 1 CAFE 3862.59 3862.59 98.99 0.296 0.296 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 22.20 22.18 0.01036 29.89 0.01270 0.184 0.00
FLOOR 1 CLEAN 672.34 672.34 57.44 0.050 0.050 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00889 18.82 0.01270 0.018 0.00
FLOOR 1 CLEAN WORK 813.53 813.53 53.07 0.062 0.062 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00919 20.92 0.01270 0.023 0.00
FLOOR 1 DICTATION 495.64 495.64 42.34 0.037 0.037 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00870 18.82 0.01270 0.005 0.00
FLOOR 1 DRESSING ROOM 131.96 131.96 31.56 0.010 0.010 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 22.20 22.20 0.00919 30.10 0.01270 0.002 0.00
FLOOR 1 HUMID 237.68 237.68 47.38 0.018 0.018 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00869 18.82 0.01270 0.002 0.00
FLOOR 1 IT ROOM 362.31 362.31 34.82 0.027 0.027 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00903 18.82 0.01270 0.004 0.00
FLOOR 1 LOBBY 3574.76 3574.76 61.86 0.273 0.273 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 22.20 22.20 0.00884 27.12 0.01270 0.032 0.00
FLOOR 1 LOCKER ROOM 3079.84 3079.84 50.23 0.236 0.236 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 22.20 22.20 0.00909 29.79 0.01270 0.042 0.00
FLOOR 1 LOUNGE 1706.94 1706.94 51.04 0.131 0.131 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00904 20.92 0.01270 0.023 0.00
FLOOR 1 MRI CONTROL ROOM 1880.04 1880.04 120.46 0.144 0.144 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 22.20 22.20 0.00880 28.86 0.01270 0.024 0.00
FLOOR 1 MRI ROOM 4808.07 4808.07 117.62 0.368 0.368 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 22.20 22.20 0.00881 27.54 0.01270 0.062 0.00
FLOOR 1 NOURISHMENT 953.15 953.15 56.37 0.071 0.071 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00890 18.82 0.01270 0.014 0.00
FLOOR 1 NURSE STATION 1274.98 1274.98 52.58 0.098 0.098 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00919 20.92 0.01270 0.020 0.00
FLOOR 1 OFFICE 1488.52 1488.52 33.17 0.110 0.110 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00887 18.82 0.01270 0.019 0.00
FLOOR 1 OPERATING ROOM 1 6218.50 6218.50 145.51 0.704 0.724 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 18.60 18.60 0.00865 24.69 0.01270 0.239 0.00
FLOOR 1 OPERATING ROOM 2 6636.63 6636.63 148.83 0.751 0.755 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 18.60 18.60 0.00863 23.98 0.01270 0.249 0.00
FLOOR 1 OPERATING ROOM 3 5928.73 5928.73 134.07 0.654 0.749 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.60 18.60 0.00857 18.82 0.01270 0.247 0.00
FLOOR 1 PACU 637.58 637.58 63.54 0.048 0.051 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00884 18.82 0.01270 0.032 0.00
FLOOR 1 PRE-OP ROOM 1 751.05 751.05 42.77 0.056 0.089 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00898 18.82 0.01270 0.052 0.00
FLOOR 1 PRE-OP ROOM 2 1417.68 1417.68 45.15 0.106 0.160 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00877 18.82 0.01270 0.093 0.00
FLOOR 1 PROCEDURE ROOM 1605.78 1605.78 60.65 0.123 0.336 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 22.20 22.20 0.00917 30.10 0.01270 0.108 0.00
FLOOR 1 RECEPTION 2404.32 2404.32 50.84 0.184 0.184 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 22.20 22.20 0.00961 29.89 0.01270 0.050 0.00
FLOOR 1 RECOVERY ROOM 3549.60 3549.60 70.75 0.272 0.272 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 22.20 22.20 0.00909 30.00 0.01270 0.161 0.00
FLOOR 1 SCHEDULING 404.78 404.78 36.61 0.030 0.030 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00927 18.82 0.01270 0.005 0.00
FLOOR 1 SOIL 655.51 655.51 56.00 0.050 0.050 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00915 20.92 0.01270 0.018 0.00
FLOOR 1 SOIL HOLD 261.58 261.58 50.28 0.020 0.020 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.19 0.00941 18.82 0.01270 0.008 0.00
FLOOR 1 SOIL WORK 870.72 870.72 52.07 0.067 0.067 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00920 20.92 0.01270 0.025 0.00
FLOOR 1 STEP DOWN 2109.94 2109.94 75.70 0.161 0.161 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 22.20 22.20 0.00909 28.53 0.01270 0.090 0.00
FLOOR 2 CONFERENCE 2449.16 2449.16 78.46 0.221 0.221 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 22.20 22.19 0.00959 29.69 0.01270 0.049 0.00
FLOOR 2 DICTATION 293.65 293.65 45.15 0.026 0.026 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00864 18.82 0.01270 0.003 0.00
FLOOR 2 EXAM 1 2669.89 2669.89 79.83 0.241 0.241 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 22.20 22.20 0.00901 27.95 0.01270 0.051 0.00
FLOOR 2 EXAM 2 2393.13 2393.13 47.70 0.216 0.255 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 22.20 22.20 0.00920 29.69 0.01270 0.076 0.00
FLOOR 2 EXAM 3 3274.76 3274.76 48.96 0.296 0.340 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 22.20 22.20 0.00918 29.69 0.01270 0.102 0.00
FLOOR 2 EXAM 4 547.44 547.44 70.15 0.049 0.049 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 22.20 22.20 0.00904 29.58 0.01270 0.012 0.00
FLOOR 2 EXAM 5 2292.88 2292.88 70.52 0.207 0.207 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 22.20 22.20 0.00902 23.28 0.01270 0.050 0.00
FLOOR 2 EXAM 6 954.64 954.64 45.67 0.086 0.106 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 22.20 22.20 0.00929 30.10 0.01270 0.032 0.00
FLOOR 2 EXAM 7 3037.57 3037.57 41.28 0.274 0.374 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00931 20.92 0.01270 0.112 0.00
FLOOR 2 EXAM 8 1201.97 1201.97 47.92 0.109 0.127 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 22.20 22.20 0.00925 30.10 0.01270 0.038 0.00
FLOOR 2 EXAM 9 1641.34 1641.34 44.61 0.148 0.187 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00925 20.92 0.01270 0.056 0.00
FLOOR 2 LOUNGE 437.59 437.59 58.88 0.039 0.039 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00873 18.82 0.01270 0.005 0.00
FLOOR 2 NURSE STATION 1 698.97 698.97 50.16 0.063 0.063 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00912 20.92 0.01270 0.011 0.00
FLOOR 2 NURSE STATION 2 860.47 860.47 51.46 0.076 0.076 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00887 18.82 0.01270 0.014 0.00
FLOOR 2 OFFICE 2663.99 2663.99 51.21 0.241 0.241 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:40:00 22.20 22.20 0.00877 22.49 0.01270 0.022 0.00
FLOOR 2 RECEPTION 5128.62 5128.62 56.10 0.463 0.463 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 22.20 22.20 0.00939 28.36 0.01270 0.098 0.00
FLOOR 2 SCHEDULING 1 1068.58 1068.58 35.50 0.093 0.093 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00872 18.82 0.01270 0.013 0.00
FLOOR 2 SCHEDULING 2 1180.22 1180.22 37.15 0.103 0.103 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00867 18.82 0.01270 0.014 0.00
FLOOR 2 WORK 4829.76 4829.76 30.76 0.420 0.420 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00883 18.82 0.01270 0.068 0.00
FLOOR 2 X-RAY 9339.09 9339.09 111.69 0.844 0.844 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.20 22.20 0.00878 20.92 0.01270 0.127 0.00
FLOOR 3 DRESSING ROOM 200.41 200.41 51.36 0.018 0.018 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00886 18.82 0.01270 0.002 0.00
FLOOR 3 HUMID 478.06 478.06 47.65 0.042 0.042 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00891 18.82 0.01270 0.004 0.00
FLOOR 3 LOCKER 657.96 657.96 59.02 0.058 0.058 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00893 18.82 0.01270 0.008 0.00
FLOOR 3 LOUNGE 3720.43 3720.43 52.76 0.336 0.336 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 22.20 22.20 0.00894 30.10 0.01270 0.048 0.00
FLOOR 3 OFFICE 8504.04 8504.04 30.15 0.739 0.739 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00875 18.82 0.01270 0.122 0.00
FLOOR 3 PHYSICAL THERAPY 1 7972.16 7972.16 66.01 0.720 0.720 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 22.20 22.20 0.00897 29.58 0.01270 0.184 0.00
FLOOR 3 PHYSICAL THERAPY 2 2702.38 2702.38 49.14 0.244 0.279 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 22.20 22.20 0.00931 30.00 0.01270 0.084 0.00
FLOOR 3 TREATMENT 2243.21 2243.21 50.73 0.203 0.225 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 22.20 22.20 0.00928 30.10 0.01270 0.067 0.00
FLOOR 3 WORK 3233.34 3233.34 60.63 0.292 0.292 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 22.20 22.20 0.00864 22.89 0.01270 0.023 0.00
FLOOR 1 BIO HAZ 105.66 105.66 20.31 0.008 0.008 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.003 0.00
FLOOR 1 ELECTRICAL ROOM 592.62 592.62 65.09 0.045 0.045 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 22.20 22.20 0.00858 26.94 0.01270 0.000 0.00
FLOOR 1 ELEVATOR PUMP ROOM 3937.67 3937.67 465.77 0.298 0.298 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00854 18.82 0.01270 0.000 0.00
FLOOR 1 IT HALL 330.49 330.49 25.41 0.025 0.025 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.004 0.00
FLOOR 1 LOBBY HALL 761.28 761.28 34.14 0.057 0.057 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.007 0.00
FLOOR 1 LOBBY TOILET 479.77 479.77 95.63 0.036 0.036 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00859 18.82 0.01270 0.000 0.00
FLOOR 1 LOCKER ROOM HALL 1150.13 1150.13 24.96 0.085 0.085 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.014 0.00
FLOOR 1 MED GAS 74.95 74.95 14.41 0.006 0.006 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 22.20 22.20 0.00933 30.10 0.01270 0.003 0.00
FLOOR 1 MRI HALL 446.26 446.26 32.68 0.033 0.033 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.004 0.00
FLOOR 1 MRI TOILET 129.47 129.47 25.81 0.010 0.010 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00953 18.82 0.01270 0.000 0.00
FLOOR 1 NURSE HALL 1404.13 1404.13 30.47 0.104 0.104 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.014 0.00
FLOOR 1 NURSE JANITOR 167.49 167.49 33.39 0.013 0.013 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.003 0.00
FLOOR 1 NURSE TOILET 207.29 207.29 41.32 0.015 0.015 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.000 0.00
FLOOR 1 PRE-OP HALL 1356.92 1356.92 27.66 0.101 0.101 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.015 0.00
FLOOR 1 PRE-OP TOILET 150.15 150.15 29.93 0.011 0.011 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 22.20 22.20 0.00876 27.12 0.01270 0.000 0.00
FLOOR 1 RECEPTION HALL 347.67 347.67 29.24 0.026 0.026 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.004 0.00
FLOOR 1 SCRUB 233.95 233.95 29.98 0.018 0.018 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.002 0.00
FLOOR 1 STERILE HALL 1344.61 1344.61 23.50 0.100 0.100 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.017 0.00
FLOOR 1 STERILE STORAGE 822.31 822.31 22.35 0.061 0.061 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.022 0.00
FLOOR 1 STORAGE 1039.51 1039.51 12.16 0.080 0.080 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 22.20 22.20 0.00867 29.03 0.01270 0.052 0.00
FLOOR 1 SUB-STERILE 600.78 600.78 32.99 0.045 0.045 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00914 18.82 0.01270 0.006 0.00
FLOOR 1 UTILITY HALL 477.32 477.32 20.07 0.037 0.037 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:40:00 22.20 22.20 0.00866 22.49 0.01270 0.007 0.00
FLOOR 1 UTILITY JANITOR 116.40 116.40 29.83 0.009 0.009 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.002 0.00
FLOOR 1 UTILITY ROOM 713.17 713.17 21.32 0.053 0.053 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00942 18.82 0.01270 0.020 0.00
FLOOR 1 VESTIBULE 214.73 214.73 32.10 0.016 0.016 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 22.20 22.20 0.00875 27.54 0.01270 0.002 0.00
FLOOR 2 CONFERENCE TOILET 223.39 223.39 37.57 0.020 0.020 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.000 0.00
FLOOR 2 EXAM HALL 1 637.42 637.42 38.12 0.056 0.056 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.005 0.00
FLOOR 2 EXAM HALL 2 632.66 632.66 37.83 0.055 0.055 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.005 0.00
FLOOR 2 EXAM HALL 3 608.74 608.74 36.40 0.053 0.053 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.005 0.00
FLOOR 2 EXAM HALL 4 625.14 625.14 33.98 0.055 0.055 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.006 0.00
FLOOR 2 EXAM HALL 5 655.46 655.46 35.63 0.057 0.057 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.006 0.00
FLOOR 2 EXAM HALL 6 650.87 650.87 35.38 0.057 0.057 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.006 0.00
FLOOR 2 JANITOR 386.72 386.72 66.07 0.034 0.034 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00887 18.82 0.01270 0.004 0.00
FLOOR 2 OFFICE HALL 1509.31 1509.31 36.59 0.132 0.132 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.013 0.00
FLOOR 2 RECEPTION HALL 1959.24 1959.24 37.39 0.171 0.171 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.016 0.00
FLOOR 2 RECEPTION TOILET 407.56 407.56 34.82 0.036 0.036 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.000 0.00
FLOOR 2 STORAGE 1 185.26 185.26 35.61 0.016 0.016 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.003 0.00
FLOOR 2 STORAGE 2 320.68 320.68 28.76 0.028 0.028 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.007 0.00
FLOOR 2 STORAGE 3 416.67 416.67 31.15 0.036 0.036 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.008 0.00
FLOOR 2 UTILITY 593.89 593.89 50.73 0.054 0.054 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:40:00 22.20 22.20 0.00863 22.49 0.01270 0.007 0.00
FLOOR 2 WORK HALL 2655.28 2655.28 34.27 0.232 0.232 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.024 0.00
FLOOR 2 WORK TOILET 209.54 209.54 41.77 0.018 0.018 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00895 18.82 0.01270 0.000 0.00
FLOOR 3 ELEVATOR HALL 889.80 889.80 25.89 0.077 0.077 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.010 0.00
FLOOR 3 JANITOR 152.63 152.63 26.08 0.014 0.014 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 22.20 22.20 0.00869 27.54 0.01270 0.004 0.00
FLOOR 3 LOUNGE TOILET 603.42 603.42 33.83 0.053 0.053 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00856 18.82 0.01270 0.000 0.00
FLOOR 3 MECHANICAL 3557.76 3557.76 109.42 0.321 0.321 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 22.20 22.20 0.00850 23.28 0.01270 0.000 0.00
FLOOR 3 MECHANICAL HALL 1058.25 1058.25 37.97 0.093 0.093 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00904 18.82 0.01270 0.008 0.00
FLOOR 3 OFFICE HALL 2435.70 2435.70 31.44 0.212 0.212 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00850 18.82 0.01270 0.024 0.00
FLOOR 3 OFFICE TOILET 148.13 148.13 29.53 0.013 0.013 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00871 18.82 0.01270 0.000 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 279.29 279.29 35.79 0.024 0.024 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00909 18.82 0.01270 0.000 0.00
FLOOR 3 STORAGE 1 278.89 278.89 27.80 0.025 0.025 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00936 18.82 0.01270 0.006 0.00
FLOOR 3 STORAGE 2 252.22 252.22 32.32 0.022 0.022 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00919 18.82 0.01270 0.005 0.00
FLOOR 3 UNDEVELOPED 1 7478.06 7478.06 35.49 0.675 0.675 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 22.20 22.20 0.00850 28.69 0.01270 0.128 0.00
FLOOR 3 UNDEVELOPED 2 3790.82 3790.82 35.42 0.342 0.342 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 22.20 22.20 0.00851 28.69 0.01270 0.065 0.00
FLOOR 3 UTILITY 413.89 413.89 20.63 0.036 0.036 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.20 22.20 0.00976 18.82 0.01270 0.012 0.00
NE STAIR 1027.76 1027.76 65.85 0.093 0.093 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 22.20 22.20 0.00880 30.10 0.01270 0.005 0.00
NW ELEVATOR 865.17 865.17 66.52 0.078 0.078 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 22.20 22.20 0.00876 27.33 0.01270 0.004 0.00
NW STAIR 1047.66 1047.66 58.73 0.095 0.095 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 22.20 22.20 0.00883 28.69 0.01270 0.005 0.00
SW STAIR 740.69 740.69 83.05 0.067 0.067 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 22.20 22.20 0.00874 28.53 0.01270 0.003 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
FLOOR 1 ANESTHESIA 362.06 362.06 36.09 0.016 0.016 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00755 -32.70 0.00018 0.015 0.00
FLOOR 1 CAFE 713.09 713.09 18.28 0.031 0.184 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.01144 -32.70 0.00018 0.184 0.00
FLOOR 1 CLEAN 0.00 0.00 0.00 0.000 0.018 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.018 0.00
FLOOR 1 CLEAN WORK 0.00 0.00 0.00 0.000 0.023 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.023 0.00
FLOOR 1 DICTATION 0.00 0.00 0.00 0.000 0.005 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.005 0.00
FLOOR 1 DRESSING ROOM 360.49 360.49 86.23 0.016 0.016 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00766 -32.70 0.00018 0.002 0.00
FLOOR 1 HUMID 0.00 0.00 0.00 0.000 0.002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.002 0.00
FLOOR 1 IT ROOM 4.02 4.02 0.39 0.000 0.004 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 21.10 2.32 0.00180 -32.70 0.00018 0.004 0.00
FLOOR 1 LOBBY 1538.97 1538.97 26.63 0.068 0.068 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00739 -32.70 0.00018 0.032 0.00
FLOOR 1 LOCKER ROOM 0.00 0.00 0.00 0.000 0.042 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.042 0.00
FLOOR 1 LOUNGE 0.00 0.00 0.00 0.000 0.023 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.023 0.00
FLOOR 1 MRI CONTROL ROOM 0.00 0.00 0.00 0.000 0.024 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.024 0.00
FLOOR 1 MRI ROOM 0.00 0.00 0.00 0.000 0.062 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.062 0.00
FLOOR 1 NOURISHMENT 0.00 0.00 0.00 0.000 0.014 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.014 0.00
FLOOR 1 NURSE STATION 0.00 0.00 0.00 0.000 0.020 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.020 0.00
FLOOR 1 OFFICE 0.00 0.00 0.00 0.000 0.019 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.019 0.00
FLOOR 1 OPERATING ROOM 1 0.00 0.00 0.00 0.000 0.239 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   18.10 18.10 0.00800 -32.70 0.00018 0.239 0.00
FLOOR 1 OPERATING ROOM 2 2.84 2.84 0.06 0.000 0.249 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:10:00 18.10 4.15 0.00159 -32.70 0.00018 0.249 0.00
FLOOR 1 OPERATING ROOM 3 0.00 0.00 0.00 0.000 0.247 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 18.10 0.00800 -32.70 0.00018 0.247 0.00
FLOOR 1 PACU 0.00 0.00 0.00 0.000 0.032 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.032 0.00
FLOOR 1 PRE-OP ROOM 1 0.00 0.00 0.00 0.000 0.052 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.052 0.00
FLOOR 1 PRE-OP ROOM 2 0.00 0.00 0.00 0.000 0.093 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.093 0.00
FLOOR 1 PROCEDURE ROOM 397.47 397.47 15.01 0.017 0.108 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00663 -32.70 0.00018 0.108 0.00
FLOOR 1 RECEPTION 37.44 37.44 0.79 0.002 0.050 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 21.10 2.29 0.00164 -32.70 0.00018 0.050 0.00
FLOOR 1 RECOVERY ROOM 1604.49 1604.49 31.98 0.071 0.161 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00759 -32.70 0.00018 0.161 0.00
FLOOR 1 SCHEDULING 113.50 113.50 10.27 0.005 0.005 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00448 -32.70 0.00018 0.005 0.00
FLOOR 1 SOIL 0.00 0.00 0.00 0.000 0.018 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.018 0.00
FLOOR 1 SOIL HOLD 2.26 2.26 0.44 0.000 0.008 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 21.10 2.31 0.00180 -32.70 0.00018 0.008 0.00
FLOOR 1 SOIL WORK 0.00 0.00 0.00 0.000 0.025 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.025 0.00
FLOOR 1 STEP DOWN 1334.42 1334.42 47.88 0.059 0.090 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00771 -32.70 0.00018 0.090 0.00
FLOOR 2 CONFERENCE 1667.32 1667.32 53.41 0.074 0.074 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00793 -32.70 0.00018 0.049 0.00
FLOOR 2 DICTATION 0.00 0.00 0.00 0.000 0.003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.003 0.00
FLOOR 2 EXAM 1 1697.23 1697.23 50.75 0.075 0.075 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00759 -32.70 0.00018 0.051 0.00
FLOOR 2 EXAM 2 691.10 691.10 13.78 0.030 0.076 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00794 -32.70 0.00018 0.076 0.00
FLOOR 2 EXAM 3 924.75 924.75 13.82 0.040 0.102 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00791 -32.70 0.00018 0.102 0.00
FLOOR 2 EXAM 4 404.97 404.97 51.89 0.018 0.018 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00774 -32.70 0.00018 0.012 0.00
FLOOR 2 EXAM 5 1251.23 1251.23 38.48 0.055 0.055 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00764 -32.70 0.00018 0.050 0.00
FLOOR 2 EXAM 6 699.46 699.46 33.46 0.031 0.032 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00750 -32.70 0.00018 0.032 0.00
FLOOR 2 EXAM 7 476.69 476.69 6.48 0.021 0.112 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00901 -32.70 0.00018 0.112 0.00
FLOOR 2 EXAM 8 749.64 749.64 29.89 0.033 0.038 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00720 -32.70 0.00018 0.038 0.00
FLOOR 2 EXAM 9 388.53 388.53 10.56 0.017 0.056 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00865 -32.70 0.00018 0.056 0.00
FLOOR 2 LOUNGE 0.00 0.00 0.00 0.000 0.005 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.005 0.00
FLOOR 2 NURSE STATION 1 0.00 0.00 0.00 0.000 0.011 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.011 0.00
FLOOR 2 NURSE STATION 2 0.00 0.00 0.00 0.000 0.014 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.014 0.00
FLOOR 2 OFFICE 2147.89 2147.89 41.29 0.095 0.095 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00749 -32.70 0.00018 0.022 0.00
FLOOR 2 RECEPTION 2560.94 2560.94 28.01 0.112 0.112 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00774 -32.70 0.00018 0.098 0.00
FLOOR 2 SCHEDULING 1 0.00 0.00 0.00 0.000 0.013 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.013 0.00
FLOOR 2 SCHEDULING 2 0.00 0.00 0.00 0.000 0.014 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.014 0.00
FLOOR 2 WORK 1305.51 1305.51 8.32 0.057 0.068 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00674 -32.70 0.00018 0.068 0.00
FLOOR 2 X-RAY 0.00 0.00 0.00 0.000 0.127 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.127 0.00
FLOOR 3 DRESSING ROOM 145.94 145.94 37.40 0.006 0.006 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.09 0.00571 -32.70 0.00018 0.002 0.00
FLOOR 3 HUMID 317.66 317.66 31.66 0.014 0.014 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.09 0.00527 -32.70 0.00018 0.004 0.00
FLOOR 3 LOCKER 325.02 325.02 29.15 0.014 0.014 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00635 -32.70 0.00018 0.008 0.00
FLOOR 3 LOUNGE 1237.33 1237.33 17.55 0.054 0.054 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.01142 -32.70 0.00018 0.048 0.00
FLOOR 3 OFFICE 7074.82 7074.82 25.08 0.310 0.310 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00818 -32.70 0.00018 0.122 0.00
FLOOR 3 PHYSICAL THERAPY 1 4771.40 4771.40 39.51 0.211 0.211 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00824 -32.70 0.00018 0.184 0.00
FLOOR 3 PHYSICAL THERAPY 2 1449.95 1449.95 26.36 0.064 0.084 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00668 -32.70 0.00018 0.084 0.00
FLOOR 3 TREATMENT 1109.93 1109.93 25.10 0.049 0.067 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00621 -32.70 0.00018 0.067 0.00
FLOOR 3 WORK 2386.76 2386.76 44.76 0.106 0.106 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00802 -32.70 0.00018 0.023 0.00
FLOOR 1 BIO HAZ 126.69 126.69 24.35 0.006 0.006 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.003 0.00
FLOOR 1 ELECTRICAL ROOM 77.81 77.81 8.55 0.003 0.003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00285 -32.70 0.00018 0.000 0.00
FLOOR 1 ELEVATOR PUMP ROOM 579.89 579.89 68.59 0.026 0.026 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00745 -32.70 0.00018 0.000 0.00
FLOOR 1 IT HALL 0.00 0.00 0.00 0.000 0.004 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.004 0.00
FLOOR 1 LOBBY HALL 0.00 0.00 0.00 0.000 0.007 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.007 0.00
FLOOR 1 LOBBY TOILET 317.04 317.04 63.20 0.014 0.014 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00764 -32.70 0.00018 0.000 0.00
FLOOR 1 LOCKER ROOM HALL 0.00 0.00 0.00 0.000 0.014 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.014 0.00
FLOOR 1 MED GAS 655.63 655.63 126.02 0.029 0.029 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00775 -32.70 0.00018 0.003 0.00
FLOOR 1 MRI HALL 4.65 4.65 0.34 0.000 0.004 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 21.10 21.10 0.00844 -32.70 0.00018 0.004 0.00
FLOOR 1 MRI TOILET 220.97 220.97 44.05 0.010 0.010 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00704 -32.70 0.00018 0.000 0.00
FLOOR 1 NURSE HALL 10.19 10.19 0.22 0.000 0.014 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 21.10 21.11 0.00845 -32.70 0.00018 0.014 0.00
FLOOR 1 NURSE JANITOR 0.00 0.00 0.00 0.000 0.003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.003 0.00
FLOOR 1 PRE-OP HALL 0.00 0.00 0.00 0.000 0.015 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.015 0.00
FLOOR 1 PRE-OP TOILET 279.99 279.99 55.81 0.012 0.012 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00753 -32.70 0.00018 0.000 0.00
FLOOR 1 RECEPTION HALL 0.00 0.00 0.00 0.000 0.004 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.004 0.00
FLOOR 1 SCRUB 120.91 120.91 15.49 0.005 0.005 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.002 0.00
FLOOR 1 STERILE HALL 316.84 316.84 5.54 0.014 0.017 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00798 -32.70 0.00018 0.017 0.00
FLOOR 1 STERILE STORAGE 0.00 0.00 0.00 0.000 0.022 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.022 0.00
FLOOR 1 STORAGE 4545.33 4545.33 53.18 0.202 0.202 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00789 -32.70 0.00018 0.052 0.00
FLOOR 1 SUB-STERILE 825.59 825.59 45.34 0.037 0.037 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00760 -32.70 0.00018 0.006 0.00
FLOOR 1 UTILITY HALL 1340.87 1340.87 56.38 0.060 0.060 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00787 -32.70 0.00018 0.007 0.00
FLOOR 1 UTILITY JANITOR 56.86 56.86 14.57 0.003 0.003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.002 0.00
FLOOR 1 UTILITY ROOM 1383.51 1383.51 41.37 0.061 0.061 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00766 -32.70 0.00018 0.020 0.00
FLOOR 1 VESTIBULE 372.10 372.10 55.63 0.017 0.017 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00757 -32.70 0.00018 0.002 0.00
FLOOR 2 CONFERENCE TOILET 96.37 96.37 16.21 0.004 0.004 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.000 0.00
FLOOR 2 EXAM HALL 1 410.91 410.91 24.57 0.018 0.018 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.005 0.00
FLOOR 2 EXAM HALL 2 257.94 257.94 15.42 0.011 0.011 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.005 0.00
FLOOR 2 EXAM HALL 3 267.41 267.41 15.99 0.012 0.012 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.005 0.00
FLOOR 2 EXAM HALL 4 163.48 163.48 8.89 0.007 0.007 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.006 0.00
FLOOR 2 EXAM HALL 5 165.30 165.30 8.99 0.007 0.007 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.006 0.00
FLOOR 2 EXAM HALL 6 226.11 226.11 12.29 0.010 0.010 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.006 0.00
FLOOR 2 JANITOR 525.53 525.53 89.79 0.023 0.023 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00737 -32.70 0.00018 0.004 0.00
FLOOR 2 OFFICE HALL 665.40 665.40 16.13 0.030 0.030 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.013 0.00
FLOOR 2 RECEPTION HALL 0.00 0.00 0.00 0.000 0.016 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   0.00 21.10 0.00800 -32.70 0.00018 0.016 0.00
FLOOR 2 RECEPTION TOILET 69.47 69.47 5.93 0.003 0.003 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00801 -32.70 0.00018 0.000 0.00
FLOOR 2 STORAGE 1 82.60 82.60 15.88 0.004 0.004 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.003 0.00
FLOOR 2 STORAGE 2 95.85 95.85 8.60 0.004 0.007 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.007 0.00
FLOOR 2 STORAGE 3 101.24 101.24 7.57 0.005 0.008 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.008 0.00
FLOOR 2 UTILITY 611.68 611.68 52.25 0.027 0.027 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00758 -32.70 0.00018 0.007 0.00
FLOOR 2 WORK HALL 9.13 9.13 0.12 0.000 0.024 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 21.10 2.34 0.00094 -32.70 0.00018 0.024 0.00
FLOOR 2 WORK TOILET 316.49 316.49 63.09 0.014 0.014 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00751 -32.70 0.00018 0.000 0.00
FLOOR 3 ELEVATOR HALL 1159.91 1159.91 33.74 0.051 0.051 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.010 0.00
FLOOR 3 JANITOR 504.62 504.62 86.22 0.022 0.022 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00783 -32.70 0.00018 0.004 0.00
FLOOR 3 LOUNGE TOILET 864.73 864.73 48.48 0.038 0.038 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00797 -32.70 0.00018 0.000 0.00
FLOOR 3 MECHANICAL 398.61 398.61 12.26 0.017 0.017 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00764 -32.70 0.00018 0.000 0.00
FLOOR 3 MECHANICAL HALL 1225.99 1225.99 43.99 0.054 0.054 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00715 -32.70 0.00018 0.008 0.00
FLOOR 3 OFFICE HALL 2521.33 2521.33 32.54 0.111 0.111 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00800 -32.70 0.00018 0.024 0.00
FLOOR 3 OFFICE TOILET 338.12 338.12 67.40 0.015 0.015 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00795 -32.70 0.00018 0.000 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 280.16 280.16 35.90 0.012 0.012 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.09 0.00600 -32.70 0.00018 0.000 0.00
FLOOR 3 STORAGE 1 408.29 408.29 40.69 0.018 0.018 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00695 -32.70 0.00018 0.006 0.00
FLOOR 3 STORAGE 2 348.30 348.30 44.63 0.015 0.015 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00713 -32.70 0.00018 0.005 0.00
FLOOR 3 UNDEVELOPED 1 6198.53 6198.53 29.42 0.272 0.272 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00798 -32.70 0.00018 0.128 0.00
FLOOR 3 UNDEVELOPED 2 4049.76 4049.76 37.84 0.179 0.179 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00798 -32.70 0.00018 0.065 0.00
FLOOR 3 UTILITY 716.14 716.14 35.69 0.032 0.032 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00682 -32.70 0.00018 0.012 0.00
NE STAIR 3622.88 3622.88 232.12 0.161 0.161 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00776 -32.70 0.00018 0.005 0.00
NW ELEVATOR 2379.85 2379.85 182.98 0.106 0.106 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00771 -32.70 0.00018 0.004 0.00
NW STAIR 3715.91 3715.91 208.32 0.165 0.165 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00773 -32.70 0.00018 0.005 0.00
SW STAIR 1814.15 1814.15 203.41 0.081 0.081 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.10 21.10 0.00772 -32.70 0.00018 0.003 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
AHU-1 6.92 6.92 2.51 2.51 7.1009 5.2993 7.1009 0.7463 1.0000
AHU-2 9.20 9.20 3.54 3.54 9.2030 4.3197 9.2030 0.4694 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 656.238 656.238 0.049076 0.00001437 12.568 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 651.64 656.24 0.049076 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00755019 46.5240 362.06 0.00 651.71 651.71
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 BIO HAZ VAV BOX 160.434 160.434 0.005623 0.00000351 3.453 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 159.21 160.43 0.005623 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 126.69 0.00 159.26 159.26
FLOOR 1 CAFE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 CAFE VAV BOX 1070.711 1070.711 0.059174 0.00002344 21.146 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1062.96 1070.71 0.059174 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.01143564 70.0095 713.09 0.00 1063.13 1063.13
FLOOR 1 CLEAN VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 CLEAN VAV BOX 302.655 302.655 0.050434 0.00000663 5.332 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 300.27 302.66 0.050434 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 300.30 300.30
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 CLEAN WORK VAV BOX 373.520 373.520 0.062243 0.00000818 6.581 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 370.58 373.52 0.062243 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 370.61 370.61
FLOOR 1 DICTATION VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 DICTATION VAV BOX 22.207 22.207 0.003701 0.00000049 0.391 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 22.03 22.21 0.003701 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 22.03 22.03
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 DRESSING ROOM VAV BOX 456.745 456.745 0.016056 0.00001000 9.823 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 453.27 453.42 0.016056 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00765675 47.1738 360.49 0.00 453.41 453.41
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 ELECTRICAL ROOM VAV BOX 131.684 131.684 0.009067 0.00000288 2.540 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 130.76 131.68 0.009067 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00284980 17.6937 77.81 0.00 130.77 130.77
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 ELEVATOR PUMP ROOM VAV BOX 936.972 936.972 0.059594 0.00002051 18.209 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 930.33 936.97 0.059594 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00745322 45.9369 579.89 0.00 930.46 930.46
FLOOR 1 HUMID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 HUMID VAV BOX 10.680 10.680 0.001780 0.00000023 0.188 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 10.60 10.68 0.001780 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 10.60 10.60
FLOOR 1 IT HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 IT HALL VAV BOX 29.645 29.645 0.004940 0.00000065 0.522 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 29.41 29.65 0.004940 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 29.41 29.41
FLOOR 1 IT ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 IT ROOM VAV BOX 0.000 0.000 0.002695 0.00000000 1.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 0.00 0.00 0.002695 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 2.32 0.00180361 38.8661 4.02 0.00 0.00 0.00
FLOOR 1 LOBBY VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOBBY VAV BOX 1943.580 1943.580 0.067519 0.00004255 41.932 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1928.77 1943.58 0.067519 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00739045 45.5512 1538.97 0.00 1929.37 1929.37
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOBBY HALL VAV BOX 67.860 67.860 0.011308 0.00000149 1.196 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 67.33 67.86 0.011308 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 67.33 67.33
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 533.788 533.788 0.036154 0.00001169 10.310 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 530.02 533.79 0.036154 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00764088 47.0763 317.04 0.00 530.09 530.09
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOCKER ROOM VAV BOX 282.822 282.822 0.047129 0.00000619 4.983 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 280.60 282.82 0.047129 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 280.62 280.62
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOCKER ROOM HALL VAV BOX 102.425 102.425 0.017068 0.00000224 1.804 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 101.62 102.42 0.017068 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 101.63 101.63
FLOOR 1 LOUNGE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOUNGE VAV BOX 156.737 156.737 0.026118 0.00000343 2.761 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 155.50 156.74 0.026118 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 155.52 155.52
FLOOR 1 MED GAS VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 MED GAS VAV BOX 831.015 831.015 0.029248 0.00001819 17.866 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 824.69 825.97 0.029248 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00775058 47.7442 655.63 0.00 824.94 824.94
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 172.644 172.644 0.028769 0.00000378 3.042 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 171.28 172.64 0.028769 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 171.30 171.30
FLOOR 1 MRI HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 MRI HALL VAV BOX 44.475 44.475 0.006631 0.00000097 0.790 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 44.12 44.47 0.006631 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00844199 51.9408 4.65 0.00 44.13 44.13
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 441.502 441.502 0.073571 0.00000967 7.778 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 438.03 441.50 0.073571 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 438.07 438.07
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 279.513 279.513 0.009780 0.00000612 6.019 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 277.38 276.18 0.009780 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00703504 43.3902 220.97 0.00 277.47 277.47
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NOURISHMENT VAV BOX 85.801 85.801 0.014298 0.00000188 1.512 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 85.13 85.80 0.014298 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 85.13 85.13
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NURSE HALL VAV BOX 135.320 135.320 0.020794 0.00000296 2.397 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 134.25 135.32 0.020794 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.11 0.00844905 51.9528 10.19 0.00 134.27 134.27
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NURSE JANITOR VAV BOX 15.013 15.013 0.002502 0.00000033 0.264 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 14.89 15.01 0.002502 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 14.90 14.90
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NURSE STATION VAV BOX 117.078 117.078 0.019510 0.00000256 2.063 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 116.16 117.08 0.019510 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 116.17 116.17
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 92.866 92.866 0.015475 0.00000203 1.636 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 92.13 92.87 0.015475 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 92.14 92.14
FLOOR 1 OFFICE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 OFFICE VAV BOX 66.279 66.279 0.011045 0.00000145 1.168 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 65.76 66.28 0.011045 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 65.76 65.76
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 OPERATING ROOM 1 VAV BOX 1072.824 1072.824 0.434164 0.00002349 18.194 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1064.63 1072.82 0.434164 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 18.10 0.00800000 59.3495 0.00 0.00 1064.67 1064.67
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 OPERATING ROOM 2 VAV BOX 0.000 0.000 0.453041 0.00000000 1.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:10:00 0.00 0.00 0.453041 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 4.15 0.00159491 30.2064 2.84 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 OPERATING ROOM 3 VAV BOX 1850.232 1850.232 0.748776 0.00004051 31.379 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1836.11 1850.23 0.748776 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 18.10 0.00800000 59.3495 0.00 0.00 1836.18 1836.18
FLOOR 1 PACU VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PACU VAV BOX 305.855 305.855 0.050967 0.00000670 5.388 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 303.45 305.85 0.050967 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 303.48 303.48
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PRE-OP HALL VAV BOX 120.639 120.639 0.020103 0.00000264 2.125 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 119.69 120.64 0.020103 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 119.70 119.70
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PRE-OP ROOM 1 VAV BOX 535.246 535.246 0.089192 0.00001172 9.430 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 531.03 535.25 0.089192 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 531.08 531.08
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PRE-OP ROOM 2 VAV BOX 957.212 957.212 0.159508 0.00002096 16.864 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 949.68 957.21 0.159508 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 949.77 949.77
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 354.485 354.485 0.012429 0.00000776 7.629 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 351.79 351.00 0.012429 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00752833 46.3922 279.99 0.00 351.89 351.89
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PROCEDURE ROOM VAV BOX 2409.631 2409.631 0.336241 0.00005276 43.008 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2390.54 2409.63 0.336241 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00663270 40.9302 397.47 0.00 2390.81 2390.81
FLOOR 1 RECEPTION VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 RECEPTION VAV BOX 0.000 0.000 0.036799 0.00000000 1.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 0.00 0.00 0.036799 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 2.29 0.00163629 35.3362 37.44 0.00 0.00 0.00
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 RECEPTION HALL VAV BOX 31.025 31.025 0.005170 0.00000068 0.547 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 30.78 31.02 0.005170 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 30.78 30.78
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 RECOVERY ROOM VAV BOX 3021.083 3021.083 0.236297 0.00006615 57.586 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2996.80 3021.08 0.236297 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00758559 46.7389 1604.49 0.00 2997.08 2997.08
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 SCHEDULING VAV BOX 143.483 143.483 0.005031 0.00000314 3.088 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 142.39 143.48 0.005031 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00448075 27.7476 113.50 0.00 142.43 142.43
FLOOR 1 SCRUB VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 SCRUB VAV BOX 153.167 153.167 0.005376 0.00000335 3.295 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 152.00 153.17 0.005376 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 120.91 0.00 152.05 152.05
FLOOR 1 SOIL VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 300.962 300.962 0.050152 0.00000659 5.302 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 298.59 300.96 0.050152 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 298.62 298.62
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 0.000 0.000 0.019575 0.00000000 1.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 0.00 0.00 0.019575 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 2.31 0.00179826 38.7656 2.26 0.00 0.00 0.00
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 399.778 399.778 0.066618 0.00000875 7.043 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 396.63 399.78 0.066618 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 396.67 396.67
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STEP DOWN VAV BOX 2002.407 2002.407 0.111399 0.00004384 39.513 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1987.92 2002.41 0.111399 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00770945 47.4927 1334.42 0.00 1988.24 1988.24
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STERILE HALL VAV BOX 436.850 436.850 0.020000 0.00000956 8.876 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 433.65 436.85 0.020000 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00797776 49.1208 316.84 0.00 433.74 433.74
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STERILE STORAGE VAV BOX 73.119 73.119 0.012184 0.00000160 1.288 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 72.54 73.12 0.012184 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 72.55 72.55
FLOOR 1 STORAGE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STORAGE VAV BOX 5754.649 5754.649 0.201576 0.00012600 123.878 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5710.81 5692.52 0.201576 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00789417 48.6139 4545.33 0.00 5712.57 5712.57
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 SUB-STERILE VAV BOX 1044.775 1044.775 0.036564 0.00002288 22.496 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1036.82 1044.78 0.036564 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00759698 46.8091 825.59 0.00 1037.14 1037.14
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 UTILITY HALL VAV BOX 1697.904 1697.904 0.059516 0.00003718 36.543 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1684.97 1680.74 0.059516 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00787059 48.4708 1340.87 0.00 1685.49 1685.49
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 UTILITY JANITOR VAV BOX 72.068 72.068 0.002535 0.00000158 1.550 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 71.52 72.07 0.002535 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 56.86 0.00 71.54 71.54
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 UTILITY ROOM VAV BOX 1750.457 1750.457 0.061199 0.00003833 37.701 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1737.12 1728.27 0.061199 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00766381 47.2148 1383.51 0.00 1737.66 1737.66
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 VESTIBULE VAV BOX 471.097 471.097 0.016515 0.00001031 10.139 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 467.51 466.40 0.016515 16.00 11.53 0.00700000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00756753 46.6305 372.10 0.00 467.65 467.65
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 CONFERENCE VAV BOX 2088.674 2088.674 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2088.67 2088.67 0.073961 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00792617 48.8093 1667.32 0.00 -999.00 -999.00
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL Coil:Heating:Electric Unknown Unknown 552.555 552.555 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 552.56 121.00 0.004285 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 96.37 0.00 -999.00 -999.00
FLOOR 2 DICTATION VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 DICTATION VAV BOX 118.886 118.886 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 118.89 79.30 0.002808 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 1 VAV BOX 3474.263 3474.263 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3474.26 2124.77 0.075240 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00759088 46.7727 1697.23 0.00 -999.00 -999.00
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 2 VAV BOX 7196.583 7196.583 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 7196.58 2158.98 0.076451 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00794039 48.8939 691.10 0.00 -999.00 -999.00
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 3 VAV BOX 9595.444 9595.444 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 9595.44 2878.63 0.101934 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00790766 48.6950 924.75 0.00 -999.00 -999.00
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 4 VAV BOX 893.967 893.967 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 893.97 507.25 0.017962 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00773681 47.6589 404.97 0.00 -999.00 -999.00
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 5 VAV BOX 4036.938 4036.938 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4036.94 1561.35 0.055288 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00763799 47.0580 1251.23 0.00 -999.00 -999.00
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 6 VAV BOX 2818.662 2818.662 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2818.66 899.57 0.031854 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00749786 46.2057 699.46 0.00 -999.00 -999.00
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 7 VAV BOX 10554.988 10554.988 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10554.99 3166.50 0.112128 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00901273 55.4009 476.69 0.00 -999.00 -999.00
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 8 VAV BOX 3346.411 3346.411 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3346.41 1079.49 0.038225 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00720307 44.4114 749.64 0.00 -999.00 -999.00
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 9 VAV BOX 5277.494 5277.494 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5277.49 1583.25 0.056064 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00864744 53.1861 388.53 0.00 -999.00 -999.00
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 1 VAV BOX 513.240 513.240 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 513.24 513.24 0.018174 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 410.91 0.00 -999.00 -999.00
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 2 VAV BOX 323.559 323.559 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 323.56 323.56 0.011457 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 257.94 0.00 -999.00 -999.00
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 3 VAV BOX 335.298 335.298 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 335.30 335.30 0.011873 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 267.41 0.00 -999.00 -999.00
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 4 VAV BOX 237.328 237.328 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 237.33 205.66 0.007283 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00799944 49.2525 163.48 0.00 -999.00 -999.00
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 5 VAV BOX 237.930 237.930 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 237.93 208.01 0.007366 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00799936 49.2521 165.30 0.00 -999.00 -999.00
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 6 VAV BOX 283.919 283.919 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 283.92 283.92 0.010054 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2559 226.11 0.00 -999.00 -999.00
FLOOR 2 JANITOR VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 JANITOR VAV BOX 661.065 661.065 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 661.07 661.07 0.023409 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00736517 45.4031 525.53 0.00 -999.00 -999.00
FLOOR 2 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 LOUNGE VAV BOX 216.196 216.196 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 216.20 143.93 0.005097 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 NURSE STATION 1 VAV BOX 479.721 479.721 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 479.72 319.85 0.011326 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 NURSE STATION 2 VAV BOX 576.075 576.075 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 576.08 383.82 0.013591 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00
FLOOR 2 OFFICE VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 OFFICE VAV BOX 2682.350 2682.350 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2682.35 2682.35 0.094984 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00748601 46.1343 2147.89 0.00 -999.00 -999.00
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 OFFICE HALL VAV BOX 833.192 833.192 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 833.19 833.19 0.029504 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 665.40 0.00 -999.00 -999.00
FLOOR 2 RECEPTION VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 RECEPTION VAV BOX 4135.986 4135.986 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4135.99 3176.76 0.112491 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00774062 47.6812 2560.94 0.00 -999.00 -999.00
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 RECEPTION HALL VAV BOX 677.989 677.989 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 677.99 450.99 0.015970 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL Coil:Heating:Electric Unknown Unknown 1005.895 1005.895 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1005.89 87.54 0.003100 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800778 49.3033 69.47 0.00 -999.00 -999.00
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 SCHEDULING 1 VAV BOX 551.185 551.185 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 551.19 367.03 0.012997 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 SCHEDULING 2 VAV BOX 580.295 580.295 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 580.30 387.42 0.013719 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 STORAGE 1 VAV BOX 134.340 134.340 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 134.34 103.83 0.003677 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 82.60 0.00 -999.00 -999.00
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 STORAGE 2 VAV BOX 287.934 287.934 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 287.93 191.91 0.006796 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00799980 49.2547 95.85 0.00 -999.00 -999.00
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 STORAGE 3 VAV BOX 345.586 345.586 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 345.59 230.29 0.008155 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00799883 49.2488 101.24 0.00 -999.00 -999.00
FLOOR 2 UTILITY VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 UTILITY VAV BOX 766.155 766.155 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 766.16 766.16 0.027130 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00757727 46.6896 611.68 0.00 -999.00 -999.00
FLOOR 2 WORK VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 WORK VAV BOX 2868.983 2868.983 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2868.98 1914.42 0.067791 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00674259 41.5993 1305.51 0.00 -999.00 -999.00
FLOOR 2 WORK HALL VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 WORK HALL VAV BOX 1002.269 1002.269 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 1002.27 666.88 0.023615 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 2.34 0.00094030 20.2660 9.13 0.00 -999.00 -999.00
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL Coil:Heating:Electric Unknown Unknown 519.230 519.230 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 519.23 397.21 0.014065 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00751387 46.3046 316.49 0.00 -999.00 -999.00
FLOOR 2 X-RAY VAV BOX REHEAT COIL Coil:Heating:Electric Unknown Unknown 5408.922 5408.922 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 5408.92 3598.29 0.127418 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 DRESSING ROOM VAV BOX 181.816 181.816 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 181.82 181.82 0.006438 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.09 0.00571322 35.3174 145.94 0.00 -999.00 -999.00
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 ELEVATOR HALL VAV BOX 1443.692 1443.692 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1443.69 1443.69 0.051122 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00799723 49.2392 1159.91 0.00 -999.00 -999.00
FLOOR 3 HUMID VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 HUMID VAV BOX 394.626 394.626 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 394.63 394.63 0.013974 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.09 0.00527123 32.6086 317.66 0.00 -999.00 -999.00
FLOOR 3 JANITOR VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 JANITOR VAV BOX 634.549 634.549 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 634.55 634.55 0.022470 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00783410 48.2497 504.62 0.00 -999.00 -999.00
FLOOR 3 LOCKER VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 LOCKER VAV BOX 403.569 403.569 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 403.57 403.57 0.014291 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00634530 39.1793 325.02 0.00 -999.00 -999.00
FLOOR 3 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 LOUNGE VAV BOX 2050.362 2050.362 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2050.36 1515.02 0.053648 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.01141704 69.8992 1237.33 0.00 -999.00 -999.00
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL Coil:Heating:Electric Unknown Unknown 1486.406 1486.406 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1486.41 1081.88 0.038310 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00797189 49.0854 864.73 0.00 -999.00 -999.00
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 MECHANICAL VAV BOX 493.798 493.798 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 493.80 493.80 0.017486 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00763948 47.0638 398.61 0.00 -999.00 -999.00
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 MECHANICAL HALL VAV BOX 1531.872 1531.872 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1531.87 1531.87 0.054245 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00714546 44.0618 1225.99 0.00 -999.00 -999.00
FLOOR 3 OFFICE VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 OFFICE VAV BOX 8748.535 8748.535 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8748.53 8748.53 0.309791 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00817958 50.3462 7074.82 0.00 -999.00 -999.00
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 OFFICE HALL VAV BOX 3136.630 3136.630 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3136.63 3136.63 0.111070 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00799711 49.2384 2521.33 0.00 -999.00 -999.00
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL Coil:Heating:Electric Unknown Unknown 424.310 424.310 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 424.31 424.31 0.015025 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00794706 48.9348 338.12 0.00 -999.00 -999.00
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 PHYSICAL THERAPY 1 VAV BOX 14035.787 14035.787 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 14035.79 5950.00 0.210693 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00823616 50.6892 4771.40 0.00 -999.00 -999.00
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 PHYSICAL THERAPY 2 VAV BOX 6548.357 6548.357 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6548.36 2366.88 0.083813 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00668336 41.2426 1449.95 0.00 -999.00 -999.00
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL Coil:Heating:Electric Unknown Unknown 690.608 690.608 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 690.61 348.87 0.012354 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.09 0.00600414 37.0974 280.16 0.00 -999.00 -999.00
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 STORAGE 1 VAV BOX 692.633 692.633 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 692.63 509.90 0.018056 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00695318 42.8903 408.29 0.00 -999.00 -999.00
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 STORAGE 2 VAV BOX 435.455 435.455 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 435.45 435.45 0.015420 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00713019 43.9689 348.30 0.00 -999.00 -999.00
FLOOR 3 TREATMENT VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 TREATMENT VAV BOX 5138.360 5138.360 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5138.36 1903.10 0.067390 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00621356 38.3739 1109.93 0.00 -999.00 -999.00
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 UNDEVELOPED 1 VAV BOX 7691.374 7691.374 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 7691.37 7691.37 0.272357 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00798049 49.1375 6198.53 0.00 -999.00 -999.00
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 UNDEVELOPED 2 VAV BOX 5047.388 5047.388 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5047.39 5047.39 0.178731 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00797505 49.1045 4049.76 0.00 -999.00 -999.00
FLOOR 3 UTILITY VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 UTILITY VAV BOX 892.290 892.290 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 892.29 892.29 0.031597 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00682127 42.0860 716.14 0.00 -999.00 -999.00
FLOOR 3 WORK VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 WORK VAV BOX 2982.527 2982.527 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2982.53 2982.53 0.105613 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00802407 49.4022 2386.76 0.00 -999.00 -999.00
NE STAIR VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT NE STAIR VAV BOX 4551.584 4551.584 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4551.58 4551.58 0.161175 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00775942 47.7972 3622.88 0.00 -999.00 -999.00
NW ELEVATOR VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT NW ELEVATOR VAV BOX 2984.036 2984.036 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2984.04 2984.04 0.105667 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00771168 47.5066 2379.85 0.00 -999.00 -999.00
NW STAIR VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT NW STAIR VAV BOX 4663.853 4663.853 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4663.85 4663.85 0.165150 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00772773 47.6047 3715.91 0.00 -999.00 -999.00
SW STAIR VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT SW STAIR VAV BOX 2276.441 2276.441 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2276.44 2276.44 0.080610 16.00 12.32 0.00780000 40.00 20.66 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.10 0.00771553 47.5302 1814.15 0.00 -999.00 -999.00
AHU-1_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC AHU-1 176331.530 123094.082 7.100871 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 175604.37 113495.35 7.100871 21.88 16.48 0.01001922 5.27 5.27 0.00700000 23.81 0.01270325 19.22 29.1652 21.04 0.00887222 54.7565 76640.86 0.00 176775.54 121649.73
AHU-1_HEATC Coil:Heating:Water AirLoopHVAC AHU-1 92954.514 92954.514 7.100871 0.00203521 1468.341 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:50:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 78855.15 92954.51 7.100871 -23.52 -23.52 0.00141751 16.00 11.53 0.00700000 -32.70 0.00018338 -32.70 29.1652 18.36 0.00728370 53.2145 17705.92 0.00 78848.47 78848.47
AHU-1_EXTRAELECHEATC Coil:Heating:Electric AirLoopHVAC AHU-1 10000000.000 10000000.000 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:50:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10000000.00 329605.19 7.100871 -23.52 -23.52 0.00141751 16.00 11.53 0.00700000 -32.70 0.00018338 -32.70 29.1652 18.36 0.00728370 53.2145 17705.92 0.00 -999.00 -999.00
AHU-1_EXTRAWATERHEATC Coil:Heating:Water AirLoopHVAC AHU-1 92954.514 92954.514 7.100871 0.00203521 1468.341 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:50:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 78855.15 92954.51 7.100871 -23.52 -23.52 0.00141751 16.00 11.53 0.00700000 -32.70 0.00018338 -32.70 29.1652 18.36 0.00728370 53.2145 17705.92 0.00 0.00 0.00
AHU-2_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC AHU-2 220453.158 156315.645 9.203000 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 224599.30 164633.21 9.203000 24.36 17.26 0.00994010 9.17 9.17 0.00780000 30.10 0.01270324 21.10 27.3520 22.20 0.00887405 51.0171 101699.63 0.00 221008.27 154360.98
AHU-2_HEATC Coil:Heating:Water AirLoopHVAC AHU-2 115747.629 115747.629 9.203000 0.00253426 1832.705 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 10:40:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 98665.72 115747.63 9.203000 -32.49 -32.49 0.00020955 16.00 12.32 0.00780000 -32.70 0.00018338 -32.70 27.3520 20.97 0.00781643 48.5130 34261.71 0.00 98643.35 98643.35



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 ANESTHESIA N/A N/A N/A Yes Yes Yes No 656.238 656.238 0.049076 0.00001437 12.568 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.1900 0.650767 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 651.64 656.24 1.0000 0.05663003 0.049076 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.01436669 60.00 48.90 11.10 0.000 651.64 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.86 0.00755019 21.10 0.00755019 46.5240 362.06 0.00 651.71 651.71 0.05663003 16.60 12.15 0.00700000 34402.9 27.91 16.46 0.00700000 45911.1
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 BIO HAZ VAV BOX FLOOR 1 BIO HAZ N/A N/A N/A Yes Yes Yes No 160.434 160.434 0.005623 0.00000351 3.453 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0464 0.159097 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 159.21 160.43 1.0000 0.00648850 0.005623 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00351231 60.00 48.90 11.10 0.000 159.21 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.98 0.00800000 21.10 0.00800000 49.2560 126.69 0.00 159.26 159.26 0.00648850 16.60 12.15 0.00700000 34402.9 40.71 20.63 0.00700000 58948.1
FLOOR 1 CAFE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 CAFE VAV BOX FLOOR 1 CAFE N/A N/A N/A Yes Yes Yes No 1070.711 1070.711 0.059174 0.00002344 21.146 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.3100 1.061785 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1062.96 1070.71 1.0000 0.06828248 0.059174 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.02344055 60.00 48.90 11.10 0.000 1062.96 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.67 0.01143564 21.10 0.01143564 70.0095 713.09 0.00 1063.13 1063.13 0.06828248 16.60 12.15 0.00700000 34402.9 31.90 17.83 0.00700000 49972.6
FLOOR 1 CLEAN VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 CLEAN VAV BOX FLOOR 1 CLEAN N/A N/A N/A Yes Yes Yes No 302.655 302.655 0.050434 0.00000663 5.332 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0876 0.300132 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 300.27 302.66 1.0000 0.05819700 0.050434 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00662588 60.00 48.90 11.10 0.000 300.27 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 300.30 300.30 0.05819700 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 CLEAN WORK VAV BOX FLOOR 1 CLEAN WORK N/A N/A N/A Yes Yes Yes No 373.520 373.520 0.062243 0.00000818 6.581 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.1081 0.370406 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 370.58 373.52 1.0000 0.07182342 0.062243 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00817728 60.00 48.90 11.10 0.000 370.58 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 370.61 370.61 0.07182342 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 DICTATION VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 DICTATION VAV BOX FLOOR 1 DICTATION N/A N/A N/A Yes Yes Yes No 22.207 22.207 0.003701 0.00000049 0.391 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0064 0.022022 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 22.03 22.21 1.0000 0.00427011 0.003701 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00048616 60.00 48.90 11.10 0.000 22.03 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 22.03 22.03 0.00427011 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 DRESSING ROOM VAV BOX FLOOR 1 DRESSING ROOM N/A N/A N/A Yes Yes Yes No 456.745 456.745 0.016056 0.00001000 9.823 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.1322 0.452937 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 453.27 453.42 1.0000 0.01852738 0.016056 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00999928 60.00 48.90 11.10 0.000 453.27 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.00 0.00765675 21.10 0.00765675 47.1738 360.49 0.00 453.41 453.41 0.01852738 16.60 12.15 0.00700000 34402.9 40.64 20.61 0.00700000 58875.1
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 ELECTRICAL ROOM VAV BOX FLOOR 1 ELECTRICAL ROOM N/A N/A N/A Yes Yes Yes No 131.684 131.684 0.009067 0.00000288 2.540 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0381 0.130586 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 130.76 131.68 1.0000 0.01046220 0.009067 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00288290 60.00 48.90 11.10 0.000 130.76 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.92 0.00284980 21.10 0.00284980 17.6937 77.81 0.00 130.77 130.77 0.01046220 16.60 12.15 0.00700000 34402.9 28.88 16.80 0.00700000 46902.4
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 ELEVATOR PUMP ROOM VAV BOX FLOOR 1 ELEVATOR PUMP ROOM N/A N/A N/A Yes Yes Yes No 936.972 936.972 0.059594 0.00002051 18.209 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.2713 0.929160 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 930.33 936.97 1.0000 0.06876712 0.059594 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.02051266 60.00 48.90 11.10 0.000 930.33 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.95 0.00745322 21.10 0.00745322 45.9369 579.89 0.00 930.46 930.46 0.06876712 16.60 12.15 0.00700000 34402.9 29.89 17.15 0.00700000 47933.5
FLOOR 1 HUMID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 HUMID VAV BOX FLOOR 1 HUMID N/A N/A N/A Yes Yes Yes No 10.680 10.680 0.001780 0.00000023 0.188 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0031 0.010591 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 10.60 10.68 1.0000 0.00205371 0.001780 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00023382 60.00 48.90 11.10 0.000 10.60 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 10.60 10.60 0.00205371 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 IT HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 IT HALL VAV BOX FLOOR 1 IT HALL N/A N/A N/A Yes Yes Yes No 29.645 29.645 0.004940 0.00000065 0.522 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0086 0.029398 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 29.41 29.65 1.0000 0.00570039 0.004940 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00064900 60.00 48.90 11.10 0.000 29.41 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 29.41 29.41 0.00570039 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 IT ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 IT ROOM VAV BOX FLOOR 1 IT ROOM N/A N/A N/A Yes Yes Yes No 0.000 0.000 0.002695 0.00000000 1.000 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 0.00 0.00 1.0000 0.00310969 0.002695 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00000000 60.00 48.90 11.10 0.000 0.00 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.89 0.00180361 2.32 0.00180361 38.8661 4.02 0.00 0.00 0.00 0.00310969 16.60 12.15 0.00700000 34402.9 16.60 12.15 0.00700000 34402.9
FLOOR 1 LOBBY VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOBBY VAV BOX FLOOR 1 LOBBY N/A N/A N/A Yes Yes Yes No 1943.580 1943.580 0.067519 0.00004255 41.932 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.5625 1.927376 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1928.77 1943.58 1.0000 0.07791130 0.067519 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.04254982 60.00 48.90 11.10 0.000 1928.77 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.87 0.00739045 21.10 0.00739045 45.5512 1538.97 0.00 1929.37 1929.37 0.07791130 16.60 12.15 0.00700000 34402.9 40.93 20.70 0.00700000 59166.6
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOBBY HALL VAV BOX FLOOR 1 LOBBY HALL N/A N/A N/A Yes Yes Yes No 67.860 67.860 0.011308 0.00000149 1.196 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0196 0.067294 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 67.33 67.86 1.0000 0.01304860 0.011308 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00148562 60.00 48.90 11.10 0.000 67.33 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 67.33 67.33 0.01304860 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 LOBBY TOILET N/A N/A N/A Yes Yes Yes No 533.788 533.788 0.036154 0.00001169 10.310 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.1546 0.529337 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 530.02 533.79 1.0000 0.04171925 0.036154 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.01168594 60.00 48.90 11.10 0.000 530.02 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.95 0.00764088 21.10 0.00764088 47.0763 317.04 0.00 530.09 530.09 0.04171925 16.60 12.15 0.00700000 34402.9 29.08 16.87 0.00700000 47109.0
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOCKER ROOM VAV BOX FLOOR 1 LOCKER ROOM N/A N/A N/A Yes Yes Yes No 282.822 282.822 0.047129 0.00000619 4.983 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0818 0.280464 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 280.60 282.82 1.0000 0.05438330 0.047129 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00619168 60.00 48.90 11.10 0.000 280.60 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 280.62 280.62 0.05438330 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOCKER ROOM HALL VAV BOX FLOOR 1 LOCKER ROOM HALL N/A N/A N/A Yes Yes Yes No 102.425 102.425 0.017068 0.00000224 1.804 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0296 0.101571 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 101.62 102.42 1.0000 0.01969510 0.017068 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00224234 60.00 48.90 11.10 0.000 101.62 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 101.63 101.63 0.01969510 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 LOUNGE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 LOUNGE VAV BOX FLOOR 1 LOUNGE N/A N/A N/A Yes Yes Yes No 156.737 156.737 0.026118 0.00000343 2.761 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0453 0.155430 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 155.50 156.74 1.0000 0.03013863 0.026118 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00343136 60.00 48.90 11.10 0.000 155.50 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 155.52 155.52 0.03013863 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 MED GAS VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 MED GAS VAV BOX FLOOR 1 MED GAS N/A N/A N/A Yes Yes Yes No 831.015 831.015 0.029248 0.00001819 17.866 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.2405 0.824087 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 824.69 825.97 1.0000 0.03375021 0.029248 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.01819300 60.00 48.90 11.10 0.000 824.69 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.04 0.00775058 21.10 0.00775058 47.7442 655.63 0.00 824.94 824.94 0.03375021 16.60 12.15 0.00700000 34402.9 40.61 20.60 0.00700000 58845.4
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 MRI CONTROL ROOM N/A N/A N/A Yes Yes Yes No 172.644 172.644 0.028769 0.00000378 3.042 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0500 0.171205 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 171.28 172.64 1.0000 0.03319741 0.028769 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00377961 60.00 48.90 11.10 0.000 171.28 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 171.30 171.30 0.03319741 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 MRI HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 MRI HALL VAV BOX FLOOR 1 MRI HALL N/A N/A N/A Yes Yes Yes No 44.475 44.475 0.006631 0.00000097 0.790 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0129 0.044104 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 44.12 44.47 1.0000 0.00765203 0.006631 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00097366 60.00 48.90 11.10 0.000 44.12 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.07 0.00844199 21.10 0.00844199 51.9408 4.65 0.00 44.13 44.13 0.00765203 16.60 12.15 0.00700000 34402.9 22.27 14.39 0.00700000 40169.7
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 MRI ROOM N/A N/A N/A Yes Yes Yes No 441.502 441.502 0.073571 0.00000967 7.778 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.1277 0.437821 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 438.03 441.50 1.0000 0.08489552 0.073571 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00966557 60.00 48.90 11.10 0.000 438.03 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 438.07 438.07 0.08489552 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 MRI TOILET N/A N/A N/A Yes Yes Yes No 279.513 279.513 0.009780 0.00000612 6.019 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0809 0.277183 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 277.38 276.18 1.0000 0.01128503 0.009780 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00611924 60.00 48.90 11.10 0.000 277.38 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.90 0.00703504 21.10 0.00703504 43.3902 220.97 0.00 277.47 277.47 0.01128503 16.60 12.15 0.00700000 34402.9 40.76 20.64 0.00700000 58990.3
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NOURISHMENT VAV BOX FLOOR 1 NOURISHMENT N/A N/A N/A Yes Yes Yes No 85.801 85.801 0.014298 0.00000188 1.512 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0248 0.085086 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 85.13 85.80 1.0000 0.01649849 0.014298 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00187840 60.00 48.90 11.10 0.000 85.13 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 85.13 85.13 0.01649849 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NURSE HALL VAV BOX FLOOR 1 NURSE HALL N/A N/A N/A Yes Yes Yes No 135.320 135.320 0.020794 0.00000296 2.397 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0392 0.134192 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 134.25 135.32 1.0000 0.02399487 0.020794 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00296249 60.00 48.90 11.10 0.000 134.25 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.08 0.00844905 21.11 0.00844905 51.9528 10.19 0.00 134.27 134.27 0.02399487 16.60 12.15 0.00700000 34402.9 22.10 14.33 0.00700000 39998.5
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NURSE JANITOR VAV BOX FLOOR 1 NURSE JANITOR N/A N/A N/A Yes Yes Yes No 15.013 15.013 0.002502 0.00000033 0.264 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0043 0.014888 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 14.89 15.01 1.0000 0.00288681 0.002502 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00032867 60.00 48.90 11.10 0.000 14.89 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 14.90 14.90 0.00288681 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 NURSE STATION VAV BOX FLOOR 1 NURSE STATION N/A N/A N/A Yes Yes Yes No 117.078 117.078 0.019510 0.00000256 2.063 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0339 0.116102 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 116.16 117.08 1.0000 0.02251270 0.019510 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00256313 60.00 48.90 11.10 0.000 116.16 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 116.17 116.17 0.02251270 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 NURSE TOILET N/A N/A N/A Yes Yes Yes No 92.866 92.866 0.015475 0.00000203 1.636 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0269 0.092092 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 92.13 92.87 1.0000 0.01785703 0.015475 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00203307 60.00 48.90 11.10 0.000 92.13 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 92.14 92.14 0.01785703 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 OFFICE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 OFFICE VAV BOX FLOOR 1 OFFICE N/A N/A N/A Yes Yes Yes No 66.279 66.279 0.011045 0.00000145 1.168 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0192 0.065727 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 65.76 66.28 1.0000 0.01274473 0.011045 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00145102 60.00 48.90 11.10 0.000 65.76 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 65.76 65.76 0.01274473 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 OPERATING ROOM 1 VAV BOX FLOOR 1 OPERATING ROOM 1 N/A N/A N/A Yes Yes Yes No 1072.824 1072.824 0.434164 0.00002349 18.194 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.3105 1.063879 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1064.63 1072.82 1.0000 0.50099313 0.434164 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.02348680 60.00 48.90 11.10 0.000 1064.63 -32.70 0.00018338 -32.70 0.00000000 0.0000 18.10 0.00800000 18.10 0.00800000 59.3495 0.00 0.00 1064.67 1064.67 0.50099313 16.60 12.15 0.00700000 34402.9 18.69 13.00 0.00700000 36528.1
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 OPERATING ROOM 2 VAV BOX FLOOR 1 OPERATING ROOM 2 N/A N/A N/A Yes Yes Yes No 0.000 0.000 0.453041 0.00000000 1.000 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:10:00 0.00 0.00 1.0000 0.52277544 0.453041 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00000000 60.00 48.90 11.10 0.000 0.00 -32.70 0.00018338 -32.70 0.00000000 0.0000 18.12 0.00159491 4.15 0.00159491 30.2064 2.84 0.00 0.00 0.00 0.52277544 16.60 12.15 0.00700000 34402.9 16.60 12.15 0.00700000 34402.9
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 OPERATING ROOM 3 VAV BOX FLOOR 1 OPERATING ROOM 3 N/A N/A N/A Yes Yes Yes No 1850.232 1850.232 0.748776 0.00004051 31.379 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.5355 1.834806 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1836.11 1850.23 1.0000 0.86403163 0.748776 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.04050622 60.00 48.90 11.10 0.000 1836.11 -32.70 0.00018338 -32.70 0.00000000 0.0000 18.10 0.00800000 18.10 0.00800000 59.3495 0.00 0.00 1836.18 1836.18 0.86403163 16.60 12.15 0.00700000 34402.9 18.69 13.00 0.00700000 36528.1
FLOOR 1 PACU VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PACU VAV BOX FLOOR 1 PACU N/A N/A N/A Yes Yes Yes No 305.855 305.855 0.050967 0.00000670 5.388 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0885 0.303305 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 303.45 305.85 1.0000 0.05881224 0.050967 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00669593 60.00 48.90 11.10 0.000 303.45 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 303.48 303.48 0.05881224 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PRE-OP HALL VAV BOX FLOOR 1 PRE-OP HALL N/A N/A N/A Yes Yes Yes No 120.639 120.639 0.020103 0.00000264 2.125 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0349 0.119633 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 119.69 120.64 1.0000 0.02319737 0.020103 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00264108 60.00 48.90 11.10 0.000 119.69 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 119.70 119.70 0.02319737 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PRE-OP ROOM 1 VAV BOX FLOOR 1 PRE-OP ROOM 1 N/A N/A N/A Yes Yes Yes No 535.246 535.246 0.089192 0.00001172 9.430 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.1549 0.530783 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 531.03 535.25 1.0000 0.10292142 0.089192 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.01171787 60.00 48.90 11.10 0.000 531.03 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 531.08 531.08 0.10292142 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PRE-OP ROOM 2 VAV BOX FLOOR 1 PRE-OP ROOM 2 N/A N/A N/A Yes Yes Yes No 957.212 957.212 0.159508 0.00002096 16.864 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.2770 0.949232 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 949.68 957.21 1.0000 0.18406053 0.159508 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.02095577 60.00 48.90 11.10 0.000 949.68 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 949.77 949.77 0.18406053 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 PRE-OP TOILET N/A N/A N/A Yes Yes Yes No 354.485 354.485 0.012429 0.00000776 7.629 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.1026 0.351530 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 351.79 351.00 1.0000 0.01434234 0.012429 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00776057 60.00 48.90 11.10 0.000 351.79 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.96 0.00752833 21.10 0.00752833 46.3922 279.99 0.00 351.89 351.89 0.01434234 16.60 12.15 0.00700000 34402.9 40.70 20.63 0.00700000 58938.2
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 PROCEDURE ROOM VAV BOX FLOOR 1 PROCEDURE ROOM N/A N/A N/A Yes Yes Yes No 2409.631 2409.631 0.336241 0.00005276 43.008 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.6972 2.389541 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2390.54 2409.63 1.0000 0.38799740 0.336241 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.05275285 60.00 48.90 11.10 0.000 2390.54 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.88 0.00663270 21.10 0.00663270 40.9302 397.47 0.00 2390.81 2390.81 0.38799740 16.60 12.15 0.00700000 34402.9 22.65 14.54 0.00700000 40564.9
FLOOR 1 RECEPTION VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 RECEPTION VAV BOX FLOOR 1 RECEPTION N/A N/A N/A Yes Yes Yes No 0.000 0.000 0.036799 0.00000000 1.000 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 0.00 0.00 1.0000 0.04246296 0.036799 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00000000 60.00 48.90 11.10 0.000 0.00 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.66 0.00163629 2.29 0.00163629 35.3362 37.44 0.00 0.00 0.00 0.04246296 16.60 12.15 0.00700000 34402.9 16.60 12.15 0.00700000 34402.9
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 RECEPTION HALL VAV BOX FLOOR 1 RECEPTION HALL N/A N/A N/A Yes Yes Yes No 31.025 31.025 0.005170 0.00000068 0.547 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0090 0.030766 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 30.78 31.02 1.0000 0.00596568 0.005170 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00067921 60.00 48.90 11.10 0.000 30.78 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 30.78 30.78 0.00596568 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 RECOVERY ROOM VAV BOX FLOOR 1 RECOVERY ROOM N/A N/A N/A Yes Yes Yes No 3021.083 3021.083 0.236297 0.00006615 57.586 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.8740 2.995896 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2996.80 3021.08 1.0000 0.27266933 0.236297 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.06613907 60.00 48.90 11.10 0.000 2996.80 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.87 0.00758559 21.10 0.00758559 46.7389 1604.49 0.00 2997.08 2997.08 0.27266933 16.60 12.15 0.00700000 34402.9 27.40 16.28 0.00700000 45394.6
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 SCHEDULING VAV BOX FLOOR 1 SCHEDULING N/A N/A N/A Yes Yes Yes No 143.483 143.483 0.005031 0.00000314 3.088 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0415 0.142286 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 142.39 143.48 1.0000 0.00580552 0.005031 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00314119 60.00 48.90 11.10 0.000 142.39 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.00 0.00448075 21.10 0.00448075 27.7476 113.50 0.00 142.43 142.43 0.00580552 16.60 12.15 0.00700000 34402.9 40.70 20.63 0.00700000 58937.1
FLOOR 1 SCRUB VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 SCRUB VAV BOX FLOOR 1 SCRUB N/A N/A N/A Yes Yes Yes No 153.167 153.167 0.005376 0.00000335 3.295 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0443 0.151890 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 152.00 153.17 1.0000 0.00620343 0.005376 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00335321 60.00 48.90 11.10 0.000 152.00 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.96 0.00800000 21.10 0.00800000 49.2560 120.91 0.00 152.05 152.05 0.00620343 16.60 12.15 0.00700000 34402.9 40.68 20.62 0.00700000 58913.1
FLOOR 1 SOIL VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 SOIL N/A N/A N/A Yes Yes Yes No 300.962 300.962 0.050152 0.00000659 5.302 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0871 0.298453 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 298.59 300.96 1.0000 0.05787151 0.050152 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00658882 60.00 48.90 11.10 0.000 298.59 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 298.62 298.62 0.05787151 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 SOIL HOLD N/A N/A N/A Yes Yes Yes No 0.000 0.000 0.019575 0.00000000 1.000 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 0.00 0.00 1.0000 0.02258806 0.019575 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00000000 60.00 48.90 11.10 0.000 0.00 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.84 0.00179826 2.31 0.00179826 38.7656 2.26 0.00 0.00 0.00 0.02258806 16.60 12.15 0.00700000 34402.9 16.60 12.15 0.00700000 34402.9
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown FLOOR 1 SOIL WORK N/A N/A N/A Yes Yes Yes No 399.778 399.778 0.066618 0.00000875 7.043 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.1157 0.396445 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 396.63 399.78 1.0000 0.07687256 0.066618 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00875214 60.00 48.90 11.10 0.000 396.63 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 396.67 396.67 0.07687256 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STEP DOWN VAV BOX FLOOR 1 STEP DOWN N/A N/A N/A Yes Yes Yes No 2002.407 2002.407 0.111399 0.00004384 39.513 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.5797 1.985712 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1987.92 2002.41 1.0000 0.12854635 0.111399 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.04383770 60.00 48.90 11.10 0.000 1987.92 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.96 0.00770945 21.10 0.00770945 47.4927 1334.42 0.00 1988.24 1988.24 0.12854635 16.60 12.15 0.00700000 34402.9 31.80 17.80 0.00700000 49870.0
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STERILE HALL VAV BOX FLOOR 1 STERILE HALL N/A N/A N/A Yes Yes Yes No 436.850 436.850 0.020000 0.00000956 8.876 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.1265 0.433208 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 433.65 436.85 1.0000 0.02307812 0.020000 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00956374 60.00 48.90 11.10 0.000 433.65 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.02 0.00797776 21.10 0.00797776 49.1208 316.84 0.00 433.74 433.74 0.02307812 16.60 12.15 0.00700000 34402.9 35.06 18.87 0.00700000 53197.3
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STERILE STORAGE VAV BOX FLOOR 1 STERILE STORAGE N/A N/A N/A Yes Yes Yes No 73.119 73.119 0.012184 0.00000160 1.288 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0212 0.072509 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 72.54 73.12 1.0000 0.01405989 0.012184 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00160076 60.00 48.90 11.10 0.000 72.54 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 72.55 72.55 0.01405989 16.60 12.15 0.00700000 34402.9 21.67 14.17 0.00700000 39563.0
FLOOR 1 STORAGE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 STORAGE VAV BOX FLOOR 1 STORAGE N/A N/A N/A Yes Yes Yes No 5754.649 5754.649 0.201576 0.00012600 123.878 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 1.6654 5.706671 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5710.81 5692.52 1.0000 0.23260340 0.201576 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.12598366 60.00 48.90 11.10 0.000 5710.81 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.96 0.00789417 21.10 0.00789417 48.6139 4545.33 0.00 5712.57 5712.57 0.23260340 16.60 12.15 0.00700000 34402.9 40.73 20.64 0.00700000 58962.2
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 SUB-STERILE VAV BOX FLOOR 1 SUB-STERILE N/A N/A N/A Yes Yes Yes No 1044.775 1044.775 0.036564 0.00002288 22.496 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.3024 1.036064 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1036.82 1044.78 1.0000 0.04219173 0.036564 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.02287274 60.00 48.90 11.10 0.000 1036.82 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.91 0.00759698 21.10 0.00759698 46.8091 825.59 0.00 1037.14 1037.14 0.04219173 16.60 12.15 0.00700000 34402.9 40.75 20.64 0.00700000 58984.4
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 UTILITY HALL VAV BOX FLOOR 1 UTILITY HALL N/A N/A N/A Yes Yes Yes No 1697.904 1697.904 0.059516 0.00003718 36.543 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.4914 1.683748 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1684.97 1680.74 1.0000 0.06867721 0.059516 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.03717137 60.00 48.90 11.10 0.000 1684.97 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.96 0.00787059 21.10 0.00787059 48.4708 1340.87 0.00 1685.49 1685.49 0.06867721 16.60 12.15 0.00700000 34402.9 40.71 20.63 0.00700000 58945.1
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 UTILITY JANITOR VAV BOX FLOOR 1 UTILITY JANITOR N/A N/A N/A Yes Yes Yes No 72.068 72.068 0.002535 0.00000158 1.550 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.0209 0.071467 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 71.52 72.07 1.0000 0.00292464 0.002535 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.00157775 60.00 48.90 11.10 0.000 71.52 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.98 0.00800000 21.10 0.00800000 49.2560 56.86 0.00 71.54 71.54 0.00292464 16.60 12.15 0.00700000 34402.9 40.63 20.61 0.00700000 58864.4
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 UTILITY ROOM VAV BOX FLOOR 1 UTILITY ROOM N/A N/A N/A Yes Yes Yes No 1750.457 1750.457 0.061199 0.00003833 37.701 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.5066 1.735863 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1737.12 1728.27 1.0000 0.07061935 0.061199 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.03832188 60.00 48.90 11.10 0.000 1737.12 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.91 0.00766381 21.10 0.00766381 47.2148 1383.51 0.00 1737.66 1737.66 0.07061935 16.60 12.15 0.00700000 34402.9 40.77 20.65 0.00700000 59008.9
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 1 VESTIBULE VAV BOX FLOOR 1 VESTIBULE N/A N/A N/A Yes Yes Yes No 471.097 471.097 0.016515 0.00001031 10.139 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 0.1363 0.467169 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 467.51 466.40 1.0000 0.01905760 0.016515 16.00 11.53 0.00700000 33792.2 40.00 20.66 0.00800000 60796.0 0.01031349 60.00 48.90 11.10 0.000 467.51 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.96 0.00756753 21.10 0.00756753 46.6305 372.10 0.00 467.65 467.65 0.01905760 16.60 12.15 0.00700000 34402.9 40.71 20.63 0.00700000 58941.8
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 CONFERENCE VAV BOX FLOOR 2 CONFERENCE N/A N/A N/A Yes No unknown No 2088.674 2088.674 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2088.67 2088.67 1.0000 0.08534578 0.073961 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2088.67 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.96 0.00792617 21.10 0.00792617 48.8093 1667.32 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL Coil:Heating:Electric Unknown Unknown Unknown FLOOR 2 CONFERENCE TOILET N/A N/A N/A Yes No unknown No 552.555 552.555 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 552.56 121.00 1.0000 0.00494414 0.004285 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 552.56 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.99 0.00800000 21.10 0.00800000 49.2560 96.37 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 DICTATION VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 DICTATION VAV BOX FLOOR 2 DICTATION N/A N/A N/A Yes No unknown No 118.886 118.886 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 118.89 79.30 1.0000 0.00324012 0.002808 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 118.89 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 1 VAV BOX FLOOR 2 EXAM 1 N/A N/A N/A Yes No unknown No 3474.263 3474.263 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3474.26 2124.77 1.0000 0.08682083 0.075240 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3474.26 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.96 0.00759088 21.10 0.00759088 46.7727 1697.23 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 2 VAV BOX FLOOR 2 EXAM 2 N/A N/A N/A Yes No unknown No 7196.583 7196.583 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 7196.58 2158.98 1.0000 0.08821839 0.076451 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7196.58 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.83 0.00794039 21.10 0.00794039 48.8939 691.10 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 3 VAV BOX FLOOR 2 EXAM 3 N/A N/A N/A Yes No unknown No 9595.444 9595.444 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 9595.44 2878.63 1.0000 0.11762451 0.101934 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9595.44 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.82 0.00790766 21.10 0.00790766 48.6950 924.75 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 4 VAV BOX FLOOR 2 EXAM 4 N/A N/A N/A Yes No unknown No 893.967 893.967 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 893.97 507.25 1.0000 0.02072705 0.017962 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 893.97 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.97 0.00773681 21.10 0.00773681 47.6589 404.97 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 5 VAV BOX FLOOR 2 EXAM 5 N/A N/A N/A Yes No unknown No 4036.938 4036.938 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4036.94 1561.35 1.0000 0.06379859 0.055288 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4036.94 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.92 0.00763799 21.10 0.00763799 47.0580 1251.23 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 6 VAV BOX FLOOR 2 EXAM 6 N/A N/A N/A Yes No unknown No 2818.662 2818.662 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2818.66 899.57 1.0000 0.03675766 0.031854 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2818.66 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.87 0.00749786 21.10 0.00749786 46.2057 699.46 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 7 VAV BOX FLOOR 2 EXAM 7 N/A N/A N/A Yes No unknown No 10554.988 10554.988 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10554.99 3166.50 1.0000 0.12938697 0.112128 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10554.99 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.91 0.00901273 21.10 0.00901273 55.4009 476.69 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 8 VAV BOX FLOOR 2 EXAM 8 N/A N/A N/A Yes No unknown No 3346.411 3346.411 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3346.41 1079.49 1.0000 0.04410919 0.038225 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3346.41 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.86 0.00720307 21.10 0.00720307 44.4114 749.64 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM 9 VAV BOX FLOOR 2 EXAM 9 N/A N/A N/A Yes No unknown No 5277.494 5277.494 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5277.49 1583.25 1.0000 0.06469348 0.056064 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5277.49 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.88 0.00864744 21.10 0.00864744 53.1861 388.53 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 1 VAV BOX FLOOR 2 EXAM HALL 1 N/A N/A N/A Yes No unknown No 513.240 513.240 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 513.24 513.24 1.0000 0.02097161 0.018174 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 513.24 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.93 0.00800000 21.10 0.00800000 49.2560 410.91 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 2 VAV BOX FLOOR 2 EXAM HALL 2 N/A N/A N/A Yes No unknown No 323.559 323.559 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 323.56 323.56 1.0000 0.01322101 0.011457 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 323.56 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.96 0.00800000 21.10 0.00800000 49.2560 257.94 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 3 VAV BOX FLOOR 2 EXAM HALL 3 N/A N/A N/A Yes No unknown No 335.298 335.298 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 335.30 335.30 1.0000 0.01370067 0.011873 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 335.30 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.95 0.00800000 21.10 0.00800000 49.2560 267.41 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 4 VAV BOX FLOOR 2 EXAM HALL 4 N/A N/A N/A Yes No unknown No 237.328 237.328 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 237.33 205.66 1.0000 0.00840351 0.007283 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 237.33 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.01 0.00799944 21.10 0.00799944 49.2525 163.48 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 5 VAV BOX FLOOR 2 EXAM HALL 5 N/A N/A N/A Yes No unknown No 237.930 237.930 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 237.93 208.01 1.0000 0.00849965 0.007366 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 237.93 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.01 0.00799936 21.10 0.00799936 49.2521 165.30 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 EXAM HALL 6 VAV BOX FLOOR 2 EXAM HALL 6 N/A N/A N/A Yes No unknown No 283.919 283.919 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 283.92 283.92 1.0000 0.01160127 0.010054 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 283.92 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.98 0.00800000 21.10 0.00800000 49.2559 226.11 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 JANITOR VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 JANITOR VAV BOX FLOOR 2 JANITOR N/A N/A N/A Yes No unknown No 661.065 661.065 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 661.07 661.07 1.0000 0.02701194 0.023409 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 661.07 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.00 0.00736517 21.10 0.00736517 45.4031 525.53 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 LOUNGE VAV BOX FLOOR 2 LOUNGE N/A N/A N/A Yes No unknown No 216.196 216.196 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 216.20 143.93 1.0000 0.00588122 0.005097 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 216.20 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 NURSE STATION 1 VAV BOX FLOOR 2 NURSE STATION 1 N/A N/A N/A Yes No unknown No 479.721 479.721 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 479.72 319.85 1.0000 0.01306939 0.011326 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 479.72 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 NURSE STATION 2 VAV BOX FLOOR 2 NURSE STATION 2 N/A N/A N/A Yes No unknown No 576.075 576.075 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 576.08 383.82 1.0000 0.01568326 0.013591 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 576.08 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 OFFICE VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 OFFICE VAV BOX FLOOR 2 OFFICE N/A N/A N/A Yes No unknown No 2682.350 2682.350 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2682.35 2682.35 1.0000 0.10960410 0.094984 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2682.35 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.91 0.00748601 21.10 0.00748601 46.1343 2147.89 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 OFFICE HALL VAV BOX FLOOR 2 OFFICE HALL N/A N/A N/A Yes No unknown No 833.192 833.192 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 833.19 833.19 1.0000 0.03404524 0.029504 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 833.19 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.94 0.00800000 21.10 0.00800000 49.2560 665.40 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 RECEPTION VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 RECEPTION VAV BOX FLOOR 2 RECEPTION N/A N/A N/A Yes No unknown No 4135.986 4135.986 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4135.99 3176.76 1.0000 0.12980624 0.112491 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4135.99 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.87 0.00774062 21.10 0.00774062 47.6812 2560.94 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 RECEPTION HALL VAV BOX FLOOR 2 RECEPTION HALL N/A N/A N/A Yes No unknown No 677.989 677.989 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 677.99 450.99 1.0000 0.01842784 0.015970 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 677.99 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL Coil:Heating:Electric Unknown Unknown Unknown FLOOR 2 RECEPTION TOILET N/A N/A N/A Yes No unknown No 1005.895 1005.895 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1005.89 87.54 1.0000 0.00357696 0.003100 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1005.89 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.03 0.00800778 21.10 0.00800778 49.3033 69.47 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 SCHEDULING 1 VAV BOX FLOOR 2 SCHEDULING 1 N/A N/A N/A Yes No unknown No 551.185 551.185 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 551.19 367.03 1.0000 0.01499712 0.012997 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 551.19 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 SCHEDULING 2 VAV BOX FLOOR 2 SCHEDULING 2 N/A N/A N/A Yes No unknown No 580.295 580.295 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 580.30 387.42 1.0000 0.01583030 0.013719 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 580.30 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 STORAGE 1 VAV BOX FLOOR 2 STORAGE 1 N/A N/A N/A Yes No unknown No 134.340 134.340 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 134.34 103.83 1.0000 0.00424271 0.003677 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 134.34 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.99 0.00800000 21.10 0.00800000 49.2560 82.60 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 STORAGE 2 VAV BOX FLOOR 2 STORAGE 2 N/A N/A N/A Yes No unknown No 287.934 287.934 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 287.93 191.91 1.0000 0.00784163 0.006796 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 287.93 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.01 0.00799980 21.10 0.00799980 49.2547 95.85 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 STORAGE 3 VAV BOX FLOOR 2 STORAGE 3 N/A N/A N/A Yes No unknown No 345.586 345.586 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 345.59 230.29 1.0000 0.00940996 0.008155 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 345.59 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.02 0.00799883 21.10 0.00799883 49.2488 101.24 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 UTILITY VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 UTILITY VAV BOX FLOOR 2 UTILITY N/A N/A N/A Yes No unknown No 766.155 766.155 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 766.16 766.16 1.0000 0.03130605 0.027130 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 766.16 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.96 0.00757727 21.10 0.00757727 46.6896 611.68 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 WORK VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 WORK VAV BOX FLOOR 2 WORK N/A N/A N/A Yes No unknown No 2868.983 2868.983 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2868.98 1914.42 1.0000 0.07822573 0.067791 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2868.98 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.90 0.00674259 21.10 0.00674259 41.5993 1305.51 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 WORK HALL VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 2 WORK HALL VAV BOX FLOOR 2 WORK HALL N/A N/A N/A Yes No unknown No 1002.269 1002.269 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 1002.27 666.88 1.0000 0.02724968 0.023615 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1002.27 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.04 0.00094030 2.34 0.00094030 20.2660 9.13 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL Coil:Heating:Electric Unknown Unknown Unknown FLOOR 2 WORK TOILET N/A N/A N/A Yes No unknown No 519.230 519.230 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 519.23 397.21 1.0000 0.01623042 0.014065 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 519.23 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.95 0.00751387 21.10 0.00751387 46.3046 316.49 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 2 X-RAY VAV BOX REHEAT COIL Coil:Heating:Electric Unknown Unknown Unknown FLOOR 2 X-RAY N/A N/A N/A Yes No unknown No 5408.922 5408.922 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 5408.92 3598.29 1.0000 0.14703064 0.127418 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5408.92 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.10 0.00800000 21.10 0.00800000 49.2560 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 DRESSING ROOM VAV BOX FLOOR 3 DRESSING ROOM N/A N/A N/A Yes No unknown No 181.816 181.816 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 181.82 181.82 1.0000 0.00742921 0.006438 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 181.82 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.90 0.00571322 21.09 0.00571322 35.3174 145.94 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 ELEVATOR HALL VAV BOX FLOOR 3 ELEVATOR HALL N/A N/A N/A Yes No unknown No 1443.692 1443.692 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1443.69 1443.69 1.0000 0.05899102 0.051122 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1443.69 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.92 0.00799723 21.10 0.00799723 49.2392 1159.91 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 HUMID VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 HUMID VAV BOX FLOOR 3 HUMID N/A N/A N/A Yes No unknown No 394.626 394.626 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 394.63 394.63 1.0000 0.01612489 0.013974 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 394.63 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.91 0.00527123 21.09 0.00527123 32.6086 317.66 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 JANITOR VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 JANITOR VAV BOX FLOOR 3 JANITOR N/A N/A N/A Yes No unknown No 634.549 634.549 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 634.55 634.55 1.0000 0.02592844 0.022470 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 634.55 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.00 0.00783410 21.10 0.00783410 48.2497 504.62 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 LOCKER VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 LOCKER VAV BOX FLOOR 3 LOCKER N/A N/A N/A Yes No unknown No 403.569 403.569 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 403.57 403.57 1.0000 0.01649034 0.014291 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 403.57 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.87 0.00634530 21.10 0.00634530 39.1793 325.02 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 LOUNGE VAV BOX FLOOR 3 LOUNGE N/A N/A N/A Yes No unknown No 2050.362 2050.362 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2050.36 1515.02 1.0000 0.06190550 0.053648 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2050.36 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.83 0.01141704 21.10 0.01141704 69.8992 1237.33 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL Coil:Heating:Electric Unknown Unknown Unknown FLOOR 3 LOUNGE TOILET N/A N/A N/A Yes No unknown No 1486.406 1486.406 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1486.41 1081.88 1.0000 0.04420711 0.038310 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1486.41 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.96 0.00797189 21.10 0.00797189 49.0854 864.73 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 MECHANICAL VAV BOX FLOOR 3 MECHANICAL N/A N/A N/A Yes No unknown No 493.798 493.798 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 493.80 493.80 1.0000 0.02017720 0.017486 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 493.80 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.95 0.00763948 21.10 0.00763948 47.0638 398.61 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 MECHANICAL HALL VAV BOX FLOOR 3 MECHANICAL HALL N/A N/A N/A Yes No unknown No 1531.872 1531.872 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1531.87 1531.87 1.0000 0.06259417 0.054245 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1531.87 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.90 0.00714546 21.10 0.00714546 44.0618 1225.99 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 OFFICE VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 OFFICE VAV BOX FLOOR 3 OFFICE N/A N/A N/A Yes No unknown No 8748.535 8748.535 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8748.53 8748.53 1.0000 0.35747587 0.309791 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8748.53 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.87 0.00817958 21.10 0.00817958 50.3462 7074.82 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 OFFICE HALL VAV BOX FLOOR 3 OFFICE HALL N/A N/A N/A Yes No unknown No 3136.630 3136.630 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3136.63 3136.63 1.0000 0.12816656 0.111070 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3136.63 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.92 0.00799711 21.10 0.00799711 49.2384 2521.33 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL Coil:Heating:Electric Unknown Unknown Unknown FLOOR 3 OFFICE TOILET N/A N/A N/A Yes No unknown No 424.310 424.310 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 424.31 424.31 1.0000 0.01733782 0.015025 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 424.31 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.01 0.00794706 21.10 0.00794706 48.9348 338.12 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 PHYSICAL THERAPY 1 VAV BOX FLOOR 3 PHYSICAL THERAPY 1 N/A N/A N/A Yes No unknown No 14035.787 14035.787 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 14035.79 5950.00 1.0000 0.24312422 0.210693 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 14035.79 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.97 0.00823616 21.10 0.00823616 50.6892 4771.40 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 PHYSICAL THERAPY 2 VAV BOX FLOOR 3 PHYSICAL THERAPY 2 N/A N/A N/A Yes No unknown No 6548.357 6548.357 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6548.36 2366.88 1.0000 0.09671349 0.083813 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6548.36 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.87 0.00668336 21.10 0.00668336 41.2426 1449.95 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL Coil:Heating:Electric Unknown Unknown Unknown FLOOR 3 PHYSICAL THERAPY TOILET N/A N/A N/A Yes No unknown No 690.608 690.608 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 690.61 348.87 1.0000 0.01425521 0.012354 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 690.61 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.90 0.00600414 21.09 0.00600414 37.0974 280.16 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 STORAGE 1 VAV BOX FLOOR 3 STORAGE 1 N/A N/A N/A Yes No unknown No 692.633 692.633 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 692.63 509.90 1.0000 0.02083520 0.018056 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 692.63 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.91 0.00695318 21.10 0.00695318 42.8903 408.29 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 STORAGE 2 VAV BOX FLOOR 3 STORAGE 2 N/A N/A N/A Yes No unknown No 435.455 435.455 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 435.45 435.45 1.0000 0.01779321 0.015420 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 435.45 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.91 0.00713019 21.10 0.00713019 43.9689 348.30 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 TREATMENT VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 TREATMENT VAV BOX FLOOR 3 TREATMENT N/A N/A N/A Yes No unknown No 5138.360 5138.360 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5138.36 1903.10 1.0000 0.07776287 0.067390 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5138.36 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.87 0.00621356 21.10 0.00621356 38.3739 1109.93 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 UNDEVELOPED 1 VAV BOX FLOOR 3 UNDEVELOPED 1 N/A N/A N/A Yes No unknown No 7691.374 7691.374 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 7691.37 7691.37 1.0000 0.31427899 0.272357 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7691.37 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.92 0.00798049 21.10 0.00798049 49.1375 6198.53 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 UNDEVELOPED 2 VAV BOX FLOOR 3 UNDEVELOPED 2 N/A N/A N/A Yes No unknown No 5047.388 5047.388 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5047.39 5047.39 1.0000 0.20624246 0.178731 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5047.39 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.91 0.00797505 21.10 0.00797505 49.1045 4049.76 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 UTILITY VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 UTILITY VAV BOX FLOOR 3 UTILITY N/A N/A N/A Yes No unknown No 892.290 892.290 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 892.29 892.29 1.0000 0.03646006 0.031597 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 892.29 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.92 0.00682127 21.10 0.00682127 42.0860 716.14 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FLOOR 3 WORK VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT FLOOR 3 WORK VAV BOX FLOOR 3 WORK N/A N/A N/A Yes No unknown No 2982.527 2982.527 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2982.53 2982.53 1.0000 0.12186970 0.105613 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2982.53 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.96 0.00802407 21.10 0.00802407 49.4022 2386.76 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
NE STAIR VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT NE STAIR VAV BOX NE STAIR N/A N/A N/A Yes No unknown No 4551.584 4551.584 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4551.58 4551.58 1.0000 0.18598329 0.161175 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4551.58 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.00 0.00775942 21.10 0.00775942 47.7972 3622.88 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
NW ELEVATOR VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT NW ELEVATOR VAV BOX NW ELEVATOR N/A N/A N/A Yes No unknown No 2984.036 2984.036 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2984.04 2984.04 1.0000 0.12193138 0.105667 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2984.04 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.95 0.00771168 21.10 0.00771168 47.5066 2379.85 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
NW STAIR VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT NW STAIR VAV BOX NW STAIR N/A N/A N/A Yes No unknown No 4663.853 4663.853 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4663.85 4663.85 1.0000 0.19057076 0.165150 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4663.85 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.01 0.00772773 21.10 0.00772773 47.6047 3715.91 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SW STAIR VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT SW STAIR VAV BOX SW STAIR N/A N/A N/A Yes No unknown No 2276.441 2276.441 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2276.44 2276.44 1.0000 0.09301815 0.080610 16.00 12.32 0.00780000 35816.8 40.00 20.66 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2276.44 -32.70 0.00018338 -32.70 0.00000000 0.0000 21.01 0.00771553 21.10 0.00771553 47.5302 1814.15 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AHU-1_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC AHU-1 FLOOR 1 ANESTHESIA; FLOOR 1 BIO HAZ; FLOOR 1 CAFE; FLOOR 1 CLEAN; FLOOR 1 CLEAN WORK; FLOOR 1 DICTATION; FLOOR 1 DRESSING ROOM; FLOOR 1 ELECTRICAL ROOM; FLOOR 1 ELEVATOR PUMP ROOM; FLOOR 1 HUMID; FLOOR 1 IT HALL; FLOOR 1 IT ROOM; FLOOR 1 LOBBY; FLOOR 1 LOBBY HALL; FLOOR 1 LOBBY TOILET; FLOOR 1 LOCKER ROOM; FLOOR 1 LOCKER ROOM HALL; FLOOR 1 LOUNGE; FLOOR 1 MED GAS; FLOOR 1 MRI CONTROL ROOM; FLOOR 1 MRI HALL; FLOOR 1 MRI ROOM; FLOOR 1 MRI TOILET; FLOOR 1 NOURISHMENT; FLOOR 1 NURSE HALL; FLOOR 1 NURSE JANITOR; FLOOR 1 NURSE STATION; FLOOR 1 NURSE TOILET; FLOOR 1 OFFICE; FLOOR 1 OPERATING ROOM 1; FLOOR 1 OPERATING ROOM 2; FLOOR 1 OPERATING ROOM 3; FLOOR 1 PACU; FLOOR 1 PRE-OP HALL; FLOOR 1 PRE-OP ROOM 1; FLOOR 1 PRE-OP ROOM 2; FLOOR 1 PRE-OP TOILET; FLOOR 1 PROCEDURE ROOM; FLOOR 1 RECEPTION; FLOOR 1 RECEPTION HALL; FLOOR 1 RECOVERY ROOM; FLOOR 1 SCHEDULING; FLOOR 1 SCRUB; FLOOR 1 SOIL; FLOOR 1 SOIL HOLD; FLOOR 1 SOIL WORK; FLOOR 1 STEP DOWN; FLOOR 1 STERILE HALL; FLOOR 1 STERILE STORAGE; FLOOR 1 STORAGE; FLOOR 1 SUB-STERILE; FLOOR 1 UTILITY HALL; FLOOR 1 UTILITY JANITOR; FLOOR 1 UTILITY ROOM; FLOOR 1 VESTIBULE; Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 176331.530 123094.082 7.100871 -999.0 -999.000 -999.0000 1.00000 0.89680 1023.4652 1004.8586 1.1539 AHU-1_FAN Fan:VariableVolume 7.100871 8.19387122   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 175604.37 113495.35 1.0041 8.19387122 7.100871 21.88 16.48 0.01001922 47451.9 5.27 5.27 0.00700000 22866.9 -999.0 -999.00 -999.00 -999.00 16216.456 159387.92 23.81 0.01270325 19.22 2.07098422 29.1652 21.06 0.00887222 21.04 0.00887222 54.7565 76640.86 0.00 176775.54 121649.73 7.86946365 26.67 19.44 0.01117891 55307.7 11.52 11.50 0.00843239 32844.2
AHU-1_HEATC Coil:Heating:Water AirLoop AirLoopHVAC AHU-1 FLOOR 1 ANESTHESIA; FLOOR 1 BIO HAZ; FLOOR 1 CAFE; FLOOR 1 CLEAN; FLOOR 1 CLEAN WORK; FLOOR 1 DICTATION; FLOOR 1 DRESSING ROOM; FLOOR 1 ELECTRICAL ROOM; FLOOR 1 ELEVATOR PUMP ROOM; FLOOR 1 HUMID; FLOOR 1 IT HALL; FLOOR 1 IT ROOM; FLOOR 1 LOBBY; FLOOR 1 LOBBY HALL; FLOOR 1 LOBBY TOILET; FLOOR 1 LOCKER ROOM; FLOOR 1 LOCKER ROOM HALL; FLOOR 1 LOUNGE; FLOOR 1 MED GAS; FLOOR 1 MRI CONTROL ROOM; FLOOR 1 MRI HALL; FLOOR 1 MRI ROOM; FLOOR 1 MRI TOILET; FLOOR 1 NOURISHMENT; FLOOR 1 NURSE HALL; FLOOR 1 NURSE JANITOR; FLOOR 1 NURSE STATION; FLOOR 1 NURSE TOILET; FLOOR 1 OFFICE; FLOOR 1 OPERATING ROOM 1; FLOOR 1 OPERATING ROOM 2; FLOOR 1 OPERATING ROOM 3; FLOOR 1 PACU; FLOOR 1 PRE-OP HALL; FLOOR 1 PRE-OP ROOM 1; FLOOR 1 PRE-OP ROOM 2; FLOOR 1 PRE-OP TOILET; FLOOR 1 PROCEDURE ROOM; FLOOR 1 RECEPTION; FLOOR 1 RECEPTION HALL; FLOOR 1 RECOVERY ROOM; FLOOR 1 SCHEDULING; FLOOR 1 SCRUB; FLOOR 1 SOIL; FLOOR 1 SOIL HOLD; FLOOR 1 SOIL WORK; FLOOR 1 STEP DOWN; FLOOR 1 STERILE HALL; FLOOR 1 STERILE STORAGE; FLOOR 1 STORAGE; FLOOR 1 SUB-STERILE; FLOOR 1 UTILITY HALL; FLOOR 1 UTILITY JANITOR; FLOOR 1 UTILITY ROOM; FLOOR 1 VESTIBULE; Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 92954.514 92954.514 7.100871 0.00203521 1468.341 -999.0000 1.00000 1.00000 1017.8526 1004.8586 1.1539 AHU-1_FAN Fan:VariableVolume 7.100871 8.19387122   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 22.9965 92.179520 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:50:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 78855.15 92954.51 1.0000 8.19387122 7.100871 -23.52 -23.52 0.00141751 -20151.0 16.00 11.53 0.00700000 33792.2 2.03500684 60.00 48.90 11.10 0.000 78855.15 -32.70 0.00018338 -32.70 2.07098422 29.1652 20.11 0.00728370 18.36 0.00728370 53.2145 17705.92 0.00 78848.47 78848.47 8.19387122 16.60 10.29 0.00521287 29878.3 26.09 14.17 0.00521287 39501.1
AHU-1_EXTRAELECHEATC Coil:Heating:Electric AirLoop AirLoopHVAC AHU-1 FLOOR 1 ANESTHESIA; FLOOR 1 BIO HAZ; FLOOR 1 CAFE; FLOOR 1 CLEAN; FLOOR 1 CLEAN WORK; FLOOR 1 DICTATION; FLOOR 1 DRESSING ROOM; FLOOR 1 ELECTRICAL ROOM; FLOOR 1 ELEVATOR PUMP ROOM; FLOOR 1 HUMID; FLOOR 1 IT HALL; FLOOR 1 IT ROOM; FLOOR 1 LOBBY; FLOOR 1 LOBBY HALL; FLOOR 1 LOBBY TOILET; FLOOR 1 LOCKER ROOM; FLOOR 1 LOCKER ROOM HALL; FLOOR 1 LOUNGE; FLOOR 1 MED GAS; FLOOR 1 MRI CONTROL ROOM; FLOOR 1 MRI HALL; FLOOR 1 MRI ROOM; FLOOR 1 MRI TOILET; FLOOR 1 NOURISHMENT; FLOOR 1 NURSE HALL; FLOOR 1 NURSE JANITOR; FLOOR 1 NURSE STATION; FLOOR 1 NURSE TOILET; FLOOR 1 OFFICE; FLOOR 1 OPERATING ROOM 1; FLOOR 1 OPERATING ROOM 2; FLOOR 1 OPERATING ROOM 3; FLOOR 1 PACU; FLOOR 1 PRE-OP HALL; FLOOR 1 PRE-OP ROOM 1; FLOOR 1 PRE-OP ROOM 2; FLOOR 1 PRE-OP TOILET; FLOOR 1 PROCEDURE ROOM; FLOOR 1 RECEPTION; FLOOR 1 RECEPTION HALL; FLOOR 1 RECOVERY ROOM; FLOOR 1 SCHEDULING; FLOOR 1 SCRUB; FLOOR 1 SOIL; FLOOR 1 SOIL HOLD; FLOOR 1 SOIL WORK; FLOOR 1 STEP DOWN; FLOOR 1 STERILE HALL; FLOOR 1 STERILE STORAGE; FLOOR 1 STORAGE; FLOOR 1 SUB-STERILE; FLOOR 1 UTILITY HALL; FLOOR 1 UTILITY JANITOR; FLOOR 1 UTILITY ROOM; FLOOR 1 VESTIBULE; Non-Coincident HeatingDesignCapacity N/A No No unknown No 10000000.000 10000000.000 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1017.8526 1004.8586 1.1539 AHU-1_FAN Fan:VariableVolume 7.100871 8.19387122   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:50:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10000000.00 329605.19 1.0000 8.19387122 7.100871 -23.52 -23.52 0.00141751 -20151.0 16.00 11.53 0.00700000 33792.2 -999.0 -999.00 -999.00 -999.00 0.000 10000000.00 -32.70 0.00018338 -32.70 2.07098422 29.1652 20.11 0.00728370 18.36 0.00728370 53.2145 17705.92 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AHU-1_EXTRAWATERHEATC Coil:Heating:Water AirLoop AirLoopHVAC AHU-1 FLOOR 1 ANESTHESIA; FLOOR 1 BIO HAZ; FLOOR 1 CAFE; FLOOR 1 CLEAN; FLOOR 1 CLEAN WORK; FLOOR 1 DICTATION; FLOOR 1 DRESSING ROOM; FLOOR 1 ELECTRICAL ROOM; FLOOR 1 ELEVATOR PUMP ROOM; FLOOR 1 HUMID; FLOOR 1 IT HALL; FLOOR 1 IT ROOM; FLOOR 1 LOBBY; FLOOR 1 LOBBY HALL; FLOOR 1 LOBBY TOILET; FLOOR 1 LOCKER ROOM; FLOOR 1 LOCKER ROOM HALL; FLOOR 1 LOUNGE; FLOOR 1 MED GAS; FLOOR 1 MRI CONTROL ROOM; FLOOR 1 MRI HALL; FLOOR 1 MRI ROOM; FLOOR 1 MRI TOILET; FLOOR 1 NOURISHMENT; FLOOR 1 NURSE HALL; FLOOR 1 NURSE JANITOR; FLOOR 1 NURSE STATION; FLOOR 1 NURSE TOILET; FLOOR 1 OFFICE; FLOOR 1 OPERATING ROOM 1; FLOOR 1 OPERATING ROOM 2; FLOOR 1 OPERATING ROOM 3; FLOOR 1 PACU; FLOOR 1 PRE-OP HALL; FLOOR 1 PRE-OP ROOM 1; FLOOR 1 PRE-OP ROOM 2; FLOOR 1 PRE-OP TOILET; FLOOR 1 PROCEDURE ROOM; FLOOR 1 RECEPTION; FLOOR 1 RECEPTION HALL; FLOOR 1 RECOVERY ROOM; FLOOR 1 SCHEDULING; FLOOR 1 SCRUB; FLOOR 1 SOIL; FLOOR 1 SOIL HOLD; FLOOR 1 SOIL WORK; FLOOR 1 STEP DOWN; FLOOR 1 STERILE HALL; FLOOR 1 STERILE STORAGE; FLOOR 1 STORAGE; FLOOR 1 SUB-STERILE; FLOOR 1 UTILITY HALL; FLOOR 1 UTILITY JANITOR; FLOOR 1 UTILITY ROOM; FLOOR 1 VESTIBULE; Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 92954.514 92954.514 7.100871 0.00203521 1468.341 -999.0000 1.00000 1.00000 1017.8526 1004.8586 1.1539 AHU-1_FAN Fan:VariableVolume 7.100871 8.19387122   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 22.9965 92.179520 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:50:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 78855.15 92954.51 1.0000 8.19387122 7.100871 -23.52 -23.52 0.00141751 -20151.0 16.00 11.53 0.00700000 33792.2 2.03500684 60.00 48.90 11.10 0.000 78855.15 -32.70 0.00018338 -32.70 2.07098422 29.1652 20.11 0.00728370 18.36 0.00728370 53.2145 17705.92 0.00 0.00 0.00 8.19387122 16.60 10.29 0.00521287 29878.3 16.60 10.29 0.00521287 29878.3
AHU-2_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC AHU-2 FLOOR 2 CONFERENCE; FLOOR 2 CONFERENCE TOILET; FLOOR 2 DICTATION; FLOOR 2 EXAM 1; FLOOR 2 EXAM 2; FLOOR 2 EXAM 3; FLOOR 2 EXAM 4; FLOOR 2 EXAM 5; FLOOR 2 EXAM 6; FLOOR 2 EXAM 7; FLOOR 2 EXAM 8; FLOOR 2 EXAM 9; FLOOR 2 EXAM HALL 1; FLOOR 2 EXAM HALL 2; FLOOR 2 EXAM HALL 3; FLOOR 2 EXAM HALL 4; FLOOR 2 EXAM HALL 5; FLOOR 2 EXAM HALL 6; FLOOR 2 JANITOR; FLOOR 2 LOUNGE; FLOOR 2 NURSE STATION 1; FLOOR 2 NURSE STATION 2; FLOOR 2 OFFICE; FLOOR 2 OFFICE HALL; FLOOR 2 RECEPTION; FLOOR 2 RECEPTION HALL; FLOOR 2 RECEPTION TOILET; FLOOR 2 SCHEDULING 1; FLOOR 2 SCHEDULING 2; FLOOR 2 STORAGE 1; FLOOR 2 STORAGE 2; FLOOR 2 STORAGE 3; FLOOR 2 UTILITY; FLOOR 2 WORK; FLOOR 2 WORK HALL; FLOOR 2 WORK TOILET; FLOOR 2 X-RAY; FLOOR 3 DRESSING ROOM; FLOOR 3 ELEVATOR HALL; FLOOR 3 HUMID; FLOOR 3 JANITOR; FLOOR 3 LOCKER; FLOOR 3 LOUNGE; FLOOR 3 LOUNGE TOILET; FLOOR 3 MECHANICAL; FLOOR 3 MECHANICAL HALL; FLOOR 3 OFFICE; FLOOR 3 OFFICE HALL; FLOOR 3 OFFICE TOILET; FLOOR 3 PHYSICAL THERAPY 1; FLOOR 3 PHYSICAL THERAPY 2; FLOOR 3 PHYSICAL THERAPY TOILET; FLOOR 3 STORAGE 1; FLOOR 3 STORAGE 2; FLOOR 3 TREATMENT; FLOOR 3 UNDEVELOPED 1; FLOOR 3 UNDEVELOPED 2; FLOOR 3 UTILITY; FLOOR 3 WORK; NE STAIR; NW ELEVATOR; NW STAIR; SW STAIR; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 220453.158 156315.645 9.203000 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.3181 1004.8586 1.1539 AHU-2_FAN Fan:VariableVolume 9.203000 10.61957043   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 224599.30 164633.21 0.9815 10.61957043 9.203000 24.36 17.26 0.00994010 49790.7 9.17 9.17 0.00780000 28850.6 -999.0 -999.00 -999.00 -999.00 21017.147 203582.15 30.10 0.01270324 21.10 2.51720000 27.3520 22.20 0.00889745 22.20 0.00887405 51.0171 101699.63 0.00 221008.27 154360.98 10.19912581 26.67 19.44 0.01117891 55307.7 11.84 11.82 0.00861683 33638.4
AHU-2_HEATC Coil:Heating:Water AirLoop AirLoopHVAC AHU-2 FLOOR 2 CONFERENCE; FLOOR 2 CONFERENCE TOILET; FLOOR 2 DICTATION; FLOOR 2 EXAM 1; FLOOR 2 EXAM 2; FLOOR 2 EXAM 3; FLOOR 2 EXAM 4; FLOOR 2 EXAM 5; FLOOR 2 EXAM 6; FLOOR 2 EXAM 7; FLOOR 2 EXAM 8; FLOOR 2 EXAM 9; FLOOR 2 EXAM HALL 1; FLOOR 2 EXAM HALL 2; FLOOR 2 EXAM HALL 3; FLOOR 2 EXAM HALL 4; FLOOR 2 EXAM HALL 5; FLOOR 2 EXAM HALL 6; FLOOR 2 JANITOR; FLOOR 2 LOUNGE; FLOOR 2 NURSE STATION 1; FLOOR 2 NURSE STATION 2; FLOOR 2 OFFICE; FLOOR 2 OFFICE HALL; FLOOR 2 RECEPTION; FLOOR 2 RECEPTION HALL; FLOOR 2 RECEPTION TOILET; FLOOR 2 SCHEDULING 1; FLOOR 2 SCHEDULING 2; FLOOR 2 STORAGE 1; FLOOR 2 STORAGE 2; FLOOR 2 STORAGE 3; FLOOR 2 UTILITY; FLOOR 2 WORK; FLOOR 2 WORK HALL; FLOOR 2 WORK TOILET; FLOOR 2 X-RAY; FLOOR 3 DRESSING ROOM; FLOOR 3 ELEVATOR HALL; FLOOR 3 HUMID; FLOOR 3 JANITOR; FLOOR 3 LOCKER; FLOOR 3 LOUNGE; FLOOR 3 LOUNGE TOILET; FLOOR 3 MECHANICAL; FLOOR 3 MECHANICAL HALL; FLOOR 3 OFFICE; FLOOR 3 OFFICE HALL; FLOOR 3 OFFICE TOILET; FLOOR 3 PHYSICAL THERAPY 1; FLOOR 3 PHYSICAL THERAPY 2; FLOOR 3 PHYSICAL THERAPY TOILET; FLOOR 3 STORAGE 1; FLOOR 3 STORAGE 2; FLOOR 3 TREATMENT; FLOOR 3 UNDEVELOPED 1; FLOOR 3 UNDEVELOPED 2; FLOOR 3 UTILITY; FLOOR 3 WORK; NE STAIR; NW ELEVATOR; NW STAIR; SW STAIR; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 115747.629 115747.629 9.203000 0.00253426 1832.705 -999.0000 1.00000 1.00000 1019.3398 1004.8586 1.1539 AHU-2_FAN Fan:VariableVolume 9.203000 10.61957043   4197.9300 999.8980 2.20765614 71.10 82.20 11.10 342900.68 28.7738 114.782601 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 10:40:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 98665.72 115747.63 1.0000 10.61957043 9.203000 -32.49 -32.49 0.00020955 -32140.0 16.00 12.32 0.00780000 35816.8 2.53400514 60.00 48.90 11.10 0.000 98665.72 -32.70 0.00018338 -32.70 2.51720000 27.3520 19.40 0.00680893 20.97 0.00781643 48.5130 34261.71 0.00 98643.35 98643.35 10.61957043 16.60 10.06 0.00499671 29331.0 25.76 13.84 0.00499671 38619.8



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
AHU-2_OA_CONTROLLER DifferentialDryBulb 0.00 9.20 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
FLOOR 2 CONFERENCE AHU-2_DCV 0.000000 0.001575 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 DICTATION AHU-2_DCV 0.000000 0.000432 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 EXAM 1 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 EXAM 2 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 EXAM 3 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 EXAM 4 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 EXAM 5 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 EXAM 6 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 EXAM 7 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 EXAM 8 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 EXAM 9 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 LOUNGE AHU-2_DCV 0.000000 0.000686 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 NURSE STATION 1 AHU-2_DCV 0.000000 0.000813 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 NURSE STATION 2 AHU-2_DCV 0.000000 0.000813 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 OFFICE AHU-2_DCV 0.000000 0.000432 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 RECEPTION AHU-2_DCV 0.000000 0.001067 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 SCHEDULING 1 AHU-2_DCV 0.000000 0.000432 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 SCHEDULING 2 AHU-2_DCV 0.000000 0.000432 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 WORK AHU-2_DCV 0.000000 0.000432 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 X-RAY AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 DRESSING ROOM AHU-2_DCV 0.000000 0.000432 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 HUMID AHU-2_DCV 0.000000 0.000432 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 LOCKER AHU-2_DCV 0.000000 0.000686 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 LOUNGE AHU-2_DCV 0.000000 0.000686 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 OFFICE AHU-2_DCV 0.000000 0.000432 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 PHYSICAL THERAPY 1 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 PHYSICAL THERAPY 2 AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 TREATMENT AHU-2_DCV 0.000000 0.001524 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 WORK AHU-2_DCV 0.000000 0.000432 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 CONFERENCE TOILET AHU-2_DCV 0.000000 0.000000 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 EXAM HALL 1 AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 EXAM HALL 2 AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 EXAM HALL 3 AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 EXAM HALL 4 AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 EXAM HALL 5 AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 EXAM HALL 6 AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 JANITOR AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 OFFICE HALL AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 RECEPTION HALL AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 RECEPTION TOILET AHU-2_DCV 0.000000 0.000000 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 STORAGE 1 AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 STORAGE 2 AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 STORAGE 3 AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 UTILITY AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 WORK HALL AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 2 WORK TOILET AHU-2_DCV 0.000000 0.000000 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 ELEVATOR HALL AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 JANITOR AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 LOUNGE TOILET AHU-2_DCV 0.000000 0.000000 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 MECHANICAL AHU-2_DCV 0.000000 0.000000 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 MECHANICAL HALL AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 OFFICE HALL AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 OFFICE TOILET AHU-2_DCV 0.000000 0.000000 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 PHYSICAL THERAPY TOILET AHU-2_DCV 0.000000 0.000000 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 STORAGE 1 AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 STORAGE 2 AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 UNDEVELOPED 1 AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 UNDEVELOPED 2 AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Sum   1.00 1.00  
FLOOR 3 UTILITY AHU-2_DCV 0.000000 0.000610 0.000000 0.000000 Sum   1.00 1.00  
NE STAIR AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  
NW ELEVATOR AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  
NW STAIR AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  
SW STAIR AHU-2_DCV 0.000000 0.000305 0.000000 0.000000 Sum   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FLOOR 1 ANESTHESIA 4206.83 7830.00 4206.83
FLOOR 1 CAFE 790.67 7329.83 537.33
FLOOR 1 CLEAN 1752.50 7830.00 1752.50
FLOOR 1 CLEAN WORK 2770.33 7830.00 2770.33
FLOOR 1 DICTATION 141.17 7224.00 141.17
FLOOR 1 DRESSING ROOM 4532.17 7224.00 4532.17
FLOOR 1 HUMID 17.33 7224.00 17.33
FLOOR 1 IT ROOM 1901.50 7224.00 1901.50
FLOOR 1 LOBBY 838.50 7593.67 738.83
FLOOR 1 LOCKER ROOM 76.67 7773.67 76.67
FLOOR 1 LOUNGE 47.67 7830.00 47.67
FLOOR 1 MRI CONTROL ROOM 609.83 6155.17 7.00
FLOOR 1 MRI ROOM 1907.33 2857.33 0.00
FLOOR 1 NOURISHMENT 22.17 7778.67 22.17
FLOOR 1 NURSE STATION 133.67 7830.00 133.67
FLOOR 1 OFFICE 44.67 7224.00 44.67
FLOOR 1 OPERATING ROOM 1 5419.50 7830.00 5419.50
FLOOR 1 OPERATING ROOM 2 5290.33 7830.00 5290.33
FLOOR 1 OPERATING ROOM 3 7085.00 7830.00 7085.00
FLOOR 1 PACU 3129.00 7830.00 3129.00
FLOOR 1 PRE-OP ROOM 1 5880.50 7830.00 5880.50
FLOOR 1 PRE-OP ROOM 2 3214.33 7830.00 3214.33
FLOOR 1 PROCEDURE ROOM 5295.17 7830.00 5295.17
FLOOR 1 RECEPTION 110.17 7677.67 74.83
FLOOR 1 RECOVERY ROOM 4288.67 7830.00 4288.67
FLOOR 1 SCHEDULING 873.33 7224.00 873.33
FLOOR 1 SOIL 2643.17 7830.00 2643.17
FLOOR 1 SOIL HOLD 6035.33 7830.00 6035.33
FLOOR 1 SOIL WORK 3242.83 7830.00 3242.83
FLOOR 1 STEP DOWN 4463.83 7830.00 4463.83
FLOOR 2 CONFERENCE 2655.50 6658.00 2655.50
FLOOR 2 DICTATION 851.67 7224.00 851.67
FLOOR 2 EXAM 1 4262.67 7808.67 4261.67
FLOOR 2 EXAM 2 4242.33 7830.00 4242.33
FLOOR 2 EXAM 3 4450.50 7830.00 4450.50
FLOOR 2 EXAM 4 3841.17 7830.00 3841.17
FLOOR 2 EXAM 5 3831.50 7830.00 3831.50
FLOOR 2 EXAM 6 4972.00 7830.00 4972.00
FLOOR 2 EXAM 7 4619.33 7830.00 4619.33
FLOOR 2 EXAM 8 4326.67 7830.00 4326.67
FLOOR 2 EXAM 9 4129.50 7830.00 4129.50
FLOOR 2 LOUNGE 488.50 7830.00 488.50
FLOOR 2 NURSE STATION 1 557.67 7830.00 557.67
FLOOR 2 NURSE STATION 2 497.67 7830.00 497.67
FLOOR 2 OFFICE 2746.00 7219.00 2746.00
FLOOR 2 RECEPTION 1799.67 7751.17 1780.33
FLOOR 2 SCHEDULING 1 318.67 7224.00 318.67
FLOOR 2 SCHEDULING 2 380.50 7224.00 380.50
FLOOR 2 WORK 1140.00 7224.00 1140.00
FLOOR 2 X-RAY 616.67 5218.33 0.17
FLOOR 3 DRESSING ROOM 1741.33 7224.00 1741.33
FLOOR 3 HUMID 1487.67 7224.00 1487.67
FLOOR 3 LOCKER 1508.50 7785.83 1508.00
FLOOR 3 LOUNGE 1399.17 7649.67 1365.50
FLOOR 3 OFFICE 2407.17 7216.67 2407.17
FLOOR 3 PHYSICAL THERAPY 1 4440.00 7794.17 4440.00
FLOOR 3 PHYSICAL THERAPY 2 4329.83 7830.00 4329.83
FLOOR 3 TREATMENT 3600.50 7830.00 3600.50
FLOOR 3 WORK 2730.67 7032.50 2677.17
FLOOR 1 BIO HAZ 0.00 0.00 0.00
FLOOR 1 ELECTRICAL ROOM 0.00 0.00 0.00
FLOOR 1 ELEVATOR PUMP ROOM 0.00 0.00 0.00
FLOOR 1 IT HALL 0.00 0.00 0.00
FLOOR 1 LOBBY HALL 0.00 0.00 0.00
FLOOR 1 LOBBY TOILET 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM HALL 0.00 0.00 0.00
FLOOR 1 MED GAS 0.00 0.00 0.00
FLOOR 1 MRI HALL 0.00 0.00 0.00
FLOOR 1 MRI TOILET 0.00 0.00 0.00
FLOOR 1 NURSE HALL 0.00 0.00 0.00
FLOOR 1 NURSE JANITOR 0.00 0.00 0.00
FLOOR 1 NURSE TOILET 0.00 0.00 0.00
FLOOR 1 PRE-OP HALL 0.00 0.00 0.00
FLOOR 1 PRE-OP TOILET 0.00 0.00 0.00
FLOOR 1 RECEPTION HALL 0.00 0.00 0.00
FLOOR 1 SCRUB 0.00 0.00 0.00
FLOOR 1 STERILE HALL 0.00 0.00 0.00
FLOOR 1 STERILE STORAGE 0.00 0.00 0.00
FLOOR 1 STORAGE 0.00 0.00 0.00
FLOOR 1 SUB-STERILE 0.00 0.00 0.00
FLOOR 1 UTILITY HALL 0.00 0.00 0.00
FLOOR 1 UTILITY JANITOR 0.00 0.00 0.00
FLOOR 1 UTILITY ROOM 0.00 0.00 0.00
FLOOR 1 VESTIBULE 0.00 0.00 0.00
FLOOR 2 CONFERENCE TOILET 0.00 0.00 0.00
FLOOR 2 EXAM HALL 1 0.00 0.00 0.00
FLOOR 2 EXAM HALL 2 0.00 0.00 0.00
FLOOR 2 EXAM HALL 3 0.00 0.00 0.00
FLOOR 2 EXAM HALL 4 0.00 0.00 0.00
FLOOR 2 EXAM HALL 5 0.00 0.00 0.00
FLOOR 2 EXAM HALL 6 0.00 0.00 0.00
FLOOR 2 JANITOR 0.00 0.00 0.00
FLOOR 2 OFFICE HALL 0.00 0.00 0.00
FLOOR 2 RECEPTION HALL 0.00 0.00 0.00
FLOOR 2 RECEPTION TOILET 0.00 0.00 0.00
FLOOR 2 STORAGE 1 0.00 0.00 0.00
FLOOR 2 STORAGE 2 0.00 0.00 0.00
FLOOR 2 STORAGE 3 0.00 0.00 0.00
FLOOR 2 UTILITY 0.00 0.00 0.00
FLOOR 2 WORK HALL 0.00 0.00 0.00
FLOOR 2 WORK TOILET 0.00 0.00 0.00
FLOOR 3 ELEVATOR HALL 0.00 0.00 0.00
FLOOR 3 JANITOR 0.00 0.00 0.00
FLOOR 3 LOUNGE TOILET 0.00 0.00 0.00
FLOOR 3 MECHANICAL 0.00 0.00 0.00
FLOOR 3 MECHANICAL HALL 0.00 0.00 0.00
FLOOR 3 OFFICE HALL 0.00 0.00 0.00
FLOOR 3 OFFICE TOILET 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 0.00 0.00 0.00
FLOOR 3 STORAGE 1 0.00 0.00 0.00
FLOOR 3 STORAGE 2 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 1 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 2 0.00 0.00 0.00
FLOOR 3 UTILITY 0.00 0.00 0.00
NE STAIR 0.00 0.00 0.00
NW ELEVATOR 0.00 0.00 0.00
NW STAIR 0.00 0.00 0.00
SW STAIR 0.00 0.00 0.00
Facility 7830.00 7830.00 7830.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FLOOR 1 ANESTHESIA 10.00 8.33 10.00 8.33
FLOOR 1 CAFE 0.00 46.50 0.00 46.50
FLOOR 1 CLEAN 3.83 0.00 3.83 0.00
FLOOR 1 CLEAN WORK 34.83 0.00 34.83 0.00
FLOOR 1 DICTATION 3.50 0.00 3.50 0.00
FLOOR 1 DRESSING ROOM 250.67 0.00 92.00 0.00
FLOOR 1 HUMID 0.00 0.00 0.00 0.00
FLOOR 1 IT ROOM 534.17 0.00 527.33 0.00
FLOOR 1 LOBBY 0.00 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM 0.00 0.00 0.00 0.00
FLOOR 1 LOUNGE 0.00 0.00 0.00 0.00
FLOOR 1 MRI CONTROL ROOM 0.00 142.50 0.00 142.50
FLOOR 1 MRI ROOM 0.00 465.00 0.00 465.00
FLOOR 1 NOURISHMENT 0.00 0.00 0.00 0.00
FLOOR 1 NURSE STATION 0.00 0.00 0.00 0.00
FLOOR 1 OFFICE 0.33 0.00 0.33 0.00
FLOOR 1 OPERATING ROOM 1 27.67 359.83 27.67 359.83
FLOOR 1 OPERATING ROOM 2 828.83 447.33 516.83 447.33
FLOOR 1 OPERATING ROOM 3 861.00 543.00 564.00 540.33
FLOOR 1 PACU 48.83 0.00 48.83 0.00
FLOOR 1 PRE-OP ROOM 1 810.67 0.00 810.67 0.00
FLOOR 1 PRE-OP ROOM 2 121.50 0.00 121.50 0.00
FLOOR 1 PROCEDURE ROOM 377.00 0.00 372.33 0.00
FLOOR 1 RECEPTION 0.00 0.50 0.00 0.50
FLOOR 1 RECOVERY ROOM 9.67 0.00 9.67 0.00
FLOOR 1 SCHEDULING 1.33 0.00 1.33 0.00
FLOOR 1 SOIL 35.17 0.00 35.17 0.00
FLOOR 1 SOIL HOLD 1933.67 0.00 1711.50 0.00
FLOOR 1 SOIL WORK 70.50 0.00 70.50 0.00
FLOOR 1 STEP DOWN 8.33 0.00 8.33 0.00
FLOOR 2 CONFERENCE 0.00 0.83 0.00 0.83
FLOOR 2 DICTATION 0.50 0.00 0.50 0.00
FLOOR 2 EXAM 1 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 2 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 3 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 4 0.00 4.67 0.00 4.67
FLOOR 2 EXAM 5 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 6 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 7 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 8 0.00 0.00 0.00 0.00
FLOOR 2 EXAM 9 0.00 0.00 0.00 0.00
FLOOR 2 LOUNGE 0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 1 0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 2 0.00 0.00 0.00 0.00
FLOOR 2 OFFICE 0.33 0.00 0.33 0.00
FLOOR 2 RECEPTION 0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 1 0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 2 0.00 0.00 0.00 0.00
FLOOR 2 WORK 0.33 0.00 0.33 0.00
FLOOR 2 X-RAY 0.00 1469.33 0.00 1469.33
FLOOR 3 DRESSING ROOM 0.00 0.00 0.00 0.00
FLOOR 3 HUMID 0.00 0.00 0.00 0.00
FLOOR 3 LOCKER 0.00 0.00 0.00 0.00
FLOOR 3 LOUNGE 0.17 0.00 0.17 0.00
FLOOR 3 OFFICE 0.17 0.00 0.17 0.00
FLOOR 3 PHYSICAL THERAPY 1 0.00 11.33 0.00 11.33
FLOOR 3 PHYSICAL THERAPY 2 0.00 0.00 0.00 0.00
FLOOR 3 TREATMENT 0.00 0.00 0.00 0.00
FLOOR 3 WORK 1.33 0.00 1.33 0.00
FLOOR 1 BIO HAZ 50.33 0.00 0.00 0.00
FLOOR 1 ELECTRICAL ROOM 0.00 0.00 0.00 0.00
FLOOR 1 ELEVATOR PUMP ROOM 3.83 0.33 0.00 0.00
FLOOR 1 IT HALL 1068.50 0.00 0.00 0.00
FLOOR 1 LOBBY HALL 0.50 0.00 0.00 0.00
FLOOR 1 LOBBY TOILET 63.83 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM HALL 19.17 0.00 0.00 0.00
FLOOR 1 MED GAS 414.17 0.00 0.00 0.00
FLOOR 1 MRI HALL 15.83 0.00 0.00 0.00
FLOOR 1 MRI TOILET 3.33 0.00 0.00 0.00
FLOOR 1 NURSE HALL 390.33 0.00 0.00 0.00
FLOOR 1 NURSE JANITOR 4.00 0.00 0.00 0.00
FLOOR 1 NURSE TOILET 1784.00 0.00 0.00 0.00
FLOOR 1 PRE-OP HALL 434.17 0.00 0.00 0.00
FLOOR 1 PRE-OP TOILET 646.83 0.00 0.00 0.00
FLOOR 1 RECEPTION HALL 36.00 0.00 0.00 0.00
FLOOR 1 SCRUB 3.17 0.00 0.00 0.00
FLOOR 1 STERILE HALL 8.17 0.00 0.00 0.00
FLOOR 1 STERILE STORAGE 17.83 0.00 0.00 0.00
FLOOR 1 STORAGE 335.50 0.00 0.00 0.00
FLOOR 1 SUB-STERILE 9.83 0.00 0.00 0.00
FLOOR 1 UTILITY HALL 178.67 0.00 0.00 0.00
FLOOR 1 UTILITY JANITOR 5.00 0.00 0.00 0.00
FLOOR 1 UTILITY ROOM 59.33 0.00 0.00 0.00
FLOOR 1 VESTIBULE 3905.67 300.50 0.00 0.00
FLOOR 2 CONFERENCE TOILET 0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 1 4.33 0.00 0.00 0.00
FLOOR 2 EXAM HALL 2 20.83 0.00 0.00 0.00
FLOOR 2 EXAM HALL 3 16.67 0.00 0.00 0.00
FLOOR 2 EXAM HALL 4 49.67 0.00 0.00 0.00
FLOOR 2 EXAM HALL 5 40.67 0.00 0.00 0.00
FLOOR 2 EXAM HALL 6 43.83 0.00 0.00 0.00
FLOOR 2 JANITOR 0.00 0.00 0.00 0.00
FLOOR 2 OFFICE HALL 12.67 0.00 0.00 0.00
FLOOR 2 RECEPTION HALL 3.67 0.00 0.00 0.00
FLOOR 2 RECEPTION TOILET 0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 1 7.50 0.00 0.00 0.00
FLOOR 2 STORAGE 2 3.33 0.00 0.00 0.00
FLOOR 2 STORAGE 3 2.83 0.00 0.00 0.00
FLOOR 2 UTILITY 1.17 0.00 0.00 0.00
FLOOR 2 WORK HALL 4.17 0.00 0.00 0.00
FLOOR 2 WORK TOILET 0.00 0.00 0.00 0.00
FLOOR 3 ELEVATOR HALL 0.00 0.00 0.00 0.00
FLOOR 3 JANITOR 46.17 0.00 0.00 0.00
FLOOR 3 LOUNGE TOILET 0.00 0.00 0.00 0.00
FLOOR 3 MECHANICAL 0.00 4348.83 0.00 0.00
FLOOR 3 MECHANICAL HALL 0.00 0.00 0.00 0.00
FLOOR 3 OFFICE HALL 0.00 0.00 0.00 0.00
FLOOR 3 OFFICE TOILET 4.33 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 1 0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 2 0.00 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 1 2.33 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 2 0.00 0.00 0.00 0.00
FLOOR 3 UTILITY 0.67 0.00 0.00 0.00
NE STAIR 79.17 0.00 0.00 0.00
NW ELEVATOR 40.83 0.00 0.00 0.00
NW STAIR 116.00 0.00 0.00 0.00
SW STAIR 26.33 0.00 0.00 0.00
Facility 5620.17 6139.50 2344.50 1786.17
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
FLOOR 1 ANESTHESIA 0.91 2.16 30.58 3.065 0.031 0.000 0.000
FLOOR 1 CAFE 17.61 42.00 118.93 1.715 0.018 0.000 0.000
FLOOR 1 CLEAN 1.06 2.52 35.68 2.706 0.000 0.000 0.000
FLOOR 1 CLEAN WORK 1.38 3.30 46.72 2.548 0.000 0.000 0.000
FLOOR 1 DICTATION 0.25 0.63 35.68 0.506 0.000 0.000 0.000
FLOOR 1 DRESSING ROOM 0.09 0.23 12.74 0.538 0.073 0.000 0.000
FLOOR 1 HUMID 0.11 0.27 15.29 0.615 0.000 0.000 0.000
FLOOR 1 IT ROOM 0.22 0.56 31.71 0.374 0.000 0.000 0.000
FLOOR 1 LOBBY 2.61 6.22 176.13 0.724 0.013 0.000 0.000
FLOOR 1 LOCKER ROOM 4.15 9.90 186.89 0.810 0.012 0.000 0.000
FLOOR 1 LOUNGE 2.26 5.40 101.94 0.827 0.000 0.000 0.000
FLOOR 1 MRI CONTROL ROOM 1.41 3.36 47.57 2.402 0.000 0.000 0.000
FLOOR 1 MRI ROOM 3.69 8.80 124.59 2.629 0.000 0.000 0.000
FLOOR 1 NOURISHMENT 1.53 3.64 51.54 0.901 0.000 0.000 0.000
FLOOR 1 NURSE STATION 2.19 5.22 73.91 0.790 0.000 0.000 0.000
FLOOR 1 OFFICE 0.94 2.42 136.77 0.417 0.000 0.000 0.000
FLOOR 1 OPERATING ROOM 1 3.86 9.20 130.26 5.368 0.035 0.000 0.000
FLOOR 1 OPERATING ROOM 2 4.02 9.60 135.92 5.628 0.018 0.000 0.000
FLOOR 1 OPERATING ROOM 3 3.99 9.52 134.79 10.543 0.000 0.000 0.000
FLOOR 1 PACU 0.91 2.16 30.58 3.187 0.000 0.000 0.000
FLOOR 1 PRE-OP ROOM 1 0.79 1.89 53.52 3.179 0.008 0.000 0.000
FLOOR 1 PRE-OP ROOM 2 1.42 3.38 95.71 3.183 0.000 0.000 0.000
FLOOR 1 PROCEDURE ROOM 2.39 5.70 80.70 7.942 0.025 0.000 0.000
FLOOR 1 RECEPTION 6.40 15.27 144.13 0.829 0.010 0.000 0.000
FLOOR 1 RECOVERY ROOM 4.53 10.80 152.91 2.951 0.031 0.000 0.000
FLOOR 1 SCHEDULING 0.23 0.60 33.70 0.387 0.022 0.000 0.000
FLOOR 1 SOIL 1.06 2.52 35.68 2.688 0.000 0.000 0.000
FLOOR 1 SOIL HOLD 0.47 1.12 15.86 2.354 0.000 0.000 0.000
FLOOR 1 SOIL WORK 1.51 3.60 50.97 2.498 0.000 0.000 0.000
FLOOR 1 STEP DOWN 2.52 6.00 84.95 2.506 0.046 0.000 0.000
FLOOR 2 CONFERENCE 6.37 16.80 95.14 1.436 0.061 0.000 0.000
FLOOR 2 DICTATION 0.14 0.35 19.82 0.432 0.000 0.000 0.000
FLOOR 2 EXAM 1 3.02 7.20 101.94 1.878 0.062 0.000 0.000
FLOOR 2 EXAM 2 4.53 10.80 152.91 2.577 0.018 0.000 0.000
FLOOR 2 EXAM 3 6.04 14.40 203.88 2.576 0.018 0.000 0.000
FLOOR 2 EXAM 4 0.70 1.68 23.79 2.086 0.044 0.000 0.000
FLOOR 2 EXAM 5 2.93 7.00 99.11 2.234 0.038 0.000 0.000
FLOOR 2 EXAM 6 1.89 4.50 63.71 2.422 0.035 0.000 0.000
FLOOR 2 EXAM 7 6.64 15.84 224.27 2.576 0.016 0.000 0.000
FLOOR 2 EXAM 8 2.26 5.40 76.46 2.397 0.035 0.000 0.000
FLOOR 2 EXAM 9 3.32 7.92 112.13 2.577 0.016 0.000 0.000
FLOOR 2 LOUNGE 0.50 1.20 22.65 1.029 0.000 0.000 0.000
FLOOR 2 NURSE STATION 1 1.26 3.00 42.48 1.063 0.000 0.000 0.000
FLOOR 2 NURSE STATION 2 1.51 3.60 50.97 1.104 0.000 0.000 0.000
FLOOR 2 OFFICE 1.09 2.80 158.57 0.461 0.037 0.000 0.000
FLOOR 2 RECEPTION 12.38 29.52 278.64 1.117 0.027 0.000 0.000
FLOOR 2 SCHEDULING 1 0.63 1.62 91.75 0.520 0.000 0.000 0.000
FLOOR 2 SCHEDULING 2 0.67 1.71 96.84 0.519 0.000 0.000 0.000
FLOOR 2 WORK 3.29 8.45 478.55 0.464 0.008 0.000 0.000
FLOOR 2 X-RAY 7.55 18.00 254.85 2.986 0.000 0.000 0.000
FLOOR 3 DRESSING ROOM 0.08 0.21 11.89 0.469 0.062 0.000 0.000
FLOOR 3 HUMID 0.21 0.54 30.58 0.516 0.062 0.000 0.000
FLOOR 3 LOCKER 0.75 1.80 33.98 1.041 0.063 0.000 0.000
FLOOR 3 LOUNGE 4.77 11.39 214.92 1.082 0.001 0.000 0.000
FLOOR 3 OFFICE 5.91 15.18 859.70 0.445 0.000 0.000 0.000
FLOOR 3 PHYSICAL THERAPY 1 10.90 26.00 368.12 2.117 0.002 0.000 0.000
FLOOR 3 PHYSICAL THERAPY 2 4.96 11.84 167.64 2.140 0.063 0.000 0.000
FLOOR 3 TREATMENT 3.99 9.52 134.79 2.090 0.063 0.000 0.000
FLOOR 3 WORK 1.12 2.87 162.54 0.572 0.003 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
FLOOR 1 ANESTHESIA 0.91 2.16 30.58 1.902 0.000 0.000 0.000
FLOOR 1 CAFE 17.61 42.00 118.93 0.679 0.000 0.000 0.000
FLOOR 1 CLEAN 1.06 2.52 35.68 1.674 0.000 0.000 0.000
FLOOR 1 CLEAN WORK 1.38 3.30 46.72 1.576 0.000 0.000 0.000
FLOOR 1 DICTATION 0.25 0.63 35.68 0.254 0.000 0.000 0.000
FLOOR 1 DRESSING ROOM 0.09 0.23 12.74 0.300 0.000 0.000 0.000
FLOOR 1 HUMID 0.11 0.27 15.29 0.285 0.000 0.000 0.000
FLOOR 1 IT ROOM 0.22 0.56 31.71 0.202 0.000 0.000 0.000
FLOOR 1 LOBBY 2.61 6.22 176.13 0.379 0.000 0.000 0.000
FLOOR 1 LOCKER ROOM 4.15 9.90 186.89 0.351 0.000 0.000 0.000
FLOOR 1 LOUNGE 2.26 5.40 101.94 0.347 0.000 0.000 0.000
FLOOR 1 MRI CONTROL ROOM 1.41 3.36 47.57 0.916 0.000 0.000 0.000
FLOOR 1 MRI ROOM 3.69 8.80 124.59 0.990 0.000 0.000 0.000
FLOOR 1 NOURISHMENT 1.53 3.64 51.54 0.368 0.000 0.000 0.000
FLOOR 1 NURSE STATION 2.19 5.22 73.91 0.337 0.000 0.000 0.000
FLOOR 1 OFFICE 0.94 2.42 136.77 0.202 0.000 0.000 0.000
FLOOR 1 OPERATING ROOM 1 3.86 9.20 130.26 2.240 0.000 0.000 0.000
FLOOR 1 OPERATING ROOM 2 4.02 9.60 135.92 2.226 0.000 0.000 0.000
FLOOR 1 OPERATING ROOM 3 3.99 9.52 134.79 6.528 0.000 0.000 0.000
FLOOR 1 PACU 0.91 2.16 30.58 1.973 0.000 0.000 0.000
FLOOR 1 PRE-OP ROOM 1 0.79 1.89 53.52 1.963 0.000 0.000 0.000
FLOOR 1 PRE-OP ROOM 2 1.42 3.38 95.71 1.965 0.000 0.000 0.000
FLOOR 1 PROCEDURE ROOM 2.39 5.70 80.70 4.912 0.000 0.000 0.000
FLOOR 1 RECEPTION 6.40 15.27 144.13 0.334 0.000 0.000 0.000
FLOOR 1 RECOVERY ROOM 4.53 10.80 152.91 1.854 0.000 0.000 0.000
FLOOR 1 SCHEDULING 0.23 0.60 33.70 0.216 0.000 0.000 0.000
FLOOR 1 SOIL 1.06 2.52 35.68 1.663 0.000 0.000 0.000
FLOOR 1 SOIL HOLD 0.47 1.12 15.86 1.455 0.000 0.000 0.000
FLOOR 1 SOIL WORK 1.51 3.60 50.97 1.545 0.000 0.000 0.000
FLOOR 1 STEP DOWN 2.52 6.00 84.95 1.571 0.000 0.000 0.000
FLOOR 2 CONFERENCE 6.37 16.80 95.14 0.000 0.000 0.000 0.000
FLOOR 2 DICTATION 0.14 0.35 19.82 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 1 3.02 7.20 101.94 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 2 4.53 10.80 152.91 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 3 6.04 14.40 203.88 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 4 0.70 1.68 23.79 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 5 2.93 7.00 99.11 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 6 1.89 4.50 63.71 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 7 6.64 15.84 224.27 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 8 2.26 5.40 76.46 0.000 0.000 0.000 0.000
FLOOR 2 EXAM 9 3.32 7.92 112.13 0.000 0.000 0.000 0.000
FLOOR 2 LOUNGE 0.50 1.20 22.65 0.000 0.000 0.000 0.000
FLOOR 2 NURSE STATION 1 1.26 3.00 42.48 0.000 0.000 0.000 0.000
FLOOR 2 NURSE STATION 2 1.51 3.60 50.97 0.000 0.000 0.000 0.000
FLOOR 2 OFFICE 1.09 2.80 158.57 0.000 0.000 0.000 0.000
FLOOR 2 RECEPTION 12.38 29.52 278.64 0.000 0.000 0.000 0.000
FLOOR 2 SCHEDULING 1 0.63 1.62 91.75 0.000 0.000 0.000 0.000
FLOOR 2 SCHEDULING 2 0.67 1.71 96.84 0.000 0.000 0.000 0.000
FLOOR 2 WORK 3.29 8.45 478.55 0.000 0.000 0.000 0.000
FLOOR 2 X-RAY 7.55 18.00 254.85 0.000 0.000 0.000 0.000
FLOOR 3 DRESSING ROOM 0.08 0.21 11.89 0.000 0.000 0.000 0.000
FLOOR 3 HUMID 0.21 0.54 30.58 0.000 0.000 0.000 0.000
FLOOR 3 LOCKER 0.75 1.80 33.98 0.000 0.000 0.000 0.000
FLOOR 3 LOUNGE 4.77 11.39 214.92 0.000 0.000 0.000 0.000
FLOOR 3 OFFICE 5.91 15.18 859.70 0.000 0.000 0.000 0.000
FLOOR 3 PHYSICAL THERAPY 1 10.90 26.00 368.12 0.000 0.000 0.000 0.000
FLOOR 3 PHYSICAL THERAPY 2 4.96 11.84 167.64 0.000 0.000 0.000 0.000
FLOOR 3 TREATMENT 3.99 9.52 134.79 0.000 0.000 0.000 0.000
FLOOR 3 WORK 1.12 2.87 162.54 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Surfaces by Class

Total Outdoors
Wall 672 86
Floor 259 30
Roof 229 29
Internal Mass 118 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 94 94
Door 23 23
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 118
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 0
Defaulted Fields 0
Fields with Defaults 0
Autosized Fields 0
Autosizable Fields 0
Autocalculated Fields 0
Autocalculatable Fields 0



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 3537.24 30321.66 10-SEP-07:00 291538.95 09-JAN-07:20
Electricity:Building 2210.22 22575.39 21-MAY-16:10 137302.90 02-JAN-16:30
Electricity:Zone:FLOOR 1 ANESTHESIA 6.13 71.75 01-JAN-00:10 350.04 02-JAN-07:10
InteriorLights:Electricity 380.82 1382.58 21-MAY-16:10 26366.16 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 ANESTHESIA 2.06 7.56 01-JAN-00:10 136.08 02-JAN-07:10
LightsWired:InteriorLights:Electricity 380.82 1382.58 21-MAY-16:10 26366.16 02-JAN-07:10
Electricity:Zone:FLOOR 1 BIO HAZ 0.30 2.38 01-JAN-00:10 18.42 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 BIO HAZ 0.19 0.71 01-JAN-00:10 12.86 02-JAN-07:10
Electricity:Zone:FLOOR 1 CAFE 10.20 133.15 01-JAN-00:10 567.04 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 CAFE 2.29 8.40 01-JAN-00:10 151.20 02-JAN-07:10
Electricity:Zone:FLOOR 1 CLEAN 7.15 83.71 01-JAN-00:10 408.38 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 CLEAN 2.41 8.82 01-JAN-00:10 158.76 02-JAN-07:10
Electricity:Zone:FLOOR 1 CLEAN WORK 9.37 109.62 01-JAN-00:10 534.79 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 CLEAN WORK 3.15 11.55 01-JAN-00:10 207.90 02-JAN-07:10
Electricity:Zone:FLOOR 1 DICTATION 3.71 45.84 01-JAN-00:10 209.37 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 DICTATION 1.10 4.66 01-JAN-00:10 72.09 02-JAN-07:10
Electricity:Zone:FLOOR 1 DRESSING ROOM 1.32 16.37 01-JAN-00:10 74.77 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 DRESSING ROOM 0.39 1.67 01-JAN-00:10 25.75 02-JAN-07:10
Electricity:Zone:FLOOR 1 ELECTRICAL ROOM 11.10 152.46 01-JAN-00:10 608.81 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 ELECTRICAL ROOM 1.87 6.86 01-JAN-00:10 123.48 02-JAN-07:10
Electricity:Zone:FLOOR 1 ELEVATOR PUMP ROOM 641.01 2424.01 01-JAN-00:10 48467.50 02-JAN-09:10
InteriorLights:Electricity:Zone:FLOOR 1 ELEVATOR PUMP ROOM 1.74 6.37 01-JAN-00:10 114.66 02-JAN-07:10
Electricity:Zone:FLOOR 1 HUMID 1.59 19.65 01-JAN-00:10 89.73 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 HUMID 0.47 2.00 01-JAN-00:10 30.90 02-JAN-07:10
Electricity:Zone:FLOOR 1 IT HALL 1.95 19.94 01-JAN-00:10 114.53 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 IT HALL 0.89 3.28 01-JAN-00:10 59.01 02-JAN-07:10
Electricity:Zone:FLOOR 1 IT ROOM 3.29 40.75 01-JAN-00:10 186.10 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 IT ROOM 0.97 4.14 01-JAN-00:10 64.08 02-JAN-07:10
Electricity:Zone:FLOOR 1 LOBBY 19.66 228.11 01-JAN-00:10 1124.38 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 LOBBY 6.77 24.82 01-JAN-00:10 446.72 02-JAN-07:10
Electricity:Zone:FLOOR 1 LOBBY HALL 3.34 34.17 01-JAN-00:10 196.34 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 LOBBY HALL 1.53 5.62 01-JAN-00:10 101.16 02-JAN-07:10
Electricity:Zone:FLOOR 1 LOBBY TOILET 0.71 7.55 01-JAN-00:10 41.62 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 LOBBY TOILET 0.31 1.12 01-JAN-00:10 20.21 02-JAN-07:10
Electricity:Zone:FLOOR 1 LOCKER ROOM 42.60 607.77 01-JAN-00:10 2311.47 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 LOCKER ROOM 5.31 19.47 01-JAN-00:10 350.46 02-JAN-07:10
Electricity:Zone:FLOOR 1 LOCKER ROOM HALL 6.91 70.63 01-JAN-00:10 405.77 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 LOCKER ROOM HALL 3.17 11.61 01-JAN-00:10 209.06 02-JAN-07:10
Electricity:Zone:FLOOR 1 LOUNGE 23.24 331.51 01-JAN-00:10 1260.80 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 LOUNGE 2.90 10.62 01-JAN-00:10 191.16 02-JAN-07:10
Electricity:Zone:FLOOR 1 MED GAS 0.30 2.38 01-JAN-00:10 18.42 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 MED GAS 0.19 0.71 01-JAN-00:10 12.86 02-JAN-07:10
Electricity:Zone:FLOOR 1 MRI CONTROL ROOM 33.80 507.09 01-JAN-00:10 1806.12 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 MRI CONTROL ROOM 2.15 7.90 01-JAN-00:10 142.13 02-JAN-07:10
Electricity:Zone:FLOOR 1 MRI HALL 2.05 20.93 01-JAN-00:10 120.26 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 MRI HALL 0.94 3.44 01-JAN-00:10 61.96 02-JAN-07:10
Electricity:Zone:FLOOR 1 MRI ROOM 87.28 1323.55 01-JAN-00:10 4648.41 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 MRI ROOM 4.40 16.13 01-JAN-00:10 290.35 02-JAN-07:10
Electricity:Zone:FLOOR 1 MRI TOILET 0.71 7.55 01-JAN-00:10 41.62 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 MRI TOILET 0.31 1.12 01-JAN-00:10 20.21 02-JAN-07:10
Electricity:Zone:FLOOR 1 NOURISHMENT 9.76 118.82 01-JAN-00:10 552.21 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 NOURISHMENT 2.91 10.65 01-JAN-00:10 191.65 02-JAN-07:10
Electricity:Zone:FLOOR 1 NURSE HALL 6.91 70.63 01-JAN-00:10 405.77 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 NURSE HALL 3.17 11.61 01-JAN-00:10 209.06 02-JAN-07:10
Electricity:Zone:FLOOR 1 NURSE JANITOR 0.29 2.30 01-JAN-00:10 17.76 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 NURSE JANITOR 0.19 0.69 01-JAN-00:10 12.40 02-JAN-07:10
Electricity:Zone:FLOOR 1 NURSE STATION 14.00 170.39 01-JAN-00:10 791.91 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 NURSE STATION 4.17 15.27 01-JAN-00:10 274.83 02-JAN-07:10
Electricity:Zone:FLOOR 1 NURSE TOILET 0.71 7.55 01-JAN-00:10 41.62 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 NURSE TOILET 0.31 1.12 01-JAN-00:10 20.21 02-JAN-07:10
Electricity:Zone:FLOOR 1 OFFICE 14.20 175.74 01-JAN-00:10 802.57 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 OFFICE 4.20 17.87 01-JAN-00:10 276.35 02-JAN-07:10
Electricity:Zone:FLOOR 1 OPERATING ROOM 1 48.84 598.77 01-JAN-00:10 2758.27 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 OPERATING ROOM 1 14.18 51.98 01-JAN-00:10 935.64 02-JAN-07:10
Electricity:Zone:FLOOR 1 OPERATING ROOM 2 50.97 624.80 01-JAN-00:10 2878.20 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 OPERATING ROOM 2 14.80 54.24 01-JAN-00:10 976.32 02-JAN-07:10
Electricity:Zone:FLOOR 1 OPERATING ROOM 3 50.54 619.60 01-JAN-00:10 2854.21 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 OPERATING ROOM 3 14.68 53.79 01-JAN-00:10 968.18 02-JAN-07:10
Electricity:Zone:FLOOR 1 PACU 7.94 103.02 01-JAN-00:10 442.39 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 PACU 1.84 6.75 01-JAN-00:10 121.50 02-JAN-07:10
Electricity:Zone:FLOOR 1 PRE-OP HALL 7.36 75.18 01-JAN-00:10 431.95 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 PRE-OP HALL 3.37 12.36 01-JAN-00:10 222.55 02-JAN-07:10
Electricity:Zone:FLOOR 1 PRE-OP ROOM 1 8.87 118.76 01-JAN-00:10 490.10 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 PRE-OP ROOM 1 1.75 6.43 01-JAN-00:10 115.67 02-JAN-07:10
Electricity:Zone:FLOOR 1 PRE-OP ROOM 2 15.87 212.38 01-JAN-00:10 876.48 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 PRE-OP ROOM 2 3.14 11.49 01-JAN-00:10 206.86 02-JAN-07:10
Electricity:Zone:FLOOR 1 PRE-OP TOILET 0.71 7.55 01-JAN-00:10 41.62 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 PRE-OP TOILET 0.31 1.12 01-JAN-00:10 20.21 02-JAN-07:10
Electricity:Zone:FLOOR 1 PROCEDURE ROOM 21.55 273.99 01-JAN-00:10 1205.90 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 PROCEDURE ROOM 5.44 19.95 01-JAN-00:10 359.10 02-JAN-07:10
Electricity:Zone:FLOOR 1 RECEPTION 16.38 187.74 01-JAN-00:10 939.35 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 RECEPTION 5.83 21.38 01-JAN-00:10 384.80 02-JAN-07:10
Electricity:Zone:FLOOR 1 RECEPTION HALL 1.78 18.23 01-JAN-00:10 104.72 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 RECEPTION HALL 0.82 3.00 01-JAN-00:10 53.95 02-JAN-07:10
Electricity:Zone:FLOOR 1 RECOVERY ROOM 39.72 515.09 01-JAN-00:10 2211.96 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 RECOVERY ROOM 9.21 33.75 01-JAN-00:10 607.50 02-JAN-07:10
Electricity:Zone:FLOOR 1 SCHEDULING 3.50 43.30 01-JAN-00:10 197.74 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 SCHEDULING 1.03 4.40 01-JAN-00:10 68.09 02-JAN-07:10
Electricity:Zone:FLOOR 1 SCRUB 1.17 11.96 01-JAN-00:10 68.72 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 SCRUB 0.54 1.97 01-JAN-00:10 35.41 02-JAN-07:10
Electricity:Zone:FLOOR 1 SOIL 7.15 83.71 01-JAN-00:10 408.38 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 SOIL 2.41 8.82 01-JAN-00:10 158.76 02-JAN-07:10
Electricity:Zone:FLOOR 1 SOIL HOLD 3.18 37.20 01-JAN-00:10 181.50 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 SOIL HOLD 1.07 3.92 01-JAN-00:10 70.56 02-JAN-07:10
Electricity:Zone:FLOOR 1 SOIL WORK 10.22 119.58 01-JAN-00:10 583.40 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 SOIL WORK 3.44 12.60 01-JAN-00:10 226.80 02-JAN-07:10
Electricity:Zone:FLOOR 1 STEP DOWN 22.07 286.16 01-JAN-00:10 1228.87 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 STEP DOWN 5.12 18.75 01-JAN-00:10 337.50 02-JAN-07:10
Electricity:Zone:FLOOR 1 STERILE HALL 8.58 87.71 01-JAN-00:10 503.95 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 STERILE HALL 3.94 14.42 01-JAN-00:10 259.64 02-JAN-07:10
Electricity:Zone:FLOOR 1 STERILE STORAGE 2.13 16.86 01-JAN-00:10 130.27 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 STERILE STORAGE 1.38 5.05 01-JAN-00:10 90.92 02-JAN-07:10
Electricity:Zone:FLOOR 1 STORAGE 4.94 39.16 01-JAN-00:10 302.65 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 STORAGE 3.20 11.73 01-JAN-00:10 211.22 02-JAN-07:10
Electricity:Zone:FLOOR 1 SUB-STERILE 2.73 27.91 01-JAN-00:10 160.35 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 SUB-STERILE 1.25 4.59 01-JAN-00:10 82.61 02-JAN-07:10
Electricity:Zone:FLOOR 1 UTILITY HALL 3.57 36.45 01-JAN-00:10 209.43 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 UTILITY HALL 1.64 5.99 01-JAN-00:10 107.90 02-JAN-07:10
Electricity:Zone:FLOOR 1 UTILITY JANITOR 0.23 1.79 01-JAN-00:10 13.82 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 UTILITY JANITOR 0.15 0.54 01-JAN-00:10 9.64 02-JAN-07:10
Electricity:Zone:FLOOR 1 UTILITY ROOM 1.93 15.32 01-JAN-00:10 118.43 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 UTILITY ROOM 1.25 4.59 01-JAN-00:10 82.65 02-JAN-07:10
Electricity:Zone:FLOOR 1 VESTIBULE 1.00 10.25 01-JAN-00:10 58.90 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 1 VESTIBULE 0.46 1.69 01-JAN-00:10 30.35 02-JAN-07:10
Electricity:Zone:FLOOR 2 CONFERENCE 7.86 99.80 19-FEB-08:00 626.00 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 CONFERENCE 1.53 0.00 01-JAN-08:50 293.33 02-JAN-07:10
Electricity:Zone:FLOOR 2 CONFERENCE TOILET 0.85 8.95 01-JAN-00:10 49.33 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 CONFERENCE TOILET 0.36 1.33 01-JAN-00:10 23.95 02-JAN-07:10
Electricity:Zone:FLOOR 2 DICTATION 2.06 25.47 01-JAN-00:10 116.31 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 DICTATION 0.61 2.59 01-JAN-00:10 40.05 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 1 12.82 137.32 01-JAN-00:10 746.02 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 1 5.36 19.66 01-JAN-00:10 353.81 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 2 19.23 205.98 01-JAN-00:10 1119.03 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 2 8.05 29.48 01-JAN-00:10 530.71 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 3 25.64 274.64 01-JAN-00:10 1492.04 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 3 10.73 39.31 01-JAN-00:10 707.62 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 4 2.99 32.04 01-JAN-00:10 174.07 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 4 1.25 4.59 01-JAN-00:10 82.56 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 5 12.47 133.51 01-JAN-00:10 725.30 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 5 5.21 19.11 01-JAN-00:10 343.98 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 6 8.01 85.82 01-JAN-00:10 466.26 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 6 3.35 12.28 01-JAN-00:10 221.13 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 7 28.21 302.10 01-JAN-00:10 1641.24 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 7 11.80 43.24 01-JAN-00:10 778.38 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 8 9.62 102.99 01-JAN-00:10 559.52 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 8 4.02 14.74 01-JAN-00:10 265.36 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM 9 14.10 151.05 01-JAN-00:10 820.62 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM 9 5.90 21.62 01-JAN-00:10 389.19 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM HALL 1 2.51 25.63 01-JAN-00:10 147.26 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 1 1.15 4.22 01-JAN-00:10 75.87 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM HALL 2 2.51 25.63 01-JAN-00:10 147.26 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 2 1.15 4.22 01-JAN-00:10 75.87 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM HALL 3 2.51 25.63 01-JAN-00:10 147.26 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 3 1.15 4.22 01-JAN-00:10 75.87 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM HALL 4 2.76 28.19 01-JAN-00:10 161.98 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 4 1.27 4.64 01-JAN-00:10 83.46 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM HALL 5 2.76 28.19 01-JAN-00:10 161.98 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 5 1.27 4.64 01-JAN-00:10 83.46 02-JAN-07:10
Electricity:Zone:FLOOR 2 EXAM HALL 6 2.76 28.19 01-JAN-00:10 161.98 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 EXAM HALL 6 1.27 4.64 01-JAN-00:10 83.46 02-JAN-07:10
Electricity:Zone:FLOOR 2 JANITOR 0.34 2.68 01-JAN-00:10 20.72 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 JANITOR 0.22 0.80 01-JAN-00:10 14.46 02-JAN-07:10
Electricity:Zone:FLOOR 2 LOUNGE 5.16 73.67 01-JAN-00:10 280.18 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 LOUNGE 0.64 2.36 01-JAN-00:10 42.48 02-JAN-07:10
Electricity:Zone:FLOOR 2 NURSE STATION 1 8.05 97.93 01-JAN-00:10 455.12 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 NURSE STATION 1 2.39 8.78 01-JAN-00:10 157.95 02-JAN-07:10
Electricity:Zone:FLOOR 2 NURSE STATION 2 9.65 117.51 01-JAN-00:10 546.14 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 NURSE STATION 2 2.87 10.53 01-JAN-00:10 189.54 02-JAN-07:10
Electricity:Zone:FLOOR 2 OFFICE 13.44 183.03 19-FEB-07:50 930.52 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 OFFICE 1.84 0.00 01-JAN-09:00 320.41 02-JAN-07:10
Electricity:Zone:FLOOR 2 OFFICE HALL 6.19 63.22 01-JAN-00:10 363.23 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 OFFICE HALL 2.84 10.40 01-JAN-00:10 187.15 02-JAN-07:10
Electricity:Zone:FLOOR 2 RECEPTION 26.18 331.12 12-MAR-16:10 1815.95 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 RECEPTION 5.79 9.51 12-MAR-16:10 743.90 02-JAN-07:10
Electricity:Zone:FLOOR 2 RECEPTION HALL 7.86 80.31 01-JAN-00:10 461.40 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 RECEPTION HALL 3.60 13.21 01-JAN-00:10 237.73 02-JAN-07:10
Electricity:Zone:FLOOR 2 RECEPTION TOILET 1.67 17.61 01-JAN-00:10 97.12 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 RECEPTION TOILET 0.71 2.62 01-JAN-00:10 47.15 02-JAN-07:10
Electricity:Zone:FLOOR 2 SCHEDULING 1 9.53 117.89 01-JAN-00:10 538.37 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 SCHEDULING 1 2.82 11.99 01-JAN-00:10 185.38 02-JAN-07:10
Electricity:Zone:FLOOR 2 SCHEDULING 2 10.06 124.43 01-JAN-00:10 568.28 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 SCHEDULING 2 2.97 12.65 01-JAN-00:10 195.68 02-JAN-07:10
Electricity:Zone:FLOOR 2 STORAGE 1 0.30 2.38 01-JAN-00:10 18.42 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 STORAGE 1 0.19 0.71 01-JAN-00:10 12.86 02-JAN-07:10
Electricity:Zone:FLOOR 2 STORAGE 2 0.64 5.11 01-JAN-00:10 39.48 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 STORAGE 2 0.42 1.53 01-JAN-00:10 27.55 02-JAN-07:10
Electricity:Zone:FLOOR 2 STORAGE 3 0.77 6.13 01-JAN-00:10 47.37 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 STORAGE 3 0.50 1.84 01-JAN-00:10 33.06 02-JAN-07:10
Electricity:Zone:FLOOR 2 UTILITY 0.68 5.36 01-JAN-00:10 41.45 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 UTILITY 0.44 1.61 01-JAN-00:10 28.93 02-JAN-07:10
Electricity:Zone:FLOOR 2 WORK 43.61 518.80 01-JAN-00:10 2487.86 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 WORK 14.69 62.53 01-JAN-00:10 966.95 02-JAN-07:10
Electricity:Zone:FLOOR 2 WORK HALL 11.62 118.76 01-JAN-00:10 682.29 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 WORK HALL 5.33 19.53 01-JAN-00:10 351.53 02-JAN-07:10
Electricity:Zone:FLOOR 2 WORK TOILET 0.71 7.55 01-JAN-00:10 41.62 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 WORK TOILET 0.31 1.12 01-JAN-00:10 20.21 02-JAN-07:10
Electricity:Zone:FLOOR 2 X-RAY 178.52 2707.26 01-JAN-00:10 9508.11 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 2 X-RAY 9.00 32.99 01-JAN-00:10 593.89 02-JAN-07:10
Electricity:Zone:FLOOR 3 DRESSING ROOM 1.24 15.28 01-JAN-00:10 69.79 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 DRESSING ROOM 0.37 1.55 01-JAN-00:10 24.03 02-JAN-07:10
Electricity:Zone:FLOOR 3 ELEVATOR HALL 5.15 52.69 01-JAN-00:10 302.69 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 ELEVATOR HALL 2.36 8.66 01-JAN-00:10 155.96 02-JAN-07:10
Electricity:Zone:FLOOR 3 HUMID 3.18 39.30 01-JAN-00:10 179.46 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 HUMID 0.94 4.00 01-JAN-00:10 61.79 02-JAN-07:10
Electricity:Zone:FLOOR 3 JANITOR 0.34 2.68 01-JAN-00:10 20.72 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 JANITOR 0.22 0.80 01-JAN-00:10 14.46 02-JAN-07:10
Electricity:Zone:FLOOR 3 LOCKER 7.75 110.50 01-JAN-00:10 420.27 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 LOCKER 0.97 3.54 01-JAN-00:10 63.72 02-JAN-07:10
Electricity:Zone:FLOOR 3 LOUNGE 47.03 688.19 12-MAR-16:10 2658.19 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 LOUNGE 4.15 11.64 12-MAR-16:10 403.03 02-JAN-07:10
Electricity:Zone:FLOOR 3 LOUNGE TOILET 2.54 26.84 01-JAN-00:10 148.00 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 LOUNGE TOILET 1.09 3.99 01-JAN-00:10 71.85 02-JAN-07:10
Electricity:Zone:FLOOR 3 MECHANICAL 39.65 544.50 01-JAN-00:10 2174.32 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 MECHANICAL 6.69 24.50 01-JAN-00:10 441.00 02-JAN-07:10
Electricity:Zone:FLOOR 3 MECHANICAL HALL 4.18 42.72 01-JAN-00:10 245.43 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 MECHANICAL HALL 1.92 7.03 01-JAN-00:10 126.45 02-JAN-07:10
Electricity:Zone:FLOOR 3 OFFICE 83.66 1061.94 30-APR-06:40 5044.74 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 OFFICE 20.76 69.65 30-APR-06:40 1737.08 02-JAN-07:10
Electricity:Zone:FLOOR 3 OFFICE HALL 11.62 118.76 01-JAN-00:10 682.29 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 OFFICE HALL 5.33 19.53 01-JAN-00:10 351.53 02-JAN-07:10
Electricity:Zone:FLOOR 3 OFFICE TOILET 0.71 7.55 01-JAN-00:10 41.62 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 OFFICE TOILET 0.31 1.12 01-JAN-00:10 20.21 02-JAN-07:10
Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 1 49.33 625.70 01-JAN-00:10 2762.36 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 1 12.59 46.14 01-JAN-00:10 830.47 02-JAN-07:10
Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 2 22.46 284.94 01-JAN-00:10 1257.94 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 2 5.73 21.01 01-JAN-00:10 378.18 02-JAN-07:10
Electricity:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 1.11 11.74 01-JAN-00:10 64.75 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 0.48 1.75 01-JAN-00:10 31.43 02-JAN-07:10
Electricity:Zone:FLOOR 3 STORAGE 1 0.58 4.60 01-JAN-00:10 35.53 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 STORAGE 1 0.38 1.38 01-JAN-00:10 24.80 02-JAN-07:10
Electricity:Zone:FLOOR 3 STORAGE 2 0.45 3.58 01-JAN-00:10 27.63 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 STORAGE 2 0.29 1.07 01-JAN-00:10 19.29 02-JAN-07:10
Electricity:Zone:FLOOR 3 TREATMENT 18.95 188.90 01-JAN-00:10 1118.35 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 TREATMENT 9.09 33.32 01-JAN-00:10 599.76 02-JAN-07:10
Electricity:Zone:FLOOR 3 UNDEVELOPED 1 54.88 770.21 01-JAN-00:10 2991.64 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 UNDEVELOPED 1 7.89 28.93 01-JAN-00:10 520.70 02-JAN-07:10
Electricity:Zone:FLOOR 3 UNDEVELOPED 2 27.88 391.22 01-JAN-00:10 1519.56 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 UNDEVELOPED 2 4.01 14.69 01-JAN-00:10 264.48 02-JAN-07:10
Electricity:Zone:FLOOR 3 UTILITY 1.16 9.19 01-JAN-00:10 71.06 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 UTILITY 0.75 2.76 01-JAN-00:10 49.59 02-JAN-07:10
Electricity:Zone:FLOOR 3 WORK 16.88 208.85 01-JAN-00:10 953.78 02-JAN-07:10
InteriorLights:Electricity:Zone:FLOOR 3 WORK 4.99 21.24 01-JAN-00:10 328.42 02-JAN-07:10
Electricity:Zone:NE STAIR 2.34 23.92 01-JAN-00:10 137.44 02-JAN-07:10
InteriorLights:Electricity:Zone:NE STAIR 1.07 3.93 01-JAN-00:10 70.81 02-JAN-07:10
Electricity:Zone:NW ELEVATOR 1.95 19.94 01-JAN-00:10 114.53 02-JAN-07:10
InteriorLights:Electricity:Zone:NW ELEVATOR 0.89 3.28 01-JAN-00:10 59.01 02-JAN-07:10
Electricity:Zone:NW STAIR 2.67 27.34 01-JAN-00:10 157.07 02-JAN-07:10
InteriorLights:Electricity:Zone:NW STAIR 1.23 4.50 01-JAN-00:10 80.93 02-JAN-07:10
Electricity:Zone:SW STAIR 1.34 13.67 01-JAN-00:10 78.54 02-JAN-07:10
InteriorLights:Electricity:Zone:SW STAIR 0.61 2.25 01-JAN-00:10 40.46 02-JAN-07:10
InteriorEquipment:Electricity 1829.40 21192.81 01-JAN-00:10 110936.74 02-JAN-09:10
InteriorEquipment:Electricity:Zone:FLOOR 1 ANESTHESIA 4.07 64.19 01-JAN-00:10 213.96 02-JAN-06:10
MiscPlug:InteriorEquipment:Electricity 1190.14 18775.17 01-JAN-00:10 62583.90 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 BIO HAZ 0.11 1.67 01-JAN-00:10 5.57 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 CAFE 7.91 124.75 01-JAN-00:10 415.84 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 CLEAN 4.75 74.89 01-JAN-00:10 249.62 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 CLEAN WORK 6.22 98.07 01-JAN-00:10 326.89 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 DICTATION 2.61 41.18 01-JAN-00:10 137.27 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 DRESSING ROOM 0.93 14.71 01-JAN-00:10 49.03 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 ELECTRICAL ROOM 9.23 145.60 01-JAN-00:10 485.33 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 ELEVATOR PUMP ROOM 639.27 2417.64 01-JAN-00:10 48352.84 02-JAN-09:10
ElevatorLift:InteriorEquipment:Electricity 636.70 2408.24 01-JAN-00:10 48164.84 02-JAN-09:10
ElevatorLightsFan:InteriorEquipment:Electricity 2.57 9.40 01-JAN-00:10 188.00 02-JAN-08:10
InteriorEquipment:Electricity:Zone:FLOOR 1 HUMID 1.12 17.65 01-JAN-00:10 58.83 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 IT HALL 1.06 16.66 01-JAN-00:10 55.52 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 IT ROOM 2.32 36.61 01-JAN-00:10 122.02 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 LOBBY 12.89 203.30 01-JAN-00:10 677.66 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 LOBBY HALL 1.81 28.55 01-JAN-00:10 95.18 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 LOBBY TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 LOCKER ROOM 37.29 588.30 01-JAN-00:10 1961.01 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 LOCKER ROOM HALL 3.74 59.01 01-JAN-00:10 196.71 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 LOUNGE 20.34 320.89 01-JAN-00:10 1069.64 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 MED GAS 0.11 1.67 01-JAN-00:10 5.57 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 MRI CONTROL ROOM 31.64 499.20 01-JAN-00:10 1663.99 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 MRI HALL 1.11 17.49 01-JAN-00:10 58.30 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 MRI ROOM 82.88 1307.42 01-JAN-00:10 4358.06 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 MRI TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 NOURISHMENT 6.86 108.17 01-JAN-00:10 360.56 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 NURSE HALL 3.74 59.01 01-JAN-00:10 196.71 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 NURSE JANITOR 0.10 1.61 01-JAN-00:10 5.37 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 NURSE STATION 9.83 155.12 01-JAN-00:10 517.07 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 NURSE TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 OFFICE 10.01 157.87 01-JAN-00:10 526.22 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 OPERATING ROOM 1 34.66 546.79 01-JAN-00:10 1822.63 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 OPERATING ROOM 2 36.17 570.56 01-JAN-00:10 1901.88 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 OPERATING ROOM 3 35.87 565.81 01-JAN-00:10 1886.03 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 PACU 6.10 96.27 01-JAN-00:10 320.89 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 PRE-OP HALL 3.98 62.82 01-JAN-00:10 209.40 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 PRE-OP ROOM 1 7.12 112.33 01-JAN-00:10 374.43 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 PRE-OP ROOM 2 12.73 200.89 01-JAN-00:10 669.62 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 PRE-OP TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 PROCEDURE ROOM 16.10 254.04 01-JAN-00:10 846.80 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 RECEPTION 10.55 166.36 01-JAN-00:10 554.54 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 RECEPTION HALL 0.97 15.23 01-JAN-00:10 50.76 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 RECOVERY ROOM 30.51 481.34 01-JAN-00:10 1604.46 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 SCHEDULING 2.47 38.89 01-JAN-00:10 129.65 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 SCRUB 0.63 9.99 01-JAN-00:10 33.31 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 SOIL 4.75 74.89 01-JAN-00:10 249.62 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 SOIL HOLD 2.11 33.28 01-JAN-00:10 110.94 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 SOIL WORK 6.78 106.98 01-JAN-00:10 356.60 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 STEP DOWN 16.95 267.41 01-JAN-00:10 891.37 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 STERILE HALL 4.65 73.29 01-JAN-00:10 244.30 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 STERILE STORAGE 0.75 11.81 01-JAN-00:10 39.35 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 STORAGE 1.74 27.43 01-JAN-00:10 91.43 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 SUB-STERILE 1.48 23.32 01-JAN-00:10 77.73 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 UTILITY HALL 1.93 30.46 01-JAN-00:10 101.53 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 UTILITY JANITOR 0.08 1.25 01-JAN-00:10 4.17 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 UTILITY ROOM 0.68 10.73 01-JAN-00:10 35.78 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 1 VESTIBULE 0.54 8.57 01-JAN-00:10 28.55 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 CONFERENCE 6.33 99.80 01-JAN-00:10 332.67 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 CONFERENCE TOILET 0.48 7.61 01-JAN-00:10 25.38 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 DICTATION 1.45 22.88 01-JAN-00:10 76.26 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 1 7.46 117.66 01-JAN-00:10 392.21 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 2 11.19 176.50 01-JAN-00:10 588.32 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 3 14.92 235.33 01-JAN-00:10 784.42 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 4 1.74 27.45 01-JAN-00:10 91.52 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 5 7.25 114.40 01-JAN-00:10 381.32 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 6 4.66 73.54 01-JAN-00:10 245.13 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 7 16.41 258.86 01-JAN-00:10 862.87 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 8 5.59 88.25 01-JAN-00:10 294.16 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM 9 8.20 129.43 01-JAN-00:10 431.43 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 1 1.36 21.42 01-JAN-00:10 71.39 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 2 1.36 21.42 01-JAN-00:10 71.39 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 3 1.36 21.42 01-JAN-00:10 71.39 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 4 1.49 23.56 01-JAN-00:10 78.53 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 5 1.49 23.56 01-JAN-00:10 78.53 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 EXAM HALL 6 1.49 23.56 01-JAN-00:10 78.53 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 JANITOR 0.12 1.88 01-JAN-00:10 6.26 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 LOUNGE 4.52 71.31 01-JAN-00:10 237.70 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 NURSE STATION 1 5.65 89.15 01-JAN-00:10 297.17 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 NURSE STATION 2 6.78 106.98 01-JAN-00:10 356.60 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 OFFICE 11.60 183.03 01-JAN-00:10 610.11 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 OFFICE HALL 3.35 52.83 01-JAN-00:10 176.09 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 RECEPTION 20.39 321.61 01-JAN-00:10 1072.05 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 RECEPTION HALL 4.25 67.10 01-JAN-00:10 223.68 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 RECEPTION TOILET 0.95 14.99 01-JAN-00:10 49.97 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 SCHEDULING 1 6.71 105.90 01-JAN-00:10 352.99 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 SCHEDULING 2 7.09 111.78 01-JAN-00:10 372.60 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 STORAGE 1 0.11 1.67 01-JAN-00:10 5.57 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 STORAGE 2 0.23 3.58 01-JAN-00:10 11.93 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 STORAGE 3 0.27 4.29 01-JAN-00:10 14.31 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 UTILITY 0.24 3.76 01-JAN-00:10 12.52 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 WORK 28.92 456.27 01-JAN-00:10 1520.91 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 WORK HALL 6.29 99.23 01-JAN-00:10 330.76 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 WORK TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 2 X-RAY 169.52 2674.27 01-JAN-00:10 8914.22 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 DRESSING ROOM 0.87 13.73 01-JAN-00:10 45.76 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 ELEVATOR HALL 2.79 44.02 01-JAN-00:10 146.74 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 HUMID 2.24 35.30 01-JAN-00:10 117.66 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 JANITOR 0.12 1.88 01-JAN-00:10 6.26 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 LOCKER 6.78 106.96 01-JAN-00:10 356.55 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 LOUNGE 42.89 676.55 01-JAN-00:10 2255.16 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 LOUNGE TOILET 1.45 22.84 01-JAN-00:10 76.15 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 MECHANICAL 32.96 520.00 01-JAN-00:10 1733.32 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 MECHANICAL HALL 2.26 35.69 01-JAN-00:10 118.98 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 OFFICE 62.90 992.30 01-JAN-00:10 3307.66 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 OFFICE HALL 6.29 99.23 01-JAN-00:10 330.76 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 OFFICE TOILET 0.41 6.42 01-JAN-00:10 21.42 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 1 36.74 579.57 01-JAN-00:10 1931.89 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY 2 16.73 263.93 01-JAN-00:10 879.75 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 0.63 9.99 01-JAN-00:10 33.31 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 STORAGE 1 0.20 3.22 01-JAN-00:10 10.73 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 STORAGE 2 0.16 2.50 01-JAN-00:10 8.35 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 TREATMENT 9.86 155.58 01-JAN-00:10 518.59 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 UNDEVELOPED 1 46.99 741.28 01-JAN-00:10 2470.94 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 UNDEVELOPED 2 23.87 376.52 01-JAN-00:10 1255.08 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 UTILITY 0.41 6.44 01-JAN-00:10 21.47 02-JAN-06:10
InteriorEquipment:Electricity:Zone:FLOOR 3 WORK 11.89 187.61 01-JAN-00:10 625.36 02-JAN-06:10
InteriorEquipment:Electricity:Zone:NE STAIR 1.27 19.99 01-JAN-00:10 66.63 02-JAN-06:10
InteriorEquipment:Electricity:Zone:NW ELEVATOR 1.06 16.66 01-JAN-00:10 55.52 02-JAN-06:10
InteriorEquipment:Electricity:Zone:NW STAIR 1.45 22.84 01-JAN-00:10 76.15 02-JAN-06:10
InteriorEquipment:Electricity:Zone:SW STAIR 0.72 11.42 01-JAN-00:10 38.07 02-JAN-06:10
ElectricityPurchased:Facility 3537.24 30321.66 10-SEP-07:00 291538.95 09-JAN-07:20
ElectricityPurchased:Plant 3537.24 30321.66 10-SEP-07:00 291538.95 09-JAN-07:20
Cogeneration:ElectricityPurchased 3537.24 30321.66 10-SEP-07:00 291538.95 09-JAN-07:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 3537.24 30321.66 10-SEP-07:00 291538.95 09-JAN-07:20
ElectricityNet:Plant 3537.24 30321.66 10-SEP-07:00 291538.95 09-JAN-07:20
Cogeneration:ElectricityNet 3537.24 30321.66 10-SEP-07:00 291538.95 09-JAN-07:20
Electricity:HVAC 1264.20 6473.30 10-OCT-21:50 172103.08 09-JAN-07:20
Fans:Electricity 345.45 6446.41 27-DEC-22:10 27402.49 21-APR-16:00
General:Fans:Electricity 345.45 6446.41 27-DEC-22:10 27402.49 21-APR-16:00
Heating:Electricity 253.03 0.00 15-APR-00:20 128516.87 09-JAN-07:20
ExteriorLights:Electricity 55.34 0.00 01-JAN-08:20 5724.00 01-JAN-06:10
General:ExteriorLights:Electricity 55.34 0.00 01-JAN-08:20 5724.00 01-JAN-06:10
Cooling:Electricity 347.07 0.00 01-JAN-00:10 109128.28 29-JUN-16:00
Humidifier:Electricity 318.66 0.00 14-APR-06:50 31787.87 06-JAN-06:10
Electricity:Plant 7.47 45.98 21-JUL-17:20 585.39 01-JAN-08:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 7.47 45.98 21-JUL-17:20 585.39 01-JAN-08:10
General:Pumps:Electricity 7.47 45.98 21-JUL-17:20 585.39 01-JAN-08:10


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 1730.69 11093.57 25-OCT-20:40 181705.78 26-DEC-12:00
Gas:Building 188.37 2971.73 01-JAN-00:10 9905.77 02-JAN-06:10
Gas:Zone:FLOOR 1 OPERATING ROOM 1 61.20 965.39 01-JAN-00:10 3217.98 02-JAN-06:10
InteriorEquipment:Gas 188.37 2971.73 01-JAN-00:10 9905.77 02-JAN-06:10
InteriorEquipment:Gas:Zone:FLOOR 1 OPERATING ROOM 1 61.20 965.39 01-JAN-00:10 3217.98 02-JAN-06:10
MiscPlug:InteriorEquipment:Gas 188.37 2971.73 01-JAN-00:10 9905.77 02-JAN-06:10
Gas:Zone:FLOOR 1 OPERATING ROOM 2 63.86 1007.37 01-JAN-00:10 3357.89 02-JAN-06:10
InteriorEquipment:Gas:Zone:FLOOR 1 OPERATING ROOM 2 63.86 1007.37 01-JAN-00:10 3357.89 02-JAN-06:10
Gas:Zone:FLOOR 1 OPERATING ROOM 3 63.32 998.97 01-JAN-00:10 3329.91 02-JAN-06:10
InteriorEquipment:Gas:Zone:FLOOR 1 OPERATING ROOM 3 63.32 998.97 01-JAN-00:10 3329.91 02-JAN-06:10
Gas:Plant 1542.32 8121.84 25-OCT-20:40 171800.01 26-DEC-12:00
WaterSystems:Gas 240.06 6496.32 03-JAN-00:30 23294.11 14-FEB-12:00
Water Heater:WaterSystems:Gas 240.06 6496.32 03-JAN-00:30 23294.11 14-FEB-12:00
Heating:Gas 1302.26 1625.52 25-OCT-20:40 150515.18 25-NOV-16:40
Boiler:Heating:Gas 1302.26 1625.52 25-OCT-20:40 150515.18 25-NOV-16:40


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 597.38 0.00 23-APR-16:10 0.00 04-JAN-12:00
Water:Plant 478.84 0.00 01-JAN-00:10 0.00 02-JAN-13:10
WaterSystems:Water 478.84 0.00 01-JAN-00:10 0.00 02-JAN-13:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MainsWater:Facility 597.38 0.00 23-APR-16:10 0.00 04-JAN-12:00
MainsWater:Plant 478.84 0.00 01-JAN-00:10 0.00 02-JAN-13:10
WaterSystems:MainsWater 478.84 0.00 01-JAN-00:10 0.00 02-JAN-13:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterUse:WaterSystems:Water 478.84 0.00 01-JAN-00:10 0.00 02-JAN-13:10
WaterUse:WaterSystems:MainsWater 478.84 0.00 01-JAN-00:10 0.00 02-JAN-13:10
Water:HVAC 118.54 0.00 14-APR-06:50 0.00 06-JAN-06:10
Humidifier:Water 118.54 0.00 14-APR-06:50 0.00 06-JAN-06:10
MainsWater:HVAC 118.54 0.00 14-APR-06:50 0.00 06-JAN-06:10
Humidifier:MainsWater 118.54 0.00 14-APR-06:50 0.00 06-JAN-06:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 1132.68 3664.36 08-SEP-21:10 150590.59 09-JAN-08:10
PlantLoopHeatingDemand:Plant 105.79 0.00 01-JAN-00:10 12900.15 24-FEB-11:10
WaterSystems:PlantLoopHeatingDemand 105.79 0.00 01-JAN-00:10 12900.15 24-FEB-11:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Facility 5743.28 50741.24 30-OCT-23:10 539161.27 30-JUN-16:00
EnergyTransfer:Building 2003.22 19667.60 17-JAN-03:10 144489.73 30-JUN-16:10
EnergyTransfer:Zone:FLOOR 1 ANESTHESIA 8.56 0.03 08-JAN-20:50 642.55 19-OCT-14:40
Heating:EnergyTransfer 100.64 0.00 12-APR-17:10 50543.82 09-JAN-05:10
Heating:EnergyTransfer:Zone:FLOOR 1 ANESTHESIA 0.03 0.00 01-JAN-08:50 150.00 13-FEB-05:10
Cooling:EnergyTransfer 1902.58 8005.34 01-JAN-00:20 144489.73 30-JUN-16:10
Cooling:EnergyTransfer:Zone:FLOOR 1 ANESTHESIA 8.53 0.00 01-JAN-00:10 642.55 19-OCT-14:40
EnergyTransfer:Zone:FLOOR 1 BIO HAZ 0.59 0.00 19-MAY-09:30 96.56 02-JAN-05:20
Heating:EnergyTransfer:Zone:FLOOR 1 BIO HAZ 0.33 0.00 02-JAN-18:10 96.56 02-JAN-05:20
Cooling:EnergyTransfer:Zone:FLOOR 1 BIO HAZ 0.25 0.00 01-JAN-00:10 19.57 30-JUN-17:00
EnergyTransfer:Zone:FLOOR 1 CAFE 41.90 0.14 01-JAN-02:40 3961.22 19-OCT-14:10
Heating:EnergyTransfer:Zone:FLOOR 1 CAFE 0.00 0.00 01-JAN-00:10 142.44 09-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 CAFE 41.90 0.00 01-JAN-02:50 3961.22 19-OCT-14:10
EnergyTransfer:Zone:FLOOR 1 CLEAN 12.94 84.16 01-JAN-17:10 591.95 16-MAR-13:50
Heating:EnergyTransfer:Zone:FLOOR 1 CLEAN 0.00 0.00 01-JAN-00:10 33.73 01-MAY-04:10
Cooling:EnergyTransfer:Zone:FLOOR 1 CLEAN 12.94 84.16 01-JAN-17:10 591.95 16-MAR-13:50
EnergyTransfer:Zone:FLOOR 1 CLEAN WORK 14.29 74.10 01-JAN-17:10 708.04 16-MAR-13:50
Heating:EnergyTransfer:Zone:FLOOR 1 CLEAN WORK 0.00 0.00 01-JAN-00:10 53.93 17-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 CLEAN WORK 14.29 74.10 01-JAN-17:10 708.04 16-MAR-13:50
EnergyTransfer:Zone:FLOOR 1 DICTATION 3.23 0.00 02-JAN-12:10 300.05 12-JAN-15:30
Heating:EnergyTransfer:Zone:FLOOR 1 DICTATION 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 DICTATION 3.23 0.00 02-JAN-12:10 300.05 12-JAN-15:30
EnergyTransfer:Zone:FLOOR 1 DRESSING ROOM 1.29 0.00 02-JAN-12:10 197.28 02-JAN-05:10
Heating:EnergyTransfer:Zone:FLOOR 1 DRESSING ROOM 0.73 0.00 02-JAN-12:10 197.28 02-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 DRESSING ROOM 0.56 0.00 01-JAN-00:10 103.42 09-AUG-14:30
EnergyTransfer:Zone:FLOOR 1 ELECTRICAL ROOM 5.06 9.46 02-JAN-04:00 478.35 25-AUG-11:00
Heating:EnergyTransfer:Zone:FLOOR 1 ELECTRICAL ROOM 0.00 0.00 01-JAN-00:10 19.81 07-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 1 ELECTRICAL ROOM 5.06 9.46 02-JAN-04:00 478.35 25-AUG-11:00
EnergyTransfer:Zone:FLOOR 1 ELEVATOR PUMP ROOM 38.22 0.09 25-DEC-07:00 3322.38 25-AUG-17:00
Heating:EnergyTransfer:Zone:FLOOR 1 ELEVATOR PUMP ROOM 0.01 0.00 01-JAN-00:10 172.26 02-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 ELEVATOR PUMP ROOM 38.21 0.00 01-JAN-03:10 3322.38 25-AUG-17:00
EnergyTransfer:Zone:FLOOR 1 HUMID 1.77 0.00 02-JAN-12:10 155.35 27-JAN-07:20
Heating:EnergyTransfer:Zone:FLOOR 1 HUMID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 HUMID 1.77 0.00 02-JAN-12:10 155.35 27-JAN-07:20
EnergyTransfer:Zone:FLOOR 1 IT HALL 1.58 0.76 26-DEC-05:50 95.19 25-AUG-07:50
Heating:EnergyTransfer:Zone:FLOOR 1 IT HALL 0.00 0.00 01-JAN-00:10 25.62 02-JAN-05:20
Cooling:EnergyTransfer:Zone:FLOOR 1 IT HALL 1.58 0.00 02-JAN-05:10 95.19 25-AUG-07:50
EnergyTransfer:Zone:FLOOR 1 IT ROOM 1.75 0.00 02-JAN-12:10 152.01 21-JUL-14:10
Heating:EnergyTransfer:Zone:FLOOR 1 IT ROOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 IT ROOM 1.75 0.00 02-JAN-12:10 152.01 21-JUL-14:10
EnergyTransfer:Zone:FLOOR 1 LOBBY 23.87 0.63 01-JAN-10:30 3124.78 30-JUN-17:00
Heating:EnergyTransfer:Zone:FLOOR 1 LOBBY 0.04 0.00 01-JAN-10:30 837.12 02-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 1 LOBBY 23.83 0.00 01-JAN-00:10 3124.78 30-JUN-17:00
EnergyTransfer:Zone:FLOOR 1 LOBBY HALL 5.89 22.57 02-JAN-08:50 511.17 30-JUN-06:20
Heating:EnergyTransfer:Zone:FLOOR 1 LOBBY HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 LOBBY HALL 5.89 22.57 02-JAN-08:50 511.17 30-JUN-06:20
EnergyTransfer:Zone:FLOOR 1 LOBBY TOILET 5.31 0.04 28-MAR-07:10 407.32 11-AUG-17:10
Heating:EnergyTransfer:Zone:FLOOR 1 LOBBY TOILET 0.06 0.00 01-JAN-11:50 211.71 02-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 1 LOBBY TOILET 5.25 0.00 01-JAN-00:10 407.32 11-AUG-17:10
EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM 31.21 49.93 02-JAN-03:00 2570.16 21-JUL-16:00
Heating:EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM 31.21 49.93 02-JAN-03:00 2570.16 21-JUL-16:00
EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM HALL 6.03 10.72 02-JAN-06:40 393.05 01-DEC-18:00
Heating:EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM HALL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 LOCKER ROOM HALL 6.03 10.72 02-JAN-06:40 393.05 01-DEC-18:00
EnergyTransfer:Zone:FLOOR 1 LOUNGE 17.24 57.74 02-JAN-03:00 1281.07 30-JUN-17:00
Heating:EnergyTransfer:Zone:FLOOR 1 LOUNGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 LOUNGE 17.24 57.74 02-JAN-03:00 1281.07 30-JUN-17:00
EnergyTransfer:Zone:FLOOR 1 MED GAS 4.13 0.00 16-AUG-11:00 365.69 16-MAR-04:40
Heating:EnergyTransfer:Zone:FLOOR 1 MED GAS 3.87 0.00 17-JAN-18:10 365.69 16-MAR-04:40
Cooling:EnergyTransfer:Zone:FLOOR 1 MED GAS 0.26 0.00 01-JAN-00:10 67.92 08-AUG-17:10
EnergyTransfer:Zone:FLOOR 1 MRI CONTROL ROOM 24.94 102.84 02-JAN-03:00 1856.93 21-JUL-15:00
Heating:EnergyTransfer:Zone:FLOOR 1 MRI CONTROL ROOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 MRI CONTROL ROOM 24.94 102.84 02-JAN-03:00 1856.93 21-JUL-15:00
EnergyTransfer:Zone:FLOOR 1 MRI HALL 2.50 0.81 02-JAN-05:40 204.72 21-JUL-17:00
Heating:EnergyTransfer:Zone:FLOOR 1 MRI HALL 0.00 0.00 01-JAN-00:10 15.54 02-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 MRI HALL 2.50 0.00 02-JAN-05:30 204.72 21-JUL-17:00
EnergyTransfer:Zone:FLOOR 1 MRI ROOM 71.54 435.52 02-JAN-03:00 4631.42 30-JUN-06:20
Heating:EnergyTransfer:Zone:FLOOR 1 MRI ROOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 MRI ROOM 71.54 435.52 02-JAN-03:00 4631.42 30-JUN-06:20
EnergyTransfer:Zone:FLOOR 1 MRI TOILET 1.67 0.00 30-MAR-14:40 183.83 02-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 1 MRI TOILET 0.26 0.00 02-JAN-18:10 183.83 02-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 1 MRI TOILET 1.42 0.00 01-JAN-00:10 112.36 09-AUG-17:10
EnergyTransfer:Zone:FLOOR 1 NOURISHMENT 9.51 43.69 02-JAN-03:00 752.96 15-DEC-10:20
Heating:EnergyTransfer:Zone:FLOOR 1 NOURISHMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 NOURISHMENT 9.51 43.69 02-JAN-03:00 752.96 15-DEC-10:20
EnergyTransfer:Zone:FLOOR 1 NURSE HALL 6.76 0.42 02-JAN-07:00 673.62 27-JAN-14:10
Heating:EnergyTransfer:Zone:FLOOR 1 NURSE HALL 0.00 0.00 01-JAN-00:10 39.24 17-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 NURSE HALL 6.76 0.00 02-JAN-06:50 673.62 27-JAN-14:10
EnergyTransfer:Zone:FLOOR 1 NURSE JANITOR 0.99 2.66 02-JAN-14:00 85.90 15-DEC-07:20
Heating:EnergyTransfer:Zone:FLOOR 1 NURSE JANITOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 NURSE JANITOR 0.99 2.66 02-JAN-14:00 85.90 15-DEC-07:20
EnergyTransfer:Zone:FLOOR 1 NURSE STATION 11.62 48.74 02-JAN-03:00 908.66 27-JAN-15:10
Heating:EnergyTransfer:Zone:FLOOR 1 NURSE STATION 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 NURSE STATION 11.62 48.74 02-JAN-03:00 908.66 27-JAN-15:10
EnergyTransfer:Zone:FLOOR 1 NURSE TOILET 2.61 0.04 17-JAN-05:30 162.04 27-OCT-17:10
Heating:EnergyTransfer:Zone:FLOOR 1 NURSE TOILET 0.00 0.00 01-JAN-00:10 32.09 17-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 NURSE TOILET 2.61 0.00 17-JAN-06:20 162.04 27-OCT-17:10
EnergyTransfer:Zone:FLOOR 1 OFFICE 10.78 0.00 02-JAN-12:10 911.74 30-JUN-14:10
Heating:EnergyTransfer:Zone:FLOOR 1 OFFICE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 OFFICE 10.78 0.00 02-JAN-12:10 911.74 30-JUN-14:10
EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 1 83.64 162.83 25-DEC-17:10 6285.74 01-SEP-14:10
Heating:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 1 0.00 0.00 01-JAN-00:10 151.97 15-APR-17:10
Cooling:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 1 83.64 162.83 25-DEC-17:10 6285.74 01-SEP-14:10
EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 2 93.78 193.47 01-JAN-17:10 6425.30 25-AUG-09:30
Heating:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 2 0.00 0.00 01-JAN-00:10 86.46 14-MAY-07:00
Cooling:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 2 93.78 193.47 01-JAN-17:10 6425.30 25-AUG-09:30
EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 3 104.45 574.95 17-JAN-03:10 5855.57 08-DEC-14:00
Heating:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 3 0.06 0.00 01-JAN-00:10 893.83 16-JAN-22:50
Cooling:EnergyTransfer:Zone:FLOOR 1 OPERATING ROOM 3 104.40 574.95 17-JAN-03:10 5855.57 08-DEC-14:00
EnergyTransfer:Zone:FLOOR 1 PACU 11.17 62.65 17-JAN-03:10 576.26 16-MAR-13:50
Heating:EnergyTransfer:Zone:FLOOR 1 PACU 0.00 0.00 01-JAN-00:10 34.96 01-MAY-04:10
Cooling:EnergyTransfer:Zone:FLOOR 1 PACU 11.17 62.65 17-JAN-03:10 576.26 16-MAR-13:50
EnergyTransfer:Zone:FLOOR 1 PRE-OP HALL 6.43 5.74 02-JAN-06:00 447.25 30-JUN-17:00
Heating:EnergyTransfer:Zone:FLOOR 1 PRE-OP HALL 0.00 0.00 01-JAN-00:10 58.65 02-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 PRE-OP HALL 6.43 0.00 02-JAN-05:30 447.25 30-JUN-17:00
EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 1 12.36 0.53 07-JAN-06:00 917.25 30-JUN-17:10
Heating:EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 1 0.00 0.00 01-JAN-00:10 147.46 07-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 1 12.36 0.00 07-JAN-05:30 917.25 30-JUN-17:10
EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 2 28.85 186.06 01-JAN-17:10 1609.21 06-OCT-17:10
Heating:EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 2 0.00 0.00 01-JAN-00:10 110.73 25-MAR-04:10
Cooling:EnergyTransfer:Zone:FLOOR 1 PRE-OP ROOM 2 28.85 186.06 01-JAN-17:10 1609.21 06-OCT-17:10
EnergyTransfer:Zone:FLOOR 1 PRE-OP TOILET 2.94 0.01 19-MAR-02:10 331.93 06-JAN-18:20
Heating:EnergyTransfer:Zone:FLOOR 1 PRE-OP TOILET 1.88 0.00 07-JAN-15:10 331.93 06-JAN-18:20
Cooling:EnergyTransfer:Zone:FLOOR 1 PRE-OP TOILET 1.06 0.00 01-JAN-00:10 150.81 29-JUN-17:00
EnergyTransfer:Zone:FLOOR 1 PROCEDURE ROOM 25.40 1.09 01-JAN-14:10 2117.13 21-JUL-17:10
Heating:EnergyTransfer:Zone:FLOOR 1 PROCEDURE ROOM 0.03 0.00 01-JAN-12:00 308.35 02-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 PROCEDURE ROOM 25.37 0.00 01-JAN-00:10 2117.13 21-JUL-17:10
EnergyTransfer:Zone:FLOOR 1 RECEPTION 24.73 51.09 02-JAN-04:00 2267.91 01-SEP-14:00
Heating:EnergyTransfer:Zone:FLOOR 1 RECEPTION 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 RECEPTION 24.73 51.09 02-JAN-04:00 2267.91 01-SEP-14:00
EnergyTransfer:Zone:FLOOR 1 RECEPTION HALL 1.76 0.84 02-JAN-06:50 118.21 25-AUG-17:00
Heating:EnergyTransfer:Zone:FLOOR 1 RECEPTION HALL 0.00 0.00 01-JAN-00:10 2.30 02-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 RECEPTION HALL 1.76 0.84 02-JAN-06:50 118.21 25-AUG-17:00
EnergyTransfer:Zone:FLOOR 1 RECOVERY ROOM 41.97 0.06 25-DEC-00:30 3089.60 19-OCT-14:30
Heating:EnergyTransfer:Zone:FLOOR 1 RECOVERY ROOM 0.12 0.00 01-JAN-08:40 676.79 13-FEB-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 RECOVERY ROOM 41.85 0.00 01-JAN-00:10 3089.60 19-OCT-14:30
EnergyTransfer:Zone:FLOOR 1 SCHEDULING 2.13 0.00 02-JAN-12:10 296.27 19-OCT-14:30
Heating:EnergyTransfer:Zone:FLOOR 1 SCHEDULING 0.01 0.00 01-JAN-00:10 112.71 02-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 1 SCHEDULING 2.13 0.00 01-JAN-02:10 296.27 19-OCT-14:30
EnergyTransfer:Zone:FLOOR 1 SCRUB 1.02 0.01 01-JAN-06:20 140.49 17-JAN-07:20
Heating:EnergyTransfer:Zone:FLOOR 1 SCRUB 0.02 0.00 01-JAN-00:10 140.49 17-JAN-07:20
Cooling:EnergyTransfer:Zone:FLOOR 1 SCRUB 1.00 0.00 01-JAN-06:20 79.43 25-AUG-07:50
EnergyTransfer:Zone:FLOOR 1 SOIL 11.60 67.14 01-JAN-17:10 572.69 16-MAR-13:50
Heating:EnergyTransfer:Zone:FLOOR 1 SOIL 0.00 0.00 01-JAN-00:10 34.75 01-MAY-04:10
Cooling:EnergyTransfer:Zone:FLOOR 1 SOIL 11.60 67.14 01-JAN-17:10 572.69 16-MAR-13:50
EnergyTransfer:Zone:FLOOR 1 SOIL HOLD 4.64 2.91 17-JAN-03:10 221.61 30-JUN-17:00
Heating:EnergyTransfer:Zone:FLOOR 1 SOIL HOLD 0.00 0.00 01-JAN-00:10 9.23 17-JAN-02:30
Cooling:EnergyTransfer:Zone:FLOOR 1 SOIL HOLD 4.64 2.59 17-JAN-03:10 221.61 30-JUN-17:00
EnergyTransfer:Zone:FLOOR 1 SOIL WORK 14.17 69.86 17-JAN-03:10 733.75 16-MAR-17:00
Heating:EnergyTransfer:Zone:FLOOR 1 SOIL WORK 0.00 0.00 01-JAN-00:10 76.06 17-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 SOIL WORK 14.17 69.86 17-JAN-03:10 733.75 16-MAR-17:00
EnergyTransfer:Zone:FLOOR 1 STEP DOWN 21.05 0.00 26-FEB-05:00 1812.91 19-OCT-15:00
Heating:EnergyTransfer:Zone:FLOOR 1 STEP DOWN 0.28 0.00 01-JAN-09:50 637.40 09-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 STEP DOWN 20.77 0.00 01-JAN-00:10 1812.91 19-OCT-15:00
EnergyTransfer:Zone:FLOOR 1 STERILE HALL 6.13 0.11 06-NOV-09:40 514.50 01-SEP-14:20
Heating:EnergyTransfer:Zone:FLOOR 1 STERILE HALL 0.05 0.00 01-JAN-00:10 369.65 17-JAN-07:20
Cooling:EnergyTransfer:Zone:FLOOR 1 STERILE HALL 6.08 0.00 02-JAN-05:20 514.50 01-SEP-14:20
EnergyTransfer:Zone:FLOOR 1 STERILE STORAGE 4.42 10.28 17-JAN-07:50 338.19 15-DEC-07:10
Heating:EnergyTransfer:Zone:FLOOR 1 STERILE STORAGE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 1 STERILE STORAGE 4.42 10.28 17-JAN-07:50 338.19 15-DEC-07:10
EnergyTransfer:Zone:FLOOR 1 STORAGE 24.09 0.00 14-OCT-02:50 2506.08 02-JAN-05:10
Heating:EnergyTransfer:Zone:FLOOR 1 STORAGE 20.66 0.00 02-JAN-18:10 2506.08 02-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 STORAGE 3.43 0.00 01-JAN-00:10 501.98 21-JUL-16:20
EnergyTransfer:Zone:FLOOR 1 SUB-STERILE 2.92 0.06 05-MAR-00:10 504.89 17-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 1 SUB-STERILE 0.83 0.00 02-JAN-18:10 504.89 17-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 1 SUB-STERILE 2.09 0.00 01-JAN-00:10 359.42 25-AUG-09:30
EnergyTransfer:Zone:FLOOR 1 UTILITY HALL 5.60 0.02 26-APR-01:50 733.62 02-JAN-05:10
Heating:EnergyTransfer:Zone:FLOOR 1 UTILITY HALL 4.05 0.00 02-JAN-18:10 733.62 02-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 UTILITY HALL 1.56 0.00 01-JAN-00:10 153.76 21-JUL-16:10
EnergyTransfer:Zone:FLOOR 1 UTILITY JANITOR 0.50 0.00 13-FEB-13:00 67.60 17-JAN-07:20
Heating:EnergyTransfer:Zone:FLOOR 1 UTILITY JANITOR 0.02 0.00 01-JAN-00:10 67.60 17-JAN-07:20
Cooling:EnergyTransfer:Zone:FLOOR 1 UTILITY JANITOR 0.48 0.00 01-JAN-05:10 33.59 25-AUG-15:20
EnergyTransfer:Zone:FLOOR 1 UTILITY ROOM 4.79 0.00 22-SEP-07:30 745.71 02-JAN-05:10
Heating:EnergyTransfer:Zone:FLOOR 1 UTILITY ROOM 2.44 0.00 02-JAN-18:10 745.71 02-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 1 UTILITY ROOM 2.34 0.00 01-JAN-00:10 283.71 29-JUL-09:30
EnergyTransfer:Zone:FLOOR 1 VESTIBULE 5.72 0.00 29-MAY-23:30 611.30 06-JAN-09:30
Heating:EnergyTransfer:Zone:FLOOR 1 VESTIBULE 5.08 0.00 20-FEB-14:20 611.30 06-JAN-09:30
Cooling:EnergyTransfer:Zone:FLOOR 1 VESTIBULE 0.64 0.00 01-JAN-00:10 442.17 29-JUN-16:00
EnergyTransfer:Zone:FLOOR 2 CONFERENCE 18.02 0.01 14-DEC-02:00 2394.64 01-SEP-13:00
Heating:EnergyTransfer:Zone:FLOOR 2 CONFERENCE 0.59 0.00 01-JAN-09:40 873.01 09-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 2 CONFERENCE 17.43 0.00 01-JAN-00:10 2394.64 01-SEP-13:00
EnergyTransfer:Zone:FLOOR 2 CONFERENCE TOILET 2.71 0.00 27-MAR-08:00 189.93 02-DEC-17:10
Heating:EnergyTransfer:Zone:FLOOR 2 CONFERENCE TOILET 0.04 0.00 01-JAN-00:10 160.84 26-DEC-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 CONFERENCE TOILET 2.67 0.00 02-JAN-05:20 189.93 02-DEC-17:10
EnergyTransfer:Zone:FLOOR 2 DICTATION 1.39 0.50 17-JAN-07:50 123.83 20-OCT-17:00
Heating:EnergyTransfer:Zone:FLOOR 2 DICTATION 0.00 0.00 01-JAN-00:10 49.85 02-JAN-07:20
Cooling:EnergyTransfer:Zone:FLOOR 2 DICTATION 1.39 0.00 02-JAN-07:20 123.83 20-OCT-17:00
EnergyTransfer:Zone:FLOOR 2 EXAM 1 18.68 0.00 10-DEC-17:00 2286.70 30-JUN-17:00
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 1 1.04 0.00 01-JAN-14:30 1239.73 07-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 1 17.64 0.00 01-JAN-00:10 2286.70 30-JUN-17:00
EnergyTransfer:Zone:FLOOR 2 EXAM 2 35.24 0.17 25-FEB-08:20 2268.90 01-SEP-17:10
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 2 0.18 0.00 01-JAN-00:10 781.95 05-JUN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 2 35.06 0.00 01-JAN-03:20 2268.90 01-SEP-17:10
EnergyTransfer:Zone:FLOOR 2 EXAM 3 44.49 0.12 23-DEC-08:30 3050.29 19-OCT-13:40
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 3 0.26 0.00 01-JAN-00:10 1059.67 05-JUN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 3 44.23 0.00 01-JAN-02:00 3050.29 19-OCT-13:40
EnergyTransfer:Zone:FLOOR 2 EXAM 4 5.27 0.01 04-MAR-11:20 546.29 19-OCT-13:20
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 4 0.11 0.00 01-JAN-09:20 247.68 09-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 4 5.15 0.00 01-JAN-00:10 546.29 19-OCT-13:20
EnergyTransfer:Zone:FLOOR 2 EXAM 5 22.54 0.05 14-JAN-15:00 1643.44 15-JUN-09:00
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 5 0.20 0.00 01-JAN-09:00 736.61 07-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 5 22.34 0.00 01-JAN-00:10 1643.44 15-JUN-09:00
EnergyTransfer:Zone:FLOOR 2 EXAM 6 12.28 0.03 15-APR-06:30 912.67 29-JUN-17:10
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 6 0.24 0.00 02-JAN-10:40 517.05 07-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 6 12.04 0.00 01-JAN-00:10 912.67 29-JUN-17:10
EnergyTransfer:Zone:FLOOR 2 EXAM 7 48.19 0.40 25-DEC-05:20 3230.10 30-JUN-17:10
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 7 0.27 0.00 01-JAN-10:10 1144.92 05-JUN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 7 47.92 0.00 01-JAN-00:10 3230.10 30-JUN-17:10
EnergyTransfer:Zone:FLOOR 2 EXAM 8 16.68 0.16 02-JAN-10:10 1155.61 30-JUN-15:30
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 8 0.19 0.00 02-JAN-10:10 541.17 07-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 8 16.49 0.00 01-JAN-00:10 1155.61 30-JUN-15:30
EnergyTransfer:Zone:FLOOR 2 EXAM 9 26.65 0.01 25-FEB-08:00 1662.95 30-JUN-17:10
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM 9 0.12 0.00 01-JAN-11:30 540.65 26-JUN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM 9 26.53 0.00 01-JAN-00:10 1662.95 30-JUN-17:10
EnergyTransfer:Zone:FLOOR 2 EXAM HALL 1 2.00 0.00 19-JAN-08:40 374.23 01-SEP-17:00
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 1 0.13 0.00 01-JAN-00:10 360.60 02-JAN-07:30
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 1 1.87 0.00 01-JAN-01:50 374.23 01-SEP-17:00
EnergyTransfer:Zone:FLOOR 2 EXAM HALL 2 1.94 0.02 04-DEC-12:00 260.95 19-OCT-15:50
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 2 0.05 0.00 01-JAN-00:10 240.14 17-JAN-07:40
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 2 1.88 0.00 02-JAN-05:20 260.95 19-OCT-15:50
EnergyTransfer:Zone:FLOOR 2 EXAM HALL 3 1.90 0.01 11-SEP-07:30 270.99 19-OCT-16:00
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 3 0.07 0.00 01-JAN-00:10 248.21 17-JAN-07:50
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 3 1.83 0.00 02-JAN-05:20 270.99 19-OCT-16:00
EnergyTransfer:Zone:FLOOR 2 EXAM HALL 4 2.03 0.02 02-DEC-09:40 243.06 06-JAN-09:00
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 4 0.04 0.00 01-JAN-13:50 195.81 02-JAN-05:30
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 4 1.99 0.00 01-JAN-00:10 243.06 06-JAN-09:00
EnergyTransfer:Zone:FLOOR 2 EXAM HALL 5 2.28 0.05 01-JAN-13:30 267.55 06-JAN-09:00
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 5 0.03 0.00 01-JAN-13:30 196.20 02-JAN-05:30
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 5 2.24 0.00 01-JAN-00:10 267.55 06-JAN-09:00
EnergyTransfer:Zone:FLOOR 2 EXAM HALL 6 2.13 0.04 21-FEB-12:10 244.69 06-JAN-06:30
Heating:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 6 0.06 0.00 02-JAN-18:10 239.43 02-JAN-05:30
Cooling:EnergyTransfer:Zone:FLOOR 2 EXAM HALL 6 2.08 0.00 01-JAN-00:10 244.69 06-JAN-06:30
EnergyTransfer:Zone:FLOOR 2 JANITOR 1.64 0.00 31-OCT-08:10 373.90 09-JAN-07:20
Heating:EnergyTransfer:Zone:FLOOR 2 JANITOR 0.46 0.00 02-JAN-18:10 373.90 09-JAN-07:20
Cooling:EnergyTransfer:Zone:FLOOR 2 JANITOR 1.18 0.00 01-JAN-00:10 235.26 30-JUN-17:00
EnergyTransfer:Zone:FLOOR 2 LOUNGE 3.66 31.82 01-JAN-08:00 285.67 25-AUG-17:00
Heating:EnergyTransfer:Zone:FLOOR 2 LOUNGE 0.00 0.00 01-JAN-00:10 20.39 25-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 LOUNGE 3.66 31.82 01-JAN-08:00 285.67 25-AUG-17:00
EnergyTransfer:Zone:FLOOR 2 NURSE STATION 1 7.10 58.00 01-JAN-08:00 527.83 30-JUN-17:00
Heating:EnergyTransfer:Zone:FLOOR 2 NURSE STATION 1 0.00 0.00 01-JAN-00:10 70.44 07-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 NURSE STATION 1 7.10 58.00 01-JAN-08:00 527.83 30-JUN-17:00
EnergyTransfer:Zone:FLOOR 2 NURSE STATION 2 8.88 67.99 01-JAN-08:00 665.49 30-JUN-17:00
Heating:EnergyTransfer:Zone:FLOOR 2 NURSE STATION 2 0.00 0.00 01-JAN-00:10 84.09 07-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 NURSE STATION 2 8.88 67.99 01-JAN-08:00 665.49 30-JUN-17:00
EnergyTransfer:Zone:FLOOR 2 OFFICE 11.22 0.01 03-MAR-07:40 1950.30 28-JUN-07:40
Heating:EnergyTransfer:Zone:FLOOR 2 OFFICE 0.84 0.00 02-JAN-15:40 1410.72 09-JAN-07:40
Cooling:EnergyTransfer:Zone:FLOOR 2 OFFICE 10.38 0.00 01-JAN-00:10 1950.30 28-JUN-07:40
EnergyTransfer:Zone:FLOOR 2 OFFICE HALL 5.14 0.02 20-MAR-07:00 604.73 17-JAN-07:30
Heating:EnergyTransfer:Zone:FLOOR 2 OFFICE HALL 0.09 0.00 01-JAN-00:10 604.73 17-JAN-07:30
Cooling:EnergyTransfer:Zone:FLOOR 2 OFFICE HALL 5.05 0.00 02-JAN-05:20 549.76 25-AUG-07:50
EnergyTransfer:Zone:FLOOR 2 RECEPTION 46.98 0.27 11-DEC-03:50 4758.08 01-SEP-15:30
Heating:EnergyTransfer:Zone:FLOOR 2 RECEPTION 0.14 0.00 01-JAN-10:10 1138.72 09-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 2 RECEPTION 46.84 0.00 01-JAN-00:10 4758.08 01-SEP-15:30
EnergyTransfer:Zone:FLOOR 2 RECEPTION HALL 8.48 3.02 09-JAN-10:20 856.71 21-APR-17:00
Heating:EnergyTransfer:Zone:FLOOR 2 RECEPTION HALL 0.01 0.00 01-JAN-00:10 386.53 02-JAN-07:30
Cooling:EnergyTransfer:Zone:FLOOR 2 RECEPTION HALL 8.48 0.00 02-JAN-07:10 856.71 21-APR-17:00
EnergyTransfer:Zone:FLOOR 2 RECEPTION TOILET 5.73 0.01 27-FEB-10:40 351.62 02-DEC-17:10
Heating:EnergyTransfer:Zone:FLOOR 2 RECEPTION TOILET 0.04 0.00 01-JAN-00:10 248.43 02-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 RECEPTION TOILET 5.69 0.00 02-JAN-05:30 351.62 02-DEC-17:10
EnergyTransfer:Zone:FLOOR 2 SCHEDULING 1 7.91 75.53 02-JAN-07:30 615.05 25-AUG-06:20
Heating:EnergyTransfer:Zone:FLOOR 2 SCHEDULING 1 0.00 0.00 01-JAN-00:10 82.10 02-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 SCHEDULING 1 7.91 71.26 02-JAN-07:20 615.05 25-AUG-06:20
EnergyTransfer:Zone:FLOOR 2 SCHEDULING 2 8.33 70.06 02-JAN-07:30 669.57 30-JUN-17:00
Heating:EnergyTransfer:Zone:FLOOR 2 SCHEDULING 2 0.00 0.00 01-JAN-00:10 88.83 07-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 SCHEDULING 2 8.33 70.06 02-JAN-07:30 669.57 30-JUN-17:00
EnergyTransfer:Zone:FLOOR 2 STORAGE 1 0.94 0.01 03-JAN-10:30 103.81 17-JAN-07:50
Heating:EnergyTransfer:Zone:FLOOR 2 STORAGE 1 0.05 0.00 01-JAN-00:10 103.81 17-JAN-07:50
Cooling:EnergyTransfer:Zone:FLOOR 2 STORAGE 1 0.89 0.00 02-JAN-05:20 64.85 05-JAN-12:40
EnergyTransfer:Zone:FLOOR 2 STORAGE 2 2.10 0.01 19-DEC-09:30 205.94 02-JAN-08:00
Heating:EnergyTransfer:Zone:FLOOR 2 STORAGE 2 0.05 0.00 01-JAN-00:10 205.94 02-JAN-08:00
Cooling:EnergyTransfer:Zone:FLOOR 2 STORAGE 2 2.05 0.00 01-JAN-03:00 113.37 16-MAR-05:20
EnergyTransfer:Zone:FLOOR 2 STORAGE 3 2.68 0.03 28-JAN-09:30 248.62 02-JAN-08:10
Heating:EnergyTransfer:Zone:FLOOR 2 STORAGE 3 0.04 0.00 01-JAN-13:30 248.62 02-JAN-08:10
Cooling:EnergyTransfer:Zone:FLOOR 2 STORAGE 3 2.63 0.00 01-JAN-00:10 153.41 02-DEC-06:20
EnergyTransfer:Zone:FLOOR 2 UTILITY 2.65 0.01 29-JAN-06:10 489.84 26-DEC-07:10
Heating:EnergyTransfer:Zone:FLOOR 2 UTILITY 0.63 0.00 02-JAN-18:10 489.84 26-DEC-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 UTILITY 2.02 0.00 01-JAN-00:10 379.95 15-JUN-08:40
EnergyTransfer:Zone:FLOOR 2 WORK 35.95 0.18 01-JAN-07:30 3499.29 30-JUN-06:10
Heating:EnergyTransfer:Zone:FLOOR 2 WORK 0.03 0.00 01-JAN-00:10 1442.56 02-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 WORK 35.92 0.00 01-JAN-07:30 3499.29 30-JUN-06:10
EnergyTransfer:Zone:FLOOR 2 WORK HALL 13.32 1.91 17-JAN-09:10 1264.08 30-JUN-17:00
Heating:EnergyTransfer:Zone:FLOOR 2 WORK HALL 0.01 0.00 01-JAN-00:10 709.97 02-JAN-08:00
Cooling:EnergyTransfer:Zone:FLOOR 2 WORK HALL 13.31 0.00 02-JAN-05:30 1264.08 30-JUN-17:00
EnergyTransfer:Zone:FLOOR 2 WORK TOILET 2.22 0.00 29-JAN-23:50 248.13 09-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 2 WORK TOILET 0.35 0.00 02-JAN-18:10 248.13 09-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 2 WORK TOILET 1.87 0.00 01-JAN-00:10 176.29 30-JUN-19:00
EnergyTransfer:Zone:FLOOR 2 X-RAY 130.89 1298.18 01-JAN-08:00 8660.01 20-OCT-15:30
Heating:EnergyTransfer:Zone:FLOOR 2 X-RAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 2 X-RAY 130.89 1298.18 01-JAN-08:00 8660.01 20-OCT-15:30
EnergyTransfer:Zone:FLOOR 3 DRESSING ROOM 0.90 0.02 06-MAR-06:40 106.07 30-JUN-15:00
Heating:EnergyTransfer:Zone:FLOOR 3 DRESSING ROOM 0.01 0.00 01-JAN-00:10 69.64 09-JAN-07:20
Cooling:EnergyTransfer:Zone:FLOOR 3 DRESSING ROOM 0.90 0.00 01-JAN-01:00 106.07 30-JUN-15:00
EnergyTransfer:Zone:FLOOR 3 ELEVATOR HALL 4.28 0.01 12-DEC-14:50 867.41 09-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 3 ELEVATOR HALL 0.74 0.00 02-JAN-18:10 867.41 09-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 ELEVATOR HALL 3.54 0.00 01-JAN-00:10 536.05 30-JUN-14:20
EnergyTransfer:Zone:FLOOR 3 HUMID 2.58 0.14 01-JAN-02:20 295.95 30-JUN-15:00
Heating:EnergyTransfer:Zone:FLOOR 3 HUMID 0.01 0.00 01-JAN-00:10 130.71 07-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 HUMID 2.57 0.00 01-JAN-02:20 295.95 30-JUN-15:00
EnergyTransfer:Zone:FLOOR 3 JANITOR 2.23 0.00 03-MAY-10:00 276.74 09-JAN-05:10
Heating:EnergyTransfer:Zone:FLOOR 3 JANITOR 1.43 0.00 02-JAN-18:10 276.74 09-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 3 JANITOR 0.80 0.00 01-JAN-00:10 104.95 30-JUN-17:00
EnergyTransfer:Zone:FLOOR 3 LOCKER 5.41 0.05 24-DEC-07:30 540.49 30-JUN-15:00
Heating:EnergyTransfer:Zone:FLOOR 3 LOCKER 0.01 0.00 01-JAN-08:20 127.58 07-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 LOCKER 5.40 0.00 01-JAN-00:10 540.49 30-JUN-15:00
EnergyTransfer:Zone:FLOOR 3 LOUNGE 35.76 0.00 24-DEC-08:00 3379.36 30-JUN-14:20
Heating:EnergyTransfer:Zone:FLOOR 3 LOUNGE 0.05 0.00 01-JAN-08:20 701.73 09-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 3 LOUNGE 35.71 0.00 01-JAN-00:10 3379.36 30-JUN-14:20
EnergyTransfer:Zone:FLOOR 3 LOUNGE TOILET 6.71 0.00 09-APR-23:50 772.03 09-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 3 LOUNGE TOILET 1.17 0.00 02-JAN-18:10 772.03 09-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 LOUNGE TOILET 5.54 0.00 01-JAN-00:10 522.85 29-JUN-15:20
EnergyTransfer:Zone:FLOOR 3 MECHANICAL 94.80 24.45 01-JAN-04:10 6112.11 17-FEB-06:10
Heating:EnergyTransfer:Zone:FLOOR 3 MECHANICAL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FLOOR 3 MECHANICAL 94.80 24.45 01-JAN-04:10 6112.11 17-FEB-06:10
EnergyTransfer:Zone:FLOOR 3 MECHANICAL HALL 4.69 0.02 21-JAN-10:30 679.71 09-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 3 MECHANICAL HALL 0.18 0.00 01-JAN-09:30 679.71 09-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 MECHANICAL HALL 4.51 0.00 01-JAN-00:10 642.93 28-JUN-07:10
EnergyTransfer:Zone:FLOOR 3 OFFICE 58.91 0.11 27-FEB-00:30 7052.53 30-JUN-14:40
Heating:EnergyTransfer:Zone:FLOOR 3 OFFICE 1.74 0.00 02-JAN-11:00 4839.99 09-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 3 OFFICE 57.17 0.00 01-JAN-00:10 7052.53 30-JUN-14:40
EnergyTransfer:Zone:FLOOR 3 OFFICE HALL 10.95 0.01 06-MAR-04:00 2002.59 26-DEC-07:10
Heating:EnergyTransfer:Zone:FLOOR 3 OFFICE HALL 0.80 0.00 01-JAN-14:40 2002.59 26-DEC-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 OFFICE HALL 10.15 0.00 01-JAN-00:10 1449.47 30-JUN-14:40
EnergyTransfer:Zone:FLOOR 3 OFFICE TOILET 1.91 0.00 10-APR-14:00 259.16 26-DEC-07:10
Heating:EnergyTransfer:Zone:FLOOR 3 OFFICE TOILET 0.67 0.00 02-JAN-18:10 259.16 26-DEC-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 OFFICE TOILET 1.25 0.00 01-JAN-00:10 146.78 30-JUN-19:00
EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 1 76.57 0.02 03-FEB-01:20 7847.76 01-SEP-13:20
Heating:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 1 2.83 0.00 01-JAN-09:20 3612.74 25-FEB-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 1 73.74 0.00 01-JAN-00:10 7847.76 01-SEP-13:20
EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 2 35.32 0.04 24-DEC-04:30 2355.41 30-JUN-15:10
Heating:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 2 0.26 0.00 01-JAN-09:20 1017.78 14-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY 2 35.06 0.00 01-JAN-00:10 2355.41 30-JUN-15:10
EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 3.67 0.01 01-JAN-12:00 233.22 30-JUN-17:10
Heating:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 0.06 0.00 01-JAN-15:50 204.05 26-DEC-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 PHYSICAL THERAPY TOILET 3.60 0.00 01-JAN-00:10 233.22 30-JUN-17:10
EnergyTransfer:Zone:FLOOR 3 STORAGE 1 3.10 0.00 25-MAR-12:50 304.31 09-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 3 STORAGE 1 0.26 0.00 02-JAN-18:10 304.31 09-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 STORAGE 1 2.84 0.00 01-JAN-00:10 233.23 30-JUN-17:10
EnergyTransfer:Zone:FLOOR 3 STORAGE 2 1.56 0.00 19-DEC-04:50 247.53 09-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 3 STORAGE 2 0.18 0.00 02-JAN-18:10 247.53 09-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 STORAGE 2 1.37 0.00 01-JAN-00:10 128.12 30-JUN-15:00
EnergyTransfer:Zone:FLOOR 3 TREATMENT 30.93 0.00 24-DEC-21:00 1926.50 30-JUN-16:50
Heating:EnergyTransfer:Zone:FLOOR 3 TREATMENT 0.15 0.00 01-JAN-09:00 752.85 07-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 TREATMENT 30.78 0.00 01-JAN-00:10 1926.50 30-JUN-16:50
EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 1 50.42 0.16 09-DEC-11:30 6427.09 01-SEP-15:30
Heating:EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 1 2.50 0.00 01-JAN-09:50 4423.78 09-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 1 47.92 0.00 01-JAN-00:10 6427.09 01-SEP-15:30
EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 2 26.27 0.06 21-FEB-06:50 3512.09 01-SEP-15:00
Heating:EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 2 2.55 0.00 01-JAN-10:50 3034.47 26-DEC-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 UNDEVELOPED 2 23.72 0.00 01-JAN-00:10 3512.09 01-SEP-15:00
EnergyTransfer:Zone:FLOOR 3 UTILITY 3.42 0.00 21-MAR-08:20 415.88 09-JAN-07:10
Heating:EnergyTransfer:Zone:FLOOR 3 UTILITY 0.47 0.00 02-JAN-18:10 415.88 09-JAN-07:10
Cooling:EnergyTransfer:Zone:FLOOR 3 UTILITY 2.95 0.00 01-JAN-00:10 197.79 30-JUN-15:10
EnergyTransfer:Zone:FLOOR 3 WORK 14.98 0.02 23-NOV-18:30 2653.58 28-JUN-07:40
Heating:EnergyTransfer:Zone:FLOOR 3 WORK 1.28 0.00 02-JAN-09:30 1531.03 09-JAN-05:10
Cooling:EnergyTransfer:Zone:FLOOR 3 WORK 13.70 0.00 01-JAN-00:10 2653.58 28-JUN-07:40
EnergyTransfer:Zone:NE STAIR 14.88 0.04 27-OCT-04:10 2011.31 09-JAN-05:10
Heating:EnergyTransfer:Zone:NE STAIR 12.69 0.00 02-JAN-18:10 2011.31 09-JAN-05:10
Cooling:EnergyTransfer:Zone:NE STAIR 2.18 0.00 01-JAN-00:10 912.03 21-JUL-13:30
EnergyTransfer:Zone:NW ELEVATOR 7.63 0.01 01-JUN-09:10 1307.80 09-JAN-05:10
Heating:EnergyTransfer:Zone:NW ELEVATOR 6.25 0.00 02-JAN-18:10 1307.80 09-JAN-05:10
Cooling:EnergyTransfer:Zone:NW ELEVATOR 1.38 0.00 01-JAN-00:10 721.02 11-AUG-17:00
EnergyTransfer:Zone:NW STAIR 15.73 0.02 30-SEP-09:30 2071.55 09-JAN-05:10
Heating:EnergyTransfer:Zone:NW STAIR 13.26 0.00 02-JAN-18:10 2071.55 09-JAN-05:10
Cooling:EnergyTransfer:Zone:NW STAIR 2.47 0.00 01-JAN-00:10 1048.85 29-JUN-16:00
EnergyTransfer:Zone:SW STAIR 5.30 0.00 02-MAY-10:20 997.20 09-JAN-05:10
Heating:EnergyTransfer:Zone:SW STAIR 3.86 0.00 02-JAN-18:10 997.20 09-JAN-05:10
Cooling:EnergyTransfer:Zone:SW STAIR 1.45 0.00 01-JAN-00:10 745.94 01-SEP-15:50
EnergyTransfer:Plant 1113.37 1261.25 20-OCT-03:20 133884.93 14-FEB-11:10
WaterSystems:EnergyTransfer 105.77 0.00 01-JAN-00:10 12900.15 24-FEB-11:10
WaterUse:WaterSystems:EnergyTransfer 105.77 0.00 01-JAN-00:10 12900.15 24-FEB-11:10
EnergyTransfer:HVAC 2626.69 3549.17 27-OCT-18:10 381641.51 30-JUN-16:00
HeatingCoils:EnergyTransfer 1279.92 2720.90 09-AUG-17:20 270597.69 25-FEB-07:10
PlantLoopHeatingDemand:HVAC 1026.90 2665.95 08-SEP-17:20 147605.14 09-JAN-06:10
HeatingCoils:PlantLoopHeatingDemand 1026.90 2665.95 08-SEP-17:20 147605.14 09-JAN-06:10
CoolingCoils:EnergyTransfer 1346.77 0.00 01-JAN-00:10 373482.08 30-JUN-16:00
Boilers:EnergyTransfer 1007.59 976.54 25-OCT-20:40 121008.89 02-JAN-06:40



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
FLOOR 1 ANESTHESIA 0.000 0.000 0.028 -8.531 0.000 0.000 2.191 2.063 4.069 2.073 0.000 0.004 0.000 0.000 -1.225 0.000 -0.165 -0.507
FLOOR 1 CAFE 0.000 0.000 0.002 -41.895 0.000 0.000 39.020 2.292 7.908 7.587 0.000 0.005 0.000 0.000 -5.491 0.000 -0.405 -9.022
FLOOR 1 CLEAN 0.000 0.000 0.000 -12.941 0.000 0.000 2.515 2.407 4.747 0.000 0.000 0.000 3.272 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 CLEAN WORK 0.000 0.000 0.000 -14.291 0.000 0.000 3.318 3.152 6.216 0.000 0.000 0.000 1.605 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 DICTATION 0.000 0.000 0.000 -3.230 0.000 0.000 0.508 1.095 2.610 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.983
FLOOR 1 DRESSING ROOM 0.000 0.000 0.726 -0.564 0.000 0.000 0.194 0.391 0.932 0.628 0.000 0.003 0.000 0.000 -1.160 0.000 -0.166 -0.984
FLOOR 1 HUMID 0.000 0.000 0.000 -1.774 0.000 0.000 0.216 0.469 1.119 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.031
FLOOR 1 IT ROOM 0.000 0.000 0.000 -1.748 0.000 0.000 0.468 0.973 2.320 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -2.015
FLOOR 1 LOBBY 0.000 0.000 0.036 -23.830 0.000 0.000 5.884 6.772 12.887 5.977 0.000 0.005 0.000 0.000 -5.824 0.000 -0.440 -1.467
FLOOR 1 LOCKER ROOM 0.000 0.000 0.000 -31.209 0.000 0.000 9.224 5.313 37.292 1.096 0.000 0.005 0.000 0.000 -3.909 0.000 -0.453 -17.360
FLOOR 1 LOUNGE 0.000 0.000 0.000 -17.242 0.000 0.000 5.032 2.898 20.341 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -11.029
FLOOR 1 MRI CONTROL ROOM 0.000 0.000 0.000 -24.937 0.000 0.000 3.072 2.155 31.643 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -11.932
FLOOR 1 MRI ROOM 0.000 0.000 0.000 -71.542 0.000 0.000 7.956 4.402 82.876 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -23.691
FLOOR 1 NOURISHMENT 0.000 0.000 0.000 -9.512 0.000 0.000 3.387 2.905 6.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -3.637
FLOOR 1 NURSE STATION 0.000 0.000 0.000 -11.624 0.000 0.000 4.883 4.166 9.833 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -7.258
FLOOR 1 OFFICE 0.000 0.000 0.000 -10.779 0.000 0.000 1.937 4.198 10.007 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -5.362
FLOOR 1 OPERATING ROOM 1 0.000 0.000 0.001 -83.639 0.000 0.000 10.149 14.184 65.258 7.434 0.000 0.029 0.000 0.000 -4.775 0.000 -0.761 -7.881
FLOOR 1 OPERATING ROOM 2 0.000 0.000 0.000 -93.778 0.000 0.000 10.719 14.801 68.095 4.964 0.000 0.020 0.000 0.000 -3.831 0.000 -0.420 -0.570
FLOOR 1 OPERATING ROOM 3 0.000 0.000 0.057 -104.395 0.000 0.000 10.696 14.677 67.528 0.000 0.000 0.000 11.436 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 PACU 0.000 0.000 0.000 -11.168 0.000 0.000 2.175 1.842 6.102 0.000 0.000 0.000 1.048 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 PRE-OP ROOM 1 0.000 0.000 0.003 -12.357 0.000 0.000 1.962 1.753 7.120 0.000 0.000 0.002 1.588 0.000 0.000 0.000 -0.072 -0.000
FLOOR 1 PRE-OP ROOM 2 0.000 0.000 0.001 -28.851 0.000 0.000 3.442 3.136 12.734 0.000 0.000 0.000 9.538 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 PROCEDURE ROOM 0.000 0.000 0.030 -25.371 0.000 0.000 5.933 5.444 16.103 1.346 0.000 0.011 0.293 0.000 -3.449 0.000 -0.339 -0.000
FLOOR 1 RECEPTION 0.000 0.000 0.000 -24.726 0.000 0.000 14.225 5.833 10.546 2.355 0.000 0.003 0.000 0.000 -2.202 0.000 -0.267 -5.767
FLOOR 1 RECOVERY ROOM 0.000 0.000 0.122 -41.850 0.000 0.000 10.960 9.209 30.511 8.382 0.000 0.022 0.000 0.000 -4.818 0.000 -0.821 -11.718
FLOOR 1 SCHEDULING 0.000 0.000 0.005 -2.129 0.000 0.000 0.488 1.034 2.465 0.407 0.000 0.002 0.000 0.000 -0.478 0.000 -0.139 -1.655
FLOOR 1 SOIL 0.000 0.000 0.000 -11.604 0.000 0.000 2.531 2.407 4.747 0.000 0.000 0.000 1.919 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 SOIL HOLD 0.000 0.000 0.000 -4.642 0.000 0.000 1.185 1.070 2.110 0.000 0.000 0.000 0.278 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 SOIL WORK 0.000 0.000 0.001 -14.166 0.000 0.000 3.633 3.438 6.781 0.000 0.000 0.000 0.313 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 STEP DOWN 0.000 0.000 0.280 -20.771 0.000 0.000 6.067 5.116 16.951 5.573 0.000 0.017 0.000 0.000 -3.558 0.000 -0.675 -9.000
FLOOR 2 CONFERENCE 0.000 0.000 0.586 -17.430 0.000 0.000 12.480 1.532 6.326 7.404 0.000 0.018 0.000 0.000 -5.026 0.000 -1.092 -4.798
FLOOR 2 DICTATION 0.000 0.000 0.001 -1.391 0.000 0.000 0.284 0.608 1.450 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.952
FLOOR 2 EXAM 1 0.000 0.000 1.037 -17.645 0.000 0.000 7.232 5.364 7.459 5.948 0.000 0.023 0.000 0.000 -5.073 0.000 -1.111 -3.233
FLOOR 2 EXAM 2 0.000 0.000 0.182 -35.063 0.000 0.000 10.960 8.045 11.188 3.436 0.000 0.013 3.812 0.000 -2.100 0.000 -0.473 -0.000
FLOOR 2 EXAM 3 0.000 0.000 0.262 -44.226 0.000 0.000 14.623 10.727 14.917 5.509 0.000 0.017 2.136 0.000 -3.335 0.000 -0.630 -0.000
FLOOR 2 EXAM 4 0.000 0.000 0.114 -5.155 0.000 0.000 1.677 1.252 1.740 2.029 0.000 0.004 0.000 0.000 -1.264 0.000 -0.187 -0.211
FLOOR 2 EXAM 5 0.000 0.000 0.198 -22.341 0.000 0.000 7.047 5.215 7.251 4.020 0.000 0.015 2.847 0.000 -3.592 0.000 -0.661 -0.000
FLOOR 2 EXAM 6 0.000 0.000 0.241 -12.041 0.000 0.000 4.574 3.352 4.662 0.991 0.000 0.010 1.278 0.000 -2.675 0.000 -0.393 -0.000
FLOOR 2 EXAM 7 0.000 0.000 0.270 -47.923 0.000 0.000 16.103 11.800 16.409 1.337 0.000 0.017 6.223 0.000 -3.607 0.000 -0.629 -0.000
FLOOR 2 EXAM 8 0.000 0.000 0.186 -16.493 0.000 0.000 5.477 4.023 5.594 1.301 0.000 0.012 3.997 0.000 -3.622 0.000 -0.474 -0.000
FLOOR 2 EXAM 9 0.000 0.000 0.121 -26.526 0.000 0.000 8.035 5.900 8.204 0.642 0.000 0.008 5.756 0.000 -1.825 0.000 -0.316 -0.000
FLOOR 2 LOUNGE 0.000 0.000 0.000 -3.659 0.000 0.000 1.124 0.644 4.520 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -2.629
FLOOR 2 NURSE STATION 1 0.000 0.000 0.000 -7.100 0.000 0.000 2.817 2.394 5.651 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -3.762
FLOOR 2 NURSE STATION 2 0.000 0.000 0.000 -8.878 0.000 0.000 3.374 2.873 6.781 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -4.152
FLOOR 2 OFFICE 0.000 0.000 0.840 -10.381 0.000 0.000 2.319 1.842 11.602 5.963 0.000 0.014 0.000 0.000 -5.570 0.000 -1.115 -5.514
FLOOR 2 RECEPTION 0.000 0.000 0.143 -46.838 0.000 0.000 28.055 5.789 20.387 12.505 0.000 0.018 0.000 0.000 -10.156 0.000 -1.383 -8.520
FLOOR 2 SCHEDULING 1 0.000 0.000 0.000 -7.914 0.000 0.000 1.301 2.816 6.713 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -2.916
FLOOR 2 SCHEDULING 2 0.000 0.000 0.000 -8.328 0.000 0.000 1.374 2.972 7.086 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -3.104
FLOOR 2 WORK 0.000 0.000 0.031 -35.923 0.000 0.000 6.841 14.688 28.923 1.073 0.000 0.009 0.000 0.000 -3.951 0.000 -0.752 -10.940
FLOOR 2 X-RAY 0.000 0.000 0.000 -130.890 0.000 0.000 16.087 9.003 169.518 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -63.718
FLOOR 3 DRESSING ROOM 0.000 0.000 0.006 -0.897 0.000 0.000 0.171 0.365 0.870 0.000 0.000 0.002 0.000 0.000 0.000 0.000 -0.141 -0.377
FLOOR 3 HUMID 0.000 0.000 0.008 -2.572 0.000 0.000 0.439 0.939 2.238 0.000 0.000 0.005 0.000 0.000 0.000 0.000 -0.366 -0.690
FLOOR 3 LOCKER 0.000 0.000 0.009 -5.403 0.000 0.000 1.694 0.966 6.780 0.000 0.000 0.005 0.000 0.000 0.000 0.000 -0.408 -3.644
FLOOR 3 LOUNGE 0.000 0.000 0.050 -35.706 0.000 0.000 10.676 4.149 42.886 1.223 0.000 0.000 0.000 0.000 -3.811 0.000 -0.022 -19.446
FLOOR 3 OFFICE 0.000 0.000 1.744 -57.167 0.000 0.000 12.458 20.760 62.901 4.107 0.000 0.001 0.000 0.000 -13.204 0.000 -0.055 -31.545
FLOOR 3 PHYSICAL THERAPY 1 0.000 0.000 2.830 -73.741 0.000 0.000 25.949 12.590 36.738 24.393 0.000 0.003 0.000 0.000 -15.551 0.000 -0.152 -13.059
FLOOR 3 PHYSICAL THERAPY 2 0.000 0.000 0.262 -35.056 0.000 0.000 11.950 5.733 16.730 0.000 0.000 0.048 2.180 0.000 0.000 0.000 -1.848 -0.000
FLOOR 3 TREATMENT 0.000 0.000 0.148 -30.781 0.000 0.000 9.514 9.092 9.862 0.000 0.000 0.036 3.630 0.000 0.000 0.000 -1.502 -0.000
FLOOR 3 WORK 0.000 0.000 1.279 -13.704 0.000 0.000 2.363 4.989 11.892 5.904 0.000 0.001 0.000 0.000 -5.570 0.000 -0.085 -7.069
FLOOR 1 BIO HAZ 0.000 0.000 0.334 -0.253 0.000 0.000 0.000 0.195 0.106 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.381
FLOOR 1 ELECTRICAL ROOM 0.000 0.000 0.000 -5.059 0.000 0.000 0.000 1.872 9.229 0.000 0.000 0.002 0.000 0.000 0.000 0.000 -0.141 -5.903
FLOOR 1 ELEVATOR PUMP ROOM 0.000 0.000 0.010 -38.210 0.000 0.000 0.000 1.738 63.927 0.000 0.000 0.005 0.000 0.000 0.000 0.000 -0.408 -27.062
FLOOR 1 IT HALL 0.000 0.000 0.000 -1.581 0.000 0.000 0.000 0.895 1.056 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.370
FLOOR 1 LOBBY HALL 0.000 0.000 0.000 -5.885 0.000 0.000 0.000 1.534 1.810 0.000 0.000 0.000 2.542 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 LOBBY TOILET 0.000 0.000 0.060 -5.246 0.000 0.000 0.000 0.306 0.407 0.000 0.000 0.003 4.580 0.000 0.000 0.000 -0.110 -0.000
FLOOR 1 LOCKER ROOM HALL 0.000 0.000 0.000 -6.028 0.000 0.000 0.000 3.169 3.741 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.882
FLOOR 1 MED GAS 0.000 0.000 3.871 -0.263 0.000 0.000 0.000 0.195 0.106 0.000 0.000 0.005 0.000 0.000 0.000 0.000 -0.196 -3.718
FLOOR 1 MRI HALL 0.000 0.000 0.000 -2.503 0.000 0.000 0.000 0.939 1.109 0.000 0.000 0.000 0.455 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 MRI TOILET 0.000 0.000 0.255 -1.418 0.000 0.000 0.000 0.306 0.407 0.000 0.000 0.003 0.557 0.000 0.000 0.000 -0.110 -0.000
FLOOR 1 NURSE HALL 0.000 0.000 0.000 -6.760 0.000 0.000 0.000 3.169 3.741 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.150
FLOOR 1 NURSE JANITOR 0.000 0.000 0.000 -0.992 0.000 0.000 0.000 0.188 0.102 0.000 0.000 0.000 0.702 0.000 0.000 0.000 0.000 0.000
FLOOR 1 NURSE TOILET 0.000 0.000 0.001 -2.610 0.000 0.000 0.000 0.306 0.407 0.000 0.000 0.000 1.896 0.000 0.000 0.000 0.000 0.000
FLOOR 1 PRE-OP HALL 0.000 0.000 0.000 -6.433 0.000 0.000 0.000 3.374 3.982 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.923
FLOOR 1 PRE-OP TOILET 0.000 0.000 1.880 -1.062 0.000 0.000 0.000 0.306 0.407 0.000 0.000 0.003 0.000 0.000 0.000 0.000 -0.107 -1.427
FLOOR 1 RECEPTION HALL 0.000 0.000 0.000 -1.758 0.000 0.000 0.000 0.818 0.965 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.025
FLOOR 1 SCRUB 0.000 0.000 0.025 -1.000 0.000 0.000 0.000 0.537 0.634 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.195
FLOOR 1 STERILE HALL 0.000 0.000 0.046 -6.083 0.000 0.000 0.000 3.936 4.646 2.033 0.000 0.000 0.000 0.000 -1.323 0.000 0.000 -3.254
FLOOR 1 STERILE STORAGE 0.000 0.000 0.000 -4.415 0.000 0.000 0.000 1.378 0.748 0.000 0.000 0.000 2.289 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 STORAGE 0.000 0.000 20.657 -3.432 0.000 0.000 0.000 3.202 1.739 2.023 0.000 0.011 0.000 0.000 -5.013 0.000 -0.462 -18.725
FLOOR 1 SUB-STERILE 0.000 0.000 0.833 -2.091 0.000 0.000 0.000 1.252 1.478 2.028 0.000 0.004 0.000 0.000 -1.798 0.000 -0.263 -1.444
FLOOR 1 UTILITY HALL 0.000 0.000 4.047 -1.556 0.000 0.000 0.000 1.636 1.931 0.000 0.000 0.003 0.000 0.000 0.000 0.000 -0.162 -5.898
FLOOR 1 UTILITY JANITOR 0.000 0.000 0.020 -0.483 0.000 0.000 0.000 0.146 0.079 0.000 0.000 0.000 0.237 0.000 0.000 0.000 0.000 -0.000
FLOOR 1 UTILITY ROOM 0.000 0.000 2.443 -2.343 0.000 0.000 0.000 1.253 0.680 1.519 0.000 0.006 0.000 0.000 -1.332 0.000 -0.335 -1.892
FLOOR 1 VESTIBULE 0.000 0.000 5.078 -0.644 0.000 0.000 0.000 0.460 0.543 0.000 0.000 0.668 9.568 0.000 0.000 0.000 -15.673 -0.000
FLOOR 2 CONFERENCE TOILET 0.000 0.000 0.041 -2.669 0.000 0.000 0.000 0.363 0.483 0.000 0.000 0.000 1.782 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 EXAM HALL 1 0.000 0.000 0.130 -1.868 0.000 0.000 0.000 1.150 1.358 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.769
FLOOR 2 EXAM HALL 2 0.000 0.000 0.054 -1.884 0.000 0.000 0.000 1.150 1.358 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.677
FLOOR 2 EXAM HALL 3 0.000 0.000 0.069 -1.832 0.000 0.000 0.000 1.150 1.358 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.745
FLOOR 2 EXAM HALL 4 0.000 0.000 0.043 -1.990 0.000 0.000 0.000 1.265 1.493 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.811
FLOOR 2 EXAM HALL 5 0.000 0.000 0.033 -2.245 0.000 0.000 0.000 1.265 1.493 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.546
FLOOR 2 EXAM HALL 6 0.000 0.000 0.057 -2.077 0.000 0.000 0.000 1.265 1.493 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.738
FLOOR 2 JANITOR 0.000 0.000 0.456 -1.185 0.000 0.000 0.000 0.219 0.119 0.000 0.000 0.006 0.829 0.000 0.000 0.000 -0.445 -0.000
FLOOR 2 OFFICE HALL 0.000 0.000 0.089 -5.053 0.000 0.000 0.000 2.837 3.349 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.222
FLOOR 2 RECEPTION HALL 0.000 0.000 0.006 -8.476 0.000 0.000 0.000 3.604 4.254 0.000 0.000 0.000 0.612 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 RECEPTION TOILET 0.000 0.000 0.037 -5.691 0.000 0.000 0.000 0.715 0.950 0.000 0.000 0.000 3.989 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 STORAGE 1 0.000 0.000 0.045 -0.890 0.000 0.000 0.000 0.195 0.106 0.000 0.000 0.000 0.544 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 STORAGE 2 0.000 0.000 0.047 -2.048 0.000 0.000 0.000 0.418 0.227 0.000 0.000 0.000 1.357 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 STORAGE 3 0.000 0.000 0.042 -2.634 0.000 0.000 0.000 0.501 0.272 0.000 0.000 0.000 1.818 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 UTILITY 0.000 0.000 0.632 -2.019 0.000 0.000 0.000 0.439 0.238 1.493 0.000 0.004 0.842 0.000 -1.383 0.000 -0.245 -0.000
FLOOR 2 WORK HALL 0.000 0.000 0.015 -13.308 0.000 0.000 0.000 5.329 6.290 0.000 0.000 0.000 1.674 0.000 0.000 0.000 0.000 -0.000
FLOOR 2 WORK TOILET 0.000 0.000 0.348 -1.867 0.000 0.000 0.000 0.306 0.407 0.000 0.000 0.004 0.960 0.000 0.000 0.000 -0.159 -0.000
FLOOR 3 ELEVATOR HALL 0.000 0.000 0.743 -3.540 0.000 0.000 0.000 2.364 2.790 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.001 -2.357
FLOOR 3 JANITOR 0.000 0.000 1.425 -0.800 0.000 0.000 0.000 0.219 0.119 0.000 0.000 0.002 0.000 0.000 0.000 0.000 -0.095 -0.870
FLOOR 3 LOUNGE TOILET 0.000 0.000 1.174 -5.541 0.000 0.000 0.000 1.089 1.448 0.938 0.000 0.000 3.621 0.000 -2.710 0.000 -0.021 -0.000
FLOOR 3 MECHANICAL 0.000 0.000 0.000 -94.795 0.000 0.000 0.000 6.685 32.962 3.859 0.000 0.000 55.625 0.000 -4.275 0.000 -0.062 0.000
FLOOR 3 MECHANICAL HALL 0.000 0.000 0.182 -4.512 0.000 0.000 0.000 1.917 2.263 0.000 0.000 0.012 1.150 0.000 0.000 0.000 -1.012 -0.000
FLOOR 3 OFFICE HALL 0.000 0.000 0.801 -10.149 0.000 0.000 0.000 5.329 6.290 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.001 -2.269
FLOOR 3 OFFICE TOILET 0.000 0.000 0.666 -1.248 0.000 0.000 0.000 0.306 0.407 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.017 -0.115
FLOOR 3 PHYSICAL THERAPY TOILET 0.000 0.000 0.064 -3.601 0.000 0.000 0.000 0.477 0.634 0.000 0.000 0.006 2.688 0.000 0.000 0.000 -0.267 -0.000
FLOOR 3 STORAGE 1 0.000 0.000 0.261 -2.843 0.000 0.000 0.000 0.376 0.204 0.000 0.000 0.008 2.333 0.000 0.000 0.000 -0.339 -0.000
FLOOR 3 STORAGE 2 0.000 0.000 0.185 -1.371 0.000 0.000 0.000 0.292 0.159 0.000 0.000 0.004 1.005 0.000 0.000 0.000 -0.274 -0.000
FLOOR 3 UNDEVELOPED 1 0.000 0.000 2.500 -47.924 0.000 0.000 0.000 7.894 46.989 19.854 0.000 0.001 0.000 0.000 -14.876 0.000 -0.068 -14.370
FLOOR 3 UNDEVELOPED 2 0.000 0.000 2.549 -23.718 0.000 0.000 0.000 4.009 23.867 10.424 0.000 0.001 0.000 0.000 -7.878 0.000 -0.079 -9.176
FLOOR 3 UTILITY 0.000 0.000 0.473 -2.947 0.000 0.000 0.000 0.752 0.408 0.000 0.000 0.013 1.993 0.000 0.000 0.000 -0.692 -0.000
NE STAIR 0.000 0.000 12.695 -2.182 0.000 0.000 0.000 1.073 1.267 2.896 0.000 0.013 0.000 0.000 -7.390 0.000 -1.026 -7.347
NW ELEVATOR 0.000 0.000 6.250 -1.379 0.000 0.000 0.000 0.895 1.056 0.000 0.000 0.010 0.000 0.000 0.000 0.000 -0.761 -6.071
NW STAIR 0.000 0.000 13.265 -2.467 0.000 0.000 0.000 1.227 1.448 2.445 0.000 0.015 0.000 0.000 -7.022 0.000 -1.176 -7.735
SW STAIR 0.000 0.000 3.858 -1.446 0.000 0.000 0.000 0.613 0.724 0.991 0.000 0.007 0.000 0.000 -0.633 0.000 -0.600 -3.514
Total Facility 0.000 0.000 100.636 -1902.580 0.000 0.000 400.968 380.820 1348.250 186.110 0.000 1.230 168.800 0.000 -186.285 0.000 -44.222 -453.728


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
FLOOR 1 ANESTHESIA 27-JAN-13:33 0.00 0.00 0.00 -648.81 0.00 0.00 142.66 136.08 213.96 674.20 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -518.09
FLOOR 1 CAFE 10-AUG-06:01 0.00 0.00 0.00 -4052.07 0.00 0.00 2751.97 151.20 415.84 0.00 0.00 0.00 736.58 0.00 -3.20 0.00 -0.33 0.00
FLOOR 1 CLEAN 15-DEC-17:57 0.00 0.00 0.00 -631.43 0.00 0.00 176.27 158.76 249.62 0.00 0.00 0.00 46.78 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 CLEAN WORK 27-JAN-15:04 0.00 0.00 0.00 -760.93 0.00 0.00 231.13 207.90 326.89 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -4.99
FLOOR 1 DICTATION 07-DEC-07:01 0.00 0.00 0.00 -492.51 0.00 0.00 41.26 72.09 137.27 0.00 0.00 0.00 241.88 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 DRESSING ROOM 21-JUL-14:05 0.00 0.00 0.00 -135.31 0.00 0.00 15.23 25.75 49.03 141.18 0.00 2.14 0.00 0.00 -0.00 0.00 0.00 -98.02
FLOOR 1 HUMID 27-OCT-06:01 0.00 0.00 0.00 -237.21 0.00 0.00 17.95 30.90 58.83 0.00 0.00 0.00 129.53 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 IT ROOM 15-DEC-15:02 0.00 0.00 0.00 -345.77 0.00 0.00 37.91 64.08 122.02 0.00 0.00 0.00 121.76 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 LOBBY 10-AUG-06:01 0.00 0.00 0.00 -3712.64 0.00 0.00 407.41 446.72 677.66 0.00 0.00 0.00 2198.84 0.00 -17.63 0.00 -0.36 0.00
FLOOR 1 LOCKER ROOM 13-SEP-05:01 0.00 0.00 0.00 -3340.23 0.00 0.00 352.24 233.64 1961.01 0.00 0.00 0.00 957.85 0.00 -150.75 0.00 -13.76 0.00
FLOOR 1 LOUNGE 10-AUG-06:01 0.00 0.00 0.00 -1797.43 0.00 0.00 353.71 191.16 1069.64 0.00 0.00 0.00 182.92 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 MRI CONTROL ROOM 21-JUL-05:01 0.00 0.00 0.00 -2231.73 0.00 0.00 108.76 94.75 1663.99 0.00 0.00 0.00 364.22 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 MRI ROOM 10-AUG-05:01 0.00 0.00 0.00 -5734.12 0.00 0.00 284.86 193.56 4358.06 0.00 0.00 0.00 897.64 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 NOURISHMENT 18-OCT-06:01 0.00 0.00 0.00 -980.46 0.00 0.00 238.43 191.65 360.56 0.00 0.00 0.00 189.82 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 NURSE STATION 18-OCT-06:01 0.00 0.00 0.00 -1337.67 0.00 0.00 341.92 274.83 517.07 0.00 0.00 0.00 203.85 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 OFFICE 10-AUG-06:01 0.00 0.00 0.00 -1524.33 0.00 0.00 158.20 276.35 526.22 0.00 0.00 0.00 563.56 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 1 14-SEP-05:01 0.00 0.00 0.00 -8314.42 0.00 0.00 360.41 623.76 3431.62 0.00 0.00 0.00 4129.12 0.00 -217.86 0.00 -12.63 0.00
FLOOR 1 OPERATING ROOM 2 14-SEP-05:01 0.00 0.00 0.00 -8684.73 0.00 0.00 375.97 650.88 3580.82 0.00 0.00 0.00 4248.13 0.00 -164.01 0.00 -7.06 0.00
FLOOR 1 OPERATING ROOM 3 27-JAN-15:04 0.00 0.00 0.00 -6953.14 0.00 0.00 738.42 968.18 3550.98 0.00 0.00 0.00 1695.56 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 PACU 27-JAN-15:04 0.00 0.00 0.00 -628.54 0.00 0.00 150.46 121.50 320.89 0.00 0.00 0.00 35.69 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 1 30-JUN-17:01 0.00 0.00 0.00 -1025.06 0.00 0.00 77.73 77.11 187.22 0.00 0.00 1.96 681.03 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 2 30-JUN-17:01 0.00 0.00 0.00 -1828.01 0.00 0.00 139.00 137.90 334.81 0.00 0.00 0.00 1216.29 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 PROCEDURE ROOM 21-JUL-17:01 0.00 0.00 0.00 -3623.33 0.00 0.00 234.69 239.40 423.40 186.62 0.00 3.59 2535.64 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 RECEPTION 10-AUG-06:01 0.00 0.00 0.00 -2543.61 0.00 0.00 1000.26 384.80 554.54 0.00 0.00 0.00 613.18 0.00 -8.96 0.00 -0.22 0.00
FLOOR 1 RECOVERY ROOM 27-JAN-13:33 0.00 0.00 0.00 -3429.17 0.00 0.00 733.56 607.50 1604.46 2709.83 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2226.18
FLOOR 1 SCHEDULING 27-OCT-14:02 0.00 0.00 0.00 -390.76 0.00 0.00 40.28 68.09 129.65 0.73 0.00 0.00 152.27 0.00 -0.00 0.00 -0.25 0.00
FLOOR 1 SOIL 15-DEC-17:57 0.00 0.00 0.00 -614.01 0.00 0.00 178.58 158.76 249.62 0.00 0.00 0.00 27.05 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 SOIL HOLD 30-JUN-17:00 0.00 0.00 0.00 -221.60 0.00 0.00 84.51 70.56 110.94 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -44.41
FLOOR 1 SOIL WORK 27-JAN-15:04 0.00 0.00 0.00 -802.10 0.00 0.00 254.39 226.80 356.60 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -35.70
FLOOR 1 STEP DOWN 19-OCT-15:00 0.00 0.00 0.00 -1812.83 0.00 0.00 419.36 337.50 891.37 1173.99 0.00 0.01 0.00 0.00 -0.00 0.00 0.00 -1009.40
FLOOR 2 CONFERENCE 01-SEP-13:00 0.00 0.00 0.00 -2394.57 0.00 0.00 1174.24 0.00 332.67 1865.34 0.00 3.18 0.00 0.00 -0.00 0.00 0.00 -980.85
FLOOR 2 DICTATION 19-MAY-06:01 0.00 0.00 0.00 -225.69 0.00 0.00 23.96 40.05 76.26 0.00 0.00 0.00 85.42 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM 1 30-JUN-17:00 0.00 0.00 0.00 -2286.63 0.00 0.00 503.20 353.81 392.21 2105.49 0.00 26.49 0.00 0.00 -0.00 0.00 0.00 -1094.57
FLOOR 2 EXAM 2 30-JUN-06:03 0.00 0.00 0.00 -2676.09 0.00 0.00 841.87 530.71 588.32 52.47 0.00 5.81 656.90 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM 3 30-JUN-06:03 0.00 0.00 0.00 -3555.43 0.00 0.00 1122.49 707.62 784.42 86.57 0.00 7.79 846.53 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM 4 19-OCT-13:15 0.00 0.00 0.00 -546.66 0.00 0.00 117.09 82.56 91.52 571.94 0.00 0.00 0.00 0.00 -0.00 0.00 -0.58 -315.87
FLOOR 2 EXAM 5 15-JUN-09:00 0.00 0.00 0.00 -1643.58 0.00 0.00 489.21 343.98 381.32 1468.38 0.00 0.00 0.00 0.00 -0.00 0.00 -5.44 -1033.86
FLOOR 2 EXAM 6 30-JUN-06:03 0.00 0.00 0.00 -1054.30 0.00 0.00 350.78 221.13 245.13 56.77 0.00 4.79 175.69 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM 7 30-JUN-06:03 0.00 0.00 0.00 -3921.79 0.00 0.00 1234.74 778.38 862.87 78.57 0.00 7.76 959.47 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM 8 30-JUN-06:03 0.00 0.00 0.00 -1257.77 0.00 0.00 420.94 265.36 294.16 74.39 0.00 5.71 197.22 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM 9 30-JUN-06:03 0.00 0.00 0.00 -1969.56 0.00 0.00 617.37 389.19 431.43 37.48 0.00 3.85 490.24 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 LOUNGE 02-FEB-07:01 0.00 0.00 0.00 -556.74 0.00 0.00 81.20 42.48 237.70 0.00 0.00 0.00 195.36 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 1 24-FEB-07:01 0.00 0.00 0.00 -837.22 0.00 0.00 204.43 157.95 297.17 0.00 0.00 0.00 177.67 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 NURSE STATION 2 24-FEB-07:01 0.00 0.00 0.00 -1012.73 0.00 0.00 244.12 189.54 356.60 0.00 0.00 0.00 222.46 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 OFFICE 29-JUN-06:03 0.00 0.00 0.00 -2657.60 0.00 0.00 183.39 0.00 610.11 1269.38 0.00 1.19 593.53 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION 30-JUN-06:03 0.00 0.00 0.00 -5422.36 0.00 0.00 1942.68 636.79 1072.05 167.47 0.00 12.82 1590.56 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 1 24-FEB-07:01 0.00 0.00 0.00 -1238.90 0.00 0.00 110.69 185.38 352.99 0.00 0.00 0.00 589.85 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 SCHEDULING 2 24-FEB-07:01 0.00 0.00 0.00 -1359.11 0.00 0.00 117.34 195.68 372.60 0.00 0.00 0.00 673.50 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 WORK 30-JUN-06:03 0.00 0.00 0.00 -5091.11 0.00 0.00 553.44 966.95 1520.91 51.74 0.00 6.18 1991.88 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 X-RAY 06-JAN-07:01 0.00 0.00 0.00 -16333.38 0.00 0.00 1179.05 593.89 8914.22 0.00 0.00 0.00 5646.23 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 DRESSING ROOM 16-JUN-06:01 0.00 0.00 0.00 -106.36 0.00 0.00 14.53 24.03 45.76 0.00 0.00 0.00 23.16 0.00 -0.00 0.00 -1.12 0.00
FLOOR 3 HUMID 30-JUN-06:01 0.00 0.00 0.00 -434.03 0.00 0.00 36.67 61.79 117.66 0.00 0.00 3.33 214.57 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 LOCKER 30-JUN-06:03 0.00 0.00 0.00 -680.02 0.00 0.00 117.90 63.72 356.55 0.00 0.00 3.68 138.17 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 LOUNGE 30-JUN-06:03 0.00 0.00 0.00 -4035.38 0.00 0.00 745.70 277.05 2255.16 58.95 0.00 0.18 698.34 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 OFFICE 30-JUN-06:03 0.00 0.00 0.00 -8986.95 0.00 0.00 994.23 1519.92 3307.66 188.38 0.00 0.45 2976.31 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY 1 01-SEP-13:20 0.00 0.00 0.00 -7847.84 0.00 0.00 1817.06 830.47 1931.89 5967.69 0.00 0.59 0.00 0.00 -0.00 0.00 0.00 -2699.87
FLOOR 3 PHYSICAL THERAPY 2 17-FEB-06:02 0.00 0.00 0.00 -2516.62 0.00 0.00 526.15 252.12 879.75 0.00 0.00 0.00 858.59 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 TREATMENT 17-FEB-06:02 0.00 0.00 0.00 -1979.57 0.00 0.00 423.05 399.84 518.59 0.00 0.00 0.00 638.08 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 WORK 29-JUN-06:03 0.00 0.00 0.00 -3209.67 0.00 0.00 187.97 328.42 625.36 1266.71 0.00 0.09 801.12 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 BIO HAZ 30-JUN-17:01 0.00 0.00 0.00 -19.59 0.00 0.00 0.00 8.57 2.78 0.00 0.00 0.00 8.24 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 ELECTRICAL ROOM 25-AUG-06:01 0.00 0.00 0.00 -618.77 0.00 0.00 0.00 123.48 485.33 0.00 0.00 0.00 9.96 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 ELEVATOR PUMP ROOM 25-AUG-17:00 0.00 0.00 0.00 -3322.37 0.00 0.00 0.00 114.66 4835.28 0.00 0.00 2.82 0.00 0.00 -0.00 0.00 0.00 -1630.39
FLOOR 1 IT HALL 06-JAN-06:20 0.00 0.00 0.00 -98.39 0.00 0.00 0.00 39.34 55.52 0.00 0.00 0.00 3.53 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 LOBBY HALL 10-AUG-06:01 0.00 0.00 0.00 -779.88 0.00 0.00 0.00 101.16 95.18 0.00 0.00 0.00 583.54 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 LOBBY TOILET 25-AUG-17:01 0.00 0.00 0.00 -421.29 0.00 0.00 0.00 13.47 10.71 0.00 0.00 0.96 396.16 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM HALL 15-DEC-07:01 0.00 0.00 0.00 -1081.32 0.00 0.00 0.00 209.06 196.71 0.00 0.00 0.00 675.54 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 MED GAS 09-AUG-06:05 0.00 0.00 0.00 -71.79 0.00 0.00 0.00 12.86 5.57 0.00 0.00 0.00 54.22 0.00 -0.00 0.00 -0.85 0.00
FLOOR 1 MRI HALL 10-AUG-06:01 0.00 0.00 0.00 -432.78 0.00 0.00 0.00 61.96 58.30 0.00 0.00 0.00 312.52 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 MRI TOILET 09-AUG-06:05 0.00 0.00 0.00 -119.12 0.00 0.00 0.00 20.21 21.42 0.00 0.00 0.00 77.94 0.00 -0.00 0.00 -0.45 0.00
FLOOR 1 NURSE HALL 27-JAN-14:10 0.00 0.00 0.00 -673.62 0.00 0.00 0.00 209.06 196.71 0.00 0.00 0.00 267.85 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 NURSE JANITOR 15-DEC-07:01 0.00 0.00 0.00 -162.77 0.00 0.00 0.00 12.40 5.37 0.00 0.00 0.00 145.01 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 NURSE TOILET 27-OCT-17:01 0.00 0.00 0.00 -174.83 0.00 0.00 0.00 13.47 10.71 0.00 0.00 0.00 150.65 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP HALL 30-JUN-17:00 0.00 0.00 0.00 -447.25 0.00 0.00 0.00 222.55 209.40 0.00 0.00 0.00 15.29 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP TOILET 29-JUN-17:01 0.00 0.00 0.00 -150.91 0.00 0.00 0.00 13.47 10.71 0.00 0.00 2.63 124.10 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 RECEPTION HALL 10-NOV-07:01 0.00 0.00 0.00 -155.63 0.00 0.00 0.00 53.95 50.76 0.00 0.00 0.00 50.92 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 SCRUB 25-AUG-07:50 0.00 0.00 0.00 -79.44 0.00 0.00 0.00 35.41 33.31 0.00 0.00 0.00 10.72 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 STERILE HALL 01-SEP-14:20 0.00 0.00 0.00 -514.50 0.00 0.00 0.00 259.64 244.30 422.24 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -411.69
FLOOR 1 STERILE STORAGE 15-DEC-07:01 0.00 0.00 0.00 -780.36 0.00 0.00 0.00 90.92 39.35 0.00 0.00 0.00 650.09 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 STORAGE 30-JUN-17:01 0.00 0.00 0.00 -502.04 0.00 0.00 0.00 140.81 45.71 328.03 0.00 11.55 0.00 0.00 -0.00 0.00 0.00 -24.07
FLOOR 1 SUB-STERILE 14-JUL-06:02 0.00 0.00 0.00 -578.18 0.00 0.00 0.00 82.61 77.73 548.49 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -130.65
FLOOR 1 UTILITY HALL 21-JUL-16:03 0.00 0.00 0.00 -153.77 0.00 0.00 0.00 107.90 101.53 0.00 0.00 1.97 0.00 0.00 -0.00 0.00 0.00 -57.63
FLOOR 1 UTILITY JANITOR 25-AUG-15:20 0.00 0.00 0.00 -33.59 0.00 0.00 0.00 9.64 4.17 0.00 0.00 0.00 19.77 0.00 -0.00 0.00 0.00 0.00
FLOOR 1 UTILITY ROOM 29-JUL-09:30 0.00 0.00 0.00 -283.70 0.00 0.00 0.00 36.73 28.62 498.50 0.00 2.21 0.00 0.00 -0.00 0.00 0.00 -282.36
FLOOR 1 VESTIBULE 29-JUN-16:00 0.00 0.00 0.00 -442.29 0.00 0.00 0.00 30.35 28.55 0.00 0.00 1260.76 0.00 0.00 -0.00 0.00 0.00 -877.37
FLOOR 2 CONFERENCE TOILET 14-FEB-07:03 0.00 0.00 0.00 -215.82 0.00 0.00 0.00 23.95 25.38 0.00 0.00 0.00 166.49 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 1 01-SEP-17:00 0.00 0.00 0.00 -374.23 0.00 0.00 0.00 75.87 71.39 0.00 0.00 0.00 226.98 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 2 19-OCT-15:50 0.00 0.00 0.00 -260.95 0.00 0.00 0.00 75.87 71.39 0.00 0.00 0.00 113.70 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 3 19-OCT-16:00 0.00 0.00 0.00 -270.99 0.00 0.00 0.00 75.87 71.39 0.00 0.00 0.00 123.73 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 4 06-JAN-07:01 0.00 0.00 0.00 -257.04 0.00 0.00 0.00 83.46 78.53 0.00 0.00 0.00 95.06 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 5 06-JAN-07:01 0.00 0.00 0.00 -281.30 0.00 0.00 0.00 83.46 78.53 0.00 0.00 0.00 119.32 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 EXAM HALL 6 06-JAN-06:11 0.00 0.00 0.00 -251.22 0.00 0.00 0.00 55.64 78.53 0.00 0.00 0.00 117.05 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 JANITOR 30-JUN-06:01 0.00 0.00 0.00 -357.72 0.00 0.00 0.00 14.46 6.26 0.00 0.00 4.07 332.93 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 OFFICE HALL 14-JUL-06:02 0.00 0.00 0.00 -1262.99 0.00 0.00 0.00 187.15 176.09 0.00 0.00 0.00 899.75 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION HALL 30-JUN-06:01 0.00 0.00 0.00 -1752.04 0.00 0.00 0.00 237.73 223.68 0.00 0.00 0.00 1290.64 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 RECEPTION TOILET 14-FEB-07:03 0.00 0.00 0.00 -453.35 0.00 0.00 0.00 47.15 49.97 0.00 0.00 0.00 356.22 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 1 26-JAN-06:01 0.00 0.00 0.00 -83.78 0.00 0.00 0.00 8.57 5.57 0.00 0.00 0.00 69.64 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 2 26-JAN-06:01 0.00 0.00 0.00 -178.18 0.00 0.00 0.00 18.37 11.93 0.00 0.00 0.00 147.89 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 STORAGE 3 26-JAN-06:01 0.00 0.00 0.00 -214.23 0.00 0.00 0.00 22.04 14.31 0.00 0.00 0.00 177.88 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 UTILITY 15-JUN-06:01 0.00 0.00 0.00 -431.79 0.00 0.00 0.00 28.93 12.52 520.16 0.00 0.00 0.00 0.00 -0.00 0.00 -3.40 -126.42
FLOOR 2 WORK HALL 29-JUN-06:03 0.00 0.00 0.00 -2495.30 0.00 0.00 0.00 351.53 330.76 0.00 0.00 0.00 1813.01 0.00 -0.00 0.00 0.00 0.00
FLOOR 2 WORK TOILET 30-JUN-06:03 0.00 0.00 0.00 -194.30 0.00 0.00 0.00 20.21 21.42 0.00 0.00 1.91 150.76 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 ELEVATOR HALL 30-JUN-06:03 0.00 0.00 0.00 -890.89 0.00 0.00 0.00 155.96 146.74 0.00 0.00 0.01 588.19 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 JANITOR 30-JUN-17:00 0.00 0.00 0.00 -104.95 0.00 0.00 0.00 14.46 6.26 0.00 0.00 2.28 81.95 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 LOUNGE TOILET 29-JUN-06:05 0.00 0.00 0.00 -554.93 0.00 0.00 0.00 71.85 76.15 140.04 0.00 0.08 266.83 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 MECHANICAL 06-JAN-06:01 0.00 0.00 0.00 -7966.01 0.00 0.00 0.00 294.00 1733.32 0.00 0.00 0.00 6404.98 0.00 -466.29 0.00 0.00 0.00
FLOOR 3 MECHANICAL HALL 30-JUN-06:03 0.00 0.00 0.00 -1091.31 0.00 0.00 0.00 126.45 118.98 0.00 0.00 9.08 836.81 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 OFFICE HALL 30-JUN-06:01 0.00 0.00 0.00 -2250.90 0.00 0.00 0.00 351.53 330.76 0.00 0.00 0.01 1568.60 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 OFFICE TOILET 30-JUN-06:03 0.00 0.00 0.00 -156.09 0.00 0.00 0.00 20.21 21.42 0.00 0.00 0.22 114.25 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 17-FEB-07:03 0.00 0.00 0.00 -266.94 0.00 0.00 0.00 31.43 33.31 0.00 0.00 0.00 202.19 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 1 29-JUN-06:05 0.00 0.00 0.00 -256.86 0.00 0.00 0.00 24.80 10.73 0.00 0.00 1.29 220.04 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 STORAGE 2 30-JUN-15:00 0.00 0.00 0.00 -128.12 0.00 0.00 0.00 19.29 8.35 0.00 0.00 9.27 91.22 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 1 30-JUN-06:01 0.00 0.00 0.00 -6942.86 0.00 0.00 0.00 520.70 2470.94 259.11 0.00 0.64 3691.47 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 2 30-JUN-06:01 0.00 0.00 0.00 -3656.38 0.00 0.00 0.00 264.48 1255.08 127.74 0.00 0.69 2008.39 0.00 -0.00 0.00 0.00 0.00
FLOOR 3 UTILITY 30-JUN-15:10 0.00 0.00 0.00 -197.80 0.00 0.00 0.00 49.59 21.47 0.00 0.00 23.02 103.73 0.00 -0.00 0.00 0.00 0.00
NE STAIR 21-JUL-13:30 0.00 0.00 0.00 -912.03 0.00 0.00 0.00 70.81 66.63 744.09 0.00 11.74 18.76 0.00 -0.00 0.00 0.00 0.00
NW ELEVATOR 11-AUG-17:00 0.00 0.00 0.00 -721.02 0.00 0.00 0.00 59.01 55.52 0.00 0.00 3.97 602.52 0.00 -0.00 0.00 0.00 0.00
NW STAIR 30-JUN-06:01 0.00 0.00 0.00 -1722.70 0.00 0.00 0.00 80.93 76.15 105.01 0.00 11.27 1449.35 0.00 -0.00 0.00 0.00 0.00
SW STAIR 30-JUN-06:01 0.00 0.00 0.00 -856.88 0.00 0.00 0.00 40.46 38.07 9.89 0.00 5.41 763.03 0.00 -0.00 0.00 0.00 0.00
Total Facility 30-JUN-16:10 0.00 0.00 0.00 -144487.68 0.00 0.00 30173.92 24326.07 72372.07 24681.81 0.00 1498.75 0.00 0.00 0.00 0.00 0.00 -8564.93


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
FLOOR 1 ANESTHESIA 04-NOV-04:01 0.00 0.00 554.77 -0.00 0.00 0.00 10.02 15.12 64.19 0.00 0.00 0.00 0.00 0.00 -74.19 0.00 -6.98 -562.93
FLOOR 1 CAFE 17-JAN-05:01 0.00 0.00 610.61 -0.00 0.00 0.00 757.93 50.40 207.92 0.00 0.00 0.00 0.00 0.00 -319.58 0.00 -15.44 -1291.85
FLOOR 1 CLEAN 17-JAN-05:01 0.00 0.00 205.43 -0.00 0.00 0.00 46.74 52.92 124.81 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -429.90
FLOOR 1 CLEAN WORK 17-JAN-05:01 0.00 0.00 262.19 -0.00 0.00 0.00 61.27 69.30 163.44 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -556.20
FLOOR 1 DICTATION - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 DRESSING ROOM 01-JAN-04:11 0.00 0.00 203.87 -0.00 0.00 0.00 0.00 1.67 14.71 0.00 0.00 0.00 0.00 0.00 -133.87 0.00 -13.78 -72.59
FLOOR 1 HUMID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 IT ROOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY 17-JAN-05:01 0.00 0.00 2440.45 -0.00 0.00 0.00 115.03 148.91 338.83 0.00 0.00 0.00 0.00 0.00 -324.64 0.00 -16.72 -2701.85
FLOOR 1 LOCKER ROOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 LOUNGE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 MRI CONTROL ROOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 MRI ROOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 NOURISHMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE STATION - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 OFFICE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 OPERATING ROOM 1 01-APR-05:07 0.00 0.00 1031.72 -0.00 0.00 0.00 37.89 103.96 1029.49 0.00 0.00 0.00 0.00 0.00 -254.42 0.00 -15.05 -1933.58
FLOOR 1 OPERATING ROOM 2 01-APR-05:07 0.00 0.00 657.80 -0.00 0.00 0.00 38.74 108.48 1074.25 0.00 0.00 0.00 0.00 0.00 -195.38 0.00 -7.78 -1676.10
FLOOR 1 OPERATING ROOM 3 16-JAN-23:10 0.00 0.00 2581.56 -0.00 0.00 0.00 0.00 53.79 1065.29 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -3700.64
FLOOR 1 PACU 04-NOV-04:01 0.00 0.00 214.05 -0.00 0.00 0.00 9.99 13.50 96.27 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -333.81
FLOOR 1 PRE-OP ROOM 1 04-NOV-04:01 0.00 0.00 396.59 -0.00 0.00 0.00 8.77 12.85 112.33 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -3.06 -527.49
FLOOR 1 PRE-OP ROOM 2 04-NOV-04:01 0.00 0.00 687.39 -0.00 0.00 0.00 15.69 22.98 200.89 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -926.95
FLOOR 1 PROCEDURE ROOM 03-APR-04:01 0.00 0.00 1647.93 -0.00 0.00 0.00 105.82 119.70 423.40 0.00 0.00 0.00 0.00 0.00 -190.89 0.00 -14.94 -2091.02
FLOOR 1 RECEPTION - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 RECOVERY ROOM 04-NOV-04:01 0.00 0.00 2547.81 -0.00 0.00 0.00 50.13 67.50 481.34 0.00 0.00 0.00 0.00 0.00 -294.66 0.00 -34.82 -2817.29
FLOOR 1 SCHEDULING 02-JAN-05:03 0.00 0.00 204.37 -0.00 0.00 0.00 10.86 22.70 64.82 0.00 0.00 0.00 0.00 0.00 -38.68 0.00 -8.54 -255.53
FLOOR 1 SOIL 17-JAN-05:01 0.00 0.00 209.02 -0.00 0.00 0.00 46.79 52.92 124.81 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -433.53
FLOOR 1 SOIL HOLD 16-JAN-23:10 0.00 0.00 23.88 -0.00 0.00 0.00 0.00 3.92 33.28 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -61.08
FLOOR 1 SOIL WORK 17-JAN-05:01 0.00 0.00 284.52 -0.00 0.00 0.00 66.83 75.60 178.30 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -605.25
FLOOR 1 STEP DOWN 04-NOV-04:01 0.00 0.00 1755.88 -0.00 0.00 0.00 27.85 37.50 267.41 0.00 0.00 0.00 0.00 0.00 -217.05 0.00 -28.75 -1842.84
FLOOR 2 CONFERENCE 11-DEC-05:03 0.00 0.00 1779.53 -0.00 0.00 0.00 311.90 97.78 166.34 0.00 0.00 0.00 0.00 0.00 -534.23 0.00 -52.22 -1769.09
FLOOR 2 DICTATION 17-JAN-07:12 0.00 0.00 91.00 -0.00 0.00 0.00 25.91 40.05 76.26 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -233.22
FLOOR 2 EXAM 1 20-NOV-06:01 0.00 0.00 2993.03 -0.00 0.00 0.00 334.18 235.87 392.21 0.00 0.00 0.00 0.00 0.00 -175.06 0.00 -49.28 -3730.96
FLOOR 2 EXAM 2 20-NOV-06:01 0.00 0.00 6101.89 -0.00 0.00 0.00 501.27 353.81 588.32 0.00 0.00 0.00 0.00 0.00 -75.92 0.00 -21.60 -7447.76
FLOOR 2 EXAM 3 20-NOV-06:01 0.00 0.00 8138.03 -0.00 0.00 0.00 668.36 471.74 784.42 0.00 0.00 0.00 0.00 0.00 -120.27 0.00 -28.79 -9913.50
FLOOR 2 EXAM 4 20-NOV-06:01 0.00 0.00 767.57 -0.00 0.00 0.00 77.98 55.04 91.52 0.00 0.00 0.00 0.00 0.00 -45.56 0.00 -8.25 -938.28
FLOOR 2 EXAM 5 20-NOV-06:01 0.00 0.00 3440.43 -0.00 0.00 0.00 324.53 229.32 381.32 0.00 0.00 0.00 0.00 0.00 -123.65 0.00 -29.79 -4222.16
FLOOR 2 EXAM 6 20-NOV-06:01 0.00 0.00 2400.41 -0.00 0.00 0.00 208.86 147.42 245.13 0.00 0.00 0.00 0.00 0.00 -84.14 0.00 -17.89 -2899.79
FLOOR 2 EXAM 7 20-NOV-06:01 0.00 0.00 8946.42 -0.00 0.00 0.00 735.20 518.92 862.87 0.00 0.00 0.00 0.00 0.00 -112.75 0.00 -28.82 -10921.84
FLOOR 2 EXAM 8 20-NOV-06:01 0.00 0.00 2847.89 -0.00 0.00 0.00 250.63 176.90 294.16 0.00 0.00 0.00 0.00 0.00 -114.11 0.00 -21.49 -3433.99
FLOOR 2 EXAM 9 20-NOV-06:01 0.00 0.00 4468.59 -0.00 0.00 0.00 367.40 259.46 431.43 0.00 0.00 0.00 0.00 0.00 -57.40 0.00 -14.43 -5455.05
FLOOR 2 LOUNGE 26-DEC-07:01 0.00 0.00 127.46 -0.00 0.00 0.00 90.31 42.48 237.70 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -497.95
FLOOR 2 NURSE STATION 1 02-JAN-06:01 0.00 0.00 332.28 -0.00 0.00 0.00 132.61 105.30 297.17 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -867.36
FLOOR 2 NURSE STATION 2 02-JAN-06:01 0.00 0.00 364.05 -0.00 0.00 0.00 159.63 126.36 356.60 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -1006.64
FLOOR 2 OFFICE 02-FEB-05:03 0.00 0.00 2279.57 -0.00 0.00 0.00 51.67 106.80 305.05 0.00 0.00 0.00 0.00 0.00 -569.83 0.00 -57.88 -2115.38
FLOOR 2 RECEPTION 27-NOV-05:02 0.00 0.00 3507.80 -0.00 0.00 0.00 541.63 247.97 536.02 0.00 0.00 0.00 0.00 0.00 -620.00 0.00 -52.44 -4160.98
FLOOR 2 SCHEDULING 1 02-JAN-07:03 0.00 0.00 360.42 -0.00 0.00 0.00 123.13 185.38 352.99 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -1021.92
FLOOR 2 SCHEDULING 2 02-JAN-07:03 0.00 0.00 422.19 -0.00 0.00 0.00 130.16 195.68 372.60 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -1120.63
FLOOR 2 WORK 09-JAN-05:03 0.00 0.00 2401.59 -0.00 0.00 0.00 152.77 322.32 760.46 0.00 0.00 0.00 0.00 0.00 -418.86 0.00 -58.56 -3159.70
FLOOR 2 X-RAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 3 DRESSING ROOM 26-DEC-05:03 0.00 0.00 153.81 -0.00 0.00 0.00 3.87 8.01 22.88 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -8.31 -180.26
FLOOR 3 HUMID 26-DEC-05:03 0.00 0.00 329.80 -0.00 0.00 0.00 9.93 20.60 58.83 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -21.35 -397.81
FLOOR 3 LOCKER 13-FEB-05:03 0.00 0.00 342.56 -0.00 0.00 0.00 32.95 21.24 178.27 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -52.02 -523.00
FLOOR 3 LOUNGE 04-DEC-06:01 0.00 0.00 1694.13 -0.00 0.00 0.00 501.09 268.69 2255.16 0.00 0.00 0.00 0.00 0.00 -225.93 0.00 -1.50 -4491.62
FLOOR 3 OFFICE 17-JAN-05:01 0.00 0.00 7522.26 -0.00 0.00 0.00 281.82 579.03 1653.83 0.00 0.00 0.00 0.00 0.00 -709.57 0.00 -2.09 -9325.28
FLOOR 3 PHYSICAL THERAPY 1 20-NOV-06:01 0.00 0.00 12025.92 -0.00 0.00 0.00 1206.76 553.64 1931.89 0.00 0.00 0.00 0.00 0.00 -557.17 0.00 -6.83 -15154.22
FLOOR 3 PHYSICAL THERAPY 2 20-NOV-06:01 0.00 0.00 5598.99 -0.00 0.00 0.00 549.54 252.12 879.75 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -83.23 -7197.18
FLOOR 3 TREATMENT 21-FEB-06:01 0.00 0.00 4387.32 -0.00 0.00 0.00 441.84 399.84 518.59 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -62.82 -5684.78
FLOOR 3 WORK 03-JAN-05:03 0.00 0.00 2523.16 -0.00 0.00 0.00 53.28 109.47 312.68 0.00 0.00 0.00 0.00 0.00 -381.82 0.00 -6.57 -2610.21
FLOOR 1 BIO HAZ 30-MAY-05:01 0.00 0.00 100.12 -0.00 0.00 0.00 0.00 8.57 5.57 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -114.26
FLOOR 1 ELECTRICAL ROOM 09-JAN-05:03 0.00 0.00 53.84 -0.00 0.00 0.00 0.00 41.16 242.66 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -10.96 -326.71
FLOOR 1 ELEVATOR PUMP ROOM 10-APR-04:01 0.00 0.00 650.29 -0.00 0.00 0.00 0.00 38.22 241.76 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -12.37 -917.90
FLOOR 1 IT HALL 02-JAN-05:08 0.00 0.00 27.19 -0.00 0.00 0.00 0.00 19.67 27.76 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -74.62
FLOOR 1 LOBBY HALL - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY TOILET 03-APR-04:01 0.00 0.00 425.80 -0.00 0.00 0.00 0.00 6.74 10.71 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -4.73 -438.51
FLOOR 1 LOCKER ROOM HALL - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 MED GAS 07-JAN-18:01 0.00 0.00 372.14 -0.00 0.00 0.00 0.00 4.29 2.78 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -8.48 -370.74
FLOOR 1 MRI HALL 02-JAN-05:05 0.00 0.00 35.17 -0.00 0.00 0.00 0.00 20.65 29.15 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -84.98
FLOOR 1 MRI TOILET 27-MAR-04:01 0.00 0.00 241.62 -0.00 0.00 0.00 0.00 6.74 10.71 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -259.06
FLOOR 1 NURSE HALL 17-JAN-05:04 0.00 0.00 92.64 -0.00 0.00 0.00 0.00 69.69 98.35 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -260.68
FLOOR 1 NURSE JANITOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 NURSE TOILET 01-MAY-04:02 0.00 0.00 68.94 -0.00 0.00 0.00 0.00 6.74 10.71 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -86.38
FLOOR 1 PRE-OP HALL 02-JAN-05:05 0.00 0.00 89.51 -0.00 0.00 0.00 0.00 74.18 104.70 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -268.40
FLOOR 1 PRE-OP TOILET 06-JAN-18:16 0.00 0.00 334.50 -0.00 0.00 0.00 0.00 13.47 10.71 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -7.23 -351.45
FLOOR 1 RECEPTION HALL 02-JAN-05:03 0.00 0.00 9.19 -0.00 0.00 0.00 0.00 17.98 25.38 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -52.55
FLOOR 1 SCRUB 17-JAN-05:01 0.00 0.00 176.73 -0.00 0.00 0.00 0.00 11.80 16.66 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -205.19
FLOOR 1 STERILE HALL 02-JAN-05:03 0.00 0.00 558.21 -0.00 0.00 0.00 0.00 86.55 122.15 0.00 0.00 0.00 0.00 0.00 -119.04 0.00 0.00 -647.87
FLOOR 1 STERILE STORAGE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 1 STORAGE 07-JAN-18:01 0.00 0.00 2560.78 -0.00 0.00 0.00 0.00 70.41 45.71 0.00 0.00 0.00 0.00 0.00 -450.24 0.00 -19.89 -2206.76
FLOOR 1 SUB-STERILE 30-MAY-05:01 0.00 0.00 561.93 -0.00 0.00 0.00 0.00 55.08 77.73 0.00 0.00 0.00 0.00 0.00 -24.05 0.00 -4.30 -666.38
FLOOR 1 UTILITY HALL 21-FEB-06:01 0.00 0.00 748.52 -0.00 0.00 0.00 0.00 71.94 101.53 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -6.54 -915.45
FLOOR 1 UTILITY JANITOR 02-JAN-05:03 0.00 0.00 84.84 -0.00 0.00 0.00 0.00 3.21 2.09 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -90.14
FLOOR 1 UTILITY ROOM 21-FEB-06:01 0.00 0.00 768.75 -0.00 0.00 0.00 0.00 55.10 35.78 0.00 0.00 0.00 0.00 0.00 -54.40 0.00 -13.21 -792.03
FLOOR 1 VESTIBULE 06-JAN-08:57 0.00 0.00 615.76 -0.00 0.00 0.00 0.00 30.35 28.55 0.00 0.00 0.00 4452.26 0.00 -0.00 0.00 -5126.92 0.00
FLOOR 2 CONFERENCE TOILET 20-NOV-06:01 0.00 0.00 475.68 -0.00 0.00 0.00 0.00 15.97 25.38 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -517.03
FLOOR 2 EXAM HALL 1 06-FEB-05:03 0.00 0.00 433.84 -0.00 0.00 0.00 0.00 25.29 35.69 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -494.82
FLOOR 2 EXAM HALL 2 18-DEC-05:03 0.00 0.00 273.99 -0.00 0.00 0.00 0.00 25.29 35.69 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -334.97
FLOOR 2 EXAM HALL 3 04-DEC-05:03 0.00 0.00 283.44 -0.00 0.00 0.00 0.00 25.29 35.69 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -344.42
FLOOR 2 EXAM HALL 4 13-NOV-05:03 0.00 0.00 201.21 -0.00 0.00 0.00 0.00 27.82 39.26 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -268.29
FLOOR 2 EXAM HALL 5 20-MAR-05:01 0.00 0.00 196.85 -0.00 0.00 0.00 0.00 55.64 78.53 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -331.02
FLOOR 2 EXAM HALL 6 02-JAN-05:30 0.00 0.00 239.43 -0.00 0.00 0.00 0.00 27.82 39.26 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -306.52
FLOOR 2 JANITOR 20-NOV-06:01 0.00 0.00 421.31 -0.00 0.00 0.00 0.00 9.64 6.26 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -18.42 -418.79
FLOOR 2 OFFICE HALL 11-DEC-05:03 0.00 0.00 689.89 -0.00 0.00 0.00 0.00 62.38 88.04 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -840.32
FLOOR 2 RECEPTION HALL 02-JAN-06:11 0.00 0.00 501.57 -0.00 0.00 0.00 0.00 158.48 223.68 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -883.73
FLOOR 2 RECEPTION TOILET 17-JAN-05:01 0.00 0.00 860.43 -0.00 0.00 0.00 0.00 15.72 24.99 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -901.14
FLOOR 2 STORAGE 1 27-FEB-05:03 0.00 0.00 113.75 -0.00 0.00 0.00 0.00 4.29 2.78 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -120.82
FLOOR 2 STORAGE 2 27-NOV-05:02 0.00 0.00 243.44 -0.00 0.00 0.00 0.00 9.18 5.96 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -258.58
FLOOR 2 STORAGE 3 11-DEC-05:03 0.00 0.00 292.41 -0.00 0.00 0.00 0.00 11.02 7.16 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -310.58
FLOOR 2 UTILITY 20-NOV-06:01 0.00 0.00 664.81 -0.00 0.00 0.00 0.00 19.29 12.52 0.00 0.00 0.00 0.00 0.00 -47.79 0.00 -10.27 -638.55
FLOOR 2 WORK HALL 02-JAN-05:03 0.00 0.00 794.97 -0.00 0.00 0.00 0.00 117.18 165.38 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -1077.52
FLOOR 2 WORK TOILET 20-NOV-06:01 0.00 0.00 449.34 -0.00 0.00 0.00 0.00 13.47 21.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -6.99 -477.24
FLOOR 3 ELEVATOR HALL 21-FEB-06:01 0.00 0.00 962.93 -0.00 0.00 0.00 0.00 103.97 146.74 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -0.05 -1213.59
FLOOR 3 JANITOR 20-NOV-06:01 0.00 0.00 280.46 -0.00 0.00 0.00 0.00 9.64 6.26 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -4.09 -292.28
FLOOR 3 LOUNGE TOILET 20-NOV-06:01 0.00 0.00 1295.08 -0.00 0.00 0.00 0.00 47.90 76.15 0.00 0.00 0.00 0.00 0.00 -87.36 0.00 -0.90 -1330.86
FLOOR 3 MECHANICAL - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLOOR 3 MECHANICAL HALL 09-JAN-05:03 0.00 0.00 1126.69 -0.00 0.00 0.00 0.00 42.15 59.49 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -79.57 -1148.76
FLOOR 3 OFFICE HALL 17-JAN-05:01 0.00 0.00 2629.60 -0.00 0.00 0.00 0.00 117.18 165.38 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -0.05 -2912.11
FLOOR 3 OFFICE TOILET 20-NOV-06:01 0.00 0.00 370.15 -0.00 0.00 0.00 0.00 13.47 21.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -0.77 -404.27
FLOOR 3 PHYSICAL THERAPY TOILET 21-FEB-06:01 0.00 0.00 598.26 -0.00 0.00 0.00 0.00 20.96 33.31 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -10.88 -641.65
FLOOR 3 STORAGE 1 20-NOV-06:01 0.00 0.00 606.18 -0.00 0.00 0.00 0.00 16.53 10.73 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -14.67 -618.78
FLOOR 3 STORAGE 2 21-FEB-06:01 0.00 0.00 275.91 -0.00 0.00 0.00 0.00 12.86 8.35 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -10.61 -286.51
FLOOR 3 UNDEVELOPED 1 17-JAN-05:01 0.00 0.00 6556.26 -0.00 0.00 0.00 0.00 173.57 1235.47 0.00 0.00 0.00 0.00 0.00 -928.40 0.00 -2.63 -7034.26
FLOOR 3 UNDEVELOPED 2 17-JAN-05:01 0.00 0.00 4238.47 -0.00 0.00 0.00 0.00 88.16 627.54 0.00 0.00 0.00 0.00 0.00 -484.46 0.00 -3.10 -4466.61
FLOOR 3 UTILITY 21-FEB-06:01 0.00 0.00 459.39 -0.00 0.00 0.00 0.00 33.06 21.47 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -27.10 -486.82
NE STAIR 09-JAN-05:03 0.00 0.00 2022.41 -0.00 0.00 0.00 0.00 23.60 33.31 0.00 0.00 0.00 0.00 0.00 -869.04 0.00 -85.26 -1125.02
NW ELEVATOR 30-MAY-05:01 0.00 0.00 1326.03 -0.00 0.00 0.00 0.00 39.34 55.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -12.51 -1408.38
NW STAIR 09-JAN-05:03 0.00 0.00 2076.34 -0.00 0.00 0.00 0.00 26.98 38.07 0.00 0.00 0.00 0.00 0.00 -804.77 0.00 -97.33 -1239.28
SW STAIR 30-MAY-05:01 0.00 0.00 1009.90 -0.00 0.00 0.00 0.00 26.98 38.07 0.00 0.00 0.00 0.00 0.00 -9.18 0.00 -9.78 -1055.99
Total Facility 21-FEB-06:01 -39106.47 39106.47 123831.23 -39106.47 0.00 0.00 18494.30 17577.44 67778.55 0.00 0.00 0.00 0.00 0.00 -7483.75 0.00 -2861.13 -178230.17



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
AHU-1 7.1009 0.0000 177.9923 1.0000 2.0710 7.1009 0.3188 1.0000 2.0710 0.2917    
AHU-2 10.7270 0.0000 0.0000 1.0000 0.0000 9.2030 0.0000 1.0000 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
AHU-1 5.2993 0.0000 177.9923 1.0000 2.0710 4.2695 1.0000 1.0000 2.0710 0.4851    
AHU-2 6.4853 0.0000 0.0000 1.0000 0.0000 4.3197 0.0000 1.0000 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
FLOOR 1 ANESTHESIA AHU-1 0.000000 2.1602 0.001524 10.03 0.0153 1.0000 0.0153 1.000 0.0153
FLOOR 1 CAFE AHU-1 0.000000 42.0041 0.004724 39.02 0.1843 1.0000 0.1843 1.000 0.1843
FLOOR 1 CLEAN AHU-1 0.000000 2.5202 0.001524 11.71 0.0178 1.0000 0.0178 1.000 0.0178
FLOOR 1 CLEAN WORK AHU-1 0.000000 3.3003 0.001524 15.33 0.0234 1.0000 0.0234 1.000 0.0234
FLOOR 1 DICTATION AHU-1 0.000000 0.6301 0.000432 11.71 0.0051 1.0000 0.0051 1.000 0.0051
FLOOR 1 DRESSING ROOM AHU-1 0.000000 0.2250 0.000432 4.18 0.0018 1.0000 0.0018 1.000 0.0018
FLOOR 1 HUMID AHU-1 0.000000 0.2700 0.000432 5.02 0.0022 1.0000 0.0022 1.000 0.0022
FLOOR 1 IT ROOM AHU-1 0.000000 0.5601 0.000432 10.41 0.0045 1.0000 0.0045 1.000 0.0045
FLOOR 1 LOBBY AHU-1 0.000000 6.2206 0.000559 57.79 0.0323 1.0000 0.0323 1.000 0.0323
FLOOR 1 LOCKER ROOM AHU-1 0.000000 9.9010 0.000686 61.32 0.0420 1.0000 0.0420 1.000 0.0420
FLOOR 1 LOUNGE AHU-1 0.000000 5.4005 0.000686 33.45 0.0229 1.0000 0.0229 1.000 0.0229
FLOOR 1 MRI CONTROL ROOM AHU-1 0.000000 3.3603 0.001524 15.61 0.0238 1.0000 0.0238 1.000 0.0238
FLOOR 1 MRI ROOM AHU-1 0.000000 8.8009 0.001524 40.88 0.0623 1.0000 0.0623 1.000 0.0623
FLOOR 1 NOURISHMENT AHU-1 0.000000 3.6404 0.000813 16.91 0.0137 1.0000 0.0137 1.000 0.0137
FLOOR 1 NURSE STATION AHU-1 0.000000 5.2205 0.000813 24.25 0.0197 1.0000 0.0197 1.000 0.0197
FLOOR 1 OFFICE AHU-1 0.000000 2.4152 0.000432 44.87 0.0194 1.0000 0.0194 1.000 0.0194
FLOOR 1 OPERATING ROOM 1 AHU-1 0.000000 9.2009 0.005588 42.74 0.2388 1.0000 0.2388 1.000 0.2388
FLOOR 1 OPERATING ROOM 2 AHU-1 0.000000 9.6009 0.005588 44.59 0.2492 1.0000 0.2492 1.000 0.2492
FLOOR 1 OPERATING ROOM 3 AHU-1 0.000000 9.5209 0.005588 44.22 0.2471 1.0000 0.2471 1.000 0.2471
FLOOR 1 PACU AHU-1 0.000000 2.1602 0.003217 10.03 0.0323 1.0000 0.0323 1.000 0.0323
FLOOR 1 PRE-OP ROOM 1 AHU-1 0.000000 1.8902 0.002963 17.56 0.0520 1.0000 0.0520 1.000 0.0520
FLOOR 1 PRE-OP ROOM 2 AHU-1 0.000000 3.3803 0.002963 31.40 0.0930 1.0000 0.0930 1.000 0.0930
FLOOR 1 PROCEDURE ROOM AHU-1 0.000000 5.7006 0.004064 26.48 0.1076 1.0000 0.1076 1.000 0.1076
FLOOR 1 RECEPTION AHU-1 0.000000 15.2715 0.001067 47.29 0.0504 1.0000 0.0504 1.000 0.0504
FLOOR 1 RECOVERY ROOM AHU-1 0.000000 10.8011 0.003217 50.17 0.1614 1.0000 0.1614 1.000 0.1614
FLOOR 1 SCHEDULING AHU-1 0.000000 0.5951 0.000432 11.06 0.0048 1.0000 0.0048 1.000 0.0048
FLOOR 1 SOIL AHU-1 0.000000 2.5202 0.001524 11.71 0.0178 1.0000 0.0178 1.000 0.0178
FLOOR 1 SOIL HOLD AHU-1 0.000000 1.1201 0.001524 5.20 0.0079 1.0000 0.0079 1.000 0.0079
FLOOR 1 SOIL WORK AHU-1 0.000000 3.6004 0.001524 16.72 0.0255 1.0000 0.0255 1.000 0.0255
FLOOR 1 STEP DOWN AHU-1 0.000000 6.0006 0.003217 27.87 0.0897 1.0000 0.0897 1.000 0.0897
FLOOR 2 CONFERENCE AHU-2 0.000000 16.8016 0.001575 31.22 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 DICTATION AHU-2 0.000000 0.3500 0.000432 6.50 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 1 AHU-2 0.000000 7.2007 0.001524 33.45 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 2 AHU-2 0.000000 10.8011 0.001524 50.17 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 3 AHU-2 0.000000 14.4014 0.001524 66.89 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 4 AHU-2 0.000000 1.6802 0.001524 7.80 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 5 AHU-2 0.000000 7.0007 0.001524 32.52 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 6 AHU-2 0.000000 4.5004 0.001524 20.90 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 7 AHU-2 0.000000 15.8415 0.001524 73.58 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 8 AHU-2 0.000000 5.4005 0.001524 25.08 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM 9 AHU-2 0.000000 7.9208 0.001524 36.79 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 LOUNGE AHU-2 0.000000 1.2001 0.000686 7.43 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 NURSE STATION 1 AHU-2 0.000000 3.0003 0.000813 13.94 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 NURSE STATION 2 AHU-2 0.000000 3.6004 0.000813 16.72 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 OFFICE AHU-2 0.000000 2.8003 0.000432 52.03 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 RECEPTION AHU-2 0.000000 29.5229 0.001067 91.42 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 SCHEDULING 1 AHU-2 0.000000 1.6202 0.000432 30.10 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 SCHEDULING 2 AHU-2 0.000000 1.7102 0.000432 31.77 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 WORK AHU-2 0.000000 8.4508 0.000432 157.01 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 X-RAY AHU-2 0.000000 18.0018 0.001524 83.61 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 DRESSING ROOM AHU-2 0.000000 0.2100 0.000432 3.90 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 HUMID AHU-2 0.000000 0.5401 0.000432 10.03 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 LOCKER AHU-2 0.000000 1.8002 0.000686 11.15 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 LOUNGE AHU-2 0.000000 11.3861 0.000686 70.51 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 OFFICE AHU-2 0.000000 15.1815 0.000432 282.05 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 PHYSICAL THERAPY 1 AHU-2 0.000000 26.0025 0.001524 120.77 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 PHYSICAL THERAPY 2 AHU-2 0.000000 11.8412 0.001524 55.00 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 TREATMENT AHU-2 0.000000 9.5209 0.001524 44.22 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 WORK AHU-2 0.000000 2.8703 0.000432 53.33 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 1 BIO HAZ AHU-1 0.000000 0.0000 0.000610 5.20 0.0032 1.0000 0.0032 1.000 0.0032
FLOOR 1 ELECTRICAL ROOM AHU-1 0.000000 0.0000 0.000000 9.10 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 1 ELEVATOR PUMP ROOM AHU-1 0.000000 0.0000 0.000000 8.45 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 1 IT HALL AHU-1 0.000000 0.0000 0.000305 13.01 0.0040 1.0000 0.0040 1.000 0.0040
FLOOR 1 LOBBY HALL AHU-1 0.000000 0.0000 0.000305 22.30 0.0068 1.0000 0.0068 1.000 0.0068
FLOOR 1 LOBBY TOILET AHU-1 0.000000 0.0000 0.000000 5.02 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 1 LOCKER ROOM HALL AHU-1 0.000000 0.0000 0.000305 46.08 0.0140 1.0000 0.0140 1.000 0.0140
FLOOR 1 MED GAS AHU-1 0.000000 0.0000 0.000610 5.20 0.0032 1.0000 0.0032 1.000 0.0032
FLOOR 1 MRI HALL AHU-1 0.000000 0.0000 0.000305 13.66 0.0042 1.0000 0.0042 1.000 0.0042
FLOOR 1 MRI TOILET AHU-1 0.000000 0.0000 0.000000 5.02 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 1 NURSE HALL AHU-1 0.000000 0.0000 0.000305 46.08 0.0140 1.0000 0.0140 1.000 0.0140
FLOOR 1 NURSE JANITOR AHU-1 0.000000 0.0000 0.000610 5.02 0.0031 1.0000 0.0031 1.000 0.0031
FLOOR 1 NURSE TOILET AHU-1 0.000000 0.0000 0.000000 5.02 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 1 PRE-OP HALL AHU-1 0.000000 0.0000 0.000305 49.05 0.0150 1.0000 0.0150 1.000 0.0150
FLOOR 1 PRE-OP TOILET AHU-1 0.000000 0.0000 0.000000 5.02 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 1 RECEPTION HALL AHU-1 0.000000 0.0000 0.000305 11.89 0.0036 1.0000 0.0036 1.000 0.0036
FLOOR 1 SCRUB AHU-1 0.000000 0.0000 0.000305 7.80 0.0024 1.0000 0.0024 1.000 0.0024
FLOOR 1 STERILE HALL AHU-1 0.000000 0.0000 0.000305 57.23 0.0174 1.0000 0.0174 1.000 0.0174
FLOOR 1 STERILE STORAGE AHU-1 0.000000 0.0000 0.000610 36.79 0.0224 1.0000 0.0224 1.000 0.0224
FLOOR 1 STORAGE AHU-1 0.000000 0.0000 0.000610 85.47 0.0521 1.0000 0.0521 1.000 0.0521
FLOOR 1 SUB-STERILE AHU-1 0.000000 0.0000 0.000305 18.21 0.0055 1.0000 0.0055 1.000 0.0055
FLOOR 1 UTILITY HALL AHU-1 0.000000 0.0000 0.000305 23.78 0.0072 1.0000 0.0072 1.000 0.0072
FLOOR 1 UTILITY JANITOR AHU-1 0.000000 0.0000 0.000610 3.90 0.0024 1.0000 0.0024 1.000 0.0024
FLOOR 1 UTILITY ROOM AHU-1 0.000000 0.0000 0.000610 33.45 0.0204 1.0000 0.0204 1.000 0.0204
FLOOR 1 VESTIBULE AHU-1 0.000000 0.0000 0.000305 6.69 0.0020 1.0000 0.0020 1.000 0.0020
FLOOR 2 CONFERENCE TOILET AHU-2 0.000000 0.0000 0.000000 5.95 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM HALL 1 AHU-2 0.000000 0.0000 0.000305 16.72 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM HALL 2 AHU-2 0.000000 0.0000 0.000305 16.72 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM HALL 3 AHU-2 0.000000 0.0000 0.000305 16.72 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM HALL 4 AHU-2 0.000000 0.0000 0.000305 18.39 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM HALL 5 AHU-2 0.000000 0.0000 0.000305 18.39 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 EXAM HALL 6 AHU-2 0.000000 0.0000 0.000305 18.39 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 JANITOR AHU-2 0.000000 0.0000 0.000610 5.85 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 OFFICE HALL AHU-2 0.000000 0.0000 0.000305 41.25 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 RECEPTION HALL AHU-2 0.000000 0.0000 0.000305 52.40 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 RECEPTION TOILET AHU-2 0.000000 0.0000 0.000000 11.71 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 STORAGE 1 AHU-2 0.000000 0.0000 0.000610 5.20 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 STORAGE 2 AHU-2 0.000000 0.0000 0.000610 11.15 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 STORAGE 3 AHU-2 0.000000 0.0000 0.000610 13.38 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 UTILITY AHU-2 0.000000 0.0000 0.000610 11.71 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 WORK HALL AHU-2 0.000000 0.0000 0.000305 77.48 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 2 WORK TOILET AHU-2 0.000000 0.0000 0.000000 5.02 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 ELEVATOR HALL AHU-2 0.000000 0.0000 0.000305 34.37 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 JANITOR AHU-2 0.000000 0.0000 0.000610 5.85 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 LOUNGE TOILET AHU-2 0.000000 0.0000 0.000000 17.84 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 MECHANICAL AHU-2 0.000000 0.0000 0.000000 32.52 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 MECHANICAL HALL AHU-2 0.000000 0.0000 0.000305 27.87 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 OFFICE HALL AHU-2 0.000000 0.0000 0.000305 77.48 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 OFFICE TOILET AHU-2 0.000000 0.0000 0.000000 5.02 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 PHYSICAL THERAPY TOILET AHU-2 0.000000 0.0000 0.000000 7.80 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 STORAGE 1 AHU-2 0.000000 0.0000 0.000610 10.03 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 STORAGE 2 AHU-2 0.000000 0.0000 0.000610 7.80 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 UNDEVELOPED 1 AHU-2 0.000000 0.0000 0.000610 210.70 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 UNDEVELOPED 2 AHU-2 0.000000 0.0000 0.000610 107.02 0.0000 1.0000 0.0000 1.000 0.0000
FLOOR 3 UTILITY AHU-2 0.000000 0.0000 0.000610 20.07 0.0000 1.0000 0.0000 1.000 0.0000
NE STAIR AHU-2 0.000000 0.0000 0.000305 15.61 0.0000 1.0000 0.0000 1.000 0.0000
NW ELEVATOR AHU-2 0.000000 0.0000 0.000305 13.01 0.0000 1.0000 0.0000 1.000 0.0000
NW STAIR AHU-2 0.000000 0.0000 0.000305 17.84 0.0000 1.0000 0.0000 1.000 0.0000
SW STAIR AHU-2 0.000000 0.0000 0.000305 8.92 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
AHU-1 0.000000 177.99 0.001571 1317.9225 2.0710 2.0710 2.0710
AHU-2   0.00 0.000759 2486.0854 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
FLOOR 1 ANESTHESIA AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0491 0.0491 0.0491 0.0153 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 CAFE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2959 0.2959 0.0592 0.1843 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 CLEAN AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0504 0.0504 0.0504 0.0178 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 CLEAN WORK AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0622 0.0622 0.0622 0.0234 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 DICTATION AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0370 0.0370 0.0074 0.0051 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 DRESSING ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0161 0.0161 0.0032 0.0018 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 HUMID AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0178 0.0178 0.0036 0.0022 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 IT ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0269 0.0269 0.0054 0.0045 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOBBY AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2735 0.2735 0.0547 0.0323 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOCKER ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2356 0.2356 0.0471 0.0420 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOUNGE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1306 0.1306 0.0261 0.0229 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI CONTROL ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1438 0.1438 0.0288 0.0238 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3679 0.3679 0.0736 0.0623 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NOURISHMENT AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0715 0.0715 0.0143 0.0137 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE STATION AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0975 0.0975 0.0195 0.0197 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OFFICE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1104 0.1104 0.0221 0.0194 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OPERATING ROOM 1 AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7236 0.7236 0.7236 0.2388 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OPERATING ROOM 2 AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7551 0.7551 0.7551 0.2492 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OPERATING ROOM 3 AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7488 0.7488 0.7488 0.2471 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PACU AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0510 0.0510 0.0510 0.0323 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP ROOM 1 AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0892 0.0892 0.0892 0.0520 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP ROOM 2 AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1595 0.1595 0.1595 0.0930 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PROCEDURE ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3362 0.3362 0.3362 0.1076 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 RECEPTION AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1840 0.1840 0.0368 0.0504 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 RECOVERY ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2716 0.2716 0.2363 0.1614 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SCHEDULING AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0301 0.0301 0.0060 0.0048 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SOIL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0502 0.0502 0.0502 0.0178 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SOIL HOLD AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0196 0.0196 0.0196 0.0079 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SOIL WORK AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0666 0.0666 0.0666 0.0255 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STEP DOWN AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1614 0.1614 0.1114 0.0897 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 CONFERENCE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2214 0.2214 0.0737 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 DICTATION AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0258 0.0258 0.0042 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2412 0.2412 0.1230 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2548 0.2548 0.2548 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 3 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3398 0.3398 0.3398 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 4 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0495 0.0495 0.0317 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 5 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2072 0.2072 0.1430 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 6 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1062 0.1062 0.0998 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 7 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3738 0.3738 0.3738 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 8 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1274 0.1274 0.1185 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 9 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1869 0.1869 0.1869 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 LOUNGE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0387 0.0387 0.0077 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 NURSE STATION 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0631 0.0631 0.0170 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 NURSE STATION 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0758 0.0758 0.0204 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 OFFICE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2407 0.2407 0.0337 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 RECEPTION AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4635 0.4635 0.1465 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 SCHEDULING 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0934 0.0934 0.0195 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 SCHEDULING 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1033 0.1033 0.0205 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 WORK AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4198 0.4198 0.1016 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 X-RAY AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8438 0.8438 0.1915 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 DRESSING ROOM AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0177 0.0177 0.0025 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 HUMID AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0421 0.0421 0.0065 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 LOCKER AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0581 0.0581 0.0114 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 LOUNGE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3361 0.3361 0.0726 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 OFFICE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7386 0.7386 0.1824 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 PHYSICAL THERAPY 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7203 0.7203 0.4970 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 PHYSICAL THERAPY 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2794 0.2794 0.2319 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 TREATMENT AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2246 0.2246 0.1820 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 WORK AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2921 0.2921 0.0345 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 BIO HAZ AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0079 0.0079 0.0016 0.0032 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 ELECTRICAL ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0453 0.0453 0.0091 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 ELEVATOR PUMP ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2980 0.2980 0.0596 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 IT HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0247 0.0247 0.0049 0.0040 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOBBY HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0565 0.0565 0.0113 0.0068 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOBBY TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0362 0.0362 0.0362 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOCKER ROOM HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0853 0.0853 0.0171 0.0140 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MED GAS AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0292 0.0292 0.0058 0.0032 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0332 0.0332 0.0066 0.0042 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0098 0.0098 0.0098 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1040 0.1040 0.0208 0.0140 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE JANITOR AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0125 0.0125 0.0025 0.0031 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0155 0.0155 0.0155 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1005 0.1005 0.0201 0.0150 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0124 0.0124 0.0124 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 RECEPTION HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0258 0.0258 0.0052 0.0036 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SCRUB AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0175 0.0175 0.0035 0.0024 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STERILE HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1000 0.1000 0.0200 0.0174 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STERILE STORAGE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0609 0.0609 0.0122 0.0224 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STORAGE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2016 0.2016 0.0403 0.0521 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SUB-STERILE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0448 0.0448 0.0090 0.0055 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 UTILITY HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0595 0.0595 0.0119 0.0072 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 UTILITY JANITOR AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0087 0.0087 0.0017 0.0024 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 UTILITY ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0612 0.0612 0.0122 0.0204 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 VESTIBULE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0165 0.0165 0.0033 0.0020 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 CONFERENCE TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0196 0.0196 0.0196 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0558 0.0558 0.0076 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0554 0.0554 0.0076 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 3 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0533 0.0533 0.0077 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 4 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0546 0.0546 0.0084 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 5 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0573 0.0573 0.0084 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 6 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0569 0.0569 0.0084 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 JANITOR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0342 0.0342 0.0054 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 OFFICE HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1320 0.1320 0.0189 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 RECEPTION HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1715 0.1715 0.0240 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 RECEPTION TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0356 0.0356 0.0356 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 STORAGE 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0162 0.0162 0.0048 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 STORAGE 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0280 0.0280 0.0102 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 STORAGE 3 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0363 0.0363 0.0122 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 UTILITY AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0536 0.0536 0.0107 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 WORK HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2320 0.2320 0.0355 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 WORK TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0184 0.0184 0.0184 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 ELEVATOR HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0770 0.0770 0.0157 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 JANITOR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0225 0.0225 0.0087 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 LOUNGE TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0526 0.0526 0.0526 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 MECHANICAL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3214 0.3214 0.0032 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 MECHANICAL HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0928 0.0928 0.0127 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 OFFICE HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2122 0.2122 0.0354 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 OFFICE TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0150 0.0150 0.0150 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 PHYSICAL THERAPY TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0245 0.0245 0.0245 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 STORAGE 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0245 0.0245 0.0245 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 STORAGE 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0221 0.0221 0.0071 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 UNDEVELOPED 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6755 0.6755 0.1925 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 UNDEVELOPED 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3424 0.3424 0.0979 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 UTILITY AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0363 0.0363 0.0183 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
NE STAIR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1612 0.1612 0.0124 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
NW ELEVATOR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1057 0.1057 0.0080 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
NW STAIR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1652 0.1652 0.0142 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
SW STAIR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0806 0.0806 0.0049 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
AHU-1 7.1009 7.1009 7.1009 4.2695 2.0710 1.0000
AHU-2 10.7270 9.2030 10.7270 4.3197 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
FLOOR 1 ANESTHESIA AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0491 0.0491 0.0491 0.0153 0.9565 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 CAFE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1479 0.1479 0.0592 0.1843 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 CLEAN AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0504 0.0504 0.0504 0.0178 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 CLEAN WORK AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0622 0.0622 0.0622 0.0234 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 DICTATION AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0185 0.0185 0.0074 0.0051 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 DRESSING ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0080 0.0080 0.0032 0.0018 0.1124 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 HUMID AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0089 0.0089 0.0036 0.0022 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 IT ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0135 0.0135 0.0054 0.0045 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOBBY AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1367 0.1367 0.0547 0.0323 0.4782 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOCKER ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1178 0.1178 0.0471 0.0420 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOUNGE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0653 0.0653 0.0261 0.0229 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI CONTROL ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0719 0.0719 0.0288 0.0238 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1839 0.1839 0.0736 0.0623 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NOURISHMENT AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0357 0.0357 0.0143 0.0137 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE STATION AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0488 0.0488 0.0195 0.0197 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OFFICE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0552 0.0552 0.0221 0.0194 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OPERATING ROOM 1 AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7236 0.7236 0.7236 0.2388 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OPERATING ROOM 2 AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7551 0.7551 0.7551 0.2492 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 OPERATING ROOM 3 AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7488 0.7488 0.7488 0.2471 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PACU AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0510 0.0510 0.0510 0.0323 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP ROOM 1 AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0892 0.0892 0.0892 0.0520 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP ROOM 2 AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1595 0.1595 0.1595 0.0930 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PROCEDURE ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3362 0.3362 0.3362 0.1076 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 RECEPTION AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0920 0.0920 0.0368 0.0504 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 RECOVERY ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2363 0.2363 0.2363 0.1614 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SCHEDULING AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0151 0.0151 0.0060 0.0048 0.9488 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SOIL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0502 0.0502 0.0502 0.0178 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SOIL HOLD AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0196 0.0196 0.0196 0.0079 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SOIL WORK AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0666 0.0666 0.0666 0.0255 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STEP DOWN AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1114 0.1114 0.1114 0.0897 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 CONFERENCE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1107 0.1107 0.0737 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 DICTATION AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0129 0.0129 0.0042 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1230 0.1230 0.1230 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2548 0.2548 0.2548 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 3 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3398 0.3398 0.3398 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 4 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0317 0.0317 0.0317 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 5 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1430 0.1430 0.1430 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 6 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0998 0.0998 0.0998 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 7 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3738 0.3738 0.3738 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 8 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1185 0.1185 0.1185 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM 9 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1869 0.1869 0.1869 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 LOUNGE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0193 0.0193 0.0077 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 NURSE STATION 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0316 0.0316 0.0170 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 NURSE STATION 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0379 0.0379 0.0204 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 OFFICE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1203 0.1203 0.0337 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 RECEPTION AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2317 0.2317 0.1465 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 SCHEDULING 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0467 0.0467 0.0195 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 SCHEDULING 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0516 0.0516 0.0205 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 WORK AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2099 0.2099 0.1016 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 X-RAY AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4219 0.4219 0.1915 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 DRESSING ROOM AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0088 0.0088 0.0025 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 HUMID AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0210 0.0210 0.0065 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 LOCKER AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0290 0.0290 0.0114 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 LOUNGE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1681 0.1681 0.0726 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 OFFICE AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3693 0.3693 0.1824 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 PHYSICAL THERAPY 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4970 0.4970 0.4970 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 PHYSICAL THERAPY 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2319 0.2319 0.2319 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 TREATMENT AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1820 0.1820 0.1820 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 WORK AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1460 0.1460 0.0345 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 BIO HAZ AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0040 0.0040 0.0016 0.0032 0.5640 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 ELECTRICAL ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0227 0.0227 0.0091 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 ELEVATOR PUMP ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1490 0.1490 0.0596 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 IT HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0124 0.0124 0.0049 0.0040 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOBBY HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0283 0.0283 0.0113 0.0068 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOBBY TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0362 0.0362 0.0362 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 LOCKER ROOM HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0427 0.0427 0.0171 0.0140 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MED GAS AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0146 0.0146 0.0058 0.0032 0.1084 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0166 0.0166 0.0066 0.0042 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 MRI TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0098 0.0098 0.0098 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0520 0.0520 0.0208 0.0140 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE JANITOR AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0063 0.0063 0.0025 0.0031 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 NURSE TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0155 0.0155 0.0155 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0503 0.0503 0.0201 0.0150 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 PRE-OP TOILET AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0124 0.0124 0.0124 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 RECEPTION HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0129 0.0129 0.0052 0.0036 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SCRUB AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0088 0.0088 0.0035 0.0024 0.4424 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STERILE HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0500 0.0500 0.0200 0.0174 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STERILE STORAGE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0305 0.0305 0.0122 0.0224 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 STORAGE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1008 0.1008 0.0403 0.0521 0.2585 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 SUB-STERILE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0224 0.0224 0.0090 0.0055 0.1518 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 UTILITY HALL AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0298 0.0298 0.0119 0.0072 0.1218 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 UTILITY JANITOR AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0044 0.0044 0.0017 0.0024 0.9384 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 UTILITY ROOM AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0306 0.0306 0.0122 0.0204 0.3331 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 1 VESTIBULE AHU-1 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0083 0.0083 0.0033 0.0020 0.1234 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 CONFERENCE TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0196 0.0196 0.0196 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0279 0.0279 0.0076 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0277 0.0277 0.0076 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 3 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0266 0.0266 0.0077 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 4 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0273 0.0273 0.0084 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 5 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0287 0.0287 0.0084 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 EXAM HALL 6 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0284 0.0284 0.0084 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 JANITOR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0171 0.0171 0.0054 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 OFFICE HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0660 0.0660 0.0189 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 RECEPTION HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0857 0.0857 0.0240 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 RECEPTION TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0356 0.0356 0.0356 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 STORAGE 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0081 0.0081 0.0048 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 STORAGE 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0140 0.0140 0.0102 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 STORAGE 3 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0182 0.0182 0.0122 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 UTILITY AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0268 0.0268 0.0107 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 WORK HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1160 0.1160 0.0355 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 2 WORK TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0184 0.0184 0.0184 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 ELEVATOR HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0385 0.0385 0.0157 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 JANITOR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0112 0.0112 0.0087 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 LOUNGE TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0526 0.0526 0.0526 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 MECHANICAL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1607 0.1607 0.0032 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 MECHANICAL HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0464 0.0464 0.0127 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 OFFICE HALL AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1061 0.1061 0.0354 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 OFFICE TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0150 0.0150 0.0150 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 PHYSICAL THERAPY TOILET AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0245 0.0245 0.0245 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 STORAGE 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0245 0.0245 0.0245 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 STORAGE 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0111 0.0111 0.0071 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 UNDEVELOPED 1 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3377 0.3377 0.1925 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 UNDEVELOPED 2 AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1712 0.1712 0.0979 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FLOOR 3 UTILITY AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0183 0.0183 0.0183 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
NE STAIR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0806 0.0806 0.0124 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
NW ELEVATOR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0528 0.0528 0.0080 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
NW STAIR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0826 0.0826 0.0142 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
SW STAIR AHU-2 AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0403 0.0403 0.0049 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
AHU-1 5.2993 4.2695 4.2695 4.2695 2.0710 1.0000
AHU-2 6.4853 4.3197 4.3197 4.3197 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2020-06-04 00:31:20

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Total gross floor area [m2] 3804.01
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
FLOOR 1 ANESTHESIA 10.03 10.03 0.00 150.16
FLOOR 1 CAFE 39.02 39.02 0.00 150.16
FLOOR 1 CLEAN 11.71 11.71 0.00 150.16
FLOOR 1 CLEAN WORK 15.33 15.33 0.00 150.16
FLOOR 1 DICTATION 11.71 11.71 0.00 138.54
FLOOR 1 DRESSING ROOM 4.18 4.18 0.00 138.54
FLOOR 1 HUMID 5.02 5.02 0.00 138.54
FLOOR 1 IT ROOM 10.41 10.41 0.00 138.54
FLOOR 1 LOBBY 57.79 57.79 0.00 150.16
FLOOR 1 LOCKER ROOM 61.32 61.32 0.00 150.16
FLOOR 1 LOUNGE 33.45 33.45 0.00 150.16
FLOOR 1 MRI CONTROL ROOM 15.61 15.61 0.00 150.16
FLOOR 1 MRI ROOM 40.88 40.88 0.00 150.16
FLOOR 1 NOURISHMENT 16.91 16.91 0.00 150.16
FLOOR 1 NURSE STATION 24.25 24.25 0.00 150.16
FLOOR 1 OFFICE 44.87 44.87 0.00 138.54
FLOOR 1 OPERATING ROOM 1 42.74 42.74 0.00 150.16
FLOOR 1 OPERATING ROOM 2 44.59 44.59 0.00 150.16
FLOOR 1 OPERATING ROOM 3 44.22 44.22 0.00 150.16
FLOOR 1 PACU 10.03 10.03 0.00 150.16
FLOOR 1 PRE-OP ROOM 1 17.56 17.56 0.00 150.16
FLOOR 1 PRE-OP ROOM 2 31.40 31.40 0.00 150.16
FLOOR 1 PROCEDURE ROOM 26.48 26.48 0.00 150.16
FLOOR 1 RECEPTION 47.29 47.29 0.00 150.16
FLOOR 1 RECOVERY ROOM 50.17 50.17 0.00 150.16
FLOOR 1 SCHEDULING 11.06 11.06 0.00 138.54
FLOOR 1 SOIL 11.71 11.71 0.00 150.16
FLOOR 1 SOIL HOLD 5.20 5.20 0.00 150.16
FLOOR 1 SOIL WORK 16.72 16.72 0.00 150.16
FLOOR 1 STEP DOWN 27.87 27.87 0.00 150.16
FLOOR 2 CONFERENCE 31.22 31.22 0.00 127.84
FLOOR 2 DICTATION 6.50 6.50 0.00 138.54
FLOOR 2 EXAM 1 33.45 33.45 0.00 150.16
FLOOR 2 EXAM 2 50.17 50.17 0.00 150.16
FLOOR 2 EXAM 3 66.89 66.89 0.00 150.16
FLOOR 2 EXAM 4 7.80 7.80 0.00 150.16
FLOOR 2 EXAM 5 32.52 32.52 0.00 150.16
FLOOR 2 EXAM 6 20.90 20.90 0.00 150.16
FLOOR 2 EXAM 7 73.58 73.58 0.00 150.16
FLOOR 2 EXAM 8 25.08 25.08 0.00 150.16
FLOOR 2 EXAM 9 36.79 36.79 0.00 150.16
FLOOR 2 LOUNGE 7.43 7.43 0.00 150.16
FLOOR 2 NURSE STATION 1 13.94 13.94 0.00 150.16
FLOOR 2 NURSE STATION 2 16.72 16.72 0.00 150.16
FLOOR 2 OFFICE 52.03 52.03 0.00 138.54
FLOOR 2 RECEPTION 91.42 91.42 0.00 150.16
FLOOR 2 SCHEDULING 1 30.10 30.10 0.00 138.54
FLOOR 2 SCHEDULING 2 31.77 31.77 0.00 138.54
FLOOR 2 WORK 157.01 157.01 0.00 138.54
FLOOR 2 X-RAY 83.61 83.61 0.00 150.16
FLOOR 3 DRESSING ROOM 3.90 3.90 0.00 138.54
FLOOR 3 HUMID 10.03 10.03 0.00 138.54
FLOOR 3 LOCKER 11.15 11.15 0.00 150.16
FLOOR 3 LOUNGE 70.51 70.51 0.00 150.16
FLOOR 3 OFFICE 282.05 282.05 0.00 138.54
FLOOR 3 PHYSICAL THERAPY 1 120.77 120.77 0.00 150.16
FLOOR 3 PHYSICAL THERAPY 2 55.00 55.00 0.00 150.16
FLOOR 3 TREATMENT 44.22 44.22 0.00 150.16
FLOOR 3 WORK 53.33 53.33 0.00 138.54
FLOOR 1 BIO HAZ 5.20 5.20 0.00 0.00
FLOOR 1 ELECTRICAL ROOM 9.10 9.10 0.00 0.00
FLOOR 1 ELEVATOR PUMP ROOM 8.45 8.45 0.00 0.00
FLOOR 1 IT HALL 13.01 13.01 0.00 0.00
FLOOR 1 LOBBY HALL 22.30 22.30 0.00 0.00
FLOOR 1 LOBBY TOILET 5.02 5.02 0.00 0.00
FLOOR 1 LOCKER ROOM HALL 46.08 46.08 0.00 0.00
FLOOR 1 MED GAS 5.20 5.20 0.00 0.00
FLOOR 1 MRI HALL 13.66 13.66 0.00 0.00
FLOOR 1 MRI TOILET 5.02 5.02 0.00 0.00
FLOOR 1 NURSE HALL 46.08 46.08 0.00 0.00
FLOOR 1 NURSE JANITOR 5.02 5.02 0.00 0.00
FLOOR 1 NURSE TOILET 5.02 5.02 0.00 0.00
FLOOR 1 PRE-OP HALL 49.05 49.05 0.00 0.00
FLOOR 1 PRE-OP TOILET 5.02 5.02 0.00 0.00
FLOOR 1 RECEPTION HALL 11.89 11.89 0.00 0.00
FLOOR 1 SCRUB 7.80 7.80 0.00 0.00
FLOOR 1 STERILE HALL 57.23 57.23 0.00 0.00
FLOOR 1 STERILE STORAGE 36.79 36.79 0.00 0.00
FLOOR 1 STORAGE 85.47 85.47 0.00 0.00
FLOOR 1 SUB-STERILE 18.21 18.21 0.00 0.00
FLOOR 1 UTILITY HALL 23.78 23.78 0.00 0.00
FLOOR 1 UTILITY JANITOR 3.90 3.90 0.00 0.00
FLOOR 1 UTILITY ROOM 33.45 33.45 0.00 0.00
FLOOR 1 VESTIBULE 6.69 6.69 0.00 0.00
FLOOR 2 CONFERENCE TOILET 5.95 5.95 0.00 0.00
FLOOR 2 EXAM HALL 1 16.72 16.72 0.00 0.00
FLOOR 2 EXAM HALL 2 16.72 16.72 0.00 0.00
FLOOR 2 EXAM HALL 3 16.72 16.72 0.00 0.00
FLOOR 2 EXAM HALL 4 18.39 18.39 0.00 0.00
FLOOR 2 EXAM HALL 5 18.39 18.39 0.00 0.00
FLOOR 2 EXAM HALL 6 18.39 18.39 0.00 0.00
FLOOR 2 JANITOR 5.85 5.85 0.00 0.00
FLOOR 2 OFFICE HALL 41.25 41.25 0.00 0.00
FLOOR 2 RECEPTION HALL 52.40 52.40 0.00 0.00
FLOOR 2 RECEPTION TOILET 11.71 11.71 0.00 0.00
FLOOR 2 STORAGE 1 5.20 5.20 0.00 0.00
FLOOR 2 STORAGE 2 11.15 11.15 0.00 0.00
FLOOR 2 STORAGE 3 13.38 13.38 0.00 0.00
FLOOR 2 UTILITY 11.71 11.71 0.00 0.00
FLOOR 2 WORK HALL 77.48 77.48 0.00 0.00
FLOOR 2 WORK TOILET 5.02 5.02 0.00 0.00
FLOOR 3 ELEVATOR HALL 34.37 34.37 0.00 0.00
FLOOR 3 JANITOR 5.85 5.85 0.00 0.00
FLOOR 3 LOUNGE TOILET 17.84 17.84 0.00 0.00
FLOOR 3 MECHANICAL 32.52 32.52 0.00 0.00
FLOOR 3 MECHANICAL HALL 27.87 27.87 0.00 0.00
FLOOR 3 OFFICE HALL 77.48 77.48 0.00 0.00
FLOOR 3 OFFICE TOILET 5.02 5.02 0.00 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 7.80 7.80 0.00 0.00
FLOOR 3 STORAGE 1 10.03 10.03 0.00 0.00
FLOOR 3 STORAGE 2 7.80 7.80 0.00 0.00
FLOOR 3 UNDEVELOPED 1 210.70 210.70 0.00 0.00
FLOOR 3 UNDEVELOPED 2 107.02 107.02 0.00 0.00
FLOOR 3 UTILITY 20.07 20.07 0.00 0.00
NE STAIR 15.61 15.61 0.00 0.00
NW ELEVATOR 13.01 13.01 0.00 0.00
NW STAIR 17.84 17.84 0.00 0.00
SW STAIR 8.92 8.92 0.00 0.00
Totals 3804.01 3804.01 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 2344.50
Number of hours cooling loads not met 1786.17
Number of hours not met 3392.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Fuel Use [GJ] Additional Fuel Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- Boiler 0.00 0.00 1302.26 150515.18 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Other 253.03 128516.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- Not Subdivided 347.07 109128.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 380.82 26366.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 55.34 5724.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 1190.14 62583.90 188.37 9905.77 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLift 636.70 48164.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLightsFan 2.57 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 345.45 27402.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 7.47 585.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 318.66 31787.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 240.06 23294.11 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1829.40 3537.24
Natural Gas 188.37 1730.69
Additional 0.00 0.00
Total 2017.78 5267.93


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 100.11
Space Heating 66.52
Space Cooling 91.24
Fans (All) 90.81
Service Water Heating 0.00
Receptacle Equipment 480.92
Miscellaneous (All) 929.87
Subtotal 929.87


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 342.34
Service Water Heating 63.11
Miscellaneous (All) 454.97
Subtotal 454.97


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 7.23
Space Heating 29.52
Space Cooling 6.59
Fans (All) 6.56
Service Water Heating 4.56
Receptacle Equipment 38.30
Miscellaneous 7.24


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
FLOOR 1 ANESTHESIA WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 ANESTHESIA WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 MRI CONTROL ROOM WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 MRI CONTROL ROOM WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 MRI ROOM WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 MRI ROOM WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 OPERATING ROOM 1 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 OPERATING ROOM 1 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 OPERATING ROOM 2 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 OPERATING ROOM 2 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 OPERATING ROOM 3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 OPERATING ROOM 3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 PACU WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 PACU WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 PRE-OP ROOM 1 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 PRE-OP ROOM 1 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 PRE-OP ROOM 2 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 PRE-OP ROOM 2 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 PROCEDURE ROOM WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 PROCEDURE ROOM WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 RECOVERY ROOM WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 RECOVERY ROOM WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 1 STEP DOWN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 1 STEP DOWN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 2 X-RAY WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 2 X-RAY WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 3 PHYSICAL THERAPY 1 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 3 PHYSICAL THERAPY 1 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
FLOOR 3 PHYSICAL THERAPY 2 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
FLOOR 3 PHYSICAL THERAPY 2 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
AHU-1_OAMINOAFRACSCHEDULE 2891. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
EXTERIOR_LGT_189_1 6932. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
BLDG_ELEVATORS 3741. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 3871. 8760.
BLDG_SWH_SCH 2170. 7965.
WORK_EFF_SCH 0. 0.
INFIL_SCH 2190. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_DOOR_OPENING_SCH 2928. 3380.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
OR_MINSA_SCHED 4747. 8760.
BLDG_LIGHT_CORRIDOR_SCH 3702. 8760.
BLDG_LIGHT_EXAM_SCH 3033. 8760.
BLDG_LIGHT_LOBBYFLR1_SCH 3694. 8760.
BLDG_LIGHT_LOCKER_SCH 3889. 8760.
BLDG_LIGHT_LOUNGE_SCH 3889. 8760.
BLDG_LIGHT_OFFICE_SCH 3346. 8760.
BLDG_LIGHT_SCH 3889. 8760.
BLDG_LIGHT_STORAGE_SCH 2610. 8760.
BLDG_LIGHT_TOILET_SCH 2567. 8760.
BLDG_EQUIP_SCH 5293. 8760.
BLDG_EQUIP_SCH_BASE 5344. 8760.
BLDG_OCC_SCH 3469. 7965.
MEETINGROOM_OCC_W_SB_SCH 2668. 6769.
OFFICE_OCC_W_SB_SCH 2970. 7341.
BLDG_OA_SCH 3744. 3744.
BLDG_CAV_SCH 5694. 8760.
BLDG_CAV_SCH_HUMID 6570. 8760.
BLDG_OA_FRAC_SCH 936. 3744.
FLOOR 2 CONFERENCE_MDP_SCH 1513. 7564.
FLOOR 1 DICTATION_MDP_SCH 1627. 8136.
FLOOR 1 DRESSING ROOM_MDP_SCH 1627. 8136.
FLOOR 1 HUMID_MDP_SCH 1627. 8136.
FLOOR 1 IT ROOM_MDP_SCH 1627. 8136.
FLOOR 1 OFFICE_MDP_SCH 1627. 8136.
FLOOR 1 SCHEDULING_MDP_SCH 1627. 8136.
FLOOR 2 DICTATION_MDP_SCH 1627. 8136.
FLOOR 2 OFFICE_MDP_SCH 1627. 8136.
FLOOR 2 SCHEDULING 1_MDP_SCH 1627. 8136.
FLOOR 2 SCHEDULING 2_MDP_SCH 1627. 8136.
FLOOR 2 WORK_MDP_SCH 1627. 8136.
FLOOR 3 DRESSING ROOM_MDP_SCH 1627. 8136.
FLOOR 3 HUMID_MDP_SCH 1627. 8136.
FLOOR 3 OFFICE_MDP_SCH 1627. 8136.
FLOOR 3 WORK_MDP_SCH 1627. 8136.
AHU_1 BALANCED EXHAUST FRACTION SCHEDULE 8760. 8760.
AHU_2 BALANCED EXHAUST FRACTION SCHEDULE 3744. 3744.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM FLOOR 1 ANESTHESIA DUALSPSCHED January 21.10 365 18.30 365
CLGSETP_SCH_YES_OPTIMUM FLOOR 1 ANESTHESIA DUALSPSCHED July 22.20 365 25.00 365
HTGSETP_SCH_YES_OPTIMUM_OFF_W_SB FLOOR 1 DICTATION DUALSPSCHED January 21.10 365 18.30 365
CLGSETP_SCH_YES_OPTIMUM_OFF_W_SB FLOOR 1 DICTATION DUALSPSCHED July 22.20 365 25.00 365
OR_HTGSETP_SCH FLOOR 1 OPERATING ROOM 1 DUALSPSCHED January 18.10 365 18.10 365
OR_CLGSETP_SCH FLOOR 1 OPERATING ROOM 1 DUALSPSCHED July 18.60 365 22.20 365



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.278519E+12
February 0.000 0.203507E+12
March 0.000 0.163567E+12
April 0.000 0.718858E+11
May 0.000 0.380277E+11
June 0.000 0.310787E+11
July 0.000 0.298021E+11
August 0.000 0.286887E+11
September 0.000 0.313629E+11
October 0.000 0.545845E+11
November 0.000 0.115365E+12
December 0.000 0.255869E+12
     
Annual Sum or Average   0.130226E+13
Minimum of Months 0.000 0.286887E+11
Maximum of Months 0.000 0.278519E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.278519E+12
February 0.000 0.203507E+12
March 0.000 0.163567E+12
April 0.000 0.718858E+11
May 0.000 0.380277E+11
June 0.000 0.310787E+11
July 0.000 0.298021E+11
August 0.000 0.286887E+11
September 0.000 0.313629E+11
October 0.000 0.545845E+11
November 0.000 0.115365E+12
December 0.000 0.255869E+12
     
Annual Sum or Average   0.130226E+13
Minimum of Months 0.000 0.286887E+11
Maximum of Months 0.000 0.278519E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.278519E+12
February 0.000 0.203507E+12
March 0.000 0.163567E+12
April 0.000 0.718858E+11
May 0.000 0.380277E+11
June 0.000 0.310787E+11
July 0.000 0.298021E+11
August 0.000 0.286887E+11
September 0.000 0.313629E+11
October 0.000 0.545845E+11
November 0.000 0.115365E+12
December 0.000 0.255869E+12
     
Annual Sum or Average   0.130226E+13
Minimum of Months 0.000 0.286887E+11
Maximum of Months 0.000 0.278519E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.278519E+12
February 0.000 0.203507E+12
March 0.000 0.163567E+12
April 0.000 0.718858E+11
May 0.000 0.380277E+11
June 0.000 0.310787E+11
July 0.000 0.298021E+11
August 0.000 0.286887E+11
September 0.000 0.313629E+11
October 0.000 0.545845E+11
November 0.000 0.115365E+12
December 0.000 0.255869E+12
     
Annual Sum or Average   0.130226E+13
Minimum of Months 0.000 0.286887E+11
Maximum of Months 0.000 0.278519E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OUTPATIENTHEALTHCARE

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.278519E+12
February 0.000 0.203507E+12
March 0.000 0.163567E+12
April 0.000 0.718858E+11
May 0.000 0.380277E+11
June 0.000 0.310787E+11
July 0.000 0.298021E+11
August 0.000 0.286887E+11
September 0.000 0.313629E+11
October 0.000 0.545845E+11
November 0.000 0.115365E+12
December 0.000 0.255869E+12
     
Annual Sum or Average   0.130226E+13
Minimum of Months 0.000 0.286887E+11
Maximum of Months 0.000 0.278519E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.278519E+12
February 0.000 0.203507E+12
March 0.000 0.163567E+12
April 0.000 0.718858E+11
May 0.000 0.380277E+11
June 0.000 0.310787E+11
July 0.000 0.298021E+11
August 0.000 0.286887E+11
September 0.000 0.313629E+11
October 0.000 0.545845E+11
November 0.000 0.115365E+12
December 0.000 0.255869E+12
     
Annual Sum or Average   0.130226E+13
Minimum of Months 0.000 0.286887E+11
Maximum of Months 0.000 0.278519E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.278519E+12
February 0.000 0.203507E+12
March 0.000 0.163567E+12
April 0.000 0.718858E+11
May 0.000 0.380277E+11
June 0.000 0.310787E+11
July 0.000 0.298021E+11
August 0.000 0.286887E+11
September 0.000 0.313629E+11
October 0.000 0.545845E+11
November 0.000 0.115365E+12
December 0.000 0.255869E+12
     
Annual Sum or Average   0.130226E+13
Minimum of Months 0.000 0.286887E+11
Maximum of Months 0.000 0.278519E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.278519E+12
February 0.000 0.203507E+12
March 0.000 0.163567E+12
April 0.000 0.718858E+11
May 0.000 0.380277E+11
June 0.000 0.310787E+11
July 0.000 0.298021E+11
August 0.000 0.286887E+11
September 0.000 0.313629E+11
October 0.000 0.545845E+11
November 0.000 0.115365E+12
December 0.000 0.255869E+12
     
Annual Sum or Average   0.130226E+13
Minimum of Months 0.000 0.286887E+11
Maximum of Months 0.000 0.278519E+12



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB [] HEATING:GAS [J]
January 0.000 0.278519E+12
February 0.000 0.203507E+12
March 0.000 0.163567E+12
April 0.000 0.718858E+11
May 0.000 0.380277E+11
June 0.000 0.310787E+11
July 0.000 0.298021E+11
August 0.000 0.286887E+11
September 0.000 0.313629E+11
October 0.000 0.545845E+11
November 0.000 0.115365E+12
December 0.000 0.255869E+12
     
Annual Sum or Average   0.130226E+13
Minimum of Months 0.000 0.286887E+11
Maximum of Months 0.000 0.278519E+12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.459560E+09 648.86 27-JAN-13:33 -14.8 -15.8 80543348.93 90.65 27-JAN-13:39 -14.8 -15.8
February 0.508067E+09 616.04 28-FEB-15:05 6.10 1.53 73290379.38 83.39 01-FEB-15:20 -19.6 -20.5
March 0.596017E+09 570.17 31-MAR-14:50 8.30 2.69 86739539.68 78.52 15-MAR-11:20 -15.0 -16.0
April 0.637783E+09 557.93 13-APR-14:10 19.08 7.51 76164172.44 74.41 13-APR-14:20 19.27 7.63
May 0.766445E+09 569.57 18-MAY-17:01 28.13 16.04 81650134.19 73.45 08-MAY-10:20 6.37 4.37
June 0.816036E+09 571.18 30-JUN-17:01 30.92 21.20 81579842.28 73.45 12-JUN-07:49 12.88 12.22
July 0.898186E+09 571.34 21-JUL-17:01 25.00 20.76 75918444.58 73.46 31-JUL-08:09 18.40 14.07
August 0.100072E+10 596.64 25-AUG-14:10 28.30 18.87 85486817.67 75.62 25-AUG-14:09 28.30 18.87
September 0.912120E+09 624.48 01-SEP-14:10 25.68 18.04 76301546.50 79.51 01-SEP-14:30 25.85 17.95
October 0.817264E+09 642.55 19-OCT-14:40 22.03 13.63 79384754.62 82.48 19-OCT-14:50 22.12 13.62
November 0.641956E+09 603.61 17-NOV-13:40 10.40 3.34 78961530.55 81.19 17-NOV-13:39 10.40 3.34
December 0.476922E+09 570.53 08-DEC-13:27 -12.5 -13.4 77563198.09 85.94 20-DEC-14:20 -19.8 -20.4
                     
Annual Sum or Average 0.853108E+10         0.953584E+09        
Minimum of Months 0.459560E+09 557.93   -14.8 -15.8 73290379.38 73.45   -19.8 -20.5
Maximum of Months 0.100072E+10 648.86   30.92 21.20 86739539.68 90.65   28.30 18.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 9433126.61 19.39 06-JAN-05:08 -34.9 -35.0 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 8673172.21 17.55 07-FEB-18:01 2.62 0.30 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 12395589.51 17.66 24-MAR-17:01 -0.7 -0.9 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 19358542.09 17.75 15-APR-14:01 4.13 3.40 0.00 0.00 01-APR-00:10 3.52 0.37
May 26331682.47 18.87 26-MAY-06:08 19.50 15.69 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 29831880.79 19.59 30-JUN-17:01 30.92 21.20 0.00 0.00 01-JUN-00:10 11.35 8.93
July 35933011.04 19.58 21-JUL-17:01 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 35029612.34 19.35 11-AUG-17:01 25.82 19.22 0.00 0.00 01-AUG-00:10 17.07 15.36
September 28132022.20 19.30 01-SEP-06:04 16.10 15.79 0.00 0.00 01-SEP-00:10 19.75 18.15
October 22744276.65 18.64 19-OCT-17:01 18.95 12.57 0.00 0.00 01-OCT-00:10 7.52 6.57
November 15149681.02 18.62 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 10197830.37 17.64 05-DEC-18:01 0.00 -0.0 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.253210E+09         0.00        
Minimum of Months 8673172.21 17.55   -34.9 -35.0 0.00 0.00   -23.1 -23.4
Maximum of Months 35933011.04 19.59   30.92 21.20 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 CAFE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.271912E+10 4035.46 27-JAN-15:04 -14.4 -15.5 0.183355E+10 1836.39 27-JAN-14:00 -14.4 -15.5
February 0.271989E+10 3884.86 03-FEB-07:01 -13.5 -13.8 0.167733E+10 1785.22 01-FEB-07:10 -22.9 -23.3
March 0.329419E+10 3889.47 10-MAR-07:01 -11.8 -12.2 0.199851E+10 1785.31 31-MAR-06:10 -3.8 -4.6
April 0.335145E+10 4001.35 24-APR-06:01 4.40 3.41 0.177229E+10 1785.27 11-APR-06:10 -2.8 -4.6
May 0.385784E+10 4028.24 19-MAY-06:01 14.47 10.08 0.191249E+10 1784.99 15-MAY-06:10 7.52 4.63
June 0.396170E+10 4040.34 09-JUN-06:01 12.12 11.47 0.191441E+10 1784.96 26-JUN-06:10 17.30 15.84
July 0.401672E+10 4045.30 27-JUL-06:01 12.25 11.42 0.178771E+10 1785.01 10-JUL-06:10 11.75 11.33
August 0.442286E+10 4052.80 10-AUG-06:01 15.10 14.70 0.201019E+10 1784.53 02-AUG-06:10 10.97 9.90
September 0.393432E+10 4049.21 08-SEP-06:01 10.68 10.02 0.178468E+10 1784.93 18-SEP-06:10 12.98 12.98
October 0.370907E+10 4043.72 20-OCT-06:01 5.92 5.92 0.183873E+10 1785.11 25-OCT-06:10 -4.2 -4.4
November 0.320748E+10 4024.27 02-NOV-06:01 4.82 3.20 0.180989E+10 1785.13 16-NOV-07:10 -1.8 -3.2
December 0.270068E+10 3902.50 07-DEC-07:01 -7.8 -7.9 0.177624E+10 1785.27 13-DEC-07:10 -25.1 -25.4
                     
Annual Sum or Average 0.418953E+11         0.221160E+11        
Minimum of Months 0.270068E+10 3884.86   -14.4 -15.5 0.167733E+10 1784.53   -25.1 -25.4
Maximum of Months 0.442286E+10 4052.80   15.10 14.70 0.201019E+10 1836.39   17.30 15.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 CLEAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.922085E+09 630.65 27-JAN-15:04 -14.4 -15.5 0.101955E+09 100.43 12-JAN-16:00 -21.1 -21.7
February 0.863474E+09 622.65 03-FEB-09:54 -11.7 -12.2 92569202.74 100.23 16-FEB-17:00 -16.1 -17.1
March 0.105642E+10 627.51 15-MAR-12:34 -12.8 -14.1 0.107659E+09 99.21 15-MAR-11:00 -13.9 -15.1
April 0.110221E+10 601.26 05-APR-09:10 -6.5 -8.8 91475435.24 95.14 05-APR-07:19 -10.8 -11.7
May 0.117763E+10 587.61 18-MAY-17:01 28.13 16.04 96762681.34 86.29 05-MAY-16:00 17.80 8.50
June 0.116961E+10 587.96 30-JUN-17:01 30.92 21.20 96367868.92 85.67 05-JUN-08:39 17.43 13.05
July 0.117462E+10 587.88 21-JUL-17:01 25.00 20.76 89365881.43 85.67 05-JUL-07:00 21.10 20.27
August 0.121912E+10 587.98 25-AUG-17:01 27.52 19.43 0.100515E+09 85.66 21-AUG-08:39 18.87 16.93
September 0.114723E+10 599.99 15-SEP-06:04 5.87 5.35 89508946.47 85.66 19-SEP-07:10 15.68 15.68
October 0.113973E+10 598.07 13-OCT-17:08 1.10 -0.3 93482911.92 86.67 30-OCT-07:19 -8.5 -8.9
November 0.102497E+10 605.07 30-NOV-18:09 1.10 -0.6 94631295.29 96.37 29-NOV-09:20 -13.3 -13.7
December 0.943694E+09 631.43 15-DEC-17:57 -8.3 -8.6 98960795.22 100.10 14-DEC-17:00 -15.0 -15.9
                     
Annual Sum or Average 0.129408E+11         0.115325E+10        
Minimum of Months 0.863474E+09 587.61   -14.4 -15.5 89365881.43 85.66   -21.1 -21.7
Maximum of Months 0.121912E+10 631.43   30.92 21.20 0.107659E+09 100.43   21.10 20.27



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.102149E+10 760.93 27-JAN-15:04 -14.4 -15.5 0.129383E+09 128.32 27-JAN-17:00 -17.8 -18.3
February 0.965902E+09 748.51 10-FEB-17:40 -13.5 -14.6 0.117770E+09 127.90 16-FEB-17:00 -16.1 -17.1
March 0.117772E+10 754.28 15-MAR-12:34 -12.8 -14.1 0.137381E+09 126.21 15-MAR-11:00 -13.9 -15.1
April 0.120687E+10 718.36 05-APR-09:10 -6.5 -8.8 0.118225E+09 119.61 05-APR-07:19 -10.8 -11.7
May 0.128999E+10 722.93 18-MAY-17:01 28.13 16.04 0.125658E+09 112.18 30-MAY-09:39 11.10 8.71
June 0.128642E+10 723.42 30-JUN-17:01 30.92 21.20 0.125182E+09 112.18 07-JUN-06:00 19.40 11.28
July 0.129459E+10 723.54 28-JUL-17:01 28.90 20.84 0.116108E+09 112.20 31-JUL-07:49 18.12 14.38
August 0.135679E+10 723.62 25-AUG-17:01 27.52 19.43 0.130643E+09 112.18 01-AUG-07:00 16.70 15.64
September 0.126391E+10 722.26 01-SEP-17:01 24.32 17.90 0.116244E+09 112.19 05-SEP-08:39 11.83 8.50
October 0.124600E+10 722.26 19-OCT-17:01 18.95 12.57 0.121314E+09 112.19 16-OCT-07:49 5.60 3.78
November 0.112667E+10 723.50 30-NOV-18:09 1.10 -0.6 0.122158E+09 121.67 29-NOV-09:20 -13.3 -13.7
December 0.105443E+10 760.08 15-DEC-17:57 -8.3 -8.6 0.125586E+09 127.87 14-DEC-17:00 -15.0 -15.9
                     
Annual Sum or Average 0.142908E+11         0.148565E+10        
Minimum of Months 0.965902E+09 718.36   -14.4 -15.5 0.116108E+09 112.18   -17.8 -18.3
Maximum of Months 0.135679E+10 760.93   30.92 21.20 0.137381E+09 128.32   19.40 15.64



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.255688E+09 486.75 20-JAN-07:01 -7.3 -7.9 23350765.23 26.78 11-JAN-07:10 -27.1 -27.3
February 0.250587E+09 491.71 03-FEB-07:01 -13.5 -13.8 21392714.22 26.78 02-FEB-07:10 -25.0 -25.3
March 0.293731E+09 491.39 10-MAR-07:01 -11.8 -12.2 25492491.51 26.78 16-MAR-06:10 -22.9 -23.2
April 0.267142E+09 485.77 06-APR-06:01 -5.5 -6.2 22330197.97 26.78 06-APR-06:10 -5.5 -6.2
May 0.276070E+09 456.73 05-MAY-06:01 3.67 0.56 23744277.67 25.40 15-MAY-12:09 19.12 12.74
June 0.271932E+09 440.09 09-JUN-14:02 13.98 12.87 23694932.82 25.40 07-JUN-12:09 21.78 13.43
July 0.269236E+09 315.77 17-JUL-14:03 19.40 14.64 21943879.90 25.40 10-JUL-12:09 24.08 16.50
August 0.284489E+09 428.26 17-AUG-14:02 10.68 9.93 24739760.69 25.40 03-AUG-14:09 21.60 17.56
September 0.268459E+09 424.24 20-SEP-14:02 9.08 7.57 21991141.86 25.40 13-SEP-12:09 19.08 13.19
October 0.268298E+09 478.59 27-OCT-06:01 2.20 1.99 22902850.90 25.44 06-OCT-06:10 -3.6 -4.0
November 0.253842E+09 490.55 10-NOV-07:01 -8.4 -9.4 22954661.74 26.78 29-NOV-07:10 -18.4 -18.6
December 0.270608E+09 492.52 07-DEC-07:01 -7.8 -7.9 22787044.24 26.78 13-DEC-07:10 -25.1 -25.4
                     
Annual Sum or Average 0.323008E+10         0.277325E+09        
Minimum of Months 0.250587E+09 315.77   -13.5 -13.8 21392714.22 25.40   -27.1 -27.3
Maximum of Months 0.293731E+09 492.52   19.40 14.64 25492491.51 26.78   24.08 17.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 2046297.44 36.51 19-JAN-15:05 -2.8 -3.5 6695577.79 7.65 02-JAN-17:49 -14.1 -14.5
February 3589356.29 36.52 07-FEB-15:05 5.50 1.59 6196404.29 7.65 22-FEB-08:50 -6.8 -7.6
March 6293374.48 36.66 30-MAR-14:05 1.28 -0.5 7476606.73 7.65 23-MAR-06:49 -18.4 -18.7
April 21686554.35 36.71 24-APR-12:05 6.20 3.48 6724803.55 7.86 14-APR-14:09 15.92 6.99
May 61581913.38 84.32 25-MAY-14:05 27.98 19.40 7551746.56 9.07 18-MAY-14:09 28.57 16.70
June 83015038.17 124.68 30-JUN-14:05 31.28 23.88 7846413.05 9.07 07-JUN-14:09 22.20 14.32
July 0.101713E+09 135.31 21-JUL-14:05 28.98 22.56 7582074.88 9.07 17-JUL-14:09 19.40 14.64
August 0.106496E+09 135.14 09-AUG-14:05 27.30 21.52 8538174.29 9.07 14-AUG-14:09 19.40 16.26
September 84600134.39 130.24 18-SEP-14:02 19.40 16.89 7315297.29 9.07 15-SEP-12:09 17.48 11.51
October 60232619.94 81.58 20-OCT-14:05 18.90 10.05 7217085.03 9.07 20-OCT-14:09 18.90 10.05
November 27811585.91 53.17 01-NOV-14:02 17.88 13.28 6955437.11 8.75 01-NOV-14:09 17.88 13.28
December 5250714.57 36.64 05-DEC-15:05 -0.6 -0.6 6611249.12 7.65 21-DEC-13:39 -17.8 -18.5
                     
Annual Sum or Average 0.564317E+09         86710869.68        
Minimum of Months 2046297.44 36.51   -2.8 -3.5 6196404.29 7.65   -18.4 -18.7
Maximum of Months 0.106496E+09 135.31   31.28 23.88 8538174.29 9.07   28.57 16.70



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.299122E+09 595.19 20-JAN-07:01 -7.3 -7.9 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.284404E+09 592.65 03-FEB-07:01 -13.5 -13.8 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.346999E+09 592.25 10-MAR-07:01 -11.8 -12.2 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.382286E+09 596.61 14-APR-06:01 2.07 1.49 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.467659E+09 614.34 19-MAY-06:01 14.47 10.08 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.508293E+09 617.36 09-JUN-06:01 12.12 11.47 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.545323E+09 618.23 27-JUL-06:01 12.25 11.42 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.582093E+09 618.74 25-AUG-06:01 9.05 8.95 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.496938E+09 617.62 08-SEP-06:01 10.68 10.02 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.449777E+09 616.04 20-OCT-06:01 5.92 5.92 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.376585E+09 615.40 02-NOV-06:01 4.82 3.20 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.319721E+09 596.73 07-DEC-07:01 -7.8 -7.9 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.505920E+10         0.00        
Minimum of Months 0.284404E+09 592.25   -13.5 -13.8 0.00 0.00   -23.1 -23.4
Maximum of Months 0.582093E+09 618.74   14.47 11.47 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.266184E+10 3067.86 20-JAN-17:05 -7.5 -8.5 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.248052E+10 3094.48 03-FEB-17:55 -7.8 -8.8 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.296491E+10 2960.87 31-MAR-17:00 8.90 3.27 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.292062E+10 3027.60 21-APR-17:00 12.20 3.28 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.339227E+10 3198.43 25-MAY-17:00 29.20 19.29 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.353611E+10 3264.92 29-JUN-17:00 34.40 23.31 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.357887E+10 3280.04 20-JUL-17:00 28.30 21.39 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.389660E+10 3322.38 25-AUG-17:00 27.80 19.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.350603E+10 3313.48 01-SEP-17:00 24.40 17.92 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.341226E+10 3211.52 19-OCT-17:00 19.40 12.77 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.309350E+10 3089.20 01-NOV-17:00 16.70 12.78 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.276666E+10 3112.70 15-DEC-17:53 -8.3 -8.6 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.382102E+11         0.00        
Minimum of Months 0.248052E+10 2960.87   -8.3 -8.8 0.00 0.00   -23.1 -23.4
Maximum of Months 0.389660E+10 3322.38   34.40 23.31 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.137870E+09 236.29 20-JAN-07:01 -7.3 -7.9 10085268.52 11.48 11-JAN-07:10 -27.1 -27.3
February 0.136285E+09 236.35 03-FEB-07:01 -13.5 -13.8 9235375.78 11.48 01-FEB-07:10 -22.9 -23.3
March 0.161828E+09 236.27 10-MAR-07:01 -11.8 -12.2 11011639.77 11.48 07-MAR-07:10 -20.8 -21.1
April 0.148089E+09 233.28 06-APR-06:01 -5.5 -6.2 9687727.35 11.48 05-APR-06:10 -13.5 -14.0
May 0.151835E+09 232.67 12-MAY-06:01 6.88 4.77 10336944.62 11.11 05-MAY-06:10 3.67 0.56
June 0.149362E+09 231.42 09-JUN-06:01 12.12 11.47 10307761.14 10.88 07-JUN-12:09 21.78 13.43
July 0.146819E+09 231.18 28-JUL-06:01 12.85 12.85 9564698.33 10.88 27-JUL-12:09 17.85 14.76
August 0.156751E+09 231.88 25-AUG-06:01 9.05 8.95 10758766.77 10.88 03-AUG-14:09 21.60 17.56
September 0.147279E+09 233.64 15-SEP-06:01 5.87 5.35 9577617.98 10.99 15-SEP-06:10 5.87 5.35
October 0.148367E+09 237.21 27-OCT-06:01 2.20 1.99 9959003.14 11.26 06-OCT-06:10 -3.6 -4.0
November 0.141796E+09 235.69 10-NOV-07:01 -8.4 -9.4 9940236.24 11.48 10-NOV-07:10 -8.4 -9.4
December 0.147428E+09 236.50 07-DEC-07:01 -7.8 -7.9 9837891.67 11.48 21-DEC-07:10 -27.9 -28.1
                     
Annual Sum or Average 0.177371E+10         0.120303E+09        
Minimum of Months 0.136285E+09 231.18   -13.5 -13.8 9235375.78 10.88   -27.9 -28.1
Maximum of Months 0.161828E+09 237.21   12.85 12.85 11011639.77 11.48   21.78 17.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 IT HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 87022432.25 98.39 06-JAN-06:20 -34.6 -34.7 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 85617761.65 89.62 23-FEB-10:50 -6.8 -7.9 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.110965E+09 90.45 09-MAR-07:03 -2.4 -3.5 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.136936E+09 93.31 14-APR-08:43 10.95 5.54 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.157745E+09 95.92 26-MAY-06:05 19.50 15.69 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.158436E+09 98.35 30-JUN-06:04 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.163683E+09 98.35 21-JUL-06:05 19.27 18.71 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.163998E+09 97.05 11-AUG-06:03 14.18 13.74 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.156468E+09 96.66 01-SEP-06:04 16.10 15.79 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.149251E+09 95.58 27-OCT-06:02 2.20 1.99 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.118321E+09 92.67 01-NOV-11:10 16.28 12.38 0.00 0.00 01-NOV-00:10 3.60 0.50
December 92212797.16 87.77 27-DEC-13:30 -5.8 -6.3 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.158066E+10         0.00        
Minimum of Months 85617761.65 87.77   -34.6 -34.7 0.00 0.00   -23.1 -23.4
Maximum of Months 0.163998E+09 98.39   26.60 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.105665E+09 248.95 20-JAN-15:02 -5.1 -6.8 18577515.04 22.47 12-JAN-15:09 -18.9 -19.7
February 94796707.29 332.06 10-FEB-15:02 -11.6 -13.0 17401219.45 22.58 03-FEB-15:09 -3.9 -5.8
March 0.119651E+09 338.32 03-MAR-15:02 -2.9 -3.5 20916609.98 22.58 03-MAR-15:09 -2.9 -3.5
April 0.147589E+09 232.12 06-APR-14:03 4.18 -1.1 18178234.18 22.58 28-APR-14:09 4.40 0.00
May 0.174823E+09 265.36 12-MAY-14:03 13.98 8.07 19605679.86 22.58 17-MAY-14:09 26.20 16.18
June 0.175915E+09 334.32 22-JUN-14:02 17.88 17.40 20060858.37 22.58 07-JUN-14:09 22.20 14.32
July 0.180616E+09 233.63 21-JUL-14:05 28.98 22.56 18831376.03 22.58 18-JUL-14:09 21.02 14.86
August 0.184096E+09 331.00 17-AUG-14:02 10.68 9.93 21312709.77 22.58 01-AUG-14:09 19.60 13.96
September 0.170702E+09 318.19 20-SEP-14:02 9.08 7.57 18476933.49 22.58 21-SEP-12:09 10.00 7.76
October 0.163165E+09 324.95 27-OCT-14:02 5.68 5.08 18767690.28 22.58 06-OCT-12:09 5.60 4.79
November 0.126737E+09 324.51 03-NOV-14:02 1.02 -1.6 18897065.75 22.58 09-NOV-15:09 2.02 -3.0
December 0.103788E+09 345.79 15-DEC-15:02 -7.8 -8.3 18631692.42 22.58 07-DEC-15:09 -8.3 -8.4
                     
Annual Sum or Average 0.174754E+10         0.229658E+09        
Minimum of Months 94796707.29 232.12   -11.6 -13.0 17401219.45 22.47   -18.9 -19.7
Maximum of Months 0.184096E+09 345.79   28.98 22.56 21312709.77 22.58   26.20 16.18



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 LOBBY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.994916E+09 1404.68 27-JAN-15:47 -14.4 -15.5 0.250039E+09 237.15 12-JAN-13:20 -19.2 -19.8
February 0.108097E+10 1700.23 08-FEB-16:30 3.85 -0.8 0.233302E+09 237.15 01-FEB-13:20 -19.8 -20.6
March 0.146920E+10 2093.87 31-MAR-17:00 8.90 3.27 0.282833E+09 237.15 15-MAR-12:20 -13.3 -14.6
April 0.186306E+10 2612.00 21-APR-17:00 12.20 3.28 0.254524E+09 240.04 14-APR-06:10 2.07 1.49
May 0.249942E+10 3637.29 19-MAY-06:01 14.47 10.08 0.279676E+09 264.40 26-MAY-06:10 19.50 15.69
June 0.269743E+10 3689.44 30-JUN-06:01 26.60 21.93 0.281336E+09 264.41 29-JUN-06:10 23.17 19.91
July 0.292405E+10 3682.63 07-JUL-06:01 14.68 12.60 0.264010E+09 264.41 21-JUL-06:10 19.27 18.71
August 0.300532E+10 3712.81 10-AUG-06:01 15.10 14.70 0.295133E+09 264.41 10-AUG-06:10 15.10 14.70
September 0.251503E+10 3644.14 01-SEP-06:01 16.10 15.79 0.259899E+09 260.61 01-SEP-06:10 16.10 15.79
October 0.213032E+10 3529.23 20-OCT-06:01 5.92 5.92 0.264610E+09 250.15 20-OCT-06:10 5.92 5.92
November 0.155968E+10 1773.57 17-NOV-15:40 10.20 3.26 0.257661E+09 239.89 10-NOV-07:10 -8.4 -9.4
December 0.109031E+10 1237.68 08-DEC-15:30 -10.9 -12.0 0.246724E+09 237.15 01-DEC-08:30 -21.3 -21.4
                     
Annual Sum or Average 0.238297E+11         0.316975E+10        
Minimum of Months 0.994916E+09 1237.68   -14.4 -15.5 0.233302E+09 237.15   -21.3 -21.4
Maximum of Months 0.300532E+10 3712.81   26.60 21.93 0.295133E+09 264.41   23.17 19.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.340869E+09 722.78 20-JAN-07:01 -7.3 -7.9 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.354742E+09 733.18 03-FEB-07:01 -13.5 -13.8 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.439847E+09 739.35 24-MAR-06:01 -5.8 -7.3 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.475286E+09 745.81 14-APR-06:01 2.07 1.49 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.558447E+09 775.57 19-MAY-06:01 14.47 10.08 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.580348E+09 776.82 30-JUN-06:01 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.609743E+09 778.60 27-JUL-06:01 12.25 11.42 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.647109E+09 779.88 10-AUG-06:01 15.10 14.70 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.573951E+09 777.56 08-SEP-06:01 10.68 10.02 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.519437E+09 776.67 20-OCT-06:01 5.92 5.92 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.419192E+09 751.85 10-NOV-07:01 -8.4 -9.4 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.366158E+09 740.18 15-DEC-07:01 -13.4 -14.1 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.588513E+10         0.00        
Minimum of Months 0.340869E+09 722.78   -13.5 -14.1 0.00 0.00   -23.1 -23.4
Maximum of Months 0.647109E+09 779.88   26.60 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.235107E+09 386.70 18-JAN-18:01 -2.9 -3.2 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.232780E+09 402.75 08-FEB-18:09 0.82 -2.4 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.287255E+09 400.46 23-MAR-17:08 0.40 -3.4 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.353300E+09 394.32 27-APR-17:05 3.80 -0.2 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.504119E+09 418.40 18-MAY-17:01 28.13 16.04 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.558023E+09 420.30 30-JUN-17:01 30.92 21.20 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.639672E+09 420.41 21-JUL-17:01 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.674472E+09 421.27 25-AUG-17:01 27.52 19.43 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.593335E+09 420.77 01-SEP-17:01 24.32 17.90 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.510557E+09 418.34 19-OCT-17:01 18.95 12.57 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.385276E+09 413.54 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.271942E+09 390.84 05-DEC-18:01 0.00 -0.0 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.524584E+10         0.00        
Minimum of Months 0.232780E+09 386.70   -2.9 -3.4 0.00 0.00   -23.1 -23.4
Maximum of Months 0.674472E+09 421.27   30.92 21.20 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.191609E+10 3145.10 20-JAN-07:01 -7.3 -7.9 0.426445E+09 420.86 25-JAN-07:10 -25.6 -25.8
February 0.188610E+10 3132.22 03-FEB-07:01 -13.5 -13.8 0.391169E+09 420.86 01-FEB-07:10 -22.9 -23.3
March 0.234634E+10 3135.28 10-MAR-07:01 -11.8 -12.2 0.468326E+09 420.86 31-MAR-06:10 -3.8 -4.6
April 0.245159E+10 3206.02 18-APR-06:01 12.38 7.00 0.415889E+09 420.86 11-APR-06:10 -2.8 -4.6
May 0.290942E+10 3233.95 19-MAY-06:01 14.47 10.08 0.449308E+09 420.85 01-MAY-06:10 -3.5 -5.7
June 0.305425E+10 3245.93 09-JUN-06:01 12.12 11.47 0.450242E+09 420.86 05-JUN-06:10 14.08 10.93
July 0.308095E+10 3247.67 27-JUL-06:01 12.25 11.42 0.419756E+09 420.86 10-JUL-06:10 11.75 11.33
August 0.331308E+10 3254.11 10-AUG-06:01 15.10 14.70 0.471064E+09 420.85 07-AUG-06:10 13.40 12.73
September 0.294856E+10 3340.26 13-SEP-05:01 3.98 3.71 0.418301E+09 420.85 11-SEP-06:10 11.78 10.17
October 0.279533E+10 3315.53 27-OCT-05:01 2.70 2.44 0.431922E+09 420.86 25-OCT-06:10 -4.2 -4.4
November 0.243132E+10 3243.64 02-NOV-06:01 4.82 3.20 0.426867E+09 420.86 16-NOV-07:10 -1.8 -3.2
December 0.207570E+10 3147.49 07-DEC-07:01 -7.8 -7.9 0.417107E+09 420.86 19-DEC-07:10 -25.8 -26.1
                     
Annual Sum or Average 0.312087E+11         0.518640E+10        
Minimum of Months 0.188610E+10 3132.22   -13.5 -13.8 0.391169E+09 420.85   -25.8 -26.1
Maximum of Months 0.331308E+10 3340.26   15.10 14.70 0.471064E+09 420.86   14.08 12.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.392116E+09 801.81 27-JAN-07:01 -22.7 -22.9 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.388129E+09 1071.44 03-FEB-07:01 -13.5 -13.8 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.475829E+09 1074.75 10-MAR-07:01 -11.8 -12.2 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.505143E+09 1046.63 07-APR-06:01 -5.7 -7.0 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.565430E+09 341.18 05-MAY-17:00 17.80 8.50 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.562638E+09 349.71 30-JUN-17:00 31.10 21.38 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.580253E+09 348.88 21-JUL-16:57 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.591867E+09 347.65 25-AUG-17:00 27.80 19.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.557835E+09 345.68 15-SEP-17:00 18.30 13.47 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.535286E+09 432.20 06-OCT-06:01 -3.6 -4.0 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.449829E+09 1060.98 10-NOV-07:01 -8.4 -9.4 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.423300E+09 1081.32 15-DEC-07:01 -13.4 -14.1 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.602766E+10         0.00        
Minimum of Months 0.388129E+09 341.18   -22.7 -22.9 0.00 0.00   -23.1 -23.4
Maximum of Months 0.591867E+09 1081.32   31.10 21.38 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.124488E+10 1744.35 20-JAN-07:01 -7.3 -7.9 0.235466E+09 229.56 06-JAN-07:10 -35.0 -35.1
February 0.118865E+10 1739.65 03-FEB-07:01 -13.5 -13.8 0.215387E+09 229.56 06-FEB-07:10 -20.7 -20.9
March 0.144110E+10 1740.21 10-MAR-07:01 -11.8 -12.2 0.257008E+09 229.56 31-MAR-06:10 -3.8 -4.6
April 0.140189E+10 1774.50 18-APR-06:01 12.38 7.00 0.227170E+09 229.56 11-APR-06:10 -2.8 -4.6
May 0.154455E+10 1788.25 19-MAY-06:01 14.47 10.08 0.244016E+09 229.56 18-MAY-06:10 15.50 11.62
June 0.157440E+10 1795.78 09-JUN-06:01 12.12 11.47 0.243958E+09 229.55 01-JUN-06:10 15.28 11.27
July 0.155520E+10 1796.11 27-JUL-06:01 12.25 11.42 0.226954E+09 229.55 06-JUL-06:10 15.78 13.13
August 0.166580E+10 1797.49 10-AUG-06:01 15.10 14.70 0.254785E+09 229.55 08-AUG-06:10 16.88 15.17
September 0.150237E+10 1795.81 29-SEP-06:01 7.30 7.25 0.226418E+09 229.55 06-SEP-06:10 2.38 2.13
October 0.147199E+10 1795.97 18-OCT-06:01 1.88 1.60 0.234479E+09 229.56 25-OCT-06:10 -4.2 -4.4
November 0.135682E+10 1794.70 02-NOV-06:01 4.82 3.20 0.232846E+09 229.56 16-NOV-07:10 -1.8 -3.2
December 0.129457E+10 1745.21 07-DEC-07:01 -7.8 -7.9 0.229694E+09 229.56 21-DEC-07:10 -27.9 -28.1
                     
Annual Sum or Average 0.172422E+11         0.282818E+10        
Minimum of Months 0.118865E+10 1739.65   -13.5 -13.8 0.215387E+09 229.55   -35.0 -35.1
Maximum of Months 0.166580E+10 1797.49   15.10 14.70 0.257008E+09 229.56   16.88 15.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 MED GAS

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 175022.15 61.91 18-JAN-18:01 -2.9 -3.2 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 286393.18 62.28 07-FEB-18:01 2.62 0.30 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 464945.80 62.08 28-MAR-17:01 7.20 3.38 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 1576604.12 62.35 14-APR-17:01 14.03 6.65 0.00 0.00 01-APR-00:10 3.52 0.37
May 11981799.91 67.84 18-MAY-17:01 28.13 16.04 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 31328217.53 68.56 29-JUN-17:01 34.13 23.48 0.00 0.00 01-JUN-00:10 11.35 8.93
July 71370404.16 70.98 21-JUL-06:05 19.27 18.71 0.00 0.00 01-JUL-00:10 15.83 13.56
August 82501172.82 71.79 09-AUG-06:05 18.98 17.80 0.00 0.00 01-AUG-00:10 17.07 15.36
September 45603935.04 68.50 01-SEP-17:01 24.32 17.90 0.00 0.00 01-SEP-00:10 19.75 18.15
October 14034747.64 67.73 19-OCT-17:01 18.95 12.57 0.00 0.00 01-OCT-00:10 7.52 6.57
November 3127060.28 67.42 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 365913.25 62.97 05-DEC-18:01 0.00 -0.0 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.262816E+09         0.00        
Minimum of Months 175022.15 61.91   -2.9 -3.2 0.00 0.00   -23.1 -23.4
Maximum of Months 82501172.82 71.79   34.13 23.48 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.169789E+10 1895.93 20-JAN-07:01 -7.3 -7.9 0.152527E+09 142.84 27-JAN-07:10 -22.7 -22.9
February 0.160491E+10 1888.90 03-FEB-07:01 -13.5 -13.8 0.138861E+09 142.84 24-FEB-07:10 -23.9 -24.2
March 0.196035E+10 1902.12 30-MAR-05:01 -1.9 -2.1 0.163995E+09 142.84 31-MAR-06:10 -3.8 -4.6
April 0.197462E+10 2136.81 14-APR-05:01 2.12 1.44 0.145317E+09 142.84 10-APR-06:10 -1.9 -3.2
May 0.228989E+10 2216.53 26-MAY-05:01 19.40 15.68 0.156964E+09 142.83 18-MAY-06:10 15.50 11.62
June 0.237678E+10 2230.20 29-JUN-05:01 22.30 19.60 0.157060E+09 142.83 22-JUN-06:10 15.97 14.47
July 0.239878E+10 2231.88 21-JUL-05:01 17.98 17.55 0.146715E+09 142.83 18-JUL-06:10 11.23 10.70
August 0.254075E+10 2231.65 09-AUG-05:01 18.40 17.29 0.164216E+09 142.83 11-AUG-06:10 14.18 13.74
September 0.225677E+10 2228.06 01-SEP-05:01 15.68 15.63 0.146019E+09 142.83 11-SEP-06:10 11.78 10.17
October 0.216043E+10 2182.91 27-OCT-05:01 2.70 2.44 0.150611E+09 142.83 25-OCT-06:10 -4.2 -4.4
November 0.193493E+10 2111.40 14-NOV-06:01 2.80 1.20 0.148751E+09 142.83 16-NOV-07:10 -1.8 -3.2
December 0.174143E+10 1912.74 06-DEC-06:01 -0.8 -0.8 0.148327E+09 142.84 21-DEC-07:10 -27.9 -28.1
                     
Annual Sum or Average 0.249375E+11         0.181936E+10        
Minimum of Months 0.160491E+10 1888.90   -13.5 -13.8 0.138861E+09 142.83   -27.9 -28.1
Maximum of Months 0.254075E+10 2231.88   22.30 19.60 0.164216E+09 142.84   15.97 14.47



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.133790E+09 114.47 30-JAN-07:02 -4.4 -4.9 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.129815E+09 114.29 10-FEB-18:00 -13.9 -15.0 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.162462E+09 121.87 31-MAR-17:00 8.90 3.27 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.194569E+09 139.25 14-APR-17:00 14.40 6.71 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.241226E+09 354.61 19-MAY-06:01 14.47 10.08 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.259251E+09 430.79 30-JUN-06:01 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.278934E+09 426.50 14-JUL-06:02 17.57 17.07 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.294235E+09 432.78 10-AUG-06:01 15.10 14.70 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.257246E+09 430.59 01-SEP-06:01 16.10 15.79 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.228866E+09 421.59 27-OCT-06:01 2.20 1.99 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.178792E+09 340.14 10-NOV-07:01 -8.4 -9.4 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.143377E+09 271.09 01-DEC-07:01 -20.3 -20.5 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.250256E+10         0.00        
Minimum of Months 0.129815E+09 114.29   -20.3 -20.5 0.00 0.00   -23.1 -23.4
Maximum of Months 0.294235E+09 432.78   26.60 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.534885E+10 5068.04 19-JAN-06:01 -3.3 -3.7 0.422832E+09 392.03 12-JAN-16:00 -21.1 -21.7
February 0.507983E+10 5145.44 21-FEB-06:01 2.80 1.20 0.378853E+09 392.17 16-FEB-17:00 -16.1 -17.1
March 0.611502E+10 5112.44 28-MAR-05:01 1.70 0.49 0.439062E+09 387.86 15-MAR-11:00 -13.9 -15.1
April 0.587066E+10 5516.43 14-APR-05:01 2.12 1.44 0.384687E+09 379.38 05-APR-06:30 -12.8 -13.4
May 0.634837E+10 5720.69 26-MAY-05:01 19.40 15.68 0.414418E+09 374.09 18-MAY-06:10 15.50 11.62
June 0.636018E+10 5731.22 29-JUN-05:01 22.30 19.60 0.413840E+09 374.08 22-JUN-06:10 15.97 14.47
July 0.629570E+10 5734.35 21-JUL-05:01 17.98 17.55 0.385916E+09 374.09 18-JUL-06:10 11.23 10.70
August 0.668790E+10 5734.12 10-AUG-05:01 15.50 14.84 0.431808E+09 374.08 11-AUG-06:10 14.18 13.74
September 0.610745E+10 5725.95 01-SEP-05:01 15.68 15.63 0.384797E+09 374.08 11-SEP-06:10 11.78 10.17
October 0.610674E+10 5710.51 20-OCT-05:01 7.52 7.52 0.397570E+09 374.45 25-OCT-06:10 -4.2 -4.4
November 0.575642E+10 5674.57 01-NOV-05:01 10.60 9.36 0.393389E+09 381.79 29-NOV-09:09 -13.8 -14.3
December 0.546531E+10 5096.44 28-DEC-06:01 -2.3 -2.7 0.405913E+09 392.86 01-DEC-17:19 -20.0 -20.5
                     
Annual Sum or Average 0.715424E+11         0.485309E+10        
Minimum of Months 0.507983E+10 5068.04   -3.3 -3.7 0.378853E+09 374.08   -21.1 -21.7
Maximum of Months 0.668790E+10 5734.35   22.30 19.60 0.439062E+09 392.86   15.97 14.47



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 37731512.42 106.07 18-JAN-18:01 -2.9 -3.2 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 38033715.48 106.52 07-FEB-18:01 2.62 0.30 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 52619770.47 106.87 24-MAR-17:01 -0.7 -0.9 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 86980014.90 106.90 15-APR-14:01 4.13 3.40 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.140300E+09 117.44 19-MAY-06:03 14.47 10.08 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.166716E+09 115.44 21-JUN-06:04 14.27 12.49 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.200933E+09 118.94 21-JUL-06:05 19.27 18.71 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.208701E+09 119.12 09-AUG-06:05 18.98 17.80 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.186140E+09 117.51 08-SEP-06:03 10.68 10.02 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.153235E+09 116.65 20-OCT-06:03 5.92 5.92 0.00 0.00 01-OCT-00:10 7.52 6.57
November 96910393.40 113.59 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 49305686.39 107.27 05-DEC-18:01 0.00 -0.0 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.141761E+10         0.00        
Minimum of Months 37731512.42 106.07   -2.9 -3.2 0.00 0.00   -23.1 -23.4
Maximum of Months 0.208701E+09 119.12   19.27 18.71 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.741154E+09 953.36 20-JAN-07:01 -7.3 -7.9 0.160935E+09 154.74 23-JAN-07:10 -22.2 -22.4
February 0.709147E+09 953.17 03-FEB-07:01 -13.5 -13.8 0.147124E+09 154.74 06-FEB-07:10 -20.7 -20.9
March 0.855233E+09 952.93 10-MAR-07:01 -11.8 -12.2 0.174737E+09 154.74 31-MAR-06:10 -3.8 -4.6
April 0.788767E+09 968.76 18-APR-06:01 12.38 7.00 0.153536E+09 154.74 11-APR-06:10 -2.8 -4.6
May 0.824989E+09 974.96 11-MAY-06:01 10.12 7.76 0.164199E+09 154.74 18-MAY-06:10 15.50 11.62
June 0.819586E+09 979.05 09-JUN-06:01 12.12 11.47 0.163799E+09 154.73 01-JUN-06:10 15.28 11.27
July 0.792959E+09 978.73 27-JUL-06:01 12.25 11.42 0.152036E+09 154.73 12-JUL-06:10 17.15 15.15
August 0.856871E+09 979.26 25-AUG-06:01 9.05 8.95 0.170892E+09 154.73 02-AUG-06:10 10.97 9.90
September 0.791330E+09 979.57 29-SEP-06:01 7.30 7.25 0.152173E+09 154.73 07-SEP-06:10 7.25 6.31
October 0.799604E+09 980.50 18-OCT-06:01 1.88 1.60 0.158030E+09 154.74 25-OCT-06:10 -4.2 -4.4
November 0.767134E+09 978.99 02-NOV-06:01 4.82 3.20 0.157500E+09 154.74 16-NOV-07:10 -1.8 -3.2
December 0.764839E+09 954.06 07-DEC-07:01 -7.8 -7.9 0.156696E+09 154.74 21-DEC-07:10 -27.9 -28.1
                     
Annual Sum or Average 0.951161E+10         0.191166E+10        
Minimum of Months 0.709147E+09 952.93   -13.5 -13.8 0.147124E+09 154.73   -27.9 -28.1
Maximum of Months 0.856871E+09 980.50   12.38 11.47 0.174737E+09 154.74   17.15 15.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.425659E+09 673.62 27-JAN-14:07 -14.4 -15.5 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.384644E+09 407.34 28-FEB-16:00 6.10 1.53 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.477316E+09 362.69 22-MAR-06:03 -2.9 -3.5 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.571792E+09 376.56 15-APR-11:04 5.60 5.06 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.660986E+09 397.90 25-MAY-06:04 16.28 13.87 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.663448E+09 393.08 28-JUN-06:05 19.55 18.19 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.680092E+09 392.90 07-JUL-06:04 14.68 12.60 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.684530E+09 393.99 23-AUG-06:04 16.20 15.82 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.651577E+09 394.20 22-SEP-06:03 9.40 9.40 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.624160E+09 410.67 20-OCT-15:50 18.40 9.93 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.517011E+09 520.26 29-NOV-13:40 1.13 -2.0 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.419244E+09 451.74 20-DEC-13:40 -20.6 -21.2 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.676046E+10         0.00        
Minimum of Months 0.384644E+09 362.69   -20.6 -21.2 0.00 0.00   -23.1 -23.4
Maximum of Months 0.684530E+09 673.62   19.55 18.19 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 70019621.76 156.49 20-JAN-07:01 -7.3 -7.9 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 71773656.08 161.82 03-FEB-07:01 -13.5 -13.8 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 87194198.99 161.83 10-MAR-07:01 -11.8 -12.2 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 83731600.35 157.13 06-APR-06:01 -5.5 -6.2 0.00 0.00 01-APR-00:10 3.52 0.37
May 88288570.60 139.43 05-MAY-06:01 3.67 0.56 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 86353266.17 52.81 09-JUN-17:00 15.00 13.26 0.00 0.00 01-JUN-00:10 11.35 8.93
July 88012917.63 52.31 28-JUL-17:00 28.90 20.78 0.00 0.00 01-JUL-00:10 15.83 13.56
August 90614972.01 52.73 25-AUG-17:00 27.80 19.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 86859084.86 103.25 15-SEP-06:01 5.87 5.35 0.00 0.00 01-SEP-00:10 19.75 18.15
October 85303587.27 159.51 27-OCT-06:01 2.20 1.99 0.00 0.00 01-OCT-00:10 7.52 6.57
November 76653782.94 158.85 10-NOV-07:01 -8.4 -9.4 0.00 0.00 01-NOV-00:10 3.60 0.50
December 77475046.36 162.77 15-DEC-07:01 -13.4 -14.1 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.992280E+09         0.00        
Minimum of Months 70019621.76 52.31   -13.5 -14.1 0.00 0.00   -23.1 -23.4
Maximum of Months 90614972.01 162.77   28.90 20.78 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.881266E+09 1299.61 20-JAN-07:01 -7.3 -7.9 0.227158E+09 221.91 25-JAN-07:10 -25.6 -25.8
February 0.845701E+09 1296.87 03-FEB-07:01 -13.5 -13.8 0.207749E+09 221.91 01-FEB-07:10 -22.9 -23.3
March 0.101509E+10 1297.13 10-MAR-07:01 -11.8 -12.2 0.247915E+09 221.91 31-MAR-06:10 -3.8 -4.6
April 0.956709E+09 1297.86 14-APR-06:01 2.07 1.49 0.218434E+09 221.90 12-APR-06:10 -0.8 -2.8
May 0.102045E+10 1331.10 19-MAY-06:01 14.47 10.08 0.233779E+09 221.90 18-MAY-06:10 15.50 11.62
June 0.102364E+10 1336.90 09-JUN-06:01 12.12 11.47 0.233345E+09 221.90 22-JUN-06:10 15.97 14.47
July 0.100097E+10 1336.61 27-JUL-06:01 12.25 11.42 0.216668E+09 221.90 28-JUL-06:10 12.85 12.85
August 0.108288E+10 1337.54 25-AUG-06:01 9.05 8.95 0.243721E+09 221.90 03-AUG-06:10 11.20 10.58
September 0.993127E+09 1337.01 29-SEP-06:01 7.30 7.25 0.216875E+09 221.90 13-SEP-06:10 4.78 4.42
October 0.982976E+09 1337.73 18-OCT-06:01 1.88 1.60 0.224927E+09 221.91 25-OCT-06:10 -4.2 -4.4
November 0.917625E+09 1335.34 02-NOV-06:01 4.82 3.20 0.223854E+09 221.91 16-NOV-07:10 -1.8 -3.2
December 0.903416E+09 1299.98 07-DEC-07:01 -7.8 -7.9 0.221192E+09 221.91 19-DEC-07:10 -25.8 -26.1
                     
Annual Sum or Average 0.116239E+11         0.271562E+10        
Minimum of Months 0.845701E+09 1296.87   -13.5 -13.8 0.207749E+09 221.90   -25.8 -26.1
Maximum of Months 0.108288E+10 1337.73   14.47 11.47 0.247915E+09 221.91   15.97 14.47



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.175815E+09 165.61 28-JAN-15:01 -8.9 -10.3 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.167319E+09 167.46 28-FEB-18:01 3.62 -0.2 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.199304E+09 169.88 24-MAR-17:01 -0.7 -0.9 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.221052E+09 166.01 14-APR-17:01 14.03 6.65 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.241373E+09 172.28 18-MAY-17:01 28.13 16.04 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.243116E+09 173.50 30-JUN-17:01 30.92 21.20 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.248458E+09 173.05 21-JUL-17:01 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.257567E+09 173.74 25-AUG-17:01 27.52 19.43 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.242956E+09 173.78 15-SEP-17:01 18.12 13.44 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.232861E+09 174.83 27-OCT-17:01 5.60 4.79 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.197658E+09 170.46 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.182996E+09 167.51 15-DEC-18:01 -8.4 -8.7 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.261047E+10         0.00        
Minimum of Months 0.167319E+09 165.61   -8.9 -10.3 0.00 0.00   -23.1 -23.4
Maximum of Months 0.257567E+09 174.83   30.92 21.20 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.649108E+09 1463.83 20-JAN-07:01 -7.3 -7.9 88339213.52 102.11 27-JAN-07:10 -22.7 -22.9
February 0.668354E+09 1472.13 03-FEB-07:01 -13.5 -13.8 81424166.38 102.67 24-FEB-07:10 -23.9 -24.2
March 0.843508E+09 1474.63 10-MAR-07:01 -11.8 -12.2 97479789.83 102.67 23-MAR-06:10 -18.8 -19.1
April 0.885826E+09 1465.47 14-APR-06:01 2.07 1.49 86352980.41 102.67 06-APR-06:10 -5.5 -6.2
May 0.101139E+10 1513.31 19-MAY-06:01 14.47 10.08 92861897.91 102.38 19-MAY-06:10 14.47 10.08
June 0.104231E+10 1518.26 30-JUN-06:01 26.60 21.93 92879917.18 102.66 30-JUN-06:10 26.60 21.93
July 0.105913E+10 1519.42 28-JUL-06:01 12.85 12.85 86492424.78 102.66 21-JUL-06:10 19.27 18.71
August 0.112636E+10 1524.36 10-AUG-06:01 15.10 14.70 97142739.75 102.66 11-AUG-06:10 14.18 13.74
September 0.101306E+10 1519.83 01-SEP-06:01 16.10 15.79 86296848.28 102.65 01-SEP-06:10 16.10 15.79
October 0.951175E+09 1518.04 27-OCT-06:02 2.20 1.99 89191298.72 102.66 27-OCT-06:10 2.20 1.99
November 0.812718E+09 1485.68 02-NOV-06:01 4.82 3.20 88332969.55 102.67 10-NOV-07:10 -8.4 -9.4
December 0.716307E+09 1479.06 07-DEC-07:01 -7.8 -7.9 86616824.62 102.67 01-DEC-07:10 -20.3 -20.5
                     
Annual Sum or Average 0.107792E+11         0.107341E+10        
Minimum of Months 0.649108E+09 1463.83   -13.5 -13.8 81424166.38 102.11   -23.9 -24.2
Maximum of Months 0.112636E+10 1524.36   26.60 21.93 97479789.83 102.67   26.60 21.93



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.532156E+10 7646.87 19-JAN-06:01 -3.3 -3.7 0.290045E+09 285.68 27-JAN-14:00 -14.4 -15.5
February 0.523624E+10 8010.37 09-FEB-06:01 -3.2 -4.4 0.258361E+09 277.71 01-FEB-14:20 -19.4 -20.3
March 0.638307E+10 7992.76 30-MAR-05:01 -1.9 -2.1 0.296329E+09 277.50 15-MAR-10:30 -16.7 -17.5
April 0.667549E+10 8041.73 14-APR-05:01 2.12 1.44 0.253773E+09 262.36 05-APR-07:30 -10.3 -11.4
May 0.771004E+10 7940.74 03-MAY-05:01 2.97 0.66 0.271536E+09 258.77 01-MAY-06:10 -3.5 -5.7
June 0.802459E+10 7889.74 30-JUN-05:01 26.20 22.42 0.272050E+09 222.45 30-JUN-13:20 31.50 24.22
July 0.828525E+10 7901.62 14-JUL-05:01 17.20 16.88 0.254723E+09 224.55 21-JUL-13:20 28.50 22.49
August 0.874811E+10 7959.20 09-AUG-05:01 18.40 17.29 0.287160E+09 229.17 25-AUG-13:20 27.57 18.62
September 0.789244E+10 8314.79 14-SEP-05:01 4.32 4.04 0.254176E+09 230.38 01-SEP-13:20 24.80 17.99
October 0.744308E+10 8204.67 27-OCT-05:01 2.70 2.44 0.262947E+09 252.93 30-OCT-06:10 -9.4 -9.8
November 0.645253E+10 8006.03 15-NOV-06:01 -1.4 -1.4 0.264076E+09 272.31 29-NOV-09:50 -11.6 -12.2
December 0.546699E+10 7898.41 28-DEC-06:01 -2.3 -2.7 0.277530E+09 279.40 01-DEC-14:20 -18.1 -18.8
                     
Annual Sum or Average 0.836394E+11         0.324271E+10        
Minimum of Months 0.523624E+10 7646.87   -3.3 -4.4 0.253773E+09 222.45   -19.4 -20.3
Maximum of Months 0.874811E+10 8314.79   26.20 22.42 0.296329E+09 285.68   31.50 24.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.609372E+10 8328.77 19-JAN-06:01 -3.3 -3.7 0.305336E+09 290.28 27-JAN-10:30 -19.1 -19.6
February 0.586300E+10 8379.04 09-FEB-06:01 -3.2 -4.4 0.269508E+09 290.82 10-FEB-10:30 -17.8 -18.3
March 0.725650E+10 8387.60 31-MAR-05:01 -3.0 -3.9 0.303901E+09 297.87 15-MAR-09:50 -18.2 -18.8
April 0.759268E+10 8397.09 14-APR-05:01 2.12 1.44 0.256332E+09 286.06 05-APR-07:30 -10.3 -11.4
May 0.886528E+10 8340.81 03-MAY-05:01 2.97 0.66 0.264852E+09 276.60 01-MAY-06:10 -3.5 -5.7
June 0.912935E+10 8322.57 29-JUN-05:01 22.30 19.60 0.264843E+09 231.12 16-JUN-09:39 20.03 12.07
July 0.923682E+10 8409.09 14-JUL-05:01 17.20 16.88 0.251448E+09 234.17 28-JUL-09:39 24.43 18.79
August 0.944339E+10 8286.41 09-AUG-05:01 18.40 17.29 0.283639E+09 235.93 25-AUG-09:39 22.07 17.42
September 0.875438E+10 8685.10 14-SEP-05:01 4.32 4.04 0.244167E+09 233.26 01-SEP-09:39 21.13 17.71
October 0.817380E+10 8564.04 27-OCT-05:01 2.70 2.44 0.254541E+09 268.55 30-OCT-06:10 -9.4 -9.8
November 0.711975E+10 8371.47 14-NOV-06:01 2.80 1.20 0.264313E+09 286.98 29-NOV-09:20 -13.3 -13.7
December 0.625009E+10 8386.18 28-DEC-06:01 -2.3 -2.7 0.291759E+09 290.34 01-DEC-12:20 -18.8 -19.3
                     
Annual Sum or Average 0.937788E+11         0.325464E+10        
Minimum of Months 0.586300E+10 8286.41   -3.3 -4.4 0.244167E+09 231.12   -19.1 -19.6
Maximum of Months 0.944339E+10 8685.10   22.30 19.60 0.305336E+09 297.87   24.43 18.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.791274E+10 6952.06 27-JAN-15:04 -14.4 -15.5 0.299622E+09 299.29 12-JAN-15:09 -18.9 -19.7
February 0.736619E+10 6914.42 03-FEB-07:01 -13.5 -13.8 0.263557E+09 296.78 16-FEB-16:10 -14.4 -15.4
March 0.877715E+10 6918.22 15-MAR-12:44 -12.5 -13.8 0.296547E+09 295.60 15-MAR-11:20 -15.0 -16.0
April 0.863853E+10 6777.59 05-APR-06:02 -13.5 -14.0 0.246763E+09 283.22 05-APR-06:10 -13.5 -14.0
May 0.927387E+10 6196.79 02-MAY-05:01 0.10 -2.2 0.258925E+09 267.68 01-MAY-06:10 -3.5 -5.7
June 0.924811E+10 5390.99 30-JUN-15:10 32.12 24.52 0.256765E+09 227.29 16-JUN-11:00 21.70 12.53
July 0.923004E+10 5388.55 14-JUL-15:10 27.20 19.92 0.237889E+09 227.27 10-JUL-13:09 25.10 16.23
August 0.965125E+10 5387.47 25-AUG-15:10 28.30 19.22 0.267769E+09 227.33 07-AUG-16:30 24.15 19.93
September 0.897558E+10 6514.63 13-SEP-05:01 3.98 3.71 0.238535E+09 227.28 21-SEP-12:09 10.00 7.76
October 0.895298E+10 6721.73 13-OCT-17:08 1.10 -0.3 0.251385E+09 271.89 30-OCT-06:10 -9.4 -9.8
November 0.836255E+10 6722.34 08-NOV-18:09 1.10 -1.4 0.257981E+09 288.11 29-NOV-09:09 -13.8 -14.3
December 0.800651E+10 6937.92 15-DEC-07:01 -13.4 -14.1 0.285264E+09 296.93 14-DEC-15:09 -16.0 -16.9
                     
Annual Sum or Average 0.104395E+12         0.316100E+10        
Minimum of Months 0.736619E+10 5387.47   -14.4 -15.5 0.237889E+09 227.27   -18.9 -19.7
Maximum of Months 0.965125E+10 6952.06   32.12 24.52 0.299622E+09 299.29   25.10 19.93



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 PACU

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.815645E+09 628.50 27-JAN-15:04 -14.4 -15.5 84760001.87 84.19 27-JAN-17:19 -17.1 -17.7
February 0.768150E+09 610.60 10-FEB-13:37 -13.2 -14.3 76742200.51 83.37 24-FEB-16:19 -18.0 -18.7
March 0.932455E+09 616.91 15-MAR-12:34 -12.8 -14.1 89479222.97 82.55 15-MAR-12:39 -12.8 -14.1
April 0.941999E+09 587.87 05-APR-09:10 -6.5 -8.8 77041557.95 77.08 05-APR-07:30 -10.3 -11.4
May 0.999456E+09 589.53 18-MAY-17:01 28.13 16.04 81890822.24 73.45 08-MAY-08:09 5.93 3.93
June 0.995620E+09 589.98 30-JUN-17:01 30.92 21.20 81587611.81 73.45 19-JUN-07:49 18.30 17.53
July 0.991250E+09 590.06 21-JUL-17:01 25.00 20.76 75658567.00 73.45 17-JUL-08:39 15.00 12.42
August 0.104827E+10 590.08 25-AUG-17:01 27.52 19.43 85132204.69 73.45 14-AUG-11:50 16.97 14.97
September 0.978850E+09 588.84 01-SEP-17:01 24.32 17.90 75759067.97 73.44 18-SEP-07:00 13.90 13.90
October 0.970826E+09 589.24 19-OCT-17:01 18.95 12.57 79078749.26 73.45 16-OCT-07:49 5.60 3.78
November 0.889807E+09 591.35 30-NOV-18:09 1.10 -0.6 79650460.82 79.49 29-NOV-09:50 -11.6 -12.2
December 0.835970E+09 616.35 15-DEC-17:08 -8.1 -8.4 81938311.71 83.64 14-DEC-16:19 -15.6 -16.5
                     
Annual Sum or Average 0.111683E+11         0.968719E+09        
Minimum of Months 0.768150E+09 587.87   -14.4 -15.5 75658567.00 73.44   -18.0 -18.7
Maximum of Months 0.104827E+10 628.50   30.92 21.20 89479222.97 84.19   18.30 17.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.342305E+09 392.56 06-JAN-06:20 -34.6 -34.7 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.335138E+09 356.44 22-FEB-07:02 -8.6 -9.0 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.450727E+09 369.36 22-MAR-06:03 -2.9 -3.5 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.557152E+09 385.34 18-APR-06:02 12.38 7.00 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.654265E+09 397.36 23-MAY-06:03 13.43 10.09 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.649201E+09 447.25 30-JUN-17:00 31.10 21.38 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.673008E+09 407.64 21-JUL-16:57 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.674688E+09 400.54 25-AUG-17:00 27.80 19.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.633724E+09 399.25 26-SEP-06:03 8.80 7.47 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.608482E+09 398.47 03-OCT-06:03 5.00 3.77 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.487212E+09 398.90 01-NOV-06:03 10.78 9.44 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.367490E+09 371.39 06-DEC-07:03 -2.1 -2.1 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.643339E+10         0.00        
Minimum of Months 0.335138E+09 356.44   -34.6 -34.7 0.00 0.00   -23.1 -23.4
Maximum of Months 0.674688E+09 447.25   31.10 21.38 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.509235E+09 929.64 28-JAN-15:01 -8.9 -10.3 64584874.92 64.29 31-JAN-15:00 -19.4 -20.0
February 0.582554E+09 907.22 08-FEB-18:01 0.82 -2.4 59896762.73 64.28 10-FEB-13:09 -13.7 -14.7
March 0.795601E+09 923.60 31-MAR-17:01 8.80 3.19 71047838.30 64.28 14-MAR-10:20 -11.8 -13.3
April 0.100517E+10 951.28 14-APR-17:01 14.03 6.65 62727157.98 64.27 05-APR-06:49 -12.1 -12.7
May 0.125291E+10 1021.58 18-MAY-17:01 28.13 16.04 68245832.97 64.27 03-MAY-15:20 21.03 10.38
June 0.131493E+10 1025.03 30-JUN-17:01 30.92 21.20 68947078.25 64.26 16-JUN-14:09 21.70 11.98
July 0.141711E+10 1023.41 21-JUL-17:01 25.00 20.76 64351382.92 64.27 25-JUL-15:30 20.25 19.32
August 0.146102E+10 1023.81 25-AUG-17:01 27.52 19.43 72539107.36 64.26 04-AUG-11:50 21.52 15.40
September 0.130397E+10 1019.98 01-SEP-17:01 24.32 17.90 63514640.58 64.26 15-SEP-13:30 19.15 12.22
October 0.117116E+10 1015.39 19-OCT-17:01 18.95 12.57 65028954.77 64.25 20-OCT-14:00 18.90 10.05
November 0.921269E+09 992.43 01-NOV-17:01 15.95 12.47 64783783.09 64.28 29-NOV-08:50 -14.7 -15.0
December 0.621931E+09 911.86 15-DEC-18:01 -8.4 -8.7 63611004.98 64.29 01-DEC-15:09 -17.9 -18.7
                     
Annual Sum or Average 0.123568E+11         0.789278E+09        
Minimum of Months 0.509235E+09 907.22   -8.9 -10.3 59896762.73 64.25   -19.4 -20.0
Maximum of Months 0.146102E+10 1025.03   30.92 21.20 72539107.36 64.29   21.70 19.32



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.208029E+10 1720.47 18-JAN-18:01 -2.9 -3.2 0.125179E+09 114.93 30-JAN-12:09 -6.7 -7.3
February 0.195698E+10 1728.92 07-FEB-18:10 2.62 0.30 0.114850E+09 115.05 10-FEB-17:19 -13.2 -14.3
March 0.234368E+10 1738.20 24-MAR-17:01 -0.7 -0.9 0.137182E+09 114.99 03-MAR-10:20 -6.5 -7.4
April 0.243982E+10 1728.17 26-APR-17:01 -0.6 -0.8 0.118963E+09 114.93 03-APR-14:09 2.80 -0.5
May 0.260990E+10 1826.64 18-MAY-17:01 28.13 16.04 0.125939E+09 114.92 01-MAY-14:09 9.42 2.05
June 0.259099E+10 1827.95 30-JUN-17:01 30.92 21.20 0.125462E+09 114.92 14-JUN-11:09 21.38 15.68
July 0.262438E+10 1827.54 21-JUL-17:01 25.00 20.76 0.116067E+09 114.92 20-JUL-09:00 25.00 20.76
August 0.271375E+10 1827.79 25-AUG-17:01 27.52 19.43 0.131016E+09 114.92 16-AUG-10:00 21.10 16.14
September 0.255273E+10 1822.19 01-SEP-17:01 24.32 17.90 0.116389E+09 114.92 01-SEP-10:09 21.97 17.74
October 0.251902E+10 1821.91 27-OCT-17:01 5.60 4.79 0.121774E+09 114.92 24-OCT-12:09 8.90 5.37
November 0.226662E+10 1812.73 01-NOV-17:01 15.95 12.47 0.123183E+09 114.92 27-NOV-10:30 -6.4 -6.9
December 0.215302E+10 1734.73 05-DEC-18:01 0.00 -0.0 0.122237E+09 115.55 15-DEC-15:30 -7.9 -8.3
                     
Annual Sum or Average 0.288512E+11         0.147824E+10        
Minimum of Months 0.195698E+10 1720.47   -2.9 -3.2 0.114850E+09 114.92   -13.2 -14.3
Maximum of Months 0.271375E+10 1827.95   30.92 21.20 0.137182E+09 115.55   25.00 20.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 1469073.81 130.75 21-JAN-15:01 -5.4 -7.2 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 6699704.30 132.00 04-FEB-15:01 7.80 2.57 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 11705589.32 132.22 28-MAR-17:01 7.20 3.38 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 45068920.65 134.23 15-APR-14:01 4.13 3.40 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.117754E+09 145.32 18-MAY-17:01 28.13 16.04 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.150716E+09 150.90 29-JUN-17:01 34.13 23.48 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.205846E+09 146.16 21-JUL-17:01 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.206617E+09 146.25 25-AUG-17:01 27.52 19.43 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.163390E+09 145.95 01-SEP-17:01 24.32 17.90 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.106977E+09 144.27 19-OCT-17:01 18.95 12.57 0.00 0.00 01-OCT-00:10 7.52 6.57
November 40636617.39 141.72 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 5482803.89 131.42 30-DEC-15:01 -3.3 -3.5 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.106236E+10         0.00        
Minimum of Months 1469073.81 130.75   -5.4 -7.2 0.00 0.00   -23.1 -23.4
Maximum of Months 0.206617E+09 150.90   34.13 23.48 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.135946E+10 3247.65 28-JAN-15:01 -8.9 -10.3 0.198574E+09 194.00 18-JAN-08:00 -13.3 -13.6
February 0.138084E+10 3245.19 03-FEB-18:01 -8.1 -9.1 0.181200E+09 193.97 02-FEB-14:09 -15.0 -16.0
March 0.171996E+10 3253.79 30-MAR-17:01 1.70 -0.6 0.215453E+09 194.01 14-MAR-09:09 -14.0 -15.1
April 0.190057E+10 3278.14 13-APR-17:01 19.03 7.22 0.188362E+09 193.90 05-APR-06:00 -11.7 -12.4
May 0.240353E+10 3547.15 18-MAY-17:01 28.13 16.04 0.202194E+09 191.52 04-MAY-16:19 20.13 10.15
June 0.258781E+10 3615.02 30-JUN-17:01 30.92 21.20 0.203348E+09 193.30 30-JUN-16:10 31.60 24.12
July 0.272570E+10 3623.07 21-JUL-17:01 25.00 20.76 0.189569E+09 193.70 21-JUL-16:19 28.33 21.65
August 0.286750E+10 3606.45 25-AUG-17:01 27.52 19.43 0.213632E+09 193.33 09-AUG-16:19 26.70 20.43
September 0.255909E+10 3570.73 01-SEP-17:01 24.32 17.90 0.188229E+09 192.39 01-SEP-16:19 25.53 17.75
October 0.236072E+10 3493.95 19-OCT-17:01 18.95 12.57 0.194826E+09 193.77 30-OCT-06:00 -9.4 -9.8
November 0.197478E+10 3427.32 01-NOV-17:01 15.95 12.47 0.195460E+09 193.94 29-NOV-08:50 -14.7 -15.0
December 0.153069E+10 3310.07 15-DEC-18:01 -8.4 -8.7 0.193532E+09 194.09 11-DEC-17:10 -17.0 -18.0
                     
Annual Sum or Average 0.253707E+11         0.236438E+10        
Minimum of Months 0.135946E+10 3245.19   -8.9 -10.3 0.181200E+09 191.52   -17.0 -18.0
Maximum of Months 0.286750E+10 3623.07   30.92 21.20 0.215453E+09 194.09   31.60 24.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.156012E+10 2456.14 20-JAN-07:01 -7.3 -7.9 0.660235E+09 649.14 11-JAN-07:10 -27.1 -27.3
February 0.157004E+10 2447.27 03-FEB-07:01 -13.5 -13.8 0.605230E+09 649.14 01-FEB-07:10 -22.9 -23.3
March 0.190735E+10 2449.15 10-MAR-07:01 -11.8 -12.2 0.723700E+09 649.14 31-MAR-06:10 -3.8 -4.6
April 0.196232E+10 2507.17 18-APR-06:01 12.38 7.00 0.642088E+09 649.12 27-APR-06:10 -3.2 -4.1
May 0.227519E+10 2528.62 19-MAY-06:01 14.47 10.08 0.692468E+09 649.09 18-MAY-06:10 15.50 11.62
June 0.235405E+10 2536.77 09-JUN-06:01 12.12 11.47 0.693201E+09 649.09 01-JUN-06:10 15.28 11.27
July 0.240300E+10 2538.39 27-JUL-06:01 12.25 11.42 0.646821E+09 649.07 03-JUL-06:10 18.90 17.14
August 0.262612E+10 2543.76 10-AUG-06:01 15.10 14.70 0.726882E+09 649.09 07-AUG-06:10 13.40 12.73
September 0.234188E+10 2538.90 08-SEP-06:01 10.68 10.02 0.645707E+09 649.11 11-SEP-06:10 11.78 10.17
October 0.220725E+10 2535.02 18-OCT-06:01 1.88 1.60 0.665961E+09 649.12 25-OCT-06:10 -4.2 -4.4
November 0.189572E+10 2532.02 02-NOV-06:01 4.82 3.20 0.656897E+09 649.13 16-NOV-07:10 -1.8 -3.2
December 0.162354E+10 2457.30 07-DEC-07:01 -7.8 -7.9 0.643306E+09 649.14 21-DEC-07:10 -27.9 -28.1
                     
Annual Sum or Average 0.247266E+11         0.800250E+10        
Minimum of Months 0.156012E+10 2447.27   -13.5 -13.8 0.605230E+09 649.07   -27.9 -28.1
Maximum of Months 0.262612E+10 2543.76   15.10 14.70 0.726882E+09 649.14   18.90 17.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.101282E+09 95.49 30-JAN-07:02 -4.4 -4.9 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 98487913.40 92.30 21-FEB-15:05 5.92 2.84 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.124267E+09 98.78 03-MAR-07:01 -12.1 -12.5 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.147282E+09 94.32 21-APR-17:00 12.20 3.28 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.172230E+09 105.15 26-MAY-17:00 19.80 15.94 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.173948E+09 118.19 30-JUN-17:00 31.10 21.38 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.182006E+09 116.06 21-JUL-16:57 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.187762E+09 118.21 25-AUG-17:00 27.80 19.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.172940E+09 116.99 01-SEP-17:00 24.40 17.92 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.162398E+09 122.49 27-OCT-06:01 2.20 1.99 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.129527E+09 155.63 10-NOV-07:01 -8.4 -9.4 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.106140E+09 153.19 01-DEC-07:01 -20.3 -20.5 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.175827E+10         0.00        
Minimum of Months 98487913.40 92.30   -20.3 -20.5 0.00 0.00   -23.1 -23.4
Maximum of Months 0.187762E+09 155.63   31.10 21.38 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.219486E+10 3429.15 27-JAN-13:33 -14.8 -15.8 0.399999E+09 432.95 27-JAN-13:39 -14.8 -15.8
February 0.240468E+10 2897.50 28-FEB-15:05 6.10 1.53 0.364685E+09 411.70 10-FEB-13:09 -13.7 -14.7
March 0.288037E+10 2724.64 31-MAR-14:10 8.30 3.01 0.433068E+09 384.68 15-MAR-11:00 -13.9 -15.1
April 0.312176E+10 2702.40 13-APR-14:10 19.08 7.51 0.380542E+09 375.20 13-APR-13:00 18.90 7.40
May 0.382080E+10 2743.15 18-MAY-17:01 28.13 16.04 0.407848E+09 367.21 08-MAY-10:20 6.37 4.37
June 0.408112E+10 2807.37 30-JUN-14:10 31.28 23.88 0.407576E+09 369.45 30-JUN-15:20 32.03 24.55
July 0.446703E+10 2833.00 27-JUL-06:03 12.25 11.42 0.379323E+09 368.65 21-JUL-16:10 29.17 21.79
August 0.493739E+10 2918.32 25-AUG-14:10 28.30 18.87 0.427866E+09 384.94 25-AUG-14:09 28.30 18.87
September 0.448796E+10 3036.70 01-SEP-14:10 25.68 18.04 0.381810E+09 402.24 01-SEP-14:09 25.68 18.04
October 0.402500E+10 3094.34 19-OCT-14:10 21.78 13.68 0.396850E+09 411.62 19-OCT-14:39 22.03 13.63
November 0.314557E+10 2896.40 17-NOV-13:10 10.10 3.23 0.394292E+09 404.62 17-NOV-13:39 10.40 3.34
December 0.228399E+10 2745.45 08-DEC-13:10 -13.0 -13.9 0.386670E+09 411.76 20-DEC-15:20 -19.3 -20.0
                     
Annual Sum or Average 0.418505E+11         0.476053E+10        
Minimum of Months 0.219486E+10 2702.40   -14.8 -15.8 0.364685E+09 367.21   -19.3 -20.0
Maximum of Months 0.493739E+10 3429.15   31.28 23.88 0.433068E+09 432.95   32.03 24.55



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 98229831.31 365.46 20-JAN-15:02 -5.1 -6.8 20051911.96 23.99 27-JAN-15:09 -14.4 -15.5
February 0.101933E+09 378.69 28-FEB-15:02 6.10 1.53 18806674.81 23.99 09-FEB-15:09 -8.4 -9.6
March 0.128215E+09 376.29 17-MAR-14:02 -2.7 -5.6 22523752.24 23.99 28-MAR-14:09 6.20 2.92
April 0.158280E+09 306.10 19-APR-14:03 6.70 0.85 20091367.78 23.99 27-APR-14:09 2.12 -1.0
May 0.203652E+09 315.21 22-MAY-14:02 19.60 13.78 22022968.46 23.99 15-MAY-14:09 21.72 13.93
June 0.219634E+09 388.63 30-JUN-06:01 26.60 21.93 22294778.61 23.99 07-JUN-14:09 22.20 14.32
July 0.241947E+09 321.32 21-JUL-14:05 28.98 22.56 20929775.45 23.99 10-JUL-12:09 24.08 16.50
August 0.265826E+09 390.72 10-AUG-06:01 15.10 14.70 23628734.36 23.99 07-AUG-12:09 19.27 17.32
September 0.234540E+09 389.08 01-SEP-06:01 16.10 15.79 20928190.81 23.99 07-SEP-14:09 23.90 14.55
October 0.209582E+09 390.76 27-OCT-14:02 5.68 5.08 21442955.25 23.99 18-OCT-12:09 13.68 9.54
November 0.158639E+09 372.09 01-NOV-14:02 17.88 13.28 20965718.02 23.99 08-NOV-13:09 2.38 -1.1
December 0.108970E+09 385.17 15-DEC-15:02 -7.8 -8.3 19991998.15 23.99 07-DEC-13:09 -8.0 -8.0
                     
Annual Sum or Average 0.212945E+10         0.253679E+09        
Minimum of Months 98229831.31 306.10   -7.8 -8.3 18806674.81 23.99   -14.4 -15.5
Maximum of Months 0.265826E+09 390.76   28.98 22.56 23628734.36 23.99   24.08 17.32



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 SCRUB

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 46289304.99 44.70 06-JAN-05:00 -35.0 -35.1 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 49405256.38 41.36 10-FEB-13:37 -13.2 -14.3 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 66429660.76 42.16 17-MAR-10:40 -7.2 -8.7 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 81523546.91 50.23 21-APR-07:55 3.30 -1.1 0.00 0.00 01-APR-00:10 3.52 0.37
May 99623322.10 52.51 18-MAY-16:40 28.30 16.15 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.105866E+09 63.10 30-JUN-16:10 31.60 24.12 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.116591E+09 74.51 14-JUL-07:12 19.40 17.91 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.118953E+09 79.44 25-AUG-07:43 16.47 14.93 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.105755E+09 67.92 01-SEP-08:20 18.53 17.08 0.00 0.00 01-SEP-00:10 19.75 18.15
October 90366353.36 49.23 20-OCT-15:20 18.70 10.00 0.00 0.00 01-OCT-00:10 7.52 6.57
November 67181083.02 42.44 01-NOV-06:03 10.78 9.44 0.00 0.00 01-NOV-00:10 3.60 0.50
December 51805995.28 41.61 15-DEC-17:57 -8.3 -8.6 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.999791E+09         0.00        
Minimum of Months 46289304.99 41.36   -35.0 -35.1 0.00 0.00   -23.1 -23.4
Maximum of Months 0.118953E+09 79.44   31.60 24.12 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 SOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.845625E+09 613.31 27-JAN-15:04 -14.4 -15.5 99365963.65 98.26 12-JAN-16:00 -21.1 -21.7
February 0.795190E+09 603.46 10-FEB-17:40 -13.5 -14.6 90345296.95 97.98 16-FEB-17:00 -16.1 -17.1
March 0.967365E+09 609.10 15-MAR-12:34 -12.8 -14.1 0.105304E+09 96.68 15-MAR-11:00 -13.9 -15.1
April 0.985193E+09 580.45 05-APR-09:10 -6.5 -8.8 90417140.07 91.90 05-APR-07:19 -10.8 -11.7
May 0.104282E+10 582.00 18-MAY-17:01 28.13 16.04 96010433.35 85.67 08-MAY-07:00 5.90 3.92
June 0.103526E+10 582.41 30-JUN-17:01 30.92 21.20 95622473.02 85.67 26-JUN-07:00 18.30 16.16
July 0.103445E+10 582.27 28-JUL-17:01 28.90 20.84 88642501.85 85.67 05-JUL-08:30 21.40 20.57
August 0.108152E+10 582.35 25-AUG-17:01 27.52 19.43 99746040.73 85.67 07-AUG-07:49 14.32 13.96
September 0.101505E+10 581.40 01-SEP-17:01 24.32 17.90 88787314.11 85.68 05-SEP-08:50 12.02 8.36
October 0.101015E+10 581.49 19-OCT-17:01 18.95 12.57 92722890.29 85.67 23-OCT-09:39 6.50 4.39
November 0.922238E+09 585.80 30-NOV-18:09 1.10 -0.6 93458164.99 93.44 29-NOV-09:20 -13.3 -13.7
December 0.869620E+09 614.01 15-DEC-17:57 -8.3 -8.6 96418572.47 97.87 14-DEC-17:00 -15.0 -15.9
                     
Annual Sum or Average 0.116045E+11         0.113684E+10        
Minimum of Months 0.795190E+09 580.45   -14.4 -15.5 88642501.85 85.67   -21.1 -21.7
Maximum of Months 0.108152E+10 614.01   30.92 21.20 0.105304E+09 98.26   21.40 20.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.273755E+09 214.87 27-JAN-15:04 -14.4 -15.5 38867936.36 39.16 12-JAN-16:00 -21.1 -21.7
February 0.258771E+09 215.15 10-FEB-17:40 -13.5 -14.6 35392807.23 39.25 16-FEB-17:00 -16.1 -17.1
March 0.335488E+09 212.59 15-MAR-12:34 -12.8 -14.1 41292274.79 38.17 15-MAR-11:00 -13.9 -15.1
April 0.387477E+09 204.57 05-APR-17:09 -0.1 -3.9 35006570.29 36.55 05-APR-07:19 -10.8 -11.7
May 0.451654E+09 215.60 26-MAY-17:00 19.80 15.94 37148970.22 35.61 05-MAY-16:00 17.80 8.50
June 0.462545E+09 221.61 30-JUN-17:00 31.10 21.38 37602454.17 36.46 30-JUN-16:00 31.10 21.38
July 0.481964E+09 221.44 21-JUL-17:00 25.00 20.76 35236524.22 36.43 21-JUL-16:00 25.00 20.76
August 0.490662E+09 220.17 11-AUG-17:00 26.10 19.35 39850235.61 36.21 11-AUG-16:00 26.10 19.35
September 0.451148E+09 218.72 01-SEP-17:00 24.40 17.92 34628633.42 35.96 01-SEP-16:00 24.40 17.92
October 0.421509E+09 212.60 06-OCT-17:00 11.10 8.71 35811398.79 35.20 05-OCT-16:00 5.00 1.34
November 0.344096E+09 210.23 30-NOV-18:09 1.10 -0.6 36618575.23 37.51 29-NOV-09:50 -11.6 -12.2
December 0.283390E+09 219.41 15-DEC-17:57 -8.3 -8.6 38130130.17 39.55 01-DEC-17:00 -20.6 -21.0
                     
Annual Sum or Average 0.464246E+10         0.445587E+09        
Minimum of Months 0.258771E+09 204.57   -14.4 -15.5 34628633.42 35.20   -21.1 -21.7
Maximum of Months 0.490662E+09 221.61   31.10 21.38 41292274.79 39.55   31.10 21.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.101771E+10 802.10 27-JAN-15:04 -14.4 -15.5 0.138725E+09 137.74 27-JAN-17:00 -17.8 -18.3
February 0.966158E+09 786.82 10-FEB-17:40 -13.5 -14.6 0.126403E+09 136.46 24-FEB-17:00 -19.4 -20.1
March 0.117034E+10 788.72 15-MAR-12:34 -12.8 -14.1 0.148300E+09 134.30 15-MAR-11:00 -13.9 -15.1
April 0.118847E+10 756.85 05-APR-08:58 -6.7 -9.0 0.128265E+09 126.95 05-APR-07:19 -10.8 -11.7
May 0.126964E+10 772.30 18-MAY-17:01 28.13 16.04 0.136458E+09 122.39 30-MAY-10:20 11.10 8.71
June 0.127203E+10 772.96 30-JUN-17:01 30.92 21.20 0.135978E+09 122.38 12-JUN-10:39 17.60 14.65
July 0.127917E+10 772.90 28-JUL-17:01 28.90 20.84 0.126106E+09 122.38 17-JUL-08:50 15.00 12.42
August 0.135284E+10 773.22 25-AUG-17:01 27.52 19.43 0.141971E+09 122.38 15-AUG-08:50 15.00 14.60
September 0.125572E+10 771.78 01-SEP-17:01 24.32 17.90 0.126261E+09 122.38 18-SEP-09:00 16.10 15.06
October 0.123026E+10 771.69 19-OCT-17:01 18.95 12.57 0.131731E+09 122.39 16-OCT-08:09 5.60 3.78
November 0.111367E+10 768.26 01-NOV-17:01 15.95 12.47 0.132511E+09 129.32 29-NOV-09:20 -13.3 -13.7
December 0.105005E+10 795.47 15-DEC-17:57 -8.3 -8.6 0.134552E+09 136.32 01-DEC-17:00 -20.6 -21.0
                     
Annual Sum or Average 0.141661E+11         0.160726E+10        
Minimum of Months 0.966158E+09 756.85   -14.4 -15.5 0.126106E+09 122.38   -20.6 -21.0
Maximum of Months 0.135284E+10 802.10   30.92 21.20 0.148300E+09 137.74   17.60 15.06



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.781509E+09 1370.07 27-JAN-15:04 -14.4 -15.5 0.219533E+09 228.75 25-JAN-15:20 -18.1 -18.9
February 0.939149E+09 1406.38 28-FEB-15:30 6.10 1.53 0.201031E+09 228.69 28-FEB-15:50 6.10 1.53
March 0.118091E+10 1325.70 31-MAR-15:10 8.40 2.80 0.239865E+09 217.24 31-MAR-15:20 8.50 2.99
April 0.144728E+10 1337.62 13-APR-15:10 20.00 8.07 0.212635E+09 219.64 13-APR-15:20 20.00 8.07
May 0.202807E+10 1429.34 18-MAY-16:10 28.45 16.26 0.229494E+09 223.89 18-MAY-16:19 28.40 16.22
June 0.222600E+10 1536.65 30-JUN-17:00 31.10 21.38 0.230261E+09 228.70 30-JUN-16:00 31.10 21.38
July 0.253984E+10 1520.24 21-JUL-16:07 29.17 21.79 0.216542E+09 228.74 21-JUL-16:00 25.00 20.76
August 0.275034E+10 1663.89 25-AUG-17:00 27.80 19.36 0.245425E+09 228.72 25-AUG-13:20 27.57 18.62
September 0.243835E+10 1787.14 01-SEP-15:30 26.10 17.71 0.216430E+09 228.72 07-SEP-14:20 23.90 14.64
October 0.207415E+10 1812.91 19-OCT-15:00 22.20 13.60 0.222735E+09 228.73 19-OCT-16:00 19.40 12.77
November 0.148804E+10 1421.14 17-NOV-13:50 10.50 3.37 0.219542E+09 228.72 17-NOV-14:20 10.60 3.41
December 0.877421E+09 1270.43 08-DEC-13:27 -12.5 -13.4 0.212945E+09 228.60 20-DEC-14:00 -18.9 -19.6
                     
Annual Sum or Average 0.207711E+11         0.266644E+10        
Minimum of Months 0.781509E+09 1270.43   -14.4 -15.5 0.201031E+09 217.24   -18.9 -19.6
Maximum of Months 0.275034E+10 1812.91   31.10 21.79 0.245425E+09 228.75   31.10 21.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.332682E+09 459.67 27-JAN-14:25 -14.4 -15.5 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.339561E+09 353.34 10-FEB-14:45 -11.9 -13.2 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.435229E+09 318.75 17-MAR-15:00 -2.2 -5.3 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.500165E+09 315.76 21-APR-14:30 11.65 3.10 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.577249E+09 314.41 18-MAY-16:20 28.40 16.22 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.599944E+09 397.29 30-JUN-16:10 31.60 24.12 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.645618E+09 413.40 21-JUL-16:07 29.17 21.79 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.672717E+09 473.35 25-AUG-14:20 28.30 18.94 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.619763E+09 514.50 01-SEP-14:20 25.77 18.00 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.562304E+09 504.83 20-OCT-14:30 18.90 10.05 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.439269E+09 395.35 17-NOV-13:50 10.50 3.37 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.358919E+09 372.98 08-DEC-13:50 -12.0 -12.9 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.608342E+10         0.00        
Minimum of Months 0.332682E+09 314.41   -14.4 -15.5 0.00 0.00   -23.1 -23.4
Maximum of Months 0.672717E+09 514.50   31.60 24.12 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.298953E+09 584.62 27-JAN-07:01 -22.7 -22.9 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.303719E+09 775.19 03-FEB-07:01 -13.5 -13.8 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.368926E+09 774.03 10-MAR-07:01 -11.8 -12.2 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.370779E+09 753.01 07-APR-06:01 -5.7 -7.0 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.403752E+09 244.36 22-MAY-06:03 9.72 6.65 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.397199E+09 244.22 19-JUN-06:04 17.88 17.12 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.410421E+09 242.08 17-JUL-06:03 13.07 12.21 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.416237E+09 242.56 21-AUG-06:03 12.77 12.42 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.398755E+09 242.13 25-SEP-06:03 6.60 5.81 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.387336E+09 430.87 06-OCT-06:01 -3.6 -4.0 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.331324E+09 761.84 10-NOV-07:01 -8.4 -9.4 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.327945E+09 780.36 15-DEC-07:01 -13.4 -14.1 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.441535E+10         0.00        
Minimum of Months 0.298953E+09 242.08   -22.7 -22.9 0.00 0.00   -23.1 -23.4
Maximum of Months 0.416237E+09 780.36   17.88 17.12 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 4734434.37 438.01 18-JAN-18:01 -2.9 -3.2 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 7518766.75 439.98 07-FEB-18:01 2.62 0.30 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 14511106.96 441.06 24-MAR-17:01 -0.7 -0.9 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 65659712.94 444.83 15-APR-14:01 4.13 3.40 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.322583E+09 473.57 25-MAY-17:01 29.23 19.28 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.547517E+09 502.03 30-JUN-17:01 30.92 21.20 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.826329E+09 501.99 21-JUL-16:13 28.33 21.65 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.775670E+09 494.43 09-AUG-17:01 26.70 20.31 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.541699E+09 485.37 01-SEP-06:14 16.10 15.79 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.254551E+09 470.78 19-OCT-17:01 18.95 12.57 0.00 0.00 01-OCT-00:10 7.52 6.57
November 63705711.59 469.81 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 7979726.19 442.88 05-DEC-18:01 0.00 -0.0 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.343246E+10         0.00        
Minimum of Months 4734434.37 438.01   -2.9 -3.2 0.00 0.00   -23.1 -23.4
Maximum of Months 0.826329E+09 502.03   30.92 21.65 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 29397856.37 98.14 18-JAN-18:01 -2.9 -3.2 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 37231073.89 101.83 09-FEB-07:04 -2.7 -3.1 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 68484014.30 104.12 23-MAR-09:35 -6.9 -7.7 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.150672E+09 121.49 21-APR-09:30 7.20 0.75 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.237375E+09 249.48 18-MAY-09:20 24.33 15.90 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.290784E+09 323.84 28-JUN-06:03 19.55 18.19 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.349993E+09 578.19 14-JUL-06:02 17.57 17.07 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.336790E+09 359.43 25-AUG-09:25 21.70 17.31 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.270185E+09 324.35 01-SEP-09:20 20.57 17.75 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.183167E+09 187.02 19-OCT-09:15 12.03 8.66 0.00 0.00 01-OCT-00:10 7.52 6.57
November 98301039.63 106.53 01-NOV-06:04 10.78 9.44 0.00 0.00 01-NOV-00:10 3.60 0.50
December 38784417.27 101.45 06-DEC-07:04 -2.1 -2.1 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.209117E+10         0.00        
Minimum of Months 29397856.37 98.14   -6.9 -7.7 0.00 0.00   -23.1 -23.4
Maximum of Months 0.349993E+09 578.19   24.33 18.19 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 4278851.86 129.66 18-JAN-18:01 -2.9 -3.2 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 8029597.74 130.31 07-FEB-18:01 2.62 0.30 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 15302290.86 130.68 24-MAR-17:01 -0.7 -0.9 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 58545417.04 131.69 15-APR-14:01 4.13 3.40 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.172542E+09 145.85 18-MAY-06:04 15.50 11.62 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.250596E+09 153.09 30-JUN-16:00 31.70 24.65 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.326955E+09 153.77 21-JUL-16:03 29.17 21.79 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.306655E+09 150.42 25-AUG-17:01 27.52 19.43 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.213235E+09 147.80 01-SEP-16:20 25.53 17.75 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.134478E+09 142.91 20-OCT-06:04 5.92 5.92 0.00 0.00 01-OCT-00:10 7.52 6.57
November 56615703.88 139.11 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 9270702.08 131.14 05-DEC-18:01 0.00 -0.0 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.155650E+10         0.00        
Minimum of Months 4278851.86 129.66   -2.9 -3.2 0.00 0.00   -23.1 -23.4
Maximum of Months 0.326955E+09 153.77   31.70 24.65 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 22522234.16 22.40 06-JAN-05:00 -35.0 -35.1 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 23485346.57 20.35 10-FEB-13:37 -13.2 -14.3 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 30938821.25 20.55 17-MAR-10:40 -7.2 -8.7 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 38413568.56 21.28 14-APR-08:43 10.95 5.54 0.00 0.00 01-APR-00:10 3.52 0.37
May 47899179.34 22.71 18-MAY-19:00 24.50 15.15 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 50856861.04 28.38 30-JUN-16:30 31.40 23.04 0.00 0.00 01-JUN-00:10 11.35 8.93
July 56292382.70 32.15 21-JUL-16:27 27.50 21.48 0.00 0.00 01-JUL-00:10 15.83 13.56
August 57755006.31 33.59 25-AUG-15:20 28.30 19.26 0.00 0.00 01-AUG-00:10 17.07 15.36
September 51047694.63 27.86 01-SEP-16:40 24.97 17.85 0.00 0.00 01-SEP-00:10 19.75 18.15
October 44328757.91 22.36 20-OCT-14:10 18.90 10.05 0.00 0.00 01-OCT-00:10 7.52 6.57
November 33390151.05 21.10 01-NOV-06:03 10.78 9.44 0.00 0.00 01-NOV-00:10 3.60 0.50
December 25639168.30 20.72 15-DEC-17:57 -8.3 -8.6 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.482569E+09         0.00        
Minimum of Months 22522234.16 20.35   -35.0 -35.1 0.00 0.00   -23.1 -23.4
Maximum of Months 57755006.31 33.59   31.40 23.04 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 24443766.77 134.12 18-JAN-18:01 -2.9 -3.2 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 33379436.91 134.73 07-FEB-18:01 2.62 0.30 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 67116052.80 135.45 24-MAR-17:01 -0.7 -0.9 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.145106E+09 143.62 15-APR-06:08 5.60 5.31 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.271422E+09 157.06 18-MAY-14:10 28.57 16.70 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.344557E+09 221.51 30-JUN-15:00 32.20 24.50 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.405874E+09 283.71 29-JUL-09:30 26.15 19.88 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.397781E+09 282.72 25-AUG-09:35 22.07 17.42 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.310399E+09 199.37 01-SEP-09:40 21.13 17.71 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.201395E+09 148.01 20-OCT-14:10 18.90 10.05 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.101732E+09 143.49 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 39498364.69 135.53 05-DEC-18:01 0.00 -0.0 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.234270E+10         0.00        
Minimum of Months 24443766.77 134.12   -2.9 -3.2 0.00 0.00   -23.1 -23.4
Maximum of Months 0.405874E+09 283.71   32.20 24.50 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 7665.19 29.01 21-JAN-15:01 -5.4 -7.2 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 223802.90 29.39 04-FEB-15:01 7.80 2.57 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 954294.70 31.89 11-MAR-15:01 -1.8 -4.7 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 7026086.28 36.28 15-APR-14:01 4.13 3.40 0.00 0.00 01-APR-00:10 3.52 0.37
May 93460288.76 337.42 25-MAY-17:00 29.20 19.29 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.146653E+09 442.17 29-JUN-16:00 35.00 24.70 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.179725E+09 354.17 21-JUL-16:00 30.00 21.90 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.136909E+09 364.44 08-AUG-16:00 30.60 22.97 0.00 0.00 01-AUG-00:10 17.07 15.36
September 54981380.05 283.28 01-SEP-16:00 26.10 17.62 0.00 0.00 01-SEP-00:10 19.75 18.15
October 20628458.59 42.39 19-OCT-15:00 22.20 13.60 0.00 0.00 01-OCT-00:10 7.52 6.57
November 3649777.44 35.93 18-NOV-15:01 4.90 1.39 0.00 0.00 01-NOV-00:10 3.60 0.50
December 8691.84 27.95 16-DEC-15:01 -5.6 -6.2 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.644228E+09         0.00        
Minimum of Months 7665.19 27.95   -5.6 -7.2 0.00 0.00   -23.1 -23.4
Maximum of Months 0.179725E+09 442.17   35.00 24.70 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.741180E+09 1748.64 26-JAN-12:04 -20.6 -21.0 0.499334E+09 650.26 27-JAN-13:00 -14.4 -15.5
February 0.929733E+09 1872.46 28-FEB-14:00 3.90 0.13 0.465256E+09 683.11 28-FEB-13:00 3.90 0.13
March 0.126252E+10 1823.41 31-MAR-14:30 8.30 2.85 0.568945E+09 671.60 23-MAR-14:30 0.30 -4.0
April 0.144368E+10 2046.26 12-APR-13:00 16.70 6.86 0.512384E+09 665.32 21-APR-12:00 10.60 2.46
May 0.184266E+10 1986.35 18-MAY-13:00 28.20 16.73 0.562531E+09 651.35 17-MAY-06:10 11.65 8.32
June 0.200580E+10 1973.18 30-JUN-13:00 31.70 24.45 0.563760E+09 658.69 15-JUN-06:10 11.57 10.07
July 0.210700E+10 1888.06 21-JUL-13:00 28.30 22.43 0.520948E+09 647.43 27-JUL-06:10 12.25 11.42
August 0.214370E+10 2136.48 25-AUG-13:00 27.20 18.51 0.589219E+09 657.64 25-AUG-06:10 9.05 8.95
September 0.176011E+10 2394.64 01-SEP-13:00 24.40 17.92 0.519030E+09 648.76 08-SEP-06:10 10.68 10.02
October 0.142974E+10 2382.54 19-OCT-12:55 20.60 13.59 0.533087E+09 662.21 18-OCT-12:39 14.83 10.30
November 0.106152E+10 1835.70 17-NOV-13:40 10.40 3.34 0.515904E+09 668.49 17-NOV-13:39 10.40 3.34
December 0.701786E+09 1700.26 20-DEC-12:06 -22.6 -23.0 0.482345E+09 640.53 19-DEC-15:20 -22.4 -22.9
                     
Annual Sum or Average 0.174294E+11         0.633274E+10        
Minimum of Months 0.701786E+09 1700.26   -22.6 -23.0 0.465256E+09 640.53   -22.4 -22.9
Maximum of Months 0.214370E+10 2394.64   31.70 24.45 0.589219E+09 683.11   14.83 11.42



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.158833E+09 209.95 26-JAN-07:03 -33.1 -33.2 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.169656E+09 215.82 14-FEB-07:03 -33.0 -33.2 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.197647E+09 170.50 16-MAR-05:03 -24.2 -24.4 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.215773E+09 175.34 13-APR-17:01 19.03 7.22 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.255215E+09 188.87 17-MAY-17:01 26.70 16.03 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.271825E+09 204.02 30-JUN-06:03 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.294435E+09 192.24 21-JUL-06:05 19.27 18.71 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.291809E+09 190.05 09-AUG-06:05 18.98 17.80 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.247396E+09 189.06 01-SEP-17:01 24.32 17.90 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.214242E+09 180.90 21-OCT-14:01 20.00 11.40 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.187787E+09 157.64 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.164314E+09 194.15 20-DEC-07:03 -29.1 -29.3 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.266893E+10         0.00        
Minimum of Months 0.158833E+09 157.64   -33.1 -33.2 0.00 0.00   -23.1 -23.4
Maximum of Months 0.294435E+09 215.82   26.70 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 99341132.49 116.30 27-JAN-18:00 -17.8 -18.3 12406312.64 13.35 20-JAN-07:10 -7.3 -7.9
February 98715333.55 197.47 09-FEB-07:01 -2.7 -3.1 11473289.29 13.90 09-FEB-07:10 -2.7 -3.1
March 0.118570E+09 202.07 30-MAR-06:01 -2.8 -3.0 13838812.29 14.02 30-MAR-06:10 -2.8 -3.0
April 0.114170E+09 204.87 14-APR-06:02 2.07 1.49 12319219.45 14.16 21-APR-06:10 -3.1 -4.6
May 0.124895E+09 225.69 19-MAY-06:01 14.47 10.08 13242527.24 14.09 05-MAY-06:10 3.67 0.56
June 0.129725E+09 210.34 09-JUN-06:01 12.12 11.47 13204733.74 14.04 16-JUN-06:10 10.78 9.76
July 0.129787E+09 217.64 28-JUL-06:01 12.85 12.85 12219797.43 13.93 27-JUL-06:10 12.25 11.42
August 0.136385E+09 225.51 11-AUG-06:01 14.18 13.74 13803074.58 14.12 25-AUG-06:10 9.05 8.95
September 0.120397E+09 207.48 15-SEP-06:02 5.87 5.35 12314493.94 14.23 15-SEP-06:10 5.87 5.35
October 0.113408E+09 208.12 20-OCT-06:02 5.92 5.92 12704919.31 14.22 20-OCT-06:10 5.92 5.92
November 0.105063E+09 199.40 17-NOV-07:01 -3.8 -4.8 12467857.90 13.98 17-NOV-07:10 -3.8 -4.8
December 0.100916E+09 134.53 15-DEC-07:01 -13.4 -14.1 12127029.78 13.52 15-DEC-07:10 -13.4 -14.1
                     
Annual Sum or Average 0.139137E+10         0.152122E+09        
Minimum of Months 98715333.55 116.30   -17.8 -18.3 11473289.29 13.35   -13.4 -14.1
Maximum of Months 0.136385E+09 225.69   14.47 13.74 13838812.29 14.23   12.25 11.42



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.353123E+09 1088.52 07-JAN-15:02 -16.8 -17.4 0.260368E+09 261.15 27-JAN-15:00 -14.4 -15.5
February 0.619508E+09 1177.67 28-FEB-15:50 6.10 1.53 0.239773E+09 274.51 28-FEB-15:20 6.10 1.53
March 0.106892E+10 1471.42 31-MAR-17:00 8.90 3.27 0.290526E+09 274.50 31-MAR-16:10 8.90 3.67
April 0.147898E+10 1879.81 21-APR-17:00 12.20 3.28 0.264684E+09 274.50 10-APR-16:00 11.10 3.24
May 0.213383E+10 2145.13 25-MAY-17:00 29.20 19.29 0.288409E+09 274.50 01-MAY-16:49 10.37 2.33
June 0.231783E+10 2286.70 30-JUN-17:00 31.10 21.38 0.287796E+09 274.49 26-JUN-16:49 26.20 18.15
July 0.251534E+10 2103.10 28-JUL-17:00 28.90 20.78 0.268941E+09 274.50 21-JUL-16:49 25.83 21.03
August 0.247437E+10 2099.88 25-AUG-17:00 27.80 19.36 0.299688E+09 274.49 01-AUG-16:00 19.40 14.40
September 0.193070E+10 2014.53 01-SEP-16:10 25.82 17.69 0.265478E+09 274.50 05-SEP-16:10 16.70 9.77
October 0.145082E+10 1705.42 19-OCT-16:10 21.32 13.42 0.270256E+09 274.50 26-OCT-16:00 12.20 7.13
November 0.919751E+09 1050.93 17-NOV-15:30 10.30 3.30 0.261024E+09 274.50 17-NOV-16:19 8.90 2.57
December 0.381571E+09 1085.62 02-DEC-15:03 -17.4 -18.2 0.251883E+09 244.69 20-DEC-08:00 -29.4 -29.6
                     
Annual Sum or Average 0.176447E+11         0.324883E+10        
Minimum of Months 0.353123E+09 1050.93   -17.4 -18.2 0.239773E+09 244.69   -29.4 -29.6
Maximum of Months 0.251534E+10 2286.70   31.10 21.38 0.299688E+09 274.51   26.20 21.03



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.210909E+10 2529.68 26-JAN-06:02 -32.9 -33.0 0.394714E+09 382.37 27-JAN-15:30 -14.4 -15.5
February 0.227619E+10 2478.18 17-FEB-06:02 -31.6 -31.7 0.360998E+09 388.54 28-FEB-15:39 6.10 1.53
March 0.279926E+10 1982.45 15-MAR-05:03 -22.2 -22.5 0.432989E+09 388.36 31-MAR-14:39 8.30 2.77
April 0.288357E+10 2267.72 13-APR-17:01 19.03 7.22 0.385340E+09 385.33 20-APR-14:09 10.00 2.58
May 0.335178E+10 2443.25 17-MAY-17:01 26.70 16.03 0.412399E+09 366.96 30-MAY-06:40 10.73 8.37
June 0.346470E+10 2676.27 30-JUN-06:03 26.60 21.93 0.410507E+09 366.96 19-JUN-06:00 18.30 17.53
July 0.359751E+10 2445.76 21-JUL-17:01 25.00 20.76 0.380690E+09 366.97 05-JUL-07:10 20.68 19.87
August 0.375047E+10 2448.87 25-AUG-17:01 27.52 19.43 0.428121E+09 366.96 28-AUG-06:00 15.00 13.99
September 0.324272E+10 2445.87 01-SEP-17:01 24.32 17.90 0.383467E+09 366.95 11-SEP-06:40 12.03 10.26
October 0.293345E+10 2332.54 21-OCT-14:01 20.00 11.40 0.397888E+09 384.11 25-OCT-13:39 10.93 6.92
November 0.250466E+10 2039.52 01-NOV-17:01 15.95 12.47 0.392320E+09 388.09 17-NOV-13:09 10.10 3.23
December 0.214930E+10 2317.79 20-DEC-06:02 -28.9 -29.1 0.381485E+09 367.03 08-DEC-07:30 -20.2 -20.6
                     
Annual Sum or Average 0.350627E+11         0.476092E+10        
Minimum of Months 0.210909E+10 1982.45   -32.9 -33.0 0.360998E+09 366.95   -20.2 -20.6
Maximum of Months 0.375047E+10 2676.27   27.52 21.93 0.432989E+09 388.54   20.68 19.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.281804E+10 3356.01 26-JAN-06:02 -32.9 -33.0 0.526797E+09 519.97 27-JAN-14:20 -14.4 -15.5
February 0.301088E+10 3290.15 17-FEB-06:02 -31.6 -31.7 0.481881E+09 528.56 28-FEB-14:50 5.73 1.30
March 0.364038E+10 2562.67 15-MAR-05:03 -22.2 -22.5 0.577193E+09 523.40 31-MAR-14:39 8.30 2.77
April 0.363891E+10 3020.30 13-APR-17:01 19.03 7.22 0.512641E+09 513.87 20-APR-14:09 10.00 2.58
May 0.412284E+10 3252.08 17-MAY-17:01 26.70 16.03 0.548122E+09 489.28 30-MAY-06:40 10.73 8.37
June 0.425522E+10 3555.67 30-JUN-06:03 26.60 21.93 0.545683E+09 489.29 19-JUN-06:49 18.22 17.45
July 0.434676E+10 3254.87 21-JUL-17:01 25.00 20.76 0.505809E+09 489.29 31-JUL-08:09 18.40 14.07
August 0.459202E+10 3259.55 25-AUG-17:01 27.52 19.43 0.568937E+09 489.28 21-AUG-08:39 18.87 16.93
September 0.402012E+10 3255.29 01-SEP-17:01 24.32 17.90 0.509760E+09 489.28 18-SEP-07:49 13.90 13.90
October 0.370594E+10 3109.60 21-OCT-14:01 20.00 11.40 0.529466E+09 515.47 25-OCT-13:39 10.93 6.92
November 0.323420E+10 2715.87 01-NOV-17:01 15.95 12.47 0.523040E+09 523.08 17-NOV-13:09 10.10 3.23
December 0.284104E+10 3090.01 20-DEC-06:02 -28.9 -29.1 0.508563E+09 496.37 20-DEC-14:09 -20.0 -20.6
                     
Annual Sum or Average 0.442263E+11         0.633789E+10        
Minimum of Months 0.281804E+10 2562.67   -32.9 -33.0 0.481881E+09 489.28   -20.0 -20.6
Maximum of Months 0.459202E+10 3555.67   27.52 21.93 0.577193E+09 528.56   18.87 17.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.249679E+09 409.26 27-JAN-14:07 -14.4 -15.5 62565420.11 67.40 27-JAN-14:09 -14.4 -15.5
February 0.309389E+09 433.97 28-FEB-14:10 4.27 0.37 58369090.04 70.05 28-FEB-14:30 5.00 0.84
March 0.386121E+09 410.88 23-MAR-14:02 0.10 -4.0 70037490.13 67.47 23-MAR-13:50 -0.2 -4.1
April 0.417922E+09 432.59 13-APR-13:10 17.98 6.83 63045120.01 65.18 21-APR-13:09 10.68 2.52
May 0.519833E+09 364.85 18-MAY-13:20 28.30 16.73 66873991.27 64.05 05-MAY-13:20 16.57 7.96
June 0.559449E+09 358.44 30-JUN-13:20 31.50 24.22 66262040.00 64.05 30-JUN-13:20 31.50 24.22
July 0.593262E+09 347.14 21-JUL-14:05 28.98 22.56 61725965.75 63.26 21-JUL-14:09 28.98 22.56
August 0.610015E+09 419.85 25-AUG-13:10 27.38 18.57 69776749.05 64.05 25-AUG-13:20 27.57 18.62
September 0.514651E+09 514.62 01-SEP-13:20 24.80 17.99 62708721.02 64.05 08-SEP-13:20 18.50 10.24
October 0.430495E+09 546.66 19-OCT-13:15 20.97 13.64 64233584.96 67.45 18-OCT-12:20 14.07 9.79
November 0.328688E+09 418.98 17-NOV-13:30 10.30 3.30 62766384.00 67.94 17-NOV-13:30 10.30 3.30
December 0.235140E+09 363.00 20-DEC-13:40 -20.6 -21.2 60135598.77 64.05 20-DEC-15:20 -19.3 -20.0
                     
Annual Sum or Average 0.515465E+10         0.768500E+09        
Minimum of Months 0.235140E+09 347.14   -20.6 -21.2 58369090.04 63.26   -19.3 -20.0
Maximum of Months 0.610015E+09 546.66   31.50 24.22 70037490.13 70.05   31.50 24.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.802207E+09 1256.71 07-JAN-15:02 -16.8 -17.4 0.253949E+09 237.87 04-JAN-11:50 -28.4 -28.7
February 0.986719E+09 1152.72 17-FEB-06:02 -31.6 -31.7 0.231800E+09 239.34 28-FEB-10:09 -5.5 -7.1
March 0.147698E+10 1057.94 31-MAR-09:40 1.13 -1.1 0.280475E+09 260.17 31-MAR-09:50 1.42 -0.9
April 0.184121E+10 1417.37 18-APR-09:25 18.05 10.93 0.257148E+09 266.88 12-APR-08:09 7.95 3.11
May 0.247458E+10 1593.62 17-MAY-08:55 21.10 13.98 0.277361E+09 266.88 03-MAY-07:00 11.50 6.35
June 0.274088E+10 1643.44 15-JUN-09:00 17.20 11.88 0.279719E+09 266.88 14-JUN-09:30 18.90 14.62
July 0.292378E+10 1636.66 19-JUL-09:10 21.88 16.41 0.261181E+09 266.88 27-JUL-08:30 19.20 14.95
August 0.281518E+10 1639.57 25-AUG-09:10 20.97 17.06 0.286618E+09 266.88 04-AUG-09:30 18.85 13.88
September 0.223884E+10 1557.82 01-SEP-09:40 21.13 17.71 0.255452E+09 266.88 14-SEP-08:30 11.10 9.34
October 0.180818E+10 1311.14 19-OCT-12:15 19.07 12.74 0.259472E+09 266.88 19-OCT-09:30 12.50 9.00
November 0.135538E+10 1154.61 01-NOV-17:01 15.95 12.47 0.253049E+09 243.01 16-NOV-09:50 1.32 -0.6
December 0.876829E+09 1191.22 02-DEC-15:03 -17.4 -18.2 0.246094E+09 237.87 21-DEC-08:50 -28.8 -29.0
                     
Annual Sum or Average 0.223408E+11         0.314232E+10        
Minimum of Months 0.802207E+09 1057.94   -31.6 -31.7 0.231800E+09 237.87   -28.8 -29.0
Maximum of Months 0.292378E+10 1643.44   21.88 17.71 0.286618E+09 266.88   19.20 14.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.426052E+09 867.73 07-JAN-15:02 -16.8 -17.4 0.162979E+09 152.92 04-JAN-11:50 -28.4 -28.7
February 0.517150E+09 852.74 17-FEB-06:02 -31.6 -31.7 0.148624E+09 152.92 17-FEB-08:20 -28.2 -28.3
March 0.780607E+09 712.52 01-MAR-07:02 -3.9 -4.1 0.178488E+09 152.91 06-MAR-08:09 -18.7 -19.0
April 0.953251E+09 885.06 13-APR-17:01 19.03 7.22 0.159358E+09 152.90 03-APR-07:19 -2.8 -4.2
May 0.132532E+10 959.58 18-MAY-17:01 28.13 16.04 0.172001E+09 152.90 01-MAY-06:49 -1.7 -4.5
June 0.147770E+10 1054.36 30-JUN-06:03 26.60 21.93 0.171773E+09 152.90 19-JUN-06:40 18.13 17.37
July 0.156036E+10 981.39 21-JUL-06:05 19.27 18.71 0.159382E+09 152.90 05-JUL-06:40 20.60 19.78
August 0.153337E+10 960.96 08-AUG-17:01 29.22 22.94 0.178896E+09 152.90 28-AUG-06:49 14.82 13.87
September 0.121446E+10 957.53 01-SEP-17:01 24.32 17.90 0.159556E+09 153.00 21-SEP-14:30 9.70 7.97
October 0.997996E+09 901.54 21-OCT-14:01 20.00 11.40 0.164833E+09 152.90 30-OCT-07:10 -9.0 -9.3
November 0.755034E+09 799.84 01-NOV-17:01 15.95 12.47 0.162098E+09 152.90 24-NOV-08:20 -10.0 -10.6
December 0.499836E+09 820.98 09-DEC-15:03 -17.4 -18.3 0.157972E+09 152.92 20-DEC-09:09 -29.0 -29.2
                     
Annual Sum or Average 0.120411E+11         0.197596E+10        
Minimum of Months 0.426052E+09 712.52   -31.6 -31.7 0.148624E+09 152.90   -29.0 -29.2
Maximum of Months 0.156036E+10 1054.36   29.22 22.94 0.178896E+09 153.00   20.60 19.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.283476E+10 3757.91 13-JAN-06:02 -31.3 -31.4 0.577082E+09 538.25 09-JAN-08:50 -31.9 -32.0
February 0.295079E+10 3835.81 17-FEB-06:02 -31.6 -31.7 0.526054E+09 538.25 27-FEB-07:30 -18.9 -19.2
March 0.375146E+10 2908.73 15-MAR-05:03 -22.2 -22.5 0.630991E+09 538.27 07-MAR-07:30 -20.2 -20.5
April 0.389829E+10 3302.58 13-APR-17:01 19.03 7.22 0.561583E+09 538.20 03-APR-07:10 -3.0 -4.4
May 0.466197E+10 3568.13 17-MAY-17:01 26.70 16.03 0.602966E+09 538.20 30-MAY-06:40 10.73 8.37
June 0.491620E+10 3922.06 30-JUN-06:03 26.60 21.93 0.600666E+09 538.21 19-JUN-06:49 18.22 17.45
July 0.499560E+10 3574.69 21-JUL-17:01 25.00 20.76 0.556473E+09 538.22 05-JUL-07:10 20.68 19.87
August 0.508340E+10 3571.58 25-AUG-17:01 27.52 19.43 0.625515E+09 538.20 21-AUG-08:39 18.87 16.93
September 0.430191E+10 3559.53 01-SEP-17:01 24.32 17.90 0.559929E+09 538.20 11-SEP-06:40 12.03 10.26
October 0.396843E+10 3362.50 21-OCT-14:01 20.00 11.40 0.580617E+09 538.20 30-OCT-06:49 -9.4 -9.8
November 0.351798E+10 2990.50 01-NOV-17:01 15.95 12.47 0.572451E+09 538.21 27-NOV-08:09 -6.7 -7.0
December 0.304278E+10 3402.78 20-DEC-06:02 -28.9 -29.1 0.559276E+09 538.34 08-DEC-07:30 -20.2 -20.6
                     
Annual Sum or Average 0.479236E+11         0.695360E+10        
Minimum of Months 0.283476E+10 2908.73   -31.6 -31.7 0.526054E+09 538.20   -31.9 -32.0
Maximum of Months 0.508340E+10 3922.06   27.52 21.93 0.630991E+09 538.34   20.68 19.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.644493E+09 1083.36 13-JAN-06:02 -31.3 -31.4 0.196047E+09 183.50 04-JAN-11:50 -28.4 -28.7
February 0.769453E+09 1111.47 17-FEB-06:02 -31.6 -31.7 0.178940E+09 183.50 17-FEB-08:09 -28.5 -28.7
March 0.112041E+10 848.72 01-MAR-07:02 -3.9 -4.1 0.215154E+09 185.59 31-MAR-16:00 8.90 3.27
April 0.133951E+10 1056.40 13-APR-17:01 19.03 7.22 0.192414E+09 186.50 20-APR-15:09 10.10 2.61
May 0.178140E+10 1178.59 26-MAY-06:05 19.50 15.69 0.207750E+09 189.69 31-MAY-16:49 10.23 7.64
June 0.194380E+10 1257.85 30-JUN-06:03 26.60 21.93 0.207288E+09 187.84 02-JUN-14:20 13.50 7.41
July 0.202221E+10 1174.51 21-JUL-06:05 19.27 18.71 0.192076E+09 183.49 21-JUL-06:19 19.63 18.95
August 0.199275E+10 1157.59 09-AUG-06:05 18.98 17.80 0.215653E+09 186.35 17-AUG-15:09 11.28 10.15
September 0.162854E+10 1141.23 01-SEP-17:01 24.32 17.90 0.193096E+09 190.60 21-SEP-14:39 9.60 7.97
October 0.139905E+10 1076.39 21-OCT-14:01 20.00 11.40 0.199032E+09 185.83 03-OCT-14:00 7.80 4.58
November 0.110348E+10 956.10 01-NOV-17:01 15.95 12.47 0.195407E+09 183.84 02-NOV-13:00 3.30 1.67
December 0.748412E+09 1025.40 20-DEC-06:02 -28.9 -29.1 0.190143E+09 183.50 20-DEC-09:09 -29.0 -29.2
                     
Annual Sum or Average 0.164935E+11         0.238300E+10        
Minimum of Months 0.644493E+09 848.72   -31.6 -31.7 0.178940E+09 183.49   -29.0 -29.2
Maximum of Months 0.202221E+10 1257.85   26.60 21.93 0.215653E+09 190.60   19.63 18.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.144599E+10 1863.36 13-JAN-06:02 -31.3 -31.4 0.288940E+09 269.13 09-JAN-08:50 -31.9 -32.0
February 0.153576E+10 1915.94 17-FEB-06:02 -31.6 -31.7 0.263583E+09 269.12 17-FEB-08:09 -28.5 -28.7
March 0.199085E+10 1454.23 15-MAR-05:03 -22.2 -22.5 0.316394E+09 269.53 31-MAR-16:00 8.90 3.27
April 0.214650E+10 1657.56 13-APR-17:01 19.03 7.22 0.282071E+09 270.30 19-APR-16:00 6.70 0.76
May 0.262874E+10 1798.04 26-MAY-06:05 19.50 15.69 0.303381E+09 270.72 31-MAY-16:00 10.20 7.61
June 0.278944E+10 1969.70 30-JUN-06:03 26.60 21.93 0.302379E+09 269.10 19-JUN-06:40 18.13 17.37
July 0.289002E+10 1832.96 21-JUL-06:05 19.27 18.71 0.280234E+09 269.10 05-JUL-06:40 20.60 19.78
August 0.290677E+10 1793.29 25-AUG-17:01 27.52 19.43 0.314957E+09 269.10 28-AUG-06:40 14.63 13.74
September 0.246112E+10 1788.14 01-SEP-17:01 24.32 17.90 0.282047E+09 273.50 21-SEP-16:00 8.90 8.32
October 0.223276E+10 1689.02 21-OCT-14:01 20.00 11.40 0.291858E+09 270.51 27-OCT-16:00 5.60 4.79
November 0.191688E+10 1502.04 01-NOV-17:01 15.95 12.47 0.287265E+09 269.10 27-NOV-08:09 -6.7 -7.0
December 0.158147E+10 1700.15 20-DEC-06:02 -28.9 -29.1 0.280160E+09 269.17 08-DEC-07:30 -20.2 -20.6
                     
Annual Sum or Average 0.265263E+11         0.349327E+10        
Minimum of Months 0.144599E+10 1454.23   -31.6 -31.7 0.263583E+09 269.10   -31.9 -32.0
Maximum of Months 0.290677E+10 1969.70   27.52 21.93 0.316394E+09 273.50   20.60 19.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 85953192.43 151.16 27-JAN-16:15 -15.2 -16.1 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.100394E+09 234.79 28-FEB-16:30 5.85 1.28 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.130333E+09 289.71 31-MAR-17:00 8.90 3.27 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.153388E+09 334.29 21-APR-17:00 12.20 3.28 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.195400E+09 297.34 18-MAY-17:00 28.20 16.09 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.211035E+09 311.52 30-JUN-17:00 31.10 21.38 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.225639E+09 283.05 21-JUL-16:57 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.228199E+09 329.49 25-AUG-17:00 27.80 19.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.182849E+09 374.23 01-SEP-17:00 24.40 17.92 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.152366E+09 361.22 19-OCT-16:35 20.17 13.05 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.115860E+09 226.66 17-NOV-16:00 10.00 3.18 0.00 0.00 01-NOV-00:10 3.60 0.50
December 87035952.70 105.94 20-DEC-06:05 -28.9 -29.1 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.186845E+10         0.00        
Minimum of Months 85953192.43 105.94   -28.9 -29.1 0.00 0.00   -23.1 -23.4
Maximum of Months 0.228199E+09 374.23   31.10 21.38 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.116932E+09 203.08 27-JAN-15:43 -14.4 -15.5 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.118903E+09 224.38 28-FEB-16:10 6.02 1.45 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.143045E+09 210.58 31-MAR-16:30 8.90 3.51 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.152579E+09 211.40 21-APR-16:20 11.87 3.15 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.179846E+09 199.51 18-MAY-17:00 28.20 16.09 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.193184E+09 208.09 30-JUN-17:00 31.10 21.38 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.202628E+09 196.69 21-JUL-16:57 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.207708E+09 218.80 25-AUG-16:50 27.88 19.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.173667E+09 232.54 01-SEP-16:20 25.53 17.75 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.153963E+09 260.95 19-OCT-15:50 21.78 13.55 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.129745E+09 219.54 17-NOV-15:40 10.20 3.26 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.112174E+09 116.26 02-DEC-06:12 -27.6 -27.8 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.188437E+10         0.00        
Minimum of Months 0.112174E+09 116.26   -27.6 -27.8 0.00 0.00   -23.1 -23.4
Maximum of Months 0.207708E+09 260.95   31.10 21.38 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.118109E+09 241.00 27-JAN-15:43 -14.4 -15.5 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.122107E+09 259.06 28-FEB-16:10 6.02 1.45 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.143586E+09 215.87 31-MAR-16:30 8.90 3.51 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.150283E+09 209.71 21-APR-16:10 11.78 3.11 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.169699E+09 184.77 18-MAY-17:00 28.20 16.09 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.181509E+09 190.69 30-JUN-17:00 31.10 21.38 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.190742E+09 178.07 21-JUL-16:57 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.196441E+09 208.05 25-AUG-16:50 27.88 19.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.166690E+09 226.64 01-SEP-16:20 25.53 17.75 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.150200E+09 270.99 19-OCT-16:00 21.70 13.54 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.129505E+09 235.05 17-NOV-15:40 10.20 3.26 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.112881E+09 148.44 20-DEC-15:40 -19.8 -20.4 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.183175E+10         0.00        
Minimum of Months 0.112881E+09 148.44   -19.8 -20.4 0.00 0.00   -23.1 -23.4
Maximum of Months 0.196441E+09 270.99   31.10 21.38 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.121815E+09 257.04 06-JAN-07:01 -35.0 -35.1 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.119456E+09 208.60 25-FEB-07:03 -29.3 -29.5 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.144079E+09 111.25 31-MAR-17:00 8.90 3.27 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.154365E+09 143.81 14-APR-17:00 14.40 6.71 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.194805E+09 173.02 18-MAY-17:00 28.20 16.09 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.216055E+09 195.80 30-JUN-17:00 31.10 21.38 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.223745E+09 189.31 21-JUL-16:57 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.221401E+09 176.13 25-AUG-17:00 27.80 19.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.179395E+09 164.19 01-SEP-17:00 24.40 17.92 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.154257E+09 136.82 20-OCT-17:00 16.70 9.67 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.134964E+09 106.91 01-NOV-17:00 16.70 12.78 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.125766E+09 157.16 02-DEC-07:03 -27.1 -27.3 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.199010E+10         0.00        
Minimum of Months 0.119456E+09 106.91   -35.0 -35.1 0.00 0.00   -23.1 -23.4
Maximum of Months 0.223745E+09 257.04   31.10 21.38 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.125312E+09 281.31 06-JAN-07:01 -35.0 -35.1 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.125222E+09 230.51 25-FEB-07:03 -29.3 -29.5 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.155326E+09 145.10 31-MAR-17:00 8.90 3.27 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.173045E+09 182.05 14-APR-17:00 14.40 6.71 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.225836E+09 218.51 18-MAY-17:00 28.20 16.09 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.253350E+09 242.98 30-JUN-17:00 31.10 21.38 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.257636E+09 235.82 21-JUL-16:57 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.258598E+09 220.70 25-AUG-17:00 27.80 19.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.210217E+09 210.89 01-SEP-17:00 24.40 17.92 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.177897E+09 179.58 20-OCT-17:00 16.70 9.67 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.150343E+09 146.92 01-NOV-17:00 16.70 12.78 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.132142E+09 179.93 02-DEC-07:03 -27.1 -27.3 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.224492E+10         0.00        
Minimum of Months 0.125222E+09 145.10   -35.0 -35.1 0.00 0.00   -23.1 -23.4
Maximum of Months 0.258598E+09 281.31   31.10 21.38 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.109522E+09 251.22 06-JAN-06:11 -34.6 -34.7 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.112923E+09 181.17 25-FEB-07:03 -29.3 -29.5 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.141897E+09 116.30 31-MAR-17:00 8.90 3.27 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.159787E+09 157.80 14-APR-17:00 14.40 6.71 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.210717E+09 198.08 18-MAY-17:00 28.20 16.09 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.237356E+09 224.46 30-JUN-17:00 31.10 21.38 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.244248E+09 217.36 21-JUL-16:57 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.243491E+09 201.66 25-AUG-17:00 27.80 19.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.196798E+09 191.86 01-SEP-17:00 24.40 17.92 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.164815E+09 158.26 20-OCT-17:00 16.70 9.67 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.137787E+09 121.69 02-NOV-17:00 3.30 1.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.117959E+09 129.17 02-DEC-06:12 -27.6 -27.8 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.207730E+10         0.00        
Minimum of Months 0.109522E+09 116.30   -34.6 -34.7 0.00 0.00   -23.1 -23.4
Maximum of Months 0.244248E+09 251.22   31.10 21.38 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 27229530.51 51.12 11-JAN-07:03 -27.1 -27.3 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 33734001.81 62.10 25-FEB-06:03 -29.4 -29.5 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 55421024.11 71.11 31-MAR-17:00 8.90 3.27 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 80514579.63 132.89 13-APR-17:00 19.40 7.36 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.141291E+09 206.31 18-MAY-17:00 28.20 16.09 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.169998E+09 357.75 30-JUN-06:01 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.184363E+09 218.17 21-JUL-16:53 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.179017E+09 230.82 10-AUG-06:01 15.10 14.70 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.127960E+09 198.13 01-SEP-17:00 24.40 17.92 0.00 0.00 01-SEP-00:10 19.75 18.15
October 92169715.27 141.79 19-OCT-16:55 19.40 12.77 0.00 0.00 01-OCT-00:10 7.52 6.57
November 59604242.97 98.52 01-NOV-17:00 16.70 12.78 0.00 0.00 01-NOV-00:10 3.60 0.50
December 33659499.70 55.24 02-DEC-06:03 -27.7 -27.9 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.118496E+10         0.00        
Minimum of Months 27229530.51 51.12   -29.4 -29.5 0.00 0.00   -23.1 -23.4
Maximum of Months 0.184363E+09 357.75   28.20 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.263996E+09 494.18 27-JAN-07:01 -22.7 -22.9 51255605.65 51.01 20-JAN-07:10 -7.3 -7.9
February 0.256160E+09 556.77 02-FEB-07:01 -25.0 -25.3 46960925.50 51.01 09-FEB-07:10 -2.7 -3.1
March 0.310774E+09 512.54 16-MAR-06:01 -22.9 -23.2 56380591.75 51.01 01-MAR-07:10 -3.9 -4.1
April 0.298993E+09 356.37 18-APR-06:02 12.38 7.00 50284540.15 51.01 11-APR-06:10 -2.8 -4.6
May 0.330302E+09 411.42 26-MAY-06:03 19.50 15.69 54110691.59 51.01 26-MAY-06:10 19.50 15.69
June 0.338569E+09 427.95 29-JUN-06:03 23.17 19.91 53986433.84 51.02 29-JUN-06:10 23.17 19.91
July 0.335078E+09 412.03 21-JUL-06:03 19.27 18.71 50129790.69 51.01 11-JUL-06:10 14.45 13.81
August 0.358124E+09 407.16 09-AUG-06:03 18.98 17.80 56349016.50 51.02 09-AUG-06:10 18.98 17.80
September 0.315131E+09 391.75 01-SEP-06:01 16.10 15.79 50284917.68 51.01 13-SEP-06:10 4.78 4.42
October 0.302611E+09 334.69 20-OCT-06:02 5.92 5.92 51931148.69 51.01 06-OCT-06:10 -3.6 -4.0
November 0.280827E+09 372.76 29-NOV-07:01 -18.4 -18.6 51059835.66 51.01 30-NOV-07:10 -1.6 -3.1
December 0.268533E+09 524.98 14-DEC-07:01 -24.1 -24.4 49828563.94 51.01 15-DEC-07:10 -13.4 -14.1
                     
Annual Sum or Average 0.365910E+10         0.622562E+09        
Minimum of Months 0.256160E+09 334.69   -25.0 -25.3 46960925.50 51.01   -13.4 -14.1
Maximum of Months 0.358124E+09 556.77   23.17 19.91 56380591.75 51.02   23.17 19.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.499013E+09 777.16 27-JAN-07:01 -22.7 -22.9 0.127122E+09 127.53 20-JAN-07:10 -7.3 -7.9
February 0.485020E+09 837.25 24-FEB-07:01 -23.9 -24.2 0.116691E+09 127.53 09-FEB-07:10 -2.7 -3.1
March 0.591449E+09 808.25 16-MAR-06:01 -22.9 -23.2 0.140328E+09 127.53 01-MAR-07:10 -3.9 -4.1
April 0.573875E+09 591.56 18-APR-06:02 12.38 7.00 0.125234E+09 127.53 28-APR-06:10 -3.4 -4.5
May 0.649938E+09 680.32 26-MAY-06:03 19.50 15.69 0.134938E+09 127.53 26-MAY-06:10 19.50 15.69
June 0.672452E+09 742.91 30-JUN-06:03 26.60 21.93 0.134682E+09 127.54 29-JUN-06:10 23.17 19.91
July 0.669131E+09 681.68 21-JUL-06:03 19.27 18.71 0.125035E+09 127.53 11-JUL-06:10 14.45 13.81
August 0.705775E+09 672.76 09-AUG-06:03 18.98 17.80 0.140493E+09 127.54 09-AUG-06:10 18.98 17.80
September 0.612848E+09 651.28 01-SEP-06:02 16.10 15.79 0.125294E+09 127.53 13-SEP-06:10 4.78 4.42
October 0.584726E+09 554.11 20-OCT-06:02 5.92 5.92 0.129386E+09 127.53 06-OCT-06:10 -3.6 -4.0
November 0.541910E+09 601.94 29-NOV-07:01 -18.4 -18.6 0.127213E+09 127.53 30-NOV-07:10 -1.6 -3.1
December 0.514207E+09 675.18 01-DEC-07:01 -20.3 -20.5 0.123848E+09 127.53 07-DEC-07:10 -7.8 -7.9
                     
Annual Sum or Average 0.710034E+10         0.155026E+10        
Minimum of Months 0.485020E+09 554.11   -23.9 -24.2 0.116691E+09 127.53   -7.8 -7.9
Maximum of Months 0.705775E+09 837.25   26.60 21.93 0.140493E+09 127.54   23.17 19.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.601007E+09 891.47 27-JAN-07:01 -22.7 -22.9 0.152562E+09 153.03 20-JAN-07:10 -7.3 -7.9
February 0.588183E+09 1012.77 24-FEB-07:01 -23.9 -24.2 0.140136E+09 153.04 09-FEB-07:10 -2.7 -3.1
March 0.724721E+09 968.25 16-MAR-06:01 -22.9 -23.2 0.168665E+09 153.04 01-MAR-07:10 -3.9 -4.1
April 0.715778E+09 712.20 18-APR-06:02 12.38 7.00 0.150755E+09 153.04 12-APR-06:10 -0.8 -2.8
May 0.822292E+09 821.13 26-MAY-06:03 19.50 15.69 0.162555E+09 153.04 26-MAY-06:10 19.50 15.69
June 0.854350E+09 897.99 30-JUN-06:03 26.60 21.93 0.162318E+09 153.04 29-JUN-06:10 23.17 19.91
July 0.848601E+09 822.11 21-JUL-06:03 19.27 18.71 0.150733E+09 153.04 11-JUL-06:10 14.45 13.81
August 0.894356E+09 811.71 09-AUG-06:03 18.98 17.80 0.169282E+09 153.05 09-AUG-06:10 18.98 17.80
September 0.778917E+09 787.15 01-SEP-06:02 16.10 15.79 0.151127E+09 153.03 13-SEP-06:10 4.78 4.42
October 0.741985E+09 668.56 20-OCT-06:02 5.92 5.92 0.155939E+09 153.04 06-OCT-06:10 -3.6 -4.0
November 0.679464E+09 729.91 29-NOV-07:01 -18.4 -18.6 0.153166E+09 153.04 30-NOV-07:10 -1.6 -3.1
December 0.627946E+09 818.82 08-DEC-07:01 -20.4 -20.7 0.148824E+09 153.03 01-DEC-07:10 -20.3 -20.5
                     
Annual Sum or Average 0.887760E+10         0.186606E+10        
Minimum of Months 0.588183E+09 668.56   -23.9 -24.2 0.140136E+09 153.03   -20.3 -20.5
Maximum of Months 0.894356E+09 1012.77   26.60 21.93 0.169282E+09 153.05   23.17 19.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.202990E+09 550.98 06-JAN-06:04 -34.5 -34.6 87824703.35 101.80 27-JAN-16:10 -14.8 -15.8
February 0.308658E+09 456.74 28-FEB-15:08 6.10 1.53 81962863.49 106.76 28-FEB-15:20 6.10 1.53
March 0.542520E+09 877.30 31-MAR-09:30 0.85 -1.2 0.102679E+09 106.76 20-MAR-14:30 0.30 -0.4
April 0.881860E+09 1855.56 21-APR-06:01 -3.1 -4.6 95987419.76 111.73 21-APR-06:10 -3.1 -4.6
May 0.128808E+10 2350.15 18-MAY-06:01 15.50 11.62 0.106772E+09 119.03 18-MAY-06:10 15.50 11.62
June 0.155302E+10 2657.45 29-JUN-06:03 23.17 19.91 0.107796E+09 119.04 29-JUN-06:10 23.17 19.91
July 0.165717E+10 2556.85 21-JUL-06:03 19.27 18.71 0.100578E+09 119.04 11-JUL-06:10 14.45 13.81
August 0.149102E+10 2449.06 09-AUG-06:03 18.98 17.80 0.112285E+09 118.96 25-AUG-06:10 9.05 8.95
September 0.105396E+10 2309.33 01-SEP-06:01 16.10 15.79 98526125.44 115.27 08-SEP-06:10 10.68 10.02
October 0.704979E+09 1823.87 20-OCT-06:01 5.92 5.92 98272866.69 110.87 20-OCT-06:10 5.92 5.92
November 0.457473E+09 550.29 17-NOV-16:00 10.00 3.18 92811749.12 106.76 01-NOV-14:20 17.97 13.31
December 0.239201E+09 412.34 21-DEC-06:04 -27.3 -27.5 85467443.65 104.05 28-DEC-17:00 -2.8 -4.1
                     
Annual Sum or Average 0.103809E+11         0.117096E+10        
Minimum of Months 0.202990E+09 412.34   -34.5 -34.6 81962863.49 101.80   -14.8 -15.8
Maximum of Months 0.165717E+10 2657.45   23.17 19.91 0.112285E+09 119.04   23.17 19.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.262880E+09 369.62 06-JAN-09:00 -35.6 -35.7 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.267386E+09 331.52 17-FEB-06:12 -31.5 -31.6 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.335289E+09 268.49 31-MAR-17:00 8.90 3.27 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.403696E+09 483.29 21-APR-07:45 2.93 -1.2 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.517855E+09 1042.54 17-MAY-06:01 11.65 8.32 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.595182E+09 1210.03 22-JUN-06:01 15.97 14.47 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.635048E+09 1263.02 14-JUL-06:02 17.57 17.07 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.610256E+09 1009.03 25-AUG-06:01 9.05 8.95 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.470855E+09 636.48 08-SEP-06:01 10.68 10.02 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.374229E+09 383.94 20-OCT-17:00 16.70 9.67 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.305828E+09 257.85 17-NOV-18:00 4.40 -0.1 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.274849E+09 292.15 02-DEC-06:17 -27.6 -27.8 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.505335E+10         0.00        
Minimum of Months 0.262880E+09 257.85   -35.6 -35.7 0.00 0.00   -23.1 -23.4
Maximum of Months 0.635048E+09 1263.02   17.57 17.07 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.242369E+10 3417.52 27-JAN-15:15 -14.4 -15.5 0.118011E+10 1125.50 19-JAN-07:19 -3.3 -3.6
February 0.270645E+10 3701.64 28-FEB-15:30 6.10 1.53 0.109924E+10 1153.65 28-FEB-15:39 6.10 1.53
March 0.347781E+10 3723.65 31-MAR-15:10 8.40 2.80 0.133993E+10 1157.52 31-MAR-15:20 8.50 2.99
April 0.379795E+10 4093.48 13-APR-15:30 20.00 8.07 0.121024E+10 1212.27 14-APR-06:10 2.07 1.49
May 0.473721E+10 4870.77 26-MAY-06:03 19.50 15.69 0.131967E+10 1245.73 19-MAY-06:10 14.47 10.08
June 0.501880E+10 5422.90 30-JUN-06:03 26.60 21.93 0.131936E+10 1246.05 16-JUN-06:10 10.78 9.76
July 0.525194E+10 4880.96 21-JUL-06:03 19.27 18.71 0.123019E+10 1246.88 27-JUL-06:10 12.25 11.42
August 0.542701E+10 4792.31 09-AUG-06:03 18.98 17.80 0.137929E+10 1254.75 03-AUG-06:10 11.20 10.58
September 0.450881E+10 4758.08 01-SEP-15:30 26.10 17.71 0.122363E+10 1242.43 08-SEP-06:10 10.68 10.02
October 0.389071E+10 4601.09 19-OCT-14:50 22.12 13.62 0.125034E+10 1236.94 20-OCT-06:10 5.92 5.92
November 0.316067E+10 3680.49 17-NOV-14:00 10.60 3.41 0.121122E+10 1148.28 02-NOV-06:10 4.82 3.20
December 0.243688E+10 2683.41 20-DEC-14:50 -19.1 -19.8 0.115190E+10 1125.51 07-DEC-07:19 -7.8 -7.9
                     
Annual Sum or Average 0.468379E+11         0.149151E+11        
Minimum of Months 0.242369E+10 2683.41   -19.1 -19.8 0.109924E+10 1125.50   -7.8 -7.9
Maximum of Months 0.542701E+10 5422.90   26.60 21.93 0.137929E+10 1254.75   14.47 11.42



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.540849E+09 947.28 06-JAN-07:01 -35.0 -35.1 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.554240E+09 1280.07 09-FEB-07:01 -2.7 -3.1 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.693585E+09 1320.25 30-MAR-06:01 -2.8 -3.0 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.705851E+09 1362.77 14-APR-06:02 2.07 1.49 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.800890E+09 1562.65 18-MAY-06:01 15.50 11.62 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.831974E+09 1751.90 30-JUN-06:01 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.837910E+09 1526.31 13-JUL-06:01 15.37 15.25 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.878874E+09 1545.23 10-AUG-06:01 15.10 14.70 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.766685E+09 1405.82 01-SEP-06:01 16.10 15.79 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.699902E+09 1383.32 20-OCT-06:02 5.92 5.92 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.615353E+09 1293.95 17-NOV-07:01 -3.8 -4.8 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.549752E+09 581.80 01-DEC-18:00 -20.6 -21.0 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.847586E+10         0.00        
Minimum of Months 0.540849E+09 581.80   -35.0 -35.1 0.00 0.00   -23.1 -23.4
Maximum of Months 0.878874E+09 1751.90   26.60 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.320748E+09 448.16 26-JAN-07:03 -33.1 -33.2 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.346945E+09 453.34 14-FEB-07:03 -33.0 -33.2 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.424984E+09 277.64 15-MAR-05:03 -22.2 -22.5 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.457283E+09 320.00 13-APR-17:01 19.03 7.22 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.551303E+09 355.80 26-MAY-06:05 19.50 15.69 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.579918E+09 376.99 30-JUN-06:03 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.628778E+09 352.63 21-JUL-06:05 19.27 18.71 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.625458E+09 350.23 09-AUG-06:05 18.98 17.80 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.536138E+09 345.33 01-SEP-17:01 24.32 17.90 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.473270E+09 330.68 21-OCT-14:01 20.00 11.40 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.398366E+09 288.94 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.347575E+09 386.05 20-DEC-07:03 -29.1 -29.3 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.569077E+10         0.00        
Minimum of Months 0.320748E+09 277.64   -33.1 -33.2 0.00 0.00   -23.1 -23.4
Maximum of Months 0.628778E+09 453.34   26.60 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.545443E+09 1154.98 27-JAN-07:01 -22.7 -22.9 58708743.27 67.01 20-JAN-07:10 -7.3 -7.9
February 0.543755E+09 1238.93 24-FEB-07:01 -23.9 -24.2 54057158.56 68.58 09-FEB-07:10 -2.7 -3.1
March 0.669594E+09 1205.00 16-MAR-06:01 -22.9 -23.2 65037932.08 68.87 31-MAR-06:10 -3.8 -4.6
April 0.649777E+09 853.14 18-APR-06:02 12.38 7.00 58031266.58 68.87 13-APR-06:10 -3.2 -4.5
May 0.721890E+09 999.91 26-MAY-06:03 19.50 15.69 62506206.32 68.87 18-MAY-06:10 15.50 11.62
June 0.741373E+09 1099.65 30-JUN-06:03 26.60 21.93 62358850.23 68.87 16-JUN-06:10 10.78 9.76
July 0.741769E+09 1009.89 21-JUL-06:03 19.27 18.71 57924008.11 68.87 27-JUL-06:10 12.25 11.42
August 0.784152E+09 983.23 09-AUG-06:03 18.98 17.80 65074673.36 68.87 03-AUG-06:10 11.20 10.58
September 0.688893E+09 964.13 01-SEP-06:02 16.10 15.79 58052668.14 68.87 29-SEP-06:10 7.30 7.25
October 0.655322E+09 818.79 20-OCT-06:02 5.92 5.92 59945993.89 68.87 26-OCT-06:10 7.20 5.86
November 0.599930E+09 867.15 29-NOV-07:01 -18.4 -18.6 58912319.50 68.87 17-NOV-07:10 -3.8 -4.8
December 0.572203E+09 977.11 01-DEC-07:01 -20.3 -20.5 57322203.77 67.40 07-DEC-07:10 -7.8 -7.9
                     
Annual Sum or Average 0.791410E+10         0.717932E+09        
Minimum of Months 0.543755E+09 818.79   -23.9 -24.2 54057158.56 67.01   -7.8 -7.9
Maximum of Months 0.784152E+09 1238.93   26.60 21.93 65074673.36 68.87   15.50 11.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.540205E+09 965.87 27-JAN-07:01 -22.7 -22.9 61549407.54 69.73 20-JAN-07:10 -7.3 -7.9
February 0.549143E+09 1359.14 24-FEB-07:01 -23.9 -24.2 56922965.57 72.46 09-FEB-07:10 -2.7 -3.1
March 0.685190E+09 1315.12 16-MAR-06:01 -22.9 -23.2 68586389.16 72.69 30-MAR-06:10 -2.8 -3.0
April 0.684630E+09 953.04 18-APR-06:02 12.38 7.00 61314768.21 72.70 19-APR-06:10 0.87 -1.2
May 0.781775E+09 1115.74 26-MAY-06:03 19.50 15.69 66137940.14 72.70 26-MAY-06:10 19.50 15.69
June 0.805377E+09 1220.58 30-JUN-06:03 26.60 21.93 65987162.23 72.70 30-JUN-06:10 26.60 21.93
July 0.809834E+09 1117.04 21-JUL-06:03 19.27 18.71 61330238.41 72.70 27-JUL-06:10 12.25 11.42
August 0.852894E+09 1099.01 09-AUG-06:03 18.98 17.80 68867330.11 72.70 03-AUG-06:10 11.20 10.58
September 0.743758E+09 1066.27 01-SEP-06:02 16.10 15.79 61419938.83 72.70 29-SEP-06:10 7.30 7.25
October 0.693426E+09 903.88 20-OCT-06:02 5.92 5.92 63336378.70 72.70 26-OCT-06:10 7.20 5.86
November 0.617571E+09 943.43 29-NOV-07:01 -18.4 -18.6 62103287.01 72.69 17-NOV-07:10 -3.8 -4.8
December 0.563704E+09 1069.30 01-DEC-07:01 -20.3 -20.5 60184274.87 70.40 01-DEC-07:10 -20.3 -20.5
                     
Annual Sum or Average 0.832751E+10         0.757740E+09        
Minimum of Months 0.540205E+09 903.88   -23.9 -24.2 56922965.57 69.73   -20.3 -20.5
Maximum of Months 0.852894E+09 1359.14   26.60 21.93 68867330.11 72.70   26.60 21.93



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 56739691.57 83.78 26-JAN-06:01 -32.9 -33.0 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 58815583.10 74.30 25-FEB-06:01 -29.4 -29.5 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 68213764.72 54.09 16-MAR-05:01 -24.2 -24.4 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 71043333.65 48.63 13-APR-16:00 20.00 8.07 0.00 0.00 01-APR-00:10 3.52 0.37
May 84331950.16 50.20 18-MAY-17:00 28.20 16.09 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 89937083.40 50.49 30-JUN-17:00 31.10 21.38 0.00 0.00 01-JUN-00:10 11.35 8.93
July 95345357.57 50.21 21-JUL-17:00 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 96438796.36 50.88 25-AUG-17:00 27.80 19.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 81493796.76 50.92 01-SEP-17:00 24.40 17.92 0.00 0.00 01-SEP-00:10 19.75 18.15
October 69724170.03 51.64 19-OCT-16:00 21.70 13.54 0.00 0.00 01-OCT-00:10 7.52 6.57
November 61402775.19 50.30 17-NOV-13:10 10.10 3.23 0.00 0.00 01-NOV-00:10 3.60 0.50
December 56806001.96 69.24 02-DEC-06:01 -27.7 -27.9 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.890292E+09         0.00        
Minimum of Months 56739691.57 48.63   -32.9 -33.0 0.00 0.00   -23.1 -23.4
Maximum of Months 96438796.36 83.78   31.10 21.38 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.112670E+09 178.18 26-JAN-06:01 -32.9 -33.0 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.121081E+09 176.42 17-FEB-06:12 -31.5 -31.6 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.151287E+09 116.20 16-MAR-05:01 -24.2 -24.4 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.161901E+09 101.60 13-APR-16:00 20.00 8.07 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.200811E+09 107.68 18-MAY-17:00 28.20 16.09 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.218725E+09 109.14 30-JUN-17:00 31.10 21.38 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.232276E+09 108.90 21-JUL-17:00 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.230401E+09 108.45 25-AUG-17:00 27.80 19.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.187504E+09 107.62 01-SEP-17:00 24.40 17.92 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.162748E+09 105.18 19-OCT-16:00 21.70 13.54 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.141211E+09 94.01 01-NOV-15:00 18.30 13.43 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.127620E+09 154.83 02-DEC-06:12 -27.6 -27.8 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.204823E+10         0.00        
Minimum of Months 0.112670E+09 94.01   -32.9 -33.0 0.00 0.00   -23.1 -23.4
Maximum of Months 0.232276E+09 178.18   31.10 21.38 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.139788E+09 214.23 26-JAN-06:01 -32.9 -33.0 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.152704E+09 212.53 17-FEB-06:12 -31.5 -31.6 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.192350E+09 139.66 16-MAR-05:01 -24.2 -24.4 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.208836E+09 125.06 13-APR-16:00 20.00 8.07 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.258573E+09 133.19 25-MAY-17:00 29.20 19.29 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.281680E+09 135.33 30-JUN-17:00 31.10 21.38 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.298715E+09 134.87 21-JUL-16:57 25.00 20.76 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.294308E+09 133.98 25-AUG-17:00 27.80 19.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.243120E+09 133.37 01-SEP-17:00 24.40 17.92 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.214442E+09 130.02 19-OCT-16:00 21.70 13.54 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.185825E+09 117.62 01-NOV-15:00 18.30 13.43 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.163761E+09 187.40 02-DEC-06:12 -27.6 -27.8 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.263410E+10         0.00        
Minimum of Months 0.139788E+09 117.62   -32.9 -33.0 0.00 0.00   -23.1 -23.4
Maximum of Months 0.298715E+09 214.23   31.10 21.38 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 32953089.16 98.67 07-JAN-15:02 -16.8 -17.4 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 50603948.41 123.78 17-FEB-06:03 -31.6 -31.7 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 97334191.44 121.12 31-MAR-09:50 1.42 -0.9 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.168845E+09 274.73 22-APR-09:10 11.47 3.74 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.256264E+09 365.51 17-MAY-08:45 20.55 13.71 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.311731E+09 431.78 15-JUN-06:01 11.57 10.07 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.344578E+09 369.25 07-JUL-09:00 18.30 13.08 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.296917E+09 361.70 25-AUG-09:10 20.97 17.06 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.210576E+09 329.91 01-SEP-09:20 20.57 17.75 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.131641E+09 206.32 19-OCT-09:15 12.03 8.66 0.00 0.00 01-OCT-00:10 7.52 6.57
November 76672023.59 88.21 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 40962394.89 96.96 02-DEC-17:10 -20.0 -20.4 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.201908E+10         0.00        
Minimum of Months 32953089.16 88.21   -31.6 -31.7 0.00 0.00   -23.1 -23.4
Maximum of Months 0.344578E+09 431.78   20.97 17.75 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.188358E+10 2306.76 20-JAN-07:01 -7.3 -7.9 0.290056E+09 324.68 20-JAN-07:10 -7.3 -7.9
February 0.194116E+10 3207.76 09-FEB-07:01 -2.7 -3.1 0.271265E+09 332.67 09-FEB-07:10 -2.7 -3.1
March 0.249673E+10 3420.75 30-MAR-06:02 -2.8 -3.0 0.330868E+09 341.79 30-MAR-06:10 -2.8 -3.0
April 0.276160E+10 3701.36 18-APR-06:02 12.38 7.00 0.298919E+09 354.75 14-APR-06:10 2.07 1.49
May 0.361467E+10 4723.30 26-MAY-06:05 19.50 15.69 0.326135E+09 359.24 26-MAY-06:10 19.50 15.69
June 0.397281E+10 5090.81 30-JUN-06:03 26.60 21.93 0.327068E+09 359.25 29-JUN-06:10 23.17 19.91
July 0.412831E+10 4720.72 21-JUL-06:05 19.27 18.71 0.304757E+09 359.23 27-JUL-06:10 12.25 11.42
August 0.422050E+10 4654.65 09-AUG-06:05 18.98 17.80 0.341520E+09 359.25 09-AUG-06:10 18.98 17.80
September 0.344720E+10 4424.49 01-SEP-06:02 16.10 15.79 0.303055E+09 359.22 15-SEP-06:10 5.87 5.35
October 0.295692E+10 3704.69 20-OCT-06:02 5.92 5.92 0.310148E+09 359.14 20-OCT-06:10 5.92 5.92
November 0.244673E+10 3530.71 02-NOV-06:02 4.82 3.20 0.301235E+09 348.64 02-NOV-06:10 4.82 3.20
December 0.205268E+10 3132.28 07-DEC-07:01 -7.8 -7.9 0.286140E+09 328.40 07-DEC-07:10 -7.8 -7.9
                     
Annual Sum or Average 0.359229E+11         0.369117E+10        
Minimum of Months 0.188358E+10 2306.76   -7.8 -7.9 0.271265E+09 324.68   -7.8 -7.9
Maximum of Months 0.422050E+10 5090.81   26.60 21.93 0.341520E+09 359.25   23.17 19.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.757588E+09 1189.06 06-JAN-07:01 -35.0 -35.1 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.776440E+09 1758.56 09-FEB-07:01 -2.7 -3.1 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.100557E+10 1838.25 30-MAR-06:02 -2.8 -3.0 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.107964E+10 1907.28 14-APR-06:02 2.07 1.49 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.130994E+10 2401.01 26-MAY-06:03 19.50 15.69 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.139486E+10 2494.91 29-JUN-06:03 23.17 19.91 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.141709E+10 2419.61 21-JUL-06:03 19.27 18.71 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.148288E+10 2349.38 09-AUG-06:03 18.98 17.80 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.125221E+10 2249.39 01-SEP-06:01 16.10 15.79 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.110288E+10 1937.52 20-OCT-06:02 5.92 5.92 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.930373E+09 1837.89 02-NOV-06:02 4.82 3.20 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.798378E+09 1251.17 01-DEC-07:01 -20.3 -20.5 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.133078E+11         0.00        
Minimum of Months 0.757588E+09 1189.06   -35.0 -35.1 0.00 0.00   -23.1 -23.4
Maximum of Months 0.148288E+10 2494.91   23.17 19.91 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 47963858.41 160.59 07-JAN-15:02 -16.8 -17.4 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 59694561.88 115.11 08-FEB-18:01 0.82 -2.4 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 91146853.80 115.39 29-MAR-17:01 4.90 1.46 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.127366E+09 163.65 13-APR-17:01 19.03 7.22 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.214732E+09 177.96 25-MAY-17:01 29.23 19.28 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.250744E+09 194.31 30-JUN-06:03 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.290643E+09 180.58 21-JUL-06:05 19.27 18.71 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.275943E+09 178.29 25-AUG-17:01 27.52 19.43 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.206924E+09 178.00 01-SEP-17:01 24.32 17.90 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.147720E+09 167.54 21-OCT-14:01 20.00 11.40 0.00 0.00 01-OCT-00:10 7.52 6.57
November 94620365.46 147.32 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 59571664.64 152.97 02-DEC-15:03 -17.4 -18.2 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.186707E+10         0.00        
Minimum of Months 47963858.41 115.11   -17.4 -18.2 0.00 0.00   -23.1 -23.4
Maximum of Months 0.290643E+09 194.31   29.23 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 2 X-RAY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.104052E+11 16333.96 06-JAN-07:01 -35.0 -35.1 0.841322E+09 773.61 27-JAN-17:00 -17.8 -18.3
February 0.962537E+10 16007.09 14-FEB-07:01 -33.0 -33.2 0.779007E+09 774.93 08-FEB-17:00 1.10 -2.2
March 0.112355E+11 11371.43 16-MAR-06:01 -22.9 -23.2 0.942335E+09 776.96 31-MAR-16:00 8.90 3.27
April 0.105705E+11 9205.61 18-APR-05:01 11.78 6.46 0.830403E+09 777.87 19-APR-16:00 6.70 0.76
May 0.115263E+11 10727.83 26-MAY-05:01 19.40 15.68 0.864827E+09 765.19 22-MAY-06:10 9.72 6.65
June 0.116404E+11 10964.31 29-JUN-05:01 22.30 19.60 0.846026E+09 765.22 16-JUN-06:10 10.78 9.76
July 0.114411E+11 10585.15 21-JUL-05:01 17.98 17.55 0.782686E+09 765.26 11-JUL-06:10 14.45 13.81
August 0.121311E+11 10504.83 09-AUG-05:01 18.40 17.29 0.881864E+09 765.20 09-AUG-06:10 18.98 17.80
September 0.108443E+11 10158.07 01-SEP-05:01 15.68 15.63 0.812019E+09 775.45 28-SEP-16:00 9.40 6.26
October 0.107544E+11 8880.69 20-OCT-05:01 7.52 7.52 0.860809E+09 776.24 27-OCT-16:00 5.60 4.79
November 0.103404E+11 10287.00 29-NOV-06:01 -20.3 -20.5 0.849573E+09 778.12 17-NOV-17:00 4.40 -0.1
December 0.103754E+11 14529.60 20-DEC-07:01 -29.1 -29.3 0.823409E+09 774.84 01-DEC-17:00 -20.6 -21.0
                     
Annual Sum or Average 0.130890E+12         0.101143E+11        
Minimum of Months 0.962537E+10 8880.69   -35.0 -35.1 0.779007E+09 765.19   -20.6 -21.0
Maximum of Months 0.121311E+11 16333.96   22.30 19.60 0.942335E+09 778.12   18.98 17.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 45607234.91 59.65 27-JAN-15:55 -14.4 -15.5 7155185.89 8.01 18-JAN-13:30 -3.9 -4.0
February 47010857.92 72.57 08-FEB-17:00 3.30 -1.0 6641695.96 8.01 28-FEB-13:09 2.48 -0.8
March 66395558.69 84.79 23-MAR-15:30 0.85 -3.6 8127344.19 8.01 24-MAR-14:09 2.62 -0.0
April 74316576.70 100.41 21-APR-16:00 11.70 3.07 7333671.45 8.06 14-APR-06:10 2.07 1.49
May 94788238.50 103.26 18-MAY-15:40 28.63 16.39 7976924.26 8.04 17-MAY-06:10 11.65 8.32
June 0.100483E+09 106.35 16-JUN-06:01 10.78 9.76 7976867.54 8.15 16-JUN-06:10 10.78 9.76
July 99907281.25 103.79 19-JUL-15:30 26.15 18.39 7395925.82 8.09 27-JUL-06:10 12.25 11.42
August 0.101550E+09 103.81 03-AUG-06:01 11.20 10.58 8308503.33 8.15 03-AUG-06:10 11.20 10.58
September 84740603.19 100.68 22-SEP-06:01 9.40 9.40 7390824.69 8.14 22-SEP-06:10 9.40 9.40
October 74234459.61 88.34 20-OCT-15:00 18.90 10.05 7587923.30 8.05 26-OCT-06:10 7.20 5.86
November 59803168.99 75.01 01-NOV-16:40 17.07 12.94 7364443.42 8.01 30-NOV-15:09 4.22 1.08
December 47663781.89 58.40 05-DEC-18:00 0.00 -0.0 7007327.87 8.01 13-DEC-15:09 -11.0 -11.3
                     
Annual Sum or Average 0.896501E+09         90266637.74        
Minimum of Months 45607234.91 58.40   -14.4 -15.5 6641695.96 8.01   -11.0 -11.3
Maximum of Months 0.101550E+09 106.35   28.63 18.39 8308503.33 8.15   12.25 11.42



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 79185445.19 149.53 07-JAN-15:02 -16.8 -17.4 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.109805E+09 134.76 24-FEB-06:03 -23.0 -23.3 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.177813E+09 138.09 31-MAR-17:00 8.90 3.27 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.254859E+09 273.96 13-APR-16:50 19.50 7.48 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.414999E+09 476.45 18-MAY-15:50 28.57 16.34 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.499688E+09 890.80 30-JUN-06:03 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.551382E+09 708.74 14-JUL-06:02 17.57 17.07 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.524091E+09 689.99 10-AUG-06:01 15.10 14.70 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.370541E+09 451.64 01-SEP-16:00 26.10 17.62 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.270841E+09 292.08 20-OCT-15:50 18.40 9.93 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.185908E+09 165.73 01-NOV-17:00 16.70 12.78 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.100705E+09 154.60 02-DEC-17:10 -20.0 -20.4 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.353982E+10         0.00        
Minimum of Months 79185445.19 134.76   -23.0 -23.3 0.00 0.00   -23.1 -23.4
Maximum of Months 0.551382E+09 890.80   28.57 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.131576E+09 177.14 27-JAN-15:55 -14.4 -15.5 18598551.20 20.59 18-JAN-13:09 -4.2 -4.4
February 0.136715E+09 215.18 08-FEB-17:25 2.20 -1.6 17268088.84 20.59 09-FEB-07:00 -2.2 -2.6
March 0.193070E+09 242.17 23-MAR-15:30 0.85 -3.6 21118319.53 20.88 30-MAR-06:10 -2.8 -3.0
April 0.214270E+09 322.29 14-APR-06:01 2.07 1.49 19038705.94 21.57 14-APR-06:10 2.07 1.49
May 0.270567E+09 379.33 18-MAY-06:01 15.50 11.62 20693500.11 21.54 17-MAY-06:10 11.65 8.32
June 0.284532E+09 434.04 30-JUN-06:01 26.60 21.93 20687367.70 21.83 16-JUN-06:10 10.78 9.76
July 0.281380E+09 371.96 19-JUL-06:01 15.05 14.14 19194695.53 21.65 27-JUL-06:10 12.25 11.42
August 0.288843E+09 377.94 10-AUG-06:01 15.10 14.70 21546567.75 21.83 03-AUG-06:10 11.20 10.58
September 0.243734E+09 330.70 22-SEP-06:01 9.40 9.40 19175235.47 21.78 22-SEP-06:10 9.40 9.40
October 0.215679E+09 325.75 26-OCT-06:01 7.20 5.86 19694799.86 21.52 26-OCT-06:10 7.20 5.86
November 0.174072E+09 217.94 17-NOV-17:00 6.70 1.28 19132763.33 20.62 02-NOV-06:10 4.82 3.20
December 0.137211E+09 173.63 28-DEC-18:00 -2.8 -4.1 18212491.77 20.59 13-DEC-15:09 -11.0 -11.3
                     
Annual Sum or Average 0.257165E+10         0.234361E+09        
Minimum of Months 0.131576E+09 173.63   -14.4 -15.5 17268088.84 20.59   -11.0 -11.3
Maximum of Months 0.288843E+09 434.04   26.60 21.93 21546567.75 21.83   12.25 11.42



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 4071811.60 76.65 07-JAN-15:02 -16.8 -17.4 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 8138612.26 54.78 08-FEB-18:01 0.82 -2.4 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 19017974.50 55.19 28-MAR-17:01 7.20 3.38 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 45604375.49 78.80 13-APR-17:01 19.03 7.22 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.111614E+09 95.14 25-MAY-19:00 27.20 18.49 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.139829E+09 104.95 30-JUN-17:00 31.10 21.38 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.165202E+09 95.19 29-JUL-18:30 27.20 20.69 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.144664E+09 92.63 11-AUG-18:00 24.40 18.55 0.00 0.00 01-AUG-00:10 17.07 15.36
September 90487737.68 90.63 01-SEP-17:00 24.40 17.92 0.00 0.00 01-SEP-00:10 19.75 18.15
October 47761285.56 80.80 21-OCT-14:01 20.00 11.40 0.00 0.00 01-OCT-00:10 7.52 6.57
November 18634417.99 70.78 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 5396973.46 73.11 09-DEC-15:03 -17.4 -18.3 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.800422E+09         0.00        
Minimum of Months 4071811.60 54.78   -17.4 -18.3 0.00 0.00   -23.1 -23.4
Maximum of Months 0.165202E+09 104.95   31.10 21.38 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 LOCKER

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.291342E+09 453.39 19-JAN-07:01 -3.3 -3.6 74121635.17 72.67 19-JAN-07:10 -3.3 -3.6
February 0.296416E+09 466.63 08-FEB-07:02 -5.1 -6.0 68392031.43 73.79 08-FEB-07:10 -5.1 -6.0
March 0.404021E+09 540.14 23-MAR-06:01 -18.8 -19.1 83086151.77 76.52 30-MAR-06:10 -2.8 -3.0
April 0.437543E+09 536.47 18-APR-06:02 12.38 7.00 74913736.36 76.52 12-APR-06:10 -0.8 -2.8
May 0.557594E+09 621.12 26-MAY-06:03 19.50 15.69 81599990.01 76.52 26-MAY-06:10 19.50 15.69
June 0.594856E+09 680.09 30-JUN-06:03 26.60 21.93 81708474.85 76.52 29-JUN-06:10 23.17 19.91
July 0.589726E+09 621.43 21-JUL-06:03 19.27 18.71 75959002.65 76.52 11-JUL-06:10 14.45 13.81
August 0.605959E+09 613.55 09-AUG-06:03 18.98 17.80 85066385.71 76.52 09-AUG-06:10 18.98 17.80
September 0.501662E+09 590.18 01-SEP-06:02 16.10 15.79 75545692.95 76.52 13-SEP-06:10 4.78 4.42
October 0.447124E+09 500.70 20-OCT-06:02 5.92 5.92 77495159.04 76.52 24-OCT-06:10 5.60 4.39
November 0.375202E+09 511.45 21-NOV-07:01 10.68 10.33 75481060.52 76.52 02-NOV-06:10 4.82 3.20
December 0.301237E+09 468.99 06-DEC-07:02 -2.1 -2.1 72408844.30 74.08 06-DEC-07:10 -2.1 -2.1
                     
Annual Sum or Average 0.540268E+10         0.925778E+09        
Minimum of Months 0.291342E+09 453.39   -18.8 -19.1 68392031.43 72.67   -5.1 -6.0
Maximum of Months 0.605959E+09 680.09   26.60 21.93 85066385.71 76.52   23.17 19.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.194122E+10 2864.58 20-JAN-07:02 -7.3 -7.9 0.471563E+09 483.99 19-JAN-07:10 -3.3 -3.6
February 0.201004E+10 2882.72 23-FEB-07:02 -7.9 -8.8 0.435434E+09 483.99 09-FEB-07:10 -2.7 -3.1
March 0.267419E+10 3251.97 23-MAR-06:01 -18.8 -19.1 0.528783E+09 483.99 01-MAR-07:10 -3.9 -4.1
April 0.290079E+10 3163.41 18-APR-06:02 12.38 7.00 0.477444E+09 483.99 11-APR-06:10 -2.8 -4.6
May 0.365228E+10 3656.02 26-MAY-06:03 19.50 15.69 0.519621E+09 484.00 26-MAY-06:10 19.50 15.69
June 0.389295E+10 4035.60 30-JUN-06:03 26.60 21.93 0.520291E+09 484.01 29-JUN-06:10 23.17 19.91
July 0.388148E+10 3794.55 05-JUL-06:03 20.60 19.78 0.484068E+09 484.01 05-JUL-06:10 20.60 19.78
August 0.397285E+10 3615.44 09-AUG-06:03 18.98 17.80 0.541600E+09 484.01 09-AUG-06:10 18.98 17.80
September 0.329636E+10 3500.63 01-SEP-06:02 16.10 15.79 0.481177E+09 483.98 18-SEP-06:10 12.98 12.98
October 0.294969E+10 2953.40 03-OCT-06:02 5.00 3.77 0.493561E+09 483.99 02-OCT-06:10 7.88 7.53
November 0.251728E+10 2994.42 21-NOV-07:01 10.68 10.33 0.481087E+09 483.99 30-NOV-07:10 -1.6 -3.1
December 0.201686E+10 3404.02 01-DEC-07:01 -20.3 -20.5 0.461093E+09 483.99 05-DEC-07:10 -1.1 -1.1
                     
Annual Sum or Average 0.357060E+11         0.589572E+10        
Minimum of Months 0.194122E+10 2864.58   -20.3 -20.5 0.435434E+09 483.98   -3.9 -4.6
Maximum of Months 0.397285E+10 4035.60   26.60 21.93 0.541600E+09 484.01   23.17 19.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 66198850.25 467.11 07-JAN-15:02 -16.8 -17.4 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.113402E+09 329.90 07-FEB-18:01 2.62 0.30 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.247184E+09 333.20 28-MAR-17:01 7.20 3.38 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.435751E+09 471.89 13-APR-17:01 19.03 7.22 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.731069E+09 523.68 26-MAY-06:05 19.50 15.69 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.845441E+09 554.96 29-JUN-06:05 23.17 19.91 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.905777E+09 521.93 21-JUL-06:05 19.27 18.71 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.831674E+09 513.68 09-AUG-06:05 18.98 17.80 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.616802E+09 510.16 01-SEP-17:01 24.32 17.90 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.421196E+09 485.11 21-OCT-14:01 20.00 11.40 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.231914E+09 425.27 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 94144389.11 443.37 09-DEC-15:03 -17.4 -18.3 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.554055E+10         0.00        
Minimum of Months 66198850.25 329.90   -17.4 -18.3 0.00 0.00   -23.1 -23.4
Maximum of Months 0.905777E+09 554.96   24.32 19.91 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.663175E+10 7966.58 06-JAN-06:01 -34.5 -34.6 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.630022E+10 7485.93 14-FEB-06:01 -32.0 -32.1 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.703146E+10 5837.14 16-MAR-05:01 -24.2 -24.4 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.783770E+10 5338.68 23-APR-15:25 26.15 16.70 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.872113E+10 5568.69 26-MAY-06:00 19.40 15.58 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.877827E+10 5862.18 28-JUN-06:00 18.90 17.78 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.976749E+10 5769.01 21-JUL-06:00 18.90 18.46 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.899361E+10 5763.29 20-AUG-08:32 19.83 15.27 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.853852E+10 5492.72 10-SEP-09:50 15.22 10.48 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.811397E+10 5312.31 22-OCT-13:52 19.40 12.75 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.717391E+10 5117.67 29-NOV-06:01 -20.3 -20.5 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.690702E+10 6832.33 20-DEC-06:01 -28.9 -29.1 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.947951E+11         0.00        
Minimum of Months 0.630022E+10 5117.67   -34.5 -34.6 0.00 0.00   -23.1 -23.4
Maximum of Months 0.976749E+10 7966.58   26.15 18.46 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.127411E+09 186.53 06-JAN-06:03 -34.5 -34.6 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.154018E+09 178.00 08-FEB-14:00 5.00 -0.2 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.244071E+09 291.17 31-MAR-15:00 8.30 2.61 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.358861E+09 701.91 14-APR-06:01 2.07 1.49 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.550992E+09 956.97 26-MAY-06:03 19.50 15.69 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.641759E+09 1091.32 30-JUN-06:03 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.667832E+09 996.20 21-JUL-06:03 19.27 18.71 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.626815E+09 949.28 09-AUG-06:03 18.98 17.80 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.461961E+09 896.71 01-SEP-06:01 16.10 15.79 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.320139E+09 710.02 20-OCT-06:01 5.92 5.92 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.217003E+09 272.13 01-NOV-16:10 17.62 13.18 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.141095E+09 146.65 20-DEC-07:04 -29.1 -29.3 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.451196E+10         0.00        
Minimum of Months 0.127411E+09 146.65   -34.5 -34.6 0.00 0.00   -23.1 -23.4
Maximum of Months 0.667832E+09 1091.32   26.60 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.177840E+10 2560.68 19-JAN-18:00 -3.3 -3.9 0.490212E+09 578.77 20-JAN-15:20 -5.2 -6.8
February 0.223202E+10 3202.17 08-FEB-15:50 4.50 -0.6 0.461046E+09 578.78 09-FEB-08:30 -2.5 -2.9
March 0.346046E+10 4064.91 31-MAR-15:20 8.50 2.99 0.572128E+09 578.78 24-MAR-14:09 2.62 -0.0
April 0.454565E+10 6030.03 18-APR-06:01 12.38 7.00 0.526542E+09 603.43 14-APR-06:10 2.07 1.49
May 0.662201E+10 8163.43 26-MAY-06:05 19.50 15.69 0.581617E+09 645.17 26-MAY-06:10 19.50 15.69
June 0.744564E+10 8986.34 30-JUN-06:03 26.60 21.93 0.585342E+09 645.37 30-JUN-06:10 26.60 21.93
July 0.764861E+10 8242.59 21-JUL-06:05 19.27 18.71 0.544942E+09 645.30 14-JUL-06:10 17.57 17.07
August 0.754528E+10 7951.49 09-AUG-06:03 18.98 17.80 0.609413E+09 645.30 10-AUG-06:10 15.10 14.70
September 0.583004E+10 7748.56 01-SEP-06:02 16.10 15.79 0.537881E+09 644.40 01-SEP-06:10 16.10 15.79
October 0.460394E+10 6090.22 20-OCT-06:02 5.92 5.92 0.546036E+09 612.43 20-OCT-06:10 5.92 5.92
November 0.339781E+10 5890.71 02-NOV-06:02 4.82 3.20 0.523282E+09 601.32 02-NOV-06:10 4.82 3.20
December 0.205737E+10 2502.35 05-DEC-18:00 0.00 -0.0 0.483732E+09 578.77 29-DEC-15:39 -11.1 -12.0
                     
Annual Sum or Average 0.571672E+11         0.646217E+10        
Minimum of Months 0.177840E+10 2502.35   -3.3 -3.9 0.461046E+09 578.77   -11.1 -12.0
Maximum of Months 0.764861E+10 8986.34   26.60 21.93 0.609413E+09 645.37   26.60 21.93



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.315830E+09 367.89 28-JAN-06:04 -26.4 -26.6 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.402637E+09 599.14 08-FEB-16:20 4.03 -0.8 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.594630E+09 824.18 31-MAR-15:50 8.80 3.56 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.801219E+09 1088.47 13-APR-15:20 20.00 8.07 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.119664E+10 1837.82 19-MAY-06:01 14.47 10.08 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.135329E+10 2250.75 30-JUN-06:01 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.141198E+10 1968.91 14-JUL-06:02 17.57 17.07 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.137135E+10 1901.56 10-AUG-06:01 15.10 14.70 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.102681E+10 1329.14 01-SEP-15:50 26.10 17.65 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.771210E+09 1058.21 19-OCT-15:50 21.78 13.55 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.546852E+09 629.70 17-NOV-16:00 10.00 3.18 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.356990E+09 393.45 02-DEC-06:04 -27.7 -27.9 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.101494E+11         0.00        
Minimum of Months 0.315830E+09 367.89   -27.7 -27.9 0.00 0.00   -23.1 -23.4
Maximum of Months 0.141198E+10 2250.75   26.60 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 13224831.89 131.86 07-JAN-15:02 -16.8 -17.4 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 20204627.31 93.74 08-FEB-18:01 0.82 -2.4 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 41005960.15 94.18 31-MAR-17:01 8.80 3.19 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 78703849.44 134.10 13-APR-17:01 19.03 7.22 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.161982E+09 146.26 25-MAY-17:01 29.23 19.28 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.195570E+09 156.10 30-JUN-06:03 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.231982E+09 147.39 21-JUL-06:05 19.27 18.71 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.211586E+09 146.28 11-AUG-17:01 25.82 19.22 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.146991E+09 145.98 01-SEP-17:01 24.32 17.90 0.00 0.00 01-SEP-00:10 19.75 18.15
October 88265260.25 137.27 21-OCT-14:01 20.00 11.40 0.00 0.00 01-OCT-00:10 7.52 6.57
November 41059507.08 120.29 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 17054348.57 126.01 09-DEC-15:03 -17.4 -18.3 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.124763E+10         0.00        
Minimum of Months 13224831.89 93.74   -17.4 -18.3 0.00 0.00   -23.1 -23.4
Maximum of Months 0.231982E+09 156.10   29.23 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.308093E+10 5716.17 27-JAN-13:40 -14.8 -15.8 0.958002E+09 1013.68 27-JAN-13:50 -14.6 -15.7
February 0.383890E+10 6344.74 28-FEB-14:10 4.27 0.37 0.895341E+09 1088.50 28-FEB-13:00 3.90 0.13
March 0.520245E+10 6249.44 23-MAR-14:02 0.10 -4.0 0.107962E+10 1076.72 23-MAR-13:00 0.00 -4.0
April 0.617660E+10 6891.70 13-APR-13:20 18.17 6.95 0.978749E+09 1044.94 21-APR-13:20 10.77 2.57
May 0.799887E+10 6514.18 18-MAY-13:10 28.25 16.73 0.105083E+10 991.27 01-MAY-12:20 8.03 1.26
June 0.863690E+10 6408.45 30-JUN-13:20 31.50 24.22 0.104079E+10 991.23 02-JUN-11:20 12.20 7.04
July 0.897540E+10 6147.89 21-JUL-13:50 28.80 22.58 0.969229E+09 991.24 21-JUL-16:00 25.00 20.76
August 0.909351E+10 6938.68 25-AUG-13:10 27.38 18.57 0.107902E+10 991.22 01-AUG-12:20 19.07 14.20
September 0.743841E+10 7847.76 01-SEP-13:20 24.80 17.99 0.970478E+09 991.25 08-SEP-13:20 18.50 10.24
October 0.600638E+10 7716.24 19-OCT-12:45 20.22 13.38 0.989656E+09 1045.33 25-OCT-13:39 10.93 6.92
November 0.440724E+10 6082.52 17-NOV-13:30 10.30 3.30 0.963671E+09 1051.01 17-NOV-13:09 10.10 3.23
December 0.288592E+10 4824.77 20-DEC-13:30 -20.9 -21.4 0.921095E+09 991.29 20-DEC-15:20 -19.3 -20.0
                     
Annual Sum or Average 0.737415E+11         0.118965E+11        
Minimum of Months 0.288592E+10 4824.77   -20.9 -21.4 0.895341E+09 991.22   -19.3 -20.0
Maximum of Months 0.909351E+10 7847.76   31.50 24.22 0.107962E+10 1088.50   25.00 20.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.191300E+10 2470.77 13-JAN-06:02 -31.3 -31.4 0.433698E+09 432.09 27-JAN-15:00 -14.4 -15.5
February 0.199113E+10 2516.67 17-FEB-06:02 -31.6 -31.7 0.397420E+09 435.37 08-FEB-15:50 4.50 -0.6
March 0.267576E+10 1922.10 16-MAR-05:03 -24.2 -24.4 0.482496E+09 448.56 23-MAR-14:00 0.60 -4.0
April 0.286380E+10 2245.62 13-APR-15:00 20.00 8.07 0.433733E+09 451.36 21-APR-14:09 11.28 2.90
May 0.356563E+10 2337.75 18-MAY-15:10 28.83 16.53 0.460778E+09 442.36 01-MAY-15:50 10.17 2.39
June 0.377471E+10 2469.44 30-JUN-06:03 26.60 21.93 0.454721E+09 432.02 02-JUN-14:20 13.50 7.41
July 0.383178E+10 2335.70 19-JUL-16:00 25.60 18.62 0.420362E+09 412.89 19-JUL-15:20 26.33 18.30
August 0.390967E+10 2340.02 25-AUG-15:10 28.30 19.22 0.472508E+09 421.73 17-AUG-15:09 11.28 10.15
September 0.325488E+10 2313.14 01-SEP-15:40 26.10 17.68 0.428450E+09 437.87 21-SEP-15:20 9.40 8.16
October 0.290004E+10 2281.67 19-OCT-14:05 21.78 13.68 0.445599E+09 442.28 25-OCT-16:40 9.63 6.12
November 0.241122E+10 1954.61 01-NOV-16:10 17.62 13.18 0.435112E+09 437.52 17-NOV-16:19 8.90 2.57
December 0.196445E+10 2122.28 20-DEC-06:02 -28.9 -29.1 0.419501E+09 422.62 28-DEC-15:20 -1.8 -3.7
                     
Annual Sum or Average 0.350561E+11         0.528438E+10        
Minimum of Months 0.191300E+10 1922.10   -31.6 -31.7 0.397420E+09 412.89   -14.4 -15.5
Maximum of Months 0.390967E+10 2516.67   28.83 21.93 0.482496E+09 451.36   26.33 18.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.162727E+09 224.09 11-JAN-07:03 -27.1 -27.3 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.182315E+09 266.94 17-FEB-07:03 -30.7 -30.9 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.255791E+09 174.86 16-MAR-06:03 -22.9 -23.2 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.297609E+09 219.88 13-APR-17:01 19.03 7.22 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.381036E+09 243.20 26-MAY-06:05 19.50 15.69 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.405543E+09 256.74 30-JUN-06:03 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.428711E+09 241.56 21-JUL-06:05 19.27 18.71 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.416965E+09 238.93 09-AUG-06:05 18.98 17.80 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.349734E+09 237.07 01-SEP-17:01 24.32 17.90 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.302760E+09 226.23 21-OCT-14:01 20.00 11.40 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.239937E+09 198.96 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.178072E+09 253.67 21-DEC-07:03 -27.9 -28.1 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.360120E+10         0.00        
Minimum of Months 0.162727E+09 174.86   -30.7 -30.9 0.00 0.00   -23.1 -23.4
Maximum of Months 0.428711E+09 266.94   26.60 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.104006E+09 224.11 07-JAN-15:02 -16.8 -17.4 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.120573E+09 164.77 03-FEB-07:03 -13.5 -13.8 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.183525E+09 166.34 04-MAR-07:05 -5.6 -5.8 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.233688E+09 220.20 13-APR-17:01 19.03 7.22 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.319773E+09 243.32 26-MAY-06:05 19.50 15.69 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.348220E+09 256.87 29-JUN-06:05 23.17 19.91 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.375022E+09 241.86 21-JUL-06:05 19.27 18.71 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.355092E+09 239.22 09-AUG-06:05 18.98 17.80 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.287822E+09 237.60 01-SEP-17:01 24.32 17.90 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.233614E+09 226.92 21-OCT-14:01 20.00 11.40 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.168472E+09 198.81 01-NOV-17:01 15.95 12.47 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.113529E+09 214.34 02-DEC-15:03 -17.4 -18.2 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.284334E+10         0.00        
Minimum of Months 0.104006E+09 164.77   -17.4 -18.2 0.00 0.00   -23.1 -23.4
Maximum of Months 0.375022E+09 256.87   24.32 19.91 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 41252272.61 91.80 26-JAN-06:03 -32.9 -33.0 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 52169861.16 89.40 17-FEB-06:03 -31.6 -31.7 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 84764930.76 62.01 16-MAR-05:03 -24.2 -24.4 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.111095E+09 78.66 13-APR-15:30 20.00 8.07 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.156231E+09 114.52 18-MAY-15:20 28.77 16.48 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.175154E+09 128.12 30-JUN-15:00 32.20 24.50 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.186232E+09 118.28 21-JUL-15:00 29.40 22.32 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.179060E+09 112.26 11-AUG-15:50 26.60 19.32 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.140783E+09 101.55 01-SEP-15:50 26.10 17.65 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.113840E+09 77.88 19-OCT-16:00 21.70 13.54 0.00 0.00 01-OCT-00:10 7.52 6.57
November 81905232.97 69.25 01-NOV-15:00 18.30 13.43 0.00 0.00 01-NOV-00:10 3.60 0.50
December 48507571.57 72.27 02-DEC-17:10 -20.0 -20.4 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.137099E+10         0.00        
Minimum of Months 41252272.61 62.01   -32.9 -33.0 0.00 0.00   -23.1 -23.4
Maximum of Months 0.186232E+09 128.12   32.20 24.50 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.175365E+10 1942.68 13-JAN-06:02 -31.3 -31.4 0.352855E+09 356.23 27-JAN-16:10 -14.8 -15.8
February 0.180938E+10 1979.61 17-FEB-06:02 -31.6 -31.7 0.325616E+09 362.95 08-FEB-17:19 2.57 -1.4
March 0.236268E+10 1589.96 16-MAR-05:03 -24.2 -24.4 0.397006E+09 362.96 23-MAR-14:20 0.20 -4.0
April 0.249933E+10 1838.56 13-APR-15:00 20.00 8.07 0.357552E+09 362.96 19-APR-14:20 6.70 0.85
May 0.307946E+10 1912.03 18-MAY-16:20 28.40 16.22 0.380392E+09 362.95 01-MAY-16:10 10.23 2.38
June 0.325186E+10 1948.80 30-JUN-06:03 26.60 21.93 0.373897E+09 359.41 02-JUN-14:20 13.50 7.41
July 0.333052E+10 1909.97 28-JUL-17:00 28.90 20.78 0.344818E+09 344.62 28-JUL-16:00 28.90 20.78
August 0.338682E+10 1913.34 25-AUG-16:20 28.13 19.38 0.388104E+09 353.10 18-AUG-16:00 13.90 11.29
September 0.282630E+10 1893.07 01-SEP-16:10 25.82 17.69 0.354663E+09 362.96 21-SEP-14:20 9.80 7.98
October 0.253555E+10 1869.26 19-OCT-15:40 21.87 13.56 0.368615E+09 362.95 25-OCT-14:20 11.30 7.17
November 0.215250E+10 1667.24 01-NOV-15:00 18.30 13.43 0.357703E+09 362.95 17-NOV-16:30 8.35 2.26
December 0.179326E+10 1668.70 20-DEC-06:02 -28.9 -29.1 0.342096E+09 349.72 28-DEC-15:00 -2.1 -3.8
                     
Annual Sum or Average 0.307813E+11         0.434332E+10        
Minimum of Months 0.175365E+10 1589.96   -31.6 -31.7 0.325616E+09 344.62   -14.8 -15.8
Maximum of Months 0.338682E+10 1979.61   28.90 21.93 0.397006E+09 362.96   28.90 20.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.154099E+10 3108.83 27-JAN-15:02 -14.4 -15.5 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.218053E+10 4672.39 28-FEB-15:30 6.10 1.53 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.312654E+10 5029.32 31-MAR-15:00 8.30 2.61 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.409677E+10 5343.57 13-APR-15:00 20.00 8.07 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.550913E+10 6167.66 25-MAY-16:40 29.17 19.39 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.595141E+10 6942.68 30-JUN-06:01 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.634017E+10 5986.95 21-JUL-16:00 30.00 21.90 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.619686E+10 6072.90 11-AUG-16:20 26.50 19.46 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.493458E+10 6427.09 01-SEP-15:30 26.10 17.71 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.385122E+10 5876.30 19-OCT-14:40 22.03 13.63 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.265900E+10 4087.97 17-NOV-13:30 10.30 3.30 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.153732E+10 2055.71 02-DEC-15:04 -17.4 -18.2 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.479245E+11         0.00        
Minimum of Months 0.153732E+10 2055.71   -17.4 -18.2 0.00 0.00   -23.1 -23.4
Maximum of Months 0.634017E+10 6942.68   30.00 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.535029E+09 1379.54 27-JAN-15:20 -14.4 -15.5 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.904793E+09 2218.61 28-FEB-15:30 6.10 1.53 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.139148E+10 2510.24 31-MAR-14:50 8.30 2.69 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.197564E+10 2789.08 13-APR-14:40 19.63 7.85 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.283636E+10 3251.87 25-MAY-16:40 29.17 19.39 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.313206E+10 3656.29 30-JUN-06:01 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.341373E+10 3205.10 21-JUL-16:00 30.00 21.90 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.332583E+10 3242.38 11-AUG-16:30 26.40 19.43 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.257315E+10 3512.09 01-SEP-15:00 26.10 17.80 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.189701E+10 3126.66 19-OCT-14:30 21.95 13.65 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.117796E+10 2055.09 17-NOV-13:30 10.30 3.30 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.555018E+09 1018.52 02-DEC-15:04 -17.4 -18.2 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.237181E+11         0.00        
Minimum of Months 0.535029E+09 1018.52   -17.4 -18.2 0.00 0.00   -23.1 -23.4
Maximum of Months 0.341373E+10 3656.29   30.00 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 94062563.59 172.87 07-JAN-15:02 -16.8 -17.4 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.110510E+09 178.55 25-FEB-06:04 -29.4 -29.5 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 0.173818E+09 123.26 23-MAR-14:02 0.10 -4.0 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 0.235042E+09 179.52 13-APR-15:00 20.00 8.07 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.341384E+09 194.51 18-MAY-15:20 28.77 16.48 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.380042E+09 197.79 30-JUN-15:10 32.12 24.52 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.405903E+09 194.81 21-JUL-15:50 29.90 21.97 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.392113E+09 193.94 25-AUG-15:40 28.30 19.32 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.307806E+09 190.52 01-SEP-15:50 26.10 17.65 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.237935E+09 183.17 19-OCT-15:10 22.12 13.59 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.165863E+09 153.94 01-NOV-16:20 17.43 13.10 0.00 0.00 01-NOV-00:10 3.60 0.50
December 0.102269E+09 179.52 02-DEC-17:10 -20.0 -20.4 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.294675E+10         0.00        
Minimum of Months 94062563.59 123.26   -29.4 -29.5 0.00 0.00   -23.1 -23.4
Maximum of Months 0.405903E+09 197.79   32.12 24.52 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FLOOR 3 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.194560E+09 354.78 19-JAN-13:30 -2.8 -3.4 90134949.24 109.42 19-JAN-15:50 -2.8 -3.5
February 0.348439E+09 705.80 28-FEB-09:53 -6.1 -7.6 85577687.89 109.43 28-FEB-13:09 2.48 -0.8
March 0.709194E+09 1431.96 31-MAR-09:40 1.13 -1.1 0.107216E+09 109.43 20-MAR-14:09 0.50 -0.5
April 0.122740E+10 2417.21 18-APR-06:01 12.38 7.00 99619298.50 116.80 18-APR-06:10 12.38 7.00
May 0.181303E+10 3010.41 26-MAY-06:03 19.50 15.69 0.111007E+09 122.01 18-MAY-06:10 15.50 11.62
June 0.212934E+10 3209.49 29-JUN-06:03 23.17 19.91 0.111991E+09 122.02 29-JUN-06:10 23.17 19.91
July 0.220510E+10 3083.69 21-JUL-06:03 19.27 18.71 0.104423E+09 122.01 11-JUL-06:10 14.45 13.81
August 0.196943E+10 2955.26 09-AUG-06:03 18.98 17.80 0.116184E+09 122.00 02-AUG-06:10 10.97 9.90
September 0.142331E+10 2842.60 01-SEP-06:01 16.10 15.79 0.101843E+09 119.88 01-SEP-06:10 16.10 15.79
October 0.914938E+09 1792.58 19-OCT-09:10 11.57 8.31 0.102340E+09 111.71 20-OCT-06:10 5.92 5.92
November 0.547673E+09 846.95 01-NOV-15:30 18.05 13.34 96519683.53 109.48 30-NOV-15:09 4.22 1.08
December 0.221490E+09 443.89 28-DEC-15:07 -1.8 -3.6 87864369.31 109.43 28-DEC-15:20 -1.8 -3.7
                     
Annual Sum or Average 0.137039E+11         0.121472E+10        
Minimum of Months 0.194560E+09 354.78   -6.1 -7.6 85577687.89 109.42   -2.8 -3.7
Maximum of Months 0.220510E+10 3209.49   23.17 19.91 0.116184E+09 122.02   23.17 19.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: NE STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 1945257.84 110.40 07-JAN-15:02 -16.8 -17.4 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 3480916.97 77.96 21-FEB-18:01 2.43 0.62 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 8032357.04 78.71 28-MAR-17:01 7.20 3.38 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 48214188.89 123.60 13-APR-15:20 20.00 8.07 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.244689E+09 615.04 18-MAY-14:30 28.70 16.65 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.440141E+09 910.60 29-JUN-15:00 34.40 24.00 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.591439E+09 912.03 21-JUL-13:30 28.60 22.52 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.499083E+09 817.21 08-AUG-14:40 30.40 23.18 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.243619E+09 630.53 01-SEP-14:20 25.77 18.00 0.00 0.00 01-SEP-00:10 19.75 18.15
October 81551084.20 160.82 20-OCT-14:10 18.90 10.05 0.00 0.00 01-OCT-00:10 7.52 6.57
November 16972328.52 116.23 01-NOV-15:00 18.30 13.43 0.00 0.00 01-NOV-00:10 3.60 0.50
December 2716280.51 104.92 02-DEC-15:03 -17.4 -18.2 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.218188E+10         0.00        
Minimum of Months 1945257.84 77.96   -17.4 -18.2 0.00 0.00   -23.1 -23.4
Maximum of Months 0.591439E+09 912.03   34.40 24.00 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: NW ELEVATOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 4982153.74 74.07 07-JAN-15:02 -16.8 -17.4 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 10426773.82 53.41 08-FEB-17:00 3.30 -1.0 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 20604325.69 57.29 31-MAR-17:12 8.70 3.11 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 50126383.72 175.66 13-APR-17:00 19.40 7.36 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.156606E+09 585.15 25-MAY-17:00 29.20 19.29 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.225884E+09 683.62 30-JUN-17:00 31.10 21.38 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.308892E+09 665.07 24-JUL-17:00 28.90 19.07 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.299440E+09 721.02 11-AUG-17:00 26.10 19.35 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.172453E+09 694.73 01-SEP-16:50 24.68 17.89 0.00 0.00 01-SEP-00:10 19.75 18.15
October 89672688.62 391.65 19-OCT-16:30 20.55 13.18 0.00 0.00 01-OCT-00:10 7.52 6.57
November 31828146.47 76.16 01-NOV-15:00 18.30 13.43 0.00 0.00 01-NOV-00:10 3.60 0.50
December 8160835.53 73.60 02-DEC-17:10 -20.0 -20.4 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.137908E+10         0.00        
Minimum of Months 4982153.74 53.41   -20.0 -20.4 0.00 0.00   -23.1 -23.4
Maximum of Months 0.308892E+09 721.02   31.10 21.38 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: NW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 2639168.19 127.14 07-JAN-15:02 -16.8 -17.4 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 4831843.37 89.47 07-FEB-18:01 2.62 0.30 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 9903350.04 90.35 28-MAR-17:01 7.20 3.38 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 53187136.16 139.34 23-APR-18:00 25.60 16.46 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.282716E+09 690.08 18-MAY-16:30 28.35 16.19 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.488822E+09 1722.70 30-JUN-06:01 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.650882E+09 975.05 21-JUL-16:07 29.17 21.79 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.566064E+09 907.88 08-AUG-16:40 29.80 23.03 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.275644E+09 700.64 01-SEP-16:30 25.25 17.80 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.102684E+09 156.75 19-OCT-16:00 21.70 13.54 0.00 0.00 01-OCT-00:10 7.52 6.57
November 25545102.93 136.48 01-NOV-15:00 18.30 13.43 0.00 0.00 01-NOV-00:10 3.60 0.50
December 3970247.63 121.01 09-DEC-15:03 -17.4 -18.3 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.246689E+10         0.00        
Minimum of Months 2639168.19 89.47   -17.4 -18.3 0.00 0.00   -23.1 -23.4
Maximum of Months 0.650882E+09 1722.70   29.80 23.03 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: SW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 6113401.34 60.09 27-JAN-15:37 -14.4 -15.5 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 17256083.27 217.00 28-FEB-15:40 6.10 1.53 0.00 0.00 01-FEB-00:10 -23.1 -23.4
March 26481772.23 218.37 31-MAR-15:50 8.80 3.56 0.00 0.00 01-MAR-00:10 -1.3 -3.2
April 64275414.38 359.24 13-APR-15:50 20.00 8.07 0.00 0.00 01-APR-00:10 3.52 0.37
May 0.162040E+09 568.20 18-MAY-16:10 28.45 16.26 0.00 0.00 01-MAY-00:10 -0.0 -1.3
June 0.221360E+09 856.90 30-JUN-06:01 26.60 21.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.300869E+09 626.98 24-JUL-16:40 28.90 18.93 0.00 0.00 01-JUL-00:10 15.83 13.56
August 0.303974E+09 684.83 25-AUG-16:30 28.05 19.37 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.192977E+09 745.94 01-SEP-15:50 26.10 17.65 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.107367E+09 586.45 19-OCT-15:10 22.12 13.59 0.00 0.00 01-OCT-00:10 7.52 6.57
November 36377205.57 246.00 17-NOV-14:20 10.60 3.41 0.00 0.00 01-NOV-00:10 3.60 0.50
December 6663586.13 53.39 02-DEC-17:10 -20.0 -20.4 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.144576E+10         0.00        
Minimum of Months 6113401.34 53.39   -20.0 -20.4 0.00 0.00   -23.1 -23.4
Maximum of Months 0.303974E+09 856.90   28.90 21.93 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6386540.41 547.68 17-JAN-05:01 -5.6
February 2443732.93 462.03 13-FEB-05:03 -23.4
March 2604545.80 548.04 25-MAR-04:02 -4.3
April 2040175.85 553.56 29-APR-04:01 0.00
May 1724135.16 543.52 01-MAY-04:02 -2.9
June 1510654.00 281.29 03-JUN-05:01 7.30
July 1336141.03 261.91 10-JUL-05:01 9.68
August 1344204.59 261.95 19-AUG-05:01 4.60
September 1266434.81 279.71 23-SEP-05:01 4.90
October 1326130.53 548.01 14-OCT-04:01 0.00
November 1607095.78 554.77 04-NOV-04:01 -3.0
December 3951716.18 547.34 30-DEC-05:02 -5.3
         
Annual Sum or Average 27541507.07      
Minimum of Months 1266434.81 261.91   -23.4
Maximum of Months 6386540.41 554.77   9.68



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 57221314.65 99.72 17-JAN-05:01 -5.6
February 38860467.51 100.10 21-FEB-06:01 2.80
March 40826715.20 99.69 27-MAR-04:01 -3.4
April 33980906.58 99.56 03-APR-04:01 -5.4
May 24397788.03 100.12 30-MAY-05:01 10.60
June 13321170.69 98.42 12-JUN-05:01 11.78
July 7450270.56 97.74 10-JUL-05:01 9.68
August 6714635.60 95.99 21-AUG-05:01 12.70
September 15188586.04 98.83 05-SEP-05:01 5.60
October 26148676.37 100.09 10-OCT-05:01 3.40
November 29818304.52 98.92 20-NOV-06:01 4.90
December 39937894.13 97.14 04-DEC-05:03 -9.2
         
Annual Sum or Average 0.333867E+09      
Minimum of Months 6714635.60 95.99   -9.2
Maximum of Months 57221314.65 100.12   12.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 CAFE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1790335.86 610.61 17-JAN-05:01 -5.6
February 53964.41 359.76 25-FEB-07:03 -29.3
March 43442.62 289.62 04-MAR-07:03 -5.6
April 44793.35 298.62 08-APR-06:03 3.48
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 73091.06 487.27 25-NOV-07:03 -19.2
December 85004.20 569.18 26-DEC-06:01 -26.7
         
Annual Sum or Average 2090631.50      
Minimum of Months 0.00 0.00   -29.3
Maximum of Months 1790335.86 610.61   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 CLEAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 33346.66 205.43 17-JAN-05:01 -5.6
February 0.00 0.00 01-FEB-00:10 -23.1
March 16758.94 195.52 27-MAR-04:01 -3.4
April 52624.89 200.07 10-APR-04:01 -2.8
May 20236.19 202.36 01-MAY-04:02 -2.9
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 11729.37 117.29 11-OCT-04:02 0.60
November 16099.41 187.83 06-NOV-05:01 -3.9
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 150795.46      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 52624.89 205.43   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 54417.86 262.19 17-JAN-05:01 -5.6
February 0.00 0.00 01-FEB-00:10 -23.1
March 34023.14 256.16 27-MAR-04:01 -3.4
April 130528.27 260.89 03-APR-04:01 -5.4
May 26115.93 261.16 01-MAY-04:02 -2.9
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 49498.43 242.00 11-OCT-04:02 0.60
November 76975.34 247.85 06-NOV-05:01 -3.9
December 11335.39 46.04 26-DEC-05:03 -25.9
         
Annual Sum or Average 382894.35      
Minimum of Months 0.00 0.00   -25.9
Maximum of Months 130528.27 262.19   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.193233E+09 203.87 01-JAN-04:11 -26.7
February 0.135756E+09 200.38 21-FEB-06:01 2.80
March 0.134349E+09 199.92 06-MAR-05:03 -18.4
April 67111944.96 200.27 10-APR-04:01 -2.8
May 14461100.15 199.82 15-MAY-05:01 6.87
June 1888112.86 195.75 12-JUN-05:01 11.78
July 355608.32 191.11 10-JUL-05:01 9.68
August 252255.34 181.46 21-AUG-06:01 12.77
September 942341.34 191.61 05-SEP-05:01 5.60
October 6602782.35 199.59 10-OCT-05:01 3.40
November 32382259.70 199.37 20-NOV-06:01 4.90
December 0.138243E+09 198.00 30-DEC-05:02 -5.3
         
Annual Sum or Average 0.725578E+09      
Minimum of Months 252255.34 181.46   -26.7
Maximum of Months 0.193233E+09 203.87   12.77



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 37100.88 53.84 09-JAN-05:03 -33.0
February 4378.26 29.19 25-FEB-07:03 -29.3
March 5920.18 39.47 04-MAR-07:03 -5.6
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 47399.32      
Minimum of Months 0.00 0.00   -33.0
Maximum of Months 37100.88 53.84   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3208184.12 626.21 17-JAN-05:01 -5.6
February 1091209.98 482.24 13-FEB-06:01 -24.0
March 1310105.08 602.29 27-MAR-04:01 -3.4
April 935038.61 650.29 10-APR-04:01 -2.8
May 599916.64 529.92 01-MAY-04:02 -2.9
June 339264.32 298.29 14-JUN-06:01 11.15
July 191603.03 335.19 05-JUL-05:02 19.60
August 74061.69 191.12 07-AUG-05:01 13.80
September 139851.12 259.49 05-SEP-06:02 6.05
October 256996.76 399.27 23-OCT-05:02 5.60
November 289211.36 524.08 06-NOV-05:01 -3.9
December 1089937.62 470.23 11-DEC-06:01 -24.3
         
Annual Sum or Average 9525380.33      
Minimum of Months 74061.69 191.12   -24.3
Maximum of Months 3208184.12 650.29   19.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 IT HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 147418.83 27.19 02-JAN-05:08 -18.2
February 0.00 0.00 01-FEB-00:10 -23.1
March 19915.38 22.52 27-MAR-04:06 -3.4
April 42318.24 23.32 17-APR-04:07 -1.1
May 20230.46 24.44 01-MAY-04:07 -2.9
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 9267.31 22.20 06-NOV-05:06 -3.9
December 6028.50 3.87 26-DEC-05:10 -25.9
         
Annual Sum or Average 245178.72      
Minimum of Months 0.00 0.00   -25.9
Maximum of Months 147418.83 27.19   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 LOBBY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 25445505.49 2440.46 17-JAN-05:01 -5.6
February 2356342.20 1716.90 27-FEB-07:02 -19.2
March 985749.47 1729.33 06-MAR-07:02 -19.3
April 519560.66 1479.46 10-APR-06:01 -1.9
May 81666.39 1361.11 30-MAY-06:01 10.63
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 172480.54 1453.27 10-OCT-06:01 3.90
November 425731.74 1451.49 27-NOV-07:01 -6.7
December 5793757.73 1917.36 26-DEC-05:03 -25.9
         
Annual Sum or Average 35780794.22      
Minimum of Months 0.00 0.00   -25.9
Maximum of Months 25445505.49 2440.46   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 13430995.87 417.22 17-JAN-05:01 -5.6
February 7091869.90 296.31 16-FEB-07:01 -15.1
March 9009021.79 402.83 27-MAR-04:01 -3.4
April 6662941.85 425.80 03-APR-04:01 -5.4
May 4225480.30 355.93 01-MAY-04:02 -2.9
June 2084613.88 249.38 03-JUN-05:01 7.30
July 1430080.91 241.94 10-JUL-05:01 9.68
August 1248199.22 238.84 07-AUG-05:01 13.80
September 1413344.54 247.29 23-SEP-05:01 4.90
October 2400768.85 327.46 30-OCT-05:01 -9.9
November 3414520.84 394.70 06-NOV-05:01 -3.9
December 7166404.50 349.74 04-DEC-06:01 -9.4
         
Annual Sum or Average 59578242.43      
Minimum of Months 1248199.22 238.84   -15.1
Maximum of Months 13430995.87 425.80   13.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 MED GAS

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.665548E+09 372.14 07-JAN-18:01 -20.1
February 0.573925E+09 366.76 06-FEB-05:03 -20.1
March 0.634724E+09 370.02 06-MAR-07:02 -19.3
April 0.453318E+09 367.32 03-APR-04:01 -5.4
May 0.231923E+09 365.35 01-MAY-04:02 -2.9
June 0.113518E+09 364.56 10-JUN-05:01 14.60
July 39919893.35 363.50 05-JUL-05:01 19.60
August 37665895.81 363.09 30-AUG-05:01 17.88
September 70739205.99 363.05 05-SEP-05:01 5.60
October 0.167157E+09 363.28 10-OCT-05:01 3.40
November 0.309424E+09 363.03 14-NOV-06:01 2.80
December 0.573503E+09 363.73 14-DEC-05:03 -23.4
         
Annual Sum or Average 0.387136E+10      
Minimum of Months 37665895.81 363.03   -23.4
Maximum of Months 0.665548E+09 372.14   19.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 19517.63 35.17 02-JAN-05:05 -18.2
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 19517.63      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 19517.63 35.17   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 63080871.56 241.58 17-JAN-05:01 -5.6
February 40851499.93 237.13 27-FEB-05:03 -17.4
March 48745726.85 241.62 27-MAR-04:01 -3.4
April 32696119.23 241.32 10-APR-04:01 -2.8
May 13390761.01 240.10 01-MAY-04:02 -2.9
June 4177031.18 208.73 12-JUN-05:01 11.78
July 1839957.70 209.71 10-JUL-05:01 9.68
August 1350766.12 203.82 21-AUG-05:01 12.70
September 1906768.09 208.91 05-SEP-05:01 5.60
October 4366007.39 231.00 30-OCT-05:01 -9.9
November 9942028.15 240.69 06-NOV-05:01 -3.9
December 32663341.36 238.89 05-DEC-05:02 -1.3
         
Annual Sum or Average 0.255011E+09      
Minimum of Months 1350766.12 203.82   -17.4
Maximum of Months 63080871.56 241.62   12.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 44385.02 92.64 17-JAN-05:04 -5.6
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 5195.56 34.64 26-DEC-05:03 -25.9
         
Annual Sum or Average 49580.58      
Minimum of Months 0.00 0.00   -25.9
Maximum of Months 44385.02 92.64   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 146053.62 68.66 17-JAN-05:01 -5.6
February 2447.40 8.29 13-FEB-06:02 -24.0
March 79265.34 67.21 27-MAR-04:01 -3.4
April 178680.18 68.55 03-APR-04:01 -5.4
May 53440.07 68.94 01-MAY-04:02 -2.9
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 1217.69 8.12 06-SEP-04:03 1.10
October 43399.74 64.66 11-OCT-04:02 0.60
November 143484.07 67.14 06-NOV-05:06 -3.9
December 28769.52 59.49 05-DEC-05:02 -1.3
         
Annual Sum or Average 676757.64      
Minimum of Months 0.00 0.00   -24.0
Maximum of Months 178680.18 68.94   17.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 25603.73 265.59 28-JAN-15:04 -8.9
February 53420.07 642.75 18-FEB-06:04 -8.3
March 176387.87 618.21 25-MAR-05:04 -3.9
April 410885.77 1031.73 01-APR-05:07 1.20
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 144980.79 897.88 04-NOV-05:06 -3.9
December 104674.71 897.56 30-DEC-06:06 -5.0
         
Annual Sum or Average 915952.94      
Minimum of Months 0.00 0.00   -8.9
Maximum of Months 410885.77 1031.73   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 121698.21 657.80 01-APR-05:07 1.20
May 89542.79 489.32 14-MAY-06:51 4.30
June 35422.30 472.30 04-JUN-05:32 4.10
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 64228.77 366.91 10-SEP-05:10 2.88
October 61630.81 534.81 08-OCT-07:03 2.70
November 28723.46 330.38 18-NOV-18:01 2.02
December 10803.75 162.06 30-DEC-06:06 -5.0
         
Annual Sum or Average 412050.10      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 121698.21 657.80   17.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 7760720.22 2581.56 16-JAN-23:10 -5.3
February 5038104.82 2168.18 05-FEB-08:02 -2.7
March 4994802.37 2338.55 20-MAR-00:51 -5.6
April 8827951.35 2500.56 02-APR-06:19 -6.1
May 2143069.03 2010.27 21-MAY-06:17 4.30
June 148996.02 1986.61 04-JUN-05:32 4.10
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 1507573.40 1895.50 10-SEP-05:10 2.88
October 6515041.21 2507.14 09-OCT-07:02 -4.0
November 16685904.35 2223.27 12-NOV-18:31 -6.1
December 3797840.80 2218.00 31-DEC-18:51 -5.6
         
Annual Sum or Average 57420003.58      
Minimum of Months 0.00 0.00   -6.1
Maximum of Months 16685904.35 2581.56   17.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 PACU

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 35809.95 210.82 17-JAN-05:01 -5.6
February 0.00 0.00 01-FEB-00:10 -23.1
March 43403.94 205.93 27-MAR-04:01 -3.4
April 115066.79 213.15 29-APR-04:01 0.00
May 20976.49 209.76 01-MAY-04:02 -2.9
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 42944.84 212.35 14-OCT-04:01 0.00
November 75465.40 214.05 04-NOV-04:01 -3.0
December 38825.63 178.04 05-DEC-05:02 -1.3
         
Annual Sum or Average 372493.04      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 115066.79 214.05   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 89532.20 89.51 02-JAN-05:05 -18.2
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 89532.20      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 89532.20 89.51   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 712616.89 381.00 17-JAN-05:01 -5.6
February 314914.38 246.10 18-FEB-05:03 -8.8
March 582290.72 390.63 25-MAR-04:02 -4.3
April 529384.51 393.01 29-APR-04:01 0.00
May 72848.43 377.35 01-MAY-04:02 -2.9
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 124801.24 385.65 14-OCT-04:01 0.00
November 385063.46 396.59 04-NOV-04:01 -3.0
December 466659.38 390.19 30-DEC-05:02 -5.3
         
Annual Sum or Average 3188579.01      
Minimum of Months 0.00 0.00   -8.8
Maximum of Months 712616.89 396.59   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 137401.18 662.81 17-JAN-05:01 -5.6
February 1123.89 7.49 18-FEB-07:03 -8.2
March 148703.47 664.39 25-MAR-04:02 -4.3
April 370725.48 676.08 29-APR-04:01 0.00
May 69595.65 658.34 01-MAY-04:02 -2.9
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 144684.30 668.56 14-OCT-04:01 0.00
November 276961.31 687.39 04-NOV-04:01 -3.0
December 166360.66 644.06 30-DEC-05:02 -5.3
         
Annual Sum or Average 1315555.92      
Minimum of Months 0.00 0.00   -8.2
Maximum of Months 370725.48 687.39   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.406960E+09 334.50 06-JAN-18:16 -24.4
February 0.299098E+09 317.34 02-FEB-18:02 -15.6
March 0.296056E+09 311.01 07-MAR-18:03 -8.4
April 0.156062E+09 306.12 10-APR-04:01 -2.8
May 63794649.65 304.09 01-MAY-04:02 -2.9
June 26094221.29 268.44 03-JUN-05:01 7.30
July 9375616.41 265.18 10-JUL-05:01 9.68
August 10414382.88 264.35 19-AUG-05:01 4.60
September 33821218.98 268.04 23-SEP-05:01 4.90
October 89355181.91 304.21 14-OCT-04:01 0.00
November 0.150569E+09 305.11 06-NOV-05:01 -3.9
December 0.338114E+09 324.09 19-DEC-18:16 -24.7
         
Annual Sum or Average 0.187971E+10      
Minimum of Months 9375616.41 264.35   -24.7
Maximum of Months 0.406960E+09 334.50   9.68



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 10840631.59 1637.23 17-JAN-05:01 -5.6
February 2764828.33 940.60 18-FEB-06:04 -8.3
March 6079342.37 1606.08 27-MAR-04:01 -3.4
April 2286332.49 1647.93 03-APR-04:01 -5.4
May 252078.62 1344.12 01-MAY-04:02 -2.9
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 645727.61 1425.99 14-OCT-04:01 0.00
November 3399665.28 1556.49 06-NOV-05:01 -3.9
December 3390964.97 1259.77 30-DEC-05:02 -5.3
         
Annual Sum or Average 29659571.25      
Minimum of Months 0.00 0.00   -8.3
Maximum of Months 10840631.59 1647.93   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1378.01 9.19 02-JAN-05:03 -18.2
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 1378.01      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 1378.01 9.19   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 34450002.39 2504.08 17-JAN-05:01 -5.6
February 10345259.78 2261.65 13-FEB-05:03 -23.4
March 11211576.16 2516.88 25-MAR-04:02 -4.3
April 7170405.62 2541.77 29-APR-04:01 0.00
May 6348342.58 2486.98 01-MAY-04:02 -2.9
June 5854310.43 1216.04 03-JUN-05:01 7.30
July 5232067.09 1117.17 08-JUL-05:01 11.70
August 5270876.05 1122.62 19-AUG-05:01 4.60
September 4848918.98 1209.25 23-SEP-05:01 4.90
October 4879972.69 2513.02 14-OCT-04:01 0.00
November 6196046.20 2547.81 04-NOV-04:01 -3.0
December 20232433.30 2513.71 30-DEC-05:02 -5.3
         
Annual Sum or Average 0.122040E+09      
Minimum of Months 4848918.98 1117.17   -23.4
Maximum of Months 34450002.39 2547.81   11.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3797046.30 204.37 02-JAN-05:03 -18.2
February 210817.87 146.54 18-FEB-07:03 -8.2
March 216426.96 146.20 04-MAR-07:03 -5.6
April 143687.31 100.65 10-APR-06:01 -1.9
May 68032.42 103.77 30-MAY-05:01 10.60
June 9915.26 83.85 12-JUN-06:01 12.38
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 9786.57 93.65 10-OCT-06:01 3.90
November 26979.40 92.56 25-NOV-07:03 -19.2
December 743905.57 140.17 26-DEC-05:03 -25.9
         
Annual Sum or Average 5226597.66      
Minimum of Months 0.00 0.00   -25.9
Maximum of Months 3797046.30 204.37   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 SCRUB

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 10126103.73 176.73 17-JAN-05:01 -5.6
February 2061148.35 134.99 27-FEB-07:02 -19.2
March 1154309.14 143.37 04-MAR-07:03 -5.6
April 1595354.97 160.61 10-APR-04:01 -2.8
May 1951566.30 127.73 30-MAY-05:01 10.60
June 488954.69 123.21 12-JUN-05:01 11.78
July 148133.56 120.87 10-JUL-05:01 9.68
August 35351.48 111.99 14-AUG-06:01 15.00
September 405038.25 120.51 05-SEP-05:01 5.60
October 1179867.60 141.75 30-OCT-06:02 -9.4
November 2045084.08 154.03 27-NOV-06:01 -7.1
December 3717171.62 145.89 26-DEC-05:03 -25.9
         
Annual Sum or Average 24908083.75      
Minimum of Months 35351.48 111.99   -25.9
Maximum of Months 10126103.73 176.73   15.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 SOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 36348.09 209.02 17-JAN-05:01 -5.6
February 0.00 0.00 01-FEB-00:10 -23.1
March 17544.23 204.68 27-MAR-04:01 -3.4
April 94390.37 207.02 03-APR-04:01 -5.4
May 20848.42 208.48 01-MAY-04:02 -2.9
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 37942.05 191.16 11-OCT-04:02 0.60
November 36929.73 197.88 06-NOV-05:01 -3.9
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 244002.90      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 94390.37 209.02   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 55473.24 23.88 16-JAN-23:10 -5.3
February 2573.22 8.09 26-FEB-20:41 -5.7
March 16611.83 14.76 20-MAR-00:51 -5.6
April 35648.68 16.95 02-APR-22:31 -5.4
May 29.96 0.30 01-MAY-04:07 -2.9
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 10323.17 18.71 09-OCT-07:02 -4.0
November 27548.75 9.80 12-NOV-18:31 -6.1
December 3615.11 6.96 31-DEC-20:22 -5.6
         
Annual Sum or Average 151823.96      
Minimum of Months 0.00 0.00   -6.1
Maximum of Months 55473.24 23.88   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 76860.64 284.52 17-JAN-05:01 -5.6
February 0.00 0.00 01-FEB-00:10 -23.1
March 69434.68 277.77 27-MAR-04:01 -3.4
April 163964.90 284.32 03-APR-04:01 -5.4
May 29433.50 283.47 01-MAY-04:02 -2.9
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 61947.75 277.71 14-OCT-04:01 0.00
November 111703.11 280.20 04-NOV-04:01 -3.0
December 58680.74 240.33 05-DEC-05:02 -1.3
         
Annual Sum or Average 572025.32      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 163964.90 284.52   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 93897390.11 1739.40 17-JAN-05:01 -5.6
February 41976698.73 1486.34 13-FEB-05:03 -23.4
March 35355234.96 1744.19 25-MAR-04:02 -4.3
April 11889797.45 1755.27 29-APR-04:01 0.00
May 6155341.41 1725.78 01-MAY-04:02 -2.9
June 5395485.07 1168.33 03-JUN-05:01 7.30
July 4866592.43 1120.18 08-JUL-05:01 11.70
August 4633919.45 1126.70 19-AUG-05:01 4.60
September 4330588.23 1163.97 23-SEP-05:01 4.90
October 4154953.46 1739.48 14-OCT-04:01 0.00
November 7998121.77 1755.88 04-NOV-04:01 -3.0
December 59363455.27 1742.15 30-DEC-05:02 -5.3
         
Annual Sum or Average 0.280018E+09      
Minimum of Months 4154953.46 1120.18   -23.4
Maximum of Months 93897390.11 1755.88   11.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 17094487.78 558.21 02-JAN-05:03 -18.2
February 2683915.67 333.58 27-FEB-07:04 -19.2
March 1823466.47 358.58 04-MAR-07:03 -5.6
April 3790315.48 432.12 10-APR-05:02 -2.7
May 5425448.98 383.72 01-MAY-06:04 -3.5
June 1880260.30 221.42 12-JUN-05:01 11.78
July 867343.51 212.75 10-JUL-05:01 9.68
August 258162.61 208.54 14-AUG-06:06 15.00
September 1136350.84 223.51 11-SEP-06:04 11.78
October 2899844.64 358.85 30-OCT-06:03 -9.4
November 3152555.00 379.71 06-NOV-07:03 -3.9
December 4533604.72 384.66 26-DEC-05:03 -25.9
         
Annual Sum or Average 45545756.00      
Minimum of Months 258162.61 208.54   -25.9
Maximum of Months 17094487.78 558.21   15.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.402033E+10 2560.77 07-JAN-18:01 -20.1
February 0.321936E+10 2543.45 21-FEB-06:01 2.80
March 0.333072E+10 2537.93 06-MAR-05:03 -18.4
April 0.206335E+10 2538.65 08-APR-05:01 3.30
May 0.842981E+09 2535.98 30-MAY-05:01 10.60
June 0.351633E+09 2536.81 14-JUN-05:01 9.18
July 0.114517E+09 2534.73 10-JUL-05:01 9.68
August 0.136365E+09 2530.21 19-AUG-05:01 4.60
September 0.418295E+09 2536.46 05-SEP-05:01 5.60
October 0.978240E+09 2534.80 07-OCT-05:01 9.50
November 0.176802E+10 2536.90 21-NOV-06:01 10.10
December 0.341351E+10 2522.80 14-DEC-05:03 -23.4
         
Annual Sum or Average 0.206573E+11      
Minimum of Months 0.114517E+09 2522.80   -23.4
Maximum of Months 0.402033E+10 2560.77   10.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.258083E+09 559.36 30-JAN-05:01 -3.9
February 0.139191E+09 561.63 21-FEB-06:01 2.80
March 0.114100E+09 557.88 27-MAR-04:01 -3.4
April 46541155.18 559.60 10-APR-04:01 -2.8
May 11851318.99 561.92 30-MAY-05:01 10.60
June 1739439.52 549.42 12-JUN-05:01 11.78
July 347640.91 538.07 10-JUL-05:01 9.68
August 221866.13 499.79 14-AUG-06:01 15.00
September 1966503.62 533.00 05-SEP-05:01 5.60
October 16153278.13 549.10 10-OCT-05:01 3.40
November 60742093.71 557.33 06-NOV-05:01 -3.9
December 0.182169E+09 552.39 04-DEC-05:03 -9.2
         
Annual Sum or Average 0.833105E+09      
Minimum of Months 221866.13 499.79   -9.2
Maximum of Months 0.258083E+09 561.92   15.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.902671E+09 746.81 17-JAN-05:01 -5.6
February 0.681687E+09 748.52 21-FEB-06:01 2.80
March 0.658974E+09 746.24 27-MAR-04:01 -3.4
April 0.357005E+09 747.35 15-APR-05:01 5.60
May 0.117366E+09 746.36 30-MAY-05:01 10.60
June 27253412.47 745.27 12-JUN-05:01 11.78
July 7600286.68 741.44 10-JUL-05:01 9.68
August 8312362.44 723.57 19-AUG-05:01 4.60
September 42799437.69 746.37 05-SEP-05:01 5.60
October 0.167417E+09 747.13 10-OCT-05:01 3.40
November 0.340246E+09 746.67 20-NOV-06:01 4.90
December 0.735411E+09 742.00 05-DEC-05:02 -1.3
         
Annual Sum or Average 0.404674E+10      
Minimum of Months 7600286.68 723.57   -5.6
Maximum of Months 0.902671E+09 748.52   11.78



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6480555.87 84.84 02-JAN-05:03 -18.2
February 1756067.73 64.68 27-FEB-07:02 -19.2
March 1346484.09 68.29 04-MAR-07:03 -5.6
April 1741990.77 82.10 10-APR-04:01 -2.8
May 2055146.66 68.92 01-MAY-06:04 -3.5
June 787622.40 58.86 12-JUN-05:01 11.78
July 245714.03 57.60 10-JUL-05:01 9.68
August 47869.58 53.68 21-AUG-06:01 12.77
September 542561.19 57.75 05-SEP-05:01 5.60
October 953196.61 67.87 30-OCT-06:02 -9.4
November 1412334.19 69.01 06-NOV-07:03 -3.9
December 2468293.64 69.49 26-DEC-05:03 -25.9
         
Annual Sum or Average 19837836.77      
Minimum of Months 47869.58 53.68   -25.9
Maximum of Months 6480555.87 84.84   12.77



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.618228E+09 767.44 30-JAN-05:01 -3.9
February 0.422961E+09 768.75 21-FEB-06:01 2.80
March 0.392626E+09 767.66 27-MAR-04:01 -3.4
April 0.170297E+09 767.81 03-APR-04:01 -5.4
May 47880212.20 766.39 30-MAY-05:01 10.60
June 6690594.50 748.55 12-JUN-05:01 11.78
July 906594.87 729.82 10-JUL-05:01 9.68
August 878409.45 694.89 16-AUG-06:01 12.80
September 7686772.63 727.20 05-SEP-05:01 5.60
October 76838251.91 763.61 10-OCT-05:01 3.40
November 0.209300E+09 767.57 06-NOV-05:01 -3.9
December 0.488645E+09 761.99 05-DEC-05:02 -1.3
         
Annual Sum or Average 0.244294E+10      
Minimum of Months 878409.45 694.89   -5.4
Maximum of Months 0.618228E+09 768.75   12.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.821616E+09 612.29 06-JAN-09:23 -33.6
February 0.670363E+09 597.80 14-FEB-07:03 -33.0
March 0.695099E+09 560.79 15-MAR-06:03 -22.5
April 0.428827E+09 482.48 05-APR-06:03 -13.5
May 0.214127E+09 394.70 01-MAY-06:03 -3.5
June 0.121279E+09 288.64 02-JUN-06:03 9.08
July 82031069.92 271.43 18-JUL-06:03 11.23
August 0.145108E+09 288.09 25-AUG-06:03 9.05
September 0.230504E+09 345.85 06-SEP-06:03 2.38
October 0.380872E+09 444.37 30-OCT-06:03 -9.4
November 0.528570E+09 524.63 29-NOV-07:03 -18.4
December 0.759333E+09 580.35 20-DEC-09:00 -29.4
         
Annual Sum or Average 0.507773E+10      
Minimum of Months 82031069.92 271.43   -33.6
Maximum of Months 0.821616E+09 612.29   11.23



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.204762E+09 1776.64 14-JAN-05:03 -23.1
February 79503271.95 1774.90 13-FEB-05:03 -23.4
March 38526377.24 1734.16 04-MAR-05:02 -5.0
April 6808869.22 1730.60 10-APR-05:01 -2.7
May 1445137.17 1703.77 13-MAY-05:01 4.57
June 809981.91 1467.61 10-JUN-05:01 14.60
July 832246.28 1477.82 05-JUL-05:01 19.60
August 649973.63 1267.04 19-AUG-05:01 4.60
September 1098466.21 1548.38 23-SEP-05:01 4.90
October 6089639.46 1712.01 30-OCT-05:01 -9.9
November 49010813.01 1765.41 27-NOV-05:02 -7.2
December 0.196294E+09 1779.53 11-DEC-05:03 -24.6
         
Annual Sum or Average 0.585831E+09      
Minimum of Months 649973.63 1267.04   -24.6
Maximum of Months 0.204762E+09 1779.53   19.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 8692257.88 471.67 17-JAN-05:01 -5.6
February 4293907.54 473.10 21-FEB-06:01 2.80
March 2917669.35 440.64 27-MAR-06:01 -3.4
April 2334073.41 470.47 10-APR-04:01 -2.8
May 2003391.82 470.21 30-MAY-05:01 10.60
June 1752390.74 455.77 12-JUN-05:01 11.78
July 1803143.32 465.09 10-JUL-05:01 9.68
August 1375359.60 441.46 28-AUG-05:01 13.90
September 1407690.25 463.33 05-SEP-05:01 5.60
October 2604979.15 472.49 16-OCT-05:01 5.60
November 5105786.57 475.68 20-NOV-06:01 4.90
December 6814339.68 441.23 04-DEC-07:01 -9.4
         
Annual Sum or Average 41104989.33      
Minimum of Months 1375359.60 440.64   -9.4
Maximum of Months 8692257.88 475.68   13.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 266884.17 91.00 17-JAN-07:12 -7.6
February 35021.93 84.28 21-FEB-07:01 2.70
March 8229.44 72.59 06-MAR-07:03 -19.3
April 8145.59 70.04 10-APR-06:01 -1.9
May 8776.55 80.83 30-MAY-06:02 10.63
June 7389.78 68.13 12-JUN-06:01 12.38
July 5241.42 32.10 05-JUL-06:03 20.60
August 0.00 0.00 01-AUG-00:10 17.07
September 4594.64 40.92 18-SEP-06:01 12.98
October 14354.17 84.88 16-OCT-06:01 5.60
November 37157.49 90.72 20-NOV-07:01 4.32
December 150218.15 86.03 18-DEC-07:02 -18.1
         
Annual Sum or Average 546013.34      
Minimum of Months 0.00 0.00   -19.3
Maximum of Months 266884.17 91.00   20.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.374593E+09 2891.79 17-JAN-05:01 -5.6
February 0.163368E+09 2986.29 21-FEB-06:01 2.80
March 63664639.87 2753.72 14-MAR-06:01 -14.2
April 12850970.05 2957.88 08-APR-05:01 3.30
May 6925840.55 2944.35 30-MAY-05:01 10.60
June 6031460.20 2854.68 12-JUN-05:01 11.78
July 5377679.70 2889.47 10-JUL-05:01 9.68
August 6645599.89 2896.73 19-AUG-05:01 4.60
September 7264872.38 2914.88 05-SEP-05:01 5.60
October 13587117.17 2983.33 10-OCT-05:01 3.40
November 61825927.45 2993.01 20-NOV-06:01 4.90
December 0.314573E+09 2763.10 04-DEC-07:01 -9.4
         
Annual Sum or Average 0.103671E+10      
Minimum of Months 5377679.70 2753.72   -14.2
Maximum of Months 0.374593E+09 2993.01   11.78



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 21001998.75 5278.12 17-JAN-07:01 -7.4
February 15210068.96 6086.27 21-FEB-06:01 2.80
March 14927258.48 5141.59 13-MAR-06:01 -13.3
April 13038020.43 5956.16 24-APR-05:01 4.40
May 14071651.23 6015.78 08-MAY-05:01 5.77
June 13870584.12 5832.56 12-JUN-05:01 11.78
July 13679368.68 6008.60 10-JUL-05:01 9.68
August 15061964.61 5759.63 28-AUG-05:01 13.90
September 13128363.02 6016.47 05-SEP-05:01 5.60
October 13432505.65 6083.11 10-OCT-05:01 3.40
November 15390761.31 6101.84 20-NOV-06:01 4.90
December 19178901.75 5294.47 04-DEC-07:01 -9.4
         
Annual Sum or Average 0.181991E+09      
Minimum of Months 13038020.43 5141.59   -13.3
Maximum of Months 21001998.75 6101.84   13.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 28946972.75 7037.87 17-JAN-07:01 -7.4
February 21069355.44 8117.09 21-FEB-06:01 2.80
March 21490955.39 6886.22 13-MAR-06:01 -13.3
April 19231349.98 8052.51 24-APR-05:01 4.40
May 21088097.26 8062.05 15-MAY-05:01 6.87
June 20687661.86 7947.99 03-JUN-05:01 7.30
July 19980209.80 8061.80 10-JUL-05:01 9.68
August 21761285.12 7970.30 19-AUG-05:01 4.60
September 19536867.52 8066.84 05-SEP-05:01 5.60
October 19754042.56 8114.06 16-OCT-05:01 5.60
November 21733092.64 8137.97 20-NOV-06:01 4.90
December 26519152.92 7051.61 04-DEC-07:01 -9.4
         
Annual Sum or Average 0.261799E+09      
Minimum of Months 19231349.98 6886.22   -13.3
Maximum of Months 28946972.75 8137.97   9.68



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 35358320.01 709.28 17-JAN-07:01 -7.4
February 15450643.57 765.13 21-FEB-06:01 2.80
March 8058529.86 705.25 13-MAR-06:01 -13.3
April 2828472.28 747.95 24-APR-05:01 4.40
May 2000699.99 756.29 08-MAY-05:01 5.77
June 1778574.24 735.22 12-JUN-05:01 11.78
July 1718582.76 756.61 10-JUL-05:01 9.68
August 1854833.24 736.62 19-AUG-05:01 4.60
September 1740776.73 750.38 05-SEP-05:01 5.60
October 3098154.62 765.14 16-OCT-05:01 5.60
November 8974146.38 767.56 20-NOV-06:01 4.90
December 31411606.71 708.66 04-DEC-07:01 -9.4
         
Annual Sum or Average 0.114273E+09      
Minimum of Months 1718582.76 705.25   -13.3
Maximum of Months 35358320.01 767.56   11.78



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 62586026.42 3169.48 17-JAN-07:01 -7.4
February 21661506.81 3439.81 21-FEB-06:01 2.80
March 14402274.31 3165.00 27-MAR-06:01 -3.4
April 8639616.34 3354.47 08-APR-05:01 3.30
May 5234727.07 3326.80 30-MAY-05:01 10.60
June 2822313.29 3133.22 10-JUN-05:01 14.60
July 2797830.82 2969.29 05-JUL-05:01 19.60
August 5212953.28 2932.96 16-AUG-06:01 12.80
September 6100950.50 3125.82 25-SEP-06:01 6.60
October 8424275.89 3414.04 10-OCT-05:01 3.40
November 13339970.91 3440.40 20-NOV-06:01 4.90
December 47250173.91 3169.86 05-DEC-07:01 -1.1
         
Annual Sum or Average 0.198473E+09      
Minimum of Months 2797830.82 2932.96   -7.4
Maximum of Months 62586026.42 3440.40   19.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 76703067.16 2212.99 17-JAN-07:01 -7.4
February 27934894.16 2397.08 21-FEB-06:01 2.80
March 15698208.41 2208.40 13-MAR-06:01 -13.3
April 7509347.08 2374.54 24-APR-05:01 4.40
May 6363355.58 2374.87 15-MAY-05:01 6.87
June 5487081.82 2293.38 12-JUN-05:01 11.78
July 5352878.92 2352.48 10-JUL-05:01 9.68
August 6173866.72 2325.06 19-AUG-05:01 4.60
September 5953130.07 2378.29 05-SEP-05:01 5.60
October 7011767.53 2394.65 10-OCT-05:01 3.40
November 12116302.43 2400.39 20-NOV-06:01 4.90
December 64907950.65 2211.77 04-DEC-07:01 -9.4
         
Annual Sum or Average 0.241212E+09      
Minimum of Months 5352878.92 2208.40   -13.3
Maximum of Months 76703067.16 2400.39   11.78



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 35861593.03 7607.60 17-JAN-07:01 -7.4
February 21327054.97 8932.97 21-FEB-06:01 2.80
March 22057954.15 7622.01 13-MAR-06:01 -13.3
April 19797374.65 8840.46 24-APR-05:01 4.40
May 21340020.05 8834.97 15-MAY-05:01 6.87
June 20512804.69 8548.95 12-JUN-05:01 11.78
July 20505227.82 8805.56 10-JUL-05:01 9.68
August 22736185.12 8450.06 28-AUG-05:01 13.90
September 20164818.19 8870.86 05-SEP-05:01 5.60
October 20476041.47 8926.12 10-OCT-05:01 3.40
November 20594115.31 8946.35 20-NOV-06:01 4.90
December 24922342.55 7614.28 04-DEC-07:01 -9.4
         
Annual Sum or Average 0.270296E+09      
Minimum of Months 19797374.65 7607.60   -13.3
Maximum of Months 35861593.03 8946.35   13.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 63781493.05 2624.63 17-JAN-07:01 -7.4
February 17487918.78 2845.71 21-FEB-06:01 2.80
March 10705171.47 2619.37 13-MAR-06:01 -13.3
April 6881947.97 2784.81 24-APR-05:01 4.40
May 5832336.70 2781.67 30-MAY-05:01 10.60
June 4750347.32 2583.50 10-JUN-05:01 14.60
July 5178669.59 2633.65 31-JUL-05:01 14.68
August 6068937.57 2659.73 28-AUG-05:01 13.90
September 5432331.54 2801.80 05-SEP-05:01 5.60
October 6446698.47 2841.79 10-OCT-05:01 3.40
November 9829887.44 2847.87 20-NOV-06:01 4.90
December 43533943.88 2622.81 04-DEC-07:01 -9.4
         
Annual Sum or Average 0.185930E+09      
Minimum of Months 4750347.32 2583.50   -13.3
Maximum of Months 63781493.05 2847.87   14.68



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 20665332.38 3838.58 17-JAN-07:01 -7.4
February 10224345.41 4466.94 21-FEB-06:01 2.80
March 10224109.43 3853.14 13-MAR-06:01 -13.3
April 8660260.52 4348.15 24-APR-05:01 4.40
May 8453345.91 4366.12 30-MAY-05:01 10.60
June 7760579.39 4072.49 10-JUN-05:01 14.60
July 8208349.24 4144.24 31-JUL-05:01 14.68
August 9258939.00 4181.95 28-AUG-05:01 13.90
September 7638006.69 4375.93 05-SEP-05:01 5.60
October 8578929.04 4461.31 10-OCT-05:01 3.40
November 9479935.76 4468.56 20-NOV-06:01 4.90
December 12145311.51 3842.34 04-DEC-07:01 -9.4
         
Annual Sum or Average 0.121297E+09      
Minimum of Months 7638006.69 3838.58   -13.3
Maximum of Months 20665332.38 4468.56   14.68



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 42325490.14 416.82 17-JAN-05:01 -5.6
February 18936300.61 433.84 06-FEB-05:03 -20.1
March 7966775.60 418.80 06-MAR-05:03 -18.4
April 3602357.21 411.76 10-APR-05:02 -2.7
May 1472580.16 396.36 31-MAY-06:01 7.83
June 545282.45 385.83 12-JUN-06:03 12.38
July 410043.06 352.50 03-JUL-06:03 18.90
August 153440.36 348.60 14-AUG-06:01 15.00
September 433976.69 364.72 11-SEP-06:02 11.78
October 4423356.00 415.44 16-OCT-05:02 5.60
November 16109644.13 421.61 06-NOV-05:01 -3.9
December 33274616.22 423.74 18-DEC-05:03 -15.2
         
Annual Sum or Average 0.129654E+09      
Minimum of Months 153440.36 348.60   -20.1
Maximum of Months 42325490.14 433.84   18.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 15018190.29 262.12 02-JAN-05:05 -18.2
February 6316349.91 252.23 08-FEB-07:01 -5.1
March 3281651.01 268.33 06-MAR-05:03 -18.4
April 2452117.14 258.62 10-APR-05:03 -2.7
May 1527217.32 250.96 09-MAY-06:01 5.12
June 691823.94 234.41 12-JUN-05:01 11.78
July 717113.47 237.26 05-JUL-05:01 19.60
August 329417.32 234.78 28-AUG-06:04 14.08
September 639756.90 248.84 05-SEP-06:12 6.50
October 3031283.46 248.71 10-OCT-06:15 3.90
November 8668408.12 269.01 06-NOV-05:01 -3.9
December 11149057.65 273.99 18-DEC-05:03 -15.2
         
Annual Sum or Average 53822386.53      
Minimum of Months 329417.32 234.41   -18.4
Maximum of Months 15018190.29 273.99   19.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 16460359.04 282.92 30-JAN-05:01 -3.9
February 7518730.48 255.01 18-FEB-07:05 -8.2
March 4025460.48 278.85 06-MAR-05:03 -18.4
April 3740763.33 274.35 10-APR-04:01 -2.8
May 3357464.76 255.89 30-MAY-06:25 10.70
June 1839947.81 256.77 12-JUN-05:02 11.78
July 2343089.12 261.91 10-JUL-05:02 9.68
August 1121490.02 256.26 07-AUG-05:01 13.80
September 1645464.28 256.72 05-SEP-06:06 6.05
October 4373323.73 269.47 16-OCT-05:03 5.60
November 10149925.04 271.67 24-NOV-06:03 -10.5
December 12244464.09 283.43 04-DEC-05:03 -9.2
         
Annual Sum or Average 68820482.19      
Minimum of Months 1121490.02 255.01   -18.4
Maximum of Months 16460359.04 283.43   13.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 14870525.15 195.81 02-JAN-05:30 -18.1
February 5658578.51 181.83 21-FEB-07:50 2.30
March 3570687.23 183.96 13-MAR-05:04 -13.3
April 1585780.64 183.74 10-APR-05:03 -2.7
May 773917.48 181.01 30-MAY-05:02 10.60
June 221660.85 166.09 12-JUN-06:08 12.38
July 312696.72 169.89 17-JUL-06:12 13.33
August 213267.52 175.50 07-AUG-06:12 13.50
September 631366.26 183.30 05-SEP-06:17 6.50
October 2390652.21 186.61 16-OCT-05:02 5.60
November 5016473.21 201.21 13-NOV-05:03 -7.9
December 7568500.85 200.71 04-DEC-05:03 -9.2
         
Annual Sum or Average 42814106.63      
Minimum of Months 213267.52 166.09   -18.1
Maximum of Months 14870525.15 201.21   13.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 13316305.53 196.20 02-JAN-05:30 -18.1
February 4575243.91 191.33 21-FEB-06:13 2.80
March 2679880.61 196.85 20-MAR-05:01 -8.7
April 723079.62 183.76 10-APR-06:16 -1.7
May 187923.61 178.34 01-MAY-06:12 -3.0
June 62571.47 164.27 12-JUN-06:02 12.38
July 60465.22 157.55 05-JUL-06:03 20.60
August 44719.19 177.09 28-AUG-06:01 14.08
September 135371.11 184.14 05-SEP-06:12 6.50
October 1089084.71 189.89 30-OCT-05:01 -9.9
November 3297404.60 182.45 27-NOV-06:04 -7.1
December 6338690.20 193.52 04-DEC-06:12 -9.4
         
Annual Sum or Average 32510739.77      
Minimum of Months 44719.19 157.55   -18.1
Maximum of Months 13316305.53 196.85   20.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 22912402.80 239.43 02-JAN-05:30 -18.1
February 8118278.31 223.69 21-FEB-06:13 2.80
March 4815800.59 223.67 06-MAR-05:03 -18.4
April 1249801.75 217.48 03-APR-05:02 -4.3
May 297624.54 210.78 01-MAY-06:12 -3.0
June 98088.66 185.81 05-JUN-06:03 14.08
July 102739.53 197.46 17-JUL-06:01 13.07
August 59331.08 182.16 21-AUG-06:02 12.77
September 185528.41 201.48 25-SEP-06:03 6.60
October 1693350.95 219.80 30-OCT-05:02 -9.9
November 5581435.70 232.48 27-NOV-06:04 -7.1
December 11564214.67 239.19 04-DEC-05:03 -9.2
         
Annual Sum or Average 56678596.99      
Minimum of Months 59331.08 182.16   -18.4
Maximum of Months 22912402.80 239.43   14.08



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.142152E+09 417.30 17-JAN-05:01 -5.6
February 84994301.96 421.08 21-FEB-06:01 2.80
March 48909405.20 411.77 27-MAR-04:01 -3.4
April 14730609.24 415.96 10-APR-04:01 -2.8
May 4452194.86 407.58 30-MAY-05:01 10.60
June 650197.91 389.59 12-JUN-06:01 12.38
July 292025.56 388.06 10-JUL-06:01 11.75
August 149109.75 384.85 21-AUG-06:01 12.77
September 1565974.35 390.93 18-SEP-06:01 12.98
October 9374137.07 420.34 10-OCT-05:01 3.40
November 33089777.17 421.31 20-NOV-06:01 4.90
December 0.115901E+09 412.64 26-DEC-05:03 -25.9
         
Annual Sum or Average 0.456261E+09      
Minimum of Months 149109.75 384.85   -25.9
Maximum of Months 0.142152E+09 421.31   12.98



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 11933.82 61.49 09-JAN-07:01 -32.3
February 12232.02 81.55 25-FEB-07:03 -29.3
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 5952.29 39.68 25-NOV-07:03 -19.2
December 13403.94 127.46 26-DEC-07:01 -26.5
         
Annual Sum or Average 43522.06      
Minimum of Months 0.00 0.00   -32.3
Maximum of Months 13403.94 127.46   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 179802.19 332.28 02-JAN-06:01 -17.8
February 15449.83 103.00 25-FEB-07:03 -29.3
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 26800.92 178.67 25-NOV-07:03 -19.2
December 76746.83 252.38 26-DEC-07:02 -26.5
         
Annual Sum or Average 298799.77      
Minimum of Months 0.00 0.00   -29.3
Maximum of Months 179802.19 332.28   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 198364.37 364.05 02-JAN-06:01 -17.8
February 19899.89 132.67 25-FEB-07:03 -29.3
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 16713.39 111.42 25-NOV-07:03 -19.2
December 74529.05 352.33 26-DEC-07:02 -26.5
         
Annual Sum or Average 309506.68      
Minimum of Months 0.00 0.00   -29.3
Maximum of Months 198364.37 364.05   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.336801E+09 2275.05 13-JAN-05:03 -30.2
February 0.112321E+09 2279.58 02-FEB-05:03 -25.5
March 37676979.10 2257.51 13-MAR-04:03 -13.3
April 6300232.32 2210.88 03-APR-04:01 -5.4
May 99889.21 1332.68 30-MAY-06:01 10.63
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 56568.73 377.12 23-SEP-06:03 4.32
October 5863107.07 2276.30 30-OCT-04:03 -10.0
November 60352855.55 2256.52 24-NOV-05:03 -10.6
December 0.280627E+09 2279.16 02-DEC-05:03 -27.3
         
Annual Sum or Average 0.840099E+09      
Minimum of Months 0.00 0.00   -30.2
Maximum of Months 0.336801E+09 2279.58   17.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 33900889.85 677.26 17-JAN-05:03 -5.6
February 11108814.79 639.35 27-FEB-06:03 -18.5
March 4346867.85 647.16 20-MAR-06:12 -10.8
April 2100695.32 594.49 04-APR-06:02 -9.2
May 474819.86 612.75 01-MAY-06:02 -3.5
June 66475.42 603.56 12-JUN-06:02 12.38
July 52431.74 517.04 10-JUL-06:01 11.75
August 0.00 0.00 01-AUG-00:10 17.07
September 190054.57 561.45 25-SEP-06:01 6.60
October 2675979.18 670.91 30-OCT-05:02 -9.9
November 11521200.40 650.20 06-NOV-06:02 -3.9
December 22960063.42 689.89 11-DEC-05:03 -24.6
         
Annual Sum or Average 89398292.39      
Minimum of Months 0.00 0.00   -24.6
Maximum of Months 33900889.85 689.89   17.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 66397543.43 3432.64 23-JAN-05:03 -22.8
February 13254771.81 3488.97 27-FEB-05:03 -17.4
March 5180043.55 3437.09 06-MAR-05:03 -18.4
April 1466692.09 3281.38 03-APR-05:01 -4.3
May 52920.47 352.80 13-MAY-06:03 4.62
June 3092.62 20.62 10-JUN-06:03 15.68
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 1067006.88 3192.01 30-OCT-05:01 -9.9
November 8459734.99 3507.79 27-NOV-05:02 -7.2
December 47103535.49 3467.25 18-DEC-05:03 -15.2
         
Annual Sum or Average 0.142985E+09      
Minimum of Months 0.00 0.00   -22.8
Maximum of Months 66397543.43 3507.79   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3340719.58 501.57 02-JAN-06:11 -17.8
February 386841.73 417.33 06-FEB-07:04 -20.7
March 136436.61 463.50 06-MAR-07:05 -19.3
April 52647.65 356.90 10-APR-06:01 -1.9
May 25359.20 422.65 30-MAY-06:01 10.63
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 95597.94 492.54 30-OCT-06:02 -9.4
November 347884.60 499.24 20-NOV-07:01 4.32
December 1783608.01 501.11 18-DEC-07:04 -18.1
         
Annual Sum or Average 6169095.33      
Minimum of Months 0.00 0.00   -20.7
Maximum of Months 3340719.58 501.57   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 10130648.37 860.43 17-JAN-05:01 -5.6
February 3807608.46 850.47 21-FEB-06:01 2.80
March 2629636.37 802.69 27-MAR-06:01 -3.4
April 1686757.65 803.86 10-APR-06:01 -1.9
May 1279305.76 831.12 30-MAY-05:01 10.60
June 1436500.07 772.18 12-JUN-06:01 12.38
July 1410854.30 782.18 10-JUL-06:01 11.75
August 1282946.02 777.13 21-AUG-06:01 12.77
September 1069166.68 800.48 05-SEP-06:01 6.05
October 1735876.02 842.69 10-OCT-05:01 3.40
November 3639896.59 846.89 20-NOV-06:01 4.90
December 6885784.96 803.54 05-DEC-07:01 -1.1
         
Annual Sum or Average 36994981.25      
Minimum of Months 1069166.68 772.18   -5.6
Maximum of Months 10130648.37 860.43   12.77



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 100336.56 360.41 02-JAN-07:03 -18.1
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 48968.19 189.08 26-DEC-07:02 -26.5
         
Annual Sum or Average 149304.75      
Minimum of Months 0.00 0.00   -26.5
Maximum of Months 100336.56 360.41   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 199942.90 422.18 02-JAN-07:03 -18.1
February 32746.47 218.31 25-FEB-07:03 -29.3
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 95121.53 212.58 26-DEC-07:13 -26.4
         
Annual Sum or Average 327810.90      
Minimum of Months 0.00 0.00   -29.3
Maximum of Months 199942.90 422.18   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 9029649.93 110.44 03-JAN-06:01 -10.6
February 4327192.64 113.75 27-FEB-05:03 -17.4
March 2851962.93 110.09 06-MAR-05:03 -18.4
April 2644263.37 104.29 08-APR-06:03 3.48
May 2667092.20 107.85 22-MAY-05:02 8.65
June 1929528.74 100.28 08-JUN-06:01 11.65
July 2371683.73 101.96 31-JUL-05:03 14.68
August 1347651.63 104.11 07-AUG-05:02 13.80
September 1589053.81 102.58 06-SEP-06:02 2.38
October 3240484.15 112.45 30-OCT-04:03 -10.0
November 6165302.11 104.33 07-NOV-07:12 -7.1
December 7043355.90 112.53 26-DEC-05:05 -25.9
         
Annual Sum or Average 45207221.14      
Minimum of Months 1347651.63 100.28   -25.9
Maximum of Months 9029649.93 113.75   14.68



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 15035691.83 243.07 30-JAN-05:01 -3.9
February 5803015.11 235.04 21-FEB-06:01 2.80
March 3498729.61 224.84 20-MAR-05:01 -8.7
April 1799981.64 226.87 10-APR-05:01 -2.7
May 1025975.23 229.57 30-MAY-05:02 10.60
June 515811.77 227.16 12-JUN-05:01 11.78
July 601239.24 207.40 10-JUL-06:01 11.75
August 396561.91 205.82 14-AUG-06:04 15.00
September 798130.82 220.65 05-SEP-05:01 5.60
October 2449666.83 230.45 10-OCT-05:01 3.40
November 5015509.90 243.44 27-NOV-05:02 -7.2
December 9831311.30 239.08 26-DEC-05:03 -25.9
         
Annual Sum or Average 46771625.19      
Minimum of Months 396561.91 205.82   -25.9
Maximum of Months 15035691.83 243.44   15.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 16603798.18 283.23 02-JAN-05:03 -18.2
February 5701969.19 275.37 21-FEB-06:01 2.80
March 3275930.68 268.82 27-MAR-05:01 -3.9
April 1021594.42 267.40 03-APR-06:12 -3.7
May 387387.09 249.65 01-MAY-06:01 -3.5
June 159392.98 249.67 05-JUN-06:03 14.08
July 229731.73 239.97 24-JUL-06:03 18.68
August 145717.09 241.14 28-AUG-06:02 14.08
September 253352.99 248.30 05-SEP-06:01 6.05
October 1286403.16 271.99 30-OCT-05:01 -9.9
November 3611313.79 282.47 24-NOV-06:01 -10.5
December 9719698.65 292.41 11-DEC-05:03 -24.6
         
Annual Sum or Average 42396289.94      
Minimum of Months 145717.09 239.97   -24.6
Maximum of Months 16603798.18 292.41   18.68



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.205635E+09 658.18 17-JAN-05:01 -5.6
February 99795380.48 663.53 21-FEB-06:01 2.80
March 50027361.77 645.59 06-MAR-05:03 -18.4
April 11778067.77 657.23 10-APR-04:01 -2.8
May 1853529.45 641.50 30-MAY-05:01 10.60
June 237492.82 589.53 12-JUN-06:01 12.38
July 203074.25 585.59 10-JUL-06:01 11.75
August 259441.81 578.30 28-AUG-06:01 14.08
September 1889790.94 636.54 05-SEP-05:01 5.60
October 16549222.40 653.88 10-OCT-05:01 3.40
November 62004924.60 664.81 20-NOV-06:01 4.90
December 0.181753E+09 649.72 26-DEC-05:03 -25.9
         
Annual Sum or Average 0.631986E+09      
Minimum of Months 203074.25 578.30   -25.9
Maximum of Months 0.205635E+09 664.81   14.08



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 17193271.02 2401.59 09-JAN-05:03 -33.0
February 3574231.89 2313.14 21-FEB-06:01 2.80
March 1079342.55 2167.65 06-MAR-07:04 -19.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 1161705.72 2142.89 27-NOV-07:02 -6.7
December 8406556.56 2311.51 04-DEC-06:01 -9.4
         
Annual Sum or Average 31415107.73      
Minimum of Months 0.00 0.00   -33.0
Maximum of Months 17193271.02 2401.59   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 9206172.08 794.97 02-JAN-05:03 -18.2
February 797072.24 744.58 06-FEB-07:04 -20.7
March 304058.43 602.78 06-MAR-07:06 -19.3
April 4474.86 74.58 10-APR-06:01 -1.9
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 52853.54 712.86 10-OCT-06:01 3.90
November 408344.82 758.36 13-NOV-07:03 -8.7
December 3929982.30 726.63 18-DEC-07:04 -18.1
         
Annual Sum or Average 14702958.27      
Minimum of Months 0.00 0.00   -20.7
Maximum of Months 9206172.08 794.97   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 96705336.05 443.17 17-JAN-05:01 -5.6
February 61291725.67 448.84 21-FEB-06:01 2.80
March 43384059.46 418.80 13-MAR-05:01 -13.3
April 16869441.27 440.36 24-APR-05:01 4.40
May 5836008.62 443.56 08-MAY-05:01 5.77
June 2038381.33 429.20 12-JUN-05:01 11.78
July 1279537.16 432.34 10-JUL-05:01 9.68
August 1206622.00 413.74 21-AUG-05:01 12.70
September 2489634.52 438.77 05-SEP-05:01 5.60
October 10181246.86 448.20 10-OCT-05:01 3.40
November 28108578.56 449.34 20-NOV-06:01 4.90
December 78678442.11 419.70 04-DEC-06:01 -9.4
         
Annual Sum or Average 0.348069E+09      
Minimum of Months 1206622.00 413.74   -13.3
Maximum of Months 96705336.05 449.34   12.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 2 X-RAY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2353476.05 153.24 02-JAN-05:03 -18.2
February 1022517.12 145.95 21-FEB-06:01 2.80
March 330445.47 142.86 13-MAR-05:01 -13.3
April 51105.48 131.04 03-APR-06:01 -3.8
May 9936.30 95.07 30-MAY-06:01 10.63
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 5008.07 70.49 05-SEP-06:01 6.05
October 93057.53 149.30 30-OCT-05:01 -9.9
November 456648.28 145.55 24-NOV-06:01 -10.5
December 1574922.32 153.81 26-DEC-05:03 -25.9
         
Annual Sum or Average 5897116.61      
Minimum of Months 0.00 0.00   -25.9
Maximum of Months 2353476.05 153.81   17.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.261932E+09 959.30 17-JAN-05:01 -5.6
February 0.129365E+09 962.93 21-FEB-06:01 2.80
March 71935785.45 948.33 06-MAR-05:03 -18.4
April 16139810.52 949.00 03-APR-04:01 -5.4
May 2332379.11 913.19 01-MAY-05:01 -3.4
June 120693.27 864.98 12-JUN-06:01 12.38
July 42516.56 708.61 10-JUL-06:01 11.75
August 27276.52 181.84 19-AUG-06:03 6.23
September 352265.33 869.74 05-SEP-06:01 6.05
October 11593655.10 943.80 30-OCT-04:03 -10.0
November 50246187.36 952.20 27-NOV-05:02 -7.2
December 0.199287E+09 951.34 26-DEC-05:03 -25.9
         
Annual Sum or Average 0.743374E+09      
Minimum of Months 27276.52 181.84   -25.9
Maximum of Months 0.261932E+09 962.93   12.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3520143.17 327.81 02-JAN-05:03 -18.2
February 1313871.12 310.96 13-FEB-06:02 -24.0
March 416997.92 315.77 13-MAR-05:01 -13.3
April 38626.78 292.70 10-APR-06:01 -1.9
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 75175.65 273.68 30-OCT-06:01 -9.4
November 562009.47 308.46 20-NOV-07:01 4.32
December 2118066.16 329.80 26-DEC-05:03 -25.9
         
Annual Sum or Average 8044890.27      
Minimum of Months 0.00 0.00   -25.9
Maximum of Months 3520143.17 329.80   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.342316E+09 280.29 09-JAN-05:03 -33.0
February 0.240581E+09 280.33 21-FEB-06:01 2.80
March 0.181411E+09 278.23 27-MAR-04:01 -3.4
April 77518988.21 279.30 26-APR-05:01 2.02
May 21419814.00 280.19 30-MAY-05:01 10.60
June 5939021.87 279.26 12-JUN-05:01 11.78
July 3641201.00 275.83 10-JUL-05:01 9.68
August 4960048.50 272.76 21-AUG-05:01 12.70
September 18717294.16 280.21 05-SEP-05:01 5.60
October 67289798.01 280.25 31-OCT-05:01 10.00
November 0.150231E+09 280.46 20-NOV-06:01 4.90
December 0.311213E+09 279.19 11-DEC-05:03 -24.6
         
Annual Sum or Average 0.142524E+10      
Minimum of Months 3641201.00 272.76   -33.0
Maximum of Months 0.342316E+09 280.46   12.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 LOCKER

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 4830962.20 331.23 02-JAN-05:03 -18.2
February 753233.50 342.56 13-FEB-05:03 -23.4
March 263262.76 319.50 13-MAR-05:01 -13.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 5195.87 51.96 14-OCT-06:02 -1.1
November 342662.71 329.08 27-NOV-06:01 -7.1
December 2696592.22 339.46 11-DEC-05:03 -24.6
         
Annual Sum or Average 8891909.27      
Minimum of Months 0.00 0.00   -24.6
Maximum of Months 4830962.20 342.56   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 26921164.95 1639.33 02-JAN-05:03 -18.2
February 3531755.26 1563.91 04-FEB-06:01 -16.0
March 1124130.45 1554.21 04-MAR-07:03 -5.6
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 7099.11 70.99 14-OCT-06:02 -1.1
November 1045684.45 1442.59 25-NOV-07:05 -19.2
December 17394093.19 1694.11 04-DEC-06:01 -9.4
         
Annual Sum or Average 50023927.41      
Minimum of Months 0.00 0.00   -19.2
Maximum of Months 26921164.95 1694.11   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.369946E+09 1281.68 17-JAN-05:01 -5.6
February 0.198690E+09 1293.73 21-FEB-06:01 2.80
March 0.114276E+09 1271.50 27-MAR-04:01 -3.4
April 29537376.68 1280.66 24-APR-05:01 4.40
May 8578872.48 1280.93 15-MAY-05:01 6.87
June 4660829.13 1231.58 12-JUN-05:01 11.78
July 4977969.87 1265.14 10-JUL-05:01 9.68
August 5536546.41 1250.90 19-AUG-05:01 4.60
September 7898449.02 1282.80 05-SEP-05:01 5.60
October 26066294.53 1291.77 10-OCT-05:01 3.40
November 88545858.27 1295.08 20-NOV-06:01 4.90
December 0.315265E+09 1264.62 30-DEC-05:02 -5.3
         
Annual Sum or Average 0.117398E+10      
Minimum of Months 4660829.13 1231.58   -5.6
Maximum of Months 0.369946E+09 1295.08   11.78



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -21.9
February 0.00 0.00 01-FEB-00:10 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:02 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:03 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 80658467.54 1126.68 09-JAN-05:03 -33.0
February 30411212.08 1119.37 13-FEB-05:03 -23.4
March 7358889.99 1092.02 06-MAR-06:01 -19.0
April 417645.63 1041.60 03-APR-06:01 -3.8
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 722817.82 1056.03 30-OCT-06:01 -9.4
November 9165829.77 1092.30 25-NOV-06:01 -19.4
December 53189241.04 1124.99 26-DEC-05:03 -25.9
         
Annual Sum or Average 0.181924E+09      
Minimum of Months 0.00 0.00   -33.0
Maximum of Months 80658467.54 1126.68   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.744197E+09 7522.27 17-JAN-05:01 -5.6
February 0.246984E+09 7436.70 14-FEB-05:03 -32.1
March 88781282.65 7420.17 06-MAR-05:03 -18.4
April 8786263.30 7260.24 03-APR-04:01 -5.4
May 786868.87 6599.56 01-MAY-05:01 -3.4
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 8657140.09 7254.67 30-OCT-04:03 -10.0
November 66765383.51 7425.57 27-NOV-05:02 -7.2
December 0.579214E+09 7469.27 26-DEC-05:03 -25.9
         
Annual Sum or Average 0.174417E+10      
Minimum of Months 0.00 0.00   -32.1
Maximum of Months 0.744197E+09 7522.27   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.303698E+09 2629.60 17-JAN-05:01 -5.6
February 0.132681E+09 2591.88 27-FEB-05:03 -17.4
March 56996985.06 2589.68 06-MAR-05:03 -18.4
April 10255490.80 2510.28 10-APR-05:01 -2.7
May 1267026.27 2416.51 01-MAY-06:01 -3.5
June 23737.85 356.07 12-JUN-06:01 12.38
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 226229.64 2161.11 05-SEP-06:01 6.05
October 13072669.60 2514.77 10-OCT-05:01 3.40
November 62315789.72 2601.46 27-NOV-05:02 -7.2
December 0.220026E+09 2601.43 26-DEC-05:03 -25.9
         
Annual Sum or Average 0.800563E+09      
Minimum of Months 0.00 0.00   -25.9
Maximum of Months 0.303698E+09 2629.60   17.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.168377E+09 366.91 17-JAN-05:01 -5.6
February 0.113293E+09 370.10 21-FEB-06:01 2.80
March 85190386.99 363.53 27-MAR-04:01 -3.4
April 35068981.91 366.78 08-APR-05:01 3.30
May 10973486.55 365.98 15-MAY-05:01 6.87
June 3772475.20 355.57 12-JUN-05:01 11.78
July 2317969.29 362.52 10-JUL-05:01 9.68
August 2500933.85 357.81 19-AUG-05:01 4.60
September 6856053.69 366.13 05-SEP-05:01 5.60
October 26288539.22 369.20 10-OCT-05:01 3.40
November 63166599.82 370.15 20-NOV-06:01 4.90
December 0.147982E+09 362.03 11-DEC-05:03 -24.6
         
Annual Sum or Average 0.665788E+09      
Minimum of Months 2317969.29 355.57   -24.6
Maximum of Months 0.168377E+09 370.15   11.78



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.860113E+09 11079.17 17-JAN-07:01 -7.4
February 0.421642E+09 11999.64 21-FEB-06:01 2.80
March 0.225327E+09 11052.83 13-MAR-06:01 -13.3
April 60732265.35 11980.45 08-APR-05:01 3.30
May 38517697.83 11981.13 06-MAY-05:01 3.40
June 33385777.34 11944.31 17-JUN-05:01 5.55
July 32656983.98 11901.19 10-JUL-05:01 9.68
August 37399137.14 11968.70 19-AUG-05:01 4.60
September 37793481.88 11966.09 23-SEP-05:01 4.90
October 71840258.82 11990.97 16-OCT-05:01 5.60
November 0.225463E+09 12025.82 20-NOV-06:01 4.90
December 0.785175E+09 11075.65 04-DEC-07:01 -9.4
         
Annual Sum or Average 0.283005E+10      
Minimum of Months 32656983.98 11052.83   -13.3
Maximum of Months 0.860113E+09 12025.82   9.68



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 48697700.72 5141.48 17-JAN-07:01 -7.4
February 26146575.69 5587.45 21-FEB-06:01 2.80
March 20252721.21 5134.90 27-MAR-06:01 -3.4
April 15650090.22 5509.36 08-APR-05:01 3.30
May 15035396.66 5506.25 30-MAY-05:01 10.60
June 14250053.80 5442.32 17-JUN-05:01 5.55
July 14523879.99 5498.78 10-JUL-05:01 9.68
August 15895752.38 5473.57 19-AUG-05:01 4.60
September 14123329.54 5518.80 05-SEP-05:01 5.60
October 15284845.51 5583.19 10-OCT-05:01 3.40
November 20109875.99 5598.94 20-NOV-06:01 4.90
December 42245765.52 5142.63 06-DEC-07:01 -2.1
         
Annual Sum or Average 0.262216E+09      
Minimum of Months 14123329.54 5134.90   -7.4
Maximum of Months 48697700.72 5598.94   10.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 18452791.76 590.92 17-JAN-05:01 -5.6
February 9913024.97 598.26 21-FEB-06:01 2.80
March 4994270.62 551.62 27-MAR-06:01 -3.4
April 2181842.65 575.22 03-APR-04:01 -5.4
May 1431601.99 575.01 30-MAY-05:01 10.60
June 1382375.21 555.34 12-JUN-05:01 11.78
July 1534261.00 569.54 10-JUL-05:01 9.68
August 1398334.06 547.03 21-AUG-05:01 12.70
September 1268487.37 575.16 05-SEP-05:01 5.60
October 2415194.91 593.62 10-OCT-05:01 3.40
November 5550936.07 592.22 20-NOV-06:01 4.90
December 13447556.63 552.48 04-DEC-07:01 -9.4
         
Annual Sum or Average 63970677.24      
Minimum of Months 1268487.37 547.03   -9.4
Maximum of Months 18452791.76 598.26   12.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 72445222.70 599.31 17-JAN-05:01 -5.6
February 41484061.06 605.37 21-FEB-06:01 2.80
March 24151403.26 591.28 27-MAR-04:01 -3.4
April 10263218.13 597.50 03-APR-04:01 -5.4
May 5179144.96 591.44 30-MAY-05:01 10.60
June 3529129.93 573.19 12-JUN-05:01 11.78
July 3980438.89 587.15 10-JUL-05:01 9.68
August 3856222.13 562.90 21-AUG-05:01 12.70
September 4733627.22 592.23 05-SEP-05:01 5.60
October 9956584.22 604.45 10-OCT-05:01 3.40
November 23346102.10 606.18 20-NOV-06:01 4.90
December 58569596.72 575.41 04-DEC-06:01 -9.4
         
Annual Sum or Average 0.261495E+09      
Minimum of Months 3529129.93 562.90   -9.4
Maximum of Months 72445222.70 606.18   12.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 63390803.60 274.30 17-JAN-05:01 -5.6
February 32302327.94 275.91 21-FEB-06:01 2.80
March 14993070.23 270.73 06-MAR-05:03 -18.4
April 3493272.92 271.03 03-APR-04:01 -5.4
May 571093.15 261.28 01-MAY-05:01 -3.4
June 109682.60 251.86 12-JUN-06:01 12.38
July 133695.19 250.88 10-JUL-06:01 11.75
August 87301.50 249.75 21-AUG-06:01 12.77
September 327688.24 255.10 05-SEP-06:01 6.05
October 3493774.60 270.94 10-OCT-05:01 3.40
November 13994670.81 272.37 06-NOV-05:01 -3.9
December 51790481.80 271.82 26-DEC-05:03 -25.9
         
Annual Sum or Average 0.184688E+09      
Minimum of Months 87301.50 249.75   -25.9
Maximum of Months 63390803.60 275.91   12.77



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 25878583.14 4035.79 17-JAN-07:01 -7.4
February 14754009.00 4387.27 21-FEB-06:01 2.80
March 12462392.78 4033.20 27-MAR-06:01 -3.4
April 9274647.07 4246.21 24-APR-05:01 4.40
May 8432434.24 4273.80 30-MAY-05:01 10.60
June 8258884.85 4148.06 12-JUN-05:01 11.78
July 9352978.13 4257.24 10-JUL-05:01 9.68
August 10102180.56 4102.07 28-AUG-05:01 13.90
September 7556645.72 4275.02 05-SEP-05:01 5.60
October 8893031.08 4374.56 10-OCT-05:01 3.40
November 12517317.46 4386.20 20-NOV-06:01 4.90
December 20782824.00 4036.97 05-DEC-07:01 -1.1
         
Annual Sum or Average 0.148266E+09      
Minimum of Months 7556645.72 4033.20   -7.4
Maximum of Months 25878583.14 4387.27   13.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.915236E+09 6556.26 17-JAN-05:01 -5.6
February 0.403491E+09 6476.78 24-FEB-05:03 -21.9
March 0.186791E+09 6459.58 06-MAR-05:03 -18.4
April 29291365.22 6461.38 03-APR-04:01 -5.4
May 5153060.68 6143.27 01-MAY-05:01 -3.4
June 1523821.19 4770.64 12-JUN-06:01 12.38
July 810742.83 3644.86 10-JUL-06:01 11.75
August 922880.42 5697.58 19-AUG-06:03 6.23
September 2982680.03 5993.68 23-SEP-06:03 4.32
October 35200653.77 6438.09 30-OCT-04:03 -10.0
November 0.159371E+09 6536.94 06-NOV-05:01 -3.9
December 0.759129E+09 6508.94 26-DEC-05:03 -25.9
         
Annual Sum or Average 0.249990E+10      
Minimum of Months 810742.83 3644.86   -25.9
Maximum of Months 0.915236E+09 6556.26   12.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.890528E+09 4238.47 17-JAN-05:01 -5.6
February 0.417792E+09 4214.30 21-FEB-06:01 2.80
March 0.213865E+09 4180.59 06-MAR-05:03 -18.4
April 33360443.10 4229.15 10-APR-04:01 -2.8
May 3720456.45 4032.85 01-MAY-05:01 -3.4
June 542646.99 2643.73 12-JUN-06:01 12.38
July 18891.66 314.86 10-JUL-06:01 11.75
August 542624.93 3617.50 19-AUG-06:03 6.23
September 1143440.98 3045.83 23-SEP-06:03 4.32
October 33647305.19 4171.94 30-OCT-04:03 -10.0
November 0.184946E+09 4234.66 06-NOV-05:01 -3.9
December 0.769340E+09 4200.58 26-DEC-05:03 -25.9
         
Annual Sum or Average 0.254945E+10      
Minimum of Months 18891.66 314.86   -25.9
Maximum of Months 0.890528E+09 4238.47   12.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.148231E+09 457.54 17-JAN-05:01 -5.6
February 82573766.97 459.39 21-FEB-06:01 2.80
March 42578757.67 453.14 06-MAR-05:03 -18.4
April 13306986.32 451.26 03-APR-04:01 -5.4
May 3652065.74 440.72 30-MAY-05:01 10.60
June 1689249.86 434.32 12-JUN-05:01 11.78
July 1962200.09 434.03 31-JUL-05:01 14.68
August 1786729.15 427.13 28-AUG-06:01 14.08
September 3080973.25 437.85 05-SEP-05:01 5.60
October 12710210.66 452.25 10-OCT-05:01 3.40
November 42501293.97 454.72 27-NOV-05:02 -7.2
December 0.118683E+09 453.91 26-DEC-05:03 -25.9
         
Annual Sum or Average 0.472756E+09      
Minimum of Months 1689249.86 427.13   -25.9
Maximum of Months 0.148231E+09 459.39   14.68



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FLOOR 3 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.488103E+09 2523.17 03-JAN-05:03 -10.1
February 0.204782E+09 2518.67 03-FEB-05:03 -11.2
March 76596673.36 2522.22 14-MAR-04:03 -12.9
April 5147930.25 2489.96 10-APR-04:01 -2.8
May 26709.84 445.16 01-MAY-05:01 -3.4
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 148827.85 992.19 23-SEP-06:03 4.32
October 7911905.44 2510.24 30-OCT-04:03 -10.0
November 73882584.48 2512.86 24-NOV-05:03 -10.6
December 0.422548E+09 2517.36 15-DEC-05:03 -14.1
         
Annual Sum or Average 0.127915E+10      
Minimum of Months 0.00 0.00   -14.1
Maximum of Months 0.488103E+09 2523.17   17.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: NE STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.306690E+10 2022.41 09-JAN-05:03 -33.0
February 0.224548E+10 2018.15 14-FEB-05:03 -32.1
March 0.194318E+10 2009.50 07-MAR-05:03 -23.6
April 0.877812E+09 2016.39 24-APR-05:01 4.40
May 0.165958E+09 2015.09 30-MAY-05:01 10.60
June 21921800.16 1972.16 12-JUN-05:01 11.78
July 6051070.68 1953.25 10-JUL-05:01 9.68
August 8513525.61 1975.50 19-AUG-05:01 4.60
September 73868172.08 1981.95 23-SEP-05:01 4.90
October 0.392171E+09 2011.39 18-OCT-05:01 2.12
November 0.117461E+10 2011.27 20-NOV-06:01 4.90
December 0.271840E+10 2013.24 20-DEC-05:03 -28.7
         
Annual Sum or Average 0.126949E+11      
Minimum of Months 6051070.68 1953.25   -33.0
Maximum of Months 0.306690E+10 2022.41   11.78



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: NW ELEVATOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.155510E+10 1321.94 09-JAN-05:03 -33.0
February 0.111115E+10 1323.00 21-FEB-06:01 2.80
March 0.968209E+09 1317.79 27-MAR-04:01 -3.4
April 0.472118E+09 1322.44 26-APR-05:01 2.02
May 0.117668E+09 1326.03 30-MAY-05:01 10.60
June 23934413.48 1289.63 12-JUN-05:01 11.78
July 3692440.69 1249.24 10-JUL-05:01 9.68
August 2987517.29 1201.88 19-AUG-06:03 6.23
September 26109683.01 1252.03 25-SEP-05:01 8.03
October 0.165488E+09 1321.87 16-OCT-05:01 5.60
November 0.494732E+09 1321.54 20-NOV-06:01 4.90
December 0.130835E+10 1316.58 26-DEC-05:03 -25.9
         
Annual Sum or Average 0.624954E+10      
Minimum of Months 2987517.29 1201.88   -33.0
Maximum of Months 0.155510E+10 1326.03   11.78



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: NW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.323604E+10 2076.34 09-JAN-05:03 -33.0
February 0.237917E+10 2070.36 14-FEB-05:03 -32.1
March 0.207308E+10 2062.48 07-MAR-05:03 -23.6
April 0.949566E+09 2069.10 24-APR-05:01 4.40
May 0.175059E+09 2068.43 30-MAY-05:01 10.60
June 19564180.08 2013.79 12-JUN-05:01 11.78
July 3770596.42 1973.55 10-JUL-05:01 9.68
August 5597600.03 1988.80 19-AUG-05:01 4.60
September 62458959.84 1997.98 05-SEP-05:01 5.60
October 0.372257E+09 2064.20 16-OCT-05:01 5.60
November 0.117566E+10 2064.30 20-NOV-06:01 4.90
December 0.281256E+10 2065.05 20-DEC-05:03 -28.7
         
Annual Sum or Average 0.132648E+11      
Minimum of Months 3770596.42 1973.55   -33.0
Maximum of Months 0.323604E+10 2076.34   11.78



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: SW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100545E+10 1008.17 09-JAN-05:03 -33.0
February 0.669606E+09 1007.03 21-FEB-06:01 2.80
March 0.569788E+09 1001.88 27-MAR-04:01 -3.4
April 0.262628E+09 1007.10 26-APR-05:01 2.02
May 57554604.29 1009.91 30-MAY-05:01 10.60
June 9246857.31 974.39 12-JUN-05:01 11.78
July 1097045.03 932.13 10-JUL-06:01 11.75
August 1315523.75 913.76 19-AUG-06:03 6.23
September 8296213.05 922.44 21-SEP-06:01 5.10
October 89644728.20 1006.94 16-OCT-05:01 5.60
November 0.311532E+09 1006.76 20-NOV-06:01 4.90
December 0.871998E+09 1003.64 26-DEC-05:03 -25.9
         
Annual Sum or Average 0.385816E+10      
Minimum of Months 1097045.03 913.76   -33.0
Maximum of Months 0.100545E+10 1009.91   11.78



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.171896E+09 136.08 02-JAN-07:10 0.342612E+09 213.96 02-JAN-06:10
February 0.156301E+09 136.08 01-FEB-07:10 0.310415E+09 213.96 01-FEB-06:10
March 0.184797E+09 136.08 01-MAR-07:10 0.354012E+09 213.96 01-MAR-06:10
April 0.166698E+09 136.08 03-APR-06:10 0.331982E+09 213.96 03-APR-05:10
May 0.178346E+09 136.08 01-MAY-06:10 0.348312E+09 213.96 01-MAY-05:10
June 0.177448E+09 136.08 01-JUN-06:10 0.341379E+09 213.96 01-JUN-05:10
July 0.167596E+09 136.08 03-JUL-06:10 0.338914E+09 213.96 03-JUL-05:10
August 0.184797E+09 136.08 01-AUG-06:10 0.354012E+09 213.96 01-AUG-05:10
September 0.166698E+09 136.08 01-SEP-06:10 0.331982E+09 213.96 01-SEP-05:10
October 0.171896E+09 136.08 02-OCT-06:10 0.342612E+09 213.96 02-OCT-05:10
November 0.168848E+09 136.08 01-NOV-06:10 0.333677E+09 213.96 01-NOV-05:10
December 0.167596E+09 136.08 01-DEC-07:10 0.338914E+09 213.96 01-DEC-06:10
             
Annual Sum or Average 0.206292E+10     0.406882E+10    
Minimum of Months 0.156301E+09 136.08   0.310415E+09 213.96  
Maximum of Months 0.184797E+09 136.08   0.354012E+09 213.96  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 16240630.93 12.86 02-JAN-07:10 8911442.72 5.57 02-JAN-06:10
February 14767248.81 12.86 01-FEB-07:10 8073991.50 5.57 01-FEB-06:10
March 17459449.66 12.86 01-MAR-07:10 9207956.55 5.57 01-MAR-06:10
April 15749503.56 12.86 03-APR-06:10 8634963.61 5.57 03-APR-05:10
May 16850040.30 12.86 01-MAY-06:10 9059699.64 5.57 01-MAY-05:10
June 16765185.83 12.86 01-JUN-06:10 8879387.17 5.57 01-JUN-05:10
July 15834358.03 12.86 03-JUL-06:10 8815276.07 5.57 03-JUL-05:10
August 17459449.66 12.86 01-AUG-06:10 9207956.55 5.57 01-AUG-05:10
September 15749503.56 12.86 01-SEP-06:10 8634963.61 5.57 01-SEP-05:10
October 16240630.93 12.86 02-OCT-06:10 8911442.72 5.57 02-OCT-05:10
November 15952640.01 12.86 01-NOV-06:10 8679039.99 5.57 01-NOV-05:10
December 15834358.03 12.86 01-DEC-07:10 8815276.07 5.57 01-DEC-06:10
             
Annual Sum or Average 0.194903E+09     0.105831E+09    
Minimum of Months 14767248.81 12.86   8073991.50 5.57  
Maximum of Months 17459449.66 12.86   9207956.55 5.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 CAFE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.190996E+09 151.20 02-JAN-07:10 0.665880E+09 415.84 02-JAN-06:10
February 0.173668E+09 151.20 01-FEB-07:10 0.603304E+09 415.84 01-FEB-06:10
March 0.205330E+09 151.20 01-MAR-07:10 0.688036E+09 415.84 01-MAR-06:10
April 0.185220E+09 151.20 03-APR-06:10 0.645221E+09 415.84 03-APR-05:10
May 0.198163E+09 151.20 01-MAY-06:10 0.676958E+09 415.84 01-MAY-05:10
June 0.197165E+09 151.20 01-JUN-06:10 0.663485E+09 415.84 01-JUN-05:10
July 0.186218E+09 151.20 03-JUL-06:10 0.658694E+09 415.84 03-JUL-05:10
August 0.205330E+09 151.20 01-AUG-06:10 0.688036E+09 415.84 01-AUG-05:10
September 0.185220E+09 151.20 01-SEP-06:10 0.645221E+09 415.84 01-SEP-05:10
October 0.190996E+09 151.20 02-OCT-06:10 0.665880E+09 415.84 02-OCT-05:10
November 0.187609E+09 151.20 01-NOV-06:10 0.648514E+09 415.84 01-NOV-05:10
December 0.186218E+09 151.20 01-DEC-07:10 0.658694E+09 415.84 01-DEC-06:10
             
Annual Sum or Average 0.229213E+10     0.790792E+10    
Minimum of Months 0.173668E+09 151.20   0.603304E+09 415.84  
Maximum of Months 0.205330E+09 151.20   0.688036E+09 415.84  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 CLEAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.200546E+09 158.76 02-JAN-07:10 0.399714E+09 249.62 02-JAN-06:10
February 0.182352E+09 158.76 01-FEB-07:10 0.362151E+09 249.62 01-FEB-06:10
March 0.215596E+09 158.76 01-MAR-07:10 0.413013E+09 249.62 01-MAR-06:10
April 0.194481E+09 158.76 03-APR-06:10 0.387312E+09 249.62 03-APR-05:10
May 0.208071E+09 158.76 01-MAY-06:10 0.406364E+09 249.62 01-MAY-05:10
June 0.207023E+09 158.76 01-JUN-06:10 0.398276E+09 249.62 01-JUN-05:10
July 0.195529E+09 158.76 03-JUL-06:10 0.395400E+09 249.62 03-JUL-05:10
August 0.215596E+09 158.76 01-AUG-06:10 0.413013E+09 249.62 01-AUG-05:10
September 0.194481E+09 158.76 01-SEP-06:10 0.387312E+09 249.62 01-SEP-05:10
October 0.200546E+09 158.76 02-OCT-06:10 0.399714E+09 249.62 02-OCT-05:10
November 0.196989E+09 158.76 01-NOV-06:10 0.389289E+09 249.62 01-NOV-05:10
December 0.195529E+09 158.76 01-DEC-07:10 0.395400E+09 249.62 01-DEC-06:10
             
Annual Sum or Average 0.240674E+10     0.474696E+10    
Minimum of Months 0.182352E+09 158.76   0.362151E+09 249.62  
Maximum of Months 0.215596E+09 158.76   0.413013E+09 249.62  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.262619E+09 207.90 02-JAN-07:10 0.523434E+09 326.89 02-JAN-06:10
February 0.238794E+09 207.90 01-FEB-07:10 0.474245E+09 326.89 01-FEB-06:10
March 0.282328E+09 207.90 01-MAR-07:10 0.540851E+09 326.89 01-MAR-06:10
April 0.254677E+09 207.90 03-APR-06:10 0.507195E+09 326.89 03-APR-05:10
May 0.272474E+09 207.90 01-MAY-06:10 0.532143E+09 326.89 01-MAY-05:10
June 0.271102E+09 207.90 01-JUN-06:10 0.521552E+09 326.89 01-JUN-05:10
July 0.256050E+09 207.90 03-JUL-06:10 0.517786E+09 326.89 03-JUL-05:10
August 0.282328E+09 207.90 01-AUG-06:10 0.540851E+09 326.89 01-AUG-05:10
September 0.254677E+09 207.90 01-SEP-06:10 0.507195E+09 326.89 01-SEP-05:10
October 0.262619E+09 207.90 02-OCT-06:10 0.523434E+09 326.89 02-OCT-05:10
November 0.257962E+09 207.90 01-NOV-06:10 0.509784E+09 326.89 01-NOV-05:10
December 0.256050E+09 207.90 01-DEC-07:10 0.517786E+09 326.89 01-DEC-06:10
             
Annual Sum or Average 0.315168E+10     0.621626E+10    
Minimum of Months 0.238794E+09 207.90   0.474245E+09 326.89  
Maximum of Months 0.282328E+09 207.90   0.540851E+09 326.89  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 91279739.78 72.09 02-JAN-07:10 0.219815E+09 137.27 02-JAN-06:10
February 82982498.28 72.09 01-FEB-07:10 0.199158E+09 137.27 01-FEB-06:10
March 98043141.13 72.09 01-MAR-07:10 0.227129E+09 137.27 01-MAR-06:10
April 88490345.08 72.09 03-APR-06:10 0.212995E+09 137.27 03-APR-05:10
May 94661440.45 72.09 01-MAY-06:10 0.223472E+09 137.27 01-MAY-05:10
June 94150160.40 72.09 01-JUN-06:10 0.219024E+09 137.27 01-JUN-05:10
July 89001625.13 72.09 03-JUL-06:10 0.217443E+09 137.27 03-JUL-05:10
August 98043141.13 72.09 01-AUG-06:10 0.227129E+09 137.27 01-AUG-05:10
September 88490345.08 72.09 01-SEP-06:10 0.212995E+09 137.27 01-SEP-05:10
October 91279739.78 72.09 02-OCT-06:10 0.219815E+09 137.27 02-OCT-05:10
November 89664873.70 72.09 01-NOV-06:10 0.214082E+09 137.27 01-NOV-05:10
December 89001625.13 72.09 01-DEC-07:10 0.217443E+09 137.27 01-DEC-06:10
             
Annual Sum or Average 0.109509E+10     0.261050E+10    
Minimum of Months 82982498.28 72.09   0.199158E+09 137.27  
Maximum of Months 98043141.13 72.09   0.227129E+09 137.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 32599907.06 25.75 02-JAN-07:10 78505166.56 49.03 02-JAN-06:10
February 29636606.53 25.75 01-FEB-07:10 71127657.65 49.03 01-FEB-06:10
March 35015407.54 25.75 01-MAR-07:10 81117298.90 49.03 01-MAR-06:10
April 31603694.67 25.75 03-APR-06:10 76069529.65 49.03 03-APR-05:10
May 33807657.30 25.75 01-MAY-06:10 79811232.73 49.03 01-MAY-05:10
June 33625057.29 25.75 01-JUN-06:10 78222773.87 49.03 01-JUN-05:10
July 31786294.69 25.75 03-JUL-06:10 77657988.50 49.03 03-JUL-05:10
August 35015407.54 25.75 01-AUG-06:10 81117298.90 49.03 01-AUG-05:10
September 31603694.67 25.75 01-SEP-06:10 76069529.65 49.03 01-SEP-05:10
October 32599907.06 25.75 02-OCT-06:10 78505166.56 49.03 02-OCT-05:10
November 32023169.18 25.75 01-NOV-06:10 76457819.59 49.03 01-NOV-05:10
December 31786294.69 25.75 01-DEC-07:10 77657988.50 49.03 01-DEC-06:10
             
Annual Sum or Average 0.391103E+09     0.932319E+09    
Minimum of Months 29636606.53 25.75   71127657.65 49.03  
Maximum of Months 35015407.54 25.75   81117298.90 49.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.155980E+09 123.48 02-JAN-07:10 0.777149E+09 485.33 02-JAN-06:10
February 0.141829E+09 123.48 01-FEB-07:10 0.704116E+09 485.33 01-FEB-06:10
March 0.167686E+09 123.48 01-MAR-07:10 0.803007E+09 485.33 01-MAR-06:10
April 0.151263E+09 123.48 03-APR-06:10 0.753038E+09 485.33 03-APR-05:10
May 0.161833E+09 123.48 01-MAY-06:10 0.790078E+09 485.33 01-MAY-05:10
June 0.161018E+09 123.48 01-JUN-06:10 0.774353E+09 485.33 01-JUN-05:10
July 0.152078E+09 123.48 03-JUL-06:10 0.768762E+09 485.33 03-JUL-05:10
August 0.167686E+09 123.48 01-AUG-06:10 0.803007E+09 485.33 01-AUG-05:10
September 0.151263E+09 123.48 01-SEP-06:10 0.753038E+09 485.33 01-SEP-05:10
October 0.155980E+09 123.48 02-OCT-06:10 0.777149E+09 485.33 02-OCT-05:10
November 0.153214E+09 123.48 01-NOV-06:10 0.756881E+09 485.33 01-NOV-05:10
December 0.152078E+09 123.48 01-DEC-07:10 0.768762E+09 485.33 01-DEC-06:10
             
Annual Sum or Average 0.187191E+10     0.922934E+10    
Minimum of Months 0.141829E+09 123.48   0.704116E+09 485.33  
Maximum of Months 0.167686E+09 123.48   0.803007E+09 485.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.144839E+09 114.66 02-JAN-07:10 0.535737E+11 48352.84 02-JAN-09:09
February 0.131698E+09 114.66 01-FEB-07:10 0.485981E+11 48352.84 01-FEB-09:09
March 0.155708E+09 114.66 01-MAR-07:10 0.564605E+11 48352.84 01-MAR-09:09
April 0.140458E+09 114.66 03-APR-06:10 0.518536E+11 48352.84 03-APR-08:09
May 0.150273E+09 114.66 01-MAY-06:10 0.550171E+11 48352.84 01-MAY-08:09
June 0.149517E+09 114.66 01-JUN-06:10 0.543208E+11 48352.84 01-JUN-08:09
July 0.141215E+09 114.66 03-JUL-06:10 0.525499E+11 48352.84 03-JUL-08:09
August 0.155708E+09 114.66 01-AUG-06:10 0.564605E+11 48352.84 01-AUG-08:09
September 0.140458E+09 114.66 01-SEP-06:10 0.518536E+11 48352.84 01-SEP-08:09
October 0.144839E+09 114.66 02-OCT-06:10 0.535737E+11 48352.84 02-OCT-08:09
November 0.142270E+09 114.66 01-NOV-06:10 0.524579E+11 48352.84 01-NOV-08:09
December 0.141215E+09 114.66 01-DEC-07:10 0.525499E+11 48352.84 01-DEC-09:09
             
Annual Sum or Average 0.173820E+10     0.639269E+12    
Minimum of Months 0.131698E+09 114.66   0.485981E+11 48352.84  
Maximum of Months 0.155708E+09 114.66   0.564605E+11 48352.84  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 39119888.48 30.90 02-JAN-07:10 94206295.03 58.83 02-JAN-06:10
February 35563927.84 30.90 01-FEB-07:10 85353275.40 58.83 01-FEB-06:10
March 42018489.05 30.90 01-MAR-07:10 97340857.01 58.83 01-MAR-06:10
April 37924433.61 30.90 03-APR-06:10 91283527.79 58.83 03-APR-05:10
May 40569188.76 30.90 01-MAY-06:10 95773576.02 58.83 01-MAY-05:10
June 40350068.74 30.90 01-JUN-06:10 93867423.47 58.83 01-JUN-05:10
July 38143553.63 30.90 03-JUL-06:10 93189680.34 58.83 03-JUL-05:10
August 42018489.05 30.90 01-AUG-06:10 97340857.01 58.83 01-AUG-05:10
September 37924433.61 30.90 01-SEP-06:10 91283527.79 58.83 01-SEP-05:10
October 39119888.48 30.90 02-OCT-06:10 94206295.03 58.83 02-OCT-05:10
November 38427803.01 30.90 01-NOV-06:10 91749476.19 58.83 01-NOV-05:10
December 38143553.63 30.90 01-DEC-07:10 93189680.34 58.83 01-DEC-06:10
             
Annual Sum or Average 0.469324E+09     0.111878E+10    
Minimum of Months 35563927.84 30.90   85353275.40 58.83  
Maximum of Months 42018489.05 30.90   97340857.01 58.83  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 IT HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 74541665.44 59.01 02-JAN-07:10 88907770.82 55.52 02-JAN-06:10
February 67779098.26 59.01 01-FEB-07:10 80552679.05 55.52 01-FEB-06:10
March 80135830.96 59.01 01-MAR-07:10 91866032.98 55.52 01-MAR-06:10
April 72287476.38 59.01 03-APR-06:10 86149391.24 55.52 03-APR-05:10
May 77338748.20 59.01 01-MAY-06:10 90386901.90 55.52 01-MAY-05:10
June 76949280.98 59.01 01-JUN-06:10 88587958.69 55.52 01-JUN-05:10
July 72676943.60 59.01 03-JUL-06:10 87948334.44 55.52 03-JUL-05:10
August 80135830.96 59.01 01-AUG-06:10 91866032.98 55.52 01-AUG-05:10
September 72287476.38 59.01 01-SEP-06:10 86149391.24 55.52 01-SEP-05:10
October 74541665.44 59.01 02-OCT-06:10 88907770.82 55.52 02-OCT-05:10
November 73219837.30 59.01 01-NOV-06:10 86589132.91 55.52 01-NOV-05:10
December 72676943.60 59.01 01-DEC-07:10 87948334.44 55.52 01-DEC-06:10
             
Annual Sum or Average 0.894571E+09     0.105586E+10    
Minimum of Months 67779098.26 59.01   80552679.05 55.52  
Maximum of Months 80135830.96 59.01   91866032.98 55.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 81137546.47 64.08 02-JAN-07:10 0.195391E+09 122.02 02-JAN-06:10
February 73762220.70 64.08 01-FEB-07:10 0.177029E+09 122.02 01-FEB-06:10
March 87149458.78 64.08 01-MAR-07:10 0.201892E+09 122.02 01-MAR-06:10
April 78658084.52 64.08 03-APR-06:10 0.189329E+09 122.02 03-APR-05:10
May 84143502.62 64.08 01-MAY-06:10 0.198642E+09 122.02 01-MAY-05:10
June 83689031.47 64.08 01-JUN-06:10 0.194688E+09 122.02 01-JUN-05:10
July 79112555.67 64.08 03-JUL-06:10 0.193282E+09 122.02 03-JUL-05:10
August 87149458.78 64.08 01-AUG-06:10 0.201892E+09 122.02 01-AUG-05:10
September 78658084.52 64.08 01-SEP-06:10 0.189329E+09 122.02 01-SEP-05:10
October 81137546.47 64.08 02-OCT-06:10 0.195391E+09 122.02 02-OCT-05:10
November 79702109.95 64.08 01-NOV-06:10 0.190295E+09 122.02 01-NOV-05:10
December 79112555.67 64.08 01-DEC-07:10 0.193282E+09 122.02 01-DEC-06:10
             
Annual Sum or Average 0.973412E+09     0.232044E+10    
Minimum of Months 73762220.70 64.08   0.177029E+09 122.02  
Maximum of Months 87149458.78 64.08   0.201892E+09 122.02  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 LOBBY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.564297E+09 446.72 02-JAN-07:10 0.108512E+10 677.66 02-JAN-06:10
February 0.513103E+09 446.72 01-FEB-07:10 0.983143E+09 677.66 01-FEB-06:10
March 0.606646E+09 446.72 01-MAR-07:10 0.112122E+10 677.66 01-MAR-06:10
April 0.547232E+09 446.72 03-APR-06:10 0.105145E+10 677.66 03-APR-05:10
May 0.585472E+09 446.72 01-MAY-06:10 0.110317E+10 677.66 01-MAY-05:10
June 0.582523E+09 446.72 01-JUN-06:10 0.108121E+10 677.66 01-JUN-05:10
July 0.550181E+09 446.72 03-JUL-06:10 0.107341E+10 677.66 03-JUL-05:10
August 0.606646E+09 446.72 01-AUG-06:10 0.112122E+10 677.66 01-AUG-05:10
September 0.547232E+09 446.72 01-SEP-06:10 0.105145E+10 677.66 01-SEP-05:10
October 0.564297E+09 446.72 02-OCT-06:10 0.108512E+10 677.66 02-OCT-05:10
November 0.554291E+09 446.72 01-NOV-06:10 0.105682E+10 677.66 01-NOV-05:10
December 0.550181E+09 446.72 01-DEC-07:10 0.107341E+10 677.66 01-DEC-06:10
             
Annual Sum or Average 0.677210E+10     0.128867E+11    
Minimum of Months 0.513103E+09 446.72   0.983143E+09 677.66  
Maximum of Months 0.606646E+09 446.72   0.112122E+10 677.66  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.127786E+09 101.16 02-JAN-07:10 0.152413E+09 95.18 02-JAN-06:10
February 0.116193E+09 101.16 01-FEB-07:10 0.138090E+09 95.18 01-FEB-06:10
March 0.137376E+09 101.16 01-MAR-07:10 0.157485E+09 95.18 01-MAR-06:10
April 0.123921E+09 101.16 03-APR-06:10 0.147685E+09 95.18 03-APR-05:10
May 0.132581E+09 101.16 01-MAY-06:10 0.154949E+09 95.18 01-MAY-05:10
June 0.131913E+09 101.16 01-JUN-06:10 0.151865E+09 95.18 01-JUN-05:10
July 0.124589E+09 101.16 03-JUL-06:10 0.150769E+09 95.18 03-JUL-05:10
August 0.137376E+09 101.16 01-AUG-06:10 0.157485E+09 95.18 01-AUG-05:10
September 0.123921E+09 101.16 01-SEP-06:10 0.147685E+09 95.18 01-SEP-05:10
October 0.127786E+09 101.16 02-OCT-06:10 0.152413E+09 95.18 02-OCT-05:10
November 0.125520E+09 101.16 01-NOV-06:10 0.148438E+09 95.18 01-NOV-05:10
December 0.124589E+09 101.16 01-DEC-07:10 0.150769E+09 95.18 01-DEC-06:10
             
Annual Sum or Average 0.153355E+10     0.181004E+10    
Minimum of Months 0.116193E+09 101.16   0.138090E+09 95.18  
Maximum of Months 0.137376E+09 101.16   0.157485E+09 95.18  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 25526594.02 20.21 02-JAN-07:10 34293067.55 21.42 02-JAN-06:10
February 23210770.97 20.21 01-FEB-07:10 31070382.70 21.42 01-FEB-06:10
March 27442301.04 20.21 01-MAR-07:10 35434113.87 21.42 01-MAR-06:10
April 24754653.00 20.21 03-APR-06:10 33229118.96 21.42 03-APR-05:10
May 26484447.53 20.21 01-MAY-06:10 34863590.71 21.42 01-MAY-05:10
June 26351075.52 20.21 01-JUN-06:10 34169711.20 21.42 01-JUN-05:10
July 24888025.01 20.21 03-JUL-06:10 33922998.48 21.42 03-JUL-05:10
August 27442301.04 20.21 01-AUG-06:10 35434113.87 21.42 01-AUG-05:10
September 24754653.00 20.21 01-SEP-06:10 33229118.96 21.42 01-SEP-05:10
October 25526594.02 20.21 02-OCT-06:10 34293067.55 21.42 02-OCT-05:10
November 25073937.51 20.21 01-NOV-06:10 33398733.96 21.42 01-NOV-05:10
December 24888025.01 20.21 01-DEC-07:10 33922998.48 21.42 01-DEC-06:10
             
Annual Sum or Average 0.306343E+09     0.407261E+09    
Minimum of Months 23210770.97 20.21   31070382.70 21.42  
Maximum of Months 27442301.04 20.21   35434113.87 21.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.442701E+09 350.46 02-JAN-07:10 0.314012E+10 1961.01 02-JAN-06:10
February 0.402538E+09 350.46 01-FEB-07:10 0.284503E+10 1961.01 01-FEB-06:10
March 0.475925E+09 350.46 01-MAR-07:10 0.324460E+10 1961.01 01-MAR-06:10
April 0.429314E+09 350.46 03-APR-06:10 0.304270E+10 1961.01 03-APR-05:10
May 0.459313E+09 350.46 01-MAY-06:10 0.319236E+10 1961.01 01-MAY-05:10
June 0.457000E+09 350.46 01-JUN-06:10 0.312883E+10 1961.01 01-JUN-05:10
July 0.431627E+09 350.46 03-JUL-06:10 0.310623E+10 1961.01 03-JUL-05:10
August 0.475925E+09 350.46 01-AUG-06:10 0.324460E+10 1961.01 01-AUG-05:10
September 0.429314E+09 350.46 01-SEP-06:10 0.304270E+10 1961.01 01-SEP-05:10
October 0.442701E+09 350.46 02-OCT-06:10 0.314012E+10 1961.01 02-OCT-05:10
November 0.434851E+09 350.46 01-NOV-06:10 0.305823E+10 1961.01 01-NOV-05:10
December 0.431627E+09 350.46 01-DEC-07:10 0.310623E+10 1961.01 01-DEC-06:10
             
Annual Sum or Average 0.531283E+10     0.372918E+11    
Minimum of Months 0.402538E+09 350.46   0.284503E+10 1961.01  
Maximum of Months 0.475925E+09 350.46   0.324460E+10 1961.01  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.264090E+09 209.06 02-JAN-07:10 0.314987E+09 196.71 02-JAN-06:10
February 0.240132E+09 209.06 01-FEB-07:10 0.285387E+09 196.71 01-FEB-06:10
March 0.283910E+09 209.06 01-MAR-07:10 0.325468E+09 196.71 01-MAR-06:10
April 0.256104E+09 209.06 03-APR-06:10 0.305215E+09 196.71 03-APR-05:10
May 0.274000E+09 209.06 01-MAY-06:10 0.320228E+09 196.71 01-MAY-05:10
June 0.272620E+09 209.06 01-JUN-06:10 0.313854E+09 196.71 01-JUN-05:10
July 0.257484E+09 209.06 03-JUL-06:10 0.311588E+09 196.71 03-JUL-05:10
August 0.283910E+09 209.06 01-AUG-06:10 0.325468E+09 196.71 01-AUG-05:10
September 0.256104E+09 209.06 01-SEP-06:10 0.305215E+09 196.71 01-SEP-05:10
October 0.264090E+09 209.06 02-OCT-06:10 0.314987E+09 196.71 02-OCT-05:10
November 0.259407E+09 209.06 01-NOV-06:10 0.306773E+09 196.71 01-NOV-05:10
December 0.257484E+09 209.06 01-DEC-07:10 0.311588E+09 196.71 01-DEC-06:10
             
Annual Sum or Average 0.316934E+10     0.374076E+10    
Minimum of Months 0.240132E+09 209.06   0.285387E+09 196.71  
Maximum of Months 0.283910E+09 209.06   0.325468E+09 196.71  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.241473E+09 191.16 02-JAN-07:10 0.171279E+10 1069.64 02-JAN-06:10
February 0.219566E+09 191.16 01-FEB-07:10 0.155183E+10 1069.64 01-FEB-06:10
March 0.259595E+09 191.16 01-MAR-07:10 0.176978E+10 1069.64 01-MAR-06:10
April 0.234171E+09 191.16 03-APR-06:10 0.165965E+10 1069.64 03-APR-05:10
May 0.250534E+09 191.16 01-MAY-06:10 0.174129E+10 1069.64 01-MAY-05:10
June 0.249273E+09 191.16 01-JUN-06:10 0.170663E+10 1069.64 01-JUN-05:10
July 0.235433E+09 191.16 03-JUL-06:10 0.169431E+10 1069.64 03-JUL-05:10
August 0.259595E+09 191.16 01-AUG-06:10 0.176978E+10 1069.64 01-AUG-05:10
September 0.234171E+09 191.16 01-SEP-06:10 0.165965E+10 1069.64 01-SEP-05:10
October 0.241473E+09 191.16 02-OCT-06:10 0.171279E+10 1069.64 02-OCT-05:10
November 0.237191E+09 191.16 01-NOV-06:10 0.166812E+10 1069.64 01-NOV-05:10
December 0.235433E+09 191.16 01-DEC-07:10 0.169431E+10 1069.64 01-DEC-06:10
             
Annual Sum or Average 0.289791E+10     0.203410E+11    
Minimum of Months 0.219566E+09 191.16   0.155183E+10 1069.64  
Maximum of Months 0.259595E+09 191.16   0.176978E+10 1069.64  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 MED GAS

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 16240630.93 12.86 02-JAN-07:10 8911442.72 5.57 02-JAN-06:10
February 14767248.81 12.86 01-FEB-07:10 8073991.50 5.57 01-FEB-06:10
March 17459449.66 12.86 01-MAR-07:10 9207956.55 5.57 01-MAR-06:10
April 15749503.56 12.86 03-APR-06:10 8634963.61 5.57 03-APR-05:10
May 16850040.30 12.86 01-MAY-06:10 9059699.64 5.57 01-MAY-05:10
June 16765185.83 12.86 01-JUN-06:10 8879387.17 5.57 01-JUN-05:10
July 15834358.03 12.86 03-JUL-06:10 8815276.07 5.57 03-JUL-05:10
August 17459449.66 12.86 01-AUG-06:10 9207956.55 5.57 01-AUG-05:10
September 15749503.56 12.86 01-SEP-06:10 8634963.61 5.57 01-SEP-05:10
October 16240630.93 12.86 02-OCT-06:10 8911442.72 5.57 02-OCT-05:10
November 15952640.01 12.86 01-NOV-06:10 8679039.99 5.57 01-NOV-05:10
December 15834358.03 12.86 01-DEC-07:10 8815276.07 5.57 01-DEC-06:10
             
Annual Sum or Average 0.194903E+09     0.105831E+09    
Minimum of Months 14767248.81 12.86   8073991.50 5.57  
Maximum of Months 17459449.66 12.86   9207956.55 5.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.179536E+09 142.13 02-JAN-07:10 0.266451E+10 1663.99 02-JAN-06:10
February 0.163248E+09 142.13 01-FEB-07:10 0.241411E+10 1663.99 01-FEB-06:10
March 0.193010E+09 142.13 01-MAR-07:10 0.275317E+10 1663.99 01-MAR-06:10
April 0.174107E+09 142.13 03-APR-06:10 0.258184E+10 1663.99 03-APR-05:10
May 0.186273E+09 142.13 01-MAY-06:10 0.270884E+10 1663.99 01-MAY-05:10
June 0.185335E+09 142.13 01-JUN-06:10 0.265493E+10 1663.99 01-JUN-05:10
July 0.175045E+09 142.13 03-JUL-06:10 0.263576E+10 1663.99 03-JUL-05:10
August 0.193010E+09 142.13 01-AUG-06:10 0.275317E+10 1663.99 01-AUG-05:10
September 0.174107E+09 142.13 01-SEP-06:10 0.258184E+10 1663.99 01-SEP-05:10
October 0.179536E+09 142.13 02-OCT-06:10 0.266451E+10 1663.99 02-OCT-05:10
November 0.176352E+09 142.13 01-NOV-06:10 0.259502E+10 1663.99 01-NOV-05:10
December 0.175045E+09 142.13 01-DEC-07:10 0.263576E+10 1663.99 01-DEC-06:10
             
Annual Sum or Average 0.215460E+10     0.316435E+11    
Minimum of Months 0.163248E+09 142.13   0.241411E+10 1663.99  
Maximum of Months 0.193010E+09 142.13   0.275317E+10 1663.99  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 78268748.71 61.96 02-JAN-07:10 93353183.15 58.30 02-JAN-06:10
February 71168053.17 61.96 01-FEB-07:10 84580334.55 58.30 01-FEB-06:10
March 84142622.51 61.96 01-MAR-07:10 96459359.21 58.30 01-MAR-06:10
April 75901850.20 61.96 03-APR-06:10 90456883.85 58.30 03-APR-05:10
May 81205685.61 61.96 01-MAY-06:10 94906271.18 58.30 01-MAY-05:10
June 80796745.03 61.96 01-JUN-06:10 93017380.33 58.30 01-JUN-05:10
July 76310790.78 61.96 03-JUL-06:10 92345774.70 58.30 03-JUL-05:10
August 84142622.51 61.96 01-AUG-06:10 96459359.21 58.30 01-AUG-05:10
September 75901850.20 61.96 01-SEP-06:10 90456883.85 58.30 01-SEP-05:10
October 78268748.71 61.96 02-OCT-06:10 93353183.15 58.30 02-OCT-05:10
November 76880829.16 61.96 01-NOV-06:10 90918612.73 58.30 01-NOV-05:10
December 76310790.78 61.96 01-DEC-07:10 92345774.70 58.30 01-DEC-06:10
             
Annual Sum or Average 0.939299E+09     0.110865E+10    
Minimum of Months 71168053.17 61.96   84580334.55 58.30  
Maximum of Months 84142622.51 61.96   96459359.21 58.30  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.366767E+09 290.35 02-JAN-07:10 0.697848E+10 4358.06 02-JAN-06:10
February 0.333493E+09 290.35 01-FEB-07:10 0.632268E+10 4358.06 01-FEB-06:10
March 0.394291E+09 290.35 01-MAR-07:10 0.721068E+10 4358.06 01-MAR-06:10
April 0.355675E+09 290.35 03-APR-06:10 0.676197E+10 4358.06 03-APR-05:10
May 0.380529E+09 290.35 01-MAY-06:10 0.709458E+10 4358.06 01-MAY-05:10
June 0.378613E+09 290.35 01-JUN-06:10 0.695338E+10 4358.06 01-JUN-05:10
July 0.357592E+09 290.35 03-JUL-06:10 0.690317E+10 4358.06 03-JUL-05:10
August 0.394291E+09 290.35 01-AUG-06:10 0.721068E+10 4358.06 01-AUG-05:10
September 0.355675E+09 290.35 01-SEP-06:10 0.676197E+10 4358.06 01-SEP-05:10
October 0.366767E+09 290.35 02-OCT-06:10 0.697848E+10 4358.06 02-OCT-05:10
November 0.360263E+09 290.35 01-NOV-06:10 0.679649E+10 4358.06 01-NOV-05:10
December 0.357592E+09 290.35 01-DEC-07:10 0.690317E+10 4358.06 01-DEC-06:10
             
Annual Sum or Average 0.440155E+10     0.828757E+11    
Minimum of Months 0.333493E+09 290.35   0.632268E+10 4358.06  
Maximum of Months 0.394291E+09 290.35   0.721068E+10 4358.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 25526594.02 20.21 02-JAN-07:10 34293067.55 21.42 02-JAN-06:10
February 23210770.97 20.21 01-FEB-07:10 31070382.70 21.42 01-FEB-06:10
March 27442301.04 20.21 01-MAR-07:10 35434113.87 21.42 01-MAR-06:10
April 24754653.00 20.21 03-APR-06:10 33229118.96 21.42 03-APR-05:10
May 26484447.53 20.21 01-MAY-06:10 34863590.71 21.42 01-MAY-05:10
June 26351075.52 20.21 01-JUN-06:10 34169711.20 21.42 01-JUN-05:10
July 24888025.01 20.21 03-JUL-06:10 33922998.48 21.42 03-JUL-05:10
August 27442301.04 20.21 01-AUG-06:10 35434113.87 21.42 01-AUG-05:10
September 24754653.00 20.21 01-SEP-06:10 33229118.96 21.42 01-SEP-05:10
October 25526594.02 20.21 02-OCT-06:10 34293067.55 21.42 02-OCT-05:10
November 25073937.51 20.21 01-NOV-06:10 33398733.96 21.42 01-NOV-05:10
December 24888025.01 20.21 01-DEC-07:10 33922998.48 21.42 01-DEC-06:10
             
Annual Sum or Average 0.306343E+09     0.407261E+09    
Minimum of Months 23210770.97 20.21   31070382.70 21.42  
Maximum of Months 27442301.04 20.21   35434113.87 21.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.242087E+09 191.65 02-JAN-07:10 0.577364E+09 360.56 02-JAN-06:10
February 0.220125E+09 191.65 01-FEB-07:10 0.523106E+09 360.56 01-FEB-06:10
March 0.260255E+09 191.65 01-MAR-07:10 0.596575E+09 360.56 01-MAR-06:10
April 0.234766E+09 191.65 03-APR-06:10 0.559451E+09 360.56 03-APR-05:10
May 0.251171E+09 191.65 01-MAY-06:10 0.586969E+09 360.56 01-MAY-05:10
June 0.249906E+09 191.65 01-JUN-06:10 0.575287E+09 360.56 01-JUN-05:10
July 0.236031E+09 191.65 03-JUL-06:10 0.571133E+09 360.56 03-JUL-05:10
August 0.260255E+09 191.65 01-AUG-06:10 0.596575E+09 360.56 01-AUG-05:10
September 0.234766E+09 191.65 01-SEP-06:10 0.559451E+09 360.56 01-SEP-05:10
October 0.242087E+09 191.65 02-OCT-06:10 0.577364E+09 360.56 02-OCT-05:10
November 0.237794E+09 191.65 01-NOV-06:10 0.562307E+09 360.56 01-NOV-05:10
December 0.236031E+09 191.65 01-DEC-07:10 0.571133E+09 360.56 01-DEC-06:10
             
Annual Sum or Average 0.290528E+10     0.685672E+10    
Minimum of Months 0.220125E+09 191.65   0.523106E+09 360.56  
Maximum of Months 0.260255E+09 191.65   0.596575E+09 360.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.264090E+09 209.06 02-JAN-07:10 0.314987E+09 196.71 02-JAN-06:10
February 0.240132E+09 209.06 01-FEB-07:10 0.285387E+09 196.71 01-FEB-06:10
March 0.283910E+09 209.06 01-MAR-07:10 0.325468E+09 196.71 01-MAR-06:10
April 0.256104E+09 209.06 03-APR-06:10 0.305215E+09 196.71 03-APR-05:10
May 0.274000E+09 209.06 01-MAY-06:10 0.320228E+09 196.71 01-MAY-05:10
June 0.272620E+09 209.06 01-JUN-06:10 0.313854E+09 196.71 01-JUN-05:10
July 0.257484E+09 209.06 03-JUL-06:10 0.311588E+09 196.71 03-JUL-05:10
August 0.283910E+09 209.06 01-AUG-06:10 0.325468E+09 196.71 01-AUG-05:10
September 0.256104E+09 209.06 01-SEP-06:10 0.305215E+09 196.71 01-SEP-05:10
October 0.264090E+09 209.06 02-OCT-06:10 0.314987E+09 196.71 02-OCT-05:10
November 0.259407E+09 209.06 01-NOV-06:10 0.306773E+09 196.71 01-NOV-05:10
December 0.257484E+09 209.06 01-DEC-07:10 0.311588E+09 196.71 01-DEC-06:10
             
Annual Sum or Average 0.316934E+10     0.374076E+10    
Minimum of Months 0.240132E+09 209.06   0.285387E+09 196.71  
Maximum of Months 0.283910E+09 209.06   0.325468E+09 196.71  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 15660608.40 12.40 02-JAN-07:10 8593131.60 5.37 02-JAN-06:10
February 14239847.06 12.40 01-FEB-07:10 7785593.60 5.37 01-FEB-06:10
March 16835897.89 12.40 01-MAR-07:10 8879054.14 5.37 01-MAR-06:10
April 15187021.29 12.40 03-APR-06:10 8326528.14 5.37 03-APR-05:10
May 16248253.14 12.40 01-MAY-06:10 8736092.87 5.37 01-MAY-05:10
June 16166429.19 12.40 01-JUN-06:10 8562221.05 5.37 01-JUN-05:10
July 15268845.24 12.40 03-JUL-06:10 8500399.96 5.37 03-JUL-05:10
August 16835897.89 12.40 01-AUG-06:10 8879054.14 5.37 01-AUG-05:10
September 15187021.29 12.40 01-SEP-06:10 8326528.14 5.37 01-SEP-05:10
October 15660608.40 12.40 02-OCT-06:10 8593131.60 5.37 02-OCT-05:10
November 15382902.87 12.40 01-NOV-06:10 8369030.14 5.37 01-NOV-05:10
December 15268845.24 12.40 01-DEC-07:10 8500399.96 5.37 01-DEC-06:10
             
Annual Sum or Average 0.187942E+09     0.102051E+09    
Minimum of Months 14239847.06 12.40   7785593.60 5.37  
Maximum of Months 16835897.89 12.40   8879054.14 5.37  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.347169E+09 274.83 02-JAN-07:10 0.827978E+09 517.07 02-JAN-06:10
February 0.315673E+09 274.83 01-FEB-07:10 0.750169E+09 517.07 01-FEB-06:10
March 0.373223E+09 274.83 01-MAR-07:10 0.855528E+09 517.07 01-MAR-06:10
April 0.336670E+09 274.83 03-APR-06:10 0.802290E+09 517.07 03-APR-05:10
May 0.360196E+09 274.83 01-MAY-06:10 0.841753E+09 517.07 01-MAY-05:10
June 0.358382E+09 274.83 01-JUN-06:10 0.825000E+09 517.07 01-JUN-05:10
July 0.338484E+09 274.83 03-JUL-06:10 0.819043E+09 517.07 03-JUL-05:10
August 0.373223E+09 274.83 01-AUG-06:10 0.855528E+09 517.07 01-AUG-05:10
September 0.336670E+09 274.83 01-SEP-06:10 0.802290E+09 517.07 01-SEP-05:10
October 0.347169E+09 274.83 02-OCT-06:10 0.827978E+09 517.07 02-OCT-05:10
November 0.341013E+09 274.83 01-NOV-06:10 0.806385E+09 517.07 01-NOV-05:10
December 0.338484E+09 274.83 01-DEC-07:10 0.819043E+09 517.07 01-DEC-06:10
             
Annual Sum or Average 0.416636E+10     0.983299E+10    
Minimum of Months 0.315673E+09 274.83   0.750169E+09 517.07  
Maximum of Months 0.373223E+09 274.83   0.855528E+09 517.07  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 25526594.02 20.21 02-JAN-07:10 34293067.55 21.42 02-JAN-06:10
February 23210770.97 20.21 01-FEB-07:10 31070382.70 21.42 01-FEB-06:10
March 27442301.04 20.21 01-MAR-07:10 35434113.87 21.42 01-MAR-06:10
April 24754653.00 20.21 03-APR-06:10 33229118.96 21.42 03-APR-05:10
May 26484447.53 20.21 01-MAY-06:10 34863590.71 21.42 01-MAY-05:10
June 26351075.52 20.21 01-JUN-06:10 34169711.20 21.42 01-JUN-05:10
July 24888025.01 20.21 03-JUL-06:10 33922998.48 21.42 03-JUL-05:10
August 27442301.04 20.21 01-AUG-06:10 35434113.87 21.42 01-AUG-05:10
September 24754653.00 20.21 01-SEP-06:10 33229118.96 21.42 01-SEP-05:10
October 25526594.02 20.21 02-OCT-06:10 34293067.55 21.42 02-OCT-05:10
November 25073937.51 20.21 01-NOV-06:10 33398733.96 21.42 01-NOV-05:10
December 24888025.01 20.21 01-DEC-07:10 33922998.48 21.42 01-DEC-06:10
             
Annual Sum or Average 0.306343E+09     0.407261E+09    
Minimum of Months 23210770.97 20.21   31070382.70 21.42  
Maximum of Months 27442301.04 20.21   35434113.87 21.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.349906E+09 276.35 02-JAN-07:10 0.842623E+09 526.22 02-JAN-06:10
February 0.318100E+09 276.35 01-FEB-07:10 0.763438E+09 526.22 01-FEB-06:10
March 0.375832E+09 276.35 01-MAR-07:10 0.870660E+09 526.22 01-MAR-06:10
April 0.339213E+09 276.35 03-APR-06:10 0.816480E+09 526.22 03-APR-05:10
May 0.362869E+09 276.35 01-MAY-06:10 0.856641E+09 526.22 01-MAY-05:10
June 0.360909E+09 276.35 01-JUN-06:10 0.839592E+09 526.22 01-JUN-05:10
July 0.341173E+09 276.35 03-JUL-06:10 0.833530E+09 526.22 03-JUL-05:10
August 0.375832E+09 276.35 01-AUG-06:10 0.870660E+09 526.22 01-AUG-05:10
September 0.339213E+09 276.35 01-SEP-06:10 0.816480E+09 526.22 01-SEP-05:10
October 0.349906E+09 276.35 02-OCT-06:10 0.842623E+09 526.22 02-OCT-05:10
November 0.343715E+09 276.35 01-NOV-06:10 0.820648E+09 526.22 01-NOV-05:10
December 0.341173E+09 276.35 01-DEC-07:10 0.833530E+09 526.22 01-DEC-06:10
             
Annual Sum or Average 0.419784E+10     0.100069E+11    
Minimum of Months 0.318100E+09 276.35   0.763438E+09 526.22  
Maximum of Months 0.375832E+09 276.35   0.870660E+09 526.22  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.118190E+10 935.64 02-JAN-07:10 0.291854E+10 1822.63 02-JAN-06:10
February 0.107468E+10 935.64 01-FEB-07:10 0.264427E+10 1822.63 01-FEB-06:10
March 0.127060E+10 935.64 01-MAR-07:10 0.301565E+10 1822.63 01-MAR-06:10
April 0.114616E+10 935.64 03-APR-06:10 0.282800E+10 1822.63 03-APR-05:10
May 0.122625E+10 935.64 01-MAY-06:10 0.296710E+10 1822.63 01-MAY-05:10
June 0.122007E+10 935.64 01-JUN-06:10 0.290805E+10 1822.63 01-JUN-05:10
July 0.115233E+10 935.64 03-JUL-06:10 0.288705E+10 1822.63 03-JUL-05:10
August 0.127060E+10 935.64 01-AUG-06:10 0.301565E+10 1822.63 01-AUG-05:10
September 0.114616E+10 935.64 01-SEP-06:10 0.282800E+10 1822.63 01-SEP-05:10
October 0.118190E+10 935.64 02-OCT-06:10 0.291854E+10 1822.63 02-OCT-05:10
November 0.116094E+10 935.64 01-NOV-06:10 0.284243E+10 1822.63 01-NOV-05:10
December 0.115233E+10 935.64 01-DEC-07:10 0.288705E+10 1822.63 01-DEC-06:10
             
Annual Sum or Average 0.141839E+11     0.346603E+11    
Minimum of Months 0.107468E+10 935.64   0.264427E+10 1822.63  
Maximum of Months 0.127060E+10 935.64   0.301565E+10 1822.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.123329E+10 976.32 02-JAN-07:10 0.304544E+10 1901.88 02-JAN-06:10
February 0.112140E+10 976.32 01-FEB-07:10 0.275924E+10 1901.88 01-FEB-06:10
March 0.132584E+10 976.32 01-MAR-07:10 0.314677E+10 1901.88 01-MAR-06:10
April 0.119599E+10 976.32 03-APR-06:10 0.295095E+10 1901.88 03-APR-05:10
May 0.127956E+10 976.32 01-MAY-06:10 0.309610E+10 1901.88 01-MAY-05:10
June 0.127312E+10 976.32 01-JUN-06:10 0.303448E+10 1901.88 01-JUN-05:10
July 0.120244E+10 976.32 03-JUL-06:10 0.301257E+10 1901.88 03-JUL-05:10
August 0.132584E+10 976.32 01-AUG-06:10 0.314677E+10 1901.88 01-AUG-05:10
September 0.119599E+10 976.32 01-SEP-06:10 0.295095E+10 1901.88 01-SEP-05:10
October 0.123329E+10 976.32 02-OCT-06:10 0.304544E+10 1901.88 02-OCT-05:10
November 0.121142E+10 976.32 01-NOV-06:10 0.296601E+10 1901.88 01-NOV-05:10
December 0.120244E+10 976.32 01-DEC-07:10 0.301257E+10 1901.88 01-DEC-06:10
             
Annual Sum or Average 0.148006E+11     0.361673E+11    
Minimum of Months 0.112140E+10 976.32   0.275924E+10 1901.88  
Maximum of Months 0.132584E+10 976.32   0.314677E+10 1901.88  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.122301E+10 968.18 02-JAN-07:10 0.302006E+10 1886.03 02-JAN-06:10
February 0.111206E+10 968.18 01-FEB-07:10 0.273625E+10 1886.03 01-FEB-06:10
March 0.131479E+10 968.18 01-MAR-07:10 0.312055E+10 1886.03 01-MAR-06:10
April 0.118603E+10 968.18 03-APR-06:10 0.292636E+10 1886.03 03-APR-05:10
May 0.126890E+10 968.18 01-MAY-06:10 0.307030E+10 1886.03 01-MAY-05:10
June 0.126251E+10 968.18 01-JUN-06:10 0.300919E+10 1886.03 01-JUN-05:10
July 0.119242E+10 968.18 03-JUL-06:10 0.298747E+10 1886.03 03-JUL-05:10
August 0.131479E+10 968.18 01-AUG-06:10 0.312055E+10 1886.03 01-AUG-05:10
September 0.118603E+10 968.18 01-SEP-06:10 0.292636E+10 1886.03 01-SEP-05:10
October 0.122301E+10 968.18 02-OCT-06:10 0.302006E+10 1886.03 02-OCT-05:10
November 0.120132E+10 968.18 01-NOV-06:10 0.294130E+10 1886.03 01-NOV-05:10
December 0.119242E+10 968.18 01-DEC-07:10 0.298747E+10 1886.03 01-DEC-06:10
             
Annual Sum or Average 0.146773E+11     0.358659E+11    
Minimum of Months 0.111206E+10 968.18   0.273625E+10 1886.03  
Maximum of Months 0.131479E+10 968.18   0.312055E+10 1886.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 PACU

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.153479E+09 121.50 02-JAN-07:10 0.513838E+09 320.89 02-JAN-06:10
February 0.139555E+09 121.50 01-FEB-07:10 0.465550E+09 320.89 01-FEB-06:10
March 0.164997E+09 121.50 01-MAR-07:10 0.530935E+09 320.89 01-MAR-06:10
April 0.148837E+09 121.50 03-APR-06:10 0.497896E+09 320.89 03-APR-05:10
May 0.159238E+09 121.50 01-MAY-06:10 0.522386E+09 320.89 01-MAY-05:10
June 0.158436E+09 121.50 01-JUN-06:10 0.511990E+09 320.89 01-JUN-05:10
July 0.149639E+09 121.50 03-JUL-06:10 0.508293E+09 320.89 03-JUL-05:10
August 0.164997E+09 121.50 01-AUG-06:10 0.530935E+09 320.89 01-AUG-05:10
September 0.148837E+09 121.50 01-SEP-06:10 0.497896E+09 320.89 01-SEP-05:10
October 0.153479E+09 121.50 02-OCT-06:10 0.513838E+09 320.89 02-OCT-05:10
November 0.150757E+09 121.50 01-NOV-06:10 0.500437E+09 320.89 01-NOV-05:10
December 0.149639E+09 121.50 01-DEC-07:10 0.508293E+09 320.89 01-DEC-06:10
             
Annual Sum or Average 0.184189E+10     0.610229E+10    
Minimum of Months 0.139555E+09 121.50   0.465550E+09 320.89  
Maximum of Months 0.164997E+09 121.50   0.530935E+09 320.89  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.281129E+09 222.55 02-JAN-07:10 0.335309E+09 209.40 02-JAN-06:10
February 0.255624E+09 222.55 01-FEB-07:10 0.303799E+09 209.40 01-FEB-06:10
March 0.302227E+09 222.55 01-MAR-07:10 0.346466E+09 209.40 01-MAR-06:10
April 0.272627E+09 222.55 03-APR-06:10 0.324906E+09 209.40 03-APR-05:10
May 0.291678E+09 222.55 01-MAY-06:10 0.340888E+09 209.40 01-MAY-05:10
June 0.290209E+09 222.55 01-JUN-06:10 0.334103E+09 209.40 01-JUN-05:10
July 0.274096E+09 222.55 03-JUL-06:10 0.331691E+09 209.40 03-JUL-05:10
August 0.302227E+09 222.55 01-AUG-06:10 0.346466E+09 209.40 01-AUG-05:10
September 0.272627E+09 222.55 01-SEP-06:10 0.324906E+09 209.40 01-SEP-05:10
October 0.281129E+09 222.55 02-OCT-06:10 0.335309E+09 209.40 02-OCT-05:10
November 0.276143E+09 222.55 01-NOV-06:10 0.326565E+09 209.40 01-NOV-05:10
December 0.274096E+09 222.55 01-DEC-07:10 0.331691E+09 209.40 01-DEC-06:10
             
Annual Sum or Average 0.337381E+10     0.398210E+10    
Minimum of Months 0.255624E+09 222.55   0.303799E+09 209.40  
Maximum of Months 0.302227E+09 222.55   0.346466E+09 209.40  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.146112E+09 115.67 02-JAN-07:10 0.599570E+09 374.43 02-JAN-06:10
February 0.132856E+09 115.67 01-FEB-07:10 0.543226E+09 374.43 01-FEB-06:10
March 0.157077E+09 115.67 01-MAR-07:10 0.619520E+09 374.43 01-MAR-06:10
April 0.141693E+09 115.67 03-APR-06:10 0.580969E+09 374.43 03-APR-05:10
May 0.151594E+09 115.67 01-MAY-06:10 0.609545E+09 374.43 01-MAY-05:10
June 0.150831E+09 115.67 01-JUN-06:10 0.597414E+09 374.43 01-JUN-05:10
July 0.142457E+09 115.67 03-JUL-06:10 0.593100E+09 374.43 03-JUL-05:10
August 0.157077E+09 115.67 01-AUG-06:10 0.619520E+09 374.43 01-AUG-05:10
September 0.141693E+09 115.67 01-SEP-06:10 0.580969E+09 374.43 01-SEP-05:10
October 0.146112E+09 115.67 02-OCT-06:10 0.599570E+09 374.43 02-OCT-05:10
November 0.143521E+09 115.67 01-NOV-06:10 0.583934E+09 374.43 01-NOV-05:10
December 0.142457E+09 115.67 01-DEC-07:10 0.593100E+09 374.43 01-DEC-06:10
             
Annual Sum or Average 0.175348E+10     0.712044E+10    
Minimum of Months 0.132856E+09 115.67   0.543226E+09 374.43  
Maximum of Months 0.157077E+09 115.67   0.619520E+09 374.43  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.261300E+09 206.86 02-JAN-07:10 0.107225E+10 669.62 02-JAN-06:10
February 0.237595E+09 206.86 01-FEB-07:10 0.971483E+09 669.62 01-FEB-06:10
March 0.280910E+09 206.86 01-MAR-07:10 0.110792E+10 669.62 01-MAR-06:10
April 0.253399E+09 206.86 03-APR-06:10 0.103898E+10 669.62 03-APR-05:10
May 0.271105E+09 206.86 01-MAY-06:10 0.109009E+10 669.62 01-MAY-05:10
June 0.269740E+09 206.86 01-JUN-06:10 0.106839E+10 669.62 01-JUN-05:10
July 0.254764E+09 206.86 03-JUL-06:10 0.106068E+10 669.62 03-JUL-05:10
August 0.280910E+09 206.86 01-AUG-06:10 0.110792E+10 669.62 01-AUG-05:10
September 0.253399E+09 206.86 01-SEP-06:10 0.103898E+10 669.62 01-SEP-05:10
October 0.261300E+09 206.86 02-OCT-06:10 0.107225E+10 669.62 02-OCT-05:10
November 0.256667E+09 206.86 01-NOV-06:10 0.104428E+10 669.62 01-NOV-05:10
December 0.254764E+09 206.86 01-DEC-07:10 0.106068E+10 669.62 01-DEC-06:10
             
Annual Sum or Average 0.313585E+10     0.127339E+11    
Minimum of Months 0.237595E+09 206.86   0.971483E+09 669.62  
Maximum of Months 0.280910E+09 206.86   0.110792E+10 669.62  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 25526594.02 20.21 02-JAN-07:10 34293067.55 21.42 02-JAN-06:10
February 23210770.97 20.21 01-FEB-07:10 31070382.70 21.42 01-FEB-06:10
March 27442301.04 20.21 01-MAR-07:10 35434113.87 21.42 01-MAR-06:10
April 24754653.00 20.21 03-APR-06:10 33229118.96 21.42 03-APR-05:10
May 26484447.53 20.21 01-MAY-06:10 34863590.71 21.42 01-MAY-05:10
June 26351075.52 20.21 01-JUN-06:10 34169711.20 21.42 01-JUN-05:10
July 24888025.01 20.21 03-JUL-06:10 33922998.48 21.42 03-JUL-05:10
August 27442301.04 20.21 01-AUG-06:10 35434113.87 21.42 01-AUG-05:10
September 24754653.00 20.21 01-SEP-06:10 33229118.96 21.42 01-SEP-05:10
October 25526594.02 20.21 02-OCT-06:10 34293067.55 21.42 02-OCT-05:10
November 25073937.51 20.21 01-NOV-06:10 33398733.96 21.42 01-NOV-05:10
December 24888025.01 20.21 01-DEC-07:10 33922998.48 21.42 01-DEC-06:10
             
Annual Sum or Average 0.306343E+09     0.407261E+09    
Minimum of Months 23210770.97 20.21   31070382.70 21.42  
Maximum of Months 27442301.04 20.21   35434113.87 21.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.453615E+09 359.10 02-JAN-07:10 0.135596E+10 846.80 02-JAN-06:10
February 0.412462E+09 359.10 01-FEB-07:10 0.122854E+10 846.80 01-FEB-06:10
March 0.487658E+09 359.10 01-MAR-07:10 0.140108E+10 846.80 01-MAR-06:10
April 0.439897E+09 359.10 03-APR-06:10 0.131389E+10 846.80 03-APR-05:10
May 0.470636E+09 359.10 01-MAY-06:10 0.137852E+10 846.80 01-MAY-05:10
June 0.468266E+09 359.10 01-JUN-06:10 0.135108E+10 846.80 01-JUN-05:10
July 0.442268E+09 359.10 03-JUL-06:10 0.134133E+10 846.80 03-JUL-05:10
August 0.487658E+09 359.10 01-AUG-06:10 0.140108E+10 846.80 01-AUG-05:10
September 0.439897E+09 359.10 01-SEP-06:10 0.131389E+10 846.80 01-SEP-05:10
October 0.453615E+09 359.10 02-OCT-06:10 0.135596E+10 846.80 02-OCT-05:10
November 0.445571E+09 359.10 01-NOV-06:10 0.132060E+10 846.80 01-NOV-05:10
December 0.442268E+09 359.10 01-DEC-07:10 0.134133E+10 846.80 01-DEC-06:10
             
Annual Sum or Average 0.544381E+10     0.161033E+11    
Minimum of Months 0.412462E+09 359.10   0.122854E+10 846.80  
Maximum of Months 0.487658E+09 359.10   0.140108E+10 846.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.486084E+09 384.80 02-JAN-07:10 0.887981E+09 554.54 02-JAN-06:10
February 0.441986E+09 384.80 01-FEB-07:10 0.804533E+09 554.54 01-FEB-06:10
March 0.522564E+09 384.80 01-MAR-07:10 0.917527E+09 554.54 01-MAR-06:10
April 0.471385E+09 384.80 03-APR-06:10 0.860432E+09 554.54 03-APR-05:10
May 0.504324E+09 384.80 01-MAY-06:10 0.902754E+09 554.54 01-MAY-05:10
June 0.501784E+09 384.80 01-JUN-06:10 0.884787E+09 554.54 01-JUN-05:10
July 0.473925E+09 384.80 03-JUL-06:10 0.878399E+09 554.54 03-JUL-05:10
August 0.522564E+09 384.80 01-AUG-06:10 0.917527E+09 554.54 01-AUG-05:10
September 0.471385E+09 384.80 01-SEP-06:10 0.860432E+09 554.54 01-SEP-05:10
October 0.486084E+09 384.80 02-OCT-06:10 0.887981E+09 554.54 02-OCT-05:10
November 0.477465E+09 384.80 01-NOV-06:10 0.864824E+09 554.54 01-NOV-05:10
December 0.473925E+09 384.80 01-DEC-07:10 0.878399E+09 554.54 01-DEC-06:10
             
Annual Sum or Average 0.583347E+10     0.105456E+11    
Minimum of Months 0.441986E+09 384.80   0.804533E+09 554.54  
Maximum of Months 0.522564E+09 384.80   0.917527E+09 554.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 68152379.83 53.95 02-JAN-07:10 81287018.65 50.76 02-JAN-06:10
February 61969461.27 53.95 01-FEB-07:10 73648085.69 50.76 01-FEB-06:10
March 73267045.45 53.95 01-MAR-07:10 83991712.62 50.76 01-MAR-06:10
April 66091406.98 53.95 03-APR-06:10 78765074.28 50.76 03-APR-05:10
May 70709712.64 53.95 01-MAY-06:10 82639365.64 50.76 01-MAY-05:10
June 70353628.32 53.95 01-JUN-06:10 80994619.30 50.76 01-JUN-05:10
July 66447491.29 53.95 03-JUL-06:10 80409820.61 50.76 03-JUL-05:10
August 73267045.45 53.95 01-AUG-06:10 83991712.62 50.76 01-AUG-05:10
September 66091406.98 53.95 01-SEP-06:10 78765074.28 50.76 01-SEP-05:10
October 68152379.83 53.95 02-OCT-06:10 81287018.65 50.76 02-OCT-05:10
November 66943851.25 53.95 01-NOV-06:10 79167123.38 50.76 01-NOV-05:10
December 66447491.29 53.95 01-DEC-07:10 80409820.61 50.76 01-DEC-06:10
             
Annual Sum or Average 0.817893E+09     0.965356E+09    
Minimum of Months 61969461.27 53.95   73648085.69 50.76  
Maximum of Months 73267045.45 53.95   83991712.62 50.76  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.767394E+09 607.50 02-JAN-07:10 0.256919E+10 1604.46 02-JAN-06:10
February 0.697774E+09 607.50 01-FEB-07:10 0.232775E+10 1604.46 01-FEB-06:10
March 0.824985E+09 607.50 01-MAR-07:10 0.265468E+10 1604.46 01-MAR-06:10
April 0.744187E+09 607.50 03-APR-06:10 0.248948E+10 1604.46 03-APR-05:10
May 0.796189E+09 607.50 01-MAY-06:10 0.261193E+10 1604.46 01-MAY-05:10
June 0.792180E+09 607.50 01-JUN-06:10 0.255995E+10 1604.46 01-JUN-05:10
July 0.748197E+09 607.50 03-JUL-06:10 0.254146E+10 1604.46 03-JUL-05:10
August 0.824985E+09 607.50 01-AUG-06:10 0.265468E+10 1604.46 01-AUG-05:10
September 0.744187E+09 607.50 01-SEP-06:10 0.248948E+10 1604.46 01-SEP-05:10
October 0.767394E+09 607.50 02-OCT-06:10 0.256919E+10 1604.46 02-OCT-05:10
November 0.753786E+09 607.50 01-NOV-06:10 0.250219E+10 1604.46 01-NOV-05:10
December 0.748197E+09 607.50 01-DEC-07:10 0.254146E+10 1604.46 01-DEC-06:10
             
Annual Sum or Average 0.920946E+10     0.305114E+11    
Minimum of Months 0.697774E+09 607.50   0.232775E+10 1604.46  
Maximum of Months 0.824985E+09 607.50   0.265468E+10 1604.46  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 86208643.12 68.09 02-JAN-07:10 0.207603E+09 129.65 02-JAN-06:10
February 78372359.49 68.09 01-FEB-07:10 0.188093E+09 129.65 01-FEB-06:10
March 92596299.95 68.09 01-MAR-07:10 0.214510E+09 129.65 01-MAR-06:10
April 83574214.80 68.09 03-APR-06:10 0.201162E+09 129.65 03-APR-05:10
May 89402471.54 68.09 01-MAY-06:10 0.211057E+09 129.65 01-MAY-05:10
June 88919595.94 68.09 01-JUN-06:10 0.206856E+09 129.65 01-JUN-05:10
July 84057090.40 68.09 03-JUL-06:10 0.205362E+09 129.65 03-JUL-05:10
August 92596299.95 68.09 01-AUG-06:10 0.214510E+09 129.65 01-AUG-05:10
September 83574214.80 68.09 01-SEP-06:10 0.201162E+09 129.65 01-SEP-05:10
October 86208643.12 68.09 02-OCT-06:10 0.207603E+09 129.65 02-OCT-05:10
November 84683491.83 68.09 01-NOV-06:10 0.202189E+09 129.65 01-NOV-05:10
December 84057090.40 68.09 01-DEC-07:10 0.205362E+09 129.65 01-DEC-06:10
             
Annual Sum or Average 0.103425E+10     0.246547E+10    
Minimum of Months 78372359.49 68.09   0.188093E+09 129.65  
Maximum of Months 92596299.95 68.09   0.214510E+09 129.65  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 SCRUB

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 44724999.26 35.41 02-JAN-07:10 53344630.77 33.31 02-JAN-06:10
February 40667458.96 35.41 01-FEB-07:10 48331578.69 33.31 01-FEB-06:10
March 48081498.57 35.41 01-MAR-07:10 55119587.01 33.31 01-MAR-06:10
April 43372485.83 35.41 03-APR-06:10 51689604.01 33.31 03-APR-05:10
May 46403248.92 35.41 01-MAY-06:10 54232108.89 33.31 01-MAY-05:10
June 46169568.59 35.41 01-JUN-06:10 53152743.61 33.31 01-JUN-05:10
July 43606166.16 35.41 03-JUL-06:10 52768969.29 33.31 03-JUL-05:10
August 48081498.57 35.41 01-AUG-06:10 55119587.01 33.31 01-AUG-05:10
September 43372485.83 35.41 01-SEP-06:10 51689604.01 33.31 01-SEP-05:10
October 44724999.26 35.41 02-OCT-06:10 53344630.77 33.31 02-OCT-05:10
November 43931902.38 35.41 01-NOV-06:10 51953448.85 33.31 01-NOV-05:10
December 43606166.16 35.41 01-DEC-07:10 52768969.29 33.31 01-DEC-06:10
             
Annual Sum or Average 0.536742E+09     0.633515E+09    
Minimum of Months 40667458.96 35.41   48331578.69 33.31  
Maximum of Months 48081498.57 35.41   55119587.01 33.31  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 SOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.200546E+09 158.76 02-JAN-07:10 0.399714E+09 249.62 02-JAN-06:10
February 0.182352E+09 158.76 01-FEB-07:10 0.362151E+09 249.62 01-FEB-06:10
March 0.215596E+09 158.76 01-MAR-07:10 0.413013E+09 249.62 01-MAR-06:10
April 0.194481E+09 158.76 03-APR-06:10 0.387312E+09 249.62 03-APR-05:10
May 0.208071E+09 158.76 01-MAY-06:10 0.406364E+09 249.62 01-MAY-05:10
June 0.207023E+09 158.76 01-JUN-06:10 0.398276E+09 249.62 01-JUN-05:10
July 0.195529E+09 158.76 03-JUL-06:10 0.395400E+09 249.62 03-JUL-05:10
August 0.215596E+09 158.76 01-AUG-06:10 0.413013E+09 249.62 01-AUG-05:10
September 0.194481E+09 158.76 01-SEP-06:10 0.387312E+09 249.62 01-SEP-05:10
October 0.200546E+09 158.76 02-OCT-06:10 0.399714E+09 249.62 02-OCT-05:10
November 0.196989E+09 158.76 01-NOV-06:10 0.389289E+09 249.62 01-NOV-05:10
December 0.195529E+09 158.76 01-DEC-07:10 0.395400E+09 249.62 01-DEC-06:10
             
Annual Sum or Average 0.240674E+10     0.474696E+10    
Minimum of Months 0.182352E+09 158.76   0.362151E+09 249.62  
Maximum of Months 0.215596E+09 158.76   0.413013E+09 249.62  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 89131391.98 70.56 02-JAN-07:10 0.177650E+09 110.94 02-JAN-06:10
February 81045215.98 70.56 01-FEB-07:10 0.160956E+09 110.94 01-FEB-06:10
March 95820479.98 70.56 01-MAR-07:10 0.183561E+09 110.94 01-MAR-06:10
April 86435999.98 70.56 03-APR-06:10 0.172139E+09 110.94 03-APR-05:10
May 92475935.98 70.56 01-MAY-06:10 0.180606E+09 110.94 01-MAY-05:10
June 92010239.98 70.56 01-JUN-06:10 0.177011E+09 110.94 01-JUN-05:10
July 86901695.98 70.56 03-JUL-06:10 0.175733E+09 110.94 03-JUL-05:10
August 95820479.98 70.56 01-AUG-06:10 0.183561E+09 110.94 01-AUG-05:10
September 86435999.98 70.56 01-SEP-06:10 0.172139E+09 110.94 01-SEP-05:10
October 89131391.98 70.56 02-OCT-06:10 0.177650E+09 110.94 02-OCT-05:10
November 87550847.98 70.56 01-NOV-06:10 0.173017E+09 110.94 01-NOV-05:10
December 86901695.98 70.56 01-DEC-07:10 0.175733E+09 110.94 01-DEC-06:10
             
Annual Sum or Average 0.106966E+10     0.210976E+10    
Minimum of Months 81045215.98 70.56   0.160956E+09 110.94  
Maximum of Months 95820479.98 70.56   0.183561E+09 110.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.286494E+09 226.80 02-JAN-07:10 0.571019E+09 356.60 02-JAN-06:10
February 0.260502E+09 226.80 01-FEB-07:10 0.517358E+09 356.60 01-FEB-06:10
March 0.307994E+09 226.80 01-MAR-07:10 0.590019E+09 356.60 01-MAR-06:10
April 0.277830E+09 226.80 03-APR-06:10 0.553303E+09 356.60 03-APR-05:10
May 0.297244E+09 226.80 01-MAY-06:10 0.580519E+09 356.60 01-MAY-05:10
June 0.295747E+09 226.80 01-JUN-06:10 0.568965E+09 356.60 01-JUN-05:10
July 0.279327E+09 226.80 03-JUL-06:10 0.564857E+09 356.60 03-JUL-05:10
August 0.307994E+09 226.80 01-AUG-06:10 0.590019E+09 356.60 01-AUG-05:10
September 0.277830E+09 226.80 01-SEP-06:10 0.553303E+09 356.60 01-SEP-05:10
October 0.286494E+09 226.80 02-OCT-06:10 0.571019E+09 356.60 02-OCT-05:10
November 0.281413E+09 226.80 01-NOV-06:10 0.556128E+09 356.60 01-NOV-05:10
December 0.279327E+09 226.80 01-DEC-07:10 0.564857E+09 356.60 01-DEC-06:10
             
Annual Sum or Average 0.343820E+10     0.678137E+10    
Minimum of Months 0.260502E+09 226.80   0.517358E+09 356.60  
Maximum of Months 0.307994E+09 226.80   0.590019E+09 356.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.426330E+09 337.50 02-JAN-07:10 0.142733E+10 891.37 02-JAN-06:10
February 0.387652E+09 337.50 01-FEB-07:10 0.129319E+10 891.37 01-FEB-06:10
March 0.458325E+09 337.50 01-MAR-07:10 0.147482E+10 891.37 01-MAR-06:10
April 0.413437E+09 337.50 03-APR-06:10 0.138304E+10 891.37 03-APR-05:10
May 0.442327E+09 337.50 01-MAY-06:10 0.145107E+10 891.37 01-MAY-05:10
June 0.440100E+09 337.50 01-JUN-06:10 0.142219E+10 891.37 01-JUN-05:10
July 0.415665E+09 337.50 03-JUL-06:10 0.141192E+10 891.37 03-JUL-05:10
August 0.458325E+09 337.50 01-AUG-06:10 0.147482E+10 891.37 01-AUG-05:10
September 0.413437E+09 337.50 01-SEP-06:10 0.138304E+10 891.37 01-SEP-05:10
October 0.426330E+09 337.50 02-OCT-06:10 0.142733E+10 891.37 02-OCT-05:10
November 0.418770E+09 337.50 01-NOV-06:10 0.139010E+10 891.37 01-NOV-05:10
December 0.415665E+09 337.50 01-DEC-07:10 0.141192E+10 891.37 01-DEC-06:10
             
Annual Sum or Average 0.511636E+10     0.169508E+11    
Minimum of Months 0.387652E+09 337.50   0.129319E+10 891.37  
Maximum of Months 0.458325E+09 337.50   0.147482E+10 891.37  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.327983E+09 259.64 02-JAN-07:10 0.391194E+09 244.30 02-JAN-06:10
February 0.298228E+09 259.64 01-FEB-07:10 0.354432E+09 244.30 01-FEB-06:10
March 0.352598E+09 259.64 01-MAR-07:10 0.404211E+09 244.30 01-MAR-06:10
April 0.318065E+09 259.64 03-APR-06:10 0.379057E+09 244.30 03-APR-05:10
May 0.340290E+09 259.64 01-MAY-06:10 0.397702E+09 244.30 01-MAY-05:10
June 0.338577E+09 259.64 01-JUN-06:10 0.389787E+09 244.30 01-JUN-05:10
July 0.319779E+09 259.64 03-JUL-06:10 0.386973E+09 244.30 03-JUL-05:10
August 0.352598E+09 259.64 01-AUG-06:10 0.404211E+09 244.30 01-AUG-05:10
September 0.318065E+09 259.64 01-SEP-06:10 0.379057E+09 244.30 01-SEP-05:10
October 0.327983E+09 259.64 02-OCT-06:10 0.391194E+09 244.30 02-OCT-05:10
November 0.322167E+09 259.64 01-NOV-06:10 0.380992E+09 244.30 01-NOV-05:10
December 0.319779E+09 259.64 01-DEC-07:10 0.386973E+09 244.30 01-DEC-06:10
             
Annual Sum or Average 0.393611E+10     0.464578E+10    
Minimum of Months 0.298228E+09 259.64   0.354432E+09 244.30  
Maximum of Months 0.352598E+09 259.64   0.404211E+09 244.30  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.114844E+09 90.92 02-JAN-07:10 63016404.11 39.35 02-JAN-06:10
February 0.104426E+09 90.92 01-FEB-07:10 57094448.86 39.35 01-FEB-06:10
March 0.123463E+09 90.92 01-MAR-07:10 65113172.95 39.35 01-MAR-06:10
April 0.111371E+09 90.92 03-APR-06:10 61061308.83 39.35 03-APR-05:10
May 0.119154E+09 90.92 01-MAY-06:10 64064788.53 39.35 01-MAY-05:10
June 0.118554E+09 90.92 01-JUN-06:10 62789726.39 39.35 01-JUN-05:10
July 0.111972E+09 90.92 03-JUL-06:10 62336370.97 39.35 03-JUL-05:10
August 0.123463E+09 90.92 01-AUG-06:10 65113172.95 39.35 01-AUG-05:10
September 0.111371E+09 90.92 01-SEP-06:10 61061308.83 39.35 01-SEP-05:10
October 0.114844E+09 90.92 02-OCT-06:10 63016404.11 39.35 02-OCT-05:10
November 0.112808E+09 90.92 01-NOV-06:10 61372990.69 39.35 01-NOV-05:10
December 0.111972E+09 90.92 01-DEC-07:10 62336370.97 39.35 01-DEC-06:10
             
Annual Sum or Average 0.137824E+10     0.748376E+09    
Minimum of Months 0.104426E+09 90.92   57094448.86 39.35  
Maximum of Months 0.123463E+09 90.92   65113172.95 39.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.266810E+09 211.22 02-JAN-07:10 0.146402E+09 91.43 02-JAN-06:10
February 0.242605E+09 211.22 01-FEB-07:10 0.132644E+09 91.43 01-FEB-06:10
March 0.286834E+09 211.22 01-MAR-07:10 0.151273E+09 91.43 01-MAR-06:10
April 0.258742E+09 211.22 03-APR-06:10 0.141860E+09 91.43 03-APR-05:10
May 0.276822E+09 211.22 01-MAY-06:10 0.148837E+09 91.43 01-MAY-05:10
June 0.275428E+09 211.22 01-JUN-06:10 0.145875E+09 91.43 01-JUN-05:10
July 0.260136E+09 211.22 03-JUL-06:10 0.144822E+09 91.43 03-JUL-05:10
August 0.286834E+09 211.22 01-AUG-06:10 0.151273E+09 91.43 01-AUG-05:10
September 0.258742E+09 211.22 01-SEP-06:10 0.141860E+09 91.43 01-SEP-05:10
October 0.266810E+09 211.22 02-OCT-06:10 0.146402E+09 91.43 02-OCT-05:10
November 0.262079E+09 211.22 01-NOV-06:10 0.142584E+09 91.43 01-NOV-05:10
December 0.260136E+09 211.22 01-DEC-07:10 0.144822E+09 91.43 01-DEC-06:10
             
Annual Sum or Average 0.320198E+10     0.173865E+10    
Minimum of Months 0.242605E+09 211.22   0.132644E+09 91.43  
Maximum of Months 0.286834E+09 211.22   0.151273E+09 91.43  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.104358E+09 82.61 02-JAN-07:10 0.124471E+09 77.73 02-JAN-06:10
February 94890737.57 82.61 01-FEB-07:10 0.112774E+09 77.73 01-FEB-06:10
March 0.112190E+09 82.61 01-MAR-07:10 0.128612E+09 77.73 01-MAR-06:10
April 0.101202E+09 82.61 03-APR-06:10 0.120609E+09 77.73 03-APR-05:10
May 0.108274E+09 82.61 01-MAY-06:10 0.126542E+09 77.73 01-MAY-05:10
June 0.107729E+09 82.61 01-JUN-06:10 0.124023E+09 77.73 01-JUN-05:10
July 0.101748E+09 82.61 03-JUL-06:10 0.123128E+09 77.73 03-JUL-05:10
August 0.112190E+09 82.61 01-AUG-06:10 0.128612E+09 77.73 01-AUG-05:10
September 0.101202E+09 82.61 01-SEP-06:10 0.120609E+09 77.73 01-SEP-05:10
October 0.104358E+09 82.61 02-OCT-06:10 0.124471E+09 77.73 02-OCT-05:10
November 0.102508E+09 82.61 01-NOV-06:10 0.121225E+09 77.73 01-NOV-05:10
December 0.101748E+09 82.61 01-DEC-07:10 0.123128E+09 77.73 01-DEC-06:10
             
Annual Sum or Average 0.125240E+10     0.147820E+10    
Minimum of Months 94890737.57 82.61   0.112774E+09 77.73  
Maximum of Months 0.112190E+09 82.61   0.128612E+09 77.73  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.136305E+09 107.90 02-JAN-07:10 0.162574E+09 101.53 02-JAN-06:10
February 0.123939E+09 107.90 01-FEB-07:10 0.147296E+09 101.53 01-FEB-06:10
March 0.146534E+09 107.90 01-MAR-07:10 0.167984E+09 101.53 01-MAR-06:10
April 0.132183E+09 107.90 03-APR-06:10 0.157530E+09 101.53 03-APR-05:10
May 0.141419E+09 107.90 01-MAY-06:10 0.165279E+09 101.53 01-MAY-05:10
June 0.140707E+09 107.90 01-JUN-06:10 0.161989E+09 101.53 01-JUN-05:10
July 0.132895E+09 107.90 03-JUL-06:10 0.160820E+09 101.53 03-JUL-05:10
August 0.146534E+09 107.90 01-AUG-06:10 0.167984E+09 101.53 01-AUG-05:10
September 0.132183E+09 107.90 01-SEP-06:10 0.157530E+09 101.53 01-SEP-05:10
October 0.136305E+09 107.90 02-OCT-06:10 0.162574E+09 101.53 02-OCT-05:10
November 0.133888E+09 107.90 01-NOV-06:10 0.158334E+09 101.53 01-NOV-05:10
December 0.132895E+09 107.90 01-DEC-07:10 0.160820E+09 101.53 01-DEC-06:10
             
Annual Sum or Average 0.163579E+10     0.193071E+10    
Minimum of Months 0.123939E+09 107.90   0.147296E+09 101.53  
Maximum of Months 0.146534E+09 107.90   0.167984E+09 101.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 12180473.20 9.64 02-JAN-07:10 6683582.04 4.17 02-JAN-06:10
February 11075436.60 9.64 01-FEB-07:10 6055493.62 4.17 01-FEB-06:10
March 13094587.24 9.64 01-MAR-07:10 6905967.42 4.17 01-MAR-06:10
April 11812127.67 9.64 03-APR-06:10 6476222.71 4.17 03-APR-05:10
May 12637530.22 9.64 01-MAY-06:10 6794774.73 4.17 01-MAY-05:10
June 12573889.37 9.64 01-JUN-06:10 6659540.38 4.17 01-JUN-05:10
July 11875768.52 9.64 03-JUL-06:10 6611457.06 4.17 03-JUL-05:10
August 13094587.24 9.64 01-AUG-06:10 6905967.42 4.17 01-AUG-05:10
September 11812127.67 9.64 01-SEP-06:10 6476222.71 4.17 01-SEP-05:10
October 12180473.20 9.64 02-OCT-06:10 6683582.04 4.17 02-OCT-05:10
November 11964480.01 9.64 01-NOV-06:10 6509279.99 4.17 01-NOV-05:10
December 11875768.52 9.64 01-DEC-07:10 6611457.06 4.17 01-DEC-06:10
             
Annual Sum or Average 0.146177E+09     79373547.16    
Minimum of Months 11075436.60 9.64   6055493.62 4.17  
Maximum of Months 13094587.24 9.64   6905967.42 4.17  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.104404E+09 82.65 02-JAN-07:10 57287596.84 35.78 02-JAN-06:10
February 94932313.75 82.65 01-FEB-07:10 51904005.23 35.78 01-FEB-06:10
March 0.112239E+09 82.65 01-MAR-07:10 59193748.89 35.78 01-MAR-06:10
April 0.101247E+09 82.65 03-APR-06:10 55510238.85 35.78 03-APR-05:10
May 0.108322E+09 82.65 01-MAY-06:10 58240672.87 35.78 01-MAY-05:10
June 0.107776E+09 82.65 01-JUN-06:10 57081526.35 35.78 01-JUN-05:10
July 0.101792E+09 82.65 03-JUL-06:10 56669385.36 35.78 03-JUL-05:10
August 0.112239E+09 82.65 01-AUG-06:10 59193748.89 35.78 01-AUG-05:10
September 0.101247E+09 82.65 01-SEP-06:10 55510238.85 35.78 01-SEP-05:10
October 0.104404E+09 82.65 02-OCT-06:10 57287596.84 35.78 02-OCT-05:10
November 0.102553E+09 82.65 01-NOV-06:10 55793585.77 35.78 01-NOV-05:10
December 0.101792E+09 82.65 01-DEC-07:10 56669385.36 35.78 01-DEC-06:10
             
Annual Sum or Average 0.125295E+10     0.680342E+09    
Minimum of Months 94932313.75 82.65   51904005.23 35.78  
Maximum of Months 0.112239E+09 82.65   59193748.89 35.78  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 38335713.65 30.35 02-JAN-07:10 45724037.20 28.55 02-JAN-06:10
February 34857821.96 30.35 01-FEB-07:10 41427129.03 28.55 01-FEB-06:10
March 41212713.06 30.35 01-MAR-07:10 47245430.53 28.55 01-MAR-06:10
April 37176416.42 30.35 03-APR-06:10 44305440.73 28.55 03-APR-05:10
May 39774213.36 30.35 01-MAY-06:10 46484733.87 28.55 01-MAY-05:10
June 39573915.93 30.35 01-JUN-06:10 45559562.25 28.55 01-JUN-05:10
July 37376713.85 30.35 03-JUL-06:10 45230612.34 28.55 03-JUL-05:10
August 41212713.06 30.35 01-AUG-06:10 47245430.53 28.55 01-AUG-05:10
September 37176416.42 30.35 01-SEP-06:10 44305440.73 28.55 01-SEP-05:10
October 38335713.65 30.35 02-OCT-06:10 45724037.20 28.55 02-OCT-05:10
November 37655916.33 30.35 01-NOV-06:10 44531593.79 28.55 01-NOV-05:10
December 37376713.85 30.35 01-DEC-07:10 45230612.34 28.55 01-DEC-06:10
             
Annual Sum or Average 0.460065E+09     0.543014E+09    
Minimum of Months 34857821.96 30.35   41427129.03 28.55  
Maximum of Months 41212713.06 30.35   47245430.53 28.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.185487E+09 293.33 02-JAN-07:10 0.532704E+09 332.67 02-JAN-06:10
February 0.138876E+09 293.33 01-FEB-07:10 0.482643E+09 332.67 01-FEB-06:10
March 0.140130E+09 293.33 01-MAR-17:00 0.550429E+09 332.67 01-MAR-06:10
April 97135767.03 263.91 03-APR-06:10 0.516177E+09 332.67 03-APR-05:10
May 79160283.84 174.20 08-MAY-05:10 0.541566E+09 332.67 01-MAY-05:10
June 72677886.16 221.75 30-JUN-06:10 0.530788E+09 332.67 01-JUN-05:10
July 68956022.98 186.70 25-JUL-05:10 0.526955E+09 332.67 03-JUL-05:10
August 0.106292E+09 268.55 31-AUG-06:10 0.550429E+09 332.67 01-AUG-05:10
September 0.112220E+09 293.33 27-SEP-06:10 0.516177E+09 332.67 01-SEP-05:10
October 0.150552E+09 293.33 02-OCT-06:10 0.532704E+09 332.67 02-OCT-05:10
November 0.183148E+09 293.33 01-NOV-06:10 0.518811E+09 332.67 01-NOV-05:10
December 0.197266E+09 293.33 01-DEC-07:10 0.526955E+09 332.67 01-DEC-06:10
             
Annual Sum or Average 0.153190E+10     0.632634E+10    
Minimum of Months 68956022.98 174.20   0.482643E+09 332.67  
Maximum of Months 0.197266E+09 293.33   0.550429E+09 332.67  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 30253741.06 23.95 02-JAN-07:10 40643588.63 25.38 02-JAN-06:10
February 27509061.89 23.95 01-FEB-07:10 36824114.70 25.38 01-FEB-06:10
March 32524208.64 23.95 01-MAR-07:10 41995938.25 25.38 01-MAR-06:10
April 29338848.00 23.95 03-APR-06:10 39382613.98 25.38 03-APR-05:10
May 31388974.85 23.95 01-MAY-06:10 41319763.44 25.38 01-MAY-05:10
June 31230904.32 23.95 01-JUN-06:10 40497388.67 25.38 01-JUN-05:10
July 29496918.53 23.95 03-JUL-06:10 40204988.75 25.38 03-JUL-05:10
August 32524208.64 23.95 01-AUG-06:10 41995938.25 25.38 01-AUG-05:10
September 29338848.00 23.95 01-SEP-06:10 39382613.98 25.38 01-SEP-05:10
October 30253741.06 23.95 02-OCT-06:10 40643588.63 25.38 02-OCT-05:10
November 29717259.27 23.95 01-NOV-06:10 39583638.92 25.38 01-NOV-05:10
December 29496918.53 23.95 01-DEC-07:10 40204988.75 25.38 01-DEC-06:10
             
Annual Sum or Average 0.363074E+09     0.482679E+09    
Minimum of Months 27509061.89 23.95   36824114.70 25.38  
Maximum of Months 32524208.64 23.95   41995938.25 25.38  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 50710966.54 40.05 02-JAN-07:10 0.122119E+09 76.26 02-JAN-06:10
February 46101387.93 40.05 01-FEB-07:10 0.110643E+09 76.26 01-FEB-06:10
March 54468411.74 40.05 01-MAR-07:10 0.126183E+09 76.26 01-MAR-06:10
April 49161302.82 40.05 03-APR-06:10 0.118330E+09 76.26 03-APR-05:10
May 52589689.14 40.05 01-MAY-06:10 0.124151E+09 76.26 01-MAY-05:10
June 52305644.67 40.05 01-JUN-06:10 0.121680E+09 76.26 01-JUN-05:10
July 49445347.30 40.05 03-JUL-06:10 0.120801E+09 76.26 03-JUL-05:10
August 54468411.74 40.05 01-AUG-06:10 0.126183E+09 76.26 01-AUG-05:10
September 49161302.82 40.05 01-SEP-06:10 0.118330E+09 76.26 01-SEP-05:10
October 50710966.54 40.05 02-OCT-06:10 0.122119E+09 76.26 02-OCT-05:10
November 49813818.72 40.05 01-NOV-06:10 0.118934E+09 76.26 01-NOV-05:10
December 49445347.30 40.05 01-DEC-07:10 0.120801E+09 76.26 01-DEC-06:10
             
Annual Sum or Average 0.608383E+09     0.145028E+10    
Minimum of Months 46101387.93 40.05   0.110643E+09 76.26  
Maximum of Months 54468411.74 40.05   0.126183E+09 76.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.446930E+09 353.81 02-JAN-07:10 0.628042E+09 392.21 02-JAN-06:10
February 0.406384E+09 353.81 01-FEB-07:10 0.569022E+09 392.21 01-FEB-06:10
March 0.480471E+09 353.81 01-MAR-07:10 0.648939E+09 392.21 01-MAR-06:10
April 0.433415E+09 353.81 03-APR-06:10 0.608557E+09 392.21 03-APR-05:10
May 0.463701E+09 353.81 01-MAY-06:10 0.638490E+09 392.21 01-MAY-05:10
June 0.461366E+09 353.81 01-JUN-06:10 0.625783E+09 392.21 01-JUN-05:10
July 0.435750E+09 353.81 03-JUL-06:10 0.621264E+09 392.21 03-JUL-05:10
August 0.480471E+09 353.81 01-AUG-06:10 0.648939E+09 392.21 01-AUG-05:10
September 0.433415E+09 353.81 01-SEP-06:10 0.608557E+09 392.21 01-SEP-05:10
October 0.446930E+09 353.81 02-OCT-06:10 0.628042E+09 392.21 02-OCT-05:10
November 0.439005E+09 353.81 01-NOV-06:10 0.611663E+09 392.21 01-NOV-05:10
December 0.435750E+09 353.81 01-DEC-07:10 0.621264E+09 392.21 01-DEC-06:10
             
Annual Sum or Average 0.536359E+10     0.745856E+10    
Minimum of Months 0.406384E+09 353.81   0.569022E+09 392.21  
Maximum of Months 0.480471E+09 353.81   0.648939E+09 392.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.670395E+09 530.71 02-JAN-07:10 0.942063E+09 588.32 02-JAN-06:10
February 0.609576E+09 530.71 01-FEB-07:10 0.853533E+09 588.32 01-FEB-06:10
March 0.720707E+09 530.71 01-MAR-07:10 0.973408E+09 588.32 01-MAR-06:10
April 0.650122E+09 530.71 03-APR-06:10 0.912835E+09 588.32 03-APR-05:10
May 0.695551E+09 530.71 01-MAY-06:10 0.957736E+09 588.32 01-MAY-05:10
June 0.692048E+09 530.71 01-JUN-06:10 0.938674E+09 588.32 01-JUN-05:10
July 0.653625E+09 530.71 03-JUL-06:10 0.931897E+09 588.32 03-JUL-05:10
August 0.720707E+09 530.71 01-AUG-06:10 0.973408E+09 588.32 01-AUG-05:10
September 0.650122E+09 530.71 01-SEP-06:10 0.912835E+09 588.32 01-SEP-05:10
October 0.670395E+09 530.71 02-OCT-06:10 0.942063E+09 588.32 02-OCT-05:10
November 0.658507E+09 530.71 01-NOV-06:10 0.917495E+09 588.32 01-NOV-05:10
December 0.653625E+09 530.71 01-DEC-07:10 0.931897E+09 588.32 01-DEC-06:10
             
Annual Sum or Average 0.804538E+10     0.111878E+11    
Minimum of Months 0.609576E+09 530.71   0.853533E+09 588.32  
Maximum of Months 0.720707E+09 530.71   0.973408E+09 588.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.893861E+09 707.62 02-JAN-07:10 0.125608E+10 784.42 02-JAN-06:10
February 0.812768E+09 707.62 01-FEB-07:10 0.113804E+10 784.42 01-FEB-06:10
March 0.960943E+09 707.62 01-MAR-07:10 0.129788E+10 784.42 01-MAR-06:10
April 0.866830E+09 707.62 03-APR-06:10 0.121711E+10 784.42 03-APR-05:10
May 0.927402E+09 707.62 01-MAY-06:10 0.127698E+10 784.42 01-MAY-05:10
June 0.922731E+09 707.62 01-JUN-06:10 0.125157E+10 784.42 01-JUN-05:10
July 0.871500E+09 707.62 03-JUL-06:10 0.124253E+10 784.42 03-JUL-05:10
August 0.960943E+09 707.62 01-AUG-06:10 0.129788E+10 784.42 01-AUG-05:10
September 0.866830E+09 707.62 01-SEP-06:10 0.121711E+10 784.42 01-SEP-05:10
October 0.893861E+09 707.62 02-OCT-06:10 0.125608E+10 784.42 02-OCT-05:10
November 0.878010E+09 707.62 01-NOV-06:10 0.122333E+10 784.42 01-NOV-05:10
December 0.871500E+09 707.62 01-DEC-07:10 0.124253E+10 784.42 01-DEC-06:10
             
Annual Sum or Average 0.107272E+11     0.149171E+11    
Minimum of Months 0.812768E+09 707.62   0.113804E+10 784.42  
Maximum of Months 0.960943E+09 707.62   0.129788E+10 784.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.104284E+09 82.56 02-JAN-07:10 0.146543E+09 91.52 02-JAN-06:10
February 94822902.70 82.56 01-FEB-07:10 0.132772E+09 91.52 01-FEB-06:10
March 0.112110E+09 82.56 01-MAR-07:10 0.151419E+09 91.52 01-MAR-06:10
April 0.101130E+09 82.56 03-APR-06:10 0.141996E+09 91.52 03-APR-05:10
May 0.108197E+09 82.56 01-MAY-06:10 0.148981E+09 91.52 01-MAY-05:10
June 0.107652E+09 82.56 01-JUN-06:10 0.146016E+09 91.52 01-JUN-05:10
July 0.101675E+09 82.56 03-JUL-06:10 0.144962E+09 91.52 03-JUL-05:10
August 0.112110E+09 82.56 01-AUG-06:10 0.151419E+09 91.52 01-AUG-05:10
September 0.101130E+09 82.56 01-SEP-06:10 0.141996E+09 91.52 01-SEP-05:10
October 0.104284E+09 82.56 02-OCT-06:10 0.146543E+09 91.52 02-OCT-05:10
November 0.102434E+09 82.56 01-NOV-06:10 0.142721E+09 91.52 01-NOV-05:10
December 0.101675E+09 82.56 01-DEC-07:10 0.144962E+09 91.52 01-DEC-06:10
             
Annual Sum or Average 0.125150E+10     0.174033E+10    
Minimum of Months 94822902.70 82.56   0.132772E+09 91.52  
Maximum of Months 0.112110E+09 82.56   0.151419E+09 91.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.434516E+09 343.98 02-JAN-07:10 0.610596E+09 381.32 02-JAN-06:10
February 0.395095E+09 343.98 01-FEB-07:10 0.553216E+09 381.32 01-FEB-06:10
March 0.467125E+09 343.98 01-MAR-07:10 0.630913E+09 381.32 01-MAR-06:10
April 0.421375E+09 343.98 03-APR-06:10 0.591652E+09 381.32 03-APR-05:10
May 0.450820E+09 343.98 01-MAY-06:10 0.620755E+09 381.32 01-MAY-05:10
June 0.448550E+09 343.98 01-JUN-06:10 0.608400E+09 381.32 01-JUN-05:10
July 0.423646E+09 343.98 03-JUL-06:10 0.604007E+09 381.32 03-JUL-05:10
August 0.467125E+09 343.98 01-AUG-06:10 0.630913E+09 381.32 01-AUG-05:10
September 0.421375E+09 343.98 01-SEP-06:10 0.591652E+09 381.32 01-SEP-05:10
October 0.434516E+09 343.98 02-OCT-06:10 0.610596E+09 381.32 02-OCT-05:10
November 0.426810E+09 343.98 01-NOV-06:10 0.594672E+09 381.32 01-NOV-05:10
December 0.423646E+09 343.98 01-DEC-07:10 0.604007E+09 381.32 01-DEC-06:10
             
Annual Sum or Average 0.521460E+10     0.725138E+10    
Minimum of Months 0.395095E+09 343.98   0.553216E+09 381.32  
Maximum of Months 0.467125E+09 343.98   0.630913E+09 381.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.279331E+09 221.13 02-JAN-07:10 0.392526E+09 245.13 02-JAN-06:10
February 0.253990E+09 221.13 01-FEB-07:10 0.355639E+09 245.13 01-FEB-06:10
March 0.300295E+09 221.13 01-MAR-07:10 0.405587E+09 245.13 01-MAR-06:10
April 0.270884E+09 221.13 03-APR-06:10 0.380348E+09 245.13 03-APR-05:10
May 0.289813E+09 221.13 01-MAY-06:10 0.399056E+09 245.13 01-MAY-05:10
June 0.288354E+09 221.13 01-JUN-06:10 0.391114E+09 245.13 01-JUN-05:10
July 0.272344E+09 221.13 03-JUL-06:10 0.388290E+09 245.13 03-JUL-05:10
August 0.300295E+09 221.13 01-AUG-06:10 0.405587E+09 245.13 01-AUG-05:10
September 0.270884E+09 221.13 01-SEP-06:10 0.380348E+09 245.13 01-SEP-05:10
October 0.279331E+09 221.13 02-OCT-06:10 0.392526E+09 245.13 02-OCT-05:10
November 0.274378E+09 221.13 01-NOV-06:10 0.382289E+09 245.13 01-NOV-05:10
December 0.272344E+09 221.13 01-DEC-07:10 0.388290E+09 245.13 01-DEC-06:10
             
Annual Sum or Average 0.335224E+10     0.466160E+10    
Minimum of Months 0.253990E+09 221.13   0.355639E+09 245.13  
Maximum of Months 0.300295E+09 221.13   0.405587E+09 245.13  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.983247E+09 778.38 02-JAN-07:10 0.138169E+10 862.87 02-JAN-06:10
February 0.894045E+09 778.38 01-FEB-07:10 0.125185E+10 862.87 01-FEB-06:10
March 0.105704E+10 778.38 01-MAR-07:10 0.142767E+10 862.87 01-MAR-06:10
April 0.953513E+09 778.38 03-APR-06:10 0.133882E+10 862.87 03-APR-05:10
May 0.102014E+10 778.38 01-MAY-06:10 0.140468E+10 862.87 01-MAY-05:10
June 0.101500E+10 778.38 01-JUN-06:10 0.137672E+10 862.87 01-JUN-05:10
July 0.958650E+09 778.38 03-JUL-06:10 0.136678E+10 862.87 03-JUL-05:10
August 0.105704E+10 778.38 01-AUG-06:10 0.142767E+10 862.87 01-AUG-05:10
September 0.953513E+09 778.38 01-SEP-06:10 0.133882E+10 862.87 01-SEP-05:10
October 0.983247E+09 778.38 02-OCT-06:10 0.138169E+10 862.87 02-OCT-05:10
November 0.965811E+09 778.38 01-NOV-06:10 0.134566E+10 862.87 01-NOV-05:10
December 0.958650E+09 778.38 01-DEC-07:10 0.136678E+10 862.87 01-DEC-06:10
             
Annual Sum or Average 0.117999E+11     0.164088E+11    
Minimum of Months 0.894045E+09 778.38   0.125185E+10 862.87  
Maximum of Months 0.105704E+10 778.38   0.142767E+10 862.87  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.335198E+09 265.36 02-JAN-07:10 0.471031E+09 294.16 02-JAN-06:10
February 0.304788E+09 265.36 01-FEB-07:10 0.426766E+09 294.16 01-FEB-06:10
March 0.360353E+09 265.36 01-MAR-07:10 0.486704E+09 294.16 01-MAR-06:10
April 0.325061E+09 265.36 03-APR-06:10 0.456417E+09 294.16 03-APR-05:10
May 0.347776E+09 265.36 01-MAY-06:10 0.478868E+09 294.16 01-MAY-05:10
June 0.346024E+09 265.36 01-JUN-06:10 0.469337E+09 294.16 01-JUN-05:10
July 0.326812E+09 265.36 03-JUL-06:10 0.465948E+09 294.16 03-JUL-05:10
August 0.360353E+09 265.36 01-AUG-06:10 0.486704E+09 294.16 01-AUG-05:10
September 0.325061E+09 265.36 01-SEP-06:10 0.456417E+09 294.16 01-SEP-05:10
October 0.335198E+09 265.36 02-OCT-06:10 0.471031E+09 294.16 02-OCT-05:10
November 0.329254E+09 265.36 01-NOV-06:10 0.458747E+09 294.16 01-NOV-05:10
December 0.326812E+09 265.36 01-DEC-07:10 0.465948E+09 294.16 01-DEC-06:10
             
Annual Sum or Average 0.402269E+10     0.559392E+10    
Minimum of Months 0.304788E+09 265.36   0.426766E+09 294.16  
Maximum of Months 0.360353E+09 265.36   0.486704E+09 294.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.491623E+09 389.19 02-JAN-07:10 0.690846E+09 431.43 02-JAN-06:10
February 0.447022E+09 389.19 01-FEB-07:10 0.625924E+09 431.43 01-FEB-06:10
March 0.528518E+09 389.19 01-MAR-07:10 0.713833E+09 431.43 01-MAR-06:10
April 0.476756E+09 389.19 03-APR-06:10 0.669412E+09 431.43 03-APR-05:10
May 0.510071E+09 389.19 01-MAY-06:10 0.702339E+09 431.43 01-MAY-05:10
June 0.507502E+09 389.19 01-JUN-06:10 0.688361E+09 431.43 01-JUN-05:10
July 0.479325E+09 389.19 03-JUL-06:10 0.683391E+09 431.43 03-JUL-05:10
August 0.528518E+09 389.19 01-AUG-06:10 0.713833E+09 431.43 01-AUG-05:10
September 0.476756E+09 389.19 01-SEP-06:10 0.669412E+09 431.43 01-SEP-05:10
October 0.491623E+09 389.19 02-OCT-06:10 0.690846E+09 431.43 02-OCT-05:10
November 0.482905E+09 389.19 01-NOV-06:10 0.672829E+09 431.43 01-NOV-05:10
December 0.479325E+09 389.19 01-DEC-07:10 0.683391E+09 431.43 01-DEC-06:10
             
Annual Sum or Average 0.589995E+10     0.820442E+10    
Minimum of Months 0.447022E+09 389.19   0.625924E+09 431.43  
Maximum of Months 0.528518E+09 389.19   0.713833E+09 431.43  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 95839284.14 75.87 02-JAN-07:10 0.114310E+09 71.39 02-JAN-06:10
February 87144554.91 75.87 01-FEB-07:10 0.103568E+09 71.39 01-FEB-06:10
March 0.103032E+09 75.87 01-MAR-07:10 0.118113E+09 71.39 01-MAR-06:10
April 92941041.06 75.87 03-APR-06:10 0.110764E+09 71.39 03-APR-05:10
May 99435533.40 75.87 01-MAY-06:10 0.116212E+09 71.39 01-MAY-05:10
June 98934789.83 75.87 01-JUN-06:10 0.113899E+09 71.39 01-JUN-05:10
July 93441784.63 75.87 03-JUL-06:10 0.113076E+09 71.39 03-JUL-05:10
August 0.103032E+09 75.87 01-AUG-06:10 0.118113E+09 71.39 01-AUG-05:10
September 92941041.06 75.87 01-SEP-06:10 0.110764E+09 71.39 01-SEP-05:10
October 95839284.14 75.87 02-OCT-06:10 0.114310E+09 71.39 02-OCT-05:10
November 94139790.81 75.87 01-NOV-06:10 0.111329E+09 71.39 01-NOV-05:10
December 93441784.63 75.87 01-DEC-07:10 0.113076E+09 71.39 01-DEC-06:10
             
Annual Sum or Average 0.115016E+10     0.135753E+10    
Minimum of Months 87144554.91 75.87   0.103568E+09 71.39  
Maximum of Months 0.103032E+09 75.87   0.118113E+09 71.39  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 95839284.14 75.87 02-JAN-07:10 0.114310E+09 71.39 02-JAN-06:10
February 87144554.91 75.87 01-FEB-07:10 0.103568E+09 71.39 01-FEB-06:10
March 0.103032E+09 75.87 01-MAR-07:10 0.118113E+09 71.39 01-MAR-06:10
April 92941041.06 75.87 03-APR-06:10 0.110764E+09 71.39 03-APR-05:10
May 99435533.40 75.87 01-MAY-06:10 0.116212E+09 71.39 01-MAY-05:10
June 98934789.83 75.87 01-JUN-06:10 0.113899E+09 71.39 01-JUN-05:10
July 93441784.63 75.87 03-JUL-06:10 0.113076E+09 71.39 03-JUL-05:10
August 0.103032E+09 75.87 01-AUG-06:10 0.118113E+09 71.39 01-AUG-05:10
September 92941041.06 75.87 01-SEP-06:10 0.110764E+09 71.39 01-SEP-05:10
October 95839284.14 75.87 02-OCT-06:10 0.114310E+09 71.39 02-OCT-05:10
November 94139790.81 75.87 01-NOV-06:10 0.111329E+09 71.39 01-NOV-05:10
December 93441784.63 75.87 01-DEC-07:10 0.113076E+09 71.39 01-DEC-06:10
             
Annual Sum or Average 0.115016E+10     0.135753E+10    
Minimum of Months 87144554.91 75.87   0.103568E+09 71.39  
Maximum of Months 0.103032E+09 75.87   0.118113E+09 71.39  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 95839284.14 75.87 02-JAN-07:10 0.114310E+09 71.39 02-JAN-06:10
February 87144554.91 75.87 01-FEB-07:10 0.103568E+09 71.39 01-FEB-06:10
March 0.103032E+09 75.87 01-MAR-07:10 0.118113E+09 71.39 01-MAR-06:10
April 92941041.06 75.87 03-APR-06:10 0.110764E+09 71.39 03-APR-05:10
May 99435533.40 75.87 01-MAY-06:10 0.116212E+09 71.39 01-MAY-05:10
June 98934789.83 75.87 01-JUN-06:10 0.113899E+09 71.39 01-JUN-05:10
July 93441784.63 75.87 03-JUL-06:10 0.113076E+09 71.39 03-JUL-05:10
August 0.103032E+09 75.87 01-AUG-06:10 0.118113E+09 71.39 01-AUG-05:10
September 92941041.06 75.87 01-SEP-06:10 0.110764E+09 71.39 01-SEP-05:10
October 95839284.14 75.87 02-OCT-06:10 0.114310E+09 71.39 02-OCT-05:10
November 94139790.81 75.87 01-NOV-06:10 0.111329E+09 71.39 01-NOV-05:10
December 93441784.63 75.87 01-DEC-07:10 0.113076E+09 71.39 01-DEC-06:10
             
Annual Sum or Average 0.115016E+10     0.135753E+10    
Minimum of Months 87144554.91 75.87   0.103568E+09 71.39  
Maximum of Months 0.103032E+09 75.87   0.118113E+09 71.39  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.105423E+09 83.46 02-JAN-07:10 0.125741E+09 78.53 02-JAN-06:10
February 95859010.40 83.46 01-FEB-07:10 0.113924E+09 78.53 01-FEB-06:10
March 0.113335E+09 83.46 01-MAR-07:10 0.129925E+09 78.53 01-MAR-06:10
April 0.102235E+09 83.46 03-APR-06:10 0.121840E+09 78.53 03-APR-05:10
May 0.109379E+09 83.46 01-MAY-06:10 0.127833E+09 78.53 01-MAY-05:10
June 0.108828E+09 83.46 01-JUN-06:10 0.125289E+09 78.53 01-JUN-05:10
July 0.102786E+09 83.46 03-JUL-06:10 0.124384E+09 78.53 03-JUL-05:10
August 0.113335E+09 83.46 01-AUG-06:10 0.129925E+09 78.53 01-AUG-05:10
September 0.102235E+09 83.46 01-SEP-06:10 0.121840E+09 78.53 01-SEP-05:10
October 0.105423E+09 83.46 02-OCT-06:10 0.125741E+09 78.53 02-OCT-05:10
November 0.103554E+09 83.46 01-NOV-06:10 0.122462E+09 78.53 01-NOV-05:10
December 0.102786E+09 83.46 01-DEC-07:10 0.124384E+09 78.53 01-DEC-06:10
             
Annual Sum or Average 0.126518E+10     0.149329E+10    
Minimum of Months 95859010.40 83.46   0.113924E+09 78.53  
Maximum of Months 0.113335E+09 83.46   0.129925E+09 78.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.105423E+09 83.46 02-JAN-07:10 0.125741E+09 78.53 02-JAN-06:10
February 95859010.40 83.46 01-FEB-07:10 0.113924E+09 78.53 01-FEB-06:10
March 0.113335E+09 83.46 01-MAR-07:10 0.129925E+09 78.53 01-MAR-06:10
April 0.102235E+09 83.46 03-APR-06:10 0.121840E+09 78.53 03-APR-05:10
May 0.109379E+09 83.46 01-MAY-06:10 0.127833E+09 78.53 01-MAY-05:10
June 0.108828E+09 83.46 01-JUN-06:10 0.125289E+09 78.53 01-JUN-05:10
July 0.102786E+09 83.46 03-JUL-06:10 0.124384E+09 78.53 03-JUL-05:10
August 0.113335E+09 83.46 01-AUG-06:10 0.129925E+09 78.53 01-AUG-05:10
September 0.102235E+09 83.46 01-SEP-06:10 0.121840E+09 78.53 01-SEP-05:10
October 0.105423E+09 83.46 02-OCT-06:10 0.125741E+09 78.53 02-OCT-05:10
November 0.103554E+09 83.46 01-NOV-06:10 0.122462E+09 78.53 01-NOV-05:10
December 0.102786E+09 83.46 01-DEC-07:10 0.124384E+09 78.53 01-DEC-06:10
             
Annual Sum or Average 0.126518E+10     0.149329E+10    
Minimum of Months 95859010.40 83.46   0.113924E+09 78.53  
Maximum of Months 0.113335E+09 83.46   0.129925E+09 78.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.105423E+09 83.46 02-JAN-07:10 0.125741E+09 78.53 02-JAN-06:10
February 95859010.40 83.46 01-FEB-07:10 0.113924E+09 78.53 01-FEB-06:10
March 0.113335E+09 83.46 01-MAR-07:10 0.129925E+09 78.53 01-MAR-06:10
April 0.102235E+09 83.46 03-APR-06:10 0.121840E+09 78.53 03-APR-05:10
May 0.109379E+09 83.46 01-MAY-06:10 0.127833E+09 78.53 01-MAY-05:10
June 0.108828E+09 83.46 01-JUN-06:10 0.125289E+09 78.53 01-JUN-05:10
July 0.102786E+09 83.46 03-JUL-06:10 0.124384E+09 78.53 03-JUL-05:10
August 0.113335E+09 83.46 01-AUG-06:10 0.129925E+09 78.53 01-AUG-05:10
September 0.102235E+09 83.46 01-SEP-06:10 0.121840E+09 78.53 01-SEP-05:10
October 0.105423E+09 83.46 02-OCT-06:10 0.125741E+09 78.53 02-OCT-05:10
November 0.103554E+09 83.46 01-NOV-06:10 0.122462E+09 78.53 01-NOV-05:10
December 0.102786E+09 83.46 01-DEC-07:10 0.124384E+09 78.53 01-DEC-06:10
             
Annual Sum or Average 0.126518E+10     0.149329E+10    
Minimum of Months 95859010.40 83.46   0.113924E+09 78.53  
Maximum of Months 0.113335E+09 83.46   0.129925E+09 78.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 18270709.80 14.46 02-JAN-07:10 10025293.76 6.26 02-JAN-06:10
February 16613154.91 14.46 01-FEB-07:10 9083168.58 6.26 01-FEB-06:10
March 19641880.87 14.46 01-MAR-07:10 10358869.18 6.26 01-MAR-06:10
April 17718191.50 14.46 03-APR-06:10 9714257.22 6.26 03-APR-05:10
May 18956295.33 14.46 01-MAY-06:10 10192081.47 6.26 01-MAY-05:10
June 18860834.06 14.46 01-JUN-06:10 9989231.55 6.26 01-JUN-05:10
July 17813652.78 14.46 03-JUL-06:10 9917107.14 6.26 03-JUL-05:10
August 19641880.87 14.46 01-AUG-06:10 10358869.18 6.26 01-AUG-05:10
September 17718191.50 14.46 01-SEP-06:10 9714257.22 6.26 01-SEP-05:10
October 18270709.80 14.46 02-OCT-06:10 10025293.76 6.26 02-OCT-05:10
November 17946720.01 14.46 01-NOV-06:10 9763842.76 6.26 01-NOV-05:10
December 17813652.78 14.46 01-DEC-07:10 9917107.14 6.26 01-DEC-06:10
             
Annual Sum or Average 0.219266E+09     0.119059E+09    
Minimum of Months 16613154.91 14.46   9083168.58 6.26  
Maximum of Months 19641880.87 14.46   10358869.18 6.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 53660736.00 42.48 02-JAN-07:10 0.380621E+09 237.70 02-JAN-06:10
February 48792528.00 42.48 01-FEB-07:10 0.344852E+09 237.70 01-FEB-06:10
March 57687840.00 42.48 01-MAR-07:10 0.393285E+09 237.70 01-MAR-06:10
April 52038000.00 42.48 03-APR-06:10 0.368812E+09 237.70 03-APR-05:10
May 55674288.00 42.48 01-MAY-06:10 0.386953E+09 237.70 01-MAY-05:10
June 55393920.00 42.48 01-JUN-06:10 0.379252E+09 237.70 01-JUN-05:10
July 52318368.00 42.48 03-JUL-06:10 0.376513E+09 237.70 03-JUL-05:10
August 57687840.00 42.48 01-AUG-06:10 0.393285E+09 237.70 01-AUG-05:10
September 52038000.00 42.48 01-SEP-06:10 0.368812E+09 237.70 01-SEP-05:10
October 53660736.00 42.48 02-OCT-06:10 0.380621E+09 237.70 02-OCT-05:10
November 52709184.00 42.48 01-NOV-06:10 0.370694E+09 237.70 01-NOV-05:10
December 52318368.00 42.48 01-DEC-07:10 0.376513E+09 237.70 01-DEC-06:10
             
Annual Sum or Average 0.643980E+09     0.452021E+10    
Minimum of Months 48792528.00 42.48   0.344852E+09 237.70  
Maximum of Months 57687840.00 42.48   0.393285E+09 237.70  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.199522E+09 157.95 02-JAN-07:10 0.475850E+09 297.17 02-JAN-06:10
February 0.181421E+09 157.95 01-FEB-07:10 0.431132E+09 297.17 01-FEB-06:10
March 0.214496E+09 157.95 01-MAR-07:10 0.491683E+09 297.17 01-MAR-06:10
April 0.193489E+09 157.95 03-APR-06:10 0.461086E+09 297.17 03-APR-05:10
May 0.207009E+09 157.95 01-MAY-06:10 0.483766E+09 297.17 01-MAY-05:10
June 0.205967E+09 157.95 01-JUN-06:10 0.474138E+09 297.17 01-JUN-05:10
July 0.194531E+09 157.95 03-JUL-06:10 0.470715E+09 297.17 03-JUL-05:10
August 0.214496E+09 157.95 01-AUG-06:10 0.491683E+09 297.17 01-AUG-05:10
September 0.193489E+09 157.95 01-SEP-06:10 0.461086E+09 297.17 01-SEP-05:10
October 0.199522E+09 157.95 02-OCT-06:10 0.475850E+09 297.17 02-OCT-05:10
November 0.195984E+09 157.95 01-NOV-06:10 0.463440E+09 297.17 01-NOV-05:10
December 0.194531E+09 157.95 01-DEC-07:10 0.470715E+09 297.17 01-DEC-06:10
             
Annual Sum or Average 0.239446E+10     0.565114E+10    
Minimum of Months 0.181421E+09 157.95   0.431132E+09 297.17  
Maximum of Months 0.214496E+09 157.95   0.491683E+09 297.17  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.239427E+09 189.54 02-JAN-07:10 0.571019E+09 356.60 02-JAN-06:10
February 0.217706E+09 189.54 01-FEB-07:10 0.517358E+09 356.60 01-FEB-06:10
March 0.257395E+09 189.54 01-MAR-07:10 0.590019E+09 356.60 01-MAR-06:10
April 0.232187E+09 189.54 03-APR-06:10 0.553303E+09 356.60 03-APR-05:10
May 0.248411E+09 189.54 01-MAY-06:10 0.580519E+09 356.60 01-MAY-05:10
June 0.247160E+09 189.54 01-JUN-06:10 0.568965E+09 356.60 01-JUN-05:10
July 0.233437E+09 189.54 03-JUL-06:10 0.564857E+09 356.60 03-JUL-05:10
August 0.257395E+09 189.54 01-AUG-06:10 0.590019E+09 356.60 01-AUG-05:10
September 0.232187E+09 189.54 01-SEP-06:10 0.553303E+09 356.60 01-SEP-05:10
October 0.239427E+09 189.54 02-OCT-06:10 0.571019E+09 356.60 02-OCT-05:10
November 0.235181E+09 189.54 01-NOV-06:10 0.556128E+09 356.60 01-NOV-05:10
December 0.233437E+09 189.54 01-DEC-07:10 0.564857E+09 356.60 01-DEC-06:10
             
Annual Sum or Average 0.287335E+10     0.678137E+10    
Minimum of Months 0.217706E+09 189.54   0.517358E+09 356.60  
Maximum of Months 0.257395E+09 189.54   0.590019E+09 356.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.234600E+09 320.41 02-JAN-07:10 0.976954E+09 610.11 02-JAN-06:10
February 0.172314E+09 320.41 01-FEB-07:10 0.885145E+09 610.11 01-FEB-06:10
March 0.170169E+09 320.41 01-MAR-17:00 0.100946E+10 610.11 01-MAR-06:10
April 0.115689E+09 275.96 03-APR-06:10 0.946644E+09 610.11 03-APR-05:10
May 89712890.38 181.36 25-MAY-05:10 0.993207E+09 610.11 01-MAY-05:10
June 80762985.48 214.82 30-JUN-06:10 0.973440E+09 610.11 01-JUN-05:10
July 76976894.47 201.48 25-JUL-05:10 0.966411E+09 610.11 03-JUL-05:10
August 0.118791E+09 286.43 31-AUG-06:10 0.100946E+10 610.11 01-AUG-05:10
September 0.133179E+09 320.41 27-SEP-06:10 0.946644E+09 610.11 01-SEP-05:10
October 0.184770E+09 320.41 02-OCT-06:10 0.976954E+09 610.11 02-OCT-05:10
November 0.223490E+09 320.41 01-NOV-06:10 0.951476E+09 610.11 01-NOV-05:10
December 0.241405E+09 320.41 01-DEC-07:10 0.966411E+09 610.11 01-DEC-06:10
             
Annual Sum or Average 0.184186E+10     0.116022E+11    
Minimum of Months 76976894.47 181.36   0.885145E+09 610.11  
Maximum of Months 0.241405E+09 320.41   0.100946E+10 610.11  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.236404E+09 187.15 02-JAN-07:10 0.281965E+09 176.09 02-JAN-06:10
February 0.214957E+09 187.15 01-FEB-07:10 0.255467E+09 176.09 01-FEB-06:10
March 0.254145E+09 187.15 01-MAR-07:10 0.291347E+09 176.09 01-MAR-06:10
April 0.229255E+09 187.15 03-APR-06:10 0.273217E+09 176.09 03-APR-05:10
May 0.245274E+09 187.15 01-MAY-06:10 0.286656E+09 176.09 01-MAY-05:10
June 0.244039E+09 187.15 01-JUN-06:10 0.280950E+09 176.09 01-JUN-05:10
July 0.230490E+09 187.15 03-JUL-06:10 0.278922E+09 176.09 03-JUL-05:10
August 0.254145E+09 187.15 01-AUG-06:10 0.291347E+09 176.09 01-AUG-05:10
September 0.229255E+09 187.15 01-SEP-06:10 0.273217E+09 176.09 01-SEP-05:10
October 0.236404E+09 187.15 02-OCT-06:10 0.281965E+09 176.09 02-OCT-05:10
November 0.232211E+09 187.15 01-NOV-06:10 0.274611E+09 176.09 01-NOV-05:10
December 0.230490E+09 187.15 01-DEC-07:10 0.278922E+09 176.09 01-DEC-06:10
             
Annual Sum or Average 0.283707E+10     0.334858E+10    
Minimum of Months 0.214957E+09 187.15   0.255467E+09 176.09  
Maximum of Months 0.254145E+09 187.15   0.291347E+09 176.09  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.596260E+09 743.90 02-JAN-07:10 0.171665E+10 1072.05 02-JAN-06:10
February 0.484985E+09 743.90 01-FEB-07:10 0.155533E+10 1072.05 01-FEB-06:10
March 0.536068E+09 743.90 01-MAR-17:00 0.177377E+10 1072.05 01-MAR-06:10
April 0.417148E+09 703.67 03-APR-06:10 0.166339E+10 1072.05 03-APR-05:10
May 0.387830E+09 542.05 22-MAY-06:10 0.174521E+10 1072.05 01-MAY-05:10
June 0.380822E+09 636.79 30-JUN-06:10 0.171047E+10 1072.05 01-JUN-05:10
July 0.358159E+09 580.64 03-JUL-06:10 0.169812E+10 1072.05 03-JUL-05:10
August 0.456071E+09 705.57 31-AUG-06:10 0.177377E+10 1072.05 01-AUG-05:10
September 0.445024E+09 743.90 27-SEP-06:10 0.166339E+10 1072.05 01-SEP-05:10
October 0.529965E+09 743.90 02-OCT-06:10 0.171665E+10 1072.05 02-OCT-05:10
November 0.587286E+09 743.90 01-NOV-06:10 0.167188E+10 1072.05 01-NOV-05:10
December 0.609695E+09 743.90 01-DEC-07:10 0.169812E+10 1072.05 01-DEC-06:10
             
Annual Sum or Average 0.578931E+10     0.203867E+11    
Minimum of Months 0.358159E+09 542.05   0.155533E+10 1072.05  
Maximum of Months 0.609695E+09 743.90   0.177377E+10 1072.05  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.300296E+09 237.73 02-JAN-07:10 0.358171E+09 223.68 02-JAN-06:10
February 0.273053E+09 237.73 01-FEB-07:10 0.324512E+09 223.68 01-FEB-06:10
March 0.322833E+09 237.73 01-MAR-07:10 0.370089E+09 223.68 01-MAR-06:10
April 0.291215E+09 237.73 03-APR-06:10 0.347059E+09 223.68 03-APR-05:10
May 0.311565E+09 237.73 01-MAY-06:10 0.364130E+09 223.68 01-MAY-05:10
June 0.309996E+09 237.73 01-JUN-06:10 0.356883E+09 223.68 01-JUN-05:10
July 0.292784E+09 237.73 03-JUL-06:10 0.354306E+09 223.68 03-JUL-05:10
August 0.322833E+09 237.73 01-AUG-06:10 0.370089E+09 223.68 01-AUG-05:10
September 0.291215E+09 237.73 01-SEP-06:10 0.347059E+09 223.68 01-SEP-05:10
October 0.300296E+09 237.73 02-OCT-06:10 0.358171E+09 223.68 02-OCT-05:10
November 0.294971E+09 237.73 01-NOV-06:10 0.348830E+09 223.68 01-NOV-05:10
December 0.292784E+09 237.73 01-DEC-07:10 0.354306E+09 223.68 01-DEC-06:10
             
Annual Sum or Average 0.360384E+10     0.425361E+10    
Minimum of Months 0.273053E+09 237.73   0.324512E+09 223.68  
Maximum of Months 0.322833E+09 237.73   0.370089E+09 223.68  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 59562052.71 47.15 02-JAN-07:10 80016946.16 49.97 02-JAN-06:10
February 54158465.60 47.15 01-FEB-07:10 72497368.03 49.97 01-FEB-06:10
March 64032035.76 47.15 01-MAR-07:10 82679380.52 49.97 01-MAR-06:10
April 57760857.00 47.15 03-APR-06:10 77534406.01 49.97 03-APR-05:10
May 61797044.24 47.15 01-MAY-06:10 81348163.34 49.97 01-MAY-05:10
June 61485842.88 47.15 01-JUN-06:10 79729115.42 49.97 01-JUN-05:10
July 58072058.36 47.15 03-JUL-06:10 79153453.93 49.97 03-JUL-05:10
August 64032035.76 47.15 01-AUG-06:10 82679380.52 49.97 01-AUG-05:10
September 57760857.00 47.15 01-SEP-06:10 77534406.01 49.97 01-SEP-05:10
October 59562052.71 47.15 02-OCT-06:10 80016946.16 49.97 02-OCT-05:10
November 58505854.18 47.15 01-NOV-06:10 77930173.28 49.97 01-NOV-05:10
December 58072058.36 47.15 01-DEC-07:10 79153453.93 49.97 01-DEC-06:10
             
Annual Sum or Average 0.714801E+09     0.950273E+09    
Minimum of Months 54158465.60 47.15   72497368.03 49.97  
Maximum of Months 64032035.76 47.15   82679380.52 49.97  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.234719E+09 185.38 02-JAN-07:10 0.565238E+09 352.99 02-JAN-06:10
February 0.213384E+09 185.38 01-FEB-07:10 0.512120E+09 352.99 01-FEB-06:10
March 0.252111E+09 185.38 01-MAR-07:10 0.584045E+09 352.99 01-MAR-06:10
April 0.227547E+09 185.38 03-APR-06:10 0.547701E+09 352.99 03-APR-05:10
May 0.243415E+09 185.38 01-MAY-06:10 0.574641E+09 352.99 01-MAY-05:10
June 0.242100E+09 185.38 01-JUN-06:10 0.563204E+09 352.99 01-JUN-05:10
July 0.228861E+09 185.38 03-JUL-06:10 0.559138E+09 352.99 03-JUL-05:10
August 0.252111E+09 185.38 01-AUG-06:10 0.584045E+09 352.99 01-AUG-05:10
September 0.227547E+09 185.38 01-SEP-06:10 0.547701E+09 352.99 01-SEP-05:10
October 0.234719E+09 185.38 02-OCT-06:10 0.565238E+09 352.99 02-OCT-05:10
November 0.230567E+09 185.38 01-NOV-06:10 0.550497E+09 352.99 01-NOV-05:10
December 0.228861E+09 185.38 01-DEC-07:10 0.559138E+09 352.99 01-DEC-06:10
             
Annual Sum or Average 0.281594E+10     0.671270E+10    
Minimum of Months 0.213384E+09 185.38   0.512120E+09 352.99  
Maximum of Months 0.252111E+09 185.38   0.584045E+09 352.99  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.247759E+09 195.68 02-JAN-07:10 0.596640E+09 372.60 02-JAN-06:10
February 0.225238E+09 195.68 01-FEB-07:10 0.540571E+09 372.60 01-FEB-06:10
March 0.266117E+09 195.68 01-MAR-07:10 0.616492E+09 372.60 01-MAR-06:10
April 0.240188E+09 195.68 03-APR-06:10 0.578129E+09 372.60 03-APR-05:10
May 0.256938E+09 195.68 01-MAY-06:10 0.606566E+09 372.60 01-MAY-05:10
June 0.255550E+09 195.68 01-JUN-06:10 0.594494E+09 372.60 01-JUN-05:10
July 0.241576E+09 195.68 03-JUL-06:10 0.590201E+09 372.60 03-JUL-05:10
August 0.266117E+09 195.68 01-AUG-06:10 0.616492E+09 372.60 01-AUG-05:10
September 0.240188E+09 195.68 01-SEP-06:10 0.578129E+09 372.60 01-SEP-05:10
October 0.247759E+09 195.68 02-OCT-06:10 0.596640E+09 372.60 02-OCT-05:10
November 0.243376E+09 195.68 01-NOV-06:10 0.581080E+09 372.60 01-NOV-05:10
December 0.241576E+09 195.68 01-DEC-07:10 0.590201E+09 372.60 01-DEC-06:10
             
Annual Sum or Average 0.297238E+10     0.708563E+10    
Minimum of Months 0.225238E+09 195.68   0.540571E+09 372.60  
Maximum of Months 0.266117E+09 195.68   0.616492E+09 372.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 16240630.93 12.86 02-JAN-07:10 8911442.72 5.57 02-JAN-06:10
February 14767248.81 12.86 01-FEB-07:10 8073991.50 5.57 01-FEB-06:10
March 17459449.66 12.86 01-MAR-07:10 9207956.55 5.57 01-MAR-06:10
April 15749503.56 12.86 03-APR-06:10 8634963.61 5.57 03-APR-05:10
May 16850040.30 12.86 01-MAY-06:10 9059699.64 5.57 01-MAY-05:10
June 16765185.83 12.86 01-JUN-06:10 8879387.17 5.57 01-JUN-05:10
July 15834358.03 12.86 03-JUL-06:10 8815276.07 5.57 03-JUL-05:10
August 17459449.66 12.86 01-AUG-06:10 9207956.55 5.57 01-AUG-05:10
September 15749503.56 12.86 01-SEP-06:10 8634963.61 5.57 01-SEP-05:10
October 16240630.93 12.86 02-OCT-06:10 8911442.72 5.57 02-OCT-05:10
November 15952640.01 12.86 01-NOV-06:10 8679039.99 5.57 01-NOV-05:10
December 15834358.03 12.86 01-DEC-07:10 8815276.07 5.57 01-DEC-06:10
             
Annual Sum or Average 0.194903E+09     0.105831E+09    
Minimum of Months 14767248.81 12.86   8073991.50 5.57  
Maximum of Months 17459449.66 12.86   9207956.55 5.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 34801352.00 27.55 02-JAN-07:10 19095812.75 11.93 02-JAN-06:10
February 31644104.58 27.55 01-FEB-07:10 17301287.18 11.93 01-FEB-06:10
March 37413106.41 27.55 01-MAR-07:10 19731195.01 11.93 01-MAR-06:10
April 33748936.20 27.55 03-APR-06:10 18503361.72 11.93 03-APR-05:10
May 36107229.21 27.55 01-MAY-06:10 19413503.88 11.93 01-MAY-05:10
June 35925398.20 27.55 01-JUN-06:10 19027122.77 11.93 01-JUN-05:10
July 33930767.20 27.55 03-JUL-06:10 18889742.83 11.93 03-JUL-05:10
August 37413106.41 27.55 01-AUG-06:10 19731195.01 11.93 01-AUG-05:10
September 33748936.20 27.55 01-SEP-06:10 18503361.72 11.93 01-SEP-05:10
October 34801352.00 27.55 02-OCT-06:10 19095812.75 11.93 02-OCT-05:10
November 34184228.60 27.55 01-NOV-06:10 18597810.44 11.93 01-NOV-05:10
December 33930767.20 27.55 01-DEC-07:10 18889742.83 11.93 01-DEC-06:10
             
Annual Sum or Average 0.417649E+09     0.226780E+09    
Minimum of Months 31644104.58 27.55   17301287.18 11.93  
Maximum of Months 37413106.41 27.55   19731195.01 11.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 41761622.40 33.06 02-JAN-07:10 22915070.46 14.31 02-JAN-06:10
February 37972925.50 33.06 01-FEB-07:10 20761630.83 14.31 01-FEB-06:10
March 44895727.70 33.06 01-MAR-07:10 23677532.33 14.31 01-MAR-06:10
April 40498723.44 33.06 03-APR-06:10 22204126.27 14.31 03-APR-05:10
May 43328675.05 33.06 01-MAY-06:10 23296301.39 14.31 01-MAY-05:10
June 43110477.85 33.06 01-JUN-06:10 22832642.15 14.31 01-JUN-05:10
July 40716920.64 33.06 03-JUL-06:10 22667785.52 14.31 03-JUL-05:10
August 44895727.70 33.06 01-AUG-06:10 23677532.33 14.31 01-AUG-05:10
September 40498723.44 33.06 01-SEP-06:10 22204126.27 14.31 01-SEP-05:10
October 41761622.40 33.06 02-OCT-06:10 22915070.46 14.31 02-OCT-05:10
November 41021074.32 33.06 01-NOV-06:10 22317465.20 14.31 01-NOV-05:10
December 40716920.64 33.06 01-DEC-07:10 22667785.52 14.31 01-DEC-06:10
             
Annual Sum or Average 0.501179E+09     0.272137E+09    
Minimum of Months 37972925.50 33.06   20761630.83 14.31  
Maximum of Months 44895727.70 33.06   23677532.33 14.31  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 36541419.60 28.93 02-JAN-07:10 20050587.52 12.52 02-JAN-06:10
February 33226309.81 28.93 01-FEB-07:10 18166337.17 12.52 01-FEB-06:10
March 39283761.73 28.93 01-MAR-07:10 20717738.37 12.52 01-MAR-06:10
April 35436383.01 28.93 03-APR-06:10 19428514.44 12.52 03-APR-05:10
May 37912590.67 28.93 01-MAY-06:10 20384162.95 12.52 01-MAY-05:10
June 37721668.12 28.93 01-JUN-06:10 19978463.11 12.52 01-JUN-05:10
July 35627305.56 28.93 03-JUL-06:10 19834214.28 12.52 03-JUL-05:10
August 39283761.73 28.93 01-AUG-06:10 20717738.37 12.52 01-AUG-05:10
September 35436383.01 28.93 01-SEP-06:10 19428514.44 12.52 01-SEP-05:10
October 36541419.60 28.93 02-OCT-06:10 20050587.52 12.52 02-OCT-05:10
November 35893440.03 28.93 01-NOV-06:10 19527685.51 12.52 01-NOV-05:10
December 35627305.56 28.93 01-DEC-07:10 19834214.28 12.52 01-DEC-06:10
             
Annual Sum or Average 0.438532E+09     0.238119E+09    
Minimum of Months 33226309.81 28.93   18166337.17 12.52  
Maximum of Months 39283761.73 28.93   20717738.37 12.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.122431E+10 966.95 02-JAN-07:10 0.243541E+10 1520.91 02-JAN-06:10
February 0.111302E+10 966.95 01-FEB-07:10 0.220654E+10 1520.91 01-FEB-06:10
March 0.131502E+10 966.95 01-MAR-07:10 0.251644E+10 1520.91 01-MAR-06:10
April 0.118689E+10 966.95 03-APR-06:10 0.235985E+10 1520.91 03-APR-05:10
May 0.126967E+10 966.95 01-MAY-06:10 0.247592E+10 1520.91 01-MAY-05:10
June 0.126281E+10 966.95 01-JUN-06:10 0.242665E+10 1520.91 01-JUN-05:10
July 0.119375E+10 966.95 03-JUL-06:10 0.240913E+10 1520.91 03-JUL-05:10
August 0.131502E+10 966.95 01-AUG-06:10 0.251644E+10 1520.91 01-AUG-05:10
September 0.118689E+10 966.95 01-SEP-06:10 0.235985E+10 1520.91 01-SEP-05:10
October 0.122431E+10 966.95 02-OCT-06:10 0.243541E+10 1520.91 02-OCT-05:10
November 0.120265E+10 966.95 01-NOV-06:10 0.237189E+10 1520.91 01-NOV-05:10
December 0.119375E+10 966.95 01-DEC-07:10 0.240913E+10 1520.91 01-DEC-06:10
             
Annual Sum or Average 0.146881E+11     0.289226E+11    
Minimum of Months 0.111302E+10 966.95   0.220654E+10 1520.91  
Maximum of Months 0.131502E+10 966.95   0.251644E+10 1520.91  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.444055E+09 351.53 02-JAN-07:10 0.529636E+09 330.76 02-JAN-06:10
February 0.403770E+09 351.53 01-FEB-07:10 0.479864E+09 330.76 01-FEB-06:10
March 0.477381E+09 351.53 01-MAR-07:10 0.547259E+09 330.76 01-MAR-06:10
April 0.430627E+09 351.53 03-APR-06:10 0.513204E+09 330.76 03-APR-05:10
May 0.460718E+09 351.53 01-MAY-06:10 0.538448E+09 330.76 01-MAY-05:10
June 0.458398E+09 351.53 01-JUN-06:10 0.527731E+09 330.76 01-JUN-05:10
July 0.432947E+09 351.53 03-JUL-06:10 0.523921E+09 330.76 03-JUL-05:10
August 0.477381E+09 351.53 01-AUG-06:10 0.547259E+09 330.76 01-AUG-05:10
September 0.430627E+09 351.53 01-SEP-06:10 0.513204E+09 330.76 01-SEP-05:10
October 0.444055E+09 351.53 02-OCT-06:10 0.529636E+09 330.76 02-OCT-05:10
November 0.436181E+09 351.53 01-NOV-06:10 0.515824E+09 330.76 01-NOV-05:10
December 0.432947E+09 351.53 01-DEC-07:10 0.523921E+09 330.76 01-DEC-06:10
             
Annual Sum or Average 0.532909E+10     0.628991E+10    
Minimum of Months 0.403770E+09 351.53   0.479864E+09 330.76  
Maximum of Months 0.477381E+09 351.53   0.547259E+09 330.76  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 25526594.02 20.21 02-JAN-07:10 34293067.55 21.42 02-JAN-06:10
February 23210770.97 20.21 01-FEB-07:10 31070382.70 21.42 01-FEB-06:10
March 27442301.04 20.21 01-MAR-07:10 35434113.87 21.42 01-MAR-06:10
April 24754653.00 20.21 03-APR-06:10 33229118.96 21.42 03-APR-05:10
May 26484447.53 20.21 01-MAY-06:10 34863590.71 21.42 01-MAY-05:10
June 26351075.52 20.21 01-JUN-06:10 34169711.20 21.42 01-JUN-05:10
July 24888025.01 20.21 03-JUL-06:10 33922998.48 21.42 03-JUL-05:10
August 27442301.04 20.21 01-AUG-06:10 35434113.87 21.42 01-AUG-05:10
September 24754653.00 20.21 01-SEP-06:10 33229118.96 21.42 01-SEP-05:10
October 25526594.02 20.21 02-OCT-06:10 34293067.55 21.42 02-OCT-05:10
November 25073937.51 20.21 01-NOV-06:10 33398733.96 21.42 01-NOV-05:10
December 24888025.01 20.21 01-DEC-07:10 33922998.48 21.42 01-DEC-06:10
             
Annual Sum or Average 0.306343E+09     0.407261E+09    
Minimum of Months 23210770.97 20.21   31070382.70 21.42  
Maximum of Months 27442301.04 20.21   35434113.87 21.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 2 X-RAY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.750204E+09 593.89 02-JAN-07:10 0.142742E+11 8914.22 02-JAN-06:10
February 0.682144E+09 593.89 01-FEB-07:10 0.129327E+11 8914.22 01-FEB-06:10
March 0.806505E+09 593.89 01-MAR-07:10 0.147491E+11 8914.22 01-MAR-06:10
April 0.727518E+09 593.89 03-APR-06:10 0.138313E+11 8914.22 03-APR-05:10
May 0.778355E+09 593.89 01-MAY-06:10 0.145116E+11 8914.22 01-MAY-05:10
June 0.774435E+09 593.89 01-JUN-06:10 0.142228E+11 8914.22 01-JUN-05:10
July 0.731437E+09 593.89 03-JUL-06:10 0.141201E+11 8914.22 03-JUL-05:10
August 0.806505E+09 593.89 01-AUG-06:10 0.147491E+11 8914.22 01-AUG-05:10
September 0.727518E+09 593.89 01-SEP-06:10 0.138313E+11 8914.22 01-SEP-05:10
October 0.750204E+09 593.89 02-OCT-06:10 0.142742E+11 8914.22 02-OCT-05:10
November 0.736901E+09 593.89 01-NOV-06:10 0.139019E+11 8914.22 01-NOV-05:10
December 0.731437E+09 593.89 01-DEC-07:10 0.141201E+11 8914.22 01-DEC-06:10
             
Annual Sum or Average 0.900317E+10     0.169518E+12    
Minimum of Months 0.682144E+09 593.89   0.129327E+11 8914.22  
Maximum of Months 0.806505E+09 593.89   0.147491E+11 8914.22  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 30426579.93 24.03 02-JAN-07:10 73271509.94 45.76 02-JAN-06:10
February 27660832.76 24.03 01-FEB-07:10 66385832.97 45.76 01-FEB-06:10
March 32681047.04 24.03 01-MAR-07:10 75709500.82 45.76 01-MAR-06:10
April 29496781.69 24.03 03-APR-06:10 70998248.16 45.76 03-APR-05:10
May 31553813.48 24.03 01-MAY-06:10 74490505.38 45.76 01-MAY-05:10
June 31383386.80 24.03 01-JUN-06:10 73007943.35 45.76 01-JUN-05:10
July 29667208.38 24.03 03-JUL-06:10 72480810.19 45.76 03-JUL-05:10
August 32681047.04 24.03 01-AUG-06:10 75709500.82 45.76 01-AUG-05:10
September 29496781.69 24.03 01-SEP-06:10 70998248.16 45.76 01-SEP-05:10
October 30426579.93 24.03 02-OCT-06:10 73271509.94 45.76 02-OCT-05:10
November 29888291.23 24.03 01-NOV-06:10 71360652.21 45.76 01-NOV-05:10
December 29667208.38 24.03 01-DEC-07:10 72480810.19 45.76 01-DEC-06:10
             
Annual Sum or Average 0.365030E+09     0.870165E+09    
Minimum of Months 27660832.76 24.03   66385832.97 45.76  
Maximum of Months 32681047.04 24.03   75709500.82 45.76  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.197003E+09 155.96 02-JAN-07:10 0.234971E+09 146.74 02-JAN-06:10
February 0.179130E+09 155.96 01-FEB-07:10 0.212889E+09 146.74 01-FEB-06:10
March 0.211788E+09 155.96 01-MAR-07:10 0.242789E+09 146.74 01-MAR-06:10
April 0.191045E+09 155.96 03-APR-06:10 0.227681E+09 146.74 03-APR-05:10
May 0.204395E+09 155.96 01-MAY-06:10 0.238880E+09 146.74 01-MAY-05:10
June 0.203366E+09 155.96 01-JUN-06:10 0.234125E+09 146.74 01-JUN-05:10
July 0.192075E+09 155.96 03-JUL-06:10 0.232435E+09 146.74 03-JUL-05:10
August 0.211788E+09 155.96 01-AUG-06:10 0.242789E+09 146.74 01-AUG-05:10
September 0.191045E+09 155.96 01-SEP-06:10 0.227681E+09 146.74 01-SEP-05:10
October 0.197003E+09 155.96 02-OCT-06:10 0.234971E+09 146.74 02-OCT-05:10
November 0.193510E+09 155.96 01-NOV-06:10 0.228843E+09 146.74 01-NOV-05:10
December 0.192075E+09 155.96 01-DEC-07:10 0.232435E+09 146.74 01-DEC-06:10
             
Annual Sum or Average 0.236422E+10     0.279049E+10    
Minimum of Months 0.179130E+09 155.96   0.212889E+09 146.74  
Maximum of Months 0.211788E+09 155.96   0.242789E+09 146.74  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 78239776.95 61.79 02-JAN-07:10 0.188413E+09 117.66 02-JAN-06:10
February 71127855.67 61.79 01-FEB-07:10 0.170707E+09 117.66 01-FEB-06:10
March 84036978.11 61.79 01-MAR-07:10 0.194682E+09 117.66 01-MAR-06:10
April 75848867.21 61.79 03-APR-06:10 0.182567E+09 117.66 03-APR-05:10
May 81138377.53 61.79 01-MAY-06:10 0.191547E+09 117.66 01-MAY-05:10
June 80700137.49 61.79 01-JUN-06:10 0.187735E+09 117.66 01-JUN-05:10
July 76287107.26 61.79 03-JUL-06:10 0.186379E+09 117.66 03-JUL-05:10
August 84036978.11 61.79 01-AUG-06:10 0.194682E+09 117.66 01-AUG-05:10
September 75848867.21 61.79 01-SEP-06:10 0.182567E+09 117.66 01-SEP-05:10
October 78239776.95 61.79 02-OCT-06:10 0.188413E+09 117.66 02-OCT-05:10
November 76855606.03 61.79 01-NOV-06:10 0.183499E+09 117.66 01-NOV-05:10
December 76287107.26 61.79 01-DEC-07:10 0.186379E+09 117.66 01-DEC-06:10
             
Annual Sum or Average 0.938647E+09     0.223757E+10    
Minimum of Months 71127855.67 61.79   0.170707E+09 117.66  
Maximum of Months 84036978.11 61.79   0.194682E+09 117.66  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 18270709.80 14.46 02-JAN-07:10 10025293.76 6.26 02-JAN-06:10
February 16613154.91 14.46 01-FEB-07:10 9083168.58 6.26 01-FEB-06:10
March 19641880.87 14.46 01-MAR-07:10 10358869.18 6.26 01-MAR-06:10
April 17718191.50 14.46 03-APR-06:10 9714257.22 6.26 03-APR-05:10
May 18956295.33 14.46 01-MAY-06:10 10192081.47 6.26 01-MAY-05:10
June 18860834.06 14.46 01-JUN-06:10 9989231.55 6.26 01-JUN-05:10
July 17813652.78 14.46 03-JUL-06:10 9917107.14 6.26 03-JUL-05:10
August 19641880.87 14.46 01-AUG-06:10 10358869.18 6.26 01-AUG-05:10
September 17718191.50 14.46 01-SEP-06:10 9714257.22 6.26 01-SEP-05:10
October 18270709.80 14.46 02-OCT-06:10 10025293.76 6.26 02-OCT-05:10
November 17946720.01 14.46 01-NOV-06:10 9763842.76 6.26 01-NOV-05:10
December 17813652.78 14.46 01-DEC-07:10 9917107.14 6.26 01-DEC-06:10
             
Annual Sum or Average 0.219266E+09     0.119059E+09    
Minimum of Months 16613154.91 14.46   9083168.58 6.26  
Maximum of Months 19641880.87 14.46   10358869.18 6.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 LOCKER

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 80491104.00 63.72 02-JAN-07:10 0.570931E+09 356.55 02-JAN-06:10
February 73188792.00 63.72 01-FEB-07:10 0.517278E+09 356.55 01-FEB-06:10
March 86531760.00 63.72 01-MAR-07:10 0.589928E+09 356.55 01-MAR-06:10
April 78057000.00 63.72 03-APR-06:10 0.553218E+09 356.55 03-APR-05:10
May 83511432.00 63.72 01-MAY-06:10 0.580429E+09 356.55 01-MAY-05:10
June 83090880.00 63.72 01-JUN-06:10 0.568877E+09 356.55 01-JUN-05:10
July 78477552.00 63.72 03-JUL-06:10 0.564770E+09 356.55 03-JUL-05:10
August 86531760.00 63.72 01-AUG-06:10 0.589928E+09 356.55 01-AUG-05:10
September 78057000.00 63.72 01-SEP-06:10 0.553218E+09 356.55 01-SEP-05:10
October 80491104.00 63.72 02-OCT-06:10 0.570931E+09 356.55 02-OCT-05:10
November 79063776.00 63.72 01-NOV-06:10 0.556042E+09 356.55 01-NOV-05:10
December 78477552.00 63.72 01-DEC-07:10 0.564770E+09 356.55 01-DEC-06:10
             
Annual Sum or Average 0.965970E+09     0.678032E+10    
Minimum of Months 73188792.00 63.72   0.517278E+09 356.55  
Maximum of Months 86531760.00 63.72   0.589928E+09 356.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.399971E+09 403.03 02-JAN-07:10 0.361114E+10 2255.16 02-JAN-06:10
February 0.335878E+09 403.03 01-FEB-07:10 0.327178E+10 2255.16 01-FEB-06:10
March 0.374211E+09 403.03 01-MAR-17:00 0.373129E+10 2255.16 01-MAR-06:10
April 0.313433E+09 358.53 03-APR-06:10 0.349910E+10 2255.16 03-APR-05:10
May 0.312333E+09 241.36 22-MAY-06:10 0.367122E+10 2255.16 01-MAY-05:10
June 0.306246E+09 277.05 30-JUN-06:10 0.359815E+10 2255.16 01-JUN-05:10
July 0.291139E+09 256.58 11-JUL-16:00 0.357217E+10 2255.16 03-JUL-05:10
August 0.340264E+09 364.71 31-AUG-06:10 0.373129E+10 2255.16 01-AUG-05:10
September 0.324835E+09 403.03 27-SEP-06:10 0.349910E+10 2255.16 01-SEP-05:10
October 0.364281E+09 403.03 02-OCT-06:10 0.361114E+10 2255.16 02-OCT-05:10
November 0.387760E+09 403.03 01-NOV-06:10 0.351696E+10 2255.16 01-NOV-05:10
December 0.398705E+09 403.03 01-DEC-07:10 0.357217E+10 2255.16 01-DEC-06:10
             
Annual Sum or Average 0.414906E+10     0.428855E+11    
Minimum of Months 0.291139E+09 241.36   0.327178E+10 2255.16  
Maximum of Months 0.399971E+09 403.03   0.373129E+10 2255.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 90761223.17 71.85 02-JAN-07:10 0.121931E+09 76.15 02-JAN-06:10
February 82527185.67 71.85 01-FEB-07:10 0.110472E+09 76.15 01-FEB-06:10
March 97572625.93 71.85 01-MAR-07:10 0.125988E+09 76.15 01-MAR-06:10
April 88016544.01 71.85 03-APR-06:10 0.118148E+09 76.15 03-APR-05:10
May 94166924.55 71.85 01-MAY-06:10 0.123959E+09 76.15 01-MAY-05:10
June 93692712.97 71.85 01-JUN-06:10 0.121492E+09 76.15 01-JUN-05:10
July 88490755.59 71.85 03-JUL-06:10 0.120615E+09 76.15 03-JUL-05:10
August 97572625.93 71.85 01-AUG-06:10 0.125988E+09 76.15 01-AUG-05:10
September 88016544.01 71.85 01-SEP-06:10 0.118148E+09 76.15 01-SEP-05:10
October 90761223.17 71.85 02-OCT-06:10 0.121931E+09 76.15 02-OCT-05:10
November 89151777.80 71.85 01-NOV-06:10 0.118751E+09 76.15 01-NOV-05:10
December 88490755.59 71.85 01-DEC-07:10 0.120615E+09 76.15 01-DEC-06:10
             
Annual Sum or Average 0.108922E+10     0.144804E+10    
Minimum of Months 82527185.67 71.85   0.110472E+09 76.15  
Maximum of Months 97572625.93 71.85   0.125988E+09 76.15  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.557071E+09 441.00 02-JAN-07:10 0.277553E+10 1733.32 02-JAN-06:10
February 0.506533E+09 441.00 01-FEB-07:10 0.251470E+10 1733.32 01-FEB-06:10
March 0.598878E+09 441.00 01-MAR-07:10 0.286788E+10 1733.32 01-MAR-06:10
April 0.540225E+09 441.00 03-APR-06:10 0.268942E+10 1733.32 03-APR-05:10
May 0.577975E+09 441.00 01-MAY-06:10 0.282171E+10 1733.32 01-MAY-05:10
June 0.575064E+09 441.00 01-JUN-06:10 0.276555E+10 1733.32 01-JUN-05:10
July 0.543136E+09 441.00 03-JUL-06:10 0.274558E+10 1733.32 03-JUL-05:10
August 0.598878E+09 441.00 01-AUG-06:10 0.286788E+10 1733.32 01-AUG-05:10
September 0.540225E+09 441.00 01-SEP-06:10 0.268942E+10 1733.32 01-SEP-05:10
October 0.557071E+09 441.00 02-OCT-06:10 0.277553E+10 1733.32 02-OCT-05:10
November 0.547193E+09 441.00 01-NOV-06:10 0.270315E+10 1733.32 01-NOV-05:10
December 0.543136E+09 441.00 01-DEC-07:10 0.274558E+10 1733.32 01-DEC-06:10
             
Annual Sum or Average 0.668538E+10     0.329619E+11    
Minimum of Months 0.506533E+09 441.00   0.251470E+10 1733.32  
Maximum of Months 0.598878E+09 441.00   0.286788E+10 1733.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.159732E+09 126.45 02-JAN-07:10 0.190517E+09 118.98 02-JAN-06:10
February 0.145241E+09 126.45 01-FEB-07:10 0.172613E+09 118.98 01-FEB-06:10
March 0.171720E+09 126.45 01-MAR-07:10 0.196856E+09 118.98 01-MAR-06:10
April 0.154902E+09 126.45 03-APR-06:10 0.184606E+09 118.98 03-APR-05:10
May 0.165726E+09 126.45 01-MAY-06:10 0.193686E+09 118.98 01-MAY-05:10
June 0.164891E+09 126.45 01-JUN-06:10 0.189831E+09 118.98 01-JUN-05:10
July 0.155736E+09 126.45 03-JUL-06:10 0.188461E+09 118.98 03-JUL-05:10
August 0.171720E+09 126.45 01-AUG-06:10 0.196856E+09 118.98 01-AUG-05:10
September 0.154902E+09 126.45 01-SEP-06:10 0.184606E+09 118.98 01-SEP-05:10
October 0.159732E+09 126.45 02-OCT-06:10 0.190517E+09 118.98 02-OCT-05:10
November 0.156900E+09 126.45 01-NOV-06:10 0.185548E+09 118.98 01-NOV-05:10
December 0.155736E+09 126.45 01-DEC-07:10 0.188461E+09 118.98 01-DEC-06:10
             
Annual Sum or Average 0.191694E+10     0.226256E+10    
Minimum of Months 0.145241E+09 126.45   0.172613E+09 118.98  
Maximum of Months 0.171720E+09 126.45   0.196856E+09 118.98  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.193104E+10 1737.08 02-JAN-07:10 0.529649E+10 3307.66 02-JAN-06:10
February 0.166304E+10 1737.08 01-FEB-07:10 0.479875E+10 3307.66 01-FEB-06:10
March 0.189329E+10 1737.08 01-MAR-17:00 0.547272E+10 3307.66 01-MAR-06:10
April 0.162293E+10 1653.49 03-APR-06:10 0.513216E+10 3307.66 03-APR-05:10
May 0.160475E+10 1284.93 22-MAY-06:10 0.538460E+10 3307.66 01-MAY-05:10
June 0.156214E+10 1519.92 30-JUN-06:10 0.527743E+10 3307.66 01-JUN-05:10
July 0.148659E+10 1315.05 11-JUL-16:00 0.523933E+10 3307.66 03-JUL-05:10
August 0.173382E+10 1664.52 31-AUG-06:10 0.547272E+10 3307.66 01-AUG-05:10
September 0.165689E+10 1737.08 27-SEP-06:10 0.513216E+10 3307.66 01-SEP-05:10
October 0.182514E+10 1737.08 02-OCT-06:10 0.529649E+10 3307.66 02-OCT-05:10
November 0.187871E+10 1737.08 01-NOV-06:10 0.515836E+10 3307.66 01-NOV-05:10
December 0.190178E+10 1737.08 01-DEC-07:10 0.523933E+10 3307.66 01-DEC-06:10
             
Annual Sum or Average 0.207601E+11     0.629005E+11    
Minimum of Months 0.148659E+10 1284.93   0.479875E+10 3307.66  
Maximum of Months 0.193104E+10 1737.08   0.547272E+10 3307.66  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.444055E+09 351.53 02-JAN-07:10 0.529636E+09 330.76 02-JAN-06:10
February 0.403770E+09 351.53 01-FEB-07:10 0.479864E+09 330.76 01-FEB-06:10
March 0.477381E+09 351.53 01-MAR-07:10 0.547259E+09 330.76 01-MAR-06:10
April 0.430627E+09 351.53 03-APR-06:10 0.513204E+09 330.76 03-APR-05:10
May 0.460718E+09 351.53 01-MAY-06:10 0.538448E+09 330.76 01-MAY-05:10
June 0.458398E+09 351.53 01-JUN-06:10 0.527731E+09 330.76 01-JUN-05:10
July 0.432947E+09 351.53 03-JUL-06:10 0.523921E+09 330.76 03-JUL-05:10
August 0.477381E+09 351.53 01-AUG-06:10 0.547259E+09 330.76 01-AUG-05:10
September 0.430627E+09 351.53 01-SEP-06:10 0.513204E+09 330.76 01-SEP-05:10
October 0.444055E+09 351.53 02-OCT-06:10 0.529636E+09 330.76 02-OCT-05:10
November 0.436181E+09 351.53 01-NOV-06:10 0.515824E+09 330.76 01-NOV-05:10
December 0.432947E+09 351.53 01-DEC-07:10 0.523921E+09 330.76 01-DEC-06:10
             
Annual Sum or Average 0.532909E+10     0.628991E+10    
Minimum of Months 0.403770E+09 351.53   0.479864E+09 330.76  
Maximum of Months 0.477381E+09 351.53   0.547259E+09 330.76  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 25526594.02 20.21 02-JAN-07:10 34293067.55 21.42 02-JAN-06:10
February 23210770.97 20.21 01-FEB-07:10 31070382.70 21.42 01-FEB-06:10
March 27442301.04 20.21 01-MAR-07:10 35434113.87 21.42 01-MAR-06:10
April 24754653.00 20.21 03-APR-06:10 33229118.96 21.42 03-APR-05:10
May 26484447.53 20.21 01-MAY-06:10 34863590.71 21.42 01-MAY-05:10
June 26351075.52 20.21 01-JUN-06:10 34169711.20 21.42 01-JUN-05:10
July 24888025.01 20.21 03-JUL-06:10 33922998.48 21.42 03-JUL-05:10
August 27442301.04 20.21 01-AUG-06:10 35434113.87 21.42 01-AUG-05:10
September 24754653.00 20.21 01-SEP-06:10 33229118.96 21.42 01-SEP-05:10
October 25526594.02 20.21 02-OCT-06:10 34293067.55 21.42 02-OCT-05:10
November 25073937.51 20.21 01-NOV-06:10 33398733.96 21.42 01-NOV-05:10
December 24888025.01 20.21 01-DEC-07:10 33922998.48 21.42 01-DEC-06:10
             
Annual Sum or Average 0.306343E+09     0.407261E+09    
Minimum of Months 23210770.97 20.21   31070382.70 21.42  
Maximum of Months 27442301.04 20.21   35434113.87 21.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.104904E+10 830.47 02-JAN-07:10 0.309350E+10 1931.89 02-JAN-06:10
February 0.953873E+09 830.47 01-FEB-07:10 0.280279E+10 1931.89 01-FEB-06:10
March 0.112777E+10 830.47 01-MAR-07:10 0.319643E+10 1931.89 01-MAR-06:10
April 0.101732E+10 830.47 03-APR-06:10 0.299752E+10 1931.89 03-APR-05:10
May 0.108841E+10 830.47 01-MAY-06:10 0.314497E+10 1931.89 01-MAY-05:10
June 0.108293E+10 830.47 01-JUN-06:10 0.308237E+10 1931.89 01-JUN-05:10
July 0.102280E+10 830.47 03-JUL-06:10 0.306012E+10 1931.89 03-JUL-05:10
August 0.112777E+10 830.47 01-AUG-06:10 0.319643E+10 1931.89 01-AUG-05:10
September 0.101732E+10 830.47 01-SEP-06:10 0.299752E+10 1931.89 01-SEP-05:10
October 0.104904E+10 830.47 02-OCT-06:10 0.309350E+10 1931.89 02-OCT-05:10
November 0.103044E+10 830.47 01-NOV-06:10 0.301283E+10 1931.89 01-NOV-05:10
December 0.102280E+10 830.47 01-DEC-07:10 0.306012E+10 1931.89 01-DEC-06:10
             
Annual Sum or Average 0.125895E+11     0.367381E+11    
Minimum of Months 0.953873E+09 830.47   0.280279E+10 1931.89  
Maximum of Months 0.112777E+10 830.47   0.319643E+10 1931.89  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.477719E+09 378.18 02-JAN-07:10 0.140873E+10 879.75 02-JAN-06:10
February 0.434379E+09 378.18 01-FEB-07:10 0.127635E+10 879.75 01-FEB-06:10
March 0.513570E+09 378.18 01-MAR-07:10 0.145561E+10 879.75 01-MAR-06:10
April 0.463272E+09 378.18 03-APR-06:10 0.136503E+10 879.75 03-APR-05:10
May 0.495645E+09 378.18 01-MAY-06:10 0.143217E+10 879.75 01-MAY-05:10
June 0.493149E+09 378.18 01-JUN-06:10 0.140367E+10 879.75 01-JUN-05:10
July 0.465768E+09 378.18 03-JUL-06:10 0.139353E+10 879.75 03-JUL-05:10
August 0.513570E+09 378.18 01-AUG-06:10 0.145561E+10 879.75 01-AUG-05:10
September 0.463272E+09 378.18 01-SEP-06:10 0.136503E+10 879.75 01-SEP-05:10
October 0.477719E+09 378.18 02-OCT-06:10 0.140873E+10 879.75 02-OCT-05:10
November 0.469248E+09 378.18 01-NOV-06:10 0.137199E+10 879.75 01-NOV-05:10
December 0.465768E+09 378.18 01-DEC-07:10 0.139353E+10 879.75 01-DEC-06:10
             
Annual Sum or Average 0.573308E+10     0.167300E+11    
Minimum of Months 0.434379E+09 378.18   0.127635E+10 879.75  
Maximum of Months 0.513570E+09 378.18   0.145561E+10 879.75  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 39708035.14 31.43 02-JAN-07:10 53344630.77 33.31 02-JAN-06:10
February 36105643.73 31.43 01-FEB-07:10 48331578.69 33.31 01-FEB-06:10
March 42688023.84 31.43 01-MAR-07:10 55119587.01 33.31 01-MAR-06:10
April 38507238.00 31.43 03-APR-06:10 51689604.01 33.31 03-APR-05:10
May 41198029.49 31.43 01-MAY-06:10 54232108.89 33.31 01-MAY-05:10
June 40990561.92 31.43 01-JUN-06:10 53152743.61 33.31 01-JUN-05:10
July 38714705.57 31.43 03-JUL-06:10 52768969.29 33.31 03-JUL-05:10
August 42688023.84 31.43 01-AUG-06:10 55119587.01 33.31 01-AUG-05:10
September 38507238.00 31.43 01-SEP-06:10 51689604.01 33.31 01-SEP-05:10
October 39708035.14 31.43 02-OCT-06:10 53344630.77 33.31 02-OCT-05:10
November 39003902.79 31.43 01-NOV-06:10 51953448.85 33.31 01-NOV-05:10
December 38714705.57 31.43 01-DEC-07:10 52768969.29 33.31 01-DEC-06:10
             
Annual Sum or Average 0.476534E+09     0.633515E+09    
Minimum of Months 36105643.73 31.43   48331578.69 33.31  
Maximum of Months 42688023.84 31.43   55119587.01 33.31  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 31321216.80 24.80 02-JAN-07:10 17186263.19 10.73 02-JAN-06:10
February 28479694.13 24.80 01-FEB-07:10 15571187.20 10.73 01-FEB-06:10
March 33671795.77 24.80 01-MAR-07:10 17758108.28 10.73 01-MAR-06:10
April 30374042.58 24.80 03-APR-06:10 16653056.29 10.73 03-APR-05:10
May 32496506.29 24.80 01-MAY-06:10 17472185.74 10.73 01-MAY-05:10
June 32332858.38 24.80 01-JUN-06:10 17124442.10 10.73 01-JUN-05:10
July 30537690.48 24.80 03-JUL-06:10 17000799.92 10.73 03-JUL-05:10
August 33671795.77 24.80 01-AUG-06:10 17758108.28 10.73 01-AUG-05:10
September 30374042.58 24.80 01-SEP-06:10 16653056.29 10.73 01-SEP-05:10
October 31321216.80 24.80 02-OCT-06:10 17186263.19 10.73 02-OCT-05:10
November 30765805.74 24.80 01-NOV-06:10 16738060.29 10.73 01-NOV-05:10
December 30537690.48 24.80 01-DEC-07:10 17000799.92 10.73 01-DEC-06:10
             
Annual Sum or Average 0.375884E+09     0.204102E+09    
Minimum of Months 28479694.13 24.80   15571187.20 10.73  
Maximum of Months 33671795.77 24.80   17758108.28 10.73  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 24360946.40 19.29 02-JAN-07:10 13367164.08 8.35 02-JAN-06:10
February 22150873.21 19.29 01-FEB-07:10 12110987.24 8.35 01-FEB-06:10
March 26189174.49 19.29 01-MAR-07:10 13811934.83 8.35 01-MAR-06:10
April 23624255.34 19.29 03-APR-06:10 12952445.41 8.35 03-APR-05:10
May 25275060.45 19.29 01-MAY-06:10 13589549.46 8.35 01-MAY-05:10
June 25147778.74 19.29 01-JUN-06:10 13319080.76 8.35 01-JUN-05:10
July 23751537.04 19.29 03-JUL-06:10 13222914.11 8.35 03-JUL-05:10
August 26189174.49 19.29 01-AUG-06:10 13811934.83 8.35 01-AUG-05:10
September 23624255.34 19.29 01-SEP-06:10 12952445.41 8.35 01-SEP-05:10
October 24360946.40 19.29 02-OCT-06:10 13367164.08 8.35 02-OCT-05:10
November 23928960.02 19.29 01-NOV-06:10 13018559.98 8.35 01-NOV-05:10
December 23751537.04 19.29 01-DEC-07:10 13222914.11 8.35 01-DEC-06:10
             
Annual Sum or Average 0.292354E+09     0.158747E+09    
Minimum of Months 22150873.21 19.29   12110987.24 8.35  
Maximum of Months 26189174.49 19.29   13811934.83 8.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.757617E+09 599.76 02-JAN-07:10 0.830411E+09 518.59 02-JAN-06:10
February 0.688884E+09 599.76 01-FEB-07:10 0.752373E+09 518.59 01-FEB-06:10
March 0.814474E+09 599.76 01-MAR-07:10 0.858042E+09 518.59 01-MAR-06:10
April 0.734706E+09 599.76 03-APR-06:10 0.804647E+09 518.59 03-APR-05:10
May 0.786045E+09 599.76 01-MAY-06:10 0.844226E+09 518.59 01-MAY-05:10
June 0.782087E+09 599.76 01-JUN-06:10 0.827424E+09 518.59 01-JUN-05:10
July 0.738664E+09 599.76 03-JUL-06:10 0.821450E+09 518.59 03-JUL-05:10
August 0.814474E+09 599.76 01-AUG-06:10 0.858042E+09 518.59 01-AUG-05:10
September 0.734706E+09 599.76 01-SEP-06:10 0.804647E+09 518.59 01-SEP-05:10
October 0.757617E+09 599.76 02-OCT-06:10 0.830411E+09 518.59 02-OCT-05:10
November 0.744182E+09 599.76 01-NOV-06:10 0.808755E+09 518.59 01-NOV-05:10
December 0.738664E+09 599.76 01-DEC-07:10 0.821450E+09 518.59 01-DEC-06:10
             
Annual Sum or Average 0.909212E+10     0.986188E+10    
Minimum of Months 0.688884E+09 599.76   0.752373E+09 518.59  
Maximum of Months 0.814474E+09 599.76   0.858042E+09 518.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.657746E+09 520.70 02-JAN-07:10 0.395666E+10 2470.94 02-JAN-06:10
February 0.598074E+09 520.70 01-FEB-07:10 0.358484E+10 2470.94 01-FEB-06:10
March 0.707108E+09 520.70 01-MAR-07:10 0.408832E+10 2470.94 01-MAR-06:10
April 0.637855E+09 520.70 03-APR-06:10 0.383391E+10 2470.94 03-APR-05:10
May 0.682427E+09 520.70 01-MAY-06:10 0.402249E+10 2470.94 01-MAY-05:10
June 0.678990E+09 520.70 01-JUN-06:10 0.394243E+10 2470.94 01-JUN-05:10
July 0.641292E+09 520.70 03-JUL-06:10 0.391397E+10 2470.94 03-JUL-05:10
August 0.707108E+09 520.70 01-AUG-06:10 0.408832E+10 2470.94 01-AUG-05:10
September 0.637855E+09 520.70 01-SEP-06:10 0.383391E+10 2470.94 01-SEP-05:10
October 0.657746E+09 520.70 02-OCT-06:10 0.395666E+10 2470.94 02-OCT-05:10
November 0.646082E+09 520.70 01-NOV-06:10 0.385348E+10 2470.94 01-NOV-05:10
December 0.641292E+09 520.70 01-DEC-07:10 0.391397E+10 2470.94 01-DEC-06:10
             
Annual Sum or Average 0.789357E+10     0.469889E+11    
Minimum of Months 0.598074E+09 520.70   0.358484E+10 2470.94  
Maximum of Months 0.707108E+09 520.70   0.408832E+10 2470.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.334093E+09 264.48 02-JAN-07:10 0.200973E+10 1255.08 02-JAN-06:10
February 0.303783E+09 264.48 01-FEB-07:10 0.182087E+10 1255.08 01-FEB-06:10
March 0.359166E+09 264.48 01-MAR-07:10 0.207660E+10 1255.08 01-MAR-06:10
April 0.323990E+09 264.48 03-APR-06:10 0.194738E+10 1255.08 03-APR-05:10
May 0.346629E+09 264.48 01-MAY-06:10 0.204317E+10 1255.08 01-MAY-05:10
June 0.344884E+09 264.48 01-JUN-06:10 0.200250E+10 1255.08 01-JUN-05:10
July 0.325735E+09 264.48 03-JUL-06:10 0.198805E+10 1255.08 03-JUL-05:10
August 0.359166E+09 264.48 01-AUG-06:10 0.207660E+10 1255.08 01-AUG-05:10
September 0.323990E+09 264.48 01-SEP-06:10 0.194738E+10 1255.08 01-SEP-05:10
October 0.334093E+09 264.48 02-OCT-06:10 0.200973E+10 1255.08 02-OCT-05:10
November 0.328169E+09 264.48 01-NOV-06:10 0.195732E+10 1255.08 01-NOV-05:10
December 0.325735E+09 264.48 01-DEC-07:10 0.198805E+10 1255.08 01-DEC-06:10
             
Annual Sum or Average 0.400943E+10     0.238674E+11    
Minimum of Months 0.303783E+09 264.48   0.182087E+10 1255.08  
Maximum of Months 0.359166E+09 264.48   0.207660E+10 1255.08  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 62642433.61 49.59 02-JAN-07:10 34372526.38 21.47 02-JAN-06:10
February 56959388.25 49.59 01-FEB-07:10 31142374.40 21.47 01-FEB-06:10
March 67343591.54 49.59 01-MAR-07:10 35516216.56 21.47 01-MAR-06:10
April 60748085.15 49.59 03-APR-06:10 33306112.57 21.47 03-APR-05:10
May 64993012.57 49.59 01-MAY-06:10 34944371.47 21.47 01-MAY-05:10
June 64665716.77 49.59 01-JUN-06:10 34248884.20 21.47 01-JUN-05:10
July 61075380.96 49.59 03-JUL-06:10 34001599.84 21.47 03-JUL-05:10
August 67343591.54 49.59 01-AUG-06:10 35516216.56 21.47 01-AUG-05:10
September 60748085.15 49.59 01-SEP-06:10 33306112.57 21.47 01-SEP-05:10
October 62642433.61 49.59 02-OCT-06:10 34372526.38 21.47 02-OCT-05:10
November 61531611.48 49.59 01-NOV-06:10 33476120.57 21.47 01-NOV-05:10
December 61075380.96 49.59 01-DEC-07:10 34001599.84 21.47 01-DEC-06:10
             
Annual Sum or Average 0.751769E+09     0.408205E+09    
Minimum of Months 56959388.25 49.59   31142374.40 21.47  
Maximum of Months 67343591.54 49.59   35516216.56 21.47  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FLOOR 3 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.415830E+09 328.42 02-JAN-07:10 0.100138E+10 625.36 02-JAN-06:10
February 0.378031E+09 328.42 01-FEB-07:10 0.907273E+09 625.36 01-FEB-06:10
March 0.446641E+09 328.42 01-MAR-07:10 0.103470E+10 625.36 01-MAR-06:10
April 0.403123E+09 328.42 03-APR-06:10 0.970310E+09 625.36 03-APR-05:10
May 0.431235E+09 328.42 01-MAY-06:10 0.101804E+10 625.36 01-MAY-05:10
June 0.428906E+09 328.42 01-JUN-06:10 0.997776E+09 625.36 01-JUN-05:10
July 0.405452E+09 328.42 03-JUL-06:10 0.990572E+09 625.36 03-JUL-05:10
August 0.446641E+09 328.42 01-AUG-06:10 0.103470E+10 625.36 01-AUG-05:10
September 0.403123E+09 328.42 01-SEP-06:10 0.970310E+09 625.36 01-SEP-05:10
October 0.415830E+09 328.42 02-OCT-06:10 0.100138E+10 625.36 02-OCT-05:10
November 0.408473E+09 328.42 01-NOV-06:10 0.975263E+09 625.36 01-NOV-05:10
December 0.405452E+09 328.42 01-DEC-07:10 0.990572E+09 625.36 01-DEC-06:10
             
Annual Sum or Average 0.498874E+10     0.118923E+11    
Minimum of Months 0.378031E+09 328.42   0.907273E+09 625.36  
Maximum of Months 0.446641E+09 328.42   0.103470E+10 625.36  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: NE STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 89449998.53 70.81 02-JAN-07:10 0.106689E+09 66.63 02-JAN-06:10
February 81334917.91 70.81 01-FEB-07:10 96663157.38 66.63 01-FEB-06:10
March 96162997.15 70.81 01-MAR-07:10 0.110239E+09 66.63 01-MAR-06:10
April 86744971.66 70.81 03-APR-06:10 0.103379E+09 66.63 03-APR-05:10
May 92806497.84 70.81 01-MAY-06:10 0.108464E+09 66.63 01-MAY-05:10
June 92339137.17 70.81 01-JUN-06:10 0.106305E+09 66.63 01-JUN-05:10
July 87212332.32 70.81 03-JUL-06:10 0.105538E+09 66.63 03-JUL-05:10
August 96162997.15 70.81 01-AUG-06:10 0.110239E+09 66.63 01-AUG-05:10
September 86744971.66 70.81 01-SEP-06:10 0.103379E+09 66.63 01-SEP-05:10
October 89449998.53 70.81 02-OCT-06:10 0.106689E+09 66.63 02-OCT-05:10
November 87863804.76 70.81 01-NOV-06:10 0.103907E+09 66.63 01-NOV-05:10
December 87212332.32 70.81 01-DEC-07:10 0.105538E+09 66.63 01-DEC-06:10
             
Annual Sum or Average 0.107348E+10     0.126703E+10    
Minimum of Months 81334917.91 70.81   96663157.38 66.63  
Maximum of Months 96162997.15 70.81   0.110239E+09 66.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: NW ELEVATOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 74541665.44 59.01 02-JAN-07:10 88907770.82 55.52 02-JAN-06:10
February 67779098.26 59.01 01-FEB-07:10 80552679.05 55.52 01-FEB-06:10
March 80135830.96 59.01 01-MAR-07:10 91866032.98 55.52 01-MAR-06:10
April 72287476.38 59.01 03-APR-06:10 86149391.24 55.52 03-APR-05:10
May 77338748.20 59.01 01-MAY-06:10 90386901.90 55.52 01-MAY-05:10
June 76949280.98 59.01 01-JUN-06:10 88587958.69 55.52 01-JUN-05:10
July 72676943.60 59.01 03-JUL-06:10 87948334.44 55.52 03-JUL-05:10
August 80135830.96 59.01 01-AUG-06:10 91866032.98 55.52 01-AUG-05:10
September 72287476.38 59.01 01-SEP-06:10 86149391.24 55.52 01-SEP-05:10
October 74541665.44 59.01 02-OCT-06:10 88907770.82 55.52 02-OCT-05:10
November 73219837.30 59.01 01-NOV-06:10 86589132.91 55.52 01-NOV-05:10
December 72676943.60 59.01 01-DEC-07:10 87948334.44 55.52 01-DEC-06:10
             
Annual Sum or Average 0.894571E+09     0.105586E+10    
Minimum of Months 67779098.26 59.01   80552679.05 55.52  
Maximum of Months 80135830.96 59.01   91866032.98 55.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: NW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 0.102229E+09 80.93 02-JAN-07:10 0.121931E+09 76.15 02-JAN-06:10
February 92954191.90 80.93 01-FEB-07:10 0.110472E+09 76.15 01-FEB-06:10
March 0.109901E+09 80.93 01-MAR-07:10 0.125988E+09 76.15 01-MAR-06:10
April 99137110.46 80.93 03-APR-06:10 0.118148E+09 76.15 03-APR-05:10
May 0.106065E+09 80.93 01-MAY-06:10 0.123959E+09 76.15 01-MAY-05:10
June 0.105530E+09 80.93 01-JUN-06:10 0.121492E+09 76.15 01-JUN-05:10
July 99671236.94 80.93 03-JUL-06:10 0.120615E+09 76.15 03-JUL-05:10
August 0.109901E+09 80.93 01-AUG-06:10 0.125988E+09 76.15 01-AUG-05:10
September 99137110.46 80.93 01-SEP-06:10 0.118148E+09 76.15 01-SEP-05:10
October 0.102229E+09 80.93 02-OCT-06:10 0.121931E+09 76.15 02-OCT-05:10
November 0.100416E+09 80.93 01-NOV-06:10 0.118751E+09 76.15 01-NOV-05:10
December 99671236.94 80.93 01-DEC-07:10 0.120615E+09 76.15 01-DEC-06:10
             
Annual Sum or Average 0.122684E+10     0.144804E+10    
Minimum of Months 92954191.90 80.93   0.110472E+09 76.15  
Maximum of Months 0.109901E+09 80.93   0.125988E+09 76.15  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: SW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE LIGHTS ELECTRIC ENERGY [J] ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP}
January 51114284.87 40.46 02-JAN-07:10 60965382.94 38.07 02-JAN-06:10
February 46477095.95 40.46 01-FEB-07:10 55236172.04 38.07 01-FEB-06:10
March 54950284.09 40.46 01-MAR-07:10 62993907.37 38.07 01-MAR-06:10
April 49568555.23 40.46 03-APR-06:10 59073920.97 38.07 03-APR-05:10
May 53032284.48 40.46 01-MAY-06:10 61979645.16 38.07 01-MAY-05:10
June 52765221.24 40.46 01-JUN-06:10 60746083.00 38.07 01-JUN-05:10
July 49835618.47 40.46 03-JUL-06:10 60307483.12 38.07 03-JUL-05:10
August 54950284.09 40.46 01-AUG-06:10 62993907.37 38.07 01-AUG-05:10
September 49568555.23 40.46 01-SEP-06:10 59073920.97 38.07 01-SEP-05:10
October 51114284.87 40.46 02-OCT-06:10 60965382.94 38.07 02-OCT-05:10
November 50207888.43 40.46 01-NOV-06:10 59375458.38 38.07 01-NOV-05:10
December 49835618.47 40.46 01-DEC-07:10 60307483.12 38.07 01-DEC-06:10
             
Annual Sum or Average 0.613420E+09     0.724019E+09    
Minimum of Months 46477095.95 40.46   55236172.04 38.07  
Maximum of Months 54950284.09 40.46   62993907.37 38.07  



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261486E+09 0.171896E+09 0.342612E+09 0.00 0.00 0.00 0.00 0.00 30181454.49
February 0.237735E+09 0.156301E+09 0.310415E+09 0.00 0.00 0.00 0.00 0.00 26284467.64
March 0.283976E+09 0.184797E+09 0.354012E+09 0.00 0.00 0.00 0.00 0.00 19398121.36
April 0.252900E+09 0.166698E+09 0.331982E+09 0.00 0.00 0.00 0.00 133126.23 14460580.21
May 0.272731E+09 0.178346E+09 0.348312E+09 0.00 0.00 0.00 0.00 468510.15 4692749.73
June 0.272311E+09 0.177448E+09 0.341379E+09 0.00 0.00 0.00 0.00 1359212.17 1702028.93
July 0.253320E+09 0.167596E+09 0.338914E+09 0.00 0.00 0.00 0.00 1538081.27 787088.63
August 0.283976E+09 0.184797E+09 0.354012E+09 0.00 0.00 0.00 0.00 843769.52 1677662.13
September 0.252900E+09 0.166698E+09 0.331982E+09 0.00 0.00 0.00 0.00 111595.43 5111610.38
October 0.261486E+09 0.171896E+09 0.342612E+09 0.00 0.00 0.00 0.00 3.00 10183964.31
November 0.257986E+09 0.168848E+09 0.333677E+09 0.00 0.00 0.00 0.00 0.00 19721996.75
December 0.253320E+09 0.167596E+09 0.338914E+09 0.00 0.00 0.00 0.00 0.00 30304666.28
                   
Annual Sum or Average 0.314413E+10 0.206292E+10 0.406882E+10         4454297.78 0.164506E+09
Minimum of Months 0.237735E+09 0.156301E+09 0.310415E+09 0.00 0.00 0.00 0.00 0.00 787088.63
Maximum of Months 0.283976E+09 0.184797E+09 0.354012E+09 0.00 0.00 0.00 0.00 1538081.27 30304666.28



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 CAFE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.508444E+10 0.190996E+09 0.665880E+09 0.00 0.00 0.00 0.00 0.00 70203331.67
February 0.462263E+10 0.173668E+09 0.603304E+09 0.00 0.00 0.00 0.00 0.00 61889846.15
March 0.552176E+10 0.205330E+09 0.688036E+09 0.00 0.00 0.00 0.00 0.00 46553995.57
April 0.491750E+10 0.185220E+09 0.645221E+09 0.00 0.00 0.00 0.00 129071.92 36376130.56
May 0.530310E+10 0.198163E+09 0.676958E+09 0.00 0.00 0.00 0.00 484836.13 13531084.98
June 0.529493E+10 0.197165E+09 0.663485E+09 0.00 0.00 0.00 0.00 1640554.04 6208066.05
July 0.492567E+10 0.186218E+09 0.658694E+09 0.00 0.00 0.00 0.00 1840798.96 3565139.28
August 0.552176E+10 0.205330E+09 0.688036E+09 0.00 0.00 0.00 0.00 781072.50 6622099.33
September 0.491750E+10 0.185220E+09 0.645221E+09 0.00 0.00 0.00 0.00 69434.51 15184743.14
October 0.508444E+10 0.190996E+09 0.665880E+09 0.00 0.00 0.00 0.00 0.00 26274555.29
November 0.501640E+10 0.187609E+09 0.648514E+09 0.00 0.00 0.00 0.00 0.00 47868377.31
December 0.492567E+10 0.186218E+09 0.658694E+09 0.00 0.00 0.00 0.00 0.00 70788170.69
                   
Annual Sum or Average 0.611358E+11 0.229213E+10 0.790792E+10         4945768.07 0.405066E+09
Minimum of Months 0.462263E+10 0.173668E+09 0.603304E+09 0.00 0.00 0.00 0.00 0.00 3565139.28
Maximum of Months 0.552176E+10 0.205330E+09 0.688036E+09 0.00 0.00 0.00 0.00 1840798.96 70788170.69



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 CLEAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.305067E+09 0.200546E+09 0.399714E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.277358E+09 0.182352E+09 0.362151E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.331305E+09 0.215596E+09 0.413013E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.295050E+09 0.194481E+09 0.387312E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.318186E+09 0.208071E+09 0.406364E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.317696E+09 0.207023E+09 0.398276E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.295540E+09 0.195529E+09 0.395400E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.331305E+09 0.215596E+09 0.413013E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.295050E+09 0.194481E+09 0.387312E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.305067E+09 0.200546E+09 0.399714E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.300984E+09 0.196989E+09 0.389289E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.295540E+09 0.195529E+09 0.395400E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.366815E+10 0.240674E+10 0.474696E+10            
Minimum of Months 0.277358E+09 0.182352E+09 0.362151E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.331305E+09 0.215596E+09 0.413013E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.399492E+09 0.262619E+09 0.523434E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.363207E+09 0.238794E+09 0.474245E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.433852E+09 0.282328E+09 0.540851E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.386375E+09 0.254677E+09 0.507195E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.416672E+09 0.272474E+09 0.532143E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.416031E+09 0.271102E+09 0.521552E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.387017E+09 0.256050E+09 0.517786E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.433852E+09 0.282328E+09 0.540851E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.386375E+09 0.254677E+09 0.507195E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.399492E+09 0.262619E+09 0.523434E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.394145E+09 0.257962E+09 0.509784E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.387017E+09 0.256050E+09 0.517786E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.480353E+10 0.315168E+10 0.621626E+10            
Minimum of Months 0.363207E+09 0.238794E+09 0.474245E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.433852E+09 0.282328E+09 0.540851E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 65324757.03 91279739.78 0.219815E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 59377482.27 82982498.28 0.199158E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 70904580.02 98043141.13 0.227129E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 63147265.13 88490345.08 0.212995E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 68114668.52 94661440.45 0.223472E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 67992184.61 94150160.40 0.219024E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 63269749.05 89001625.13 0.217443E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 70904580.02 98043141.13 0.227129E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 63147265.13 88490345.08 0.212995E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 65324757.03 91279739.78 0.219815E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 64467369.59 89664873.70 0.214082E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 63269749.05 89001625.13 0.217443E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.785244E+09 0.109509E+10 0.261050E+10            
Minimum of Months 59377482.27 82982498.28 0.199158E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 70904580.02 98043141.13 0.227129E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 23330270.37 32599907.06 78505166.56 0.00 0.00 0.00 0.00 0.00 29689616.90
February 21206243.67 29636606.53 71127657.65 0.00 0.00 0.00 0.00 0.00 25711282.34
March 25323064.29 35015407.54 81117298.90 0.00 0.00 0.00 0.00 0.00 19028340.46
April 22552594.69 31603694.67 76069529.65 0.00 0.00 0.00 0.00 110769.29 14385462.56
May 24326667.33 33807657.30 79811232.73 0.00 0.00 0.00 0.00 314774.52 5004800.13
June 24282923.07 33625057.29 78222773.87 0.00 0.00 0.00 0.00 889871.36 2099317.12
July 22596338.94 31786294.69 77657988.50 0.00 0.00 0.00 0.00 927078.10 1215267.13
August 25323064.29 35015407.54 81117298.90 0.00 0.00 0.00 0.00 420561.64 2427552.60
September 22552594.69 31603694.67 76069529.65 0.00 0.00 0.00 0.00 34357.09 5970182.62
October 23330270.37 32599907.06 78505166.56 0.00 0.00 0.00 0.00 21.03 10626543.34
November 23024060.57 32023169.18 76457819.59 0.00 0.00 0.00 0.00 0.00 19659629.32
December 22596338.94 31786294.69 77657988.50 0.00 0.00 0.00 0.00 0.00 29845690.26
                   
Annual Sum or Average 0.280444E+09 0.391103E+09 0.932319E+09         2697433.02 0.165664E+09
Minimum of Months 21206243.67 29636606.53 71127657.65 0.00 0.00 0.00 0.00 0.00 1215267.13
Maximum of Months 25323064.29 35015407.54 81117298.90 0.00 0.00 0.00 0.00 927078.10 29845690.26



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 27996324.44 39119888.48 94206295.03 0.00 0.00 0.00 0.00 0.00 0.00
February 25447492.40 35563927.84 85353275.40 0.00 0.00 0.00 0.00 0.00 0.00
March 30387677.15 42018489.05 97340857.01 0.00 0.00 0.00 0.00 0.00 0.00
April 27063113.63 37924433.61 91283527.79 0.00 0.00 0.00 0.00 0.00 0.00
May 29192000.80 40569188.76 95773576.02 0.00 0.00 0.00 0.00 0.00 0.00
June 29139507.69 40350068.74 93867423.47 0.00 0.00 0.00 0.00 0.00 0.00
July 27115606.73 38143553.63 93189680.34 0.00 0.00 0.00 0.00 0.00 0.00
August 30387677.15 42018489.05 97340857.01 0.00 0.00 0.00 0.00 0.00 0.00
September 27063113.63 37924433.61 91283527.79 0.00 0.00 0.00 0.00 0.00 0.00
October 27996324.44 39119888.48 94206295.03 0.00 0.00 0.00 0.00 0.00 0.00
November 27628872.68 38427803.01 91749476.19 0.00 0.00 0.00 0.00 0.00 0.00
December 27115606.73 38143553.63 93189680.34 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.336533E+09 0.469324E+09 0.111878E+10            
Minimum of Months 25447492.40 35563927.84 85353275.40 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30387677.15 42018489.05 97340857.01 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 58066450.69 81137546.47 0.195391E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 52779984.24 73762220.70 0.177029E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 63026293.35 87149458.78 0.201892E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 56130902.33 78658084.52 0.189329E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 60546372.02 84143502.62 0.198642E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 60437497.43 83689031.47 0.194688E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 56239776.93 79112555.67 0.193282E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 63026293.35 87149458.78 0.201892E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 56130902.33 78658084.52 0.189329E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 58066450.69 81137546.47 0.195391E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 57304328.52 79702109.95 0.190295E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 56239776.93 79112555.67 0.193282E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.697995E+09 0.973412E+09 0.232044E+10            
Minimum of Months 52779984.24 73762220.70 0.177029E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 63026293.35 87149458.78 0.201892E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 LOBBY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.752982E+09 0.564297E+09 0.108512E+10 0.00 0.00 0.00 0.00 0.00 75808442.05
February 0.684590E+09 0.513103E+09 0.983143E+09 0.00 0.00 0.00 0.00 0.00 66753032.40
March 0.817746E+09 0.606646E+09 0.112122E+10 0.00 0.00 0.00 0.00 0.00 50258117.62
April 0.728259E+09 0.547232E+09 0.105145E+10 0.00 0.00 0.00 0.00 112151.78 39613590.35
May 0.785364E+09 0.585472E+09 0.110317E+10 0.00 0.00 0.00 0.00 523540.04 15198332.83
June 0.784155E+09 0.582523E+09 0.108121E+10 0.00 0.00 0.00 0.00 1704164.60 7035079.47
July 0.729468E+09 0.550181E+09 0.107341E+10 0.00 0.00 0.00 0.00 1897828.10 4264217.70
August 0.817746E+09 0.606646E+09 0.112122E+10 0.00 0.00 0.00 0.00 847605.81 7468278.55
September 0.728259E+09 0.547232E+09 0.105145E+10 0.00 0.00 0.00 0.00 77416.18 16679175.60
October 0.752982E+09 0.564297E+09 0.108512E+10 0.00 0.00 0.00 0.00 0.55 28556796.45
November 0.742904E+09 0.554291E+09 0.105682E+10 0.00 0.00 0.00 0.00 0.00 51894992.78
December 0.729468E+09 0.550181E+09 0.107341E+10 0.00 0.00 0.00 0.00 0.00 76624991.50
                   
Annual Sum or Average 0.905392E+10 0.677210E+10 0.128867E+11         5162707.07 0.440155E+09
Minimum of Months 0.684590E+09 0.513103E+09 0.983143E+09 0.00 0.00 0.00 0.00 0.00 4264217.70
Maximum of Months 0.817746E+09 0.606646E+09 0.112122E+10 0.00 0.00 0.00 0.00 1897828.10 76624991.50



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.119848E+10 0.442701E+09 0.314012E+10 0.00 0.00 0.00 0.00 0.00 78113154.66
February 0.108962E+10 0.402538E+09 0.284503E+10 0.00 0.00 0.00 0.00 0.00 68742975.17
March 0.130156E+10 0.475925E+09 0.324460E+10 0.00 0.00 0.00 0.00 0.00 51566976.21
April 0.115913E+10 0.429314E+09 0.304270E+10 0.00 0.00 0.00 0.00 143824.84 40864780.80
May 0.125002E+10 0.459313E+09 0.319236E+10 0.00 0.00 0.00 0.00 545881.92 15520241.35
June 0.124809E+10 0.457000E+09 0.312883E+10 0.00 0.00 0.00 0.00 1744156.22 7244093.96
July 0.116105E+10 0.431627E+09 0.310623E+10 0.00 0.00 0.00 0.00 1957612.92 4211640.57
August 0.130156E+10 0.475925E+09 0.324460E+10 0.00 0.00 0.00 0.00 866629.18 7483957.08
September 0.115913E+10 0.429314E+09 0.304270E+10 0.00 0.00 0.00 0.00 77907.35 17006762.45
October 0.119848E+10 0.442701E+09 0.314012E+10 0.00 0.00 0.00 0.00 0.90 29490564.77
November 0.118244E+10 0.434851E+09 0.305823E+10 0.00 0.00 0.00 0.00 0.00 53699876.11
December 0.116105E+10 0.431627E+09 0.310623E+10 0.00 0.00 0.00 0.00 0.00 79127589.86
                   
Annual Sum or Average 0.144106E+11 0.531283E+10 0.372918E+11         5336013.33 0.453073E+09
Minimum of Months 0.108962E+10 0.402538E+09 0.284503E+10 0.00 0.00 0.00 0.00 0.00 4211640.57
Maximum of Months 0.130156E+10 0.475925E+09 0.324460E+10 0.00 0.00 0.00 0.00 1957612.92 79127589.86



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.653714E+09 0.241473E+09 0.171279E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.594339E+09 0.219566E+09 0.155183E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.709940E+09 0.259595E+09 0.176978E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.632250E+09 0.234171E+09 0.165965E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.681827E+09 0.250534E+09 0.174129E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.680777E+09 0.249273E+09 0.170663E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.633300E+09 0.235433E+09 0.169431E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.709940E+09 0.259595E+09 0.176978E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.632250E+09 0.234171E+09 0.165965E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.653714E+09 0.241473E+09 0.171279E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.644965E+09 0.237191E+09 0.166812E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.633300E+09 0.235433E+09 0.169431E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.786032E+10 0.289791E+10 0.203410E+11            
Minimum of Months 0.594339E+09 0.219566E+09 0.155183E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.709940E+09 0.259595E+09 0.176978E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.406755E+09 0.179536E+09 0.266451E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.369811E+09 0.163248E+09 0.241411E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.441741E+09 0.193010E+09 0.275317E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.393400E+09 0.174107E+09 0.258184E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.424248E+09 0.186273E+09 0.270884E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.423595E+09 0.185335E+09 0.265493E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.394053E+09 0.175045E+09 0.263576E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.441741E+09 0.193010E+09 0.275317E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.393400E+09 0.174107E+09 0.258184E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.406755E+09 0.179536E+09 0.266451E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.401312E+09 0.176352E+09 0.259502E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.394053E+09 0.175045E+09 0.263576E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.489086E+10 0.215460E+10 0.316435E+11            
Minimum of Months 0.369811E+09 0.163248E+09 0.241411E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.441741E+09 0.193010E+09 0.275317E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.106531E+10 0.366767E+09 0.697848E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.968552E+09 0.333493E+09 0.632268E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.115694E+10 0.394291E+09 0.721068E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.103033E+10 0.355675E+09 0.676197E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.111113E+10 0.380529E+09 0.709458E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.110941E+10 0.378613E+09 0.695338E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.103204E+10 0.357592E+09 0.690317E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.115694E+10 0.394291E+09 0.721068E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.103033E+10 0.355675E+09 0.676197E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.106531E+10 0.366767E+09 0.697848E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.105105E+10 0.360263E+09 0.679649E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.103204E+10 0.357592E+09 0.690317E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.128094E+11 0.440155E+10 0.828757E+11            
Minimum of Months 0.968552E+09 0.333493E+09 0.632268E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.115694E+10 0.394291E+09 0.721068E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.440652E+09 0.242087E+09 0.577364E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.400628E+09 0.220125E+09 0.523106E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.478552E+09 0.260255E+09 0.596575E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.426184E+09 0.234766E+09 0.559451E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.459602E+09 0.251171E+09 0.586969E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.458894E+09 0.249906E+09 0.575287E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.426891E+09 0.236031E+09 0.571133E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.478552E+09 0.260255E+09 0.596575E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.426184E+09 0.234766E+09 0.559451E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.440652E+09 0.242087E+09 0.577364E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.434754E+09 0.237794E+09 0.562307E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.426891E+09 0.236031E+09 0.571133E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.529844E+10 0.290528E+10 0.685672E+10            
Minimum of Months 0.400628E+09 0.220125E+09 0.523106E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.478552E+09 0.260255E+09 0.596575E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.631924E+09 0.347169E+09 0.827978E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.574527E+09 0.315673E+09 0.750169E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.686275E+09 0.373223E+09 0.855528E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.611175E+09 0.336670E+09 0.802290E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.659100E+09 0.360196E+09 0.841753E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.658085E+09 0.358382E+09 0.825000E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.612190E+09 0.338484E+09 0.819043E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.686275E+09 0.373223E+09 0.855528E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.611175E+09 0.336670E+09 0.802290E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.631924E+09 0.347169E+09 0.827978E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.623466E+09 0.341013E+09 0.806385E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.612190E+09 0.338484E+09 0.819043E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.759831E+10 0.416636E+10 0.983299E+10            
Minimum of Months 0.574527E+09 0.315673E+09 0.750169E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.686275E+09 0.373223E+09 0.855528E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.250412E+09 0.349906E+09 0.842623E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.227614E+09 0.318100E+09 0.763438E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.271801E+09 0.375832E+09 0.870660E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.242065E+09 0.339213E+09 0.816480E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.261106E+09 0.362869E+09 0.856641E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.260637E+09 0.360909E+09 0.839592E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.242534E+09 0.341173E+09 0.833530E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.271801E+09 0.375832E+09 0.870660E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.242065E+09 0.339213E+09 0.816480E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.250412E+09 0.349906E+09 0.842623E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.247125E+09 0.343715E+09 0.820648E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.242534E+09 0.341173E+09 0.833530E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.301010E+10 0.419784E+10 0.100069E+11            
Minimum of Months 0.227614E+09 0.318100E+09 0.763438E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.271801E+09 0.375832E+09 0.870660E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.111374E+10 0.118190E+10 0.291854E+10 0.257644E+10 0.00 0.00 0.00 0.00 0.142732E+09
February 0.101258E+10 0.107468E+10 0.264427E+10 0.233432E+10 0.00 0.00 0.00 0.00 0.123316E+09
March 0.120953E+10 0.127060E+10 0.301565E+10 0.266217E+10 0.00 0.00 0.00 0.00 89581189.20
April 0.107717E+10 0.114616E+10 0.282800E+10 0.249651E+10 0.00 0.00 0.00 636260.23 64579985.73
May 0.116163E+10 0.122625E+10 0.296710E+10 0.261930E+10 0.00 0.00 0.00 3248954.90 20466437.20
June 0.115984E+10 0.122007E+10 0.290805E+10 0.256717E+10 0.00 0.00 0.00 8654453.99 7229789.22
July 0.107896E+10 0.115233E+10 0.288705E+10 0.254864E+10 0.00 0.00 0.00 9598091.63 3422705.14
August 0.120953E+10 0.127060E+10 0.301565E+10 0.266217E+10 0.00 0.00 0.00 5715051.62 7293790.62
September 0.107717E+10 0.114616E+10 0.282800E+10 0.249651E+10 0.00 0.00 0.00 1182308.62 21790039.29
October 0.111374E+10 0.118190E+10 0.291854E+10 0.257644E+10 0.00 0.00 0.00 172186.81 45608336.79
November 0.109883E+10 0.116094E+10 0.284243E+10 0.250925E+10 0.00 0.00 0.00 329.67 91057279.68
December 0.107896E+10 0.115233E+10 0.288705E+10 0.254864E+10 0.00 0.00 0.00 0.00 0.143434E+09
                   
Annual Sum or Average 0.133917E+11 0.141839E+11 0.346603E+11 0.305975E+11       29207637.47 0.760511E+09
Minimum of Months 0.101258E+10 0.107468E+10 0.264427E+10 0.233432E+10 0.00 0.00 0.00 0.00 3422705.14
Maximum of Months 0.120953E+10 0.127060E+10 0.301565E+10 0.266217E+10 0.00 0.00 0.00 9598091.63 0.143434E+09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.116216E+10 0.123329E+10 0.304544E+10 0.268846E+10 0.00 0.00 0.00 0.00 80183834.30
February 0.105660E+10 0.112140E+10 0.275924E+10 0.243581E+10 0.00 0.00 0.00 0.00 69237586.64
March 0.126212E+10 0.132584E+10 0.314677E+10 0.277791E+10 0.00 0.00 0.00 0.00 50072827.66
April 0.112400E+10 0.119599E+10 0.295095E+10 0.260505E+10 0.00 0.00 0.00 383784.71 35697281.53
May 0.121214E+10 0.127956E+10 0.309610E+10 0.273319E+10 0.00 0.00 0.00 2073965.07 10207356.34
June 0.121027E+10 0.127312E+10 0.303448E+10 0.267879E+10 0.00 0.00 0.00 5773353.26 3251678.81
July 0.112587E+10 0.120244E+10 0.301257E+10 0.265945E+10 0.00 0.00 0.00 6329922.42 1458584.22
August 0.126212E+10 0.132584E+10 0.314677E+10 0.277791E+10 0.00 0.00 0.00 3759994.10 3496913.57
September 0.112400E+10 0.119599E+10 0.295095E+10 0.260505E+10 0.00 0.00 0.00 1063940.56 10588024.45
October 0.116216E+10 0.123329E+10 0.304544E+10 0.268846E+10 0.00 0.00 0.00 170797.11 24253876.52
November 0.114661E+10 0.121142E+10 0.296601E+10 0.261835E+10 0.00 0.00 0.00 4234.24 50616508.55
December 0.112587E+10 0.120244E+10 0.301257E+10 0.265945E+10 0.00 0.00 0.00 0.00 80692213.31
                   
Annual Sum or Average 0.139739E+11 0.148006E+11 0.361673E+11 0.319279E+11       19559991.45 0.419757E+09
Minimum of Months 0.105660E+10 0.112140E+10 0.275924E+10 0.243581E+10 0.00 0.00 0.00 0.00 1458584.22
Maximum of Months 0.126212E+10 0.132584E+10 0.314677E+10 0.277791E+10 0.00 0.00 0.00 6329922.42 80692213.31



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.115247E+10 0.122301E+10 0.302006E+10 0.266606E+10 0.00 0.00 0.00 0.00 0.00
February 0.104780E+10 0.111206E+10 0.273625E+10 0.241551E+10 0.00 0.00 0.00 0.00 0.00
March 0.125160E+10 0.131479E+10 0.312055E+10 0.275476E+10 0.00 0.00 0.00 0.00 0.00
April 0.111463E+10 0.118603E+10 0.292636E+10 0.258334E+10 0.00 0.00 0.00 0.00 0.00
May 0.120204E+10 0.126890E+10 0.307030E+10 0.271041E+10 0.00 0.00 0.00 0.00 0.00
June 0.120019E+10 0.126251E+10 0.300919E+10 0.265647E+10 0.00 0.00 0.00 0.00 0.00
July 0.111648E+10 0.119242E+10 0.298747E+10 0.263728E+10 0.00 0.00 0.00 0.00 0.00
August 0.125160E+10 0.131479E+10 0.312055E+10 0.275476E+10 0.00 0.00 0.00 0.00 0.00
September 0.111463E+10 0.118603E+10 0.292636E+10 0.258334E+10 0.00 0.00 0.00 0.00 0.00
October 0.115247E+10 0.122301E+10 0.302006E+10 0.266606E+10 0.00 0.00 0.00 0.00 0.00
November 0.113705E+10 0.120132E+10 0.294130E+10 0.259653E+10 0.00 0.00 0.00 0.00 0.00
December 0.111648E+10 0.119242E+10 0.298747E+10 0.263728E+10 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.138574E+11 0.146773E+11 0.358659E+11 0.316618E+11          
Minimum of Months 0.104780E+10 0.111206E+10 0.273625E+10 0.241551E+10 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.125160E+10 0.131479E+10 0.312055E+10 0.275476E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 PACU

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.261486E+09 0.153479E+09 0.513838E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.237735E+09 0.139555E+09 0.465550E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.283976E+09 0.164997E+09 0.530935E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.252900E+09 0.148837E+09 0.497896E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.272731E+09 0.159238E+09 0.522386E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.272311E+09 0.158436E+09 0.511990E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.253320E+09 0.149639E+09 0.508293E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.283976E+09 0.164997E+09 0.530935E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.252900E+09 0.148837E+09 0.497896E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.261486E+09 0.153479E+09 0.513838E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.257986E+09 0.150757E+09 0.500437E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.253320E+09 0.149639E+09 0.508293E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.314413E+10 0.184189E+10 0.610229E+10            
Minimum of Months 0.237735E+09 0.139555E+09 0.465550E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.283976E+09 0.164997E+09 0.530935E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.228800E+09 0.146112E+09 0.599570E+09 0.00 0.00 0.00 0.00 0.00 13290009.51
February 0.208019E+09 0.132856E+09 0.543226E+09 0.00 0.00 0.00 0.00 0.00 11567963.42
March 0.248479E+09 0.157077E+09 0.619520E+09 0.00 0.00 0.00 0.00 0.00 8492523.58
April 0.221288E+09 0.141693E+09 0.580969E+09 0.00 0.00 0.00 0.00 59514.19 6283119.65
May 0.238640E+09 0.151594E+09 0.609545E+09 0.00 0.00 0.00 0.00 221875.54 2009948.92
June 0.238272E+09 0.150831E+09 0.597414E+09 0.00 0.00 0.00 0.00 633018.65 709545.53
July 0.221655E+09 0.142457E+09 0.593100E+09 0.00 0.00 0.00 0.00 722751.55 323637.42
August 0.248479E+09 0.157077E+09 0.619520E+09 0.00 0.00 0.00 0.00 408828.15 705250.86
September 0.221288E+09 0.141693E+09 0.580969E+09 0.00 0.00 0.00 0.00 61460.50 2164685.33
October 0.228800E+09 0.146112E+09 0.599570E+09 0.00 0.00 0.00 0.00 5007.63 4397726.76
November 0.225738E+09 0.143521E+09 0.583934E+09 0.00 0.00 0.00 0.00 0.00 8635863.39
December 0.221655E+09 0.142457E+09 0.593100E+09 0.00 0.00 0.00 0.00 0.00 13369356.70
                   
Annual Sum or Average 0.275111E+10 0.175348E+10 0.712044E+10         2112456.22 71949631.06
Minimum of Months 0.208019E+09 0.132856E+09 0.543226E+09 0.00 0.00 0.00 0.00 0.00 323637.42
Maximum of Months 0.248479E+09 0.157077E+09 0.619520E+09 0.00 0.00 0.00 0.00 722751.55 13369356.70



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.409177E+09 0.261300E+09 0.107225E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.372012E+09 0.237595E+09 0.971483E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.444370E+09 0.280910E+09 0.110792E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.395742E+09 0.253399E+09 0.103898E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.426773E+09 0.271105E+09 0.109009E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.426116E+09 0.269740E+09 0.106839E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.396399E+09 0.254764E+09 0.106068E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.444370E+09 0.280910E+09 0.110792E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.395742E+09 0.253399E+09 0.103898E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.409177E+09 0.261300E+09 0.107225E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.403701E+09 0.256667E+09 0.104428E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.396399E+09 0.254764E+09 0.106068E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.491998E+10 0.313585E+10 0.127339E+11            
Minimum of Months 0.372012E+09 0.237595E+09 0.971483E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.444370E+09 0.280910E+09 0.110792E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.690032E+09 0.453615E+09 0.135596E+10 0.00 0.00 0.00 0.00 0.00 62939573.65
February 0.627357E+09 0.412462E+09 0.122854E+10 0.00 0.00 0.00 0.00 0.00 54484581.07
March 0.749381E+09 0.487658E+09 0.140108E+10 0.00 0.00 0.00 0.00 0.00 40117914.56
April 0.667375E+09 0.439897E+09 0.131389E+10 0.00 0.00 0.00 0.00 283186.78 29669235.38
May 0.719706E+09 0.470636E+09 0.137852E+10 0.00 0.00 0.00 0.00 1126254.38 9460428.94
June 0.718598E+09 0.468266E+09 0.135108E+10 0.00 0.00 0.00 0.00 3141894.86 3288708.56
July 0.668484E+09 0.442268E+09 0.134133E+10 0.00 0.00 0.00 0.00 3578690.24 1479876.58
August 0.749381E+09 0.487658E+09 0.140108E+10 0.00 0.00 0.00 0.00 2049691.24 3236630.14
September 0.667375E+09 0.439897E+09 0.131389E+10 0.00 0.00 0.00 0.00 310845.48 10122792.11
October 0.690032E+09 0.453615E+09 0.135596E+10 0.00 0.00 0.00 0.00 27659.07 20793629.29
November 0.680797E+09 0.445571E+09 0.132060E+10 0.00 0.00 0.00 0.00 0.00 40698996.12
December 0.668484E+09 0.442268E+09 0.134133E+10 0.00 0.00 0.00 0.00 0.00 63109224.76
                   
Annual Sum or Average 0.829700E+10 0.544381E+10 0.161033E+11         10518222.04 0.339402E+09
Minimum of Months 0.627357E+09 0.412462E+09 0.122854E+10 0.00 0.00 0.00 0.00 0.00 1479876.58
Maximum of Months 0.749381E+09 0.487658E+09 0.140108E+10 0.00 0.00 0.00 0.00 3578690.24 63109224.76



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.184856E+10 0.486084E+09 0.887981E+09 0.00 0.00 0.00 0.00 0.00 46145178.33
February 0.168066E+10 0.441986E+09 0.804533E+09 0.00 0.00 0.00 0.00 0.00 40666008.73
March 0.200755E+10 0.522564E+09 0.917527E+09 0.00 0.00 0.00 0.00 0.00 30520196.59
April 0.178786E+10 0.471385E+09 0.860432E+09 0.00 0.00 0.00 0.00 75349.35 24132676.56
May 0.192806E+10 0.504324E+09 0.902754E+09 0.00 0.00 0.00 0.00 321392.44 9127186.99
June 0.192509E+10 0.501784E+09 0.884787E+09 0.00 0.00 0.00 0.00 1045116.91 4236475.09
July 0.179083E+10 0.473925E+09 0.878399E+09 0.00 0.00 0.00 0.00 1174943.99 2466340.98
August 0.200755E+10 0.522564E+09 0.917527E+09 0.00 0.00 0.00 0.00 511657.38 4434865.90
September 0.178786E+10 0.471385E+09 0.860432E+09 0.00 0.00 0.00 0.00 45950.52 10068096.18
October 0.184856E+10 0.486084E+09 0.887981E+09 0.00 0.00 0.00 0.00 0.97 17386903.76
November 0.182382E+10 0.477465E+09 0.864824E+09 0.00 0.00 0.00 0.00 0.00 31623942.47
December 0.179083E+10 0.473925E+09 0.878399E+09 0.00 0.00 0.00 0.00 0.00 46683701.45
                   
Annual Sum or Average 0.222272E+11 0.583347E+10 0.105456E+11         3174411.55 0.267492E+09
Minimum of Months 0.168066E+10 0.441986E+09 0.804533E+09 0.00 0.00 0.00 0.00 0.00 2466340.98
Maximum of Months 0.200755E+10 0.522564E+09 0.917527E+09 0.00 0.00 0.00 0.00 1174943.99 46683701.45



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.130743E+10 0.767394E+09 0.256919E+10 0.00 0.00 0.00 0.00 0.00 0.150694E+09
February 0.118868E+10 0.697774E+09 0.232775E+10 0.00 0.00 0.00 0.00 0.00 0.131114E+09
March 0.141988E+10 0.824985E+09 0.265468E+10 0.00 0.00 0.00 0.00 0.00 96888302.62
April 0.126450E+10 0.744187E+09 0.248948E+10 0.00 0.00 0.00 0.00 665698.16 72263215.44
May 0.136365E+10 0.796189E+09 0.261193E+10 0.00 0.00 0.00 0.00 2355738.29 23432299.84
June 0.136155E+10 0.792180E+09 0.255995E+10 0.00 0.00 0.00 0.00 6816944.06 8493665.65
July 0.126660E+10 0.748197E+09 0.254146E+10 0.00 0.00 0.00 0.00 7712442.72 3927413.23
August 0.141988E+10 0.824985E+09 0.265468E+10 0.00 0.00 0.00 0.00 4212165.73 8370573.01
September 0.126450E+10 0.744187E+09 0.248948E+10 0.00 0.00 0.00 0.00 551430.46 25534870.29
October 0.130743E+10 0.767394E+09 0.256919E+10 0.00 0.00 0.00 0.00 1620.49 50893233.69
November 0.128993E+10 0.753786E+09 0.250219E+10 0.00 0.00 0.00 0.00 0.00 98521039.24
December 0.126660E+10 0.748197E+09 0.254146E+10 0.00 0.00 0.00 0.00 0.00 0.151300E+09
                   
Annual Sum or Average 0.157206E+11 0.920946E+10 0.305114E+11         22316039.91 0.821432E+09
Minimum of Months 0.118868E+10 0.697774E+09 0.232775E+10 0.00 0.00 0.00 0.00 0.00 3927413.23
Maximum of Months 0.141988E+10 0.824985E+09 0.265468E+10 0.00 0.00 0.00 0.00 7712442.72 0.151300E+09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 61695603.86 86208643.12 0.207603E+09 0.00 0.00 0.00 0.00 0.00 24148214.68
February 56078733.26 78372359.49 0.188093E+09 0.00 0.00 0.00 0.00 0.00 21274286.91
March 66965436.69 92596299.95 0.214510E+09 0.00 0.00 0.00 0.00 0.00 15883824.27
April 59639083.73 83574214.80 0.201162E+09 0.00 0.00 0.00 0.00 55036.23 12376532.31
May 64330520.27 89402471.54 0.211057E+09 0.00 0.00 0.00 0.00 188726.47 4533836.61
June 64214841.02 88919595.94 0.206856E+09 0.00 0.00 0.00 0.00 616905.03 2014262.25
July 59754762.99 84057090.40 0.205362E+09 0.00 0.00 0.00 0.00 687495.35 1141802.80
August 66965436.69 92596299.95 0.214510E+09 0.00 0.00 0.00 0.00 303833.42 2163647.49
September 59639083.73 83574214.80 0.201162E+09 0.00 0.00 0.00 0.00 22684.03 5147730.48
October 61695603.86 86208643.12 0.207603E+09 0.00 0.00 0.00 0.00 0.05 9042082.30
November 60885849.06 84683491.83 0.202189E+09 0.00 0.00 0.00 0.00 0.00 16550082.28
December 59754762.99 84057090.40 0.205362E+09 0.00 0.00 0.00 0.00 0.00 24486935.23
                   
Annual Sum or Average 0.741620E+09 0.103425E+10 0.246547E+10         1874680.58 0.138763E+09
Minimum of Months 56078733.26 78372359.49 0.188093E+09 0.00 0.00 0.00 0.00 0.00 1141802.80
Maximum of Months 66965436.69 92596299.95 0.214510E+09 0.00 0.00 0.00 0.00 687495.35 24486935.23



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 SOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.305067E+09 0.200546E+09 0.399714E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.277358E+09 0.182352E+09 0.362151E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.331305E+09 0.215596E+09 0.413013E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.295050E+09 0.194481E+09 0.387312E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.318186E+09 0.208071E+09 0.406364E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.317696E+09 0.207023E+09 0.398276E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.295540E+09 0.195529E+09 0.395400E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.331305E+09 0.215596E+09 0.413013E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.295050E+09 0.194481E+09 0.387312E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.305067E+09 0.200546E+09 0.399714E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.300984E+09 0.196989E+09 0.389289E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.295540E+09 0.195529E+09 0.395400E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.366815E+10 0.240674E+10 0.474696E+10            
Minimum of Months 0.277358E+09 0.182352E+09 0.362151E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.331305E+09 0.215596E+09 0.413013E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.135585E+09 89131391.98 0.177650E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.123270E+09 81045215.98 0.160956E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.147247E+09 95820479.98 0.183561E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.131133E+09 86435999.98 0.172139E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.141416E+09 92475935.98 0.180606E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.141198E+09 92010239.98 0.177011E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.131351E+09 86901695.98 0.175733E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.147247E+09 95820479.98 0.183561E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.131133E+09 86435999.98 0.172139E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.135585E+09 89131391.98 0.177650E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.133771E+09 87550847.98 0.173017E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.131351E+09 86901695.98 0.175733E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.163029E+10 0.106966E+10 0.210976E+10            
Minimum of Months 0.123270E+09 81045215.98 0.160956E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.147247E+09 95820479.98 0.183561E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.435809E+09 0.286494E+09 0.571019E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.396226E+09 0.260502E+09 0.517358E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.473293E+09 0.307994E+09 0.590019E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.421500E+09 0.277830E+09 0.553303E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.454551E+09 0.297244E+09 0.580519E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.453852E+09 0.295747E+09 0.568965E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.422200E+09 0.279327E+09 0.564857E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.473293E+09 0.307994E+09 0.590019E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.421500E+09 0.277830E+09 0.553303E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.435809E+09 0.286494E+09 0.571019E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.429977E+09 0.281413E+09 0.556128E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.422200E+09 0.279327E+09 0.564857E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.524021E+10 0.343820E+10 0.678137E+10            
Minimum of Months 0.396226E+09 0.260502E+09 0.517358E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.473293E+09 0.307994E+09 0.590019E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.726349E+09 0.426330E+09 0.142733E+10 0.00 0.00 0.00 0.00 0.00 0.123346E+09
February 0.660376E+09 0.387652E+09 0.129319E+10 0.00 0.00 0.00 0.00 0.00 0.107129E+09
March 0.788822E+09 0.458325E+09 0.147482E+10 0.00 0.00 0.00 0.00 0.00 79365267.57
April 0.702500E+09 0.413437E+09 0.138304E+10 0.00 0.00 0.00 0.00 541843.24 59506836.52
May 0.757586E+09 0.442327E+09 0.145107E+10 0.00 0.00 0.00 0.00 1776164.25 19433251.21
June 0.756419E+09 0.440100E+09 0.142219E+10 0.00 0.00 0.00 0.00 5230854.44 7064581.80
July 0.703667E+09 0.415665E+09 0.141192E+10 0.00 0.00 0.00 0.00 5812223.94 3325337.97
August 0.788822E+09 0.458325E+09 0.147482E+10 0.00 0.00 0.00 0.00 2893066.63 7154363.47
September 0.702500E+09 0.413437E+09 0.138304E+10 0.00 0.00 0.00 0.00 345091.76 21459961.03
October 0.726349E+09 0.426330E+09 0.142733E+10 0.00 0.00 0.00 0.00 3.18 42100402.46
November 0.716628E+09 0.418770E+09 0.139010E+10 0.00 0.00 0.00 0.00 0.00 80874137.07
December 0.703667E+09 0.415665E+09 0.141192E+10 0.00 0.00 0.00 0.00 0.00 0.123792E+09
                   
Annual Sum or Average 0.873369E+10 0.511636E+10 0.169508E+11         16599247.44 0.674552E+09
Minimum of Months 0.660376E+09 0.387652E+09 0.129319E+10 0.00 0.00 0.00 0.00 0.00 3325337.97
Maximum of Months 0.788822E+09 0.458325E+09 0.147482E+10 0.00 0.00 0.00 0.00 5812223.94 0.123792E+09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.156707E+10 0.185487E+09 0.532704E+09 0.00 0.00 0.00 0.00 0.00 0.193036E+09
February 0.142154E+10 0.138876E+09 0.482643E+09 0.00 0.00 0.00 0.00 0.00 0.168845E+09
March 0.170280E+10 0.140130E+09 0.550429E+09 0.00 0.00 0.00 0.00 0.00 0.127253E+09
April 0.150610E+10 97135767.03 0.516177E+09 0.00 0.00 0.00 0.00 498852.71 98621681.92
May 0.163493E+10 79160283.84 0.541566E+09 0.00 0.00 0.00 0.00 1683403.34 35273807.25
June 0.163167E+10 72677886.16 0.530788E+09 0.00 0.00 0.00 0.00 5675136.08 14769751.70
July 0.150936E+10 68956022.98 0.526955E+09 0.00 0.00 0.00 0.00 6692748.72 7592618.72
August 0.170280E+10 0.106292E+09 0.550429E+09 0.00 0.00 0.00 0.00 2862730.16 15115693.47
September 0.150610E+10 0.112220E+09 0.516177E+09 0.00 0.00 0.00 0.00 271358.79 38971125.27
October 0.156707E+10 0.150552E+09 0.532704E+09 0.00 0.00 0.00 0.00 0.00 69976301.94
November 0.155364E+10 0.183148E+09 0.518811E+09 0.00 0.00 0.00 0.00 0.00 0.128792E+09
December 0.150936E+10 0.197266E+09 0.526955E+09 0.00 0.00 0.00 0.00 0.00 0.193351E+09
                   
Annual Sum or Average 0.188124E+11 0.153190E+10 0.632634E+10         17684229.79 0.109160E+10
Minimum of Months 0.142154E+10 68956022.98 0.482643E+09 0.00 0.00 0.00 0.00 0.00 7592618.72
Maximum of Months 0.170280E+10 0.197266E+09 0.550429E+09 0.00 0.00 0.00 0.00 6692748.72 0.193351E+09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 36291531.68 50710966.54 0.122119E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 32987490.15 46101387.93 0.110643E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 39391433.35 54468411.74 0.126183E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 35081813.96 49161302.82 0.118330E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 37841482.51 52589689.14 0.124151E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 37773435.89 52305644.67 0.121680E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 35149860.58 49445347.30 0.120801E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 39391433.35 54468411.74 0.126183E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 35081813.96 49161302.82 0.118330E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 36291531.68 50710966.54 0.122119E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 35815205.33 49813818.72 0.118934E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 35149860.58 49445347.30 0.120801E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.436247E+09 0.608383E+09 0.145028E+10            
Minimum of Months 32987490.15 46101387.93 0.110643E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 39391433.35 54468411.74 0.126183E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.871619E+09 0.446930E+09 0.628042E+09 0.00 0.00 0.00 0.00 0.00 0.200695E+09
February 0.792452E+09 0.406384E+09 0.569022E+09 0.00 0.00 0.00 0.00 0.00 0.174092E+09
March 0.946587E+09 0.480471E+09 0.648939E+09 0.00 0.00 0.00 0.00 0.00 0.129988E+09
April 0.843000E+09 0.433415E+09 0.608557E+09 0.00 0.00 0.00 0.00 637860.54 99850451.24
May 0.909103E+09 0.463701E+09 0.638490E+09 0.00 0.00 0.00 0.00 2176163.51 34451723.68
June 0.907703E+09 0.461366E+09 0.625783E+09 0.00 0.00 0.00 0.00 7260735.07 13213848.29
July 0.844400E+09 0.435750E+09 0.621264E+09 0.00 0.00 0.00 0.00 8244622.86 6541174.73
August 0.946587E+09 0.480471E+09 0.648939E+09 0.00 0.00 0.00 0.00 4115694.33 13207370.74
September 0.843000E+09 0.433415E+09 0.608557E+09 0.00 0.00 0.00 0.00 490306.56 37093122.19
October 0.871619E+09 0.446930E+09 0.628042E+09 0.00 0.00 0.00 0.00 0.00 69744359.81
November 0.859954E+09 0.439005E+09 0.611663E+09 0.00 0.00 0.00 0.00 0.00 0.131090E+09
December 0.844400E+09 0.435750E+09 0.621264E+09 0.00 0.00 0.00 0.00 0.00 0.200783E+09
                   
Annual Sum or Average 0.104804E+11 0.536359E+10 0.745856E+10         22925382.87 0.111075E+10
Minimum of Months 0.792452E+09 0.406384E+09 0.569022E+09 0.00 0.00 0.00 0.00 0.00 6541174.73
Maximum of Months 0.946587E+09 0.480471E+09 0.648939E+09 0.00 0.00 0.00 0.00 8244622.86 0.200783E+09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.130743E+10 0.670395E+09 0.942063E+09 0.00 0.00 0.00 0.00 0.00 86356487.46
February 0.118868E+10 0.609576E+09 0.853533E+09 0.00 0.00 0.00 0.00 0.00 74870960.90
March 0.141988E+10 0.720707E+09 0.973408E+09 0.00 0.00 0.00 0.00 0.00 55757633.78
April 0.126450E+10 0.650122E+09 0.912835E+09 0.00 0.00 0.00 0.00 381249.54 42215037.83
May 0.136365E+10 0.695551E+09 0.957736E+09 0.00 0.00 0.00 0.00 1307991.50 13998299.64
June 0.136155E+10 0.692048E+09 0.938674E+09 0.00 0.00 0.00 0.00 3855911.86 5157097.36
July 0.126660E+10 0.653625E+09 0.931897E+09 0.00 0.00 0.00 0.00 4398545.11 2377343.30
August 0.141988E+10 0.720707E+09 0.973408E+09 0.00 0.00 0.00 0.00 2454994.47 5032317.07
September 0.126450E+10 0.650122E+09 0.912835E+09 0.00 0.00 0.00 0.00 359992.40 15159625.77
October 0.130743E+10 0.670395E+09 0.942063E+09 0.00 0.00 0.00 0.00 18688.67 29647351.08
November 0.128993E+10 0.658507E+09 0.917495E+09 0.00 0.00 0.00 0.00 0.00 56492577.63
December 0.126660E+10 0.653625E+09 0.931897E+09 0.00 0.00 0.00 0.00 0.00 86409808.09
                   
Annual Sum or Average 0.157206E+11 0.804538E+10 0.111878E+11         12777373.55 0.473475E+09
Minimum of Months 0.118868E+10 0.609576E+09 0.853533E+09 0.00 0.00 0.00 0.00 0.00 2377343.30
Maximum of Months 0.141988E+10 0.720707E+09 0.973408E+09 0.00 0.00 0.00 0.00 4398545.11 86409808.09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.174324E+10 0.893861E+09 0.125608E+10 0.00 0.00 0.00 0.00 0.00 0.115129E+09
February 0.158490E+10 0.812768E+09 0.113804E+10 0.00 0.00 0.00 0.00 0.00 99812124.04
March 0.189317E+10 0.960943E+09 0.129788E+10 0.00 0.00 0.00 0.00 0.00 74248030.82
April 0.168600E+10 0.866830E+09 0.121711E+10 0.00 0.00 0.00 0.00 508331.06 56067777.47
May 0.181821E+10 0.927402E+09 0.127698E+10 0.00 0.00 0.00 0.00 1776311.84 18477000.69
June 0.181541E+10 0.922731E+09 0.125157E+10 0.00 0.00 0.00 0.00 5196797.18 6763392.84
July 0.168880E+10 0.871500E+09 0.124253E+10 0.00 0.00 0.00 0.00 5931710.84 3095853.49
August 0.189317E+10 0.960943E+09 0.129788E+10 0.00 0.00 0.00 0.00 3334137.55 6580720.94
September 0.168600E+10 0.866830E+09 0.121711E+10 0.00 0.00 0.00 0.00 484700.54 20023004.73
October 0.174324E+10 0.893861E+09 0.125608E+10 0.00 0.00 0.00 0.00 28083.88 39363658.51
November 0.171991E+10 0.878010E+09 0.122333E+10 0.00 0.00 0.00 0.00 0.00 75226483.21
December 0.168880E+10 0.871500E+09 0.124253E+10 0.00 0.00 0.00 0.00 0.00 0.115190E+09
                   
Annual Sum or Average 0.209608E+11 0.107272E+11 0.149171E+11         17260072.90 0.629977E+09
Minimum of Months 0.158490E+10 0.812768E+09 0.113804E+10 0.00 0.00 0.00 0.00 0.00 3095853.49
Maximum of Months 0.189317E+10 0.960943E+09 0.129788E+10 0.00 0.00 0.00 0.00 5931710.84 0.115190E+09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.203378E+09 0.104284E+09 0.146543E+09 0.00 0.00 0.00 0.00 0.00 33637941.84
February 0.184905E+09 94822902.70 0.132772E+09 0.00 0.00 0.00 0.00 0.00 29379032.74
March 0.220870E+09 0.112110E+09 0.151419E+09 0.00 0.00 0.00 0.00 0.00 21977989.75
April 0.196700E+09 0.101130E+09 0.141996E+09 0.00 0.00 0.00 0.00 115464.18 16832359.77
May 0.212124E+09 0.108197E+09 0.148981E+09 0.00 0.00 0.00 0.00 400325.97 5676114.41
June 0.211797E+09 0.107652E+09 0.146016E+09 0.00 0.00 0.00 0.00 1281780.80 2154447.39
July 0.197027E+09 0.101675E+09 0.144962E+09 0.00 0.00 0.00 0.00 1484040.42 1025847.36
August 0.220870E+09 0.112110E+09 0.151419E+09 0.00 0.00 0.00 0.00 701417.16 2152609.25
September 0.196700E+09 0.101130E+09 0.141996E+09 0.00 0.00 0.00 0.00 71594.75 6280789.62
October 0.203378E+09 0.104284E+09 0.146543E+09 0.00 0.00 0.00 0.00 0.00 11829808.76
November 0.200656E+09 0.102434E+09 0.142721E+09 0.00 0.00 0.00 0.00 0.00 22177707.80
December 0.197027E+09 0.101675E+09 0.144962E+09 0.00 0.00 0.00 0.00 0.00 33664884.30
                   
Annual Sum or Average 0.244543E+10 0.125150E+10 0.174033E+10         4054623.28 0.186790E+09
Minimum of Months 0.184905E+09 94822902.70 0.132772E+09 0.00 0.00 0.00 0.00 0.00 1025847.36
Maximum of Months 0.220870E+09 0.112110E+09 0.151419E+09 0.00 0.00 0.00 0.00 1484040.42 33664884.30



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.847407E+09 0.434516E+09 0.610596E+09 0.00 0.00 0.00 0.00 0.00 0.119617E+09
February 0.770439E+09 0.395095E+09 0.553216E+09 0.00 0.00 0.00 0.00 0.00 0.103530E+09
March 0.920293E+09 0.467125E+09 0.630913E+09 0.00 0.00 0.00 0.00 0.00 77201834.85
April 0.819584E+09 0.421375E+09 0.591652E+09 0.00 0.00 0.00 0.00 506387.55 59374108.74
May 0.883850E+09 0.450820E+09 0.620755E+09 0.00 0.00 0.00 0.00 1579952.63 20414890.88
June 0.882489E+09 0.448550E+09 0.608400E+09 0.00 0.00 0.00 0.00 4565857.36 8005986.77
July 0.820945E+09 0.423646E+09 0.604007E+09 0.00 0.00 0.00 0.00 5260637.02 3914826.25
August 0.920293E+09 0.467125E+09 0.630913E+09 0.00 0.00 0.00 0.00 2786330.29 7771878.08
September 0.819584E+09 0.421375E+09 0.591652E+09 0.00 0.00 0.00 0.00 419797.76 21948505.56
October 0.847407E+09 0.434516E+09 0.610596E+09 0.00 0.00 0.00 0.00 20927.62 41498618.85
November 0.836066E+09 0.426810E+09 0.594672E+09 0.00 0.00 0.00 0.00 0.00 78205256.37
December 0.820945E+09 0.423646E+09 0.604007E+09 0.00 0.00 0.00 0.00 0.00 0.119723E+09
                   
Annual Sum or Average 0.101893E+11 0.521460E+10 0.725138E+10         15139890.23 0.661206E+09
Minimum of Months 0.770439E+09 0.395095E+09 0.553216E+09 0.00 0.00 0.00 0.00 0.00 3914826.25
Maximum of Months 0.920293E+09 0.467125E+09 0.630913E+09 0.00 0.00 0.00 0.00 5260637.02 0.119723E+09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.544762E+09 0.279331E+09 0.392526E+09 0.00 0.00 0.00 0.00 0.00 71732237.91
February 0.495282E+09 0.253990E+09 0.355639E+09 0.00 0.00 0.00 0.00 0.00 62046755.46
March 0.591617E+09 0.300295E+09 0.405587E+09 0.00 0.00 0.00 0.00 0.00 46088392.58
April 0.526875E+09 0.270884E+09 0.380348E+09 0.00 0.00 0.00 0.00 317706.98 34883558.97
May 0.568189E+09 0.289813E+09 0.399056E+09 0.00 0.00 0.00 0.00 1067999.45 11647383.04
June 0.567314E+09 0.288354E+09 0.391114E+09 0.00 0.00 0.00 0.00 3133788.75 4359811.91
July 0.527750E+09 0.272344E+09 0.388290E+09 0.00 0.00 0.00 0.00 3585249.03 2023047.28
August 0.591617E+09 0.300295E+09 0.405587E+09 0.00 0.00 0.00 0.00 2002153.76 4240188.90
September 0.526875E+09 0.270884E+09 0.380348E+09 0.00 0.00 0.00 0.00 302913.57 12588720.96
October 0.544762E+09 0.279331E+09 0.392526E+09 0.00 0.00 0.00 0.00 21944.59 24537860.52
November 0.537471E+09 0.274378E+09 0.382289E+09 0.00 0.00 0.00 0.00 0.00 46768098.57
December 0.527750E+09 0.272344E+09 0.388290E+09 0.00 0.00 0.00 0.00 0.00 71796237.06
                   
Annual Sum or Average 0.655026E+10 0.335224E+10 0.466160E+10         10431756.13 0.392712E+09
Minimum of Months 0.495282E+09 0.253990E+09 0.355639E+09 0.00 0.00 0.00 0.00 0.00 2023047.28
Maximum of Months 0.591617E+09 0.300295E+09 0.405587E+09 0.00 0.00 0.00 0.00 3585249.03 71796237.06



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.191756E+10 0.983247E+09 0.138169E+10 0.00 0.00 0.00 0.00 0.00 0.115071E+09
February 0.174339E+10 0.894045E+09 0.125185E+10 0.00 0.00 0.00 0.00 0.00 99587980.78
March 0.208249E+10 0.105704E+10 0.142767E+10 0.00 0.00 0.00 0.00 0.00 74055502.29
April 0.185460E+10 0.953513E+09 0.133882E+10 0.00 0.00 0.00 0.00 509005.75 55972599.15
May 0.200003E+10 0.102014E+10 0.140468E+10 0.00 0.00 0.00 0.00 1783540.50 18535346.06
June 0.199695E+10 0.101500E+10 0.137672E+10 0.00 0.00 0.00 0.00 5196754.94 6819577.32
July 0.185768E+10 0.958650E+09 0.136678E+10 0.00 0.00 0.00 0.00 5939880.51 3120995.74
August 0.208249E+10 0.105704E+10 0.142767E+10 0.00 0.00 0.00 0.00 3369298.98 6616493.59
September 0.185460E+10 0.953513E+09 0.133882E+10 0.00 0.00 0.00 0.00 503871.10 20009274.66
October 0.191756E+10 0.983247E+09 0.138169E+10 0.00 0.00 0.00 0.00 39774.57 39331013.10
November 0.189190E+10 0.965811E+09 0.134566E+10 0.00 0.00 0.00 0.00 0.00 75126800.27
December 0.185768E+10 0.958650E+09 0.136678E+10 0.00 0.00 0.00 0.00 0.00 0.115217E+09
                   
Annual Sum or Average 0.230569E+11 0.117999E+11 0.164088E+11         17342126.35 0.629463E+09
Minimum of Months 0.174339E+10 0.894045E+09 0.125185E+10 0.00 0.00 0.00 0.00 0.00 3120995.74
Maximum of Months 0.208249E+10 0.105704E+10 0.142767E+10 0.00 0.00 0.00 0.00 5939880.51 0.115217E+09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.653714E+09 0.335198E+09 0.471031E+09 0.00 0.00 0.00 0.00 0.00 86167852.83
February 0.594339E+09 0.304788E+09 0.426766E+09 0.00 0.00 0.00 0.00 0.00 74584126.26
March 0.709940E+09 0.360353E+09 0.486704E+09 0.00 0.00 0.00 0.00 0.00 55539126.85
April 0.632250E+09 0.325061E+09 0.456417E+09 0.00 0.00 0.00 0.00 381247.97 42254233.73
May 0.681827E+09 0.347776E+09 0.478868E+09 0.00 0.00 0.00 0.00 1248707.86 14250638.79
June 0.680777E+09 0.346024E+09 0.469337E+09 0.00 0.00 0.00 0.00 3687398.48 5407640.78
July 0.633300E+09 0.326812E+09 0.465948E+09 0.00 0.00 0.00 0.00 4234470.06 2514596.64
August 0.709940E+09 0.360353E+09 0.486704E+09 0.00 0.00 0.00 0.00 2347916.32 5238210.42
September 0.632250E+09 0.325061E+09 0.456417E+09 0.00 0.00 0.00 0.00 356181.17 15385394.94
October 0.653714E+09 0.335198E+09 0.471031E+09 0.00 0.00 0.00 0.00 23863.07 29749165.53
November 0.644965E+09 0.329254E+09 0.458747E+09 0.00 0.00 0.00 0.00 0.00 56410118.94
December 0.633300E+09 0.326812E+09 0.465948E+09 0.00 0.00 0.00 0.00 0.00 86283320.64
                   
Annual Sum or Average 0.786032E+10 0.402269E+10 0.559392E+10         12279784.93 0.473784E+09
Minimum of Months 0.594339E+09 0.304788E+09 0.426766E+09 0.00 0.00 0.00 0.00 0.00 2514596.64
Maximum of Months 0.709940E+09 0.360353E+09 0.486704E+09 0.00 0.00 0.00 0.00 4234470.06 86283320.64



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.958781E+09 0.491623E+09 0.690846E+09 0.00 0.00 0.00 0.00 0.00 57585604.60
February 0.871697E+09 0.447022E+09 0.625924E+09 0.00 0.00 0.00 0.00 0.00 49866125.25
March 0.104125E+10 0.528518E+09 0.713833E+09 0.00 0.00 0.00 0.00 0.00 37137103.49
April 0.927300E+09 0.476756E+09 0.669412E+09 0.00 0.00 0.00 0.00 254165.58 28210077.64
May 0.100001E+10 0.510071E+09 0.702339E+09 0.00 0.00 0.00 0.00 858886.15 9438645.22
June 0.998473E+09 0.507502E+09 0.688361E+09 0.00 0.00 0.00 0.00 2529489.59 3541355.06
July 0.928840E+09 0.479325E+09 0.683391E+09 0.00 0.00 0.00 0.00 2897580.86 1638786.38
August 0.104125E+10 0.528518E+09 0.713833E+09 0.00 0.00 0.00 0.00 1616751.67 3439388.73
September 0.927300E+09 0.476756E+09 0.669412E+09 0.00 0.00 0.00 0.00 242724.13 10204393.93
October 0.958781E+09 0.491623E+09 0.690846E+09 0.00 0.00 0.00 0.00 17177.23 19858874.56
November 0.945949E+09 0.482905E+09 0.672829E+09 0.00 0.00 0.00 0.00 0.00 37739883.04
December 0.928840E+09 0.479325E+09 0.683391E+09 0.00 0.00 0.00 0.00 0.00 57679967.18
                   
Annual Sum or Average 0.115285E+11 0.589995E+10 0.820442E+10         8416775.21 0.316340E+09
Minimum of Months 0.871697E+09 0.447022E+09 0.625924E+09 0.00 0.00 0.00 0.00 0.00 1638786.38
Maximum of Months 0.104125E+10 0.528518E+09 0.713833E+09 0.00 0.00 0.00 0.00 2897580.86 57679967.18



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.145270E+09 53660736.00 0.380621E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.132075E+09 48792528.00 0.344852E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.157764E+09 57687840.00 0.393285E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.140500E+09 52038000.00 0.368812E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.151517E+09 55674288.00 0.386953E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.151284E+09 55393920.00 0.379252E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.140733E+09 52318368.00 0.376513E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.157764E+09 57687840.00 0.393285E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.140500E+09 52038000.00 0.368812E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.145270E+09 53660736.00 0.380621E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.143326E+09 52709184.00 0.370694E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.140733E+09 52318368.00 0.376513E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.174674E+10 0.643980E+09 0.452021E+10            
Minimum of Months 0.132075E+09 48792528.00 0.344852E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.157764E+09 57687840.00 0.393285E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.363175E+09 0.199522E+09 0.475850E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.330188E+09 0.181421E+09 0.431132E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.394411E+09 0.214496E+09 0.491683E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.351250E+09 0.193489E+09 0.461086E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.378793E+09 0.207009E+09 0.483766E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.378210E+09 0.205967E+09 0.474138E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.351833E+09 0.194531E+09 0.470715E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.394411E+09 0.214496E+09 0.491683E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.351250E+09 0.193489E+09 0.461086E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.363175E+09 0.199522E+09 0.475850E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.358314E+09 0.195984E+09 0.463440E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.351833E+09 0.194531E+09 0.470715E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.436684E+10 0.239446E+10 0.565114E+10            
Minimum of Months 0.330188E+09 0.181421E+09 0.431132E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.394411E+09 0.214496E+09 0.491683E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.435809E+09 0.239427E+09 0.571019E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.396226E+09 0.217706E+09 0.517358E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.473293E+09 0.257395E+09 0.590019E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.421500E+09 0.232187E+09 0.553303E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.454551E+09 0.248411E+09 0.580519E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.453852E+09 0.247160E+09 0.568965E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.422200E+09 0.233437E+09 0.564857E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.473293E+09 0.257395E+09 0.590019E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.421500E+09 0.232187E+09 0.553303E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.435809E+09 0.239427E+09 0.571019E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.429977E+09 0.235181E+09 0.556128E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.422200E+09 0.233437E+09 0.564857E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.524021E+10 0.287335E+10 0.678137E+10            
Minimum of Months 0.396226E+09 0.217706E+09 0.517358E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.473293E+09 0.257395E+09 0.590019E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.290332E+09 0.234600E+09 0.976954E+09 0.00 0.00 0.00 0.00 0.00 0.192625E+09
February 0.263900E+09 0.172314E+09 0.885145E+09 0.00 0.00 0.00 0.00 0.00 0.168212E+09
March 0.315131E+09 0.170169E+09 0.100946E+10 0.00 0.00 0.00 0.00 0.00 0.127842E+09
April 0.280655E+09 0.115689E+09 0.946644E+09 0.00 0.00 0.00 0.00 372870.27 0.101944E+09
May 0.302732E+09 89712890.38 0.993207E+09 0.00 0.00 0.00 0.00 1466808.49 39418822.95
June 0.302187E+09 80762985.48 0.973440E+09 0.00 0.00 0.00 0.00 4484201.35 18224251.63
July 0.281199E+09 76976894.47 0.966411E+09 0.00 0.00 0.00 0.00 5200543.91 10344669.96
August 0.315131E+09 0.118791E+09 0.100946E+10 0.00 0.00 0.00 0.00 2293952.96 18759914.14
September 0.280655E+09 0.133179E+09 0.946644E+09 0.00 0.00 0.00 0.00 208422.74 42228968.23
October 0.290332E+09 0.184770E+09 0.976954E+09 0.00 0.00 0.00 0.00 0.00 72099239.73
November 0.286522E+09 0.223490E+09 0.951476E+09 0.00 0.00 0.00 0.00 0.00 0.129995E+09
December 0.281199E+09 0.241405E+09 0.966411E+09 0.00 0.00 0.00 0.00 0.00 0.193280E+09
                   
Annual Sum or Average 0.348998E+10 0.184186E+10 0.116022E+11         14026799.72 0.111497E+10
Minimum of Months 0.263900E+09 76976894.47 0.885145E+09 0.00 0.00 0.00 0.00 0.00 10344669.96
Maximum of Months 0.315131E+09 0.241405E+09 0.100946E+10 0.00 0.00 0.00 0.00 5200543.91 0.193280E+09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.357364E+10 0.596260E+09 0.171665E+10 0.00 0.00 0.00 0.00 0.00 0.239768E+09
February 0.324905E+10 0.484985E+09 0.155533E+10 0.00 0.00 0.00 0.00 0.00 0.210551E+09
March 0.388101E+10 0.536068E+09 0.177377E+10 0.00 0.00 0.00 0.00 0.00 0.159599E+09
April 0.345630E+10 0.417148E+09 0.166339E+10 0.00 0.00 0.00 0.00 430791.28 0.126073E+09
May 0.372732E+10 0.387830E+09 0.174521E+10 0.00 0.00 0.00 0.00 1787290.79 47380066.07
June 0.372158E+10 0.380822E+09 0.171047E+10 0.00 0.00 0.00 0.00 5992827.10 21017956.96
July 0.346204E+10 0.358159E+09 0.169812E+10 0.00 0.00 0.00 0.00 6823888.68 11789342.34
August 0.388101E+10 0.456071E+09 0.177377E+10 0.00 0.00 0.00 0.00 3008138.67 21772281.44
September 0.345630E+10 0.445024E+09 0.166339E+10 0.00 0.00 0.00 0.00 249261.29 51704084.06
October 0.357364E+10 0.529965E+09 0.171665E+10 0.00 0.00 0.00 0.00 0.00 89889568.82
November 0.352581E+10 0.587286E+09 0.167188E+10 0.00 0.00 0.00 0.00 0.00 0.162512E+09
December 0.346204E+10 0.609695E+09 0.169812E+10 0.00 0.00 0.00 0.00 0.00 0.240732E+09
                   
Annual Sum or Average 0.429697E+11 0.578931E+10 0.203867E+11         18292197.82 0.138279E+10
Minimum of Months 0.324905E+10 0.358159E+09 0.155533E+10 0.00 0.00 0.00 0.00 0.00 11789342.34
Maximum of Months 0.388101E+10 0.609695E+09 0.177377E+10 0.00 0.00 0.00 0.00 6823888.68 0.240732E+09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.167978E+09 0.234719E+09 0.565238E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.152685E+09 0.213384E+09 0.512120E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.182326E+09 0.252111E+09 0.584045E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.162379E+09 0.227547E+09 0.547701E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.175152E+09 0.243415E+09 0.574641E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.174837E+09 0.242100E+09 0.563204E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.162694E+09 0.228861E+09 0.559138E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.182326E+09 0.252111E+09 0.584045E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.162379E+09 0.227547E+09 0.547701E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.167978E+09 0.234719E+09 0.565238E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.165773E+09 0.230567E+09 0.550497E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.162694E+09 0.228861E+09 0.559138E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.201920E+10 0.281594E+10 0.671270E+10            
Minimum of Months 0.152685E+09 0.213384E+09 0.512120E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.182326E+09 0.252111E+09 0.584045E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.177310E+09 0.247759E+09 0.596640E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.161167E+09 0.225238E+09 0.540571E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.192455E+09 0.266117E+09 0.616492E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.171400E+09 0.240188E+09 0.578129E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.184883E+09 0.256938E+09 0.606566E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.184550E+09 0.255550E+09 0.594494E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.171732E+09 0.241576E+09 0.590201E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.192455E+09 0.266117E+09 0.616492E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.171400E+09 0.240188E+09 0.578129E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.177310E+09 0.247759E+09 0.596640E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.174983E+09 0.243376E+09 0.581080E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.171732E+09 0.241576E+09 0.590201E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.213138E+10 0.297238E+10 0.708563E+10            
Minimum of Months 0.161167E+09 0.225238E+09 0.540571E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.192455E+09 0.266117E+09 0.616492E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.876181E+09 0.122431E+10 0.243541E+10 0.00 0.00 0.00 0.00 0.00 0.129367E+09
February 0.796412E+09 0.111302E+10 0.220654E+10 0.00 0.00 0.00 0.00 0.00 0.113599E+09
March 0.951022E+09 0.131502E+10 0.251644E+10 0.00 0.00 0.00 0.00 0.00 85963709.86
April 0.846975E+09 0.118689E+10 0.235985E+10 0.00 0.00 0.00 0.00 268995.26 68614110.04
May 0.913602E+09 0.126967E+10 0.247592E+10 0.00 0.00 0.00 0.00 963859.00 26295826.49
June 0.911959E+09 0.126281E+10 0.242665E+10 0.00 0.00 0.00 0.00 3055808.32 12212235.56
July 0.848618E+09 0.119375E+10 0.240913E+10 0.00 0.00 0.00 0.00 3465839.86 7046421.84
August 0.951022E+09 0.131502E+10 0.251644E+10 0.00 0.00 0.00 0.00 1581730.05 12464142.54
September 0.846975E+09 0.118689E+10 0.235985E+10 0.00 0.00 0.00 0.00 133003.21 28490651.08
October 0.876181E+09 0.122431E+10 0.243541E+10 0.00 0.00 0.00 0.00 0.00 49132362.95
November 0.864681E+09 0.120265E+10 0.237189E+10 0.00 0.00 0.00 0.00 0.00 88682097.04
December 0.848618E+09 0.119375E+10 0.240913E+10 0.00 0.00 0.00 0.00 0.00 0.130564E+09
                   
Annual Sum or Average 0.105322E+11 0.146881E+11 0.289226E+11         9469235.70 0.752431E+09
Minimum of Months 0.796412E+09 0.111302E+10 0.220654E+10 0.00 0.00 0.00 0.00 0.00 7046421.84
Maximum of Months 0.951022E+09 0.131502E+10 0.251644E+10 0.00 0.00 0.00 0.00 3465839.86 0.130564E+09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 X-RAY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.217905E+10 0.750204E+09 0.142742E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.198113E+10 0.682144E+09 0.129327E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.236647E+10 0.806505E+09 0.147491E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.210750E+10 0.727518E+09 0.138313E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.227276E+10 0.778355E+09 0.145116E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.226926E+10 0.774435E+09 0.142228E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.211100E+10 0.731437E+09 0.141201E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.236647E+10 0.806505E+09 0.147491E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.210750E+10 0.727518E+09 0.138313E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.217905E+10 0.750204E+09 0.142742E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.214988E+10 0.736901E+09 0.139019E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.211100E+10 0.731437E+09 0.141201E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.262011E+11 0.900317E+10 0.169518E+12            
Minimum of Months 0.198113E+10 0.682144E+09 0.129327E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.236647E+10 0.806505E+09 0.147491E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 21774919.01 30426579.93 73271509.94 0.00 0.00 0.00 0.00 0.00 24570577.28
February 19792494.09 27660832.76 66385832.97 0.00 0.00 0.00 0.00 0.00 21506537.45
March 23634860.01 32681047.04 75709500.82 0.00 0.00 0.00 0.00 0.00 16325202.19
April 21049088.38 29496781.69 70998248.16 0.00 0.00 0.00 0.00 58528.86 12912478.60
May 22704889.51 31553813.48 74490505.38 0.00 0.00 0.00 0.00 187081.69 4821674.08
June 22664061.54 31383386.80 73007943.35 0.00 0.00 0.00 0.00 625240.66 2147725.66
July 21089916.35 29667208.38 72480810.19 0.00 0.00 0.00 0.00 718040.41 1151852.87
August 23634860.01 32681047.04 75709500.82 0.00 0.00 0.00 0.00 330165.89 2152327.45
September 21049088.38 29496781.69 70998248.16 0.00 0.00 0.00 0.00 30184.34 5207178.95
October 21774919.01 30426579.93 73271509.94 0.00 0.00 0.00 0.00 0.00 9200007.79
November 21489123.20 29888291.23 71360652.21 0.00 0.00 0.00 0.00 0.00 16699459.50
December 21089916.35 29667208.38 72480810.19 0.00 0.00 0.00 0.00 0.00 24698182.04
                   
Annual Sum or Average 0.261748E+09 0.365030E+09 0.870165E+09         1949241.85 0.141393E+09
Minimum of Months 19792494.09 27660832.76 66385832.97 0.00 0.00 0.00 0.00 0.00 1151852.87
Maximum of Months 23634860.01 32681047.04 75709500.82 0.00 0.00 0.00 0.00 718040.41 24698182.04



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 55992648.88 78239776.95 0.188413E+09 0.00 0.00 0.00 0.00 0.00 63359428.12
February 50894984.80 71127855.67 0.170707E+09 0.00 0.00 0.00 0.00 0.00 55499763.15
March 60775354.31 84036978.11 0.194682E+09 0.00 0.00 0.00 0.00 0.00 42179213.19
April 54126227.25 75848867.21 0.182567E+09 0.00 0.00 0.00 0.00 141233.68 33446923.27
May 58384001.59 81138377.53 0.191547E+09 0.00 0.00 0.00 0.00 469319.88 12592906.06
June 58279015.38 80700137.49 0.187735E+09 0.00 0.00 0.00 0.00 1564441.97 5674066.92
July 54231213.47 76287107.26 0.186379E+09 0.00 0.00 0.00 0.00 1795292.87 3083638.71
August 60775354.31 84036978.11 0.194682E+09 0.00 0.00 0.00 0.00 818283.79 5694422.29
September 54126227.25 75848867.21 0.182567E+09 0.00 0.00 0.00 0.00 72491.86 13587875.29
October 55992648.88 78239776.95 0.188413E+09 0.00 0.00 0.00 0.00 0.00 23856040.32
November 55257745.36 76855606.03 0.183499E+09 0.00 0.00 0.00 0.00 0.00 43178714.73
December 54231213.47 76287107.26 0.186379E+09 0.00 0.00 0.00 0.00 0.00 63700290.68
                   
Annual Sum or Average 0.673067E+09 0.938647E+09 0.223757E+10         4861064.04 0.365853E+09
Minimum of Months 50894984.80 71127855.67 0.170707E+09 0.00 0.00 0.00 0.00 0.00 3083638.71
Maximum of Months 60775354.31 84036978.11 0.194682E+09 0.00 0.00 0.00 0.00 1795292.87 63700290.68



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 LOCKER

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.217905E+09 80491104.00 0.570931E+09 0.00 0.00 0.00 0.00 0.00 70312305.11
February 0.198113E+09 73188792.00 0.517278E+09 0.00 0.00 0.00 0.00 0.00 61518700.60
March 0.236647E+09 86531760.00 0.589928E+09 0.00 0.00 0.00 0.00 0.00 46804722.29
April 0.210750E+09 78057000.00 0.553218E+09 0.00 0.00 0.00 0.00 140458.10 37328401.61
May 0.227276E+09 83511432.00 0.580429E+09 0.00 0.00 0.00 0.00 498891.28 14340610.40
June 0.226926E+09 83090880.00 0.568877E+09 0.00 0.00 0.00 0.00 1619392.51 6631066.70
July 0.211100E+09 78477552.00 0.564770E+09 0.00 0.00 0.00 0.00 1837715.46 3725995.53
August 0.236647E+09 86531760.00 0.589928E+09 0.00 0.00 0.00 0.00 829448.00 6642643.94
September 0.210750E+09 78057000.00 0.553218E+09 0.00 0.00 0.00 0.00 71776.29 15385150.89
October 0.217905E+09 80491104.00 0.570931E+09 0.00 0.00 0.00 0.00 0.00 26650751.09
November 0.214988E+09 79063776.00 0.556042E+09 0.00 0.00 0.00 0.00 0.00 47941678.26
December 0.211100E+09 78477552.00 0.564770E+09 0.00 0.00 0.00 0.00 0.00 70652464.14
                   
Annual Sum or Average 0.262011E+10 0.965970E+09 0.678032E+10         4997681.65 0.407934E+09
Minimum of Months 0.198113E+09 73188792.00 0.517278E+09 0.00 0.00 0.00 0.00 0.00 3725995.53
Maximum of Months 0.236647E+09 86531760.00 0.589928E+09 0.00 0.00 0.00 0.00 1837715.46 70652464.14



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.137825E+10 0.399971E+09 0.361114E+10 0.00 0.00 0.00 0.00 0.00 3707174.52
February 0.125306E+10 0.335878E+09 0.327178E+10 0.00 0.00 0.00 0.00 0.00 3250323.58
March 0.149679E+10 0.374211E+09 0.373129E+10 0.00 0.00 0.00 0.00 0.00 2469465.57
April 0.133299E+10 0.313433E+09 0.349910E+10 0.00 0.00 0.00 0.00 6194.81 1983382.87
May 0.143752E+10 0.312333E+09 0.367122E+10 0.00 0.00 0.00 0.00 25626.60 769868.77
June 0.143531E+10 0.306246E+09 0.359815E+10 0.00 0.00 0.00 0.00 81205.78 360168.53
July 0.133521E+10 0.291139E+09 0.357217E+10 0.00 0.00 0.00 0.00 91634.96 206370.92
August 0.149679E+10 0.340264E+09 0.373129E+10 0.00 0.00 0.00 0.00 40860.47 362458.15
September 0.133299E+10 0.324835E+09 0.349910E+10 0.00 0.00 0.00 0.00 3705.04 824416.74
October 0.137825E+10 0.364281E+09 0.361114E+10 0.00 0.00 0.00 0.00 0.00 1416030.42
November 0.135980E+10 0.387760E+09 0.351696E+10 0.00 0.00 0.00 0.00 0.00 2537191.87
December 0.133521E+10 0.398705E+09 0.357217E+10 0.00 0.00 0.00 0.00 0.00 3725406.22
                   
Annual Sum or Average 0.165722E+11 0.414906E+10 0.428855E+11         249227.66 21612258.17
Minimum of Months 0.125306E+10 0.291139E+09 0.327178E+10 0.00 0.00 0.00 0.00 0.00 206370.92
Maximum of Months 0.149679E+10 0.399971E+09 0.373129E+10 0.00 0.00 0.00 0.00 91634.96 3725406.22



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.157402E+10 0.193104E+10 0.529649E+10 0.00 0.00 0.00 0.00 0.00 9392338.77
February 0.143071E+10 0.166304E+10 0.479875E+10 0.00 0.00 0.00 0.00 0.00 8218135.95
March 0.170846E+10 0.189329E+10 0.547272E+10 0.00 0.00 0.00 0.00 0.00 6251260.44
April 0.152155E+10 0.162293E+10 0.513216E+10 0.00 0.00 0.00 0.00 19796.27 4996527.93
May 0.164124E+10 0.160475E+10 0.538460E+10 0.00 0.00 0.00 0.00 70061.46 1915172.65
June 0.163829E+10 0.156214E+10 0.527743E+10 0.00 0.00 0.00 0.00 222357.80 883109.47
July 0.152450E+10 0.148659E+10 0.523933E+10 0.00 0.00 0.00 0.00 251936.79 499740.26
August 0.170846E+10 0.173382E+10 0.547272E+10 0.00 0.00 0.00 0.00 115260.34 890330.85
September 0.152155E+10 0.165689E+10 0.513216E+10 0.00 0.00 0.00 0.00 9857.90 2058157.97
October 0.157402E+10 0.182514E+10 0.529649E+10 0.00 0.00 0.00 0.00 0.00 3556015.10
November 0.155336E+10 0.187871E+10 0.515836E+10 0.00 0.00 0.00 0.00 0.00 6401677.22
December 0.152450E+10 0.190178E+10 0.523933E+10 0.00 0.00 0.00 0.00 0.00 9443642.59
                   
Annual Sum or Average 0.189207E+11 0.207601E+11 0.629005E+11         689270.57 54506109.20
Minimum of Months 0.143071E+10 0.148659E+10 0.479875E+10 0.00 0.00 0.00 0.00 0.00 499740.26
Maximum of Months 0.170846E+10 0.193104E+10 0.547272E+10 0.00 0.00 0.00 0.00 251936.79 9443642.59



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.314751E+10 0.104904E+10 0.309350E+10 0.00 0.00 0.00 0.00 0.00 27623979.26
February 0.286163E+10 0.953873E+09 0.280279E+10 0.00 0.00 0.00 0.00 0.00 24064982.89
March 0.341823E+10 0.112777E+10 0.319643E+10 0.00 0.00 0.00 0.00 0.00 17942112.75
April 0.304417E+10 0.101732E+10 0.299752E+10 0.00 0.00 0.00 0.00 105992.56 13725168.68
May 0.328287E+10 0.108841E+10 0.314497E+10 0.00 0.00 0.00 0.00 332355.09 4606067.96
June 0.327782E+10 0.108293E+10 0.308237E+10 0.00 0.00 0.00 0.00 1055160.63 1707018.99
July 0.304922E+10 0.102280E+10 0.306012E+10 0.00 0.00 0.00 0.00 1221201.29 801811.95
August 0.341823E+10 0.112777E+10 0.319643E+10 0.00 0.00 0.00 0.00 618736.44 1658342.27
September 0.304417E+10 0.101732E+10 0.299752E+10 0.00 0.00 0.00 0.00 70354.15 5017713.26
October 0.314751E+10 0.104904E+10 0.309350E+10 0.00 0.00 0.00 0.00 0.00 9566793.04
November 0.310539E+10 0.103044E+10 0.301283E+10 0.00 0.00 0.00 0.00 0.00 18083418.60
December 0.304922E+10 0.102280E+10 0.306012E+10 0.00 0.00 0.00 0.00 0.00 27629353.87
                   
Annual Sum or Average 0.378460E+11 0.125895E+11 0.367381E+11         3403800.16 0.152427E+09
Minimum of Months 0.286163E+10 0.953873E+09 0.280279E+10 0.00 0.00 0.00 0.00 0.00 801811.95
Maximum of Months 0.341823E+10 0.112777E+10 0.319643E+10 0.00 0.00 0.00 0.00 1221201.29 27629353.87



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.143333E+10 0.477719E+09 0.140873E+10 0.00 0.00 0.00 0.00 0.00 0.336101E+09
February 0.130314E+10 0.434379E+09 0.127635E+10 0.00 0.00 0.00 0.00 0.00 0.291230E+09
March 0.155661E+10 0.513570E+09 0.145561E+10 0.00 0.00 0.00 0.00 0.00 0.217440E+09
April 0.138627E+10 0.463272E+09 0.136503E+10 0.00 0.00 0.00 0.00 1478770.34 0.165599E+09
May 0.149497E+10 0.495645E+09 0.143217E+10 0.00 0.00 0.00 0.00 4873078.10 55326920.92
June 0.149267E+10 0.493149E+09 0.140367E+10 0.00 0.00 0.00 0.00 14504672.06 20385329.28
July 0.138857E+10 0.465768E+09 0.139353E+10 0.00 0.00 0.00 0.00 16643043.26 9331850.70
August 0.155661E+10 0.513570E+09 0.145561E+10 0.00 0.00 0.00 0.00 9214657.91 19725501.55
September 0.138627E+10 0.463272E+09 0.136503E+10 0.00 0.00 0.00 0.00 1364692.16 59775889.83
October 0.143333E+10 0.477719E+09 0.140873E+10 0.00 0.00 0.00 0.00 79317.60 0.116163E+09
November 0.141415E+10 0.469248E+09 0.137199E+10 0.00 0.00 0.00 0.00 0.00 0.220115E+09
December 0.138857E+10 0.465768E+09 0.139353E+10 0.00 0.00 0.00 0.00 0.00 0.336356E+09
                   
Annual Sum or Average 0.172345E+11 0.573308E+10 0.167300E+11         48158231.43 0.184755E+10
Minimum of Months 0.130314E+10 0.434379E+09 0.127635E+10 0.00 0.00 0.00 0.00 0.00 9331850.70
Maximum of Months 0.155661E+10 0.513570E+09 0.145561E+10 0.00 0.00 0.00 0.00 16643043.26 0.336356E+09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.115247E+10 0.757617E+09 0.830411E+09 0.00 0.00 0.00 0.00 0.00 0.271078E+09
February 0.104780E+10 0.688884E+09 0.752373E+09 0.00 0.00 0.00 0.00 0.00 0.235415E+09
March 0.125160E+10 0.814474E+09 0.858042E+09 0.00 0.00 0.00 0.00 0.00 0.176634E+09
April 0.111463E+10 0.734706E+09 0.804647E+09 0.00 0.00 0.00 0.00 1180904.90 0.135324E+09
May 0.120204E+10 0.786045E+09 0.844226E+09 0.00 0.00 0.00 0.00 3565190.20 45941660.44
June 0.120019E+10 0.782087E+09 0.827424E+09 0.00 0.00 0.00 0.00 10957730.58 17321341.77
July 0.111648E+10 0.738664E+09 0.821450E+09 0.00 0.00 0.00 0.00 12726863.58 7977493.31
August 0.125160E+10 0.814474E+09 0.858042E+09 0.00 0.00 0.00 0.00 6867032.36 16851586.92
September 0.111463E+10 0.734706E+09 0.804647E+09 0.00 0.00 0.00 0.00 1013039.82 49786902.79
October 0.115247E+10 0.757617E+09 0.830411E+09 0.00 0.00 0.00 0.00 33147.30 95244722.44
November 0.113705E+10 0.744182E+09 0.808755E+09 0.00 0.00 0.00 0.00 0.00 0.178888E+09
December 0.111648E+10 0.738664E+09 0.821450E+09 0.00 0.00 0.00 0.00 0.00 0.271458E+09
                   
Annual Sum or Average 0.138574E+11 0.909212E+10 0.986188E+10         36343908.74 0.150192E+10
Minimum of Months 0.104780E+10 0.688884E+09 0.752373E+09 0.00 0.00 0.00 0.00 0.00 7977493.31
Maximum of Months 0.125160E+10 0.814474E+09 0.858042E+09 0.00 0.00 0.00 0.00 12726863.58 0.271458E+09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.297591E+09 0.415830E+09 0.100138E+10 0.00 0.00 0.00 0.00 0.00 14520729.40
February 0.270497E+09 0.378031E+09 0.907273E+09 0.00 0.00 0.00 0.00 0.00 12723897.45
March 0.323010E+09 0.446641E+09 0.103470E+10 0.00 0.00 0.00 0.00 0.00 9696262.31
April 0.287671E+09 0.403123E+09 0.970310E+09 0.00 0.00 0.00 0.00 20290.72 7799895.22
May 0.310300E+09 0.431235E+09 0.101804E+10 0.00 0.00 0.00 0.00 104995.87 3083011.77
June 0.309742E+09 0.428906E+09 0.997776E+09 0.00 0.00 0.00 0.00 309573.75 1450957.71
July 0.288229E+09 0.405452E+09 0.990572E+09 0.00 0.00 0.00 0.00 352952.22 834882.06
August 0.323010E+09 0.446641E+09 0.103470E+10 0.00 0.00 0.00 0.00 157278.79 1478000.20
September 0.287671E+09 0.403123E+09 0.970310E+09 0.00 0.00 0.00 0.00 15040.47 3252671.75
October 0.297591E+09 0.415830E+09 0.100138E+10 0.00 0.00 0.00 0.00 0.00 5515109.30
November 0.293685E+09 0.408473E+09 0.975263E+09 0.00 0.00 0.00 0.00 0.00 9820455.50
December 0.288229E+09 0.405452E+09 0.990572E+09 0.00 0.00 0.00 0.00 0.00 14554626.93
                   
Annual Sum or Average 0.357722E+10 0.498874E+10 0.118923E+11         960131.83 84730499.60
Minimum of Months 0.270497E+09 0.378031E+09 0.907273E+09 0.00 0.00 0.00 0.00 0.00 834882.06
Maximum of Months 0.323010E+09 0.446641E+09 0.103470E+10 0.00 0.00 0.00 0.00 352952.22 14554626.93



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 16240630.93 8911442.72 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 14767248.81 8073991.50 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 17459449.66 9207956.55 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 15749503.56 8634963.61 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 16850040.30 9059699.64 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 16765185.83 8879387.17 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 15834358.03 8815276.07 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 17459449.66 9207956.55 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 15749503.56 8634963.61 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 16240630.93 8911442.72 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 15952640.01 8679039.99 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 15834358.03 8815276.07 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.194903E+09 0.105831E+09            
Minimum of Months 0.00 14767248.81 8073991.50 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 17459449.66 9207956.55 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.155980E+09 0.777149E+09 0.00 0.00 0.00 0.00 0.00 24576978.13
February 0.00 0.141829E+09 0.704116E+09 0.00 0.00 0.00 0.00 0.00 21544989.19
March 0.00 0.167686E+09 0.803007E+09 0.00 0.00 0.00 0.00 0.00 16122479.18
April 0.00 0.151263E+09 0.753038E+09 0.00 0.00 0.00 0.00 54318.21 12621988.75
May 0.00 0.161833E+09 0.790078E+09 0.00 0.00 0.00 0.00 183280.13 4693606.56
June 0.00 0.161018E+09 0.774353E+09 0.00 0.00 0.00 0.00 579257.56 2138642.78
July 0.00 0.152078E+09 0.768762E+09 0.00 0.00 0.00 0.00 648305.82 1248954.46
August 0.00 0.167686E+09 0.803007E+09 0.00 0.00 0.00 0.00 283155.82 2309122.55
September 0.00 0.151263E+09 0.753038E+09 0.00 0.00 0.00 0.00 25253.31 5250864.03
October 0.00 0.155980E+09 0.777149E+09 0.00 0.00 0.00 0.00 0.00 9171703.34
November 0.00 0.153214E+09 0.756881E+09 0.00 0.00 0.00 0.00 0.00 16795597.54
December 0.00 0.152078E+09 0.768762E+09 0.00 0.00 0.00 0.00 0.00 24851715.90
                   
Annual Sum or Average   0.187191E+10 0.922934E+10         1773570.85 0.141327E+09
Minimum of Months 0.00 0.141829E+09 0.704116E+09 0.00 0.00 0.00 0.00 0.00 1248954.46
Maximum of Months 0.00 0.167686E+09 0.803007E+09 0.00 0.00 0.00 0.00 648305.82 24851715.90



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.144839E+09 0.535737E+10 0.00 0.00 0.00 0.00 0.00 71198870.46
February 0.00 0.131698E+09 0.485981E+10 0.00 0.00 0.00 0.00 0.00 62250148.12
March 0.00 0.155708E+09 0.564605E+10 0.00 0.00 0.00 0.00 0.00 46640680.30
April 0.00 0.140458E+09 0.518536E+10 0.00 0.00 0.00 0.00 178945.39 36291027.46
May 0.00 0.150273E+09 0.550171E+10 0.00 0.00 0.00 0.00 478901.78 13447597.55
June 0.00 0.149517E+09 0.543208E+10 0.00 0.00 0.00 0.00 1650116.08 6072373.49
July 0.00 0.141215E+09 0.525499E+10 0.00 0.00 0.00 0.00 1785786.77 3351447.55
August 0.00 0.155708E+09 0.564605E+10 0.00 0.00 0.00 0.00 747970.85 6364876.21
September 0.00 0.140458E+09 0.518536E+10 0.00 0.00 0.00 0.00 72236.67 14948512.03
October 0.00 0.144839E+09 0.535737E+10 0.00 0.00 0.00 0.00 0.02 26394741.35
November 0.00 0.142270E+09 0.524579E+10 0.00 0.00 0.00 0.00 0.00 48705445.10
December 0.00 0.141215E+09 0.525499E+10 0.00 0.00 0.00 0.00 0.00 71866349.58
                   
Annual Sum or Average   0.173820E+10 0.639269E+11         4913957.55 0.407532E+09
Minimum of Months 0.00 0.131698E+09 0.485981E+10 0.00 0.00 0.00 0.00 0.00 3351447.55
Maximum of Months 0.00 0.155708E+09 0.564605E+10 0.00 0.00 0.00 0.00 1785786.77 71866349.58



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 IT HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 74541665.44 88907770.82 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 67779098.26 80552679.05 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 80135830.96 91866032.98 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 72287476.38 86149391.24 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 77338748.20 90386901.90 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 76949280.98 88587958.69 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 72676943.60 87948334.44 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 80135830.96 91866032.98 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 72287476.38 86149391.24 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 74541665.44 88907770.82 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 73219837.30 86589132.91 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 72676943.60 87948334.44 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.894571E+09 0.105586E+10            
Minimum of Months 0.00 67779098.26 80552679.05 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 80135830.96 91866032.98 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.127786E+09 0.152413E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.116193E+09 0.138090E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.137376E+09 0.157485E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.123921E+09 0.147685E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.132581E+09 0.154949E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.131913E+09 0.151865E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.124589E+09 0.150769E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.137376E+09 0.157485E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.123921E+09 0.147685E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.127786E+09 0.152413E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.125520E+09 0.148438E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.124589E+09 0.150769E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.153355E+10 0.181004E+10            
Minimum of Months 0.00 0.116193E+09 0.138090E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.137376E+09 0.157485E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 25526594.02 34293067.55 0.00 0.00 0.00 0.00 0.00 20114455.88
February 0.00 23210770.97 31070382.70 0.00 0.00 0.00 0.00 0.00 17462673.92
March 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 0.00 12937697.64
April 0.00 24754653.00 33229118.96 0.00 0.00 0.00 0.00 88758.83 9657920.67
May 0.00 26484447.53 34863590.71 0.00 0.00 0.00 0.00 299778.41 3151142.27
June 0.00 26351075.52 34169711.20 0.00 0.00 0.00 0.00 880847.73 1154633.16
July 0.00 24888025.01 33922998.48 0.00 0.00 0.00 0.00 998299.12 537583.15
August 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 545806.12 1140794.85
September 0.00 24754653.00 33229118.96 0.00 0.00 0.00 0.00 83309.44 3424298.95
October 0.00 25526594.02 34293067.55 0.00 0.00 0.00 0.00 5507.97 6800353.14
November 0.00 25073937.51 33398733.96 0.00 0.00 0.00 0.00 0.00 13182661.92
December 0.00 24888025.01 33922998.48 0.00 0.00 0.00 0.00 0.00 20213072.34
                   
Annual Sum or Average   0.306343E+09 0.407261E+09         2902307.62 0.109777E+09
Minimum of Months 0.00 23210770.97 31070382.70 0.00 0.00 0.00 0.00 0.00 537583.15
Maximum of Months 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 998299.12 20213072.34



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.264090E+09 0.314987E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.240132E+09 0.285387E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.283910E+09 0.325468E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.256104E+09 0.305215E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.274000E+09 0.320228E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.272620E+09 0.313854E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.257484E+09 0.311588E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.283910E+09 0.325468E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.256104E+09 0.305215E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.264090E+09 0.314987E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.259407E+09 0.306773E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.257484E+09 0.311588E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.316934E+10 0.374076E+10            
Minimum of Months 0.00 0.240132E+09 0.285387E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.283910E+09 0.325468E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 MED GAS

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 16240630.93 8911442.72 0.00 0.00 0.00 0.00 0.00 35862895.25
February 0.00 14767248.81 8073991.50 0.00 0.00 0.00 0.00 0.00 31095682.10
March 0.00 17459449.66 9207956.55 0.00 0.00 0.00 0.00 0.00 22999245.26
April 0.00 15749503.56 8634963.61 0.00 0.00 0.00 0.00 162529.86 17322015.20
May 0.00 16850040.30 9059699.64 0.00 0.00 0.00 0.00 581287.47 5656556.76
June 0.00 16765185.83 8879387.17 0.00 0.00 0.00 0.00 1618624.20 2059599.21
July 0.00 15834358.03 8815276.07 0.00 0.00 0.00 0.00 1732814.33 966200.68
August 0.00 17459449.66 9207956.55 0.00 0.00 0.00 0.00 901232.65 2078321.78
September 0.00 15749503.56 8634963.61 0.00 0.00 0.00 0.00 141534.57 6167925.89
October 0.00 16240630.93 8911442.72 0.00 0.00 0.00 0.00 10342.21 12188380.97
November 0.00 15952640.01 8679039.99 0.00 0.00 0.00 0.00 0.00 23463301.94
December 0.00 15834358.03 8815276.07 0.00 0.00 0.00 0.00 0.00 36101944.30
                   
Annual Sum or Average   0.194903E+09 0.105831E+09         5148365.30 0.195962E+09
Minimum of Months 0.00 14767248.81 8073991.50 0.00 0.00 0.00 0.00 0.00 966200.68
Maximum of Months 0.00 17459449.66 9207956.55 0.00 0.00 0.00 0.00 1732814.33 36101944.30



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 78268748.71 93353183.15 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 71168053.17 84580334.55 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 84142622.51 96459359.21 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 75901850.20 90456883.85 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 81205685.61 94906271.18 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 80796745.03 93017380.33 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 76310790.78 92345774.70 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 84142622.51 96459359.21 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 75901850.20 90456883.85 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 78268748.71 93353183.15 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 76880829.16 90918612.73 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 76310790.78 92345774.70 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.939299E+09 0.110865E+10            
Minimum of Months 0.00 71168053.17 84580334.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 84142622.51 96459359.21 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 25526594.02 34293067.55 0.00 0.00 0.00 0.00 0.00 20046267.25
February 0.00 23210770.97 31070382.70 0.00 0.00 0.00 0.00 0.00 17389115.75
March 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 0.00 12861213.80
April 0.00 24754653.00 33229118.96 0.00 0.00 0.00 0.00 88756.22 9645288.53
May 0.00 26484447.53 34863590.71 0.00 0.00 0.00 0.00 289487.23 3202345.93
June 0.00 26351075.52 34169711.20 0.00 0.00 0.00 0.00 830544.94 1219966.76
July 0.00 24888025.01 33922998.48 0.00 0.00 0.00 0.00 914453.20 604500.67
August 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 481165.50 1280326.21
September 0.00 24754653.00 33229118.96 0.00 0.00 0.00 0.00 65380.43 3605089.58
October 0.00 25526594.02 34293067.55 0.00 0.00 0.00 0.00 2714.34 6936050.98
November 0.00 25073937.51 33398733.96 0.00 0.00 0.00 0.00 0.00 13237113.38
December 0.00 24888025.01 33922998.48 0.00 0.00 0.00 0.00 0.00 20162139.70
                   
Annual Sum or Average   0.306343E+09 0.407261E+09         2672501.88 0.110189E+09
Minimum of Months 0.00 23210770.97 31070382.70 0.00 0.00 0.00 0.00 0.00 604500.67
Maximum of Months 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 914453.20 20162139.70



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.264090E+09 0.314987E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.240132E+09 0.285387E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.283910E+09 0.325468E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.256104E+09 0.305215E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.274000E+09 0.320228E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.272620E+09 0.313854E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.257484E+09 0.311588E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.283910E+09 0.325468E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.256104E+09 0.305215E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.264090E+09 0.314987E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.259407E+09 0.306773E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.257484E+09 0.311588E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.316934E+10 0.374076E+10            
Minimum of Months 0.00 0.240132E+09 0.285387E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.283910E+09 0.325468E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 15660608.40 8593131.60 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 14239847.06 7785593.60 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 16835897.89 8879054.14 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 15187021.29 8326528.14 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 16248253.14 8736092.87 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 16166429.19 8562221.05 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 15268845.24 8500399.96 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 16835897.89 8879054.14 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 15187021.29 8326528.14 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 15660608.40 8593131.60 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 15382902.87 8369030.14 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 15268845.24 8500399.96 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.187942E+09 0.102051E+09            
Minimum of Months 0.00 14239847.06 7785593.60 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 16835897.89 8879054.14 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 25526594.02 34293067.55 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 23210770.97 31070382.70 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 24754653.00 33229118.96 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 26484447.53 34863590.71 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 26351075.52 34169711.20 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 24888025.01 33922998.48 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 24754653.00 33229118.96 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 25526594.02 34293067.55 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 25073937.51 33398733.96 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 24888025.01 33922998.48 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.306343E+09 0.407261E+09            
Minimum of Months 0.00 23210770.97 31070382.70 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.281129E+09 0.335309E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.255624E+09 0.303799E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.302227E+09 0.346466E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.272627E+09 0.324906E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.291678E+09 0.340888E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.290209E+09 0.334103E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.274096E+09 0.331691E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.302227E+09 0.346466E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.272627E+09 0.324906E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.281129E+09 0.335309E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.276143E+09 0.326565E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.274096E+09 0.331691E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.337381E+10 0.398210E+10            
Minimum of Months 0.00 0.255624E+09 0.303799E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.302227E+09 0.346466E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 25526594.02 34293067.55 0.00 0.00 0.00 0.00 0.00 19511511.58
February 0.00 23210770.97 31070382.70 0.00 0.00 0.00 0.00 0.00 16952521.23
March 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 0.00 12567678.12
April 0.00 24754653.00 33229118.96 0.00 0.00 0.00 0.00 88757.27 9527963.90
May 0.00 26484447.53 34863590.71 0.00 0.00 0.00 0.00 299204.27 3132071.94
June 0.00 26351075.52 34169711.20 0.00 0.00 0.00 0.00 863519.22 1149316.29
July 0.00 24888025.01 33922998.48 0.00 0.00 0.00 0.00 969474.45 553997.21
August 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 520781.52 1170850.69
September 0.00 24754653.00 33229118.96 0.00 0.00 0.00 0.00 78067.81 3419926.58
October 0.00 25526594.02 34293067.55 0.00 0.00 0.00 0.00 3472.04 6720170.70
November 0.00 25073937.51 33398733.96 0.00 0.00 0.00 0.00 0.00 12899423.65
December 0.00 24888025.01 33922998.48 0.00 0.00 0.00 0.00 0.00 19659031.09
                   
Annual Sum or Average   0.306343E+09 0.407261E+09         2823276.58 0.107264E+09
Minimum of Months 0.00 23210770.97 31070382.70 0.00 0.00 0.00 0.00 0.00 553997.21
Maximum of Months 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 969474.45 19659031.09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 68152379.83 81287018.65 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 61969461.27 73648085.69 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 73267045.45 83991712.62 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 66091406.98 78765074.28 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 70709712.64 82639365.64 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 70353628.32 80994619.30 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 66447491.29 80409820.61 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 73267045.45 83991712.62 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 66091406.98 78765074.28 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 68152379.83 81287018.65 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 66943851.25 79167123.38 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 66447491.29 80409820.61 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.817893E+09 0.965356E+09            
Minimum of Months 0.00 61969461.27 73648085.69 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 73267045.45 83991712.62 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 SCRUB

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 44724999.26 53344630.77 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 40667458.96 48331578.69 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 48081498.57 55119587.01 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 43372485.83 51689604.01 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 46403248.92 54232108.89 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 46169568.59 53152743.61 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 43606166.16 52768969.29 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 48081498.57 55119587.01 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 43372485.83 51689604.01 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 44724999.26 53344630.77 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 43931902.38 51953448.85 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 43606166.16 52768969.29 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.536742E+09 0.633515E+09            
Minimum of Months 0.00 40667458.96 48331578.69 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 48081498.57 55119587.01 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.327983E+09 0.391194E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.298228E+09 0.354432E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.352598E+09 0.404211E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.318065E+09 0.379057E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.340290E+09 0.397702E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.338577E+09 0.389787E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.319779E+09 0.386973E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.352598E+09 0.404211E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.318065E+09 0.379057E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.327983E+09 0.391194E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.322167E+09 0.380992E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.319779E+09 0.386973E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.393611E+10 0.464578E+10            
Minimum of Months 0.00 0.298228E+09 0.354432E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.352598E+09 0.404211E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.114844E+09 63016404.11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.104426E+09 57094448.86 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.123463E+09 65113172.95 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.111371E+09 61061308.83 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.119154E+09 64064788.53 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.118554E+09 62789726.39 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.111972E+09 62336370.97 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.123463E+09 65113172.95 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.111371E+09 61061308.83 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.114844E+09 63016404.11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.112808E+09 61372990.69 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.111972E+09 62336370.97 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.137824E+10 0.748376E+09            
Minimum of Months 0.00 0.104426E+09 57094448.86 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.123463E+09 65113172.95 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.266810E+09 0.146402E+09 0.00 0.00 0.00 0.00 0.00 84315750.41
February 0.00 0.242605E+09 0.132644E+09 0.00 0.00 0.00 0.00 0.00 73116383.76
March 0.00 0.286834E+09 0.151273E+09 0.00 0.00 0.00 0.00 0.00 54126825.31
April 0.00 0.258742E+09 0.141860E+09 0.00 0.00 0.00 0.00 379005.56 40730775.75
May 0.00 0.276822E+09 0.148837E+09 0.00 0.00 0.00 0.00 1229633.86 13436826.81
June 0.00 0.275428E+09 0.145875E+09 0.00 0.00 0.00 0.00 3398394.01 5042936.51
July 0.00 0.260136E+09 0.144822E+09 0.00 0.00 0.00 0.00 3602918.65 2607174.24
August 0.00 0.286834E+09 0.151273E+09 0.00 0.00 0.00 0.00 1919109.29 5417731.11
September 0.00 0.258742E+09 0.141860E+09 0.00 0.00 0.00 0.00 287136.46 14857323.52
October 0.00 0.266810E+09 0.146402E+09 0.00 0.00 0.00 0.00 20576.92 28715730.97
November 0.00 0.262079E+09 0.142584E+09 0.00 0.00 0.00 0.00 0.00 55104168.43
December 0.00 0.260136E+09 0.144822E+09 0.00 0.00 0.00 0.00 0.00 84746777.14
                   
Annual Sum or Average   0.320198E+10 0.173865E+10         10836774.74 0.462218E+09
Minimum of Months 0.00 0.242605E+09 0.132644E+09 0.00 0.00 0.00 0.00 0.00 2607174.24
Maximum of Months 0.00 0.286834E+09 0.151273E+09 0.00 0.00 0.00 0.00 3602918.65 84746777.14



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.104358E+09 0.124471E+09 0.00 0.00 0.00 0.00 0.00 46744308.00
February 0.00 94890737.57 0.112774E+09 0.00 0.00 0.00 0.00 0.00 40608510.09
March 0.00 0.112190E+09 0.128612E+09 0.00 0.00 0.00 0.00 0.00 30238157.49
April 0.00 0.101202E+09 0.120609E+09 0.00 0.00 0.00 0.00 136568.21 23248523.29
May 0.00 0.108274E+09 0.126542E+09 0.00 0.00 0.00 0.00 464634.43 8346826.27
June 0.00 0.107729E+09 0.124023E+09 0.00 0.00 0.00 0.00 1324304.82 3624458.94
July 0.00 0.101748E+09 0.123128E+09 0.00 0.00 0.00 0.00 1478473.23 2087467.74
August 0.00 0.112190E+09 0.128612E+09 0.00 0.00 0.00 0.00 649055.41 4001828.29
September 0.00 0.101202E+09 0.120609E+09 0.00 0.00 0.00 0.00 63121.30 9386882.07
October 0.00 0.104358E+09 0.124471E+09 0.00 0.00 0.00 0.00 139.13 16723079.34
November 0.00 0.102508E+09 0.121225E+09 0.00 0.00 0.00 0.00 0.00 31084115.97
December 0.00 0.101748E+09 0.123128E+09 0.00 0.00 0.00 0.00 0.00 46986017.42
                   
Annual Sum or Average   0.125240E+10 0.147820E+10         4116296.54 0.263080E+09
Minimum of Months 0.00 94890737.57 0.112774E+09 0.00 0.00 0.00 0.00 0.00 2087467.74
Maximum of Months 0.00 0.112190E+09 0.128612E+09 0.00 0.00 0.00 0.00 1478473.23 46986017.42



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.136305E+09 0.162574E+09 0.00 0.00 0.00 0.00 0.00 29398470.53
February 0.00 0.123939E+09 0.147296E+09 0.00 0.00 0.00 0.00 0.00 25464598.97
March 0.00 0.146534E+09 0.167984E+09 0.00 0.00 0.00 0.00 0.00 18869409.25
April 0.00 0.132183E+09 0.157530E+09 0.00 0.00 0.00 0.00 127747.03 14217605.01
May 0.00 0.141419E+09 0.165279E+09 0.00 0.00 0.00 0.00 398372.78 4786428.53
June 0.00 0.140707E+09 0.161989E+09 0.00 0.00 0.00 0.00 1080709.26 1891366.44
July 0.00 0.132895E+09 0.160820E+09 0.00 0.00 0.00 0.00 1150209.73 1009507.54
August 0.00 0.146534E+09 0.167984E+09 0.00 0.00 0.00 0.00 592222.30 2038939.66
September 0.00 0.132183E+09 0.157530E+09 0.00 0.00 0.00 0.00 82533.56 5380621.46
October 0.00 0.136305E+09 0.162574E+09 0.00 0.00 0.00 0.00 3424.17 10132301.90
November 0.00 0.133888E+09 0.158334E+09 0.00 0.00 0.00 0.00 0.00 19234039.45
December 0.00 0.132895E+09 0.160820E+09 0.00 0.00 0.00 0.00 0.00 29499253.52
                   
Annual Sum or Average   0.163579E+10 0.193071E+10         3435218.83 0.161923E+09
Minimum of Months 0.00 0.123939E+09 0.147296E+09 0.00 0.00 0.00 0.00 0.00 1009507.54
Maximum of Months 0.00 0.146534E+09 0.167984E+09 0.00 0.00 0.00 0.00 1150209.73 29499253.52



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 12180473.20 6683582.04 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 11075436.60 6055493.62 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 13094587.24 6905967.42 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 11812127.67 6476222.71 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 12637530.22 6794774.73 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 12573889.37 6659540.38 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 11875768.52 6611457.06 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 13094587.24 6905967.42 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 11812127.67 6476222.71 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 12180473.20 6683582.04 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 11964480.01 6509279.99 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 11875768.52 6611457.06 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.146177E+09 79373547.16            
Minimum of Months 0.00 11075436.60 6055493.62 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 13094587.24 6905967.42 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.104404E+09 57287596.84 0.00 0.00 0.00 0.00 0.00 59842054.81
February 0.00 94932313.75 51904005.23 0.00 0.00 0.00 0.00 0.00 51876921.72
March 0.00 0.112239E+09 59193748.89 0.00 0.00 0.00 0.00 0.00 38582538.16
April 0.00 0.101247E+09 55510238.85 0.00 0.00 0.00 0.00 199926.58 29451840.61
May 0.00 0.108322E+09 58240672.87 0.00 0.00 0.00 0.00 684441.12 10438115.93
June 0.00 0.107776E+09 57081526.35 0.00 0.00 0.00 0.00 1824944.42 4445774.39
July 0.00 0.101792E+09 56669385.36 0.00 0.00 0.00 0.00 1930990.43 2621587.44
August 0.00 0.112239E+09 59193748.89 0.00 0.00 0.00 0.00 888375.77 4885321.59
September 0.00 0.101247E+09 55510238.85 0.00 0.00 0.00 0.00 90287.37 11806948.45
October 0.00 0.104404E+09 57287596.84 0.00 0.00 0.00 0.00 5075.76 21251588.92
November 0.00 0.102553E+09 55793585.77 0.00 0.00 0.00 0.00 0.00 39598454.08
December 0.00 0.101792E+09 56669385.36 0.00 0.00 0.00 0.00 0.00 60099645.73
                   
Annual Sum or Average   0.125295E+10 0.680342E+09         5624041.44 0.334901E+09
Minimum of Months 0.00 94932313.75 51904005.23 0.00 0.00 0.00 0.00 0.00 2621587.44
Maximum of Months 0.00 0.112239E+09 59193748.89 0.00 0.00 0.00 0.00 1930990.43 60099645.73



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 38335713.65 45724037.20 0.00 0.00 0.00 0.00 0.00 0.299159E+10
February 0.00 34857821.96 41427129.03 0.00 0.00 0.00 0.00 0.00 0.222233E+10
March 0.00 41212713.06 47245430.53 0.00 0.00 0.00 0.00 0.00 0.211373E+10
April 0.00 37176416.42 44305440.73 0.00 0.00 0.00 0.00 96614.52 0.111281E+10
May 0.00 39774213.36 46484733.87 0.00 0.00 0.00 0.00 0.115225E+09 0.520190E+09
June 0.00 39573915.93 45559562.25 0.00 0.00 0.00 0.00 0.195088E+09 0.226560E+09
July 0.00 37376713.85 45230612.34 0.00 0.00 0.00 0.00 0.207654E+09 0.149268E+09
August 0.00 41212713.06 47245430.53 0.00 0.00 0.00 0.00 0.132474E+09 0.312252E+09
September 0.00 37176416.42 44305440.73 0.00 0.00 0.00 0.00 16774885.22 0.641786E+09
October 0.00 38335713.65 45724037.20 0.00 0.00 0.00 0.00 1186935.61 0.117292E+10
November 0.00 37655916.33 44531593.79 0.00 0.00 0.00 0.00 0.00 0.160586E+10
December 0.00 37376713.85 45230612.34 0.00 0.00 0.00 0.00 0.00 0.260373E+10
                   
Annual Sum or Average   0.460065E+09 0.543014E+09         0.668499E+09 0.156730E+11
Minimum of Months 0.00 34857821.96 41427129.03 0.00 0.00 0.00 0.00 0.00 0.149268E+09
Maximum of Months 0.00 41212713.06 47245430.53 0.00 0.00 0.00 0.00 0.207654E+09 0.299159E+10



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 30253741.06 40643588.63 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 27509061.89 36824114.70 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 32524208.64 41995938.25 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 29338848.00 39382613.98 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 31388974.85 41319763.44 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 31230904.32 40497388.67 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 29496918.53 40204988.75 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 32524208.64 41995938.25 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 29338848.00 39382613.98 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 30253741.06 40643588.63 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 29717259.27 39583638.92 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 29496918.53 40204988.75 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.363074E+09 0.482679E+09            
Minimum of Months 0.00 27509061.89 36824114.70 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 32524208.64 41995938.25 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 95839284.14 0.114310E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 87144554.91 0.103568E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.103032E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 92941041.06 0.110764E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 99435533.40 0.116212E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 98934789.83 0.113899E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 93441784.63 0.113076E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.103032E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 92941041.06 0.110764E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 95839284.14 0.114310E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 94139790.81 0.111329E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 93441784.63 0.113076E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.115016E+10 0.135753E+10            
Minimum of Months 0.00 87144554.91 0.103568E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.103032E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 95839284.14 0.114310E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 87144554.91 0.103568E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.103032E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 92941041.06 0.110764E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 99435533.40 0.116212E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 98934789.83 0.113899E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 93441784.63 0.113076E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.103032E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 92941041.06 0.110764E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 95839284.14 0.114310E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 94139790.81 0.111329E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 93441784.63 0.113076E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.115016E+10 0.135753E+10            
Minimum of Months 0.00 87144554.91 0.103568E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.103032E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 95839284.14 0.114310E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 87144554.91 0.103568E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.103032E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 92941041.06 0.110764E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 99435533.40 0.116212E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 98934789.83 0.113899E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 93441784.63 0.113076E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.103032E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 92941041.06 0.110764E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 95839284.14 0.114310E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 94139790.81 0.111329E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 93441784.63 0.113076E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.115016E+10 0.135753E+10            
Minimum of Months 0.00 87144554.91 0.103568E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.103032E+09 0.118113E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.105423E+09 0.125741E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 95859010.40 0.113924E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.113335E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.102235E+09 0.121840E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.109379E+09 0.127833E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.108828E+09 0.125289E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.102786E+09 0.124384E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.113335E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.102235E+09 0.121840E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.105423E+09 0.125741E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.103554E+09 0.122462E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.102786E+09 0.124384E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.126518E+10 0.149329E+10            
Minimum of Months 0.00 95859010.40 0.113924E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.113335E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.105423E+09 0.125741E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 95859010.40 0.113924E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.113335E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.102235E+09 0.121840E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.109379E+09 0.127833E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.108828E+09 0.125289E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.102786E+09 0.124384E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.113335E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.102235E+09 0.121840E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.105423E+09 0.125741E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.103554E+09 0.122462E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.102786E+09 0.124384E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.126518E+10 0.149329E+10            
Minimum of Months 0.00 95859010.40 0.113924E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.113335E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.105423E+09 0.125741E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 95859010.40 0.113924E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.113335E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.102235E+09 0.121840E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.109379E+09 0.127833E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.108828E+09 0.125289E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.102786E+09 0.124384E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.113335E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.102235E+09 0.121840E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.105423E+09 0.125741E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.103554E+09 0.122462E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.102786E+09 0.124384E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.126518E+10 0.149329E+10            
Minimum of Months 0.00 95859010.40 0.113924E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.113335E+09 0.129925E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 18270709.80 10025293.76 0.00 0.00 0.00 0.00 0.00 77284194.81
February 0.00 16613154.91 9083168.58 0.00 0.00 0.00 0.00 0.00 67189862.11
March 0.00 19641880.87 10358869.18 0.00 0.00 0.00 0.00 0.00 50811363.63
April 0.00 17718191.50 9714257.22 0.00 0.00 0.00 0.00 191905.58 39884645.13
May 0.00 18956295.33 10192081.47 0.00 0.00 0.00 0.00 579718.42 15427065.11
June 0.00 18860834.06 9989231.55 0.00 0.00 0.00 0.00 1845801.36 7268128.93
July 0.00 17813652.78 9917107.14 0.00 0.00 0.00 0.00 2111465.12 4200837.50
August 0.00 19641880.87 10358869.18 0.00 0.00 0.00 0.00 979385.95 7493789.99
September 0.00 17718191.50 9714257.22 0.00 0.00 0.00 0.00 91098.80 16750732.48
October 0.00 18270709.80 10025293.76 0.00 0.00 0.00 0.00 0.00 28712552.13
November 0.00 17946720.01 9763842.76 0.00 0.00 0.00 0.00 0.00 52026878.90
December 0.00 17813652.78 9917107.14 0.00 0.00 0.00 0.00 0.00 77636585.03
                   
Annual Sum or Average   0.219266E+09 0.119059E+09         5799375.23 0.444687E+09
Minimum of Months 0.00 16613154.91 9083168.58 0.00 0.00 0.00 0.00 0.00 4200837.50
Maximum of Months 0.00 19641880.87 10358869.18 0.00 0.00 0.00 0.00 2111465.12 77636585.03



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.236404E+09 0.281965E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.214957E+09 0.255467E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.254145E+09 0.291347E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.229255E+09 0.273217E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.245274E+09 0.286656E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.244039E+09 0.280950E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.230490E+09 0.278922E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.254145E+09 0.291347E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.229255E+09 0.273217E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.236404E+09 0.281965E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.232211E+09 0.274611E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.230490E+09 0.278922E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.283707E+10 0.334858E+10            
Minimum of Months 0.00 0.214957E+09 0.255467E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.254145E+09 0.291347E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.300296E+09 0.358171E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.273053E+09 0.324512E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.322833E+09 0.370089E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.291215E+09 0.347059E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.311565E+09 0.364130E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.309996E+09 0.356883E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.292784E+09 0.354306E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.322833E+09 0.370089E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.291215E+09 0.347059E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.300296E+09 0.358171E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.294971E+09 0.348830E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.292784E+09 0.354306E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.360384E+10 0.425361E+10            
Minimum of Months 0.00 0.273053E+09 0.324512E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.322833E+09 0.370089E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 59562052.71 80016946.16 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 54158465.60 72497368.03 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 64032035.76 82679380.52 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 57760857.00 77534406.01 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 61797044.24 81348163.34 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 61485842.88 79729115.42 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 58072058.36 79153453.93 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 64032035.76 82679380.52 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 57760857.00 77534406.01 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 59562052.71 80016946.16 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 58505854.18 77930173.28 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 58072058.36 79153453.93 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.714801E+09 0.950273E+09            
Minimum of Months 0.00 54158465.60 72497368.03 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 64032035.76 82679380.52 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 16240630.93 8911442.72 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 14767248.81 8073991.50 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 17459449.66 9207956.55 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 15749503.56 8634963.61 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 16850040.30 9059699.64 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 16765185.83 8879387.17 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 15834358.03 8815276.07 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 17459449.66 9207956.55 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 15749503.56 8634963.61 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 16240630.93 8911442.72 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 15952640.01 8679039.99 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 15834358.03 8815276.07 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.194903E+09 0.105831E+09            
Minimum of Months 0.00 14767248.81 8073991.50 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 17459449.66 9207956.55 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 34801352.00 19095812.75 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 31644104.58 17301287.18 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 37413106.41 19731195.01 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 33748936.20 18503361.72 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 36107229.21 19413503.88 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 35925398.20 19027122.77 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 33930767.20 18889742.83 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 37413106.41 19731195.01 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 33748936.20 18503361.72 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 34801352.00 19095812.75 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 34184228.60 18597810.44 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 33930767.20 18889742.83 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.417649E+09 0.226780E+09            
Minimum of Months 0.00 31644104.58 17301287.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 37413106.41 19731195.01 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 41761622.40 22915070.46 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 37972925.50 20761630.83 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 44895727.70 23677532.33 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 40498723.44 22204126.27 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 43328675.05 23296301.39 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 43110477.85 22832642.15 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 40716920.64 22667785.52 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 44895727.70 23677532.33 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 40498723.44 22204126.27 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 41761622.40 22915070.46 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 41021074.32 22317465.20 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 40716920.64 22667785.52 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.501179E+09 0.272137E+09            
Minimum of Months 0.00 37972925.50 20761630.83 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 44895727.70 23677532.33 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 36541419.60 20050587.52 0.00 0.00 0.00 0.00 0.00 43156212.92
February 0.00 33226309.81 18166337.17 0.00 0.00 0.00 0.00 0.00 37474288.96
March 0.00 39283761.73 20717738.37 0.00 0.00 0.00 0.00 0.00 28196944.07
April 0.00 35436383.01 19428514.44 0.00 0.00 0.00 0.00 109917.05 22226671.51
May 0.00 37912590.67 20384162.95 0.00 0.00 0.00 0.00 367094.73 8260910.00
June 0.00 37721668.12 19978463.11 0.00 0.00 0.00 0.00 1126264.87 3641066.19
July 0.00 35627305.56 19834214.28 0.00 0.00 0.00 0.00 1324619.59 1982521.13
August 0.00 39283761.73 20717738.37 0.00 0.00 0.00 0.00 599603.36 3669236.81
September 0.00 35436383.01 19428514.44 0.00 0.00 0.00 0.00 62655.96 8725617.99
October 0.00 36541419.60 20050587.52 0.00 0.00 0.00 0.00 460.77 15461327.05
November 0.00 35893440.03 19527685.51 0.00 0.00 0.00 0.00 0.00 28537151.77
December 0.00 35627305.56 19834214.28 0.00 0.00 0.00 0.00 0.00 43247170.50
                   
Annual Sum or Average   0.438532E+09 0.238119E+09         3590616.33 0.244579E+09
Minimum of Months 0.00 33226309.81 18166337.17 0.00 0.00 0.00 0.00 0.00 1982521.13
Maximum of Months 0.00 39283761.73 20717738.37 0.00 0.00 0.00 0.00 1324619.59 43247170.50



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 0.444055E+09 0.529636E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.403770E+09 0.479864E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.477381E+09 0.547259E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.430627E+09 0.513204E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.460718E+09 0.538448E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.458398E+09 0.527731E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.432947E+09 0.523921E+09 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.477381E+09 0.547259E+09 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.430627E+09 0.513204E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.444055E+09 0.529636E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.436181E+09 0.515824E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.432947E+09 0.523921E+09 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average   0.532909E+10 0.628991E+10            
Minimum of Months 0.00 0.403770E+09 0.479864E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.477381E+09 0.547259E+09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 25526594.02 34293067.55 0.00 0.00 0.00 0.00 0.00 28701923.63
February 0.00 23210770.97 31070382.70 0.00 0.00 0.00 0.00 0.00 24845795.40
March 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 0.00 18498198.43
April 0.00 24754653.00 33229118.96 0.00 0.00 0.00 0.00 122325.03 14072528.95
May 0.00 26484447.53 34863590.71 0.00 0.00 0.00 0.00 391092.90 4842614.64
June 0.00 26351075.52 34169711.20 0.00 0.00 0.00 0.00 1144967.35 1904502.34
July 0.00 24888025.01 33922998.48 0.00 0.00 0.00 0.00 1285542.85 946635.96
August 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 698067.84 1916004.53
September 0.00 24754653.00 33229118.96 0.00 0.00 0.00 0.00 105256.15 5270036.86
October 0.00 25526594.02 34293067.55 0.00 0.00 0.00 0.00 5482.12 9967689.64
November 0.00 25073937.51 33398733.96 0.00 0.00 0.00 0.00 0.00 18799901.23
December 0.00 24888025.01 33922998.48 0.00 0.00 0.00 0.00 0.00 28740317.84
                   
Annual Sum or Average   0.306343E+09 0.407261E+09         3752734.24 0.158506E+09
Minimum of Months 0.00 23210770.97 31070382.70 0.00 0.00 0.00 0.00 0.00 946635.96
Maximum of Months 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 1285542.85 28740317.84



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.197003E+09 0.234971E+09 0.00 0.00 0.00 0.00 0.00 228519.25
February 0.00 0.179130E+09 0.212889E+09 0.00 0.00 0.00 0.00 0.00 198706.92
March 0.00 0.211788E+09 0.242789E+09 0.00 0.00 0.00 0.00 0.00 149776.73
April 0.00 0.191045E+09 0.227681E+09 0.00 0.00 0.00 0.00 554.63 118567.63
May 0.00 0.204395E+09 0.238880E+09 0.00 0.00 0.00 0.00 1792.54 45254.64
June 0.00 0.203366E+09 0.234125E+09 0.00 0.00 0.00 0.00 5625.73 20724.80
July 0.00 0.192075E+09 0.232435E+09 0.00 0.00 0.00 0.00 6351.28 11940.86
August 0.00 0.211788E+09 0.242789E+09 0.00 0.00 0.00 0.00 2943.69 21421.69
September 0.00 0.191045E+09 0.227681E+09 0.00 0.00 0.00 0.00 251.31 49210.29
October 0.00 0.197003E+09 0.234971E+09 0.00 0.00 0.00 0.00 0.00 84640.15
November 0.00 0.193510E+09 0.228843E+09 0.00 0.00 0.00 0.00 0.00 153376.96
December 0.00 0.192075E+09 0.232435E+09 0.00 0.00 0.00 0.00 0.00 229390.16
                   
Annual Sum or Average   0.236422E+10 0.279049E+10         17519.19 1311530.08
Minimum of Months 0.00 0.179130E+09 0.212889E+09 0.00 0.00 0.00 0.00 0.00 11940.86
Maximum of Months 0.00 0.211788E+09 0.242789E+09 0.00 0.00 0.00 0.00 6351.28 229390.16



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 18270709.80 10025293.76 0.00 0.00 0.00 0.00 0.00 17259686.66
February 0.00 16613154.91 9083168.58 0.00 0.00 0.00 0.00 0.00 14931911.38
March 0.00 19641880.87 10358869.18 0.00 0.00 0.00 0.00 0.00 11085027.43
April 0.00 17718191.50 9714257.22 0.00 0.00 0.00 0.00 64698.09 8444398.16
May 0.00 18956295.33 10192081.47 0.00 0.00 0.00 0.00 205994.83 2960992.57
June 0.00 18860834.06 9989231.55 0.00 0.00 0.00 0.00 597624.85 1202246.45
July 0.00 17813652.78 9917107.14 0.00 0.00 0.00 0.00 674598.62 619576.22
August 0.00 19641880.87 10358869.18 0.00 0.00 0.00 0.00 360768.77 1200366.36
September 0.00 17718191.50 9714257.22 0.00 0.00 0.00 0.00 53809.69 3174426.60
October 0.00 18270709.80 10025293.76 0.00 0.00 0.00 0.00 2421.58 5938989.83
November 0.00 17946720.01 9763842.76 0.00 0.00 0.00 0.00 0.00 11238219.22
December 0.00 17813652.78 9917107.14 0.00 0.00 0.00 0.00 0.00 17275116.53
                   
Annual Sum or Average   0.219266E+09 0.119059E+09         1959916.44 95330957.40
Minimum of Months 0.00 16613154.91 9083168.58 0.00 0.00 0.00 0.00 0.00 619576.22
Maximum of Months 0.00 19641880.87 10358869.18 0.00 0.00 0.00 0.00 674598.62 17275116.53



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 90761223.17 0.121931E+09 0.00 0.00 0.00 0.00 0.00 3728232.70
February 0.00 82527185.67 0.110472E+09 0.00 0.00 0.00 0.00 0.00 3225467.56
March 0.00 97572625.93 0.125988E+09 0.00 0.00 0.00 0.00 0.00 2398398.19
April 0.00 88016544.01 0.118148E+09 0.00 0.00 0.00 0.00 15031.45 1828628.08
May 0.00 94166924.55 0.123959E+09 0.00 0.00 0.00 0.00 49364.58 626053.82
June 0.00 93692712.97 0.121492E+09 0.00 0.00 0.00 0.00 146675.52 241891.28
July 0.00 88490755.59 0.120615E+09 0.00 0.00 0.00 0.00 167598.13 114937.48
August 0.00 97572625.93 0.125988E+09 0.00 0.00 0.00 0.00 90581.48 233379.08
September 0.00 88016544.01 0.118148E+09 0.00 0.00 0.00 0.00 13171.82 669198.45
October 0.00 90761223.17 0.121931E+09 0.00 0.00 0.00 0.00 676.31 1283805.67
November 0.00 89151777.80 0.118751E+09 0.00 0.00 0.00 0.00 0.00 2432928.91
December 0.00 88490755.59 0.120615E+09 0.00 0.00 0.00 0.00 0.00 3731073.65
                   
Annual Sum or Average   0.108922E+10 0.144804E+10         483099.29 20513994.87
Minimum of Months 0.00 82527185.67 0.110472E+09 0.00 0.00 0.00 0.00 0.00 114937.48
Maximum of Months 0.00 97572625.93 0.125988E+09 0.00 0.00 0.00 0.00 167598.13 3731073.65



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.557071E+09 0.277553E+10 0.00 0.00 0.00 0.00 0.00 10076157.48
February 0.00 0.506533E+09 0.251470E+10 0.00 0.00 0.00 0.00 0.00 8929590.45
March 0.00 0.598878E+09 0.286788E+10 0.00 0.00 0.00 0.00 0.00 6717415.34
April 0.00 0.540225E+09 0.268942E+10 0.00 0.00 0.00 0.00 0.00 5730065.37
May 0.00 0.577975E+09 0.282171E+10 0.00 0.00 0.00 0.00 60489.55 2484248.99
June 0.00 0.575064E+09 0.276555E+10 0.00 0.00 0.00 0.00 160241.12 1323613.52
July 0.00 0.543136E+09 0.274558E+10 0.00 0.00 0.00 0.00 180774.55 884962.08
August 0.00 0.598878E+09 0.286788E+10 0.00 0.00 0.00 0.00 87155.13 1360283.95
September 0.00 0.540225E+09 0.268942E+10 0.00 0.00 0.00 0.00 9050.57 2631778.16
October 0.00 0.557071E+09 0.277553E+10 0.00 0.00 0.00 0.00 0.00 4154964.87
November 0.00 0.547193E+09 0.270315E+10 0.00 0.00 0.00 0.00 0.00 7136398.75
December 0.00 0.543136E+09 0.274558E+10 0.00 0.00 0.00 0.00 0.00 10217140.22
                   
Annual Sum or Average   0.668538E+10 0.329619E+11         497710.92 61646619.18
Minimum of Months 0.00 0.506533E+09 0.251470E+10 0.00 0.00 0.00 0.00 0.00 884962.08
Maximum of Months 0.00 0.598878E+09 0.286788E+10 0.00 0.00 0.00 0.00 180774.55 10217140.22



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.159732E+09 0.190517E+09 0.00 0.00 0.00 0.00 0.00 0.173274E+09
February 0.00 0.145241E+09 0.172613E+09 0.00 0.00 0.00 0.00 0.00 0.151806E+09
March 0.00 0.171720E+09 0.196856E+09 0.00 0.00 0.00 0.00 0.00 0.115523E+09
April 0.00 0.154902E+09 0.184606E+09 0.00 0.00 0.00 0.00 251900.39 92942559.10
May 0.00 0.165726E+09 0.193686E+09 0.00 0.00 0.00 0.00 1278307.46 36419717.29
June 0.00 0.164891E+09 0.189831E+09 0.00 0.00 0.00 0.00 3871699.99 17059639.48
July 0.00 0.155736E+09 0.188461E+09 0.00 0.00 0.00 0.00 4406888.59 9895708.63
August 0.00 0.171720E+09 0.196856E+09 0.00 0.00 0.00 0.00 1966853.05 17349159.90
September 0.00 0.154902E+09 0.184606E+09 0.00 0.00 0.00 0.00 178876.14 38889027.42
October 0.00 0.159732E+09 0.190517E+09 0.00 0.00 0.00 0.00 0.00 66314341.24
November 0.00 0.156900E+09 0.185548E+09 0.00 0.00 0.00 0.00 0.00 0.118248E+09
December 0.00 0.155736E+09 0.188461E+09 0.00 0.00 0.00 0.00 0.00 0.174091E+09
                   
Annual Sum or Average   0.191694E+10 0.226256E+10         11954525.61 0.101181E+10
Minimum of Months 0.00 0.145241E+09 0.172613E+09 0.00 0.00 0.00 0.00 0.00 9895708.63
Maximum of Months 0.00 0.171720E+09 0.196856E+09 0.00 0.00 0.00 0.00 4406888.59 0.174091E+09



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.444055E+09 0.529636E+09 0.00 0.00 0.00 0.00 0.00 228051.87
February 0.00 0.403770E+09 0.479864E+09 0.00 0.00 0.00 0.00 0.00 199745.76
March 0.00 0.477381E+09 0.547259E+09 0.00 0.00 0.00 0.00 0.00 151593.43
April 0.00 0.430627E+09 0.513204E+09 0.00 0.00 0.00 0.00 412.64 121124.31
May 0.00 0.460718E+09 0.538448E+09 0.00 0.00 0.00 0.00 1711.31 46426.32
June 0.00 0.458398E+09 0.527731E+09 0.00 0.00 0.00 0.00 5455.07 21270.21
July 0.00 0.432947E+09 0.523921E+09 0.00 0.00 0.00 0.00 6190.11 12070.88
August 0.00 0.477381E+09 0.547259E+09 0.00 0.00 0.00 0.00 2806.30 21624.43
September 0.00 0.430627E+09 0.513204E+09 0.00 0.00 0.00 0.00 236.61 49911.45
October 0.00 0.444055E+09 0.529636E+09 0.00 0.00 0.00 0.00 0.00 85905.27
November 0.00 0.436181E+09 0.515824E+09 0.00 0.00 0.00 0.00 0.00 154823.91
December 0.00 0.432947E+09 0.523921E+09 0.00 0.00 0.00 0.00 0.00 229100.37
                   
Annual Sum or Average   0.532909E+10 0.628991E+10         16812.04 1321648.23
Minimum of Months 0.00 0.403770E+09 0.479864E+09 0.00 0.00 0.00 0.00 0.00 12070.88
Maximum of Months 0.00 0.477381E+09 0.547259E+09 0.00 0.00 0.00 0.00 6190.11 229100.37



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 25526594.02 34293067.55 0.00 0.00 0.00 0.00 0.00 3173566.87
February 0.00 23210770.97 31070382.70 0.00 0.00 0.00 0.00 0.00 2744497.18
March 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 0.00 2036246.67
April 0.00 24754653.00 33229118.96 0.00 0.00 0.00 0.00 13529.43 1544001.21
May 0.00 26484447.53 34863590.71 0.00 0.00 0.00 0.00 42696.01 527106.87
June 0.00 26351075.52 34169711.20 0.00 0.00 0.00 0.00 125688.88 204977.77
July 0.00 24888025.01 33922998.48 0.00 0.00 0.00 0.00 140589.67 101511.48
August 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 76593.13 205700.77
September 0.00 24754653.00 33229118.96 0.00 0.00 0.00 0.00 11678.95 570836.94
October 0.00 25526594.02 34293067.55 0.00 0.00 0.00 0.00 662.09 1087328.07
November 0.00 25073937.51 33398733.96 0.00 0.00 0.00 0.00 0.00 2064457.31
December 0.00 24888025.01 33922998.48 0.00 0.00 0.00 0.00 0.00 3175362.19
                   
Annual Sum or Average   0.306343E+09 0.407261E+09         411438.17 17435593.34
Minimum of Months 0.00 23210770.97 31070382.70 0.00 0.00 0.00 0.00 0.00 101511.48
Maximum of Months 0.00 27442301.04 35434113.87 0.00 0.00 0.00 0.00 140589.67 3175362.19



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 39708035.14 53344630.77 0.00 0.00 0.00 0.00 0.00 47964208.48
February 0.00 36105643.73 48331578.69 0.00 0.00 0.00 0.00 0.00 41611706.71
March 0.00 42688023.84 55119587.01 0.00 0.00 0.00 0.00 0.00 31178411.51
April 0.00 38507238.00 51689604.01 0.00 0.00 0.00 0.00 177705.05 23957291.11
May 0.00 41198029.49 54232108.89 0.00 0.00 0.00 0.00 618015.26 8298085.47
June 0.00 40990561.92 53152743.61 0.00 0.00 0.00 0.00 1863643.39 3260355.96
July 0.00 38714705.57 52768969.29 0.00 0.00 0.00 0.00 2129179.40 1572081.39
August 0.00 42688023.84 55119587.01 0.00 0.00 0.00 0.00 1128979.35 3192941.96
September 0.00 38507238.00 51689604.01 0.00 0.00 0.00 0.00 156028.59 8916030.61
October 0.00 39708035.14 53344630.77 0.00 0.00 0.00 0.00 5052.96 16912600.08
November 0.00 39003902.79 51953448.85 0.00 0.00 0.00 0.00 0.00 31682882.11
December 0.00 38714705.57 52768969.29 0.00 0.00 0.00 0.00 0.00 48082149.17
                   
Annual Sum or Average   0.476534E+09 0.633515E+09         6078604.01 0.266629E+09
Minimum of Months 0.00 36105643.73 48331578.69 0.00 0.00 0.00 0.00 0.00 1572081.39
Maximum of Months 0.00 42688023.84 55119587.01 0.00 0.00 0.00 0.00 2129179.40 48082149.17



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 31321216.80 17186263.19 0.00 0.00 0.00 0.00 0.00 61394285.89
February 0.00 28479694.13 15571187.20 0.00 0.00 0.00 0.00 0.00 53197888.03
March 0.00 33671795.77 17758108.28 0.00 0.00 0.00 0.00 0.00 39765674.10
April 0.00 30374042.58 16653056.29 0.00 0.00 0.00 0.00 242890.01 30386024.54
May 0.00 32496506.29 17472185.74 0.00 0.00 0.00 0.00 821407.15 10403598.41
June 0.00 32332858.38 17124442.10 0.00 0.00 0.00 0.00 2462655.84 4019056.12
July 0.00 30537690.48 17000799.92 0.00 0.00 0.00 0.00 2820460.43 1909917.67
August 0.00 33671795.77 17758108.28 0.00 0.00 0.00 0.00 1508566.75 3928096.47
September 0.00 30374042.58 16653056.29 0.00 0.00 0.00 0.00 217008.26 11194120.71
October 0.00 31321216.80 17186263.19 0.00 0.00 0.00 0.00 8049.21 21409561.53
November 0.00 30765805.74 16738060.29 0.00 0.00 0.00 0.00 0.00 40328352.31
December 0.00 30537690.48 17000799.92 0.00 0.00 0.00 0.00 0.00 61498055.59
                   
Annual Sum or Average   0.375884E+09 0.204102E+09         8081037.65 0.339435E+09
Minimum of Months 0.00 28479694.13 15571187.20 0.00 0.00 0.00 0.00 0.00 1909917.67
Maximum of Months 0.00 33671795.77 17758108.28 0.00 0.00 0.00 0.00 2820460.43 61498055.59



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 24360946.40 13367164.08 0.00 0.00 0.00 0.00 0.00 48079084.68
February 0.00 22150873.21 12110987.24 0.00 0.00 0.00 0.00 0.00 41804360.51
March 0.00 26189174.49 13811934.83 0.00 0.00 0.00 0.00 0.00 31565104.28
April 0.00 23624255.34 12952445.41 0.00 0.00 0.00 0.00 121387.04 24844172.39
May 0.00 25275060.45 13589549.46 0.00 0.00 0.00 0.00 396164.04 9285717.84
June 0.00 25147778.74 13319080.76 0.00 0.00 0.00 0.00 1275290.89 4092201.03
July 0.00 23751537.04 13222914.11 0.00 0.00 0.00 0.00 1475597.56 2201916.36
August 0.00 26189174.49 13811934.83 0.00 0.00 0.00 0.00 690681.25 4083237.17
September 0.00 23624255.34 12952445.41 0.00 0.00 0.00 0.00 63628.14 9927063.09
October 0.00 24360946.40 13367164.08 0.00 0.00 0.00 0.00 44.14 17593633.72
November 0.00 23928960.02 13018559.98 0.00 0.00 0.00 0.00 0.00 32161866.52
December 0.00 23751537.04 13222914.11 0.00 0.00 0.00 0.00 0.00 48264005.10
                   
Annual Sum or Average   0.292354E+09 0.158747E+09         4022793.06 0.273902E+09
Minimum of Months 0.00 22150873.21 12110987.24 0.00 0.00 0.00 0.00 0.00 2201916.36
Maximum of Months 0.00 26189174.49 13811934.83 0.00 0.00 0.00 0.00 1475597.56 48264005.10



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.657746E+09 0.395666E+10 0.00 0.00 0.00 0.00 0.00 11751768.59
February 0.00 0.598074E+09 0.358484E+10 0.00 0.00 0.00 0.00 0.00 10321771.98
March 0.00 0.707108E+09 0.408832E+10 0.00 0.00 0.00 0.00 0.00 7806525.61
April 0.00 0.637855E+09 0.383391E+10 0.00 0.00 0.00 0.00 16096.94 6187068.43
May 0.00 0.682427E+09 0.402249E+10 0.00 0.00 0.00 0.00 87381.88 2338282.62
June 0.00 0.678990E+09 0.394243E+10 0.00 0.00 0.00 0.00 288841.94 1026324.28
July 0.00 0.641292E+09 0.391397E+10 0.00 0.00 0.00 0.00 327565.12 567962.48
August 0.00 0.707108E+09 0.408832E+10 0.00 0.00 0.00 0.00 143797.76 1051589.52
September 0.00 0.637855E+09 0.383391E+10 0.00 0.00 0.00 0.00 12216.54 2517267.83
October 0.00 0.657746E+09 0.395666E+10 0.00 0.00 0.00 0.00 0.00 4361584.97
November 0.00 0.646082E+09 0.385348E+10 0.00 0.00 0.00 0.00 0.00 7898234.62
December 0.00 0.641292E+09 0.391397E+10 0.00 0.00 0.00 0.00 0.00 11774836.94
                   
Annual Sum or Average   0.789357E+10 0.469889E+11         875900.18 67603217.87
Minimum of Months 0.00 0.598074E+09 0.358484E+10 0.00 0.00 0.00 0.00 0.00 567962.48
Maximum of Months 0.00 0.707108E+09 0.408832E+10 0.00 0.00 0.00 0.00 327565.12 11774836.94



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.334093E+09 0.200973E+10 0.00 0.00 0.00 0.00 0.00 13759960.43
February 0.00 0.303783E+09 0.182087E+10 0.00 0.00 0.00 0.00 0.00 12051631.73
March 0.00 0.359166E+09 0.207660E+10 0.00 0.00 0.00 0.00 0.00 9107924.01
April 0.00 0.323990E+09 0.194738E+10 0.00 0.00 0.00 0.00 16183.80 7218924.47
May 0.00 0.346629E+09 0.204317E+10 0.00 0.00 0.00 0.00 102052.47 2764478.12
June 0.00 0.344884E+09 0.200250E+10 0.00 0.00 0.00 0.00 327367.62 1234792.90
July 0.00 0.325735E+09 0.198805E+10 0.00 0.00 0.00 0.00 368225.60 708063.84
August 0.00 0.359166E+09 0.207660E+10 0.00 0.00 0.00 0.00 162495.33 1287333.21
September 0.00 0.323990E+09 0.194738E+10 0.00 0.00 0.00 0.00 14318.57 2990156.86
October 0.00 0.334093E+09 0.200973E+10 0.00 0.00 0.00 0.00 0.00 5098542.39
November 0.00 0.328169E+09 0.195732E+10 0.00 0.00 0.00 0.00 0.00 9208521.01
December 0.00 0.325735E+09 0.198805E+10 0.00 0.00 0.00 0.00 0.00 13778402.33
                   
Annual Sum or Average   0.400943E+10 0.238674E+11         990643.39 79208731.27
Minimum of Months 0.00 0.303783E+09 0.182087E+10 0.00 0.00 0.00 0.00 0.00 708063.84
Maximum of Months 0.00 0.359166E+09 0.207660E+10 0.00 0.00 0.00 0.00 368225.60 13778402.33



Table of Contents

Report: SpaceGainsMonthly

For: FLOOR 3 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 62642433.61 34372526.38 0.00 0.00 0.00 0.00 0.00 0.123267E+09
February 0.00 56959388.25 31142374.40 0.00 0.00 0.00 0.00 0.00 0.107056E+09
March 0.00 67343591.54 35516216.56 0.00 0.00 0.00 0.00 0.00 80452080.50
April 0.00 60748085.15 33306112.57 0.00 0.00 0.00 0.00 357197.71 62396014.56
May 0.00 64993012.57 34944371.47 0.00 0.00 0.00 0.00 1331162.47 22395419.05
June 0.00 64665716.77 34248884.20 0.00 0.00 0.00 0.00 4023947.13 9238047.12
July 0.00 61075380.96 34001599.84 0.00 0.00 0.00 0.00 4617502.94 4719461.01
August 0.00 67343591.54 35516216.56 0.00 0.00 0.00 0.00 2324729.52 9143828.38
September 0.00 60748085.15 33306112.57 0.00 0.00 0.00 0.00 270220.98 23931699.67
October 0.00 62642433.61 34372526.38 0.00 0.00 0.00 0.00 8997.06 44119096.09
November 0.00 61531611.48 33476120.57 0.00 0.00 0.00 0.00 0.00 81769053.66
December 0.00 61075380.96 34001599.84 0.00 0.00 0.00 0.00 0.00 0.123653E+09
                   
Annual Sum or Average   0.751769E+09 0.408205E+09         12933757.82 0.692141E+09
Minimum of Months 0.00 56959388.25 31142374.40 0.00 0.00 0.00 0.00 0.00 4719461.01
Maximum of Months 0.00 67343591.54 35516216.56 0.00 0.00 0.00 0.00 4617502.94 0.123653E+09



Table of Contents

Report: SpaceGainsMonthly

For: NE STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 89449998.53 0.106689E+09 0.00 0.00 0.00 0.00 0.00 0.183810E+09
February 0.00 81334917.91 96663157.38 0.00 0.00 0.00 0.00 0.00 0.158992E+09
March 0.00 96162997.15 0.110239E+09 0.00 0.00 0.00 0.00 0.00 0.117690E+09
April 0.00 86744971.66 0.103379E+09 0.00 0.00 0.00 0.00 481747.34 89411662.42
May 0.00 92806497.84 0.108464E+09 0.00 0.00 0.00 0.00 1481548.21 32356112.76
June 0.00 92339137.17 0.106305E+09 0.00 0.00 0.00 0.00 4339259.47 14488150.02
July 0.00 87212332.32 0.105538E+09 0.00 0.00 0.00 0.00 4733806.47 8762900.95
August 0.00 96162997.15 0.110239E+09 0.00 0.00 0.00 0.00 2144725.56 15802739.14
September 0.00 86744971.66 0.103379E+09 0.00 0.00 0.00 0.00 197046.69 36729656.78
October 0.00 89449998.53 0.106689E+09 0.00 0.00 0.00 0.00 0.00 63865131.55
November 0.00 87863804.76 0.103907E+09 0.00 0.00 0.00 0.00 0.00 0.119577E+09
December 0.00 87212332.32 0.105538E+09 0.00 0.00 0.00 0.00 0.00 0.184119E+09
                   
Annual Sum or Average   0.107348E+10 0.126703E+10         13378133.73 0.102561E+10
Minimum of Months 0.00 81334917.91 96663157.38 0.00 0.00 0.00 0.00 0.00 8762900.95
Maximum of Months 0.00 96162997.15 0.110239E+09 0.00 0.00 0.00 0.00 4733806.47 0.184119E+09



Table of Contents

Report: SpaceGainsMonthly

For: NW ELEVATOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 74541665.44 88907770.82 0.00 0.00 0.00 0.00 0.00 0.135177E+09
February 0.00 67779098.26 80552679.05 0.00 0.00 0.00 0.00 0.00 0.117050E+09
March 0.00 80135830.96 91866032.98 0.00 0.00 0.00 0.00 0.00 87055054.12
April 0.00 72287476.38 86149391.24 0.00 0.00 0.00 0.00 333612.35 66654568.34
May 0.00 77338748.20 90386901.90 0.00 0.00 0.00 0.00 1132454.34 24511629.62
June 0.00 76949280.98 88587958.69 0.00 0.00 0.00 0.00 3431135.04 10815773.86
July 0.00 72676943.60 87948334.44 0.00 0.00 0.00 0.00 3659540.42 6735110.38
August 0.00 80135830.96 91866032.98 0.00 0.00 0.00 0.00 1645408.48 12296160.92
September 0.00 72287476.38 86149391.24 0.00 0.00 0.00 0.00 147601.29 28007753.81
October 0.00 74541665.44 88907770.82 0.00 0.00 0.00 0.00 0.00 48385438.32
November 0.00 73219837.30 86589132.91 0.00 0.00 0.00 0.00 0.00 88696631.50
December 0.00 72676943.60 87948334.44 0.00 0.00 0.00 0.00 0.00 0.135364E+09
                   
Annual Sum or Average   0.894571E+09 0.105586E+10         10349751.92 0.760749E+09
Minimum of Months 0.00 67779098.26 80552679.05 0.00 0.00 0.00 0.00 0.00 6735110.38
Maximum of Months 0.00 80135830.96 91866032.98 0.00 0.00 0.00 0.00 3659540.42 0.135364E+09



Table of Contents

Report: SpaceGainsMonthly

For: NW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.102229E+09 0.121931E+09 0.00 0.00 0.00 0.00 0.00 0.209831E+09
February 0.00 92954191.90 0.110472E+09 0.00 0.00 0.00 0.00 0.00 0.181604E+09
March 0.00 0.109901E+09 0.125988E+09 0.00 0.00 0.00 0.00 0.00 0.134469E+09
April 0.00 99137110.46 0.118148E+09 0.00 0.00 0.00 0.00 559828.34 0.102168E+09
May 0.00 0.106065E+09 0.123959E+09 0.00 0.00 0.00 0.00 1662268.96 37503551.37
June 0.00 0.105530E+09 0.121492E+09 0.00 0.00 0.00 0.00 4861939.09 17236335.73
July 0.00 99671236.94 0.120615E+09 0.00 0.00 0.00 0.00 5268797.31 10814517.13
August 0.00 0.109901E+09 0.125988E+09 0.00 0.00 0.00 0.00 2458702.89 19018799.55
September 0.00 99137110.46 0.118148E+09 0.00 0.00 0.00 0.00 225295.45 42668124.94
October 0.00 0.102229E+09 0.121931E+09 0.00 0.00 0.00 0.00 302.80 73325303.53
November 0.00 0.100416E+09 0.118751E+09 0.00 0.00 0.00 0.00 0.00 0.136867E+09
December 0.00 99671236.94 0.120615E+09 0.00 0.00 0.00 0.00 0.00 0.210337E+09
                   
Annual Sum or Average   0.122684E+10 0.144804E+10         15037134.85 0.117584E+10
Minimum of Months 0.00 92954191.90 0.110472E+09 0.00 0.00 0.00 0.00 0.00 10814517.13
Maximum of Months 0.00 0.109901E+09 0.125988E+09 0.00 0.00 0.00 0.00 5268797.31 0.210337E+09



Table of Contents

Report: SpaceGainsMonthly

For: SW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 51114284.87 60965382.94 0.00 0.00 0.00 0.00 0.00 0.105295E+09
February 0.00 46477095.95 55236172.04 0.00 0.00 0.00 0.00 0.00 91525086.40
March 0.00 54950284.09 62993907.37 0.00 0.00 0.00 0.00 0.00 68307367.63
April 0.00 49568555.23 59073920.97 0.00 0.00 0.00 0.00 134420.15 52937622.59
May 0.00 53032284.48 61979645.16 0.00 0.00 0.00 0.00 775567.24 19990258.34
June 0.00 52765221.24 60746083.00 0.00 0.00 0.00 0.00 2422925.39 9097728.15
July 0.00 49835618.47 60307483.12 0.00 0.00 0.00 0.00 2611927.13 5771413.09
August 0.00 54950284.09 62993907.37 0.00 0.00 0.00 0.00 1153444.28 10532989.24
September 0.00 49568555.23 59073920.97 0.00 0.00 0.00 0.00 110238.01 23110579.95
October 0.00 51114284.87 60965382.94 0.00 0.00 0.00 0.00 0.00 38560561.96
November 0.00 50207888.43 59375458.38 0.00 0.00 0.00 0.00 0.00 69624540.73
December 0.00 49835618.47 60307483.12 0.00 0.00 0.00 0.00 0.00 0.105404E+09
                   
Annual Sum or Average   0.613420E+09 0.724019E+09         7208522.20 0.600158E+09
Minimum of Months 0.00 46477095.95 55236172.04 0.00 0.00 0.00 0.00 0.00 5771413.09
Maximum of Months 0.00 54950284.09 62993907.37 0.00 0.00 0.00 0.00 2611927.13 0.105404E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 233.30 02-JAN-07:10 136.08 02-JAN-07:10 213.96 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 38.99 04-JAN-11:57
February 233.30 01-FEB-07:10 136.08 01-FEB-07:10 213.96 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 39.01 12-FEB-23:00
March 233.30 01-MAR-07:10 136.08 01-MAR-07:10 213.96 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 21.31 14-MAR-15:10
April 233.30 03-APR-06:10 136.08 03-APR-06:10 213.96 03-APR-05:10 0.00 0.00 0.00 0.00 6.80 23-APR-16:00 19.50 26-APR-15:00
May 233.30 01-MAY-06:10 136.08 01-MAY-06:10 213.96 01-MAY-05:10 0.00 0.00 0.00 0.00 3.13 24-MAY-18:00 7.48 20-MAY-06:10
June 233.30 01-JUN-06:10 136.08 01-JUN-06:10 213.96 01-JUN-05:10 0.00 0.00 0.00 0.00 6.60 29-JUN-16:00 7.94 09-JUN-09:00
July 233.30 03-JUL-06:10 136.08 03-JUL-06:10 213.96 03-JUL-05:10 0.00 0.00 0.00 0.00 7.66 15-JUL-16:00 3.94 08-JUL-14:00
August 233.30 01-AUG-06:10 136.08 01-AUG-06:10 213.96 01-AUG-05:10 0.00 0.00 0.00 0.00 4.96 08-AUG-16:00 9.91 17-AUG-14:00
September 233.30 01-SEP-06:10 136.08 01-SEP-06:10 213.96 01-SEP-05:10 0.00 0.00 0.00 0.00 1.83 07-SEP-15:00 8.54 20-SEP-06:07
October 233.30 02-OCT-06:10 136.08 02-OCT-06:10 213.96 02-OCT-05:10 0.00 0.00 0.00 0.00 0.01 22-OCT-15:00 14.70 31-OCT-11:00
November 233.30 01-NOV-06:10 136.08 01-NOV-06:10 213.96 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 20.44 22-NOV-02:00
December 233.30 01-DEC-07:10 136.08 01-DEC-07:10 213.96 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 35.47 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 233.30   136.08   213.96   0.00 0.00 0.00 0.00 0.00   3.94  
Maximum of Months 233.30   136.08   213.96   0.00 0.00 0.00 0.00 7.66   39.01  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 CAFE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 4536.44 02-JAN-07:10 151.20 02-JAN-07:10 415.84 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 88.77 04-JAN-12:00
February 4536.44 01-FEB-07:10 151.20 01-FEB-07:10 415.84 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 89.53 12-FEB-23:00
March 4536.44 01-MAR-07:10 151.20 01-MAR-07:10 415.84 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 49.02 14-MAR-15:50
April 4536.44 03-APR-06:10 151.20 03-APR-06:10 415.84 03-APR-05:10 0.00 0.00 0.00 0.00 8.71 23-APR-16:10 48.93 04-APR-18:00
May 4536.44 01-MAY-06:10 151.20 01-MAY-06:10 415.84 01-MAY-05:10 0.00 0.00 0.00 0.00 5.15 24-MAY-15:00 18.12 09-MAY-05:09
June 4536.44 01-JUN-06:10 151.20 01-JUN-06:10 415.84 01-JUN-05:10 0.00 0.00 0.00 0.00 13.51 29-JUN-16:00 19.57 09-JUN-09:00
July 4536.44 03-JUL-06:10 151.20 03-JUL-06:10 415.84 03-JUL-05:10 0.00 0.00 0.00 0.00 10.99 15-JUL-14:01 10.18 08-JUL-14:10
August 4536.44 01-AUG-06:10 151.20 01-AUG-06:10 415.84 01-AUG-05:10 0.00 0.00 0.00 0.00 9.76 08-AUG-16:00 24.31 17-AUG-14:00
September 4536.44 01-SEP-06:10 151.20 01-SEP-06:10 415.84 01-SEP-05:10 0.00 0.00 0.00 0.00 2.83 07-SEP-15:00 22.04 20-SEP-06:00
October 4536.44 02-OCT-06:10 151.20 02-OCT-06:10 415.84 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 34.55 31-OCT-10:55
November 4536.44 01-NOV-06:10 151.20 01-NOV-06:10 415.84 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 50.75 22-NOV-02:00
December 4536.44 01-DEC-07:10 151.20 01-DEC-07:10 415.84 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 81.34 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 4536.44   151.20   415.84   0.00 0.00 0.00 0.00 0.00   10.18  
Maximum of Months 4536.44   151.20   415.84   0.00 0.00 0.00 0.00 13.51   89.53  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 CLEAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 272.19 02-JAN-07:10 158.76 02-JAN-07:10 249.62 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 272.19 01-FEB-07:10 158.76 01-FEB-07:10 249.62 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 272.19 01-MAR-07:10 158.76 01-MAR-07:10 249.62 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 272.19 03-APR-06:10 158.76 03-APR-06:10 249.62 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 272.19 01-MAY-06:10 158.76 01-MAY-06:10 249.62 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 272.19 01-JUN-06:10 158.76 01-JUN-06:10 249.62 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 272.19 03-JUL-06:10 158.76 03-JUL-06:10 249.62 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 272.19 01-AUG-06:10 158.76 01-AUG-06:10 249.62 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 272.19 01-SEP-06:10 158.76 01-SEP-06:10 249.62 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 272.19 02-OCT-06:10 158.76 02-OCT-06:10 249.62 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 272.19 01-NOV-06:10 158.76 01-NOV-06:10 249.62 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 272.19 01-DEC-07:10 158.76 01-DEC-07:10 249.62 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 272.19   158.76   249.62   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 272.19   158.76   249.62   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 356.43 02-JAN-07:10 207.90 02-JAN-07:10 326.89 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 356.43 01-FEB-07:10 207.90 01-FEB-07:10 326.89 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 356.43 01-MAR-07:10 207.90 01-MAR-07:10 326.89 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 356.43 03-APR-06:10 207.90 03-APR-06:10 326.89 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 356.43 01-MAY-06:10 207.90 01-MAY-06:10 326.89 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 356.43 01-JUN-06:10 207.90 01-JUN-06:10 326.89 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 356.43 03-JUL-06:10 207.90 03-JUL-06:10 326.89 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 356.43 01-AUG-06:10 207.90 01-AUG-06:10 326.89 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 356.43 01-SEP-06:10 207.90 01-SEP-06:10 326.89 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 356.43 02-OCT-06:10 207.90 02-OCT-06:10 326.89 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 356.43 01-NOV-06:10 207.90 01-NOV-06:10 326.89 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 356.43 01-DEC-07:10 207.90 01-DEC-07:10 326.89 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 356.43   207.90   326.89   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 356.43   207.90   326.89   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 68.05 02-JAN-07:10 72.09 02-JAN-07:10 137.27 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 68.05 01-FEB-07:10 72.09 01-FEB-07:10 137.27 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 68.05 01-MAR-07:10 72.09 01-MAR-07:10 137.27 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 68.05 03-APR-06:10 72.09 03-APR-06:10 137.27 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 68.05 01-MAY-06:10 72.09 01-MAY-06:10 137.27 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 68.05 01-JUN-06:10 72.09 01-JUN-06:10 137.27 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 68.05 03-JUL-06:10 72.09 03-JUL-06:10 137.27 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 68.05 01-AUG-06:10 72.09 01-AUG-06:10 137.27 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 68.05 01-SEP-06:10 72.09 01-SEP-06:10 137.27 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 68.05 02-OCT-06:10 72.09 02-OCT-06:10 137.27 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 68.05 01-NOV-06:10 72.09 01-NOV-06:10 137.27 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 68.05 01-DEC-07:10 72.09 01-DEC-07:10 137.27 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 68.05   72.09   137.27   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 68.05   72.09   137.27   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 24.30 02-JAN-07:10 25.75 02-JAN-07:10 49.03 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 38.52 04-JAN-12:00
February 24.30 01-FEB-07:10 25.75 01-FEB-07:10 49.03 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 38.86 12-FEB-23:00
March 24.30 01-MAR-07:10 25.75 01-MAR-07:10 49.03 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 21.31 14-MAR-15:10
April 24.30 03-APR-06:10 25.75 03-APR-06:10 49.03 03-APR-05:10 0.00 0.00 0.00 0.00 5.77 23-APR-16:00 19.50 26-APR-15:00
May 24.30 01-MAY-06:10 25.75 01-MAY-06:10 49.03 01-MAY-05:10 0.00 0.00 0.00 0.00 2.33 24-MAY-15:00 7.48 20-MAY-06:08
June 24.30 01-JUN-06:10 25.75 01-JUN-06:10 49.03 01-JUN-05:10 0.00 0.00 0.00 0.00 6.07 29-JUN-16:00 7.94 09-JUN-09:00
July 24.30 03-JUL-06:10 25.75 03-JUL-06:10 49.03 03-JUL-05:10 0.00 0.00 0.00 0.00 5.46 15-JUL-15:00 4.22 08-JUL-14:00
August 24.30 01-AUG-06:10 25.75 01-AUG-06:10 49.03 01-AUG-05:10 0.00 0.00 0.00 0.00 4.39 08-AUG-16:00 10.98 17-AUG-14:00
September 24.30 01-SEP-06:10 25.75 01-SEP-06:10 49.03 01-SEP-05:10 0.00 0.00 0.00 0.00 1.27 07-SEP-15:00 8.72 28-SEP-12:00
October 24.30 02-OCT-06:10 25.75 02-OCT-06:10 49.03 02-OCT-05:10 0.00 0.00 0.00 0.00 0.04 19-OCT-15:00 14.70 31-OCT-11:00
November 24.30 01-NOV-06:10 25.75 01-NOV-06:10 49.03 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 20.88 22-NOV-02:00
December 24.30 01-DEC-07:10 25.75 01-DEC-07:10 49.03 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 35.09 18-DEC-15:10
                             
Annual Sum or Average                            
Minimum of Months 24.30   25.75   49.03   0.00 0.00 0.00 0.00 0.00   4.22  
Maximum of Months 24.30   25.75   49.03   0.00 0.00 0.00 0.00 6.07   38.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 29.16 02-JAN-07:10 30.90 02-JAN-07:10 58.83 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 29.16 01-FEB-07:10 30.90 01-FEB-07:10 58.83 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 29.16 01-MAR-07:10 30.90 01-MAR-07:10 58.83 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 29.16 03-APR-06:10 30.90 03-APR-06:10 58.83 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 29.16 01-MAY-06:10 30.90 01-MAY-06:10 58.83 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 29.16 01-JUN-06:10 30.90 01-JUN-06:10 58.83 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 29.16 03-JUL-06:10 30.90 03-JUL-06:10 58.83 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 29.16 01-AUG-06:10 30.90 01-AUG-06:10 58.83 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 29.16 01-SEP-06:10 30.90 01-SEP-06:10 58.83 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 29.16 02-OCT-06:10 30.90 02-OCT-06:10 58.83 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 29.16 01-NOV-06:10 30.90 01-NOV-06:10 58.83 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 29.16 01-DEC-07:10 30.90 01-DEC-07:10 58.83 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 29.16   30.90   58.83   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 29.16   30.90   58.83   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 60.49 02-JAN-07:10 64.08 02-JAN-07:10 122.02 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 60.49 01-FEB-07:10 64.08 01-FEB-07:10 122.02 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 60.49 01-MAR-07:10 64.08 01-MAR-07:10 122.02 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 60.49 03-APR-06:10 64.08 03-APR-06:10 122.02 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 60.49 01-MAY-06:10 64.08 01-MAY-06:10 122.02 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 60.49 01-JUN-06:10 64.08 01-JUN-06:10 122.02 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 60.49 03-JUL-06:10 64.08 03-JUL-06:10 122.02 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 60.49 01-AUG-06:10 64.08 01-AUG-06:10 122.02 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 60.49 01-SEP-06:10 64.08 01-SEP-06:10 122.02 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 60.49 02-OCT-06:10 64.08 02-OCT-06:10 122.02 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 60.49 01-NOV-06:10 64.08 01-NOV-06:10 122.02 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 60.49 01-DEC-07:10 64.08 01-DEC-07:10 122.02 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 60.49   64.08   122.02   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 60.49   64.08   122.02   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 LOBBY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 671.83 02-JAN-07:10 446.72 02-JAN-07:10 677.66 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 96.43 04-JAN-12:00
February 671.83 01-FEB-07:10 446.72 01-FEB-07:10 677.66 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 98.84 12-FEB-23:00
March 671.83 01-MAR-07:10 446.72 01-MAR-07:10 677.66 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 53.94 14-MAR-15:00
April 671.83 03-APR-06:10 446.72 03-APR-06:10 677.66 03-APR-05:10 0.00 0.00 0.00 0.00 7.45 23-APR-16:00 51.46 04-APR-18:00
May 671.83 01-MAY-06:10 446.72 01-MAY-06:10 677.66 01-MAY-05:10 0.00 0.00 0.00 0.00 5.66 24-MAY-15:00 18.96 09-MAY-08:70
June 671.83 01-JUN-06:10 446.72 01-JUN-06:10 677.66 01-JUN-05:10 0.00 0.00 0.00 0.00 14.85 29-JUN-16:00 21.55 09-JUN-09:00
July 671.83 03-JUL-06:10 446.72 03-JUL-06:10 677.66 03-JUL-05:10 0.00 0.00 0.00 0.00 12.12 15-JUL-14:01 11.11 08-JUL-14:10
August 671.83 01-AUG-06:10 446.72 01-AUG-06:10 677.66 01-AUG-05:10 0.00 0.00 0.00 0.00 10.73 08-AUG-16:00 26.76 17-AUG-14:00
September 671.83 01-SEP-06:10 446.72 01-SEP-06:10 677.66 01-SEP-05:10 0.00 0.00 0.00 0.00 3.10 07-SEP-15:00 22.90 20-SEP-06:00
October 671.83 02-OCT-06:10 446.72 02-OCT-06:10 677.66 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 19-OCT-15:00 38.01 31-OCT-10:55
November 671.83 01-NOV-06:10 446.72 01-NOV-06:10 677.66 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 56.35 22-NOV-02:00
December 671.83 01-DEC-07:10 446.72 01-DEC-07:10 677.66 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 88.95 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 671.83   446.72   677.66   0.00 0.00 0.00 0.00 0.00   11.11  
Maximum of Months 671.83   446.72   677.66   0.00 0.00 0.00 0.00 14.85   98.84  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1069.30 02-JAN-07:10 350.46 02-JAN-07:10 1961.01 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 97.65 04-JAN-12:00
February 1069.30 01-FEB-07:10 350.46 01-FEB-07:10 1961.01 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 102.84 12-FEB-23:00
March 1069.30 01-MAR-07:10 350.46 01-MAR-07:10 1961.01 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 53.93 14-MAR-15:00
April 1069.30 03-APR-06:10 350.46 03-APR-06:10 1961.01 03-APR-05:10 0.00 0.00 0.00 0.00 9.42 23-APR-16:10 51.50 04-APR-18:00
May 1069.30 01-MAY-06:10 350.46 01-MAY-06:10 1961.01 01-MAY-05:10 0.00 0.00 0.00 0.00 5.66 24-MAY-15:00 19.94 09-MAY-05:07
June 1069.30 01-JUN-06:10 350.46 01-JUN-06:10 1961.01 01-JUN-05:10 0.00 0.00 0.00 0.00 14.85 29-JUN-16:00 21.55 09-JUN-09:00
July 1069.30 03-JUL-06:10 350.46 03-JUL-06:10 1961.01 03-JUL-05:10 0.00 0.00 0.00 0.00 12.11 15-JUL-14:01 11.53 08-JUL-14:10
August 1069.30 01-AUG-06:10 350.46 01-AUG-06:10 1961.01 01-AUG-05:10 0.00 0.00 0.00 0.00 10.73 08-AUG-16:00 26.76 17-AUG-14:00
September 1069.30 01-SEP-06:10 350.46 01-SEP-06:10 1961.01 01-SEP-05:10 0.00 0.00 0.00 0.00 3.10 07-SEP-15:00 24.25 20-SEP-06:00
October 1069.30 02-OCT-06:10 350.46 02-OCT-06:10 1961.01 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 19-OCT-15:00 38.01 31-OCT-10:55
November 1069.30 01-NOV-06:10 350.46 01-NOV-06:10 1961.01 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 58.96 22-NOV-02:00
December 1069.30 01-DEC-07:10 350.46 01-DEC-07:10 1961.01 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 89.48 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 1069.30   350.46   1961.01   0.00 0.00 0.00 0.00 0.00   11.53  
Maximum of Months 1069.30   350.46   1961.01   0.00 0.00 0.00 0.00 14.85   102.84  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 583.26 02-JAN-07:10 191.16 02-JAN-07:10 1069.64 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 583.26 01-FEB-07:10 191.16 01-FEB-07:10 1069.64 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 583.26 01-MAR-07:10 191.16 01-MAR-07:10 1069.64 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 583.26 03-APR-06:10 191.16 03-APR-06:10 1069.64 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 583.26 01-MAY-06:10 191.16 01-MAY-06:10 1069.64 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 583.26 01-JUN-06:10 191.16 01-JUN-06:10 1069.64 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 583.26 03-JUL-06:10 191.16 03-JUL-06:10 1069.64 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 583.26 01-AUG-06:10 191.16 01-AUG-06:10 1069.64 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 583.26 01-SEP-06:10 191.16 01-SEP-06:10 1069.64 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 583.26 02-OCT-06:10 191.16 02-OCT-06:10 1069.64 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 583.26 01-NOV-06:10 191.16 01-NOV-06:10 1069.64 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 583.26 01-DEC-07:10 191.16 01-DEC-07:10 1069.64 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 583.26   191.16   1069.64   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 583.26   191.16   1069.64   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 362.92 02-JAN-07:10 142.13 02-JAN-07:10 1663.99 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 362.92 01-FEB-07:10 142.13 01-FEB-07:10 1663.99 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 362.92 01-MAR-07:10 142.13 01-MAR-07:10 1663.99 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 362.92 03-APR-06:10 142.13 03-APR-06:10 1663.99 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 362.92 01-MAY-06:10 142.13 01-MAY-06:10 1663.99 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 362.92 01-JUN-06:10 142.13 01-JUN-06:10 1663.99 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 362.92 03-JUL-06:10 142.13 03-JUL-06:10 1663.99 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 362.92 01-AUG-06:10 142.13 01-AUG-06:10 1663.99 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 362.92 01-SEP-06:10 142.13 01-SEP-06:10 1663.99 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 362.92 02-OCT-06:10 142.13 02-OCT-06:10 1663.99 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 362.92 01-NOV-06:10 142.13 01-NOV-06:10 1663.99 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 362.92 01-DEC-07:10 142.13 01-DEC-07:10 1663.99 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 362.92   142.13   1663.99   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 362.92   142.13   1663.99   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 950.49 02-JAN-07:10 290.35 02-JAN-07:10 4358.06 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 950.49 01-FEB-07:10 290.35 01-FEB-07:10 4358.06 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 950.49 01-MAR-07:10 290.35 01-MAR-07:10 4358.06 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 950.49 03-APR-06:10 290.35 03-APR-06:10 4358.06 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 950.49 01-MAY-06:10 290.35 01-MAY-06:10 4358.06 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 950.49 01-JUN-06:10 290.35 01-JUN-06:10 4358.06 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 950.49 03-JUL-06:10 290.35 03-JUL-06:10 4358.06 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 950.49 01-AUG-06:10 290.35 01-AUG-06:10 4358.06 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 950.49 01-SEP-06:10 290.35 01-SEP-06:10 4358.06 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 950.49 02-OCT-06:10 290.35 02-OCT-06:10 4358.06 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 950.49 01-NOV-06:10 290.35 01-NOV-06:10 4358.06 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 950.49 01-DEC-07:10 290.35 01-DEC-07:10 4358.06 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 950.49   290.35   4358.06   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 950.49   290.35   4358.06   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 393.16 02-JAN-07:10 191.65 02-JAN-07:10 360.56 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 393.16 01-FEB-07:10 191.65 01-FEB-07:10 360.56 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 393.16 01-MAR-07:10 191.65 01-MAR-07:10 360.56 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 393.16 03-APR-06:10 191.65 03-APR-06:10 360.56 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 393.16 01-MAY-06:10 191.65 01-MAY-06:10 360.56 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 393.16 01-JUN-06:10 191.65 01-JUN-06:10 360.56 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 393.16 03-JUL-06:10 191.65 03-JUL-06:10 360.56 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 393.16 01-AUG-06:10 191.65 01-AUG-06:10 360.56 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 393.16 01-SEP-06:10 191.65 01-SEP-06:10 360.56 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 393.16 02-OCT-06:10 191.65 02-OCT-06:10 360.56 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 393.16 01-NOV-06:10 191.65 01-NOV-06:10 360.56 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 393.16 01-DEC-07:10 191.65 01-DEC-07:10 360.56 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 393.16   191.65   360.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 393.16   191.65   360.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 563.81 02-JAN-07:10 274.83 02-JAN-07:10 517.07 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 563.81 01-FEB-07:10 274.83 01-FEB-07:10 517.07 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 563.81 01-MAR-07:10 274.83 01-MAR-07:10 517.07 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 563.81 03-APR-06:10 274.83 03-APR-06:10 517.07 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 563.81 01-MAY-06:10 274.83 01-MAY-06:10 517.07 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 563.81 01-JUN-06:10 274.83 01-JUN-06:10 517.07 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 563.81 03-JUL-06:10 274.83 03-JUL-06:10 517.07 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 563.81 01-AUG-06:10 274.83 01-AUG-06:10 517.07 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 563.81 01-SEP-06:10 274.83 01-SEP-06:10 517.07 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 563.81 02-OCT-06:10 274.83 02-OCT-06:10 517.07 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 563.81 01-NOV-06:10 274.83 01-NOV-06:10 517.07 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 563.81 01-DEC-07:10 274.83 01-DEC-07:10 517.07 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 563.81   274.83   517.07   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 563.81   274.83   517.07   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 260.85 02-JAN-07:10 276.35 02-JAN-07:10 526.22 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 260.85 01-FEB-07:10 276.35 01-FEB-07:10 526.22 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 260.85 01-MAR-07:10 276.35 01-MAR-07:10 526.22 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 260.85 03-APR-06:10 276.35 03-APR-06:10 526.22 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 260.85 01-MAY-06:10 276.35 01-MAY-06:10 526.22 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 260.85 01-JUN-06:10 276.35 01-JUN-06:10 526.22 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 260.85 03-JUL-06:10 276.35 03-JUL-06:10 526.22 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 260.85 01-AUG-06:10 276.35 01-AUG-06:10 526.22 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 260.85 01-SEP-06:10 276.35 01-SEP-06:10 526.22 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 260.85 02-OCT-06:10 276.35 02-OCT-06:10 526.22 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 260.85 01-NOV-06:10 276.35 01-NOV-06:10 526.22 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 260.85 01-DEC-07:10 276.35 01-DEC-07:10 526.22 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 260.85   276.35   526.22   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 260.85   276.35   526.22   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 993.70 02-JAN-07:10 935.64 02-JAN-07:10 1822.63 02-JAN-06:10 1608.99 02-JAN-06:10 0.00 0.00 0.00 0.00 01-JAN-00:10 179.15 04-JAN-12:00
February 993.70 01-FEB-07:10 935.64 01-FEB-07:10 1822.63 01-FEB-06:10 1608.99 01-FEB-06:10 0.00 0.00 0.00 0.00 01-FEB-00:10 192.47 12-FEB-23:00
March 993.70 01-MAR-07:10 935.64 01-MAR-07:10 1822.63 01-MAR-06:10 1608.99 01-MAR-06:10 0.00 0.00 0.00 0.00 01-MAR-00:10 95.45 15-MAR-05:00
April 993.70 03-APR-06:10 935.64 03-APR-06:10 1822.63 03-APR-05:10 1608.99 03-APR-05:10 0.00 0.00 0.00 31.31 23-APR-16:00 95.58 04-APR-18:00
May 993.70 01-MAY-06:10 935.64 01-MAY-06:10 1822.63 01-MAY-05:10 1608.99 01-MAY-05:10 0.00 0.00 0.00 19.16 24-MAY-15:00 36.51 09-MAY-03:30
June 993.70 01-JUN-06:10 935.64 01-JUN-06:10 1822.63 01-JUN-05:10 1608.99 01-JUN-05:10 0.00 0.00 0.00 39.27 30-JUN-15:00 26.58 09-JUN-09:00
July 993.70 03-JUL-06:10 935.64 03-JUL-06:10 1822.63 03-JUL-05:10 1608.99 03-JUL-05:10 0.00 0.00 0.00 43.39 15-JUL-16:00 12.47 06-JUL-04:00
August 993.70 01-AUG-06:10 935.64 01-AUG-06:10 1822.63 01-AUG-05:10 1608.99 01-AUG-05:10 0.00 0.00 0.00 30.92 08-AUG-16:00 33.81 17-AUG-14:00
September 993.70 01-SEP-06:10 935.64 01-SEP-06:10 1822.63 01-SEP-05:10 1608.99 01-SEP-05:10 0.00 0.00 0.00 19.97 07-SEP-15:00 41.84 20-SEP-03:54
October 993.70 02-OCT-06:10 935.64 02-OCT-06:10 1822.63 02-OCT-05:10 1608.99 02-OCT-05:10 0.00 0.00 0.00 9.13 19-OCT-15:00 65.08 31-OCT-18:55
November 993.70 01-NOV-06:10 935.64 01-NOV-06:10 1822.63 01-NOV-05:10 1608.99 01-NOV-05:10 0.00 0.00 0.00 0.21 01-NOV-15:00 100.65 22-NOV-02:00
December 993.70 01-DEC-07:10 935.64 01-DEC-07:10 1822.63 01-DEC-06:10 1608.99 01-DEC-06:10 0.00 0.00 0.00 0.00 01-DEC-00:03 162.90 18-DEC-15:00
                               
Annual Sum or Average                              
Minimum of Months 993.70   935.64   1822.63   1608.99   0.00 0.00 0.00 0.00   12.47  
Maximum of Months 993.70   935.64   1822.63   1608.99   0.00 0.00 0.00 43.39   192.47  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1036.90 02-JAN-07:10 976.32 02-JAN-07:10 1901.88 02-JAN-06:10 1678.94 02-JAN-06:10 0.00 0.00 0.00 0.00 01-JAN-00:10 100.44 04-JAN-12:00
February 1036.90 01-FEB-07:10 976.32 01-FEB-07:10 1901.88 01-FEB-06:10 1678.94 01-FEB-06:10 0.00 0.00 0.00 0.00 01-FEB-00:10 110.04 12-FEB-23:00
March 1036.90 01-MAR-07:10 976.32 01-MAR-07:10 1901.88 01-MAR-06:10 1678.94 01-MAR-06:10 0.00 0.00 0.00 0.00 01-MAR-00:10 54.00 15-MAR-05:00
April 1036.90 03-APR-06:10 976.32 03-APR-06:10 1901.88 03-APR-05:10 1678.94 03-APR-05:10 0.00 0.00 0.00 17.48 23-APR-16:00 53.34 04-APR-18:00
May 1036.90 01-MAY-06:10 976.32 01-MAY-06:10 1901.88 01-MAY-05:10 1678.94 01-MAY-05:10 0.00 0.00 0.00 11.05 24-MAY-15:00 20.84 09-MAY-03:30
June 1036.90 01-JUN-06:10 976.32 01-JUN-06:10 1901.88 01-JUN-05:10 1678.94 01-JUN-05:10 0.00 0.00 0.00 22.16 30-JUN-15:00 13.76 09-JUN-09:00
July 1036.90 03-JUL-06:10 976.32 03-JUL-06:10 1901.88 03-JUL-05:10 1678.94 03-JUL-05:10 0.00 0.00 0.00 26.57 15-JUL-16:00 7.04 06-JUL-04:00
August 1036.90 01-AUG-06:10 976.32 01-AUG-06:10 1901.88 01-AUG-05:10 1678.94 01-AUG-05:10 0.00 0.00 0.00 17.61 08-AUG-16:00 17.74 17-AUG-14:00
September 1036.90 01-SEP-06:10 976.32 01-SEP-06:10 1901.88 01-SEP-05:10 1678.94 01-SEP-05:10 0.00 0.00 0.00 11.90 07-SEP-15:00 23.47 20-SEP-03:54
October 1036.90 02-OCT-06:10 976.32 02-OCT-06:10 1901.88 02-OCT-05:10 1678.94 02-OCT-05:10 0.00 0.00 0.00 5.85 19-OCT-15:00 36.32 31-OCT-18:55
November 1036.90 01-NOV-06:10 976.32 01-NOV-06:10 1901.88 01-NOV-05:10 1678.94 01-NOV-05:10 0.00 0.00 0.00 0.50 01-NOV-14:50 56.94 22-NOV-02:00
December 1036.90 01-DEC-07:10 976.32 01-DEC-07:10 1901.88 01-DEC-06:10 1678.94 01-DEC-06:10 0.00 0.00 0.00 0.00 01-DEC-00:03 91.57 18-DEC-15:00
                               
Annual Sum or Average                              
Minimum of Months 1036.90   976.32   1901.88   1678.94   0.00 0.00 0.00 0.00   7.04  
Maximum of Months 1036.90   976.32   1901.88   1678.94   0.00 0.00 0.00 26.57   110.04  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1028.26 02-JAN-07:10 968.18 02-JAN-07:10 1886.03 02-JAN-06:10 1664.95 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00
February 1028.26 01-FEB-07:10 968.18 01-FEB-07:10 1886.03 01-FEB-06:10 1664.95 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00
March 1028.26 01-MAR-07:10 968.18 01-MAR-07:10 1886.03 01-MAR-06:10 1664.95 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 1028.26 03-APR-06:10 968.18 03-APR-06:10 1886.03 03-APR-05:10 1664.95 03-APR-05:10 0.00 0.00 0.00 0.00 0.00
May 1028.26 01-MAY-06:10 968.18 01-MAY-06:10 1886.03 01-MAY-05:10 1664.95 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00
June 1028.26 01-JUN-06:10 968.18 01-JUN-06:10 1886.03 01-JUN-05:10 1664.95 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00
July 1028.26 03-JUL-06:10 968.18 03-JUL-06:10 1886.03 03-JUL-05:10 1664.95 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00
August 1028.26 01-AUG-06:10 968.18 01-AUG-06:10 1886.03 01-AUG-05:10 1664.95 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00
September 1028.26 01-SEP-06:10 968.18 01-SEP-06:10 1886.03 01-SEP-05:10 1664.95 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00
October 1028.26 02-OCT-06:10 968.18 02-OCT-06:10 1886.03 02-OCT-05:10 1664.95 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00
November 1028.26 01-NOV-06:10 968.18 01-NOV-06:10 1886.03 01-NOV-05:10 1664.95 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00
December 1028.26 01-DEC-07:10 968.18 01-DEC-07:10 1886.03 01-DEC-06:10 1664.95 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00
                           
Annual Sum or Average                          
Minimum of Months 1028.26   968.18   1886.03   1664.95   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1028.26   968.18   1886.03   1664.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 PACU

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 233.30 02-JAN-07:10 121.50 02-JAN-07:10 320.89 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 233.30 01-FEB-07:10 121.50 01-FEB-07:10 320.89 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 233.30 01-MAR-07:10 121.50 01-MAR-07:10 320.89 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 233.30 03-APR-06:10 121.50 03-APR-06:10 320.89 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 233.30 01-MAY-06:10 121.50 01-MAY-06:10 320.89 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 233.30 01-JUN-06:10 121.50 01-JUN-06:10 320.89 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 233.30 03-JUL-06:10 121.50 03-JUL-06:10 320.89 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 233.30 01-AUG-06:10 121.50 01-AUG-06:10 320.89 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 233.30 01-SEP-06:10 121.50 01-SEP-06:10 320.89 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 233.30 02-OCT-06:10 121.50 02-OCT-06:10 320.89 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 233.30 01-NOV-06:10 121.50 01-NOV-06:10 320.89 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 233.30 01-DEC-07:10 121.50 01-DEC-07:10 320.89 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 233.30   121.50   320.89   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 233.30   121.50   320.89   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 204.14 02-JAN-07:10 115.67 02-JAN-07:10 374.43 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 16.86 04-JAN-11:53
February 204.14 01-FEB-07:10 115.67 01-FEB-07:10 374.43 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 17.84 12-FEB-23:00
March 204.14 01-MAR-07:10 115.67 01-MAR-07:10 374.43 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 9.28 06-MAR-13:00
April 204.14 03-APR-06:10 115.67 03-APR-06:10 374.43 03-APR-05:10 0.00 0.00 0.00 0.00 3.02 23-APR-16:00 8.42 19-APR-10:00
May 204.14 01-MAY-06:10 115.67 01-MAY-06:10 374.43 01-MAY-05:10 0.00 0.00 0.00 0.00 1.57 24-MAY-17:10 3.01 20-MAY-06:10
June 204.14 01-JUN-06:10 115.67 01-JUN-06:10 374.43 01-JUN-05:10 0.00 0.00 0.00 0.00 2.93 29-JUN-16:00 3.41 09-JUN-09:00
July 204.14 03-JUL-06:10 115.67 03-JUL-06:10 374.43 03-JUL-05:10 0.00 0.00 0.00 0.00 3.66 15-JUL-16:00 1.55 08-JUL-14:00
August 204.14 01-AUG-06:10 115.67 01-AUG-06:10 374.43 01-AUG-05:10 0.00 0.00 0.00 0.00 2.21 08-AUG-16:00 4.36 17-AUG-14:00
September 204.14 01-SEP-06:10 115.67 01-SEP-06:10 374.43 01-SEP-05:10 0.00 0.00 0.00 0.00 0.93 07-SEP-15:00 3.59 20-SEP-06:10
October 204.14 02-OCT-06:10 115.67 02-OCT-06:10 374.43 02-OCT-05:10 0.00 0.00 0.00 0.00 0.30 21-OCT-15:00 6.32 31-OCT-10:55
November 204.14 01-NOV-06:10 115.67 01-NOV-06:10 374.43 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 9.08 22-NOV-02:00
December 204.14 01-DEC-07:10 115.67 01-DEC-07:10 374.43 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 15.65 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 204.14   115.67   374.43   0.00 0.00 0.00 0.00 0.00   1.55  
Maximum of Months 204.14   115.67   374.43   0.00 0.00 0.00 0.00 3.66   17.84  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 365.08 02-JAN-07:10 206.86 02-JAN-07:10 669.62 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 365.08 01-FEB-07:10 206.86 01-FEB-07:10 669.62 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 365.08 01-MAR-07:10 206.86 01-MAR-07:10 669.62 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 365.08 03-APR-06:10 206.86 03-APR-06:10 669.62 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 365.08 01-MAY-06:10 206.86 01-MAY-06:10 669.62 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 365.08 01-JUN-06:10 206.86 01-JUN-06:10 669.62 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 365.08 03-JUL-06:10 206.86 03-JUL-06:10 669.62 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 365.08 01-AUG-06:10 206.86 01-AUG-06:10 669.62 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 365.08 01-SEP-06:10 206.86 01-SEP-06:10 669.62 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 365.08 02-OCT-06:10 206.86 02-OCT-06:10 669.62 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 365.08 01-NOV-06:10 206.86 01-NOV-06:10 669.62 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 365.08 01-DEC-07:10 206.86 01-DEC-07:10 669.62 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 365.08   206.86   669.62   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 365.08   206.86   669.62   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 615.66 02-JAN-07:10 359.10 02-JAN-07:10 846.80 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 81.56 04-JAN-12:00
February 615.66 01-FEB-07:10 359.10 01-FEB-07:10 846.80 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 82.47 12-FEB-23:00
March 615.66 01-MAR-07:10 359.10 01-MAR-07:10 846.80 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 44.30 14-MAR-16:00
April 615.66 03-APR-06:10 359.10 03-APR-06:10 846.80 03-APR-05:10 0.00 0.00 0.00 0.00 14.35 23-APR-16:00 40.15 26-APR-15:00
May 615.66 01-MAY-06:10 359.10 01-MAY-06:10 846.80 01-MAY-05:10 0.00 0.00 0.00 0.00 7.93 24-MAY-17:09 14.27 09-MAY-08:20
June 615.66 01-JUN-06:10 359.10 01-JUN-06:10 846.80 01-JUN-05:10 0.00 0.00 0.00 0.00 13.95 29-JUN-16:00 15.62 09-JUN-09:00
July 615.66 03-JUL-06:10 359.10 03-JUL-06:10 846.80 03-JUL-05:10 0.00 0.00 0.00 0.00 17.37 15-JUL-16:00 6.85 08-JUL-14:00
August 615.66 01-AUG-06:10 359.10 01-AUG-06:10 846.80 01-AUG-05:10 0.00 0.00 0.00 0.00 10.97 08-AUG-17:07 20.22 17-AUG-14:00
September 615.66 01-SEP-06:10 359.10 01-SEP-06:10 846.80 01-SEP-05:10 0.00 0.00 0.00 0.00 4.65 07-SEP-15:00 16.91 20-SEP-06:10
October 615.66 02-OCT-06:10 359.10 02-OCT-06:10 846.80 02-OCT-05:10 0.00 0.00 0.00 0.00 1.53 21-OCT-15:00 30.25 31-OCT-11:00
November 615.66 01-NOV-06:10 359.10 01-NOV-06:10 846.80 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 43.16 22-NOV-02:00
December 615.66 01-DEC-07:10 359.10 01-DEC-07:10 846.80 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 74.21 18-DEC-15:08
                             
Annual Sum or Average                            
Minimum of Months 615.66   359.10   846.80   0.00 0.00 0.00 0.00 0.00   6.85  
Maximum of Months 615.66   359.10   846.80   0.00 0.00 0.00 0.00 17.37   82.47  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1649.32 02-JAN-07:10 384.80 02-JAN-07:10 554.54 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 57.70 04-JAN-12:00
February 1649.32 01-FEB-07:10 384.80 01-FEB-07:10 554.54 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 60.66 12-FEB-23:00
March 1649.32 01-MAR-07:10 384.80 01-MAR-07:10 554.54 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 31.87 14-MAR-15:00
April 1649.32 03-APR-06:10 384.80 03-APR-06:10 554.54 03-APR-05:10 0.00 0.00 0.00 0.00 5.28 23-APR-16:00 30.68 04-APR-18:00
May 1649.32 01-MAY-06:10 384.80 01-MAY-06:10 554.54 01-MAY-05:10 0.00 0.00 0.00 0.00 3.35 24-MAY-15:00 11.66 09-MAY-06:00
June 1649.32 01-JUN-06:10 384.80 01-JUN-06:10 554.54 01-JUN-05:10 0.00 0.00 0.00 0.00 8.77 29-JUN-16:00 12.73 09-JUN-09:00
July 1649.32 03-JUL-06:10 384.80 03-JUL-06:10 554.54 03-JUL-05:10 0.00 0.00 0.00 0.00 7.19 15-JUL-15:00 6.70 08-JUL-14:10
August 1649.32 01-AUG-06:10 384.80 01-AUG-06:10 554.54 01-AUG-05:10 0.00 0.00 0.00 0.00 6.34 08-AUG-16:00 15.81 17-AUG-14:00
September 1649.32 01-SEP-06:10 384.80 01-SEP-06:10 554.54 01-SEP-05:10 0.00 0.00 0.00 0.00 1.84 07-SEP-15:00 14.33 20-SEP-06:00
October 1649.32 02-OCT-06:10 384.80 02-OCT-06:10 554.54 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 19-OCT-15:00 22.46 31-OCT-10:55
November 1649.32 01-NOV-06:10 384.80 01-NOV-06:10 554.54 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 34.68 22-NOV-02:00
December 1649.32 01-DEC-07:10 384.80 01-DEC-07:10 554.54 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 52.87 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 1649.32   384.80   554.54   0.00 0.00 0.00 0.00 0.00   6.70  
Maximum of Months 1649.32   384.80   554.54   0.00 0.00 0.00 0.00 8.77   60.66  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1166.51 02-JAN-07:10 607.50 02-JAN-07:10 1604.46 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 194.89 04-JAN-11:57
February 1166.51 01-FEB-07:10 607.50 01-FEB-07:10 1604.46 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 194.32 12-FEB-23:00
March 1166.51 01-MAR-07:10 607.50 01-MAR-07:10 1604.46 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 106.57 14-MAR-15:10
April 1166.51 03-APR-06:10 607.50 03-APR-06:10 1604.46 03-APR-05:10 0.00 0.00 0.00 0.00 33.98 23-APR-16:00 97.49 26-APR-15:00
May 1166.51 01-MAY-06:10 607.50 01-MAY-06:10 1604.46 01-MAY-05:10 0.00 0.00 0.00 0.00 15.75 24-MAY-17:50 37.38 20-MAY-06:10
June 1166.51 01-JUN-06:10 607.50 01-JUN-06:10 1604.46 01-JUN-05:10 0.00 0.00 0.00 0.00 32.98 29-JUN-16:00 39.72 09-JUN-09:00
July 1166.51 03-JUL-06:10 607.50 03-JUL-06:10 1604.46 03-JUL-05:10 0.00 0.00 0.00 0.00 38.58 15-JUL-16:00 19.69 08-JUL-14:00
August 1166.51 01-AUG-06:10 607.50 01-AUG-06:10 1604.46 01-AUG-05:10 0.00 0.00 0.00 0.00 24.44 08-AUG-16:00 49.56 17-AUG-14:00
September 1166.51 01-SEP-06:10 607.50 01-SEP-06:10 1604.46 01-SEP-05:10 0.00 0.00 0.00 0.00 8.99 24-SEP-15:00 42.71 20-SEP-06:10
October 1166.51 02-OCT-06:10 607.50 02-OCT-06:10 1604.46 02-OCT-05:10 0.00 0.00 0.00 0.00 0.47 22-OCT-15:00 73.49 31-OCT-11:00
November 1166.51 01-NOV-06:10 607.50 01-NOV-06:10 1604.46 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 102.19 22-NOV-02:00
December 1166.51 01-DEC-07:10 607.50 01-DEC-07:10 1604.46 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 177.24 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 1166.51   607.50   1604.46   0.00 0.00 0.00 0.00 0.00   19.69  
Maximum of Months 1166.51   607.50   1604.46   0.00 0.00 0.00 0.00 38.58   194.89  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 64.27 02-JAN-07:10 68.09 02-JAN-07:10 129.65 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 30.39 04-JAN-12:00
February 64.27 01-FEB-07:10 68.09 01-FEB-07:10 129.65 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 31.72 12-FEB-23:00
March 64.27 01-MAR-07:10 68.09 01-MAR-07:10 129.65 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 17.08 14-MAR-15:00
April 64.27 03-APR-06:10 68.09 03-APR-06:10 129.65 03-APR-05:10 0.00 0.00 0.00 0.00 3.39 23-APR-16:00 15.91 19-APR-10:00
May 64.27 01-MAY-06:10 68.09 01-MAY-06:10 129.65 01-MAY-05:10 0.00 0.00 0.00 0.00 1.80 24-MAY-15:00 5.88 09-MAY-09:00
June 64.27 01-JUN-06:10 68.09 01-JUN-06:10 129.65 01-JUN-05:10 0.00 0.00 0.00 0.00 4.72 29-JUN-16:00 6.86 09-JUN-09:00
July 64.27 03-JUL-06:10 68.09 03-JUL-06:10 129.65 03-JUL-05:10 0.00 0.00 0.00 0.00 4.26 15-JUL-15:00 3.77 08-JUL-14:00
August 64.27 01-AUG-06:10 68.09 01-AUG-06:10 129.65 01-AUG-05:10 0.00 0.00 0.00 0.00 3.41 08-AUG-16:00 8.92 17-AUG-14:00
September 64.27 01-SEP-06:10 68.09 01-SEP-06:10 129.65 01-SEP-05:10 0.00 0.00 0.00 0.00 0.99 07-SEP-15:00 7.15 28-SEP-12:00
October 64.27 02-OCT-06:10 68.09 02-OCT-06:10 129.65 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 19-OCT-15:00 12.07 31-OCT-11:00
November 64.27 01-NOV-06:10 68.09 01-NOV-06:10 129.65 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 17.95 22-NOV-02:00
December 64.27 01-DEC-07:10 68.09 01-DEC-07:10 129.65 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 28.16 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 64.27   68.09   129.65   0.00 0.00 0.00 0.00 0.00   3.77  
Maximum of Months 64.27   68.09   129.65   0.00 0.00 0.00 0.00 4.72   31.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 SOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 272.19 02-JAN-07:10 158.76 02-JAN-07:10 249.62 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 272.19 01-FEB-07:10 158.76 01-FEB-07:10 249.62 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 272.19 01-MAR-07:10 158.76 01-MAR-07:10 249.62 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 272.19 03-APR-06:10 158.76 03-APR-06:10 249.62 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 272.19 01-MAY-06:10 158.76 01-MAY-06:10 249.62 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 272.19 01-JUN-06:10 158.76 01-JUN-06:10 249.62 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 272.19 03-JUL-06:10 158.76 03-JUL-06:10 249.62 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 272.19 01-AUG-06:10 158.76 01-AUG-06:10 249.62 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 272.19 01-SEP-06:10 158.76 01-SEP-06:10 249.62 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 272.19 02-OCT-06:10 158.76 02-OCT-06:10 249.62 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 272.19 01-NOV-06:10 158.76 01-NOV-06:10 249.62 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 272.19 01-DEC-07:10 158.76 01-DEC-07:10 249.62 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 272.19   158.76   249.62   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 272.19   158.76   249.62   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 120.97 02-JAN-07:10 70.56 02-JAN-07:10 110.94 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 120.97 01-FEB-07:10 70.56 01-FEB-07:10 110.94 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 120.97 01-MAR-07:10 70.56 01-MAR-07:10 110.94 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 120.97 03-APR-06:10 70.56 03-APR-06:10 110.94 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 120.97 01-MAY-06:10 70.56 01-MAY-06:10 110.94 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 120.97 01-JUN-06:10 70.56 01-JUN-06:10 110.94 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 120.97 03-JUL-06:10 70.56 03-JUL-06:10 110.94 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 120.97 01-AUG-06:10 70.56 01-AUG-06:10 110.94 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 120.97 01-SEP-06:10 70.56 01-SEP-06:10 110.94 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 120.97 02-OCT-06:10 70.56 02-OCT-06:10 110.94 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 120.97 01-NOV-06:10 70.56 01-NOV-06:10 110.94 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 120.97 01-DEC-07:10 70.56 01-DEC-07:10 110.94 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 120.97   70.56   110.94   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 120.97   70.56   110.94   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 388.84 02-JAN-07:10 226.80 02-JAN-07:10 356.60 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 388.84 01-FEB-07:10 226.80 01-FEB-07:10 356.60 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 388.84 01-MAR-07:10 226.80 01-MAR-07:10 356.60 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 388.84 03-APR-06:10 226.80 03-APR-06:10 356.60 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 388.84 01-MAY-06:10 226.80 01-MAY-06:10 356.60 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 388.84 01-JUN-06:10 226.80 01-JUN-06:10 356.60 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 388.84 03-JUL-06:10 226.80 03-JUL-06:10 356.60 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 388.84 01-AUG-06:10 226.80 01-AUG-06:10 356.60 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 388.84 01-SEP-06:10 226.80 01-SEP-06:10 356.60 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 388.84 02-OCT-06:10 226.80 02-OCT-06:10 356.60 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 388.84 01-NOV-06:10 226.80 01-NOV-06:10 356.60 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 388.84 01-DEC-07:10 226.80 01-DEC-07:10 356.60 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 388.84   226.80   356.60   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 388.84   226.80   356.60   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 648.06 02-JAN-07:10 337.50 02-JAN-07:10 891.37 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 160.13 04-JAN-11:57
February 648.06 01-FEB-07:10 337.50 01-FEB-07:10 891.37 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 159.76 12-FEB-23:00
March 648.06 01-MAR-07:10 337.50 01-MAR-07:10 891.37 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 87.62 14-MAR-15:50
April 648.06 03-APR-06:10 337.50 03-APR-06:10 891.37 03-APR-05:10 0.00 0.00 0.00 0.00 27.07 23-APR-16:00 80.17 26-APR-15:00
May 648.06 01-MAY-06:10 337.50 01-MAY-06:10 891.37 01-MAY-05:10 0.00 0.00 0.00 0.00 11.34 24-MAY-17:50 30.74 20-MAY-06:10
June 648.06 01-JUN-06:10 337.50 01-JUN-06:10 891.37 01-JUN-05:10 0.00 0.00 0.00 0.00 24.99 29-JUN-16:00 32.66 09-JUN-09:00
July 648.06 03-JUL-06:10 337.50 03-JUL-06:10 891.37 03-JUL-05:10 0.00 0.00 0.00 0.00 29.66 15-JUL-16:00 16.20 08-JUL-14:00
August 648.06 01-AUG-06:10 337.50 01-AUG-06:10 891.37 01-AUG-05:10 0.00 0.00 0.00 0.00 18.05 08-AUG-16:00 40.75 17-AUG-14:00
September 648.06 01-SEP-06:10 337.50 01-SEP-06:10 891.37 01-SEP-05:10 0.00 0.00 0.00 0.00 6.17 24-SEP-15:00 35.12 20-SEP-06:06
October 648.06 02-OCT-06:10 337.50 02-OCT-06:10 891.37 02-OCT-05:10 0.00 0.00 0.00 0.00 0.01 19-OCT-15:00 60.43 31-OCT-10:55
November 648.06 01-NOV-06:10 337.50 01-NOV-06:10 891.37 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 84.03 22-NOV-02:00
December 648.06 01-DEC-07:10 337.50 01-DEC-07:10 891.37 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 145.78 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 648.06   337.50   891.37   0.00 0.00 0.00 0.00 0.00   16.20  
Maximum of Months 648.06   337.50   891.37   0.00 0.00 0.00 0.00 29.66   160.13  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1814.58 02-JAN-07:10 293.33 02-JAN-07:10 332.67 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 249.70 04-JAN-11:53
February 1814.58 01-FEB-07:10 293.33 01-FEB-07:10 332.67 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 248.35 12-FEB-23:00
March 1814.58 01-MAR-07:10 293.33 01-MAR-17:00 332.67 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 141.01 14-MAR-15:00
April 1814.58 03-APR-06:10 263.91 03-APR-06:10 332.67 03-APR-05:10 0.00 0.00 0.00 0.00 29.78 23-APR-16:00 130.93 26-APR-15:00
May 1814.58 01-MAY-06:10 174.20 08-MAY-05:10 332.67 01-MAY-05:10 0.00 0.00 0.00 0.00 14.75 24-MAY-15:00 49.59 09-MAY-08:20
June 1814.58 01-JUN-06:10 221.75 30-JUN-06:10 332.67 01-JUN-05:10 0.00 0.00 0.00 0.00 38.74 29-JUN-16:00 56.39 09-JUN-09:00
July 1814.58 03-JUL-06:10 186.70 25-JUL-05:10 332.67 03-JUL-05:10 0.00 0.00 0.00 0.00 39.65 15-JUL-16:00 25.23 08-JUL-14:00
August 1814.58 01-AUG-06:10 268.55 31-AUG-06:10 332.67 01-AUG-05:10 0.00 0.00 0.00 0.00 27.98 08-AUG-16:00 67.11 17-AUG-14:10
September 1814.58 01-SEP-06:10 293.33 27-SEP-06:10 332.67 01-SEP-05:10 0.00 0.00 0.00 0.00 8.02 07-SEP-15:00 58.52 20-SEP-06:07
October 1814.58 02-OCT-06:10 293.33 02-OCT-06:10 332.67 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 95.82 31-OCT-11:10
November 1814.58 01-NOV-06:10 293.33 01-NOV-06:10 332.67 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 133.36 22-NOV-02:00
December 1814.58 01-DEC-07:10 293.33 01-DEC-07:10 332.67 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 228.20 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 1814.58   174.20   332.67   0.00 0.00 0.00 0.00 0.00   25.23  
Maximum of Months 1814.58   293.33   332.67   0.00 0.00 0.00 0.00 39.65   249.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 37.80 02-JAN-07:10 40.05 02-JAN-07:10 76.26 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 37.80 01-FEB-07:10 40.05 01-FEB-07:10 76.26 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 37.80 01-MAR-07:10 40.05 01-MAR-07:10 76.26 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 37.80 03-APR-06:10 40.05 03-APR-06:10 76.26 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 37.80 01-MAY-06:10 40.05 01-MAY-06:10 76.26 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 37.80 01-JUN-06:10 40.05 01-JUN-06:10 76.26 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 37.80 03-JUL-06:10 40.05 03-JUL-06:10 76.26 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 37.80 01-AUG-06:10 40.05 01-AUG-06:10 76.26 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 37.80 01-SEP-06:10 40.05 01-SEP-06:10 76.26 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 37.80 02-OCT-06:10 40.05 02-OCT-06:10 76.26 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 37.80 01-NOV-06:10 40.05 01-NOV-06:10 76.26 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 37.80 01-DEC-07:10 40.05 01-DEC-07:10 76.26 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 37.80   40.05   76.26   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 37.80   40.05   76.26   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 777.68 02-JAN-07:10 353.81 02-JAN-07:10 392.21 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 262.19 04-JAN-11:53
February 777.68 01-FEB-07:10 353.81 01-FEB-07:10 392.21 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 260.77 12-FEB-23:00
March 777.68 01-MAR-07:10 353.81 01-MAR-07:10 392.21 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 144.59 14-MAR-16:00
April 777.68 03-APR-06:10 353.81 03-APR-06:10 392.21 03-APR-05:10 0.00 0.00 0.00 0.00 32.12 23-APR-16:00 130.86 26-APR-15:00
May 777.68 01-MAY-06:10 353.81 01-MAY-06:10 392.21 01-MAY-05:10 0.00 0.00 0.00 0.00 15.48 24-MAY-15:00 50.30 20-MAY-06:05
June 777.68 01-JUN-06:10 353.81 01-JUN-06:10 392.21 01-JUN-05:10 0.00 0.00 0.00 0.00 40.67 29-JUN-16:00 53.96 09-JUN-09:00
July 777.68 03-JUL-06:10 353.81 03-JUL-06:10 392.21 03-JUL-05:10 0.00 0.00 0.00 0.00 44.66 15-JUL-16:00 26.49 08-JUL-14:00
August 777.68 01-AUG-06:10 353.81 01-AUG-06:10 392.21 01-AUG-05:10 0.00 0.00 0.00 0.00 29.37 08-AUG-16:00 67.95 17-AUG-14:00
September 777.68 01-SEP-06:10 353.81 01-SEP-06:10 392.21 01-SEP-05:10 0.00 0.00 0.00 0.00 9.43 07-SEP-13:00 58.32 20-SEP-06:02
October 777.68 02-OCT-06:10 353.81 02-OCT-06:10 392.21 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 98.66 31-OCT-10:55
November 777.68 01-NOV-06:10 353.81 01-NOV-06:10 392.21 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 137.20 22-NOV-02:00
December 777.68 01-DEC-07:10 353.81 01-DEC-07:10 392.21 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 239.61 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 777.68   353.81   392.21   0.00 0.00 0.00 0.00 0.00   26.49  
Maximum of Months 777.68   353.81   392.21   0.00 0.00 0.00 0.00 44.66   262.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1166.51 02-JAN-07:10 530.71 02-JAN-07:10 588.32 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 112.36 04-JAN-11:53
February 1166.51 01-FEB-07:10 530.71 01-FEB-07:10 588.32 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 111.76 12-FEB-23:00
March 1166.51 01-MAR-07:10 530.71 01-MAR-07:10 588.32 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 61.29 14-MAR-15:00
April 1166.51 03-APR-06:10 530.71 03-APR-06:10 588.32 03-APR-05:10 0.00 0.00 0.00 0.00 19.49 23-APR-16:00 56.08 26-APR-15:00
May 1166.51 01-MAY-06:10 530.71 01-MAY-06:10 588.32 01-MAY-05:10 0.00 0.00 0.00 0.00 8.94 24-MAY-17:50 21.51 20-MAY-06:10
June 1166.51 01-JUN-06:10 530.71 01-JUN-06:10 588.32 01-JUN-05:10 0.00 0.00 0.00 0.00 18.93 29-JUN-16:00 22.87 09-JUN-09:00
July 1166.51 03-JUL-06:10 530.71 03-JUL-06:10 588.32 03-JUL-05:10 0.00 0.00 0.00 0.00 22.53 15-JUL-16:00 11.35 08-JUL-14:00
August 1166.51 01-AUG-06:10 530.71 01-AUG-06:10 588.32 01-AUG-05:10 0.00 0.00 0.00 0.00 14.24 08-AUG-16:00 28.54 17-AUG-14:00
September 1166.51 01-SEP-06:10 530.71 01-SEP-06:10 588.32 01-SEP-05:10 0.00 0.00 0.00 0.00 5.97 07-SEP-15:00 25.27 20-SEP-06:02
October 1166.51 02-OCT-06:10 530.71 02-OCT-06:10 588.32 02-OCT-05:10 0.00 0.00 0.00 0.00 1.55 19-OCT-15:00 42.28 31-OCT-10:55
November 1166.51 01-NOV-06:10 530.71 01-NOV-06:10 588.32 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 59.91 22-NOV-02:00
December 1166.51 01-DEC-07:10 530.71 01-DEC-07:10 588.32 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 102.69 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 1166.51   530.71   588.32   0.00 0.00 0.00 0.00 0.00   11.35  
Maximum of Months 1166.51   530.71   588.32   0.00 0.00 0.00 0.00 22.53   112.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1555.35 02-JAN-07:10 707.62 02-JAN-07:10 784.42 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 149.82 04-JAN-11:53
February 1555.35 01-FEB-07:10 707.62 01-FEB-07:10 784.42 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 149.01 12-FEB-23:00
March 1555.35 01-MAR-07:10 707.62 01-MAR-07:10 784.42 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 81.72 14-MAR-15:00
April 1555.35 03-APR-06:10 707.62 03-APR-06:10 784.42 03-APR-05:10 0.00 0.00 0.00 0.00 25.98 23-APR-16:00 74.78 26-APR-15:00
May 1555.35 01-MAY-06:10 707.62 01-MAY-06:10 784.42 01-MAY-05:10 0.00 0.00 0.00 0.00 12.14 24-MAY-17:50 28.69 20-MAY-06:10
June 1555.35 01-JUN-06:10 707.62 01-JUN-06:10 784.42 01-JUN-05:10 0.00 0.00 0.00 0.00 25.24 29-JUN-16:00 30.49 09-JUN-09:00
July 1555.35 03-JUL-06:10 707.62 03-JUL-06:10 784.42 03-JUL-05:10 0.00 0.00 0.00 0.00 30.63 15-JUL-16:00 15.14 08-JUL-14:00
August 1555.35 01-AUG-06:10 707.62 01-AUG-06:10 784.42 01-AUG-05:10 0.00 0.00 0.00 0.00 18.98 08-AUG-16:00 38.05 17-AUG-14:00
September 1555.35 01-SEP-06:10 707.62 01-SEP-06:10 784.42 01-SEP-05:10 0.00 0.00 0.00 0.00 7.96 07-SEP-15:00 33.66 20-SEP-06:02
October 1555.35 02-OCT-06:10 707.62 02-OCT-06:10 784.42 02-OCT-05:10 0.00 0.00 0.00 0.00 2.07 19-OCT-15:00 56.38 31-OCT-10:55
November 1555.35 01-NOV-06:10 707.62 01-NOV-06:10 784.42 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 79.30 22-NOV-02:00
December 1555.35 01-DEC-07:10 707.62 01-DEC-07:10 784.42 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 136.92 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 1555.35   707.62   784.42   0.00 0.00 0.00 0.00 0.00   15.14  
Maximum of Months 1555.35   707.62   784.42   0.00 0.00 0.00 0.00 30.63   149.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 181.46 02-JAN-07:10 82.56 02-JAN-07:10 91.52 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 43.70 04-JAN-12:00
February 181.46 01-FEB-07:10 82.56 01-FEB-07:10 91.52 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 43.46 12-FEB-23:00
March 181.46 01-MAR-07:10 82.56 01-MAR-07:10 91.52 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 24.68 14-MAR-15:00
April 181.46 03-APR-06:10 82.56 03-APR-06:10 91.52 03-APR-05:10 0.00 0.00 0.00 0.00 6.32 23-APR-16:00 22.53 19-APR-10:00
May 181.46 01-MAY-06:10 82.56 01-MAY-06:10 91.52 01-MAY-05:10 0.00 0.00 0.00 0.00 2.77 24-MAY-17:40 8.37 20-MAY-06:10
June 181.46 01-JUN-06:10 82.56 01-JUN-06:10 91.52 01-JUN-05:10 0.00 0.00 0.00 0.00 6.85 29-JUN-16:00 8.89 09-JUN-09:00
July 181.46 03-JUL-06:10 82.56 03-JUL-06:10 91.52 03-JUL-05:10 0.00 0.00 0.00 0.00 7.59 15-JUL-16:00 4.42 08-JUL-14:00
August 181.46 01-AUG-06:10 82.56 01-AUG-06:10 91.52 01-AUG-05:10 0.00 0.00 0.00 0.00 4.92 08-AUG-16:00 11.35 17-AUG-14:00
September 181.46 01-SEP-06:10 82.56 01-SEP-06:10 91.52 01-SEP-05:10 0.00 0.00 0.00 0.00 1.40 07-SEP-15:00 9.76 20-SEP-06:02
October 181.46 02-OCT-06:10 82.56 02-OCT-06:10 91.52 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 16.44 31-OCT-10:55
November 181.46 01-NOV-06:10 82.56 01-NOV-06:10 91.52 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 23.17 22-NOV-02:00
December 181.46 01-DEC-07:10 82.56 01-DEC-07:10 91.52 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 39.93 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 181.46   82.56   91.52   0.00 0.00 0.00 0.00 0.00   4.42  
Maximum of Months 181.46   82.56   91.52   0.00 0.00 0.00 0.00 7.59   43.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 756.07 02-JAN-07:10 343.98 02-JAN-07:10 381.32 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 156.06 04-JAN-11:53
February 756.07 01-FEB-07:10 343.98 01-FEB-07:10 381.32 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 155.22 12-FEB-23:00
March 756.07 01-MAR-07:10 343.98 01-MAR-07:10 381.32 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 85.13 14-MAR-15:00
April 756.07 03-APR-06:10 343.98 03-APR-06:10 381.32 03-APR-05:10 0.00 0.00 0.00 0.00 25.84 23-APR-16:00 82.45 19-APR-10:00
May 756.07 01-MAY-06:10 343.98 01-MAY-06:10 381.32 01-MAY-05:10 0.00 0.00 0.00 0.00 10.92 24-MAY-17:40 29.92 20-MAY-06:05
June 756.07 01-JUN-06:10 343.98 01-JUN-06:10 381.32 01-JUN-05:10 0.00 0.00 0.00 0.00 25.45 29-JUN-16:00 31.96 09-JUN-09:00
July 756.07 03-JUL-06:10 343.98 03-JUL-06:10 381.32 03-JUL-05:10 0.00 0.00 0.00 0.00 27.99 15-JUL-16:00 15.77 08-JUL-14:00
August 756.07 01-AUG-06:10 343.98 01-AUG-06:10 381.32 01-AUG-05:10 0.00 0.00 0.00 0.00 18.89 08-AUG-16:00 40.62 17-AUG-14:00
September 756.07 01-SEP-06:10 343.98 01-SEP-06:10 381.32 01-SEP-05:10 0.00 0.00 0.00 0.00 7.72 07-SEP-15:00 35.20 20-SEP-06:02
October 756.07 02-OCT-06:10 343.98 02-OCT-06:10 381.32 02-OCT-05:10 0.00 0.00 0.00 0.00 2.16 19-OCT-15:00 58.73 31-OCT-10:55
November 756.07 01-NOV-06:10 343.98 01-NOV-06:10 381.32 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 82.76 22-NOV-02:00
December 756.07 01-DEC-07:10 343.98 01-DEC-07:10 381.32 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 142.62 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 756.07   343.98   381.32   0.00 0.00 0.00 0.00 0.00   15.77  
Maximum of Months 756.07   343.98   381.32   0.00 0.00 0.00 0.00 27.99   156.06  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 486.05 02-JAN-07:10 221.13 02-JAN-07:10 245.13 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 93.64 04-JAN-11:53
February 486.05 01-FEB-07:10 221.13 01-FEB-07:10 245.13 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 93.13 12-FEB-23:00
March 486.05 01-MAR-07:10 221.13 01-MAR-07:10 245.13 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 51.08 14-MAR-15:00
April 486.05 03-APR-06:10 221.13 03-APR-06:10 245.13 03-APR-05:10 0.00 0.00 0.00 0.00 16.24 23-APR-16:00 46.74 26-APR-15:00
May 486.05 01-MAY-06:10 221.13 01-MAY-06:10 245.13 01-MAY-05:10 0.00 0.00 0.00 0.00 7.21 24-MAY-17:10 17.93 20-MAY-06:10
June 486.05 01-JUN-06:10 221.13 01-JUN-06:10 245.13 01-JUN-05:10 0.00 0.00 0.00 0.00 15.78 29-JUN-16:00 19.06 09-JUN-09:00
July 486.05 03-JUL-06:10 221.13 03-JUL-06:10 245.13 03-JUL-05:10 0.00 0.00 0.00 0.00 17.86 15-JUL-16:00 9.46 08-JUL-14:00
August 486.05 01-AUG-06:10 221.13 01-AUG-06:10 245.13 01-AUG-05:10 0.00 0.00 0.00 0.00 11.86 08-AUG-16:00 23.78 17-AUG-14:00
September 486.05 01-SEP-06:10 221.13 01-SEP-06:10 245.13 01-SEP-05:10 0.00 0.00 0.00 0.00 4.97 07-SEP-15:00 21.05 20-SEP-06:02
October 486.05 02-OCT-06:10 221.13 02-OCT-06:10 245.13 02-OCT-05:10 0.00 0.00 0.00 0.00 1.29 19-OCT-15:00 35.24 31-OCT-10:55
November 486.05 01-NOV-06:10 221.13 01-NOV-06:10 245.13 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 49.34 22-NOV-02:00
December 486.05 01-DEC-07:10 221.13 01-DEC-07:10 245.13 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 85.57 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 486.05   221.13   245.13   0.00 0.00 0.00 0.00 0.00   9.46  
Maximum of Months 486.05   221.13   245.13   0.00 0.00 0.00 0.00 17.86   93.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1710.89 02-JAN-07:10 778.38 02-JAN-07:10 862.87 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 149.82 04-JAN-11:53
February 1710.89 01-FEB-07:10 778.38 01-FEB-07:10 862.87 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 149.01 12-FEB-23:00
March 1710.89 01-MAR-07:10 778.38 01-MAR-07:10 862.87 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 81.72 14-MAR-15:00
April 1710.89 03-APR-06:10 778.38 03-APR-06:10 862.87 03-APR-05:10 0.00 0.00 0.00 0.00 25.98 23-APR-16:00 74.78 26-APR-15:00
May 1710.89 01-MAY-06:10 778.38 01-MAY-06:10 862.87 01-MAY-05:10 0.00 0.00 0.00 0.00 12.34 24-MAY-17:50 28.69 20-MAY-06:10
June 1710.89 01-JUN-06:10 778.38 01-JUN-06:10 862.87 01-JUN-05:10 0.00 0.00 0.00 0.00 25.24 29-JUN-16:00 30.49 09-JUN-09:00
July 1710.89 03-JUL-06:10 778.38 03-JUL-06:10 862.87 03-JUL-05:10 0.00 0.00 0.00 0.00 30.67 15-JUL-16:00 15.14 08-JUL-14:00
August 1710.89 01-AUG-06:10 778.38 01-AUG-06:10 862.87 01-AUG-05:10 0.00 0.00 0.00 0.00 18.98 08-AUG-16:00 38.05 17-AUG-14:00
September 1710.89 01-SEP-06:10 778.38 01-SEP-06:10 862.87 01-SEP-05:10 0.00 0.00 0.00 0.00 7.95 07-SEP-15:00 33.71 20-SEP-06:02
October 1710.89 02-OCT-06:10 778.38 02-OCT-06:10 862.87 02-OCT-05:10 0.00 0.00 0.00 0.00 2.34 21-OCT-15:00 56.38 31-OCT-10:55
November 1710.89 01-NOV-06:10 778.38 01-NOV-06:10 862.87 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 80.15 22-NOV-02:00
December 1710.89 01-DEC-07:10 778.38 01-DEC-07:10 862.87 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 136.92 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 1710.89   778.38   862.87   0.00 0.00 0.00 0.00 0.00   15.14  
Maximum of Months 1710.89   778.38   862.87   0.00 0.00 0.00 0.00 30.67   149.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 583.26 02-JAN-07:10 265.36 02-JAN-07:10 294.16 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 112.37 04-JAN-11:53
February 583.26 01-FEB-07:10 265.36 01-FEB-07:10 294.16 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 111.76 12-FEB-23:00
March 583.26 01-MAR-07:10 265.36 01-MAR-07:10 294.16 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 61.29 14-MAR-15:00
April 583.26 03-APR-06:10 265.36 03-APR-06:10 294.16 03-APR-05:10 0.00 0.00 0.00 0.00 19.49 23-APR-16:00 56.08 26-APR-15:00
May 583.26 01-MAY-06:10 265.36 01-MAY-06:10 294.16 01-MAY-05:10 0.00 0.00 0.00 0.00 8.34 24-MAY-17:10 21.51 20-MAY-06:10
June 583.26 01-JUN-06:10 265.36 01-JUN-06:10 294.16 01-JUN-05:10 0.00 0.00 0.00 0.00 18.93 29-JUN-16:00 22.87 09-JUN-09:00
July 583.26 03-JUL-06:10 265.36 03-JUL-06:10 294.16 03-JUL-05:10 0.00 0.00 0.00 0.00 20.99 15-JUL-16:00 11.35 08-JUL-14:00
August 583.26 01-AUG-06:10 265.36 01-AUG-06:10 294.16 01-AUG-05:10 0.00 0.00 0.00 0.00 14.24 08-AUG-16:00 28.92 17-AUG-14:00
September 583.26 01-SEP-06:10 265.36 01-SEP-06:10 294.16 01-SEP-05:10 0.00 0.00 0.00 0.00 5.97 07-SEP-15:00 25.31 20-SEP-06:02
October 583.26 02-OCT-06:10 265.36 02-OCT-06:10 294.16 02-OCT-05:10 0.00 0.00 0.00 0.00 1.55 19-OCT-15:00 42.28 31-OCT-10:55
November 583.26 01-NOV-06:10 265.36 01-NOV-06:10 294.16 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 60.32 22-NOV-02:00
December 583.26 01-DEC-07:10 265.36 01-DEC-07:10 294.16 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 102.69 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 583.26   265.36   294.16   0.00 0.00 0.00 0.00 0.00   11.35  
Maximum of Months 583.26   265.36   294.16   0.00 0.00 0.00 0.00 20.99   112.37  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 855.44 02-JAN-07:10 389.19 02-JAN-07:10 431.43 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 74.91 04-JAN-11:53
February 855.44 01-FEB-07:10 389.19 01-FEB-07:10 431.43 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 74.51 12-FEB-23:00
March 855.44 01-MAR-07:10 389.19 01-MAR-07:10 431.43 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 40.86 14-MAR-15:00
April 855.44 03-APR-06:10 389.19 03-APR-06:10 431.43 03-APR-05:10 0.00 0.00 0.00 0.00 12.99 23-APR-16:00 37.39 26-APR-15:00
May 855.44 01-MAY-06:10 389.19 01-MAY-06:10 431.43 01-MAY-05:10 0.00 0.00 0.00 0.00 5.90 24-MAY-17:10 14.34 20-MAY-06:10
June 855.44 01-JUN-06:10 389.19 01-JUN-06:10 431.43 01-JUN-05:10 0.00 0.00 0.00 0.00 12.62 29-JUN-16:00 15.25 09-JUN-09:00
July 855.44 03-JUL-06:10 389.19 03-JUL-06:10 431.43 03-JUL-05:10 0.00 0.00 0.00 0.00 14.71 15-JUL-16:00 7.57 08-JUL-14:00
August 855.44 01-AUG-06:10 389.19 01-AUG-06:10 431.43 01-AUG-05:10 0.00 0.00 0.00 0.00 9.49 08-AUG-16:00 19.03 17-AUG-14:00
September 855.44 01-SEP-06:10 389.19 01-SEP-06:10 431.43 01-SEP-05:10 0.00 0.00 0.00 0.00 3.98 07-SEP-15:00 16.83 20-SEP-06:02
October 855.44 02-OCT-06:10 389.19 02-OCT-06:10 431.43 02-OCT-05:10 0.00 0.00 0.00 0.00 1.03 19-OCT-15:00 28.19 31-OCT-10:55
November 855.44 01-NOV-06:10 389.19 01-NOV-06:10 431.43 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 40.68 22-NOV-02:00
December 855.44 01-DEC-07:10 389.19 01-DEC-07:10 431.43 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 68.46 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 855.44   389.19   431.43   0.00 0.00 0.00 0.00 0.00   7.57  
Maximum of Months 855.44   389.19   431.43   0.00 0.00 0.00 0.00 14.71   74.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 129.61 02-JAN-07:10 42.48 02-JAN-07:10 237.70 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 129.61 01-FEB-07:10 42.48 01-FEB-07:10 237.70 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 129.61 01-MAR-07:10 42.48 01-MAR-07:10 237.70 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 129.61 03-APR-06:10 42.48 03-APR-06:10 237.70 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 129.61 01-MAY-06:10 42.48 01-MAY-06:10 237.70 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 129.61 01-JUN-06:10 42.48 01-JUN-06:10 237.70 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 129.61 03-JUL-06:10 42.48 03-JUL-06:10 237.70 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 129.61 01-AUG-06:10 42.48 01-AUG-06:10 237.70 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 129.61 01-SEP-06:10 42.48 01-SEP-06:10 237.70 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 129.61 02-OCT-06:10 42.48 02-OCT-06:10 237.70 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 129.61 01-NOV-06:10 42.48 01-NOV-06:10 237.70 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 129.61 01-DEC-07:10 42.48 01-DEC-07:10 237.70 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 129.61   42.48   237.70   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 129.61   42.48   237.70   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 324.03 02-JAN-07:10 157.95 02-JAN-07:10 297.17 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 324.03 01-FEB-07:10 157.95 01-FEB-07:10 297.17 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 324.03 01-MAR-07:10 157.95 01-MAR-07:10 297.17 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 324.03 03-APR-06:10 157.95 03-APR-06:10 297.17 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 324.03 01-MAY-06:10 157.95 01-MAY-06:10 297.17 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 324.03 01-JUN-06:10 157.95 01-JUN-06:10 297.17 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 324.03 03-JUL-06:10 157.95 03-JUL-06:10 297.17 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 324.03 01-AUG-06:10 157.95 01-AUG-06:10 297.17 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 324.03 01-SEP-06:10 157.95 01-SEP-06:10 297.17 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 324.03 02-OCT-06:10 157.95 02-OCT-06:10 297.17 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 324.03 01-NOV-06:10 157.95 01-NOV-06:10 297.17 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 324.03 01-DEC-07:10 157.95 01-DEC-07:10 297.17 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 324.03   157.95   297.17   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 324.03   157.95   297.17   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 388.84 02-JAN-07:10 189.54 02-JAN-07:10 356.60 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 388.84 01-FEB-07:10 189.54 01-FEB-07:10 356.60 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 388.84 01-MAR-07:10 189.54 01-MAR-07:10 356.60 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 388.84 03-APR-06:10 189.54 03-APR-06:10 356.60 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 388.84 01-MAY-06:10 189.54 01-MAY-06:10 356.60 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 388.84 01-JUN-06:10 189.54 01-JUN-06:10 356.60 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 388.84 03-JUL-06:10 189.54 03-JUL-06:10 356.60 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 388.84 01-AUG-06:10 189.54 01-AUG-06:10 356.60 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 388.84 01-SEP-06:10 189.54 01-SEP-06:10 356.60 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 388.84 02-OCT-06:10 189.54 02-OCT-06:10 356.60 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 388.84 01-NOV-06:10 189.54 01-NOV-06:10 356.60 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 388.84 01-DEC-07:10 189.54 01-DEC-07:10 356.60 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 388.84   189.54   356.60   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 388.84   189.54   356.60   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 302.43 02-JAN-07:10 320.41 02-JAN-07:10 610.11 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 249.70 04-JAN-11:53
February 302.43 01-FEB-07:10 320.41 01-FEB-07:10 610.11 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 248.35 12-FEB-23:00
March 302.43 01-MAR-07:10 320.41 01-MAR-17:00 610.11 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 138.04 14-MAR-15:50
April 302.43 03-APR-06:10 275.96 03-APR-06:10 610.11 03-APR-05:10 0.00 0.00 0.00 0.00 24.82 23-APR-16:00 131.93 19-APR-10:00
May 302.43 01-MAY-06:10 181.36 25-MAY-05:10 610.11 01-MAY-05:10 0.00 0.00 0.00 0.00 14.74 24-MAY-15:00 49.60 09-MAY-08:70
June 302.43 01-JUN-06:10 214.82 30-JUN-06:10 610.11 01-JUN-05:10 0.00 0.00 0.00 0.00 38.73 29-JUN-16:00 56.40 09-JUN-09:00
July 302.43 03-JUL-06:10 201.48 25-JUL-05:10 610.11 03-JUL-05:10 0.00 0.00 0.00 0.00 31.97 15-JUL-15:00 29.07 08-JUL-14:00
August 302.43 01-AUG-06:10 286.43 31-AUG-06:10 610.11 01-AUG-05:10 0.00 0.00 0.00 0.00 27.97 08-AUG-16:00 70.05 17-AUG-14:00
September 302.43 01-SEP-06:10 320.41 27-SEP-06:10 610.11 01-SEP-05:10 0.00 0.00 0.00 0.00 8.01 07-SEP-15:00 58.14 20-SEP-06:00
October 302.43 02-OCT-06:10 320.41 02-OCT-06:10 610.11 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 96.63 31-OCT-10:55
November 302.43 01-NOV-06:10 320.41 01-NOV-06:10 610.11 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 141.51 22-NOV-02:00
December 302.43 01-DEC-07:10 320.41 01-DEC-07:10 610.11 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 228.20 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 302.43   181.36   610.11   0.00 0.00 0.00 0.00 0.00   29.07  
Maximum of Months 302.43   320.41   610.11   0.00 0.00 0.00 0.00 38.73   249.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 3188.47 02-JAN-07:10 743.90 02-JAN-07:10 1072.05 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 305.91 04-JAN-11:57
February 3188.47 01-FEB-07:10 743.90 01-FEB-07:10 1072.05 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 304.23 12-FEB-23:00
March 3188.47 01-MAR-07:10 743.90 01-MAR-17:00 1072.05 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 172.74 14-MAR-15:00
April 3188.47 03-APR-06:10 703.67 03-APR-06:10 1072.05 03-APR-05:10 0.00 0.00 0.00 0.00 28.21 23-APR-16:00 161.60 19-APR-10:00
May 3188.47 01-MAY-06:10 542.05 22-MAY-06:10 1072.05 01-MAY-05:10 0.00 0.00 0.00 0.00 18.06 24-MAY-15:00 60.75 09-MAY-08:20
June 3188.47 01-JUN-06:10 636.79 30-JUN-06:10 1072.05 01-JUN-05:10 0.00 0.00 0.00 0.00 47.45 29-JUN-16:00 69.08 09-JUN-09:00
July 3188.47 03-JUL-06:10 580.64 03-JUL-06:10 1072.05 03-JUL-05:10 0.00 0.00 0.00 0.00 41.75 15-JUL-15:40 35.61 08-JUL-14:00
August 3188.47 01-AUG-06:10 705.57 31-AUG-06:10 1072.05 01-AUG-05:10 0.00 0.00 0.00 0.00 34.27 08-AUG-16:00 85.80 17-AUG-14:00
September 3188.47 01-SEP-06:10 743.90 27-SEP-06:10 1072.05 01-SEP-05:10 0.00 0.00 0.00 0.00 9.82 07-SEP-15:00 74.37 20-SEP-06:00
October 3188.47 02-OCT-06:10 743.90 02-OCT-06:10 1072.05 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 121.79 31-OCT-10:55
November 3188.47 01-NOV-06:10 743.90 01-NOV-06:10 1072.05 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 175.34 22-NOV-02:00
December 3188.47 01-DEC-07:10 743.90 01-DEC-07:10 1072.05 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 281.36 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 3188.47   542.05   1072.05   0.00 0.00 0.00 0.00 0.00   35.61  
Maximum of Months 3188.47   743.90   1072.05   0.00 0.00 0.00 0.00 47.45   305.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 174.98 02-JAN-07:10 185.38 02-JAN-07:10 352.99 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 174.98 01-FEB-07:10 185.38 01-FEB-07:10 352.99 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 174.98 01-MAR-07:10 185.38 01-MAR-07:10 352.99 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 174.98 03-APR-06:10 185.38 03-APR-06:10 352.99 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 174.98 01-MAY-06:10 185.38 01-MAY-06:10 352.99 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 174.98 01-JUN-06:10 185.38 01-JUN-06:10 352.99 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 174.98 03-JUL-06:10 185.38 03-JUL-06:10 352.99 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 174.98 01-AUG-06:10 185.38 01-AUG-06:10 352.99 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 174.98 01-SEP-06:10 185.38 01-SEP-06:10 352.99 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 174.98 02-OCT-06:10 185.38 02-OCT-06:10 352.99 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 174.98 01-NOV-06:10 185.38 01-NOV-06:10 352.99 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 174.98 01-DEC-07:10 185.38 01-DEC-07:10 352.99 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 174.98   185.38   352.99   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 174.98   185.38   352.99   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 184.70 02-JAN-07:10 195.68 02-JAN-07:10 372.60 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 184.70 01-FEB-07:10 195.68 01-FEB-07:10 372.60 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 184.70 01-MAR-07:10 195.68 01-MAR-07:10 372.60 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 184.70 03-APR-06:10 195.68 03-APR-06:10 372.60 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 184.70 01-MAY-06:10 195.68 01-MAY-06:10 372.60 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 184.70 01-JUN-06:10 195.68 01-JUN-06:10 372.60 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 184.70 03-JUL-06:10 195.68 03-JUL-06:10 372.60 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 184.70 01-AUG-06:10 195.68 01-AUG-06:10 372.60 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 184.70 01-SEP-06:10 195.68 01-SEP-06:10 372.60 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 184.70 02-OCT-06:10 195.68 02-OCT-06:10 372.60 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 184.70 01-NOV-06:10 195.68 01-NOV-06:10 372.60 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 184.70 01-DEC-07:10 195.68 01-DEC-07:10 372.60 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 184.70   195.68   372.60   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 184.70   195.68   372.60   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 912.69 02-JAN-07:10 966.95 02-JAN-07:10 1520.91 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 162.30 04-JAN-12:00
February 912.69 01-FEB-07:10 966.95 01-FEB-07:10 1520.91 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 167.81 12-FEB-23:00
March 912.69 01-MAR-07:10 966.95 01-MAR-07:10 1520.91 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 91.66 14-MAR-15:00
April 912.69 03-APR-06:10 966.95 03-APR-06:10 1520.91 03-APR-05:10 0.00 0.00 0.00 0.00 17.52 23-APR-16:00 85.75 19-APR-10:00
May 912.69 01-MAY-06:10 966.95 01-MAY-06:10 1520.91 01-MAY-05:10 0.00 0.00 0.00 0.00 9.58 24-MAY-15:00 33.76 20-MAY-06:00
June 912.69 01-JUN-06:10 966.95 01-JUN-06:10 1520.91 01-JUN-05:10 0.00 0.00 0.00 0.00 25.18 29-JUN-16:00 36.66 09-JUN-09:00
July 912.69 03-JUL-06:10 966.95 03-JUL-06:10 1520.91 03-JUL-05:10 0.00 0.00 0.00 0.00 21.63 15-JUL-15:00 18.90 08-JUL-14:00
August 912.69 01-AUG-06:10 966.95 01-AUG-06:10 1520.91 01-AUG-05:10 0.00 0.00 0.00 0.00 18.18 08-AUG-16:00 45.53 17-AUG-14:00
September 912.69 01-SEP-06:10 966.95 01-SEP-06:10 1520.91 01-SEP-05:10 0.00 0.00 0.00 0.00 5.21 07-SEP-15:00 40.88 20-SEP-06:00
October 912.69 02-OCT-06:10 966.95 02-OCT-06:10 1520.91 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 64.63 31-OCT-10:55
November 912.69 01-NOV-06:10 966.95 01-NOV-06:10 1520.91 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 99.32 22-NOV-02:00
December 912.69 01-DEC-07:10 966.95 01-DEC-07:10 1520.91 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 148.35 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 912.69   966.95   1520.91   0.00 0.00 0.00 0.00 0.00   18.90  
Maximum of Months 912.69   966.95   1520.91   0.00 0.00 0.00 0.00 25.18   167.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 X-RAY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1944.19 02-JAN-07:10 593.89 02-JAN-07:10 8914.22 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 1944.19 01-FEB-07:10 593.89 01-FEB-07:10 8914.22 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 1944.19 01-MAR-07:10 593.89 01-MAR-07:10 8914.22 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 1944.19 03-APR-06:10 593.89 03-APR-06:10 8914.22 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 1944.19 01-MAY-06:10 593.89 01-MAY-06:10 8914.22 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 1944.19 01-JUN-06:10 593.89 01-JUN-06:10 8914.22 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 1944.19 03-JUL-06:10 593.89 03-JUL-06:10 8914.22 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 1944.19 01-AUG-06:10 593.89 01-AUG-06:10 8914.22 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 1944.19 01-SEP-06:10 593.89 01-SEP-06:10 8914.22 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 1944.19 02-OCT-06:10 593.89 02-OCT-06:10 8914.22 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 1944.19 01-NOV-06:10 593.89 01-NOV-06:10 8914.22 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 1944.19 01-DEC-07:10 593.89 01-DEC-07:10 8914.22 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average                        
Minimum of Months 1944.19   593.89   8914.22   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1944.19   593.89   8914.22   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 22.68 02-JAN-07:10 24.03 02-JAN-07:10 45.76 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 31.05 04-JAN-12:00
February 22.68 01-FEB-07:10 24.03 01-FEB-07:10 45.76 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 31.11 12-FEB-23:00
March 22.68 01-MAR-07:10 24.03 01-MAR-07:10 45.76 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 17.54 14-MAR-15:00
April 22.68 03-APR-06:10 24.03 03-APR-06:10 45.76 03-APR-05:10 0.00 0.00 0.00 0.00 3.59 23-APR-16:00 16.41 19-APR-10:00
May 22.68 01-MAY-06:10 24.03 01-MAY-06:10 45.76 01-MAY-05:10 0.00 0.00 0.00 0.00 1.83 24-MAY-15:00 6.17 09-MAY-08:70
June 22.68 01-JUN-06:10 24.03 01-JUN-06:10 45.76 01-JUN-05:10 0.00 0.00 0.00 0.00 4.81 29-JUN-16:00 7.02 09-JUN-09:00
July 22.68 03-JUL-06:10 24.03 03-JUL-06:10 45.76 03-JUL-05:10 0.00 0.00 0.00 0.00 4.23 15-JUL-15:10 3.62 08-JUL-14:00
August 22.68 01-AUG-06:10 24.03 01-AUG-06:10 45.76 01-AUG-05:10 0.00 0.00 0.00 0.00 3.47 08-AUG-16:00 8.72 17-AUG-14:00
September 22.68 01-SEP-06:10 24.03 01-SEP-06:10 45.76 01-SEP-05:10 0.00 0.00 0.00 0.00 0.98 07-SEP-15:00 7.28 20-SEP-06:00
October 22.68 02-OCT-06:10 24.03 02-OCT-06:10 45.76 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 12.37 31-OCT-10:55
November 22.68 01-NOV-06:10 24.03 01-NOV-06:10 45.76 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 18.21 22-NOV-02:00
December 22.68 01-DEC-07:10 24.03 01-DEC-07:10 45.76 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 28.37 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 22.68   24.03   45.76   0.00 0.00 0.00 0.00 0.00   3.62  
Maximum of Months 22.68   24.03   45.76   0.00 0.00 0.00 0.00 4.81   31.11  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 58.33 02-JAN-07:10 61.79 02-JAN-07:10 117.66 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 79.84 04-JAN-12:00
February 58.33 01-FEB-07:10 61.79 01-FEB-07:10 117.66 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 80.04 12-FEB-23:00
March 58.33 01-MAR-07:10 61.79 01-MAR-07:10 117.66 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 45.10 14-MAR-15:00
April 58.33 03-APR-06:10 61.79 03-APR-06:10 117.66 03-APR-05:10 0.00 0.00 0.00 0.00 8.82 23-APR-16:00 42.21 19-APR-10:00
May 58.33 01-MAY-06:10 61.79 01-MAY-06:10 117.66 01-MAY-05:10 0.00 0.00 0.00 0.00 4.69 24-MAY-15:00 15.87 09-MAY-08:70
June 58.33 01-JUN-06:10 61.79 01-JUN-06:10 117.66 01-JUN-05:10 0.00 0.00 0.00 0.00 12.36 29-JUN-16:00 18.06 09-JUN-09:00
July 58.33 03-JUL-06:10 61.79 03-JUL-06:10 117.66 03-JUL-05:10 0.00 0.00 0.00 0.00 10.62 15-JUL-15:10 9.31 08-JUL-14:00
August 58.33 01-AUG-06:10 61.79 01-AUG-06:10 117.66 01-AUG-05:10 0.00 0.00 0.00 0.00 8.92 08-AUG-16:00 22.43 17-AUG-14:00
September 58.33 01-SEP-06:10 61.79 01-SEP-06:10 117.66 01-SEP-05:10 0.00 0.00 0.00 0.00 2.53 07-SEP-15:00 19.14 20-SEP-06:00
October 58.33 02-OCT-06:10 61.79 02-OCT-06:10 117.66 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 31.81 31-OCT-10:55
November 58.33 01-NOV-06:10 61.79 01-NOV-06:10 117.66 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 47.17 22-NOV-02:00
December 58.33 01-DEC-07:10 61.79 01-DEC-07:10 117.66 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 73.05 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 58.33   61.79   117.66   0.00 0.00 0.00 0.00 0.00   9.31  
Maximum of Months 58.33   61.79   117.66   0.00 0.00 0.00 0.00 12.36   80.04  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 LOCKER

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 194.42 02-JAN-07:10 63.72 02-JAN-07:10 356.55 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 90.04 04-JAN-11:57
February 194.42 01-FEB-07:10 63.72 01-FEB-07:10 356.55 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 88.24 12-FEB-23:00
March 194.42 01-MAR-07:10 63.72 01-MAR-07:10 356.55 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 50.11 14-MAR-15:00
April 194.42 03-APR-06:10 63.72 03-APR-06:10 356.55 03-APR-05:10 0.00 0.00 0.00 0.00 8.81 23-APR-16:10 46.90 19-APR-10:00
May 194.42 01-MAY-06:10 63.72 01-MAY-06:10 356.55 01-MAY-05:10 0.00 0.00 0.00 0.00 5.22 24-MAY-15:00 18.41 09-MAY-05:40
June 194.42 01-JUN-06:10 63.72 01-JUN-06:10 356.55 01-JUN-05:10 0.00 0.00 0.00 0.00 13.73 29-JUN-16:00 20.06 09-JUN-09:00
July 194.42 03-JUL-06:10 63.72 03-JUL-06:10 356.55 03-JUL-05:10 0.00 0.00 0.00 0.00 11.19 15-JUL-14:01 10.58 08-JUL-14:10
August 194.42 01-AUG-06:10 63.72 01-AUG-06:10 356.55 01-AUG-05:10 0.00 0.00 0.00 0.00 9.91 08-AUG-16:00 24.92 17-AUG-14:00
September 194.42 01-SEP-06:10 63.72 01-SEP-06:10 356.55 01-SEP-05:10 0.00 0.00 0.00 0.00 2.81 07-SEP-15:00 22.55 20-SEP-06:00
October 194.42 02-OCT-06:10 63.72 02-OCT-06:10 356.55 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 35.34 31-OCT-10:55
November 194.42 01-NOV-06:10 63.72 01-NOV-06:10 356.55 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 52.21 22-NOV-02:00
December 194.42 01-DEC-07:10 63.72 01-DEC-07:10 356.55 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 83.10 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 194.42   63.72   356.55   0.00 0.00 0.00 0.00 0.00   10.58  
Maximum of Months 194.42   63.72   356.55   0.00 0.00 0.00 0.00 13.73   90.04  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1229.70 02-JAN-07:10 403.03 02-JAN-07:10 2255.16 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 4.76 04-JAN-12:00
February 1229.70 01-FEB-07:10 403.03 01-FEB-07:10 2255.16 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 4.71 12-FEB-23:00
March 1229.70 01-MAR-07:10 403.03 01-MAR-17:00 2255.16 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2.63 14-MAR-15:00
April 1229.70 03-APR-06:10 358.53 03-APR-06:10 2255.16 03-APR-05:10 0.00 0.00 0.00 0.00 0.41 23-APR-16:10 2.49 04-APR-18:00
May 1229.70 01-MAY-06:10 241.36 22-MAY-06:10 2255.16 01-MAY-05:10 0.00 0.00 0.00 0.00 0.27 24-MAY-15:00 0.97 09-MAY-05:09
June 1229.70 01-JUN-06:10 277.05 30-JUN-06:10 2255.16 01-JUN-05:10 0.00 0.00 0.00 0.00 0.72 29-JUN-16:00 1.05 09-JUN-09:00
July 1229.70 03-JUL-06:10 256.58 11-JUL-16:00 2255.16 03-JUL-05:10 0.00 0.00 0.00 0.00 0.59 15-JUL-14:01 0.57 08-JUL-14:10
August 1229.70 01-AUG-06:10 364.71 31-AUG-06:10 2255.16 01-AUG-05:10 0.00 0.00 0.00 0.00 0.52 08-AUG-16:00 1.31 17-AUG-14:00
September 1229.70 01-SEP-06:10 403.03 27-SEP-06:10 2255.16 01-SEP-05:10 0.00 0.00 0.00 0.00 0.15 07-SEP-15:00 1.18 20-SEP-06:00
October 1229.70 02-OCT-06:10 403.03 02-OCT-06:10 2255.16 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 1.86 31-OCT-10:55
November 1229.70 01-NOV-06:10 403.03 01-NOV-06:10 2255.16 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2.80 22-NOV-02:00
December 1229.70 01-DEC-07:10 403.03 01-DEC-07:10 2255.16 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 4.36 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 1229.70   241.36   2255.16   0.00 0.00 0.00 0.00 0.00   0.57  
Maximum of Months 1229.70   403.03   2255.16   0.00 0.00 0.00 0.00 0.72   4.76  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1639.60 02-JAN-07:10 1737.08 02-JAN-07:10 3307.66 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 12.09 04-JAN-12:00
February 1639.60 01-FEB-07:10 1737.08 01-FEB-07:10 3307.66 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 12.03 12-FEB-23:00
March 1639.60 01-MAR-07:10 1737.08 01-MAR-17:00 3307.66 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 6.83 14-MAR-15:00
April 1639.60 03-APR-06:10 1653.49 03-APR-06:10 3307.66 03-APR-05:10 0.00 0.00 0.00 0.00 1.26 23-APR-16:00 6.39 19-APR-10:00
May 1639.60 01-MAY-06:10 1284.93 22-MAY-06:10 3307.66 01-MAY-05:10 0.00 0.00 0.00 0.00 0.71 24-MAY-15:00 2.40 09-MAY-08:70
June 1639.60 01-JUN-06:10 1519.92 30-JUN-06:10 3307.66 01-JUN-05:10 0.00 0.00 0.00 0.00 1.87 29-JUN-16:00 2.73 09-JUN-09:00
July 1639.60 03-JUL-06:10 1315.05 11-JUL-16:00 3307.66 03-JUL-05:10 0.00 0.00 0.00 0.00 1.53 15-JUL-14:01 1.41 08-JUL-14:00
August 1639.60 01-AUG-06:10 1664.52 31-AUG-06:10 3307.66 01-AUG-05:10 0.00 0.00 0.00 0.00 1.35 08-AUG-16:00 3.40 17-AUG-14:00
September 1639.60 01-SEP-06:10 1737.08 27-SEP-06:10 3307.66 01-SEP-05:10 0.00 0.00 0.00 0.00 0.38 07-SEP-15:00 2.97 20-SEP-06:00
October 1639.60 02-OCT-06:10 1737.08 02-OCT-06:10 3307.66 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 4.82 31-OCT-10:55
November 1639.60 01-NOV-06:10 1737.08 01-NOV-06:10 3307.66 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 7.11 22-NOV-02:00
December 1639.60 01-DEC-07:10 1737.08 01-DEC-07:10 3307.66 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 11.05 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 1639.60   1284.93   3307.66   0.00 0.00 0.00 0.00 0.00   1.41  
Maximum of Months 1639.60   1737.08   3307.66   0.00 0.00 0.00 0.00 1.87   12.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2808.27 02-JAN-07:10 830.47 02-JAN-07:10 1931.89 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 36.00 04-JAN-12:00
February 2808.27 01-FEB-07:10 830.47 01-FEB-07:10 1931.89 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 35.82 12-FEB-23:00
March 2808.27 01-MAR-07:10 830.47 01-MAR-07:10 1931.89 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 20.34 14-MAR-15:00
April 2808.27 03-APR-06:10 830.47 03-APR-06:10 1931.89 03-APR-05:10 0.00 0.00 0.00 0.00 5.67 23-APR-16:00 19.03 19-APR-10:00
May 2808.27 01-MAY-06:10 830.47 01-MAY-06:10 1931.89 01-MAY-05:10 0.00 0.00 0.00 0.00 2.38 24-MAY-18:00 6.90 20-MAY-06:10
June 2808.27 01-JUN-06:10 830.47 01-JUN-06:10 1931.89 01-JUN-05:10 0.00 0.00 0.00 0.00 5.57 29-JUN-16:00 7.34 09-JUN-09:00
July 2808.27 03-JUL-06:10 830.47 03-JUL-06:10 1931.89 03-JUL-05:10 0.00 0.00 0.00 0.00 6.49 15-JUL-16:00 3.65 08-JUL-14:00
August 2808.27 01-AUG-06:10 830.47 01-AUG-06:10 1931.89 01-AUG-05:10 0.00 0.00 0.00 0.00 4.02 08-AUG-16:00 9.61 17-AUG-14:00
September 2808.27 01-SEP-06:10 830.47 01-SEP-06:10 1931.89 01-SEP-05:10 0.00 0.00 0.00 0.00 1.38 03-SEP-16:10 8.10 20-SEP-06:03
October 2808.27 02-OCT-06:10 830.47 02-OCT-06:10 1931.89 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 13.56 31-OCT-10:55
November 2808.27 01-NOV-06:10 830.47 01-NOV-06:10 1931.89 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 18.85 22-NOV-02:00
December 2808.27 01-DEC-07:10 830.47 01-DEC-07:10 1931.89 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 32.91 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 2808.27   830.47   1931.89   0.00 0.00 0.00 0.00 0.00   3.65  
Maximum of Months 2808.27   830.47   1931.89   0.00 0.00 0.00 0.00 6.49   36.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1278.84 02-JAN-07:10 378.18 02-JAN-07:10 879.75 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 437.62 04-JAN-11:53
February 1278.84 01-FEB-07:10 378.18 01-FEB-07:10 879.75 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 435.32 12-FEB-23:00
March 1278.84 01-MAR-07:10 378.18 01-MAR-07:10 879.75 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 239.97 14-MAR-16:00
April 1278.84 03-APR-06:10 378.18 03-APR-06:10 879.75 03-APR-05:10 0.00 0.00 0.00 0.00 75.69 23-APR-16:00 221.56 19-APR-10:00
May 1278.84 01-MAY-06:10 378.18 01-MAY-06:10 879.75 01-MAY-05:10 0.00 0.00 0.00 0.00 32.08 24-MAY-18:00 83.86 20-MAY-06:10
June 1278.84 01-JUN-06:10 378.18 01-JUN-06:10 879.75 01-JUN-05:10 0.00 0.00 0.00 0.00 72.11 29-JUN-16:00 89.61 09-JUN-09:00
July 1278.84 03-JUL-06:10 378.18 03-JUL-06:10 879.75 03-JUL-05:10 0.00 0.00 0.00 0.00 83.97 15-JUL-16:00 44.32 08-JUL-14:00
August 1278.84 01-AUG-06:10 378.18 01-AUG-06:10 879.75 01-AUG-05:10 0.00 0.00 0.00 0.00 54.38 08-AUG-16:00 115.52 17-AUG-14:00
September 1278.84 01-SEP-06:10 378.18 01-SEP-06:10 879.75 01-SEP-05:10 0.00 0.00 0.00 0.00 22.74 07-SEP-15:00 98.94 20-SEP-06:03
October 1278.84 02-OCT-06:10 378.18 02-OCT-06:10 879.75 02-OCT-05:10 0.00 0.00 0.00 0.00 5.69 19-OCT-15:00 164.78 31-OCT-10:55
November 1278.84 01-NOV-06:10 378.18 01-NOV-06:10 879.75 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 229.32 22-NOV-02:00
December 1278.84 01-DEC-07:10 378.18 01-DEC-07:10 879.75 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 399.95 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 1278.84   378.18   879.75   0.00 0.00 0.00 0.00 0.00   44.32  
Maximum of Months 1278.84   378.18   879.75   0.00 0.00 0.00 0.00 83.97   437.62  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1028.26 02-JAN-07:10 599.76 02-JAN-07:10 518.59 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 351.87 04-JAN-11:53
February 1028.26 01-FEB-07:10 599.76 01-FEB-07:10 518.59 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 350.02 12-FEB-23:00
March 1028.26 01-MAR-07:10 599.76 01-MAR-07:10 518.59 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 195.11 14-MAR-16:00
April 1028.26 03-APR-06:10 599.76 03-APR-06:10 518.59 03-APR-05:10 0.00 0.00 0.00 0.00 59.79 23-APR-16:00 180.15 19-APR-10:00
May 1028.26 01-MAY-06:10 599.76 01-MAY-06:10 518.59 01-MAY-05:10 0.00 0.00 0.00 0.00 23.84 24-MAY-17:50 67.57 20-MAY-06:05
June 1028.26 01-JUN-06:10 599.76 01-JUN-06:10 518.59 01-JUN-05:10 0.00 0.00 0.00 0.00 56.43 29-JUN-16:00 74.54 09-JUN-09:00
July 1028.26 03-JUL-06:10 599.76 03-JUL-06:10 518.59 03-JUL-05:10 0.00 0.00 0.00 0.00 65.19 15-JUL-16:00 35.63 08-JUL-14:00
August 1028.26 01-AUG-06:10 599.76 01-AUG-06:10 518.59 01-AUG-05:10 0.00 0.00 0.00 0.00 42.05 08-AUG-16:00 95.83 17-AUG-14:00
September 1028.26 01-SEP-06:10 599.76 01-SEP-06:10 518.59 01-SEP-05:10 0.00 0.00 0.00 0.00 16.24 03-SEP-15:00 79.08 20-SEP-06:03
October 1028.26 02-OCT-06:10 599.76 02-OCT-06:10 518.59 02-OCT-05:10 0.00 0.00 0.00 0.00 2.97 22-OCT-15:00 134.01 31-OCT-11:00
November 1028.26 01-NOV-06:10 599.76 01-NOV-06:10 518.59 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 188.63 22-NOV-02:00
December 1028.26 01-DEC-07:10 599.76 01-DEC-07:10 518.59 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 321.58 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 1028.26   599.76   518.59   0.00 0.00 0.00 0.00 0.00   35.63  
Maximum of Months 1028.26   599.76   518.59   0.00 0.00 0.00 0.00 65.19   351.87  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 309.99 02-JAN-07:10 328.42 02-JAN-07:10 625.36 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 18.85 04-JAN-11:53
February 309.99 01-FEB-07:10 328.42 01-FEB-07:10 625.36 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 18.75 12-FEB-23:00
March 309.99 01-MAR-07:10 328.42 01-MAR-07:10 625.36 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 10.65 14-MAR-15:00
April 309.99 03-APR-06:10 328.42 03-APR-06:10 625.36 03-APR-05:10 0.00 0.00 0.00 0.00 1.50 23-APR-16:00 9.97 19-APR-10:00
May 309.99 01-MAY-06:10 328.42 01-MAY-06:10 625.36 01-MAY-05:10 0.00 0.00 0.00 0.00 1.11 24-MAY-15:00 3.75 09-MAY-08:70
June 309.99 01-JUN-06:10 328.42 01-JUN-06:10 625.36 01-JUN-05:10 0.00 0.00 0.00 0.00 2.92 29-JUN-16:00 4.26 09-JUN-09:00
July 309.99 03-JUL-06:10 328.42 03-JUL-06:10 625.36 03-JUL-05:10 0.00 0.00 0.00 0.00 2.37 15-JUL-14:01 2.20 08-JUL-14:00
August 309.99 01-AUG-06:10 328.42 01-AUG-06:10 625.36 01-AUG-05:10 0.00 0.00 0.00 0.00 2.11 08-AUG-16:00 5.30 17-AUG-14:00
September 309.99 01-SEP-06:10 328.42 01-SEP-06:10 625.36 01-SEP-05:10 0.00 0.00 0.00 0.00 0.60 07-SEP-15:00 4.46 20-SEP-06:00
October 309.99 02-OCT-06:10 328.42 02-OCT-06:10 625.36 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 7.51 31-OCT-10:55
November 309.99 01-NOV-06:10 328.42 01-NOV-06:10 625.36 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 10.68 22-NOV-02:00
December 309.99 01-DEC-07:10 328.42 01-DEC-07:10 625.36 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 17.23 18-DEC-15:00
                             
Annual Sum or Average                            
Minimum of Months 309.99   328.42   625.36   0.00 0.00 0.00 0.00 0.00   2.20  
Maximum of Months 309.99   328.42   625.36   0.00 0.00 0.00 0.00 2.92   18.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 12.86 02-JAN-07:10 5.57 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 12.86 01-FEB-07:10 5.57 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 12.86 01-MAR-07:10 5.57 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 12.86 03-APR-06:10 5.57 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 12.86 01-MAY-06:10 5.57 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 12.86 01-JUN-06:10 5.57 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 12.86 03-JUL-06:10 5.57 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 12.86 01-AUG-06:10 5.57 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 12.86 01-SEP-06:10 5.57 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 12.86 02-OCT-06:10 5.57 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 12.86 01-NOV-06:10 5.57 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 12.86 01-DEC-07:10 5.57 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 12.86   5.57   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 12.86   5.57   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 123.48 02-JAN-07:10 485.33 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 31.07 04-JAN-11:53
February 0.00 123.48 01-FEB-07:10 485.33 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 31.86 12-FEB-23:00
March 0.00 123.48 01-MAR-07:10 485.33 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 17.16 14-MAR-15:00
April 0.00 123.48 03-APR-06:10 485.33 03-APR-05:10 0.00 0.00 0.00 0.00 3.36 23-APR-16:10 16.05 19-APR-10:00
May 0.00 123.48 01-MAY-06:10 485.33 01-MAY-05:10 0.00 0.00 0.00 0.00 1.80 24-MAY-15:00 6.21 09-MAY-05:10
June 0.00 123.48 01-JUN-06:10 485.33 01-JUN-05:10 0.00 0.00 0.00 0.00 4.72 29-JUN-16:00 6.86 09-JUN-09:00
July 0.00 123.48 03-JUL-06:10 485.33 03-JUL-05:10 0.00 0.00 0.00 0.00 3.92 15-JUL-15:00 3.53 08-JUL-14:00
August 0.00 123.48 01-AUG-06:10 485.33 01-AUG-05:10 0.00 0.00 0.00 0.00 3.41 08-AUG-16:00 8.52 17-AUG-14:00
September 0.00 123.48 01-SEP-06:10 485.33 01-SEP-05:10 0.00 0.00 0.00 0.00 0.99 07-SEP-15:00 7.72 20-SEP-06:00
October 0.00 123.48 02-OCT-06:10 485.33 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 12.10 31-OCT-10:55
November 0.00 123.48 01-NOV-06:10 485.33 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 18.16 22-NOV-02:00
December 0.00 123.48 01-DEC-07:10 485.33 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 28.47 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 123.48   485.33   0.00 0.00 0.00 0.00 0.00   3.53  
Maximum of Months 0.00 123.48   485.33   0.00 0.00 0.00 0.00 4.72   31.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 114.66 02-JAN-07:10 4835.28 02-JAN-09:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 88.77 04-JAN-11:53
February 0.00 114.66 01-FEB-07:10 4835.28 01-FEB-09:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 89.31 12-FEB-23:00
March 0.00 114.66 01-MAR-07:10 4835.28 01-MAR-09:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 49.03 14-MAR-15:00
April 0.00 114.66 03-APR-06:10 4835.28 03-APR-08:09 0.00 0.00 0.00 0.00 11.11 23-APR-16:00 48.93 04-APR-18:00
May 0.00 114.66 01-MAY-06:10 4835.28 01-MAY-08:09 0.00 0.00 0.00 0.00 5.15 24-MAY-15:00 17.23 09-MAY-08:70
June 0.00 114.66 01-JUN-06:10 4835.28 01-JUN-08:09 0.00 0.00 0.00 0.00 13.50 29-JUN-16:00 19.59 09-JUN-09:00
July 0.00 114.66 03-JUL-06:10 4835.28 03-JUL-08:09 0.00 0.00 0.00 0.00 10.91 15-JUL-14:00 13.01 08-JUL-14:10
August 0.00 114.66 01-AUG-06:10 4835.28 01-AUG-08:09 0.00 0.00 0.00 0.00 9.75 08-AUG-16:00 24.33 17-AUG-14:00
September 0.00 114.66 01-SEP-06:10 4835.28 01-SEP-08:09 0.00 0.00 0.00 0.00 2.82 07-SEP-15:00 19.93 20-SEP-03:52
October 0.00 114.66 02-OCT-06:10 4835.28 02-OCT-08:09 0.00 0.00 0.00 0.00 0.00 19-OCT-15:00 34.56 31-OCT-10:55
November 0.00 114.66 01-NOV-06:10 4835.28 01-NOV-08:09 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 52.97 21-NOV-22:00
December 0.00 114.66 01-DEC-07:10 4835.28 01-DEC-09:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 81.35 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 114.66   4835.28   0.00 0.00 0.00 0.00 0.00   13.01  
Maximum of Months 0.00 114.66   4835.28   0.00 0.00 0.00 0.00 13.50   89.31  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 IT HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 59.01 02-JAN-07:10 55.52 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 59.01 01-FEB-07:10 55.52 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 59.01 01-MAR-07:10 55.52 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 59.01 03-APR-06:10 55.52 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 59.01 01-MAY-06:10 55.52 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 59.01 01-JUN-06:10 55.52 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 59.01 03-JUL-06:10 55.52 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 59.01 01-AUG-06:10 55.52 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 59.01 01-SEP-06:10 55.52 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 59.01 02-OCT-06:10 55.52 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 59.01 01-NOV-06:10 55.52 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 59.01 01-DEC-07:10 55.52 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 59.01   55.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 59.01   55.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 101.16 02-JAN-07:10 95.18 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 101.16 01-FEB-07:10 95.18 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 101.16 01-MAR-07:10 95.18 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 101.16 03-APR-06:10 95.18 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 101.16 01-MAY-06:10 95.18 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 101.16 01-JUN-06:10 95.18 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 101.16 03-JUL-06:10 95.18 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 101.16 01-AUG-06:10 95.18 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 101.16 01-SEP-06:10 95.18 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 101.16 02-OCT-06:10 95.18 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 101.16 01-NOV-06:10 95.18 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 101.16 01-DEC-07:10 95.18 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 101.16   95.18   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 101.16   95.18   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 20.21 02-JAN-07:10 21.42 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 25.87 04-JAN-11:57
February 0.00 20.21 01-FEB-07:10 21.42 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 26.00 12-FEB-23:00
March 0.00 20.21 01-MAR-07:10 21.42 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 14.21 14-MAR-15:40
April 0.00 20.21 03-APR-06:10 21.42 03-APR-05:10 0.00 0.00 0.00 0.00 4.53 23-APR-16:00 13.00 26-APR-15:00
May 0.00 20.21 01-MAY-06:10 21.42 01-MAY-05:10 0.00 0.00 0.00 0.00 2.02 24-MAY-17:10 4.98 20-MAY-06:10
June 0.00 20.21 01-JUN-06:10 21.42 01-JUN-05:10 0.00 0.00 0.00 0.00 4.40 29-JUN-16:00 5.29 09-JUN-09:00
July 0.00 20.21 03-JUL-06:10 21.42 03-JUL-05:10 0.00 0.00 0.00 0.00 4.98 15-JUL-16:00 2.63 08-JUL-14:00
August 0.00 20.21 01-AUG-06:10 21.42 01-AUG-05:10 0.00 0.00 0.00 0.00 3.31 08-AUG-16:00 6.61 17-AUG-14:00
September 0.00 20.21 01-SEP-06:10 21.42 01-SEP-05:10 0.00 0.00 0.00 0.00 1.39 07-SEP-15:00 5.69 20-SEP-06:10
October 0.00 20.21 02-OCT-06:10 21.42 02-OCT-05:10 0.00 0.00 0.00 0.00 0.37 19-OCT-15:00 9.80 31-OCT-11:00
November 0.00 20.21 01-NOV-06:10 21.42 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 13.63 22-NOV-02:00
December 0.00 20.21 01-DEC-07:10 21.42 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 23.56 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 20.21   21.42   0.00 0.00 0.00 0.00 0.00   2.63  
Maximum of Months 0.00 20.21   21.42   0.00 0.00 0.00 0.00 4.98   26.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 209.06 02-JAN-07:10 196.71 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 209.06 01-FEB-07:10 196.71 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 209.06 01-MAR-07:10 196.71 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 209.06 03-APR-06:10 196.71 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 209.06 01-MAY-06:10 196.71 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 209.06 01-JUN-06:10 196.71 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 209.06 03-JUL-06:10 196.71 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 209.06 01-AUG-06:10 196.71 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 209.06 01-SEP-06:10 196.71 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 209.06 02-OCT-06:10 196.71 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 209.06 01-NOV-06:10 196.71 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 209.06 01-DEC-07:10 196.71 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 209.06   196.71   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 209.06   196.71   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 MED GAS

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 12.86 02-JAN-07:10 5.57 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 44.81 04-JAN-12:00
February 0.00 12.86 01-FEB-07:10 5.57 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 47.17 12-FEB-23:00
March 0.00 12.86 01-MAR-07:10 5.57 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 25.80 14-MAR-16:00
April 0.00 12.86 03-APR-06:10 5.57 03-APR-05:10 0.00 0.00 0.00 0.00 8.25 23-APR-16:00 23.67 26-APR-15:00
May 0.00 12.86 01-MAY-06:10 5.57 01-MAY-05:10 0.00 0.00 0.00 0.00 3.97 24-MAY-17:10 9.07 20-MAY-06:10
June 0.00 12.86 01-JUN-06:10 5.57 01-JUN-05:10 0.00 0.00 0.00 0.00 8.01 29-JUN-16:00 9.64 09-JUN-09:00
July 0.00 12.86 03-JUL-06:10 5.57 03-JUL-05:10 0.00 0.00 0.00 0.00 8.28 15-JUL-16:00 4.78 08-JUL-14:00
August 0.00 12.86 01-AUG-06:10 5.57 01-AUG-05:10 0.00 0.00 0.00 0.00 6.02 08-AUG-16:00 12.03 17-AUG-14:00
September 0.00 12.86 01-SEP-06:10 5.57 01-SEP-05:10 0.00 0.00 0.00 0.00 2.54 07-SEP-15:00 10.37 20-SEP-06:09
October 0.00 12.86 02-OCT-06:10 5.57 02-OCT-05:10 0.00 0.00 0.00 0.00 0.67 19-OCT-15:00 17.84 31-OCT-11:00
November 0.00 12.86 01-NOV-06:10 5.57 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 24.81 22-NOV-02:00
December 0.00 12.86 01-DEC-07:10 5.57 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 42.17 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 12.86   5.57   0.00 0.00 0.00 0.00 0.00   4.78  
Maximum of Months 0.00 12.86   5.57   0.00 0.00 0.00 0.00 8.28   47.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 61.96 02-JAN-07:10 58.30 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 61.96 01-FEB-07:10 58.30 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 61.96 01-MAR-07:10 58.30 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 61.96 03-APR-06:10 58.30 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 61.96 01-MAY-06:10 58.30 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 61.96 01-JUN-06:10 58.30 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 61.96 03-JUL-06:10 58.30 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 61.96 01-AUG-06:10 58.30 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 61.96 01-SEP-06:10 58.30 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 61.96 02-OCT-06:10 58.30 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 61.96 01-NOV-06:10 58.30 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 61.96 01-DEC-07:10 58.30 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 61.96   58.30   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 61.96   58.30   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 20.21 02-JAN-07:10 21.42 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 25.96 04-JAN-11:57
February 0.00 20.21 01-FEB-07:10 21.42 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 25.93 12-FEB-23:00
March 0.00 20.21 01-MAR-07:10 21.42 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 14.21 14-MAR-15:50
April 0.00 20.21 03-APR-06:10 21.42 03-APR-05:10 0.00 0.00 0.00 0.00 4.53 23-APR-16:00 13.00 26-APR-15:00
May 0.00 20.21 01-MAY-06:10 21.42 01-MAY-05:10 0.00 0.00 0.00 0.00 1.98 24-MAY-17:10 4.98 20-MAY-06:08
June 0.00 20.21 01-JUN-06:10 21.42 01-JUN-05:10 0.00 0.00 0.00 0.00 4.40 29-JUN-16:00 5.30 09-JUN-09:00
July 0.00 20.21 03-JUL-06:10 21.42 03-JUL-05:10 0.00 0.00 0.00 0.00 4.63 15-JUL-16:00 2.63 08-JUL-14:00
August 0.00 20.21 01-AUG-06:10 21.42 01-AUG-05:10 0.00 0.00 0.00 0.00 3.31 08-AUG-16:00 6.61 17-AUG-14:00
September 0.00 20.21 01-SEP-06:10 21.42 01-SEP-05:10 0.00 0.00 0.00 0.00 1.39 07-SEP-15:00 5.70 20-SEP-06:03
October 0.00 20.21 02-OCT-06:10 21.42 02-OCT-05:10 0.00 0.00 0.00 0.00 0.37 19-OCT-15:00 9.80 31-OCT-10:55
November 0.00 20.21 01-NOV-06:10 21.42 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 14.03 22-NOV-02:00
December 0.00 20.21 01-DEC-07:10 21.42 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 23.66 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 20.21   21.42   0.00 0.00 0.00 0.00 0.00   2.63  
Maximum of Months 0.00 20.21   21.42   0.00 0.00 0.00 0.00 4.63   25.96  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 209.06 02-JAN-07:10 196.71 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 209.06 01-FEB-07:10 196.71 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 209.06 01-MAR-07:10 196.71 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 209.06 03-APR-06:10 196.71 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 209.06 01-MAY-06:10 196.71 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 209.06 01-JUN-06:10 196.71 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 209.06 03-JUL-06:10 196.71 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 209.06 01-AUG-06:10 196.71 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 209.06 01-SEP-06:10 196.71 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 209.06 02-OCT-06:10 196.71 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 209.06 01-NOV-06:10 196.71 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 209.06 01-DEC-07:10 196.71 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 209.06   196.71   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 209.06   196.71   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 12.40 02-JAN-07:10 5.37 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 12.40 01-FEB-07:10 5.37 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 12.40 01-MAR-07:10 5.37 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 12.40 03-APR-06:10 5.37 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 12.40 01-MAY-06:10 5.37 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 12.40 01-JUN-06:10 5.37 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 12.40 03-JUL-06:10 5.37 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 12.40 01-AUG-06:10 5.37 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 12.40 01-SEP-06:10 5.37 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 12.40 02-OCT-06:10 5.37 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 12.40 01-NOV-06:10 5.37 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 12.40 01-DEC-07:10 5.37 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 12.40   5.37   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 12.40   5.37   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 20.21 02-JAN-07:10 21.42 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 20.21 01-FEB-07:10 21.42 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 20.21 01-MAR-07:10 21.42 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 20.21 03-APR-06:10 21.42 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 20.21 01-MAY-06:10 21.42 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 20.21 01-JUN-06:10 21.42 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 20.21 03-JUL-06:10 21.42 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 20.21 01-AUG-06:10 21.42 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 20.21 01-SEP-06:10 21.42 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 20.21 02-OCT-06:10 21.42 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 20.21 01-NOV-06:10 21.42 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 20.21 01-DEC-07:10 21.42 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 20.21   21.42   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 20.21   21.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 222.55 02-JAN-07:10 209.40 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 222.55 01-FEB-07:10 209.40 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 222.55 01-MAR-07:10 209.40 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 222.55 03-APR-06:10 209.40 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 222.55 01-MAY-06:10 209.40 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 222.55 01-JUN-06:10 209.40 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 222.55 03-JUL-06:10 209.40 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 222.55 01-AUG-06:10 209.40 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 222.55 01-SEP-06:10 209.40 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 222.55 02-OCT-06:10 209.40 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 222.55 01-NOV-06:10 209.40 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 222.55 01-DEC-07:10 209.40 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 222.55   209.40   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 222.55   209.40   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 20.21 02-JAN-07:10 21.42 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 23.48 04-JAN-11:53
February 0.00 20.21 01-FEB-07:10 21.42 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 25.91 12-FEB-23:00
March 0.00 20.21 01-MAR-07:10 21.42 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 13.66 14-MAR-16:00
April 0.00 20.21 03-APR-06:10 21.42 03-APR-05:10 0.00 0.00 0.00 0.00 4.53 23-APR-16:00 13.00 26-APR-15:00
May 0.00 20.21 01-MAY-06:10 21.42 01-MAY-05:10 0.00 0.00 0.00 0.00 1.99 10-MAY-17:10 4.98 20-MAY-06:10
June 0.00 20.21 01-JUN-06:10 21.42 01-JUN-05:10 0.00 0.00 0.00 0.00 4.37 29-JUN-16:00 5.29 09-JUN-09:00
July 0.00 20.21 03-JUL-06:10 21.42 03-JUL-05:10 0.00 0.00 0.00 0.00 4.86 15-JUL-16:00 2.63 08-JUL-14:00
August 0.00 20.21 01-AUG-06:10 21.42 01-AUG-05:10 0.00 0.00 0.00 0.00 3.31 08-AUG-16:00 6.61 17-AUG-14:00
September 0.00 20.21 01-SEP-06:10 21.42 01-SEP-05:10 0.00 0.00 0.00 0.00 1.39 07-SEP-15:00 5.69 20-SEP-06:10
October 0.00 20.21 02-OCT-06:10 21.42 02-OCT-05:10 0.00 0.00 0.00 0.00 0.37 19-OCT-15:00 9.80 31-OCT-10:55
November 0.00 20.21 01-NOV-06:10 21.42 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 13.63 22-NOV-02:00
December 0.00 20.21 01-DEC-07:10 21.42 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 22.12 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 20.21   21.42   0.00 0.00 0.00 0.00 0.00   2.63  
Maximum of Months 0.00 20.21   21.42   0.00 0.00 0.00 0.00 4.86   25.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 53.95 02-JAN-07:10 50.76 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 53.95 01-FEB-07:10 50.76 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 53.95 01-MAR-07:10 50.76 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 53.95 03-APR-06:10 50.76 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 53.95 01-MAY-06:10 50.76 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 53.95 01-JUN-06:10 50.76 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 53.95 03-JUL-06:10 50.76 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 53.95 01-AUG-06:10 50.76 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 53.95 01-SEP-06:10 50.76 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 53.95 02-OCT-06:10 50.76 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 53.95 01-NOV-06:10 50.76 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 53.95 01-DEC-07:10 50.76 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 53.95   50.76   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 53.95   50.76   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 SCRUB

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 35.41 02-JAN-07:10 33.31 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 35.41 01-FEB-07:10 33.31 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 35.41 01-MAR-07:10 33.31 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 35.41 03-APR-06:10 33.31 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 35.41 01-MAY-06:10 33.31 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 35.41 01-JUN-06:10 33.31 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 35.41 03-JUL-06:10 33.31 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 35.41 01-AUG-06:10 33.31 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 35.41 01-SEP-06:10 33.31 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 35.41 02-OCT-06:10 33.31 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 35.41 01-NOV-06:10 33.31 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 35.41 01-DEC-07:10 33.31 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 35.41   33.31   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 35.41   33.31   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 259.64 02-JAN-07:10 244.30 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 259.64 01-FEB-07:10 244.30 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 259.64 01-MAR-07:10 244.30 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 259.64 03-APR-06:10 244.30 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 259.64 01-MAY-06:10 244.30 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 259.64 01-JUN-06:10 244.30 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 259.64 03-JUL-06:10 244.30 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 259.64 01-AUG-06:10 244.30 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 259.64 01-SEP-06:10 244.30 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 259.64 02-OCT-06:10 244.30 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 259.64 01-NOV-06:10 244.30 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 259.64 01-DEC-07:10 244.30 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 259.64   244.30   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 259.64   244.30   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 90.92 02-JAN-07:10 39.35 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 90.92 01-FEB-07:10 39.35 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 90.92 01-MAR-07:10 39.35 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 90.92 03-APR-06:10 39.35 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 90.92 01-MAY-06:10 39.35 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 90.92 01-JUN-06:10 39.35 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 90.92 03-JUL-06:10 39.35 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 90.92 01-AUG-06:10 39.35 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 90.92 01-SEP-06:10 39.35 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 90.92 02-OCT-06:10 39.35 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 90.92 01-NOV-06:10 39.35 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 90.92 01-DEC-07:10 39.35 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 90.92   39.35   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 90.92   39.35   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 211.22 02-JAN-07:10 91.43 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 107.09 04-JAN-12:00
February 0.00 211.22 01-FEB-07:10 91.43 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 110.58 12-FEB-23:00
March 0.00 211.22 01-MAR-07:10 91.43 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 60.64 14-MAR-15:00
April 0.00 211.22 03-APR-06:10 91.43 03-APR-05:10 0.00 0.00 0.00 0.00 19.34 23-APR-16:00 55.47 26-APR-15:00
May 0.00 211.22 01-MAY-06:10 91.43 01-MAY-05:10 0.00 0.00 0.00 0.00 8.08 24-MAY-17:50 21.27 20-MAY-06:10
June 0.00 211.22 01-JUN-06:10 91.43 01-JUN-05:10 0.00 0.00 0.00 0.00 18.19 29-JUN-16:00 22.60 09-JUN-09:00
July 0.00 211.22 03-JUL-06:10 91.43 03-JUL-05:10 0.00 0.00 0.00 0.00 18.20 15-JUL-16:00 11.21 08-JUL-14:00
August 0.00 211.22 01-AUG-06:10 91.43 01-AUG-05:10 0.00 0.00 0.00 0.00 13.85 08-AUG-16:00 28.20 17-AUG-14:00
September 0.00 211.22 01-SEP-06:10 91.43 01-SEP-05:10 0.00 0.00 0.00 0.00 5.95 07-SEP-15:00 24.31 20-SEP-06:07
October 0.00 211.22 02-OCT-06:10 91.43 02-OCT-05:10 0.00 0.00 0.00 0.00 1.56 19-OCT-15:00 41.82 31-OCT-11:00
November 0.00 211.22 01-NOV-06:10 91.43 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 58.16 22-NOV-02:00
December 0.00 211.22 01-DEC-07:10 91.43 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 99.72 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 211.22   91.43   0.00 0.00 0.00 0.00 0.00   11.21  
Maximum of Months 0.00 211.22   91.43   0.00 0.00 0.00 0.00 19.34   110.58  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 82.61 02-JAN-07:10 77.73 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 60.69 04-JAN-11:57
February 0.00 82.61 01-FEB-07:10 77.73 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 60.45 12-FEB-23:00
March 0.00 82.61 01-MAR-07:10 77.73 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 33.15 14-MAR-16:00
April 0.00 82.61 03-APR-06:10 77.73 03-APR-05:10 0.00 0.00 0.00 0.00 7.95 23-APR-16:00 31.53 19-APR-10:00
May 0.00 82.61 01-MAY-06:10 77.73 01-MAY-05:10 0.00 0.00 0.00 0.00 3.70 24-MAY-15:00 11.63 20-MAY-06:10
June 0.00 82.61 01-JUN-06:10 77.73 01-JUN-05:10 0.00 0.00 0.00 0.00 9.45 29-JUN-16:00 12.59 09-JUN-09:00
July 0.00 82.61 03-JUL-06:10 77.73 03-JUL-05:10 0.00 0.00 0.00 0.00 8.87 15-JUL-15:30 6.13 08-JUL-14:00
August 0.00 82.61 01-AUG-06:10 77.73 01-AUG-05:10 0.00 0.00 0.00 0.00 6.83 08-AUG-16:00 15.91 17-AUG-14:00
September 0.00 82.61 01-SEP-06:10 77.73 01-SEP-05:10 0.00 0.00 0.00 0.00 1.97 07-SEP-15:00 13.38 20-SEP-06:03
October 0.00 82.61 02-OCT-06:10 77.73 02-OCT-05:10 0.00 0.00 0.00 0.00 0.12 19-OCT-15:00 22.86 31-OCT-11:00
November 0.00 82.61 01-NOV-06:10 77.73 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 33.47 22-NOV-02:00
December 0.00 82.61 01-DEC-07:10 77.73 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 55.38 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 82.61   77.73   0.00 0.00 0.00 0.00 0.00   6.13  
Maximum of Months 0.00 82.61   77.73   0.00 0.00 0.00 0.00 9.45   60.69  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 107.90 02-JAN-07:10 101.53 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 37.81 04-JAN-12:00
February 0.00 107.90 01-FEB-07:10 101.53 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 38.38 12-FEB-23:00
March 0.00 107.90 01-MAR-07:10 101.53 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 21.05 14-MAR-16:00
April 0.00 107.90 03-APR-06:10 101.53 03-APR-05:10 0.00 0.00 0.00 0.00 6.45 23-APR-16:00 19.25 26-APR-15:00
May 0.00 107.90 01-MAY-06:10 101.53 01-MAY-05:10 0.00 0.00 0.00 0.00 2.74 24-MAY-15:00 7.38 20-MAY-06:10
June 0.00 107.90 01-JUN-06:10 101.53 01-JUN-05:10 0.00 0.00 0.00 0.00 6.13 29-JUN-16:00 7.84 09-JUN-09:00
July 0.00 107.90 03-JUL-06:10 101.53 03-JUL-05:10 0.00 0.00 0.00 0.00 6.10 15-JUL-15:40 3.89 08-JUL-14:00
August 0.00 107.90 01-AUG-06:10 101.53 01-AUG-05:10 0.00 0.00 0.00 0.00 4.59 08-AUG-16:00 9.79 17-AUG-14:00
September 0.00 107.90 01-SEP-06:10 101.53 01-SEP-05:10 0.00 0.00 0.00 0.00 2.06 07-SEP-15:00 8.45 20-SEP-06:04
October 0.00 107.90 02-OCT-06:10 101.53 02-OCT-05:10 0.00 0.00 0.00 0.00 0.54 19-OCT-15:00 14.51 31-OCT-11:00
November 0.00 107.90 01-NOV-06:10 101.53 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 20.20 22-NOV-02:00
December 0.00 107.90 01-DEC-07:10 101.53 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 35.04 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 107.90   101.53   0.00 0.00 0.00 0.00 0.00   3.89  
Maximum of Months 0.00 107.90   101.53   0.00 0.00 0.00 0.00 6.45   38.38  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 9.64 02-JAN-07:10 4.17 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 9.64 01-FEB-07:10 4.17 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 9.64 01-MAR-07:10 4.17 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 9.64 03-APR-06:10 4.17 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 9.64 01-MAY-06:10 4.17 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 9.64 01-JUN-06:10 4.17 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 9.64 03-JUL-06:10 4.17 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 9.64 01-AUG-06:10 4.17 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 9.64 01-SEP-06:10 4.17 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 9.64 02-OCT-06:10 4.17 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 9.64 01-NOV-06:10 4.17 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 9.64 01-DEC-07:10 4.17 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 9.64   4.17   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 9.64   4.17   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 82.65 02-JAN-07:10 35.78 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 77.61 04-JAN-12:00
February 0.00 82.65 01-FEB-07:10 35.78 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 77.72 12-FEB-23:00
March 0.00 82.65 01-MAR-07:10 35.78 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 42.62 14-MAR-15:00
April 0.00 82.65 03-APR-06:10 35.78 03-APR-05:10 0.00 0.00 0.00 0.00 11.13 23-APR-16:00 38.99 26-APR-15:00
May 0.00 82.65 01-MAY-06:10 35.78 01-MAY-05:10 0.00 0.00 0.00 0.00 5.25 24-MAY-15:00 15.05 20-MAY-06:08
June 0.00 82.65 01-JUN-06:10 35.78 01-JUN-05:10 0.00 0.00 0.00 0.00 12.15 29-JUN-16:00 15.88 09-JUN-09:00
July 0.00 82.65 03-JUL-06:10 35.78 03-JUL-05:10 0.00 0.00 0.00 0.00 11.37 15-JUL-15:00 7.88 08-JUL-14:00
August 0.00 82.65 01-AUG-06:10 35.78 01-AUG-05:10 0.00 0.00 0.00 0.00 8.78 08-AUG-16:00 19.82 17-AUG-14:00
September 0.00 82.65 01-SEP-06:10 35.78 01-SEP-05:10 0.00 0.00 0.00 0.00 3.06 07-SEP-15:00 17.08 20-SEP-06:09
October 0.00 82.65 02-OCT-06:10 35.78 02-OCT-05:10 0.00 0.00 0.00 0.00 0.94 19-OCT-15:00 29.39 31-OCT-10:55
November 0.00 82.65 01-NOV-06:10 35.78 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 42.69 22-NOV-02:00
December 0.00 82.65 01-DEC-07:10 35.78 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 71.17 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 82.65   35.78   0.00 0.00 0.00 0.00 0.00   7.88  
Maximum of Months 0.00 82.65   35.78   0.00 0.00 0.00 0.00 12.15   77.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 30.35 02-JAN-07:10 28.55 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 14604.83 09-JAN-07:01
February 0.00 30.35 01-FEB-07:10 28.55 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 13315.36 14-FEB-07:01
March 0.00 30.35 01-MAR-07:10 28.55 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 10535.05 06-MAR-07:01
April 0.00 30.35 03-APR-06:10 28.55 03-APR-05:10 0.00 0.00 0.00 0.00 4.95 23-APR-16:00 8107.37 05-APR-06:01
May 0.00 30.35 01-MAY-06:10 28.55 01-MAY-05:10 0.00 0.00 0.00 0.00 789.28 25-MAY-15:00 5902.83 01-MAY-06:01
June 0.00 30.35 01-JUN-06:10 28.55 01-JUN-05:10 0.00 0.00 0.00 0.00 1296.77 29-JUN-12:55 2774.41 02-JUN-06:01
July 0.00 30.35 03-JUL-06:10 28.55 03-JUL-05:10 0.00 0.00 0.00 0.00 836.16 24-JUL-13:45 2215.69 27-JUL-06:01
August 0.00 30.35 01-AUG-06:10 28.55 01-AUG-05:10 0.00 0.00 0.00 0.00 924.78 08-AUG-13:05 3172.44 25-AUG-06:01
September 0.00 30.35 01-SEP-06:10 28.55 01-SEP-05:10 0.00 0.00 0.00 0.00 463.11 01-SEP-14:05 4605.34 06-SEP-06:01
October 0.00 30.35 02-OCT-06:10 28.55 02-OCT-05:10 0.00 0.00 0.00 0.00 163.91 19-OCT-14:05 7895.79 30-OCT-06:01
November 0.00 30.35 01-NOV-06:10 28.55 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 9345.42 29-NOV-07:01
December 0.00 30.35 01-DEC-07:10 28.55 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 12883.14 26-DEC-07:01
                           
Annual Sum or Average                          
Minimum of Months 0.00 30.35   28.55   0.00 0.00 0.00 0.00 0.00   2215.69  
Maximum of Months 0.00 30.35   28.55   0.00 0.00 0.00 0.00 1296.77   14604.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 23.95 02-JAN-07:10 25.38 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 23.95 01-FEB-07:10 25.38 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 23.95 01-MAR-07:10 25.38 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 23.95 03-APR-06:10 25.38 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 23.95 01-MAY-06:10 25.38 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 23.95 01-JUN-06:10 25.38 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 23.95 03-JUL-06:10 25.38 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 23.95 01-AUG-06:10 25.38 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 23.95 01-SEP-06:10 25.38 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 23.95 02-OCT-06:10 25.38 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 23.95 01-NOV-06:10 25.38 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 23.95 01-DEC-07:10 25.38 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 23.95   25.38   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 23.95   25.38   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 75.87 02-JAN-07:10 71.39 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 75.87 01-FEB-07:10 71.39 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 75.87 01-MAR-07:10 71.39 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 75.87 03-APR-06:10 71.39 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 75.87 01-MAY-06:10 71.39 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 75.87 01-JUN-06:10 71.39 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 75.87 03-JUL-06:10 71.39 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 75.87 01-AUG-06:10 71.39 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 75.87 01-SEP-06:10 71.39 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 75.87 02-OCT-06:10 71.39 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 75.87 01-NOV-06:10 71.39 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 75.87 01-DEC-07:10 71.39 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 75.87   71.39   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 75.87   71.39   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 75.87 02-JAN-07:10 71.39 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 75.87 01-FEB-07:10 71.39 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 75.87 01-MAR-07:10 71.39 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 75.87 03-APR-06:10 71.39 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 75.87 01-MAY-06:10 71.39 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 75.87 01-JUN-06:10 71.39 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 75.87 03-JUL-06:10 71.39 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 75.87 01-AUG-06:10 71.39 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 75.87 01-SEP-06:10 71.39 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 75.87 02-OCT-06:10 71.39 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 75.87 01-NOV-06:10 71.39 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 75.87 01-DEC-07:10 71.39 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 75.87   71.39   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 75.87   71.39   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 75.87 02-JAN-07:10 71.39 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 75.87 01-FEB-07:10 71.39 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 75.87 01-MAR-07:10 71.39 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 75.87 03-APR-06:10 71.39 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 75.87 01-MAY-06:10 71.39 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 75.87 01-JUN-06:10 71.39 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 75.87 03-JUL-06:10 71.39 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 75.87 01-AUG-06:10 71.39 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 75.87 01-SEP-06:10 71.39 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 75.87 02-OCT-06:10 71.39 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 75.87 01-NOV-06:10 71.39 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 75.87 01-DEC-07:10 71.39 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 75.87   71.39   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 75.87   71.39   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 83.46 02-JAN-07:10 78.53 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 83.46 01-FEB-07:10 78.53 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 83.46 01-MAR-07:10 78.53 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 83.46 03-APR-06:10 78.53 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 83.46 01-MAY-06:10 78.53 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 83.46 01-JUN-06:10 78.53 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 83.46 03-JUL-06:10 78.53 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 83.46 01-AUG-06:10 78.53 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 83.46 01-SEP-06:10 78.53 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 83.46 02-OCT-06:10 78.53 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 83.46 01-NOV-06:10 78.53 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 83.46 01-DEC-07:10 78.53 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 83.46   78.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 83.46   78.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 83.46 02-JAN-07:10 78.53 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 83.46 01-FEB-07:10 78.53 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 83.46 01-MAR-07:10 78.53 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 83.46 03-APR-06:10 78.53 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 83.46 01-MAY-06:10 78.53 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 83.46 01-JUN-06:10 78.53 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 83.46 03-JUL-06:10 78.53 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 83.46 01-AUG-06:10 78.53 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 83.46 01-SEP-06:10 78.53 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 83.46 02-OCT-06:10 78.53 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 83.46 01-NOV-06:10 78.53 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 83.46 01-DEC-07:10 78.53 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 83.46   78.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 83.46   78.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 83.46 02-JAN-07:10 78.53 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 83.46 01-FEB-07:10 78.53 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 83.46 01-MAR-07:10 78.53 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 83.46 03-APR-06:10 78.53 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 83.46 01-MAY-06:10 78.53 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 83.46 01-JUN-06:10 78.53 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 83.46 03-JUL-06:10 78.53 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 83.46 01-AUG-06:10 78.53 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 83.46 01-SEP-06:10 78.53 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 83.46 02-OCT-06:10 78.53 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 83.46 01-NOV-06:10 78.53 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 83.46 01-DEC-07:10 78.53 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 83.46   78.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 83.46   78.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 14.46 02-JAN-07:10 6.26 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 99.88 04-JAN-12:00
February 0.00 14.46 01-FEB-07:10 6.26 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 99.34 12-FEB-23:00
March 0.00 14.46 01-MAR-07:10 6.26 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 54.48 14-MAR-15:00
April 0.00 14.46 03-APR-06:10 6.26 03-APR-05:10 0.00 0.00 0.00 0.00 11.72 23-APR-16:00 49.85 26-APR-15:00
May 0.00 14.46 01-MAY-06:10 6.26 01-MAY-05:10 0.00 0.00 0.00 0.00 5.89 24-MAY-15:00 19.67 20-MAY-06:00
June 0.00 14.46 01-JUN-06:10 6.26 01-JUN-05:10 0.00 0.00 0.00 0.00 15.49 29-JUN-16:00 22.22 09-JUN-09:00
July 0.00 14.46 03-JUL-06:10 6.26 03-JUL-05:10 0.00 0.00 0.00 0.00 12.66 15-JUL-15:00 11.53 08-JUL-14:00
August 0.00 14.46 01-AUG-06:10 6.26 01-AUG-05:10 0.00 0.00 0.00 0.00 11.19 08-AUG-16:00 28.02 17-AUG-14:00
September 0.00 14.46 01-SEP-06:10 6.26 01-SEP-05:10 0.00 0.00 0.00 0.00 3.20 07-SEP-15:00 23.19 20-SEP-01:00
October 0.00 14.46 02-OCT-06:10 6.26 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 37.59 31-OCT-10:55
November 0.00 14.46 01-NOV-06:10 6.26 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 57.63 22-NOV-02:00
December 0.00 14.46 01-DEC-07:10 6.26 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 91.28 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 14.46   6.26   0.00 0.00 0.00 0.00 0.00   11.53  
Maximum of Months 0.00 14.46   6.26   0.00 0.00 0.00 0.00 15.49   99.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 187.15 02-JAN-07:10 176.09 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 187.15 01-FEB-07:10 176.09 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 187.15 01-MAR-07:10 176.09 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 187.15 03-APR-06:10 176.09 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 187.15 01-MAY-06:10 176.09 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 187.15 01-JUN-06:10 176.09 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 187.15 03-JUL-06:10 176.09 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 187.15 01-AUG-06:10 176.09 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 187.15 01-SEP-06:10 176.09 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 187.15 02-OCT-06:10 176.09 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 187.15 01-NOV-06:10 176.09 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 187.15 01-DEC-07:10 176.09 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 187.15   176.09   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 187.15   176.09   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 237.73 02-JAN-07:10 223.68 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 237.73 01-FEB-07:10 223.68 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 237.73 01-MAR-07:10 223.68 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 237.73 03-APR-06:10 223.68 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 237.73 01-MAY-06:10 223.68 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 237.73 01-JUN-06:10 223.68 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 237.73 03-JUL-06:10 223.68 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 237.73 01-AUG-06:10 223.68 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 237.73 01-SEP-06:10 223.68 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 237.73 02-OCT-06:10 223.68 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 237.73 01-NOV-06:10 223.68 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 237.73 01-DEC-07:10 223.68 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 237.73   223.68   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 237.73   223.68   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 47.15 02-JAN-07:10 49.97 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 47.15 01-FEB-07:10 49.97 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 47.15 01-MAR-07:10 49.97 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 47.15 03-APR-06:10 49.97 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 47.15 01-MAY-06:10 49.97 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 47.15 01-JUN-06:10 49.97 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 47.15 03-JUL-06:10 49.97 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 47.15 01-AUG-06:10 49.97 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 47.15 01-SEP-06:10 49.97 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 47.15 02-OCT-06:10 49.97 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 47.15 01-NOV-06:10 49.97 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 47.15 01-DEC-07:10 49.97 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 47.15   49.97   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 47.15   49.97   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 12.86 02-JAN-07:10 5.57 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 12.86 01-FEB-07:10 5.57 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 12.86 01-MAR-07:10 5.57 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 12.86 03-APR-06:10 5.57 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 12.86 01-MAY-06:10 5.57 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 12.86 01-JUN-06:10 5.57 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 12.86 03-JUL-06:10 5.57 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 12.86 01-AUG-06:10 5.57 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 12.86 01-SEP-06:10 5.57 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 12.86 02-OCT-06:10 5.57 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 12.86 01-NOV-06:10 5.57 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 12.86 01-DEC-07:10 5.57 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 12.86   5.57   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 12.86   5.57   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 27.55 02-JAN-07:10 11.93 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 27.55 01-FEB-07:10 11.93 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 27.55 01-MAR-07:10 11.93 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 27.55 03-APR-06:10 11.93 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 27.55 01-MAY-06:10 11.93 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 27.55 01-JUN-06:10 11.93 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 27.55 03-JUL-06:10 11.93 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 27.55 01-AUG-06:10 11.93 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 27.55 01-SEP-06:10 11.93 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 27.55 02-OCT-06:10 11.93 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 27.55 01-NOV-06:10 11.93 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 27.55 01-DEC-07:10 11.93 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 27.55   11.93   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 27.55   11.93   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 33.06 02-JAN-07:10 14.31 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 33.06 01-FEB-07:10 14.31 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 33.06 01-MAR-07:10 14.31 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 33.06 03-APR-06:10 14.31 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 33.06 01-MAY-06:10 14.31 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 33.06 01-JUN-06:10 14.31 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 33.06 03-JUL-06:10 14.31 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 33.06 01-AUG-06:10 14.31 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 33.06 01-SEP-06:10 14.31 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 33.06 02-OCT-06:10 14.31 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 33.06 01-NOV-06:10 14.31 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 33.06 01-DEC-07:10 14.31 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 33.06   14.31   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 33.06   14.31   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 28.93 02-JAN-07:10 12.52 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 56.18 04-JAN-12:00
February 0.00 28.93 01-FEB-07:10 12.52 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 55.88 12-FEB-23:00
March 0.00 28.93 01-MAR-07:10 12.52 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 30.65 14-MAR-15:00
April 0.00 28.93 03-APR-06:10 12.52 03-APR-05:10 0.00 0.00 0.00 0.00 6.75 23-APR-16:00 29.68 19-APR-10:00
May 0.00 28.93 01-MAY-06:10 12.52 01-MAY-05:10 0.00 0.00 0.00 0.00 3.32 24-MAY-15:00 10.84 20-MAY-06:05
June 0.00 28.93 01-JUN-06:10 12.52 01-JUN-05:10 0.00 0.00 0.00 0.00 8.71 29-JUN-16:00 11.93 09-JUN-09:00
July 0.00 28.93 03-JUL-06:10 12.52 03-JUL-05:10 0.00 0.00 0.00 0.00 7.99 15-JUL-15:10 5.78 08-JUL-14:00
August 0.00 28.93 01-AUG-06:10 12.52 01-AUG-05:10 0.00 0.00 0.00 0.00 6.29 08-AUG-16:00 14.87 17-AUG-14:00
September 0.00 28.93 01-SEP-06:10 12.52 01-SEP-05:10 0.00 0.00 0.00 0.00 1.80 07-SEP-15:00 12.33 20-SEP-06:03
October 0.00 28.93 02-OCT-06:10 12.52 02-OCT-05:10 0.00 0.00 0.00 0.00 0.22 19-OCT-15:00 21.14 31-OCT-10:55
November 0.00 28.93 01-NOV-06:10 12.52 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 31.06 22-NOV-02:00
December 0.00 28.93 01-DEC-07:10 12.52 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 51.34 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 28.93   12.52   0.00 0.00 0.00 0.00 0.00   5.78  
Maximum of Months 0.00 28.93   12.52   0.00 0.00 0.00 0.00 8.71   56.18  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.00 351.53 02-JAN-07:10 330.76 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 351.53 01-FEB-07:10 330.76 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 351.53 01-MAR-07:10 330.76 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 351.53 03-APR-06:10 330.76 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 351.53 01-MAY-06:10 330.76 01-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 351.53 01-JUN-06:10 330.76 01-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 351.53 03-JUL-06:10 330.76 03-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 351.53 01-AUG-06:10 330.76 01-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 351.53 01-SEP-06:10 330.76 01-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 351.53 02-OCT-06:10 330.76 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 351.53 01-NOV-06:10 330.76 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 351.53 01-DEC-07:10 330.76 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 0.00 351.53   330.76   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 351.53   330.76   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 20.21 02-JAN-07:10 21.42 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 37.45 04-JAN-12:00
February 0.00 20.21 01-FEB-07:10 21.42 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 37.25 12-FEB-23:00
March 0.00 20.21 01-MAR-07:10 21.42 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 20.43 14-MAR-15:00
April 0.00 20.21 03-APR-06:10 21.42 03-APR-05:10 0.00 0.00 0.00 0.00 6.31 23-APR-16:00 18.69 26-APR-15:00
May 0.00 20.21 01-MAY-06:10 21.42 01-MAY-05:10 0.00 0.00 0.00 0.00 2.74 24-MAY-17:10 7.17 20-MAY-06:10
June 0.00 20.21 01-JUN-06:10 21.42 01-JUN-05:10 0.00 0.00 0.00 0.00 6.31 29-JUN-16:00 7.62 09-JUN-09:00
July 0.00 20.21 03-JUL-06:10 21.42 03-JUL-05:10 0.00 0.00 0.00 0.00 6.60 15-JUL-15:40 3.78 08-JUL-14:00
August 0.00 20.21 01-AUG-06:10 21.42 01-AUG-05:10 0.00 0.00 0.00 0.00 4.75 08-AUG-16:00 9.51 17-AUG-14:00
September 0.00 20.21 01-SEP-06:10 21.42 01-SEP-05:10 0.00 0.00 0.00 0.00 1.99 07-SEP-15:00 8.19 20-SEP-06:05
October 0.00 20.21 02-OCT-06:10 21.42 02-OCT-05:10 0.00 0.00 0.00 0.00 0.52 19-OCT-15:00 14.09 31-OCT-10:55
November 0.00 20.21 01-NOV-06:10 21.42 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 20.18 22-NOV-02:00
December 0.00 20.21 01-DEC-07:10 21.42 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 34.23 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 20.21   21.42   0.00 0.00 0.00 0.00 0.00   3.78  
Maximum of Months 0.00 20.21   21.42   0.00 0.00 0.00 0.00 6.60   37.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 155.96 02-JAN-07:10 146.74 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.30 04-JAN-12:00
February 0.00 155.96 01-FEB-07:10 146.74 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.29 12-FEB-23:00
March 0.00 155.96 01-MAR-07:10 146.74 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.16 14-MAR-15:00
April 0.00 155.96 03-APR-06:10 146.74 03-APR-05:10 0.00 0.00 0.00 0.00 0.03 23-APR-16:00 0.15 19-APR-10:00
May 0.00 155.96 01-MAY-06:10 146.74 01-MAY-05:10 0.00 0.00 0.00 0.00 0.02 24-MAY-15:00 0.06 20-MAY-06:00
June 0.00 155.96 01-JUN-06:10 146.74 01-JUN-05:10 0.00 0.00 0.00 0.00 0.05 29-JUN-16:00 0.07 09-JUN-09:00
July 0.00 155.96 03-JUL-06:10 146.74 03-JUL-05:10 0.00 0.00 0.00 0.00 0.04 15-JUL-15:00 0.03 08-JUL-14:00
August 0.00 155.96 01-AUG-06:10 146.74 01-AUG-05:10 0.00 0.00 0.00 0.00 0.03 08-AUG-16:00 0.08 17-AUG-14:00
September 0.00 155.96 01-SEP-06:10 146.74 01-SEP-05:10 0.00 0.00 0.00 0.00 0.01 07-SEP-15:00 0.07 20-SEP-06:00
October 0.00 155.96 02-OCT-06:10 146.74 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 0.11 31-OCT-11:00
November 0.00 155.96 01-NOV-06:10 146.74 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.17 22-NOV-02:00
December 0.00 155.96 01-DEC-07:10 146.74 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.27 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 155.96   146.74   0.00 0.00 0.00 0.00 0.00   0.03  
Maximum of Months 0.00 155.96   146.74   0.00 0.00 0.00 0.00 0.05   0.30  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 14.46 02-JAN-07:10 6.26 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 22.58 04-JAN-12:00
February 0.00 14.46 01-FEB-07:10 6.26 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 22.46 12-FEB-23:00
March 0.00 14.46 01-MAR-07:10 6.26 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 12.32 14-MAR-15:00
April 0.00 14.46 03-APR-06:10 6.26 03-APR-05:10 0.00 0.00 0.00 0.00 3.46 23-APR-16:00 11.28 26-APR-15:00
May 0.00 14.46 01-MAY-06:10 6.26 01-MAY-05:10 0.00 0.00 0.00 0.00 1.53 24-MAY-15:00 4.33 20-MAY-06:10
June 0.00 14.46 01-JUN-06:10 6.26 01-JUN-05:10 0.00 0.00 0.00 0.00 3.54 29-JUN-16:00 4.60 09-JUN-09:00
July 0.00 14.46 03-JUL-06:10 6.26 03-JUL-05:10 0.00 0.00 0.00 0.00 3.55 15-JUL-15:00 2.29 08-JUL-14:00
August 0.00 14.46 01-AUG-06:10 6.26 01-AUG-05:10 0.00 0.00 0.00 0.00 2.71 08-AUG-16:00 5.74 17-AUG-14:00
September 0.00 14.46 01-SEP-06:10 6.26 01-SEP-05:10 0.00 0.00 0.00 0.00 1.19 07-SEP-15:00 4.94 20-SEP-06:05
October 0.00 14.46 02-OCT-06:10 6.26 02-OCT-05:10 0.00 0.00 0.00 0.00 0.31 19-OCT-15:00 8.50 31-OCT-11:00
November 0.00 14.46 01-NOV-06:10 6.26 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 11.82 22-NOV-02:00
December 0.00 14.46 01-DEC-07:10 6.26 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 20.64 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 14.46   6.26   0.00 0.00 0.00 0.00 0.00   2.29  
Maximum of Months 0.00 14.46   6.26   0.00 0.00 0.00 0.00 3.55   22.58  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 71.85 02-JAN-07:10 76.15 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 4.87 04-JAN-12:00
February 0.00 71.85 01-FEB-07:10 76.15 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 4.84 12-FEB-23:00
March 0.00 71.85 01-MAR-07:10 76.15 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2.66 14-MAR-15:00
April 0.00 71.85 03-APR-06:10 76.15 03-APR-05:10 0.00 0.00 0.00 0.00 0.77 23-APR-16:00 2.43 26-APR-15:00
May 0.00 71.85 01-MAY-06:10 76.15 01-MAY-05:10 0.00 0.00 0.00 0.00 0.34 24-MAY-15:00 0.94 20-MAY-06:05
June 0.00 71.85 01-JUN-06:10 76.15 01-JUN-05:10 0.00 0.00 0.00 0.00 0.81 29-JUN-16:00 0.99 09-JUN-09:00
July 0.00 71.85 03-JUL-06:10 76.15 03-JUL-05:10 0.00 0.00 0.00 0.00 0.83 15-JUL-16:00 0.49 08-JUL-14:00
August 0.00 71.85 01-AUG-06:10 76.15 01-AUG-05:10 0.00 0.00 0.00 0.00 0.62 08-AUG-16:00 1.24 17-AUG-14:00
September 0.00 71.85 01-SEP-06:10 76.15 01-SEP-05:10 0.00 0.00 0.00 0.00 0.26 07-SEP-15:00 1.07 20-SEP-06:05
October 0.00 71.85 02-OCT-06:10 76.15 02-OCT-05:10 0.00 0.00 0.00 0.00 0.07 19-OCT-15:00 1.83 31-OCT-10:55
November 0.00 71.85 01-NOV-06:10 76.15 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2.58 22-NOV-02:00
December 0.00 71.85 01-DEC-07:10 76.15 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 4.45 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 71.85   76.15   0.00 0.00 0.00 0.00 0.00   0.49  
Maximum of Months 0.00 71.85   76.15   0.00 0.00 0.00 0.00 0.83   4.87  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 441.00 02-JAN-07:10 1733.32 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 11.75 04-JAN-11:53
February 0.00 441.00 01-FEB-07:10 1733.32 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 14.10 12-FEB-23:00
March 0.00 441.00 01-MAR-07:10 1733.32 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 6.79 17-MAR-04:00
April 0.00 441.00 03-APR-06:10 1733.32 03-APR-05:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 6.48 04-APR-18:00
May 0.00 441.00 01-MAY-06:10 1733.32 01-MAY-05:10 0.00 0.00 0.00 0.00 0.68 24-MAY-15:00 3.17 20-MAY-06:10
June 0.00 441.00 01-JUN-06:10 1733.32 01-JUN-05:10 0.00 0.00 0.00 0.00 1.78 29-JUN-16:00 2.60 09-JUN-09:00
July 0.00 441.00 03-JUL-06:10 1733.32 03-JUL-05:10 0.00 0.00 0.00 0.00 1.32 15-JUL-14:00 1.92 09-JUL-10:00
August 0.00 441.00 01-AUG-06:10 1733.32 01-AUG-05:10 0.00 0.00 0.00 0.00 1.28 08-AUG-16:00 3.23 17-AUG-14:00
September 0.00 441.00 01-SEP-06:10 1733.32 01-SEP-05:10 0.00 0.00 0.00 0.00 0.36 07-SEP-15:00 3.85 20-SEP-06:00
October 0.00 441.00 02-OCT-06:10 1733.32 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 4.58 31-OCT-10:55
November 0.00 441.00 01-NOV-06:10 1733.32 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 8.58 22-NOV-02:00
December 0.00 441.00 01-DEC-07:10 1733.32 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 10.79 16-DEC-06:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 441.00   1733.32   0.00 0.00 0.00 0.00 0.00   1.92  
Maximum of Months 0.00 441.00   1733.32   0.00 0.00 0.00 0.00 1.78   14.10  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 126.45 02-JAN-07:10 118.98 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 221.76 04-JAN-11:57
February 0.00 126.45 01-FEB-07:10 118.98 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 222.08 12-FEB-23:00
March 0.00 126.45 01-MAR-07:10 118.98 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 123.04 14-MAR-16:00
April 0.00 126.45 03-APR-06:10 118.98 03-APR-05:10 0.00 0.00 0.00 0.00 18.70 23-APR-16:00 117.24 19-APR-10:00
May 0.00 126.45 01-MAY-06:10 118.98 01-MAY-05:10 0.00 0.00 0.00 0.00 13.04 24-MAY-15:00 45.23 20-MAY-06:00
June 0.00 126.45 01-JUN-06:10 118.98 01-JUN-05:10 0.00 0.00 0.00 0.00 34.33 29-JUN-16:00 50.16 09-JUN-09:00
July 0.00 126.45 03-JUL-06:10 118.98 03-JUL-05:10 0.00 0.00 0.00 0.00 28.05 15-JUL-14:01 25.87 08-JUL-14:00
August 0.00 126.45 01-AUG-06:10 118.98 01-AUG-05:10 0.00 0.00 0.00 0.00 24.77 08-AUG-16:00 62.30 17-AUG-14:00
September 0.00 126.45 01-SEP-06:10 118.98 01-SEP-05:10 0.00 0.00 0.00 0.00 7.03 07-SEP-15:00 52.76 20-SEP-06:00
October 0.00 126.45 02-OCT-06:10 118.98 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 87.17 31-OCT-10:55
November 0.00 126.45 01-NOV-06:10 118.98 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 129.86 22-NOV-02:00
December 0.00 126.45 01-DEC-07:10 118.98 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 202.68 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 126.45   118.98   0.00 0.00 0.00 0.00 0.00   25.87  
Maximum of Months 0.00 126.45   118.98   0.00 0.00 0.00 0.00 34.33   222.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 351.53 02-JAN-07:10 330.76 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.29 04-JAN-12:00
February 0.00 351.53 01-FEB-07:10 330.76 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.29 12-FEB-23:00
March 0.00 351.53 01-MAR-07:10 330.76 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.16 14-MAR-16:00
April 0.00 351.53 03-APR-06:10 330.76 03-APR-05:10 0.00 0.00 0.00 0.00 0.03 23-APR-16:00 0.15 19-APR-10:00
May 0.00 351.53 01-MAY-06:10 330.76 01-MAY-05:10 0.00 0.00 0.00 0.00 0.02 24-MAY-15:00 0.06 20-MAY-06:00
June 0.00 351.53 01-JUN-06:10 330.76 01-JUN-05:10 0.00 0.00 0.00 0.00 0.05 29-JUN-16:00 0.07 09-JUN-09:00
July 0.00 351.53 03-JUL-06:10 330.76 03-JUL-05:10 0.00 0.00 0.00 0.00 0.04 15-JUL-15:00 0.03 08-JUL-14:00
August 0.00 351.53 01-AUG-06:10 330.76 01-AUG-05:10 0.00 0.00 0.00 0.00 0.03 08-AUG-16:00 0.08 17-AUG-14:00
September 0.00 351.53 01-SEP-06:10 330.76 01-SEP-05:10 0.00 0.00 0.00 0.00 0.01 07-SEP-15:00 0.07 20-SEP-06:00
October 0.00 351.53 02-OCT-06:10 330.76 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 0.11 31-OCT-11:00
November 0.00 351.53 01-NOV-06:10 330.76 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.17 22-NOV-02:00
December 0.00 351.53 01-DEC-07:10 330.76 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.27 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 351.53   330.76   0.00 0.00 0.00 0.00 0.00   0.03  
Maximum of Months 0.00 351.53   330.76   0.00 0.00 0.00 0.00 0.05   0.29  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 20.21 02-JAN-07:10 21.42 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 4.15 04-JAN-12:00
February 0.00 20.21 01-FEB-07:10 21.42 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 4.13 12-FEB-23:00
March 0.00 20.21 01-MAR-07:10 21.42 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2.26 14-MAR-15:00
April 0.00 20.21 03-APR-06:10 21.42 03-APR-05:10 0.00 0.00 0.00 0.00 0.70 23-APR-16:00 2.07 26-APR-15:00
May 0.00 20.21 01-MAY-06:10 21.42 01-MAY-05:10 0.00 0.00 0.00 0.00 0.29 24-MAY-17:10 0.79 20-MAY-06:10
June 0.00 20.21 01-JUN-06:10 21.42 01-JUN-05:10 0.00 0.00 0.00 0.00 0.70 29-JUN-16:00 0.85 09-JUN-09:00
July 0.00 20.21 03-JUL-06:10 21.42 03-JUL-05:10 0.00 0.00 0.00 0.00 0.72 15-JUL-16:00 0.42 08-JUL-14:00
August 0.00 20.21 01-AUG-06:10 21.42 01-AUG-05:10 0.00 0.00 0.00 0.00 0.52 08-AUG-16:00 1.05 17-AUG-14:00
September 0.00 20.21 01-SEP-06:10 21.42 01-SEP-05:10 0.00 0.00 0.00 0.00 0.22 07-SEP-15:00 0.91 20-SEP-06:05
October 0.00 20.21 02-OCT-06:10 21.42 02-OCT-05:10 0.00 0.00 0.00 0.00 0.06 19-OCT-15:00 1.56 31-OCT-10:55
November 0.00 20.21 01-NOV-06:10 21.42 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2.17 22-NOV-02:00
December 0.00 20.21 01-DEC-07:10 21.42 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 3.79 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 20.21   21.42   0.00 0.00 0.00 0.00 0.00   0.42  
Maximum of Months 0.00 20.21   21.42   0.00 0.00 0.00 0.00 0.72   4.15  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 31.43 02-JAN-07:10 33.31 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 62.09 04-JAN-12:00
February 0.00 31.43 01-FEB-07:10 33.31 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 61.77 12-FEB-23:00
March 0.00 31.43 01-MAR-07:10 33.31 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 33.88 14-MAR-15:00
April 0.00 31.43 03-APR-06:10 33.31 03-APR-05:10 0.00 0.00 0.00 0.00 9.50 23-APR-16:00 31.01 26-APR-15:00
May 0.00 31.43 01-MAY-06:10 33.31 01-MAY-05:10 0.00 0.00 0.00 0.00 4.37 24-MAY-15:00 11.99 20-MAY-06:05
June 0.00 31.43 01-JUN-06:10 33.31 01-JUN-05:10 0.00 0.00 0.00 0.00 10.44 29-JUN-16:00 12.66 09-JUN-09:00
July 0.00 31.43 03-JUL-06:10 33.31 03-JUL-05:10 0.00 0.00 0.00 0.00 10.86 15-JUL-16:00 6.29 08-JUL-14:00
August 0.00 31.43 01-AUG-06:10 33.31 01-AUG-05:10 0.00 0.00 0.00 0.00 7.85 08-AUG-16:00 15.79 17-AUG-14:00
September 0.00 31.43 01-SEP-06:10 33.31 01-SEP-05:10 0.00 0.00 0.00 0.00 3.27 07-SEP-15:00 13.61 20-SEP-06:02
October 0.00 31.43 02-OCT-06:10 33.31 02-OCT-05:10 0.00 0.00 0.00 0.00 0.84 19-OCT-15:00 23.38 31-OCT-10:55
November 0.00 31.43 01-NOV-06:10 33.31 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 34.50 22-NOV-02:00
December 0.00 31.43 01-DEC-07:10 33.31 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 56.75 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 31.43   33.31   0.00 0.00 0.00 0.00 0.00   6.29  
Maximum of Months 0.00 31.43   33.31   0.00 0.00 0.00 0.00 10.86   62.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 24.80 02-JAN-07:10 10.73 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 79.84 04-JAN-12:00
February 0.00 24.80 01-FEB-07:10 10.73 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 79.42 12-FEB-23:00
March 0.00 24.80 01-MAR-07:10 10.73 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 43.56 14-MAR-15:00
April 0.00 24.80 03-APR-06:10 10.73 03-APR-05:10 0.00 0.00 0.00 0.00 12.72 23-APR-16:00 39.87 26-APR-15:00
May 0.00 24.80 01-MAY-06:10 10.73 01-MAY-05:10 0.00 0.00 0.00 0.00 5.68 24-MAY-17:10 15.41 20-MAY-06:05
June 0.00 24.80 01-JUN-06:10 10.73 01-JUN-05:10 0.00 0.00 0.00 0.00 13.42 29-JUN-16:00 16.28 09-JUN-09:00
July 0.00 24.80 03-JUL-06:10 10.73 03-JUL-05:10 0.00 0.00 0.00 0.00 14.22 15-JUL-16:00 8.09 08-JUL-14:00
August 0.00 24.80 01-AUG-06:10 10.73 01-AUG-05:10 0.00 0.00 0.00 0.00 10.09 08-AUG-16:00 20.31 17-AUG-14:00
September 0.00 24.80 01-SEP-06:10 10.73 01-SEP-05:10 0.00 0.00 0.00 0.00 4.21 07-SEP-15:00 17.54 20-SEP-06:03
October 0.00 24.80 02-OCT-06:10 10.73 02-OCT-05:10 0.00 0.00 0.00 0.00 1.08 19-OCT-15:00 30.06 31-OCT-10:55
November 0.00 24.80 01-NOV-06:10 10.73 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 43.22 22-NOV-02:00
December 0.00 24.80 01-DEC-07:10 10.73 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 72.96 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 24.80   10.73   0.00 0.00 0.00 0.00 0.00   8.09  
Maximum of Months 0.00 24.80   10.73   0.00 0.00 0.00 0.00 14.22   79.84  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 19.29 02-JAN-07:10 8.35 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 62.09 04-JAN-12:00
February 0.00 19.29 01-FEB-07:10 8.35 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 61.77 12-FEB-23:00
March 0.00 19.29 01-MAR-07:10 8.35 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 33.88 14-MAR-15:00
April 0.00 19.29 03-APR-06:10 8.35 03-APR-05:10 0.00 0.00 0.00 0.00 7.38 23-APR-16:00 31.39 19-APR-10:00
May 0.00 19.29 01-MAY-06:10 8.35 01-MAY-05:10 0.00 0.00 0.00 0.00 3.65 24-MAY-15:00 11.97 20-MAY-06:00
June 0.00 19.29 01-JUN-06:10 8.35 01-JUN-05:10 0.00 0.00 0.00 0.00 9.61 29-JUN-16:00 13.55 09-JUN-09:00
July 0.00 19.29 03-JUL-06:10 8.35 03-JUL-05:10 0.00 0.00 0.00 0.00 8.93 15-JUL-15:00 6.63 08-JUL-14:00
August 0.00 19.29 01-AUG-06:10 8.35 01-AUG-05:10 0.00 0.00 0.00 0.00 6.94 08-AUG-16:00 16.99 17-AUG-14:00
September 0.00 19.29 01-SEP-06:10 8.35 01-SEP-05:10 0.00 0.00 0.00 0.00 1.97 07-SEP-15:00 13.81 20-SEP-06:00
October 0.00 19.29 02-OCT-06:10 8.35 02-OCT-05:10 0.00 0.00 0.00 0.00 0.07 19-OCT-15:00 23.38 31-OCT-10:55
November 0.00 19.29 01-NOV-06:10 8.35 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 35.61 22-NOV-02:00
December 0.00 19.29 01-DEC-07:10 8.35 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 56.75 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 19.29   8.35   0.00 0.00 0.00 0.00 0.00   6.63  
Maximum of Months 0.00 19.29   8.35   0.00 0.00 0.00 0.00 9.61   62.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 520.70 02-JAN-07:10 2470.94 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 15.22 04-JAN-12:00
February 0.00 520.70 01-FEB-07:10 2470.94 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 15.14 12-FEB-23:00
March 0.00 520.70 01-MAR-07:10 2470.94 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 8.60 14-MAR-15:00
April 0.00 520.70 03-APR-06:10 2470.94 03-APR-05:10 0.00 0.00 0.00 0.00 1.15 23-APR-16:00 8.05 19-APR-10:00
May 0.00 520.70 01-MAY-06:10 2470.94 01-MAY-05:10 0.00 0.00 0.00 0.00 0.89 24-MAY-15:00 2.99 09-MAY-09:00
June 0.00 520.70 01-JUN-06:10 2470.94 01-JUN-05:10 0.00 0.00 0.00 0.00 2.36 29-JUN-16:00 3.44 09-JUN-09:00
July 0.00 520.70 03-JUL-06:10 2470.94 03-JUL-05:10 0.00 0.00 0.00 0.00 1.96 15-JUL-15:50 1.76 08-JUL-14:00
August 0.00 520.70 01-AUG-06:10 2470.94 01-AUG-05:10 0.00 0.00 0.00 0.00 1.70 08-AUG-16:00 4.28 17-AUG-14:00
September 0.00 520.70 01-SEP-06:10 2470.94 01-SEP-05:10 0.00 0.00 0.00 0.00 0.48 07-SEP-15:00 3.44 28-SEP-12:00
October 0.00 520.70 02-OCT-06:10 2470.94 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 5.88 31-OCT-11:00
November 0.00 520.70 01-NOV-06:10 2470.94 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 8.59 22-NOV-02:00
December 0.00 520.70 01-DEC-07:10 2470.94 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 13.91 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 520.70   2470.94   0.00 0.00 0.00 0.00 0.00   1.76  
Maximum of Months 0.00 520.70   2470.94   0.00 0.00 0.00 0.00 2.36   15.22  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 264.48 02-JAN-07:10 1255.08 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 17.88 04-JAN-12:00
February 0.00 264.48 01-FEB-07:10 1255.08 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 17.79 12-FEB-23:00
March 0.00 264.48 01-MAR-07:10 1255.08 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 10.10 14-MAR-15:00
April 0.00 264.48 03-APR-06:10 1255.08 03-APR-05:10 0.00 0.00 0.00 0.00 1.26 23-APR-16:00 9.45 19-APR-10:00
May 0.00 264.48 01-MAY-06:10 1255.08 01-MAY-05:10 0.00 0.00 0.00 0.00 1.05 24-MAY-15:00 3.46 20-MAY-06:05
June 0.00 264.48 01-JUN-06:10 1255.08 01-JUN-05:10 0.00 0.00 0.00 0.00 2.77 29-JUN-16:00 4.05 09-JUN-09:00
July 0.00 264.48 03-JUL-06:10 1255.08 03-JUL-05:10 0.00 0.00 0.00 0.00 2.26 15-JUL-14:01 2.07 08-JUL-14:00
August 0.00 264.48 01-AUG-06:10 1255.08 01-AUG-05:10 0.00 0.00 0.00 0.00 2.00 08-AUG-16:00 5.02 17-AUG-14:00
September 0.00 264.48 01-SEP-06:10 1255.08 01-SEP-05:10 0.00 0.00 0.00 0.00 0.57 07-SEP-15:00 4.04 28-SEP-12:00
October 0.00 264.48 02-OCT-06:10 1255.08 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 6.80 31-OCT-11:00
November 0.00 264.48 01-NOV-06:10 1255.08 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 10.00 22-NOV-02:00
December 0.00 264.48 01-DEC-07:10 1255.08 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 16.34 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 264.48   1255.08   0.00 0.00 0.00 0.00 0.00   2.07  
Maximum of Months 0.00 264.48   1255.08   0.00 0.00 0.00 0.00 2.77   17.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FLOOR 3 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 49.59 02-JAN-07:10 21.47 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 159.67 04-JAN-12:00
February 0.00 49.59 01-FEB-07:10 21.47 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 158.83 12-FEB-23:00
March 0.00 49.59 01-MAR-07:10 21.47 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 87.12 14-MAR-15:00
April 0.00 49.59 03-APR-06:10 21.47 03-APR-05:10 0.00 0.00 0.00 0.00 20.82 23-APR-16:00 79.74 26-APR-15:00
May 0.00 49.59 01-MAY-06:10 21.47 01-MAY-05:10 0.00 0.00 0.00 0.00 10.31 24-MAY-15:00 30.71 20-MAY-06:05
June 0.00 49.59 01-JUN-06:10 21.47 01-JUN-05:10 0.00 0.00 0.00 0.00 25.31 29-JUN-16:00 32.55 09-JUN-09:00
July 0.00 49.59 03-JUL-06:10 21.47 03-JUL-05:10 0.00 0.00 0.00 0.00 24.95 15-JUL-15:30 16.17 08-JUL-14:00
August 0.00 49.59 01-AUG-06:10 21.47 01-AUG-05:10 0.00 0.00 0.00 0.00 18.99 08-AUG-16:00 40.62 17-AUG-14:00
September 0.00 49.59 01-SEP-06:10 21.47 01-SEP-05:10 0.00 0.00 0.00 0.00 7.55 07-SEP-15:00 34.96 20-SEP-06:05
October 0.00 49.59 02-OCT-06:10 21.47 02-OCT-05:10 0.00 0.00 0.00 0.00 1.76 19-OCT-15:00 60.12 31-OCT-10:55
November 0.00 49.59 01-NOV-06:10 21.47 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 89.18 22-NOV-02:00
December 0.00 49.59 01-DEC-07:10 21.47 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 145.93 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 49.59   21.47   0.00 0.00 0.00 0.00 0.00   16.17  
Maximum of Months 0.00 49.59   21.47   0.00 0.00 0.00 0.00 25.31   159.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: NE STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 70.81 02-JAN-07:10 66.63 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 238.59 04-JAN-12:00
February 0.00 70.81 01-FEB-07:10 66.63 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 239.52 12-FEB-23:00
March 0.00 70.81 01-MAR-07:10 66.63 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 131.36 14-MAR-15:00
April 0.00 70.81 03-APR-06:10 66.63 03-APR-05:10 0.00 0.00 0.00 0.00 27.91 23-APR-16:00 120.19 26-APR-15:00
May 0.00 70.81 01-MAY-06:10 66.63 01-MAY-05:10 0.00 0.00 0.00 0.00 14.21 24-MAY-15:00 46.11 20-MAY-06:10
June 0.00 70.81 01-JUN-06:10 66.63 01-JUN-05:10 0.00 0.00 0.00 0.00 37.35 29-JUN-16:00 49.02 09-JUN-09:00
July 0.00 70.81 03-JUL-06:10 66.63 03-JUL-05:10 0.00 0.00 0.00 0.00 30.41 15-JUL-14:01 24.33 08-JUL-14:00
August 0.00 70.81 01-AUG-06:10 66.63 01-AUG-05:10 0.00 0.00 0.00 0.00 26.97 08-AUG-16:00 61.17 17-AUG-14:00
September 0.00 70.81 01-SEP-06:10 66.63 01-SEP-05:10 0.00 0.00 0.00 0.00 7.73 07-SEP-15:00 52.68 20-SEP-06:05
October 0.00 70.81 02-OCT-06:10 66.63 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 90.62 31-OCT-11:00
November 0.00 70.81 01-NOV-06:10 66.63 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 126.02 22-NOV-02:00
December 0.00 70.81 01-DEC-07:10 66.63 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 220.08 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 70.81   66.63   0.00 0.00 0.00 0.00 0.00   24.33  
Maximum of Months 0.00 70.81   66.63   0.00 0.00 0.00 0.00 37.35   239.52  



Table of Contents

Report: PeakSpaceGainsMonthly

For: NW ELEVATOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 59.01 02-JAN-07:10 55.52 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 176.40 04-JAN-12:00
February 0.00 59.01 01-FEB-07:10 55.52 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 175.82 12-FEB-23:00
March 0.00 59.01 01-MAR-07:10 55.52 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 96.42 14-MAR-15:00
April 0.00 59.01 03-APR-06:10 55.52 03-APR-05:10 0.00 0.00 0.00 0.00 19.82 23-APR-16:00 88.23 26-APR-15:00
May 0.00 59.01 01-MAY-06:10 55.52 01-MAY-05:10 0.00 0.00 0.00 0.00 10.43 24-MAY-15:00 33.85 20-MAY-06:10
June 0.00 59.01 01-JUN-06:10 55.52 01-JUN-05:10 0.00 0.00 0.00 0.00 27.42 29-JUN-16:00 35.98 09-JUN-09:00
July 0.00 59.01 03-JUL-06:10 55.52 03-JUL-05:10 0.00 0.00 0.00 0.00 22.51 15-JUL-14:01 17.86 08-JUL-14:00
August 0.00 59.01 01-AUG-06:10 55.52 01-AUG-05:10 0.00 0.00 0.00 0.00 19.80 08-AUG-16:00 45.74 17-AUG-14:00
September 0.00 59.01 01-SEP-06:10 55.52 01-SEP-05:10 0.00 0.00 0.00 0.00 5.67 07-SEP-15:00 38.86 20-SEP-06:04
October 0.00 59.01 02-OCT-06:10 55.52 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 66.52 31-OCT-11:00
November 0.00 59.01 01-NOV-06:10 55.52 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 93.26 22-NOV-02:00
December 0.00 59.01 01-DEC-07:10 55.52 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 161.55 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 59.01   55.52   0.00 0.00 0.00 0.00 0.00   17.86  
Maximum of Months 0.00 59.01   55.52   0.00 0.00 0.00 0.00 27.42   176.40  



Table of Contents

Report: PeakSpaceGainsMonthly

For: NW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 80.93 02-JAN-07:10 76.15 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 269.95 04-JAN-12:00
February 0.00 80.93 01-FEB-07:10 76.15 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 273.66 12-FEB-23:00
March 0.00 80.93 01-MAR-07:10 76.15 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 150.08 14-MAR-15:00
April 0.00 80.93 03-APR-06:10 76.15 03-APR-05:10 0.00 0.00 0.00 0.00 32.74 23-APR-16:00 137.33 26-APR-15:00
May 0.00 80.93 01-MAY-06:10 76.15 01-MAY-05:10 0.00 0.00 0.00 0.00 16.24 24-MAY-15:00 52.68 20-MAY-06:10
June 0.00 80.93 01-JUN-06:10 76.15 01-JUN-05:10 0.00 0.00 0.00 0.00 42.68 29-JUN-16:00 56.00 09-JUN-09:00
July 0.00 80.93 03-JUL-06:10 76.15 03-JUL-05:10 0.00 0.00 0.00 0.00 34.78 15-JUL-14:01 27.83 08-JUL-14:00
August 0.00 80.93 01-AUG-06:10 76.15 01-AUG-05:10 0.00 0.00 0.00 0.00 30.82 08-AUG-16:00 71.68 17-AUG-14:00
September 0.00 80.93 01-SEP-06:10 76.15 01-SEP-05:10 0.00 0.00 0.00 0.00 8.83 07-SEP-15:00 60.33 20-SEP-06:04
October 0.00 80.93 02-OCT-06:10 76.15 02-OCT-05:10 0.00 0.00 0.00 0.00 0.35 19-OCT-15:00 103.54 31-OCT-11:00
November 0.00 80.93 01-NOV-06:10 76.15 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 143.99 22-NOV-02:00
December 0.00 80.93 01-DEC-07:10 76.15 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 251.45 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 80.93   76.15   0.00 0.00 0.00 0.00 0.00   27.83  
Maximum of Months 0.00 80.93   76.15   0.00 0.00 0.00 0.00 42.68   273.66  



Table of Contents

Report: PeakSpaceGainsMonthly

For: SW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 40.46 02-JAN-07:10 38.07 02-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 137.57 04-JAN-12:00
February 0.00 40.46 01-FEB-07:10 38.07 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 136.83 12-FEB-23:00
March 0.00 40.46 01-MAR-07:10 38.07 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 75.04 14-MAR-15:00
April 0.00 40.46 03-APR-06:10 38.07 03-APR-05:10 0.00 0.00 0.00 0.00 9.85 23-APR-16:00 68.66 26-APR-15:00
May 0.00 40.46 01-MAY-06:10 38.07 01-MAY-05:10 0.00 0.00 0.00 0.00 8.12 24-MAY-15:00 26.34 20-MAY-06:10
June 0.00 40.46 01-JUN-06:10 38.07 01-JUN-05:10 0.00 0.00 0.00 0.00 21.34 29-JUN-16:00 28.48 09-JUN-09:00
July 0.00 40.46 03-JUL-06:10 38.07 03-JUL-05:10 0.00 0.00 0.00 0.00 17.40 15-JUL-14:01 14.95 06-JUL-22:00
August 0.00 40.46 01-AUG-06:10 38.07 01-AUG-05:10 0.00 0.00 0.00 0.00 15.41 08-AUG-16:00 37.34 17-AUG-14:00
September 0.00 40.46 01-SEP-06:10 38.07 01-SEP-05:10 0.00 0.00 0.00 0.00 4.41 07-SEP-15:00 30.27 20-SEP-06:03
October 0.00 40.46 02-OCT-06:10 38.07 02-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:02 51.77 31-OCT-11:00
November 0.00 40.46 01-NOV-06:10 38.07 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 72.51 22-NOV-02:00
December 0.00 40.46 01-DEC-07:10 38.07 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 125.72 18-DEC-15:00
                           
Annual Sum or Average                          
Minimum of Months 0.00 40.46   38.07   0.00 0.00 0.00 0.00 0.00   14.95  
Maximum of Months 0.00 40.46   38.07   0.00 0.00 0.00 0.00 21.34   137.57  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 648.86 27-JAN-13:33 1399.82 816.48 1283.77 0.00 0.00 0.00 0.00 0.00 0.00
February 616.04 28-FEB-15:05 933.21 544.32 855.84 0.00 0.00 0.00 0.00 0.00 7.67
March 570.17 31-MAR-14:50 233.30 136.08 213.96 0.00 0.00 0.00 0.00 0.00 4.71
April 557.93 13-APR-14:10 466.61 272.16 427.92 0.00 0.00 0.00 0.00 0.00 0.72
May 569.57 18-MAY-17:01 1296.13 907.20 1069.81 0.00 0.00 0.00 0.00 1.62 0.00
June 571.18 30-JUN-17:01 1296.13 907.20 1069.81 0.00 0.00 0.00 0.00 4.37 0.00
July 571.34 21-JUL-17:01 1296.13 907.20 1069.81 0.00 0.00 0.00 0.00 1.44 0.00
August 596.64 25-AUG-14:10 466.61 272.16 427.92 0.00 0.00 0.00 0.00 2.03 0.00
September 624.48 01-SEP-14:10 466.61 272.16 427.92 0.00 0.00 0.00 0.00 1.12 0.00
October 642.55 19-OCT-14:40 233.30 136.08 213.96 0.00 0.00 0.00 0.00 0.00 0.09
November 603.61 17-NOV-13:40 233.30 136.08 213.96 0.00 0.00 0.00 0.00 0.00 6.78
December 570.53 08-DEC-13:27 699.91 408.24 641.88 0.00 0.00 0.00 0.00 0.00 7.43
                       
Annual Sum or Average                      
Minimum of Months 557.93   233.30 136.08 213.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 648.86   1399.82 907.20 1283.77 0.00 0.00 0.00 0.00 4.37 7.67



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 19.39 06-JAN-05:08 0.00 17.14 11.13 0.00 0.00 0.00 0.00 0.00 0.00
February 17.55 07-FEB-18:01 0.00 85.71 27.83 0.00 0.00 0.00 0.00 0.00 0.00
March 17.66 24-MAR-17:01 0.00 85.71 27.83 0.00 0.00 0.00 0.00 0.00 0.00
April 17.75 15-APR-14:01 0.00 34.28 22.26 0.00 0.00 0.00 0.00 0.00 0.00
May 18.87 26-MAY-06:08 0.00 51.43 22.26 0.00 0.00 0.00 0.00 0.00 0.00
June 19.59 30-JUN-17:01 0.00 85.71 27.83 0.00 0.00 0.00 0.00 0.00 0.00
July 19.58 21-JUL-17:01 0.00 85.71 27.83 0.00 0.00 0.00 0.00 0.00 0.00
August 19.35 11-AUG-17:01 0.00 77.14 25.04 0.00 0.00 0.00 0.00 0.00 0.00
September 19.30 01-SEP-06:04 0.00 102.85 44.52 0.00 0.00 0.00 0.00 0.00 0.00
October 18.64 19-OCT-17:01 0.00 77.14 25.04 0.00 0.00 0.00 0.00 0.00 0.00
November 18.62 01-NOV-17:01 0.00 68.57 22.26 0.00 0.00 0.00 0.00 0.00 0.00
December 17.64 05-DEC-18:01 0.00 85.71 27.83 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 17.55   0.00 17.14 11.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19.59   0.00 102.85 44.52 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 CAFE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4035.46 27-JAN-15:04 22682.21 756.00 2079.21 0.00 0.00 0.00 0.00 0.00 0.00
February 3884.86 03-FEB-07:01 45364.41 1512.00 4158.42 0.00 0.00 0.00 0.00 0.00 23.94
March 3889.47 10-MAR-07:01 45364.41 1512.00 4158.42 0.00 0.00 0.00 0.00 0.00 1.60
April 4001.35 24-APR-06:01 45364.41 1512.00 4158.42 0.00 0.00 0.00 0.00 0.00 9.10
May 4028.24 19-MAY-06:01 40827.97 1360.80 3742.58 0.00 0.00 0.00 0.00 0.00 0.36
June 4040.34 09-JUN-06:01 45364.41 1512.00 4158.42 0.00 0.00 0.00 0.00 0.00 9.90
July 4045.30 27-JUL-06:01 45364.41 1512.00 4158.42 0.00 0.00 0.00 0.00 0.00 4.88
August 4052.80 10-AUG-06:01 40827.97 1360.80 3742.58 0.00 0.00 0.00 0.00 0.00 0.33
September 4049.21 08-SEP-06:01 45364.41 1512.00 4158.42 0.00 0.00 0.00 0.00 0.00 8.33
October 4043.72 20-OCT-06:01 45364.41 1512.00 4158.42 0.00 0.00 0.00 0.00 0.00 3.73
November 4024.27 02-NOV-06:01 45364.41 1512.00 4158.42 0.00 0.00 0.00 0.00 0.00 23.34
December 3902.50 07-DEC-07:01 45364.41 1512.00 4158.42 0.00 0.00 0.00 0.00 0.00 18.29
                       
Annual Sum or Average                      
Minimum of Months 3884.86   22682.21 756.00 2079.21 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4052.80   45364.41 1512.00 4158.42 0.00 0.00 0.00 0.00 0.00 23.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 CLEAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 630.65 27-JAN-15:04 1360.93 793.80 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
February 622.65 03-FEB-09:54 1360.93 793.80 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
March 627.51 15-MAR-12:34 1360.93 793.80 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
April 601.26 05-APR-09:10 816.56 476.28 748.86 0.00 0.00 0.00 0.00 0.00 0.00
May 587.61 18-MAY-17:01 1512.15 1058.40 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
June 587.96 30-JUN-17:01 1512.15 1058.40 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
July 587.88 21-JUL-17:01 1512.15 1058.40 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
August 587.98 25-AUG-17:01 1512.15 1058.40 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
September 599.99 15-SEP-06:04 2721.86 1587.60 2496.21 0.00 0.00 0.00 0.00 0.00 0.00
October 598.07 13-OCT-17:08 1512.15 1058.40 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
November 605.07 30-NOV-18:09 1512.15 1058.40 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
December 631.43 15-DEC-17:57 1088.75 635.04 998.49 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 587.61   816.56 476.28 748.86 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 631.43   2721.86 1587.60 2496.21 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 760.93 27-JAN-15:04 1782.17 1039.50 1634.43 0.00 0.00 0.00 0.00 0.00 0.00
February 748.51 10-FEB-17:40 1069.30 623.70 980.66 0.00 0.00 0.00 0.00 0.00 0.00
March 754.28 15-MAR-12:34 1782.17 1039.50 1634.43 0.00 0.00 0.00 0.00 0.00 0.00
April 718.36 05-APR-09:10 1069.30 623.70 980.66 0.00 0.00 0.00 0.00 0.00 0.00
May 722.93 18-MAY-17:01 1980.19 1386.00 1634.43 0.00 0.00 0.00 0.00 0.00 0.00
June 723.42 30-JUN-17:01 1980.19 1386.00 1634.43 0.00 0.00 0.00 0.00 0.00 0.00
July 723.54 28-JUL-17:01 1980.19 1386.00 1634.43 0.00 0.00 0.00 0.00 0.00 0.00
August 723.62 25-AUG-17:01 1980.19 1386.00 1634.43 0.00 0.00 0.00 0.00 0.00 0.00
September 722.26 01-SEP-17:01 1782.17 1247.40 1470.98 0.00 0.00 0.00 0.00 0.00 0.00
October 722.26 19-OCT-17:01 1782.17 1247.40 1470.98 0.00 0.00 0.00 0.00 0.00 0.00
November 723.50 30-NOV-18:09 1980.19 1386.00 1634.43 0.00 0.00 0.00 0.00 0.00 0.00
December 760.08 15-DEC-17:57 1425.74 831.60 1307.54 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 718.36   1069.30 623.70 980.66 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 760.93   1980.19 1386.00 1634.43 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 486.75 20-JAN-07:01 680.47 720.92 1372.74 0.00 0.00 0.00 0.00 0.00 0.00
February 491.71 03-FEB-07:01 680.47 720.92 1372.74 0.00 0.00 0.00 0.00 0.00 0.00
March 491.39 10-MAR-07:01 680.47 720.92 1372.74 0.00 0.00 0.00 0.00 0.00 0.00
April 485.77 06-APR-06:01 680.47 720.92 1372.74 0.00 0.00 0.00 0.00 0.00 0.00
May 456.73 05-MAY-06:01 680.47 720.92 1372.74 0.00 0.00 0.00 0.00 0.00 0.00
June 440.09 09-JUN-14:02 272.19 288.37 549.10 0.00 0.00 0.00 0.00 0.00 0.00
July 315.77 17-JUL-14:03 204.14 216.28 411.82 0.00 0.00 0.00 0.00 0.00 0.00
August 428.26 17-AUG-14:02 272.19 288.37 549.10 0.00 0.00 0.00 0.00 0.00 0.00
September 424.24 20-SEP-14:02 272.19 288.37 549.10 0.00 0.00 0.00 0.00 0.00 0.00
October 478.59 27-OCT-06:01 680.47 720.92 1372.74 0.00 0.00 0.00 0.00 0.00 0.00
November 490.55 10-NOV-07:01 680.47 720.92 1372.74 0.00 0.00 0.00 0.00 0.00 0.00
December 492.52 07-DEC-07:01 680.47 720.92 1372.74 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 315.77   204.14 216.28 411.82 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 492.52   680.47 720.92 1372.74 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 36.51 19-JAN-15:05 97.21 102.99 196.11 0.00 0.00 0.00 0.00 0.00 8.00
February 36.52 07-FEB-15:05 97.21 102.99 196.11 0.00 0.00 0.00 0.00 0.00 8.08
March 36.66 30-MAR-14:05 97.21 102.99 196.11 0.00 0.00 0.00 0.00 0.00 2.79
April 36.71 24-APR-12:05 97.21 102.99 196.11 0.00 0.00 0.00 0.00 0.00 4.29
May 84.32 25-MAY-14:05 48.60 51.49 98.05 0.00 0.00 0.00 0.00 1.61 0.00
June 124.68 30-JUN-14:05 48.60 51.49 98.05 0.00 0.00 0.00 0.00 4.50 0.00
July 135.31 21-JUL-14:05 48.60 51.49 98.05 0.00 0.00 0.00 0.00 2.14 0.00
August 135.14 09-AUG-14:05 48.60 51.49 98.05 0.00 0.00 0.00 0.00 1.27 0.00
September 130.24 18-SEP-14:02 97.21 102.99 196.11 0.00 0.00 0.00 0.00 0.00 0.71
October 81.58 20-OCT-14:05 48.60 51.49 98.05 0.00 0.00 0.00 0.00 0.00 1.26
November 53.17 01-NOV-14:02 97.21 102.99 196.11 0.00 0.00 0.00 0.00 0.00 1.69
December 36.64 05-DEC-15:05 97.21 102.99 196.11 0.00 0.00 0.00 0.00 0.00 2.61
                       
Annual Sum or Average                      
Minimum of Months 36.51   48.60 51.49 98.05 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 135.31   97.21 102.99 196.11 0.00 0.00 0.00 0.00 4.50 8.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 595.19 20-JAN-07:01 0.00 1234.80 4853.30 0.00 0.00 0.00 0.00 0.00 13.39
February 592.65 03-FEB-07:01 0.00 1234.80 4853.30 0.00 0.00 0.00 0.00 0.00 8.38
March 592.25 10-MAR-07:01 0.00 1234.80 4853.30 0.00 0.00 0.00 0.00 0.00 0.56
April 596.61 14-APR-06:01 0.00 1234.80 4853.30 0.00 0.00 0.00 0.00 0.00 0.55
May 614.34 19-MAY-06:01 0.00 1111.32 4367.97 0.00 0.00 0.00 0.00 0.00 0.12
June 617.36 09-JUN-06:01 0.00 1234.80 4853.30 0.00 0.00 0.00 0.00 0.00 3.48
July 618.23 27-JUL-06:01 0.00 1234.80 4853.30 0.00 0.00 0.00 0.00 0.00 1.71
August 618.74 25-AUG-06:01 0.00 1234.80 4853.30 0.00 0.00 0.00 0.00 0.00 0.00
September 617.62 08-SEP-06:01 0.00 1234.80 4853.30 0.00 0.00 0.00 0.00 0.00 2.92
October 616.04 20-OCT-06:01 0.00 1234.80 4853.30 0.00 0.00 0.00 0.00 0.00 1.30
November 615.40 02-NOV-06:01 0.00 1234.80 4853.30 0.00 0.00 0.00 0.00 0.00 8.19
December 596.73 07-DEC-07:01 0.00 1234.80 4853.30 0.00 0.00 0.00 0.00 0.00 6.41
                       
Annual Sum or Average                      
Minimum of Months 592.25   0.00 1111.32 4367.97 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 618.74   0.00 1234.80 4853.30 0.00 0.00 0.00 0.00 0.00 13.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3067.86 20-JAN-17:05 0.00 687.96 29011.70 0.00 0.00 0.00 0.00 0.00 19.61
February 3094.48 03-FEB-17:55 0.00 687.96 29011.70 0.00 0.00 0.00 0.00 0.00 11.56
March 2960.87 31-MAR-17:00 0.00 114.66 4835.28 0.00 0.00 0.00 0.00 0.00 11.92
April 3027.60 21-APR-17:00 0.00 114.66 4835.28 0.00 0.00 0.00 0.00 0.00 7.91
May 3198.43 25-MAY-17:00 0.00 114.66 4835.28 0.00 0.00 0.00 0.00 2.24 0.00
June 3264.92 29-JUN-17:00 0.00 114.66 4835.28 0.00 0.00 0.00 0.00 7.88 0.00
July 3280.04 20-JUL-17:00 0.00 114.66 4835.28 0.00 0.00 0.00 0.00 4.05 0.00
August 3322.38 25-AUG-17:00 0.00 114.66 4835.28 0.00 0.00 0.00 0.00 2.82 0.00
September 3313.48 01-SEP-17:00 0.00 114.66 4835.28 0.00 0.00 0.00 0.00 1.29 0.00
October 3211.52 19-OCT-17:00 0.00 229.32 9670.57 0.00 0.00 0.00 0.00 0.00 1.92
November 3089.20 01-NOV-17:00 0.00 114.66 4835.28 0.00 0.00 0.00 0.00 0.00 1.91
December 3112.70 15-DEC-17:53 0.00 458.64 19341.13 0.00 0.00 0.00 0.00 0.00 17.34
                       
Annual Sum or Average                      
Minimum of Months 2960.87   0.00 114.66 4835.28 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3322.38   0.00 687.96 29011.70 0.00 0.00 0.00 0.00 7.88 19.61



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 236.29 20-JAN-07:01 291.63 308.97 588.32 0.00 0.00 0.00 0.00 0.00 0.00
February 236.35 03-FEB-07:01 291.63 308.97 588.32 0.00 0.00 0.00 0.00 0.00 0.00
March 236.27 10-MAR-07:01 291.63 308.97 588.32 0.00 0.00 0.00 0.00 0.00 0.00
April 233.28 06-APR-06:01 291.63 308.97 588.32 0.00 0.00 0.00 0.00 0.00 0.00
May 232.67 12-MAY-06:01 291.63 308.97 588.32 0.00 0.00 0.00 0.00 0.00 0.00
June 231.42 09-JUN-06:01 291.63 308.97 588.32 0.00 0.00 0.00 0.00 0.00 0.00
July 231.18 28-JUL-06:01 262.47 278.07 529.49 0.00 0.00 0.00 0.00 0.00 0.00
August 231.88 25-AUG-06:01 291.63 308.97 588.32 0.00 0.00 0.00 0.00 0.00 0.00
September 233.64 15-SEP-06:01 291.63 308.97 588.32 0.00 0.00 0.00 0.00 0.00 0.00
October 237.21 27-OCT-06:01 291.63 308.97 588.32 0.00 0.00 0.00 0.00 0.00 0.00
November 235.69 10-NOV-07:01 291.63 308.97 588.32 0.00 0.00 0.00 0.00 0.00 0.00
December 236.50 07-DEC-07:01 291.63 308.97 588.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 231.18   262.47 278.07 529.49 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 237.21   291.63 308.97 588.32 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 IT HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 98.39 06-JAN-06:20 0.00 354.06 499.71 0.00 0.00 0.00 0.00 0.00 0.00
February 89.62 23-FEB-10:50 0.00 177.03 166.57 0.00 0.00 0.00 0.00 0.00 0.00
March 90.45 09-MAR-07:03 0.00 590.10 555.23 0.00 0.00 0.00 0.00 0.00 0.00
April 93.31 14-APR-08:43 0.00 177.03 166.57 0.00 0.00 0.00 0.00 0.00 0.00
May 95.92 26-MAY-06:05 0.00 236.04 222.09 0.00 0.00 0.00 0.00 0.00 0.00
June 98.35 30-JUN-06:04 0.00 413.07 388.66 0.00 0.00 0.00 0.00 0.00 0.00
July 98.35 21-JUL-06:05 0.00 236.04 222.09 0.00 0.00 0.00 0.00 0.00 0.00
August 97.05 11-AUG-06:03 0.00 531.09 499.71 0.00 0.00 0.00 0.00 0.00 0.00
September 96.66 01-SEP-06:04 0.00 472.08 444.18 0.00 0.00 0.00 0.00 0.00 0.00
October 95.58 27-OCT-06:02 0.00 590.10 555.23 0.00 0.00 0.00 0.00 0.00 0.00
November 92.67 01-NOV-11:10 0.00 236.04 222.09 0.00 0.00 0.00 0.00 0.00 0.00
December 87.77 27-DEC-13:30 0.00 177.03 166.57 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 87.77   0.00 177.03 166.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 98.39   0.00 590.10 555.23 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 248.95 20-JAN-15:02 241.94 256.33 488.09 0.00 0.00 0.00 0.00 0.00 0.00
February 332.06 10-FEB-15:02 362.92 384.49 732.13 0.00 0.00 0.00 0.00 0.00 0.00
March 338.32 03-MAR-15:02 302.43 320.41 610.11 0.00 0.00 0.00 0.00 0.00 0.00
April 232.12 06-APR-14:03 181.46 192.25 366.06 0.00 0.00 0.00 0.00 0.00 0.00
May 265.36 12-MAY-14:03 181.46 192.25 366.06 0.00 0.00 0.00 0.00 0.00 0.00
June 334.32 22-JUN-14:02 241.94 256.33 488.09 0.00 0.00 0.00 0.00 0.00 0.00
July 233.63 21-JUL-14:05 120.97 128.16 244.04 0.00 0.00 0.00 0.00 0.00 0.00
August 331.00 17-AUG-14:02 241.94 256.33 488.09 0.00 0.00 0.00 0.00 0.00 0.00
September 318.19 20-SEP-14:02 241.94 256.33 488.09 0.00 0.00 0.00 0.00 0.00 0.00
October 324.95 27-OCT-14:02 241.94 256.33 488.09 0.00 0.00 0.00 0.00 0.00 0.00
November 324.51 03-NOV-14:02 241.94 256.33 488.09 0.00 0.00 0.00 0.00 0.00 0.00
December 345.79 15-DEC-15:02 362.92 384.49 732.13 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 232.12   120.97 128.16 244.04 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 345.79   362.92 384.49 732.13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 LOBBY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1404.68 27-JAN-15:47 2015.48 1340.16 2032.97 0.00 0.00 0.00 0.00 0.00 0.00
February 1700.23 08-FEB-16:30 671.83 446.72 677.66 0.00 0.00 0.00 0.00 0.00 13.43
March 2093.87 31-MAR-17:00 671.83 446.72 677.66 0.00 0.00 0.00 0.00 0.00 13.11
April 2612.00 21-APR-17:00 671.83 446.72 677.66 0.00 0.00 0.00 0.00 0.00 8.70
May 3637.29 19-MAY-06:01 6046.43 4020.48 6098.90 0.00 0.00 0.00 0.00 0.00 0.38
June 3689.44 30-JUN-06:01 4702.78 3127.04 4743.59 0.00 0.00 0.00 0.00 3.58 0.00
July 3682.63 07-JUL-06:01 5374.60 3573.76 5421.25 0.00 0.00 0.00 0.00 0.00 6.20
August 3712.81 10-AUG-06:01 6046.43 4020.48 6098.90 0.00 0.00 0.00 0.00 0.00 0.36
September 3644.14 01-SEP-06:01 5374.60 3573.76 5421.25 0.00 0.00 0.00 0.00 0.00 3.03
October 3529.23 20-OCT-06:01 6718.25 4467.20 6776.56 0.00 0.00 0.00 0.00 0.00 3.96
November 1773.57 17-NOV-15:40 671.83 446.72 677.66 0.00 0.00 0.00 0.00 0.00 15.16
December 1237.68 08-DEC-15:30 671.83 446.72 677.66 0.00 0.00 0.00 0.00 0.00 16.91
                       
Annual Sum or Average                      
Minimum of Months 1237.68   671.83 446.72 677.66 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3712.81   6718.25 4467.20 6776.56 0.00 0.00 0.00 0.00 3.58 16.91



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 722.78 20-JAN-07:01 0.00 1011.60 951.82 0.00 0.00 0.00 0.00 0.00 0.00
February 733.18 03-FEB-07:01 0.00 1011.60 951.82 0.00 0.00 0.00 0.00 0.00 0.00
March 739.35 24-MAR-06:01 0.00 1011.60 951.82 0.00 0.00 0.00 0.00 0.00 0.00
April 745.81 14-APR-06:01 0.00 1011.60 951.82 0.00 0.00 0.00 0.00 0.00 0.00
May 775.57 19-MAY-06:01 0.00 910.44 856.64 0.00 0.00 0.00 0.00 0.00 0.00
June 776.82 30-JUN-06:01 0.00 708.12 666.28 0.00 0.00 0.00 0.00 0.00 0.00
July 778.60 27-JUL-06:01 0.00 1011.60 951.82 0.00 0.00 0.00 0.00 0.00 0.00
August 779.88 10-AUG-06:01 0.00 910.44 856.64 0.00 0.00 0.00 0.00 0.00 0.00
September 777.56 08-SEP-06:01 0.00 1011.60 951.82 0.00 0.00 0.00 0.00 0.00 0.00
October 776.67 20-OCT-06:01 0.00 1011.60 951.82 0.00 0.00 0.00 0.00 0.00 0.00
November 751.85 10-NOV-07:01 0.00 1011.60 951.82 0.00 0.00 0.00 0.00 0.00 0.00
December 740.18 15-DEC-07:01 0.00 1011.60 951.82 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 722.78   0.00 708.12 666.28 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 779.88   0.00 1011.60 951.82 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 386.70 18-JAN-18:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 6.39
February 402.75 08-FEB-18:09 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 2.35
March 400.46 23-MAR-17:08 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 3.85
April 394.32 27-APR-17:05 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 1.93
May 418.40 18-MAY-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 1.08 0.00
June 420.30 30-JUN-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 2.91 0.00
July 420.41 21-JUL-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.96 0.00
August 421.27 25-AUG-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.96 0.00
September 420.77 01-SEP-17:01 0.00 121.25 96.37 0.00 0.00 0.00 0.00 0.55 0.00
October 418.34 19-OCT-17:01 0.00 121.25 96.37 0.00 0.00 0.00 0.00 0.00 0.40
November 413.54 01-NOV-17:01 0.00 107.78 85.66 0.00 0.00 0.00 0.00 0.00 0.42
December 390.84 05-DEC-18:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 1.74
                       
Annual Sum or Average                      
Minimum of Months 386.70   0.00 107.78 85.66 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 421.27   0.00 134.72 107.08 0.00 0.00 0.00 0.00 2.91 6.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3145.10 20-JAN-07:01 10693.04 3504.60 19610.07 0.00 0.00 0.00 0.00 0.00 42.31
February 3132.22 03-FEB-07:01 10693.04 3504.60 19610.07 0.00 0.00 0.00 0.00 0.00 26.47
March 3135.28 10-MAR-07:01 10693.04 3504.60 19610.07 0.00 0.00 0.00 0.00 0.00 1.77
April 3206.02 18-APR-06:01 9623.74 3154.14 17649.06 0.00 0.00 0.00 0.00 0.00 8.70
May 3233.95 19-MAY-06:01 9623.74 3154.14 17649.06 0.00 0.00 0.00 0.00 0.00 0.40
June 3245.93 09-JUN-06:01 10693.04 3504.60 19610.07 0.00 0.00 0.00 0.00 0.00 11.04
July 3247.67 27-JUL-06:01 10693.04 3504.60 19610.07 0.00 0.00 0.00 0.00 0.00 5.44
August 3254.11 10-AUG-06:01 9623.74 3154.14 17649.06 0.00 0.00 0.00 0.00 0.00 0.37
September 3340.26 13-SEP-05:01 5940.58 2336.40 19610.07 0.00 0.00 0.00 0.00 0.00 13.76
October 3315.53 27-OCT-05:01 5940.58 2336.40 19610.07 0.00 0.00 0.00 0.00 0.00 8.66
November 3243.64 02-NOV-06:01 10693.04 3504.60 19610.07 0.00 0.00 0.00 0.00 0.00 25.95
December 3147.49 07-DEC-07:01 10693.04 3504.60 19610.07 0.00 0.00 0.00 0.00 0.00 20.24
                       
Annual Sum or Average                      
Minimum of Months 3132.22   5940.58 2336.40 17649.06 0.00 0.00 0.00 0.00 0.00 0.37
Maximum of Months 3340.26   10693.04 3504.60 19610.07 0.00 0.00 0.00 0.00 0.00 42.31



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 801.81 27-JAN-07:01 0.00 2090.65 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
February 1071.44 03-FEB-07:01 0.00 2090.65 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
March 1074.75 10-MAR-07:01 0.00 2090.65 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
April 1046.63 07-APR-06:01 0.00 2090.65 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
May 341.18 05-MAY-17:00 0.00 209.06 196.71 0.00 0.00 0.00 0.00 0.00 0.00
June 349.71 30-JUN-17:00 0.00 209.06 196.71 0.00 0.00 0.00 0.00 0.00 0.00
July 348.88 21-JUL-16:57 0.00 627.19 590.13 0.00 0.00 0.00 0.00 0.00 0.00
August 347.65 25-AUG-17:00 0.00 209.06 196.71 0.00 0.00 0.00 0.00 0.00 0.00
September 345.68 15-SEP-17:00 0.00 209.06 196.71 0.00 0.00 0.00 0.00 0.00 0.00
October 432.20 06-OCT-06:01 0.00 2090.65 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
November 1060.98 10-NOV-07:01 0.00 2090.65 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
December 1081.32 15-DEC-07:01 0.00 2090.65 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 341.18   0.00 209.06 196.71 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1081.32   0.00 2090.65 1967.10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1744.35 20-JAN-07:01 5832.57 1911.60 10696.40 0.00 0.00 0.00 0.00 0.00 0.00
February 1739.65 03-FEB-07:01 5832.57 1911.60 10696.40 0.00 0.00 0.00 0.00 0.00 0.00
March 1740.21 10-MAR-07:01 5832.57 1911.60 10696.40 0.00 0.00 0.00 0.00 0.00 0.00
April 1774.50 18-APR-06:01 5249.31 1720.44 9626.76 0.00 0.00 0.00 0.00 0.00 0.00
May 1788.25 19-MAY-06:01 5249.31 1720.44 9626.76 0.00 0.00 0.00 0.00 0.00 0.00
June 1795.78 09-JUN-06:01 5832.57 1911.60 10696.40 0.00 0.00 0.00 0.00 0.00 0.00
July 1796.11 27-JUL-06:01 5832.57 1911.60 10696.40 0.00 0.00 0.00 0.00 0.00 0.00
August 1797.49 10-AUG-06:01 5249.31 1720.44 9626.76 0.00 0.00 0.00 0.00 0.00 0.00
September 1795.81 29-SEP-06:01 5832.57 1911.60 10696.40 0.00 0.00 0.00 0.00 0.00 0.00
October 1795.97 18-OCT-06:01 5832.57 1911.60 10696.40 0.00 0.00 0.00 0.00 0.00 0.00
November 1794.70 02-NOV-06:01 5832.57 1911.60 10696.40 0.00 0.00 0.00 0.00 0.00 0.00
December 1745.21 07-DEC-07:01 5832.57 1911.60 10696.40 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 1739.65   5249.31 1720.44 9626.76 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1797.49   5832.57 1911.60 10696.40 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 MED GAS

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 61.91 18-JAN-18:01 0.00 85.71 27.83 0.00 0.00 0.00 0.00 0.00 11.59
February 62.28 07-FEB-18:01 0.00 85.71 27.83 0.00 0.00 0.00 0.00 0.00 5.34
March 62.08 28-MAR-17:01 0.00 77.14 25.04 0.00 0.00 0.00 0.00 0.00 2.96
April 62.35 14-APR-17:01 0.00 68.57 22.26 0.00 0.00 0.00 0.00 0.00 1.84
May 67.84 18-MAY-17:01 0.00 85.71 27.83 0.00 0.00 0.00 0.00 1.97 0.00
June 68.56 29-JUN-17:01 0.00 85.71 27.83 0.00 0.00 0.00 0.00 4.92 0.00
July 70.98 21-JUL-06:05 0.00 51.43 22.26 0.00 0.00 0.00 0.00 0.00 0.39
August 71.79 09-AUG-06:05 0.00 51.43 22.26 0.00 0.00 0.00 0.00 0.00 0.85
September 68.50 01-SEP-17:01 0.00 77.14 25.04 0.00 0.00 0.00 0.00 0.98 0.00
October 67.73 19-OCT-17:01 0.00 77.14 25.04 0.00 0.00 0.00 0.00 0.00 0.73
November 67.42 01-NOV-17:01 0.00 68.57 22.26 0.00 0.00 0.00 0.00 0.00 0.78
December 62.97 05-DEC-18:01 0.00 85.71 27.83 0.00 0.00 0.00 0.00 0.00 3.16
                       
Annual Sum or Average                      
Minimum of Months 61.91   0.00 51.43 22.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 71.79   0.00 85.71 27.83 0.00 0.00 0.00 0.00 4.92 11.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1895.93 20-JAN-07:01 3629.15 1421.28 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
February 1888.90 03-FEB-07:01 3629.15 1421.28 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
March 1902.12 30-MAR-05:01 2016.20 947.52 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
April 2136.81 14-APR-05:01 2016.20 947.52 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
May 2216.53 26-MAY-05:01 2016.20 947.52 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
June 2230.20 29-JUN-05:01 2016.20 947.52 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
July 2231.88 21-JUL-05:01 2016.20 947.52 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
August 2231.65 09-AUG-05:01 2016.20 947.52 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
September 2228.06 01-SEP-05:01 2016.20 947.52 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
October 2182.91 27-OCT-05:01 2016.20 947.52 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
November 2111.40 14-NOV-06:01 2016.20 947.52 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
December 1912.74 06-DEC-06:01 2016.20 947.52 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 1888.90   2016.20 947.52 16639.88 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2231.88   3629.15 1421.28 16639.88 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 114.47 30-JAN-07:02 0.00 619.61 582.99 0.00 0.00 0.00 0.00 0.00 0.00
February 114.29 10-FEB-18:00 0.00 61.96 58.30 0.00 0.00 0.00 0.00 0.00 0.00
March 121.87 31-MAR-17:00 0.00 61.96 58.30 0.00 0.00 0.00 0.00 0.00 0.00
April 139.25 14-APR-17:00 0.00 61.96 58.30 0.00 0.00 0.00 0.00 0.00 0.00
May 354.61 19-MAY-06:01 0.00 557.65 524.69 0.00 0.00 0.00 0.00 0.00 0.00
June 430.79 30-JUN-06:01 0.00 433.72 408.09 0.00 0.00 0.00 0.00 0.00 0.00
July 426.50 14-JUL-06:02 0.00 371.76 349.79 0.00 0.00 0.00 0.00 0.00 0.00
August 432.78 10-AUG-06:01 0.00 557.65 524.69 0.00 0.00 0.00 0.00 0.00 0.00
September 430.59 01-SEP-06:01 0.00 495.69 466.39 0.00 0.00 0.00 0.00 0.00 0.00
October 421.59 27-OCT-06:01 0.00 619.61 582.99 0.00 0.00 0.00 0.00 0.00 0.00
November 340.14 10-NOV-07:01 0.00 619.61 582.99 0.00 0.00 0.00 0.00 0.00 0.00
December 271.09 01-DEC-07:01 0.00 619.61 582.99 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 114.29   0.00 61.96 58.30 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 432.78   0.00 619.61 582.99 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5068.04 19-JAN-06:01 5280.51 1935.65 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
February 5145.44 21-FEB-06:01 5280.51 1935.65 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
March 5112.44 28-MAR-05:01 5280.51 1935.65 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
April 5516.43 14-APR-05:01 5280.51 1935.65 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
May 5720.69 26-MAY-05:01 5280.51 1935.65 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
June 5731.22 29-JUN-05:01 5280.51 1935.65 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
July 5734.35 21-JUL-05:01 5280.51 1935.65 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
August 5734.12 10-AUG-05:01 5280.51 1935.65 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
September 5725.95 01-SEP-05:01 5280.51 1935.65 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
October 5710.51 20-OCT-05:01 5280.51 1935.65 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
November 5674.57 01-NOV-05:01 5280.51 1935.65 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
December 5096.44 28-DEC-06:01 5280.51 1935.65 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 5068.04   5280.51 1935.65 43580.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5734.35   5280.51 1935.65 43580.63 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 106.07 18-JAN-18:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 6.43
February 106.52 07-FEB-18:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 2.97
March 106.87 24-MAR-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 7.61
April 106.90 15-APR-14:01 0.00 53.89 85.66 0.00 0.00 0.00 0.00 0.00 7.82
May 117.44 19-MAY-06:03 0.00 181.87 192.74 0.00 0.00 0.00 0.00 0.00 0.08
June 115.44 21-JUN-06:04 0.00 161.66 171.33 0.00 0.00 0.00 0.00 0.00 0.61
July 118.94 21-JUL-06:05 0.00 80.83 85.66 0.00 0.00 0.00 0.00 0.00 0.22
August 119.12 09-AUG-06:05 0.00 80.83 85.66 0.00 0.00 0.00 0.00 0.00 0.45
September 117.51 08-SEP-06:03 0.00 202.08 214.16 0.00 0.00 0.00 0.00 0.00 2.15
October 116.65 20-OCT-06:03 0.00 202.08 214.16 0.00 0.00 0.00 0.00 0.00 1.00
November 113.59 01-NOV-17:01 0.00 107.78 85.66 0.00 0.00 0.00 0.00 0.00 0.44
December 107.27 05-DEC-18:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 1.75
                       
Annual Sum or Average                      
Minimum of Months 106.07   0.00 53.89 85.66 0.00 0.00 0.00 0.00 0.00 0.08
Maximum of Months 119.12   0.00 202.08 214.16 0.00 0.00 0.00 0.00 0.00 7.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 953.36 20-JAN-07:01 3931.58 1916.46 3605.64 0.00 0.00 0.00 0.00 0.00 0.00
February 953.17 03-FEB-07:01 3931.58 1916.46 3605.64 0.00 0.00 0.00 0.00 0.00 0.00
March 952.93 10-MAR-07:01 3931.58 1916.46 3605.64 0.00 0.00 0.00 0.00 0.00 0.00
April 968.76 18-APR-06:01 3538.42 1724.81 3245.08 0.00 0.00 0.00 0.00 0.00 0.00
May 974.96 11-MAY-06:01 3931.58 1916.46 3605.64 0.00 0.00 0.00 0.00 0.00 0.00
June 979.05 09-JUN-06:01 3931.58 1916.46 3605.64 0.00 0.00 0.00 0.00 0.00 0.00
July 978.73 27-JUL-06:01 3931.58 1916.46 3605.64 0.00 0.00 0.00 0.00 0.00 0.00
August 979.26 25-AUG-06:01 3931.58 1916.46 3605.64 0.00 0.00 0.00 0.00 0.00 0.00
September 979.57 29-SEP-06:01 3931.58 1916.46 3605.64 0.00 0.00 0.00 0.00 0.00 0.00
October 980.50 18-OCT-06:01 3931.58 1916.46 3605.64 0.00 0.00 0.00 0.00 0.00 0.00
November 978.99 02-NOV-06:01 3931.58 1916.46 3605.64 0.00 0.00 0.00 0.00 0.00 0.00
December 954.06 07-DEC-07:01 3931.58 1916.46 3605.64 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 952.93   3538.42 1724.81 3245.08 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 980.50   3931.58 1916.46 3605.64 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 673.62 27-JAN-14:07 0.00 627.19 590.13 0.00 0.00 0.00 0.00 0.00 0.00
February 407.34 28-FEB-16:00 0.00 209.06 196.71 0.00 0.00 0.00 0.00 0.00 0.00
March 362.69 22-MAR-06:03 0.00 2090.65 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
April 376.56 15-APR-11:04 0.00 464.59 786.84 0.00 0.00 0.00 0.00 0.00 0.00
May 397.90 25-MAY-06:04 0.00 1463.45 1376.97 0.00 0.00 0.00 0.00 0.00 0.00
June 393.08 28-JUN-06:05 0.00 836.26 786.84 0.00 0.00 0.00 0.00 0.00 0.00
July 392.90 07-JUL-06:04 0.00 1672.52 1573.68 0.00 0.00 0.00 0.00 0.00 0.00
August 393.99 23-AUG-06:04 0.00 1463.45 1376.97 0.00 0.00 0.00 0.00 0.00 0.00
September 394.20 22-SEP-06:03 0.00 2090.65 1967.10 0.00 0.00 0.00 0.00 0.00 0.00
October 410.67 20-OCT-15:50 0.00 209.06 196.71 0.00 0.00 0.00 0.00 0.00 0.00
November 520.26 29-NOV-13:40 0.00 209.06 196.71 0.00 0.00 0.00 0.00 0.00 0.00
December 451.74 20-DEC-13:40 0.00 209.06 196.71 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 362.69   0.00 209.06 196.71 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 673.62   0.00 2090.65 1967.10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 156.49 20-JAN-07:01 0.00 123.98 53.66 0.00 0.00 0.00 0.00 0.00 0.00
February 161.82 03-FEB-07:01 0.00 123.98 53.66 0.00 0.00 0.00 0.00 0.00 0.00
March 161.83 10-MAR-07:01 0.00 123.98 53.66 0.00 0.00 0.00 0.00 0.00 0.00
April 157.13 06-APR-06:01 0.00 123.98 53.66 0.00 0.00 0.00 0.00 0.00 0.00
May 139.43 05-MAY-06:01 0.00 123.98 53.66 0.00 0.00 0.00 0.00 0.00 0.00
June 52.81 09-JUN-17:00 0.00 12.40 5.37 0.00 0.00 0.00 0.00 0.00 0.00
July 52.31 28-JUL-17:00 0.00 12.40 5.37 0.00 0.00 0.00 0.00 0.00 0.00
August 52.73 25-AUG-17:00 0.00 12.40 5.37 0.00 0.00 0.00 0.00 0.00 0.00
September 103.25 15-SEP-06:01 0.00 123.98 53.66 0.00 0.00 0.00 0.00 0.00 0.00
October 159.51 27-OCT-06:01 0.00 123.98 53.66 0.00 0.00 0.00 0.00 0.00 0.00
November 158.85 10-NOV-07:01 0.00 123.98 53.66 0.00 0.00 0.00 0.00 0.00 0.00
December 162.77 15-DEC-07:01 0.00 123.98 53.66 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 52.31   0.00 12.40 5.37 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 162.77   0.00 123.98 53.66 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1299.61 20-JAN-07:01 5638.15 2748.33 5170.73 0.00 0.00 0.00 0.00 0.00 0.00
February 1296.87 03-FEB-07:01 5638.15 2748.33 5170.73 0.00 0.00 0.00 0.00 0.00 0.00
March 1297.13 10-MAR-07:01 5638.15 2748.33 5170.73 0.00 0.00 0.00 0.00 0.00 0.00
April 1297.86 14-APR-06:01 5638.15 2748.33 5170.73 0.00 0.00 0.00 0.00 0.00 0.00
May 1331.10 19-MAY-06:01 5074.33 2473.50 4653.65 0.00 0.00 0.00 0.00 0.00 0.00
June 1336.90 09-JUN-06:01 5638.15 2748.33 5170.73 0.00 0.00 0.00 0.00 0.00 0.00
July 1336.61 27-JUL-06:01 5638.15 2748.33 5170.73 0.00 0.00 0.00 0.00 0.00 0.00
August 1337.54 25-AUG-06:01 5638.15 2748.33 5170.73 0.00 0.00 0.00 0.00 0.00 0.00
September 1337.01 29-SEP-06:01 5638.15 2748.33 5170.73 0.00 0.00 0.00 0.00 0.00 0.00
October 1337.73 18-OCT-06:01 5638.15 2748.33 5170.73 0.00 0.00 0.00 0.00 0.00 0.00
November 1335.34 02-NOV-06:01 5638.15 2748.33 5170.73 0.00 0.00 0.00 0.00 0.00 0.00
December 1299.98 07-DEC-07:01 5638.15 2748.33 5170.73 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 1296.87   5074.33 2473.50 4653.65 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1337.73   5638.15 2748.33 5170.73 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 165.61 28-JAN-15:01 0.00 60.62 96.37 0.00 0.00 0.00 0.00 0.00 0.00
February 167.46 28-FEB-18:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 0.00
March 169.88 24-MAR-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 0.00
April 166.01 14-APR-17:01 0.00 107.78 85.66 0.00 0.00 0.00 0.00 0.00 0.00
May 172.28 18-MAY-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 0.00
June 173.50 30-JUN-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 0.00
July 173.05 21-JUL-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 0.00
August 173.74 25-AUG-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 0.00
September 173.78 15-SEP-17:01 0.00 107.78 85.66 0.00 0.00 0.00 0.00 0.00 0.00
October 174.83 27-OCT-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 0.00
November 170.46 01-NOV-17:01 0.00 107.78 85.66 0.00 0.00 0.00 0.00 0.00 0.00
December 167.51 15-DEC-18:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 165.61   0.00 60.62 85.66 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 174.83   0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1463.83 20-JAN-07:01 2608.45 2763.54 5262.18 0.00 0.00 0.00 0.00 0.00 0.00
February 1472.13 03-FEB-07:01 2608.45 2763.54 5262.18 0.00 0.00 0.00 0.00 0.00 0.00
March 1474.63 10-MAR-07:01 2608.45 2763.54 5262.18 0.00 0.00 0.00 0.00 0.00 0.00
April 1465.47 14-APR-06:01 2608.45 2763.54 5262.18 0.00 0.00 0.00 0.00 0.00 0.00
May 1513.31 19-MAY-06:01 2347.61 2487.18 4735.96 0.00 0.00 0.00 0.00 0.00 0.00
June 1518.26 30-JUN-06:01 1825.92 1934.47 3683.53 0.00 0.00 0.00 0.00 0.00 0.00
July 1519.42 28-JUL-06:01 2347.61 2487.18 4735.96 0.00 0.00 0.00 0.00 0.00 0.00
August 1524.36 10-AUG-06:01 2347.61 2487.18 4735.96 0.00 0.00 0.00 0.00 0.00 0.00
September 1519.83 01-SEP-06:01 2086.76 2210.83 4209.75 0.00 0.00 0.00 0.00 0.00 0.00
October 1518.04 27-OCT-06:02 2608.45 2763.54 5262.18 0.00 0.00 0.00 0.00 0.00 0.00
November 1485.68 02-NOV-06:01 2608.45 2763.54 5262.18 0.00 0.00 0.00 0.00 0.00 0.00
December 1479.06 07-DEC-07:01 2608.45 2763.54 5262.18 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 1463.83   1825.92 1934.47 3683.53 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1524.36   2608.45 2763.54 5262.18 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7646.87 19-JAN-06:01 5520.54 6237.60 18226.32 16089.88 0.00 0.00 0.00 0.00 24.25
February 8010.37 09-FEB-06:01 5520.54 6237.60 18226.32 16089.88 0.00 0.00 0.00 0.00 24.11
March 7992.76 30-MAR-05:01 5520.54 6237.60 18226.32 16089.88 0.00 0.00 0.00 0.00 38.37
April 8041.73 14-APR-05:01 5520.54 6237.60 18226.32 16089.88 0.00 0.00 0.00 0.00 0.00
May 7940.74 03-MAY-05:01 5520.54 6237.60 18226.32 16089.88 0.00 0.00 0.00 0.00 2.84
June 7889.74 30-JUN-05:01 5520.54 6237.60 18226.32 16089.88 0.00 0.00 0.00 8.84 0.00
July 7901.62 14-JUL-05:01 5520.54 6237.60 18226.32 16089.88 0.00 0.00 0.00 0.00 3.45
August 7959.20 09-AUG-05:01 5520.54 6237.60 18226.32 16089.88 0.00 0.00 0.00 0.00 2.75
September 8314.79 14-SEP-05:01 5520.54 6237.60 18226.32 16089.88 0.00 0.00 0.00 0.00 12.63
October 8204.67 27-OCT-05:01 5520.54 6237.60 18226.32 16089.88 0.00 0.00 0.00 0.00 14.98
November 8006.03 15-NOV-06:01 5520.54 6237.60 18226.32 16089.88 0.00 0.00 0.00 0.00 19.54
December 7898.41 28-DEC-06:01 5520.54 6237.60 18226.32 16089.88 0.00 0.00 0.00 0.00 24.00
                       
Annual Sum or Average                      
Minimum of Months 7646.87   5520.54 6237.60 18226.32 16089.88 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8314.79   5520.54 6237.60 18226.32 16089.88 0.00 0.00 0.00 8.84 38.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8328.77 19-JAN-06:01 5760.56 6508.80 19018.77 16789.44 0.00 0.00 0.00 0.00 13.76
February 8379.04 09-FEB-06:01 5760.56 6508.80 19018.77 16789.44 0.00 0.00 0.00 0.00 13.47
March 8387.60 31-MAR-05:01 5760.56 6508.80 19018.77 16789.44 0.00 0.00 0.00 0.00 14.00
April 8397.09 14-APR-05:01 5760.56 6508.80 19018.77 16789.44 0.00 0.00 0.00 0.00 0.00
May 8340.81 03-MAY-05:01 5760.56 6508.80 19018.77 16789.44 0.00 0.00 0.00 0.00 1.59
June 8322.57 29-JUN-05:01 5760.56 6508.80 19018.77 16789.44 0.00 0.00 0.00 1.31 0.00
July 8409.09 14-JUL-05:01 5760.56 6508.80 19018.77 16789.44 0.00 0.00 0.00 0.00 2.04
August 8286.41 09-AUG-05:01 5760.56 6508.80 19018.77 16789.44 0.00 0.00 0.00 0.00 1.52
September 8685.10 14-SEP-05:01 5760.56 6508.80 19018.77 16789.44 0.00 0.00 0.00 0.00 7.06
October 8564.04 27-OCT-05:01 5760.56 6508.80 19018.77 16789.44 0.00 0.00 0.00 0.00 8.36
November 8371.47 14-NOV-06:01 5760.56 6508.80 19018.77 16789.44 0.00 0.00 0.00 0.00 19.19
December 8386.18 28-DEC-06:01 5760.56 6508.80 19018.77 16789.44 0.00 0.00 0.00 0.00 13.49
                       
Annual Sum or Average                      
Minimum of Months 8286.41   5760.56 6508.80 19018.77 16789.44 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8685.10   5760.56 6508.80 19018.77 16789.44 0.00 0.00 0.00 1.31 19.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6952.06 27-JAN-15:04 5141.30 4840.92 9430.14 8324.76 0.00 0.00 0.00 0.00 0.00
February 6914.42 03-FEB-07:01 10282.60 9681.84 18860.28 16649.53 0.00 0.00 0.00 0.00 0.00
March 6918.22 15-MAR-12:44 5141.30 4840.92 9430.14 8324.76 0.00 0.00 0.00 0.00 0.00
April 6777.59 05-APR-06:02 10282.60 9681.84 18860.28 16649.53 0.00 0.00 0.00 0.00 0.00
May 6196.79 02-MAY-05:01 5712.56 6454.56 18860.28 16649.53 0.00 0.00 0.00 0.00 0.00
June 5390.99 30-JUN-15:10 1028.26 968.18 1886.03 1664.95 0.00 0.00 0.00 0.00 0.00
July 5388.55 14-JUL-15:10 1028.26 968.18 1886.03 1664.95 0.00 0.00 0.00 0.00 0.00
August 5387.47 25-AUG-15:10 1028.26 968.18 1886.03 1664.95 0.00 0.00 0.00 0.00 0.00
September 6514.63 13-SEP-05:01 5712.56 6454.56 18860.28 16649.53 0.00 0.00 0.00 0.00 0.00
October 6721.73 13-OCT-17:08 5712.56 6454.56 9430.14 8324.76 0.00 0.00 0.00 0.00 0.00
November 6722.34 08-NOV-18:09 5712.56 6454.56 9430.14 8324.76 0.00 0.00 0.00 0.00 0.00
December 6937.92 15-DEC-07:01 10282.60 9681.84 18860.28 16649.53 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 5387.47   1028.26 968.18 1886.03 1664.95 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6952.06   10282.60 9681.84 18860.28 16649.53 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 PACU

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 628.50 27-JAN-15:04 1166.51 607.50 1604.46 0.00 0.00 0.00 0.00 0.00 0.00
February 610.60 10-FEB-13:37 699.91 364.50 962.68 0.00 0.00 0.00 0.00 0.00 0.00
March 616.91 15-MAR-12:34 1166.51 607.50 1604.46 0.00 0.00 0.00 0.00 0.00 0.00
April 587.87 05-APR-09:10 699.91 364.50 962.68 0.00 0.00 0.00 0.00 0.00 0.00
May 589.53 18-MAY-17:01 1296.13 810.00 1604.46 0.00 0.00 0.00 0.00 0.00 0.00
June 589.98 30-JUN-17:01 1296.13 810.00 1604.46 0.00 0.00 0.00 0.00 0.00 0.00
July 590.06 21-JUL-17:01 1296.13 810.00 1604.46 0.00 0.00 0.00 0.00 0.00 0.00
August 590.08 25-AUG-17:01 1296.13 810.00 1604.46 0.00 0.00 0.00 0.00 0.00 0.00
September 588.84 01-SEP-17:01 1166.51 729.00 1444.01 0.00 0.00 0.00 0.00 0.00 0.00
October 589.24 19-OCT-17:01 1166.51 729.00 1444.01 0.00 0.00 0.00 0.00 0.00 0.00
November 591.35 30-NOV-18:09 1296.13 810.00 1604.46 0.00 0.00 0.00 0.00 0.00 0.00
December 616.35 15-DEC-17:08 933.21 486.00 1283.57 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 587.87   699.91 364.50 962.68 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 628.50   1296.13 810.00 1604.46 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 392.56 06-JAN-06:20 0.00 1335.32 1884.61 0.00 0.00 0.00 0.00 0.00 0.00
February 356.44 22-FEB-07:02 0.00 2225.53 2094.01 0.00 0.00 0.00 0.00 0.00 0.00
March 369.36 22-MAR-06:03 0.00 2225.53 2094.01 0.00 0.00 0.00 0.00 0.00 0.00
April 385.34 18-APR-06:02 0.00 2002.97 1884.61 0.00 0.00 0.00 0.00 0.00 0.00
May 397.36 23-MAY-06:03 0.00 2002.97 1884.61 0.00 0.00 0.00 0.00 0.00 0.00
June 447.25 30-JUN-17:00 0.00 222.55 209.40 0.00 0.00 0.00 0.00 0.00 0.00
July 407.64 21-JUL-16:57 0.00 667.66 628.20 0.00 0.00 0.00 0.00 0.00 0.00
August 400.54 25-AUG-17:00 0.00 222.55 209.40 0.00 0.00 0.00 0.00 0.00 0.00
September 399.25 26-SEP-06:03 0.00 2225.53 2094.01 0.00 0.00 0.00 0.00 0.00 0.00
October 398.47 03-OCT-06:03 0.00 2225.53 2094.01 0.00 0.00 0.00 0.00 0.00 0.00
November 398.90 01-NOV-06:03 0.00 2225.53 2094.01 0.00 0.00 0.00 0.00 0.00 0.00
December 371.39 06-DEC-07:03 0.00 2225.53 2094.01 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 356.44   0.00 222.55 209.40 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 447.25   0.00 2225.53 2094.01 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 929.64 28-JAN-15:01 408.28 347.00 1684.94 0.00 0.00 0.00 0.00 0.00 8.94
February 907.22 08-FEB-18:01 1134.11 771.12 1872.16 0.00 0.00 0.00 0.00 0.00 1.50
March 923.60 31-MAR-17:01 907.29 616.90 1497.73 0.00 0.00 0.00 0.00 0.00 2.13
April 951.28 14-APR-17:01 907.29 616.90 1497.73 0.00 0.00 0.00 0.00 0.00 0.67
May 1021.58 18-MAY-17:01 1134.11 771.12 1872.16 0.00 0.00 0.00 0.00 0.73 0.00
June 1025.03 30-JUN-17:01 1134.11 771.12 1872.16 0.00 0.00 0.00 0.00 1.96 0.00
July 1023.41 21-JUL-17:01 1134.11 771.12 1872.16 0.00 0.00 0.00 0.00 0.66 0.00
August 1023.81 25-AUG-17:01 1134.11 771.12 1872.16 0.00 0.00 0.00 0.00 0.65 0.00
September 1019.98 01-SEP-17:01 1020.70 694.01 1684.94 0.00 0.00 0.00 0.00 0.38 0.00
October 1015.39 19-OCT-17:01 1020.70 694.01 1684.94 0.00 0.00 0.00 0.00 0.00 0.24
November 992.43 01-NOV-17:01 907.29 616.90 1497.73 0.00 0.00 0.00 0.00 0.00 0.27
December 911.86 15-DEC-18:01 1134.11 771.12 1872.16 0.00 0.00 0.00 0.00 0.00 3.27
                       
Annual Sum or Average                      
Minimum of Months 907.22   408.28 347.00 1497.73 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1025.03   1134.11 771.12 1872.16 0.00 0.00 0.00 0.00 1.96 8.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1720.47 18-JAN-18:01 2028.20 1379.04 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
February 1728.92 07-FEB-18:10 2028.20 1379.04 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
March 1738.20 24-MAR-17:01 2028.20 1379.04 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
April 1728.17 26-APR-17:01 2028.20 1379.04 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
May 1826.64 18-MAY-17:01 2028.20 1379.04 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
June 1827.95 30-JUN-17:01 2028.20 1379.04 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
July 1827.54 21-JUL-17:01 2028.20 1379.04 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
August 1827.79 25-AUG-17:01 2028.20 1379.04 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
September 1822.19 01-SEP-17:01 1825.38 1241.14 3013.29 0.00 0.00 0.00 0.00 0.00 0.00
October 1821.91 27-OCT-17:01 2028.20 1379.04 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
November 1812.73 01-NOV-17:01 1622.56 1103.23 2678.48 0.00 0.00 0.00 0.00 0.00 0.00
December 1734.73 05-DEC-18:01 2028.20 1379.04 3348.10 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 1720.47   1622.56 1103.23 2678.48 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1827.95   2028.20 1379.04 3348.10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 130.75 21-JAN-15:01 0.00 60.62 96.37 0.00 0.00 0.00 0.00 0.00 9.74
February 132.00 04-FEB-15:01 0.00 53.89 85.66 0.00 0.00 0.00 0.00 0.00 4.16
March 132.22 28-MAR-17:01 0.00 121.25 96.37 0.00 0.00 0.00 0.00 0.00 1.63
April 134.23 15-APR-14:01 0.00 53.89 85.66 0.00 0.00 0.00 0.00 0.00 7.77
May 145.32 18-MAY-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 1.07 0.00
June 150.90 29-JUN-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 2.63 0.00
July 146.16 21-JUL-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.93 0.00
August 146.25 25-AUG-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.94 0.00
September 145.95 01-SEP-17:01 0.00 121.25 96.37 0.00 0.00 0.00 0.00 0.53 0.00
October 144.27 19-OCT-17:01 0.00 121.25 96.37 0.00 0.00 0.00 0.00 0.00 0.41
November 141.72 01-NOV-17:01 0.00 107.78 85.66 0.00 0.00 0.00 0.00 0.00 0.42
December 131.42 30-DEC-15:01 0.00 53.89 85.66 0.00 0.00 0.00 0.00 0.00 3.15
                       
Annual Sum or Average                      
Minimum of Months 130.75   0.00 53.89 85.66 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 150.90   0.00 134.72 107.08 0.00 0.00 0.00 0.00 2.63 9.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3247.65 28-JAN-15:01 1231.32 1077.30 3810.59 0.00 0.00 0.00 0.00 0.00 41.52
February 3245.19 03-FEB-18:01 3420.33 2394.00 4233.99 0.00 0.00 0.00 0.00 0.00 8.55
March 3253.79 30-MAR-17:01 3420.33 2394.00 4233.99 0.00 0.00 0.00 0.00 0.00 9.97
April 3278.14 13-APR-17:01 3078.30 2154.60 3810.59 0.00 0.00 0.00 0.00 0.00 1.01
May 3547.15 18-MAY-17:01 3420.33 2394.00 4233.99 0.00 0.00 0.00 0.00 3.85 0.00
June 3615.02 30-JUN-17:01 3420.33 2394.00 4233.99 0.00 0.00 0.00 0.00 9.91 0.00
July 3623.07 21-JUL-17:01 3420.33 2394.00 4233.99 0.00 0.00 0.00 0.00 3.59 0.00
August 3606.45 25-AUG-17:01 3420.33 2394.00 4233.99 0.00 0.00 0.00 0.00 3.40 0.00
September 3570.73 01-SEP-17:01 3078.30 2154.60 3810.59 0.00 0.00 0.00 0.00 2.18 0.00
October 3493.95 19-OCT-17:01 3078.30 2154.60 3810.59 0.00 0.00 0.00 0.00 0.00 0.62
November 3427.32 01-NOV-17:01 2736.27 1915.20 3387.19 0.00 0.00 0.00 0.00 0.00 1.05
December 3310.07 15-DEC-18:01 3420.33 2394.00 4233.99 0.00 0.00 0.00 0.00 0.00 15.37
                       
Annual Sum or Average                      
Minimum of Months 3245.19   1231.32 1077.30 3387.19 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3623.07   3420.33 2394.00 4233.99 0.00 0.00 0.00 0.00 9.91 41.52



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2456.14 20-JAN-07:01 16493.20 3848.04 5545.45 0.00 0.00 0.00 0.00 0.00 24.98
February 2447.27 03-FEB-07:01 16493.20 3848.04 5545.45 0.00 0.00 0.00 0.00 0.00 15.63
March 2449.15 10-MAR-07:01 16493.20 3848.04 5545.45 0.00 0.00 0.00 0.00 0.00 1.05
April 2507.17 18-APR-06:01 14843.88 3463.24 4990.90 0.00 0.00 0.00 0.00 0.00 5.14
May 2528.62 19-MAY-06:01 14843.88 3463.24 4990.90 0.00 0.00 0.00 0.00 0.00 0.24
June 2536.77 09-JUN-06:01 16493.20 3848.04 5545.45 0.00 0.00 0.00 0.00 0.00 6.52
July 2538.39 27-JUL-06:01 16493.20 3848.04 5545.45 0.00 0.00 0.00 0.00 0.00 3.21
August 2543.76 10-AUG-06:01 14843.88 3463.24 4990.90 0.00 0.00 0.00 0.00 0.00 0.22
September 2538.90 08-SEP-06:01 16493.20 3848.04 5545.45 0.00 0.00 0.00 0.00 0.00 5.47
October 2535.02 18-OCT-06:01 16493.20 3848.04 5545.45 0.00 0.00 0.00 0.00 0.00 9.44
November 2532.02 02-NOV-06:01 16493.20 3848.04 5545.45 0.00 0.00 0.00 0.00 0.00 15.31
December 2457.30 07-DEC-07:01 16493.20 3848.04 5545.45 0.00 0.00 0.00 0.00 0.00 11.95
                       
Annual Sum or Average                      
Minimum of Months 2447.27   14843.88 3463.24 4990.90 0.00 0.00 0.00 0.00 0.00 0.22
Maximum of Months 2543.76   16493.20 3848.04 5545.45 0.00 0.00 0.00 0.00 0.00 24.98



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 95.49 30-JAN-07:02 0.00 539.52 507.64 0.00 0.00 0.00 0.00 0.00 0.00
February 92.30 21-FEB-15:05 0.00 215.81 203.06 0.00 0.00 0.00 0.00 0.00 0.00
March 98.78 03-MAR-07:01 0.00 539.52 507.64 0.00 0.00 0.00 0.00 0.00 0.00
April 94.32 21-APR-17:00 0.00 53.95 50.76 0.00 0.00 0.00 0.00 0.00 0.00
May 105.15 26-MAY-17:00 0.00 53.95 50.76 0.00 0.00 0.00 0.00 0.00 0.00
June 118.19 30-JUN-17:00 0.00 53.95 50.76 0.00 0.00 0.00 0.00 0.00 0.00
July 116.06 21-JUL-16:57 0.00 161.86 152.29 0.00 0.00 0.00 0.00 0.00 0.00
August 118.21 25-AUG-17:00 0.00 53.95 50.76 0.00 0.00 0.00 0.00 0.00 0.00
September 116.99 01-SEP-17:00 0.00 53.95 50.76 0.00 0.00 0.00 0.00 0.00 0.00
October 122.49 27-OCT-06:01 0.00 539.52 507.64 0.00 0.00 0.00 0.00 0.00 0.00
November 155.63 10-NOV-07:01 0.00 539.52 507.64 0.00 0.00 0.00 0.00 0.00 0.00
December 153.19 01-DEC-07:01 0.00 539.52 507.64 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 92.30   0.00 53.95 50.76 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 155.63   0.00 539.52 507.64 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3429.15 27-JAN-13:33 6999.08 3645.00 9626.76 0.00 0.00 0.00 0.00 0.00 0.00
February 2897.50 28-FEB-15:05 4666.05 2430.00 6417.84 0.00 0.00 0.00 0.00 0.00 37.81
March 2724.64 31-MAR-14:10 2333.03 1215.00 3208.92 0.00 0.00 0.00 0.00 0.00 23.32
April 2702.40 13-APR-14:10 2333.03 1215.00 3208.92 0.00 0.00 0.00 0.00 0.00 3.72
May 2743.15 18-MAY-17:01 6480.63 4050.00 8022.30 0.00 0.00 0.00 0.00 8.11 0.00
June 2807.37 30-JUN-14:10 2333.03 1215.00 3208.92 0.00 0.00 0.00 0.00 25.25 0.00
July 2833.00 27-JUL-06:03 11665.14 6075.00 16044.60 0.00 0.00 0.00 0.00 0.00 9.13
August 2918.32 25-AUG-14:10 2333.03 1215.00 3208.92 0.00 0.00 0.00 0.00 9.91 0.00
September 3036.70 01-SEP-14:10 2333.03 1215.00 3208.92 0.00 0.00 0.00 0.00 5.46 0.00
October 3094.34 19-OCT-14:10 2333.03 1215.00 3208.92 0.00 0.00 0.00 0.00 0.00 0.87
November 2896.40 17-NOV-13:10 2333.03 1215.00 3208.92 0.00 0.00 0.00 0.00 0.00 33.48
December 2745.45 08-DEC-13:10 5832.57 3037.50 8022.30 0.00 0.00 0.00 0.00 0.00 37.94
                       
Annual Sum or Average                      
Minimum of Months 2702.40   2333.03 1215.00 3208.92 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3429.15   11665.14 6075.00 16044.60 0.00 0.00 0.00 0.00 25.25 37.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 365.46 20-JAN-15:02 257.07 272.35 518.59 0.00 0.00 0.00 0.00 0.00 10.59
February 378.69 28-FEB-15:02 257.07 272.35 518.59 0.00 0.00 0.00 0.00 0.00 6.02
March 376.29 17-MAR-14:02 321.33 340.44 648.24 0.00 0.00 0.00 0.00 0.00 5.44
April 306.10 19-APR-14:03 192.80 204.26 388.94 0.00 0.00 0.00 0.00 0.00 9.85
May 315.21 22-MAY-14:02 257.07 272.35 518.59 0.00 0.00 0.00 0.00 0.00 0.61
June 388.63 30-JUN-06:01 449.86 476.61 907.54 0.00 0.00 0.00 0.00 1.29 0.00
July 321.32 21-JUL-14:05 128.53 136.17 259.30 0.00 0.00 0.00 0.00 1.66 0.00
August 390.72 10-AUG-06:01 578.40 612.78 1166.83 0.00 0.00 0.00 0.00 0.00 0.11
September 389.08 01-SEP-06:01 514.13 544.70 1037.18 0.00 0.00 0.00 0.00 0.00 0.91
October 390.76 27-OCT-14:02 257.07 272.35 518.59 0.00 0.00 0.00 0.00 0.00 0.25
November 372.09 01-NOV-14:02 257.07 272.35 518.59 0.00 0.00 0.00 0.00 0.00 1.32
December 385.17 15-DEC-15:02 385.60 408.52 777.89 0.00 0.00 0.00 0.00 0.00 3.04
                       
Annual Sum or Average                      
Minimum of Months 306.10   128.53 136.17 259.30 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 390.76   578.40 612.78 1166.83 0.00 0.00 0.00 0.00 1.66 10.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 SCRUB

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 44.70 06-JAN-05:00 0.00 11.80 16.66 0.00 0.00 0.00 0.00 0.00 0.00
February 41.36 10-FEB-13:37 0.00 106.22 99.94 0.00 0.00 0.00 0.00 0.00 0.00
March 42.16 17-MAR-10:40 0.00 106.22 99.94 0.00 0.00 0.00 0.00 0.00 0.00
April 50.23 21-APR-07:55 0.00 70.81 66.63 0.00 0.00 0.00 0.00 0.00 0.00
May 52.51 18-MAY-16:40 0.00 35.41 33.31 0.00 0.00 0.00 0.00 0.00 0.00
June 63.10 30-JUN-16:10 0.00 35.41 33.31 0.00 0.00 0.00 0.00 0.00 0.00
July 74.51 14-JUL-07:12 0.00 283.25 266.51 0.00 0.00 0.00 0.00 0.00 0.00
August 79.44 25-AUG-07:43 0.00 106.22 99.94 0.00 0.00 0.00 0.00 0.00 0.00
September 67.92 01-SEP-08:20 0.00 70.81 66.63 0.00 0.00 0.00 0.00 0.00 0.00
October 49.23 20-OCT-15:20 0.00 35.41 33.31 0.00 0.00 0.00 0.00 0.00 0.00
November 42.44 01-NOV-06:03 0.00 354.06 333.14 0.00 0.00 0.00 0.00 0.00 0.00
December 41.61 15-DEC-17:57 0.00 141.62 133.25 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 41.36   0.00 11.80 16.66 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 79.44   0.00 354.06 333.14 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 SOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 613.31 27-JAN-15:04 1360.93 793.80 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
February 603.46 10-FEB-17:40 816.56 476.28 748.86 0.00 0.00 0.00 0.00 0.00 0.00
March 609.10 15-MAR-12:34 1360.93 793.80 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
April 580.45 05-APR-09:10 816.56 476.28 748.86 0.00 0.00 0.00 0.00 0.00 0.00
May 582.00 18-MAY-17:01 1512.15 1058.40 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
June 582.41 30-JUN-17:01 1512.15 1058.40 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
July 582.27 28-JUL-17:01 1512.15 1058.40 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
August 582.35 25-AUG-17:01 1512.15 1058.40 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
September 581.40 01-SEP-17:01 1360.93 952.56 1123.30 0.00 0.00 0.00 0.00 0.00 0.00
October 581.49 19-OCT-17:01 1360.93 952.56 1123.30 0.00 0.00 0.00 0.00 0.00 0.00
November 585.80 30-NOV-18:09 1512.15 1058.40 1248.11 0.00 0.00 0.00 0.00 0.00 0.00
December 614.01 15-DEC-17:57 1088.75 635.04 998.49 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 580.45   816.56 476.28 748.86 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 614.01   1512.15 1058.40 1248.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 214.87 27-JAN-15:04 604.86 352.80 554.71 0.00 0.00 0.00 0.00 0.00 0.00
February 215.15 10-FEB-17:40 362.92 211.68 332.83 0.00 0.00 0.00 0.00 0.00 0.00
March 212.59 15-MAR-12:34 604.86 352.80 554.71 0.00 0.00 0.00 0.00 0.00 0.00
April 204.57 05-APR-17:09 672.07 470.40 554.71 0.00 0.00 0.00 0.00 0.00 0.00
May 215.60 26-MAY-17:00 120.97 70.56 110.94 0.00 0.00 0.00 0.00 0.00 0.00
June 221.61 30-JUN-17:00 120.97 70.56 110.94 0.00 0.00 0.00 0.00 0.00 0.00
July 221.44 21-JUL-17:00 362.92 211.68 332.83 0.00 0.00 0.00 0.00 0.00 0.00
August 220.17 11-AUG-17:00 120.97 70.56 110.94 0.00 0.00 0.00 0.00 0.00 0.00
September 218.72 01-SEP-17:00 120.97 70.56 110.94 0.00 0.00 0.00 0.00 0.00 0.00
October 212.60 06-OCT-17:00 120.97 70.56 110.94 0.00 0.00 0.00 0.00 0.00 0.00
November 210.23 30-NOV-18:09 672.07 470.40 554.71 0.00 0.00 0.00 0.00 0.00 0.00
December 219.41 15-DEC-17:57 483.89 282.24 443.77 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 204.57   120.97 70.56 110.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 221.61   672.07 470.40 554.71 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 802.10 27-JAN-15:04 1944.19 1134.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00
February 786.82 10-FEB-17:40 1166.51 680.40 1069.81 0.00 0.00 0.00 0.00 0.00 0.00
March 788.72 15-MAR-12:34 1944.19 1134.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00
April 756.85 05-APR-08:58 2333.03 1360.80 2139.61 0.00 0.00 0.00 0.00 0.00 0.00
May 772.30 18-MAY-17:01 2160.21 1512.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00
June 772.96 30-JUN-17:01 2160.21 1512.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00
July 772.90 28-JUL-17:01 2160.21 1512.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00
August 773.22 25-AUG-17:01 2160.21 1512.00 1783.01 0.00 0.00 0.00 0.00 0.00 0.00
September 771.78 01-SEP-17:01 1944.19 1360.80 1604.71 0.00 0.00 0.00 0.00 0.00 0.00
October 771.69 19-OCT-17:01 1944.19 1360.80 1604.71 0.00 0.00 0.00 0.00 0.00 0.00
November 768.26 01-NOV-17:01 1728.17 1209.60 1426.41 0.00 0.00 0.00 0.00 0.00 0.00
December 795.47 15-DEC-17:57 1555.35 907.20 1426.41 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 756.85   1166.51 680.40 1069.81 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 802.10   2333.03 1512.00 2139.61 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1370.07 27-JAN-15:04 3240.32 1687.50 4456.83 0.00 0.00 0.00 0.00 0.00 0.00
February 1406.38 28-FEB-15:30 648.06 337.50 891.37 0.00 0.00 0.00 0.00 0.00 29.84
March 1325.70 31-MAR-15:10 648.06 337.50 891.37 0.00 0.00 0.00 0.00 0.00 21.04
April 1337.62 13-APR-15:10 648.06 337.50 891.37 0.00 0.00 0.00 0.00 0.00 2.64
May 1429.34 18-MAY-16:10 648.06 337.50 891.37 0.00 0.00 0.00 0.00 5.99 0.00
June 1536.65 30-JUN-17:00 648.06 337.50 891.37 0.00 0.00 0.00 0.00 16.28 0.00
July 1520.24 21-JUL-16:07 1944.19 1012.50 2674.10 0.00 0.00 0.00 0.00 8.05 0.00
August 1663.89 25-AUG-17:00 648.06 337.50 891.37 0.00 0.00 0.00 0.00 5.21 0.00
September 1787.14 01-SEP-15:30 648.06 337.50 891.37 0.00 0.00 0.00 0.00 3.92 0.00
October 1812.91 19-OCT-15:00 648.06 337.50 891.37 0.00 0.00 0.00 0.00 0.01 0.00
November 1421.14 17-NOV-13:50 648.06 337.50 891.37 0.00 0.00 0.00 0.00 0.00 28.27
December 1270.43 08-DEC-13:27 1944.19 1012.50 2674.10 0.00 0.00 0.00 0.00 0.00 30.40
                       
Annual Sum or Average                      
Minimum of Months 1270.43   648.06 337.50 891.37 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1812.91   3240.32 1687.50 4456.83 0.00 0.00 0.00 0.00 16.28 30.40



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 459.67 27-JAN-14:25 0.00 519.29 488.60 0.00 0.00 0.00 0.00 0.00 0.00
February 353.34 10-FEB-14:45 0.00 519.29 488.60 0.00 0.00 0.00 0.00 0.00 0.00
March 318.75 17-MAR-15:00 0.00 259.64 244.30 0.00 0.00 0.00 0.00 0.00 0.00
April 315.76 21-APR-14:30 0.00 259.64 244.30 0.00 0.00 0.00 0.00 0.00 0.00
May 314.41 18-MAY-16:20 0.00 259.64 244.30 0.00 0.00 0.00 0.00 0.00 0.00
June 397.29 30-JUN-16:10 0.00 259.64 244.30 0.00 0.00 0.00 0.00 0.00 0.00
July 413.40 21-JUL-16:07 0.00 778.93 732.90 0.00 0.00 0.00 0.00 0.00 0.00
August 473.35 25-AUG-14:20 0.00 259.64 244.30 0.00 0.00 0.00 0.00 0.00 0.00
September 514.50 01-SEP-14:20 0.00 259.64 244.30 0.00 0.00 0.00 0.00 0.00 0.00
October 504.83 20-OCT-14:30 0.00 259.64 244.30 0.00 0.00 0.00 0.00 0.00 0.00
November 395.35 17-NOV-13:50 0.00 259.64 244.30 0.00 0.00 0.00 0.00 0.00 0.00
December 372.98 08-DEC-13:50 0.00 778.93 732.90 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 314.41   0.00 259.64 244.30 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 514.50   0.00 778.93 732.90 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 584.62 27-JAN-07:01 0.00 909.16 393.54 0.00 0.00 0.00 0.00 0.00 0.00
February 775.19 03-FEB-07:01 0.00 909.16 393.54 0.00 0.00 0.00 0.00 0.00 0.00
March 774.03 10-MAR-07:01 0.00 909.16 393.54 0.00 0.00 0.00 0.00 0.00 0.00
April 753.01 07-APR-06:01 0.00 909.16 393.54 0.00 0.00 0.00 0.00 0.00 0.00
May 244.36 22-MAY-06:03 0.00 909.16 393.54 0.00 0.00 0.00 0.00 0.00 0.00
June 244.22 19-JUN-06:04 0.00 454.58 196.77 0.00 0.00 0.00 0.00 0.00 0.00
July 242.08 17-JUL-06:03 0.00 818.24 354.18 0.00 0.00 0.00 0.00 0.00 0.00
August 242.56 21-AUG-06:03 0.00 818.24 354.18 0.00 0.00 0.00 0.00 0.00 0.00
September 242.13 25-SEP-06:03 0.00 909.16 393.54 0.00 0.00 0.00 0.00 0.00 0.00
October 430.87 06-OCT-06:01 0.00 909.16 393.54 0.00 0.00 0.00 0.00 0.00 0.00
November 761.84 10-NOV-07:01 0.00 909.16 393.54 0.00 0.00 0.00 0.00 0.00 0.00
December 780.36 15-DEC-07:01 0.00 909.16 393.54 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 242.08   0.00 454.58 196.77 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 780.36   0.00 909.16 393.54 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 438.01 18-JAN-18:01 0.00 1408.12 457.14 0.00 0.00 0.00 0.00 0.00 27.45
February 439.98 07-FEB-18:01 0.00 1408.12 457.14 0.00 0.00 0.00 0.00 0.00 12.68
March 441.06 24-MAR-17:01 0.00 1408.12 457.14 0.00 0.00 0.00 0.00 0.00 32.49
April 444.83 15-APR-14:01 0.00 563.25 365.71 0.00 0.00 0.00 0.00 0.00 33.56
May 473.57 25-MAY-17:01 0.00 1267.31 411.43 0.00 0.00 0.00 0.00 3.21 0.00
June 502.03 30-JUN-17:01 0.00 1408.12 457.14 0.00 0.00 0.00 0.00 11.55 0.00
July 501.99 21-JUL-16:13 0.00 633.65 274.28 0.00 0.00 0.00 0.00 5.70 0.00
August 494.43 09-AUG-17:01 0.00 1267.31 411.43 0.00 0.00 0.00 0.00 3.44 0.00
September 485.37 01-SEP-06:14 0.00 1056.09 457.14 0.00 0.00 0.00 0.00 0.00 2.62
October 470.78 19-OCT-17:01 0.00 1267.31 411.43 0.00 0.00 0.00 0.00 0.00 1.79
November 469.81 01-NOV-17:01 0.00 1126.50 365.71 0.00 0.00 0.00 0.00 0.00 1.87
December 442.88 05-DEC-18:01 0.00 1408.12 457.14 0.00 0.00 0.00 0.00 0.00 7.47
                       
Annual Sum or Average                      
Minimum of Months 438.01   0.00 563.25 274.28 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 502.03   0.00 1408.12 457.14 0.00 0.00 0.00 0.00 11.55 33.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 98.14 18-JAN-18:01 0.00 550.76 388.66 0.00 0.00 0.00 0.00 0.00 15.06
February 101.83 09-FEB-07:04 0.00 826.14 777.32 0.00 0.00 0.00 0.00 0.00 14.50
March 104.12 23-MAR-09:35 0.00 495.69 466.39 0.00 0.00 0.00 0.00 0.00 1.82
April 121.49 21-APR-09:30 0.00 165.23 155.46 0.00 0.00 0.00 0.00 0.00 6.18
May 249.48 18-MAY-09:20 0.00 82.61 77.73 0.00 0.00 0.00 0.00 0.57 0.00
June 323.84 28-JUN-06:03 0.00 330.46 310.93 0.00 0.00 0.00 0.00 0.00 0.00
July 578.19 14-JUL-06:02 0.00 495.69 466.39 0.00 0.00 0.00 0.00 0.00 0.00
August 359.43 25-AUG-09:25 0.00 165.23 155.46 0.00 0.00 0.00 0.00 0.00 0.14
September 324.35 01-SEP-09:20 0.00 82.61 77.73 0.00 0.00 0.00 0.00 0.00 0.84
October 187.02 19-OCT-09:15 0.00 165.23 155.46 0.00 0.00 0.00 0.00 0.00 5.47
November 106.53 01-NOV-06:04 0.00 826.14 777.32 0.00 0.00 0.00 0.00 0.00 3.91
December 101.45 06-DEC-07:04 0.00 826.14 777.32 0.00 0.00 0.00 0.00 0.00 11.62
                       
Annual Sum or Average                      
Minimum of Months 98.14   0.00 82.61 77.73 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 578.19   0.00 826.14 777.32 0.00 0.00 0.00 0.00 0.57 15.06



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 129.66 18-JAN-18:01 0.00 719.36 507.64 0.00 0.00 0.00 0.00 0.00 9.54
February 130.31 07-FEB-18:01 0.00 719.36 507.64 0.00 0.00 0.00 0.00 0.00 4.41
March 130.68 24-MAR-17:01 0.00 719.36 507.64 0.00 0.00 0.00 0.00 0.00 11.29
April 131.69 15-APR-14:01 0.00 287.74 406.11 0.00 0.00 0.00 0.00 0.00 11.67
May 145.85 18-MAY-06:04 0.00 755.33 710.69 0.00 0.00 0.00 0.00 0.00 0.05
June 153.09 30-JUN-16:00 0.00 107.90 101.53 0.00 0.00 0.00 0.00 3.90 0.00
July 153.77 21-JUL-16:03 0.00 323.71 304.58 0.00 0.00 0.00 0.00 1.97 0.00
August 150.42 25-AUG-17:01 0.00 719.36 507.64 0.00 0.00 0.00 0.00 1.24 0.00
September 147.80 01-SEP-16:20 0.00 107.90 101.53 0.00 0.00 0.00 0.00 0.91 0.00
October 142.91 20-OCT-06:04 0.00 1079.04 1015.28 0.00 0.00 0.00 0.00 0.00 1.48
November 139.11 01-NOV-17:01 0.00 575.49 406.11 0.00 0.00 0.00 0.00 0.00 0.65
December 131.14 05-DEC-18:01 0.00 719.36 507.64 0.00 0.00 0.00 0.00 0.00 2.59
                       
Annual Sum or Average                      
Minimum of Months 129.66   0.00 107.90 101.53 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 153.77   0.00 1079.04 1015.28 0.00 0.00 0.00 0.00 3.90 11.67



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 22.40 06-JAN-05:00 0.00 3.21 2.09 0.00 0.00 0.00 0.00 0.00 0.00
February 20.35 10-FEB-13:37 0.00 28.93 12.52 0.00 0.00 0.00 0.00 0.00 0.00
March 20.55 17-MAR-10:40 0.00 28.93 12.52 0.00 0.00 0.00 0.00 0.00 0.00
April 21.28 14-APR-08:43 0.00 28.93 12.52 0.00 0.00 0.00 0.00 0.00 0.00
May 22.71 18-MAY-19:00 0.00 6.43 2.09 0.00 0.00 0.00 0.00 0.00 0.00
June 28.38 30-JUN-16:30 0.00 9.64 4.17 0.00 0.00 0.00 0.00 0.00 0.00
July 32.15 21-JUL-16:27 0.00 28.93 12.52 0.00 0.00 0.00 0.00 0.00 0.00
August 33.59 25-AUG-15:20 0.00 9.64 4.17 0.00 0.00 0.00 0.00 0.00 0.00
September 27.86 01-SEP-16:40 0.00 9.64 4.17 0.00 0.00 0.00 0.00 0.00 0.00
October 22.36 20-OCT-14:10 0.00 19.29 8.35 0.00 0.00 0.00 0.00 0.00 0.00
November 21.10 01-NOV-06:03 0.00 96.43 41.74 0.00 0.00 0.00 0.00 0.00 0.00
December 20.72 15-DEC-17:57 0.00 38.57 16.70 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 20.35   0.00 3.21 2.09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 33.59   0.00 96.43 41.74 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 134.12 18-JAN-18:01 0.00 551.00 178.88 0.00 0.00 0.00 0.00 0.00 19.36
February 134.73 07-FEB-18:01 0.00 551.00 178.88 0.00 0.00 0.00 0.00 0.00 8.95
March 135.45 24-MAR-17:01 0.00 551.00 178.88 0.00 0.00 0.00 0.00 0.00 22.95
April 143.62 15-APR-06:08 0.00 110.20 71.55 0.00 0.00 0.00 0.00 0.00 11.52
May 157.06 18-MAY-14:10 0.00 165.30 71.55 0.00 0.00 0.00 0.00 3.22 0.00
June 221.51 30-JUN-15:00 0.00 82.65 35.78 0.00 0.00 0.00 0.00 11.72 0.00
July 283.71 29-JUL-09:30 0.00 36.73 28.62 0.00 0.00 0.00 0.00 2.21 0.00
August 282.72 25-AUG-09:35 0.00 165.30 71.55 0.00 0.00 0.00 0.00 0.00 0.05
September 199.37 01-SEP-09:40 0.00 82.65 35.78 0.00 0.00 0.00 0.00 0.00 0.77
October 148.01 20-OCT-14:10 0.00 165.30 71.55 0.00 0.00 0.00 0.00 0.00 1.87
November 143.49 01-NOV-17:01 0.00 440.80 143.10 0.00 0.00 0.00 0.00 0.00 1.33
December 135.53 05-DEC-18:01 0.00 551.00 178.88 0.00 0.00 0.00 0.00 0.00 5.27
                       
Annual Sum or Average                      
Minimum of Months 134.12   0.00 36.73 28.62 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 283.71   0.00 551.00 178.88 0.00 0.00 0.00 0.00 11.72 22.95



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 29.01 21-JAN-15:01 0.00 91.04 128.50 0.00 0.00 0.00 0.00 0.00 12.25
February 29.39 04-FEB-15:01 0.00 80.93 114.22 0.00 0.00 0.00 0.00 0.00 4.92
March 31.89 11-MAR-15:01 0.00 80.93 114.22 0.00 0.00 0.00 0.00 0.00 9.09
April 36.28 15-APR-14:01 0.00 80.93 114.22 0.00 0.00 0.00 0.00 0.00 10.46
May 337.42 25-MAY-17:00 0.00 30.35 28.55 0.00 0.00 0.00 0.00 714.03 0.00
June 442.17 29-JUN-16:00 0.00 30.35 28.55 0.00 0.00 0.00 0.00 1260.76 0.00
July 354.17 21-JUL-16:00 0.00 30.35 28.55 0.00 0.00 0.00 0.00 760.17 0.00
August 364.44 08-AUG-16:00 0.00 30.35 28.55 0.00 0.00 0.00 0.00 865.11 0.00
September 283.28 01-SEP-16:00 0.00 30.35 28.55 0.00 0.00 0.00 0.00 412.34 0.00
October 42.39 19-OCT-15:00 0.00 30.35 28.55 0.00 0.00 0.00 0.00 146.60 0.00
November 35.93 18-NOV-15:01 0.00 80.93 114.22 0.00 0.00 0.00 0.00 0.00 4.10
December 27.95 16-DEC-15:01 0.00 80.93 114.22 0.00 0.00 0.00 0.00 0.00 6.48
                       
Annual Sum or Average                      
Minimum of Months 27.95   0.00 30.35 28.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 442.17   0.00 91.04 128.50 0.00 0.00 0.00 0.00 1260.76 12.25



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1748.64 26-JAN-12:04 9072.88 0.00 1663.37 0.00 0.00 0.00 0.00 0.00 60.09
February 1872.46 28-FEB-14:00 1814.58 0.00 332.67 0.00 0.00 0.00 0.00 0.00 59.96
March 1823.41 31-MAR-14:30 1814.58 0.00 332.67 0.00 0.00 0.00 0.00 0.00 32.86
April 2046.26 12-APR-13:00 1814.58 0.00 332.67 0.00 0.00 0.00 0.00 0.00 12.22
May 1986.35 18-MAY-13:00 1814.58 0.00 332.67 0.00 0.00 0.00 0.00 10.59 0.00
June 1973.18 30-JUN-13:00 1814.58 0.00 332.67 0.00 0.00 0.00 0.00 22.53 0.00
July 1888.06 21-JUL-13:00 1814.58 0.00 332.67 0.00 0.00 0.00 0.00 11.61 0.00
August 2136.48 25-AUG-13:00 1814.58 0.00 332.67 0.00 0.00 0.00 0.00 9.56 0.00
September 2394.64 01-SEP-13:00 1814.58 0.00 332.67 0.00 0.00 0.00 0.00 3.18 0.00
October 2382.54 19-OCT-12:55 3629.15 0.00 665.35 0.00 0.00 0.00 0.00 0.00 4.04
November 1835.70 17-NOV-13:40 1814.58 0.00 332.67 0.00 0.00 0.00 0.00 0.00 45.39
December 1700.26 20-DEC-12:06 9072.88 0.00 1663.37 0.00 0.00 0.00 0.00 0.00 80.13
                       
Annual Sum or Average                      
Minimum of Months 1700.26   1814.58 0.00 332.67 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2394.64   9072.88 0.00 1663.37 0.00 0.00 0.00 0.00 22.53 80.13



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 209.95 26-JAN-07:03 0.00 239.50 253.82 0.00 0.00 0.00 0.00 0.00 0.00
February 215.82 14-FEB-07:03 0.00 239.50 253.82 0.00 0.00 0.00 0.00 0.00 0.00
March 170.50 16-MAR-05:03 0.00 159.67 253.82 0.00 0.00 0.00 0.00 0.00 0.00
April 175.34 13-APR-17:01 0.00 143.70 114.22 0.00 0.00 0.00 0.00 0.00 0.00
May 188.87 17-MAY-17:01 0.00 159.67 126.91 0.00 0.00 0.00 0.00 0.00 0.00
June 204.02 30-JUN-06:03 0.00 167.65 177.67 0.00 0.00 0.00 0.00 0.00 0.00
July 192.24 21-JUL-06:05 0.00 95.80 101.53 0.00 0.00 0.00 0.00 0.00 0.00
August 190.05 09-AUG-06:05 0.00 95.80 101.53 0.00 0.00 0.00 0.00 0.00 0.00
September 189.06 01-SEP-17:01 0.00 143.70 114.22 0.00 0.00 0.00 0.00 0.00 0.00
October 180.90 21-OCT-14:01 0.00 63.87 101.53 0.00 0.00 0.00 0.00 0.00 0.00
November 157.64 01-NOV-17:01 0.00 127.73 101.53 0.00 0.00 0.00 0.00 0.00 0.00
December 194.15 20-DEC-07:03 0.00 239.50 253.82 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 157.64   0.00 63.87 101.53 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 215.82   0.00 239.50 253.82 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 116.30 27-JAN-18:00 37.80 40.05 76.26 0.00 0.00 0.00 0.00 0.00 0.00
February 197.47 09-FEB-07:01 378.04 400.51 762.63 0.00 0.00 0.00 0.00 0.00 0.00
March 202.07 30-MAR-06:01 378.04 400.51 762.63 0.00 0.00 0.00 0.00 0.00 0.00
April 204.87 14-APR-06:02 378.04 400.51 762.63 0.00 0.00 0.00 0.00 0.00 0.00
May 225.69 19-MAY-06:01 340.23 360.46 686.37 0.00 0.00 0.00 0.00 0.00 0.00
June 210.34 09-JUN-06:01 378.04 400.51 762.63 0.00 0.00 0.00 0.00 0.00 0.00
July 217.64 28-JUL-06:01 340.23 360.46 686.37 0.00 0.00 0.00 0.00 0.00 0.00
August 225.51 11-AUG-06:01 340.23 360.46 686.37 0.00 0.00 0.00 0.00 0.00 0.00
September 207.48 15-SEP-06:02 378.04 400.51 762.63 0.00 0.00 0.00 0.00 0.00 0.00
October 208.12 20-OCT-06:02 378.04 400.51 762.63 0.00 0.00 0.00 0.00 0.00 0.00
November 199.40 17-NOV-07:01 378.04 400.51 762.63 0.00 0.00 0.00 0.00 0.00 0.00
December 134.53 15-DEC-07:01 378.04 400.51 762.63 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 116.30   37.80 40.05 76.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 225.69   378.04 400.51 762.63 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1088.52 07-JAN-15:02 1555.35 1061.42 1764.96 0.00 0.00 0.00 0.00 0.00 74.83
February 1177.67 28-FEB-15:50 777.68 353.81 392.21 0.00 0.00 0.00 0.00 0.00 45.89
March 1471.42 31-MAR-17:00 777.68 353.81 392.21 0.00 0.00 0.00 0.00 0.00 36.01
April 1879.81 21-APR-17:00 777.68 353.81 392.21 0.00 0.00 0.00 0.00 0.00 23.92
May 2145.13 25-MAY-17:00 777.68 353.81 392.21 0.00 0.00 0.00 0.00 6.76 0.00
June 2286.70 30-JUN-17:00 777.68 353.81 392.21 0.00 0.00 0.00 0.00 26.49 0.00
July 2103.10 28-JUL-17:00 777.68 353.81 392.21 0.00 0.00 0.00 0.00 18.40 0.00
August 2099.88 25-AUG-17:00 777.68 353.81 392.21 0.00 0.00 0.00 0.00 8.47 0.00
September 2014.53 01-SEP-16:10 777.68 353.81 392.21 0.00 0.00 0.00 0.00 5.61 0.00
October 1705.42 19-OCT-16:10 1555.35 707.62 784.42 0.00 0.00 0.00 0.00 0.00 2.27
November 1050.93 17-NOV-15:30 777.68 353.81 392.21 0.00 0.00 0.00 0.00 0.00 42.85
December 1085.62 02-DEC-15:03 1382.53 943.49 1568.85 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 1050.93   777.68 353.81 392.21 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2286.70   1555.35 1061.42 1764.96 0.00 0.00 0.00 0.00 26.49 74.83



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2529.68 26-JAN-06:02 6480.63 3538.08 5883.19 0.00 0.00 0.00 0.00 0.00 22.31
February 2478.18 17-FEB-06:02 6480.63 3538.08 5883.19 0.00 0.00 0.00 0.00 0.00 0.00
March 1982.45 15-MAR-05:03 6480.63 3538.08 5883.19 0.00 0.00 0.00 0.00 0.00 54.31
April 2267.72 13-APR-17:01 5832.57 3184.27 2647.43 0.00 0.00 0.00 0.00 0.00 2.59
May 2443.25 17-MAY-17:01 6480.63 3538.08 2941.59 0.00 0.00 0.00 0.00 3.44 0.00
June 2676.27 30-JUN-06:03 8165.59 3714.98 4118.23 0.00 0.00 0.00 0.00 5.81 0.00
July 2445.76 21-JUL-17:01 6480.63 3538.08 2941.59 0.00 0.00 0.00 0.00 4.15 0.00
August 2448.87 25-AUG-17:01 6480.63 3538.08 2941.59 0.00 0.00 0.00 0.00 4.15 0.00
September 2445.87 01-SEP-17:01 5832.57 3184.27 2647.43 0.00 0.00 0.00 0.00 2.37 0.00
October 2332.54 21-OCT-14:01 2073.80 1415.23 2353.27 0.00 0.00 0.00 0.00 0.00 0.83
November 2039.52 01-NOV-17:01 5184.50 2830.46 2353.27 0.00 0.00 0.00 0.00 0.00 1.86
December 2317.79 20-DEC-06:02 6480.63 3538.08 5883.19 0.00 0.00 0.00 0.00 0.00 46.89
                       
Annual Sum or Average                      
Minimum of Months 1982.45   2073.80 1415.23 2353.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2676.27   8165.59 3714.98 5883.19 0.00 0.00 0.00 0.00 5.81 54.31



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3356.01 26-JAN-06:02 8640.84 4717.44 7844.25 0.00 0.00 0.00 0.00 0.00 29.74
February 3290.15 17-FEB-06:02 8640.84 4717.44 7844.25 0.00 0.00 0.00 0.00 0.00 0.00
March 2562.67 15-MAR-05:03 8640.84 4717.44 7844.25 0.00 0.00 0.00 0.00 0.00 72.41
April 3020.30 13-APR-17:01 7776.76 4245.70 3529.91 0.00 0.00 0.00 0.00 0.00 3.43
May 3252.08 17-MAY-17:01 8640.84 4717.44 3922.12 0.00 0.00 0.00 0.00 4.59 0.00
June 3555.67 30-JUN-06:03 10887.46 4953.31 5490.97 0.00 0.00 0.00 0.00 7.79 0.00
July 3254.87 21-JUL-17:01 8640.84 4717.44 3922.12 0.00 0.00 0.00 0.00 5.55 0.00
August 3259.55 25-AUG-17:01 8640.84 4717.44 3922.12 0.00 0.00 0.00 0.00 5.54 0.00
September 3255.29 01-SEP-17:01 7776.76 4245.70 3529.91 0.00 0.00 0.00 0.00 3.18 0.00
October 3109.60 21-OCT-14:01 2765.07 1886.98 3137.70 0.00 0.00 0.00 0.00 0.00 1.11
November 2715.87 01-NOV-17:01 6912.67 3773.95 3137.70 0.00 0.00 0.00 0.00 0.00 2.48
December 3090.01 20-DEC-06:02 8640.84 4717.44 7844.25 0.00 0.00 0.00 0.00 0.00 62.52
                       
Annual Sum or Average                      
Minimum of Months 2562.67   2765.07 1886.98 3137.70 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3555.67   10887.46 4953.31 7844.25 0.00 0.00 0.00 0.00 7.79 72.41



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 409.26 27-JAN-14:07 544.37 247.67 274.55 0.00 0.00 0.00 0.00 0.00 0.00
February 433.97 28-FEB-14:10 362.92 165.11 183.03 0.00 0.00 0.00 0.00 0.00 10.41
March 410.88 23-MAR-14:02 725.83 330.22 366.06 0.00 0.00 0.00 0.00 0.00 0.51
April 432.59 13-APR-13:10 362.92 165.11 183.03 0.00 0.00 0.00 0.00 0.00 1.17
May 364.85 18-MAY-13:20 181.46 82.56 91.52 0.00 0.00 0.00 0.00 1.82 0.00
June 358.44 30-JUN-13:20 181.46 82.56 91.52 0.00 0.00 0.00 0.00 4.23 0.00
July 347.14 21-JUL-14:05 362.92 165.11 183.03 0.00 0.00 0.00 0.00 2.45 0.00
August 419.85 25-AUG-13:10 362.92 165.11 183.03 0.00 0.00 0.00 0.00 1.73 0.00
September 514.62 01-SEP-13:20 181.46 82.56 91.52 0.00 0.00 0.00 0.00 0.73 0.00
October 546.66 19-OCT-13:15 362.92 165.11 183.03 0.00 0.00 0.00 0.00 0.00 0.58
November 418.98 17-NOV-13:30 181.46 82.56 91.52 0.00 0.00 0.00 0.00 0.00 8.05
December 363.00 20-DEC-13:40 181.46 82.56 91.52 0.00 0.00 0.00 0.00 0.00 14.29
                       
Annual Sum or Average                      
Minimum of Months 347.14   181.46 82.56 91.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 546.66   725.83 330.22 366.06 0.00 0.00 0.00 0.00 4.23 14.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1256.71 07-JAN-15:02 1512.15 1031.94 1715.93 0.00 0.00 0.00 0.00 0.00 44.48
February 1152.72 17-FEB-06:02 4200.41 2293.20 3813.18 0.00 0.00 0.00 0.00 0.00 0.00
March 1057.94 31-MAR-09:40 756.07 343.98 381.32 0.00 0.00 0.00 0.00 0.00 43.50
April 1417.37 18-APR-09:25 1512.15 687.96 762.64 0.00 0.00 0.00 0.00 0.00 10.02
May 1593.62 17-MAY-08:55 1512.15 687.96 762.64 0.00 0.00 0.00 0.00 0.00 0.50
June 1643.44 15-JUN-09:00 756.07 343.98 381.32 0.00 0.00 0.00 0.00 0.00 5.44
July 1636.66 19-JUL-09:10 756.07 343.98 381.32 0.00 0.00 0.00 0.00 0.00 0.32
August 1639.57 25-AUG-09:10 1512.15 687.96 762.64 0.00 0.00 0.00 0.00 0.00 0.82
September 1557.82 01-SEP-09:40 756.07 343.98 381.32 0.00 0.00 0.00 0.00 0.00 1.33
October 1311.14 19-OCT-12:15 1512.15 687.96 762.64 0.00 0.00 0.00 0.00 0.00 2.37
November 1154.61 01-NOV-17:01 3360.33 1834.56 1525.27 0.00 0.00 0.00 0.00 0.00 2.62
December 1191.22 02-DEC-15:03 1344.13 917.28 1525.27 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 1057.94   756.07 343.98 381.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1643.44   4200.41 2293.20 3813.18 0.00 0.00 0.00 0.00 0.00 44.48



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 867.73 07-JAN-15:02 972.09 663.39 1103.10 0.00 0.00 0.00 0.00 0.00 26.63
February 852.74 17-FEB-06:02 2700.26 1474.20 2451.33 0.00 0.00 0.00 0.00 0.00 0.00
March 712.52 01-MAR-07:02 4860.47 2211.30 2451.33 0.00 0.00 0.00 0.00 0.00 12.68
April 885.06 13-APR-17:01 2430.24 1326.78 1103.10 0.00 0.00 0.00 0.00 0.00 2.13
May 959.58 18-MAY-17:01 2700.26 1474.20 1225.66 0.00 0.00 0.00 0.00 3.86 0.00
June 1054.36 30-JUN-06:03 3402.33 1547.91 1715.93 0.00 0.00 0.00 0.00 4.79 0.00
July 981.39 21-JUL-06:05 1944.19 884.52 980.53 0.00 0.00 0.00 0.00 0.00 0.79
August 960.96 08-AUG-17:01 2700.26 1474.20 1225.66 0.00 0.00 0.00 0.00 9.39 0.00
September 957.53 01-SEP-17:01 2430.24 1326.78 1103.10 0.00 0.00 0.00 0.00 1.98 0.00
October 901.54 21-OCT-14:01 864.08 589.68 980.53 0.00 0.00 0.00 0.00 0.00 0.61
November 799.84 01-NOV-17:01 2160.21 1179.36 980.53 0.00 0.00 0.00 0.00 0.00 1.56
December 820.98 09-DEC-15:03 864.08 589.68 980.53 0.00 0.00 0.00 0.00 0.00 54.55
                       
Annual Sum or Average                      
Minimum of Months 712.52   864.08 589.68 980.53 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1054.36   4860.47 2211.30 2451.33 0.00 0.00 0.00 0.00 9.39 54.55



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3757.91 13-JAN-06:02 9504.92 5189.18 8628.67 0.00 0.00 0.00 0.00 0.00 4.50
February 3835.81 17-FEB-06:02 9504.92 5189.18 8628.67 0.00 0.00 0.00 0.00 0.00 0.00
March 2908.73 15-MAR-05:03 9504.92 5189.18 8628.67 0.00 0.00 0.00 0.00 0.00 72.42
April 3302.58 13-APR-17:01 8554.43 4670.27 3882.90 0.00 0.00 0.00 0.00 0.00 3.35
May 3568.13 17-MAY-17:01 9504.92 5189.18 4314.34 0.00 0.00 0.00 0.00 4.61 0.00
June 3922.06 30-JUN-06:03 11976.21 5448.64 6040.07 0.00 0.00 0.00 0.00 7.76 0.00
July 3574.69 21-JUL-17:01 9504.92 5189.18 4314.34 0.00 0.00 0.00 0.00 5.57 0.00
August 3571.58 25-AUG-17:01 9504.92 5189.18 4314.34 0.00 0.00 0.00 0.00 5.57 0.00
September 3559.53 01-SEP-17:01 8554.43 4670.27 3882.90 0.00 0.00 0.00 0.00 3.22 0.00
October 3362.50 21-OCT-14:01 3041.58 2075.67 3451.47 0.00 0.00 0.00 0.00 0.00 0.94
November 2990.50 01-NOV-17:01 7603.94 4151.35 3451.47 0.00 0.00 0.00 0.00 0.00 2.48
December 3402.78 20-DEC-06:02 9504.92 5189.18 8628.67 0.00 0.00 0.00 0.00 0.00 62.53
                       
Annual Sum or Average                      
Minimum of Months 2908.73   3041.58 2075.67 3451.47 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3922.06   11976.21 5448.64 8628.67 0.00 0.00 0.00 0.00 7.76 72.42



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1083.36 13-JAN-06:02 3240.32 1769.04 2941.59 0.00 0.00 0.00 0.00 0.00 3.37
February 1111.47 17-FEB-06:02 3240.32 1769.04 2941.59 0.00 0.00 0.00 0.00 0.00 0.00
March 848.72 01-MAR-07:02 5832.57 2653.56 2941.59 0.00 0.00 0.00 0.00 0.00 15.23
April 1056.40 13-APR-17:01 2916.28 1592.14 1323.72 0.00 0.00 0.00 0.00 0.00 2.61
May 1178.59 26-MAY-06:05 2333.03 1061.42 1176.64 0.00 0.00 0.00 0.00 0.00 1.12
June 1257.85 30-JUN-06:03 4082.80 1857.49 2059.11 0.00 0.00 0.00 0.00 5.71 0.00
July 1174.51 21-JUL-06:05 2333.03 1061.42 1176.64 0.00 0.00 0.00 0.00 0.00 0.98
August 1157.59 09-AUG-06:05 2333.03 1061.42 1176.64 0.00 0.00 0.00 0.00 0.00 1.96
September 1141.23 01-SEP-17:01 2916.28 1592.14 1323.72 0.00 0.00 0.00 0.00 2.35 0.00
October 1076.39 21-OCT-14:01 1036.90 707.62 1176.64 0.00 0.00 0.00 0.00 0.00 0.78
November 956.10 01-NOV-17:01 2592.25 1415.23 1176.64 0.00 0.00 0.00 0.00 0.00 1.88
December 1025.40 20-DEC-06:02 3240.32 1769.04 2941.59 0.00 0.00 0.00 0.00 0.00 46.87
                       
Annual Sum or Average                      
Minimum of Months 848.72   1036.90 707.62 1176.64 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1257.85   5832.57 2653.56 2941.59 0.00 0.00 0.00 0.00 5.71 46.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1863.36 13-JAN-06:02 4752.46 2594.59 4314.34 0.00 0.00 0.00 0.00 0.00 2.25
February 1915.94 17-FEB-06:02 4752.46 2594.59 4314.34 0.00 0.00 0.00 0.00 0.00 0.00
March 1454.23 15-MAR-05:03 4752.46 2594.59 4314.34 0.00 0.00 0.00 0.00 0.00 36.21
April 1657.56 13-APR-17:01 4277.22 2335.13 1941.45 0.00 0.00 0.00 0.00 0.00 1.70
May 1798.04 26-MAY-06:05 3421.77 1556.76 1725.73 0.00 0.00 0.00 0.00 0.00 0.72
June 1969.70 30-JUN-06:03 5988.10 2724.32 3020.04 0.00 0.00 0.00 0.00 3.85 0.00
July 1832.96 21-JUL-06:05 3421.77 1556.76 1725.73 0.00 0.00 0.00 0.00 0.00 0.62
August 1793.29 25-AUG-17:01 4752.46 2594.59 2157.17 0.00 0.00 0.00 0.00 2.77 0.00
September 1788.14 01-SEP-17:01 4277.22 2335.13 1941.45 0.00 0.00 0.00 0.00 1.59 0.00
October 1689.02 21-OCT-14:01 1520.79 1037.84 1725.73 0.00 0.00 0.00 0.00 0.00 0.49
November 1502.04 01-NOV-17:01 3801.97 2075.67 1725.73 0.00 0.00 0.00 0.00 0.00 1.25
December 1700.15 20-DEC-06:02 4752.46 2594.59 4314.34 0.00 0.00 0.00 0.00 0.00 31.26
                       
Annual Sum or Average                      
Minimum of Months 1454.23   1520.79 1037.84 1725.73 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1969.70   5988.10 2724.32 4314.34 0.00 0.00 0.00 0.00 3.85 36.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 151.16 27-JAN-16:15 0.00 151.74 142.77 0.00 0.00 0.00 0.00 0.00 0.00
February 234.79 28-FEB-16:30 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
March 289.71 31-MAR-17:00 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
April 334.29 21-APR-17:00 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
May 297.34 18-MAY-17:00 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
June 311.52 30-JUN-17:00 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
July 283.05 21-JUL-16:57 0.00 227.61 214.16 0.00 0.00 0.00 0.00 0.00 0.00
August 329.49 25-AUG-17:00 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
September 374.23 01-SEP-17:00 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
October 361.22 19-OCT-16:35 0.00 151.74 142.77 0.00 0.00 0.00 0.00 0.00 0.00
November 226.66 17-NOV-16:00 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
December 105.94 20-DEC-06:05 0.00 505.80 713.87 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 105.94   0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 374.23   0.00 505.80 713.87 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 203.08 27-JAN-15:43 0.00 227.61 214.16 0.00 0.00 0.00 0.00 0.00 0.00
February 224.38 28-FEB-16:10 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
March 210.58 31-MAR-16:30 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
April 211.40 21-APR-16:20 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
May 199.51 18-MAY-17:00 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
June 208.09 30-JUN-17:00 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
July 196.69 21-JUL-16:57 0.00 227.61 214.16 0.00 0.00 0.00 0.00 0.00 0.00
August 218.80 25-AUG-16:50 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
September 232.54 01-SEP-16:20 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
October 260.95 19-OCT-15:50 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
November 219.54 17-NOV-15:40 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
December 116.26 02-DEC-06:12 0.00 33.72 85.66 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 116.26   0.00 33.72 71.39 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 260.95   0.00 227.61 214.16 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 241.00 27-JAN-15:43 0.00 227.61 214.16 0.00 0.00 0.00 0.00 0.00 0.00
February 259.06 28-FEB-16:10 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
March 215.87 31-MAR-16:30 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
April 209.71 21-APR-16:10 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
May 184.77 18-MAY-17:00 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
June 190.69 30-JUN-17:00 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
July 178.07 21-JUL-16:57 0.00 227.61 214.16 0.00 0.00 0.00 0.00 0.00 0.00
August 208.05 25-AUG-16:50 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
September 226.64 01-SEP-16:20 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
October 270.99 19-OCT-16:00 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
November 235.05 17-NOV-15:40 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
December 148.44 20-DEC-15:40 0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 148.44   0.00 75.87 71.39 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 270.99   0.00 227.61 214.16 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 257.04 06-JAN-07:01 0.00 834.57 785.25 0.00 0.00 0.00 0.00 0.00 0.00
February 208.60 25-FEB-07:03 0.00 111.28 157.05 0.00 0.00 0.00 0.00 0.00 0.00
March 111.25 31-MAR-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
April 143.81 14-APR-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
May 173.02 18-MAY-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
June 195.80 30-JUN-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
July 189.31 21-JUL-16:57 0.00 250.37 235.58 0.00 0.00 0.00 0.00 0.00 0.00
August 176.13 25-AUG-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
September 164.19 01-SEP-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
October 136.82 20-OCT-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
November 106.91 01-NOV-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
December 157.16 02-DEC-07:03 0.00 111.28 157.05 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 106.91   0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 257.04   0.00 834.57 785.25 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 281.31 06-JAN-07:01 0.00 834.57 785.25 0.00 0.00 0.00 0.00 0.00 0.00
February 230.51 25-FEB-07:03 0.00 111.28 157.05 0.00 0.00 0.00 0.00 0.00 0.00
March 145.10 31-MAR-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
April 182.05 14-APR-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
May 218.51 18-MAY-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
June 242.98 30-JUN-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
July 235.82 21-JUL-16:57 0.00 250.37 235.58 0.00 0.00 0.00 0.00 0.00 0.00
August 220.70 25-AUG-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
September 210.89 01-SEP-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
October 179.58 20-OCT-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
November 146.92 01-NOV-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
December 179.93 02-DEC-07:03 0.00 111.28 157.05 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 145.10   0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 281.31   0.00 834.57 785.25 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 251.22 06-JAN-06:11 0.00 500.74 706.73 0.00 0.00 0.00 0.00 0.00 0.00
February 181.17 25-FEB-07:03 0.00 111.28 157.05 0.00 0.00 0.00 0.00 0.00 0.00
March 116.30 31-MAR-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
April 157.80 14-APR-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
May 198.08 18-MAY-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
June 224.46 30-JUN-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
July 217.36 21-JUL-16:57 0.00 250.37 235.58 0.00 0.00 0.00 0.00 0.00 0.00
August 201.66 25-AUG-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
September 191.86 01-SEP-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
October 158.26 20-OCT-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
November 121.69 02-NOV-17:00 0.00 83.46 78.53 0.00 0.00 0.00 0.00 0.00 0.00
December 129.17 02-DEC-06:12 0.00 37.09 94.23 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 116.30   0.00 37.09 78.53 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 251.22   0.00 500.74 706.73 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 51.12 11-JAN-07:03 0.00 144.64 62.61 0.00 0.00 0.00 0.00 0.00 0.00
February 62.10 25-FEB-06:03 0.00 11.25 13.15 0.00 0.00 0.00 0.00 0.00 2.90
March 71.11 31-MAR-17:00 0.00 14.46 6.26 0.00 0.00 0.00 0.00 0.00 13.72
April 132.89 13-APR-17:00 0.00 14.46 6.26 0.00 0.00 0.00 0.00 0.00 3.53
May 206.31 18-MAY-17:00 0.00 14.46 6.26 0.00 0.00 0.00 0.00 3.45 0.00
June 357.75 30-JUN-06:01 0.00 101.25 43.83 0.00 0.00 0.00 0.00 4.07 0.00
July 218.17 21-JUL-16:53 0.00 43.39 18.78 0.00 0.00 0.00 0.00 2.72 0.00
August 230.82 10-AUG-06:01 0.00 130.17 56.35 0.00 0.00 0.00 0.00 0.00 0.35
September 198.13 01-SEP-17:00 0.00 14.46 6.26 0.00 0.00 0.00 0.00 1.47 0.00
October 141.79 19-OCT-16:55 0.00 28.93 12.52 0.00 0.00 0.00 0.00 0.00 2.22
November 98.52 01-NOV-17:00 0.00 14.46 6.26 0.00 0.00 0.00 0.00 0.00 2.20
December 55.24 02-DEC-06:03 0.00 11.25 13.15 0.00 0.00 0.00 0.00 0.00 22.81
                       
Annual Sum or Average                      
Minimum of Months 51.12   0.00 11.25 6.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 357.75   0.00 144.64 62.61 0.00 0.00 0.00 0.00 4.07 22.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 494.18 27-JAN-07:01 1296.13 424.80 2376.98 0.00 0.00 0.00 0.00 0.00 0.00
February 556.77 02-FEB-07:01 1296.13 424.80 2376.98 0.00 0.00 0.00 0.00 0.00 0.00
March 512.54 16-MAR-06:01 1296.13 424.80 2376.98 0.00 0.00 0.00 0.00 0.00 0.00
April 356.37 18-APR-06:02 1166.51 382.32 2139.28 0.00 0.00 0.00 0.00 0.00 0.00
May 411.42 26-MAY-06:03 518.45 169.92 950.79 0.00 0.00 0.00 0.00 0.00 0.00
June 427.95 29-JUN-06:03 518.45 169.92 950.79 0.00 0.00 0.00 0.00 0.00 0.00
July 412.03 21-JUL-06:03 518.45 169.92 950.79 0.00 0.00 0.00 0.00 0.00 0.00
August 407.16 09-AUG-06:03 518.45 169.92 950.79 0.00 0.00 0.00 0.00 0.00 0.00
September 391.75 01-SEP-06:01 1036.90 339.84 1901.58 0.00 0.00 0.00 0.00 0.00 0.00
October 334.69 20-OCT-06:02 1296.13 424.80 2376.98 0.00 0.00 0.00 0.00 0.00 0.00
November 372.76 29-NOV-07:01 1296.13 424.80 2376.98 0.00 0.00 0.00 0.00 0.00 0.00
December 524.98 14-DEC-07:01 1296.13 424.80 2376.98 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 334.69   518.45 169.92 950.79 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 556.77   1296.13 424.80 2376.98 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 777.16 27-JAN-07:01 3240.32 1579.50 2971.68 0.00 0.00 0.00 0.00 0.00 0.00
February 837.25 24-FEB-07:01 3240.32 1579.50 2971.68 0.00 0.00 0.00 0.00 0.00 0.00
March 808.25 16-MAR-06:01 3240.32 1579.50 2971.68 0.00 0.00 0.00 0.00 0.00 0.00
April 591.56 18-APR-06:02 2916.28 1421.55 2674.51 0.00 0.00 0.00 0.00 0.00 0.00
May 680.32 26-MAY-06:03 1296.13 631.80 1188.67 0.00 0.00 0.00 0.00 0.00 0.00
June 742.91 30-JUN-06:03 2268.22 1105.65 2080.18 0.00 0.00 0.00 0.00 0.00 0.00
July 681.68 21-JUL-06:03 1296.13 631.80 1188.67 0.00 0.00 0.00 0.00 0.00 0.00
August 672.76 09-AUG-06:03 1296.13 631.80 1188.67 0.00 0.00 0.00 0.00 0.00 0.00
September 651.28 01-SEP-06:02 2592.25 1263.60 2377.35 0.00 0.00 0.00 0.00 0.00 0.00
October 554.11 20-OCT-06:02 3240.32 1579.50 2971.68 0.00 0.00 0.00 0.00 0.00 0.00
November 601.94 29-NOV-07:01 3240.32 1579.50 2971.68 0.00 0.00 0.00 0.00 0.00 0.00
December 675.18 01-DEC-07:01 3240.32 1579.50 2971.68 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 554.11   1296.13 631.80 1188.67 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 837.25   3240.32 1579.50 2971.68 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 891.47 27-JAN-07:01 3888.38 1895.40 3566.02 0.00 0.00 0.00 0.00 0.00 0.00
February 1012.77 24-FEB-07:01 3888.38 1895.40 3566.02 0.00 0.00 0.00 0.00 0.00 0.00
March 968.25 16-MAR-06:01 3888.38 1895.40 3566.02 0.00 0.00 0.00 0.00 0.00 0.00
April 712.20 18-APR-06:02 3499.54 1705.86 3209.42 0.00 0.00 0.00 0.00 0.00 0.00
May 821.13 26-MAY-06:03 1555.35 758.16 1426.41 0.00 0.00 0.00 0.00 0.00 0.00
June 897.99 30-JUN-06:03 2721.86 1326.78 2496.21 0.00 0.00 0.00 0.00 0.00 0.00
July 822.11 21-JUL-06:03 1555.35 758.16 1426.41 0.00 0.00 0.00 0.00 0.00 0.00
August 811.71 09-AUG-06:03 1555.35 758.16 1426.41 0.00 0.00 0.00 0.00 0.00 0.00
September 787.15 01-SEP-06:02 3110.70 1516.32 2852.81 0.00 0.00 0.00 0.00 0.00 0.00
October 668.56 20-OCT-06:02 3888.38 1895.40 3566.02 0.00 0.00 0.00 0.00 0.00 0.00
November 729.91 29-NOV-07:01 3888.38 1895.40 3566.02 0.00 0.00 0.00 0.00 0.00 0.00
December 818.82 08-DEC-07:01 3888.38 1895.40 3566.02 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 668.56   1555.35 758.16 1426.41 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1012.77   3888.38 1895.40 3566.02 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 550.98 06-JAN-06:04 1680.16 2136.07 6101.08 0.00 0.00 0.00 0.00 0.00 0.00
February 456.74 28-FEB-15:08 1209.72 463.45 2440.43 0.00 0.00 0.00 0.00 0.00 49.14
March 877.30 31-MAR-09:30 302.43 0.00 610.11 0.00 0.00 0.00 0.00 0.00 73.28
April 1855.56 21-APR-06:01 3024.29 0.00 6101.08 0.00 0.00 0.00 0.00 0.00 6.89
May 2350.15 18-MAY-06:01 2117.01 0.00 4270.76 0.00 0.00 0.00 0.00 0.00 0.42
June 2657.45 29-JUN-06:03 1209.72 0.00 2440.43 0.00 0.00 0.00 0.00 1.19 0.00
July 2556.85 21-JUL-06:03 1209.72 0.00 2440.43 0.00 0.00 0.00 0.00 0.00 3.77
August 2449.06 09-AUG-06:03 1209.72 666.15 2440.43 0.00 0.00 0.00 0.00 0.00 6.76
September 2309.33 01-SEP-06:01 2419.44 1137.64 4880.87 0.00 0.00 0.00 0.00 0.00 7.78
October 1823.87 20-OCT-06:01 3024.29 3204.10 6101.08 0.00 0.00 0.00 0.00 0.00 10.34
November 550.29 17-NOV-16:00 302.43 247.13 610.11 0.00 0.00 0.00 0.00 0.00 37.36
December 412.34 21-DEC-06:04 1680.16 2136.07 6101.08 0.00 0.00 0.00 0.00 0.00 26.10
                       
Annual Sum or Average                      
Minimum of Months 412.34   302.43 0.00 610.11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2657.45   3024.29 3204.10 6101.08 0.00 0.00 0.00 0.00 1.19 73.28



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 369.62 06-JAN-09:00 0.00 561.44 528.26 0.00 0.00 0.00 0.00 0.00 0.00
February 331.52 17-FEB-06:12 0.00 748.59 1056.52 0.00 0.00 0.00 0.00 0.00 0.00
March 268.49 31-MAR-17:00 0.00 187.15 176.09 0.00 0.00 0.00 0.00 0.00 0.00
April 483.29 21-APR-07:45 0.00 374.29 352.17 0.00 0.00 0.00 0.00 0.00 0.00
May 1042.54 17-MAY-06:01 0.00 1871.47 1760.87 0.00 0.00 0.00 0.00 0.00 0.00
June 1210.03 22-JUN-06:01 0.00 1310.03 1232.61 0.00 0.00 0.00 0.00 0.00 0.00
July 1263.02 14-JUL-06:02 0.00 1122.88 1056.52 0.00 0.00 0.00 0.00 0.00 0.00
August 1009.03 25-AUG-06:01 0.00 1871.47 1760.87 0.00 0.00 0.00 0.00 0.00 0.00
September 636.48 08-SEP-06:01 0.00 1871.47 1760.87 0.00 0.00 0.00 0.00 0.00 0.00
October 383.94 20-OCT-17:00 0.00 187.15 176.09 0.00 0.00 0.00 0.00 0.00 0.00
November 257.85 17-NOV-18:00 0.00 374.29 352.17 0.00 0.00 0.00 0.00 0.00 0.00
December 292.15 02-DEC-06:17 0.00 83.18 211.30 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 257.85   0.00 83.18 176.09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1263.02   0.00 1871.47 1760.87 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3417.52 27-JAN-15:15 6376.94 342.20 2144.09 0.00 0.00 0.00 0.00 0.00 0.00
February 3701.64 28-FEB-15:30 3188.47 171.10 1072.05 0.00 0.00 0.00 0.00 0.00 57.73
March 3723.65 31-MAR-15:10 3188.47 171.10 1072.05 0.00 0.00 0.00 0.00 0.00 42.44
April 4093.48 13-APR-15:30 3188.47 171.10 1072.05 0.00 0.00 0.00 0.00 0.00 6.85
May 4870.77 26-MAY-06:03 12753.88 1894.02 4288.19 0.00 0.00 0.00 0.00 0.00 5.51
June 5422.90 30-JUN-06:03 22319.29 4457.51 7504.33 0.00 0.00 0.00 0.00 12.82 0.00
July 4880.96 21-JUL-06:03 12753.88 1604.29 4288.19 0.00 0.00 0.00 0.00 0.00 4.49
August 4792.31 09-AUG-06:03 12753.88 2455.95 4288.19 0.00 0.00 0.00 0.00 0.00 8.56
September 4758.08 01-SEP-15:30 3188.47 171.10 1072.05 0.00 0.00 0.00 0.00 7.42 0.00
October 4601.09 19-OCT-14:50 3188.47 171.10 1072.05 0.00 0.00 0.00 0.00 0.00 0.39
November 3680.49 17-NOV-14:00 3188.47 171.10 1072.05 0.00 0.00 0.00 0.00 0.00 54.22
December 2683.41 20-DEC-14:50 3188.47 171.10 1072.05 0.00 0.00 0.00 0.00 0.00 101.50
                       
Annual Sum or Average                      
Minimum of Months 2683.41   3188.47 171.10 1072.05 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5422.90   22319.29 4457.51 7504.33 0.00 0.00 0.00 0.00 12.82 101.50



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 947.28 06-JAN-07:01 0.00 2377.27 2236.78 0.00 0.00 0.00 0.00 0.00 0.00
February 1280.07 09-FEB-07:01 0.00 2377.27 2236.78 0.00 0.00 0.00 0.00 0.00 0.00
March 1320.25 30-MAR-06:01 0.00 2377.27 2236.78 0.00 0.00 0.00 0.00 0.00 0.00
April 1362.77 14-APR-06:02 0.00 2377.27 2236.78 0.00 0.00 0.00 0.00 0.00 0.00
May 1562.65 18-MAY-06:01 0.00 1664.09 1565.75 0.00 0.00 0.00 0.00 0.00 0.00
June 1751.90 30-JUN-06:01 0.00 1664.09 1565.75 0.00 0.00 0.00 0.00 0.00 0.00
July 1526.31 13-JUL-06:01 0.00 1901.81 1789.42 0.00 0.00 0.00 0.00 0.00 0.00
August 1545.23 10-AUG-06:01 0.00 2139.54 2013.10 0.00 0.00 0.00 0.00 0.00 0.00
September 1405.82 01-SEP-06:01 0.00 1901.81 1789.42 0.00 0.00 0.00 0.00 0.00 0.00
October 1383.32 20-OCT-06:02 0.00 2377.27 2236.78 0.00 0.00 0.00 0.00 0.00 0.00
November 1293.95 17-NOV-07:01 0.00 2377.27 2236.78 0.00 0.00 0.00 0.00 0.00 0.00
December 581.80 01-DEC-18:00 0.00 237.73 223.68 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 581.80   0.00 237.73 223.68 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1751.90   0.00 2377.27 2236.78 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 448.16 26-JAN-07:03 0.00 471.52 499.71 0.00 0.00 0.00 0.00 0.00 0.00
February 453.34 14-FEB-07:03 0.00 471.52 499.71 0.00 0.00 0.00 0.00 0.00 0.00
March 277.64 15-MAR-05:03 0.00 314.34 499.71 0.00 0.00 0.00 0.00 0.00 0.00
April 320.00 13-APR-17:01 0.00 282.91 224.87 0.00 0.00 0.00 0.00 0.00 0.00
May 355.80 26-MAY-06:05 0.00 188.61 199.88 0.00 0.00 0.00 0.00 0.00 0.00
June 376.99 30-JUN-06:03 0.00 330.06 349.79 0.00 0.00 0.00 0.00 0.00 0.00
July 352.63 21-JUL-06:05 0.00 188.61 199.88 0.00 0.00 0.00 0.00 0.00 0.00
August 350.23 09-AUG-06:05 0.00 188.61 199.88 0.00 0.00 0.00 0.00 0.00 0.00
September 345.33 01-SEP-17:01 0.00 282.91 224.87 0.00 0.00 0.00 0.00 0.00 0.00
October 330.68 21-OCT-14:01 0.00 125.74 199.88 0.00 0.00 0.00 0.00 0.00 0.00
November 288.94 01-NOV-17:01 0.00 251.48 199.88 0.00 0.00 0.00 0.00 0.00 0.00
December 386.05 20-DEC-07:03 0.00 471.52 499.71 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 277.64   0.00 125.74 199.88 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 453.34   0.00 471.52 499.71 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1154.98 27-JAN-07:01 1749.77 1853.80 3529.91 0.00 0.00 0.00 0.00 0.00 0.00
February 1238.93 24-FEB-07:01 1749.77 1853.80 3529.91 0.00 0.00 0.00 0.00 0.00 0.00
March 1205.00 16-MAR-06:01 1749.77 1853.80 3529.91 0.00 0.00 0.00 0.00 0.00 0.00
April 853.14 18-APR-06:02 1574.79 1668.42 3176.92 0.00 0.00 0.00 0.00 0.00 0.00
May 999.91 26-MAY-06:03 699.91 741.52 1411.96 0.00 0.00 0.00 0.00 0.00 0.00
June 1099.65 30-JUN-06:03 1224.84 1297.66 2470.94 0.00 0.00 0.00 0.00 0.00 0.00
July 1009.89 21-JUL-06:03 699.91 741.52 1411.96 0.00 0.00 0.00 0.00 0.00 0.00
August 983.23 09-AUG-06:03 699.91 741.52 1411.96 0.00 0.00 0.00 0.00 0.00 0.00
September 964.13 01-SEP-06:02 1399.82 1483.04 2823.93 0.00 0.00 0.00 0.00 0.00 0.00
October 818.79 20-OCT-06:02 1749.77 1853.80 3529.91 0.00 0.00 0.00 0.00 0.00 0.00
November 867.15 29-NOV-07:01 1749.77 1853.80 3529.91 0.00 0.00 0.00 0.00 0.00 0.00
December 977.11 01-DEC-07:01 1749.77 1853.80 3529.91 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 818.79   699.91 741.52 1411.96 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1238.93   1749.77 1853.80 3529.91 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 965.87 27-JAN-07:01 1846.98 1956.79 3726.02 0.00 0.00 0.00 0.00 0.00 0.00
February 1359.14 24-FEB-07:01 1846.98 1956.79 3726.02 0.00 0.00 0.00 0.00 0.00 0.00
March 1315.12 16-MAR-06:01 1846.98 1956.79 3726.02 0.00 0.00 0.00 0.00 0.00 0.00
April 953.04 18-APR-06:02 1662.28 1761.11 3353.42 0.00 0.00 0.00 0.00 0.00 0.00
May 1115.74 26-MAY-06:03 738.79 782.72 1490.41 0.00 0.00 0.00 0.00 0.00 0.00
June 1220.58 30-JUN-06:03 1292.89 1369.75 2608.21 0.00 0.00 0.00 0.00 0.00 0.00
July 1117.04 21-JUL-06:03 738.79 782.72 1490.41 0.00 0.00 0.00 0.00 0.00 0.00
August 1099.01 09-AUG-06:03 738.79 782.72 1490.41 0.00 0.00 0.00 0.00 0.00 0.00
September 1066.27 01-SEP-06:02 1477.58 1565.43 2980.81 0.00 0.00 0.00 0.00 0.00 0.00
October 903.88 20-OCT-06:02 1846.98 1956.79 3726.02 0.00 0.00 0.00 0.00 0.00 0.00
November 943.43 29-NOV-07:01 1846.98 1956.79 3726.02 0.00 0.00 0.00 0.00 0.00 0.00
December 1069.30 01-DEC-07:01 1846.98 1956.79 3726.02 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 903.88   738.79 782.72 1490.41 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1359.14   1846.98 1956.79 3726.02 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 83.78 26-JAN-06:01 0.00 85.71 55.65 0.00 0.00 0.00 0.00 0.00 0.00
February 74.30 25-FEB-06:01 0.00 10.00 11.69 0.00 0.00 0.00 0.00 0.00 0.00
March 54.09 16-MAR-05:01 0.00 85.71 55.65 0.00 0.00 0.00 0.00 0.00 0.00
April 48.63 13-APR-16:00 0.00 12.86 5.57 0.00 0.00 0.00 0.00 0.00 0.00
May 50.20 18-MAY-17:00 0.00 12.86 5.57 0.00 0.00 0.00 0.00 0.00 0.00
June 50.49 30-JUN-17:00 0.00 12.86 5.57 0.00 0.00 0.00 0.00 0.00 0.00
July 50.21 21-JUL-17:00 0.00 38.57 16.70 0.00 0.00 0.00 0.00 0.00 0.00
August 50.88 25-AUG-17:00 0.00 12.86 5.57 0.00 0.00 0.00 0.00 0.00 0.00
September 50.92 01-SEP-17:00 0.00 12.86 5.57 0.00 0.00 0.00 0.00 0.00 0.00
October 51.64 19-OCT-16:00 0.00 12.86 5.57 0.00 0.00 0.00 0.00 0.00 0.00
November 50.30 17-NOV-13:10 0.00 25.71 11.13 0.00 0.00 0.00 0.00 0.00 0.00
December 69.24 02-DEC-06:01 0.00 10.00 11.69 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 48.63   0.00 10.00 5.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 83.78   0.00 85.71 55.65 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 178.18 26-JAN-06:01 0.00 183.67 119.25 0.00 0.00 0.00 0.00 0.00 0.00
February 176.42 17-FEB-06:12 0.00 110.20 71.55 0.00 0.00 0.00 0.00 0.00 0.00
March 116.20 16-MAR-05:01 0.00 183.67 119.25 0.00 0.00 0.00 0.00 0.00 0.00
April 101.60 13-APR-16:00 0.00 27.55 11.93 0.00 0.00 0.00 0.00 0.00 0.00
May 107.68 18-MAY-17:00 0.00 27.55 11.93 0.00 0.00 0.00 0.00 0.00 0.00
June 109.14 30-JUN-17:00 0.00 27.55 11.93 0.00 0.00 0.00 0.00 0.00 0.00
July 108.90 21-JUL-17:00 0.00 82.65 35.78 0.00 0.00 0.00 0.00 0.00 0.00
August 108.45 25-AUG-17:00 0.00 27.55 11.93 0.00 0.00 0.00 0.00 0.00 0.00
September 107.62 01-SEP-17:00 0.00 27.55 11.93 0.00 0.00 0.00 0.00 0.00 0.00
October 105.18 19-OCT-16:00 0.00 27.55 11.93 0.00 0.00 0.00 0.00 0.00 0.00
November 94.01 01-NOV-15:00 0.00 27.55 11.93 0.00 0.00 0.00 0.00 0.00 0.00
December 154.83 02-DEC-06:12 0.00 12.24 14.31 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 94.01   0.00 12.24 11.93 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 178.18   0.00 183.67 119.25 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 214.23 26-JAN-06:01 0.00 220.40 143.10 0.00 0.00 0.00 0.00 0.00 0.00
February 212.53 17-FEB-06:12 0.00 132.24 85.86 0.00 0.00 0.00 0.00 0.00 0.00
March 139.66 16-MAR-05:01 0.00 220.40 143.10 0.00 0.00 0.00 0.00 0.00 0.00
April 125.06 13-APR-16:00 0.00 33.06 14.31 0.00 0.00 0.00 0.00 0.00 0.00
May 133.19 25-MAY-17:00 0.00 33.06 14.31 0.00 0.00 0.00 0.00 0.00 0.00
June 135.33 30-JUN-17:00 0.00 33.06 14.31 0.00 0.00 0.00 0.00 0.00 0.00
July 134.87 21-JUL-16:57 0.00 99.18 42.93 0.00 0.00 0.00 0.00 0.00 0.00
August 133.98 25-AUG-17:00 0.00 33.06 14.31 0.00 0.00 0.00 0.00 0.00 0.00
September 133.37 01-SEP-17:00 0.00 33.06 14.31 0.00 0.00 0.00 0.00 0.00 0.00
October 130.02 19-OCT-16:00 0.00 33.06 14.31 0.00 0.00 0.00 0.00 0.00 0.00
November 117.62 01-NOV-15:00 0.00 33.06 14.31 0.00 0.00 0.00 0.00 0.00 0.00
December 187.40 02-DEC-06:12 0.00 14.69 17.17 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 117.62   0.00 14.69 14.31 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 214.23   0.00 220.40 143.10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 98.67 07-JAN-15:02 0.00 86.78 56.35 0.00 0.00 0.00 0.00 0.00 16.17
February 123.78 17-FEB-06:03 0.00 192.85 125.22 0.00 0.00 0.00 0.00 0.00 0.00
March 121.12 31-MAR-09:50 0.00 28.93 12.52 0.00 0.00 0.00 0.00 0.00 15.22
April 274.73 22-APR-09:10 0.00 12.86 10.02 0.00 0.00 0.00 0.00 0.00 3.31
May 365.51 17-MAY-08:45 0.00 57.86 25.04 0.00 0.00 0.00 0.00 0.00 0.28
June 431.78 15-JUN-06:01 0.00 289.28 125.22 0.00 0.00 0.00 0.00 0.00 3.40
July 369.25 07-JUL-09:00 0.00 28.93 12.52 0.00 0.00 0.00 0.00 0.00 2.63
August 361.70 25-AUG-09:10 0.00 57.86 25.04 0.00 0.00 0.00 0.00 0.00 0.29
September 329.91 01-SEP-09:20 0.00 28.93 12.52 0.00 0.00 0.00 0.00 0.00 0.79
October 206.32 19-OCT-09:15 0.00 57.86 25.04 0.00 0.00 0.00 0.00 0.00 5.07
November 88.21 01-NOV-17:01 0.00 154.28 50.09 0.00 0.00 0.00 0.00 0.00 0.97
December 96.96 02-DEC-17:10 0.00 9.64 6.26 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 88.21   0.00 9.64 6.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 431.78   0.00 289.28 125.22 0.00 0.00 0.00 0.00 0.00 16.17



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2306.76 20-JAN-07:01 9126.89 9669.51 15209.12 0.00 0.00 0.00 0.00 0.00 69.97
February 3207.76 09-FEB-07:01 9126.89 9669.51 15209.12 0.00 0.00 0.00 0.00 0.00 40.77
March 3420.75 30-MAR-06:02 9126.89 9669.51 15209.12 0.00 0.00 0.00 0.00 0.00 26.28
April 3701.36 18-APR-06:02 8214.20 8702.56 13688.21 0.00 0.00 0.00 0.00 0.00 13.80
May 4723.30 26-MAY-06:05 3650.76 3867.81 6083.65 0.00 0.00 0.00 0.00 0.00 2.72
June 5090.81 30-JUN-06:03 6388.82 6768.66 10646.39 0.00 0.00 0.00 0.00 6.18 0.00
July 4720.72 21-JUL-06:05 3650.76 3867.81 6083.65 0.00 0.00 0.00 0.00 0.00 2.25
August 4654.65 09-AUG-06:05 3650.76 3867.81 6083.65 0.00 0.00 0.00 0.00 0.00 4.32
September 4424.49 01-SEP-06:02 7301.51 7735.61 12167.30 0.00 0.00 0.00 0.00 0.00 5.28
October 3704.69 20-OCT-06:02 9126.89 9669.51 15209.12 0.00 0.00 0.00 0.00 0.00 6.97
November 3530.71 02-NOV-06:02 9126.89 9669.51 15209.12 0.00 0.00 0.00 0.00 0.00 43.18
December 3132.28 07-DEC-07:01 9126.89 9669.51 15209.12 0.00 0.00 0.00 0.00 0.00 33.55
                       
Annual Sum or Average                      
Minimum of Months 2306.76   3650.76 3867.81 6083.65 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5090.81   9126.89 9669.51 15209.12 0.00 0.00 0.00 0.00 6.18 69.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1189.06 06-JAN-07:01 0.00 3515.32 3307.58 0.00 0.00 0.00 0.00 0.00 0.00
February 1758.56 09-FEB-07:01 0.00 3515.32 3307.58 0.00 0.00 0.00 0.00 0.00 0.00
March 1838.25 30-MAR-06:02 0.00 3515.32 3307.58 0.00 0.00 0.00 0.00 0.00 0.00
April 1907.28 14-APR-06:02 0.00 3515.32 3307.58 0.00 0.00 0.00 0.00 0.00 0.00
May 2401.01 26-MAY-06:03 0.00 1406.13 1323.03 0.00 0.00 0.00 0.00 0.00 0.00
June 2494.91 29-JUN-06:03 0.00 1406.13 1323.03 0.00 0.00 0.00 0.00 0.00 0.00
July 2419.61 21-JUL-06:03 0.00 1406.13 1323.03 0.00 0.00 0.00 0.00 0.00 0.00
August 2349.38 09-AUG-06:03 0.00 1406.13 1323.03 0.00 0.00 0.00 0.00 0.00 0.00
September 2249.39 01-SEP-06:01 0.00 2812.26 2646.06 0.00 0.00 0.00 0.00 0.00 0.00
October 1937.52 20-OCT-06:02 0.00 3515.32 3307.58 0.00 0.00 0.00 0.00 0.00 0.00
November 1837.89 02-NOV-06:02 0.00 3515.32 3307.58 0.00 0.00 0.00 0.00 0.00 0.00
December 1251.17 01-DEC-07:01 0.00 3515.32 3307.58 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 1189.06   0.00 1406.13 1323.03 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2494.91   0.00 3515.32 3307.58 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 160.59 07-JAN-15:02 0.00 60.62 96.37 0.00 0.00 0.00 0.00 0.00 10.66
February 115.11 08-FEB-18:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 3.32
March 115.39 29-MAR-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 3.64
April 163.65 13-APR-17:01 0.00 121.25 96.37 0.00 0.00 0.00 0.00 0.00 0.87
May 177.96 25-MAY-17:01 0.00 121.25 96.37 0.00 0.00 0.00 0.00 1.09 0.00
June 194.31 30-JUN-06:03 0.00 141.46 149.91 0.00 0.00 0.00 0.00 1.91 0.00
July 180.58 21-JUL-06:05 0.00 80.83 85.66 0.00 0.00 0.00 0.00 0.00 0.31
August 178.29 25-AUG-17:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 1.37 0.00
September 178.00 01-SEP-17:01 0.00 121.25 96.37 0.00 0.00 0.00 0.00 0.77 0.00
October 167.54 21-OCT-14:01 0.00 53.89 85.66 0.00 0.00 0.00 0.00 0.00 0.27
November 147.32 01-NOV-17:01 0.00 107.78 85.66 0.00 0.00 0.00 0.00 0.00 0.62
December 152.97 02-DEC-15:03 0.00 53.89 85.66 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 115.11   0.00 53.89 85.66 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 194.31   0.00 141.46 149.91 0.00 0.00 0.00 0.00 1.91 10.66



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 2 X-RAY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16333.96 06-JAN-07:01 19441.89 5938.92 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
February 16007.09 14-FEB-07:01 19441.89 5938.92 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
March 11371.43 16-MAR-06:01 19441.89 5938.92 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
April 9205.61 18-APR-05:01 10801.05 3959.28 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
May 10727.83 26-MAY-05:01 10801.05 3959.28 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
June 10964.31 29-JUN-05:01 10801.05 3959.28 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
July 10585.15 21-JUL-05:01 10801.05 3959.28 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
August 10504.83 09-AUG-05:01 10801.05 3959.28 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
September 10158.07 01-SEP-05:01 10801.05 3959.28 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
October 8880.69 20-OCT-05:01 10801.05 3959.28 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
November 10287.00 29-NOV-06:01 10801.05 3959.28 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
December 14529.60 20-DEC-07:01 19441.89 5938.92 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 8880.69   10801.05 3959.28 89142.19 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16333.96   19441.89 5938.92 89142.19 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 59.65 27-JAN-15:55 90.73 96.12 183.03 0.00 0.00 0.00 0.00 0.00 0.00
February 72.57 08-FEB-17:00 22.68 24.03 45.76 0.00 0.00 0.00 0.00 0.00 3.63
March 84.79 23-MAR-15:30 22.68 24.03 45.76 0.00 0.00 0.00 0.00 0.00 2.45
April 100.41 21-APR-16:00 22.68 24.03 45.76 0.00 0.00 0.00 0.00 0.00 0.97
May 103.26 18-MAY-15:40 22.68 24.03 45.76 0.00 0.00 0.00 0.00 1.14 0.00
June 106.35 16-JUN-06:01 226.82 240.31 457.58 0.00 0.00 0.00 0.00 0.00 1.12
July 103.79 19-JUL-15:30 22.68 24.03 45.76 0.00 0.00 0.00 0.00 0.54 0.00
August 103.81 03-AUG-06:01 226.82 240.31 457.58 0.00 0.00 0.00 0.00 0.00 1.14
September 100.68 22-SEP-06:01 226.82 240.31 457.58 0.00 0.00 0.00 0.00 0.00 1.17
October 88.34 20-OCT-15:00 22.68 24.03 45.76 0.00 0.00 0.00 0.00 0.00 0.82
November 75.01 01-NOV-16:40 22.68 24.03 45.76 0.00 0.00 0.00 0.00 0.00 0.69
December 58.40 05-DEC-18:00 22.68 24.03 45.76 0.00 0.00 0.00 0.00 0.00 2.12
                       
Annual Sum or Average                      
Minimum of Months 58.40   22.68 24.03 45.76 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 106.35   226.82 240.31 457.58 0.00 0.00 0.00 0.00 1.14 3.63



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 149.53 07-JAN-15:02 0.00 467.87 660.33 0.00 0.00 0.00 0.00 0.00 0.09
February 134.76 24-FEB-06:03 0.00 1039.70 1467.39 0.00 0.00 0.00 0.00 0.00 0.15
March 138.09 31-MAR-17:00 0.00 155.96 146.74 0.00 0.00 0.00 0.00 0.00 0.04
April 273.96 13-APR-16:50 0.00 155.96 146.74 0.00 0.00 0.00 0.00 0.00 0.01
May 476.45 18-MAY-15:50 0.00 155.96 146.74 0.00 0.00 0.00 0.00 0.01 0.00
June 890.80 30-JUN-06:03 0.00 1091.69 1027.17 0.00 0.00 0.00 0.00 0.01 0.00
July 708.74 14-JUL-06:02 0.00 935.73 880.44 0.00 0.00 0.00 0.00 0.00 0.00
August 689.99 10-AUG-06:01 0.00 1403.60 1320.65 0.00 0.00 0.00 0.00 0.00 0.00
September 451.64 01-SEP-16:00 0.00 155.96 146.74 0.00 0.00 0.00 0.00 0.01 0.00
October 292.08 20-OCT-15:50 0.00 155.96 146.74 0.00 0.00 0.00 0.00 0.00 0.01
November 165.73 01-NOV-17:00 0.00 155.96 146.74 0.00 0.00 0.00 0.00 0.00 0.01
December 154.60 02-DEC-17:10 0.00 51.99 73.37 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 134.76   0.00 51.99 73.37 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 890.80   0.00 1403.60 1467.39 0.00 0.00 0.00 0.00 0.01 0.15



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 177.14 27-JAN-15:55 233.30 247.17 470.65 0.00 0.00 0.00 0.00 0.00 0.00
February 215.18 08-FEB-17:25 116.65 123.59 235.33 0.00 0.00 0.00 0.00 0.00 8.33
March 242.17 23-MAR-15:30 58.33 61.79 117.66 0.00 0.00 0.00 0.00 0.00 6.31
April 322.29 14-APR-06:01 583.26 617.93 1176.64 0.00 0.00 0.00 0.00 0.00 1.41
May 379.33 18-MAY-06:01 408.28 432.55 823.65 0.00 0.00 0.00 0.00 0.00 0.12
June 434.04 30-JUN-06:01 408.28 432.55 823.65 0.00 0.00 0.00 0.00 3.33 0.00
July 371.96 19-JUL-06:01 408.28 432.55 823.65 0.00 0.00 0.00 0.00 0.00 0.00
August 377.94 10-AUG-06:01 524.93 556.14 1058.97 0.00 0.00 0.00 0.00 0.00 0.28
September 330.70 22-SEP-06:01 583.26 617.93 1176.64 0.00 0.00 0.00 0.00 0.00 3.10
October 325.75 26-OCT-06:01 583.26 617.93 1176.64 0.00 0.00 0.00 0.00 0.00 6.13
November 217.94 17-NOV-17:00 116.65 123.59 235.33 0.00 0.00 0.00 0.00 0.00 11.39
December 173.63 28-DEC-18:00 58.33 61.79 117.66 0.00 0.00 0.00 0.00 0.00 17.09
                       
Annual Sum or Average                      
Minimum of Months 173.63   58.33 61.79 117.66 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 434.04   583.26 617.93 1176.64 0.00 0.00 0.00 0.00 3.33 17.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 76.65 07-JAN-15:02 0.00 43.39 28.17 0.00 0.00 0.00 0.00 0.00 6.44
February 54.78 08-FEB-18:01 0.00 96.43 31.30 0.00 0.00 0.00 0.00 0.00 2.01
March 55.19 28-MAR-17:01 0.00 86.78 28.17 0.00 0.00 0.00 0.00 0.00 1.45
April 78.80 13-APR-17:01 0.00 86.78 28.17 0.00 0.00 0.00 0.00 0.00 0.56
May 95.14 25-MAY-19:00 0.00 9.64 3.13 0.00 0.00 0.00 0.00 0.43 0.00
June 104.95 30-JUN-17:00 0.00 14.46 6.26 0.00 0.00 0.00 0.00 2.28 0.00
July 95.19 29-JUL-18:30 0.00 4.82 3.13 0.00 0.00 0.00 0.00 0.38 0.00
August 92.63 11-AUG-18:00 0.00 9.64 3.13 0.00 0.00 0.00 0.00 0.39 0.00
September 90.63 01-SEP-17:00 0.00 14.46 6.26 0.00 0.00 0.00 0.00 0.42 0.00
October 80.80 21-OCT-14:01 0.00 38.57 25.04 0.00 0.00 0.00 0.00 0.00 0.19
November 70.78 01-NOV-17:01 0.00 77.14 25.04 0.00 0.00 0.00 0.00 0.00 0.38
December 73.11 09-DEC-15:03 0.00 38.57 25.04 0.00 0.00 0.00 0.00 0.00 13.20
                       
Annual Sum or Average                      
Minimum of Months 54.78   0.00 4.82 3.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 104.95   0.00 96.43 31.30 0.00 0.00 0.00 0.00 2.28 13.20



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 LOCKER

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 453.39 19-JAN-07:01 1944.19 637.20 3565.47 0.00 0.00 0.00 0.00 0.00 12.79
February 466.63 08-FEB-07:02 1944.19 637.20 3565.47 0.00 0.00 0.00 0.00 0.00 13.08
March 540.14 23-MAR-06:01 1944.19 637.20 3565.47 0.00 0.00 0.00 0.00 0.00 0.00
April 536.47 18-APR-06:02 1749.77 573.48 3208.92 0.00 0.00 0.00 0.00 0.00 7.83
May 621.12 26-MAY-06:03 777.68 254.88 1426.19 0.00 0.00 0.00 0.00 0.00 1.70
June 680.09 30-JUN-06:03 1360.93 446.04 2495.83 0.00 0.00 0.00 0.00 3.68 0.00
July 621.43 21-JUL-06:03 777.68 254.88 1426.19 0.00 0.00 0.00 0.00 0.00 1.37
August 613.55 09-AUG-06:03 777.68 254.88 1426.19 0.00 0.00 0.00 0.00 0.00 2.64
September 590.18 01-SEP-06:02 1555.35 509.76 2852.37 0.00 0.00 0.00 0.00 0.00 2.75
October 500.70 20-OCT-06:02 1944.19 637.20 3565.47 0.00 0.00 0.00 0.00 0.00 3.78
November 511.45 21-NOV-07:01 1944.19 637.20 3565.47 0.00 0.00 0.00 0.00 0.00 11.37
December 468.99 06-DEC-07:02 1944.19 637.20 3565.47 0.00 0.00 0.00 0.00 0.00 17.86
                       
Annual Sum or Average                      
Minimum of Months 453.39   777.68 254.88 1426.19 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 680.09   1944.19 637.20 3565.47 0.00 0.00 0.00 0.00 3.68 17.86



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2864.58 20-JAN-07:02 12297.00 4030.29 22551.58 0.00 0.00 0.00 0.00 0.00 2.05
February 2882.72 23-FEB-07:02 12297.00 4030.29 22551.58 0.00 0.00 0.00 0.00 0.00 1.33
March 3251.97 23-MAR-06:01 12297.00 4030.29 22551.58 0.00 0.00 0.00 0.00 0.00 0.00
April 3163.41 18-APR-06:02 11067.30 2275.92 20296.42 0.00 0.00 0.00 0.00 0.00 0.42
May 3656.02 26-MAY-06:03 4918.80 838.30 9020.63 0.00 0.00 0.00 0.00 0.00 0.09
June 4035.60 30-JUN-06:03 8607.90 1939.35 15786.10 0.00 0.00 0.00 0.00 0.18 0.00
July 3794.55 05-JUL-06:03 4918.80 838.30 9020.63 0.00 0.00 0.00 0.00 0.00 0.06
August 3615.44 09-AUG-06:03 4918.80 1067.56 9020.63 0.00 0.00 0.00 0.00 0.00 0.14
September 3500.63 01-SEP-06:02 9837.60 2138.89 18041.26 0.00 0.00 0.00 0.00 0.00 0.15
October 2953.40 03-OCT-06:02 12297.00 4030.29 22551.58 0.00 0.00 0.00 0.00 0.00 1.01
November 2994.42 21-NOV-07:01 12297.00 4030.29 22551.58 0.00 0.00 0.00 0.00 0.00 0.60
December 3404.02 01-DEC-07:01 12297.00 4030.29 22551.58 0.00 0.00 0.00 0.00 0.00 2.59
                       
Annual Sum or Average                      
Minimum of Months 2864.58   4918.80 838.30 9020.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4035.60   12297.00 4030.29 22551.58 0.00 0.00 0.00 0.00 0.18 2.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 467.11 07-JAN-15:02 0.00 215.55 342.66 0.00 0.00 0.00 0.00 0.00 1.39
February 329.90 07-FEB-18:01 0.00 479.00 380.73 0.00 0.00 0.00 0.00 0.00 0.56
March 333.20 28-MAR-17:01 0.00 431.10 342.66 0.00 0.00 0.00 0.00 0.00 0.31
April 471.89 13-APR-17:01 0.00 431.10 342.66 0.00 0.00 0.00 0.00 0.00 0.12
May 523.68 26-MAY-06:05 0.00 287.40 304.58 0.00 0.00 0.00 0.00 0.00 0.05
June 554.96 29-JUN-06:05 0.00 287.40 304.58 0.00 0.00 0.00 0.00 0.08 0.00
July 521.93 21-JUL-06:05 0.00 287.40 304.58 0.00 0.00 0.00 0.00 0.00 0.04
August 513.68 09-AUG-06:05 0.00 287.40 304.58 0.00 0.00 0.00 0.00 0.00 0.09
September 510.16 01-SEP-17:01 0.00 431.10 342.66 0.00 0.00 0.00 0.00 0.10 0.00
October 485.11 21-OCT-14:01 0.00 191.60 304.58 0.00 0.00 0.00 0.00 0.00 0.04
November 425.27 01-NOV-17:01 0.00 383.20 304.58 0.00 0.00 0.00 0.00 0.00 0.08
December 443.37 09-DEC-15:03 0.00 191.60 304.58 0.00 0.00 0.00 0.00 0.00 2.85
                       
Annual Sum or Average                      
Minimum of Months 329.90   0.00 191.60 304.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 554.96   0.00 479.00 380.73 0.00 0.00 0.00 0.00 0.10 2.85



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7966.58 06-JAN-06:01 0.00 2940.00 17333.20 0.00 0.00 0.00 0.00 0.00 0.00
February 7485.93 14-FEB-06:01 0.00 2940.00 17333.20 0.00 0.00 0.00 0.00 0.00 4.02
March 5837.14 16-MAR-05:01 0.00 2940.00 17333.20 0.00 0.00 0.00 0.00 0.00 4.18
April 5338.68 23-APR-15:25 0.00 98.00 1733.32 0.00 0.00 0.00 0.00 0.00 0.19
May 5568.69 26-MAY-06:00 0.00 294.00 1733.32 0.00 0.00 0.00 0.00 0.00 0.58
June 5862.18 28-JUN-06:00 0.00 294.00 1733.32 0.00 0.00 0.00 0.00 0.00 0.00
July 5769.01 21-JUL-06:00 0.00 294.00 1733.32 0.00 0.00 0.00 0.00 0.00 0.45
August 5763.29 20-AUG-08:32 0.00 245.00 4333.30 0.00 0.00 0.00 0.00 0.00 1.30
September 5492.72 10-SEP-09:50 0.00 49.00 866.66 0.00 0.00 0.00 0.00 0.00 1.21
October 5312.31 22-OCT-13:52 0.00 294.00 5199.96 0.00 0.00 0.00 0.00 0.00 0.63
November 5117.67 29-NOV-06:01 0.00 2940.00 17333.20 0.00 0.00 0.00 0.00 0.00 2.52
December 6832.33 20-DEC-06:01 0.00 2940.00 17333.20 0.00 0.00 0.00 0.00 0.00 5.36
                       
Annual Sum or Average                      
Minimum of Months 5117.67   0.00 49.00 866.66 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7966.58   0.00 2940.00 17333.20 0.00 0.00 0.00 0.00 0.00 5.36



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 186.53 06-JAN-06:03 0.00 843.00 1189.78 0.00 0.00 0.00 0.00 0.00 0.00
February 178.00 08-FEB-14:00 0.00 126.45 118.98 0.00 0.00 0.00 0.00 0.00 15.92
March 291.17 31-MAR-15:00 0.00 126.45 118.98 0.00 0.00 0.00 0.00 0.00 28.28
April 701.91 14-APR-06:01 0.00 1264.50 1189.78 0.00 0.00 0.00 0.00 0.00 3.91
May 956.97 26-MAY-06:03 0.00 505.80 475.91 0.00 0.00 0.00 0.00 0.00 3.84
June 1091.32 30-JUN-06:03 0.00 885.15 832.84 0.00 0.00 0.00 0.00 9.08 0.00
July 996.20 21-JUL-06:03 0.00 505.80 475.91 0.00 0.00 0.00 0.00 0.00 3.48
August 949.28 09-AUG-06:03 0.00 505.80 475.91 0.00 0.00 0.00 0.00 0.00 6.13
September 896.71 01-SEP-06:01 0.00 1011.60 951.82 0.00 0.00 0.00 0.00 0.00 7.00
October 710.02 20-OCT-06:01 0.00 1264.50 1189.78 0.00 0.00 0.00 0.00 0.00 9.23
November 272.13 01-NOV-16:10 0.00 126.45 118.98 0.00 0.00 0.00 0.00 0.00 4.89
December 146.65 20-DEC-07:04 0.00 1264.50 1189.78 0.00 0.00 0.00 0.00 0.00 99.87
                       
Annual Sum or Average                      
Minimum of Months 146.65   0.00 126.45 118.98 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1091.32   0.00 1264.50 1189.78 0.00 0.00 0.00 0.00 9.08 99.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2560.68 19-JAN-18:00 1639.60 1737.08 3307.66 0.00 0.00 0.00 0.00 0.00 3.34
February 3202.17 08-FEB-15:50 1639.60 1422.28 3307.66 0.00 0.00 0.00 0.00 0.00 2.00
March 4064.91 31-MAR-15:20 1639.60 1202.34 3307.66 0.00 0.00 0.00 0.00 0.00 1.75
April 6030.03 18-APR-06:01 14756.40 12312.96 29768.92 0.00 0.00 0.00 0.00 0.00 1.04
May 8163.43 26-MAY-06:05 6558.40 4921.20 13230.63 0.00 0.00 0.00 0.00 0.00 0.20
June 8986.34 30-JUN-06:03 11477.20 10639.45 23153.60 0.00 0.00 0.00 0.00 0.45 0.00
July 8242.59 21-JUL-06:05 6558.40 4307.96 13230.63 0.00 0.00 0.00 0.00 0.00 0.16
August 7951.49 09-AUG-06:03 6558.40 5811.51 13230.63 0.00 0.00 0.00 0.00 0.00 0.38
September 7748.56 01-SEP-06:02 13116.80 11746.07 26461.26 0.00 0.00 0.00 0.00 0.00 0.39
October 6090.22 20-OCT-06:02 16396.00 17370.80 33076.58 0.00 0.00 0.00 0.00 0.00 0.50
November 5890.71 02-NOV-06:02 16396.00 17370.80 33076.58 0.00 0.00 0.00 0.00 0.00 3.15
December 2502.35 05-DEC-18:00 1639.60 1737.08 3307.66 0.00 0.00 0.00 0.00 0.00 0.82
                       
Annual Sum or Average                      
Minimum of Months 2502.35   1639.60 1202.34 3307.66 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8986.34   16396.00 17370.80 33076.58 0.00 0.00 0.00 0.00 0.45 3.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 367.89 28-JAN-06:04 0.00 273.41 694.59 0.00 0.00 0.00 0.00 0.00 0.08
February 599.14 08-FEB-16:20 0.00 351.53 330.76 0.00 0.00 0.00 0.00 0.00 0.04
March 824.18 31-MAR-15:50 0.00 351.53 330.76 0.00 0.00 0.00 0.00 0.00 0.05
April 1088.47 13-APR-15:20 0.00 351.53 330.76 0.00 0.00 0.00 0.00 0.00 0.01
May 1837.82 19-MAY-06:01 0.00 3163.79 2976.82 0.00 0.00 0.00 0.00 0.00 0.00
June 2250.75 30-JUN-06:01 0.00 2460.72 2315.31 0.00 0.00 0.00 0.00 0.01 0.00
July 1968.91 14-JUL-06:02 0.00 2109.19 1984.55 0.00 0.00 0.00 0.00 0.00 0.00
August 1901.56 10-AUG-06:01 0.00 3163.79 2976.82 0.00 0.00 0.00 0.00 0.00 0.00
September 1329.14 01-SEP-15:50 0.00 351.53 330.76 0.00 0.00 0.00 0.00 0.01 0.00
October 1058.21 19-OCT-15:50 0.00 351.53 330.76 0.00 0.00 0.00 0.00 0.00 0.00
November 629.70 17-NOV-16:00 0.00 351.53 330.76 0.00 0.00 0.00 0.00 0.00 0.04
December 393.45 02-DEC-06:04 0.00 273.41 694.59 0.00 0.00 0.00 0.00 0.00 0.07
                       
Annual Sum or Average                      
Minimum of Months 367.89   0.00 273.41 330.76 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2250.75   0.00 3163.79 2976.82 0.00 0.00 0.00 0.00 0.01 0.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 131.86 07-JAN-15:02 0.00 60.62 96.37 0.00 0.00 0.00 0.00 0.00 1.18
February 93.74 08-FEB-18:01 0.00 134.72 107.08 0.00 0.00 0.00 0.00 0.00 0.37
March 94.18 31-MAR-17:01 0.00 107.78 85.66 0.00 0.00 0.00 0.00 0.00 0.53
April 134.10 13-APR-17:01 0.00 121.25 96.37 0.00 0.00 0.00 0.00 0.00 0.10
May 146.26 25-MAY-17:01 0.00 121.25 96.37 0.00 0.00 0.00 0.00 0.12 0.00
June 156.10 30-JUN-06:03 0.00 141.46 149.91 0.00 0.00 0.00 0.00 0.22 0.00
July 147.39 21-JUL-06:05 0.00 80.83 85.66 0.00 0.00 0.00 0.00 0.00 0.04
August 146.28 11-AUG-17:01 0.00 121.25 96.37 0.00 0.00 0.00 0.00 0.12 0.00
September 145.98 01-SEP-17:01 0.00 121.25 96.37 0.00 0.00 0.00 0.00 0.08 0.00
October 137.27 21-OCT-14:01 0.00 53.89 85.66 0.00 0.00 0.00 0.00 0.00 0.03
November 120.29 01-NOV-17:01 0.00 107.78 85.66 0.00 0.00 0.00 0.00 0.00 0.07
December 126.01 09-DEC-15:03 0.00 53.89 85.66 0.00 0.00 0.00 0.00 0.00 2.43
                       
Annual Sum or Average                      
Minimum of Months 93.74   0.00 53.89 85.66 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 156.10   0.00 141.46 149.91 0.00 0.00 0.00 0.00 0.22 2.43



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5716.17 27-JAN-13:40 16849.64 4982.80 11591.36 0.00 0.00 0.00 0.00 0.00 0.00
February 6344.74 28-FEB-14:10 5616.55 1660.93 3863.79 0.00 0.00 0.00 0.00 0.00 8.60
March 6249.44 23-MAR-14:02 11233.09 3321.86 7727.57 0.00 0.00 0.00 0.00 0.00 0.43
April 6891.70 13-APR-13:20 2808.27 830.47 1931.89 0.00 0.00 0.00 0.00 0.00 0.99
May 6514.18 18-MAY-13:10 5616.55 1660.93 3863.79 0.00 0.00 0.00 0.00 1.51 0.00
June 6408.45 30-JUN-13:20 2808.27 830.47 1931.89 0.00 0.00 0.00 0.00 3.48 0.00
July 6147.89 21-JUL-13:50 2808.27 830.47 1931.89 0.00 0.00 0.00 0.00 1.80 0.00
August 6938.68 25-AUG-13:10 5616.55 1660.93 3863.79 0.00 0.00 0.00 0.00 1.42 0.00
September 7847.76 01-SEP-13:20 2808.27 830.47 1931.89 0.00 0.00 0.00 0.00 0.59 0.00
October 7716.24 19-OCT-12:45 5616.55 1660.93 3863.79 0.00 0.00 0.00 0.00 0.00 0.68
November 6082.52 17-NOV-13:30 2808.27 830.47 1931.89 0.00 0.00 0.00 0.00 0.00 6.62
December 4824.77 20-DEC-13:30 2808.27 830.47 1931.89 0.00 0.00 0.00 0.00 0.00 11.79
                       
Annual Sum or Average                      
Minimum of Months 4824.77   2808.27 830.47 1931.89 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7847.76   16849.64 4982.80 11591.36 0.00 0.00 0.00 0.00 3.48 11.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2470.77 13-JAN-06:02 7104.69 2521.21 8797.54 0.00 0.00 0.00 0.00 0.00 13.14
February 2516.67 17-FEB-06:02 7104.69 2521.21 8797.54 0.00 0.00 0.00 0.00 0.00 0.00
March 1922.10 16-MAR-05:03 7104.69 2521.21 8797.54 0.00 0.00 0.00 0.00 0.00 139.25
April 2245.62 13-APR-15:00 1278.84 378.18 879.75 0.00 0.00 0.00 0.00 0.00 5.27
May 2337.75 18-MAY-15:10 1278.84 378.18 879.75 0.00 0.00 0.00 0.00 18.76 0.00
June 2469.44 30-JUN-06:03 8951.91 2647.27 6158.28 0.00 0.00 0.00 0.00 22.01 0.00
July 2335.70 19-JUL-16:00 1278.84 378.18 879.75 0.00 0.00 0.00 0.00 9.08 0.00
August 2340.02 25-AUG-15:10 1278.84 378.18 879.75 0.00 0.00 0.00 0.00 19.81 0.00
September 2313.14 01-SEP-15:40 1278.84 378.18 879.75 0.00 0.00 0.00 0.00 12.83 0.00
October 2281.67 19-OCT-14:05 2557.69 756.36 1759.51 0.00 0.00 0.00 0.00 2.96 0.00
November 1954.61 01-NOV-16:10 1278.84 378.18 879.75 0.00 0.00 0.00 0.00 0.00 7.35
December 2122.28 20-DEC-06:02 7104.69 2521.21 8797.54 0.00 0.00 0.00 0.00 0.00 182.80
                       
Annual Sum or Average                      
Minimum of Months 1922.10   1278.84 378.18 879.75 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2516.67   8951.91 2647.27 8797.54 0.00 0.00 0.00 0.00 22.01 182.80



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 224.09 11-JAN-07:03 0.00 314.34 333.14 0.00 0.00 0.00 0.00 0.00 0.00
February 266.94 17-FEB-07:03 0.00 314.34 333.14 0.00 0.00 0.00 0.00 0.00 0.00
March 174.86 16-MAR-06:03 0.00 314.34 333.14 0.00 0.00 0.00 0.00 0.00 22.62
April 219.88 13-APR-17:01 0.00 188.61 149.91 0.00 0.00 0.00 0.00 0.00 1.51
May 243.20 26-MAY-06:05 0.00 125.74 133.25 0.00 0.00 0.00 0.00 0.00 0.63
June 256.74 30-JUN-06:03 0.00 220.04 233.20 0.00 0.00 0.00 0.00 3.20 0.00
July 241.56 21-JUL-06:05 0.00 125.74 133.25 0.00 0.00 0.00 0.00 0.00 0.54
August 238.93 09-AUG-06:05 0.00 125.74 133.25 0.00 0.00 0.00 0.00 0.00 1.10
September 237.07 01-SEP-17:01 0.00 188.61 149.91 0.00 0.00 0.00 0.00 1.27 0.00
October 226.23 21-OCT-14:01 0.00 83.83 133.25 0.00 0.00 0.00 0.00 0.00 0.52
November 198.96 01-NOV-17:01 0.00 167.65 133.25 0.00 0.00 0.00 0.00 0.00 1.06
December 253.67 21-DEC-07:03 0.00 314.34 333.14 0.00 0.00 0.00 0.00 0.00 4.49
                       
Annual Sum or Average                      
Minimum of Months 174.86   0.00 83.83 133.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 266.94   0.00 314.34 333.14 0.00 0.00 0.00 0.00 3.20 22.62



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 224.11 07-JAN-15:02 0.00 74.39 48.30 0.00 0.00 0.00 0.00 0.00 22.94
February 164.77 03-FEB-07:03 0.00 247.95 107.33 0.00 0.00 0.00 0.00 0.00 21.00
March 166.34 04-MAR-07:05 0.00 33.06 21.47 0.00 0.00 0.00 0.00 0.00 19.08
April 220.20 13-APR-17:01 0.00 148.77 48.30 0.00 0.00 0.00 0.00 0.00 1.93
May 243.32 26-MAY-06:05 0.00 99.18 42.93 0.00 0.00 0.00 0.00 0.00 0.80
June 256.87 29-JUN-06:05 0.00 99.18 42.93 0.00 0.00 0.00 0.00 1.29 0.00
July 241.86 21-JUL-06:05 0.00 99.18 42.93 0.00 0.00 0.00 0.00 0.00 0.69
August 239.22 09-AUG-06:05 0.00 99.18 42.93 0.00 0.00 0.00 0.00 0.00 1.40
September 237.60 01-SEP-17:01 0.00 148.77 48.30 0.00 0.00 0.00 0.00 1.63 0.00
October 226.92 21-OCT-14:01 0.00 66.12 42.93 0.00 0.00 0.00 0.00 0.00 0.66
November 198.81 01-NOV-17:01 0.00 132.24 42.93 0.00 0.00 0.00 0.00 0.00 1.35
December 214.34 02-DEC-15:03 0.00 66.12 42.93 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 164.77   0.00 33.06 21.47 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 256.87   0.00 247.95 107.33 0.00 0.00 0.00 0.00 1.63 22.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 91.80 26-JAN-06:03 0.00 128.57 83.48 0.00 0.00 0.00 0.00 0.00 12.33
February 89.40 17-FEB-06:03 0.00 128.57 83.48 0.00 0.00 0.00 0.00 0.00 0.00
March 62.01 16-MAR-05:03 0.00 128.57 83.48 0.00 0.00 0.00 0.00 0.00 19.76
April 78.66 13-APR-15:30 0.00 19.29 8.35 0.00 0.00 0.00 0.00 0.00 1.40
May 114.52 18-MAY-15:20 0.00 19.29 8.35 0.00 0.00 0.00 0.00 2.34 0.00
June 128.12 30-JUN-15:00 0.00 19.29 8.35 0.00 0.00 0.00 0.00 9.27 0.00
July 118.28 21-JUL-15:00 0.00 19.29 8.35 0.00 0.00 0.00 0.00 4.70 0.00
August 112.26 11-AUG-15:50 0.00 19.29 8.35 0.00 0.00 0.00 0.00 1.09 0.00
September 101.55 01-SEP-15:50 0.00 19.29 8.35 0.00 0.00 0.00 0.00 1.42 0.00
October 77.88 19-OCT-16:00 0.00 19.29 8.35 0.00 0.00 0.00 0.00 0.00 0.26
November 69.25 01-NOV-15:00 0.00 19.29 8.35 0.00 0.00 0.00 0.00 0.00 1.28
December 72.27 02-DEC-17:10 0.00 6.43 4.17 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 62.01   0.00 6.43 4.17 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 128.12   0.00 128.57 83.48 0.00 0.00 0.00 0.00 9.27 19.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1942.68 13-JAN-06:02 5712.56 3998.40 5185.92 0.00 0.00 0.00 0.00 0.00 10.57
February 1979.61 17-FEB-06:02 5712.56 3998.40 5185.92 0.00 0.00 0.00 0.00 0.00 0.00
March 1589.96 16-MAR-05:03 5712.56 3998.40 5185.92 0.00 0.00 0.00 0.00 0.00 112.07
April 1838.56 13-APR-15:00 1028.26 599.76 518.59 0.00 0.00 0.00 0.00 0.00 5.34
May 1912.03 18-MAY-16:20 1028.26 599.76 518.59 0.00 0.00 0.00 0.00 13.48 0.00
June 1948.80 30-JUN-06:03 7197.82 4198.32 3630.14 0.00 0.00 0.00 0.00 17.52 0.00
July 1909.97 28-JUL-17:00 1028.26 599.76 518.59 0.00 0.00 0.00 0.00 26.46 0.00
August 1913.34 25-AUG-16:20 1028.26 599.76 518.59 0.00 0.00 0.00 0.00 12.98 0.00
September 1893.07 01-SEP-16:10 1028.26 599.76 518.59 0.00 0.00 0.00 0.00 8.71 0.00
October 1869.26 19-OCT-15:40 1028.26 599.76 518.59 0.00 0.00 0.00 0.00 1.18 0.00
November 1667.24 01-NOV-15:00 1028.26 599.76 518.59 0.00 0.00 0.00 0.00 0.00 6.25
December 1668.70 20-DEC-06:02 5712.56 3998.40 5185.92 0.00 0.00 0.00 0.00 0.00 147.03
                       
Annual Sum or Average                      
Minimum of Months 1589.96   1028.26 599.76 518.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1979.61   7197.82 4198.32 5185.92 0.00 0.00 0.00 0.00 26.46 147.03



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3108.83 27-JAN-15:02 0.00 2603.49 12354.69 0.00 0.00 0.00 0.00 0.00 0.00
February 4672.39 28-FEB-15:30 0.00 520.70 2470.94 0.00 0.00 0.00 0.00 0.00 2.83
March 5029.32 31-MAR-15:00 0.00 520.70 2470.94 0.00 0.00 0.00 0.00 0.00 1.94
April 5343.57 13-APR-15:00 0.00 520.70 2470.94 0.00 0.00 0.00 0.00 0.00 0.29
May 6167.66 25-MAY-16:40 0.00 520.70 2470.94 0.00 0.00 0.00 0.00 0.43 0.00
June 6942.68 30-JUN-06:01 0.00 3644.89 17296.57 0.00 0.00 0.00 0.00 0.64 0.00
July 5986.95 21-JUL-16:00 0.00 520.70 2470.94 0.00 0.00 0.00 0.00 0.79 0.00
August 6072.90 11-AUG-16:20 0.00 520.70 2470.94 0.00 0.00 0.00 0.00 0.33 0.00
September 6427.09 01-SEP-15:30 0.00 520.70 2470.94 0.00 0.00 0.00 0.00 0.37 0.00
October 5876.30 19-OCT-14:40 0.00 520.70 2470.94 0.00 0.00 0.00 0.00 0.00 0.04
November 4087.97 17-NOV-13:30 0.00 520.70 2470.94 0.00 0.00 0.00 0.00 0.00 2.67
December 2055.71 02-DEC-15:04 0.00 1388.53 9883.75 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 2055.71   0.00 520.70 2470.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6942.68   0.00 3644.89 17296.57 0.00 0.00 0.00 0.00 0.79 2.83



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1379.54 27-JAN-15:20 0.00 528.96 2510.16 0.00 0.00 0.00 0.00 0.00 0.00
February 2218.61 28-FEB-15:30 0.00 264.48 1255.08 0.00 0.00 0.00 0.00 0.00 3.33
March 2510.24 31-MAR-14:50 0.00 264.48 1255.08 0.00 0.00 0.00 0.00 0.00 2.28
April 2789.08 13-APR-14:40 0.00 264.48 1255.08 0.00 0.00 0.00 0.00 0.00 0.40
May 3251.87 25-MAY-16:40 0.00 264.48 1255.08 0.00 0.00 0.00 0.00 0.50 0.00
June 3656.29 30-JUN-06:01 0.00 1851.37 8785.56 0.00 0.00 0.00 0.00 0.69 0.00
July 3205.10 21-JUL-16:00 0.00 264.48 1255.08 0.00 0.00 0.00 0.00 0.93 0.00
August 3242.38 11-AUG-16:30 0.00 264.48 1255.08 0.00 0.00 0.00 0.00 0.40 0.00
September 3512.09 01-SEP-15:00 0.00 264.48 1255.08 0.00 0.00 0.00 0.00 0.46 0.00
October 3126.66 19-OCT-14:30 0.00 264.48 1255.08 0.00 0.00 0.00 0.00 0.00 0.06
November 2055.09 17-NOV-13:30 0.00 264.48 1255.08 0.00 0.00 0.00 0.00 0.00 3.14
December 1018.52 02-DEC-15:04 0.00 705.28 5020.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 1018.52   0.00 264.48 1255.08 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3656.29   0.00 1851.37 8785.56 0.00 0.00 0.00 0.00 0.93 3.33



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 172.87 07-JAN-15:02 0.00 148.77 96.60 0.00 0.00 0.00 0.00 0.00 46.19
February 178.55 25-FEB-06:04 0.00 38.57 45.08 0.00 0.00 0.00 0.00 0.00 4.63
March 123.26 23-MAR-14:02 0.00 198.36 85.86 0.00 0.00 0.00 0.00 0.00 1.75
April 179.52 13-APR-15:00 0.00 49.59 21.47 0.00 0.00 0.00 0.00 0.00 2.07
May 194.51 18-MAY-15:20 0.00 49.59 21.47 0.00 0.00 0.00 0.00 6.36 0.00
June 197.79 30-JUN-15:10 0.00 49.59 21.47 0.00 0.00 0.00 0.00 23.02 0.00
July 194.81 21-JUL-15:50 0.00 49.59 21.47 0.00 0.00 0.00 0.00 9.40 0.00
August 193.94 25-AUG-15:40 0.00 49.59 21.47 0.00 0.00 0.00 0.00 6.30 0.00
September 190.52 01-SEP-15:50 0.00 49.59 21.47 0.00 0.00 0.00 0.00 4.22 0.00
October 183.17 19-OCT-15:10 0.00 49.59 21.47 0.00 0.00 0.00 0.00 1.54 0.00
November 153.94 01-NOV-16:20 0.00 49.59 21.47 0.00 0.00 0.00 0.00 0.00 2.73
December 179.52 02-DEC-17:10 0.00 16.53 10.73 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 123.26   0.00 16.53 10.73 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 197.79   0.00 198.36 96.60 0.00 0.00 0.00 0.00 23.02 46.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FLOOR 3 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 354.78 19-JAN-13:30 309.99 328.42 625.36 0.00 0.00 0.00 0.00 0.00 3.53
February 705.80 28-FEB-09:53 929.97 985.26 1876.08 0.00 0.00 0.00 0.00 0.00 4.08
March 1431.96 31-MAR-09:40 309.99 328.42 625.36 0.00 0.00 0.00 0.00 0.00 5.32
April 2417.21 18-APR-06:01 2789.91 2955.78 5628.25 0.00 0.00 0.00 0.00 0.00 1.64
May 3010.41 26-MAY-06:03 1239.96 1313.68 2501.44 0.00 0.00 0.00 0.00 0.00 0.33
June 3209.49 29-JUN-06:03 1239.96 1313.68 2501.44 0.00 0.00 0.00 0.00 0.09 0.00
July 3083.69 21-JUL-06:03 1239.96 1313.68 2501.44 0.00 0.00 0.00 0.00 0.00 0.28
August 2955.26 09-AUG-06:03 1239.96 1313.68 2501.44 0.00 0.00 0.00 0.00 0.00 0.51
September 2842.60 01-SEP-06:01 2479.92 2627.36 5002.89 0.00 0.00 0.00 0.00 0.00 0.60
October 1792.58 19-OCT-09:10 619.98 656.84 1250.72 0.00 0.00 0.00 0.00 0.00 1.71
November 846.95 01-NOV-15:30 309.99 328.42 625.36 0.00 0.00 0.00 0.00 0.00 0.43
December 443.89 28-DEC-15:07 929.97 985.26 1876.08 0.00 0.00 0.00 0.00 0.00 2.52
                       
Annual Sum or Average                      
Minimum of Months 354.78   309.99 328.42 625.36 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3209.49   2789.91 2955.78 5628.25 0.00 0.00 0.00 0.00 0.09 5.32



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: NE STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 110.40 07-JAN-15:02 0.00 212.44 299.82 0.00 0.00 0.00 0.00 0.00 68.81
February 77.96 21-FEB-18:01 0.00 472.08 333.14 0.00 0.00 0.00 0.00 0.00 66.25
March 78.71 28-MAR-17:01 0.00 424.87 299.82 0.00 0.00 0.00 0.00 0.00 15.48
April 123.60 13-APR-15:20 0.00 70.81 66.63 0.00 0.00 0.00 0.00 0.00 3.78
May 615.04 18-MAY-14:30 0.00 70.81 66.63 0.00 0.00 0.00 0.00 9.44 0.00
June 910.60 29-JUN-15:00 0.00 70.81 66.63 0.00 0.00 0.00 0.00 35.70 0.00
July 912.03 21-JUL-13:30 0.00 70.81 66.63 0.00 0.00 0.00 0.00 11.74 0.00
August 817.21 08-AUG-14:40 0.00 70.81 66.63 0.00 0.00 0.00 0.00 24.53 0.00
September 630.53 01-SEP-14:20 0.00 70.81 66.63 0.00 0.00 0.00 0.00 6.28 0.00
October 160.82 20-OCT-14:10 0.00 141.62 133.25 0.00 0.00 0.00 0.00 0.00 7.72
November 116.23 01-NOV-15:00 0.00 70.81 66.63 0.00 0.00 0.00 0.00 0.00 4.51
December 104.92 02-DEC-15:03 0.00 188.83 266.51 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 77.96   0.00 70.81 66.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 912.03   0.00 472.08 333.14 0.00 0.00 0.00 0.00 35.70 68.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: NW ELEVATOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 74.07 07-JAN-15:02 0.00 177.03 249.85 0.00 0.00 0.00 0.00 0.00 50.89
February 53.41 08-FEB-17:00 0.00 59.01 55.52 0.00 0.00 0.00 0.00 0.00 19.67
March 57.29 31-MAR-17:12 0.00 196.70 138.81 0.00 0.00 0.00 0.00 0.00 24.47
April 175.66 13-APR-17:00 0.00 59.01 55.52 0.00 0.00 0.00 0.00 0.00 6.25
May 585.15 25-MAY-17:00 0.00 59.01 55.52 0.00 0.00 0.00 0.00 4.55 0.00
June 683.62 30-JUN-17:00 0.00 59.01 55.52 0.00 0.00 0.00 0.00 17.86 0.00
July 665.07 24-JUL-17:00 0.00 59.01 55.52 0.00 0.00 0.00 0.00 7.89 0.00
August 721.02 11-AUG-17:00 0.00 59.01 55.52 0.00 0.00 0.00 0.00 3.97 0.00
September 694.73 01-SEP-16:50 0.00 59.01 55.52 0.00 0.00 0.00 0.00 2.87 0.00
October 391.65 19-OCT-16:30 0.00 59.01 55.52 0.00 0.00 0.00 0.00 0.00 2.63
November 76.16 01-NOV-15:00 0.00 59.01 55.52 0.00 0.00 0.00 0.00 0.00 3.42
December 73.60 02-DEC-17:10 0.00 19.67 27.76 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 53.41   0.00 19.67 27.76 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 721.02   0.00 196.70 249.85 0.00 0.00 0.00 0.00 17.86 50.89



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: NW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 127.14 07-JAN-15:02 0.00 242.78 342.66 0.00 0.00 0.00 0.00 0.00 78.72
February 89.47 07-FEB-18:01 0.00 539.52 380.73 0.00 0.00 0.00 0.00 0.00 31.51
March 90.35 28-MAR-17:01 0.00 485.57 342.66 0.00 0.00 0.00 0.00 0.00 17.70
April 139.34 23-APR-18:00 0.00 4.50 22.84 0.00 0.00 0.00 0.00 24.15 0.00
May 690.08 18-MAY-16:30 0.00 80.93 76.15 0.00 0.00 0.00 0.00 9.73 0.00
June 1722.70 30-JUN-06:01 0.00 566.50 533.02 0.00 0.00 0.00 0.00 11.27 0.00
July 975.05 21-JUL-16:07 0.00 242.78 228.44 0.00 0.00 0.00 0.00 13.74 0.00
August 907.88 08-AUG-16:40 0.00 80.93 76.15 0.00 0.00 0.00 0.00 26.66 0.00
September 700.64 01-SEP-16:30 0.00 80.93 76.15 0.00 0.00 0.00 0.00 5.23 0.00
October 156.75 19-OCT-16:00 0.00 80.93 76.15 0.00 0.00 0.00 0.00 0.00 1.38
November 136.48 01-NOV-15:00 0.00 80.93 76.15 0.00 0.00 0.00 0.00 0.00 5.49
December 121.01 09-DEC-15:03 0.00 215.81 304.58 0.00 0.00 0.00 0.00 0.00 161.37
                       
Annual Sum or Average                      
Minimum of Months 89.47   0.00 4.50 22.84 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1722.70   0.00 566.50 533.02 0.00 0.00 0.00 0.00 26.66 161.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: SW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 60.09 27-JAN-15:37 0.00 121.39 114.22 0.00 0.00 0.00 0.00 0.00 0.00
February 217.00 28-FEB-15:40 0.00 40.46 38.07 0.00 0.00 0.00 0.00 0.00 24.83
March 218.37 31-MAR-15:50 0.00 40.46 38.07 0.00 0.00 0.00 0.00 0.00 23.26
April 359.24 13-APR-15:50 0.00 40.46 38.07 0.00 0.00 0.00 0.00 0.00 3.39
May 568.20 18-MAY-16:10 0.00 40.46 38.07 0.00 0.00 0.00 0.00 4.94 0.00
June 856.90 30-JUN-06:01 0.00 283.25 266.51 0.00 0.00 0.00 0.00 5.41 0.00
July 626.98 24-JUL-16:40 0.00 40.46 38.07 0.00 0.00 0.00 0.00 6.71 0.00
August 684.83 25-AUG-16:30 0.00 40.46 38.07 0.00 0.00 0.00 0.00 4.64 0.00
September 745.94 01-SEP-15:50 0.00 40.46 38.07 0.00 0.00 0.00 0.00 3.17 0.00
October 586.45 19-OCT-15:10 0.00 40.46 38.07 0.00 0.00 0.00 0.00 0.00 0.17
November 246.00 17-NOV-14:20 0.00 40.46 38.07 0.00 0.00 0.00 0.00 0.00 24.28
December 53.39 02-DEC-17:10 0.00 13.49 19.04 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 53.39   0.00 13.49 19.04 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 856.90   0.00 283.25 266.51 0.00 0.00 0.00 0.00 6.71 24.83



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP}
January 0.341560E+12 291538.95 09-JAN-07:19 0.315620E+12 181549.19 06-JAN-13:00
February 0.288795E+12 273247.97 14-FEB-07:10 0.237280E+12 181538.13 14-FEB-11:00
March 0.305452E+12 222485.53 16-MAR-06:10 0.201764E+12 164740.34 06-MAR-06:19
April 0.273325E+12 212563.90 13-APR-16:00 0.107596E+12 155761.20 05-APR-05:10
May 0.284449E+12 232589.65 25-MAY-15:00 0.748796E+11 99776.07 01-MAY-05:00
June 0.298989E+12 273202.82 29-JUN-15:00 0.664034E+11 50359.13 12-JUN-11:20
July 0.311419E+12 248590.69 21-JUL-15:20 0.648542E+11 48299.16 03-JUL-11:39
August 0.312610E+12 252539.65 08-AUG-14:00 0.644360E+11 47992.58 14-AUG-12:09
September 0.255504E+12 225124.98 01-SEP-14:50 0.653335E+11 53236.39 06-SEP-05:40
October 0.258273E+12 204060.09 19-OCT-14:00 0.900283E+11 139536.94 30-OCT-05:19
November 0.280783E+12 206379.95 13-NOV-07:10 0.150381E+12 164740.34 29-NOV-06:19
December 0.326077E+12 268817.21 26-DEC-07:10 0.292117E+12 181705.78 26-DEC-11:00
             
Annual Sum or Average 0.353724E+13     0.173069E+13    
Minimum of Months 0.255504E+12 204060.09   0.644360E+11 47992.58  
Maximum of Months 0.341560E+12 291538.95   0.315620E+12 181705.78  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.322416E+11 0.671449E+10 0.153788E+12 0.00 0.278340E+11 0.127005E+10 0.560834E+11 0.185936E+09 0.00 0.634427E+11 0.00 0.00 0.00
February 0.290675E+11 0.525917E+10 0.139395E+12 0.00 0.258266E+11 0.980687E+09 0.335769E+11 0.152469E+10 0.00 0.531643E+11 0.00 0.00 0.00
March 0.341738E+11 0.477048E+10 0.160009E+12 0.00 0.294973E+11 0.886372E+09 0.249414E+11 0.326396E+10 0.00 0.479097E+11 0.00 0.00 0.00
April 0.305859E+11 0.367640E+10 0.148959E+12 0.00 0.286056E+11 0.563691E+09 0.148078E+11 0.140636E+11 0.00 0.320628E+11 0.00 0.00 0.00
May 0.324509E+11 0.311290E+10 0.156899E+12 0.00 0.301300E+11 0.339517E+09 0.973472E+10 0.411931E+11 0.00 0.105890E+11 0.00 0.00 0.00
June 0.322277E+11 0.270655E+10 0.154175E+12 0.00 0.297538E+11 0.255729E+09 0.923382E+10 0.701017E+11 0.00 0.535064E+09 0.00 0.00 0.00
July 0.304535E+11 0.292806E+10 0.151683E+12 0.00 0.299008E+11 0.239899E+09 0.102154E+11 0.859982E+11 0.00 0.00 0.00 0.00 0.00
August 0.338151E+11 0.346012E+10 0.160009E+12 0.00 0.308733E+11 0.236370E+09 0.889053E+10 0.753253E+11 0.00 0.00 0.00 0.00 0.00
September 0.306917E+11 0.416766E+10 0.148959E+12 0.00 0.290011E+11 0.283308E+09 0.718181E+10 0.347028E+11 0.00 0.517084E+09 0.00 0.00 0.00
October 0.319490E+11 0.537164E+10 0.153788E+12 0.00 0.289148E+11 0.498220E+09 0.111224E+11 0.142697E+11 0.00 0.123596E+11 0.00 0.00 0.00
November 0.316424E+11 0.619733E+10 0.150059E+12 0.00 0.273424E+11 0.718378E+09 0.207817E+11 0.605267E+10 0.00 0.379894E+11 0.00 0.00 0.00
December 0.315205E+11 0.697894E+10 0.151683E+12 0.00 0.277683E+11 0.119563E+10 0.464575E+11 0.383754E+09 0.00 0.600897E+11 0.00 0.00 0.00
                           
Annual Sum or Average 0.380820E+12 0.553437E+11 0.182940E+13   0.345448E+12 0.746785E+10 0.253027E+12 0.347065E+12   0.318659E+12      
Minimum of Months 0.290675E+11 0.270655E+10 0.139395E+12 0.00 0.258266E+11 0.236370E+09 0.718181E+10 0.185936E+09 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.341738E+11 0.697894E+10 0.160009E+12 0.00 0.308733E+11 0.127005E+10 0.560834E+11 0.859982E+11 0.00 0.634427E+11 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

INTERIOREQUIPMENT:GAS [J] EXTERIOREQUIPMENT:GAS [] HEATING:GAS [J] COOLING:GAS [] WATERSYSTEMS:GAS [J] COGENERATION:GAS [] HUMIDIFIER:GAS []
January 0.158619E+11 0.00 0.278519E+12 0.00 0.212390E+11 0.00 0.00
February 0.143713E+11 0.00 0.203507E+12 0.00 0.194018E+11 0.00 0.00
March 0.163897E+11 0.00 0.163567E+12 0.00 0.218071E+11 0.00 0.00
April 0.153698E+11 0.00 0.718858E+11 0.00 0.203409E+11 0.00 0.00
May 0.161258E+11 0.00 0.380277E+11 0.00 0.207261E+11 0.00 0.00
June 0.158049E+11 0.00 0.310787E+11 0.00 0.195198E+11 0.00 0.00
July 0.156907E+11 0.00 0.298021E+11 0.00 0.193613E+11 0.00 0.00
August 0.163897E+11 0.00 0.286887E+11 0.00 0.193576E+11 0.00 0.00
September 0.153698E+11 0.00 0.313629E+11 0.00 0.186008E+11 0.00 0.00
October 0.158619E+11 0.00 0.545845E+11 0.00 0.195819E+11 0.00 0.00
November 0.154482E+11 0.00 0.115365E+12 0.00 0.195673E+11 0.00 0.00
December 0.156907E+11 0.00 0.255869E+12 0.00 0.205574E+11 0.00 0.00
               
Annual Sum or Average 0.188374E+12   0.130226E+13   0.240061E+12    
Minimum of Months 0.143713E+11 0.00 0.286887E+11 0.00 0.186008E+11 0.00 0.00
Maximum of Months 0.163897E+11 0.00 0.278519E+12 0.00 0.218071E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum}[W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum}[W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum}[W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum}[W] HEATING:ELECTRICITY {TIMESTAMP}
January 26366.16 02-JAN-07:10 5724.00 01-JAN-06:10 110936.74 02-JAN-09:09 0.00 21640.07 27-JAN-15:09 585.39 01-JAN-08:09 128516.87 09-JAN-07:19
February 26366.16 01-FEB-07:10 5724.00 01-FEB-06:10 110936.74 01-FEB-09:09 0.00 23006.24 08-FEB-15:39 585.39 01-FEB-00:10 125842.41 25-FEB-07:10
March 26366.16 01-MAR-17:00 5724.00 01-MAR-06:10 110936.74 01-MAR-09:09 0.00 25992.06 31-MAR-15:20 585.39 04-MAR-23:30 73603.08 18-MAR-06:10
April 26123.98 03-APR-06:10 5724.00 01-APR-05:10 110936.74 03-APR-08:09 0.00 27402.49 21-APR-15:00 471.34 05-APR-05:10 43184.65 03-APR-06:10
May 25126.30 22-MAY-06:10 3649.90 01-MAY-19:30 110936.74 01-MAY-08:09 0.00 24324.26 18-MAY-16:10 364.06 01-MAY-05:10 32596.30 01-MAY-06:10
June 25738.74 30-JUN-06:10 3649.90 01-JUN-19:00 110936.74 01-JUN-08:09 0.00 26360.93 30-JUN-16:30 304.71 02-JUN-22:10 29998.70 10-JUN-06:10
July 25318.62 03-JUL-06:10 3649.90 01-JUL-20:19 110936.74 03-JUL-08:09 0.00 25518.22 21-JUL-15:00 234.62 10-JUL-06:10 27887.83 22-JUL-06:10
August 26158.20 31-AUG-06:10 5724.00 15-AUG-05:10 110936.74 01-AUG-08:09 0.00 25225.79 25-AUG-15:00 298.39 19-AUG-01:49 27323.48 19-AUG-06:10
September 26366.16 27-SEP-06:10 5724.00 01-SEP-05:10 110936.74 01-SEP-08:09 0.00 25603.64 01-SEP-15:30 311.96 06-SEP-03:20 30109.29 23-SEP-06:10
October 26366.16 02-OCT-06:10 5724.00 01-OCT-05:10 110936.74 02-OCT-08:09 0.00 24806.35 26-OCT-14:50 436.79 30-OCT-05:19 49659.93 30-OCT-06:10
November 26366.16 01-NOV-06:10 5724.00 01-NOV-05:10 110936.74 01-NOV-08:09 0.00 23612.24 17-NOV-15:30 585.39 25-NOV-06:19 83476.14 25-NOV-07:10
December 26366.16 01-DEC-07:10 5724.00 01-DEC-06:10 110936.74 01-DEC-09:09 0.00 19388.52 01-DEC-15:09 585.39 01-DEC-06:19 114338.27 02-DEC-07:10
                           
Annual Sum or Average                          
Minimum of Months 25126.30   3649.90   110936.74   0.00 19388.52   234.62   27323.48  
Maximum of Months 26366.16   5724.00   110936.74   0.00 27402.49   585.39   128516.87  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

COOLING:ELECTRICITY {Maximum}[W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY {Maximum}[W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 3638.71 18-JAN-15:00 0.00 31787.87 06-JAN-06:10 0.00 0.00 0.00
February 16039.01 28-FEB-15:39 0.00 30962.00 14-FEB-04:10 0.00 0.00 0.00
March 21913.11 31-MAR-15:00 0.00 30901.30 05-MAR-06:00 0.00 0.00 0.00
April 36704.95 13-APR-14:00 0.00 26232.29 05-APR-00:00 0.00 0.00 0.00
May 69831.81 25-MAY-15:00 0.00 22930.51 01-MAY-02:00 0.00 0.00 0.00
June 109128.28 29-JUN-15:00 0.00 7388.46 03-JUN-14:09 0.00 0.00 0.00
July 90437.06 15-JUL-13:00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 89836.21 08-AUG-14:00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 61163.84 01-SEP-14:09 0.00 7731.86 09-SEP-03:00 0.00 0.00 0.00
October 41688.60 19-OCT-14:00 0.00 23485.56 30-OCT-04:00 0.00 0.00 0.00
November 29703.37 01-NOV-14:00 0.00 28339.31 29-NOV-03:00 0.00 0.00 0.00
December 4677.97 05-DEC-17:00 0.00 31266.69 24-DEC-07:00 0.00 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 3638.71   0.00 0.00   0.00 0.00 0.00
Maximum of Months 109128.28   0.00 31787.87   0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 291538.95 09-JAN-07:19 26366.16 86760.32 5724.00 0.00 15244.37 585.39 128516.87 0.00 0.00
February 273247.97 14-FEB-07:10 26366.16 86760.32 5724.00 0.00 16112.64 585.39 110269.20 0.00 0.00
March 222485.53 16-MAR-06:10 26366.16 86760.32 5724.00 0.00 16618.64 585.39 60625.03 0.00 0.00
April 212563.90 13-APR-16:00 24491.48 110936.74 0.00 0.00 21486.19 83.98 5749.42 35188.66 0.00
May 232589.65 25-MAY-15:00 24480.26 110936.74 0.00 0.00 23637.43 80.98 3622.43 69831.81 0.00
June 273202.82 29-JUN-15:00 24326.07 110936.74 0.00 0.00 25686.34 74.99 3050.40 109128.28 0.00
July 248590.69 21-JUL-15:20 24326.07 110936.74 0.00 0.00 25293.85 75.07 3249.31 84709.65 0.00
August 252539.65 08-AUG-14:00 24326.07 110936.74 0.00 0.00 23526.55 82.27 3831.80 89836.21 0.00
September 225124.98 01-SEP-14:50 24459.72 110936.74 0.00 0.00 25446.84 76.21 3330.52 60874.96 0.00
October 204060.09 19-OCT-14:00 24931.04 110936.74 0.00 0.00 22532.85 81.31 3889.56 41688.60 0.00
November 206379.95 13-NOV-07:10 26366.16 86760.32 5724.00 0.00 16189.72 401.79 52145.72 194.47 0.00
December 268817.21 26-DEC-07:10 26366.16 86760.32 5724.00 0.00 15984.79 585.39 105286.66 0.00 0.00
                       
Annual Sum or Average                      
Minimum of Months 204060.09   24326.07 86760.32 0.00 0.00 15244.37 74.99 3050.40 0.00 0.00
Maximum of Months 291538.95   26366.16 110936.74 5724.00 0.00 25686.34 585.39 128516.87 109128.28 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

INTERIOREQUIPMENT:GAS {Maximum}[W] INTERIOREQUIPMENT:GAS {TIMESTAMP} EXTERIOREQUIPMENT:GAS [] HEATING:GAS {Maximum}[W] HEATING:GAS {TIMESTAMP} COOLING:GAS [] WATERSYSTEMS:GAS {Maximum}[W] WATERSYSTEMS:GAS {TIMESTAMP} COGENERATION:GAS []
January 9905.77 02-JAN-06:10 0.00 150194.51 07-JAN-16:10 0.00 23178.10 23-JAN-11:50 0.00
February 9905.77 01-FEB-06:10 0.00 149259.33 14-FEB-06:00 0.00 23294.11 14-FEB-11:00 0.00
March 9905.77 01-MAR-06:10 0.00 149291.77 18-MAR-05:00 0.00 23101.73 02-MAR-11:00 0.00
April 9905.77 03-APR-05:10 0.00 139359.11 05-APR-05:10 0.00 23003.34 04-APR-10:39 0.00
May 9905.77 01-MAY-05:10 0.00 83373.99 01-MAY-05:00 0.00 22827.08 01-MAY-12:39 0.00
June 9905.77 01-JUN-05:10 0.00 32377.38 17-JUN-05:19 0.00 22589.49 01-JUN-12:20 0.00
July 9905.77 03-JUL-05:10 0.00 27482.60 10-JUL-05:10 0.00 22361.14 03-JUL-12:50 0.00
August 9905.77 01-AUG-05:10 0.00 37864.68 19-AUG-05:19 0.00 22214.84 01-AUG-12:50 0.00
September 9905.77 01-SEP-05:10 0.00 40984.29 23-SEP-06:10 0.00 22245.93 29-SEP-12:20 0.00
October 9905.77 02-OCT-05:10 0.00 123134.85 30-OCT-05:19 0.00 22431.61 31-OCT-12:20 0.00
November 9905.77 01-NOV-05:10 0.00 150515.18 25-NOV-16:40 0.00 22654.37 30-NOV-11:00 0.00
December 9905.77 01-DEC-06:10 0.00 150343.84 23-DEC-16:10 0.00 23036.68 18-DEC-13:09 0.00
                   
Annual Sum or Average                  
Minimum of Months 9905.77   0.00 27482.60   0.00 22214.84   0.00
Maximum of Months 9905.77   0.00 150515.18   0.00 23294.11   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.83 19.83 6.83 19.83 8.33 22.90 8.33 22.90
February 1.50 19.48 1.50 19.48 0.00 0.00 0.00 0.00
March 0.17 20.53 0.17 20.53 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 19.36 0.50 19.36 0.00 0.00 0.00 0.00
December 1.00 19.90 1.00 19.90 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 10.00 19.77 10.00 19.77 8.33 22.90 8.33 22.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.83 20.53 6.83 20.53 8.33 22.90 8.33 22.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 25.17 20.16 0.00 0.00 0.00 0.00 0.00 0.00
February 6.33 20.38 0.00 0.00 0.00 0.00 0.00 0.00
March 2.50 20.42 0.00 0.00 0.00 0.00 0.00 0.00
April 1.83 20.42 0.00 0.00 0.00 0.00 0.00 0.00
May 1.50 20.43 0.00 0.00 0.00 0.00 0.00 0.00
June 0.17 20.51 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.17 20.47 0.00 0.00 0.00 0.00 0.00 0.00
October 1.33 20.40 0.00 0.00 0.00 0.00 0.00 0.00
November 1.33 20.47 0.00 0.00 0.00 0.00 0.00 0.00
December 10.00 20.17 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 50.33 20.24 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25.17 20.51 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 CAFE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 24.67 23.11 24.67 23.11
February 0.00 0.00 0.00 0.00 10.33 22.93 10.33 22.93
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 11.50 22.91 11.50 22.91
                 
Annual Sum or Average 0.00   0.00   46.50 23.02 46.50 23.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 24.67 23.11 24.67 23.11



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 CLEAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.17 20.47 0.17 20.47 0.00 0.00 0.00 0.00
May 0.33 20.44 0.33 20.44 0.00 0.00 0.00 0.00
June 0.67 20.41 0.67 20.41 0.00 0.00 0.00 0.00
July 0.83 20.39 0.83 20.39 0.00 0.00 0.00 0.00
August 0.67 20.40 0.67 20.40 0.00 0.00 0.00 0.00
September 0.83 20.45 0.83 20.45 0.00 0.00 0.00 0.00
October 0.33 20.48 0.33 20.48 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3.83 20.43 3.83 20.43 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.83 20.48 0.83 20.48 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 1.83 20.26 1.83 20.26 0.00 0.00 0.00 0.00
May 3.50 20.23 3.50 20.23 0.00 0.00 0.00 0.00
June 5.17 20.11 5.17 20.11 0.00 0.00 0.00 0.00
July 8.33 20.16 8.33 20.16 0.00 0.00 0.00 0.00
August 6.33 20.17 6.33 20.17 0.00 0.00 0.00 0.00
September 6.67 20.21 6.67 20.21 0.00 0.00 0.00 0.00
October 2.83 20.27 2.83 20.27 0.00 0.00 0.00 0.00
November 0.17 20.50 0.17 20.50 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 34.83 20.19 34.83 20.19 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8.33 20.50 8.33 20.50 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 2.00 20.42 2.00 20.42 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 1.33 20.46 1.33 20.46 0.00 0.00 0.00 0.00
October 0.17 20.52 0.17 20.52 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3.50 20.44 3.50 20.44 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.00 20.52 2.00 20.52 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 96.00 19.49 52.17 19.89 0.00 0.00 0.00 0.00
February 52.00 19.60 18.00 20.01 0.00 0.00 0.00 0.00
March 39.50 19.60 7.17 20.30 0.00 0.00 0.00 0.00
April 10.33 19.74 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 5.33 19.75 0.33 20.53 0.00 0.00 0.00 0.00
December 47.50 19.57 14.33 20.11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 250.67 19.56 92.00 19.98 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 96.00 19.75 52.17 20.53 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.67 19.65 0.00 0.00 0.00 0.00 0.00 0.00
February 0.67 19.40 0.00 0.00 0.00 0.00 0.00 0.00
March 0.33 19.43 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.17 19.50 0.00 0.00 0.33 22.76 0.00 0.00
                 
Annual Sum or Average 3.83 19.54 0.00   0.33 22.76 0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.67 19.65 0.00 0.00 0.33 22.76 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 IT HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 55.00 20.01 0.00 0.00 0.00 0.00 0.00 0.00
February 29.83 20.15 0.00 0.00 0.00 0.00 0.00 0.00
March 46.83 20.26 0.00 0.00 0.00 0.00 0.00 0.00
April 119.17 20.18 0.00 0.00 0.00 0.00 0.00 0.00
May 138.67 20.11 0.00 0.00 0.00 0.00 0.00 0.00
June 118.33 20.15 0.00 0.00 0.00 0.00 0.00 0.00
July 108.33 20.17 0.00 0.00 0.00 0.00 0.00 0.00
August 96.83 20.21 0.00 0.00 0.00 0.00 0.00 0.00
September 122.67 20.13 0.00 0.00 0.00 0.00 0.00 0.00
October 133.67 20.13 0.00 0.00 0.00 0.00 0.00 0.00
November 74.50 20.24 0.00 0.00 0.00 0.00 0.00 0.00
December 24.67 20.24 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1068.50 20.16 0.00   0.00   0.00  
Minimum of Months 24.67 20.01 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 138.67 20.26 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 67.50 19.78 60.67 20.02 0.00 0.00 0.00 0.00
February 26.17 20.15 26.17 20.15 0.00 0.00 0.00 0.00
March 30.33 20.24 30.33 20.24 0.00 0.00 0.00 0.00
April 60.67 20.06 60.67 20.06 0.00 0.00 0.00 0.00
May 67.33 20.07 67.33 20.07 0.00 0.00 0.00 0.00
June 45.50 20.12 45.50 20.12 0.00 0.00 0.00 0.00
July 29.17 20.22 29.17 20.22 0.00 0.00 0.00 0.00
August 27.00 20.27 27.00 20.27 0.00 0.00 0.00 0.00
September 47.00 20.09 47.00 20.09 0.00 0.00 0.00 0.00
October 66.67 20.09 66.67 20.09 0.00 0.00 0.00 0.00
November 39.83 20.17 39.83 20.17 0.00 0.00 0.00 0.00
December 27.00 20.18 27.00 20.18 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 534.17 20.09 527.33 20.12 0.00   0.00  
Minimum of Months 26.17 19.78 26.17 20.02 0.00 0.00 0.00 0.00
Maximum of Months 67.50 20.27 67.33 20.27 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 LOBBY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 20.37 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.50 20.37 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 20.37 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 31.83 20.10 0.00 0.00 0.00 0.00 0.00 0.00
February 15.17 20.17 0.00 0.00 0.00 0.00 0.00 0.00
March 1.33 19.90 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.67 20.10 0.00 0.00 0.00 0.00 0.00 0.00
December 13.83 20.14 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 63.83 20.12 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31.83 20.17 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.83 20.23 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 5.67 20.37 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 3.00 20.44 0.00 0.00 0.00 0.00 0.00 0.00
October 3.50 20.44 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 20.54 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 19.17 20.34 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.83 20.54 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 MED GAS

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 150.67 19.06 0.00 0.00 0.00 0.00 0.00 0.00
February 96.33 19.34 0.00 0.00 0.00 0.00 0.00 0.00
March 75.33 19.66 0.00 0.00 0.00 0.00 0.00 0.00
April 11.00 20.34 0.00 0.00 0.00 0.00 0.00 0.00
May 0.17 20.46 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 2.67 20.13 0.00 0.00 0.00 0.00 0.00 0.00
December 78.00 19.51 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 414.17 19.36 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 150.67 20.46 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 52.17 22.88 52.17 22.88
February 0.00 0.00 0.00 0.00 39.00 22.90 39.00 22.90
March 0.00 0.00 0.00 0.00 4.33 22.81 4.33 22.81
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 1.50 22.82 1.50 22.82
December 0.00 0.00 0.00 0.00 45.50 22.92 45.50 22.92
                 
Annual Sum or Average 0.00   0.00   142.50 22.90 142.50 22.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 52.17 22.92 52.17 22.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 11.33 20.19 0.00 0.00 0.00 0.00 0.00 0.00
February 3.00 20.40 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.50 20.27 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 15.83 20.23 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11.33 20.40 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 169.67 23.36 169.67 23.36
February 0.00 0.00 0.00 0.00 105.83 23.41 105.83 23.41
March 0.00 0.00 0.00 0.00 50.17 23.31 50.17 23.31
April 0.00 0.00 0.00 0.00 1.67 23.27 1.67 23.27
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 1.17 23.10 1.17 23.10
November 0.00 0.00 0.00 0.00 6.67 23.24 6.67 23.24
December 0.00 0.00 0.00 0.00 129.83 23.34 129.83 23.34
                 
Annual Sum or Average 0.00   0.00   465.00 23.36 465.00 23.36
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 169.67 23.41 169.67 23.41



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.83 20.31 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 20.31 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3.33 20.31 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.83 20.31 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 24.33 20.14 0.00 0.00 0.00 0.00 0.00 0.00
February 6.17 20.23 0.00 0.00 0.00 0.00 0.00 0.00
March 9.50 20.34 0.00 0.00 0.00 0.00 0.00 0.00
April 40.83 20.25 0.00 0.00 0.00 0.00 0.00 0.00
May 63.50 20.17 0.00 0.00 0.00 0.00 0.00 0.00
June 52.33 20.26 0.00 0.00 0.00 0.00 0.00 0.00
July 45.83 20.25 0.00 0.00 0.00 0.00 0.00 0.00
August 31.17 20.34 0.00 0.00 0.00 0.00 0.00 0.00
September 32.50 20.25 0.00 0.00 0.00 0.00 0.00 0.00
October 50.33 20.27 0.00 0.00 0.00 0.00 0.00 0.00
November 29.17 20.31 0.00 0.00 0.00 0.00 0.00 0.00
December 4.67 19.99 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 390.33 20.24 0.00   0.00   0.00  
Minimum of Months 4.67 19.99 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 63.50 20.34 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.83 20.31 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 2.50 20.46 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.67 20.53 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 4.00 20.44 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.50 20.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 49.17 20.11 0.00 0.00 0.00 0.00 0.00 0.00
February 30.17 20.19 0.00 0.00 0.00 0.00 0.00 0.00
March 52.83 20.25 0.00 0.00 0.00 0.00 0.00 0.00
April 153.50 20.11 0.00 0.00 0.00 0.00 0.00 0.00
May 226.83 19.95 0.00 0.00 0.00 0.00 0.00 0.00
June 240.33 19.93 0.00 0.00 0.00 0.00 0.00 0.00
July 235.33 19.88 0.00 0.00 0.00 0.00 0.00 0.00
August 241.50 19.95 0.00 0.00 0.00 0.00 0.00 0.00
September 215.50 19.95 0.00 0.00 0.00 0.00 0.00 0.00
October 197.00 20.02 0.00 0.00 0.00 0.00 0.00 0.00
November 116.50 20.17 0.00 0.00 0.00 0.00 0.00 0.00
December 25.33 20.28 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1784.00 19.99 0.00   0.00   0.00  
Minimum of Months 25.33 19.88 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 241.50 20.28 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 20.41 0.33 20.41 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 20.41 0.33 20.41 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 20.41 0.33 20.41 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.83 17.13 0.83 17.13 130.17 19.59 130.17 19.59
February 1.50 17.18 1.50 17.18 77.50 19.62 77.50 19.62
March 1.67 16.98 1.67 16.98 44.83 19.46 44.83 19.46
April 5.67 16.69 5.67 16.69 5.33 19.43 5.33 19.43
May 3.83 16.76 3.83 16.76 1.00 19.39 1.00 19.39
June 3.67 16.69 3.67 16.69 0.00 0.00 0.00 0.00
July 2.17 16.90 2.17 16.90 0.00 0.00 0.00 0.00
August 1.33 16.73 1.33 16.73 0.00 0.00 0.00 0.00
September 2.33 16.74 2.33 16.74 0.00 0.00 0.00 0.00
October 3.00 16.76 3.00 16.76 1.33 19.38 1.33 19.38
November 0.67 17.06 0.67 17.06 12.00 19.45 12.00 19.45
December 1.00 17.05 1.00 17.05 87.67 19.57 87.67 19.57
                 
Annual Sum or Average 27.67 16.81 27.67 16.81 359.83 19.57 359.83 19.57
Minimum of Months 0.67 16.69 0.67 16.69 0.00 0.00 0.00 0.00
Maximum of Months 5.67 17.18 5.67 17.18 130.17 19.62 130.17 19.62



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 9.83 16.19 6.00 15.89 152.50 19.64 152.50 19.64
February 3.17 16.64 3.17 16.64 96.17 19.71 96.17 19.71
March 4.67 16.72 4.67 16.72 60.17 19.66 60.17 19.66
April 26.83 15.96 19.83 16.15 6.83 19.66 6.83 19.66
May 138.33 15.81 86.33 16.05 1.00 19.58 1.00 19.58
June 170.00 15.94 110.00 16.14 0.00 0.00 0.00 0.00
July 151.83 15.99 91.83 16.22 0.00 0.00 0.00 0.00
August 81.17 16.16 51.17 16.42 0.00 0.00 0.00 0.00
September 161.17 15.89 96.00 16.15 0.00 0.00 0.00 0.00
October 77.67 15.94 43.67 16.23 2.17 19.40 2.17 19.40
November 3.17 16.71 3.17 16.71 13.17 19.64 13.17 19.64
December 1.00 16.35 1.00 16.35 115.33 19.63 115.33 19.63
                 
Annual Sum or Average 828.83 15.95 516.83 16.19 447.33 19.65 447.33 19.65
Minimum of Months 1.00 15.81 1.00 15.89 0.00 0.00 0.00 0.00
Maximum of Months 170.00 16.72 110.00 16.72 152.50 19.71 152.50 19.71



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 10.50 16.69 5.83 16.44 178.67 19.83 177.67 19.84
February 5.83 17.23 4.33 17.26 125.50 19.79 124.33 19.80
March 8.83 17.02 7.17 17.08 65.50 19.79 65.17 19.79
April 31.33 16.56 21.67 16.72 6.33 19.69 6.33 19.69
May 108.33 16.28 78.00 16.47 0.83 19.38 0.83 19.38
June 149.50 16.18 103.33 16.32 0.00 0.00 0.00 0.00
July 169.83 16.08 104.83 16.24 0.00 0.00 0.00 0.00
August 106.00 16.09 65.33 16.26 0.00 0.00 0.00 0.00
September 165.67 16.10 104.33 16.27 0.00 0.00 0.00 0.00
October 79.83 16.34 56.83 16.49 2.00 19.49 2.00 19.49
November 18.33 17.15 9.50 17.00 18.33 19.57 18.33 19.57
December 7.00 16.87 2.83 17.16 145.83 19.77 145.67 19.77
                 
Annual Sum or Average 861.00 16.22 564.00 16.38 543.00 19.79 540.33 19.79
Minimum of Months 5.83 16.08 2.83 16.24 0.00 0.00 0.00 0.00
Maximum of Months 169.83 17.23 104.83 17.26 178.67 19.83 177.67 19.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 PACU

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 3.50 20.16 3.50 20.16 0.00 0.00 0.00 0.00
May 5.33 19.99 5.33 19.99 0.00 0.00 0.00 0.00
June 8.00 19.93 8.00 19.93 0.00 0.00 0.00 0.00
July 10.83 19.94 10.83 19.94 0.00 0.00 0.00 0.00
August 8.00 19.93 8.00 19.93 0.00 0.00 0.00 0.00
September 8.50 19.98 8.50 19.98 0.00 0.00 0.00 0.00
October 4.50 20.02 4.50 20.02 0.00 0.00 0.00 0.00
November 0.17 20.38 0.17 20.38 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 48.83 19.97 48.83 19.97 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10.83 20.38 10.83 20.38 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 130.33 20.05 0.00 0.00 0.00 0.00 0.00 0.00
February 35.67 20.34 0.00 0.00 0.00 0.00 0.00 0.00
March 23.67 20.42 0.00 0.00 0.00 0.00 0.00 0.00
April 37.33 20.38 0.00 0.00 0.00 0.00 0.00 0.00
May 34.50 20.34 0.00 0.00 0.00 0.00 0.00 0.00
June 11.33 20.42 0.00 0.00 0.00 0.00 0.00 0.00
July 4.00 20.47 0.00 0.00 0.00 0.00 0.00 0.00
August 1.00 20.52 0.00 0.00 0.00 0.00 0.00 0.00
September 12.00 20.40 0.00 0.00 0.00 0.00 0.00 0.00
October 34.33 20.35 0.00 0.00 0.00 0.00 0.00 0.00
November 42.33 20.40 0.00 0.00 0.00 0.00 0.00 0.00
December 67.67 20.29 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 434.17 20.26 0.00   0.00   0.00  
Minimum of Months 1.00 20.05 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 130.33 20.52 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 137.83 19.77 137.83 19.77 0.00 0.00 0.00 0.00
February 87.50 20.14 87.50 20.14 0.00 0.00 0.00 0.00
March 81.17 20.21 81.17 20.21 0.00 0.00 0.00 0.00
April 90.50 20.04 90.50 20.04 0.00 0.00 0.00 0.00
May 56.67 20.00 56.67 20.00 0.00 0.00 0.00 0.00
June 45.67 19.95 45.67 19.95 0.00 0.00 0.00 0.00
July 32.50 19.96 32.50 19.96 0.00 0.00 0.00 0.00
August 28.17 20.01 28.17 20.01 0.00 0.00 0.00 0.00
September 42.00 20.00 42.00 20.00 0.00 0.00 0.00 0.00
October 52.67 20.05 52.67 20.05 0.00 0.00 0.00 0.00
November 53.00 20.21 53.00 20.21 0.00 0.00 0.00 0.00
December 103.00 20.17 103.00 20.17 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 810.67 20.04 810.67 20.04 0.00   0.00  
Minimum of Months 28.17 19.77 28.17 19.77 0.00 0.00 0.00 0.00
Maximum of Months 137.83 20.21 137.83 20.21 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.17 20.13 1.17 20.13 0.00 0.00 0.00 0.00
February 0.50 20.32 0.50 20.32 0.00 0.00 0.00 0.00
March 0.33 20.38 0.33 20.38 0.00 0.00 0.00 0.00
April 8.83 20.17 8.83 20.17 0.00 0.00 0.00 0.00
May 16.00 20.11 16.00 20.11 0.00 0.00 0.00 0.00
June 18.00 20.06 18.00 20.06 0.00 0.00 0.00 0.00
July 22.00 20.01 22.00 20.01 0.00 0.00 0.00 0.00
August 19.33 20.07 19.33 20.07 0.00 0.00 0.00 0.00
September 20.50 20.07 20.50 20.07 0.00 0.00 0.00 0.00
October 13.00 20.11 13.00 20.11 0.00 0.00 0.00 0.00
November 1.67 20.37 1.67 20.37 0.00 0.00 0.00 0.00
December 0.17 20.38 0.17 20.38 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 121.50 20.08 121.50 20.08 0.00   0.00  
Minimum of Months 0.17 20.01 0.17 20.01 0.00 0.00 0.00 0.00
Maximum of Months 22.00 20.38 22.00 20.38 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 216.17 18.50 0.00 0.00 0.00 0.00 0.00 0.00
February 133.17 18.98 0.00 0.00 0.00 0.00 0.00 0.00
March 110.17 19.69 0.00 0.00 0.00 0.00 0.00 0.00
April 11.17 20.28 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 5.50 20.34 0.00 0.00 0.00 0.00 0.00 0.00
December 170.67 19.13 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 646.83 19.01 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 216.17 20.34 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 59.67 19.46 59.67 19.46 0.00 0.00 0.00 0.00
February 24.67 19.69 24.67 19.69 0.00 0.00 0.00 0.00
March 21.67 19.96 21.67 19.96 0.00 0.00 0.00 0.00
April 40.67 19.64 40.67 19.64 0.00 0.00 0.00 0.00
May 35.50 19.68 35.50 19.68 0.00 0.00 0.00 0.00
June 35.00 19.64 35.00 19.64 0.00 0.00 0.00 0.00
July 27.67 19.62 27.67 19.62 0.00 0.00 0.00 0.00
August 27.17 19.75 27.17 19.75 0.00 0.00 0.00 0.00
September 34.17 19.73 34.17 19.73 0.00 0.00 0.00 0.00
October 29.83 19.75 29.83 19.75 0.00 0.00 0.00 0.00
November 15.83 20.04 15.83 20.04 0.00 0.00 0.00 0.00
December 25.17 19.46 20.50 19.87 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 377.00 19.66 372.33 19.69 0.00   0.00  
Minimum of Months 15.83 19.46 15.83 19.46 0.00 0.00 0.00 0.00
Maximum of Months 59.67 20.04 59.67 20.04 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.50 22.78 0.50 22.78
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.50 22.78 0.50 22.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.50 22.78 0.50 22.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 23.17 20.23 0.00 0.00 0.00 0.00 0.00 0.00
February 4.00 20.43 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 4.67 20.40 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 2.67 20.46 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.50 20.27 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 36.00 20.29 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23.17 20.46 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.17 19.84 6.17 19.84 0.00 0.00 0.00 0.00
February 1.17 19.49 1.17 19.49 0.00 0.00 0.00 0.00
March 0.50 19.79 0.50 19.79 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.83 19.80 0.83 19.80 0.00 0.00 0.00 0.00
December 1.00 19.89 1.00 19.89 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 9.67 19.80 9.67 19.80 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.17 19.89 6.17 19.89 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.00 20.41 1.00 20.41 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 20.46 0.33 20.46 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.33 20.42 1.33 20.42 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 20.46 1.00 20.46 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 SCRUB

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.50 20.35 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.67 20.33 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3.17 20.34 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.50 20.35 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 SOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 1.50 20.37 1.50 20.37 0.00 0.00 0.00 0.00
May 3.33 20.22 3.33 20.22 0.00 0.00 0.00 0.00
June 5.00 20.15 5.00 20.15 0.00 0.00 0.00 0.00
July 9.00 20.15 9.00 20.15 0.00 0.00 0.00 0.00
August 6.67 20.16 6.67 20.16 0.00 0.00 0.00 0.00
September 6.83 20.21 6.83 20.21 0.00 0.00 0.00 0.00
October 2.83 20.29 2.83 20.29 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 35.17 20.19 35.17 20.19 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9.00 20.37 9.00 20.37 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 161.83 18.83 130.17 19.25 0.00 0.00 0.00 0.00
February 101.33 19.31 94.33 19.47 0.00 0.00 0.00 0.00
March 118.83 19.22 108.33 19.42 0.00 0.00 0.00 0.00
April 199.33 18.74 167.17 19.05 0.00 0.00 0.00 0.00
May 241.50 18.53 210.00 18.75 0.00 0.00 0.00 0.00
June 198.17 18.68 172.83 18.87 0.00 0.00 0.00 0.00
July 153.00 18.99 148.33 19.04 0.00 0.00 0.00 0.00
August 132.33 19.11 122.00 19.24 0.00 0.00 0.00 0.00
September 200.50 18.57 179.17 18.73 0.00 0.00 0.00 0.00
October 210.50 18.65 179.67 18.91 0.00 0.00 0.00 0.00
November 127.00 19.33 124.67 19.36 0.00 0.00 0.00 0.00
December 89.33 19.25 74.83 19.67 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1933.67 18.86 1711.50 19.07 0.00   0.00  
Minimum of Months 89.33 18.53 74.83 18.73 0.00 0.00 0.00 0.00
Maximum of Months 241.50 19.33 210.00 19.67 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.17 20.51 0.17 20.51 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 6.17 20.20 6.17 20.20 0.00 0.00 0.00 0.00
May 9.50 20.06 9.50 20.06 0.00 0.00 0.00 0.00
June 11.17 19.95 11.17 19.95 0.00 0.00 0.00 0.00
July 13.83 19.97 13.83 19.97 0.00 0.00 0.00 0.00
August 10.50 20.01 10.50 20.01 0.00 0.00 0.00 0.00
September 12.00 20.00 12.00 20.00 0.00 0.00 0.00 0.00
October 6.83 20.06 6.83 20.06 0.00 0.00 0.00 0.00
November 0.33 20.43 0.33 20.43 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 70.50 20.02 70.50 20.02 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13.83 20.51 13.83 20.51 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.33 19.82 5.33 19.82 0.00 0.00 0.00 0.00
February 1.17 19.51 1.17 19.51 0.00 0.00 0.00 0.00
March 0.50 19.36 0.50 19.36 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 19.33 0.50 19.33 0.00 0.00 0.00 0.00
December 0.83 19.77 0.83 19.77 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 8.33 19.71 8.33 19.71 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.33 19.82 5.33 19.82 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.83 20.21 0.00 0.00 0.00 0.00 0.00 0.00
February 0.17 20.44 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.17 20.41 0.00 0.00 0.00 0.00 0.00 0.00
May 0.67 20.39 0.00 0.00 0.00 0.00 0.00 0.00
June 0.17 20.43 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.17 20.46 0.00 0.00 0.00 0.00 0.00 0.00
October 0.17 20.43 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.83 20.25 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 8.17 20.26 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.83 20.46 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.83 20.25 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 6.00 20.39 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 2.83 20.47 0.00 0.00 0.00 0.00 0.00 0.00
October 2.17 20.50 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 17.83 20.36 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.83 20.50 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 136.00 19.37 0.00 0.00 0.00 0.00 0.00 0.00
February 71.50 19.67 0.00 0.00 0.00 0.00 0.00 0.00
March 43.00 19.95 0.00 0.00 0.00 0.00 0.00 0.00
April 3.33 20.41 0.00 0.00 0.00 0.00 0.00 0.00
May 0.17 20.40 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.17 20.48 0.00 0.00 0.00 0.00 0.00 0.00
November 3.17 20.24 0.00 0.00 0.00 0.00 0.00 0.00
December 78.17 19.77 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 335.50 19.62 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 136.00 20.48 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.83 20.04 0.00 0.00 0.00 0.00 0.00 0.00
February 1.00 20.38 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 2.00 20.22 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 9.83 20.11 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.83 20.38 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 92.33 19.84 0.00 0.00 0.00 0.00 0.00 0.00
February 35.67 19.95 0.00 0.00 0.00 0.00 0.00 0.00
March 11.00 20.23 0.00 0.00 0.00 0.00 0.00 0.00
April 0.33 20.42 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.83 20.39 0.00 0.00 0.00 0.00 0.00 0.00
December 37.50 19.99 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 178.67 19.93 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 92.33 20.42 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.50 20.24 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.17 20.47 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.33 20.35 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 5.00 20.28 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.50 20.47 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 32.17 20.09 0.00 0.00 0.00 0.00 0.00 0.00
February 9.33 20.26 0.00 0.00 0.00 0.00 0.00 0.00
March 3.00 20.41 0.00 0.00 0.00 0.00 0.00 0.00
April 0.17 20.43 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 20.45 0.00 0.00 0.00 0.00 0.00 0.00
December 14.50 20.15 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 59.33 20.15 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 32.17 20.45 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 561.17 0.31 0.00 0.00 0.00 0.00 0.00 0.00
February 470.00 2.91 0.00 0.00 0.00 0.00 0.00 0.00
March 540.17 6.22 0.00 0.00 0.00 0.00 0.00 0.00
April 325.17 9.48 0.00 0.00 0.00 0.00 0.00 0.00
May 198.00 13.45 0.00 0.00 47.17 25.36 0.00 0.00
June 127.00 16.85 0.00 0.00 75.17 26.40 0.00 0.00
July 91.17 18.25 0.00 0.00 102.17 25.40 0.00 0.00
August 157.50 17.05 0.00 0.00 66.00 25.20 0.00 0.00
September 234.67 13.73 0.00 0.00 10.00 24.06 0.00 0.00
October 289.50 8.86 0.00 0.00 0.00 0.00 0.00 0.00
November 389.83 7.31 0.00 0.00 0.00 0.00 0.00 0.00
December 521.50 2.05 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3905.67 6.87 0.00   300.50 25.56 0.00  
Minimum of Months 91.17 0.31 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 561.17 18.25 0.00 0.00 102.17 26.40 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.83 22.82 0.83 22.82
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.83 22.82 0.83 22.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.83 22.82 0.83 22.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 20.27 0.33 20.27 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 20.39 0.17 20.39 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.50 20.31 0.50 20.31 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 20.39 0.33 20.39 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 3.67 23.01 3.67 23.01
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 1.00 22.78 1.00 22.78
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.67 22.96 4.67 22.96
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.67 23.01 3.67 23.01



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.00 20.02 0.00 0.00 0.00 0.00 0.00 0.00
February 0.17 20.49 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.17 20.33 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 4.33 20.12 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.00 20.49 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 11.83 19.74 0.00 0.00 0.00 0.00 0.00 0.00
February 3.50 20.22 0.00 0.00 0.00 0.00 0.00 0.00
March 0.17 20.40 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 20.47 0.00 0.00 0.00 0.00 0.00 0.00
December 5.17 19.92 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 20.83 19.88 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11.83 20.47 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 9.33 19.74 0.00 0.00 0.00 0.00 0.00 0.00
February 1.83 20.36 0.00 0.00 0.00 0.00 0.00 0.00
March 0.17 20.44 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 20.49 0.00 0.00 0.00 0.00 0.00 0.00
December 5.17 19.96 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 16.67 19.89 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9.33 20.49 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 27.67 19.72 0.00 0.00 0.00 0.00 0.00 0.00
February 7.17 20.01 0.00 0.00 0.00 0.00 0.00 0.00
March 0.83 20.40 0.00 0.00 0.00 0.00 0.00 0.00
April 0.33 20.49 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.50 20.42 0.00 0.00 0.00 0.00 0.00 0.00
November 1.50 20.41 0.00 0.00 0.00 0.00 0.00 0.00
December 11.67 19.70 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 49.67 19.80 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 27.67 20.49 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 23.17 19.68 0.00 0.00 0.00 0.00 0.00 0.00
February 6.33 19.99 0.00 0.00 0.00 0.00 0.00 0.00
March 0.50 20.37 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.17 20.45 0.00 0.00 0.00 0.00 0.00 0.00
November 0.67 20.40 0.00 0.00 0.00 0.00 0.00 0.00
December 9.83 19.70 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 40.67 19.76 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23.17 20.45 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 26.33 19.71 0.00 0.00 0.00 0.00 0.00 0.00
February 6.50 20.02 0.00 0.00 0.00 0.00 0.00 0.00
March 0.50 20.40 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.83 20.47 0.00 0.00 0.00 0.00 0.00 0.00
December 9.67 19.79 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 43.83 19.80 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26.33 20.47 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 20.41 0.33 20.41 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 20.41 0.33 20.41 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 20.41 0.33 20.41 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 8.67 19.76 0.00 0.00 0.00 0.00 0.00 0.00
February 1.00 20.37 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 3.00 20.12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 12.67 19.90 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8.67 20.37 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.17 19.85 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 20.16 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3.67 19.89 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.17 20.16 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.33 20.05 0.00 0.00 0.00 0.00 0.00 0.00
February 0.50 20.50 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 2.67 20.16 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 7.50 20.12 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.33 20.50 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.33 20.30 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.00 20.41 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3.33 20.34 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.33 20.41 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 20.34 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.67 20.40 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2.83 20.36 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.17 20.40 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.17 20.38 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.17 20.38 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.17 20.38 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 20.40 0.33 20.40 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 20.40 0.33 20.40 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 20.40 0.33 20.40 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.33 19.87 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.83 20.26 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 4.17 19.95 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.33 20.26 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 2 X-RAY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 133.67 23.09 133.67 23.09
February 0.00 0.00 0.00 0.00 164.83 23.17 164.83 23.17
March 0.00 0.00 0.00 0.00 235.17 23.22 235.17 23.22
April 0.00 0.00 0.00 0.00 166.50 23.19 166.50 23.19
May 0.00 0.00 0.00 0.00 81.50 23.02 81.50 23.02
June 0.00 0.00 0.00 0.00 22.00 22.91 22.00 22.91
July 0.00 0.00 0.00 0.00 0.83 22.81 0.83 22.81
August 0.00 0.00 0.00 0.00 14.50 22.97 14.50 22.97
September 0.00 0.00 0.00 0.00 105.83 23.12 105.83 23.12
October 0.00 0.00 0.00 0.00 195.17 23.15 195.17 23.15
November 0.00 0.00 0.00 0.00 192.50 23.17 192.50 23.17
December 0.00 0.00 0.00 0.00 156.83 23.14 156.83 23.14
                 
Annual Sum or Average 0.00   0.00   1469.33 23.15 1469.33 23.15
Minimum of Months 0.00 0.00 0.00 0.00 0.83 22.81 0.83 22.81
Maximum of Months 0.00 0.00 0.00 0.00 235.17 23.22 235.17 23.22



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 23.50 20.19 0.00 0.00 0.00 0.00 0.00 0.00
February 9.50 20.35 0.00 0.00 0.00 0.00 0.00 0.00
March 2.17 20.43 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 20.50 0.00 0.00 0.00 0.00 0.00 0.00
December 10.50 20.31 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 46.17 20.26 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23.50 20.50 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 LOCKER

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.17 20.18 0.17 20.18 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 20.18 0.17 20.18 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 20.18 0.17 20.18 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 331.17 26.36 0.00 0.00
February 0.00 0.00 0.00 0.00 311.33 26.59 0.00 0.00
March 0.00 0.00 0.00 0.00 328.83 26.81 0.00 0.00
April 0.00 0.00 0.00 0.00 382.33 26.90 0.00 0.00
May 0.00 0.00 0.00 0.00 381.83 27.08 0.00 0.00
June 0.00 0.00 0.00 0.00 350.83 26.98 0.00 0.00
July 0.00 0.00 0.00 0.00 402.17 26.83 0.00 0.00
August 0.00 0.00 0.00 0.00 358.17 26.93 0.00 0.00
September 0.00 0.00 0.00 0.00 394.33 26.98 0.00 0.00
October 0.00 0.00 0.00 0.00 391.50 27.17 0.00 0.00
November 0.00 0.00 0.00 0.00 359.33 26.85 0.00 0.00
December 0.00 0.00 0.00 0.00 357.00 26.40 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4348.83 26.83 0.00  
Minimum of Months 0.00 0.00 0.00 0.00 311.33 26.36 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 402.17 27.17 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.17 20.48 0.17 20.48 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 20.48 0.17 20.48 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 20.48 0.17 20.48 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.00 20.38 0.00 0.00 0.00 0.00 0.00 0.00
February 0.33 20.52 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 4.33 20.39 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.00 20.52 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 4.67 22.95 4.67 22.95
March 0.00 0.00 0.00 0.00 5.83 22.91 5.83 22.91
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.83 22.77 0.83 22.77
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   11.33 22.92 11.33 22.92
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.83 22.95 5.83 22.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.00 20.40 0.00 0.00 0.00 0.00 0.00 0.00
February 0.17 20.30 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 20.51 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2.33 20.40 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.00 20.51 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 20.49 0.00 0.00 0.00 0.00 0.00 0.00
February 0.17 20.53 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 20.48 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.67 20.50 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 20.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FLOOR 3 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.83 20.09 0.83 20.09 0.00 0.00 0.00 0.00
February 0.33 20.36 0.33 20.36 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 20.50 0.17 20.50 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.33 20.21 1.33 20.21 0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.83 20.50 0.83 20.50 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: NE STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 39.83 19.82 0.00 0.00 0.00 0.00 0.00 0.00
February 18.00 20.08 0.00 0.00 0.00 0.00 0.00 0.00
March 6.00 20.30 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 20.46 0.00 0.00 0.00 0.00 0.00 0.00
December 14.83 20.17 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 79.17 19.99 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 39.83 20.46 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: NW ELEVATOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 21.00 20.18 0.00 0.00 0.00 0.00 0.00 0.00
February 9.17 20.33 0.00 0.00 0.00 0.00 0.00 0.00
March 3.83 20.37 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 20.52 0.00 0.00 0.00 0.00 0.00 0.00
December 6.67 20.34 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 40.83 20.26 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21.00 20.52 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: NW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 60.33 19.84 0.00 0.00 0.00 0.00 0.00 0.00
February 25.17 20.03 0.00 0.00 0.00 0.00 0.00 0.00
March 9.50 20.26 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 20.44 0.00 0.00 0.00 0.00 0.00 0.00
December 20.50 20.09 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 116.00 19.96 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 60.33 20.44 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: SW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 13.17 20.17 0.00 0.00 0.00 0.00 0.00 0.00
February 6.33 20.36 0.00 0.00 0.00 0.00 0.00 0.00
March 2.17 20.40 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 20.51 0.00 0.00 0.00 0.00 0.00 0.00
December 4.50 20.34 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 26.33 20.26 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13.17 20.51 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.98 406.00 19.21 406.00 19.21
February 597.00 20.14 320.83 19.33 320.83 19.33
March 684.00 20.06 362.00 19.22 362.00 19.22
April 645.00 19.74 380.50 18.87 380.50 18.87
May 669.00 19.62 377.50 18.60 377.50 18.60
June 660.00 19.64 342.33 18.50 342.33 18.50
July 654.00 19.62 323.17 18.46 323.17 18.46
August 684.00 19.71 307.33 18.47 307.33 18.47
September 645.00 19.70 334.17 18.58 334.17 18.58
October 654.00 19.80 346.67 18.74 346.67 18.74
November 630.00 19.99 328.00 19.03 328.00 19.03
December 654.00 20.07 378.33 19.33 378.33 19.33
             
Annual Sum or Average 7830.00 19.84 4206.83 18.87 4206.83 18.87
Minimum of Months 597.00 19.62 307.33 18.46 307.33 18.46
Maximum of Months 684.00 20.14 406.00 19.33 406.00 19.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 BIO HAZ

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 CAFE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 628.33 21.68 115.17 20.08 107.50 19.74
February 563.83 21.97 54.67 21.26 40.83 20.03
March 642.67 21.99 57.67 21.99 34.17 20.01
April 603.17 21.84 64.50 21.61 41.00 19.79
May 634.50 21.98 68.50 22.47 47.50 21.52
June 626.33 22.10 62.67 23.82 41.17 23.48
July 607.67 22.22 59.17 24.38 37.67 24.44
August 626.00 22.36 74.17 24.38 42.50 24.53
September 579.17 22.17 46.50 24.54 14.67 24.44
October 590.17 21.99 48.00 23.12 16.50 20.19
November 594.33 21.92 60.67 21.57 41.67 20.08
December 633.67 21.84 79.00 20.29 72.17 19.85
             
Annual Sum or Average 7329.83 22.00 790.67 22.24 537.33 21.12
Minimum of Months 563.83 21.68 46.50 20.08 14.67 19.74
Maximum of Months 642.67 22.36 115.17 24.54 107.50 24.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 CLEAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 21.21 64.83 19.26 64.83 19.26
February 597.00 21.37 21.00 19.14 21.00 19.14
March 684.00 21.11 48.17 19.25 48.17 19.25
April 645.00 20.38 172.00 19.14 172.00 19.14
May 669.00 20.01 248.50 18.91 248.50 18.91
June 660.00 19.96 213.83 18.78 213.83 18.78
July 654.00 19.87 205.67 18.63 205.67 18.63
August 684.00 19.97 189.83 18.71 189.83 18.71
September 645.00 19.95 233.17 18.82 233.17 18.82
October 654.00 20.19 225.50 19.08 225.50 19.08
November 630.00 20.73 91.83 19.26 91.83 19.26
December 654.00 21.36 38.17 19.55 38.17 19.55
             
Annual Sum or Average 7830.00 20.50 1752.50 18.93 1752.50 18.93
Minimum of Months 597.00 19.87 21.00 18.63 21.00 18.63
Maximum of Months 684.00 21.37 248.50 19.55 248.50 19.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 20.84 126.33 19.29 126.33 19.29
February 597.00 21.00 82.83 19.53 82.83 19.53
March 684.00 20.76 131.83 19.26 131.83 19.26
April 645.00 20.10 270.17 18.97 270.17 18.97
May 669.00 19.79 334.00 18.74 334.00 18.74
June 660.00 19.74 305.00 18.59 305.00 18.59
July 654.00 19.67 307.67 18.53 307.67 18.53
August 684.00 19.76 298.00 18.57 298.00 18.57
September 645.00 19.73 324.00 18.68 324.00 18.68
October 654.00 19.94 306.00 18.88 306.00 18.88
November 630.00 20.43 182.17 19.15 182.17 19.15
December 654.00 20.98 102.33 19.51 102.33 19.51
             
Annual Sum or Average 7830.00 20.22 2770.33 18.84 2770.33 18.84
Minimum of Months 597.00 19.67 82.83 18.53 82.83 18.53
Maximum of Months 684.00 21.00 334.00 19.53 334.00 19.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 604.00 22.27 21.17 20.29 21.17 20.29
February 551.00 22.48 1.67 20.52 1.67 20.52
March 630.00 22.41 3.33 20.52 3.33 20.52
April 595.00 22.00 11.50 20.44 11.50 20.44
May 617.00 21.74 34.67 20.26 34.67 20.26
June 608.00 21.72 7.33 20.24 7.33 20.24
July 604.00 21.63 4.83 20.19 4.83 20.19
August 630.00 21.74 4.00 20.22 4.00 20.22
September 595.00 21.71 22.17 20.17 22.17 20.17
October 604.00 21.85 27.17 20.40 27.17 20.40
November 582.00 22.19 2.83 20.52 2.83 20.52
December 604.00 22.45 0.50 20.64 0.50 20.64
             
Annual Sum or Average 7224.00 22.01 141.17 20.30 141.17 20.30
Minimum of Months 551.00 21.63 0.50 20.17 0.50 20.17
Maximum of Months 630.00 22.48 34.67 20.64 34.67 20.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 604.00 19.32 604.00 19.32 604.00 19.32
February 551.00 19.44 551.00 19.44 551.00 19.44
March 630.00 19.54 622.83 19.52 622.83 19.52
April 595.00 19.64 555.17 19.53 555.17 19.53
May 617.00 20.23 370.00 19.60 370.00 19.60
June 608.00 20.74 194.67 19.66 194.67 19.66
July 604.00 21.21 56.83 19.82 56.83 19.82
August 630.00 21.34 28.00 19.99 28.00 19.99
September 595.00 20.90 154.33 20.00 154.33 20.00
October 604.00 20.34 337.17 19.76 337.17 19.76
November 582.00 19.90 459.67 19.58 459.67 19.58
December 604.00 19.47 598.50 19.46 598.50 19.46
             
Annual Sum or Average 7224.00 20.18 4532.17 19.54 4532.17 19.54
Minimum of Months 551.00 19.32 28.00 19.32 28.00 19.32
Maximum of Months 630.00 21.34 622.83 20.00 622.83 20.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 604.00 22.49 13.83 20.51 13.83 20.51
February 551.00 22.70 0.00 0.00 0.00 0.00
March 630.00 22.65 0.00 0.00 0.00 0.00
April 595.00 22.32 0.00 0.00 0.00 0.00
May 617.00 22.10 3.50 20.37 3.50 20.37
June 608.00 22.08 0.00 0.00 0.00 0.00
July 604.00 22.01 0.00 0.00 0.00 0.00
August 630.00 22.10 0.00 0.00 0.00 0.00
September 595.00 22.08 0.00 0.00 0.00 0.00
October 604.00 22.20 0.00 0.00 0.00 0.00
November 582.00 22.47 0.00 0.00 0.00 0.00
December 604.00 22.67 0.00 0.00 0.00 0.00
             
Annual Sum or Average 7224.00 22.32 17.33 20.48 17.33 20.48
Minimum of Months 551.00 22.01 0.00 0.00 0.00 0.00
Maximum of Months 630.00 22.70 13.83 20.51 13.83 20.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 IT HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 IT ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 604.00 20.82 297.33 20.10 297.33 20.10
February 551.00 21.14 170.33 20.28 170.33 20.28
March 630.00 21.20 168.67 20.28 168.67 20.28
April 595.00 20.93 229.00 20.12 229.00 20.12
May 617.00 20.95 198.00 20.01 198.00 20.01
June 608.00 21.17 86.00 19.98 86.00 19.98
July 604.00 21.28 42.50 19.94 42.50 19.94
August 630.00 21.37 29.17 19.99 29.17 19.99
September 595.00 21.08 109.33 19.96 109.33 19.96
October 604.00 20.94 213.00 20.09 213.00 20.09
November 582.00 21.13 173.17 20.26 173.17 20.26
December 604.00 21.17 185.00 20.25 185.00 20.25
             
Annual Sum or Average 7224.00 21.10 1901.50 20.13 1901.50 20.13
Minimum of Months 551.00 20.82 29.17 19.94 29.17 19.94
Maximum of Months 630.00 21.37 297.33 20.28 297.33 20.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 LOBBY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 20.96 244.50 19.89 244.50 19.89
February 597.00 21.37 114.00 20.09 114.00 20.09
March 684.00 21.58 80.17 20.17 80.17 20.17
April 640.33 21.71 51.67 20.09 51.67 20.09
May 636.67 22.05 25.00 22.34 12.00 19.82
June 609.67 22.18 18.17 24.59 0.00 0.00
July 583.00 22.37 38.33 24.51 0.00 0.00
August 621.33 22.38 27.83 24.53 0.00 0.00
September 629.67 22.20 2.33 24.42 0.00 0.00
October 654.00 21.91 21.50 20.12 21.50 20.12
November 630.00 21.65 59.67 20.19 59.67 20.19
December 654.00 21.25 155.33 19.95 155.33 19.95
             
Annual Sum or Average 7593.67 21.79 838.50 20.55 738.83 20.01
Minimum of Months 583.00 20.96 2.33 19.89 0.00 0.00
Maximum of Months 684.00 22.38 244.50 24.59 244.50 20.19



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 22.03 36.00 19.85 36.00 19.85
February 597.00 22.30 6.00 20.25 6.00 20.25
March 684.00 22.34 5.00 20.51 5.00 20.51
April 645.00 22.25 5.33 20.49 5.33 20.49
May 663.83 22.32 1.33 20.52 1.33 20.52
June 649.50 22.42 0.00 0.00 0.00 0.00
July 638.00 22.48 0.00 0.00 0.00 0.00
August 662.33 22.51 0.00 0.00 0.00 0.00
September 642.00 22.46 0.00 0.00 0.00 0.00
October 654.00 22.43 3.17 20.51 3.17 20.51
November 630.00 22.45 0.00 0.00 0.00 0.00
December 654.00 22.30 19.83 20.48 19.83 20.48
             
Annual Sum or Average 7773.67 22.36 76.67 20.17 76.67 20.17
Minimum of Months 597.00 22.03 0.00 0.00 0.00 0.00
Maximum of Months 684.00 22.51 36.00 20.52 36.00 20.52



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 22.37 25.00 20.35 25.00 20.35
February 597.00 22.56 4.33 20.41 4.33 20.41
March 684.00 22.54 1.17 20.64 1.17 20.64
April 645.00 22.31 1.67 20.66 1.67 20.66
May 669.00 22.23 3.50 20.22 3.50 20.22
June 660.00 22.27 0.00 0.00 0.00 0.00
July 654.00 22.28 0.00 0.00 0.00 0.00
August 684.00 22.32 0.00 0.00 0.00 0.00
September 645.00 22.25 3.17 20.36 3.17 20.36
October 654.00 22.29 3.67 20.39 3.67 20.39
November 630.00 22.47 0.00 0.00 0.00 0.00
December 654.00 22.56 5.17 20.78 5.17 20.78
             
Annual Sum or Average 7830.00 22.37 47.67 20.41 47.67 20.41
Minimum of Months 597.00 22.23 0.00 0.00 0.00 0.00
Maximum of Months 684.00 22.56 25.00 20.78 25.00 20.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 MED GAS

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 614.17 22.89 6.83 20.90 6.83 20.90
February 542.67 23.01 0.00 0.00 0.00 0.00
March 610.50 22.87 0.00 0.00 0.00 0.00
April 571.00 22.77 5.00 24.98 0.00 0.00
May 531.50 22.78 53.00 24.82 0.00 0.00
June 440.83 22.67 114.50 24.71 0.00 0.00
July 339.00 22.51 173.17 24.71 0.00 0.00
August 364.00 22.50 160.83 24.71 0.00 0.00
September 464.00 22.77 72.83 24.84 0.00 0.00
October 538.67 22.83 21.17 24.93 0.00 0.00
November 544.17 22.91 2.33 24.87 0.00 0.00
December 594.67 23.03 0.17 21.02 0.17 21.02
             
Annual Sum or Average 6155.17 22.82 609.83 24.70 7.00 20.90
Minimum of Months 339.00 22.50 0.00 0.00 0.00 0.00
Maximum of Months 614.17 23.03 173.17 24.98 6.83 21.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 MRI HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 MRI ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 225.83 22.95 81.50 24.98 0.00 0.00
February 192.67 22.65 102.50 24.99 0.00 0.00
March 301.67 22.55 101.33 24.98 0.00 0.00
April 327.00 22.52 94.50 24.93 0.00 0.00
May 260.67 22.46 150.33 24.80 0.00 0.00
June 199.83 22.35 242.33 24.68 0.00 0.00
July 127.83 22.34 315.67 24.66 0.00 0.00
August 132.33 22.37 315.83 24.64 0.00 0.00
September 245.83 22.33 189.67 24.79 0.00 0.00
October 311.50 22.46 117.00 24.90 0.00 0.00
November 308.50 22.51 91.50 24.96 0.00 0.00
December 223.67 22.84 105.17 24.97 0.00 0.00
             
Annual Sum or Average 2857.33 22.53 1907.33 24.79 0.00  
Minimum of Months 127.83 22.33 81.50 24.64 0.00 0.00
Maximum of Months 327.00 22.95 315.83 24.99 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 MRI TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 645.50 22.63 12.33 20.74 12.33 20.74
February 584.67 22.80 0.00 0.00 0.00 0.00
March 668.83 22.72 0.00 0.00 0.00 0.00
April 644.17 22.40 0.00 0.00 0.00 0.00
May 669.00 22.18 3.50 20.19 3.50 20.19
June 660.00 22.17 0.00 0.00 0.00 0.00
July 654.00 22.10 0.00 0.00 0.00 0.00
August 684.00 22.19 0.00 0.00 0.00 0.00
September 645.00 22.16 3.17 20.25 3.17 20.25
October 654.00 22.28 3.17 20.39 3.17 20.39
November 627.33 22.57 0.00 0.00 0.00 0.00
December 642.17 22.78 0.00 0.00 0.00 0.00
             
Annual Sum or Average 7778.67 22.41 22.17 20.54 22.17 20.54
Minimum of Months 584.67 22.10 0.00 0.00 0.00 0.00
Maximum of Months 684.00 22.80 12.33 20.74 12.33 20.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 NURSE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 NURSE STATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 22.32 27.00 20.38 27.00 20.38
February 597.00 22.52 4.33 20.38 4.33 20.38
March 684.00 22.48 3.33 20.42 3.33 20.42
April 645.00 22.16 9.67 20.32 9.67 20.32
May 669.00 21.97 27.83 20.19 27.83 20.19
June 660.00 21.97 6.67 20.13 6.67 20.13
July 654.00 21.92 3.33 20.15 3.33 20.15
August 684.00 22.02 0.00 0.00 0.00 0.00
September 645.00 21.98 16.67 20.25 16.67 20.25
October 654.00 22.06 21.83 20.40 21.83 20.40
November 630.00 22.30 7.17 20.41 7.17 20.41
December 654.00 22.47 5.83 20.66 5.83 20.66
             
Annual Sum or Average 7830.00 22.18 133.67 20.32 133.67 20.32
Minimum of Months 597.00 21.92 0.00 0.00 0.00 0.00
Maximum of Months 684.00 22.52 27.83 20.66 27.83 20.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 604.00 22.00 31.33 20.05 31.33 20.05
February 551.00 22.29 4.50 20.49 4.50 20.49
March 630.00 22.34 0.00 0.00 0.00 0.00
April 595.00 22.21 0.00 0.00 0.00 0.00
May 617.00 22.17 0.00 0.00 0.00 0.00
June 608.00 22.22 0.00 0.00 0.00 0.00
July 604.00 22.24 0.00 0.00 0.00 0.00
August 630.00 22.29 0.00 0.00 0.00 0.00
September 595.00 22.22 0.00 0.00 0.00 0.00
October 604.00 22.20 1.17 20.57 1.17 20.57
November 582.00 22.27 0.00 0.00 0.00 0.00
December 604.00 22.25 7.67 20.55 7.67 20.55
             
Annual Sum or Average 7224.00 22.22 44.67 20.20 44.67 20.20
Minimum of Months 551.00 22.00 0.00 0.00 0.00 0.00
Maximum of Months 630.00 22.34 31.33 20.57 31.33 20.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.55 521.00 19.12 521.00 19.12
February 597.00 19.63 455.83 19.08 455.83 19.08
March 684.00 19.39 548.33 18.84 548.33 18.84
April 645.00 18.93 542.50 18.47 542.50 18.47
May 669.00 18.92 510.83 18.48 510.83 18.48
June 660.00 19.00 415.00 18.37 415.00 18.37
July 654.00 19.10 269.67 18.25 269.67 18.25
August 684.00 19.23 262.83 18.24 262.83 18.24
September 645.00 19.08 402.83 18.42 402.83 18.42
October 654.00 19.08 496.50 18.53 496.50 18.53
November 630.00 19.27 507.17 18.69 507.17 18.69
December 654.00 19.64 487.00 19.03 487.00 19.03
             
Annual Sum or Average 7830.00 19.23 5419.50 18.66 5419.50 18.66
Minimum of Months 597.00 18.92 262.83 18.24 262.83 18.24
Maximum of Months 684.00 19.64 548.33 19.12 548.33 19.12



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.78 418.50 18.98 418.50 18.98
February 597.00 19.80 355.17 18.75 355.17 18.75
March 684.00 19.46 468.33 18.49 468.33 18.49
April 645.00 18.83 515.17 18.19 515.17 18.19
May 669.00 18.35 505.50 17.64 505.50 17.64
June 660.00 18.27 436.83 17.28 436.83 17.28
July 654.00 18.46 346.67 17.22 346.67 17.22
August 684.00 18.73 365.33 17.51 365.33 17.51
September 645.00 18.26 471.17 17.47 471.17 17.47
October 654.00 18.56 528.33 17.94 528.33 17.94
November 630.00 19.16 481.83 18.39 481.83 18.39
December 654.00 19.88 397.50 18.88 397.50 18.88
             
Annual Sum or Average 7830.00 18.96 5290.33 18.06 5290.33 18.06
Minimum of Months 597.00 18.26 346.67 17.22 346.67 17.22
Maximum of Months 684.00 19.88 528.33 18.98 528.33 18.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.04 449.33 18.60 449.33 18.60
February 597.00 19.03 421.33 18.63 421.33 18.63
March 684.00 18.60 563.83 18.34 563.83 18.34
April 645.00 17.79 638.67 17.77 638.67 17.77
May 669.00 17.34 669.00 17.34 669.00 17.34
June 660.00 17.21 660.00 17.21 660.00 17.21
July 654.00 17.14 654.00 17.14 654.00 17.14
August 684.00 17.21 684.00 17.21 684.00 17.21
September 645.00 17.21 645.00 17.21 645.00 17.21
October 654.00 17.58 654.00 17.58 654.00 17.58
November 630.00 18.23 614.50 18.19 614.50 18.19
December 654.00 19.09 431.33 18.66 431.33 18.66
             
Annual Sum or Average 7830.00 17.95 7085.00 17.74 7085.00 17.74
Minimum of Months 597.00 17.14 421.33 17.14 421.33 17.14
Maximum of Months 684.00 19.09 684.00 18.66 684.00 18.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 PACU

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 20.76 162.17 19.31 162.17 19.31
February 597.00 20.89 118.67 19.51 118.67 19.51
March 684.00 20.64 168.00 19.22 168.00 19.22
April 645.00 19.97 294.00 18.85 294.00 18.85
May 669.00 19.68 358.50 18.65 358.50 18.65
June 660.00 19.64 327.00 18.50 327.00 18.50
July 654.00 19.57 332.33 18.46 332.33 18.46
August 684.00 19.65 321.50 18.46 321.50 18.46
September 645.00 19.63 344.17 18.59 344.17 18.59
October 654.00 19.83 328.17 18.77 328.17 18.77
November 630.00 20.31 231.67 19.15 231.67 19.15
December 654.00 20.87 142.83 19.46 142.83 19.46
             
Annual Sum or Average 7830.00 20.12 3129.00 18.79 3129.00 18.79
Minimum of Months 597.00 19.57 118.67 18.46 118.67 18.46
Maximum of Months 684.00 20.89 358.50 19.51 358.50 19.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.52 628.50 19.46 628.50 19.46
February 597.00 19.75 541.50 19.63 541.50 19.63
March 684.00 19.70 629.33 19.60 629.33 19.60
April 645.00 19.39 538.00 19.12 538.00 19.12
May 669.00 19.34 456.67 18.72 456.67 18.72
June 660.00 19.40 384.83 18.50 384.83 18.50
July 654.00 19.38 369.33 18.42 369.33 18.42
August 684.00 19.45 365.67 18.42 365.67 18.42
September 645.00 19.34 406.00 18.56 406.00 18.56
October 654.00 19.38 483.17 18.94 483.17 18.94
November 630.00 19.65 492.00 19.36 492.00 19.36
December 654.00 19.73 585.50 19.58 585.50 19.58
             
Annual Sum or Average 7830.00 19.50 5880.50 19.11 5880.50 19.11
Minimum of Months 597.00 19.34 365.67 18.42 365.67 18.42
Maximum of Months 684.00 19.75 629.33 19.63 629.33 19.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 20.36 184.83 19.17 184.83 19.17
February 597.00 20.56 113.50 19.24 113.50 19.24
March 684.00 20.43 159.17 18.92 159.17 18.92
April 645.00 19.81 302.17 18.67 302.17 18.67
May 669.00 19.52 369.00 18.52 369.00 18.52
June 660.00 19.50 341.83 18.40 341.83 18.40
July 654.00 19.42 345.50 18.37 345.50 18.37
August 684.00 19.51 338.67 18.37 338.67 18.37
September 645.00 19.47 360.00 18.46 360.00 18.46
October 654.00 19.67 339.83 18.63 339.83 18.63
November 630.00 20.16 218.00 18.90 218.00 18.90
December 654.00 20.53 141.83 19.26 141.83 19.26
             
Annual Sum or Average 7830.00 19.90 3214.33 18.63 3214.33 18.63
Minimum of Months 597.00 19.42 113.50 18.37 113.50 18.37
Maximum of Months 684.00 20.56 369.00 19.26 369.00 19.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.44 525.50 19.08 525.50 19.08
February 597.00 19.54 441.67 19.09 441.67 19.09
March 684.00 19.54 493.50 19.10 493.50 19.10
April 645.00 19.30 484.33 18.86 484.33 18.86
May 669.00 19.24 448.00 18.60 448.00 18.60
June 660.00 19.27 390.33 18.43 390.33 18.43
July 654.00 19.24 382.83 18.39 382.83 18.39
August 684.00 19.31 380.33 18.38 380.33 18.38
September 645.00 19.23 404.67 18.48 404.67 18.48
October 654.00 19.29 438.17 18.68 438.17 18.68
November 630.00 19.48 422.00 18.90 422.00 18.90
December 654.00 19.55 483.83 19.09 483.83 19.09
             
Annual Sum or Average 7830.00 19.37 5295.17 18.78 5295.17 18.78
Minimum of Months 597.00 19.23 380.33 18.38 380.33 18.38
Maximum of Months 684.00 19.55 525.50 19.10 525.50 19.10



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 652.83 22.05 42.33 20.02 42.33 20.02
February 596.00 22.34 4.33 20.36 4.33 20.36
March 682.17 22.38 1.17 20.76 1.17 20.76
April 644.83 22.27 4.00 20.21 4.00 20.21
May 654.83 22.28 5.17 21.61 3.33 20.22
June 634.00 22.33 5.33 24.14 0.00 0.00
July 620.83 22.41 10.00 24.15 0.00 0.00
August 638.67 22.48 15.50 24.17 0.00 0.00
September 627.83 22.45 2.67 24.24 0.00 0.00
October 645.83 22.38 0.00 0.00 0.00 0.00
November 625.83 22.36 2.33 20.63 2.33 20.63
December 654.00 22.27 17.33 20.17 17.33 20.17
             
Annual Sum or Average 7677.67 22.33 110.17 21.42 74.83 20.12
Minimum of Months 596.00 22.05 0.00 0.00 0.00 0.00
Maximum of Months 682.17 22.48 42.33 24.24 42.33 20.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.91 430.33 19.24 430.33 19.24
February 597.00 20.08 343.33 19.34 343.33 19.34
March 684.00 20.03 383.67 19.27 383.67 19.27
April 645.00 19.73 389.17 18.90 389.17 18.90
May 669.00 19.61 379.00 18.60 379.00 18.60
June 660.00 19.63 339.67 18.48 339.67 18.48
July 654.00 19.60 317.50 18.42 317.50 18.42
August 684.00 19.71 299.33 18.42 299.33 18.42
September 645.00 19.69 329.83 18.55 329.83 18.55
October 654.00 19.79 342.50 18.72 342.50 18.72
November 630.00 19.97 333.50 19.05 333.50 19.05
December 654.00 20.02 400.83 19.34 400.83 19.34
             
Annual Sum or Average 7830.00 19.81 4288.67 18.89 4288.67 18.89
Minimum of Months 597.00 19.60 299.33 18.42 299.33 18.42
Maximum of Months 684.00 20.08 430.33 19.34 430.33 19.34



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 SCHEDULING

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 604.00 20.88 252.50 20.13 252.50 20.13
February 551.00 21.29 113.83 20.37 113.83 20.37
March 630.00 21.33 111.67 20.40 111.67 20.40
April 595.00 21.28 114.33 20.31 114.33 20.31
May 617.00 21.48 64.17 20.18 64.17 20.18
June 608.00 21.66 14.50 20.22 14.50 20.22
July 604.00 21.83 1.17 20.28 1.17 20.28
August 630.00 21.99 0.00 0.00 0.00 0.00
September 595.00 21.88 0.00 0.00 0.00 0.00
October 604.00 21.73 24.17 20.38 24.17 20.38
November 582.00 21.60 44.17 20.44 44.17 20.44
December 604.00 21.26 132.83 20.26 132.83 20.26
             
Annual Sum or Average 7224.00 21.52 873.33 20.27 873.33 20.27
Minimum of Months 551.00 20.88 0.00 0.00 0.00 0.00
Maximum of Months 630.00 21.99 252.50 20.44 252.50 20.44



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 SCRUB

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 SOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 20.92 108.83 19.29 108.83 19.29
February 597.00 21.08 59.33 19.45 59.33 19.45
March 684.00 20.83 110.17 19.22 110.17 19.22
April 645.00 20.14 259.83 19.00 259.83 19.00
May 669.00 19.80 328.00 18.76 328.00 18.76
June 660.00 19.75 301.33 18.60 301.33 18.60
July 654.00 19.67 308.17 18.54 308.17 18.54
August 684.00 19.76 297.00 18.57 297.00 18.57
September 645.00 19.74 321.50 18.69 321.50 18.69
October 654.00 19.97 296.67 18.90 296.67 18.90
November 630.00 20.48 171.67 19.19 171.67 19.19
December 654.00 21.06 80.67 19.48 80.67 19.48
             
Annual Sum or Average 7830.00 20.26 2643.17 18.83 2643.17 18.83
Minimum of Months 597.00 19.67 59.33 18.54 59.33 18.54
Maximum of Months 684.00 21.08 328.00 19.48 328.00 19.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.74 508.33 19.41 508.33 19.41
February 597.00 19.90 443.67 19.59 443.67 19.59
March 684.00 19.71 513.17 19.44 513.17 19.44
April 645.00 19.09 583.50 18.96 583.50 18.96
May 669.00 18.90 550.83 18.66 550.83 18.66
June 660.00 19.01 470.33 18.59 470.33 18.59
July 654.00 19.07 448.33 18.63 448.33 18.63
August 684.00 19.17 433.00 18.66 433.00 18.66
September 645.00 18.93 514.83 18.64 514.83 18.64
October 654.00 19.01 577.67 18.86 577.67 18.86
November 630.00 19.48 518.17 19.29 518.17 19.29
December 654.00 19.96 473.50 19.63 473.50 19.63
             
Annual Sum or Average 7830.00 19.33 6035.33 19.03 6035.33 19.03
Minimum of Months 597.00 18.90 433.00 18.59 433.00 18.59
Maximum of Months 684.00 19.96 583.50 19.63 583.50 19.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 SOIL WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 20.64 184.33 19.38 184.33 19.38
February 597.00 20.81 131.50 19.54 131.50 19.54
March 684.00 20.60 179.00 19.27 179.00 19.27
April 645.00 19.97 306.17 18.92 306.17 18.92
May 669.00 19.69 365.67 18.70 365.67 18.70
June 660.00 19.66 333.00 18.55 333.00 18.55
July 654.00 19.59 335.67 18.50 335.67 18.50
August 684.00 19.68 325.33 18.52 325.33 18.52
September 645.00 19.65 350.67 18.64 350.67 18.64
October 654.00 19.83 337.33 18.82 337.33 18.82
November 630.00 20.29 240.17 19.19 240.17 19.19
December 654.00 20.77 154.00 19.47 154.00 19.47
             
Annual Sum or Average 7830.00 20.09 3242.83 18.85 3242.83 18.85
Minimum of Months 597.00 19.59 131.50 18.50 131.50 18.50
Maximum of Months 684.00 20.81 365.67 19.54 365.67 19.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 STEP DOWN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.74 492.17 19.25 492.17 19.25
February 597.00 19.89 404.17 19.30 404.17 19.30
March 684.00 19.92 464.00 19.37 464.00 19.37
April 645.00 19.76 413.00 19.05 413.00 19.05
May 669.00 19.73 370.00 18.72 370.00 18.72
June 660.00 19.78 309.17 18.53 309.17 18.53
July 654.00 19.86 273.50 18.51 273.50 18.51
August 684.00 20.03 252.00 18.59 252.00 18.59
September 645.00 19.90 302.00 18.67 302.00 18.67
October 654.00 19.89 341.83 18.83 341.83 18.83
November 630.00 19.95 366.33 19.12 366.33 19.12
December 654.00 19.84 475.67 19.36 475.67 19.36
             
Annual Sum or Average 7830.00 19.86 4463.83 19.00 4463.83 19.00
Minimum of Months 597.00 19.73 252.00 18.51 252.00 18.51
Maximum of Months 684.00 20.03 492.17 19.37 492.17 19.37



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 STERILE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 1 VESTIBULE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 CONFERENCE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 559.00 19.92 427.00 19.30 427.00 19.30
February 508.00 20.24 338.50 19.37 338.50 19.37
March 583.00 20.63 325.33 19.56 325.33 19.56
April 545.00 20.89 244.83 19.67 244.83 19.67
May 571.00 21.15 149.33 19.77 149.33 19.77
June 558.50 21.24 55.67 19.54 55.67 19.54
July 554.00 21.20 52.00 19.23 52.00 19.23
August 581.17 21.34 24.83 19.66 24.83 19.66
September 542.33 21.21 84.33 19.81 84.33 19.81
October 559.00 20.91 212.33 19.49 212.33 19.49
November 543.00 20.43 319.17 19.40 319.17 19.40
December 554.00 19.93 422.17 19.31 422.17 19.31
             
Annual Sum or Average 6658.00 20.76 2655.50 19.45 2655.50 19.45
Minimum of Months 508.00 19.92 24.83 19.23 24.83 19.23
Maximum of Months 583.00 21.34 427.00 19.81 427.00 19.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 604.00 21.53 198.83 20.63 198.83 20.63
February 551.00 21.79 97.83 20.68 97.83 20.68
March 630.00 21.96 74.50 20.79 74.50 20.79
April 595.00 21.95 65.83 20.68 65.83 20.68
May 617.00 21.88 50.83 20.44 50.83 20.44
June 608.00 21.87 13.17 20.25 13.17 20.25
July 604.00 21.78 12.83 20.16 12.83 20.16
August 630.00 21.91 0.00 0.00 0.00 0.00
September 595.00 21.94 18.17 20.25 18.17 20.25
October 604.00 21.88 63.83 20.50 63.83 20.50
November 582.00 21.78 110.50 20.63 110.50 20.63
December 604.00 21.64 145.33 20.65 145.33 20.65
             
Annual Sum or Average 7224.00 21.83 851.67 20.61 851.67 20.61
Minimum of Months 551.00 21.53 0.00 0.00 0.00 0.00
Maximum of Months 630.00 21.96 198.83 20.79 198.83 20.79



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.59 634.83 19.54 634.83 19.54
February 597.00 19.73 524.17 19.52 524.17 19.52
March 684.00 19.96 522.33 19.54 522.33 19.54
April 645.00 20.26 377.00 19.48 377.00 19.48
May 664.50 20.48 215.00 19.31 215.00 19.31
June 653.17 20.47 141.00 19.06 140.00 19.03
July 649.33 20.50 95.17 18.80 95.17 18.80
August 678.83 20.51 95.50 18.97 95.50 18.97
September 644.83 20.41 198.50 19.20 198.50 19.20
October 654.00 20.11 343.33 19.22 343.33 19.22
November 630.00 19.79 475.33 19.36 475.33 19.36
December 654.00 19.58 640.50 19.55 640.50 19.55
             
Annual Sum or Average 7808.67 20.12 4262.67 19.42 4261.67 19.41
Minimum of Months 597.00 19.58 95.17 18.80 95.17 18.80
Maximum of Months 684.00 20.51 640.50 19.55 640.50 19.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.76 508.83 19.38 508.83 19.38
February 597.00 19.89 418.33 19.38 418.33 19.38
March 684.00 20.03 424.33 19.41 424.33 19.41
April 645.00 20.03 362.50 19.27 362.50 19.27
May 669.00 19.92 321.17 18.98 321.17 18.98
June 660.00 19.84 266.83 18.71 266.83 18.71
July 654.00 19.75 248.00 18.56 248.00 18.56
August 684.00 19.84 229.00 18.57 229.00 18.57
September 645.00 19.98 242.67 18.93 242.67 18.93
October 654.00 19.99 321.33 19.09 321.33 19.09
November 630.00 19.91 390.50 19.24 390.50 19.24
December 654.00 19.75 508.83 19.37 508.83 19.37
             
Annual Sum or Average 7830.00 19.89 4242.33 19.15 4242.33 19.15
Minimum of Months 597.00 19.75 229.00 18.56 229.00 18.56
Maximum of Months 684.00 20.03 508.83 19.41 508.83 19.41



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.76 498.50 19.34 498.50 19.34
February 597.00 19.88 410.83 19.33 410.83 19.33
March 684.00 19.99 427.50 19.36 427.50 19.36
April 645.00 19.96 374.83 19.20 374.83 19.20
May 669.00 19.82 344.17 18.86 344.17 18.86
June 660.00 19.76 304.33 18.62 304.33 18.62
July 654.00 19.66 297.50 18.49 297.50 18.49
August 684.00 19.75 282.83 18.51 282.83 18.51
September 645.00 19.89 279.67 18.84 279.67 18.84
October 654.00 19.92 336.17 19.01 336.17 19.01
November 630.00 19.88 392.83 19.19 392.83 19.19
December 654.00 19.74 501.33 19.33 501.33 19.33
             
Annual Sum or Average 7830.00 19.83 4450.50 19.06 4450.50 19.06
Minimum of Months 597.00 19.66 279.67 18.49 279.67 18.49
Maximum of Months 684.00 19.99 501.33 19.36 501.33 19.36



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.85 521.50 19.44 521.50 19.44
February 597.00 20.16 406.00 19.50 406.00 19.50
March 684.00 20.34 414.67 19.60 414.67 19.60
April 645.00 20.45 342.50 19.58 342.50 19.58
May 669.00 20.38 270.00 19.38 270.00 19.38
June 660.00 20.33 192.33 19.14 192.33 19.14
July 654.00 20.28 156.67 18.91 156.67 18.91
August 684.00 20.44 124.33 19.05 124.33 19.05
September 645.00 20.54 179.83 19.32 179.83 19.32
October 654.00 20.39 285.67 19.35 285.67 19.35
November 630.00 20.12 406.00 19.45 406.00 19.45
December 654.00 19.82 541.67 19.50 541.67 19.50
             
Annual Sum or Average 7830.00 20.26 3841.17 19.42 3841.17 19.42
Minimum of Months 597.00 19.82 124.33 18.91 124.33 18.91
Maximum of Months 684.00 20.54 541.67 19.60 541.67 19.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.64 617.67 19.55 617.67 19.55
February 597.00 19.71 491.00 19.42 491.00 19.42
March 684.00 19.93 452.50 19.32 452.50 19.32
April 645.00 20.21 347.00 19.32 347.00 19.32
May 669.00 20.35 223.33 19.35 223.33 19.35
June 660.00 20.43 87.50 19.12 87.50 19.12
July 654.00 20.39 79.33 18.89 79.33 18.89
August 684.00 20.34 45.33 19.09 45.33 19.09
September 645.00 20.31 164.17 19.28 164.17 19.28
October 654.00 20.09 319.17 19.23 319.17 19.23
November 630.00 19.85 408.00 19.22 408.00 19.22
December 654.00 19.65 596.50 19.51 596.50 19.51
             
Annual Sum or Average 7830.00 20.08 3831.50 19.36 3831.50 19.36
Minimum of Months 597.00 19.64 45.33 18.89 45.33 18.89
Maximum of Months 684.00 20.43 617.67 19.55 617.67 19.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.62 634.50 19.57 634.50 19.57
February 597.00 19.67 540.67 19.52 540.67 19.52
March 684.00 19.80 541.83 19.46 541.83 19.46
April 645.00 19.87 430.83 19.28 430.83 19.28
May 669.00 19.92 336.33 19.02 336.33 19.02
June 660.00 19.94 258.50 18.83 258.50 18.83
July 654.00 19.86 233.83 18.68 233.83 18.68
August 684.00 19.91 240.33 18.72 240.33 18.72
September 645.00 19.94 293.00 18.96 293.00 18.96
October 654.00 19.87 375.17 19.06 375.17 19.06
November 630.00 19.77 473.83 19.35 473.83 19.35
December 654.00 19.63 613.17 19.53 613.17 19.53
             
Annual Sum or Average 7830.00 19.82 4972.00 19.27 4972.00 19.27
Minimum of Months 597.00 19.62 233.83 18.68 233.83 18.68
Maximum of Months 684.00 19.94 634.50 19.57 634.50 19.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 7

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.72 570.67 19.53 570.67 19.53
February 597.00 19.79 464.17 19.43 464.17 19.43
March 684.00 19.92 456.33 19.37 456.33 19.37
April 645.00 19.92 380.83 19.16 380.83 19.16
May 669.00 19.84 339.17 18.88 339.17 18.88
June 660.00 19.79 292.33 18.66 292.33 18.66
July 654.00 19.68 283.67 18.51 283.67 18.51
August 684.00 19.75 279.00 18.52 279.00 18.52
September 645.00 19.87 285.33 18.83 285.33 18.83
October 654.00 19.90 344.67 19.01 344.67 19.01
November 630.00 19.86 394.83 19.19 394.83 19.19
December 654.00 19.75 528.33 19.43 528.33 19.43
             
Annual Sum or Average 7830.00 19.82 4619.33 19.12 4619.33 19.12
Minimum of Months 597.00 19.68 279.00 18.51 279.00 18.51
Maximum of Months 684.00 19.92 570.67 19.53 570.67 19.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.66 626.33 19.59 626.33 19.59
February 597.00 19.74 520.50 19.54 520.50 19.54
March 684.00 19.92 494.33 19.49 494.33 19.49
April 645.00 20.03 381.33 19.35 381.33 19.35
May 669.00 20.08 288.17 19.20 288.17 19.20
June 660.00 20.08 166.33 18.94 166.33 18.94
July 654.00 19.97 152.33 18.67 152.33 18.67
August 684.00 20.03 143.50 18.72 143.50 18.72
September 645.00 20.10 220.00 19.09 220.00 19.09
October 654.00 20.04 331.17 19.20 331.17 19.20
November 630.00 19.89 417.17 19.33 417.17 19.33
December 654.00 19.69 585.50 19.53 585.50 19.53
             
Annual Sum or Average 7830.00 19.94 4326.67 19.35 4326.67 19.35
Minimum of Months 597.00 19.66 143.50 18.67 143.50 18.67
Maximum of Months 684.00 20.10 626.33 19.59 626.33 19.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM 9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.76 578.17 19.59 578.17 19.59
February 597.00 19.85 467.83 19.52 467.83 19.52
March 684.00 20.01 448.33 19.48 448.33 19.48
April 645.00 20.06 366.17 19.33 366.17 19.33
May 669.00 20.01 301.50 19.13 301.50 19.13
June 660.00 19.97 186.00 18.81 186.00 18.81
July 654.00 19.86 174.67 18.59 174.67 18.59
August 684.00 19.94 169.67 18.64 169.67 18.64
September 645.00 20.06 213.50 19.02 213.50 19.02
October 654.00 20.05 314.17 19.20 314.17 19.20
November 630.00 19.96 379.33 19.30 379.33 19.30
December 654.00 19.80 530.17 19.50 530.17 19.50
             
Annual Sum or Average 7830.00 19.94 4129.50 19.30 4129.50 19.30
Minimum of Months 597.00 19.76 169.67 18.59 169.67 18.59
Maximum of Months 684.00 20.06 578.17 19.59 578.17 19.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 21.88 131.83 20.75 131.83 20.75
February 597.00 22.07 69.67 20.95 69.67 20.95
March 684.00 22.21 42.83 21.03 42.83 21.03
April 645.00 22.25 23.50 20.95 23.50 20.95
May 669.00 22.21 18.50 20.76 18.50 20.76
June 660.00 22.20 0.00 0.00 0.00 0.00
July 654.00 22.14 3.17 20.39 3.17 20.39
August 684.00 22.23 0.00 0.00 0.00 0.00
September 645.00 22.26 0.00 0.00 0.00 0.00
October 654.00 22.21 25.83 20.75 25.83 20.75
November 630.00 22.10 68.50 20.86 68.50 20.86
December 654.00 21.96 104.67 20.88 104.67 20.88
             
Annual Sum or Average 7830.00 22.14 488.50 20.85 488.50 20.85
Minimum of Months 597.00 21.88 0.00 0.00 0.00 0.00
Maximum of Months 684.00 22.26 131.83 21.03 131.83 21.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 21.69 158.33 20.48 158.33 20.48
February 597.00 21.90 86.50 20.65 86.50 20.65
March 684.00 22.08 55.00 20.77 55.00 20.77
April 645.00 22.13 24.50 20.75 24.50 20.75
May 669.00 22.14 10.00 20.60 10.00 20.60
June 660.00 22.14 0.00 0.00 0.00 0.00
July 654.00 22.08 0.00 0.00 0.00 0.00
August 684.00 22.15 0.00 0.00 0.00 0.00
September 645.00 22.15 0.17 20.36 0.17 20.36
October 654.00 22.10 26.00 20.50 26.00 20.50
November 630.00 21.99 77.00 20.65 77.00 20.65
December 654.00 21.80 120.17 20.55 120.17 20.55
             
Annual Sum or Average 7830.00 22.03 557.67 20.59 557.67 20.59
Minimum of Months 597.00 21.69 0.00 0.00 0.00 0.00
Maximum of Months 684.00 22.15 158.33 20.77 158.33 20.77



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 21.70 156.83 20.51 156.83 20.51
February 597.00 21.92 84.50 20.68 84.50 20.68
March 684.00 22.12 47.00 20.80 47.00 20.80
April 645.00 22.22 16.17 20.79 16.17 20.79
May 669.00 22.25 3.50 20.82 3.50 20.82
June 660.00 22.27 0.00 0.00 0.00 0.00
July 654.00 22.21 0.00 0.00 0.00 0.00
August 684.00 22.27 0.00 0.00 0.00 0.00
September 645.00 22.29 0.00 0.00 0.00 0.00
October 654.00 22.22 22.50 20.65 22.50 20.65
November 630.00 22.08 54.00 20.62 54.00 20.62
December 654.00 21.85 113.17 20.61 113.17 20.61
             
Annual Sum or Average 7830.00 22.12 497.67 20.62 497.67 20.62
Minimum of Months 597.00 21.70 0.00 0.00 0.00 0.00
Maximum of Months 684.00 22.29 156.83 20.82 156.83 20.82



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 604.00 19.81 588.83 19.77 588.83 19.77
February 551.00 20.19 478.17 19.97 478.17 19.97
March 630.00 20.79 393.50 20.21 393.50 20.21
April 595.00 21.44 158.50 20.26 158.50 20.26
May 617.00 22.03 18.67 20.32 18.67 20.32
June 606.17 22.25 0.00 0.00 0.00 0.00
July 604.00 22.32 1.33 20.23 1.33 20.23
August 626.83 22.28 0.00 0.00 0.00 0.00
September 595.00 21.92 5.50 20.35 5.50 20.35
October 604.00 21.33 153.00 20.26 153.00 20.26
November 582.00 20.64 371.33 20.05 371.33 20.05
December 604.00 19.92 577.17 19.85 577.17 19.85
             
Annual Sum or Average 7219.00 21.26 2746.00 19.98 2746.00 19.98
Minimum of Months 551.00 19.81 0.00 0.00 0.00 0.00
Maximum of Months 630.00 22.32 588.83 20.35 588.83 20.35



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 20.55 411.00 19.73 411.00 19.73
February 597.00 20.96 304.17 19.97 304.17 19.97
March 684.00 21.33 231.67 20.15 231.67 20.15
April 645.00 21.63 105.00 20.13 105.00 20.13
May 657.17 21.89 27.67 20.70 23.50 20.13
June 641.17 21.92 6.33 23.69 0.50 20.28
July 628.67 21.96 4.83 23.91 0.00 0.00
August 664.00 22.02 4.33 23.89 0.00 0.00
September 642.17 21.95 0.17 23.76 0.00 0.00
October 654.00 21.63 81.33 20.01 81.33 20.01
November 630.00 21.17 220.17 19.90 220.17 19.90
December 654.00 20.65 403.00 19.83 403.00 19.83
             
Annual Sum or Average 7751.17 21.48 1799.67 19.95 1780.33 19.91
Minimum of Months 597.00 20.55 0.17 19.73 0.00 0.00
Maximum of Months 684.00 22.02 411.00 23.91 411.00 20.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 604.00 21.86 95.83 20.66 95.83 20.66
February 551.00 22.09 49.17 20.96 49.17 20.96
March 630.00 22.26 21.33 21.09 21.33 21.09
April 595.00 22.30 11.67 20.96 11.67 20.96
May 617.00 22.27 0.67 21.09 0.67 21.09
June 608.00 22.26 0.00 0.00 0.00 0.00
July 604.00 22.21 0.00 0.00 0.00 0.00
August 630.00 22.28 0.00 0.00 0.00 0.00
September 595.00 22.30 0.00 0.00 0.00 0.00
October 604.00 22.25 19.67 20.91 19.67 20.91
November 582.00 22.15 48.33 20.97 48.33 20.97
December 604.00 22.00 72.00 20.86 72.00 20.86
             
Annual Sum or Average 7224.00 22.19 318.67 20.85 318.67 20.85
Minimum of Months 551.00 21.86 0.00 0.00 0.00 0.00
Maximum of Months 630.00 22.30 95.83 21.09 95.83 21.09



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 604.00 21.74 133.17 20.73 133.17 20.73
February 551.00 22.03 57.17 20.94 57.17 20.94
March 630.00 22.23 21.83 21.00 21.83 21.00
April 595.00 22.31 10.33 20.95 10.33 20.95
May 617.00 22.33 0.33 21.13 0.33 21.13
June 608.00 22.32 0.00 0.00 0.00 0.00
July 604.00 22.29 0.00 0.00 0.00 0.00
August 630.00 22.35 0.00 0.00 0.00 0.00
September 595.00 22.36 0.00 0.00 0.00 0.00
October 604.00 22.27 19.67 20.90 19.67 20.90
November 582.00 22.11 50.33 20.89 50.33 20.89
December 604.00 21.88 87.67 20.83 87.67 20.83
             
Annual Sum or Average 7224.00 22.19 380.50 20.84 380.50 20.84
Minimum of Months 551.00 21.74 0.00 0.00 0.00 0.00
Maximum of Months 630.00 22.36 133.17 21.13 133.17 21.13



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 STORAGE 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 604.00 21.04 357.83 20.49 357.83 20.49
February 551.00 21.40 217.67 20.66 217.67 20.66
March 630.00 21.74 115.33 20.69 115.33 20.69
April 595.00 22.01 30.50 20.66 30.50 20.66
May 617.00 22.28 5.67 20.74 5.67 20.74
June 608.00 22.40 0.00 0.00 0.00 0.00
July 604.00 22.43 0.00 0.00 0.00 0.00
August 630.00 22.44 0.00 0.00 0.00 0.00
September 595.00 22.33 0.00 0.00 0.00 0.00
October 604.00 22.08 27.17 20.50 27.17 20.50
November 582.00 21.74 121.83 20.63 121.83 20.63
December 604.00 21.26 264.00 20.52 264.00 20.52
             
Annual Sum or Average 7224.00 21.94 1140.00 20.57 1140.00 20.57
Minimum of Months 551.00 21.04 0.00 0.00 0.00 0.00
Maximum of Months 630.00 22.44 357.83 20.74 357.83 20.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 WORK HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 WORK TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 2 X-RAY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 580.50 23.27 0.17 22.13 0.17 22.13
February 497.67 23.42 1.50 25.00 0.00 0.00
March 476.33 23.48 15.67 25.00 0.00 0.00
April 445.50 23.39 8.00 24.95 0.00 0.00
May 444.17 23.04 58.33 24.77 0.00 0.00
June 392.67 22.68 95.83 24.67 0.00 0.00
July 402.50 22.66 112.50 24.59 0.00 0.00
August 358.33 22.63 139.33 24.54 0.00 0.00
September 277.50 22.90 107.00 24.69 0.00 0.00
October 341.33 23.35 58.00 24.88 0.00 0.00
November 436.17 23.44 18.50 24.86 0.00 0.00
December 565.67 23.36 1.83 24.98 0.00 0.00
             
Annual Sum or Average 5218.33 23.17 616.67 24.67 0.17 22.13
Minimum of Months 277.50 22.63 0.17 22.13 0.00 0.00
Maximum of Months 580.50 23.48 139.33 25.00 0.17 22.13



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 604.00 20.80 393.50 20.20 393.50 20.20
February 551.00 21.10 300.33 20.37 300.33 20.37
March 630.00 21.51 211.00 20.58 211.00 20.58
April 595.00 21.72 105.67 20.53 105.67 20.53
May 617.00 21.88 52.83 20.51 52.83 20.51
June 608.00 21.92 6.83 20.34 6.83 20.34
July 604.00 21.83 12.83 20.21 12.83 20.21
August 630.00 21.90 0.00 0.00 0.00 0.00
September 595.00 21.87 25.67 20.29 25.67 20.29
October 604.00 21.71 74.50 20.25 74.50 20.25
November 582.00 21.38 199.50 20.31 199.50 20.31
December 604.00 20.92 358.67 20.23 358.67 20.23
             
Annual Sum or Average 7224.00 21.55 1741.33 20.33 1741.33 20.33
Minimum of Months 551.00 20.80 0.00 0.00 0.00 0.00
Maximum of Months 630.00 21.92 393.50 20.58 393.50 20.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 604.00 20.92 363.67 20.22 363.67 20.22
February 551.00 21.23 265.50 20.39 265.50 20.39
March 630.00 21.66 168.67 20.60 168.67 20.60
April 595.00 21.88 75.33 20.49 75.33 20.49
May 617.00 22.04 35.67 20.50 35.67 20.50
June 608.00 22.08 3.67 20.42 3.67 20.42
July 604.00 22.00 2.00 20.29 2.00 20.29
August 630.00 22.06 0.00 0.00 0.00 0.00
September 595.00 22.03 9.67 20.32 9.67 20.32
October 604.00 21.87 66.67 20.33 66.67 20.33
November 582.00 21.52 171.67 20.33 171.67 20.33
December 604.00 21.03 325.17 20.24 325.17 20.24
             
Annual Sum or Average 7224.00 21.70 1487.67 20.34 1487.67 20.34
Minimum of Months 551.00 20.92 0.00 0.00 0.00 0.00
Maximum of Months 630.00 22.08 363.67 20.60 363.67 20.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 LOCKER

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 20.95 361.83 20.01 361.83 20.01
February 597.00 21.24 277.17 20.20 277.17 20.20
March 684.00 21.66 201.67 20.50 201.67 20.50
April 645.00 21.98 76.00 20.62 76.00 20.62
May 661.50 22.26 21.67 20.62 21.67 20.62
June 646.33 22.34 0.50 24.19 0.00 0.00
July 640.00 22.31 0.00 0.00 0.00 0.00
August 675.00 22.31 0.00 0.00 0.00 0.00
September 645.00 22.22 6.67 20.42 6.67 20.42
October 654.00 21.98 55.50 20.42 55.50 20.42
November 630.00 21.59 182.33 20.29 182.33 20.29
December 654.00 21.07 325.17 20.02 325.17 20.02
             
Annual Sum or Average 7785.83 21.83 1508.50 20.20 1508.00 20.20
Minimum of Months 597.00 20.95 0.00 0.00 0.00 0.00
Maximum of Months 684.00 22.34 361.83 24.19 361.83 20.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 21.03 351.50 20.05 351.50 20.05
February 597.00 21.35 268.33 20.30 268.33 20.30
March 684.00 21.75 177.50 20.50 177.50 20.50
April 645.00 22.14 49.50 20.72 49.50 20.72
May 646.83 22.39 11.83 22.40 6.33 20.69
June 612.83 22.43 8.50 24.47 0.00 0.00
July 597.50 22.41 13.17 24.35 0.00 0.00
August 642.50 22.41 6.50 24.31 0.00 0.00
September 632.00 22.36 0.00 0.00 0.00 0.00
October 654.00 22.14 35.33 20.55 35.33 20.55
November 630.00 21.75 162.50 20.45 162.50 20.45
December 654.00 21.17 314.50 20.11 314.50 20.11
             
Annual Sum or Average 7649.67 21.94 1399.17 20.36 1365.50 20.26
Minimum of Months 597.00 21.03 0.00 0.00 0.00 0.00
Maximum of Months 684.00 22.43 351.50 24.47 351.50 20.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 MECHANICAL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 604.00 20.04 539.67 19.82 539.67 19.82
February 551.00 20.43 421.00 19.96 421.00 19.96
March 630.00 20.98 351.17 20.22 351.17 20.22
April 595.00 21.54 155.50 20.48 155.50 20.48
May 616.83 22.04 35.83 20.51 35.83 20.51
June 603.33 22.22 0.00 0.00 0.00 0.00
July 601.50 22.25 0.00 0.00 0.00 0.00
August 630.00 22.20 0.00 0.00 0.00 0.00
September 595.00 21.98 8.50 20.33 8.50 20.33
October 604.00 21.56 113.33 20.30 113.33 20.30
November 582.00 21.00 286.33 20.08 286.33 20.08
December 604.00 20.24 495.83 19.88 495.83 19.88
             
Annual Sum or Average 7216.67 21.38 2407.17 20.02 2407.17 20.02
Minimum of Months 551.00 20.04 0.00 0.00 0.00 0.00
Maximum of Months 630.00 22.25 539.67 20.51 539.67 20.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.69 530.83 19.28 530.83 19.28
February 595.00 19.90 429.83 19.23 429.83 19.23
March 683.00 20.06 439.17 19.23 439.17 19.23
April 645.00 20.19 359.00 19.10 359.00 19.10
May 668.00 20.17 310.00 18.87 310.00 18.87
June 659.00 20.12 266.67 18.67 266.67 18.67
July 654.00 20.05 261.00 18.55 261.00 18.55
August 670.33 20.05 253.00 18.58 253.00 18.58
September 635.67 20.16 268.17 18.83 268.17 18.83
October 646.17 20.03 340.33 18.94 340.33 18.94
November 630.00 19.86 430.00 19.14 430.00 19.14
December 654.00 19.65 552.00 19.34 552.00 19.34
             
Annual Sum or Average 7794.17 20.00 4440.00 19.05 4440.00 19.05
Minimum of Months 595.00 19.65 253.00 18.55 253.00 18.55
Maximum of Months 683.00 20.19 552.00 19.34 552.00 19.34



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.73 496.83 19.28 496.83 19.28
February 597.00 19.83 418.67 19.25 418.67 19.25
March 684.00 20.04 413.67 19.25 413.67 19.25
April 645.00 20.12 353.50 19.18 353.50 19.18
May 669.00 20.02 321.83 18.97 321.83 18.97
June 660.00 19.92 280.83 18.74 280.83 18.74
July 654.00 19.80 280.00 18.59 280.00 18.59
August 684.00 19.87 279.17 18.62 279.17 18.62
September 645.00 20.05 282.50 18.93 282.50 18.93
October 654.00 20.07 331.83 19.03 331.83 19.03
November 630.00 19.92 375.50 19.09 375.50 19.09
December 654.00 19.72 495.50 19.28 495.50 19.28
             
Annual Sum or Average 7830.00 19.93 4329.83 19.06 4329.83 19.06
Minimum of Months 597.00 19.72 279.17 18.59 279.17 18.59
Maximum of Months 684.00 20.12 496.83 19.28 496.83 19.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 TREATMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 654.00 19.87 455.33 19.28 455.33 19.28
February 597.00 20.03 378.67 19.31 378.67 19.31
March 684.00 20.31 365.00 19.38 365.00 19.38
April 645.00 20.41 309.17 19.36 309.17 19.36
May 669.00 20.33 262.17 19.19 262.17 19.19
June 660.00 20.21 195.17 18.91 195.17 18.91
July 654.00 20.06 198.83 18.71 198.83 18.71
August 684.00 20.16 174.83 18.75 174.83 18.75
September 645.00 20.36 199.50 19.08 199.50 19.08
October 654.00 20.37 281.00 19.23 281.00 19.23
November 630.00 20.17 335.83 19.20 335.83 19.20
December 654.00 19.88 445.00 19.27 445.00 19.27
             
Annual Sum or Average 7830.00 20.18 3600.50 19.19 3600.50 19.19
Minimum of Months 597.00 19.87 174.83 18.71 174.83 18.71
Maximum of Months 684.00 20.41 455.33 19.38 455.33 19.38



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FLOOR 3 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 604.00 19.70 574.67 19.59 574.67 19.59
February 551.00 20.12 447.83 19.70 447.83 19.70
March 630.00 20.79 366.00 19.93 366.00 19.93
April 595.00 21.55 181.83 20.28 181.83 20.28
May 599.33 22.23 18.67 20.51 18.67 20.51
June 548.00 22.33 21.67 24.75 0.00 0.00
July 538.17 22.38 21.17 24.59 0.00 0.00
August 584.67 22.32 10.67 24.81 0.00 0.00
September 592.33 22.05 1.17 20.60 1.17 20.60
October 604.00 21.44 160.17 20.24 160.17 20.24
November 582.00 20.61 364.17 19.85 364.17 19.85
December 604.00 19.78 562.67 19.63 562.67 19.63
             
Annual Sum or Average 7032.50 21.26 2730.67 19.89 2677.17 19.79
Minimum of Months 538.17 19.70 1.17 19.59 0.00 0.00
Maximum of Months 630.00 22.38 574.67 24.81 574.67 20.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: NE STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: NW ELEVATOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: NW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: SW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 ANESTHESIA PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.97693 36.70541 -0.6665 16.14723
February 597.00000 20.14043 36.37029 -0.6019 14.08398
March 684.00000 20.05890 36.59413 -0.6229 14.42838
April 645.00000 19.73942 37.38036 -0.6758 16.10055
May 669.00000 19.62246 43.09130 -1.9526 72.07219
June 660.00000 19.63834 51.20934 -1.8821 69.11399
July 654.00000 19.61695 54.92315 -1.8420 67.42405
August 684.00000 19.71338 53.99976 -1.7914 65.07240
September 645.00000 19.69608 46.19278 -1.8491 67.70459
October 654.00000 19.79636 39.29618 -0.6133 14.59707
November 630.00000 19.98753 37.44739 -0.6129 14.42920
December 654.00000 20.06929 36.52076 -0.6386 14.89646
           
Annual Sum or Average 7830.00000 19.83542 42.56851 -1.1537 37.51051
Minimum of Months 597.00000 19.61695 36.37029 -1.9526 14.08398
Maximum of Months 684.00000 20.14043 54.92315 -0.6019 72.07219



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 CAFE PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 21.77441 39.98894 -0.2431 8.38693
February 597.00000 22.11539 39.15653 -0.1370 6.90692
March 684.00000 22.15458 40.00109 -0.1171 6.67050
April 645.00000 22.01429 40.41317 -0.1162 6.88842
May 669.00000 22.09372 45.33353 -1.1103 32.89485
June 660.00000 22.19987 52.04296 -1.0111 28.47788
July 654.00000 22.32932 54.16967 -0.9316 25.03559
August 684.00000 22.48530 53.45175 -0.8680 22.38949
September 645.00000 22.34564 47.07985 -0.9764 26.71512
October 654.00000 22.18933 41.96191 -0.0439 6.48131
November 630.00000 22.07033 40.81185 -0.1189 6.92200
December 654.00000 21.92419 39.78354 -0.2033 7.54052
           
Annual Sum or Average 7830.00000 22.14300 44.59264 -0.4949 15.56402
Minimum of Months 597.00000 21.77441 39.15653 -1.1103 6.48131
Maximum of Months 684.00000 22.48530 54.16967 -0.0439 32.89485



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 CLEAN PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 21.20927 32.59686 -0.3012 7.77625
February 597.00000 21.36928 32.26622 -0.2543 6.91655
March 684.00000 21.11137 32.79612 -0.2981 7.46182
April 645.00000 20.38195 34.40398 -0.4468 9.94443
May 669.00000 20.01462 40.58000 -1.7280 62.36886
June 660.00000 19.96301 48.71871 -1.6961 60.84030
July 654.00000 19.86762 52.68455 -1.7116 61.59625
August 684.00000 19.96844 51.69848 -1.6761 59.85430
September 645.00000 19.95299 44.00345 -1.7256 62.29511
October 654.00000 20.19120 36.78837 -0.4786 10.66806
November 630.00000 20.72688 34.31076 -0.3782 8.57477
December 654.00000 21.36335 32.36299 -0.2593 7.00529
           
Annual Sum or Average 7830.00000 20.50273 39.53349 -0.9216 30.77616
Minimum of Months 597.00000 19.86762 32.26622 -1.7280 6.91655
Maximum of Months 684.00000 21.36928 52.68455 -0.2543 62.36886



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 CLEAN WORK PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 20.83428 33.40215 -0.4110 9.47775
February 597.00000 21.00436 33.04532 -0.3605 8.34824
March 684.00000 20.76268 33.56308 -0.4024 9.07336
April 645.00000 20.09707 35.09224 -0.5400 12.07740
May 669.00000 19.78745 41.22960 -1.8424 67.68611
June 660.00000 19.74352 49.47321 -1.8072 66.09262
July 654.00000 19.66761 53.43716 -1.8138 66.45736
August 684.00000 19.76182 52.46928 -1.7797 64.82063
September 645.00000 19.73397 44.68506 -1.8351 67.43850
October 654.00000 19.94379 37.43631 -0.5634 12.73776
November 630.00000 20.43323 35.00568 -0.4732 10.43240
December 654.00000 20.97722 33.18464 -0.3700 8.56025
           
Annual Sum or Average 7830.00000 20.22240 40.26795 -1.0254 33.95672
Minimum of Months 597.00000 19.66761 33.04532 -1.8424 8.34824
Maximum of Months 684.00000 21.00436 53.43716 -0.3605 67.68611



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 DICTATION PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 604.00000 22.27456 30.37590 -0.1680 6.05394
February 551.00000 22.48691 29.93571 -0.1122 5.50113
March 630.00000 22.41754 30.19282 -0.1241 5.56602
April 595.00000 22.00852 31.33669 -0.2171 6.29832
May 617.00000 21.74387 36.77027 -1.3807 44.72427
June 608.00000 21.73072 44.01602 -1.3401 42.63227
July 604.00000 21.64096 47.62645 -1.3516 43.24251
August 630.00000 21.75164 46.64185 -1.3159 41.38706
September 595.00000 21.71988 39.82417 -1.3683 44.07099
October 604.00000 21.85407 33.53714 -0.2424 6.63636
November 582.00000 22.19227 31.45432 -0.1768 5.89703
December 604.00000 22.45383 30.06064 -0.1217 5.59132
           
Annual Sum or Average 7224.00000 22.01915 36.06354 -0.6672 21.69009
Minimum of Months 551.00000 21.64096 29.93571 -1.3807 5.50113
Maximum of Months 630.00000 22.48691 47.62645 -0.1122 44.72427



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 DRESSING ROOM PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 604.00000 19.29413 34.38529 -0.9800 26.22284
February 551.00000 19.41454 34.13778 -0.9361 24.49457
March 630.00000 19.51966 34.65173 -0.9093 23.49369
April 595.00000 19.62431 34.84262 -0.8482 21.22703
May 617.00000 20.23050 39.83462 -1.9246 71.33868
June 608.00000 20.74905 47.49250 -1.6803 60.05480
July 604.00000 21.21510 49.72235 -1.4919 50.57977
August 630.00000 21.34706 48.48985 -1.4454 48.18599
September 595.00000 20.90741 41.83999 -1.6384 58.21023
October 604.00000 20.34525 36.21180 -0.6062 13.45969
November 582.00000 19.88946 34.68132 -0.7497 17.84228
December 604.00000 19.45070 34.21343 -0.9104 23.50484
           
Annual Sum or Average 7224.00000 20.17407 39.28447 -1.1812 36.75924
Minimum of Months 551.00000 19.29413 34.13778 -1.9246 13.45969
Maximum of Months 630.00000 21.34706 49.72235 -0.6062 71.33868



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 HUMID PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 604.00000 22.49563 29.72794 -0.1078 5.61411
February 551.00000 22.70380 29.30523 -0.0529 5.24922
March 630.00000 22.65304 29.48156 -0.0598 5.25951
April 595.00000 22.33038 30.38967 -0.1328 5.54393
May 617.00000 22.10447 35.66156 -1.2489 37.93554
June 608.00000 22.08618 42.72284 -1.2102 35.98812
July 604.00000 22.02115 46.18680 -1.2146 36.22765
August 630.00000 22.10555 45.28664 -1.1862 34.80952
September 595.00000 22.08939 38.60635 -1.2345 37.19805
October 604.00000 22.20378 32.48328 -0.1519 5.70981
November 582.00000 22.47970 30.57645 -0.0995 5.35708
December 604.00000 22.67724 29.42276 -0.0606 5.29282
           
Annual Sum or Average 7224.00000 22.32610 35.06668 -0.5702 18.53407
Minimum of Months 551.00000 22.02115 29.30523 -1.2489 5.24922
Maximum of Months 630.00000 22.70380 46.18680 -0.0529 37.93554



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 IT ROOM PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 604.00000 20.82305 34.26725 -0.5398 11.96237
February 551.00000 21.15096 33.77000 -0.4630 10.05607
March 630.00000 21.20487 33.88861 -0.4458 9.69844
April 595.00000 20.93505 34.39880 -0.4943 10.74384
May 617.00000 20.96136 39.20207 -1.6713 59.76811
June 608.00000 21.17438 46.27913 -1.5560 53.89009
July 604.00000 21.29238 49.24895 -1.4963 50.77554
August 630.00000 21.38300 48.45504 -1.4715 49.47300
September 595.00000 21.09056 42.08819 -1.6096 56.65708
October 604.00000 20.95098 36.15943 -0.4764 10.44896
November 582.00000 21.13746 34.64802 -0.4531 9.88718
December 604.00000 21.17870 33.75878 -0.4575 10.01056
           
Annual Sum or Average 7224.00000 21.10784 38.92005 -0.9343 28.87184
Minimum of Months 551.00000 20.82305 33.75878 -1.6713 9.69844
Maximum of Months 630.00000 21.38300 49.24895 -0.4458 59.76811



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 LOBBY PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 20.95619 34.53664 -0.4866 11.16954
February 597.00000 21.36499 33.51703 -0.3781 8.82660
March 684.00000 21.57537 33.31545 -0.3163 7.88963
April 645.00000 21.73031 32.85373 -0.2498 7.20485
May 669.00000 22.15489 36.73211 -1.1583 34.46468
June 660.00000 22.33034 43.11880 -1.0354 28.81337
July 654.00000 22.55605 45.49338 -0.9261 24.12520
August 684.00000 22.53267 45.04285 -0.9377 24.39253
September 645.00000 22.24633 39.27137 -1.0997 31.13916
October 654.00000 21.90745 34.35777 -0.1840 6.31723
November 630.00000 21.64513 33.75002 -0.2836 7.40848
December 654.00000 21.24929 33.91747 -0.4097 9.49646
           
Annual Sum or Average 7830.00000 21.86045 37.21760 -0.6262 16.88995
Minimum of Months 597.00000 20.95619 32.85373 -1.1583 6.31723
Maximum of Months 684.00000 22.55605 45.49338 -0.1840 34.46468



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 LOCKER ROOM PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 22.02797 32.48642 -0.2574 7.07468
February 597.00000 22.29324 31.93159 -0.1835 6.03007
March 684.00000 22.33768 32.15084 -0.1623 5.85833
April 645.00000 22.25215 32.47833 -0.1614 5.85862
May 669.00000 22.33096 37.34226 -1.1609 33.88675
June 660.00000 22.44762 43.85475 -1.0604 29.21301
July 654.00000 22.51696 46.66357 -1.0149 27.19837
August 684.00000 22.56173 46.02773 -0.9953 26.33728
September 645.00000 22.46664 39.69147 -1.0822 30.11216
October 654.00000 22.42451 34.03566 -0.0913 5.47415
November 630.00000 22.45197 32.53826 -0.1134 5.57322
December 654.00000 22.30218 31.88897 -0.1795 6.10052
           
Annual Sum or Average 7830.00000 22.36872 36.83152 -0.5441 15.87091
Minimum of Months 597.00000 22.02797 31.88897 -1.1609 5.47415
Maximum of Months 684.00000 22.56173 46.66357 -0.0913 33.88675



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 LOUNGE PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 22.36507 31.75470 -0.1668 6.09947
February 597.00000 22.56036 31.42424 -0.1117 5.56514
March 684.00000 22.53675 31.70011 -0.1067 5.52618
April 645.00000 22.31320 32.39867 -0.1483 5.76422
May 669.00000 22.22484 37.64519 -1.2161 36.47774
June 660.00000 22.27198 44.31602 -1.1478 33.15998
July 654.00000 22.27315 47.35213 -1.1294 32.28351
August 684.00000 22.32114 46.72630 -1.1107 31.39579
September 645.00000 22.24358 40.31290 -1.1874 35.02771
October 654.00000 22.28407 34.41805 -0.1394 5.75471
November 630.00000 22.46507 32.62809 -0.1167 5.57975
December 654.00000 22.56008 31.42613 -0.1130 5.61501
           
Annual Sum or Average 7830.00000 22.36690 36.92079 -0.5643 17.52625
Minimum of Months 597.00000 22.22484 31.42424 -1.2161 5.52618
Maximum of Months 684.00000 22.56036 47.35213 -0.1067 36.47774



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 MRI CONTROL ROOM PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 23.00678 30.37081 0.00468 5.64469
February 597.00000 23.18280 30.10429 0.05957 5.51482
March 684.00000 23.07799 30.41440 0.05629 5.50114
April 645.00000 22.99394 30.79183 0.06444 5.55411
May 669.00000 23.13128 35.20485 -0.7996 19.52242
June 660.00000 23.23325 41.34594 -0.6913 16.04259
July 654.00000 23.39225 43.77127 -0.6121 13.86886
August 684.00000 23.34726 43.44030 -0.6212 14.04989
September 645.00000 23.24522 37.49678 -0.7288 17.05645
October 654.00000 23.15340 32.26350 0.13437 5.83236
November 630.00000 23.16214 30.92477 0.09817 5.66848
December 654.00000 23.19202 30.08213 0.05903 5.58719
           
Annual Sum or Average 7830.00000 23.17689 34.75363 -0.2528 10.05097
Minimum of Months 597.00000 22.99394 30.08213 -0.7996 5.50114
Maximum of Months 684.00000 23.39225 43.77127 0.13437 19.52242



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 MRI ROOM PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 23.91015 27.92014 0.29911 7.35693
February 597.00000 23.89709 27.91048 0.31852 7.56872
March 684.00000 23.65740 28.38893 0.28621 7.17688
April 645.00000 23.50577 28.96630 0.26366 6.92967
May 669.00000 23.50637 33.77634 -0.5908 13.34544
June 660.00000 23.50645 40.10626 -0.5324 11.94947
July 654.00000 23.58686 42.74785 -0.4904 11.08471
August 684.00000 23.53810 42.39086 -0.4960 11.17053
September 645.00000 23.52977 36.23794 -0.5611 12.57138
October 654.00000 23.52460 30.74869 0.28507 7.17070
November 630.00000 23.57690 29.27986 0.27482 7.05481
December 654.00000 23.92067 27.93119 0.31576 7.51350
           
Annual Sum or Average 7830.00000 23.63626 33.10843 -0.0576 9.26819
Minimum of Months 597.00000 23.50577 27.91048 -0.5908 6.92967
Maximum of Months 684.00000 23.92067 42.74785 0.31852 13.34544



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 NOURISHMENT PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 22.65219 31.81661 -0.0554 5.57537
February 597.00000 22.83822 31.50954 -0.0034 5.33682
March 684.00000 22.75548 31.91405 -0.0133 5.34455
April 645.00000 22.39685 32.96302 -0.0937 5.51434
May 669.00000 22.18246 38.61839 -1.1930 35.39475
June 660.00000 22.17027 45.55119 -1.1511 33.35640
July 654.00000 22.10178 48.81384 -1.1595 33.78326
August 684.00000 22.18480 48.09020 -1.1285 32.28998
September 645.00000 22.16200 41.40188 -1.1808 34.77812
October 654.00000 22.28210 35.25366 -0.1091 5.64162
November 630.00000 22.57523 33.14126 -0.0548 5.37223
December 654.00000 22.80992 31.55501 -0.0127 5.37585
           
Annual Sum or Average 7830.00000 22.42250 37.63769 -0.5200 17.48934
Minimum of Months 597.00000 22.10178 31.50954 -1.1930 5.33682
Maximum of Months 684.00000 22.83822 48.81384 -0.0034 35.39475



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 NURSE STATION PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 22.31531 32.89550 -0.1571 6.06777
February 597.00000 22.51449 32.53610 -0.1015 5.56044
March 684.00000 22.47703 32.95790 -0.1016 5.55961
April 645.00000 22.15771 33.98912 -0.1694 6.01912
May 669.00000 21.96830 39.64774 -1.2901 40.21248
June 660.00000 21.97261 46.61011 -1.2408 37.74652
July 654.00000 21.91805 49.83694 -1.2422 37.83561
August 684.00000 22.02086 49.04530 -1.2046 35.95645
September 645.00000 21.97915 42.34486 -1.2640 38.87022
October 654.00000 22.05802 36.27549 -0.1799 6.19256
November 630.00000 22.29990 34.24625 -0.1412 5.80978
December 654.00000 22.47081 32.61745 -0.1155 5.66632
           
Annual Sum or Average 7830.00000 22.17677 38.66856 -0.6076 19.49090
Minimum of Months 597.00000 21.91805 32.53610 -1.2901 5.55961
Maximum of Months 684.00000 22.51449 49.83694 -0.1015 40.21248



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 OFFICE PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 604.00000 22.00617 31.50686 -0.2538 6.84667
February 551.00000 22.30076 30.79661 -0.1756 5.83805
March 630.00000 22.34795 30.79752 -0.1550 5.65557
April 595.00000 22.21550 31.24817 -0.1726 5.78453
May 617.00000 22.17256 36.13906 -1.2332 37.14915
June 608.00000 22.22308 42.85428 -1.1658 33.81864
July 604.00000 22.24460 45.97385 -1.1377 32.46545
August 630.00000 22.29957 45.21021 -1.1192 31.57853
September 595.00000 22.22862 38.81129 -1.1908 34.99763
October 604.00000 22.20249 33.10964 -0.1598 5.73963
November 582.00000 22.27402 31.66763 -0.1650 5.74750
December 604.00000 22.26042 30.95176 -0.1873 5.98097
           
Annual Sum or Average 7224.00000 22.23125 35.82702 -0.5989 17.80055
Minimum of Months 551.00000 22.00617 30.79661 -1.2332 5.65557
Maximum of Months 630.00000 22.34795 45.97385 -0.1550 37.14915



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 OPERATING ROOM 1 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.54654 35.88118 -0.7634 18.43535
February 597.00000 19.62805 35.70410 -0.7141 16.69264
March 684.00000 19.38451 36.29207 -0.7491 17.79961
April 645.00000 18.93311 37.54247 -0.7932 19.34436
May 669.00000 18.91941 43.58776 -2.0402 77.06924
June 660.00000 18.99633 51.80079 -1.9295 72.32097
July 654.00000 19.10141 55.26870 -1.8482 68.57924
August 684.00000 19.23117 54.14311 -1.8022 66.44511
September 645.00000 19.08438 46.57598 -1.9209 72.00624
October 654.00000 19.08031 39.48081 -0.7101 16.62062
November 630.00000 19.26654 37.40869 -0.7322 17.32867
December 654.00000 19.64252 35.75867 -0.7268 17.18278
           
Annual Sum or Average 7830.00000 19.23186 42.54971 -1.2349 40.32353
Minimum of Months 597.00000 18.91941 35.70410 -2.0402 16.62062
Maximum of Months 684.00000 19.64252 55.26870 -0.7101 77.06924



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 OPERATING ROOM 2 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.77572 35.42295 -0.6798 16.04989
February 597.00000 19.80292 35.38122 -0.6489 15.14020
March 684.00000 19.45799 36.17354 -0.6964 16.57863
April 645.00000 18.83040 37.83455 -0.7783 19.26836
May 669.00000 18.34649 45.14825 -2.1637 79.51159
June 660.00000 18.26623 54.14546 -2.1115 77.28375
July 654.00000 18.46024 57.51401 -2.0172 73.83955
August 684.00000 18.73412 55.80371 -1.9427 71.61567
September 645.00000 18.26346 49.03450 -2.1547 79.34327
October 654.00000 18.55988 40.79586 -0.8106 20.44716
November 630.00000 19.15858 37.72692 -0.7339 17.69228
December 654.00000 19.88020 35.28241 -0.6410 14.91721
           
Annual Sum or Average 7830.00000 18.95490 43.46228 -1.2901 42.17507
Minimum of Months 597.00000 18.26346 35.28241 -2.1637 14.91721
Maximum of Months 684.00000 19.88020 57.51401 -0.6410 79.51159



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 OPERATING ROOM 3 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.03805 36.44565 -0.7229 16.99354
February 597.00000 19.03190 36.43191 -0.7073 16.22895
March 684.00000 18.60397 37.37040 -0.7835 18.65297
April 645.00000 17.78607 39.52812 -0.9482 24.57381
May 669.00000 17.33834 46.96016 -2.4437 90.64093
June 660.00000 17.21394 56.70417 -2.4264 90.17389
July 654.00000 17.13722 61.37567 -2.4357 90.41442
August 684.00000 17.21337 60.21605 -2.4058 89.67995
September 645.00000 17.20747 51.19702 -2.4600 90.98155
October 654.00000 17.57840 42.35199 -0.9810 25.90812
November 630.00000 18.22564 39.14901 -0.8611 21.22050
December 654.00000 19.09345 36.40107 -0.6992 15.97349
           
Annual Sum or Average 7830.00000 17.94593 45.46632 -1.5000 49.74195
Minimum of Months 597.00000 17.13722 36.40107 -2.4600 15.97349
Maximum of Months 684.00000 19.09345 61.37567 -0.6992 90.98155



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 PACU PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 20.76159 35.14042 -0.4251 9.87673
February 597.00000 20.89011 34.89356 -0.3843 8.85112
March 684.00000 20.64206 35.38938 -0.4281 9.66690
April 645.00000 19.97360 36.86314 -0.5673 12.90667
May 669.00000 19.67904 42.86065 -1.8834 69.39187
June 660.00000 19.64409 51.01285 -1.8465 67.78687
July 654.00000 19.57140 54.88015 -1.8543 68.23676
August 684.00000 19.65493 54.00581 -1.8221 66.69139
September 645.00000 19.63282 46.23817 -1.8731 69.04678
October 654.00000 19.82926 39.15263 -0.5893 13.56446
November 630.00000 20.31157 36.75005 -0.5001 11.18206
December 654.00000 20.86464 34.94636 -0.3943 9.10074
           
Annual Sum or Average 7830.00000 20.11481 41.94216 -1.0562 35.05615
Minimum of Months 597.00000 19.57140 34.89356 -1.8834 8.85112
Maximum of Months 684.00000 20.89011 54.88015 -0.3843 69.39187



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 1 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.51938 36.39650 -0.8079 19.30171
February 597.00000 19.74992 35.90518 -0.7309 16.65995
March 684.00000 19.69654 36.04989 -0.7220 16.37174
April 645.00000 19.39345 36.90011 -0.7485 17.45231
May 669.00000 19.34491 42.59243 -2.0171 75.83341
June 660.00000 19.39807 50.75212 -1.9362 72.26734
July 654.00000 19.37659 54.60878 -1.9072 71.05323
August 684.00000 19.45391 53.69334 -1.8837 69.92156
September 645.00000 19.34144 45.99246 -1.9799 74.38216
October 654.00000 19.38068 39.02848 -0.7203 16.68681
November 630.00000 19.64799 36.93367 -0.7020 15.91276
December 654.00000 19.72526 35.99904 -0.7410 17.00869
           
Annual Sum or Average 7830.00000 19.50058 42.16218 -1.2490 40.58581
Minimum of Months 597.00000 19.34144 35.90518 -2.0171 15.91276
Maximum of Months 684.00000 19.74992 54.60878 -0.7020 75.83341



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 2 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 20.35717 34.15061 -0.4912 10.71920
February 597.00000 20.55628 33.73002 -0.4343 9.43131
March 684.00000 20.43315 34.04737 -0.4512 9.94317
April 645.00000 19.80635 35.57248 -0.5766 12.98191
May 669.00000 19.52320 41.74204 -1.8831 69.71781
June 660.00000 19.49617 50.06474 -1.8430 67.93796
July 654.00000 19.41858 54.10577 -1.8495 68.35252
August 684.00000 19.50555 53.14317 -1.8203 66.90088
September 645.00000 19.47073 45.25072 -1.8762 69.50682
October 654.00000 19.66616 37.92600 -0.5966 13.55629
November 630.00000 20.15857 35.42408 -0.5089 11.23345
December 654.00000 20.52422 33.88722 -0.4444 9.66562
           
Annual Sum or Average 7830.00000 19.90423 40.85274 -1.0732 35.35817
Minimum of Months 597.00000 19.41858 33.73002 -1.8831 9.43131
Maximum of Months 684.00000 20.55628 54.10577 -0.4343 69.71781



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 PROCEDURE ROOM PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.44019 35.40888 -0.7960 19.39577
February 597.00000 19.54023 35.17824 -0.7520 17.80889
March 684.00000 19.53703 35.21927 -0.7405 17.35999
April 645.00000 19.29931 35.98324 -0.7575 17.95982
May 669.00000 19.23555 41.80015 -2.0137 75.55453
June 660.00000 19.26822 50.10404 -1.9243 71.70630
July 654.00000 19.23556 54.10648 -1.8976 70.61136
August 684.00000 19.30691 53.13649 -1.8708 69.31677
September 645.00000 19.23125 45.24613 -1.9585 73.33311
October 654.00000 19.29142 38.10428 -0.7040 16.38988
November 630.00000 19.48068 36.17848 -0.7042 16.35801
December 654.00000 19.55242 35.26886 -0.7441 17.61760
           
Annual Sum or Average 7830.00000 19.36695 41.40283 -1.2460 40.62401
Minimum of Months 597.00000 19.23125 35.17824 -2.0137 16.35801
Maximum of Months 684.00000 19.55242 54.10648 -0.7040 75.55453



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 RECEPTION PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 22.05466 35.65839 -0.1966 6.64221
February 597.00000 22.34501 34.87645 -0.1153 5.72472
March 684.00000 22.38058 35.39792 -0.0982 5.61382
April 645.00000 22.27259 35.75475 -0.1061 5.68686
May 669.00000 22.31098 40.74004 -1.1146 31.88345
June 660.00000 22.39379 47.29943 -1.0320 28.11277
July 654.00000 22.48439 49.77920 -0.9766 25.69573
August 684.00000 22.57757 49.10584 -0.9395 24.13978
September 645.00000 22.48839 42.71847 -1.0219 27.54830
October 654.00000 22.40323 37.34912 -0.0509 5.50148
November 630.00000 22.36941 36.06390 -0.0874 5.63388
December 654.00000 22.26393 35.11860 -0.1407 5.96789
           
Annual Sum or Average 7830.00000 22.36293 40.06387 -0.4956 14.97951
Minimum of Months 597.00000 22.05466 34.87645 -1.1146 5.50148
Maximum of Months 684.00000 22.57757 49.77920 -0.0509 31.88345



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 RECOVERY ROOM PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.91255 35.43923 -0.6994 16.99470
February 597.00000 20.07588 35.08833 -0.6305 14.80278
March 684.00000 20.02989 35.30569 -0.6398 14.86464
April 645.00000 19.72863 36.13842 -0.6815 16.25867
May 669.00000 19.60937 42.03185 -1.9441 71.69196
June 660.00000 19.62630 50.29757 -1.8653 68.35530
July 654.00000 19.60396 54.12257 -1.8205 66.43269
August 684.00000 19.70596 53.13646 -1.7662 63.89743
September 645.00000 19.68746 45.19909 -1.8287 66.79976
October 654.00000 19.78852 38.11174 -0.6076 14.44621
November 630.00000 19.97252 36.22898 -0.6183 14.55169
December 654.00000 20.01945 35.28688 -0.6648 15.60117
           
Annual Sum or Average 7830.00000 19.81110 41.45861 -1.1549 37.38693
Minimum of Months 597.00000 19.60396 35.08833 -1.9441 14.44621
Maximum of Months 684.00000 20.07588 54.12257 -0.6076 71.69196



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 SCHEDULING PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 604.00000 20.88559 33.35437 -0.5225 11.47356
February 551.00000 21.29374 32.52766 -0.4249 9.24870
March 630.00000 21.33197 32.89176 -0.4141 9.01787
April 595.00000 21.28638 33.04057 -0.4133 9.07612
May 617.00000 21.48786 37.67390 -1.4946 50.68598
June 608.00000 21.66829 44.78935 -1.3822 44.82886
July 604.00000 21.83372 47.56186 -1.2998 40.54488
August 630.00000 21.99334 46.33064 -1.2451 37.74876
September 595.00000 21.88496 39.66655 -1.3285 41.98545
October 604.00000 21.73960 34.01541 -0.2833 7.09569
November 582.00000 21.61036 32.73787 -0.3339 7.75446
December 604.00000 21.26095 32.70328 -0.4311 9.44338
           
Annual Sum or Average 7224.00000 21.52535 37.34707 -0.8036 23.44846
Minimum of Months 551.00000 20.88559 32.52766 -1.4946 7.09569
Maximum of Months 630.00000 21.99334 47.56186 -0.2833 50.68598



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 SOIL PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 20.91993 33.14425 -0.3833 8.99618
February 597.00000 21.08228 32.80341 -0.3357 7.96441
March 684.00000 20.83064 33.33496 -0.3802 8.70087
April 645.00000 20.13718 34.91799 -0.5259 11.74423
May 669.00000 19.80421 41.09694 -1.8325 67.23163
June 660.00000 19.75368 49.35059 -1.8010 65.80108
July 654.00000 19.66603 53.35416 -1.8136 66.44200
August 684.00000 19.76023 52.38010 -1.7801 64.82972
September 645.00000 19.74241 44.57287 -1.8300 67.19559
October 654.00000 19.96970 37.28636 -0.5538 12.50440
November 630.00000 20.48382 34.80839 -0.4557 10.06820
December 654.00000 21.06232 32.93039 -0.3433 8.13290
           
Annual Sum or Average 7830.00000 20.26080 40.09841 -1.0119 33.65886
Minimum of Months 597.00000 19.66603 32.80341 -1.8325 7.96441
Maximum of Months 684.00000 21.08228 53.35416 -0.3357 67.23163



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 SOIL HOLD PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.73426 35.66686 -0.7256 16.97145
February 597.00000 19.90376 35.28465 -0.6762 15.24918
March 684.00000 19.71096 35.72691 -0.7020 15.96702
April 645.00000 19.09199 37.24179 -0.8108 19.56251
May 669.00000 18.90344 43.44308 -2.1646 81.77117
June 660.00000 19.00862 51.68266 -2.0750 78.45174
July 654.00000 19.06921 55.35509 -2.0294 76.75579
August 684.00000 19.17069 54.34181 -2.0011 75.57038
September 645.00000 18.92708 46.87365 -2.1296 80.68001
October 654.00000 19.01079 39.56756 -0.8085 19.50296
November 630.00000 19.48392 37.04553 -0.7357 16.97864
December 654.00000 19.95953 35.26941 -0.6661 14.99850
           
Annual Sum or Average 7830.00000 19.32706 42.38963 -1.3022 43.09233
Minimum of Months 597.00000 18.90344 35.26941 -2.1646 14.99850
Maximum of Months 684.00000 19.95953 55.35509 -0.6661 81.77117



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 SOIL WORK PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 20.64226 33.79939 -0.4707 10.57360
February 597.00000 20.81085 33.44367 -0.4205 9.34935
March 684.00000 20.60102 33.91181 -0.4570 10.09688
April 645.00000 19.97004 35.39160 -0.5883 13.29774
May 669.00000 19.69075 41.49720 -1.9024 70.36904
June 660.00000 19.65628 49.76735 -1.8634 68.66253
July 654.00000 19.58575 53.73859 -1.8673 68.93038
August 684.00000 19.67788 52.77610 -1.8327 67.28822
September 645.00000 19.64600 44.95082 -1.8892 69.89763
October 654.00000 19.83241 37.71885 -0.6077 13.90136
November 630.00000 20.29345 35.32751 -0.5245 11.59915
December 654.00000 20.76622 33.61869 -0.4344 9.68458
           
Annual Sum or Average 7830.00000 20.09182 40.59390 -1.0803 35.67004
Minimum of Months 597.00000 19.58575 33.44367 -1.9024 9.34935
Maximum of Months 684.00000 20.81085 53.73859 -0.4205 70.36904



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 1 STEP DOWN PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.73747 36.64028 -0.8006 20.24162
February 597.00000 19.89138 36.30229 -0.7319 17.92749
March 684.00000 19.91635 36.44770 -0.7239 17.48807
April 645.00000 19.75824 36.92820 -0.7147 17.40061
May 669.00000 19.73161 42.59858 -1.9292 70.82352
June 660.00000 19.78447 50.74180 -1.8301 66.54258
July 654.00000 19.85923 54.16429 -1.7401 62.51439
August 684.00000 20.03072 53.02555 -1.6708 59.32260
September 645.00000 19.89724 45.50566 -1.7794 64.45408
October 654.00000 19.88838 38.77306 -0.6052 14.54810
November 630.00000 19.94580 37.15139 -0.6557 15.70904
December 654.00000 19.84473 36.46205 -0.7572 18.48239
           
Annual Sum or Average 7830.00000 19.85728 42.14883 -1.1683 37.41476
Minimum of Months 597.00000 19.73161 36.30229 -1.9292 14.54810
Maximum of Months 684.00000 20.03072 54.16429 -0.6052 70.82352



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 CONFERENCE PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 559.00000 19.91224 15.76962 -0.8610 23.21616
February 508.00000 20.22924 16.70576 -0.7447 19.57078
March 583.00000 20.61280 20.42553 -0.6156 15.58972
April 545.00000 20.87704 24.17778 -0.5007 12.51406
May 571.00000 21.14256 38.65485 -1.4943 50.77500
June 562.00000 21.24266 51.75200 -1.3565 44.13521
July 554.00000 21.18970 55.16127 -1.3391 43.33589
August 583.00000 21.33149 56.42710 -1.2950 41.09038
September 545.00000 21.20713 47.12034 -1.4292 47.68804
October 559.00000 20.89459 34.93973 -0.4470 11.60391
November 543.00000 20.41860 24.95041 -0.6491 16.72022
December 554.00000 19.92213 17.24620 -0.8518 22.70924
           
Annual Sum or Average 6666.00000 20.75471 33.80048 -0.9686 29.21176
Minimum of Months 508.00000 19.91224 15.76962 -1.4943 11.60391
Maximum of Months 583.00000 21.33149 56.42710 -0.4470 50.77500



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 DICTATION PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 604.00000 21.52643 11.10714 -0.4897 10.82921
February 551.00000 21.78978 12.24660 -0.4163 9.15944
March 630.00000 21.95653 15.82252 -0.3519 8.05126
April 595.00000 21.95174 20.13308 -0.3256 7.62636
May 617.00000 21.88074 34.27794 -1.3836 44.84831
June 608.00000 21.86932 46.69837 -1.3061 40.86698
July 604.00000 21.77546 50.67198 -1.3135 41.29529
August 630.00000 21.90794 51.43213 -1.2623 38.65093
September 595.00000 21.93499 42.48913 -1.3149 41.29581
October 604.00000 21.87786 30.39776 -0.2823 7.30855
November 582.00000 21.77326 20.04289 -0.3736 8.65717
December 604.00000 21.63849 12.26362 -0.4551 10.02830
           
Annual Sum or Average 7224.00000 21.82456 29.16219 -0.7783 22.57608
Minimum of Months 551.00000 21.52643 11.10714 -1.3836 7.30855
Maximum of Months 630.00000 21.95653 51.43213 -0.2823 44.84831



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 1 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.59051 12.32699 -0.9880 26.98467
February 597.00000 19.73415 13.88313 -0.8937 23.53769
March 684.00000 19.95379 18.00862 -0.7822 19.67893
April 645.00000 20.25425 22.53776 -0.6331 15.24778
May 669.00000 20.49661 37.49814 -1.6491 58.35087
June 660.00000 20.48885 51.20722 -1.5471 53.49803
July 654.00000 20.51008 55.13286 -1.4978 51.06121
August 684.00000 20.52439 56.29272 -1.4987 51.15854
September 645.00000 20.40779 46.78363 -1.6449 58.33830
October 654.00000 20.11310 34.01256 -0.6127 14.65039
November 630.00000 19.79415 22.81523 -0.7983 20.18704
December 654.00000 19.57973 13.86907 -0.9713 26.25490
           
Annual Sum or Average 7830.00000 20.12586 32.24937 -1.1305 35.09900
Minimum of Months 597.00000 19.57973 12.32699 -1.6491 14.65039
Maximum of Months 684.00000 20.52439 56.29272 -0.6127 58.35087



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 2 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.76083 11.72631 -0.8138 20.30630
February 597.00000 19.88672 13.30769 -0.7486 18.11593
March 684.00000 20.02434 17.44907 -0.6811 15.93700
April 645.00000 20.02749 22.35225 -0.6368 14.57324
May 669.00000 19.91580 38.32887 -1.8104 66.20905
June 660.00000 19.84363 52.53150 -1.7420 62.99657
July 654.00000 19.75024 56.97558 -1.7412 62.90559
August 684.00000 19.84140 57.92675 -1.7014 61.03963
September 645.00000 19.98047 47.45719 -1.7382 62.93339
October 654.00000 19.99253 33.81735 -0.5867 13.49104
November 630.00000 19.90998 22.19712 -0.6927 16.57387
December 654.00000 19.74712 13.26158 -0.8046 19.93188
           
Annual Sum or Average 7830.00000 19.89009 32.50913 -1.1477 36.53273
Minimum of Months 597.00000 19.74712 11.72631 -1.8104 13.49104
Maximum of Months 684.00000 20.02749 57.92675 -0.5867 66.20905



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 3 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.75906 11.73008 -0.8084 20.19697
February 597.00000 19.87752 13.31645 -0.7458 18.12818
March 684.00000 19.99089 17.48632 -0.6878 16.22909
April 645.00000 19.95674 22.44562 -0.6575 15.26260
May 669.00000 19.81980 38.54721 -1.8564 68.16943
June 660.00000 19.75950 52.80144 -1.7858 64.98357
July 654.00000 19.65639 57.31918 -1.7919 65.20944
August 684.00000 19.74732 58.27123 -1.7498 63.28952
September 645.00000 19.89072 47.71997 -1.7791 64.81164
October 654.00000 19.92461 33.96492 -0.6066 14.11146
November 630.00000 19.88065 22.24284 -0.6995 16.85670
December 654.00000 19.73772 13.27127 -0.8025 19.90789
           
Annual Sum or Average 7830.00000 19.83293 32.65972 -1.1708 37.55809
Minimum of Months 597.00000 19.65639 11.73008 -1.8564 14.11146
Maximum of Months 684.00000 19.99089 58.27123 -0.6066 68.16943



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 4 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.85229 11.97162 -0.8389 21.84319
February 597.00000 20.15464 13.36090 -0.7283 18.51379
March 684.00000 20.34160 17.42450 -0.6539 15.99577
April 645.00000 20.44767 22.12599 -0.5857 13.94967
May 669.00000 20.37886 37.60581 -1.7234 61.86321
June 660.00000 20.33377 51.45899 -1.6424 58.09317
July 654.00000 20.28248 55.64379 -1.6260 57.17668
August 684.00000 20.43988 56.35709 -1.5682 54.54056
September 645.00000 20.53516 46.26890 -1.6186 57.03485
October 654.00000 20.39018 33.24853 -0.5394 13.01852
November 630.00000 20.12345 22.21539 -0.6904 17.14871
December 654.00000 19.82314 13.54047 -0.8404 21.61143
           
Annual Sum or Average 7830.00000 20.26053 31.99172 -1.0936 34.47551
Minimum of Months 597.00000 19.82314 11.97162 -1.7234 13.01852
Maximum of Months 684.00000 20.53516 56.35709 -0.5394 61.86321



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 5 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.63731 12.00818 -0.9010 23.46261
February 597.00000 19.71240 13.63537 -0.8390 21.24795
March 684.00000 19.92734 17.74266 -0.7334 17.80447
April 645.00000 20.21411 22.30670 -0.5962 13.98049
May 669.00000 20.35082 37.59255 -1.6367 57.92036
June 660.00000 20.43165 51.04484 -1.4955 50.97652
July 654.00000 20.39386 55.11289 -1.4680 49.64028
August 684.00000 20.34036 56.49348 -1.5002 51.16918
September 645.00000 20.31081 46.71737 -1.6189 57.14434
October 654.00000 20.09300 33.80233 -0.5729 13.07120
November 630.00000 19.84660 22.44063 -0.7310 17.75777
December 654.00000 19.64637 13.52820 -0.8778 22.62356
           
Annual Sum or Average 7830.00000 20.07955 32.09021 -1.0853 33.26600
Minimum of Months 597.00000 19.63731 12.00818 -1.6367 13.07120
Maximum of Months 684.00000 20.43165 56.49348 -0.5729 57.92036



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 6 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.61597 11.90496 -0.9332 24.62286
February 597.00000 19.66855 13.55588 -0.8822 22.70092
March 684.00000 19.79635 17.75780 -0.8020 19.87471
April 645.00000 19.86935 22.60558 -0.7238 17.17992
May 669.00000 19.92103 38.35909 -1.8469 67.81407
June 660.00000 19.93704 52.34887 -1.7307 62.46567
July 654.00000 19.85635 56.73669 -1.7232 62.05267
August 684.00000 19.90539 57.81873 -1.7121 61.58876
September 645.00000 19.93683 47.63331 -1.8033 66.04751
October 654.00000 19.87089 34.15116 -0.6594 15.42247
November 630.00000 19.76744 22.43056 -0.7788 19.26941
December 654.00000 19.62587 13.43206 -0.9056 23.62566
           
Annual Sum or Average 7830.00000 19.81583 32.62402 -1.2140 38.81394
Minimum of Months 597.00000 19.61597 11.90496 -1.8469 15.42247
Maximum of Months 684.00000 19.93704 57.81873 -0.6594 67.81407



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 7 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.72221 11.75065 -0.8343 20.89425
February 597.00000 19.79386 13.38688 -0.7864 19.20846
March 684.00000 19.92150 17.55336 -0.7153 16.91795
April 645.00000 19.92250 22.46774 -0.6701 15.47488
May 669.00000 19.84041 38.50087 -1.8392 67.52070
June 660.00000 19.79163 52.69366 -1.7564 63.68213
July 654.00000 19.67616 57.23599 -1.7690 64.23151
August 684.00000 19.74944 58.25254 -1.7422 62.97334
September 645.00000 19.87165 47.76409 -1.7900 65.38294
October 654.00000 19.89930 34.02625 -0.6156 14.18702
November 630.00000 19.85505 22.25216 -0.7072 16.89092
December 654.00000 19.74586 13.25453 -0.8059 19.94940
           
Annual Sum or Average 7830.00000 19.81583 32.66097 -1.1756 37.56152
Minimum of Months 597.00000 19.67616 11.75065 -1.8392 14.18702
Maximum of Months 684.00000 19.92250 58.25254 -0.6156 67.52070



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 8 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.65634 11.88357 -0.9001 23.34724
February 597.00000 19.73685 13.50864 -0.8405 21.15703
March 684.00000 19.91693 17.63554 -0.7480 18.01677
April 645.00000 20.03172 22.40364 -0.6600 15.16321
May 669.00000 20.08229 38.02172 -1.7604 63.89194
June 660.00000 20.08252 51.90565 -1.6522 58.66688
July 654.00000 19.97068 56.35203 -1.6589 58.93678
August 684.00000 20.02555 57.40538 -1.6449 58.29819
September 645.00000 20.09865 47.18385 -1.7190 62.01161
October 654.00000 20.03505 33.82750 -0.5958 13.59220
November 630.00000 19.88631 22.27502 -0.7239 17.45893
December 654.00000 19.68761 13.38073 -0.8650 22.10058
           
Annual Sum or Average 7830.00000 19.93617 32.37604 -1.1528 36.29984
Minimum of Months 597.00000 19.65634 11.88357 -1.7604 13.59220
Maximum of Months 684.00000 20.09865 57.40538 -0.5958 63.89194



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 EXAM 9 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.75721 11.72132 -0.8331 20.82400
February 597.00000 19.85137 13.33877 -0.7786 18.90249
March 684.00000 20.00500 17.46044 -0.6994 16.37192
April 645.00000 20.05571 22.28881 -0.6379 14.44465
May 669.00000 20.01309 38.10061 -1.7762 64.72097
June 660.00000 19.97336 52.10307 -1.6888 60.49622
July 654.00000 19.85878 56.57972 -1.6973 60.84723
August 684.00000 19.93758 57.56611 -1.6697 59.53460
September 645.00000 20.05462 47.22057 -1.7200 62.08194
October 654.00000 20.05267 33.70641 -0.5749 13.00226
November 630.00000 19.95956 22.10798 -0.6821 16.07514
December 654.00000 19.79573 13.20631 -0.7997 19.70267
           
Annual Sum or Average 7830.00000 19.94362 32.34612 -1.1357 35.85181
Minimum of Months 597.00000 19.75721 11.72132 -1.7762 13.00226
Maximum of Months 684.00000 20.05571 57.56611 -0.5749 64.72097



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 LOUNGE PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 21.87287 11.92563 -0.4131 9.27649
February 597.00000 22.06512 13.01785 -0.3522 8.06811
March 684.00000 22.20809 16.56014 -0.2886 7.16424
April 645.00000 22.25031 20.70195 -0.2487 6.63680
May 669.00000 22.20839 34.87841 -1.2594 38.59691
June 660.00000 22.19390 46.93073 -1.1800 34.66622
July 654.00000 22.13801 50.71370 -1.1752 34.49409
August 684.00000 22.22563 51.49325 -1.1359 32.53655
September 645.00000 22.25560 42.54193 -1.1954 35.39637
October 654.00000 22.20815 30.84633 -0.1977 6.33790
November 630.00000 22.10009 20.69603 -0.2941 7.45190
December 654.00000 21.95615 13.00217 -0.3824 8.66790
           
Annual Sum or Average 7830.00000 22.14136 29.64265 -0.6821 19.27444
Minimum of Months 597.00000 21.87287 11.92563 -1.2594 6.33790
Maximum of Months 684.00000 22.25560 51.49325 -0.1977 38.59691



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 NURSE STATION 1 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 21.68453 12.86723 -0.4283 9.80358
February 597.00000 21.89763 13.83585 -0.3620 8.37091
March 684.00000 22.07450 17.31283 -0.2891 7.28128
April 645.00000 22.13228 21.45101 -0.2435 6.63528
May 669.00000 22.13460 35.61219 -1.2329 37.34781
June 660.00000 22.13818 47.74799 -1.1439 33.00504
July 654.00000 22.07449 51.54287 -1.1413 32.93505
August 684.00000 22.14822 52.39554 -1.1086 31.33644
September 645.00000 22.15328 43.39323 -1.1809 34.76227
October 654.00000 22.09600 31.63677 -0.1908 6.35561
November 630.00000 21.98522 21.44895 -0.2887 7.51736
December 654.00000 21.80318 13.80341 -0.3876 8.99283
           
Annual Sum or Average 7830.00000 22.02858 30.45443 -0.6714 18.85150
Minimum of Months 597.00000 21.68453 12.86723 -1.2329 6.35561
Maximum of Months 684.00000 22.15328 52.39554 -0.1908 37.34781



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 NURSE STATION 2 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 21.69423 12.85532 -0.4261 9.74030
February 597.00000 21.92127 13.79847 -0.3557 8.26309
March 684.00000 22.12248 17.23009 -0.2754 7.11104
April 645.00000 22.22338 21.27134 -0.2167 6.33489
May 669.00000 22.25227 35.27173 -1.1821 34.87777
June 660.00000 22.26665 47.25883 -1.0882 30.40185
July 654.00000 22.20912 51.01779 -1.0841 30.25702
August 684.00000 22.26647 51.91007 -1.0568 28.97745
September 645.00000 22.28618 42.94655 -1.1245 32.09868
October 654.00000 22.22003 31.32473 -0.1540 6.02404
November 630.00000 22.08032 21.25499 -0.2610 7.16293
December 654.00000 21.84421 13.73844 -0.3765 8.77616
           
Annual Sum or Average 7830.00000 22.11773 30.18808 -0.6382 17.64443
Minimum of Months 597.00000 21.69423 12.85532 -1.1821 6.02404
Maximum of Months 684.00000 22.28618 51.91007 -0.1540 34.87777



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 OFFICE PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 604.00000 19.81373 12.24338 -0.9165 23.83937
February 551.00000 20.18549 13.56324 -0.8012 19.67453
March 630.00000 20.79017 17.08805 -0.6249 14.43905
April 595.00000 21.43225 20.61081 -0.4240 9.84296
May 617.00000 22.03135 33.73719 -1.2801 39.82376
June 608.00000 22.25690 45.59163 -1.1032 31.27819
July 604.00000 22.31837 49.05856 -1.0517 28.94893
August 630.00000 22.28416 50.27553 -1.0759 29.82695
September 595.00000 21.92119 42.42577 -1.2843 39.85594
October 604.00000 21.32931 31.49839 -0.4053 9.45823
November 582.00000 20.63535 21.50125 -0.6448 15.33622
December 604.00000 19.91474 13.60484 -0.8781 22.40439
           
Annual Sum or Average 7224.00000 21.25537 29.44867 -0.8761 23.80154
Minimum of Months 551.00000 19.81373 12.24338 -1.2843 9.45823
Maximum of Months 630.00000 22.31837 50.27553 -0.4053 39.85594



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 RECEPTION PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 20.55244 15.45288 -0.6852 16.90635
February 597.00000 20.95632 16.07029 -0.5616 13.42330
March 684.00000 21.33097 19.53990 -0.4404 10.53148
April 645.00000 21.62437 23.25862 -0.3228 8.30748
May 669.00000 21.92054 36.99885 -1.2288 37.61327
June 660.00000 21.96867 49.37815 -1.1147 32.12625
July 654.00000 22.02122 52.74191 -1.0611 29.65300
August 684.00000 22.06922 53.70542 -1.0418 28.62701
September 645.00000 21.95448 44.84495 -1.1710 34.54149
October 654.00000 21.63167 33.61514 -0.2626 7.69583
November 630.00000 21.17100 23.93348 -0.4577 11.28979
December 654.00000 20.65215 16.61290 -0.6521 15.82453
           
Annual Sum or Average 7830.00000 21.49472 32.37407 -0.7534 20.65734
Minimum of Months 597.00000 20.55244 15.45288 -1.2288 7.69583
Maximum of Months 684.00000 22.06922 53.70542 -0.2626 37.61327



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 SCHEDULING 1 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 604.00000 21.85767 10.71180 -0.4012 8.94993
February 551.00000 22.09026 11.88023 -0.3320 7.63322
March 630.00000 22.25444 15.37850 -0.2645 6.74931
April 595.00000 22.29526 19.51497 -0.2260 6.28422
May 617.00000 22.26894 33.36087 -1.2220 36.64744
June 608.00000 22.26068 45.34923 -1.1420 32.73123
July 604.00000 22.21269 49.11044 -1.1346 32.42721
August 630.00000 22.28335 50.00053 -1.1018 30.83183
September 595.00000 22.30088 41.32525 -1.1623 33.70151
October 604.00000 22.25003 29.56849 -0.1756 6.01487
November 582.00000 22.14421 19.42461 -0.2701 6.98316
December 604.00000 21.99512 11.82202 -0.3574 8.15079
           
Annual Sum or Average 7224.00000 22.18579 28.31234 -0.6540 18.24441
Minimum of Months 551.00000 21.85767 10.71180 -1.2220 6.01487
Maximum of Months 630.00000 22.30088 50.00053 -0.1756 36.64744



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 SCHEDULING 2 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 604.00000 21.73562 10.84330 -0.4338 9.55163
February 551.00000 22.03076 11.95165 -0.3484 7.89662
March 630.00000 22.22562 15.42341 -0.2725 6.86367
April 595.00000 22.31378 19.49515 -0.2203 6.24617
May 617.00000 22.32698 33.22649 -1.1967 35.44212
June 608.00000 22.31887 45.16318 -1.1158 31.53654
July 604.00000 22.28626 48.87067 -1.1025 30.94406
August 630.00000 22.34632 49.78477 -1.0736 29.56103
September 595.00000 22.35683 41.16885 -1.1382 32.56024
October 604.00000 22.26745 29.53056 -0.1700 6.00098
November 582.00000 22.10680 19.48545 -0.2799 7.15285
December 604.00000 21.88082 11.96381 -0.3886 8.66343
           
Annual Sum or Average 7224.00000 22.18505 28.26577 -0.6497 17.84469
Minimum of Months 551.00000 21.73562 10.84330 -1.1967 6.00098
Maximum of Months 630.00000 22.35683 49.78477 -0.1700 35.44212



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 WORK PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 604.00000 21.03734 11.52900 -0.5971 13.47316
February 551.00000 21.40004 12.67538 -0.4974 10.89956
March 630.00000 21.73566 16.10202 -0.3890 8.79935
April 595.00000 22.01311 19.98986 -0.2858 7.09291
May 617.00000 22.28074 33.30673 -1.1901 35.26829
June 608.00000 22.39420 45.04437 -1.0582 28.99407
July 604.00000 22.43314 48.55273 -1.0169 27.14710
August 630.00000 22.43730 49.59570 -1.0101 26.80768
September 595.00000 22.32748 41.27624 -1.1256 32.01413
October 604.00000 22.07623 29.94555 -0.2064 6.41983
November 582.00000 21.73540 20.03257 -0.3626 8.60820
December 604.00000 21.25756 12.58116 -0.5323 11.93203
           
Annual Sum or Average 7224.00000 21.93324 28.57125 -0.6928 18.23434
Minimum of Months 551.00000 21.03734 11.52900 -1.1901 6.41983
Maximum of Months 630.00000 22.43730 49.59570 -0.2064 35.26829



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 2 X-RAY PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 23.43448 9.71503 0.05114 5.64058
February 597.00000 23.62697 10.93096 0.11534 5.75457
March 684.00000 23.74036 14.27872 0.17711 6.07599
April 645.00000 23.69422 18.20113 0.19367 6.14441
May 669.00000 23.42730 31.63437 -0.6916 15.85070
June 660.00000 23.23458 43.21472 -0.6596 14.93777
July 654.00000 23.17347 46.79517 -0.6648 15.11078
August 684.00000 23.21883 47.61791 -0.6315 14.12189
September 645.00000 23.51798 38.61547 -0.6222 13.95853
October 654.00000 23.70500 27.44509 0.25288 6.76375
November 630.00000 23.68164 18.09241 0.17691 6.15479
December 654.00000 23.53716 10.85198 0.08730 5.71260
           
Annual Sum or Average 7830.00000 23.49711 26.64075 -0.1895 9.74313
Minimum of Months 597.00000 23.17347 9.71503 -0.6916 5.64058
Maximum of Months 684.00000 23.74036 47.61791 0.25288 15.85070



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 DRESSING ROOM PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 604.00000 20.80165 11.21298 -0.6571 15.44219
February 551.00000 21.09652 12.44107 -0.5782 13.24902
March 630.00000 21.50655 15.92769 -0.4577 10.38899
April 595.00000 21.72124 20.04753 -0.3764 8.68874
May 617.00000 21.87896 33.93022 -1.3754 44.57044
June 608.00000 21.91719 46.76135 -1.2795 39.69261
July 604.00000 21.82630 50.94020 -1.2861 40.09339
August 630.00000 21.89470 51.63907 -1.2595 38.67633
September 595.00000 21.86494 42.40045 -1.3347 42.43031
October 604.00000 21.71147 30.36827 -0.3201 8.03470
November 582.00000 21.37586 20.08475 -0.4648 10.85087
December 604.00000 20.91376 12.42154 -0.6217 14.56376
           
Annual Sum or Average 7224.00000 21.54753 29.21088 -0.8386 24.05432
Minimum of Months 551.00000 20.80165 11.21298 -1.3754 8.03470
Maximum of Months 630.00000 21.91719 51.63907 -0.3201 44.57044



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 HUMID PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 604.00000 20.91350 11.04562 -0.6238 14.61064
February 551.00000 21.22976 12.24942 -0.5387 12.36000
March 630.00000 21.65557 15.69833 -0.4128 9.58308
April 595.00000 21.87707 19.78680 -0.3282 7.98053
May 617.00000 22.04166 33.55329 -1.3022 40.92557
June 608.00000 22.07999 46.20540 -1.2057 36.10854
July 604.00000 21.99721 50.31927 -1.2107 36.43283
August 630.00000 22.05824 51.01708 -1.1855 35.09336
September 595.00000 22.02873 41.90124 -1.2620 38.82287
October 604.00000 21.86831 30.00076 -0.2720 7.44946
November 582.00000 21.51785 19.82396 -0.4218 10.08397
December 604.00000 21.03033 12.23435 -0.5870 13.74426
           
Annual Sum or Average 7224.00000 21.69682 28.84714 -0.7833 22.08053
Minimum of Months 551.00000 20.91350 11.04562 -1.3022 7.44946
Maximum of Months 630.00000 22.07999 51.01708 -0.2720 40.92557



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 LOCKER PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 20.95050 12.61606 -0.6358 15.41075
February 597.00000 21.23905 13.65451 -0.5509 13.02497
March 684.00000 21.65402 16.99304 -0.4190 9.95877
April 645.00000 21.97475 20.83229 -0.3016 7.70630
May 669.00000 22.27781 34.40707 -1.2007 36.04139
June 660.00000 22.37540 46.42870 -1.0756 30.07830
July 654.00000 22.34505 50.25121 -1.0627 29.54204
August 684.00000 22.32832 51.22012 -1.0655 29.55638
September 645.00000 22.22184 42.42984 -1.1824 34.99524
October 654.00000 21.97962 31.06615 -0.2420 7.15631
November 630.00000 21.58773 21.08536 -0.4097 10.13149
December 654.00000 21.07207 13.66513 -0.5943 14.38964
           
Annual Sum or Average 7830.00000 21.84079 29.74816 -0.7319 19.94676
Minimum of Months 597.00000 20.95050 12.61606 -1.2007 7.15631
Maximum of Months 684.00000 22.37540 51.22012 -0.2420 36.04139



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 LOUNGE PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 21.02446 12.69457 -0.6361 15.45174
February 597.00000 21.34203 13.66365 -0.5371 12.69912
March 684.00000 21.74897 16.98825 -0.3976 9.64404
April 645.00000 22.13919 20.72004 -0.2549 7.14535
May 669.00000 22.44871 34.12215 -1.1099 31.91093
June 660.00000 22.54978 45.67709 -0.9754 25.86488
July 654.00000 22.54598 49.26800 -0.9516 24.90878
August 684.00000 22.50664 50.43749 -0.9647 25.28934
September 645.00000 22.39530 42.00247 -1.0963 31.02192
October 654.00000 22.13573 30.86164 -0.1957 6.67939
November 630.00000 21.74159 21.00277 -0.3748 9.50734
December 654.00000 21.17143 13.70605 -0.5864 14.19870
           
Annual Sum or Average 7830.00000 21.98633 29.45205 -0.6764 17.95052
Minimum of Months 597.00000 21.02446 12.69457 -1.1099 6.67939
Maximum of Months 684.00000 22.54978 50.43749 -0.1957 31.91093



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 OFFICE PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 604.00000 20.03452 12.35239 -0.8756 22.73363
February 551.00000 20.42238 13.57229 -0.7617 18.86113
March 630.00000 20.97836 16.91950 -0.5932 13.94866
April 595.00000 21.54086 20.57150 -0.4124 9.51170
May 617.00000 22.04253 33.66907 -1.2760 39.66727
June 608.00000 22.23028 45.34701 -1.1153 31.80997
July 604.00000 22.24879 48.93757 -1.0819 30.27753
August 630.00000 22.20240 50.22756 -1.0984 30.89196
September 595.00000 21.97569 42.14895 -1.2609 38.70659
October 604.00000 21.55620 30.91862 -0.3485 8.59977
November 582.00000 20.99533 20.98505 -0.5632 13.54470
December 604.00000 20.24082 13.54321 -0.8114 20.61859
           
Annual Sum or Average 7224.00000 21.38275 29.28181 -0.8523 23.35227
Minimum of Months 551.00000 20.03452 12.35239 -1.2760 8.59977
Maximum of Months 630.00000 22.24879 50.22756 -0.3485 39.66727



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 1 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.69010 12.42432 -0.9281 25.80442
February 597.00000 19.90619 13.88228 -0.8201 22.57928
March 684.00000 20.06627 18.01937 -0.7304 19.52999
April 645.00000 20.18617 22.70903 -0.6267 16.41873
May 669.00000 20.17565 38.34064 -1.7214 61.09044
June 660.00000 20.12487 52.34569 -1.6272 57.14759
July 654.00000 20.04923 56.62481 -1.6155 56.66526
August 684.00000 20.09540 57.77076 -1.6057 56.31933
September 645.00000 20.18931 47.53092 -1.6818 59.68608
October 654.00000 20.05684 34.25013 -0.6049 15.68785
November 630.00000 19.86217 22.89071 -0.7645 20.32614
December 654.00000 19.65306 14.00106 -0.9301 25.51827
           
Annual Sum or Average 7830.00000 20.00634 32.79266 -1.1432 36.61874
Minimum of Months 597.00000 19.65306 12.42432 -1.7214 15.68785
Maximum of Months 684.00000 20.18931 57.77076 -0.6049 61.09044



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 2 PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.72833 12.61589 -0.8468 21.88157
February 597.00000 19.82496 14.20063 -0.7946 20.15071
March 684.00000 20.03743 18.31644 -0.7016 17.25986
April 645.00000 20.12167 23.09564 -0.6328 15.16055
May 669.00000 20.02265 39.01512 -1.7911 64.78535
June 660.00000 19.92394 53.32041 -1.7260 61.89367
July 654.00000 19.79906 57.83001 -1.7407 62.52128
August 684.00000 19.87324 58.87000 -1.7145 61.36169
September 645.00000 20.05084 48.15551 -1.7462 62.94397
October 654.00000 20.06500 34.55594 -0.5892 14.13955
November 630.00000 19.92351 23.03421 -0.7079 17.58962
December 654.00000 19.72033 14.11588 -0.8332 21.40108
           
Annual Sum or Average 7830.00000 19.92503 33.32534 -1.1580 37.02430
Minimum of Months 597.00000 19.72033 12.61589 -1.7911 14.13955
Maximum of Months 684.00000 20.12167 58.87000 -0.5892 64.78535



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 TREATMENT PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 654.00000 19.86600 11.91765 -0.7897 19.96715
February 597.00000 20.02869 13.45436 -0.7239 17.96149
March 684.00000 20.30675 17.43316 -0.6190 14.95513
April 645.00000 20.40775 22.18234 -0.5492 13.02488
May 669.00000 20.33208 37.75287 -1.6662 59.00773
June 660.00000 20.20882 51.85635 -1.6094 56.36537
July 654.00000 20.05713 56.40028 -1.6320 57.39663
August 684.00000 20.15517 57.30665 -1.5970 55.76526
September 645.00000 20.36330 46.74703 -1.6195 56.87057
October 654.00000 20.37253 33.37428 -0.4999 12.11612
November 630.00000 20.16791 22.12367 -0.6298 15.46674
December 654.00000 19.87903 13.39659 -0.7721 19.39462
           
Annual Sum or Average 7830.00000 20.18013 32.22242 -1.0646 33.43597
Minimum of Months 597.00000 19.86600 11.91765 -1.6662 12.11612
Maximum of Months 684.00000 20.40775 57.30665 -0.4999 59.00773



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FLOOR 3 WORK PEOPLE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 604.00000 19.69356 12.57907 -0.9737 26.58345
February 551.00000 20.11513 13.78462 -0.8406 21.91570
March 630.00000 20.78420 17.03008 -0.6339 15.55055
April 595.00000 21.54779 20.26857 -0.3901 9.79795
May 617.00000 22.28436 33.05527 -1.1657 34.77701
June 608.00000 22.52019 44.41023 -0.9820 26.63920
July 604.00000 22.56637 47.84462 -0.9381 24.76072
August 630.00000 22.45505 49.33438 -0.9935 26.85130
September 595.00000 22.05917 41.79829 -1.2192 36.92309
October 604.00000 21.43473 31.11207 -0.3786 9.35318
November 582.00000 20.60638 21.48525 -0.6612 16.42862
December 604.00000 19.77596 13.96820 -0.9383 25.22548
           
Annual Sum or Average 7224.00000 21.33461 29.06424 -0.8440 22.93752
Minimum of Months 551.00000 19.69356 12.57907 -1.2192 9.35318
Maximum of Months 630.00000 22.56637 49.33438 -0.3786 36.92309



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum}[W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRIC POWER [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum}[] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.223148E+12 0.00 744.00 121008.89 02-JAN-06:01 0.00 66.74 82.24 1.40 0.00 0.83 1.20 02-JAN-06:01
February 0.162158E+12 0.00 672.00 121008.89 01-FEB-06:02 0.00 66.00 82.22 1.07 0.00 0.66 1.20 01-FEB-06:02
March 0.129038E+12 0.00 744.00 121008.89 03-MAR-06:01 0.00 65.22 82.21 0.72 0.00 0.48 1.20 03-MAR-06:01
April 0.544651E+11 0.00 720.00 121008.89 05-APR-05:01 0.00 66.99 82.20 0.35 0.00 0.21 1.20 05-APR-05:01
May 0.260190E+11 0.00 744.00 77045.58 01-MAY-06:01 0.00 66.83 82.20 0.17 0.00 0.10 0.76 01-MAY-06:01
June 0.202542E+11 0.00 720.00 37092.26 12-JUN-05:01 0.00 66.23 82.20 0.12 0.00 0.08 0.37 12-JUN-05:01
July 0.190226E+11 0.00 744.00 37112.23 10-JUL-05:01 0.00 66.34 82.20 0.11 0.00 0.07 0.37 10-JUL-05:01
August 0.183028E+11 0.00 744.00 41605.19 19-AUG-06:03 0.00 66.59 82.20 0.11 0.00 0.07 0.41 19-AUG-06:03
September 0.207480E+11 0.00 720.00 52445.56 06-SEP-06:01 0.00 67.08 82.20 0.14 0.00 0.08 0.52 06-SEP-06:01
October 0.400273E+11 0.00 744.00 121008.89 30-OCT-05:01 0.00 67.91 82.20 0.28 0.00 0.15 1.20 30-OCT-05:01
November 0.899323E+11 0.00 720.00 121008.89 24-NOV-06:01 0.00 65.41 82.20 0.51 0.00 0.34 1.20 24-NOV-06:01
December 0.204476E+12 0.00 744.00 121008.89 01-DEC-06:01 0.00 66.31 82.23 1.26 0.00 0.76 1.20 01-DEC-06:01
                           
Annual Sum or Average 0.100759E+13   8760.00       66.48 82.21 0.52 0.00 0.32    
Minimum of Months 0.183028E+11 0.00 672.00 37092.26   0.00 65.22 82.20 0.11 0.00 0.07 0.37  
Maximum of Months 0.223148E+12 0.00 744.00 121008.89   0.00 67.91 82.24 1.40 0.00 0.83 1.20  



Table of Contents

Report: DXReportMonthly

For: AHU-1_COOLC DXCOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRIC ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum}[] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM}[] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum}[W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRIC POWER {Maximum}[W] COOLING COIL ELECTRIC POWER {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRIC POWER []
January 0.613024E+09 0.185936E+09 27.82 0.585041E+09 27983397.45 0.00 0.30 19-JAN-07:01 0.00 01-JAN-00:10 15309.37 19-JAN-07:01 15309.37 19-JAN-07:01 678.44 18-JAN-15:30 4479.99 19-JAN-07:01 0.00
February 0.465325E+10 0.132739E+10 86.29 0.463282E+10 20431057.58 0.00 0.65 28-FEB-15:02 0.00 01-FEB-00:10 36122.53 28-FEB-15:02 36122.53 28-FEB-15:02 672.77 21-FEB-07:00 9660.81 28-FEB-15:02 0.00
March 0.941316E+10 0.271203E+10 196.47 0.927986E+10 0.133302E+09 0.00 0.74 31-MAR-17:00 0.00 01-MAR-00:10 42075.97 31-MAR-17:00 42075.97 31-MAR-17:00 1222.55 26-MAR-16:03 10982.65 31-MAR-17:00 0.00
April 0.336983E+11 0.905881E+10 397.59 0.328879E+11 0.810496E+09 0.00 1.00 12-APR-13:50 0.00 01-APR-00:10 69657.50 13-APR-16:00 69657.50 13-APR-16:00 7899.69 23-APR-11:20 16878.51 13-APR-16:00 0.00
May 0.912710E+11 0.237815E+11 654.44 0.814013E+11 0.986975E+10 0.00 1.00 02-MAY-14:05 0.00 01-MAY-00:10 117341.08 25-MAY-16:00 93094.83 25-MAY-17:00 35723.46 26-MAY-12:00 31557.38 25-MAY-16:00 0.00
June 0.150507E+12 0.382064E+11 703.85 0.107982E+12 0.425254E+11 0.00 1.00 01-JUN-08:25 0.00 02-JUN-21:33 166941.85 30-JUN-16:00 108876.66 29-JUN-16:00 65385.91 30-JUN-16:00 48893.55 29-JUN-16:00 0.00
July 0.183454E+12 0.461181E+11 744.00 0.120141E+12 0.633135E+11 0.00 1.00 01-JUL-08:15 0.04 02-JUL-04:52 157698.56 15-JUL-14:00 97382.59 21-JUL-16:00 73958.77 15-JUL-14:00 42054.11 15-JUL-14:00 0.00
August 0.163446E+12 0.409750E+11 740.50 0.112167E+12 0.512796E+11 0.00 1.00 01-AUG-05:01 0.00 19-AUG-01:40 150528.89 08-AUG-15:00 96847.75 08-AUG-16:00 55730.86 31-AUG-13:00 40778.40 08-AUG-15:00 0.00
September 0.875521E+11 0.226086E+11 664.45 0.704994E+11 0.170527E+11 0.00 1.00 01-SEP-00:10 0.00 05-SEP-04:52 109417.67 01-SEP-14:05 88685.45 01-SEP-16:00 35387.14 18-SEP-17:00 27931.26 01-SEP-14:05 0.00
October 0.394280E+11 0.106673E+11 463.98 0.365304E+11 0.289762E+10 0.00 1.00 18-OCT-14:05 0.00 01-OCT-01:11 77081.77 19-OCT-14:05 76811.65 19-OCT-15:00 12868.72 07-OCT-12:10 18895.57 19-OCT-14:05 0.00
November 0.185569E+11 0.507048E+10 243.87 0.172511E+11 0.130583E+10 0.00 1.00 01-NOV-11:30 0.00 01-NOV-00:10 71316.21 21-NOV-13:05 62113.69 01-NOV-14:02 20992.28 21-NOV-13:00 17153.11 21-NOV-13:05 0.00
December 0.128082E+10 0.383754E+09 46.54 0.122295E+10 57871955.67 0.00 0.40 05-DEC-07:01 0.00 01-DEC-00:03 20467.11 05-DEC-07:01 20467.11 05-DEC-07:01 1032.52 05-DEC-12:30 5852.73 05-DEC-07:01 0.00
                                       
Annual Sum or Average 0.783874E+12 0.201095E+12 4969.81 0.594580E+12 0.189295E+12                            
Minimum of Months 0.613024E+09 0.185936E+09 27.82 0.585041E+09 20431057.58 0.00 0.30   0.00   15309.37   15309.37   672.77   4479.99   0.00
Maximum of Months 0.183454E+12 0.461181E+11 744.00 0.120141E+12 0.633135E+11 0.00 1.00   0.04   166941.85   108876.66   73958.77   48893.55   0.00



Table of Contents

Report: DXReportMonthly

For: AHU-2_COOLC DXCOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRIC ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum}[] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM}[] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum}[W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRIC POWER {Maximum}[W] COOLING COIL ELECTRIC POWER {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRIC POWER []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00
February 0.662896E+09 0.197300E+09 21.54 0.662896E+09 0.00 0.00 0.36 28-FEB-15:40 0.00 01-FEB-00:10 23158.76 28-FEB-15:40 23158.76 28-FEB-15:40 0.00 28-FEB-16:20 6679.82 28-FEB-15:40 0.00
March 0.190342E+10 0.551935E+09 38.74 0.190342E+10 0.00 0.00 0.59 31-MAR-16:00 0.00 01-MAR-00:10 40337.91 31-MAR-16:00 40337.91 31-MAR-16:00 0.00 28-MAR-16:10 10963.08 31-MAR-16:00 0.00
April 0.186185E+11 0.500481E+10 171.78 0.185119E+11 0.106567E+09 0.00 1.00 13-APR-14:05 0.00 01-APR-00:10 82056.76 13-APR-15:00 82056.76 13-APR-15:00 7907.21 23-APR-11:10 19885.71 13-APR-15:00 0.00
May 0.664248E+11 0.174116E+11 413.19 0.610321E+11 0.539272E+10 0.00 1.00 03-MAY-12:00 0.00 01-MAY-00:10 142397.30 25-MAY-16:00 119107.24 25-MAY-16:50 35485.38 26-MAY-12:00 38274.44 25-MAY-16:00 0.00
June 0.123370E+12 0.318954E+11 535.83 0.963661E+11 0.270040E+11 0.00 1.00 01-JUN-09:30 0.00 01-JUN-00:10 210291.37 30-JUN-06:01 141527.39 29-JUN-16:00 76417.11 30-JUN-06:03 60234.73 29-JUN-16:00 0.00
July 0.154804E+12 0.398801E+11 627.02 0.117886E+12 0.369180E+11 0.00 1.00 01-JUL-09:50 0.00 01-JUL-01:30 183194.25 15-JUL-14:00 125227.32 21-JUL-16:00 82912.14 15-JUL-14:00 48382.95 15-JUL-14:00 0.00
August 0.134127E+12 0.343504E+11 612.52 0.960643E+11 0.380626E+11 0.00 1.00 01-AUG-05:01 0.00 01-AUG-23:12 182278.61 08-AUG-15:00 122830.20 08-AUG-16:00 91141.43 30-AUG-06:03 49057.82 08-AUG-15:00 0.00
September 0.462269E+11 0.120943E+11 323.08 0.390028E+11 0.722410E+10 0.00 1.00 01-SEP-06:01 0.00 01-SEP-22:00 131397.20 01-SEP-14:05 113178.78 01-SEP-15:20 54411.37 01-SEP-08:10 33547.15 01-SEP-14:05 0.00
October 0.133119E+11 0.360235E+10 164.00 0.130443E+11 0.267626E+09 0.00 1.00 19-OCT-12:05 0.00 01-OCT-00:02 92656.15 19-OCT-15:00 92656.15 19-OCT-15:00 10833.57 07-OCT-13:00 22794.12 19-OCT-15:00 0.00
November 0.344317E+10 0.982193E+09 64.05 0.315634E+10 0.286829E+09 0.00 0.72 01-NOV-15:00 0.00 01-NOV-00:10 50098.43 01-NOV-15:00 42960.77 01-NOV-15:00 13496.43 21-NOV-13:00 13061.40 01-NOV-15:00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00
                                       
Annual Sum or Average 0.562893E+12 0.145970E+12 2971.74 0.447631E+12 0.115262E+12                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.154804E+12 0.398801E+11 627.02 0.117886E+12 0.380626E+11 0.00 1.00   0.00   210291.37   141527.39   91141.43   60234.73   0.00



Table of Contents

Report: WindowReportMonthly

For: 78F987

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.67 54.05 23.62 63.82 82.97 0.00 0.00 744.00
February 98.35 66.46 31.89 88.86 69.75 0.00 0.00 672.00
March 86.64 54.85 31.79 74.66 57.11 0.00 0.00 744.00
April 78.39 42.52 35.87 67.94 34.14 0.00 0.00 720.00
May 65.85 22.44 43.40 61.14 15.29 0.00 0.00 744.00
June 59.07 15.67 43.40 60.06 8.47 0.00 0.00 720.00
July 64.58 20.38 44.20 68.39 6.86 0.00 0.00 744.00
August 69.02 28.83 40.19 73.75 8.73 0.00 0.00 744.00
September 74.02 39.42 34.59 76.88 18.47 0.00 0.00 720.00
October 63.25 37.22 26.03 60.62 33.01 0.00 0.00 744.00
November 56.34 35.37 20.96 49.40 51.98 0.00 0.00 720.00
December 59.96 39.33 20.63 45.32 80.95 0.00 0.00 744.00
                 
Annual Sum or Average 70.92 37.87 33.05 65.74 38.84 0.00 0.00 8760.00
Minimum of Months 56.34 15.67 20.63 45.32 6.86 0.00 0.00 672.00
Maximum of Months 98.35 66.46 44.20 88.86 82.97 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: D8037E

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 293.97 206.10 87.87 244.73 349.41 14.33 0.00 744.00
February 360.75 244.99 115.76 331.42 304.62 3.00 0.00 672.00
March 304.06 189.27 114.79 264.21 252.89 0.00 0.00 744.00
April 289.63 156.93 132.70 250.80 155.71 0.00 0.00 720.00
May 250.07 87.74 162.32 222.70 76.80 0.00 0.00 744.00
June 224.96 62.06 162.90 215.92 48.17 0.00 0.00 720.00
July 246.01 80.19 165.82 247.17 42.37 0.00 0.00 744.00
August 259.46 110.04 149.42 269.34 52.94 0.00 0.00 744.00
September 265.91 139.41 126.51 272.96 93.92 0.00 0.00 720.00
October 226.84 132.37 94.47 215.17 154.10 0.00 0.00 744.00
November 211.10 133.74 77.35 185.99 227.57 0.00 0.00 720.00
December 229.29 151.26 78.02 174.01 338.17 6.50 0.00 744.00
                 
Annual Sum or Average 262.87 140.52 122.35 240.57 174.13 23.83 0.00 8760.00
Minimum of Months 211.10 62.06 77.35 174.01 42.37 0.00 0.00 672.00
Maximum of Months 360.75 244.99 165.82 331.42 349.41 14.33 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 4A8120

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.79 0.00 10.79 0.08 93.45 0.00 0.00 744.00
February 16.64 0.00 16.64 1.41 72.02 0.00 0.00 672.00
March 20.54 0.00 20.54 4.01 51.75 0.00 0.00 744.00
April 26.68 0.04 26.64 16.75 25.98 0.00 0.00 720.00
May 36.07 0.86 35.21 39.57 9.02 0.00 0.00 744.00
June 39.33 2.71 36.62 51.27 4.13 0.00 0.00 720.00
July 38.10 1.90 36.20 52.44 3.29 0.00 0.00 744.00
August 30.06 0.19 29.86 39.15 4.28 0.00 0.00 744.00
September 23.80 0.00 23.80 23.45 12.87 0.00 0.00 720.00
October 16.46 0.00 16.46 8.12 27.05 0.00 0.00 744.00
November 10.88 0.00 10.88 1.26 49.83 0.00 0.00 720.00
December 9.12 0.00 9.12 0.00 89.20 0.00 0.00 744.00
                 
Annual Sum or Average 23.24 0.48 22.76 19.91 36.77 0.00 0.00 8760.00
Minimum of Months 9.12 0.00 9.12 0.00 3.29 0.00 0.00 672.00
Maximum of Months 39.33 2.71 36.62 52.44 93.45 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: AAE778

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 98.15 41.81 56.35 29.76 396.01 0.00 0.00 744.00
February 160.23 74.33 85.90 84.17 320.89 0.00 0.00 672.00
March 211.25 109.64 101.61 146.51 251.14 0.00 0.00 744.00
April 270.04 138.65 131.39 234.10 150.79 0.00 0.00 720.00
May 331.24 160.41 170.84 349.62 76.56 0.00 0.00 744.00
June 319.48 140.32 179.16 359.35 49.13 0.00 0.00 720.00
July 341.51 161.04 180.47 395.39 44.63 0.00 0.00 744.00
August 280.77 129.54 151.23 312.56 54.26 0.00 0.00 744.00
September 219.24 100.13 119.11 213.85 93.59 0.00 0.00 720.00
October 138.06 56.49 81.58 96.31 154.88 0.00 0.00 744.00
November 83.65 28.79 54.86 30.24 244.81 0.00 0.00 720.00
December 74.65 26.63 48.02 14.78 386.13 0.00 0.00 744.00
                 
Annual Sum or Average 210.97 97.45 113.52 189.52 184.67 0.00 0.00 8760.00
Minimum of Months 74.65 26.63 48.02 14.78 44.63 0.00 0.00 672.00
Maximum of Months 341.51 161.04 180.47 395.39 396.01 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 3AAD8B

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.23 0.00 12.23 0.00 137.98 0.00 0.00 744.00
February 18.79 0.00 18.79 0.31 112.51 0.00 0.00 672.00
March 23.16 0.00 23.16 1.51 86.58 0.00 0.00 744.00
April 30.14 0.09 30.05 10.81 49.86 0.00 0.00 720.00
May 41.34 1.43 39.91 33.82 23.11 0.00 0.00 744.00
June 44.01 2.81 41.20 45.06 14.28 0.00 0.00 720.00
July 42.60 2.15 40.45 46.92 12.16 0.00 0.00 744.00
August 33.95 0.33 33.62 34.34 15.21 0.00 0.00 744.00
September 26.92 0.00 26.92 18.69 28.65 0.00 0.00 720.00
October 18.75 0.00 18.75 4.40 50.44 0.00 0.00 744.00
November 12.37 0.00 12.37 0.52 83.94 0.00 0.00 720.00
December 10.38 0.00 10.38 0.00 133.17 0.00 0.00 744.00
                 
Annual Sum or Average 26.26 0.57 25.69 16.47 62.11 0.00 0.00 8760.00
Minimum of Months 10.38 0.00 10.38 0.00 12.16 0.00 0.00 672.00
Maximum of Months 44.01 2.81 41.20 46.92 137.98 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 8128A9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.43 0.00 13.43 0.00 137.43 0.00 0.00 744.00
February 20.58 0.00 20.58 0.52 111.51 0.00 0.00 672.00
March 25.31 0.00 25.31 2.13 85.52 0.00 0.00 744.00
April 32.73 0.06 32.67 12.70 49.58 0.00 0.00 720.00
May 45.16 1.55 43.61 37.41 23.14 0.00 0.00 744.00
June 48.88 3.62 45.26 49.52 14.34 0.00 0.00 720.00
July 46.93 2.60 44.33 51.09 12.42 0.00 0.00 744.00
August 37.08 0.33 36.74 37.57 15.47 0.00 0.00 744.00
September 29.44 0.00 29.44 21.13 28.84 0.00 0.00 720.00
October 20.56 0.00 20.56 5.59 50.27 0.00 0.00 744.00
November 13.59 0.00 13.59 0.67 83.43 0.00 0.00 720.00
December 11.41 0.00 11.41 0.00 132.77 0.00 0.00 744.00
                 
Annual Sum or Average 28.80 0.68 28.11 18.31 61.85 0.00 0.00 8760.00
Minimum of Months 11.41 0.00 11.41 0.00 12.42 0.00 0.00 672.00
Maximum of Months 48.88 3.62 45.26 51.09 137.43 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 9B1541

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.67 54.05 23.62 66.11 80.71 0.00 0.00 744.00
February 98.35 66.46 31.89 91.70 67.93 0.00 0.00 672.00
March 86.64 54.85 31.79 77.34 54.95 0.00 0.00 744.00
April 78.39 42.52 35.87 71.03 33.05 0.00 0.00 720.00
May 65.85 22.44 43.40 64.43 15.48 0.00 0.00 744.00
June 59.07 15.67 43.40 63.25 9.00 0.00 0.00 720.00
July 64.58 20.38 44.20 71.22 7.65 0.00 0.00 744.00
August 69.02 28.83 40.19 77.10 9.58 0.00 0.00 744.00
September 74.02 39.42 34.59 80.08 18.65 0.00 0.00 720.00
October 63.25 37.22 26.03 63.45 32.06 0.00 0.00 744.00
November 56.34 35.37 20.96 51.85 50.13 0.00 0.00 720.00
December 59.96 39.33 20.63 47.10 78.41 0.00 0.00 744.00
                 
Annual Sum or Average 70.92 37.87 33.05 68.56 38.00 0.00 0.00 8760.00
Minimum of Months 56.34 15.67 20.63 47.10 7.65 0.00 0.00 672.00
Maximum of Months 98.35 66.46 44.20 91.70 80.71 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: CF850A

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.67 54.05 23.62 66.11 80.71 0.00 0.00 744.00
February 98.35 66.46 31.89 91.70 67.93 0.00 0.00 672.00
March 86.64 54.85 31.79 77.34 54.95 0.00 0.00 744.00
April 78.39 42.52 35.87 71.03 33.05 0.00 0.00 720.00
May 65.85 22.44 43.40 64.44 15.45 0.00 0.00 744.00
June 59.07 15.67 43.40 63.26 8.99 0.00 0.00 720.00
July 64.58 20.38 44.20 71.24 7.64 0.00 0.00 744.00
August 69.02 28.83 40.19 77.10 9.57 0.00 0.00 744.00
September 74.02 39.42 34.59 80.08 18.65 0.00 0.00 720.00
October 63.25 37.22 26.03 63.45 32.06 0.00 0.00 744.00
November 56.34 35.37 20.96 51.85 50.13 0.00 0.00 720.00
December 59.96 39.33 20.63 47.10 78.41 0.00 0.00 744.00
                 
Annual Sum or Average 70.92 37.87 33.05 68.56 38.00 0.00 0.00 8760.00
Minimum of Months 56.34 15.67 20.63 47.10 7.64 0.00 0.00 672.00
Maximum of Months 98.35 66.46 44.20 91.70 80.71 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: A6BA23

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.70 10.31 14.39 6.66 92.51 0.00 0.00 744.00
February 38.82 16.55 22.26 18.49 72.55 0.00 0.00 672.00
March 52.92 26.55 26.37 37.25 54.94 0.00 0.00 744.00
April 73.36 39.58 33.78 69.43 31.21 0.00 0.00 720.00
May 79.39 34.90 44.48 89.38 14.30 0.00 0.00 744.00
June 89.87 43.00 46.87 110.77 8.46 0.00 0.00 720.00
July 88.04 41.35 46.70 111.02 7.30 0.00 0.00 744.00
August 67.88 29.68 38.21 82.80 9.33 0.00 0.00 744.00
September 54.37 24.34 30.02 58.04 18.19 0.00 0.00 720.00
October 32.91 12.48 20.43 24.98 32.05 0.00 0.00 744.00
November 20.95 7.00 13.95 8.35 53.68 0.00 0.00 720.00
December 19.11 7.06 12.05 3.99 90.20 0.00 0.00 744.00
                 
Annual Sum or Average 53.58 24.42 29.16 51.93 40.26 0.00 0.00 8760.00
Minimum of Months 19.11 7.00 12.05 3.99 7.30 0.00 0.00 672.00
Maximum of Months 89.87 43.00 46.87 111.02 92.51 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: D10D28

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.70 10.31 14.39 6.66 92.82 0.00 0.00 744.00
February 38.82 16.55 22.26 18.46 72.93 0.00 0.00 672.00
March 52.92 26.55 26.37 37.23 55.00 0.00 0.00 744.00
April 73.36 39.58 33.78 69.43 31.21 0.00 0.00 720.00
May 79.39 34.90 44.48 89.38 14.30 0.00 0.00 744.00
June 89.87 43.00 46.87 110.77 8.46 0.00 0.00 720.00
July 88.04 41.35 46.70 111.02 7.30 0.00 0.00 744.00
August 67.88 29.68 38.21 82.80 9.33 0.00 0.00 744.00
September 54.37 24.34 30.02 58.02 18.19 0.00 0.00 720.00
October 32.91 12.48 20.43 24.88 32.09 0.00 0.00 744.00
November 20.95 7.00 13.95 8.34 53.86 0.00 0.00 720.00
December 19.11 7.06 12.05 3.99 90.37 0.00 0.00 744.00
                 
Annual Sum or Average 53.58 24.42 29.16 51.91 40.36 0.00 0.00 8760.00
Minimum of Months 19.11 7.00 12.05 3.99 7.30 0.00 0.00 672.00
Maximum of Months 89.87 43.00 46.87 111.02 92.82 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 591336

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.70 10.31 14.39 6.58 94.18 0.00 0.00 744.00
February 38.82 16.55 22.26 18.41 74.01 0.00 0.00 672.00
March 52.92 26.55 26.37 37.18 55.98 0.00 0.00 744.00
April 73.36 39.58 33.78 69.51 31.78 0.00 0.00 720.00
May 79.39 34.90 44.48 90.25 13.96 0.00 0.00 744.00
June 89.87 43.00 46.87 112.10 7.85 0.00 0.00 720.00
July 88.04 41.35 46.70 112.39 6.76 0.00 0.00 744.00
August 67.88 29.68 38.21 83.83 8.77 0.00 0.00 744.00
September 54.37 24.34 30.02 59.42 16.88 0.00 0.00 720.00
October 32.91 12.48 20.43 25.57 31.27 0.00 0.00 744.00
November 20.95 7.00 13.95 8.48 54.27 0.00 0.00 720.00
December 19.11 7.06 12.05 3.94 91.87 0.00 0.00 744.00
                 
Annual Sum or Average 53.58 24.42 29.16 52.47 40.50 0.00 0.00 8760.00
Minimum of Months 19.11 7.00 12.05 3.94 6.76 0.00 0.00 672.00
Maximum of Months 89.87 43.00 46.87 112.39 94.18 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 38B811

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.70 10.31 14.39 6.58 94.18 0.00 0.00 744.00
February 38.82 16.55 22.26 18.41 74.01 0.00 0.00 672.00
March 52.92 26.55 26.37 37.18 55.98 0.00 0.00 744.00
April 73.36 39.58 33.78 69.51 31.78 0.00 0.00 720.00
May 79.39 34.90 44.48 90.25 13.96 0.00 0.00 744.00
June 89.87 43.00 46.87 112.10 7.85 0.00 0.00 720.00
July 88.04 41.35 46.70 112.39 6.76 0.00 0.00 744.00
August 67.88 29.68 38.21 83.83 8.77 0.00 0.00 744.00
September 54.37 24.34 30.02 59.42 16.88 0.00 0.00 720.00
October 32.91 12.48 20.43 25.57 31.27 0.00 0.00 744.00
November 20.95 7.00 13.95 8.48 54.27 0.00 0.00 720.00
December 19.11 7.06 12.05 3.94 91.87 0.00 0.00 744.00
                 
Annual Sum or Average 53.58 24.42 29.16 52.47 40.50 0.00 0.00 8760.00
Minimum of Months 19.11 7.00 12.05 3.94 6.76 0.00 0.00 672.00
Maximum of Months 89.87 43.00 46.87 112.39 94.18 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: C044D6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.70 10.31 14.39 6.58 94.18 0.00 0.00 744.00
February 38.82 16.55 22.26 18.41 74.01 0.00 0.00 672.00
March 52.92 26.55 26.37 37.18 55.98 0.00 0.00 744.00
April 73.36 39.58 33.78 69.51 31.78 0.00 0.00 720.00
May 79.39 34.90 44.48 90.25 13.96 0.00 0.00 744.00
June 89.87 43.00 46.87 112.10 7.85 0.00 0.00 720.00
July 88.04 41.35 46.70 112.39 6.76 0.00 0.00 744.00
August 67.88 29.68 38.21 83.83 8.77 0.00 0.00 744.00
September 54.37 24.34 30.02 59.42 16.88 0.00 0.00 720.00
October 32.91 12.48 20.43 25.57 31.27 0.00 0.00 744.00
November 20.95 7.00 13.95 8.48 54.27 0.00 0.00 720.00
December 19.11 7.06 12.05 3.94 91.87 0.00 0.00 744.00
                 
Annual Sum or Average 53.58 24.42 29.16 52.47 40.50 0.00 0.00 8760.00
Minimum of Months 19.11 7.00 12.05 3.94 6.76 0.00 0.00 672.00
Maximum of Months 89.87 43.00 46.87 112.39 94.18 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 1D94BE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.87 0.00 13.87 0.03 128.28 0.00 0.00 744.00
February 21.29 0.00 21.29 1.00 101.92 0.00 0.00 672.00
March 26.19 0.00 26.19 3.34 76.42 0.00 0.00 744.00
April 33.80 0.03 33.77 16.10 42.47 0.00 0.00 720.00
May 46.88 1.70 45.18 43.12 18.15 0.00 0.00 744.00
June 51.77 4.58 47.19 57.17 10.23 0.00 0.00 720.00
July 49.38 3.17 46.22 58.50 8.38 0.00 0.00 744.00
August 38.42 0.34 38.08 43.08 10.54 0.00 0.00 744.00
September 30.43 0.00 30.43 25.10 22.74 0.00 0.00 720.00
October 21.20 0.00 21.20 7.75 42.58 0.00 0.00 744.00
November 14.03 0.00 14.03 0.98 73.93 0.00 0.00 720.00
December 11.76 0.00 11.76 0.00 123.17 0.00 0.00 744.00
                 
Annual Sum or Average 29.96 0.82 29.14 21.48 54.71 0.00 0.00 8760.00
Minimum of Months 11.76 0.00 11.76 0.00 8.38 0.00 0.00 672.00
Maximum of Months 51.77 4.58 47.19 58.50 128.28 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 18748E

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.68 0.00 13.68 0.02 128.35 0.00 0.00 744.00
February 21.03 0.00 21.03 0.95 102.03 0.00 0.00 672.00
March 25.89 0.00 25.89 3.22 76.51 0.00 0.00 744.00
April 33.45 0.03 33.42 15.82 42.44 0.00 0.00 720.00
May 46.07 1.50 44.58 42.33 17.98 0.00 0.00 744.00
June 51.57 4.84 46.73 56.88 9.93 0.00 0.00 720.00
July 48.93 3.18 45.75 58.09 8.22 0.00 0.00 744.00
August 37.87 0.26 37.60 42.54 10.46 0.00 0.00 744.00
September 30.06 0.00 30.06 24.73 22.69 0.00 0.00 720.00
October 20.90 0.00 20.90 7.53 42.58 0.00 0.00 744.00
November 13.83 0.00 13.83 0.94 73.99 0.00 0.00 720.00
December 11.60 0.00 11.60 0.00 123.24 0.00 0.00 744.00
                 
Annual Sum or Average 29.61 0.82 28.79 21.22 54.67 0.00 0.00 8760.00
Minimum of Months 11.60 0.00 11.60 0.00 8.22 0.00 0.00 672.00
Maximum of Months 51.57 4.84 46.73 58.09 128.35 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 137A56

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 89.57 61.74 27.84 72.45 143.16 0.00 0.00 744.00
February 111.66 74.59 37.06 99.16 122.89 0.00 0.00 672.00
March 95.91 58.31 37.60 79.00 100.85 0.00 0.00 744.00
April 92.41 48.26 44.15 77.31 61.75 0.00 0.00 720.00
May 82.05 28.32 53.73 72.06 29.66 0.00 0.00 744.00
June 74.43 20.21 54.23 71.28 18.46 0.00 0.00 720.00
July 81.68 26.31 55.37 82.84 15.68 0.00 0.00 744.00
August 85.10 35.47 49.63 88.64 19.65 0.00 0.00 744.00
September 84.60 43.01 41.59 84.44 35.92 0.00 0.00 720.00
October 70.80 40.17 30.63 63.84 60.84 0.00 0.00 744.00
November 65.29 40.63 24.66 55.47 92.44 0.00 0.00 720.00
December 69.87 45.36 24.51 51.76 139.33 0.00 0.00 744.00
                 
Annual Sum or Average 83.43 43.34 40.10 74.68 69.82 0.00 0.00 8760.00
Minimum of Months 65.29 20.21 24.51 51.76 15.68 0.00 0.00 672.00
Maximum of Months 111.66 74.59 55.37 99.16 143.16 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 8D508E

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.67 54.05 23.62 64.43 81.80 0.00 0.00 744.00
February 98.35 66.46 31.89 89.59 68.73 0.00 0.00 672.00
March 86.64 54.85 31.79 75.31 56.14 0.00 0.00 744.00
April 78.39 42.52 35.87 68.68 33.49 0.00 0.00 720.00
May 65.85 22.44 43.40 62.03 14.95 0.00 0.00 744.00
June 59.07 15.67 43.40 61.00 8.27 0.00 0.00 720.00
July 64.58 20.38 44.20 69.25 6.68 0.00 0.00 744.00
August 69.02 28.83 40.19 74.58 8.49 0.00 0.00 744.00
September 74.02 39.42 34.59 77.58 18.12 0.00 0.00 720.00
October 63.25 37.22 26.03 61.22 32.44 0.00 0.00 744.00
November 56.34 35.37 20.96 49.91 51.11 0.00 0.00 720.00
December 59.96 39.33 20.63 45.76 79.71 0.00 0.00 744.00
                 
Annual Sum or Average 70.92 37.87 33.05 66.45 38.19 0.00 0.00 8760.00
Minimum of Months 56.34 15.67 20.63 45.76 6.68 0.00 0.00 672.00
Maximum of Months 98.35 66.46 44.20 89.59 81.80 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: B2D381

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.67 54.05 23.62 64.43 81.80 0.00 0.00 744.00
February 98.35 66.46 31.89 89.59 68.73 0.00 0.00 672.00
March 86.64 54.85 31.79 75.31 56.14 0.00 0.00 744.00
April 78.39 42.52 35.87 68.68 33.49 0.00 0.00 720.00
May 65.85 22.44 43.40 62.03 14.95 0.00 0.00 744.00
June 59.07 15.67 43.40 61.00 8.27 0.00 0.00 720.00
July 64.58 20.38 44.20 69.25 6.68 0.00 0.00 744.00
August 69.02 28.83 40.19 74.58 8.49 0.00 0.00 744.00
September 74.02 39.42 34.59 77.58 18.12 0.00 0.00 720.00
October 63.25 37.22 26.03 61.22 32.44 0.00 0.00 744.00
November 56.34 35.37 20.96 49.91 51.11 0.00 0.00 720.00
December 59.96 39.33 20.63 45.76 79.71 0.00 0.00 744.00
                 
Annual Sum or Average 70.92 37.87 33.05 66.45 38.19 0.00 0.00 8760.00
Minimum of Months 56.34 15.67 20.63 45.76 6.68 0.00 0.00 672.00
Maximum of Months 98.35 66.46 44.20 89.59 81.80 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 1DA13A

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.67 54.05 23.62 64.43 81.80 0.00 0.00 744.00
February 98.35 66.46 31.89 89.59 68.73 0.00 0.00 672.00
March 86.64 54.85 31.79 75.31 56.14 0.00 0.00 744.00
April 78.39 42.52 35.87 68.68 33.49 0.00 0.00 720.00
May 65.85 22.44 43.40 62.03 14.95 0.00 0.00 744.00
June 59.07 15.67 43.40 61.00 8.27 0.00 0.00 720.00
July 64.58 20.38 44.20 69.25 6.68 0.00 0.00 744.00
August 69.02 28.83 40.19 74.58 8.49 0.00 0.00 744.00
September 74.02 39.42 34.59 77.58 18.12 0.00 0.00 720.00
October 63.25 37.22 26.03 61.22 32.44 0.00 0.00 744.00
November 56.34 35.37 20.96 49.91 51.11 0.00 0.00 720.00
December 59.96 39.33 20.63 45.76 79.71 0.00 0.00 744.00
                 
Annual Sum or Average 70.92 37.87 33.05 66.45 38.19 0.00 0.00 8760.00
Minimum of Months 56.34 15.67 20.63 45.76 6.68 0.00 0.00 672.00
Maximum of Months 98.35 66.46 44.20 89.59 81.80 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 44E54A

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.67 54.05 23.62 64.43 81.80 0.00 0.00 744.00
February 98.35 66.46 31.89 89.59 68.73 0.00 0.00 672.00
March 86.64 54.85 31.79 75.31 56.14 0.00 0.00 744.00
April 78.39 42.52 35.87 68.68 33.49 0.00 0.00 720.00
May 65.85 22.44 43.40 62.03 14.95 0.00 0.00 744.00
June 59.07 15.67 43.40 61.00 8.27 0.00 0.00 720.00
July 64.58 20.38 44.20 69.25 6.68 0.00 0.00 744.00
August 69.02 28.83 40.19 74.58 8.49 0.00 0.00 744.00
September 74.02 39.42 34.59 77.58 18.12 0.00 0.00 720.00
October 63.25 37.22 26.03 61.22 32.44 0.00 0.00 744.00
November 56.34 35.37 20.96 49.91 51.11 0.00 0.00 720.00
December 59.96 39.33 20.63 45.76 79.71 0.00 0.00 744.00
                 
Annual Sum or Average 70.92 37.87 33.05 66.45 38.19 0.00 0.00 8760.00
Minimum of Months 56.34 15.67 20.63 45.76 6.68 0.00 0.00 672.00
Maximum of Months 98.35 66.46 44.20 89.59 81.80 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 757D10

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.22 10.21 5.01 11.80 32.26 0.00 0.00 744.00
February 19.56 12.72 6.84 16.58 27.23 0.00 0.00 672.00
March 17.38 10.27 7.11 13.51 21.92 0.00 0.00 744.00
April 16.17 7.77 8.40 12.58 13.00 0.00 0.00 720.00
May 14.65 4.53 10.12 12.73 5.86 0.00 0.00 744.00
June 13.30 3.03 10.27 13.22 3.47 0.00 0.00 720.00
July 14.78 4.25 10.52 15.50 2.85 0.00 0.00 744.00
August 15.37 6.01 9.37 15.98 3.73 0.00 0.00 744.00
September 15.14 7.31 7.83 14.55 7.34 0.00 0.00 720.00
October 12.88 7.16 5.72 11.08 13.02 0.00 0.00 744.00
November 11.31 6.83 4.47 9.15 20.45 0.00 0.00 720.00
December 11.81 7.44 4.36 8.41 31.48 0.00 0.00 744.00
                 
Annual Sum or Average 14.77 7.26 7.50 12.90 15.16 0.00 0.00 8760.00
Minimum of Months 11.31 3.03 4.36 8.41 2.85 0.00 0.00 672.00
Maximum of Months 19.56 12.72 10.52 16.58 32.26 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: E33BAE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.25 10.45 12.80 7.51 94.18 0.00 0.00 744.00
February 38.12 18.58 19.54 21.00 75.21 0.00 0.00 672.00
March 50.49 27.41 23.08 36.78 57.37 0.00 0.00 744.00
April 64.63 34.66 29.97 59.14 32.25 0.00 0.00 720.00
May 78.37 39.68 38.70 87.89 14.09 0.00 0.00 744.00
June 72.42 32.50 39.93 87.36 7.84 0.00 0.00 720.00
July 79.31 38.62 40.69 97.97 6.40 0.00 0.00 744.00
August 66.83 32.39 34.44 79.02 8.31 0.00 0.00 744.00
September 52.09 25.03 27.06 53.84 17.81 0.00 0.00 720.00
October 32.58 14.12 18.46 24.23 32.85 0.00 0.00 744.00
November 19.60 7.20 12.40 7.71 55.36 0.00 0.00 720.00
December 17.57 6.66 10.91 3.75 91.09 0.00 0.00 744.00
                 
Annual Sum or Average 49.67 23.98 25.70 47.35 40.92 0.00 0.00 8760.00
Minimum of Months 17.57 6.66 10.91 3.75 6.40 0.00 0.00 672.00
Maximum of Months 79.31 39.68 40.69 97.97 94.18 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 24167A

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.67 54.05 23.62 64.93 80.37 0.00 0.00 744.00
February 98.35 66.46 31.89 90.12 67.32 0.00 0.00 672.00
March 86.64 54.85 31.79 75.72 54.90 0.00 0.00 744.00
April 78.39 42.52 35.87 68.91 32.96 0.00 0.00 720.00
May 65.85 22.44 43.40 61.87 14.92 0.00 0.00 744.00
June 59.07 15.67 43.40 60.63 8.28 0.00 0.00 720.00
July 64.58 20.38 44.20 68.58 6.95 0.00 0.00 744.00
August 69.02 28.83 40.19 73.92 8.90 0.00 0.00 744.00
September 74.02 39.42 34.59 77.30 18.34 0.00 0.00 720.00
October 63.25 37.22 26.03 61.19 32.33 0.00 0.00 744.00
November 56.34 35.37 20.96 50.08 50.49 0.00 0.00 720.00
December 59.96 39.33 20.63 46.11 78.33 0.00 0.00 744.00
                 
Annual Sum or Average 70.92 37.87 33.05 66.45 37.71 0.00 0.00 8760.00
Minimum of Months 56.34 15.67 20.63 46.11 6.95 0.00 0.00 672.00
Maximum of Months 98.35 66.46 44.20 90.12 80.37 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 2C0938

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.67 54.05 23.62 64.93 80.37 0.00 0.00 744.00
February 98.35 66.46 31.89 90.12 67.32 0.00 0.00 672.00
March 86.64 54.85 31.79 75.72 54.90 0.00 0.00 744.00
April 78.39 42.52 35.87 68.91 32.97 0.00 0.00 720.00
May 65.85 22.44 43.40 61.87 14.92 0.00 0.00 744.00
June 59.07 15.67 43.40 60.64 8.28 0.00 0.00 720.00
July 64.58 20.38 44.20 68.58 6.95 0.00 0.00 744.00
August 69.02 28.83 40.19 73.91 8.91 0.00 0.00 744.00
September 74.02 39.42 34.59 77.30 18.34 0.00 0.00 720.00
October 63.25 37.22 26.03 61.19 32.33 0.00 0.00 744.00
November 56.34 35.37 20.96 50.08 50.49 0.00 0.00 720.00
December 59.96 39.33 20.63 46.11 78.33 0.00 0.00 744.00
                 
Annual Sum or Average 70.92 37.87 33.05 66.45 37.71 0.00 0.00 8760.00
Minimum of Months 56.34 15.67 20.63 46.11 6.95 0.00 0.00 672.00
Maximum of Months 98.35 66.46 44.20 90.12 80.37 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 8600DD

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.67 54.05 23.62 63.32 86.58 0.00 0.00 744.00
February 98.35 66.46 31.89 88.14 73.23 0.00 0.00 672.00
March 86.64 54.85 31.79 73.84 60.80 0.00 0.00 744.00
April 78.39 42.52 35.87 66.69 37.58 0.00 0.00 720.00
May 65.85 22.44 43.40 59.20 17.94 0.00 0.00 744.00
June 59.07 15.67 43.40 57.64 10.69 0.00 0.00 720.00
July 64.58 20.38 44.20 65.94 9.07 0.00 0.00 744.00
August 69.02 28.83 40.19 71.81 11.38 0.00 0.00 744.00
September 74.02 39.42 34.59 75.65 21.33 0.00 0.00 720.00
October 63.25 37.22 26.03 59.76 36.14 0.00 0.00 744.00
November 56.34 35.37 20.96 48.79 55.52 0.00 0.00 720.00
December 59.96 39.33 20.63 44.83 84.96 0.00 0.00 744.00
                 
Annual Sum or Average 70.92 37.87 33.05 64.47 41.96 0.00 0.00 8760.00
Minimum of Months 56.34 15.67 20.63 44.83 9.07 0.00 0.00 672.00
Maximum of Months 98.35 66.46 44.20 88.14 86.58 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: A1ED60

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.09 0.00 14.09 0.05 124.97 0.00 0.00 744.00
February 21.64 0.00 21.64 1.06 98.45 0.00 0.00 672.00
March 26.62 0.00 26.62 3.45 73.43 0.00 0.00 744.00
April 34.89 0.27 34.63 16.33 39.92 0.00 0.00 720.00
May 49.06 2.61 46.44 43.39 16.50 0.00 0.00 744.00
June 54.74 5.98 48.76 57.92 9.31 0.00 0.00 720.00
July 52.29 4.45 47.84 58.18 8.51 0.00 0.00 744.00
August 39.73 0.67 39.06 41.78 10.98 0.00 0.00 744.00
September 30.97 0.01 30.96 24.50 22.38 0.00 0.00 720.00
October 21.50 0.00 21.50 7.55 41.52 0.00 0.00 744.00
November 14.24 0.00 14.24 0.91 71.97 0.00 0.00 720.00
December 11.94 0.00 11.94 0.00 120.06 0.00 0.00 744.00
                 
Annual Sum or Average 31.02 1.17 29.85 21.38 52.98 0.00 0.00 8760.00
Minimum of Months 11.94 0.00 11.94 0.00 8.51 0.00 0.00 672.00
Maximum of Months 54.74 5.98 48.76 58.18 124.97 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: E8D997

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.09 0.00 14.09 0.05 124.97 0.00 0.00 744.00
February 21.64 0.00 21.64 1.06 98.45 0.00 0.00 672.00
March 26.62 0.00 26.62 3.45 73.43 0.00 0.00 744.00
April 34.89 0.27 34.63 16.33 39.92 0.00 0.00 720.00
May 49.06 2.61 46.44 43.39 16.50 0.00 0.00 744.00
June 54.74 5.98 48.76 57.92 9.31 0.00 0.00 720.00
July 52.29 4.45 47.84 58.18 8.51 0.00 0.00 744.00
August 39.73 0.67 39.06 41.78 10.98 0.00 0.00 744.00
September 30.97 0.01 30.96 24.50 22.38 0.00 0.00 720.00
October 21.50 0.00 21.50 7.55 41.52 0.00 0.00 744.00
November 14.24 0.00 14.24 0.91 71.97 0.00 0.00 720.00
December 11.94 0.00 11.94 0.00 120.06 0.00 0.00 744.00
                 
Annual Sum or Average 31.02 1.17 29.85 21.38 52.98 0.00 0.00 8760.00
Minimum of Months 11.94 0.00 11.94 0.00 8.51 0.00 0.00 672.00
Maximum of Months 54.74 5.98 48.76 58.18 124.97 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 88E1FC

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.09 0.00 14.09 0.05 124.97 0.00 0.00 744.00
February 21.64 0.00 21.64 1.06 98.45 0.00 0.00 672.00
March 26.62 0.00 26.62 3.45 73.43 0.00 0.00 744.00
April 34.89 0.27 34.63 16.33 39.92 0.00 0.00 720.00
May 49.06 2.61 46.44 43.39 16.50 0.00 0.00 744.00
June 54.74 5.98 48.76 57.92 9.31 0.00 0.00 720.00
July 52.29 4.45 47.84 58.18 8.51 0.00 0.00 744.00
August 39.73 0.67 39.06 41.78 10.98 0.00 0.00 744.00
September 30.97 0.01 30.96 24.50 22.38 0.00 0.00 720.00
October 21.50 0.00 21.50 7.55 41.52 0.00 0.00 744.00
November 14.24 0.00 14.24 0.91 71.97 0.00 0.00 720.00
December 11.94 0.00 11.94 0.00 120.06 0.00 0.00 744.00
                 
Annual Sum or Average 31.02 1.17 29.85 21.38 52.98 0.00 0.00 8760.00
Minimum of Months 11.94 0.00 11.94 0.00 8.51 0.00 0.00 672.00
Maximum of Months 54.74 5.98 48.76 58.18 124.97 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: F83F33

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.93 13.74 19.19 8.05 128.04 0.00 0.00 744.00
February 51.76 22.07 29.69 22.82 100.18 0.00 0.00 672.00
March 70.55 35.40 35.16 46.73 76.84 0.00 0.00 744.00
April 97.82 52.78 45.04 86.89 44.16 0.00 0.00 720.00
May 105.85 46.54 59.31 111.29 20.99 0.00 0.00 744.00
June 119.83 57.33 62.50 138.51 13.20 0.00 0.00 720.00
July 117.39 55.13 62.26 138.83 11.88 0.00 0.00 744.00
August 90.51 39.57 50.94 101.86 15.08 0.00 0.00 744.00
September 72.49 32.46 40.03 70.93 27.08 0.00 0.00 720.00
October 43.88 16.64 27.24 29.16 46.65 0.00 0.00 744.00
November 27.93 9.33 18.60 9.39 76.83 0.00 0.00 720.00
December 25.48 9.41 16.07 4.86 125.34 0.00 0.00 744.00
                 
Annual Sum or Average 71.44 32.56 38.88 64.31 57.02 0.00 0.00 8760.00
Minimum of Months 25.48 9.33 16.07 4.86 11.88 0.00 0.00 672.00
Maximum of Months 119.83 57.33 62.50 138.83 128.04 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: B1F5EE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.47 10.31 14.16 6.09 95.29 0.00 0.00 744.00
February 38.48 16.55 21.92 17.17 74.29 0.00 0.00 672.00
March 52.51 26.55 25.96 35.11 56.90 0.00 0.00 744.00
April 72.87 39.58 33.29 65.30 32.47 0.00 0.00 720.00
May 78.71 34.90 43.81 83.37 15.35 0.00 0.00 744.00
June 89.20 43.00 46.20 103.73 9.69 0.00 0.00 720.00
July 87.39 41.35 46.04 103.71 8.81 0.00 0.00 744.00
August 67.31 29.68 37.63 76.19 10.99 0.00 0.00 744.00
September 53.89 24.34 29.54 53.02 19.98 0.00 0.00 720.00
October 32.55 12.48 20.07 21.81 34.48 0.00 0.00 744.00
November 20.70 7.00 13.70 7.05 56.85 0.00 0.00 720.00
December 18.91 7.06 11.85 3.68 93.19 0.00 0.00 744.00
                 
Annual Sum or Average 53.14 24.42 28.72 48.17 42.23 0.00 0.00 8760.00
Minimum of Months 18.91 7.00 11.85 3.68 8.81 0.00 0.00 672.00
Maximum of Months 89.20 43.00 46.20 103.73 95.29 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: F52F3D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.70 10.31 14.39 5.96 96.75 0.00 0.00 744.00
February 38.82 16.55 22.26 16.66 76.34 0.00 0.00 672.00
March 52.92 26.55 26.37 34.25 59.42 0.00 0.00 744.00
April 73.36 39.58 33.78 63.85 34.30 0.00 0.00 720.00
May 79.39 34.90 44.48 82.59 16.12 0.00 0.00 744.00
June 89.87 43.00 46.87 103.62 9.82 0.00 0.00 720.00
July 88.04 41.35 46.70 104.49 8.27 0.00 0.00 744.00
August 67.88 29.68 38.21 76.44 10.50 0.00 0.00 744.00
September 54.37 24.34 30.02 52.58 20.07 0.00 0.00 720.00
October 32.91 12.48 20.43 21.27 34.85 0.00 0.00 744.00
November 20.95 7.00 13.95 6.87 57.40 0.00 0.00 720.00
December 19.11 7.06 12.05 3.61 93.90 0.00 0.00 744.00
                 
Annual Sum or Average 53.58 24.42 29.16 47.84 43.01 0.00 0.00 8760.00
Minimum of Months 19.11 7.00 12.05 3.61 8.27 0.00 0.00 672.00
Maximum of Months 89.87 43.00 46.87 104.49 96.75 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 80885D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 233.00 162.15 70.85 189.12 249.07 0.00 0.00 744.00
February 295.06 199.38 95.68 262.47 210.02 0.00 0.00 672.00
March 259.92 164.56 95.37 219.37 175.79 0.00 0.00 744.00
April 235.17 127.57 107.60 197.38 109.99 0.00 0.00 720.00
May 197.54 67.33 130.21 174.77 53.26 0.00 0.00 744.00
June 177.22 47.01 130.21 169.94 31.66 0.00 0.00 720.00
July 193.75 61.15 132.61 195.57 26.28 0.00 0.00 744.00
August 207.06 86.48 120.58 213.10 32.83 0.00 0.00 744.00
September 222.06 118.27 103.78 224.18 62.52 0.00 0.00 720.00
October 189.76 111.67 78.09 177.74 104.24 0.00 0.00 744.00
November 169.01 106.12 62.89 145.54 157.55 0.00 0.00 720.00
December 179.89 118.00 61.89 134.37 242.06 0.00 0.00 744.00
                 
Annual Sum or Average 212.75 113.60 99.15 191.47 120.88 0.00 0.00 8760.00
Minimum of Months 169.01 47.01 61.89 134.37 26.28 0.00 0.00 672.00
Maximum of Months 295.06 199.38 132.61 262.47 249.07 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: FEEF06

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.67 54.05 23.62 64.23 81.66 0.00 0.00 744.00
February 98.35 66.46 31.89 89.01 68.53 0.00 0.00 672.00
March 86.64 54.85 31.79 74.49 57.09 0.00 0.00 744.00
April 78.39 42.52 35.87 67.05 35.79 0.00 0.00 720.00
May 65.85 22.44 43.40 59.29 17.31 0.00 0.00 744.00
June 59.07 15.67 43.40 57.93 10.01 0.00 0.00 720.00
July 64.58 20.38 44.20 66.29 8.40 0.00 0.00 744.00
August 69.02 28.83 40.19 72.27 10.28 0.00 0.00 744.00
September 74.02 39.42 34.59 76.05 19.92 0.00 0.00 720.00
October 63.25 37.22 26.03 60.38 33.49 0.00 0.00 744.00
November 56.34 35.37 20.96 49.52 51.19 0.00 0.00 720.00
December 59.96 39.33 20.63 45.65 79.25 0.00 0.00 744.00
                 
Annual Sum or Average 70.92 37.87 33.05 65.01 39.28 0.00 0.00 8760.00
Minimum of Months 56.34 15.67 20.63 45.65 8.40 0.00 0.00 672.00
Maximum of Months 98.35 66.46 44.20 89.01 81.66 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 2BE8DE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.78 10.45 13.33 7.37 96.40 0.00 0.00 744.00
February 38.86 18.58 20.28 20.70 77.23 0.00 0.00 672.00
March 51.32 27.41 23.91 36.07 59.98 0.00 0.00 744.00
April 65.62 34.66 30.95 57.68 35.25 0.00 0.00 720.00
May 79.81 39.68 40.13 86.33 16.63 0.00 0.00 744.00
June 73.76 32.50 41.26 85.74 9.79 0.00 0.00 720.00
July 80.57 38.62 41.95 96.65 8.09 0.00 0.00 744.00
August 68.00 32.39 35.61 78.37 9.94 0.00 0.00 744.00
September 53.14 25.03 28.10 53.59 19.67 0.00 0.00 720.00
October 33.43 14.12 19.31 24.20 34.44 0.00 0.00 744.00
November 20.17 7.20 12.98 7.66 56.59 0.00 0.00 720.00
December 18.06 6.66 11.40 3.69 92.79 0.00 0.00 744.00
                 
Annual Sum or Average 50.61 23.98 26.63 46.67 42.93 0.00 0.00 8760.00
Minimum of Months 18.06 6.66 11.40 3.69 8.09 0.00 0.00 672.00
Maximum of Months 80.57 39.68 41.95 96.65 96.40 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 513E2A

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.06 10.45 11.61 7.19 97.34 0.00 0.00 744.00
February 36.38 18.58 17.80 19.97 78.42 0.00 0.00 672.00
March 48.45 27.41 21.04 34.93 61.07 0.00 0.00 744.00
April 59.48 32.54 26.94 52.22 36.02 0.00 0.00 720.00
May 64.05 30.65 33.40 67.66 16.84 0.00 0.00 744.00
June 59.99 25.30 34.69 69.16 9.54 0.00 0.00 720.00
July 66.49 30.89 35.60 79.52 7.64 0.00 0.00 744.00
August 59.05 28.54 30.51 67.95 9.66 0.00 0.00 744.00
September 49.57 24.98 24.59 50.07 19.39 0.00 0.00 720.00
October 30.72 14.12 16.60 22.28 34.73 0.00 0.00 744.00
November 18.34 7.20 11.15 7.20 57.35 0.00 0.00 720.00
December 16.51 6.66 9.86 3.61 93.62 0.00 0.00 744.00
                 
Annual Sum or Average 44.30 21.46 22.84 40.26 43.32 0.00 0.00 8760.00
Minimum of Months 16.51 6.66 9.86 3.61 7.64 0.00 0.00 672.00
Maximum of Months 66.49 32.54 35.60 79.52 97.34 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: BA5CD9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.23 10.45 12.78 7.30 96.90 0.00 0.00 744.00
February 38.06 18.58 19.48 20.45 77.78 0.00 0.00 672.00
March 50.40 27.41 22.99 35.67 60.34 0.00 0.00 744.00
April 64.50 34.66 29.84 56.85 35.32 0.00 0.00 720.00
May 74.01 36.35 37.67 79.56 16.88 0.00 0.00 744.00
June 68.23 29.34 38.89 79.00 9.74 0.00 0.00 720.00
July 74.97 35.33 39.64 89.75 7.97 0.00 0.00 744.00
August 65.72 31.67 34.05 75.82 9.87 0.00 0.00 744.00
September 52.01 25.03 26.98 52.46 19.57 0.00 0.00 720.00
October 32.56 14.12 18.44 23.53 34.56 0.00 0.00 744.00
November 19.58 7.20 12.39 7.50 56.93 0.00 0.00 720.00
December 17.56 6.66 10.90 3.67 93.21 0.00 0.00 744.00
                 
Annual Sum or Average 48.46 23.09 25.37 44.44 43.11 0.00 0.00 8760.00
Minimum of Months 17.56 6.66 10.90 3.67 7.97 0.00 0.00 672.00
Maximum of Months 74.97 36.35 39.64 89.75 96.90 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 1AD478

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 129.44 90.08 39.36 105.94 140.50 0.00 0.00 744.00
February 163.92 110.77 53.16 147.42 117.76 0.00 0.00 672.00
March 144.40 91.42 52.98 123.70 97.69 0.00 0.00 744.00
April 130.65 70.87 59.78 112.19 60.13 0.00 0.00 720.00
May 109.75 37.41 72.34 100.69 27.76 0.00 0.00 744.00
June 98.46 26.12 72.34 99.07 15.65 0.00 0.00 720.00
July 107.64 33.97 73.67 113.53 12.48 0.00 0.00 744.00
August 115.03 48.04 66.99 122.72 15.61 0.00 0.00 744.00
September 123.36 65.71 57.66 127.79 32.60 0.00 0.00 720.00
October 105.42 62.04 43.38 100.68 56.85 0.00 0.00 744.00
November 93.89 58.95 34.94 81.94 88.12 0.00 0.00 720.00
December 99.94 65.56 34.38 75.20 136.56 0.00 0.00 744.00
                 
Annual Sum or Average 118.19 63.11 55.08 108.97 66.58 0.00 0.00 8760.00
Minimum of Months 93.89 26.12 34.38 75.20 12.48 0.00 0.00 672.00
Maximum of Months 163.92 110.77 73.67 147.42 140.50 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 27F0AC

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 207.11 144.13 62.98 169.36 224.70 0.00 0.00 744.00
February 262.28 177.23 85.05 235.68 188.17 0.00 0.00 672.00
March 231.04 146.27 84.77 197.86 155.71 0.00 0.00 744.00
April 209.04 113.40 95.64 179.73 95.20 0.00 0.00 720.00
May 175.59 59.85 115.74 161.83 43.26 0.00 0.00 744.00
June 157.53 41.79 115.74 159.44 24.12 0.00 0.00 720.00
July 172.22 54.35 117.87 182.72 18.94 0.00 0.00 744.00
August 184.05 76.87 107.18 197.19 23.78 0.00 0.00 744.00
September 197.38 105.13 92.25 204.95 50.95 0.00 0.00 720.00
October 168.67 99.26 69.41 161.34 89.97 0.00 0.00 744.00
November 150.23 94.33 55.91 131.13 140.43 0.00 0.00 720.00
December 159.90 104.89 55.01 120.26 218.32 0.00 0.00 744.00
                 
Annual Sum or Average 189.11 100.98 88.14 174.70 105.77 0.00 0.00 8760.00
Minimum of Months 150.23 41.79 55.01 120.26 18.94 0.00 0.00 672.00
Maximum of Months 262.28 177.23 117.87 235.68 224.70 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 724114

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.67 54.05 23.62 62.85 84.00 0.00 0.00 744.00
February 98.35 66.46 31.89 87.33 70.66 0.00 0.00 672.00
March 86.64 54.85 31.79 73.17 58.80 0.00 0.00 744.00
April 78.39 42.52 35.87 66.19 36.28 0.00 0.00 720.00
May 65.85 22.44 43.40 59.29 16.89 0.00 0.00 744.00
June 59.07 15.67 43.40 58.21 9.65 0.00 0.00 720.00
July 64.58 20.38 44.20 66.85 7.78 0.00 0.00 744.00
August 69.02 28.83 40.19 72.23 9.83 0.00 0.00 744.00
September 74.02 39.42 34.59 75.39 20.01 0.00 0.00 720.00
October 63.25 37.22 26.03 59.47 34.43 0.00 0.00 744.00
November 56.34 35.37 20.96 48.52 52.84 0.00 0.00 720.00
December 59.96 39.33 20.63 44.62 81.58 0.00 0.00 744.00
                 
Annual Sum or Average 70.92 37.87 33.05 64.35 40.09 0.00 0.00 8760.00
Minimum of Months 56.34 15.67 20.63 44.62 7.78 0.00 0.00 672.00
Maximum of Months 98.35 66.46 44.20 87.33 84.00 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: D538C4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.90 13.74 19.16 7.99 129.14 0.00 0.00 744.00
February 51.71 22.07 29.64 22.57 100.92 0.00 0.00 672.00
March 70.49 35.40 35.09 46.17 77.95 0.00 0.00 744.00
April 97.74 52.78 44.97 85.82 45.21 0.00 0.00 720.00
May 105.75 46.54 59.21 110.69 21.15 0.00 0.00 744.00
June 119.73 57.33 62.40 138.64 12.85 0.00 0.00 720.00
July 117.29 55.13 62.16 139.90 10.79 0.00 0.00 744.00
August 90.42 39.57 50.85 103.10 13.37 0.00 0.00 744.00
September 72.42 32.46 39.96 71.25 26.06 0.00 0.00 720.00
October 43.83 16.64 27.19 29.21 45.99 0.00 0.00 744.00
November 27.89 9.33 18.56 9.40 76.33 0.00 0.00 720.00
December 25.45 9.41 16.04 4.81 125.65 0.00 0.00 744.00
                 
Annual Sum or Average 71.37 32.56 38.81 64.34 56.94 0.00 0.00 8760.00
Minimum of Months 25.45 9.33 16.04 4.81 10.79 0.00 0.00 672.00
Maximum of Months 119.73 57.33 62.40 139.90 129.14 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 5635BC

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.13 13.74 18.39 7.89 129.41 0.00 0.00 744.00
February 50.59 22.07 28.52 22.10 101.21 0.00 0.00 672.00
March 69.17 35.40 33.77 45.47 78.28 0.00 0.00 744.00
April 96.13 52.78 43.36 84.47 45.21 0.00 0.00 720.00
May 103.54 46.54 57.00 108.41 20.94 0.00 0.00 744.00
June 117.53 57.33 60.20 136.36 12.68 0.00 0.00 720.00
July 115.14 55.13 60.01 137.69 10.56 0.00 0.00 744.00
August 88.53 39.57 48.96 101.12 13.18 0.00 0.00 744.00
September 70.84 32.46 38.38 69.64 25.88 0.00 0.00 720.00
October 42.65 16.64 26.01 28.27 45.96 0.00 0.00 744.00
November 27.10 9.33 17.76 9.16 76.54 0.00 0.00 720.00
December 24.78 9.41 15.37 4.77 125.89 0.00 0.00 744.00
                 
Annual Sum or Average 69.92 32.56 37.36 63.15 56.97 0.00 0.00 8760.00
Minimum of Months 24.78 9.33 15.37 4.77 10.56 0.00 0.00 672.00
Maximum of Months 117.53 57.33 60.20 137.69 129.41 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 831C1D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 21.13 0.00 21.13 0.04 197.27 0.00 0.00 744.00
February 32.46 0.00 32.46 1.28 156.92 0.00 0.00 672.00
March 39.93 0.00 39.93 4.30 119.12 0.00 0.00 744.00
April 52.34 0.40 51.94 22.26 66.81 0.00 0.00 720.00
May 73.59 3.92 69.67 62.64 28.55 0.00 0.00 744.00
June 82.11 8.97 73.14 85.34 16.28 0.00 0.00 720.00
July 78.43 6.68 71.75 87.88 13.44 0.00 0.00 744.00
August 59.60 1.01 58.59 63.09 17.13 0.00 0.00 744.00
September 46.43 0.01 46.42 36.01 36.42 0.00 0.00 720.00
October 32.26 0.00 32.26 10.58 66.75 0.00 0.00 744.00
November 21.36 0.00 21.36 1.24 114.04 0.00 0.00 720.00
December 17.90 0.00 17.90 0.00 188.61 0.00 0.00 744.00
                 
Annual Sum or Average 46.53 1.76 44.78 31.41 84.81 0.00 0.00 8760.00
Minimum of Months 17.90 0.00 17.90 0.00 13.44 0.00 0.00 672.00
Maximum of Months 82.11 8.97 73.14 87.88 197.27 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 9BB95F

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.09 0.00 14.09 0.02 133.11 0.00 0.00 744.00
February 21.64 0.00 21.64 0.83 106.11 0.00 0.00 672.00
March 26.62 0.00 26.62 2.85 80.67 0.00 0.00 744.00
April 34.86 0.25 34.60 14.87 45.27 0.00 0.00 720.00
May 49.06 2.61 46.44 42.19 19.10 0.00 0.00 744.00
June 54.74 5.98 48.76 57.64 10.75 0.00 0.00 720.00
July 52.29 4.45 47.84 59.46 8.70 0.00 0.00 744.00
August 39.73 0.67 39.06 42.72 11.16 0.00 0.00 744.00
September 30.94 0.00 30.94 24.30 24.31 0.00 0.00 720.00
October 21.50 0.00 21.50 7.11 44.98 0.00 0.00 744.00
November 14.24 0.00 14.24 0.83 77.10 0.00 0.00 720.00
December 11.94 0.00 11.94 0.00 127.39 0.00 0.00 744.00
                 
Annual Sum or Average 31.02 1.17 29.85 21.20 57.18 0.00 0.00 8760.00
Minimum of Months 11.94 0.00 11.94 0.00 8.70 0.00 0.00 672.00
Maximum of Months 54.74 5.98 48.76 59.46 133.11 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: C0778D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.09 0.00 14.09 0.02 133.11 0.00 0.00 744.00
February 21.64 0.00 21.64 0.83 106.11 0.00 0.00 672.00
March 26.62 0.00 26.62 2.85 80.67 0.00 0.00 744.00
April 34.83 0.25 34.59 14.86 45.30 0.00 0.00 720.00
May 49.06 2.61 46.44 42.19 19.10 0.00 0.00 744.00
June 54.74 5.98 48.76 57.64 10.75 0.00 0.00 720.00
July 52.29 4.45 47.84 59.46 8.70 0.00 0.00 744.00
August 39.73 0.67 39.06 42.72 11.16 0.00 0.00 744.00
September 30.94 0.00 30.94 24.30 24.31 0.00 0.00 720.00
October 21.50 0.00 21.50 7.11 44.98 0.00 0.00 744.00
November 14.24 0.00 14.24 0.83 77.10 0.00 0.00 720.00
December 11.94 0.00 11.94 0.00 127.39 0.00 0.00 744.00
                 
Annual Sum or Average 31.02 1.17 29.85 21.20 57.19 0.00 0.00 8760.00
Minimum of Months 11.94 0.00 11.94 0.00 8.70 0.00 0.00 672.00
Maximum of Months 54.74 5.98 48.76 59.46 133.11 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 7D2D69

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.09 0.00 14.09 0.02 132.36 0.00 0.00 744.00
February 21.64 0.00 21.64 0.81 105.60 0.00 0.00 672.00
March 26.62 0.00 26.62 2.75 80.53 0.00 0.00 744.00
April 34.77 0.22 34.55 14.43 45.74 0.00 0.00 720.00
May 49.05 2.61 46.44 41.14 19.75 0.00 0.00 744.00
June 54.74 5.98 48.76 56.21 11.38 0.00 0.00 720.00
July 52.28 4.45 47.83 58.04 9.37 0.00 0.00 744.00
August 39.63 0.63 39.00 41.49 11.98 0.00 0.00 744.00
September 30.94 0.00 30.94 23.57 25.15 0.00 0.00 720.00
October 21.50 0.00 21.50 6.79 45.64 0.00 0.00 744.00
November 14.24 0.00 14.24 0.78 77.27 0.00 0.00 720.00
December 11.94 0.00 11.94 0.00 126.76 0.00 0.00 744.00
                 
Annual Sum or Average 31.00 1.16 29.84 20.63 57.43 0.00 0.00 8760.00
Minimum of Months 11.94 0.00 11.94 0.00 9.37 0.00 0.00 672.00
Maximum of Months 54.74 5.98 48.76 58.04 132.36 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 2EF63B

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.09 0.00 14.09 0.02 132.36 0.00 0.00 744.00
February 21.64 0.00 21.64 0.81 105.60 0.00 0.00 672.00
March 26.62 0.00 26.62 2.75 80.53 0.00 0.00 744.00
April 34.71 0.20 34.51 14.43 45.79 0.00 0.00 720.00
May 48.97 2.56 46.41 41.05 19.76 0.00 0.00 744.00
June 54.74 5.98 48.76 56.21 11.38 0.00 0.00 720.00
July 52.28 4.45 47.83 58.03 9.37 0.00 0.00 744.00
August 39.55 0.60 38.95 41.39 11.98 0.00 0.00 744.00
September 30.94 0.00 30.94 23.57 25.15 0.00 0.00 720.00
October 21.50 0.00 21.50 6.79 45.64 0.00 0.00 744.00
November 14.24 0.00 14.24 0.78 77.27 0.00 0.00 720.00
December 11.94 0.00 11.94 0.00 126.76 0.00 0.00 744.00
                 
Annual Sum or Average 30.98 1.15 29.83 20.61 57.43 0.00 0.00 8760.00
Minimum of Months 11.94 0.00 11.94 0.00 9.37 0.00 0.00 672.00
Maximum of Months 54.74 5.98 48.76 58.03 132.36 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: C417C0

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.92 0.00 13.92 0.02 133.50 0.00 0.00 744.00
February 21.38 0.00 21.38 0.76 106.67 0.00 0.00 672.00
March 26.31 0.00 26.31 2.64 81.37 0.00 0.00 744.00
April 34.20 0.13 34.07 14.20 46.22 0.00 0.00 720.00
May 47.70 2.10 45.60 40.32 19.74 0.00 0.00 744.00
June 53.47 5.59 47.88 55.57 11.23 0.00 0.00 720.00
July 50.95 4.00 46.94 57.31 9.20 0.00 0.00 744.00
August 38.80 0.44 38.36 41.03 11.85 0.00 0.00 744.00
September 30.58 0.00 30.58 23.39 25.18 0.00 0.00 720.00
October 21.25 0.00 21.25 6.64 45.95 0.00 0.00 744.00
November 14.07 0.00 14.07 0.76 78.00 0.00 0.00 720.00
December 11.79 0.00 11.79 0.00 127.87 0.00 0.00 744.00
                 
Annual Sum or Average 30.41 1.03 29.39 20.34 57.86 0.00 0.00 8760.00
Minimum of Months 11.79 0.00 11.79 0.00 9.20 0.00 0.00 672.00
Maximum of Months 53.47 5.59 47.88 57.31 133.50 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: EB042B

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.70 10.31 14.39 5.95 97.16 0.00 0.00 744.00
February 38.82 16.55 22.26 16.80 76.60 0.00 0.00 672.00
March 52.92 26.55 26.37 34.21 60.09 0.00 0.00 744.00
April 73.36 39.58 33.78 63.39 35.70 0.00 0.00 720.00
May 79.39 34.90 44.48 81.22 17.62 0.00 0.00 744.00
June 89.87 43.00 46.87 101.81 11.32 0.00 0.00 720.00
July 88.04 41.35 46.70 102.71 9.85 0.00 0.00 744.00
August 67.88 29.68 38.21 75.42 12.12 0.00 0.00 744.00
September 54.37 24.34 30.02 52.19 21.50 0.00 0.00 720.00
October 32.91 12.48 20.43 21.28 36.28 0.00 0.00 744.00
November 20.95 7.00 13.95 6.86 58.55 0.00 0.00 720.00
December 19.11 7.06 12.05 3.59 94.68 0.00 0.00 744.00
                 
Annual Sum or Average 53.58 24.42 29.16 47.27 44.16 0.00 0.00 8760.00
Minimum of Months 19.11 7.00 12.05 3.59 9.85 0.00 0.00 672.00
Maximum of Months 89.87 43.00 46.87 102.71 97.16 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 4C1F71

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.70 10.31 14.39 5.95 97.16 0.00 0.00 744.00
February 38.82 16.55 22.26 16.80 76.60 0.00 0.00 672.00
March 52.92 26.55 26.37 34.21 60.08 0.00 0.00 744.00
April 73.36 39.58 33.78 63.39 35.70 0.00 0.00 720.00
May 79.39 34.90 44.48 81.23 17.62 0.00 0.00 744.00
June 89.87 43.00 46.87 101.81 11.32 0.00 0.00 720.00
July 88.04 41.35 46.70 102.71 9.85 0.00 0.00 744.00
August 67.88 29.68 38.21 75.42 12.12 0.00 0.00 744.00
September 54.37 24.34 30.02 52.19 21.50 0.00 0.00 720.00
October 32.91 12.48 20.43 21.28 36.28 0.00 0.00 744.00
November 20.95 7.00 13.95 6.86 58.55 0.00 0.00 720.00
December 19.11 7.06 12.05 3.59 94.68 0.00 0.00 744.00
                 
Annual Sum or Average 53.58 24.42 29.16 47.27 44.16 0.00 0.00 8760.00
Minimum of Months 19.11 7.00 12.05 3.59 9.85 0.00 0.00 672.00
Maximum of Months 89.87 43.00 46.87 102.71 97.16 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: D23C8B

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.70 10.31 14.39 5.95 97.16 0.00 0.00 744.00
February 38.82 16.55 22.26 16.80 76.60 0.00 0.00 672.00
March 52.92 26.55 26.37 34.21 60.09 0.00 0.00 744.00
April 73.36 39.58 33.78 63.39 35.70 0.00 0.00 720.00
May 79.39 34.90 44.48 81.22 17.62 0.00 0.00 744.00
June 89.87 43.00 46.87 101.81 11.32 0.00 0.00 720.00
July 88.04 41.35 46.70 102.71 9.85 0.00 0.00 744.00
August 67.88 29.68 38.21 75.42 12.12 0.00 0.00 744.00
September 54.37 24.34 30.02 52.19 21.50 0.00 0.00 720.00
October 32.91 12.48 20.43 21.28 36.28 0.00 0.00 744.00
November 20.95 7.00 13.95 6.86 58.55 0.00 0.00 720.00
December 19.11 7.06 12.05 3.59 94.68 0.00 0.00 744.00
                 
Annual Sum or Average 53.58 24.42 29.16 47.27 44.16 0.00 0.00 8760.00
Minimum of Months 19.11 7.00 12.05 3.59 9.85 0.00 0.00 672.00
Maximum of Months 89.87 43.00 46.87 102.71 97.16 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: B4E4BE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.70 10.31 14.39 5.95 97.16 0.00 0.00 744.00
February 38.82 16.55 22.26 16.80 76.60 0.00 0.00 672.00
March 52.92 26.55 26.37 34.21 60.09 0.00 0.00 744.00
April 73.36 39.58 33.78 63.39 35.70 0.00 0.00 720.00
May 79.39 34.90 44.48 81.22 17.62 0.00 0.00 744.00
June 89.87 43.00 46.87 101.81 11.32 0.00 0.00 720.00
July 88.04 41.35 46.70 102.71 9.85 0.00 0.00 744.00
August 67.88 29.68 38.21 75.42 12.12 0.00 0.00 744.00
September 54.37 24.34 30.02 52.19 21.50 0.00 0.00 720.00
October 32.91 12.48 20.43 21.28 36.28 0.00 0.00 744.00
November 20.95 7.00 13.95 6.86 58.55 0.00 0.00 720.00
December 19.11 7.06 12.05 3.59 94.68 0.00 0.00 744.00
                 
Annual Sum or Average 53.58 24.42 29.16 47.27 44.16 0.00 0.00 8760.00
Minimum of Months 19.11 7.00 12.05 3.59 9.85 0.00 0.00 672.00
Maximum of Months 89.87 43.00 46.87 102.71 97.16 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: EEF55D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 221.17 154.58 66.59 182.77 259.31 0.00 0.00 744.00
February 271.87 184.03 87.84 247.79 224.79 0.00 0.00 672.00
March 244.02 154.63 89.39 211.35 185.57 0.00 0.00 744.00
April 228.64 125.98 102.67 193.19 116.59 0.00 0.00 720.00
May 191.93 67.30 124.63 167.54 58.14 0.00 0.00 744.00
June 171.45 47.01 124.44 162.09 35.76 0.00 0.00 720.00
July 187.94 61.12 126.82 186.95 30.67 0.00 0.00 744.00
August 201.38 86.08 115.30 205.75 37.57 0.00 0.00 744.00
September 212.88 114.51 98.37 216.10 68.58 0.00 0.00 720.00
October 175.53 102.82 72.71 165.79 113.03 0.00 0.00 744.00
November 159.06 100.31 58.76 138.56 167.38 0.00 0.00 720.00
December 172.60 113.45 59.15 130.13 250.32 0.00 0.00 744.00
                 
Annual Sum or Average 202.75 108.84 93.92 183.55 128.54 0.00 0.00 8760.00
Minimum of Months 159.06 47.01 58.76 130.13 30.67 0.00 0.00 672.00
Maximum of Months 271.87 184.03 126.82 247.79 259.31 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: E55A57

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 90.25 61.84 28.42 72.89 137.38 0.00 0.00 744.00
February 115.06 76.79 38.27 102.14 116.95 0.00 0.00 672.00
March 106.60 66.61 39.99 90.45 95.71 0.00 0.00 744.00
April 102.68 56.20 46.48 87.55 59.43 0.00 0.00 720.00
May 88.62 31.97 56.65 77.16 28.98 0.00 0.00 744.00
June 79.62 22.74 56.88 75.13 17.70 0.00 0.00 720.00
July 87.35 29.35 58.00 87.24 14.94 0.00 0.00 744.00
August 92.13 39.87 52.26 95.16 18.49 0.00 0.00 744.00
September 93.64 49.52 44.12 94.86 34.28 0.00 0.00 720.00
October 76.02 43.79 32.22 69.81 57.46 0.00 0.00 744.00
November 65.95 40.67 25.28 55.88 87.19 0.00 0.00 720.00
December 70.39 45.36 25.03 52.14 132.72 0.00 0.00 744.00
                 
Annual Sum or Average 88.85 46.87 41.98 79.87 66.54 0.00 0.00 8760.00
Minimum of Months 65.95 22.74 25.03 52.14 14.94 0.00 0.00 672.00
Maximum of Months 115.06 76.79 58.00 102.14 137.38 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 93D018

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.75 31.35 42.39 21.87 297.54 0.00 0.00 744.00
February 120.35 55.74 64.61 62.13 240.58 0.00 0.00 672.00
March 158.64 82.23 76.41 108.98 188.57 0.00 0.00 744.00
April 202.77 103.99 98.78 174.87 113.23 0.00 0.00 720.00
May 248.79 120.30 128.48 263.88 56.09 0.00 0.00 744.00
June 239.94 105.24 134.70 272.63 34.74 0.00 0.00 720.00
July 256.45 120.78 135.66 300.62 30.22 0.00 0.00 744.00
August 210.87 97.16 113.71 237.18 37.20 0.00 0.00 744.00
September 164.69 75.10 89.59 161.53 67.52 0.00 0.00 720.00
October 103.76 42.37 61.39 72.42 113.37 0.00 0.00 744.00
November 62.88 21.59 41.28 22.58 180.15 0.00 0.00 720.00
December 56.11 19.98 36.13 10.83 287.68 0.00 0.00 744.00
                 
Annual Sum or Average 158.46 73.09 85.37 142.95 136.81 0.00 0.00 8760.00
Minimum of Months 56.11 19.98 36.13 10.83 30.22 0.00 0.00 672.00
Maximum of Months 256.45 120.78 135.66 300.62 297.54 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: DD9F5D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.70 10.31 14.39 5.86 97.76 0.00 0.00 744.00
February 38.82 16.55 22.26 16.67 76.70 0.00 0.00 672.00
March 52.92 26.55 26.37 34.17 59.84 0.00 0.00 744.00
April 73.36 39.58 33.78 63.38 35.20 0.00 0.00 720.00
May 79.39 34.90 44.48 81.36 17.05 0.00 0.00 744.00
June 89.87 43.00 46.87 102.00 10.76 0.00 0.00 720.00
July 88.04 41.35 46.70 102.96 9.27 0.00 0.00 744.00
August 67.88 29.68 38.21 75.60 11.42 0.00 0.00 744.00
September 54.37 24.34 30.02 52.42 20.72 0.00 0.00 720.00
October 32.91 12.48 20.43 21.38 35.60 0.00 0.00 744.00
November 20.95 7.00 13.95 6.84 58.31 0.00 0.00 720.00
December 19.11 7.06 12.05 3.54 95.23 0.00 0.00 744.00
                 
Annual Sum or Average 53.58 24.42 29.16 47.33 43.86 0.00 0.00 8760.00
Minimum of Months 19.11 7.00 12.05 3.54 9.27 0.00 0.00 672.00
Maximum of Months 89.87 43.00 46.87 102.96 97.76 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 15B02B

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.79 0.00 13.79 0.01 138.02 0.00 0.00 744.00
February 21.20 0.00 21.20 0.58 111.83 0.00 0.00 672.00
March 26.10 0.00 26.10 2.11 86.59 0.00 0.00 744.00
April 33.95 0.13 33.81 12.50 50.85 0.00 0.00 720.00
May 46.05 1.25 44.80 36.28 23.85 0.00 0.00 744.00
June 51.33 4.42 46.91 49.66 14.45 0.00 0.00 720.00
July 49.08 2.98 46.10 51.37 12.69 0.00 0.00 744.00
August 38.25 0.30 37.95 37.33 16.21 0.00 0.00 744.00
September 30.32 0.00 30.32 20.92 29.90 0.00 0.00 720.00
October 21.05 0.00 21.05 5.41 51.22 0.00 0.00 744.00
November 13.93 0.00 13.93 0.60 83.71 0.00 0.00 720.00
December 11.68 0.00 11.68 0.00 132.89 0.00 0.00 744.00
                 
Annual Sum or Average 29.77 0.76 29.01 18.18 62.48 0.00 0.00 8760.00
Minimum of Months 11.68 0.00 11.68 0.00 12.69 0.00 0.00 672.00
Maximum of Months 51.33 4.42 46.91 51.37 138.02 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 820282

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.28 0.00 12.28 0.00 138.74 0.00 0.00 744.00
February 18.99 0.00 18.99 0.31 113.07 0.00 0.00 672.00
March 23.50 0.00 23.50 1.44 87.94 0.00 0.00 744.00
April 30.77 0.13 30.63 10.37 51.37 0.00 0.00 720.00
May 41.50 1.13 40.37 31.88 23.70 0.00 0.00 744.00
June 45.25 3.24 42.02 43.70 14.52 0.00 0.00 720.00
July 43.88 2.30 41.58 46.21 12.44 0.00 0.00 744.00
August 34.52 0.30 34.22 33.50 15.87 0.00 0.00 744.00
September 27.21 0.00 27.21 17.93 29.72 0.00 0.00 720.00
October 18.73 0.00 18.73 3.97 51.59 0.00 0.00 744.00
November 12.36 0.00 12.36 0.43 84.45 0.00 0.00 720.00
December 10.36 0.00 10.36 0.00 133.47 0.00 0.00 744.00
                 
Annual Sum or Average 26.65 0.59 26.06 15.91 62.86 0.00 0.00 8760.00
Minimum of Months 10.36 0.00 10.36 0.00 12.44 0.00 0.00 672.00
Maximum of Months 45.25 3.24 42.02 46.21 138.74 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 9BA05A

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.09 0.00 14.09 0.02 134.79 0.00 0.00 744.00
February 21.64 0.00 21.64 0.68 108.56 0.00 0.00 672.00
March 26.62 0.00 26.62 2.38 84.01 0.00 0.00 744.00
April 34.89 0.27 34.63 13.23 49.09 0.00 0.00 720.00
May 49.06 2.61 46.44 38.75 22.56 0.00 0.00 744.00
June 54.74 5.98 48.76 53.19 13.77 0.00 0.00 720.00
July 52.29 4.45 47.84 54.85 11.87 0.00 0.00 744.00
August 39.73 0.67 39.06 39.33 15.05 0.00 0.00 744.00
September 30.97 0.01 30.96 22.07 28.49 0.00 0.00 720.00
October 21.50 0.00 21.50 6.04 49.17 0.00 0.00 744.00
November 14.24 0.00 14.24 0.69 80.77 0.00 0.00 720.00
December 11.94 0.00 11.94 0.00 129.34 0.00 0.00 744.00
                 
Annual Sum or Average 31.02 1.17 29.85 19.39 60.42 0.00 0.00 8760.00
Minimum of Months 11.94 0.00 11.94 0.00 11.87 0.00 0.00 672.00
Maximum of Months 54.74 5.98 48.76 54.85 134.79 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: C639E8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.09 0.00 14.09 0.02 134.79 0.00 0.00 744.00
February 21.64 0.00 21.64 0.68 108.56 0.00 0.00 672.00
March 26.62 0.00 26.62 2.38 84.01 0.00 0.00 744.00
April 34.89 0.27 34.63 13.23 49.09 0.00 0.00 720.00
May 49.06 2.61 46.44 38.75 22.56 0.00 0.00 744.00
June 54.74 5.98 48.76 53.19 13.77 0.00 0.00 720.00
July 52.29 4.45 47.84 54.85 11.87 0.00 0.00 744.00
August 39.73 0.67 39.06 39.33 15.05 0.00 0.00 744.00
September 30.96 0.00 30.95 22.07 28.50 0.00 0.00 720.00
October 21.50 0.00 21.50 6.04 49.17 0.00 0.00 744.00
November 14.24 0.00 14.24 0.69 80.77 0.00 0.00 720.00
December 11.94 0.00 11.94 0.00 129.34 0.00 0.00 744.00
                 
Annual Sum or Average 31.02 1.17 29.85 19.39 60.42 0.00 0.00 8760.00
Minimum of Months 11.94 0.00 11.94 0.00 11.87 0.00 0.00 672.00
Maximum of Months 54.74 5.98 48.76 54.85 134.79 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: A2790A

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 21.13 0.00 21.13 0.04 198.92 0.00 0.00 744.00
February 32.46 0.00 32.46 1.08 158.44 0.00 0.00 672.00
March 39.93 0.00 39.93 3.67 120.83 0.00 0.00 744.00
April 52.34 0.40 51.94 20.37 67.98 0.00 0.00 720.00
May 73.59 3.92 69.67 59.32 29.32 0.00 0.00 744.00
June 82.11 8.97 73.14 81.66 16.86 0.00 0.00 720.00
July 78.43 6.68 71.75 84.41 13.88 0.00 0.00 744.00
August 59.60 1.01 58.59 60.12 17.74 0.00 0.00 744.00
September 46.43 0.01 46.42 33.84 37.23 0.00 0.00 720.00
October 32.26 0.00 32.26 9.39 67.98 0.00 0.00 744.00
November 21.36 0.00 21.36 1.01 115.63 0.00 0.00 720.00
December 17.90 0.00 17.90 0.00 190.11 0.00 0.00 744.00
                 
Annual Sum or Average 46.53 1.76 44.78 29.76 85.94 0.00 0.00 8760.00
Minimum of Months 17.90 0.00 17.90 0.00 13.88 0.00 0.00 672.00
Maximum of Months 82.11 8.97 73.14 84.41 198.92 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 79FCEE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.92 13.74 19.18 7.60 142.88 0.00 0.00 744.00
February 51.73 22.07 29.66 21.30 114.11 0.00 0.00 672.00
March 70.52 35.40 35.13 44.50 90.02 0.00 0.00 744.00
April 97.78 52.78 45.00 82.55 56.20 0.00 0.00 720.00
May 105.80 46.54 59.26 105.74 29.28 0.00 0.00 744.00
June 119.78 57.33 62.45 133.37 19.67 0.00 0.00 720.00
July 117.34 55.13 62.21 134.47 17.61 0.00 0.00 744.00
August 90.47 39.57 50.90 99.27 21.21 0.00 0.00 744.00
September 72.46 32.46 40.00 67.84 35.80 0.00 0.00 720.00
October 43.86 16.64 27.22 27.13 58.21 0.00 0.00 744.00
November 27.91 9.33 18.58 8.75 90.46 0.00 0.00 720.00
December 25.47 9.41 16.06 4.49 139.91 0.00 0.00 744.00
                 
Annual Sum or Average 71.41 32.56 38.85 61.62 67.76 0.00 0.00 8760.00
Minimum of Months 25.47 9.33 16.06 4.49 17.61 0.00 0.00 672.00
Maximum of Months 119.78 57.33 62.45 134.47 142.88 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: EDE617

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.39 13.74 18.65 7.54 143.09 0.00 0.00 744.00
February 50.94 22.07 28.87 21.00 114.39 0.00 0.00 672.00
March 69.57 35.40 34.17 43.99 90.29 0.00 0.00 744.00
April 96.60 52.78 43.82 81.57 56.25 0.00 0.00 720.00
May 104.22 46.54 57.68 104.11 29.15 0.00 0.00 744.00
June 118.16 57.33 60.83 131.68 19.57 0.00 0.00 720.00
July 115.74 55.13 60.61 132.80 17.47 0.00 0.00 744.00
August 89.09 39.57 49.52 97.81 21.09 0.00 0.00 744.00
September 71.33 32.46 38.88 66.69 35.70 0.00 0.00 720.00
October 43.06 16.64 26.42 26.50 58.22 0.00 0.00 744.00
November 27.37 9.33 18.04 8.60 90.64 0.00 0.00 720.00
December 25.02 9.41 15.60 4.47 140.10 0.00 0.00 744.00
                 
Annual Sum or Average 70.36 32.56 37.80 60.76 67.81 0.00 0.00 8760.00
Minimum of Months 25.02 9.33 15.60 4.47 17.47 0.00 0.00 672.00
Maximum of Months 118.16 57.33 60.83 132.80 143.09 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: C61F0D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.09 0.00 14.09 0.02 133.24 0.00 0.00 744.00
February 21.64 0.00 21.64 0.72 107.14 0.00 0.00 672.00
March 26.62 0.00 26.62 2.32 82.99 0.00 0.00 744.00
April 34.89 0.26 34.62 12.99 48.43 0.00 0.00 720.00
May 49.06 2.61 46.44 38.17 22.29 0.00 0.00 744.00
June 54.74 5.98 48.76 52.48 13.65 0.00 0.00 720.00
July 52.29 4.45 47.84 54.11 11.85 0.00 0.00 744.00
August 39.73 0.67 39.06 38.59 15.00 0.00 0.00 744.00
September 30.95 0.00 30.94 21.58 28.28 0.00 0.00 720.00
October 21.50 0.00 21.50 5.82 48.68 0.00 0.00 744.00
November 14.24 0.00 14.24 0.65 79.83 0.00 0.00 720.00
December 11.94 0.00 11.94 0.00 127.99 0.00 0.00 744.00
                 
Annual Sum or Average 31.02 1.17 29.85 19.07 59.75 0.00 0.00 8760.00
Minimum of Months 11.94 0.00 11.94 0.00 11.85 0.00 0.00 672.00
Maximum of Months 54.74 5.98 48.76 54.11 133.24 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 7248C5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.91 0.00 12.91 0.01 133.84 0.00 0.00 744.00
February 19.86 0.00 19.86 0.47 108.18 0.00 0.00 672.00
March 24.48 0.00 24.48 1.65 84.08 0.00 0.00 744.00
April 31.93 0.13 31.80 10.99 49.08 0.00 0.00 720.00
May 43.22 1.14 42.08 33.29 22.68 0.00 0.00 744.00
June 46.95 3.29 43.66 45.16 13.83 0.00 0.00 720.00
July 45.45 2.34 43.11 47.62 11.73 0.00 0.00 744.00
August 35.90 0.30 35.61 34.78 14.84 0.00 0.00 744.00
September 28.45 0.00 28.44 19.12 28.15 0.00 0.00 720.00
October 19.74 0.00 19.74 4.64 48.89 0.00 0.00 744.00
November 13.04 0.00 13.04 0.50 80.41 0.00 0.00 720.00
December 10.94 0.00 10.94 0.00 128.46 0.00 0.00 744.00
                 
Annual Sum or Average 27.78 0.60 27.18 16.62 60.15 0.00 0.00 8760.00
Minimum of Months 10.94 0.00 10.94 0.00 11.73 0.00 0.00 672.00
Maximum of Months 46.95 3.29 43.66 47.62 133.84 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 29FA28

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.09 0.00 14.09 0.02 133.24 0.00 0.00 744.00
February 21.64 0.00 21.64 0.72 107.14 0.00 0.00 672.00
March 26.62 0.00 26.62 2.32 82.99 0.00 0.00 744.00
April 34.84 0.24 34.60 12.98 48.48 0.00 0.00 720.00
May 49.06 2.61 46.44 38.17 22.29 0.00 0.00 744.00
June 54.74 5.98 48.76 52.48 13.65 0.00 0.00 720.00
July 52.29 4.45 47.84 54.11 11.85 0.00 0.00 744.00
August 39.73 0.67 39.06 38.59 15.00 0.00 0.00 744.00
September 30.95 0.00 30.94 21.58 28.28 0.00 0.00 720.00
October 21.50 0.00 21.50 5.82 48.68 0.00 0.00 744.00
November 14.24 0.00 14.24 0.65 79.83 0.00 0.00 720.00
December 11.94 0.00 11.94 0.00 127.99 0.00 0.00 744.00
                 
Annual Sum or Average 31.02 1.17 29.85 19.07 59.76 0.00 0.00 8760.00
Minimum of Months 11.94 0.00 11.94 0.00 11.85 0.00 0.00 672.00
Maximum of Months 54.74 5.98 48.76 54.11 133.24 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: F0B23F

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.09 0.00 14.09 0.02 133.24 0.00 0.00 744.00
February 21.64 0.00 21.64 0.72 107.14 0.00 0.00 672.00
March 26.62 0.00 26.62 2.32 82.99 0.00 0.00 744.00
April 34.72 0.19 34.53 12.97 48.57 0.00 0.00 720.00
May 49.06 2.61 46.44 38.17 22.29 0.00 0.00 744.00
June 54.74 5.98 48.76 52.48 13.65 0.00 0.00 720.00
July 52.29 4.45 47.84 54.11 11.85 0.00 0.00 744.00
August 39.71 0.66 39.05 38.58 15.00 0.00 0.00 744.00
September 30.94 0.00 30.94 21.58 28.29 0.00 0.00 720.00
October 21.50 0.00 21.50 5.82 48.68 0.00 0.00 744.00
November 14.24 0.00 14.24 0.65 79.83 0.00 0.00 720.00
December 11.94 0.00 11.94 0.00 127.99 0.00 0.00 744.00
                 
Annual Sum or Average 31.00 1.16 29.84 19.07 59.76 0.00 0.00 8760.00
Minimum of Months 11.94 0.00 11.94 0.00 11.85 0.00 0.00 672.00
Maximum of Months 54.74 5.98 48.76 54.11 133.24 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: EEC10E

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.01 0.00 14.01 0.02 133.29 0.00 0.00 744.00
February 21.51 0.00 21.51 0.70 107.22 0.00 0.00 672.00
March 26.46 0.00 26.46 2.26 83.07 0.00 0.00 744.00
April 34.42 0.15 34.27 12.79 48.68 0.00 0.00 720.00
May 48.64 2.51 46.13 37.81 22.29 0.00 0.00 744.00
June 54.45 5.98 48.47 52.17 13.63 0.00 0.00 720.00
July 51.97 4.44 47.54 53.78 11.83 0.00 0.00 744.00
August 39.22 0.53 38.70 38.13 14.99 0.00 0.00 744.00
September 30.76 0.00 30.76 21.39 28.28 0.00 0.00 720.00
October 21.39 0.00 21.39 5.74 48.69 0.00 0.00 744.00
November 14.16 0.00 14.16 0.64 79.87 0.00 0.00 720.00
December 11.87 0.00 11.87 0.00 128.02 0.00 0.00 744.00
                 
Annual Sum or Average 30.78 1.14 29.65 18.90 59.79 0.00 0.00 8760.00
Minimum of Months 11.87 0.00 11.87 0.00 11.83 0.00 0.00 672.00
Maximum of Months 54.45 5.98 48.47 53.78 133.29 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 944FCE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.95 0.00 13.95 0.02 133.32 0.00 0.00 744.00
February 21.42 0.00 21.42 0.69 107.27 0.00 0.00 672.00
March 26.36 0.00 26.36 2.22 83.12 0.00 0.00 744.00
April 34.26 0.14 34.12 12.68 48.73 0.00 0.00 720.00
May 47.00 1.55 45.45 36.82 22.64 0.00 0.00 744.00
June 52.94 5.10 47.84 50.88 13.65 0.00 0.00 720.00
July 50.40 3.51 46.89 52.45 11.83 0.00 0.00 744.00
August 38.71 0.34 38.37 37.74 15.07 0.00 0.00 744.00
September 30.64 0.00 30.64 21.27 28.27 0.00 0.00 720.00
October 21.31 0.00 21.31 5.68 48.69 0.00 0.00 744.00
November 14.11 0.00 14.11 0.63 79.90 0.00 0.00 720.00
December 11.83 0.00 11.83 0.00 128.04 0.00 0.00 744.00
                 
Annual Sum or Average 30.29 0.89 29.40 18.54 59.85 0.00 0.00 8760.00
Minimum of Months 11.83 0.00 11.83 0.00 11.83 0.00 0.00 672.00
Maximum of Months 52.94 5.10 47.84 52.45 133.32 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: C41399

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.09 0.00 14.09 0.02 133.24 0.00 0.00 744.00
February 21.64 0.00 21.64 0.72 107.14 0.00 0.00 672.00
March 26.62 0.00 26.62 2.32 82.99 0.00 0.00 744.00
April 34.89 0.27 34.63 12.99 48.43 0.00 0.00 720.00
May 49.06 2.61 46.44 38.17 22.29 0.00 0.00 744.00
June 54.74 5.98 48.76 52.48 13.65 0.00 0.00 720.00
July 52.29 4.45 47.84 54.11 11.85 0.00 0.00 744.00
August 39.73 0.67 39.06 38.59 15.00 0.00 0.00 744.00
September 30.95 0.00 30.95 21.58 28.28 0.00 0.00 720.00
October 21.50 0.00 21.50 5.82 48.68 0.00 0.00 744.00
November 14.24 0.00 14.24 0.65 79.83 0.00 0.00 720.00
December 11.94 0.00 11.94 0.00 127.99 0.00 0.00 744.00
                 
Annual Sum or Average 31.02 1.17 29.85 19.07 59.75 0.00 0.00 8760.00
Minimum of Months 11.94 0.00 11.94 0.00 11.85 0.00 0.00 672.00
Maximum of Months 54.74 5.98 48.76 54.11 133.24 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 95BA33

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.05 15.46 21.59 9.04 142.67 0.00 0.00 744.00
February 58.23 24.83 33.40 25.17 111.66 0.00 0.00 672.00
March 79.37 39.82 39.55 51.59 85.76 0.00 0.00 744.00
April 110.05 59.37 50.67 96.20 48.64 0.00 0.00 720.00
May 119.08 52.36 66.72 124.83 21.58 0.00 0.00 744.00
June 134.81 64.50 70.31 157.00 12.29 0.00 0.00 720.00
July 132.06 62.02 70.04 158.50 9.81 0.00 0.00 744.00
August 101.83 44.52 57.31 116.14 12.40 0.00 0.00 744.00
September 81.55 36.51 45.04 79.85 26.75 0.00 0.00 720.00
October 49.37 18.72 30.65 32.53 48.93 0.00 0.00 744.00
November 31.42 10.50 20.92 10.54 83.20 0.00 0.00 720.00
December 28.67 10.59 18.08 5.47 138.19 0.00 0.00 744.00
                 
Annual Sum or Average 80.37 36.63 43.74 72.48 61.62 0.00 0.00 8760.00
Minimum of Months 28.67 10.50 18.08 5.47 9.81 0.00 0.00 672.00
Maximum of Months 134.81 64.50 70.31 158.50 142.67 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: F27282

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.05 15.46 21.59 9.04 142.78 0.00 0.00 744.00
February 58.23 24.83 33.40 25.16 112.15 0.00 0.00 672.00
March 79.37 39.82 39.55 51.54 86.15 0.00 0.00 744.00
April 110.05 59.37 50.67 96.16 48.65 0.00 0.00 720.00
May 119.08 52.36 66.72 124.83 21.58 0.00 0.00 744.00
June 134.81 64.50 70.31 157.00 12.29 0.00 0.00 720.00
July 132.06 62.02 70.04 158.50 9.81 0.00 0.00 744.00
August 101.83 44.52 57.31 116.13 12.40 0.00 0.00 744.00
September 81.55 36.51 45.04 79.69 26.76 0.00 0.00 720.00
October 49.37 18.72 30.65 32.36 49.13 0.00 0.00 744.00
November 31.42 10.50 20.92 10.54 83.30 0.00 0.00 720.00
December 28.67 10.59 18.08 5.47 138.21 0.00 0.00 744.00
                 
Annual Sum or Average 80.37 36.63 43.74 72.44 61.73 0.00 0.00 8760.00
Minimum of Months 28.67 10.50 18.08 5.47 9.81 0.00 0.00 672.00
Maximum of Months 134.81 64.50 70.31 158.50 142.78 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 3DB407

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 194.16 135.12 59.04 157.57 203.73 0.00 0.00 744.00
February 245.88 166.15 79.73 218.37 170.40 0.00 0.00 672.00
March 216.60 137.13 79.47 182.77 141.06 0.00 0.00 744.00
April 195.98 106.31 89.67 164.93 86.47 0.00 0.00 720.00
May 164.62 56.11 108.51 147.08 39.44 0.00 0.00 744.00
June 147.68 39.18 108.51 144.30 21.88 0.00 0.00 720.00
July 161.46 50.95 110.50 165.99 17.19 0.00 0.00 744.00
August 172.55 72.07 100.48 179.96 21.49 0.00 0.00 744.00
September 185.05 98.56 86.48 187.97 46.24 0.00 0.00 720.00
October 158.13 93.06 65.07 148.72 81.33 0.00 0.00 744.00
November 140.84 88.43 52.41 121.49 126.70 0.00 0.00 720.00
December 149.91 98.33 51.57 111.99 197.61 0.00 0.00 744.00
                 
Annual Sum or Average 177.29 94.66 82.63 160.52 95.80 0.00 0.00 8760.00
Minimum of Months 140.84 39.18 51.57 111.99 17.19 0.00 0.00 672.00
Maximum of Months 245.88 166.15 110.50 218.37 203.73 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 3DADE2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 194.16 135.12 59.04 157.57 203.73 0.00 0.00 744.00
February 245.88 166.15 79.73 218.37 170.40 0.00 0.00 672.00
March 216.60 137.13 79.47 182.77 141.06 0.00 0.00 744.00
April 195.98 106.31 89.67 164.93 86.46 0.00 0.00 720.00
May 164.62 56.11 108.51 147.08 39.46 0.00 0.00 744.00
June 147.68 39.18 108.51 144.30 21.88 0.00 0.00 720.00
July 161.46 50.95 110.50 165.99 17.19 0.00 0.00 744.00
August 172.55 72.07 100.48 179.96 21.49 0.00 0.00 744.00
September 185.05 98.56 86.48 187.97 46.24 0.00 0.00 720.00
October 158.13 93.06 65.07 148.72 81.33 0.00 0.00 744.00
November 140.84 88.43 52.41 121.49 126.70 0.00 0.00 720.00
December 149.91 98.33 51.57 111.99 197.61 0.00 0.00 744.00
                 
Annual Sum or Average 177.29 94.66 82.63 160.52 95.80 0.00 0.00 8760.00
Minimum of Months 140.84 39.18 51.57 111.99 17.19 0.00 0.00 672.00
Maximum of Months 245.88 166.15 110.50 218.37 203.73 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: DF3E2C

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 194.16 135.12 59.04 157.57 203.73 0.00 0.00 744.00
February 245.88 166.15 79.73 218.37 170.40 0.00 0.00 672.00
March 216.60 137.13 79.47 182.77 141.06 0.00 0.00 744.00
April 195.98 106.31 89.67 164.93 86.48 0.00 0.00 720.00
May 164.62 56.11 108.51 147.08 39.47 0.00 0.00 744.00
June 147.68 39.18 108.51 144.30 21.87 0.00 0.00 720.00
July 161.46 50.95 110.50 165.97 17.18 0.00 0.00 744.00
August 172.55 72.07 100.48 179.96 21.51 0.00 0.00 744.00
September 185.05 98.56 86.48 187.97 46.24 0.00 0.00 720.00
October 158.13 93.06 65.07 148.72 81.33 0.00 0.00 744.00
November 140.84 88.43 52.41 121.49 126.70 0.00 0.00 720.00
December 149.91 98.33 51.57 111.99 197.61 0.00 0.00 744.00
                 
Annual Sum or Average 177.29 94.66 82.63 160.52 95.80 0.00 0.00 8760.00
Minimum of Months 140.84 39.18 51.57 111.99 17.18 0.00 0.00 672.00
Maximum of Months 245.88 166.15 110.50 218.37 203.73 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 5031C8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 194.16 135.12 59.04 157.57 203.73 0.00 0.00 744.00
February 245.88 166.15 79.73 218.37 170.40 0.00 0.00 672.00
March 216.60 137.13 79.47 182.77 141.06 0.00 0.00 744.00
April 195.98 106.31 89.67 164.93 86.47 0.00 0.00 720.00
May 164.62 56.11 108.51 147.07 39.60 0.00 0.00 744.00
June 147.68 39.18 108.51 144.12 21.94 0.00 0.00 720.00
July 161.46 50.95 110.50 165.83 17.24 0.00 0.00 744.00
August 172.55 72.07 100.48 179.96 21.53 0.00 0.00 744.00
September 185.05 98.56 86.48 187.97 46.24 0.00 0.00 720.00
October 158.13 93.06 65.07 148.72 81.33 0.00 0.00 744.00
November 140.84 88.43 52.41 121.49 126.70 0.00 0.00 720.00
December 149.91 98.33 51.57 111.99 197.61 0.00 0.00 744.00
                 
Annual Sum or Average 177.29 94.66 82.63 160.50 95.83 0.00 0.00 8760.00
Minimum of Months 140.84 39.18 51.57 111.99 17.24 0.00 0.00 672.00
Maximum of Months 245.88 166.15 110.50 218.37 203.73 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: C087D0

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 194.16 135.12 59.04 157.76 207.63 0.00 0.00 744.00
February 245.88 166.15 79.73 218.65 175.25 0.00 0.00 672.00
March 216.60 137.13 79.47 182.76 147.69 0.00 0.00 744.00
April 195.98 106.31 89.67 163.80 94.17 0.00 0.00 720.00
May 164.62 56.11 108.51 143.21 47.21 0.00 0.00 744.00
June 147.68 39.18 108.51 139.03 28.68 0.00 0.00 720.00
July 161.46 50.95 110.50 160.19 24.29 0.00 0.00 744.00
August 172.55 72.07 100.48 175.65 29.66 0.00 0.00 744.00
September 185.05 98.56 86.48 185.41 54.51 0.00 0.00 720.00
October 158.13 93.06 65.07 147.30 88.93 0.00 0.00 744.00
November 140.84 88.43 52.41 120.94 132.96 0.00 0.00 720.00
December 149.91 98.33 51.57 111.99 202.21 0.00 0.00 744.00
                 
Annual Sum or Average 177.29 94.66 82.63 158.47 102.45 0.00 0.00 8760.00
Minimum of Months 140.84 39.18 51.57 111.99 24.29 0.00 0.00 672.00
Maximum of Months 245.88 166.15 110.50 218.65 207.63 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: D2CA75

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 194.16 135.12 59.04 157.76 207.63 0.00 0.00 744.00
February 245.88 166.15 79.73 218.65 175.25 0.00 0.00 672.00
March 216.60 137.13 79.47 182.76 147.69 0.00 0.00 744.00
April 195.98 106.31 89.67 163.80 94.19 0.00 0.00 720.00
May 164.62 56.11 108.51 143.23 47.17 0.00 0.00 744.00
June 147.68 39.18 108.51 139.10 28.68 0.00 0.00 720.00
July 161.46 50.95 110.50 160.25 24.28 0.00 0.00 744.00
August 172.55 72.07 100.48 175.65 29.65 0.00 0.00 744.00
September 185.05 98.56 86.48 185.41 54.51 0.00 0.00 720.00
October 158.13 93.06 65.07 147.30 88.93 0.00 0.00 744.00
November 140.84 88.43 52.41 120.94 132.96 0.00 0.00 720.00
December 149.91 98.33 51.57 111.99 202.21 0.00 0.00 744.00
                 
Annual Sum or Average 177.29 94.66 82.63 158.48 102.44 0.00 0.00 8760.00
Minimum of Months 140.84 39.18 51.57 111.99 24.28 0.00 0.00 672.00
Maximum of Months 245.88 166.15 110.50 218.65 207.63 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: B0FB49

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 155.33 108.10 47.23 126.21 166.10 0.00 0.00 744.00
February 196.71 132.92 63.79 174.92 140.20 0.00 0.00 672.00
March 173.28 109.70 63.58 146.21 118.15 0.00 0.00 744.00
April 156.78 85.05 71.73 131.04 75.36 0.00 0.00 720.00
May 131.70 44.89 86.81 114.56 37.78 0.00 0.00 744.00
June 118.15 31.34 86.81 111.26 22.94 0.00 0.00 720.00
July 129.17 40.76 88.40 128.17 19.42 0.00 0.00 744.00
August 138.04 57.65 80.38 140.51 23.75 0.00 0.00 744.00
September 148.04 78.85 69.19 148.33 43.61 0.00 0.00 720.00
October 126.51 74.45 52.06 117.84 71.14 0.00 0.00 744.00
November 112.67 70.74 41.93 96.75 106.37 0.00 0.00 720.00
December 119.93 78.67 41.26 89.59 161.77 0.00 0.00 744.00
                 
Annual Sum or Average 141.83 75.73 66.10 126.78 81.96 0.00 0.00 8760.00
Minimum of Months 112.67 31.34 41.26 89.59 19.42 0.00 0.00 672.00
Maximum of Months 196.71 132.92 88.40 174.92 166.10 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: FE9BC9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 36.76 15.68 21.08 10.82 146.66 0.00 0.00 744.00
February 59.92 27.87 32.05 30.69 117.82 0.00 0.00 672.00
March 78.95 41.12 37.84 53.83 92.36 0.00 0.00 744.00
April 100.87 51.99 48.87 86.29 55.45 0.00 0.00 720.00
May 123.10 59.61 63.49 129.60 27.29 0.00 0.00 744.00
June 116.49 50.61 65.88 131.38 16.80 0.00 0.00 720.00
July 125.34 58.82 66.52 146.22 14.25 0.00 0.00 744.00
August 104.85 48.58 56.27 117.35 17.42 0.00 0.00 744.00
September 82.00 37.55 44.45 80.04 32.41 0.00 0.00 720.00
October 51.78 21.18 30.60 35.89 54.65 0.00 0.00 744.00
November 31.37 10.80 20.57 11.17 87.93 0.00 0.00 720.00
December 28.01 9.99 18.02 5.37 141.54 0.00 0.00 744.00
                 
Annual Sum or Average 78.39 36.20 42.19 70.13 66.84 0.00 0.00 8760.00
Minimum of Months 28.01 9.99 18.02 5.37 14.25 0.00 0.00 672.00
Maximum of Months 125.34 59.61 66.52 146.22 146.66 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 9DF7DE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 36.26 15.68 20.58 10.73 147.22 0.00 0.00 744.00
February 59.13 27.87 31.26 30.39 118.74 0.00 0.00 672.00
March 77.98 41.12 36.86 53.25 93.03 0.00 0.00 744.00
April 99.63 51.99 47.64 85.21 55.56 0.00 0.00 720.00
May 119.10 57.78 61.32 125.06 27.47 0.00 0.00 744.00
June 112.89 49.19 63.71 127.19 16.79 0.00 0.00 720.00
July 121.91 57.51 64.40 142.20 14.18 0.00 0.00 744.00
August 102.31 47.77 54.54 114.46 17.41 0.00 0.00 744.00
September 80.90 37.55 43.35 78.80 32.35 0.00 0.00 720.00
October 51.05 21.18 29.86 35.25 55.00 0.00 0.00 744.00
November 30.87 10.80 20.07 11.01 88.32 0.00 0.00 720.00
December 27.60 9.99 17.61 5.33 141.95 0.00 0.00 744.00
                 
Annual Sum or Average 76.73 35.75 40.98 68.47 67.12 0.00 0.00 8760.00
Minimum of Months 27.60 9.99 17.61 5.33 14.18 0.00 0.00 672.00
Maximum of Months 121.91 57.78 64.40 142.20 147.22 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: D0BE44

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 34.74 15.68 19.06 10.55 147.88 0.00 0.00 744.00
February 56.90 27.87 29.02 29.67 119.78 0.00 0.00 672.00
March 75.33 41.12 34.21 52.07 93.98 0.00 0.00 744.00
April 93.27 49.54 43.73 79.31 56.43 0.00 0.00 720.00
May 109.06 53.20 55.86 113.54 27.51 0.00 0.00 744.00
June 102.57 44.59 57.98 115.15 16.74 0.00 0.00 720.00
July 112.20 53.22 58.98 130.74 13.86 0.00 0.00 744.00
August 95.82 45.67 50.15 107.09 17.17 0.00 0.00 744.00
September 77.64 37.47 40.17 75.56 32.13 0.00 0.00 720.00
October 48.72 21.18 27.54 33.57 55.17 0.00 0.00 744.00
November 29.30 10.80 18.50 10.59 88.94 0.00 0.00 720.00
December 26.28 9.99 16.29 5.24 142.50 0.00 0.00 744.00
                 
Annual Sum or Average 71.90 34.23 37.67 63.80 67.46 0.00 0.00 8760.00
Minimum of Months 26.28 9.99 16.29 5.24 13.86 0.00 0.00 672.00
Maximum of Months 112.20 53.22 58.98 130.74 147.88 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 6B5226

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 49.57 20.90 28.66 14.58 196.35 0.00 0.00 744.00
February 80.79 37.16 43.63 41.41 157.60 0.00 0.00 672.00
March 106.40 54.82 51.58 72.44 123.12 0.00 0.00 744.00
April 135.93 69.33 66.61 116.22 73.81 0.00 0.00 720.00
May 166.95 80.20 86.74 175.66 36.89 0.00 0.00 744.00
June 160.98 70.16 90.82 181.38 22.85 0.00 0.00 720.00
July 171.93 80.52 91.40 199.91 19.98 0.00 0.00 744.00
August 141.47 64.77 76.70 157.69 24.40 0.00 0.00 744.00
September 110.59 50.07 60.52 107.41 44.10 0.00 0.00 720.00
October 69.82 28.24 41.57 48.40 73.56 0.00 0.00 744.00
November 42.35 14.40 27.96 15.14 117.21 0.00 0.00 720.00
December 37.77 13.32 24.46 7.24 189.18 0.00 0.00 744.00
                 
Annual Sum or Average 106.35 48.73 57.63 95.12 89.64 0.00 0.00 8760.00
Minimum of Months 37.77 13.32 24.46 7.24 19.98 0.00 0.00 672.00
Maximum of Months 171.93 80.52 91.40 199.91 196.35 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 8F59F7

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 151.69 105.59 46.10 124.79 169.12 0.00 0.00 744.00
February 194.10 131.50 62.61 174.43 141.79 0.00 0.00 672.00
March 172.33 109.51 62.81 145.76 118.32 0.00 0.00 744.00
April 156.03 85.05 70.99 130.24 75.35 0.00 0.00 720.00
May 130.75 44.89 85.86 113.32 38.31 0.00 0.00 744.00
June 117.12 31.34 85.78 109.74 23.60 0.00 0.00 720.00
July 128.12 40.76 87.36 126.29 20.40 0.00 0.00 744.00
August 137.17 57.65 79.52 138.97 24.75 0.00 0.00 744.00
September 147.35 78.84 68.50 147.23 44.44 0.00 0.00 720.00
October 125.28 73.96 51.32 117.35 71.87 0.00 0.00 744.00
November 110.95 69.85 41.09 96.19 107.25 0.00 0.00 720.00
December 117.04 76.58 40.46 88.18 163.84 0.00 0.00 744.00
                 
Annual Sum or Average 140.31 75.10 65.21 125.70 83.00 0.00 0.00 8760.00
Minimum of Months 110.95 31.34 40.46 88.18 20.40 0.00 0.00 672.00
Maximum of Months 194.10 131.50 87.36 174.43 169.12 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 44F571

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 135.09 93.62 41.47 109.23 173.62 0.00 0.00 744.00
February 178.84 121.81 57.03 160.50 145.25 0.00 0.00 672.00
March 161.78 103.82 57.97 138.04 120.15 0.00 0.00 744.00
April 149.61 83.51 66.10 125.26 75.95 0.00 0.00 720.00
May 124.71 44.69 80.02 107.28 38.12 0.00 0.00 744.00
June 110.93 31.27 79.66 103.27 23.38 0.00 0.00 720.00
July 121.80 40.63 81.17 119.65 19.98 0.00 0.00 744.00
August 131.15 57.09 74.06 132.76 24.40 0.00 0.00 744.00
September 139.85 76.22 63.63 140.38 44.49 0.00 0.00 720.00
October 116.25 68.95 47.29 108.84 72.65 0.00 0.00 744.00
November 100.50 63.23 37.28 86.25 109.34 0.00 0.00 720.00
December 102.82 66.63 36.19 75.74 168.49 0.00 0.00 744.00
                 
Annual Sum or Average 130.78 70.62 60.16 116.95 84.39 0.00 0.00 8760.00
Minimum of Months 100.50 31.27 36.19 75.74 19.98 0.00 0.00 672.00
Maximum of Months 178.84 121.81 81.17 160.50 173.62 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 6BD844

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.70 10.31 14.39 5.94 96.73 0.00 0.00 744.00
February 38.82 16.55 22.26 16.65 76.19 0.00 0.00 672.00
March 52.92 26.55 26.37 33.95 59.99 0.00 0.00 744.00
April 73.36 39.58 33.78 62.78 35.85 0.00 0.00 720.00
May 79.39 34.90 44.48 80.28 17.95 0.00 0.00 744.00
June 89.87 43.00 46.87 100.83 11.61 0.00 0.00 720.00
July 88.04 41.35 46.70 101.79 10.08 0.00 0.00 744.00
August 67.88 29.68 38.21 74.74 12.28 0.00 0.00 744.00
September 54.37 24.34 30.02 51.58 21.71 0.00 0.00 720.00
October 32.91 12.48 20.43 20.90 36.44 0.00 0.00 744.00
November 20.95 7.00 13.95 6.78 58.36 0.00 0.00 720.00
December 19.11 7.06 12.05 3.58 94.17 0.00 0.00 744.00
                 
Annual Sum or Average 53.58 24.42 29.16 46.80 44.15 0.00 0.00 8760.00
Minimum of Months 19.11 7.00 12.05 3.58 10.08 0.00 0.00 672.00
Maximum of Months 89.87 43.00 46.87 101.79 96.73 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 86D536

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.70 10.31 14.39 5.94 96.73 0.00 0.00 744.00
February 38.82 16.55 22.26 16.65 76.19 0.00 0.00 672.00
March 52.92 26.55 26.37 33.95 59.99 0.00 0.00 744.00
April 73.36 39.58 33.78 62.78 35.85 0.00 0.00 720.00
May 79.39 34.90 44.48 80.28 17.95 0.00 0.00 744.00
June 89.87 43.00 46.87 100.83 11.61 0.00 0.00 720.00
July 88.04 41.35 46.70 101.79 10.08 0.00 0.00 744.00
August 67.88 29.68 38.21 74.74 12.28 0.00 0.00 744.00
September 54.37 24.34 30.02 51.58 21.71 0.00 0.00 720.00
October 32.91 12.48 20.43 20.90 36.44 0.00 0.00 744.00
November 20.95 7.00 13.95 6.78 58.36 0.00 0.00 720.00
December 19.11 7.06 12.05 3.58 94.17 0.00 0.00 744.00
                 
Annual Sum or Average 53.58 24.42 29.16 46.80 44.15 0.00 0.00 8760.00
Minimum of Months 19.11 7.00 12.05 3.58 10.08 0.00 0.00 672.00
Maximum of Months 89.87 43.00 46.87 101.79 96.73 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: BAF71D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.70 10.31 14.39 5.94 96.73 0.00 0.00 744.00
February 38.82 16.55 22.26 16.65 76.19 0.00 0.00 672.00
March 52.92 26.55 26.37 33.95 59.99 0.00 0.00 744.00
April 73.36 39.58 33.78 62.78 35.85 0.00 0.00 720.00
May 79.39 34.90 44.48 80.28 17.95 0.00 0.00 744.00
June 89.87 43.00 46.87 100.83 11.61 0.00 0.00 720.00
July 88.04 41.35 46.70 101.79 10.08 0.00 0.00 744.00
August 67.88 29.68 38.21 74.74 12.28 0.00 0.00 744.00
September 54.37 24.34 30.02 51.58 21.71 0.00 0.00 720.00
October 32.91 12.48 20.43 20.90 36.44 0.00 0.00 744.00
November 20.95 7.00 13.95 6.78 58.36 0.00 0.00 720.00
December 19.11 7.06 12.05 3.58 94.17 0.00 0.00 744.00
                 
Annual Sum or Average 53.58 24.42 29.16 46.80 44.15 0.00 0.00 8760.00
Minimum of Months 19.11 7.00 12.05 3.58 10.08 0.00 0.00 672.00
Maximum of Months 89.87 43.00 46.87 101.79 96.73 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 3833A2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.70 10.31 14.39 5.94 96.73 0.00 0.00 744.00
February 38.82 16.55 22.26 16.65 76.19 0.00 0.00 672.00
March 52.92 26.55 26.37 33.95 59.99 0.00 0.00 744.00
April 73.36 39.58 33.78 62.78 35.85 0.00 0.00 720.00
May 79.39 34.90 44.48 80.28 17.95 0.00 0.00 744.00
June 89.87 43.00 46.87 100.83 11.61 0.00 0.00 720.00
July 88.04 41.35 46.70 101.79 10.08 0.00 0.00 744.00
August 67.88 29.68 38.21 74.74 12.28 0.00 0.00 744.00
September 54.37 24.34 30.02 51.58 21.71 0.00 0.00 720.00
October 32.91 12.48 20.43 20.90 36.44 0.00 0.00 744.00
November 20.95 7.00 13.95 6.78 58.36 0.00 0.00 720.00
December 19.11 7.06 12.05 3.58 94.17 0.00 0.00 744.00
                 
Annual Sum or Average 53.58 24.42 29.16 46.80 44.15 0.00 0.00 8760.00
Minimum of Months 19.11 7.00 12.05 3.58 10.08 0.00 0.00 672.00
Maximum of Months 89.87 43.00 46.87 101.79 96.73 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 2111A1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 8.23 3.44 4.80 2.13 30.30 0.00 0.00 744.00
February 12.94 5.52 7.42 5.93 23.44 0.00 0.00 672.00
March 17.64 8.85 8.79 11.96 17.81 0.00 0.00 744.00
April 24.45 13.19 11.26 22.04 10.04 0.00 0.00 720.00
May 26.46 11.63 14.83 27.82 4.86 0.00 0.00 744.00
June 29.96 14.33 15.62 34.38 3.15 0.00 0.00 720.00
July 29.35 13.78 15.57 34.36 2.93 0.00 0.00 744.00
August 22.63 9.89 12.74 25.31 3.58 0.00 0.00 744.00
September 18.12 8.11 10.01 17.72 6.31 0.00 0.00 720.00
October 10.97 4.16 6.81 7.44 10.68 0.00 0.00 744.00
November 6.98 2.33 4.65 2.45 17.71 0.00 0.00 720.00
December 6.37 2.35 4.02 1.29 29.51 0.00 0.00 744.00
                 
Annual Sum or Average 17.86 8.14 9.72 16.12 13.32 0.00 0.00 8760.00
Minimum of Months 6.37 2.33 4.02 1.29 2.93 0.00 0.00 672.00
Maximum of Months 29.96 14.33 15.62 34.38 30.30 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 9BC521

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 28.85 0.00 28.85 0.07 262.78 0.00 0.00 744.00
February 44.31 0.00 44.31 1.72 207.47 0.00 0.00 672.00
March 54.52 0.00 54.52 5.78 155.36 0.00 0.00 744.00
April 71.46 0.54 70.91 29.61 85.47 0.00 0.00 720.00
May 100.46 5.35 95.11 81.01 38.00 0.00 0.00 744.00
June 112.10 12.24 99.85 108.49 23.54 0.00 0.00 720.00
July 107.08 9.12 97.96 109.49 22.13 0.00 0.00 744.00
August 81.36 1.37 79.99 77.89 27.87 0.00 0.00 744.00
September 63.42 0.01 63.41 44.32 51.89 0.00 0.00 720.00
October 44.04 0.00 44.04 12.96 89.58 0.00 0.00 744.00
November 29.16 0.00 29.16 1.53 151.60 0.00 0.00 720.00
December 24.44 0.00 24.44 0.00 251.57 0.00 0.00 744.00
                 
Annual Sum or Average 63.53 2.40 61.13 39.64 113.56 0.00 0.00 8760.00
Minimum of Months 24.44 0.00 24.44 0.00 22.13 0.00 0.00 672.00
Maximum of Months 112.10 12.24 99.85 109.49 262.78 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 142781

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 28.17 0.00 28.17 0.07 254.66 0.00 0.00 744.00
February 43.28 0.00 43.28 1.72 200.97 0.00 0.00 672.00
March 53.25 0.00 53.25 5.77 150.56 0.00 0.00 744.00
April 69.79 0.53 69.26 29.11 82.95 0.00 0.00 720.00
May 98.12 5.23 92.89 79.22 37.03 0.00 0.00 744.00
June 109.48 11.96 97.52 105.90 23.00 0.00 0.00 720.00
July 104.58 8.91 95.67 106.82 21.64 0.00 0.00 744.00
August 79.46 1.34 78.12 76.06 27.21 0.00 0.00 744.00
September 61.91 0.01 61.90 43.39 50.51 0.00 0.00 720.00
October 43.01 0.00 43.01 12.80 86.99 0.00 0.00 744.00
November 28.48 0.00 28.48 1.52 146.92 0.00 0.00 720.00
December 23.87 0.00 23.87 0.00 243.67 0.00 0.00 744.00
                 
Annual Sum or Average 62.04 2.34 59.70 38.76 110.14 0.00 0.00 8760.00
Minimum of Months 23.87 0.00 23.87 0.00 21.64 0.00 0.00 672.00
Maximum of Months 109.48 11.96 97.52 106.82 254.66 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: E74902

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 28.17 0.00 28.17 0.08 254.19 0.00 0.00 744.00
February 43.28 0.00 43.28 1.80 200.72 0.00 0.00 672.00
March 53.25 0.00 53.25 6.01 150.50 0.00 0.00 744.00
April 69.79 0.53 69.26 29.73 83.42 0.00 0.00 720.00
May 98.12 5.23 92.89 79.29 38.36 0.00 0.00 744.00
June 109.48 11.96 97.52 105.61 24.41 0.00 0.00 720.00
July 104.58 8.91 95.67 106.23 23.35 0.00 0.00 744.00
August 79.46 1.34 78.12 75.76 29.16 0.00 0.00 744.00
September 61.94 0.01 61.93 43.60 52.31 0.00 0.00 720.00
October 43.01 0.00 43.01 13.04 88.10 0.00 0.00 744.00
November 28.48 0.00 28.48 1.51 147.46 0.00 0.00 720.00
December 23.87 0.00 23.87 0.00 243.70 0.00 0.00 744.00
                 
Annual Sum or Average 62.05 2.34 59.70 38.78 110.95 0.00 0.00 8760.00
Minimum of Months 23.87 0.00 23.87 0.00 23.35 0.00 0.00 672.00
Maximum of Months 109.48 11.96 97.52 106.23 254.19 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: 93BBC3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 28.17 0.00 28.17 0.07 256.17 0.00 0.00 744.00
February 43.28 0.00 43.28 1.76 202.36 0.00 0.00 672.00
March 53.25 0.00 53.25 5.88 151.67 0.00 0.00 744.00
April 69.79 0.53 69.26 29.55 83.94 0.00 0.00 720.00
May 98.12 5.23 92.89 79.19 38.45 0.00 0.00 744.00
June 109.48 11.96 97.52 105.66 24.41 0.00 0.00 720.00
July 104.58 8.91 95.67 106.34 23.33 0.00 0.00 744.00
August 79.46 1.34 78.12 75.76 29.19 0.00 0.00 744.00
September 61.94 0.01 61.93 43.48 52.52 0.00 0.00 720.00
October 43.01 0.00 43.01 12.90 88.60 0.00 0.00 744.00
November 28.48 0.00 28.48 1.48 148.61 0.00 0.00 720.00
December 23.87 0.00 23.87 0.00 245.72 0.00 0.00 744.00
                 
Annual Sum or Average 62.05 2.34 59.70 38.74 111.72 0.00 0.00 8760.00
Minimum of Months 23.87 0.00 23.87 0.00 23.33 0.00 0.00 672.00
Maximum of Months 109.48 11.96 97.52 106.34 256.17 0.00 0.00 744.00



Table of Contents

Report: WindowReportMonthly

For: C635A6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 38.56 27.01 11.55 31.96 40.24 0.00 0.00 744.00
February 47.74 32.49 15.25 44.12 34.54 0.00 0.00 672.00
March 40.76 25.75 15.01 36.07 28.86 0.00 0.00 744.00
April 38.25 21.00 17.25 32.91 17.66 0.00 0.00 720.00
May 32.17 11.22 20.95 28.39 8.98 0.00 0.00 744.00
June 28.77 7.84 20.94 27.17 5.67 0.00 0.00 720.00
July 31.53 10.19 21.34 30.98 5.26 0.00 0.00 744.00
August 33.74 14.35 19.38 34.12 6.47 0.00 0.00 744.00
September 35.64 19.11 16.53 36.20 11.25 0.00 0.00 720.00
October 30.26 17.89 12.37 28.97 17.88 0.00 0.00 744.00
November 27.74 17.58 10.17 24.45 25.80 0.00 0.00 720.00
December 29.77 19.67 10.11 22.75 39.17 0.00 0.00 744.00
                 
Annual Sum or Average 34.49 18.59 15.90 31.42 20.09 0.00 0.00 8760.00
Minimum of Months 27.74 7.84 10.11 22.75 5.26 0.00 0.00 672.00
Maximum of Months 47.74 32.49 21.34 44.12 40.24 0.00 0.00 744.00



Table of Contents

Report: WindowEnergyReportMonthly

For: 78F987

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.208019E+09 0.144763E+09 63255465.77 0.170944E+09 0.222235E+09
February 0.237938E+09 0.160780E+09 77157523.13 0.214975E+09 0.168729E+09
March 0.232058E+09 0.146915E+09 85142476.22 0.199980E+09 0.152969E+09
April 0.203187E+09 0.110222E+09 92965343.12 0.176106E+09 88501828.09
May 0.176366E+09 60115035.59 0.116251E+09 0.163751E+09 40960694.58
June 0.153118E+09 40618846.20 0.112500E+09 0.155666E+09 21960997.26
July 0.172981E+09 54590944.70 0.118390E+09 0.183176E+09 18385215.77
August 0.184859E+09 77208326.48 0.107651E+09 0.197544E+09 23394821.16
September 0.191856E+09 0.102188E+09 89667623.89 0.199283E+09 47865236.80
October 0.169417E+09 99701737.44 69714834.93 0.162352E+09 88417349.11
November 0.146025E+09 91684299.18 54340559.53 0.128046E+09 0.134725E+09
December 0.160606E+09 0.105351E+09 55254886.48 0.121376E+09 0.216810E+09
           
Annual Sum or Average 0.223643E+10 0.119414E+10 0.104229E+10 0.207320E+10 0.122495E+10
Minimum of Months 0.146025E+09 40618846.20 54340559.53 0.121376E+09 18385215.77
Maximum of Months 0.237938E+09 0.160780E+09 0.118390E+09 0.214975E+09 0.222235E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: D8037E

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.787375E+09 0.552019E+09 0.235357E+09 0.655495E+09 0.935869E+09
February 0.872717E+09 0.592671E+09 0.280046E+09 0.801771E+09 0.736939E+09
March 0.814404E+09 0.506944E+09 0.307460E+09 0.707664E+09 0.677332E+09
April 0.750717E+09 0.406750E+09 0.343966E+09 0.650066E+09 0.403605E+09
May 0.669779E+09 0.235010E+09 0.434769E+09 0.596472E+09 0.205695E+09
June 0.583101E+09 0.160872E+09 0.422229E+09 0.559677E+09 0.124869E+09
July 0.658909E+09 0.214774E+09 0.444135E+09 0.662025E+09 0.113484E+09
August 0.694925E+09 0.294722E+09 0.400203E+09 0.721394E+09 0.141787E+09
September 0.689244E+09 0.361342E+09 0.327902E+09 0.707511E+09 0.243434E+09
October 0.607555E+09 0.354540E+09 0.253015E+09 0.576311E+09 0.412738E+09
November 0.547165E+09 0.346663E+09 0.200502E+09 0.482073E+09 0.589868E+09
December 0.614124E+09 0.405146E+09 0.208977E+09 0.466066E+09 0.905743E+09
           
Annual Sum or Average 0.829002E+10 0.443146E+10 0.385856E+10 0.758653E+10 0.549136E+10
Minimum of Months 0.547165E+09 0.160872E+09 0.200502E+09 0.466066E+09 0.113484E+09
Maximum of Months 0.872717E+09 0.592671E+09 0.444135E+09 0.801771E+09 0.935869E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 4A8120

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 28900621.33 0.00 28900621.33 218560.57 0.250305E+09
February 40256813.88 0.00 40256813.88 3419216.40 0.174240E+09
March 55024122.34 0.00 55024122.34 10734141.77 0.138596E+09
April 69159547.79 113020.56 69046527.23 43409614.41 67351579.54
May 96619118.54 2313438.49 94305680.05 0.105988E+09 24158684.57
June 0.101951E+09 7019081.47 94931905.43 0.132902E+09 10715280.78
July 0.102046E+09 5079708.54 96966193.07 0.140447E+09 8813737.76
August 80500344.42 521203.12 79979141.30 0.104869E+09 11471413.89
September 61702208.85 504.77 61701704.08 60770800.49 33370608.04
October 44084096.87 0.00 44084096.87 21760529.04 72455508.85
November 28193042.44 0.00 28193042.44 3265988.94 0.129162E+09
December 24420294.73 0.00 24420294.73 5693.04 0.238913E+09
           
Annual Sum or Average 0.732857E+09 15046956.95 0.717810E+09 0.627790E+09 0.115955E+10
Minimum of Months 24420294.73 0.00 24420294.73 5693.04 8813737.76
Maximum of Months 0.102046E+09 7019081.47 96966193.07 0.140447E+09 0.250305E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: AAE778

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.262893E+09 0.111973E+09 0.150921E+09 79707512.45 0.106066E+10
February 0.387618E+09 0.179808E+09 0.207810E+09 0.203615E+09 0.776287E+09
March 0.565810E+09 0.293661E+09 0.272149E+09 0.392417E+09 0.672645E+09
April 0.699946E+09 0.359389E+09 0.340558E+09 0.606791E+09 0.390854E+09
May 0.887201E+09 0.429631E+09 0.457570E+09 0.936432E+09 0.205057E+09
June 0.828104E+09 0.363711E+09 0.464393E+09 0.931438E+09 0.127350E+09
July 0.914709E+09 0.431337E+09 0.483373E+09 0.105901E+10 0.119537E+09
August 0.752027E+09 0.346961E+09 0.405066E+09 0.837150E+09 0.145326E+09
September 0.568283E+09 0.259545E+09 0.308738E+09 0.554310E+09 0.242596E+09
October 0.369790E+09 0.151294E+09 0.218496E+09 0.257946E+09 0.414827E+09
November 0.216815E+09 74627239.38 0.142188E+09 78370532.34 0.634540E+09
December 0.199947E+09 71337519.96 0.128610E+09 39598799.27 0.103421E+10
           
Annual Sum or Average 0.665314E+10 0.307327E+10 0.357987E+10 0.597679E+10 0.582389E+10
Minimum of Months 0.199947E+09 71337519.96 0.128610E+09 39598799.27 0.119537E+09
Maximum of Months 0.914709E+09 0.431337E+09 0.483373E+09 0.105901E+10 0.106066E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: 3AAD8B

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 32755502.45 0.00 32755502.45 0.00 0.369562E+09
February 45458360.12 0.00 45458360.12 744568.12 0.272183E+09
March 62037919.62 0.00 62037919.62 4052427.70 0.231895E+09
April 78114622.27 233067.49 77881554.78 28030079.66 0.129242E+09
May 0.110729E+09 3824086.79 0.106905E+09 90593172.24 61893510.54
June 0.114065E+09 7284045.90 0.106781E+09 0.116798E+09 37020980.84
July 0.114104E+09 5754737.89 0.108350E+09 0.125679E+09 32561901.57
August 90923713.55 874607.26 90049106.29 91969802.17 40745887.64
September 69775149.99 0.00 69775149.99 48437165.99 74260659.00
October 50210813.86 0.00 50210813.86 11782605.81 0.135085E+09
November 32051654.21 0.00 32051654.21 1341187.05 0.217563E+09
December 27809659.94 0.00 27809659.94 0.00 0.356694E+09
           
Annual Sum or Average 0.828036E+09 17970545.34 0.810066E+09 0.519428E+09 0.195871E+10
Minimum of Months 27809659.94 0.00 27809659.94 0.00 32561901.57
Maximum of Months 0.114104E+09 7284045.90 0.108350E+09 0.125679E+09 0.369562E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 8128A9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 35957810.47 0.00 35957810.47 5545.68 0.368101E+09
February 49792952.65 0.00 49792952.65 1246163.85 0.269753E+09
March 67782637.29 0.00 67782637.29 5700137.83 0.229060E+09
April 84845851.60 167542.31 84678309.28 32927986.45 0.128514E+09
May 0.120959E+09 4155039.37 0.116804E+09 0.100191E+09 61983232.48
June 0.126707E+09 9395216.81 0.117311E+09 0.128354E+09 37175019.81
July 0.125691E+09 6951989.40 0.118739E+09 0.136845E+09 33270656.61
August 99302712.08 893130.75 98409581.32 0.100622E+09 41447342.56
September 76307250.26 0.00 76307250.26 54776460.29 74740577.56
October 55056342.64 0.00 55056342.64 14984743.77 0.134634E+09
November 35229933.50 0.00 35229933.50 1725728.20 0.216255E+09
December 30549122.76 0.00 30549122.76 0.00 0.355616E+09
           
Annual Sum or Average 0.908181E+09 21562918.64 0.886619E+09 0.577379E+09 0.195055E+10
Minimum of Months 30549122.76 0.00 30549122.76 0.00 33270656.61
Maximum of Months 0.126707E+09 9395216.81 0.118739E+09 0.136845E+09 0.368101E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 9B1541

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.208019E+09 0.144763E+09 63255465.77 0.177079E+09 0.216164E+09
February 0.237938E+09 0.160780E+09 77157523.13 0.221847E+09 0.164345E+09
March 0.232058E+09 0.146915E+09 85142476.22 0.207157E+09 0.147189E+09
April 0.203187E+09 0.110222E+09 92965343.12 0.184117E+09 85674139.66
May 0.176366E+09 60115035.59 0.116251E+09 0.172575E+09 41466538.34
June 0.153118E+09 40618846.20 0.112500E+09 0.163933E+09 23319392.40
July 0.172981E+09 54590944.70 0.118390E+09 0.190749E+09 20486736.98
August 0.184859E+09 77208326.48 0.107651E+09 0.206493E+09 25662111.03
September 0.191856E+09 0.102188E+09 89667623.89 0.207571E+09 48345137.51
October 0.169417E+09 99701737.44 69714834.93 0.169932E+09 85881405.89
November 0.146025E+09 91684299.18 54340559.53 0.134392E+09 0.129944E+09
December 0.160606E+09 0.105351E+09 55254886.48 0.126159E+09 0.210010E+09
           
Annual Sum or Average 0.223643E+10 0.119414E+10 0.104229E+10 0.216200E+10 0.119849E+10
Minimum of Months 0.146025E+09 40618846.20 54340559.53 0.126159E+09 20486736.98
Maximum of Months 0.237938E+09 0.160780E+09 0.118390E+09 0.221847E+09 0.216164E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CF850A

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.208019E+09 0.144763E+09 63255465.77 0.177079E+09 0.216164E+09
February 0.237938E+09 0.160780E+09 77157523.13 0.221847E+09 0.164345E+09
March 0.232058E+09 0.146915E+09 85142476.22 0.207157E+09 0.147189E+09
April 0.203187E+09 0.110222E+09 92965343.12 0.184117E+09 85659188.00
May 0.176366E+09 60115035.59 0.116251E+09 0.172584E+09 41381060.02
June 0.153118E+09 40618846.20 0.112500E+09 0.163958E+09 23301055.13
July 0.172981E+09 54590944.70 0.118390E+09 0.190801E+09 20468260.20
August 0.184859E+09 77208326.48 0.107651E+09 0.206496E+09 25623457.72
September 0.191856E+09 0.102188E+09 89667623.89 0.207571E+09 48345137.51
October 0.169417E+09 99701737.44 69714834.93 0.169932E+09 85881405.89
November 0.146025E+09 91684299.18 54340559.53 0.134392E+09 0.129944E+09
December 0.160606E+09 0.105351E+09 55254886.48 0.126159E+09 0.210010E+09
           
Annual Sum or Average 0.223643E+10 0.119414E+10 0.104229E+10 0.216209E+10 0.119831E+10
Minimum of Months 0.146025E+09 40618846.20 54340559.53 0.126159E+09 20468260.20
Maximum of Months 0.237938E+09 0.160780E+09 0.118390E+09 0.221847E+09 0.216164E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: A6BA23

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66154644.95 27601261.26 38553383.68 17842000.29 0.247767E+09
February 93910992.53 40047706.36 53863286.17 44733738.71 0.175519E+09
March 0.141729E+09 71108672.13 70619852.85 99768986.34 0.147157E+09
April 0.190160E+09 0.102597E+09 87562509.23 0.179961E+09 80888124.00
May 0.212627E+09 93488700.05 0.119138E+09 0.239407E+09 38289265.15
June 0.232952E+09 0.111454E+09 0.121498E+09 0.287118E+09 21931737.11
July 0.235812E+09 0.110742E+09 0.125070E+09 0.297354E+09 19562169.14
August 0.181819E+09 79488612.79 0.102331E+09 0.221778E+09 24982141.76
September 0.140920E+09 63096177.99 77823577.19 0.150446E+09 47143684.12
October 88152517.12 33429015.42 54723501.70 66906466.19 85836382.71
November 54292532.24 18141898.49 36150633.75 21636875.88 0.139131E+09
December 51187152.06 18907669.02 32279483.05 10686914.05 0.241580E+09
           
Annual Sum or Average 0.168972E+10 0.770104E+09 0.919612E+09 0.163764E+10 0.126979E+10
Minimum of Months 51187152.06 18141898.49 32279483.05 10686914.05 19562169.14
Maximum of Months 0.235812E+09 0.111454E+09 0.125070E+09 0.297354E+09 0.247767E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: D10D28

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66154644.95 27601261.26 38553383.68 17842250.79 0.248604E+09
February 93910992.53 40047706.36 53863286.17 44660368.08 0.176420E+09
March 0.141729E+09 71108672.13 70619852.85 99705982.48 0.147307E+09
April 0.190160E+09 0.102597E+09 87562509.23 0.179961E+09 80888124.00
May 0.212627E+09 93488700.05 0.119138E+09 0.239407E+09 38289265.15
June 0.232952E+09 0.111454E+09 0.121498E+09 0.287118E+09 21931737.11
July 0.235812E+09 0.110742E+09 0.125070E+09 0.297354E+09 19562169.14
August 0.181819E+09 79488612.79 0.102331E+09 0.221777E+09 24982141.76
September 0.140920E+09 63096177.99 77823577.19 0.150392E+09 47143688.27
October 88152517.12 33429015.42 54723501.70 66632855.64 85941209.14
November 54292532.24 18141898.49 36150633.75 21619650.46 0.139611E+09
December 51187152.06 18907669.02 32279483.05 10686914.05 0.242055E+09
           
Annual Sum or Average 0.168972E+10 0.770104E+09 0.919612E+09 0.163716E+10 0.127274E+10
Minimum of Months 51187152.06 18141898.49 32279483.05 10686914.05 19562169.14
Maximum of Months 0.235812E+09 0.111454E+09 0.125070E+09 0.297354E+09 0.248604E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 591336

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66154644.95 27601261.26 38553383.68 17632458.12 0.252243E+09
February 93910992.53 40047706.36 53863286.17 44530306.10 0.179034E+09
March 0.141729E+09 71108672.13 70619852.85 99578514.70 0.149941E+09
April 0.190160E+09 0.102597E+09 87562509.23 0.180175E+09 82365649.54
May 0.212627E+09 93488700.05 0.119138E+09 0.241723E+09 37381881.85
June 0.232952E+09 0.111454E+09 0.121498E+09 0.290553E+09 20356177.48
July 0.235812E+09 0.110742E+09 0.125070E+09 0.301035E+09 18109070.24
August 0.181819E+09 79488612.79 0.102331E+09 0.224527E+09 23492738.09
September 0.140920E+09 63096177.99 77823577.19 0.154007E+09 43758130.18
October 88152517.12 33429015.42 54723501.70 68485584.97 83745573.56
November 54292532.24 18141898.49 36150633.75 21981953.35 0.140672E+09
December 51187152.06 18907669.02 32279483.05 10545333.29 0.246055E+09
           
Annual Sum or Average 0.168972E+10 0.770104E+09 0.919612E+09 0.165477E+10 0.127715E+10
Minimum of Months 51187152.06 18141898.49 32279483.05 10545333.29 18109070.24
Maximum of Months 0.235812E+09 0.111454E+09 0.125070E+09 0.301035E+09 0.252243E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 38B811

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66154644.95 27601261.26 38553383.68 17632458.12 0.252243E+09
February 93910992.53 40047706.36 53863286.17 44530306.10 0.179034E+09
March 0.141729E+09 71108672.13 70619852.85 99578514.70 0.149941E+09
April 0.190160E+09 0.102597E+09 87562509.23 0.180175E+09 82365649.54
May 0.212627E+09 93488700.05 0.119138E+09 0.241723E+09 37381881.85
June 0.232952E+09 0.111454E+09 0.121498E+09 0.290553E+09 20356177.48
July 0.235812E+09 0.110742E+09 0.125070E+09 0.301035E+09 18109070.24
August 0.181819E+09 79488612.79 0.102331E+09 0.224527E+09 23492738.09
September 0.140920E+09 63096177.99 77823577.19 0.154007E+09 43758130.18
October 88152517.12 33429015.42 54723501.70 68485584.97 83745573.56
November 54292532.24 18141898.49 36150633.75 21981953.35 0.140672E+09
December 51187152.06 18907669.02 32279483.05 10545333.29 0.246055E+09
           
Annual Sum or Average 0.168972E+10 0.770104E+09 0.919612E+09 0.165477E+10 0.127715E+10
Minimum of Months 51187152.06 18141898.49 32279483.05 10545333.29 18109070.24
Maximum of Months 0.235812E+09 0.111454E+09 0.125070E+09 0.301035E+09 0.252243E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C044D6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66154644.95 27601261.26 38553383.68 17632458.12 0.252243E+09
February 93910992.53 40047706.36 53863286.17 44530306.10 0.179034E+09
March 0.141729E+09 71108672.13 70619852.85 99578514.70 0.149941E+09
April 0.190160E+09 0.102597E+09 87562509.23 0.180175E+09 82365649.54
May 0.212627E+09 93488700.05 0.119138E+09 0.241723E+09 37381881.85
June 0.232952E+09 0.111454E+09 0.121498E+09 0.290553E+09 20356177.48
July 0.235812E+09 0.110742E+09 0.125070E+09 0.301035E+09 18109070.24
August 0.181819E+09 79488612.79 0.102331E+09 0.224527E+09 23492738.09
September 0.140920E+09 63096177.99 77823577.19 0.154007E+09 43758130.18
October 88152517.12 33429015.42 54723501.70 68485584.97 83745573.56
November 54292532.24 18141898.49 36150633.75 21981953.35 0.140672E+09
December 51187152.06 18907669.02 32279483.05 10545333.29 0.246055E+09
           
Annual Sum or Average 0.168972E+10 0.770104E+09 0.919612E+09 0.165477E+10 0.127715E+10
Minimum of Months 51187152.06 18141898.49 32279483.05 10545333.29 18109070.24
Maximum of Months 0.235812E+09 0.111454E+09 0.125070E+09 0.301035E+09 0.252243E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 1D94BE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37151508.86 0.00 37151508.86 70644.53 0.343572E+09
February 51510871.40 0.00 51510871.40 2424956.49 0.246566E+09
March 70149122.26 0.00 70149122.26 8953388.13 0.204670E+09
April 87604831.81 70414.33 87534417.48 41726294.44 0.110088E+09
May 0.125573E+09 4565499.96 0.121007E+09 0.115504E+09 48602252.29
June 0.134185E+09 11866571.72 0.122319E+09 0.148190E+09 26517131.28
July 0.132263E+09 8479183.97 0.123784E+09 0.156683E+09 22445932.30
August 0.102900E+09 906593.22 0.101993E+09 0.115395E+09 28240738.65
September 78881155.06 17.86 78881137.20 65057099.41 58936267.02
October 56769130.58 0.00 56769130.58 20748863.26 0.114059E+09
November 36359880.57 0.00 36359880.57 2551063.53 0.191625E+09
December 31506495.61 0.00 31506495.61 0.00 0.329899E+09
           
Annual Sum or Average 0.944854E+09 25888281.06 0.918965E+09 0.677304E+09 0.172522E+10
Minimum of Months 31506495.61 0.00 31506495.61 0.00 22445932.30
Maximum of Months 0.134185E+09 11866571.72 0.123784E+09 0.156683E+09 0.343572E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 18748E

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 36651505.51 0.00 36651505.51 63217.04 0.343771E+09
February 50870309.15 0.00 50870309.15 2296633.81 0.246830E+09
March 69331989.74 0.00 69331989.74 8633375.99 0.204930E+09
April 86697912.90 72809.29 86625103.62 41014174.91 0.110010E+09
May 0.123403E+09 4010906.46 0.119392E+09 0.113382E+09 48149010.16
June 0.133669E+09 12541326.43 0.121127E+09 0.147441E+09 25742716.30
July 0.131060E+09 8525865.63 0.122534E+09 0.155577E+09 22027467.23
August 0.101421E+09 707517.64 0.100713E+09 0.113926E+09 28011509.23
September 77912443.28 87.81 77912355.47 64102861.67 58818398.10
October 55979411.80 0.00 55979411.80 20160675.42 0.114059E+09
November 35844192.21 0.00 35844192.21 2449055.07 0.191792E+09
December 31056130.81 0.00 31056130.81 0.00 0.330075E+09
           
Annual Sum or Average 0.933896E+09 25858513.25 0.908037E+09 0.669045E+09 0.172422E+10
Minimum of Months 31056130.81 0.00 31056130.81 0.00 22027467.23
Maximum of Months 0.133669E+09 12541326.43 0.122534E+09 0.155577E+09 0.343771E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 137A56

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.239911E+09 0.165353E+09 74558105.85 0.194062E+09 0.383443E+09
February 0.270118E+09 0.180460E+09 89657553.56 0.239888E+09 0.297302E+09
March 0.256878E+09 0.156174E+09 0.100704E+09 0.211596E+09 0.270114E+09
April 0.239515E+09 0.125090E+09 0.114425E+09 0.200384E+09 0.160054E+09
May 0.219759E+09 75854945.99 0.143904E+09 0.193018E+09 79437318.14
June 0.192932E+09 52378133.02 0.140554E+09 0.184766E+09 47847899.77
July 0.218781E+09 70478076.00 0.148303E+09 0.221875E+09 42008903.57
August 0.227942E+09 95010658.26 0.132931E+09 0.237401E+09 52643391.67
September 0.219289E+09 0.111487E+09 0.107802E+09 0.218871E+09 93101961.29
October 0.189625E+09 0.107596E+09 82028783.73 0.170982E+09 0.162952E+09
November 0.169237E+09 0.105318E+09 63919169.37 0.143782E+09 0.239595E+09
December 0.187143E+09 0.121485E+09 65658022.47 0.138629E+09 0.373188E+09
           
Annual Sum or Average 0.263113E+10 0.136668E+10 0.126444E+10 0.235525E+10 0.220169E+10
Minimum of Months 0.169237E+09 52378133.02 63919169.37 0.138629E+09 42008903.57
Maximum of Months 0.270118E+09 0.180460E+09 0.148303E+09 0.239888E+09 0.383443E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 8D508E

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.208019E+09 0.144763E+09 63255465.77 0.172582E+09 0.219085E+09
February 0.237938E+09 0.160780E+09 77157523.13 0.216732E+09 0.166273E+09
March 0.232058E+09 0.146915E+09 85142476.22 0.201720E+09 0.150356E+09
April 0.203187E+09 0.110222E+09 92965343.12 0.178023E+09 86815334.78
May 0.176366E+09 60115035.59 0.116251E+09 0.166148E+09 40031506.39
June 0.153118E+09 40618846.20 0.112500E+09 0.158116E+09 21432577.93
July 0.172981E+09 54590944.70 0.118390E+09 0.185492E+09 17899277.85
August 0.184859E+09 77208326.48 0.107651E+09 0.199750E+09 22750364.64
September 0.191856E+09 0.102188E+09 89667623.89 0.201092E+09 46956392.53
October 0.169417E+09 99701737.44 69714834.93 0.163965E+09 86890536.40
November 0.146025E+09 91684299.18 54340559.53 0.129366E+09 0.132487E+09
December 0.160606E+09 0.105351E+09 55254886.48 0.122570E+09 0.213503E+09
           
Annual Sum or Average 0.223643E+10 0.119414E+10 0.104229E+10 0.209556E+10 0.120448E+10
Minimum of Months 0.146025E+09 40618846.20 54340559.53 0.122570E+09 17899277.85
Maximum of Months 0.237938E+09 0.160780E+09 0.118390E+09 0.216732E+09 0.219085E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: B2D381

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.208019E+09 0.144763E+09 63255465.77 0.172582E+09 0.219085E+09
February 0.237938E+09 0.160780E+09 77157523.13 0.216732E+09 0.166273E+09
March 0.232058E+09 0.146915E+09 85142476.22 0.201720E+09 0.150356E+09
April 0.203187E+09 0.110222E+09 92965343.12 0.178023E+09 86815334.78
May 0.176366E+09 60115035.59 0.116251E+09 0.166148E+09 40031506.39
June 0.153118E+09 40618846.20 0.112500E+09 0.158116E+09 21432577.93
July 0.172981E+09 54590944.70 0.118390E+09 0.185492E+09 17899277.85
August 0.184859E+09 77208326.48 0.107651E+09 0.199750E+09 22750364.64
September 0.191856E+09 0.102188E+09 89667623.89 0.201092E+09 46956392.53
October 0.169417E+09 99701737.44 69714834.93 0.163965E+09 86890536.40
November 0.146025E+09 91684299.18 54340559.53 0.129366E+09 0.132487E+09
December 0.160606E+09 0.105351E+09 55254886.48 0.122570E+09 0.213503E+09
           
Annual Sum or Average 0.223643E+10 0.119414E+10 0.104229E+10 0.209556E+10 0.120448E+10
Minimum of Months 0.146025E+09 40618846.20 54340559.53 0.122570E+09 17899277.85
Maximum of Months 0.237938E+09 0.160780E+09 0.118390E+09 0.216732E+09 0.219085E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 1DA13A

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.208019E+09 0.144763E+09 63255465.77 0.172582E+09 0.219085E+09
February 0.237938E+09 0.160780E+09 77157523.13 0.216732E+09 0.166273E+09
March 0.232058E+09 0.146915E+09 85142476.22 0.201720E+09 0.150356E+09
April 0.203187E+09 0.110222E+09 92965343.12 0.178023E+09 86815334.78
May 0.176366E+09 60115035.59 0.116251E+09 0.166148E+09 40031506.39
June 0.153118E+09 40618846.20 0.112500E+09 0.158116E+09 21432577.93
July 0.172981E+09 54590944.70 0.118390E+09 0.185492E+09 17899277.85
August 0.184859E+09 77208326.48 0.107651E+09 0.199750E+09 22750364.64
September 0.191856E+09 0.102188E+09 89667623.89 0.201092E+09 46956392.53
October 0.169417E+09 99701737.44 69714834.93 0.163965E+09 86890536.40
November 0.146025E+09 91684299.18 54340559.53 0.129366E+09 0.132487E+09
December 0.160606E+09 0.105351E+09 55254886.48 0.122570E+09 0.213503E+09
           
Annual Sum or Average 0.223643E+10 0.119414E+10 0.104229E+10 0.209556E+10 0.120448E+10
Minimum of Months 0.146025E+09 40618846.20 54340559.53 0.122570E+09 17899277.85
Maximum of Months 0.237938E+09 0.160780E+09 0.118390E+09 0.216732E+09 0.219085E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 44E54A

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.208019E+09 0.144763E+09 63255465.77 0.172582E+09 0.219085E+09
February 0.237938E+09 0.160780E+09 77157523.13 0.216732E+09 0.166273E+09
March 0.232058E+09 0.146915E+09 85142476.22 0.201720E+09 0.150356E+09
April 0.203187E+09 0.110222E+09 92965343.12 0.178023E+09 86815334.78
May 0.176366E+09 60115035.59 0.116251E+09 0.166148E+09 40031506.39
June 0.153118E+09 40618846.20 0.112500E+09 0.158116E+09 21432577.93
July 0.172981E+09 54590944.70 0.118390E+09 0.185492E+09 17899277.85
August 0.184859E+09 77208326.48 0.107651E+09 0.199750E+09 22750364.64
September 0.191856E+09 0.102188E+09 89667623.89 0.201092E+09 46956392.53
October 0.169417E+09 99701737.44 69714834.93 0.163965E+09 86890536.40
November 0.146025E+09 91684299.18 54340559.53 0.129366E+09 0.132487E+09
December 0.160606E+09 0.105351E+09 55254886.48 0.122570E+09 0.213503E+09
           
Annual Sum or Average 0.223643E+10 0.119414E+10 0.104229E+10 0.209556E+10 0.120448E+10
Minimum of Months 0.146025E+09 40618846.20 54340559.53 0.122570E+09 17899277.85
Maximum of Months 0.237938E+09 0.160780E+09 0.118390E+09 0.216732E+09 0.219085E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 757D10

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 40757572.28 27337234.09 13420338.19 31616719.93 86403663.45
February 47316214.80 30780258.90 16535955.90 40119431.09 65869466.05
March 46555829.10 27514007.44 19041821.66 36172501.83 58710482.82
April 41901726.12 20137316.27 21764409.84 32619419.16 33697086.62
May 39242654.21 12130490.57 27112163.65 34091109.84 15695072.38
June 34475913.49 7853008.83 26622904.67 34260465.69 8990153.95
July 39580632.79 11391369.73 28189263.06 41509296.64 7629303.47
August 41179813.47 16085035.59 25094777.88 42801514.87 9982055.71
September 39233813.75 18946597.70 20287216.05 37701754.03 19017134.28
October 34506839.52 19181267.49 15325572.03 29676613.01 34873389.13
November 29305013.64 17708679.71 11596333.92 23716788.35 53001434.66
December 31619160.37 19937033.16 11682127.21 22523701.60 84306717.26
           
Annual Sum or Average 0.465675E+09 0.229002E+09 0.236673E+09 0.406809E+09 0.478176E+09
Minimum of Months 29305013.64 7853008.83 11596333.92 22523701.60 7629303.47
Maximum of Months 47316214.80 30780258.90 28189263.06 42801514.87 86403663.45



Table of Contents

Report: WindowEnergyReportMonthly

For: E33BAE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62279903.89 27993126.01 34286777.88 20104449.38 0.252261E+09
February 92221179.66 44951949.84 47269229.82 50811242.71 0.181938E+09
March 0.135226E+09 73415177.65 61810811.41 98506841.03 0.153665E+09
April 0.167521E+09 89847182.29 77673679.34 0.153287E+09 83592684.30
May 0.209915E+09 0.106267E+09 0.103648E+09 0.235418E+09 37737043.80
June 0.187715E+09 84229119.13 0.103486E+09 0.226435E+09 20332741.62
July 0.212426E+09 0.103446E+09 0.108979E+09 0.262410E+09 17136723.12
August 0.178994E+09 86740319.10 92253926.23 0.211636E+09 22258759.01
September 0.135017E+09 64886265.28 70130273.73 0.139557E+09 46163396.62
October 87257694.32 37823508.38 49434185.94 64902581.94 87974660.12
November 50798159.77 18656809.84 32141349.93 19994292.40 0.143503E+09
December 47055100.24 17834379.99 29220720.25 10049145.26 0.243972E+09
           
Annual Sum or Average 0.156643E+10 0.756091E+09 0.810335E+09 0.149311E+10 0.129053E+10
Minimum of Months 47055100.24 17834379.99 29220720.25 10049145.26 17136723.12
Maximum of Months 0.212426E+09 0.106267E+09 0.108979E+09 0.262410E+09 0.252261E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 24167A

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.208019E+09 0.144763E+09 63255465.77 0.173896E+09 0.215268E+09
February 0.237938E+09 0.160780E+09 77157523.13 0.218019E+09 0.162852E+09
March 0.232058E+09 0.146915E+09 85142476.22 0.202818E+09 0.147046E+09
April 0.203187E+09 0.110222E+09 92965343.12 0.178605E+09 85435338.14
May 0.176366E+09 60115035.59 0.116251E+09 0.165720E+09 39953651.21
June 0.153118E+09 40618846.20 0.112500E+09 0.157153E+09 21474586.98
July 0.172981E+09 54590944.70 0.118390E+09 0.183672E+09 18602953.30
August 0.184859E+09 77208326.48 0.107651E+09 0.198000E+09 23829632.33
September 0.191856E+09 0.102188E+09 89667623.89 0.200362E+09 47525489.38
October 0.169417E+09 99701737.44 69714834.93 0.163896E+09 86599138.62
November 0.146025E+09 91684299.18 54340559.53 0.129812E+09 0.130865E+09
December 0.160606E+09 0.105351E+09 55254886.48 0.123514E+09 0.209799E+09
           
Annual Sum or Average 0.223643E+10 0.119414E+10 0.104229E+10 0.209547E+10 0.118925E+10
Minimum of Months 0.146025E+09 40618846.20 54340559.53 0.123514E+09 18602953.30
Maximum of Months 0.237938E+09 0.160780E+09 0.118390E+09 0.218019E+09 0.215268E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 2C0938

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.208019E+09 0.144763E+09 63255465.77 0.173896E+09 0.215268E+09
February 0.237938E+09 0.160780E+09 77157523.13 0.218019E+09 0.162852E+09
March 0.232058E+09 0.146915E+09 85142476.22 0.202818E+09 0.147046E+09
April 0.203187E+09 0.110222E+09 92965343.12 0.178603E+09 85457042.57
May 0.176366E+09 60115035.59 0.116251E+09 0.165701E+09 39972721.68
June 0.153118E+09 40618846.20 0.112500E+09 0.157177E+09 21473535.82
July 0.172981E+09 54590944.70 0.118390E+09 0.183685E+09 18601619.73
August 0.184859E+09 77208326.48 0.107651E+09 0.197972E+09 23857425.13
September 0.191856E+09 0.102188E+09 89667623.89 0.200362E+09 47525489.38
October 0.169417E+09 99701737.44 69714834.93 0.163896E+09 86599138.62
November 0.146025E+09 91684299.18 54340559.53 0.129812E+09 0.130865E+09
December 0.160606E+09 0.105351E+09 55254886.48 0.123514E+09 0.209799E+09
           
Annual Sum or Average 0.223643E+10 0.119414E+10 0.104229E+10 0.209546E+10 0.118932E+10
Minimum of Months 0.146025E+09 40618846.20 54340559.53 0.123514E+09 18601619.73
Maximum of Months 0.237938E+09 0.160780E+09 0.118390E+09 0.218019E+09 0.215268E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 8600DD

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.208019E+09 0.144763E+09 63255465.77 0.169608E+09 0.231886E+09
February 0.237938E+09 0.160780E+09 77157523.13 0.213228E+09 0.177160E+09
March 0.232058E+09 0.146915E+09 85142476.22 0.197760E+09 0.162839E+09
April 0.203187E+09 0.110222E+09 92965343.12 0.172871E+09 97396999.28
May 0.176366E+09 60115035.59 0.116251E+09 0.158567E+09 48054232.60
June 0.153118E+09 40618846.20 0.112500E+09 0.149393E+09 27699356.32
July 0.172981E+09 54590944.70 0.118390E+09 0.176623E+09 24302746.96
August 0.184859E+09 77208326.48 0.107651E+09 0.192324E+09 30474650.03
September 0.191856E+09 0.102188E+09 89667623.89 0.196078E+09 55282620.72
October 0.169417E+09 99701737.44 69714834.93 0.160068E+09 96784236.62
November 0.146025E+09 91684299.18 54340559.53 0.126459E+09 0.143899E+09
December 0.160606E+09 0.105351E+09 55254886.48 0.120084E+09 0.227552E+09
           
Annual Sum or Average 0.223643E+10 0.119414E+10 0.104229E+10 0.203306E+10 0.132333E+10
Minimum of Months 0.146025E+09 40618846.20 54340559.53 0.120084E+09 24302746.96
Maximum of Months 0.237938E+09 0.160780E+09 0.118390E+09 0.213228E+09 0.231886E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: A1ED60

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37731459.39 0.00 37731459.39 122613.81 0.334718E+09
February 52349543.58 0.00 52349543.58 2559635.98 0.238173E+09
March 71307748.97 0.00 71307748.97 9233318.01 0.196681E+09
April 90445924.50 687456.19 89758468.32 42327303.30 0.103480E+09
May 0.131398E+09 7001709.07 0.124396E+09 0.116220E+09 44199241.39
June 0.141884E+09 15497143.17 0.126387E+09 0.150124E+09 24140757.99
July 0.140048E+09 11925910.96 0.128122E+09 0.155838E+09 22790787.70
August 0.106416E+09 1796240.19 0.104620E+09 0.111891E+09 29401700.33
September 80274825.05 18471.35 80256353.70 63503594.09 58007849.17
October 57597588.49 0.00 57597588.49 20213005.48 0.111214E+09
November 36906694.75 0.00 36906694.75 2349264.65 0.186550E+09
December 31969110.43 0.00 31969110.43 0.00 0.321561E+09
           
Annual Sum or Average 0.978330E+09 36926930.92 0.941403E+09 0.674383E+09 0.167092E+10
Minimum of Months 31969110.43 0.00 31969110.43 0.00 22790787.70
Maximum of Months 0.141884E+09 15497143.17 0.128122E+09 0.155838E+09 0.334718E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: E8D997

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37731459.39 0.00 37731459.39 122613.81 0.334718E+09
February 52349543.58 0.00 52349543.58 2559635.98 0.238173E+09
March 71307748.97 0.00 71307748.97 9233318.01 0.196681E+09
April 90445924.50 687456.19 89758468.32 42327303.30 0.103480E+09
May 0.131398E+09 7001709.07 0.124396E+09 0.116220E+09 44199241.39
June 0.141884E+09 15497143.17 0.126387E+09 0.150124E+09 24140757.99
July 0.140048E+09 11925910.96 0.128122E+09 0.155838E+09 22790787.70
August 0.106416E+09 1796240.19 0.104620E+09 0.111891E+09 29401700.33
September 80274825.05 18471.35 80256353.70 63503594.09 58007849.17
October 57597588.49 0.00 57597588.49 20213005.48 0.111214E+09
November 36906694.75 0.00 36906694.75 2349264.65 0.186550E+09
December 31969110.43 0.00 31969110.43 0.00 0.321561E+09
           
Annual Sum or Average 0.978330E+09 36926930.92 0.941403E+09 0.674383E+09 0.167092E+10
Minimum of Months 31969110.43 0.00 31969110.43 0.00 22790787.70
Maximum of Months 0.141884E+09 15497143.17 0.128122E+09 0.155838E+09 0.334718E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 88E1FC

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37731459.39 0.00 37731459.39 122613.81 0.334718E+09
February 52349543.58 0.00 52349543.58 2559635.98 0.238173E+09
March 71307748.97 0.00 71307748.97 9233318.01 0.196681E+09
April 90445924.50 687456.19 89758468.32 42327303.30 0.103480E+09
May 0.131398E+09 7001709.07 0.124396E+09 0.116220E+09 44199241.39
June 0.141884E+09 15497143.17 0.126387E+09 0.150124E+09 24140757.99
July 0.140048E+09 11925910.96 0.128122E+09 0.155838E+09 22790787.70
August 0.106416E+09 1796240.19 0.104620E+09 0.111891E+09 29401700.33
September 80274825.05 18471.35 80256353.70 63503594.09 58007849.17
October 57597588.49 0.00 57597588.49 20213005.48 0.111214E+09
November 36906694.75 0.00 36906694.75 2349264.65 0.186550E+09
December 31969110.43 0.00 31969110.43 0.00 0.321561E+09
           
Annual Sum or Average 0.978330E+09 36926930.92 0.941403E+09 0.674383E+09 0.167092E+10
Minimum of Months 31969110.43 0.00 31969110.43 0.00 22790787.70
Maximum of Months 0.141884E+09 15497143.17 0.128122E+09 0.155838E+09 0.334718E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: F83F33

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 88206193.26 36801681.69 51404511.58 21555996.54 0.342936E+09
February 0.125215E+09 53396941.81 71817714.90 55212141.44 0.242355E+09
March 0.188971E+09 94811562.85 94159803.80 0.125159E+09 0.205798E+09
April 0.253547E+09 0.136797E+09 0.116750E+09 0.225227E+09 0.114468E+09
May 0.283502E+09 0.124652E+09 0.158851E+09 0.298074E+09 56227895.41
June 0.310603E+09 0.148606E+09 0.161997E+09 0.359021E+09 34224291.23
July 0.314416E+09 0.147657E+09 0.166760E+09 0.371855E+09 31825886.01
August 0.242426E+09 0.105985E+09 0.136441E+09 0.272813E+09 40398677.07
September 0.187893E+09 84128237.32 0.103765E+09 0.183853E+09 70183879.02
October 0.117537E+09 44572020.56 72964668.94 78104436.22 0.124941E+09
November 72390042.99 24189197.99 48200845.00 24337395.50 0.199151E+09
December 68249536.08 25210225.35 43039310.73 13006522.83 0.335723E+09
           
Annual Sum or Average 0.225296E+10 0.102681E+10 0.122615E+10 0.202822E+10 0.179823E+10
Minimum of Months 68249536.08 24189197.99 43039310.73 13006522.83 31825886.01
Maximum of Months 0.314416E+09 0.148606E+09 0.166760E+09 0.371855E+09 0.342936E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: B1F5EE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 65531766.75 27601261.26 37930505.49 16305345.52 0.255237E+09
February 93085187.80 40047706.36 53037481.45 41546918.15 0.179720E+09
March 0.140649E+09 71108672.13 69540600.64 94040533.43 0.152394E+09
April 0.188884E+09 0.102597E+09 86286145.54 0.169253E+09 84169099.79
May 0.210822E+09 93488700.05 0.117333E+09 0.223301E+09 41106898.46
June 0.231210E+09 0.111454E+09 0.119755E+09 0.268872E+09 25112795.53
July 0.234054E+09 0.110742E+09 0.123312E+09 0.277782E+09 23586016.38
August 0.180273E+09 79488612.79 0.100785E+09 0.204063E+09 29434419.32
September 0.139673E+09 63096177.99 76576459.30 0.137426E+09 51797809.71
October 87194180.13 33429015.42 53765164.71 58419467.58 92361271.51
November 53665040.71 18141898.49 35523142.21 18269584.80 0.147365E+09
December 50643488.89 18907669.02 31735819.88 9846695.92 0.249590E+09
           
Annual Sum or Average 0.167568E+10 0.770104E+09 0.905580E+09 0.151913E+10 0.133187E+10
Minimum of Months 50643488.89 18141898.49 31735819.88 9846695.92 23586016.38
Maximum of Months 0.234054E+09 0.111454E+09 0.123312E+09 0.277782E+09 0.255237E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: F52F3D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66154644.95 27601261.26 38553383.68 15957348.97 0.259122E+09
February 93910992.53 40047706.36 53863286.17 40313154.82 0.184687E+09
March 0.141729E+09 71108672.13 70619852.85 91725948.60 0.159145E+09
April 0.190160E+09 0.102597E+09 87562509.23 0.165499E+09 88915461.39
May 0.212627E+09 93488700.05 0.119138E+09 0.221222E+09 43167524.61
June 0.232952E+09 0.111454E+09 0.121498E+09 0.268580E+09 25461639.09
July 0.235812E+09 0.110742E+09 0.125070E+09 0.279869E+09 22148817.46
August 0.181819E+09 79488612.79 0.102331E+09 0.204734E+09 28132928.06
September 0.140920E+09 63096177.99 77823577.19 0.136277E+09 52010666.49
October 88152517.12 33429015.42 54723501.70 56976656.53 93343689.27
November 54292532.24 18141898.49 36150633.75 17812815.78 0.148780E+09
December 51187152.06 18907669.02 32279483.05 9672532.41 0.251510E+09
           
Annual Sum or Average 0.168972E+10 0.770104E+09 0.919612E+09 0.150864E+10 0.135642E+10
Minimum of Months 51187152.06 18141898.49 32279483.05 9672532.41 22148817.46
Maximum of Months 0.235812E+09 0.111454E+09 0.125070E+09 0.279869E+09 0.259122E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 80885D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.624057E+09 0.434290E+09 0.189766E+09 0.506548E+09 0.667109E+09
February 0.713813E+09 0.482341E+09 0.231473E+09 0.634976E+09 0.508092E+09
March 0.696173E+09 0.440746E+09 0.255427E+09 0.587569E+09 0.470840E+09
April 0.609562E+09 0.330666E+09 0.278896E+09 0.511610E+09 0.285093E+09
May 0.529098E+09 0.180345E+09 0.348753E+09 0.468093E+09 0.142661E+09
June 0.459355E+09 0.121857E+09 0.337499E+09 0.440474E+09 82059584.44
July 0.518944E+09 0.163773E+09 0.355171E+09 0.523814E+09 70389968.58
August 0.554578E+09 0.231625E+09 0.322953E+09 0.570754E+09 87936445.78
September 0.575568E+09 0.306565E+09 0.269003E+09 0.581083E+09 0.162062E+09
October 0.508250E+09 0.299105E+09 0.209145E+09 0.476055E+09 0.279195E+09
November 0.438075E+09 0.275053E+09 0.163022E+09 0.377232E+09 0.408366E+09
December 0.481818E+09 0.316053E+09 0.165765E+09 0.359906E+09 0.648325E+09
           
Annual Sum or Average 0.670929E+10 0.358242E+10 0.312687E+10 0.603811E+10 0.381213E+10
Minimum of Months 0.438075E+09 0.121857E+09 0.163022E+09 0.359906E+09 70389968.58
Maximum of Months 0.713813E+09 0.482341E+09 0.355171E+09 0.634976E+09 0.667109E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FEEF06

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.208019E+09 0.144763E+09 63255465.77 0.172046E+09 0.218724E+09
February 0.237938E+09 0.160780E+09 77157523.13 0.215336E+09 0.165777E+09
March 0.232058E+09 0.146915E+09 85142476.22 0.199512E+09 0.152904E+09
April 0.203187E+09 0.110222E+09 92965343.12 0.173795E+09 92774797.05
May 0.176366E+09 60115035.59 0.116251E+09 0.158812E+09 46357631.24
June 0.153118E+09 40618846.20 0.112500E+09 0.150150E+09 25936441.21
July 0.172981E+09 54590944.70 0.118390E+09 0.177558E+09 22490878.62
August 0.184859E+09 77208326.48 0.107651E+09 0.193570E+09 27543316.36
September 0.191856E+09 0.102188E+09 89667623.89 0.197131E+09 51621358.08
October 0.169417E+09 99701737.44 69714834.93 0.161729E+09 89700675.37
November 0.146025E+09 91684299.18 54340559.53 0.128367E+09 0.132672E+09
December 0.160606E+09 0.105351E+09 55254886.48 0.122268E+09 0.212261E+09
           
Annual Sum or Average 0.223643E+10 0.119414E+10 0.104229E+10 0.205027E+10 0.123876E+10
Minimum of Months 0.146025E+09 40618846.20 54340559.53 0.122268E+09 22490878.62
Maximum of Months 0.237938E+09 0.160780E+09 0.118390E+09 0.215336E+09 0.218724E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 2BE8DE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 63703982.43 27993126.01 35710856.43 19734487.02 0.258199E+09
February 94005072.52 44951949.84 49053122.69 50079001.98 0.186842E+09
March 0.137464E+09 73415177.65 64048842.56 96616707.76 0.160663E+09
April 0.170078E+09 89847182.29 80230388.87 0.149518E+09 91377854.34
May 0.213757E+09 0.106267E+09 0.107490E+09 0.231221E+09 44554775.24
June 0.191179E+09 84229119.13 0.106950E+09 0.222236E+09 25381362.26
July 0.215801E+09 0.103446E+09 0.112355E+09 0.258861E+09 21666821.37
August 0.182119E+09 86740319.10 95378909.84 0.209919E+09 26634608.47
September 0.137727E+09 64886265.28 72840586.27 0.138893E+09 50996226.82
October 89543985.49 37823508.38 51720477.12 64810972.06 92237507.48
November 52288645.51 18656809.84 33631835.66 19867600.67 0.146683E+09
December 48363105.39 17834379.99 30528725.40 9886630.95 0.248537E+09
           
Annual Sum or Average 0.159603E+10 0.756091E+09 0.839939E+09 0.147164E+10 0.135377E+10
Minimum of Months 48363105.39 17834379.99 30528725.40 9886630.95 21666821.37
Maximum of Months 0.215801E+09 0.106267E+09 0.112355E+09 0.258861E+09 0.258199E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 513E2A

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59076561.87 27993126.01 31083435.86 19254766.46 0.260706E+09
February 88020575.15 44951949.84 43068625.31 48322924.47 0.189705E+09
March 0.129778E+09 73415177.65 56362552.69 93550209.95 0.163571E+09
April 0.154177E+09 84356296.29 69820726.26 0.135345E+09 93370125.06
May 0.171559E+09 82099572.91 89459010.49 0.181230E+09 45096145.34
June 0.155498E+09 65581716.96 89916181.35 0.179250E+09 24731723.78
July 0.178097E+09 82740805.29 95356403.94 0.212987E+09 20469819.45
August 0.158169E+09 76443288.00 81725462.43 0.181996E+09 25875847.40
September 0.128490E+09 64752255.41 63738242.94 0.129778E+09 50247207.35
October 82286754.11 37823508.38 44463245.73 59673078.94 93029112.24
November 47546229.39 18656809.84 28889419.54 18669658.72 0.148645E+09
December 44230199.13 17834379.99 26395819.14 9676137.14 0.250762E+09
           
Annual Sum or Average 0.139693E+10 0.676649E+09 0.720279E+09 0.126973E+10 0.136621E+10
Minimum of Months 44230199.13 17834379.99 26395819.14 9676137.14 20469819.45
Maximum of Months 0.178097E+09 84356296.29 95356403.94 0.212987E+09 0.260706E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BA5CD9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62214197.84 27993126.01 34221071.83 19562013.37 0.259544E+09
February 92078328.28 44951949.84 47126378.44 49481733.67 0.188159E+09
March 0.134989E+09 73415177.65 61574147.73 95534080.25 0.161621E+09
April 0.167184E+09 89839980.39 77343739.58 0.147351E+09 91562149.42
May 0.198234E+09 97351279.88 0.100883E+09 0.213097E+09 45200364.55
June 0.176861E+09 76061316.11 0.100799E+09 0.204772E+09 25253215.66
July 0.200802E+09 94622460.17 0.106179E+09 0.240378E+09 21339421.71
August 0.176012E+09 84816688.95 91195077.52 0.203074E+09 26437075.10
September 0.134810E+09 64886265.28 69923268.82 0.135987E+09 50731260.61
October 87207589.18 37823508.38 49384080.80 63029626.81 92559702.83
November 50761866.71 18656809.84 32105056.87 19445861.64 0.147565E+09
December 47032561.17 17834379.99 29198181.18 9816388.10 0.249659E+09
           
Annual Sum or Average 0.152819E+10 0.728253E+09 0.799932E+09 0.140153E+10 0.135963E+10
Minimum of Months 47032561.17 17834379.99 29198181.18 9816388.10 21339421.71
Maximum of Months 0.200802E+09 97351279.88 0.106179E+09 0.240378E+09 0.259544E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 1AD478

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.346698E+09 0.241272E+09 0.105426E+09 0.283749E+09 0.376302E+09
February 0.396563E+09 0.267967E+09 0.128596E+09 0.356629E+09 0.284896E+09
March 0.386763E+09 0.244859E+09 0.141904E+09 0.331309E+09 0.261659E+09
April 0.338646E+09 0.183704E+09 0.154942E+09 0.290785E+09 0.155846E+09
May 0.293943E+09 0.100192E+09 0.193752E+09 0.269679E+09 74345117.49
June 0.255197E+09 67698076.99 0.187499E+09 0.256777E+09 40567819.20
July 0.288302E+09 90984907.83 0.197317E+09 0.304075E+09 33414803.36
August 0.308099E+09 0.128681E+09 0.179419E+09 0.328688E+09 41807238.74
September 0.319760E+09 0.170314E+09 0.149446E+09 0.331230E+09 84504935.21
October 0.282361E+09 0.166170E+09 0.116191E+09 0.269669E+09 0.152280E+09
November 0.243375E+09 0.152807E+09 90567599.22 0.212384E+09 0.228417E+09
December 0.267677E+09 0.175585E+09 92091477.47 0.201426E+09 0.365762E+09
           
Annual Sum or Average 0.372738E+10 0.199023E+10 0.173715E+10 0.343640E+10 0.209980E+10
Minimum of Months 0.243375E+09 67698076.99 90567599.22 0.201426E+09 33414803.36
Maximum of Months 0.396563E+09 0.267967E+09 0.197317E+09 0.356629E+09 0.376302E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 27F0AC

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.554717E+09 0.386036E+09 0.168681E+09 0.453618E+09 0.601845E+09
February 0.634501E+09 0.428747E+09 0.205753E+09 0.570166E+09 0.455214E+09
March 0.618820E+09 0.391774E+09 0.227047E+09 0.529952E+09 0.417042E+09
April 0.541833E+09 0.293926E+09 0.247908E+09 0.465868E+09 0.246753E+09
May 0.470309E+09 0.160307E+09 0.310003E+09 0.433458E+09 0.115878E+09
June 0.408316E+09 0.108317E+09 0.299999E+09 0.413265E+09 62528657.76
July 0.461284E+09 0.145576E+09 0.315708E+09 0.489386E+09 50741702.25
August 0.492959E+09 0.205889E+09 0.287070E+09 0.528151E+09 63684997.67
September 0.511616E+09 0.272502E+09 0.239114E+09 0.531241E+09 0.132071E+09
October 0.451778E+09 0.265871E+09 0.185906E+09 0.432141E+09 0.240987E+09
November 0.389400E+09 0.244491E+09 0.144908E+09 0.339882E+09 0.363999E+09
December 0.428283E+09 0.280936E+09 0.147346E+09 0.322103E+09 0.584749E+09
           
Annual Sum or Average 0.596381E+10 0.318437E+10 0.277944E+10 0.550923E+10 0.333549E+10
Minimum of Months 0.389400E+09 0.108317E+09 0.144908E+09 0.322103E+09 50741702.25
Maximum of Months 0.634501E+09 0.428747E+09 0.315708E+09 0.570166E+09 0.601845E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 724114

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.208019E+09 0.144763E+09 63255465.77 0.168341E+09 0.224978E+09
February 0.237938E+09 0.160780E+09 77157523.13 0.211271E+09 0.170938E+09
March 0.232058E+09 0.146915E+09 85142476.22 0.195985E+09 0.157488E+09
April 0.203187E+09 0.110222E+09 92965343.12 0.171553E+09 94044959.59
May 0.176366E+09 60115035.59 0.116251E+09 0.158802E+09 45224902.17
June 0.153118E+09 40618846.20 0.112500E+09 0.150880E+09 25006124.60
July 0.172981E+09 54590944.70 0.118390E+09 0.179052E+09 20826560.19
August 0.184859E+09 77208326.48 0.107651E+09 0.193472E+09 26335972.64
September 0.191856E+09 0.102188E+09 89667623.89 0.195406E+09 51858486.48
October 0.169417E+09 99701737.44 69714834.93 0.159288E+09 92224994.21
November 0.146025E+09 91684299.18 54340559.53 0.125754E+09 0.136967E+09
December 0.160606E+09 0.105351E+09 55254886.48 0.119516E+09 0.218502E+09
           
Annual Sum or Average 0.223643E+10 0.119414E+10 0.104229E+10 0.202932E+10 0.126440E+10
Minimum of Months 0.146025E+09 40618846.20 54340559.53 0.119516E+09 20826560.19
Maximum of Months 0.237938E+09 0.160780E+09 0.118390E+09 0.211271E+09 0.224978E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: D538C4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 88113123.38 36801681.69 51311441.69 21387310.74 0.345879E+09
February 0.125090E+09 53396941.81 71693341.05 54602641.89 0.244147E+09
March 0.188808E+09 94811562.85 93996377.28 0.123674E+09 0.208782E+09
April 0.253353E+09 0.136797E+09 0.116556E+09 0.222449E+09 0.117183E+09
May 0.283230E+09 0.124652E+09 0.158578E+09 0.296471E+09 56660783.13
June 0.310338E+09 0.148606E+09 0.161732E+09 0.359346E+09 33305270.52
July 0.314147E+09 0.147657E+09 0.166491E+09 0.374714E+09 28894128.29
August 0.242191E+09 0.105985E+09 0.136206E+09 0.276153E+09 35820048.65
September 0.187705E+09 84128237.32 0.103577E+09 0.184676E+09 67554659.10
October 0.117394E+09 44572020.56 72822374.19 78235082.54 0.123186E+09
November 72296811.01 24189197.99 48107613.02 24367506.80 0.197841E+09
December 68168916.26 25210225.35 42958690.91 12880368.37 0.336529E+09
           
Annual Sum or Average 0.225084E+10 0.102681E+10 0.122403E+10 0.202896E+10 0.179578E+10
Minimum of Months 68168916.26 24189197.99 42958690.91 12880368.37 28894128.29
Maximum of Months 0.314147E+09 0.148606E+09 0.166491E+09 0.374714E+09 0.345879E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 5635BC

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 86069006.00 36801681.69 49267324.32 21138923.60 0.346605E+09
February 0.122384E+09 53396941.81 68986809.39 53466368.89 0.244854E+09
March 0.185274E+09 94811562.85 90462354.43 0.121798E+09 0.209661E+09
April 0.249176E+09 0.136797E+09 0.112379E+09 0.218953E+09 0.117179E+09
May 0.277316E+09 0.124652E+09 0.152665E+09 0.290362E+09 56087631.43
June 0.304637E+09 0.148606E+09 0.156031E+09 0.353457E+09 32876095.08
July 0.308400E+09 0.147657E+09 0.160743E+09 0.368796E+09 28295483.98
August 0.237131E+09 0.105985E+09 0.131146E+09 0.270851E+09 35293631.15
September 0.183617E+09 84128237.32 99489178.93 0.180506E+09 67090108.94
October 0.114246E+09 44572020.56 69674137.76 75707978.39 0.123102E+09
November 70235657.33 24189197.99 46046459.34 23747509.04 0.198397E+09
December 66382553.05 25210225.35 41172327.69 12768455.57 0.337197E+09
           
Annual Sum or Average 0.220487E+10 0.102681E+10 0.117806E+10 0.199155E+10 0.179664E+10
Minimum of Months 66382553.05 24189197.99 41172327.69 12768455.57 28295483.98
Maximum of Months 0.308400E+09 0.148606E+09 0.160743E+09 0.368796E+09 0.346605E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 831C1D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 56597189.09 0.00 56597189.09 108705.88 0.528369E+09
February 78524315.38 0.00 78524315.38 3094843.19 0.379620E+09
March 0.106962E+09 0.00 0.106962E+09 11519777.46 0.319054E+09
April 0.135665E+09 1030161.93 0.134635E+09 57695808.78 0.173159E+09
May 0.197097E+09 10502563.60 0.186594E+09 0.167786E+09 76468929.79
June 0.212826E+09 23245714.75 0.189581E+09 0.221196E+09 42197450.07
July 0.210072E+09 17888866.44 0.192183E+09 0.235390E+09 35985336.89
August 0.159624E+09 2694360.29 0.156930E+09 0.168989E+09 45889727.90
September 0.120348E+09 21360.89 0.120327E+09 93326156.49 94404495.63
October 86396382.73 0.00 86396382.73 28334067.58 0.178779E+09
November 55360042.13 0.00 55360042.13 3209542.46 0.295603E+09
December 47953665.65 0.00 47953665.65 0.00 0.505176E+09
           
Annual Sum or Average 0.146743E+10 55383027.90 0.141204E+10 0.990651E+09 0.267471E+10
Minimum of Months 47953665.65 0.00 47953665.65 0.00 35985336.89
Maximum of Months 0.212826E+09 23245714.75 0.192183E+09 0.235390E+09 0.528369E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 9BB95F

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37731459.39 0.00 37731459.39 66006.17 0.356522E+09
February 52349543.58 0.00 52349543.58 2012156.96 0.256698E+09
March 71307748.97 0.00 71307748.97 7628135.75 0.216074E+09
April 90353288.22 658260.83 89695027.39 38540358.95 0.117332E+09
May 0.131398E+09 7001709.07 0.124396E+09 0.113005E+09 51169204.41
June 0.141884E+09 15497143.17 0.126387E+09 0.149403E+09 27851206.25
July 0.140048E+09 11925910.96 0.128122E+09 0.159269E+09 23304515.31
August 0.106416E+09 1796240.19 0.104620E+09 0.114429E+09 29878180.93
September 80203422.45 8238.77 80195183.68 62985694.53 63022536.75
October 57597588.49 0.00 57597588.49 19035980.14 0.120476E+09
November 36906694.75 0.00 36906694.75 2146078.83 0.199836E+09
December 31969110.43 0.00 31969110.43 0.00 0.341202E+09
           
Annual Sum or Average 0.978166E+09 36887502.98 0.941278E+09 0.668521E+09 0.180336E+10
Minimum of Months 31969110.43 0.00 31969110.43 0.00 23304515.31
Maximum of Months 0.141884E+09 15497143.17 0.128122E+09 0.159269E+09 0.356522E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C0778D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37731459.39 0.00 37731459.39 66006.17 0.356522E+09
February 52349543.58 0.00 52349543.58 2012156.96 0.256698E+09
March 71307748.97 0.00 71307748.97 7628135.75 0.216074E+09
April 90281081.67 636503.73 89644577.94 38516896.23 0.117412E+09
May 0.131398E+09 7001709.07 0.124396E+09 0.113005E+09 51169204.41
June 0.141884E+09 15497143.17 0.126387E+09 0.149403E+09 27851206.25
July 0.140048E+09 11925909.72 0.128122E+09 0.159269E+09 23304515.31
August 0.106416E+09 1796189.74 0.104620E+09 0.114429E+09 29878181.20
September 80203422.45 8238.77 80195183.68 62985694.53 63022536.75
October 57597588.49 0.00 57597588.49 19035980.14 0.120476E+09
November 36906694.75 0.00 36906694.75 2146078.83 0.199836E+09
December 31969110.43 0.00 31969110.43 0.00 0.341202E+09
           
Annual Sum or Average 0.978093E+09 36865694.20 0.941227E+09 0.668497E+09 0.180345E+10
Minimum of Months 31969110.43 0.00 31969110.43 0.00 23304515.31
Maximum of Months 0.141884E+09 15497143.17 0.128122E+09 0.159269E+09 0.356522E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 7D2D69

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37731459.39 0.00 37731459.39 65945.57 0.354516E+09
February 52349543.58 0.00 52349543.58 1966226.28 0.255468E+09
March 71307748.97 0.00 71307748.97 7377387.15 0.215705E+09
April 90131516.76 582595.13 89548921.63 37413472.20 0.118558E+09
May 0.131388E+09 6996100.02 0.124392E+09 0.110177E+09 52909096.38
June 0.141884E+09 15497143.17 0.126387E+09 0.145702E+09 29509079.01
July 0.140038E+09 11923502.78 0.128115E+09 0.155447E+09 25095276.46
August 0.106144E+09 1686288.02 0.104458E+09 0.111116E+09 32099683.80
September 80203422.45 8238.77 80195183.68 61100664.63 65186178.87
October 57597588.49 0.00 57597588.49 18185738.47 0.122243E+09
November 36906694.75 0.00 36906694.75 2029837.43 0.200290E+09
December 31969110.43 0.00 31969110.43 0.00 0.339509E+09
           
Annual Sum or Average 0.977652E+09 36693867.88 0.940958E+09 0.650583E+09 0.181109E+10
Minimum of Months 31969110.43 0.00 31969110.43 0.00 25095276.46
Maximum of Months 0.141884E+09 15497143.17 0.128115E+09 0.155447E+09 0.354516E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 2EF63B

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37731459.39 0.00 37731459.39 65945.57 0.354516E+09
February 52349543.58 0.00 52349543.58 1966226.28 0.255468E+09
March 71307748.97 0.00 71307748.97 7377387.15 0.215705E+09
April 89973436.53 512786.13 89460650.40 37394695.51 0.118688E+09
May 0.131161E+09 6867145.75 0.124293E+09 0.109951E+09 52914661.54
June 0.141883E+09 15496699.56 0.126387E+09 0.145702E+09 29509079.01
July 0.140018E+09 11915815.91 0.128102E+09 0.155425E+09 25095276.46
August 0.105928E+09 1598705.63 0.104329E+09 0.110869E+09 32100549.90
September 80203422.45 8238.77 80195183.68 61100664.63 65186178.87
October 57597588.49 0.00 57597588.49 18185738.47 0.122243E+09
November 36906694.75 0.00 36906694.75 2029837.43 0.200290E+09
December 31969110.43 0.00 31969110.43 0.00 0.339509E+09
           
Annual Sum or Average 0.977029E+09 36399391.74 0.940629E+09 0.650068E+09 0.181122E+10
Minimum of Months 31969110.43 0.00 31969110.43 0.00 25095276.46
Maximum of Months 0.141883E+09 15496699.56 0.128102E+09 0.155425E+09 0.354516E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C417C0

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37275524.39 0.00 37275524.39 58203.80 0.357565E+09
February 51727473.56 0.00 51727473.56 1848554.52 0.258060E+09
March 70478984.28 0.00 70478984.28 7070974.32 0.217950E+09
April 88658776.45 349527.55 88309248.90 36794104.01 0.119801E+09
May 0.127762E+09 5618087.37 0.122144E+09 0.107999E+09 52884641.41
June 0.138584E+09 14481153.02 0.124103E+09 0.144032E+09 29116379.25
July 0.136459E+09 10725090.88 0.125734E+09 0.153512E+09 24644405.52
August 0.103931E+09 1177653.96 0.102753E+09 0.109897E+09 31745059.88
September 79266736.76 8238.77 79258497.99 60637381.73 65258666.36
October 56912200.71 0.00 56912200.71 17779560.88 0.123065E+09
November 36456822.10 0.00 36456822.10 1964022.09 0.202167E+09
December 31582148.99 0.00 31582148.99 0.00 0.342477E+09
           
Annual Sum or Average 0.959095E+09 32359751.54 0.926735E+09 0.641593E+09 0.182473E+10
Minimum of Months 31582148.99 0.00 31582148.99 0.00 24644405.52
Maximum of Months 0.138584E+09 14481153.02 0.125734E+09 0.153512E+09 0.357565E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: EB042B

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66154644.95 27601261.26 38553383.68 15940127.64 0.260234E+09
February 93910992.53 40047706.36 53863286.17 40639352.68 0.185315E+09
March 0.141729E+09 71108672.13 70619852.85 91636578.46 0.160934E+09
April 0.190160E+09 0.102597E+09 87562509.23 0.164300E+09 92527027.54
May 0.212627E+09 93488700.05 0.119138E+09 0.217553E+09 47182417.99
June 0.232952E+09 0.111454E+09 0.121498E+09 0.263900E+09 29343190.14
July 0.235812E+09 0.110742E+09 0.125070E+09 0.275099E+09 26390527.72
August 0.181819E+09 79488612.79 0.102331E+09 0.201999E+09 32450488.85
September 0.140920E+09 63096177.99 77823577.19 0.135276E+09 55722056.39
October 88152517.12 33429015.42 54723501.70 56993353.84 97169974.58
November 54292532.24 18141898.49 36150633.75 17779775.12 0.151769E+09
December 51187152.06 18907669.02 32279483.05 9614422.15 0.253597E+09
           
Annual Sum or Average 0.168972E+10 0.770104E+09 0.919612E+09 0.149073E+10 0.139264E+10
Minimum of Months 51187152.06 18141898.49 32279483.05 9614422.15 26390527.72
Maximum of Months 0.235812E+09 0.111454E+09 0.125070E+09 0.275099E+09 0.260234E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 4C1F71

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66154644.95 27601261.26 38553383.68 15941023.85 0.260221E+09
February 93910992.53 40047706.36 53863286.17 40641220.02 0.185307E+09
March 0.141729E+09 71108672.13 70619852.85 91639098.24 0.160927E+09
April 0.190160E+09 0.102597E+09 87562509.23 0.164303E+09 92523762.00
May 0.212627E+09 93488700.05 0.119138E+09 0.217555E+09 47181690.13
June 0.232952E+09 0.111454E+09 0.121498E+09 0.263901E+09 29343126.42
July 0.235812E+09 0.110742E+09 0.125070E+09 0.275100E+09 26390641.85
August 0.181819E+09 79488612.79 0.102331E+09 0.202000E+09 32450332.77
September 0.140920E+09 63096177.99 77823577.19 0.135277E+09 55720628.23
October 88152517.12 33429015.42 54723501.70 56994887.71 97166627.61
November 54292532.24 18141898.49 36150633.75 17780595.32 0.151763E+09
December 51187152.06 18907669.02 32279483.05 9615106.49 0.253585E+09
           
Annual Sum or Average 0.168972E+10 0.770104E+09 0.919612E+09 0.149075E+10 0.139258E+10
Minimum of Months 51187152.06 18141898.49 32279483.05 9615106.49 26390641.85
Maximum of Months 0.235812E+09 0.111454E+09 0.125070E+09 0.275100E+09 0.260221E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: D23C8B

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66154644.95 27601261.26 38553383.68 15940127.64 0.260234E+09
February 93910992.53 40047706.36 53863286.17 40639352.68 0.185315E+09
March 0.141729E+09 71108672.13 70619852.85 91636578.46 0.160934E+09
April 0.190160E+09 0.102597E+09 87562509.23 0.164300E+09 92527027.54
May 0.212627E+09 93488700.05 0.119138E+09 0.217553E+09 47182417.99
June 0.232952E+09 0.111454E+09 0.121498E+09 0.263900E+09 29343190.14
July 0.235812E+09 0.110742E+09 0.125070E+09 0.275099E+09 26390527.72
August 0.181819E+09 79488612.79 0.102331E+09 0.201999E+09 32450488.85
September 0.140920E+09 63096177.99 77823577.19 0.135276E+09 55722056.39
October 88152517.12 33429015.42 54723501.70 56993353.84 97169974.58
November 54292532.24 18141898.49 36150633.75 17779775.12 0.151769E+09
December 51187152.06 18907669.02 32279483.05 9614422.15 0.253597E+09
           
Annual Sum or Average 0.168972E+10 0.770104E+09 0.919612E+09 0.149073E+10 0.139264E+10
Minimum of Months 51187152.06 18141898.49 32279483.05 9614422.15 26390527.72
Maximum of Months 0.235812E+09 0.111454E+09 0.125070E+09 0.275099E+09 0.260234E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: B4E4BE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66154644.95 27601261.26 38553383.68 15940127.64 0.260234E+09
February 93910992.53 40047706.36 53863286.17 40639352.68 0.185315E+09
March 0.141729E+09 71108672.13 70619852.85 91636578.46 0.160934E+09
April 0.190160E+09 0.102597E+09 87562509.23 0.164300E+09 92527027.54
May 0.212627E+09 93488700.05 0.119138E+09 0.217553E+09 47182417.99
June 0.232952E+09 0.111454E+09 0.121498E+09 0.263900E+09 29343190.14
July 0.235812E+09 0.110742E+09 0.125070E+09 0.275099E+09 26390527.72
August 0.181819E+09 79488612.79 0.102331E+09 0.201999E+09 32450488.85
September 0.140920E+09 63096177.99 77823577.19 0.135276E+09 55722056.39
October 88152517.12 33429015.42 54723501.70 56993353.84 97169974.58
November 54292532.24 18141898.49 36150633.75 17779775.12 0.151769E+09
December 51187152.06 18907669.02 32279483.05 9614422.15 0.253597E+09
           
Annual Sum or Average 0.168972E+10 0.770104E+09 0.919612E+09 0.149073E+10 0.139264E+10
Minimum of Months 51187152.06 18141898.49 32279483.05 9614422.15 26390527.72
Maximum of Months 0.235812E+09 0.111454E+09 0.125070E+09 0.275099E+09 0.260234E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: EEF55D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.592385E+09 0.414023E+09 0.178362E+09 0.489541E+09 0.694539E+09
February 0.657701E+09 0.445195E+09 0.212506E+09 0.599462E+09 0.543822E+09
March 0.653582E+09 0.414152E+09 0.239430E+09 0.566071E+09 0.497034E+09
April 0.592645E+09 0.326528E+09 0.266117E+09 0.500757E+09 0.302214E+09
May 0.514067E+09 0.180257E+09 0.333810E+09 0.448732E+09 0.155724E+09
June 0.444394E+09 0.121855E+09 0.322539E+09 0.420144E+09 92695554.74
July 0.503375E+09 0.163693E+09 0.339682E+09 0.500723E+09 82141267.88
August 0.539379E+09 0.230558E+09 0.308820E+09 0.551069E+09 0.100615E+09
September 0.551786E+09 0.296809E+09 0.254976E+09 0.560140E+09 0.177765E+09
October 0.470146E+09 0.275394E+09 0.194752E+09 0.444065E+09 0.302738E+09
November 0.412295E+09 0.259997E+09 0.152298E+09 0.359140E+09 0.433843E+09
December 0.462279E+09 0.303860E+09 0.158419E+09 0.348545E+09 0.670465E+09
           
Annual Sum or Average 0.639403E+10 0.343232E+10 0.296171E+10 0.578839E+10 0.405360E+10
Minimum of Months 0.412295E+09 0.121855E+09 0.152298E+09 0.348545E+09 82141267.88
Maximum of Months 0.657701E+09 0.445195E+09 0.339682E+09 0.599462E+09 0.694539E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: E55A57

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.241736E+09 0.165627E+09 76109122.08 0.195235E+09 0.367964E+09
February 0.278358E+09 0.185774E+09 92583690.77 0.247097E+09 0.282914E+09
March 0.285515E+09 0.178417E+09 0.107098E+09 0.242268E+09 0.256345E+09
April 0.266158E+09 0.145670E+09 0.120488E+09 0.226930E+09 0.154055E+09
May 0.237365E+09 85624167.89 0.151741E+09 0.206657E+09 77609153.52
June 0.206383E+09 58941852.43 0.147441E+09 0.194744E+09 45875327.10
July 0.233947E+09 78612671.35 0.155334E+09 0.233667E+09 40013193.20
August 0.246758E+09 0.106775E+09 0.139982E+09 0.254869E+09 49534516.54
September 0.242723E+09 0.128356E+09 0.114368E+09 0.245877E+09 88848563.33
October 0.203599E+09 0.117293E+09 86306122.55 0.186983E+09 0.153892E+09
November 0.170947E+09 0.105424E+09 65522696.10 0.144833E+09 0.226001E+09
December 0.188529E+09 0.121485E+09 67043569.92 0.139652E+09 0.355469E+09
           
Annual Sum or Average 0.280202E+10 0.147800E+10 0.132402E+10 0.251881E+10 0.209852E+10
Minimum of Months 0.170947E+09 58941852.43 65522696.10 0.139652E+09 40013193.20
Maximum of Months 0.285515E+09 0.185774E+09 0.155334E+09 0.254869E+09 0.367964E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 93D018

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.197521E+09 83979378.02 0.113542E+09 58578255.12 0.796940E+09
February 0.291154E+09 0.134856E+09 0.156298E+09 0.150313E+09 0.582020E+09
March 0.424910E+09 0.220246E+09 0.204664E+09 0.291904E+09 0.505077E+09
April 0.525591E+09 0.269542E+09 0.256049E+09 0.453271E+09 0.293496E+09
May 0.666349E+09 0.322223E+09 0.344125E+09 0.706765E+09 0.150222E+09
June 0.621933E+09 0.272783E+09 0.349149E+09 0.706660E+09 90049924.08
July 0.686865E+09 0.323503E+09 0.363363E+09 0.805181E+09 80928241.19
August 0.564792E+09 0.260221E+09 0.304571E+09 0.635254E+09 99624123.87
September 0.426881E+09 0.194659E+09 0.232222E+09 0.418696E+09 0.175021E+09
October 0.277907E+09 0.113471E+09 0.164437E+09 0.193968E+09 0.303639E+09
November 0.162979E+09 55970429.53 0.107009E+09 58524107.30 0.466950E+09
December 0.150283E+09 53503139.97 96780295.38 29001250.63 0.770514E+09
           
Annual Sum or Average 0.499716E+10 0.230496E+10 0.269221E+10 0.450812E+10 0.431448E+10
Minimum of Months 0.150283E+09 53503139.97 96780295.38 29001250.63 80928241.19
Maximum of Months 0.686865E+09 0.323503E+09 0.363363E+09 0.805181E+09 0.796940E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: DD9F5D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66154644.95 27601261.26 38553383.68 15695623.26 0.261847E+09
February 93910992.53 40047706.36 53863286.17 40319702.12 0.185554E+09
March 0.141729E+09 71108672.13 70619852.85 91512424.13 0.160276E+09
April 0.190160E+09 0.102597E+09 87562509.23 0.164282E+09 91229133.92
May 0.212627E+09 93488700.05 0.119138E+09 0.217921E+09 45675546.77
June 0.232952E+09 0.111454E+09 0.121498E+09 0.264372E+09 27900254.05
July 0.235812E+09 0.110742E+09 0.125070E+09 0.275764E+09 24827409.03
August 0.181819E+09 79488612.79 0.102331E+09 0.202475E+09 30585642.87
September 0.140920E+09 63096177.99 77823577.19 0.135861E+09 53695151.39
October 88152517.12 33429015.42 54723501.70 57253308.18 95360256.95
November 54292532.24 18141898.49 36150633.75 17740230.80 0.151142E+09
December 51187152.06 18907669.02 32279483.05 9484228.50 0.255056E+09
           
Annual Sum or Average 0.168972E+10 0.770104E+09 0.919612E+09 0.149268E+10 0.138315E+10
Minimum of Months 51187152.06 18141898.49 32279483.05 9484228.50 24827409.03
Maximum of Months 0.235812E+09 0.111454E+09 0.125070E+09 0.275764E+09 0.261847E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 15B02B

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 36939962.27 0.00 36939962.27 24324.20 0.369682E+09
February 51287910.55 0.00 51287910.55 1401097.61 0.270538E+09
March 69909285.73 0.00 69909285.73 5644966.56 0.231911E+09
April 87989632.46 349527.55 87640104.91 32408884.31 0.131813E+09
May 0.123347E+09 3349252.32 0.119998E+09 97165002.45 63888837.99
June 0.133053E+09 11468901.80 0.121584E+09 0.128706E+09 37450130.32
July 0.131444E+09 7973477.22 0.123471E+09 0.137582E+09 33999615.06
August 0.102446E+09 797154.99 0.101649E+09 99988981.21 43404998.69
September 78602082.14 8238.77 78593843.37 54225440.65 77489109.58
October 56391049.64 0.00 56391049.64 14482225.15 0.137190E+09
November 36115920.13 0.00 36115920.13 1553903.29 0.216985E+09
December 31285938.87 0.00 31285938.87 0.00 0.355938E+09
           
Annual Sum or Average 0.938812E+09 23946552.64 0.914865E+09 0.573183E+09 0.197029E+10
Minimum of Months 31285938.87 0.00 31285938.87 0.00 33999615.06
Maximum of Months 0.133053E+09 11468901.80 0.123471E+09 0.137582E+09 0.369682E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 820282

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 32898126.95 0.00 32898126.95 768.79 0.371597E+09
February 45942280.76 0.00 45942280.76 757552.93 0.273550E+09
March 62934674.74 0.00 62934674.74 3847746.32 0.235530E+09
April 79752433.34 349527.55 79402905.79 26868342.96 0.133155E+09
May 0.111161E+09 3028172.52 0.108132E+09 85380521.58 63478189.83
June 0.117296E+09 8390341.06 0.108905E+09 0.113265E+09 37632997.51
July 0.117536E+09 6163295.24 0.111373E+09 0.123761E+09 33332467.94
August 92464386.48 797154.99 91667231.50 89717348.59 42505046.47
September 70527158.64 8238.77 70518919.88 46475009.65 77029877.33
October 50160551.95 0.00 50160551.95 10632935.57 0.138176E+09
November 32037181.48 0.00 32037181.48 1121416.19 0.218894E+09
December 27750015.20 0.00 27750015.20 0.00 0.357495E+09
           
Annual Sum or Average 0.840459E+09 18736730.13 0.821723E+09 0.501828E+09 0.198237E+10
Minimum of Months 27750015.20 0.00 27750015.20 0.00 33332467.94
Maximum of Months 0.117536E+09 8390341.06 0.111373E+09 0.123761E+09 0.371597E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 9BA05A

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37731459.39 0.00 37731459.39 41901.76 0.361032E+09
February 52349543.58 0.00 52349543.58 1645590.81 0.262628E+09
March 71307748.97 0.00 71307748.97 6364023.21 0.225018E+09
April 90445924.50 687456.19 89758468.32 34299847.73 0.127244E+09
May 0.131398E+09 7001709.07 0.124396E+09 0.103776E+09 60434200.10
June 0.141884E+09 15497143.17 0.126387E+09 0.137881E+09 35680488.93
July 0.140048E+09 11925910.96 0.128122E+09 0.146901E+09 31791924.10
August 0.106416E+09 1796240.19 0.104620E+09 0.105343E+09 40301240.69
September 80267299.97 17598.03 80249701.94 57213777.55 73834879.48
October 57597588.49 0.00 57597588.49 16173419.02 0.131694E+09
November 36906694.75 0.00 36906694.75 1791089.51 0.209344E+09
December 31969110.43 0.00 31969110.43 0.00 0.346431E+09
           
Annual Sum or Average 0.978322E+09 36926057.60 0.941396E+09 0.611430E+09 0.190543E+10
Minimum of Months 31969110.43 0.00 31969110.43 0.00 31791924.10
Maximum of Months 0.141884E+09 15497143.17 0.128122E+09 0.146901E+09 0.361032E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C639E8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37731459.39 0.00 37731459.39 41901.76 0.361032E+09
February 52349543.58 0.00 52349543.58 1645590.81 0.262628E+09
March 71307748.97 0.00 71307748.97 6364023.21 0.225018E+09
April 90445924.50 687456.19 89758468.32 34299847.73 0.127244E+09
May 0.131398E+09 7001709.07 0.124396E+09 0.103776E+09 60434200.10
June 0.141884E+09 15497143.17 0.126387E+09 0.137881E+09 35680488.93
July 0.140048E+09 11925910.96 0.128122E+09 0.146901E+09 31791924.10
August 0.106416E+09 1796240.19 0.104620E+09 0.105343E+09 40301240.69
September 80235675.05 11273.86 80224401.18 57202970.85 73868020.50
October 57597588.49 0.00 57597588.49 16173419.02 0.131694E+09
November 36906694.75 0.00 36906694.75 1791089.51 0.209344E+09
December 31969110.43 0.00 31969110.43 0.00 0.346431E+09
           
Annual Sum or Average 0.978290E+09 36919733.44 0.941371E+09 0.611419E+09 0.190547E+10
Minimum of Months 31969110.43 0.00 31969110.43 0.00 31791924.10
Maximum of Months 0.141884E+09 15497143.17 0.128122E+09 0.146901E+09 0.361032E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: A2790A

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 56597189.09 0.00 56597189.09 102219.92 0.532794E+09
February 78524315.38 0.00 78524315.38 2619324.40 0.383290E+09
March 0.106962E+09 0.00 0.106962E+09 9817899.07 0.323642E+09
April 0.135669E+09 1031184.28 0.134638E+09 52795929.94 0.176204E+09
May 0.197097E+09 10502563.60 0.186594E+09 0.158885E+09 78528497.79
June 0.212826E+09 23245714.75 0.189581E+09 0.211659E+09 43689020.81
July 0.210072E+09 17888866.44 0.192183E+09 0.226088E+09 37169792.33
August 0.159624E+09 2694360.29 0.156930E+09 0.161029E+09 47518772.28
September 0.120343E+09 15517.43 0.120328E+09 87709399.16 96506837.27
October 86396382.73 0.00 86396382.73 25150004.01 0.182079E+09
November 55360042.13 0.00 55360042.13 2625930.73 0.299717E+09
December 47953665.65 0.00 47953665.65 0.00 0.509189E+09
           
Annual Sum or Average 0.146743E+10 55378206.79 0.141205E+10 0.938482E+09 0.271033E+10
Minimum of Months 47953665.65 0.00 47953665.65 0.00 37169792.33
Maximum of Months 0.212826E+09 23245714.75 0.192183E+09 0.226088E+09 0.532794E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 79FCEE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 88165979.27 36801681.69 51364297.58 20347025.12 0.382682E+09
February 0.125157E+09 53396941.81 71759561.05 51518193.43 0.276055E+09
March 0.188891E+09 94811562.85 94079464.18 0.119190E+09 0.241106E+09
April 0.253447E+09 0.136797E+09 0.116651E+09 0.213961E+09 0.145659E+09
May 0.283373E+09 0.124652E+09 0.158721E+09 0.283227E+09 78411518.84
June 0.310466E+09 0.148606E+09 0.161860E+09 0.345683E+09 50983751.43
July 0.314273E+09 0.147657E+09 0.166616E+09 0.360160E+09 47173678.56
August 0.242307E+09 0.105985E+09 0.136322E+09 0.265883E+09 56804024.02
September 0.187806E+09 84128237.32 0.103678E+09 0.175831E+09 92789074.06
October 0.117479E+09 44572020.56 72907223.35 72667580.35 0.155901E+09
November 72352126.69 24189197.99 48162928.70 22682445.11 0.234479E+09
December 68217458.19 25210225.35 43007232.84 12032697.44 0.374746E+09
           
Annual Sum or Average 0.225193E+10 0.102681E+10 0.122513E+10 0.194318E+10 0.213679E+10
Minimum of Months 68217458.19 24189197.99 43007232.84 12032697.44 47173678.56
Maximum of Months 0.314273E+09 0.148606E+09 0.166616E+09 0.360160E+09 0.382682E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: EDE617

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 86742688.97 36801681.69 49941007.28 20195579.60 0.383265E+09
February 0.123228E+09 53396941.81 69830708.61 50811847.77 0.276741E+09
March 0.186333E+09 94811562.85 91521091.43 0.117825E+09 0.241833E+09
April 0.250386E+09 0.136797E+09 0.113589E+09 0.211424E+09 0.145800E+09
May 0.279134E+09 0.124652E+09 0.154482E+09 0.278838E+09 78086322.18
June 0.306276E+09 0.148606E+09 0.157670E+09 0.341309E+09 50726401.88
July 0.309997E+09 0.147657E+09 0.162340E+09 0.355695E+09 46785275.23
August 0.238609E+09 0.105985E+09 0.132624E+09 0.261978E+09 56479460.12
September 0.184900E+09 84128237.32 0.100771E+09 0.172870E+09 92523238.08
October 0.115328E+09 44572020.56 70755703.76 70990650.22 0.155930E+09
November 70940755.07 24189197.99 46751557.08 22290579.76 0.234933E+09
December 67001325.41 25210225.35 41791100.06 11966998.23 0.375242E+09
           
Annual Sum or Average 0.221887E+10 0.102681E+10 0.119207E+10 0.191619E+10 0.213835E+10
Minimum of Months 67001325.41 24189197.99 41791100.06 11966998.23 46785275.23
Maximum of Months 0.309997E+09 0.148606E+09 0.162340E+09 0.355695E+09 0.383265E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C61F0D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37731459.39 0.00 37731459.39 60270.30 0.356878E+09
February 52349543.58 0.00 52349543.58 1749767.46 0.259195E+09
March 71307748.97 0.00 71307748.97 6207802.52 0.222280E+09
April 90424020.07 678677.22 89745342.85 33664863.52 0.125542E+09
May 0.131398E+09 7001709.07 0.124396E+09 0.102227E+09 59705414.41
June 0.141884E+09 15497143.17 0.126387E+09 0.136036E+09 35383365.95
July 0.140048E+09 11925910.96 0.128122E+09 0.144924E+09 31734247.51
August 0.106416E+09 1796240.19 0.104620E+09 0.103357E+09 40168830.12
September 80216319.31 9205.43 80207113.88 55929304.12 73309274.97
October 57597588.49 0.00 57597588.49 15594099.05 0.130388E+09
November 36906694.75 0.00 36906694.75 1671885.96 0.206928E+09
December 31969110.43 0.00 31969110.43 0.00 0.342818E+09
           
Annual Sum or Average 0.978249E+09 36908886.03 0.941340E+09 0.601421E+09 0.188433E+10
Minimum of Months 31969110.43 0.00 31969110.43 0.00 31734247.51
Maximum of Months 0.141884E+09 15497143.17 0.128122E+09 0.144924E+09 0.356878E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 7248C5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 34581597.23 0.00 34581597.23 21084.23 0.358482E+09
February 48051105.42 0.00 48051105.42 1128949.79 0.261716E+09
March 65580358.78 0.00 65580358.78 4417071.66 0.225196E+09
April 82774861.43 349527.55 82425333.88 28485096.70 0.127220E+09
May 0.115772E+09 3062289.01 0.112710E+09 89164924.15 60758146.19
June 0.121706E+09 8537067.62 0.113169E+09 0.117042E+09 35858563.66
July 0.121744E+09 6265169.06 0.115478E+09 0.127558E+09 31406695.79
August 96165420.87 798758.82 95366662.05 93163759.74 39745120.03
September 73731147.94 8238.77 73722909.17 49561873.02 72970214.56
October 52863283.49 0.00 52863283.49 12415129.30 0.130950E+09
November 33799154.31 0.00 33799154.31 1302905.46 0.208431E+09
December 29296269.07 0.00 29296269.07 0.00 0.344063E+09
           
Annual Sum or Average 0.876065E+09 19021050.84 0.857044E+09 0.524261E+09 0.189680E+10
Minimum of Months 29296269.07 0.00 29296269.07 0.00 31406695.79
Maximum of Months 0.121744E+09 8537067.62 0.115478E+09 0.127558E+09 0.358482E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 29FA28

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37731459.39 0.00 37731459.39 60270.30 0.356878E+09
February 52349543.58 0.00 52349543.58 1749767.46 0.259195E+09
March 71307748.97 0.00 71307748.97 6207802.52 0.222280E+09
April 90294964.82 623684.57 89671280.25 33649461.57 0.125658E+09
May 0.131398E+09 7001709.07 0.124396E+09 0.102227E+09 59705414.41
June 0.141884E+09 15497143.17 0.126387E+09 0.136036E+09 35383365.95
July 0.140048E+09 11925910.96 0.128122E+09 0.144924E+09 31734247.51
August 0.106416E+09 1796240.19 0.104620E+09 0.103357E+09 40168830.12
September 80211227.32 8776.60 80202450.73 55927131.55 73314323.39
October 57597588.49 0.00 57597588.49 15594099.05 0.130388E+09
November 36906694.75 0.00 36906694.75 1671885.96 0.206928E+09
December 31969110.43 0.00 31969110.43 0.00 0.342818E+09
           
Annual Sum or Average 0.978115E+09 36853464.55 0.941262E+09 0.601403E+09 0.188445E+10
Minimum of Months 31969110.43 0.00 31969110.43 0.00 31734247.51
Maximum of Months 0.141884E+09 15497143.17 0.128122E+09 0.144924E+09 0.356878E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: F0B23F

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37731459.39 0.00 37731459.39 60270.30 0.356878E+09
February 52349543.58 0.00 52349543.58 1749767.46 0.259195E+09
March 71307748.97 0.00 71307748.97 6207802.52 0.222280E+09
April 89995991.23 487100.26 89508890.97 33619103.86 0.125905E+09
May 0.131398E+09 7001709.07 0.124396E+09 0.102227E+09 59705414.41
June 0.141884E+09 15497143.17 0.126387E+09 0.136036E+09 35383365.95
July 0.140048E+09 11925871.97 0.128122E+09 0.144923E+09 31734247.51
August 0.106369E+09 1770780.78 0.104598E+09 0.103321E+09 40169241.72
September 80206332.71 8370.66 80197962.05 55925029.89 73319073.80
October 57597588.49 0.00 57597588.49 15594099.05 0.130388E+09
November 36906694.75 0.00 36906694.75 1671885.96 0.206928E+09
December 31969110.43 0.00 31969110.43 0.00 0.342818E+09
           
Annual Sum or Average 0.977764E+09 36690975.90 0.941073E+09 0.601335E+09 0.188470E+10
Minimum of Months 31969110.43 0.00 31969110.43 0.00 31734247.51
Maximum of Months 0.141884E+09 15497143.17 0.128122E+09 0.144923E+09 0.356878E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: EEC10E

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37511014.77 0.00 37511014.77 56716.97 0.356999E+09
February 52030756.44 0.00 52030756.44 1700347.47 0.259396E+09
March 70867344.12 0.00 70867344.12 6042345.86 0.222501E+09
April 89220915.47 381946.39 88838969.08 33152825.01 0.126173E+09
May 0.130278E+09 6725919.94 0.123552E+09 0.101260E+09 59704598.82
June 0.141127E+09 15491812.18 0.125636E+09 0.135221E+09 35338674.07
July 0.139209E+09 11891274.35 0.127318E+09 0.144039E+09 31675311.20
August 0.105058E+09 1413152.76 0.103645E+09 0.102128E+09 40142617.17
September 79726713.64 8260.57 79718453.07 55443698.11 73297535.23
October 57282683.89 0.00 57282683.89 15364320.73 0.130408E+09
November 36698845.56 0.00 36698845.56 1647080.88 0.207031E+09
December 31793266.21 0.00 31793266.21 0.00 0.342900E+09
           
Annual Sum or Average 0.970804E+09 35912366.19 0.934891E+09 0.596056E+09 0.188557E+10
Minimum of Months 31793266.21 0.00 31793266.21 0.00 31675311.20
Maximum of Months 0.141127E+09 15491812.18 0.127318E+09 0.144039E+09 0.356999E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 944FCE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37370041.36 0.00 37370041.36 54580.39 0.357074E+09
February 51830099.78 0.00 51830099.78 1669404.76 0.259519E+09
March 70592772.03 0.00 70592772.03 5942199.95 0.222637E+09
April 88798063.43 354962.94 88443100.48 32868190.33 0.126315E+09
May 0.125879E+09 4154517.15 0.121724E+09 98606808.99 60649527.34
June 0.137227E+09 13218009.49 0.124009E+09 0.131888E+09 35384549.18
July 0.134995E+09 9406288.75 0.125589E+09 0.140484E+09 31672995.47
August 0.103677E+09 904689.68 0.102773E+09 0.101082E+09 40364532.40
September 79425272.88 8238.77 79417034.11 55142320.91 73282476.20
October 57078370.65 0.00 57078370.65 15217779.08 0.130423E+09
November 36564206.91 0.00 36564206.91 1630655.40 0.207096E+09
December 31678812.08 0.00 31678812.08 0.00 0.342953E+09
           
Annual Sum or Average 0.955115E+09 28046706.78 0.927069E+09 0.584586E+09 0.188737E+10
Minimum of Months 31678812.08 0.00 31678812.08 0.00 31672995.47
Maximum of Months 0.137227E+09 13218009.49 0.125589E+09 0.140484E+09 0.357074E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C41399

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 37731459.39 0.00 37731459.39 60270.30 0.356878E+09
February 52349543.58 0.00 52349543.58 1749767.46 0.259195E+09
March 71307748.97 0.00 71307748.97 6207802.52 0.222280E+09
April 90445924.50 687456.19 89758468.32 33668202.88 0.125521E+09
May 0.131398E+09 7001709.07 0.124396E+09 0.102227E+09 59705414.41
June 0.141884E+09 15497143.17 0.126387E+09 0.136036E+09 35383365.95
July 0.140048E+09 11925910.96 0.128122E+09 0.144924E+09 31734247.51
August 0.106416E+09 1796240.19 0.104620E+09 0.103357E+09 40168830.12
September 80221411.21 9634.26 80211776.96 55931476.38 73304263.11
October 57597588.49 0.00 57597588.49 15594099.05 0.130388E+09
November 36906694.75 0.00 36906694.75 1671885.96 0.206928E+09
December 31969110.43 0.00 31969110.43 0.00 0.342818E+09
           
Annual Sum or Average 0.978276E+09 36918093.83 0.941358E+09 0.601427E+09 0.188431E+10
Minimum of Months 31969110.43 0.00 31969110.43 0.00 31734247.51
Maximum of Months 0.141884E+09 15497143.17 0.128122E+09 0.144924E+09 0.356878E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 95BA33

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 99231967.42 41401891.90 57830075.52 24220061.46 0.382115E+09
February 0.140866E+09 60071559.53 80794929.26 60883356.48 0.270120E+09
March 0.212593E+09 0.106663E+09 0.105930E+09 0.138184E+09 0.229703E+09
April 0.285240E+09 0.153896E+09 0.131344E+09 0.249347E+09 0.126083E+09
May 0.318940E+09 0.140233E+09 0.178707E+09 0.334346E+09 57798813.11
June 0.349428E+09 0.167182E+09 0.182247E+09 0.406940E+09 31844846.64
July 0.353718E+09 0.166114E+09 0.187605E+09 0.424525E+09 26261748.10
August 0.272729E+09 0.119233E+09 0.153496E+09 0.311082E+09 33218956.07
September 0.211380E+09 94644266.99 0.116735E+09 0.206959E+09 69342819.87
October 0.132229E+09 50143523.13 82085252.56 87140727.98 0.131059E+09
November 81438798.37 27212847.74 54225950.63 27317264.00 0.215650E+09
December 76780728.09 28361503.52 48419224.57 14645594.63 0.370129E+09
           
Annual Sum or Average 0.253457E+10 0.115516E+10 0.137942E+10 0.228559E+10 0.194333E+10
Minimum of Months 76780728.09 27212847.74 48419224.57 14645594.63 26261748.10
Maximum of Months 0.353718E+09 0.167182E+09 0.187605E+09 0.424525E+09 0.382115E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: F27282

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 99231967.42 41401891.90 57830075.52 24220061.46 0.382409E+09
February 0.140866E+09 60071559.53 80794929.26 60874978.04 0.271319E+09
March 0.212593E+09 0.106663E+09 0.105930E+09 0.138045E+09 0.230731E+09
April 0.285240E+09 0.153896E+09 0.131344E+09 0.249247E+09 0.126102E+09
May 0.318940E+09 0.140233E+09 0.178707E+09 0.334343E+09 57798813.11
June 0.349428E+09 0.167182E+09 0.182247E+09 0.406940E+09 31844846.64
July 0.353718E+09 0.166114E+09 0.187605E+09 0.424524E+09 26261748.10
August 0.272729E+09 0.119233E+09 0.153496E+09 0.311036E+09 33218956.07
September 0.211380E+09 94644266.99 0.116735E+09 0.206565E+09 69351351.87
October 0.132229E+09 50143523.13 82085252.56 86674261.91 0.131591E+09
November 81438798.37 27212847.74 54225950.63 27315936.85 0.215916E+09
December 76780728.09 28361503.52 48419224.57 14645594.63 0.370192E+09
           
Annual Sum or Average 0.253457E+10 0.115516E+10 0.137942E+10 0.228443E+10 0.194674E+10
Minimum of Months 76780728.09 27212847.74 48419224.57 14645594.63 26261748.10
Maximum of Months 0.353718E+09 0.167182E+09 0.187605E+09 0.424524E+09 0.382409E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 3DB407

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.520047E+09 0.361909E+09 0.158139E+09 0.422030E+09 0.545673E+09
February 0.594845E+09 0.401951E+09 0.192894E+09 0.528275E+09 0.412236E+09
March 0.580144E+09 0.367288E+09 0.212856E+09 0.489543E+09 0.377805E+09
April 0.507969E+09 0.275555E+09 0.232413E+09 0.427495E+09 0.224127E+09
May 0.440915E+09 0.150288E+09 0.290627E+09 0.393935E+09 0.105647E+09
June 0.382796E+09 0.101547E+09 0.281249E+09 0.374022E+09 56708587.82
July 0.432454E+09 0.136477E+09 0.295976E+09 0.444582E+09 46034763.10
August 0.462149E+09 0.193021E+09 0.269128E+09 0.482016E+09 57551762.95
September 0.479640E+09 0.255471E+09 0.224169E+09 0.487229E+09 0.119862E+09
October 0.423541E+09 0.249254E+09 0.174287E+09 0.398330E+09 0.217825E+09
November 0.365062E+09 0.229211E+09 0.135851E+09 0.314912E+09 0.328404E+09
December 0.401515E+09 0.263378E+09 0.138137E+09 0.299946E+09 0.529284E+09
           
Annual Sum or Average 0.559108E+10 0.298535E+10 0.260573E+10 0.506231E+10 0.302116E+10
Minimum of Months 0.365062E+09 0.101547E+09 0.135851E+09 0.299946E+09 46034763.10
Maximum of Months 0.594845E+09 0.401951E+09 0.295976E+09 0.528275E+09 0.545673E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 3DADE2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.520047E+09 0.361909E+09 0.158139E+09 0.422030E+09 0.545673E+09
February 0.594845E+09 0.401951E+09 0.192894E+09 0.528275E+09 0.412236E+09
March 0.580144E+09 0.367288E+09 0.212856E+09 0.489543E+09 0.377805E+09
April 0.507969E+09 0.275555E+09 0.232413E+09 0.427495E+09 0.224112E+09
May 0.440915E+09 0.150288E+09 0.290627E+09 0.393935E+09 0.105700E+09
June 0.382796E+09 0.101547E+09 0.281249E+09 0.374022E+09 56708888.89
July 0.432454E+09 0.136477E+09 0.295976E+09 0.444580E+09 46047465.74
August 0.462149E+09 0.193021E+09 0.269128E+09 0.482016E+09 57567472.56
September 0.479640E+09 0.255471E+09 0.224169E+09 0.487229E+09 0.119863E+09
October 0.423541E+09 0.249254E+09 0.174287E+09 0.398330E+09 0.217825E+09
November 0.365062E+09 0.229211E+09 0.135851E+09 0.314912E+09 0.328404E+09
December 0.401515E+09 0.263378E+09 0.138137E+09 0.299946E+09 0.529284E+09
           
Annual Sum or Average 0.559108E+10 0.298535E+10 0.260573E+10 0.506231E+10 0.302123E+10
Minimum of Months 0.365062E+09 0.101547E+09 0.135851E+09 0.299946E+09 46047465.74
Maximum of Months 0.594845E+09 0.401951E+09 0.295976E+09 0.528275E+09 0.545673E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: DF3E2C

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.520047E+09 0.361909E+09 0.158139E+09 0.422030E+09 0.545673E+09
February 0.594845E+09 0.401951E+09 0.192894E+09 0.528275E+09 0.412236E+09
March 0.580144E+09 0.367288E+09 0.212856E+09 0.489543E+09 0.377805E+09
April 0.507969E+09 0.275555E+09 0.232413E+09 0.427495E+09 0.224161E+09
May 0.440915E+09 0.150288E+09 0.290627E+09 0.393927E+09 0.105729E+09
June 0.382796E+09 0.101547E+09 0.281249E+09 0.374013E+09 56674650.11
July 0.432454E+09 0.136477E+09 0.295976E+09 0.444547E+09 46025394.82
August 0.462149E+09 0.193021E+09 0.269128E+09 0.482005E+09 57618467.60
September 0.479640E+09 0.255471E+09 0.224169E+09 0.487229E+09 0.119865E+09
October 0.423541E+09 0.249254E+09 0.174287E+09 0.398330E+09 0.217825E+09
November 0.365062E+09 0.229211E+09 0.135851E+09 0.314912E+09 0.328404E+09
December 0.401515E+09 0.263378E+09 0.138137E+09 0.299946E+09 0.529284E+09
           
Annual Sum or Average 0.559108E+10 0.298535E+10 0.260573E+10 0.506225E+10 0.302130E+10
Minimum of Months 0.365062E+09 0.101547E+09 0.135851E+09 0.299946E+09 46025394.82
Maximum of Months 0.594845E+09 0.401951E+09 0.295976E+09 0.528275E+09 0.545673E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 5031C8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.520047E+09 0.361909E+09 0.158139E+09 0.422030E+09 0.545673E+09
February 0.594845E+09 0.401951E+09 0.192894E+09 0.528275E+09 0.412236E+09
March 0.580144E+09 0.367288E+09 0.212856E+09 0.489543E+09 0.377805E+09
April 0.507969E+09 0.275555E+09 0.232413E+09 0.427495E+09 0.224138E+09
May 0.440915E+09 0.150288E+09 0.290627E+09 0.393902E+09 0.106061E+09
June 0.382796E+09 0.101547E+09 0.281249E+09 0.373562E+09 56880552.63
July 0.432454E+09 0.136477E+09 0.295976E+09 0.444164E+09 46183189.78
August 0.462149E+09 0.193021E+09 0.269128E+09 0.482004E+09 57654751.60
September 0.479640E+09 0.255471E+09 0.224169E+09 0.487229E+09 0.119867E+09
October 0.423541E+09 0.249254E+09 0.174287E+09 0.398330E+09 0.217825E+09
November 0.365062E+09 0.229211E+09 0.135851E+09 0.314912E+09 0.328404E+09
December 0.401515E+09 0.263378E+09 0.138137E+09 0.299946E+09 0.529284E+09
           
Annual Sum or Average 0.559108E+10 0.298535E+10 0.260573E+10 0.506139E+10 0.302201E+10
Minimum of Months 0.365062E+09 0.101547E+09 0.135851E+09 0.299946E+09 46183189.78
Maximum of Months 0.594845E+09 0.401951E+09 0.295976E+09 0.528275E+09 0.545673E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C087D0

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.520047E+09 0.361909E+09 0.158139E+09 0.422539E+09 0.556105E+09
February 0.594845E+09 0.401951E+09 0.192894E+09 0.528953E+09 0.423977E+09
March 0.580144E+09 0.367288E+09 0.212856E+09 0.489516E+09 0.395562E+09
April 0.507969E+09 0.275555E+09 0.232413E+09 0.424575E+09 0.244091E+09
May 0.440915E+09 0.150288E+09 0.290627E+09 0.383576E+09 0.126440E+09
June 0.382796E+09 0.101547E+09 0.281249E+09 0.360363E+09 74348676.61
July 0.432454E+09 0.136477E+09 0.295976E+09 0.429049E+09 65048967.55
August 0.462149E+09 0.193021E+09 0.269128E+09 0.470460E+09 79446413.76
September 0.479640E+09 0.255471E+09 0.224169E+09 0.480588E+09 0.141299E+09
October 0.423541E+09 0.249254E+09 0.174287E+09 0.394533E+09 0.238186E+09
November 0.365062E+09 0.229211E+09 0.135851E+09 0.313474E+09 0.344630E+09
December 0.401515E+09 0.263378E+09 0.138137E+09 0.299957E+09 0.541606E+09
           
Annual Sum or Average 0.559108E+10 0.298535E+10 0.260573E+10 0.499758E+10 0.323074E+10
Minimum of Months 0.365062E+09 0.101547E+09 0.135851E+09 0.299957E+09 65048967.55
Maximum of Months 0.594845E+09 0.401951E+09 0.295976E+09 0.528953E+09 0.556105E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: D2CA75

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.520047E+09 0.361909E+09 0.158139E+09 0.422539E+09 0.556105E+09
February 0.594845E+09 0.401951E+09 0.192894E+09 0.528953E+09 0.423977E+09
March 0.580144E+09 0.367288E+09 0.212856E+09 0.489516E+09 0.395562E+09
April 0.507969E+09 0.275555E+09 0.232413E+09 0.424569E+09 0.244143E+09
May 0.440915E+09 0.150288E+09 0.290627E+09 0.383637E+09 0.126331E+09
June 0.382796E+09 0.101547E+09 0.281249E+09 0.360547E+09 74336060.30
July 0.432454E+09 0.136477E+09 0.295976E+09 0.429215E+09 65025016.07
August 0.462149E+09 0.193021E+09 0.269128E+09 0.470452E+09 79415808.06
September 0.479640E+09 0.255471E+09 0.224169E+09 0.480589E+09 0.141298E+09
October 0.423541E+09 0.249254E+09 0.174287E+09 0.394533E+09 0.238186E+09
November 0.365062E+09 0.229211E+09 0.135851E+09 0.313474E+09 0.344630E+09
December 0.401515E+09 0.263378E+09 0.138137E+09 0.299957E+09 0.541606E+09
           
Annual Sum or Average 0.559108E+10 0.298535E+10 0.260573E+10 0.499798E+10 0.323061E+10
Minimum of Months 0.365062E+09 0.101547E+09 0.135851E+09 0.299957E+09 65025016.07
Maximum of Months 0.594845E+09 0.401951E+09 0.295976E+09 0.528953E+09 0.556105E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: B0FB49

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.416038E+09 0.289527E+09 0.126511E+09 0.338031E+09 0.444884E+09
February 0.475876E+09 0.321561E+09 0.154315E+09 0.423162E+09 0.339181E+09
March 0.464115E+09 0.293830E+09 0.170285E+09 0.391613E+09 0.316449E+09
April 0.406375E+09 0.220444E+09 0.185931E+09 0.339655E+09 0.195320E+09
May 0.352732E+09 0.120230E+09 0.232502E+09 0.306829E+09 0.101181E+09
June 0.306237E+09 81237692.39 0.224999E+09 0.288378E+09 59470005.68
July 0.345963E+09 0.109182E+09 0.236781E+09 0.343282E+09 52024651.42
August 0.369719E+09 0.154417E+09 0.215302E+09 0.376331E+09 63621552.49
September 0.383712E+09 0.204377E+09 0.179335E+09 0.384471E+09 0.113039E+09
October 0.338833E+09 0.199403E+09 0.139430E+09 0.315626E+09 0.190549E+09
November 0.292050E+09 0.183369E+09 0.108681E+09 0.250779E+09 0.275704E+09
December 0.321212E+09 0.210702E+09 0.110510E+09 0.239966E+09 0.433285E+09
           
Annual Sum or Average 0.447286E+10 0.238828E+10 0.208458E+10 0.399812E+10 0.258471E+10
Minimum of Months 0.292050E+09 81237692.39 0.108681E+09 0.239966E+09 52024651.42
Maximum of Months 0.475876E+09 0.321561E+09 0.236781E+09 0.423162E+09 0.444884E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: FE9BC9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 98459059.43 41989689.01 56469370.42 28986473.78 0.392809E+09
February 0.144967E+09 67427924.76 77539142.26 74234974.34 0.285034E+09
March 0.211470E+09 0.110123E+09 0.101347E+09 0.144178E+09 0.247371E+09
April 0.261449E+09 0.134771E+09 0.126678E+09 0.223651E+09 0.143734E+09
May 0.329717E+09 0.159656E+09 0.170062E+09 0.347113E+09 73098513.66
June 0.301940E+09 0.131170E+09 0.170770E+09 0.340536E+09 43536269.69
July 0.335717E+09 0.157538E+09 0.178179E+09 0.391629E+09 38171363.41
August 0.280821E+09 0.130110E+09 0.150710E+09 0.314316E+09 46668866.50
September 0.212552E+09 97329397.92 0.115223E+09 0.207463E+09 84005969.08
October 0.138681E+09 56735262.56 81946140.00 96135087.45 0.146363E+09
November 81298237.90 27985214.77 53313023.14 28947140.29 0.227910E+09
December 75009480.66 26751569.98 48257910.68 14385217.38 0.379101E+09
           
Annual Sum or Average 0.247208E+10 0.114159E+10 0.133049E+10 0.221158E+10 0.210780E+10
Minimum of Months 75009480.66 26751569.98 48257910.68 14385217.38 38171363.41
Maximum of Months 0.335717E+09 0.159656E+09 0.178179E+09 0.391629E+09 0.392809E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 9DF7DE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 97111591.78 41989689.01 55121902.77 28752080.53 0.394304E+09
February 0.143053E+09 67427924.76 75625271.78 73510453.91 0.287267E+09
March 0.208854E+09 0.110123E+09 98731571.77 0.142614E+09 0.249165E+09
April 0.258232E+09 0.134760E+09 0.123472E+09 0.220865E+09 0.143999E+09
May 0.319001E+09 0.154765E+09 0.164236E+09 0.334969E+09 73568473.75
June 0.292616E+09 0.127489E+09 0.165127E+09 0.329683E+09 43528759.43
July 0.326531E+09 0.154045E+09 0.172486E+09 0.380861E+09 37969435.46
August 0.274024E+09 0.127945E+09 0.146079E+09 0.306582E+09 46640205.30
September 0.209682E+09 97329397.92 0.112353E+09 0.204246E+09 83843691.45
October 0.136725E+09 56735262.56 79989529.26 94416992.74 0.147307E+09
November 80009137.56 27985214.77 52023922.80 28526672.50 0.228927E+09
December 73912951.87 26751569.98 47161381.89 14274222.20 0.380210E+09
           
Annual Sum or Average 0.241975E+10 0.112735E+10 0.129241E+10 0.215930E+10 0.211673E+10
Minimum of Months 73912951.87 26751569.98 47161381.89 14274222.20 37969435.46
Maximum of Months 0.326531E+09 0.154765E+09 0.172486E+09 0.380861E+09 0.394304E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: D0BE44

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 93050957.10 41989689.01 51061268.09 28245439.09 0.396095E+09
February 0.137641E+09 67427924.76 70212869.25 71781190.37 0.289778E+09
March 0.201755E+09 0.110123E+09 91632177.59 0.139475E+09 0.251712E+09
April 0.241754E+09 0.128414E+09 0.113339E+09 0.205584E+09 0.146261E+09
May 0.292098E+09 0.142478E+09 0.149620E+09 0.304097E+09 73695969.75
June 0.265862E+09 0.115581E+09 0.150281E+09 0.298457E+09 43382048.32
July 0.300513E+09 0.142548E+09 0.157964E+09 0.350186E+09 37112358.79
August 0.256653E+09 0.122327E+09 0.134326E+09 0.286831E+09 45979899.02
September 0.201250E+09 97128383.11 0.104122E+09 0.195839E+09 83284984.30
October 0.130504E+09 56735262.56 73768389.06 89906638.19 0.147769E+09
November 75933908.90 27985214.77 47948694.13 27457493.07 0.230521E+09
December 70386755.52 26751569.98 43635185.53 14042605.70 0.381676E+09
           
Annual Sum or Average 0.226740E+10 0.107949E+10 0.118791E+10 0.201190E+10 0.212727E+10
Minimum of Months 70386755.52 26751569.98 43635185.53 14042605.70 37112358.79
Maximum of Months 0.300513E+09 0.142548E+09 0.157964E+09 0.350186E+09 0.396095E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 6B5226

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.132758E+09 55986252.01 76771272.12 39051607.90 0.525894E+09
February 0.195455E+09 89903899.68 0.105551E+09 0.100172E+09 0.381256E+09
March 0.284974E+09 0.146830E+09 0.138144E+09 0.194027E+09 0.329760E+09
April 0.352341E+09 0.179694E+09 0.172646E+09 0.301247E+09 0.191323E+09
May 0.447148E+09 0.214816E+09 0.232332E+09 0.470477E+09 98818074.61
June 0.417261E+09 0.181856E+09 0.235405E+09 0.470134E+09 59214507.69
July 0.460487E+09 0.215668E+09 0.244819E+09 0.535441E+09 53520547.32
August 0.378906E+09 0.173481E+09 0.205425E+09 0.422370E+09 65341274.36
September 0.286642E+09 0.129773E+09 0.156869E+09 0.278398E+09 0.114320E+09
October 0.186996E+09 75647016.75 0.111349E+09 0.129628E+09 0.197024E+09
November 0.109777E+09 37313619.69 72463741.63 39251965.38 0.303806E+09
December 0.101175E+09 35668759.98 65506503.16 19391470.90 0.506705E+09
           
Annual Sum or Average 0.335392E+10 0.153664E+10 0.181728E+10 0.299959E+10 0.282698E+10
Minimum of Months 0.101175E+09 35668759.98 65506503.16 19391470.90 53520547.32
Maximum of Months 0.460487E+09 0.215668E+09 0.244819E+09 0.535441E+09 0.525894E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 8F59F7

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.406289E+09 0.282808E+09 0.123481E+09 0.334233E+09 0.452967E+09
February 0.469576E+09 0.318122E+09 0.151454E+09 0.421971E+09 0.343027E+09
March 0.461565E+09 0.293323E+09 0.168242E+09 0.390407E+09 0.316895E+09
April 0.404442E+09 0.220444E+09 0.183998E+09 0.337580E+09 0.195312E+09
May 0.350204E+09 0.120230E+09 0.229974E+09 0.303527E+09 0.102621E+09
June 0.303574E+09 81237692.39 0.222336E+09 0.284447E+09 61171874.42
July 0.343169E+09 0.109182E+09 0.233987E+09 0.338268E+09 54639504.34
August 0.367401E+09 0.154416E+09 0.212986E+09 0.372205E+09 66277467.41
September 0.381920E+09 0.204361E+09 0.177559E+09 0.381608E+09 0.115185E+09
October 0.335555E+09 0.198106E+09 0.137448E+09 0.314300E+09 0.192488E+09
November 0.287572E+09 0.181057E+09 0.106514E+09 0.249334E+09 0.277980E+09
December 0.313486E+09 0.205106E+09 0.108380E+09 0.236192E+09 0.438840E+09
           
Annual Sum or Average 0.442475E+10 0.236839E+10 0.205636E+10 0.396407E+10 0.261741E+10
Minimum of Months 0.287572E+09 81237692.39 0.106514E+09 0.236192E+09 54639504.34
Maximum of Months 0.469576E+09 0.318122E+09 0.233987E+09 0.421971E+09 0.452967E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 44F571

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.361824E+09 0.250763E+09 0.111061E+09 0.292552E+09 0.465019E+09
February 0.432651E+09 0.294694E+09 0.137957E+09 0.388278E+09 0.351394E+09
March 0.433323E+09 0.278061E+09 0.155263E+09 0.369733E+09 0.321818E+09
April 0.387791E+09 0.216467E+09 0.171324E+09 0.324676E+09 0.196852E+09
May 0.334025E+09 0.119694E+09 0.214331E+09 0.287335E+09 0.102096E+09
June 0.287535E+09 81061226.58 0.206474E+09 0.267681E+09 60603717.46
July 0.326220E+09 0.108813E+09 0.217407E+09 0.320482E+09 53518882.86
August 0.351274E+09 0.152899E+09 0.198375E+09 0.355589E+09 65354427.07
September 0.362501E+09 0.197564E+09 0.164937E+09 0.363877E+09 0.115312E+09
October 0.311352E+09 0.184683E+09 0.126669E+09 0.291520E+09 0.194594E+09
November 0.260504E+09 0.163883E+09 96621158.83 0.223567E+09 0.283403E+09
December 0.275397E+09 0.178457E+09 96939790.35 0.202858E+09 0.451274E+09
           
Annual Sum or Average 0.412440E+10 0.222704E+10 0.189736E+10 0.368815E+10 0.266124E+10
Minimum of Months 0.260504E+09 81061226.58 96621158.83 0.202858E+09 53518882.86
Maximum of Months 0.433323E+09 0.294694E+09 0.217407E+09 0.388278E+09 0.465019E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 6BD844

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66154644.95 27601261.26 38553383.68 15914968.85 0.259088E+09
February 93910992.53 40047706.36 53863286.17 40282999.78 0.184314E+09
March 0.141729E+09 71108672.13 70619852.85 90926693.71 0.160690E+09
April 0.190160E+09 0.102597E+09 87562509.23 0.162737E+09 92920064.45
May 0.212627E+09 93488700.05 0.119138E+09 0.215016E+09 48081459.17
June 0.232952E+09 0.111454E+09 0.121498E+09 0.261359E+09 30099091.05
July 0.235812E+09 0.110742E+09 0.125070E+09 0.272643E+09 26988176.54
August 0.181819E+09 79488612.79 0.102331E+09 0.200185E+09 32902146.60
September 0.140920E+09 63096177.99 77823577.19 0.133703E+09 56268837.53
October 88152517.12 33429015.42 54723501.70 55979529.77 97613708.07
November 54292532.24 18141898.49 36150633.75 17578216.87 0.151270E+09
December 51187152.06 18907669.02 32279483.05 9587210.92 0.252235E+09
           
Annual Sum or Average 0.168972E+10 0.770104E+09 0.919612E+09 0.147591E+10 0.139247E+10
Minimum of Months 51187152.06 18141898.49 32279483.05 9587210.92 26988176.54
Maximum of Months 0.235812E+09 0.111454E+09 0.125070E+09 0.272643E+09 0.259088E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 86D536

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66154644.95 27601261.26 38553383.68 15914968.85 0.259088E+09
February 93910992.53 40047706.36 53863286.17 40282999.78 0.184314E+09
March 0.141729E+09 71108672.13 70619852.85 90926693.71 0.160690E+09
April 0.190160E+09 0.102597E+09 87562509.23 0.162737E+09 92920064.45
May 0.212627E+09 93488700.05 0.119138E+09 0.215016E+09 48081459.17
June 0.232952E+09 0.111454E+09 0.121498E+09 0.261359E+09 30099091.05
July 0.235812E+09 0.110742E+09 0.125070E+09 0.272643E+09 26988176.54
August 0.181819E+09 79488612.79 0.102331E+09 0.200185E+09 32902146.60
September 0.140920E+09 63096177.99 77823577.19 0.133703E+09 56268837.53
October 88152517.12 33429015.42 54723501.70 55979529.77 97613708.07
November 54292532.24 18141898.49 36150633.75 17578216.87 0.151270E+09
December 51187152.06 18907669.02 32279483.05 9587210.92 0.252235E+09
           
Annual Sum or Average 0.168972E+10 0.770104E+09 0.919612E+09 0.147591E+10 0.139247E+10
Minimum of Months 51187152.06 18141898.49 32279483.05 9587210.92 26988176.54
Maximum of Months 0.235812E+09 0.111454E+09 0.125070E+09 0.272643E+09 0.259088E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BAF71D

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66154644.95 27601261.26 38553383.68 15914968.85 0.259088E+09
February 93910992.53 40047706.36 53863286.17 40282999.78 0.184314E+09
March 0.141729E+09 71108672.13 70619852.85 90926693.71 0.160690E+09
April 0.190160E+09 0.102597E+09 87562509.23 0.162737E+09 92920064.45
May 0.212627E+09 93488700.05 0.119138E+09 0.215016E+09 48081459.17
June 0.232952E+09 0.111454E+09 0.121498E+09 0.261359E+09 30099091.05
July 0.235812E+09 0.110742E+09 0.125070E+09 0.272643E+09 26988176.54
August 0.181819E+09 79488612.79 0.102331E+09 0.200185E+09 32902146.60
September 0.140920E+09 63096177.99 77823577.19 0.133703E+09 56268837.53
October 88152517.12 33429015.42 54723501.70 55979529.77 97613708.07
November 54292532.24 18141898.49 36150633.75 17578216.87 0.151270E+09
December 51187152.06 18907669.02 32279483.05 9587210.92 0.252235E+09
           
Annual Sum or Average 0.168972E+10 0.770104E+09 0.919612E+09 0.147591E+10 0.139247E+10
Minimum of Months 51187152.06 18141898.49 32279483.05 9587210.92 26988176.54
Maximum of Months 0.235812E+09 0.111454E+09 0.125070E+09 0.272643E+09 0.259088E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 3833A2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66154644.95 27601261.26 38553383.68 15914968.85 0.259088E+09
February 93910992.53 40047706.36 53863286.17 40282999.78 0.184314E+09
March 0.141729E+09 71108672.13 70619852.85 90926693.71 0.160690E+09
April 0.190160E+09 0.102597E+09 87562509.23 0.162737E+09 92920064.45
May 0.212627E+09 93488700.05 0.119138E+09 0.215016E+09 48081459.17
June 0.232952E+09 0.111454E+09 0.121498E+09 0.261359E+09 30099091.05
July 0.235812E+09 0.110742E+09 0.125070E+09 0.272643E+09 26988176.54
August 0.181819E+09 79488612.79 0.102331E+09 0.200185E+09 32902146.60
September 0.140920E+09 63096177.99 77823577.19 0.133703E+09 56268837.53
October 88152517.12 33429015.42 54723501.70 55979529.77 97613708.07
November 54292532.24 18141898.49 36150633.75 17578216.87 0.151270E+09
December 51187152.06 18907669.02 32279483.05 9587210.92 0.252235E+09
           
Annual Sum or Average 0.168972E+10 0.770104E+09 0.919612E+09 0.147591E+10 0.139247E+10
Minimum of Months 51187152.06 18141898.49 32279483.05 9587210.92 26988176.54
Maximum of Months 0.235812E+09 0.111454E+09 0.125070E+09 0.272643E+09 0.259088E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 2111A1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 22051548.32 9200420.42 12851127.89 5714914.12 81166594.14
February 31303664.18 13349235.45 17954428.72 14354286.43 56709613.76
March 47242841.66 23702890.71 23539950.95 32030075.39 47701158.64
April 63386662.52 34199159.44 29187503.08 57136022.00 26014065.99
May 70875569.29 31162900.02 39712669.27 74504843.68 13003944.91
June 77650741.11 37151498.51 40499242.60 89110353.12 8162702.74
July 78604044.28 36914153.66 41689890.61 92019499.69 7856925.18
August 60606487.08 26496204.26 34110282.82 67777201.84 9578627.87
September 46973251.73 21032059.33 25941192.40 45929795.66 16363815.22
October 29384172.37 11143005.14 18241167.23 19933924.56 28616245.23
November 18097510.75 6047299.50 12050211.25 6338995.32 45915414.53
December 17062384.02 6302556.34 10759827.68 3460670.85 79049369.71
           
Annual Sum or Average 0.563239E+09 0.256701E+09 0.306537E+09 0.508311E+09 0.420138E+09
Minimum of Months 17062384.02 6047299.50 10759827.68 3460670.85 7856925.18
Maximum of Months 78604044.28 37151498.51 41689890.61 92019499.69 81166594.14



Table of Contents

Report: WindowEnergyReportMonthly

For: 9BC521

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 77268202.41 0.00 77268202.41 184552.82 0.703824E+09
February 0.107204E+09 0.00 0.107204E+09 4152097.75 0.501901E+09
March 0.146027E+09 0.00 0.146027E+09 15472437.20 0.416129E+09
April 0.185219E+09 1407804.11 0.183811E+09 76746097.79 0.221526E+09
May 0.269083E+09 14338418.98 0.254744E+09 0.216978E+09 0.101781E+09
June 0.290557E+09 31735756.16 0.258821E+09 0.281204E+09 61027441.74
July 0.286797E+09 24422424.07 0.262374E+09 0.293252E+09 59273096.14
August 0.217924E+09 3678422.54 0.214246E+09 0.208614E+09 74658069.04
September 0.164387E+09 37382.79 0.164349E+09 0.114871E+09 0.134504E+09
October 0.117951E+09 0.00 0.117951E+09 34706333.24 0.239939E+09
November 75579211.78 0.00 75579211.78 3976125.21 0.392945E+09
December 65467801.55 0.00 65467801.55 0.00 0.673807E+09
           
Annual Sum or Average 0.200346E+10 75620208.66 0.192784E+10 0.125016E+10 0.358131E+10
Minimum of Months 65467801.55 0.00 65467801.55 0.00 59273096.14
Maximum of Months 0.290557E+09 31735756.16 0.262374E+09 0.293252E+09 0.703824E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 142781

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 75462918.79 0.00 75462918.79 191814.96 0.682069E+09
February 0.104699E+09 0.00 0.104699E+09 4167626.42 0.486184E+09
March 0.142615E+09 0.00 0.142615E+09 15450369.01 0.403257E+09
April 0.180892E+09 1374912.37 0.179517E+09 75445295.03 0.215010E+09
May 0.262796E+09 14003418.14 0.248793E+09 0.212182E+09 99176628.66
June 0.283768E+09 30994286.33 0.252774E+09 0.274486E+09 59621473.44
July 0.280096E+09 23851821.92 0.256244E+09 0.286096E+09 57951827.25
August 0.212833E+09 3592480.39 0.209240E+09 0.203719E+09 72868391.55
September 0.160470E+09 29661.71 0.160441E+09 0.112471E+09 0.130918E+09
October 0.115195E+09 0.00 0.115195E+09 34279271.89 0.233000E+09
November 73813389.50 0.00 73813389.50 3947253.50 0.380815E+09
December 63938220.87 0.00 63938220.87 0.00 0.652655E+09
           
Annual Sum or Average 0.195658E+10 73846580.86 0.188273E+10 0.122244E+10 0.347353E+10
Minimum of Months 63938220.87 0.00 63938220.87 0.00 57951827.25
Maximum of Months 0.283768E+09 30994286.33 0.256244E+09 0.286096E+09 0.682069E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: E74902

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 75462918.79 0.00 75462918.79 201123.82 0.680817E+09
February 0.104699E+09 0.00 0.104699E+09 4366152.51 0.485574E+09
March 0.142615E+09 0.00 0.142615E+09 16083833.19 0.403087E+09
April 0.180892E+09 1374912.37 0.179517E+09 77071341.03 0.216234E+09
May 0.262796E+09 14003418.14 0.248793E+09 0.212368E+09 0.102733E+09
June 0.283768E+09 30994286.33 0.252774E+09 0.273735E+09 63280201.22
July 0.280096E+09 23851821.92 0.256244E+09 0.284525E+09 62542101.03
August 0.212833E+09 3592480.39 0.209240E+09 0.202910E+09 78099037.47
September 0.160550E+09 36942.70 0.160513E+09 0.113021E+09 0.135583E+09
October 0.115195E+09 0.00 0.115195E+09 34917145.97 0.235954E+09
November 73813389.50 0.00 73813389.50 3908003.07 0.382225E+09
December 63938220.87 0.00 63938220.87 0.00 0.652725E+09
           
Annual Sum or Average 0.195666E+10 73853861.84 0.188281E+10 0.122311E+10 0.349885E+10
Minimum of Months 63938220.87 0.00 63938220.87 0.00 62542101.03
Maximum of Months 0.283768E+09 30994286.33 0.256244E+09 0.284525E+09 0.680817E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: 93BBC3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 75462918.79 0.00 75462918.79 189109.83 0.686122E+09
February 0.104699E+09 0.00 0.104699E+09 4251047.36 0.489556E+09
March 0.142615E+09 0.00 0.142615E+09 15742969.43 0.406232E+09
April 0.180892E+09 1374912.37 0.179517E+09 76589577.10 0.217583E+09
May 0.262796E+09 14003418.14 0.248793E+09 0.212094E+09 0.102985E+09
June 0.283768E+09 30994286.33 0.252774E+09 0.273879E+09 63283621.51
July 0.280096E+09 23851821.92 0.256244E+09 0.284814E+09 62498464.08
August 0.212833E+09 3592480.39 0.209240E+09 0.202926E+09 78176837.13
September 0.160550E+09 36942.70 0.160513E+09 0.112713E+09 0.136141E+09
October 0.115195E+09 0.00 0.115195E+09 34538792.81 0.237310E+09
November 73813389.50 0.00 73813389.50 3843485.53 0.385188E+09
December 63938220.87 0.00 63938220.87 0.00 0.658137E+09
           
Annual Sum or Average 0.195666E+10 73853861.84 0.188281E+10 0.122158E+10 0.352321E+10
Minimum of Months 63938220.87 0.00 63938220.87 0.00 62498464.08
Maximum of Months 0.283768E+09 30994286.33 0.256244E+09 0.284814E+09 0.686122E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: C635A6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.103274E+09 72350150.56 30924146.67 85613475.85 0.107785E+09
February 0.115482E+09 78599936.93 36881978.39 0.106739E+09 83556009.33
March 0.109161E+09 68971186.35 40190300.95 96600825.85 77291910.85
April 99132157.72 54424258.63 44707899.10 85312033.58 45768733.61
May 86175977.59 30053896.50 56122081.09 76031826.50 24049339.80
June 74582883.39 20309423.10 54273460.30 70437542.45 14689934.24
July 84454167.63 27286660.82 57167506.81 82980569.67 14101143.97
August 90361262.02 38446687.57 51914574.45 91388658.37 17337865.17
September 92372306.67 49536371.72 42835934.96 93834996.41 29162417.77
October 81053482.05 47918598.11 33134883.94 77586332.89 47887193.26
November 71914945.22 45565072.56 26349872.66 63368610.02 66863475.94
December 79742004.34 52675576.32 27066428.02 60921878.93 0.104921E+09
           
Annual Sum or Average 0.108771E+10 0.586138E+09 0.501569E+09 0.990816E+09 0.633415E+09
Minimum of Months 71914945.22 20309423.10 26349872.66 60921878.93 14101143.97
Maximum of Months 0.115482E+09 78599936.93 57167506.81 0.106739E+09 0.107785E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 63.82 82.97 77.67 54.05 23.62 0.00 0.00
February 88.86 69.75 98.35 66.46 31.89 0.00 0.00
March 74.66 57.11 86.64 54.85 31.79 0.00 0.00
April 67.94 34.14 78.39 42.52 35.87 0.00 0.00
May 61.14 15.29 65.85 22.44 43.40 0.00 0.00
June 60.06 8.47 59.07 15.67 43.40 0.00 0.00
July 68.39 6.86 64.58 20.38 44.20 0.00 0.00
August 73.75 8.73 69.02 28.83 40.19 0.00 0.00
September 76.88 18.47 74.02 39.42 34.59 0.00 0.00
October 60.62 33.01 63.25 37.22 26.03 0.00 0.00
November 49.40 51.98 56.34 35.37 20.96 0.00 0.00
December 45.32 80.95 59.96 39.33 20.63 0.00 0.00
               
Annual Sum or Average 65.74 38.84 70.92 37.87 33.05 0.00 0.00
Minimum of Months 45.32 6.86 56.34 15.67 20.63 0.00 0.00
Maximum of Months 88.86 82.97 98.35 66.46 44.20 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 CAFE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 244.73 349.41 293.97 206.10 87.87 0.00 0.00
February 331.42 304.62 360.75 244.99 115.76 0.00 0.00
March 264.21 252.89 304.06 189.27 114.79 0.00 0.00
April 250.80 155.71 289.63 156.93 132.70 0.00 0.00
May 222.70 76.80 250.07 87.74 162.32 0.00 0.00
June 215.92 48.17 224.96 62.06 162.90 0.00 0.00
July 247.17 42.37 246.01 80.19 165.82 0.00 0.00
August 269.34 52.94 259.46 110.04 149.42 0.00 0.00
September 272.96 93.92 265.91 139.41 126.51 0.00 0.00
October 215.17 154.10 226.84 132.37 94.47 0.00 0.00
November 185.99 227.57 211.10 133.74 77.35 0.00 0.00
December 174.01 338.17 229.29 151.26 78.02 0.00 0.00
               
Annual Sum or Average 240.57 174.13 262.87 140.52 122.35 0.00 0.00
Minimum of Months 174.01 42.37 211.10 62.06 77.35 0.00 0.00
Maximum of Months 331.42 349.41 360.75 244.99 165.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 CLEAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.08 93.45 10.79 0.00 10.79 0.00 0.00
February 1.41 72.02 16.64 0.00 16.64 0.00 0.00
March 4.01 51.75 20.54 0.00 20.54 0.00 0.00
April 16.75 25.98 26.68 0.04 26.64 0.00 0.00
May 39.57 9.02 36.07 0.86 35.21 0.00 0.00
June 51.27 4.13 39.33 2.71 36.62 0.00 0.00
July 52.44 3.29 38.10 1.90 36.20 0.00 0.00
August 39.15 4.28 30.06 0.19 29.86 0.00 0.00
September 23.45 12.87 23.80 0.00 23.80 0.00 0.00
October 8.12 27.05 16.46 0.00 16.46 0.00 0.00
November 1.26 49.83 10.88 0.00 10.88 0.00 0.00
December 0.00 89.20 9.12 0.00 9.12 0.00 0.00
               
Annual Sum or Average 19.91 36.77 23.24 0.48 22.76 0.00 0.00
Minimum of Months 0.00 3.29 9.12 0.00 9.12 0.00 0.00
Maximum of Months 52.44 93.45 39.33 2.71 36.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 IT HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 LOBBY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 29.76 396.01 98.15 41.81 56.35 0.00 0.00
February 84.17 320.89 160.23 74.33 85.90 0.00 0.00
March 146.51 251.14 211.25 109.64 101.61 0.00 0.00
April 234.10 150.79 270.04 138.65 131.39 0.00 0.00
May 349.62 76.56 331.24 160.41 170.84 0.00 0.00
June 359.35 49.13 319.48 140.32 179.16 0.00 0.00
July 395.39 44.63 341.51 161.04 180.47 0.00 0.00
August 312.56 54.26 280.77 129.54 151.23 0.00 0.00
September 213.85 93.59 219.24 100.13 119.11 0.00 0.00
October 96.31 154.88 138.06 56.49 81.58 0.00 0.00
November 30.24 244.81 83.65 28.79 54.86 0.00 0.00
December 14.78 386.13 74.65 26.63 48.02 0.00 0.00
               
Annual Sum or Average 189.52 184.67 210.97 97.45 113.52 0.00 0.00
Minimum of Months 14.78 44.63 74.65 26.63 48.02 0.00 0.00
Maximum of Months 395.39 396.01 341.51 161.04 180.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 275.41 25.65 0.00 25.65 0.00 0.00
February 0.81 224.00 39.37 0.00 39.37 0.00 0.00
March 3.59 172.05 48.47 0.00 48.47 0.00 0.00
April 23.48 99.41 62.87 0.15 62.72 0.00 0.00
May 71.21 46.23 86.50 2.98 83.52 0.00 0.00
June 94.52 28.56 92.89 6.43 86.46 0.00 0.00
July 97.99 24.55 89.53 4.74 84.79 0.00 0.00
August 71.90 30.68 71.02 0.66 70.36 0.00 0.00
September 39.82 57.48 56.36 0.00 56.36 0.00 0.00
October 9.97 100.68 39.30 0.00 39.30 0.00 0.00
November 1.17 167.36 25.96 0.00 25.96 0.00 0.00
December 0.00 265.95 21.79 0.00 21.79 0.00 0.00
               
Annual Sum or Average 34.76 123.94 55.06 1.25 53.80 0.00 0.00
Minimum of Months 0.00 24.55 21.79 0.00 21.79 0.00 0.00
Maximum of Months 97.99 275.41 92.89 6.43 86.46 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 MED GAS

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 127.21 328.40 204.73 128.71 76.02 0.00 0.00
February 210.98 271.96 274.35 166.03 108.32 0.00 0.00
March 223.26 213.94 279.11 162.80 116.31 0.00 0.00
April 277.42 125.01 303.51 164.21 139.30 0.00 0.00
May 305.59 57.48 290.47 114.70 175.77 0.00 0.00
June 347.08 33.95 297.89 117.34 180.55 0.00 0.00
July 363.89 29.29 305.25 123.46 181.80 0.00 0.00
August 319.32 37.33 273.80 117.01 156.80 0.00 0.00
September 275.37 72.82 256.77 127.53 129.24 0.00 0.00
October 175.90 127.42 192.33 99.41 92.92 0.00 0.00
November 115.72 203.14 154.57 84.74 69.82 0.00 0.00
December 87.06 322.26 158.15 92.79 65.36 0.00 0.00
               
Annual Sum or Average 235.74 151.40 248.99 124.57 124.42 0.00 0.00
Minimum of Months 87.06 29.29 154.57 84.74 65.36 0.00 0.00
Maximum of Months 363.89 328.40 305.25 166.03 181.80 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 19.75 282.53 74.10 30.92 43.18 0.00 0.00
February 55.22 222.02 116.46 49.66 66.79 0.00 0.00
March 111.54 167.94 158.75 79.65 79.10 0.00 0.00
April 208.54 95.33 220.09 118.75 101.35 0.00 0.00
May 270.75 41.87 238.16 104.71 133.44 0.00 0.00
June 336.29 23.56 269.62 129.00 140.62 0.00 0.00
July 337.18 20.28 264.13 124.04 140.09 0.00 0.00
August 251.49 26.31 203.65 89.03 114.62 0.00 0.00
September 178.25 50.65 163.10 73.03 90.07 0.00 0.00
October 76.71 93.80 98.74 37.44 61.29 0.00 0.00
November 25.44 162.82 62.84 21.00 41.84 0.00 0.00
December 11.81 275.60 57.33 21.18 36.16 0.00 0.00
               
Annual Sum or Average 157.42 121.49 160.74 73.26 87.48 0.00 0.00
Minimum of Months 11.81 20.28 57.33 21.00 36.16 0.00 0.00
Maximum of Months 337.18 282.53 269.62 129.00 140.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 PACU

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.05 256.62 27.55 0.00 27.55 0.00 0.00
February 1.95 203.95 42.32 0.00 42.32 0.00 0.00
March 6.57 152.93 52.08 0.00 52.08 0.00 0.00
April 31.92 84.91 67.25 0.06 67.19 0.00 0.00
May 85.44 36.11 92.96 3.20 89.75 0.00 0.00
June 114.00 20.11 103.34 9.42 93.92 0.00 0.00
July 116.57 16.59 98.31 6.35 91.96 0.00 0.00
August 85.62 21.00 76.28 0.60 75.68 0.00 0.00
September 49.83 45.43 60.49 0.00 60.49 0.00 0.00
October 15.27 85.17 42.10 0.00 42.10 0.00 0.00
November 1.93 147.92 27.86 0.00 27.86 0.00 0.00
December 0.00 246.41 23.36 0.00 23.36 0.00 0.00
               
Annual Sum or Average 42.69 109.37 59.57 1.64 57.93 0.00 0.00
Minimum of Months 0.00 16.59 23.36 0.00 23.36 0.00 0.00
Maximum of Months 116.57 256.62 103.34 9.42 93.92 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 72.45 143.16 89.57 61.74 27.84 0.00 0.00
February 99.16 122.89 111.66 74.59 37.06 0.00 0.00
March 79.00 100.85 95.91 58.31 37.60 0.00 0.00
April 77.31 61.75 92.41 48.26 44.15 0.00 0.00
May 72.06 29.66 82.05 28.32 53.73 0.00 0.00
June 71.28 18.46 74.43 20.21 54.23 0.00 0.00
July 82.84 15.68 81.68 26.31 55.37 0.00 0.00
August 88.64 19.65 85.10 35.47 49.63 0.00 0.00
September 84.44 35.92 84.60 43.01 41.59 0.00 0.00
October 63.84 60.84 70.80 40.17 30.63 0.00 0.00
November 55.47 92.44 65.29 40.63 24.66 0.00 0.00
December 51.76 139.33 69.87 45.36 24.51 0.00 0.00
               
Annual Sum or Average 74.68 69.82 83.43 43.34 40.10 0.00 0.00
Minimum of Months 51.76 15.68 65.29 20.21 24.51 0.00 0.00
Maximum of Months 99.16 143.16 111.66 74.59 55.37 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 257.74 327.19 310.66 216.19 94.47 0.00 0.00
February 358.35 274.92 393.42 265.84 127.58 0.00 0.00
March 301.26 224.55 346.56 219.41 127.15 0.00 0.00
April 274.73 133.97 313.56 170.10 143.47 0.00 0.00
May 248.13 59.78 263.39 89.78 173.61 0.00 0.00
June 244.01 33.07 236.29 62.68 173.61 0.00 0.00
July 277.02 26.73 258.34 81.53 176.81 0.00 0.00
August 298.31 33.98 276.07 115.31 160.77 0.00 0.00
September 310.33 72.46 296.07 157.70 138.38 0.00 0.00
October 244.87 129.76 253.01 148.90 104.11 0.00 0.00
November 199.64 204.46 225.35 141.49 83.86 0.00 0.00
December 183.05 318.85 239.85 157.33 82.52 0.00 0.00
               
Annual Sum or Average 265.80 152.78 283.67 151.46 132.20 0.00 0.00
Minimum of Months 183.05 26.73 225.35 62.68 82.52 0.00 0.00
Maximum of Months 358.35 327.19 393.42 265.84 176.81 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 11.80 32.26 15.22 10.21 5.01 0.00 0.00
February 16.58 27.23 19.56 12.72 6.84 0.00 0.00
March 13.51 21.92 17.38 10.27 7.11 0.00 0.00
April 12.58 13.00 16.17 7.77 8.40 0.00 0.00
May 12.73 5.86 14.65 4.53 10.12 0.00 0.00
June 13.22 3.47 13.30 3.03 10.27 0.00 0.00
July 15.50 2.85 14.78 4.25 10.52 0.00 0.00
August 15.98 3.73 15.37 6.01 9.37 0.00 0.00
September 14.55 7.34 15.14 7.31 7.83 0.00 0.00
October 11.08 13.02 12.88 7.16 5.72 0.00 0.00
November 9.15 20.45 11.31 6.83 4.47 0.00 0.00
December 8.41 31.48 11.81 7.44 4.36 0.00 0.00
               
Annual Sum or Average 12.90 15.16 14.77 7.26 7.50 0.00 0.00
Minimum of Months 8.41 2.85 11.31 3.03 4.36 0.00 0.00
Maximum of Months 16.58 32.26 19.56 12.72 10.52 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 SCRUB

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 SOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 125.78 243.35 178.58 118.55 60.03 0.00 0.00
February 193.43 202.02 234.83 151.50 83.33 0.00 0.00
March 183.33 162.28 223.77 137.11 86.65 0.00 0.00
April 194.70 95.93 221.41 119.71 101.70 0.00 0.00
May 211.13 43.43 210.07 84.56 125.50 0.00 0.00
June 208.58 24.36 190.57 63.84 126.73 0.00 0.00
July 235.10 20.26 208.48 79.39 129.09 0.00 0.00
August 226.73 25.99 204.87 90.04 114.83 0.00 0.00
September 208.02 54.06 200.13 103.88 96.24 0.00 0.00
October 145.39 96.28 159.08 88.57 70.51 0.00 0.00
November 104.04 152.50 132.27 77.94 54.33 0.00 0.00
December 86.27 238.04 137.50 85.33 52.17 0.00 0.00
               
Annual Sum or Average 176.72 112.82 191.50 99.71 91.80 0.00 0.00
Minimum of Months 86.27 20.26 132.27 63.84 52.17 0.00 0.00
Maximum of Months 235.10 243.35 234.83 151.50 129.09 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 63.32 86.58 77.67 54.05 23.62 0.00 0.00
February 88.14 73.23 98.35 66.46 31.89 0.00 0.00
March 73.84 60.80 86.64 54.85 31.79 0.00 0.00
April 66.69 37.58 78.39 42.52 35.87 0.00 0.00
May 59.20 17.94 65.85 22.44 43.40 0.00 0.00
June 57.64 10.69 59.07 15.67 43.40 0.00 0.00
July 65.94 9.07 64.58 20.38 44.20 0.00 0.00
August 71.81 11.38 69.02 28.83 40.19 0.00 0.00
September 75.65 21.33 74.02 39.42 34.59 0.00 0.00
October 59.76 36.14 63.25 37.22 26.03 0.00 0.00
November 48.79 55.52 56.34 35.37 20.96 0.00 0.00
December 44.83 84.96 59.96 39.33 20.63 0.00 0.00
               
Annual Sum or Average 64.47 41.96 70.92 37.87 33.05 0.00 0.00
Minimum of Months 44.83 9.07 56.34 15.67 20.63 0.00 0.00
Maximum of Months 88.14 86.58 98.35 66.46 44.20 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.14 374.91 42.26 0.00 42.26 0.00 0.00
February 3.17 295.35 64.92 0.00 64.92 0.00 0.00
March 10.34 220.30 79.87 0.00 79.87 0.00 0.00
April 48.99 119.77 104.68 0.80 103.89 0.00 0.00
May 130.18 49.51 147.18 7.84 139.33 0.00 0.00
June 173.75 27.94 164.22 17.94 146.28 0.00 0.00
July 174.55 25.53 156.86 13.36 143.51 0.00 0.00
August 125.33 32.93 119.19 2.01 117.18 0.00 0.00
September 73.50 67.14 92.91 0.02 92.89 0.00 0.00
October 22.64 124.57 64.51 0.00 64.51 0.00 0.00
November 2.72 215.91 42.72 0.00 42.72 0.00 0.00
December 0.00 360.17 35.81 0.00 35.81 0.00 0.00
               
Annual Sum or Average 64.15 158.95 93.07 3.51 89.56 0.00 0.00
Minimum of Months 0.00 25.53 35.81 0.00 35.81 0.00 0.00
Maximum of Months 174.55 374.91 164.22 17.94 146.28 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 8.05 128.04 32.93 13.74 19.19 0.00 0.00
February 22.82 100.18 51.76 22.07 29.69 0.00 0.00
March 46.73 76.84 70.55 35.40 35.16 0.00 0.00
April 86.89 44.16 97.82 52.78 45.04 0.00 0.00
May 111.29 20.99 105.85 46.54 59.31 0.00 0.00
June 138.51 13.20 119.83 57.33 62.50 0.00 0.00
July 138.83 11.88 117.39 55.13 62.26 0.00 0.00
August 101.86 15.08 90.51 39.57 50.94 0.00 0.00
September 70.93 27.08 72.49 32.46 40.03 0.00 0.00
October 29.16 46.65 43.88 16.64 27.24 0.00 0.00
November 9.39 76.83 27.93 9.33 18.60 0.00 0.00
December 4.86 125.34 25.48 9.41 16.07 0.00 0.00
               
Annual Sum or Average 64.31 57.02 71.44 32.56 38.88 0.00 0.00
Minimum of Months 4.86 11.88 25.48 9.33 16.07 0.00 0.00
Maximum of Months 138.83 128.04 119.83 57.33 62.50 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 6.09 95.29 24.47 10.31 14.16 0.00 0.00
February 17.17 74.29 38.48 16.55 21.92 0.00 0.00
March 35.11 56.90 52.51 26.55 25.96 0.00 0.00
April 65.30 32.47 72.87 39.58 33.29 0.00 0.00
May 83.37 15.35 78.71 34.90 43.81 0.00 0.00
June 103.73 9.69 89.20 43.00 46.20 0.00 0.00
July 103.71 8.81 87.39 41.35 46.04 0.00 0.00
August 76.19 10.99 67.31 29.68 37.63 0.00 0.00
September 53.02 19.98 53.89 24.34 29.54 0.00 0.00
October 21.81 34.48 32.55 12.48 20.07 0.00 0.00
November 7.05 56.85 20.70 7.00 13.70 0.00 0.00
December 3.68 93.19 18.91 7.06 11.85 0.00 0.00
               
Annual Sum or Average 48.17 42.23 53.14 24.42 28.72 0.00 0.00
Minimum of Months 3.68 8.81 18.91 7.00 11.85 0.00 0.00
Maximum of Months 103.73 95.29 89.20 43.00 46.20 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 183.66 334.39 257.70 172.45 85.24 0.00 0.00
February 272.02 279.25 333.88 215.93 117.95 0.00 0.00
March 246.67 228.26 312.84 191.10 121.73 0.00 0.00
April 255.32 138.38 308.53 167.15 141.38 0.00 0.00
May 253.76 65.78 276.93 102.24 174.69 0.00 0.00
June 271.99 39.91 267.09 90.01 177.08 0.00 0.00
July 298.95 33.44 281.79 102.49 179.30 0.00 0.00
August 288.59 42.39 274.94 116.16 158.78 0.00 0.00
September 275.22 81.05 276.42 142.62 133.81 0.00 0.00
October 197.90 137.98 222.67 124.15 98.52 0.00 0.00
November 148.48 211.02 189.96 113.12 76.84 0.00 0.00
December 128.71 326.69 199.00 125.06 73.94 0.00 0.00
               
Annual Sum or Average 234.77 159.36 266.33 138.02 128.31 0.00 0.00
Minimum of Months 128.71 33.44 189.96 90.01 73.94 0.00 0.00
Maximum of Months 298.95 334.39 333.88 215.93 179.30 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 58.34 344.55 146.73 85.40 61.33 0.00 0.00
February 131.41 283.22 211.66 122.20 89.45 0.00 0.00
March 171.94 229.27 236.82 137.08 99.73 0.00 0.00
April 231.07 139.66 267.99 144.39 123.60 0.00 0.00
May 291.86 66.67 283.72 129.12 154.60 0.00 0.00
June 291.70 38.96 261.06 102.81 158.24 0.00 0.00
July 332.10 31.99 286.62 125.22 161.40 0.00 0.00
August 294.16 39.50 261.78 121.42 140.36 0.00 0.00
September 231.70 78.08 228.74 114.47 114.26 0.00 0.00
October 127.86 134.68 159.97 79.59 80.38 0.00 0.00
November 62.36 212.52 114.44 56.97 57.47 0.00 0.00
December 35.12 337.38 112.09 59.31 52.78 0.00 0.00
               
Annual Sum or Average 188.59 160.85 214.28 106.39 107.89 0.00 0.00
Minimum of Months 35.12 31.99 112.09 56.97 52.78 0.00 0.00
Maximum of Months 332.10 344.55 286.62 144.39 161.40 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 105.94 140.50 129.44 90.08 39.36 0.00 0.00
February 147.42 117.76 163.92 110.77 53.16 0.00 0.00
March 123.70 97.69 144.40 91.42 52.98 0.00 0.00
April 112.19 60.13 130.65 70.87 59.78 0.00 0.00
May 100.69 27.76 109.75 37.41 72.34 0.00 0.00
June 99.07 15.65 98.46 26.12 72.34 0.00 0.00
July 113.53 12.48 107.64 33.97 73.67 0.00 0.00
August 122.72 15.61 115.03 48.04 66.99 0.00 0.00
September 127.79 32.60 123.36 65.71 57.66 0.00 0.00
October 100.68 56.85 105.42 62.04 43.38 0.00 0.00
November 81.94 88.12 93.89 58.95 34.94 0.00 0.00
December 75.20 136.56 99.94 65.56 34.38 0.00 0.00
               
Annual Sum or Average 108.97 66.58 118.19 63.11 55.08 0.00 0.00
Minimum of Months 75.20 12.48 93.89 26.12 34.38 0.00 0.00
Maximum of Months 147.42 140.50 163.92 110.77 73.67 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 169.36 224.70 207.11 144.13 62.98 0.00 0.00
February 235.68 188.17 262.28 177.23 85.05 0.00 0.00
March 197.86 155.71 231.04 146.27 84.77 0.00 0.00
April 179.73 95.20 209.04 113.40 95.64 0.00 0.00
May 161.83 43.26 175.59 59.85 115.74 0.00 0.00
June 159.44 24.12 157.53 41.79 115.74 0.00 0.00
July 182.72 18.94 172.22 54.35 117.87 0.00 0.00
August 197.19 23.78 184.05 76.87 107.18 0.00 0.00
September 204.95 50.95 197.38 105.13 92.25 0.00 0.00
October 161.34 89.97 168.67 99.26 69.41 0.00 0.00
November 131.13 140.43 150.23 94.33 55.91 0.00 0.00
December 120.26 218.32 159.90 104.89 55.01 0.00 0.00
               
Annual Sum or Average 174.70 105.77 189.11 100.98 88.14 0.00 0.00
Minimum of Months 120.26 18.94 150.23 41.79 55.01 0.00 0.00
Maximum of Months 235.68 224.70 262.28 177.23 117.87 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 62.85 84.00 77.67 54.05 23.62 0.00 0.00
February 87.33 70.66 98.35 66.46 31.89 0.00 0.00
March 73.17 58.80 86.64 54.85 31.79 0.00 0.00
April 66.19 36.28 78.39 42.52 35.87 0.00 0.00
May 59.29 16.89 65.85 22.44 43.40 0.00 0.00
June 58.21 9.65 59.07 15.67 43.40 0.00 0.00
July 66.85 7.78 64.58 20.38 44.20 0.00 0.00
August 72.23 9.83 69.02 28.83 40.19 0.00 0.00
September 75.39 20.01 74.02 39.42 34.59 0.00 0.00
October 59.47 34.43 63.25 37.22 26.03 0.00 0.00
November 48.52 52.84 56.34 35.37 20.96 0.00 0.00
December 44.62 81.58 59.96 39.33 20.63 0.00 0.00
               
Annual Sum or Average 64.35 40.09 70.92 37.87 33.05 0.00 0.00
Minimum of Months 44.62 7.78 56.34 15.67 20.63 0.00 0.00
Maximum of Months 87.33 84.00 98.35 66.46 44.20 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 15.88 258.54 65.03 27.48 37.55 0.00 0.00
February 44.66 202.13 102.30 44.14 58.15 0.00 0.00
March 91.64 156.22 139.67 70.80 68.87 0.00 0.00
April 170.29 90.41 193.88 105.55 88.32 0.00 0.00
May 219.10 42.09 209.28 93.08 116.20 0.00 0.00
June 275.00 25.53 237.26 114.67 122.59 0.00 0.00
July 277.59 21.35 232.43 110.26 122.18 0.00 0.00
August 204.23 26.55 178.96 79.14 99.82 0.00 0.00
September 140.89 51.95 143.26 64.91 78.34 0.00 0.00
October 57.47 91.95 86.48 33.28 53.20 0.00 0.00
November 18.56 152.86 54.99 18.66 36.32 0.00 0.00
December 9.57 251.54 50.24 18.82 31.41 0.00 0.00
               
Annual Sum or Average 127.49 113.91 141.29 65.12 76.17 0.00 0.00
Minimum of Months 9.57 21.35 50.24 18.66 31.41 0.00 0.00
Maximum of Months 277.59 258.54 237.26 114.67 122.59 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.04 197.27 21.13 0.00 21.13 0.00 0.00
February 1.28 156.92 32.46 0.00 32.46 0.00 0.00
March 4.30 119.12 39.93 0.00 39.93 0.00 0.00
April 22.26 66.81 52.34 0.40 51.94 0.00 0.00
May 62.64 28.55 73.59 3.92 69.67 0.00 0.00
June 85.34 16.28 82.11 8.97 73.14 0.00 0.00
July 87.88 13.44 78.43 6.68 71.75 0.00 0.00
August 63.09 17.13 59.60 1.01 58.59 0.00 0.00
September 36.01 36.42 46.43 0.01 46.42 0.00 0.00
October 10.58 66.75 32.26 0.00 32.26 0.00 0.00
November 1.24 114.04 21.36 0.00 21.36 0.00 0.00
December 0.00 188.61 17.90 0.00 17.90 0.00 0.00
               
Annual Sum or Average 31.41 84.81 46.53 1.76 44.78 0.00 0.00
Minimum of Months 0.00 13.44 17.90 0.00 17.90 0.00 0.00
Maximum of Months 87.88 197.27 82.11 8.97 73.14 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.05 266.22 28.17 0.00 28.17 0.00 0.00
February 1.66 212.22 43.28 0.00 43.28 0.00 0.00
March 5.70 161.35 53.25 0.00 53.25 0.00 0.00
April 29.73 90.56 69.69 0.50 69.19 0.00 0.00
May 84.38 38.21 98.12 5.23 92.89 0.00 0.00
June 115.28 21.49 109.48 11.96 97.52 0.00 0.00
July 118.93 17.40 104.58 8.91 95.67 0.00 0.00
August 85.45 22.31 79.46 1.34 78.12 0.00 0.00
September 48.60 48.63 61.89 0.01 61.88 0.00 0.00
October 14.21 89.96 43.01 0.00 43.01 0.00 0.00
November 1.66 154.19 28.48 0.00 28.48 0.00 0.00
December 0.00 254.78 23.87 0.00 23.87 0.00 0.00
               
Annual Sum or Average 42.40 114.37 62.03 2.34 59.69 0.00 0.00
Minimum of Months 0.00 17.40 23.87 0.00 23.87 0.00 0.00
Maximum of Months 118.93 266.22 109.48 11.96 97.52 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.05 264.72 28.17 0.00 28.17 0.00 0.00
February 1.63 211.20 43.28 0.00 43.28 0.00 0.00
March 5.51 161.07 53.25 0.00 53.25 0.00 0.00
April 28.86 91.53 69.48 0.42 69.06 0.00 0.00
May 82.19 39.51 98.02 5.18 92.85 0.00 0.00
June 112.42 22.77 109.48 11.96 97.52 0.00 0.00
July 116.07 18.74 104.56 8.90 95.66 0.00 0.00
August 82.88 23.97 79.18 1.23 77.95 0.00 0.00
September 47.15 50.30 61.89 0.01 61.88 0.00 0.00
October 13.58 91.28 43.01 0.00 43.01 0.00 0.00
November 1.57 154.54 28.48 0.00 28.48 0.00 0.00
December 0.00 253.52 23.87 0.00 23.87 0.00 0.00
               
Annual Sum or Average 41.24 114.86 61.98 2.32 59.66 0.00 0.00
Minimum of Months 0.00 18.74 23.87 0.00 23.87 0.00 0.00
Maximum of Months 116.07 264.72 109.48 11.96 97.52 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.02 133.50 13.92 0.00 13.92 0.00 0.00
February 0.76 106.67 21.38 0.00 21.38 0.00 0.00
March 2.64 81.37 26.31 0.00 26.31 0.00 0.00
April 14.20 46.22 34.20 0.13 34.07 0.00 0.00
May 40.32 19.74 47.70 2.10 45.60 0.00 0.00
June 55.57 11.23 53.47 5.59 47.88 0.00 0.00
July 57.31 9.20 50.95 4.00 46.94 0.00 0.00
August 41.03 11.85 38.80 0.44 38.36 0.00 0.00
September 23.39 25.18 30.58 0.00 30.58 0.00 0.00
October 6.64 45.95 21.25 0.00 21.25 0.00 0.00
November 0.76 78.00 14.07 0.00 14.07 0.00 0.00
December 0.00 127.87 11.79 0.00 11.79 0.00 0.00
               
Annual Sum or Average 20.34 57.86 30.41 1.03 29.39 0.00 0.00
Minimum of Months 0.00 9.20 11.79 0.00 11.79 0.00 0.00
Maximum of Months 57.31 133.50 53.47 5.59 47.88 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 23.81 388.64 98.80 41.22 57.58 0.00 0.00
February 67.20 306.40 155.28 66.22 89.06 0.00 0.00
March 136.85 240.34 211.66 106.20 105.47 0.00 0.00
April 253.55 142.79 293.46 158.33 135.13 0.00 0.00
May 324.90 70.46 317.54 139.62 177.92 0.00 0.00
June 407.25 45.28 359.49 172.00 187.50 0.00 0.00
July 410.84 39.41 352.17 165.39 186.78 0.00 0.00
August 301.67 48.46 271.53 118.71 152.82 0.00 0.00
September 208.76 85.99 217.47 97.37 120.10 0.00 0.00
October 85.12 145.12 131.65 49.92 81.73 0.00 0.00
November 27.44 234.21 83.78 28.00 55.79 0.00 0.00
December 14.36 378.73 76.44 28.24 48.21 0.00 0.00
               
Annual Sum or Average 189.08 176.64 214.32 97.68 116.64 0.00 0.00
Minimum of Months 14.36 39.41 76.44 28.00 48.21 0.00 0.00
Maximum of Months 410.84 388.64 359.49 172.00 187.50 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 244.75 661.45 385.17 247.77 137.40 0.00 0.00
February 393.20 563.46 507.28 316.56 190.72 0.00 0.00
March 397.92 456.99 509.26 303.47 205.79 0.00 0.00
April 448.61 282.26 534.10 286.17 247.94 0.00 0.00
May 506.10 140.73 529.34 219.57 309.77 0.00 0.00
June 508.31 86.65 491.01 174.99 316.02 0.00 0.00
July 573.97 74.98 531.73 211.25 320.48 0.00 0.00
August 537.54 92.71 504.38 223.10 281.28 0.00 0.00
September 471.16 169.05 471.22 239.13 232.09 0.00 0.00
October 305.47 281.29 355.31 188.98 166.33 0.00 0.00
November 206.46 424.16 287.89 162.57 125.32 0.00 0.00
December 165.95 643.57 299.09 178.78 120.31 0.00 0.00
               
Annual Sum or Average 396.52 322.04 450.06 228.80 221.27 0.00 0.00
Minimum of Months 165.95 74.98 287.89 162.57 120.31 0.00 0.00
Maximum of Months 573.97 661.45 534.10 316.56 320.48 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 5.86 97.76 24.70 10.31 14.39 0.00 0.00
February 16.67 76.70 38.82 16.55 22.26 0.00 0.00
March 34.17 59.84 52.92 26.55 26.37 0.00 0.00
April 63.38 35.20 73.36 39.58 33.78 0.00 0.00
May 81.36 17.05 79.39 34.90 44.48 0.00 0.00
June 102.00 10.76 89.87 43.00 46.87 0.00 0.00
July 102.96 9.27 88.04 41.35 46.70 0.00 0.00
August 75.60 11.42 67.88 29.68 38.21 0.00 0.00
September 52.42 20.72 54.37 24.34 30.02 0.00 0.00
October 21.38 35.60 32.91 12.48 20.43 0.00 0.00
November 6.84 58.31 20.95 7.00 13.95 0.00 0.00
December 3.54 95.23 19.11 7.06 12.05 0.00 0.00
               
Annual Sum or Average 47.33 43.86 53.58 24.42 29.16 0.00 0.00
Minimum of Months 3.54 9.27 19.11 7.00 12.05 0.00 0.00
Maximum of Months 102.96 97.76 89.87 43.00 46.87 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.01 276.76 26.07 0.00 26.07 0.00 0.00
February 0.87 224.88 40.19 0.00 40.19 0.00 0.00
March 3.49 174.47 49.60 0.00 49.60 0.00 0.00
April 22.80 102.16 64.72 0.27 64.45 0.00 0.00
May 68.13 47.53 87.56 2.38 85.17 0.00 0.00
June 93.08 28.69 96.59 7.66 88.92 0.00 0.00
July 97.43 25.00 92.96 5.28 87.68 0.00 0.00
August 70.82 32.07 72.77 0.60 72.18 0.00 0.00
September 38.84 59.60 57.53 0.01 57.53 0.00 0.00
October 9.33 102.76 39.78 0.00 39.78 0.00 0.00
November 1.01 168.15 26.29 0.00 26.29 0.00 0.00
December 0.00 266.37 22.04 0.00 22.04 0.00 0.00
               
Annual Sum or Average 34.03 125.28 56.42 1.35 55.07 0.00 0.00
Minimum of Months 0.00 25.00 22.04 0.00 22.04 0.00 0.00
Maximum of Months 97.43 276.76 96.59 7.66 88.92 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 2 X-RAY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 LOCKER

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.03 269.59 28.17 0.00 28.17 0.00 0.00
February 1.36 217.12 43.28 0.00 43.28 0.00 0.00
March 4.75 168.02 53.25 0.00 53.25 0.00 0.00
April 26.47 98.18 69.79 0.53 69.26 0.00 0.00
May 77.49 45.13 98.12 5.23 92.89 0.00 0.00
June 106.39 27.53 109.48 11.96 97.52 0.00 0.00
July 109.69 23.74 104.58 8.91 95.67 0.00 0.00
August 78.66 30.09 79.46 1.34 78.12 0.00 0.00
September 44.14 56.98 61.92 0.01 61.91 0.00 0.00
October 12.08 98.34 43.01 0.00 43.01 0.00 0.00
November 1.38 161.53 28.48 0.00 28.48 0.00 0.00
December 0.00 258.68 23.87 0.00 23.87 0.00 0.00
               
Annual Sum or Average 38.78 120.84 62.04 2.34 59.70 0.00 0.00
Minimum of Months 0.00 23.74 23.87 0.00 23.87 0.00 0.00
Maximum of Months 109.69 269.59 109.48 11.96 97.52 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.04 198.92 21.13 0.00 21.13 0.00 0.00
February 1.08 158.44 32.46 0.00 32.46 0.00 0.00
March 3.67 120.83 39.93 0.00 39.93 0.00 0.00
April 20.37 67.98 52.34 0.40 51.94 0.00 0.00
May 59.32 29.32 73.59 3.92 69.67 0.00 0.00
June 81.66 16.86 82.11 8.97 73.14 0.00 0.00
July 84.41 13.88 78.43 6.68 71.75 0.00 0.00
August 60.12 17.74 59.60 1.01 58.59 0.00 0.00
September 33.84 37.23 46.43 0.01 46.42 0.00 0.00
October 9.39 67.98 32.26 0.00 32.26 0.00 0.00
November 1.01 115.63 21.36 0.00 21.36 0.00 0.00
December 0.00 190.11 17.90 0.00 17.90 0.00 0.00
               
Annual Sum or Average 29.76 85.94 46.53 1.76 44.78 0.00 0.00
Minimum of Months 0.00 13.88 17.90 0.00 17.90 0.00 0.00
Maximum of Months 84.41 198.92 82.11 8.97 73.14 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 15.14 285.97 65.30 27.48 37.82 0.00 0.00
February 42.29 228.50 102.67 44.14 58.53 0.00 0.00
March 88.49 180.30 140.09 70.80 69.30 0.00 0.00
April 164.11 112.44 194.38 105.55 88.83 0.00 0.00
May 209.85 58.43 210.02 93.08 116.94 0.00 0.00
June 265.04 39.24 237.94 114.67 123.28 0.00 0.00
July 267.27 35.08 233.08 110.26 122.82 0.00 0.00
August 197.08 42.30 179.55 79.14 100.41 0.00 0.00
September 134.53 71.49 143.79 64.91 78.88 0.00 0.00
October 53.63 116.42 86.92 33.28 53.64 0.00 0.00
November 17.35 181.10 55.28 18.66 36.62 0.00 0.00
December 8.96 280.01 50.48 18.82 31.66 0.00 0.00
               
Annual Sum or Average 122.38 135.56 141.77 65.12 76.65 0.00 0.00
Minimum of Months 8.96 35.08 50.48 18.66 31.66 0.00 0.00
Maximum of Months 267.27 285.97 237.94 114.67 123.28 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.14 933.42 97.22 0.00 97.22 0.00 0.00
February 4.73 751.23 149.35 0.00 149.35 0.00 0.00
March 15.33 582.17 183.79 0.00 183.79 0.00 0.00
April 88.32 340.34 239.95 1.37 238.58 0.00 0.00
May 260.13 156.33 335.10 15.66 319.43 0.00 0.00
June 357.76 95.34 373.30 38.29 335.02 0.00 0.00
July 370.08 82.57 356.98 28.10 328.88 0.00 0.00
August 264.85 104.74 272.74 3.84 268.91 0.00 0.00
September 148.08 197.83 213.63 0.02 213.61 0.00 0.00
October 39.30 340.96 148.45 0.00 148.45 0.00 0.00
November 4.33 559.50 98.26 0.00 98.26 0.00 0.00
December 0.00 896.50 82.38 0.00 82.38 0.00 0.00
               
Annual Sum or Average 130.22 418.69 212.91 7.30 205.61 0.00 0.00
Minimum of Months 0.00 82.57 82.38 0.00 82.38 0.00 0.00
Maximum of Months 370.08 933.42 373.30 38.29 335.02 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 614.05 1066.06 850.75 571.40 279.35 0.00 0.00
February 902.09 883.71 1100.00 714.26 385.73 0.00 0.00
March 812.87 714.78 1025.15 628.17 396.98 0.00 0.00
April 833.99 425.10 1003.99 543.99 460.01 0.00 0.00
May 827.61 190.80 896.63 329.16 567.47 0.00 0.00
June 886.93 108.06 860.36 285.71 574.65 0.00 0.00
July 978.18 85.81 909.97 327.86 582.11 0.00 0.00
August 949.69 108.39 893.84 377.30 516.54 0.00 0.00
September 906.97 234.02 903.29 467.27 436.01 0.00 0.00
October 656.45 420.04 731.27 409.69 321.58 0.00 0.00
November 495.44 661.68 626.21 374.72 251.49 0.00 0.00
December 431.10 1039.07 656.97 414.51 242.45 0.00 0.00
               
Annual Sum or Average 773.50 493.10 869.91 451.92 417.99 0.00 0.00
Minimum of Months 431.10 85.81 626.21 285.71 242.45 0.00 0.00
Maximum of Months 978.18 1066.06 1100.00 714.26 582.11 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 420.46 969.74 651.42 425.37 226.05 0.00 0.00
February 666.36 810.46 864.43 548.84 315.59 0.00 0.00
March 647.89 669.88 838.74 507.31 331.43 0.00 0.00
April 698.48 420.19 842.49 451.20 391.30 0.00 0.00
May 766.25 211.48 812.19 327.70 484.50 0.00 0.00
June 762.17 129.70 745.47 254.08 491.39 0.00 0.00
July 867.25 109.76 811.54 312.23 499.31 0.00 0.00
August 829.83 134.19 786.11 343.80 442.31 0.00 0.00
September 751.23 247.20 758.67 388.54 370.13 0.00 0.00
October 511.18 407.84 594.32 324.12 270.20 0.00 0.00
November 353.08 619.15 485.89 279.99 205.89 0.00 0.00
December 285.76 948.43 501.62 305.30 196.33 0.00 0.00
               
Annual Sum or Average 629.57 471.70 723.44 371.24 352.20 0.00 0.00
Minimum of Months 285.76 109.76 485.89 254.08 196.33 0.00 0.00
Maximum of Months 867.25 969.74 864.43 548.84 499.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 226.44 516.93 336.35 220.12 116.23 0.00 0.00
February 361.33 429.65 453.74 290.48 163.26 0.00 0.00
March 345.96 351.31 440.51 268.15 172.36 0.00 0.00
April 365.95 219.34 441.58 237.89 203.69 0.00 0.00
May 394.11 111.18 422.41 169.78 252.63 0.00 0.00
June 393.05 68.49 389.03 132.78 256.26 0.00 0.00
July 445.11 59.62 421.85 161.91 259.94 0.00 0.00
August 428.93 73.05 409.79 179.51 230.28 0.00 0.00
September 393.76 131.77 397.79 205.13 192.66 0.00 0.00
October 272.05 215.55 311.34 171.16 140.18 0.00 0.00
November 190.32 326.52 253.80 147.47 106.33 0.00 0.00
December 153.12 503.47 257.64 156.52 101.11 0.00 0.00
               
Annual Sum or Average 330.54 249.80 377.44 194.45 183.00 0.00 0.00
Minimum of Months 153.12 59.62 253.80 132.78 101.11 0.00 0.00
Maximum of Months 445.11 516.93 453.74 290.48 259.94 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FLOOR 3 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 23.77 386.93 98.80 41.22 57.58 0.00 0.00
February 66.61 304.75 155.28 66.22 89.06 0.00 0.00
March 135.79 239.98 211.66 106.20 105.47 0.00 0.00
April 251.14 143.40 293.46 158.33 135.13 0.00 0.00
May 321.11 71.81 317.54 139.62 177.92 0.00 0.00
June 403.33 46.45 359.49 172.00 187.50 0.00 0.00
July 407.17 40.30 352.17 165.39 186.78 0.00 0.00
August 298.96 49.14 271.53 118.71 152.82 0.00 0.00
September 206.33 86.83 217.47 97.37 120.10 0.00 0.00
October 83.60 145.78 131.65 49.92 81.73 0.00 0.00
November 27.13 233.44 83.78 28.00 55.79 0.00 0.00
December 14.32 376.70 76.44 28.24 48.21 0.00 0.00
               
Annual Sum or Average 187.20 176.62 214.32 97.68 116.64 0.00 0.00
Minimum of Months 14.32 40.30 76.44 28.00 48.21 0.00 0.00
Maximum of Months 407.17 386.93 359.49 172.00 187.50 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: NE STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.16 545.62 65.26 3.44 61.82 0.00 0.00
February 3.90 426.41 100.53 5.52 95.01 0.00 0.00
March 15.07 315.30 125.41 8.85 116.56 0.00 0.00
April 74.20 171.89 165.70 14.27 151.43 0.00 0.00
May 186.68 78.52 225.04 22.22 202.83 0.00 0.00
June 248.66 49.59 251.53 38.53 213.00 0.00 0.00
July 250.60 46.64 241.00 31.81 209.20 0.00 0.00
August 178.94 58.34 183.45 12.61 170.85 0.00 0.00
September 103.61 106.89 143.45 8.14 135.31 0.00 0.00
October 30.44 184.50 98.02 4.16 93.86 0.00 0.00
November 3.34 314.07 64.62 2.33 62.29 0.00 0.00
December 0.00 523.47 54.69 2.35 52.33 0.00 0.00
               
Annual Sum or Average 91.84 234.35 143.43 12.88 130.55 0.00 0.00
Minimum of Months 0.00 46.64 54.69 2.33 52.33 0.00 0.00
Maximum of Months 250.60 545.62 251.53 38.53 213.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: NW ELEVATOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: NW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.15 510.36 56.35 0.00 56.35 0.00 0.00
February 3.56 403.08 86.56 0.00 86.56 0.00 0.00
March 11.88 302.16 106.49 0.00 106.49 0.00 0.00
April 59.28 167.37 139.58 1.06 138.52 0.00 0.00
May 158.48 76.81 196.23 10.46 185.78 0.00 0.00
June 211.27 48.83 218.96 23.92 195.04 0.00 0.00
July 212.57 46.68 209.15 17.81 191.34 0.00 0.00
August 151.52 58.35 158.93 2.68 156.24 0.00 0.00
September 87.09 104.83 123.88 0.03 123.85 0.00 0.00
October 25.93 176.70 86.02 0.00 86.02 0.00 0.00
November 2.99 296.07 56.95 0.00 56.95 0.00 0.00
December 0.00 489.42 47.74 0.00 47.74 0.00 0.00
               
Annual Sum or Average 77.52 222.67 124.09 4.68 119.41 0.00 0.00
Minimum of Months 0.00 46.68 47.74 0.00 47.74 0.00 0.00
Maximum of Months 212.57 510.36 218.96 23.92 195.04 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: SW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 31.96 40.24 38.56 27.01 11.55 0.00 0.00
February 44.12 34.54 47.74 32.49 15.25 0.00 0.00
March 36.07 28.86 40.76 25.75 15.01 0.00 0.00
April 32.91 17.66 38.25 21.00 17.25 0.00 0.00
May 28.39 8.98 32.17 11.22 20.95 0.00 0.00
June 27.17 5.67 28.77 7.84 20.94 0.00 0.00
July 30.98 5.26 31.53 10.19 21.34 0.00 0.00
August 34.12 6.47 33.74 14.35 19.38 0.00 0.00
September 36.20 11.25 35.64 19.11 16.53 0.00 0.00
October 28.97 17.88 30.26 17.89 12.37 0.00 0.00
November 24.45 25.80 27.74 17.58 10.17 0.00 0.00
December 22.75 39.17 29.77 19.67 10.11 0.00 0.00
               
Annual Sum or Average 31.42 20.09 34.49 18.59 15.90 0.00 0.00
Minimum of Months 22.75 5.26 27.74 7.84 10.11 0.00 0.00
Maximum of Months 44.12 40.24 47.74 32.49 21.34 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.170944E+09 0.222235E+09 0.208019E+09 0.144763E+09 63255465.77 0.00 0.00
February 0.214975E+09 0.168729E+09 0.237938E+09 0.160780E+09 77157523.13 0.00 0.00
March 0.199980E+09 0.152969E+09 0.232058E+09 0.146915E+09 85142476.22 0.00 0.00
April 0.176106E+09 88501828.09 0.203187E+09 0.110222E+09 92965343.12 0.00 0.00
May 0.163751E+09 40960694.58 0.176366E+09 60115035.59 0.116251E+09 0.00 0.00
June 0.155666E+09 21960997.26 0.153118E+09 40618846.20 0.112500E+09 0.00 0.00
July 0.183176E+09 18385215.77 0.172981E+09 54590944.70 0.118390E+09 0.00 0.00
August 0.197544E+09 23394821.16 0.184859E+09 77208326.48 0.107651E+09 0.00 0.00
September 0.199283E+09 47865236.80 0.191856E+09 0.102188E+09 89667623.89 0.00 0.00
October 0.162352E+09 88417349.11 0.169417E+09 99701737.44 69714834.93 0.00 0.00
November 0.128046E+09 0.134725E+09 0.146025E+09 91684299.18 54340559.53 0.00 0.00
December 0.121376E+09 0.216810E+09 0.160606E+09 0.105351E+09 55254886.48 0.00 0.00
               
Annual Sum or Average 0.207320E+10 0.122495E+10 0.223643E+10 0.119414E+10 0.104229E+10 0.00 0.00
Minimum of Months 0.121376E+09 18385215.77 0.146025E+09 40618846.20 54340559.53 0.00 0.00
Maximum of Months 0.214975E+09 0.222235E+09 0.237938E+09 0.160780E+09 0.118390E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 CAFE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.655495E+09 0.935869E+09 0.787375E+09 0.552019E+09 0.235357E+09 0.00 0.00
February 0.801771E+09 0.736939E+09 0.872717E+09 0.592671E+09 0.280046E+09 0.00 0.00
March 0.707664E+09 0.677332E+09 0.814404E+09 0.506944E+09 0.307460E+09 0.00 0.00
April 0.650066E+09 0.403605E+09 0.750717E+09 0.406750E+09 0.343966E+09 0.00 0.00
May 0.596472E+09 0.205695E+09 0.669779E+09 0.235010E+09 0.434769E+09 0.00 0.00
June 0.559677E+09 0.124869E+09 0.583101E+09 0.160872E+09 0.422229E+09 0.00 0.00
July 0.662025E+09 0.113484E+09 0.658909E+09 0.214774E+09 0.444135E+09 0.00 0.00
August 0.721394E+09 0.141787E+09 0.694925E+09 0.294722E+09 0.400203E+09 0.00 0.00
September 0.707511E+09 0.243434E+09 0.689244E+09 0.361342E+09 0.327902E+09 0.00 0.00
October 0.576311E+09 0.412738E+09 0.607555E+09 0.354540E+09 0.253015E+09 0.00 0.00
November 0.482073E+09 0.589868E+09 0.547165E+09 0.346663E+09 0.200502E+09 0.00 0.00
December 0.466066E+09 0.905743E+09 0.614124E+09 0.405146E+09 0.208977E+09 0.00 0.00
               
Annual Sum or Average 0.758653E+10 0.549136E+10 0.829002E+10 0.443146E+10 0.385856E+10 0.00 0.00
Minimum of Months 0.466066E+09 0.113484E+09 0.547165E+09 0.160872E+09 0.200502E+09 0.00 0.00
Maximum of Months 0.801771E+09 0.935869E+09 0.872717E+09 0.592671E+09 0.444135E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 CLEAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 218560.57 0.250305E+09 28900621.33 0.00 28900621.33 0.00 0.00
February 3419216.40 0.174240E+09 40256813.88 0.00 40256813.88 0.00 0.00
March 10734141.77 0.138596E+09 55024122.34 0.00 55024122.34 0.00 0.00
April 43409614.41 67351579.54 69159547.79 113020.56 69046527.23 0.00 0.00
May 0.105988E+09 24158684.57 96619118.54 2313438.49 94305680.05 0.00 0.00
June 0.132902E+09 10715280.78 0.101951E+09 7019081.47 94931905.43 0.00 0.00
July 0.140447E+09 8813737.76 0.102046E+09 5079708.54 96966193.07 0.00 0.00
August 0.104869E+09 11471413.89 80500344.42 521203.12 79979141.30 0.00 0.00
September 60770800.49 33370608.04 61702208.85 504.77 61701704.08 0.00 0.00
October 21760529.04 72455508.85 44084096.87 0.00 44084096.87 0.00 0.00
November 3265988.94 0.129162E+09 28193042.44 0.00 28193042.44 0.00 0.00
December 5693.04 0.238913E+09 24420294.73 0.00 24420294.73 0.00 0.00
               
Annual Sum or Average 0.627790E+09 0.115955E+10 0.732857E+09 15046956.95 0.717810E+09 0.00 0.00
Minimum of Months 5693.04 8813737.76 24420294.73 0.00 24420294.73 0.00 0.00
Maximum of Months 0.140447E+09 0.250305E+09 0.102046E+09 7019081.47 96966193.07 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 IT HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 LOBBY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 79707512.45 0.106066E+10 0.262893E+09 0.111973E+09 0.150921E+09 0.00 0.00
February 0.203615E+09 0.776287E+09 0.387618E+09 0.179808E+09 0.207810E+09 0.00 0.00
March 0.392417E+09 0.672645E+09 0.565810E+09 0.293661E+09 0.272149E+09 0.00 0.00
April 0.606791E+09 0.390854E+09 0.699946E+09 0.359389E+09 0.340558E+09 0.00 0.00
May 0.936432E+09 0.205057E+09 0.887201E+09 0.429631E+09 0.457570E+09 0.00 0.00
June 0.931438E+09 0.127350E+09 0.828104E+09 0.363711E+09 0.464393E+09 0.00 0.00
July 0.105901E+10 0.119537E+09 0.914709E+09 0.431337E+09 0.483373E+09 0.00 0.00
August 0.837150E+09 0.145326E+09 0.752027E+09 0.346961E+09 0.405066E+09 0.00 0.00
September 0.554310E+09 0.242596E+09 0.568283E+09 0.259545E+09 0.308738E+09 0.00 0.00
October 0.257946E+09 0.414827E+09 0.369790E+09 0.151294E+09 0.218496E+09 0.00 0.00
November 78370532.34 0.634540E+09 0.216815E+09 74627239.38 0.142188E+09 0.00 0.00
December 39598799.27 0.103421E+10 0.199947E+09 71337519.96 0.128610E+09 0.00 0.00
               
Annual Sum or Average 0.597679E+10 0.582389E+10 0.665314E+10 0.307327E+10 0.357987E+10 0.00 0.00
Minimum of Months 39598799.27 0.119537E+09 0.199947E+09 71337519.96 0.128610E+09 0.00 0.00
Maximum of Months 0.105901E+10 0.106066E+10 0.914709E+09 0.431337E+09 0.483373E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 1251.36 0.737659E+09 68713312.92 0.00 68713312.92 0.00 0.00
February 1950719.74 0.541896E+09 95251312.77 0.00 95251312.77 0.00 0.00
March 9624892.95 0.460828E+09 0.129821E+09 0.00 0.129821E+09 0.00 0.00
April 60869762.30 0.257668E+09 0.162960E+09 400609.80 0.162560E+09 0.00 0.00
May 0.190736E+09 0.123829E+09 0.231688E+09 7979126.16 0.223709E+09 0.00 0.00
June 0.244988E+09 74031209.24 0.240772E+09 16679262.70 0.224093E+09 0.00 0.00
July 0.262456E+09 65764098.43 0.239796E+09 12706727.29 0.227089E+09 0.00 0.00
August 0.192571E+09 82172465.17 0.190226E+09 1767738.01 0.188459E+09 0.00 0.00
September 0.103201E+09 0.148989E+09 0.146082E+09 0.00 0.146082E+09 0.00 0.00
October 26704089.03 0.269656E+09 0.105267E+09 0.00 0.105267E+09 0.00 0.00
November 3045141.92 0.433796E+09 67281587.71 0.00 67281587.71 0.00 0.00
December 0.00 0.712310E+09 58358782.70 0.00 58358782.70 0.00 0.00
               
Annual Sum or Average 0.109615E+10 0.390860E+10 0.173622E+10 39533463.98 0.169668E+10 0.00 0.00
Minimum of Months 0.00 65764098.43 58358782.70 0.00 58358782.70 0.00 0.00
Maximum of Months 0.262456E+09 0.737659E+09 0.240772E+09 16679262.70 0.227089E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 MED GAS

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.340725E+09 0.879580E+09 0.548347E+09 0.344729E+09 0.203618E+09 0.00 0.00
February 0.510396E+09 0.657938E+09 0.663698E+09 0.401656E+09 0.262042E+09 0.00 0.00
March 0.597970E+09 0.573022E+09 0.747572E+09 0.436048E+09 0.311525E+09 0.00 0.00
April 0.719069E+09 0.324023E+09 0.786695E+09 0.425639E+09 0.361056E+09 0.00 0.00
May 0.818502E+09 0.153956E+09 0.777985E+09 0.307207E+09 0.470778E+09 0.00 0.00
June 0.899629E+09 87986868.30 0.772141E+09 0.304147E+09 0.467995E+09 0.00 0.00
July 0.974638E+09 78458791.66 0.817587E+09 0.330667E+09 0.486920E+09 0.00 0.00
August 0.855271E+09 99976663.04 0.733358E+09 0.313394E+09 0.419964E+09 0.00 0.00
September 0.713760E+09 0.188758E+09 0.665551E+09 0.330569E+09 0.334982E+09 0.00 0.00
October 0.471132E+09 0.341269E+09 0.515138E+09 0.266262E+09 0.248877E+09 0.00 0.00
November 0.299941E+09 0.526529E+09 0.400635E+09 0.219652E+09 0.180982E+09 0.00 0.00
December 0.233171E+09 0.863136E+09 0.423586E+09 0.248518E+09 0.175069E+09 0.00 0.00
               
Annual Sum or Average 0.743420E+10 0.477463E+10 0.785229E+10 0.392849E+10 0.392381E+10 0.00 0.00
Minimum of Months 0.233171E+09 78458791.66 0.400635E+09 0.219652E+09 0.175069E+09 0.00 0.00
Maximum of Months 0.974638E+09 0.879580E+09 0.817587E+09 0.436048E+09 0.486920E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 52897374.36 0.756729E+09 0.198464E+09 82803783.79 0.115660E+09 0.00 0.00
February 0.133591E+09 0.537103E+09 0.281733E+09 0.120143E+09 0.161590E+09 0.00 0.00
March 0.298736E+09 0.449822E+09 0.425186E+09 0.213326E+09 0.211860E+09 0.00 0.00
April 0.540526E+09 0.247097E+09 0.570480E+09 0.307792E+09 0.262688E+09 0.00 0.00
May 0.725169E+09 0.112146E+09 0.637880E+09 0.280466E+09 0.357414E+09 0.00 0.00
June 0.871659E+09 61068532.45 0.698857E+09 0.334363E+09 0.364493E+09 0.00 0.00
July 0.903105E+09 54327210.73 0.707436E+09 0.332227E+09 0.375209E+09 0.00 0.00
August 0.673581E+09 70478214.26 0.545458E+09 0.238466E+09 0.306993E+09 0.00 0.00
September 0.462021E+09 0.131274E+09 0.422759E+09 0.189289E+09 0.233471E+09 0.00 0.00
October 0.205457E+09 0.251237E+09 0.264458E+09 0.100287E+09 0.164171E+09 0.00 0.00
November 65945860.04 0.422017E+09 0.162878E+09 54425695.48 0.108452E+09 0.00 0.00
December 31635999.87 0.738165E+09 0.153561E+09 56723007.05 96838449.14 0.00 0.00
               
Annual Sum or Average 0.496432E+10 0.383146E+10 0.506915E+10 0.231031E+10 0.275884E+10 0.00 0.00
Minimum of Months 31635999.87 54327210.73 0.153561E+09 54425695.48 96838449.14 0.00 0.00
Maximum of Months 0.903105E+09 0.756729E+09 0.707436E+09 0.334363E+09 0.375209E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 PACU

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 133699.88 0.687343E+09 73803014.38 0.00 73803014.38 0.00 0.00
February 4720958.64 0.493395E+09 0.102381E+09 0.00 0.102381E+09 0.00 0.00
March 17584289.63 0.409598E+09 0.139481E+09 0.00 0.139481E+09 0.00 0.00
April 82738702.02 0.220096E+09 0.174303E+09 143223.62 0.174160E+09 0.00 0.00
May 0.228849E+09 96715191.55 0.248976E+09 8576406.41 0.240400E+09 0.00 0.00
June 0.295497E+09 52126593.33 0.267854E+09 24407898.15 0.243446E+09 0.00 0.00
July 0.312225E+09 44438436.26 0.263322E+09 17005049.60 0.246317E+09 0.00 0.00
August 0.229317E+09 56248058.86 0.204320E+09 1614110.86 0.202706E+09 0.00 0.00
September 0.129159E+09 0.117754E+09 0.156794E+09 105.67 0.156793E+09 0.00 0.00
October 40907178.14 0.228116E+09 0.112749E+09 0.00 0.112749E+09 0.00 0.00
November 4997345.88 0.383414E+09 72204072.78 0.00 72204072.78 0.00 0.00
December 0.00 0.659974E+09 62562626.42 0.00 62562626.42 0.00 0.00
               
Annual Sum or Average 0.134613E+10 0.344922E+10 0.187875E+10 51746794.31 0.182700E+10 0.00 0.00
Minimum of Months 0.00 44438436.26 62562626.42 0.00 62562626.42 0.00 0.00
Maximum of Months 0.312225E+09 0.687343E+09 0.267854E+09 24407898.15 0.246317E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.194062E+09 0.383443E+09 0.239911E+09 0.165353E+09 74558105.85 0.00 0.00
February 0.239888E+09 0.297302E+09 0.270118E+09 0.180460E+09 89657553.56 0.00 0.00
March 0.211596E+09 0.270114E+09 0.256878E+09 0.156174E+09 0.100704E+09 0.00 0.00
April 0.200384E+09 0.160054E+09 0.239515E+09 0.125090E+09 0.114425E+09 0.00 0.00
May 0.193018E+09 79437318.14 0.219759E+09 75854945.99 0.143904E+09 0.00 0.00
June 0.184766E+09 47847899.77 0.192932E+09 52378133.02 0.140554E+09 0.00 0.00
July 0.221875E+09 42008903.57 0.218781E+09 70478076.00 0.148303E+09 0.00 0.00
August 0.237401E+09 52643391.67 0.227942E+09 95010658.26 0.132931E+09 0.00 0.00
September 0.218871E+09 93101961.29 0.219289E+09 0.111487E+09 0.107802E+09 0.00 0.00
October 0.170982E+09 0.162952E+09 0.189625E+09 0.107596E+09 82028783.73 0.00 0.00
November 0.143782E+09 0.239595E+09 0.169237E+09 0.105318E+09 63919169.37 0.00 0.00
December 0.138629E+09 0.373188E+09 0.187143E+09 0.121485E+09 65658022.47 0.00 0.00
               
Annual Sum or Average 0.235525E+10 0.220169E+10 0.263113E+10 0.136668E+10 0.126444E+10 0.00 0.00
Minimum of Months 0.138629E+09 42008903.57 0.169237E+09 52378133.02 63919169.37 0.00 0.00
Maximum of Months 0.239888E+09 0.383443E+09 0.270118E+09 0.180460E+09 0.148303E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.690327E+09 0.876339E+09 0.832076E+09 0.579054E+09 0.253022E+09 0.00 0.00
February 0.866930E+09 0.665090E+09 0.951751E+09 0.643121E+09 0.308630E+09 0.00 0.00
March 0.806882E+09 0.601424E+09 0.928231E+09 0.587661E+09 0.340570E+09 0.00 0.00
April 0.712094E+09 0.347261E+09 0.812750E+09 0.440889E+09 0.371861E+09 0.00 0.00
May 0.664593E+09 0.160126E+09 0.705464E+09 0.240460E+09 0.465004E+09 0.00 0.00
June 0.632465E+09 85730311.72 0.612473E+09 0.162475E+09 0.449998E+09 0.00 0.00
July 0.741969E+09 71597111.41 0.691926E+09 0.218364E+09 0.473562E+09 0.00 0.00
August 0.799002E+09 91001458.56 0.739438E+09 0.308833E+09 0.430605E+09 0.00 0.00
September 0.804368E+09 0.187826E+09 0.767424E+09 0.408753E+09 0.358670E+09 0.00 0.00
October 0.655861E+09 0.347562E+09 0.677666E+09 0.398807E+09 0.278859E+09 0.00 0.00
November 0.517465E+09 0.529949E+09 0.584099E+09 0.366737E+09 0.217362E+09 0.00 0.00
December 0.490282E+09 0.854011E+09 0.642424E+09 0.421405E+09 0.221020E+09 0.00 0.00
               
Annual Sum or Average 0.838224E+10 0.481792E+10 0.894572E+10 0.477656E+10 0.416916E+10 0.00 0.00
Minimum of Months 0.490282E+09 71597111.41 0.584099E+09 0.162475E+09 0.217362E+09 0.00 0.00
Maximum of Months 0.866930E+09 0.876339E+09 0.951751E+09 0.643121E+09 0.473562E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 31616719.93 86403663.45 40757572.28 27337234.09 13420338.19 0.00 0.00
February 40119431.09 65869466.05 47316214.80 30780258.90 16535955.90 0.00 0.00
March 36172501.83 58710482.82 46555829.10 27514007.44 19041821.66 0.00 0.00
April 32619419.16 33697086.62 41901726.12 20137316.27 21764409.84 0.00 0.00
May 34091109.84 15695072.38 39242654.21 12130490.57 27112163.65 0.00 0.00
June 34260465.69 8990153.95 34475913.49 7853008.83 26622904.67 0.00 0.00
July 41509296.64 7629303.47 39580632.79 11391369.73 28189263.06 0.00 0.00
August 42801514.87 9982055.71 41179813.47 16085035.59 25094777.88 0.00 0.00
September 37701754.03 19017134.28 39233813.75 18946597.70 20287216.05 0.00 0.00
October 29676613.01 34873389.13 34506839.52 19181267.49 15325572.03 0.00 0.00
November 23716788.35 53001434.66 29305013.64 17708679.71 11596333.92 0.00 0.00
December 22523701.60 84306717.26 31619160.37 19937033.16 11682127.21 0.00 0.00
               
Annual Sum or Average 0.406809E+09 0.478176E+09 0.465675E+09 0.229002E+09 0.236673E+09 0.00 0.00
Minimum of Months 22523701.60 7629303.47 29305013.64 7853008.83 11596333.92 0.00 0.00
Maximum of Months 42801514.87 86403663.45 47316214.80 30780258.90 28189263.06 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 SCRUB

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 SOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.336878E+09 0.651780E+09 0.478318E+09 0.317520E+09 0.160798E+09 0.00 0.00
February 0.467945E+09 0.488738E+09 0.568097E+09 0.366513E+09 0.201584E+09 0.00 0.00
March 0.491032E+09 0.434645E+09 0.599341E+09 0.367246E+09 0.232096E+09 0.00 0.00
April 0.504667E+09 0.248657E+09 0.573896E+09 0.310291E+09 0.263604E+09 0.00 0.00
May 0.565499E+09 0.116324E+09 0.562647E+09 0.226497E+09 0.336150E+09 0.00 0.00
June 0.540638E+09 63154023.87 0.493952E+09 0.165467E+09 0.328485E+09 0.00 0.00
July 0.629698E+09 54272643.41 0.558388E+09 0.212628E+09 0.345760E+09 0.00 0.00
August 0.607276E+09 69613354.15 0.548713E+09 0.241157E+09 0.307556E+09 0.00 0.00
September 0.539178E+09 0.140111E+09 0.518728E+09 0.269263E+09 0.249466E+09 0.00 0.00
October 0.389405E+09 0.257882E+09 0.426091E+09 0.237227E+09 0.188864E+09 0.00 0.00
November 0.269671E+09 0.395284E+09 0.342848E+09 0.202025E+09 0.140822E+09 0.00 0.00
December 0.231072E+09 0.637564E+09 0.368267E+09 0.228537E+09 0.139730E+09 0.00 0.00
               
Annual Sum or Average 0.557296E+10 0.355803E+10 0.603929E+10 0.314437E+10 0.289492E+10 0.00 0.00
Minimum of Months 0.231072E+09 54272643.41 0.342848E+09 0.165467E+09 0.139730E+09 0.00 0.00
Maximum of Months 0.629698E+09 0.651780E+09 0.599341E+09 0.367246E+09 0.345760E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.169608E+09 0.231886E+09 0.208019E+09 0.144763E+09 63255465.77 0.00 0.00
February 0.213228E+09 0.177160E+09 0.237938E+09 0.160780E+09 77157523.13 0.00 0.00
March 0.197760E+09 0.162839E+09 0.232058E+09 0.146915E+09 85142476.22 0.00 0.00
April 0.172871E+09 97396999.28 0.203187E+09 0.110222E+09 92965343.12 0.00 0.00
May 0.158567E+09 48054232.60 0.176366E+09 60115035.59 0.116251E+09 0.00 0.00
June 0.149393E+09 27699356.32 0.153118E+09 40618846.20 0.112500E+09 0.00 0.00
July 0.176623E+09 24302746.96 0.172981E+09 54590944.70 0.118390E+09 0.00 0.00
August 0.192324E+09 30474650.03 0.184859E+09 77208326.48 0.107651E+09 0.00 0.00
September 0.196078E+09 55282620.72 0.191856E+09 0.102188E+09 89667623.89 0.00 0.00
October 0.160068E+09 96784236.62 0.169417E+09 99701737.44 69714834.93 0.00 0.00
November 0.126459E+09 0.143899E+09 0.146025E+09 91684299.18 54340559.53 0.00 0.00
December 0.120084E+09 0.227552E+09 0.160606E+09 0.105351E+09 55254886.48 0.00 0.00
               
Annual Sum or Average 0.203306E+10 0.132333E+10 0.223643E+10 0.119414E+10 0.104229E+10 0.00 0.00
Minimum of Months 0.120084E+09 24302746.96 0.146025E+09 40618846.20 54340559.53 0.00 0.00
Maximum of Months 0.213228E+09 0.231886E+09 0.237938E+09 0.160780E+09 0.118390E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 367841.43 0.100415E+10 0.113194E+09 0.00 0.113194E+09 0.00 0.00
February 7678907.93 0.714518E+09 0.157049E+09 0.00 0.157049E+09 0.00 0.00
March 27699954.03 0.590043E+09 0.213923E+09 0.00 0.213923E+09 0.00 0.00
April 0.126982E+09 0.310441E+09 0.271338E+09 2062368.56 0.269275E+09 0.00 0.00
May 0.348661E+09 0.132598E+09 0.394194E+09 21005127.21 0.373189E+09 0.00 0.00
June 0.450372E+09 72422273.96 0.425653E+09 46491429.50 0.379161E+09 0.00 0.00
July 0.467515E+09 68372363.09 0.420144E+09 35777732.88 0.384367E+09 0.00 0.00
August 0.335674E+09 88205101.00 0.319249E+09 5388720.58 0.313860E+09 0.00 0.00
September 0.190511E+09 0.174024E+09 0.240824E+09 55414.04 0.240769E+09 0.00 0.00
October 60639016.43 0.333643E+09 0.172793E+09 0.00 0.172793E+09 0.00 0.00
November 7047793.95 0.559649E+09 0.110720E+09 0.00 0.110720E+09 0.00 0.00
December 0.00 0.964683E+09 95907331.30 0.00 95907331.30 0.00 0.00
               
Annual Sum or Average 0.202315E+10 0.501275E+10 0.293499E+10 0.110781E+09 0.282421E+10 0.00 0.00
Minimum of Months 0.00 68372363.09 95907331.30 0.00 95907331.30 0.00 0.00
Maximum of Months 0.467515E+09 0.100415E+10 0.425653E+09 46491429.50 0.384367E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 21555996.54 0.342936E+09 88206193.26 36801681.69 51404511.58 0.00 0.00
February 55212141.44 0.242355E+09 0.125215E+09 53396941.81 71817714.90 0.00 0.00
March 0.125159E+09 0.205798E+09 0.188971E+09 94811562.85 94159803.80 0.00 0.00
April 0.225227E+09 0.114468E+09 0.253547E+09 0.136797E+09 0.116750E+09 0.00 0.00
May 0.298074E+09 56227895.41 0.283502E+09 0.124652E+09 0.158851E+09 0.00 0.00
June 0.359021E+09 34224291.23 0.310603E+09 0.148606E+09 0.161997E+09 0.00 0.00
July 0.371855E+09 31825886.01 0.314416E+09 0.147657E+09 0.166760E+09 0.00 0.00
August 0.272813E+09 40398677.07 0.242426E+09 0.105985E+09 0.136441E+09 0.00 0.00
September 0.183853E+09 70183879.02 0.187893E+09 84128237.32 0.103765E+09 0.00 0.00
October 78104436.22 0.124941E+09 0.117537E+09 44572020.56 72964668.94 0.00 0.00
November 24337395.50 0.199151E+09 72390042.99 24189197.99 48200845.00 0.00 0.00
December 13006522.83 0.335723E+09 68249536.08 25210225.35 43039310.73 0.00 0.00
               
Annual Sum or Average 0.202822E+10 0.179823E+10 0.225296E+10 0.102681E+10 0.122615E+10 0.00 0.00
Minimum of Months 13006522.83 31825886.01 68249536.08 24189197.99 43039310.73 0.00 0.00
Maximum of Months 0.371855E+09 0.342936E+09 0.314416E+09 0.148606E+09 0.166760E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 16305345.52 0.255237E+09 65531766.75 27601261.26 37930505.49 0.00 0.00
February 41546918.15 0.179720E+09 93085187.80 40047706.36 53037481.45 0.00 0.00
March 94040533.43 0.152394E+09 0.140649E+09 71108672.13 69540600.64 0.00 0.00
April 0.169253E+09 84169099.79 0.188884E+09 0.102597E+09 86286145.54 0.00 0.00
May 0.223301E+09 41106898.46 0.210822E+09 93488700.05 0.117333E+09 0.00 0.00
June 0.268872E+09 25112795.53 0.231210E+09 0.111454E+09 0.119755E+09 0.00 0.00
July 0.277782E+09 23586016.38 0.234054E+09 0.110742E+09 0.123312E+09 0.00 0.00
August 0.204063E+09 29434419.32 0.180273E+09 79488612.79 0.100785E+09 0.00 0.00
September 0.137426E+09 51797809.71 0.139673E+09 63096177.99 76576459.30 0.00 0.00
October 58419467.58 92361271.51 87194180.13 33429015.42 53765164.71 0.00 0.00
November 18269584.80 0.147365E+09 53665040.71 18141898.49 35523142.21 0.00 0.00
December 9846695.92 0.249590E+09 50643488.89 18907669.02 31735819.88 0.00 0.00
               
Annual Sum or Average 0.151913E+10 0.133187E+10 0.167568E+10 0.770104E+09 0.905580E+09 0.00 0.00
Minimum of Months 9846695.92 23586016.38 50643488.89 18141898.49 31735819.88 0.00 0.00
Maximum of Months 0.277782E+09 0.255237E+09 0.234054E+09 0.111454E+09 0.123312E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.491903E+09 0.895629E+09 0.690211E+09 0.461892E+09 0.228320E+09 0.00 0.00
February 0.658069E+09 0.675559E+09 0.807724E+09 0.522389E+09 0.285336E+09 0.00 0.00
March 0.660678E+09 0.611368E+09 0.837901E+09 0.511854E+09 0.326047E+09 0.00 0.00
April 0.661792E+09 0.358691E+09 0.799722E+09 0.433264E+09 0.366459E+09 0.00 0.00
May 0.679670E+09 0.176183E+09 0.741725E+09 0.273834E+09 0.467891E+09 0.00 0.00
June 0.704986E+09 0.103453E+09 0.692307E+09 0.233311E+09 0.458996E+09 0.00 0.00
July 0.800720E+09 89575344.80 0.754756E+09 0.274515E+09 0.480241E+09 0.00 0.00
August 0.772958E+09 0.113538E+09 0.736398E+09 0.311114E+09 0.425284E+09 0.00 0.00
September 0.713374E+09 0.210086E+09 0.716488E+09 0.369661E+09 0.346826E+09 0.00 0.00
October 0.530065E+09 0.369572E+09 0.596402E+09 0.332534E+09 0.263868E+09 0.00 0.00
November 0.384867E+09 0.546968E+09 0.492367E+09 0.293195E+09 0.199172E+09 0.00 0.00
December 0.344739E+09 0.874995E+09 0.533005E+09 0.334961E+09 0.198044E+09 0.00 0.00
               
Annual Sum or Average 0.740382E+10 0.502562E+10 0.839901E+10 0.435252E+10 0.404649E+10 0.00 0.00
Minimum of Months 0.344739E+09 89575344.80 0.492367E+09 0.233311E+09 0.198044E+09 0.00 0.00
Maximum of Months 0.800720E+09 0.895629E+09 0.837901E+09 0.522389E+09 0.480241E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.156261E+09 0.922836E+09 0.393014E+09 0.228743E+09 0.164271E+09 0.00 0.00
February 0.317902E+09 0.685165E+09 0.512042E+09 0.295636E+09 0.216406E+09 0.00 0.00
March 0.460521E+09 0.614068E+09 0.634289E+09 0.367161E+09 0.267128E+09 0.00 0.00
April 0.598933E+09 0.362009E+09 0.694626E+09 0.374266E+09 0.320360E+09 0.00 0.00
May 0.781714E+09 0.178564E+09 0.759916E+09 0.345833E+09 0.414083E+09 0.00 0.00
June 0.756080E+09 0.100975E+09 0.676656E+09 0.266491E+09 0.410165E+09 0.00 0.00
July 0.889490E+09 85673491.45 0.767682E+09 0.335400E+09 0.432281E+09 0.00 0.00
August 0.787867E+09 0.105799E+09 0.701159E+09 0.325209E+09 0.375951E+09 0.00 0.00
September 0.600568E+09 0.202376E+09 0.592883E+09 0.296713E+09 0.296170E+09 0.00 0.00
October 0.342454E+09 0.360739E+09 0.428455E+09 0.213172E+09 0.215283E+09 0.00 0.00
November 0.161642E+09 0.550857E+09 0.296622E+09 0.147655E+09 0.148967E+09 0.00 0.00
December 94077758.37 0.903649E+09 0.300232E+09 0.158854E+09 0.141378E+09 0.00 0.00
               
Annual Sum or Average 0.594751E+10 0.507271E+10 0.675757E+10 0.335513E+10 0.340244E+10 0.00 0.00
Minimum of Months 94077758.37 85673491.45 0.296622E+09 0.147655E+09 0.141378E+09 0.00 0.00
Maximum of Months 0.889490E+09 0.922836E+09 0.767682E+09 0.374266E+09 0.432281E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.283749E+09 0.376302E+09 0.346698E+09 0.241272E+09 0.105426E+09 0.00 0.00
February 0.356629E+09 0.284896E+09 0.396563E+09 0.267967E+09 0.128596E+09 0.00 0.00
March 0.331309E+09 0.261659E+09 0.386763E+09 0.244859E+09 0.141904E+09 0.00 0.00
April 0.290785E+09 0.155846E+09 0.338646E+09 0.183704E+09 0.154942E+09 0.00 0.00
May 0.269679E+09 74345117.49 0.293943E+09 0.100192E+09 0.193752E+09 0.00 0.00
June 0.256777E+09 40567819.20 0.255197E+09 67698076.99 0.187499E+09 0.00 0.00
July 0.304075E+09 33414803.36 0.288302E+09 90984907.83 0.197317E+09 0.00 0.00
August 0.328688E+09 41807238.74 0.308099E+09 0.128681E+09 0.179419E+09 0.00 0.00
September 0.331230E+09 84504935.21 0.319760E+09 0.170314E+09 0.149446E+09 0.00 0.00
October 0.269669E+09 0.152280E+09 0.282361E+09 0.166170E+09 0.116191E+09 0.00 0.00
November 0.212384E+09 0.228417E+09 0.243375E+09 0.152807E+09 90567599.22 0.00 0.00
December 0.201426E+09 0.365762E+09 0.267677E+09 0.175585E+09 92091477.47 0.00 0.00
               
Annual Sum or Average 0.343640E+10 0.209980E+10 0.372738E+10 0.199023E+10 0.173715E+10 0.00 0.00
Minimum of Months 0.201426E+09 33414803.36 0.243375E+09 67698076.99 90567599.22 0.00 0.00
Maximum of Months 0.356629E+09 0.376302E+09 0.396563E+09 0.267967E+09 0.197317E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.453618E+09 0.601845E+09 0.554717E+09 0.386036E+09 0.168681E+09 0.00 0.00
February 0.570166E+09 0.455214E+09 0.634501E+09 0.428747E+09 0.205753E+09 0.00 0.00
March 0.529952E+09 0.417042E+09 0.618820E+09 0.391774E+09 0.227047E+09 0.00 0.00
April 0.465868E+09 0.246753E+09 0.541833E+09 0.293926E+09 0.247908E+09 0.00 0.00
May 0.433458E+09 0.115878E+09 0.470309E+09 0.160307E+09 0.310003E+09 0.00 0.00
June 0.413265E+09 62528657.76 0.408316E+09 0.108317E+09 0.299999E+09 0.00 0.00
July 0.489386E+09 50741702.25 0.461284E+09 0.145576E+09 0.315708E+09 0.00 0.00
August 0.528151E+09 63684997.67 0.492959E+09 0.205889E+09 0.287070E+09 0.00 0.00
September 0.531241E+09 0.132071E+09 0.511616E+09 0.272502E+09 0.239114E+09 0.00 0.00
October 0.432141E+09 0.240987E+09 0.451778E+09 0.265871E+09 0.185906E+09 0.00 0.00
November 0.339882E+09 0.363999E+09 0.389400E+09 0.244491E+09 0.144908E+09 0.00 0.00
December 0.322103E+09 0.584749E+09 0.428283E+09 0.280936E+09 0.147346E+09 0.00 0.00
               
Annual Sum or Average 0.550923E+10 0.333549E+10 0.596381E+10 0.318437E+10 0.277944E+10 0.00 0.00
Minimum of Months 0.322103E+09 50741702.25 0.389400E+09 0.108317E+09 0.144908E+09 0.00 0.00
Maximum of Months 0.570166E+09 0.601845E+09 0.634501E+09 0.428747E+09 0.315708E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.168341E+09 0.224978E+09 0.208019E+09 0.144763E+09 63255465.77 0.00 0.00
February 0.211271E+09 0.170938E+09 0.237938E+09 0.160780E+09 77157523.13 0.00 0.00
March 0.195985E+09 0.157488E+09 0.232058E+09 0.146915E+09 85142476.22 0.00 0.00
April 0.171553E+09 94044959.59 0.203187E+09 0.110222E+09 92965343.12 0.00 0.00
May 0.158802E+09 45224902.17 0.176366E+09 60115035.59 0.116251E+09 0.00 0.00
June 0.150880E+09 25006124.60 0.153118E+09 40618846.20 0.112500E+09 0.00 0.00
July 0.179052E+09 20826560.19 0.172981E+09 54590944.70 0.118390E+09 0.00 0.00
August 0.193472E+09 26335972.64 0.184859E+09 77208326.48 0.107651E+09 0.00 0.00
September 0.195406E+09 51858486.48 0.191856E+09 0.102188E+09 89667623.89 0.00 0.00
October 0.159288E+09 92224994.21 0.169417E+09 99701737.44 69714834.93 0.00 0.00
November 0.125754E+09 0.136967E+09 0.146025E+09 91684299.18 54340559.53 0.00 0.00
December 0.119516E+09 0.218502E+09 0.160606E+09 0.105351E+09 55254886.48 0.00 0.00
               
Annual Sum or Average 0.202932E+10 0.126440E+10 0.223643E+10 0.119414E+10 0.104229E+10 0.00 0.00
Minimum of Months 0.119516E+09 20826560.19 0.146025E+09 40618846.20 54340559.53 0.00 0.00
Maximum of Months 0.211271E+09 0.224978E+09 0.237938E+09 0.160780E+09 0.118390E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 42522167.46 0.692479E+09 0.174182E+09 73603363.37 0.100579E+09 0.00 0.00
February 0.108051E+09 0.488983E+09 0.247474E+09 0.106794E+09 0.140680E+09 0.00 0.00
March 0.245445E+09 0.418417E+09 0.374082E+09 0.189623E+09 0.184459E+09 0.00 0.00
April 0.441388E+09 0.234348E+09 0.502529E+09 0.273593E+09 0.228935E+09 0.00 0.00
May 0.586831E+09 0.112747E+09 0.560546E+09 0.249303E+09 0.311243E+09 0.00 0.00
June 0.712802E+09 66179909.95 0.614975E+09 0.297212E+09 0.317763E+09 0.00 0.00
July 0.743509E+09 57188281.88 0.622547E+09 0.295313E+09 0.327234E+09 0.00 0.00
August 0.547003E+09 71112440.06 0.479322E+09 0.211970E+09 0.267352E+09 0.00 0.00
September 0.365179E+09 0.134642E+09 0.371323E+09 0.168256E+09 0.203066E+09 0.00 0.00
October 0.153925E+09 0.246270E+09 0.231641E+09 89144041.12 0.142497E+09 0.00 0.00
November 48101349.56 0.396224E+09 0.142532E+09 48378395.98 94154072.37 0.00 0.00
December 25645456.85 0.673723E+09 0.134551E+09 50420450.71 84131018.60 0.00 0.00
               
Annual Sum or Average 0.402040E+10 0.359231E+10 0.445570E+10 0.205361E+10 0.240209E+10 0.00 0.00
Minimum of Months 25645456.85 57188281.88 0.134551E+09 48378395.98 84131018.60 0.00 0.00
Maximum of Months 0.743509E+09 0.692479E+09 0.622547E+09 0.297212E+09 0.327234E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 108705.88 0.528369E+09 56597189.09 0.00 56597189.09 0.00 0.00
February 3094843.19 0.379620E+09 78524315.38 0.00 78524315.38 0.00 0.00
March 11519777.46 0.319054E+09 0.106962E+09 0.00 0.106962E+09 0.00 0.00
April 57695808.78 0.173159E+09 0.135665E+09 1030161.93 0.134635E+09 0.00 0.00
May 0.167786E+09 76468929.79 0.197097E+09 10502563.60 0.186594E+09 0.00 0.00
June 0.221196E+09 42197450.07 0.212826E+09 23245714.75 0.189581E+09 0.00 0.00
July 0.235390E+09 35985336.89 0.210072E+09 17888866.44 0.192183E+09 0.00 0.00
August 0.168989E+09 45889727.90 0.159624E+09 2694360.29 0.156930E+09 0.00 0.00
September 93326156.49 94404495.63 0.120348E+09 21360.89 0.120327E+09 0.00 0.00
October 28334067.58 0.178779E+09 86396382.73 0.00 86396382.73 0.00 0.00
November 3209542.46 0.295603E+09 55360042.13 0.00 55360042.13 0.00 0.00
December 0.00 0.505176E+09 47953665.65 0.00 47953665.65 0.00 0.00
               
Annual Sum or Average 0.990651E+09 0.267471E+10 0.146743E+10 55383027.90 0.141204E+10 0.00 0.00
Minimum of Months 0.00 35985336.89 47953665.65 0.00 47953665.65 0.00 0.00
Maximum of Months 0.235390E+09 0.528369E+09 0.212826E+09 23245714.75 0.192183E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 132012.33 0.713043E+09 75462918.79 0.00 75462918.79 0.00 0.00
February 4024313.93 0.513397E+09 0.104699E+09 0.00 0.104699E+09 0.00 0.00
March 15256271.49 0.432148E+09 0.142615E+09 0.00 0.142615E+09 0.00 0.00
April 77055383.59 0.234742E+09 0.180634E+09 1294764.56 0.179340E+09 0.00 0.00
May 0.226011E+09 0.102338E+09 0.262796E+09 14003418.14 0.248793E+09 0.00 0.00
June 0.298807E+09 55702412.51 0.283768E+09 30994286.33 0.252774E+09 0.00 0.00
July 0.318538E+09 46609030.63 0.280096E+09 23851820.68 0.256244E+09 0.00 0.00
August 0.228858E+09 59756362.13 0.212832E+09 3592429.93 0.209240E+09 0.00 0.00
September 0.125971E+09 0.126045E+09 0.160407E+09 16477.53 0.160390E+09 0.00 0.00
October 38071960.28 0.240952E+09 0.115195E+09 0.00 0.115195E+09 0.00 0.00
November 4292157.67 0.399671E+09 73813389.50 0.00 73813389.50 0.00 0.00
December 0.00 0.682403E+09 63938220.87 0.00 63938220.87 0.00 0.00
               
Annual Sum or Average 0.133702E+10 0.360681E+10 0.195626E+10 73753197.18 0.188251E+10 0.00 0.00
Minimum of Months 0.00 46609030.63 63938220.87 0.00 63938220.87 0.00 0.00
Maximum of Months 0.318538E+09 0.713043E+09 0.283768E+09 30994286.33 0.256244E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 131891.14 0.709032E+09 75462918.79 0.00 75462918.79 0.00 0.00
February 3932452.55 0.510935E+09 0.104699E+09 0.00 0.104699E+09 0.00 0.00
March 14754774.29 0.431410E+09 0.142615E+09 0.00 0.142615E+09 0.00 0.00
April 74804680.57 0.237242E+09 0.180105E+09 1095381.27 0.179010E+09 0.00 0.00
May 0.220127E+09 0.105822E+09 0.262549E+09 13863245.77 0.248686E+09 0.00 0.00
June 0.291404E+09 59018158.01 0.283768E+09 30993842.73 0.252774E+09 0.00 0.00
July 0.310873E+09 50190552.93 0.280056E+09 23839318.69 0.256217E+09 0.00 0.00
August 0.221985E+09 64200132.94 0.212072E+09 3284993.65 0.208787E+09 0.00 0.00
September 0.122201E+09 0.130372E+09 0.160407E+09 16477.53 0.160390E+09 0.00 0.00
October 36371476.93 0.244486E+09 0.115195E+09 0.00 0.115195E+09 0.00 0.00
November 4059674.85 0.400580E+09 73813389.50 0.00 73813389.50 0.00 0.00
December 0.00 0.679019E+09 63938220.87 0.00 63938220.87 0.00 0.00
               
Annual Sum or Average 0.130064E+10 0.362231E+10 0.195468E+10 73093259.63 0.188159E+10 0.00 0.00
Minimum of Months 0.00 50190552.93 63938220.87 0.00 63938220.87 0.00 0.00
Maximum of Months 0.310873E+09 0.709032E+09 0.283768E+09 30993842.73 0.256217E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 58203.80 0.357565E+09 37275524.39 0.00 37275524.39 0.00 0.00
February 1848554.52 0.258060E+09 51727473.56 0.00 51727473.56 0.00 0.00
March 7070974.32 0.217950E+09 70478984.28 0.00 70478984.28 0.00 0.00
April 36794104.01 0.119801E+09 88658776.45 349527.55 88309248.90 0.00 0.00
May 0.107999E+09 52884641.41 0.127762E+09 5618087.37 0.122144E+09 0.00 0.00
June 0.144032E+09 29116379.25 0.138584E+09 14481153.02 0.124103E+09 0.00 0.00
July 0.153512E+09 24644405.52 0.136459E+09 10725090.88 0.125734E+09 0.00 0.00
August 0.109897E+09 31745059.88 0.103931E+09 1177653.96 0.102753E+09 0.00 0.00
September 60637381.73 65258666.36 79266736.76 8238.77 79258497.99 0.00 0.00
October 17779560.88 0.123065E+09 56912200.71 0.00 56912200.71 0.00 0.00
November 1964022.09 0.202167E+09 36456822.10 0.00 36456822.10 0.00 0.00
December 0.00 0.342477E+09 31582148.99 0.00 31582148.99 0.00 0.00
               
Annual Sum or Average 0.641593E+09 0.182473E+10 0.959095E+09 32359751.54 0.926735E+09 0.00 0.00
Minimum of Months 0.00 24644405.52 31582148.99 0.00 31582148.99 0.00 0.00
Maximum of Months 0.153512E+09 0.357565E+09 0.138584E+09 14481153.02 0.125734E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 63761406.75 0.104092E+10 0.264619E+09 0.110405E+09 0.154214E+09 0.00 0.00
February 0.162559E+09 0.741253E+09 0.375644E+09 0.160191E+09 0.215453E+09 0.00 0.00
March 0.366549E+09 0.643727E+09 0.566914E+09 0.284435E+09 0.282479E+09 0.00 0.00
April 0.657201E+09 0.370105E+09 0.760640E+09 0.410390E+09 0.350250E+09 0.00 0.00
May 0.870214E+09 0.188729E+09 0.850507E+09 0.373955E+09 0.476552E+09 0.00 0.00
June 0.105560E+10 0.117373E+09 0.931809E+09 0.445818E+09 0.485991E+09 0.00 0.00
July 0.110040E+10 0.105562E+09 0.943249E+09 0.442970E+09 0.500279E+09 0.00 0.00
August 0.807997E+09 0.129802E+09 0.727278E+09 0.317954E+09 0.409323E+09 0.00 0.00
September 0.541104E+09 0.222887E+09 0.563679E+09 0.252385E+09 0.311294E+09 0.00 0.00
October 0.227975E+09 0.388677E+09 0.352610E+09 0.133716E+09 0.218894E+09 0.00 0.00
November 71119920.68 0.607071E+09 0.217170E+09 72567593.97 0.144603E+09 0.00 0.00
December 38458372.93 0.101438E+10 0.204749E+09 75630676.06 0.129118E+09 0.00 0.00
               
Annual Sum or Average 0.596294E+10 0.557048E+10 0.675887E+10 0.308042E+10 0.367845E+10 0.00 0.00
Minimum of Months 38458372.93 0.105562E+09 0.204749E+09 72567593.97 0.129118E+09 0.00 0.00
Maximum of Months 0.110040E+10 0.104092E+10 0.943249E+09 0.445818E+09 0.500279E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.655551E+09 0.177164E+10 0.103164E+10 0.663630E+09 0.368013E+09 0.00 0.00
February 0.951229E+09 0.136311E+10 0.122721E+10 0.765825E+09 0.461387E+09 0.00 0.00
March 0.106579E+10 0.122400E+10 0.136401E+10 0.812815E+09 0.551192E+09 0.00 0.00
April 0.116281E+10 0.731616E+09 0.138439E+10 0.741740E+09 0.642654E+09 0.00 0.00
May 0.135554E+10 0.376938E+09 0.141778E+10 0.588104E+09 0.829676E+09 0.00 0.00
June 0.131753E+10 0.224603E+09 0.127271E+10 0.453580E+09 0.819130E+09 0.00 0.00
July 0.153731E+10 0.200821E+09 0.142419E+10 0.565809E+09 0.858378E+09 0.00 0.00
August 0.143974E+10 0.248325E+09 0.135093E+10 0.597555E+09 0.753374E+09 0.00 0.00
September 0.122126E+10 0.438181E+09 0.122139E+10 0.619824E+09 0.601566E+09 0.00 0.00
October 0.818165E+09 0.753418E+09 0.951652E+09 0.506157E+09 0.445495E+09 0.00 0.00
November 0.535132E+09 0.109943E+10 0.746221E+09 0.421392E+09 0.324829E+09 0.00 0.00
December 0.444494E+09 0.172374E+10 0.801091E+09 0.478848E+09 0.322243E+09 0.00 0.00
               
Annual Sum or Average 0.125046E+11 0.101558E+11 0.141932E+11 0.721528E+10 0.697794E+10 0.00 0.00
Minimum of Months 0.444494E+09 0.200821E+09 0.746221E+09 0.421392E+09 0.322243E+09 0.00 0.00
Maximum of Months 0.153731E+10 0.177164E+10 0.142419E+10 0.812815E+09 0.858378E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 15695623.26 0.261847E+09 66154644.95 27601261.26 38553383.68 0.00 0.00
February 40319702.12 0.185554E+09 93910992.53 40047706.36 53863286.17 0.00 0.00
March 91512424.13 0.160276E+09 0.141729E+09 71108672.13 70619852.85 0.00 0.00
April 0.164282E+09 91229133.92 0.190160E+09 0.102597E+09 87562509.23 0.00 0.00
May 0.217921E+09 45675546.77 0.212627E+09 93488700.05 0.119138E+09 0.00 0.00
June 0.264372E+09 27900254.05 0.232952E+09 0.111454E+09 0.121498E+09 0.00 0.00
July 0.275764E+09 24827409.03 0.235812E+09 0.110742E+09 0.125070E+09 0.00 0.00
August 0.202475E+09 30585642.87 0.181819E+09 79488612.79 0.102331E+09 0.00 0.00
September 0.135861E+09 53695151.39 0.140920E+09 63096177.99 77823577.19 0.00 0.00
October 57253308.18 95360256.95 88152517.12 33429015.42 54723501.70 0.00 0.00
November 17740230.80 0.151142E+09 54292532.24 18141898.49 36150633.75 0.00 0.00
December 9484228.50 0.255056E+09 51187152.06 18907669.02 32279483.05 0.00 0.00
               
Annual Sum or Average 0.149268E+10 0.138315E+10 0.168972E+10 0.770104E+09 0.919612E+09 0.00 0.00
Minimum of Months 9484228.50 24827409.03 51187152.06 18141898.49 32279483.05 0.00 0.00
Maximum of Months 0.275764E+09 0.261847E+09 0.235812E+09 0.111454E+09 0.125070E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 16554.76 0.741271E+09 69838089.22 0.00 69838089.22 0.00 0.00
February 2096295.82 0.544026E+09 97230191.31 0.00 97230191.31 0.00 0.00
March 9356871.77 0.467305E+09 0.132844E+09 0.00 0.132844E+09 0.00 0.00
April 59109066.16 0.264799E+09 0.167742E+09 699055.10 0.167043E+09 0.00 0.00
May 0.182491E+09 0.127312E+09 0.234507E+09 6377424.85 0.228130E+09 0.00 0.00
June 0.241259E+09 74370426.08 0.250348E+09 19859242.86 0.230489E+09 0.00 0.00
July 0.260962E+09 66950846.74 0.248981E+09 14136772.46 0.234844E+09 0.00 0.00
August 0.189680E+09 85883488.56 0.194911E+09 1594309.97 0.193317E+09 0.00 0.00
September 0.100662E+09 0.154480E+09 0.149129E+09 16477.53 0.149113E+09 0.00 0.00
October 24978577.41 0.275230E+09 0.106552E+09 0.00 0.106552E+09 0.00 0.00
November 2630653.86 0.435834E+09 68153101.61 0.00 68153101.61 0.00 0.00
December 0.00 0.713433E+09 59035954.07 0.00 59035954.07 0.00 0.00
               
Annual Sum or Average 0.107324E+10 0.395089E+10 0.177927E+10 42683282.77 0.173659E+10 0.00 0.00
Minimum of Months 0.00 66950846.74 59035954.07 0.00 59035954.07 0.00 0.00
Maximum of Months 0.260962E+09 0.741271E+09 0.250348E+09 19859242.86 0.234844E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 2 X-RAY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 LOCKER

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 83803.52 0.722063E+09 75462918.79 0.00 75462918.79 0.00 0.00
February 3291181.63 0.525257E+09 0.104699E+09 0.00 0.104699E+09 0.00 0.00
March 12728046.42 0.450037E+09 0.142615E+09 0.00 0.142615E+09 0.00 0.00
April 68599695.46 0.254488E+09 0.180892E+09 1374912.37 0.179517E+09 0.00 0.00
May 0.207552E+09 0.120868E+09 0.262796E+09 14003418.14 0.248793E+09 0.00 0.00
June 0.275762E+09 71360977.87 0.283768E+09 30994286.33 0.252774E+09 0.00 0.00
July 0.293802E+09 63583848.21 0.280096E+09 23851821.92 0.256244E+09 0.00 0.00
August 0.210685E+09 80602481.39 0.212833E+09 3592480.39 0.209240E+09 0.00 0.00
September 0.114415E+09 0.147701E+09 0.160503E+09 28871.89 0.160474E+09 0.00 0.00
October 32346838.05 0.263388E+09 0.115195E+09 0.00 0.115195E+09 0.00 0.00
November 3582179.01 0.418688E+09 73813389.50 0.00 73813389.50 0.00 0.00
December 0.00 0.692862E+09 63938220.87 0.00 63938220.87 0.00 0.00
               
Annual Sum or Average 0.122285E+10 0.381090E+10 0.195661E+10 73845791.04 0.188277E+10 0.00 0.00
Minimum of Months 0.00 63583848.21 63938220.87 0.00 63938220.87 0.00 0.00
Maximum of Months 0.293802E+09 0.722063E+09 0.283768E+09 30994286.33 0.256244E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 102219.92 0.532794E+09 56597189.09 0.00 56597189.09 0.00 0.00
February 2619324.40 0.383290E+09 78524315.38 0.00 78524315.38 0.00 0.00
March 9817899.07 0.323642E+09 0.106962E+09 0.00 0.106962E+09 0.00 0.00
April 52795929.94 0.176204E+09 0.135669E+09 1031184.28 0.134638E+09 0.00 0.00
May 0.158885E+09 78528497.79 0.197097E+09 10502563.60 0.186594E+09 0.00 0.00
June 0.211659E+09 43689020.81 0.212826E+09 23245714.75 0.189581E+09 0.00 0.00
July 0.226088E+09 37169792.33 0.210072E+09 17888866.44 0.192183E+09 0.00 0.00
August 0.161029E+09 47518772.28 0.159624E+09 2694360.29 0.156930E+09 0.00 0.00
September 87709399.16 96506837.27 0.120343E+09 15517.43 0.120328E+09 0.00 0.00
October 25150004.01 0.182079E+09 86396382.73 0.00 86396382.73 0.00 0.00
November 2625930.73 0.299717E+09 55360042.13 0.00 55360042.13 0.00 0.00
December 0.00 0.509189E+09 47953665.65 0.00 47953665.65 0.00 0.00
               
Annual Sum or Average 0.938482E+09 0.271033E+10 0.146743E+10 55378206.79 0.141205E+10 0.00 0.00
Minimum of Months 0.00 37169792.33 47953665.65 0.00 47953665.65 0.00 0.00
Maximum of Months 0.226088E+09 0.532794E+09 0.212826E+09 23245714.75 0.192183E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 40542130.16 0.765947E+09 0.174909E+09 73603363.37 0.101305E+09 0.00 0.00
February 0.102320E+09 0.552785E+09 0.248384E+09 0.106794E+09 0.141590E+09 0.00 0.00
March 0.237001E+09 0.482924E+09 0.375224E+09 0.189623E+09 0.185601E+09 0.00 0.00
April 0.425370E+09 0.291445E+09 0.503833E+09 0.273593E+09 0.230240E+09 0.00 0.00
May 0.562064E+09 0.156497E+09 0.562506E+09 0.249303E+09 0.313203E+09 0.00 0.00
June 0.686991E+09 0.101710E+09 0.616742E+09 0.297212E+09 0.319530E+09 0.00 0.00
July 0.715854E+09 93958641.64 0.624270E+09 0.295313E+09 0.328956E+09 0.00 0.00
August 0.527860E+09 0.113283E+09 0.480916E+09 0.211970E+09 0.268947E+09 0.00 0.00
September 0.348698E+09 0.185309E+09 0.372706E+09 0.168256E+09 0.204449E+09 0.00 0.00
October 0.143648E+09 0.311821E+09 0.232807E+09 89144041.12 0.143663E+09 0.00 0.00
November 44969269.78 0.469408E+09 0.143293E+09 48378395.98 94914485.78 0.00 0.00
December 23999695.67 0.749988E+09 0.135219E+09 50420450.71 84798332.90 0.00 0.00
               
Annual Sum or Average 0.385932E+10 0.427508E+10 0.447081E+10 0.205361E+10 0.241720E+10 0.00 0.00
Minimum of Months 23999695.67 93958641.64 0.135219E+09 48378395.98 84798332.90 0.00 0.00
Maximum of Months 0.715854E+09 0.765947E+09 0.624270E+09 0.297212E+09 0.328956E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 366164.04 0.250006E+10 0.260388E+09 0.00 0.260388E+09 0.00 0.00
February 11450659.05 0.181737E+10 0.361310E+09 0.00 0.361310E+09 0.00 0.00
March 41056732.07 0.155928E+10 0.492271E+09 0.00 0.492271E+09 0.00 0.00
April 0.228934E+09 0.882161E+09 0.621955E+09 3563355.12 0.618391E+09 0.00 0.00
May 0.696725E+09 0.418719E+09 0.897521E+09 41949562.37 0.855571E+09 0.00 0.00
June 0.927306E+09 0.247128E+09 0.967597E+09 99235461.96 0.868361E+09 0.00 0.00
July 0.991233E+09 0.221150E+09 0.956140E+09 75266337.01 0.880874E+09 0.00 0.00
August 0.709378E+09 0.280539E+09 0.730519E+09 10276102.61 0.720243E+09 0.00 0.00
September 0.383831E+09 0.512767E+09 0.553738E+09 60725.05 0.553678E+09 0.00 0.00
October 0.105267E+09 0.913225E+09 0.397615E+09 0.00 0.397615E+09 0.00 0.00
November 11223858.28 0.145023E+10 0.254689E+09 0.00 0.254689E+09 0.00 0.00
December 0.00 0.240119E+10 0.220645E+09 0.00 0.220645E+09 0.00 0.00
               
Annual Sum or Average 0.410677E+10 0.132038E+11 0.671439E+10 0.230352E+09 0.648404E+10 0.00 0.00
Minimum of Months 0.00 0.221150E+09 0.220645E+09 0.00 0.220645E+09 0.00 0.00
Maximum of Months 0.991233E+09 0.250006E+10 0.967597E+09 99235461.96 0.880874E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.164467E+10 0.285533E+10 0.227865E+10 0.153044E+10 0.748215E+09 0.00 0.00
February 0.218234E+10 0.213787E+10 0.266111E+10 0.172795E+10 0.933165E+09 0.00 0.00
March 0.217720E+10 0.191445E+10 0.274576E+10 0.168248E+10 0.106328E+10 0.00 0.00
April 0.216170E+10 0.110185E+10 0.260235E+10 0.141001E+10 0.119234E+10 0.00 0.00
May 0.221668E+10 0.511026E+09 0.240154E+10 0.881616E+09 0.151992E+10 0.00 0.00
June 0.229893E+10 0.280090E+09 0.223004E+10 0.740552E+09 0.148949E+10 0.00 0.00
July 0.261995E+10 0.229841E+09 0.243725E+10 0.878137E+09 0.155911E+10 0.00 0.00
August 0.254364E+10 0.290314E+09 0.239405E+10 0.101055E+10 0.138350E+10 0.00 0.00
September 0.235088E+10 0.606586E+09 0.234132E+10 0.121117E+10 0.113015E+10 0.00 0.00
October 0.175824E+10 0.112505E+10 0.195862E+10 0.109730E+10 0.861319E+09 0.00 0.00
November 0.128418E+10 0.171508E+10 0.162313E+10 0.971269E+09 0.651857E+09 0.00 0.00
December 0.115465E+10 0.278304E+10 0.175962E+10 0.111023E+10 0.649387E+09 0.00 0.00
               
Annual Sum or Average 0.243930E+11 0.155505E+11 0.274335E+11 0.142517E+11 0.131817E+11 0.00 0.00
Minimum of Months 0.115465E+10 0.229841E+09 0.162313E+10 0.740552E+09 0.649387E+09 0.00 0.00
Maximum of Months 0.261995E+10 0.285533E+10 0.274576E+10 0.172795E+10 0.155911E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.112616E+10 0.259736E+10 0.174475E+10 0.113931E+10 0.605441E+09 0.00 0.00
February 0.161206E+10 0.196068E+10 0.209123E+10 0.132775E+10 0.763480E+09 0.00 0.00
March 0.173530E+10 0.179421E+10 0.224648E+10 0.135877E+10 0.887708E+09 0.00 0.00
April 0.181047E+10 0.108912E+10 0.218375E+10 0.116950E+10 0.101425E+10 0.00 0.00
May 0.205233E+10 0.566424E+09 0.217538E+10 0.877704E+09 0.129767E+10 0.00 0.00
June 0.197555E+10 0.336189E+09 0.193225E+10 0.658572E+09 0.127367E+10 0.00 0.00
July 0.232285E+10 0.293975E+09 0.217363E+10 0.836268E+09 0.133736E+10 0.00 0.00
August 0.222263E+10 0.359428E+09 0.210551E+10 0.920840E+09 0.118467E+10 0.00 0.00
September 0.194718E+10 0.640752E+09 0.196648E+10 0.100711E+10 0.959371E+09 0.00 0.00
October 0.136916E+10 0.109236E+10 0.159183E+10 0.868118E+09 0.723708E+09 0.00 0.00
November 0.915177E+09 0.160484E+10 0.125942E+10 0.725746E+09 0.533670E+09 0.00 0.00
December 0.765372E+09 0.254027E+10 0.134355E+10 0.817713E+09 0.525839E+09 0.00 0.00
               
Annual Sum or Average 0.198542E+11 0.148756E+11 0.228142E+11 0.117074E+11 0.111068E+11 0.00 0.00
Minimum of Months 0.765372E+09 0.293975E+09 0.125942E+10 0.658572E+09 0.525839E+09 0.00 0.00
Maximum of Months 0.232285E+10 0.259736E+10 0.224648E+10 0.135877E+10 0.133736E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.606505E+09 0.138455E+10 0.900871E+09 0.589557E+09 0.311314E+09 0.00 0.00
February 0.874141E+09 0.103940E+10 0.109768E+10 0.702719E+09 0.394962E+09 0.00 0.00
March 0.926631E+09 0.940937E+09 0.117986E+10 0.718214E+09 0.461648E+09 0.00 0.00
April 0.948549E+09 0.568534E+09 0.114457E+10 0.616606E+09 0.527968E+09 0.00 0.00
May 0.105560E+10 0.297792E+09 0.113138E+10 0.454739E+09 0.676637E+09 0.00 0.00
June 0.101879E+10 0.177520E+09 0.100837E+10 0.344155E+09 0.664215E+09 0.00 0.00
July 0.119219E+10 0.159675E+09 0.112988E+10 0.433663E+09 0.696213E+09 0.00 0.00
August 0.114885E+10 0.195655E+09 0.109758E+10 0.480795E+09 0.616786E+09 0.00 0.00
September 0.102062E+10 0.341555E+09 0.103106E+10 0.531697E+09 0.499365E+09 0.00 0.00
October 0.728665E+09 0.577323E+09 0.833902E+09 0.458436E+09 0.375466E+09 0.00 0.00
November 0.493302E+09 0.846338E+09 0.657853E+09 0.382254E+09 0.275599E+09 0.00 0.00
December 0.410127E+09 0.134850E+10 0.690058E+09 0.419232E+09 0.270826E+09 0.00 0.00
               
Annual Sum or Average 0.104240E+11 0.787778E+10 0.119031E+11 0.613207E+10 0.577100E+10 0.00 0.00
Minimum of Months 0.410127E+09 0.159675E+09 0.657853E+09 0.344155E+09 0.270826E+09 0.00 0.00
Maximum of Months 0.119219E+10 0.138455E+10 0.117986E+10 0.718214E+09 0.696213E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FLOOR 3 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 63659875.40 0.103635E+10 0.264619E+09 0.110405E+09 0.154214E+09 0.00 0.00
February 0.161132E+09 0.737255E+09 0.375644E+09 0.160191E+09 0.215453E+09 0.00 0.00
March 0.363707E+09 0.642760E+09 0.566914E+09 0.284435E+09 0.282479E+09 0.00 0.00
April 0.650949E+09 0.371680E+09 0.760640E+09 0.410390E+09 0.350250E+09 0.00 0.00
May 0.860064E+09 0.192326E+09 0.850507E+09 0.373955E+09 0.476552E+09 0.00 0.00
June 0.104544E+10 0.120396E+09 0.931809E+09 0.445818E+09 0.485991E+09 0.00 0.00
July 0.109057E+10 0.107953E+09 0.943249E+09 0.442970E+09 0.500279E+09 0.00 0.00
August 0.800738E+09 0.131609E+09 0.727278E+09 0.317954E+09 0.409323E+09 0.00 0.00
September 0.534811E+09 0.225075E+09 0.563679E+09 0.252385E+09 0.311294E+09 0.00 0.00
October 0.223918E+09 0.390455E+09 0.352610E+09 0.133716E+09 0.218894E+09 0.00 0.00
November 70312867.47 0.605081E+09 0.217170E+09 72567593.97 0.144603E+09 0.00 0.00
December 38348843.70 0.100894E+10 0.204749E+09 75630676.06 0.129118E+09 0.00 0.00
               
Annual Sum or Average 0.590365E+10 0.556988E+10 0.675887E+10 0.308042E+10 0.367845E+10 0.00 0.00
Minimum of Months 38348843.70 0.107953E+09 0.204749E+09 72567593.97 0.129118E+09 0.00 0.00
Maximum of Months 0.109057E+10 0.103635E+10 0.943249E+09 0.445818E+09 0.500279E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: NE STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 421947.31 0.146139E+10 0.174783E+09 9200420.42 0.165582E+09 0.00 0.00
February 9445165.42 0.103157E+10 0.243207E+09 13349235.45 0.229857E+09 0.00 0.00
March 40352807.43 0.844487E+09 0.335886E+09 23702890.71 0.312183E+09 0.00 0.00
April 0.192329E+09 0.445551E+09 0.429498E+09 36981875.93 0.392516E+09 0.00 0.00
May 0.500005E+09 0.210302E+09 0.602755E+09 59504737.14 0.543250E+09 0.00 0.00
June 0.644538E+09 0.128549E+09 0.651976E+09 99881541.01 0.552095E+09 0.00 0.00
July 0.671197E+09 0.124912E+09 0.645497E+09 85188399.65 0.560309E+09 0.00 0.00
August 0.479272E+09 0.156267E+09 0.491363E+09 33767107.19 0.457596E+09 0.00 0.00
September 0.268556E+09 0.277069E+09 0.371830E+09 21099103.84 0.350731E+09 0.00 0.00
October 81536520.15 0.494172E+09 0.262530E+09 11143005.14 0.251387E+09 0.00 0.00
November 8659846.51 0.814073E+09 0.167490E+09 6047299.50 0.161443E+09 0.00 0.00
December 0.00 0.140205E+10 0.146468E+09 6302556.34 0.140166E+09 0.00 0.00
               
Annual Sum or Average 0.289631E+10 0.739039E+10 0.452328E+10 0.406168E+09 0.411711E+10 0.00 0.00
Minimum of Months 0.00 0.124912E+09 0.146468E+09 6047299.50 0.140166E+09 0.00 0.00
Maximum of Months 0.671197E+09 0.146139E+10 0.651976E+09 99881541.01 0.560309E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: NW ELEVATOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: NW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 389925.74 0.136694E+10 0.150926E+09 0.00 0.150926E+09 0.00 0.00
February 8616390.94 0.975128E+09 0.209398E+09 0.00 0.209398E+09 0.00 0.00
March 31824357.39 0.809316E+09 0.285231E+09 0.00 0.285231E+09 0.00 0.00
April 0.153660E+09 0.433816E+09 0.361784E+09 2749824.74 0.359034E+09 0.00 0.00
May 0.424461E+09 0.205718E+09 0.525592E+09 28006836.28 0.497585E+09 0.00 0.00
June 0.547614E+09 0.126564E+09 0.567537E+09 61988572.67 0.505548E+09 0.00 0.00
July 0.569338E+09 0.125041E+09 0.560192E+09 47703643.84 0.512489E+09 0.00 0.00
August 0.405835E+09 0.156276E+09 0.425665E+09 7184960.77 0.418480E+09 0.00 0.00
September 0.225734E+09 0.271724E+09 0.321099E+09 73885.39 0.321025E+09 0.00 0.00
October 69454558.96 0.473263E+09 0.230390E+09 0.00 0.230390E+09 0.00 0.00
November 7751475.94 0.767414E+09 0.147627E+09 0.00 0.147627E+09 0.00 0.00
December 0.00 0.131086E+10 0.127876E+09 0.00 0.127876E+09 0.00 0.00
               
Annual Sum or Average 0.244468E+10 0.702206E+10 0.391332E+10 0.147708E+09 0.376561E+10 0.00 0.00
Minimum of Months 0.00 0.125041E+09 0.127876E+09 0.00 0.127876E+09 0.00 0.00
Maximum of Months 0.569338E+09 0.136694E+10 0.567537E+09 61988572.67 0.512489E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: SW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 85613475.85 0.107785E+09 0.103274E+09 72350150.56 30924146.67 0.00 0.00
February 0.106739E+09 83556009.33 0.115482E+09 78599936.93 36881978.39 0.00 0.00
March 96600825.85 77291910.85 0.109161E+09 68971186.35 40190300.95 0.00 0.00
April 85312033.58 45768733.61 99132157.72 54424258.63 44707899.10 0.00 0.00
May 76031826.50 24049339.80 86175977.59 30053896.50 56122081.09 0.00 0.00
June 70437542.45 14689934.24 74582883.39 20309423.10 54273460.30 0.00 0.00
July 82980569.67 14101143.97 84454167.63 27286660.82 57167506.81 0.00 0.00
August 91388658.37 17337865.17 90361262.02 38446687.57 51914574.45 0.00 0.00
September 93834996.41 29162417.77 92372306.67 49536371.72 42835934.96 0.00 0.00
October 77586332.89 47887193.26 81053482.05 47918598.11 33134883.94 0.00 0.00
November 63368610.02 66863475.94 71914945.22 45565072.56 26349872.66 0.00 0.00
December 60921878.93 0.104921E+09 79742004.34 52675576.32 27066428.02 0.00 0.00
               
Annual Sum or Average 0.990816E+09 0.633415E+09 0.108771E+10 0.586138E+09 0.501569E+09 0.00 0.00
Minimum of Months 60921878.93 14101143.97 71914945.22 20309423.10 26349872.66 0.00 0.00
Maximum of Months 0.106739E+09 0.107785E+09 0.115482E+09 78599936.93 57167506.81 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -16.9 -17.3 -20.0 3.73 -31.9 33.25 98.18 0.00
February -11.6 -12.6 -16.7 4.33 -26.7 48.91 138.70 0.00
March -6.2 -7.5 -10.8 3.55 -19.4 56.69 163.76 0.01
April 3.97 0.48 -4.8 4.72 -9.1 70.41 207.70 0.01
May 13.43 8.45 3.53 3.60 2.20 102.27 202.62 0.00
June 18.03 14.18 11.55 3.74 7.84 104.36 210.60 0.06
July 19.67 16.51 14.78 3.14 8.96 101.67 223.82 0.04
August 17.94 15.19 13.59 3.45 8.98 87.39 175.79 0.04
September 12.29 9.87 7.80 3.78 3.33 70.27 143.96 0.00
October 5.42 3.48 1.07 3.53 -4.7 51.74 90.11 0.00
November -2.0 -3.6 -6.9 4.42 -13.7 34.68 65.95 0.00
December -14.6 -15.1 -18.1 3.91 -28.3 29.58 68.99 0.00
                 
Annual Sum or Average 3.36 1.07 -2.0 3.82 -8.5 66.03 149.18 0.01
Minimum of Months -16.9 -17.3 -20.0 3.14 -31.9 29.58 65.95 0.00
Maximum of Months 19.67 16.51 14.78 4.72 8.98 104.36 223.82 0.06



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.10 29-JAN-14:00 -0.9 -4.4 2.60 -11.4 145.00 110.00
February 8.90 20-FEB-15:00 2.85 -6.7 8.80 -9.0 49.00 646.00
March 11.10 26-MAR-15:00 5.46 -1.1 5.20 -5.7 53.00 842.00
April 26.70 23-APR-15:00 16.93 11.10 11.30 12.03 75.50 811.00
May 29.40 25-MAY-17:00 19.24 13.90 1.50 16.49 47.50 582.00
June 35.00 29-JUN-15:00 24.70 21.10 6.70 24.66 132.00 705.00
July 31.10 15-JUL-14:20 25.34 23.33 8.07 19.92 299.67 518.33
August 30.60 08-AUG-14:00 23.35 20.60 6.70 17.93 163.50 672.50
September 26.10 01-SEP-14:00 17.80 13.30 3.60 14.28 112.00 751.50
October 22.20 19-OCT-14:00 13.60 7.20 6.70 8.15 35.50 701.50
November 18.30 01-NOV-14:00 13.43 10.00 3.10 11.84 105.00 30.50
December 1.10 28-DEC-02:00 0.43 -0.6 4.60 -5.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 1.10   -0.9 -6.7 1.50 -11.4 0.00 0.00
Maximum of Months 35.00   25.34 23.33 11.30 24.66 299.67 842.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -35.6 06-JAN-08:00 -35.7 -37.8 0.00 -57.8 27.00 381.00
February -33.3 14-FEB-06:00 -33.4 -36.7 0.00 -55.6 0.00 0.00
March -28.9 05-MAR-06:00 -29.1 -32.2 1.50 -50.6 27.00 41.50
April -13.9 05-APR-05:00 -14.3 -16.1 0.00 -32.5 14.50 199.00
May -3.9 01-MAY-05:00 -6.0 -12.2 0.00 -22.4 35.00 415.00
June 1.10 04-JUN-04:00 0.61 0.00 0.00 -14.9 37.00 169.50
July 6.10 02-JUL-04:00 6.10 6.10 0.00 -8.8 33.50 204.50
August 4.40 19-AUG-03:00 4.40 4.40 0.00 -10.7 0.00 0.00
September 1.10 06-SEP-03:00 1.10 1.10 0.00 -14.7 0.00 0.00
October -10.0 30-OCT-03:00 -10.6 -12.8 1.50 -28.2 0.00 0.00
November -20.6 29-NOV-05:00 -20.8 -22.2 2.10 -37.8 0.00 0.00
December -31.1 24-DEC-06:19 -31.3 -35.1 3.33 -53.1 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -35.6   -35.7 -37.8 0.00 -57.8 0.00 0.00
Maximum of Months 6.10   6.10 6.10 3.33 -8.8 37.00 415.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -0.4 16-JAN-12:00 0.00 -1.1 5.70 -6.6 172.50 3.00
February 3.33 21-FEB-12:00 6.70 -1.1 7.70 -6.0 270.00 303.00
March 5.46 26-MAR-15:00 11.10 -1.1 5.20 -5.7 53.00 842.00
April 16.93 23-APR-15:00 26.70 11.10 11.30 12.03 75.50 811.00
May 19.90 26-MAY-11:00 25.60 17.20 6.20 22.64 300.50 6.00
June 24.70 29-JUN-15:00 35.00 21.10 6.70 24.66 132.00 705.00
July 25.75 15-JUL-13:00 31.10 23.90 7.70 18.99 333.00 421.00
August 23.35 08-AUG-14:00 30.60 20.60 6.70 17.93 163.50 672.50
September 18.67 01-SEP-00:00 19.00 17.50 2.80 16.30 0.00 0.00
October 13.70 19-OCT-13:00 21.70 7.80 5.70 7.75 54.50 739.00
November 14.29 21-NOV-12:00 15.00 13.90 5.20 11.46 134.50 25.50
December 0.43 28-DEC-02:00 1.10 -0.6 4.60 -5.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -0.4   0.00 -1.1 2.80 -6.6 0.00 0.00
Maximum of Months 25.75   35.00 23.90 11.30 24.66 333.00 842.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -1.1 16-JAN-11:00 -0.6 -0.8 5.70 -7.3 164.50 5.00
February -0.6 21-FEB-08:00 4.40 2.24 8.80 -6.6 123.00 89.50
March 0.00 29-MAR-20:00 1.70 0.95 1.50 -4.8 0.00 0.00
April 11.10 23-APR-13:00 24.40 16.06 10.80 9.72 98.50 903.50
May 17.20 26-MAY-11:00 25.60 19.90 6.20 22.64 300.50 6.00
June 22.80 29-JUN-23:19 26.30 23.71 5.20 14.28 0.00 0.00
July 23.90 15-JUL-13:00 31.10 25.75 7.70 18.99 333.00 421.00
August 20.60 08-AUG-14:00 30.60 23.35 6.70 17.93 163.50 672.50
September 17.92 01-SEP-00:10 19.75 18.15 3.22 13.22 0.00 0.00
October 12.20 07-OCT-12:20 14.47 13.16 3.43 9.18 163.17 18.50
November 13.90 21-NOV-12:00 15.00 14.29 5.20 11.46 134.50 25.50
December -0.0 06-DEC-02:00 0.00 -0.0 3.60 -6.4 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -1.1   -0.6 -0.8 1.50 -7.3 0.00 0.00
Maximum of Months 23.90   31.10 25.75 10.80 22.64 333.00 903.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 1.89 11.66 0.00
February 18.00 13.00 16.00 0.58 19.92 0.00
March 18.00 13.00 16.00 0.81 26.63 0.00
April 18.00 13.00 16.00 2.58 37.52 0.00
May 18.00 13.00 16.00 5.43 45.25 0.00
June 18.00 13.00 16.00 8.61 47.76 0.00
July 18.00 13.00 16.00 11.25 48.86 0.00
August 18.00 13.00 16.00 12.66 38.94 0.00
September 18.00 13.00 16.00 12.41 29.23 0.00
October 18.00 13.00 16.00 10.60 17.37 0.00
November 18.00 13.00 16.00 7.72 10.89 0.00
December 18.00 13.00 16.00 4.55 9.11 0.00
             
Annual Sum or Average 18.00 13.00 16.00 6.63 28.63 0.00
Minimum of Months 18.00 13.00 16.00 0.58 9.11 0.00
Maximum of Months 18.00 13.00 16.00 12.66 48.86 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January -.278252E+10 -.957451E+10 0.00 0.00 744.00 0.00 -.128869E+10 74.39 0.00 0.00
February -.223890E+10 -.891302E+10 0.00 0.00 672.00 0.00 -.115768E+10 74.35 0.00 0.00
March -.172480E+10 -.106198E+11 0.00 0.00 744.00 0.00 -.126058E+10 73.65 0.00 0.00
April -.280817E+10 -.918001E+10 0.00 0.00 720.00 0.00 -.123256E+10 74.59 0.00 0.00
May -.300140E+10 -.941532E+10 0.00 0.00 744.00 0.00 -.126561E+10 74.29 0.00 0.00
June -.321534E+10 -.883573E+10 0.00 0.00 720.00 0.00 -.122829E+10 74.26 0.00 0.00
July -.469900E+10 -.778550E+10 0.00 0.00 744.00 0.00 -.129526E+10 75.39 0.00 0.00
August -.400928E+10 -.849586E+10 0.00 0.00 744.00 0.00 -.127489E+10 74.43 0.00 0.00
September -.448977E+10 -.760888E+10 0.00 0.00 720.00 0.00 -.124631E+10 75.22 0.00 0.00
October -.432979E+10 -.815288E+10 0.00 0.00 744.00 0.00 -.128134E+10 74.96 0.00 0.00
November -.354257E+10 -.849645E+10 0.00 0.00 720.00 0.00 -.123695E+10 74.55 0.00 0.00
December -.354063E+10 -.885532E+10 0.00 0.00 744.00 0.00 -.129843E+10 74.94 0.00 0.00
                     
Annual Sum or Average -.403822E+11 -.105933E+12     8760.00   -.150666E+11 74.59    
Minimum of Months -.469900E+10 -.106198E+11 0.00 0.00 672.00 0.00 -.129843E+10 73.65 0.00 0.00
Maximum of Months -.172480E+10 -.760888E+10 0.00 0.00 744.00 0.00 -.115768E+10 75.39 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: FLOOR 2 RECEPTION_DAYLCTRL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 243.33 0.33 0.23 01-JAN-09:39 729.66 22.96 99.00 192.67 1671.16 28.78 181.00 176.83
February 265.33 0.33 0.23 01-FEB-09:30 600.45 22.04 136.83 208.67 1101.93 25.53 196.00 192.67
March 254.17 0.33 0.23 02-MAR-10:39 872.84 19.69 82.17 246.17 580.89 22.82 214.00 218.17
April 296.33 0.33 0.23 01-APR-10:39 1143.96 18.84 66.67 284.83 611.65 21.83 224.00 251.83
May 437.50 0.33 0.23 01-MAY-08:30 1244.44 20.48 118.83 347.00 417.28 22.19 275.67 300.00
June 401.83 0.33 0.23 01-JUN-07:30 857.89 20.91 115.33 335.33 409.67 22.24 266.00 264.00
July 409.17 0.31 0.23 01-JUL-07:30 951.04 21.01 121.83 345.67 448.04 22.54 285.00 285.83
August 352.83 0.30 0.23 01-AUG-07:00 1250.13 19.95 94.67 306.00 526.04 22.86 259.33 264.50
September 344.17 0.33 0.23 01-SEP-08:30 1174.41 21.17 137.00 273.00 521.13 22.69 230.67 245.67
October 299.00 0.34 0.23 01-OCT-08:09 596.28 21.10 108.67 224.17 440.88 22.99 207.67 198.50
November 255.50 0.37 0.23 01-NOV-09:09 396.18 19.22 50.33 165.33 1190.14 27.47 180.67 161.17
December 226.33 0.33 0.23 01-DEC-08:00 625.88 23.04 80.67 161.50 1157.41 28.08 169.67 149.67
                         
Annual Sum or Average 3785.50 0.33     909.38 20.80 1212.00 3090.33 692.44 23.79 2689.67 2708.83
Minimum of Months 226.33 0.30 0.23   396.18 18.84 50.33 161.50 409.67 21.83 169.67 149.67
Maximum of Months 437.50 0.37 0.23   1250.13 23.04 137.00 347.00 1671.16 28.78 285.00 300.00



Table of Contents

Report: DaylightingReportMonthly

For: FLOOR 3 OFFICE_DAYLCTRL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 243.33 0.77 0.62 29-JAN-12:30 303.78 18.47 2.50 114.17 126.17 20.52 101.83 0.00
February 265.33 0.74 0.62 17-FEB-10:00 374.77 19.55 31.83 163.67 160.53 21.74 175.50 0.00
March 254.17 0.73 0.62 02-MAR-11:30 383.69 19.75 46.00 223.83 175.10 22.22 218.17 1.33
April 296.33 0.71 0.62 01-APR-11:39 421.34 19.92 93.17 272.67 191.99 22.41 299.00 7.67
May 437.50 0.67 0.62 02-MAY-06:49 632.46 22.40 248.67 396.50 244.66 23.81 393.50 64.67
June 401.83 0.65 0.62 01-JUN-04:00 717.06 24.69 341.33 414.50 304.99 25.63 407.17 164.67
July 409.17 0.65 0.62 01-JUL-04:00 744.06 24.17 318.67 417.17 289.52 25.39 413.83 150.83
August 352.83 0.67 0.62 01-AUG-07:00 572.29 21.50 187.33 352.33 244.42 23.83 335.67 45.00
September 344.17 0.71 0.62 02-SEP-09:20 450.09 20.48 93.83 259.83 186.79 22.59 257.33 0.00
October 299.00 0.74 0.62 01-OCT-12:50 381.53 19.66 37.67 189.50 150.80 21.50 174.17 0.00
November 255.50 0.77 0.68 28-NOV-12:30 298.72 18.47 0.00 117.00 118.52 20.12 82.33 0.00
December 226.33 0.78 0.69 01-DEC-10:00 286.19 18.36 0.00 104.33 114.53 20.13 52.17 0.00
                         
Annual Sum or Average 3785.50 0.71     495.85 21.03 1401.00 3025.50 204.61 22.84 2910.67 434.17
Minimum of Months 226.33 0.65 0.62   286.19 18.36 0.00 104.33 114.53 20.12 52.17 0.00
Maximum of Months 437.50 0.78 0.69   744.06 24.69 341.33 417.17 304.99 25.63 413.83 164.67



Table of Contents

Report: DaylightingReportMonthly

For: FLOOR 3 LOUNGE_DAYLCTRL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 243.33 0.61 0.52 02-JAN-12:09 279.38 19.01 6.00 203.67 111.84 20.94 120.17 29.83
February 265.33 0.57 0.52 01-FEB-10:50 345.06 20.02 45.33 238.17 141.63 21.97 185.50 113.17
March 254.17 0.57 0.52 02-MAR-10:39 355.24 20.28 60.83 311.83 152.32 22.30 229.67 143.67
April 296.33 0.56 0.52 01-APR-08:09 391.59 20.44 113.17 353.83 164.93 22.34 298.50 207.33
May 437.50 0.54 0.52 01-MAY-06:19 550.24 21.85 260.67 430.00 212.15 23.58 388.00 331.67
June 401.83 0.54 0.52 01-JUN-04:00 613.66 22.35 308.67 440.17 238.95 24.09 399.33 367.17
July 409.17 0.53 0.52 01-JUL-04:00 601.22 22.31 297.00 440.33 236.95 24.10 404.83 374.83
August 352.83 0.54 0.52 01-AUG-07:40 531.65 21.81 212.83 386.50 210.89 23.60 339.17 303.33
September 344.17 0.56 0.52 01-SEP-07:30 415.17 20.87 109.50 329.33 163.65 22.65 262.33 201.00
October 299.00 0.58 0.52 01-OCT-07:49 350.48 20.08 54.00 275.83 133.75 21.79 189.83 98.33
November 255.50 0.61 0.52 01-NOV-09:09 274.37 18.99 0.50 212.50 105.36 20.60 109.17 11.00
December 226.33 0.62 0.52 01-DEC-09:00 263.00 18.89 0.00 190.17 101.79 20.62 74.83 4.67
                         
Annual Sum or Average 3785.50 0.56     439.59 20.82 1468.50 3812.33 174.04 22.62 3001.33 2186.00
Minimum of Months 226.33 0.53 0.52   263.00 18.89 0.00 190.17 101.79 20.60 74.83 4.67
Maximum of Months 437.50 0.62 0.52   613.66 22.35 308.67 440.33 238.95 24.10 404.83 374.83



Table of Contents

Report: DaylightingReportMonthly

For: FLOOR 2 OFFICE_DAYLCTRL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 243.33 0.22 0.00 01-JAN-08:00 718.62 12.62 0.00 161.00 501.13 12.20 0.00 77.17
February 265.33 0.17 0.00 01-FEB-08:50 1318.00 13.81 0.00 190.33 355.23 13.47 0.00 122.83
March 254.17 0.16 0.00 02-MAR-10:39 2300.93 13.98 0.00 240.33 789.31 13.95 0.00 136.83
April 296.33 0.15 0.00 01-APR-07:30 1774.42 14.12 0.00 277.17 1178.83 14.17 0.00 174.67
May 437.50 0.12 0.00 01-MAY-05:19 1467.56 15.87 0.00 338.33 560.65 15.58 0.00 248.33
June 401.83 0.12 0.00 01-JUN-04:00 843.51 16.38 0.00 357.50 729.47 16.13 0.00 230.33
July 409.17 0.11 0.00 01-JUL-04:00 918.32 16.42 0.00 363.83 672.79 16.26 0.00 244.17
August 352.83 0.11 0.00 01-AUG-07:40 1522.75 15.86 0.00 315.33 557.87 15.60 0.00 195.50
September 344.17 0.14 0.00 01-SEP-06:40 1311.38 14.65 0.00 260.17 740.97 14.28 0.00 163.00
October 299.00 0.18 0.00 01-OCT-06:49 940.92 13.73 0.00 215.17 429.25 13.17 0.00 115.33
November 255.50 0.23 0.00 01-NOV-08:30 544.32 12.46 0.00 160.83 355.26 11.81 0.00 63.50
December 226.33 0.23 0.00 01-DEC-08:39 401.52 12.32 0.00 145.67 298.44 11.72 0.00 46.83
                         
Annual Sum or Average 3785.50 0.15     1186.60 14.64 0.00 3025.67 612.43 14.33 0.00 1818.50
Minimum of Months 226.33 0.11 0.00   401.52 12.32 0.00 145.67 298.44 11.72 0.00 46.83
Maximum of Months 437.50 0.23 0.00   2300.93 16.42 0.00 363.83 1178.83 16.26 0.00 248.33



Table of Contents

Report: DaylightingReportMonthly

For: FLOOR 2 CONFERENCE_DAYLCTRL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 243.33 0.08 0.00 01-JAN-08:50 2682.47 0.00 0.00 196.50 2685.16 0.00 0.00 215.17
February 265.33 0.09 0.00 01-FEB-08:39 1594.48 0.00 0.00 212.83 2036.03 0.00 0.00 233.67
March 254.17 0.09 0.00 02-MAR-10:39 903.81 0.00 0.00 251.17 2121.25 0.00 0.00 276.67
April 296.33 0.12 0.00 01-APR-08:09 672.20 0.00 0.00 266.17 1934.09 0.00 0.00 302.33
May 437.50 0.12 0.00 01-MAY-06:10 549.50 0.00 0.00 309.67 776.35 0.00 0.00 350.67
June 401.83 0.12 0.00 01-JUN-05:30 538.34 0.00 0.00 286.67 762.54 0.00 0.00 353.00
July 409.17 0.11 0.00 01-JUL-05:30 579.58 0.00 0.00 307.50 819.04 0.00 0.00 364.50
August 352.83 0.10 0.00 01-AUG-07:40 664.60 0.00 0.00 275.33 980.71 0.00 0.00 323.50
September 344.17 0.11 0.00 01-SEP-06:40 763.41 0.00 0.00 257.17 1853.33 0.00 0.00 286.67
October 299.00 0.10 0.00 01-OCT-06:49 659.71 0.00 0.00 220.17 1202.71 0.00 0.00 254.83
November 255.50 0.13 0.00 01-NOV-08:20 1810.93 0.00 0.00 174.83 2058.64 0.00 0.00 204.50
December 226.33 0.10 0.00 01-DEC-08:39 1684.03 0.00 0.00 170.33 1892.31 0.00 0.00 190.67
                         
Annual Sum or Average 3785.50 0.11     987.17 0.00 0.00 2928.33 1475.33 0.00 0.00 3356.17
Minimum of Months 226.33 0.08 0.00   538.34 0.00 0.00 170.33 762.54 0.00 0.00 190.67
Maximum of Months 437.50 0.13 0.00   2682.47 0.00 0.00 309.67 2685.16 0.00 0.00 364.50



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.271474E+09 693.87 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.170742E+09 694.33 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.299317E+09 693.87 21-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.435680E+09 697.12 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.481064E+09 697.10 30-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 0.441094E+09 697.47 12-JUN-06:02 0.00 0.00 0.00 0.00 0.00
July 0.395531E+09 697.45 17-JUL-06:02 0.00 0.00 0.00 0.00 0.00
August 0.314733E+09 697.81 28-AUG-06:02 0.00 0.00 0.00 0.00 0.00
September 0.335905E+09 697.23 11-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.362681E+09 697.18 23-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.288784E+09 697.62 20-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.253771E+09 693.69 05-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.405078E+10              
Minimum of Months 0.170742E+09 693.69   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.481064E+09 697.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 BIO HAZ VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 80348144.45 133.52 06-JAN-05:05 0.00 0.00 0.00 0.00 0.00
February 57514768.32 133.24 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 62837719.62 133.25 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 55987973.71 134.99 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 45438692.39 135.95 25-MAY-06:04 0.00 0.00 0.00 0.00 0.00
June 29942676.59 136.26 27-JUN-06:04 0.00 0.00 0.00 0.00 0.00
July 19624428.78 136.60 24-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 19905496.48 136.24 01-AUG-06:04 0.00 0.00 0.00 0.00 0.00
September 32882882.53 136.22 19-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 47434285.10 135.47 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 49885989.09 135.80 21-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 58990577.25 133.24 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.560794E+09              
Minimum of Months 19624428.78 133.24   0.00 0.00 0.00 0.00 0.00
Maximum of Months 80348144.45 136.60   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 CAFE VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 30941224.75 1029.22 09-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 228673.05 814.88 25-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 458206.20 677.76 04-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 1224301.72 949.84 08-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 71445.16 476.30 13-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 176127.76 893.61 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 11446395.87 990.22 26-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 44546374.52              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 30941224.75 1029.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 CLEAN VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 16398314.56 319.43 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 14155753.61 319.63 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 30093127.29 319.66 28-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 91056880.06 320.90 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.160102E+09 321.46 24-MAY-06:04 0.00 0.00 0.00 0.00 0.00
June 0.166940E+09 321.56 27-JUN-06:04 0.00 0.00 0.00 0.00 0.00
July 0.188875E+09 321.69 24-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 0.168748E+09 321.52 01-AUG-06:04 0.00 0.00 0.00 0.00 0.00
September 0.169910E+09 321.45 19-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 0.129435E+09 321.32 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 52521735.20 321.32 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 9093232.80 319.34 05-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.119733E+10              
Minimum of Months 9093232.80 319.34   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.188875E+09 321.69   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 62858142.40 394.22 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 50517230.05 394.48 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 93627045.30 394.51 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.213020E+09 396.03 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.318950E+09 396.99 26-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.323958E+09 397.02 28-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 0.352800E+09 397.01 24-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 0.318100E+09 396.97 30-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.323358E+09 396.72 19-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 0.274452E+09 396.56 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.143479E+09 396.55 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 44047818.10 394.48 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.251917E+10              
Minimum of Months 44047818.10 394.22   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.352800E+09 397.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 DICTATION VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 417080.12 43.87 30-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 337.17 2.25 05-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 325095.78 43.92 05-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 231843.01 43.67 10-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 974356.07              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 417080.12 43.92   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.249524E+09 274.22 06-JAN-05:20 0.00 0.00 0.00 0.00 0.00
February 0.178745E+09 269.67 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.187736E+09 269.70 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.113913E+09 272.48 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 34806005.90 273.09 30-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 8556992.69 273.89 12-JUN-06:02 0.00 0.00 0.00 0.00 0.00
July 2018924.07 273.11 10-JUL-06:02 0.00 0.00 0.00 0.00 0.00
August 1292683.02 270.78 19-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 5839942.57 273.02 25-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 23300435.58 273.06 23-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 60515584.20 273.78 20-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.183062E+09 268.84 05-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.104931E+10              
Minimum of Months 1292683.02 268.84   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.249524E+09 274.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 261465.50 137.91 09-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 14751.94 98.35 25-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 19308.48 99.09 04-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 88546.64 214.64 01-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 15207.29 85.87 30-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 399279.86              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 261465.50 214.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 63687616.75 1531.72 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 27926001.92 1532.80 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 37462824.71 1532.74 27-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 69442749.65 1538.63 24-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 61104010.92 1539.35 30-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 32758350.36 1540.29 12-JUN-06:02 0.00 0.00 0.00 0.00 0.00
July 21572009.42 1538.15 10-JUL-05:02 0.00 0.00 0.00 0.00 0.00
August 11162922.09 1537.90 28-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 17312859.80 1538.12 05-SEP-05:02 0.00 0.00 0.00 0.00 0.00
October 25423094.77 1537.99 02-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 17422401.15 1540.52 20-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 36254695.88 1524.80 05-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.421530E+09              
Minimum of Months 11162922.09 1524.80   0.00 0.00 0.00 0.00 0.00
Maximum of Months 69442749.65 1540.52   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 HUMID VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 IT HALL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 14569403.60 47.06 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 10959768.60 47.09 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 15160809.28 47.09 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 28030900.15 47.29 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 31185807.85 47.41 26-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 27768279.04 47.41 28-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 27006561.59 47.41 24-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 24537503.96 47.40 30-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 28886925.33 47.37 19-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 31306682.07 47.36 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 22521488.15 47.35 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 10956439.95 47.09 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.272891E+09              
Minimum of Months 10956439.95 47.06   0.00 0.00 0.00 0.00 0.00
Maximum of Months 31306682.07 47.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 IT ROOM VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 LOBBY VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 89324890.44 2908.53 17-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 14333715.08 2924.80 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 5871708.83 2623.22 06-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 4045402.98 2908.84 10-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 278493.16 2926.24 30-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 392489.79 2908.32 10-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 3559143.57 2923.09 20-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 33239598.12 2908.61 04-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.151045E+09              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 89324890.44 2926.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 800236.40 107.20 17-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 136877.40 69.74 26-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 937113.79              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 800236.40 107.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.306278E+09 564.43 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.263204E+09 564.81 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.379240E+09 564.78 27-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.446374E+09 567.08 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.426589E+09 567.88 22-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.380304E+09 567.62 05-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 0.327156E+09 567.38 17-JUL-06:02 0.00 0.00 0.00 0.00 0.00
August 0.307319E+09 567.66 28-AUG-06:02 0.00 0.00 0.00 0.00 0.00
September 0.330995E+09 567.19 11-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.361943E+09 567.13 23-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.308878E+09 567.48 20-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.272228E+09 564.28 05-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.411051E+10              
Minimum of Months 0.263204E+09 564.28   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.446374E+09 567.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 850011.43 106.31 01-JAN-04:11 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 850011.43              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 850011.43 106.31   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 11686992.47 162.50 17-JAN-11:10 0.00 0.00 0.00 0.00 0.00
February 2116757.44 162.70 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 1583607.36 163.34 24-APR-06:14 0.00 0.00 0.00 0.00 0.00
May 7117687.00 163.63 22-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 2413862.11 163.63 19-JUN-06:04 0.00 0.00 0.00 0.00 0.00
July 2555792.66 163.74 05-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 1032218.54 163.56 21-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 4632345.85 163.56 18-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 6010165.27 163.54 02-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 5708.06 95.13 20-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 600338.88 105.26 26-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 39755475.64              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 11686992.47 163.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 LOUNGE VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 MED GAS VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.808388E+09 510.05 06-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.701880E+09 490.66 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.812000E+09 490.71 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.631443E+09 496.78 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.384865E+09 498.52 22-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.236650E+09 499.45 05-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 0.127222E+09 499.32 17-JUL-06:02 0.00 0.00 0.00 0.00 0.00
August 0.116241E+09 499.46 07-AUG-06:02 0.00 0.00 0.00 0.00 0.00
September 0.175123E+09 498.10 11-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.296634E+09 497.92 02-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.431584E+09 498.14 20-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.707962E+09 490.66 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.542999E+10              
Minimum of Months 0.116241E+09 490.66   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.812000E+09 510.05   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 MRI HALL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 6463584.61 70.81 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 1636431.44 70.86 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 109492.97 63.68 06-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 1112076.17 70.81 17-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 423426.33 71.15 30-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 607780.30 70.85 10-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 25710.28 34.07 27-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 832904.09 51.78 11-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 11211406.20              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 6463584.61 71.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 MRI ROOM VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 MRI TOILET VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.164957E+09 295.79 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.131429E+09 295.99 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.169342E+09 295.98 27-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.159656E+09 297.22 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.128359E+09 297.27 30-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 98792471.30 297.52 12-JUN-06:02 0.00 0.00 0.00 0.00 0.00
July 75631327.99 297.52 17-JUL-06:02 0.00 0.00 0.00 0.00 0.00
August 73101157.96 297.68 28-AUG-06:02 0.00 0.00 0.00 0.00 0.00
September 79254524.26 297.38 11-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 96253118.71 297.29 02-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.103235E+09 297.44 20-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.126089E+09 295.71 05-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.140610E+10              
Minimum of Months 73101157.96 295.71   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.169342E+09 297.68   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 NURSE HALL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 31562547.12 215.26 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 13029122.34 215.41 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 22955667.69 215.43 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 69568834.35 216.32 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 95218435.68 216.75 25-MAY-06:04 0.00 0.00 0.00 0.00 0.00
June 87576100.14 216.87 28-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 76137986.70 216.86 24-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 55816562.65 216.74 01-AUG-06:04 0.00 0.00 0.00 0.00 0.00
September 58699721.00 216.69 19-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 71969725.36 216.63 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 52509652.26 216.61 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 15819295.12 215.41 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.650864E+09              
Minimum of Months 13029122.34 215.26   0.00 0.00 0.00 0.00 0.00
Maximum of Months 95218435.68 216.87   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 520648.50 22.78 02-JAN-13:40 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 584329.09 23.95 30-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 454.84 6.82 12-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 5725.86 15.86 05-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 409988.84 23.97 05-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 308094.21 23.84 10-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1829241.33              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 584329.09 23.97   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 NURSE STATION VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 71232256.79 98.01 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 65227977.82 98.08 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 98233639.33 98.09 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.113632E+09 98.46 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.136747E+09 98.70 26-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.135333E+09 98.71 28-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 0.139703E+09 98.71 24-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 0.136655E+09 98.70 30-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.131654E+09 98.63 19-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 0.124174E+09 98.59 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 98379054.42 98.59 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 68211340.51 98.08 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.131918E+10              
Minimum of Months 65227977.82 98.01   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.139703E+09 98.71   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 OFFICE VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 599756.12 114.92 02-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 599756.12              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 599756.12 114.92   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.273566E+09 1434.53 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.288208E+09 1435.50 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.676327E+09 1435.64 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.868746E+09 1441.36 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.937736E+09 1443.99 25-MAY-06:04 0.00 0.00 0.00 0.00 0.00
June 0.785242E+09 1443.31 19-JUN-06:04 0.00 0.00 0.00 0.00 0.00
July 0.635288E+09 1444.47 03-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 0.670560E+09 1443.73 29-AUG-06:04 0.00 0.00 0.00 0.00 0.00
September 0.816411E+09 1443.62 19-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 0.901679E+09 1443.33 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.658323E+09 1443.13 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.316793E+09 1435.51 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.782888E+10              
Minimum of Months 0.273566E+09 1434.53   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.937736E+09 1444.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.102689E+10 1952.12 16-JAN-08:12 0.00 0.00 0.00 0.00 0.00
February 0.811504E+09 1950.80 21-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.155416E+10 1953.68 27-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.327257E+10 1961.41 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.437016E+10 1964.91 25-MAY-06:04 0.00 0.00 0.00 0.00 0.00
June 0.437708E+10 1965.91 28-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 0.464311E+10 1965.85 24-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 0.450468E+10 1965.68 30-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.438345E+10 1964.42 19-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 0.386960E+10 1963.97 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.211225E+10 1963.28 21-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.887085E+09 1951.19 17-DEC-06:06 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.358125E+11              
Minimum of Months 0.811504E+09 1950.80   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.464311E+10 1965.91   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 PACU VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 60222821.67 322.80 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 46997562.77 323.01 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 89301170.27 323.05 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.203833E+09 324.29 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.302730E+09 325.07 26-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.309241E+09 325.10 28-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 0.344467E+09 325.09 24-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 0.307784E+09 325.06 30-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.307180E+09 324.85 19-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 0.258270E+09 324.72 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.130606E+09 324.71 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 44819839.51 323.02 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.240545E+10              
Minimum of Months 44819839.51 322.80   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.344467E+09 325.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.126305E+09 191.50 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 69081821.26 191.63 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 47461801.28 191.65 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 46852325.74 192.44 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 51309592.60 192.72 22-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 25366116.91 192.73 01-JUN-06:04 0.00 0.00 0.00 0.00 0.00
July 19635362.47 192.92 24-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 11961415.03 192.70 14-AUG-06:02 0.00 0.00 0.00 0.00 0.00
September 21896453.14 192.69 26-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 50959935.42 192.71 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 54924080.83 192.69 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 86450300.51 191.63 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.612205E+09              
Minimum of Months 11961415.03 191.50   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.126305E+09 192.92   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.701863E+09 564.91 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.568446E+09 565.27 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.738489E+09 565.33 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.858294E+09 567.51 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.940704E+09 568.88 26-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.906452E+09 568.92 28-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 0.871539E+09 568.90 24-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 0.859285E+09 568.85 30-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.874884E+09 568.49 19-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 0.868078E+09 568.26 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.694103E+09 568.25 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.622152E+09 565.28 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.950429E+10              
Minimum of Months 0.568446E+09 564.91   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.940704E+09 568.92   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.478553E+09 1010.25 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.457392E+09 1010.91 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.755623E+09 1011.01 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.107189E+10 1014.91 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.139349E+10 1017.36 26-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.142513E+10 1017.43 28-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 0.148686E+10 1017.40 24-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 0.145943E+10 1017.30 30-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.139995E+10 1016.66 19-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 0.125426E+10 1016.25 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.859445E+09 1016.23 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.449879E+09 1010.92 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.124919E+11              
Minimum of Months 0.449879E+09 1010.25   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.148686E+10 1017.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.544241E+09 375.13 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.428282E+09 375.38 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.483911E+09 375.42 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.375515E+09 376.94 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.263298E+09 377.00 30-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 0.198260E+09 377.43 05-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 0.141206E+09 377.32 17-JUL-06:02 0.00 0.00 0.00 0.00 0.00
August 0.146812E+09 377.42 07-AUG-06:02 0.00 0.00 0.00 0.00 0.00
September 0.188004E+09 377.15 11-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.274767E+09 377.03 02-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.330209E+09 377.22 20-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.479303E+09 375.38 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.385381E+10              
Minimum of Months 0.141206E+09 375.13   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.544241E+09 377.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.310582E+10 2543.36 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.271952E+10 2545.03 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.387666E+10 2545.28 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.503598E+10 2555.12 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.575988E+10 2561.44 26-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.566263E+10 2561.61 28-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 0.576903E+10 2561.54 24-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 0.573455E+10 2561.30 30-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.555158E+10 2559.69 19-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 0.523964E+10 2558.48 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.392294E+10 2558.52 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.294960E+10 2545.04 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.553278E+11              
Minimum of Months 0.271952E+10 2543.36   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.576903E+10 2561.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 RECEPTION VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 5527397.11 49.25 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 1577325.07 49.28 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 28284.08 26.30 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 1345603.23 49.25 17-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 2039929.61 49.54 31-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 219624.47 49.53 05-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 1965.94 32.77 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 430965.09 49.54 05-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 1604103.19 49.44 10-OCT-14:05 0.00 0.00 0.00 0.00 0.00
November 197807.58 49.53 20-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 597254.52 32.59 26-DEC-08:20 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 13570259.87              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 5527397.11 49.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.129828E+10 3190.85 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.815857E+09 3192.97 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.140504E+10 3190.84 21-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.203602E+10 3204.35 24-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.217407E+10 3205.65 30-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 0.196156E+10 3207.33 12-JUN-06:02 0.00 0.00 0.00 0.00 0.00
July 0.175154E+10 3207.25 17-JUL-06:02 0.00 0.00 0.00 0.00 0.00
August 0.138906E+10 3208.86 28-AUG-06:02 0.00 0.00 0.00 0.00 0.00
September 0.151316E+10 3206.23 11-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.164806E+10 3206.04 23-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.132025E+10 3208.06 20-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.119976E+10 3190.02 05-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.185126E+11              
Minimum of Months 0.815857E+09 3190.02   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.217407E+10 3208.86   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 SCHEDULING VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 11636975.97 254.26 17-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 1781060.95 255.71 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 1289175.89 254.20 27-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 1891574.76 256.23 15-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 595878.99 256.85 30-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 45496.21 255.79 12-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 36458.42 254.24 10-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 271813.92 253.98 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 2291759.13 254.45 27-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 19840194.25              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 11636975.97 256.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 SCRUB VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 24937222.77 209.00 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 9675535.82 209.14 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 9204304.19 209.13 27-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 10672085.12 209.93 24-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 8926598.22 210.34 22-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 3762083.05 210.39 26-JUN-06:04 0.00 0.00 0.00 0.00 0.00
July 1535442.03 210.31 10-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 372858.17 209.16 21-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 2783636.58 210.34 18-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 9492576.56 210.28 31-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 12568714.18 210.32 21-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 14020176.80 209.14 05-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.107951E+09              
Minimum of Months 372858.17 209.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 24937222.77 210.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 SOIL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 41728167.21 317.64 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 35492081.79 317.85 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 68012846.93 317.88 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.164516E+09 319.10 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.255941E+09 319.87 26-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.263685E+09 319.90 28-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 0.292681E+09 319.89 24-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 0.267744E+09 319.86 30-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.265003E+09 319.65 19-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 0.218597E+09 319.52 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.109442E+09 319.52 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 29263087.51 317.85 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.201210E+10              
Minimum of Months 29263087.51 317.64   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.292681E+09 319.90   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 SOIL WORK VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.103442E+09 421.93 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 84274016.18 422.21 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.156061E+09 422.25 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.307907E+09 423.88 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.434064E+09 424.90 26-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.435286E+09 424.93 28-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 0.468909E+09 424.92 24-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 0.423557E+09 424.88 30-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.427099E+09 424.61 19-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 0.376163E+09 424.43 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.215887E+09 424.43 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 81505210.53 422.21 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.351415E+10              
Minimum of Months 81505210.53 421.93   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.468909E+09 424.93   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 STEP DOWN VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.883578E+09 2111.40 20-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.556615E+09 2115.67 21-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.830264E+09 2112.27 31-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.100223E+10 2125.68 15-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.840609E+09 2126.69 27-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.676028E+09 2127.07 24-JUN-05:02 0.00 0.00 0.00 0.00 0.00
July 0.474636E+09 2127.96 29-JUL-05:02 0.00 0.00 0.00 0.00 0.00
August 0.347032E+09 2128.04 12-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.469390E+09 2127.13 02-SEP-05:02 0.00 0.00 0.00 0.00 0.00
October 0.645400E+09 2126.14 07-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.610218E+09 2126.00 21-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.756493E+09 2112.39 28-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.809249E+10              
Minimum of Months 0.347032E+09 2111.40   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.100223E+10 2128.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 STERILE HALL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 65954965.92 715.27 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 14690776.06 715.78 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 12792924.27 715.86 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 32304774.26 718.87 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 42000493.74 719.96 22-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 20755966.96 720.26 19-JUN-06:04 0.00 0.00 0.00 0.00 0.00
July 10905790.72 720.99 24-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 3552984.01 720.13 14-AUG-06:02 0.00 0.00 0.00 0.00 0.00
September 11870401.40 719.92 18-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 27851485.44 719.71 31-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 29319693.85 719.86 21-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 24292907.95 715.76 05-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.296293E+09              
Minimum of Months 3552984.01 715.27   0.00 0.00 0.00 0.00 0.00
Maximum of Months 65954965.92 720.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 4825382.04 115.51 17-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 324334.58 116.15 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 5221593.80 116.81 22-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 2119075.15 116.81 19-JUN-06:04 0.00 0.00 0.00 0.00 0.00
July 2618083.66 116.89 05-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 797663.92 116.76 21-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 3567427.67 116.76 18-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 3531509.35 116.52 10-OCT-14:05 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 173995.83 75.14 26-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 23179065.99              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 5221593.80 116.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 STORAGE VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.498292E+10 3441.52 06-JAN-05:20 0.00 0.00 0.00 0.00 0.00
February 0.406776E+10 3382.76 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.443746E+10 3383.11 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.311104E+10 3425.63 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.162275E+10 3447.40 24-MAY-06:04 0.00 0.00 0.00 0.00 0.00
June 0.891984E+09 3454.69 19-JUN-06:04 0.00 0.00 0.00 0.00 0.00
July 0.447875E+09 3445.53 17-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 0.526396E+09 3453.93 14-AUG-06:02 0.00 0.00 0.00 0.00 0.00
September 0.941662E+09 3452.90 18-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.173405E+10 3437.36 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.258493E+10 3445.76 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.432053E+10 3382.78 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.296694E+11              
Minimum of Months 0.447875E+09 3382.76   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.498292E+10 3454.69   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.377547E+09 750.35 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.227800E+09 750.86 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.213848E+09 750.94 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.110301E+09 760.70 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 43763014.77 763.67 31-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 11213821.87 763.75 12-JUN-06:02 0.00 0.00 0.00 0.00 0.00
July 2521976.04 760.94 10-JUL-06:02 0.00 0.00 0.00 0.00 0.00
August 1797644.74 753.40 15-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 15125816.76 763.32 18-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 73555552.31 760.93 02-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.142871E+09 761.26 20-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.283332E+09 750.87 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.150368E+10              
Minimum of Months 1797644.74 750.35   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.377547E+09 763.75   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.116339E+10 1015.44 06-JAN-05:20 0.00 0.00 0.00 0.00 0.00
February 0.897415E+09 998.10 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.921946E+09 1000.35 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.585684E+09 1010.75 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.267231E+09 1015.94 25-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.107891E+09 1016.02 12-JUN-06:02 0.00 0.00 0.00 0.00 0.00
July 36527985.43 1016.50 10-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 58765329.37 1019.10 14-AUG-06:02 0.00 0.00 0.00 0.00 0.00
September 0.154636E+09 1018.80 18-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.331519E+09 1016.18 31-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.526617E+09 1018.61 21-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.965860E+09 998.11 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.601749E+10              
Minimum of Months 36527985.43 998.10   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.116339E+10 1019.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 14738935.64 100.87 30-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 6737981.66 100.94 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 7386839.94 100.95 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 8231322.20 101.37 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 7048970.94 101.52 22-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 3731406.28 101.56 19-JUN-06:04 0.00 0.00 0.00 0.00 0.00
July 1611155.22 101.51 17-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 538571.05 101.54 14-AUG-06:02 0.00 0.00 0.00 0.00 0.00
September 2715976.53 101.52 18-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 5847768.16 101.49 31-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 7021309.75 101.51 21-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 8033153.37 100.94 05-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 73643390.76              
Minimum of Months 538571.05 100.87   0.00 0.00 0.00 0.00 0.00
Maximum of Months 14738935.64 101.56   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.848039E+09 1035.21 06-JAN-05:05 0.00 0.00 0.00 0.00 0.00
February 0.594428E+09 1026.68 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.577635E+09 1026.78 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.317593E+09 1039.79 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.128023E+09 1045.84 23-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 32723048.33 1046.24 01-JUN-06:04 0.00 0.00 0.00 0.00 0.00
July 7515489.98 1045.76 10-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 9686759.83 1044.74 16-AUG-06:02 0.00 0.00 0.00 0.00 0.00
September 58687534.19 1046.03 18-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.199074E+09 1045.51 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.360697E+09 1045.95 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.675862E+09 1026.68 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.380996E+10              
Minimum of Months 7515489.98 1026.68   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.848039E+09 1046.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 1 VESTIBULE VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.548177E+09 289.21 06-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.487950E+09 276.93 21-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.566033E+09 276.96 21-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.434530E+09 280.44 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.247941E+09 284.74 26-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.158003E+09 285.84 28-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 0.112086E+09 286.29 05-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 0.187469E+09 285.80 30-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.264394E+09 284.55 19-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 0.382314E+09 281.99 20-OCT-06:14 0.00 0.00 0.00 0.00 0.00
November 0.475605E+09 282.65 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.540080E+09 276.33 06-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.440458E+10              
Minimum of Months 0.112086E+09 276.33   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.566033E+09 289.21   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AHU-1_HEATC

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.969063E+11 69671.84 01-JAN-04:11 0.00 0.00 0.00 0.00 0.00
February 0.666282E+11 65183.67 19-FEB-07:20 0.00 0.00 0.00 0.00 0.00
March 0.486768E+11 67834.57 05-MAR-08:05 0.00 0.00 0.00 0.00 0.00
April 0.157964E+11 42398.20 05-APR-03:00 0.00 0.00 0.00 0.00 0.00
May 0.208801E+10 22314.34 01-MAY-04:00 0.00 0.00 0.00 0.00 0.00
June 0.245548E+09 10857.02 04-JUN-05:00 0.00 0.00 0.00 0.00 0.00
July 961819.66 6.93 07-JUL-10:10 0.00 0.00 0.00 0.00 0.00
August 37753930.58 4993.46 19-AUG-05:00 0.00 0.00 0.00 0.00 0.00
September 0.655271E+09 11877.84 06-SEP-03:23 0.00 0.00 0.00 0.00 0.00
October 0.955786E+10 37444.07 30-OCT-04:08 0.00 0.00 0.00 0.00 0.00
November 0.338222E+11 60992.38 29-NOV-04:00 0.00 0.00 0.00 0.00 0.00
December 0.871341E+11 72446.14 24-DEC-10:37 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.361549E+12              
Minimum of Months 961819.66 6.93   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.969063E+11 72446.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AHU-2_HEATC

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.649201E+11 84230.52 23-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.453093E+11 84374.49 06-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.338843E+11 84441.60 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.852958E+10 75365.36 05-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.830292E+09 42833.02 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 49530992.78 12735.96 17-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 1489699.29 2016.86 18-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 53949433.44 16671.70 19-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.370261E+09 25099.22 06-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.415520E+10 67216.62 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.191898E+11 85068.74 29-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.591617E+11 85710.53 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.236456E+12              
Minimum of Months 1489699.29 2016.86   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.649201E+11 85710.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AHU-1_EXTRAWATERHEATC

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.485117E+11 32944.83 08-JAN-08:07 0.00 0.00 0.00 0.00 0.00
February 0.385151E+11 31997.27 12-FEB-13:35 0.00 0.00 0.00 0.00 0.00
March 0.285029E+11 31980.76 26-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.850589E+10 32204.86 16-APR-07:25 0.00 0.00 0.00 0.00 0.00
May 0.105507E+10 31993.19 07-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 2011180.79 26815.74 04-JUN-05:32 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.652841E+09 32016.81 10-SEP-05:17 0.00 0.00 0.00 0.00 0.00
October 0.662713E+10 32453.61 15-OCT-05:23 0.00 0.00 0.00 0.00 0.00
November 0.212468E+11 32051.97 19-NOV-11:15 0.00 0.00 0.00 0.00 0.00
December 0.461239E+11 33086.67 25-DEC-11:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.199743E+12              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.485117E+11 33086.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 CONFERENCE VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.691319E+09 2088.67 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.324273E+09 2088.67 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.181596E+09 2088.67 03-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 85952454.85 2088.67 03-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 20874789.97 2088.67 13-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 24348411.62 1947.71 10-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 16183448.83 2088.67 05-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 17473078.43 1654.45 19-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 24833182.48 1919.16 23-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 96937986.09 2088.67 10-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.242207E+09 2088.67 04-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.611858E+09 2088.67 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.233786E+10              
Minimum of Months 16183448.83 1654.45   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.691319E+09 2088.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.151643E+09 552.56 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 95578439.04 552.56 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 91363242.02 552.56 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 74014472.45 552.56 10-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 95643822.17 552.56 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.110072E+09 552.56 02-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.110882E+09 552.56 03-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.109687E+09 552.56 02-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 80281805.50 552.56 01-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 79306535.04 552.56 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 84734091.14 552.56 01-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.126794E+09 552.56 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.121000E+10              
Minimum of Months 74014472.45 552.56   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.151643E+09 552.56   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 DICTATION VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 1699172.32 118.89 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 296994.82 118.89 06-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 39872.89 118.89 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 18808.96 118.89 10-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 36710.77 118.89 30-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 17376.81 97.62 12-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 20618.01 72.14 05-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 7970.79 70.93 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 36024.50 118.89 10-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 149885.43 118.89 06-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 1045800.05 118.89 04-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3369235.36              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1699172.32 118.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 1 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.174797E+10 3474.26 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.101467E+10 3474.26 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.653522E+09 3474.26 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.313042E+09 3474.26 08-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.153829E+09 3474.26 02-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.174171E+09 3474.26 05-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.165374E+09 3474.26 03-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.152621E+09 3474.26 07-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.145762E+09 3474.26 05-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.305211E+09 3474.26 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.652127E+09 3474.26 01-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.153502E+10 3474.26 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.701331E+10              
Minimum of Months 0.145762E+09 3474.26   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.174797E+10 3474.26   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 2 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.160778E+10 7196.58 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.876962E+09 7196.58 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.663736E+09 7196.58 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.567034E+09 7196.58 08-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.859711E+09 7196.58 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.113989E+10 7196.58 07-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.128698E+10 7196.58 05-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.106181E+10 7196.58 01-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.674281E+09 7196.58 01-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.554181E+09 7196.58 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.723377E+09 7196.58 14-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.130562E+10 7196.58 11-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.113214E+11              
Minimum of Months 0.554181E+09 7196.58   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.160778E+10 7196.58   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 3 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.213707E+10 9595.44 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.118505E+10 9595.44 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.940772E+09 9595.44 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.892834E+09 9595.44 08-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.139457E+10 9595.44 06-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.180430E+10 9595.44 03-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.207573E+10 9595.44 01-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.172637E+10 9595.44 01-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.111414E+10 9595.44 01-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.872021E+09 9595.44 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.104084E+10 9595.44 01-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.175773E+10 9595.44 11-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.169414E+11              
Minimum of Months 0.872021E+09 9595.44   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.213707E+10 9595.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 4 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.261252E+09 893.97 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.133632E+09 893.97 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 97076552.01 893.97 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 63575423.27 893.97 08-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 46220431.42 893.97 02-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 56968180.82 893.97 05-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 62218755.18 893.97 03-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 48151555.00 893.97 07-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 35477339.55 893.97 05-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 62255281.76 893.97 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.111899E+09 893.97 01-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.231210E+09 893.97 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.120994E+10              
Minimum of Months 35477339.55 893.97   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.261252E+09 893.97   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 5 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.128507E+10 4036.94 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.731791E+09 4036.94 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.429699E+09 4036.94 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.181515E+09 4036.94 08-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 86356526.47 4036.94 30-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 98435250.90 4036.94 10-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 96142980.65 4036.94 05-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.115404E+09 3915.62 07-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.106512E+09 4036.94 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.198511E+09 4036.94 07-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.433025E+09 4036.94 03-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.105823E+10 4036.94 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.482069E+10              
Minimum of Months 86356526.47 3915.62   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.128507E+10 4036.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 6 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.105838E+10 2818.66 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.684456E+09 2818.66 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.517550E+09 2818.66 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.356046E+09 2818.66 08-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.325070E+09 2818.66 06-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.352489E+09 2818.66 07-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.382974E+09 2818.66 03-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.370543E+09 2818.66 01-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.307067E+09 2818.66 02-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.332964E+09 2818.66 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.474832E+09 2818.66 01-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.877469E+09 2818.66 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.603984E+10              
Minimum of Months 0.307067E+09 2818.66   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.105838E+10 2818.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 7 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.258196E+10 10554.99 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.158317E+10 10554.99 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.120761E+10 10554.99 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.105156E+10 10554.99 08-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.143090E+10 10554.99 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.178236E+10 10554.99 07-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.209068E+10 10554.99 05-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.186964E+10 10554.99 01-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.132448E+10 10554.99 01-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.103959E+10 10554.99 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.115546E+10 10554.99 14-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.201994E+10 10554.99 11-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.191374E+11              
Minimum of Months 0.103959E+10 10554.99   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.258196E+10 10554.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 8 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.110377E+10 3346.41 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.661824E+09 3346.41 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.454109E+09 3346.41 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.269135E+09 3346.41 24-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.235936E+09 3346.41 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.279386E+09 3346.41 10-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.324916E+09 3346.41 03-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.311265E+09 3346.41 01-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.232838E+09 3346.41 05-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.238118E+09 3346.41 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.391661E+09 3346.41 14-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.873356E+09 3346.41 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.537631E+10              
Minimum of Months 0.232838E+09 3346.41   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.110377E+10 3346.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM 9 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.128312E+10 5277.49 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.758249E+09 5277.49 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.534119E+09 5277.49 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.402912E+09 5277.49 24-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.514872E+09 5277.49 15-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.657738E+09 5277.49 10-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.750499E+09 5277.49 05-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.676945E+09 5277.49 01-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.450654E+09 5277.49 05-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.359222E+09 5277.49 16-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.476336E+09 5277.49 20-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.975469E+09 5277.49 11-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.784014E+10              
Minimum of Months 0.359222E+09 5277.49   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.128312E+10 5277.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 91781562.85 513.24 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 41520486.18 513.24 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 19036318.30 513.24 02-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 7879217.41 513.24 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 3681782.31 513.24 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 2133586.09 513.24 05-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 1886240.89 513.24 03-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 654629.68 513.24 07-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 1642619.90 513.24 05-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 9463926.53 513.24 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 29773654.37 513.24 01-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 70627432.43 513.24 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.280081E+09              
Minimum of Months 654629.68 513.24   0.00 0.00 0.00 0.00 0.00
Maximum of Months 91781562.85 513.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 50331007.12 323.56 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 21081746.72 323.56 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 8619881.62 323.56 04-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 5658709.07 323.56 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 4123450.74 323.56 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 2885349.87 323.56 05-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 3359755.07 323.56 03-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 1450428.25 323.56 07-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 2180322.33 323.56 05-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 6914020.86 323.56 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 18454741.03 323.56 04-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 34001379.77 323.56 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.159061E+09              
Minimum of Months 1450428.25 323.56   0.00 0.00 0.00 0.00 0.00
Maximum of Months 50331007.12 323.56   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 51084325.23 335.30 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 21453917.34 335.30 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 10184187.59 335.30 03-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 8122167.41 335.30 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 7851951.65 335.30 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 6303294.08 335.30 05-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 8044952.46 335.30 03-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 4251520.01 335.30 07-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 4538413.31 335.30 05-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 9774570.62 335.30 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 20972613.40 335.30 01-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 36029768.66 335.30 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.188612E+09              
Minimum of Months 4251520.01 335.30   0.00 0.00 0.00 0.00 0.00
Maximum of Months 51084325.23 335.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 62276391.81 237.33 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 22855364.48 237.33 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 9964994.87 237.33 04-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 4538134.66 237.33 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 2750482.84 237.33 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 1363101.34 237.33 05-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 1718405.54 237.33 03-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 1186432.29 237.33 07-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 2372607.63 237.33 05-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 6241417.82 237.33 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 13020731.05 237.33 04-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 32575625.52 237.33 02-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.160864E+09              
Minimum of Months 1186432.29 237.33   0.00 0.00 0.00 0.00 0.00
Maximum of Months 62276391.81 237.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 56644306.22 237.93 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 19370645.61 237.93 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 7576466.07 237.93 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 2452930.37 237.93 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 839449.23 237.93 01-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 193438.38 237.93 05-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 149781.14 237.93 05-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 82732.58 237.93 07-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 569907.02 237.93 05-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 3282266.89 237.93 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 9158778.93 237.93 06-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 28013324.76 237.93 02-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.128334E+09              
Minimum of Months 82732.58 237.93   0.00 0.00 0.00 0.00 0.00
Maximum of Months 56644306.22 237.93   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 82043166.59 283.92 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 29825137.40 283.92 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 12526460.18 283.92 04-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 3577409.13 283.92 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 1224438.23 283.92 01-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 371513.80 283.92 05-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 337568.22 283.92 05-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 222042.45 283.92 07-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 802224.04 283.92 05-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 4472132.01 283.92 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 13707762.34 283.92 06-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 41937291.25 283.92 02-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.191047E+09              
Minimum of Months 222042.45 283.92   0.00 0.00 0.00 0.00 0.00
Maximum of Months 82043166.59 283.92   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 JANITOR VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.209650E+09 661.07 05-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.128853E+09 661.07 14-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 79826926.54 581.90 16-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 29267527.10 488.27 10-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 9144515.58 490.02 30-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 2611386.88 507.07 05-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 2019787.10 499.07 17-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 1494854.70 499.53 07-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 4099386.77 503.19 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 18490344.78 488.60 10-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 56271304.38 538.61 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.168272E+09 646.27 20-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.710000E+09              
Minimum of Months 1494854.70 488.27   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.209650E+09 661.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 LOUNGE VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 58962.73 216.20 09-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 104338.30 216.20 25-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 16913.07 112.75 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 37886.11 216.20 26-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 218100.21              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 104338.30 216.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 1183559.43 479.72 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 653864.51 479.72 25-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 58379.52 340.65 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 637911.49 479.72 02-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2533714.96              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1183559.43 479.72   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 1228590.68 576.08 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 729126.37 576.08 25-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 45909.21 306.06 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 599763.67 576.08 02-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2603389.94              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1228590.68 576.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 OFFICE VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.649898E+09 2682.35 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.260830E+09 2682.35 01-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 94094472.72 2682.35 02-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 16971551.10 2682.35 03-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 163795.33 1718.61 30-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 102179.70 588.94 23-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 14541086.89 2682.35 10-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.129616E+09 2682.35 04-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.527329E+09 2682.35 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.169355E+10              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.649898E+09 2682.35   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.122720E+09 833.19 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 40842711.82 833.19 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 13894337.70 833.19 04-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 5222004.01 833.19 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 1647482.66 833.19 01-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 178295.65 833.19 12-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 95062.95 675.49 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 802739.02 833.19 05-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 6945180.99 833.19 10-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 29363149.41 833.19 06-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 73854242.04 833.19 02-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.295565E+09              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122720E+09 833.19   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 RECEPTION VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.460646E+09 4135.99 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.151415E+09 4135.99 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 51459665.29 4135.99 04-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 4876775.63 4135.99 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 202083.86 1273.86 13-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 209596.60 1203.99 10-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 130600.92 870.67 19-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 213320.76 780.87 23-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 4855387.09 4135.99 14-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 51817269.37 4135.99 04-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.311551E+09 4135.99 02-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.103738E+10              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.460646E+09 4135.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 21433405.84 677.99 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 3298409.14 677.99 06-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 704273.24 677.99 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 146346.12 677.99 10-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 80362.26 677.99 30-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 341969.44 677.99 10-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 1444681.02 677.99 06-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 10168854.36 677.99 04-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 37618301.42              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 21433405.84 677.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.251501E+09 1005.89 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.147889E+09 1005.89 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.120003E+09 1005.89 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 93265277.58 1005.89 11-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.117029E+09 1005.89 08-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.142869E+09 1005.89 05-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.143269E+09 1005.89 05-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.134618E+09 1005.89 07-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 90873321.61 1005.89 05-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 88715112.73 1005.89 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.115612E+09 1005.89 01-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.194481E+09 1005.89 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.164013E+10              
Minimum of Months 88715112.73 1005.89   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.251501E+09 1005.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 900949.36 551.19 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 46134.16 307.56 25-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 396439.40 551.19 26-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1343522.93              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 900949.36 551.19   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 1693554.64 580.30 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 342646.65 580.30 25-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 19733.20 131.55 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 769832.12 580.30 26-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2825766.61              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1693554.64 580.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 34616099.86 134.34 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 17856383.86 134.34 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 13472341.84 134.34 02-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 10652658.65 134.34 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 12368223.35 134.34 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 13755899.97 134.34 01-JUN-06:02 0.00 0.00 0.00 0.00 0.00
July 15296135.56 134.34 03-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 12179173.97 134.34 01-AUG-06:02 0.00 0.00 0.00 0.00 0.00
September 8891184.25 134.34 01-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 13364482.69 134.34 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 19057079.18 134.34 01-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 28200611.50 134.34 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.199710E+09              
Minimum of Months 8891184.25 134.34   0.00 0.00 0.00 0.00 0.00
Maximum of Months 34616099.86 134.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 75747954.39 287.93 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 35894522.15 287.93 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 20546330.95 287.93 01-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 11258483.89 287.93 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 8509287.88 287.93 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 8171819.67 287.93 05-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 9215783.38 287.93 03-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 6351772.48 287.93 07-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 7467047.46 287.93 05-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 13450956.41 287.93 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 23629917.06 287.93 01-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 48906108.03 287.93 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.269150E+09              
Minimum of Months 6351772.48 287.93   0.00 0.00 0.00 0.00 0.00
Maximum of Months 75747954.39 287.93   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 87033653.30 345.59 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 37155441.99 345.59 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 18268205.33 345.59 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 6956704.81 345.59 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 4125816.01 345.59 01-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 2960269.01 345.59 05-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 3601921.88 345.59 03-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 2129944.39 345.59 07-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 3222028.40 345.59 05-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 7610809.98 345.59 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 18154960.18 345.59 06-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 49900354.77 345.59 02-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.241120E+09              
Minimum of Months 2129944.39 345.59   0.00 0.00 0.00 0.00 0.00
Maximum of Months 87033653.30 345.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 UTILITY VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.334064E+09 766.16 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.184427E+09 766.16 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.109170E+09 766.16 03-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 33097459.21 766.16 10-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 7975028.52 766.16 30-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 3164411.89 766.16 12-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 1259876.88 766.16 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 2354381.35 766.16 14-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 10903652.23 766.16 11-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 55325266.81 766.16 10-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.129037E+09 766.16 01-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.290395E+09 766.16 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.116117E+10              
Minimum of Months 1259876.88 766.16   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.334064E+09 766.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 WORK VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.159914E+09 2868.98 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 29350453.21 2868.98 06-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 3608310.20 2868.98 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 4579675.75 2868.98 13-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 62482368.04 2868.98 02-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.259934E+09              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.159914E+09 2868.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 WORK HALL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 42056521.27 1002.27 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 6106685.64 1002.27 06-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 1472773.42 1002.27 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 17444.36 290.74 10-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 102912.58 1002.27 10-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 1925732.79 1002.27 06-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 19606025.96 1002.27 04-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 71288096.01              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 42056521.27 1002.27   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 WORK TOILET VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.309016E+09 519.23 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.220418E+09 519.23 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.194194E+09 519.23 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.139899E+09 519.23 08-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.116484E+09 519.23 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.112977E+09 519.23 02-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.102485E+09 519.23 03-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.107852E+09 519.23 02-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 99166705.30 519.23 01-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.121674E+09 519.23 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.163985E+09 519.23 01-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.262650E+09 519.23 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.195080E+10              
Minimum of Months 99166705.30 519.23   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.309016E+09 519.23   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 2 X-RAY VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 7702117.33 181.82 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 3330178.72 181.82 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 906814.98 181.82 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 127364.94 181.82 03-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 12767.82 122.61 30-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 231.28 1.54 24-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 3553.05 14.71 31-JUL-06:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 7435.98 90.28 05-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 203336.94 181.82 10-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 1098773.84 181.82 06-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 4762536.07 181.82 02-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 18155110.97              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 7702117.33 181.82   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.433408E+09 1443.69 04-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.231145E+09 1443.69 14-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.134871E+09 1311.34 16-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 34277317.99 1105.61 10-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 5738623.86 1113.90 30-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 333111.41 1128.09 12-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 75776.11 925.70 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 61760.88 280.71 19-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 1104270.71 1133.79 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 23755541.62 1103.92 11-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 95913037.28 1213.96 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.332596E+09 1443.69 02-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.129328E+10              
Minimum of Months 61760.88 280.71   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.433408E+09 1443.69   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 HUMID VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 13978920.55 394.63 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 5513937.28 394.63 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 1203228.13 394.63 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 69278.56 394.63 03-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 177929.01 394.63 10-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 1524817.08 394.63 06-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 8207233.13 394.63 02-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 30675343.73              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 13978920.55 394.63   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 JANITOR VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.468043E+09 484.67 06-JAN-06:30 0.00 0.00 0.00 0.00 0.00
February 0.337600E+09 467.35 14-FEB-06:20 0.00 0.00 0.00 0.00 0.00
March 0.273989E+09 382.47 16-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.148372E+09 332.09 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 68809705.38 339.13 27-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 46202514.10 351.14 28-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 35463759.15 356.78 05-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 48462041.43 349.21 01-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 71661457.66 341.88 19-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.136881E+09 323.94 20-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.236467E+09 363.40 25-NOV-06:13 0.00 0.00 0.00 0.00 0.00
December 0.423485E+09 439.35 20-DEC-06:20 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.229544E+10              
Minimum of Months 35463759.15 323.94   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.468043E+09 484.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 LOCKER VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 17426287.72 403.57 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 5529325.95 403.57 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 1047212.04 403.57 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 15515.94 58.44 22-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 12180.78 121.81 14-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 1370222.76 403.57 13-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 12373055.51 403.57 02-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 37773800.70              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 17426287.72 403.57   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 LOUNGE VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.104420E+09 2050.36 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 26222959.32 2050.36 04-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 5924591.14 2050.36 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 22682.04 226.82 22-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 51449.60 514.50 14-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 6399949.90 2050.36 25-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 73188784.49 2050.36 02-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.216231E+09              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.104420E+09 2050.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.104038E+10 1486.41 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.699596E+09 1486.41 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.542974E+09 1486.41 04-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.298086E+09 1486.41 05-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.190916E+09 1486.41 01-MAY-04:02 0.00 0.00 0.00 0.00 0.00
June 0.176886E+09 1486.41 02-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 0.182293E+09 1486.41 03-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.222919E+09 1486.41 01-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.218412E+09 1486.41 01-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.313760E+09 1486.41 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.497049E+09 1486.41 01-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.907175E+09 1486.41 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.529045E+10              
Minimum of Months 0.176886E+09 1486.41   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.104038E+10 1486.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 MECHANICAL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:02 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.166028E+09 1531.87 04-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 67119019.60 1531.87 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 17974540.51 1531.87 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 1266943.67 1303.98 10-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 1536968.76 1319.10 30-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 19892679.71 1461.56 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.114084E+09 1531.87 02-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.387902E+09              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.166028E+09 1531.87   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 OFFICE VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.186781E+10 8748.53 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.732415E+09 8748.53 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.270801E+09 8748.53 03-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 20144475.67 8748.53 03-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 1004361.08 8748.53 01-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 41935.29 279.57 19-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 23234662.05 8748.53 10-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.207170E+09 8748.53 04-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.137958E+10 8748.53 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.450220E+10              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.186781E+10 8748.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.572627E+09 3136.63 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.255436E+09 3136.63 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.115217E+09 3136.63 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 22839208.88 3030.90 10-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 2837164.06 3035.44 30-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 40305.26 604.58 12-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 8405.94 140.10 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 390870.28 2768.55 05-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 25032483.37 3035.74 16-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.114371E+09 3136.63 25-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.417795E+09 3136.63 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.152660E+10              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.572627E+09 3136.63   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.364704E+09 424.31 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.267465E+09 424.31 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.233854E+09 424.31 01-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.152249E+09 424.31 01-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 0.107825E+09 424.31 01-MAY-04:02 0.00 0.00 0.00 0.00 0.00
June 98413050.73 424.31 01-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 86516226.00 424.31 03-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 97442776.87 424.31 01-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 97754880.14 424.31 01-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.137375E+09 424.31 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.201605E+09 424.31 01-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.325802E+09 424.31 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.217101E+10              
Minimum of Months 86516226.00 424.31   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.364704E+09 424.31   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.497570E+10 14035.79 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.291724E+10 14035.79 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.207458E+10 14035.79 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.114144E+10 14035.79 08-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.666982E+09 14035.79 02-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.785855E+09 14035.79 03-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.101438E+10 14035.79 01-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.776459E+09 14035.79 01-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.693775E+09 14035.79 01-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.116672E+10 14035.79 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.218174E+10 14035.79 01-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.448455E+10 14035.79 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.228794E+11              
Minimum of Months 0.666982E+09 14035.79   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.497570E+10 14035.79   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.147885E+10 6548.36 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.853710E+09 6548.36 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.487028E+09 6548.36 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.337468E+09 6548.36 08-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.335560E+09 6548.36 02-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.469637E+09 6548.36 03-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.646553E+09 6548.36 01-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.490491E+09 6548.36 01-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.352144E+09 6548.36 01-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.316367E+09 6548.36 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.535683E+09 6548.36 01-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.118801E+10 6548.36 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.749150E+10              
Minimum of Months 0.316367E+09 6548.36   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.147885E+10 6548.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.224102E+09 690.61 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.143006E+09 690.61 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.105037E+09 690.61 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 69015948.99 690.61 11-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 70087467.67 690.61 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 85039756.83 690.61 02-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 90992241.26 690.61 03-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 93228801.45 690.61 02-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 67241486.55 690.61 01-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 69857168.74 690.61 02-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 98607949.26 690.61 01-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.183019E+09 690.61 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.129924E+10              
Minimum of Months 67241486.55 690.61   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.224102E+09 690.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.325164E+09 692.63 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.223448E+09 692.63 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.180021E+09 692.63 01-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.124298E+09 692.63 01-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.119831E+09 692.63 02-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.131277E+09 692.63 01-JUN-06:02 0.00 0.00 0.00 0.00 0.00
July 0.133583E+09 692.63 03-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.144047E+09 692.63 01-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.117065E+09 692.63 01-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.128699E+09 692.63 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.172156E+09 692.63 01-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.279990E+09 692.63 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.207958E+10              
Minimum of Months 0.117065E+09 692.63   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.325164E+09 692.63   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.132104E+09 435.45 05-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 75595416.73 435.45 14-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 41428202.68 376.66 16-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 12602572.45 317.40 24-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 2847834.47 319.97 30-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 938249.67 328.21 05-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 1022753.30 335.15 31-JUL-06:02 0.00 0.00 0.00 0.00 0.00
August 857588.73 329.15 14-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 2266657.36 330.35 18-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 11483720.37 318.98 02-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 36486534.15 348.65 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.108040E+09 418.34 20-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.425674E+09              
Minimum of Months 857588.73 317.40   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.132104E+09 435.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 TREATMENT VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.963924E+09 5138.36 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.510668E+09 5138.36 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.265871E+09 5138.36 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.164369E+09 5138.36 08-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.144334E+09 5138.36 08-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.223610E+09 5138.36 07-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.314690E+09 5138.36 03-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.217660E+09 5138.36 01-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.162639E+09 5138.36 02-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.150890E+09 5138.36 02-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.278457E+09 5138.36 14-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.746922E+09 5138.36 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.414403E+10              
Minimum of Months 0.144334E+09 5138.36   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.963924E+09 5138.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.234132E+10 7691.37 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.109083E+10 7691.37 01-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.588951E+09 7691.37 01-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.126437E+09 7691.37 01-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 18203079.25 7691.37 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 5470034.25 6272.60 12-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 2689948.15 4952.35 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 4211230.00 7691.37 19-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 11950483.74 7691.37 05-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.123087E+09 7691.37 04-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.541485E+09 7691.37 03-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.194960E+10 7691.37 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.680424E+10              
Minimum of Months 2689948.15 4952.35   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.234132E+10 7691.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.181008E+10 5047.39 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.886665E+09 5047.39 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.510956E+09 5047.39 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.121148E+09 4894.85 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 14549029.79 4898.22 30-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 2195810.79 3475.97 12-JUN-06:01 0.00 0.00 0.00 0.00 0.00
July 112193.22 977.53 10-JUL-06:01 0.00 0.00 0.00 0.00 0.00
August 2342423.87 4639.32 19-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 5414683.06 3907.28 23-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.109201E+09 4898.95 16-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.478412E+09 5047.39 25-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.155829E+10 5047.39 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.549936E+10              
Minimum of Months 112193.22 977.53   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.181008E+10 5047.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 UTILITY VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.329586E+09 769.89 06-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.209725E+09 734.65 14-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.141585E+09 624.17 16-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 64958492.20 541.92 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 26547596.40 553.54 27-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 20428878.71 574.26 26-JUN-06:04 0.00 0.00 0.00 0.00 0.00
July 22586693.31 584.83 22-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 23775545.74 564.65 01-AUG-06:02 0.00 0.00 0.00 0.00 0.00
September 29871709.87 554.57 01-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 66218398.15 528.66 03-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.131620E+09 577.75 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.277656E+09 693.23 20-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.134456E+10              
Minimum of Months 20428878.71 528.66   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.329586E+09 769.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLOOR 3 WORK VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.825584E+09 2982.53 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.356134E+09 2982.53 01-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.140243E+09 2982.53 02-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 12656314.97 2982.53 03-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 67624.38 614.83 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 581.49 3.88 19-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 221210.48 1273.33 23-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 15503884.04 2982.53 10-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.139685E+09 2982.53 04-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.692406E+09 2982.53 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.218250E+10              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.825584E+09 2982.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: NE STAIR VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.382702E+10 3476.57 06-JAN-06:30 0.00 0.00 0.00 0.00 0.00
February 0.275383E+10 3352.29 14-FEB-06:20 0.00 0.00 0.00 0.00 0.00
March 0.236524E+10 2758.67 16-MAR-05:20 0.00 0.00 0.00 0.00 0.00
April 0.108760E+10 2381.52 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.227444E+09 2433.60 27-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 37508755.87 2478.34 24-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 11019333.96 2363.15 10-JUL-06:02 0.00 0.00 0.00 0.00 0.00
August 16166661.23 2414.62 17-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 0.106880E+09 2429.72 19-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.518161E+09 2324.45 03-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.143825E+10 2606.76 25-NOV-06:13 0.00 0.00 0.00 0.00 0.00
December 0.333701E+10 3151.47 20-DEC-06:20 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.157261E+11              
Minimum of Months 11019333.96 2324.45   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.382702E+10 3476.57   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: NW ELEVATOR VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.198023E+10 2279.32 06-JAN-06:30 0.00 0.00 0.00 0.00 0.00
February 0.139253E+10 2197.83 14-FEB-06:20 0.00 0.00 0.00 0.00 0.00
March 0.120455E+10 1799.09 16-MAR-05:15 0.00 0.00 0.00 0.00 0.00
April 0.598283E+09 1561.20 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.162790E+09 1580.10 23-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 43103139.96 1627.46 19-JUN-06:02 0.00 0.00 0.00 0.00 0.00
July 8004393.92 1599.97 31-JUL-06:02 0.00 0.00 0.00 0.00 0.00
August 5674938.14 1544.70 16-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 43501356.58 1577.19 18-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.224277E+09 1524.15 03-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.624373E+09 1664.87 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.163568E+10 2066.16 20-DEC-06:20 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.792299E+10              
Minimum of Months 5674938.14 1524.15   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.198023E+10 2279.32   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: NW STAIR VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.402937E+10 3562.37 06-JAN-06:30 0.00 0.00 0.00 0.00 0.00
February 0.291969E+10 3435.01 14-FEB-06:20 0.00 0.00 0.00 0.00 0.00
March 0.253045E+10 2826.74 16-MAR-05:20 0.00 0.00 0.00 0.00 0.00
April 0.118558E+10 2440.24 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.242418E+09 2493.63 27-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 37315214.42 2509.76 10-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 7942478.41 2421.44 10-JUL-06:02 0.00 0.00 0.00 0.00 0.00
August 9885056.22 2437.72 28-AUG-06:01 0.00 0.00 0.00 0.00 0.00
September 96384843.93 2465.17 18-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.500639E+09 2381.82 03-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.144811E+10 2671.09 25-NOV-06:13 0.00 0.00 0.00 0.00 0.00
December 0.345482E+10 3229.23 20-DEC-06:20 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.164626E+11              
Minimum of Months 7942478.41 2381.82   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.402937E+10 3562.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: SW STAIR VAV BOX REHEAT COIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.127543E+10 1738.81 06-JAN-06:30 0.00 0.00 0.00 0.00 0.00
February 0.840786E+09 1676.65 14-FEB-06:20 0.00 0.00 0.00 0.00 0.00
March 0.707831E+09 1372.14 16-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.329956E+09 1190.98 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 76880546.87 1186.15 24-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 15302254.86 1224.96 10-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 2105001.57 1182.03 10-JUL-06:02 0.00 0.00 0.00 0.00 0.00
August 1933973.46 1147.04 19-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 13205001.44 1186.25 18-SEP-06:01 0.00 0.00 0.00 0.00 0.00
October 0.119341E+09 1162.77 03-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.387558E+09 1270.04 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.108557E+10 1576.20 20-DEC-06:20 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.485590E+10              
Minimum of Months 1933973.46 1147.04   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.127543E+10 1738.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AHU-1_EXTRAELECHEATC

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum}[W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.943985E+10 23309.13 06-JAN-07:15 0.00 0.00 0.00 0.00 0.00
February 0.629936E+10 21474.98 14-FEB-06:27 0.00 0.00 0.00 0.00 0.00
March 0.543910E+10 12370.38 16-MAR-05:20 0.00 0.00 0.00 0.00 0.00
April 0.411307E+10 3820.20 05-APR-07:33 0.00 0.00 0.00 0.00 0.00
May 0.178681E+10 2554.95 05-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.273938E+09 2373.71 02-JUN-17:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.355733E+09 2464.35 08-SEP-17:00 0.00 0.00 0.00 0.00 0.00
October 0.241601E+10 3550.96 30-OCT-07:23 0.00 0.00 0.00 0.00 0.00
November 0.426979E+10 13430.47 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.780977E+10 17874.70 26-DEC-07:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.422034E+11              
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.943985E+10 23309.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AHU-1_COOLC DXCOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.613024E+09 0.585041E+09 15309.37 19-JAN-07:01 15309.37 0.00
February 0.00 0.00 0.465325E+10 0.463282E+10 36122.53 28-FEB-15:02 36122.53 0.00
March 0.00 0.00 0.941316E+10 0.927986E+10 42075.97 31-MAR-17:00 42075.97 0.00
April 0.00 0.00 0.336983E+11 0.328879E+11 69657.50 13-APR-16:00 69657.50 0.00
May 0.00 0.00 0.912710E+11 0.814013E+11 117341.08 25-MAY-16:00 92387.04 0.00
June 0.00 0.00 0.150507E+12 0.107982E+12 166941.85 30-JUN-16:00 101555.94 0.00
July 0.00 0.00 0.183454E+12 0.120141E+12 157698.56 15-JUL-14:00 83739.79 0.00
August 0.00 0.00 0.163446E+12 0.112167E+12 150528.89 08-AUG-15:00 96340.53 0.00
September 0.00 0.00 0.875521E+11 0.704994E+11 109417.67 01-SEP-14:05 87631.60 0.00
October 0.00 0.00 0.394280E+11 0.365304E+11 77081.77 19-OCT-14:05 76105.25 0.00
November 0.00 0.00 0.185569E+11 0.172511E+11 71316.21 21-NOV-13:05 51253.35 0.00
December 0.00 0.00 0.128082E+10 0.122295E+10 20467.11 05-DEC-07:01 20467.11 0.00
                 
Annual Sum or Average     0.783874E+12 0.594580E+12        
Minimum of Months 0.00 0.00 0.613024E+09 0.585041E+09 15309.37   15309.37 0.00
Maximum of Months 0.00 0.00 0.183454E+12 0.120141E+12 166941.85   101555.94 0.00



Table of Contents

Report: CoilReportMonthly

For: AHU-2_COOLC DXCOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum}[W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.662896E+09 0.662896E+09 23158.76 28-FEB-15:40 23158.76 0.00
March 0.00 0.00 0.190342E+10 0.190342E+10 40337.91 31-MAR-16:00 40337.91 0.00
April 0.00 0.00 0.186185E+11 0.185119E+11 82056.76 13-APR-15:00 82056.76 0.00
May 0.00 0.00 0.664248E+11 0.610321E+11 142397.30 25-MAY-16:00 118141.60 0.00
June 0.00 0.00 0.123370E+12 0.963661E+11 210291.37 30-JUN-06:01 136660.43 0.00
July 0.00 0.00 0.154804E+12 0.117886E+12 183194.25 15-JUL-14:00 100282.11 0.00
August 0.00 0.00 0.134127E+12 0.960643E+11 182278.61 08-AUG-15:00 122539.30 0.00
September 0.00 0.00 0.462269E+11 0.390028E+11 131397.20 01-SEP-14:05 111395.51 0.00
October 0.00 0.00 0.133119E+11 0.130443E+11 92656.15 19-OCT-15:00 92656.15 0.00
November 0.00 0.00 0.344317E+10 0.315634E+10 50098.43 01-NOV-15:00 42960.77 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average     0.562893E+12 0.447631E+12        
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.154804E+12 0.117886E+12 210291.37   136660.43 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1592.48 5747.52 01-JAN-10:15 3089.79 14201.37 23-JAN-13:09
February 1849.73 5741.92 01-FEB-05:50 3099.53 14441.62 13-FEB-13:07
March 2198.82 5743.37 31-MAR-00:40 3263.44 12995.32 02-MAR-11:27
April 2446.20 5749.67 30-APR-09:10 2793.34 12721.78 03-APR-10:50
May 2387.80 5758.20 31-MAY-00:40 2777.67 12219.70 01-MAY-12:40
June 2436.03 5766.20 30-JUN-00:40 2624.59 11527.27 01-JUN-12:30
July 2475.37 5771.98 31-JUL-04:10 2133.82 10832.79 03-JUL-12:45
August 2449.32 5773.69 27-AUG-11:00 2355.37 10395.53 01-AUG-12:20
September 2532.84 5773.62 01-SEP-00:10 2132.06 10492.67 29-SEP-12:40
October 2425.33 5770.72 01-OCT-10:20 2297.32 11044.87 31-OCT-12:15
November 2304.57 5764.05 01-NOV-00:10 2588.25 11721.77 30-NOV-13:40
December 1880.09 5755.71 01-DEC-01:05 2717.11 13711.54 26-DEC-13:01
             
Annual Sum or Average 2249.50     2653.71    
Minimum of Months 1592.48 5741.92   2132.06 10395.53  
Maximum of Months 2532.84 5773.69   3263.44 14441.62  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 91105.75 246939.17 09-JAN-07:10
February 0.00 0.00 01-FEB-00:10 70865.94 235503.65 14-FEB-07:10
March 0.00 0.00 01-MAR-00:10 49344.86 197440.68 16-MAR-06:03
April 0.00 0.00 01-APR-00:10 21013.97 163945.63 05-APR-05:01
May 0.00 0.00 01-MAY-00:10 9714.38 77045.58 01-MAY-06:01
June 0.00 0.00 01-JUN-00:10 7814.11 37092.26 12-JUN-05:01
July 0.00 0.00 01-JUL-00:10 7102.24 37112.23 10-JUL-05:01
August 0.00 0.00 01-AUG-00:10 6833.49 41605.19 19-AUG-06:03
September 0.00 0.00 01-SEP-00:10 8004.64 52445.56 06-SEP-06:01
October 0.00 0.00 01-OCT-00:02 14944.68 129339.85 30-OCT-05:01
November 0.00 0.00 01-NOV-00:10 35034.44 188932.42 25-NOV-07:08
December 0.00 0.00 01-DEC-00:03 80975.73 235560.92 26-DEC-07:10
             
Annual Sum or Average 0.00     33427.17    
Minimum of Months 0.00 0.00   6833.49 37092.26  
Maximum of Months 0.00 0.00   91105.75 246939.17  



Table of Contents

Report: FanReportMonthly

For: AHU-1_FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.128924E+11 0.91 11876.03 27-JAN-15:02 1.60
February 0.116340E+11 0.91 10988.48 10-FEB-16:24 1.53
March 0.126039E+11 0.90 10587.98 13-MAR-06:01 1.49
April 0.113698E+11 0.87 10386.73 04-APR-06:01 1.48
May 0.119504E+11 0.87 10552.15 05-MAY-06:01 1.49
June 0.119191E+11 0.89 10508.65 30-JUN-06:01 1.48
July 0.119722E+11 0.87 10604.51 14-JUL-06:02 1.48
August 0.125313E+11 0.89 10719.50 14-AUG-06:01 1.49
September 0.116311E+11 0.88 10729.11 15-SEP-06:01 1.50
October 0.118017E+11 0.87 10808.77 27-OCT-06:01 1.51
November 0.117165E+11 0.88 10494.33 10-NOV-07:01 1.48
December 0.127322E+11 0.91 11141.42 01-DEC-15:02 1.54
           
Annual Sum or Average 0.144755E+12 0.89      
Minimum of Months 0.113698E+11 0.87 10386.73   1.48
Maximum of Months 0.128924E+11 0.91 11876.03   1.60



Table of Contents

Report: FanReportMonthly

For: AHU-2_FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.124274E+11 0.79 10326.68 09-JAN-07:01 1.26
February 0.119102E+11 0.82 13039.43 08-FEB-15:40 1.45
March 0.143241E+11 0.85 15887.01 31-MAR-15:20 1.64
April 0.147805E+11 0.87 16984.97 21-APR-16:00 1.71
May 0.156379E+11 0.88 17864.68 19-MAY-06:01 1.76
June 0.153518E+11 0.88 21008.74 30-JUN-06:01 1.94
July 0.154143E+11 0.87 17369.05 27-JUL-06:01 1.72
August 0.157728E+11 0.88 17403.74 03-AUG-06:01 1.72
September 0.149147E+11 0.87 16094.32 08-SEP-06:01 1.64
October 0.145988E+11 0.85 15408.48 20-OCT-06:01 1.60
November 0.131981E+11 0.83 13082.93 17-NOV-15:30 1.45
December 0.125219E+11 0.80 10581.43 07-DEC-07:01 1.28
           
Annual Sum or Average 0.170852E+12 0.85      
Minimum of Months 0.119102E+11 0.79 10326.68   1.26
Maximum of Months 0.157728E+11 0.88 21008.74   1.94



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 ANESTHESIA EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.146257E+09 0.69 54.61 01-JAN-00:10 0.69
February 0.132103E+09 0.69 54.61 01-FEB-00:10 0.69
March 0.146257E+09 0.69 54.61 01-MAR-00:10 0.69
April 0.141539E+09 0.69 54.61 01-APR-00:10 0.69
May 0.146257E+09 0.69 54.61 01-MAY-00:10 0.69
June 0.141539E+09 0.68 54.61 01-JUN-00:10 0.69
July 0.146257E+09 0.68 54.61 01-JUL-00:10 0.68
August 0.146257E+09 0.68 54.61 01-AUG-00:10 0.68
September 0.141539E+09 0.68 54.61 01-SEP-00:10 0.68
October 0.146257E+09 0.69 54.61 01-OCT-00:02 0.69
November 0.141539E+09 0.69 54.61 01-NOV-00:10 0.69
December 0.146257E+09 0.69 54.61 01-DEC-00:03 0.69
           
Annual Sum or Average 0.172206E+10 0.69      
Minimum of Months 0.132103E+09 0.68 54.61   0.68
Maximum of Months 0.146257E+09 0.69 54.61   0.69



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 LOBBY TOILET EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 91410565.55 0.69 34.13 01-JAN-00:10 0.69
February 82564381.78 0.69 34.13 01-FEB-00:10 0.69
March 91410565.55 0.69 34.13 01-MAR-00:10 0.69
April 88461837.62 0.69 34.13 01-APR-00:10 0.69
May 91410565.55 0.69 34.13 01-MAY-00:10 0.69
June 88461837.62 0.68 34.13 01-JUN-00:10 0.69
July 91410565.55 0.68 34.13 01-JUL-00:10 0.68
August 91410565.55 0.68 34.13 01-AUG-00:10 0.68
September 88461837.62 0.68 34.13 01-SEP-00:10 0.68
October 91410565.55 0.69 34.13 01-OCT-00:02 0.69
November 88461837.62 0.69 34.13 01-NOV-00:10 0.69
December 91410565.55 0.69 34.13 01-DEC-00:03 0.69
           
Annual Sum or Average 0.107629E+10 0.69      
Minimum of Months 82564381.78 0.68 34.13   0.68
Maximum of Months 91410565.55 0.69 34.13   0.69



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 MRI CONTROL ROOM EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.341343E+09 0.69 127.44 01-JAN-00:10 0.69
February 0.308310E+09 0.69 127.44 01-FEB-00:10 0.69
March 0.341343E+09 0.69 127.44 01-MAR-00:10 0.69
April 0.330332E+09 0.69 127.44 01-APR-00:10 0.69
May 0.341343E+09 0.68 127.44 01-MAY-00:10 0.69
June 0.330332E+09 0.68 127.44 01-JUN-00:10 0.69
July 0.341343E+09 0.68 127.44 01-JUL-00:10 0.68
August 0.341343E+09 0.68 127.44 01-AUG-00:10 0.68
September 0.330332E+09 0.68 127.44 01-SEP-00:10 0.68
October 0.341343E+09 0.69 127.44 01-OCT-00:02 0.69
November 0.330332E+09 0.69 127.44 01-NOV-00:10 0.69
December 0.341343E+09 0.69 127.44 01-DEC-00:03 0.69
           
Annual Sum or Average 0.401904E+10 0.69      
Minimum of Months 0.308310E+09 0.68 127.44   0.68
Maximum of Months 0.341343E+09 0.69 127.44   0.69



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 MRI ROOM EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.359705E+09 0.28 134.30 01-JAN-00:10 0.28
February 0.324894E+09 0.28 134.30 01-FEB-00:10 0.28
March 0.359705E+09 0.28 134.30 01-MAR-00:10 0.28
April 0.348101E+09 0.28 134.30 01-APR-00:10 0.28
May 0.359705E+09 0.28 134.30 01-MAY-00:10 0.28
June 0.348101E+09 0.28 134.30 01-JUN-00:10 0.28
July 0.359705E+09 0.27 134.30 01-JUL-00:10 0.28
August 0.359705E+09 0.27 134.30 01-AUG-00:10 0.28
September 0.348101E+09 0.28 134.30 01-SEP-00:10 0.27
October 0.359705E+09 0.28 134.30 01-OCT-00:02 0.28
November 0.348101E+09 0.28 134.30 01-NOV-00:10 0.28
December 0.359705E+09 0.28 134.30 01-DEC-00:03 0.28
           
Annual Sum or Average 0.423523E+10 0.28      
Minimum of Months 0.324894E+09 0.27 134.30   0.27
Maximum of Months 0.359705E+09 0.28 134.30   0.28



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 MRI TOILET EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 91410565.55 0.69 34.13 01-JAN-00:10 0.69
February 82564381.78 0.69 34.13 01-FEB-00:10 0.69
March 91410565.55 0.69 34.13 01-MAR-00:10 0.69
April 88461837.62 0.69 34.13 01-APR-00:10 0.69
May 91410565.55 0.69 34.13 01-MAY-00:10 0.69
June 88461837.62 0.68 34.13 01-JUN-00:10 0.69
July 91410565.55 0.68 34.13 01-JUL-00:10 0.68
August 91410565.55 0.68 34.13 01-AUG-00:10 0.68
September 88461837.62 0.68 34.13 01-SEP-00:10 0.68
October 91410565.55 0.69 34.13 01-OCT-00:02 0.69
November 88461837.62 0.69 34.13 01-NOV-00:10 0.69
December 91410565.55 0.69 34.13 01-DEC-00:03 0.69
           
Annual Sum or Average 0.107629E+10 0.69      
Minimum of Months 82564381.78 0.68 34.13   0.68
Maximum of Months 91410565.55 0.69 34.13   0.69



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 NURSE TOILET EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 91410565.55 0.69 34.13 01-JAN-00:10 0.69
February 82564381.78 0.69 34.13 01-FEB-00:10 0.69
March 91410565.55 0.69 34.13 01-MAR-00:10 0.69
April 88461837.62 0.69 34.13 01-APR-00:10 0.69
May 91410565.55 0.69 34.13 01-MAY-00:10 0.69
June 88461837.62 0.68 34.13 01-JUN-00:10 0.69
July 91410565.55 0.68 34.13 01-JUL-00:10 0.68
August 91410565.55 0.68 34.13 01-AUG-00:10 0.68
September 88461837.62 0.68 34.13 01-SEP-00:10 0.68
October 91410565.55 0.69 34.13 01-OCT-00:02 0.69
November 88461837.62 0.69 34.13 01-NOV-00:10 0.69
December 91410565.55 0.69 34.13 01-DEC-00:03 0.69
           
Annual Sum or Average 0.107629E+10 0.69      
Minimum of Months 82564381.78 0.68 34.13   0.68
Maximum of Months 91410565.55 0.69 34.13   0.69



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 PRE-OP TOILET EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 91410565.55 0.69 34.13 01-JAN-00:10 0.69
February 82564381.78 0.69 34.13 01-FEB-00:10 0.69
March 91410565.55 0.69 34.13 01-MAR-00:10 0.69
April 88461837.62 0.69 34.13 01-APR-00:10 0.69
May 91410565.55 0.69 34.13 01-MAY-00:10 0.69
June 88461837.62 0.68 34.13 01-JUN-00:10 0.69
July 91410565.55 0.68 34.13 01-JUL-00:10 0.68
August 91410565.55 0.68 34.13 01-AUG-00:10 0.68
September 88461837.62 0.68 34.13 01-SEP-00:10 0.68
October 91410565.55 0.69 34.13 01-OCT-00:02 0.69
November 88461837.62 0.69 34.13 01-NOV-00:10 0.69
December 91410565.55 0.69 34.13 01-DEC-00:03 0.69
           
Annual Sum or Average 0.107629E+10 0.69      
Minimum of Months 82564381.78 0.68 34.13   0.68
Maximum of Months 91410565.55 0.69 34.13   0.69



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 SOIL EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.213291E+09 0.69 79.63 01-JAN-00:10 0.69
February 0.192650E+09 0.69 79.63 01-FEB-00:10 0.69
March 0.213291E+09 0.69 79.63 01-MAR-00:10 0.69
April 0.206411E+09 0.69 79.63 01-APR-00:10 0.69
May 0.213291E+09 0.69 79.63 01-MAY-00:10 0.69
June 0.206411E+09 0.68 79.63 01-JUN-00:10 0.69
July 0.213291E+09 0.68 79.63 01-JUL-00:10 0.68
August 0.213291E+09 0.68 79.63 01-AUG-00:10 0.68
September 0.206411E+09 0.68 79.63 01-SEP-00:10 0.68
October 0.213291E+09 0.69 79.63 01-OCT-00:02 0.69
November 0.206411E+09 0.69 79.63 01-NOV-00:10 0.69
December 0.213291E+09 0.69 79.63 01-DEC-00:03 0.69
           
Annual Sum or Average 0.251133E+10 0.69      
Minimum of Months 0.192650E+09 0.68 79.63   0.68
Maximum of Months 0.213291E+09 0.69 79.63   0.69



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 SOIL HOLD EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 94796142.05 0.69 35.39 01-JAN-00:10 0.69
February 85622321.85 0.69 35.39 01-FEB-00:10 0.69
March 94796142.05 0.69 35.39 01-MAR-00:10 0.69
April 91738201.98 0.69 35.39 01-APR-00:10 0.69
May 94796142.05 0.69 35.39 01-MAY-00:10 0.69
June 91738201.98 0.68 35.39 01-JUN-00:10 0.69
July 94796142.05 0.68 35.39 01-JUL-00:10 0.68
August 94796142.05 0.68 35.39 01-AUG-00:10 0.68
September 91738201.98 0.68 35.39 01-SEP-00:10 0.68
October 94796142.05 0.69 35.39 01-OCT-00:02 0.69
November 91738201.98 0.69 35.39 01-NOV-00:10 0.69
December 94796142.05 0.69 35.39 01-DEC-00:03 0.69
           
Annual Sum or Average 0.111615E+10 0.69      
Minimum of Months 85622321.85 0.68 35.39   0.68
Maximum of Months 94796142.05 0.69 35.39   0.69



Table of Contents

Report: FanReportMonthly

For: FLOOR 1 SOIL WORK EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.304702E+09 0.69 113.76 01-JAN-00:10 0.69
February 0.275215E+09 0.69 113.76 01-FEB-00:10 0.69
March 0.304702E+09 0.69 113.76 01-MAR-00:10 0.69
April 0.294873E+09 0.69 113.76 01-APR-00:10 0.69
May 0.304702E+09 0.69 113.76 01-MAY-00:10 0.69
June 0.294873E+09 0.68 113.76 01-JUN-00:10 0.69
July 0.304702E+09 0.68 113.76 01-JUL-00:10 0.68
August 0.304702E+09 0.68 113.76 01-AUG-00:10 0.68
September 0.294873E+09 0.68 113.76 01-SEP-00:10 0.68
October 0.304702E+09 0.69 113.76 01-OCT-00:02 0.69
November 0.294873E+09 0.69 113.76 01-NOV-00:10 0.69
December 0.304702E+09 0.69 113.76 01-DEC-00:03 0.69
           
Annual Sum or Average 0.358762E+10 0.69      
Minimum of Months 0.275215E+09 0.68 113.76   0.68
Maximum of Months 0.304702E+09 0.69 113.76   0.69



Table of Contents

Report: FanReportMonthly

For: FLOOR 2 CONFERENCE TOILET EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 43684858.09 0.28 40.45 02-JAN-06:01 0.69
February 40190069.44 0.28 40.45 01-FEB-06:01 0.69
March 47179646.73 0.30 40.45 01-MAR-06:01 0.69
April 43684858.09 0.29 40.45 01-APR-05:01 0.69
May 45432252.41 0.29 40.45 01-MAY-05:01 0.69
June 45432252.41 0.30 40.45 01-JUN-05:01 0.68
July 43684858.09 0.27 40.45 01-JUL-05:01 0.68
August 47179646.73 0.30 40.45 01-AUG-05:01 0.68
September 43684858.09 0.29 40.45 01-SEP-05:01 0.68
October 43684858.09 0.28 40.45 02-OCT-05:01 0.69
November 41937463.76 0.28 40.45 01-NOV-05:01 0.68
December 43684858.09 0.28 40.45 01-DEC-06:01 0.69
           
Annual Sum or Average 0.529460E+09 0.29      
Minimum of Months 40190069.44 0.27 40.45   0.68
Maximum of Months 47179646.73 0.30 40.45   0.69



Table of Contents

Report: FanReportMonthly

For: FLOOR 2 RECEPTION TOILET EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 86004564.36 0.28 79.63 02-JAN-06:01 0.69
February 79124199.21 0.28 79.63 01-FEB-06:01 0.69
March 92884929.51 0.30 79.63 01-MAR-06:01 0.69
April 86004564.36 0.29 79.63 01-APR-05:01 0.69
May 89444746.93 0.29 79.63 01-MAY-05:01 0.69
June 89444746.93 0.30 79.63 01-JUN-05:01 0.68
July 86004564.36 0.27 79.63 01-JUL-05:01 0.68
August 92884929.51 0.30 79.63 01-AUG-05:01 0.68
September 86004564.36 0.29 79.63 01-SEP-05:01 0.68
October 86004564.36 0.28 79.63 02-OCT-05:01 0.69
November 82564381.78 0.28 79.63 01-NOV-05:01 0.68
December 86004564.36 0.28 79.63 01-DEC-06:01 0.69
           
Annual Sum or Average 0.104238E+10 0.29      
Minimum of Months 79124199.21 0.27 79.63   0.68
Maximum of Months 92884929.51 0.30 79.63   0.69



Table of Contents

Report: FanReportMonthly

For: FLOOR 2 WORK TOILET EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 36859099.01 0.28 34.13 02-JAN-06:01 0.69
February 33910371.09 0.28 34.13 01-FEB-06:01 0.69
March 39807826.93 0.30 34.13 01-MAR-06:01 0.69
April 36859099.01 0.29 34.13 01-APR-05:01 0.69
May 38333462.97 0.29 34.13 01-MAY-05:01 0.69
June 38333462.97 0.30 34.13 01-JUN-05:01 0.68
July 36859099.01 0.27 34.13 01-JUL-05:01 0.68
August 39807826.93 0.30 34.13 01-AUG-05:01 0.68
September 36859099.01 0.29 34.13 01-SEP-05:01 0.68
October 36859099.01 0.28 34.13 02-OCT-05:01 0.69
November 35384735.05 0.28 34.13 01-NOV-05:01 0.68
December 36859099.01 0.28 34.13 01-DEC-06:01 0.69
           
Annual Sum or Average 0.446732E+09 0.29      
Minimum of Months 33910371.09 0.27 34.13   0.68
Maximum of Months 39807826.93 0.30 34.13   0.69



Table of Contents

Report: FanReportMonthly

For: FLOOR 2 X-RAY EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.296685E+09 0.11 274.71 02-JAN-06:01 0.28
February 0.272950E+09 0.11 274.71 01-FEB-06:01 0.28
March 0.320420E+09 0.12 274.71 01-MAR-06:01 0.28
April 0.296685E+09 0.12 274.71 01-APR-05:01 0.28
May 0.308553E+09 0.12 274.71 01-MAY-05:01 0.28
June 0.308553E+09 0.12 274.71 01-JUN-05:01 0.28
July 0.296685E+09 0.11 274.71 01-JUL-05:01 0.27
August 0.320420E+09 0.12 274.71 01-AUG-05:01 0.27
September 0.296685E+09 0.11 274.71 01-SEP-05:01 0.27
October 0.296685E+09 0.11 274.71 02-OCT-05:01 0.28
November 0.284818E+09 0.11 274.71 01-NOV-05:01 0.28
December 0.296685E+09 0.11 274.71 01-DEC-06:01 0.28
           
Annual Sum or Average 0.359582E+10 0.11      
Minimum of Months 0.272950E+09 0.11 274.71   0.27
Maximum of Months 0.320420E+09 0.12 274.71   0.28



Table of Contents

Report: FanReportMonthly

For: FLOOR 3 LOUNGE TOILET EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.131055E+09 0.28 121.35 02-JAN-06:01 0.69
February 0.120570E+09 0.28 121.35 01-FEB-06:01 0.69
March 0.141539E+09 0.30 121.35 01-MAR-06:01 0.69
April 0.131055E+09 0.29 121.35 01-APR-05:01 0.69
May 0.136297E+09 0.29 121.35 01-MAY-05:01 0.69
June 0.136297E+09 0.30 121.35 01-JUN-05:01 0.68
July 0.131055E+09 0.27 121.35 01-JUL-05:01 0.68
August 0.141539E+09 0.30 121.35 01-AUG-05:01 0.68
September 0.131055E+09 0.29 121.35 01-SEP-05:01 0.68
October 0.131055E+09 0.28 121.35 02-OCT-05:01 0.69
November 0.125812E+09 0.28 121.35 01-NOV-05:01 0.68
December 0.131055E+09 0.28 121.35 01-DEC-06:01 0.69
           
Annual Sum or Average 0.158838E+10 0.29      
Minimum of Months 0.120570E+09 0.27 121.35   0.68
Maximum of Months 0.141539E+09 0.30 121.35   0.69



Table of Contents

Report: FanReportMonthly

For: FLOOR 3 OFFICE TOILET EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 36859099.01 0.28 34.13 02-JAN-06:01 0.69
February 33910371.09 0.28 34.13 01-FEB-06:01 0.69
March 39807826.93 0.30 34.13 01-MAR-06:01 0.69
April 36859099.01 0.29 34.13 01-APR-05:01 0.69
May 38333462.97 0.29 34.13 01-MAY-05:01 0.69
June 38333462.97 0.30 34.13 01-JUN-05:01 0.68
July 36859099.01 0.27 34.13 01-JUL-05:01 0.68
August 39807826.93 0.30 34.13 01-AUG-05:01 0.68
September 36859099.01 0.29 34.13 01-SEP-05:01 0.68
October 36859099.01 0.28 34.13 02-OCT-05:01 0.69
November 35384735.05 0.28 34.13 01-NOV-05:01 0.68
December 36859099.01 0.28 34.13 01-DEC-06:01 0.69
           
Annual Sum or Average 0.446732E+09 0.29      
Minimum of Months 33910371.09 0.27 34.13   0.68
Maximum of Months 39807826.93 0.30 34.13   0.69



Table of Contents

Report: FanReportMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET EXHAUST FAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

FAN ELECTRIC ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRIC POWER {Maximum}[W] FAN ELECTRIC POWER {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 57336376.24 0.28 53.09 02-JAN-06:01 0.69
February 52749466.14 0.28 53.09 01-FEB-06:01 0.69
March 61923286.34 0.30 53.09 01-MAR-06:01 0.69
April 57336376.24 0.29 53.09 01-APR-05:01 0.69
May 59629831.29 0.29 53.09 01-MAY-05:01 0.69
June 59629831.29 0.30 53.09 01-JUN-05:01 0.68
July 57336376.24 0.27 53.09 01-JUL-05:01 0.68
August 61923286.34 0.30 53.09 01-AUG-05:01 0.68
September 57336376.24 0.29 53.09 01-SEP-05:01 0.68
October 57336376.24 0.28 53.09 02-OCT-05:01 0.69
November 55042921.19 0.28 53.09 01-NOV-05:01 0.68
December 57336376.24 0.28 53.09 01-DEC-06:01 0.69
           
Annual Sum or Average 0.694917E+09 0.29      
Minimum of Months 52749466.14 0.27 53.09   0.68
Maximum of Months 61923286.34 0.30 53.09   0.69



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PUMP ELECTRIC ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRIC POWER {Maximum}[W] PUMP ELECTRIC POWER {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.125105E+10 0.113721E+10 577.32 01-JAN-00:10 524.79 524.79 72.50 2.21
February 0.963345E+09 0.875681E+09 577.32 01-FEB-00:10 524.79 524.79 72.84 2.21
March 0.866503E+09 0.787652E+09 577.32 04-MAR-23:30 524.79 524.79 72.97 2.21
April 0.544956E+09 0.495365E+09 577.32 05-APR-05:01 524.79 524.79 64.47 2.21
May 0.320084E+09 0.290956E+09 393.14 01-MAY-05:01 357.36 357.36 61.92 0.87
June 0.236557E+09 0.215030E+09 312.16 04-JUN-06:02 283.75 283.75 73.16 0.54
July 0.220901E+09 0.200799E+09 306.70 10-JUL-06:01 278.79 278.79 67.42 0.53
August 0.216501E+09 0.196800E+09 311.05 19-AUG-05:01 282.75 282.75 74.97 0.54
September 0.264572E+09 0.240496E+09 326.29 23-SEP-06:03 296.60 296.60 63.10 0.59
October 0.479222E+09 0.435613E+09 463.63 30-OCT-05:01 421.44 421.44 62.88 1.60
November 0.700078E+09 0.636371E+09 577.32 25-NOV-06:01 524.79 524.79 69.51 2.21
December 0.117663E+10 0.106956E+10 577.32 01-DEC-06:01 524.79 524.79 68.97 2.21
                 
Annual Sum or Average 0.724041E+10 0.658153E+10            
Minimum of Months 0.216501E+09 0.196800E+09 306.70   278.79 278.79 61.92 0.53
Maximum of Months 0.125105E+10 0.113721E+10 577.32   524.79 524.79 74.97 2.21



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PUMP ELECTRIC ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRIC POWER {Maximum}[W] PUMP ELECTRIC POWER {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 18996128.28 5698838.48 8.07 01-JAN-08:62 2.42 2.42 81.29 0.06
February 17341607.26 5202482.18 8.07 01-FEB-00:10 2.42 2.42 1.86 0.00
March 19868776.16 5960632.85 8.07 01-MAR-00:10 2.42 2.42 79.57 0.06
April 18735907.35 5620772.20 8.07 01-APR-00:10 2.42 2.42 81.65 0.06
May 19433057.39 5829917.22 8.07 01-MAY-00:10 2.42 2.42 80.14 0.06
June 19171626.12 5751487.84 8.07 01-JUN-00:10 2.42 2.42 81.70 0.06
July 18997338.61 5699201.58 8.07 01-JUL-00:10 2.42 2.42 81.73 0.06
August 19868776.16 5960632.85 8.07 01-AUG-00:10 2.42 2.42 81.75 0.06
September 18735907.35 5620772.20 8.07 01-SEP-00:10 2.42 2.42 81.76 0.06
October 18997338.61 5699201.58 8.07 01-OCT-07:03 2.42 2.42 81.27 0.06
November 18300188.57 5490056.57 8.07 01-NOV-00:10 2.42 2.42 81.72 0.06
December 18997338.61 5699201.58 8.07 01-DEC-00:03 2.42 2.42 80.21 0.06
                 
Annual Sum or Average 0.227444E+09 68233197.14            
Minimum of Months 17341607.26 5202482.18 8.07   2.42 2.42 1.86 0.00
Maximum of Months 19868776.16 5960632.85 8.07   2.42 2.42 81.76 0.06



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1592.48 5747.52 01-JAN-10:15 81.66 82.22 3089.79 14201.37 23-JAN-13:09
February 1849.73 5741.92 01-FEB-05:50 81.64 82.22 3099.53 14441.62 13-FEB-13:07
March 2198.82 5743.37 31-MAR-00:40 81.65 82.22 3263.44 12995.32 02-MAR-11:27
April 2446.20 5749.67 30-APR-09:10 81.67 82.22 2793.34 12721.78 03-APR-10:50
May 2387.80 5758.20 31-MAY-00:40 81.70 82.22 2777.67 12219.70 01-MAY-12:40
June 2436.03 5766.20 30-JUN-00:40 81.73 82.22 2624.59 11527.27 01-JUN-12:30
July 2475.37 5771.98 31-JUL-04:10 81.75 82.22 2133.82 10832.79 03-JUL-12:45
August 2449.32 5773.69 27-AUG-11:00 81.76 82.22 2355.37 10395.53 01-AUG-12:20
September 2532.84 5773.62 01-SEP-00:10 81.76 82.22 2132.06 10492.67 29-SEP-12:40
October 2425.33 5770.72 01-OCT-10:20 81.75 82.22 2297.32 11044.87 31-OCT-12:15
November 2304.57 5764.05 01-NOV-00:10 81.72 82.22 2588.25 11721.77 30-NOV-13:40
December 1880.09 5755.71 01-DEC-01:05 81.69 82.22 2717.11 13711.54 26-DEC-13:01
                 
Annual Sum or Average 2249.50         2653.71    
Minimum of Months 1592.48 5741.92   81.64 82.22 2132.06 10395.53  
Maximum of Months 2532.84 5773.69   81.76 82.22 3263.44 14441.62  



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 72.50 82.20 91105.75 246939.17 09-JAN-07:10
February 0.00 0.00 01-FEB-00:10 72.84 82.20 70865.94 235503.65 14-FEB-07:10
March 0.00 0.00 01-MAR-00:10 71.57 82.20 49344.86 197440.68 16-MAR-06:03
April 0.00 0.00 01-APR-00:10 76.47 82.20 21013.97 163945.63 05-APR-05:01
May 0.00 0.00 01-MAY-00:10 69.87 82.20 9714.38 77045.58 01-MAY-06:01
June 0.00 0.00 01-JUN-00:10 64.26 82.20 7814.11 37092.26 12-JUN-05:01
July 0.00 0.00 01-JUL-00:10 67.13 82.20 7102.24 37112.23 10-JUL-05:01
August 0.00 0.00 01-AUG-00:10 65.69 82.20 6833.49 41605.19 19-AUG-06:03
September 0.00 0.00 01-SEP-00:10 67.21 82.20 8004.64 52445.56 06-SEP-06:01
October 0.00 0.00 01-OCT-00:02 65.90 82.20 14944.68 129339.85 30-OCT-05:01
November 0.00 0.00 01-NOV-00:10 76.60 82.20 35034.44 188932.42 25-NOV-07:08
December 0.00 0.00 01-DEC-00:03 64.19 82.20 80975.73 235560.92 26-DEC-07:10
                 
Annual Sum or Average 0.00         33427.17    
Minimum of Months 0.00 0.00   64.19 82.20 6833.49 37092.26  
Maximum of Months 0.00 0.00   76.60 82.20 91105.75 246939.17  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 2.07 0.20
February 7.52 0.18
March 7.40 0.22
April 5.00 0.32
May 2.71 0.40
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 3.52 0.43
October 18.25 0.19
November 12.28 0.28
December 0.68 0.12
     
Annual Sum or Average 59.44 0.25
Minimum of Months 0.00 0.00
Maximum of Months 18.25 0.43



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 CAFE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 1.57 13.49
February 1.36 11.76
March 2.52 5.97
April 3.39 6.85
May 3.22 9.65
June 3.17 10.72
July 1.92 9.77
August 2.64 9.00
September 2.52 9.51
October 2.72 8.80
November 2.44 9.76
December 1.17 6.58
     
Annual Sum or Average 28.64 9.16
Minimum of Months 1.17 5.97
Maximum of Months 3.39 13.49



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 CLEAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 3.36 0.22
February 7.74 0.34
March 7.38 0.31
April 15.77 0.22
May 2.26 0.35
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 2.59 0.49
October 18.40 0.22
November 13.96 0.35
December 3.31 1.34
     
Annual Sum or Average 74.77 0.33
Minimum of Months 0.00 0.00
Maximum of Months 18.40 1.34



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 3.19 0.23
February 6.94 0.29
March 7.08 0.38
April 15.21 0.25
May 2.07 0.54
June 0.08 1.65
July 0.08 1.65
August 0.00 0.00
September 2.57 0.68
October 17.64 0.28
November 13.07 0.39
December 2.31 1.69
     
Annual Sum or Average 70.25 0.38
Minimum of Months 0.00 0.00
Maximum of Months 17.64 1.69



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.08 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.08 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.08 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 2.74 0.02
February 2.94 0.00
March 3.07 0.01
April 1.42 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.08 0.00
November 0.69 0.00
December 2.93 0.01
     
Annual Sum or Average 13.88 0.01
Minimum of Months 0.00 0.00
Maximum of Months 3.07 0.02



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.04 0.00
March 0.16 0.00
April 0.07 0.00
May 0.08 0.00
June 0.00 0.00
July 0.08 0.00
August 0.00 0.00
September 0.14 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.58  
Minimum of Months 0.00 0.00
Maximum of Months 0.16 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 3.96 0.00
February 9.15 0.00
March 8.18 0.00
April 14.67 0.00
May 4.34 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 4.00 0.00
October 20.87 0.00
November 14.56 0.00
December 5.74 0.00
     
Annual Sum or Average 85.45  
Minimum of Months 0.00 0.00
Maximum of Months 20.87 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 IT HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.14 0.00
February 0.31 0.14
March 0.36 0.00
April 0.61 0.00
May 0.58 0.00
June 0.33 0.00
July 0.42 0.00
August 0.33 0.00
September 0.31 0.00
October 1.08 0.00
November 0.42 0.00
December 0.14 0.00
     
Annual Sum or Average 5.03 0.01
Minimum of Months 0.14 0.00
Maximum of Months 1.08 0.14



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 LOBBY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.08 1.24
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.08 1.24
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.17 1.24
Minimum of Months 0.00 0.00
Maximum of Months 0.08 1.24



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 2.44 0.00
February 7.34 0.00
March 7.95 0.00
April 5.73 0.00
May 3.20 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 4.30 0.00
October 22.50 0.00
November 16.33 0.00
December 1.41 0.00
     
Annual Sum or Average 71.22  
Minimum of Months 0.00 0.00
Maximum of Months 22.50 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.22 1.98
February 0.18 3.35
March 0.18 3.35
April 0.35 1.98
May 0.31 1.98
June 0.06 1.98
July 0.00 0.00
August 0.11 1.98
September 0.31 1.98
October 0.11 1.98
November 0.00 0.00
December 0.06 1.98
     
Annual Sum or Average 1.88 2.24
Minimum of Months 0.00 0.00
Maximum of Months 0.35 3.35



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.08 2.70
March 0.12 2.16
April 0.04 1.08
May 0.08 1.08
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.08 1.08
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.42 1.73
Minimum of Months 0.00 0.00
Maximum of Months 0.12 2.70



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 MED GAS

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.08 0.00
May 0.17 0.00
June 0.08 0.00
July 0.08 0.00
August 0.00 0.00
September 0.00 0.00
October 0.32 0.00
November 0.76 0.00
December 0.00 0.00
     
Annual Sum or Average 1.50  
Minimum of Months 0.00 0.00
Maximum of Months 0.76 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 1.82 1.16
February 3.77 2.45
March 2.40 1.28
April 2.31 0.62
May 1.79 0.52
June 1.03 0.60
July 1.00 0.46
August 1.25 0.52
September 1.44 0.56
October 1.99 0.55
November 3.81 1.94
December 6.89 2.56
     
Annual Sum or Average 29.51 1.54
Minimum of Months 1.00 0.46
Maximum of Months 6.89 2.56



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 1.14 5.48
February 4.28 7.63
March 4.03 7.38
April 1.28 3.29
May 0.75 0.98
June 0.67 1.54
July 0.75 1.03
August 0.67 1.16
September 1.00 1.32
October 1.25 2.06
November 5.24 7.21
December 8.57 7.72
     
Annual Sum or Average 29.62 6.21
Minimum of Months 0.67 0.98
Maximum of Months 8.57 7.72



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.06 0.00
February 0.34 0.00
March 0.06 0.00
April 0.20 0.00
May 0.08 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.14 0.00
October 0.18 0.00
November 0.36 0.00
December 0.06 0.00
     
Annual Sum or Average 1.47  
Minimum of Months 0.00 0.00
Maximum of Months 0.36 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.08 3.28
February 0.14 2.40
March 0.08 1.82
April 0.00 0.00
May 0.08 0.73
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.17 0.73
October 0.00 0.00
November 0.00 0.00
December 0.14 3.28
     
Annual Sum or Average 0.69 2.01
Minimum of Months 0.00 0.00
Maximum of Months 0.17 3.28



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.08 2.61
March 0.12 2.09
April 0.04 1.04
May 0.25 1.04
June 0.25 1.04
July 0.42 1.04
August 0.50 1.04
September 0.33 1.04
October 0.17 1.04
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 2.17 1.16
Minimum of Months 0.00 0.00
Maximum of Months 0.50 2.61



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 1.14 0.00
February 2.19 0.00
March 2.23 0.00
April 1.48 0.00
May 0.46 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.49 0.00
October 2.46 0.00
November 3.43 0.00
December 1.32 0.00
     
Annual Sum or Average 15.20  
Minimum of Months 0.00 0.00
Maximum of Months 3.43 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 18.46 1.29
February 21.07 2.84
March 21.90 2.91
April 14.19 1.46
May 4.21 1.59
June 2.39 2.30
July 2.17 2.18
August 2.64 1.94
September 2.40 1.87
October 21.61 0.81
November 21.05 3.05
December 19.77 4.62
     
Annual Sum or Average 151.86 2.42
Minimum of Months 2.17 0.81
Maximum of Months 21.90 4.62



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 20.32 1.25
February 22.76 2.81
March 23.67 3.19
April 16.02 1.80
May 4.16 1.58
June 2.39 2.52
July 2.17 2.23
August 2.61 1.90
September 2.97 2.55
October 21.04 0.88
November 23.33 3.17
December 21.42 4.64
     
Annual Sum or Average 162.86 2.55
Minimum of Months 2.17 0.88
Maximum of Months 23.67 4.64



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 23.67 1.00
February 27.94 2.51
March 24.50 3.16
April 23.40 1.14
May 5.43 1.38
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 4.68 1.78
October 29.60 0.95
November 35.43 2.60
December 21.78 4.47
     
Annual Sum or Average 196.43 2.20
Minimum of Months 0.00 0.00
Maximum of Months 35.43 4.47



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 PACU

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 3.61 0.17
February 9.19 0.30
March 8.82 0.31
April 16.51 0.18
May 3.35 0.34
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 2.96 0.44
October 21.05 0.19
November 14.97 0.30
December 3.44 1.06
     
Annual Sum or Average 83.91 0.28
Minimum of Months 0.00 0.00
Maximum of Months 21.05 1.06



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 3.21 0.34
February 8.71 0.33
March 9.69 0.34
April 10.01 0.24
May 3.44 0.29
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 3.58 0.37
October 21.67 0.17
November 15.82 0.35
December 3.62 1.09
     
Annual Sum or Average 79.76 0.32
Minimum of Months 0.00 0.00
Maximum of Months 21.67 1.09



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 3.29 0.21
February 8.63 0.24
March 8.53 0.35
April 16.41 0.28
May 3.35 0.52
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 2.96 0.66
October 21.03 0.30
November 14.96 0.45
December 1.69 0.17
     
Annual Sum or Average 80.85 0.34
Minimum of Months 0.00 0.00
Maximum of Months 21.03 0.66



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.23 0.00
March 0.17 0.00
April 0.03 0.00
May 0.17 0.00
June 0.00 0.00
July 0.04 0.00
August 0.00 0.00
September 0.20 0.00
October 0.78 0.00
November 0.58 0.00
December 0.00 0.00
     
Annual Sum or Average 2.20  
Minimum of Months 0.00 0.00
Maximum of Months 0.78 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 1.57 3.42
February 4.97 2.11
March 8.03 2.62
April 2.80 1.53
May 2.43 1.10
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 2.74 1.17
October 11.93 0.75
November 8.77 2.66
December 7.25 1.50
     
Annual Sum or Average 50.52 1.79
Minimum of Months 0.00 0.00
Maximum of Months 11.93 3.42



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.25 6.62
February 0.14 5.80
March 0.14 5.80
April 0.39 3.05
May 0.64 3.05
June 0.64 3.05
July 0.89 3.05
August 1.00 3.05
September 0.58 3.05
October 0.39 3.05
November 0.06 3.05
December 0.00 0.00
     
Annual Sum or Average 5.11 3.38
Minimum of Months 0.00 0.00
Maximum of Months 1.00 6.62



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 2.16 1.10
February 7.48 1.01
March 7.09 1.08
April 5.03 1.66
May 2.71 2.01
June 0.04 2.16
July 0.00 0.00
August 0.00 0.00
September 3.26 2.14
October 18.51 0.97
November 12.00 1.46
December 0.58 0.54
     
Annual Sum or Average 58.86 1.26
Minimum of Months 0.00 0.00
Maximum of Months 18.51 2.16



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.08 0.00
July 0.17 0.00
August 0.00 0.00
September 0.08 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.33 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.17 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 SCRUB

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 SOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 3.23 0.18
February 7.26 0.26
March 7.22 0.30
April 15.45 0.19
May 2.25 0.39
June 0.33 1.26
July 0.25 1.26
August 0.00 0.00
September 2.78 0.54
October 18.47 0.22
November 13.56 0.32
December 2.72 1.30
     
Annual Sum or Average 73.54 0.31
Minimum of Months 0.00 0.00
Maximum of Months 18.47 1.30



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 2.44 0.19
February 4.09 0.17
March 4.34 0.15
April 6.54 0.12
May 1.51 0.19
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 1.57 0.21
October 8.92 0.12
November 7.74 0.25
December 2.64 0.62
     
Annual Sum or Average 39.78 0.20
Minimum of Months 0.00 0.00
Maximum of Months 8.92 0.62



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 3.19 0.27
February 7.03 0.32
March 6.71 0.34
April 15.35 0.28
May 1.92 0.61
June 0.33 1.80
July 0.25 1.80
August 0.00 0.00
September 2.82 0.83
October 17.44 0.32
November 12.94 0.40
December 1.54 1.17
     
Annual Sum or Average 69.53 0.38
Minimum of Months 0.00 0.00
Maximum of Months 17.44 1.80



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 1.35 0.46
February 2.28 0.81
March 3.86 0.61
April 3.38 0.97
May 1.48 1.13
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 2.53 1.17
October 11.65 0.62
November 7.71 0.99
December 0.29 0.30
     
Annual Sum or Average 34.53 0.80
Minimum of Months 0.00 0.00
Maximum of Months 11.65 1.17



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 1.22 0.00
February 2.24 0.00
March 2.01 0.00
April 1.33 0.00
May 0.17 0.00
June 0.17 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.33 0.00
November 1.15 0.00
December 1.75 0.00
     
Annual Sum or Average 10.37  
Minimum of Months 0.00 0.00
Maximum of Months 2.24 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.08 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.08  
Minimum of Months 0.00 0.00
Maximum of Months 0.08 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.33 0.00
February 0.47 0.00
March 0.17 0.00
April 0.42 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.33 0.00
     
Annual Sum or Average 1.72  
Minimum of Months 0.00 0.00
Maximum of Months 0.47 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.17 0.00
February 0.25 0.00
March 0.08 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.06 0.00
December 0.25 0.00
     
Annual Sum or Average 0.81  
Minimum of Months 0.00 0.00
Maximum of Months 0.25 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 2.04 0.00
February 1.88 0.00
March 1.88 0.00
April 1.10 0.00
May 0.68 0.00
June 0.61 0.00
July 0.99 0.00
August 0.17 0.00
September 0.53 0.00
October 0.67 0.00
November 1.10 0.00
December 1.85 0.00
     
Annual Sum or Average 13.49  
Minimum of Months 0.17 0.00
Maximum of Months 2.04 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.44 4.94
February 0.94 1.38
March 1.06 3.18
April 1.14 3.24
May 1.44 1.62
June 1.08 2.07
July 1.00 3.36
August 1.83 2.14
September 1.69 2.04
October 1.72 3.93
November 1.36 4.49
December 0.94 8.40
     
Annual Sum or Average 14.67 3.18
Minimum of Months 0.44 1.38
Maximum of Months 1.83 8.40



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.04 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.04  
Minimum of Months 0.00 0.00
Maximum of Months 0.04 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.03 1.44
     
Annual Sum or Average 0.03 1.44
Minimum of Months 0.00 0.00
Maximum of Months 0.03 1.44



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.03 1.40
December 0.03 1.40
     
Annual Sum or Average 0.07 1.40
Minimum of Months 0.00 0.00
Maximum of Months 0.03 1.40



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.03 1.08
December 0.03 1.08
     
Annual Sum or Average 0.07 1.08
Minimum of Months 0.00 0.00
Maximum of Months 0.03 1.08



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.06 0.00
December 0.00 0.00
     
Annual Sum or Average 0.06  
Minimum of Months 0.00 0.00
Maximum of Months 0.06 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.03 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.06 0.00
December 0.00 0.00
     
Annual Sum or Average 0.09  
Minimum of Months 0.00 0.00
Maximum of Months 0.06 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.14 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.06 0.00
December 0.08 0.00
     
Annual Sum or Average 0.28  
Minimum of Months 0.00 0.00
Maximum of Months 0.14 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.08 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.06 0.00
December 0.06 0.00
     
Annual Sum or Average 0.19  
Minimum of Months 0.00 0.00
Maximum of Months 0.08 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.08 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.06 0.00
December 0.06 0.00
     
Annual Sum or Average 0.19  
Minimum of Months 0.00 0.00
Maximum of Months 0.08 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.08 0.24
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.08 0.24
Minimum of Months 0.00 0.00
Maximum of Months 0.08 0.24



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.08 0.56
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.08 0.56
Minimum of Months 0.00 0.00
Maximum of Months 0.08 0.56



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.08 5.90
March 0.00 0.00
April 0.08 5.90
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.17 5.90
December 0.00 0.00
     
Annual Sum or Average 0.33 5.90
Minimum of Months 0.00 0.00
Maximum of Months 0.17 5.90



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.08 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.08  
Minimum of Months 0.00 0.00
Maximum of Months 0.08 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 2 X-RAY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.94 1.42
February 1.11 2.28
March 0.76 2.62
April 1.32 2.32
May 2.03 2.71
June 2.12 3.59
July 2.16 2.98
August 2.26 3.16
September 1.61 2.73
October 0.95 2.84
November 1.27 2.30
December 1.18 1.66
     
Annual Sum or Average 17.71 2.69
Minimum of Months 0.76 1.42
Maximum of Months 2.26 3.59



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.08 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.08  
Minimum of Months 0.00 0.00
Maximum of Months 0.08 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 LOCKER

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.17 2.28
February 0.06 2.28
March 0.00 0.00
April 0.11 2.28
May 0.11 2.28
June 0.17 2.28
July 0.00 0.00
August 0.17 2.28
September 0.17 2.28
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.94 2.28
Minimum of Months 0.00 0.00
Maximum of Months 0.17 2.28



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.07 0.00
     
Annual Sum or Average 0.07  
Minimum of Months 0.00 0.00
Maximum of Months 0.07 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 2.89 0.00
February 1.39 0.00
March 0.84 0.00
April 0.69 0.00
May 1.95 0.00
June 1.68 0.00
July 2.14 0.00
August 1.83 0.00
September 0.65 0.00
October 0.84 0.00
November 0.64 0.00
December 2.47 0.00
     
Annual Sum or Average 18.02  
Minimum of Months 0.64 0.00
Maximum of Months 2.89 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.08 5.20
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.03 5.20
     
Annual Sum or Average 0.12 5.20
Minimum of Months 0.00 0.00
Maximum of Months 0.08 5.20



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.03 2.37
     
Annual Sum or Average 0.03 2.37
Minimum of Months 0.00 0.00
Maximum of Months 0.03 2.37



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.03 0.00
     
Annual Sum or Average 0.03  
Minimum of Months 0.00 0.00
Maximum of Months 0.03 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FLOOR 3 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.08 0.57
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.08 0.57
Minimum of Months 0.00 0.00
Maximum of Months 0.08 0.57



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: NE STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.93 0.00
February 1.25 0.00
March 1.06 0.00
April 0.17 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.39 0.00
December 1.02 0.00
     
Annual Sum or Average 4.81  
Minimum of Months 0.00 0.00
Maximum of Months 1.25 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: NW ELEVATOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.67 0.00
February 0.25 0.00
March 0.17 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.42 0.00
     
Annual Sum or Average 1.50  
Minimum of Months 0.00 0.00
Maximum of Months 0.67 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: NW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 1.12 0.00
February 1.86 0.00
March 1.22 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.48 0.00
December 1.32 0.00
     
Annual Sum or Average 6.01  
Minimum of Months 0.00 0.00
Maximum of Months 1.86 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: SW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.33 0.00
February 0.33 0.00
March 0.14 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.08 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.33 0.00
     
Annual Sum or Average 1.22  
Minimum of Months 0.00 0.00
Maximum of Months 0.33 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AHU-1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRIC ENERGY [J] AIR SYSTEM GAS ENERGY [J] AIR SYSTEM WATER VOLUME [m3]
January 0.164393E+12 0.00 0.00 0.859609E+11 0.00 23.60
February 0.120039E+12 0.00 0.00 0.724251E+11 0.00 19.78
March 0.968230E+11 0.00 0.00 0.686647E+11 0.00 17.82
April 0.465961E+11 0.00 0.00 0.566045E+11 0.00 11.93
May 0.255560E+11 0.00 0.00 0.481077E+11 0.00 3.94
June 0.204781E+11 0.00 0.00 0.509345E+11 0.00 0.20
July 0.192789E+11 0.00 0.00 0.580903E+11 0.00 0.00
August 0.184982E+11 0.00 0.00 0.535062E+11 0.00 0.00
September 0.206772E+11 0.00 0.00 0.351125E+11 0.00 0.19
October 0.364119E+11 0.00 0.00 0.372447E+11 0.00 4.60
November 0.718611E+11 0.00 0.00 0.590462E+11 0.00 14.13
December 0.149829E+12 0.00 0.00 0.810154E+11 0.00 22.35
             
Annual Sum or Average 0.790441E+12 0.00 0.00 0.706713E+12 0.00 118.54
Minimum of Months 0.184982E+11 0.00 0.00 0.351125E+11 0.00 0.00
Maximum of Months 0.164393E+12 0.00 0.00 0.859609E+11 0.00 23.60



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AHU-2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRIC ENERGY [J] AIR SYSTEM GAS ENERGY [J] AIR SYSTEM WATER VOLUME [m3]
January 0.649201E+11 0.00 0.00 0.590709E+11 0.00 0.00
February 0.453093E+11 0.00 0.00 0.393850E+11 0.00 0.00
March 0.338843E+11 0.00 0.00 0.343784E+11 0.00 0.00
April 0.852958E+10 0.00 0.00 0.304800E+11 0.00 0.00
May 0.830292E+09 0.00 0.00 0.409974E+11 0.00 0.00
June 49530992.78 0.00 0.00 0.562071E+11 0.00 0.00
July 1489699.29 0.00 0.00 0.655099E+11 0.00 0.00
August 53949433.44 0.00 0.00 0.590137E+11 0.00 0.00
September 0.370261E+09 0.00 0.00 0.338350E+11 0.00 0.00
October 0.415520E+10 0.00 0.00 0.269076E+11 0.00 0.00
November 0.191898E+11 0.00 0.00 0.306922E+11 0.00 0.00
December 0.591617E+11 0.00 0.00 0.511696E+11 0.00 0.00
             
Annual Sum or Average 0.236456E+12 0.00 0.00 0.527647E+12 0.00 0.00
Minimum of Months 1489699.29 0.00 0.00 0.269076E+11 0.00 0.00
Maximum of Months 0.649201E+11 0.00 0.00 0.655099E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AHU-1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.128924E+11 0.613024E+09 0.173833E+12 0.00 0.00 0.631583E+11 0.00 0.00
February 0.116340E+11 0.465325E+10 0.126338E+12 0.00 0.00 0.529261E+11 0.00 0.00
March 0.126039E+11 0.941316E+10 0.102262E+12 0.00 0.00 0.476950E+11 0.00 0.00
April 0.113698E+11 0.336983E+11 0.507092E+11 0.00 0.00 0.319191E+11 0.00 0.00
May 0.119504E+11 0.912710E+11 0.273428E+11 0.00 0.00 0.105416E+11 0.00 0.00
June 0.119191E+11 0.150507E+12 0.207520E+11 0.00 0.00 0.532666E+09 0.00 0.00
July 0.119722E+11 0.183454E+12 0.192789E+11 0.00 0.00 0.00 0.00 0.00
August 0.125313E+11 0.163446E+12 0.184982E+11 0.00 0.00 0.00 0.00 0.00
September 0.116311E+11 0.875521E+11 0.210329E+11 0.00 0.00 0.514766E+09 0.00 0.00
October 0.118017E+11 0.394280E+11 0.388279E+11 0.00 0.00 0.123043E+11 0.00 0.00
November 0.117165E+11 0.185569E+11 0.761309E+11 0.00 0.00 0.378192E+11 0.00 0.00
December 0.127322E+11 0.128082E+10 0.157639E+12 0.00 0.00 0.598204E+11 0.00 0.00
                 
Annual Sum or Average 0.144755E+12 0.783874E+12 0.832645E+12 0.00 0.00 0.317231E+12 0.00 0.00
Minimum of Months 0.113698E+11 0.613024E+09 0.184982E+11 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.128924E+11 0.183454E+12 0.173833E+12 0.00 0.00 0.631583E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AHU-2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.124274E+11 0.00 0.111564E+12 0.00 0.00 0.00 0.00 0.00
February 0.119102E+11 0.662896E+09 0.725868E+11 0.00 0.00 0.00 0.00 0.00
March 0.143241E+11 0.190342E+10 0.533866E+11 0.00 0.00 0.00 0.00 0.00
April 0.147805E+11 0.186185E+11 0.192243E+11 0.00 0.00 0.00 0.00 0.00
May 0.156379E+11 0.664248E+11 0.877820E+10 0.00 0.00 0.00 0.00 0.00
June 0.153518E+11 0.123370E+12 0.900941E+10 0.00 0.00 0.00 0.00 0.00
July 0.154143E+11 0.154804E+12 0.102169E+11 0.00 0.00 0.00 0.00 0.00
August 0.157728E+11 0.134127E+12 0.894448E+10 0.00 0.00 0.00 0.00 0.00
September 0.149147E+11 0.462269E+11 0.719634E+10 0.00 0.00 0.00 0.00 0.00
October 0.145988E+11 0.133119E+11 0.128616E+11 0.00 0.00 0.00 0.00 0.00
November 0.131981E+11 0.344317E+10 0.357017E+11 0.00 0.00 0.00 0.00 0.00
December 0.125219E+11 0.00 0.978095E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.170852E+12 0.562893E+12 0.447279E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.119102E+11 0.00 0.719634E+10 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.157728E+11 0.154804E+12 0.111564E+12 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AHU-1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

AIR SYSTEM FAN ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL GAS ENERGY [J] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] AIR SYSTEM HUMIDIFIER GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J]
January 0.128924E+11 0.164393E+12 0.00 0.00 0.185936E+09 0.943985E+10 0.00 0.00 0.634427E+11 0.00 0.00 0.00
February 0.116340E+11 0.120039E+12 0.00 0.00 0.132739E+10 0.629936E+10 0.00 0.00 0.531643E+11 0.00 0.00 0.00
March 0.126039E+11 0.968230E+11 0.00 0.00 0.271203E+10 0.543910E+10 0.00 0.00 0.479097E+11 0.00 0.00 0.00
April 0.113698E+11 0.465961E+11 0.00 0.00 0.905881E+10 0.411307E+10 0.00 0.00 0.320628E+11 0.00 0.00 0.00
May 0.119504E+11 0.255560E+11 0.00 0.00 0.237815E+11 0.178681E+10 0.00 0.00 0.105890E+11 0.00 0.00 0.00
June 0.119191E+11 0.204781E+11 0.00 0.00 0.382064E+11 0.273938E+09 0.00 0.00 0.535064E+09 0.00 0.00 0.00
July 0.119722E+11 0.192789E+11 0.00 0.00 0.461181E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.125313E+11 0.184982E+11 0.00 0.00 0.409750E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.116311E+11 0.206772E+11 0.00 0.00 0.226086E+11 0.355733E+09 0.00 0.00 0.517084E+09 0.00 0.00 0.00
October 0.118017E+11 0.364119E+11 0.00 0.00 0.106673E+11 0.241601E+10 0.00 0.00 0.123596E+11 0.00 0.00 0.00
November 0.117165E+11 0.718611E+11 0.00 0.00 0.507048E+10 0.426979E+10 0.00 0.00 0.379894E+11 0.00 0.00 0.00
December 0.127322E+11 0.149829E+12 0.00 0.00 0.383754E+09 0.780977E+10 0.00 0.00 0.600897E+11 0.00 0.00 0.00
                         
Annual Sum or Average 0.144755E+12 0.790441E+12 0.00 0.00 0.201095E+12 0.422034E+11 0.00 0.00 0.318659E+12   0.00 0.00
Minimum of Months 0.113698E+11 0.184982E+11 0.00 0.00 0.185936E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.128924E+11 0.164393E+12 0.00 0.00 0.461181E+11 0.943985E+10 0.00 0.00 0.634427E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AHU-2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

AIR SYSTEM FAN ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] AIR SYSTEM HEATING COIL GAS ENERGY [J] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] AIR SYSTEM HUMIDIFIER GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J]
January 0.124274E+11 0.649201E+11 0.00 0.00 0.00 0.466435E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.119102E+11 0.453093E+11 0.00 0.00 0.197300E+09 0.272775E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.143241E+11 0.338843E+11 0.00 0.00 0.551935E+09 0.195023E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.147805E+11 0.852958E+10 0.00 0.00 0.500481E+10 0.106948E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.156379E+11 0.830292E+09 0.00 0.00 0.174116E+11 0.794791E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.153518E+11 49530992.78 0.00 0.00 0.318954E+11 0.895988E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.154143E+11 1489699.29 0.00 0.00 0.398801E+11 0.102154E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.157728E+11 53949433.44 0.00 0.00 0.343504E+11 0.889053E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.149147E+11 0.370261E+09 0.00 0.00 0.120943E+11 0.682607E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.145988E+11 0.415520E+10 0.00 0.00 0.360235E+10 0.870639E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.131981E+11 0.191898E+11 0.00 0.00 0.982193E+09 0.165119E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.125219E+11 0.591617E+11 0.00 0.00 0.00 0.386478E+11 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.170852E+12 0.236456E+12 0.00 0.00 0.145970E+12 0.210824E+12 0.00 0.00 0.00   0.00 0.00
Minimum of Months 0.119102E+11 1489699.29 0.00 0.00 0.00 0.682607E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.157728E+11 0.649201E+11 0.00 0.00 0.398801E+11 0.466435E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 ANESTHESIA

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.288203E+10 0.00 0.00 318153.48 0.00 0.467199E+09 0.507776E+09 0.00 3.10
February 0.251297E+10 0.00 0.00 232613.80 0.00 0.132365E+09 0.426051E+09 0.00 3.09
March 0.233426E+10 0.00 0.00 151517.64 0.00 0.100010E+09 0.401332E+09 0.00 3.10
April 0.150510E+10 0.00 0.00 146231.71 10921484.14 19387279.34 0.238284E+09 0.00 3.18
May 0.617313E+09 31671829.47 33662.55 82240.91 48183138.89 6626513.21 80129888.97 5934.71 3.16
June 0.160084E+09 0.119729E+09 866632.35 71253.16 0.357911E+09 1249259.23 22050915.94 24159.21 3.12
July 57171877.68 0.168616E+09 1029887.78 26533.18 0.610601E+09 447007.42 3390597.77 34078.46 3.18
August 71890435.26 0.148344E+09 374522.58 36999.35 0.318106E+09 753900.77 13542258.49 34575.01 3.13
September 0.421057E+09 14851190.82 28878.24 196104.43 62701299.73 2162504.05 0.111294E+09 5664.93 3.15
October 0.116236E+10 0.00 0.00 238167.49 1289245.03 4988962.02 0.239000E+09 0.00 3.16
November 0.195513E+10 2397.08 0.00 211263.76 0.00 23762838.77 0.336372E+09 0.00 3.15
December 0.294609E+10 0.00 0.00 156492.58 0.00 0.295180E+09 0.431424E+09 0.00 3.10
                   
Annual Sum or Average 0.166255E+11 0.483215E+09 2333583.49 1867571.48 0.140971E+10 0.105413E+10 0.281065E+10 104412.33 3.13
Minimum of Months 57171877.68 0.00 0.00 26533.18 0.00 447007.42 3390597.77 0.00 3.09
Maximum of Months 0.294609E+10 0.168616E+09 1029887.78 318153.48 0.610601E+09 0.467199E+09 0.507776E+09 34575.01 3.18



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 BIO HAZ

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 76794930.36 0.00 0.00 0.00 0.00 75487141.69 0.00 0.00 0.23
February 69868270.88 0.00 0.00 0.00 0.00 42200477.24 0.00 0.00 0.22
March 63339738.55 0.00 0.00 0.00 0.00 37246074.23 0.00 0.00 0.21
April 40325478.13 0.00 0.00 0.00 353396.55 21361420.53 0.00 0.00 0.21
May 16692585.04 0.00 324887.31 0.00 2257109.61 8203539.52 0.00 4670.41 0.21
June 4875285.61 0.00 1980782.91 0.00 13597229.41 1223419.10 0.00 21358.52 0.20
July 1760704.88 0.00 2061562.18 0.00 23291201.18 250750.28 0.00 20401.11 0.20
August 2498573.35 0.00 1309342.85 0.00 13804724.41 328112.67 0.00 15961.53 0.20
September 13291913.97 0.00 257161.90 0.00 2254737.54 4650113.18 0.00 5946.70 0.20
October 34237282.39 0.00 493.60 0.00 41117.99 13876868.62 0.00 105.70 0.21
November 55797317.56 0.00 30.96 0.00 0.00 24207782.69 0.00 46.60 0.21
December 79060630.99 0.00 0.00 0.00 0.00 54372807.23 0.00 0.00 0.21
                   
Annual Sum or Average 0.458543E+09 0.00 5934261.72 0.00 55599516.70 0.283409E+09 0.00 68490.57 0.21
Minimum of Months 1760704.88 0.00 0.00 0.00 0.00 250750.28 0.00 0.00 0.20
Maximum of Months 79060630.99 0.00 2061562.18 0.00 23291201.18 75487141.69 0.00 21358.52 0.23



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 CAFE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.325894E+10 0.00 0.00 7864688.75 0.00 59952709.05 0.486370E+10 0.00 1.66
February 0.256007E+10 0.00 0.00 7844188.63 0.00 272253.10 0.392897E+10 0.00 1.69
March 0.226962E+10 0.00 0.00 8634567.14 0.00 134892.86 0.355492E+10 0.00 1.67
April 0.143501E+10 0.00 0.00 7143226.21 13168738.05 91920.30 0.196859E+10 0.00 1.61
May 0.591982E+09 0.182348E+09 0.00 5509403.51 40688380.73 0.00 0.709370E+09 0.00 1.64
June 0.159906E+09 0.742533E+09 0.00 3543353.08 0.333925E+09 0.00 0.172103E+09 0.00 1.67
July 60987446.03 0.993040E+09 0.00 1628183.17 0.610947E+09 0.00 33382033.63 0.00 1.65
August 72124314.90 0.892681E+09 0.00 2279454.81 0.284035E+09 0.00 95212801.31 0.00 1.75
September 0.395630E+09 89825065.91 0.00 6483077.34 65316682.82 0.00 0.740996E+09 0.00 1.67
October 0.115235E+10 94398.53 0.00 7772669.51 1472723.94 0.00 0.159373E+10 0.00 1.62
November 0.197829E+10 10048.58 0.00 7542330.32 0.00 212212.16 0.247461E+10 0.00 1.63
December 0.318705E+10 0.00 0.00 7338072.52 0.00 5434478.90 0.426777E+10 0.00 1.61
                   
Annual Sum or Average 0.171220E+11 0.290053E+10 0.00 73583214.99 0.134955E+10 66098466.37 0.244034E+11 0.00 1.66
Minimum of Months 60987446.03 0.00 0.00 1628183.17 0.00 0.00 33382033.63 0.00 1.61
Maximum of Months 0.325894E+10 0.993040E+09 0.00 8634567.14 0.610947E+09 59952709.05 0.486370E+10 0.00 1.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 CLEAN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.310415E+10 0.00 0.00 728571.67 0.00 2214600.41 0.856965E+09 0.00 2.74
February 0.244022E+10 0.00 0.00 692912.10 0.00 556815.02 0.715148E+09 0.00 2.74
March 0.223298E+10 0.00 0.00 633735.53 0.00 386655.79 0.680214E+09 0.00 2.74
April 0.145448E+10 0.00 0.00 267300.08 11223686.32 2679722.48 0.354280E+09 0.00 2.81
May 0.591886E+09 32821351.51 56478.32 144755.17 49221870.65 3051268.77 0.128553E+09 5582.31 2.78
June 0.156426E+09 0.130755E+09 1383893.83 100910.44 0.359610E+09 1327952.36 30677329.40 23483.15 2.75
July 58118319.69 0.180953E+09 2716344.93 27815.82 0.618169E+09 613736.60 3965036.89 34149.95 2.80
August 72936536.05 0.153675E+09 816170.64 48907.38 0.325259E+09 903321.54 14720673.02 27949.25 2.76
September 0.424126E+09 15190877.87 45113.74 184681.95 64493892.47 2987989.16 0.122207E+09 4016.40 2.78
October 0.115291E+10 12374.29 0.00 238307.81 1312544.71 2859892.27 0.289502E+09 0.00 2.78
November 0.191736E+10 2463.41 0.00 310536.04 0.00 950399.55 0.460916E+09 0.00 2.78
December 0.295388E+10 0.00 0.00 749654.35 0.00 505163.31 0.819345E+09 0.00 2.74
                   
Annual Sum or Average 0.165595E+11 0.513411E+09 5018001.47 4128088.32 0.142929E+10 19037517.26 0.447649E+10 95181.06 2.77
Minimum of Months 58118319.69 0.00 0.00 27815.82 0.00 386655.79 3965036.89 0.00 2.74
Maximum of Months 0.310415E+10 0.180953E+09 2716344.93 749654.35 0.618169E+09 3051268.77 0.856965E+09 34149.95 2.81



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 CLEAN WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.398536E+10 0.00 0.00 507478.50 0.00 8051582.34 0.898295E+09 0.00 2.58
February 0.313502E+10 0.00 0.00 469866.57 0.00 2507131.42 0.757721E+09 0.00 2.58
March 0.286042E+10 0.00 0.00 410161.58 0.00 2858950.60 0.732877E+09 0.00 2.58
April 0.184444E+10 0.00 0.00 199909.38 13851633.10 12847865.61 0.378409E+09 0.00 2.65
May 0.771275E+09 39135300.47 133755.81 110935.04 62034043.60 10212083.21 0.111472E+09 26554.22 2.62
June 0.201398E+09 0.129721E+09 4131726.32 82078.28 0.472986E+09 3836751.78 27358372.75 78739.98 2.59
July 72102058.51 0.154070E+09 12881315.02 23838.95 0.822566E+09 1671893.94 3613711.45 107766.77 2.64
August 90022052.96 0.154247E+09 3281790.83 43399.88 0.434494E+09 2281793.14 17009465.26 91976.05 2.60
September 0.545657E+09 14386982.66 96779.80 153264.70 83908280.14 8563070.14 0.123795E+09 10986.79 2.61
October 0.148129E+10 0.00 0.00 188970.63 1635139.41 10633055.10 0.291857E+09 0.00 2.62
November 0.243726E+10 3040.19 0.00 225523.33 0.00 4909615.25 0.494302E+09 0.00 2.62
December 0.376948E+10 0.00 0.00 489740.60 0.00 3095581.39 0.885180E+09 0.00 2.58
                   
Annual Sum or Average 0.211937E+11 0.491562E+09 20525367.78 2905167.44 0.189148E+10 71469373.92 0.472189E+10 316023.82 2.61
Minimum of Months 72102058.51 0.00 0.00 23838.95 0.00 1671893.94 3613711.45 0.00 2.58
Maximum of Months 0.398536E+10 0.154247E+09 12881315.02 507478.50 0.822566E+09 12847865.61 0.898295E+09 107766.77 2.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.432107E+09 0.00 0.00 537109.78 0.00 0.00 0.368677E+09 0.00 0.54
February 0.341363E+09 0.00 0.00 588644.17 0.00 0.00 0.317096E+09 0.00 0.56
March 0.308527E+09 0.00 0.00 644798.55 0.00 0.00 0.270121E+09 0.00 0.54
April 0.199801E+09 0.00 0.00 376895.76 1647038.64 0.00 0.110401E+09 0.00 0.48
May 82354993.27 7818593.00 0.00 211650.66 7140722.75 784375.97 30486242.76 0.00 0.45
June 22133922.75 30408834.47 0.00 132655.49 50598750.27 0.00 7668755.83 0.00 0.44
July 8270736.16 38054761.99 0.00 41017.18 88439301.58 0.00 1008454.97 0.00 0.44
August 10290327.69 33846953.18 0.00 70909.75 46581778.97 0.00 4154080.76 0.00 0.45
September 59123193.45 3292565.79 0.00 234636.66 9296849.10 716159.39 30372980.02 0.00 0.45
October 0.161792E+09 2296.91 0.00 321030.35 191634.34 945711.53 73888402.74 0.00 0.46
November 0.266563E+09 266.56 0.00 422253.14 0.00 0.00 0.146719E+09 0.00 0.49
December 0.414132E+09 0.00 0.00 611556.26 0.00 0.00 0.356575E+09 0.00 0.55
                   
Annual Sum or Average 0.230646E+10 0.113424E+09 0.00 4193157.76 0.203896E+09 2446246.89 0.171717E+10 0.00 0.49
Minimum of Months 8270736.16 0.00 0.00 41017.18 0.00 0.00 1008454.97 0.00 0.44
Maximum of Months 0.432107E+09 38054761.99 0.00 644798.55 88439301.58 945711.53 0.368677E+09 0.00 0.56



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 24664398.88 0.00 0.00 0.00 0.00 0.305578E+09 0.00 0.00 0.61
February 29846200.73 0.00 0.00 0.00 0.00 0.205059E+09 0.00 0.00 0.55
March 38722406.14 0.00 0.00 0.00 0.00 0.171282E+09 0.00 0.00 0.53
April 47712565.36 0.00 0.00 0.00 714626.02 69366717.16 0.00 0.00 0.50
May 34223573.29 1035153.05 10358.32 1.23 3671136.42 10809793.30 610.93 464.93 0.47
June 10986224.03 7050630.56 306000.64 2582.78 24608381.41 571868.50 120395.29 2950.41 0.48
July 3791659.79 12242109.54 18941.58 3199.21 40304443.71 55989.00 100775.52 624.95 0.50
August 5185148.89 12340248.47 3786.05 3166.94 21213322.45 95984.16 216047.71 132.83 0.51
September 31139459.96 935520.95 310.84 9930.79 4216393.73 776101.99 1643527.78 3.54 0.48
October 79205693.89 0.00 0.00 1548.80 83935.23 9117039.20 160880.83 0.00 0.47
November 89343883.93 0.00 0.00 107.35 0.00 59429979.81 25579.27 0.00 0.48
December 55093631.11 0.00 0.00 0.00 0.00 0.222677E+09 0.00 0.00 0.54
                   
Annual Sum or Average 0.449915E+09 33603662.56 339397.42 20537.11 94812238.97 0.105482E+10 2267817.33 4176.66 0.51
Minimum of Months 3791659.79 0.00 0.00 0.00 0.00 55989.00 0.00 0.00 0.47
Maximum of Months 89343883.93 12340248.47 306000.64 9930.79 40304443.71 0.305578E+09 1643527.78 2950.41 0.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.538580E+09 0.00 0.00 633922.26 0.00 312287.66 0.448096E+09 0.00 0.86
February 0.427398E+09 0.00 0.00 650791.44 0.00 39412.63 0.355813E+09 0.00 0.86
March 0.385385E+09 0.00 0.00 739054.44 0.00 20668.21 0.312606E+09 0.00 0.85
April 0.242466E+09 0.00 0.00 654813.43 2017706.90 71590.37 0.180458E+09 0.00 0.86
May 95763893.43 18365155.70 0.00 563135.79 8618319.29 0.00 72754660.60 0.00 0.90
June 25434822.18 83295995.72 0.00 407712.41 59609924.54 0.00 20235869.01 0.00 0.95
July 9461118.18 0.120439E+09 0.00 202325.12 0.104271E+09 0.00 4108796.86 0.00 0.98
August 11527490.55 0.100355E+09 0.00 288236.28 55434899.26 0.00 11474341.06 0.00 1.02
September 67172473.10 9461787.48 0.00 728792.65 11207249.17 0.00 80560764.92 0.00 0.94
October 0.190915E+09 6109.59 0.00 808565.91 234761.91 0.00 0.164294E+09 0.00 0.89
November 0.322389E+09 1066.57 0.00 762013.01 0.00 0.00 0.248374E+09 0.00 0.88
December 0.513163E+09 0.00 0.00 719251.18 0.00 0.00 0.437701E+09 0.00 0.88
                   
Annual Sum or Average 0.282966E+10 0.331924E+09 0.00 7158613.91 0.241394E+09 443958.87 0.233648E+10 0.00 0.91
Minimum of Months 9461118.18 0.00 0.00 202325.12 0.00 0.00 4108796.86 0.00 0.85
Maximum of Months 0.538580E+09 0.120439E+09 0.00 808565.91 0.104271E+09 312287.66 0.448096E+09 0.00 1.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.223744E+10 0.00 0.00 7549587.64 0.00 0.165690E+09 0.586349E+10 0.00 7.81
February 0.187251E+10 0.00 0.00 7135478.86 0.00 42811328.66 0.448577E+10 0.00 7.68
March 0.171989E+10 0.00 0.00 8092260.48 0.00 32437297.84 0.392782E+10 0.00 7.56
April 0.114172E+10 3180141.61 0.00 6580785.78 10082064.13 25795635.10 0.206362E+10 0.00 7.07
May 0.490287E+09 0.188310E+09 0.00 4728056.02 23460890.53 7036363.27 0.688906E+09 0.00 7.09
June 0.135909E+09 0.808352E+09 227791.78 2774045.43 0.213596E+09 321941.44 0.162650E+09 2938.48 7.24
July 54272647.25 0.117124E+10 348315.69 928915.90 0.383751E+09 208358.48 30173859.83 5029.21 7.14
August 49889252.79 0.997508E+09 13893.55 1383151.91 0.128432E+09 82718.54 97900539.72 892.88 7.49
September 0.271601E+09 99587211.99 0.00 5708813.48 47975687.69 687265.51 0.759655E+09 0.00 7.21
October 0.821354E+09 136161.58 0.00 7824003.58 1470893.13 1814198.52 0.188439E+10 0.00 7.32
November 0.132680E+10 8355.86 0.00 7825960.15 0.00 2292247.93 0.328492E+10 0.00 7.69
December 0.212846E+10 0.00 0.00 7940370.00 0.00 81923903.99 0.555916E+10 0.00 7.82
                   
Annual Sum or Average 0.122501E+11 0.326832E+10 590001.01 68471429.22 0.808769E+09 0.361102E+09 0.288085E+11 8860.57 7.43
Minimum of Months 49889252.79 0.00 0.00 928915.90 0.00 82718.54 30173859.83 0.00 7.07
Maximum of Months 0.223744E+10 0.117124E+10 348315.69 8092260.48 0.383751E+09 0.165690E+09 0.586349E+10 5029.21 7.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.205925E+09 0.00 0.00 307559.18 0.00 0.00 0.207900E+09 0.00 0.65
February 0.162261E+09 0.00 0.00 337367.05 0.00 0.00 0.180549E+09 0.00 0.68
March 0.146181E+09 0.00 0.00 380307.51 0.00 0.00 0.157667E+09 0.00 0.66
April 93980256.02 0.00 0.00 245108.90 792143.85 0.00 68223374.20 0.00 0.58
May 38409653.85 4601495.38 0.00 146744.13 3421619.73 0.00 20142631.56 0.00 0.55
June 10373352.88 18468258.05 0.00 91042.93 23992199.06 0.00 4961904.92 0.00 0.54
July 3900617.16 23925040.50 0.00 32428.61 41423674.52 0.00 690617.58 0.00 0.53
August 4815061.46 20375046.70 0.00 54223.44 22152899.09 0.00 2678377.09 0.00 0.54
September 27636468.57 1980171.56 0.00 161068.64 4459404.92 0.00 19441404.57 0.00 0.54
October 76494439.16 1628.37 0.00 212911.99 92166.61 0.00 46251196.45 0.00 0.55
November 0.126534E+09 165.30 0.00 264452.20 0.00 0.00 89662969.45 0.00 0.60
December 0.196773E+09 0.00 0.00 351026.25 0.00 0.00 0.204227E+09 0.00 0.67
                   
Annual Sum or Average 0.109328E+10 69351805.86 0.00 2584240.83 96334107.77 0.00 0.100240E+10 0.00 0.59
Minimum of Months 3900617.16 0.00 0.00 32428.61 0.00 0.00 690617.58 0.00 0.53
Maximum of Months 0.205925E+09 23925040.50 0.00 380307.51 41423674.52 0.00 0.207900E+09 0.00 0.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 IT HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.347373E+09 0.00 0.00 1425.44 0.00 80757316.28 3168788.80 0.00 0.27
February 0.287369E+09 0.00 0.00 764.95 0.00 44403393.08 2350013.64 0.00 0.26
March 0.264356E+09 0.00 0.00 0.00 0.00 51578028.17 0.00 0.00 0.27
April 0.149181E+09 0.00 0.00 0.00 1099359.01 70534035.07 0.00 0.00 0.31
May 55386954.82 0.00 1723781.27 0.00 7333582.06 38679785.05 0.00 47775.20 0.31
June 15715971.51 0.00 15612482.07 0.00 41825612.74 6876849.72 0.00 246077.30 0.30
July 5396700.73 0.00 29294234.29 0.00 66708657.88 1867995.36 0.00 293053.00 0.31
August 7843249.27 0.00 15633599.33 0.00 40634435.07 2090091.90 0.00 265889.75 0.30
September 43559932.44 0.00 2061742.73 0.00 6956241.53 25660143.26 0.00 72473.18 0.31
October 0.116434E+09 0.00 3550.69 0.00 127911.35 62883184.45 0.00 1110.16 0.31
November 0.204705E+09 0.00 259.27 0.00 0.00 69657393.56 0.00 343.96 0.29
December 0.342640E+09 0.00 0.00 1389.34 0.00 49750720.41 3136083.97 0.00 0.26
                   
Annual Sum or Average 0.183996E+10 0.00 64329649.64 3579.72 0.164686E+09 0.504739E+09 8654886.41 926722.55 0.29
Minimum of Months 5396700.73 0.00 0.00 0.00 0.00 1867995.36 0.00 0.00 0.26
Maximum of Months 0.347373E+09 0.00 29294234.29 1425.44 66708657.88 80757316.28 3168788.80 293053.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 IT ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.340844E+09 0.00 0.00 28584.79 0.00 0.109897E+09 26512695.21 0.00 0.37
February 0.280734E+09 0.00 0.00 45487.45 0.00 40715988.30 31881620.01 0.00 0.34
March 0.255336E+09 0.00 0.00 45263.49 0.00 32152434.31 31406666.35 0.00 0.34
April 0.158686E+09 0.00 0.00 30416.40 1199448.81 31171118.39 15497699.01 0.00 0.36
May 62193482.81 3258477.82 61857.95 22369.77 5337429.55 21020109.80 4239573.12 10452.22 0.36
June 16754543.67 12871373.78 4156153.18 25945.96 38710117.26 2353982.56 2171841.12 52017.50 0.35
July 5995657.61 16889994.33 3821354.61 8537.43 67049671.82 958222.08 255856.24 28317.05 0.35
August 7530421.52 15507926.49 1146868.04 20519.08 35904133.67 703142.21 1756812.80 16245.33 0.35
September 44956885.14 1141769.14 170163.78 46533.21 7334207.39 10004693.45 8432990.79 3760.54 0.35
October 0.124537E+09 0.00 0.00 41228.82 140879.30 27797847.37 13798303.01 0.00 0.36
November 0.212166E+09 0.00 0.00 43504.59 0.00 26085128.90 23755871.44 0.00 0.35
December 0.336473E+09 0.00 0.00 62184.74 0.00 42150220.83 41337511.52 0.00 0.34
                   
Annual Sum or Average 0.184621E+10 49669541.56 9356397.57 420575.73 0.155676E+09 0.345010E+09 0.201047E+09 110792.64 0.35
Minimum of Months 5995657.61 0.00 0.00 8537.43 0.00 703142.21 255856.24 0.00 0.34
Maximum of Months 0.340844E+09 16889994.33 4156153.18 62184.74 67049671.82 0.109897E+09 41337511.52 52017.50 0.37



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 LOBBY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.348199E+10 0.00 0.00 837837.98 0.00 0.280704E+09 0.729101E+09 0.00 0.63
February 0.284509E+10 0.00 0.00 1347395.30 0.00 19228151.69 0.802748E+09 0.00 0.65
March 0.253357E+10 0.00 0.00 1757952.79 0.00 3683922.48 0.854569E+09 0.00 0.65
April 0.153863E+10 0.00 0.00 2052478.53 12172002.26 639985.67 0.644761E+09 0.00 0.70
May 0.600945E+09 0.108699E+09 0.00 2160719.03 43421697.47 29674.85 0.288321E+09 0.00 0.77
June 0.157949E+09 0.444566E+09 0.00 1611264.80 0.341002E+09 0.00 84209624.44 0.00 0.81
July 58376573.11 0.638283E+09 0.00 828740.79 0.588275E+09 0.00 17239354.70 0.00 0.84
August 71760741.28 0.506206E+09 0.00 1078637.26 0.315875E+09 0.00 46999010.12 0.00 0.85
September 0.421360E+09 45472890.87 0.00 2805319.28 66494154.16 0.00 0.329475E+09 0.00 0.78
October 0.120809E+10 25116.45 0.00 2704081.68 1416222.77 129399.35 0.582070E+09 0.00 0.72
November 0.208575E+10 4081.05 0.00 1896824.75 0.00 3310830.67 0.693238E+09 0.00 0.67
December 0.341641E+10 0.00 0.00 1193070.93 0.00 77406557.80 0.810222E+09 0.00 0.63
                   
Annual Sum or Average 0.184199E+11 0.174326E+10 0.00 20274323.10 0.136866E+10 0.385133E+09 0.588295E+10 0.00 0.72
Minimum of Months 58376573.11 0.00 0.00 828740.79 0.00 0.00 17239354.70 0.00 0.63
Maximum of Months 0.348199E+10 0.638283E+09 0.00 2805319.28 0.588275E+09 0.280704E+09 0.854569E+09 0.00 0.85



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 LOBBY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.687094E+09 0.00 0.00 572240.99 0.00 2981350.78 0.425962E+09 0.00 0.40
February 0.532823E+09 0.00 0.00 738839.82 0.00 0.00 0.406909E+09 0.00 0.42
March 0.480149E+09 0.00 0.00 888472.85 0.00 0.00 0.365715E+09 0.00 0.42
April 0.304655E+09 0.00 0.00 751751.63 2516511.06 0.00 0.202105E+09 0.00 0.42
May 0.122189E+09 20311203.62 0.00 598094.67 10770147.24 0.00 74709564.41 0.00 0.43
June 32474175.64 87361516.46 0.00 410117.49 75036327.19 0.00 20899535.19 0.00 0.44
July 12030403.91 0.121642E+09 0.00 206822.86 0.130480E+09 0.00 4028100.19 0.00 0.45
August 14632342.96 99744874.60 0.00 306860.82 69387915.02 0.00 12012336.06 0.00 0.47
September 85695002.93 9239995.13 0.00 773316.18 14074170.29 0.00 83669636.82 0.00 0.44
October 0.243972E+09 7400.88 0.00 811487.66 292798.19 0.00 0.160529E+09 0.00 0.42
November 0.411881E+09 937.92 0.00 693752.02 0.00 0.00 0.232391E+09 0.00 0.41
December 0.648227E+09 0.00 0.00 708109.65 0.00 750713.64 0.438053E+09 0.00 0.41
                   
Annual Sum or Average 0.357582E+10 0.338308E+09 0.00 7459866.64 0.302558E+09 3732064.42 0.242698E+10 0.00 0.43
Minimum of Months 12030403.91 0.00 0.00 206822.86 0.00 0.00 4028100.19 0.00 0.40
Maximum of Months 0.687094E+09 0.121642E+09 0.00 888472.85 0.130480E+09 2981350.78 0.438053E+09 0.00 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 LOBBY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.214914E+10 0.00 0.00 11626.16 0.00 0.540016E+09 0.152522E+09 0.00 4.56
February 0.187797E+10 0.00 0.00 15296.95 0.00 0.243067E+09 0.141809E+09 0.00 4.55
March 0.172197E+10 0.00 0.00 22656.31 0.00 0.197342E+09 0.169758E+09 0.00 4.56
April 0.111453E+10 0.00 0.00 28721.46 8045840.38 70220736.33 0.113967E+09 0.00 4.69
May 0.457059E+09 22262488.06 41235.25 27473.70 36551763.95 25287106.58 36373959.39 2714.99 4.65
June 0.119211E+09 79329482.93 1713352.71 30673.56 0.271478E+09 2754732.58 13155504.16 12681.04 4.60
July 42408343.61 0.120445E+09 1574535.99 10938.65 0.452796E+09 743716.15 1802139.68 17044.34 4.68
August 54114301.86 0.102460E+09 256839.25 15837.59 0.241202E+09 719260.17 8671387.89 16223.54 4.62
September 0.325624E+09 9404473.36 33635.37 66000.62 47717349.99 4442043.07 63788074.16 2788.37 4.64
October 0.888012E+09 8870.66 0.00 60664.84 940914.14 19471314.27 0.128687E+09 0.00 4.65
November 0.147876E+10 0.00 0.00 43418.91 1765.92 56336507.31 0.170660E+09 0.00 4.63
December 0.216963E+10 0.00 0.00 16123.63 0.00 0.366486E+09 0.169647E+09 0.00 4.56
                   
Annual Sum or Average 0.123984E+11 0.333910E+09 3619598.58 349432.37 0.105873E+10 0.152689E+10 0.117084E+10 51452.27 4.62
Minimum of Months 42408343.61 0.00 0.00 10938.65 0.00 719260.17 1802139.68 0.00 4.55
Maximum of Months 0.216963E+10 0.120445E+09 1713352.71 66000.62 0.452796E+09 0.540016E+09 0.170660E+09 17044.34 4.69



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 LOCKER ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.272651E+10 0.00 0.00 4655027.21 0.00 0.00 0.306912E+10 0.00 0.75
February 0.215538E+10 0.00 0.00 4966100.79 0.00 0.00 0.254567E+10 0.00 0.77
March 0.193464E+10 0.00 0.00 5880359.87 0.00 0.00 0.232676E+10 0.00 0.77
April 0.122151E+10 0.00 0.00 5011078.74 10488188.34 0.00 0.130427E+10 0.00 0.75
May 0.486181E+09 0.115357E+09 0.00 4127980.21 44772278.49 0.00 0.511016E+09 0.00 0.79
June 0.130728E+09 0.517849E+09 0.00 2747129.43 0.300731E+09 0.00 0.131106E+09 0.00 0.82
July 48620486.09 0.700860E+09 0.00 1285832.97 0.532425E+09 0.00 25493541.97 0.00 0.80
August 59656223.66 0.583081E+09 0.00 1831471.43 0.278175E+09 0.00 72063232.66 0.00 0.84
September 0.346554E+09 58192148.46 0.00 4719911.44 57094071.99 0.00 0.515342E+09 0.00 0.80
October 0.977329E+09 41635.41 0.00 5619476.58 1220309.59 0.00 0.111744E+10 0.00 0.78
November 0.164663E+10 7408.34 0.00 5542430.48 0.00 0.00 0.173249E+10 0.00 0.78
December 0.260531E+10 0.00 0.00 5343473.67 0.00 0.00 0.302773E+10 0.00 0.78
                   
Annual Sum or Average 0.143390E+11 0.197539E+10 0.00 51730272.82 0.122491E+10 0.00 0.163785E+11 0.00 0.79
Minimum of Months 48620486.09 0.00 0.00 1285832.97 0.00 0.00 25493541.97 0.00 0.75
Maximum of Months 0.272651E+10 0.700860E+09 0.00 5880359.87 0.532425E+09 0.00 0.306912E+10 0.00 0.84



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.113319E+10 0.00 0.00 317108.43 0.00 60183714.63 0.275811E+09 0.00 0.26
February 0.854914E+09 0.00 0.00 519270.07 0.00 5157443.05 0.328081E+09 0.00 0.26
March 0.772027E+09 0.00 0.00 602390.14 0.00 0.00 0.294289E+09 0.00 0.25
April 0.518760E+09 0.00 0.00 276321.93 3798333.53 4339432.65 0.109146E+09 0.00 0.25
May 0.222040E+09 12024645.24 0.00 118620.67 17274365.60 8984177.63 21751101.02 0.00 0.25
June 56214168.25 38871485.21 324452.30 87452.59 0.133986E+09 792155.92 7838653.13 11157.42 0.24
July 20437783.21 50788080.49 755537.75 16260.67 0.227911E+09 292281.79 665936.45 7927.22 0.25
August 24717828.89 45138428.61 214215.99 64735.28 0.123015E+09 70314.04 5938675.77 1707.60 0.25
September 0.154036E+09 3699923.20 0.00 181382.89 24085340.20 5372794.52 32982815.63 0.00 0.25
October 0.424828E+09 0.00 0.00 226108.34 448380.69 11905206.32 66771778.07 0.00 0.25
November 0.687930E+09 0.00 0.00 288214.28 833.67 0.00 0.138059E+09 0.00 0.25
December 0.104217E+10 0.00 0.00 528628.11 0.00 2139876.14 0.366099E+09 0.00 0.26
                   
Annual Sum or Average 0.591127E+10 0.150523E+09 1294206.04 3226493.40 0.530520E+09 99237396.69 0.164743E+10 20792.23 0.25
Minimum of Months 20437783.21 0.00 0.00 16260.67 0.00 0.00 665936.45 0.00 0.24
Maximum of Months 0.113319E+10 50788080.49 755537.75 602390.14 0.227911E+09 60183714.63 0.366099E+09 11157.42 0.26



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.148711E+10 0.00 0.00 3244142.59 0.00 0.00 0.210552E+10 0.00 0.85
February 0.118268E+10 0.00 0.00 3292195.67 0.00 0.00 0.167763E+10 0.00 0.85
March 0.106567E+10 0.00 0.00 3763811.18 0.00 0.00 0.149439E+10 0.00 0.84
April 0.676765E+09 0.00 0.00 2904792.99 5812439.51 0.00 0.764705E+09 0.00 0.78
May 0.270721E+09 58841414.95 0.00 2154936.72 24824898.84 0.00 0.272082E+09 0.00 0.78
June 72833547.15 0.251950E+09 0.00 1373009.14 0.172542E+09 0.00 66992144.50 0.00 0.79
July 27208599.28 0.335809E+09 0.00 607337.03 0.300447E+09 0.00 12194740.76 0.00 0.76
August 33234854.26 0.278454E+09 0.00 878484.55 0.160141E+09 0.00 36002222.46 0.00 0.80
September 0.193380E+09 27798165.11 0.00 2306867.25 32299643.24 0.00 0.257740E+09 0.00 0.77
October 0.546688E+09 20199.36 0.00 2879791.97 676282.26 0.00 0.581295E+09 0.00 0.77
November 0.914853E+09 3827.53 0.00 3096160.64 0.00 0.00 0.984824E+09 0.00 0.80
December 0.142933E+10 0.00 0.00 3496503.97 0.00 0.00 0.196038E+10 0.00 0.85
                   
Annual Sum or Average 0.790047E+10 0.952876E+09 0.00 29998033.69 0.696742E+09 0.00 0.102138E+11 0.00 0.80
Minimum of Months 27208599.28 0.00 0.00 607337.03 0.00 0.00 12194740.76 0.00 0.76
Maximum of Months 0.148711E+10 0.335809E+09 0.00 3763811.18 0.300447E+09 0.00 0.210552E+10 0.00 0.85



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 MED GAS

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 2291021.84 0.00 0.00 0.00 0.00 0.848099E+09 0.00 0.00 1.25
February 2472734.28 0.00 0.00 0.00 0.00 0.638152E+09 0.00 0.00 1.19
March 2470822.65 0.00 0.00 0.00 0.00 0.585431E+09 0.00 0.00 1.18
April 3304596.52 0.00 1297841.09 0.00 0.00 0.293129E+09 0.00 3950.27 0.97
May 3979750.25 0.00 5735864.51 0.00 3748333.96 93327123.76 0.00 63855.36 0.78
June 2079610.32 0.00 19635688.42 0.00 37604579.88 20693986.40 0.00 135516.64 0.73
July 2401175.89 0.00 12794853.17 0.00 80251614.37 4988062.94 0.00 93185.71 0.73
August 6155437.47 0.00 7464578.50 0.00 48156975.86 4262013.72 0.00 78136.24 0.72
September 24053390.44 0.00 1216002.79 0.00 8023097.03 40916781.96 0.00 14594.98 0.73
October 25667167.55 0.00 1883.40 0.00 151464.53 0.149940E+09 0.00 324.23 0.75
November 11515418.33 0.00 151.51 0.00 0.00 0.307156E+09 0.00 134.21 0.81
December 3676890.27 0.00 0.00 0.00 0.00 0.713385E+09 0.00 0.00 1.11
                   
Annual Sum or Average 90068015.82 0.00 48146863.40 0.00 0.177936E+09 0.369948E+10 0.00 389697.65 0.91
Minimum of Months 2079610.32 0.00 0.00 0.00 0.00 4262013.72 0.00 0.00 0.72
Maximum of Months 25667167.55 0.00 19635688.42 0.00 80251614.37 0.848099E+09 0.00 135516.64 1.25



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.132634E+10 0.00 0.00 5290988.26 0.00 0.00 0.319394E+10 0.00 2.30
February 0.957063E+09 0.00 0.00 5167277.86 0.00 0.00 0.260031E+10 0.00 2.29
March 0.835173E+09 0.00 0.00 5806782.14 0.00 0.00 0.243599E+10 0.00 2.33
April 0.543546E+09 2932732.68 0.00 4754980.24 3469612.90 0.00 0.136275E+10 0.00 2.22
May 0.219194E+09 0.109729E+09 0.00 3903455.16 8876435.23 0.00 0.524803E+09 0.00 2.28
June 55769737.20 0.532686E+09 0.00 2469081.84 67881394.00 0.00 0.132810E+09 0.00 2.36
July 17691039.40 0.784174E+09 0.00 1197342.14 0.111395E+09 0.00 34805792.08 0.00 2.31
August 16605974.50 0.597700E+09 0.00 1582465.40 33165095.71 0.00 76953358.30 0.00 2.40
September 0.126117E+09 61879722.18 0.00 4307274.74 19218182.95 0.00 0.505079E+09 0.00 2.27
October 0.428613E+09 62810.34 0.00 5159203.77 716005.40 0.00 0.110308E+10 0.00 2.23
November 0.668545E+09 5917.92 0.00 5188471.06 0.00 0.00 0.184051E+10 0.00 2.28
December 0.118913E+10 0.00 0.00 5512763.74 0.00 0.00 0.303292E+10 0.00 2.30
                   
Annual Sum or Average 0.638379E+10 0.208917E+10 0.00 50340086.35 0.244722E+09 0.00 0.168439E+11 0.00 2.30
Minimum of Months 16605974.50 0.00 0.00 1197342.14 0.00 0.00 34805792.08 0.00 2.22
Maximum of Months 0.132634E+10 0.784174E+09 0.00 5806782.14 0.111395E+09 0.00 0.319394E+10 0.00 2.40



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 MRI HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.466680E+09 0.00 0.00 53933.61 0.00 29934244.95 50345396.92 0.00 0.33
February 0.357599E+09 0.00 0.00 93254.82 0.00 3493249.73 68642323.01 0.00 0.32
March 0.327217E+09 0.00 0.00 101023.48 0.00 215783.25 60685415.75 0.00 0.31
April 0.201500E+09 0.00 0.00 97300.22 1475746.68 3004644.08 40184438.82 0.00 0.33
May 81141965.75 7487479.04 0.00 106708.72 6379476.48 417017.76 16473974.44 0.00 0.34
June 19990157.23 33236661.21 0.00 108001.22 45103740.50 0.00 6545390.67 0.00 0.35
July 7296501.47 47160663.69 0.00 55739.01 77323030.84 0.00 1225206.56 0.00 0.36
August 9062113.57 40002059.84 0.00 87727.85 41293421.69 0.00 4329662.88 0.00 0.37
September 52890658.35 3667404.83 0.00 227722.30 8309337.35 0.00 28310679.89 0.00 0.35
October 0.151925E+09 2502.63 0.00 202907.14 171704.38 1374937.05 48846784.09 0.00 0.34
November 0.265777E+09 323.90 0.00 139588.60 0.00 0.00 57628574.65 0.00 0.33
December 0.429711E+09 0.00 0.00 113627.88 0.00 3994303.88 82563059.36 0.00 0.32
                   
Annual Sum or Average 0.237079E+10 0.131557E+09 0.00 1387534.85 0.180056E+09 42434180.69 0.465781E+09 0.00 0.34
Minimum of Months 7296501.47 0.00 0.00 53933.61 0.00 0.00 1225206.56 0.00 0.31
Maximum of Months 0.466680E+09 47160663.69 0.00 227722.30 77323030.84 29934244.95 82563059.36 0.00 0.37



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 MRI ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.802529E+09 0.00 0.00 21873588.01 0.00 0.00 0.125863E+11 0.00 2.62
February 0.292262E+09 0.00 0.00 20465382.24 0.00 0.00 0.106249E+11 0.00 2.69
March 0.311861E+09 0.00 0.00 21881436.44 0.00 0.00 0.986344E+10 0.00 2.75
April 0.431281E+09 14537549.30 0.00 16742031.14 1898829.85 0.00 0.527874E+10 0.00 2.50
May 0.157629E+09 0.304901E+09 0.00 12699448.91 6762116.63 0.00 0.193850E+10 0.00 2.38
June 48297216.47 0.147289E+10 0.00 7649656.90 90052879.85 0.00 0.458838E+09 0.00 2.39
July 21636124.75 0.218285E+10 0.00 3528477.04 0.132018E+09 0.00 0.117616E+09 0.00 2.30
August 6318794.55 0.160386E+10 0.00 4591812.99 25049045.03 0.00 0.243412E+09 0.00 2.40
September 97425842.33 0.198430E+09 0.00 13137095.60 12825578.03 0.00 0.161799E+10 0.00 2.32
October 0.402536E+09 2000863.73 0.00 17220776.43 77274.28 0.00 0.394599E+10 0.00 2.39
November 0.448207E+09 15991.60 0.00 17697873.95 0.00 0.00 0.710807E+10 0.00 2.59
December 0.684950E+09 0.00 0.00 21469645.95 0.00 0.00 0.120601E+11 0.00 2.66
                   
Annual Sum or Average 0.370493E+10 0.577949E+10 0.00 0.178957E+09 0.268683E+09 0.00 0.658439E+11 0.00 2.50
Minimum of Months 6318794.55 0.00 0.00 3528477.04 0.00 0.00 0.117616E+09 0.00 2.30
Maximum of Months 0.802529E+09 0.218285E+10 0.00 21881436.44 0.132018E+09 0.00 0.125863E+11 0.00 2.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 MRI TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.459795E+09 0.00 0.00 0.00 0.00 0.308878E+09 0.00 0.00 1.23
February 0.415887E+09 0.00 0.00 0.00 0.00 0.196215E+09 0.00 0.00 1.23
March 0.370164E+09 0.00 0.00 0.00 0.00 0.194935E+09 0.00 0.00 1.23
April 0.253363E+09 0.00 0.00 0.00 2176393.76 97945903.37 0.00 0.00 1.27
May 0.109952E+09 0.00 69014.95 0.00 15849846.37 30368409.53 0.00 2238.06 1.26
June 33901359.19 0.00 2299222.04 0.00 93048695.34 2657067.28 0.00 12005.85 1.25
July 11752009.67 0.00 1286860.49 0.00 0.154194E+09 411026.31 0.00 10828.20 1.27
August 16794242.17 0.00 201773.37 0.00 92825265.51 388083.01 0.00 7128.92 1.25
September 0.102887E+09 0.00 20497.21 0.00 15439267.77 3668335.77 0.00 1497.80 1.26
October 0.263327E+09 0.00 0.00 0.00 256916.07 16972644.13 0.00 0.00 1.26
November 0.397941E+09 0.00 0.00 0.00 477.68 63477342.39 0.00 0.00 1.25
December 0.493544E+09 0.00 0.00 0.00 0.00 0.238368E+09 0.00 0.00 1.23
                   
Annual Sum or Average 0.292931E+10 0.00 3877368.06 0.00 0.373791E+09 0.115428E+10 0.00 33698.82 1.25
Minimum of Months 11752009.67 0.00 0.00 0.00 0.00 388083.01 0.00 0.00 1.23
Maximum of Months 0.493544E+09 0.00 2299222.04 0.00 0.154194E+09 0.308878E+09 0.00 12005.85 1.27



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 NOURISHMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.802561E+09 0.00 0.00 2069186.79 0.00 0.00 0.126668E+10 0.00 0.97
February 0.629273E+09 0.00 0.00 2101019.00 0.00 0.00 0.101433E+10 0.00 0.97
March 0.563376E+09 0.00 0.00 2332214.27 0.00 0.00 0.916169E+09 0.00 0.96
April 0.367286E+09 0.00 0.00 1626815.82 3181845.41 0.00 0.437395E+09 0.00 0.86
May 0.148819E+09 31103434.14 0.00 1108391.83 13616169.98 0.00 0.143374E+09 0.00 0.83
June 40171548.25 0.127287E+09 0.00 673747.64 94827188.35 0.00 33973012.70 0.00 0.82
July 15110616.09 0.166045E+09 0.00 273030.79 0.165281E+09 0.00 5602508.21 0.00 0.79
August 18402100.95 0.141314E+09 0.00 407665.16 87940447.55 0.00 18010758.32 0.00 0.82
September 0.106484E+09 14131060.09 0.00 1163015.84 17723240.08 0.00 0.133750E+09 0.00 0.81
October 0.299950E+09 10060.83 0.00 1523998.29 370210.41 0.00 0.314200E+09 0.00 0.82
November 0.497442E+09 2112.93 0.00 1738587.94 0.00 0.00 0.564910E+09 0.00 0.88
December 0.765877E+09 0.00 0.00 2183663.48 0.00 0.00 0.117138E+10 0.00 0.97
                   
Annual Sum or Average 0.425475E+10 0.479892E+09 0.00 17201336.85 0.382940E+09 0.00 0.601978E+10 0.00 0.87
Minimum of Months 15110616.09 0.00 0.00 273030.79 0.00 0.00 5602508.21 0.00 0.79
Maximum of Months 0.802561E+09 0.166045E+09 0.00 2332214.27 0.165281E+09 0.00 0.126668E+10 0.00 0.97



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 NURSE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.145647E+10 0.00 0.00 225709.77 0.00 0.142814E+09 0.187389E+09 0.00 0.31
February 0.117166E+10 0.00 0.00 151618.98 0.00 35634428.61 0.132416E+09 0.00 0.30
March 0.111626E+10 0.00 0.00 51272.71 0.00 70637019.82 55342429.95 0.00 0.30
April 0.660566E+09 0.00 0.00 29809.10 4627572.52 0.163037E+09 21230770.98 0.00 0.33
May 0.246501E+09 3604760.26 960547.34 7657.57 29846748.51 0.123501E+09 2449161.07 41554.13 0.35
June 69107842.84 14501402.42 44376587.83 4369.62 0.170467E+09 19841162.88 683933.41 370568.88 0.34
July 23363026.05 19065054.92 63554195.76 733.23 0.286005E+09 6168865.36 30435.26 463605.45 0.34
August 34062704.81 20064481.43 26833588.27 1853.61 0.167305E+09 4016651.57 866924.69 292814.02 0.32
September 0.199990E+09 2530819.06 6679902.24 36065.21 27887646.37 50575216.30 6519455.62 95712.43 0.33
October 0.527299E+09 0.00 0.00 67441.19 546269.61 0.136500E+09 14782261.96 0.00 0.33
November 0.874889E+09 0.00 2343.29 134099.34 0.00 0.146430E+09 63037780.53 195.89 0.33
December 0.143145E+10 0.00 0.00 139965.23 0.00 65877092.28 0.138018E+09 0.00 0.30
                   
Annual Sum or Average 0.781162E+10 59766518.09 0.142407E+09 850595.54 0.686685E+09 0.965033E+09 0.622766E+09 1264450.80 0.32
Minimum of Months 23363026.05 0.00 0.00 733.23 0.00 4016651.57 30435.26 0.00 0.30
Maximum of Months 0.145647E+10 20064481.43 63554195.76 225709.77 0.286005E+09 0.163037E+09 0.187389E+09 463605.45 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 NURSE JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.153517E+09 0.00 0.00 103198.73 0.00 2763605.25 78446335.30 0.00 0.37
February 0.118298E+09 0.00 0.00 139527.22 0.00 0.00 80363096.69 0.00 0.40
March 0.107493E+09 0.00 0.00 163531.99 0.00 0.00 70813196.75 0.00 0.39
April 70902636.98 0.00 0.00 87252.01 556741.61 0.00 27427199.05 0.00 0.36
May 30530468.30 2079640.21 0.00 38537.24 2428473.06 708830.97 6135034.30 0.00 0.34
June 7746378.22 7407686.67 0.00 21648.61 18382207.43 0.00 1847379.45 0.00 0.33
July 2956050.66 9518380.24 0.00 4439.76 31855072.86 0.00 156456.41 0.00 0.34
August 3475230.06 7876376.39 0.00 16715.80 17203285.43 0.00 1156246.68 0.00 0.34
September 21167841.50 635576.24 0.00 50081.43 3482081.57 541377.52 7272225.13 0.00 0.34
October 58574246.25 944.15 0.00 67525.78 64777.36 748585.80 16402262.94 0.00 0.34
November 93734886.81 122.20 0.00 94088.47 0.00 0.00 36015614.74 0.00 0.36
December 0.144697E+09 0.00 0.00 143040.70 0.00 0.00 88476498.02 0.00 0.39
                   
Annual Sum or Average 0.813093E+09 27518726.09 0.00 929587.72 73972639.32 4762399.53 0.414512E+09 0.00 0.36
Minimum of Months 2956050.66 0.00 0.00 4439.76 0.00 0.00 156456.41 0.00 0.33
Maximum of Months 0.153517E+09 9518380.24 0.00 163531.99 31855072.86 2763605.25 88476498.02 0.00 0.40



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 NURSE STATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.111531E+10 0.00 0.00 2202000.66 0.00 0.00 0.147137E+10 0.00 0.84
February 0.889243E+09 0.00 0.00 2242849.27 0.00 0.00 0.117339E+10 0.00 0.85
March 0.800387E+09 0.00 0.00 2542255.61 0.00 0.00 0.103287E+10 0.00 0.83
April 0.508875E+09 0.00 0.00 1851345.50 4341726.39 0.00 0.500618E+09 0.00 0.76
May 0.205601E+09 38318724.66 0.00 1271312.38 18615668.39 0.00 0.165537E+09 0.00 0.73
June 55639783.86 0.155765E+09 0.00 791638.08 0.129999E+09 0.00 40038635.27 0.00 0.73
July 20877824.01 0.203453E+09 0.00 319704.49 0.225991E+09 0.00 6562415.93 0.00 0.71
August 25454877.67 0.174572E+09 0.00 486794.25 0.120248E+09 0.00 21767589.49 0.00 0.74
September 0.146633E+09 17410683.93 0.00 1379107.60 24225710.07 0.00 0.160349E+09 0.00 0.72
October 0.412812E+09 11325.09 0.00 1763316.19 505163.54 0.00 0.366418E+09 0.00 0.73
November 0.688290E+09 2435.78 0.00 1962795.47 0.00 0.00 0.639024E+09 0.00 0.77
December 0.107822E+10 0.00 0.00 2310555.69 0.00 0.00 0.133956E+10 0.00 0.84
                   
Annual Sum or Average 0.594733E+10 0.589533E+09 0.00 19123675.18 0.523927E+09 0.00 0.691751E+10 0.00 0.77
Minimum of Months 20877824.01 0.00 0.00 319704.49 0.00 0.00 6562415.93 0.00 0.71
Maximum of Months 0.111531E+10 0.203453E+09 0.00 2542255.61 0.225991E+09 0.00 0.147137E+10 0.00 0.85



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 NURSE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.111100E+10 0.00 0.00 0.00 0.00 0.105326E+09 0.00 0.00 1.96
February 0.921364E+09 0.00 0.00 0.00 0.00 47204605.55 0.00 0.00 1.95
March 0.841878E+09 0.00 0.00 0.00 0.00 52313811.89 0.00 0.00 1.96
April 0.462308E+09 0.00 0.00 0.00 3443848.53 93589920.68 0.00 0.00 2.01
May 0.165781E+09 0.00 6668334.23 0.00 18465712.50 56257964.36 0.00 58937.91 1.99
June 44220816.72 0.00 36139088.30 0.00 0.114529E+09 13627944.51 0.00 225989.37 1.97
July 15733149.65 0.00 55085863.42 0.00 0.190650E+09 3513208.38 0.00 308282.92 2.00
August 20831083.87 0.00 38144931.37 0.00 0.108752E+09 6357619.87 0.00 316882.30 1.97
September 0.123667E+09 0.00 3935478.44 0.00 20466455.83 44941919.70 0.00 63421.21 1.98
October 0.353622E+09 0.00 5281.30 0.00 400694.69 89915022.67 0.00 558.91 1.99
November 0.639227E+09 0.00 584.38 0.00 0.00 90905649.06 0.00 171.48 1.98
December 0.109994E+10 0.00 0.00 0.00 0.00 58209924.40 0.00 0.00 1.96
                   
Annual Sum or Average 0.579957E+10 0.00 0.139980E+09 0.00 0.456708E+09 0.662163E+09 0.00 974244.11 1.98
Minimum of Months 15733149.65 0.00 0.00 0.00 0.00 3513208.38 0.00 0.00 1.95
Maximum of Months 0.111100E+10 0.00 55085863.42 0.00 0.190650E+09 0.105326E+09 0.00 316882.30 2.01



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.131845E+10 0.00 0.00 1259010.46 0.00 3679337.74 0.831084E+09 0.00 0.38
February 0.102970E+10 0.00 0.00 1554060.54 0.00 0.00 0.789118E+09 0.00 0.40
March 0.925076E+09 0.00 0.00 1874403.10 0.00 0.00 0.732272E+09 0.00 0.41
April 0.585668E+09 0.00 0.00 1505615.05 4915813.28 0.00 0.390932E+09 0.00 0.40
May 0.235767E+09 33766470.76 0.00 1119342.71 21074971.60 0.00 0.140257E+09 0.00 0.40
June 63224239.71 0.145846E+09 0.00 755071.98 0.147039E+09 0.00 37558314.55 0.00 0.41
July 23638208.76 0.194249E+09 0.00 339791.88 0.255523E+09 0.00 6525957.70 0.00 0.41
August 28820180.38 0.161954E+09 0.00 519877.87 0.136204E+09 0.00 21205881.56 0.00 0.42
September 0.167689E+09 15640452.73 0.00 1314119.95 27525642.26 0.00 0.145468E+09 0.00 0.40
October 0.472003E+09 10369.18 0.00 1502893.99 571959.04 0.00 0.303498E+09 0.00 0.39
November 0.791271E+09 1066.23 0.00 1502587.88 0.00 0.00 0.477731E+09 0.00 0.39
December 0.125084E+10 0.00 0.00 1570588.90 0.00 0.00 0.877937E+09 0.00 0.40
                   
Annual Sum or Average 0.689215E+10 0.551468E+09 0.00 14817364.32 0.592854E+09 3679337.74 0.475359E+10 0.00 0.40
Minimum of Months 23638208.76 0.00 0.00 339791.88 0.00 0.00 6525957.70 0.00 0.38
Maximum of Months 0.131845E+10 0.194249E+09 0.00 1874403.10 0.255523E+09 3679337.74 0.877937E+09 0.00 0.42



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.680218E+10 0.00 0.00 17870635.63 0.00 0.112807E+09 0.202080E+11 0.00 5.11
February 0.483776E+10 0.00 0.00 17070165.24 0.00 0.101189E+09 0.167097E+11 0.00 5.21
March 0.421968E+10 0.00 0.00 17510388.42 0.00 90300352.39 0.158308E+11 0.00 5.22
April 0.288329E+10 27711635.17 0.00 13120724.48 16839201.49 0.151152E+09 0.900341E+10 0.00 5.12
May 0.128423E+10 0.574784E+09 1394329.25 10140572.38 74253262.89 57381252.65 0.334631E+10 96758.20 4.99
June 0.328238E+09 0.286003E+10 27987132.45 6791455.19 0.637391E+09 14094469.52 0.811836E+09 243089.39 5.02
July 0.125261E+09 0.446885E+10 15693745.38 2815171.97 0.104741E+10 5240194.24 0.183423E+09 154517.23 4.93
August 0.132350E+09 0.311790E+10 5303511.74 3781766.42 0.437900E+09 9207892.36 0.412974E+09 81686.72 5.05
September 0.802527E+09 0.375937E+09 217922.81 11393341.04 0.119183E+09 24540050.10 0.290774E+10 17454.32 5.01
October 0.219794E+10 8633030.91 95989.52 14468697.20 258869.56 44013203.79 0.735017E+10 13706.36 5.11
November 0.354745E+10 35344.00 0.00 14880734.57 0.00 43802087.83 0.129017E+11 0.00 5.34
December 0.594241E+10 0.00 0.00 17442657.40 0.00 73960439.66 0.196289E+11 0.00 5.12
                   
Annual Sum or Average 0.331033E+11 0.114339E+11 50692631.14 0.147286E+09 0.233323E+10 0.727688E+09 0.109295E+12 607212.23 5.10
Minimum of Months 0.125261E+09 0.00 0.00 2815171.97 0.00 5240194.24 0.183423E+09 0.00 4.93
Maximum of Months 0.680218E+10 0.446885E+10 27987132.45 17870635.63 0.104741E+10 0.151152E+09 0.202080E+11 243089.39 5.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.530413E+10 0.00 0.00 21155269.71 0.00 0.683425E+09 0.233950E+11 0.00 5.30
February 0.359720E+10 0.00 0.00 19698403.69 0.00 0.159615E+09 0.192605E+11 0.00 5.30
March 0.332714E+10 0.00 0.00 19648416.54 0.00 0.245004E+09 0.178381E+11 0.00 5.30
April 0.272238E+10 26636407.34 0.00 13643456.94 17571340.68 0.682400E+09 0.951557E+10 0.00 5.25
May 0.105583E+10 0.572631E+09 0.101418E+09 8181994.70 60322747.34 0.113021E+10 0.336867E+10 2633590.20 5.77
June 0.230646E+09 0.269208E+10 0.115624E+10 4939293.04 0.449297E+09 0.436371E+09 0.795966E+09 6879625.98 5.99
July 81181160.73 0.422952E+10 0.164690E+10 2260076.58 0.752538E+09 0.173997E+09 0.178141E+09 10033432.27 5.75
August 0.135818E+09 0.306663E+10 0.306162E+09 2998535.18 0.462168E+09 59627612.80 0.410249E+09 5104096.15 5.44
September 0.733587E+09 0.290559E+09 0.294274E+09 8203085.26 81962592.34 0.704216E+09 0.284483E+10 6063949.14 5.88
October 0.207207E+10 989152.41 10637963.22 11716755.88 54650.27 0.116755E+10 0.739947E+10 699569.88 5.49
November 0.342462E+10 36880.70 0.00 14802965.38 0.00 0.129217E+09 0.139427E+11 0.00 5.41
December 0.447055E+10 0.00 0.00 20937098.88 0.00 85572519.92 0.227830E+11 0.00 5.23
                   
Annual Sum or Average 0.271551E+11 0.108791E+11 0.351564E+10 0.148185E+09 0.182392E+10 0.565721E+10 0.121732E+12 31414263.62 5.51
Minimum of Months 81181160.73 0.00 0.00 2260076.58 0.00 59627612.80 0.178141E+09 0.00 5.23
Maximum of Months 0.530413E+10 0.422952E+10 0.164690E+10 21155269.71 0.752538E+09 0.116755E+10 0.233950E+11 10033432.27 5.99



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.339383E+11 0.00 0.00 22488722.65 0.00 0.109920E+10 0.237931E+11 0.00 10.69
February 0.279042E+11 0.00 0.00 20340545.34 0.00 0.532023E+09 0.184086E+11 0.00 10.67
March 0.255506E+11 0.00 0.00 20205296.08 0.00 0.665357E+09 0.170303E+11 0.00 10.68
April 0.166531E+11 69794839.63 39241685.09 12766952.66 57587734.55 0.114323E+10 0.908868E+10 10094.09 10.95
May 0.610374E+10 0.514089E+09 0.170366E+09 8090085.77 0.532151E+09 0.123623E+10 0.339551E+10 2384067.35 10.84
June 0.150120E+10 0.244231E+10 0.181002E+10 4756912.83 0.304158E+10 0.551818E+09 0.741295E+09 7269236.27 10.72
July 0.483277E+09 0.411275E+10 0.331822E+10 1974579.99 0.446310E+10 0.289059E+09 0.156945E+09 11064156.22 10.90
August 0.856224E+09 0.279565E+10 0.776963E+09 2647217.19 0.354402E+10 86095204.57 0.370589E+09 6472088.44 10.76
September 0.421905E+10 0.265890E+09 0.478250E+09 7943208.03 0.433831E+09 0.123022E+10 0.270110E+10 5811436.08 10.81
October 0.124055E+11 980909.48 17873410.46 11427632.04 83169.46 0.201390E+10 0.703021E+10 733144.06 10.85
November 0.210123E+11 36573.36 0.00 14555862.96 0.00 0.127711E+10 0.130243E+11 0.00 10.83
December 0.330213E+11 0.00 0.00 21687571.40 0.00 0.534354E+09 0.224611E+11 0.00 10.68
                   
Annual Sum or Average 0.183649E+12 0.102015E+11 0.661093E+10 0.148885E+09 0.120724E+11 0.106586E+11 0.118202E+12 33744222.51 10.78
Minimum of Months 0.483277E+09 0.00 0.00 1974579.99 0.00 86095204.57 0.156945E+09 0.00 10.67
Maximum of Months 0.339383E+11 0.411275E+10 0.331822E+10 22488722.65 0.446310E+10 0.201390E+10 0.237931E+11 11064156.22 10.95



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 PACU

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.316559E+10 0.00 0.00 533294.58 0.00 6397554.69 0.833447E+09 0.00 3.23
February 0.251503E+10 0.00 0.00 468566.05 0.00 2512584.44 0.671975E+09 0.00 3.22
March 0.229986E+10 0.00 0.00 423827.63 0.00 2239371.27 0.642500E+09 0.00 3.22
April 0.145516E+10 0.00 0.00 258452.97 11342339.23 10732661.37 0.364700E+09 0.00 3.31
May 0.584231E+09 33370317.97 152216.87 165283.85 49428250.70 9096957.44 0.137792E+09 22485.74 3.28
June 0.155811E+09 0.132116E+09 3781769.25 113833.12 0.361014E+09 3782406.74 30817860.54 59507.97 3.24
July 56655567.75 0.184166E+09 11418010.00 35379.93 0.614682E+09 1468489.54 5228577.69 83418.30 3.30
August 71801161.71 0.155650E+09 2883736.70 52521.69 0.326246E+09 2310280.02 15382222.72 70731.64 3.25
September 0.418989E+09 15552536.38 80730.75 204768.96 64936039.04 7683247.08 0.128437E+09 7513.38 3.27
October 0.115250E+10 12505.10 0.00 259742.53 1326420.47 8918810.98 0.299109E+09 0.00 3.28
November 0.193854E+10 2489.45 0.00 283294.20 0.00 4976227.40 0.460899E+09 0.00 3.27
December 0.303633E+10 0.00 0.00 490349.54 0.00 3303047.89 0.774262E+09 0.00 3.22
                   
Annual Sum or Average 0.168505E+11 0.520869E+09 18316463.58 3289315.05 0.142897E+10 63421638.86 0.436455E+10 243657.03 3.26
Minimum of Months 56655567.75 0.00 0.00 35379.93 0.00 1468489.54 5228577.69 0.00 3.22
Maximum of Months 0.316559E+10 0.184166E+09 11418010.00 533294.58 0.614682E+09 10732661.37 0.833447E+09 83418.30 3.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 PRE-OP HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.125508E+10 0.00 0.00 0.00 0.00 0.705373E+09 0.00 0.00 0.32
February 0.111279E+10 0.00 0.00 0.00 0.00 0.290875E+09 0.00 0.00 0.29
March 0.109751E+10 0.00 0.00 0.00 0.00 0.151511E+09 0.00 0.00 0.28
April 0.666912E+09 0.00 0.00 6081.23 4473770.25 0.126391E+09 4671696.40 0.00 0.29
May 0.249550E+09 9596116.67 0.00 17596.24 23542096.03 85359491.15 4738694.72 0.00 0.30
June 70605202.36 39074140.34 9189822.07 25184.79 0.158933E+09 4855612.41 2594274.61 68218.79 0.28
July 23772533.17 40617336.87 17115040.42 6658.55 0.276319E+09 2276991.66 313395.19 80490.14 0.28
August 32181403.26 39525102.42 3544058.75 9639.45 0.153277E+09 710074.63 2844865.07 23821.65 0.27
September 0.205517E+09 3511579.92 1500577.06 30598.43 28107984.57 20622574.31 5337754.71 9859.82 0.28
October 0.527688E+09 0.00 0.00 15822.51 528113.76 0.110644E+09 4257126.93 0.00 0.29
November 0.877592E+09 0.00 0.00 539.04 981.92 0.174291E+09 1027888.25 0.00 0.30
December 0.130425E+10 0.00 0.00 0.00 0.00 0.402742E+09 0.00 0.00 0.30
                   
Annual Sum or Average 0.742345E+10 0.132324E+09 31349498.30 112120.24 0.645183E+09 0.207565E+10 25785695.89 182390.39 0.29
Minimum of Months 23772533.17 0.00 0.00 0.00 0.00 710074.63 0.00 0.00 0.27
Maximum of Months 0.130425E+10 40617336.87 17115040.42 30598.43 0.276319E+09 0.705373E+09 5337754.71 80490.14 0.32



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.558259E+10 0.00 0.00 0.00 0.00 0.142785E+10 0.00 0.00 3.21
February 0.482911E+10 0.00 0.00 0.00 0.00 0.753370E+09 0.00 0.00 3.21
March 0.459830E+10 0.00 0.00 0.00 0.00 0.555501E+09 0.00 0.00 3.21
April 0.280997E+10 0.00 0.00 10162.87 19849093.66 0.346534E+09 47478841.87 0.00 3.30
May 0.112135E+10 44486795.94 827044.45 15193.30 99818461.11 0.124017E+09 34369211.06 70923.25 3.27
June 0.286710E+09 0.131269E+09 32782778.00 21857.30 0.705420E+09 25907186.63 20780390.38 227413.28 3.24
July 0.101719E+09 0.176878E+09 36075323.77 6269.99 0.120488E+10 6568459.95 2635746.02 280847.79 3.30
August 0.131190E+09 0.175534E+09 11477446.94 9525.99 0.661226E+09 9161398.89 16344885.10 251298.93 3.25
September 0.864094E+09 13775602.98 968592.64 23831.46 0.126227E+09 62774278.03 44907820.28 38155.98 3.27
October 0.238660E+10 0.00 11245.78 9664.16 2331342.78 0.151799E+09 17976846.63 531.20 3.27
November 0.388706E+10 0.00 0.00 2225.03 4356.53 0.309347E+09 11810207.96 0.00 3.26
December 0.571932E+10 0.00 0.00 0.00 0.00 0.955845E+09 0.00 0.00 3.21
                   
Annual Sum or Average 0.323180E+11 0.541943E+09 82142431.57 98730.11 0.281975E+10 0.472868E+10 0.196304E+09 869170.43 3.25
Minimum of Months 0.101719E+09 0.00 0.00 0.00 0.00 6568459.95 0.00 0.00 3.21
Maximum of Months 0.571932E+10 0.176878E+09 36075323.77 23831.46 0.120488E+10 0.142785E+10 47478841.87 280847.79 3.30



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.109269E+11 0.00 0.00 200807.93 0.00 71854450.40 0.153825E+10 0.00 3.22
February 0.865121E+10 0.00 0.00 211893.39 0.00 25802501.51 0.130625E+10 0.00 3.22
March 0.776428E+10 0.00 0.00 312859.72 0.00 23240837.49 0.142901E+10 0.00 3.22
April 0.497138E+10 0.00 0.00 221887.76 35497320.93 68721333.91 0.689576E+09 0.00 3.31
May 0.203496E+10 81536433.40 1048349.17 117951.10 0.177005E+09 64682911.23 0.188892E+09 86163.48 3.28
June 0.515944E+09 0.254195E+09 23510201.45 95479.81 0.127737E+10 21344678.79 58889632.32 257018.82 3.24
July 0.183558E+09 0.332577E+09 48700808.40 22993.85 0.215443E+10 8047633.64 6752389.76 384809.94 3.30
August 0.229324E+09 0.329557E+09 15791043.82 50397.79 0.117172E+10 11914526.58 38957971.15 330555.36 3.25
September 0.143451E+10 29607658.67 1037253.21 172664.44 0.221485E+09 54633134.83 0.248616E+09 45226.01 3.27
October 0.394635E+10 0.00 0.00 198539.38 4190341.15 63477004.99 0.561712E+09 0.00 3.28
November 0.647664E+10 0.00 0.00 236367.26 7791.05 36228766.99 0.101271E+10 0.00 3.27
December 0.103380E+11 0.00 0.00 229536.70 0.00 27852171.93 0.157149E+10 0.00 3.22
                   
Annual Sum or Average 0.574731E+11 0.102747E+10 90087656.05 2071379.13 0.504171E+10 0.477800E+09 0.865111E+10 1103773.60 3.26
Minimum of Months 0.183558E+09 0.00 0.00 22993.85 0.00 8047633.64 6752389.76 0.00 3.22
Maximum of Months 0.109269E+11 0.332577E+09 48700808.40 312859.72 0.215443E+10 71854450.40 0.157149E+10 384809.94 3.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 23825405.89 0.00 0.00 0.00 0.00 0.953096E+09 0.00 0.00 1.56
February 0.108190E+09 0.00 0.00 0.00 0.00 0.669741E+09 0.00 0.00 1.56
March 0.117937E+09 0.00 0.00 0.00 0.00 0.600257E+09 0.00 0.00 1.56
April 0.195179E+09 0.00 0.00 0.00 2766017.76 0.251305E+09 0.00 0.00 1.61
May 0.120504E+09 0.00 1277584.41 0.00 18949217.91 57832131.67 0.00 7607.64 1.60
June 35040194.22 2941620.55 11712331.13 0.00 0.106504E+09 11422563.86 0.00 37131.15 1.58
July 13546194.35 73215.58 8964966.59 0.00 0.188548E+09 1912025.64 0.00 30445.89 1.61
August 16658287.01 626931.87 4170060.22 0.00 0.113416E+09 5179037.38 0.00 25678.94 1.59
September 96710968.62 31851.20 1161742.64 0.00 18450197.17 38711682.45 0.00 6204.40 1.59
October 0.254199E+09 0.00 4615.24 0.00 321828.51 0.102039E+09 0.00 75.48 1.60
November 0.328254E+09 0.00 511.64 0.00 0.00 0.258172E+09 0.00 95.45 1.59
December 0.110108E+09 0.00 0.00 0.00 0.00 0.820092E+09 0.00 0.00 1.56
                   
Annual Sum or Average 0.142015E+10 3673619.19 27291811.88 0.00 0.448955E+09 0.376976E+10 0.00 107238.95 1.59
Minimum of Months 13546194.35 0.00 0.00 0.00 0.00 1912025.64 0.00 0.00 1.56
Maximum of Months 0.328254E+09 2941620.55 11712331.13 0.00 0.188548E+09 0.953096E+09 0.00 37131.15 1.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.197453E+11 0.00 0.00 120572.73 0.00 0.434164E+10 0.234119E+10 0.00 8.03
February 0.181161E+11 0.00 0.00 117852.97 0.00 0.109166E+10 0.183713E+10 0.00 8.01
March 0.164212E+11 0.00 0.00 174467.82 0.00 0.735740E+09 0.227191E+10 0.00 8.03
April 0.101623E+11 0.00 0.00 208725.95 74827926.54 0.572889E+09 0.134312E+10 0.00 8.25
May 0.411410E+10 0.202893E+09 3779276.08 166289.50 0.340594E+09 0.272991E+09 0.437194E+09 126892.44 8.18
June 0.104621E+10 0.690018E+09 0.102755E+09 161308.66 0.248552E+10 74194552.16 0.136374E+09 330532.74 8.10
July 0.377194E+09 0.891188E+09 0.107006E+09 52566.33 0.434744E+10 22275082.75 18663623.51 416856.02 8.23
August 0.465822E+09 0.860605E+09 41184183.96 86303.07 0.229651E+10 35681551.08 89166489.86 367150.68 8.13
September 0.289772E+10 70727968.66 3327020.26 289206.57 0.457482E+09 0.175892E+09 0.589632E+09 45987.16 8.16
October 0.808596E+10 0.00 44009.46 258547.99 8788791.54 0.273879E+09 0.127706E+10 387.87 8.18
November 0.135620E+11 0.00 0.00 225553.63 16423.44 0.381104E+09 0.192102E+10 0.00 8.15
December 0.206682E+11 0.00 0.00 136313.47 0.00 0.223076E+10 0.226525E+10 0.00 8.02
                   
Annual Sum or Average 0.115662E+12 0.271543E+10 0.258095E+09 1997708.69 0.100112E+11 0.102087E+11 0.145277E+11 1287806.91 8.12
Minimum of Months 0.377194E+09 0.00 0.00 52566.33 0.00 22275082.75 18663623.51 0.00 8.01
Maximum of Months 0.206682E+11 0.891188E+09 0.107006E+09 289206.57 0.434744E+10 0.434164E+10 0.234119E+10 416856.02 8.25



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.214447E+10 0.00 0.00 3918097.83 0.00 0.00 0.252921E+10 0.00 0.78
February 0.169742E+10 0.00 0.00 4094798.65 0.00 0.00 0.210441E+10 0.00 0.81
March 0.151985E+10 0.00 0.00 4630697.49 0.00 0.00 0.187362E+10 0.00 0.80
April 0.959565E+09 0.00 0.00 3887040.18 8189269.77 0.00 0.103156E+10 0.00 0.78
May 0.384227E+09 94470336.29 0.00 3074856.96 34514893.16 0.00 0.383356E+09 0.00 0.80
June 0.102820E+09 0.400176E+09 0.00 2013502.08 0.238040E+09 0.00 97162719.50 0.00 0.82
July 38278058.37 0.544904E+09 0.00 947395.97 0.416400E+09 0.00 18919259.03 0.00 0.81
August 46650342.18 0.474678E+09 0.00 1384912.20 0.214752E+09 0.00 55036369.83 0.00 0.86
September 0.269665E+09 47147240.05 0.00 3684523.48 44444810.15 0.00 0.406896E+09 0.00 0.82
October 0.769497E+09 26271.86 0.00 4334262.38 952828.47 0.00 0.860541E+09 0.00 0.79
November 0.130160E+10 5632.36 0.00 4136564.27 0.00 0.00 0.132164E+10 0.00 0.79
December 0.205308E+10 0.00 0.00 4069088.25 0.00 0.00 0.236440E+10 0.00 0.79
                   
Annual Sum or Average 0.112871E+11 0.156141E+10 0.00 40175739.73 0.957294E+09 0.00 0.130467E+11 0.00 0.80
Minimum of Months 38278058.37 0.00 0.00 947395.97 0.00 0.00 18919259.03 0.00 0.78
Maximum of Months 0.214447E+10 0.544904E+09 0.00 4630697.49 0.416400E+09 0.00 0.252921E+10 0.00 0.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.377050E+09 0.00 0.00 15487.82 0.00 28439059.57 18275396.38 0.00 0.29
February 0.293114E+09 0.00 0.00 34713.35 0.00 3711488.23 31843927.08 0.00 0.28
March 0.262173E+09 0.00 0.00 43824.53 0.00 0.00 37193767.68 0.00 0.28
April 0.164219E+09 0.00 0.00 41086.00 1150521.57 3928280.07 20986503.69 0.00 0.29
May 67327692.82 4084879.25 0.00 32437.07 5100247.57 2553461.70 6327540.52 0.00 0.29
June 16993643.04 14564197.07 0.00 30347.05 39218567.09 83705.63 2498712.63 0.00 0.29
July 6138715.60 19929775.71 0.00 9542.59 66082082.69 0.00 303663.98 0.00 0.29
August 7343296.60 18211804.38 0.00 28777.83 34783388.82 0.00 2057825.15 0.00 0.29
September 45347611.74 1425529.90 0.00 72382.35 7159731.17 574028.14 11927866.89 0.00 0.29
October 0.129104E+09 1268.47 0.00 67677.92 134546.79 3310783.42 19388034.23 0.00 0.29
November 0.219925E+09 0.00 0.00 47511.48 252.52 187484.18 25700908.26 0.00 0.28
December 0.352756E+09 0.00 0.00 32386.19 0.00 3374257.29 36260212.88 0.00 0.28
                   
Annual Sum or Average 0.194149E+10 58217454.78 0.00 456174.19 0.153629E+09 46162548.24 0.212764E+09 0.00 0.29
Minimum of Months 6138715.60 0.00 0.00 9542.59 0.00 0.00 303663.98 0.00 0.28
Maximum of Months 0.377050E+09 19929775.71 0.00 72382.35 66082082.69 28439059.57 37193767.68 0.00 0.29



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.136286E+11 0.00 0.00 1284700.50 0.00 0.234609E+10 0.263328E+10 0.00 2.99
February 0.119582E+11 0.00 0.00 1040742.19 0.00 0.646640E+09 0.218409E+10 0.00 2.98
March 0.109610E+11 0.00 0.00 832804.28 0.00 0.608399E+09 0.208369E+10 0.00 2.98
April 0.714221E+10 0.00 0.00 873086.68 52586128.04 47253302.63 0.129800E+10 0.00 3.06
May 0.284613E+10 0.153777E+09 156197.61 578768.94 0.230725E+09 17423792.10 0.526300E+09 28204.23 3.04
June 0.742851E+09 0.626547E+09 3694357.28 475744.82 0.167374E+10 5104092.38 0.134896E+09 114256.48 3.01
July 0.268705E+09 0.894194E+09 4120200.46 178934.98 0.285852E+10 1795597.16 23203851.68 162228.03 3.06
August 0.341559E+09 0.737836E+09 1791552.37 232305.15 0.150810E+10 3127169.13 70241483.91 163811.97 3.02
September 0.198086E+10 72886352.67 139886.38 1174156.08 0.300523E+09 8704415.99 0.583844E+09 26436.38 3.03
October 0.545167E+10 57977.01 0.00 1367124.03 6149641.22 18875067.33 0.130071E+10 0.00 3.04
November 0.928034E+10 11541.75 0.00 1143550.16 0.00 0.110040E+09 0.175730E+10 0.00 3.03
December 0.139256E+11 0.00 0.00 763848.39 0.00 0.151796E+10 0.224531E+10 0.00 2.98
                   
Annual Sum or Average 0.785277E+11 0.248531E+10 9902194.10 9945766.20 0.663034E+10 0.533141E+10 0.148409E+11 494937.08 3.02
Minimum of Months 0.268705E+09 0.00 0.00 178934.98 0.00 1795597.16 23203851.68 0.00 2.98
Maximum of Months 0.139256E+11 0.894194E+09 4120200.46 1367124.03 0.285852E+10 0.234609E+10 0.263328E+10 163811.97 3.06



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 SCHEDULING

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.405867E+09 0.00 0.00 47943.42 0.00 27558362.68 35785793.45 0.00 0.34
February 0.327822E+09 0.00 0.00 69405.25 0.00 2173473.58 43260128.83 0.00 0.34
March 0.301685E+09 0.00 0.00 55228.94 0.00 1326499.23 35593111.07 0.00 0.34
April 0.185867E+09 0.00 0.00 77075.48 1340139.61 325300.34 27189375.45 0.00 0.35
May 74272642.46 6755240.31 0.00 82088.81 5814686.81 70409.63 11456446.37 0.00 0.37
June 18660859.20 27655021.76 0.00 81506.65 41836299.72 6277.84 4700073.15 0.00 0.38
July 6721213.28 39331841.03 0.00 41457.95 71433220.23 0.00 924055.33 0.00 0.40
August 8344138.99 38368880.83 0.00 71781.53 37703484.40 0.00 3528521.62 0.00 0.42
September 48090589.94 3693278.68 0.00 210813.06 7546654.63 0.00 25805425.35 0.00 0.40
October 0.136571E+09 1561.01 0.00 213023.95 155926.38 11374.68 46566702.18 0.00 0.38
November 0.236443E+09 93.64 0.00 150079.06 0.00 240949.19 56653708.74 0.00 0.37
December 0.388304E+09 0.00 0.00 73312.70 0.00 4878983.92 52214092.66 0.00 0.34
                   
Annual Sum or Average 0.213865E+10 0.115806E+09 0.00 1173716.80 0.165830E+09 36591631.09 0.343677E+09 0.00 0.37
Minimum of Months 6721213.28 0.00 0.00 41457.95 0.00 0.00 924055.33 0.00 0.34
Maximum of Months 0.405867E+09 39331841.03 0.00 213023.95 71433220.23 27558362.68 56653708.74 0.00 0.42



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 SCRUB

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.246826E+09 0.00 0.00 0.00 0.00 32310841.10 0.00 0.00 0.29
February 0.212941E+09 0.00 0.00 0.00 0.00 6953054.87 0.00 0.00 0.29
March 0.198783E+09 0.00 0.00 0.00 0.00 4041254.87 0.00 0.00 0.29
April 0.120850E+09 0.00 0.00 2600.55 780268.94 3116842.41 2218814.15 0.00 0.29
May 47752262.88 1063089.23 0.00 4985.93 4663854.50 1390524.74 1288808.80 0.00 0.29
June 12360854.72 6274501.99 22378.20 8046.42 28547434.48 107909.08 649460.79 757.08 0.29
July 4181460.98 9960365.69 21835.15 5546.19 47677770.79 23626.67 159482.92 422.33 0.30
August 5865068.58 9148160.75 0.00 4970.99 25279864.62 5360.17 303460.19 0.00 0.30
September 36511055.80 774401.48 1272.89 13858.56 4965784.68 193664.04 1634269.98 222.27 0.29
October 98337428.22 0.00 0.00 3213.94 92108.16 1765886.86 500393.39 0.00 0.29
November 0.160024E+09 0.00 0.00 0.00 171.26 5590296.98 0.00 0.00 0.29
December 0.247528E+09 0.00 0.00 101.29 0.00 14703281.23 1679411.12 0.00 0.29
                   
Annual Sum or Average 0.139196E+10 27220519.13 45486.24 43323.87 0.112007E+09 70202543.02 8434101.34 1401.68 0.29
Minimum of Months 4181460.98 0.00 0.00 0.00 0.00 5360.17 0.00 0.00 0.29
Maximum of Months 0.247528E+09 9960365.69 22378.20 13858.56 47677770.79 32310841.10 2218814.15 757.08 0.30



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 SOIL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.318302E+10 0.00 0.00 453101.12 0.00 4627628.52 0.753788E+09 0.00 2.72
February 0.249583E+10 0.00 0.00 418741.63 0.00 1453302.44 0.641258E+09 0.00 2.72
March 0.228424E+10 0.00 0.00 370668.36 0.00 1776412.68 0.611532E+09 0.00 2.72
April 0.146611E+10 0.00 0.00 172880.01 11160913.10 9630539.27 0.325655E+09 0.00 2.79
May 0.612376E+09 32013352.44 109104.64 92470.40 49503552.44 7833834.16 99285602.80 20064.70 2.77
June 0.161807E+09 0.108408E+09 3156357.66 66539.37 0.377398E+09 2928664.81 22675916.76 59099.39 2.74
July 58069137.63 0.128584E+09 10529044.57 18675.88 0.658189E+09 1374010.09 2912269.78 85015.28 2.78
August 72545521.82 0.126648E+09 2646035.18 34314.02 0.347728E+09 1749625.08 13784391.25 72367.67 2.75
September 0.438272E+09 12850761.00 78488.82 124287.79 66350361.25 6759952.98 0.101276E+09 8343.81 2.76
October 0.117876E+10 0.00 0.00 158403.41 1317508.82 8270792.95 0.250235E+09 0.00 2.77
November 0.194368E+10 2449.63 0.00 196483.34 0.00 3153100.40 0.419203E+09 0.00 2.76
December 0.300246E+10 0.00 0.00 446923.67 0.00 1237075.98 0.749224E+09 0.00 2.72
                   
Annual Sum or Average 0.168972E+11 0.408507E+09 16519030.87 2553488.99 0.151165E+10 50794939.35 0.399083E+10 244890.84 2.75
Minimum of Months 58069137.63 0.00 0.00 18675.88 0.00 1237075.98 2912269.78 0.00 2.72
Maximum of Months 0.318302E+10 0.128584E+09 10529044.57 453101.12 0.658189E+09 9630539.27 0.753788E+09 85015.28 2.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 SOIL HOLD

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.114565E+10 0.00 0.00 8032.51 0.00 0.318663E+09 74253986.32 0.00 2.38
February 0.104064E+10 0.00 0.00 6263.36 0.00 0.136922E+09 47608043.09 0.00 2.38
March 0.990495E+09 0.00 0.00 172.92 0.00 0.138094E+09 2509443.15 0.00 2.38
April 0.537022E+09 0.00 1877474.64 0.00 2477760.56 0.166156E+09 0.00 1025.20 2.44
May 0.191019E+09 0.00 3620919.32 0.00 28139877.63 89846567.30 0.00 106807.15 2.42
June 55144123.90 7178403.94 42754340.48 0.00 0.140599E+09 18031065.42 0.00 339796.96 2.40
July 18173620.07 8786264.58 46545290.77 0.00 0.255601E+09 6171860.49 0.00 299324.34 2.44
August 30449061.57 6088398.58 24161155.35 0.00 0.155655E+09 3943006.67 0.00 312230.20 2.41
September 0.163123E+09 820156.33 8243849.12 0.00 21763357.08 50157420.08 0.00 119834.62 2.42
October 0.425218E+09 0.00 458195.31 0.00 23707.69 0.135829E+09 0.00 32339.11 2.42
November 0.792132E+09 0.00 835.87 33.70 0.00 0.130503E+09 938472.15 120.25 2.42
December 0.123543E+10 0.00 0.00 8952.07 0.00 0.163132E+09 66426571.34 0.00 2.38
                   
Annual Sum or Average 0.662449E+10 22873223.43 0.127662E+09 23454.56 0.604260E+09 0.135745E+10 0.191737E+09 1211477.84 2.41
Minimum of Months 18173620.07 0.00 0.00 0.00 0.00 3943006.67 0.00 0.00 2.38
Maximum of Months 0.123543E+10 8786264.58 46545290.77 8952.07 0.255601E+09 0.318663E+09 74253986.32 339796.96 2.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 SOIL WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.437774E+10 0.00 0.00 354926.77 0.00 14187674.31 0.843855E+09 0.00 2.53
February 0.344335E+10 0.00 0.00 316339.46 0.00 6026968.64 0.719888E+09 0.00 2.52
March 0.313407E+10 0.00 0.00 294567.22 0.00 5560609.32 0.709473E+09 0.00 2.53
April 0.202918E+10 0.00 0.00 163748.92 14825394.21 21788563.99 0.341953E+09 0.00 2.59
May 0.839631E+09 38267501.75 300263.23 93299.31 69843723.87 20695282.91 95431802.25 41576.28 2.57
June 0.214810E+09 0.122544E+09 7468613.73 71431.24 0.519453E+09 6713530.21 27437438.84 116934.27 2.54
July 76727875.04 0.156083E+09 17118523.47 20911.16 0.885830E+09 2437304.47 3667392.19 163706.23 2.59
August 95746230.61 0.154469E+09 4738545.73 37882.88 0.474397E+09 3621744.93 17638560.93 136125.39 2.55
September 0.592049E+09 13886759.05 141588.99 132522.13 91277092.24 14398723.52 0.119263E+09 15260.28 2.56
October 0.162018E+10 0.00 0.00 159415.81 1750088.68 15396940.42 0.273639E+09 0.00 2.57
November 0.268137E+10 0.00 0.00 185674.44 3253.92 9397469.90 0.452188E+09 0.00 2.56
December 0.415856E+10 0.00 0.00 312145.62 0.00 6186425.95 0.820658E+09 0.00 2.53
                   
Annual Sum or Average 0.232634E+11 0.485250E+09 29767535.15 2142864.95 0.205738E+10 0.126411E+09 0.442509E+10 473602.46 2.55
Minimum of Months 76727875.04 0.00 0.00 20911.16 0.00 2437304.47 3667392.19 0.00 2.52
Maximum of Months 0.437774E+10 0.156083E+09 17118523.47 354926.77 0.885830E+09 21788563.99 0.843855E+09 163706.23 2.59



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 STEP DOWN

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.519363E+10 0.00 0.00 344421.84 0.00 0.278161E+10 0.788550E+09 0.00 2.53
February 0.484325E+10 0.00 0.00 314514.99 0.00 0.140079E+10 0.728030E+09 0.00 2.52
March 0.491605E+10 0.00 0.00 297465.39 0.00 0.771384E+09 0.749231E+09 0.00 2.53
April 0.327348E+10 0.00 0.00 404553.40 24791033.97 0.204806E+09 0.523021E+09 0.00 2.60
May 0.135198E+10 72937748.49 71881.64 295074.20 0.108333E+09 22176797.36 0.223925E+09 12692.37 2.58
June 0.355894E+09 0.293676E+09 1306302.87 268459.68 0.791618E+09 2123641.65 58146254.89 54089.76 2.55
July 0.126845E+09 0.427605E+09 1673001.56 115226.51 0.134203E+10 679350.09 10908278.73 73743.61 2.60
August 0.161399E+09 0.351854E+09 555740.12 138477.85 0.709826E+09 1270139.94 32914027.08 67532.23 2.57
September 0.936835E+09 35815857.92 52480.29 737757.11 0.141655E+09 3018121.97 0.274006E+09 11695.80 2.58
October 0.260146E+10 27332.49 0.00 782671.65 2899166.95 10743595.86 0.581653E+09 0.00 2.59
November 0.441383E+10 5441.20 0.00 547627.57 0.00 92077165.36 0.749580E+09 0.00 2.57
December 0.565509E+10 0.00 0.00 202841.00 0.00 0.192512E+10 0.756709E+09 0.00 2.53
                   
Annual Sum or Average 0.338297E+11 0.118192E+10 3659406.48 4449091.19 0.312115E+10 0.721579E+10 0.547667E+10 219753.78 2.56
Minimum of Months 0.126845E+09 0.00 0.00 115226.51 0.00 679350.09 10908278.73 0.00 2.52
Maximum of Months 0.565509E+10 0.427605E+09 1673001.56 782671.65 0.134203E+10 0.278161E+10 0.788550E+09 73743.61 2.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 STERILE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.144259E+10 0.00 0.00 93560.91 0.00 0.112931E+09 70553481.24 0.00 0.23
February 0.118493E+10 0.00 0.00 66911.09 0.00 18667726.21 57956533.46 0.00 0.22
March 0.111694E+10 0.00 0.00 51641.81 0.00 8377129.19 34553771.72 0.00 0.22
April 0.690592E+09 0.00 0.00 46094.29 4450771.00 12826047.31 19884693.15 0.00 0.23
May 0.276363E+09 7660395.61 0.00 20208.02 25034427.84 10725659.30 3826063.26 0.00 0.23
June 72603735.47 30262078.87 275100.25 21304.84 0.168537E+09 934146.08 1561683.36 14008.29 0.23
July 24417856.68 39975833.29 515165.97 8293.39 0.284612E+09 279816.27 312470.44 11015.82 0.23
August 33086686.75 49374287.97 0.00 11731.70 0.148761E+09 74412.18 1996003.35 0.00 0.23
September 0.208647E+09 4980287.24 12984.70 92068.92 28476823.35 1610465.41 9876135.25 1638.67 0.23
October 0.552219E+09 0.00 0.00 108293.96 525398.77 8529210.64 17186351.96 0.00 0.23
November 0.900670E+09 0.00 0.00 72413.95 976.87 14914210.93 35030652.46 0.00 0.23
December 0.142471E+10 0.00 0.00 46582.92 0.00 39908974.79 51953154.31 0.00 0.22
                   
Annual Sum or Average 0.792777E+10 0.132253E+09 803250.93 639105.79 0.660399E+09 0.229778E+09 0.304691E+09 26662.79 0.23
Minimum of Months 24417856.68 0.00 0.00 8293.39 0.00 74412.18 312470.44 0.00 0.22
Maximum of Months 0.144259E+10 49374287.97 515165.97 108293.96 0.284612E+09 0.112931E+09 70553481.24 14008.29 0.23



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 STERILE STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.800340E+09 0.00 0.00 299031.99 0.00 25897980.66 0.243910E+09 0.00 0.23
February 0.598302E+09 0.00 0.00 471500.30 0.00 733742.73 0.289433E+09 0.00 0.24
March 0.542955E+09 0.00 0.00 561632.79 0.00 0.00 0.252809E+09 0.00 0.24
April 0.365012E+09 0.00 0.00 224968.75 2711545.27 0.00 88065522.98 0.00 0.22
May 0.157439E+09 6586980.26 0.00 74602.45 13535361.97 6578812.77 16115556.00 0.00 0.22
June 41555192.51 20640025.67 453252.73 38884.88 99569489.96 528401.39 3931718.59 10024.29 0.22
July 14910625.23 29006011.10 2197702.48 3087.28 0.166087E+09 208653.43 156831.38 9019.11 0.22
August 18114318.53 24090074.97 197524.89 29104.79 93322720.07 50195.62 3471330.51 1369.44 0.22
September 0.112458E+09 2293459.83 0.00 102750.67 17245801.35 4105953.28 20122041.71 0.00 0.22
October 0.304322E+09 2989.52 0.00 153385.70 317099.42 7375937.51 46839694.80 0.00 0.22
November 0.484751E+09 0.00 0.00 235228.63 595.14 0.00 0.108896E+09 0.00 0.22
December 0.734158E+09 0.00 0.00 477282.51 0.00 911878.69 0.312017E+09 0.00 0.24
                   
Annual Sum or Average 0.417432E+10 82619541.34 2848480.11 2671460.74 0.392789E+09 46391556.08 0.138577E+10 20412.84 0.23
Minimum of Months 14910625.23 0.00 0.00 3087.28 0.00 0.00 156831.38 0.00 0.22
Maximum of Months 0.800340E+09 29006011.10 2197702.48 561632.79 0.166087E+09 25897980.66 0.312017E+09 10024.29 0.24



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 STORAGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 53348052.91 0.00 0.00 0.00 0.00 0.523696E+10 0.00 0.00 0.48
February 58765657.48 0.00 0.00 0.00 0.00 0.373741E+10 0.00 0.00 0.43
March 72812426.83 0.00 0.00 0.00 0.00 0.332995E+10 0.00 0.00 0.42
April 0.135823E+09 0.00 997770.02 0.00 7972724.88 0.164168E+10 0.00 1333.44 0.36
May 0.171278E+09 0.00 14610844.05 0.00 50912094.46 0.460414E+09 0.00 187286.56 0.32
June 95152597.58 0.00 56401068.36 0.00 0.337205E+09 58895229.09 0.00 573743.26 0.30
July 40454911.68 0.00 33718566.46 0.00 0.607782E+09 10400903.06 0.00 380393.17 0.31
August 52308067.30 0.00 22993992.70 0.00 0.360593E+09 19572286.71 0.00 338714.38 0.30
September 0.291809E+09 0.00 7153581.69 0.00 56549034.76 0.157224E+09 0.00 102209.32 0.31
October 0.499612E+09 0.00 12754.67 0.00 1043879.82 0.719478E+09 0.00 2460.12 0.32
November 0.292184E+09 0.00 947.23 0.00 0.00 0.190043E+10 0.00 1021.93 0.34
December 75757127.07 0.00 0.00 0.00 0.00 0.443947E+10 0.00 0.00 0.43
                   
Annual Sum or Average 0.183930E+10 0.00 0.135890E+09 0.00 0.142206E+10 0.217119E+11 0.00 1587162.18 0.36
Minimum of Months 40454911.68 0.00 0.00 0.00 0.00 10400903.06 0.00 0.00 0.30
Maximum of Months 0.499612E+09 0.00 56401068.36 0.00 0.607782E+09 0.523696E+10 0.00 573743.26 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 SUB-STERILE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.314585E+09 0.00 0.00 0.00 0.00 0.467027E+09 0.00 0.00 0.34
February 0.325919E+09 0.00 0.00 0.00 0.00 0.259294E+09 0.00 0.00 0.32
March 0.341496E+09 0.00 0.00 0.00 0.00 0.187983E+09 0.00 0.00 0.32
April 0.256342E+09 0.00 0.00 5297.49 1992841.89 65487494.68 3162498.25 0.00 0.32
May 0.114212E+09 5216468.17 0.00 36928.94 9971093.67 9515682.91 5700182.49 185.83 0.32
June 30708983.81 26516678.07 242764.48 72555.71 70342605.17 233837.11 3630924.92 2978.29 0.33
July 10443630.09 51776252.61 27390.97 51415.76 0.113461E+09 30894.67 1111210.38 828.64 0.36
August 14976840.03 36215502.20 0.00 41405.07 63130095.78 22914.58 1002204.56 8.65 0.35
September 91959762.51 3005309.48 13746.52 75805.51 12633899.16 874668.24 6695975.40 1006.34 0.33
October 0.231422E+09 0.00 0.00 16565.92 235248.38 24080073.03 2274453.55 0.00 0.32
November 0.338074E+09 0.00 0.00 0.00 437.39 89373977.76 0.00 0.00 0.32
December 0.360855E+09 0.00 0.00 0.00 0.00 0.345963E+09 0.00 0.00 0.32
                   
Annual Sum or Average 0.243100E+10 0.122730E+09 283901.97 299974.40 0.271767E+09 0.144989E+10 23577449.54 5007.75 0.33
Minimum of Months 10443630.09 0.00 0.00 0.00 0.00 22914.58 0.00 0.00 0.32
Maximum of Months 0.360855E+09 51776252.61 242764.48 75805.51 0.113461E+09 0.467027E+09 6695975.40 2978.29 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 UTILITY HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 51980161.97 0.00 0.00 0.00 0.00 0.130915E+10 0.00 0.00 0.44
February 70538965.78 0.00 0.00 0.00 0.00 0.914263E+09 0.00 0.00 0.40
March 0.107128E+09 0.00 0.00 0.00 0.00 0.757101E+09 0.00 0.00 0.39
April 0.148497E+09 0.00 0.00 0.00 2648973.16 0.319304E+09 0.00 0.00 0.35
May 0.108800E+09 0.00 283117.46 0.00 19094636.41 67670590.02 0.00 9476.35 0.33
June 40041387.33 4139597.18 4860210.55 0.00 0.107110E+09 4754873.07 0.00 58081.41 0.32
July 14007778.10 4835365.42 2207507.42 0.00 0.182302E+09 877690.85 0.00 24236.47 0.33
August 19574359.14 350494.77 575626.70 0.00 0.112344E+09 1452434.87 0.00 21399.57 0.32
September 0.102328E+09 0.00 538096.05 0.00 18279568.70 28308967.34 0.00 9799.34 0.32
October 0.208261E+09 0.00 4198.31 0.00 308210.27 0.142652E+09 0.00 293.93 0.33
November 0.212993E+09 0.00 427.43 0.00 0.00 0.401219E+09 0.00 153.97 0.35
December 0.106439E+09 0.00 0.00 0.00 0.00 0.107077E+10 0.00 0.00 0.41
                   
Annual Sum or Average 0.119059E+10 9325457.38 8469183.92 0.00 0.442087E+09 0.501753E+10 0.00 123441.03 0.36
Minimum of Months 14007778.10 0.00 0.00 0.00 0.00 877690.85 0.00 0.00 0.32
Maximum of Months 0.212993E+09 4835365.42 4860210.55 0.00 0.182302E+09 0.130915E+10 0.00 58081.41 0.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.120535E+09 0.00 0.00 0.00 0.00 19220767.99 0.00 0.00 0.29
February 0.104304E+09 0.00 0.00 0.00 0.00 5420411.26 0.00 0.00 0.28
March 96882716.02 0.00 0.00 0.00 0.00 4258359.38 0.00 0.00 0.28
April 59826355.35 0.00 0.00 0.00 388784.30 3129485.86 0.00 0.00 0.29
May 23716181.39 125484.12 0.00 74.20 2718612.21 1421142.63 83273.69 0.00 0.29
June 6334095.43 2140332.68 71866.75 989.01 14937135.33 111456.05 96698.11 1080.08 0.29
July 2100670.67 3634174.28 39072.74 844.59 24592092.83 30848.82 45695.43 522.93 0.30
August 3033916.35 3233555.35 52.44 310.27 13607895.32 5043.94 30932.93 0.54 0.29
September 18502005.54 292920.56 13292.00 1702.53 2485241.65 255451.11 305341.93 184.10 0.29
October 48771948.15 0.00 0.00 119.03 45894.70 1308515.61 68318.94 0.00 0.29
November 79006250.70 0.00 0.00 0.00 85.33 3532554.31 0.00 0.00 0.29
December 0.122949E+09 0.00 0.00 0.00 0.00 8735550.05 0.00 0.00 0.29
                   
Annual Sum or Average 0.685962E+09 9426466.99 124283.93 4039.63 58775741.67 47429587.01 630261.02 1787.65 0.29
Minimum of Months 2100670.67 0.00 0.00 0.00 0.00 5043.94 0.00 0.00 0.28
Maximum of Months 0.122949E+09 3634174.28 71866.75 1702.53 24592092.83 19220767.99 305341.93 1080.08 0.30



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 UTILITY ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.298215E+09 0.00 0.00 0.00 0.00 0.958330E+09 0.00 0.00 0.30
February 0.353348E+09 0.00 0.00 0.00 0.00 0.559060E+09 0.00 0.00 0.27
March 0.362133E+09 0.00 0.00 0.00 0.00 0.431380E+09 0.00 0.00 0.25
April 0.305136E+09 0.00 0.00 0.00 2723884.14 0.151683E+09 0.00 0.00 0.25
May 0.142029E+09 826060.91 6077.38 0.00 19096251.06 35462792.37 0.00 1300.51 0.24
June 44636520.66 17065267.74 1150073.22 2245.69 0.104104E+09 709591.34 495368.95 11406.01 0.24
July 14745404.41 40406148.82 84425.58 10367.51 0.162341E+09 93748.94 410580.22 2415.81 0.24
August 21278923.16 23510732.99 5417.09 6871.10 96599980.08 124157.26 131565.36 738.94 0.24
September 0.126881E+09 2066225.09 102015.87 17.49 17391841.54 6828198.95 52397.94 3795.80 0.24
October 0.280009E+09 0.00 0.00 0.00 321545.50 75215725.19 0.00 0.00 0.24
November 0.396048E+09 0.00 467.25 0.00 0.00 0.214301E+09 0.00 130.59 0.25
December 0.370386E+09 0.00 0.00 0.00 0.00 0.720229E+09 0.00 0.00 0.27
                   
Annual Sum or Average 0.271485E+10 83874435.56 1348476.39 19501.79 0.402579E+09 0.315342E+10 1089912.47 19787.66 0.25
Minimum of Months 14745404.41 0.00 0.00 0.00 0.00 93748.94 0.00 0.00 0.24
Maximum of Months 0.396048E+09 40406148.82 1150073.22 10367.51 0.162341E+09 0.958330E+09 495368.95 11406.01 0.30



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 1 VESTIBULE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 17951.98 0.00 0.00 0.00 0.00 0.587340E+09 0.00 0.00 0.65
February 532846.77 0.00 0.00 0.00 0.00 0.452047E+09 0.00 0.00 0.64
March 2499684.35 0.00 0.00 0.00 0.00 0.408170E+09 0.00 0.00 0.64
April 10360099.22 0.00 0.00 0.00 735077.60 0.203128E+09 0.00 0.00 0.54
May 22020786.55 10261146.54 392030.27 2559.26 3020081.33 46212797.13 5925.03 153025.65 0.49
June 8940719.92 38272717.85 4300656.89 30462.94 21786897.68 7485142.81 146134.75 812313.01 0.50
July 3403983.43 46412988.57 3960777.84 156.08 40571515.72 1630952.71 816.38 1048993.55 0.51
August 3988231.39 31965746.90 5587247.49 0.00 21531970.96 4317478.44 0.00 2143454.38 0.50
September 18131677.10 1849158.86 971248.42 8109.52 4159258.91 35967772.71 11818.39 759331.81 0.45
October 32285674.07 0.00 867.38 0.00 85526.90 0.120219E+09 0.00 525.02 0.49
November 14119281.87 0.00 0.00 0.00 0.00 0.280365E+09 0.00 403.34 0.58
December 23960.38 0.00 0.00 0.00 0.00 0.532845E+09 0.00 0.00 0.64
                   
Annual Sum or Average 0.116325E+09 0.128762E+09 15212828.28 41287.80 91890329.11 0.267973E+10 164694.55 4918046.75 0.55
Minimum of Months 17951.98 0.00 0.00 0.00 0.00 1630952.71 0.00 0.00 0.45
Maximum of Months 32285674.07 46412988.57 5587247.49 30462.94 40571515.72 0.587340E+09 146134.75 2143454.38 0.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 CONFERENCE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.113457E+10 0.00 0.00 929019.43 0.00 0.634648E+09 0.896757E+09 0.00 0.83
February 0.105334E+10 0.00 0.00 1301929.12 0.00 0.302623E+09 0.897003E+09 0.00 0.93
March 0.112512E+10 0.00 0.00 1609598.26 0.00 0.172563E+09 0.102292E+10 0.00 1.03
April 0.994892E+09 0.00 0.00 1862867.79 106645.53 33446669.58 0.696596E+09 0.00 1.31
May 0.773005E+09 39580955.11 0.00 1758554.02 2266947.74 1219406.29 0.427276E+09 0.00 1.79
June 0.440555E+09 0.220453E+09 89586.08 1468047.15 96097273.81 367947.20 0.259798E+09 2691.58 1.80
July 0.307084E+09 0.298710E+09 396144.01 840583.11 0.135720E+09 271063.17 94757888.90 4938.56 1.52
August 0.388953E+09 0.239005E+09 0.00 1206704.46 88011448.59 287082.19 0.216205E+09 0.00 2.02
September 0.835498E+09 15731167.26 0.00 1928130.42 10998023.75 978194.71 0.536402E+09 0.00 2.02
October 0.103621E+10 0.00 0.00 1771051.36 0.00 32065227.79 0.671404E+09 0.00 1.39
November 0.950306E+09 0.00 0.00 1327866.85 0.00 0.213127E+09 0.757010E+09 0.00 1.08
December 0.109641E+10 0.00 0.00 751659.35 0.00 0.594658E+09 0.727614E+09 0.00 0.81
                   
Annual Sum or Average 0.101359E+11 0.813479E+09 485730.08 16756011.31 0.333200E+09 0.198625E+10 0.720375E+10 7630.14 1.38
Minimum of Months 0.307084E+09 0.00 0.00 751659.35 0.00 271063.17 94757888.90 0.00 0.81
Maximum of Months 0.113457E+10 0.298710E+09 396144.01 1928130.42 0.135720E+09 0.634648E+09 0.102292E+10 4938.56 2.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.534347E+09 0.00 0.00 0.00 0.00 0.105917E+09 0.00 0.00 1.04
February 0.463066E+09 0.00 0.00 0.00 0.00 52650082.35 0.00 0.00 1.09
March 0.486993E+09 0.00 0.00 0.00 0.00 30030164.73 0.00 0.00 1.18
April 0.368693E+09 0.00 0.00 0.00 28304.72 15314929.80 0.00 0.00 1.49
May 0.267171E+09 0.00 12225.45 0.00 6639067.14 9518470.11 0.00 508.35 2.11
June 0.156549E+09 0.00 492659.37 0.00 60071539.43 3927857.37 0.00 4917.42 2.11
July 95385492.36 0.00 1711238.90 0.00 86882917.34 3002628.94 0.00 7581.54 1.81
August 0.137880E+09 0.00 75200.72 0.00 60566230.54 3160977.13 0.00 1900.49 2.39
September 0.301886E+09 0.00 0.00 0.00 5003981.46 5811486.09 0.00 0.00 2.38
October 0.377983E+09 0.00 0.00 0.00 0.00 14734157.43 0.00 0.00 1.61
November 0.391540E+09 0.00 0.00 0.00 0.00 47253584.28 0.00 0.00 1.28
December 0.518316E+09 0.00 0.00 0.00 0.00 83635268.58 0.00 0.00 1.05
                   
Annual Sum or Average 0.409981E+10 0.00 2291324.44 0.00 0.219192E+09 0.374956E+09 0.00 14907.80 1.63
Minimum of Months 95385492.36 0.00 0.00 0.00 0.00 3002628.94 0.00 0.00 1.04
Maximum of Months 0.534347E+09 0.00 1711238.90 0.00 86882917.34 0.105917E+09 0.00 7581.54 2.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 DICTATION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 82285135.74 0.00 0.00 99450.23 0.00 1487068.21 93832823.99 0.00 0.26
February 60715130.73 0.00 0.00 141018.60 0.00 155596.13 99382887.55 0.00 0.31
March 59297438.10 0.00 0.00 184891.68 0.00 33118.30 0.110296E+09 0.00 0.36
April 52671547.35 0.00 0.00 161403.36 6089.95 12514.35 61945120.58 0.00 0.40
May 42924706.48 2481806.42 0.00 124384.60 120648.14 13981.20 30679881.76 0.00 0.53
June 25592404.99 13532716.45 0.00 94803.42 5177054.10 2999.75 16926495.42 0.00 0.51
July 17776237.05 16580423.30 4974.41 45891.09 8492584.31 3880.28 4830804.43 33.50 0.41
August 22222627.31 14186238.81 0.00 76701.84 4747528.90 0.00 15682578.16 0.00 0.58
September 44895308.90 811279.30 0.00 144971.37 625890.86 4668.77 43801321.13 0.00 0.60
October 54738209.14 0.00 0.00 151072.43 0.00 20446.18 60513000.71 0.00 0.43
November 58707655.63 0.00 0.00 136935.65 0.00 66136.59 72865630.81 0.00 0.36
December 72052953.93 0.00 0.00 126102.09 0.00 940945.29 0.102126E+09 0.00 0.28
                   
Annual Sum or Average 0.593879E+09 47592464.28 4974.41 1487626.35 19169796.26 2741355.05 0.712882E+09 33.50 0.42
Minimum of Months 17776237.05 0.00 0.00 45891.09 0.00 0.00 4830804.43 0.00 0.26
Maximum of Months 82285135.74 16580423.30 4974.41 184891.68 8492584.31 1487068.21 0.110296E+09 33.50 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.199294E+10 0.00 0.00 11261.90 0.00 0.195402E+10 78771173.93 0.00 1.17
February 0.199875E+10 0.00 0.00 101504.05 0.00 0.109150E+10 0.155601E+09 0.00 1.22
March 0.246863E+10 0.00 0.00 192384.96 0.00 0.486752E+09 0.307334E+09 0.00 1.33
April 0.204865E+10 0.00 0.00 448960.70 177969.65 57438659.53 0.327343E+09 0.00 1.68
May 0.146307E+10 40985207.08 51550.14 418307.86 3988979.07 8396968.02 0.272594E+09 603.83 2.37
June 0.855872E+09 0.214575E+09 532820.76 384690.52 0.181685E+09 3163566.61 0.151573E+09 21144.58 2.38
July 0.570755E+09 0.289640E+09 1039587.81 197278.08 0.279845E+09 1842017.43 46412335.92 27807.62 2.04
August 0.728628E+09 0.222497E+09 318747.12 216577.07 0.169947E+09 3929825.53 0.154863E+09 10490.32 2.68
September 0.153935E+10 11508440.82 0.00 465159.57 21152183.35 7606209.25 0.391975E+09 0.00 2.68
October 0.207582E+10 0.00 0.00 362003.09 0.00 63337281.53 0.338344E+09 0.00 1.80
November 0.211728E+10 0.00 0.00 105414.84 0.00 0.416708E+09 0.225074E+09 0.00 1.43
December 0.210530E+10 0.00 0.00 372.49 0.00 0.166217E+10 17379766.26 0.00 1.18
                   
Annual Sum or Average 0.199651E+11 0.779206E+09 1942705.83 2903915.11 0.656796E+09 0.575686E+10 0.246727E+10 60046.35 1.83
Minimum of Months 0.570755E+09 0.00 0.00 372.49 0.00 1842017.43 17379766.26 0.00 1.17
Maximum of Months 0.246863E+10 0.289640E+09 1039587.81 465159.57 0.279845E+09 0.195402E+10 0.391975E+09 27807.62 2.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.631610E+10 0.00 0.00 163963.03 0.00 0.206208E+09 0.181644E+10 0.00 1.61
February 0.527437E+10 0.00 0.00 243841.26 0.00 81397012.10 0.136078E+10 0.00 1.69
March 0.508985E+10 0.00 0.00 381071.77 0.00 38484612.10 0.160509E+10 0.00 1.83
April 0.402965E+10 0.00 0.00 417786.92 368646.06 19684034.61 0.951637E+09 0.00 2.30
May 0.304766E+10 74745009.83 99437.72 285922.03 11781273.92 10853750.69 0.544855E+09 8593.94 3.25
June 0.178617E+10 0.335092E+09 1404559.08 265119.81 0.452318E+09 7025314.37 0.296617E+09 50004.08 3.25
July 0.119095E+10 0.448778E+09 2899232.69 119465.12 0.702219E+09 4617027.70 85735883.30 69840.25 2.79
August 0.151449E+10 0.401447E+09 640141.50 193999.94 0.387701E+09 6762106.79 0.315496E+09 41840.42 3.68
September 0.317355E+10 21358203.00 0.00 412204.14 43814599.41 9637128.90 0.823908E+09 0.00 3.68
October 0.395098E+10 0.00 0.00 416162.61 0.00 15014178.15 0.114841E+10 0.00 2.48
November 0.433726E+10 0.00 0.00 354130.24 0.00 80179237.61 0.129714E+10 0.00 1.98
December 0.613933E+10 0.00 0.00 123706.30 0.00 0.137255E+09 0.156321E+10 0.00 1.63
                   
Annual Sum or Average 0.458504E+11 0.128142E+10 5043370.99 3377373.18 0.159820E+10 0.617118E+09 0.118093E+11 170278.69 2.52
Minimum of Months 0.119095E+10 0.00 0.00 119465.12 0.00 4617027.70 85735883.30 0.00 1.61
Maximum of Months 0.631610E+10 0.448778E+09 2899232.69 417786.92 0.702219E+09 0.206208E+09 0.181644E+10 69840.25 3.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.829146E+10 0.00 0.00 293061.94 0.00 0.299737E+09 0.252706E+10 0.00 1.61
February 0.688563E+10 0.00 0.00 414274.16 0.00 0.111936E+09 0.195773E+10 0.00 1.69
March 0.676737E+10 0.00 0.00 554897.66 0.00 59499858.14 0.215097E+10 0.00 1.83
April 0.537235E+10 0.00 0.00 556887.58 491528.07 31243116.32 0.126437E+10 0.00 2.30
May 0.409558E+10 91284447.86 131253.31 347036.21 24083930.47 21729841.65 0.687214E+09 12788.91 3.25
June 0.239518E+10 0.433070E+09 1963897.46 320629.88 0.616715E+09 11212741.39 0.380055E+09 69847.06 3.25
July 0.159938E+10 0.544902E+09 5155021.87 140690.05 0.988463E+09 7477740.08 0.101566E+09 100792.55 2.79
August 0.203408E+10 0.524362E+09 848974.74 225506.45 0.527835E+09 12514482.63 0.402446E+09 60334.48 3.68
September 0.425244E+10 28477604.01 0.00 519249.66 58419465.88 18058059.11 0.107233E+10 0.00 3.68
October 0.528870E+10 0.00 0.00 551485.66 0.00 25511898.57 0.150500E+10 0.00 2.48
November 0.573536E+10 0.00 0.00 517920.39 0.00 0.111598E+09 0.177243E+10 0.00 1.98
December 0.796005E+10 0.00 0.00 193423.57 0.00 0.204583E+09 0.228840E+10 0.00 1.63
                   
Annual Sum or Average 0.606776E+11 0.162210E+10 8099147.38 4635063.20 0.221601E+10 0.915101E+09 0.161096E+11 243763.00 2.52
Minimum of Months 0.159938E+10 0.00 0.00 140690.05 0.00 7477740.08 0.101566E+09 0.00 1.61
Maximum of Months 0.829146E+10 0.544902E+09 5155021.87 556887.58 0.988463E+09 0.299737E+09 0.252706E+10 100792.55 3.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.632765E+09 0.00 0.00 164868.09 0.00 0.235797E+09 0.188542E+09 0.00 1.31
February 0.525163E+09 0.00 0.00 250735.82 0.00 0.119590E+09 0.214666E+09 0.00 1.40
March 0.595894E+09 0.00 0.00 256489.98 0.00 57870728.56 0.202099E+09 0.00 1.50
April 0.505758E+09 0.00 0.00 238141.18 45793.60 12262878.12 0.111836E+09 0.00 1.87
May 0.377927E+09 9516813.08 12765.66 105939.28 1238784.18 3146430.38 66500713.41 654.14 2.60
June 0.221399E+09 46318618.87 190879.45 83587.09 51517867.31 1144420.73 37005124.95 6244.81 2.60
July 0.148858E+09 67714286.17 438022.48 44813.40 75185746.69 884093.17 9393291.87 8778.25 2.23
August 0.189864E+09 55446779.07 81621.54 57501.69 43368332.58 1155464.87 37112350.35 3094.96 2.95
September 0.391787E+09 3266845.51 0.00 205605.24 5400137.80 2289276.72 0.106064E+09 0.00 2.97
October 0.516093E+09 0.00 0.00 207968.32 0.00 16473082.93 0.114368E+09 0.00 2.04
November 0.515174E+09 0.00 0.00 165073.10 0.00 62919914.24 0.149018E+09 0.00 1.62
December 0.663406E+09 0.00 0.00 76414.14 0.00 0.191643E+09 0.123058E+09 0.00 1.30
                   
Annual Sum or Average 0.528409E+10 0.182263E+09 723289.14 1857137.35 0.176757E+09 0.705177E+09 0.135966E+10 18772.16 2.04
Minimum of Months 0.148858E+09 0.00 0.00 44813.40 0.00 884093.17 9393291.87 0.00 1.30
Maximum of Months 0.663406E+09 67714286.17 438022.48 256489.98 75185746.69 0.235797E+09 0.214666E+09 8778.25 2.97



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.392874E+10 0.00 0.00 3009.03 0.00 0.624351E+09 0.124631E+09 0.00 1.39
February 0.327116E+10 0.00 0.00 20433.76 0.00 0.207070E+09 0.289539E+09 0.00 1.46
March 0.283758E+10 0.00 0.00 202233.33 0.00 84484510.76 0.855072E+09 0.00 1.58
April 0.206968E+10 0.00 0.00 859205.18 206792.75 12261790.59 0.728579E+09 0.00 1.99
May 0.153199E+10 43799261.09 57599.65 850007.96 4737831.85 4325887.99 0.487920E+09 3000.92 2.82
June 0.876918E+09 0.259437E+09 564543.01 979959.40 0.182546E+09 1538595.08 0.296596E+09 17376.78 2.83
July 0.613166E+09 0.378611E+09 1022360.84 537189.26 0.267724E+09 1263508.24 0.104537E+09 20306.97 2.42
August 0.800074E+09 0.269959E+09 371298.58 402947.50 0.172750E+09 3014792.51 0.227110E+09 11260.55 3.19
September 0.163612E+10 13280477.72 0.00 700257.78 23278336.91 4471349.53 0.607463E+09 0.00 3.19
October 0.217888E+10 0.00 0.00 277653.87 0.00 10974890.11 0.679085E+09 0.00 2.14
November 0.255468E+10 0.00 0.00 83199.29 0.00 70666325.74 0.580370E+09 0.00 1.71
December 0.381702E+10 0.00 0.00 5843.87 0.00 0.416565E+09 0.164231E+09 0.00 1.41
                   
Annual Sum or Average 0.261160E+11 0.965087E+09 2015802.08 4921940.24 0.651244E+09 0.144099E+10 0.514513E+10 51945.22 2.18
Minimum of Months 0.613166E+09 0.00 0.00 3009.03 0.00 1263508.24 0.104537E+09 0.00 1.39
Maximum of Months 0.392874E+10 0.378611E+09 1022360.84 979959.40 0.267724E+09 0.624351E+09 0.855072E+09 20306.97 3.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.254285E+10 0.00 0.00 229.72 0.00 0.699239E+09 23986171.30 0.00 1.51
February 0.220031E+10 0.00 0.00 2640.13 0.00 0.357502E+09 72924999.74 0.00 1.58
March 0.214988E+10 0.00 0.00 21848.21 0.00 0.153433E+09 0.334071E+09 0.00 1.72
April 0.167070E+10 0.00 0.00 57415.17 144386.37 18676394.51 0.269440E+09 0.00 2.16
May 0.120727E+10 28531805.82 39042.76 89655.65 5357655.32 6804049.63 0.197261E+09 3269.64 3.06
June 0.700724E+09 0.137566E+09 550556.62 103877.64 0.170836E+09 3120174.89 0.114666E+09 19147.28 3.06
July 0.466704E+09 0.181514E+09 987074.00 47521.25 0.269442E+09 1975641.57 33164638.78 26955.45 2.62
August 0.597801E+09 0.147672E+09 251627.99 66377.67 0.161411E+09 2958621.67 0.118645E+09 15481.59 3.46
September 0.127065E+10 8015545.05 0.00 105795.44 17510469.23 6053333.97 0.292797E+09 0.00 3.46
October 0.165804E+10 0.00 0.00 51933.52 0.00 14691261.89 0.330522E+09 0.00 2.33
November 0.186910E+10 0.00 0.00 20837.27 0.00 0.109102E+09 0.260120E+09 0.00 1.86
December 0.242739E+10 0.00 0.00 690.53 0.00 0.598419E+09 44829738.33 0.00 1.53
                   
Annual Sum or Average 0.187614E+11 0.503299E+09 1828301.38 568822.21 0.624702E+09 0.197197E+10 0.209243E+10 64853.96 2.37
Minimum of Months 0.466704E+09 0.00 0.00 229.72 0.00 1975641.57 23986171.30 0.00 1.51
Maximum of Months 0.254285E+10 0.181514E+09 987074.00 105795.44 0.269442E+09 0.699239E+09 0.334071E+09 26955.45 3.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 7

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.953104E+10 0.00 0.00 105421.12 0.00 0.421909E+09 0.227735E+10 0.00 1.61
February 0.796161E+10 0.00 0.00 147407.72 0.00 77671722.38 0.181185E+10 0.00 1.69
March 0.753533E+10 0.00 0.00 349464.85 0.00 53799335.68 0.228676E+10 0.00 1.83
April 0.597819E+10 0.00 0.00 387382.03 540680.88 29410709.68 0.132738E+10 0.00 2.30
May 0.449084E+10 95510543.72 144693.50 367422.47 31394672.45 15533047.96 0.778617E+09 13752.93 3.25
June 0.261894E+10 0.465672E+09 2027112.34 356905.89 0.689228E+09 10052244.03 0.436098E+09 73274.14 3.25
July 0.174800E+10 0.587489E+09 4489705.92 152901.41 0.110040E+10 6931293.81 0.124337E+09 104696.91 2.79
August 0.222704E+10 0.516240E+09 934700.43 250628.08 0.641177E+09 10219192.94 0.456673E+09 65539.72 3.68
September 0.473532E+10 29418422.82 0.00 464718.18 66168354.05 14367809.62 0.112753E+10 0.00 3.68
October 0.595120E+10 0.00 0.00 376563.27 0.00 21025843.03 0.152913E+10 0.00 2.48
November 0.651373E+10 0.00 0.00 295226.52 0.00 55193740.12 0.181268E+10 0.00 1.98
December 0.916552E+10 0.00 0.00 133233.86 0.00 0.119189E+09 0.221371E+10 0.00 1.63
                   
Annual Sum or Average 0.684568E+11 0.169433E+10 7596212.20 3387275.40 0.252891E+10 0.835302E+09 0.161821E+11 257263.70 2.52
Minimum of Months 0.174800E+10 0.00 0.00 105421.12 0.00 6931293.81 0.124337E+09 0.00 1.61
Maximum of Months 0.953104E+10 0.587489E+09 4489705.92 464718.18 0.110040E+10 0.421909E+09 0.228676E+10 104696.91 3.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 8

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.325636E+10 0.00 0.00 3554.42 0.00 0.541150E+09 80082802.98 0.00 1.50
February 0.272745E+10 0.00 0.00 11831.01 0.00 0.233193E+09 0.162648E+09 0.00 1.57
March 0.251806E+10 0.00 0.00 67395.28 0.00 89728000.15 0.523360E+09 0.00 1.70
April 0.192347E+10 0.00 0.00 126798.79 171420.42 11036251.87 0.391014E+09 0.00 2.14
May 0.139784E+10 36065876.24 47459.82 174377.73 4168845.70 4608818.25 0.273076E+09 2774.91 3.03
June 0.816743E+09 0.200022E+09 625244.43 181524.18 0.166155E+09 2637961.44 0.152324E+09 19107.62 3.03
July 0.550146E+09 0.264816E+09 928243.06 79430.40 0.270822E+09 1956637.04 43681236.50 28144.99 2.60
August 0.699828E+09 0.198243E+09 302885.93 118329.23 0.168711E+09 2754217.72 0.151479E+09 14235.67 3.43
September 0.148667E+10 9931564.40 0.00 211759.27 20373788.72 4167450.10 0.372447E+09 0.00 3.42
October 0.192086E+10 0.00 0.00 123321.82 0.00 8225889.99 0.449186E+09 0.00 2.30
November 0.217541E+10 0.00 0.00 64423.43 0.00 65179626.84 0.416786E+09 0.00 1.84
December 0.307448E+10 0.00 0.00 6134.20 0.00 0.414570E+09 0.156507E+09 0.00 1.51
                   
Annual Sum or Average 0.225473E+11 0.709079E+09 1903833.24 1168879.75 0.630402E+09 0.137921E+10 0.317259E+10 64263.18 2.34
Minimum of Months 0.550146E+09 0.00 0.00 3554.42 0.00 1956637.04 43681236.50 0.00 1.50
Maximum of Months 0.325636E+10 0.264816E+09 928243.06 211759.27 0.270822E+09 0.541150E+09 0.523360E+09 28144.99 3.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM 9

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.498460E+10 0.00 0.00 38933.87 0.00 0.252062E+09 0.878498E+09 0.00 1.61
February 0.406210E+10 0.00 0.00 65597.47 0.00 46182912.20 0.817292E+09 0.00 1.69
March 0.379693E+10 0.00 0.00 176911.38 0.00 24738967.09 0.111628E+10 0.00 1.83
April 0.299103E+10 0.00 0.00 213962.79 270340.44 11366757.59 0.665074E+09 0.00 2.30
May 0.222295E+10 55162199.76 74321.61 217676.65 8290408.33 6526637.91 0.412978E+09 4901.60 3.25
June 0.129936E+10 0.266571E+09 985482.80 217005.43 0.310913E+09 4343048.39 0.228803E+09 30699.65 3.25
July 0.871037E+09 0.332955E+09 1545788.92 96699.00 0.511695E+09 3177582.97 65400655.80 45309.25 2.79
August 0.111058E+10 0.283528E+09 476408.82 156536.97 0.295180E+09 4343569.17 0.232013E+09 23711.26 3.68
September 0.234941E+10 15324950.03 0.00 286367.69 32468438.41 5933060.83 0.583206E+09 0.00 3.68
October 0.296057E+10 0.00 0.00 221657.48 0.00 8609360.59 0.781469E+09 0.00 2.48
November 0.328340E+10 0.00 0.00 161806.72 0.00 29195477.27 0.878192E+09 0.00 1.98
December 0.472346E+10 0.00 0.00 57541.68 0.00 63577100.52 0.962180E+09 0.00 1.63
                   
Annual Sum or Average 0.346554E+11 0.953541E+09 3082002.15 1910697.14 0.115882E+10 0.460056E+09 0.762138E+10 104621.76 2.52
Minimum of Months 0.871037E+09 0.00 0.00 38933.87 0.00 3177582.97 65400655.80 0.00 1.61
Maximum of Months 0.498460E+10 0.332955E+09 1545788.92 286367.69 0.511695E+09 0.252062E+09 0.111628E+10 45309.25 3.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM HALL 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.158444E+09 0.00 0.00 12345.41 0.00 99283759.30 12251600.33 0.00 0.15
February 0.147375E+09 0.00 0.00 28258.47 0.00 45640076.94 21614470.19 0.00 0.16
March 0.166100E+09 0.00 0.00 38300.43 0.00 20801501.38 28502428.98 0.00 0.18
April 0.127978E+09 0.00 0.00 80556.44 11063.47 5594061.00 29453531.33 0.00 0.23
May 93746377.88 4713651.83 0.00 73735.92 244059.44 2168213.86 18179347.91 0.00 0.33
June 53541376.91 21693479.54 41946.52 70416.29 12512924.62 570241.88 13045183.32 894.62 0.33
July 36337230.89 26196140.20 112007.82 35817.71 19135080.51 262075.92 2591854.40 1552.58 0.28
August 46827801.15 23070339.34 0.00 49486.85 11120317.19 144777.34 10762364.75 0.00 0.37
September 99250518.49 1434717.32 0.00 99855.91 1339628.46 667637.52 29635242.40 0.00 0.36
October 0.132280E+09 0.00 0.00 78225.43 0.00 5946647.96 27243942.57 0.00 0.25
November 0.132343E+09 0.00 0.00 38144.81 0.00 26679023.87 23495584.43 0.00 0.19
December 0.164109E+09 0.00 0.00 921.82 0.00 76467492.80 3389771.43 0.00 0.15
                   
Annual Sum or Average 0.135833E+10 77108328.23 153954.34 606065.48 44363073.69 0.284226E+09 0.220165E+09 2447.20 0.25
Minimum of Months 36337230.89 0.00 0.00 921.82 0.00 144777.34 2591854.40 0.00 0.15
Maximum of Months 0.166100E+09 26196140.20 112007.82 99855.91 19135080.51 99283759.30 29635242.40 1552.58 0.37



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM HALL 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.189296E+09 0.00 0.00 31456.45 0.00 73008843.35 28752478.32 0.00 0.16
February 0.160320E+09 0.00 0.00 50908.73 0.00 25625470.45 37631828.98 0.00 0.17
March 0.163662E+09 0.00 0.00 60960.21 0.00 9046957.94 45842955.24 0.00 0.18
April 0.126230E+09 0.00 0.00 82184.64 11060.21 4274171.64 32611267.15 0.00 0.23
May 94380544.40 3653203.23 0.00 56367.44 300535.69 2564241.24 15723184.33 0.00 0.32
June 54507562.77 15573721.21 68494.54 54540.46 13690077.87 804249.11 10366659.87 2023.79 0.31
July 36761061.91 17825111.82 215354.53 22453.19 22366157.43 609113.39 1503866.89 4231.54 0.27
August 47871984.01 17516236.23 0.00 36059.99 12409367.05 431390.08 8823150.03 0.00 0.35
September 98142177.01 1135774.90 0.00 90011.23 1372584.17 1063325.44 29439313.71 0.00 0.36
October 0.129210E+09 0.00 0.00 85564.90 0.00 4810169.32 32225828.30 0.00 0.25
November 0.131493E+09 0.00 0.00 64652.57 0.00 17929938.55 39845044.23 0.00 0.20
December 0.190119E+09 0.00 0.00 13559.42 0.00 44071913.19 17171240.51 0.00 0.15
                   
Annual Sum or Average 0.142199E+10 55704047.40 283849.07 648719.21 50149782.41 0.184240E+09 0.299937E+09 6255.33 0.25
Minimum of Months 36761061.91 0.00 0.00 13559.42 0.00 431390.08 1503866.89 0.00 0.15
Maximum of Months 0.190119E+09 17825111.82 215354.53 90011.23 22366157.43 73008843.35 45842955.24 4231.54 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM HALL 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.187246E+09 0.00 0.00 40866.00 0.00 67233681.01 36011985.68 0.00 0.17
February 0.156856E+09 0.00 0.00 60446.05 0.00 23220537.45 44966662.86 0.00 0.17
March 0.163411E+09 0.00 0.00 64759.12 0.00 10586782.33 46387319.77 0.00 0.18
April 0.127727E+09 0.00 0.00 76641.14 11095.70 5928032.54 29681374.18 0.00 0.23
May 95862367.76 2923956.58 0.00 38604.62 538677.32 4447840.43 10903927.54 0.00 0.31
June 55915606.25 11448411.71 194221.92 38039.58 15785866.71 1598827.82 6910007.48 4439.80 0.31
July 36602235.42 13145722.41 707652.36 14502.84 24681817.31 1354422.26 968266.56 10757.79 0.26
August 49586194.62 13747790.90 2271.52 22168.69 14420647.04 1593581.99 5048552.25 87.37 0.35
September 0.102509E+09 1067077.48 0.00 68010.13 1403524.81 2259463.22 20824179.26 0.00 0.35
October 0.133210E+09 0.00 0.00 74951.68 0.00 6299956.19 25427866.03 0.00 0.25
November 0.132826E+09 0.00 0.00 61744.20 0.00 19649441.38 38231130.64 0.00 0.20
December 0.188172E+09 0.00 0.00 16686.11 0.00 45193242.46 19739464.38 0.00 0.16
                   
Annual Sum or Average 0.142992E+10 42332959.08 904145.80 577420.18 56841628.89 0.189366E+09 0.285101E+09 15284.96 0.24
Minimum of Months 36602235.42 0.00 0.00 14502.84 0.00 1354422.26 968266.56 0.00 0.16
Maximum of Months 0.188172E+09 13747790.90 707652.36 76641.14 24681817.31 67233681.01 46387319.77 10757.79 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM HALL 4

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.212456E+09 0.00 0.00 1457.82 0.00 0.114736E+09 2881093.39 0.00 0.17
February 0.188022E+09 0.00 0.00 8134.00 0.00 36049691.23 12405715.72 0.00 0.16
March 0.185796E+09 0.00 0.00 30796.79 0.00 12010757.41 29549150.13 0.00 0.17
April 0.140152E+09 0.00 0.00 54935.56 12157.15 3946913.13 26755866.70 0.00 0.22
May 0.103272E+09 3533671.87 0.00 60404.69 293543.21 1794691.51 19101617.76 0.00 0.31
June 58487302.02 17347344.11 21610.53 68703.29 14182581.34 389013.04 13965145.86 1294.65 0.31
July 40251390.98 18598313.84 106901.40 25922.03 24680632.11 279480.94 2106004.45 2872.20 0.26
August 50855196.86 16394554.73 0.00 42818.86 13607089.20 503582.19 12159801.52 0.00 0.35
September 0.107571E+09 902991.89 0.00 74835.40 1469665.62 1282080.40 31526374.76 0.00 0.35
October 0.140689E+09 0.00 0.00 56350.42 0.00 5074000.70 28499196.27 0.00 0.23
November 0.155935E+09 0.00 0.00 33663.73 0.00 14490313.69 23732152.05 0.00 0.18
December 0.220394E+09 0.00 0.00 3846.72 0.00 51703657.85 8271341.60 0.00 0.16
                   
Annual Sum or Average 0.160388E+10 56776876.44 128511.93 461869.31 54245668.62 0.242260E+09 0.210953E+09 4166.86 0.24
Minimum of Months 40251390.98 0.00 0.00 1457.82 0.00 279480.94 2106004.45 0.00 0.16
Maximum of Months 0.220394E+09 18598313.84 106901.40 74835.40 24680632.11 0.114736E+09 31526374.76 2872.20 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM HALL 5

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.218339E+09 0.00 0.00 5225.10 0.00 0.100919E+09 4734903.56 0.00 0.17
February 0.188763E+09 0.00 0.00 20925.66 0.00 31339062.79 17661543.34 0.00 0.16
March 0.179533E+09 0.00 0.00 58274.05 0.00 9691759.75 45599712.53 0.00 0.18
April 0.131391E+09 0.00 0.00 104783.71 12187.99 2188143.03 46895739.66 0.00 0.23
May 94892396.73 4957586.35 0.00 136470.63 249621.09 455752.54 37498317.29 0.00 0.34
June 53261252.67 27248331.97 2896.07 142959.56 10876174.08 38783.78 26409610.36 151.11 0.35
July 36995158.15 33354638.50 12221.48 61953.61 17170283.53 15240.21 6669475.13 221.67 0.28
August 46793969.53 26144265.73 0.00 97577.16 10205698.85 24378.36 22967775.58 0.00 0.39
September 98022781.12 1449226.41 0.00 158540.59 1294820.12 219060.28 58126481.95 0.00 0.38
October 0.129617E+09 0.00 0.00 119717.36 0.00 2803602.47 55223772.75 0.00 0.25
November 0.148704E+09 0.00 0.00 73029.02 0.00 10291084.81 44304976.06 0.00 0.19
December 0.217203E+09 0.00 0.00 15786.88 0.00 45804795.46 16728557.33 0.00 0.16
                   
Annual Sum or Average 0.154352E+10 93154048.96 15117.55 995243.30 39808785.66 0.203791E+09 0.382821E+09 372.78 0.26
Minimum of Months 36995158.15 0.00 0.00 5225.10 0.00 15240.21 4734903.56 0.00 0.16
Maximum of Months 0.218339E+09 33354638.50 12221.48 158540.59 17170283.53 0.100919E+09 58126481.95 221.67 0.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 EXAM HALL 6

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.196237E+09 0.00 0.00 606.72 0.00 0.136013E+09 1899943.78 0.00 0.17
February 0.189281E+09 0.00 0.00 4757.88 0.00 43050456.85 4529358.21 0.00 0.16
March 0.189082E+09 0.00 0.00 26041.80 0.00 14221992.44 23898165.20 0.00 0.17
April 0.139237E+09 0.00 0.00 66089.32 12181.00 2998714.92 30032319.37 0.00 0.22
May 98871224.85 4357544.31 0.00 92612.28 254486.05 690865.90 28140021.69 0.00 0.33
June 55135562.36 23842890.19 4163.21 108871.18 11513579.72 79888.67 21028410.72 278.65 0.33
July 38532264.82 28236818.62 25501.35 45752.13 19068390.25 28469.90 4535731.06 498.57 0.28
August 47945164.75 22149585.90 0.00 73308.42 11432435.09 66221.59 18669355.77 0.00 0.37
September 0.102064E+09 1228091.78 0.00 117583.26 1361740.62 328678.35 45745969.84 0.00 0.37
October 0.136705E+09 0.00 0.00 81582.74 0.00 3574576.70 38183107.36 0.00 0.24
November 0.153732E+09 0.00 0.00 42684.42 0.00 14613787.27 27327765.38 0.00 0.19
December 0.214074E+09 0.00 0.00 1803.07 0.00 60726629.96 4239606.44 0.00 0.16
                   
Annual Sum or Average 0.156089E+10 79814930.80 29664.56 661693.20 43642812.74 0.276393E+09 0.248230E+09 777.21 0.25
Minimum of Months 38532264.82 0.00 0.00 606.72 0.00 28469.90 1899943.78 0.00 0.16
Maximum of Months 0.214074E+09 28236818.62 25501.35 117583.26 19068390.25 0.136013E+09 45745969.84 498.57 0.37



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 44669936.54 0.00 0.00 0.00 0.00 0.159181E+09 0.00 0.00 0.33
February 53353806.64 0.00 0.00 683.23 0.00 0.101509E+09 421568.89 0.00 0.33
March 78371460.14 0.00 0.00 2925.31 0.00 66090208.71 2786182.67 0.00 0.34
April 82965438.82 0.00 0.00 17601.13 7764.47 18106948.60 6586258.84 0.00 0.43
May 62191359.44 3801868.60 0.00 55243.67 153822.11 4922679.61 13088495.72 0.00 0.67
June 36163753.11 22652594.42 39424.63 64604.63 6273143.69 916696.41 10559763.07 406.57 0.69
July 22873880.58 28097940.58 17475.81 39900.89 9903940.94 437672.11 4473319.18 340.45 0.60
August 30365610.70 20998445.38 0.00 53019.95 6269007.04 334303.43 10707703.89 0.00 0.77
September 67509825.13 1080782.17 0.00 62037.55 822870.10 2274401.57 22043203.40 0.00 0.73
October 89202149.91 0.00 0.00 26218.45 0.00 10701012.29 11189072.47 0.00 0.47
November 78035672.49 0.00 0.00 7507.78 0.00 41397375.57 4277173.12 0.00 0.37
December 57269879.60 0.00 0.00 0.00 0.00 0.125240E+09 0.00 0.00 0.32
                   
Annual Sum or Average 0.702973E+09 76631631.15 56900.43 329742.58 23430548.35 0.531112E+09 86132741.25 747.02 0.50
Minimum of Months 22873880.58 0.00 0.00 0.00 0.00 334303.43 0.00 0.00 0.32
Maximum of Months 89202149.91 28097940.58 39424.63 64604.63 9903940.94 0.159181E+09 22043203.40 406.57 0.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 99622270.57 0.00 0.00 539829.66 0.00 44261.05 0.401789E+09 0.00 0.66
February 83976037.24 0.00 0.00 567089.34 0.00 34923.60 0.358784E+09 0.00 0.75
March 87047210.60 0.00 0.00 704986.68 0.00 0.00 0.381935E+09 0.00 0.85
April 83010542.46 0.00 0.00 611328.59 11074.66 0.00 0.220288E+09 0.00 0.91
May 67154909.07 7271263.52 0.00 528296.54 171028.15 0.00 0.124667E+09 0.00 1.17
June 41005969.38 44704003.04 0.00 381489.59 7229182.41 0.00 63430249.99 0.00 1.14
July 27592081.07 57884137.70 0.00 224185.41 11797856.04 0.00 25550171.90 0.00 0.91
August 34300512.65 44651682.26 0.00 348773.63 8066616.33 0.00 61735883.32 0.00 1.30
September 72313067.05 2521874.95 0.00 561069.32 1106115.61 0.00 0.154957E+09 0.00 1.32
October 86436662.69 0.00 0.00 600396.81 0.00 0.00 0.223182E+09 0.00 0.98
November 84183156.74 0.00 0.00 577641.01 0.00 26241.89 0.281020E+09 0.00 0.87
December 95925866.91 0.00 0.00 563291.48 0.00 44153.79 0.401575E+09 0.00 0.70
                   
Annual Sum or Average 0.862568E+09 0.157033E+09 0.00 6208378.07 28381873.20 149580.33 0.269891E+10 0.00 0.96
Minimum of Months 27592081.07 0.00 0.00 224185.41 0.00 0.00 25550171.90 0.00 0.66
Maximum of Months 99622270.57 57884137.70 0.00 704986.68 11797856.04 44261.05 0.401789E+09 0.00 1.32



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 NURSE STATION 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.227842E+09 0.00 0.00 909624.25 0.00 458133.03 0.703293E+09 0.00 0.65
February 0.193244E+09 0.00 0.00 987369.98 0.00 100411.02 0.633522E+09 0.00 0.75
March 0.199772E+09 0.00 0.00 1248344.24 0.00 0.00 0.682001E+09 0.00 0.86
April 0.186093E+09 0.00 0.00 1101789.28 24573.76 0.00 0.398622E+09 0.00 0.94
May 0.149718E+09 13692878.83 0.00 981838.77 388547.20 0.00 0.232488E+09 0.00 1.24
June 91349727.39 84195290.70 0.00 713896.71 16234468.98 0.00 0.119481E+09 0.00 1.22
July 61616995.54 0.108141E+09 0.00 417843.65 26302792.67 0.00 47636284.40 0.00 0.98
August 76287906.16 83147363.86 0.00 649048.03 17954453.26 0.00 0.116283E+09 0.00 1.38
September 0.161215E+09 4727740.53 0.00 1027296.49 2454378.12 0.00 0.284901E+09 0.00 1.39
October 0.192961E+09 0.00 0.00 1093981.87 0.00 0.00 0.408442E+09 0.00 1.01
November 0.188642E+09 0.00 0.00 1048071.27 0.00 58228.57 0.510548E+09 0.00 0.89
December 0.219756E+09 0.00 0.00 997720.26 0.00 205251.38 0.715009E+09 0.00 0.70
                   
Annual Sum or Average 0.194850E+10 0.293904E+09 0.00 11176824.79 63359213.99 822024.00 0.485223E+10 0.00 1.00
Minimum of Months 61616995.54 0.00 0.00 417843.65 0.00 0.00 47636284.40 0.00 0.65
Maximum of Months 0.227842E+09 0.108141E+09 0.00 1248344.24 26302792.67 458133.03 0.715009E+09 0.00 1.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 NURSE STATION 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.273251E+09 0.00 0.00 1095417.24 0.00 495539.67 0.844900E+09 0.00 0.65
February 0.230643E+09 0.00 0.00 1205743.87 0.00 118010.79 0.770400E+09 0.00 0.75
March 0.236949E+09 0.00 0.00 1549743.66 0.00 0.00 0.839349E+09 0.00 0.87
April 0.221079E+09 0.00 0.00 1407550.53 29509.55 0.00 0.504436E+09 0.00 0.97
May 0.178773E+09 17497861.35 0.00 1285124.15 442684.86 0.00 0.300766E+09 0.00 1.30
June 0.109008E+09 0.108614E+09 0.00 941732.47 19169865.58 0.00 0.155701E+09 0.00 1.28
July 73090059.55 0.139742E+09 0.00 557975.92 31195962.55 0.00 63789361.96 0.00 1.02
August 89953601.56 0.106223E+09 0.00 864485.93 21484143.61 0.00 0.152580E+09 0.00 1.45
September 0.192743E+09 6059033.13 0.00 1359208.83 2947355.70 0.00 0.368475E+09 0.00 1.45
October 0.230079E+09 0.00 0.00 1435194.77 0.00 0.00 0.526583E+09 0.00 1.06
November 0.224394E+09 0.00 0.00 1351935.74 0.00 69924.15 0.647258E+09 0.00 0.93
December 0.260946E+09 0.00 0.00 1229732.46 0.00 205279.69 0.877386E+09 0.00 0.71
                   
Annual Sum or Average 0.232091E+10 0.378135E+09 0.00 14283845.56 75269521.85 888754.29 0.605162E+10 0.00 1.04
Minimum of Months 73090059.55 0.00 0.00 557975.92 0.00 0.00 63789361.96 0.00 0.65
Maximum of Months 0.273251E+09 0.139742E+09 0.00 1549743.66 31195962.55 495539.67 0.877386E+09 0.00 1.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.505600E+09 0.00 0.00 0.00 0.00 0.625053E+09 0.00 0.00 0.21
February 0.587950E+09 0.00 0.00 32290.79 0.00 0.292862E+09 21889697.91 0.00 0.22
March 0.647249E+09 0.00 0.00 336188.53 0.00 0.101557E+09 0.222543E+09 0.00 0.26
April 0.467632E+09 0.00 0.00 1272760.49 48740.01 13522737.18 0.430939E+09 0.00 0.42
May 0.325203E+09 30518343.03 0.00 1714827.37 865631.68 61442.32 0.355442E+09 0.00 0.63
June 0.186658E+09 0.206494E+09 0.00 1800033.11 34208447.41 0.00 0.281569E+09 0.00 0.73
July 0.125859E+09 0.297168E+09 0.00 1082082.41 51714784.84 0.00 0.117519E+09 0.00 0.64
August 0.161417E+09 0.187986E+09 0.00 1216834.73 36357749.85 0.00 0.187314E+09 0.00 0.74
September 0.345436E+09 10752230.01 0.00 1407782.94 4963274.47 51918.29 0.374877E+09 0.00 0.65
October 0.515353E+09 0.00 0.00 592945.01 0.00 9487069.31 0.236574E+09 0.00 0.37
November 0.530375E+09 0.00 0.00 201473.00 0.00 0.128713E+09 0.124028E+09 0.00 0.26
December 0.529140E+09 0.00 0.00 293.40 0.00 0.520926E+09 2600976.06 0.00 0.21
                   
Annual Sum or Average 0.492787E+10 0.732918E+09 0.00 9657511.80 0.128159E+09 0.169223E+10 0.235530E+10 0.00 0.45
Minimum of Months 0.125859E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.21
Maximum of Months 0.647249E+09 0.297168E+09 0.00 1800033.11 51714784.84 0.625053E+09 0.430939E+09 0.00 0.74



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.512841E+09 0.00 0.00 12.60 0.00 0.155500E+09 684981.83 0.00 0.15
February 0.450414E+09 0.00 0.00 8150.53 0.00 41009501.03 14911200.73 0.00 0.15
March 0.428068E+09 0.00 0.00 89888.98 0.00 14125246.04 69030832.81 0.00 0.17
April 0.289058E+09 0.00 0.00 326894.28 27314.43 4438411.79 0.122816E+09 0.00 0.24
May 0.211422E+09 10395325.34 0.00 378233.00 544141.45 917971.14 86041676.95 0.00 0.34
June 0.115072E+09 62955320.93 0.00 430481.42 24587810.40 58711.96 74018010.05 0.00 0.37
July 79295455.66 86905123.15 22313.98 242328.93 36649091.55 11002.94 26035325.93 147.34 0.31
August 0.102056E+09 63312766.57 0.00 297915.81 21898632.11 0.00 55088495.30 0.00 0.40
September 0.215584E+09 3333746.99 0.00 378973.03 3267941.01 207294.72 0.119464E+09 0.00 0.38
October 0.309728E+09 0.00 0.00 193157.98 0.00 5378744.12 82442140.19 0.00 0.24
November 0.348674E+09 0.00 0.00 80940.74 0.00 29265784.65 55850921.34 0.00 0.18
December 0.505567E+09 0.00 0.00 1633.12 0.00 86850311.95 7140889.31 0.00 0.15
                   
Annual Sum or Average 0.356778E+10 0.226902E+09 22313.98 2428610.42 86974930.95 0.337763E+09 0.713524E+09 147.34 0.26
Minimum of Months 79295455.66 0.00 0.00 12.60 0.00 0.00 684981.83 0.00 0.15
Maximum of Months 0.512841E+09 86905123.15 22313.98 430481.42 36649091.55 0.155500E+09 0.122816E+09 147.34 0.40



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 RECEPTION

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.262965E+10 0.00 0.00 3050637.77 0.00 0.267625E+09 0.278210E+10 0.00 0.60
February 0.209701E+10 0.00 0.00 4210092.21 0.00 77676215.31 0.284259E+10 0.00 0.71
March 0.205692E+10 0.00 0.00 5547719.16 0.00 13808686.73 0.325431E+10 0.00 0.81
April 0.176687E+10 0.00 0.00 5604860.37 211866.51 1772396.82 0.212817E+10 0.00 1.00
May 0.134992E+10 0.106221E+09 0.00 5727417.83 3520710.81 220564.72 0.138153E+10 0.00 1.40
June 0.815050E+09 0.632196E+09 0.00 4348404.48 0.142293E+09 83055.76 0.729026E+09 0.00 1.38
July 0.542671E+09 0.822386E+09 0.00 2662434.55 0.231964E+09 0.00 0.310814E+09 0.00 1.16
August 0.669081E+09 0.643769E+09 0.00 3978989.65 0.155389E+09 0.00 0.735966E+09 0.00 1.60
September 0.144770E+10 38458602.45 0.00 6199622.74 21160807.75 0.00 0.174759E+10 0.00 1.58
October 0.179483E+10 0.00 0.00 5849686.43 0.00 1724824.63 0.225393E+10 0.00 1.08
November 0.189304E+10 0.00 0.00 4636468.75 0.00 40771781.93 0.244065E+10 0.00 0.85
December 0.248931E+10 0.00 0.00 3177338.82 0.00 0.214607E+09 0.259986E+10 0.00 0.61
                   
Annual Sum or Average 0.195521E+11 0.224303E+10 0.00 54993672.76 0.554539E+09 0.618289E+09 0.232066E+11 0.00 1.07
Minimum of Months 0.542671E+09 0.00 0.00 2662434.55 0.00 0.00 0.310814E+09 0.00 0.60
Maximum of Months 0.262965E+10 0.822386E+09 0.00 6199622.74 0.231964E+09 0.267625E+09 0.325431E+10 0.00 1.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 RECEPTION HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.546323E+09 0.00 0.00 396026.58 0.00 40352262.64 0.378938E+09 0.00 0.18
February 0.387602E+09 0.00 0.00 693385.45 0.00 2199615.08 0.485679E+09 0.00 0.21
March 0.353029E+09 0.00 0.00 1010647.20 0.00 604096.04 0.611360E+09 0.00 0.26
April 0.300911E+09 0.00 0.00 1001131.02 34730.08 76865.04 0.381710E+09 0.00 0.30
May 0.240073E+09 17932111.64 0.00 849981.70 688038.95 20924.71 0.204552E+09 0.00 0.40
June 0.143686E+09 97656455.87 0.00 651601.69 27206983.60 0.00 0.113917E+09 0.00 0.39
July 98379781.73 0.119674E+09 0.00 333999.00 46093773.76 0.00 35905772.92 0.00 0.32
August 0.124251E+09 0.100130E+09 0.00 537755.11 26585961.50 0.00 0.105160E+09 0.00 0.44
September 0.250787E+09 5729323.59 0.00 976019.35 3517115.10 0.00 0.292247E+09 0.00 0.46
October 0.313447E+09 0.00 0.00 945277.35 0.00 202105.65 0.372927E+09 0.00 0.32
November 0.351332E+09 0.00 0.00 737336.01 0.00 940642.77 0.400162E+09 0.00 0.26
December 0.487486E+09 0.00 0.00 547922.26 0.00 12217354.80 0.436236E+09 0.00 0.19
                   
Annual Sum or Average 0.359731E+10 0.341122E+09 0.00 8681082.71 0.104127E+09 56613866.73 0.381879E+10 0.00 0.31
Minimum of Months 98379781.73 0.00 0.00 333999.00 0.00 0.00 35905772.92 0.00 0.18
Maximum of Months 0.546323E+09 0.119674E+09 0.00 1010647.20 46093773.76 40352262.64 0.611360E+09 0.00 0.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.104400E+10 0.00 0.00 0.00 0.00 0.121558E+09 0.00 0.00 0.97
February 0.889944E+09 0.00 0.00 0.00 0.00 48887784.58 0.00 0.00 1.01
March 0.920391E+09 0.00 0.00 0.00 0.00 20819658.99 0.00 0.00 1.10
April 0.691583E+09 0.00 0.00 0.00 51527.11 7480512.82 0.00 0.00 1.38
May 0.501406E+09 0.00 5403.84 0.00 12103533.07 2289870.54 0.00 282.54 1.95
June 0.291211E+09 0.00 130052.15 0.00 0.110128E+09 927888.45 0.00 4295.60 1.95
July 0.178550E+09 0.00 308311.94 0.00 0.160980E+09 559955.19 0.00 6139.86 1.68
August 0.255926E+09 0.00 66484.68 0.00 0.110330E+09 830753.36 0.00 1305.09 2.21
September 0.559082E+09 0.00 0.00 0.00 9109459.26 1063062.00 0.00 0.00 2.21
October 0.706365E+09 0.00 0.00 0.00 0.00 8553613.30 0.00 0.00 1.49
November 0.763517E+09 0.00 0.00 0.00 0.00 35281369.12 0.00 0.00 1.19
December 0.101249E+10 0.00 0.00 0.00 0.00 83324318.60 0.00 0.00 0.97
                   
Annual Sum or Average 0.781447E+10 0.00 510252.61 0.00 0.402703E+09 0.331577E+09 0.00 12023.09 1.51
Minimum of Months 0.178550E+09 0.00 0.00 0.00 0.00 559955.19 0.00 0.00 0.97
Maximum of Months 0.104400E+10 0.00 308311.94 0.00 0.160980E+09 0.121558E+09 0.00 6139.86 2.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 SCHEDULING 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.294464E+09 0.00 0.00 823504.56 0.00 512412.87 0.669622E+09 0.00 0.31
February 0.230263E+09 0.00 0.00 1026683.16 0.00 0.00 0.661286E+09 0.00 0.37
March 0.233618E+09 0.00 0.00 1386306.80 0.00 0.00 0.737905E+09 0.00 0.44
April 0.217818E+09 0.00 0.00 1230980.90 28234.54 0.00 0.430388E+09 0.00 0.48
May 0.174867E+09 14396084.85 0.00 1076868.35 469189.98 0.00 0.242876E+09 0.00 0.63
June 0.107115E+09 89173507.03 0.00 778792.70 18782072.07 0.00 0.126829E+09 0.00 0.62
July 72038384.94 0.114813E+09 0.00 452906.53 30156089.02 0.00 50129526.89 0.00 0.50
August 89481837.76 87517167.73 0.00 732295.70 20780259.75 0.00 0.124673E+09 0.00 0.71
September 0.187307E+09 4912224.46 0.00 1157663.46 2820009.78 0.00 0.309756E+09 0.00 0.71
October 0.225827E+09 0.00 0.00 1194637.05 0.00 0.00 0.430960E+09 0.00 0.52
November 0.224838E+09 0.00 0.00 1093728.49 0.00 0.00 0.521836E+09 0.00 0.44
December 0.266762E+09 0.00 0.00 999129.98 0.00 298477.21 0.724821E+09 0.00 0.35
                   
Annual Sum or Average 0.232440E+10 0.310812E+09 0.00 11953497.68 73035855.13 810890.08 0.503108E+10 0.00 0.51
Minimum of Months 72038384.94 0.00 0.00 452906.53 0.00 0.00 50129526.89 0.00 0.31
Maximum of Months 0.294464E+09 0.114813E+09 0.00 1386306.80 30156089.02 512412.87 0.737905E+09 0.00 0.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 SCHEDULING 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.338613E+09 0.00 0.00 696476.11 0.00 855256.56 0.612109E+09 0.00 0.29
February 0.251786E+09 0.00 0.00 986638.83 0.00 93739.06 0.638927E+09 0.00 0.35
March 0.249986E+09 0.00 0.00 1374172.64 0.00 0.00 0.736701E+09 0.00 0.42
April 0.229269E+09 0.00 0.00 1292822.27 29725.70 0.00 0.450021E+09 0.00 0.48
May 0.183115E+09 16126815.30 0.00 1175964.93 493969.55 0.00 0.265038E+09 0.00 0.64
June 0.112073E+09 99242884.12 0.00 853839.02 19776327.54 0.00 0.139493E+09 0.00 0.63
July 75376878.22 0.127590E+09 0.00 510678.14 31672851.14 0.00 56761115.30 0.00 0.51
August 93570720.50 96741516.41 0.00 810263.70 21829626.73 0.00 0.137391E+09 0.00 0.72
September 0.196320E+09 5419834.94 0.00 1261329.34 2968944.43 0.00 0.336087E+09 0.00 0.73
October 0.237789E+09 0.00 0.00 1260849.01 0.00 0.00 0.453957E+09 0.00 0.52
November 0.239282E+09 0.00 0.00 1091997.88 0.00 0.00 0.527064E+09 0.00 0.43
December 0.299029E+09 0.00 0.00 901016.45 0.00 497615.79 0.670881E+09 0.00 0.32
                   
Annual Sum or Average 0.250621E+10 0.345121E+09 0.00 12216048.32 76771445.10 1446611.41 0.502443E+10 0.00 0.51
Minimum of Months 75376878.22 0.00 0.00 510678.14 0.00 0.00 56761115.30 0.00 0.29
Maximum of Months 0.338613E+09 0.127590E+09 0.00 1374172.64 31672851.14 855256.56 0.736701E+09 0.00 0.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.111388E+09 0.00 0.00 5737.34 0.00 40437305.36 6312188.47 0.00 0.29
February 0.104760E+09 0.00 0.00 1893.11 0.00 18939870.92 2305850.21 0.00 0.31
March 0.113008E+09 0.00 0.00 537.88 0.00 11677092.69 1299423.17 0.00 0.33
April 85897458.32 0.00 0.00 1267.57 6881.57 6236604.05 1369939.29 0.00 0.42
May 62438351.64 5793.19 1281.10 6.89 1610055.75 4907827.32 38943.81 85.42 0.59
June 37380038.34 210625.05 360773.85 0.00 14157119.08 1694491.37 0.00 3464.58 0.59
July 22471464.26 0.00 1219989.86 0.00 20337936.74 1502427.77 0.00 7462.65 0.50
August 32370770.60 236393.33 55252.92 0.00 14452684.43 1994708.85 0.00 579.69 0.67
September 71651098.93 112818.04 2158.20 631.60 1101612.39 2906437.83 325049.49 1.62 0.66
October 86904419.41 0.00 0.00 2385.25 0.00 7277043.60 1455750.05 0.00 0.45
November 84061698.20 0.00 0.00 7417.37 0.00 17929352.16 5332317.63 0.00 0.36
December 0.114063E+09 0.00 0.00 167.89 0.00 32867557.58 1035043.78 0.00 0.30
                   
Annual Sum or Average 0.926394E+09 565629.62 1639455.92 20044.91 51666289.96 0.148371E+09 19474505.89 11593.96 0.46
Minimum of Months 22471464.26 0.00 0.00 0.00 0.00 1502427.77 0.00 0.00 0.29
Maximum of Months 0.114063E+09 236393.33 1219989.86 7417.37 20337936.74 40437305.36 6312188.47 7462.65 0.67



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.264108E+09 0.00 0.00 0.00 0.00 71322990.07 0.00 0.00 0.29
February 0.240663E+09 0.00 0.00 0.00 0.00 28444102.59 0.00 0.00 0.30
March 0.254551E+09 0.00 0.00 0.00 0.00 15080999.23 0.00 0.00 0.33
April 0.193990E+09 0.00 0.00 84.62 14749.47 5624972.70 565632.13 0.00 0.42
May 0.139956E+09 53198.88 0.00 286.75 3413025.40 3004495.79 1269990.30 0.00 0.59
June 81047038.47 3054595.88 81301.62 352.91 28427361.13 832467.31 1761680.29 1357.48 0.59
July 50614373.38 3198225.94 228845.93 15.92 42747787.91 624143.09 47404.84 3118.29 0.50
August 71885273.61 1013498.77 11063.07 81.42 30576245.27 704526.10 935096.12 166.93 0.67
September 0.157360E+09 77075.67 0.00 95.59 2530477.11 1921382.34 1090559.24 0.00 0.66
October 0.197676E+09 0.00 0.00 0.00 0.00 7044315.03 0.00 0.00 0.45
November 0.209428E+09 0.00 0.00 0.00 0.00 19399000.70 0.00 0.00 0.36
December 0.271218E+09 0.00 0.00 0.00 0.00 43463890.02 0.00 0.00 0.29
                   
Annual Sum or Average 0.213250E+10 7396595.14 321210.61 917.20 0.107710E+09 0.197467E+09 5670362.92 4642.70 0.45
Minimum of Months 50614373.38 0.00 0.00 0.00 0.00 624143.09 0.00 0.00 0.29
Maximum of Months 0.271218E+09 3198225.94 228845.93 352.91 42747787.91 71322990.07 1761680.29 3118.29 0.67



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 STORAGE 3

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.318695E+09 0.00 0.00 0.00 0.00 84057596.75 0.00 0.00 0.29
February 0.293778E+09 0.00 0.00 0.00 0.00 29288323.37 0.00 0.00 0.30
March 0.303351E+09 0.00 0.00 1214.95 0.00 16353555.85 3886770.02 0.00 0.33
April 0.224470E+09 0.00 0.00 7402.69 17702.72 4026251.95 11733238.91 0.00 0.42
May 0.158387E+09 2929966.99 0.00 16816.93 1230290.96 1119163.24 13568381.12 0.00 0.59
June 88466214.86 13542949.42 10122.64 21110.91 24330434.32 169356.02 11723510.51 577.87 0.59
July 60115468.67 14352922.77 78551.91 6692.40 40989488.99 98266.06 1325665.49 1328.53 0.51
August 76661952.83 12270716.24 0.00 15382.88 25657644.15 145732.54 11405589.69 0.00 0.67
September 0.165238E+09 881377.87 0.00 28307.65 2248278.88 578904.21 26758668.19 0.00 0.67
October 0.223692E+09 0.00 0.00 10323.50 0.00 4453879.65 17527307.74 0.00 0.45
November 0.251529E+09 0.00 0.00 2368.32 0.00 15843442.05 7233517.32 0.00 0.36
December 0.332566E+09 0.00 0.00 0.00 0.00 44898472.13 0.00 0.00 0.29
                   
Annual Sum or Average 0.249695E+10 43977933.29 88674.55 109620.23 94473840.01 0.201033E+09 0.105163E+09 1906.40 0.46
Minimum of Months 60115468.67 0.00 0.00 0.00 0.00 98266.06 0.00 0.00 0.29
Maximum of Months 0.332566E+09 14352922.77 78551.91 28307.65 40989488.99 84057596.75 26758668.19 1328.53 0.67



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 62818686.26 0.00 0.00 0.00 0.00 0.303030E+09 0.00 0.00 0.30
February 97196318.68 0.00 0.00 0.00 0.00 0.190332E+09 0.00 0.00 0.31
March 0.164683E+09 0.00 0.00 6450.55 0.00 0.115716E+09 5359467.72 0.00 0.33
April 0.161879E+09 0.00 0.00 119624.38 15521.40 24710754.78 38121803.14 0.00 0.45
May 0.128924E+09 4417614.49 0.00 160664.19 347724.06 3910004.30 30347771.63 0.00 0.65
June 69107566.11 28590166.80 5810.10 231043.46 16542575.09 99547.11 35669225.43 244.92 0.71
July 47326174.17 43618359.06 25468.52 128167.74 23913388.45 42688.47 13003261.69 707.68 0.63
August 70129826.58 24075793.33 0.00 92757.05 16525781.91 218121.13 10589884.24 0.00 0.73
September 0.153098E+09 1537840.44 0.00 90340.26 1857004.52 3665784.77 18537488.38 0.00 0.70
October 0.174537E+09 0.00 0.00 17745.63 0.00 37045424.13 5916945.09 0.00 0.45
November 0.134770E+09 0.00 0.00 0.00 0.00 0.107706E+09 0.00 0.00 0.36
December 74004403.53 0.00 0.00 0.00 0.00 0.264970E+09 0.00 0.00 0.30
                   
Annual Sum or Average 0.133847E+10 0.102240E+09 31278.62 846793.25 59201995.43 0.105145E+10 0.157546E+09 952.60 0.49
Minimum of Months 47326174.17 0.00 0.00 0.00 0.00 42688.47 0.00 0.00 0.30
Maximum of Months 0.174537E+09 43618359.06 25468.52 231043.46 23913388.45 0.303030E+09 38121803.14 707.68 0.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.242738E+10 0.00 0.00 1098623.53 0.00 89868355.43 0.111490E+10 0.00 0.23
February 0.170200E+10 0.00 0.00 2084579.22 0.00 13646640.12 0.147785E+10 0.00 0.26
March 0.153846E+10 0.00 0.00 3351539.53 0.00 2760856.43 0.201966E+10 0.00 0.31
April 0.121789E+10 0.00 0.00 4205132.59 146964.08 0.00 0.153330E+10 0.00 0.40
May 0.919675E+09 78775911.60 0.00 5043470.36 2386062.69 0.00 0.111283E+10 0.00 0.60
June 0.554598E+09 0.510517E+09 0.00 4142070.94 96158093.57 0.00 0.640214E+09 0.00 0.62
July 0.371333E+09 0.668748E+09 0.00 2645384.39 0.156070E+09 0.00 0.281138E+09 0.00 0.52
August 0.460717E+09 0.486818E+09 0.00 4050123.96 0.107863E+09 0.00 0.643330E+09 0.00 0.71
September 0.979511E+09 26744908.92 0.00 5584081.37 14678481.82 0.00 0.145825E+10 0.00 0.69
October 0.123457E+10 0.00 0.00 4689380.90 0.00 0.00 0.173124E+10 0.00 0.45
November 0.138382E+10 0.00 0.00 3334913.58 0.00 2190253.39 0.167064E+10 0.00 0.35
December 0.211202E+10 0.00 0.00 1942712.33 0.00 41419530.13 0.151891E+10 0.00 0.25
                   
Annual Sum or Average 0.149020E+11 0.177160E+10 0.00 42172012.71 0.377303E+09 0.149886E+09 0.152023E+11 0.00 0.45
Minimum of Months 0.371333E+09 0.00 0.00 1098623.53 0.00 0.00 0.281138E+09 0.00 0.23
Maximum of Months 0.242738E+10 0.668748E+09 0.00 5584081.37 0.156070E+09 89868355.43 0.201966E+10 0.00 0.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 WORK HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.847044E+09 0.00 0.00 449022.76 0.00 69634785.37 0.437892E+09 0.00 0.17
February 0.595052E+09 0.00 0.00 893902.73 0.00 3838745.59 0.622931E+09 0.00 0.20
March 0.527741E+09 0.00 0.00 1446051.85 0.00 1429354.66 0.865472E+09 0.00 0.25
April 0.434641E+09 0.00 0.00 1656960.36 51341.39 27672.85 0.613815E+09 0.00 0.31
May 0.341447E+09 29689254.18 0.00 1655742.63 1017126.13 0.00 0.379537E+09 0.00 0.44
June 0.207270E+09 0.177742E+09 0.00 1304964.31 36535495.44 0.00 0.217060E+09 0.00 0.44
July 0.139150E+09 0.230347E+09 0.00 756247.20 56266410.95 0.00 83104643.34 0.00 0.36
August 0.172933E+09 0.173231E+09 0.00 1213087.18 38840865.43 0.00 0.213876E+09 0.00 0.51
September 0.357515E+09 9690732.74 0.00 1863425.47 5127876.29 0.00 0.528452E+09 0.00 0.50
October 0.450683E+09 0.00 0.00 1659707.87 0.00 63941.57 0.631786E+09 0.00 0.34
November 0.515675E+09 0.00 0.00 1185443.90 0.00 1250393.18 0.613675E+09 0.00 0.26
December 0.734693E+09 0.00 0.00 764887.76 0.00 25845566.53 0.598383E+09 0.00 0.18
                   
Annual Sum or Average 0.532385E+10 0.620700E+09 0.00 14849444.02 0.137839E+09 0.102090E+09 0.580598E+10 0.00 0.33
Minimum of Months 0.139150E+09 0.00 0.00 449022.76 0.00 0.00 83104643.34 0.00 0.17
Maximum of Months 0.847044E+09 0.230347E+09 0.00 1863425.47 56266410.95 69634785.37 0.865472E+09 0.00 0.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 WORK TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.128231E+09 0.00 0.00 0.00 0.00 0.473418E+09 0.00 0.00 1.16
February 0.148342E+09 0.00 0.00 0.00 0.00 0.336271E+09 0.00 0.00 1.22
March 0.216723E+09 0.00 0.00 0.00 0.00 0.269119E+09 0.00 0.00 1.32
April 0.251118E+09 0.00 0.00 0.00 26597.66 0.109730E+09 0.00 0.00 1.66
May 0.231224E+09 0.00 7573.63 0.00 6242834.85 28778157.00 0.00 220.81 2.35
June 0.144704E+09 2000009.95 559223.86 0.00 54353325.71 6094431.19 0.00 3619.32 2.35
July 89797142.90 230832.09 541794.37 0.00 82481280.43 2657168.11 0.00 4239.65 2.02
August 0.129022E+09 188644.79 46580.70 0.00 56749532.25 3513217.83 0.00 1160.69 2.66
September 0.275815E+09 0.00 0.00 0.00 4702190.19 13324715.94 0.00 0.00 2.66
October 0.305921E+09 0.00 0.00 0.00 0.00 63111359.09 0.00 0.00 1.79
November 0.240114E+09 0.00 0.00 0.00 0.00 0.172215E+09 0.00 0.00 1.43
December 0.151098E+09 0.00 0.00 0.00 0.00 0.414549E+09 0.00 0.00 1.17
                   
Annual Sum or Average 0.231211E+10 2419486.82 1155172.57 0.00 0.204556E+09 0.189278E+10 0.00 9240.47 1.82
Minimum of Months 89797142.90 0.00 0.00 0.00 0.00 2657168.11 0.00 0.00 1.16
Maximum of Months 0.305921E+09 2000009.95 559223.86 0.00 82481280.43 0.473418E+09 0.00 4239.65 2.66



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 2 X-RAY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.896529E+09 0.00 0.00 35769444.24 0.00 0.00 0.169812E+11 0.00 2.07
February 0.649406E+09 0.00 0.00 36293592.38 0.00 0.00 0.141334E+11 0.00 2.20
March 0.530824E+09 0.00 0.00 43556315.73 0.00 0.00 0.144344E+11 0.00 2.40
April 0.558389E+09 0.00 0.00 34953766.60 277072.83 0.00 0.897578E+10 0.00 2.54
May 0.716291E+09 0.243981E+09 0.00 27253627.07 1048568.86 0.00 0.544365E+10 0.00 3.29
June 0.471065E+09 0.160845E+10 0.00 17400509.36 0.121906E+09 0.00 0.284143E+10 0.00 3.30
July 0.363334E+09 0.218232E+10 0.00 10415907.14 0.158820E+09 0.00 0.140705E+10 0.00 2.68
August 0.395530E+09 0.158011E+10 0.00 15830873.60 0.129442E+09 0.00 0.268737E+10 0.00 3.73
September 0.688113E+09 95185846.83 0.00 28687924.22 17667339.14 0.00 0.626872E+10 0.00 3.62
October 0.746819E+09 0.00 0.00 35107904.02 0.00 0.00 0.886687E+10 0.00 2.69
November 0.635701E+09 0.00 0.00 35744497.88 0.00 0.00 0.112752E+11 0.00 2.51
December 0.808835E+09 0.00 0.00 37118329.96 0.00 0.00 0.164592E+11 0.00 2.14
                   
Annual Sum or Average 0.746084E+10 0.571005E+10 0.00 0.358133E+09 0.429161E+09 0.00 0.109774E+12 0.00 2.77
Minimum of Months 0.363334E+09 0.00 0.00 10415907.14 0.00 0.00 0.140705E+10 0.00 2.07
Maximum of Months 0.896529E+09 0.218232E+10 0.00 43556315.73 0.158820E+09 0.00 0.169812E+11 0.00 3.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 DRESSING ROOM

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 56107737.59 0.00 0.00 36200.01 0.00 6311407.45 33567121.84 0.00 0.24
February 43226163.13 0.00 0.00 54055.46 0.00 3041502.26 36754580.36 0.00 0.28
March 41071437.72 0.00 0.00 88016.58 0.00 791805.39 55591879.22 0.00 0.35
April 32617420.95 0.00 0.00 103646.88 3655.78 97100.67 40606849.57 0.00 0.44
May 24862098.86 2376552.10 0.00 110102.90 72424.74 5008.67 27285056.05 0.00 0.64
June 15025390.41 13621106.36 0.00 86598.31 2691229.75 0.00 14047275.47 0.00 0.63
July 10345796.86 17374617.14 0.00 41947.75 4451435.24 0.00 4252780.95 0.00 0.50
August 13018740.55 13479331.35 0.00 61052.87 2804318.33 0.00 11903603.69 0.00 0.68
September 26609727.82 770885.62 0.00 110299.91 365131.80 3161.19 34082672.24 0.00 0.69
October 32639025.26 0.00 0.00 104015.19 0.00 159118.57 43299894.15 0.00 0.47
November 36482760.87 0.00 0.00 74767.14 0.00 1027639.07 40791211.53 0.00 0.37
December 51645547.87 0.00 0.00 48577.28 0.00 4580893.10 37454799.06 0.00 0.25
                   
Annual Sum or Average 0.383652E+09 47622492.57 0.00 919280.28 10388195.64 16017636.37 0.379638E+09 0.00 0.46
Minimum of Months 10345796.86 0.00 0.00 36200.01 0.00 0.00 4252780.95 0.00 0.24
Maximum of Months 56107737.59 17374617.14 0.00 110299.91 4451435.24 6311407.45 55591879.22 0.00 0.69



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.153443E+09 0.00 0.00 0.00 0.00 0.393483E+09 0.00 0.00 0.15
February 0.207605E+09 0.00 0.00 0.00 0.00 0.222063E+09 0.00 0.00 0.16
March 0.292469E+09 0.00 0.00 4667.42 0.00 0.125067E+09 4682869.31 0.00 0.17
April 0.265342E+09 0.00 0.00 60854.73 22733.58 25297104.60 23211399.67 0.00 0.21
May 0.184887E+09 10823107.12 0.00 205090.69 450375.73 3613108.41 46478475.52 0.00 0.33
June 0.102532E+09 65200241.15 0.00 255794.78 18728231.79 75255.98 40223031.78 0.00 0.35
July 68583047.86 87252559.56 0.00 157906.28 27770422.41 15078.67 14806575.51 0.00 0.31
August 86397761.27 61963441.37 0.00 199033.31 17695395.44 19997.45 38349688.21 0.00 0.39
September 0.195623E+09 3331108.04 0.00 216372.39 2351470.20 365178.45 71176435.06 0.00 0.36
October 0.277688E+09 0.00 0.00 71437.01 0.00 14155216.20 28333736.11 0.00 0.23
November 0.272620E+09 0.00 0.00 4428.99 0.00 79993754.83 3642819.69 0.00 0.18
December 0.199341E+09 0.00 0.00 0.00 0.00 0.303388E+09 0.00 0.00 0.15
                   
Annual Sum or Average 0.230653E+10 0.228570E+09 0.00 1175585.60 67018629.15 0.116754E+10 0.270905E+09 0.00 0.25
Minimum of Months 68583047.86 0.00 0.00 0.00 0.00 15078.67 0.00 0.00 0.15
Maximum of Months 0.292469E+09 87252559.56 0.00 255794.78 27770422.41 0.393483E+09 71176435.06 0.00 0.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 HUMID

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.139543E+09 0.00 0.00 129901.29 0.00 11078492.75 0.117582E+09 0.00 0.26
February 0.106082E+09 0.00 0.00 189395.36 0.00 4610064.79 0.126132E+09 0.00 0.31
March 97734922.25 0.00 0.00 297629.26 0.00 842627.25 0.182816E+09 0.00 0.39
April 80657911.93 0.00 0.00 337277.42 9430.84 32405.70 0.129079E+09 0.00 0.49
May 62726801.97 6773830.90 0.00 349052.88 186834.78 0.00 85545027.26 0.00 0.70
June 38020317.54 39497425.22 0.00 268558.95 6841913.68 0.00 43808052.62 0.00 0.69
July 26070030.36 50661558.73 0.00 136655.28 11115459.61 0.00 14187870.59 0.00 0.55
August 32631356.56 38929549.79 0.00 202960.65 7187868.70 0.00 38275457.63 0.00 0.75
September 67260577.35 2220127.39 0.00 351781.29 941933.96 0.00 0.105904E+09 0.00 0.76
October 81770767.79 0.00 0.00 339492.07 0.00 106452.04 0.137148E+09 0.00 0.53
November 87344530.43 0.00 0.00 255344.80 0.00 1614510.00 0.135997E+09 0.00 0.41
December 0.127124E+09 0.00 0.00 169661.34 0.00 6970823.18 0.130205E+09 0.00 0.28
                   
Annual Sum or Average 0.946967E+09 0.138082E+09 0.00 3027710.60 26283441.58 25255375.72 0.124668E+10 0.00 0.51
Minimum of Months 26070030.36 0.00 0.00 129901.29 0.00 0.00 14187870.59 0.00 0.26
Maximum of Months 0.139543E+09 50661558.73 0.00 351781.29 11115459.61 11078492.75 0.182816E+09 0.00 0.76



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 JANITOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 12231869.53 0.00 0.00 0.00 0.00 0.295649E+09 0.00 0.00 0.50
February 21348671.63 0.00 0.00 0.00 0.00 0.220682E+09 0.00 0.00 0.51
March 44755541.52 0.00 0.00 0.00 0.00 0.190365E+09 0.00 0.00 0.54
April 73464413.38 0.00 0.00 0.00 12611.88 98237490.15 0.00 0.00 0.68
May 90576302.94 377893.06 2314.07 0.00 2583480.22 32866445.02 0.00 190.35 0.96
June 61488800.03 4506834.95 722855.14 16.80 21770661.61 10076534.75 3180.02 4307.29 0.96
July 38487402.84 2827891.02 824387.89 0.00 35833119.24 5385331.99 0.00 5458.50 0.82
August 52666965.63 1270288.93 232316.92 0.00 25520685.77 10238079.00 0.00 1735.10 1.08
September 0.101794E+09 53374.29 13146.37 0.00 2163104.69 35424184.92 0.00 24.82 1.08
October 83793408.09 0.00 0.00 0.00 0.00 91659226.92 0.00 0.00 0.73
November 41712873.50 0.00 0.00 0.00 0.00 0.155787E+09 0.00 0.00 0.58
December 16714190.16 0.00 0.00 0.00 0.00 0.265625E+09 0.00 0.00 0.50
                   
Annual Sum or Average 0.639035E+09 9036282.25 1795020.39 16.80 87883663.41 0.141200E+10 3180.02 11716.07 0.75
Minimum of Months 12231869.53 0.00 0.00 0.00 0.00 5385331.99 0.00 0.00 0.50
Maximum of Months 0.101794E+09 4506834.95 824387.89 16.80 35833119.24 0.295649E+09 3180.02 5458.50 1.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 LOCKER

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.173354E+09 0.00 0.00 504296.85 0.00 17209897.66 0.422107E+09 0.00 0.54
February 0.146655E+09 0.00 0.00 596241.79 0.00 3929995.78 0.389225E+09 0.00 0.62
March 0.145886E+09 0.00 0.00 835899.40 0.00 553083.44 0.473576E+09 0.00 0.77
April 0.130582E+09 0.00 0.00 848439.00 16548.77 0.00 0.312552E+09 0.00 0.91
May 0.100967E+09 13794688.99 0.00 894412.25 243805.71 0.00 0.211469E+09 0.00 1.29
June 60975918.89 86138249.97 0.00 685454.19 10627926.85 0.00 0.110408E+09 0.00 1.30
July 40915221.34 0.111774E+09 0.00 401511.49 17399404.81 0.00 44991827.34 0.00 1.04
August 50649435.58 82367904.77 0.00 588162.99 12001106.70 0.00 0.102770E+09 0.00 1.43
September 0.109234E+09 4631744.00 0.00 886335.87 1652858.38 0.00 0.246771E+09 0.00 1.39
October 0.133461E+09 0.00 0.00 868569.91 0.00 14449.52 0.330282E+09 0.00 0.98
November 0.134384E+09 0.00 0.00 737980.10 0.00 1937343.50 0.368053E+09 0.00 0.82
December 0.158849E+09 0.00 0.00 588197.42 0.00 11203046.53 0.438930E+09 0.00 0.58
                   
Annual Sum or Average 0.138591E+10 0.298707E+09 0.00 8435501.26 41941651.22 34847816.43 0.345114E+10 0.00 0.97
Minimum of Months 40915221.34 0.00 0.00 401511.49 0.00 0.00 44991827.34 0.00 0.54
Maximum of Months 0.173354E+09 0.111774E+09 0.00 894412.25 17399404.81 17209897.66 0.473576E+09 0.00 1.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 LOUNGE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.104027E+10 0.00 0.00 3648931.80 0.00 94945213.86 0.292779E+10 0.00 0.57
February 0.875244E+09 0.00 0.00 4307936.34 0.00 25202118.26 0.273772E+10 0.00 0.66
March 0.887955E+09 0.00 0.00 5918513.49 0.00 2879036.87 0.322118E+10 0.00 0.80
April 0.792957E+09 0.00 0.00 5946329.51 105030.10 0.00 0.213574E+10 0.00 0.94
May 0.614407E+09 87732079.65 0.00 6171263.01 1484848.58 0.00 0.143478E+10 0.00 1.33
June 0.376955E+09 0.558490E+09 0.00 4713269.61 66853851.89 0.00 0.746098E+09 0.00 1.34
July 0.255181E+09 0.732600E+09 0.00 2838455.04 0.108611E+09 0.00 0.316587E+09 0.00 1.08
August 0.313053E+09 0.530298E+09 0.00 4134132.46 75655577.62 0.00 0.698188E+09 0.00 1.48
September 0.668305E+09 29493552.70 0.00 6126460.81 10490198.20 0.00 0.165213E+10 0.00 1.43
October 0.819783E+09 0.00 0.00 6061141.57 0.00 91706.78 0.221929E+10 0.00 1.01
November 0.817783E+09 0.00 0.00 5314550.04 0.00 4028153.81 0.254761E+10 0.00 0.86
December 0.963708E+09 0.00 0.00 4207435.89 0.00 60314089.06 0.301988E+10 0.00 0.61
                   
Annual Sum or Average 0.842560E+10 0.193861E+10 0.00 59388419.57 0.263201E+09 0.187460E+09 0.236570E+11 0.00 1.01
Minimum of Months 0.255181E+09 0.00 0.00 2838455.04 0.00 0.00 0.316587E+09 0.00 0.57
Maximum of Months 0.104027E+10 0.732600E+09 0.00 6171263.01 0.108611E+09 94945213.86 0.322118E+10 0.00 1.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.254146E+09 0.00 0.00 0.00 0.00 0.146820E+10 0.00 0.00 0.94
February 0.423483E+09 0.00 0.00 0.00 0.00 0.963823E+09 0.00 0.00 0.98
March 0.787217E+09 0.00 0.00 0.00 0.00 0.603605E+09 0.00 0.00 1.06
April 0.855531E+09 0.00 0.00 0.00 76141.36 0.177472E+09 0.00 0.00 1.33
May 0.711508E+09 8613130.19 20095.47 0.35 9258290.58 32801495.70 467.59 2217.74 1.89
June 0.422271E+09 39392552.56 435844.42 2102.66 0.123090E+09 5600856.61 3818034.83 16011.87 1.89
July 0.258959E+09 44101727.88 1561933.86 121.50 0.192656E+09 4989824.51 720379.58 24512.01 1.62
August 0.369747E+09 33434416.42 169121.73 22.72 0.129519E+09 9659014.32 2716.32 11250.93 2.14
September 0.794961E+09 984562.82 0.00 0.00 12476440.29 32763130.68 0.00 0.00 2.14
October 0.909273E+09 0.00 0.00 0.00 0.00 0.147159E+09 0.00 0.00 1.44
November 0.695081E+09 0.00 0.00 0.00 0.00 0.485300E+09 0.00 0.00 1.15
December 0.363645E+09 0.00 0.00 0.00 0.00 0.125564E+10 0.00 0.00 0.94
                   
Annual Sum or Average 0.684582E+10 0.126526E+09 2186995.48 2247.22 0.467076E+09 0.518701E+10 4541598.32 53992.56 1.46
Minimum of Months 0.254146E+09 0.00 0.00 0.00 0.00 4989824.51 0.00 0.00 0.94
Maximum of Months 0.909273E+09 44101727.88 1561933.86 2102.66 0.192656E+09 0.146820E+10 3818034.83 24512.01 2.14



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 MECHANICAL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 7754971.51 0.00 0.00 33458518.04 0.00 0.00 0.641426E+10 0.00 2.04
February 4925346.67 0.00 0.00 36338518.55 0.00 0.00 0.588341E+10 0.00 2.38
March 2292298.89 0.00 0.00 42629615.44 0.00 0.00 0.637228E+10 0.00 2.71
April 300952.78 464888.51 0.00 49795028.63 0.00 0.00 0.498497E+10 0.00 3.56
May 118743.28 82310706.80 0.00 52815432.40 0.00 0.00 0.371565E+10 0.00 5.22
June 31466.80 0.797717E+09 0.00 40129103.69 4609.64 0.00 0.217998E+10 0.00 5.34
July 2549.38 0.122010E+10 0.00 29262424.49 9006.20 0.00 0.144225E+10 0.00 4.82
August 26780.89 0.756982E+09 0.00 32854226.99 1681.12 0.00 0.194926E+10 0.00 6.10
September 170645.09 61389601.83 0.00 60653261.19 6747.63 0.00 0.404688E+10 0.00 5.91
October 339181.22 0.00 0.00 58440992.72 0.00 0.00 0.501737E+10 0.00 3.88
November 1426070.78 0.00 0.00 45809066.10 0.00 0.00 0.535854E+10 0.00 2.91
December 6117274.91 0.00 0.00 36210764.22 0.00 0.00 0.655352E+10 0.00 2.19
                   
Annual Sum or Average 23506282.22 0.291897E+10 0.00 0.518397E+09 22044.59 0.00 0.539184E+11 0.00 3.93
Minimum of Months 2549.38 0.00 0.00 29262424.49 0.00 0.00 0.144225E+10 0.00 2.04
Maximum of Months 7754971.51 0.122010E+10 0.00 60653261.19 9006.20 0.00 0.655352E+10 0.00 6.10



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.247844E+09 0.00 0.00 55.81 0.00 0.177650E+09 1100486.88 0.00 0.15
February 0.247455E+09 0.00 0.00 18017.03 0.00 81174970.28 12557826.15 0.00 0.15
March 0.262024E+09 0.00 0.00 154080.85 0.00 17874987.69 94722264.66 0.00 0.19
April 0.177995E+09 0.00 0.00 474624.03 18382.69 670545.14 0.163329E+09 0.00 0.30
May 0.119822E+09 14156368.42 0.00 746212.49 364180.16 0.00 0.163589E+09 0.00 0.49
June 72020093.75 91898538.06 0.00 728737.09 12387763.47 0.00 0.110515E+09 0.00 0.55
July 48675375.20 0.126115E+09 0.00 429384.44 19644383.95 0.00 45386648.56 0.00 0.47
August 61764623.44 83455874.28 0.00 527254.03 13911401.90 0.00 83376265.02 0.00 0.57
September 0.128071E+09 4677810.39 0.00 657478.22 1836026.79 0.00 0.181203E+09 0.00 0.51
October 0.179320E+09 0.00 0.00 343700.71 0.00 1409683.71 0.134367E+09 0.00 0.28
November 0.220235E+09 0.00 0.00 117192.15 0.00 20630117.69 61165884.96 0.00 0.19
December 0.269628E+09 0.00 0.00 999.53 0.00 0.123537E+09 4003391.11 0.00 0.15
                   
Annual Sum or Average 0.203485E+10 0.320304E+09 0.00 4197736.39 48162138.96 0.422947E+09 0.105532E+10 0.00 0.33
Minimum of Months 48675375.20 0.00 0.00 55.81 0.00 0.00 1100486.88 0.00 0.15
Maximum of Months 0.269628E+09 0.126115E+09 0.00 746212.49 19644383.95 0.177650E+09 0.181203E+09 0.00 0.57



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 OFFICE

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.404983E+10 0.00 0.00 378149.87 0.00 0.163467E+10 0.406200E+09 0.00 0.21
February 0.339626E+10 0.00 0.00 1439409.78 0.00 0.715854E+09 0.958075E+09 0.00 0.23
March 0.317813E+10 0.00 0.00 3344417.25 0.00 0.261479E+09 0.221430E+10 0.00 0.28
April 0.235983E+10 0.00 0.00 5998920.30 263914.43 7472258.93 0.228254E+10 0.00 0.39
May 0.172643E+10 0.162799E+09 0.00 8402823.16 4385621.85 574554.46 0.192875E+10 0.00 0.62
June 0.102332E+10 0.102962E+10 0.00 7442017.94 0.176371E+09 0.00 0.111958E+10 0.00 0.64
July 0.690219E+09 0.134263E+10 0.00 4293643.35 0.284726E+09 0.00 0.442774E+09 0.00 0.53
August 0.866939E+09 0.950662E+09 0.00 6255757.45 0.194998E+09 0.00 0.101698E+10 0.00 0.70
September 0.185982E+10 52496572.71 0.00 8253602.52 26359251.24 0.00 0.229516E+10 0.00 0.66
October 0.233960E+10 0.00 0.00 6309666.34 0.00 14546430.83 0.250478E+10 0.00 0.42
November 0.274197E+10 0.00 0.00 3632304.37 0.00 0.177651E+09 0.193968E+10 0.00 0.31
December 0.378044E+10 0.00 0.00 1034762.23 0.00 0.119374E+10 0.816679E+09 0.00 0.22
                   
Annual Sum or Average 0.280128E+11 0.353821E+10 0.00 56785474.56 0.687104E+09 0.400600E+10 0.179255E+11 0.00 0.44
Minimum of Months 0.690219E+09 0.00 0.00 378149.87 0.00 0.00 0.406200E+09 0.00 0.21
Maximum of Months 0.404983E+10 0.134263E+10 0.00 8402823.16 0.284726E+09 0.163467E+10 0.250478E+10 0.00 0.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 OFFICE HALL

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.673040E+09 0.00 0.00 1987.42 0.00 0.526998E+09 4144806.64 0.00 0.15
February 0.658320E+09 0.00 0.00 60512.19 0.00 0.259782E+09 44836598.70 0.00 0.16
March 0.707660E+09 0.00 0.00 245120.21 0.00 0.117709E+09 0.174115E+09 0.00 0.18
April 0.543272E+09 0.00 0.00 658837.10 51262.60 17915857.71 0.245281E+09 0.00 0.25
May 0.373363E+09 32392567.75 0.00 1070218.55 1015565.30 1923308.20 0.246493E+09 0.00 0.40
June 0.216380E+09 0.186957E+09 0.00 1007612.88 38936802.12 21980.58 0.156779E+09 0.00 0.41
July 0.146111E+09 0.244163E+09 0.00 532361.94 60655980.18 0.00 52775482.61 0.00 0.35
August 0.186820E+09 0.177313E+09 0.00 696471.61 39219355.25 0.00 0.129548E+09 0.00 0.45
September 0.399008E+09 10003210.07 0.00 990298.39 5126350.15 97302.11 0.304417E+09 0.00 0.42
October 0.554451E+09 0.00 0.00 576723.79 0.00 16846409.09 0.231976E+09 0.00 0.26
November 0.589722E+09 0.00 0.00 243060.97 0.00 0.102019E+09 0.143136E+09 0.00 0.19
December 0.698991E+09 0.00 0.00 1196.23 0.00 0.413675E+09 5458200.86 0.00 0.15
                   
Annual Sum or Average 0.574714E+10 0.650829E+09 0.00 6084401.28 0.145005E+09 0.145699E+10 0.173896E+10 0.00 0.28
Minimum of Months 0.146111E+09 0.00 0.00 1196.23 0.00 0.00 4144806.64 0.00 0.15
Maximum of Months 0.707660E+09 0.244163E+09 0.00 1070218.55 60655980.18 0.526998E+09 0.304417E+09 0.00 0.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 OFFICE TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 46410834.90 0.00 0.00 0.00 0.00 0.445251E+09 0.00 0.00 0.95
February 63425892.90 0.00 0.00 0.00 0.00 0.332595E+09 0.00 0.00 0.99
March 0.118766E+09 0.00 0.00 0.00 0.00 0.278258E+09 0.00 0.00 1.08
April 0.167632E+09 0.00 0.00 0.00 21735.34 0.127249E+09 0.00 0.00 1.35
May 0.172658E+09 0.00 9280.52 0.00 5098172.89 39812413.38 0.00 497.83 1.92
June 0.111079E+09 629448.44 805794.16 0.00 45070656.26 12151813.31 0.00 5428.64 1.92
July 70057384.49 0.00 1062723.32 0.00 66968510.36 5495346.30 0.00 6484.22 1.65
August 99984428.25 0.00 163355.40 0.00 46402274.36 8321731.04 0.00 2688.22 2.17
September 0.203247E+09 0.00 0.00 0.00 3842582.41 33035101.72 0.00 0.00 2.17
October 0.192652E+09 0.00 0.00 0.00 0.00 0.108917E+09 0.00 0.00 1.46
November 0.115700E+09 0.00 0.00 0.00 0.00 0.221252E+09 0.00 0.00 1.17
December 61681885.46 0.00 0.00 0.00 0.00 0.400559E+09 0.00 0.00 0.96
                   
Annual Sum or Average 0.142330E+10 629448.44 2041153.41 0.00 0.167404E+09 0.201290E+10 0.00 15098.90 1.48
Minimum of Months 46410834.90 0.00 0.00 0.00 0.00 5495346.30 0.00 0.00 0.95
Maximum of Months 0.203247E+09 629448.44 1062723.32 0.00 66968510.36 0.445251E+09 0.00 6484.22 2.17



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.791009E+10 0.00 0.00 2285564.92 0.00 0.437897E+10 0.418590E+10 0.00 1.32
February 0.668075E+10 0.00 0.00 4165743.94 0.00 0.249217E+10 0.422977E+10 0.00 1.40
March 0.793440E+10 0.00 0.00 4963861.02 0.00 0.121657E+10 0.431934E+10 0.00 1.53
April 0.693246E+10 0.00 0.00 5232089.72 718985.30 0.325883E+09 0.273713E+10 0.00 1.92
May 0.524621E+10 0.158657E+09 188006.82 4038740.12 15043527.87 59288539.42 0.174307E+10 22691.69 2.65
June 0.315629E+10 0.935505E+09 2755276.10 3140785.60 0.628774E+09 18121998.84 0.900300E+09 124824.00 2.64
July 0.222185E+10 0.130517E+10 7453545.61 1570855.21 0.956142E+09 13636309.48 0.263113E+09 176368.66 2.27
August 0.286286E+10 0.980612E+09 1225138.18 1510005.42 0.597475E+09 27206424.63 0.692453E+09 106721.04 3.00
September 0.569484E+10 62987009.98 0.00 4500734.65 72660790.05 53397753.27 0.211596E+10 0.00 3.01
October 0.700396E+10 0.00 0.00 3899446.59 0.00 0.343207E+09 0.278377E+10 0.00 2.06
November 0.686822E+10 0.00 0.00 2857489.43 0.00 0.130781E+10 0.318267E+10 0.00 1.64
December 0.846537E+10 0.00 0.00 1134831.35 0.00 0.361284E+10 0.324162E+10 0.00 1.32
                   
Annual Sum or Average 0.709773E+11 0.344293E+10 11621966.71 39300147.96 0.227081E+10 0.138491E+11 0.303951E+11 430605.39 2.06
Minimum of Months 0.222185E+10 0.00 0.00 1134831.35 0.00 13636309.48 0.263113E+09 0.00 1.32
Maximum of Months 0.846537E+10 0.130517E+10 7453545.61 5232089.72 0.956142E+09 0.437897E+10 0.431934E+10 176368.66 3.01



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.519844E+10 0.00 0.00 260629.35 0.00 0.445847E+09 0.194325E+10 0.00 1.34
February 0.444708E+10 0.00 0.00 324156.15 0.00 0.241702E+09 0.142267E+10 0.00 1.40
March 0.438643E+10 0.00 0.00 749488.15 0.00 62635743.97 0.167745E+10 0.00 1.52
April 0.343853E+10 0.00 0.00 1004107.95 335440.60 21881675.96 0.108948E+10 0.00 1.91
May 0.256717E+10 70899319.94 88249.83 818926.90 7833188.92 12592807.11 0.698477E+09 10050.97 2.70
June 0.155212E+10 0.402897E+09 1280235.21 550447.89 0.313574E+09 6894320.80 0.342250E+09 56114.10 2.70
July 0.106571E+10 0.539554E+09 3479335.71 233372.22 0.506909E+09 4829982.70 95230755.81 80379.69 2.32
August 0.135977E+10 0.421543E+09 574717.38 326868.88 0.296523E+09 8060917.45 0.303328E+09 46657.85 3.06
September 0.274537E+10 23664610.62 0.00 849422.52 35637811.96 13055740.06 0.887263E+09 0.00 3.05
October 0.339946E+10 0.00 0.00 889639.10 0.00 20831523.64 0.123292E+10 0.00 2.06
November 0.368474E+10 0.00 0.00 620766.61 0.00 83442978.12 0.143136E+10 0.00 1.64
December 0.493510E+10 0.00 0.00 225389.70 0.00 0.433028E+09 0.176540E+10 0.00 1.35
                   
Annual Sum or Average 0.387799E+11 0.145856E+10 5422538.14 6853215.42 0.116081E+10 0.135480E+10 0.128891E+11 193202.62 2.09
Minimum of Months 0.106571E+10 0.00 0.00 225389.70 0.00 4829982.70 95230755.81 0.00 1.34
Maximum of Months 0.519844E+10 0.539554E+09 3479335.71 1004107.95 0.506909E+09 0.445847E+09 0.194325E+10 80379.69 3.06



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.554366E+09 0.00 0.00 0.00 0.00 0.245863E+09 0.00 0.00 0.99
February 0.517144E+09 0.00 0.00 0.00 0.00 0.127421E+09 0.00 0.00 1.04
March 0.595546E+09 0.00 0.00 0.00 0.00 50651513.29 0.00 0.00 1.13
April 0.467574E+09 0.00 0.00 10.47 35376.49 12034350.55 340906.79 0.00 1.42
May 0.342163E+09 238606.52 9897.95 0.00 8064741.33 3654724.63 0.00 469.13 2.01
June 0.199354E+09 7472861.25 195801.26 0.00 68028727.88 1216436.93 0.00 4569.13 2.01
July 0.121678E+09 2913319.20 693138.80 0.00 0.107125E+09 1291474.18 0.00 7246.83 1.72
August 0.174589E+09 61082.41 63384.12 0.00 75668189.74 1690226.55 0.00 2061.11 2.28
September 0.381798E+09 0.00 0.00 0.00 6254197.28 2775990.15 0.00 0.00 2.27
October 0.478358E+09 0.00 0.00 0.00 0.00 12476768.54 0.00 0.00 1.53
November 0.498460E+09 0.00 0.00 0.00 0.00 49963899.89 0.00 0.00 1.22
December 0.578618E+09 0.00 0.00 0.00 0.00 0.173727E+09 0.00 0.00 1.00
                   
Annual Sum or Average 0.490965E+10 10685869.39 962222.12 10.47 0.265176E+09 0.682766E+09 340906.79 14346.20 1.55
Minimum of Months 0.121678E+09 0.00 0.00 0.00 0.00 1216436.93 0.00 0.00 0.99
Maximum of Months 0.595546E+09 7472861.25 693138.80 10.47 0.107125E+09 0.245863E+09 340906.79 7246.83 2.28



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 STORAGE 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.285785E+09 0.00 0.00 0.00 0.00 0.516791E+09 0.00 0.00 0.78
February 0.321249E+09 0.00 0.00 0.00 0.00 0.325206E+09 0.00 0.00 0.81
March 0.453510E+09 0.00 0.00 0.00 0.00 0.194583E+09 0.00 0.00 0.88
April 0.418957E+09 0.00 0.00 0.00 35480.25 62400066.75 0.00 0.00 1.11
May 0.324909E+09 0.00 26795.18 0.00 8309913.18 21922975.05 0.00 1390.45 1.57
June 0.193794E+09 0.00 861329.70 0.00 75052219.58 7365010.94 0.00 10441.92 1.57
July 0.117062E+09 0.00 2428903.81 0.00 0.108618E+09 6268744.62 0.00 16583.04 1.34
August 0.166678E+09 0.00 363350.36 0.00 75647699.95 10118853.34 0.00 5970.81 1.77
September 0.366383E+09 0.00 0.00 0.00 6272540.66 19319216.25 0.00 0.00 1.77
October 0.440254E+09 0.00 0.00 0.00 0.00 52020132.97 0.00 0.00 1.19
November 0.397435E+09 0.00 0.00 0.00 0.00 0.152597E+09 0.00 0.00 0.95
December 0.320636E+09 0.00 0.00 0.00 0.00 0.433916E+09 0.00 0.00 0.78
                   
Annual Sum or Average 0.380665E+10 0.00 3680379.05 0.00 0.273936E+09 0.180251E+10 0.00 34386.22 1.21
Minimum of Months 0.117062E+09 0.00 0.00 0.00 0.00 6268744.62 0.00 0.00 0.78
Maximum of Months 0.453510E+09 0.00 2428903.81 0.00 0.108618E+09 0.516791E+09 0.00 16583.04 1.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 STORAGE 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 86073442.45 0.00 0.00 0.00 0.00 0.148833E+09 0.00 0.00 0.29
February 0.100913E+09 0.00 0.00 0.00 0.00 87773367.14 0.00 0.00 0.30
March 0.139011E+09 0.00 0.00 966.32 0.00 46999625.77 2734001.52 0.00 0.33
April 0.124240E+09 0.00 0.00 12080.25 10307.70 9326253.67 6488839.95 0.00 0.42
May 89289968.27 2594683.65 0.00 29144.12 234067.13 1336961.05 10430937.33 0.00 0.60
June 51250534.92 14104137.92 2831.62 40968.22 10638697.61 95525.38 7451463.28 191.58 0.60
July 34135132.39 17180212.69 21205.23 17599.74 17301915.01 73905.78 1671167.35 374.87 0.51
August 45940192.93 12373352.37 0.00 16176.42 11045522.74 77581.20 5389239.73 0.00 0.67
September 98173361.53 612830.80 0.00 22420.04 1284028.58 682123.34 13239682.15 0.00 0.67
October 0.130900E+09 0.00 0.00 7657.84 0.00 6745607.88 5460194.09 0.00 0.45
November 0.125245E+09 0.00 0.00 115.76 0.00 34583253.29 279283.31 0.00 0.36
December 97292379.04 0.00 0.00 0.00 0.00 0.123151E+09 0.00 0.00 0.29
                   
Annual Sum or Average 0.112247E+10 46865217.43 24036.85 147128.71 40514538.77 0.459678E+09 53144808.69 566.45 0.46
Minimum of Months 34135132.39 0.00 0.00 0.00 0.00 73905.78 0.00 0.00 0.29
Maximum of Months 0.139011E+09 17180212.69 21205.23 40968.22 17301915.01 0.148833E+09 13239682.15 374.87 0.67



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 TREATMENT

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.406558E+10 0.00 0.00 324428.99 0.00 0.255983E+09 0.163210E+10 0.00 1.31
February 0.342453E+10 0.00 0.00 478101.41 0.00 0.101918E+09 0.126905E+10 0.00 1.37
March 0.332286E+10 0.00 0.00 927865.97 0.00 29016118.02 0.146114E+10 0.00 1.48
April 0.263298E+10 0.00 0.00 1193477.18 263213.28 10854015.59 0.930997E+09 0.00 1.87
May 0.195364E+10 55749282.93 71839.34 1015645.97 6030483.66 6212149.93 0.612712E+09 5295.27 2.64
June 0.118676E+10 0.323061E+09 984956.76 652454.19 0.239165E+09 4141883.78 0.300760E+09 37549.57 2.64
July 0.830635E+09 0.433879E+09 2269042.04 266326.28 0.387727E+09 3186297.54 80850054.65 56115.27 2.26
August 0.104777E+10 0.337289E+09 460006.32 397224.87 0.226163E+09 4291055.71 0.259117E+09 26928.77 2.98
September 0.209443E+10 19708488.33 0.00 1104983.21 26824892.59 5973429.50 0.761182E+09 0.00 2.98
October 0.257389E+10 0.00 0.00 1192652.49 0.00 8649564.05 0.106975E+10 0.00 2.01
November 0.279416E+10 0.00 0.00 828206.02 0.00 58279680.83 0.122733E+10 0.00 1.61
December 0.390216E+10 0.00 0.00 287612.29 0.00 0.182274E+09 0.151298E+10 0.00 1.32
                   
Annual Sum or Average 0.298294E+11 0.116969E+10 3785844.45 8668978.87 0.886174E+09 0.670779E+09 0.111180E+11 125888.89 2.04
Minimum of Months 0.830635E+09 0.00 0.00 266326.28 0.00 3186297.54 80850054.65 0.00 1.31
Maximum of Months 0.406558E+10 0.433879E+09 2269042.04 1193477.18 0.387727E+09 0.255983E+09 0.163210E+10 56115.27 2.98



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.364396E+10 0.00 0.00 629874.94 0.00 0.230328E+10 0.556182E+09 0.00 0.30
February 0.309581E+10 0.00 0.00 1700026.81 0.00 0.122842E+10 0.111445E+10 0.00 0.33
March 0.338917E+10 0.00 0.00 2565324.79 0.00 0.660769E+09 0.161290E+10 0.00 0.37
April 0.293882E+10 0.00 0.00 3627274.30 278487.08 74281472.25 0.135121E+10 0.00 0.50
May 0.201855E+10 0.131453E+09 0.00 4411673.58 5517117.66 5904046.06 0.106192E+10 0.00 0.71
June 0.118927E+10 0.721582E+09 37850.90 3704568.44 0.221060E+09 821558.08 0.573483E+09 1163.28 0.70
July 0.829453E+09 0.968725E+09 288597.19 1802545.41 0.348011E+09 408909.55 0.184094E+09 2182.52 0.60
August 0.105436E+10 0.742259E+09 0.00 2231956.39 0.215772E+09 888052.64 0.441693E+09 0.00 0.77
September 0.220543E+10 45897491.88 0.00 4272998.31 27814738.13 3007566.41 0.126440E+10 0.00 0.77
October 0.299980E+10 0.00 0.00 2954047.05 0.00 80358221.10 0.117865E+10 0.00 0.51
November 0.306516E+10 0.00 0.00 1630128.67 0.00 0.490351E+09 0.103926E+10 0.00 0.38
December 0.371811E+10 0.00 0.00 185460.69 0.00 0.195518E+10 0.293745E+09 0.00 0.29
                   
Annual Sum or Average 0.301479E+11 0.260992E+10 326448.09 29715879.39 0.818453E+09 0.680368E+10 0.106720E+11 3345.81 0.52
Minimum of Months 0.829453E+09 0.00 0.00 185460.69 0.00 408909.55 0.184094E+09 0.00 0.29
Maximum of Months 0.371811E+10 0.968725E+09 288597.19 4411673.58 0.348011E+09 0.230328E+10 0.161290E+10 2182.52 0.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.145397E+10 0.00 0.00 204755.45 0.00 0.164366E+10 0.164019E+09 0.00 0.29
February 0.142516E+10 0.00 0.00 579142.49 0.00 0.872307E+09 0.403208E+09 0.00 0.32
March 0.168545E+10 0.00 0.00 914700.91 0.00 0.543829E+09 0.570167E+09 0.00 0.36
April 0.150145E+10 0.00 0.00 1637643.17 141667.67 86431951.85 0.586670E+09 0.00 0.49
May 0.104237E+10 71064816.87 0.00 2172508.01 2806583.47 6883302.18 0.503528E+09 0.00 0.71
June 0.605298E+09 0.401393E+09 0.00 1915702.86 0.106326E+09 348279.46 0.292145E+09 0.00 0.71
July 0.411608E+09 0.544425E+09 0.00 1062564.60 0.166030E+09 46244.78 0.110776E+09 0.00 0.62
August 0.516242E+09 0.409915E+09 0.00 1346324.09 0.108532E+09 207574.17 0.251014E+09 0.00 0.79
September 0.113054E+10 25407299.04 0.00 2192879.21 14149486.92 1249019.82 0.628254E+09 0.00 0.78
October 0.158690E+10 0.00 0.00 1338386.62 0.00 62928111.14 0.495947E+09 0.00 0.51
November 0.150707E+10 0.00 0.00 575300.10 0.00 0.440753E+09 0.354110E+09 0.00 0.38
December 0.151366E+10 0.00 0.00 24239.05 0.00 0.146353E+10 51070071.48 0.00 0.29
                   
Annual Sum or Average 0.143797E+11 0.145221E+10 0.00 13964146.55 0.397986E+09 0.512218E+10 0.441091E+10 0.00 0.52
Minimum of Months 0.411608E+09 0.00 0.00 24239.05 0.00 46244.78 51070071.48 0.00 0.29
Maximum of Months 0.168545E+10 0.544425E+09 0.00 2192879.21 0.166030E+09 0.164366E+10 0.628254E+09 0.00 0.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 UTILITY

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.182911E+09 0.00 0.00 0.00 0.00 0.417054E+09 0.00 0.00 0.29
February 0.203751E+09 0.00 0.00 0.00 0.00 0.279506E+09 0.00 0.00 0.30
March 0.315435E+09 0.00 0.00 0.00 0.00 0.169046E+09 0.00 0.00 0.33
April 0.317087E+09 0.00 0.00 0.00 26523.20 42750452.76 0.00 0.00 0.41
May 0.250436E+09 1041180.31 2707.83 0.00 5189024.63 8838230.68 0.00 219.19 0.59
June 0.148564E+09 8490140.47 140270.85 34.55 48122543.70 1778838.45 33024.49 3898.92 0.59
July 90764439.23 6444687.59 431847.88 0.00 76140762.74 1431065.33 0.00 7784.61 0.50
August 0.130121E+09 1913029.71 34479.94 0.00 54877464.84 2042919.00 0.00 1423.81 0.66
September 0.281516E+09 0.00 0.00 0.00 4689027.39 6814317.32 0.00 0.00 0.66
October 0.333031E+09 0.00 0.00 0.00 0.00 34968406.42 0.00 0.00 0.45
November 0.284298E+09 0.00 0.00 0.00 0.00 0.126877E+09 0.00 0.00 0.36
December 0.206770E+09 0.00 0.00 0.00 0.00 0.357294E+09 0.00 0.00 0.29
                   
Annual Sum or Average 0.274468E+10 17889038.09 609306.50 34.55 0.189045E+09 0.144840E+10 33024.49 13326.54 0.45
Minimum of Months 90764439.23 0.00 0.00 0.00 0.00 1431065.33 0.00 0.00 0.29
Maximum of Months 0.333031E+09 8490140.47 431847.88 34.55 76140762.74 0.417054E+09 33024.49 7784.61 0.66



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FLOOR 3 WORK

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.546574E+09 0.00 0.00 10636.71 0.00 0.624135E+09 15173841.67 0.00 0.21
February 0.539294E+09 0.00 0.00 253213.00 0.00 0.276404E+09 0.164225E+09 0.00 0.23
March 0.505664E+09 0.00 0.00 994271.63 0.00 0.122674E+09 0.602153E+09 0.00 0.32
April 0.434169E+09 0.00 0.00 2215381.59 49858.05 7751932.88 0.789770E+09 0.00 0.55
May 0.315395E+09 46308035.54 0.00 2854287.06 831886.85 30905.25 0.630575E+09 0.00 0.85
June 0.187026E+09 0.308565E+09 0.00 2741243.34 32521674.73 0.00 0.428508E+09 0.00 0.97
July 0.127655E+09 0.439384E+09 0.00 1588201.50 50097762.78 0.00 0.175959E+09 0.00 0.81
August 0.162977E+09 0.276627E+09 0.00 1764999.15 36913657.19 0.00 0.277004E+09 0.00 0.93
September 0.348396E+09 16137109.17 0.00 2222357.68 4979723.14 69054.81 0.605222E+09 0.00 0.82
October 0.446148E+09 0.00 0.00 1252104.70 0.00 11972395.19 0.497644E+09 0.00 0.45
November 0.482251E+09 0.00 0.00 561007.69 0.00 0.117761E+09 0.295888E+09 0.00 0.30
December 0.525246E+09 0.00 0.00 24738.33 0.00 0.537984E+09 26744313.35 0.00 0.21
                   
Annual Sum or Average 0.462079E+10 0.108702E+10 0.00 16482442.38 0.125395E+09 0.169878E+10 0.450887E+10 0.00 0.56
Minimum of Months 0.127655E+09 0.00 0.00 10636.71 0.00 0.00 15173841.67 0.00 0.21
Maximum of Months 0.546574E+09 0.439384E+09 0.00 2854287.06 50097762.78 0.624135E+09 0.789770E+09 0.00 0.97



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: NE STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 4731276.23 0.00 0.00 0.00 0.00 0.186657E+10 0.00 0.00 0.36
February 8414313.96 0.00 0.00 0.00 0.00 0.124984E+10 0.00 0.00 0.30
March 18789301.46 0.00 0.00 0.00 0.00 0.974577E+09 0.00 0.00 0.26
April 58788237.82 0.00 0.00 0.00 17952.98 0.376962E+09 0.00 0.00 0.19
May 0.114262E+09 11159567.63 4004.47 51491.95 604383.58 85687408.43 3088943.75 662.30 0.20
June 82781700.80 89086254.04 858658.87 207392.08 16120400.43 12732791.54 14787075.99 11450.18 0.23
July 54463340.62 0.135871E+09 80519.64 165677.24 24203342.12 4227123.99 11534879.57 2731.38 0.23
August 80602068.74 88265635.67 9985.46 103171.64 16052088.80 5738329.39 8562954.96 795.81 0.26
September 0.154889E+09 4480288.92 0.00 99192.79 1867762.80 41251987.05 13154867.26 0.00 0.21
October 0.110802E+09 0.00 0.00 6923.33 0.00 0.204335E+09 804624.22 0.00 0.15
November 31699266.16 0.00 0.00 0.00 0.00 0.547865E+09 0.00 0.00 0.19
December 6716124.76 0.00 0.00 0.00 0.00 0.154363E+10 0.00 0.00 0.32
                   
Annual Sum or Average 0.726939E+09 0.328862E+09 953168.44 633849.03 58865930.71 0.691342E+10 51933345.74 15639.67 0.24
Minimum of Months 4731276.23 0.00 0.00 0.00 0.00 4227123.99 0.00 0.00 0.15
Maximum of Months 0.154889E+09 0.135871E+09 858658.87 207392.08 24203342.12 0.186657E+10 14787075.99 11450.18 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: NW ELEVATOR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 10637543.15 0.00 0.00 0.00 0.00 0.103606E+10 0.00 0.00 0.24
February 20951129.47 0.00 0.00 0.00 0.00 0.697615E+09 0.00 0.00 0.21
March 36780362.35 0.00 0.00 0.00 0.00 0.554113E+09 0.00 0.00 0.19
April 59471367.30 0.00 0.00 3070.23 11617.19 0.218845E+09 637570.78 0.00 0.14
May 78758556.28 5527216.77 0.00 19727.78 894944.37 54959241.66 1818219.69 0.00 0.15
June 55185119.94 38433513.66 691044.84 44645.69 13860491.62 12144024.77 2335464.03 7741.35 0.16
July 37286421.93 56584835.43 87525.37 47476.23 19596726.42 2361004.98 2719352.20 1505.64 0.15
August 55000265.62 47148361.54 2425.36 39398.10 11791039.87 1874049.01 2587881.93 44.40 0.18
September 0.106615E+09 2622625.91 0.00 56390.71 1314101.88 18512430.24 8411938.47 0.00 0.16
October 94555195.21 0.00 0.00 26841.15 0.00 93754899.57 6147679.28 0.00 0.12
November 51163087.77 0.00 0.00 0.00 0.00 0.272134E+09 0.00 0.00 0.13
December 18307110.66 0.00 0.00 0.00 0.00 0.819030E+09 0.00 0.00 0.21
                   
Annual Sum or Average 0.624711E+09 0.150317E+09 780995.56 237549.89 47468921.35 0.378141E+10 24658106.39 9291.39 0.17
Minimum of Months 10637543.15 0.00 0.00 0.00 0.00 1874049.01 0.00 0.00 0.12
Maximum of Months 0.106615E+09 56584835.43 691044.84 56390.71 19596726.42 0.103606E+10 8411938.47 7741.35 0.24



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: NW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 6217322.27 0.00 0.00 0.00 0.00 0.197487E+10 0.00 0.00 0.33
February 11393386.77 0.00 0.00 0.00 0.00 0.134006E+10 0.00 0.00 0.29
March 23526266.38 0.00 0.00 0.00 0.00 0.105810E+10 0.00 0.00 0.25
April 70865785.94 0.00 0.00 0.00 20545.97 0.411575E+09 0.00 0.00 0.18
May 0.137820E+09 12832999.73 0.00 43971.22 592562.38 88709487.47 3374989.17 0.00 0.20
June 97414549.60 99601698.10 344699.82 184157.52 18522791.73 14349437.72 12154254.32 5727.81 0.22
July 64136917.62 0.146165E+09 21934.80 160480.60 26283679.17 2966888.05 11221806.22 861.48 0.22
August 94452031.69 96689227.39 0.00 106164.39 17761046.37 3189443.81 10473970.04 0.00 0.25
September 0.178784E+09 4527132.15 0.00 81751.65 2109634.51 40141898.14 14238019.16 0.00 0.21
October 0.141852E+09 0.00 0.00 3628.99 0.00 0.201570E+09 539604.34 0.00 0.15
November 45162454.94 0.00 0.00 0.00 0.00 0.565090E+09 0.00 0.00 0.18
December 9686126.16 0.00 0.00 0.00 0.00 0.161337E+10 0.00 0.00 0.29
                   
Annual Sum or Average 0.881312E+09 0.359816E+09 366634.62 580154.37 65290260.12 0.731400E+10 52002643.26 6589.30 0.23
Minimum of Months 6217322.27 0.00 0.00 0.00 0.00 2966888.05 0.00 0.00 0.15
Maximum of Months 0.178784E+09 0.146165E+09 344699.82 184157.52 26283679.17 0.197487E+10 14238019.16 5727.81 0.33



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: SW STAIR

Timestamp: 2020-06-04 00:31:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 13583584.88 0.00 0.00 696.88 0.00 0.636753E+09 395108.02 0.00 0.22
February 21202218.48 0.00 0.00 12346.41 0.00 0.419093E+09 6523605.95 0.00 0.19
March 31989789.16 0.00 0.00 9922.61 0.00 0.331453E+09 5933264.57 0.00 0.17
April 43504355.19 0.00 0.00 51625.99 7113.27 0.124085E+09 12673479.37 0.00 0.14
May 52385136.08 8740848.62 0.00 71814.11 181211.58 26509345.27 7987531.88 0.00 0.17
June 34616486.56 49287515.75 93811.39 102235.46 6722030.79 4807254.02 6742456.08 1405.12 0.18
July 22897289.70 74198736.28 0.00 86829.62 8934875.21 626767.09 5426856.51 0.00 0.19
August 32380677.57 63288990.18 0.00 85286.57 5434781.29 553939.20 7632373.84 0.00 0.23
September 63356669.32 4156120.75 0.00 184176.26 721743.08 5401526.70 34424757.22 0.00 0.20
October 64235277.28 0.00 0.00 111869.01 0.00 49296231.48 27345683.39 0.00 0.14
November 40313382.23 0.00 0.00 20845.50 0.00 0.164826E+09 9954455.36 0.00 0.13
December 14767956.32 0.00 0.00 0.00 0.00 0.521798E+09 0.00 0.00 0.19
                   
Annual Sum or Average 0.435233E+09 0.199672E+09 93811.39 737648.43 22001755.23 0.228520E+10 0.125040E+09 1405.12 0.18
Minimum of Months 13583584.88 0.00 0.00 0.00 0.00 553939.20 0.00 0.00 0.13
Maximum of Months 64235277.28 74198736.28 93811.39 184176.26 8934875.21 0.636753E+09 34424757.22 1405.12 0.23