Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2020-06-03 19:12:25
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2485.77 | 1083.60 | 1083.60 |
Net Site Energy | 2485.77 | 1083.60 | 1083.60 |
Total Source Energy | 5570.39 | 2428.25 | 2428.25 |
Net Source Energy | 5570.39 | 2428.25 | 2428.25 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1002.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 135.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 492.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 114.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 443.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 102.74 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1380.61 | 1105.15 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1002.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 135.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 492.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 114.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 443.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 102.74 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 264.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 252.24 | 481.76 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 601.84 | 481.76 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 264.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 252.24 | 481.76 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 601.84 | 481.76 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1380.614 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1380.614 | 100.00 |
Total On-Site and Utility Electric Sources | 1380.614 | 100.00 |
Total Electricity End Uses | 1380.614 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2401.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 8.56 |
Skylight-Roof Ratio [%] | 0.37 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 9.0309 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 18.2986 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 18.2986 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 18.2986 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 13.9931 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.7414 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.7414 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-15:00 | 09-JAN-07:10 | - | - | - | 30-MAR-11:09 |
Heating | 0.00 | 327590.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 57603.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 34564.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18717.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 2159.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 121656.31 | 329749.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 327590.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 57603.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 34564.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 18717.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 2159.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1086.62 | 0.00 | 0.00 | 0.00 |
Cooling | 427.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1558.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 363.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1404.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 111.37 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4372.41 | 1197.99 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 473.68 | 0.00 | 0.00 | 0.00 |
Cooling | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 679.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 612.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 48.55 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1906.02 | 522.23 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 473.68 | 0.00 | 0.00 | 0.00 |
Cooling | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 679.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 612.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 48.55 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1906.02 | 522.23 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.77 |
CORE_RETAIL DIRECT AIR | 8.02 |
POINT_OF_SALE DIRECT AIR | 1.25 |
FRONT_RETAIL DIRECT AIR | 1.01 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 3.91 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 3.91 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 87550.48 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 53548.48 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 295239.35 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 38691.39 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 33402.06 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.77 | 1.77 | 1.77 | 1.77 | 1.81 | 1.81 | 1.00 | 0.977163 | 1.81 |
PSZ-AC:2 | 8.02 | 8.02 | 8.02 | 8.02 | 8.22 | 8.22 | 1.00 | 0.975582 | 8.22 |
PSZ-AC:3 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.00 | 1.00 | 1.25 |
PSZ-AC:4 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.00 | 1.00 | 1.01 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.81 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 8.22 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.25 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 1.01 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.81 | 1.81 | 1.81 | 1.81 | 34171.62 | 53548.48 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 8.22 | 8.22 | 8.22 | 8.22 | 165446.60 | 295239.35 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.25 | 1.25 | 1.25 | 1.25 | 22617.78 | 38691.39 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 1.01 | 19055.17 | 33402.06 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.81 | 0.906450 | 1.81 | 31855.86 | 34171.62 | 17085.81 | 34171.62 | 0.753879 | 0.753880 | 0.753880 | 0.753880 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 8.22 | 4.11 | 8.22 | 155117.75 | 165446.60 | 82723.30 | 165446.60 | 0.733482 | 0.733480 | 0.733480 | 0.733480 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.25 | 0.624635 | 1.25 | 21007.79 | 22617.78 | 11308.89 | 22617.78 | 0.767154 | 0.767160 | 0.767160 | 0.767160 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.01 | 0.504990 | 1.01 | 17766.07 | 19055.17 | 9527.58 | 19055.17 | 0.753576 | 0.753580 | 0.753580 | 0.753580 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.81 | 1984.23 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 8.22 | 14157.73 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.25 | 1424.31 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1151.49 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 65 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 6.69 | 10 | 14 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 9.031 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.101 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 18.299 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 21.529 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 18.299 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 39.819 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 18.299 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 21.529 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 13.993 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.993 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 3430.757 | 9.031 | 55.928 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3430.757 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 29286.673 | 18.299 | 113.324 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29286.673 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2759.619 | 18.299 | 113.324 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2759.619 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2759.619 | 18.299 | 113.324 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2759.619 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 167.917 | 13.993 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 167.917 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.4290 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1659 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.3309E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1913 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1913 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.3147 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.163 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.950 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 30.14 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.149 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.149 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.101 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8390000 | 2.8390000 | 2.8390000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 9 | 0.21485751E-14 | -0.22894401E-15 | -0.17283669E-09 | -0.31350098E-16 |
25 | 8 | 0.25115787E-07 | 0.58773152E-13 | 0.41104347E-03 | -0.28557513E-09 |
26 | 7 | -0.13231082E-01 | 0.29616277E-08 | -0.24509747E-01 | 0.15044224E-03 |
27 | 6 | 0.43223401 | 0.10185882E-05 | 0.49492235 | -0.50646574E-02 |
28 | 5 | -5.4528708 | 0.37659386E-04 | -4.6163278 | 0.66436381E-01 |
29 | 4 | 34.162830 | 0.30532126E-03 | 22.123982 | -0.43752457 |
30 | 3 | -113.69342 | 0.66011806E-03 | -56.975280 | 1.5508408 |
31 | 2 | 199.57555 | 0.36866733E-03 | 79.115267 | -2.9395356 |
32 | 1 | -172.06709 | 0.39096546E-04 | -55.617513 | 2.7614060 |
33 | 0 | 57.057407 | 0.22087022E-06 | 15.500460 | |
34 | 7 | -0.25528060E-08 | -0.12031403E-14 | 0.68407999E-14 | -0.93970880E-16 |
35 | 6 | 0.47134542E-05 | 0.31734324E-08 | 0.31924928E-02 | -0.26781305E-04 |
36 | 5 | -0.33464294E-03 | 0.18778732E-05 | -0.22387365 | 0.19574661E-02 |
37 | 4 | 0.76699050E-02 | 0.85441795E-04 | 4.8320287 | -0.45288849E-01 |
38 | 3 | -0.67267585E-01 | 0.67916014E-03 | -38.035443 | 0.39880879 |
39 | 2 | 0.23873650 | 0.11294419E-02 | 116.51125 | -1.4183045 |
40 | 1 | -0.34450630 | 0.34392527E-03 | -143.92338 | 2.0493041 |
41 | 0 | 0.16794560 | 0.83374149E-05 | 60.838472 | |
42 | 7 | -0.12973758E-07 | 0.34411372E-14 | -0.15771944E-13 | 0.23851239E-15 |
43 | 6 | 0.18530215E-05 | 0.67214774E-09 | 0.32028229E-02 | -0.26867962E-04 |
44 | 5 | -0.88022991E-04 | 0.38590341E-06 | -0.22446025 | 0.19626440E-02 |
45 | 4 | 0.17210852E-02 | 0.17282655E-04 | 4.8417890 | -0.45382682E-01 |
46 | 3 | -0.14132592E-01 | 0.13559951E-03 | -38.090529 | 0.39941776 |
47 | 2 | 0.48779578E-01 | 0.22269637E-03 | 116.61840 | -1.4197378 |
48 | 1 | -0.69488798E-01 | 0.66762873E-04 | -143.98642 | 2.0503404 |
49 | 0 | 0.33651223E-01 | 0.15845250E-05 | 60.838472 | |
50 | 7 | -0.22078744E-08 | -0.78010070E-15 | 0.51210754E-14 | -0.71692469E-16 |
51 | 6 | 0.53924046E-05 | 0.36628569E-08 | 0.31905048E-02 | -0.26764628E-04 |
52 | 5 | -0.38538745E-03 | 0.21680609E-05 | -0.22376067 | 0.19564689E-02 |
53 | 4 | 0.88497020E-02 | 0.98671011E-04 | 4.8301469 | -0.45270761E-01 |
54 | 3 | -0.77667315E-01 | 0.78446833E-03 | -38.024813 | 0.39869130 |
55 | 2 | 0.27571886 | 0.13048573E-02 | 116.49056 | -1.4180278 |
56 | 1 | -0.39792016 | 0.39739385E-03 | -143.91120 | 2.0491039 |
57 | 0 | 0.19399612 | 0.96507839E-05 | 60.838472 | |
58 | 7 | -0.22078744E-08 | -0.78010070E-15 | 0.51210754E-14 | -0.71692469E-16 |
59 | 6 | 0.53924046E-05 | 0.36628569E-08 | 0.31905048E-02 | -0.26764628E-04 |
60 | 5 | -0.38538745E-03 | 0.21680609E-05 | -0.22376067 | 0.19564689E-02 |
61 | 4 | 0.88497020E-02 | 0.98671011E-04 | 4.8301469 | -0.45270761E-01 |
62 | 3 | -0.77667315E-01 | 0.78446833E-03 | -38.024813 | 0.39869130 |
63 | 2 | 0.27571886 | 0.13048573E-02 | 116.49056 | -1.4180278 |
64 | 1 | -0.39792016 | 0.39739385E-03 | -143.91120 | 2.0491039 |
65 | 0 | 0.19399612 | 0.96507839E-05 | 60.838472 | |
66 | 7 | -0.13255510E-08 | -0.17188199E-15 | 0.92128295E-14 | -0.12705258E-15 |
67 | 6 | 0.87884716E-05 | 0.60547316E-08 | 0.31807701E-02 | -0.26682965E-04 |
68 | 5 | -0.63593173E-03 | 0.35898785E-05 | -0.22320731 | 0.19515846E-02 |
69 | 4 | 0.14651324E-01 | 0.16347926E-03 | 4.8209294 | -0.45182156E-01 |
70 | 3 | -0.12872491 | 0.13006479E-02 | -37.972737 | 0.39811570 |
71 | 2 | 0.45715725 | 0.21644648E-02 | 116.38920 | -1.4166720 |
72 | 1 | -0.65988557 | 0.65992538E-03 | -143.85153 | 2.0481231 |
73 | 0 | 0.32173707 | 0.15909640E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.41_SHGC_0.45 | 30 | 1 | VerySmooth | 2.330 | 0.445 | 0.367 | 0.451 |
2 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 31 | 1 | VerySmooth | 5.779 | 0.680 | 0.573 | 0.680 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.14065E-002 | 0.36619 | 0.42864 | 0.42864 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12199 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.57291 | 6.11155E-002 | 6.11155E-002 | 0.68000 | 0.13462 | 0.14960 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.727 | 0.1878 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
31 | SKYLIGHTS_R2C4 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
32 | SKYLIGHTS_R2C1 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
33 | SKYLIGHTS_R2C2 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
34 | SKYLIGHTS_R2C3 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C3 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C1 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C2 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
39 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
40 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
42 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
43 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
44 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
45 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
46 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
47 | POINT_OF_SALE_ROOF | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
48 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
49 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
50 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
52 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
54 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | FRONT_RETAIL_ROOF | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
58 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
59 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
60 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
62 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
63 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
64 | FRONT_ENTRY_ROOF | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
65 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.448 | 1.180E-003 | 5.356E-004 | 0.697 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.367 | 2.293E-004 | 1.864E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 2.497E-002 | 2.080E-003 | 6.862E-004 | 1.228 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 20077.15321 | 24092.58385 | 1.47625 | 1.77150 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27032E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 31429.52760 | 37715.43311 | 1.38859 | 1.66631 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 90715.29508 | 108858.35409 | 6.68511 | 8.02213 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27032E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 77256.05000 | 92707.26000 | 3.37433 | 4.04919 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 13594.90599 | 16313.88719 | 1.04106 | 1.24927 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27032E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 15327.73742 | 18393.28490 | 0.67899 | 0.81479 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 10990.83208 | 13188.99849 | 0.84165 | 1.00998 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27032E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 15327.09698 | 18392.51637 | 0.67896 | 0.81475 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10000 | 1.27032E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 72874.51922 | 87449.42307 | 3.25899 | 3.91079 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | -32.70000 | 1.83376E-004 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 23540.70 | 1.81290 | 1.81290 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 51224.19 | 1.66631 | 1.66631 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 113907.70 | 8.22291 | 8.22291 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 207189.30 | 4.04919 | 4.04919 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 17288.62 | 1.24927 | 1.24927 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 29087.51 | 0.81479 | 0.81479 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 14224.00 | 1.00998 | 1.00998 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 29086.75 | 0.81475 | 0.81475 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.77150 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 8.02213 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24927 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00998 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.91079 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 3.91079 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 87550.47779 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.77150 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.77150 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.77150 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.77150 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.81290 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.81290 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.97716 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.02213 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 8.02213 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.02213 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 8.02213 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.22291 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 8.22291 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97558 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24927 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24927 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24927 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24927 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.24927 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.24927 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00998 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00998 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00998 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00998 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00998 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00998 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.81290 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 8.22291 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.24927 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.00998 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.81290 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.81290 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.81290 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.81290 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.81290 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.81290 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.90645 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.81290 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 31855.86238 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 34171.62000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 17085.81000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 34171.62000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75388 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75388 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75388 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75388 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34171.62000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 53548.48378 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.81290 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1984.23018 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 53548.48378 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.22291 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.22291 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.22291 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.22291 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 8.22291 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 8.22291 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.11146 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 8.22291 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 155117.74564 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 165446.60000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 82723.30000 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 165446.60000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73348 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73348 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73348 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73348 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 165446.60000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 295239.35399 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 8.22291 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 14157.73148 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 295239.35399 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.24927 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.24927 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.24927 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.24927 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.24927 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.24927 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62464 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.24927 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21007.79362 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22617.78000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11308.89000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22617.78000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76715 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76716 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76716 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76716 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22617.78000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 38691.39375 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.24927 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1424.31011 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 38691.39375 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00998 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00998 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00998 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00998 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00998 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00998 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50499 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.00998 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17766.06537 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19055.17000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9527.58500 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 19055.17000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75358 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75358 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75358 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75358 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19055.17000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33402.06320 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00998 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1151.49041 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 33402.06320 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 32748.2 | 10.23 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 158983.8 | 11.62 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 21637.5 | 100.28 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 18262.2 | 129.78 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 25 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.166 | 0.159 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 3.309E-002 | 3.283E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1591.92 | 1600.48 | 1593.79 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
32 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
33 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
34 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
40 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.41_SHGC_0.45 | N/A | 2.330 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.191 | 0.183 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.41_SHGC_0.45 | N/A | 2.330 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.191 | 0.183 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
56 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
57 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
58 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.41_SHGC_0.45 | N/A | 2.330 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.315 | 0.292 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | |
1 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C4 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
2 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C1 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
3 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C2 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
4 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C3 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
5 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C3 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
6 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C1 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
7 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C4 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
8 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C2 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 7 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 0.3613184014 | 0.5962829651 | Pass | Pass | 0.3224260102 | 0.5554245143 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 0.1289522225 | 0.3132853473 | Pass | Pass | 0.9017301848 | 4.6704442480 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 0.3473286227 | 0.6698716216 | Pass | Pass | 0.3607179966 | 0.4610402356 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 0.3687457881 | 0.6628063038 | Pass | Pass | 0.3433070209 | 0.5241272994 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.2026569986 | 0.5028809443 | Pass | Pass | 0.1475055817 | 0.5656795673 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 1600.48 | 1591.92 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.166 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.033 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.191 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.191 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.315 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.41_SHGC_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.330 | 0.445 | 0.451 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.41_SHGC_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.330 | 0.445 | 0.451 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.41_SHGC_0.45 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.330 | 0.445 | 0.451 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 92.49 | 2.649 | 0.467 | 0.472 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 92.49 | 2.649 | 0.467 | 0.472 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 9.0309 | 379.89 | 3430.76 | LightsWired | BLDG_LIGHT_BACK_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 43.96 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 18.2986 | 1600.48 | 29286.67 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 375.23 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 18.2986 | 150.81 | 2759.62 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 35.36 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 18.2986 | 150.81 | 2759.62 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 35.36 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 13.9931 | 12.00 | 167.92 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 2.15 |
Interior Lighting Total | 16.7414 | 2293.99 | 38404.58 | 492.05 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7321.52 | AstronomicalClock | - | 83.52 | 83.52 | 114.78 | |
Exterior Lighting Total | 7321.52 | 114.78 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 34171.62 | 25761.30 | 8410.32 | 0.75 | 3.50 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 165446.60 | 121351.77 | 44094.83 | 0.73 | 3.23 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22617.78 | 17351.46 | 5266.32 | 0.77 | 3.50 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 19055.17 | 14359.60 | 4695.57 | 0.75 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 32748.2 | 10.23 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 158983.8 | 11.62 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 21637.5 | 100.28 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 18262.2 | 129.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 87550.48 | 0.79 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 53548.48 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 295239.35 | 0.79 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 38691.39 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 33402.06 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.58 | 1018.41 | 3.91 | 6846.22 | 1750.60 | 1.00 | 1.14 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.81 | 1984.23 | 1094.51 | 1.00 | 1.30 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.59 | 1018.41 | 8.22 | 14157.73 | 1721.74 | 1.00 | 1.13 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.25 | 1424.31 | 1140.11 | 1.00 | 1.31 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.01 | 1151.49 | 1140.11 | 1.00 | 1.36 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 20077.15 | 24092.58 | 63.42 | 1.476 | 1.771 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01000 | 20.92 | 0.01270 | 0.232 | 0.00 |
CORE_RETAIL | 90715.30 | 108858.35 | 68.02 | 6.685 | 8.022 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00964 | 20.92 | 0.01270 | 1.890 | 0.00 |
POINT_OF_SALE | 13594.91 | 16313.89 | 108.18 | 1.041 | 1.249 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00895 | 29.79 | 0.01270 | 0.178 | 0.00 |
FRONT_RETAIL | 10990.83 | 13189.00 | 87.45 | 0.842 | 1.010 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00906 | 29.79 | 0.01270 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.12 | 100.00 | 0.00001 | 30.10 | 0.01270 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 31429.53 | 37715.43 | 99.28 | 1.389 | 1.666 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00781 | -32.70 | 0.00018 | 0.232 | 0.00 |
CORE_RETAIL | 77256.05 | 92707.26 | 57.92 | 3.374 | 4.049 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00781 | -32.70 | 0.00018 | 1.890 | 0.00 |
POINT_OF_SALE | 15327.74 | 18393.28 | 121.96 | 0.679 | 0.815 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00786 | -32.70 | 0.00018 | 0.178 | 0.00 |
FRONT_RETAIL | 15327.10 | 18392.52 | 121.96 | 0.679 | 0.815 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00786 | -32.70 | 0.00018 | 0.178 | 0.00 |
FRONT_ENTRY | 72874.52 | 87449.42 | 7287.45 | 3.259 | 3.911 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 21.11 | 20.97 | 0.00597 | -32.70 | 0.00018 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.81 | 1.81 | 1.67 | 1.67 | 1.8129 | 1.7715 | 1.8129 | 0.9772 | 1.0000 |
PSZ-AC:2 | 8.22 | 8.22 | 4.05 | 4.05 | 8.2229 | 8.0221 | 8.2229 | 0.9756 | 1.0000 |
PSZ-AC:3 | 1.25 | 1.25 | 0.81 | 0.81 | 1.2493 | 1.2493 | 1.2493 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.01 | 1.01 | 0.81 | 0.81 | 1.0100 | 1.0100 | 1.0100 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 87550.478 | 87550.478 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 87550.48 | 87550.48 | 3.910792 | 20.78 | 12.41 | 0.00594714 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 20.97 | 0.00596810 | 37.1502 | 87449.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 34171.620 | 0.000 | 1.812900 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 34171.62 | 27748.82 | 1.812900 | 24.73 | 17.25 | 0.00977793 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 12.7733 | 23.88 | 0.00999663 | 51.8035 | 20077.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 53548.484 | 53548.484 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 53548.48 | 53548.48 | 1.812901 | 13.49 | 10.22 | 0.00675271 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 12.7733 | 21.11 | 0.00781299 | 48.0919 | 31429.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 165446.600 | 0.000 | 8.222910 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 165446.60 | 130625.75 | 8.222910 | 25.39 | 17.68 | 0.01004150 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 22.9871 | 23.89 | 0.00963938 | 49.9781 | 84889.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 295239.354 | 295239.354 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 295239.35 | 295239.35 | 8.222914 | -4.13 | -4.13 | 0.00424753 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 22.9871 | 21.11 | 0.00780574 | 48.0470 | 77256.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 22617.780 | 0.000 | 1.249270 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 22617.78 | 19191.91 | 1.249270 | 24.74 | 17.02 | 0.00948637 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01270324 | 21.04 | 14.2572 | 23.89 | 0.00895055 | 46.4502 | 13583.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 38691.394 | 38691.394 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38691.39 | 38691.39 | 1.249274 | 9.21 | 7.69 | 0.00618356 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 14.2571 | 21.11 | 0.00786211 | 48.3900 | 15327.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 19055.170 | 0.000 | 1.009980 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 19055.17 | 15697.30 | 1.009980 | 24.97 | 17.26 | 0.00970087 | 12.80 | 11.72 | 0.00850000 | 30.00 | 0.01270324 | 21.07 | 17.6351 | 23.89 | 0.00905594 | 46.9893 | 10971.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 33402.063 | 33402.063 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33402.06 | 33402.06 | 1.009982 | 9.21 | 7.69 | 0.00618348 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 17.6350 | 21.11 | 0.00786210 | 48.3900 | 15327.10 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 87550.478 | 87550.478 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 3.910792 | 4.51276016 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 87550.48 | 87550.48 | 1.0000 | 4.51276016 | 3.910792 | 20.78 | 12.41 | 0.00594714 | 35983.6 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87550.48 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00596810 | 20.97 | 0.00596810 | 37.1502 | 87449.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34171.620 | 0.000 | 1.812900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0167 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 34171.62 | 27748.82 | 1.0000 | 2.09195037 | 1.812900 | 24.73 | 17.25 | 0.00977793 | 49756.6 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34171.62 | 30.10 | 0.01270324 | 21.10 | 0.23156651 | 12.7733 | 23.89 | 0.00931702 | 23.88 | 0.00999663 | 51.8035 | 20077.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 53548.484 | 53548.484 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.812901 | 2.09195161 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 53548.48 | 53548.48 | 1.0000 | 2.09195161 | 1.812901 | 13.49 | 10.22 | 0.00675271 | 30611.1 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53548.48 | -32.70 | 0.00018338 | -32.70 | 0.23156651 | 12.7733 | 20.94 | 0.00781299 | 21.11 | 0.00781299 | 48.0919 | 31429.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 165446.600 | 0.000 | 8.222910 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5067 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 165446.60 | 130625.75 | 1.0000 | 9.48862024 | 8.222910 | 25.39 | 17.68 | 0.01004150 | 51103.2 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 165446.60 | 30.10 | 0.01270324 | 21.10 | 1.89021192 | 22.9871 | 23.89 | 0.00919027 | 23.89 | 0.00963938 | 49.9781 | 84889.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 295239.354 | 295239.354 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.222914 | 9.48862523 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 295239.35 | 295239.35 | 1.0000 | 9.48862523 | 8.222914 | -4.13 | -4.13 | 0.00424753 | 6442.0 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 295239.35 | -32.70 | 0.00018338 | -32.70 | 1.89021192 | 22.9871 | 20.89 | 0.00780574 | 21.11 | 0.00780574 | 48.0470 | 77256.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22617.780 | 0.000 | 1.249270 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.4747 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 22617.78 | 19191.91 | 1.0000 | 1.44156371 | 1.249270 | 24.74 | 17.02 | 0.00948637 | 49025.8 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22617.78 | 29.89 | 0.01270324 | 21.04 | 0.17811053 | 14.2572 | 23.89 | 0.00895096 | 23.89 | 0.00895055 | 46.4502 | 13583.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38691.394 | 38691.394 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.249274 | 1.44156880 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38691.39 | 38691.39 | 1.0000 | 1.44156880 | 1.249274 | 9.21 | 7.69 | 0.00618356 | 24827.4 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38691.39 | -32.70 | 0.00018338 | -32.70 | 0.17811053 | 14.2571 | 20.94 | 0.00786211 | 21.11 | 0.00786211 | 48.3900 | 15327.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19055.170 | 0.000 | 1.009980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8734 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 19055.17 | 15697.30 | 1.0000 | 1.16544103 | 1.009980 | 24.97 | 17.26 | 0.00970087 | 49799.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19055.17 | 30.00 | 0.01270324 | 21.07 | 0.17811053 | 17.6351 | 23.89 | 0.00905667 | 23.89 | 0.00905594 | 46.9893 | 10971.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33402.063 | 33402.063 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.009982 | 1.16544328 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33402.06 | 33402.06 | 1.0000 | 1.16544328 | 1.009982 | 9.21 | 7.69 | 0.00618348 | 24826.7 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33402.06 | -32.70 | 0.00018338 | -32.70 | 0.17811053 | 17.6350 | 20.94 | 0.00786210 | 21.11 | 0.00786210 | 48.3900 | 15327.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 1.89 | 8.22 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 3024.17 | 3652.50 | 2362.17 |
CORE_RETAIL | 2993.67 | 3127.17 | 1801.33 |
POINT_OF_SALE | 2984.00 | 3007.17 | 1657.83 |
FRONT_RETAIL | 3085.00 | 3331.17 | 1976.17 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3728.50 | 3699.00 | 2401.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 141.33 | 1.00 | 0.00 | 0.00 |
CORE_RETAIL | 1.50 | 22.33 | 0.00 | 0.00 |
POINT_OF_SALE | 104.00 | 25.17 | 0.00 | 0.00 |
FRONT_RETAIL | 132.00 | 2.67 | 0.00 | 0.00 |
FRONT_ENTRY | 0.50 | 0.00 | 0.00 | 0.00 |
Facility | 231.83 | 48.33 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.47 | 61.34 | 2317.33 | 0.365 | 0.054 | 0.000 | 0.000 |
CORE_RETAIL | 128.37 | 258.43 | 9762.95 | 0.745 | 0.011 | 0.000 | 0.000 |
POINT_OF_SALE | 12.10 | 24.35 | 919.94 | 0.707 | 0.059 | 0.000 | 0.000 |
FRONT_RETAIL | 12.10 | 24.35 | 919.94 | 0.707 | 0.059 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.47 | 61.34 | 2317.33 | 0.352 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.37 | 258.43 | 9762.95 | 0.682 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.10 | 24.35 | 919.94 | 0.682 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.10 | 24.35 | 919.94 | 0.682 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 11 | 11 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1380.61 | 3715.40 | 26-MAR-18:10 | 121656.31 | 29-JUN-16:00 |
Electricity:Building | 687.20 | 3715.40 | 01-JAN-00:10 | 45335.16 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 93.95 | 631.39 | 01-JAN-00:10 | 5846.82 | 02-JAN-09:10 |
InteriorLights:Electricity | 492.05 | 1920.23 | 01-JAN-00:10 | 34564.13 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 43.96 | 171.54 | 01-JAN-00:10 | 3087.68 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 492.05 | 1920.23 | 01-JAN-00:10 | 34564.13 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 459.53 | 2239.77 | 01-JAN-00:10 | 31010.61 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 375.23 | 1464.33 | 01-JAN-00:10 | 26358.01 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 88.28 | 624.80 | 01-JAN-00:10 | 5404.55 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 35.36 | 137.98 | 01-JAN-00:10 | 2483.66 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 43.30 | 211.05 | 01-JAN-00:10 | 2922.06 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 35.36 | 137.98 | 01-JAN-00:10 | 2483.66 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 2.15 | 8.40 | 01-JAN-00:10 | 151.13 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 2.15 | 8.40 | 01-JAN-00:10 | 151.13 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1380.61 | 3715.40 | 26-MAR-18:10 | 121656.31 | 29-JUN-16:00 |
ElectricityPurchased:Plant | 1380.61 | 3715.40 | 26-MAR-18:10 | 121656.31 | 29-JUN-16:00 |
Cogeneration:ElectricityPurchased | 1380.61 | 3715.40 | 26-MAR-18:10 | 121656.31 | 29-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1380.61 | 3715.40 | 26-MAR-18:10 | 121656.31 | 29-JUN-16:00 |
ElectricityNet:Plant | 1380.61 | 3715.40 | 26-MAR-18:10 | 121656.31 | 29-JUN-16:00 |
Cogeneration:ElectricityNet | 1380.61 | 3715.40 | 26-MAR-18:10 | 121656.31 | 29-JUN-16:00 |
Electricity:HVAC | 578.63 | 0.00 | 02-JAN-21:10 | 76321.14 | 29-JUN-16:00 |
Fans:Electricity | 443.49 | 0.00 | 02-JAN-21:10 | 25563.98 | 15-JAN-08:10 |
General:Fans:Electricity | 443.49 | 0.00 | 02-JAN-21:10 | 25563.98 | 15-JAN-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 135.14 | 0.00 | 01-JAN-00:10 | 57603.38 | 29-JUN-16:00 |
ExteriorLights:Electricity | 114.78 | 0.00 | 01-JAN-08:20 | 7321.52 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 114.78 | 0.00 | 01-JAN-08:20 | 7321.52 | 01-JAN-00:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1105.15 | 1862.00 | 05-JAN-21:10 | 329749.88 | 09-JAN-07:10 |
Gas:Plant | 102.74 | 1862.00 | 02-JAN-05:20 | 6513.32 | 24-FEB-13:00 |
WaterSystems:Gas | 102.74 | 1862.00 | 02-JAN-05:20 | 6513.32 | 24-FEB-13:00 |
Water Heater:WaterSystems:Gas | 102.74 | 1862.00 | 02-JAN-05:20 | 6513.32 | 24-FEB-13:00 |
Gas:HVAC | 1002.42 | 0.00 | 01-JAN-00:40 | 327590.78 | 09-JAN-07:10 |
Heating:Gas | 1002.42 | 0.00 | 01-JAN-00:40 | 327590.78 | 09-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2066.44 | 0.00 | 02-JAN-21:10 | 387493.61 | 09-JAN-07:10 |
EnergyTransfer:Building | 820.90 | 0.00 | 02-JAN-21:10 | 167161.21 | 26-DEC-05:10 |
EnergyTransfer:Zone:BACK_SPACE | 128.79 | 0.00 | 01-JAN-00:40 | 47017.89 | 27-DEC-05:20 |
Heating:EnergyTransfer | 383.44 | 0.00 | 02-JAN-21:10 | 167161.21 | 26-DEC-05:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 89.26 | 0.00 | 01-JAN-00:40 | 47017.89 | 27-DEC-05:20 |
Cooling:EnergyTransfer | 437.45 | 0.00 | 01-JAN-00:10 | 83677.00 | 30-JUN-14:50 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 39.53 | 0.00 | 01-JAN-00:10 | 12680.74 | 30-JUN-15:00 |
EnergyTransfer:Zone:CORE_RETAIL | 382.44 | 0.00 | 01-JAN-00:10 | 98800.51 | 01-JAN-08:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 70.49 | 0.00 | 01-JAN-00:10 | 98800.51 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 311.95 | 0.00 | 01-JAN-00:10 | 53342.55 | 30-JUN-14:50 |
EnergyTransfer:Zone:POINT_OF_SALE | 75.51 | 0.00 | 01-JAN-00:40 | 24543.89 | 16-DEC-05:20 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 21.54 | 0.00 | 01-JAN-00:40 | 24543.89 | 16-DEC-05:20 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 53.97 | 0.00 | 01-JAN-00:10 | 11436.63 | 01-SEP-13:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 64.16 | 0.00 | 01-JAN-00:40 | 24270.23 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 32.16 | 0.00 | 01-JAN-00:40 | 24270.23 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 32.00 | 0.00 | 01-JAN-00:10 | 9425.31 | 01-SEP-14:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 170.00 | 0.00 | 02-JAN-21:10 | 66118.90 | 05-JAN-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 170.00 | 0.00 | 02-JAN-21:10 | 66118.90 | 05-JAN-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1245.55 | 0.00 | 01-JAN-00:40 | 260346.62 | 09-JAN-07:10 |
HeatingCoils:EnergyTransfer | 797.03 | 0.00 | 01-JAN-00:40 | 260346.62 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 448.52 | 0.00 | 01-JAN-00:10 | 185446.75 | 30-JUN-15:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 89.256 | -39.532 | 0.000 | 0.000 | 40.108 | 43.956 | 49.992 | 0.000 | 0.000 | 0.175 | 0.001 | 0.000 | 0.000 | 0.000 | -42.675 | -141.280 |
CORE_RETAIL | 0.000 | 0.000 | 70.493 | -311.946 | 0.000 | 0.000 | 168.085 | 375.227 | 84.299 | 13.684 | 0.000 | 0.143 | 0.006 | 0.000 | -15.796 | 0.000 | -37.006 | -347.183 |
POINT_OF_SALE | 0.000 | 0.000 | 21.536 | -53.972 | 0.000 | 0.000 | 15.670 | 35.357 | 52.922 | 38.234 | 0.000 | 0.076 | 0.001 | 0.000 | -29.536 | 0.000 | -19.009 | -61.278 |
FRONT_RETAIL | 0.000 | 0.000 | 32.165 | -31.999 | 0.000 | 0.000 | 15.902 | 35.357 | 7.943 | 38.292 | 0.000 | 0.076 | 0.000 | 0.000 | -29.102 | 0.000 | -18.642 | -49.992 |
FRONT_ENTRY | 169.995 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.151 | 0.000 | 7.691 | 0.000 | 0.031 | 0.000 | 0.000 | -6.074 | 0.000 | -169.102 | -4.693 |
Total Facility | 169.995 | 0.000 | 213.450 | -437.450 | 0.000 | 0.000 | 239.765 | 492.048 | 195.156 | 97.901 | 0.000 | 0.501 | 0.008 | 0.000 | -80.507 | 0.000 | -286.434 | -604.427 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 13-AUG-18:40 | 0.00 | 0.00 | 0.00 | -14977.80 | 0.00 | 0.00 | 0.00 | 171.54 | 459.86 | 0.00 | 0.00 | 0.00 | 14633.17 | 0.00 | -0.00 | 0.00 | -286.76 | 0.00 |
CORE_RETAIL | 25-AUG-05:01 | 0.00 | 0.00 | 0.00 | -113435.38 | 0.00 | 0.00 | 0.00 | 1464.33 | 1033.91 | 0.00 | 0.00 | 0.00 | 111612.83 | 0.00 | -675.69 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 08-AUG-20:43 | 0.00 | 0.00 | 0.00 | -15048.77 | 0.00 | 0.00 | 0.00 | 551.92 | 649.09 | 0.00 | 0.00 | 0.00 | 14195.40 | 0.00 | -311.09 | 0.00 | -36.54 | 0.00 |
FRONT_RETAIL | 23-JUL-18:43 | 0.00 | 0.00 | 0.00 | -12132.46 | 0.00 | 0.00 | 0.00 | 137.98 | 73.07 | 452.18 | 0.00 | 180.79 | 11288.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-AUG-05:01 | 0.00 | 0.00 | 0.00 | -127437.12 | 0.00 | 0.00 | 0.00 | 1920.23 | 2393.56 | 0.00 | 0.00 | 0.00 | 126670.56 | 0.00 | -3547.23 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 31-OCT-04:01 | 0.00 | 0.00 | 52115.72 | 0.00 | 0.00 | 0.00 | 0.00 | 171.54 | 613.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3304.95 | -49595.45 |
CORE_RETAIL | 25-DEC-07:01 | 0.00 | 0.00 | 302001.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.33 | 775.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1561.23 | 0.00 | -5654.14 | -297025.56 |
POINT_OF_SALE | 31-OCT-04:01 | 0.00 | 0.00 | 36765.65 | 0.00 | 0.00 | 0.00 | 0.00 | 137.98 | 649.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -694.28 | 0.00 | -1619.71 | -35238.72 |
FRONT_RETAIL | 01-NOV-04:01 | 0.00 | 0.00 | 31842.84 | 0.00 | 0.00 | 0.00 | 0.00 | 137.98 | 97.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -685.80 | 0.00 | -443.11 | -30949.33 |
FRONT_ENTRY | 05-JAN-18:00 | 66118.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.13 | 0.00 | 0.00 | 0.00 | 0.00 | 74.67 | 0.00 | -725.38 | 0.00 | -65619.28 | 0.00 |
Total Facility | 03-JAN-05:01 | 5540.20 | 0.00 | 410951.83 | 0.00 | 0.00 | 0.00 | 0.00 | 1920.23 | 2393.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5128.66 | 0.00 | -16035.27 | -399641.90 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.7715 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.8129 | 0.1277 | 1.0000 | 0.2316 | 0.1277 | ||
PSZ-AC:2 | 8.0221 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.2229 | 0.2299 | 1.0000 | 1.8902 | 0.2299 | ||
PSZ-AC:3 | 1.2493 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.2493 | 0.1426 | 1.0000 | 0.1781 | 0.1426 | ||
PSZ-AC:4 | 1.0100 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0100 | 0.1764 | 1.0000 | 0.1781 | 0.1764 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.7715 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.7715 | 1.0000 | 1.0000 | 0.2316 | 0.1307 | ||
PSZ-AC:2 | 8.0221 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.0221 | 1.0000 | 1.0000 | 1.8902 | 0.2356 | ||
PSZ-AC:3 | 1.2493 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.2493 | 1.0000 | 1.0000 | 0.1781 | 0.1426 | ||
PSZ-AC:4 | 1.0100 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0100 | 1.0000 | 1.0000 | 0.1781 | 0.1764 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.7715 | 1.7715 | 1.7715 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.0221 | 8.0221 | 8.0221 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.2493 | 1.2493 | 1.2493 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0100 | 1.0100 | 1.0100 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.7715 | 1.8129 | 1.7715 | 1.7715 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.0221 | 8.2229 | 8.0221 | 8.0221 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.2493 | 1.2493 | 1.2493 | 1.2493 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0100 | 1.0100 | 1.0100 | 1.0100 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.7715 | 1.7715 | 1.7715 | 0.2316 | 0.1390 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.0221 | 8.0221 | 8.0221 | 1.8902 | 0.4668 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.2493 | 1.2493 | 1.2493 | 0.1781 | 0.2186 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0100 | 1.0100 | 1.0100 | 0.1781 | 0.2186 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.7715 | 1.7715 | 1.7715 | 1.7715 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.0221 | 8.0221 | 8.0221 | 8.0221 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.2493 | 1.2493 | 1.2493 | 1.2493 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0100 | 1.0100 | 1.0100 | 1.0100 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1002.42 | 327590.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 135.14 | 57603.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 492.05 | 34564.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 114.78 | 7321.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 443.49 | 25563.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 102.74 | 6513.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1380.61 |
Natural Gas | 0.00 | 1105.15 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 2485.77 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 214.49 |
Space Heating | 0.00 |
Space Cooling | 58.91 |
Fans (All) | 193.33 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 601.84 |
Subtotal | 601.84 |
Natural Gas [MJ/m2] | |
Space Heating | 436.97 |
Service Water Heating | 44.78 |
Miscellaneous (All) | 481.76 |
Subtotal | 481.76 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.79 |
Space Heating | 40.33 |
Space Cooling | 5.44 |
Fans (All) | 17.84 |
Service Water Heating | 4.13 |
Receptacle Equipment | 7.85 |
Miscellaneous | 4.62 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3609. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_SETBACK | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_SCH_PSZ_AC_2 | CORE_RETAIL DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.271776E+12 |
February | 0.000 | 0.179648E+12 |
March | 0.000 | 0.136349E+12 |
April | 0.000 | 0.404562E+11 |
May | 0.000 | 0.305641E+10 |
June | 0.000 | 0.865193E+08 |
July | 0.000 | 0.215288E+08 |
August | 0.000 | 0.103478E+09 |
September | 0.000 | 0.116523E+10 |
October | 0.000 | 0.235751E+11 |
November | 0.000 | 0.981403E+11 |
December | 0.000 | 0.248040E+12 |
Annual Sum or Average | 0.100242E+13 | |
Minimum of Months | 0.000 | 0.215288E+08 |
Maximum of Months | 0.000 | 0.271776E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.271776E+12 |
February | 0.000 | 0.179648E+12 |
March | 0.000 | 0.136349E+12 |
April | 0.000 | 0.404562E+11 |
May | 0.000 | 0.305641E+10 |
June | 0.000 | 0.865193E+08 |
July | 0.000 | 0.215288E+08 |
August | 0.000 | 0.103478E+09 |
September | 0.000 | 0.116523E+10 |
October | 0.000 | 0.235751E+11 |
November | 0.000 | 0.981403E+11 |
December | 0.000 | 0.248040E+12 |
Annual Sum or Average | 0.100242E+13 | |
Minimum of Months | 0.000 | 0.215288E+08 |
Maximum of Months | 0.000 | 0.271776E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.271776E+12 |
February | 0.000 | 0.179648E+12 |
March | 0.000 | 0.136349E+12 |
April | 0.000 | 0.404562E+11 |
May | 0.000 | 0.305641E+10 |
June | 0.000 | 0.865193E+08 |
July | 0.000 | 0.215288E+08 |
August | 0.000 | 0.103478E+09 |
September | 0.000 | 0.116523E+10 |
October | 0.000 | 0.235751E+11 |
November | 0.000 | 0.981403E+11 |
December | 0.000 | 0.248040E+12 |
Annual Sum or Average | 0.100242E+13 | |
Minimum of Months | 0.000 | 0.215288E+08 |
Maximum of Months | 0.000 | 0.271776E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.271776E+12 |
February | 0.000 | 0.179648E+12 |
March | 0.000 | 0.136349E+12 |
April | 0.000 | 0.404562E+11 |
May | 0.000 | 0.305641E+10 |
June | 0.000 | 0.865193E+08 |
July | 0.000 | 0.215288E+08 |
August | 0.000 | 0.103478E+09 |
September | 0.000 | 0.116523E+10 |
October | 0.000 | 0.235751E+11 |
November | 0.000 | 0.981403E+11 |
December | 0.000 | 0.248040E+12 |
Annual Sum or Average | 0.100242E+13 | |
Minimum of Months | 0.000 | 0.215288E+08 |
Maximum of Months | 0.000 | 0.271776E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.271776E+12 |
February | 0.000 | 0.179648E+12 |
March | 0.000 | 0.136349E+12 |
April | 0.000 | 0.404562E+11 |
May | 0.000 | 0.305641E+10 |
June | 0.000 | 0.865193E+08 |
July | 0.000 | 0.215288E+08 |
August | 0.000 | 0.103478E+09 |
September | 0.000 | 0.116523E+10 |
October | 0.000 | 0.235751E+11 |
November | 0.000 | 0.981403E+11 |
December | 0.000 | 0.248040E+12 |
Annual Sum or Average | 0.100242E+13 | |
Minimum of Months | 0.000 | 0.215288E+08 |
Maximum of Months | 0.000 | 0.271776E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.271776E+12 |
February | 0.000 | 0.179648E+12 |
March | 0.000 | 0.136349E+12 |
April | 0.000 | 0.404562E+11 |
May | 0.000 | 0.305641E+10 |
June | 0.000 | 0.865193E+08 |
July | 0.000 | 0.215288E+08 |
August | 0.000 | 0.103478E+09 |
September | 0.000 | 0.116523E+10 |
October | 0.000 | 0.235751E+11 |
November | 0.000 | 0.981403E+11 |
December | 0.000 | 0.248040E+12 |
Annual Sum or Average | 0.100242E+13 | |
Minimum of Months | 0.000 | 0.215288E+08 |
Maximum of Months | 0.000 | 0.271776E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.271776E+12 |
February | 0.000 | 0.179648E+12 |
March | 0.000 | 0.136349E+12 |
April | 0.000 | 0.404562E+11 |
May | 0.000 | 0.305641E+10 |
June | 0.000 | 0.865193E+08 |
July | 0.000 | 0.215288E+08 |
August | 0.000 | 0.103478E+09 |
September | 0.000 | 0.116523E+10 |
October | 0.000 | 0.235751E+11 |
November | 0.000 | 0.981403E+11 |
December | 0.000 | 0.248040E+12 |
Annual Sum or Average | 0.100242E+13 | |
Minimum of Months | 0.000 | 0.215288E+08 |
Maximum of Months | 0.000 | 0.271776E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.271776E+12 |
February | 0.000 | 0.179648E+12 |
March | 0.000 | 0.136349E+12 |
April | 0.000 | 0.404562E+11 |
May | 0.000 | 0.305641E+10 |
June | 0.000 | 0.865193E+08 |
July | 0.000 | 0.215288E+08 |
August | 0.000 | 0.103478E+09 |
September | 0.000 | 0.116523E+10 |
October | 0.000 | 0.235751E+11 |
November | 0.000 | 0.981403E+11 |
December | 0.000 | 0.248040E+12 |
Annual Sum or Average | 0.100242E+13 | |
Minimum of Months | 0.000 | 0.215288E+08 |
Maximum of Months | 0.000 | 0.271776E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.271776E+12 |
February | 0.000 | 0.179648E+12 |
March | 0.000 | 0.136349E+12 |
April | 0.000 | 0.404562E+11 |
May | 0.000 | 0.305641E+10 |
June | 0.000 | 0.865193E+08 |
July | 0.000 | 0.215288E+08 |
August | 0.000 | 0.103478E+09 |
September | 0.000 | 0.116523E+10 |
October | 0.000 | 0.235751E+11 |
November | 0.000 | 0.981403E+11 |
December | 0.000 | 0.248040E+12 |
Annual Sum or Average | 0.100242E+13 | |
Minimum of Months | 0.000 | 0.215288E+08 |
Maximum of Months | 0.000 | 0.271776E+12 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2429796.94 | 5756.84 | 20-JAN-06:05 | -6.8 | -7.3 | 0.165229E+10 | 1854.44 | 19-JAN-15:00 | -2.8 | -3.5 |
February | 9119784.18 | 5368.31 | 12-FEB-08:06 | -4.4 | -5.5 | 0.150876E+10 | 1854.45 | 04-FEB-11:09 | 0.37 | -1.8 |
March | 0.181855E+09 | 2972.15 | 20-MAR-14:00 | 0.60 | -0.6 | 0.172685E+10 | 1956.61 | 31-MAR-14:00 | 8.30 | 2.61 |
April | 0.925389E+09 | 3415.60 | 14-APR-05:02 | 2.12 | 1.44 | 0.176407E+10 | 2451.26 | 18-APR-14:30 | 16.40 | 9.65 |
May | 0.439935E+10 | 14222.21 | 25-MAY-20:33 | 23.53 | 16.77 | 0.215693E+10 | 2451.26 | 31-MAY-14:30 | 10.70 | 8.02 |
June | 0.750233E+10 | 14817.03 | 30-JUN-21:00 | 20.60 | 16.65 | 0.219366E+10 | 2451.30 | 17-JUN-11:09 | 22.12 | 12.94 |
July | 0.999423E+10 | 14521.02 | 21-JUL-21:00 | 21.70 | 20.13 | 0.218601E+10 | 2451.25 | 08-JUL-10:09 | 13.30 | 12.39 |
August | 0.887982E+10 | 14978.02 | 13-AUG-18:40 | 21.13 | 14.83 | 0.227854E+10 | 2451.24 | 19-AUG-10:09 | 17.57 | 13.14 |
September | 0.497000E+10 | 11728.08 | 01-SEP-20:25 | 15.85 | 14.82 | 0.211603E+10 | 2451.29 | 06-SEP-14:00 | 20.00 | 11.90 |
October | 0.219144E+10 | 4280.42 | 21-OCT-14:50 | 20.00 | 11.19 | 0.186295E+10 | 2451.28 | 21-OCT-15:00 | 20.00 | 11.44 |
November | 0.474811E+09 | 5075.28 | 27-NOV-06:04 | -7.1 | -7.6 | 0.160901E+10 | 2393.39 | 01-NOV-14:00 | 18.30 | 13.43 |
December | 863899.47 | 9401.85 | 10-DEC-08:06 | -26.5 | -26.8 | 0.165479E+10 | 1854.44 | 06-DEC-15:00 | -6.9 | -7.0 |
Annual Sum or Average | 0.395316E+11 | 0.227099E+11 | ||||||||
Minimum of Months | 863899.47 | 2972.15 | -26.5 | -26.8 | 0.150876E+10 | 1854.44 | -6.9 | -7.0 | ||
Maximum of Months | 0.999423E+10 | 14978.02 | 23.53 | 20.13 | 0.227854E+10 | 2451.30 | 22.12 | 13.43 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300361E+10 | 55685.78 | 22-JAN-09:05 | -11.9 | -12.5 | 0.695905E+10 | 7812.80 | 02-JAN-15:09 | -11.8 | -12.5 |
February | 0.655813E+10 | 68271.15 | 11-FEB-07:04 | -16.0 | -16.4 | 0.635557E+10 | 7955.75 | 04-FEB-16:10 | 7.70 | 2.50 |
March | 0.138342E+11 | 77175.13 | 18-MAR-06:04 | -20.2 | -20.4 | 0.730851E+10 | 9196.11 | 31-MAR-14:00 | 8.30 | 2.61 |
April | 0.228674E+11 | 62422.43 | 05-APR-06:04 | -13.5 | -14.0 | 0.779537E+10 | 10327.13 | 22-APR-10:30 | 14.15 | 5.07 |
May | 0.374940E+11 | 68704.64 | 22-MAY-20:33 | 17.37 | 12.31 | 0.925404E+10 | 10327.35 | 18-MAY-14:09 | 28.57 | 16.70 |
June | 0.465993E+11 | 80017.74 | 09-JUN-05:02 | 12.70 | 11.73 | 0.926848E+10 | 10327.24 | 15-JUN-14:00 | 21.70 | 13.19 |
July | 0.531857E+11 | 98975.17 | 01-JUL-05:02 | 9.78 | 9.47 | 0.921395E+10 | 10327.15 | 08-JUL-10:09 | 13.30 | 12.39 |
August | 0.498323E+11 | 113442.96 | 25-AUG-05:01 | 7.88 | 7.62 | 0.960598E+10 | 10327.11 | 10-AUG-14:09 | 18.95 | 16.67 |
September | 0.354430E+11 | 67869.36 | 03-SEP-19:03 | 17.02 | 14.20 | 0.898649E+10 | 10327.52 | 07-SEP-14:20 | 23.90 | 14.64 |
October | 0.257909E+11 | 44036.26 | 25-OCT-06:01 | -4.2 | -4.4 | 0.799455E+10 | 10327.19 | 21-OCT-12:09 | 18.07 | 11.00 |
November | 0.132395E+11 | 55793.49 | 24-NOV-07:04 | -10.0 | -10.7 | 0.685410E+10 | 10327.05 | 01-NOV-14:09 | 17.88 | 13.28 |
December | 0.409904E+10 | 63416.52 | 09-DEC-07:04 | -13.7 | -14.0 | 0.696965E+10 | 7812.80 | 11-DEC-15:09 | -17.7 | -18.6 |
Annual Sum or Average | 0.311947E+12 | 0.965657E+11 | ||||||||
Minimum of Months | 0.300361E+10 | 44036.26 | -20.2 | -20.4 | 0.635557E+10 | 7812.80 | -17.7 | -18.6 | ||
Maximum of Months | 0.531857E+11 | 113442.96 | 17.37 | 14.20 | 0.960598E+10 | 10327.52 | 28.57 | 16.70 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.886122E+09 | 8681.70 | 01-JAN-08:04 | -26.7 | -26.9 | 0.655930E+09 | 736.18 | 14-JAN-16:19 | -12.6 | -13.1 |
February | 0.152782E+10 | 8041.19 | 13-FEB-06:04 | -24.0 | -24.3 | 0.620253E+09 | 973.09 | 04-FEB-16:10 | 7.70 | 2.50 |
March | 0.218954E+10 | 6073.65 | 13-MAR-05:04 | -13.3 | -14.5 | 0.723037E+09 | 973.09 | 29-MAR-14:09 | 3.98 | 0.93 |
April | 0.333760E+10 | 7329.44 | 22-APR-13:40 | 17.23 | 7.20 | 0.763135E+09 | 973.10 | 22-APR-10:09 | 13.58 | 4.69 |
May | 0.595402E+10 | 11693.81 | 25-MAY-20:10 | 24.63 | 17.27 | 0.874225E+09 | 973.19 | 24-MAY-14:09 | 27.22 | 17.66 |
June | 0.736918E+10 | 13962.82 | 29-JUN-20:43 | 27.98 | 23.69 | 0.872589E+09 | 973.19 | 21-JUN-14:30 | 24.40 | 16.57 |
July | 0.914643E+10 | 14860.14 | 23-JUL-18:43 | 27.48 | 21.59 | 0.868086E+09 | 973.17 | 31-JUL-14:09 | 20.50 | 14.51 |
August | 0.924933E+10 | 15050.28 | 08-AUG-20:43 | 23.17 | 19.28 | 0.905021E+09 | 973.20 | 25-AUG-14:00 | 28.30 | 19.19 |
September | 0.702730E+10 | 14743.57 | 01-SEP-20:43 | 15.28 | 14.47 | 0.849251E+09 | 973.16 | 01-SEP-14:09 | 25.68 | 18.04 |
October | 0.442544E+10 | 10285.89 | 22-OCT-18:10 | 12.75 | 9.21 | 0.795470E+09 | 973.12 | 07-OCT-10:30 | 11.95 | 11.31 |
November | 0.212447E+10 | 5272.08 | 17-NOV-13:30 | 10.30 | 3.30 | 0.683196E+09 | 973.10 | 14-NOV-15:09 | 10.73 | 6.42 |
December | 0.734944E+09 | 8358.09 | 20-DEC-06:04 | -28.9 | -29.1 | 0.657109E+09 | 743.81 | 28-DEC-15:09 | -1.8 | -3.6 |
Annual Sum or Average | 0.539722E+11 | 0.926730E+10 | ||||||||
Minimum of Months | 0.734944E+09 | 5272.08 | -28.9 | -29.1 | 0.620253E+09 | 736.18 | -12.6 | -13.1 | ||
Maximum of Months | 0.924933E+10 | 15050.28 | 27.98 | 23.69 | 0.905021E+09 | 973.20 | 28.30 | 19.19 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252426E+09 | 7334.69 | 27-JAN-06:04 | -22.8 | -22.9 | 0.655928E+09 | 736.18 | 04-JAN-15:50 | -27.3 | -27.6 |
February | 0.626335E+09 | 7686.43 | 19-FEB-08:04 | -23.5 | -23.7 | 0.604657E+09 | 918.79 | 28-FEB-15:50 | 6.10 | 1.53 |
March | 0.967336E+09 | 5650.16 | 14-MAR-05:04 | -13.4 | -14.4 | 0.695539E+09 | 972.87 | 31-MAR-14:00 | 8.30 | 2.61 |
April | 0.176203E+10 | 5086.57 | 23-APR-18:20 | 24.83 | 15.87 | 0.719573E+09 | 973.10 | 13-APR-14:20 | 19.27 | 7.63 |
May | 0.342999E+10 | 8349.07 | 25-MAY-20:10 | 24.63 | 17.27 | 0.850673E+09 | 973.15 | 15-MAY-14:30 | 22.15 | 14.11 |
June | 0.454765E+10 | 11112.99 | 29-JUN-20:43 | 27.98 | 23.69 | 0.867640E+09 | 973.16 | 07-JUN-14:09 | 22.20 | 14.32 |
July | 0.608646E+10 | 12133.39 | 23-JUL-18:43 | 27.48 | 21.59 | 0.866896E+09 | 973.15 | 07-JUL-14:00 | 22.20 | 14.39 |
August | 0.612114E+10 | 11869.90 | 08-AUG-20:43 | 23.17 | 19.28 | 0.902949E+09 | 973.14 | 05-AUG-15:00 | 22.80 | 14.57 |
September | 0.449630E+10 | 11702.90 | 01-SEP-20:43 | 15.28 | 14.47 | 0.828644E+09 | 973.16 | 01-SEP-14:09 | 25.68 | 18.04 |
October | 0.265112E+10 | 7524.48 | 20-OCT-14:05 | 18.90 | 10.05 | 0.737954E+09 | 973.13 | 18-OCT-14:09 | 16.78 | 11.26 |
November | 0.882204E+09 | 4049.02 | 10-NOV-19:53 | -6.1 | -7.7 | 0.647813E+09 | 973.10 | 01-NOV-14:00 | 18.30 | 13.43 |
December | 0.176536E+09 | 7328.75 | 10-DEC-14:42 | -22.3 | -22.9 | 0.656922E+09 | 736.18 | 16-DEC-12:30 | -9.2 | -9.5 |
Annual Sum or Average | 0.319995E+11 | 0.903519E+10 | ||||||||
Minimum of Months | 0.176536E+09 | 4049.02 | -23.5 | -23.7 | 0.604657E+09 | 736.18 | -27.3 | -27.6 | ||
Maximum of Months | 0.612114E+10 | 12133.39 | 27.98 | 23.69 | 0.902949E+09 | 973.16 | 25.68 | 18.04 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -23.1 | -23.4 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 | 13.56 | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.56 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.4 | 0.00 | 0.00 | -23.1 | -23.4 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.00 | 0.00 | 19.75 | 18.15 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236523E+11 | 50259.12 | 29-JAN-07:31 | -6.1 |
February | 0.170556E+11 | 51817.51 | 21-FEB-05:32 | 2.60 |
March | 0.126713E+11 | 50523.09 | 28-MAR-04:42 | 1.78 |
April | 0.464794E+10 | 51389.16 | 18-APR-04:02 | 11.70 |
May | 0.375373E+09 | 49837.01 | 09-MAY-04:01 | 4.63 |
June | 14011457.24 | 1833.65 | 25-JUN-07:10 | 22.98 |
July | 2993843.99 | 1687.75 | 23-JUL-07:07 | 22.38 |
August | 1918790.18 | 593.37 | 09-AUG-05:10 | 18.40 |
September | 4738486.17 | 17913.35 | 28-SEP-05:01 | 6.70 |
October | 0.161414E+10 | 52115.37 | 31-OCT-04:01 | 10.00 |
November | 0.822710E+10 | 52097.32 | 01-NOV-04:01 | 10.60 |
December | 0.209880E+11 | 50983.37 | 05-DEC-05:41 | -1.1 |
Annual Sum or Average | 0.892555E+11 | |||
Minimum of Months | 1918790.18 | 593.37 | -6.1 | |
Maximum of Months | 0.236523E+11 | 52115.37 | 22.98 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215166E+11 | 301603.24 | 05-JAN-05:01 | -31.9 |
February | 0.123093E+11 | 301551.46 | 14-FEB-05:01 | -32.1 |
March | 0.773935E+10 | 301488.61 | 06-MAR-05:01 | -18.4 |
April | 0.238472E+10 | 298023.68 | 04-APR-05:01 | -9.0 |
May | 0.723632E+09 | 34876.37 | 01-MAY-05:02 | -3.4 |
June | 0.107738E+09 | 15696.50 | 09-JUN-05:04 | 12.70 |
July | 0.103085E+09 | 15938.19 | 01-JUL-05:03 | 9.78 |
August | 0.130059E+09 | 16165.29 | 25-AUG-05:03 | 7.88 |
September | 0.367969E+09 | 15256.29 | 08-SEP-05:03 | 10.10 |
October | 0.157800E+10 | 109668.60 | 30-OCT-05:02 | -9.9 |
November | 0.560437E+10 | 299415.12 | 25-NOV-06:01 | -19.4 |
December | 0.179288E+11 | 302001.17 | 25-DEC-07:01 | -28.6 |
Annual Sum or Average | 0.704936E+11 | |||
Minimum of Months | 0.103085E+09 | 15256.29 | -32.1 | |
Maximum of Months | 0.215166E+11 | 302001.17 | 12.70 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.614435E+10 | 35247.73 | 29-JAN-07:31 | -6.1 |
February | 0.375507E+10 | 35608.11 | 21-FEB-05:01 | 2.30 |
March | 0.262458E+10 | 35218.23 | 28-MAR-04:01 | 2.12 |
April | 0.924462E+09 | 35691.53 | 08-APR-04:01 | 4.22 |
May | 58927048.03 | 34269.22 | 01-MAY-04:01 | -2.9 |
June | 238577.11 | 232.16 | 10-JUN-07:42 | 18.43 |
July | 659877.62 | 639.87 | 05-JUL-05:10 | 19.60 |
August | 169741.25 | 291.67 | 30-AUG-05:10 | 17.88 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19.75 |
October | 0.336943E+09 | 36765.20 | 31-OCT-04:01 | 10.00 |
November | 0.195803E+10 | 36756.40 | 01-NOV-04:01 | 10.60 |
December | 0.573234E+10 | 35613.93 | 05-DEC-05:41 | -1.1 |
Annual Sum or Average | 0.215358E+11 | |||
Minimum of Months | 0.00 | 0.00 | -6.1 | |
Maximum of Months | 0.614435E+10 | 36765.20 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.866685E+10 | 30012.35 | 16-JAN-07:01 | -1.6 |
February | 0.543328E+10 | 30652.66 | 21-FEB-05:01 | 2.30 |
March | 0.409447E+10 | 30336.28 | 28-MAR-04:01 | 2.12 |
April | 0.161649E+10 | 30793.30 | 08-APR-04:01 | 4.22 |
May | 0.156807E+09 | 30095.41 | 09-MAY-04:01 | 4.63 |
June | 1107659.68 | 333.01 | 25-JUN-07:10 | 22.98 |
July | 1091863.53 | 877.70 | 23-JUL-07:07 | 22.38 |
August | 44259.48 | 123.22 | 09-AUG-05:10 | 18.40 |
September | 7750790.95 | 12076.82 | 23-SEP-04:47 | 5.10 |
October | 0.720598E+09 | 31839.55 | 31-OCT-04:01 | 10.00 |
November | 0.316842E+10 | 31841.78 | 01-NOV-04:01 | 10.60 |
December | 0.829798E+10 | 30317.77 | 05-DEC-05:11 | -1.2 |
Annual Sum or Average | 0.321649E+11 | |||
Minimum of Months | 44259.48 | 123.22 | -1.6 | |
Maximum of Months | 0.866685E+10 | 31841.78 | 22.98 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.352290E+11 | 66118.90 | 05-JAN-18:00 | -28.3 |
February | 0.247851E+11 | 57592.25 | 01-FEB-18:00 | -23.3 |
March | 0.225437E+11 | 46244.53 | 15-MAR-11:10 | -15.3 |
April | 0.118534E+11 | 33485.81 | 04-APR-11:03 | -4.9 |
May | 0.396702E+10 | 18408.70 | 01-MAY-11:10 | 6.72 |
June | 0.144907E+10 | 10489.82 | 02-JUN-11:10 | 12.20 |
July | 0.622803E+09 | 9749.61 | 09-JUL-11:02 | 14.08 |
August | 0.104670E+10 | 11378.67 | 17-AUG-12:00 | 10.60 |
September | 0.453486E+10 | 16164.40 | 27-SEP-11:05 | 7.38 |
October | 0.112749E+11 | 26611.46 | 29-OCT-11:10 | 0.68 |
November | 0.188747E+11 | 46011.38 | 25-NOV-17:00 | -15.6 |
December | 0.338138E+11 | 63579.13 | 24-DEC-12:10 | -26.9 |
Annual Sum or Average | 0.169995E+12 | |||
Minimum of Months | 0.622803E+09 | 9749.61 | -28.3 | |
Maximum of Months | 0.352290E+11 | 66118.90 | 14.08 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.368607E+10 | 3087.68 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.335384E+10 | 3087.68 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.382564E+10 | 3087.68 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.360950E+10 | 3087.68 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.375586E+10 | 3087.68 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.369163E+10 | 3087.68 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.367372E+10 | 3087.68 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.382564E+10 | 3087.68 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.360950E+10 | 3087.68 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.368607E+10 | 3087.68 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.356442E+10 | 3087.68 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.367372E+10 | 3087.68 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.439556E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.335384E+10 | 3087.68 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.382564E+10 | 3087.68 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.314662E+11 | 26358.01 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.286301E+11 | 26358.01 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.326576E+11 | 26358.01 | 01-MAR-09:09 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.308125E+11 | 26358.01 | 01-APR-09:09 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.320619E+11 | 26358.01 | 01-MAY-08:09 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.315136E+11 | 26358.01 | 01-JUN-08:09 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.313608E+11 | 26358.01 | 01-JUL-09:09 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.326576E+11 | 26358.01 | 01-AUG-08:09 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.308125E+11 | 26358.01 | 01-SEP-08:09 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.314662E+11 | 26358.01 | 02-OCT-08:09 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.304277E+11 | 26358.01 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.313608E+11 | 26358.01 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.375227E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.286301E+11 | 26358.01 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.326576E+11 | 26358.01 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.296499E+10 | 2483.66 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.269775E+10 | 2483.66 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.307725E+10 | 2483.66 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.290340E+10 | 2483.66 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.302112E+10 | 2483.66 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.296946E+10 | 2483.66 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.295506E+10 | 2483.66 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.307725E+10 | 2483.66 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.290340E+10 | 2483.66 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.296499E+10 | 2483.66 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.286713E+10 | 2483.66 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.295506E+10 | 2483.66 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.353568E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.269775E+10 | 2483.66 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.307725E+10 | 2483.66 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.296499E+10 | 2483.66 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.269775E+10 | 2483.66 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.307725E+10 | 2483.66 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.290340E+10 | 2483.66 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.302112E+10 | 2483.66 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.296946E+10 | 2483.66 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.295506E+10 | 2483.66 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.307725E+10 | 2483.66 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.290340E+10 | 2483.66 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.296499E+10 | 2483.66 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.286713E+10 | 2483.66 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.295506E+10 | 2483.66 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.353568E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.269775E+10 | 2483.66 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.307725E+10 | 2483.66 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.180413E+09 | 151.13 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.164152E+09 | 151.13 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.187244E+09 | 151.13 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.176665E+09 | 151.13 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.183829E+09 | 151.13 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.180685E+09 | 151.13 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.179809E+09 | 151.13 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.187244E+09 | 151.13 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.176665E+09 | 151.13 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.180413E+09 | 151.13 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.174459E+09 | 151.13 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.179809E+09 | 151.13 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.215139E+10 | ||||
Minimum of Months | 0.164152E+09 | 151.13 | 0.00 | 0.00 | |
Maximum of Months | 0.187244E+09 | 151.13 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.368607E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718775E+10 |
February | 0.479114E+10 | 0.335384E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620276E+10 |
March | 0.548013E+10 | 0.382564E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438355E+10 |
April | 0.518069E+10 | 0.360950E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3511497.30 | 0.356805E+10 |
May | 0.536353E+10 | 0.375586E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14962371.22 | 0.178409E+10 |
June | 0.528933E+10 | 0.369163E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68878685.40 | 0.100374E+10 |
July | 0.525489E+10 | 0.367372E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63165574.43 | 0.670809E+09 |
August | 0.548013E+10 | 0.382564E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23972943.77 | 0.105774E+10 |
September | 0.518069E+10 | 0.360950E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 780149.18 | 0.186515E+10 |
October | 0.524694E+10 | 0.368607E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266995E+10 |
November | 0.504819E+10 | 0.356442E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485369E+10 |
December | 0.525489E+10 | 0.367372E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742728E+10 |
Annual Sum or Average | 0.628175E+11 | 0.439556E+11 | 0.499918E+11 | 0.175271E+09 | 0.426746E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.335384E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670809E+09 |
Maximum of Months | 0.548013E+10 | 0.382564E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68878685.40 | 0.742728E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.314662E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606865E+10 |
February | 0.201852E+11 | 0.286301E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529500E+10 |
March | 0.230879E+11 | 0.326576E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379933E+10 |
April | 0.218263E+11 | 0.308125E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2350043.54 | 0.323742E+10 |
May | 0.225967E+11 | 0.320619E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12256250.71 | 0.164812E+10 |
June | 0.222841E+11 | 0.315136E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56384720.32 | 0.900982E+09 |
July | 0.221389E+11 | 0.313608E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51688246.33 | 0.564335E+09 |
August | 0.230879E+11 | 0.326576E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19615946.90 | 0.903851E+09 |
September | 0.218263E+11 | 0.308125E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 638501.17 | 0.166707E+10 |
October | 0.221054E+11 | 0.314662E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236545E+10 |
November | 0.212681E+11 | 0.304277E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425172E+10 |
December | 0.221389E+11 | 0.313608E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630436E+10 |
Annual Sum or Average | 0.264651E+12 | 0.375227E+12 | 0.842987E+11 | 0.142934E+09 | 0.370063E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.286301E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564335E+09 |
Maximum of Months | 0.230879E+11 | 0.326576E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56384720.32 | 0.630436E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.296499E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312794E+10 |
February | 0.190200E+10 | 0.269775E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272793E+10 |
March | 0.217552E+10 | 0.307725E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196645E+10 |
April | 0.205665E+10 | 0.290340E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1298150.53 | 0.164678E+10 |
May | 0.212923E+10 | 0.302112E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6488753.03 | 0.821584E+09 |
June | 0.209978E+10 | 0.296946E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29838390.67 | 0.457898E+09 |
July | 0.208610E+10 | 0.295506E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27346908.44 | 0.296090E+09 |
August | 0.217552E+10 | 0.307725E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10385963.93 | 0.472737E+09 |
September | 0.205665E+10 | 0.290340E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 337753.40 | 0.854666E+09 |
October | 0.208295E+10 | 0.296499E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123678E+10 |
November | 0.200405E+10 | 0.286713E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216914E+10 |
December | 0.208610E+10 | 0.295506E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323070E+10 |
Annual Sum or Average | 0.249375E+11 | 0.353568E+11 | 0.529224E+11 | 75695920.00 | 0.190087E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.269775E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296090E+09 |
Maximum of Months | 0.217552E+10 | 0.307725E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29838390.67 | 0.323070E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.296499E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311837E+10 |
February | 0.190200E+10 | 0.269775E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270612E+10 |
March | 0.217552E+10 | 0.307725E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192954E+10 |
April | 0.205665E+10 | 0.290340E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1293744.42 | 0.158577E+10 |
May | 0.212923E+10 | 0.302112E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6491977.01 | 0.781208E+09 |
June | 0.209978E+10 | 0.296946E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29861352.20 | 0.434728E+09 |
July | 0.208610E+10 | 0.295506E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27359503.05 | 0.290127E+09 |
August | 0.217552E+10 | 0.307725E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10389219.35 | 0.462080E+09 |
September | 0.205665E+10 | 0.290340E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 337903.25 | 0.819026E+09 |
October | 0.208295E+10 | 0.296499E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118056E+10 |
November | 0.200405E+10 | 0.286713E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211805E+10 |
December | 0.208610E+10 | 0.295506E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321683E+10 |
Annual Sum or Average | 0.249375E+11 | 0.353568E+11 | 0.794328E+10 | 75733699.28 | 0.186424E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.269775E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290127E+09 |
Maximum of Months | 0.217552E+10 | 0.307725E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29861352.20 | 0.321683E+10 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.180413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340472E+11 |
February | 0.00 | 0.164152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241268E+11 |
March | 0.00 | 0.187244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219387E+11 |
April | 0.00 | 0.176665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118597E+11 |
May | 0.00 | 0.183829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1069296.17 | 0.441636E+10 |
June | 0.00 | 0.180685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22658443.82 | 0.188915E+10 |
July | 0.00 | 0.179809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7200264.18 | 0.110238E+10 |
August | 0.00 | 0.187244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436668.87 | 0.175471E+10 |
September | 0.00 | 0.176665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532697E+10 |
October | 0.00 | 0.180413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115898E+11 |
November | 0.00 | 0.174459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184363E+11 |
December | 0.00 | 0.179809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326138E+11 |
Annual Sum or Average | 0.00 | 0.215139E+10 | 31364673.04 | 0.169102E+12 | |||||
Minimum of Months | 0.00 | 0.164152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110238E+10 |
Maximum of Months | 0.00 | 0.187244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22658443.82 | 0.340472E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 3087.68 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 15138.14 | 04-JAN-06:00 |
February | 5888.82 | 01-FEB-15:09 | 3087.68 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 17001.17 | 12-FEB-23:00 |
March | 5888.82 | 01-MAR-15:09 | 3087.68 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 9364.05 | 15-MAR-05:00 |
April | 5888.82 | 01-APR-10:09 | 3087.68 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 528.41 | 23-APR-18:10 | 7161.44 | 01-APR-21:02 |
May | 5888.82 | 01-MAY-14:09 | 3087.68 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.09 | 24-MAY-15:00 | 3531.29 | 09-MAY-04:04 |
June | 5888.82 | 01-JUN-14:09 | 3087.68 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.27 | 29-JUN-20:20 | 2467.89 | 09-JUN-20:10 |
July | 5888.82 | 01-JUL-10:09 | 3087.68 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 818.05 | 23-JUL-18:03 | 2153.89 | 06-JUL-21:55 |
August | 5888.82 | 01-AUG-14:09 | 3087.68 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 414.83 | 08-AUG-16:00 | 3054.63 | 27-AUG-06:00 |
September | 5888.82 | 01-SEP-14:09 | 3087.68 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 | 01-SEP-15:00 | 4204.50 | 20-SEP-01:00 |
October | 5888.82 | 02-OCT-14:09 | 3087.68 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5883.76 | 31-OCT-20:02 |
November | 5888.82 | 01-NOV-14:09 | 3087.68 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9287.99 | 23-NOV-08:00 |
December | 5888.82 | 01-DEC-15:09 | 3087.68 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 15257.57 | 16-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 3087.68 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2153.89 | |||||
Maximum of Months | 5888.82 | 3087.68 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 818.05 | 17001.17 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 26358.01 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 11708.49 | 04-JAN-05:51 |
February | 24809.68 | 01-FEB-15:09 | 26358.01 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 14497.80 | 12-FEB-22:52 |
March | 24809.68 | 01-MAR-15:09 | 26358.01 | 01-MAR-09:09 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7136.00 | 15-MAR-04:52 |
April | 24809.68 | 01-APR-10:09 | 26358.01 | 01-APR-09:09 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 354.58 | 23-APR-18:05 | 5935.11 | 02-APR-01:00 |
May | 24809.68 | 01-MAY-14:09 | 26358.01 | 01-MAY-08:09 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 156.42 | 24-MAY-15:00 | 3189.34 | 20-MAY-04:55 |
June | 24809.68 | 01-JUN-14:09 | 26358.01 | 01-JUN-08:09 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 646.07 | 29-JUN-20:20 | 2214.40 | 10-JUN-22:00 |
July | 24809.68 | 01-JUL-10:09 | 26358.01 | 01-JUL-09:09 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 671.41 | 23-JUL-18:03 | 1747.35 | 06-JUL-21:55 |
August | 24809.68 | 01-AUG-14:09 | 26358.01 | 01-AUG-08:09 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 339.54 | 08-AUG-16:00 | 2812.33 | 27-AUG-06:00 |
September | 24809.68 | 01-SEP-14:09 | 26358.01 | 01-SEP-08:09 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.07 | 01-SEP-15:00 | 3941.24 | 20-SEP-01:00 |
October | 24809.68 | 02-OCT-14:09 | 26358.01 | 02-OCT-08:09 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4868.29 | 31-OCT-20:35 |
November | 24809.68 | 01-NOV-14:09 | 26358.01 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8525.26 | 22-NOV-01:55 |
December | 24809.68 | 01-DEC-15:09 | 26358.01 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 11363.52 | 16-DEC-05:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 26358.01 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1747.35 | |||||
Maximum of Months | 24809.68 | 26358.01 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 671.41 | 14497.80 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2483.66 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6571.89 | 04-JAN-05:51 |
February | 2337.76 | 01-FEB-15:09 | 2483.66 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 7367.25 | 12-FEB-22:52 |
March | 2337.76 | 01-MAR-15:09 | 2483.66 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4057.72 | 15-MAR-05:00 |
April | 2337.76 | 01-APR-10:09 | 2483.66 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 156.92 | 23-APR-18:05 | 3110.41 | 01-APR-21:02 |
May | 2337.76 | 01-MAY-14:09 | 2483.66 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.78 | 24-MAY-15:00 | 1551.80 | 09-MAY-04:04 |
June | 2337.76 | 01-JUN-14:09 | 2483.66 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.73 | 29-JUN-20:47 | 1090.58 | 09-JUN-20:10 |
July | 2337.76 | 01-JUL-10:09 | 2483.66 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 361.06 | 23-JUL-18:10 | 975.77 | 06-JUL-22:00 |
August | 2337.76 | 01-AUG-14:09 | 2483.66 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.76 | 08-AUG-16:00 | 1400.15 | 27-AUG-06:00 |
September | 2337.76 | 01-SEP-14:09 | 2483.66 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.66 | 01-SEP-15:00 | 1875.47 | 20-SEP-01:00 |
October | 2337.76 | 02-OCT-14:09 | 2483.66 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2552.05 | 31-OCT-20:02 |
November | 2337.76 | 01-NOV-14:09 | 2483.66 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4024.76 | 23-NOV-08:00 |
December | 2337.76 | 01-DEC-15:09 | 2483.66 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6611.84 | 16-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2483.66 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 975.77 | |||||
Maximum of Months | 2337.76 | 2483.66 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 361.06 | 7367.25 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2483.66 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6637.70 | 04-JAN-06:00 |
February | 2337.76 | 01-FEB-15:09 | 2483.66 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 7367.11 | 12-FEB-22:52 |
March | 2337.76 | 01-MAR-15:09 | 2483.66 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4019.07 | 15-MAR-04:51 |
April | 2337.76 | 01-APR-10:09 | 2483.66 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 173.08 | 23-APR-18:05 | 3104.45 | 01-APR-21:02 |
May | 2337.76 | 01-MAY-14:09 | 2483.66 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.81 | 24-MAY-15:00 | 1513.25 | 09-MAY-04:04 |
June | 2337.76 | 01-JUN-14:09 | 2483.66 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 342.04 | 29-JUN-20:47 | 1029.30 | 09-JUN-20:10 |
July | 2337.76 | 01-JUL-10:09 | 2483.66 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 361.49 | 23-JUL-18:10 | 966.05 | 06-JUL-21:55 |
August | 2337.76 | 01-AUG-14:09 | 2483.66 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.76 | 08-AUG-16:00 | 1354.79 | 27-AUG-06:00 |
September | 2337.76 | 01-SEP-14:09 | 2483.66 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.66 | 01-SEP-15:00 | 1789.14 | 20-SEP-01:00 |
October | 2337.76 | 02-OCT-14:09 | 2483.66 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2547.36 | 31-OCT-20:02 |
November | 2337.76 | 01-NOV-14:09 | 2483.66 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4024.76 | 23-NOV-08:00 |
December | 2337.76 | 01-DEC-15:09 | 2483.66 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6531.13 | 16-DEC-05:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2483.66 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 966.05 | |||||
Maximum of Months | 2337.76 | 2483.66 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 361.49 | 7367.11 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 151.13 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 65619.28 | 05-JAN-18:00 |
February | 0.00 | 01-FEB-00:10 | 151.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 57298.56 | 01-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 151.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 46450.99 | 15-MAR-11:10 |
April | 0.00 | 01-APR-00:10 | 151.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 35263.88 | 04-APR-11:02 |
May | 0.00 | 01-MAY-00:10 | 151.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.44 | 25-MAY-17:00 | 19026.11 | 01-MAY-11:05 |
June | 0.00 | 01-JUN-00:10 | 151.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.34 | 29-JUN-16:00 | 11247.88 | 09-JUN-11:02 |
July | 0.00 | 01-JUL-00:10 | 151.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.76 | 15-JUL-13:55 | 10555.39 | 09-JUL-11:02 |
August | 0.00 | 01-AUG-00:10 | 151.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.91 | 08-AUG-16:00 | 11878.73 | 17-AUG-12:00 |
September | 0.00 | 01-SEP-00:10 | 151.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 16588.59 | 27-SEP-11:05 |
October | 0.00 | 01-OCT-00:10 | 151.13 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 26498.20 | 29-OCT-11:10 |
November | 0.00 | 01-NOV-00:10 | 151.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 45577.65 | 25-NOV-17:00 |
December | 0.00 | 01-DEC-00:10 | 151.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 63877.02 | 24-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 151.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10555.39 | ||||
Maximum of Months | 0.00 | 151.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.34 | 65619.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5756.84 | 20-JAN-06:05 | 0.00 | 1029.23 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1956.94 |
February | 5368.31 | 12-FEB-08:06 | 0.00 | 1200.76 | 3219.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1526.87 |
March | 2972.15 | 20-MAR-14:00 | 5152.71 | 3087.68 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.94 |
April | 3415.60 | 14-APR-05:02 | 0.00 | 1372.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14222.21 | 25-MAY-20:33 | 0.00 | 2058.45 | 1839.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.06 |
June | 14817.03 | 30-JUN-21:00 | 0.00 | 1372.30 | 1226.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.69 |
July | 14521.02 | 21-JUL-21:00 | 0.00 | 1372.30 | 1226.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.74 |
August | 14978.02 | 13-AUG-18:40 | 0.00 | 514.61 | 1379.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.76 |
September | 11728.08 | 01-SEP-20:25 | 0.00 | 1372.30 | 1226.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4280.42 | 21-OCT-14:50 | 5888.82 | 3087.68 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.57 |
November | 5075.28 | 27-NOV-06:04 | 0.00 | 1372.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 866.02 |
December | 9401.85 | 10-DEC-08:06 | 0.00 | 1200.76 | 3219.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2191.96 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2972.15 | 0.00 | 514.61 | 1226.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14978.02 | 5888.82 | 3087.68 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2191.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 55685.78 | 22-JAN-09:05 | 12404.84 | 11714.67 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.13 |
February | 68271.15 | 11-FEB-07:04 | 15506.05 | 14643.34 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77175.13 | 18-MAR-06:04 | 15506.05 | 14643.34 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 62422.43 | 05-APR-06:04 | 15506.05 | 29286.67 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 68704.64 | 22-MAY-20:33 | 0.00 | 17572.00 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 612.21 |
June | 80017.74 | 09-JUN-05:02 | 0.00 | 7321.67 | 5169.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.91 |
July | 98975.17 | 01-JUL-05:02 | 0.00 | 8786.00 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.49 |
August | 113442.96 | 25-AUG-05:01 | 0.00 | 10250.34 | 7237.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67869.36 | 03-SEP-19:03 | 0.00 | 5857.33 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 646.57 |
October | 44036.26 | 25-OCT-06:01 | 21708.47 | 41001.34 | 14474.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 55793.49 | 24-NOV-07:04 | 15506.05 | 29286.67 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 664.84 |
December | 63416.52 | 09-DEC-07:04 | 15506.05 | 14643.34 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 827.78 |
Annual Sum or Average | |||||||||||
Minimum of Months | 44036.26 | 0.00 | 5857.33 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 113442.96 | 21708.47 | 41001.34 | 14474.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8681.70 | 01-JAN-08:04 | 0.00 | 965.87 | 3407.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862.54 |
February | 8041.19 | 13-FEB-06:04 | 0.00 | 965.87 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.66 |
March | 6073.65 | 13-MAR-05:04 | 0.00 | 965.87 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.69 |
April | 7329.44 | 22-APR-13:40 | 2337.76 | 2483.66 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.33 |
May | 11693.81 | 25-MAY-20:10 | 0.00 | 1655.77 | 1947.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.24 | 0.00 |
June | 13962.82 | 29-JUN-20:43 | 0.00 | 1655.77 | 1947.26 | 0.00 | 0.00 | 0.00 | 0.00 | 313.53 | 0.00 |
July | 14860.14 | 23-JUL-18:43 | 0.00 | 413.94 | 1460.44 | 0.00 | 0.00 | 0.00 | 0.00 | 182.80 | 0.00 |
August | 15050.28 | 08-AUG-20:43 | 0.00 | 1655.77 | 1947.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.54 |
September | 14743.57 | 01-SEP-20:43 | 0.00 | 1655.77 | 1947.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10285.89 | 22-OCT-18:10 | 0.00 | 689.90 | 2434.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 900.49 |
November | 5272.08 | 17-NOV-13:30 | 2045.54 | 2483.66 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.85 |
December | 8358.09 | 20-DEC-06:04 | 0.00 | 965.87 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 856.04 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5272.08 | 0.00 | 413.94 | 1460.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15050.28 | 2337.76 | 2483.66 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 313.53 | 1176.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7334.69 | 27-JAN-06:04 | 0.00 | 1103.85 | 779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.26 |
February | 7686.43 | 19-FEB-08:04 | 0.00 | 965.87 | 511.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 646.22 |
March | 5650.16 | 14-MAR-05:04 | 0.00 | 965.87 | 681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 692.27 |
April | 5086.57 | 23-APR-18:20 | 0.00 | 275.96 | 146.13 | 0.00 | 0.00 | 0.00 | 0.00 | 130.04 | 0.00 |
May | 8349.07 | 25-MAY-20:10 | 0.00 | 1655.77 | 292.27 | 0.00 | 0.00 | 0.00 | 0.00 | 28.40 | 0.00 |
June | 11112.99 | 29-JUN-20:43 | 0.00 | 1655.77 | 292.27 | 0.00 | 0.00 | 0.00 | 0.00 | 318.01 | 0.00 |
July | 12133.39 | 23-JUL-18:43 | 0.00 | 413.94 | 219.20 | 0.00 | 0.00 | 0.00 | 0.00 | 180.79 | 0.00 |
August | 11869.90 | 08-AUG-20:43 | 0.00 | 1655.77 | 292.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.13 |
September | 11702.90 | 01-SEP-20:43 | 0.00 | 1655.77 | 292.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7524.48 | 20-OCT-14:05 | 9351.05 | 9934.63 | 1753.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.95 |
November | 4049.02 | 10-NOV-19:53 | 2629.98 | 4139.43 | 1022.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.52 |
December | 7328.75 | 10-DEC-14:42 | 5844.40 | 8278.86 | 1948.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 909.11 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4049.02 | 0.00 | 275.96 | 146.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12133.39 | 9351.05 | 9934.63 | 1948.47 | 0.00 | 0.00 | 0.00 | 0.00 | 318.01 | 909.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 50.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.69 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 41.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.96 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.65 |
April | 0.00 | 01-APR-00:10 | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.85 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.95 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.98 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 16.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.73 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.85 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 16.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.48 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.44 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.48 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.26 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.95 | |
Maximum of Months | 0.00 | 0.00 | 50.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.96 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.112692E+12 | 78220.67 | 02-JAN-16:30 | 0.280775E+12 | 329749.88 | 09-JAN-07:10 |
February | 0.100472E+12 | 78220.67 | 01-FEB-17:10 | 0.187869E+12 | 306196.57 | 14-FEB-07:10 |
March | 0.110903E+12 | 78220.67 | 01-MAR-17:00 | 0.145516E+12 | 255706.43 | 16-MAR-06:10 |
April | 0.104449E+12 | 84302.58 | 22-APR-15:00 | 0.491513E+11 | 181358.22 | 05-APR-06:10 |
May | 0.116911E+12 | 104442.58 | 25-MAY-14:00 | 0.118411E+11 | 93928.37 | 01-MAY-06:10 |
June | 0.125944E+12 | 121656.31 | 29-JUN-15:00 | 0.843247E+10 | 8309.25 | 02-JUN-11:00 |
July | 0.136045E+12 | 117572.26 | 15-JUL-14:20 | 0.839836E+10 | 6693.18 | 08-JUL-11:00 |
August | 0.132943E+12 | 114103.26 | 08-AUG-14:00 | 0.848766E+10 | 10480.33 | 17-AUG-13:00 |
September | 0.112526E+12 | 101152.83 | 01-SEP-14:20 | 0.925790E+10 | 14659.98 | 27-SEP-11:20 |
October | 0.108696E+12 | 86279.68 | 21-OCT-12:30 | 0.320352E+11 | 134957.85 | 30-OCT-06:10 |
November | 0.106367E+12 | 81856.07 | 01-NOV-16:00 | 0.106501E+12 | 237899.46 | 25-NOV-07:10 |
December | 0.112665E+12 | 78220.67 | 01-DEC-16:19 | 0.256887E+12 | 309594.53 | 24-DEC-09:09 |
Annual Sum or Average | 0.138061E+13 | 0.110515E+13 | ||||
Minimum of Months | 0.100472E+12 | 78220.67 | 0.839836E+10 | 6693.18 | ||
Maximum of Months | 0.136045E+12 | 121656.31 | 0.280775E+12 | 329749.88 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.412627E+11 | 0.125945E+11 | 0.164409E+11 | 0.00 | 0.423941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.375436E+11 | 0.103453E+11 | 0.149157E+11 | 0.00 | 0.376611E+11 | 0.00 | 0.00 | 6438879.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.428250E+11 | 0.100554E+11 | 0.168545E+11 | 0.00 | 0.411492E+11 | 0.00 | 0.00 | 19025729.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.404055E+11 | 0.832457E+10 | 0.160165E+11 | 0.00 | 0.376329E+11 | 0.00 | 0.00 | 0.206977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.420438E+11 | 0.733617E+10 | 0.166477E+11 | 0.00 | 0.348350E+11 | 0.00 | 0.00 | 0.160483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.413249E+11 | 0.641365E+10 | 0.162772E+11 | 0.00 | 0.318836E+11 | 0.00 | 0.00 | 0.300447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.411244E+11 | 0.694959E+10 | 0.163871E+11 | 0.00 | 0.318979E+11 | 0.00 | 0.00 | 0.396861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.428250E+11 | 0.803464E+10 | 0.168545E+11 | 0.00 | 0.327495E+11 | 0.00 | 0.00 | 0.324795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.404055E+11 | 0.911529E+10 | 0.160165E+11 | 0.00 | 0.344427E+11 | 0.00 | 0.00 | 0.125461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.412627E+11 | 0.108769E+11 | 0.164409E+11 | 0.00 | 0.380003E+11 | 0.00 | 0.00 | 0.211571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.399008E+11 | 0.118038E+11 | 0.159174E+11 | 0.00 | 0.386256E+11 | 0.00 | 0.00 | 0.119695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.411244E+11 | 0.129327E+11 | 0.163871E+11 | 0.00 | 0.422205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.492048E+12 | 0.114782E+12 | 0.195156E+12 | 0.443492E+12 | 0.00 | 0.135135E+12 | |||||||
Minimum of Months | 0.375436E+11 | 0.641365E+10 | 0.149157E+11 | 0.00 | 0.318836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.428250E+11 | 0.129327E+11 | 0.168545E+11 | 0.00 | 0.423941E+11 | 0.00 | 0.00 | 0.396861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.271776E+12 | 0.00 | 0.899893E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.179648E+12 | 0.00 | 0.822136E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.136349E+12 | 0.00 | 0.916759E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.404562E+11 | 0.00 | 0.869505E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.305641E+10 | 0.00 | 0.878468E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 86519341.13 | 0.00 | 0.834595E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 21528819.08 | 0.00 | 0.837683E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.103478E+09 | 0.00 | 0.838418E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.116523E+10 | 0.00 | 0.809267E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.235751E+11 | 0.00 | 0.846012E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.981403E+11 | 0.00 | 0.836085E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.248040E+12 | 0.00 | 0.884746E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100242E+13 | 0.102736E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 21528819.08 | 0.00 | 0.809267E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.271776E+12 | 0.00 | 0.916759E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 34564.13 | 02-JAN-09:09 | 7321.52 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 25563.98 | 01-JAN-08:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 34564.13 | 01-FEB-09:09 | 7321.52 | 01-FEB-00:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 25563.98 | 01-FEB-08:39 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 34564.13 | 01-MAR-09:09 | 7321.52 | 01-MAR-00:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 25563.98 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 34564.13 | 01-APR-09:09 | 7321.52 | 01-APR-00:10 | 10771.04 | 01-APR-09:09 | 0.00 | 25563.98 | 01-APR-07:19 | 0.00 | 0.00 | 01-APR-00:10 |
May | 34564.13 | 01-MAY-08:09 | 7321.52 | 01-MAY-00:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 25563.98 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 34564.13 | 01-JUN-08:09 | 7321.52 | 01-JUN-00:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 25563.98 | 02-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 34564.13 | 01-JUL-09:09 | 7321.52 | 01-JUL-00:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 25563.98 | 01-JUL-12:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 34564.13 | 01-AUG-08:09 | 7321.52 | 01-AUG-00:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 25563.98 | 01-AUG-11:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 34564.13 | 01-SEP-08:09 | 7321.52 | 01-SEP-00:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 25563.98 | 02-SEP-13:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 34564.13 | 02-OCT-08:09 | 7321.52 | 01-OCT-00:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 25563.98 | 01-OCT-07:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 34564.13 | 01-NOV-08:09 | 7321.52 | 01-NOV-00:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 25563.98 | 01-NOV-07:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 34564.13 | 01-DEC-09:09 | 7321.52 | 01-DEC-00:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 25563.98 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 34564.13 | 7321.52 | 10771.04 | 0.00 | 25563.98 | 0.00 | 0.00 | |||||
Maximum of Months | 34564.13 | 7321.52 | 10771.04 | 0.00 | 25563.98 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 492.19 | 28-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 824.34 | 31-MAR-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21407.50 | 23-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40389.66 | 25-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 57603.38 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 53519.34 | 15-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 50050.33 | 08-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37099.90 | 01-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19044.89 | 19-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6836.29 | 01-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57603.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 78220.67 | 02-JAN-16:30 | 34564.13 | 10771.04 | 7321.52 | 0.00 | 25563.98 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78220.67 | 01-FEB-17:10 | 34564.13 | 10771.04 | 7321.52 | 0.00 | 25563.98 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 78220.67 | 01-MAR-17:00 | 34564.13 | 10771.04 | 7321.52 | 0.00 | 25563.98 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84302.58 | 22-APR-15:00 | 34564.13 | 10771.04 | 0.00 | 0.00 | 25563.98 | 0.00 | 0.00 | 13403.43 | 0.00 |
May | 104442.58 | 25-MAY-14:00 | 34564.13 | 10771.04 | 0.00 | 0.00 | 18717.76 | 0.00 | 0.00 | 40389.66 | 0.00 |
June | 121656.31 | 29-JUN-15:00 | 34564.13 | 10771.04 | 0.00 | 0.00 | 18717.76 | 0.00 | 0.00 | 57603.38 | 0.00 |
July | 117572.26 | 15-JUL-14:20 | 34564.13 | 10771.04 | 0.00 | 0.00 | 18717.76 | 0.00 | 0.00 | 53519.34 | 0.00 |
August | 114103.26 | 08-AUG-14:00 | 34564.13 | 10771.04 | 0.00 | 0.00 | 18717.76 | 0.00 | 0.00 | 50050.33 | 0.00 |
September | 101152.83 | 01-SEP-14:20 | 34564.13 | 10771.04 | 0.00 | 0.00 | 18717.76 | 0.00 | 0.00 | 37099.90 | 0.00 |
October | 86279.68 | 21-OCT-12:30 | 34564.13 | 10771.04 | 0.00 | 0.00 | 25563.98 | 0.00 | 0.00 | 15380.54 | 0.00 |
November | 81856.07 | 01-NOV-16:00 | 34564.13 | 10771.04 | 7321.52 | 0.00 | 25563.98 | 0.00 | 0.00 | 3635.40 | 0.00 |
December | 78220.67 | 01-DEC-16:19 | 34564.13 | 10771.04 | 7321.52 | 0.00 | 25563.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 78220.67 | 34564.13 | 10771.04 | 0.00 | 0.00 | 18717.76 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 121656.31 | 34564.13 | 10771.04 | 7321.52 | 0.00 | 25563.98 | 0.00 | 0.00 | 57603.38 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 327590.78 | 09-JAN-07:10 | 0.00 | 6423.46 | 31-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 304334.57 | 14-FEB-07:10 | 0.00 | 6513.32 | 24-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 251099.65 | 16-MAR-06:10 | 0.00 | 6511.84 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 179496.22 | 05-APR-06:10 | 0.00 | 6323.85 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 92066.37 | 01-MAY-06:10 | 0.00 | 5859.53 | 03-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 3143.14 | 02-JUN-11:00 | 0.00 | 5167.83 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 1630.29 | 08-JUL-11:00 | 0.00 | 5111.66 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 5556.54 | 17-AUG-13:00 | 0.00 | 5078.39 | 01-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 10372.74 | 27-SEP-11:20 | 0.00 | 5085.42 | 29-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 133095.85 | 30-OCT-06:10 | 0.00 | 5134.33 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 233257.48 | 25-NOV-07:10 | 0.00 | 5516.48 | 29-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 305007.86 | 24-DEC-09:09 | 0.00 | 6054.86 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 1630.29 | 0.00 | 5078.39 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 327590.78 | 0.00 | 6513.32 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.50 | 16.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28.00 | 16.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15.50 | 18.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7.00 | 19.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.50 | 20.31 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.45 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.67 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.17 | 19.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36.00 | 16.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.33 | 17.29 | 0.00 | 1.00 | 24.47 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.50 | 20.33 | 0.00 | 0.00 | 0.50 | 24.49 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 16.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.49 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.50 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 24.48 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 24.49 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.48 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 17.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 16.73 | 0.00 | 22.33 | 24.49 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 17.08 | 0.00 | 0.00 | 8.17 | 24.50 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.67 | 16.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18.33 | 17.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10.67 | 18.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4.00 | 20.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 20.39 | 0.00 | 0.00 | 2.17 | 24.48 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.50 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 24.49 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 24.49 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.48 | 0.00 | 0.00 |
October | 1.67 | 20.40 | 0.00 | 0.00 | 0.33 | 24.46 | 0.00 | 0.00 |
November | 7.00 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29.50 | 16.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 104.00 | 17.26 | 0.00 | 25.17 | 24.49 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.67 | 20.40 | 0.00 | 0.00 | 8.50 | 24.50 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.33 | 16.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26.50 | 16.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14.17 | 18.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5.50 | 19.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.50 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.47 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.46 | 0.00 | 0.00 |
October | 2.67 | 20.25 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 0.00 |
November | 10.33 | 19.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36.00 | 16.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.00 | 16.99 | 0.00 | 2.67 | 24.47 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.33 | 20.36 | 0.00 | 0.00 | 1.33 | 24.49 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 18.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 19.53 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 414.00 | 21.11 | 414.00 | 21.11 |
February | 376.00 | 21.11 | 376.00 | 21.11 | 376.00 | 21.11 |
March | 422.00 | 21.11 | 415.00 | 21.11 | 415.00 | 21.11 |
April | 405.00 | 21.71 | 241.33 | 21.12 | 241.33 | 21.12 |
May | 316.17 | 23.16 | 40.00 | 22.88 | 14.67 | 21.14 |
June | 141.17 | 23.58 | 136.67 | 23.89 | 18.17 | 23.88 |
July | 44.17 | 23.70 | 275.33 | 23.89 | 17.33 | 23.89 |
August | 46.50 | 23.57 | 226.00 | 23.89 | 0.00 | 0.00 |
September | 259.50 | 23.31 | 34.17 | 23.89 | 0.00 | 0.00 |
October | 414.00 | 22.04 | 108.17 | 21.11 | 108.17 | 21.11 |
November | 399.00 | 21.19 | 342.50 | 21.11 | 342.50 | 21.11 |
December | 415.00 | 21.11 | 415.00 | 21.11 | 415.00 | 21.11 |
Annual Sum or Average | 3652.50 | 21.78 | 3024.17 | 21.75 | 2362.17 | 21.15 |
Minimum of Months | 44.17 | 21.11 | 34.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 422.00 | 23.70 | 415.00 | 23.89 | 415.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 412.67 | 21.11 | 412.67 | 21.11 |
February | 376.00 | 21.11 | 346.17 | 21.11 | 346.17 | 21.11 |
March | 422.00 | 21.15 | 279.00 | 21.11 | 279.00 | 21.11 |
April | 392.67 | 22.06 | 62.17 | 21.11 | 62.17 | 21.11 |
May | 155.00 | 23.15 | 105.17 | 23.81 | 2.83 | 21.11 |
June | 36.33 | 23.61 | 287.83 | 23.89 | 8.00 | 23.89 |
July | 30.83 | 23.83 | 378.17 | 23.89 | 25.17 | 23.89 |
August | 18.67 | 23.60 | 353.67 | 23.89 | 8.33 | 23.89 |
September | 101.33 | 23.04 | 116.00 | 23.89 | 4.17 | 23.89 |
October | 366.33 | 22.02 | 16.17 | 21.11 | 16.17 | 21.11 |
November | 399.00 | 21.26 | 226.83 | 21.11 | 226.83 | 21.11 |
December | 415.00 | 21.11 | 409.83 | 21.11 | 409.83 | 21.11 |
Annual Sum or Average | 3127.17 | 21.59 | 2993.67 | 22.26 | 1801.33 | 21.18 |
Minimum of Months | 18.67 | 21.11 | 16.17 | 21.11 | 2.83 | 21.11 |
Maximum of Months | 422.00 | 23.83 | 412.67 | 23.89 | 412.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 392.00 | 21.11 | 392.00 | 21.11 |
February | 376.00 | 21.33 | 275.00 | 21.11 | 275.00 | 21.11 |
March | 420.50 | 21.50 | 253.00 | 21.11 | 253.00 | 21.11 |
April | 343.17 | 22.16 | 108.33 | 21.35 | 98.83 | 21.11 |
May | 170.33 | 23.14 | 108.50 | 23.75 | 5.33 | 21.11 |
June | 50.83 | 23.41 | 265.50 | 23.89 | 1.33 | 23.89 |
July | 13.17 | 23.59 | 365.33 | 23.89 | 2.83 | 23.89 |
August | 13.67 | 23.29 | 347.50 | 23.89 | 0.00 | 0.00 |
September | 89.50 | 22.98 | 192.83 | 23.89 | 0.00 | 0.00 |
October | 305.50 | 22.30 | 81.83 | 22.69 | 35.33 | 21.11 |
November | 395.50 | 21.61 | 194.17 | 21.11 | 194.17 | 21.11 |
December | 415.00 | 21.11 | 400.00 | 21.11 | 400.00 | 21.11 |
Annual Sum or Average | 3007.17 | 21.73 | 2984.00 | 22.35 | 1657.83 | 21.12 |
Minimum of Months | 13.17 | 21.11 | 81.83 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 420.50 | 23.59 | 400.00 | 23.89 | 400.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 403.00 | 21.11 | 403.00 | 21.11 |
February | 376.00 | 21.17 | 310.00 | 21.11 | 310.00 | 21.11 |
March | 422.00 | 21.22 | 310.67 | 21.11 | 310.67 | 21.11 |
April | 374.50 | 21.76 | 156.67 | 21.18 | 152.67 | 21.11 |
May | 229.33 | 22.73 | 94.33 | 23.58 | 10.50 | 21.11 |
June | 113.17 | 23.21 | 223.50 | 23.89 | 24.50 | 23.87 |
July | 49.83 | 23.46 | 345.50 | 23.89 | 22.67 | 23.89 |
August | 39.00 | 23.06 | 323.33 | 23.89 | 0.00 | 0.00 |
September | 158.00 | 22.54 | 145.00 | 23.89 | 0.83 | 23.89 |
October | 341.33 | 21.65 | 108.50 | 21.92 | 76.83 | 21.11 |
November | 399.00 | 21.27 | 257.00 | 21.11 | 257.00 | 21.11 |
December | 415.00 | 21.11 | 407.50 | 21.11 | 407.50 | 21.11 |
Annual Sum or Average | 3331.17 | 21.59 | 3085.00 | 22.15 | 1976.17 | 21.18 |
Minimum of Months | 39.00 | 21.11 | 94.33 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 422.00 | 23.46 | 407.50 | 23.89 | 407.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10989 | 13.28792 | -0.8504 | 20.41829 |
February | 376.00000 | 21.10991 | 15.07767 | -0.8027 | 18.75775 |
March | 422.00000 | 21.11463 | 19.28608 | -0.7367 | 16.65464 |
April | 405.00000 | 21.70478 | 23.95549 | -0.4817 | 11.32410 |
May | 418.00000 | 23.32053 | 35.59860 | -0.9197 | 25.29476 |
June | 408.00000 | 23.76841 | 47.77392 | -0.6008 | 13.41526 |
July | 415.00000 | 23.86542 | 51.54393 | -0.4778 | 10.02709 |
August | 422.00000 | 23.84760 | 50.53242 | -0.5165 | 10.89778 |
September | 405.00000 | 23.49519 | 42.67171 | -0.7808 | 19.37903 |
October | 414.00000 | 22.03690 | 33.92297 | -0.2892 | 8.57493 |
November | 399.00000 | 21.18989 | 23.25012 | -0.6493 | 14.42675 |
December | 415.00000 | 21.10989 | 14.77823 | -0.8205 | 19.37963 |
Annual Sum or Average | 4913.00000 | 22.31735 | 31.10816 | -0.6597 | 15.69808 |
Minimum of Months | 376.00000 | 21.10989 | 13.28792 | -0.9197 | 8.57493 |
Maximum of Months | 422.00000 | 23.86542 | 51.54393 | -0.2892 | 25.29476 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09588 | 11.05227 | -0.7419 | 16.77180 |
February | 376.00000 | 21.09763 | 13.16172 | -0.6796 | 14.91245 |
March | 422.00000 | 21.14055 | 17.19367 | -0.5881 | 12.60189 |
April | 405.00000 | 22.11774 | 21.69536 | -0.2427 | 8.13352 |
May | 418.00000 | 23.61570 | 33.56462 | -0.6507 | 15.50277 |
June | 408.00000 | 23.86354 | 46.22187 | -0.4270 | 9.18403 |
July | 415.00000 | 23.88459 | 51.35564 | -0.3604 | 7.90500 |
August | 422.00000 | 23.87503 | 50.23013 | -0.3944 | 8.47287 |
September | 405.00000 | 23.67657 | 40.67776 | -0.5867 | 13.07378 |
October | 414.00000 | 22.24043 | 31.47617 | -0.1366 | 7.29754 |
November | 399.00000 | 21.25477 | 21.10238 | -0.5289 | 11.60481 |
December | 415.00000 | 21.09638 | 12.61619 | -0.7162 | 15.98853 |
Annual Sum or Average | 4913.00000 | 22.42472 | 29.33569 | -0.5035 | 11.77034 |
Minimum of Months | 376.00000 | 21.09588 | 11.05227 | -0.7419 | 7.29754 |
Maximum of Months | 422.00000 | 23.88459 | 51.35564 | -0.1366 | 16.77180 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10977 | 10.29606 | -0.7465 | 17.07597 |
February | 376.00000 | 21.33389 | 12.16037 | -0.6097 | 14.05127 |
March | 422.00000 | 21.50817 | 16.02168 | -0.5192 | 12.37468 |
April | 405.00000 | 22.41365 | 20.61284 | -0.1975 | 8.70243 |
May | 418.00000 | 23.56124 | 32.53883 | -0.6776 | 17.18311 |
June | 408.00000 | 23.81955 | 44.73443 | -0.4479 | 10.05836 |
July | 415.00000 | 23.87678 | 48.83622 | -0.3399 | 7.79768 |
August | 422.00000 | 23.86623 | 47.14621 | -0.3587 | 8.22143 |
September | 405.00000 | 23.66948 | 38.89123 | -0.5431 | 12.91844 |
October | 414.00000 | 22.69963 | 29.74202 | -0.0309 | 7.90540 |
November | 399.00000 | 21.63306 | 20.11068 | -0.4539 | 11.17945 |
December | 415.00000 | 21.11155 | 11.85060 | -0.7398 | 16.81731 |
Annual Sum or Average | 4913.00000 | 22.56035 | 27.87831 | -0.4715 | 12.01623 |
Minimum of Months | 376.00000 | 21.10977 | 10.29606 | -0.7465 | 7.79768 |
Maximum of Months | 422.00000 | 23.87678 | 48.83622 | -0.0309 | 17.18311 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10985 | 10.34385 | -0.7804 | 18.14192 |
February | 376.00000 | 21.16733 | 12.30686 | -0.6788 | 15.36871 |
March | 422.00000 | 21.21953 | 16.28214 | -0.6158 | 13.79855 |
April | 405.00000 | 21.91755 | 21.06217 | -0.3348 | 9.94299 |
May | 418.00000 | 23.23482 | 33.40679 | -0.8244 | 22.61274 |
June | 408.00000 | 23.68226 | 46.74511 | -0.5321 | 12.44731 |
July | 415.00000 | 23.82973 | 51.00838 | -0.3874 | 8.71794 |
August | 422.00000 | 23.80180 | 49.37436 | -0.4132 | 9.35421 |
September | 405.00000 | 23.34354 | 40.49972 | -0.6818 | 17.55719 |
October | 414.00000 | 22.03157 | 30.85318 | -0.2018 | 8.68897 |
November | 399.00000 | 21.27294 | 20.59626 | -0.5647 | 12.68607 |
December | 415.00000 | 21.10978 | 11.90608 | -0.7746 | 17.90343 |
Annual Sum or Average | 4913.00000 | 22.32068 | 28.83900 | -0.5652 | 13.92935 |
Minimum of Months | 376.00000 | 21.10978 | 10.34385 | -0.8244 | 8.68897 |
Maximum of Months | 422.00000 | 23.82973 | 51.00838 | -0.2018 | 22.61274 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.178836E+09 | 54863626.87 | 27.69 | 0.171602E+09 | 7233566.73 | 0.00 | 0.19 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 5022.00 | 23-APR-16:00 | 4387.73 | 23-APR-16:00 | 634.27 | 23-APR-16:00 | 1608.92 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.518007E+10 | 0.153246E+10 | 256.19 | 0.451412E+10 | 0.665949E+09 | 0.00 | 0.65 | 25-MAY-20:33 | 0.00 | 01-MAY-00:10 | 18439.85 | 25-MAY-20:33 | 16009.33 | 25-MAY-20:33 | 3687.59 | 26-MAY-12:00 | 5208.18 | 25-MAY-20:33 | 0.00 | 01-MAY-00:10 |
June | 0.118259E+11 | 0.343731E+10 | 373.38 | 0.920586E+10 | 0.262001E+10 | 0.00 | 0.82 | 30-JUN-01:00 | 0.00 | 01-JUN-00:10 | 27478.66 | 30-JUN-01:00 | 17453.41 | 29-JUN-22:20 | 11578.70 | 30-JUN-03:45 | 7267.92 | 29-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.166398E+11 | 0.477304E+10 | 433.77 | 0.125051E+11 | 0.413477E+10 | 0.00 | 0.74 | 03-JUL-21:00 | 0.00 | 01-JUL-00:05 | 23294.79 | 15-JUL-14:30 | 16501.06 | 23-JUL-19:40 | 8394.18 | 15-JUL-14:10 | 6662.72 | 15-JUL-14:40 | 0.00 | 01-JUL-00:05 |
August | 0.137032E+11 | 0.390021E+10 | 412.65 | 0.103955E+11 | 0.330773E+10 | 0.00 | 0.67 | 08-AUG-15:00 | 0.00 | 01-AUG-00:10 | 21349.82 | 08-AUG-15:00 | 16332.41 | 13-AUG-18:40 | 6106.09 | 08-AUG-15:00 | 6220.31 | 08-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.481299E+10 | 0.139681E+10 | 272.84 | 0.402696E+10 | 0.786035E+09 | 0.00 | 0.55 | 01-SEP-20:25 | 0.00 | 01-SEP-00:05 | 16278.94 | 01-SEP-14:50 | 13201.66 | 01-SEP-15:00 | 4565.41 | 01-SEP-05:05 | 4649.04 | 01-SEP-15:00 | 0.00 | 01-SEP-00:05 |
October | 0.422844E+09 | 0.125990E+09 | 47.25 | 0.385695E+09 | 37148626.54 | 0.00 | 0.21 | 21-OCT-14:50 | 0.00 | 01-OCT-00:10 | 5639.60 | 19-OCT-15:00 | 5220.89 | 21-OCT-14:50 | 696.42 | 19-OCT-15:00 | 1672.75 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.527636E+11 | 0.152207E+11 | 1823.78 | 0.412048E+11 | 0.115589E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.166398E+11 | 0.477304E+10 | 433.77 | 0.125051E+11 | 0.413477E+10 | 0.00 | 0.82 | 0.00 | 27478.66 | 17453.41 | 11578.70 | 7267.92 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.431278E+10 | 0.138088E+10 | 66.97 | 0.419911E+10 | 0.113668E+09 | 0.00 | 0.35 | 23-APR-18:45 | 0.00 | 01-APR-00:10 | 47141.51 | 23-APR-16:00 | 41667.92 | 23-APR-16:00 | 5473.59 | 23-APR-16:00 | 15643.84 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.373412E+11 | 0.117501E+11 | 304.65 | 0.335408E+11 | 0.380035E+10 | 0.00 | 0.67 | 26-MAY-20:20 | 0.00 | 01-MAY-00:10 | 94938.36 | 26-MAY-20:20 | 81173.14 | 26-MAY-20:20 | 21471.03 | 26-MAY-12:00 | 28791.37 | 25-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.703108E+11 | 0.217222E+11 | 379.44 | 0.556352E+11 | 0.146756E+11 | 0.00 | 0.79 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 | 128244.94 | 30-JUN-15:00 | 98643.82 | 09-JUN-05:02 | 41566.01 | 30-JUN-16:00 | 40783.80 | 29-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.921855E+11 | 0.282358E+11 | 434.47 | 0.689460E+11 | 0.232395E+11 | 0.00 | 0.84 | 01-JUL-05:02 | 0.00 | 01-JUL-00:05 | 134351.61 | 01-JUL-05:02 | 118066.03 | 01-JUL-05:02 | 49865.91 | 15-JUL-14:00 | 37898.14 | 15-JUL-14:20 | 0.00 | 01-JUL-00:05 |
August | 0.742537E+11 | 0.226415E+11 | 394.36 | 0.561596E+11 | 0.180941E+11 | 0.00 | 0.94 | 25-AUG-05:01 | 0.00 | 01-AUG-00:10 | 154697.21 | 25-AUG-05:01 | 132509.50 | 25-AUG-05:01 | 34769.95 | 08-AUG-15:00 | 39435.82 | 25-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.264368E+11 | 0.822946E+10 | 246.42 | 0.228066E+11 | 0.363016E+10 | 0.00 | 0.64 | 03-SEP-19:03 | 0.00 | 01-SEP-00:05 | 88256.93 | 03-SEP-19:03 | 79579.69 | 03-SEP-19:03 | 21499.00 | 19-SEP-05:03 | 26202.06 | 03-SEP-19:03 | 0.00 | 01-SEP-00:05 |
October | 0.349499E+10 | 0.111163E+10 | 56.54 | 0.325486E+10 | 0.240132E+09 | 0.00 | 0.29 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 38851.90 | 19-OCT-15:00 | 35263.84 | 19-OCT-15:00 | 5044.47 | 07-OCT-14:00 | 12207.04 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.210418E+09 | 68308485.56 | 4.67 | 0.168782E+09 | 41636263.81 | 0.00 | 0.14 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 17454.81 | 01-NOV-15:00 | 13971.41 | 01-NOV-15:00 | 3483.39 | 01-NOV-15:00 | 5623.38 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.308546E+12 | 0.951398E+11 | 1887.50 | 0.244711E+12 | 0.638352E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.921855E+11 | 0.282358E+11 | 434.47 | 0.689460E+11 | 0.232395E+11 | 0.00 | 0.94 | 0.00 | 154697.21 | 132509.50 | 49865.91 | 40783.80 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 21343402.62 | 6438879.42 | 8.00 | 21343402.62 | 0.00 | 0.00 | 0.10 | 28-FEB-15:10 | 0.00 | 01-FEB-00:02 | 1647.50 | 28-FEB-15:10 | 1647.50 | 28-FEB-15:10 | 0.00 | 01-FEB-00:02 | 492.19 | 28-FEB-15:10 | 0.00 | 01-FEB-00:02 |
March | 63395744.87 | 18994087.64 | 19.67 | 63395744.87 | 0.00 | 0.00 | 0.17 | 31-MAR-14:30 | 0.00 | 01-MAR-00:10 | 2784.99 | 31-MAR-14:30 | 2784.99 | 31-MAR-14:30 | 0.00 | 31-MAR-12:50 | 817.82 | 31-MAR-14:30 | 0.00 | 01-MAR-00:10 |
April | 0.155216E+10 | 0.446414E+09 | 128.54 | 0.154041E+10 | 11751361.65 | 0.00 | 0.46 | 23-APR-18:15 | 0.00 | 01-APR-00:10 | 8540.74 | 23-APR-14:20 | 7906.50 | 23-APR-14:20 | 639.46 | 23-APR-14:40 | 2478.30 | 23-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.614647E+10 | 0.177354E+10 | 355.92 | 0.573215E+10 | 0.414317E+09 | 0.00 | 0.75 | 25-MAY-20:10 | 0.00 | 01-MAY-00:10 | 14776.12 | 25-MAY-20:10 | 13426.17 | 25-MAY-20:10 | 2411.08 | 26-MAY-12:00 | 4056.05 | 25-MAY-20:10 | 0.00 | 01-MAY-00:10 |
June | 0.102797E+11 | 0.294300E+10 | 430.31 | 0.852177E+10 | 0.175789E+10 | 0.00 | 1.00 | 29-JUN-20:10 | 0.00 | 01-JUN-00:10 | 23764.99 | 29-JUN-20:43 | 17307.53 | 29-JUN-20:10 | 6923.39 | 29-JUN-20:43 | 5970.69 | 29-JUN-20:10 | 0.00 | 01-JUN-00:10 |
July | 0.137258E+11 | 0.388998E+10 | 510.84 | 0.109255E+11 | 0.280028E+10 | 0.00 | 1.00 | 23-JUL-18:43 | 0.00 | 01-JUL-00:10 | 23442.09 | 23-JUL-18:43 | 17813.44 | 23-JUL-18:43 | 6300.12 | 03-JUL-20:10 | 5854.07 | 23-JUL-18:43 | 0.00 | 01-JUL-00:05 |
August | 0.125955E+11 | 0.352064E+10 | 504.18 | 0.102569E+11 | 0.233861E+10 | 0.00 | 0.96 | 08-AUG-20:43 | 0.00 | 01-AUG-00:15 | 22069.35 | 08-AUG-20:43 | 17024.80 | 08-AUG-20:43 | 5044.55 | 08-AUG-20:43 | 5299.16 | 08-AUG-20:43 | 0.00 | 01-AUG-00:10 |
September | 0.665354E+10 | 0.186896E+10 | 366.40 | 0.607450E+10 | 0.579033E+09 | 0.00 | 0.85 | 01-SEP-20:43 | 0.00 | 01-SEP-00:05 | 17902.78 | 01-SEP-20:43 | 15135.50 | 01-SEP-20:43 | 2767.28 | 01-SEP-20:43 | 4449.23 | 01-SEP-20:43 | 0.00 | 01-SEP-00:05 |
October | 0.211383E+10 | 0.595933E+09 | 158.69 | 0.205349E+10 | 60338554.91 | 0.00 | 0.59 | 22-OCT-18:10 | 0.00 | 01-OCT-00:10 | 11106.02 | 19-OCT-14:10 | 10592.51 | 19-OCT-14:10 | 787.09 | 07-OCT-13:50 | 2967.18 | 19-OCT-14:20 | 0.00 | 01-OCT-00:10 |
November | 0.159747E+09 | 47263078.95 | 23.64 | 0.147688E+09 | 12059170.31 | 0.00 | 0.23 | 17-NOV-13:30 | 0.00 | 01-NOV-00:10 | 3876.82 | 17-NOV-13:30 | 3876.82 | 17-NOV-13:30 | 511.57 | 01-NOV-15:00 | 1120.09 | 17-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.533114E+11 | 0.151112E+11 | 2506.20 | 0.453371E+11 | 0.797428E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.137258E+11 | 0.388998E+10 | 510.84 | 0.109255E+11 | 0.280028E+10 | 0.00 | 1.00 | 0.00 | 23764.99 | 17813.44 | 6923.39 | 5970.69 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 103379.17 | 31641.80 | 0.50 | 103379.17 | 0.00 | 0.00 | 0.01 | 31-MAR-14:50 | 0.00 | 01-MAR-00:10 | 90.93 | 31-MAR-14:50 | 90.93 | 31-MAR-14:50 | 0.00 | 01-MAR-00:10 | 27.82 | 31-MAR-14:50 | 0.00 | 01-MAR-00:10 |
April | 0.642049E+09 | 0.187612E+09 | 74.27 | 0.630498E+09 | 11550208.51 | 0.00 | 0.42 | 23-APR-18:20 | 0.00 | 01-APR-00:10 | 6107.18 | 23-APR-14:20 | 5836.46 | 23-APR-18:20 | 596.49 | 23-APR-14:30 | 1882.69 | 23-APR-18:20 | 0.00 | 01-APR-00:10 |
May | 0.339128E+10 | 0.992230E+09 | 253.22 | 0.305115E+10 | 0.340125E+09 | 0.00 | 0.67 | 25-MAY-20:10 | 0.00 | 01-MAY-00:10 | 10789.15 | 25-MAY-20:10 | 9491.07 | 25-MAY-20:10 | 2194.60 | 26-MAY-12:00 | 3063.56 | 25-MAY-20:10 | 0.00 | 01-MAY-00:10 |
June | 0.672246E+10 | 0.194215E+10 | 359.29 | 0.530025E+10 | 0.142221E+10 | 0.00 | 1.00 | 29-JUN-20:10 | 0.00 | 01-JUN-00:10 | 20182.61 | 29-JUN-20:43 | 13833.05 | 29-JUN-20:10 | 6711.33 | 29-JUN-20:43 | 5042.77 | 29-JUN-20:10 | 0.00 | 01-JUN-00:10 |
July | 0.978921E+10 | 0.278736E+10 | 439.11 | 0.740567E+10 | 0.238354E+10 | 0.00 | 1.00 | 23-JUL-18:10 | 0.00 | 01-JUL-00:05 | 19846.98 | 23-JUL-18:43 | 14621.31 | 23-JUL-18:10 | 5925.51 | 03-JUL-20:10 | 5014.82 | 23-JUL-18:10 | 0.00 | 01-JUL-00:05 |
August | 0.860729E+10 | 0.241717E+10 | 421.90 | 0.668302E+10 | 0.192427E+10 | 0.00 | 0.94 | 08-AUG-20:43 | 0.00 | 01-AUG-00:10 | 18144.93 | 08-AUG-20:43 | 13254.82 | 08-AUG-20:43 | 4890.12 | 08-AUG-20:43 | 4387.52 | 08-AUG-20:43 | 0.00 | 01-AUG-00:10 |
September | 0.372683E+10 | 0.105086E+10 | 252.63 | 0.332753E+10 | 0.399296E+09 | 0.00 | 0.83 | 01-SEP-20:43 | 0.00 | 01-SEP-00:15 | 14496.52 | 01-SEP-20:43 | 11616.99 | 01-SEP-20:43 | 2879.53 | 01-SEP-20:43 | 3643.18 | 01-SEP-20:43 | 0.00 | 01-SEP-00:05 |
October | 0.100292E+10 | 0.282153E+09 | 75.24 | 0.965522E+09 | 37401729.32 | 0.00 | 0.52 | 19-OCT-14:20 | 0.00 | 01-OCT-00:10 | 8445.01 | 19-OCT-14:20 | 7911.33 | 19-OCT-14:20 | 690.40 | 22-OCT-12:40 | 2289.63 | 19-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 13626539.39 | 4123054.36 | 5.67 | 12922593.57 | 703945.82 | 0.00 | 0.08 | 17-NOV-13:50 | 0.00 | 01-NOV-00:10 | 1104.06 | 17-NOV-13:50 | 1104.06 | 17-NOV-13:50 | 137.48 | 01-NOV-15:00 | 331.55 | 17-NOV-13:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.338958E+11 | 0.966368E+10 | 1881.83 | 0.273767E+11 | 0.651910E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.978921E+10 | 0.278736E+10 | 439.11 | 0.740567E+10 | 0.238354E+10 | 0.00 | 1.00 | 0.00 | 20182.61 | 14621.31 | 6711.33 | 5042.77 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.61 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.70 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 34.94 | 78.92 | 6.50 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 71.91 | 51.85 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 103.97 | 30.89 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 115.82 | 22.96 | 3.50 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.27 | 20.77 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 92.98 | 23.30 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.49 | 35.68 | 0.00 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 24.94 | 52.96 | 5.00 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.73 | 78.14 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.24 | 62.61 | 22.67 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.27 | 129.61 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.61 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.70 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 34.94 | 78.92 | 6.50 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 71.91 | 51.85 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 103.97 | 30.89 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 115.82 | 22.96 | 3.50 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.27 | 20.77 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 92.98 | 23.30 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.49 | 35.68 | 0.00 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 24.94 | 52.96 | 5.00 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.73 | 78.14 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.24 | 62.61 | 22.67 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.27 | 129.61 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.61 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.70 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 34.94 | 78.92 | 6.50 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 71.91 | 51.85 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 103.97 | 30.89 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 115.82 | 22.96 | 3.50 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.27 | 20.77 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 92.98 | 23.30 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.49 | 35.68 | 0.00 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 24.94 | 52.96 | 5.00 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.73 | 78.14 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.24 | 62.61 | 22.67 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.27 | 129.61 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.61 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.70 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 34.94 | 78.92 | 6.50 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 71.91 | 51.85 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 103.97 | 30.89 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 115.82 | 22.96 | 3.50 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.27 | 20.77 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 92.98 | 23.30 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.49 | 35.68 | 0.00 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 24.94 | 52.96 | 5.00 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.73 | 78.14 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.24 | 62.61 | 22.67 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.27 | 129.61 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.61 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.70 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 34.94 | 78.92 | 6.50 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 71.91 | 51.85 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 103.97 | 30.89 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 115.82 | 22.96 | 3.50 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.27 | 20.77 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 92.98 | 23.30 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.49 | 35.68 | 0.00 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 24.94 | 52.96 | 5.00 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.73 | 78.14 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.24 | 62.61 | 22.67 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.27 | 129.61 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.61 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.70 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 34.94 | 78.92 | 6.50 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 71.91 | 51.85 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 103.97 | 30.89 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 115.82 | 22.96 | 3.50 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.27 | 20.77 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 92.98 | 23.30 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.49 | 35.68 | 0.00 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 24.94 | 52.96 | 5.00 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.73 | 78.14 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.24 | 62.61 | 22.67 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.27 | 129.61 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.61 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.70 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 34.94 | 78.92 | 6.50 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 71.91 | 51.85 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 103.97 | 30.89 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 115.82 | 22.96 | 3.50 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.27 | 20.77 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 92.98 | 23.30 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.49 | 35.68 | 0.00 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 24.94 | 52.96 | 5.00 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.73 | 78.14 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.24 | 62.61 | 22.67 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.27 | 129.61 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.61 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.70 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 34.94 | 78.92 | 6.50 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 71.91 | 51.85 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 103.97 | 30.89 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 115.82 | 22.96 | 3.50 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.27 | 20.77 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 92.98 | 23.30 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.49 | 35.68 | 0.00 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 24.94 | 52.96 | 5.00 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.73 | 78.14 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.24 | 62.61 | 22.67 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.27 | 129.61 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1542.81 | 1073.16 | 469.65 | 1164.43 | 1794.43 | 0.00 | 0.00 | 744.00 |
February | 1954.07 | 1319.82 | 634.25 | 1663.18 | 1508.33 | 0.00 | 0.00 | 672.00 |
March | 1722.64 | 1090.48 | 632.16 | 1420.27 | 1268.35 | 0.00 | 0.00 | 744.00 |
April | 1560.16 | 846.91 | 713.25 | 1302.67 | 844.93 | 0.00 | 0.00 | 720.00 |
May | 1311.30 | 448.16 | 863.13 | 1119.46 | 485.76 | 0.00 | 0.00 | 744.00 |
June | 1176.59 | 313.47 | 863.12 | 1064.52 | 336.17 | 0.00 | 0.00 | 720.00 |
July | 1286.39 | 407.38 | 879.02 | 1236.55 | 305.25 | 0.00 | 0.00 | 744.00 |
August | 1373.97 | 574.69 | 799.28 | 1356.88 | 366.70 | 0.00 | 0.00 | 744.00 |
September | 1472.28 | 784.33 | 687.95 | 1416.39 | 590.37 | 0.00 | 0.00 | 720.00 |
October | 1257.16 | 739.54 | 517.61 | 1110.63 | 855.21 | 0.00 | 0.00 | 744.00 |
November | 1119.24 | 702.32 | 416.91 | 910.31 | 1167.67 | 0.00 | 0.00 | 720.00 |
December | 1191.25 | 780.99 | 410.25 | 821.87 | 1744.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1410.45 | 753.18 | 657.26 | 1212.38 | 936.57 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1119.24 | 313.47 | 410.25 | 821.87 | 305.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1954.07 | 1319.82 | 879.02 | 1663.18 | 1794.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1542.81 | 1073.16 | 469.65 | 1161.98 | 1792.40 | 0.00 | 0.00 | 744.00 |
February | 1954.07 | 1319.82 | 634.25 | 1663.89 | 1498.84 | 0.00 | 0.00 | 672.00 |
March | 1722.64 | 1090.48 | 632.16 | 1423.90 | 1251.15 | 0.00 | 0.00 | 744.00 |
April | 1560.16 | 846.91 | 713.25 | 1309.68 | 820.05 | 0.00 | 0.00 | 720.00 |
May | 1311.30 | 448.16 | 863.13 | 1124.67 | 467.52 | 0.00 | 0.00 | 744.00 |
June | 1176.59 | 313.47 | 863.12 | 1065.57 | 324.24 | 0.00 | 0.00 | 720.00 |
July | 1286.39 | 407.38 | 879.02 | 1232.93 | 300.37 | 0.00 | 0.00 | 744.00 |
August | 1373.97 | 574.69 | 799.28 | 1353.72 | 360.75 | 0.00 | 0.00 | 744.00 |
September | 1472.28 | 784.33 | 687.95 | 1419.41 | 573.14 | 0.00 | 0.00 | 720.00 |
October | 1257.16 | 739.54 | 517.61 | 1119.31 | 824.09 | 0.00 | 0.00 | 744.00 |
November | 1119.24 | 702.32 | 416.91 | 914.27 | 1147.78 | 0.00 | 0.00 | 720.00 |
December | 1191.25 | 780.99 | 410.25 | 820.20 | 1742.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1410.45 | 753.18 | 657.26 | 1214.23 | 922.80 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1119.24 | 313.47 | 410.25 | 820.20 | 300.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1954.07 | 1319.82 | 879.02 | 1663.89 | 1792.40 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.46 | 220.82 | 96.64 | 231.09 | 376.65 | 0.00 | 0.00 | 744.00 |
February | 402.08 | 271.57 | 130.51 | 331.00 | 314.62 | 0.00 | 0.00 | 672.00 |
March | 354.46 | 224.38 | 130.08 | 284.15 | 264.82 | 0.00 | 0.00 | 744.00 |
April | 321.03 | 174.26 | 146.76 | 263.25 | 170.91 | 0.00 | 0.00 | 720.00 |
May | 269.82 | 92.22 | 177.60 | 228.52 | 94.25 | 0.00 | 0.00 | 744.00 |
June | 242.10 | 64.50 | 177.60 | 214.83 | 65.12 | 0.00 | 0.00 | 720.00 |
July | 264.69 | 83.82 | 180.87 | 246.79 | 62.74 | 0.00 | 0.00 | 744.00 |
August | 282.71 | 118.25 | 164.46 | 275.27 | 73.66 | 0.00 | 0.00 | 744.00 |
September | 302.94 | 161.39 | 141.56 | 290.29 | 114.53 | 0.00 | 0.00 | 720.00 |
October | 258.68 | 152.17 | 106.51 | 225.89 | 169.47 | 0.00 | 0.00 | 744.00 |
November | 230.30 | 144.51 | 85.79 | 180.51 | 242.45 | 0.00 | 0.00 | 720.00 |
December | 245.12 | 160.70 | 84.42 | 162.63 | 368.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 290.22 | 154.98 | 135.24 | 243.89 | 192.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 230.30 | 64.50 | 84.42 | 162.63 | 62.74 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 402.08 | 271.57 | 180.87 | 331.00 | 376.65 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2751613.22 | 0.347141E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36368687.33 | 0.246028E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93596583.09 | 0.211391E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.186383E+09 | 0.134395E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.278467E+09 | 82736707.83 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300198E+09 | 59517897.97 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327497E+09 | 55624074.96 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249035E+09 | 62397828.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.154209E+09 | 92470795.13 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 66803108.57 | 0.141846E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 14840428.78 | 0.202549E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 0.338373E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171054E+10 | 0.197447E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 55624074.96 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327497E+09 | 0.347141E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2751613.22 | 0.347141E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36368687.33 | 0.246028E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93596583.09 | 0.211391E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.186383E+09 | 0.134395E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.278467E+09 | 82736707.83 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300198E+09 | 59517897.97 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327497E+09 | 55624074.96 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249035E+09 | 62397828.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.154209E+09 | 92470795.13 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 66803108.57 | 0.141846E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 14840428.78 | 0.202549E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 0.338373E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171054E+10 | 0.197447E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 55624074.96 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327497E+09 | 0.347141E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2751613.22 | 0.347141E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36368687.33 | 0.246028E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93596583.09 | 0.211391E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.186383E+09 | 0.134395E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.278467E+09 | 82736707.83 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300198E+09 | 59517897.97 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327497E+09 | 55624074.96 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249035E+09 | 62397828.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.154209E+09 | 92470795.13 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 66803108.57 | 0.141846E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 14840428.78 | 0.202549E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 0.338373E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171054E+10 | 0.197447E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 55624074.96 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327497E+09 | 0.347141E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2751613.22 | 0.347141E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36368687.33 | 0.246028E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93596583.09 | 0.211391E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.186383E+09 | 0.134395E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.278467E+09 | 82736707.83 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300198E+09 | 59517897.97 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327497E+09 | 55624074.96 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249035E+09 | 62397828.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.154209E+09 | 92470795.13 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 66803108.57 | 0.141846E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 14840428.78 | 0.202549E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 0.338373E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171054E+10 | 0.197447E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 55624074.96 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327497E+09 | 0.347141E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2751613.22 | 0.347141E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36368687.33 | 0.246028E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93596583.09 | 0.211391E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.186383E+09 | 0.134395E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.278467E+09 | 82736707.83 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300198E+09 | 59517897.97 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327497E+09 | 55624074.96 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249035E+09 | 62397828.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.154209E+09 | 92470795.13 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 66803108.57 | 0.141846E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 14840428.78 | 0.202549E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 0.338373E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171054E+10 | 0.197447E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 55624074.96 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327497E+09 | 0.347141E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2751613.22 | 0.347141E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36368687.33 | 0.246028E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93596583.09 | 0.211391E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.186383E+09 | 0.134395E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.278467E+09 | 82736707.83 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300198E+09 | 59517897.97 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327497E+09 | 55624074.96 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249035E+09 | 62397828.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.154209E+09 | 92470795.13 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 66803108.57 | 0.141846E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 14840428.78 | 0.202549E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 0.338373E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171054E+10 | 0.197447E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 55624074.96 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327497E+09 | 0.347141E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2751613.22 | 0.347141E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36368687.33 | 0.246028E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93596583.09 | 0.211391E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.186383E+09 | 0.134395E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.278467E+09 | 82736707.83 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300198E+09 | 59517897.97 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327497E+09 | 55624074.96 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249035E+09 | 62397828.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.154209E+09 | 92470795.13 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 66803108.57 | 0.141846E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 14840428.78 | 0.202549E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 0.338373E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171054E+10 | 0.197447E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 55624074.96 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327497E+09 | 0.347141E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2751613.22 | 0.347141E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36368687.33 | 0.246028E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93596583.09 | 0.211391E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.186383E+09 | 0.134395E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.278467E+09 | 82736707.83 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300198E+09 | 59517897.97 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327497E+09 | 55624074.96 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249035E+09 | 62397828.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.154209E+09 | 92470795.13 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 66803108.57 | 0.141846E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 14840428.78 | 0.202549E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 0.338373E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171054E+10 | 0.197447E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 394806.97 | 55624074.96 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327497E+09 | 0.347141E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.413226E+10 | 0.287434E+10 | 0.125792E+10 | 0.311882E+10 | 0.480620E+10 |
February | 0.472728E+10 | 0.319290E+10 | 0.153439E+10 | 0.402356E+10 | 0.364894E+10 |
March | 0.461392E+10 | 0.292075E+10 | 0.169318E+10 | 0.380405E+10 | 0.339715E+10 |
April | 0.404395E+10 | 0.219520E+10 | 0.184875E+10 | 0.337651E+10 | 0.219005E+10 |
May | 0.351217E+10 | 0.120036E+10 | 0.231181E+10 | 0.299836E+10 | 0.130106E+10 |
June | 0.304972E+10 | 0.812512E+09 | 0.223721E+10 | 0.275923E+10 | 0.871362E+09 |
July | 0.344548E+10 | 0.109112E+10 | 0.235436E+10 | 0.331197E+10 | 0.817588E+09 |
August | 0.368004E+10 | 0.153925E+10 | 0.214079E+10 | 0.363428E+10 | 0.982170E+09 |
September | 0.381615E+10 | 0.203299E+10 | 0.178317E+10 | 0.367129E+10 | 0.153023E+10 |
October | 0.336717E+10 | 0.198079E+10 | 0.138638E+10 | 0.297471E+10 | 0.229061E+10 |
November | 0.290106E+10 | 0.182043E+10 | 0.108064E+10 | 0.235952E+10 | 0.302660E+10 |
December | 0.319063E+10 | 0.209181E+10 | 0.109882E+10 | 0.220130E+10 | 0.467378E+10 |
Annual Sum or Average | 0.444798E+11 | 0.237524E+11 | 0.207274E+11 | 0.382336E+11 | 0.295357E+11 |
Minimum of Months | 0.290106E+10 | 0.812512E+09 | 0.108064E+10 | 0.220130E+10 | 0.817588E+09 |
Maximum of Months | 0.472728E+10 | 0.319290E+10 | 0.235436E+10 | 0.402356E+10 | 0.480620E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.413226E+10 | 0.287434E+10 | 0.125792E+10 | 0.311225E+10 | 0.480075E+10 |
February | 0.472728E+10 | 0.319290E+10 | 0.153439E+10 | 0.402527E+10 | 0.362598E+10 |
March | 0.461392E+10 | 0.292075E+10 | 0.169318E+10 | 0.381379E+10 | 0.335108E+10 |
April | 0.404395E+10 | 0.219520E+10 | 0.184875E+10 | 0.339470E+10 | 0.212557E+10 |
May | 0.351217E+10 | 0.120036E+10 | 0.231181E+10 | 0.301232E+10 | 0.125221E+10 |
June | 0.304972E+10 | 0.812512E+09 | 0.223721E+10 | 0.276195E+10 | 0.840423E+09 |
July | 0.344548E+10 | 0.109112E+10 | 0.235436E+10 | 0.330228E+10 | 0.804503E+09 |
August | 0.368004E+10 | 0.153925E+10 | 0.214079E+10 | 0.362581E+10 | 0.966230E+09 |
September | 0.381615E+10 | 0.203299E+10 | 0.178317E+10 | 0.367912E+10 | 0.148559E+10 |
October | 0.336717E+10 | 0.198079E+10 | 0.138638E+10 | 0.299796E+10 | 0.220724E+10 |
November | 0.290106E+10 | 0.182043E+10 | 0.108064E+10 | 0.236980E+10 | 0.297505E+10 |
December | 0.319063E+10 | 0.209181E+10 | 0.109882E+10 | 0.219682E+10 | 0.466690E+10 |
Annual Sum or Average | 0.444798E+11 | 0.237524E+11 | 0.207274E+11 | 0.382921E+11 | 0.291015E+11 |
Minimum of Months | 0.290106E+10 | 0.812512E+09 | 0.108064E+10 | 0.219682E+10 | 0.804503E+09 |
Maximum of Months | 0.472728E+10 | 0.319290E+10 | 0.235436E+10 | 0.402527E+10 | 0.480075E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.850274E+09 | 0.591437E+09 | 0.258836E+09 | 0.618957E+09 | 0.100883E+10 |
February | 0.972707E+09 | 0.656985E+09 | 0.315722E+09 | 0.800762E+09 | 0.761124E+09 |
March | 0.949382E+09 | 0.600986E+09 | 0.348396E+09 | 0.761068E+09 | 0.709283E+09 |
April | 0.832101E+09 | 0.451694E+09 | 0.380406E+09 | 0.682335E+09 | 0.443008E+09 |
May | 0.722681E+09 | 0.246992E+09 | 0.475689E+09 | 0.612073E+09 | 0.252441E+09 |
June | 0.627525E+09 | 0.167186E+09 | 0.460339E+09 | 0.556848E+09 | 0.168782E+09 |
July | 0.708958E+09 | 0.224513E+09 | 0.484444E+09 | 0.661003E+09 | 0.168056E+09 |
August | 0.757222E+09 | 0.316722E+09 | 0.440500E+09 | 0.737277E+09 | 0.197295E+09 |
September | 0.785229E+09 | 0.418316E+09 | 0.366912E+09 | 0.752421E+09 | 0.296866E+09 |
October | 0.692844E+09 | 0.407576E+09 | 0.285267E+09 | 0.605025E+09 | 0.453918E+09 |
November | 0.596936E+09 | 0.374579E+09 | 0.222357E+09 | 0.467889E+09 | 0.628438E+09 |
December | 0.656519E+09 | 0.430420E+09 | 0.226098E+09 | 0.435599E+09 | 0.985960E+09 |
Annual Sum or Average | 0.915238E+10 | 0.488741E+10 | 0.426497E+10 | 0.769126E+10 | 0.607400E+10 |
Minimum of Months | 0.596936E+09 | 0.167186E+09 | 0.222357E+09 | 0.435599E+09 | 0.168056E+09 |
Maximum of Months | 0.972707E+09 | 0.656985E+09 | 0.484444E+09 | 0.800762E+09 | 0.100883E+10 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.22 | 1036.86 | 182.26 | 67.23 | 115.02 | 0.00 | 0.00 |
February | 120.27 | 813.59 | 321.63 | 152.44 | 169.19 | 0.00 | 0.00 |
March | 279.56 | 631.40 | 452.47 | 256.34 | 196.13 | 0.00 | 0.00 |
April | 575.26 | 414.80 | 660.85 | 417.17 | 243.69 | 0.00 | 0.00 |
May | 831.74 | 247.12 | 807.24 | 453.29 | 353.95 | 0.00 | 0.00 |
June | 926.54 | 183.70 | 847.59 | 486.40 | 361.18 | 0.00 | 0.00 |
July | 978.19 | 166.14 | 870.16 | 518.27 | 351.90 | 0.00 | 0.00 |
August | 743.83 | 186.37 | 687.95 | 385.50 | 302.45 | 0.00 | 0.00 |
September | 475.95 | 285.40 | 502.48 | 259.33 | 243.14 | 0.00 | 0.00 |
October | 199.53 | 423.67 | 301.04 | 122.02 | 179.01 | 0.00 | 0.00 |
November | 45.80 | 625.15 | 175.65 | 55.68 | 119.97 | 0.00 | 0.00 |
December | 1.18 | 1010.67 | 141.64 | 39.28 | 102.36 | 0.00 | 0.00 |
Annual Sum or Average | 433.93 | 500.88 | 496.79 | 268.29 | 228.50 | 0.00 | 0.00 |
Minimum of Months | 1.18 | 166.14 | 141.64 | 39.28 | 102.36 | 0.00 | 0.00 |
Maximum of Months | 978.19 | 1036.86 | 870.16 | 518.27 | 361.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1164.43 | 1794.43 | 1542.81 | 1073.16 | 469.65 | 0.00 | 0.00 |
February | 1663.18 | 1508.33 | 1954.07 | 1319.82 | 634.25 | 0.00 | 0.00 |
March | 1420.27 | 1268.35 | 1722.64 | 1090.48 | 632.16 | 0.00 | 0.00 |
April | 1302.67 | 844.93 | 1560.16 | 846.91 | 713.25 | 0.00 | 0.00 |
May | 1119.46 | 485.76 | 1311.30 | 448.16 | 863.13 | 0.00 | 0.00 |
June | 1064.52 | 336.17 | 1176.59 | 313.47 | 863.12 | 0.00 | 0.00 |
July | 1236.55 | 305.25 | 1286.39 | 407.38 | 879.02 | 0.00 | 0.00 |
August | 1356.88 | 366.70 | 1373.97 | 574.69 | 799.28 | 0.00 | 0.00 |
September | 1416.39 | 590.37 | 1472.28 | 784.33 | 687.95 | 0.00 | 0.00 |
October | 1110.63 | 855.21 | 1257.16 | 739.54 | 517.61 | 0.00 | 0.00 |
November | 910.31 | 1167.67 | 1119.24 | 702.32 | 416.91 | 0.00 | 0.00 |
December | 821.87 | 1744.99 | 1191.25 | 780.99 | 410.25 | 0.00 | 0.00 |
Annual Sum or Average | 1212.38 | 936.57 | 1410.45 | 753.18 | 657.26 | 0.00 | 0.00 |
Minimum of Months | 821.87 | 305.25 | 1119.24 | 313.47 | 410.25 | 0.00 | 0.00 |
Maximum of Months | 1663.18 | 1794.43 | 1954.07 | 1319.82 | 879.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1161.98 | 1792.40 | 1542.81 | 1073.16 | 469.65 | 0.00 | 0.00 |
February | 1663.89 | 1498.84 | 1954.07 | 1319.82 | 634.25 | 0.00 | 0.00 |
March | 1423.90 | 1251.15 | 1722.64 | 1090.48 | 632.16 | 0.00 | 0.00 |
April | 1309.68 | 820.05 | 1560.16 | 846.91 | 713.25 | 0.00 | 0.00 |
May | 1124.67 | 467.52 | 1311.30 | 448.16 | 863.13 | 0.00 | 0.00 |
June | 1065.57 | 324.24 | 1176.59 | 313.47 | 863.12 | 0.00 | 0.00 |
July | 1232.93 | 300.37 | 1286.39 | 407.38 | 879.02 | 0.00 | 0.00 |
August | 1353.72 | 360.75 | 1373.97 | 574.69 | 799.28 | 0.00 | 0.00 |
September | 1419.41 | 573.14 | 1472.28 | 784.33 | 687.95 | 0.00 | 0.00 |
October | 1119.31 | 824.09 | 1257.16 | 739.54 | 517.61 | 0.00 | 0.00 |
November | 914.27 | 1147.78 | 1119.24 | 702.32 | 416.91 | 0.00 | 0.00 |
December | 820.20 | 1742.42 | 1191.25 | 780.99 | 410.25 | 0.00 | 0.00 |
Annual Sum or Average | 1214.23 | 922.80 | 1410.45 | 753.18 | 657.26 | 0.00 | 0.00 |
Minimum of Months | 820.20 | 300.37 | 1119.24 | 313.47 | 410.25 | 0.00 | 0.00 |
Maximum of Months | 1663.89 | 1792.40 | 1954.07 | 1319.82 | 879.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 231.09 | 376.65 | 317.46 | 220.82 | 96.64 | 0.00 | 0.00 |
February | 331.00 | 314.62 | 402.08 | 271.57 | 130.51 | 0.00 | 0.00 |
March | 284.15 | 264.82 | 354.46 | 224.38 | 130.08 | 0.00 | 0.00 |
April | 263.25 | 170.91 | 321.03 | 174.26 | 146.76 | 0.00 | 0.00 |
May | 228.52 | 94.25 | 269.82 | 92.22 | 177.60 | 0.00 | 0.00 |
June | 214.83 | 65.12 | 242.10 | 64.50 | 177.60 | 0.00 | 0.00 |
July | 246.79 | 62.74 | 264.69 | 83.82 | 180.87 | 0.00 | 0.00 |
August | 275.27 | 73.66 | 282.71 | 118.25 | 164.46 | 0.00 | 0.00 |
September | 290.29 | 114.53 | 302.94 | 161.39 | 141.56 | 0.00 | 0.00 |
October | 225.89 | 169.47 | 258.68 | 152.17 | 106.51 | 0.00 | 0.00 |
November | 180.51 | 242.45 | 230.30 | 144.51 | 85.79 | 0.00 | 0.00 |
December | 162.63 | 368.12 | 245.12 | 160.70 | 84.42 | 0.00 | 0.00 |
Annual Sum or Average | 243.89 | 192.61 | 290.22 | 154.98 | 135.24 | 0.00 | 0.00 |
Minimum of Months | 162.63 | 62.74 | 230.30 | 64.50 | 84.42 | 0.00 | 0.00 |
Maximum of Months | 331.00 | 376.65 | 402.08 | 271.57 | 180.87 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 22012905.77 | 0.277713E+10 | 0.488160E+09 | 0.180078E+09 | 0.308082E+09 | 0.00 | 0.00 |
February | 0.290949E+09 | 0.196823E+10 | 0.778076E+09 | 0.368773E+09 | 0.409303E+09 | 0.00 | 0.00 |
March | 0.748773E+09 | 0.169113E+10 | 0.121189E+10 | 0.686580E+09 | 0.525307E+09 | 0.00 | 0.00 |
April | 0.149106E+10 | 0.107516E+10 | 0.171293E+10 | 0.108129E+10 | 0.631635E+09 | 0.00 | 0.00 |
May | 0.222774E+10 | 0.661894E+09 | 0.216212E+10 | 0.121410E+10 | 0.948021E+09 | 0.00 | 0.00 |
June | 0.240158E+10 | 0.476143E+09 | 0.219694E+10 | 0.126075E+10 | 0.936188E+09 | 0.00 | 0.00 |
July | 0.261998E+10 | 0.444993E+09 | 0.233065E+10 | 0.138813E+10 | 0.942516E+09 | 0.00 | 0.00 |
August | 0.199228E+10 | 0.499183E+09 | 0.184260E+10 | 0.103253E+10 | 0.810078E+09 | 0.00 | 0.00 |
September | 0.123367E+10 | 0.739766E+09 | 0.130242E+10 | 0.672196E+09 | 0.630220E+09 | 0.00 | 0.00 |
October | 0.534425E+09 | 0.113477E+10 | 0.806295E+09 | 0.326826E+09 | 0.479469E+09 | 0.00 | 0.00 |
November | 0.118723E+09 | 0.162039E+10 | 0.455285E+09 | 0.144321E+09 | 0.310964E+09 | 0.00 | 0.00 |
December | 3158455.75 | 0.270698E+10 | 0.379362E+09 | 0.105199E+09 | 0.274163E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136844E+11 | 0.157958E+11 | 0.156667E+11 | 0.846078E+10 | 0.720595E+10 | 0.00 | 0.00 |
Minimum of Months | 3158455.75 | 0.444993E+09 | 0.379362E+09 | 0.105199E+09 | 0.274163E+09 | 0.00 | 0.00 |
Maximum of Months | 0.261998E+10 | 0.277713E+10 | 0.233065E+10 | 0.138813E+10 | 0.948021E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.311882E+10 | 0.480620E+10 | 0.413226E+10 | 0.287434E+10 | 0.125792E+10 | 0.00 | 0.00 |
February | 0.402356E+10 | 0.364894E+10 | 0.472728E+10 | 0.319290E+10 | 0.153439E+10 | 0.00 | 0.00 |
March | 0.380405E+10 | 0.339715E+10 | 0.461392E+10 | 0.292075E+10 | 0.169318E+10 | 0.00 | 0.00 |
April | 0.337651E+10 | 0.219005E+10 | 0.404395E+10 | 0.219520E+10 | 0.184875E+10 | 0.00 | 0.00 |
May | 0.299836E+10 | 0.130106E+10 | 0.351217E+10 | 0.120036E+10 | 0.231181E+10 | 0.00 | 0.00 |
June | 0.275923E+10 | 0.871362E+09 | 0.304972E+10 | 0.812512E+09 | 0.223721E+10 | 0.00 | 0.00 |
July | 0.331197E+10 | 0.817588E+09 | 0.344548E+10 | 0.109112E+10 | 0.235436E+10 | 0.00 | 0.00 |
August | 0.363428E+10 | 0.982170E+09 | 0.368004E+10 | 0.153925E+10 | 0.214079E+10 | 0.00 | 0.00 |
September | 0.367129E+10 | 0.153023E+10 | 0.381615E+10 | 0.203299E+10 | 0.178317E+10 | 0.00 | 0.00 |
October | 0.297471E+10 | 0.229061E+10 | 0.336717E+10 | 0.198079E+10 | 0.138638E+10 | 0.00 | 0.00 |
November | 0.235952E+10 | 0.302660E+10 | 0.290106E+10 | 0.182043E+10 | 0.108064E+10 | 0.00 | 0.00 |
December | 0.220130E+10 | 0.467378E+10 | 0.319063E+10 | 0.209181E+10 | 0.109882E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.382336E+11 | 0.295357E+11 | 0.444798E+11 | 0.237524E+11 | 0.207274E+11 | 0.00 | 0.00 |
Minimum of Months | 0.220130E+10 | 0.817588E+09 | 0.290106E+10 | 0.812512E+09 | 0.108064E+10 | 0.00 | 0.00 |
Maximum of Months | 0.402356E+10 | 0.480620E+10 | 0.472728E+10 | 0.319290E+10 | 0.235436E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.311225E+10 | 0.480075E+10 | 0.413226E+10 | 0.287434E+10 | 0.125792E+10 | 0.00 | 0.00 |
February | 0.402527E+10 | 0.362598E+10 | 0.472728E+10 | 0.319290E+10 | 0.153439E+10 | 0.00 | 0.00 |
March | 0.381379E+10 | 0.335108E+10 | 0.461392E+10 | 0.292075E+10 | 0.169318E+10 | 0.00 | 0.00 |
April | 0.339470E+10 | 0.212557E+10 | 0.404395E+10 | 0.219520E+10 | 0.184875E+10 | 0.00 | 0.00 |
May | 0.301232E+10 | 0.125221E+10 | 0.351217E+10 | 0.120036E+10 | 0.231181E+10 | 0.00 | 0.00 |
June | 0.276195E+10 | 0.840423E+09 | 0.304972E+10 | 0.812512E+09 | 0.223721E+10 | 0.00 | 0.00 |
July | 0.330228E+10 | 0.804503E+09 | 0.344548E+10 | 0.109112E+10 | 0.235436E+10 | 0.00 | 0.00 |
August | 0.362581E+10 | 0.966230E+09 | 0.368004E+10 | 0.153925E+10 | 0.214079E+10 | 0.00 | 0.00 |
September | 0.367912E+10 | 0.148559E+10 | 0.381615E+10 | 0.203299E+10 | 0.178317E+10 | 0.00 | 0.00 |
October | 0.299796E+10 | 0.220724E+10 | 0.336717E+10 | 0.198079E+10 | 0.138638E+10 | 0.00 | 0.00 |
November | 0.236980E+10 | 0.297505E+10 | 0.290106E+10 | 0.182043E+10 | 0.108064E+10 | 0.00 | 0.00 |
December | 0.219682E+10 | 0.466690E+10 | 0.319063E+10 | 0.209181E+10 | 0.109882E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.382921E+11 | 0.291015E+11 | 0.444798E+11 | 0.237524E+11 | 0.207274E+11 | 0.00 | 0.00 |
Minimum of Months | 0.219682E+10 | 0.804503E+09 | 0.290106E+10 | 0.812512E+09 | 0.108064E+10 | 0.00 | 0.00 |
Maximum of Months | 0.402527E+10 | 0.480075E+10 | 0.472728E+10 | 0.319290E+10 | 0.235436E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.618957E+09 | 0.100883E+10 | 0.850274E+09 | 0.591437E+09 | 0.258836E+09 | 0.00 | 0.00 |
February | 0.800762E+09 | 0.761124E+09 | 0.972707E+09 | 0.656985E+09 | 0.315722E+09 | 0.00 | 0.00 |
March | 0.761068E+09 | 0.709283E+09 | 0.949382E+09 | 0.600986E+09 | 0.348396E+09 | 0.00 | 0.00 |
April | 0.682335E+09 | 0.443008E+09 | 0.832101E+09 | 0.451694E+09 | 0.380406E+09 | 0.00 | 0.00 |
May | 0.612073E+09 | 0.252441E+09 | 0.722681E+09 | 0.246992E+09 | 0.475689E+09 | 0.00 | 0.00 |
June | 0.556848E+09 | 0.168782E+09 | 0.627525E+09 | 0.167186E+09 | 0.460339E+09 | 0.00 | 0.00 |
July | 0.661003E+09 | 0.168056E+09 | 0.708958E+09 | 0.224513E+09 | 0.484444E+09 | 0.00 | 0.00 |
August | 0.737277E+09 | 0.197295E+09 | 0.757222E+09 | 0.316722E+09 | 0.440500E+09 | 0.00 | 0.00 |
September | 0.752421E+09 | 0.296866E+09 | 0.785229E+09 | 0.418316E+09 | 0.366912E+09 | 0.00 | 0.00 |
October | 0.605025E+09 | 0.453918E+09 | 0.692844E+09 | 0.407576E+09 | 0.285267E+09 | 0.00 | 0.00 |
November | 0.467889E+09 | 0.628438E+09 | 0.596936E+09 | 0.374579E+09 | 0.222357E+09 | 0.00 | 0.00 |
December | 0.435599E+09 | 0.985960E+09 | 0.656519E+09 | 0.430420E+09 | 0.226098E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.769126E+10 | 0.607400E+10 | 0.915238E+10 | 0.488741E+10 | 0.426497E+10 | 0.00 | 0.00 |
Minimum of Months | 0.435599E+09 | 0.168056E+09 | 0.596936E+09 | 0.167186E+09 | 0.222357E+09 | 0.00 | 0.00 |
Maximum of Months | 0.800762E+09 | 0.100883E+10 | 0.972707E+09 | 0.656985E+09 | 0.484444E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.3 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.6 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.5 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.48 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.18 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.96 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.19 | 13.59 | 3.45 | 8.98 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.33 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.48 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.07 | -2.0 | 3.82 | -8.5 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.3 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.98 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -0.9 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.85 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.46 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.93 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.24 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.70 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.34 | 23.33 | 8.07 | 19.92 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.35 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.80 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.60 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.43 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -0.9 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.34 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.3 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.0 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.61 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.6 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.4 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.33 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.46 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.93 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.90 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.70 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.75 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.35 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.70 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.4 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.75 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.24 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.06 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.90 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.75 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.35 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.22 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.16 | 3.43 | 9.18 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 06-DEC-02:00 | 0.00 | -0.0 | 3.60 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.75 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.329051E+10 | -.270575E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -584756218.9 | 58.99 | 0.00 | 0.00 |
February | 0.304685E+10 | -.252020E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -526651227.7 | 59.00 | 0.00 | 0.00 |
March | 0.342727E+10 | -.284828E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -578995439.3 | 58.99 | 0.00 | 0.00 |
April | 0.317254E+10 | -.262637E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -546172474.6 | 59.00 | 0.00 | 0.00 |
May | 0.311325E+10 | -.258140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -531854817.4 | 58.99 | 0.00 | 0.00 |
June | 0.288568E+10 | -.238190E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -503775295.9 | 58.99 | 0.00 | 0.00 |
July | 0.277923E+10 | -.226378E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -515447374.0 | 59.00 | 0.00 | 0.00 |
August | 0.278492E+10 | -.226847E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -516450863.9 | 58.99 | 0.00 | 0.00 |
September | 0.267839E+10 | -.216892E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -509466807.7 | 58.99 | 0.00 | 0.00 |
October | 0.284734E+10 | -.229377E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -553573288.7 | 58.99 | 0.00 | 0.00 |
November | 0.289762E+10 | -.234053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -557084925.9 | 58.99 | 0.00 | 0.00 |
December | 0.316535E+10 | -.258154E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -583807349.7 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360889E+11 | -.295809E+11 | 8760.00 | -.650804E+10 | 58.99 | |||||
Minimum of Months | 0.267839E+10 | -.284828E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -584756218.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.342727E+10 | -.216892E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -503775295.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | ||||||||||
Minimum of Months | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.378824E+11 | 53548.48 | 01-JAN-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.271730E+11 | 53548.48 | 01-FEB-03:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211187E+11 | 53548.48 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.765964E+10 | 53548.48 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.653283E+09 | 53548.48 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28534052.51 | 20389.81 | 28-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.330994E+10 | 53548.48 | 06-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141320E+11 | 53548.48 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.340813E+11 | 53548.48 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146039E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.378824E+11 | 53548.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117278E+12 | 295239.35 | 01-JAN-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.764449E+11 | 295239.35 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.560008E+11 | 295239.35 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127893E+11 | 295239.35 | 04-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.401201E+09 | 66724.35 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.703212E+10 | 120734.18 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.399879E+11 | 295239.35 | 12-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105663E+12 | 295239.35 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.415597E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117278E+12 | 295239.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159300E+11 | 38691.39 | 01-JAN-06:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.993148E+10 | 38691.39 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.722999E+10 | 38691.39 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.233866E+10 | 38691.39 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.190059E+09 | 38691.39 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8968439.32 | 1319.07 | 23-SEP-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100950E+10 | 38691.39 | 06-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.508408E+10 | 38691.39 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148783E+11 | 38691.39 | 01-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.566010E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159300E+11 | 38691.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.197856E+11 | 33402.06 | 01-JAN-03:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129925E+11 | 33402.06 | 01-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102996E+11 | 33402.06 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.399314E+10 | 33402.06 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.471779E+09 | 33402.06 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5117545.64 | 1433.76 | 03-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5278421.51 | 2333.91 | 19-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121516E+09 | 13122.32 | 23-SEP-04:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231289E+10 | 33402.06 | 06-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.777329E+10 | 33402.06 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186610E+11 | 33402.06 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.764216E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.197856E+11 | 33402.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.251962E+11 | 59272.68 | 05-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162988E+11 | 50746.03 | 01-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137695E+11 | 38269.76 | 15-MAR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.541202E+10 | 23528.55 | 04-APR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.718211E+09 | 9016.46 | 08-MAY-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 63497009.19 | 2490.94 | 02-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17061589.12 | 1292.01 | 08-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 76777659.88 | 4403.56 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.765918E+09 | 8299.73 | 27-SEP-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.508096E+10 | 19732.83 | 29-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110519E+11 | 39165.03 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.239222E+11 | 56728.67 | 24-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102373E+12 | |||||||
Minimum of Months | 17061589.12 | 1292.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.251962E+11 | 59272.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.178836E+09 | 0.171602E+09 | 5022.00 | 23-APR-16:00 | 4387.73 | 0.00 |
May | 0.00 | 0.00 | 0.518007E+10 | 0.451412E+10 | 18439.85 | 25-MAY-20:33 | 16009.33 | 0.00 |
June | 0.00 | 0.00 | 0.118259E+11 | 0.920586E+10 | 27478.66 | 30-JUN-01:00 | 16042.15 | 0.00 |
July | 0.00 | 0.00 | 0.166398E+11 | 0.125051E+11 | 23294.79 | 15-JUL-14:30 | 14955.69 | 0.00 |
August | 0.00 | 0.00 | 0.137032E+11 | 0.103955E+11 | 21349.82 | 08-AUG-15:00 | 15243.73 | 0.00 |
September | 0.00 | 0.00 | 0.481299E+10 | 0.402696E+10 | 16278.94 | 01-SEP-14:50 | 13167.60 | 0.00 |
October | 0.00 | 0.00 | 0.422844E+09 | 0.385695E+09 | 5639.60 | 19-OCT-15:00 | 4943.19 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.527636E+11 | 0.412048E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.166398E+11 | 0.125051E+11 | 27478.66 | 16042.15 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.431278E+10 | 0.419911E+10 | 47141.51 | 23-APR-16:00 | 41667.92 | 0.00 |
May | 0.00 | 0.00 | 0.373412E+11 | 0.335408E+11 | 94938.36 | 26-MAY-20:20 | 81173.14 | 0.00 |
June | 0.00 | 0.00 | 0.703108E+11 | 0.556352E+11 | 128244.94 | 30-JUN-15:00 | 87651.31 | 0.00 |
July | 0.00 | 0.00 | 0.921855E+11 | 0.689460E+11 | 134351.61 | 01-JUL-05:02 | 118066.03 | 0.00 |
August | 0.00 | 0.00 | 0.742537E+11 | 0.561596E+11 | 154697.21 | 25-AUG-05:01 | 132509.50 | 0.00 |
September | 0.00 | 0.00 | 0.264368E+11 | 0.228066E+11 | 88256.93 | 03-SEP-19:03 | 79579.69 | 0.00 |
October | 0.00 | 0.00 | 0.349499E+10 | 0.325486E+10 | 38851.90 | 19-OCT-15:00 | 35263.84 | 0.00 |
November | 0.00 | 0.00 | 0.210418E+09 | 0.168782E+09 | 17454.81 | 01-NOV-15:00 | 13971.41 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.308546E+12 | 0.244711E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.921855E+11 | 0.689460E+11 | 154697.21 | 132509.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 21343402.62 | 21343402.62 | 1647.50 | 28-FEB-15:10 | 1647.50 | 0.00 |
March | 0.00 | 0.00 | 63395744.87 | 63395744.87 | 2784.99 | 31-MAR-14:30 | 2784.99 | 0.00 |
April | 0.00 | 0.00 | 0.155216E+10 | 0.154041E+10 | 8540.74 | 23-APR-14:20 | 7906.50 | 0.00 |
May | 0.00 | 0.00 | 0.614647E+10 | 0.573215E+10 | 14776.12 | 25-MAY-20:10 | 13426.17 | 0.00 |
June | 0.00 | 0.00 | 0.102797E+11 | 0.852177E+10 | 23764.99 | 29-JUN-20:43 | 16841.60 | 0.00 |
July | 0.00 | 0.00 | 0.137258E+11 | 0.109255E+11 | 23442.09 | 23-JUL-18:43 | 17813.44 | 0.00 |
August | 0.00 | 0.00 | 0.125955E+11 | 0.102569E+11 | 22069.35 | 08-AUG-20:43 | 17024.80 | 0.00 |
September | 0.00 | 0.00 | 0.665354E+10 | 0.607450E+10 | 17902.78 | 01-SEP-20:43 | 15135.50 | 0.00 |
October | 0.00 | 0.00 | 0.211383E+10 | 0.205349E+10 | 11106.02 | 19-OCT-14:10 | 10592.51 | 0.00 |
November | 0.00 | 0.00 | 0.159747E+09 | 0.147688E+09 | 3876.82 | 17-NOV-13:30 | 3876.82 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.533114E+11 | 0.453371E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.137258E+11 | 0.109255E+11 | 23764.99 | 17813.44 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 103379.17 | 103379.17 | 90.93 | 31-MAR-14:50 | 90.93 | 0.00 |
April | 0.00 | 0.00 | 0.642049E+09 | 0.630498E+09 | 6107.18 | 23-APR-14:20 | 5513.26 | 0.00 |
May | 0.00 | 0.00 | 0.339128E+10 | 0.305115E+10 | 10789.15 | 25-MAY-20:10 | 9491.07 | 0.00 |
June | 0.00 | 0.00 | 0.672246E+10 | 0.530025E+10 | 20182.61 | 29-JUN-20:43 | 13471.28 | 0.00 |
July | 0.00 | 0.00 | 0.978921E+10 | 0.740567E+10 | 19846.98 | 23-JUL-18:43 | 14476.07 | 0.00 |
August | 0.00 | 0.00 | 0.860729E+10 | 0.668302E+10 | 18144.93 | 08-AUG-20:43 | 13254.82 | 0.00 |
September | 0.00 | 0.00 | 0.372683E+10 | 0.332753E+10 | 14496.52 | 01-SEP-20:43 | 11616.99 | 0.00 |
October | 0.00 | 0.00 | 0.100292E+10 | 0.965522E+09 | 8445.01 | 19-OCT-14:20 | 7911.33 | 0.00 |
November | 0.00 | 0.00 | 13626539.39 | 12922593.57 | 1104.06 | 17-NOV-13:50 | 1104.06 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.338958E+11 | 0.273767E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.978921E+10 | 0.740567E+10 | 20182.61 | 14476.07 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.117851E+11 | 0.97 | 6846.22 | 01-JAN-00:05 | 1.51 |
February | 0.100319E+11 | 0.91 | 6846.22 | 01-FEB-00:04 | 1.51 |
March | 0.103766E+11 | 0.85 | 6846.22 | 01-MAR-05:01 | 1.50 |
April | 0.821853E+10 | 0.70 | 6846.22 | 01-APR-04:01 | 1.50 |
May | 0.435025E+10 | 0.36 | 6846.22 | 01-MAY-04:01 | 1.50 |
June | 0.176530E+10 | 0.15 | 6846.22 | 01-JUN-04:02 | 1.49 |
July | 0.828986E+09 | 0.07 | 6846.22 | 01-JUL-07:08 | 1.48 |
August | 0.139222E+10 | 0.11 | 6846.22 | 01-AUG-07:09 | 1.48 |
September | 0.494805E+10 | 0.42 | 6846.22 | 01-SEP-07:09 | 1.48 |
October | 0.796937E+10 | 0.65 | 6846.22 | 01-OCT-07:01 | 1.49 |
November | 0.955142E+10 | 0.81 | 6846.22 | 01-NOV-04:01 | 1.50 |
December | 0.116198E+11 | 0.95 | 6846.22 | 01-DEC-01:06 | 1.50 |
Annual Sum or Average | 0.828375E+11 | 0.58 | |||
Minimum of Months | 0.828986E+09 | 0.07 | 6846.22 | 1.48 | |
Maximum of Months | 0.117851E+11 | 0.97 | 6846.22 | 1.51 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.346754E+10 | 0.72 | 1984.23 | 01-JAN-18:40 | 0.94 |
February | 0.309712E+10 | 0.70 | 1984.23 | 02-FEB-10:50 | 0.94 |
March | 0.337456E+10 | 0.64 | 1984.23 | 18-MAR-06:27 | 0.94 |
April | 0.316820E+10 | 0.59 | 1984.23 | 04-APR-05:35 | 0.94 |
May | 0.321640E+10 | 0.57 | 1984.23 | 14-MAY-17:10 | 0.94 |
June | 0.315160E+10 | 0.58 | 1984.23 | 02-JUN-09:15 | 0.93 |
July | 0.322543E+10 | 0.59 | 1984.23 | 11-JUL-15:30 | 0.93 |
August | 0.325571E+10 | 0.58 | 1984.23 | 14-AUG-19:13 | 0.93 |
September | 0.310795E+10 | 0.56 | 1984.23 | 02-SEP-07:27 | 0.93 |
October | 0.320380E+10 | 0.57 | 1984.23 | 06-OCT-09:24 | 0.94 |
November | 0.315591E+10 | 0.61 | 1984.23 | 10-NOV-19:00 | 0.94 |
December | 0.344478E+10 | 0.71 | 1984.23 | 12-DEC-07:08 | 0.94 |
Annual Sum or Average | 0.388690E+11 | 0.62 | |||
Minimum of Months | 0.309712E+10 | 0.56 | 1984.23 | 0.93 | |
Maximum of Months | 0.346754E+10 | 0.72 | 1984.23 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.227701E+11 | 0.92 | 14157.73 | 19-JAN-13:30 | 1.48 |
February | 0.206286E+11 | 0.91 | 14157.73 | 04-FEB-18:20 | 1.48 |
March | 0.230997E+11 | 0.91 | 14157.73 | 03-MAR-18:13 | 1.48 |
April | 0.221728E+11 | 0.89 | 14157.73 | 01-APR-10:12 | 1.47 |
May | 0.230810E+11 | 0.93 | 14157.73 | 01-MAY-06:30 | 1.48 |
June | 0.228406E+11 | 0.98 | 14157.73 | 03-JUN-16:40 | 1.47 |
July | 0.235839E+11 | 1.03 | 14157.73 | 01-JUL-05:08 | 1.46 |
August | 0.237900E+11 | 1.02 | 14157.73 | 02-AUG-07:53 | 1.46 |
September | 0.223241E+11 | 0.92 | 14157.73 | 22-SEP-17:08 | 1.46 |
October | 0.226807E+11 | 0.88 | 14157.73 | 08-OCT-17:18 | 1.48 |
November | 0.218660E+11 | 0.88 | 14157.73 | 04-NOV-19:11 | 1.48 |
December | 0.227938E+11 | 0.91 | 14157.73 | 04-DEC-06:53 | 1.48 |
Annual Sum or Average | 0.271631E+12 | 0.93 | |||
Minimum of Months | 0.206286E+11 | 0.88 | 14157.73 | 1.46 | |
Maximum of Months | 0.237900E+11 | 1.03 | 14157.73 | 1.48 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.239440E+10 | 0.72 | 1424.31 | 18-JAN-19:40 | 0.98 |
February | 0.214395E+10 | 0.70 | 1424.31 | 02-FEB-15:20 | 0.98 |
March | 0.236741E+10 | 0.65 | 1424.31 | 05-MAR-14:30 | 0.98 |
April | 0.224828E+10 | 0.61 | 1424.31 | 05-APR-06:50 | 0.98 |
May | 0.231872E+10 | 0.62 | 1424.31 | 03-MAY-16:50 | 0.97 |
June | 0.228967E+10 | 0.66 | 1424.31 | 01-JUN-07:35 | 0.97 |
July | 0.237197E+10 | 0.72 | 1424.31 | 06-JUL-07:00 | 0.97 |
August | 0.239869E+10 | 0.72 | 1424.31 | 02-AUG-07:13 | 0.97 |
September | 0.225252E+10 | 0.64 | 1424.31 | 22-SEP-10:45 | 0.97 |
October | 0.229082E+10 | 0.60 | 1424.31 | 02-OCT-09:45 | 0.97 |
November | 0.223312E+10 | 0.62 | 1424.31 | 21-NOV-19:25 | 0.97 |
December | 0.239197E+10 | 0.72 | 1424.31 | 08-DEC-17:20 | 0.98 |
Annual Sum or Average | 0.277015E+11 | 0.67 | |||
Minimum of Months | 0.214395E+10 | 0.60 | 1424.31 | 0.97 | |
Maximum of Months | 0.239869E+10 | 0.72 | 1424.31 | 0.98 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.197696E+10 | 0.76 | 1151.49 | 02-JAN-18:20 | 0.98 |
February | 0.175953E+10 | 0.72 | 1151.49 | 01-FEB-12:00 | 0.98 |
March | 0.193093E+10 | 0.66 | 1151.49 | 01-MAR-12:09 | 0.98 |
April | 0.182508E+10 | 0.62 | 1151.49 | 01-APR-09:22 | 0.98 |
May | 0.186863E+10 | 0.60 | 1151.49 | 01-MAY-08:13 | 0.98 |
June | 0.183643E+10 | 0.62 | 1151.49 | 02-JUN-10:42 | 0.97 |
July | 0.188764E+10 | 0.65 | 1151.49 | 02-JUL-09:20 | 0.97 |
August | 0.191284E+10 | 0.66 | 1151.49 | 01-AUG-07:30 | 0.96 |
September | 0.181006E+10 | 0.60 | 1151.49 | 01-SEP-08:00 | 0.96 |
October | 0.185559E+10 | 0.60 | 1151.49 | 01-OCT-17:13 | 0.97 |
November | 0.181914E+10 | 0.64 | 1151.49 | 01-NOV-06:55 | 0.97 |
December | 0.197009E+10 | 0.75 | 1151.49 | 05-DEC-12:03 | 0.98 |
Annual Sum or Average | 0.224529E+11 | 0.66 | |||
Minimum of Months | 0.175953E+10 | 0.60 | 1151.49 | 0.96 | |
Maximum of Months | 0.197696E+10 | 0.76 | 1151.49 | 0.98 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.97 | 0.00 |
February | 3.50 | 0.00 |
March | 2.56 | 0.00 |
April | 0.96 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.53 | 0.00 |
November | 2.22 | 0.00 |
December | 3.84 | 0.00 |
Annual Sum or Average | 17.59 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.97 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.30 | 0.00 |
February | 0.17 | 0.00 |
March | 0.11 | 0.00 |
April | 0.79 | 24.02 |
May | 0.87 | 25.84 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.03 | 25.84 |
September | 0.73 | 25.84 |
October | 1.28 | 25.84 |
November | 0.17 | 0.00 |
December | 0.28 | 0.00 |
Annual Sum or Average | 4.74 | 19.94 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.28 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.35 | 0.00 |
February | 1.45 | 0.00 |
March | 0.99 | 0.00 |
April | 0.30 | 0.00 |
May | 0.04 | 12.18 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.12 | 0.00 |
November | 0.77 | 0.00 |
December | 3.18 | 0.00 |
Annual Sum or Average | 9.18 | 0.06 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.18 | 12.18 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.82 | 0.00 |
February | 2.28 | 0.00 |
March | 1.71 | 0.00 |
April | 0.59 | 0.00 |
May | 0.03 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.40 | 0.00 |
November | 1.86 | 0.00 |
December | 3.37 | 0.00 |
Annual Sum or Average | 13.07 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.37 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 85.73 | 0.00 |
February | 66.76 | 0.00 |
March | 56.04 | 0.00 |
April | 69.46 | 0.00 |
May | 68.34 | 0.00 |
June | 27.87 | 0.00 |
July | 20.40 | 0.00 |
August | 27.95 | 0.00 |
September | 84.16 | 0.00 |
October | 75.48 | 0.00 |
November | 55.45 | 0.00 |
December | 77.92 | 0.00 |
Annual Sum or Average | 715.56 | 0.00 |
Minimum of Months | 20.40 | 0.00 |
Maximum of Months | 85.73 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.346754E+10 | 0.473530E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.309712E+10 | 0.339663E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.337456E+10 | 0.263984E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.322306E+10 | 0.957455E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.474885E+10 | 0.816604E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.658891E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.799848E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.715593E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.450476E+10 | 35667565.64 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.332979E+10 | 0.413742E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.315591E+10 | 0.176650E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.344478E+10 | 0.426016E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.540897E+11 | 0.182549E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.309712E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.799848E+10 | 0.473530E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.227701E+11 | 0.147985E+12 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.206286E+11 | 0.964605E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.230997E+11 | 0.706635E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.235537E+11 | 0.161379E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.348311E+11 | 0.506247E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.445629E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.518196E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.464315E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.305535E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.237923E+11 | 0.887333E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.219344E+11 | 0.504580E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.227938E+11 | 0.133328E+12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.366771E+12 | 0.524413E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.206286E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.518196E+11 | 0.147985E+12 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.239440E+10 | 0.199124E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.215039E+10 | 0.124144E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.238641E+10 | 0.903749E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.269469E+10 | 0.292332E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.409226E+10 | 0.237574E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.523267E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.626195E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.591933E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.412148E+10 | 11210549.15 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.288676E+10 | 0.126188E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.228038E+10 | 0.635509E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.239197E+10 | 0.185979E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.428127E+11 | 0.707513E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.215039E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.626195E+10 | 0.199124E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.197696E+10 | 0.247320E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.175953E+10 | 0.162406E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.193096E+10 | 0.128745E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.201269E+10 | 0.499143E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.286086E+10 | 0.589724E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.377858E+10 | 6396932.05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.467499E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.433000E+10 | 6598026.89 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.286092E+10 | 0.151895E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.213774E+10 | 0.289112E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.182326E+10 | 0.971662E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.197009E+10 | 0.233262E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.321166E+11 | 0.955270E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.175953E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.467499E+10 | 0.247320E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.346754E+10 | 0.00 | 0.378824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.309712E+10 | 0.00 | 0.271730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.337456E+10 | 0.00 | 0.211187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.316820E+10 | 0.178836E+09 | 0.765964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.321640E+10 | 0.518007E+10 | 0.653283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.315160E+10 | 0.118259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.322543E+10 | 0.166398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.325571E+10 | 0.137032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.310795E+10 | 0.481299E+10 | 28534052.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.320380E+10 | 0.422844E+09 | 0.330994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.315591E+10 | 0.00 | 0.141320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344478E+10 | 0.00 | 0.340813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.388690E+11 | 0.527636E+11 | 0.146039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.309712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.346754E+10 | 0.166398E+11 | 0.378824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.227701E+11 | 0.00 | 0.117278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206286E+11 | 0.00 | 0.764449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230997E+11 | 0.00 | 0.560008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.221728E+11 | 0.431278E+10 | 0.127893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.230810E+11 | 0.373412E+11 | 0.401201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.228406E+11 | 0.703108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.235839E+11 | 0.921855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.237900E+11 | 0.742537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.223241E+11 | 0.264368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.226807E+11 | 0.349499E+10 | 0.703212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.218660E+11 | 0.210418E+09 | 0.399879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227938E+11 | 0.00 | 0.105663E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271631E+12 | 0.308546E+12 | 0.415597E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.206286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.237900E+11 | 0.921855E+11 | 0.117278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.239440E+10 | 0.00 | 0.159300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214395E+10 | 21343402.62 | 0.993148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.236741E+10 | 63395744.87 | 0.722999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.224828E+10 | 0.155216E+10 | 0.233866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.231872E+10 | 0.614647E+10 | 0.190059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.228967E+10 | 0.102797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.237197E+10 | 0.137258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.239869E+10 | 0.125955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.225252E+10 | 0.665354E+10 | 8968439.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229082E+10 | 0.211383E+10 | 0.100950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223312E+10 | 0.159747E+09 | 0.508408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.239197E+10 | 0.00 | 0.148783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277015E+11 | 0.533114E+11 | 0.566010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.214395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.239869E+10 | 0.137258E+11 | 0.159300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.197696E+10 | 0.00 | 0.197856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175953E+10 | 0.00 | 0.129925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193093E+10 | 103379.17 | 0.102996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182508E+10 | 0.642049E+09 | 0.399314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.186863E+10 | 0.339128E+10 | 0.471779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.183643E+10 | 0.672246E+10 | 5117545.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.188764E+10 | 0.978921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191284E+10 | 0.860729E+10 | 5278421.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.181006E+10 | 0.372683E+10 | 0.121516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185559E+10 | 0.100292E+10 | 0.231289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181914E+10 | 13626539.39 | 0.777329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197009E+10 | 0.00 | 0.186610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224529E+11 | 0.338958E+11 | 0.764216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.175953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.197696E+10 | 0.978921E+10 | 0.197856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.346754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.309712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.337456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.316820E+10 | 0.00 | 0.00 | 0.00 | 54863626.87 | 0.00 | 0.957455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.321640E+10 | 0.00 | 0.00 | 0.00 | 0.153246E+10 | 0.00 | 0.816604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.315160E+10 | 0.00 | 0.00 | 0.00 | 0.343731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.322543E+10 | 0.00 | 0.00 | 0.00 | 0.477304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.325571E+10 | 0.00 | 0.00 | 0.00 | 0.390021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.310795E+10 | 0.00 | 0.00 | 0.00 | 0.139681E+10 | 0.00 | 35667565.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.320380E+10 | 0.00 | 0.00 | 0.00 | 0.125990E+09 | 0.00 | 0.413742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.315591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.388690E+11 | 0.00 | 0.00 | 0.00 | 0.152207E+11 | 0.00 | 0.182549E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.309712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.346754E+10 | 0.00 | 0.00 | 0.00 | 0.477304E+10 | 0.00 | 0.473530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.227701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.221728E+11 | 0.00 | 0.00 | 0.00 | 0.138088E+10 | 0.00 | 0.161379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.230810E+11 | 0.00 | 0.00 | 0.00 | 0.117501E+11 | 0.00 | 0.506247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.228406E+11 | 0.00 | 0.00 | 0.00 | 0.217222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.235839E+11 | 0.00 | 0.00 | 0.00 | 0.282358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.237900E+11 | 0.00 | 0.00 | 0.00 | 0.226415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.223241E+11 | 0.00 | 0.00 | 0.00 | 0.822946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.226807E+11 | 0.00 | 0.00 | 0.00 | 0.111163E+10 | 0.00 | 0.887333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.218660E+11 | 0.00 | 0.00 | 0.00 | 68308485.56 | 0.00 | 0.504580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133328E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271631E+12 | 0.00 | 0.00 | 0.00 | 0.951398E+11 | 0.00 | 0.524413E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.206286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.237900E+11 | 0.00 | 0.00 | 0.00 | 0.282358E+11 | 0.00 | 0.147985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.239440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214395E+10 | 0.00 | 0.00 | 0.00 | 6438879.42 | 0.00 | 0.124144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.236741E+10 | 0.00 | 0.00 | 0.00 | 18994087.64 | 0.00 | 0.903749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.224828E+10 | 0.00 | 0.00 | 0.00 | 0.446414E+09 | 0.00 | 0.292332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.231872E+10 | 0.00 | 0.00 | 0.00 | 0.177354E+10 | 0.00 | 0.237574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.228967E+10 | 0.00 | 0.00 | 0.00 | 0.294300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.237197E+10 | 0.00 | 0.00 | 0.00 | 0.388998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.239869E+10 | 0.00 | 0.00 | 0.00 | 0.352064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.225252E+10 | 0.00 | 0.00 | 0.00 | 0.186896E+10 | 0.00 | 11210549.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229082E+10 | 0.00 | 0.00 | 0.00 | 0.595933E+09 | 0.00 | 0.126188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223312E+10 | 0.00 | 0.00 | 0.00 | 47263078.95 | 0.00 | 0.635509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.239197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277015E+11 | 0.00 | 0.00 | 0.00 | 0.151112E+11 | 0.00 | 0.707513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.214395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.239869E+10 | 0.00 | 0.00 | 0.00 | 0.388998E+10 | 0.00 | 0.199124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.197696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193093E+10 | 0.00 | 0.00 | 0.00 | 31641.80 | 0.00 | 0.128745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182508E+10 | 0.00 | 0.00 | 0.00 | 0.187612E+09 | 0.00 | 0.499143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.186863E+10 | 0.00 | 0.00 | 0.00 | 0.992230E+09 | 0.00 | 0.589724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.183643E+10 | 0.00 | 0.00 | 0.00 | 0.194215E+10 | 0.00 | 6396932.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.188764E+10 | 0.00 | 0.00 | 0.00 | 0.278736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191284E+10 | 0.00 | 0.00 | 0.00 | 0.241717E+10 | 0.00 | 6598026.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.181006E+10 | 0.00 | 0.00 | 0.00 | 0.105086E+10 | 0.00 | 0.151895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185559E+10 | 0.00 | 0.00 | 0.00 | 0.282153E+09 | 0.00 | 0.289112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181914E+10 | 0.00 | 0.00 | 0.00 | 4123054.36 | 0.00 | 0.971662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224529E+11 | 0.00 | 0.00 | 0.00 | 0.966368E+10 | 0.00 | 0.955270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.175953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.197696E+10 | 0.00 | 0.00 | 0.00 | 0.278736E+10 | 0.00 | 0.247320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5346304.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188809E+11 | 0.00 | 0.00 | 0.24 |
February | 80852274.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141647E+11 | 0.00 | 0.00 | 0.23 |
March | 0.877102E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123572E+11 | 0.00 | 0.00 | 0.23 |
April | 0.321694E+10 | 8092611.21 | 0.00 | 258604.17 | 6856550.25 | 0.463968E+10 | 0.263394E+09 | 0.00 | 0.22 |
May | 0.225353E+10 | 0.128383E+09 | 0.00 | 5911887.84 | 0.00 | 0.388303E+09 | 0.178216E+10 | 0.00 | 0.22 |
June | 0.721227E+09 | 0.121170E+10 | 0.00 | 8933408.76 | 1126321.52 | 0.00 | 0.152663E+10 | 0.00 | 0.23 |
July | 0.328717E+09 | 0.193028E+10 | 0.00 | 8559009.86 | 3192389.47 | 0.00 | 0.761173E+09 | 0.00 | 0.22 |
August | 0.511638E+09 | 0.921079E+09 | 0.00 | 11975128.76 | 181574.65 | 0.00 | 0.125027E+10 | 0.00 | 0.23 |
September | 0.215777E+10 | 28447700.77 | 0.00 | 11038193.33 | 0.00 | 1998452.09 | 0.287167E+10 | 0.00 | 0.22 |
October | 0.526498E+10 | 0.00 | 0.00 | 1144787.68 | 0.00 | 0.207383E+10 | 0.682317E+09 | 0.00 | 0.22 |
November | 0.198090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864746E+10 | 0.00 | 0.00 | 0.22 |
December | 2165110.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177069E+11 | 0.00 | 0.00 | 0.23 |
Annual Sum or Average | 0.174012E+11 | 0.422798E+10 | 0.00 | 47821020.41 | 11356835.89 | 0.788610E+11 | 0.913762E+10 | 0.00 | 0.23 |
Minimum of Months | 2165110.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 0.526498E+10 | 0.193028E+10 | 0.00 | 11975128.76 | 6856550.25 | 0.188809E+11 | 0.287167E+10 | 0.00 | 0.24 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.386515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.893754E+11 | 0.00 | 0.00 | 0.39 |
February | 0.508447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462991E+11 | 0.00 | 0.00 | 0.39 |
March | 0.647123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273403E+11 | 0.00 | 0.00 | 0.40 |
April | 0.454993E+11 | 0.101136E+09 | 0.00 | 13569054.32 | 0.00 | 0.448414E+10 | 0.848887E+10 | 0.00 | 0.40 |
May | 0.113078E+11 | 0.135828E+10 | 0.00 | 63381476.79 | 0.00 | 0.231015E+09 | 0.213337E+11 | 0.00 | 0.43 |
June | 0.225455E+10 | 0.967955E+10 | 0.00 | 65332161.53 | 42231796.01 | 0.00 | 0.156061E+11 | 0.00 | 0.47 |
July | 0.433193E+09 | 0.152962E+11 | 0.00 | 45721482.66 | 48400643.08 | 0.00 | 0.875419E+10 | 0.00 | 0.47 |
August | 0.105438E+10 | 0.731804E+10 | 0.00 | 68673877.49 | 4044522.44 | 0.00 | 0.148091E+11 | 0.00 | 0.49 |
September | 0.113229E+11 | 0.250522E+09 | 0.00 | 80888657.65 | 0.00 | 0.00 | 0.285523E+11 | 0.00 | 0.46 |
October | 0.465102E+11 | 0.00 | 0.00 | 14231856.80 | 0.00 | 0.194762E+10 | 0.981115E+10 | 0.00 | 0.40 |
November | 0.547434E+11 | 0.00 | 0.00 | 391100.88 | 0.00 | 0.203661E+11 | 0.446937E+09 | 0.00 | 0.39 |
December | 0.468734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742864E+11 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.374208E+12 | 0.340038E+11 | 0.00 | 0.352190E+09 | 94676961.53 | 0.264330E+12 | 0.107802E+12 | 0.00 | 0.42 |
Minimum of Months | 0.433193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.647123E+11 | 0.152962E+11 | 0.00 | 80888657.65 | 48400643.08 | 0.893754E+11 | 0.285523E+11 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.388389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969859E+10 | 0.00 | 0.00 | 0.44 |
February | 0.465808E+10 | 0.00 | 0.00 | 236955.74 | 0.00 | 0.535251E+10 | 0.284220E+09 | 0.00 | 0.44 |
March | 0.498065E+10 | 0.00 | 0.00 | 559833.34 | 0.00 | 0.406396E+10 | 0.627897E+09 | 0.00 | 0.44 |
April | 0.338407E+10 | 11634067.96 | 0.00 | 4858211.58 | 0.00 | 0.123239E+10 | 0.142583E+10 | 0.00 | 0.43 |
May | 0.101667E+10 | 0.156657E+09 | 0.00 | 11251428.56 | 0.00 | 0.106920E+09 | 0.199059E+10 | 0.00 | 0.43 |
June | 0.376379E+09 | 0.109360E+10 | 0.00 | 9483042.09 | 0.00 | 0.00 | 0.107041E+10 | 0.00 | 0.44 |
July | 0.155847E+09 | 0.176650E+10 | 0.00 | 7603028.89 | 503706.19 | 0.00 | 0.517098E+09 | 0.00 | 0.44 |
August | 0.228543E+09 | 0.950067E+09 | 0.00 | 11906943.08 | 149151.18 | 0.00 | 0.844391E+09 | 0.00 | 0.45 |
September | 0.942386E+09 | 51251722.22 | 0.00 | 18052840.96 | 0.00 | 0.00 | 0.251920E+10 | 0.00 | 0.43 |
October | 0.330429E+10 | 0.00 | 0.00 | 8138748.43 | 0.00 | 0.575484E+09 | 0.204973E+10 | 0.00 | 0.42 |
November | 0.441861E+10 | 0.00 | 0.00 | 710939.69 | 0.00 | 0.289335E+10 | 0.563732E+09 | 0.00 | 0.43 |
December | 0.366897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911914E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.310184E+11 | 0.402971E+10 | 0.00 | 72801972.36 | 652857.38 | 0.330423E+11 | 0.118931E+11 | 0.00 | 0.44 |
Minimum of Months | 0.155847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.498065E+10 | 0.176650E+10 | 0.00 | 18052840.96 | 503706.19 | 0.969859E+10 | 0.251920E+10 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.158671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122885E+11 | 0.00 | 0.00 | 0.45 |
February | 0.244011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796875E+10 | 0.00 | 0.00 | 0.44 |
March | 0.318685E+10 | 0.00 | 0.00 | 19568.00 | 0.00 | 0.644715E+10 | 32293239.10 | 0.00 | 0.44 |
April | 0.260905E+10 | 10711888.42 | 0.00 | 1660316.03 | 0.00 | 0.260845E+10 | 0.676694E+09 | 0.00 | 0.43 |
May | 0.156876E+10 | 0.136528E+09 | 0.00 | 4273683.37 | 0.00 | 0.298521E+09 | 0.117408E+10 | 0.00 | 0.43 |
June | 0.618039E+09 | 0.952009E+09 | 0.00 | 4771986.73 | 253250.41 | 0.00 | 0.900110E+09 | 0.00 | 0.44 |
July | 0.302855E+09 | 0.153019E+10 | 0.00 | 4693004.41 | 2735986.41 | 0.00 | 0.457365E+09 | 0.00 | 0.44 |
August | 0.466149E+09 | 0.800365E+09 | 0.00 | 7161401.16 | 167397.90 | 357770.34 | 0.761247E+09 | 0.00 | 0.44 |
September | 0.177121E+10 | 37490428.79 | 0.00 | 9219010.46 | 0.00 | 32464475.47 | 0.165913E+10 | 0.00 | 0.43 |
October | 0.351309E+10 | 0.00 | 0.00 | 3443372.66 | 0.00 | 0.141350E+10 | 0.787047E+09 | 0.00 | 0.42 |
November | 0.287076E+10 | 0.00 | 0.00 | 63538.00 | 0.00 | 0.487229E+10 | 72639448.82 | 0.00 | 0.43 |
December | 0.124763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117861E+11 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.221812E+11 | 0.346729E+10 | 0.00 | 35305880.82 | 3156634.72 | 0.477161E+11 | 0.652061E+10 | 0.00 | 0.44 |
Minimum of Months | 0.302855E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.351309E+10 | 0.153019E+10 | 0.00 | 9219010.46 | 2735986.41 | 0.122885E+11 | 0.165913E+10 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |