Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2020-06-03 19:11:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2191.72 | 955.42 | 955.42 |
Net Site Energy | 2191.72 | 955.42 | 955.42 |
Total Source Energy | 4570.26 | 1992.27 | 1992.27 |
Net Source Energy | 4570.26 | 1992.27 | 1992.27 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1037.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 76.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 456.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 265.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 100.69 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1053.50 | 1138.22 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1037.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 76.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 456.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 194.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 265.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 100.69 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 225.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 149.01 | 496.17 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 459.24 | 496.17 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 225.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 149.01 | 496.17 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 459.24 | 496.17 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1053.499 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1053.499 | 100.00 |
Total On-Site and Utility Electric Sources | 1053.499 | 100.00 |
Total Electricity End Uses | 1053.499 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2604.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 8.56 |
Skylight-Roof Ratio [%] | 0.37 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.5670 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 18.0834 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 18.0834 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 18.0834 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 9.6875 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.2979 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.2979 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-15:00 | 09-JAN-07:10 | - | - | - | 21-MAR-11:09 |
Heating | 0.00 | 325171.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 46443.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 31890.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10752.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12011.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 101098.61 | 327031.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 325171.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 46443.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 31890.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10752.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 12011.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1124.68 | 0.00 | 0.00 | 0.00 |
Cooling | 242.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1446.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 191.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 616.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 839.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 109.15 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3336.43 | 1233.83 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 490.27 | 0.00 | 0.00 | 0.00 |
Cooling | 105.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 630.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 83.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 366.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 47.58 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1454.42 | 537.85 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 490.27 | 0.00 | 0.00 | 0.00 |
Cooling | 105.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 630.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 83.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 366.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 47.58 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1454.42 | 537.85 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.73 |
CORE_RETAIL DIRECT AIR | 7.91 |
POINT_OF_SALE DIRECT AIR | 1.24 |
FRONT_RETAIL DIRECT AIR | 1.00 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 3.91 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 3.91 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 87508.79 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 52566.48 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 292643.53 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 38463.27 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 33276.24 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.73 | 1.73 | 1.73 | 1.73 | 1.77 | 1.77 | 1.00 | 0.975367 | 1.77 |
PSZ-AC:2 | 7.91 | 7.91 | 7.91 | 7.91 | 8.07 | 8.07 | 1.00 | 0.979948 | 8.07 |
PSZ-AC:3 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.00 | 1.00 | 1.24 |
PSZ-AC:4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.77 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 8.07 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.24 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 1.00 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.77 | 1.77 | 1.77 | 1.17 | 33476.47 | 52566.48 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 8.07 | 8.07 | 8.07 | 5.32 | 163086.63 | 292643.53 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 1.24 | 22401.40 | 38463.27 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 1.00 | 18912.72 | 33276.24 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.77 | 0.885370 | 1.18 | 31216.30 | 33476.47 | 16738.24 | 16738.24 | 0.752919 | 0.752920 | 0.752920 | 0.752920 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 8.07 | 4.03 | 5.38 | 152966.56 | 163086.63 | 81543.32 | 81543.32 | 0.732037 | 0.732040 | 0.732040 | 0.732040 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.24 | 0.619500 | 0.826000 | 20804.17 | 22401.40 | 11200.70 | 11200.70 | 0.767611 | 0.767610 | 0.767610 | 0.767610 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.00 | 0.502165 | 0.669553 | 17630.33 | 18912.72 | 9456.36 | 9456.36 | 0.754187 | 0.754190 | 0.754190 | 0.754190 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.77 | 1894.77 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 8.07 | 13590.42 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.24 | 1371.77 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.00 | 1111.95 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 65 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 6.69 | 10 | 14 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.567 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.637 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 18.083 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 21.313 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 18.083 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 39.603 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 18.083 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 21.313 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 9.688 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.688 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2874.639 | 7.567 | 46.863 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2874.639 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 28942.124 | 18.083 | 111.990 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28942.124 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2727.153 | 18.083 | 111.990 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2727.153 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2727.153 | 18.083 | 111.990 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2727.153 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 116.250 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 116.250 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.4290 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1659 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.3309E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1913 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1913 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.3147 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.163 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.950 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 30.14 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.149 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.149 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.101 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8390000 | 2.8390000 | 2.8390000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 9 | 0.21485751E-14 | -0.22894401E-15 | -0.17283669E-09 | -0.31350098E-16 |
25 | 8 | 0.25115787E-07 | 0.58773152E-13 | 0.41104347E-03 | -0.28557513E-09 |
26 | 7 | -0.13231082E-01 | 0.29616277E-08 | -0.24509747E-01 | 0.15044224E-03 |
27 | 6 | 0.43223401 | 0.10185882E-05 | 0.49492235 | -0.50646574E-02 |
28 | 5 | -5.4528708 | 0.37659386E-04 | -4.6163278 | 0.66436381E-01 |
29 | 4 | 34.162830 | 0.30532126E-03 | 22.123982 | -0.43752457 |
30 | 3 | -113.69342 | 0.66011806E-03 | -56.975280 | 1.5508408 |
31 | 2 | 199.57555 | 0.36866733E-03 | 79.115267 | -2.9395356 |
32 | 1 | -172.06709 | 0.39096546E-04 | -55.617513 | 2.7614060 |
33 | 0 | 57.057407 | 0.22087022E-06 | 15.500460 | |
34 | 7 | -0.25528060E-08 | -0.12031403E-14 | 0.68407999E-14 | -0.93970880E-16 |
35 | 6 | 0.47134542E-05 | 0.31734324E-08 | 0.31924928E-02 | -0.26781305E-04 |
36 | 5 | -0.33464294E-03 | 0.18778732E-05 | -0.22387365 | 0.19574661E-02 |
37 | 4 | 0.76699050E-02 | 0.85441795E-04 | 4.8320287 | -0.45288849E-01 |
38 | 3 | -0.67267585E-01 | 0.67916014E-03 | -38.035443 | 0.39880879 |
39 | 2 | 0.23873650 | 0.11294419E-02 | 116.51125 | -1.4183045 |
40 | 1 | -0.34450630 | 0.34392527E-03 | -143.92338 | 2.0493041 |
41 | 0 | 0.16794560 | 0.83374149E-05 | 60.838472 | |
42 | 7 | -0.12973758E-07 | 0.34411372E-14 | -0.15771944E-13 | 0.23851239E-15 |
43 | 6 | 0.18530215E-05 | 0.67214774E-09 | 0.32028229E-02 | -0.26867962E-04 |
44 | 5 | -0.88022991E-04 | 0.38590341E-06 | -0.22446025 | 0.19626440E-02 |
45 | 4 | 0.17210852E-02 | 0.17282655E-04 | 4.8417890 | -0.45382682E-01 |
46 | 3 | -0.14132592E-01 | 0.13559951E-03 | -38.090529 | 0.39941776 |
47 | 2 | 0.48779578E-01 | 0.22269637E-03 | 116.61840 | -1.4197378 |
48 | 1 | -0.69488798E-01 | 0.66762873E-04 | -143.98642 | 2.0503404 |
49 | 0 | 0.33651223E-01 | 0.15845250E-05 | 60.838472 | |
50 | 7 | -0.22078744E-08 | -0.78010070E-15 | 0.51210754E-14 | -0.71692469E-16 |
51 | 6 | 0.53924046E-05 | 0.36628569E-08 | 0.31905048E-02 | -0.26764628E-04 |
52 | 5 | -0.38538745E-03 | 0.21680609E-05 | -0.22376067 | 0.19564689E-02 |
53 | 4 | 0.88497020E-02 | 0.98671011E-04 | 4.8301469 | -0.45270761E-01 |
54 | 3 | -0.77667315E-01 | 0.78446833E-03 | -38.024813 | 0.39869130 |
55 | 2 | 0.27571886 | 0.13048573E-02 | 116.49056 | -1.4180278 |
56 | 1 | -0.39792016 | 0.39739385E-03 | -143.91120 | 2.0491039 |
57 | 0 | 0.19399612 | 0.96507839E-05 | 60.838472 | |
58 | 7 | -0.22078744E-08 | -0.78010070E-15 | 0.51210754E-14 | -0.71692469E-16 |
59 | 6 | 0.53924046E-05 | 0.36628569E-08 | 0.31905048E-02 | -0.26764628E-04 |
60 | 5 | -0.38538745E-03 | 0.21680609E-05 | -0.22376067 | 0.19564689E-02 |
61 | 4 | 0.88497020E-02 | 0.98671011E-04 | 4.8301469 | -0.45270761E-01 |
62 | 3 | -0.77667315E-01 | 0.78446833E-03 | -38.024813 | 0.39869130 |
63 | 2 | 0.27571886 | 0.13048573E-02 | 116.49056 | -1.4180278 |
64 | 1 | -0.39792016 | 0.39739385E-03 | -143.91120 | 2.0491039 |
65 | 0 | 0.19399612 | 0.96507839E-05 | 60.838472 | |
66 | 7 | -0.13255510E-08 | -0.17188199E-15 | 0.92128295E-14 | -0.12705258E-15 |
67 | 6 | 0.87884716E-05 | 0.60547316E-08 | 0.31807701E-02 | -0.26682965E-04 |
68 | 5 | -0.63593173E-03 | 0.35898785E-05 | -0.22320731 | 0.19515846E-02 |
69 | 4 | 0.14651324E-01 | 0.16347926E-03 | 4.8209294 | -0.45182156E-01 |
70 | 3 | -0.12872491 | 0.13006479E-02 | -37.972737 | 0.39811570 |
71 | 2 | 0.45715725 | 0.21644648E-02 | 116.38920 | -1.4166720 |
72 | 1 | -0.65988557 | 0.65992538E-03 | -143.85153 | 2.0481231 |
73 | 0 | 0.32173707 | 0.15909640E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.41_SHGC_0.45 | 30 | 1 | VerySmooth | 2.330 | 0.445 | 0.367 | 0.451 |
2 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 31 | 1 | VerySmooth | 5.779 | 0.680 | 0.573 | 0.680 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.14065E-002 | 0.36619 | 0.42864 | 0.42864 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12199 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.57291 | 6.11155E-002 | 6.11155E-002 | 0.68000 | 0.13462 | 0.14960 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 8 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1915 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
31 | SKYLIGHTS_R2C4 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
32 | SKYLIGHTS_R2C1 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
33 | SKYLIGHTS_R2C2 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
34 | SKYLIGHTS_R2C3 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C3 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C1 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C2 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
39 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
40 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
42 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
43 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
44 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
45 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
46 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
47 | POINT_OF_SALE_ROOF | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
48 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
49 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
50 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
52 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
54 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | FRONT_RETAIL_ROOF | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
58 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
59 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
60 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
62 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
63 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
64 | FRONT_ENTRY_ROOF | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
65 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 19591.00740 | 23509.20888 | 1.43927 | 1.72712 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27032E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 30839.42321 | 37007.30785 | 1.36213 | 1.63456 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 89436.51407 | 107323.81689 | 6.58762 | 7.90514 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27032E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 76554.12225 | 91864.94670 | 3.34281 | 4.01137 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 13483.25168 | 16179.90202 | 1.03250 | 1.23900 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27032E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 15049.12290 | 18058.94748 | 0.66653 | 0.79984 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 10929.40219 | 13115.28262 | 0.83694 | 1.00433 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27032E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 15048.48012 | 18058.17614 | 0.66650 | 0.79980 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10000 | 1.27032E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 72839.70570 | 87407.64684 | 3.25745 | 3.90894 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | -32.70000 | 1.83376E-004 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 22765.97 | 1.77074 | 1.77074 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 50521.26 | 1.63456 | 1.63456 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 111651.05 | 8.06690 | 8.06690 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 206349.97 | 4.01137 | 4.01137 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 17155.85 | 1.23900 | 1.23900 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 28756.40 | 0.79984 | 0.79984 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 14147.93 | 1.00433 | 1.00433 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 28755.63 | 0.79980 | 0.79980 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.72712 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.90514 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.23900 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00433 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.90894 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 3.90894 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 87508.79042 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.72712 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.72712 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.72712 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.72712 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.77074 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.77074 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.97537 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.90514 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.90514 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.90514 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.90514 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.06690 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 8.06690 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97995 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.23900 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.23900 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.23900 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.23900 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.23900 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.23900 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00433 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00433 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00433 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00433 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00433 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00433 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.77074 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 8.06690 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.23900 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.00433 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.77074 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.77074 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.77074 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.77074 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.16869 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.77074 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.88537 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.18049 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 31216.30361 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 33476.47000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16738.23500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 16738.23500 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75292 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75292 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75292 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75292 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33476.47000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 52566.48319 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.77074 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1894.77444 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 52566.48319 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.06690 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.06690 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.06690 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.06690 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.32415 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 8.06690 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.03345 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.37793 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 152966.56160 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 163086.63000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 81543.31500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 81543.31500 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73204 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73204 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73204 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73204 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 163086.63000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 292643.53395 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 8.06690 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 13590.42074 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 292643.53395 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.23900 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.23900 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.23900 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.23900 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.23900 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.23900 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61950 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.82600 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 20804.17496 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22401.40000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11200.70000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11200.70000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76761 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76761 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76761 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76761 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22401.40000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 38463.27214 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.23900 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1371.77237 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 38463.27214 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00433 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00433 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00433 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00433 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00433 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00433 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50217 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66955 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17630.32824 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18912.72000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9456.36000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9456.36000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75419 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75419 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75419 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75419 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18912.72000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33276.24274 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00433 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1111.94990 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 33276.24274 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 32086.1 | 11.41 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 156746.0 | 12.68 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 21429.2 | 110.98 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 18124.2 | 147.13 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 25 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.166 | 0.159 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 3.309E-002 | 3.283E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1591.92 | 1600.48 | 1593.79 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
32 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
33 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
34 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
40 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.41_SHGC_0.45 | N/A | 2.330 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.191 | 0.183 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.41_SHGC_0.45 | N/A | 2.330 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.191 | 0.183 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
56 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
57 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
58 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.41_SHGC_0.45 | N/A | 2.330 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.315 | 0.292 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | |
1 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C4 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
2 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C1 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
3 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C2 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
4 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C3 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
5 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C3 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
6 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C1 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
7 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C4 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
8 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C2 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 7 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 0.3106774859 | 0.5943202816 | Pass | Pass | 0.2924211944 | 0.4394113448 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 0.1238262565 | 0.3369556598 | Pass | Pass | 0.5395036630 | 3.6569579323 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 0.2976919722 | 0.6565445716 | Pass | Pass | 0.4967064255 | 1.0743494501 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 0.3204419869 | 0.6681319277 | Pass | Pass | 0.4533848096 | 1.3134277999 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1951413843 | 0.5160927469 | Pass | Pass | 0.1201475902 | 0.5491206810 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 1600.48 | 1591.92 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.166 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.033 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.191 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.191 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.315 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.68 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.680 | 0.680 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.41_SHGC_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.330 | 0.445 | 0.451 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.41_SHGC_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.330 | 0.445 | 0.451 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.41_SHGC_0.45 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.330 | 0.445 | 0.451 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 92.49 | 2.649 | 0.467 | 0.472 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 92.49 | 2.649 | 0.467 | 0.472 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.5670 | 379.89 | 2874.64 | LightsWired | BLDG_LIGHT_BACK_SCH | 63.14 | 168.00 | 62.27 | 0.0000 | Y | 33.60 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 18.0834 | 1600.48 | 28942.12 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 64.78 | 0.0000 | Y | 351.92 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 18.0834 | 150.81 | 2727.15 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.94 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 18.0834 | 150.81 | 2727.15 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.94 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 9.6875 | 12.00 | 116.25 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 57.54 | 168.00 | 56.76 | 0.0000 | Y | 1.24 |
Interior Lighting Total | 16.2979 | 2293.99 | 37387.32 | 456.64 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.17 | 28942.12 | 4989.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 316.30 | AstronomicalClock | - | 42.55 | 42.55 | 2.53 | |
EXTERIOR_LIGHTS_B | 4328.00 | AstronomicalClock | - | 83.52 | 71.23 | 57.87 | |
Exterior Lighting Total | 4644.30 | 60.39 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 33476.47 | 25205.10 | 8271.37 | 0.75 | 3.80 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 163086.63 | 119385.94 | 43700.69 | 0.73 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22401.40 | 17195.54 | 5205.86 | 0.77 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18912.72 | 14263.78 | 4648.94 | 0.75 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 32086.1 | 11.41 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 156746.0 | 12.68 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 21429.2 | 110.98 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 18124.2 | 147.13 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 87508.79 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 52566.48 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 292643.53 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 38463.27 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 33276.24 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.60 | 1018.41 | 3.91 | 6678.80 | 1708.60 | 1.00 | 1.17 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.77 | 1894.77 | 1070.05 | 1.00 | 1.33 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 8.07 | 13590.42 | 1684.71 | 1.00 | 1.15 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.24 | 1371.77 | 1107.16 | 1.00 | 1.35 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1111.95 | 1107.16 | 1.00 | 1.40 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 19591.01 | 23509.21 | 61.88 | 1.439 | 1.727 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01021 | 20.92 | 0.01270 | 0.232 | 0.00 |
CORE_RETAIL | 89436.51 | 107323.82 | 67.06 | 6.588 | 7.905 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00967 | 20.92 | 0.01270 | 1.890 | 0.00 |
POINT_OF_SALE | 13483.25 | 16179.90 | 107.29 | 1.033 | 1.239 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00893 | 29.79 | 0.01270 | 0.178 | 0.00 |
FRONT_RETAIL | 10929.40 | 13115.28 | 86.97 | 0.837 | 1.004 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00903 | 29.79 | 0.01270 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 100.00 | 0.00001 | 30.10 | 0.01270 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 30839.42 | 37007.31 | 97.42 | 1.362 | 1.635 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00788 | -32.70 | 0.00018 | 0.232 | 0.00 |
CORE_RETAIL | 76554.12 | 91864.95 | 57.40 | 3.343 | 4.011 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00788 | -32.70 | 0.00018 | 1.890 | 0.00 |
POINT_OF_SALE | 15049.12 | 18058.95 | 119.75 | 0.667 | 0.800 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00792 | -32.70 | 0.00018 | 0.178 | 0.00 |
FRONT_RETAIL | 15048.48 | 18058.18 | 119.74 | 0.667 | 0.800 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00792 | -32.70 | 0.00018 | 0.178 | 0.00 |
FRONT_ENTRY | 72839.71 | 87407.65 | 7283.97 | 3.257 | 3.909 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 21.11 | 20.97 | 0.00597 | -32.70 | 0.00018 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.77 | 1.77 | 1.63 | 1.63 | 1.7707 | 1.7271 | 1.7707 | 0.9754 | 1.0000 |
PSZ-AC:2 | 8.07 | 8.07 | 4.01 | 4.01 | 8.0669 | 7.9051 | 8.0669 | 0.9799 | 1.0000 |
PSZ-AC:3 | 1.24 | 1.24 | 0.80 | 0.80 | 1.2390 | 1.2390 | 1.2390 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.00 | 1.00 | 0.80 | 0.80 | 1.0043 | 1.0043 | 1.0043 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 87508.790 | 87508.790 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 87508.79 | 87508.79 | 3.908936 | 20.78 | 12.41 | 0.00594714 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 20.97 | 0.00596811 | 37.1502 | 87407.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 16738.235 | 0.000 | 1.770740 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 16738.24 | 13576.59 | 1.770740 | 24.76 | 17.27 | 0.00978861 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 13.0774 | 23.88 | 0.01021311 | 52.9098 | 19591.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 52566.483 | 52566.483 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52566.48 | 52566.48 | 1.770739 | 13.34 | 10.20 | 0.00679070 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 13.0774 | 21.11 | 0.00788125 | 48.5058 | 30839.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 81543.315 | 0.000 | 8.066900 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 81543.32 | 64182.75 | 8.066900 | 25.43 | 17.71 | 0.01006787 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 23.4317 | 23.89 | 0.00966928 | 50.1309 | 82979.40 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 292643.534 | 292643.534 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 292643.53 | 292643.53 | 8.066898 | -4.36 | -4.36 | 0.00425333 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 23.4317 | 21.11 | 0.00788015 | 48.4986 | 76554.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 11200.700 | 0.000 | 1.239000 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 11200.70 | 9523.18 | 1.239000 | 24.75 | 17.01 | 0.00947386 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01270324 | 21.04 | 14.3753 | 23.89 | 0.00893071 | 46.3484 | 13471.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 38463.272 | 38463.272 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38463.27 | 38463.27 | 1.239002 | 8.99 | 7.60 | 0.00619476 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 14.3753 | 21.11 | 0.00791688 | 48.7220 | 15049.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 9456.360 | 0.000 | 1.004330 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 9456.36 | 7809.79 | 1.004330 | 24.97 | 17.25 | 0.00968413 | 12.80 | 11.72 | 0.00850000 | 30.00 | 0.01270324 | 21.07 | 17.7343 | 23.89 | 0.00903084 | 46.8607 | 10907.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 33276.243 | 33276.243 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33276.24 | 33276.24 | 1.004327 | 8.99 | 7.60 | 0.00619468 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 17.7343 | 21.11 | 0.00791687 | 48.7220 | 15048.48 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 87508.790 | 87508.790 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 3.908936 | 4.51061830 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 87508.79 | 87508.79 | 1.0000 | 4.51061830 | 3.908936 | 20.78 | 12.41 | 0.00594714 | 35983.5 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87508.79 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00596811 | 20.97 | 0.00596811 | 37.1502 | 87407.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16738.235 | 0.000 | 1.770740 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0365 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 16738.24 | 13576.59 | 1.0000 | 2.04330090 | 1.770740 | 24.76 | 17.27 | 0.00978861 | 49815.7 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16738.24 | 30.10 | 0.01270324 | 21.10 | 0.23156651 | 13.0774 | 23.89 | 0.00930974 | 23.88 | 0.01021311 | 52.9098 | 19591.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52566.483 | 52566.483 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.770739 | 2.04329975 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52566.48 | 52566.48 | 1.0000 | 2.04329975 | 1.770739 | 13.34 | 10.20 | 0.00679070 | 30560.4 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52566.48 | -32.70 | 0.00018338 | -32.70 | 0.23156651 | 13.0774 | 20.94 | 0.00788125 | 21.11 | 0.00788125 | 48.5058 | 30839.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 81543.315 | 0.000 | 8.066900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5557 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 81543.32 | 64182.75 | 1.0000 | 9.30859643 | 8.066900 | 25.43 | 17.71 | 0.01006787 | 51205.9 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81543.32 | 30.10 | 0.01270324 | 21.10 | 1.89021192 | 23.4317 | 23.89 | 0.00919927 | 23.89 | 0.00966928 | 50.1309 | 82979.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 292643.534 | 292643.534 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.066898 | 9.30859383 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 292643.53 | 292643.53 | 1.0000 | 9.30859383 | 8.066898 | -4.36 | -4.36 | 0.00425333 | 6217.9 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 292643.53 | -32.70 | 0.00018338 | -32.70 | 1.89021192 | 23.4317 | 20.89 | 0.00788015 | 21.11 | 0.00788015 | 48.4986 | 76554.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11200.700 | 0.000 | 1.239000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.4514 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 11200.70 | 9523.18 | 1.0000 | 1.42971290 | 1.239000 | 24.75 | 17.01 | 0.00947386 | 49001.3 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11200.70 | 29.89 | 0.01270324 | 21.04 | 0.17811053 | 14.3753 | 23.89 | 0.00893113 | 23.89 | 0.00893071 | 46.3484 | 13471.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38463.272 | 38463.272 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.239002 | 1.42971571 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38463.27 | 38463.27 | 1.0000 | 1.42971571 | 1.239002 | 8.99 | 7.60 | 0.00619476 | 24633.5 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38463.27 | -32.70 | 0.00018338 | -32.70 | 0.17811053 | 14.3753 | 20.94 | 0.00791688 | 21.11 | 0.00791688 | 48.7220 | 15049.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9456.360 | 0.000 | 1.004330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8423 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 9456.36 | 7809.79 | 1.0000 | 1.15892135 | 1.004330 | 24.97 | 17.25 | 0.00968413 | 49763.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9456.36 | 30.00 | 0.01270324 | 21.07 | 0.17811053 | 17.7343 | 23.89 | 0.00903168 | 23.89 | 0.00903084 | 46.8607 | 10907.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33276.243 | 33276.243 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.004327 | 1.15891840 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33276.24 | 33276.24 | 1.0000 | 1.15891840 | 1.004327 | 8.99 | 7.60 | 0.00619468 | 24632.8 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33276.24 | -32.70 | 0.00018338 | -32.70 | 0.17811053 | 17.7343 | 20.94 | 0.00791687 | 21.11 | 0.00791687 | 48.7220 | 15048.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.77 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 1.89 | 8.07 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.24 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.00 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 3107.67 | 3895.33 | 2573.33 |
CORE_RETAIL | 2938.67 | 3448.83 | 1934.50 |
POINT_OF_SALE | 2970.50 | 3200.50 | 1790.83 |
FRONT_RETAIL | 3082.33 | 3479.17 | 2108.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3738.33 | 3924.17 | 2604.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 92.00 | 0.33 | 0.00 | 0.00 |
CORE_RETAIL | 0.67 | 17.33 | 0.00 | 0.00 |
POINT_OF_SALE | 67.33 | 21.33 | 0.00 | 0.00 |
FRONT_RETAIL | 91.83 | 2.83 | 0.00 | 0.00 |
FRONT_ENTRY | 0.17 | 0.00 | 0.00 | 0.00 |
Facility | 148.33 | 38.67 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.47 | 61.34 | 2317.33 | 0.525 | 0.030 | 0.000 | 0.000 |
CORE_RETAIL | 128.37 | 258.43 | 9762.95 | 0.848 | 0.006 | 0.000 | 0.000 |
POINT_OF_SALE | 12.10 | 24.35 | 919.94 | 1.366 | 0.033 | 0.000 | 0.000 |
FRONT_RETAIL | 12.10 | 24.35 | 919.94 | 1.112 | 0.033 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.47 | 61.34 | 2317.33 | 0.352 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.37 | 258.43 | 9762.95 | 0.682 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.10 | 24.35 | 919.94 | 0.682 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.10 | 24.35 | 919.94 | 0.682 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 11 | 11 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1053.50 | 3566.84 | 28-MAY-06:10 | 101098.61 | 29-JUN-16:00 |
Electricity:Building | 651.27 | 3483.68 | 28-MAY-07:30 | 44140.05 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 83.46 | 599.86 | 01-JAN-00:10 | 5099.20 | 02-JAN-09:10 |
InteriorLights:Electricity | 456.64 | 1703.05 | 28-MAY-07:30 | 33387.34 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 33.60 | 143.73 | 01-JAN-00:10 | 2344.76 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 456.64 | 1703.05 | 28-MAY-07:30 | 33387.34 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 435.99 | 2049.94 | 28-MAY-07:30 | 30692.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 351.92 | 1280.79 | 28-MAY-07:30 | 26047.91 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 87.72 | 619.23 | 01-JAN-00:10 | 5370.36 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 34.94 | 136.36 | 01-JAN-00:10 | 2454.44 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 42.86 | 208.83 | 01-JAN-00:10 | 2892.10 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 34.94 | 136.36 | 01-JAN-00:10 | 2454.44 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.24 | 5.81 | 01-JAN-00:10 | 85.79 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.24 | 5.81 | 01-JAN-00:10 | 85.79 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 194.63 | 1780.63 | 01-JAN-00:10 | 10752.72 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.86 | 456.13 | 01-JAN-00:10 | 2754.45 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 194.63 | 1780.63 | 01-JAN-00:10 | 10752.72 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.07 | 769.15 | 01-JAN-00:10 | 4644.69 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.78 | 482.87 | 01-JAN-00:10 | 2915.92 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.92 | 72.48 | 01-JAN-00:10 | 437.66 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1053.50 | 3566.84 | 28-MAY-06:10 | 101098.61 | 29-JUN-16:00 |
ElectricityPurchased:Plant | 1053.50 | 3566.84 | 28-MAY-06:10 | 101098.61 | 29-JUN-16:00 |
Cogeneration:ElectricityPurchased | 1053.50 | 3566.84 | 28-MAY-06:10 | 101098.61 | 29-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1053.50 | 3566.84 | 28-MAY-06:10 | 101098.61 | 29-JUN-16:00 |
ElectricityNet:Plant | 1053.50 | 3566.84 | 28-MAY-06:10 | 101098.61 | 29-JUN-16:00 |
Cogeneration:ElectricityNet | 1053.50 | 3566.84 | 28-MAY-06:10 | 101098.61 | 29-JUN-16:00 |
Electricity:HVAC | 341.83 | 0.00 | 01-JAN-20:10 | 58455.44 | 29-JUN-16:00 |
Fans:Electricity | 265.18 | 0.00 | 01-JAN-20:10 | 21001.02 | 01-JAN-09:10 |
General:Fans:Electricity | 265.18 | 0.00 | 01-JAN-20:10 | 21001.02 | 01-JAN-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 76.65 | 0.00 | 01-JAN-00:10 | 46443.95 | 29-JUN-16:00 |
ExteriorLights:Electricity | 60.39 | 0.00 | 01-JAN-08:20 | 4644.30 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.39 | 0.00 | 01-JAN-08:20 | 4644.30 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1138.22 | 1860.00 | 03-JAN-21:10 | 327031.47 | 09-JAN-07:10 |
Gas:Plant | 100.69 | 1860.00 | 01-JAN-21:00 | 6347.39 | 24-FEB-12:50 |
WaterSystems:Gas | 100.69 | 1860.00 | 01-JAN-21:00 | 6347.39 | 24-FEB-12:50 |
Water Heater:WaterSystems:Gas | 100.69 | 1860.00 | 01-JAN-21:00 | 6347.39 | 24-FEB-12:50 |
Gas:HVAC | 1037.53 | 0.00 | 01-JAN-00:40 | 325171.47 | 09-JAN-07:10 |
Heating:Gas | 1037.53 | 0.00 | 01-JAN-00:40 | 325171.47 | 09-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAR-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1924.35 | 0.00 | 01-JAN-20:10 | 381971.67 | 09-JAN-07:10 |
EnergyTransfer:Building | 796.22 | 0.00 | 01-JAN-20:10 | 173928.08 | 09-JAN-05:10 |
EnergyTransfer:Zone:BACK_SPACE | 120.13 | 0.00 | 01-JAN-00:40 | 53122.00 | 25-DEC-07:20 |
Heating:EnergyTransfer | 361.00 | 0.00 | 01-JAN-20:10 | 173928.08 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 81.78 | 0.00 | 01-JAN-00:40 | 53122.00 | 25-DEC-07:20 |
Cooling:EnergyTransfer | 435.21 | 0.00 | 01-JAN-00:10 | 79693.44 | 30-JUN-14:40 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 38.35 | 0.00 | 01-JAN-00:10 | 11762.30 | 30-JUN-15:00 |
EnergyTransfer:Zone:CORE_RETAIL | 373.09 | 0.00 | 01-JAN-00:10 | 96526.82 | 01-JAN-08:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 63.86 | 0.00 | 01-JAN-00:10 | 96526.82 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 309.23 | 0.00 | 01-JAN-00:10 | 58746.41 | 16-JUN-20:20 |
EnergyTransfer:Zone:POINT_OF_SALE | 73.27 | 0.00 | 01-JAN-00:40 | 22869.81 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 18.12 | 0.00 | 01-JAN-00:40 | 22869.81 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 55.14 | 0.00 | 01-JAN-00:10 | 11326.20 | 01-SEP-13:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 60.39 | 0.00 | 01-JAN-00:40 | 24230.13 | 24-DEC-07:20 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 27.91 | 0.00 | 01-JAN-00:40 | 24230.13 | 24-DEC-07:20 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 32.49 | 0.00 | 01-JAN-00:10 | 9318.62 | 01-SEP-13:30 |
EnergyTransfer:Zone:FRONT_ENTRY | 169.34 | 0.00 | 01-JAN-20:10 | 66105.83 | 05-JAN-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 169.34 | 0.00 | 01-JAN-20:10 | 66105.83 | 05-JAN-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1128.13 | 0.00 | 01-JAN-00:40 | 260137.18 | 09-JAN-07:10 |
HeatingCoils:EnergyTransfer | 830.02 | 0.00 | 01-JAN-00:40 | 260137.18 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 298.11 | 0.00 | 01-JAN-00:10 | 172981.09 | 30-JUN-15:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 81.777 | -38.351 | 0.000 | 0.000 | 40.343 | 33.603 | 49.857 | 0.000 | 0.000 | 0.098 | 0.001 | 0.000 | 0.000 | 0.000 | -23.841 | -143.486 |
CORE_RETAIL | 0.000 | 0.000 | 63.858 | -309.227 | 0.000 | 0.000 | 169.459 | 351.917 | 84.072 | 13.744 | 0.000 | 0.079 | 0.005 | 0.000 | -15.745 | 0.000 | -20.526 | -337.631 |
POINT_OF_SALE | 0.000 | 0.000 | 18.123 | -55.144 | 0.000 | 0.000 | 15.654 | 34.941 | 52.780 | 38.221 | 0.000 | 0.042 | 0.003 | 0.000 | -29.693 | 0.000 | -10.677 | -64.246 |
FRONT_RETAIL | 0.000 | 0.000 | 27.906 | -32.487 | 0.000 | 0.000 | 15.898 | 34.941 | 7.922 | 38.281 | 0.000 | 0.042 | 0.003 | 0.000 | -29.233 | 0.000 | -10.459 | -52.810 |
FRONT_ENTRY | 169.339 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.239 | 0.000 | 7.695 | 0.000 | 0.039 | 0.000 | 0.000 | -6.078 | 0.000 | -167.831 | -4.402 |
Total Facility | 169.339 | 0.000 | 191.664 | -435.209 | 0.000 | 0.000 | 241.354 | 456.640 | 194.630 | 97.940 | 0.000 | 0.301 | 0.012 | 0.000 | -80.750 | 0.000 | -233.335 | -602.574 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 02-JUL-18:30 | 0.00 | 0.00 | 0.00 | -25768.77 | 0.00 | 0.00 | 0.00 | 143.73 | 456.13 | 0.00 | 0.00 | 0.00 | 25218.69 | 0.00 | -0.00 | 0.00 | -49.78 | 0.00 |
CORE_RETAIL | 21-MAY-18:31 | 0.00 | 0.00 | 0.00 | -165569.79 | 0.00 | 0.00 | 0.00 | 1447.11 | 769.15 | 0.00 | 0.00 | 0.00 | 163609.87 | 0.00 | -22.80 | 0.00 | -233.55 | 0.00 |
POINT_OF_SALE | 04-SEP-18:10 | 0.00 | 0.00 | 0.00 | -26561.24 | 0.00 | 0.00 | 0.00 | 136.36 | 482.87 | 0.00 | 0.00 | 0.00 | 26873.88 | 0.00 | -634.68 | 0.00 | -297.19 | 0.00 |
FRONT_RETAIL | 04-SEP-19:01 | 0.00 | 0.00 | 0.00 | -23144.83 | 0.00 | 0.00 | 0.00 | 136.36 | 72.48 | 0.00 | 0.00 | 0.00 | 24214.82 | 0.00 | -1025.31 | 0.00 | -253.52 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-MAY-20:18 | 0.00 | 0.00 | 0.00 | -177550.32 | 0.00 | 0.00 | 0.00 | 7477.46 | 2374.18 | 0.00 | 0.00 | 0.00 | 170128.70 | 0.00 | -1701.51 | 0.00 | -728.51 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 04-JAN-05:41 | 0.00 | 0.00 | 56973.15 | 0.00 | 0.00 | 0.00 | 0.00 | 143.73 | 608.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7482.20 | -50242.86 |
CORE_RETAIL | 26-DEC-05:41 | 0.00 | 0.00 | 302060.87 | 0.00 | 0.00 | 0.00 | 0.00 | 1447.11 | 1025.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1545.01 | 0.00 | -2211.23 | -300777.27 |
POINT_OF_SALE | 25-DEC-07:21 | 0.00 | 0.00 | 41192.99 | 0.00 | 0.00 | 0.00 | 0.00 | 136.36 | 482.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3242.03 | 0.00 | -1669.53 | -36900.66 |
FRONT_RETAIL | 08-JAN-07:31 | 0.00 | 0.00 | 35274.30 | 0.00 | 0.00 | 0.00 | 0.00 | 136.36 | 72.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2891.34 | 0.00 | -1721.72 | -30870.07 |
FRONT_ENTRY | 05-JAN-18:00 | 66105.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.79 | 0.00 | 0.00 | 0.00 | 0.00 | 106.17 | 0.00 | -725.85 | 0.00 | -65571.91 | 0.00 |
Total Facility | 01-JAN-07:01 | 5817.59 | 0.00 | 424339.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1869.37 | 1780.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8381.47 | 0.00 | -9278.18 | -416147.15 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.7271 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.7707 | 0.1308 | 1.0000 | 0.2316 | 0.1308 | ||
PSZ-AC:2 | 7.9051 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.0669 | 0.2343 | 1.0000 | 1.8902 | 0.2343 | ||
PSZ-AC:3 | 1.2390 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.2390 | 0.1438 | 1.0000 | 0.1781 | 0.1438 | ||
PSZ-AC:4 | 1.0043 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0043 | 0.1773 | 1.0000 | 0.1781 | 0.1773 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.7271 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.7271 | 1.0000 | 1.0000 | 0.2316 | 0.1341 | ||
PSZ-AC:2 | 7.9051 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.9051 | 1.0000 | 1.0000 | 1.8902 | 0.2391 | ||
PSZ-AC:3 | 1.2390 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.2390 | 1.0000 | 1.0000 | 0.1781 | 0.1438 | ||
PSZ-AC:4 | 1.0043 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0043 | 1.0000 | 1.0000 | 0.1781 | 0.1773 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.7271 | 1.7271 | 1.7271 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.9051 | 7.9051 | 7.9051 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.2390 | 1.2390 | 1.2390 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0043 | 1.0043 | 1.0043 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.7271 | 1.7707 | 1.7271 | 1.7271 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.9051 | 8.0669 | 7.9051 | 7.9051 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.2390 | 1.2390 | 1.2390 | 1.2390 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0043 | 1.0043 | 1.0043 | 1.0043 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.7271 | 1.7271 | 1.7271 | 0.2316 | 0.1417 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.9051 | 7.9051 | 7.9051 | 1.8902 | 0.4712 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.2390 | 1.2390 | 1.2390 | 0.1781 | 0.2227 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0043 | 1.0043 | 1.0043 | 0.1781 | 0.2227 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.7271 | 1.7271 | 1.7271 | 1.7271 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.9051 | 7.9051 | 7.9051 | 7.9051 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.2390 | 1.2390 | 1.2390 | 1.2390 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0043 | 1.0043 | 1.0043 | 1.0043 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1037.53 | 325171.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 76.65 | 46443.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 456.64 | 33387.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.39 | 4644.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 194.63 | 10752.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 265.18 | 21001.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 100.69 | 6347.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 194.63 | 1053.50 |
Natural Gas | 0.00 | 1138.22 |
Additional | 0.00 | 0.00 |
Total | 194.63 | 2191.72 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 199.06 |
Space Heating | 0.00 |
Space Cooling | 33.41 |
Fans (All) | 115.60 |
Service Water Heating | 0.00 |
Receptacle Equipment | 84.84 |
Miscellaneous (All) | 459.24 |
Subtotal | 459.24 |
Natural Gas [MJ/m2] | |
Space Heating | 452.28 |
Service Water Heating | 43.89 |
Miscellaneous (All) | 496.17 |
Subtotal | 496.17 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 20.83 |
Space Heating | 47.34 |
Space Cooling | 3.50 |
Fans (All) | 12.10 |
Service Water Heating | 4.59 |
Receptacle Equipment | 8.88 |
Miscellaneous | 2.76 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3292. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3001. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4559. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_SETBACK | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_SCH_PSZ_AC_2 | CORE_RETAIL DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.269866E+12 |
February | 0.000 | 0.181940E+12 |
March | 0.000 | 0.145403E+12 |
April | 0.000 | 0.482984E+11 |
May | 0.000 | 0.341344E+10 |
June | 0.000 | 0.966164E+08 |
July | 0.000 | 0.274609E+08 |
August | 0.000 | 0.101088E+09 |
September | 0.000 | 0.128008E+10 |
October | 0.000 | 0.330151E+11 |
November | 0.000 | 0.106750E+12 |
December | 0.000 | 0.247339E+12 |
Annual Sum or Average | 0.103753E+13 | |
Minimum of Months | 0.000 | 0.274609E+08 |
Maximum of Months | 0.000 | 0.269866E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.269866E+12 |
February | 0.000 | 0.181940E+12 |
March | 0.000 | 0.145403E+12 |
April | 0.000 | 0.482984E+11 |
May | 0.000 | 0.341344E+10 |
June | 0.000 | 0.966164E+08 |
July | 0.000 | 0.274609E+08 |
August | 0.000 | 0.101088E+09 |
September | 0.000 | 0.128008E+10 |
October | 0.000 | 0.330151E+11 |
November | 0.000 | 0.106750E+12 |
December | 0.000 | 0.247339E+12 |
Annual Sum or Average | 0.103753E+13 | |
Minimum of Months | 0.000 | 0.274609E+08 |
Maximum of Months | 0.000 | 0.269866E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.269866E+12 |
February | 0.000 | 0.181940E+12 |
March | 0.000 | 0.145403E+12 |
April | 0.000 | 0.482984E+11 |
May | 0.000 | 0.341344E+10 |
June | 0.000 | 0.966164E+08 |
July | 0.000 | 0.274609E+08 |
August | 0.000 | 0.101088E+09 |
September | 0.000 | 0.128008E+10 |
October | 0.000 | 0.330151E+11 |
November | 0.000 | 0.106750E+12 |
December | 0.000 | 0.247339E+12 |
Annual Sum or Average | 0.103753E+13 | |
Minimum of Months | 0.000 | 0.274609E+08 |
Maximum of Months | 0.000 | 0.269866E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.269866E+12 |
February | 0.000 | 0.181940E+12 |
March | 0.000 | 0.145403E+12 |
April | 0.000 | 0.482984E+11 |
May | 0.000 | 0.341344E+10 |
June | 0.000 | 0.966164E+08 |
July | 0.000 | 0.274609E+08 |
August | 0.000 | 0.101088E+09 |
September | 0.000 | 0.128008E+10 |
October | 0.000 | 0.330151E+11 |
November | 0.000 | 0.106750E+12 |
December | 0.000 | 0.247339E+12 |
Annual Sum or Average | 0.103753E+13 | |
Minimum of Months | 0.000 | 0.274609E+08 |
Maximum of Months | 0.000 | 0.269866E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.269866E+12 |
February | 0.000 | 0.181940E+12 |
March | 0.000 | 0.145403E+12 |
April | 0.000 | 0.482984E+11 |
May | 0.000 | 0.341344E+10 |
June | 0.000 | 0.966164E+08 |
July | 0.000 | 0.274609E+08 |
August | 0.000 | 0.101088E+09 |
September | 0.000 | 0.128008E+10 |
October | 0.000 | 0.330151E+11 |
November | 0.000 | 0.106750E+12 |
December | 0.000 | 0.247339E+12 |
Annual Sum or Average | 0.103753E+13 | |
Minimum of Months | 0.000 | 0.274609E+08 |
Maximum of Months | 0.000 | 0.269866E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.269866E+12 |
February | 0.000 | 0.181940E+12 |
March | 0.000 | 0.145403E+12 |
April | 0.000 | 0.482984E+11 |
May | 0.000 | 0.341344E+10 |
June | 0.000 | 0.966164E+08 |
July | 0.000 | 0.274609E+08 |
August | 0.000 | 0.101088E+09 |
September | 0.000 | 0.128008E+10 |
October | 0.000 | 0.330151E+11 |
November | 0.000 | 0.106750E+12 |
December | 0.000 | 0.247339E+12 |
Annual Sum or Average | 0.103753E+13 | |
Minimum of Months | 0.000 | 0.274609E+08 |
Maximum of Months | 0.000 | 0.269866E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.269866E+12 |
February | 0.000 | 0.181940E+12 |
March | 0.000 | 0.145403E+12 |
April | 0.000 | 0.482984E+11 |
May | 0.000 | 0.341344E+10 |
June | 0.000 | 0.966164E+08 |
July | 0.000 | 0.274609E+08 |
August | 0.000 | 0.101088E+09 |
September | 0.000 | 0.128008E+10 |
October | 0.000 | 0.330151E+11 |
November | 0.000 | 0.106750E+12 |
December | 0.000 | 0.247339E+12 |
Annual Sum or Average | 0.103753E+13 | |
Minimum of Months | 0.000 | 0.274609E+08 |
Maximum of Months | 0.000 | 0.269866E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.269866E+12 |
February | 0.000 | 0.181940E+12 |
March | 0.000 | 0.145403E+12 |
April | 0.000 | 0.482984E+11 |
May | 0.000 | 0.341344E+10 |
June | 0.000 | 0.966164E+08 |
July | 0.000 | 0.274609E+08 |
August | 0.000 | 0.101088E+09 |
September | 0.000 | 0.128008E+10 |
October | 0.000 | 0.330151E+11 |
November | 0.000 | 0.106750E+12 |
December | 0.000 | 0.247339E+12 |
Annual Sum or Average | 0.103753E+13 | |
Minimum of Months | 0.000 | 0.274609E+08 |
Maximum of Months | 0.000 | 0.269866E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.269866E+12 |
February | 0.000 | 0.181940E+12 |
March | 0.000 | 0.145403E+12 |
April | 0.000 | 0.482984E+11 |
May | 0.000 | 0.341344E+10 |
June | 0.000 | 0.966164E+08 |
July | 0.000 | 0.274609E+08 |
August | 0.000 | 0.101088E+09 |
September | 0.000 | 0.128008E+10 |
October | 0.000 | 0.330151E+11 |
November | 0.000 | 0.106750E+12 |
December | 0.000 | 0.247339E+12 |
Annual Sum or Average | 0.103753E+13 | |
Minimum of Months | 0.000 | 0.274609E+08 |
Maximum of Months | 0.000 | 0.269866E+12 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -21.9 | -22.1 | 0.165228E+10 | 1854.44 | 20-JAN-15:20 | -5.2 | -6.8 |
February | 7270276.57 | 925.13 | 08-FEB-15:20 | 4.80 | -0.3 | 0.150875E+10 | 1854.44 | 10-FEB-15:00 | -11.1 | -12.6 |
March | 0.170505E+09 | 4180.12 | 20-MAR-12:45 | 1.70 | -1.0 | 0.172574E+10 | 1861.49 | 31-MAR-14:00 | 8.30 | 2.61 |
April | 0.122160E+10 | 3740.93 | 24-APR-10:10 | 4.50 | 2.71 | 0.171514E+10 | 2451.24 | 13-APR-14:00 | 20.00 | 8.07 |
May | 0.434699E+10 | 25428.38 | 25-MAY-20:31 | 23.53 | 16.77 | 0.210887E+10 | 2451.25 | 22-MAY-14:30 | 20.20 | 14.04 |
June | 0.694697E+10 | 23109.49 | 28-JUN-23:09 | 22.12 | 18.40 | 0.218599E+10 | 2451.26 | 07-JUN-14:09 | 22.20 | 14.32 |
July | 0.929477E+10 | 25770.27 | 02-JUL-18:30 | 21.95 | 16.45 | 0.218474E+10 | 2451.32 | 25-JUL-14:30 | 23.05 | 20.24 |
August | 0.830842E+10 | 24555.32 | 11-AUG-20:41 | 19.40 | 17.19 | 0.227624E+10 | 2451.26 | 10-AUG-14:09 | 18.95 | 16.67 |
September | 0.496490E+10 | 19053.02 | 01-SEP-20:33 | 15.57 | 14.65 | 0.207753E+10 | 2451.28 | 02-SEP-13:50 | 15.33 | 13.44 |
October | 0.254164E+10 | 4190.10 | 21-OCT-06:03 | 2.20 | 1.76 | 0.178467E+10 | 2451.24 | 21-OCT-12:50 | 19.13 | 11.25 |
November | 0.548088E+09 | 5025.56 | 22-NOV-11:33 | -1.3 | -4.3 | 0.159923E+10 | 2256.39 | 01-NOV-14:00 | 18.30 | 13.43 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 | 0.165478E+10 | 1854.45 | 01-DEC-15:00 | -18.7 | -19.3 |
Annual Sum or Average | 0.383511E+11 | 0.224740E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -21.9 | -22.1 | 0.150875E+10 | 1854.44 | -18.7 | -19.3 | ||
Maximum of Months | 0.929477E+10 | 25770.27 | 23.53 | 18.40 | 0.227624E+10 | 2451.32 | 23.05 | 20.24 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317923E+10 | 58910.31 | 22-JAN-09:05 | -11.9 | -12.5 | 0.695904E+10 | 7812.80 | 04-JAN-15:09 | -27.7 | -27.9 |
February | 0.685106E+10 | 74033.42 | 28-FEB-07:04 | -14.9 | -15.3 | 0.635449E+10 | 7812.80 | 25-FEB-11:09 | -18.0 | -18.9 |
March | 0.140669E+11 | 80588.38 | 18-MAR-06:04 | -20.2 | -20.4 | 0.727332E+10 | 8340.37 | 31-MAR-14:00 | 8.30 | 2.61 |
April | 0.238423E+11 | 65304.39 | 05-APR-06:05 | -13.5 | -14.0 | 0.748234E+10 | 10327.10 | 13-APR-14:30 | 19.45 | 7.74 |
May | 0.365088E+11 | 165569.84 | 21-MAY-18:31 | 19.83 | 10.40 | 0.903292E+10 | 10327.13 | 15-MAY-14:09 | 21.72 | 13.93 |
June | 0.442548E+11 | 134867.36 | 06-JUN-22:41 | 20.10 | 14.99 | 0.924021E+10 | 10327.26 | 07-JUN-14:09 | 22.20 | 14.32 |
July | 0.505293E+11 | 140533.63 | 16-JUL-18:17 | 19.03 | 14.35 | 0.920466E+10 | 10327.79 | 27-JUL-14:09 | 16.97 | 15.85 |
August | 0.481951E+11 | 136381.81 | 06-AUG-18:18 | 19.63 | 14.98 | 0.958720E+10 | 10327.16 | 10-AUG-14:09 | 18.95 | 16.67 |
September | 0.362567E+11 | 145763.83 | 07-SEP-20:54 | 18.90 | 13.68 | 0.875733E+10 | 10327.58 | 02-SEP-13:50 | 15.33 | 13.44 |
October | 0.270733E+11 | 62889.50 | 30-OCT-06:04 | -9.4 | -9.8 | 0.756294E+10 | 10327.09 | 21-OCT-12:50 | 19.13 | 11.25 |
November | 0.140204E+11 | 63725.92 | 24-NOV-07:04 | -10.0 | -10.7 | 0.676837E+10 | 10326.92 | 01-NOV-14:00 | 18.30 | 13.43 |
December | 0.445124E+10 | 88391.22 | 18-DEC-13:42 | -22.8 | -23.4 | 0.696958E+10 | 7812.80 | 23-DEC-11:09 | -15.4 | -16.0 |
Annual Sum or Average | 0.309229E+12 | 0.951924E+11 | ||||||||
Minimum of Months | 0.317923E+10 | 58910.31 | -22.8 | -23.4 | 0.635449E+10 | 7812.80 | -27.7 | -27.9 | ||
Maximum of Months | 0.505293E+11 | 165569.84 | 20.10 | 14.99 | 0.958720E+10 | 10327.79 | 22.20 | 16.67 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104008E+10 | 6699.43 | 27-JAN-09:32 | -20.6 | -20.9 | 0.655929E+09 | 736.18 | 14-JAN-15:50 | -12.9 | -13.4 |
February | 0.175686E+10 | 7373.51 | 01-FEB-18:22 | -24.1 | -24.6 | 0.622262E+09 | 973.09 | 04-FEB-16:19 | 7.60 | 2.44 |
March | 0.240419E+10 | 5099.40 | 18-MAR-08:32 | -12.6 | -13.5 | 0.724680E+09 | 973.08 | 28-MAR-14:09 | 6.20 | 2.92 |
April | 0.346500E+10 | 20329.42 | 23-APR-19:51 | 21.70 | 14.25 | 0.765917E+09 | 973.10 | 22-APR-10:30 | 14.15 | 5.07 |
May | 0.596532E+10 | 22541.44 | 16-MAY-20:11 | 19.53 | 12.53 | 0.875388E+09 | 973.13 | 19-MAY-14:00 | 17.80 | 14.99 |
June | 0.735741E+10 | 21647.20 | 08-JUN-20:11 | 18.87 | 13.51 | 0.873323E+09 | 973.15 | 23-JUN-14:09 | 22.38 | 20.08 |
July | 0.915541E+10 | 22558.28 | 07-JUL-20:12 | 15.77 | 12.06 | 0.868263E+09 | 973.25 | 25-JUL-14:30 | 23.05 | 20.24 |
August | 0.931078E+10 | 21247.74 | 04-AUG-20:10 | 16.42 | 12.71 | 0.905265E+09 | 973.26 | 10-AUG-14:09 | 18.95 | 16.67 |
September | 0.703271E+10 | 26562.52 | 04-SEP-18:10 | 14.03 | 8.90 | 0.850649E+09 | 973.18 | 02-SEP-13:50 | 15.33 | 13.44 |
October | 0.442498E+10 | 26482.58 | 22-OCT-18:08 | 12.75 | 9.21 | 0.797230E+09 | 973.11 | 07-OCT-10:50 | 12.12 | 11.47 |
November | 0.233834E+10 | 5428.31 | 17-NOV-13:30 | 10.30 | 3.30 | 0.687089E+09 | 973.09 | 14-NOV-15:09 | 10.73 | 6.42 |
December | 0.893837E+09 | 7164.75 | 10-DEC-16:02 | -23.0 | -23.5 | 0.657262E+09 | 754.37 | 28-DEC-15:09 | -1.8 | -3.6 |
Annual Sum or Average | 0.551449E+11 | 0.928326E+10 | ||||||||
Minimum of Months | 0.893837E+09 | 5099.40 | -24.1 | -24.6 | 0.622262E+09 | 736.18 | -12.9 | -13.4 | ||
Maximum of Months | 0.931078E+10 | 26562.52 | 21.70 | 14.25 | 0.905265E+09 | 973.26 | 23.05 | 20.24 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303125E+09 | 6627.83 | 31-JAN-14:02 | -18.5 | -19.1 | 0.655927E+09 | 736.18 | 04-JAN-15:00 | -27.2 | -27.5 |
February | 0.736846E+09 | 5655.09 | 14-FEB-16:53 | -13.9 | -15.4 | 0.605675E+09 | 932.79 | 28-FEB-15:50 | 6.10 | 1.53 |
March | 0.108032E+10 | 3935.26 | 18-MAR-12:30 | -2.8 | -6.0 | 0.696451E+09 | 973.01 | 31-MAR-14:00 | 8.30 | 2.61 |
April | 0.182483E+10 | 4815.01 | 22-APR-13:40 | 17.23 | 7.20 | 0.719738E+09 | 973.10 | 13-APR-14:30 | 19.45 | 7.74 |
May | 0.341177E+10 | 18816.59 | 16-MAY-20:20 | 19.53 | 12.53 | 0.850098E+09 | 973.11 | 26-MAY-14:30 | 20.45 | 15.78 |
June | 0.451761E+10 | 18057.99 | 08-JUN-20:16 | 18.87 | 13.51 | 0.868855E+09 | 973.13 | 06-JUN-14:20 | 20.20 | 14.72 |
July | 0.606303E+10 | 18718.92 | 07-JUL-20:12 | 15.77 | 12.06 | 0.867399E+09 | 973.23 | 25-JUL-14:30 | 23.05 | 20.24 |
August | 0.615327E+10 | 18695.01 | 05-AUG-21:22 | 15.60 | 12.08 | 0.903626E+09 | 973.21 | 10-AUG-14:09 | 18.95 | 16.67 |
September | 0.451668E+10 | 23145.96 | 04-SEP-19:01 | 12.02 | 8.53 | 0.829148E+09 | 973.15 | 02-SEP-13:30 | 17.20 | 13.96 |
October | 0.264713E+10 | 7591.63 | 20-OCT-14:03 | 18.90 | 10.05 | 0.736480E+09 | 973.10 | 21-OCT-10:09 | 12.35 | 8.15 |
November | 0.101242E+10 | 4047.41 | 10-NOV-12:20 | -3.1 | -5.2 | 0.649119E+09 | 973.10 | 01-NOV-14:00 | 18.30 | 13.43 |
December | 0.220801E+09 | 7395.63 | 10-DEC-15:12 | -22.4 | -23.0 | 0.656922E+09 | 736.18 | 09-DEC-12:30 | -14.9 | -15.7 |
Annual Sum or Average | 0.324878E+11 | 0.903944E+10 | ||||||||
Minimum of Months | 0.220801E+09 | 3935.26 | -22.4 | -23.0 | 0.605675E+09 | 736.18 | -27.2 | -27.5 | ||
Maximum of Months | 0.615327E+10 | 23145.96 | 19.53 | 13.51 | 0.903626E+09 | 973.23 | 23.05 | 20.24 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -23.1 | -23.4 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 | 13.56 | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.56 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.4 | 0.00 | 0.00 | -23.1 | -23.4 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.00 | 0.00 | 19.75 | 18.15 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215375E+11 | 56972.70 | 04-JAN-05:41 | -28.8 |
February | 0.153222E+11 | 56080.95 | 19-FEB-07:41 | -23.8 |
March | 0.118661E+11 | 55578.16 | 08-MAR-05:41 | -19.2 |
April | 0.443567E+10 | 54118.90 | 07-APR-04:42 | -6.1 |
May | 0.440361E+09 | 53220.44 | 01-MAY-04:12 | -3.0 |
June | 60337431.32 | 967.41 | 30-JUN-05:10 | 26.20 |
July | 33454248.73 | 996.24 | 21-JUL-05:07 | 17.98 |
August | 52376953.99 | 1055.67 | 31-AUG-05:07 | 16.70 |
September | 76241900.09 | 11239.98 | 28-SEP-05:02 | 6.70 |
October | 0.172551E+10 | 53663.97 | 30-OCT-04:11 | -10.0 |
November | 0.735983E+10 | 55310.67 | 26-NOV-07:41 | -9.5 |
December | 0.188670E+11 | 56240.47 | 16-DEC-05:41 | -15.7 |
Annual Sum or Average | 0.817766E+11 | |||
Minimum of Months | 33454248.73 | 967.41 | -28.8 | |
Maximum of Months | 0.215375E+11 | 56972.70 | 26.20 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199505E+11 | 298992.94 | 01-JAN-07:01 | -27.6 |
February | 0.114197E+11 | 298635.35 | 14-FEB-05:01 | -32.1 |
March | 0.721070E+10 | 298539.15 | 06-MAR-05:01 | -18.4 |
April | 0.184149E+10 | 248790.80 | 04-APR-05:02 | -9.0 |
May | 0.466362E+09 | 98893.41 | 01-MAY-06:03 | -3.5 |
June | 0.145905E+09 | 7469.37 | 30-JUN-05:05 | 26.20 |
July | 0.107924E+09 | 6925.52 | 16-JUL-07:03 | 17.38 |
August | 0.141657E+09 | 6898.13 | 14-AUG-05:04 | 15.92 |
September | 0.313158E+09 | 6577.85 | 03-SEP-07:04 | 14.50 |
October | 0.969481E+09 | 200375.74 | 30-OCT-06:02 | -9.4 |
November | 0.486712E+10 | 296537.94 | 25-NOV-06:01 | -19.4 |
December | 0.164246E+11 | 302060.60 | 26-DEC-05:41 | -26.5 |
Annual Sum or Average | 0.638586E+11 | |||
Minimum of Months | 0.107924E+09 | 6577.85 | -32.1 | |
Maximum of Months | 0.199505E+11 | 302060.60 | 26.20 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.513171E+10 | 40906.00 | 04-JAN-05:41 | -28.8 |
February | 0.300159E+10 | 39654.10 | 24-FEB-05:51 | -22.8 |
March | 0.226370E+10 | 39635.64 | 08-MAR-05:51 | -18.9 |
April | 0.827220E+09 | 38247.49 | 28-APR-04:01 | -4.9 |
May | 0.136548E+09 | 38224.99 | 01-MAY-04:01 | -2.9 |
June | 49081001.38 | 1556.38 | 28-JUN-05:04 | 15.15 |
July | 11205708.13 | 1580.78 | 20-JUL-05:04 | 15.37 |
August | 14802773.76 | 1605.20 | 29-AUG-05:03 | 14.40 |
September | 61024455.55 | 1543.11 | 01-SEP-05:04 | 15.68 |
October | 0.349415E+09 | 38245.57 | 30-OCT-04:01 | -10.0 |
November | 0.158939E+10 | 38870.53 | 23-NOV-07:42 | -10.0 |
December | 0.468757E+10 | 41192.85 | 25-DEC-07:21 | -28.3 |
Annual Sum or Average | 0.181232E+11 | |||
Minimum of Months | 11205708.13 | 1543.11 | -28.8 | |
Maximum of Months | 0.513171E+10 | 41192.85 | 15.68 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.744528E+10 | 35274.25 | 08-JAN-07:31 | -22.8 |
February | 0.456258E+10 | 34487.19 | 03-FEB-05:41 | -11.6 |
March | 0.361153E+10 | 34749.65 | 15-MAR-05:01 | -22.2 |
April | 0.141975E+10 | 33650.35 | 05-APR-04:11 | -12.6 |
May | 0.210486E+09 | 33259.56 | 01-MAY-04:01 | -2.9 |
June | 70516884.61 | 1087.16 | 11-JUN-07:53 | 10.60 |
July | 31729574.12 | 1209.07 | 30-JUL-07:07 | 21.65 |
August | 29148590.39 | 1214.17 | 10-AUG-05:05 | 15.50 |
September | 87898467.51 | 5932.64 | 29-SEP-05:02 | 7.20 |
October | 0.698168E+09 | 33271.98 | 30-OCT-04:01 | -10.0 |
November | 0.266302E+10 | 34066.34 | 23-NOV-07:42 | -10.0 |
December | 0.707556E+10 | 35205.41 | 10-DEC-07:41 | -26.5 |
Annual Sum or Average | 0.279057E+11 | |||
Minimum of Months | 29148590.39 | 1087.16 | -26.5 | |
Maximum of Months | 0.744528E+10 | 35274.25 | 21.65 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.350485E+11 | 66105.83 | 05-JAN-18:00 | -28.3 |
February | 0.246295E+11 | 57622.52 | 01-FEB-18:00 | -23.3 |
March | 0.224592E+11 | 46021.35 | 15-MAR-11:10 | -15.3 |
April | 0.118145E+11 | 33430.91 | 04-APR-11:04 | -4.9 |
May | 0.396084E+10 | 17239.76 | 01-MAY-11:10 | 6.72 |
June | 0.144025E+10 | 10357.80 | 09-JUN-11:03 | 12.38 |
July | 0.627678E+09 | 9287.77 | 08-JUL-11:10 | 13.30 |
August | 0.106838E+10 | 11312.65 | 17-AUG-12:00 | 10.60 |
September | 0.455616E+10 | 16202.24 | 27-SEP-11:04 | 7.38 |
October | 0.113019E+11 | 27556.83 | 29-OCT-11:03 | 0.68 |
November | 0.187887E+11 | 46026.68 | 25-NOV-17:00 | -15.6 |
December | 0.336428E+11 | 63511.08 | 24-DEC-12:10 | -26.9 |
Annual Sum or Average | 0.169338E+12 | |||
Minimum of Months | 0.627678E+09 | 9287.77 | -28.3 | |
Maximum of Months | 0.350485E+11 | 66105.83 | 13.30 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.281822E+10 | 2344.76 | 02-JAN-09:09 | 0.420015E+10 | 2754.45 | 02-JAN-09:09 |
February | 0.256399E+10 | 2344.76 | 01-FEB-09:09 | 0.381055E+10 | 2754.45 | 01-FEB-09:09 |
March | 0.292411E+10 | 2344.76 | 01-MAR-09:09 | 0.430594E+10 | 2754.45 | 01-MAR-09:09 |
April | 0.275920E+10 | 2344.76 | 01-APR-09:09 | 0.409182E+10 | 2754.45 | 01-APR-09:09 |
May | 0.287117E+10 | 2344.76 | 01-MAY-08:09 | 0.425304E+10 | 2754.45 | 01-MAY-08:09 |
June | 0.282172E+10 | 2344.76 | 01-JUN-08:09 | 0.415844E+10 | 2754.45 | 01-JUN-08:09 |
July | 0.280865E+10 | 2344.76 | 01-JUL-09:09 | 0.418643E+10 | 2754.45 | 01-JUL-09:09 |
August | 0.292411E+10 | 2344.76 | 01-AUG-08:09 | 0.430594E+10 | 2754.45 | 01-AUG-08:09 |
September | 0.275920E+10 | 2344.76 | 01-SEP-08:09 | 0.409182E+10 | 2754.45 | 01-SEP-08:09 |
October | 0.281822E+10 | 2344.76 | 02-OCT-08:09 | 0.420015E+10 | 2754.45 | 02-OCT-08:09 |
November | 0.272540E+10 | 2344.76 | 01-NOV-08:09 | 0.406638E+10 | 2754.45 | 01-NOV-08:09 |
December | 0.280865E+10 | 2344.76 | 01-DEC-09:09 | 0.418643E+10 | 2754.45 | 01-DEC-09:09 |
Annual Sum or Average | 0.336027E+11 | 0.498571E+11 | ||||
Minimum of Months | 0.256399E+10 | 2344.76 | 0.381055E+10 | 2754.45 | ||
Maximum of Months | 0.292411E+10 | 2344.76 | 0.430594E+10 | 2754.45 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.306408E+11 | 26047.91 | 02-JAN-09:09 | 0.708251E+10 | 4644.69 | 02-JAN-09:09 |
February | 0.276438E+11 | 26047.91 | 01-FEB-09:09 | 0.642555E+10 | 4644.69 | 01-FEB-09:09 |
March | 0.311682E+11 | 26047.91 | 01-MAR-09:09 | 0.726089E+10 | 4644.69 | 01-MAR-09:09 |
April | 0.287630E+11 | 26047.91 | 01-APR-16:40 | 0.689984E+10 | 4644.69 | 01-APR-09:09 |
May | 0.285817E+11 | 26047.91 | 01-MAY-15:00 | 0.717170E+10 | 4644.69 | 01-MAY-08:09 |
June | 0.282282E+11 | 26047.91 | 08-JUN-16:30 | 0.701217E+10 | 4644.69 | 01-JUN-08:09 |
July | 0.279469E+11 | 26047.91 | 11-JUL-16:30 | 0.705936E+10 | 4644.69 | 01-JUL-09:09 |
August | 0.297945E+11 | 26047.91 | 02-AUG-16:30 | 0.726089E+10 | 4644.69 | 01-AUG-08:09 |
September | 0.288860E+11 | 26047.91 | 01-SEP-08:09 | 0.689984E+10 | 4644.69 | 01-SEP-08:09 |
October | 0.301130E+11 | 26047.91 | 02-OCT-08:09 | 0.708251E+10 | 4644.69 | 02-OCT-08:09 |
November | 0.295839E+11 | 26047.91 | 01-NOV-08:09 | 0.685694E+10 | 4644.69 | 01-NOV-08:09 |
December | 0.305668E+11 | 26047.91 | 01-DEC-09:09 | 0.705936E+10 | 4644.69 | 01-DEC-09:09 |
Annual Sum or Average | 0.351917E+12 | 0.840716E+11 | ||||
Minimum of Months | 0.276438E+11 | 26047.91 | 0.642555E+10 | 4644.69 | ||
Maximum of Months | 0.311682E+11 | 26047.91 | 0.726089E+10 | 4644.69 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.293011E+10 | 2454.44 | 02-JAN-09:09 | 0.444637E+10 | 2915.92 | 02-JAN-09:09 |
February | 0.266601E+10 | 2454.44 | 01-FEB-09:09 | 0.403394E+10 | 2915.92 | 01-FEB-09:09 |
March | 0.304105E+10 | 2454.44 | 01-MAR-09:09 | 0.455836E+10 | 2915.92 | 01-MAR-09:09 |
April | 0.286924E+10 | 2454.44 | 01-APR-09:09 | 0.433169E+10 | 2915.92 | 01-APR-09:09 |
May | 0.298558E+10 | 2454.44 | 01-MAY-08:09 | 0.450237E+10 | 2915.92 | 01-MAY-08:09 |
June | 0.293453E+10 | 2454.44 | 01-JUN-08:09 | 0.440222E+10 | 2915.92 | 01-JUN-08:09 |
July | 0.292029E+10 | 2454.44 | 01-JUL-09:09 | 0.443184E+10 | 2915.92 | 01-JUL-09:09 |
August | 0.304105E+10 | 2454.44 | 01-AUG-08:09 | 0.455836E+10 | 2915.92 | 01-AUG-08:09 |
September | 0.286924E+10 | 2454.44 | 01-SEP-08:09 | 0.433169E+10 | 2915.92 | 01-SEP-08:09 |
October | 0.293011E+10 | 2454.44 | 02-OCT-08:09 | 0.444637E+10 | 2915.92 | 02-OCT-08:09 |
November | 0.283340E+10 | 2454.44 | 01-NOV-08:09 | 0.430476E+10 | 2915.92 | 01-NOV-08:09 |
December | 0.292029E+10 | 2454.44 | 01-DEC-09:09 | 0.443184E+10 | 2915.92 | 01-DEC-09:09 |
Annual Sum or Average | 0.349409E+11 | 0.527798E+11 | ||||
Minimum of Months | 0.266601E+10 | 2454.44 | 0.403394E+10 | 2915.92 | ||
Maximum of Months | 0.304105E+10 | 2454.44 | 0.455836E+10 | 2915.92 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.293011E+10 | 2454.44 | 02-JAN-09:09 | 0.667369E+09 | 437.66 | 02-JAN-09:09 |
February | 0.266601E+10 | 2454.44 | 01-FEB-09:09 | 0.605465E+09 | 437.66 | 01-FEB-09:09 |
March | 0.304105E+10 | 2454.44 | 01-MAR-09:09 | 0.684178E+09 | 437.66 | 01-MAR-09:09 |
April | 0.286924E+10 | 2454.44 | 01-APR-09:09 | 0.650156E+09 | 437.66 | 01-APR-09:09 |
May | 0.298558E+10 | 2454.44 | 01-MAY-08:09 | 0.675774E+09 | 437.66 | 01-MAY-08:09 |
June | 0.293453E+10 | 2454.44 | 01-JUN-08:09 | 0.660742E+09 | 437.66 | 01-JUN-08:09 |
July | 0.292029E+10 | 2454.44 | 01-JUL-09:09 | 0.665188E+09 | 437.66 | 01-JUL-09:09 |
August | 0.304105E+10 | 2454.44 | 01-AUG-08:09 | 0.684178E+09 | 437.66 | 01-AUG-08:09 |
September | 0.286924E+10 | 2454.44 | 01-SEP-08:09 | 0.650156E+09 | 437.66 | 01-SEP-08:09 |
October | 0.293011E+10 | 2454.44 | 02-OCT-08:09 | 0.667369E+09 | 437.66 | 02-OCT-08:09 |
November | 0.283340E+10 | 2454.44 | 01-NOV-08:09 | 0.646114E+09 | 437.66 | 01-NOV-08:09 |
December | 0.292029E+10 | 2454.44 | 01-DEC-09:09 | 0.665188E+09 | 437.66 | 01-DEC-09:09 |
Annual Sum or Average | 0.349409E+11 | 0.792188E+10 | ||||
Minimum of Months | 0.266601E+10 | 2454.44 | 0.605465E+09 | 437.66 | ||
Maximum of Months | 0.304105E+10 | 2454.44 | 0.684178E+09 | 437.66 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.103900E+09 | 85.79 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 94517577.03 | 85.79 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.107770E+09 | 85.79 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.101704E+09 | 85.79 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.105835E+09 | 85.79 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.103997E+09 | 85.79 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.103541E+09 | 85.79 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.107770E+09 | 85.79 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.101704E+09 | 85.79 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.103900E+09 | 85.79 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.100485E+09 | 85.79 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.103541E+09 | 85.79 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.123866E+10 | ||||
Minimum of Months | 94517577.03 | 85.79 | 0.00 | 0.00 | |
Maximum of Months | 0.107770E+09 | 85.79 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.281822E+10 | 0.420015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401544E+10 |
February | 0.479114E+10 | 0.256399E+10 | 0.381055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346502E+10 |
March | 0.548013E+10 | 0.292411E+10 | 0.430594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245371E+10 |
April | 0.518069E+10 | 0.275920E+10 | 0.409182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2226383.92 | 0.199091E+10 |
May | 0.536353E+10 | 0.287117E+10 | 0.425304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8314011.73 | 0.985570E+09 |
June | 0.528933E+10 | 0.282172E+10 | 0.415844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38281773.08 | 0.559262E+09 |
July | 0.525489E+10 | 0.280865E+10 | 0.418643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35077757.20 | 0.374913E+09 |
August | 0.548013E+10 | 0.292411E+10 | 0.430594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13326000.63 | 0.592087E+09 |
September | 0.518069E+10 | 0.275920E+10 | 0.409182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 433297.60 | 0.103536E+10 |
October | 0.524694E+10 | 0.281822E+10 | 0.420015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147638E+10 |
November | 0.504819E+10 | 0.272540E+10 | 0.406638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273770E+10 |
December | 0.525489E+10 | 0.280865E+10 | 0.418643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415442E+10 |
Annual Sum or Average | 0.628175E+11 | 0.336027E+11 | 0.498571E+11 | 97659224.16 | 0.238408E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.256399E+10 | 0.381055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374913E+09 |
Maximum of Months | 0.548013E+10 | 0.292411E+10 | 0.430594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38281773.08 | 0.415442E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.306408E+11 | 0.708251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338742E+10 |
February | 0.201852E+11 | 0.276438E+11 | 0.642555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295707E+10 |
March | 0.230879E+11 | 0.311682E+11 | 0.726089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211585E+10 |
April | 0.218263E+11 | 0.287630E+11 | 0.689984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1338836.40 | 0.177691E+10 |
May | 0.225967E+11 | 0.285817E+11 | 0.717170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6810914.93 | 0.896685E+09 |
June | 0.222841E+11 | 0.282282E+11 | 0.701217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31323856.35 | 0.495248E+09 |
July | 0.221389E+11 | 0.279469E+11 | 0.705936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28705261.41 | 0.310152E+09 |
August | 0.230879E+11 | 0.297945E+11 | 0.726089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10904765.83 | 0.497878E+09 |
September | 0.218263E+11 | 0.288860E+11 | 0.689984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 354686.92 | 0.909234E+09 |
October | 0.221054E+11 | 0.301130E+11 | 0.708251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128874E+10 |
November | 0.212681E+11 | 0.295839E+11 | 0.685694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237151E+10 |
December | 0.221389E+11 | 0.305668E+11 | 0.705936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351946E+10 |
Annual Sum or Average | 0.264651E+12 | 0.351917E+12 | 0.840716E+11 | 79438321.85 | 0.205261E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.276438E+11 | 0.642555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310152E+09 |
Maximum of Months | 0.230879E+11 | 0.311682E+11 | 0.726089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31323856.35 | 0.351946E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.293011E+10 | 0.444637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175047E+10 |
February | 0.190200E+10 | 0.266601E+10 | 0.403394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152949E+10 |
March | 0.217552E+10 | 0.304105E+10 | 0.455836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110586E+10 |
April | 0.205665E+10 | 0.286924E+10 | 0.433169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 738961.28 | 0.930220E+09 |
May | 0.212923E+10 | 0.298558E+10 | 0.450237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3605592.62 | 0.463009E+09 |
June | 0.209978E+10 | 0.293453E+10 | 0.440222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16582775.56 | 0.256075E+09 |
July | 0.208610E+10 | 0.292029E+10 | 0.443184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15212255.37 | 0.162845E+09 |
August | 0.217552E+10 | 0.304105E+10 | 0.455836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5770923.59 | 0.262017E+09 |
September | 0.205665E+10 | 0.286924E+10 | 0.433169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 187854.81 | 0.481773E+09 |
October | 0.208295E+10 | 0.293011E+10 | 0.444637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696115E+09 |
November | 0.200405E+10 | 0.283340E+10 | 0.430476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123006E+10 |
December | 0.208610E+10 | 0.292029E+10 | 0.443184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180950E+10 |
Annual Sum or Average | 0.249375E+11 | 0.349409E+11 | 0.527798E+11 | 42098363.23 | 0.106774E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.266601E+10 | 0.403394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162845E+09 |
Maximum of Months | 0.217552E+10 | 0.304105E+10 | 0.455836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16582775.56 | 0.180950E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.293011E+10 | 0.667369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174038E+10 |
February | 0.190200E+10 | 0.266601E+10 | 0.605465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151447E+10 |
March | 0.217552E+10 | 0.304105E+10 | 0.684178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108309E+10 |
April | 0.205665E+10 | 0.286924E+10 | 0.650156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 714397.72 | 0.894049E+09 |
May | 0.212923E+10 | 0.298558E+10 | 0.675774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3607169.24 | 0.440160E+09 |
June | 0.209978E+10 | 0.293453E+10 | 0.660742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16584620.77 | 0.245588E+09 |
July | 0.208610E+10 | 0.292029E+10 | 0.665188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15213006.83 | 0.161800E+09 |
August | 0.217552E+10 | 0.304105E+10 | 0.684178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5772299.36 | 0.258621E+09 |
September | 0.205665E+10 | 0.286924E+10 | 0.650156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 187853.98 | 0.462171E+09 |
October | 0.208295E+10 | 0.293011E+10 | 0.667369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663298E+09 |
November | 0.200405E+10 | 0.283340E+10 | 0.646114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119709E+10 |
December | 0.208610E+10 | 0.292029E+10 | 0.665188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179813E+10 |
Annual Sum or Average | 0.249375E+11 | 0.349409E+11 | 0.792188E+10 | 42079347.90 | 0.104588E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.266601E+10 | 0.605465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161800E+09 |
Maximum of Months | 0.217552E+10 | 0.304105E+10 | 0.684178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16584620.77 | 0.179813E+10 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.103900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338519E+11 |
February | 0.00 | 94517577.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239519E+11 |
March | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218105E+11 |
April | 0.00 | 0.101704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117562E+11 |
May | 0.00 | 0.105835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1451349.72 | 0.434036E+10 |
June | 0.00 | 0.103997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26953805.40 | 0.183280E+10 |
July | 0.00 | 0.103541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10192807.35 | 0.106219E+10 |
August | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727340.10 | 0.171943E+10 |
September | 0.00 | 0.101704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527630E+10 |
October | 0.00 | 0.103900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115087E+11 |
November | 0.00 | 0.100485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183011E+11 |
December | 0.00 | 0.103541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324200E+11 |
Annual Sum or Average | 0.00 | 0.123866E+10 | 39325302.57 | 0.167831E+12 | |||||
Minimum of Months | 0.00 | 94517577.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106219E+10 |
Maximum of Months | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26953805.40 | 0.338519E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2344.76 | 02-JAN-09:09 | 2754.45 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 8509.95 | 04-JAN-06:00 |
February | 5888.82 | 01-FEB-15:09 | 2344.76 | 01-FEB-09:09 | 2754.45 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 9500.35 | 12-FEB-22:53 |
March | 5888.82 | 01-MAR-15:09 | 2344.76 | 01-MAR-09:09 | 2754.45 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5202.25 | 15-MAR-05:00 |
April | 5888.82 | 01-APR-10:09 | 2344.76 | 01-APR-09:09 | 2754.45 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 338.27 | 23-APR-18:10 | 3982.87 | 01-APR-21:02 |
May | 5888.82 | 01-MAY-14:09 | 2344.76 | 01-MAY-08:09 | 2754.45 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.15 | 24-MAY-15:00 | 1938.63 | 09-MAY-04:05 |
June | 5888.82 | 01-JUN-14:09 | 2344.76 | 01-JUN-08:09 | 2754.45 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 438.49 | 29-JUN-20:20 | 1345.62 | 09-JUN-20:10 |
July | 5888.82 | 01-JUL-10:09 | 2344.76 | 01-JUL-09:09 | 2754.45 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 456.81 | 23-JUL-18:03 | 1210.12 | 06-JUL-22:00 |
August | 5888.82 | 01-AUG-14:09 | 2344.76 | 01-AUG-08:09 | 2754.45 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 230.45 | 08-AUG-16:00 | 1756.38 | 27-AUG-06:00 |
September | 5888.82 | 01-SEP-14:09 | 2344.76 | 01-SEP-08:09 | 2754.45 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.05 | 01-SEP-15:00 | 2420.57 | 20-SEP-01:00 |
October | 5888.82 | 02-OCT-14:09 | 2344.76 | 02-OCT-08:09 | 2754.45 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3275.00 | 31-OCT-20:02 |
November | 5888.82 | 01-NOV-14:09 | 2344.76 | 01-NOV-08:09 | 2754.45 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5159.99 | 23-NOV-08:00 |
December | 5888.82 | 01-DEC-15:09 | 2344.76 | 01-DEC-09:09 | 2754.45 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8476.79 | 16-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2344.76 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1210.12 | |||||
Maximum of Months | 5888.82 | 2344.76 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 456.81 | 9500.35 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 26047.91 | 02-JAN-09:09 | 4644.69 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6513.02 | 04-JAN-05:51 |
February | 24809.68 | 01-FEB-15:09 | 26047.91 | 01-FEB-09:09 | 4644.69 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 8213.60 | 12-FEB-22:52 |
March | 24809.68 | 01-MAR-15:09 | 26047.91 | 01-MAR-09:09 | 4644.69 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3916.62 | 15-MAR-04:51 |
April | 24809.68 | 01-APR-10:09 | 26047.91 | 01-APR-16:40 | 4644.69 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 202.23 | 23-APR-18:05 | 3323.74 | 02-APR-01:00 |
May | 24809.68 | 01-MAY-14:09 | 26047.91 | 01-MAY-15:00 | 4644.69 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.90 | 24-MAY-15:00 | 1778.12 | 20-MAY-05:00 |
June | 24809.68 | 01-JUN-14:09 | 26047.91 | 08-JUN-16:30 | 4644.69 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 358.91 | 29-JUN-20:20 | 1228.64 | 10-JUN-22:00 |
July | 24809.68 | 01-JUL-10:09 | 26047.91 | 11-JUL-16:30 | 4644.69 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 373.83 | 23-JUL-18:03 | 937.79 | 06-JUL-04:00 |
August | 24809.68 | 01-AUG-14:09 | 26047.91 | 02-AUG-16:30 | 4644.69 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 188.64 | 08-AUG-16:00 | 1569.22 | 27-AUG-06:00 |
September | 24809.68 | 01-SEP-14:09 | 26047.91 | 01-SEP-08:09 | 4644.69 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.15 | 01-SEP-15:00 | 2203.16 | 20-SEP-01:00 |
October | 24809.68 | 02-OCT-14:09 | 26047.91 | 02-OCT-08:09 | 4644.69 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2716.19 | 31-OCT-20:55 |
November | 24809.68 | 01-NOV-14:09 | 26047.91 | 01-NOV-08:09 | 4644.69 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4784.77 | 22-NOV-02:00 |
December | 24809.68 | 01-DEC-15:09 | 26047.91 | 01-DEC-09:09 | 4644.69 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6374.74 | 16-DEC-05:54 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 26047.91 | 4644.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 937.79 | |||||
Maximum of Months | 24809.68 | 26047.91 | 4644.69 | 0.00 | 0.00 | 0.00 | 0.00 | 373.83 | 8213.60 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2454.44 | 02-JAN-09:09 | 2915.92 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3687.61 | 04-JAN-06:00 |
February | 2337.76 | 01-FEB-15:09 | 2454.44 | 01-FEB-09:09 | 2915.92 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 4074.85 | 12-FEB-22:52 |
March | 2337.76 | 01-MAR-15:09 | 2454.44 | 01-MAR-09:09 | 2915.92 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2254.29 | 15-MAR-04:59 |
April | 2337.76 | 01-APR-10:09 | 2454.44 | 01-APR-09:09 | 2915.92 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.41 | 23-APR-18:05 | 1731.89 | 01-APR-21:02 |
May | 2337.76 | 01-MAY-14:09 | 2454.44 | 01-MAY-08:09 | 2915.92 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.00 | 24-MAY-15:00 | 861.47 | 20-MAY-05:00 |
June | 2337.76 | 01-JUN-14:09 | 2454.44 | 01-JUN-08:09 | 2915.92 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.85 | 29-JUN-20:20 | 612.21 | 09-JUN-20:10 |
July | 2337.76 | 01-JUL-10:09 | 2454.44 | 01-JUL-09:09 | 2915.92 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 200.73 | 23-JUL-18:10 | 508.19 | 06-JUL-21:44 |
August | 2337.76 | 01-AUG-14:09 | 2454.44 | 01-AUG-08:09 | 2915.92 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.86 | 08-AUG-16:00 | 803.79 | 27-AUG-06:00 |
September | 2337.76 | 01-SEP-14:09 | 2454.44 | 01-SEP-08:09 | 2915.92 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 01-SEP-15:00 | 1088.79 | 20-SEP-01:00 |
October | 2337.76 | 02-OCT-14:09 | 2454.44 | 02-OCT-08:09 | 2915.92 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1421.25 | 31-OCT-20:02 |
November | 2337.76 | 01-NOV-14:09 | 2454.44 | 01-NOV-08:09 | 2915.92 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2288.44 | 22-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 2454.44 | 01-DEC-09:09 | 2915.92 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3673.24 | 16-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2454.44 | 2915.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.19 | |||||
Maximum of Months | 2337.76 | 2454.44 | 2915.92 | 0.00 | 0.00 | 0.00 | 0.00 | 200.73 | 4074.85 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2454.44 | 02-JAN-09:09 | 437.66 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3687.61 | 04-JAN-06:00 |
February | 2337.76 | 01-FEB-15:09 | 2454.44 | 01-FEB-09:09 | 437.66 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 4070.75 | 12-FEB-22:52 |
March | 2337.76 | 01-MAR-15:09 | 2454.44 | 01-MAR-09:09 | 437.66 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2233.78 | 15-MAR-04:51 |
April | 2337.76 | 01-APR-10:09 | 2454.44 | 01-APR-09:09 | 437.66 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.60 | 23-APR-18:05 | 1727.71 | 01-APR-21:02 |
May | 2337.76 | 01-MAY-14:09 | 2454.44 | 01-MAY-08:09 | 437.66 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.00 | 24-MAY-15:00 | 868.15 | 09-MAY-04:05 |
June | 2337.76 | 01-JUN-14:09 | 2454.44 | 01-JUN-08:09 | 437.66 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.95 | 29-JUN-20:20 | 581.06 | 09-JUN-20:10 |
July | 2337.76 | 01-JUL-10:09 | 2454.44 | 01-JUL-09:09 | 437.66 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 201.92 | 23-JUL-18:10 | 549.50 | 06-JUL-22:00 |
August | 2337.76 | 01-AUG-14:09 | 2454.44 | 01-AUG-08:09 | 437.66 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.86 | 08-AUG-16:00 | 780.44 | 27-AUG-06:00 |
September | 2337.76 | 01-SEP-14:09 | 2454.44 | 01-SEP-08:09 | 437.66 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 01-SEP-15:00 | 1039.72 | 20-SEP-01:00 |
October | 2337.76 | 02-OCT-14:09 | 2454.44 | 02-OCT-08:09 | 437.66 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1418.57 | 31-OCT-20:02 |
November | 2337.76 | 01-NOV-14:09 | 2454.44 | 01-NOV-08:09 | 437.66 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2235.98 | 23-NOV-08:00 |
December | 2337.76 | 01-DEC-15:09 | 2454.44 | 01-DEC-09:09 | 437.66 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3628.88 | 16-DEC-05:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2454.44 | 437.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.50 | |||||
Maximum of Months | 2337.76 | 2454.44 | 437.66 | 0.00 | 0.00 | 0.00 | 0.00 | 201.92 | 4070.75 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 85.79 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 65571.91 | 05-JAN-18:00 |
February | 0.00 | 01-FEB-00:10 | 85.79 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 57298.56 | 01-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 85.79 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 46211.49 | 15-MAR-11:10 |
April | 0.00 | 01-APR-00:10 | 85.79 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 35060.01 | 04-APR-11:02 |
May | 0.00 | 01-MAY-00:10 | 85.79 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.31 | 25-MAY-17:00 | 17566.07 | 01-MAY-11:10 |
June | 0.00 | 01-JUN-00:10 | 85.79 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 833.12 | 30-JUN-11:02 | 10917.81 | 09-JUN-11:03 |
July | 0.00 | 01-JUL-00:10 | 85.79 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.15 | 15-JUL-13:55 | 9581.58 | 08-JUL-11:10 |
August | 0.00 | 01-AUG-00:10 | 85.79 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.47 | 08-AUG-16:00 | 11974.51 | 17-AUG-11:02 |
September | 0.00 | 01-SEP-00:10 | 85.79 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 16951.28 | 27-SEP-11:02 |
October | 0.00 | 01-OCT-00:10 | 85.79 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 29498.28 | 29-OCT-11:01 |
November | 0.00 | 01-NOV-00:10 | 85.79 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 45558.42 | 25-NOV-17:00 |
December | 0.00 | 01-DEC-00:10 | 85.79 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 63794.90 | 24-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 85.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9581.58 | ||||
Maximum of Months | 0.00 | 85.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 833.12 | 65571.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 718.66 | 2280.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2727.58 |
February | 925.13 | 08-FEB-15:20 | 5888.82 | 2344.76 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.37 |
March | 4180.12 | 20-MAR-12:45 | 10305.43 | 4689.51 | 5508.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.37 |
April | 3740.93 | 24-APR-10:10 | 25763.57 | 11723.78 | 13772.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.78 |
May | 25428.38 | 25-MAY-20:31 | 0.00 | 4024.49 | 4257.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 |
June | 23109.49 | 28-JUN-23:09 | 0.00 | 1149.86 | 4865.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.12 |
July | 25770.27 | 02-JUL-18:30 | 0.00 | 862.39 | 2736.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.78 |
August | 24555.32 | 11-AUG-20:41 | 0.00 | 4599.42 | 4865.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.75 |
September | 19053.02 | 01-SEP-20:33 | 0.00 | 1724.78 | 1824.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4190.10 | 21-OCT-06:03 | 2208.31 | 781.59 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.83 |
November | 5025.56 | 22-NOV-11:33 | 15458.14 | 7034.27 | 8263.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 868.30 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 143.73 | 608.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2658.98 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 143.73 | 608.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25770.27 | 25763.57 | 11723.78 | 13772.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2727.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 58910.31 | 22-JAN-09:05 | 12404.84 | 11576.85 | 6192.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1064.57 |
February | 74033.42 | 28-FEB-07:04 | 15506.05 | 28942.12 | 10321.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.05 |
March | 80588.38 | 18-MAR-06:04 | 15506.05 | 14471.06 | 7741.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65304.39 | 05-APR-06:05 | 12404.84 | 23153.70 | 8257.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 165569.84 | 21-MAY-18:31 | 0.00 | 13023.96 | 6922.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.55 |
June | 134867.36 | 06-JUN-22:41 | 0.00 | 10129.74 | 7178.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.14 |
July | 140533.63 | 16-JUL-18:17 | 0.00 | 14471.06 | 7691.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559.47 |
August | 136381.81 | 06-AUG-18:18 | 0.00 | 14471.06 | 7691.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.02 |
September | 145763.83 | 07-SEP-20:54 | 0.00 | 57884.25 | 10255.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.84 |
October | 62889.50 | 30-OCT-06:04 | 15506.05 | 28942.12 | 10321.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.21 |
November | 63725.92 | 24-NOV-07:04 | 15506.05 | 28942.12 | 10321.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.01 |
December | 88391.22 | 18-DEC-13:42 | 130250.83 | 147306.15 | 27868.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1783.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 58910.31 | 0.00 | 10129.74 | 6192.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 165569.84 | 130250.83 | 147306.15 | 27868.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1783.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6699.43 | 27-JAN-09:32 | 7305.51 | 12272.19 | 14579.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.54 |
February | 7373.51 | 01-FEB-18:22 | 7305.51 | 6817.88 | 14579.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.45 |
March | 5099.40 | 18-MAR-08:32 | 5844.40 | 6545.17 | 10367.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20329.42 | 23-APR-19:51 | 0.00 | 1363.58 | 4828.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.30 |
May | 22541.44 | 16-MAY-20:11 | 0.00 | 5454.31 | 6438.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.80 |
June | 21647.20 | 08-JUN-20:11 | 0.00 | 5454.31 | 6438.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.95 |
July | 22558.28 | 07-JUL-20:12 | 0.00 | 2727.15 | 3219.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.43 |
August | 21247.74 | 04-AUG-20:10 | 0.00 | 1636.29 | 1931.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.46 |
September | 26562.52 | 04-SEP-18:10 | 0.00 | 545.43 | 1931.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.19 |
October | 26482.58 | 22-OCT-18:08 | 0.00 | 818.15 | 2897.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.01 |
November | 5428.31 | 17-NOV-13:30 | 2045.54 | 2454.44 | 2915.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.24 |
December | 7164.75 | 10-DEC-16:02 | 5844.40 | 8181.46 | 12959.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.96 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5099.40 | 0.00 | 545.43 | 1931.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26562.52 | 7305.51 | 12272.19 | 14579.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6627.83 | 31-JAN-14:02 | 10227.71 | 12272.19 | 2188.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.81 |
February | 5655.09 | 14-FEB-16:53 | 8182.17 | 9817.75 | 1750.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.82 |
March | 3935.26 | 18-MAR-12:30 | 2337.76 | 2454.44 | 437.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4815.01 | 22-APR-13:40 | 2337.76 | 2454.44 | 437.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.63 |
May | 18816.59 | 16-MAY-20:20 | 0.00 | 5454.31 | 966.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.76 |
June | 18057.99 | 08-JUN-20:16 | 0.00 | 5454.31 | 966.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.93 |
July | 18718.92 | 07-JUL-20:12 | 0.00 | 2727.15 | 483.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.80 |
August | 18695.01 | 05-AUG-21:22 | 0.00 | 818.15 | 434.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.46 |
September | 23145.96 | 04-SEP-19:01 | 0.00 | 954.50 | 507.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.52 |
October | 7591.63 | 20-OCT-14:03 | 7013.29 | 7363.31 | 1312.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.86 |
November | 4047.41 | 10-NOV-12:20 | 2045.54 | 2454.44 | 437.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.01 |
December | 7395.63 | 10-DEC-15:12 | 5844.40 | 8181.46 | 1945.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.81 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3935.26 | 0.00 | 818.15 | 434.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23145.96 | 10227.71 | 12272.19 | 2188.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 29.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.18 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 29.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.76 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.08 |
April | 0.00 | 01-APR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.86 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.04 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.24 |
July | 0.00 | 01-JUL-00:03 | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.46 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.60 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.25 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.33 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.04 | |
Maximum of Months | 0.00 | 0.00 | 29.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.76 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.923597E+11 | 67627.04 | 05-JAN-17:00 | 0.278681E+12 | 327031.47 | 09-JAN-07:10 |
February | 0.814119E+11 | 66994.72 | 01-FEB-17:00 | 0.189995E+12 | 305815.45 | 14-FEB-07:10 |
March | 0.889911E+11 | 66106.67 | 06-MAR-17:00 | 0.154386E+12 | 255733.71 | 06-MAR-07:10 |
April | 0.802344E+11 | 61963.44 | 13-APR-14:09 | 0.568233E+11 | 194792.93 | 05-APR-06:10 |
May | 0.839283E+11 | 81141.46 | 25-MAY-14:00 | 0.120335E+11 | 129841.76 | 01-MAY-06:10 |
June | 0.909360E+11 | 101098.61 | 29-JUN-15:00 | 0.828322E+10 | 8571.20 | 02-JUN-11:00 |
July | 0.987454E+11 | 93568.00 | 15-JUL-14:09 | 0.824260E+10 | 6871.13 | 08-JUL-11:00 |
August | 0.958381E+11 | 90837.99 | 08-AUG-15:30 | 0.832198E+10 | 10633.00 | 17-AUG-13:00 |
September | 0.807036E+11 | 80131.91 | 01-SEP-13:30 | 0.921347E+10 | 30701.44 | 23-SEP-06:49 |
October | 0.837062E+11 | 64924.24 | 31-OCT-16:00 | 0.413033E+11 | 169923.31 | 30-OCT-06:10 |
November | 0.847820E+11 | 66329.83 | 25-NOV-17:10 | 0.114934E+12 | 239413.69 | 25-NOV-07:10 |
December | 0.918622E+11 | 67247.48 | 19-DEC-17:00 | 0.256003E+12 | 307167.73 | 25-DEC-09:09 |
Annual Sum or Average | 0.105350E+13 | 0.113822E+13 | ||||
Minimum of Months | 0.802344E+11 | 61963.44 | 0.824260E+10 | 6871.13 | ||
Maximum of Months | 0.987454E+11 | 101098.61 | 0.278681E+12 | 327031.47 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.394232E+11 | 0.690792E+10 | 0.163964E+11 | 0.00 | 0.296322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.356343E+11 | 0.558583E+10 | 0.148755E+11 | 0.00 | 0.253163E+11 | 0.00 | 0.00 | 12.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.402821E+11 | 0.529728E+10 | 0.168094E+11 | 0.00 | 0.266023E+11 | 0.00 | 0.00 | 833.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373624E+11 | 0.423424E+10 | 0.159735E+11 | 0.00 | 0.223405E+11 | 0.00 | 0.00 | 0.323753E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.375298E+11 | 0.364892E+10 | 0.166029E+11 | 0.00 | 0.185424E+11 | 0.00 | 0.00 | 0.760420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.370230E+11 | 0.316256E+10 | 0.162336E+11 | 0.00 | 0.160727E+11 | 0.00 | 0.00 | 0.184442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.366997E+11 | 0.341824E+10 | 0.163428E+11 | 0.00 | 0.158115E+11 | 0.00 | 0.00 | 0.264733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.389085E+11 | 0.402126E+10 | 0.168094E+11 | 0.00 | 0.164611E+11 | 0.00 | 0.00 | 0.196379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.374854E+11 | 0.473583E+10 | 0.159735E+11 | 0.00 | 0.186995E+11 | 0.00 | 0.00 | 0.380942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.388953E+11 | 0.581837E+10 | 0.163964E+11 | 0.00 | 0.222381E+11 | 0.00 | 0.00 | 0.357984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.380766E+11 | 0.644121E+10 | 0.158742E+11 | 0.00 | 0.243900E+11 | 0.00 | 0.00 | 2693.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.393196E+11 | 0.712249E+10 | 0.163428E+11 | 0.00 | 0.290773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.456640E+12 | 0.603942E+11 | 0.194630E+12 | 0.265184E+12 | 0.00 | 0.766507E+11 | |||||||
Minimum of Months | 0.356343E+11 | 0.316256E+10 | 0.148755E+11 | 0.00 | 0.158115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.402821E+11 | 0.712249E+10 | 0.168094E+11 | 0.00 | 0.296322E+11 | 0.00 | 0.00 | 0.264733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.269866E+12 | 0.00 | 0.881471E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.181940E+12 | 0.00 | 0.805476E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.145403E+12 | 0.00 | 0.898296E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.482984E+11 | 0.00 | 0.852492E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.341344E+10 | 0.00 | 0.862003E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 96616415.86 | 0.00 | 0.818660E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 27460943.58 | 0.00 | 0.821513E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.101088E+09 | 0.00 | 0.822089E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.128008E+10 | 0.00 | 0.793339E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.330151E+11 | 0.00 | 0.828819E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.106750E+12 | 0.00 | 0.818390E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.247339E+12 | 0.00 | 0.866395E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.103753E+13 | 0.100689E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 27460943.58 | 0.00 | 0.793339E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.269866E+12 | 0.00 | 0.898296E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 33387.34 | 02-JAN-09:09 | 4644.30 | 01-JAN-06:10 | 10752.72 | 02-JAN-09:09 | 0.00 | 21001.02 | 01-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 33387.34 | 01-FEB-09:09 | 4644.30 | 01-FEB-06:10 | 10752.72 | 01-FEB-09:09 | 0.00 | 19907.78 | 14-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 33387.34 | 01-MAR-09:09 | 4644.30 | 01-MAR-06:10 | 10752.72 | 01-MAR-09:09 | 0.00 | 19737.04 | 05-MAR-09:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 33387.34 | 01-APR-16:40 | 4644.30 | 01-APR-05:10 | 10752.72 | 01-APR-09:09 | 0.00 | 18120.70 | 02-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 33387.34 | 01-MAY-15:00 | 4644.30 | 01-MAY-19:30 | 10752.72 | 01-MAY-08:09 | 0.00 | 16752.29 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 33387.34 | 08-JUN-16:30 | 4644.30 | 01-JUN-19:00 | 10752.72 | 01-JUN-08:09 | 0.00 | 15356.60 | 02-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 33387.34 | 11-JUL-16:30 | 4644.30 | 01-JUL-20:19 | 10752.72 | 01-JUL-09:09 | 0.00 | 15356.60 | 01-JUL-12:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 33387.34 | 02-AUG-16:30 | 4644.30 | 01-AUG-19:49 | 10752.72 | 01-AUG-08:09 | 0.00 | 15356.60 | 02-AUG-11:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 33387.34 | 01-SEP-08:09 | 4644.30 | 01-SEP-05:10 | 10752.72 | 01-SEP-08:09 | 0.00 | 15687.45 | 23-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 33387.34 | 02-OCT-08:09 | 4644.30 | 01-OCT-05:10 | 10752.72 | 02-OCT-08:09 | 0.00 | 17583.84 | 30-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 33387.34 | 01-NOV-08:09 | 4644.30 | 01-NOV-05:10 | 10752.72 | 01-NOV-08:09 | 0.00 | 18779.66 | 26-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 33387.34 | 01-DEC-09:09 | 4644.30 | 01-DEC-06:10 | 10752.72 | 01-DEC-09:09 | 0.00 | 20886.26 | 25-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 33387.34 | 4644.30 | 10752.72 | 0.00 | 15356.60 | 0.00 | 0.00 | |||||
Maximum of Months | 33387.34 | 4644.30 | 10752.72 | 0.00 | 21001.02 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.02 | 08-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.10 | 31-MAR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14314.03 | 23-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29820.50 | 25-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46443.95 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42464.06 | 15-JUL-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39114.14 | 08-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28039.61 | 01-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10640.98 | 19-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.22 | 01-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46443.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 67627.04 | 05-JAN-17:00 | 33387.34 | 10752.72 | 4644.30 | 0.00 | 18842.69 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 66994.72 | 01-FEB-17:00 | 33387.34 | 10752.72 | 4644.30 | 0.00 | 18210.37 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 66106.67 | 06-MAR-17:00 | 33387.34 | 10752.72 | 4644.30 | 0.00 | 17322.32 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 61963.44 | 13-APR-14:09 | 31890.45 | 10752.72 | 0.00 | 0.00 | 15356.60 | 0.00 | 0.00 | 3963.67 | 0.00 |
May | 81141.46 | 25-MAY-14:00 | 31890.45 | 10752.72 | 0.00 | 0.00 | 8677.80 | 0.00 | 0.00 | 29820.50 | 0.00 |
June | 101098.61 | 29-JUN-15:00 | 31890.45 | 10752.72 | 0.00 | 0.00 | 12011.49 | 0.00 | 0.00 | 46443.95 | 0.00 |
July | 93568.00 | 15-JUL-14:09 | 28896.68 | 10752.72 | 0.00 | 0.00 | 11454.55 | 0.00 | 0.00 | 42464.06 | 0.00 |
August | 90837.99 | 08-AUG-15:30 | 31890.45 | 10752.72 | 0.00 | 0.00 | 10172.84 | 0.00 | 0.00 | 38021.99 | 0.00 |
September | 80131.91 | 01-SEP-13:30 | 33387.34 | 10752.72 | 0.00 | 0.00 | 8677.80 | 0.00 | 0.00 | 27314.05 | 0.00 |
October | 64924.24 | 31-OCT-16:00 | 33387.34 | 10752.72 | 4644.30 | 0.00 | 16139.88 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 66329.83 | 25-NOV-17:10 | 33387.34 | 10752.72 | 4644.30 | 0.00 | 17545.48 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 67247.48 | 19-DEC-17:00 | 33387.34 | 10752.72 | 4644.30 | 0.00 | 18463.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 61963.44 | 28896.68 | 10752.72 | 0.00 | 0.00 | 8677.80 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 101098.61 | 33387.34 | 10752.72 | 4644.30 | 0.00 | 18842.69 | 0.00 | 0.00 | 46443.95 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 325171.47 | 09-JAN-07:10 | 0.00 | 6249.77 | 31-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 303955.45 | 14-FEB-07:10 | 0.00 | 6347.39 | 24-FEB-12:50 | 0.00 |
March | 0.00 | 0.00 | 252932.70 | 16-MAR-06:10 | 0.00 | 6344.68 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 190203.94 | 05-APR-06:10 | 0.00 | 6140.83 | 04-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 125259.75 | 01-MAY-06:10 | 0.00 | 5654.49 | 05-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 3426.73 | 02-JUN-11:00 | 0.00 | 5148.16 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 1826.02 | 08-JUL-11:00 | 0.00 | 5092.75 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 5727.05 | 17-AUG-13:00 | 0.00 | 5059.68 | 01-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 26097.19 | 23-SEP-06:49 | 0.00 | 5068.15 | 29-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 165356.80 | 30-OCT-06:10 | 0.00 | 5114.29 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 234787.74 | 25-NOV-07:10 | 0.00 | 5334.97 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 302964.43 | 25-DEC-09:09 | 0.00 | 5816.46 | 26-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 1826.02 | 0.00 | 5059.68 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 325171.47 | 0.00 | 6347.39 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.50 | 17.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14.00 | 18.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11.83 | 19.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6.33 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.50 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.67 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8.33 | 19.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19.83 | 17.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.00 | 18.22 | 0.00 | 0.33 | 24.46 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 28.50 | 20.40 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 17.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.48 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.49 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.48 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.47 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.51 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 17.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 17.09 | 0.00 | 17.33 | 24.48 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 17.17 | 0.00 | 0.00 | 6.33 | 24.51 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.67 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11.50 | 18.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8.00 | 19.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3.00 | 20.17 | 0.00 | 0.00 | 0.17 | 24.50 | 0.00 | 0.00 |
May | 0.17 | 20.42 | 0.00 | 0.00 | 1.17 | 24.48 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.50 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 24.49 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.48 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.49 | 0.00 | 0.00 |
October | 0.67 | 20.39 | 0.00 | 0.00 | 0.50 | 24.47 | 0.00 | 0.00 |
November | 5.50 | 19.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17.83 | 17.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.33 | 18.19 | 0.00 | 21.33 | 24.49 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.67 | 20.42 | 0.00 | 0.00 | 7.00 | 24.50 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.83 | 16.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13.83 | 17.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10.50 | 19.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4.33 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.33 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.49 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.48 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 0.00 |
October | 2.50 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7.67 | 19.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23.83 | 17.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.83 | 17.70 | 0.00 | 2.83 | 24.48 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 28.83 | 20.34 | 0.00 | 0.00 | 1.50 | 24.49 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 18.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 18.75 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 18.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 414.00 | 21.11 | 414.00 | 21.11 |
February | 376.00 | 21.11 | 376.00 | 21.11 | 376.00 | 21.11 |
March | 422.00 | 21.11 | 419.50 | 21.11 | 419.50 | 21.11 |
April | 405.00 | 21.49 | 261.33 | 21.11 | 261.33 | 21.11 |
May | 325.00 | 22.88 | 49.33 | 22.71 | 21.00 | 21.12 |
June | 209.83 | 23.55 | 147.17 | 23.87 | 66.83 | 23.85 |
July | 91.00 | 23.74 | 267.50 | 23.89 | 63.00 | 23.89 |
August | 100.67 | 23.65 | 245.67 | 23.89 | 49.17 | 23.88 |
September | 323.83 | 23.16 | 46.00 | 23.87 | 21.33 | 23.84 |
October | 414.00 | 21.70 | 116.33 | 21.11 | 116.33 | 21.11 |
November | 399.00 | 21.15 | 349.83 | 21.11 | 349.83 | 21.11 |
December | 415.00 | 21.11 | 415.00 | 21.11 | 415.00 | 21.11 |
Annual Sum or Average | 3895.33 | 21.79 | 3107.67 | 21.77 | 2573.33 | 21.33 |
Minimum of Months | 91.00 | 21.11 | 46.00 | 21.11 | 21.00 | 21.11 |
Maximum of Months | 422.00 | 23.74 | 419.50 | 23.89 | 419.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 413.00 | 21.11 | 413.00 | 21.11 |
February | 376.00 | 21.11 | 345.50 | 21.11 | 345.50 | 21.11 |
March | 422.00 | 21.11 | 282.17 | 21.11 | 282.17 | 21.11 |
April | 398.83 | 21.73 | 73.67 | 21.11 | 73.67 | 21.11 |
May | 217.67 | 22.78 | 93.83 | 23.76 | 4.50 | 21.11 |
June | 100.83 | 23.52 | 263.17 | 23.89 | 52.50 | 23.89 |
July | 75.83 | 23.75 | 372.67 | 23.89 | 61.17 | 23.89 |
August | 56.83 | 23.49 | 344.00 | 23.89 | 29.00 | 23.89 |
September | 178.50 | 22.67 | 87.50 | 23.88 | 9.83 | 23.89 |
October | 394.33 | 21.64 | 25.33 | 21.11 | 25.33 | 21.11 |
November | 399.00 | 21.18 | 228.67 | 21.11 | 228.67 | 21.11 |
December | 415.00 | 21.11 | 409.17 | 21.11 | 409.17 | 21.11 |
Annual Sum or Average | 3448.83 | 21.61 | 2938.67 | 22.20 | 1934.50 | 21.33 |
Minimum of Months | 56.83 | 21.11 | 25.33 | 21.11 | 4.50 | 21.11 |
Maximum of Months | 422.00 | 23.75 | 413.00 | 23.89 | 413.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 391.00 | 21.11 | 391.00 | 21.11 |
February | 376.00 | 21.36 | 270.17 | 21.11 | 270.17 | 21.11 |
March | 421.00 | 21.52 | 246.83 | 21.11 | 246.83 | 21.11 |
April | 352.33 | 22.25 | 102.33 | 21.28 | 96.17 | 21.11 |
May | 186.33 | 23.31 | 110.83 | 23.76 | 5.33 | 21.11 |
June | 110.00 | 23.78 | 268.00 | 23.89 | 56.67 | 23.89 |
July | 64.17 | 23.87 | 377.17 | 23.89 | 57.17 | 23.89 |
August | 51.17 | 23.80 | 360.33 | 23.89 | 40.50 | 23.89 |
September | 102.17 | 23.30 | 189.67 | 23.89 | 10.33 | 23.89 |
October | 312.17 | 22.38 | 70.33 | 22.59 | 32.83 | 21.11 |
November | 396.17 | 21.66 | 187.67 | 21.11 | 187.67 | 21.11 |
December | 415.00 | 21.11 | 396.17 | 21.11 | 396.17 | 21.11 |
Annual Sum or Average | 3200.50 | 21.90 | 2970.50 | 22.37 | 1790.83 | 21.37 |
Minimum of Months | 51.17 | 21.11 | 70.33 | 21.11 | 5.33 | 21.11 |
Maximum of Months | 421.00 | 23.87 | 396.17 | 23.89 | 396.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 402.50 | 21.11 | 402.50 | 21.11 |
February | 376.00 | 21.18 | 307.17 | 21.11 | 307.17 | 21.11 |
March | 422.00 | 21.23 | 307.83 | 21.11 | 307.83 | 21.11 |
April | 380.67 | 21.80 | 155.00 | 21.19 | 150.67 | 21.11 |
May | 235.83 | 22.78 | 90.83 | 23.58 | 10.00 | 21.11 |
June | 154.17 | 23.50 | 226.50 | 23.89 | 65.83 | 23.88 |
July | 88.00 | 23.74 | 357.83 | 23.89 | 66.83 | 23.89 |
August | 82.17 | 23.61 | 335.83 | 23.89 | 50.33 | 23.88 |
September | 167.00 | 22.71 | 137.17 | 23.89 | 12.50 | 23.89 |
October | 345.33 | 21.67 | 104.50 | 21.84 | 77.17 | 21.11 |
November | 399.00 | 21.29 | 250.00 | 21.11 | 250.00 | 21.11 |
December | 415.00 | 21.11 | 407.17 | 21.11 | 407.17 | 21.11 |
Annual Sum or Average | 3479.17 | 21.70 | 3082.33 | 22.16 | 2108.00 | 21.37 |
Minimum of Months | 82.17 | 21.11 | 90.83 | 21.11 | 10.00 | 21.11 |
Maximum of Months | 422.00 | 23.74 | 407.17 | 23.89 | 407.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10985 | 14.65011 | -0.8451 | 20.21525 |
February | 376.00000 | 21.10988 | 16.47653 | -0.7978 | 18.57773 |
March | 422.00000 | 21.10991 | 20.78242 | -0.7333 | 16.52097 |
April | 405.00000 | 21.48739 | 25.36530 | -0.5261 | 11.80611 |
May | 418.00000 | 23.08896 | 36.39793 | -0.9977 | 28.67037 |
June | 408.00000 | 23.70946 | 48.97596 | -0.6248 | 14.25584 |
July | 415.00000 | 23.85395 | 53.97203 | -0.4776 | 10.04964 |
August | 422.00000 | 23.82947 | 53.58193 | -0.5132 | 10.86556 |
September | 405.00000 | 23.29914 | 43.70316 | -0.8449 | 21.85476 |
October | 414.00000 | 21.69297 | 35.59378 | -0.3634 | 9.04629 |
November | 399.00000 | 21.14987 | 24.39011 | -0.6531 | 14.37876 |
December | 415.00000 | 21.10986 | 16.08884 | -0.8148 | 19.17233 |
Annual Sum or Average | 4913.00000 | 22.22350 | 32.63873 | -0.6820 | 16.27399 |
Minimum of Months | 376.00000 | 21.10985 | 14.65011 | -0.9977 | 9.04629 |
Maximum of Months | 422.00000 | 23.85395 | 53.97203 | -0.3634 | 28.67037 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09584 | 11.28405 | -0.7390 | 16.67273 |
February | 376.00000 | 21.09600 | 13.41687 | -0.6778 | 14.85382 |
March | 422.00000 | 21.10172 | 17.47102 | -0.5966 | 12.73489 |
April | 405.00000 | 21.75756 | 21.94434 | -0.3239 | 8.67384 |
May | 418.00000 | 23.31047 | 33.78202 | -0.7586 | 19.51884 |
June | 408.00000 | 23.78984 | 47.16912 | -0.4587 | 10.02732 |
July | 415.00000 | 23.85413 | 53.04697 | -0.3729 | 8.17410 |
August | 422.00000 | 23.82057 | 51.99374 | -0.4117 | 8.90662 |
September | 405.00000 | 23.34390 | 41.55955 | -0.6907 | 16.65138 |
October | 414.00000 | 21.75323 | 32.36942 | -0.2447 | 7.68880 |
November | 399.00000 | 21.16867 | 21.47517 | -0.5437 | 11.73754 |
December | 415.00000 | 21.09595 | 12.85066 | -0.7127 | 15.87614 |
Annual Sum or Average | 4913.00000 | 22.27672 | 30.00865 | -0.5435 | 12.61435 |
Minimum of Months | 376.00000 | 21.09584 | 11.28405 | -0.7586 | 7.68880 |
Maximum of Months | 422.00000 | 23.85413 | 53.04697 | -0.2447 | 19.51884 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10966 | 10.74059 | -0.7407 | 16.88288 |
February | 376.00000 | 21.35667 | 12.57433 | -0.5992 | 13.83458 |
March | 422.00000 | 21.52484 | 16.47421 | -0.5099 | 12.17541 |
April | 405.00000 | 22.45574 | 19.93655 | -0.1960 | 8.47912 |
May | 418.00000 | 23.62265 | 32.01027 | -0.6708 | 16.68895 |
June | 408.00000 | 23.86043 | 46.27969 | -0.4291 | 9.54593 |
July | 415.00000 | 23.88653 | 52.39473 | -0.3179 | 7.42762 |
August | 422.00000 | 23.87901 | 51.44825 | -0.3298 | 7.73814 |
September | 405.00000 | 23.73983 | 38.96283 | -0.5266 | 12.16201 |
October | 414.00000 | 22.74777 | 29.35177 | -0.0300 | 7.70968 |
November | 399.00000 | 21.67392 | 20.29175 | -0.4398 | 10.92883 |
December | 415.00000 | 21.11281 | 12.25593 | -0.7331 | 16.60791 |
Annual Sum or Average | 4913.00000 | 22.59081 | 28.70599 | -0.4597 | 11.67359 |
Minimum of Months | 376.00000 | 21.10966 | 10.74059 | -0.7407 | 7.42762 |
Maximum of Months | 422.00000 | 23.88653 | 52.39473 | -0.0300 | 16.88288 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10973 | 10.78879 | -0.7762 | 17.99436 |
February | 376.00000 | 21.17772 | 12.75236 | -0.6711 | 15.17218 |
March | 422.00000 | 21.22897 | 16.79309 | -0.6084 | 13.61225 |
April | 405.00000 | 21.92251 | 20.85453 | -0.3381 | 9.83850 |
May | 418.00000 | 23.25693 | 33.33390 | -0.8253 | 22.59094 |
June | 408.00000 | 23.73747 | 47.65505 | -0.5117 | 11.75138 |
July | 415.00000 | 23.85610 | 53.61731 | -0.3650 | 8.23456 |
August | 422.00000 | 23.83285 | 52.50550 | -0.3847 | 8.75158 |
September | 405.00000 | 23.40004 | 40.52648 | -0.6688 | 16.95707 |
October | 414.00000 | 22.03451 | 30.88105 | -0.2075 | 8.62412 |
November | 399.00000 | 21.28526 | 20.85670 | -0.5568 | 12.50083 |
December | 415.00000 | 21.10982 | 12.30873 | -0.7693 | 17.72477 |
Annual Sum or Average | 4913.00000 | 22.33996 | 29.55577 | -0.5563 | 13.63995 |
Minimum of Months | 376.00000 | 21.10973 | 10.78879 | -0.8253 | 8.23456 |
Maximum of Months | 422.00000 | 23.85610 | 53.61731 | -0.2075 | 22.59094 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 12963457.04 | 3861874.20 | 4.61 | 11069788.76 | 1893668.28 | 0.00 | 0.18 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 2318.70 | 23-APR-16:00 | 1969.02 | 23-APR-16:00 | 349.67 | 23-APR-16:00 | 686.55 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.258577E+10 | 0.669854E+09 | 161.51 | 0.212204E+10 | 0.463727E+09 | 0.00 | 1.00 | 18-MAY-21:15 | 0.00 | 01-MAY-00:10 | 34088.31 | 25-MAY-20:31 | 26915.41 | 25-MAY-20:31 | 7912.04 | 25-MAY-20:55 | 7479.25 | 25-MAY-20:31 | 0.00 | 01-MAY-00:10 |
June | 0.753082E+10 | 0.187207E+10 | 290.32 | 0.551395E+10 | 0.201688E+10 | 0.00 | 1.00 | 25-JUN-19:04 | 0.00 | 01-JUN-00:10 | 36293.55 | 27-JUN-20:20 | 24621.41 | 30-JUN-20:16 | 16847.87 | 27-JUN-21:37 | 7713.48 | 27-JUN-20:20 | 0.00 | 01-JUN-00:10 |
July | 0.122225E+11 | 0.295194E+10 | 359.71 | 0.840374E+10 | 0.381872E+10 | 0.00 | 1.00 | 02-JUL-18:32 | 0.00 | 01-JUL-00:03 | 37238.50 | 03-JUL-23:02 | 25024.24 | 02-JUL-18:30 | 21406.27 | 04-JUL-01:05 | 7801.34 | 03-JUL-23:02 | 0.00 | 01-JUL-00:03 |
August | 0.850771E+10 | 0.206144E+10 | 320.55 | 0.582342E+10 | 0.268429E+10 | 0.00 | 1.00 | 07-AUG-21:01 | 0.00 | 01-AUG-00:10 | 36361.98 | 31-AUG-20:32 | 26862.76 | 13-AUG-18:40 | 17729.94 | 31-AUG-20:43 | 7692.91 | 31-AUG-20:32 | 0.00 | 01-AUG-00:10 |
September | 0.107941E+10 | 0.274735E+09 | 148.93 | 0.841160E+09 | 0.238250E+09 | 0.00 | 1.00 | 01-SEP-20:33 | 0.00 | 01-SEP-00:10 | 33542.36 | 01-SEP-20:33 | 18420.98 | 01-SEP-20:33 | 15121.38 | 01-SEP-20:33 | 7140.45 | 01-SEP-20:33 | 0.00 | 01-SEP-00:10 |
October | 16132020.58 | 4510443.49 | 14.28 | 15163146.06 | 968874.52 | 0.00 | 0.14 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1821.92 | 19-OCT-15:00 | 1680.40 | 19-OCT-15:00 | 141.52 | 19-OCT-15:00 | 507.62 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.319553E+11 | 0.783841E+10 | 1299.90 | 0.227305E+11 | 0.922473E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.122225E+11 | 0.295194E+10 | 359.71 | 0.840374E+10 | 0.381872E+10 | 0.00 | 1.00 | 0.00 | 37238.50 | 26915.41 | 21406.27 | 7801.34 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.714094E+09 | 0.217793E+09 | 32.24 | 0.634479E+09 | 79614686.88 | 0.00 | 0.50 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 34467.67 | 23-APR-16:00 | 29589.34 | 23-APR-16:00 | 4878.33 | 23-APR-16:00 | 10445.66 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.202176E+11 | 0.564896E+10 | 215.20 | 0.168825E+11 | 0.333507E+10 | 0.00 | 1.00 | 15-MAY-20:35 | 0.00 | 01-MAY-00:10 | 166145.29 | 25-MAY-21:51 | 153478.05 | 21-MAY-18:31 | 57263.32 | 26-MAY-20:20 | 40638.95 | 25-MAY-20:31 | 0.00 | 01-MAY-00:10 |
June | 0.506376E+11 | 0.136694E+11 | 332.25 | 0.363219E+11 | 0.143157E+11 | 0.00 | 1.00 | 04-JUN-18:43 | 0.00 | 01-JUN-00:10 | 177567.01 | 19-JUN-20:19 | 153478.05 | 04-JUN-18:43 | 97321.49 | 19-JUN-20:35 | 42043.73 | 27-JUN-20:12 | 0.00 | 01-JUN-00:10 |
July | 0.726914E+11 | 0.191899E+11 | 385.07 | 0.483427E+11 | 0.243487E+11 | 0.00 | 1.00 | 02-JUL-18:16 | 0.00 | 01-JUL-00:03 | 181181.91 | 04-JUL-00:22 | 138336.46 | 26-JUL-21:53 | 101288.77 | 04-JUL-00:35 | 42409.48 | 03-JUL-23:20 | 0.00 | 01-JUL-00:03 |
August | 0.536572E+11 | 0.142111E+11 | 349.61 | 0.356628E+11 | 0.179944E+11 | 0.00 | 1.00 | 01-AUG-00:25 | 0.00 | 01-AUG-00:10 | 177659.61 | 31-AUG-20:17 | 130236.82 | 13-AUG-18:16 | 91813.26 | 28-AUG-20:20 | 41993.09 | 31-AUG-20:17 | 0.00 | 01-AUG-00:10 |
September | 0.962960E+10 | 0.269933E+10 | 170.98 | 0.746392E+10 | 0.216568E+10 | 0.00 | 1.00 | 01-SEP-00:42 | 0.00 | 01-SEP-00:10 | 172676.22 | 01-SEP-00:42 | 126200.04 | 07-SEP-20:54 | 84116.22 | 01-SEP-00:42 | 40606.40 | 01-SEP-00:42 | 0.00 | 01-SEP-00:10 |
October | 0.589069E+09 | 0.176693E+09 | 25.26 | 0.547913E+09 | 41156129.87 | 0.00 | 0.35 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 22773.91 | 19-OCT-15:00 | 20737.13 | 19-OCT-15:00 | 2330.92 | 19-OCT-14:10 | 6711.15 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 411.06 | 130.60 | 0.17 | 308.89 | 102.16 | 0.00 | 0.00 | 01-NOV-14:30 | 0.00 | 01-NOV-00:10 | 0.69 | 01-NOV-14:30 | 0.51 | 01-NOV-14:30 | 0.17 | 01-NOV-14:30 | 0.22 | 01-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.208137E+12 | 0.558132E+11 | 1510.79 | 0.145856E+12 | 0.622803E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.726914E+11 | 0.191899E+11 | 385.07 | 0.483427E+11 | 0.243487E+11 | 0.00 | 1.00 | 0.00 | 181181.91 | 153478.05 | 101288.77 | 42409.48 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 46.25 | 12.35 | 0.33 | 46.25 | 0.00 | 0.00 | 0.00 | 08-FEB-15:10 | 0.00 | 01-FEB-00:02 | 0.07 | 08-FEB-15:10 | 0.07 | 08-FEB-15:10 | 0.00 | 01-FEB-00:02 | 0.02 | 08-FEB-15:10 | 0.00 | 01-FEB-00:02 |
March | 3105.48 | 829.51 | 7.95 | 3105.48 | 0.00 | 0.00 | 0.00 | 31-MAR-14:10 | 0.00 | 01-MAR-00:10 | 0.36 | 31-MAR-14:10 | 0.36 | 31-MAR-14:10 | 0.00 | 28-MAR-16:20 | 0.10 | 31-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.282119E+09 | 68627229.35 | 80.25 | 0.269308E+09 | 12811755.19 | 0.00 | 1.00 | 23-APR-19:00 | 0.00 | 01-APR-00:10 | 22048.79 | 23-APR-19:00 | 20627.63 | 23-APR-19:00 | 2271.14 | 23-APR-19:51 | 4855.75 | 23-APR-19:00 | 0.00 | 01-APR-00:10 |
May | 0.339911E+10 | 0.788385E+09 | 253.63 | 0.307059E+10 | 0.328520E+09 | 0.00 | 1.00 | 10-MAY-20:35 | 0.00 | 01-MAY-00:10 | 22743.98 | 25-MAY-20:41 | 21096.99 | 10-MAY-20:35 | 7405.37 | 26-MAY-20:15 | 4969.12 | 25-MAY-20:41 | 0.00 | 01-MAY-00:10 |
June | 0.750639E+10 | 0.172575E+10 | 328.08 | 0.593255E+10 | 0.157384E+10 | 0.00 | 1.00 | 04-JUN-18:20 | 0.00 | 01-JUN-00:10 | 24390.73 | 27-JUN-20:10 | 21177.38 | 04-JUN-18:20 | 13231.91 | 19-JUN-20:40 | 5189.30 | 28-JUN-20:10 | 0.00 | 01-JUN-00:10 |
July | 0.113221E+11 | 0.253167E+10 | 386.79 | 0.839437E+10 | 0.292768E+10 | 0.00 | 1.00 | 02-JUL-18:11 | 0.00 | 01-JUL-00:03 | 24880.08 | 04-JUL-00:22 | 17859.52 | 05-JUL-20:11 | 14397.93 | 04-JUL-02:43 | 5244.68 | 03-JUL-22:02 | 0.00 | 01-JUL-00:03 |
August | 0.892836E+10 | 0.197208E+10 | 354.05 | 0.664327E+10 | 0.228509E+10 | 0.00 | 1.00 | 01-AUG-20:15 | 0.00 | 01-AUG-00:10 | 24390.33 | 31-AUG-20:12 | 18974.57 | 13-AUG-18:10 | 12609.47 | 28-AUG-20:15 | 5209.63 | 08-AUG-20:10 | 0.00 | 01-AUG-00:10 |
September | 0.222424E+10 | 0.510272E+09 | 237.02 | 0.193771E+10 | 0.286530E+09 | 0.00 | 1.00 | 01-SEP-00:30 | 0.00 | 01-SEP-00:10 | 23698.57 | 01-SEP-01:07 | 19671.53 | 04-SEP-18:10 | 12132.80 | 01-SEP-01:07 | 4988.36 | 01-SEP-01:07 | 0.00 | 01-SEP-00:10 |
October | 0.463582E+09 | 0.106830E+09 | 90.25 | 0.445781E+09 | 17800385.08 | 0.00 | 1.00 | 22-OCT-18:08 | 0.00 | 01-OCT-00:10 | 21081.59 | 22-OCT-18:08 | 17613.88 | 22-OCT-18:08 | 3467.71 | 22-OCT-18:08 | 4463.27 | 22-OCT-18:08 | 0.00 | 01-OCT-00:10 |
November | 9092.53 | 2432.10 | 12.57 | 8341.96 | 750.57 | 0.00 | 0.00 | 21-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.60 | 21-NOV-14:00 | 0.47 | 17-NOV-13:00 | 0.17 | 21-NOV-14:00 | 0.16 | 21-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.341259E+11 | 0.770362E+10 | 1750.93 | 0.266936E+11 | 0.743228E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.113221E+11 | 0.253167E+10 | 386.79 | 0.839437E+10 | 0.292768E+10 | 0.00 | 1.00 | 0.00 | 24880.08 | 21177.38 | 14397.93 | 5244.68 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 16.68 | 4.33 | 0.17 | 16.68 | 0.00 | 0.00 | 0.00 | 31-MAR-14:30 | 0.00 | 01-MAR-00:10 | 0.03 | 31-MAR-14:30 | 0.03 | 31-MAR-14:30 | 0.00 | 01-MAR-00:10 | 0.01 | 31-MAR-14:30 | 0.00 | 01-MAR-00:10 |
April | 0.138487E+09 | 33470906.92 | 46.81 | 0.128704E+09 | 9782982.72 | 0.00 | 0.69 | 23-APR-18:20 | 0.00 | 01-APR-00:10 | 5920.93 | 23-APR-14:20 | 5653.62 | 23-APR-18:20 | 593.74 | 23-APR-13:40 | 1407.12 | 23-APR-18:20 | 0.00 | 01-APR-00:10 |
May | 0.215989E+10 | 0.497005E+09 | 195.04 | 0.191542E+10 | 0.244467E+09 | 0.00 | 1.00 | 16-MAY-20:20 | 0.00 | 01-MAY-00:10 | 19293.50 | 25-MAY-20:11 | 16710.08 | 28-MAY-18:21 | 6466.95 | 26-MAY-20:20 | 4150.78 | 25-MAY-20:11 | 0.00 | 01-MAY-00:10 |
June | 0.519515E+10 | 0.117698E+10 | 293.55 | 0.401572E+10 | 0.117943E+10 | 0.00 | 1.00 | 06-JUN-20:30 | 0.00 | 01-JUN-00:10 | 20672.30 | 19-JUN-20:50 | 15181.52 | 08-JUN-20:16 | 11566.11 | 19-JUN-20:50 | 4238.98 | 27-JUN-20:10 | 0.00 | 01-JUN-00:10 |
July | 0.820678E+10 | 0.179975E+10 | 353.26 | 0.595469E+10 | 0.225208E+10 | 0.00 | 1.00 | 02-JUL-18:11 | 0.00 | 01-JUL-00:03 | 21021.00 | 03-JUL-22:48 | 14770.64 | 05-JUL-20:11 | 11701.09 | 04-JUL-00:05 | 4287.20 | 03-JUL-22:48 | 0.00 | 01-JUL-00:03 |
August | 0.643085E+10 | 0.139326E+10 | 320.21 | 0.471920E+10 | 0.171164E+10 | 0.00 | 1.00 | 03-AUG-20:20 | 0.00 | 01-AUG-00:10 | 20606.60 | 31-AUG-20:12 | 15726.29 | 13-AUG-18:10 | 10736.16 | 28-AUG-20:20 | 4232.31 | 31-AUG-20:12 | 0.00 | 01-AUG-00:10 |
September | 0.144900E+10 | 0.325090E+09 | 176.56 | 0.126123E+10 | 0.187774E+09 | 0.00 | 1.00 | 01-SEP-00:25 | 0.00 | 01-SEP-00:10 | 19947.41 | 01-SEP-00:25 | 15152.95 | 04-SEP-19:01 | 9588.23 | 01-SEP-00:25 | 4082.17 | 01-SEP-00:25 | 0.00 | 01-SEP-00:10 |
October | 0.308486E+09 | 69950290.02 | 47.23 | 0.294814E+09 | 13672152.86 | 0.00 | 0.75 | 19-OCT-14:30 | 0.00 | 01-OCT-00:10 | 6904.31 | 19-OCT-14:30 | 6698.05 | 19-OCT-14:40 | 689.12 | 22-OCT-13:00 | 1482.82 | 19-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 505.00 | 131.00 | 1.67 | 505.00 | 0.00 | 0.00 | 0.00 | 17-NOV-13:30 | 0.00 | 01-NOV-00:10 | 0.14 | 17-NOV-13:30 | 0.14 | 17-NOV-13:30 | 0.00 | 17-NOV-15:10 | 0.04 | 17-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.238886E+11 | 0.529551E+10 | 1434.50 | 0.182898E+11 | 0.559885E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.820678E+10 | 0.179975E+10 | 353.26 | 0.595469E+10 | 0.225208E+10 | 0.00 | 1.00 | 0.00 | 21021.00 | 16710.08 | 11701.09 | 4287.20 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.94 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.99 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 35.00 | 79.00 | 6.67 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 72.41 | 51.18 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 104.57 | 30.36 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 116.06 | 22.78 | 5.33 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.44 | 20.64 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 93.16 | 23.14 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.97 | 35.03 | 1.50 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 25.48 | 51.74 | 5.83 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.79 | 78.21 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.48 | 62.41 | 27.00 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.44 | 129.94 | 6.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.94 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.99 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 35.00 | 79.00 | 6.67 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 72.41 | 51.18 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 104.57 | 30.36 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 116.06 | 22.78 | 5.33 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.44 | 20.64 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 93.16 | 23.14 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.97 | 35.03 | 1.50 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 25.48 | 51.74 | 5.83 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.79 | 78.21 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.48 | 62.41 | 27.00 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.44 | 129.94 | 6.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.94 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.99 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 35.00 | 79.00 | 6.67 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 72.41 | 51.18 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 104.57 | 30.36 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 116.06 | 22.78 | 5.33 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.44 | 20.64 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 93.16 | 23.14 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.97 | 35.03 | 1.50 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 25.48 | 51.74 | 5.83 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.79 | 78.21 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.48 | 62.41 | 27.00 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.44 | 129.94 | 6.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.94 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.99 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 35.00 | 79.00 | 6.67 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 72.41 | 51.18 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 104.57 | 30.36 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 116.06 | 22.78 | 5.33 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.44 | 20.64 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 93.16 | 23.14 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.97 | 35.03 | 1.50 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 25.48 | 51.74 | 5.83 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.79 | 78.21 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.48 | 62.41 | 27.00 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.44 | 129.94 | 6.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.94 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.99 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 35.00 | 79.00 | 6.67 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 72.41 | 51.18 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 104.57 | 30.36 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 116.06 | 22.78 | 5.33 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.44 | 20.64 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 93.16 | 23.14 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.97 | 35.03 | 1.50 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 25.48 | 51.74 | 5.83 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.79 | 78.21 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.48 | 62.41 | 27.00 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.44 | 129.94 | 6.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.94 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.99 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 35.00 | 79.00 | 6.67 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 72.41 | 51.18 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 104.57 | 30.36 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 116.06 | 22.78 | 5.33 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.44 | 20.64 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 93.16 | 23.14 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.97 | 35.03 | 1.50 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 25.48 | 51.74 | 5.83 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.79 | 78.21 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.48 | 62.41 | 27.00 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.44 | 129.94 | 6.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.94 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.99 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 35.00 | 79.00 | 6.67 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 72.41 | 51.18 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 104.57 | 30.36 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 116.06 | 22.78 | 5.33 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.44 | 20.64 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 93.16 | 23.14 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.97 | 35.03 | 1.50 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 25.48 | 51.74 | 5.83 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.79 | 78.21 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.48 | 62.41 | 27.00 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.44 | 129.94 | 6.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.78 | 8.40 | 14.38 | 1.03 | 129.94 | 0.00 | 0.00 | 744.00 |
February | 40.20 | 19.05 | 21.15 | 15.03 | 101.99 | 0.00 | 0.00 | 672.00 |
March | 56.56 | 32.04 | 24.52 | 35.00 | 79.00 | 6.67 | 0.00 | 744.00 |
April | 82.61 | 52.15 | 30.46 | 72.41 | 51.18 | 6.17 | 0.00 | 720.00 |
May | 100.91 | 56.66 | 44.24 | 104.57 | 30.36 | 0.00 | 0.00 | 744.00 |
June | 105.95 | 60.80 | 45.15 | 116.06 | 22.78 | 5.33 | 0.00 | 720.00 |
July | 108.77 | 64.78 | 43.99 | 122.44 | 20.64 | 0.00 | 0.00 | 744.00 |
August | 85.99 | 48.19 | 37.81 | 93.16 | 23.14 | 1.50 | 0.00 | 744.00 |
September | 62.81 | 32.42 | 30.39 | 59.97 | 35.03 | 1.50 | 0.00 | 720.00 |
October | 37.63 | 15.25 | 22.38 | 25.48 | 51.74 | 5.83 | 0.00 | 744.00 |
November | 21.96 | 6.96 | 15.00 | 5.79 | 78.21 | 0.00 | 0.00 | 720.00 |
December | 17.70 | 4.91 | 12.80 | 0.15 | 126.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.10 | 33.54 | 28.56 | 54.48 | 62.41 | 27.00 | 0.00 | 8760.00 |
Minimum of Months | 17.70 | 4.91 | 12.80 | 0.15 | 20.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.77 | 64.78 | 45.15 | 122.44 | 129.94 | 6.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1542.81 | 1073.16 | 469.65 | 1163.86 | 1802.10 | 0.00 | 0.00 | 744.00 |
February | 1954.07 | 1319.82 | 634.25 | 1661.89 | 1517.25 | 0.00 | 0.00 | 672.00 |
March | 1722.64 | 1090.48 | 632.16 | 1419.30 | 1277.32 | 0.00 | 0.00 | 744.00 |
April | 1560.16 | 846.91 | 713.25 | 1302.16 | 851.49 | 0.00 | 0.00 | 720.00 |
May | 1311.30 | 448.16 | 863.13 | 1119.29 | 488.23 | 0.00 | 0.00 | 744.00 |
June | 1176.59 | 313.47 | 863.12 | 1064.00 | 336.96 | 0.00 | 0.00 | 720.00 |
July | 1286.39 | 407.38 | 879.02 | 1237.28 | 303.49 | 0.00 | 0.00 | 744.00 |
August | 1373.97 | 574.69 | 799.28 | 1357.34 | 365.71 | 0.00 | 0.00 | 744.00 |
September | 1472.28 | 784.33 | 687.95 | 1416.06 | 594.08 | 0.00 | 0.00 | 720.00 |
October | 1257.16 | 739.54 | 517.61 | 1110.83 | 857.95 | 0.00 | 0.00 | 744.00 |
November | 1119.24 | 702.32 | 416.91 | 908.80 | 1180.21 | 0.00 | 0.00 | 720.00 |
December | 1191.25 | 780.99 | 410.25 | 821.25 | 1753.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1410.45 | 753.18 | 657.26 | 1211.97 | 941.57 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1119.24 | 313.47 | 410.25 | 821.25 | 303.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1954.07 | 1319.82 | 879.02 | 1661.89 | 1802.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1542.81 | 1073.16 | 469.65 | 1161.65 | 1797.20 | 0.00 | 0.00 | 744.00 |
February | 1954.07 | 1319.82 | 634.25 | 1662.94 | 1506.07 | 0.00 | 0.00 | 672.00 |
March | 1722.64 | 1090.48 | 632.16 | 1423.20 | 1258.58 | 0.00 | 0.00 | 744.00 |
April | 1560.16 | 846.91 | 713.25 | 1309.89 | 824.73 | 0.00 | 0.00 | 720.00 |
May | 1311.30 | 448.16 | 863.13 | 1125.17 | 469.29 | 0.00 | 0.00 | 744.00 |
June | 1176.59 | 313.47 | 863.12 | 1064.13 | 326.42 | 0.00 | 0.00 | 720.00 |
July | 1286.39 | 407.38 | 879.02 | 1232.75 | 300.35 | 0.00 | 0.00 | 744.00 |
August | 1373.97 | 574.69 | 799.28 | 1353.44 | 361.93 | 0.00 | 0.00 | 744.00 |
September | 1472.28 | 784.33 | 687.95 | 1418.95 | 576.79 | 0.00 | 0.00 | 720.00 |
October | 1257.16 | 739.54 | 517.61 | 1120.10 | 825.13 | 0.00 | 0.00 | 744.00 |
November | 1119.24 | 702.32 | 416.91 | 913.25 | 1157.50 | 0.00 | 0.00 | 720.00 |
December | 1191.25 | 780.99 | 410.25 | 819.72 | 1749.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1410.45 | 753.18 | 657.26 | 1213.88 | 926.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1119.24 | 313.47 | 410.25 | 819.72 | 300.35 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1954.07 | 1319.82 | 879.02 | 1662.94 | 1797.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.46 | 220.82 | 96.64 | 231.09 | 376.58 | 0.00 | 0.00 | 744.00 |
February | 402.08 | 271.57 | 130.51 | 331.09 | 315.04 | 0.00 | 0.00 | 672.00 |
March | 354.46 | 224.38 | 130.08 | 284.35 | 265.64 | 0.00 | 0.00 | 744.00 |
April | 321.03 | 174.26 | 146.76 | 263.38 | 170.96 | 0.00 | 0.00 | 720.00 |
May | 269.82 | 92.22 | 177.60 | 228.89 | 94.00 | 0.00 | 0.00 | 744.00 |
June | 242.10 | 64.50 | 177.60 | 215.04 | 64.97 | 0.00 | 0.00 | 720.00 |
July | 264.69 | 83.82 | 180.87 | 247.07 | 62.39 | 0.00 | 0.00 | 744.00 |
August | 282.71 | 118.25 | 164.46 | 275.33 | 73.51 | 0.00 | 0.00 | 744.00 |
September | 302.94 | 161.39 | 141.56 | 290.41 | 114.55 | 0.00 | 0.00 | 720.00 |
October | 258.68 | 152.17 | 106.51 | 226.06 | 169.40 | 0.00 | 0.00 | 744.00 |
November | 230.30 | 144.51 | 85.79 | 180.33 | 243.64 | 0.00 | 0.00 | 720.00 |
December | 245.12 | 160.70 | 84.42 | 162.41 | 368.31 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 290.22 | 154.98 | 135.24 | 243.99 | 192.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 230.30 | 64.50 | 84.42 | 162.41 | 62.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 402.08 | 271.57 | 180.87 | 331.09 | 376.58 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2747895.16 | 0.348025E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36354634.43 | 0.246725E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93746302.82 | 0.211600E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.187692E+09 | 0.132662E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.280084E+09 | 81309245.72 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300825E+09 | 59033611.76 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327943E+09 | 55289238.92 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249518E+09 | 61981672.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.155444E+09 | 90807753.82 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 68243131.38 | 0.138580E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 15000262.22 | 0.202732E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 0.339364E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171799E+10 | 0.196811E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 55289238.92 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327943E+09 | 0.348025E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2747895.16 | 0.348025E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36354634.43 | 0.246725E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93746302.82 | 0.211600E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.187692E+09 | 0.132662E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.280084E+09 | 81309245.72 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300825E+09 | 59033611.76 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327943E+09 | 55289238.92 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249518E+09 | 61981672.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.155444E+09 | 90807753.82 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 68243131.38 | 0.138580E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 15000262.22 | 0.202732E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 0.339364E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171799E+10 | 0.196811E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 55289238.92 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327943E+09 | 0.348025E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2747895.16 | 0.348025E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36354634.43 | 0.246725E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93746302.82 | 0.211600E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.187692E+09 | 0.132662E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.280084E+09 | 81309245.72 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300825E+09 | 59033611.76 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327943E+09 | 55289238.92 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249518E+09 | 61981672.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.155444E+09 | 90807753.82 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 68243131.38 | 0.138580E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 15000262.22 | 0.202732E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 0.339364E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171799E+10 | 0.196811E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 55289238.92 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327943E+09 | 0.348025E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2747895.16 | 0.348025E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36354634.43 | 0.246725E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93746302.82 | 0.211600E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.187692E+09 | 0.132662E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.280084E+09 | 81309245.72 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300825E+09 | 59033611.76 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327943E+09 | 55289238.92 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249518E+09 | 61981672.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.155444E+09 | 90807753.82 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 68243131.38 | 0.138580E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 15000262.22 | 0.202732E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 0.339364E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171799E+10 | 0.196811E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 55289238.92 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327943E+09 | 0.348025E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2747895.16 | 0.348025E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36354634.43 | 0.246725E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93746302.82 | 0.211600E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.187692E+09 | 0.132662E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.280084E+09 | 81309245.72 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300825E+09 | 59033611.76 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327943E+09 | 55289238.92 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249518E+09 | 61981672.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.155444E+09 | 90807753.82 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 68243131.38 | 0.138580E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 15000262.22 | 0.202732E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 0.339364E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171799E+10 | 0.196811E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 55289238.92 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327943E+09 | 0.348025E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2747895.16 | 0.348025E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36354634.43 | 0.246725E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93746302.82 | 0.211600E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.187692E+09 | 0.132662E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.280084E+09 | 81309245.72 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300825E+09 | 59033611.76 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327943E+09 | 55289238.92 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249518E+09 | 61981672.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.155444E+09 | 90807753.82 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 68243131.38 | 0.138580E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 15000262.22 | 0.202732E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 0.339364E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171799E+10 | 0.196811E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 55289238.92 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327943E+09 | 0.348025E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2747895.16 | 0.348025E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36354634.43 | 0.246725E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93746302.82 | 0.211600E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.187692E+09 | 0.132662E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.280084E+09 | 81309245.72 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300825E+09 | 59033611.76 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327943E+09 | 55289238.92 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249518E+09 | 61981672.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.155444E+09 | 90807753.82 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 68243131.38 | 0.138580E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 15000262.22 | 0.202732E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 0.339364E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171799E+10 | 0.196811E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 55289238.92 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327943E+09 | 0.348025E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61019949.83 | 22509744.57 | 38510205.26 | 2747895.16 | 0.348025E+09 |
February | 97259523.45 | 46096640.56 | 51162882.90 | 36354634.43 | 0.246725E+09 |
March | 0.151486E+09 | 85822473.89 | 65663384.04 | 93746302.82 | 0.211600E+09 |
April | 0.214116E+09 | 0.135161E+09 | 78954366.19 | 0.187692E+09 | 0.132662E+09 |
May | 0.270265E+09 | 0.151763E+09 | 0.118503E+09 | 0.280084E+09 | 81309245.72 |
June | 0.274618E+09 | 0.157594E+09 | 0.117023E+09 | 0.300825E+09 | 59033611.76 |
July | 0.291331E+09 | 0.173517E+09 | 0.117815E+09 | 0.327943E+09 | 55289238.92 |
August | 0.230326E+09 | 0.129066E+09 | 0.101260E+09 | 0.249518E+09 | 61981672.20 |
September | 0.162802E+09 | 84024481.83 | 78777531.92 | 0.155444E+09 | 90807753.82 |
October | 0.100787E+09 | 40853246.56 | 59933590.44 | 68243131.38 | 0.138580E+09 |
November | 56910602.18 | 18040072.40 | 38870529.77 | 15000262.22 | 0.202732E+09 |
December | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 0.339364E+09 |
Annual Sum or Average | 0.195834E+10 | 0.105760E+10 | 0.900743E+09 | 0.171799E+10 | 0.196811E+10 |
Minimum of Months | 47420277.43 | 13149918.88 | 34270358.55 | 392258.87 | 55289238.92 |
Maximum of Months | 0.291331E+09 | 0.173517E+09 | 0.118503E+09 | 0.327943E+09 | 0.348025E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.413226E+10 | 0.287434E+10 | 0.125792E+10 | 0.311728E+10 | 0.482674E+10 |
February | 0.472728E+10 | 0.319290E+10 | 0.153439E+10 | 0.402045E+10 | 0.367054E+10 |
March | 0.461392E+10 | 0.292075E+10 | 0.169318E+10 | 0.380145E+10 | 0.342118E+10 |
April | 0.404395E+10 | 0.219520E+10 | 0.184875E+10 | 0.337520E+10 | 0.220707E+10 |
May | 0.351217E+10 | 0.120036E+10 | 0.231181E+10 | 0.299792E+10 | 0.130767E+10 |
June | 0.304972E+10 | 0.812512E+09 | 0.223721E+10 | 0.275790E+10 | 0.873412E+09 |
July | 0.344548E+10 | 0.109112E+10 | 0.235436E+10 | 0.331394E+10 | 0.812881E+09 |
August | 0.368004E+10 | 0.153925E+10 | 0.214079E+10 | 0.363549E+10 | 0.979513E+09 |
September | 0.381615E+10 | 0.203299E+10 | 0.178317E+10 | 0.367043E+10 | 0.153987E+10 |
October | 0.336717E+10 | 0.198079E+10 | 0.138638E+10 | 0.297526E+10 | 0.229793E+10 |
November | 0.290106E+10 | 0.182043E+10 | 0.108064E+10 | 0.235560E+10 | 0.305911E+10 |
December | 0.319063E+10 | 0.209181E+10 | 0.109882E+10 | 0.219964E+10 | 0.469748E+10 |
Annual Sum or Average | 0.444798E+11 | 0.237524E+11 | 0.207274E+11 | 0.382206E+11 | 0.296934E+11 |
Minimum of Months | 0.290106E+10 | 0.812512E+09 | 0.108064E+10 | 0.219964E+10 | 0.812881E+09 |
Maximum of Months | 0.472728E+10 | 0.319290E+10 | 0.235436E+10 | 0.402045E+10 | 0.482674E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.413226E+10 | 0.287434E+10 | 0.125792E+10 | 0.311137E+10 | 0.481363E+10 |
February | 0.472728E+10 | 0.319290E+10 | 0.153439E+10 | 0.402298E+10 | 0.364347E+10 |
March | 0.461392E+10 | 0.292075E+10 | 0.169318E+10 | 0.381190E+10 | 0.337097E+10 |
April | 0.404395E+10 | 0.219520E+10 | 0.184875E+10 | 0.339524E+10 | 0.213771E+10 |
May | 0.351217E+10 | 0.120036E+10 | 0.231181E+10 | 0.301364E+10 | 0.125694E+10 |
June | 0.304972E+10 | 0.812512E+09 | 0.223721E+10 | 0.275824E+10 | 0.846092E+09 |
July | 0.344548E+10 | 0.109112E+10 | 0.235436E+10 | 0.330179E+10 | 0.804455E+09 |
August | 0.368004E+10 | 0.153925E+10 | 0.214079E+10 | 0.362504E+10 | 0.969384E+09 |
September | 0.381615E+10 | 0.203299E+10 | 0.178317E+10 | 0.367793E+10 | 0.149503E+10 |
October | 0.336717E+10 | 0.198079E+10 | 0.138638E+10 | 0.300007E+10 | 0.221002E+10 |
November | 0.290106E+10 | 0.182043E+10 | 0.108064E+10 | 0.236715E+10 | 0.300023E+10 |
December | 0.319063E+10 | 0.209181E+10 | 0.109882E+10 | 0.219555E+10 | 0.468526E+10 |
Annual Sum or Average | 0.444798E+11 | 0.237524E+11 | 0.207274E+11 | 0.382809E+11 | 0.292332E+11 |
Minimum of Months | 0.290106E+10 | 0.812512E+09 | 0.108064E+10 | 0.219555E+10 | 0.804455E+09 |
Maximum of Months | 0.472728E+10 | 0.319290E+10 | 0.235436E+10 | 0.402298E+10 | 0.481363E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.850274E+09 | 0.591437E+09 | 0.258836E+09 | 0.618955E+09 | 0.100863E+10 |
February | 0.972707E+09 | 0.656985E+09 | 0.315722E+09 | 0.800984E+09 | 0.762135E+09 |
March | 0.949382E+09 | 0.600986E+09 | 0.348396E+09 | 0.761604E+09 | 0.711494E+09 |
April | 0.832101E+09 | 0.451694E+09 | 0.380406E+09 | 0.682693E+09 | 0.443141E+09 |
May | 0.722681E+09 | 0.246992E+09 | 0.475689E+09 | 0.613069E+09 | 0.251757E+09 |
June | 0.627525E+09 | 0.167186E+09 | 0.460339E+09 | 0.557386E+09 | 0.168410E+09 |
July | 0.708958E+09 | 0.224513E+09 | 0.484444E+09 | 0.661742E+09 | 0.167115E+09 |
August | 0.757222E+09 | 0.316722E+09 | 0.440500E+09 | 0.737440E+09 | 0.196896E+09 |
September | 0.785229E+09 | 0.418316E+09 | 0.366912E+09 | 0.752750E+09 | 0.296901E+09 |
October | 0.692844E+09 | 0.407576E+09 | 0.285267E+09 | 0.605474E+09 | 0.453719E+09 |
November | 0.596936E+09 | 0.374579E+09 | 0.222357E+09 | 0.467411E+09 | 0.631513E+09 |
December | 0.656519E+09 | 0.430420E+09 | 0.226098E+09 | 0.435007E+09 | 0.986494E+09 |
Annual Sum or Average | 0.915238E+10 | 0.488741E+10 | 0.426497E+10 | 0.769452E+10 | 0.607820E+10 |
Minimum of Months | 0.596936E+09 | 0.167186E+09 | 0.222357E+09 | 0.435007E+09 | 0.167115E+09 |
Maximum of Months | 0.972707E+09 | 0.656985E+09 | 0.484444E+09 | 0.800984E+09 | 0.100863E+10 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.21 | 1039.50 | 182.26 | 67.23 | 115.02 | 0.00 | 0.00 |
February | 120.22 | 815.89 | 321.63 | 152.44 | 169.19 | 0.00 | 0.00 |
March | 280.01 | 632.02 | 452.47 | 256.34 | 196.13 | 0.00 | 0.00 |
April | 579.30 | 409.45 | 660.85 | 417.17 | 243.69 | 0.00 | 0.00 |
May | 836.57 | 242.86 | 807.24 | 453.29 | 353.95 | 0.00 | 0.00 |
June | 928.47 | 182.20 | 847.59 | 486.40 | 361.18 | 0.00 | 0.00 |
July | 979.52 | 165.14 | 870.16 | 518.27 | 351.90 | 0.00 | 0.00 |
August | 745.27 | 185.13 | 687.95 | 385.50 | 302.45 | 0.00 | 0.00 |
September | 479.77 | 280.27 | 502.48 | 259.33 | 243.14 | 0.00 | 0.00 |
October | 203.83 | 413.92 | 301.04 | 122.02 | 179.01 | 0.00 | 0.00 |
November | 46.30 | 625.71 | 175.65 | 55.68 | 119.97 | 0.00 | 0.00 |
December | 1.17 | 1013.63 | 141.64 | 39.28 | 102.36 | 0.00 | 0.00 |
Annual Sum or Average | 435.82 | 499.27 | 496.79 | 268.29 | 228.50 | 0.00 | 0.00 |
Minimum of Months | 1.17 | 165.14 | 141.64 | 39.28 | 102.36 | 0.00 | 0.00 |
Maximum of Months | 979.52 | 1039.50 | 870.16 | 518.27 | 361.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1163.86 | 1802.10 | 1542.81 | 1073.16 | 469.65 | 0.00 | 0.00 |
February | 1661.89 | 1517.25 | 1954.07 | 1319.82 | 634.25 | 0.00 | 0.00 |
March | 1419.30 | 1277.32 | 1722.64 | 1090.48 | 632.16 | 0.00 | 0.00 |
April | 1302.16 | 851.49 | 1560.16 | 846.91 | 713.25 | 0.00 | 0.00 |
May | 1119.29 | 488.23 | 1311.30 | 448.16 | 863.13 | 0.00 | 0.00 |
June | 1064.00 | 336.96 | 1176.59 | 313.47 | 863.12 | 0.00 | 0.00 |
July | 1237.28 | 303.49 | 1286.39 | 407.38 | 879.02 | 0.00 | 0.00 |
August | 1357.34 | 365.71 | 1373.97 | 574.69 | 799.28 | 0.00 | 0.00 |
September | 1416.06 | 594.08 | 1472.28 | 784.33 | 687.95 | 0.00 | 0.00 |
October | 1110.83 | 857.95 | 1257.16 | 739.54 | 517.61 | 0.00 | 0.00 |
November | 908.80 | 1180.21 | 1119.24 | 702.32 | 416.91 | 0.00 | 0.00 |
December | 821.25 | 1753.84 | 1191.25 | 780.99 | 410.25 | 0.00 | 0.00 |
Annual Sum or Average | 1211.97 | 941.57 | 1410.45 | 753.18 | 657.26 | 0.00 | 0.00 |
Minimum of Months | 821.25 | 303.49 | 1119.24 | 313.47 | 410.25 | 0.00 | 0.00 |
Maximum of Months | 1661.89 | 1802.10 | 1954.07 | 1319.82 | 879.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1161.65 | 1797.20 | 1542.81 | 1073.16 | 469.65 | 0.00 | 0.00 |
February | 1662.94 | 1506.07 | 1954.07 | 1319.82 | 634.25 | 0.00 | 0.00 |
March | 1423.20 | 1258.58 | 1722.64 | 1090.48 | 632.16 | 0.00 | 0.00 |
April | 1309.89 | 824.73 | 1560.16 | 846.91 | 713.25 | 0.00 | 0.00 |
May | 1125.17 | 469.29 | 1311.30 | 448.16 | 863.13 | 0.00 | 0.00 |
June | 1064.13 | 326.42 | 1176.59 | 313.47 | 863.12 | 0.00 | 0.00 |
July | 1232.75 | 300.35 | 1286.39 | 407.38 | 879.02 | 0.00 | 0.00 |
August | 1353.44 | 361.93 | 1373.97 | 574.69 | 799.28 | 0.00 | 0.00 |
September | 1418.95 | 576.79 | 1472.28 | 784.33 | 687.95 | 0.00 | 0.00 |
October | 1120.10 | 825.13 | 1257.16 | 739.54 | 517.61 | 0.00 | 0.00 |
November | 913.25 | 1157.50 | 1119.24 | 702.32 | 416.91 | 0.00 | 0.00 |
December | 819.72 | 1749.28 | 1191.25 | 780.99 | 410.25 | 0.00 | 0.00 |
Annual Sum or Average | 1213.88 | 926.98 | 1410.45 | 753.18 | 657.26 | 0.00 | 0.00 |
Minimum of Months | 819.72 | 300.35 | 1119.24 | 313.47 | 410.25 | 0.00 | 0.00 |
Maximum of Months | 1662.94 | 1797.20 | 1954.07 | 1319.82 | 879.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 231.09 | 376.58 | 317.46 | 220.82 | 96.64 | 0.00 | 0.00 |
February | 331.09 | 315.04 | 402.08 | 271.57 | 130.51 | 0.00 | 0.00 |
March | 284.35 | 265.64 | 354.46 | 224.38 | 130.08 | 0.00 | 0.00 |
April | 263.38 | 170.96 | 321.03 | 174.26 | 146.76 | 0.00 | 0.00 |
May | 228.89 | 94.00 | 269.82 | 92.22 | 177.60 | 0.00 | 0.00 |
June | 215.04 | 64.97 | 242.10 | 64.50 | 177.60 | 0.00 | 0.00 |
July | 247.07 | 62.39 | 264.69 | 83.82 | 180.87 | 0.00 | 0.00 |
August | 275.33 | 73.51 | 282.71 | 118.25 | 164.46 | 0.00 | 0.00 |
September | 290.41 | 114.55 | 302.94 | 161.39 | 141.56 | 0.00 | 0.00 |
October | 226.06 | 169.40 | 258.68 | 152.17 | 106.51 | 0.00 | 0.00 |
November | 180.33 | 243.64 | 230.30 | 144.51 | 85.79 | 0.00 | 0.00 |
December | 162.41 | 368.31 | 245.12 | 160.70 | 84.42 | 0.00 | 0.00 |
Annual Sum or Average | 243.99 | 192.74 | 290.22 | 154.98 | 135.24 | 0.00 | 0.00 |
Minimum of Months | 162.41 | 62.39 | 230.30 | 64.50 | 84.42 | 0.00 | 0.00 |
Maximum of Months | 331.09 | 376.58 | 402.08 | 271.57 | 180.87 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 21983161.29 | 0.278420E+10 | 0.488160E+09 | 0.180078E+09 | 0.308082E+09 | 0.00 | 0.00 |
February | 0.290837E+09 | 0.197380E+10 | 0.778076E+09 | 0.368773E+09 | 0.409303E+09 | 0.00 | 0.00 |
March | 0.749970E+09 | 0.169280E+10 | 0.121189E+10 | 0.686580E+09 | 0.525307E+09 | 0.00 | 0.00 |
April | 0.150154E+10 | 0.106129E+10 | 0.171293E+10 | 0.108129E+10 | 0.631635E+09 | 0.00 | 0.00 |
May | 0.224067E+10 | 0.650474E+09 | 0.216212E+10 | 0.121410E+10 | 0.948021E+09 | 0.00 | 0.00 |
June | 0.240660E+10 | 0.472269E+09 | 0.219694E+10 | 0.126075E+10 | 0.936188E+09 | 0.00 | 0.00 |
July | 0.262355E+10 | 0.442314E+09 | 0.233065E+10 | 0.138813E+10 | 0.942516E+09 | 0.00 | 0.00 |
August | 0.199614E+10 | 0.495853E+09 | 0.184260E+10 | 0.103253E+10 | 0.810078E+09 | 0.00 | 0.00 |
September | 0.124355E+10 | 0.726462E+09 | 0.130242E+10 | 0.672196E+09 | 0.630220E+09 | 0.00 | 0.00 |
October | 0.545945E+09 | 0.110864E+10 | 0.806295E+09 | 0.326826E+09 | 0.479469E+09 | 0.00 | 0.00 |
November | 0.120002E+09 | 0.162185E+10 | 0.455285E+09 | 0.144321E+09 | 0.310964E+09 | 0.00 | 0.00 |
December | 3138070.99 | 0.271492E+10 | 0.379362E+09 | 0.105199E+09 | 0.274163E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.137439E+11 | 0.157449E+11 | 0.156667E+11 | 0.846078E+10 | 0.720595E+10 | 0.00 | 0.00 |
Minimum of Months | 3138070.99 | 0.442314E+09 | 0.379362E+09 | 0.105199E+09 | 0.274163E+09 | 0.00 | 0.00 |
Maximum of Months | 0.262355E+10 | 0.278420E+10 | 0.233065E+10 | 0.138813E+10 | 0.948021E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.311728E+10 | 0.482674E+10 | 0.413226E+10 | 0.287434E+10 | 0.125792E+10 | 0.00 | 0.00 |
February | 0.402045E+10 | 0.367054E+10 | 0.472728E+10 | 0.319290E+10 | 0.153439E+10 | 0.00 | 0.00 |
March | 0.380145E+10 | 0.342118E+10 | 0.461392E+10 | 0.292075E+10 | 0.169318E+10 | 0.00 | 0.00 |
April | 0.337520E+10 | 0.220707E+10 | 0.404395E+10 | 0.219520E+10 | 0.184875E+10 | 0.00 | 0.00 |
May | 0.299792E+10 | 0.130767E+10 | 0.351217E+10 | 0.120036E+10 | 0.231181E+10 | 0.00 | 0.00 |
June | 0.275790E+10 | 0.873412E+09 | 0.304972E+10 | 0.812512E+09 | 0.223721E+10 | 0.00 | 0.00 |
July | 0.331394E+10 | 0.812881E+09 | 0.344548E+10 | 0.109112E+10 | 0.235436E+10 | 0.00 | 0.00 |
August | 0.363549E+10 | 0.979513E+09 | 0.368004E+10 | 0.153925E+10 | 0.214079E+10 | 0.00 | 0.00 |
September | 0.367043E+10 | 0.153987E+10 | 0.381615E+10 | 0.203299E+10 | 0.178317E+10 | 0.00 | 0.00 |
October | 0.297526E+10 | 0.229793E+10 | 0.336717E+10 | 0.198079E+10 | 0.138638E+10 | 0.00 | 0.00 |
November | 0.235560E+10 | 0.305911E+10 | 0.290106E+10 | 0.182043E+10 | 0.108064E+10 | 0.00 | 0.00 |
December | 0.219964E+10 | 0.469748E+10 | 0.319063E+10 | 0.209181E+10 | 0.109882E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.382206E+11 | 0.296934E+11 | 0.444798E+11 | 0.237524E+11 | 0.207274E+11 | 0.00 | 0.00 |
Minimum of Months | 0.219964E+10 | 0.812881E+09 | 0.290106E+10 | 0.812512E+09 | 0.108064E+10 | 0.00 | 0.00 |
Maximum of Months | 0.402045E+10 | 0.482674E+10 | 0.472728E+10 | 0.319290E+10 | 0.235436E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.311137E+10 | 0.481363E+10 | 0.413226E+10 | 0.287434E+10 | 0.125792E+10 | 0.00 | 0.00 |
February | 0.402298E+10 | 0.364347E+10 | 0.472728E+10 | 0.319290E+10 | 0.153439E+10 | 0.00 | 0.00 |
March | 0.381190E+10 | 0.337097E+10 | 0.461392E+10 | 0.292075E+10 | 0.169318E+10 | 0.00 | 0.00 |
April | 0.339524E+10 | 0.213771E+10 | 0.404395E+10 | 0.219520E+10 | 0.184875E+10 | 0.00 | 0.00 |
May | 0.301364E+10 | 0.125694E+10 | 0.351217E+10 | 0.120036E+10 | 0.231181E+10 | 0.00 | 0.00 |
June | 0.275824E+10 | 0.846092E+09 | 0.304972E+10 | 0.812512E+09 | 0.223721E+10 | 0.00 | 0.00 |
July | 0.330179E+10 | 0.804455E+09 | 0.344548E+10 | 0.109112E+10 | 0.235436E+10 | 0.00 | 0.00 |
August | 0.362504E+10 | 0.969384E+09 | 0.368004E+10 | 0.153925E+10 | 0.214079E+10 | 0.00 | 0.00 |
September | 0.367793E+10 | 0.149503E+10 | 0.381615E+10 | 0.203299E+10 | 0.178317E+10 | 0.00 | 0.00 |
October | 0.300007E+10 | 0.221002E+10 | 0.336717E+10 | 0.198079E+10 | 0.138638E+10 | 0.00 | 0.00 |
November | 0.236715E+10 | 0.300023E+10 | 0.290106E+10 | 0.182043E+10 | 0.108064E+10 | 0.00 | 0.00 |
December | 0.219555E+10 | 0.468526E+10 | 0.319063E+10 | 0.209181E+10 | 0.109882E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.382809E+11 | 0.292332E+11 | 0.444798E+11 | 0.237524E+11 | 0.207274E+11 | 0.00 | 0.00 |
Minimum of Months | 0.219555E+10 | 0.804455E+09 | 0.290106E+10 | 0.812512E+09 | 0.108064E+10 | 0.00 | 0.00 |
Maximum of Months | 0.402298E+10 | 0.481363E+10 | 0.472728E+10 | 0.319290E+10 | 0.235436E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.618955E+09 | 0.100863E+10 | 0.850274E+09 | 0.591437E+09 | 0.258836E+09 | 0.00 | 0.00 |
February | 0.800984E+09 | 0.762135E+09 | 0.972707E+09 | 0.656985E+09 | 0.315722E+09 | 0.00 | 0.00 |
March | 0.761604E+09 | 0.711494E+09 | 0.949382E+09 | 0.600986E+09 | 0.348396E+09 | 0.00 | 0.00 |
April | 0.682693E+09 | 0.443141E+09 | 0.832101E+09 | 0.451694E+09 | 0.380406E+09 | 0.00 | 0.00 |
May | 0.613069E+09 | 0.251757E+09 | 0.722681E+09 | 0.246992E+09 | 0.475689E+09 | 0.00 | 0.00 |
June | 0.557386E+09 | 0.168410E+09 | 0.627525E+09 | 0.167186E+09 | 0.460339E+09 | 0.00 | 0.00 |
July | 0.661742E+09 | 0.167115E+09 | 0.708958E+09 | 0.224513E+09 | 0.484444E+09 | 0.00 | 0.00 |
August | 0.737440E+09 | 0.196896E+09 | 0.757222E+09 | 0.316722E+09 | 0.440500E+09 | 0.00 | 0.00 |
September | 0.752750E+09 | 0.296901E+09 | 0.785229E+09 | 0.418316E+09 | 0.366912E+09 | 0.00 | 0.00 |
October | 0.605474E+09 | 0.453719E+09 | 0.692844E+09 | 0.407576E+09 | 0.285267E+09 | 0.00 | 0.00 |
November | 0.467411E+09 | 0.631513E+09 | 0.596936E+09 | 0.374579E+09 | 0.222357E+09 | 0.00 | 0.00 |
December | 0.435007E+09 | 0.986494E+09 | 0.656519E+09 | 0.430420E+09 | 0.226098E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.769452E+10 | 0.607820E+10 | 0.915238E+10 | 0.488741E+10 | 0.426497E+10 | 0.00 | 0.00 |
Minimum of Months | 0.435007E+09 | 0.167115E+09 | 0.596936E+09 | 0.167186E+09 | 0.222357E+09 | 0.00 | 0.00 |
Maximum of Months | 0.800984E+09 | 0.100863E+10 | 0.972707E+09 | 0.656985E+09 | 0.484444E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.3 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.6 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.5 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.48 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.18 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.96 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.19 | 13.59 | 3.45 | 8.98 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.33 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.48 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.07 | -2.0 | 3.82 | -8.5 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.3 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.98 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -0.9 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.85 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.46 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.93 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.24 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.70 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.34 | 23.33 | 8.07 | 19.92 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.35 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.80 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.60 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.43 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -0.9 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.34 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.3 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.0 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.61 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.6 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.4 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.33 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.46 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.93 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.90 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.70 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.75 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.35 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.70 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.4 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.75 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.24 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.06 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.90 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.75 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.35 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.22 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.16 | 3.43 | 9.18 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 06-DEC-02:00 | 0.00 | -0.0 | 3.60 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.75 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.314333E+10 | -.270575E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -437577983.2 | 58.99 | 0.00 | 0.00 |
February | 0.291436E+10 | -.252021E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -394153003.8 | 59.00 | 0.00 | 0.00 |
March | 0.328153E+10 | -.284828E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -433250146.7 | 58.99 | 0.00 | 0.00 |
April | 0.303678E+10 | -.262634E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -410441033.5 | 59.00 | 0.00 | 0.00 |
May | 0.298182E+10 | -.258139E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -400431971.2 | 59.00 | 0.00 | 0.00 |
June | 0.275996E+10 | -.238190E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -378059492.2 | 59.00 | 0.00 | 0.00 |
July | 0.265029E+10 | -.226381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -386482171.3 | 58.99 | 0.00 | 0.00 |
August | 0.265559E+10 | -.226849E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -387105040.7 | 58.99 | 0.00 | 0.00 |
September | 0.255210E+10 | -.216891E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -383190548.2 | 58.99 | 0.00 | 0.00 |
October | 0.271139E+10 | -.229376E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -417628982.6 | 59.00 | 0.00 | 0.00 |
November | 0.275701E+10 | -.234051E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -416497930.7 | 58.99 | 0.00 | 0.00 |
December | 0.301824E+10 | -.258158E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -436653178.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.344624E+11 | -.295809E+11 | 8760.00 | -.488147E+10 | 59.00 | |||||
Minimum of Months | 0.255210E+10 | -.284828E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -437577983.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.328153E+10 | -.216891E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -378059492.2 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.98 | 0.89 | 24-JAN-12:20 | 144.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.97 | 0.89 | 05-FEB-11:30 | 181.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.97 | 0.83 | 05-MAR-11:30 | 194.82 | 0.00 | 0.00 | 2.33 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.95 | 0.83 | 01-APR-11:30 | 231.93 | 0.00 | 0.00 | 16.17 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.91 | 0.83 | 01-MAY-08:09 | 1460.66 | 0.00 | 0.00 | 134.33 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.92 | 0.83 | 01-JUN-10:50 | 428.06 | 0.00 | 0.00 | 102.50 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.91 | 0.83 | 01-JUL-08:09 | 1558.93 | 0.00 | 0.00 | 127.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.92 | 0.83 | 01-AUG-08:50 | 330.39 | 0.00 | 0.00 | 55.50 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.95 | 0.83 | 02-SEP-11:30 | 249.54 | 0.00 | 0.00 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.96 | 0.89 | 02-OCT-10:20 | 202.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.98 | 0.94 | 01-NOV-08:50 | 151.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.98 | 0.94 | 01-DEC-11:09 | 140.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.94 | 524.07 | 0.00 | 0.00 | 447.83 | ||||||
Minimum of Months | 226.33 | 0.91 | 0.83 | 140.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 437.50 | 0.98 | 0.94 | 1558.93 | 0.00 | 0.00 | 134.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.344369E+11 | 52566.48 | 01-JAN-03:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248400E+11 | 52566.48 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204237E+11 | 52566.48 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.786743E+10 | 52566.48 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.642086E+09 | 52566.48 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 53139139.83 | 10669.99 | 28-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.394975E+10 | 52566.48 | 05-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137787E+11 | 52566.48 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.309934E+11 | 52566.48 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136985E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.344369E+11 | 52566.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126044E+12 | 292643.53 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.855718E+11 | 292643.53 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.674374E+11 | 292643.53 | 03-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204176E+11 | 261582.10 | 04-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.975337E+09 | 147936.01 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106642E+09 | 15945.51 | 23-SEP-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147284E+11 | 261752.92 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.500799E+11 | 292643.53 | 12-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114644E+12 | 292643.53 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.480005E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126044E+12 | 292643.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.132984E+11 | 38463.27 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.792401E+10 | 38463.27 | 01-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.582119E+10 | 38463.27 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164848E+10 | 38463.27 | 02-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81708072.12 | 38463.27 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 455080.98 | 876.36 | 23-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.658703E+09 | 38463.27 | 06-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.392071E+10 | 38463.27 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123492E+11 | 38463.27 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.457029E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132984E+11 | 38463.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167561E+11 | 33276.24 | 01-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107937E+11 | 33276.24 | 01-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.874353E+10 | 33276.24 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.320051E+10 | 33276.24 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.267353E+09 | 33276.24 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48145471.01 | 5233.85 | 29-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188533E+10 | 33276.24 | 06-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.646234E+10 | 33276.24 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158173E+11 | 33276.24 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.639743E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167561E+11 | 33276.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.253582E+11 | 59427.03 | 05-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164225E+11 | 50943.72 | 01-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138969E+11 | 38471.88 | 15-MAR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.550469E+10 | 23674.87 | 04-APR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.764265E+09 | 9581.10 | 08-MAY-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 77293132.69 | 2741.39 | 02-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21968754.86 | 1460.82 | 08-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80870397.49 | 4581.64 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.815681E+09 | 8520.29 | 27-SEP-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.518986E+10 | 19883.03 | 29-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111583E+11 | 39347.78 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240666E+11 | 56831.18 | 24-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103357E+12 | |||||||
Minimum of Months | 21968754.86 | 1460.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.253582E+11 | 59427.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 12963457.04 | 11069788.76 | 2318.70 | 23-APR-16:00 | 1969.02 | 0.00 |
May | 0.00 | 0.00 | 0.258577E+10 | 0.212204E+10 | 34088.31 | 25-MAY-20:31 | 26915.41 | 0.00 |
June | 0.00 | 0.00 | 0.753082E+10 | 0.551395E+10 | 36293.55 | 27-JUN-20:20 | 19753.84 | 0.00 |
July | 0.00 | 0.00 | 0.122225E+11 | 0.840374E+10 | 37238.50 | 03-JUL-23:02 | 17224.57 | 0.00 |
August | 0.00 | 0.00 | 0.850771E+10 | 0.582342E+10 | 36361.98 | 31-AUG-20:32 | 19141.56 | 0.00 |
September | 0.00 | 0.00 | 0.107941E+10 | 0.841160E+09 | 33542.36 | 01-SEP-20:33 | 18420.98 | 0.00 |
October | 0.00 | 0.00 | 16132020.58 | 15163146.06 | 1821.92 | 19-OCT-15:00 | 1680.40 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.319553E+11 | 0.227305E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.122225E+11 | 0.840374E+10 | 37238.50 | 26915.41 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.714094E+09 | 0.634479E+09 | 34467.67 | 23-APR-16:00 | 29589.34 | 0.00 |
May | 0.00 | 0.00 | 0.202176E+11 | 0.168825E+11 | 166145.29 | 25-MAY-21:51 | 124548.60 | 0.00 |
June | 0.00 | 0.00 | 0.506376E+11 | 0.363219E+11 | 177567.01 | 19-JUN-20:19 | 84144.01 | 0.00 |
July | 0.00 | 0.00 | 0.726914E+11 | 0.483427E+11 | 181181.91 | 04-JUL-00:22 | 83732.70 | 0.00 |
August | 0.00 | 0.00 | 0.536572E+11 | 0.356628E+11 | 177659.61 | 31-AUG-20:17 | 95568.97 | 0.00 |
September | 0.00 | 0.00 | 0.962960E+10 | 0.746392E+10 | 172676.22 | 01-SEP-00:42 | 88560.00 | 0.00 |
October | 0.00 | 0.00 | 0.589069E+09 | 0.547913E+09 | 22773.91 | 19-OCT-15:00 | 20737.13 | 0.00 |
November | 0.00 | 0.00 | 411.06 | 308.89 | 0.69 | 01-NOV-14:30 | 0.51 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.208137E+12 | 0.145856E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.726914E+11 | 0.483427E+11 | 181181.91 | 124548.60 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 46.25 | 46.25 | 0.07 | 08-FEB-15:10 | 0.07 | 0.00 |
March | 0.00 | 0.00 | 3105.48 | 3105.48 | 0.36 | 31-MAR-14:10 | 0.36 | 0.00 |
April | 0.00 | 0.00 | 0.282119E+09 | 0.269308E+09 | 22048.79 | 23-APR-19:00 | 20627.63 | 0.00 |
May | 0.00 | 0.00 | 0.339911E+10 | 0.307059E+10 | 22743.98 | 25-MAY-20:41 | 18403.60 | 0.00 |
June | 0.00 | 0.00 | 0.750639E+10 | 0.593255E+10 | 24390.73 | 27-JUN-20:10 | 13150.97 | 0.00 |
July | 0.00 | 0.00 | 0.113221E+11 | 0.839437E+10 | 24880.08 | 04-JUL-00:22 | 11204.62 | 0.00 |
August | 0.00 | 0.00 | 0.892836E+10 | 0.664327E+10 | 24390.33 | 31-AUG-20:12 | 12997.06 | 0.00 |
September | 0.00 | 0.00 | 0.222424E+10 | 0.193771E+10 | 23698.57 | 01-SEP-01:07 | 11565.77 | 0.00 |
October | 0.00 | 0.00 | 0.463582E+09 | 0.445781E+09 | 21081.59 | 22-OCT-18:08 | 17613.88 | 0.00 |
November | 0.00 | 0.00 | 9092.53 | 8341.96 | 0.60 | 21-NOV-14:00 | 0.43 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.341259E+11 | 0.266936E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.113221E+11 | 0.839437E+10 | 24880.08 | 20627.63 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 16.68 | 16.68 | 0.03 | 31-MAR-14:30 | 0.03 | 0.00 |
April | 0.00 | 0.00 | 0.138487E+09 | 0.128704E+09 | 5920.93 | 23-APR-14:20 | 5369.20 | 0.00 |
May | 0.00 | 0.00 | 0.215989E+10 | 0.191542E+10 | 19293.50 | 25-MAY-20:11 | 15534.95 | 0.00 |
June | 0.00 | 0.00 | 0.519515E+10 | 0.401572E+10 | 20672.30 | 19-JUN-20:50 | 9106.19 | 0.00 |
July | 0.00 | 0.00 | 0.820678E+10 | 0.595469E+10 | 21021.00 | 03-JUL-22:48 | 9947.84 | 0.00 |
August | 0.00 | 0.00 | 0.643085E+10 | 0.471920E+10 | 20606.60 | 31-AUG-20:12 | 10747.72 | 0.00 |
September | 0.00 | 0.00 | 0.144900E+10 | 0.126123E+10 | 19947.41 | 01-SEP-00:25 | 10359.17 | 0.00 |
October | 0.00 | 0.00 | 0.308486E+09 | 0.294814E+09 | 6904.31 | 19-OCT-14:30 | 6684.20 | 0.00 |
November | 0.00 | 0.00 | 505.00 | 505.00 | 0.14 | 17-NOV-13:30 | 0.14 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.238886E+11 | 0.182898E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.820678E+10 | 0.595469E+10 | 21021.00 | 15534.95 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112374E+11 | 0.92 | 6678.80 | 01-JAN-00:04 | 1.47 |
February | 0.962472E+10 | 0.88 | 6678.80 | 01-FEB-00:04 | 1.47 |
March | 0.100254E+11 | 0.82 | 6678.80 | 01-MAR-05:01 | 1.47 |
April | 0.796401E+10 | 0.67 | 6678.80 | 01-APR-04:01 | 1.47 |
May | 0.428976E+10 | 0.35 | 6678.80 | 01-MAY-04:01 | 1.47 |
June | 0.174830E+10 | 0.15 | 6678.80 | 01-JUN-04:02 | 1.46 |
July | 0.826794E+09 | 0.07 | 6678.80 | 01-JUL-07:08 | 1.45 |
August | 0.139380E+10 | 0.11 | 6678.80 | 01-AUG-07:09 | 1.44 |
September | 0.490481E+10 | 0.41 | 6678.80 | 01-SEP-07:08 | 1.44 |
October | 0.781262E+10 | 0.64 | 6678.80 | 01-OCT-07:02 | 1.45 |
November | 0.922298E+10 | 0.78 | 6678.80 | 01-NOV-04:01 | 1.46 |
December | 0.110729E+11 | 0.91 | 6678.80 | 01-DEC-02:34 | 1.47 |
Annual Sum or Average | 0.801235E+11 | 0.56 | |||
Minimum of Months | 0.826794E+09 | 0.07 | 6678.80 | 1.44 | |
Maximum of Months | 0.112374E+11 | 0.92 | 6678.80 | 1.47 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.203018E+10 | 0.55 | 1894.77 | 01-JAN-03:22 | 0.92 |
February | 0.169129E+10 | 0.52 | 1894.77 | 01-FEB-05:01 | 0.92 |
March | 0.171573E+10 | 0.45 | 1894.77 | 01-MAR-05:01 | 0.92 |
April | 0.137604E+10 | 0.39 | 1894.77 | 01-APR-04:01 | 0.92 |
May | 0.124205E+10 | 0.34 | 1894.77 | 01-MAY-04:01 | 0.92 |
June | 0.121772E+10 | 0.34 | 1894.77 | 25-JUN-19:04 | 0.90 |
July | 0.125173E+10 | 0.34 | 1894.77 | 03-JUL-23:02 | 0.90 |
August | 0.125165E+10 | 0.34 | 1894.77 | 07-AUG-21:01 | 0.90 |
September | 0.118851E+10 | 0.33 | 988.67 | 28-SEP-05:02 | 0.65 |
October | 0.130824E+10 | 0.36 | 1894.77 | 05-OCT-04:02 | 0.91 |
November | 0.149371E+10 | 0.41 | 1894.77 | 01-NOV-04:01 | 0.92 |
December | 0.194988E+10 | 0.53 | 1894.77 | 01-DEC-05:01 | 0.92 |
Annual Sum or Average | 0.177167E+11 | 0.41 | |||
Minimum of Months | 0.118851E+10 | 0.33 | 988.67 | 0.65 | |
Maximum of Months | 0.203018E+10 | 0.55 | 1894.77 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.122477E+11 | 0.67 | 13590.42 | 01-JAN-07:01 | 1.45 |
February | 0.103006E+11 | 0.63 | 13590.42 | 01-FEB-06:01 | 1.45 |
March | 0.107472E+11 | 0.60 | 13590.42 | 03-MAR-06:02 | 1.45 |
April | 0.908196E+10 | 0.55 | 12724.92 | 04-APR-06:02 | 1.40 |
May | 0.894719E+10 | 0.54 | 13590.42 | 16-MAY-20:18 | 1.44 |
June | 0.907288E+10 | 0.56 | 13590.42 | 06-JUN-20:17 | 1.43 |
July | 0.949181E+10 | 0.57 | 13590.42 | 02-JUL-18:16 | 1.43 |
August | 0.951583E+10 | 0.57 | 13590.42 | 06-AUG-18:18 | 1.43 |
September | 0.864099E+10 | 0.54 | 13590.42 | 01-SEP-00:42 | 1.42 |
October | 0.911914E+10 | 0.54 | 12729.68 | 30-OCT-06:02 | 1.41 |
November | 0.979105E+10 | 0.57 | 13590.42 | 12-NOV-08:62 | 1.45 |
December | 0.119402E+11 | 0.65 | 13590.42 | 01-DEC-06:02 | 1.44 |
Annual Sum or Average | 0.118897E+12 | 0.58 | |||
Minimum of Months | 0.864099E+10 | 0.54 | 12724.92 | 1.40 | |
Maximum of Months | 0.122477E+11 | 0.67 | 13590.42 | 1.45 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.226298E+10 | 0.67 | 1371.77 | 01-JAN-08:40 | 0.95 |
February | 0.203440E+10 | 0.64 | 1371.77 | 01-FEB-07:37 | 0.95 |
March | 0.226644E+10 | 0.62 | 1371.77 | 01-MAR-06:42 | 0.95 |
April | 0.216144E+10 | 0.59 | 1371.77 | 01-APR-06:03 | 0.95 |
May | 0.225456E+10 | 0.59 | 1371.77 | 01-MAY-05:06 | 0.95 |
June | 0.224251E+10 | 0.61 | 1371.77 | 01-JUN-09:30 | 0.94 |
July | 0.238476E+10 | 0.65 | 1371.77 | 01-JUL-12:13 | 0.94 |
August | 0.240836E+10 | 0.67 | 1371.77 | 01-AUG-15:30 | 0.94 |
September | 0.220296E+10 | 0.61 | 1371.77 | 01-SEP-06:20 | 0.93 |
October | 0.220721E+10 | 0.58 | 1371.77 | 01-OCT-17:50 | 0.95 |
November | 0.213967E+10 | 0.60 | 1371.77 | 01-NOV-05:45 | 0.95 |
December | 0.226183E+10 | 0.66 | 1371.77 | 01-DEC-08:30 | 0.95 |
Annual Sum or Average | 0.268271E+11 | 0.62 | |||
Minimum of Months | 0.203440E+10 | 0.58 | 1371.77 | 0.93 | |
Maximum of Months | 0.240836E+10 | 0.67 | 1371.77 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.185397E+10 | 0.70 | 1111.95 | 01-JAN-10:10 | 0.95 |
February | 0.166526E+10 | 0.67 | 1111.95 | 01-FEB-12:30 | 0.95 |
March | 0.184752E+10 | 0.63 | 1111.95 | 01-MAR-06:23 | 0.95 |
April | 0.175706E+10 | 0.60 | 1111.95 | 01-APR-05:08 | 0.95 |
May | 0.180887E+10 | 0.58 | 1111.95 | 01-MAY-06:07 | 0.95 |
June | 0.179126E+10 | 0.59 | 1111.95 | 01-JUN-16:40 | 0.95 |
July | 0.185638E+10 | 0.60 | 1111.95 | 01-JUL-06:00 | 0.94 |
August | 0.189146E+10 | 0.61 | 1111.95 | 01-AUG-08:30 | 0.94 |
September | 0.176220E+10 | 0.59 | 1111.95 | 01-SEP-11:03 | 0.94 |
October | 0.179093E+10 | 0.58 | 1111.95 | 01-OCT-10:58 | 0.94 |
November | 0.174255E+10 | 0.60 | 1111.95 | 01-NOV-05:02 | 0.95 |
December | 0.185254E+10 | 0.69 | 1111.95 | 01-DEC-06:07 | 0.95 |
Annual Sum or Average | 0.216200E+11 | 0.62 | |||
Minimum of Months | 0.166526E+10 | 0.58 | 1111.95 | 0.94 | |
Maximum of Months | 0.189146E+10 | 0.70 | 1111.95 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.28 | 0.00 |
February | 2.25 | 0.00 |
March | 1.85 | 0.00 |
April | 0.87 | 0.00 |
May | 0.00 | 0.00 |
June | 0.06 | 0.00 |
July | 0.03 | 0.00 |
August | 0.06 | 0.00 |
September | 0.00 | 0.00 |
October | 0.32 | 0.00 |
November | 1.78 | 0.00 |
December | 3.38 | 0.00 |
Annual Sum or Average | 13.88 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.38 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.38 | 25.84 |
May | 2.45 | 17.10 |
June | 1.29 | 4.46 |
July | 1.72 | 0.00 |
August | 2.75 | 0.78 |
September | 2.01 | 17.63 |
October | 0.81 | 25.84 |
November | 0.00 | 0.00 |
December | 0.06 | 0.00 |
Annual Sum or Average | 11.53 | 10.03 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.75 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.14 | 0.00 |
February | 0.87 | 0.00 |
March | 0.37 | 0.00 |
April | 0.76 | 1.48 |
May | 2.16 | 0.87 |
June | 2.56 | 0.00 |
July | 6.35 | 0.00 |
August | 4.95 | 0.00 |
September | 1.45 | 0.70 |
October | 0.58 | 2.44 |
November | 0.81 | 0.00 |
December | 2.36 | 0.00 |
Annual Sum or Average | 25.36 | 0.21 |
Minimum of Months | 0.37 | 0.00 |
Maximum of Months | 6.35 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.90 | 0.00 |
February | 1.23 | 0.00 |
March | 1.08 | 0.00 |
April | 0.63 | 0.32 |
May | 0.71 | 0.59 |
June | 0.92 | 0.00 |
July | 2.72 | 0.00 |
August | 3.37 | 0.00 |
September | 0.72 | 1.32 |
October | 0.86 | 1.69 |
November | 1.46 | 0.00 |
December | 3.27 | 0.00 |
Annual Sum or Average | 19.87 | 0.15 |
Minimum of Months | 0.63 | 0.00 |
Maximum of Months | 3.37 | 1.69 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 81.12 | 0.00 |
February | 61.58 | 0.00 |
March | 51.23 | 0.00 |
April | 68.29 | 0.00 |
May | 68.16 | 0.00 |
June | 27.88 | 0.00 |
July | 18.87 | 0.00 |
August | 29.48 | 0.00 |
September | 82.50 | 0.00 |
October | 69.46 | 0.00 |
November | 55.48 | 0.00 |
December | 71.16 | 0.00 |
Annual Sum or Average | 685.21 | 0.00 |
Minimum of Months | 18.87 | 0.00 |
Maximum of Months | 82.50 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.203018E+10 | 0.430462E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.169129E+10 | 0.310500E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.171573E+10 | 0.255297E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.137991E+10 | 0.983429E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.191190E+10 | 0.802607E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.308979E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.420366E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.331309E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.146325E+10 | 66423924.79 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.131275E+10 | 0.493719E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.149371E+10 | 0.172234E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.194988E+10 | 0.387417E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.255551E+11 | 0.171231E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.131275E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.420366E+10 | 0.430462E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.122477E+11 | 0.157554E+12 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.103006E+11 | 0.106965E+12 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.107472E+11 | 0.842967E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.929975E+10 | 0.255220E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.145961E+11 | 0.121917E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.227423E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.286817E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.237269E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.113403E+11 | 0.133302E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.929583E+10 | 0.184105E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.979105E+10 | 0.625999E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.119402E+11 | 0.143305E+12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.174710E+12 | 0.600006E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.929583E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.286817E+11 | 0.157554E+12 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.226298E+10 | 0.166230E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.203440E+10 | 0.990502E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.226644E+10 | 0.727649E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.223007E+10 | 0.206060E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.304294E+10 | 0.102135E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.396826E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.491643E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.438043E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.271323E+10 | 568851.22 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.231404E+10 | 0.823379E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.213968E+10 | 0.490089E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.226183E+10 | 0.154365E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.345307E+11 | 0.571286E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.203440E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.491643E+10 | 0.166230E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.185397E+10 | 0.209451E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.166526E+10 | 0.134922E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.184752E+10 | 0.109294E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.179053E+10 | 0.400064E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.230587E+10 | 0.334191E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.296824E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.365613E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.328472E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.208729E+10 | 60181838.76 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.186088E+10 | 0.235667E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.174255E+10 | 0.807793E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.185254E+10 | 0.197716E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.269155E+11 | 0.799679E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.166526E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.365613E+10 | 0.209451E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.203018E+10 | 0.00 | 0.344369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169129E+10 | 0.00 | 0.248400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171573E+10 | 0.00 | 0.204237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137604E+10 | 12963457.04 | 0.786743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124205E+10 | 0.257925E+10 | 0.642086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121772E+10 | 0.748838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125173E+10 | 0.120920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125165E+10 | 0.844502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118851E+10 | 0.107713E+10 | 53139139.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130824E+10 | 16132020.58 | 0.394975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149371E+10 | 0.00 | 0.137787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194988E+10 | 0.00 | 0.309934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177167E+11 | 0.317109E+11 | 0.136985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.203018E+10 | 0.120920E+11 | 0.344369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.122477E+11 | 0.00 | 0.126044E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103006E+11 | 0.00 | 0.855718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107472E+11 | 0.00 | 0.674374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.908196E+10 | 0.714094E+09 | 0.204176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.894719E+10 | 0.198167E+11 | 0.975337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.907288E+10 | 0.494196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.949181E+10 | 0.706388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.951583E+10 | 0.518004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.864099E+10 | 0.953325E+10 | 0.106642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.911914E+10 | 0.589069E+09 | 0.147284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.979105E+10 | 411.06 | 0.500799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119402E+11 | 0.00 | 0.114644E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118897E+12 | 0.202512E+12 | 0.480005E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.864099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122477E+11 | 0.706388E+11 | 0.126044E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.226298E+10 | 0.00 | 0.132984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.203440E+10 | 46.25 | 0.792401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226644E+10 | 3105.48 | 0.582119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216144E+10 | 0.282119E+09 | 0.164848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225456E+10 | 0.339911E+10 | 81708072.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.224251E+10 | 0.750639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.238476E+10 | 0.113221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.240836E+10 | 0.892836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.220296E+10 | 0.222424E+10 | 455080.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220721E+10 | 0.463582E+09 | 0.658703E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213967E+10 | 9092.53 | 0.392071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.226183E+10 | 0.00 | 0.123492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268271E+11 | 0.341259E+11 | 0.457029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.203440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.240836E+10 | 0.113221E+11 | 0.132984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.185397E+10 | 0.00 | 0.167561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166526E+10 | 0.00 | 0.107937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184752E+10 | 16.68 | 0.874353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.175706E+10 | 0.138487E+09 | 0.320051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180887E+10 | 0.215989E+10 | 0.267353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179126E+10 | 0.519515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185638E+10 | 0.820678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189146E+10 | 0.643085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176220E+10 | 0.144900E+10 | 48145471.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179093E+10 | 0.308486E+09 | 0.188533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174255E+10 | 505.00 | 0.646234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185254E+10 | 0.00 | 0.158173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216200E+11 | 0.238886E+11 | 0.639743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.166526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189146E+10 | 0.820678E+10 | 0.167561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.203018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137604E+10 | 0.00 | 0.00 | 0.00 | 3861874.20 | 0.00 | 0.983429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124205E+10 | 0.00 | 0.00 | 0.00 | 0.669854E+09 | 0.00 | 0.802607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121772E+10 | 0.00 | 0.00 | 0.00 | 0.187207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125173E+10 | 0.00 | 0.00 | 0.00 | 0.295194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125165E+10 | 0.00 | 0.00 | 0.00 | 0.206144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118851E+10 | 0.00 | 0.00 | 0.00 | 0.274735E+09 | 0.00 | 66423924.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130824E+10 | 0.00 | 0.00 | 0.00 | 4510443.49 | 0.00 | 0.493719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177167E+11 | 0.00 | 0.00 | 0.00 | 0.783841E+10 | 0.00 | 0.171231E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.118851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.203018E+10 | 0.00 | 0.00 | 0.00 | 0.295194E+10 | 0.00 | 0.430462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.122477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.908196E+10 | 0.00 | 0.00 | 0.00 | 0.217793E+09 | 0.00 | 0.255220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.894719E+10 | 0.00 | 0.00 | 0.00 | 0.564896E+10 | 0.00 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.907288E+10 | 0.00 | 0.00 | 0.00 | 0.136694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.949181E+10 | 0.00 | 0.00 | 0.00 | 0.191899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.951583E+10 | 0.00 | 0.00 | 0.00 | 0.142111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.864099E+10 | 0.00 | 0.00 | 0.00 | 0.269933E+10 | 0.00 | 0.133302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.911914E+10 | 0.00 | 0.00 | 0.00 | 0.176693E+09 | 0.00 | 0.184105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.979105E+10 | 0.00 | 0.00 | 0.00 | 130.60 | 0.00 | 0.625999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143305E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118897E+12 | 0.00 | 0.00 | 0.00 | 0.558132E+11 | 0.00 | 0.600006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.864099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122477E+11 | 0.00 | 0.00 | 0.00 | 0.191899E+11 | 0.00 | 0.157554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.226298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.203440E+10 | 0.00 | 0.00 | 0.00 | 12.35 | 0.00 | 0.990502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226644E+10 | 0.00 | 0.00 | 0.00 | 829.51 | 0.00 | 0.727649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216144E+10 | 0.00 | 0.00 | 0.00 | 68627229.35 | 0.00 | 0.206060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225456E+10 | 0.00 | 0.00 | 0.00 | 0.788385E+09 | 0.00 | 0.102135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.224251E+10 | 0.00 | 0.00 | 0.00 | 0.172575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.238476E+10 | 0.00 | 0.00 | 0.00 | 0.253167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.240836E+10 | 0.00 | 0.00 | 0.00 | 0.197208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.220296E+10 | 0.00 | 0.00 | 0.00 | 0.510272E+09 | 0.00 | 568851.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220721E+10 | 0.00 | 0.00 | 0.00 | 0.106830E+09 | 0.00 | 0.823379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 2432.10 | 0.00 | 0.490089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.226183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268271E+11 | 0.00 | 0.00 | 0.00 | 0.770362E+10 | 0.00 | 0.571286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.203440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.240836E+10 | 0.00 | 0.00 | 0.00 | 0.253167E+10 | 0.00 | 0.166230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.185397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184752E+10 | 0.00 | 0.00 | 0.00 | 4.33 | 0.00 | 0.109294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.175706E+10 | 0.00 | 0.00 | 0.00 | 33470906.92 | 0.00 | 0.400064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180887E+10 | 0.00 | 0.00 | 0.00 | 0.497005E+09 | 0.00 | 0.334191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179126E+10 | 0.00 | 0.00 | 0.00 | 0.117698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185638E+10 | 0.00 | 0.00 | 0.00 | 0.179975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189146E+10 | 0.00 | 0.00 | 0.00 | 0.139326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176220E+10 | 0.00 | 0.00 | 0.00 | 0.325090E+09 | 0.00 | 60181838.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179093E+10 | 0.00 | 0.00 | 0.00 | 69950290.02 | 0.00 | 0.235667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174255E+10 | 0.00 | 0.00 | 0.00 | 131.00 | 0.00 | 0.807793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216200E+11 | 0.00 | 0.00 | 0.00 | 0.529551E+10 | 0.00 | 0.799679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.166526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189146E+10 | 0.00 | 0.00 | 0.00 | 0.179975E+10 | 0.00 | 0.209451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162731E+11 | 0.00 | 0.00 | 0.20 |
February | 80195097.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123145E+11 | 0.00 | 0.00 | 0.20 |
March | 0.832024E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110194E+11 | 0.00 | 0.00 | 0.21 |
April | 0.334622E+10 | 2146511.27 | 101165.03 | 36259.49 | 14908364.89 | 0.396925E+10 | 44913654.66 | 2090.75 | 0.20 |
May | 0.256729E+10 | 0.100182E+09 | 0.00 | 4327591.26 | 0.00 | 0.214328E+09 | 0.228197E+10 | 0.00 | 0.33 |
June | 0.713182E+09 | 0.120958E+10 | 0.00 | 7971165.91 | 895046.12 | 0.00 | 0.321953E+10 | 0.00 | 0.45 |
July | 0.238170E+09 | 0.200729E+10 | 0.00 | 9374419.58 | 546010.93 | 0.00 | 0.244613E+10 | 0.00 | 0.47 |
August | 0.442529E+09 | 0.924520E+09 | 0.00 | 12718334.40 | 25903.99 | 0.00 | 0.368752E+10 | 0.00 | 0.52 |
September | 0.261166E+10 | 28642714.52 | 0.00 | 8322156.42 | 0.00 | 2957505.65 | 0.425938E+10 | 0.00 | 0.37 |
October | 0.527553E+10 | 0.00 | 0.00 | 598666.99 | 0.00 | 0.190806E+10 | 0.386809E+09 | 0.00 | 0.22 |
November | 0.217870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751225E+10 | 0.00 | 0.00 | 0.20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154113E+11 | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.182855E+11 | 0.427237E+10 | 101165.03 | 43348594.04 | 16375325.92 | 0.686252E+11 | 0.163263E+11 | 2090.75 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.527553E+10 | 0.200729E+10 | 101165.03 | 12718334.40 | 14908364.89 | 0.162731E+11 | 0.425938E+10 | 2090.75 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.422659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.860681E+11 | 0.00 | 0.00 | 0.39 |
February | 0.525888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448569E+11 | 0.00 | 0.00 | 0.39 |
March | 0.652383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269888E+11 | 0.00 | 0.00 | 0.40 |
April | 0.480367E+11 | 77942817.21 | 0.00 | 6351727.51 | 7349.94 | 0.487906E+10 | 0.518297E+10 | 0.00 | 0.42 |
May | 0.169048E+11 | 0.122790E+10 | 0.00 | 44620646.71 | 0.00 | 0.309825E+09 | 0.187885E+11 | 0.00 | 0.55 |
June | 0.400135E+10 | 0.965760E+10 | 0.00 | 64064471.12 | 2078077.23 | 0.00 | 0.185267E+11 | 0.00 | 0.65 |
July | 0.149387E+10 | 0.153370E+11 | 0.00 | 57804575.65 | 3420025.12 | 0.00 | 0.122894E+11 | 0.00 | 0.66 |
August | 0.278952E+10 | 0.705723E+10 | 0.00 | 78777550.97 | 0.00 | 0.00 | 0.193359E+11 | 0.00 | 0.70 |
September | 0.191331E+11 | 0.249835E+09 | 0.00 | 57262488.29 | 0.00 | 0.00 | 0.248352E+11 | 0.00 | 0.56 |
October | 0.501559E+11 | 0.00 | 0.00 | 7288665.76 | 0.00 | 0.271568E+10 | 0.424173E+10 | 0.00 | 0.41 |
November | 0.555327E+11 | 0.00 | 50895.90 | 141487.34 | 0.00 | 0.197130E+11 | 0.276848E+09 | 55861.05 | 0.39 |
December | 0.504018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710671E+11 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.408543E+12 | 0.336075E+11 | 50895.90 | 0.316312E+09 | 5505452.29 | 0.256599E+12 | 0.103477E+12 | 55861.05 | 0.49 |
Minimum of Months | 0.149387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.652383E+11 | 0.153370E+11 | 50895.90 | 78777550.97 | 3420025.12 | 0.860681E+11 | 0.248352E+11 | 55861.05 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.454953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747753E+10 | 0.00 | 0.00 | 0.39 |
February | 0.508924E+10 | 0.00 | 0.00 | 290527.85 | 0.00 | 0.377164E+10 | 0.363472E+09 | 0.00 | 0.39 |
March | 0.530989E+10 | 0.00 | 0.00 | 642554.60 | 0.00 | 0.279100E+10 | 0.745991E+09 | 0.00 | 0.40 |
April | 0.339700E+10 | 8802422.24 | 0.00 | 4955738.13 | 0.00 | 0.669948E+09 | 0.275779E+10 | 0.00 | 0.61 |
May | 0.783178E+09 | 0.133183E+09 | 0.00 | 11659432.61 | 0.00 | 38876355.30 | 0.487189E+10 | 0.00 | 1.06 |
June | 0.219656E+09 | 0.111401E+10 | 0.00 | 11409289.31 | 0.00 | 0.00 | 0.384543E+10 | 0.00 | 1.31 |
July | 47183303.72 | 0.186083E+10 | 0.00 | 10842507.04 | 4253826.39 | 0.00 | 0.303895E+10 | 0.00 | 1.34 |
August | 73129744.34 | 0.986686E+09 | 0.00 | 16323883.61 | 0.00 | 0.00 | 0.463793E+10 | 0.00 | 1.55 |
September | 0.675817E+09 | 43492521.96 | 0.00 | 19333759.57 | 0.00 | 0.00 | 0.710713E+10 | 0.00 | 1.22 |
October | 0.316181E+10 | 0.00 | 0.00 | 8081497.33 | 0.00 | 0.278023E+09 | 0.376226E+10 | 0.00 | 0.63 |
November | 0.461542E+10 | 0.00 | 0.00 | 871295.30 | 0.00 | 0.198307E+10 | 0.796046E+09 | 0.00 | 0.41 |
December | 0.429903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707646E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.322209E+11 | 0.414700E+10 | 0.00 | 84410485.34 | 4253826.39 | 0.240865E+11 | 0.319269E+11 | 0.00 | 0.81 |
Minimum of Months | 47183303.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.530989E+10 | 0.186083E+10 | 0.00 | 19333759.57 | 4253826.39 | 0.747753E+10 | 0.710713E+10 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101878E+11 | 0.00 | 0.00 | 0.39 |
February | 0.273550E+10 | 0.00 | 0.00 | 2053.96 | 0.00 | 0.638751E+10 | 14774583.53 | 0.00 | 0.39 |
March | 0.354710E+10 | 0.00 | 0.00 | 22355.86 | 0.00 | 0.508153E+10 | 35099945.74 | 0.00 | 0.40 |
April | 0.275121E+10 | 8068460.50 | 0.00 | 1679659.12 | 0.00 | 0.190139E+10 | 0.119071E+10 | 0.00 | 0.49 |
May | 0.145062E+10 | 0.112897E+09 | 0.00 | 4464612.24 | 0.00 | 0.137651E+09 | 0.238669E+10 | 0.00 | 0.75 |
June | 0.458373E+09 | 0.931991E+09 | 0.00 | 5467114.64 | 1725695.83 | 0.00 | 0.237280E+10 | 0.00 | 0.95 |
July | 0.190492E+09 | 0.154413E+10 | 0.00 | 6293366.32 | 3799847.81 | 0.00 | 0.197994E+10 | 0.00 | 1.01 |
August | 0.326466E+09 | 0.786208E+09 | 0.00 | 9399074.64 | 14220.95 | 0.00 | 0.296328E+10 | 0.00 | 1.14 |
September | 0.156305E+10 | 36839339.64 | 0.00 | 9758294.11 | 0.00 | 6242976.00 | 0.400919E+10 | 0.00 | 0.88 |
October | 0.354313E+10 | 0.00 | 0.00 | 3458772.13 | 0.00 | 0.969121E+09 | 0.147865E+10 | 0.00 | 0.51 |
November | 0.323386E+10 | 0.00 | 0.00 | 69789.17 | 0.00 | 0.377951E+10 | 93922990.19 | 0.00 | 0.39 |
December | 0.144133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993940E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.230865E+11 | 0.342014E+10 | 0.00 | 40615092.18 | 5539764.59 | 0.383901E+11 | 0.165251E+11 | 0.00 | 0.64 |
Minimum of Months | 0.190492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.354710E+10 | 0.154413E+10 | 0.00 | 9758294.11 | 3799847.81 | 0.101878E+11 | 0.400919E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |