Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2020-06-03 19:12:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1069.05 | 466.02 | 466.02 |
Net Site Energy | 1069.05 | 466.02 | 466.02 |
Total Source Energy | 2838.25 | 1237.25 | 1237.25 |
Net Source Energy | 2838.25 | 1237.25 | 1237.25 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 171.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 203.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 38.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 138.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 91.29 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 806.24 | 262.81 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 171.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 203.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 232.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 38.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 138.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 91.29 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 117.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 148.82 | 114.56 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 351.46 | 114.56 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 117.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 148.82 | 114.56 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 351.46 | 114.56 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 806.241 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 806.241 | 100.00 |
Total On-Site and Utility Electric Sources | 806.241 | 100.00 |
Total Electricity End Uses | 806.241 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1205.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 4.6739 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 11.3021 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 11.3021 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 11.3021 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 9.0417 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 10.1926 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 10.1926 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-JUL-14:30 | 12-FEB-09:09 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 188534.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 47099.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 15285.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9603.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 82728.79 | 190394.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 188534.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 47099.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 15285.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9603.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 185.92 | 0.00 | 0.00 | 0.00 |
Cooling | 643.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 734.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 121.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 615.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 98.96 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2553.36 | 284.88 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 81.05 | 0.00 | 0.00 | 0.00 |
Cooling | 280.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 320.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 190.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 43.14 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1113.07 | 124.19 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 81.05 | 0.00 | 0.00 | 0.00 |
Cooling | 280.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 320.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 190.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 43.14 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1113.07 | 124.19 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.80 |
CORE_RETAIL DIRECT AIR | 6.61 |
POINT_OF_SALE DIRECT AIR | 1.05 |
FRONT_RETAIL DIRECT AIR | 0.790276 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 1.14 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 1.14 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 32530.01 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 47374.01 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 207445.73 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 29106.88 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 23258.50 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.80 | 1.80 | 1.80 | 1.80 | 1.82 | 1.82 | 1.00 | 0.985654 | 1.82 |
PSZ-AC:2 | 6.61 | 6.61 | 6.61 | 6.61 | 6.85 | 6.85 | 1.00 | 0.964278 | 6.85 |
PSZ-AC:3 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
PSZ-AC:4 | 0.790276 | 0.790276 | 0.790276 | 0.790276 | 0.794373 | 0.794373 | 1.00 | 0.994842 | 0.794373 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.82 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 6.85 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.05 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 0.794373 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.82 | 1.82 | 1.82 | 1.20 | 36016.74 | 47374.01 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 6.85 | 6.85 | 6.85 | 4.52 | 167739.42 | 207445.73 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 0.694843 | 22205.53 | 29106.88 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.794373 | 0.794373 | 0.794373 | 0.794373 | 17910.90 | 23258.50 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.82 | 0.911595 | 1.22 | 33732.88 | 36016.74 | 18008.37 | 18008.37 | 0.739077 | 0.739080 | 0.739080 | 0.739080 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 6.85 | 3.43 | 4.57 | 159448.46 | 167739.42 | 83869.71 | 83869.71 | 0.679601 | 0.679600 | 0.679600 | 0.679600 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.05 | 0.526395 | 0.701860 | 20870.29 | 22205.53 | 11102.76 | 11102.76 | 0.719544 | 0.719540 | 0.719540 | 0.719540 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 0.794370 | 0.397185 | 0.529580 | 16923.79 | 17910.90 | 8955.45 | 8955.45 | 0.700921 | 0.700920 | 0.700920 | 0.700920 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.82 | 1950.90 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 6.85 | 11543.37 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1165.61 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.794373 | 879.50 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 4.674 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 12.744 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 11.302 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 14.532 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 11.302 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 32.822 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 11.302 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 14.532 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 9.042 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.042 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 1775.580 | 4.674 | 28.946 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1775.580 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 18088.827 | 11.302 | 69.994 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18088.827 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 1704.471 | 11.302 | 69.994 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1704.471 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 1704.471 | 11.302 | 69.994 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1704.471 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 108.500 | 9.042 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.500 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.7800 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 9 | -0.41768822E-14 | 0.27520919E-16 | -0.15672466E-09 | 0.83927561E-16 |
25 | 8 | 0.22856702E-07 | 0.10578700E-12 | 0.38803401E-03 | -0.25988854E-09 |
26 | 7 | -0.12546900E-01 | 0.54357740E-08 | -0.23525379E-01 | 0.14266284E-03 |
27 | 6 | 0.41364683 | 0.18861797E-05 | 0.47915075 | -0.48455579E-02 |
28 | 5 | -5.2715232 | 0.70271773E-04 | -4.4954566 | 0.64187715E-01 |
29 | 4 | 33.360936 | 0.57369956E-03 | 21.652120 | -0.42687724 |
30 | 3 | -111.98802 | 0.12481219E-02 | -56.042688 | 1.5262008 |
31 | 2 | 197.88617 | 0.70096321E-03 | 78.258916 | -2.9127067 |
32 | 1 | -171.44340 | 0.74721452E-04 | -55.366563 | 2.7504751 |
33 | 0 | 57.057407 | 0.42462867E-06 | 15.540328 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.42_SHGC_0.25 | 30 | 1 | VerySmooth | 2.387 | 0.252 | 0.162 | 0.276 |
2 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 31 | 1 | VerySmooth | 3.127 | 0.296 | 0.212 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.02786E-002 | 0.16139 | 0.62081 | 0.62081 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.15759E-002 | 0.21195 | 0.55558 | 0.55558 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 7.71143E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1915 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 20479.96245 | 24575.95493 | 1.49753 | 1.79703 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 21596.83701 | 25916.20441 | 0.94156 | 1.12987 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 75715.01831 | 90858.02197 | 5.50589 | 6.60706 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 52788.12810 | 63345.75372 | 2.26656 | 2.71987 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 11862.12043 | 14234.54451 | 0.87733 | 1.05279 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 10544.57920 | 12653.49504 | 0.46160 | 0.55392 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 8976.93855 | 10772.32626 | 0.65856 | 0.79028 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 10547.67066 | 12657.20479 | 0.46174 | 0.55408 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40000 | 1.44457E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 27100.98757 | 32521.18509 | 0.95056 | 1.14067 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | -6.30000 | 2.29779E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 24680.02 | 1.82319 | 1.82319 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 32515.03 | 1.12987 | 1.12987 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 103448.92 | 6.85182 | 6.85182 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 120628.44 | 2.71987 | 2.71987 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 15124.45 | 1.05279 | 1.05279 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 17992.86 | 0.55392 | 0.55392 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 12249.99 | 0.79437 | 0.79437 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 17996.53 | 0.55408 | 0.55408 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.79703 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.60706 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05279 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.79028 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.14067 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.14067 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 32530.00641 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.79703 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.79703 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.79703 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.79703 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.82319 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.82319 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.98565 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.60706 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.60706 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.60706 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 6.60706 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.85182 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 6.85182 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.96428 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05279 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05279 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05279 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05279 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05279 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05279 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.79028 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.79028 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.79028 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.79028 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.79437 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.79437 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 0.99484 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.82319 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 6.85182 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.05279 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.79437 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.82319 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.82319 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.82319 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.82319 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.20330 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.82319 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.91160 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.21546 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 33732.87799 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 36016.74000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 18008.37000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 18008.37000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73908 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73908 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73908 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73908 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36016.74000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 47374.01143 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.82319 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1950.89770 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 47374.01143 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.85182 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 6.85182 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 6.85182 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.85182 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.52220 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 6.85182 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.42591 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.56788 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 159448.45652 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 167739.42000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 83869.71000 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 83869.71000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67960 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67960 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67960 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67960 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 167739.42000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 207445.73422 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 6.85182 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 11543.36790 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 207445.73422 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05279 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05279 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05279 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05279 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69484 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05279 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52640 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70186 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 20870.29105 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22205.53000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11102.76500 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11102.76500 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71954 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71954 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71954 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71954 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22205.53000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29106.88101 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05279 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1165.60767 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29106.88101 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.79437 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.79437 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.79437 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.79437 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.79437 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.79437 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.39719 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.52958 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16923.78550 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17910.90000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8955.45000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8955.45000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70092 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70092 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70092 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70092 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17910.90000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23258.50040 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.79437 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 879.49736 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 23258.50040 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 34584.2 | 11.50 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 162335.4 | 13.14 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 21377.4 | 118.85 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 17285.4 | 171.60 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.25 | N/A | 2.387 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.25 | N/A | 2.387 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.25 | N/A | 2.387 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 5.3268807840E-002 | 0.2253839135 | Pass | Pass | 8.6798900487E-002 | 0.2529679709 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 3.3708355098E-002 | 0.1381175182 | Pass | Pass | 0.2765870815 | 1.5092269884 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 5.5580240211E-002 | 0.2347169907 | Pass | Pass | 0.3127016156 | 1.4562435582 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 6.4929067762E-002 | 0.2732465385 | Pass | Pass | 6.3021175680E-002 | 0.2226571820 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1378259169 | 0.5883020378 | Pass | Pass | 6.1247541543E-002 | 0.6103285580 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.55_SHGC_0.3 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.296 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.42_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.387 | 0.252 | 0.276 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.42_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.387 | 0.252 | 0.276 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.42_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.387 | 0.252 | 0.276 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 2.550 | 0.262 | 0.303 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 2.550 | 0.262 | 0.303 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 4.6739 | 379.89 | 1775.58 | LightsWired | BLDG_LIGHT_BACK_SCH | 55.08 | 168.00 | 53.35 | 0.0000 | Y | 17.78 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 11.3021 | 1600.48 | 18088.83 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 50.98 | 0.0000 | Y | 173.11 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 11.3021 | 150.81 | 1704.47 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 65.23 | 0.0000 | Y | 20.87 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 11.3021 | 150.81 | 1704.47 | LightsWired | BLDG_LIGHT_FRONT_SCH | 67.15 | 168.00 | 63.20 | 0.0000 | Y | 20.22 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 9.0417 | 12.00 | 108.50 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 57.54 | 168.00 | 4.00 | 0.0000 | Y | 0.08 |
Interior Lighting Total | 10.1926 | 2293.99 | 23381.85 | 232.07 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 18088.83 | 4522.21 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 18088.83 | 4522.21 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 316.30 | AstronomicalClock | - | 41.77 | 41.77 | 2.48 | |
EXTERIOR_LIGHTS_B | 3054.90 | AstronomicalClock | - | 83.77 | 62.77 | 36.00 | |
Exterior Lighting Total | 3371.20 | 38.48 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 36016.74 | 26619.25 | 9397.49 | 0.74 | 3.80 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 167739.42 | 113995.71 | 53743.71 | 0.68 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22205.53 | 15977.77 | 6227.76 | 0.72 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17910.90 | 12554.11 | 5356.79 | 0.70 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 34584.2 | 11.50 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 162335.4 | 13.14 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 21377.4 | 118.85 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 17285.4 | 171.60 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 32530.01 | 0.81 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 47374.01 | 0.81 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 207445.73 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29106.88 | 0.81 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 23258.50 | 0.81 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.56 | 622.50 | 1.14 | 1262.90 | 1107.16 | 1.00 | 1.36 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.82 | 1950.90 | 1070.05 | 1.00 | 1.33 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 6.85 | 11543.37 | 1684.71 | 1.00 | 1.16 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1165.61 | 1107.16 | 1.00 | 1.39 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.79 | 879.50 | 1107.16 | 1.00 | 1.47 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 20479.96 | 24575.95 | 64.69 | 1.498 | 1.797 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01002 | 27.37 | 0.01445 | 0.232 | 0.00 |
CORE_RETAIL | 75715.02 | 90858.02 | 56.77 | 5.506 | 6.607 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01030 | 27.37 | 0.01445 | 1.890 | 0.00 |
POINT_OF_SALE | 11862.12 | 14234.54 | 94.39 | 0.877 | 1.053 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00909 | 27.37 | 0.01445 | 0.178 | 0.00 |
FRONT_RETAIL | 8976.94 | 10772.33 | 71.43 | 0.659 | 0.790 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.00979 | 27.37 | 0.01445 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 33.65 | 100.00 | 0.00001 | 34.40 | 0.01445 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 21596.84 | 25916.20 | 68.22 | 0.942 | 1.130 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00743 | -6.30 | 0.00230 | 0.232 | 0.00 |
CORE_RETAIL | 52788.13 | 63345.75 | 39.58 | 2.267 | 2.720 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00744 | -6.30 | 0.00230 | 1.890 | 0.00 |
POINT_OF_SALE | 10544.58 | 12653.50 | 83.90 | 0.462 | 0.554 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00763 | -6.30 | 0.00230 | 0.178 | 0.00 |
FRONT_RETAIL | 10547.67 | 12657.20 | 83.93 | 0.462 | 0.554 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00763 | -6.30 | 0.00230 | 0.178 | 0.00 |
FRONT_ENTRY | 27100.99 | 32521.19 | 2710.10 | 0.951 | 1.141 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 16.00 | 15.91 | 0.00504 | -6.30 | 0.00230 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.82 | 1.82 | 1.13 | 1.13 | 1.8232 | 1.7970 | 1.8232 | 0.9857 | 1.0000 |
PSZ-AC:2 | 6.85 | 6.85 | 2.72 | 2.72 | 6.8518 | 6.6071 | 6.8518 | 0.9643 | 1.0000 |
PSZ-AC:3 | 1.05 | 1.05 | 0.55 | 0.55 | 1.0528 | 1.0528 | 1.0528 | 1.0000 | 1.0000 |
PSZ-AC:4 | 0.79 | 0.79 | 0.55 | 0.55 | 0.7944 | 0.7903 | 0.7944 | 0.9948 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 32530.006 | 32530.006 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 32530.01 | 32530.01 | 1.140667 | 15.63 | 9.34 | 0.00500465 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 15.91 | 0.00503871 | 43.4132 | 32521.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 18008.370 | 0.000 | 1.823190 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 18008.37 | 13421.42 | 1.823190 | 24.40 | 17.65 | 0.01032962 | 12.80 | 11.77 | 0.00850000 | 27.97 | 0.01444568 | 21.76 | 12.7012 | 23.88 | 0.01002255 | 52.2538 | 20479.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 47374.011 | 47374.011 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 47374.01 | 47374.01 | 1.823188 | 15.33 | 10.67 | 0.00637975 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 12.7012 | 21.11 | 0.00743200 | 46.0569 | 21596.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 83869.710 | 0.000 | 6.851820 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 83869.71 | 60995.13 | 6.851820 | 27.09 | 18.96 | 0.01090680 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01444567 | 23.51 | 27.5870 | 23.88 | 0.01030143 | 53.6858 | 74996.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 207445.734 | 207445.734 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 207445.73 | 207445.73 | 6.851824 | 1.98 | 1.07 | 0.00386532 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 27.5870 | 21.11 | 0.00743660 | 46.0826 | 52788.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 11102.765 | 0.000 | 1.052790 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 11102.76 | 8848.56 | 1.052790 | 25.76 | 17.83 | 0.01000081 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01444567 | 23.51 | 16.9180 | 23.89 | 0.00909322 | 47.4699 | 10952.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 29106.881 | 29106.881 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29106.88 | 29106.88 | 1.052792 | 12.16 | 8.78 | 0.00591524 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 16.9179 | 21.11 | 0.00762970 | 47.2660 | 10544.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 8955.450 | 0.000 | 0.794370 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 8955.45 | 6834.95 | 0.794370 | 26.29 | 18.31 | 0.01039337 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01444567 | 23.51 | 22.4216 | 23.88 | 0.00979453 | 51.0820 | 8519.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 23258.500 | 23258.500 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23258.50 | 23258.50 | 0.794373 | 12.16 | 8.79 | 0.00591596 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 22.4215 | 21.11 | 0.00763001 | 47.2679 | 10547.67 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 32530.006 | 32530.006 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 1.140667 | 1.32428813 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 32530.01 | 32530.01 | 1.0000 | 1.32428813 | 1.140667 | 15.63 | 9.34 | 0.00500465 | 28372.2 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32530.01 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 15.92 | 0.00503871 | 15.91 | 0.00503871 | 43.4132 | 32521.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18008.370 | 0.000 | 1.823190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0422 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 18008.37 | 13421.42 | 1.0000 | 2.11668082 | 1.823190 | 24.40 | 17.65 | 0.01032962 | 50823.9 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18008.37 | 27.97 | 0.01444568 | 21.76 | 0.23156651 | 12.7012 | 23.88 | 0.00973077 | 23.88 | 0.01002255 | 52.2538 | 20479.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 47374.011 | 47374.011 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.823188 | 2.11667888 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 47374.01 | 47374.01 | 1.0000 | 2.11667888 | 1.823188 | 15.33 | 10.67 | 0.00637975 | 31543.9 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47374.01 | -6.30 | 0.00229779 | -6.30 | 0.23156651 | 12.7012 | 20.91 | 0.00743200 | 21.11 | 0.00743200 | 46.0569 | 21596.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 83869.710 | 0.000 | 6.851820 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.1152 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 83869.71 | 60995.13 | 1.0000 | 7.95480228 | 6.851820 | 27.09 | 18.96 | 0.01090680 | 55047.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 83869.71 | 34.40 | 0.01444567 | 23.51 | 1.89021192 | 27.5870 | 23.89 | 0.00935662 | 23.88 | 0.01030143 | 53.6858 | 74996.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 207445.734 | 207445.734 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 6.851824 | 7.95480672 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 207445.73 | 207445.73 | 1.0000 | 7.95480672 | 6.851824 | 1.98 | 1.07 | 0.00386532 | 11674.2 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 207445.73 | -6.30 | 0.00229779 | -6.30 | 1.89021192 | 27.5870 | 20.86 | 0.00743660 | 21.11 | 0.00743660 | 46.0826 | 52788.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11102.765 | 0.000 | 1.052790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4310 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 11102.76 | 8848.56 | 1.0000 | 1.22226449 | 1.052790 | 25.76 | 17.83 | 0.01000081 | 51374.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11102.76 | 34.40 | 0.01444567 | 23.51 | 0.17811053 | 16.9180 | 23.89 | 0.00903801 | 23.89 | 0.00909322 | 47.4699 | 10952.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29106.881 | 29106.881 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.052792 | 1.22226662 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29106.88 | 29106.88 | 1.0000 | 1.22226662 | 1.052792 | 12.16 | 8.78 | 0.00591524 | 27142.5 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29106.88 | -6.30 | 0.00229779 | -6.30 | 0.17811053 | 16.9179 | 20.90 | 0.00762970 | 21.11 | 0.00762970 | 47.2660 | 10544.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8955.450 | 0.000 | 0.794370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1608 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 8955.45 | 6834.95 | 1.0000 | 0.92224493 | 0.794370 | 26.29 | 18.31 | 0.01039337 | 52922.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8955.45 | 34.40 | 0.01444567 | 23.51 | 0.17811053 | 22.4216 | 23.89 | 0.00919053 | 23.88 | 0.00979453 | 51.0820 | 8519.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23258.500 | 23258.500 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.794373 | 0.92224879 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23258.50 | 23258.50 | 1.0000 | 0.92224879 | 0.794373 | 12.16 | 8.79 | 0.00591596 | 27147.0 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23258.50 | -6.30 | 0.00229779 | -6.30 | 0.17811053 | 22.4215 | 20.90 | 0.00763001 | 21.11 | 0.00763001 | 47.2679 | 10547.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialEnthalpy | 0.23 | 1.82 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialEnthalpy | 1.89 | 6.85 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialEnthalpy | 0.18 | 1.05 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialEnthalpy | 0.18 | 0.79 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 2646.00 | 2765.67 | 1026.33 |
CORE_RETAIL | 2614.67 | 2536.83 | 757.33 |
POINT_OF_SALE | 2596.33 | 1983.50 | 367.50 |
FRONT_RETAIL | 2602.50 | 2451.00 | 732.17 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3219.83 | 2947.00 | 1205.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 18.67 | 9.50 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 9.33 | 83.33 | 0.00 | 0.00 |
FRONT_RETAIL | 16.17 | 16.33 | 0.00 | 0.00 |
FRONT_ENTRY | 400.67 | 0.00 | 0.00 | 0.00 |
Facility | 422.00 | 97.33 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.42 | 61.34 | 2317.33 | 0.502 | 0.029 | 0.000 | 0.000 |
CORE_RETAIL | 128.15 | 258.43 | 9762.95 | 0.793 | 0.006 | 0.000 | 0.000 |
POINT_OF_SALE | 12.08 | 24.35 | 919.94 | 0.973 | 0.032 | 0.000 | 0.000 |
FRONT_RETAIL | 12.08 | 24.35 | 919.94 | 0.956 | 0.032 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.42 | 61.34 | 2317.33 | 0.352 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.15 | 258.43 | 9762.95 | 0.681 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.08 | 24.35 | 919.94 | 0.681 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.08 | 24.35 | 919.94 | 0.681 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 806.24 | 2265.44 | 19-FEB-07:40 | 82728.79 | 08-JUL-14:30 |
Electricity:Building | 426.36 | 2265.44 | 01-JAN-00:10 | 31292.41 | 02-JAN-17:40 |
Electricity:Zone:BACK_SPACE | 67.55 | 535.60 | 01-JAN-00:10 | 4001.15 | 02-JAN-09:10 |
InteriorLights:Electricity | 232.07 | 493.85 | 01-JAN-00:10 | 20551.52 | 02-JAN-17:40 |
InteriorLights:Electricity:Zone:BACK_SPACE | 17.78 | 81.78 | 01-JAN-00:10 | 1249.73 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 232.07 | 493.85 | 01-JAN-00:10 | 20551.52 | 02-JAN-17:40 |
Electricity:Zone:CORE_RETAIL | 257.04 | 1109.80 | 01-JAN-00:10 | 20919.52 | 02-JAN-17:40 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 173.11 | 344.55 | 01-JAN-00:10 | 16279.94 | 02-JAN-17:40 |
Electricity:Zone:POINT_OF_SALE | 73.56 | 512.89 | 01-JAN-00:10 | 4446.74 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 20.87 | 32.47 | 01-JAN-00:10 | 1534.02 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 28.13 | 104.57 | 01-JAN-00:10 | 1922.42 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 20.22 | 32.47 | 01-JAN-00:10 | 1485.24 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 0.08 | 2.58 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 0.08 | 2.58 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 |
InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.77 | 453.82 | 01-JAN-00:10 | 2751.42 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 83.93 | 765.25 | 01-JAN-00:10 | 4639.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.69 | 480.42 | 01-JAN-00:10 | 2912.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.91 | 72.11 | 01-JAN-00:10 | 437.18 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 806.24 | 2265.44 | 19-FEB-07:40 | 82728.79 | 08-JUL-14:30 |
ElectricityPurchased:Plant | 806.24 | 2265.44 | 19-FEB-07:40 | 82728.79 | 08-JUL-14:30 |
Cogeneration:ElectricityPurchased | 806.24 | 2265.44 | 19-FEB-07:40 | 82728.79 | 08-JUL-14:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 806.24 | 2265.44 | 19-FEB-07:40 | 82728.79 | 08-JUL-14:30 |
ElectricityNet:Plant | 806.24 | 2265.44 | 19-FEB-07:40 | 82728.79 | 08-JUL-14:30 |
Cogeneration:ElectricityNet | 806.24 | 2265.44 | 19-FEB-07:40 | 82728.79 | 08-JUL-14:30 |
Electricity:HVAC | 341.40 | 0.00 | 01-JAN-00:10 | 56702.80 | 08-JUL-14:30 |
Fans:Electricity | 138.14 | 0.00 | 01-JAN-00:10 | 12307.49 | 12-FEB-09:10 |
General:Fans:Electricity | 138.14 | 0.00 | 01-JAN-00:10 | 12307.49 | 12-FEB-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 203.26 | 0.00 | 01-JAN-00:10 | 47099.62 | 08-JUL-14:30 |
ExteriorLights:Electricity | 38.48 | 0.00 | 01-JAN-07:50 | 3371.20 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 38.48 | 0.00 | 01-JAN-07:50 | 3371.20 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 262.81 | 1860.00 | 09-JAN-05:40 | 190394.29 | 12-FEB-09:10 |
Gas:Plant | 91.29 | 1860.00 | 09-JAN-05:40 | 5043.70 | 01-FEB-12:10 |
WaterSystems:Gas | 91.29 | 1860.00 | 09-JAN-05:40 | 5043.70 | 01-FEB-12:10 |
Water Heater:WaterSystems:Gas | 91.29 | 1860.00 | 09-JAN-05:40 | 5043.70 | 01-FEB-12:10 |
Gas:HVAC | 171.51 | 0.00 | 01-JAN-00:10 | 188534.29 | 12-FEB-09:10 |
Heating:Gas | 171.51 | 0.00 | 01-JAN-00:10 | 188534.29 | 12-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1507.77 | 0.00 | 01-JAN-00:10 | 237645.06 | 08-JUL-14:00 |
EnergyTransfer:Building | 593.54 | 0.00 | 01-JAN-00:10 | 98907.73 | 12-FEB-08:10 |
EnergyTransfer:Zone:BACK_SPACE | 91.22 | 0.00 | 01-JAN-00:10 | 41966.08 | 12-FEB-07:10 |
Heating:EnergyTransfer | 47.38 | 0.00 | 01-JAN-00:10 | 98907.73 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 14.36 | 0.00 | 01-JAN-00:10 | 41966.08 | 12-FEB-07:10 |
Cooling:EnergyTransfer | 546.16 | 0.00 | 01-JAN-00:10 | 72407.88 | 08-JUL-14:50 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 76.86 | 0.00 | 01-JAN-00:10 | 12074.71 | 08-JUL-16:00 |
EnergyTransfer:Zone:CORE_RETAIL | 359.48 | 0.00 | 01-JAN-00:10 | 67008.81 | 09-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 12.02 | 0.00 | 01-JAN-00:10 | 63289.13 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 347.46 | 0.00 | 01-JAN-00:10 | 55795.70 | 08-JUN-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 78.75 | 0.00 | 01-JAN-00:10 | 18664.85 | 12-FEB-07:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 2.59 | 0.00 | 01-JAN-00:10 | 18664.85 | 12-FEB-07:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 76.16 | 0.00 | 01-JAN-00:10 | 9008.47 | 11-OCT-14:10 |
EnergyTransfer:Zone:FRONT_RETAIL | 50.68 | 0.00 | 01-JAN-00:10 | 17924.48 | 12-FEB-07:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 4.99 | 0.00 | 01-JAN-00:10 | 17924.48 | 12-FEB-07:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 45.69 | 0.00 | 01-JAN-00:10 | 9266.64 | 11-OCT-21:40 |
EnergyTransfer:Zone:FRONT_ENTRY | 13.41 | 0.00 | 01-JAN-00:10 | 25274.62 | 07-JAN-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 13.41 | 0.00 | 01-JAN-00:10 | 25274.62 | 07-JAN-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 914.23 | 0.00 | 01-JAN-00:10 | 166041.90 | 08-JUL-14:00 |
HeatingCoils:EnergyTransfer | 137.87 | 0.00 | 01-JAN-00:10 | 151384.89 | 12-FEB-09:10 |
CoolingCoils:EnergyTransfer | 776.37 | 0.00 | 01-JAN-00:10 | 166041.90 | 08-JUL-14:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 14.362 | -76.858 | 0.000 | 0.000 | 38.513 | 17.781 | 49.772 | 0.000 | 0.000 | 0.645 | 0.000 | 0.000 | 0.000 | 0.000 | -11.204 | -33.010 |
CORE_RETAIL | 0.000 | 0.000 | 12.024 | -347.453 | 0.000 | 0.000 | 162.048 | 173.112 | 83.927 | 28.405 | 0.000 | 0.462 | 0.000 | 0.000 | -16.168 | 0.000 | -10.021 | -86.336 |
POINT_OF_SALE | 0.000 | 0.000 | 2.590 | -76.160 | 0.000 | 0.000 | 14.978 | 20.870 | 52.689 | 27.269 | 0.000 | 0.279 | 0.002 | 0.000 | -14.067 | 0.000 | -5.196 | -23.252 |
FRONT_RETAIL | 0.000 | 0.000 | 4.992 | -45.686 | 0.000 | 0.000 | 15.176 | 20.222 | 7.908 | 27.264 | 0.000 | 0.279 | 0.000 | 0.000 | -13.640 | 0.000 | -4.968 | -11.548 |
FRONT_ENTRY | 13.410 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.081 | 0.000 | 5.562 | 0.000 | 1.153 | 3.413 | 0.000 | -2.582 | 0.000 | -21.038 | 0.000 |
Total Facility | 13.410 | 0.000 | 33.967 | -546.157 | 0.000 | 0.000 | 230.715 | 232.067 | 194.297 | 88.500 | 0.000 | 2.819 | 3.415 | 0.000 | -46.457 | 0.000 | -52.427 | -154.146 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 09-JUN-23:21 | 0.00 | 0.00 | 0.00 | -37046.72 | 0.00 | 0.00 | 0.00 | 81.78 | 605.09 | 0.00 | 0.00 | 0.00 | 36700.85 | 0.00 | -0.00 | 0.00 | -341.00 | 0.00 |
CORE_RETAIL | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | -168331.63 | 0.00 | 0.00 | 1655.29 | 344.55 | 2062.04 | 0.00 | 0.00 | 0.00 | 165434.46 | 0.00 | -1003.45 | 0.00 | -161.26 | 0.00 |
POINT_OF_SALE | 09-JUN-21:31 | 0.00 | 0.00 | 0.00 | -20318.92 | 0.00 | 0.00 | 0.00 | 32.47 | 640.56 | 0.00 | 0.00 | 0.00 | 20152.99 | 0.00 | -436.90 | 0.00 | -70.20 | 0.00 |
FRONT_RETAIL | 11-OCT-23:31 | 0.00 | 0.00 | 0.00 | -20447.36 | 0.00 | 0.00 | 0.00 | 32.47 | 96.14 | 0.00 | 0.00 | 0.00 | 21707.94 | 0.00 | -1006.92 | 0.00 | -382.27 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | -174130.66 | 0.00 | 0.00 | 2426.15 | 493.85 | 4773.73 | 0.00 | 0.00 | 0.00 | 169758.70 | 0.00 | -2787.00 | 0.00 | -534.76 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 10-JAN-05:42 | 0.00 | 0.00 | 49229.96 | 0.00 | 0.00 | 0.00 | 0.00 | 81.78 | 605.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1666.11 | -48250.72 |
CORE_RETAIL | 13-FEB-06:01 | 0.00 | 0.00 | 212413.48 | 0.00 | 0.00 | 0.00 | 0.00 | 344.55 | 1020.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1842.53 | 0.00 | -799.74 | -211136.09 |
POINT_OF_SALE | 12-FEB-07:11 | 0.00 | 0.00 | 29690.01 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 480.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2346.67 | 0.00 | -2168.45 | -25687.78 |
FRONT_RETAIL | 10-JAN-05:42 | 0.00 | 0.00 | 23987.96 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 96.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1677.42 | 0.00 | -719.69 | -21719.46 |
FRONT_ENTRY | 07-JAN-18:00 | 25273.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 445.45 | 0.00 | -347.42 | 0.00 | -25374.43 | 0.00 |
Total Facility | 12-FEB-08:61 | 4736.08 | 0.00 | 245433.56 | 0.00 | 0.00 | 0.00 | 0.00 | 493.85 | 1771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4706.43 | 0.00 | -7422.79 | -240305.85 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.7970 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.8232 | 0.1270 | 1.0000 | 0.2316 | 0.1270 | ||
PSZ-AC:2 | 6.6071 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 6.8518 | 0.2759 | 1.0000 | 1.8902 | 0.2759 | ||
PSZ-AC:3 | 1.0528 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0528 | 0.1692 | 1.0000 | 0.1781 | 0.1692 | ||
PSZ-AC:4 | 0.7903 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.7944 | 0.2242 | 1.0000 | 0.1781 | 0.2242 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.7970 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.7970 | 1.0000 | 1.0000 | 0.2316 | 0.1289 | ||
PSZ-AC:2 | 6.6071 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 6.6071 | 1.0000 | 1.0000 | 1.8902 | 0.2861 | ||
PSZ-AC:3 | 1.0528 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0528 | 1.0000 | 1.0000 | 0.1781 | 0.1692 | ||
PSZ-AC:4 | 0.7903 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.7903 | 1.0000 | 1.0000 | 0.1781 | 0.2254 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.7970 | 1.7970 | 1.7970 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 6.6071 | 6.6071 | 6.6071 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.0528 | 1.0528 | 1.0528 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.7903 | 0.7903 | 0.7903 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.7970 | 1.8232 | 1.7970 | 1.7970 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.6071 | 6.8518 | 6.6071 | 6.6071 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.0528 | 1.0528 | 1.0528 | 1.0528 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.7903 | 0.7944 | 0.7903 | 0.7903 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.7970 | 1.7970 | 1.7970 | 0.2316 | 0.2049 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 6.6071 | 6.6071 | 6.6071 | 1.8902 | 0.6950 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.0528 | 1.0528 | 1.0528 | 0.1781 | 0.3215 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.7903 | 0.7903 | 0.7903 | 0.1781 | 0.3215 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.7970 | 1.7970 | 1.7970 | 1.7970 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.6071 | 6.6071 | 6.6071 | 6.6071 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.0528 | 1.0528 | 1.0528 | 1.0528 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.7903 | 0.7903 | 0.7903 | 0.7903 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 171.51 | 188534.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 203.26 | 47099.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 232.07 | 20551.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 38.48 | 3371.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 194.30 | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 138.14 | 12307.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 91.29 | 5043.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 194.30 | 806.24 |
Natural Gas | 0.00 | 262.81 |
Additional | 0.00 | 0.00 |
Total | 194.30 | 1069.05 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 101.16 |
Space Heating | 0.00 |
Space Cooling | 88.61 |
Fans (All) | 60.22 |
Service Water Heating | 0.00 |
Receptacle Equipment | 84.70 |
Miscellaneous (All) | 351.46 |
Subtotal | 351.46 |
Natural Gas [MJ/m2] | |
Space Heating | 74.77 |
Service Water Heating | 39.80 |
Miscellaneous (All) | 114.56 |
Subtotal | 114.56 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 21.71 |
Space Heating | 16.04 |
Space Cooling | 19.01 |
Fans (All) | 12.92 |
Service Water Heating | 8.54 |
Receptacle Equipment | 18.17 |
Miscellaneous | 3.60 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 2872. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3001. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3501. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4552. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_SETBACK | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_FRONTENTRY_STD2013 | FRONT_ENTRY DUALSPSCHED | January | 16.00 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.774491E+11 |
February | 0.000 | 0.432745E+11 |
March | 0.000 | 0.603069E+10 |
April | 0.000 | 0.877079E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.709746E+09 |
November | 0.000 | 0.823018E+10 |
December | 0.000 | 0.349409E+11 |
Annual Sum or Average | 0.171512E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.774491E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.774491E+11 |
February | 0.000 | 0.432745E+11 |
March | 0.000 | 0.603069E+10 |
April | 0.000 | 0.877079E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.709746E+09 |
November | 0.000 | 0.823018E+10 |
December | 0.000 | 0.349409E+11 |
Annual Sum or Average | 0.171512E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.774491E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.774491E+11 |
February | 0.000 | 0.432745E+11 |
March | 0.000 | 0.603069E+10 |
April | 0.000 | 0.877079E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.709746E+09 |
November | 0.000 | 0.823018E+10 |
December | 0.000 | 0.349409E+11 |
Annual Sum or Average | 0.171512E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.774491E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.774491E+11 |
February | 0.000 | 0.432745E+11 |
March | 0.000 | 0.603069E+10 |
April | 0.000 | 0.877079E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.709746E+09 |
November | 0.000 | 0.823018E+10 |
December | 0.000 | 0.349409E+11 |
Annual Sum or Average | 0.171512E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.774491E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.774491E+11 |
February | 0.000 | 0.432745E+11 |
March | 0.000 | 0.603069E+10 |
April | 0.000 | 0.877079E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.709746E+09 |
November | 0.000 | 0.823018E+10 |
December | 0.000 | 0.349409E+11 |
Annual Sum or Average | 0.171512E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.774491E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.774491E+11 |
February | 0.000 | 0.432745E+11 |
March | 0.000 | 0.603069E+10 |
April | 0.000 | 0.877079E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.709746E+09 |
November | 0.000 | 0.823018E+10 |
December | 0.000 | 0.349409E+11 |
Annual Sum or Average | 0.171512E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.774491E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.774491E+11 |
February | 0.000 | 0.432745E+11 |
March | 0.000 | 0.603069E+10 |
April | 0.000 | 0.877079E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.709746E+09 |
November | 0.000 | 0.823018E+10 |
December | 0.000 | 0.349409E+11 |
Annual Sum or Average | 0.171512E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.774491E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.774491E+11 |
February | 0.000 | 0.432745E+11 |
March | 0.000 | 0.603069E+10 |
April | 0.000 | 0.877079E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.709746E+09 |
November | 0.000 | 0.823018E+10 |
December | 0.000 | 0.349409E+11 |
Annual Sum or Average | 0.171512E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.774491E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.774491E+11 |
February | 0.000 | 0.432745E+11 |
March | 0.000 | 0.603069E+10 |
April | 0.000 | 0.877079E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.709746E+09 |
November | 0.000 | 0.823018E+10 |
December | 0.000 | 0.349409E+11 |
Annual Sum or Average | 0.171512E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.774491E+11 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328631E+09 | 3163.39 | 21-JAN-12:00 | 6.70 | 3.53 | 0.168075E+10 | 2315.57 | 20-JAN-15:00 | 17.20 | 12.76 |
February | 0.732826E+09 | 4693.75 | 01-FEB-09:25 | -0.3 | -1.1 | 0.163180E+10 | 2451.25 | 22-FEB-15:39 | 16.27 | 13.43 |
March | 0.246802E+10 | 9315.12 | 30-MAR-20:45 | 23.98 | 16.89 | 0.206972E+10 | 2451.27 | 11-MAR-12:30 | 22.50 | 14.49 |
April | 0.399947E+10 | 7033.96 | 19-APR-14:50 | 26.52 | 17.57 | 0.210362E+10 | 2451.30 | 28-APR-14:50 | 25.50 | 15.63 |
May | 0.760684E+10 | 28205.95 | 04-MAY-20:30 | 20.60 | 16.40 | 0.222758E+10 | 2451.25 | 12-MAY-14:09 | 23.90 | 15.17 |
June | 0.125642E+11 | 37050.94 | 09-JUN-23:21 | 19.45 | 11.43 | 0.220147E+10 | 2451.25 | 09-JUN-14:09 | 29.90 | 18.88 |
July | 0.145219E+11 | 25768.38 | 07-JUL-21:23 | 30.00 | 22.75 | 0.218726E+10 | 2451.26 | 29-JUL-10:30 | 18.85 | 18.85 |
August | 0.155234E+11 | 25674.22 | 18-AUG-22:03 | 29.32 | 23.09 | 0.228101E+10 | 2451.23 | 26-AUG-10:50 | 28.62 | 21.04 |
September | 0.101813E+11 | 32944.51 | 14-SEP-20:31 | 20.57 | 13.90 | 0.215588E+10 | 2451.30 | 28-SEP-14:09 | 19.40 | 18.21 |
October | 0.513378E+10 | 18695.78 | 02-OCT-21:45 | 18.27 | 15.66 | 0.212214E+10 | 2451.24 | 21-OCT-10:30 | 17.50 | 12.22 |
November | 0.248928E+10 | 5157.27 | 04-NOV-16:00 | 21.10 | 18.17 | 0.189881E+10 | 2451.24 | 04-NOV-11:20 | 16.87 | 16.52 |
December | 0.130936E+10 | 4186.32 | 01-DEC-09:55 | 1.70 | -0.7 | 0.174482E+10 | 2451.21 | 12-DEC-15:00 | 22.20 | 15.96 |
Annual Sum or Average | 0.768591E+11 | 0.243048E+11 | ||||||||
Minimum of Months | 0.328631E+09 | 3163.39 | -0.3 | -1.1 | 0.163180E+10 | 2315.57 | 16.27 | 12.22 | ||
Maximum of Months | 0.155234E+11 | 37050.94 | 30.00 | 23.09 | 0.228101E+10 | 2451.30 | 29.90 | 21.04 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108035E+11 | 54092.14 | 26-JAN-07:05 | -5.1 | -7.0 | 0.711308E+10 | 10326.98 | 31-JAN-15:00 | 20.00 | 13.57 |
February | 0.128456E+11 | 54954.45 | 09-FEB-07:05 | -5.6 | -7.4 | 0.696008E+10 | 10327.27 | 22-FEB-15:39 | 16.27 | 13.43 |
March | 0.226235E+11 | 99948.64 | 31-MAR-06:03 | 17.30 | 16.12 | 0.883593E+10 | 10327.31 | 11-MAR-11:39 | 20.57 | 13.67 |
April | 0.268991E+11 | 152749.75 | 18-APR-06:03 | 13.30 | 12.05 | 0.889481E+10 | 10327.24 | 08-APR-10:09 | 20.87 | 14.37 |
May | 0.355281E+11 | 147409.70 | 17-MAY-06:02 | 16.78 | 13.16 | 0.938502E+10 | 10327.13 | 10-MAY-14:09 | 20.78 | 12.15 |
June | 0.432129E+11 | 168369.76 | 08-JUN-06:03 | 12.07 | 8.46 | 0.927658E+10 | 10326.99 | 19-JUN-14:09 | 31.70 | 23.32 |
July | 0.456963E+11 | 121471.08 | 03-JUL-06:02 | 18.68 | 16.73 | 0.921830E+10 | 10326.98 | 29-JUL-11:20 | 19.60 | 19.60 |
August | 0.474021E+11 | 120403.07 | 26-AUG-06:02 | 21.78 | 17.45 | 0.961348E+10 | 10327.04 | 26-AUG-11:20 | 29.47 | 21.46 |
September | 0.367321E+11 | 157967.97 | 14-SEP-06:03 | 12.30 | 10.99 | 0.908128E+10 | 10327.10 | 30-SEP-11:20 | 17.80 | 16.04 |
October | 0.290963E+11 | 119481.05 | 11-OCT-06:03 | 17.70 | 16.28 | 0.886826E+10 | 10327.22 | 04-OCT-14:09 | 19.68 | 12.49 |
November | 0.206034E+11 | 42781.15 | 04-NOV-06:05 | 16.10 | 15.06 | 0.797143E+10 | 10327.11 | 18-NOV-12:20 | 18.33 | 9.64 |
December | 0.160142E+11 | 53960.20 | 18-DEC-07:05 | -5.1 | -6.8 | 0.738504E+10 | 10327.15 | 11-DEC-15:00 | 21.10 | 15.90 |
Annual Sum or Average | 0.347457E+12 | 0.102603E+12 | ||||||||
Minimum of Months | 0.108035E+11 | 42781.15 | -5.6 | -7.4 | 0.696008E+10 | 10326.98 | 16.27 | 9.64 | ||
Maximum of Months | 0.474021E+11 | 168369.76 | 21.78 | 17.45 | 0.961348E+10 | 10327.31 | 31.70 | 23.32 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251839E+10 | 4135.14 | 26-JAN-12:10 | -0.9 | -4.3 | 0.717480E+09 | 973.15 | 31-JAN-15:00 | 20.00 | 13.57 |
February | 0.283330E+10 | 15555.88 | 26-FEB-19:21 | 20.00 | 10.70 | 0.692617E+09 | 973.15 | 22-FEB-15:30 | 17.20 | 13.31 |
March | 0.440445E+10 | 19291.62 | 13-MAR-22:01 | 20.32 | 14.51 | 0.871384E+09 | 973.13 | 11-MAR-11:20 | 19.43 | 13.14 |
April | 0.494004E+10 | 16097.86 | 15-APR-23:11 | 19.03 | 12.80 | 0.845126E+09 | 973.13 | 07-APR-14:09 | 22.57 | 13.55 |
May | 0.665305E+10 | 16932.25 | 14-MAY-19:11 | 22.07 | 13.60 | 0.884810E+09 | 973.13 | 23-MAY-14:20 | 24.27 | 20.59 |
June | 0.904784E+10 | 20310.64 | 09-JUN-21:31 | 22.07 | 12.90 | 0.873872E+09 | 973.13 | 14-JUN-14:09 | 30.10 | 22.72 |
July | 0.101954E+11 | 15813.07 | 07-JUL-21:23 | 30.00 | 22.75 | 0.868297E+09 | 973.13 | 01-JUL-15:09 | 28.95 | 23.37 |
August | 0.114954E+11 | 16153.81 | 18-AUG-22:03 | 29.32 | 23.09 | 0.905508E+09 | 973.11 | 26-AUG-10:09 | 27.48 | 20.44 |
September | 0.897049E+10 | 20215.80 | 14-SEP-20:41 | 20.28 | 13.79 | 0.855847E+09 | 973.13 | 30-SEP-13:00 | 17.80 | 16.04 |
October | 0.693935E+10 | 16948.02 | 11-OCT-22:02 | 14.40 | 8.96 | 0.855025E+09 | 973.14 | 05-OCT-14:00 | 20.60 | 15.45 |
November | 0.480945E+10 | 14497.08 | 08-NOV-21:15 | 14.63 | 7.27 | 0.804849E+09 | 973.13 | 04-NOV-13:39 | 17.43 | 17.12 |
December | 0.335354E+10 | 11811.55 | 12-DEC-21:25 | 18.30 | 14.61 | 0.784893E+09 | 973.15 | 13-DEC-15:00 | 17.20 | 16.88 |
Annual Sum or Average | 0.761607E+11 | 0.995971E+10 | ||||||||
Minimum of Months | 0.251839E+10 | 4135.14 | -0.9 | -4.3 | 0.692617E+09 | 973.11 | 17.20 | 13.14 | ||
Maximum of Months | 0.114954E+11 | 20310.64 | 30.00 | 23.09 | 0.905508E+09 | 973.15 | 30.10 | 23.37 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.965753E+09 | 3097.98 | 15-JAN-11:03 | 0.78 | -2.6 | 0.685130E+09 | 973.10 | 30-JAN-15:00 | 16.70 | 10.50 |
February | 0.117915E+10 | 4132.49 | 28-FEB-15:40 | 23.87 | 12.90 | 0.664505E+09 | 973.11 | 22-FEB-15:30 | 17.20 | 13.31 |
March | 0.210351E+10 | 13987.26 | 30-MAR-23:01 | 21.42 | 15.72 | 0.840222E+09 | 973.13 | 11-MAR-14:09 | 25.18 | 16.16 |
April | 0.247232E+10 | 15537.45 | 17-APR-21:11 | 20.00 | 14.02 | 0.831258E+09 | 973.13 | 18-APR-14:00 | 25.60 | 16.91 |
May | 0.371413E+10 | 14887.45 | 14-MAY-18:21 | 24.20 | 14.41 | 0.882338E+09 | 973.13 | 12-MAY-14:09 | 23.90 | 15.17 |
June | 0.589887E+10 | 17201.54 | 10-JUN-21:21 | 21.65 | 12.05 | 0.873688E+09 | 973.14 | 17-JUN-15:00 | 25.60 | 22.49 |
July | 0.698796E+10 | 12278.59 | 07-JUL-21:23 | 30.00 | 22.75 | 0.868300E+09 | 973.12 | 29-JUL-11:09 | 19.50 | 19.50 |
August | 0.811521E+10 | 12564.72 | 18-AUG-22:43 | 28.98 | 23.26 | 0.905526E+09 | 973.12 | 26-AUG-10:20 | 27.77 | 20.59 |
September | 0.586501E+10 | 15590.85 | 14-SEP-20:51 | 20.00 | 13.68 | 0.855339E+09 | 973.14 | 28-SEP-14:20 | 19.40 | 18.15 |
October | 0.423648E+10 | 20448.76 | 11-OCT-23:31 | 13.67 | 8.36 | 0.839464E+09 | 973.12 | 18-OCT-14:00 | 25.00 | 23.04 |
November | 0.256749E+10 | 5403.50 | 06-NOV-15:10 | 20.60 | 10.46 | 0.778156E+09 | 973.10 | 04-NOV-11:20 | 16.87 | 16.52 |
December | 0.158155E+10 | 3603.36 | 12-DEC-14:00 | 22.80 | 17.06 | 0.737187E+09 | 973.11 | 11-DEC-15:00 | 21.10 | 15.90 |
Annual Sum or Average | 0.456874E+11 | 0.976111E+10 | ||||||||
Minimum of Months | 0.965753E+09 | 3097.98 | 0.78 | -2.6 | 0.664505E+09 | 973.10 | 16.70 | 10.50 | ||
Maximum of Months | 0.811521E+10 | 20448.76 | 30.00 | 23.26 | 0.905526E+09 | 973.14 | 27.77 | 23.04 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 | 18.59 | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.28 | 21.38 | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 | 21.87 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 | 18.45 | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.59 | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.59 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.80 | 1.51 | 0.00 | 0.00 | 1.80 | 1.51 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 21.87 | 0.00 | 0.00 | 25.13 | 21.87 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.632881E+10 | 49229.74 | 10-JAN-05:42 | -4.2 |
February | 0.375714E+10 | 48838.83 | 13-FEB-05:11 | -5.2 |
March | 0.553684E+09 | 47833.39 | 23-MAR-04:01 | 5.18 |
April | 0.118291E+09 | 44725.40 | 07-APR-04:02 | 3.80 |
May | 35293203.69 | 1106.36 | 19-MAY-05:05 | 16.60 |
June | 9448481.46 | 1317.94 | 26-JUN-05:05 | 23.30 |
July | 3842184.71 | 1337.26 | 14-JUL-05:05 | 23.30 |
August | 6091908.99 | 1374.38 | 02-AUG-05:05 | 23.40 |
September | 12615958.34 | 1802.52 | 13-SEP-05:05 | 18.72 |
October | 74797614.48 | 15827.53 | 31-OCT-05:03 | 8.30 |
November | 0.587469E+09 | 48018.98 | 22-NOV-05:01 | -2.9 |
December | 0.287414E+10 | 48602.22 | 03-DEC-07:42 | -3.8 |
Annual Sum or Average | 0.143616E+11 | |||
Minimum of Months | 3842184.71 | 1106.36 | -5.2 | |
Maximum of Months | 0.632881E+10 | 49229.74 | 23.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.440538E+10 | 212275.30 | 09-JAN-06:01 | -2.4 |
February | 0.238598E+10 | 212413.47 | 13-FEB-06:01 | -5.6 |
March | 0.494427E+09 | 15761.52 | 25-MAR-06:10 | 4.60 |
April | 0.462936E+09 | 4553.99 | 02-APR-07:12 | 12.97 |
May | 0.469408E+09 | 4517.02 | 14-MAY-07:13 | 14.07 |
June | 0.336072E+09 | 5943.51 | 25-JUN-08:06 | 23.87 |
July | 0.222892E+09 | 10364.70 | 16-JUL-08:20 | 26.33 |
August | 0.180970E+09 | 8015.87 | 06-AUG-08:20 | 25.17 |
September | 0.421509E+09 | 5652.99 | 17-SEP-08:20 | 23.87 |
October | 0.478931E+09 | 4569.00 | 08-OCT-07:12 | 11.83 |
November | 0.570632E+09 | 44869.27 | 22-NOV-07:05 | -3.2 |
December | 0.159462E+10 | 161069.31 | 04-DEC-06:03 | -2.9 |
Annual Sum or Average | 0.120238E+11 | |||
Minimum of Months | 0.180970E+09 | 4517.02 | -5.6 | |
Maximum of Months | 0.440538E+10 | 212413.47 | 26.33 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119025E+10 | 29496.70 | 10-JAN-05:42 | -4.2 |
February | 0.701292E+09 | 29690.03 | 12-FEB-07:11 | -12.6 |
March | 82352765.77 | 28961.25 | 23-MAR-04:01 | 5.18 |
April | 35508323.26 | 5838.08 | 06-APR-04:40 | 0.37 |
May | 14900213.48 | 652.36 | 18-MAY-05:05 | 16.52 |
June | 1745802.65 | 746.75 | 16-JUN-05:05 | 20.68 |
July | 1331555.56 | 780.63 | 26-JUL-05:05 | 21.78 |
August | 227140.34 | 521.21 | 20-AUG-07:10 | 23.98 |
September | 4672511.35 | 740.36 | 05-SEP-05:05 | 21.70 |
October | 19750654.87 | 2511.19 | 31-OCT-05:03 | 8.30 |
November | 87293559.65 | 29117.15 | 22-NOV-05:01 | -2.9 |
December | 0.450226E+09 | 29242.59 | 03-DEC-07:01 | -3.4 |
Annual Sum or Average | 0.258955E+10 | |||
Minimum of Months | 227140.34 | 521.21 | -12.6 | |
Maximum of Months | 0.119025E+10 | 29690.03 | 23.98 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.209966E+10 | 23987.89 | 10-JAN-05:42 | -4.2 |
February | 0.126233E+10 | 23875.74 | 12-FEB-07:11 | -12.6 |
March | 0.251250E+09 | 23345.12 | 23-MAR-04:01 | 5.18 |
April | 0.115599E+09 | 22933.99 | 06-APR-04:02 | 0.92 |
May | 43431971.76 | 1047.98 | 19-MAY-05:05 | 16.60 |
June | 9824880.01 | 974.16 | 04-JUN-07:05 | 20.37 |
July | 2023824.80 | 938.76 | 03-JUL-05:10 | 17.88 |
August | 408115.30 | 554.04 | 20-AUG-07:10 | 23.98 |
September | 7805607.68 | 999.96 | 24-SEP-07:03 | 17.85 |
October | 71032950.30 | 17261.43 | 31-OCT-04:03 | 8.80 |
November | 0.206622E+09 | 23437.76 | 22-NOV-05:01 | -2.9 |
December | 0.922468E+09 | 23531.36 | 17-DEC-07:42 | -2.1 |
Annual Sum or Average | 0.499246E+10 | |||
Minimum of Months | 408115.30 | 554.04 | -12.6 | |
Maximum of Months | 0.209966E+10 | 23987.89 | 23.98 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.651181E+10 | 25274.62 | 07-JAN-18:00 | -5.0 |
February | 0.377202E+10 | 25213.80 | 11-FEB-18:00 | -5.0 |
March | 0.373340E+09 | 12957.51 | 22-MAR-11:10 | 4.40 |
April | 18265815.30 | 2021.27 | 26-APR-07:10 | 4.97 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 7813964.69 | 2637.49 | 26-OCT-07:07 | 2.57 |
November | 0.698445E+09 | 20664.95 | 21-NOV-16:51 | 7.20 |
December | 0.202880E+10 | 17029.75 | 17-DEC-18:00 | 1.10 |
Annual Sum or Average | 0.134105E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.651181E+10 | 25274.62 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.149153E+10 | 1249.73 | 02-JAN-09:09 | 0.419292E+10 | 2751.42 | 02-JAN-09:09 |
February | 0.135698E+10 | 1249.73 | 01-FEB-09:09 | 0.380401E+10 | 2751.42 | 01-FEB-09:09 |
March | 0.154631E+10 | 1249.73 | 01-MAR-09:09 | 0.429860E+10 | 2751.42 | 01-MAR-09:09 |
April | 0.146057E+10 | 1249.73 | 01-APR-09:09 | 0.408483E+10 | 2751.42 | 01-APR-09:09 |
May | 0.151892E+10 | 1249.73 | 01-MAY-08:09 | 0.424576E+10 | 2751.42 | 01-MAY-08:09 |
June | 0.149233E+10 | 1249.73 | 01-JUN-08:09 | 0.415135E+10 | 2751.42 | 01-JUN-08:09 |
July | 0.148716E+10 | 1249.73 | 01-JUL-09:09 | 0.417924E+10 | 2751.42 | 01-JUL-09:09 |
August | 0.154631E+10 | 1249.73 | 01-AUG-08:09 | 0.429860E+10 | 2751.42 | 01-AUG-08:09 |
September | 0.146057E+10 | 1249.73 | 01-SEP-08:09 | 0.408483E+10 | 2751.42 | 01-SEP-08:09 |
October | 0.149153E+10 | 1249.73 | 02-OCT-08:09 | 0.419292E+10 | 2751.42 | 02-OCT-08:09 |
November | 0.144192E+10 | 1249.73 | 01-NOV-08:09 | 0.405935E+10 | 2751.42 | 01-NOV-08:09 |
December | 0.148716E+10 | 1249.73 | 01-DEC-09:09 | 0.417924E+10 | 2751.42 | 01-DEC-09:09 |
Annual Sum or Average | 0.177813E+11 | 0.497716E+11 | ||||
Minimum of Months | 0.135698E+10 | 1249.73 | 0.380401E+10 | 2751.42 | ||
Maximum of Months | 0.154631E+10 | 1249.73 | 0.429860E+10 | 2751.42 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.163692E+11 | 16279.94 | 02-JAN-17:40 | 0.707031E+10 | 4639.58 | 02-JAN-09:09 |
February | 0.145928E+11 | 16258.90 | 10-FEB-17:00 | 0.641452E+10 | 4639.58 | 01-FEB-09:09 |
March | 0.152399E+11 | 15771.86 | 03-MAR-17:00 | 0.724851E+10 | 4639.58 | 01-MAR-09:09 |
April | 0.132521E+11 | 15020.93 | 08-APR-16:00 | 0.688804E+10 | 4639.58 | 01-APR-09:09 |
May | 0.134683E+11 | 14564.99 | 26-MAY-16:00 | 0.715941E+10 | 4639.58 | 01-MAY-08:09 |
June | 0.130812E+11 | 14319.12 | 08-JUN-16:00 | 0.700021E+10 | 4639.58 | 01-JUN-08:09 |
July | 0.129196E+11 | 14542.41 | 27-JUL-08:09 | 0.704724E+10 | 4639.58 | 01-JUL-09:09 |
August | 0.133690E+11 | 14493.69 | 24-AUG-08:09 | 0.724851E+10 | 4639.58 | 01-AUG-08:09 |
September | 0.134984E+11 | 15359.16 | 30-SEP-16:00 | 0.688804E+10 | 4639.58 | 01-SEP-08:09 |
October | 0.157397E+11 | 16115.70 | 30-OCT-16:30 | 0.707031E+10 | 4639.58 | 02-OCT-08:09 |
November | 0.154215E+11 | 16279.94 | 06-NOV-17:40 | 0.684509E+10 | 4639.58 | 01-NOV-08:09 |
December | 0.161606E+11 | 16279.94 | 01-DEC-17:30 | 0.704724E+10 | 4639.58 | 01-DEC-09:09 |
Annual Sum or Average | 0.173112E+12 | 0.839274E+11 | ||||
Minimum of Months | 0.129196E+11 | 14319.12 | 0.641452E+10 | 4639.58 | ||
Maximum of Months | 0.163692E+11 | 16279.94 | 0.724851E+10 | 4639.58 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.174880E+10 | 1534.02 | 02-JAN-09:09 | 0.443872E+10 | 2912.71 | 02-JAN-09:09 |
February | 0.159209E+10 | 1534.02 | 01-FEB-09:09 | 0.402701E+10 | 2912.71 | 01-FEB-09:09 |
March | 0.181792E+10 | 1534.02 | 01-MAR-09:09 | 0.455059E+10 | 2912.71 | 01-MAR-09:09 |
April | 0.171453E+10 | 1534.02 | 01-APR-09:09 | 0.432429E+10 | 2912.71 | 01-APR-09:09 |
May | 0.178336E+10 | 1534.02 | 01-MAY-08:09 | 0.449465E+10 | 2912.71 | 01-MAY-08:09 |
June | 0.175416E+10 | 1534.02 | 01-JUN-08:09 | 0.439471E+10 | 2912.71 | 01-JUN-08:09 |
July | 0.174372E+10 | 1534.02 | 01-JUL-09:09 | 0.442423E+10 | 2912.71 | 01-JUL-09:09 |
August | 0.181792E+10 | 1534.02 | 01-AUG-08:09 | 0.455059E+10 | 2912.71 | 01-AUG-08:09 |
September | 0.171453E+10 | 1534.02 | 01-SEP-08:09 | 0.432429E+10 | 2912.71 | 01-SEP-08:09 |
October | 0.174880E+10 | 1534.02 | 02-OCT-08:09 | 0.443872E+10 | 2912.71 | 02-OCT-08:09 |
November | 0.169012E+10 | 1534.02 | 01-NOV-08:09 | 0.429732E+10 | 2912.71 | 01-NOV-08:09 |
December | 0.174372E+10 | 1534.02 | 01-DEC-09:09 | 0.442423E+10 | 2912.71 | 01-DEC-09:09 |
Annual Sum or Average | 0.208697E+11 | 0.526893E+11 | ||||
Minimum of Months | 0.159209E+10 | 1534.02 | 0.402701E+10 | 2912.71 | ||
Maximum of Months | 0.181792E+10 | 1534.02 | 0.455059E+10 | 2912.71 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.169457E+10 | 1485.24 | 02-JAN-09:09 | 0.666220E+09 | 437.18 | 02-JAN-09:09 |
February | 0.154270E+10 | 1485.24 | 01-FEB-09:09 | 0.604426E+09 | 437.18 | 01-FEB-09:09 |
March | 0.176147E+10 | 1485.24 | 01-MAR-09:09 | 0.683011E+09 | 437.18 | 01-MAR-09:09 |
April | 0.166132E+10 | 1485.24 | 01-APR-09:09 | 0.649045E+09 | 437.18 | 01-APR-09:09 |
May | 0.172802E+10 | 1485.24 | 01-MAY-08:09 | 0.674616E+09 | 437.18 | 01-MAY-08:09 |
June | 0.169970E+10 | 1485.24 | 01-JUN-08:09 | 0.659615E+09 | 437.18 | 01-JUN-08:09 |
July | 0.168964E+10 | 1485.24 | 01-JUL-09:09 | 0.664046E+09 | 437.18 | 01-JUL-09:09 |
August | 0.176147E+10 | 1485.24 | 01-AUG-08:09 | 0.683011E+09 | 437.18 | 01-AUG-08:09 |
September | 0.166132E+10 | 1485.24 | 01-SEP-08:09 | 0.649045E+09 | 437.18 | 01-SEP-08:09 |
October | 0.169457E+10 | 1485.24 | 02-OCT-08:09 | 0.666220E+09 | 437.18 | 02-OCT-08:09 |
November | 0.163772E+10 | 1485.24 | 01-NOV-08:09 | 0.644998E+09 | 437.18 | 01-NOV-08:09 |
December | 0.168964E+10 | 1485.24 | 01-DEC-09:09 | 0.664046E+09 | 437.18 | 01-DEC-09:09 |
Annual Sum or Average | 0.202221E+11 | 0.790830E+10 | ||||
Minimum of Months | 0.154270E+10 | 1485.24 | 0.604426E+09 | 437.18 | ||
Maximum of Months | 0.176147E+10 | 1485.24 | 0.683011E+09 | 437.18 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 6919213.84 | 2.58 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 6249612.50 | 2.58 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 6919213.84 | 2.58 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 6696013.39 | 2.58 | 01-APR-00:10 | 0.00 | 0.00 |
May | 6919213.84 | 2.58 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 6696013.39 | 2.58 | 01-JUN-00:10 | 0.00 | 0.00 |
July | 6919213.84 | 2.58 | 01-JUL-00:10 | 0.00 | 0.00 |
August | 6919213.84 | 2.58 | 01-AUG-00:10 | 0.00 | 0.00 |
September | 6696013.39 | 2.58 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 6919213.84 | 2.58 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 6696013.39 | 2.58 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 6919213.84 | 2.58 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 81468162.94 | ||||
Minimum of Months | 6249612.50 | 2.58 | 0.00 | 0.00 | |
Maximum of Months | 6919213.84 | 2.58 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.149153E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219529E+10 |
February | 0.479114E+10 | 0.135698E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 670403.78 | 0.186004E+10 |
March | 0.548013E+10 | 0.154631E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4832063.84 | 0.119115E+10 |
April | 0.518069E+10 | 0.146057E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12475390.82 | 0.757117E+09 |
May | 0.536353E+10 | 0.151892E+10 | 0.424576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38522070.91 | 0.484494E+09 |
June | 0.528933E+10 | 0.149233E+10 | 0.415135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158246E+09 | 0.192444E+09 |
July | 0.525489E+10 | 0.148716E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181468E+09 | 0.108755E+09 |
August | 0.548013E+10 | 0.154631E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190858E+09 | 43784106.90 |
September | 0.518069E+10 | 0.146057E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49515133.98 | 0.237902E+09 |
October | 0.524694E+10 | 0.149153E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8495192.67 | 0.912075E+09 |
November | 0.504819E+10 | 0.144192E+10 | 0.405935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55539.88 | 0.127828E+10 |
December | 0.525489E+10 | 0.148716E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194266E+10 |
Annual Sum or Average | 0.628175E+11 | 0.177813E+11 | 0.497716E+11 | 0.645138E+09 | 0.112040E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.135698E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43784106.90 |
Maximum of Months | 0.548013E+10 | 0.154631E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190858E+09 | 0.219529E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.163692E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190152E+10 |
February | 0.201852E+11 | 0.145928E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 398132.25 | 0.163981E+10 |
March | 0.230879E+11 | 0.152399E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3939680.33 | 0.108676E+10 |
April | 0.218263E+11 | 0.132521E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10176413.40 | 0.684581E+09 |
May | 0.225967E+11 | 0.134683E+11 | 0.715941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30729196.17 | 0.443191E+09 |
June | 0.222841E+11 | 0.130812E+11 | 0.700021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118045E+09 | 0.213538E+09 |
July | 0.221389E+11 | 0.129196E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125128E+09 | 0.133761E+09 |
August | 0.230879E+11 | 0.133690E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129676E+09 | 84927843.97 |
September | 0.218263E+11 | 0.134984E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36915752.08 | 0.229174E+09 |
October | 0.221054E+11 | 0.157397E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6952850.44 | 0.795367E+09 |
November | 0.212681E+11 | 0.154215E+11 | 0.684509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44075.14 | 0.111589E+10 |
December | 0.221389E+11 | 0.161606E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169274E+10 |
Annual Sum or Average | 0.264651E+12 | 0.173112E+12 | 0.839274E+11 | 0.462006E+09 | 0.100213E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.129196E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84927843.97 |
Maximum of Months | 0.230879E+11 | 0.163692E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129676E+09 | 0.190152E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.174880E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100380E+10 |
February | 0.190200E+10 | 0.159209E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 210901.36 | 0.862686E+09 |
March | 0.217552E+10 | 0.181792E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2102054.99 | 0.579352E+09 |
April | 0.205665E+10 | 0.171453E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5390090.31 | 0.348382E+09 |
May | 0.212923E+10 | 0.178336E+10 | 0.449465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16709939.43 | 0.213129E+09 |
June | 0.209978E+10 | 0.175416E+10 | 0.439471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68561574.59 | 82417744.89 |
July | 0.208610E+10 | 0.174372E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78311198.67 | 46543398.95 |
August | 0.217552E+10 | 0.181792E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82206045.91 | 18576869.37 |
September | 0.205665E+10 | 0.171453E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21433358.96 | 0.102656E+09 |
October | 0.208295E+10 | 0.174880E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3680450.69 | 0.415215E+09 |
November | 0.200405E+10 | 0.169012E+10 | 0.429732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23379.36 | 0.614479E+09 |
December | 0.208610E+10 | 0.174372E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908513E+09 |
Annual Sum or Average | 0.249375E+11 | 0.208697E+11 | 0.526893E+11 | 0.278629E+09 | 0.519575E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.159209E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18576869.37 |
Maximum of Months | 0.217552E+10 | 0.181792E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82206045.91 | 0.100380E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.169457E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968822E+09 |
February | 0.190200E+10 | 0.154270E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 210818.07 | 0.826664E+09 |
March | 0.217552E+10 | 0.176147E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2101439.22 | 0.541508E+09 |
April | 0.205665E+10 | 0.166132E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5395269.59 | 0.326527E+09 |
May | 0.212923E+10 | 0.172802E+10 | 0.674616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16700023.76 | 0.204914E+09 |
June | 0.209978E+10 | 0.169970E+10 | 0.659615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68655732.32 | 82997415.56 |
July | 0.208610E+10 | 0.168964E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78558915.31 | 46920984.57 |
August | 0.217552E+10 | 0.176147E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82534025.82 | 18785792.04 |
September | 0.205665E+10 | 0.166132E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21467277.94 | 0.101522E+09 |
October | 0.208295E+10 | 0.169457E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3680104.85 | 0.400201E+09 |
November | 0.200405E+10 | 0.163772E+10 | 0.644998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23336.54 | 0.583033E+09 |
December | 0.208610E+10 | 0.168964E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866119E+09 |
Annual Sum or Average | 0.249375E+11 | 0.202221E+11 | 0.790830E+10 | 0.279327E+09 | 0.496801E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.154270E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18785792.04 |
Maximum of Months | 0.217552E+10 | 0.176147E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82534025.82 | 0.968822E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755501E+10 |
February | 0.00 | 6249612.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3160.78 | 0.460969E+10 |
March | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 910865.28 | 0.136666E+10 |
April | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26180080.74 | 0.514002E+09 |
May | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91650792.67 | 0.254065E+09 |
June | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319055E+09 | 84951235.75 |
July | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378537E+09 | 96735461.07 |
August | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289876E+09 | 66977703.56 |
September | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46823864.94 | 0.264542E+09 |
October | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351826.13 | 0.955838E+09 |
November | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44517.41 | 0.186281E+10 |
December | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340626E+10 |
Annual Sum or Average | 0.00 | 81468162.94 | 0.115343E+10 | 0.210376E+11 | |||||
Minimum of Months | 0.00 | 6249612.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66977703.56 |
Maximum of Months | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378537E+09 | 0.755501E+10 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 1249.73 | 02-JAN-09:09 | 2751.42 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4714.42 | 07-JAN-05:10 |
February | 5888.82 | 01-FEB-15:09 | 1249.73 | 01-FEB-09:09 | 2751.42 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.82 | 28-FEB-15:00 | 5497.21 | 12-FEB-00:55 |
March | 5888.82 | 01-MAR-15:09 | 1249.73 | 01-MAR-09:09 | 2751.42 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 135.20 | 30-MAR-16:00 | 3553.96 | 22-MAR-04:47 |
April | 5888.82 | 01-APR-10:09 | 1249.73 | 01-APR-09:09 | 2751.42 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.08 | 04-APR-15:00 | 1727.38 | 05-APR-05:00 |
May | 5888.82 | 01-MAY-14:09 | 1249.73 | 01-MAY-08:09 | 2751.42 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 332.80 | 29-MAY-18:05 | 1472.55 | 10-MAY-04:00 |
June | 5888.82 | 01-JUN-14:09 | 1249.73 | 01-JUN-08:09 | 2751.42 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 518.61 | 11-JUN-18:03 | 997.03 | 07-JUN-03:00 |
July | 5888.82 | 01-JUL-10:09 | 1249.73 | 01-JUL-09:09 | 2751.42 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 581.96 | 09-JUL-19:30 | 735.54 | 28-JUL-23:55 |
August | 5888.82 | 01-AUG-14:09 | 1249.73 | 01-AUG-08:09 | 2751.42 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 717.91 | 18-AUG-20:03 | 458.09 | 25-AUG-04:55 |
September | 5888.82 | 01-SEP-14:09 | 1249.73 | 01-SEP-08:09 | 2751.42 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 281.07 | 03-SEP-18:05 | 1041.96 | 29-SEP-05:00 |
October | 5888.82 | 02-OCT-14:09 | 1249.73 | 02-OCT-08:09 | 2751.42 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.94 | 11-OCT-14:00 | 1972.13 | 28-OCT-04:00 |
November | 5888.82 | 01-NOV-14:09 | 1249.73 | 01-NOV-08:09 | 2751.42 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.13 | 19-NOV-14:55 | 3125.09 | 30-NOV-21:05 |
December | 5888.82 | 01-DEC-15:09 | 1249.73 | 01-DEC-09:09 | 2751.42 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4954.13 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 1249.73 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.09 | |||||
Maximum of Months | 5888.82 | 1249.73 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 717.91 | 5497.21 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 16279.94 | 02-JAN-17:40 | 4639.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3486.62 | 07-JAN-04:53 |
February | 24809.68 | 01-FEB-15:09 | 16258.90 | 10-FEB-17:00 | 4639.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.33 | 28-FEB-15:00 | 4961.38 | 12-FEB-00:55 |
March | 24809.68 | 01-MAR-15:09 | 15771.86 | 03-MAR-17:00 | 4639.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.67 | 30-MAR-16:00 | 2949.45 | 22-MAR-03:00 |
April | 24809.68 | 01-APR-10:09 | 15020.93 | 08-APR-16:00 | 4639.58 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.02 | 04-APR-15:00 | 1607.75 | 05-APR-05:00 |
May | 24809.68 | 01-MAY-14:09 | 14564.99 | 26-MAY-16:00 | 4639.58 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 272.59 | 29-MAY-18:05 | 1321.29 | 10-MAY-04:00 |
June | 24809.68 | 01-JUN-14:09 | 14319.12 | 08-JUN-16:00 | 4639.58 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 425.25 | 11-JUN-18:03 | 927.53 | 07-JUN-03:00 |
July | 24809.68 | 01-JUL-10:09 | 14542.41 | 27-JUL-08:09 | 4639.58 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 426.87 | 09-JUL-18:03 | 666.88 | 28-JUL-22:00 |
August | 24809.68 | 01-AUG-14:09 | 14493.69 | 24-AUG-08:09 | 4639.58 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 590.26 | 18-AUG-20:03 | 430.55 | 25-AUG-04:55 |
September | 24809.68 | 01-SEP-14:09 | 15359.16 | 30-SEP-16:00 | 4639.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 231.92 | 03-SEP-18:05 | 917.28 | 29-SEP-05:00 |
October | 24809.68 | 02-OCT-14:09 | 16115.70 | 30-OCT-16:30 | 4639.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.54 | 11-OCT-14:00 | 1835.79 | 28-OCT-04:00 |
November | 24809.68 | 01-NOV-14:09 | 16279.94 | 06-NOV-17:40 | 4639.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | 19-NOV-15:00 | 2737.39 | 07-NOV-02:00 |
December | 24809.68 | 01-DEC-15:09 | 16279.94 | 01-DEC-17:30 | 4639.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4630.49 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 14319.12 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.55 | |||||
Maximum of Months | 24809.68 | 16279.94 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 590.26 | 4961.38 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1534.02 | 02-JAN-09:09 | 2912.71 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2068.94 | 07-JAN-05:05 |
February | 2337.76 | 01-FEB-15:09 | 1534.02 | 01-FEB-09:09 | 2912.71 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 | 28-FEB-15:00 | 2394.71 | 12-FEB-00:55 |
March | 2337.76 | 01-MAR-15:09 | 1534.02 | 01-MAR-09:09 | 2912.71 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.59 | 30-MAR-16:00 | 1530.21 | 22-MAR-04:04 |
April | 2337.76 | 01-APR-10:09 | 1534.02 | 01-APR-09:09 | 2912.71 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 | 04-APR-15:00 | 779.39 | 05-APR-05:00 |
May | 2337.76 | 01-MAY-14:09 | 1534.02 | 01-MAY-08:09 | 2912.71 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 139.61 | 29-MAY-18:05 | 650.43 | 10-MAY-04:00 |
June | 2337.76 | 01-JUN-14:09 | 1534.02 | 01-JUN-08:09 | 2912.71 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 227.85 | 11-JUN-18:10 | 439.89 | 07-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 1534.02 | 01-JUL-09:09 | 2912.71 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 253.46 | 09-JUL-18:47 | 328.20 | 28-JUL-22:00 |
August | 2337.76 | 01-AUG-14:09 | 1534.02 | 01-AUG-08:09 | 2912.71 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 318.65 | 18-AUG-20:10 | 187.06 | 25-AUG-04:45 |
September | 2337.76 | 01-SEP-14:09 | 1534.02 | 01-SEP-08:09 | 2912.71 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 127.57 | 03-SEP-18:20 | 456.80 | 29-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 1534.02 | 02-OCT-08:09 | 2912.71 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.35 | 11-OCT-14:00 | 965.46 | 28-OCT-04:00 |
November | 2337.76 | 01-NOV-14:09 | 1534.02 | 01-NOV-08:09 | 2912.71 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.65 | 19-NOV-15:00 | 1438.19 | 07-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 1534.02 | 01-DEC-09:09 | 2912.71 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2228.08 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1534.02 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.06 | |||||
Maximum of Months | 2337.76 | 1534.02 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 318.65 | 2394.71 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1485.24 | 02-JAN-09:09 | 437.18 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2042.90 | 07-JAN-05:10 |
February | 2337.76 | 01-FEB-15:09 | 1485.24 | 01-FEB-09:09 | 437.18 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.06 | 28-FEB-15:00 | 2341.29 | 12-FEB-00:55 |
March | 2337.76 | 01-MAR-15:09 | 1485.24 | 01-MAR-09:09 | 437.18 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.58 | 30-MAR-16:00 | 1541.13 | 22-MAR-04:47 |
April | 2337.76 | 01-APR-10:09 | 1485.24 | 01-APR-09:09 | 437.18 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.53 | 04-APR-15:00 | 722.86 | 05-APR-05:00 |
May | 2337.76 | 01-MAY-14:09 | 1485.24 | 01-MAY-08:09 | 437.18 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 141.92 | 29-MAY-18:05 | 618.46 | 10-MAY-04:00 |
June | 2337.76 | 01-JUN-14:09 | 1485.24 | 01-JUN-08:09 | 437.18 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 228.15 | 11-JUN-18:10 | 435.72 | 07-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 1485.24 | 01-JUL-09:09 | 437.18 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 252.13 | 09-JUL-19:30 | 317.36 | 28-JUL-21:55 |
August | 2337.76 | 01-AUG-14:09 | 1485.24 | 01-AUG-08:09 | 437.18 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 318.56 | 18-AUG-20:10 | 177.49 | 25-AUG-05:00 |
September | 2337.76 | 01-SEP-14:09 | 1485.24 | 01-SEP-08:09 | 437.18 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 126.41 | 03-SEP-18:20 | 430.41 | 29-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 1485.24 | 02-OCT-08:09 | 437.18 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.34 | 11-OCT-14:00 | 907.83 | 28-OCT-04:00 |
November | 2337.76 | 01-NOV-14:09 | 1485.24 | 01-NOV-08:09 | 437.18 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 | 19-NOV-15:00 | 1378.98 | 07-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 1485.24 | 01-DEC-09:09 | 437.18 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2132.51 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1485.24 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.49 | |||||
Maximum of Months | 2337.76 | 1485.24 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 318.56 | 2341.29 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 25397.65 | 07-JAN-17:00 |
February | 0.00 | 01-FEB-00:10 | 2.58 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 | 01-FEB-18:53 | 25582.19 | 11-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 2.58 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.86 | 28-MAR-17:00 | 13412.95 | 22-MAR-11:10 |
April | 0.00 | 01-APR-00:10 | 2.58 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.87 | 16-APR-11:03 | 6568.26 | 05-APR-11:01 |
May | 0.00 | 01-MAY-00:10 | 2.58 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 985.09 | 30-MAY-11:02 | 2194.01 | 24-MAY-11:02 |
June | 0.00 | 01-JUN-00:10 | 2.58 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.47 | 06-JUN-11:02 | 1341.67 | 07-JUN-07:01 |
July | 0.00 | 01-JUL-00:10 | 2.58 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2662.92 | 08-JUL-11:01 | 2039.83 | 28-JUL-11:02 |
August | 0.00 | 01-AUG-00:10 | 2.58 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2180.45 | 01-AUG-11:01 | 1138.63 | 08-AUG-16:53 |
September | 0.00 | 01-SEP-00:10 | 2.58 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.84 | 09-SEP-11:03 | 2091.98 | 30-SEP-11:02 |
October | 0.00 | 01-OCT-00:10 | 2.58 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.49 | 10-OCT-16:00 | 5806.77 | 25-OCT-11:01 |
November | 0.00 | 01-NOV-00:10 | 2.58 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.42 | 19-NOV-14:55 | 14621.40 | 20-NOV-12:03 |
December | 0.00 | 01-DEC-00:10 | 2.58 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 17693.11 | 17-DEC-18:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1138.63 | ||||
Maximum of Months | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2662.92 | 25582.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3163.39 | 21-JAN-12:00 | 5888.82 | 1249.73 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.07 |
February | 4693.75 | 01-FEB-09:25 | 7361.02 | 2499.45 | 5502.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 817.87 |
March | 9315.12 | 30-MAR-20:45 | 0.00 | 163.56 | 1210.17 | 0.00 | 0.00 | 0.00 | 0.00 | 5.18 | 0.00 |
April | 7033.96 | 19-APR-14:50 | 5888.82 | 1249.73 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 77.82 | 0.00 |
May | 28205.95 | 04-MAY-20:30 | 0.00 | 736.04 | 5445.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.17 |
June | 37050.94 | 09-JUN-23:21 | 0.00 | 654.26 | 4840.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.00 |
July | 25768.38 | 07-JUL-21:23 | 0.00 | 245.35 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 328.13 | 0.00 |
August | 25674.22 | 18-AUG-22:03 | 0.00 | 245.35 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 414.52 | 0.00 |
September | 32944.51 | 14-SEP-20:31 | 0.00 | 654.26 | 4840.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.47 |
October | 18695.78 | 02-OCT-21:45 | 0.00 | 163.56 | 1210.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.46 |
November | 5157.27 | 04-NOV-16:00 | 11777.63 | 2499.45 | 5502.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.03 |
December | 4186.32 | 01-DEC-09:55 | 7361.02 | 2499.45 | 5502.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.63 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3163.39 | 0.00 | 163.56 | 1210.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37050.94 | 11777.63 | 2499.45 | 5502.84 | 0.00 | 0.00 | 0.00 | 0.00 | 414.52 | 817.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 54092.14 | 26-JAN-07:05 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.55 |
February | 54954.45 | 09-FEB-07:05 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.30 |
March | 99948.64 | 31-MAR-06:03 | 9303.63 | 1033.65 | 6186.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.82 |
April | 152749.75 | 18-APR-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.25 |
May | 147409.70 | 17-MAY-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.23 |
June | 168369.76 | 08-JUN-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.26 |
July | 121471.08 | 03-JUL-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.32 |
August | 120403.07 | 26-AUG-06:02 | 18607.26 | 2067.29 | 9279.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.94 |
September | 157967.97 | 14-SEP-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.45 |
October | 119481.05 | 11-OCT-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.59 |
November | 42781.15 | 04-NOV-06:05 | 6202.42 | 689.10 | 3093.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.92 |
December | 53960.20 | 18-DEC-07:05 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.11 |
Annual Sum or Average | |||||||||||
Minimum of Months | 42781.15 | 6202.42 | 689.10 | 3093.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.94 | |
Maximum of Months | 168369.76 | 18607.26 | 2067.29 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4135.14 | 26-JAN-12:10 | 2045.54 | 1534.02 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.04 |
February | 15555.88 | 26-FEB-19:21 | 0.00 | 292.19 | 4323.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.11 |
March | 19291.62 | 13-MAR-22:01 | 0.00 | 292.19 | 5765.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.57 |
April | 16097.86 | 15-APR-23:11 | 0.00 | 259.73 | 3843.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.72 |
May | 16932.25 | 14-MAY-19:11 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.89 |
June | 20310.64 | 09-JUN-21:31 | 0.00 | 292.19 | 5765.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.20 |
July | 15813.07 | 07-JUL-21:23 | 0.00 | 97.40 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 142.49 | 0.00 |
August | 16153.81 | 18-AUG-22:03 | 0.00 | 97.40 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 177.90 | 0.00 |
September | 20215.80 | 14-SEP-20:41 | 0.00 | 259.73 | 5124.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.53 |
October | 16948.02 | 11-OCT-22:02 | 0.00 | 162.33 | 3202.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.71 |
November | 14497.08 | 08-NOV-21:15 | 0.00 | 64.93 | 1281.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.11 |
December | 11811.55 | 12-DEC-21:25 | 0.00 | 64.93 | 1281.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4135.14 | 0.00 | 64.93 | 1281.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20310.64 | 2045.54 | 1534.02 | 5765.03 | 0.00 | 0.00 | 0.00 | 0.00 | 177.90 | 321.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3097.98 | 15-JAN-11:03 | 1753.32 | 1980.32 | 874.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.98 |
February | 4132.49 | 28-FEB-15:40 | 2337.76 | 1485.24 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
March | 13987.26 | 30-MAR-23:01 | 0.00 | 324.66 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.63 |
April | 15537.45 | 17-APR-21:11 | 0.00 | 324.66 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.21 |
May | 14887.45 | 14-MAY-18:21 | 0.00 | 324.66 | 721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 | 0.00 |
June | 17201.54 | 10-JUN-21:21 | 0.00 | 324.66 | 721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.41 |
July | 12278.59 | 07-JUL-21:23 | 0.00 | 97.40 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 141.65 | 0.00 |
August | 12564.72 | 18-AUG-22:43 | 0.00 | 97.40 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 153.43 | 0.00 |
September | 15590.85 | 14-SEP-20:51 | 0.00 | 292.19 | 865.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.88 |
October | 20448.76 | 11-OCT-23:31 | 0.00 | 259.73 | 769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.27 |
November | 5403.50 | 06-NOV-15:10 | 2337.76 | 1485.24 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 |
December | 3603.36 | 12-DEC-14:00 | 2045.54 | 1485.24 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3097.98 | 0.00 | 97.40 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20448.76 | 2337.76 | 1980.32 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 153.43 | 382.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.18 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.65 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.08 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.24 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.70 |
June | 0.00 | 01-JUN-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.86 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.05 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.62 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.92 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 | |
Maximum of Months | 0.00 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.92 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.553532E+11 | 44561.21 | 07-JAN-17:00 | 0.855667E+11 | 168625.09 | 08-JAN-09:09 |
February | 0.493260E+11 | 47297.89 | 28-FEB-16:00 | 0.506227E+11 | 190394.29 | 12-FEB-09:09 |
March | 0.548529E+11 | 56772.54 | 30-MAR-15:00 | 0.141243E+11 | 64779.20 | 19-MAR-08:20 |
April | 0.574584E+11 | 57922.24 | 17-APR-15:00 | 0.849096E+10 | 53892.34 | 06-APR-06:00 |
May | 0.703000E+11 | 63844.96 | 06-MAY-15:00 | 0.766897E+10 | 4938.93 | 01-MAY-11:39 |
June | 0.848770E+11 | 72645.86 | 06-JUN-14:00 | 0.727726E+10 | 4887.68 | 01-JUN-11:20 |
July | 0.924992E+11 | 82728.79 | 08-JUL-14:30 | 0.735686E+10 | 4849.62 | 03-JUL-11:30 |
August | 0.976270E+11 | 78413.26 | 18-AUG-15:00 | 0.740958E+10 | 4847.76 | 31-AUG-11:39 |
September | 0.766044E+11 | 73758.32 | 07-SEP-15:00 | 0.722970E+10 | 4879.80 | 29-SEP-11:50 |
October | 0.612080E+11 | 64923.55 | 10-OCT-15:00 | 0.832060E+10 | 50741.00 | 26-OCT-06:00 |
November | 0.522567E+11 | 49325.61 | 04-NOV-16:00 | 0.157884E+11 | 110971.82 | 22-NOV-07:10 |
December | 0.538780E+11 | 44632.62 | 12-DEC-15:09 | 0.429513E+11 | 148534.34 | 18-DEC-07:10 |
Annual Sum or Average | 0.806241E+12 | 0.262807E+12 | ||||
Minimum of Months | 0.493260E+11 | 44561.21 | 0.722970E+10 | 4847.76 | ||
Maximum of Months | 0.976270E+11 | 82728.79 | 0.855667E+11 | 190394.29 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.213111E+11 | 0.401236E+10 | 0.163682E+11 | 0.00 | 0.136553E+11 | 0.00 | 0.00 | 6328202.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190908E+11 | 0.336320E+10 | 0.148500E+11 | 0.00 | 0.114120E+11 | 0.00 | 0.00 | 0.610032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203725E+11 | 0.334486E+10 | 0.167807E+11 | 0.00 | 0.112559E+11 | 0.00 | 0.00 | 0.309889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180952E+11 | 0.285878E+10 | 0.159462E+11 | 0.00 | 0.106180E+11 | 0.00 | 0.00 | 0.994024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185055E+11 | 0.262477E+10 | 0.165744E+11 | 0.00 | 0.110172E+11 | 0.00 | 0.00 | 0.215780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.180341E+11 | 0.239558E+10 | 0.162059E+11 | 0.00 | 0.112000E+11 | 0.00 | 0.00 | 0.370415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178470E+11 | 0.252971E+10 | 0.163148E+11 | 0.00 | 0.118597E+11 | 0.00 | 0.00 | 0.439479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.185016E+11 | 0.280480E+10 | 0.167807E+11 | 0.00 | 0.122144E+11 | 0.00 | 0.00 | 0.473255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183415E+11 | 0.307319E+10 | 0.159462E+11 | 0.00 | 0.109979E+11 | 0.00 | 0.00 | 0.282456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.206816E+11 | 0.356736E+10 | 0.163682E+11 | 0.00 | 0.109250E+11 | 0.00 | 0.00 | 0.966593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201979E+11 | 0.379530E+10 | 0.158468E+11 | 0.00 | 0.108117E+11 | 0.00 | 0.00 | 0.160500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210881E+11 | 0.410541E+10 | 0.163148E+11 | 0.00 | 0.121750E+11 | 0.00 | 0.00 | 0.194760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232067E+12 | 0.384753E+11 | 0.194297E+12 | 0.138142E+12 | 0.00 | 0.203260E+12 | |||||||
Minimum of Months | 0.178470E+11 | 0.239558E+10 | 0.148500E+11 | 0.00 | 0.106180E+11 | 0.00 | 0.00 | 6328202.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.213111E+11 | 0.410541E+10 | 0.167807E+11 | 0.00 | 0.136553E+11 | 0.00 | 0.00 | 0.473255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.774491E+11 | 0.00 | 0.811755E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.432745E+11 | 0.00 | 0.734815E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.603069E+10 | 0.00 | 0.809359E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.877079E+09 | 0.00 | 0.761389E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.766897E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.727726E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.735686E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.740958E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.722970E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.709746E+09 | 0.00 | 0.761085E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.823018E+10 | 0.00 | 0.755820E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.349409E+11 | 0.00 | 0.801039E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.171512E+12 | 0.912950E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.722970E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.774491E+11 | 0.00 | 0.811755E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 20551.52 | 02-JAN-17:40 | 3371.20 | 01-JAN-06:10 | 10740.89 | 02-JAN-09:09 | 0.00 | 11756.32 | 08-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 20530.48 | 10-FEB-17:00 | 3371.20 | 01-FEB-06:10 | 10740.89 | 01-FEB-09:09 | 0.00 | 12307.49 | 12-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 20043.44 | 03-MAR-17:00 | 3371.20 | 01-MAR-06:10 | 10740.89 | 01-MAR-09:09 | 0.00 | 9390.57 | 19-MAR-08:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 19292.51 | 08-APR-16:00 | 3371.20 | 01-APR-05:10 | 10740.89 | 01-APR-09:09 | 0.00 | 8939.66 | 06-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 18836.57 | 26-MAY-16:00 | 3371.20 | 01-MAY-05:10 | 10740.89 | 01-MAY-08:09 | 0.00 | 9513.85 | 31-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 18590.69 | 08-JUN-16:00 | 3371.20 | 01-JUN-05:10 | 10740.89 | 01-JUN-08:09 | 0.00 | 9513.85 | 12-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 18813.99 | 27-JUL-08:09 | 3371.20 | 01-JUL-05:10 | 10740.89 | 01-JUL-09:09 | 0.00 | 9618.10 | 08-JUL-14:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 18765.26 | 24-AUG-08:09 | 3371.20 | 01-AUG-05:10 | 10740.89 | 01-AUG-08:09 | 0.00 | 9513.85 | 02-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 19630.74 | 30-SEP-16:00 | 3371.20 | 01-SEP-05:10 | 10740.89 | 01-SEP-08:09 | 0.00 | 9513.85 | 02-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 20387.27 | 30-OCT-16:30 | 3371.20 | 01-OCT-05:10 | 10740.89 | 02-OCT-08:09 | 0.00 | 9513.85 | 18-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 20551.52 | 06-NOV-17:40 | 3371.20 | 01-NOV-05:10 | 10740.89 | 01-NOV-08:09 | 0.00 | 9950.79 | 22-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 20551.52 | 01-DEC-17:30 | 3371.20 | 01-DEC-06:10 | 10740.89 | 01-DEC-09:09 | 0.00 | 11045.25 | 03-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 18590.69 | 3371.20 | 10740.89 | 0.00 | 8939.66 | 0.00 | 0.00 | |||||
Maximum of Months | 20551.52 | 3371.20 | 10740.89 | 0.00 | 12307.49 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 545.35 | 31-JAN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12428.33 | 28-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23052.99 | 30-MAR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23165.76 | 17-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30850.31 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38380.11 | 06-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 47099.62 | 08-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42714.18 | 19-AUG-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37752.57 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29413.77 | 10-OCT-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14881.78 | 05-NOV-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8556.48 | 12-DEC-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 545.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47099.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 44561.21 | 07-JAN-17:00 | 20551.52 | 10740.89 | 3371.20 | 0.00 | 9897.60 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 47297.89 | 28-FEB-16:00 | 19177.26 | 10740.89 | 0.00 | 0.00 | 6743.45 | 0.00 | 0.00 | 10636.30 | 0.00 |
March | 56772.54 | 30-MAR-15:00 | 17369.21 | 10740.89 | 0.00 | 0.00 | 6743.45 | 0.00 | 0.00 | 21919.00 | 0.00 |
April | 57922.24 | 17-APR-15:00 | 18067.30 | 10740.89 | 0.00 | 0.00 | 6743.45 | 0.00 | 0.00 | 22370.61 | 0.00 |
May | 63844.96 | 06-MAY-15:00 | 17437.62 | 10740.89 | 0.00 | 0.00 | 6743.45 | 0.00 | 0.00 | 28923.00 | 0.00 |
June | 72645.86 | 06-JUN-14:00 | 15767.64 | 10740.89 | 0.00 | 0.00 | 7757.22 | 0.00 | 0.00 | 38380.11 | 0.00 |
July | 82728.79 | 08-JUL-14:30 | 15285.11 | 10740.89 | 0.00 | 0.00 | 9603.17 | 0.00 | 0.00 | 47099.62 | 0.00 |
August | 78413.26 | 18-AUG-15:00 | 17424.63 | 10740.89 | 0.00 | 0.00 | 8469.27 | 0.00 | 0.00 | 41778.47 | 0.00 |
September | 73758.32 | 07-SEP-15:00 | 17461.27 | 10740.89 | 0.00 | 0.00 | 7803.59 | 0.00 | 0.00 | 37752.57 | 0.00 |
October | 64923.55 | 10-OCT-15:00 | 18714.43 | 10740.89 | 0.00 | 0.00 | 6851.51 | 0.00 | 0.00 | 28616.72 | 0.00 |
November | 49325.61 | 04-NOV-16:00 | 19463.77 | 10740.89 | 0.00 | 0.00 | 6743.45 | 0.00 | 0.00 | 12377.51 | 0.00 |
December | 44632.62 | 12-DEC-15:09 | 18591.81 | 10740.89 | 0.00 | 0.00 | 6743.45 | 0.00 | 0.00 | 8556.48 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 44561.21 | 15285.11 | 10740.89 | 0.00 | 0.00 | 6743.45 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82728.79 | 20551.52 | 10740.89 | 3371.20 | 0.00 | 9897.60 | 0.00 | 0.00 | 47099.62 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 164662.59 | 09-JAN-07:10 | 0.00 | 5043.30 | 27-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 188534.29 | 12-FEB-09:09 | 0.00 | 5043.70 | 01-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 62582.74 | 18-MAR-06:19 | 0.00 | 5028.83 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 50234.02 | 06-APR-06:40 | 0.00 | 4986.31 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4938.93 | 01-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4887.68 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4849.62 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4847.76 | 31-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4879.80 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 46207.30 | 26-OCT-06:00 | 0.00 | 4933.42 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 109111.82 | 22-NOV-07:10 | 0.00 | 4986.09 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 146674.34 | 18-DEC-07:10 | 0.00 | 5025.23 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4847.76 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 188534.29 | 0.00 | 5043.70 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.33 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.50 | 19.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 20.53 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.48 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.48 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.49 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.48 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.00 | 0.00 |
November | 1.00 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.17 | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.67 | 20.12 | 0.00 | 9.50 | 24.48 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.33 | 20.53 | 0.00 | 0.00 | 3.50 | 24.49 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 20.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.67 | 20.09 | 0.00 | 0.00 | 0.17 | 24.53 | 0.00 | 0.00 |
March | 0.17 | 20.55 | 0.00 | 0.00 | 1.17 | 24.48 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.51 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.49 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 24.49 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 24.53 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 24.54 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 24.51 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 24.49 | 0.00 | 0.00 |
November | 0.17 | 20.55 | 0.00 | 0.00 | 2.17 | 24.48 | 0.00 | 0.00 |
December | 2.00 | 20.37 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 0.00 |
Annual Sum or Average | 9.33 | 20.18 | 0.00 | 83.33 | 24.52 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.33 | 20.55 | 0.00 | 0.00 | 26.83 | 24.54 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.50 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.33 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 20.48 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 0.00 |
April | 0.17 | 20.54 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.47 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.49 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 24.49 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.49 | 0.00 | 0.00 |
October | 0.17 | 20.49 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 0.00 |
November | 0.67 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.67 | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16.17 | 20.15 | 0.00 | 16.33 | 24.49 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.50 | 20.54 | 0.00 | 0.00 | 7.00 | 24.49 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.33 | 12.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43.17 | 13.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 55.50 | 13.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14.33 | 13.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36.83 | 14.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 41.50 | 13.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 141.00 | 13.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 400.67 | 13.34 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 141.00 | 14.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.23 | 337.83 | 21.14 | 337.83 | 21.14 |
February | 376.00 | 21.74 | 194.17 | 21.20 | 194.17 | 21.20 |
March | 390.33 | 22.58 | 48.83 | 21.70 | 40.33 | 21.24 |
April | 278.50 | 23.31 | 57.50 | 23.62 | 36.83 | 23.47 |
May | 138.50 | 23.73 | 243.33 | 23.88 | 64.33 | 23.84 |
June | 15.17 | 23.83 | 310.33 | 23.89 | 0.00 | 0.00 |
July | 28.00 | 23.89 | 390.67 | 23.89 | 28.00 | 23.89 |
August | 0.00 | 0.00 | 403.17 | 23.89 | 0.00 | 0.00 |
September | 32.33 | 23.81 | 291.83 | 23.89 | 20.33 | 23.89 |
October | 303.33 | 23.32 | 100.00 | 23.87 | 41.50 | 23.84 |
November | 374.50 | 22.54 | 63.33 | 22.13 | 58.00 | 21.97 |
December | 415.00 | 21.49 | 205.00 | 21.25 | 205.00 | 21.25 |
Annual Sum or Average | 2765.67 | 22.34 | 2646.00 | 23.05 | 1026.33 | 21.72 |
Minimum of Months | 0.00 | 0.00 | 48.83 | 21.14 | 0.00 | 0.00 |
Maximum of Months | 415.00 | 23.89 | 403.17 | 23.89 | 337.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.26 | 232.83 | 21.16 | 232.83 | 21.16 |
February | 376.00 | 21.84 | 110.33 | 21.19 | 110.33 | 21.19 |
March | 329.00 | 22.53 | 35.50 | 23.57 | 4.00 | 21.11 |
April | 167.83 | 23.08 | 115.33 | 23.88 | 10.50 | 23.87 |
May | 77.17 | 23.64 | 304.67 | 23.88 | 51.83 | 23.88 |
June | 21.50 | 23.80 | 354.67 | 23.89 | 15.17 | 23.90 |
July | 57.83 | 23.89 | 415.00 | 23.89 | 57.83 | 23.89 |
August | 59.83 | 23.90 | 421.33 | 23.89 | 59.83 | 23.90 |
September | 59.00 | 23.82 | 361.67 | 23.89 | 52.00 | 23.89 |
October | 215.33 | 22.90 | 130.00 | 23.86 | 47.67 | 23.81 |
November | 346.50 | 22.39 | 42.50 | 23.19 | 24.50 | 22.69 |
December | 412.83 | 21.51 | 90.83 | 21.42 | 90.83 | 21.42 |
Annual Sum or Average | 2536.83 | 22.24 | 2614.67 | 23.43 | 757.33 | 22.30 |
Minimum of Months | 21.50 | 21.26 | 35.50 | 21.16 | 4.00 | 21.11 |
Maximum of Months | 414.00 | 23.90 | 421.33 | 23.89 | 232.83 | 23.90 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 412.83 | 21.76 | 149.00 | 21.25 | 149.00 | 21.25 |
February | 328.83 | 22.10 | 89.50 | 21.15 | 89.50 | 21.15 |
March | 273.17 | 22.96 | 73.33 | 23.55 | 8.83 | 21.11 |
April | 161.00 | 23.24 | 146.83 | 23.82 | 10.67 | 22.93 |
May | 54.33 | 23.56 | 291.00 | 23.89 | 20.00 | 23.89 |
June | 8.83 | 23.66 | 335.67 | 23.89 | 0.00 | 0.00 |
July | 11.17 | 23.89 | 397.50 | 23.89 | 11.17 | 23.89 |
August | 0.00 | 0.00 | 408.17 | 23.89 | 0.00 | 0.00 |
September | 8.17 | 23.59 | 359.50 | 23.89 | 2.33 | 23.89 |
October | 119.33 | 23.03 | 201.00 | 23.89 | 18.17 | 23.87 |
November | 226.50 | 22.88 | 76.83 | 23.70 | 10.33 | 22.45 |
December | 379.33 | 22.34 | 68.00 | 22.14 | 47.50 | 21.38 |
Annual Sum or Average | 1983.50 | 22.50 | 2596.33 | 23.58 | 367.50 | 21.69 |
Minimum of Months | 0.00 | 0.00 | 68.00 | 21.15 | 0.00 | 0.00 |
Maximum of Months | 412.83 | 23.89 | 408.17 | 23.89 | 149.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.42 | 209.67 | 21.16 | 209.67 | 21.16 |
February | 357.00 | 21.86 | 136.00 | 21.14 | 136.00 | 21.14 |
March | 322.83 | 22.61 | 64.67 | 22.98 | 21.17 | 21.11 |
April | 214.17 | 23.02 | 106.00 | 23.73 | 21.50 | 23.09 |
May | 120.33 | 23.56 | 275.00 | 23.88 | 63.67 | 23.85 |
June | 29.50 | 23.74 | 330.83 | 23.89 | 13.67 | 23.89 |
July | 53.00 | 23.89 | 398.67 | 23.89 | 53.00 | 23.89 |
August | 29.17 | 23.89 | 409.67 | 23.89 | 29.17 | 23.89 |
September | 48.83 | 23.73 | 345.50 | 23.89 | 33.17 | 23.89 |
October | 181.00 | 22.83 | 167.83 | 23.87 | 40.33 | 23.82 |
November | 286.83 | 22.58 | 61.50 | 23.48 | 20.17 | 22.63 |
December | 394.33 | 21.85 | 97.17 | 21.56 | 90.67 | 21.40 |
Annual Sum or Average | 2451.00 | 22.35 | 2602.50 | 23.40 | 732.17 | 22.14 |
Minimum of Months | 29.17 | 21.42 | 61.50 | 21.14 | 13.67 | 21.11 |
Maximum of Months | 414.00 | 23.89 | 409.67 | 23.89 | 209.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.23103 | 30.71193 | -0.5925 | 13.11873 |
February | 376.00000 | 21.72932 | 33.13178 | -0.4287 | 10.64539 |
March | 422.00000 | 22.66962 | 39.07614 | -0.0991 | 7.17296 |
April | 405.00000 | 23.48038 | 44.77895 | 0.17880 | 6.81534 |
May | 418.00000 | 23.83467 | 52.23557 | -0.5442 | 11.62524 |
June | 408.00000 | 23.88720 | 51.36050 | -0.4464 | 9.32099 |
July | 415.00000 | 23.88958 | 55.89025 | -0.3929 | 8.27744 |
August | 422.00000 | 23.88958 | 55.78377 | -0.3860 | 8.16411 |
September | 405.00000 | 23.88225 | 54.06577 | -0.4681 | 9.69662 |
October | 414.00000 | 23.46380 | 48.19156 | 0.22161 | 7.02683 |
November | 399.00000 | 22.60956 | 39.04889 | -0.1060 | 7.35521 |
December | 415.00000 | 21.48636 | 35.39929 | -0.4486 | 10.55953 |
Annual Sum or Average | 4913.00000 | 23.01340 | 45.07262 | -0.2926 | 9.14246 |
Minimum of Months | 376.00000 | 21.23103 | 30.71193 | -0.5925 | 6.81534 |
Maximum of Months | 422.00000 | 23.88958 | 55.89025 | 0.22161 | 13.11873 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.25181 | 27.90732 | -0.5061 | 11.13192 |
February | 376.00000 | 21.83616 | 30.47805 | -0.3183 | 9.00737 |
March | 422.00000 | 22.83024 | 36.43399 | 0.02568 | 6.72597 |
April | 405.00000 | 23.54940 | 42.68399 | 0.27857 | 7.48620 |
May | 418.00000 | 23.84853 | 50.55014 | -0.4529 | 9.63281 |
June | 408.00000 | 23.90372 | 51.99916 | -0.3678 | 7.99535 |
July | 415.00000 | 23.91218 | 58.08671 | -0.3103 | 7.05709 |
August | 422.00000 | 23.91305 | 58.41042 | -0.3041 | 6.98004 |
September | 405.00000 | 23.88939 | 55.20032 | -0.3945 | 8.39809 |
October | 414.00000 | 23.38083 | 47.15957 | 0.27111 | 7.59361 |
November | 399.00000 | 22.58851 | 36.96443 | -0.0372 | 7.02900 |
December | 415.00000 | 21.51637 | 32.90603 | -0.3628 | 9.05984 |
Annual Sum or Average | 4913.00000 | 23.04371 | 44.18102 | -0.2066 | 8.16974 |
Minimum of Months | 376.00000 | 21.25181 | 27.90732 | -0.5061 | 6.72597 |
Maximum of Months | 422.00000 | 23.91305 | 58.41042 | 0.27857 | 11.13192 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.76138 | 26.45999 | -0.3743 | 9.74636 |
February | 376.00000 | 22.31323 | 28.43866 | -0.1990 | 8.71698 |
March | 422.00000 | 23.27726 | 33.55947 | 0.12780 | 7.18124 |
April | 405.00000 | 23.62548 | 40.75921 | 0.28610 | 7.72092 |
May | 418.00000 | 23.84435 | 48.01788 | -0.4606 | 9.88481 |
June | 408.00000 | 23.88418 | 48.59146 | -0.3696 | 8.10588 |
July | 415.00000 | 23.88957 | 53.04543 | -0.3126 | 7.16907 |
August | 422.00000 | 23.88950 | 52.45734 | -0.2866 | 6.85177 |
September | 405.00000 | 23.88186 | 49.75788 | -0.3651 | 8.01165 |
October | 414.00000 | 23.64158 | 43.16040 | 0.35752 | 8.56157 |
November | 399.00000 | 23.31404 | 33.29299 | 0.16160 | 7.15986 |
December | 415.00000 | 22.47184 | 30.21292 | -0.1322 | 7.58762 |
Annual Sum or Average | 4913.00000 | 23.32290 | 40.75050 | -0.1311 | 8.05425 |
Minimum of Months | 376.00000 | 21.76138 | 26.45999 | -0.4606 | 6.85177 |
Maximum of Months | 422.00000 | 23.88957 | 53.04543 | 0.35752 | 9.88481 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.42163 | 27.08604 | -0.4808 | 11.08328 |
February | 376.00000 | 21.95729 | 29.31705 | -0.3091 | 9.50226 |
March | 422.00000 | 22.90296 | 35.27806 | 0.01684 | 7.21539 |
April | 405.00000 | 23.42045 | 42.84019 | 0.21374 | 7.37928 |
May | 418.00000 | 23.79181 | 51.38977 | -0.5087 | 11.13719 |
June | 408.00000 | 23.87857 | 51.78479 | -0.3949 | 8.55126 |
July | 415.00000 | 23.88918 | 57.44524 | -0.3268 | 7.34173 |
August | 422.00000 | 23.88963 | 56.44575 | -0.3049 | 7.06117 |
September | 405.00000 | 23.86794 | 53.45413 | -0.3906 | 8.47308 |
October | 414.00000 | 23.42694 | 45.50079 | 0.29119 | 8.20179 |
November | 399.00000 | 22.94636 | 34.98984 | 0.05476 | 7.20129 |
December | 415.00000 | 21.94558 | 31.46743 | -0.2728 | 8.61355 |
Annual Sum or Average | 4913.00000 | 23.11948 | 43.20163 | -0.2012 | 8.47564 |
Minimum of Months | 376.00000 | 21.42163 | 27.08604 | -0.5087 | 7.06117 |
Maximum of Months | 422.00000 | 23.88963 | 57.44524 | 0.29119 | 11.13719 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 78389246.28 | 21971364.57 | 14.25 | 78389234.71 | 11.57 | 0.00 | 0.33 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 4622.35 | 28-FEB-15:10 | 4622.35 | 28-FEB-15:10 | 0.03 | 22-FEB-15:23 | 1282.69 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.921051E+09 | 0.248111E+09 | 89.53 | 0.713009E+09 | 0.208042E+09 | 0.00 | 0.79 | 30-MAR-20:45 | 0.00 | 01-MAR-00:10 | 12650.14 | 30-MAR-20:45 | 11461.79 | 30-MAR-15:00 | 2764.97 | 30-MAR-11:45 | 3202.37 | 30-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 0.378070E+10 | 0.100985E+10 | 225.03 | 0.308418E+10 | 0.696513E+09 | 0.00 | 0.71 | 19-APR-15:50 | 0.00 | 01-APR-00:10 | 11630.76 | 19-APR-15:50 | 11040.32 | 15-APR-14:00 | 3639.68 | 04-APR-14:10 | 2957.44 | 18-APR-13:10 | 0.00 | 01-APR-00:10 |
May | 0.103805E+11 | 0.265388E+10 | 360.81 | 0.764639E+10 | 0.273413E+10 | 0.00 | 1.00 | 03-MAY-20:31 | 0.00 | 01-MAY-00:10 | 37389.32 | 22-MAY-20:32 | 30507.21 | 15-MAY-21:00 | 15473.76 | 03-MAY-22:20 | 8008.59 | 19-MAY-21:00 | 0.00 | 01-MAY-00:10 |
June | 0.208791E+11 | 0.524888E+10 | 524.73 | 0.153524E+11 | 0.552671E+10 | 0.00 | 1.00 | 02-JUN-00:21 | 0.00 | 01-JUN-00:05 | 36915.03 | 07-JUN-01:12 | 33954.97 | 10-JUN-21:21 | 16432.49 | 07-JUN-01:12 | 8021.35 | 09-JUN-20:19 | 0.00 | 01-JUN-00:05 |
July | 0.254564E+11 | 0.637378E+10 | 588.81 | 0.179391E+11 | 0.751732E+10 | 0.00 | 1.00 | 07-JUL-20:43 | 0.00 | 01-JUL-00:05 | 37830.00 | 28-JUL-21:35 | 28579.64 | 07-JUL-21:23 | 20991.32 | 28-JUL-21:35 | 9039.42 | 09-JUL-18:43 | 0.00 | 01-JUL-00:05 |
August | 0.278404E+11 | 0.689029E+10 | 615.67 | 0.192584E+11 | 0.858205E+10 | 0.00 | 1.00 | 02-AUG-20:10 | 0.00 | 01-AUG-00:05 | 37020.85 | 02-AUG-20:43 | 28525.30 | 18-AUG-22:03 | 9768.45 | 10-AUG-20:43 | 8985.99 | 18-AUG-20:10 | 0.00 | 01-AUG-00:05 |
September | 0.157959E+11 | 0.392012E+10 | 468.53 | 0.111054E+11 | 0.469051E+10 | 0.00 | 1.00 | 13-SEP-05:00 | 0.00 | 01-SEP-00:10 | 37785.45 | 21-SEP-23:15 | 29702.74 | 14-SEP-20:31 | 19544.50 | 21-SEP-23:15 | 7976.21 | 21-SEP-23:15 | 0.00 | 01-SEP-00:05 |
October | 0.426127E+10 | 0.107287E+10 | 214.34 | 0.293135E+10 | 0.132992E+10 | 0.00 | 1.00 | 02-OCT-21:45 | 0.00 | 01-OCT-00:10 | 36643.34 | 19-OCT-20:45 | 21602.17 | 02-OCT-21:45 | 16884.73 | 19-OCT-20:45 | 7788.78 | 19-OCT-20:45 | 0.00 | 01-OCT-00:10 |
November | 0.307803E+09 | 82216618.33 | 67.39 | 0.208228E+09 | 99575175.27 | 0.00 | 0.45 | 05-NOV-15:30 | 0.00 | 01-NOV-00:10 | 7034.68 | 05-NOV-15:10 | 4834.38 | 05-NOV-16:00 | 2574.46 | 04-NOV-15:55 | 1830.34 | 05-NOV-15:30 | 0.00 | 01-NOV-00:10 |
December | 5654856.06 | 1613707.85 | 6.29 | 4129993.47 | 1524862.59 | 0.00 | 0.08 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 | 1118.18 | 12-DEC-15:10 | 830.06 | 12-DEC-15:10 | 288.13 | 12-DEC-15:10 | 317.71 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.109707E+12 | 0.275236E+11 | 3175.37 | 0.783209E+11 | 0.313863E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.278404E+11 | 0.689029E+10 | 615.67 | 0.192584E+11 | 0.858205E+10 | 0.00 | 1.00 | 0.00 | 37830.00 | 33954.97 | 20991.32 | 9039.42 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 6973.28 | 2215.03 | 0.67 | 5604.09 | 1369.19 | 0.00 | 0.00 | 31-JAN-14:50 | 0.00 | 01-JAN-00:10 | 5.43 | 31-JAN-14:50 | 4.37 | 31-JAN-14:50 | 1.07 | 31-JAN-14:50 | 1.73 | 31-JAN-14:50 | 0.00 | 01-JAN-00:10 |
February | 0.116845E+10 | 0.360710E+09 | 33.81 | 0.114513E+10 | 23314561.79 | 0.00 | 0.41 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 27079.40 | 28-FEB-15:10 | 26113.61 | 28-FEB-15:10 | 965.80 | 28-FEB-15:10 | 8217.34 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.724000E+10 | 0.213777E+10 | 121.99 | 0.537642E+10 | 0.186359E+10 | 0.00 | 0.72 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 136972.52 | 31-MAR-06:03 | 76500.31 | 31-MAR-06:03 | 60472.20 | 31-MAR-06:03 | 32551.28 | 31-MAR-06:03 | 0.00 | 01-MAR-00:10 |
April | 0.246185E+11 | 0.718520E+10 | 249.83 | 0.191168E+11 | 0.550168E+10 | 0.00 | 1.00 | 18-APR-06:03 | 0.00 | 01-APR-00:10 | 165706.27 | 19-APR-06:03 | 101935.67 | 18-APR-06:03 | 68782.78 | 23-APR-08:63 | 39435.13 | 19-APR-06:03 | 0.00 | 01-APR-00:10 |
May | 0.549001E+11 | 0.154164E+11 | 360.14 | 0.382188E+11 | 0.166813E+11 | 0.00 | 1.00 | 04-MAY-06:03 | 0.00 | 01-MAY-00:10 | 179044.24 | 26-MAY-06:03 | 118858.40 | 07-MAY-08:62 | 95767.13 | 26-MAY-06:03 | 41968.46 | 26-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.934769E+11 | 0.255438E+11 | 408.91 | 0.624287E+11 | 0.310481E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:05 | 181564.35 | 18-JUN-08:62 | 149444.29 | 11-JUN-08:62 | 89486.30 | 21-JUN-06:02 | 43162.72 | 25-JUN-08:62 | 0.00 | 01-JUN-00:05 |
July | 0.111394E+12 | 0.299769E+11 | 430.12 | 0.688037E+11 | 0.425903E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 186318.92 | 30-JUL-08:62 | 122119.77 | 25-JUL-06:02 | 99639.98 | 28-JUL-06:02 | 44379.76 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.120082E+12 | 0.318678E+11 | 443.54 | 0.720688E+11 | 0.480129E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:05 | 185229.30 | 20-AUG-08:62 | 128907.10 | 26-AUG-06:02 | 99038.64 | 23-AUG-06:04 | 43963.60 | 06-AUG-08:62 | 0.00 | 01-AUG-00:05 |
September | 0.701056E+11 | 0.190006E+11 | 377.31 | 0.437176E+11 | 0.263880E+11 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 186414.53 | 17-SEP-08:62 | 121201.43 | 16-SEP-06:02 | 91602.41 | 17-SEP-08:04 | 43590.95 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.228674E+11 | 0.638100E+10 | 214.55 | 0.149632E+11 | 0.790422E+10 | 0.00 | 1.00 | 11-OCT-06:03 | 0.00 | 01-OCT-00:10 | 182617.67 | 19-OCT-06:02 | 102489.73 | 18-OCT-06:02 | 104080.26 | 19-OCT-06:04 | 42391.48 | 19-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.307454E+10 | 0.916736E+09 | 92.27 | 0.213624E+10 | 0.938300E+09 | 0.00 | 0.46 | 05-NOV-16:00 | 0.00 | 01-NOV-00:10 | 34010.44 | 05-NOV-15:00 | 22661.60 | 05-NOV-16:00 | 15411.03 | 04-NOV-06:05 | 9870.36 | 05-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 0.282267E+09 | 86124144.81 | 11.52 | 0.185031E+09 | 97236577.70 | 0.00 | 0.27 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 | 18552.26 | 12-DEC-15:10 | 13050.86 | 12-DEC-15:10 | 5883.22 | 12-DEC-14:00 | 5602.77 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.509209E+12 | 0.138873E+12 | 2744.65 | 0.328161E+12 | 0.181049E+12 | 0.00 | ||||||||||||||
Minimum of Months | 6973.28 | 2215.03 | 0.67 | 5604.09 | 1369.19 | 0.00 | 0.00 | 0.00 | 5.43 | 4.37 | 1.07 | 1.73 | 0.00 | |||||||
Maximum of Months | 0.120082E+12 | 0.318678E+11 | 443.54 | 0.720688E+11 | 0.480129E+11 | 0.00 | 1.00 | 0.00 | 186414.53 | 149444.29 | 104080.26 | 44379.76 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 23331601.51 | 6324671.08 | 21.97 | 19464251.49 | 3867350.02 | 0.00 | 0.24 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 | 2043.40 | 31-JAN-15:10 | 1809.96 | 31-JAN-15:00 | 271.70 | 31-JAN-15:50 | 544.71 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.616362E+09 | 0.156443E+09 | 79.52 | 0.613038E+09 | 3323948.14 | 0.00 | 1.00 | 26-FEB-19:21 | 0.00 | 01-FEB-00:10 | 20897.25 | 26-FEB-19:21 | 20897.25 | 26-FEB-19:21 | 676.51 | 28-FEB-21:20 | 4424.25 | 26-FEB-19:21 | 0.00 | 01-FEB-00:10 |
March | 0.195854E+10 | 0.491667E+09 | 204.98 | 0.157952E+10 | 0.379011E+09 | 0.00 | 1.00 | 13-MAR-20:11 | 0.00 | 01-MAR-00:10 | 22142.91 | 30-MAR-23:40 | 18376.08 | 13-MAR-20:11 | 6417.71 | 31-MAR-00:31 | 4716.10 | 13-MAR-20:11 | 0.00 | 01-MAR-00:10 |
April | 0.449220E+10 | 0.113147E+10 | 283.19 | 0.369662E+10 | 0.795572E+09 | 0.00 | 1.00 | 11-APR-20:20 | 0.00 | 01-APR-00:10 | 22923.43 | 21-APR-20:25 | 18934.48 | 16-APR-20:00 | 10045.78 | 21-APR-21:45 | 4859.82 | 21-APR-20:25 | 0.00 | 01-APR-00:10 |
May | 0.885532E+10 | 0.219893E+10 | 419.85 | 0.670201E+10 | 0.215331E+10 | 0.00 | 1.00 | 04-MAY-21:40 | 0.00 | 01-MAY-00:10 | 22576.61 | 20-MAY-22:40 | 20522.46 | 14-MAY-18:20 | 9138.22 | 21-MAY-00:20 | 4855.83 | 14-MAY-18:20 | 0.00 | 01-MAY-00:10 |
June | 0.147999E+11 | 0.367902E+10 | 556.90 | 0.110150E+11 | 0.378493E+10 | 0.00 | 1.00 | 02-JUN-01:00 | 0.00 | 01-JUN-00:05 | 22233.46 | 06-JUN-01:30 | 20880.08 | 10-JUN-23:00 | 8272.33 | 06-JUN-01:30 | 4863.37 | 09-JUN-20:21 | 0.00 | 01-JUN-00:05 |
July | 0.178376E+11 | 0.443225E+10 | 617.76 | 0.126555E+11 | 0.518213E+10 | 0.00 | 1.00 | 07-JUL-20:43 | 0.00 | 01-JUL-00:10 | 21940.21 | 07-JUL-20:43 | 17793.02 | 07-JUL-21:23 | 5938.75 | 28-JUL-22:05 | 5559.81 | 09-JUL-18:43 | 0.00 | 01-JUL-00:05 |
August | 0.201342E+11 | 0.494515E+10 | 643.22 | 0.141742E+11 | 0.596006E+10 | 0.00 | 1.00 | 02-AUG-20:08 | 0.00 | 01-AUG-00:10 | 22765.64 | 03-AUG-20:43 | 18165.48 | 18-AUG-22:03 | 6068.75 | 19-AUG-21:10 | 5518.99 | 18-AUG-20:08 | 0.00 | 01-AUG-00:05 |
September | 0.131253E+11 | 0.317477E+10 | 527.86 | 0.956589E+10 | 0.355942E+10 | 0.00 | 1.00 | 07-SEP-20:43 | 0.00 | 01-SEP-00:05 | 22842.59 | 29-SEP-20:22 | 18196.22 | 14-SEP-20:10 | 9765.91 | 29-SEP-20:22 | 5127.49 | 07-SEP-20:43 | 0.00 | 01-SEP-00:05 |
October | 0.582385E+10 | 0.138987E+10 | 304.88 | 0.444314E+10 | 0.138071E+10 | 0.00 | 1.00 | 02-OCT-22:02 | 0.00 | 01-OCT-00:10 | 22539.73 | 19-OCT-20:12 | 19667.66 | 11-OCT-20:10 | 10095.14 | 19-OCT-21:00 | 4792.44 | 19-OCT-20:12 | 0.00 | 01-OCT-00:10 |
November | 0.179917E+10 | 0.446246E+09 | 178.44 | 0.145833E+10 | 0.340832E+09 | 0.00 | 1.00 | 03-NOV-20:20 | 0.00 | 01-NOV-00:10 | 22694.83 | 03-NOV-20:20 | 12957.81 | 03-NOV-20:20 | 9737.02 | 03-NOV-20:20 | 4820.61 | 03-NOV-20:20 | 0.00 | 01-NOV-00:10 |
December | 0.337340E+09 | 83552147.60 | 65.33 | 0.233991E+09 | 0.103349E+09 | 0.00 | 1.00 | 12-DEC-21:25 | 0.00 | 01-DEC-00:10 | 22031.15 | 12-DEC-21:25 | 14589.38 | 12-DEC-21:25 | 7441.77 | 12-DEC-21:25 | 4691.58 | 12-DEC-21:25 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.898031E+11 | 0.221357E+11 | 3903.90 | 0.661566E+11 | 0.236465E+11 | 0.00 | ||||||||||||||
Minimum of Months | 23331601.51 | 6324671.08 | 21.97 | 19464251.49 | 3323948.14 | 0.00 | 0.24 | 0.00 | 2043.40 | 1809.96 | 271.70 | 544.71 | 0.00 | |||||||
Maximum of Months | 0.201342E+11 | 0.494515E+10 | 643.22 | 0.141742E+11 | 0.596006E+10 | 0.00 | 1.00 | 0.00 | 22923.43 | 20897.25 | 10095.14 | 5559.81 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 5315.73 | 1316.24 | 5.25 | 4528.16 | 787.57 | 0.00 | 0.00 | 31-JAN-14:00 | 0.00 | 01-JAN-00:10 | 0.80 | 31-JAN-14:00 | 0.67 | 31-JAN-14:00 | 0.13 | 31-JAN-14:00 | 0.20 | 31-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 0.311492E+09 | 70907500.91 | 52.05 | 0.311435E+09 | 56481.10 | 0.00 | 0.64 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 5358.88 | 28-FEB-15:10 | 5358.88 | 28-FEB-15:10 | 19.62 | 28-FEB-11:10 | 1186.95 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.983150E+09 | 0.221341E+09 | 146.36 | 0.790882E+09 | 0.192268E+09 | 0.00 | 1.00 | 30-MAR-23:01 | 0.00 | 01-MAR-00:10 | 18009.15 | 30-MAR-23:01 | 13129.63 | 30-MAR-23:01 | 5082.42 | 30-MAR-23:30 | 3551.00 | 30-MAR-23:01 | 0.00 | 01-MAR-00:10 |
April | 0.270613E+10 | 0.613726E+09 | 232.08 | 0.225357E+10 | 0.452565E+09 | 0.00 | 1.00 | 12-APR-20:45 | 0.00 | 01-APR-00:10 | 18089.51 | 18-APR-20:21 | 14982.75 | 16-APR-19:55 | 6067.19 | 20-APR-20:45 | 3550.89 | 18-APR-20:21 | 0.00 | 01-APR-00:10 |
May | 0.592504E+10 | 0.130886E+10 | 350.56 | 0.443577E+10 | 0.148927E+10 | 0.00 | 1.00 | 03-MAY-20:31 | 0.00 | 01-MAY-00:10 | 18607.42 | 22-MAY-21:15 | 16054.91 | 14-MAY-18:21 | 8283.70 | 22-MAY-21:15 | 3634.35 | 22-MAY-21:15 | 0.00 | 01-MAY-00:10 |
June | 0.117389E+11 | 0.256975E+10 | 522.08 | 0.852705E+10 | 0.321188E+10 | 0.00 | 1.00 | 02-JUN-00:21 | 0.00 | 01-JUN-00:05 | 18407.60 | 07-JUN-01:17 | 16660.47 | 10-JUN-21:21 | 8283.31 | 07-JUN-01:17 | 3739.51 | 25-JUN-18:10 | 0.00 | 01-JUN-00:05 |
July | 0.144636E+11 | 0.316501E+10 | 590.19 | 0.100328E+11 | 0.443079E+10 | 0.00 | 1.00 | 07-JUL-20:10 | 0.00 | 01-JUL-00:05 | 17938.31 | 07-JUL-20:10 | 13603.33 | 07-JUL-21:23 | 6020.16 | 26-JUL-20:10 | 4180.22 | 09-JUL-18:10 | 0.00 | 01-JUL-00:05 |
August | 0.167408E+11 | 0.362223E+10 | 631.39 | 0.114708E+11 | 0.526997E+10 | 0.00 | 1.00 | 01-AUG-20:43 | 0.00 | 01-AUG-00:10 | 18577.71 | 03-AUG-20:10 | 13915.19 | 18-AUG-22:43 | 6418.37 | 08-AUG-20:10 | 4153.09 | 06-AUG-18:10 | 0.00 | 01-AUG-00:05 |
September | 0.100687E+11 | 0.215009E+10 | 484.05 | 0.718653E+10 | 0.288217E+10 | 0.00 | 1.00 | 07-SEP-20:10 | 0.00 | 01-SEP-00:05 | 18967.95 | 21-SEP-20:25 | 14326.76 | 14-SEP-20:11 | 9919.99 | 21-SEP-20:25 | 3899.88 | 07-SEP-20:10 | 0.00 | 01-SEP-00:05 |
October | 0.389240E+10 | 0.822193E+09 | 253.09 | 0.290186E+10 | 0.990547E+09 | 0.00 | 1.00 | 02-OCT-21:40 | 0.00 | 01-OCT-00:10 | 18462.59 | 16-OCT-23:01 | 15472.46 | 11-OCT-20:11 | 8076.98 | 11-OCT-02:10 | 3612.66 | 16-OCT-23:01 | 0.00 | 01-OCT-00:10 |
November | 0.712448E+09 | 0.159807E+09 | 122.62 | 0.576647E+09 | 0.135801E+09 | 0.00 | 0.73 | 05-NOV-18:25 | 0.00 | 01-NOV-00:10 | 6677.09 | 05-NOV-13:40 | 4851.34 | 05-NOV-18:25 | 2310.62 | 05-NOV-13:30 | 1376.58 | 05-NOV-13:40 | 0.00 | 01-NOV-00:10 |
December | 0.104167E+09 | 23470126.94 | 30.30 | 74035745.34 | 30131625.06 | 0.00 | 0.60 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5357.03 | 12-DEC-14:00 | 3767.04 | 12-DEC-14:00 | 1589.99 | 12-DEC-14:00 | 1147.30 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.676468E+11 | 0.147274E+11 | 3420.03 | 0.485614E+11 | 0.190854E+11 | 0.00 | ||||||||||||||
Minimum of Months | 5315.73 | 1316.24 | 5.25 | 4528.16 | 787.57 | 0.00 | 0.00 | 0.00 | 0.80 | 0.67 | 0.13 | 0.20 | 0.00 | |||||||
Maximum of Months | 0.167408E+11 | 0.362223E+10 | 631.39 | 0.114708E+11 | 0.526997E+10 | 0.00 | 1.00 | 0.00 | 18967.95 | 16660.47 | 9919.99 | 4180.22 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.22 | 14.70 | 12.52 | 12.03 | 58.41 | 0.00 | 0.00 | 744.00 |
February | 34.65 | 21.33 | 13.31 | 25.59 | 50.12 | 0.00 | 0.00 | 672.00 |
March | 51.11 | 31.35 | 19.76 | 50.79 | 35.94 | 0.00 | 0.00 | 744.00 |
April | 64.79 | 40.30 | 24.49 | 75.57 | 30.18 | 0.00 | 0.00 | 720.00 |
May | 71.96 | 41.83 | 30.14 | 89.42 | 21.23 | 0.00 | 0.00 | 744.00 |
June | 76.90 | 45.61 | 31.29 | 101.95 | 15.91 | 0.00 | 0.00 | 720.00 |
July | 71.47 | 40.67 | 30.80 | 96.47 | 12.08 | 0.00 | 0.00 | 744.00 |
August | 65.63 | 36.07 | 29.57 | 89.06 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 48.85 | 27.34 | 21.51 | 58.84 | 19.98 | 0.00 | 0.00 | 720.00 |
October | 41.55 | 27.94 | 13.62 | 41.44 | 34.71 | 0.00 | 0.00 | 744.00 |
November | 30.35 | 16.94 | 13.41 | 21.59 | 44.15 | 0.00 | 0.00 | 720.00 |
December | 24.44 | 12.93 | 11.51 | 10.87 | 51.55 | 3.83 | 0.00 | 744.00 |
Annual Sum or Average | 50.83 | 29.79 | 21.04 | 56.29 | 32.04 | 3.83 | 0.00 | 8760.00 |
Minimum of Months | 24.44 | 12.93 | 11.51 | 10.87 | 11.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 76.90 | 45.61 | 31.29 | 101.95 | 58.41 | 3.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 866.15 | 603.94 | 262.21 | 997.40 | 867.60 | 0.00 | 0.00 | 744.00 |
February | 808.40 | 541.95 | 266.45 | 978.02 | 749.40 | 0.00 | 0.00 | 672.00 |
March | 726.74 | 378.67 | 348.06 | 882.06 | 528.34 | 0.00 | 0.00 | 744.00 |
April | 544.19 | 177.02 | 367.17 | 668.78 | 430.42 | 0.00 | 0.00 | 720.00 |
May | 439.66 | 50.95 | 388.71 | 583.62 | 279.17 | 0.00 | 0.00 | 744.00 |
June | 406.50 | 22.47 | 384.04 | 677.17 | 167.48 | 0.00 | 0.00 | 720.00 |
July | 410.98 | 30.50 | 380.48 | 721.63 | 109.48 | 0.00 | 0.00 | 744.00 |
August | 490.71 | 91.54 | 399.17 | 848.93 | 89.64 | 0.00 | 0.00 | 744.00 |
September | 539.68 | 200.64 | 339.04 | 802.08 | 233.59 | 0.00 | 0.00 | 720.00 |
October | 782.65 | 507.02 | 275.63 | 1078.58 | 506.41 | 0.00 | 0.00 | 744.00 |
November | 842.16 | 558.92 | 283.24 | 1096.75 | 650.59 | 0.00 | 0.00 | 720.00 |
December | 853.76 | 600.68 | 253.08 | 1045.45 | 760.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 641.92 | 312.63 | 329.30 | 864.70 | 446.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 406.50 | 22.47 | 253.08 | 583.62 | 89.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 866.15 | 603.94 | 399.17 | 1096.75 | 867.60 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 866.15 | 603.94 | 262.21 | 1002.45 | 847.11 | 0.00 | 0.00 | 744.00 |
February | 808.40 | 541.95 | 266.45 | 981.65 | 726.29 | 0.00 | 0.00 | 672.00 |
March | 726.74 | 378.67 | 348.06 | 887.62 | 504.89 | 0.00 | 0.00 | 744.00 |
April | 544.19 | 177.02 | 367.17 | 670.51 | 413.58 | 0.00 | 0.00 | 720.00 |
May | 439.66 | 50.95 | 388.71 | 580.69 | 271.57 | 0.00 | 0.00 | 744.00 |
June | 406.50 | 22.47 | 384.04 | 670.71 | 165.54 | 0.00 | 0.00 | 720.00 |
July | 410.98 | 30.50 | 380.48 | 715.39 | 107.58 | 0.00 | 0.00 | 744.00 |
August | 490.71 | 91.54 | 399.17 | 842.31 | 87.40 | 0.00 | 0.00 | 744.00 |
September | 539.68 | 200.64 | 339.04 | 796.83 | 231.14 | 0.00 | 0.00 | 720.00 |
October | 782.65 | 507.02 | 275.63 | 1077.51 | 493.86 | 0.00 | 0.00 | 744.00 |
November | 842.16 | 558.92 | 283.24 | 1101.04 | 628.11 | 0.00 | 0.00 | 720.00 |
December | 853.76 | 600.68 | 253.08 | 1051.82 | 732.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 641.92 | 312.63 | 329.30 | 864.52 | 432.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 406.50 | 22.47 | 253.08 | 580.69 | 87.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 866.15 | 603.94 | 399.17 | 1101.04 | 847.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 178.22 | 124.27 | 53.95 | 218.12 | 150.55 | 0.00 | 0.00 | 744.00 |
February | 166.34 | 111.51 | 54.83 | 210.84 | 130.17 | 0.00 | 0.00 | 672.00 |
March | 149.54 | 77.92 | 71.62 | 194.28 | 91.15 | 0.00 | 0.00 | 744.00 |
April | 111.97 | 36.42 | 75.55 | 141.34 | 78.80 | 0.00 | 0.00 | 720.00 |
May | 90.47 | 10.48 | 79.98 | 115.05 | 54.97 | 0.00 | 0.00 | 744.00 |
June | 83.64 | 4.62 | 79.02 | 119.05 | 39.42 | 0.00 | 0.00 | 720.00 |
July | 84.56 | 6.28 | 78.29 | 124.27 | 29.12 | 0.00 | 0.00 | 744.00 |
August | 100.97 | 18.84 | 82.13 | 148.84 | 27.20 | 0.00 | 0.00 | 744.00 |
September | 111.05 | 41.28 | 69.76 | 154.03 | 51.53 | 0.00 | 0.00 | 720.00 |
October | 161.04 | 104.33 | 56.72 | 225.32 | 92.86 | 0.00 | 0.00 | 744.00 |
November | 173.29 | 115.01 | 58.28 | 236.34 | 113.23 | 0.00 | 0.00 | 720.00 |
December | 175.67 | 123.60 | 52.08 | 230.48 | 126.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 132.08 | 64.33 | 67.76 | 176.36 | 81.88 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 83.64 | 4.62 | 52.08 | 115.05 | 27.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 178.22 | 124.27 | 82.13 | 236.34 | 150.55 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72893380.74 | 39367451.69 | 33525929.05 | 32209833.86 | 0.156437E+09 |
February | 83818740.70 | 51607845.29 | 32210895.41 | 61904440.21 | 0.121262E+09 |
March | 0.136906E+09 | 83975699.96 | 52930338.58 | 0.136045E+09 | 96270418.51 |
April | 0.167940E+09 | 0.104450E+09 | 63489573.96 | 0.195874E+09 | 78229838.65 |
May | 0.192749E+09 | 0.112026E+09 | 80722788.52 | 0.239510E+09 | 56854424.77 |
June | 0.199319E+09 | 0.118215E+09 | 81103983.87 | 0.264261E+09 | 41238096.69 |
July | 0.191437E+09 | 0.108936E+09 | 82501741.52 | 0.258382E+09 | 32360402.99 |
August | 0.175797E+09 | 96600479.13 | 79196179.05 | 0.238538E+09 | 30558661.31 |
September | 0.126614E+09 | 70862761.88 | 55750764.82 | 0.152511E+09 | 51800002.97 |
October | 0.111296E+09 | 74828145.65 | 36468210.65 | 0.110990E+09 | 92960085.80 |
November | 78661237.61 | 43904636.06 | 34756601.55 | 55968566.65 | 0.114442E+09 |
December | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 0.138083E+09 |
Annual Sum or Average | 0.160288E+10 | 0.939396E+09 | 0.663487E+09 | 0.177531E+10 | 0.101050E+10 |
Minimum of Months | 65452537.81 | 34622167.76 | 30830370.05 | 29112980.26 | 30558661.31 |
Maximum of Months | 0.199319E+09 | 0.118215E+09 | 82501741.52 | 0.264261E+09 | 0.156437E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.267145E+10 | 0.232378E+10 |
February | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.236603E+10 | 0.181295E+10 |
March | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.236250E+10 | 0.141510E+10 |
April | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.173348E+10 | 0.111565E+10 |
May | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.156316E+10 | 0.747718E+09 |
June | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.175523E+10 | 0.434118E+09 |
July | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.193282E+10 | 0.293220E+09 |
August | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.227378E+10 | 0.240098E+09 |
September | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.207898E+10 | 0.605470E+09 |
October | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.288888E+10 | 0.135637E+10 |
November | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.284278E+10 | 0.168634E+10 |
December | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.280012E+10 | 0.203647E+10 |
Annual Sum or Average | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.272692E+11 | 0.140673E+11 |
Minimum of Months | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.156316E+10 | 0.240098E+09 |
Maximum of Months | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.288888E+10 | 0.232378E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.268496E+10 | 0.226889E+10 |
February | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.237481E+10 | 0.175704E+10 |
March | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.237739E+10 | 0.135231E+10 |
April | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.173796E+10 | 0.107199E+10 |
May | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.155532E+10 | 0.727382E+09 |
June | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.173849E+10 | 0.429074E+09 |
July | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.191611E+10 | 0.288149E+09 |
August | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.225605E+10 | 0.234086E+09 |
September | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.206539E+10 | 0.599127E+09 |
October | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.288601E+10 | 0.132276E+10 |
November | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.285389E+10 | 0.162806E+10 |
December | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.281719E+10 | 0.196122E+10 |
Annual Sum or Average | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.272636E+11 | 0.136401E+11 |
Minimum of Months | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.155532E+10 | 0.234086E+09 |
Maximum of Months | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.288601E+10 | 0.226889E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.477354E+09 | 0.332844E+09 | 0.144510E+09 | 0.584214E+09 | 0.403235E+09 |
February | 0.402408E+09 | 0.269774E+09 | 0.132634E+09 | 0.510061E+09 | 0.314918E+09 |
March | 0.400520E+09 | 0.208695E+09 | 0.191825E+09 | 0.520364E+09 | 0.244146E+09 |
April | 0.290238E+09 | 94412838.34 | 0.195825E+09 | 0.366344E+09 | 0.204256E+09 |
May | 0.242305E+09 | 28079908.65 | 0.214225E+09 | 0.308152E+09 | 0.147227E+09 |
June | 0.216806E+09 | 11981890.80 | 0.204824E+09 | 0.308568E+09 | 0.102170E+09 |
July | 0.226499E+09 | 16810004.70 | 0.209689E+09 | 0.332832E+09 | 77992066.92 |
August | 0.270442E+09 | 50451868.80 | 0.219990E+09 | 0.398662E+09 | 72848644.49 |
September | 0.287834E+09 | 0.107009E+09 | 0.180825E+09 | 0.399242E+09 | 0.133572E+09 |
October | 0.431332E+09 | 0.279427E+09 | 0.151906E+09 | 0.603490E+09 | 0.248724E+09 |
November | 0.449158E+09 | 0.298093E+09 | 0.151064E+09 | 0.612589E+09 | 0.293499E+09 |
December | 0.470522E+09 | 0.331044E+09 | 0.139478E+09 | 0.617305E+09 | 0.339583E+09 |
Annual Sum or Average | 0.416542E+10 | 0.202862E+10 | 0.213680E+10 | 0.556182E+10 | 0.258217E+10 |
Minimum of Months | 0.216806E+09 | 11981890.80 | 0.132634E+09 | 0.308152E+09 | 72848644.49 |
Maximum of Months | 0.477354E+09 | 0.332844E+09 | 0.219990E+09 | 0.617305E+09 | 0.403235E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 192.41 | 934.51 | 435.44 | 235.17 | 200.27 | 0.00 | 0.00 |
February | 409.42 | 802.00 | 554.36 | 341.32 | 213.04 | 0.00 | 0.00 |
March | 812.70 | 575.09 | 817.84 | 501.65 | 316.19 | 0.00 | 0.00 |
April | 1209.10 | 482.90 | 1036.67 | 644.75 | 391.91 | 0.00 | 0.00 |
May | 1430.76 | 339.63 | 1151.43 | 669.21 | 482.21 | 0.00 | 0.00 |
June | 1631.24 | 254.56 | 1230.36 | 729.72 | 500.64 | 0.00 | 0.00 |
July | 1543.50 | 193.31 | 1143.59 | 650.75 | 492.84 | 0.00 | 0.00 |
August | 1424.96 | 182.55 | 1050.16 | 577.06 | 473.10 | 0.00 | 0.00 |
September | 941.43 | 319.75 | 781.56 | 437.42 | 344.14 | 0.00 | 0.00 |
October | 663.02 | 555.32 | 664.85 | 447.00 | 217.85 | 0.00 | 0.00 |
November | 345.48 | 706.43 | 485.56 | 271.02 | 214.55 | 0.00 | 0.00 |
December | 173.91 | 824.87 | 390.99 | 206.82 | 184.17 | 0.00 | 0.00 |
Annual Sum or Average | 900.71 | 512.68 | 813.23 | 476.61 | 336.62 | 0.00 | 0.00 |
Minimum of Months | 173.91 | 182.55 | 390.99 | 206.82 | 184.17 | 0.00 | 0.00 |
Maximum of Months | 1631.24 | 934.51 | 1230.36 | 729.72 | 500.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 997.40 | 867.60 | 866.15 | 603.94 | 262.21 | 0.00 | 0.00 |
February | 978.02 | 749.40 | 808.40 | 541.95 | 266.45 | 0.00 | 0.00 |
March | 882.06 | 528.34 | 726.74 | 378.67 | 348.06 | 0.00 | 0.00 |
April | 668.78 | 430.42 | 544.19 | 177.02 | 367.17 | 0.00 | 0.00 |
May | 583.62 | 279.17 | 439.66 | 50.95 | 388.71 | 0.00 | 0.00 |
June | 677.17 | 167.48 | 406.50 | 22.47 | 384.04 | 0.00 | 0.00 |
July | 721.63 | 109.48 | 410.98 | 30.50 | 380.48 | 0.00 | 0.00 |
August | 848.93 | 89.64 | 490.71 | 91.54 | 399.17 | 0.00 | 0.00 |
September | 802.08 | 233.59 | 539.68 | 200.64 | 339.04 | 0.00 | 0.00 |
October | 1078.58 | 506.41 | 782.65 | 507.02 | 275.63 | 0.00 | 0.00 |
November | 1096.75 | 650.59 | 842.16 | 558.92 | 283.24 | 0.00 | 0.00 |
December | 1045.45 | 760.33 | 853.76 | 600.68 | 253.08 | 0.00 | 0.00 |
Annual Sum or Average | 864.70 | 446.07 | 641.92 | 312.63 | 329.30 | 0.00 | 0.00 |
Minimum of Months | 583.62 | 89.64 | 406.50 | 22.47 | 253.08 | 0.00 | 0.00 |
Maximum of Months | 1096.75 | 867.60 | 866.15 | 603.94 | 399.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1002.45 | 847.11 | 866.15 | 603.94 | 262.21 | 0.00 | 0.00 |
February | 981.65 | 726.29 | 808.40 | 541.95 | 266.45 | 0.00 | 0.00 |
March | 887.62 | 504.89 | 726.74 | 378.67 | 348.06 | 0.00 | 0.00 |
April | 670.51 | 413.58 | 544.19 | 177.02 | 367.17 | 0.00 | 0.00 |
May | 580.69 | 271.57 | 439.66 | 50.95 | 388.71 | 0.00 | 0.00 |
June | 670.71 | 165.54 | 406.50 | 22.47 | 384.04 | 0.00 | 0.00 |
July | 715.39 | 107.58 | 410.98 | 30.50 | 380.48 | 0.00 | 0.00 |
August | 842.31 | 87.40 | 490.71 | 91.54 | 399.17 | 0.00 | 0.00 |
September | 796.83 | 231.14 | 539.68 | 200.64 | 339.04 | 0.00 | 0.00 |
October | 1077.51 | 493.86 | 782.65 | 507.02 | 275.63 | 0.00 | 0.00 |
November | 1101.04 | 628.11 | 842.16 | 558.92 | 283.24 | 0.00 | 0.00 |
December | 1051.82 | 732.23 | 853.76 | 600.68 | 253.08 | 0.00 | 0.00 |
Annual Sum or Average | 864.52 | 432.52 | 641.92 | 312.63 | 329.30 | 0.00 | 0.00 |
Minimum of Months | 580.69 | 87.40 | 406.50 | 22.47 | 253.08 | 0.00 | 0.00 |
Maximum of Months | 1101.04 | 847.11 | 866.15 | 603.94 | 399.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 218.12 | 150.55 | 178.22 | 124.27 | 53.95 | 0.00 | 0.00 |
February | 210.84 | 130.17 | 166.34 | 111.51 | 54.83 | 0.00 | 0.00 |
March | 194.28 | 91.15 | 149.54 | 77.92 | 71.62 | 0.00 | 0.00 |
April | 141.34 | 78.80 | 111.97 | 36.42 | 75.55 | 0.00 | 0.00 |
May | 115.05 | 54.97 | 90.47 | 10.48 | 79.98 | 0.00 | 0.00 |
June | 119.05 | 39.42 | 83.64 | 4.62 | 79.02 | 0.00 | 0.00 |
July | 124.27 | 29.12 | 84.56 | 6.28 | 78.29 | 0.00 | 0.00 |
August | 148.84 | 27.20 | 100.97 | 18.84 | 82.13 | 0.00 | 0.00 |
September | 154.03 | 51.53 | 111.05 | 41.28 | 69.76 | 0.00 | 0.00 |
October | 225.32 | 92.86 | 161.04 | 104.33 | 56.72 | 0.00 | 0.00 |
November | 236.34 | 113.23 | 173.29 | 115.01 | 58.28 | 0.00 | 0.00 |
December | 230.48 | 126.79 | 175.67 | 123.60 | 52.08 | 0.00 | 0.00 |
Annual Sum or Average | 176.36 | 81.88 | 132.08 | 64.33 | 67.76 | 0.00 | 0.00 |
Minimum of Months | 115.05 | 27.20 | 83.64 | 4.62 | 52.08 | 0.00 | 0.00 |
Maximum of Months | 236.34 | 150.55 | 178.22 | 124.27 | 82.13 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.515357E+09 | 0.250299E+10 | 0.116629E+10 | 0.629879E+09 | 0.536415E+09 | 0.00 | 0.00 |
February | 0.990471E+09 | 0.194020E+10 | 0.134110E+10 | 0.825726E+09 | 0.515374E+09 | 0.00 | 0.00 |
March | 0.217673E+10 | 0.154033E+10 | 0.219050E+10 | 0.134361E+10 | 0.846885E+09 | 0.00 | 0.00 |
April | 0.313398E+10 | 0.125168E+10 | 0.268704E+10 | 0.167120E+10 | 0.101583E+10 | 0.00 | 0.00 |
May | 0.383216E+10 | 0.909671E+09 | 0.308398E+10 | 0.179241E+10 | 0.129156E+10 | 0.00 | 0.00 |
June | 0.422817E+10 | 0.659810E+09 | 0.318910E+10 | 0.189143E+10 | 0.129766E+10 | 0.00 | 0.00 |
July | 0.413412E+10 | 0.517766E+09 | 0.306300E+10 | 0.174297E+10 | 0.132003E+10 | 0.00 | 0.00 |
August | 0.381660E+10 | 0.488939E+09 | 0.281275E+10 | 0.154561E+10 | 0.126714E+10 | 0.00 | 0.00 |
September | 0.244018E+10 | 0.828800E+09 | 0.202582E+10 | 0.113380E+10 | 0.892012E+09 | 0.00 | 0.00 |
October | 0.177584E+10 | 0.148736E+10 | 0.178074E+10 | 0.119725E+10 | 0.583491E+09 | 0.00 | 0.00 |
November | 0.895497E+09 | 0.183107E+10 | 0.125858E+10 | 0.702474E+09 | 0.556106E+09 | 0.00 | 0.00 |
December | 0.465808E+09 | 0.220933E+10 | 0.104724E+10 | 0.553955E+09 | 0.493286E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.284049E+11 | 0.161679E+11 | 0.256461E+11 | 0.150303E+11 | 0.106158E+11 | 0.00 | 0.00 |
Minimum of Months | 0.465808E+09 | 0.488939E+09 | 0.104724E+10 | 0.553955E+09 | 0.493286E+09 | 0.00 | 0.00 |
Maximum of Months | 0.422817E+10 | 0.250299E+10 | 0.318910E+10 | 0.189143E+10 | 0.132003E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.267145E+10 | 0.232378E+10 | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.00 | 0.00 |
February | 0.236603E+10 | 0.181295E+10 | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.00 | 0.00 |
March | 0.236250E+10 | 0.141510E+10 | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.00 | 0.00 |
April | 0.173348E+10 | 0.111565E+10 | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.00 | 0.00 |
May | 0.156316E+10 | 0.747718E+09 | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.00 | 0.00 |
June | 0.175523E+10 | 0.434118E+09 | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.00 | 0.00 |
July | 0.193282E+10 | 0.293220E+09 | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.00 | 0.00 |
August | 0.227378E+10 | 0.240098E+09 | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.00 | 0.00 |
September | 0.207898E+10 | 0.605470E+09 | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.00 | 0.00 |
October | 0.288888E+10 | 0.135637E+10 | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.00 | 0.00 |
November | 0.284278E+10 | 0.168634E+10 | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.00 | 0.00 |
December | 0.280012E+10 | 0.203647E+10 | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.272692E+11 | 0.140673E+11 | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.00 | 0.00 |
Minimum of Months | 0.156316E+10 | 0.240098E+09 | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.288888E+10 | 0.232378E+10 | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.268496E+10 | 0.226889E+10 | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.00 | 0.00 |
February | 0.237481E+10 | 0.175704E+10 | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.00 | 0.00 |
March | 0.237739E+10 | 0.135231E+10 | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.00 | 0.00 |
April | 0.173796E+10 | 0.107199E+10 | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.00 | 0.00 |
May | 0.155532E+10 | 0.727382E+09 | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.00 | 0.00 |
June | 0.173849E+10 | 0.429074E+09 | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.00 | 0.00 |
July | 0.191611E+10 | 0.288149E+09 | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.00 | 0.00 |
August | 0.225605E+10 | 0.234086E+09 | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.00 | 0.00 |
September | 0.206539E+10 | 0.599127E+09 | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.00 | 0.00 |
October | 0.288601E+10 | 0.132276E+10 | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.00 | 0.00 |
November | 0.285389E+10 | 0.162806E+10 | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.00 | 0.00 |
December | 0.281719E+10 | 0.196122E+10 | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.272636E+11 | 0.136401E+11 | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.00 | 0.00 |
Minimum of Months | 0.155532E+10 | 0.234086E+09 | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.288601E+10 | 0.226889E+10 | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.584214E+09 | 0.403235E+09 | 0.477354E+09 | 0.332844E+09 | 0.144510E+09 | 0.00 | 0.00 |
February | 0.510061E+09 | 0.314918E+09 | 0.402408E+09 | 0.269774E+09 | 0.132634E+09 | 0.00 | 0.00 |
March | 0.520364E+09 | 0.244146E+09 | 0.400520E+09 | 0.208695E+09 | 0.191825E+09 | 0.00 | 0.00 |
April | 0.366344E+09 | 0.204256E+09 | 0.290238E+09 | 94412838.34 | 0.195825E+09 | 0.00 | 0.00 |
May | 0.308152E+09 | 0.147227E+09 | 0.242305E+09 | 28079908.65 | 0.214225E+09 | 0.00 | 0.00 |
June | 0.308568E+09 | 0.102170E+09 | 0.216806E+09 | 11981890.80 | 0.204824E+09 | 0.00 | 0.00 |
July | 0.332832E+09 | 77992066.92 | 0.226499E+09 | 16810004.70 | 0.209689E+09 | 0.00 | 0.00 |
August | 0.398662E+09 | 72848644.49 | 0.270442E+09 | 50451868.80 | 0.219990E+09 | 0.00 | 0.00 |
September | 0.399242E+09 | 0.133572E+09 | 0.287834E+09 | 0.107009E+09 | 0.180825E+09 | 0.00 | 0.00 |
October | 0.603490E+09 | 0.248724E+09 | 0.431332E+09 | 0.279427E+09 | 0.151906E+09 | 0.00 | 0.00 |
November | 0.612589E+09 | 0.293499E+09 | 0.449158E+09 | 0.298093E+09 | 0.151064E+09 | 0.00 | 0.00 |
December | 0.617305E+09 | 0.339583E+09 | 0.470522E+09 | 0.331044E+09 | 0.139478E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.556182E+10 | 0.258217E+10 | 0.416542E+10 | 0.202862E+10 | 0.213680E+10 | 0.00 | 0.00 |
Minimum of Months | 0.308152E+09 | 72848644.49 | 0.216806E+09 | 11981890.80 | 0.132634E+09 | 0.00 | 0.00 |
Maximum of Months | 0.617305E+09 | 0.403235E+09 | 0.477354E+09 | 0.332844E+09 | 0.219990E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.45 | -3.0 | 4.56 | -7.9 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.23 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.96 | 3.80 | 4.89 | 2.24 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.53 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.43 | 13.69 | 3.50 | 11.45 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.34 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.67 | 19.85 | 3.24 | 17.63 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.41 | 20.72 | 3.39 | 18.20 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.43 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.01 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.21 | 4.17 | 4.16 | 0.29 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.67 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.28 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.45 | -3.0 | 3.06 | -7.9 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.41 | 20.72 | 5.19 | 18.20 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.95 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.72 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.85 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.53 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.47 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.37 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.89 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.82 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.04 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.54 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.94 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.76 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.72 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.89 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.7 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.7 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.4 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.0 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.44 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.1 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.7 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.80 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.15 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.00 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.33 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.31 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.05 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.12 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.09 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.19 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.87 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.80 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.12 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.80 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.78 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.09 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.88 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.80 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.257166E+10 | -.214399E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -427669366.8 | 58.99 | 0.00 | 0.00 |
February | 0.233579E+10 | -.195629E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -379500360.0 | 58.99 | 0.00 | 0.00 |
March | 0.255040E+10 | -.214514E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -405262568.2 | 58.99 | 0.00 | 0.00 |
April | 0.229019E+10 | -.190919E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -380998932.7 | 59.00 | 0.00 | 0.00 |
May | 0.220299E+10 | -.181625E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -386740333.3 | 58.99 | 0.00 | 0.00 |
June | 0.201397E+10 | -.164085E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373114740.1 | 58.99 | 0.00 | 0.00 |
July | 0.194652E+10 | -.156098E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385546267.3 | 58.99 | 0.00 | 0.00 |
August | 0.199088E+10 | -.160533E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385548713.7 | 58.99 | 0.00 | 0.00 |
September | 0.197390E+10 | -.160075E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373148962.8 | 58.99 | 0.00 | 0.00 |
October | 0.215644E+10 | -.176385E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -392585114.6 | 58.99 | 0.00 | 0.00 |
November | 0.224340E+10 | -.185069E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -392708644.6 | 58.99 | 0.00 | 0.00 |
December | 0.248302E+10 | -.206169E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -421332413.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.267592E+11 | -.220550E+11 | 8760.00 | -.470416E+10 | 58.99 | |||||
Minimum of Months | 0.194652E+10 | -.214514E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -427669366.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.257166E+10 | -.156098E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -373114740.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.86 | 0.58 | 09-JAN-12:30 | 167.14 | 4.01 | 0.00 | 0.00 | 138.36 | 2.83 | 0.00 | 0.00 |
February | 263.00 | 0.85 | 0.50 | 15-FEB-12:20 | 181.14 | 3.99 | 0.00 | 0.00 | 148.39 | 2.74 | 0.00 | 0.00 |
March | 351.67 | 0.79 | 0.50 | 02-MAR-11:30 | 244.69 | 5.76 | 0.00 | 4.33 | 202.79 | 4.24 | 0.00 | 2.33 |
April | 369.33 | 0.74 | 0.50 | 01-APR-11:20 | 1707.62 | 7.00 | 0.00 | 69.17 | 1791.68 | 5.37 | 0.00 | 56.83 |
May | 407.00 | 0.74 | 0.50 | 01-MAY-10:30 | 304.34 | 8.82 | 0.00 | 40.67 | 256.37 | 7.08 | 0.00 | 28.17 |
June | 411.67 | 0.74 | 0.50 | 01-JUN-10:39 | 302.46 | 9.31 | 0.00 | 38.33 | 254.12 | 7.54 | 0.00 | 26.17 |
July | 411.00 | 0.73 | 0.50 | 01-JUL-10:39 | 309.98 | 9.23 | 0.00 | 40.50 | 260.59 | 7.53 | 0.00 | 27.17 |
August | 390.50 | 0.71 | 0.50 | 01-AUG-11:00 | 403.21 | 8.81 | 0.00 | 62.33 | 302.09 | 7.07 | 0.00 | 36.83 |
September | 298.50 | 0.73 | 0.50 | 01-SEP-10:00 | 2014.71 | 6.69 | 0.00 | 87.50 | 1440.64 | 5.06 | 0.00 | 45.50 |
October | 293.50 | 0.83 | 0.50 | 01-OCT-11:30 | 194.44 | 3.96 | 0.00 | 2.33 | 169.41 | 2.79 | 0.00 | 2.33 |
November | 299.00 | 0.83 | 0.61 | 03-NOV-09:50 | 196.41 | 4.30 | 0.00 | 2.00 | 355.47 | 2.97 | 0.00 | 28.33 |
December | 285.17 | 0.84 | 0.62 | 28-DEC-13:09 | 817.40 | 3.85 | 0.00 | 37.33 | 129.43 | 2.63 | 0.00 | 0.00 |
Annual Sum or Average | 4071.00 | 0.77 | 564.11 | 6.64 | 0.00 | 384.50 | 459.16 | 5.12 | 0.00 | 253.67 | ||
Minimum of Months | 263.00 | 0.71 | 0.50 | 167.14 | 3.85 | 0.00 | 0.00 | 129.43 | 2.63 | 0.00 | 0.00 | |
Maximum of Months | 411.67 | 0.86 | 0.62 | 2014.71 | 9.31 | 0.00 | 87.50 | 1791.68 | 7.54 | 0.00 | 56.83 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109596E+11 | 47374.01 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.633755E+10 | 47374.01 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.979642E+09 | 47374.01 | 18-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139513E+09 | 44913.33 | 07-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 58659377.16 | 15427.40 | 31-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107340E+10 | 47374.01 | 21-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.515481E+10 | 47374.01 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247032E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109596E+11 | 47374.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.379848E+11 | 207445.73 | 05-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206135E+11 | 207445.73 | 03-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.285314E+10 | 46921.24 | 18-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.372364E+09 | 34222.72 | 07-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.392831E+09 | 37313.17 | 26-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.442301E+10 | 93248.81 | 22-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181413E+11 | 207445.73 | 04-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.847810E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.379848E+11 | 207445.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.317639E+10 | 29106.88 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185494E+10 | 29106.88 | 02-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226575E+09 | 29106.88 | 23-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 60329027.59 | 5730.94 | 06-APR-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27057569.29 | 4129.36 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178090E+09 | 29106.88 | 21-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119399E+10 | 29106.88 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.671737E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.317639E+10 | 29106.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.477852E+10 | 23258.50 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.287454E+10 | 23258.50 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.536448E+09 | 23258.50 | 18-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133282E+09 | 23258.50 | 06-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90989894.49 | 17448.10 | 31-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.438146E+09 | 23258.50 | 21-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210697E+10 | 23258.50 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109589E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.477852E+10 | 23258.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.535965E+10 | 29104.07 | 02-JAN-17:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311417E+10 | 26770.25 | 08-FEB-17:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.253387E+09 | 11694.12 | 22-MAR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 290694.48 | 238.65 | 26-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 446101.46 | 1006.38 | 26-OCT-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.498520E+09 | 25847.24 | 21-NOV-16:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147828E+10 | 15766.85 | 17-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107047E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.535965E+10 | 29104.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 78389246.28 | 78389234.71 | 4622.35 | 28-FEB-15:10 | 4622.35 | 0.00 |
March | 0.00 | 0.00 | 0.921051E+09 | 0.713009E+09 | 12650.14 | 30-MAR-20:45 | 10474.17 | 0.00 |
April | 0.00 | 0.00 | 0.378070E+10 | 0.308418E+10 | 11630.76 | 19-APR-15:50 | 10302.27 | 0.00 |
May | 0.00 | 0.00 | 0.103805E+11 | 0.764639E+10 | 37389.32 | 22-MAY-20:32 | 21981.16 | 0.00 |
June | 0.00 | 0.00 | 0.208791E+11 | 0.153524E+11 | 36915.03 | 07-JUN-01:12 | 20482.54 | 0.00 |
July | 0.00 | 0.00 | 0.254564E+11 | 0.179391E+11 | 37830.00 | 28-JUL-21:35 | 16838.68 | 0.00 |
August | 0.00 | 0.00 | 0.278404E+11 | 0.192584E+11 | 37020.85 | 02-AUG-20:43 | 27999.96 | 0.00 |
September | 0.00 | 0.00 | 0.157959E+11 | 0.111054E+11 | 37785.45 | 21-SEP-23:15 | 18240.95 | 0.00 |
October | 0.00 | 0.00 | 0.426127E+10 | 0.293135E+10 | 36643.34 | 19-OCT-20:45 | 19758.61 | 0.00 |
November | 0.00 | 0.00 | 0.307803E+09 | 0.208228E+09 | 7034.68 | 05-NOV-15:10 | 4682.83 | 0.00 |
December | 0.00 | 0.00 | 5654856.06 | 4129993.47 | 1118.18 | 12-DEC-15:10 | 830.06 | 0.00 |
Annual Sum or Average | 0.109707E+12 | 0.783209E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.278404E+11 | 0.192584E+11 | 37830.00 | 27999.96 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6973.28 | 5604.09 | 5.43 | 31-JAN-14:50 | 4.37 | 0.00 |
February | 0.00 | 0.00 | 0.116845E+10 | 0.114513E+10 | 27079.40 | 28-FEB-15:10 | 26113.61 | 0.00 |
March | 0.00 | 0.00 | 0.724000E+10 | 0.537642E+10 | 136972.52 | 31-MAR-06:03 | 76500.31 | 0.00 |
April | 0.00 | 0.00 | 0.246185E+11 | 0.191168E+11 | 165706.27 | 19-APR-06:03 | 101307.44 | 0.00 |
May | 0.00 | 0.00 | 0.549001E+11 | 0.382188E+11 | 179044.24 | 26-MAY-06:03 | 83277.11 | 0.00 |
June | 0.00 | 0.00 | 0.934769E+11 | 0.624287E+11 | 181564.35 | 18-JUN-08:62 | 104038.17 | 0.00 |
July | 0.00 | 0.00 | 0.111394E+12 | 0.688037E+11 | 186318.92 | 30-JUL-08:62 | 92581.90 | 0.00 |
August | 0.00 | 0.00 | 0.120082E+12 | 0.720688E+11 | 185229.30 | 20-AUG-08:62 | 99627.86 | 0.00 |
September | 0.00 | 0.00 | 0.701056E+11 | 0.437176E+11 | 186414.53 | 17-SEP-08:62 | 95153.06 | 0.00 |
October | 0.00 | 0.00 | 0.228674E+11 | 0.149632E+11 | 182617.67 | 19-OCT-06:02 | 78650.35 | 0.00 |
November | 0.00 | 0.00 | 0.307454E+10 | 0.213624E+10 | 34010.44 | 05-NOV-15:00 | 21525.59 | 0.00 |
December | 0.00 | 0.00 | 0.282267E+09 | 0.185031E+09 | 18552.26 | 12-DEC-15:10 | 13050.86 | 0.00 |
Annual Sum or Average | 0.509209E+12 | 0.328161E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 6973.28 | 5604.09 | 5.43 | 4.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.120082E+12 | 0.720688E+11 | 186414.53 | 104038.17 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 23331601.51 | 19464251.49 | 2043.40 | 31-JAN-15:10 | 1799.57 | 0.00 |
February | 0.00 | 0.00 | 0.616362E+09 | 0.613038E+09 | 20897.25 | 26-FEB-19:21 | 20897.25 | 0.00 |
March | 0.00 | 0.00 | 0.195854E+10 | 0.157952E+10 | 22142.91 | 30-MAR-23:40 | 16183.42 | 0.00 |
April | 0.00 | 0.00 | 0.449220E+10 | 0.369662E+10 | 22923.43 | 21-APR-20:25 | 13059.15 | 0.00 |
May | 0.00 | 0.00 | 0.885532E+10 | 0.670201E+10 | 22576.61 | 20-MAY-22:40 | 13948.16 | 0.00 |
June | 0.00 | 0.00 | 0.147999E+11 | 0.110150E+11 | 22233.46 | 06-JUN-01:30 | 13961.14 | 0.00 |
July | 0.00 | 0.00 | 0.178376E+11 | 0.126555E+11 | 21940.21 | 07-JUL-20:43 | 17607.52 | 0.00 |
August | 0.00 | 0.00 | 0.201342E+11 | 0.141742E+11 | 22765.64 | 03-AUG-20:43 | 17517.13 | 0.00 |
September | 0.00 | 0.00 | 0.131253E+11 | 0.956589E+10 | 22842.59 | 29-SEP-20:22 | 13076.68 | 0.00 |
October | 0.00 | 0.00 | 0.582385E+10 | 0.444314E+10 | 22539.73 | 19-OCT-20:12 | 12665.97 | 0.00 |
November | 0.00 | 0.00 | 0.179917E+10 | 0.145833E+10 | 22694.83 | 03-NOV-20:20 | 12957.81 | 0.00 |
December | 0.00 | 0.00 | 0.337340E+09 | 0.233991E+09 | 22031.15 | 12-DEC-21:25 | 14589.38 | 0.00 |
Annual Sum or Average | 0.898031E+11 | 0.661566E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 23331601.51 | 19464251.49 | 2043.40 | 1799.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201342E+11 | 0.141742E+11 | 22923.43 | 20897.25 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 5315.73 | 4528.16 | 0.80 | 31-JAN-14:00 | 0.67 | 0.00 |
February | 0.00 | 0.00 | 0.311492E+09 | 0.311435E+09 | 5358.88 | 28-FEB-15:10 | 5358.88 | 0.00 |
March | 0.00 | 0.00 | 0.983150E+09 | 0.790882E+09 | 18009.15 | 30-MAR-23:01 | 13129.63 | 0.00 |
April | 0.00 | 0.00 | 0.270613E+10 | 0.225357E+10 | 18089.51 | 18-APR-20:21 | 12613.96 | 0.00 |
May | 0.00 | 0.00 | 0.592504E+10 | 0.443577E+10 | 18607.42 | 22-MAY-21:15 | 10323.73 | 0.00 |
June | 0.00 | 0.00 | 0.117389E+11 | 0.852705E+10 | 18407.60 | 07-JUN-01:17 | 10124.29 | 0.00 |
July | 0.00 | 0.00 | 0.144636E+11 | 0.100328E+11 | 17938.31 | 07-JUL-20:10 | 13091.41 | 0.00 |
August | 0.00 | 0.00 | 0.167408E+11 | 0.114708E+11 | 18577.71 | 03-AUG-20:10 | 12827.32 | 0.00 |
September | 0.00 | 0.00 | 0.100687E+11 | 0.718653E+10 | 18967.95 | 21-SEP-20:25 | 9047.96 | 0.00 |
October | 0.00 | 0.00 | 0.389240E+10 | 0.290186E+10 | 18462.59 | 16-OCT-23:01 | 10873.17 | 0.00 |
November | 0.00 | 0.00 | 0.712448E+09 | 0.576647E+09 | 6677.09 | 05-NOV-13:40 | 4427.22 | 0.00 |
December | 0.00 | 0.00 | 0.104167E+09 | 74035745.34 | 5357.03 | 12-DEC-14:00 | 3767.04 | 0.00 |
Annual Sum or Average | 0.676468E+11 | 0.485614E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 5315.73 | 4528.16 | 0.80 | 0.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.167408E+11 | 0.114708E+11 | 18967.95 | 13129.63 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.118305E+10 | 0.33 | 1262.90 | 01-JAN-16:51 | 0.94 |
February | 0.679621E+09 | 0.21 | 1262.90 | 01-FEB-08:63 | 0.94 |
March | 0.120026E+09 | 0.03 | 1262.90 | 06-MAR-08:07 | 0.94 |
April | 16670278.84 | 0.00 | 1262.90 | 06-APR-07:05 | 0.94 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 8158333.43 | 0.00 | 1262.90 | 13-OCT-07:08 | 0.94 |
November | 0.207419E+09 | 0.06 | 1262.90 | 07-NOV-08:08 | 0.94 |
December | 0.555537E+09 | 0.15 | 1262.90 | 01-DEC-08:65 | 0.94 |
Annual Sum or Average | 0.277048E+10 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118305E+10 | 0.33 | 1262.90 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154532E+10 | 0.39 | 1950.90 | 01-JAN-07:01 | 0.91 |
February | 0.130692E+10 | 0.37 | 1950.90 | 01-FEB-05:01 | 0.91 |
March | 0.130032E+10 | 0.34 | 1950.90 | 18-MAR-04:02 | 0.91 |
April | 0.122573E+10 | 0.33 | 1849.56 | 07-APR-04:02 | 0.91 |
May | 0.129030E+10 | 0.35 | 1950.90 | 03-MAY-20:31 | 0.90 |
June | 0.137589E+10 | 0.43 | 1950.90 | 02-JUN-00:21 | 0.90 |
July | 0.147760E+10 | 0.46 | 1950.90 | 07-JUL-20:43 | 0.90 |
August | 0.153191E+10 | 0.48 | 1950.90 | 02-AUG-20:10 | 0.90 |
September | 0.132280E+10 | 0.40 | 1950.90 | 19-SEP-20:34 | 0.90 |
October | 0.125942E+10 | 0.33 | 1161.55 | 31-OCT-05:03 | 0.70 |
November | 0.123493E+10 | 0.34 | 1950.90 | 21-NOV-05:01 | 0.91 |
December | 0.139509E+10 | 0.37 | 1950.90 | 01-DEC-05:01 | 0.91 |
Annual Sum or Average | 0.162662E+11 | 0.38 | |||
Minimum of Months | 0.122573E+10 | 0.33 | 1161.55 | 0.70 | |
Maximum of Months | 0.154532E+10 | 0.48 | 1950.90 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.866519E+10 | 0.57 | 11543.37 | 05-JAN-07:03 | 1.44 |
February | 0.740370E+10 | 0.55 | 11543.37 | 03-FEB-07:03 | 1.44 |
March | 0.762622E+10 | 0.53 | 8825.27 | 31-MAR-06:03 | 1.25 |
April | 0.724796E+10 | 0.52 | 11543.37 | 18-APR-06:03 | 1.42 |
May | 0.748733E+10 | 0.52 | 11543.37 | 04-MAY-06:03 | 1.42 |
June | 0.743511E+10 | 0.53 | 11543.37 | 01-JUN-06:02 | 1.42 |
July | 0.781105E+10 | 0.53 | 11543.37 | 01-JUL-06:02 | 1.41 |
August | 0.796345E+10 | 0.54 | 11543.37 | 01-AUG-06:02 | 1.41 |
September | 0.729548E+10 | 0.52 | 11543.37 | 01-SEP-06:02 | 1.41 |
October | 0.741756E+10 | 0.52 | 11543.37 | 11-OCT-06:03 | 1.41 |
November | 0.727870E+10 | 0.52 | 7730.66 | 22-NOV-07:05 | 1.18 |
December | 0.801930E+10 | 0.55 | 11543.37 | 04-DEC-07:03 | 1.44 |
Annual Sum or Average | 0.916510E+11 | 0.53 | |||
Minimum of Months | 0.724796E+10 | 0.52 | 7730.66 | 1.18 | |
Maximum of Months | 0.866519E+10 | 0.57 | 11543.37 | 1.44 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.830607E+09 | 0.38 | 1165.61 | 01-JAN-07:01 | 0.94 |
February | 0.728344E+09 | 0.37 | 1165.61 | 02-FEB-05:01 | 0.94 |
March | 0.770382E+09 | 0.35 | 1165.61 | 13-MAR-22:01 | 0.94 |
April | 0.744987E+09 | 0.35 | 842.68 | 11-APR-21:01 | 0.80 |
May | 0.789513E+09 | 0.39 | 970.01 | 23-MAY-23:01 | 0.86 |
June | 0.861376E+09 | 0.48 | 1165.61 | 03-JUN-23:16 | 0.94 |
July | 0.943898E+09 | 0.51 | 1165.61 | 07-JUL-20:43 | 0.93 |
August | 0.101484E+10 | 0.54 | 1165.61 | 02-AUG-20:08 | 0.93 |
September | 0.858797E+09 | 0.48 | 1165.61 | 07-SEP-20:43 | 0.93 |
October | 0.792689E+09 | 0.39 | 852.72 | 10-OCT-20:10 | 0.81 |
November | 0.729889E+09 | 0.35 | 1165.61 | 21-NOV-05:01 | 0.94 |
December | 0.780833E+09 | 0.36 | 1165.61 | 01-DEC-05:01 | 0.94 |
Annual Sum or Average | 0.984615E+10 | 0.41 | |||
Minimum of Months | 0.728344E+09 | 0.35 | 842.68 | 0.80 | |
Maximum of Months | 0.101484E+10 | 0.54 | 1165.61 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143112E+10 | 0.59 | 879.50 | 01-JAN-08:62 | 0.94 |
February | 0.129342E+10 | 0.59 | 879.50 | 04-FEB-09:00 | 0.95 |
March | 0.143900E+10 | 0.58 | 879.50 | 02-MAR-08:02 | 0.94 |
April | 0.138270E+10 | 0.57 | 879.50 | 19-APR-18:40 | 0.94 |
May | 0.145008E+10 | 0.60 | 879.50 | 15-MAY-10:10 | 0.93 |
June | 0.152760E+10 | 0.73 | 879.50 | 01-JUN-17:00 | 0.93 |
July | 0.162719E+10 | 0.78 | 879.50 | 01-JUL-05:20 | 0.93 |
August | 0.170420E+10 | 0.83 | 879.50 | 23-AUG-07:05 | 0.93 |
September | 0.152086E+10 | 0.72 | 879.50 | 01-SEP-15:50 | 0.93 |
October | 0.144716E+10 | 0.60 | 879.50 | 03-OCT-08:55 | 0.93 |
November | 0.136077E+10 | 0.56 | 879.50 | 02-NOV-11:00 | 0.93 |
December | 0.142422E+10 | 0.58 | 879.50 | 03-DEC-08:30 | 0.95 |
Annual Sum or Average | 0.176083E+11 | 0.65 | |||
Minimum of Months | 0.129342E+10 | 0.56 | 879.50 | 0.93 | |
Maximum of Months | 0.170420E+10 | 0.83 | 879.50 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.34 | 0.00 |
February | 0.69 | 0.00 |
March | 0.50 | 0.00 |
April | 0.06 | 0.00 |
May | 0.08 | 0.00 |
June | 0.42 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.06 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.31 | 0.00 |
Annual Sum or Average | 3.44 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.34 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.31 | 25.84 |
March | 1.79 | 25.84 |
April | 1.39 | 25.84 |
May | 1.58 | 25.84 |
June | 1.42 | 12.16 |
July | 1.50 | 2.87 |
August | 1.25 | 0.00 |
September | 0.83 | 20.67 |
October | 1.76 | 25.84 |
November | 1.32 | 25.84 |
December | 0.21 | 25.84 |
Annual Sum or Average | 13.36 | 19.07 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.79 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.23 | 0.00 |
February | 0.60 | 0.00 |
March | 0.37 | 0.81 |
April | 2.04 | 0.05 |
May | 1.51 | 0.00 |
June | 1.67 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 2.56 | 0.00 |
October | 1.72 | 0.35 |
November | 1.01 | 1.10 |
December | 0.29 | 1.04 |
Annual Sum or Average | 12.02 | 0.20 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.56 | 1.10 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.70 | 0.00 |
February | 0.69 | 0.30 |
March | 0.60 | 0.51 |
April | 0.88 | 0.00 |
May | 0.93 | 0.00 |
June | 0.58 | 0.46 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 1.14 | 0.00 |
October | 1.70 | 0.78 |
November | 0.46 | 2.44 |
December | 0.21 | 1.46 |
Annual Sum or Average | 7.88 | 0.45 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.70 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 7.18 | 0.00 |
February | 9.49 | 0.00 |
March | 4.79 | 0.00 |
April | 2.29 | 0.00 |
May | 2.81 | 0.00 |
June | 4.56 | 0.00 |
July | 4.33 | 0.00 |
August | 2.28 | 0.00 |
September | 3.03 | 0.00 |
October | 5.47 | 0.00 |
November | 5.85 | 0.00 |
December | 7.57 | 0.00 |
Annual Sum or Average | 59.65 | 0.00 |
Minimum of Months | 2.28 | 0.00 |
Maximum of Months | 9.49 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.154532E+10 | 0.135304E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.132890E+10 | 0.782414E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.154843E+10 | 0.120943E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.223557E+10 | 0.172239E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.394418E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.662477E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.785138E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.842220E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.524292E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.233229E+10 | 72418984.14 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.131715E+10 | 0.132518E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.139670E+10 | 0.636396E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.437898E+11 | 0.304977E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.131715E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.842220E+10 | 0.135304E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.866520E+10 | 0.474810E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.776441E+10 | 0.257669E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.976399E+10 | 0.356642E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.144332E+11 | 0.465454E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.229037E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.329789E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.377880E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.398312E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.262961E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.137986E+11 | 0.491039E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.819544E+10 | 0.552876E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.810542E+10 | 0.226767E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.230524E+12 | 0.105976E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.776441E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.398312E+11 | 0.474810E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.836931E+09 | 0.392147E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.884786E+09 | 0.229004E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.126205E+10 | 0.279722E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.187645E+10 | 74480280.97 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.298845E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.454040E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.537615E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.595999E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.403357E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.218256E+10 | 33404406.54 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.117613E+10 | 0.219865E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.864385E+09 | 0.147406E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.319818E+11 | 0.829305E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.836931E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.595999E+10 | 0.392147E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.143113E+10 | 0.589940E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.136432E+10 | 0.354881E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.166034E+10 | 0.662282E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.199643E+10 | 0.164546E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.275895E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.409734E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.479221E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.532643E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.367095E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.226936E+10 | 0.112333E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.152057E+10 | 0.540921E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.144769E+10 | 0.260119E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.323357E+11 | 0.135295E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.136432E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.532643E+10 | 0.589940E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154532E+10 | 0.00 | 0.109596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130692E+10 | 78389246.28 | 0.633755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130032E+10 | 0.921051E+09 | 0.979642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122573E+10 | 0.378070E+10 | 0.139513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129030E+10 | 0.103319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137589E+10 | 0.208248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147760E+10 | 0.254526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153191E+10 | 0.278404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132280E+10 | 0.157493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125942E+10 | 0.425381E+10 | 58659377.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123493E+10 | 0.307803E+09 | 0.107340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139509E+10 | 5654856.06 | 0.515481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162662E+11 | 0.109546E+12 | 0.247032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154532E+10 | 0.278404E+11 | 0.109596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.866519E+10 | 6973.28 | 0.379848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.740370E+10 | 0.116845E+10 | 0.206135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.762622E+10 | 0.724000E+10 | 0.285314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.724796E+10 | 0.246185E+11 | 0.372364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.748733E+10 | 0.549001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.743511E+10 | 0.934769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.781105E+10 | 0.111394E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.796345E+10 | 0.120082E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.729548E+10 | 0.701056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.741756E+10 | 0.228674E+11 | 0.392831E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.727870E+10 | 0.307454E+10 | 0.442301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.801930E+10 | 0.282267E+09 | 0.181413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.916510E+11 | 0.509209E+12 | 0.847810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.724796E+10 | 6973.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.866519E+10 | 0.120082E+12 | 0.379848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.830607E+09 | 23331601.51 | 0.317639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.728344E+09 | 0.613756E+09 | 0.185494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.770382E+09 | 0.195389E+10 | 0.226575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.744987E+09 | 0.444222E+10 | 60329027.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.789513E+09 | 0.882105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.861376E+09 | 0.147459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.943898E+09 | 0.178376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101484E+10 | 0.201342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.858797E+09 | 0.130901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.792689E+09 | 0.579364E+10 | 27057569.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.729889E+09 | 0.179685E+10 | 0.178090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.780833E+09 | 0.335093E+09 | 0.119399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.984615E+10 | 0.895876E+11 | 0.671737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.728344E+09 | 23331601.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101484E+10 | 0.201342E+11 | 0.317639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143112E+10 | 5315.73 | 0.477852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129342E+10 | 0.311492E+09 | 0.287454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143900E+10 | 0.983150E+09 | 0.536448E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138270E+10 | 0.270613E+10 | 0.133282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145008E+10 | 0.592504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152760E+10 | 0.117389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162719E+10 | 0.144636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170420E+10 | 0.167408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152086E+10 | 0.100687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144716E+10 | 0.389240E+10 | 90989894.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136077E+10 | 0.712448E+09 | 0.438146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142422E+10 | 0.104167E+09 | 0.210697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176083E+11 | 0.676468E+11 | 0.109589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129342E+10 | 5315.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170420E+10 | 0.167408E+11 | 0.477852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.154532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130692E+10 | 0.00 | 0.00 | 0.00 | 21971364.57 | 0.00 | 0.782414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130032E+10 | 0.00 | 0.00 | 0.00 | 0.248111E+09 | 0.00 | 0.120943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122573E+10 | 0.00 | 0.00 | 0.00 | 0.100985E+10 | 0.00 | 0.172239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129030E+10 | 0.00 | 0.00 | 0.00 | 0.265388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137589E+10 | 0.00 | 0.00 | 0.00 | 0.524888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147760E+10 | 0.00 | 0.00 | 0.00 | 0.637378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153191E+10 | 0.00 | 0.00 | 0.00 | 0.689029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132280E+10 | 0.00 | 0.00 | 0.00 | 0.392012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125942E+10 | 0.00 | 0.00 | 0.00 | 0.107287E+10 | 0.00 | 72418984.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123493E+10 | 0.00 | 0.00 | 0.00 | 82216618.33 | 0.00 | 0.132518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139509E+10 | 0.00 | 0.00 | 0.00 | 1613707.85 | 0.00 | 0.636396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162662E+11 | 0.00 | 0.00 | 0.00 | 0.275236E+11 | 0.00 | 0.304977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.122573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154532E+10 | 0.00 | 0.00 | 0.00 | 0.689029E+10 | 0.00 | 0.135304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.866519E+10 | 0.00 | 0.00 | 0.00 | 2215.03 | 0.00 | 0.474810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.740370E+10 | 0.00 | 0.00 | 0.00 | 0.360710E+09 | 0.00 | 0.257669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.762622E+10 | 0.00 | 0.00 | 0.00 | 0.213777E+10 | 0.00 | 0.356642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.724796E+10 | 0.00 | 0.00 | 0.00 | 0.718520E+10 | 0.00 | 0.465454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.748733E+10 | 0.00 | 0.00 | 0.00 | 0.154164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.743511E+10 | 0.00 | 0.00 | 0.00 | 0.255438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.781105E+10 | 0.00 | 0.00 | 0.00 | 0.299769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.796345E+10 | 0.00 | 0.00 | 0.00 | 0.318678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.729548E+10 | 0.00 | 0.00 | 0.00 | 0.190006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.741756E+10 | 0.00 | 0.00 | 0.00 | 0.638100E+10 | 0.00 | 0.491039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.727870E+10 | 0.00 | 0.00 | 0.00 | 0.916736E+09 | 0.00 | 0.552876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.801930E+10 | 0.00 | 0.00 | 0.00 | 86124144.81 | 0.00 | 0.226767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.916510E+11 | 0.00 | 0.00 | 0.00 | 0.138873E+12 | 0.00 | 0.105976E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.724796E+10 | 0.00 | 0.00 | 0.00 | 2215.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.866519E+10 | 0.00 | 0.00 | 0.00 | 0.318678E+11 | 0.00 | 0.474810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.830607E+09 | 0.00 | 0.00 | 0.00 | 6324671.08 | 0.00 | 0.392147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.728344E+09 | 0.00 | 0.00 | 0.00 | 0.156443E+09 | 0.00 | 0.229004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.770382E+09 | 0.00 | 0.00 | 0.00 | 0.491667E+09 | 0.00 | 0.279722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.744987E+09 | 0.00 | 0.00 | 0.00 | 0.113147E+10 | 0.00 | 74480280.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.789513E+09 | 0.00 | 0.00 | 0.00 | 0.219893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.861376E+09 | 0.00 | 0.00 | 0.00 | 0.367902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.943898E+09 | 0.00 | 0.00 | 0.00 | 0.443225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101484E+10 | 0.00 | 0.00 | 0.00 | 0.494515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.858797E+09 | 0.00 | 0.00 | 0.00 | 0.317477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.792689E+09 | 0.00 | 0.00 | 0.00 | 0.138987E+10 | 0.00 | 33404406.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.729889E+09 | 0.00 | 0.00 | 0.00 | 0.446246E+09 | 0.00 | 0.219865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.780833E+09 | 0.00 | 0.00 | 0.00 | 83552147.60 | 0.00 | 0.147406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.984615E+10 | 0.00 | 0.00 | 0.00 | 0.221357E+11 | 0.00 | 0.829305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.728344E+09 | 0.00 | 0.00 | 0.00 | 6324671.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101484E+10 | 0.00 | 0.00 | 0.00 | 0.494515E+10 | 0.00 | 0.392147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.143112E+10 | 0.00 | 0.00 | 0.00 | 1316.24 | 0.00 | 0.589940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129342E+10 | 0.00 | 0.00 | 0.00 | 70907500.91 | 0.00 | 0.354881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143900E+10 | 0.00 | 0.00 | 0.00 | 0.221341E+09 | 0.00 | 0.662282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138270E+10 | 0.00 | 0.00 | 0.00 | 0.613726E+09 | 0.00 | 0.164546E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145008E+10 | 0.00 | 0.00 | 0.00 | 0.130886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152760E+10 | 0.00 | 0.00 | 0.00 | 0.256975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162719E+10 | 0.00 | 0.00 | 0.00 | 0.316501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170420E+10 | 0.00 | 0.00 | 0.00 | 0.362223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152086E+10 | 0.00 | 0.00 | 0.00 | 0.215009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144716E+10 | 0.00 | 0.00 | 0.00 | 0.822193E+09 | 0.00 | 0.112333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136077E+10 | 0.00 | 0.00 | 0.00 | 0.159807E+09 | 0.00 | 0.540921E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142422E+10 | 0.00 | 0.00 | 0.00 | 23470126.94 | 0.00 | 0.260119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176083E+11 | 0.00 | 0.00 | 0.00 | 0.147274E+11 | 0.00 | 0.135295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.129342E+10 | 0.00 | 0.00 | 0.00 | 1316.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170420E+10 | 0.00 | 0.00 | 0.00 | 0.362223E+10 | 0.00 | 0.589940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629223E+10 | 0.00 | 0.00 | 0.20 |
February | 0.210635E+10 | 0.00 | 0.00 | 178302.97 | 618282.39 | 0.346072E+10 | 0.195871E+09 | 0.00 | 0.22 |
March | 0.322351E+10 | 27951350.66 | 0.00 | 1547311.28 | 0.00 | 0.434413E+09 | 0.133784E+10 | 0.00 | 0.29 |
April | 0.131220E+10 | 93663900.61 | 0.00 | 3695778.17 | 2816563.28 | 67678753.07 | 0.206080E+10 | 0.00 | 0.40 |
May | 0.262309E+09 | 0.117679E+10 | 0.00 | 4821858.43 | 0.00 | 0.00 | 0.183111E+10 | 0.00 | 0.40 |
June | 37509404.97 | 0.450406E+10 | 0.00 | 2784712.76 | 0.00 | 0.00 | 0.519907E+09 | 0.00 | 0.28 |
July | 67224.41 | 0.646576E+10 | 0.00 | 391058.45 | 0.00 | 0.00 | 0.147411E+09 | 0.00 | 0.22 |
August | 0.00 | 0.724758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
September | 88004619.97 | 0.306957E+10 | 0.00 | 3701281.43 | 0.00 | 0.00 | 0.128187E+10 | 0.00 | 0.33 |
October | 0.185272E+10 | 0.551035E+09 | 0.00 | 4608121.86 | 1911036.66 | 22133709.33 | 0.292456E+10 | 0.00 | 0.36 |
November | 0.322422E+10 | 511307.96 | 5408488.69 | 1842911.55 | 17855133.65 | 0.454167E+09 | 0.179384E+10 | 1277.39 | 0.29 |
December | 0.335184E+10 | 0.00 | 0.00 | 208836.77 | 0.00 | 0.266766E+10 | 0.259159E+09 | 0.00 | 0.21 |
Annual Sum or Average | 0.169306E+11 | 0.231369E+11 | 5408488.69 | 23780173.67 | 23201015.98 | 0.133990E+11 | 0.123524E+11 | 1277.39 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.335184E+10 | 0.724758E+10 | 5408488.69 | 4821858.43 | 17855133.65 | 0.629223E+10 | 0.292456E+10 | 1277.39 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.447906E+11 | 0.00 | 0.00 | 83977.32 | 0.00 | 0.148304E+11 | 0.205827E+09 | 0.00 | 0.39 |
February | 0.340559E+11 | 0.00 | 0.00 | 3209867.61 | 0.00 | 0.730154E+10 | 0.267881E+10 | 0.00 | 0.42 |
March | 0.239722E+11 | 0.472527E+09 | 0.00 | 13614043.70 | 370542.13 | 0.271446E+09 | 0.101217E+11 | 0.00 | 0.47 |
April | 0.942628E+10 | 0.188967E+10 | 0.00 | 20440307.22 | 846757.33 | 0.00 | 0.104530E+11 | 0.00 | 0.50 |
May | 0.178188E+10 | 0.113353E+11 | 0.00 | 24567039.17 | 16459166.60 | 0.00 | 0.668479E+10 | 0.00 | 0.49 |
June | 0.391167E+09 | 0.353553E+11 | 0.00 | 8795116.96 | 0.218105E+09 | 0.00 | 0.154321E+10 | 0.00 | 0.43 |
July | 10635663.57 | 0.486846E+11 | 0.00 | 2857149.53 | 0.387904E+09 | 0.00 | 0.550219E+09 | 0.00 | 0.41 |
August | 8937782.34 | 0.543426E+11 | 0.00 | 1323108.32 | 0.416140E+09 | 0.00 | 99743005.95 | 0.00 | 0.41 |
September | 0.922271E+09 | 0.228939E+11 | 0.00 | 16098169.87 | 0.139448E+09 | 0.00 | 0.480816E+10 | 0.00 | 0.46 |
October | 0.144450E+11 | 0.453185E+10 | 0.00 | 24676960.55 | 9976406.70 | 13739792.01 | 0.126970E+11 | 0.00 | 0.49 |
November | 0.257162E+11 | 40665625.29 | 0.00 | 12005763.38 | 73037156.83 | 0.106142E+10 | 0.964468E+10 | 0.00 | 0.46 |
December | 0.394717E+11 | 0.00 | 0.00 | 1596871.68 | 0.00 | 0.624417E+10 | 0.169150E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.194993E+12 | 0.179546E+12 | 0.00 | 0.129268E+09 | 0.126229E+10 | 0.297227E+11 | 0.611787E+11 | 0.00 | 0.44 |
Minimum of Months | 8937782.34 | 0.00 | 0.00 | 83977.32 | 0.00 | 0.00 | 99743005.95 | 0.00 | 0.39 |
Maximum of Months | 0.447906E+11 | 0.543426E+11 | 0.00 | 24676960.55 | 0.416140E+09 | 0.148304E+11 | 0.126970E+11 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.405902E+10 | 0.00 | 0.00 | 684493.68 | 0.00 | 0.122579E+10 | 0.633906E+09 | 0.00 | 0.42 |
February | 0.275280E+10 | 75940.79 | 0.00 | 2846855.32 | 0.00 | 0.638240E+09 | 0.129316E+10 | 0.00 | 0.55 |
March | 0.128063E+10 | 89584586.80 | 0.00 | 5762679.14 | 0.00 | 66191641.81 | 0.291487E+10 | 0.00 | 0.69 |
April | 0.587328E+09 | 0.306037E+09 | 0.00 | 4337049.25 | 0.00 | 18257147.88 | 0.180295E+10 | 0.00 | 0.68 |
May | 0.141789E+09 | 0.140369E+10 | 0.00 | 3188201.53 | 0.00 | 0.00 | 0.925124E+09 | 0.00 | 0.61 |
June | 28912858.02 | 0.385637E+10 | 0.00 | 1479122.96 | 0.00 | 0.00 | 0.258499E+09 | 0.00 | 0.49 |
July | 0.00 | 0.538798E+10 | 0.00 | 142672.23 | 0.00 | 0.00 | 45902233.85 | 0.00 | 0.41 |
August | 0.00 | 0.608941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 36093099.84 | 0.290332E+10 | 0.00 | 2460801.63 | 0.00 | 0.00 | 0.701300E+09 | 0.00 | 0.54 |
October | 0.753158E+09 | 0.720534E+09 | 0.00 | 8387968.26 | 0.00 | 2073860.47 | 0.288943E+10 | 0.00 | 0.74 |
November | 0.144802E+10 | 53073234.39 | 0.00 | 7442904.57 | 2711319.10 | 55147786.90 | 0.312372E+10 | 0.00 | 0.69 |
December | 0.287184E+10 | 2425485.60 | 0.00 | 2905338.70 | 0.00 | 0.444201E+09 | 0.189228E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.139596E+11 | 0.208125E+11 | 0.00 | 39638087.27 | 2711319.10 | 0.244991E+10 | 0.164811E+11 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.405902E+10 | 0.608941E+10 | 0.00 | 8387968.26 | 2711319.10 | 0.122579E+10 | 0.312372E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.262853E+10 | 0.00 | 0.00 | 78996.11 | 0.00 | 0.285408E+10 | 0.166083E+09 | 0.00 | 0.40 |
February | 0.198028E+10 | 107449.25 | 0.00 | 1100245.16 | 0.00 | 0.168381E+10 | 0.660319E+09 | 0.00 | 0.51 |
March | 0.171200E+10 | 55757009.18 | 0.00 | 2050355.32 | 0.00 | 0.328275E+09 | 0.160854E+10 | 0.00 | 0.62 |
April | 0.912640E+09 | 0.168642E+09 | 0.00 | 1769608.48 | 468707.60 | 73443139.12 | 0.111663E+10 | 0.00 | 0.66 |
May | 0.261665E+09 | 0.101347E+10 | 0.00 | 1831000.93 | 0.00 | 0.00 | 0.914609E+09 | 0.00 | 0.65 |
June | 59757058.27 | 0.338866E+10 | 0.00 | 783326.13 | 0.00 | 0.00 | 0.208177E+09 | 0.00 | 0.49 |
July | 8167496.88 | 0.477106E+10 | 0.00 | 293895.96 | 0.00 | 0.00 | 0.192242E+09 | 0.00 | 0.43 |
August | 0.00 | 0.547052E+10 | 0.00 | 30598.42 | 0.00 | 0.00 | 5724961.61 | 0.00 | 0.41 |
September | 0.117583E+09 | 0.243246E+10 | 0.00 | 1633195.75 | 0.00 | 0.00 | 0.657860E+09 | 0.00 | 0.55 |
October | 0.113296E+10 | 0.533921E+09 | 0.00 | 4461179.61 | 0.00 | 52871142.91 | 0.208113E+10 | 0.00 | 0.71 |
November | 0.199852E+10 | 16520393.98 | 0.00 | 3275874.09 | 3762779.80 | 0.148452E+09 | 0.200592E+10 | 0.00 | 0.65 |
December | 0.280002E+10 | 0.00 | 0.00 | 773059.25 | 0.00 | 0.116752E+10 | 0.731345E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.136121E+11 | 0.178511E+11 | 0.00 | 18081335.21 | 4231487.40 | 0.630845E+10 | 0.103486E+11 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 30598.42 | 0.00 | 0.00 | 5724961.61 | 0.00 | 0.40 |
Maximum of Months | 0.280002E+10 | 0.547052E+10 | 0.00 | 4461179.61 | 3762779.80 | 0.285408E+10 | 0.208113E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |