Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2020-06-03 19:13:11
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1438.19 | 626.94 | 626.94 |
Net Site Energy | 1438.19 | 626.94 | 626.94 |
Total Source Energy | 3108.81 | 1355.20 | 1355.20 |
Net Source Energy | 3108.81 | 1355.20 | 1355.20 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 593.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 66.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 266.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 38.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 159.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 18.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 100.67 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 744.03 | 694.16 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 593.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 66.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 266.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 38.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 159.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 18.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 100.67 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 98.38 | 302.60 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 92.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 324.34 | 302.60 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 98.38 | 302.60 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 92.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 324.34 | 302.60 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 744.028 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 744.028 | 100.00 |
Total On-Site and Utility Electric Sources | 744.028 | 100.00 |
Total Electricity End Uses | 744.028 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 18.83 | 3.75 |
Air to Air Heat Recovery for Heating | 483.37 | 96.25 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 502.19 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2580.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 6.69 |
Skylight-Roof Ratio [%] | 0.29 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 4.6739 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 11.3021 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 11.3021 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 11.3021 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 9.0417 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 10.1926 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 10.1926 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-15:00 | 09-JAN-07:10 | - | - | - | 07-APR-11:20 |
Heating | 0.00 | 300867.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 32463.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19245.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7070.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1406.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 70927.31 | 302727.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 300867.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 32463.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19245.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7070.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 1406.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 643.35 | 0.00 | 0.00 | 0.00 |
Cooling | 209.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 844.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 122.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 615.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 505.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 59.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 109.13 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2356.34 | 752.47 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 280.45 | 0.00 | 0.00 | 0.00 |
Cooling | 91.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 367.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 220.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 26.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 47.57 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1027.18 | 328.02 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 280.45 | 0.00 | 0.00 | 0.00 |
Cooling | 91.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 367.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 220.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 26.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 47.57 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1027.18 | 328.02 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.50 |
CORE_RETAIL DIRECT AIR | 6.51 |
POINT_OF_SALE DIRECT AIR | 1.01 |
FRONT_RETAIL DIRECT AIR | 0.778631 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 2.75 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 2.75 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 78159.25 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 47583.22 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 261615.20 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 33325.75 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 28269.85 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.50 | 1.50 | 1.50 | 1.50 | 1.57 | 1.57 | 1.00 | 0.954724 | 1.57 |
PSZ-AC:2 | 6.51 | 6.51 | 6.51 | 6.51 | 6.77 | 6.77 | 1.00 | 0.962251 | 6.77 |
PSZ-AC:3 | 1.01 | 1.01 | 1.01 | 1.01 | 1.02 | 1.02 | 1.00 | 0.983592 | 1.02 |
PSZ-AC:4 | 0.778631 | 0.778631 | 0.778631 | 0.778631 | 0.778631 | 0.778631 | 1.00 | 1.00 | 0.778631 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.57 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 6.77 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.02 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 0.778631 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.57 | 1.57 | 1.57 | 1.04 | 29929.44 | 47583.22 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 6.77 | 6.77 | 6.77 | 4.47 | 145380.57 | 261615.20 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 0.676164 | 19185.52 | 33325.75 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.778631 | 0.778631 | 0.778631 | 0.778631 | 15486.62 | 28269.85 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.57 | 0.785000 | 1.05 | 27959.40 | 29929.44 | 14964.72 | 14964.72 | 0.750252 | 0.750250 | 0.750250 | 0.750250 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 6.77 | 3.38 | 4.51 | 137030.49 | 145380.57 | 72690.29 | 72690.29 | 0.714219 | 0.714220 | 0.714220 | 0.714220 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.02 | 0.512245 | 0.682993 | 17876.13 | 19185.52 | 9592.76 | 9592.76 | 0.755987 | 0.755990 | 0.755990 | 0.755990 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 0.778630 | 0.389315 | 0.519087 | 14506.04 | 15486.62 | 7743.31 | 7743.31 | 0.736989 | 0.736990 | 0.736990 | 0.736990 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.57 | 1679.98 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 6.77 | 11397.85 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1134.27 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.778631 | 862.07 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PSZ-AC:2 OA HEAT RECOVERY | 1.89 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 65 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 6.69 | 10 | 14 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 4.674 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 12.744 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 11.302 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 14.532 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 11.302 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 32.822 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 11.302 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 14.532 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 9.042 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.042 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 1775.580 | 4.674 | 28.946 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1775.580 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 18088.827 | 11.302 | 69.994 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18088.827 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 1704.471 | 11.302 | 69.994 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1704.471 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 1704.471 | 11.302 | 69.994 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1704.471 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 108.500 | 9.042 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.500 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.4290 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1626 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.3245E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1876 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1876 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.3083 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.163 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.071 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 30.74 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.255 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.255 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.166 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
21 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
22 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
23 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
24 | 9 | 0.21485751E-14 | -0.22894401E-15 | -0.17283669E-09 | -0.31350098E-16 |
25 | 8 | 0.25115787E-07 | 0.58773152E-13 | 0.41104347E-03 | -0.28557513E-09 |
26 | 7 | -0.13231082E-01 | 0.29616277E-08 | -0.24509747E-01 | 0.15044224E-03 |
27 | 6 | 0.43223401 | 0.10185882E-05 | 0.49492235 | -0.50646574E-02 |
28 | 5 | -5.4528708 | 0.37659386E-04 | -4.6163278 | 0.66436381E-01 |
29 | 4 | 34.162830 | 0.30532126E-03 | 22.123982 | -0.43752457 |
30 | 3 | -113.69342 | 0.66011806E-03 | -56.975280 | 1.5508408 |
31 | 2 | 199.57555 | 0.36866733E-03 | 79.115267 | -2.9395356 |
32 | 1 | -172.06709 | 0.39096546E-04 | -55.617513 | 2.7614060 |
33 | 0 | 57.057407 | 0.22087022E-06 | 15.500460 | |
34 | 7 | -0.26050204E-08 | -0.12788232E-14 | 0.72012043E-14 | -0.10759993E-15 |
35 | 6 | 0.46268903E-05 | 0.31105256E-08 | 0.31927482E-02 | -0.26783447E-04 |
36 | 5 | -0.32814218E-03 | 0.18406109E-05 | -0.22388816 | 0.19575942E-02 |
37 | 4 | 0.75185520E-02 | 0.83742768E-04 | 4.8322704 | -0.45291172E-01 |
38 | 3 | -0.65932714E-01 | 0.66563724E-03 | -38.036808 | 0.39882388 |
39 | 2 | 0.23398852 | 0.11069120E-02 | 116.51391 | -1.4183400 |
40 | 1 | -0.33764803 | 0.33706295E-03 | -143.92494 | 2.0493298 |
41 | 0 | 0.16460056 | 0.81667941E-05 | 60.838472 | |
42 | 7 | -0.13230309E-07 | 0.37916998E-14 | -0.15049525E-13 | 0.22417729E-15 |
43 | 6 | 0.18547234E-05 | 0.66099219E-09 | 0.32028734E-02 | -0.26868386E-04 |
44 | 5 | -0.87212401E-04 | 0.37903059E-06 | -0.22446311 | 0.19626693E-02 |
45 | 4 | 0.16961484E-02 | 0.16963791E-04 | 4.8418364 | -0.45383137E-01 |
46 | 3 | -0.13893192E-01 | 0.13302771E-03 | -38.090796 | 0.39942071 |
47 | 2 | 0.47900219E-01 | 0.21836098E-03 | 116.61891 | -1.4197447 |
48 | 1 | -0.68200360E-01 | 0.65422817E-04 | -143.98673 | 2.0503454 |
49 | 0 | 0.33018262E-01 | 0.15509510E-05 | 60.838472 | |
50 | 7 | -0.22533252E-08 | -0.83022561E-15 | 0.55998268E-14 | -0.82362556E-16 |
51 | 6 | 0.52906431E-05 | 0.35900773E-08 | 0.31908013E-02 | -0.26767116E-04 |
52 | 5 | -0.37780547E-03 | 0.21247575E-05 | -0.22377752 | 0.19566176E-02 |
53 | 4 | 0.86735859E-02 | 0.96698006E-04 | 4.8304276 | -0.45273459E-01 |
54 | 3 | -0.76115433E-01 | 0.76875592E-03 | -38.026399 | 0.39870883 |
55 | 2 | 0.27020106 | 0.12787018E-02 | 116.49365 | -1.4180690 |
56 | 1 | -0.38995133 | 0.38940098E-03 | -143.91302 | 2.0491338 |
57 | 0 | 0.19010978 | 0.94626858E-05 | 60.838472 | |
58 | 7 | -0.22533252E-08 | -0.83022561E-15 | 0.55998268E-14 | -0.82362556E-16 |
59 | 6 | 0.52906431E-05 | 0.35900773E-08 | 0.31908013E-02 | -0.26767116E-04 |
60 | 5 | -0.37780547E-03 | 0.21247575E-05 | -0.22377752 | 0.19566176E-02 |
61 | 4 | 0.86735859E-02 | 0.96698006E-04 | 4.8304276 | -0.45273459E-01 |
62 | 3 | -0.76115433E-01 | 0.76875592E-03 | -38.026399 | 0.39870883 |
63 | 2 | 0.27020106 | 0.12787018E-02 | 116.49365 | -1.4180690 |
64 | 1 | -0.38995133 | 0.38940098E-03 | -143.91302 | 2.0491338 |
65 | 0 | 0.19010978 | 0.94626858E-05 | 60.838472 | |
66 | 7 | -0.13537006E-08 | -0.18318356E-15 | 0.98030882E-14 | -0.13575894E-15 |
67 | 6 | 0.86108132E-05 | 0.59308231E-08 | 0.31812743E-02 | -0.26687195E-04 |
68 | 5 | -0.62289903E-03 | 0.35162463E-05 | -0.22323598 | 0.19518377E-02 |
69 | 4 | 0.14350116E-01 | 0.16012171E-03 | 4.8214069 | -0.45186747E-01 |
70 | 3 | -0.12607627 | 0.12739000E-02 | -37.975436 | 0.39814552 |
71 | 2 | 0.44774849 | 0.21199048E-02 | 116.39445 | -1.4167422 |
72 | 1 | -0.64630340 | 0.64631860E-03 | -143.85462 | 2.0481739 |
73 | 0 | 0.31511470 | 0.15583169E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.29_SHGC_0.4 | 30 | 1 | VerySmooth | 1.647 | 0.395 | 0.315 | 0.441 |
2 | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | 31 | 1 | VerySmooth | 2.500 | 0.549 | 0.472 | 0.551 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.26414E-002 | 0.31435 | 0.48879 | 0.48879 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.79131E-002 | 0.47116 | 0.33239 | 0.33239 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.12208 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 8 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1915 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
31 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
32 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
33 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
34 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
39 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
40 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
42 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
43 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
44 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
45 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
46 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
47 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
48 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
49 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
50 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
52 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
54 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
58 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
59 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
60 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
62 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
63 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
64 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
65 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 17101.83228 | 20522.19873 | 1.24910 | 1.49892 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27032E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 26927.33111 | 32312.79733 | 1.18642 | 1.42371 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 74195.75007 | 89034.90009 | 5.42505 | 6.51006 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27032E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 61252.54699 | 73503.05639 | 2.66487 | 3.19784 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 11296.98336 | 13556.38003 | 0.83973 | 1.00768 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27032E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 13038.54744 | 15646.25693 | 0.57660 | 0.69192 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 8473.25933 | 10167.91120 | 0.64886 | 0.77863 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27032E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 13037.81184 | 15645.37421 | 0.57657 | 0.69188 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10000 | 1.27032E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 65118.91993 | 78142.70392 | 2.28972 | 2.74766 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:40:00 | -32.70000 | 1.83376E-004 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 19594.29 | 1.57000 | 1.57000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 45917.83 | 1.42371 | 1.42371 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 90617.71 | 6.76545 | 6.76545 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 188289.28 | 3.19784 | 3.19784 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 14388.48 | 1.02449 | 1.02449 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 26355.83 | 0.69192 | 0.69192 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 11242.59 | 0.77863 | 0.77863 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 26354.95 | 0.69188 | 0.69188 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.49892 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.51006 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00768 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.77863 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.74766 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.74766 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 78159.25101 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.49892 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.49892 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.49892 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.49892 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.57000 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.57000 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.95472 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.51006 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.51006 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.51006 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 6.51006 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.76545 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 6.76545 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.96225 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00768 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00768 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00768 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00768 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02449 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02449 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 0.98359 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.77863 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.77863 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.77863 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.77863 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77863 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.77863 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.57000 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 6.76545 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.02449 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.77863 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.57000 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.57000 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.57000 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.57000 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03620 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.57000 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78500 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04667 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27959.39625 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29929.44000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14964.72000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 14964.72000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75025 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75025 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75025 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75025 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29929.44000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 47583.22036 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.57000 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1679.97670 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 47583.22036 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.76545 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | HeatExchanger:AirToAir:SensibleAndLatent | PSZ-AC:2 OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.89021 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 6.76545 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 6.76545 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.76545 |
74 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.46520 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 6.76545 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.38273 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.51030 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 137030.49021 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 145380.57000 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 72690.28500 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 72690.28500 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71422 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71422 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71422 |
85 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71422 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 145380.57000 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 261615.19951 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
89 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 6.76545 |
91 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 11397.85046 |
92 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 261615.19951 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02449 |
94 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02449 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02449 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02449 |
98 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67616 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02449 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51225 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68299 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17876.12912 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19185.52000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9592.76000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9592.76000 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75599 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75599 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75599 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75599 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19185.52000 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33325.75067 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
113 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02449 |
115 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1134.27328 |
116 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 33325.75067 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77863 |
118 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77863 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77863 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77863 |
122 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77863 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.77863 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.38932 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.51909 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 14506.03877 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 15486.62000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7743.31000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 7743.31000 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73699 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73699 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73699 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73699 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15486.62000 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28269.85415 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.77863 |
139 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 862.06784 |
140 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28269.85415 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 28696.5 | 11.43 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 140057.4 | 12.81 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 18381.2 | 115.95 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 14874.8 | 167.08 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 25 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.163 | 0.156 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 3.245E-002 | 3.220E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 1593.79 | 1600.48 | 1593.79 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | N/A | 2.500 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
32 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | N/A | 2.500 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
33 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | N/A | 2.500 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
34 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | N/A | 2.500 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | N/A | 2.500 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | N/A | 2.500 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | N/A | 2.500 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | N/A | 2.500 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
40 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.4 | N/A | 1.647 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.188 | 0.179 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.4 | N/A | 1.647 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.188 | 0.179 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
56 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
57 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
58 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.4 | N/A | 1.647 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.308 | 0.287 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 8 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 0.2689400178 | 0.5292745481 | Pass | Pass | 0.2404276445 | 0.6838478411 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 8.0782487560E-002 | 0.2712136829 | Pass | Pass | 6.7203429008E-002 | 0.2013159855 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 0.1896224414 | 0.5240022894 | Pass | Pass | 0.5967815876 | 2.3386246426 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 0.2556572772 | 0.5842433339 | Pass | Pass | 0.6713915241 | 3.7949123889 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1076466272 | 0.1791071462 | Pass | Pass | 0.1563797181 | 0.8909727105 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 1600.48 | 1593.79 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.163 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.032 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.188 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.188 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.308 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 2.500 | 0.549 | 0.551 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 2.500 | 0.549 | 0.551 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 2.500 | 0.549 | 0.551 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 2.500 | 0.549 | 0.551 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 2.500 | 0.549 | 0.551 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 2.500 | 0.549 | 0.551 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 2.500 | 0.549 | 0.551 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.44_SHGC_0.55 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 2.500 | 0.549 | 0.551 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.29_SHGC_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.647 | 0.395 | 0.441 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.29_SHGC_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.647 | 0.395 | 0.441 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.29_SHGC_0.4 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 1.647 | 0.395 | 0.441 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 90.63 | 1.710 | 0.406 | 0.449 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 90.63 | 1.710 | 0.406 | 0.449 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 4.6739 | 379.89 | 1775.58 | LightsWired | BLDG_LIGHT_BACK_SCH | 55.08 | 168.00 | 53.35 | 0.0000 | Y | 17.78 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 11.3021 | 1600.48 | 18088.83 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 61.12 | 0.0000 | Y | 207.55 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 11.3021 | 150.81 | 1704.47 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 65.23 | 0.0000 | Y | 20.87 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 11.3021 | 150.81 | 1704.47 | LightsWired | BLDG_LIGHT_FRONT_SCH | 67.15 | 168.00 | 63.20 | 0.0000 | Y | 20.22 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 9.0417 | 12.00 | 108.50 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 57.54 | 168.00 | 4.00 | 0.0000 | Y | 0.08 |
Interior Lighting Total | 10.1926 | 2293.99 | 23381.85 | 266.50 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Continuous/Off | 0.17 | 18088.83 | 3118.51 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 316.30 | AstronomicalClock | - | 42.55 | 42.55 | 2.53 | |
EXTERIOR_LIGHTS_B | 3054.90 | AstronomicalClock | - | 83.52 | 63.04 | 36.15 | |
Exterior Lighting Total | 3371.20 | 38.67 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 29929.44 | 22454.56 | 7474.88 | 0.75 | 3.80 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 145380.57 | 103833.71 | 41546.86 | 0.71 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 19185.52 | 14504.06 | 4681.46 | 0.76 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 15486.62 | 11413.48 | 4073.14 | 0.74 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 28696.5 | 11.43 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 140057.4 | 12.81 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 18381.2 | 115.95 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 14874.8 | 167.08 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 78159.25 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 47583.22 | 0.81 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 261615.20 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 33325.75 | 0.81 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28269.85 | 0.81 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.75 | 2940.13 | 1070.05 | 1.00 | 1.26 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:40:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.57 | 1679.98 | 1070.05 | 1.00 | 1.35 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 6.77 | 11397.85 | 1684.71 | 1.00 | 1.16 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1134.27 | 1107.16 | 1.00 | 1.40 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.78 | 862.07 | 1107.16 | 1.00 | 1.47 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 17101.83 | 20522.20 | 54.02 | 1.249 | 1.499 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01072 | 20.92 | 0.01270 | 0.232 | 0.00 |
CORE_RETAIL | 74195.75 | 89034.90 | 55.63 | 5.425 | 6.510 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01058 | 20.92 | 0.01270 | 1.890 | 0.00 |
POINT_OF_SALE | 11296.98 | 13556.38 | 89.89 | 0.840 | 1.008 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00915 | 20.92 | 0.01270 | 0.178 | 0.00 |
FRONT_RETAIL | 8473.26 | 10167.91 | 67.42 | 0.649 | 0.779 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00918 | 29.79 | 0.01270 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 29.92 | 100.00 | 0.00001 | 30.10 | 0.01270 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 26927.33 | 32312.80 | 85.06 | 1.186 | 1.424 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00783 | -32.70 | 0.00018 | 0.232 | 0.00 |
CORE_RETAIL | 61252.55 | 73503.06 | 45.93 | 2.665 | 3.198 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00775 | -32.70 | 0.00018 | 1.890 | 0.00 |
POINT_OF_SALE | 13038.55 | 15646.26 | 103.75 | 0.577 | 0.692 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00789 | -32.70 | 0.00018 | 0.178 | 0.00 |
FRONT_RETAIL | 13037.81 | 15645.37 | 103.74 | 0.577 | 0.692 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00789 | -32.70 | 0.00018 | 0.178 | 0.00 |
FRONT_ENTRY | 65118.92 | 78142.70 | 6511.89 | 2.290 | 2.748 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:40:00 | 16.00 | 15.83 | 0.00540 | -32.70 | 0.00018 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.57 | 1.57 | 1.42 | 1.42 | 1.5700 | 1.4989 | 1.5700 | 0.9547 | 1.0000 |
PSZ-AC:2 | 6.77 | 6.77 | 3.20 | 3.20 | 6.7654 | 6.5101 | 6.7654 | 0.9623 | 1.0000 |
PSZ-AC:3 | 1.02 | 1.02 | 0.69 | 0.69 | 1.0245 | 1.0077 | 1.0245 | 0.9836 | 1.0000 |
PSZ-AC:4 | 0.78 | 0.78 | 0.69 | 0.69 | 0.7786 | 0.7786 | 0.7786 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 78159.251 | 78159.251 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:40:00 | 78159.25 | 78159.25 | 2.747660 | 15.57 | 9.65 | 0.00536989 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 15.83 | 0.00539678 | 46.4427 | 78142.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 14964.720 | 0.000 | 1.570000 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 14964.72 | 10621.06 | 1.570000 | 23.56 | 17.50 | 0.01056798 | 12.80 | 11.72 | 0.00850000 | 21.71 | 0.01270324 | 18.57 | 14.7495 | 23.88 | 0.01072341 | 55.5114 | 17101.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 47583.220 | 47583.220 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 47583.22 | 47583.22 | 1.570002 | 12.19 | 9.48 | 0.00658502 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 14.7494 | 21.11 | 0.00782850 | 48.1857 | 26927.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 72690.285 | 0.000 | 6.765450 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 72690.29 | 54884.96 | 6.765450 | 25.85 | 18.14 | 0.01043450 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 27.9392 | 23.88 | 0.01057587 | 54.7608 | 74195.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 261615.200 | 261615.200 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 261615.20 | 261615.20 | 6.765449 | -10.78 | -10.78 | 0.00327814 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 27.9392 | 21.11 | 0.00775169 | 47.7181 | 61252.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 9592.760 | 0.000 | 1.024490 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 9592.76 | 7944.14 | 1.024490 | 24.93 | 17.22 | 0.00966229 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01270324 | 21.04 | 17.3853 | 23.89 | 0.00914600 | 47.4521 | 11128.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 33325.751 | 33325.751 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33325.75 | 33325.75 | 1.024490 | 7.15 | 6.38 | 0.00590293 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 17.3853 | 21.11 | 0.00788560 | 48.5323 | 13038.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 7743.310 | 0.000 | 0.778630 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 7743.31 | 6146.32 | 0.778630 | 25.29 | 17.61 | 0.00999184 | 12.80 | 11.72 | 0.00850000 | 30.00 | 0.01270324 | 21.07 | 22.8749 | 23.89 | 0.00918373 | 47.6426 | 8448.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 28269.854 | 28269.854 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28269.85 | 28269.85 | 0.778631 | 7.15 | 6.38 | 0.00590280 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 22.8748 | 21.11 | 0.00788559 | 48.5322 | 13037.81 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 78159.251 | 78159.251 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 2.747660 | 3.17059342 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:40:00 | 78159.25 | 78159.25 | 1.0000 | 3.17059342 | 2.747660 | 15.57 | 9.65 | 0.00536989 | 29235.6 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 78159.25 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 15.83 | 0.00539678 | 15.83 | 0.00539678 | 46.4427 | 78142.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14964.720 | 0.000 | 1.570000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4853 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 14964.72 | 10621.06 | 1.0000 | 1.81166202 | 1.570000 | 23.56 | 17.50 | 0.01056798 | 50570.2 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14964.72 | 21.71 | 0.01270324 | 18.57 | 0.23156651 | 14.7495 | 23.88 | 0.01019855 | 23.88 | 0.01072341 | 55.5114 | 17101.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 47583.220 | 47583.220 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.570002 | 1.81166471 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 47583.22 | 47583.22 | 1.0000 | 1.81166471 | 1.570002 | 12.19 | 9.48 | 0.00658502 | 28861.9 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47583.22 | -32.70 | 0.00018338 | -32.70 | 0.23156651 | 14.7494 | 20.90 | 0.00782850 | 21.11 | 0.00782850 | 48.1857 | 26927.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 72690.285 | 0.000 | 6.765450 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2372 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 72690.29 | 54884.96 | 1.0000 | 7.80682092 | 6.765450 | 25.85 | 18.14 | 0.01043450 | 52570.9 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 72690.29 | 30.10 | 0.01270324 | 21.10 | 1.89021192 | 27.9392 | 23.89 | 0.00938831 | 23.88 | 0.01057587 | 54.7608 | 74195.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 261615.200 | 261615.200 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 6.765449 | 7.80681941 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 261615.20 | 261615.20 | 1.0000 | 7.80681941 | 6.765449 | -10.78 | -10.78 | 0.00327814 | -2698.7 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 261615.20 | -32.70 | 0.00018338 | -32.70 | 1.89021192 | 27.9392 | 20.91 | 0.00775169 | 21.11 | 0.00775169 | 47.7181 | 61252.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9592.760 | 0.000 | 1.024490 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8017 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 9592.76 | 7944.14 | 1.0000 | 1.18218448 | 1.024490 | 24.93 | 17.22 | 0.00966229 | 49667.2 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9592.76 | 29.89 | 0.01270324 | 21.04 | 0.17811053 | 17.3853 | 23.89 | 0.00902097 | 23.89 | 0.00914600 | 47.4521 | 11128.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33325.751 | 33325.751 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.024490 | 1.18218471 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33325.75 | 33325.75 | 1.0000 | 1.18218471 | 1.024490 | 7.15 | 6.38 | 0.00590293 | 22025.6 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33325.75 | -32.70 | 0.00018338 | -32.70 | 0.17811053 | 17.3853 | 20.96 | 0.00788560 | 21.11 | 0.00788560 | 48.5323 | 13038.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 7743.310 | 0.000 | 0.778630 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4143 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 7743.31 | 6146.32 | 1.0000 | 0.89848051 | 0.778630 | 25.29 | 17.61 | 0.00999184 | 50870.6 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7743.31 | 30.00 | 0.01270324 | 21.07 | 0.17811053 | 22.8749 | 23.89 | 0.00918455 | 23.89 | 0.00918373 | 47.6426 | 8448.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28269.854 | 28269.854 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.778631 | 0.89848138 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28269.85 | 28269.85 | 1.0000 | 0.89848138 | 0.778631 | 7.15 | 6.38 | 0.00590280 | 22024.5 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28269.85 | -32.70 | 0.00018338 | -32.70 | 0.17811053 | 22.8748 | 20.96 | 0.00788559 | 21.11 | 0.00788559 | 48.5322 | 13037.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.57 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 1.89 | 6.77 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.02 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 2976.33 | 4017.33 | 2569.67 |
CORE_RETAIL | 2576.00 | 3257.00 | 1643.83 |
POINT_OF_SALE | 2844.33 | 3275.00 | 1777.17 |
FRONT_RETAIL | 2929.00 | 3508.83 | 2037.17 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3573.00 | 4036.83 | 2580.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 66.83 | 0.50 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 45.83 | 38.33 | 0.00 | 0.00 |
FRONT_RETAIL | 62.83 | 4.33 | 0.00 | 0.00 |
FRONT_ENTRY | 353.17 | 0.00 | 0.00 | 0.00 |
Facility | 441.33 | 42.83 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.44 | 61.34 | 2317.33 | 0.505 | 0.030 | 0.000 | 0.000 |
CORE_RETAIL | 128.26 | 258.43 | 9762.95 | 0.819 | 0.006 | 0.000 | 0.000 |
POINT_OF_SALE | 12.09 | 24.35 | 919.94 | 1.024 | 0.033 | 0.000 | 0.000 |
FRONT_RETAIL | 12.09 | 24.35 | 919.94 | 0.707 | 0.033 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.44 | 61.34 | 2317.33 | 0.352 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.26 | 258.43 | 9762.95 | 0.682 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.09 | 24.35 | 919.94 | 0.682 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.09 | 24.35 | 919.94 | 0.682 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 11 | 11 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 744.03 | 2265.44 | 19-MAR-06:40 | 70927.31 | 29-JUN-16:00 |
Electricity:Building | 460.80 | 2265.44 | 01-JAN-00:10 | 31292.41 | 02-JAN-16:30 |
Electricity:Zone:BACK_SPACE | 67.55 | 535.60 | 01-JAN-00:10 | 4001.15 | 02-JAN-09:10 |
InteriorLights:Electricity | 266.50 | 493.85 | 01-JAN-00:10 | 20551.52 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:BACK_SPACE | 17.78 | 81.78 | 01-JAN-00:10 | 1249.73 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 266.50 | 493.85 | 01-JAN-00:10 | 20551.52 | 02-JAN-16:30 |
Electricity:Zone:CORE_RETAIL | 291.47 | 1109.80 | 01-JAN-00:10 | 20919.52 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 207.55 | 344.55 | 01-JAN-00:10 | 16279.94 | 02-JAN-16:30 |
Electricity:Zone:POINT_OF_SALE | 73.56 | 512.89 | 01-JAN-00:10 | 4446.74 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 20.87 | 32.47 | 01-JAN-00:10 | 1534.02 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 28.13 | 104.57 | 01-JAN-00:10 | 1922.42 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 20.22 | 32.47 | 01-JAN-00:10 | 1485.24 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 0.08 | 2.58 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 0.08 | 2.58 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 |
InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.77 | 453.82 | 01-JAN-00:10 | 2751.42 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 83.93 | 765.25 | 01-JAN-00:10 | 4639.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.69 | 480.42 | 01-JAN-00:10 | 2912.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.91 | 72.11 | 01-JAN-00:10 | 437.18 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 744.03 | 2265.44 | 19-MAR-06:40 | 70927.31 | 29-JUN-16:00 |
ElectricityPurchased:Plant | 744.03 | 2265.44 | 19-MAR-06:40 | 70927.31 | 29-JUN-16:00 |
Cogeneration:ElectricityPurchased | 744.03 | 2265.44 | 19-MAR-06:40 | 70927.31 | 29-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 744.03 | 2265.44 | 19-MAR-06:40 | 70927.31 | 29-JUN-16:00 |
ElectricityNet:Plant | 744.03 | 2265.44 | 19-MAR-06:40 | 70927.31 | 29-JUN-16:00 |
Cogeneration:ElectricityNet | 744.03 | 2265.44 | 19-MAR-06:40 | 70927.31 | 29-JUN-16:00 |
Electricity:HVAC | 244.56 | 0.00 | 02-JAN-21:10 | 40941.84 | 30-JUN-15:00 |
Fans:Electricity | 159.55 | 0.00 | 02-JAN-21:10 | 14722.83 | 01-JAN-09:10 |
General:Fans:Electricity | 159.55 | 0.00 | 02-JAN-21:10 | 14722.83 | 01-JAN-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 66.14 | 0.00 | 01-JAN-00:10 | 32463.97 | 29-JUN-16:00 |
ExteriorLights:Electricity | 38.67 | 0.00 | 01-JAN-08:20 | 3371.20 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 38.67 | 0.00 | 01-JAN-08:20 | 3371.20 | 01-JAN-06:10 |
HeatRecovery:Electricity | 18.87 | 0.00 | 01-JAN-00:10 | 1406.23 | 02-JAN-07:40 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 694.16 | 1860.00 | 26-JAN-05:40 | 302727.41 | 09-JAN-07:10 |
Gas:Plant | 100.67 | 1860.00 | 01-JAN-07:50 | 6347.47 | 24-FEB-12:10 |
WaterSystems:Gas | 100.67 | 1860.00 | 01-JAN-07:50 | 6347.47 | 24-FEB-12:10 |
Water Heater:WaterSystems:Gas | 100.67 | 1860.00 | 01-JAN-07:50 | 6347.47 | 24-FEB-12:10 |
Gas:HVAC | 593.49 | 0.00 | 01-JAN-20:10 | 300867.41 | 09-JAN-07:10 |
Heating:Gas | 593.49 | 0.00 | 01-JAN-20:10 | 300867.41 | 09-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 07-APR-11:20 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 07-APR-11:20 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 07-APR-11:20 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 07-APR-11:20 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 07-APR-11:20 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 07-APR-11:20 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 07-APR-11:20 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 07-APR-11:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1816.82 | 0.00 | 02-JAN-21:10 | 340820.99 | 09-JAN-07:10 |
EnergyTransfer:Building | 587.57 | 0.00 | 02-JAN-21:10 | 142789.59 | 01-JAN-07:10 |
EnergyTransfer:Zone:BACK_SPACE | 100.09 | 0.00 | 01-JAN-00:40 | 48138.17 | 25-DEC-07:20 |
Heating:EnergyTransfer | 261.86 | 0.00 | 02-JAN-21:10 | 142789.59 | 01-JAN-07:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 65.98 | 0.00 | 01-JAN-00:40 | 48138.17 | 25-DEC-07:20 |
Cooling:EnergyTransfer | 325.70 | 0.00 | 01-JAN-00:10 | 63752.22 | 30-JUN-14:50 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 34.11 | 0.00 | 01-JAN-00:10 | 9364.17 | 30-JUN-15:00 |
EnergyTransfer:Zone:CORE_RETAIL | 259.48 | 0.00 | 01-JAN-00:10 | 79937.71 | 01-JAN-08:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 44.22 | 0.00 | 01-JAN-00:10 | 79937.71 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 215.26 | 0.00 | 01-JAN-00:10 | 43967.62 | 10-AUG-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 63.89 | 0.00 | 01-JAN-00:10 | 21440.30 | 24-DEC-07:20 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 13.76 | 0.00 | 01-JAN-00:10 | 21440.30 | 24-DEC-07:20 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 50.13 | 0.00 | 01-JAN-00:10 | 9590.25 | 01-SEP-13:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 49.47 | 0.00 | 01-JAN-00:40 | 21620.25 | 24-DEC-07:20 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 23.27 | 0.00 | 01-JAN-00:40 | 21620.25 | 24-DEC-07:20 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 26.20 | 0.00 | 01-JAN-00:10 | 7583.80 | 01-SEP-13:30 |
EnergyTransfer:Zone:FRONT_ENTRY | 114.64 | 0.00 | 02-JAN-20:10 | 58697.03 | 05-JAN-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 114.64 | 0.00 | 02-JAN-20:10 | 58697.03 | 05-JAN-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1229.26 | 0.00 | 01-JAN-20:10 | 241564.46 | 09-JAN-07:10 |
HeatingCoils:EnergyTransfer | 477.66 | 0.00 | 01-JAN-20:10 | 241564.46 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 249.40 | 0.00 | 01-JAN-00:10 | 121975.99 | 30-JUN-15:00 |
HeatRecoveryForHeating:EnergyTransfer | 483.37 | 0.00 | 01-JAN-00:10 | 77032.01 | 31-JAN-18:50 |
HeatRecoveryForCooling:EnergyTransfer | 18.83 | 0.00 | 01-JAN-00:10 | 39909.81 | 15-JUL-14:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 65.979 | -34.107 | 0.000 | 0.000 | 40.351 | 17.781 | 49.772 | 0.000 | 0.000 | 0.098 | 0.001 | 0.000 | 0.000 | 0.000 | -24.055 | -115.819 |
CORE_RETAIL | 0.000 | 0.000 | 44.216 | -215.261 | 0.000 | 0.000 | 165.561 | 207.546 | 83.927 | 9.905 | 0.000 | 0.075 | 0.001 | 0.000 | -7.165 | 0.000 | -21.061 | -267.744 |
POINT_OF_SALE | 0.000 | 0.000 | 13.760 | -50.132 | 0.000 | 0.000 | 15.783 | 20.870 | 52.689 | 34.074 | 0.000 | 0.042 | 0.000 | 0.000 | -22.038 | 0.000 | -10.725 | -54.324 |
FRONT_RETAIL | 0.000 | 0.000 | 23.268 | -26.203 | 0.000 | 0.000 | 15.970 | 20.222 | 7.908 | 33.990 | 0.000 | 0.042 | 0.001 | 0.000 | -21.791 | 0.000 | -10.507 | -42.901 |
FRONT_ENTRY | 114.638 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.081 | 0.000 | 7.144 | 0.000 | 0.093 | 5.674 | 0.000 | -4.156 | 0.000 | -123.475 | -0.000 |
Total Facility | 114.638 | 0.000 | 147.224 | -325.703 | 0.000 | 0.000 | 237.666 | 266.501 | 194.297 | 85.114 | 0.000 | 0.350 | 5.677 | 0.000 | -55.150 | 0.000 | -189.822 | -480.788 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 13-AUG-19:01 | 0.00 | 0.00 | 0.00 | -26811.31 | 0.00 | 0.00 | 0.00 | 81.78 | 453.82 | 0.00 | 0.00 | 0.00 | 26473.68 | 0.00 | -0.00 | 0.00 | -197.97 | 0.00 |
CORE_RETAIL | 25-AUG-06:03 | 0.00 | 0.00 | 0.00 | -157639.17 | 0.00 | 0.00 | 1646.88 | 344.55 | 2062.04 | 0.00 | 0.00 | 0.00 | 153754.05 | 0.00 | -168.35 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 04-JUN-18:31 | 0.00 | 0.00 | 0.00 | -19317.73 | 0.00 | 0.00 | 0.00 | 32.47 | 480.42 | 189.72 | 0.00 | 0.00 | 18677.96 | 0.00 | -0.00 | 0.00 | -62.83 | 0.00 |
FRONT_RETAIL | 18-MAY-20:17 | 0.00 | 0.00 | 0.00 | -12785.61 | 0.00 | 0.00 | 0.00 | 32.47 | 96.14 | 0.00 | 0.00 | 0.00 | 13080.52 | 0.00 | -401.00 | 0.00 | -22.53 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-AUG-06:03 | 0.00 | 0.00 | 0.00 | -165626.98 | 0.00 | 0.00 | 2417.74 | 493.85 | 4773.73 | 0.00 | 0.00 | 0.00 | 159351.16 | 0.00 | -1409.49 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 05-JAN-05:41 | 0.00 | 0.00 | 50914.11 | 0.00 | 0.00 | 0.00 | 0.00 | 81.78 | 605.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4226.56 | -47374.41 |
CORE_RETAIL | 05-JAN-05:01 | 0.00 | 0.00 | 267282.68 | 0.00 | 0.00 | 0.00 | 0.00 | 344.55 | 1020.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -753.46 | 0.00 | -2720.69 | -265173.40 |
POINT_OF_SALE | 25-DEC-07:21 | 0.00 | 0.00 | 35502.36 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 480.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2458.85 | 0.00 | -1686.12 | -31870.27 |
FRONT_RETAIL | 25-DEC-07:21 | 0.00 | 0.00 | 30129.15 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 72.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2455.84 | 0.00 | -1673.78 | -26104.11 |
FRONT_ENTRY | 05-JAN-18:00 | 58697.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 599.32 | 0.00 | -507.09 | 0.00 | -58791.82 | 0.00 |
Total Facility | 10-DEC-08:61 | 8315.18 | 0.00 | 380609.36 | 0.00 | 0.00 | 0.00 | 0.00 | 493.85 | 1771.59 | 8.17 | 0.00 | 0.00 | 0.00 | 0.00 | -766.51 | 0.00 | -10411.46 | -380020.18 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.4989 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.5700 | 0.1475 | 1.0000 | 0.2316 | 0.1475 | ||
PSZ-AC:2 | 6.5101 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 6.7654 | 0.2794 | 1.0000 | 1.8902 | 0.2794 | ||
PSZ-AC:3 | 1.0077 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0245 | 0.1739 | 1.0000 | 0.1781 | 0.1739 | ||
PSZ-AC:4 | 0.7786 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.7786 | 0.2287 | 1.0000 | 0.1781 | 0.2287 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.4989 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.4989 | 1.0000 | 1.0000 | 0.2316 | 0.1545 | ||
PSZ-AC:2 | 6.5101 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 6.5101 | 1.0000 | 1.0000 | 1.8902 | 0.2904 | ||
PSZ-AC:3 | 1.0077 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0077 | 1.0000 | 1.0000 | 0.1781 | 0.1768 | ||
PSZ-AC:4 | 0.7786 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.7786 | 1.0000 | 1.0000 | 0.1781 | 0.2287 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.4989 | 1.4989 | 1.4989 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 6.5101 | 6.5101 | 6.5101 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.0077 | 1.0077 | 1.0077 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.7786 | 0.7786 | 0.7786 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.4989 | 1.5700 | 1.4989 | 1.4989 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.5101 | 6.7654 | 6.5101 | 6.5101 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.0077 | 1.0245 | 1.0077 | 1.0077 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.7786 | 0.7786 | 0.7786 | 0.7786 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.4989 | 1.4989 | 1.4989 | 0.2316 | 0.1627 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 6.5101 | 6.5101 | 6.5101 | 1.8902 | 0.5911 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.0077 | 1.0077 | 1.0077 | 0.1781 | 0.2574 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.7786 | 0.7786 | 0.7786 | 0.1781 | 0.2574 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.4989 | 1.4989 | 1.4989 | 1.4989 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.5101 | 6.5101 | 6.5101 | 6.5101 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.0077 | 1.0077 | 1.0077 | 1.0077 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.7786 | 0.7786 | 0.7786 | 0.7786 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:11
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 593.49 | 300867.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 66.14 | 32463.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 266.50 | 20551.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 38.67 | 3371.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 194.30 | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 159.55 | 14722.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 18.87 | 1406.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 100.67 | 6347.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 194.30 | 744.03 |
Natural Gas | 0.00 | 694.16 |
Additional | 0.00 | 0.00 |
Total | 194.30 | 1438.19 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 116.17 |
Space Heating | 0.00 |
Space Cooling | 28.83 |
Fans (All) | 69.55 |
Service Water Heating | 0.00 |
Receptacle Equipment | 84.70 |
Miscellaneous (All) | 324.34 |
Subtotal | 324.34 |
Natural Gas [MJ/m2] | |
Space Heating | 258.72 |
Service Water Heating | 43.88 |
Miscellaneous (All) | 302.60 |
Subtotal | 302.60 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.53 |
Space Heating | 41.27 |
Space Cooling | 4.60 |
Fans (All) | 11.09 |
Service Water Heating | 7.00 |
Receptacle Equipment | 13.51 |
Miscellaneous | 4.00 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 2872. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3001. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3501. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4552. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_SETBACK | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_FRONTENTRY_STD2013 | FRONT_ENTRY DUALSPSCHED | January | 16.00 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.175835E+12 |
February | 0.000 | 0.105430E+12 |
March | 0.000 | 0.757624E+11 |
April | 0.000 | 0.217674E+11 |
May | 0.000 | 0.129854E+10 |
June | 0.000 | 243704.656 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.775581E+08 |
October | 0.000 | 0.103452E+11 |
November | 0.000 | 0.493095E+11 |
December | 0.000 | 0.153668E+12 |
Annual Sum or Average | 0.593494E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.175835E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.175835E+12 |
February | 0.000 | 0.105430E+12 |
March | 0.000 | 0.757624E+11 |
April | 0.000 | 0.217674E+11 |
May | 0.000 | 0.129854E+10 |
June | 0.000 | 243704.656 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.775581E+08 |
October | 0.000 | 0.103452E+11 |
November | 0.000 | 0.493095E+11 |
December | 0.000 | 0.153668E+12 |
Annual Sum or Average | 0.593494E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.175835E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.175835E+12 |
February | 0.000 | 0.105430E+12 |
March | 0.000 | 0.757624E+11 |
April | 0.000 | 0.217674E+11 |
May | 0.000 | 0.129854E+10 |
June | 0.000 | 243704.656 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.775581E+08 |
October | 0.000 | 0.103452E+11 |
November | 0.000 | 0.493095E+11 |
December | 0.000 | 0.153668E+12 |
Annual Sum or Average | 0.593494E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.175835E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.175835E+12 |
February | 0.000 | 0.105430E+12 |
March | 0.000 | 0.757624E+11 |
April | 0.000 | 0.217674E+11 |
May | 0.000 | 0.129854E+10 |
June | 0.000 | 243704.656 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.775581E+08 |
October | 0.000 | 0.103452E+11 |
November | 0.000 | 0.493095E+11 |
December | 0.000 | 0.153668E+12 |
Annual Sum or Average | 0.593494E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.175835E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.175835E+12 |
February | 0.000 | 0.105430E+12 |
March | 0.000 | 0.757624E+11 |
April | 0.000 | 0.217674E+11 |
May | 0.000 | 0.129854E+10 |
June | 0.000 | 243704.656 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.775581E+08 |
October | 0.000 | 0.103452E+11 |
November | 0.000 | 0.493095E+11 |
December | 0.000 | 0.153668E+12 |
Annual Sum or Average | 0.593494E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.175835E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.175835E+12 |
February | 0.000 | 0.105430E+12 |
March | 0.000 | 0.757624E+11 |
April | 0.000 | 0.217674E+11 |
May | 0.000 | 0.129854E+10 |
June | 0.000 | 243704.656 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.775581E+08 |
October | 0.000 | 0.103452E+11 |
November | 0.000 | 0.493095E+11 |
December | 0.000 | 0.153668E+12 |
Annual Sum or Average | 0.593494E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.175835E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.175835E+12 |
February | 0.000 | 0.105430E+12 |
March | 0.000 | 0.757624E+11 |
April | 0.000 | 0.217674E+11 |
May | 0.000 | 0.129854E+10 |
June | 0.000 | 243704.656 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.775581E+08 |
October | 0.000 | 0.103452E+11 |
November | 0.000 | 0.493095E+11 |
December | 0.000 | 0.153668E+12 |
Annual Sum or Average | 0.593494E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.175835E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.175835E+12 |
February | 0.000 | 0.105430E+12 |
March | 0.000 | 0.757624E+11 |
April | 0.000 | 0.217674E+11 |
May | 0.000 | 0.129854E+10 |
June | 0.000 | 243704.656 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.775581E+08 |
October | 0.000 | 0.103452E+11 |
November | 0.000 | 0.493095E+11 |
December | 0.000 | 0.153668E+12 |
Annual Sum or Average | 0.593494E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.175835E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.175835E+12 |
February | 0.000 | 0.105430E+12 |
March | 0.000 | 0.757624E+11 |
April | 0.000 | 0.217674E+11 |
May | 0.000 | 0.129854E+10 |
June | 0.000 | 243704.656 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.775581E+08 |
October | 0.000 | 0.103452E+11 |
November | 0.000 | 0.493095E+11 |
December | 0.000 | 0.153668E+12 |
Annual Sum or Average | 0.593494E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.175835E+12 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -21.9 | -22.1 | 0.165228E+10 | 1854.44 | 21-JAN-13:39 | -6.5 | -8.0 |
February | 5052688.72 | 717.07 | 08-FEB-15:50 | 4.50 | -0.6 | 0.150875E+10 | 1854.44 | 18-FEB-16:00 | -12.2 | -13.4 |
March | 0.151955E+09 | 3143.00 | 27-MAR-17:33 | 6.47 | 2.28 | 0.172573E+10 | 1854.44 | 04-MAR-13:09 | -6.0 | -7.0 |
April | 0.128499E+10 | 3834.59 | 24-APR-10:10 | 4.50 | 2.71 | 0.169827E+10 | 2362.01 | 22-APR-15:00 | 18.90 | 8.01 |
May | 0.365379E+10 | 6700.83 | 25-MAY-15:00 | 28.90 | 19.65 | 0.209330E+10 | 2451.24 | 10-MAY-14:09 | 24.25 | 13.39 |
June | 0.559590E+10 | 22417.06 | 30-JUN-22:22 | 18.35 | 14.95 | 0.218349E+10 | 2451.26 | 07-JUN-14:09 | 22.20 | 14.32 |
July | 0.770235E+10 | 23670.53 | 02-JUL-19:02 | 20.92 | 16.42 | 0.218500E+10 | 2451.29 | 25-JUL-14:30 | 23.05 | 20.24 |
August | 0.709617E+10 | 26813.25 | 13-AUG-19:01 | 20.03 | 14.43 | 0.227680E+10 | 2451.27 | 10-AUG-14:39 | 17.60 | 15.80 |
September | 0.467992E+10 | 17590.10 | 01-SEP-20:42 | 15.28 | 14.47 | 0.208474E+10 | 2451.26 | 07-SEP-14:00 | 23.90 | 14.99 |
October | 0.317055E+10 | 4886.82 | 04-OCT-06:03 | 0.00 | -0.2 | 0.180330E+10 | 2451.20 | 19-OCT-14:09 | 21.78 | 13.68 |
November | 0.766472E+09 | 5235.42 | 09-NOV-17:35 | -2.1 | -5.3 | 0.159968E+10 | 2249.46 | 01-NOV-14:00 | 18.30 | 13.43 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 | 0.165479E+10 | 1854.44 | 08-DEC-15:00 | -11.9 | -12.8 |
Annual Sum or Average | 0.341071E+11 | 0.224661E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -21.9 | -22.1 | 0.150875E+10 | 1854.44 | -12.2 | -13.4 | ||
Maximum of Months | 0.770235E+10 | 26813.25 | 28.90 | 19.65 | 0.227680E+10 | 2451.29 | 24.25 | 20.24 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316492E+10 | 100699.52 | 04-JAN-14:00 | -27.8 | -28.1 | 0.695934E+10 | 7949.48 | 19-JAN-15:00 | -2.8 | -3.5 |
February | 0.536739E+10 | 65050.99 | 24-FEB-07:05 | -23.9 | -24.2 | 0.643297E+10 | 9107.54 | 08-FEB-15:00 | 4.40 | -0.7 |
March | 0.910150E+10 | 25973.54 | 16-MAR-06:05 | -22.9 | -23.2 | 0.760177E+10 | 10325.92 | 31-MAR-14:00 | 8.30 | 2.61 |
April | 0.125231E+11 | 20806.15 | 22-APR-14:50 | 18.22 | 7.73 | 0.839127E+10 | 10327.19 | 15-APR-12:09 | 5.50 | 5.17 |
May | 0.243684E+11 | 153041.78 | 19-MAY-06:03 | 14.47 | 10.08 | 0.935670E+10 | 10327.17 | 10-MAY-14:09 | 24.25 | 13.39 |
June | 0.319725E+11 | 145003.45 | 09-JUN-06:03 | 12.12 | 11.47 | 0.927628E+10 | 10327.17 | 07-JUN-14:20 | 22.20 | 14.26 |
July | 0.375849E+11 | 149770.43 | 08-JUL-06:03 | 11.97 | 10.77 | 0.921738E+10 | 10327.65 | 25-JUL-14:30 | 23.05 | 20.24 |
August | 0.360830E+11 | 157714.92 | 25-AUG-06:03 | 9.05 | 8.95 | 0.961176E+10 | 10327.10 | 10-AUG-14:09 | 18.95 | 16.67 |
September | 0.259862E+11 | 147272.25 | 02-SEP-06:02 | 13.22 | 10.59 | 0.907483E+10 | 10327.27 | 02-SEP-13:50 | 15.33 | 13.44 |
October | 0.153894E+11 | 23920.21 | 21-OCT-14:50 | 20.00 | 11.19 | 0.882786E+10 | 10327.23 | 28-OCT-10:09 | 8.90 | 7.17 |
November | 0.929219E+10 | 23798.62 | 25-NOV-07:05 | -19.2 | -19.5 | 0.736784E+10 | 10327.15 | 21-NOV-15:20 | 9.10 | 8.60 |
December | 0.442806E+10 | 47459.66 | 02-DEC-07:05 | -27.1 | -27.3 | 0.697176E+10 | 8032.52 | 05-DEC-15:00 | -0.4 | -0.4 |
Annual Sum or Average | 0.215262E+12 | 0.990898E+11 | ||||||||
Minimum of Months | 0.316492E+10 | 20806.15 | -27.8 | -28.1 | 0.643297E+10 | 7949.48 | -2.8 | -3.5 | ||
Maximum of Months | 0.375849E+11 | 157714.92 | 20.00 | 11.47 | 0.961176E+10 | 10327.65 | 24.25 | 20.24 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102935E+10 | 7372.25 | 09-JAN-17:32 | -18.3 | -19.1 | 0.655925E+09 | 736.18 | 14-JAN-14:30 | -13.6 | -14.1 |
February | 0.174774E+10 | 7750.06 | 10-FEB-20:52 | -20.0 | -20.4 | 0.609498E+09 | 962.80 | 28-FEB-15:39 | 6.10 | 1.53 |
March | 0.234850E+10 | 6338.16 | 15-MAR-18:42 | -13.1 | -14.5 | 0.703134E+09 | 973.05 | 31-MAR-14:20 | 8.30 | 2.93 |
April | 0.335443E+10 | 14160.64 | 23-APR-19:01 | 23.03 | 14.62 | 0.737035E+09 | 973.09 | 22-APR-11:20 | 15.37 | 5.88 |
May | 0.505282E+10 | 16400.05 | 21-MAY-18:21 | 20.30 | 10.57 | 0.864447E+09 | 973.16 | 19-MAY-14:09 | 17.63 | 14.64 |
June | 0.613568E+10 | 19317.77 | 04-JUN-18:31 | 21.10 | 11.72 | 0.871420E+09 | 973.14 | 06-JUN-14:30 | 20.00 | 14.71 |
July | 0.779712E+10 | 13508.00 | 30-JUL-20:31 | 20.20 | 17.95 | 0.867916E+09 | 973.21 | 25-JUL-14:30 | 23.05 | 20.24 |
August | 0.805716E+10 | 13104.45 | 27-AUG-07:01 | 12.88 | 11.52 | 0.904725E+09 | 973.14 | 01-AUG-14:00 | 20.60 | 15.16 |
September | 0.636640E+10 | 14604.43 | 10-SEP-19:02 | 13.22 | 10.20 | 0.845092E+09 | 973.14 | 02-SEP-14:20 | 15.53 | 13.70 |
October | 0.475652E+10 | 16779.23 | 22-OCT-19:04 | 9.72 | 7.54 | 0.774362E+09 | 973.10 | 07-OCT-11:20 | 12.77 | 12.01 |
November | 0.258156E+10 | 4807.76 | 10-NOV-12:40 | -3.0 | -5.2 | 0.663952E+09 | 973.07 | 01-NOV-14:09 | 17.88 | 13.28 |
December | 0.904595E+09 | 5896.08 | 22-DEC-16:42 | -11.1 | -11.3 | 0.656920E+09 | 736.18 | 11-DEC-15:30 | -17.6 | -18.5 |
Annual Sum or Average | 0.501319E+11 | 0.915443E+10 | ||||||||
Minimum of Months | 0.904595E+09 | 4807.76 | -20.0 | -20.4 | 0.609498E+09 | 736.18 | -17.6 | -18.5 | ||
Maximum of Months | 0.805716E+10 | 19317.77 | 23.03 | 17.95 | 0.904725E+09 | 973.21 | 23.05 | 20.24 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248353E+09 | 8168.69 | 13-JAN-11:20 | -24.3 | -24.5 | 0.655909E+09 | 736.18 | 07-JAN-16:30 | -18.0 | -18.5 |
February | 0.598373E+09 | 5782.14 | 27-FEB-10:32 | -12.8 | -13.9 | 0.601224E+09 | 855.17 | 28-FEB-15:39 | 6.10 | 1.53 |
March | 0.847084E+09 | 5560.65 | 14-MAR-10:23 | -11.6 | -13.1 | 0.688829E+09 | 900.06 | 31-MAR-14:00 | 8.30 | 2.61 |
April | 0.147174E+10 | 3313.66 | 22-APR-13:40 | 17.23 | 7.20 | 0.706917E+09 | 973.10 | 22-APR-11:20 | 15.37 | 5.88 |
May | 0.258159E+10 | 12786.16 | 18-MAY-20:17 | 20.00 | 13.67 | 0.834282E+09 | 973.12 | 22-MAY-14:09 | 19.60 | 13.78 |
June | 0.330774E+10 | 10983.01 | 26-JUN-20:20 | 18.90 | 17.08 | 0.864747E+09 | 973.13 | 06-JUN-14:39 | 19.80 | 14.70 |
July | 0.467285E+10 | 12107.90 | 02-JUL-18:18 | 22.23 | 16.44 | 0.866916E+09 | 973.13 | 25-JUL-14:09 | 24.35 | 20.60 |
August | 0.485711E+10 | 12024.87 | 04-AUG-20:18 | 16.13 | 12.59 | 0.901828E+09 | 973.13 | 21-AUG-14:00 | 21.70 | 18.72 |
September | 0.383601E+10 | 12539.85 | 07-SEP-20:57 | 18.90 | 13.68 | 0.819250E+09 | 973.14 | 11-SEP-14:09 | 18.98 | 14.78 |
October | 0.263944E+10 | 6262.35 | 21-OCT-14:00 | 20.00 | 11.45 | 0.728097E+09 | 973.10 | 21-OCT-11:20 | 16.33 | 10.20 |
November | 0.958234E+09 | 4132.65 | 10-NOV-12:40 | -3.0 | -5.2 | 0.642705E+09 | 971.93 | 17-NOV-15:30 | 10.30 | 3.30 |
December | 0.184260E+09 | 3154.54 | 02-DEC-13:50 | -18.3 | -19.0 | 0.656922E+09 | 736.18 | 30-DEC-16:40 | -3.3 | -3.4 |
Annual Sum or Average | 0.262028E+11 | 0.896763E+10 | ||||||||
Minimum of Months | 0.184260E+09 | 3154.54 | -24.3 | -24.5 | 0.601224E+09 | 736.18 | -18.0 | -18.5 | ||
Maximum of Months | 0.485711E+10 | 12786.16 | 22.23 | 17.08 | 0.901828E+09 | 973.14 | 24.35 | 20.60 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 | -23.4 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 | 13.56 | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.56 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.4 | 0.00 | 0.00 | -23.1 | -23.4 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.00 | 0.00 | 19.75 | 18.15 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176796E+11 | 50913.91 | 05-JAN-05:41 | -32.6 |
February | 0.127272E+11 | 50133.96 | 06-FEB-05:41 | -20.5 |
March | 0.100853E+11 | 50025.92 | 05-MAR-07:31 | -27.4 |
April | 0.344646E+10 | 48518.87 | 07-APR-04:42 | -6.1 |
May | 0.299430E+09 | 48129.49 | 01-MAY-04:01 | -2.9 |
June | 52711880.98 | 841.46 | 28-JUN-05:07 | 15.15 |
July | 24321541.64 | 872.13 | 30-JUL-07:07 | 21.65 |
August | 32715107.08 | 896.32 | 10-AUG-05:07 | 15.50 |
September | 62347658.23 | 962.63 | 01-SEP-05:05 | 15.68 |
October | 0.820493E+09 | 48245.00 | 30-OCT-04:01 | -10.0 |
November | 0.550128E+10 | 48731.16 | 25-NOV-05:21 | -19.1 |
December | 0.152466E+11 | 50614.56 | 20-DEC-06:01 | -28.9 |
Annual Sum or Average | 0.659784E+11 | |||
Minimum of Months | 24321541.64 | 841.46 | -32.6 | |
Maximum of Months | 0.176796E+11 | 50913.91 | 21.65 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138183E+11 | 267282.71 | 05-JAN-05:01 | -31.9 |
February | 0.789560E+10 | 265855.97 | 01-FEB-06:01 | -22.8 |
March | 0.500407E+10 | 265753.62 | 06-MAR-06:01 | -19.0 |
April | 0.888385E+09 | 159397.80 | 05-APR-06:03 | -13.5 |
May | 0.472274E+09 | 4551.41 | 14-MAY-07:33 | 6.37 |
June | 0.446504E+09 | 6765.36 | 30-JUN-06:20 | 26.50 |
July | 0.474019E+09 | 5970.53 | 30-JUL-08:20 | 24.80 |
August | 0.473893E+09 | 4503.41 | 27-AUG-07:12 | 12.97 |
September | 0.457426E+09 | 4510.29 | 10-SEP-07:12 | 7.40 |
October | 0.474596E+09 | 4530.41 | 08-OCT-07:25 | 2.50 |
November | 0.257810E+10 | 261761.90 | 29-NOV-06:02 | -20.3 |
December | 0.112339E+11 | 267231.19 | 25-DEC-07:01 | -28.6 |
Annual Sum or Average | 0.442170E+11 | |||
Minimum of Months | 0.446504E+09 | 4503.41 | -31.9 | |
Maximum of Months | 0.138183E+11 | 267282.71 | 26.50 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391531E+10 | 35321.03 | 07-JAN-05:21 | -22.5 |
February | 0.235441E+10 | 34300.60 | 06-FEB-05:41 | -20.5 |
March | 0.185477E+10 | 34481.06 | 05-MAR-07:31 | -27.4 |
April | 0.615498E+09 | 33311.53 | 28-APR-04:01 | -4.9 |
May | 60241429.16 | 33176.02 | 01-MAY-04:01 | -2.9 |
June | 19148672.09 | 602.22 | 27-JUN-05:05 | 15.68 |
July | 8285973.75 | 631.04 | 16-JUL-07:03 | 17.38 |
August | 9003354.22 | 641.24 | 15-AUG-05:04 | 13.90 |
September | 19890357.01 | 685.78 | 08-SEP-05:03 | 10.10 |
October | 0.155821E+09 | 33307.83 | 30-OCT-04:01 | -10.0 |
November | 0.117638E+10 | 33561.87 | 25-NOV-05:12 | -19.1 |
December | 0.357172E+10 | 35502.27 | 25-DEC-07:21 | -28.3 |
Annual Sum or Average | 0.137605E+11 | |||
Minimum of Months | 8285973.75 | 602.22 | -28.3 | |
Maximum of Months | 0.391531E+10 | 35502.27 | 17.38 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.620373E+10 | 29610.84 | 08-JAN-08:61 | -22.9 |
February | 0.384345E+10 | 29567.48 | 01-FEB-06:01 | -22.8 |
March | 0.322450E+10 | 29392.94 | 05-MAR-07:31 | -27.4 |
April | 0.118432E+10 | 28445.74 | 04-APR-04:12 | -7.8 |
May | 0.162392E+09 | 28302.54 | 01-MAY-04:01 | -2.9 |
June | 56509097.98 | 916.77 | 28-JUN-05:07 | 15.15 |
July | 20104596.92 | 911.01 | 20-JUL-05:07 | 15.37 |
August | 21723289.97 | 966.05 | 12-AUG-05:07 | 16.20 |
September | 65204098.78 | 1524.80 | 29-SEP-05:02 | 7.20 |
October | 0.415833E+09 | 28388.46 | 30-OCT-04:01 | -10.0 |
November | 0.214900E+10 | 28621.12 | 26-NOV-07:12 | -9.8 |
December | 0.592161E+10 | 30129.07 | 25-DEC-07:21 | -28.3 |
Annual Sum or Average | 0.232684E+11 | |||
Minimum of Months | 20104596.92 | 911.01 | -28.3 | |
Maximum of Months | 0.620373E+10 | 30129.07 | 16.20 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.287811E+11 | 58697.03 | 05-JAN-18:00 | -28.3 |
February | 0.189556E+11 | 50449.11 | 01-FEB-18:00 | -23.3 |
March | 0.161636E+11 | 38330.43 | 15-MAR-11:10 | -15.3 |
April | 0.555579E+10 | 24354.76 | 04-APR-11:10 | -4.9 |
May | 0.225450E+09 | 10969.72 | 01-MAY-11:05 | 6.72 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 28323467.78 | 2534.34 | 23-SEP-07:25 | 5.30 |
October | 0.495134E+10 | 19873.16 | 29-OCT-17:00 | -1.1 |
November | 0.126552E+11 | 39084.05 | 25-NOV-17:00 | -15.6 |
December | 0.273219E+11 | 55996.31 | 24-DEC-12:10 | -26.9 |
Annual Sum or Average | 0.114638E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.3 | |
Maximum of Months | 0.287811E+11 | 58697.03 | 17.07 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.149153E+10 | 1249.73 | 02-JAN-09:09 | 0.419292E+10 | 2751.42 | 02-JAN-09:09 |
February | 0.135698E+10 | 1249.73 | 01-FEB-09:09 | 0.380401E+10 | 2751.42 | 01-FEB-09:09 |
March | 0.154631E+10 | 1249.73 | 01-MAR-09:09 | 0.429860E+10 | 2751.42 | 01-MAR-09:09 |
April | 0.146057E+10 | 1249.73 | 01-APR-09:09 | 0.408483E+10 | 2751.42 | 01-APR-09:09 |
May | 0.151892E+10 | 1249.73 | 01-MAY-08:09 | 0.424576E+10 | 2751.42 | 01-MAY-08:09 |
June | 0.149233E+10 | 1249.73 | 01-JUN-08:09 | 0.415135E+10 | 2751.42 | 01-JUN-08:09 |
July | 0.148716E+10 | 1249.73 | 01-JUL-09:09 | 0.417924E+10 | 2751.42 | 01-JUL-09:09 |
August | 0.154631E+10 | 1249.73 | 01-AUG-08:09 | 0.429860E+10 | 2751.42 | 01-AUG-08:09 |
September | 0.146057E+10 | 1249.73 | 01-SEP-08:09 | 0.408483E+10 | 2751.42 | 01-SEP-08:09 |
October | 0.149153E+10 | 1249.73 | 02-OCT-08:09 | 0.419292E+10 | 2751.42 | 02-OCT-08:09 |
November | 0.144192E+10 | 1249.73 | 01-NOV-08:09 | 0.405935E+10 | 2751.42 | 01-NOV-08:09 |
December | 0.148716E+10 | 1249.73 | 01-DEC-09:09 | 0.417924E+10 | 2751.42 | 01-DEC-09:09 |
Annual Sum or Average | 0.177813E+11 | 0.497716E+11 | ||||
Minimum of Months | 0.135698E+10 | 1249.73 | 0.380401E+10 | 2751.42 | ||
Maximum of Months | 0.154631E+10 | 1249.73 | 0.429860E+10 | 2751.42 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.180793E+11 | 16279.94 | 02-JAN-16:30 | 0.707031E+10 | 4639.58 | 02-JAN-09:09 |
February | 0.162613E+11 | 16279.94 | 01-FEB-17:10 | 0.641452E+10 | 4639.58 | 01-FEB-09:09 |
March | 0.183435E+11 | 16279.94 | 01-MAR-17:00 | 0.724851E+10 | 4639.58 | 01-MAR-09:09 |
April | 0.169875E+11 | 15929.60 | 21-APR-16:00 | 0.688804E+10 | 4639.58 | 01-APR-09:09 |
May | 0.168787E+11 | 15853.23 | 04-MAY-16:00 | 0.715941E+10 | 4639.58 | 01-MAY-08:09 |
June | 0.166583E+11 | 15693.50 | 09-JUN-16:00 | 0.700021E+10 | 4639.58 | 01-JUN-08:09 |
July | 0.164896E+11 | 15710.90 | 11-JUL-16:00 | 0.704724E+10 | 4639.58 | 01-JUL-09:09 |
August | 0.176024E+11 | 15771.71 | 31-AUG-08:09 | 0.724851E+10 | 4639.58 | 01-AUG-08:09 |
September | 0.170316E+11 | 16054.58 | 30-SEP-16:00 | 0.688804E+10 | 4639.58 | 01-SEP-08:09 |
October | 0.177190E+11 | 16279.94 | 27-OCT-16:00 | 0.707031E+10 | 4639.58 | 02-OCT-08:09 |
November | 0.174320E+11 | 16279.94 | 01-NOV-16:00 | 0.684509E+10 | 4639.58 | 01-NOV-08:09 |
December | 0.180630E+11 | 16279.94 | 01-DEC-16:19 | 0.704724E+10 | 4639.58 | 01-DEC-09:09 |
Annual Sum or Average | 0.207546E+12 | 0.839274E+11 | ||||
Minimum of Months | 0.162613E+11 | 15693.50 | 0.641452E+10 | 4639.58 | ||
Maximum of Months | 0.183435E+11 | 16279.94 | 0.724851E+10 | 4639.58 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.174880E+10 | 1534.02 | 02-JAN-09:09 | 0.443872E+10 | 2912.71 | 02-JAN-09:09 |
February | 0.159209E+10 | 1534.02 | 01-FEB-09:09 | 0.402701E+10 | 2912.71 | 01-FEB-09:09 |
March | 0.181792E+10 | 1534.02 | 01-MAR-09:09 | 0.455059E+10 | 2912.71 | 01-MAR-09:09 |
April | 0.171453E+10 | 1534.02 | 01-APR-09:09 | 0.432429E+10 | 2912.71 | 01-APR-09:09 |
May | 0.178336E+10 | 1534.02 | 01-MAY-08:09 | 0.449465E+10 | 2912.71 | 01-MAY-08:09 |
June | 0.175416E+10 | 1534.02 | 01-JUN-08:09 | 0.439471E+10 | 2912.71 | 01-JUN-08:09 |
July | 0.174372E+10 | 1534.02 | 01-JUL-09:09 | 0.442423E+10 | 2912.71 | 01-JUL-09:09 |
August | 0.181792E+10 | 1534.02 | 01-AUG-08:09 | 0.455059E+10 | 2912.71 | 01-AUG-08:09 |
September | 0.171453E+10 | 1534.02 | 01-SEP-08:09 | 0.432429E+10 | 2912.71 | 01-SEP-08:09 |
October | 0.174880E+10 | 1534.02 | 02-OCT-08:09 | 0.443872E+10 | 2912.71 | 02-OCT-08:09 |
November | 0.169012E+10 | 1534.02 | 01-NOV-08:09 | 0.429732E+10 | 2912.71 | 01-NOV-08:09 |
December | 0.174372E+10 | 1534.02 | 01-DEC-09:09 | 0.442423E+10 | 2912.71 | 01-DEC-09:09 |
Annual Sum or Average | 0.208697E+11 | 0.526893E+11 | ||||
Minimum of Months | 0.159209E+10 | 1534.02 | 0.402701E+10 | 2912.71 | ||
Maximum of Months | 0.181792E+10 | 1534.02 | 0.455059E+10 | 2912.71 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.169457E+10 | 1485.24 | 02-JAN-09:09 | 0.666220E+09 | 437.18 | 02-JAN-09:09 |
February | 0.154270E+10 | 1485.24 | 01-FEB-09:09 | 0.604426E+09 | 437.18 | 01-FEB-09:09 |
March | 0.176147E+10 | 1485.24 | 01-MAR-09:09 | 0.683011E+09 | 437.18 | 01-MAR-09:09 |
April | 0.166132E+10 | 1485.24 | 01-APR-09:09 | 0.649045E+09 | 437.18 | 01-APR-09:09 |
May | 0.172802E+10 | 1485.24 | 01-MAY-08:09 | 0.674616E+09 | 437.18 | 01-MAY-08:09 |
June | 0.169970E+10 | 1485.24 | 01-JUN-08:09 | 0.659615E+09 | 437.18 | 01-JUN-08:09 |
July | 0.168964E+10 | 1485.24 | 01-JUL-09:09 | 0.664046E+09 | 437.18 | 01-JUL-09:09 |
August | 0.176147E+10 | 1485.24 | 01-AUG-08:09 | 0.683011E+09 | 437.18 | 01-AUG-08:09 |
September | 0.166132E+10 | 1485.24 | 01-SEP-08:09 | 0.649045E+09 | 437.18 | 01-SEP-08:09 |
October | 0.169457E+10 | 1485.24 | 02-OCT-08:09 | 0.666220E+09 | 437.18 | 02-OCT-08:09 |
November | 0.163772E+10 | 1485.24 | 01-NOV-08:09 | 0.644998E+09 | 437.18 | 01-NOV-08:09 |
December | 0.168964E+10 | 1485.24 | 01-DEC-09:09 | 0.664046E+09 | 437.18 | 01-DEC-09:09 |
Annual Sum or Average | 0.202221E+11 | 0.790830E+10 | ||||
Minimum of Months | 0.154270E+10 | 1485.24 | 0.604426E+09 | 437.18 | ||
Maximum of Months | 0.176147E+10 | 1485.24 | 0.683011E+09 | 437.18 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 6919213.84 | 2.58 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 6249612.50 | 2.58 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 6919213.84 | 2.58 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 6696013.39 | 2.58 | 01-APR-00:10 | 0.00 | 0.00 |
May | 6919213.84 | 2.58 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 6696013.39 | 2.58 | 01-JUN-00:10 | 0.00 | 0.00 |
July | 6919213.84 | 2.58 | 01-JUL-00:10 | 0.00 | 0.00 |
August | 6919213.84 | 2.58 | 01-AUG-00:10 | 0.00 | 0.00 |
September | 6696013.39 | 2.58 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 6919213.84 | 2.58 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 6696013.39 | 2.58 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 6919213.84 | 2.58 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 81468162.94 | ||||
Minimum of Months | 6249612.50 | 2.58 | 0.00 | 0.00 | |
Maximum of Months | 6919213.84 | 2.58 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.149153E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403586E+10 |
February | 0.479114E+10 | 0.135698E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348143E+10 |
March | 0.548013E+10 | 0.154631E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247577E+10 |
April | 0.518069E+10 | 0.146057E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2550406.08 | 0.201388E+10 |
May | 0.536353E+10 | 0.151892E+10 | 0.424576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8319561.23 | 0.989075E+09 |
June | 0.528933E+10 | 0.149233E+10 | 0.415135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38250412.30 | 0.560500E+09 |
July | 0.525489E+10 | 0.148716E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35050417.26 | 0.377916E+09 |
August | 0.548013E+10 | 0.154631E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13307924.29 | 0.597417E+09 |
September | 0.518069E+10 | 0.146057E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 433316.42 | 0.105229E+10 |
October | 0.524694E+10 | 0.149153E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151315E+10 |
November | 0.504819E+10 | 0.144192E+10 | 0.405935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277985E+10 |
December | 0.525489E+10 | 0.148716E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417744E+10 |
Annual Sum or Average | 0.628175E+11 | 0.177813E+11 | 0.497716E+11 | 97912037.58 | 0.240546E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.135698E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377916E+09 |
Maximum of Months | 0.548013E+10 | 0.154631E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38250412.30 | 0.417744E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.180793E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342028E+10 |
February | 0.201852E+11 | 0.162613E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298799E+10 |
March | 0.230879E+11 | 0.183435E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214592E+10 |
April | 0.218263E+11 | 0.169875E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1349800.64 | 0.186061E+10 |
May | 0.225967E+11 | 0.168787E+11 | 0.715941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6803431.58 | 0.927762E+09 |
June | 0.222841E+11 | 0.166583E+11 | 0.700021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27434920.97 | 0.519102E+09 |
July | 0.221389E+11 | 0.164896E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28210827.71 | 0.342171E+09 |
August | 0.230879E+11 | 0.176024E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10889884.75 | 0.531800E+09 |
September | 0.218263E+11 | 0.170316E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 354743.75 | 0.943758E+09 |
October | 0.221054E+11 | 0.177190E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138577E+10 |
November | 0.212681E+11 | 0.174320E+11 | 0.684509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244027E+10 |
December | 0.221389E+11 | 0.180630E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355577E+10 |
Annual Sum or Average | 0.264651E+12 | 0.207546E+12 | 0.839274E+11 | 75043609.40 | 0.210612E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.162613E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342171E+09 |
Maximum of Months | 0.230879E+11 | 0.183435E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28210827.71 | 0.355577E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.174880E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176044E+10 |
February | 0.190200E+10 | 0.159209E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153702E+10 |
March | 0.217552E+10 | 0.181792E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110825E+10 |
April | 0.205665E+10 | 0.171453E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 710336.07 | 0.929530E+09 |
May | 0.212923E+10 | 0.178336E+10 | 0.449465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3604302.15 | 0.461858E+09 |
June | 0.209978E+10 | 0.175416E+10 | 0.439471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16617793.79 | 0.256709E+09 |
July | 0.208610E+10 | 0.174372E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15212747.89 | 0.163535E+09 |
August | 0.217552E+10 | 0.181792E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5771548.80 | 0.262441E+09 |
September | 0.205665E+10 | 0.171453E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 187967.33 | 0.482427E+09 |
October | 0.208295E+10 | 0.174880E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700934E+09 |
November | 0.200405E+10 | 0.169012E+10 | 0.429732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123930E+10 |
December | 0.208610E+10 | 0.174372E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182234E+10 |
Annual Sum or Average | 0.249375E+11 | 0.208697E+11 | 0.526893E+11 | 42104696.02 | 0.107248E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.159209E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163535E+09 |
Maximum of Months | 0.217552E+10 | 0.181792E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16617793.79 | 0.182234E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.169457E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174856E+10 |
February | 0.190200E+10 | 0.154270E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152016E+10 |
March | 0.217552E+10 | 0.176147E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108742E+10 |
April | 0.205665E+10 | 0.166132E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 686905.47 | 0.897351E+09 |
May | 0.212923E+10 | 0.172802E+10 | 0.674616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3602990.16 | 0.435849E+09 |
June | 0.209978E+10 | 0.169970E+10 | 0.659615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16587210.79 | 0.243993E+09 |
July | 0.208610E+10 | 0.168964E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15198663.00 | 0.163421E+09 |
August | 0.217552E+10 | 0.176147E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5772863.76 | 0.259992E+09 |
September | 0.205665E+10 | 0.166132E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 187876.66 | 0.461999E+09 |
October | 0.208295E+10 | 0.169457E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672129E+09 |
November | 0.200405E+10 | 0.163772E+10 | 0.644998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120916E+10 |
December | 0.208610E+10 | 0.168964E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180665E+10 |
Annual Sum or Average | 0.249375E+11 | 0.202221E+11 | 0.790830E+10 | 42036509.83 | 0.105067E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.154270E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163421E+09 |
Maximum of Months | 0.217552E+10 | 0.176147E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16587210.79 | 0.180665E+10 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289462E+11 |
February | 0.00 | 6249612.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194773E+11 |
March | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168306E+11 |
April | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 794993.67 | 0.662597E+10 |
May | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9058044.99 | 0.119387E+10 |
June | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46546326.61 | 0.542545E+09 |
July | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33048373.43 | 0.452132E+09 |
August | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3639500.03 | 0.728478E+09 |
September | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146353E+10 |
October | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631527E+10 |
November | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134220E+11 |
December | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274772E+11 |
Annual Sum or Average | 0.00 | 81468162.94 | 93087238.72 | 0.123475E+12 | |||||
Minimum of Months | 0.00 | 6249612.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452132E+09 |
Maximum of Months | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46546326.61 | 0.289462E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 1249.73 | 02-JAN-09:09 | 2751.42 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 8509.95 | 04-JAN-05:59 |
February | 5888.82 | 01-FEB-15:09 | 1249.73 | 01-FEB-09:09 | 2751.42 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 9445.09 | 12-FEB-23:00 |
March | 5888.82 | 01-MAR-15:09 | 1249.73 | 01-MAR-09:09 | 2751.42 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5202.25 | 15-MAR-05:00 |
April | 5888.82 | 01-APR-10:09 | 1249.73 | 01-APR-09:09 | 2751.42 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 392.10 | 23-APR-18:10 | 3967.96 | 01-APR-21:03 |
May | 5888.82 | 01-MAY-14:09 | 1249.73 | 01-MAY-08:09 | 2751.42 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.17 | 24-MAY-15:00 | 1959.62 | 09-MAY-04:06 |
June | 5888.82 | 01-JUN-14:09 | 1249.73 | 01-JUN-08:09 | 2751.42 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 438.50 | 29-JUN-20:20 | 1331.90 | 09-JUN-20:10 |
July | 5888.82 | 01-JUL-10:09 | 1249.73 | 01-JUL-09:09 | 2751.42 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 460.12 | 23-JUL-18:03 | 1199.02 | 06-JUL-22:00 |
August | 5888.82 | 01-AUG-14:09 | 1249.73 | 01-AUG-08:09 | 2751.42 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 230.46 | 08-AUG-16:00 | 1788.64 | 27-AUG-06:00 |
September | 5888.82 | 01-SEP-14:09 | 1249.73 | 01-SEP-08:09 | 2751.42 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.05 | 01-SEP-15:00 | 2442.10 | 20-SEP-01:00 |
October | 5888.82 | 02-OCT-14:09 | 1249.73 | 02-OCT-08:09 | 2751.42 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3254.97 | 31-OCT-20:05 |
November | 5888.82 | 01-NOV-14:09 | 1249.73 | 01-NOV-08:09 | 2751.42 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5215.58 | 22-NOV-02:00 |
December | 5888.82 | 01-DEC-15:09 | 1249.73 | 01-DEC-09:09 | 2751.42 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8476.79 | 16-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 1249.73 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.02 | |||||
Maximum of Months | 5888.82 | 1249.73 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 460.12 | 9445.09 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 16279.94 | 02-JAN-16:30 | 4639.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 6547.89 | 04-JAN-05:59 |
February | 24809.68 | 01-FEB-15:09 | 16279.94 | 01-FEB-17:10 | 4639.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8311.45 | 12-FEB-22:55 |
March | 24809.68 | 01-MAR-15:09 | 16279.94 | 01-MAR-17:00 | 4639.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3942.56 | 15-MAR-04:53 |
April | 24809.68 | 01-APR-10:09 | 15929.60 | 21-APR-16:00 | 4639.58 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 203.79 | 23-APR-18:05 | 3435.41 | 02-APR-01:00 |
May | 24809.68 | 01-MAY-14:09 | 15853.23 | 04-MAY-16:00 | 4639.58 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.90 | 24-MAY-15:00 | 1791.28 | 20-MAY-05:00 |
June | 24809.68 | 01-JUN-14:09 | 15693.50 | 09-JUN-16:00 | 4639.58 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 347.71 | 29-JUN-20:03 | 1224.01 | 10-JUN-22:00 |
July | 24809.68 | 01-JUL-10:09 | 15710.90 | 11-JUL-16:00 | 4639.58 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 375.90 | 23-JUL-18:03 | 1146.72 | 06-JUL-22:00 |
August | 24809.68 | 01-AUG-14:09 | 15771.71 | 31-AUG-08:09 | 4639.58 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 188.63 | 08-AUG-16:00 | 1624.00 | 27-AUG-06:00 |
September | 24809.68 | 01-SEP-14:09 | 16054.58 | 30-SEP-16:00 | 4639.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.14 | 01-SEP-15:00 | 2211.06 | 20-SEP-01:00 |
October | 24809.68 | 02-OCT-14:09 | 16279.94 | 27-OCT-16:00 | 4639.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2808.20 | 31-OCT-21:00 |
November | 24809.68 | 01-NOV-14:09 | 16279.94 | 01-NOV-16:00 | 4639.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4974.61 | 22-NOV-02:00 |
December | 24809.68 | 01-DEC-15:09 | 16279.94 | 01-DEC-16:19 | 4639.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6300.74 | 16-DEC-05:53 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 15693.50 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1146.72 | |||||
Maximum of Months | 24809.68 | 16279.94 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 375.90 | 8311.45 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1534.02 | 02-JAN-09:09 | 2912.71 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3655.43 | 04-JAN-05:51 |
February | 2337.76 | 01-FEB-15:09 | 1534.02 | 01-FEB-09:09 | 2912.71 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4101.57 | 12-FEB-23:00 |
March | 2337.76 | 01-MAR-15:09 | 1534.02 | 01-MAR-09:09 | 2912.71 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2254.29 | 15-MAR-05:00 |
April | 2337.76 | 01-APR-10:09 | 1534.02 | 01-APR-09:09 | 2912.71 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 93.70 | 23-APR-18:05 | 1726.60 | 01-APR-21:03 |
May | 2337.76 | 01-MAY-14:09 | 1534.02 | 01-MAY-08:09 | 2912.71 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.01 | 24-MAY-15:00 | 869.45 | 20-MAY-05:00 |
June | 2337.76 | 01-JUN-14:09 | 1534.02 | 01-JUN-08:09 | 2912.71 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.99 | 29-JUN-20:20 | 609.67 | 09-JUN-20:10 |
July | 2337.76 | 01-JUL-10:09 | 1534.02 | 01-JUL-09:09 | 2912.71 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 202.12 | 23-JUL-18:10 | 491.84 | 06-JUL-04:00 |
August | 2337.76 | 01-AUG-14:09 | 1534.02 | 01-AUG-08:09 | 2912.71 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.87 | 08-AUG-16:00 | 813.51 | 27-AUG-06:00 |
September | 2337.76 | 01-SEP-14:09 | 1534.02 | 01-SEP-08:09 | 2912.71 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 01-SEP-15:00 | 1093.61 | 20-SEP-01:00 |
October | 2337.76 | 02-OCT-14:09 | 1534.02 | 02-OCT-08:09 | 2912.71 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1415.40 | 31-OCT-20:05 |
November | 2337.76 | 01-NOV-14:09 | 1534.02 | 01-NOV-08:09 | 2912.71 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2323.09 | 22-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 1534.02 | 01-DEC-09:09 | 2912.71 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3673.24 | 16-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1534.02 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.84 | |||||
Maximum of Months | 2337.76 | 1534.02 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 202.12 | 4101.57 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1485.24 | 02-JAN-09:09 | 437.18 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3687.61 | 04-JAN-05:59 |
February | 2337.76 | 01-FEB-15:09 | 1485.24 | 01-FEB-09:09 | 437.18 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4105.82 | 12-FEB-23:00 |
March | 2337.76 | 01-MAR-15:09 | 1485.24 | 01-MAR-09:09 | 437.18 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2254.29 | 15-MAR-05:00 |
April | 2337.76 | 01-APR-10:09 | 1485.24 | 01-APR-09:09 | 437.18 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 102.64 | 23-APR-18:05 | 1721.07 | 01-APR-21:03 |
May | 2337.76 | 01-MAY-14:09 | 1485.24 | 01-MAY-08:09 | 437.18 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.00 | 24-MAY-15:00 | 869.05 | 09-MAY-04:06 |
June | 2337.76 | 01-JUN-14:09 | 1485.24 | 01-JUN-08:09 | 437.18 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.99 | 29-JUN-20:20 | 554.74 | 09-JUN-20:10 |
July | 2337.76 | 01-JUL-10:09 | 1485.24 | 01-JUL-09:09 | 437.18 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 202.94 | 23-JUL-18:10 | 533.95 | 06-JUL-22:00 |
August | 2337.76 | 01-AUG-14:09 | 1485.24 | 01-AUG-08:09 | 437.18 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.86 | 08-AUG-16:00 | 793.46 | 27-AUG-06:00 |
September | 2337.76 | 01-SEP-14:09 | 1485.24 | 01-SEP-08:09 | 437.18 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 01-SEP-15:00 | 1038.67 | 20-SEP-01:00 |
October | 2337.76 | 02-OCT-14:09 | 1485.24 | 02-OCT-08:09 | 437.18 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1407.98 | 31-OCT-20:05 |
November | 2337.76 | 01-NOV-14:09 | 1485.24 | 01-NOV-08:09 | 437.18 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2236.11 | 23-NOV-07:55 |
December | 2337.76 | 01-DEC-15:09 | 1485.24 | 01-DEC-09:09 | 437.18 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3673.24 | 16-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1485.24 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.95 | |||||
Maximum of Months | 2337.76 | 1485.24 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 202.94 | 4105.82 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 58791.82 | 05-JAN-18:00 |
February | 0.00 | 01-FEB-00:10 | 2.58 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 50707.04 | 01-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 2.58 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 39172.72 | 15-MAR-11:10 |
April | 0.00 | 01-APR-00:10 | 2.58 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.27 | 23-APR-16:00 | 25015.21 | 04-APR-11:10 |
May | 0.00 | 01-MAY-00:10 | 2.58 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.36 | 25-MAY-17:00 | 11225.11 | 01-MAY-11:05 |
June | 0.00 | 01-JUN-00:10 | 2.58 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1284.98 | 30-JUN-11:02 | 5055.92 | 02-JUN-11:01 |
July | 0.00 | 01-JUL-00:10 | 2.58 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 646.53 | 15-JUL-13:55 | 4552.30 | 08-JUL-11:01 |
August | 0.00 | 01-AUG-00:10 | 2.58 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.65 | 08-AUG-16:00 | 5267.88 | 17-AUG-11:01 |
September | 0.00 | 01-SEP-00:10 | 2.58 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 7839.87 | 27-SEP-11:01 |
October | 0.00 | 01-OCT-00:10 | 2.58 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 20333.46 | 29-OCT-17:00 |
November | 0.00 | 01-NOV-00:10 | 2.58 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 39218.40 | 25-NOV-17:00 |
December | 0.00 | 01-DEC-00:10 | 2.58 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 57007.86 | 24-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4552.30 | ||||
Maximum of Months | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1284.98 | 58791.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 245.35 | 1361.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2722.58 |
February | 717.07 | 08-FEB-15:50 | 5888.82 | 1249.73 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.01 |
March | 3143.00 | 27-MAR-17:33 | 11041.53 | 2082.88 | 8254.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.53 |
April | 3834.59 | 24-APR-10:10 | 15458.14 | 3749.18 | 8254.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.02 |
May | 6700.83 | 25-MAY-15:00 | 5888.82 | 1249.73 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 73.78 | 0.00 |
June | 22417.06 | 30-JUN-22:22 | 0.00 | 408.91 | 3025.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.71 |
July | 23670.53 | 02-JUL-19:02 | 0.00 | 490.69 | 2722.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.73 |
August | 26813.25 | 13-AUG-19:01 | 0.00 | 572.47 | 3176.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.97 |
September | 17590.10 | 01-SEP-20:42 | 0.00 | 408.91 | 3025.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4886.82 | 04-OCT-06:03 | 2208.31 | 245.35 | 3668.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.65 |
November | 5235.42 | 09-NOV-17:35 | 7361.02 | 2499.45 | 5502.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.73 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 81.78 | 605.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2706.63 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 81.78 | 605.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26813.25 | 15458.14 | 3749.18 | 8254.25 | 0.00 | 0.00 | 0.00 | 0.00 | 73.78 | 2722.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 100699.52 | 04-JAN-14:00 | 151959.30 | 111149.26 | 32477.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1805.85 |
February | 65050.99 | 24-FEB-07:05 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1009.94 |
March | 25973.54 | 16-MAR-06:05 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 771.50 |
April | 20806.15 | 22-APR-14:50 | 24809.68 | 15520.76 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.53 |
May | 153041.78 | 19-MAY-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.92 |
June | 145003.45 | 09-JUN-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.25 |
July | 149770.43 | 08-JUL-06:03 | 12404.84 | 1378.20 | 6186.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.17 |
August | 157714.92 | 25-AUG-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 147272.25 | 02-SEP-06:02 | 15506.05 | 1722.75 | 7732.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.14 |
October | 23920.21 | 21-OCT-14:50 | 24809.68 | 15771.22 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.28 |
November | 23798.62 | 25-NOV-07:05 | 12404.84 | 1378.20 | 6186.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 739.52 |
December | 47459.66 | 02-DEC-07:05 | 12404.84 | 1378.20 | 6186.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.02 |
Annual Sum or Average | |||||||||||
Minimum of Months | 20806.15 | 12404.84 | 1378.20 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 157714.92 | 151959.30 | 111149.26 | 32477.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1805.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7372.25 | 09-JAN-17:32 | 7305.51 | 7670.12 | 14563.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.92 |
February | 7750.06 | 10-FEB-20:52 | 5259.96 | 5113.41 | 13592.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.59 |
March | 6338.16 | 15-MAR-18:42 | 4383.30 | 4261.18 | 11327.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.64 |
April | 14160.64 | 23-APR-19:01 | 0.00 | 259.73 | 3843.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.16 |
May | 16400.05 | 21-MAY-18:21 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.70 |
June | 19317.77 | 04-JUN-18:31 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.83 |
July | 13508.00 | 30-JUL-20:31 | 0.00 | 227.26 | 3362.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 |
August | 13104.45 | 27-AUG-07:01 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.31 |
September | 14604.43 | 10-SEP-19:02 | 0.00 | 162.33 | 2402.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.98 |
October | 16779.23 | 22-OCT-19:04 | 0.00 | 227.26 | 3362.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.74 |
November | 4807.76 | 10-NOV-12:40 | 2045.54 | 1534.02 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.27 |
December | 5896.08 | 22-DEC-16:42 | 8182.17 | 6136.09 | 11650.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.91 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4807.76 | 0.00 | 162.33 | 2402.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.16 | |
Maximum of Months | 19317.77 | 8182.17 | 7670.12 | 14563.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8168.69 | 13-JAN-11:20 | 12273.25 | 8911.45 | 2623.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.55 |
February | 5782.14 | 27-FEB-10:32 | 5844.40 | 5940.97 | 1748.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.86 |
March | 5560.65 | 14-MAR-10:23 | 8182.17 | 5940.97 | 1748.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.26 |
April | 3313.66 | 22-APR-13:40 | 2337.76 | 1485.24 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.63 |
May | 12786.16 | 18-MAY-20:17 | 0.00 | 227.26 | 673.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 |
June | 10983.01 | 26-JUN-20:20 | 0.00 | 194.80 | 576.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.65 |
July | 12107.90 | 02-JUL-18:18 | 0.00 | 194.80 | 432.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.34 |
August | 12024.87 | 04-AUG-20:18 | 0.00 | 194.80 | 576.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.69 |
September | 12539.85 | 07-SEP-20:57 | 0.00 | 227.26 | 673.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.53 |
October | 6262.35 | 21-OCT-14:00 | 2337.76 | 1485.24 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.07 |
November | 4132.65 | 10-NOV-12:40 | 2045.54 | 1485.24 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.72 |
December | 3154.54 | 02-DEC-13:50 | 2337.76 | 1485.24 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.17 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3154.54 | 0.00 | 194.80 | 432.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.34 | |
Maximum of Months | 12786.16 | 12273.25 | 8911.45 | 2623.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 7.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.55 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 7.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.16 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.93 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.15 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.35 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.59 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.31 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.54 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.59 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.78 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.35 | |
Maximum of Months | 0.00 | 0.00 | 7.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.16 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.641727E+11 | 48966.38 | 04-JAN-17:00 | 0.184649E+12 | 302727.41 | 09-JAN-07:10 |
February | 0.563629E+11 | 46924.80 | 01-FEB-17:00 | 0.113483E+12 | 285826.09 | 14-FEB-07:10 |
March | 0.616391E+11 | 46272.55 | 06-MAR-17:00 | 0.847436E+11 | 210850.06 | 15-MAR-06:00 |
April | 0.559242E+11 | 44854.99 | 19-APR-14:00 | 0.302912E+11 | 115344.39 | 05-APR-06:10 |
May | 0.599894E+11 | 61184.82 | 25-MAY-14:00 | 0.991671E+10 | 48526.92 | 01-MAY-06:19 |
June | 0.652158E+11 | 70927.31 | 29-JUN-15:00 | 0.818810E+10 | 5146.81 | 01-JUN-11:09 |
July | 0.719434E+11 | 67071.89 | 15-JUL-14:09 | 0.821300E+10 | 5092.52 | 03-JUL-11:09 |
August | 0.695035E+11 | 66780.84 | 08-AUG-14:00 | 0.822074E+10 | 5059.20 | 01-AUG-11:20 |
September | 0.576882E+11 | 61647.59 | 01-SEP-14:09 | 0.800901E+10 | 12802.10 | 23-SEP-06:30 |
October | 0.592313E+11 | 47727.82 | 28-OCT-16:00 | 0.186312E+11 | 59891.69 | 30-OCT-06:19 |
November | 0.585943E+11 | 46281.91 | 25-NOV-17:19 | 0.574905E+11 | 147716.95 | 25-NOV-07:10 |
December | 0.637631E+11 | 48601.29 | 19-DEC-17:00 | 0.162329E+12 | 286799.56 | 25-DEC-09:09 |
Annual Sum or Average | 0.744028E+12 | 0.694164E+12 | ||||
Minimum of Months | 0.559242E+11 | 44854.99 | 0.800901E+10 | 5059.20 | ||
Maximum of Months | 0.719434E+11 | 70927.31 | 0.184649E+12 | 302727.41 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.230211E+11 | 0.456456E+10 | 0.163682E+11 | 0.00 | 0.181231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209584E+10 | 0.00 | 0.00 |
February | 0.207593E+11 | 0.364841E+10 | 0.148500E+11 | 0.00 | 0.152017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190347E+10 | 0.00 | 0.00 |
March | 0.234762E+11 | 0.339543E+10 | 0.167807E+11 | 0.00 | 0.158495E+11 | 0.00 | 0.00 | 956911.97 | 0.00 | 0.00 | 0.213634E+10 | 0.00 | 0.00 |
April | 0.218306E+11 | 0.263830E+10 | 0.159462E+11 | 0.00 | 0.126234E+11 | 0.00 | 0.00 | 0.992321E+09 | 0.00 | 0.00 | 0.189334E+10 | 0.00 | 0.00 |
May | 0.219159E+11 | 0.223076E+10 | 0.165744E+11 | 0.00 | 0.107964E+11 | 0.00 | 0.00 | 0.721220E+10 | 0.00 | 0.00 | 0.125971E+10 | 0.00 | 0.00 |
June | 0.216112E+11 | 0.191883E+10 | 0.162059E+11 | 0.00 | 0.104324E+11 | 0.00 | 0.00 | 0.141810E+11 | 0.00 | 0.00 | 0.866432E+09 | 0.00 | 0.00 |
July | 0.214171E+11 | 0.206936E+10 | 0.163148E+11 | 0.00 | 0.107335E+11 | 0.00 | 0.00 | 0.204280E+11 | 0.00 | 0.00 | 0.980744E+09 | 0.00 | 0.00 |
August | 0.227350E+11 | 0.247162E+10 | 0.167807E+11 | 0.00 | 0.108726E+11 | 0.00 | 0.00 | 0.159777E+11 | 0.00 | 0.00 | 0.665904E+09 | 0.00 | 0.00 |
September | 0.218747E+11 | 0.300239E+10 | 0.159462E+11 | 0.00 | 0.103642E+11 | 0.00 | 0.00 | 0.546505E+10 | 0.00 | 0.00 | 0.103569E+10 | 0.00 | 0.00 |
October | 0.226608E+11 | 0.377368E+10 | 0.163682E+11 | 0.00 | 0.126842E+11 | 0.00 | 0.00 | 0.182743E+10 | 0.00 | 0.00 | 0.191697E+10 | 0.00 | 0.00 |
November | 0.222084E+11 | 0.424030E+10 | 0.158468E+11 | 0.00 | 0.142311E+11 | 0.00 | 0.00 | 57909532.87 | 0.00 | 0.00 | 0.200978E+10 | 0.00 | 0.00 |
December | 0.229904E+11 | 0.472031E+10 | 0.163148E+11 | 0.00 | 0.176367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210090E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.266501E+12 | 0.386740E+11 | 0.194297E+12 | 0.159549E+12 | 0.00 | 0.661425E+11 | 0.188651E+11 | ||||||
Minimum of Months | 0.207593E+11 | 0.191883E+10 | 0.148500E+11 | 0.00 | 0.103642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665904E+09 | 0.00 | 0.00 |
Maximum of Months | 0.234762E+11 | 0.472031E+10 | 0.167807E+11 | 0.00 | 0.181231E+11 | 0.00 | 0.00 | 0.204280E+11 | 0.00 | 0.00 | 0.213634E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.175835E+12 | 0.00 | 0.881384E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.105430E+12 | 0.00 | 0.805262E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.757624E+11 | 0.00 | 0.898120E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.217674E+11 | 0.00 | 0.852379E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.129854E+10 | 0.00 | 0.861817E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 243704.66 | 0.00 | 0.818786E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.821300E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.822074E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 77558111.36 | 0.00 | 0.793145E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.103452E+11 | 0.00 | 0.828602E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.493095E+11 | 0.00 | 0.818101E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.153668E+12 | 0.00 | 0.866078E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.593494E+12 | 0.100670E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.793145E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.175835E+12 | 0.00 | 0.898120E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 20551.52 | 02-JAN-16:30 | 3371.20 | 01-JAN-06:10 | 10740.89 | 02-JAN-09:09 | 0.00 | 14722.83 | 01-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 20551.52 | 01-FEB-17:10 | 3371.20 | 01-FEB-06:10 | 10740.89 | 01-FEB-09:09 | 0.00 | 13811.51 | 14-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 20551.52 | 01-MAR-17:00 | 3371.20 | 01-MAR-06:10 | 10740.89 | 01-MAR-09:09 | 0.00 | 12698.92 | 15-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 20201.17 | 21-APR-16:00 | 3371.20 | 01-APR-05:10 | 10740.89 | 01-APR-09:09 | 0.00 | 10593.47 | 05-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 20124.81 | 04-MAY-16:00 | 3371.20 | 01-MAY-19:30 | 10740.89 | 01-MAY-08:09 | 0.00 | 9886.63 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 19965.08 | 09-JUN-16:00 | 3371.20 | 01-JUN-19:00 | 10740.89 | 01-JUN-08:09 | 0.00 | 9313.28 | 25-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 19982.47 | 11-JUL-16:00 | 3371.20 | 01-JUL-20:19 | 10740.89 | 01-JUL-09:09 | 0.00 | 10139.13 | 23-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 20043.29 | 31-AUG-08:09 | 3371.20 | 01-AUG-19:49 | 10740.89 | 01-AUG-08:09 | 0.00 | 9282.39 | 30-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 20326.15 | 30-SEP-16:00 | 3371.20 | 01-SEP-05:10 | 10740.89 | 01-SEP-08:09 | 0.00 | 9512.13 | 23-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 20551.52 | 27-OCT-16:00 | 3371.20 | 01-OCT-05:10 | 10740.89 | 02-OCT-08:09 | 0.00 | 10177.09 | 30-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 20551.52 | 01-NOV-16:00 | 3371.20 | 01-NOV-05:10 | 10740.89 | 01-NOV-08:09 | 0.00 | 11533.82 | 26-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 20551.52 | 01-DEC-16:19 | 3371.20 | 01-DEC-06:10 | 10740.89 | 01-DEC-09:09 | 0.00 | 14640.95 | 24-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 19965.08 | 3371.20 | 10740.89 | 0.00 | 9282.39 | 0.00 | 0.00 | |||||
Maximum of Months | 20551.52 | 3371.20 | 10740.89 | 0.00 | 14722.83 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 1406.23 | 02-JAN-07:40 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 1406.23 | 01-FEB-07:30 | 0.00 | 0.00 |
March | 437.18 | 31-MAR-14:50 | 0.00 | 0.00 | 1406.23 | 01-MAR-11:20 | 0.00 | 0.00 |
April | 10351.55 | 23-APR-15:00 | 0.00 | 0.00 | 1406.23 | 01-APR-11:09 | 0.00 | 0.00 |
May | 22975.44 | 25-MAY-14:00 | 0.00 | 0.00 | 1406.23 | 01-MAY-11:50 | 0.00 | 0.00 |
June | 32463.97 | 29-JUN-15:00 | 0.00 | 0.00 | 1406.23 | 01-JUN-07:10 | 0.00 | 0.00 |
July | 30175.09 | 15-JUL-14:09 | 0.00 | 0.00 | 1406.23 | 08-JUL-17:10 | 0.00 | 0.00 |
August | 28742.32 | 08-AUG-14:00 | 0.00 | 0.00 | 1406.23 | 04-AUG-07:19 | 0.00 | 0.00 |
September | 23103.34 | 01-SEP-14:09 | 0.00 | 0.00 | 1406.23 | 01-SEP-17:10 | 0.00 | 0.00 |
October | 9363.08 | 19-OCT-14:00 | 0.00 | 0.00 | 1406.23 | 01-OCT-08:09 | 0.00 | 0.00 |
November | 3696.62 | 01-NOV-13:00 | 0.00 | 0.00 | 1406.23 | 01-NOV-07:10 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 1406.23 | 02-DEC-07:19 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 1406.23 | 0.00 | 0.00 | ||
Maximum of Months | 32463.97 | 0.00 | 0.00 | 1406.23 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 48966.38 | 04-JAN-17:00 | 20551.52 | 10740.89 | 3371.20 | 0.00 | 12896.55 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46924.80 | 01-FEB-17:00 | 20551.52 | 10740.89 | 3371.20 | 0.00 | 10854.97 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 46272.55 | 06-MAR-17:00 | 20551.52 | 10740.89 | 3371.20 | 0.00 | 10202.72 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44854.99 | 19-APR-14:00 | 19851.54 | 10740.89 | 0.00 | 0.00 | 9487.03 | 0.00 | 0.00 | 3369.30 | 0.00 |
May | 61184.82 | 25-MAY-14:00 | 19494.28 | 10740.89 | 0.00 | 0.00 | 6568.00 | 0.00 | 0.00 | 22975.44 | 0.00 |
June | 70927.31 | 29-JUN-15:00 | 19245.75 | 10740.89 | 0.00 | 0.00 | 7070.48 | 0.00 | 0.00 | 32463.97 | 0.00 |
July | 67071.89 | 15-JUL-14:09 | 17744.86 | 10740.89 | 0.00 | 0.00 | 7004.83 | 0.00 | 0.00 | 30175.09 | 0.00 |
August | 66780.84 | 08-AUG-14:00 | 18990.57 | 10740.89 | 0.00 | 0.00 | 6900.84 | 0.00 | 0.00 | 28742.32 | 0.00 |
September | 61647.59 | 01-SEP-14:09 | 19638.39 | 10740.89 | 0.00 | 0.00 | 6758.74 | 0.00 | 0.00 | 23103.34 | 0.00 |
October | 47727.82 | 28-OCT-16:00 | 20551.52 | 10740.89 | 3371.20 | 0.00 | 9487.03 | 0.00 | 0.00 | 2170.95 | 0.00 |
November | 46281.91 | 25-NOV-17:19 | 20551.52 | 10740.89 | 3371.20 | 0.00 | 10212.07 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 48601.29 | 19-DEC-17:00 | 20551.52 | 10740.89 | 3371.20 | 0.00 | 12531.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 44854.99 | 17744.86 | 10740.89 | 0.00 | 0.00 | 6568.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70927.31 | 20551.52 | 10740.89 | 3371.20 | 0.00 | 12896.55 | 0.00 | 0.00 | 32463.97 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 300867.41 | 09-JAN-07:10 | 0.00 | 6206.89 | 25-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 283966.09 | 14-FEB-07:10 | 0.00 | 6347.47 | 24-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 206258.51 | 15-MAR-06:00 | 0.00 | 6341.88 | 03-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 113484.39 | 05-APR-06:10 | 0.00 | 6134.54 | 04-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 43944.47 | 01-MAY-06:19 | 0.00 | 5694.92 | 03-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 392.42 | 03-JUN-06:00 | 0.00 | 5146.81 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 5092.52 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 5059.20 | 01-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 8197.68 | 23-SEP-06:30 | 0.00 | 5067.40 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 58031.69 | 30-OCT-06:19 | 0.00 | 5114.12 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 143090.37 | 25-NOV-07:10 | 0.00 | 5288.09 | 28-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 284487.02 | 24-DEC-09:09 | 0.00 | 5871.63 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5059.20 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 300867.41 | 0.00 | 6347.47 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.83 | 18.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11.50 | 19.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11.00 | 19.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5.83 | 20.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.33 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.53 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.83 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.83 | 20.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14.67 | 18.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.83 | 19.22 | 0.00 | 0.50 | 24.48 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.83 | 20.51 | 0.00 | 0.00 | 0.17 | 24.53 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.00 | 18.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8.50 | 19.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6.00 | 19.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2.17 | 20.22 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.49 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 24.50 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 24.50 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 24.49 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.48 | 0.00 | 0.00 |
October | 0.33 | 20.49 | 0.00 | 0.00 | 0.83 | 24.48 | 0.00 | 0.00 |
November | 4.50 | 20.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11.33 | 18.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.83 | 19.34 | 0.00 | 38.33 | 24.49 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.00 | 20.49 | 0.00 | 0.00 | 12.17 | 24.50 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.17 | 17.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10.00 | 19.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8.50 | 19.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4.17 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.33 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.46 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.49 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.46 | 0.00 | 0.00 |
October | 1.00 | 20.46 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 0.00 |
November | 6.17 | 19.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15.50 | 18.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.83 | 18.90 | 0.00 | 4.33 | 24.48 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.17 | 20.46 | 0.00 | 0.00 | 1.50 | 24.49 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5.50 | 10.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11.67 | 12.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70.17 | 12.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65.67 | 13.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16.17 | 14.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6.17 | 15.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6.83 | 13.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 77.00 | 13.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 70.83 | 12.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23.17 | 12.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 353.17 | 12.91 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.00 | 15.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 414.00 | 21.11 | 414.00 | 21.11 |
February | 376.00 | 21.11 | 376.00 | 21.11 | 376.00 | 21.11 |
March | 422.00 | 21.11 | 419.50 | 21.11 | 419.50 | 21.11 |
April | 405.00 | 21.42 | 264.33 | 21.11 | 264.33 | 21.11 |
May | 341.33 | 22.84 | 30.17 | 22.27 | 17.67 | 21.12 |
June | 263.00 | 23.60 | 139.83 | 23.87 | 76.50 | 23.85 |
July | 108.00 | 23.78 | 243.17 | 23.89 | 80.00 | 23.89 |
August | 119.00 | 23.73 | 220.67 | 23.89 | 67.83 | 23.89 |
September | 341.00 | 23.27 | 39.00 | 23.87 | 24.17 | 23.86 |
October | 414.00 | 21.78 | 83.17 | 21.11 | 83.17 | 21.11 |
November | 399.00 | 21.15 | 331.50 | 21.11 | 331.50 | 21.11 |
December | 415.00 | 21.11 | 415.00 | 21.11 | 415.00 | 21.11 |
Annual Sum or Average | 4017.33 | 21.86 | 2976.33 | 21.72 | 2569.67 | 21.38 |
Minimum of Months | 108.00 | 21.11 | 30.17 | 21.11 | 17.67 | 21.11 |
Maximum of Months | 422.00 | 23.78 | 419.50 | 23.89 | 419.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 402.83 | 21.11 | 402.83 | 21.11 |
February | 376.00 | 21.19 | 308.67 | 21.11 | 308.67 | 21.11 |
March | 422.00 | 21.44 | 232.00 | 21.11 | 232.00 | 21.11 |
April | 399.50 | 22.79 | 28.00 | 21.12 | 28.00 | 21.12 |
May | 209.00 | 23.67 | 65.67 | 23.89 | 0.00 | 0.00 |
June | 91.50 | 23.88 | 218.83 | 23.89 | 49.50 | 23.89 |
July | 44.83 | 23.89 | 368.33 | 23.89 | 44.00 | 23.89 |
August | 37.67 | 23.88 | 340.67 | 23.89 | 34.83 | 23.89 |
September | 95.17 | 23.75 | 80.83 | 23.89 | 13.83 | 23.89 |
October | 353.33 | 23.14 | 1.83 | 21.11 | 1.83 | 21.11 |
November | 399.00 | 21.80 | 142.33 | 21.12 | 142.33 | 21.12 |
December | 415.00 | 21.11 | 386.00 | 21.11 | 386.00 | 21.11 |
Annual Sum or Average | 3257.00 | 22.06 | 2576.00 | 22.27 | 1643.83 | 21.35 |
Minimum of Months | 37.67 | 21.11 | 1.83 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 422.00 | 23.89 | 402.83 | 23.89 | 402.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 392.83 | 21.11 | 392.83 | 21.11 |
February | 376.00 | 21.22 | 284.33 | 21.11 | 284.33 | 21.11 |
March | 422.00 | 21.30 | 273.17 | 21.11 | 273.17 | 21.11 |
April | 382.00 | 22.02 | 104.33 | 21.21 | 100.50 | 21.11 |
May | 222.67 | 23.08 | 84.33 | 23.70 | 5.83 | 21.11 |
June | 119.83 | 23.59 | 221.17 | 23.89 | 46.83 | 23.89 |
July | 55.33 | 23.79 | 364.33 | 23.89 | 44.00 | 23.89 |
August | 32.50 | 23.59 | 343.83 | 23.89 | 17.50 | 23.89 |
September | 118.33 | 23.03 | 142.17 | 23.89 | 9.50 | 23.89 |
October | 318.83 | 22.06 | 52.67 | 22.75 | 21.50 | 21.11 |
November | 398.50 | 21.43 | 182.83 | 21.11 | 182.83 | 21.11 |
December | 415.00 | 21.11 | 398.33 | 21.11 | 398.33 | 21.11 |
Annual Sum or Average | 3275.00 | 21.75 | 2844.33 | 22.27 | 1777.17 | 21.29 |
Minimum of Months | 32.50 | 21.11 | 52.67 | 21.11 | 5.83 | 21.11 |
Maximum of Months | 422.00 | 23.79 | 398.33 | 23.89 | 398.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 404.50 | 21.11 | 404.50 | 21.11 |
February | 376.00 | 21.13 | 321.33 | 21.11 | 321.33 | 21.11 |
March | 422.00 | 21.15 | 326.33 | 21.11 | 326.33 | 21.11 |
April | 393.67 | 21.72 | 168.67 | 21.11 | 168.67 | 21.11 |
May | 291.50 | 22.72 | 67.17 | 23.41 | 11.50 | 21.11 |
June | 166.50 | 23.35 | 171.67 | 23.88 | 50.83 | 23.86 |
July | 55.83 | 23.58 | 318.00 | 23.89 | 29.17 | 23.89 |
August | 46.67 | 23.22 | 299.50 | 23.89 | 0.67 | 23.89 |
September | 177.00 | 22.51 | 111.50 | 23.89 | 6.00 | 23.88 |
October | 351.67 | 21.60 | 81.17 | 21.87 | 59.00 | 21.11 |
November | 399.00 | 21.22 | 251.00 | 21.11 | 251.00 | 21.11 |
December | 415.00 | 21.11 | 408.17 | 21.11 | 408.17 | 21.11 |
Annual Sum or Average | 3508.83 | 21.63 | 2929.00 | 22.04 | 2037.17 | 21.23 |
Minimum of Months | 46.67 | 21.11 | 67.17 | 21.11 | 0.67 | 21.11 |
Maximum of Months | 422.00 | 23.58 | 408.17 | 23.89 | 408.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10984 | 14.53116 | -0.8212 | 19.35201 |
February | 376.00000 | 21.10987 | 16.34401 | -0.7813 | 18.00028 |
March | 422.00000 | 21.10987 | 20.74231 | -0.7221 | 16.14863 |
April | 405.00000 | 21.41369 | 25.49416 | -0.5338 | 11.70157 |
May | 418.00000 | 23.02401 | 37.21191 | -1.0344 | 29.95463 |
June | 408.00000 | 23.70058 | 49.97773 | -0.6596 | 15.11612 |
July | 415.00000 | 23.85970 | 55.05453 | -0.5050 | 10.54371 |
August | 422.00000 | 23.84159 | 54.44410 | -0.5315 | 11.17157 |
September | 405.00000 | 23.36375 | 44.02890 | -0.8290 | 20.87717 |
October | 414.00000 | 21.77969 | 35.46809 | -0.3201 | 8.36776 |
November | 399.00000 | 21.15168 | 24.49479 | -0.6294 | 13.72223 |
December | 415.00000 | 21.10986 | 15.99365 | -0.7918 | 18.36575 |
Annual Sum or Average | 4913.00000 | 22.22547 | 32.96040 | -0.6794 | 16.10597 |
Minimum of Months | 376.00000 | 21.10984 | 14.53116 | -1.0344 | 8.36776 |
Maximum of Months | 422.00000 | 23.85970 | 55.05453 | -0.3201 | 29.95463 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09683 | 17.02186 | -0.6885 | 15.13047 |
February | 376.00000 | 21.17578 | 19.79352 | -0.6213 | 13.37311 |
March | 422.00000 | 21.42513 | 24.72310 | -0.5037 | 11.04187 |
April | 405.00000 | 22.79504 | 27.77905 | -0.1043 | 6.77997 |
May | 418.00000 | 23.77909 | 35.41896 | -0.6648 | 15.14362 |
June | 408.00000 | 23.89688 | 47.00901 | -0.4831 | 10.14227 |
July | 415.00000 | 23.90588 | 52.02081 | -0.4092 | 8.59687 |
August | 422.00000 | 23.90213 | 52.18200 | -0.4268 | 8.91620 |
September | 405.00000 | 23.86227 | 42.00698 | -0.5725 | 12.11852 |
October | 414.00000 | 23.24921 | 35.95159 | 0.08058 | 6.17176 |
November | 399.00000 | 21.78786 | 27.92254 | -0.3790 | 9.36887 |
December | 415.00000 | 21.09871 | 19.09557 | -0.6603 | 14.33918 |
Annual Sum or Average | 4913.00000 | 22.67566 | 33.52938 | -0.4523 | 10.91967 |
Minimum of Months | 376.00000 | 21.09683 | 17.02186 | -0.6885 | 6.17176 |
Maximum of Months | 422.00000 | 23.90588 | 52.18200 | 0.08058 | 15.14362 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10970 | 10.79516 | -0.7260 | 16.36039 |
February | 376.00000 | 21.21757 | 12.73306 | -0.6228 | 13.86595 |
March | 422.00000 | 21.29789 | 16.76937 | -0.5598 | 12.49939 |
April | 405.00000 | 22.12563 | 20.66160 | -0.2683 | 8.80896 |
May | 418.00000 | 23.45031 | 32.58816 | -0.7604 | 19.55767 |
June | 408.00000 | 23.79976 | 46.25048 | -0.5007 | 11.01294 |
July | 415.00000 | 23.87372 | 51.41749 | -0.3825 | 8.28950 |
August | 422.00000 | 23.86219 | 50.27456 | -0.3910 | 8.54895 |
September | 405.00000 | 23.63389 | 39.42398 | -0.5844 | 13.56814 |
October | 414.00000 | 22.47886 | 30.02307 | -0.0688 | 7.60477 |
November | 399.00000 | 21.43650 | 20.72141 | -0.4747 | 10.98890 |
December | 415.00000 | 21.10964 | 12.32225 | -0.7188 | 16.10196 |
Annual Sum or Average | 4913.00000 | 22.46029 | 28.80632 | -0.5045 | 12.26455 |
Minimum of Months | 376.00000 | 21.10964 | 10.79516 | -0.7604 | 7.60477 |
Maximum of Months | 422.00000 | 23.87372 | 51.41749 | -0.0688 | 19.55767 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10971 | 10.78426 | -0.7650 | 17.56165 |
February | 376.00000 | 21.13214 | 12.75632 | -0.6826 | 15.23781 |
March | 422.00000 | 21.14828 | 16.86361 | -0.6351 | 13.96109 |
April | 405.00000 | 21.77607 | 21.63352 | -0.3799 | 10.03244 |
May | 418.00000 | 23.07040 | 34.57740 | -0.9214 | 25.98289 |
June | 408.00000 | 23.66800 | 48.16269 | -0.5896 | 13.58356 |
July | 415.00000 | 23.84530 | 52.28282 | -0.4343 | 9.30435 |
August | 422.00000 | 23.81049 | 50.59905 | -0.4554 | 9.88253 |
September | 405.00000 | 23.28520 | 41.53841 | -0.7298 | 18.68389 |
October | 414.00000 | 21.95070 | 31.53725 | -0.2145 | 8.37036 |
November | 399.00000 | 21.22396 | 21.01890 | -0.5636 | 12.39548 |
December | 415.00000 | 21.10985 | 12.31106 | -0.7581 | 17.30544 |
Annual Sum or Average | 4913.00000 | 22.27149 | 29.64952 | -0.5938 | 14.35970 |
Minimum of Months | 376.00000 | 21.10971 | 10.78426 | -0.9214 | 8.37036 |
Maximum of Months | 422.00000 | 23.84530 | 52.28282 | -0.2145 | 25.98289 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 1325910.73 | 403073.20 | 0.67 | 1108257.96 | 217652.77 | 0.00 | 0.07 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 837.41 | 23-APR-16:00 | 698.51 | 23-APR-16:00 | 138.89 | 23-APR-16:00 | 254.32 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.193340E+10 | 0.508204E+09 | 139.68 | 0.155898E+10 | 0.374419E+09 | 0.00 | 0.82 | 25-MAY-15:00 | 0.00 | 01-MAY-00:10 | 11742.23 | 25-MAY-15:00 | 8838.67 | 25-MAY-15:00 | 3756.57 | 26-MAY-10:50 | 2958.10 | 25-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.607727E+10 | 0.152002E+10 | 278.02 | 0.431621E+10 | 0.176106E+10 | 0.00 | 1.00 | 25-JUN-18:42 | 0.00 | 01-JUN-00:10 | 32210.61 | 27-JUN-20:53 | 21215.80 | 30-JUN-20:28 | 15766.41 | 27-JUN-21:42 | 6901.86 | 25-JUN-18:42 | 0.00 | 01-JUN-00:10 |
July | 0.101571E+11 | 0.246722E+10 | 358.66 | 0.678477E+10 | 0.337233E+10 | 0.00 | 1.00 | 02-JUL-19:02 | 0.00 | 01-JUL-00:05 | 33366.58 | 03-JUL-23:03 | 21372.13 | 02-JUL-19:02 | 19814.76 | 04-JUL-00:40 | 6976.88 | 03-JUL-23:03 | 0.00 | 01-JUL-00:05 |
August | 0.696046E+10 | 0.169781E+10 | 318.10 | 0.465526E+10 | 0.230520E+10 | 0.00 | 1.00 | 08-AUG-20:33 | 0.00 | 01-AUG-00:10 | 32453.14 | 31-AUG-20:55 | 23265.21 | 13-AUG-19:01 | 17016.32 | 28-AUG-21:25 | 6867.65 | 08-AUG-20:33 | 0.00 | 01-AUG-00:10 |
September | 0.815616E+09 | 0.207769E+09 | 140.56 | 0.622384E+09 | 0.193232E+09 | 0.00 | 1.00 | 01-SEP-20:40 | 0.00 | 01-SEP-00:10 | 29897.52 | 01-SEP-20:40 | 16001.24 | 01-SEP-20:40 | 13957.24 | 01-SEP-20:42 | 6365.54 | 01-SEP-20:40 | 0.00 | 01-SEP-00:10 |
October | 7635045.11 | 2154454.00 | 13.74 | 7110356.15 | 524688.95 | 0.00 | 0.11 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1187.29 | 19-OCT-15:00 | 1090.65 | 19-OCT-15:00 | 96.64 | 19-OCT-15:00 | 334.06 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.259528E+11 | 0.640358E+10 | 1249.43 | 0.179458E+11 | 0.800698E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.101571E+11 | 0.246722E+10 | 358.66 | 0.678477E+10 | 0.337233E+10 | 0.00 | 1.00 | 0.00 | 33366.58 | 23265.21 | 19814.76 | 6976.88 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 3041743.78 | 956728.77 | 1.33 | 2968333.37 | 73410.41 | 0.00 | 0.03 | 31-MAR-14:50 | 0.00 | 01-MAR-00:10 | 1393.26 | 31-MAR-14:50 | 1369.82 | 31-MAR-14:50 | 25.03 | 31-MAR-16:00 | 437.14 | 31-MAR-14:50 | 0.00 | 01-MAR-00:10 |
April | 0.282742E+10 | 0.860163E+09 | 123.65 | 0.268124E+10 | 0.146190E+09 | 0.00 | 0.41 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 24673.58 | 23-APR-16:00 | 20211.18 | 23-APR-16:00 | 4462.40 | 23-APR-16:00 | 7675.85 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.190123E+11 | 0.553746E+10 | 336.81 | 0.157315E+11 | 0.328080E+10 | 0.00 | 1.00 | 18-MAY-06:03 | 0.00 | 01-MAY-00:10 | 147235.27 | 26-MAY-06:02 | 109033.53 | 19-MAY-06:03 | 48465.33 | 25-MAY-06:03 | 34994.55 | 26-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.357297E+11 | 0.100710E+11 | 360.74 | 0.258387E+11 | 0.989101E+10 | 0.00 | 1.00 | 07-JUN-06:03 | 0.00 | 01-JUN-00:10 | 158706.71 | 25-JUN-08:62 | 123770.30 | 18-JUN-08:62 | 77670.15 | 23-JUN-06:03 | 38614.54 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.508127E+11 | 0.140117E+11 | 382.68 | 0.343644E+11 | 0.164483E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 161499.41 | 30-JUL-08:62 | 95701.28 | 06-JUL-06:02 | 81009.19 | 05-JUL-06:03 | 38144.05 | 30-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.397780E+11 | 0.109589E+11 | 368.72 | 0.266098E+11 | 0.131682E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 153691.53 | 30-AUG-06:02 | 100889.77 | 20-AUG-08:62 | 79593.69 | 30-AUG-06:04 | 36162.49 | 30-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.140757E+11 | 0.410084E+10 | 319.41 | 0.111044E+11 | 0.297128E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 149312.99 | 01-SEP-06:02 | 92715.29 | 02-SEP-06:02 | 73987.36 | 01-SEP-06:02 | 35412.59 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.510415E+10 | 0.153648E+10 | 175.37 | 0.435285E+10 | 0.751300E+09 | 0.00 | 0.36 | 02-OCT-15:00 | 0.00 | 01-OCT-00:10 | 21246.93 | 02-OCT-15:00 | 17916.30 | 19-OCT-15:00 | 6822.20 | 07-OCT-14:30 | 6148.88 | 02-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.188901E+09 | 57787352.19 | 11.00 | 0.142386E+09 | 46515642.25 | 0.00 | 0.21 | 01-NOV-14:00 | 0.00 | 01-NOV-00:10 | 12299.47 | 01-NOV-14:00 | 9192.24 | 01-NOV-14:00 | 3107.23 | 01-NOV-14:00 | 3696.62 | 01-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.167532E+12 | 0.471353E+11 | 2079.71 | 0.120828E+12 | 0.467037E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.508127E+11 | 0.140117E+11 | 382.68 | 0.343644E+11 | 0.164483E+11 | 0.00 | 1.00 | 0.00 | 161499.41 | 123770.30 | 81009.19 | 38614.54 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 648.10 | 183.20 | 1.33 | 648.10 | 0.00 | 0.00 | 0.00 | 31-MAR-14:10 | 0.00 | 01-MAR-00:10 | 0.25 | 31-MAR-14:10 | 0.25 | 31-MAR-14:10 | 0.00 | 01-MAR-00:10 | 0.07 | 31-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.252793E+09 | 65303464.83 | 56.47 | 0.236048E+09 | 16745108.52 | 0.00 | 1.00 | 23-APR-19:10 | 0.00 | 01-APR-00:10 | 18763.68 | 23-APR-19:10 | 16946.52 | 23-APR-19:10 | 2801.09 | 23-APR-20:21 | 4117.39 | 23-APR-19:10 | 0.00 | 01-APR-00:10 |
May | 0.277770E+10 | 0.681363E+09 | 231.50 | 0.238621E+10 | 0.391487E+09 | 0.00 | 1.00 | 16-MAY-20:11 | 0.00 | 01-MAY-00:10 | 19428.89 | 25-MAY-20:32 | 16629.10 | 28-MAY-18:21 | 6770.10 | 26-MAY-20:15 | 4269.56 | 25-MAY-20:32 | 0.00 | 01-MAY-00:10 |
June | 0.636943E+10 | 0.153119E+10 | 328.79 | 0.472331E+10 | 0.164612E+10 | 0.00 | 1.00 | 04-JUN-18:31 | 0.00 | 01-JUN-00:10 | 20800.30 | 19-JUN-20:20 | 18072.01 | 04-JUN-18:31 | 11605.39 | 19-JUN-20:22 | 4418.80 | 27-JUN-20:17 | 0.00 | 01-JUN-00:10 |
July | 0.995361E+10 | 0.231783E+10 | 395.83 | 0.687091E+10 | 0.308270E+10 | 0.00 | 1.00 | 02-JUL-18:12 | 0.00 | 01-JUL-00:05 | 21344.57 | 03-JUL-23:40 | 14734.93 | 05-JUL-20:11 | 12704.55 | 04-JUL-03:07 | 4488.98 | 03-JUL-22:13 | 0.00 | 01-JUL-00:05 |
August | 0.825017E+10 | 0.189715E+10 | 359.22 | 0.571693E+10 | 0.253324E+10 | 0.00 | 1.00 | 01-AUG-02:33 | 0.00 | 01-AUG-00:10 | 20790.77 | 31-AUG-20:17 | 15524.95 | 13-AUG-18:17 | 11023.49 | 28-AUG-20:12 | 4412.47 | 31-AUG-20:17 | 0.00 | 01-AUG-00:10 |
September | 0.241715E+10 | 0.576768E+09 | 226.19 | 0.199367E+10 | 0.423478E+09 | 0.00 | 1.00 | 01-SEP-00:30 | 0.00 | 01-SEP-00:10 | 20259.00 | 01-SEP-01:10 | 14930.83 | 24-SEP-18:20 | 10974.37 | 01-SEP-01:10 | 4267.21 | 01-SEP-01:10 | 0.00 | 01-SEP-00:10 |
October | 0.567450E+09 | 0.135715E+09 | 71.83 | 0.517864E+09 | 49586015.14 | 0.00 | 1.00 | 22-OCT-19:04 | 0.00 | 01-OCT-00:10 | 18055.17 | 22-OCT-19:04 | 13673.45 | 22-OCT-19:04 | 4381.72 | 22-OCT-19:04 | 3822.54 | 22-OCT-19:04 | 0.00 | 01-OCT-00:10 |
November | 2635.02 | 745.83 | 5.64 | 2497.38 | 137.64 | 0.00 | 0.00 | 17-NOV-13:00 | 0.00 | 01-NOV-00:10 | 0.41 | 17-NOV-13:00 | 0.41 | 17-NOV-13:00 | 0.06 | 01-NOV-13:00 | 0.12 | 17-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.305883E+11 | 0.720532E+10 | 1676.81 | 0.224450E+11 | 0.814335E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.995361E+10 | 0.231783E+10 | 395.83 | 0.687091E+10 | 0.308270E+10 | 0.00 | 1.00 | 0.00 | 21344.57 | 18072.01 | 12704.55 | 4488.98 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.290080E+09 | 66451431.43 | 50.86 | 0.281314E+09 | 8766066.10 | 0.00 | 0.58 | 23-APR-14:20 | 0.00 | 01-APR-00:10 | 4255.76 | 23-APR-14:20 | 3802.50 | 23-APR-14:20 | 453.26 | 23-APR-14:20 | 954.26 | 23-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.218459E+10 | 0.485171E+09 | 215.06 | 0.191825E+10 | 0.266334E+09 | 0.00 | 1.00 | 18-MAY-20:17 | 0.00 | 01-MAY-00:10 | 15463.37 | 18-MAY-20:17 | 14078.56 | 18-MAY-20:17 | 2697.95 | 25-MAY-20:18 | 3037.86 | 18-MAY-20:17 | 0.00 | 01-MAY-00:10 |
June | 0.487208E+10 | 0.105877E+10 | 340.85 | 0.373491E+10 | 0.113717E+10 | 0.00 | 1.00 | 26-JUN-20:20 | 0.00 | 01-JUN-00:10 | 16045.03 | 28-JUN-20:52 | 12263.97 | 26-JUN-20:20 | 4671.36 | 25-JUN-20:02 | 3199.37 | 28-JUN-20:52 | 0.00 | 01-JUN-00:10 |
July | 0.772193E+10 | 0.163126E+10 | 450.91 | 0.571162E+10 | 0.201031E+10 | 0.00 | 1.00 | 11-JUL-20:18 | 0.00 | 01-JUL-00:05 | 16294.14 | 30-JUL-20:31 | 13439.80 | 02-JUL-18:18 | 6221.91 | 15-JUL-21:30 | 3226.95 | 23-JUL-18:10 | 0.00 | 01-JUL-00:05 |
August | 0.680708E+10 | 0.142381E+10 | 430.26 | 0.517349E+10 | 0.163359E+10 | 0.00 | 1.00 | 08-AUG-20:42 | 0.00 | 01-AUG-00:10 | 16129.20 | 08-AUG-20:42 | 13352.67 | 04-AUG-20:18 | 5078.39 | 31-AUG-20:20 | 3224.46 | 08-AUG-20:42 | 0.00 | 01-AUG-00:10 |
September | 0.272412E+10 | 0.579675E+09 | 245.96 | 0.241362E+10 | 0.310506E+09 | 0.00 | 1.00 | 03-SEP-18:18 | 0.00 | 01-SEP-00:15 | 15717.59 | 03-SEP-18:18 | 13829.22 | 07-SEP-20:57 | 3406.14 | 01-SEP-00:42 | 3083.59 | 03-SEP-18:18 | 0.00 | 01-SEP-00:10 |
October | 0.725273E+09 | 0.153081E+09 | 64.98 | 0.693651E+09 | 31622279.62 | 0.00 | 0.89 | 19-OCT-20:33 | 0.00 | 01-OCT-00:10 | 6957.25 | 19-OCT-20:33 | 6807.44 | 19-OCT-20:33 | 625.98 | 22-OCT-12:40 | 1368.06 | 19-OCT-20:33 | 0.00 | 01-OCT-00:10 |
November | 495950.42 | 121434.85 | 1.00 | 495950.42 | 0.00 | 0.00 | 0.03 | 17-NOV-13:40 | 0.00 | 01-NOV-00:10 | 209.27 | 17-NOV-13:40 | 209.27 | 17-NOV-13:40 | 0.00 | 01-NOV-00:10 | 51.13 | 17-NOV-13:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.253257E+11 | 0.539835E+10 | 1799.89 | 0.199274E+11 | 0.539830E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.772193E+10 | 0.163126E+10 | 450.91 | 0.571162E+10 | 0.201031E+10 | 0.00 | 1.00 | 0.00 | 16294.14 | 14078.56 | 6221.91 | 3226.95 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.55 | 5.36 | 11.19 | 1.44 | 57.06 | 0.00 | 0.00 | 744.00 |
February | 29.84 | 13.38 | 16.46 | 10.71 | 45.10 | 0.00 | 0.00 | 672.00 |
March | 43.29 | 24.21 | 19.08 | 26.96 | 35.05 | 0.00 | 0.00 | 744.00 |
April | 64.53 | 40.82 | 23.71 | 54.04 | 23.95 | 0.00 | 0.00 | 720.00 |
May | 79.25 | 44.81 | 34.44 | 75.54 | 14.91 | 0.00 | 0.00 | 744.00 |
June | 83.37 | 48.23 | 35.14 | 83.41 | 10.76 | 0.17 | 0.00 | 720.00 |
July | 85.63 | 51.39 | 34.24 | 87.21 | 10.40 | 0.00 | 0.00 | 744.00 |
August | 67.44 | 38.02 | 29.43 | 66.47 | 11.44 | 0.00 | 0.00 | 744.00 |
September | 48.67 | 25.01 | 23.66 | 42.06 | 17.07 | 0.00 | 0.00 | 720.00 |
October | 28.60 | 11.18 | 17.42 | 17.09 | 25.31 | 0.00 | 0.00 | 744.00 |
November | 16.29 | 4.62 | 11.67 | 3.73 | 35.54 | 0.00 | 0.00 | 720.00 |
December | 12.98 | 3.02 | 9.96 | 0.57 | 55.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.13 | 25.90 | 22.23 | 39.26 | 28.40 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 12.98 | 3.02 | 9.96 | 0.57 | 10.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.63 | 51.39 | 35.14 | 87.21 | 57.06 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.55 | 5.36 | 11.19 | 1.44 | 57.06 | 0.00 | 0.00 | 744.00 |
February | 29.84 | 13.38 | 16.46 | 10.71 | 45.10 | 0.00 | 0.00 | 672.00 |
March | 43.29 | 24.21 | 19.08 | 26.96 | 35.05 | 0.00 | 0.00 | 744.00 |
April | 64.53 | 40.82 | 23.71 | 54.04 | 23.95 | 0.00 | 0.00 | 720.00 |
May | 79.25 | 44.81 | 34.44 | 75.54 | 14.91 | 0.00 | 0.00 | 744.00 |
June | 83.37 | 48.23 | 35.14 | 83.41 | 10.76 | 0.17 | 0.00 | 720.00 |
July | 85.63 | 51.39 | 34.24 | 87.21 | 10.40 | 0.00 | 0.00 | 744.00 |
August | 67.44 | 38.02 | 29.43 | 66.47 | 11.44 | 0.00 | 0.00 | 744.00 |
September | 48.67 | 25.01 | 23.66 | 42.06 | 17.07 | 0.00 | 0.00 | 720.00 |
October | 28.60 | 11.18 | 17.42 | 17.09 | 25.31 | 0.00 | 0.00 | 744.00 |
November | 16.29 | 4.62 | 11.67 | 3.73 | 35.54 | 0.00 | 0.00 | 720.00 |
December | 12.98 | 3.02 | 9.96 | 0.57 | 55.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.13 | 25.90 | 22.23 | 39.26 | 28.40 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 12.98 | 3.02 | 9.96 | 0.57 | 10.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.63 | 51.39 | 35.14 | 87.21 | 57.06 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.55 | 5.36 | 11.19 | 1.44 | 57.06 | 0.00 | 0.00 | 744.00 |
February | 29.84 | 13.38 | 16.46 | 10.71 | 45.10 | 0.00 | 0.00 | 672.00 |
March | 43.29 | 24.21 | 19.08 | 26.96 | 35.05 | 0.00 | 0.00 | 744.00 |
April | 64.53 | 40.82 | 23.71 | 54.04 | 23.95 | 0.00 | 0.00 | 720.00 |
May | 79.25 | 44.81 | 34.44 | 75.54 | 14.91 | 0.00 | 0.00 | 744.00 |
June | 83.37 | 48.23 | 35.14 | 83.41 | 10.76 | 0.17 | 0.00 | 720.00 |
July | 85.63 | 51.39 | 34.24 | 87.21 | 10.40 | 0.00 | 0.00 | 744.00 |
August | 67.44 | 38.02 | 29.43 | 66.47 | 11.44 | 0.00 | 0.00 | 744.00 |
September | 48.67 | 25.01 | 23.66 | 42.06 | 17.07 | 0.00 | 0.00 | 720.00 |
October | 28.60 | 11.18 | 17.42 | 17.09 | 25.31 | 0.00 | 0.00 | 744.00 |
November | 16.29 | 4.62 | 11.67 | 3.73 | 35.54 | 0.00 | 0.00 | 720.00 |
December | 12.98 | 3.02 | 9.96 | 0.57 | 55.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.13 | 25.90 | 22.23 | 39.26 | 28.40 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 12.98 | 3.02 | 9.96 | 0.57 | 10.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.63 | 51.39 | 35.14 | 87.21 | 57.06 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.55 | 5.36 | 11.19 | 1.44 | 57.06 | 0.00 | 0.00 | 744.00 |
February | 29.84 | 13.38 | 16.46 | 10.71 | 45.10 | 0.00 | 0.00 | 672.00 |
March | 43.29 | 24.21 | 19.08 | 26.96 | 35.05 | 0.00 | 0.00 | 744.00 |
April | 64.53 | 40.82 | 23.71 | 54.04 | 23.95 | 0.00 | 0.00 | 720.00 |
May | 79.25 | 44.81 | 34.44 | 75.54 | 14.91 | 0.00 | 0.00 | 744.00 |
June | 83.37 | 48.23 | 35.14 | 83.41 | 10.76 | 0.17 | 0.00 | 720.00 |
July | 85.63 | 51.39 | 34.24 | 87.21 | 10.40 | 0.00 | 0.00 | 744.00 |
August | 67.44 | 38.02 | 29.43 | 66.47 | 11.44 | 0.00 | 0.00 | 744.00 |
September | 48.67 | 25.01 | 23.66 | 42.06 | 17.07 | 0.00 | 0.00 | 720.00 |
October | 28.60 | 11.18 | 17.42 | 17.09 | 25.31 | 0.00 | 0.00 | 744.00 |
November | 16.29 | 4.62 | 11.67 | 3.73 | 35.54 | 0.00 | 0.00 | 720.00 |
December | 12.98 | 3.02 | 9.96 | 0.57 | 55.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.13 | 25.90 | 22.23 | 39.26 | 28.40 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 12.98 | 3.02 | 9.96 | 0.57 | 10.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.63 | 51.39 | 35.14 | 87.21 | 57.06 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.55 | 5.36 | 11.19 | 1.44 | 57.06 | 0.00 | 0.00 | 744.00 |
February | 29.84 | 13.38 | 16.46 | 10.71 | 45.10 | 0.00 | 0.00 | 672.00 |
March | 43.29 | 24.21 | 19.08 | 26.96 | 35.05 | 0.00 | 0.00 | 744.00 |
April | 64.53 | 40.82 | 23.71 | 54.04 | 23.95 | 0.00 | 0.00 | 720.00 |
May | 79.25 | 44.81 | 34.44 | 75.54 | 14.91 | 0.00 | 0.00 | 744.00 |
June | 83.37 | 48.23 | 35.14 | 83.41 | 10.76 | 0.17 | 0.00 | 720.00 |
July | 85.63 | 51.39 | 34.24 | 87.21 | 10.40 | 0.00 | 0.00 | 744.00 |
August | 67.44 | 38.02 | 29.43 | 66.47 | 11.44 | 0.00 | 0.00 | 744.00 |
September | 48.67 | 25.01 | 23.66 | 42.06 | 17.07 | 0.00 | 0.00 | 720.00 |
October | 28.60 | 11.18 | 17.42 | 17.09 | 25.31 | 0.00 | 0.00 | 744.00 |
November | 16.29 | 4.62 | 11.67 | 3.73 | 35.54 | 0.00 | 0.00 | 720.00 |
December | 12.98 | 3.02 | 9.96 | 0.57 | 55.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.13 | 25.90 | 22.23 | 39.26 | 28.40 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 12.98 | 3.02 | 9.96 | 0.57 | 10.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.63 | 51.39 | 35.14 | 87.21 | 57.06 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.55 | 5.36 | 11.19 | 1.44 | 57.06 | 0.00 | 0.00 | 744.00 |
February | 29.84 | 13.38 | 16.46 | 10.71 | 45.10 | 0.00 | 0.00 | 672.00 |
March | 43.29 | 24.21 | 19.08 | 26.96 | 35.05 | 0.00 | 0.00 | 744.00 |
April | 64.53 | 40.82 | 23.71 | 54.04 | 23.95 | 0.00 | 0.00 | 720.00 |
May | 79.25 | 44.81 | 34.44 | 75.54 | 14.91 | 0.00 | 0.00 | 744.00 |
June | 83.37 | 48.23 | 35.14 | 83.41 | 10.76 | 0.17 | 0.00 | 720.00 |
July | 85.63 | 51.39 | 34.24 | 87.21 | 10.40 | 0.00 | 0.00 | 744.00 |
August | 67.44 | 38.02 | 29.43 | 66.47 | 11.44 | 0.00 | 0.00 | 744.00 |
September | 48.67 | 25.01 | 23.66 | 42.06 | 17.07 | 0.00 | 0.00 | 720.00 |
October | 28.60 | 11.18 | 17.42 | 17.09 | 25.31 | 0.00 | 0.00 | 744.00 |
November | 16.29 | 4.62 | 11.67 | 3.73 | 35.54 | 0.00 | 0.00 | 720.00 |
December | 12.98 | 3.02 | 9.96 | 0.57 | 55.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.13 | 25.90 | 22.23 | 39.26 | 28.40 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 12.98 | 3.02 | 9.96 | 0.57 | 10.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.63 | 51.39 | 35.14 | 87.21 | 57.06 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.55 | 5.36 | 11.19 | 1.44 | 57.06 | 0.00 | 0.00 | 744.00 |
February | 29.84 | 13.38 | 16.46 | 10.71 | 45.10 | 0.00 | 0.00 | 672.00 |
March | 43.29 | 24.21 | 19.08 | 26.96 | 35.05 | 0.00 | 0.00 | 744.00 |
April | 64.53 | 40.82 | 23.71 | 54.04 | 23.95 | 0.00 | 0.00 | 720.00 |
May | 79.25 | 44.81 | 34.44 | 75.54 | 14.91 | 0.00 | 0.00 | 744.00 |
June | 83.37 | 48.23 | 35.14 | 83.41 | 10.76 | 0.17 | 0.00 | 720.00 |
July | 85.63 | 51.39 | 34.24 | 87.21 | 10.40 | 0.00 | 0.00 | 744.00 |
August | 67.44 | 38.02 | 29.43 | 66.47 | 11.44 | 0.00 | 0.00 | 744.00 |
September | 48.67 | 25.01 | 23.66 | 42.06 | 17.07 | 0.00 | 0.00 | 720.00 |
October | 28.60 | 11.18 | 17.42 | 17.09 | 25.31 | 0.00 | 0.00 | 744.00 |
November | 16.29 | 4.62 | 11.67 | 3.73 | 35.54 | 0.00 | 0.00 | 720.00 |
December | 12.98 | 3.02 | 9.96 | 0.57 | 55.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.13 | 25.90 | 22.23 | 39.26 | 28.40 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 12.98 | 3.02 | 9.96 | 0.57 | 10.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.63 | 51.39 | 35.14 | 87.21 | 57.06 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.55 | 5.36 | 11.19 | 1.44 | 57.06 | 0.00 | 0.00 | 744.00 |
February | 29.84 | 13.38 | 16.46 | 10.71 | 45.10 | 0.00 | 0.00 | 672.00 |
March | 43.29 | 24.21 | 19.08 | 26.96 | 35.05 | 0.00 | 0.00 | 744.00 |
April | 64.53 | 40.82 | 23.71 | 54.04 | 23.95 | 0.00 | 0.00 | 720.00 |
May | 79.25 | 44.81 | 34.44 | 75.54 | 14.91 | 0.00 | 0.00 | 744.00 |
June | 83.37 | 48.23 | 35.14 | 83.41 | 10.76 | 0.17 | 0.00 | 720.00 |
July | 85.63 | 51.39 | 34.24 | 87.21 | 10.40 | 0.00 | 0.00 | 744.00 |
August | 67.44 | 38.02 | 29.43 | 66.47 | 11.44 | 0.00 | 0.00 | 744.00 |
September | 48.67 | 25.01 | 23.66 | 42.06 | 17.07 | 0.00 | 0.00 | 720.00 |
October | 28.60 | 11.18 | 17.42 | 17.09 | 25.31 | 0.00 | 0.00 | 744.00 |
November | 16.29 | 4.62 | 11.67 | 3.73 | 35.54 | 0.00 | 0.00 | 720.00 |
December | 12.98 | 3.02 | 9.96 | 0.57 | 55.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.13 | 25.90 | 22.23 | 39.26 | 28.40 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 12.98 | 3.02 | 9.96 | 0.57 | 10.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.63 | 51.39 | 35.14 | 87.21 | 57.06 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1325.49 | 922.43 | 403.06 | 1104.81 | 1344.25 | 0.00 | 0.00 | 744.00 |
February | 1678.58 | 1134.26 | 544.32 | 1534.96 | 1132.88 | 0.00 | 0.00 | 672.00 |
March | 1478.67 | 936.14 | 542.53 | 1281.31 | 945.33 | 0.00 | 0.00 | 744.00 |
April | 1337.86 | 725.74 | 612.12 | 1137.09 | 624.78 | 0.00 | 0.00 | 720.00 |
May | 1123.80 | 383.05 | 740.75 | 958.27 | 359.48 | 0.00 | 0.00 | 744.00 |
June | 1008.19 | 267.45 | 740.74 | 904.86 | 246.31 | 0.00 | 0.00 | 720.00 |
July | 1102.23 | 347.85 | 754.38 | 1040.15 | 224.72 | 0.00 | 0.00 | 744.00 |
August | 1177.92 | 491.97 | 685.95 | 1159.17 | 269.61 | 0.00 | 0.00 | 744.00 |
September | 1263.25 | 672.85 | 590.41 | 1243.07 | 439.79 | 0.00 | 0.00 | 720.00 |
October | 1079.52 | 635.30 | 444.22 | 1005.63 | 643.05 | 0.00 | 0.00 | 744.00 |
November | 961.48 | 603.68 | 357.80 | 847.59 | 876.38 | 0.00 | 0.00 | 720.00 |
December | 1023.38 | 671.30 | 352.08 | 786.63 | 1301.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1210.32 | 646.25 | 564.07 | 1080.47 | 698.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 961.48 | 267.45 | 352.08 | 786.63 | 224.72 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1678.58 | 1134.26 | 754.38 | 1534.96 | 1344.25 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1325.49 | 922.43 | 403.06 | 1100.45 | 1342.77 | 0.00 | 0.00 | 744.00 |
February | 1678.58 | 1134.26 | 544.32 | 1531.54 | 1126.80 | 0.00 | 0.00 | 672.00 |
March | 1478.67 | 936.14 | 542.53 | 1279.49 | 936.77 | 0.00 | 0.00 | 744.00 |
April | 1337.86 | 725.74 | 612.12 | 1137.47 | 609.68 | 0.00 | 0.00 | 720.00 |
May | 1123.80 | 383.05 | 740.75 | 958.91 | 345.91 | 0.00 | 0.00 | 744.00 |
June | 1008.19 | 267.45 | 740.74 | 901.00 | 238.58 | 0.00 | 0.00 | 720.00 |
July | 1102.23 | 347.85 | 754.38 | 1031.97 | 224.22 | 0.00 | 0.00 | 744.00 |
August | 1177.92 | 491.97 | 685.95 | 1151.65 | 268.90 | 0.00 | 0.00 | 744.00 |
September | 1263.25 | 672.85 | 590.41 | 1241.46 | 428.90 | 0.00 | 0.00 | 720.00 |
October | 1079.52 | 635.30 | 444.22 | 1007.76 | 625.00 | 0.00 | 0.00 | 744.00 |
November | 961.48 | 603.68 | 357.80 | 846.91 | 865.75 | 0.00 | 0.00 | 720.00 |
December | 1023.38 | 671.30 | 352.08 | 783.28 | 1300.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1210.32 | 646.25 | 564.07 | 1077.83 | 690.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 961.48 | 267.45 | 352.08 | 783.28 | 224.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1678.58 | 1134.26 | 754.38 | 1531.54 | 1342.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 272.74 | 189.80 | 82.94 | 230.17 | 261.77 | 0.00 | 0.00 | 744.00 |
February | 345.39 | 233.39 | 112.00 | 319.58 | 217.71 | 0.00 | 0.00 | 672.00 |
March | 304.26 | 192.62 | 111.63 | 268.53 | 177.36 | 0.00 | 0.00 | 744.00 |
April | 275.28 | 149.33 | 125.95 | 244.12 | 112.46 | 0.00 | 0.00 | 720.00 |
May | 231.24 | 78.82 | 152.42 | 205.70 | 64.71 | 0.00 | 0.00 | 744.00 |
June | 207.45 | 55.03 | 152.42 | 186.47 | 45.98 | 0.00 | 0.00 | 720.00 |
July | 226.80 | 71.58 | 155.23 | 209.21 | 45.97 | 0.00 | 0.00 | 744.00 |
August | 242.37 | 101.23 | 141.14 | 237.63 | 53.34 | 0.00 | 0.00 | 744.00 |
September | 259.93 | 138.45 | 121.48 | 265.69 | 78.40 | 0.00 | 0.00 | 720.00 |
October | 222.13 | 130.72 | 91.41 | 216.34 | 114.50 | 0.00 | 0.00 | 744.00 |
November | 197.84 | 124.22 | 73.62 | 178.69 | 161.73 | 0.00 | 0.00 | 720.00 |
December | 210.58 | 138.13 | 72.45 | 164.38 | 251.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 249.04 | 132.97 | 116.07 | 226.54 | 131.79 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 197.84 | 55.03 | 72.45 | 164.38 | 45.97 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 345.39 | 233.39 | 155.23 | 319.58 | 261.77 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44338527.55 | 14363050.60 | 29975476.95 | 3848855.61 | 0.152817E+09 |
February | 72185296.75 | 32361260.33 | 39824036.42 | 25907365.04 | 0.109104E+09 |
March | 0.115947E+09 | 64835963.83 | 51110900.12 | 72216633.75 | 93883714.99 |
April | 0.167269E+09 | 0.105813E+09 | 61456301.45 | 0.140060E+09 | 62076625.17 |
May | 0.212253E+09 | 0.120013E+09 | 92239775.99 | 0.202339E+09 | 39934683.52 |
June | 0.216088E+09 | 0.125000E+09 | 91088427.67 | 0.216198E+09 | 27892827.10 |
July | 0.229345E+09 | 0.137641E+09 | 91704197.78 | 0.233587E+09 | 27859702.93 |
August | 0.180640E+09 | 0.101822E+09 | 78818274.75 | 0.178026E+09 | 30644833.79 |
September | 0.126142E+09 | 64823089.04 | 61318657.64 | 0.109028E+09 | 44255437.27 |
October | 76604016.35 | 29953058.60 | 46650957.75 | 45780967.39 | 67787591.33 |
November | 42225731.70 | 11969786.26 | 30255945.44 | 9660186.87 | 92111137.45 |
December | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 0.147301E+09 |
Annual Sum or Average | 0.151779E+10 | 0.816671E+09 | 0.701118E+09 | 0.123818E+10 | 0.895668E+09 |
Minimum of Months | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 27859702.93 |
Maximum of Months | 0.229345E+09 | 0.137641E+09 | 92239775.99 | 0.233587E+09 | 0.152817E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44338527.55 | 14363050.60 | 29975476.95 | 3848855.61 | 0.152817E+09 |
February | 72185296.75 | 32361260.33 | 39824036.42 | 25907365.04 | 0.109104E+09 |
March | 0.115947E+09 | 64835963.83 | 51110900.12 | 72216633.75 | 93883714.99 |
April | 0.167269E+09 | 0.105813E+09 | 61456301.45 | 0.140060E+09 | 62076625.17 |
May | 0.212253E+09 | 0.120013E+09 | 92239775.99 | 0.202339E+09 | 39934683.52 |
June | 0.216088E+09 | 0.125000E+09 | 91088427.67 | 0.216198E+09 | 27892827.10 |
July | 0.229345E+09 | 0.137641E+09 | 91704197.78 | 0.233587E+09 | 27859702.93 |
August | 0.180640E+09 | 0.101822E+09 | 78818274.75 | 0.178026E+09 | 30644833.79 |
September | 0.126142E+09 | 64823089.04 | 61318657.64 | 0.109028E+09 | 44255437.27 |
October | 76604016.35 | 29953058.60 | 46650957.75 | 45780967.39 | 67787591.33 |
November | 42225731.70 | 11969786.26 | 30255945.44 | 9660186.87 | 92111137.45 |
December | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 0.147301E+09 |
Annual Sum or Average | 0.151779E+10 | 0.816671E+09 | 0.701118E+09 | 0.123818E+10 | 0.895668E+09 |
Minimum of Months | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 27859702.93 |
Maximum of Months | 0.229345E+09 | 0.137641E+09 | 92239775.99 | 0.233587E+09 | 0.152817E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44338527.55 | 14363050.60 | 29975476.95 | 3848855.61 | 0.152817E+09 |
February | 72185296.75 | 32361260.33 | 39824036.42 | 25907365.04 | 0.109104E+09 |
March | 0.115947E+09 | 64835963.83 | 51110900.12 | 72216633.75 | 93883714.99 |
April | 0.167269E+09 | 0.105813E+09 | 61456301.45 | 0.140060E+09 | 62076625.17 |
May | 0.212253E+09 | 0.120013E+09 | 92239775.99 | 0.202339E+09 | 39934683.52 |
June | 0.216088E+09 | 0.125000E+09 | 91088427.67 | 0.216198E+09 | 27892827.10 |
July | 0.229345E+09 | 0.137641E+09 | 91704197.78 | 0.233587E+09 | 27859702.93 |
August | 0.180640E+09 | 0.101822E+09 | 78818274.75 | 0.178026E+09 | 30644833.79 |
September | 0.126142E+09 | 64823089.04 | 61318657.64 | 0.109028E+09 | 44255437.27 |
October | 76604016.35 | 29953058.60 | 46650957.75 | 45780967.39 | 67787591.33 |
November | 42225731.70 | 11969786.26 | 30255945.44 | 9660186.87 | 92111137.45 |
December | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 0.147301E+09 |
Annual Sum or Average | 0.151779E+10 | 0.816671E+09 | 0.701118E+09 | 0.123818E+10 | 0.895668E+09 |
Minimum of Months | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 27859702.93 |
Maximum of Months | 0.229345E+09 | 0.137641E+09 | 92239775.99 | 0.233587E+09 | 0.152817E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44338527.55 | 14363050.60 | 29975476.95 | 3848855.61 | 0.152817E+09 |
February | 72185296.75 | 32361260.33 | 39824036.42 | 25907365.04 | 0.109104E+09 |
March | 0.115947E+09 | 64835963.83 | 51110900.12 | 72216633.75 | 93883714.99 |
April | 0.167269E+09 | 0.105813E+09 | 61456301.45 | 0.140060E+09 | 62076625.17 |
May | 0.212253E+09 | 0.120013E+09 | 92239775.99 | 0.202339E+09 | 39934683.52 |
June | 0.216088E+09 | 0.125000E+09 | 91088427.67 | 0.216198E+09 | 27892827.10 |
July | 0.229345E+09 | 0.137641E+09 | 91704197.78 | 0.233587E+09 | 27859702.93 |
August | 0.180640E+09 | 0.101822E+09 | 78818274.75 | 0.178026E+09 | 30644833.79 |
September | 0.126142E+09 | 64823089.04 | 61318657.64 | 0.109028E+09 | 44255437.27 |
October | 76604016.35 | 29953058.60 | 46650957.75 | 45780967.39 | 67787591.33 |
November | 42225731.70 | 11969786.26 | 30255945.44 | 9660186.87 | 92111137.45 |
December | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 0.147301E+09 |
Annual Sum or Average | 0.151779E+10 | 0.816671E+09 | 0.701118E+09 | 0.123818E+10 | 0.895668E+09 |
Minimum of Months | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 27859702.93 |
Maximum of Months | 0.229345E+09 | 0.137641E+09 | 92239775.99 | 0.233587E+09 | 0.152817E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44338527.55 | 14363050.60 | 29975476.95 | 3848855.61 | 0.152817E+09 |
February | 72185296.75 | 32361260.33 | 39824036.42 | 25907365.04 | 0.109104E+09 |
March | 0.115947E+09 | 64835963.83 | 51110900.12 | 72216633.75 | 93883714.99 |
April | 0.167269E+09 | 0.105813E+09 | 61456301.45 | 0.140060E+09 | 62076625.17 |
May | 0.212253E+09 | 0.120013E+09 | 92239775.99 | 0.202339E+09 | 39934683.52 |
June | 0.216088E+09 | 0.125000E+09 | 91088427.67 | 0.216198E+09 | 27892827.10 |
July | 0.229345E+09 | 0.137641E+09 | 91704197.78 | 0.233587E+09 | 27859702.93 |
August | 0.180640E+09 | 0.101822E+09 | 78818274.75 | 0.178026E+09 | 30644833.79 |
September | 0.126142E+09 | 64823089.04 | 61318657.64 | 0.109028E+09 | 44255437.27 |
October | 76604016.35 | 29953058.60 | 46650957.75 | 45780967.39 | 67787591.33 |
November | 42225731.70 | 11969786.26 | 30255945.44 | 9660186.87 | 92111137.45 |
December | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 0.147301E+09 |
Annual Sum or Average | 0.151779E+10 | 0.816671E+09 | 0.701118E+09 | 0.123818E+10 | 0.895668E+09 |
Minimum of Months | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 27859702.93 |
Maximum of Months | 0.229345E+09 | 0.137641E+09 | 92239775.99 | 0.233587E+09 | 0.152817E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44338527.55 | 14363050.60 | 29975476.95 | 3848855.61 | 0.152817E+09 |
February | 72185296.75 | 32361260.33 | 39824036.42 | 25907365.04 | 0.109104E+09 |
March | 0.115947E+09 | 64835963.83 | 51110900.12 | 72216633.75 | 93883714.99 |
April | 0.167269E+09 | 0.105813E+09 | 61456301.45 | 0.140060E+09 | 62076625.17 |
May | 0.212253E+09 | 0.120013E+09 | 92239775.99 | 0.202339E+09 | 39934683.52 |
June | 0.216088E+09 | 0.125000E+09 | 91088427.67 | 0.216198E+09 | 27892827.10 |
July | 0.229345E+09 | 0.137641E+09 | 91704197.78 | 0.233587E+09 | 27859702.93 |
August | 0.180640E+09 | 0.101822E+09 | 78818274.75 | 0.178026E+09 | 30644833.79 |
September | 0.126142E+09 | 64823089.04 | 61318657.64 | 0.109028E+09 | 44255437.27 |
October | 76604016.35 | 29953058.60 | 46650957.75 | 45780967.39 | 67787591.33 |
November | 42225731.70 | 11969786.26 | 30255945.44 | 9660186.87 | 92111137.45 |
December | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 0.147301E+09 |
Annual Sum or Average | 0.151779E+10 | 0.816671E+09 | 0.701118E+09 | 0.123818E+10 | 0.895668E+09 |
Minimum of Months | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 27859702.93 |
Maximum of Months | 0.229345E+09 | 0.137641E+09 | 92239775.99 | 0.233587E+09 | 0.152817E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44338527.55 | 14363050.60 | 29975476.95 | 3848855.61 | 0.152817E+09 |
February | 72185296.75 | 32361260.33 | 39824036.42 | 25907365.04 | 0.109104E+09 |
March | 0.115947E+09 | 64835963.83 | 51110900.12 | 72216633.75 | 93883714.99 |
April | 0.167269E+09 | 0.105813E+09 | 61456301.45 | 0.140060E+09 | 62076625.17 |
May | 0.212253E+09 | 0.120013E+09 | 92239775.99 | 0.202339E+09 | 39934683.52 |
June | 0.216088E+09 | 0.125000E+09 | 91088427.67 | 0.216198E+09 | 27892827.10 |
July | 0.229345E+09 | 0.137641E+09 | 91704197.78 | 0.233587E+09 | 27859702.93 |
August | 0.180640E+09 | 0.101822E+09 | 78818274.75 | 0.178026E+09 | 30644833.79 |
September | 0.126142E+09 | 64823089.04 | 61318657.64 | 0.109028E+09 | 44255437.27 |
October | 76604016.35 | 29953058.60 | 46650957.75 | 45780967.39 | 67787591.33 |
November | 42225731.70 | 11969786.26 | 30255945.44 | 9660186.87 | 92111137.45 |
December | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 0.147301E+09 |
Annual Sum or Average | 0.151779E+10 | 0.816671E+09 | 0.701118E+09 | 0.123818E+10 | 0.895668E+09 |
Minimum of Months | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 27859702.93 |
Maximum of Months | 0.229345E+09 | 0.137641E+09 | 92239775.99 | 0.233587E+09 | 0.152817E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44338527.55 | 14363050.60 | 29975476.95 | 3848855.61 | 0.152817E+09 |
February | 72185296.75 | 32361260.33 | 39824036.42 | 25907365.04 | 0.109104E+09 |
March | 0.115947E+09 | 64835963.83 | 51110900.12 | 72216633.75 | 93883714.99 |
April | 0.167269E+09 | 0.105813E+09 | 61456301.45 | 0.140060E+09 | 62076625.17 |
May | 0.212253E+09 | 0.120013E+09 | 92239775.99 | 0.202339E+09 | 39934683.52 |
June | 0.216088E+09 | 0.125000E+09 | 91088427.67 | 0.216198E+09 | 27892827.10 |
July | 0.229345E+09 | 0.137641E+09 | 91704197.78 | 0.233587E+09 | 27859702.93 |
August | 0.180640E+09 | 0.101822E+09 | 78818274.75 | 0.178026E+09 | 30644833.79 |
September | 0.126142E+09 | 64823089.04 | 61318657.64 | 0.109028E+09 | 44255437.27 |
October | 76604016.35 | 29953058.60 | 46650957.75 | 45780967.39 | 67787591.33 |
November | 42225731.70 | 11969786.26 | 30255945.44 | 9660186.87 | 92111137.45 |
December | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 0.147301E+09 |
Annual Sum or Average | 0.151779E+10 | 0.816671E+09 | 0.701118E+09 | 0.123818E+10 | 0.895668E+09 |
Minimum of Months | 34752389.89 | 8077114.19 | 26675275.70 | 1529981.26 | 27859702.93 |
Maximum of Months | 0.229345E+09 | 0.137641E+09 | 92239775.99 | 0.233587E+09 | 0.152817E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355020E+10 | 0.247064E+10 | 0.107956E+10 | 0.295912E+10 | 0.360045E+10 |
February | 0.406082E+10 | 0.274399E+10 | 0.131683E+10 | 0.371336E+10 | 0.274065E+10 |
March | 0.396046E+10 | 0.250736E+10 | 0.145310E+10 | 0.343186E+10 | 0.253197E+10 |
April | 0.346774E+10 | 0.188113E+10 | 0.158661E+10 | 0.294733E+10 | 0.161942E+10 |
May | 0.300999E+10 | 0.102597E+10 | 0.198402E+10 | 0.256664E+10 | 0.962819E+09 |
June | 0.261323E+10 | 0.693230E+09 | 0.192000E+10 | 0.234540E+10 | 0.638444E+09 |
July | 0.295223E+10 | 0.931688E+09 | 0.202054E+10 | 0.278594E+10 | 0.601891E+09 |
August | 0.315494E+10 | 0.131769E+10 | 0.183725E+10 | 0.310471E+10 | 0.722135E+09 |
September | 0.327435E+10 | 0.174402E+10 | 0.153033E+10 | 0.322204E+10 | 0.113994E+10 |
October | 0.289138E+10 | 0.170158E+10 | 0.118980E+10 | 0.269347E+10 | 0.172234E+10 |
November | 0.249217E+10 | 0.156475E+10 | 0.927415E+09 | 0.219694E+10 | 0.227157E+10 |
December | 0.274102E+10 | 0.179800E+10 | 0.943020E+09 | 0.210691E+10 | 0.348645E+10 |
Annual Sum or Average | 0.381685E+11 | 0.203800E+11 | 0.177885E+11 | 0.340737E+11 | 0.220381E+11 |
Minimum of Months | 0.249217E+10 | 0.693230E+09 | 0.927415E+09 | 0.210691E+10 | 0.601891E+09 |
Maximum of Months | 0.406082E+10 | 0.274399E+10 | 0.202054E+10 | 0.371336E+10 | 0.360045E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355020E+10 | 0.247064E+10 | 0.107956E+10 | 0.294744E+10 | 0.359647E+10 |
February | 0.406082E+10 | 0.274399E+10 | 0.131683E+10 | 0.370511E+10 | 0.272595E+10 |
March | 0.396046E+10 | 0.250736E+10 | 0.145310E+10 | 0.342700E+10 | 0.250904E+10 |
April | 0.346774E+10 | 0.188113E+10 | 0.158661E+10 | 0.294833E+10 | 0.158030E+10 |
May | 0.300999E+10 | 0.102597E+10 | 0.198402E+10 | 0.256834E+10 | 0.926473E+09 |
June | 0.261323E+10 | 0.693230E+09 | 0.192000E+10 | 0.233540E+10 | 0.618402E+09 |
July | 0.295223E+10 | 0.931688E+09 | 0.202054E+10 | 0.276404E+10 | 0.600538E+09 |
August | 0.315494E+10 | 0.131769E+10 | 0.183725E+10 | 0.308459E+10 | 0.720232E+09 |
September | 0.327435E+10 | 0.174402E+10 | 0.153033E+10 | 0.321788E+10 | 0.111170E+10 |
October | 0.289138E+10 | 0.170158E+10 | 0.118980E+10 | 0.269918E+10 | 0.167400E+10 |
November | 0.249217E+10 | 0.156475E+10 | 0.927415E+09 | 0.219520E+10 | 0.224403E+10 |
December | 0.274102E+10 | 0.179800E+10 | 0.943020E+09 | 0.209795E+10 | 0.348365E+10 |
Annual Sum or Average | 0.381685E+11 | 0.203800E+11 | 0.177885E+11 | 0.339904E+11 | 0.217908E+11 |
Minimum of Months | 0.249217E+10 | 0.693230E+09 | 0.927415E+09 | 0.209795E+10 | 0.600538E+09 |
Maximum of Months | 0.406082E+10 | 0.274399E+10 | 0.202054E+10 | 0.370511E+10 | 0.359647E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.730506E+09 | 0.508370E+09 | 0.222136E+09 | 0.616487E+09 | 0.701133E+09 |
February | 0.835572E+09 | 0.564616E+09 | 0.270956E+09 | 0.773123E+09 | 0.526688E+09 |
March | 0.814923E+09 | 0.515926E+09 | 0.298997E+09 | 0.719221E+09 | 0.475033E+09 |
April | 0.713539E+09 | 0.387070E+09 | 0.326469E+09 | 0.632753E+09 | 0.291494E+09 |
May | 0.619349E+09 | 0.211108E+09 | 0.408242E+09 | 0.550937E+09 | 0.173316E+09 |
June | 0.537710E+09 | 0.142642E+09 | 0.395067E+09 | 0.483329E+09 | 0.119174E+09 |
July | 0.607463E+09 | 0.191708E+09 | 0.415755E+09 | 0.560343E+09 | 0.123131E+09 |
August | 0.649176E+09 | 0.271134E+09 | 0.378041E+09 | 0.636470E+09 | 0.142870E+09 |
September | 0.673746E+09 | 0.358857E+09 | 0.314888E+09 | 0.688658E+09 | 0.203215E+09 |
October | 0.594945E+09 | 0.350125E+09 | 0.244819E+09 | 0.579441E+09 | 0.306679E+09 |
November | 0.512799E+09 | 0.321970E+09 | 0.190829E+09 | 0.463159E+09 | 0.419208E+09 |
December | 0.564004E+09 | 0.369964E+09 | 0.194040E+09 | 0.440287E+09 | 0.674313E+09 |
Annual Sum or Average | 0.785373E+10 | 0.419349E+10 | 0.366024E+10 | 0.714421E+10 | 0.415625E+10 |
Minimum of Months | 0.512799E+09 | 0.142642E+09 | 0.190829E+09 | 0.440287E+09 | 0.119174E+09 |
Maximum of Months | 0.835572E+09 | 0.564616E+09 | 0.415755E+09 | 0.773123E+09 | 0.701133E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.50 | 456.44 | 132.43 | 42.90 | 89.53 | 0.00 | 0.00 |
February | 85.67 | 360.79 | 238.71 | 107.01 | 131.69 | 0.00 | 0.00 |
March | 215.70 | 280.42 | 346.32 | 193.66 | 152.66 | 0.00 | 0.00 |
April | 432.28 | 191.59 | 516.26 | 326.58 | 189.68 | 0.00 | 0.00 |
May | 604.36 | 119.28 | 633.97 | 358.46 | 275.51 | 0.00 | 0.00 |
June | 667.28 | 86.09 | 666.94 | 385.80 | 281.14 | 0.00 | 0.00 |
July | 697.69 | 83.21 | 685.02 | 411.11 | 273.91 | 0.00 | 0.00 |
August | 531.74 | 91.53 | 539.55 | 304.13 | 235.42 | 0.00 | 0.00 |
September | 336.50 | 136.59 | 389.33 | 200.07 | 189.26 | 0.00 | 0.00 |
October | 136.74 | 202.47 | 228.81 | 89.47 | 139.34 | 0.00 | 0.00 |
November | 29.82 | 284.29 | 130.33 | 36.94 | 93.38 | 0.00 | 0.00 |
December | 4.57 | 439.97 | 103.80 | 24.13 | 79.68 | 0.00 | 0.00 |
Annual Sum or Average | 314.10 | 227.21 | 385.03 | 207.17 | 177.86 | 0.00 | 0.00 |
Minimum of Months | 4.57 | 83.21 | 103.80 | 24.13 | 79.68 | 0.00 | 0.00 |
Maximum of Months | 697.69 | 456.44 | 685.02 | 411.11 | 281.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1104.81 | 1344.25 | 1325.49 | 922.43 | 403.06 | 0.00 | 0.00 |
February | 1534.96 | 1132.88 | 1678.58 | 1134.26 | 544.32 | 0.00 | 0.00 |
March | 1281.31 | 945.33 | 1478.67 | 936.14 | 542.53 | 0.00 | 0.00 |
April | 1137.09 | 624.78 | 1337.86 | 725.74 | 612.12 | 0.00 | 0.00 |
May | 958.27 | 359.48 | 1123.80 | 383.05 | 740.75 | 0.00 | 0.00 |
June | 904.86 | 246.31 | 1008.19 | 267.45 | 740.74 | 0.00 | 0.00 |
July | 1040.15 | 224.72 | 1102.23 | 347.85 | 754.38 | 0.00 | 0.00 |
August | 1159.17 | 269.61 | 1177.92 | 491.97 | 685.95 | 0.00 | 0.00 |
September | 1243.07 | 439.79 | 1263.25 | 672.85 | 590.41 | 0.00 | 0.00 |
October | 1005.63 | 643.05 | 1079.52 | 635.30 | 444.22 | 0.00 | 0.00 |
November | 847.59 | 876.38 | 961.48 | 603.68 | 357.80 | 0.00 | 0.00 |
December | 786.63 | 1301.69 | 1023.38 | 671.30 | 352.08 | 0.00 | 0.00 |
Annual Sum or Average | 1080.47 | 698.82 | 1210.32 | 646.25 | 564.07 | 0.00 | 0.00 |
Minimum of Months | 786.63 | 224.72 | 961.48 | 267.45 | 352.08 | 0.00 | 0.00 |
Maximum of Months | 1534.96 | 1344.25 | 1678.58 | 1134.26 | 754.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1100.45 | 1342.77 | 1325.49 | 922.43 | 403.06 | 0.00 | 0.00 |
February | 1531.54 | 1126.80 | 1678.58 | 1134.26 | 544.32 | 0.00 | 0.00 |
March | 1279.49 | 936.77 | 1478.67 | 936.14 | 542.53 | 0.00 | 0.00 |
April | 1137.47 | 609.68 | 1337.86 | 725.74 | 612.12 | 0.00 | 0.00 |
May | 958.91 | 345.91 | 1123.80 | 383.05 | 740.75 | 0.00 | 0.00 |
June | 901.00 | 238.58 | 1008.19 | 267.45 | 740.74 | 0.00 | 0.00 |
July | 1031.97 | 224.22 | 1102.23 | 347.85 | 754.38 | 0.00 | 0.00 |
August | 1151.65 | 268.90 | 1177.92 | 491.97 | 685.95 | 0.00 | 0.00 |
September | 1241.46 | 428.90 | 1263.25 | 672.85 | 590.41 | 0.00 | 0.00 |
October | 1007.76 | 625.00 | 1079.52 | 635.30 | 444.22 | 0.00 | 0.00 |
November | 846.91 | 865.75 | 961.48 | 603.68 | 357.80 | 0.00 | 0.00 |
December | 783.28 | 1300.65 | 1023.38 | 671.30 | 352.08 | 0.00 | 0.00 |
Annual Sum or Average | 1077.83 | 690.98 | 1210.32 | 646.25 | 564.07 | 0.00 | 0.00 |
Minimum of Months | 783.28 | 224.22 | 961.48 | 267.45 | 352.08 | 0.00 | 0.00 |
Maximum of Months | 1531.54 | 1342.77 | 1678.58 | 1134.26 | 754.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 230.17 | 261.77 | 272.74 | 189.80 | 82.94 | 0.00 | 0.00 |
February | 319.58 | 217.71 | 345.39 | 233.39 | 112.00 | 0.00 | 0.00 |
March | 268.53 | 177.36 | 304.26 | 192.62 | 111.63 | 0.00 | 0.00 |
April | 244.12 | 112.46 | 275.28 | 149.33 | 125.95 | 0.00 | 0.00 |
May | 205.70 | 64.71 | 231.24 | 78.82 | 152.42 | 0.00 | 0.00 |
June | 186.47 | 45.98 | 207.45 | 55.03 | 152.42 | 0.00 | 0.00 |
July | 209.21 | 45.97 | 226.80 | 71.58 | 155.23 | 0.00 | 0.00 |
August | 237.63 | 53.34 | 242.37 | 101.23 | 141.14 | 0.00 | 0.00 |
September | 265.69 | 78.40 | 259.93 | 138.45 | 121.48 | 0.00 | 0.00 |
October | 216.34 | 114.50 | 222.13 | 130.72 | 91.41 | 0.00 | 0.00 |
November | 178.69 | 161.73 | 197.84 | 124.22 | 73.62 | 0.00 | 0.00 |
December | 164.38 | 251.76 | 210.58 | 138.13 | 72.45 | 0.00 | 0.00 |
Annual Sum or Average | 226.54 | 131.79 | 249.04 | 132.97 | 116.07 | 0.00 | 0.00 |
Minimum of Months | 164.38 | 45.97 | 197.84 | 55.03 | 72.45 | 0.00 | 0.00 |
Maximum of Months | 319.58 | 261.77 | 345.39 | 233.39 | 155.23 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 30790844.86 | 0.122253E+10 | 0.354708E+09 | 0.114904E+09 | 0.239804E+09 | 0.00 | 0.00 |
February | 0.207259E+09 | 0.872834E+09 | 0.577482E+09 | 0.258890E+09 | 0.318592E+09 | 0.00 | 0.00 |
March | 0.577733E+09 | 0.751070E+09 | 0.927575E+09 | 0.518688E+09 | 0.408887E+09 | 0.00 | 0.00 |
April | 0.112048E+10 | 0.496613E+09 | 0.133815E+10 | 0.846504E+09 | 0.491650E+09 | 0.00 | 0.00 |
May | 0.161871E+10 | 0.319477E+09 | 0.169802E+10 | 0.960102E+09 | 0.737918E+09 | 0.00 | 0.00 |
June | 0.172958E+10 | 0.223143E+09 | 0.172871E+10 | 0.999998E+09 | 0.728707E+09 | 0.00 | 0.00 |
July | 0.186869E+10 | 0.222878E+09 | 0.183476E+10 | 0.110113E+10 | 0.733634E+09 | 0.00 | 0.00 |
August | 0.142421E+10 | 0.245159E+09 | 0.144512E+10 | 0.814573E+09 | 0.630546E+09 | 0.00 | 0.00 |
September | 0.872220E+09 | 0.354043E+09 | 0.100913E+10 | 0.518585E+09 | 0.490549E+09 | 0.00 | 0.00 |
October | 0.366248E+09 | 0.542301E+09 | 0.612832E+09 | 0.239624E+09 | 0.373208E+09 | 0.00 | 0.00 |
November | 77281494.98 | 0.736889E+09 | 0.337806E+09 | 95758290.08 | 0.242048E+09 | 0.00 | 0.00 |
December | 12239850.04 | 0.117840E+10 | 0.278019E+09 | 64616913.49 | 0.213402E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.990545E+10 | 0.716535E+10 | 0.121423E+11 | 0.653337E+10 | 0.560895E+10 | 0.00 | 0.00 |
Minimum of Months | 12239850.04 | 0.222878E+09 | 0.278019E+09 | 64616913.49 | 0.213402E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186869E+10 | 0.122253E+10 | 0.183476E+10 | 0.110113E+10 | 0.737918E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.295912E+10 | 0.360045E+10 | 0.355020E+10 | 0.247064E+10 | 0.107956E+10 | 0.00 | 0.00 |
February | 0.371336E+10 | 0.274065E+10 | 0.406082E+10 | 0.274399E+10 | 0.131683E+10 | 0.00 | 0.00 |
March | 0.343186E+10 | 0.253197E+10 | 0.396046E+10 | 0.250736E+10 | 0.145310E+10 | 0.00 | 0.00 |
April | 0.294733E+10 | 0.161942E+10 | 0.346774E+10 | 0.188113E+10 | 0.158661E+10 | 0.00 | 0.00 |
May | 0.256664E+10 | 0.962819E+09 | 0.300999E+10 | 0.102597E+10 | 0.198402E+10 | 0.00 | 0.00 |
June | 0.234540E+10 | 0.638444E+09 | 0.261323E+10 | 0.693230E+09 | 0.192000E+10 | 0.00 | 0.00 |
July | 0.278594E+10 | 0.601891E+09 | 0.295223E+10 | 0.931688E+09 | 0.202054E+10 | 0.00 | 0.00 |
August | 0.310471E+10 | 0.722135E+09 | 0.315494E+10 | 0.131769E+10 | 0.183725E+10 | 0.00 | 0.00 |
September | 0.322204E+10 | 0.113994E+10 | 0.327435E+10 | 0.174402E+10 | 0.153033E+10 | 0.00 | 0.00 |
October | 0.269347E+10 | 0.172234E+10 | 0.289138E+10 | 0.170158E+10 | 0.118980E+10 | 0.00 | 0.00 |
November | 0.219694E+10 | 0.227157E+10 | 0.249217E+10 | 0.156475E+10 | 0.927415E+09 | 0.00 | 0.00 |
December | 0.210691E+10 | 0.348645E+10 | 0.274102E+10 | 0.179800E+10 | 0.943020E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.340737E+11 | 0.220381E+11 | 0.381685E+11 | 0.203800E+11 | 0.177885E+11 | 0.00 | 0.00 |
Minimum of Months | 0.210691E+10 | 0.601891E+09 | 0.249217E+10 | 0.693230E+09 | 0.927415E+09 | 0.00 | 0.00 |
Maximum of Months | 0.371336E+10 | 0.360045E+10 | 0.406082E+10 | 0.274399E+10 | 0.202054E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.294744E+10 | 0.359647E+10 | 0.355020E+10 | 0.247064E+10 | 0.107956E+10 | 0.00 | 0.00 |
February | 0.370511E+10 | 0.272595E+10 | 0.406082E+10 | 0.274399E+10 | 0.131683E+10 | 0.00 | 0.00 |
March | 0.342700E+10 | 0.250904E+10 | 0.396046E+10 | 0.250736E+10 | 0.145310E+10 | 0.00 | 0.00 |
April | 0.294833E+10 | 0.158030E+10 | 0.346774E+10 | 0.188113E+10 | 0.158661E+10 | 0.00 | 0.00 |
May | 0.256834E+10 | 0.926473E+09 | 0.300999E+10 | 0.102597E+10 | 0.198402E+10 | 0.00 | 0.00 |
June | 0.233540E+10 | 0.618402E+09 | 0.261323E+10 | 0.693230E+09 | 0.192000E+10 | 0.00 | 0.00 |
July | 0.276404E+10 | 0.600538E+09 | 0.295223E+10 | 0.931688E+09 | 0.202054E+10 | 0.00 | 0.00 |
August | 0.308459E+10 | 0.720232E+09 | 0.315494E+10 | 0.131769E+10 | 0.183725E+10 | 0.00 | 0.00 |
September | 0.321788E+10 | 0.111170E+10 | 0.327435E+10 | 0.174402E+10 | 0.153033E+10 | 0.00 | 0.00 |
October | 0.269918E+10 | 0.167400E+10 | 0.289138E+10 | 0.170158E+10 | 0.118980E+10 | 0.00 | 0.00 |
November | 0.219520E+10 | 0.224403E+10 | 0.249217E+10 | 0.156475E+10 | 0.927415E+09 | 0.00 | 0.00 |
December | 0.209795E+10 | 0.348365E+10 | 0.274102E+10 | 0.179800E+10 | 0.943020E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.339904E+11 | 0.217908E+11 | 0.381685E+11 | 0.203800E+11 | 0.177885E+11 | 0.00 | 0.00 |
Minimum of Months | 0.209795E+10 | 0.600538E+09 | 0.249217E+10 | 0.693230E+09 | 0.927415E+09 | 0.00 | 0.00 |
Maximum of Months | 0.370511E+10 | 0.359647E+10 | 0.406082E+10 | 0.274399E+10 | 0.202054E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.616487E+09 | 0.701133E+09 | 0.730506E+09 | 0.508370E+09 | 0.222136E+09 | 0.00 | 0.00 |
February | 0.773123E+09 | 0.526688E+09 | 0.835572E+09 | 0.564616E+09 | 0.270956E+09 | 0.00 | 0.00 |
March | 0.719221E+09 | 0.475033E+09 | 0.814923E+09 | 0.515926E+09 | 0.298997E+09 | 0.00 | 0.00 |
April | 0.632753E+09 | 0.291494E+09 | 0.713539E+09 | 0.387070E+09 | 0.326469E+09 | 0.00 | 0.00 |
May | 0.550937E+09 | 0.173316E+09 | 0.619349E+09 | 0.211108E+09 | 0.408242E+09 | 0.00 | 0.00 |
June | 0.483329E+09 | 0.119174E+09 | 0.537710E+09 | 0.142642E+09 | 0.395067E+09 | 0.00 | 0.00 |
July | 0.560343E+09 | 0.123131E+09 | 0.607463E+09 | 0.191708E+09 | 0.415755E+09 | 0.00 | 0.00 |
August | 0.636470E+09 | 0.142870E+09 | 0.649176E+09 | 0.271134E+09 | 0.378041E+09 | 0.00 | 0.00 |
September | 0.688658E+09 | 0.203215E+09 | 0.673746E+09 | 0.358857E+09 | 0.314888E+09 | 0.00 | 0.00 |
October | 0.579441E+09 | 0.306679E+09 | 0.594945E+09 | 0.350125E+09 | 0.244819E+09 | 0.00 | 0.00 |
November | 0.463159E+09 | 0.419208E+09 | 0.512799E+09 | 0.321970E+09 | 0.190829E+09 | 0.00 | 0.00 |
December | 0.440287E+09 | 0.674313E+09 | 0.564004E+09 | 0.369964E+09 | 0.194040E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.714421E+10 | 0.415625E+10 | 0.785373E+10 | 0.419349E+10 | 0.366024E+10 | 0.00 | 0.00 |
Minimum of Months | 0.440287E+09 | 0.119174E+09 | 0.512799E+09 | 0.142642E+09 | 0.190829E+09 | 0.00 | 0.00 |
Maximum of Months | 0.773123E+09 | 0.701133E+09 | 0.835572E+09 | 0.564616E+09 | 0.415755E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.3 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.6 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.5 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.48 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.18 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.96 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.19 | 13.59 | 3.45 | 8.98 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.33 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.48 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.07 | -2.0 | 3.82 | -8.5 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.3 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.98 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -0.9 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.85 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.46 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.93 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.24 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.70 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.34 | 23.33 | 8.07 | 19.92 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.35 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.80 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.60 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.43 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -0.9 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.34 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.3 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.0 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.61 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.6 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.4 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.33 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.46 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.93 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.90 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.70 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.75 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.35 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.70 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.4 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.75 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.24 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.06 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.90 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.75 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.35 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.22 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.16 | 3.43 | 9.18 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 06-DEC-02:00 | 0.00 | -0.0 | 3.60 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.75 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.314217E+10 | -.270574E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -436426971.0 | 59.00 | 0.00 | 0.00 |
February | 0.291327E+10 | -.252022E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -393056142.7 | 59.00 | 0.00 | 0.00 |
March | 0.327997E+10 | -.284829E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -431677952.4 | 58.99 | 0.00 | 0.00 |
April | 0.303574E+10 | -.262634E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -409397314.7 | 59.00 | 0.00 | 0.00 |
May | 0.298172E+10 | -.258139E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -400330826.6 | 59.00 | 0.00 | 0.00 |
June | 0.275981E+10 | -.238190E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -377909267.6 | 59.00 | 0.00 | 0.00 |
July | 0.264989E+10 | -.226381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -386075872.4 | 58.99 | 0.00 | 0.00 |
August | 0.265512E+10 | -.226847E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -386649136.6 | 59.00 | 0.00 | 0.00 |
September | 0.255054E+10 | -.216893E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -381606103.2 | 58.99 | 0.00 | 0.00 |
October | 0.270822E+10 | -.229380E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -414415735.2 | 58.99 | 0.00 | 0.00 |
November | 0.275493E+10 | -.234052E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -414402227.6 | 58.99 | 0.00 | 0.00 |
December | 0.301711E+10 | -.258157E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -435541858.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.344485E+11 | -.295810E+11 | 8760.00 | -.486749E+10 | 58.99 | |||||
Minimum of Months | 0.255054E+10 | -.284829E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -436426971.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.327997E+10 | -.216893E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -377909267.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.96 | 0.90 | 30-JAN-12:30 | 114.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.95 | 0.87 | 26-FEB-12:30 | 143.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.95 | 0.83 | 05-MAR-11:30 | 154.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.94 | 0.83 | 01-APR-11:30 | 183.97 | 0.00 | 0.00 | 4.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.91 | 0.83 | 01-MAY-08:09 | 1150.42 | 0.00 | 0.00 | 83.33 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.91 | 0.83 | 01-JUN-10:50 | 339.85 | 0.00 | 0.00 | 53.17 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.90 | 0.83 | 01-JUL-08:09 | 1229.72 | 0.00 | 0.00 | 95.33 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.91 | 0.83 | 01-AUG-08:50 | 262.53 | 0.00 | 0.00 | 11.33 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.94 | 0.83 | 02-SEP-11:30 | 198.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.95 | 0.87 | 07-OCT-11:30 | 160.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.96 | 0.91 | 02-NOV-12:30 | 119.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.96 | 0.92 | 04-DEC-12:20 | 111.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.93 | 414.05 | 0.00 | 0.00 | 247.17 | ||||||
Minimum of Months | 226.33 | 0.90 | 0.83 | 111.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 437.50 | 0.96 | 0.92 | 1229.72 | 0.00 | 0.00 | 95.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.308154E+11 | 47583.22 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224436E+11 | 47583.22 | 01-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188477E+11 | 47583.22 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.692927E+10 | 47583.22 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.493061E+09 | 47583.22 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8700491.20 | 2668.87 | 23-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.258201E+10 | 47583.22 | 06-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118845E+11 | 47583.22 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.276083E+11 | 47583.22 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121613E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.308154E+11 | 47583.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.569059E+11 | 261615.20 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.282012E+11 | 261615.20 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141981E+11 | 261615.20 | 05-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154898E+10 | 179660.85 | 05-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45247993.80 | 12663.11 | 01-MAY-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120914E+09 | 17846.59 | 30-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.766236E+10 | 261615.20 | 25-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.454378E+11 | 261615.20 | 02-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154121E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.569059E+11 | 261615.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133302E+11 | 33325.75 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.840505E+10 | 33325.75 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.670268E+10 | 33325.75 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.207039E+10 | 33325.75 | 02-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117127E+09 | 33325.75 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3460744.51 | 1730.02 | 23-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.773624E+09 | 33325.75 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.443168E+10 | 33325.75 | 03-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124774E+11 | 33325.75 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.483117E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133302E+11 | 33325.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159866E+11 | 28269.85 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105756E+11 | 28269.85 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.897508E+10 | 28269.85 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.333851E+10 | 28269.85 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.291938E+09 | 28269.85 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 197400.77 | 317.86 | 03-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 50660834.49 | 2477.58 | 23-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172370E+10 | 28269.85 | 06-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.636258E+10 | 28269.85 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151182E+11 | 28269.85 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.624231E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159866E+11 | 28269.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.243720E+11 | 55756.91 | 05-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152303E+11 | 47508.98 | 01-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123126E+11 | 35379.92 | 15-MAR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.367909E+10 | 21252.56 | 04-APR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102597E+09 | 7190.40 | 01-MAY-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.313860E+10 | 21699.60 | 23-OCT-16:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.938644E+10 | 36143.92 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229743E+11 | 53056.18 | 24-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.911959E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.243720E+11 | 55756.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1325910.73 | 1108257.96 | 837.41 | 23-APR-16:00 | 698.51 | 0.00 |
May | 0.00 | 0.00 | 0.193340E+10 | 0.155898E+10 | 11742.23 | 25-MAY-15:00 | 8838.67 | 0.00 |
June | 0.00 | 0.00 | 0.607727E+10 | 0.431621E+10 | 32210.61 | 27-JUN-20:53 | 17447.04 | 0.00 |
July | 0.00 | 0.00 | 0.101571E+11 | 0.678477E+10 | 33366.58 | 03-JUL-23:03 | 14274.78 | 0.00 |
August | 0.00 | 0.00 | 0.696046E+10 | 0.465526E+10 | 32453.14 | 31-AUG-20:55 | 16152.39 | 0.00 |
September | 0.00 | 0.00 | 0.815616E+09 | 0.622384E+09 | 29897.52 | 01-SEP-20:40 | 16001.24 | 0.00 |
October | 0.00 | 0.00 | 7635045.11 | 7110356.15 | 1187.29 | 19-OCT-15:00 | 1090.65 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.259528E+11 | 0.179458E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101571E+11 | 0.678477E+10 | 33366.58 | 17447.04 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 3041743.78 | 2968333.37 | 1393.26 | 31-MAR-14:50 | 1369.82 | 0.00 |
April | 0.00 | 0.00 | 0.282742E+10 | 0.268124E+10 | 24673.58 | 23-APR-16:00 | 20211.18 | 0.00 |
May | 0.00 | 0.00 | 0.190123E+11 | 0.157315E+11 | 147235.27 | 26-MAY-06:02 | 100026.17 | 0.00 |
June | 0.00 | 0.00 | 0.357297E+11 | 0.258387E+11 | 158706.71 | 25-JUN-08:62 | 88882.58 | 0.00 |
July | 0.00 | 0.00 | 0.508127E+11 | 0.343644E+11 | 161499.41 | 30-JUL-08:62 | 82811.48 | 0.00 |
August | 0.00 | 0.00 | 0.397780E+11 | 0.266098E+11 | 153691.53 | 30-AUG-06:02 | 74313.56 | 0.00 |
September | 0.00 | 0.00 | 0.140757E+11 | 0.111044E+11 | 149312.99 | 01-SEP-06:02 | 75325.64 | 0.00 |
October | 0.00 | 0.00 | 0.510415E+10 | 0.435285E+10 | 21246.93 | 02-OCT-15:00 | 15973.88 | 0.00 |
November | 0.00 | 0.00 | 0.188901E+09 | 0.142386E+09 | 12299.47 | 01-NOV-14:00 | 9192.24 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.167532E+12 | 0.120828E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.508127E+11 | 0.343644E+11 | 161499.41 | 100026.17 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 648.10 | 648.10 | 0.25 | 31-MAR-14:10 | 0.25 | 0.00 |
April | 0.00 | 0.00 | 0.252793E+09 | 0.236048E+09 | 18763.68 | 23-APR-19:10 | 16946.52 | 0.00 |
May | 0.00 | 0.00 | 0.277770E+10 | 0.238621E+10 | 19428.89 | 25-MAY-20:32 | 15272.27 | 0.00 |
June | 0.00 | 0.00 | 0.636943E+10 | 0.472331E+10 | 20800.30 | 19-JUN-20:20 | 9287.68 | 0.00 |
July | 0.00 | 0.00 | 0.995361E+10 | 0.687091E+10 | 21344.57 | 03-JUL-23:40 | 9284.03 | 0.00 |
August | 0.00 | 0.00 | 0.825017E+10 | 0.571693E+10 | 20790.77 | 31-AUG-20:17 | 10696.50 | 0.00 |
September | 0.00 | 0.00 | 0.241715E+10 | 0.199367E+10 | 20259.00 | 01-SEP-01:10 | 9284.63 | 0.00 |
October | 0.00 | 0.00 | 0.567450E+09 | 0.517864E+09 | 18055.17 | 22-OCT-19:04 | 13673.45 | 0.00 |
November | 0.00 | 0.00 | 2635.02 | 2497.38 | 0.41 | 17-NOV-13:00 | 0.41 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.305883E+11 | 0.224450E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.995361E+10 | 0.687091E+10 | 21344.57 | 16946.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.290080E+09 | 0.281314E+09 | 4255.76 | 23-APR-14:20 | 3802.50 | 0.00 |
May | 0.00 | 0.00 | 0.218459E+10 | 0.191825E+10 | 15463.37 | 18-MAY-20:17 | 14078.56 | 0.00 |
June | 0.00 | 0.00 | 0.487208E+10 | 0.373491E+10 | 16045.03 | 28-JUN-20:52 | 11897.84 | 0.00 |
July | 0.00 | 0.00 | 0.772193E+10 | 0.571162E+10 | 16294.14 | 30-JUL-20:31 | 11377.48 | 0.00 |
August | 0.00 | 0.00 | 0.680708E+10 | 0.517349E+10 | 16129.20 | 08-AUG-20:42 | 11692.36 | 0.00 |
September | 0.00 | 0.00 | 0.272412E+10 | 0.241362E+10 | 15717.59 | 03-SEP-18:18 | 13300.72 | 0.00 |
October | 0.00 | 0.00 | 0.725273E+09 | 0.693651E+09 | 6957.25 | 19-OCT-20:33 | 6807.44 | 0.00 |
November | 0.00 | 0.00 | 495950.42 | 495950.42 | 209.27 | 17-NOV-13:40 | 209.27 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.253257E+11 | 0.199274E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.772193E+10 | 0.571162E+10 | 16294.14 | 14078.56 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.509592E+10 | 0.60 | 2940.13 | 01-JAN-00:03 | 0.92 |
February | 0.421351E+10 | 0.55 | 2940.13 | 01-FEB-00:07 | 0.92 |
March | 0.420143E+10 | 0.49 | 2940.13 | 01-MAR-08:70 | 0.92 |
April | 0.211272E+10 | 0.25 | 2940.13 | 01-APR-07:10 | 0.92 |
May | 0.173938E+09 | 0.02 | 2940.13 | 01-MAY-07:10 | 0.92 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 62683493.07 | 0.01 | 2940.13 | 06-SEP-07:06 | 0.91 |
October | 0.210931E+10 | 0.25 | 2940.13 | 01-OCT-07:05 | 0.91 |
November | 0.353461E+10 | 0.43 | 2940.13 | 02-NOV-07:10 | 0.91 |
December | 0.498888E+10 | 0.58 | 2940.13 | 01-DEC-01:47 | 0.92 |
Annual Sum or Average | 0.264930E+11 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.509592E+10 | 0.60 | 2940.13 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.178176E+10 | 0.52 | 1679.98 | 01-JAN-07:01 | 0.92 |
February | 0.148993E+10 | 0.48 | 1679.98 | 01-FEB-05:11 | 0.92 |
March | 0.152433E+10 | 0.44 | 1679.98 | 01-MAR-05:01 | 0.92 |
April | 0.121317E+10 | 0.38 | 1679.98 | 01-APR-04:01 | 0.92 |
May | 0.109820E+10 | 0.34 | 1679.98 | 01-MAY-04:01 | 0.92 |
June | 0.107698E+10 | 0.34 | 1679.98 | 29-JUN-01:37 | 0.90 |
July | 0.110468E+10 | 0.34 | 1679.98 | 02-JUL-19:02 | 0.91 |
August | 0.110795E+10 | 0.34 | 1679.98 | 08-AUG-20:33 | 0.90 |
September | 0.105331E+10 | 0.33 | 1269.07 | 01-SEP-00:42 | 0.79 |
October | 0.113561E+10 | 0.35 | 1679.98 | 06-OCT-04:02 | 0.92 |
November | 0.130856E+10 | 0.40 | 1679.98 | 01-NOV-04:01 | 0.92 |
December | 0.170769E+10 | 0.50 | 1679.98 | 01-DEC-05:01 | 0.92 |
Annual Sum or Average | 0.156022E+11 | 0.40 | |||
Minimum of Months | 0.105331E+10 | 0.33 | 1269.07 | 0.79 | |
Maximum of Months | 0.178176E+10 | 0.52 | 1679.98 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.879805E+10 | 0.59 | 11397.85 | 01-JAN-07:01 | 1.45 |
February | 0.736886E+10 | 0.56 | 11397.85 | 01-FEB-06:01 | 1.45 |
March | 0.780619E+10 | 0.55 | 11397.85 | 05-MAR-08:61 | 1.45 |
April | 0.718010E+10 | 0.53 | 9255.54 | 05-APR-06:03 | 1.31 |
May | 0.737710E+10 | 0.53 | 11397.85 | 18-MAY-06:03 | 1.43 |
June | 0.720866E+10 | 0.53 | 11397.85 | 07-JUN-06:03 | 1.43 |
July | 0.735843E+10 | 0.52 | 11397.85 | 01-JUL-06:02 | 1.43 |
August | 0.746621E+10 | 0.53 | 11397.85 | 01-AUG-06:02 | 1.42 |
September | 0.714524E+10 | 0.52 | 11397.85 | 01-SEP-06:02 | 1.42 |
October | 0.730690E+10 | 0.52 | 5025.66 | 30-OCT-06:20 | 0.93 |
November | 0.724143E+10 | 0.53 | 11397.85 | 25-NOV-06:02 | 1.44 |
December | 0.851145E+10 | 0.58 | 11397.85 | 02-DEC-06:02 | 1.45 |
Annual Sum or Average | 0.907686E+11 | 0.54 | |||
Minimum of Months | 0.714524E+10 | 0.52 | 5025.66 | 0.93 | |
Maximum of Months | 0.879805E+10 | 0.59 | 11397.85 | 1.45 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.101706E+10 | 0.48 | 1134.27 | 01-JAN-07:01 | 0.95 |
February | 0.843147E+09 | 0.44 | 1134.27 | 01-FEB-05:01 | 0.95 |
March | 0.886004E+09 | 0.42 | 1134.27 | 01-MAR-05:01 | 0.95 |
April | 0.756605E+09 | 0.37 | 1134.27 | 02-APR-06:01 | 0.95 |
May | 0.748214E+09 | 0.36 | 1134.27 | 01-MAY-04:01 | 0.95 |
June | 0.766268E+09 | 0.37 | 1134.27 | 04-JUN-18:31 | 0.95 |
July | 0.833146E+09 | 0.40 | 1134.27 | 22-JUL-04:52 | 0.93 |
August | 0.841653E+09 | 0.41 | 1134.27 | 08-AUG-20:42 | 0.93 |
September | 0.740017E+09 | 0.37 | 732.55 | 07-SEP-20:11 | 0.76 |
October | 0.746079E+09 | 0.36 | 1134.27 | 30-OCT-04:01 | 0.95 |
November | 0.797436E+09 | 0.39 | 1134.27 | 03-NOV-04:01 | 0.95 |
December | 0.999680E+09 | 0.47 | 1134.27 | 01-DEC-05:01 | 0.95 |
Annual Sum or Average | 0.997531E+10 | 0.40 | |||
Minimum of Months | 0.740017E+09 | 0.36 | 732.55 | 0.76 | |
Maximum of Months | 0.101706E+10 | 0.48 | 1134.27 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143029E+10 | 0.66 | 862.07 | 01-JAN-08:06 | 0.95 |
February | 0.128629E+10 | 0.63 | 862.07 | 02-FEB-15:10 | 0.95 |
March | 0.143159E+10 | 0.62 | 862.07 | 19-MAR-13:00 | 0.95 |
April | 0.136083E+10 | 0.59 | 862.07 | 01-APR-07:30 | 0.95 |
May | 0.139896E+10 | 0.58 | 862.07 | 01-MAY-05:30 | 0.95 |
June | 0.138054E+10 | 0.60 | 862.07 | 01-JUN-09:20 | 0.94 |
July | 0.143724E+10 | 0.63 | 862.07 | 01-JUL-05:02 | 0.94 |
August | 0.145682E+10 | 0.64 | 862.07 | 01-AUG-07:09 | 0.94 |
September | 0.136292E+10 | 0.59 | 862.07 | 01-SEP-07:50 | 0.94 |
October | 0.138631E+10 | 0.58 | 862.07 | 04-OCT-19:55 | 0.94 |
November | 0.134909E+10 | 0.59 | 862.07 | 20-NOV-19:00 | 0.94 |
December | 0.142897E+10 | 0.65 | 862.07 | 01-DEC-06:42 | 0.95 |
Annual Sum or Average | 0.167098E+11 | 0.61 | |||
Minimum of Months | 0.128629E+10 | 0.58 | 862.07 | 0.94 | |
Maximum of Months | 0.145682E+10 | 0.66 | 862.07 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.32 | 0.00 |
February | 2.78 | 0.00 |
March | 2.28 | 0.00 |
April | 0.53 | 0.00 |
May | 0.22 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.06 | 0.00 |
September | 0.00 | 0.00 |
October | 0.10 | 2.63 |
November | 1.10 | 0.00 |
December | 3.30 | 0.00 |
Annual Sum or Average | 13.68 | 0.02 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.32 | 2.63 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.00 |
February | 0.03 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.25 | 25.84 |
December | 0.03 | 0.00 |
Annual Sum or Average | 0.39 | 16.38 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.25 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.87 | 0.00 |
February | 1.64 | 0.00 |
March | 1.06 | 0.00 |
April | 0.08 | 2.44 |
May | 2.42 | 0.22 |
June | 3.94 | 0.10 |
July | 10.10 | 0.00 |
August | 9.80 | 0.00 |
September | 2.36 | 0.46 |
October | 0.60 | 2.44 |
November | 0.44 | 0.00 |
December | 2.68 | 0.00 |
Annual Sum or Average | 37.98 | 0.10 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 10.10 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.28 | 0.00 |
February | 2.49 | 0.00 |
March | 1.99 | 0.00 |
April | 0.31 | 0.00 |
May | 0.14 | 0.00 |
June | 0.17 | 2.44 |
July | 0.17 | 2.44 |
August | 0.08 | 2.44 |
September | 0.78 | 2.44 |
October | 1.10 | 1.45 |
November | 0.96 | 0.00 |
December | 3.45 | 0.00 |
Annual Sum or Average | 14.92 | 0.30 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 3.45 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 74.26 | 0.00 |
February | 33.57 | 0.00 |
March | 20.81 | 0.00 |
April | 16.87 | 0.00 |
May | 10.13 | 0.00 |
June | 2.67 | 0.00 |
July | 3.53 | 0.00 |
August | 3.35 | 0.00 |
September | 13.39 | 0.00 |
October | 26.43 | 0.00 |
November | 13.10 | 0.00 |
December | 59.88 | 0.00 |
Annual Sum or Average | 277.98 | 0.00 |
Minimum of Months | 2.67 | 0.00 |
Maximum of Months | 74.26 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.178176E+10 | 0.380437E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.148993E+10 | 0.277081E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.152433E+10 | 0.232688E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.121358E+10 | 0.855465E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.160640E+10 | 0.608717E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.259699E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.357190E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.280577E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.126108E+10 | 10741347.16 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.113777E+10 | 0.318767E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.130856E+10 | 0.146722E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.170769E+10 | 0.340843E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.220057E+11 | 0.150139E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.113777E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.357190E+10 | 0.380437E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.879805E+10 | 0.711324E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.736886E+10 | 0.352514E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.780715E+10 | 0.177476E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.804027E+10 | 0.193623E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.129146E+11 | 56559992.26 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.172797E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.213701E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.184251E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.112461E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.884338E+10 | 0.151142E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.729922E+10 | 0.957795E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.851145E+10 | 0.567972E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.137904E+12 | 0.192651E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.729922E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.213701E+11 | 0.711324E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.101706E+10 | 0.164571E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.843147E+09 | 0.103766E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.886004E+09 | 0.827492E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.821908E+09 | 0.255604E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.142958E+10 | 0.144601E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.229746E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.315097E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.273880E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.131678E+10 | 4272524.08 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.881794E+09 | 0.955091E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.797437E+09 | 0.547121E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.999680E+09 | 0.154042E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.171806E+11 | 0.596440E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.797437E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.315097E+10 | 0.164571E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.143029E+10 | 0.197366E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.128629E+10 | 0.130563E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.143159E+10 | 0.110804E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.142728E+10 | 0.412161E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.188414E+10 | 0.360417E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.243931E+10 | 243704.66 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.306851E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.288063E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.194260E+10 | 62544240.11 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.153939E+10 | 0.212803E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.134921E+10 | 0.785503E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.142897E+10 | 0.186644E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.221082E+11 | 0.770655E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.128629E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.306851E+10 | 0.197366E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.178176E+10 | 0.00 | 0.308154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148993E+10 | 0.00 | 0.224436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152433E+10 | 0.00 | 0.188477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121317E+10 | 1325910.73 | 0.692927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109820E+10 | 0.193340E+10 | 0.493061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107698E+10 | 0.603497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110468E+10 | 0.100573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110795E+10 | 0.691623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105331E+10 | 0.812366E+09 | 8700491.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113561E+10 | 7635045.11 | 0.258201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130856E+10 | 0.00 | 0.118845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170769E+10 | 0.00 | 0.276083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156022E+11 | 0.257632E+11 | 0.121613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178176E+10 | 0.100573E+11 | 0.308154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.879805E+10 | 0.00 | 0.569059E+11 | 0.742967E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.736886E+10 | 0.00 | 0.282012E+11 | 0.666357E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.780619E+10 | 3041743.78 | 0.141981E+11 | 0.708335E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.718010E+10 | 0.282742E+10 | 0.154898E+10 | 0.460933E+11 | 53779416.99 | 0.00 | 0.00 | 0.00 |
May | 0.737710E+10 | 0.190123E+11 | 45247993.80 | 0.174556E+11 | 0.781256E+09 | 0.00 | 0.00 | 0.00 |
June | 0.720866E+10 | 0.357297E+11 | 0.00 | 0.445531E+10 | 0.568464E+10 | 0.00 | 0.00 | 0.00 |
July | 0.735843E+10 | 0.508127E+11 | 0.00 | 0.138407E+10 | 0.873746E+10 | 0.00 | 0.00 | 0.00 |
August | 0.746621E+10 | 0.397780E+11 | 0.00 | 0.318074E+10 | 0.344906E+10 | 0.00 | 0.00 | 0.00 |
September | 0.714524E+10 | 0.140757E+11 | 0.00 | 0.175619E+11 | 0.122177E+09 | 0.00 | 0.00 | 0.00 |
October | 0.730690E+10 | 0.510415E+10 | 0.120914E+09 | 0.459681E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724143E+10 | 0.188901E+09 | 0.766236E+10 | 0.595043E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.851145E+10 | 0.00 | 0.454378E+11 | 0.759971E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.907686E+11 | 0.167532E+12 | 0.154121E+12 | 0.483366E+12 | 0.188284E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.714524E+10 | 0.00 | 0.00 | 0.138407E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.879805E+10 | 0.508127E+11 | 0.569059E+11 | 0.759971E+11 | 0.873746E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.101706E+10 | 0.00 | 0.133302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.843147E+09 | 0.00 | 0.840505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.886004E+09 | 648.10 | 0.670268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.756605E+09 | 0.251771E+09 | 0.207039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.748214E+09 | 0.274003E+10 | 0.117127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.766268E+09 | 0.625109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.833146E+09 | 0.965966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.841653E+09 | 0.803698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.740017E+09 | 0.239623E+10 | 3460744.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.746079E+09 | 0.566924E+09 | 0.773624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.797436E+09 | 2635.02 | 0.443168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.999680E+09 | 0.00 | 0.124774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.997531E+10 | 0.299027E+11 | 0.483117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.740017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101706E+10 | 0.965966E+10 | 0.133302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143029E+10 | 0.00 | 0.159866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128629E+10 | 0.00 | 0.105756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143159E+10 | 0.00 | 0.897508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136083E+10 | 0.290080E+09 | 0.333851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139896E+10 | 0.218459E+10 | 0.291938E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138054E+10 | 0.487208E+10 | 197400.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143724E+10 | 0.772193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145682E+10 | 0.680708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136292E+10 | 0.272412E+10 | 50660834.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138631E+10 | 0.725273E+09 | 0.172370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134909E+10 | 495950.42 | 0.636258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142897E+10 | 0.00 | 0.151182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167098E+11 | 0.253257E+11 | 0.624231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145682E+10 | 0.772193E+10 | 0.159866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.178176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121317E+10 | 0.00 | 0.00 | 0.00 | 403073.20 | 0.00 | 0.855465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109820E+10 | 0.00 | 0.00 | 0.00 | 0.508204E+09 | 0.00 | 0.608717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107698E+10 | 0.00 | 0.00 | 0.00 | 0.152002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110468E+10 | 0.00 | 0.00 | 0.00 | 0.246722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110795E+10 | 0.00 | 0.00 | 0.00 | 0.169781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105331E+10 | 0.00 | 0.00 | 0.00 | 0.207769E+09 | 0.00 | 10741347.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113561E+10 | 0.00 | 0.00 | 0.00 | 2154454.00 | 0.00 | 0.318767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156022E+11 | 0.00 | 0.00 | 0.00 | 0.640358E+10 | 0.00 | 0.150139E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.105331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178176E+10 | 0.00 | 0.00 | 0.00 | 0.246722E+10 | 0.00 | 0.380437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.879805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.736886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.780619E+10 | 0.00 | 0.00 | 0.00 | 956728.77 | 0.00 | 0.177476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.718010E+10 | 0.00 | 0.00 | 0.00 | 0.860163E+09 | 0.00 | 0.193623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.737710E+10 | 0.00 | 0.00 | 0.00 | 0.553746E+10 | 0.00 | 56559992.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.720866E+10 | 0.00 | 0.00 | 0.00 | 0.100710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.735843E+10 | 0.00 | 0.00 | 0.00 | 0.140117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.746621E+10 | 0.00 | 0.00 | 0.00 | 0.109589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.714524E+10 | 0.00 | 0.00 | 0.00 | 0.410084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.730690E+10 | 0.00 | 0.00 | 0.00 | 0.153648E+10 | 0.00 | 0.151142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724143E+10 | 0.00 | 0.00 | 0.00 | 57787352.19 | 0.00 | 0.957795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.851145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.907686E+11 | 0.00 | 0.00 | 0.00 | 0.471353E+11 | 0.00 | 0.192651E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.714524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.879805E+10 | 0.00 | 0.00 | 0.00 | 0.140117E+11 | 0.00 | 0.711324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.101706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.843147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.886004E+09 | 0.00 | 0.00 | 0.00 | 183.20 | 0.00 | 0.827492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.756605E+09 | 0.00 | 0.00 | 0.00 | 65303464.83 | 0.00 | 0.255604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.748214E+09 | 0.00 | 0.00 | 0.00 | 0.681363E+09 | 0.00 | 0.144601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.766268E+09 | 0.00 | 0.00 | 0.00 | 0.153119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.833146E+09 | 0.00 | 0.00 | 0.00 | 0.231783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.841653E+09 | 0.00 | 0.00 | 0.00 | 0.189715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.740017E+09 | 0.00 | 0.00 | 0.00 | 0.576768E+09 | 0.00 | 4272524.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.746079E+09 | 0.00 | 0.00 | 0.00 | 0.135715E+09 | 0.00 | 0.955091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.797436E+09 | 0.00 | 0.00 | 0.00 | 745.83 | 0.00 | 0.547121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.999680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.997531E+10 | 0.00 | 0.00 | 0.00 | 0.720532E+10 | 0.00 | 0.596440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.740017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101706E+10 | 0.00 | 0.00 | 0.00 | 0.231783E+10 | 0.00 | 0.164571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.143029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136083E+10 | 0.00 | 0.00 | 0.00 | 66451431.43 | 0.00 | 0.412161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139896E+10 | 0.00 | 0.00 | 0.00 | 0.485171E+09 | 0.00 | 0.360417E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138054E+10 | 0.00 | 0.00 | 0.00 | 0.105877E+10 | 0.00 | 243704.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143724E+10 | 0.00 | 0.00 | 0.00 | 0.163126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145682E+10 | 0.00 | 0.00 | 0.00 | 0.142381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136292E+10 | 0.00 | 0.00 | 0.00 | 0.579675E+09 | 0.00 | 62544240.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138631E+10 | 0.00 | 0.00 | 0.00 | 0.153081E+09 | 0.00 | 0.212803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134909E+10 | 0.00 | 0.00 | 0.00 | 121434.85 | 0.00 | 0.785503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167098E+11 | 0.00 | 0.00 | 0.00 | 0.539835E+10 | 0.00 | 0.770655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.128629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145682E+10 | 0.00 | 0.00 | 0.00 | 0.163126E+10 | 0.00 | 0.197366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162547E+11 | 0.00 | 0.00 | 0.20 |
February | 73418360.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123023E+11 | 0.00 | 0.00 | 0.20 |
March | 0.805145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110408E+11 | 0.00 | 0.00 | 0.21 |
April | 0.359439E+10 | 0.00 | 173874.25 | 0.00 | 11155501.05 | 0.372288E+10 | 0.00 | 789.40 | 0.20 |
May | 0.294395E+10 | 72138096.02 | 0.00 | 2673039.76 | 0.00 | 0.165606E+09 | 0.172089E+10 | 0.00 | 0.30 |
June | 0.789090E+09 | 0.107250E+10 | 0.00 | 5477255.57 | 67210.36 | 0.00 | 0.296803E+10 | 0.00 | 0.42 |
July | 0.213948E+09 | 0.176471E+10 | 0.00 | 6935660.52 | 1026.85 | 0.00 | 0.249810E+10 | 0.00 | 0.45 |
August | 0.422612E+09 | 0.767435E+09 | 0.00 | 9110274.67 | 11469.68 | 0.00 | 0.375661E+10 | 0.00 | 0.50 |
September | 0.266394E+10 | 19831634.41 | 0.00 | 5757027.95 | 0.00 | 0.00 | 0.404719E+10 | 0.00 | 0.35 |
October | 0.627574E+10 | 0.00 | 0.00 | 252783.78 | 0.00 | 0.958021E+09 | 0.351089E+09 | 0.00 | 0.21 |
November | 0.269883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701126E+10 | 0.00 | 0.00 | 0.20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153969E+11 | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.204811E+11 | 0.369661E+10 | 173874.25 | 30206042.25 | 11235207.95 | 0.668525E+11 | 0.153419E+11 | 789.40 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.627574E+10 | 0.176471E+10 | 173874.25 | 9110274.67 | 11155501.05 | 0.162547E+11 | 0.404719E+10 | 789.40 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423277E+11 | 0.00 | 0.00 | 0.39 |
February | 0.196817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192625E+11 | 0.00 | 0.00 | 0.39 |
March | 0.242925E+11 | 0.00 | 0.00 | 64699.20 | 0.00 | 0.880700E+10 | 0.133509E+09 | 0.00 | 0.40 |
April | 0.155566E+11 | 23751673.64 | 0.00 | 12470384.71 | 913591.90 | 0.994681E+09 | 0.873530E+10 | 0.00 | 0.41 |
May | 0.257900E+10 | 0.371098E+09 | 0.00 | 41130416.22 | 6447.86 | 13561356.03 | 0.189619E+11 | 0.00 | 0.50 |
June | 0.333308E+09 | 0.442995E+10 | 0.00 | 43294765.44 | 29369077.67 | 0.00 | 0.163006E+11 | 0.00 | 0.56 |
July | 97379636.24 | 0.753223E+10 | 0.00 | 39607583.50 | 33430516.75 | 0.00 | 0.102821E+11 | 0.00 | 0.55 |
August | 0.214179E+09 | 0.372156E+10 | 0.00 | 54452636.72 | 3487593.60 | 0.00 | 0.162671E+11 | 0.00 | 0.59 |
September | 0.167929E+10 | 0.122580E+09 | 0.00 | 57944914.55 | 0.00 | 0.00 | 0.259766E+11 | 0.00 | 0.51 |
October | 0.132195E+11 | 0.00 | 0.00 | 23229551.90 | 0.00 | 15084893.84 | 0.124284E+11 | 0.00 | 0.41 |
November | 0.228550E+11 | 0.00 | 0.00 | 747413.30 | 0.00 | 0.433521E+10 | 0.938065E+09 | 0.00 | 0.39 |
December | 0.196972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341040E+11 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.139567E+12 | 0.162012E+11 | 0.00 | 0.272942E+09 | 67207227.79 | 0.109860E+12 | 0.110024E+12 | 0.00 | 0.46 |
Minimum of Months | 97379636.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.242925E+11 | 0.753223E+10 | 0.00 | 57944914.55 | 33430516.75 | 0.423277E+11 | 0.259766E+11 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.504931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698528E+10 | 0.00 | 0.00 | 0.39 |
February | 0.555346E+10 | 0.00 | 0.00 | 33017.04 | 0.00 | 0.352348E+10 | 76159009.36 | 0.00 | 0.39 |
March | 0.589204E+10 | 0.00 | 0.00 | 75744.27 | 0.00 | 0.267578E+10 | 0.133644E+09 | 0.00 | 0.40 |
April | 0.379305E+10 | 10650829.99 | 0.00 | 2568247.75 | 0.00 | 0.643029E+09 | 0.153030E+10 | 0.00 | 0.49 |
May | 0.107561E+10 | 0.151256E+09 | 0.00 | 6246891.24 | 0.00 | 29964290.37 | 0.294111E+10 | 0.00 | 0.71 |
June | 0.279008E+09 | 0.109126E+10 | 0.00 | 7003504.54 | 0.00 | 0.00 | 0.234727E+10 | 0.00 | 0.85 |
July | 74278905.50 | 0.186384E+10 | 0.00 | 7165100.16 | 13996.70 | 0.00 | 0.168636E+10 | 0.00 | 0.90 |
August | 0.117591E+09 | 0.104900E+10 | 0.00 | 10167341.59 | 15842.82 | 0.00 | 0.271881E+10 | 0.00 | 1.01 |
September | 0.849108E+09 | 48601949.30 | 0.00 | 12152489.72 | 0.00 | 0.00 | 0.468130E+10 | 0.00 | 0.82 |
October | 0.367211E+10 | 0.00 | 0.00 | 5435724.17 | 0.00 | 0.148965E+09 | 0.244660E+10 | 0.00 | 0.51 |
November | 0.532140E+10 | 0.00 | 0.00 | 344305.91 | 0.00 | 0.161099E+10 | 0.281985E+09 | 0.00 | 0.40 |
December | 0.485821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652474E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.365352E+11 | 0.421460E+10 | 0.00 | 51192366.39 | 29839.52 | 0.221422E+11 | 0.188435E+11 | 0.00 | 0.60 |
Minimum of Months | 74278905.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.589204E+10 | 0.186384E+10 | 0.00 | 12152489.72 | 15842.82 | 0.698528E+10 | 0.468130E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.171734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103158E+11 | 0.00 | 0.00 | 0.39 |
February | 0.255966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655971E+10 | 0.00 | 0.00 | 0.39 |
March | 0.317621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545752E+10 | 0.00 | 0.00 | 0.40 |
April | 0.291935E+10 | 8424620.63 | 0.00 | 705245.34 | 0.00 | 0.190158E+10 | 0.488888E+09 | 0.00 | 0.40 |
May | 0.175004E+10 | 0.104366E+09 | 0.00 | 1931245.62 | 0.00 | 0.131795E+09 | 0.864792E+09 | 0.00 | 0.40 |
June | 0.574055E+09 | 0.825498E+09 | 0.00 | 2762468.74 | 0.00 | 0.00 | 0.868993E+09 | 0.00 | 0.41 |
July | 0.188216E+09 | 0.135362E+10 | 0.00 | 2925851.31 | 0.00 | 0.00 | 0.489495E+09 | 0.00 | 0.40 |
August | 0.310276E+09 | 0.685802E+09 | 0.00 | 4219943.19 | 0.00 | 0.00 | 0.794414E+09 | 0.00 | 0.41 |
September | 0.172123E+10 | 30054190.77 | 0.00 | 5552038.20 | 0.00 | 793082.24 | 0.151976E+10 | 0.00 | 0.40 |
October | 0.393866E+10 | 0.00 | 0.00 | 2090373.56 | 0.00 | 0.686202E+09 | 0.648900E+09 | 0.00 | 0.39 |
November | 0.330334E+10 | 0.00 | 0.00 | 35118.66 | 0.00 | 0.372844E+10 | 45514152.48 | 0.00 | 0.39 |
December | 0.143732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994431E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.235957E+11 | 0.300776E+10 | 0.00 | 20222284.63 | 0.00 | 0.387262E+11 | 0.572076E+10 | 0.00 | 0.40 |
Minimum of Months | 0.188216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.393866E+10 | 0.135362E+10 | 0.00 | 5552038.20 | 0.00 | 0.103158E+11 | 0.151976E+10 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |