Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2020-06-03 19:12:33
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1415.14 | 616.89 | 616.89 |
Net Site Energy | 1415.14 | 616.89 | 616.89 |
Total Source Energy | 2989.06 | 1302.99 | 1302.99 |
Net Source Energy | 2989.06 | 1302.99 | 1302.99 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 619.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 77.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 238.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 38.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 149.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 96.72 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 698.53 | 716.60 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 619.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 77.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 238.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 38.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 149.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 96.72 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 120.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 98.84 | 312.38 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 304.51 | 312.38 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 120.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 98.84 | 312.38 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 304.51 | 312.38 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 698.534 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 698.534 | 100.00 |
Total On-Site and Utility Electric Sources | 698.534 | 100.00 |
Total Electricity End Uses | 698.534 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2121.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 4.6739 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 11.3021 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 11.3021 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 11.3021 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 9.0417 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 10.1926 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 10.1926 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUL-13:00 | 07-FEB-07:10 | - | - | - | 22-FEB-12:30 |
Heating | 0.00 | 233473.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 36012.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 16658.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8493.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 71905.99 | 235333.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 233473.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 36012.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 16658.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8493.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 671.95 | 0.00 | 0.00 | 0.00 |
Cooling | 245.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 756.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 122.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 615.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 472.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 104.85 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2212.26 | 776.80 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 292.92 | 0.00 | 0.00 | 0.00 |
Cooling | 107.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 329.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 205.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 45.70 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 964.37 | 338.62 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 292.92 | 0.00 | 0.00 | 0.00 |
Cooling | 107.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 329.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 205.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 45.70 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 964.37 | 338.62 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.59 |
CORE_RETAIL DIRECT AIR | 6.46 |
POINT_OF_SALE DIRECT AIR | 1.00 |
FRONT_RETAIL DIRECT AIR | 0.721089 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 1.71 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 1.71 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 49472.11 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 45896.27 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 228847.98 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 30333.28 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 24020.69 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.59 | 1.59 | 1.59 | 1.59 | 1.64 | 1.64 | 1.00 | 0.969284 | 1.64 |
PSZ-AC:2 | 6.46 | 6.46 | 6.46 | 6.46 | 6.74 | 6.74 | 1.00 | 0.957993 | 6.74 |
PSZ-AC:3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PSZ-AC:4 | 0.721089 | 0.721089 | 0.721089 | 0.721089 | 0.734616 | 0.734616 | 1.00 | 0.981585 | 0.734616 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.64 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 6.74 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.00 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 0.734616 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.64 | 1.64 | 1.64 | 1.08 | 32090.83 | 45896.27 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 6.74 | 6.74 | 6.74 | 4.45 | 149424.71 | 228847.98 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 0.661470 | 19642.91 | 30333.28 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.734616 | 0.734616 | 0.734616 | 0.734616 | 15358.88 | 24020.69 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.64 | 0.818395 | 1.09 | 30051.26 | 32090.83 | 16045.42 | 16045.42 | 0.741416 | 0.741420 | 0.741420 | 0.741420 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 6.74 | 3.37 | 4.50 | 141170.13 | 149424.71 | 74712.35 | 74712.35 | 0.705718 | 0.705720 | 0.705720 | 0.705720 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.00 | 0.501115 | 0.668153 | 18375.76 | 19642.91 | 9821.45 | 9821.45 | 0.741523 | 0.741520 | 0.741520 | 0.741520 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 0.734620 | 0.367310 | 0.489747 | 14445.64 | 15358.88 | 7679.44 | 7679.44 | 0.722095 | 0.722090 | 0.722090 | 0.722090 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.64 | 1751.44 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 6.74 | 11363.26 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.00 | 1109.63 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.734616 | 813.34 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 4.674 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 12.744 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 11.302 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 14.532 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 11.302 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 32.822 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 11.302 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 14.532 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 9.042 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.042 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 1775.580 | 4.674 | 28.946 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1775.580 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 18088.827 | 11.302 | 69.994 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18088.827 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 1704.471 | 11.302 | 69.994 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1704.471 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 1704.471 | 11.302 | 69.994 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1704.471 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 108.500 | 9.042 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.500 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.5534 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1659 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.3309E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1913 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1913 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.3147 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.640 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.950 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 30.14 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.149 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.149 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.101 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 9 | 0.29758781E-14 | -0.29065710E-15 | -0.16717921E-09 | -0.54082436E-16 |
25 | 8 | 0.24322757E-07 | 0.75510264E-13 | 0.40304845E-03 | -0.27655812E-09 |
26 | 7 | -0.12993629E-01 | 0.38338009E-08 | -0.24168191E-01 | 0.14774231E-03 |
27 | 6 | 0.42578349 | 0.13225368E-05 | 0.48945559 | -0.49886206E-02 |
28 | 5 | -5.3899404 | 0.49024379E-04 | -4.5744615 | 0.65656055E-01 |
29 | 4 | 33.884590 | 0.39840510E-03 | 21.960611 | -0.43383013 |
30 | 3 | -113.10176 | 0.86320527E-03 | -56.652426 | 1.5422922 |
31 | 2 | 198.98955 | 0.48301085E-03 | 78.818690 | -2.9302292 |
32 | 1 | -171.85079 | 0.51313109E-04 | -55.530381 | 2.7576150 |
33 | 0 | 57.057407 | 0.29052359E-06 | 15.514123 | |
34 | 7 | -0.25528060E-08 | -0.12031403E-14 | 0.68407999E-14 | -0.93970880E-16 |
35 | 6 | 0.47134542E-05 | 0.31734324E-08 | 0.31924928E-02 | -0.26781305E-04 |
36 | 5 | -0.33464294E-03 | 0.18778732E-05 | -0.22387365 | 0.19574661E-02 |
37 | 4 | 0.76699050E-02 | 0.85441795E-04 | 4.8320287 | -0.45288849E-01 |
38 | 3 | -0.67267585E-01 | 0.67916014E-03 | -38.035443 | 0.39880879 |
39 | 2 | 0.23873650 | 0.11294419E-02 | 116.51125 | -1.4183045 |
40 | 1 | -0.34450630 | 0.34392527E-03 | -143.92338 | 2.0493041 |
41 | 0 | 0.16794560 | 0.83374149E-05 | 60.838472 | |
42 | 7 | -0.12973758E-07 | 0.34411372E-14 | -0.15771944E-13 | 0.23851239E-15 |
43 | 6 | 0.18530215E-05 | 0.67214774E-09 | 0.32028229E-02 | -0.26867962E-04 |
44 | 5 | -0.88022991E-04 | 0.38590341E-06 | -0.22446025 | 0.19626440E-02 |
45 | 4 | 0.17210852E-02 | 0.17282655E-04 | 4.8417890 | -0.45382682E-01 |
46 | 3 | -0.14132592E-01 | 0.13559951E-03 | -38.090529 | 0.39941776 |
47 | 2 | 0.48779578E-01 | 0.22269637E-03 | 116.61840 | -1.4197378 |
48 | 1 | -0.69488798E-01 | 0.66762873E-04 | -143.98642 | 2.0503404 |
49 | 0 | 0.33651223E-01 | 0.15845250E-05 | 60.838472 | |
50 | 7 | -0.22078744E-08 | -0.78010070E-15 | 0.51210754E-14 | -0.71692469E-16 |
51 | 6 | 0.53924046E-05 | 0.36628569E-08 | 0.31905048E-02 | -0.26764628E-04 |
52 | 5 | -0.38538745E-03 | 0.21680609E-05 | -0.22376067 | 0.19564689E-02 |
53 | 4 | 0.88497020E-02 | 0.98671011E-04 | 4.8301469 | -0.45270761E-01 |
54 | 3 | -0.77667315E-01 | 0.78446833E-03 | -38.024813 | 0.39869130 |
55 | 2 | 0.27571886 | 0.13048573E-02 | 116.49056 | -1.4180278 |
56 | 1 | -0.39792016 | 0.39739385E-03 | -143.91120 | 2.0491039 |
57 | 0 | 0.19399612 | 0.96507839E-05 | 60.838472 | |
58 | 7 | -0.22078744E-08 | -0.78010070E-15 | 0.51210754E-14 | -0.71692469E-16 |
59 | 6 | 0.53924046E-05 | 0.36628569E-08 | 0.31905048E-02 | -0.26764628E-04 |
60 | 5 | -0.38538745E-03 | 0.21680609E-05 | -0.22376067 | 0.19564689E-02 |
61 | 4 | 0.88497020E-02 | 0.98671011E-04 | 4.8301469 | -0.45270761E-01 |
62 | 3 | -0.77667315E-01 | 0.78446833E-03 | -38.024813 | 0.39869130 |
63 | 2 | 0.27571886 | 0.13048573E-02 | 116.49056 | -1.4180278 |
64 | 1 | -0.39792016 | 0.39739385E-03 | -143.91120 | 2.0491039 |
65 | 0 | 0.19399612 | 0.96507839E-05 | 60.838472 | |
66 | 7 | -0.13255510E-08 | -0.17188199E-15 | 0.92128295E-14 | -0.12705258E-15 |
67 | 6 | 0.87884716E-05 | 0.60547316E-08 | 0.31807701E-02 | -0.26682965E-04 |
68 | 5 | -0.63593173E-03 | 0.35898785E-05 | -0.22320731 | 0.19515846E-02 |
69 | 4 | 0.14651324E-01 | 0.16347926E-03 | 4.8209294 | -0.45182156E-01 |
70 | 3 | -0.12872491 | 0.13006479E-02 | -37.972737 | 0.39811570 |
71 | 2 | 0.45715725 | 0.21644648E-02 | 116.38920 | -1.4166720 |
72 | 1 | -0.65988557 | 0.65992538E-03 | -143.85153 | 2.0481231 |
73 | 0 | 0.32173707 | 0.15909640E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.36_SHGC_0.38 | 30 | 1 | VerySmooth | 2.045 | 0.374 | 0.294 | 0.419 |
2 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 31 | 1 | VerySmooth | 2.843 | 0.395 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.65598E-002 | 0.29373 | 0.50072 | 0.50072 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1915 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 18373.93027 | 22048.71632 | 1.32210 | 1.58652 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33455E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 23624.48047 | 28349.37656 | 1.02035 | 1.22442 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 74948.38062 | 89938.05674 | 5.38465 | 6.46158 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33455E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 56824.14860 | 68188.97832 | 2.41870 | 2.90245 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 11432.33680 | 13718.80415 | 0.83519 | 1.00223 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33455E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 11621.96247 | 13946.35497 | 0.50399 | 0.60479 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 8305.92020 | 9967.10424 | 0.60091 | 0.72109 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33455E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 11623.83760 | 13948.60512 | 0.50408 | 0.60489 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30000 | 1.33455E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 41221.37210 | 49465.64652 | 1.42700 | 1.71240 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -16.30000 | 9.24091E-004 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 21434.98 | 1.63679 | 1.63679 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 37740.86 | 1.22442 | 1.22442 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 94548.43 | 6.74492 | 6.74492 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 148411.35 | 2.90245 | 2.90245 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 13977.90 | 1.00223 | 1.00223 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 21409.38 | 0.60479 | 0.60479 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 10932.86 | 0.73462 | 0.73462 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 21411.62 | 0.60489 | 0.60489 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.58652 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.46158 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00223 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.72109 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.71240 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.71240 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 49472.11153 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.58652 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.58652 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.58652 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.58652 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.63679 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.63679 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.96928 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.46158 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.46158 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.46158 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 6.46158 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.74492 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 6.74492 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.95799 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00223 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00223 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00223 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00223 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00223 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00223 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.72109 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.72109 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.72109 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.72109 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.73462 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.73462 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 0.98159 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.63679 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 6.74492 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.00223 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.73462 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.63679 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.63679 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.63679 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.63679 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.08028 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.63679 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.81840 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.09119 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 30051.25990 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 32090.83000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16045.41500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 16045.41500 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74142 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74142 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74142 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74142 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32090.83000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 45896.27327 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.63679 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1751.44263 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 45896.27327 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.74492 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 6.74492 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 6.74492 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.74492 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.45164 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 6.74492 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.37246 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.49661 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 141170.13458 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 149424.71000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 74712.35500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 74712.35500 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70572 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70572 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70572 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70572 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 149424.71000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 228847.97996 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 6.74492 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 11363.25736 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 228847.97996 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00223 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00223 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00223 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00223 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66147 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00223 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50112 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66815 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18375.75802 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19642.91000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9821.45500 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9821.45500 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74152 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74152 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74152 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74152 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19642.91000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30333.27614 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00223 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1109.62505 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 30333.27614 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.73462 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.73462 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.73462 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.73462 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.73462 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.73462 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.36731 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.48975 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 14445.63664 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 15358.88000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7679.44000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 7679.44000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72210 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72209 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72209 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72209 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15358.88000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24020.69259 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.73462 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 813.33683 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 24020.69259 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 30804.9 | 11.49 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 144114.9 | 12.96 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 18855.5 | 118.05 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 14781.1 | 175.25 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.166 | 0.159 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 3.309E-002 | 3.283E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | N/A | 2.843 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.191 | 0.183 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.191 | 0.183 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.315 | 0.292 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 7 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 8.6577918380E-002 | 0.3484087714 | Pass | Pass | 3.8222758778E-002 | 0.1497867850 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 4.5683022539E-002 | 0.2073747444 | Pass | Pass | 0.2501034020 | 2.1519742416 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 9.3010797311E-002 | 0.4030300968 | Pass | Pass | 5.3942697457E-002 | 0.1705824986 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 0.1018740930 | 0.4216762490 | Pass | Pass | 3.6649920526E-002 | 0.1461534447 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1297833987 | 0.1950481899 | Pass | Pass | 0.1040717419 | 0.5993883550 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.166 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.033 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.191 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.191 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.315 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.5_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.395 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.36_SHGC_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.045 | 0.374 | 0.419 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.36_SHGC_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.045 | 0.374 | 0.419 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.36_SHGC_0.38 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.045 | 0.374 | 0.419 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 2.221 | 0.379 | 0.415 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 2.221 | 0.379 | 0.415 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 4.6739 | 379.89 | 1775.58 | LightsWired | BLDG_LIGHT_BACK_SCH | 55.08 | 168.00 | 53.35 | 0.0000 | Y | 17.78 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 11.3021 | 1600.48 | 18088.83 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 53.01 | 0.0000 | Y | 180.00 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 11.3021 | 150.81 | 1704.47 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 65.23 | 0.0000 | Y | 20.87 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 11.3021 | 150.81 | 1704.47 | LightsWired | BLDG_LIGHT_FRONT_SCH | 67.15 | 168.00 | 63.20 | 0.0000 | Y | 20.22 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 9.0417 | 12.00 | 108.50 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 57.54 | 168.00 | 4.00 | 0.0000 | Y | 0.08 |
Interior Lighting Total | 10.1926 | 2293.99 | 23381.85 | 238.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 18088.83 | 4522.21 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 18088.83 | 4522.21 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 316.30 | AstronomicalClock | - | 42.04 | 42.04 | 2.50 | |
EXTERIOR_LIGHTS_B | 3054.90 | AstronomicalClock | - | 83.67 | 62.85 | 36.04 | |
Exterior Lighting Total | 3371.20 | 38.54 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 32090.83 | 23792.78 | 8298.05 | 0.74 | 3.80 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 149424.71 | 105452.01 | 43972.70 | 0.71 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 19642.91 | 14565.61 | 5077.30 | 0.74 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 15358.88 | 11090.49 | 4268.39 | 0.72 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 30804.9 | 11.49 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 144114.9 | 12.96 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 18855.5 | 118.05 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 14781.1 | 175.25 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 49472.11 | 0.81 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 45896.27 | 0.81 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 228847.98 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 30333.28 | 0.81 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 24020.69 | 0.81 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.58 | 622.50 | 1.71 | 1832.35 | 1070.05 | 1.00 | 1.33 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.64 | 1751.44 | 1070.05 | 1.00 | 1.35 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 6.74 | 11363.26 | 1684.71 | 1.00 | 1.16 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1109.63 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.73 | 813.34 | 1107.16 | 1.00 | 1.49 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 18373.93 | 22048.72 | 58.04 | 1.322 | 1.587 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01047 | 23.42 | 0.01335 | 0.232 | 0.00 |
CORE_RETAIL | 74948.38 | 89938.06 | 56.19 | 5.385 | 6.462 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01051 | 23.42 | 0.01335 | 1.890 | 0.00 |
POINT_OF_SALE | 11432.34 | 13718.80 | 90.97 | 0.835 | 1.002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00915 | 23.42 | 0.01335 | 0.178 | 0.00 |
FRONT_RETAIL | 8305.92 | 9967.10 | 66.09 | 0.601 | 0.721 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01006 | 23.42 | 0.01335 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.07 | 100.00 | 0.00001 | 30.30 | 0.01335 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 23624.48 | 28349.38 | 74.63 | 1.020 | 1.224 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00749 | -16.30 | 0.00092 | 0.232 | 0.00 |
CORE_RETAIL | 56824.15 | 68188.98 | 42.61 | 2.419 | 2.902 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00737 | -16.30 | 0.00092 | 1.890 | 0.00 |
POINT_OF_SALE | 11621.96 | 13946.35 | 92.48 | 0.504 | 0.605 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00766 | -16.30 | 0.00092 | 0.178 | 0.00 |
FRONT_RETAIL | 11623.84 | 13948.61 | 92.49 | 0.504 | 0.605 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00766 | -16.30 | 0.00092 | 0.178 | 0.00 |
FRONT_ENTRY | 41221.37 | 49465.65 | 4122.14 | 1.427 | 1.712 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | 16.00 | 15.87 | 0.00497 | -16.30 | 0.00092 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.64 | 1.64 | 1.22 | 1.22 | 1.6368 | 1.5865 | 1.6368 | 0.9693 | 1.0000 |
PSZ-AC:2 | 6.74 | 6.74 | 2.90 | 2.90 | 6.7449 | 6.4616 | 6.7449 | 0.9580 | 1.0000 |
PSZ-AC:3 | 1.00 | 1.00 | 0.60 | 0.60 | 1.0022 | 1.0022 | 1.0022 | 1.0000 | 1.0000 |
PSZ-AC:4 | 0.73 | 0.73 | 0.60 | 0.60 | 0.7346 | 0.7211 | 0.7346 | 0.9816 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 49472.112 | 49472.112 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | 49472.11 | 49472.11 | 1.712398 | 15.60 | 9.34 | 0.00493485 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 15.87 | 0.00496832 | 43.4142 | 49465.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 16045.415 | 0.000 | 1.636790 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 16045.42 | 11485.84 | 1.636790 | 23.90 | 17.75 | 0.01051950 | 12.80 | 11.87 | 0.00850000 | 24.01 | 0.01334551 | 19.95 | 14.1476 | 23.88 | 0.01046811 | 55.1496 | 18373.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 45896.273 | 45896.273 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 45896.27 | 45896.27 | 1.636790 | 13.87 | 10.00 | 0.00624836 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 14.1476 | 21.11 | 0.00749016 | 46.9305 | 23624.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 74712.355 | 0.000 | 6.744920 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 74712.35 | 55109.43 | 6.744920 | 25.86 | 18.45 | 0.01058638 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01334551 | 21.80 | 28.0242 | 23.88 | 0.01051450 | 55.3911 | 74649.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 228847.980 | 228847.980 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 228847.98 | 228847.98 | 6.744915 | -3.35 | -3.35 | 0.00317266 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 28.0243 | 21.11 | 0.00737156 | 46.1946 | 56824.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 9821.455 | 0.000 | 1.002230 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 9821.45 | 7901.28 | 1.002230 | 25.07 | 17.60 | 0.00984907 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01334551 | 21.80 | 17.7714 | 23.89 | 0.00915329 | 48.3125 | 10690.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 30333.276 | 30333.276 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30333.28 | 30333.28 | 1.002228 | 9.99 | 7.61 | 0.00567897 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 17.7715 | 21.11 | 0.00766382 | 48.0042 | 11621.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 7679.440 | 0.000 | 0.734620 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 7679.44 | 5889.15 | 0.734620 | 25.45 | 18.03 | 0.01023285 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01334551 | 21.80 | 24.2453 | 23.88 | 0.01006017 | 53.0322 | 8113.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 24020.693 | 24020.693 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24020.69 | 24020.69 | 0.734616 | 9.99 | 7.61 | 0.00567940 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 24.2454 | 21.11 | 0.00766396 | 48.0051 | 11623.84 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 49472.112 | 49472.112 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 1.712398 | 2.01022759 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | 49472.11 | 49472.11 | 1.0000 | 2.01022759 | 1.712398 | 15.60 | 9.34 | 0.00493485 | 28159.7 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49472.11 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 15.87 | 0.00496832 | 15.87 | 0.00496832 | 43.4142 | 49465.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16045.415 | 0.000 | 1.636790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3952 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 16045.42 | 11485.84 | 1.0000 | 1.92146921 | 1.636790 | 23.90 | 17.75 | 0.01051950 | 50793.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16045.42 | 24.01 | 0.01334551 | 19.95 | 0.23156651 | 14.1476 | 23.88 | 0.01005380 | 23.88 | 0.01046811 | 55.1496 | 18373.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 45896.273 | 45896.273 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.636790 | 1.92146917 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 45896.27 | 45896.27 | 1.0000 | 1.92146917 | 1.636790 | 13.87 | 10.00 | 0.00624836 | 29725.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45896.27 | -16.30 | 0.00092409 | -16.30 | 0.23156651 | 14.1476 | 20.91 | 0.00749016 | 21.11 | 0.00749016 | 46.9305 | 23624.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 74712.355 | 0.000 | 6.744920 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5196 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 74712.35 | 55109.43 | 1.0000 | 7.91803233 | 6.744920 | 25.86 | 18.45 | 0.01058638 | 52973.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 74712.35 | 30.30 | 0.01334551 | 21.80 | 1.89021192 | 28.0242 | 23.89 | 0.00935791 | 23.88 | 0.01051450 | 55.3911 | 74649.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 228847.980 | 228847.980 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 6.744915 | 7.91802668 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 228847.98 | 228847.98 | 1.0000 | 7.91802668 | 6.744915 | -3.35 | -3.35 | 0.00317266 | 4551.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 228847.98 | -16.30 | 0.00092409 | -16.30 | 1.89021192 | 28.0243 | 20.84 | 0.00737156 | 21.11 | 0.00737156 | 46.1946 | 56824.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9821.455 | 0.000 | 1.002230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.1489 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 9821.45 | 7901.28 | 1.0000 | 1.17654317 | 1.002230 | 25.07 | 17.60 | 0.00984907 | 50282.9 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9821.45 | 30.30 | 0.01334551 | 21.80 | 0.17811053 | 17.7714 | 23.89 | 0.00905833 | 23.89 | 0.00915329 | 48.3125 | 10690.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30333.276 | 30333.276 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.002228 | 1.17654036 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30333.28 | 30333.28 | 1.0000 | 1.17654036 | 1.002228 | 9.99 | 7.61 | 0.00567897 | 24347.4 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30333.28 | -16.30 | 0.00092409 | -16.30 | 0.17811053 | 17.7715 | 20.97 | 0.00766382 | 21.11 | 0.00766382 | 48.0042 | 11621.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 7679.440 | 0.000 | 0.734620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8623 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 7679.44 | 5889.15 | 1.0000 | 0.86238901 | 0.734620 | 25.45 | 18.03 | 0.01023285 | 51645.2 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7679.44 | 30.30 | 0.01334551 | 21.80 | 0.17811053 | 24.2453 | 23.89 | 0.00923350 | 23.88 | 0.01006017 | 53.0322 | 8113.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24020.693 | 24020.693 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.734616 | 0.86238465 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24020.69 | 24020.69 | 1.0000 | 0.86238465 | 0.734616 | 9.99 | 7.61 | 0.00567940 | 24350.3 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24020.69 | -16.30 | 0.00092409 | -16.30 | 0.17811053 | 24.2454 | 20.97 | 0.00766396 | 21.11 | 0.00766396 | 48.0051 | 11623.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.64 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 1.89 | 6.74 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.00 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 2664.83 | 3838.50 | 2089.67 |
CORE_RETAIL | 2439.00 | 3423.00 | 1493.50 |
POINT_OF_SALE | 2557.67 | 3162.33 | 1396.17 |
FRONT_RETAIL | 2654.67 | 3331.67 | 1620.50 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3178.67 | 3865.00 | 2121.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 46.83 | 1.33 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 35.33 | 36.67 | 0.00 | 0.00 |
FRONT_RETAIL | 51.17 | 4.83 | 0.00 | 0.00 |
FRONT_ENTRY | 469.67 | 0.00 | 0.00 | 0.00 |
Facility | 528.50 | 42.33 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.47 | 61.34 | 2317.33 | 0.531 | 0.040 | 0.000 | 0.000 |
CORE_RETAIL | 128.37 | 258.43 | 9762.95 | 0.819 | 0.008 | 0.000 | 0.000 |
POINT_OF_SALE | 12.10 | 24.35 | 919.94 | 1.032 | 0.043 | 0.000 | 0.000 |
FRONT_RETAIL | 12.10 | 24.35 | 919.94 | 0.707 | 0.043 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.47 | 61.34 | 2317.33 | 0.350 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.37 | 258.43 | 9762.95 | 0.678 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.10 | 24.35 | 919.94 | 0.678 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.10 | 24.35 | 919.94 | 0.678 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 698.53 | 2265.44 | 12-FEB-07:40 | 71905.99 | 15-JUL-14:00 |
Electricity:Building | 433.25 | 2265.44 | 01-JAN-00:10 | 31292.41 | 02-JAN-16:50 |
Electricity:Zone:BACK_SPACE | 67.55 | 535.60 | 01-JAN-00:10 | 4001.15 | 02-JAN-09:10 |
InteriorLights:Electricity | 238.96 | 493.85 | 01-JAN-00:10 | 20551.52 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:BACK_SPACE | 17.78 | 81.78 | 01-JAN-00:10 | 1249.73 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 238.96 | 493.85 | 01-JAN-00:10 | 20551.52 | 02-JAN-16:50 |
Electricity:Zone:CORE_RETAIL | 263.93 | 1109.80 | 01-JAN-00:10 | 20919.52 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 180.00 | 344.55 | 01-JAN-00:10 | 16279.94 | 02-JAN-16:50 |
Electricity:Zone:POINT_OF_SALE | 73.56 | 512.89 | 01-JAN-00:10 | 4446.74 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 20.87 | 32.47 | 01-JAN-00:10 | 1534.02 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 28.13 | 104.57 | 01-JAN-00:10 | 1922.42 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 20.22 | 32.47 | 01-JAN-00:10 | 1485.24 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 0.08 | 2.58 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 0.08 | 2.58 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 |
InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.77 | 453.82 | 01-JAN-00:10 | 2751.42 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 83.93 | 765.25 | 01-JAN-00:10 | 4639.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.69 | 480.42 | 01-JAN-00:10 | 2912.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.91 | 72.11 | 01-JAN-00:10 | 437.18 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 698.53 | 2265.44 | 12-FEB-07:40 | 71905.99 | 15-JUL-14:00 |
ElectricityPurchased:Plant | 698.53 | 2265.44 | 12-FEB-07:40 | 71905.99 | 15-JUL-14:00 |
Cogeneration:ElectricityPurchased | 698.53 | 2265.44 | 12-FEB-07:40 | 71905.99 | 15-JUL-14:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 698.53 | 2265.44 | 12-FEB-07:40 | 71905.99 | 15-JUL-14:00 |
ElectricityNet:Plant | 698.53 | 2265.44 | 12-FEB-07:40 | 71905.99 | 15-JUL-14:00 |
Cogeneration:ElectricityNet | 698.53 | 2265.44 | 12-FEB-07:40 | 71905.99 | 15-JUL-14:00 |
Electricity:HVAC | 226.74 | 0.00 | 01-JAN-00:10 | 44506.74 | 15-JUL-14:00 |
Fans:Electricity | 149.18 | 0.00 | 01-JAN-00:10 | 12349.22 | 10-DEC-09:10 |
General:Fans:Electricity | 149.18 | 0.00 | 01-JAN-00:10 | 12349.22 | 10-DEC-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 77.56 | 0.00 | 01-JAN-00:10 | 36012.95 | 15-JUL-14:00 |
ExteriorLights:Electricity | 38.54 | 0.00 | 01-JAN-08:00 | 3371.20 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 38.54 | 0.00 | 01-JAN-08:00 | 3371.20 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 716.60 | 1860.00 | 26-JAN-05:40 | 235333.45 | 07-FEB-07:10 |
Gas:Plant | 96.72 | 1860.00 | 02-JAN-06:10 | 5264.95 | 07-FEB-12:30 |
WaterSystems:Gas | 96.72 | 1860.00 | 02-JAN-06:10 | 5264.95 | 07-FEB-12:30 |
Water Heater:WaterSystems:Gas | 96.72 | 1860.00 | 02-JAN-06:10 | 5264.95 | 07-FEB-12:30 |
Gas:HVAC | 619.88 | 0.00 | 01-JAN-00:10 | 233473.45 | 07-FEB-07:10 |
Heating:Gas | 619.88 | 0.00 | 01-JAN-00:10 | 233473.45 | 07-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 22-FEB-12:30 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 22-FEB-12:30 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 22-FEB-12:30 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 22-FEB-12:30 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 22-FEB-12:30 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 22-FEB-12:30 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 22-FEB-12:30 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 22-FEB-12:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1354.08 | 0.00 | 01-JAN-00:10 | 278823.24 | 07-FEB-07:10 |
EnergyTransfer:Building | 553.81 | 0.00 | 01-JAN-00:10 | 126522.44 | 07-FEB-06:10 |
EnergyTransfer:Zone:BACK_SPACE | 83.88 | 0.00 | 01-JAN-00:10 | 43518.90 | 13-FEB-05:10 |
Heating:EnergyTransfer | 165.00 | 0.00 | 01-JAN-00:10 | 126522.44 | 07-FEB-06:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 42.34 | 0.00 | 01-JAN-00:10 | 43518.90 | 13-FEB-05:10 |
Cooling:EnergyTransfer | 388.82 | 0.00 | 01-JAN-00:10 | 68486.81 | 13-JUN-06:10 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 41.54 | 0.00 | 01-JAN-00:10 | 11405.69 | 30-JUN-21:00 |
EnergyTransfer:Zone:CORE_RETAIL | 299.20 | 0.00 | 01-JAN-00:10 | 75253.83 | 29-DEC-07:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 29.81 | 0.00 | 01-JAN-00:10 | 74008.67 | 07-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 269.39 | 0.00 | 01-JAN-00:10 | 60582.02 | 13-JUN-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 60.88 | 0.00 | 01-JAN-00:10 | 20002.00 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 9.52 | 0.00 | 01-JAN-00:10 | 20002.00 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 51.36 | 0.00 | 01-JAN-00:10 | 8667.94 | 21-SEP-13:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 43.78 | 0.00 | 01-JAN-00:10 | 19842.84 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 17.25 | 0.00 | 01-JAN-00:10 | 19842.84 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 26.53 | 0.00 | 01-JAN-00:10 | 6603.72 | 21-SEP-14:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 66.07 | 0.00 | 01-JAN-00:10 | 38683.25 | 06-FEB-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 66.07 | 0.00 | 01-JAN-00:10 | 38683.25 | 06-FEB-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 800.27 | 0.00 | 01-JAN-00:10 | 187470.36 | 07-FEB-07:10 |
HeatingCoils:EnergyTransfer | 498.42 | 0.00 | 01-JAN-00:10 | 187470.36 | 07-FEB-07:10 |
CoolingCoils:EnergyTransfer | 301.85 | 0.00 | 01-JAN-00:10 | 142669.91 | 15-JUL-14:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 42.341 | -41.538 | 0.000 | 0.000 | 40.110 | 17.781 | 49.772 | 0.000 | 0.000 | 0.165 | 0.001 | 0.000 | 0.000 | 0.000 | -24.184 | -84.448 |
CORE_RETAIL | 0.000 | 0.000 | 29.814 | -269.387 | 0.000 | 0.000 | 168.965 | 180.003 | 83.927 | 27.458 | 0.000 | 0.121 | 0.002 | 0.000 | -20.525 | 0.000 | -21.142 | -179.234 |
POINT_OF_SALE | 0.000 | 0.000 | 9.521 | -51.360 | 0.000 | 0.000 | 15.673 | 20.870 | 52.689 | 26.540 | 0.000 | 0.072 | 0.000 | 0.000 | -19.066 | 0.000 | -10.835 | -44.103 |
FRONT_RETAIL | 0.000 | 0.000 | 17.249 | -26.527 | 0.000 | 0.000 | 15.881 | 20.222 | 7.908 | 26.538 | 0.000 | 0.071 | 0.001 | 0.000 | -18.684 | 0.000 | -10.522 | -32.136 |
FRONT_ENTRY | 66.070 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.081 | 0.000 | 5.661 | 0.000 | 0.080 | 6.675 | 0.000 | -3.432 | 0.000 | -75.135 | 0.000 |
Total Facility | 66.070 | 0.000 | 98.925 | -388.812 | 0.000 | 0.000 | 240.629 | 238.957 | 194.297 | 86.197 | 0.000 | 0.509 | 6.679 | 0.000 | -61.708 | 0.000 | -141.819 | -339.920 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 16-AUG-21:35 | 0.00 | 0.00 | 0.00 | -26848.54 | 0.00 | 0.00 | 0.00 | 81.78 | 605.09 | 0.00 | 0.00 | 0.00 | 26335.18 | 0.00 | -0.00 | 0.00 | -173.52 | 0.00 |
CORE_RETAIL | 13-JUN-06:03 | 0.00 | 0.00 | 0.00 | -165188.09 | 0.00 | 0.00 | 1660.40 | 344.55 | 2062.04 | 0.00 | 0.00 | 0.00 | 162138.55 | 0.00 | -590.28 | 0.00 | -427.15 | 0.00 |
POINT_OF_SALE | 23-MAY-21:11 | 0.00 | 0.00 | 0.00 | -18646.21 | 0.00 | 0.00 | 0.00 | 32.47 | 640.56 | 0.00 | 0.00 | 0.00 | 18394.43 | 0.00 | -341.64 | 0.00 | -79.60 | 0.00 |
FRONT_RETAIL | 30-JUN-20:19 | 0.00 | 0.00 | 0.00 | -13654.43 | 0.00 | 0.00 | 0.00 | 32.47 | 96.14 | 0.00 | 0.00 | 0.00 | 14208.30 | 0.00 | -527.73 | 0.00 | -154.75 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 13-JUN-06:03 | 0.00 | 0.00 | 0.00 | -173405.81 | 0.00 | 0.00 | 2433.04 | 493.85 | 4773.73 | 0.00 | 0.00 | 0.00 | 169225.52 | 0.00 | -2105.50 | 0.00 | -1414.82 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 26-DEC-05:41 | 0.00 | 0.00 | 49190.65 | 0.00 | 0.00 | 0.00 | 0.00 | 81.78 | 605.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6326.01 | -43551.51 |
CORE_RETAIL | 07-FEB-05:01 | 0.00 | 0.00 | 235158.57 | 0.00 | 0.00 | 0.00 | 0.00 | 344.55 | 1020.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2050.24 | 0.00 | -4800.29 | -229672.92 |
POINT_OF_SALE | 07-FEB-06:01 | 0.00 | 0.00 | 31936.78 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 640.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2265.02 | 0.00 | -611.50 | -29733.28 |
FRONT_RETAIL | 06-FEB-05:31 | 0.00 | 0.00 | 25542.19 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 96.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2124.94 | 0.00 | -2425.27 | -21120.59 |
FRONT_ENTRY | 06-FEB-18:00 | 38682.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 459.27 | 0.00 | -443.30 | 0.00 | -38701.27 | 0.00 |
Total Facility | 07-FEB-06:01 | 1700.37 | 0.00 | 341202.37 | 0.00 | 0.00 | 0.00 | 0.00 | 493.85 | 2362.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7069.60 | 0.00 | -3831.88 | -334857.22 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.5865 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.6368 | 0.1415 | 1.0000 | 0.2316 | 0.1415 | ||
PSZ-AC:2 | 6.4616 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 6.7449 | 0.2802 | 1.0000 | 1.8902 | 0.2802 | ||
PSZ-AC:3 | 1.0022 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0022 | 0.1777 | 1.0000 | 0.1781 | 0.1777 | ||
PSZ-AC:4 | 0.7211 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.7346 | 0.2425 | 1.0000 | 0.1781 | 0.2425 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.5865 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.5865 | 1.0000 | 1.0000 | 0.2316 | 0.1460 | ||
PSZ-AC:2 | 6.4616 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 6.4616 | 1.0000 | 1.0000 | 1.8902 | 0.2925 | ||
PSZ-AC:3 | 1.0022 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0022 | 1.0000 | 1.0000 | 0.1781 | 0.1777 | ||
PSZ-AC:4 | 0.7211 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.7211 | 1.0000 | 1.0000 | 0.1781 | 0.2470 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.5865 | 1.5865 | 1.5865 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 6.4616 | 6.4616 | 6.4616 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.0022 | 1.0022 | 1.0022 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.7211 | 0.7211 | 0.7211 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.5865 | 1.6368 | 1.5865 | 1.5865 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.4616 | 6.7449 | 6.4616 | 6.4616 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.0022 | 1.0022 | 1.0022 | 1.0022 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.7211 | 0.7346 | 0.7211 | 0.7211 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.5865 | 1.5865 | 1.5865 | 0.2316 | 0.1891 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 6.4616 | 6.4616 | 6.4616 | 1.8902 | 0.6512 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.0022 | 1.0022 | 1.0022 | 0.1781 | 0.2945 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.7211 | 0.7211 | 0.7211 | 0.1781 | 0.2945 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.5865 | 1.5865 | 1.5865 | 1.5865 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.4616 | 6.4616 | 6.4616 | 6.4616 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.0022 | 1.0022 | 1.0022 | 1.0022 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.7211 | 0.7211 | 0.7211 | 0.7211 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:33
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 619.88 | 233473.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 77.56 | 36012.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 238.96 | 20551.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 38.54 | 3371.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 194.30 | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 149.18 | 12349.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 96.72 | 5264.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 194.30 | 698.53 |
Natural Gas | 0.00 | 716.60 |
Additional | 0.00 | 0.00 |
Total | 194.30 | 1415.14 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 104.17 |
Space Heating | 0.00 |
Space Cooling | 33.81 |
Fans (All) | 65.03 |
Service Water Heating | 0.00 |
Receptacle Equipment | 84.70 |
Miscellaneous (All) | 304.51 |
Subtotal | 304.51 |
Natural Gas [MJ/m2] | |
Space Heating | 270.22 |
Service Water Heating | 42.16 |
Miscellaneous (All) | 312.38 |
Subtotal | 312.38 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 16.89 |
Space Heating | 43.80 |
Space Cooling | 5.48 |
Fans (All) | 10.54 |
Service Water Heating | 6.83 |
Receptacle Equipment | 13.73 |
Miscellaneous | 2.72 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 2872. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3001. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3501. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4552. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_SETBACK | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_FRONTENTRY_STD2013 | FRONT_ENTRY DUALSPSCHED | January | 16.00 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153796E+12 |
February | 0.000 | 0.145073E+12 |
March | 0.000 | 0.842288E+11 |
April | 0.000 | 0.320585E+11 |
May | 0.000 | 0.175250E+10 |
June | 0.000 | 640804.232 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.506829E+08 |
October | 0.000 | 0.145810E+11 |
November | 0.000 | 0.484413E+11 |
December | 0.000 | 0.139899E+12 |
Annual Sum or Average | 0.619881E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.153796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153796E+12 |
February | 0.000 | 0.145073E+12 |
March | 0.000 | 0.842288E+11 |
April | 0.000 | 0.320585E+11 |
May | 0.000 | 0.175250E+10 |
June | 0.000 | 640804.232 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.506829E+08 |
October | 0.000 | 0.145810E+11 |
November | 0.000 | 0.484413E+11 |
December | 0.000 | 0.139899E+12 |
Annual Sum or Average | 0.619881E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.153796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153796E+12 |
February | 0.000 | 0.145073E+12 |
March | 0.000 | 0.842288E+11 |
April | 0.000 | 0.320585E+11 |
May | 0.000 | 0.175250E+10 |
June | 0.000 | 640804.232 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.506829E+08 |
October | 0.000 | 0.145810E+11 |
November | 0.000 | 0.484413E+11 |
December | 0.000 | 0.139899E+12 |
Annual Sum or Average | 0.619881E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.153796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153796E+12 |
February | 0.000 | 0.145073E+12 |
March | 0.000 | 0.842288E+11 |
April | 0.000 | 0.320585E+11 |
May | 0.000 | 0.175250E+10 |
June | 0.000 | 640804.232 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.506829E+08 |
October | 0.000 | 0.145810E+11 |
November | 0.000 | 0.484413E+11 |
December | 0.000 | 0.139899E+12 |
Annual Sum or Average | 0.619881E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.153796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153796E+12 |
February | 0.000 | 0.145073E+12 |
March | 0.000 | 0.842288E+11 |
April | 0.000 | 0.320585E+11 |
May | 0.000 | 0.175250E+10 |
June | 0.000 | 640804.232 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.506829E+08 |
October | 0.000 | 0.145810E+11 |
November | 0.000 | 0.484413E+11 |
December | 0.000 | 0.139899E+12 |
Annual Sum or Average | 0.619881E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.153796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153796E+12 |
February | 0.000 | 0.145073E+12 |
March | 0.000 | 0.842288E+11 |
April | 0.000 | 0.320585E+11 |
May | 0.000 | 0.175250E+10 |
June | 0.000 | 640804.232 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.506829E+08 |
October | 0.000 | 0.145810E+11 |
November | 0.000 | 0.484413E+11 |
December | 0.000 | 0.139899E+12 |
Annual Sum or Average | 0.619881E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.153796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153796E+12 |
February | 0.000 | 0.145073E+12 |
March | 0.000 | 0.842288E+11 |
April | 0.000 | 0.320585E+11 |
May | 0.000 | 0.175250E+10 |
June | 0.000 | 640804.232 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.506829E+08 |
October | 0.000 | 0.145810E+11 |
November | 0.000 | 0.484413E+11 |
December | 0.000 | 0.139899E+12 |
Annual Sum or Average | 0.619881E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.153796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153796E+12 |
February | 0.000 | 0.145073E+12 |
March | 0.000 | 0.842288E+11 |
April | 0.000 | 0.320585E+11 |
May | 0.000 | 0.175250E+10 |
June | 0.000 | 640804.232 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.506829E+08 |
October | 0.000 | 0.145810E+11 |
November | 0.000 | 0.484413E+11 |
December | 0.000 | 0.139899E+12 |
Annual Sum or Average | 0.619881E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.153796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153796E+12 |
February | 0.000 | 0.145073E+12 |
March | 0.000 | 0.842288E+11 |
April | 0.000 | 0.320585E+11 |
May | 0.000 | 0.175250E+10 |
June | 0.000 | 640804.232 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.506829E+08 |
October | 0.000 | 0.145810E+11 |
November | 0.000 | 0.484413E+11 |
December | 0.000 | 0.139899E+12 |
Annual Sum or Average | 0.619881E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.153796E+12 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3272722.53 | 3873.78 | 14-JAN-15:25 | 3.60 | 3.00 | 0.165229E+10 | 1854.44 | 23-JAN-15:00 | -8.3 | -9.5 |
February | 7149434.16 | 689.79 | 18-FEB-15:00 | 2.80 | 0.62 | 0.150876E+10 | 1854.44 | 08-FEB-15:00 | -7.8 | -9.1 |
March | 0.695458E+09 | 4316.32 | 25-MAR-13:05 | 1.78 | -2.0 | 0.177996E+10 | 2451.25 | 14-MAR-14:00 | 24.40 | 16.50 |
April | 0.165649E+10 | 3934.48 | 10-APR-14:50 | 4.18 | 3.42 | 0.172035E+10 | 2451.24 | 08-APR-13:00 | 20.60 | 13.76 |
May | 0.296095E+10 | 5100.70 | 27-MAY-16:00 | 21.70 | 11.99 | 0.209677E+10 | 2451.24 | 20-MAY-11:20 | 16.47 | 9.78 |
June | 0.693714E+10 | 24204.40 | 11-JUN-19:42 | 22.48 | 16.18 | 0.219390E+10 | 2451.29 | 10-JUN-13:09 | 21.10 | 13.36 |
July | 0.994462E+10 | 26543.83 | 03-JUL-20:37 | 20.37 | 15.54 | 0.218706E+10 | 2451.40 | 15-JUL-10:00 | 22.20 | 20.99 |
August | 0.935129E+10 | 26849.98 | 16-AUG-21:35 | 20.37 | 15.46 | 0.228024E+10 | 2451.32 | 15-AUG-14:00 | 23.30 | 20.62 |
September | 0.569777E+10 | 21364.65 | 17-SEP-01:58 | 23.90 | 18.46 | 0.213628E+10 | 2451.26 | 22-SEP-14:09 | 23.90 | 15.31 |
October | 0.282291E+10 | 4049.53 | 23-OCT-17:05 | 4.40 | 2.50 | 0.187860E+10 | 2451.25 | 11-OCT-14:00 | 22.20 | 14.59 |
November | 0.134697E+10 | 3876.38 | 11-NOV-16:15 | 3.53 | 1.20 | 0.161779E+10 | 2270.93 | 04-NOV-15:00 | 18.30 | 13.47 |
December | 0.114484E+09 | 4637.36 | 21-DEC-12:55 | 0.60 | 0.13 | 0.165500E+10 | 1854.44 | 09-DEC-16:00 | -7.2 | -7.2 |
Annual Sum or Average | 0.415385E+11 | 0.227070E+11 | ||||||||
Minimum of Months | 3272722.53 | 689.79 | 0.60 | -2.0 | 0.150876E+10 | 1854.44 | -8.3 | -9.5 | ||
Maximum of Months | 0.994462E+10 | 26849.98 | 23.90 | 18.46 | 0.228024E+10 | 2451.40 | 24.40 | 20.99 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.620850E+10 | 62055.63 | 12-JAN-07:05 | -8.5 | -10.0 | 0.695901E+10 | 7812.78 | 17-JAN-15:39 | 7.43 | 6.34 |
February | 0.586010E+10 | 62701.69 | 25-FEB-07:05 | -8.8 | -9.6 | 0.635451E+10 | 7812.78 | 06-FEB-15:09 | -13.3 | -13.6 |
March | 0.150414E+11 | 66129.29 | 04-MAR-07:05 | -10.4 | -11.2 | 0.750814E+10 | 10327.19 | 16-MAR-14:00 | 19.40 | 15.85 |
April | 0.196495E+11 | 53034.60 | 17-APR-06:05 | -4.2 | -5.2 | 0.733951E+10 | 10327.15 | 08-APR-14:09 | 20.40 | 13.65 |
May | 0.256168E+11 | 93430.32 | 24-MAY-06:03 | 18.03 | 15.61 | 0.890232E+10 | 10327.04 | 20-MAY-11:20 | 16.47 | 9.78 |
June | 0.365985E+11 | 165286.18 | 13-JUN-06:03 | 8.80 | 7.95 | 0.923630E+10 | 10327.49 | 10-JUN-13:09 | 21.10 | 13.36 |
July | 0.418926E+11 | 146934.98 | 06-JUL-06:03 | 13.07 | 10.51 | 0.921605E+10 | 10327.52 | 15-JUL-10:00 | 22.20 | 20.99 |
August | 0.404518E+11 | 158950.28 | 03-AUG-06:03 | 11.57 | 9.85 | 0.960462E+10 | 10327.05 | 26-AUG-15:30 | 23.90 | 20.64 |
September | 0.310156E+11 | 148022.85 | 23-SEP-06:03 | 12.88 | 11.58 | 0.897460E+10 | 10327.30 | 18-SEP-14:00 | 17.80 | 13.19 |
October | 0.235091E+11 | 38700.50 | 24-OCT-06:03 | 1.70 | 0.40 | 0.778773E+10 | 10327.00 | 12-OCT-14:00 | 18.30 | 15.22 |
November | 0.157361E+11 | 50887.25 | 24-NOV-07:05 | -3.2 | -3.9 | 0.683096E+10 | 10199.18 | 04-NOV-15:00 | 18.30 | 13.47 |
December | 0.780829E+10 | 61593.83 | 07-DEC-07:05 | -8.3 | -8.6 | 0.697245E+10 | 7812.77 | 30-DEC-11:09 | 0.00 | -1.7 |
Annual Sum or Average | 0.269388E+12 | 0.956862E+11 | ||||||||
Minimum of Months | 0.586010E+10 | 38700.50 | -10.4 | -11.2 | 0.635451E+10 | 7812.77 | -13.3 | -13.6 | ||
Maximum of Months | 0.418926E+11 | 165286.18 | 18.03 | 15.61 | 0.960462E+10 | 10327.52 | 23.90 | 20.99 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122362E+10 | 5945.55 | 24-JAN-09:43 | -10.8 | -12.2 | 0.656302E+09 | 758.51 | 11-JAN-15:00 | 11.70 | 10.13 |
February | 0.116207E+10 | 6023.03 | 21-FEB-10:23 | -11.1 | -12.3 | 0.601352E+09 | 841.28 | 22-FEB-15:50 | 10.60 | 4.98 |
March | 0.290463E+10 | 11917.82 | 15-MAR-20:21 | 20.00 | 14.13 | 0.733686E+09 | 973.09 | 16-MAR-14:09 | 18.98 | 15.27 |
April | 0.284753E+10 | 4207.37 | 08-APR-13:50 | 20.68 | 13.71 | 0.743915E+09 | 973.13 | 08-APR-14:09 | 20.40 | 13.65 |
May | 0.393163E+10 | 18646.45 | 23-MAY-21:11 | 20.60 | 13.33 | 0.864411E+09 | 973.13 | 13-MAY-13:09 | 21.70 | 14.65 |
June | 0.652324E+10 | 16015.02 | 16-JUN-21:11 | 20.40 | 15.98 | 0.871922E+09 | 973.16 | 10-JUN-13:09 | 21.10 | 13.36 |
July | 0.853043E+10 | 14702.63 | 08-JUL-00:11 | 19.40 | 14.69 | 0.868208E+09 | 973.27 | 15-JUL-10:50 | 22.77 | 20.99 |
August | 0.882200E+10 | 13864.44 | 30-AUG-00:11 | 20.00 | 17.78 | 0.905255E+09 | 973.18 | 15-AUG-14:00 | 23.30 | 20.62 |
September | 0.701582E+10 | 15152.21 | 09-SEP-00:11 | 20.40 | 16.89 | 0.852398E+09 | 973.15 | 18-SEP-14:09 | 17.80 | 12.77 |
October | 0.429442E+10 | 14074.13 | 11-OCT-21:23 | 15.60 | 10.69 | 0.810951E+09 | 973.15 | 12-OCT-14:00 | 18.30 | 15.22 |
November | 0.283194E+10 | 4549.21 | 01-NOV-12:00 | 11.10 | 6.26 | 0.695743E+09 | 973.10 | 04-NOV-11:20 | 15.37 | 12.57 |
December | 0.127334E+10 | 4873.82 | 25-DEC-15:13 | -5.4 | -6.1 | 0.660792E+09 | 900.23 | 16-DEC-13:00 | 5.60 | 2.83 |
Annual Sum or Average | 0.513607E+11 | 0.926493E+10 | ||||||||
Minimum of Months | 0.116207E+10 | 4207.37 | -11.1 | -12.3 | 0.601352E+09 | 758.51 | 5.60 | 2.83 | ||
Maximum of Months | 0.882200E+10 | 18646.45 | 20.68 | 17.78 | 0.905255E+09 | 973.27 | 23.30 | 20.99 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172167E+09 | 3971.13 | 27-JAN-12:23 | -3.0 | -4.3 | 0.655919E+09 | 736.18 | 03-JAN-15:30 | -6.1 | -7.4 |
February | 0.214627E+09 | 4370.53 | 04-FEB-14:03 | -5.1 | -6.3 | 0.598968E+09 | 742.20 | 22-FEB-15:39 | 10.60 | 4.97 |
March | 0.105123E+10 | 4401.99 | 04-MAR-16:42 | -4.9 | -6.5 | 0.710473E+09 | 973.10 | 16-MAR-14:09 | 18.98 | 15.27 |
April | 0.113314E+10 | 2673.09 | 04-APR-16:35 | 3.17 | 2.66 | 0.699791E+09 | 973.12 | 08-APR-14:09 | 20.40 | 13.65 |
May | 0.175179E+10 | 3022.79 | 23-MAY-14:50 | 23.90 | 13.32 | 0.825115E+09 | 973.11 | 31-MAY-14:09 | 21.70 | 14.16 |
June | 0.361094E+10 | 13654.45 | 30-JUN-20:19 | 19.43 | 11.14 | 0.867473E+09 | 973.13 | 02-JUN-14:09 | 24.40 | 18.95 |
July | 0.534956E+10 | 12076.00 | 04-JUL-20:18 | 24.03 | 17.08 | 0.867965E+09 | 973.13 | 28-JUL-14:30 | 22.80 | 21.19 |
August | 0.555148E+10 | 12524.92 | 02-AUG-21:00 | 18.30 | 12.86 | 0.904492E+09 | 973.12 | 21-AUG-14:09 | 19.60 | 14.44 |
September | 0.419653E+10 | 11989.93 | 22-SEP-22:50 | 14.60 | 11.65 | 0.844823E+09 | 973.14 | 06-SEP-14:50 | 16.70 | 13.56 |
October | 0.229014E+10 | 7327.37 | 11-OCT-20:33 | 15.77 | 10.71 | 0.760058E+09 | 973.11 | 10-OCT-14:09 | 17.30 | 13.64 |
November | 0.101338E+10 | 3107.98 | 22-NOV-11:23 | 1.40 | -0.8 | 0.663913E+09 | 973.09 | 04-NOV-15:39 | 18.30 | 13.56 |
December | 0.192550E+09 | 2933.72 | 02-DEC-11:43 | 2.30 | 1.24 | 0.657387E+09 | 789.95 | 16-DEC-13:00 | 5.60 | 2.83 |
Annual Sum or Average | 0.265275E+11 | 0.905638E+10 | ||||||||
Minimum of Months | 0.172167E+09 | 2673.09 | -5.1 | -6.5 | 0.598968E+09 | 736.18 | -6.1 | -7.4 | ||
Maximum of Months | 0.555148E+10 | 13654.45 | 24.03 | 17.08 | 0.904492E+09 | 973.14 | 24.40 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.3 | -4.6 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.8 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.8 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.71 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.71 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.03 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.03 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 16.82 | 13.49 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.49 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.27 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.06 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.06 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -4.9 | -6.8 | 0.00 | 0.00 | -4.9 | -6.8 | ||
Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108107E+11 | 48678.29 | 10-JAN-05:41 | -13.3 |
February | 0.105642E+11 | 49157.90 | 06-FEB-05:31 | -14.3 |
March | 0.593959E+10 | 47941.87 | 02-MAR-05:42 | 1.10 |
April | 0.229817E+10 | 46663.55 | 16-APR-06:12 | -3.5 |
May | 0.210850E+09 | 46165.82 | 01-MAY-04:01 | 3.53 |
June | 40629321.05 | 865.09 | 19-JUN-05:07 | 16.70 |
July | 11619975.48 | 1207.15 | 21-JUL-05:05 | 25.60 |
August | 13559413.30 | 969.71 | 06-AUG-07:04 | 20.28 |
September | 56094345.89 | 914.86 | 16-SEP-05:10 | 21.20 |
October | 0.739323E+09 | 46627.93 | 30-OCT-04:01 | -0.5 |
November | 0.249261E+10 | 46863.61 | 25-NOV-05:42 | -1.7 |
December | 0.916353E+10 | 49190.06 | 26-DEC-05:41 | -12.2 |
Annual Sum or Average | 0.423408E+11 | |||
Minimum of Months | 11619975.48 | 865.09 | -14.3 | |
Maximum of Months | 0.108107E+11 | 49190.06 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.784906E+10 | 233867.21 | 30-JAN-06:01 | -10.1 |
February | 0.750377E+10 | 235158.57 | 07-FEB-05:01 | -15.7 |
March | 0.316658E+10 | 233091.20 | 06-MAR-06:01 | -11.1 |
April | 0.995534E+09 | 164945.40 | 17-APR-06:03 | -4.2 |
May | 0.472933E+09 | 10822.26 | 08-MAY-06:13 | 4.47 |
June | 0.445440E+09 | 7071.48 | 18-JUN-08:20 | 24.60 |
July | 0.394984E+09 | 9477.22 | 21-JUL-06:08 | 25.68 |
August | 0.436874E+09 | 4464.32 | 20-AUG-07:12 | 15.97 |
September | 0.451257E+09 | 4488.03 | 10-SEP-07:12 | 11.10 |
October | 0.586855E+09 | 84179.46 | 30-OCT-06:03 | -0.4 |
November | 0.127453E+10 | 164463.01 | 24-NOV-07:03 | -3.2 |
December | 0.623653E+10 | 233933.29 | 11-DEC-06:01 | -18.5 |
Annual Sum or Average | 0.298143E+11 | |||
Minimum of Months | 0.394984E+09 | 4464.32 | -18.5 | |
Maximum of Months | 0.784906E+10 | 235158.57 | 25.68 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.247301E+10 | 31691.09 | 12-JAN-05:31 | -7.2 |
February | 0.256109E+10 | 31936.83 | 07-FEB-06:01 | -16.2 |
March | 0.111621E+10 | 30819.40 | 06-MAR-05:11 | -11.1 |
April | 0.496150E+09 | 30413.25 | 17-APR-04:01 | -3.4 |
May | 50347313.98 | 20961.37 | 01-MAY-04:01 | 3.53 |
June | 12519929.81 | 661.08 | 27-JUN-05:05 | 21.20 |
July | 4390714.83 | 807.08 | 16-JUL-07:05 | 23.48 |
August | 4575320.36 | 611.95 | 20-AUG-07:02 | 15.78 |
September | 13981780.84 | 627.52 | 22-SEP-05:05 | 13.22 |
October | 0.129353E+09 | 30417.22 | 30-OCT-04:01 | -0.5 |
November | 0.520651E+09 | 30412.54 | 12-NOV-07:01 | 1.02 |
December | 0.213884E+10 | 31661.05 | 26-DEC-06:01 | -12.2 |
Annual Sum or Average | 0.952112E+10 | |||
Minimum of Months | 4390714.83 | 611.95 | -16.2 | |
Maximum of Months | 0.256109E+10 | 31936.83 | 23.48 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.434241E+10 | 25385.06 | 24-JAN-06:01 | -12.1 |
February | 0.427474E+10 | 25542.16 | 06-FEB-05:31 | -14.3 |
March | 0.193908E+10 | 24677.91 | 21-MAR-04:42 | -2.2 |
April | 0.102840E+10 | 24235.10 | 17-APR-04:01 | -3.4 |
May | 0.168746E+09 | 23973.10 | 01-MAY-04:01 | 3.53 |
June | 43853595.78 | 797.79 | 28-JUN-05:07 | 17.20 |
July | 11955100.05 | 979.56 | 02-JUL-07:04 | 19.50 |
August | 9558155.79 | 938.68 | 20-AUG-07:02 | 15.78 |
September | 45276720.62 | 3269.52 | 30-SEP-05:03 | 7.20 |
October | 0.359735E+09 | 24237.61 | 30-OCT-04:01 | -0.5 |
November | 0.106616E+10 | 24233.47 | 12-NOV-07:01 | 1.02 |
December | 0.395900E+10 | 24695.52 | 26-DEC-05:11 | -12.2 |
Annual Sum or Average | 0.172489E+11 | |||
Minimum of Months | 9558155.79 | 797.79 | -14.3 | |
Maximum of Months | 0.434241E+10 | 25542.16 | 19.50 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162092E+11 | 35336.77 | 31-JAN-18:00 | -12.2 |
February | 0.153955E+11 | 38683.25 | 06-FEB-18:00 | -14.4 |
March | 0.915480E+10 | 30175.45 | 06-MAR-18:00 | -8.3 |
April | 0.283203E+10 | 22742.32 | 16-APR-11:10 | -3.1 |
May | 9823667.00 | 1969.99 | 08-MAY-07:10 | 5.87 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.156538E+10 | 20559.23 | 29-OCT-16:21 | 6.95 |
November | 0.535620E+10 | 20452.75 | 19-NOV-15:51 | 7.20 |
December | 0.155471E+11 | 36294.77 | 10-DEC-18:00 | -12.8 |
Annual Sum or Average | 0.660700E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.4 | |
Maximum of Months | 0.162092E+11 | 38683.25 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.149153E+10 | 1249.73 | 02-JAN-09:09 | 0.419292E+10 | 2751.42 | 02-JAN-09:09 |
February | 0.135698E+10 | 1249.73 | 01-FEB-09:09 | 0.380401E+10 | 2751.42 | 01-FEB-09:09 |
March | 0.154631E+10 | 1249.73 | 01-MAR-09:09 | 0.429860E+10 | 2751.42 | 01-MAR-09:09 |
April | 0.146057E+10 | 1249.73 | 01-APR-09:09 | 0.408483E+10 | 2751.42 | 01-APR-09:09 |
May | 0.151892E+10 | 1249.73 | 01-MAY-08:09 | 0.424576E+10 | 2751.42 | 01-MAY-08:09 |
June | 0.149233E+10 | 1249.73 | 01-JUN-08:09 | 0.415135E+10 | 2751.42 | 01-JUN-08:09 |
July | 0.148716E+10 | 1249.73 | 01-JUL-09:09 | 0.417924E+10 | 2751.42 | 01-JUL-09:09 |
August | 0.154631E+10 | 1249.73 | 01-AUG-08:09 | 0.429860E+10 | 2751.42 | 01-AUG-08:09 |
September | 0.146057E+10 | 1249.73 | 01-SEP-08:09 | 0.408483E+10 | 2751.42 | 01-SEP-08:09 |
October | 0.149153E+10 | 1249.73 | 02-OCT-08:09 | 0.419292E+10 | 2751.42 | 02-OCT-08:09 |
November | 0.144192E+10 | 1249.73 | 01-NOV-08:09 | 0.405935E+10 | 2751.42 | 01-NOV-08:09 |
December | 0.148716E+10 | 1249.73 | 01-DEC-09:09 | 0.417924E+10 | 2751.42 | 01-DEC-09:09 |
Annual Sum or Average | 0.177813E+11 | 0.497716E+11 | ||||
Minimum of Months | 0.135698E+10 | 1249.73 | 0.380401E+10 | 2751.42 | ||
Maximum of Months | 0.154631E+10 | 1249.73 | 0.429860E+10 | 2751.42 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.168934E+11 | 16279.94 | 02-JAN-16:49 | 0.707031E+10 | 4639.58 | 02-JAN-09:09 |
February | 0.143037E+11 | 16279.94 | 01-FEB-17:30 | 0.641452E+10 | 4639.58 | 01-FEB-09:09 |
March | 0.160351E+11 | 16279.94 | 01-MAR-17:00 | 0.724851E+10 | 4639.58 | 01-MAR-09:09 |
April | 0.137822E+11 | 15094.55 | 25-APR-16:00 | 0.688804E+10 | 4639.58 | 01-APR-09:09 |
May | 0.141977E+11 | 14962.09 | 11-MAY-16:00 | 0.715941E+10 | 4639.58 | 01-MAY-08:09 |
June | 0.136918E+11 | 14610.42 | 14-JUN-16:00 | 0.700021E+10 | 4639.58 | 01-JUN-08:09 |
July | 0.135959E+11 | 14669.51 | 08-JUL-16:00 | 0.704724E+10 | 4639.58 | 01-JUL-09:09 |
August | 0.141544E+11 | 15157.35 | 28-AUG-16:00 | 0.724851E+10 | 4639.58 | 01-AUG-08:09 |
September | 0.146003E+11 | 15710.62 | 29-SEP-16:00 | 0.688804E+10 | 4639.58 | 01-SEP-08:09 |
October | 0.159268E+11 | 16279.94 | 28-OCT-16:00 | 0.707031E+10 | 4639.58 | 02-OCT-08:09 |
November | 0.158743E+11 | 16279.94 | 01-NOV-16:00 | 0.684509E+10 | 4639.58 | 01-NOV-08:09 |
December | 0.169470E+11 | 16279.94 | 01-DEC-16:40 | 0.704724E+10 | 4639.58 | 01-DEC-09:09 |
Annual Sum or Average | 0.180003E+12 | 0.839274E+11 | ||||
Minimum of Months | 0.135959E+11 | 14610.42 | 0.641452E+10 | 4639.58 | ||
Maximum of Months | 0.169470E+11 | 16279.94 | 0.724851E+10 | 4639.58 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.174880E+10 | 1534.02 | 02-JAN-09:09 | 0.443872E+10 | 2912.71 | 02-JAN-09:09 |
February | 0.159209E+10 | 1534.02 | 01-FEB-09:09 | 0.402701E+10 | 2912.71 | 01-FEB-09:09 |
March | 0.181792E+10 | 1534.02 | 01-MAR-09:09 | 0.455059E+10 | 2912.71 | 01-MAR-09:09 |
April | 0.171453E+10 | 1534.02 | 01-APR-09:09 | 0.432429E+10 | 2912.71 | 01-APR-09:09 |
May | 0.178336E+10 | 1534.02 | 01-MAY-08:09 | 0.449465E+10 | 2912.71 | 01-MAY-08:09 |
June | 0.175416E+10 | 1534.02 | 01-JUN-08:09 | 0.439471E+10 | 2912.71 | 01-JUN-08:09 |
July | 0.174372E+10 | 1534.02 | 01-JUL-09:09 | 0.442423E+10 | 2912.71 | 01-JUL-09:09 |
August | 0.181792E+10 | 1534.02 | 01-AUG-08:09 | 0.455059E+10 | 2912.71 | 01-AUG-08:09 |
September | 0.171453E+10 | 1534.02 | 01-SEP-08:09 | 0.432429E+10 | 2912.71 | 01-SEP-08:09 |
October | 0.174880E+10 | 1534.02 | 02-OCT-08:09 | 0.443872E+10 | 2912.71 | 02-OCT-08:09 |
November | 0.169012E+10 | 1534.02 | 01-NOV-08:09 | 0.429732E+10 | 2912.71 | 01-NOV-08:09 |
December | 0.174372E+10 | 1534.02 | 01-DEC-09:09 | 0.442423E+10 | 2912.71 | 01-DEC-09:09 |
Annual Sum or Average | 0.208697E+11 | 0.526893E+11 | ||||
Minimum of Months | 0.159209E+10 | 1534.02 | 0.402701E+10 | 2912.71 | ||
Maximum of Months | 0.181792E+10 | 1534.02 | 0.455059E+10 | 2912.71 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.169457E+10 | 1485.24 | 02-JAN-09:09 | 0.666220E+09 | 437.18 | 02-JAN-09:09 |
February | 0.154270E+10 | 1485.24 | 01-FEB-09:09 | 0.604426E+09 | 437.18 | 01-FEB-09:09 |
March | 0.176147E+10 | 1485.24 | 01-MAR-09:09 | 0.683011E+09 | 437.18 | 01-MAR-09:09 |
April | 0.166132E+10 | 1485.24 | 01-APR-09:09 | 0.649045E+09 | 437.18 | 01-APR-09:09 |
May | 0.172802E+10 | 1485.24 | 01-MAY-08:09 | 0.674616E+09 | 437.18 | 01-MAY-08:09 |
June | 0.169970E+10 | 1485.24 | 01-JUN-08:09 | 0.659615E+09 | 437.18 | 01-JUN-08:09 |
July | 0.168964E+10 | 1485.24 | 01-JUL-09:09 | 0.664046E+09 | 437.18 | 01-JUL-09:09 |
August | 0.176147E+10 | 1485.24 | 01-AUG-08:09 | 0.683011E+09 | 437.18 | 01-AUG-08:09 |
September | 0.166132E+10 | 1485.24 | 01-SEP-08:09 | 0.649045E+09 | 437.18 | 01-SEP-08:09 |
October | 0.169457E+10 | 1485.24 | 02-OCT-08:09 | 0.666220E+09 | 437.18 | 02-OCT-08:09 |
November | 0.163772E+10 | 1485.24 | 01-NOV-08:09 | 0.644998E+09 | 437.18 | 01-NOV-08:09 |
December | 0.168964E+10 | 1485.24 | 01-DEC-09:09 | 0.664046E+09 | 437.18 | 01-DEC-09:09 |
Annual Sum or Average | 0.202221E+11 | 0.790830E+10 | ||||
Minimum of Months | 0.154270E+10 | 1485.24 | 0.604426E+09 | 437.18 | ||
Maximum of Months | 0.176147E+10 | 1485.24 | 0.683011E+09 | 437.18 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 6919213.84 | 2.58 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 6249612.50 | 2.58 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 6919213.84 | 2.58 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 6696013.39 | 2.58 | 01-APR-00:10 | 0.00 | 0.00 |
May | 6919213.84 | 2.58 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 6696013.39 | 2.58 | 01-JUN-00:10 | 0.00 | 0.00 |
July | 6919213.84 | 2.58 | 01-JUL-00:10 | 0.00 | 0.00 |
August | 6919213.84 | 2.58 | 01-AUG-00:10 | 0.00 | 0.00 |
September | 6696013.39 | 2.58 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 6919213.84 | 2.58 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 6696013.39 | 2.58 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 6919213.84 | 2.58 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 81468162.94 | ||||
Minimum of Months | 6249612.50 | 2.58 | 0.00 | 0.00 | |
Maximum of Months | 6919213.84 | 2.58 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.149153E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400374E+10 |
February | 0.479114E+10 | 0.135698E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423505E+10 |
March | 0.548013E+10 | 0.154631E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1223272.67 | 0.255074E+10 |
April | 0.518069E+10 | 0.146057E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196844E+10 |
May | 0.536353E+10 | 0.151892E+10 | 0.424576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1151287.61 | 0.111370E+10 |
June | 0.528933E+10 | 0.149233E+10 | 0.415135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30810289.42 | 0.730428E+09 |
July | 0.525489E+10 | 0.148716E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77754103.76 | 0.352357E+09 |
August | 0.548013E+10 | 0.154631E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49815616.19 | 0.458272E+09 |
September | 0.518069E+10 | 0.146057E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4000613.95 | 0.743390E+09 |
October | 0.524694E+10 | 0.149153E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158578E+10 |
November | 0.504819E+10 | 0.144192E+10 | 0.405935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224546E+10 |
December | 0.525489E+10 | 0.148716E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419638E+10 |
Annual Sum or Average | 0.628175E+11 | 0.177813E+11 | 0.497716E+11 | 0.164755E+09 | 0.241837E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.135698E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352357E+09 |
Maximum of Months | 0.548013E+10 | 0.154631E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77754103.76 | 0.423505E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.168934E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345638E+10 |
February | 0.201852E+11 | 0.143037E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365261E+10 |
March | 0.230879E+11 | 0.160351E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 923949.29 | 0.221990E+10 |
April | 0.218263E+11 | 0.137822E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174729E+10 |
May | 0.225967E+11 | 0.141977E+11 | 0.715941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 942585.91 | 0.101422E+10 |
June | 0.222841E+11 | 0.136918E+11 | 0.700021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24646860.92 | 0.660415E+09 |
July | 0.221389E+11 | 0.135959E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54047119.81 | 0.347480E+09 |
August | 0.230879E+11 | 0.141544E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37785726.38 | 0.427503E+09 |
September | 0.218263E+11 | 0.146003E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3096810.40 | 0.656160E+09 |
October | 0.221054E+11 | 0.159268E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138253E+10 |
November | 0.212681E+11 | 0.158743E+11 | 0.684509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195318E+10 |
December | 0.221389E+11 | 0.169470E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362462E+10 |
Annual Sum or Average | 0.264651E+12 | 0.180003E+12 | 0.839274E+11 | 0.121443E+09 | 0.211423E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.135959E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347480E+09 |
Maximum of Months | 0.230879E+11 | 0.169470E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54047119.81 | 0.365261E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.174880E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175919E+10 |
February | 0.190200E+10 | 0.159209E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185686E+10 |
March | 0.217552E+10 | 0.181792E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 489284.47 | 0.115630E+10 |
April | 0.205665E+10 | 0.171453E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908743E+09 |
May | 0.212923E+10 | 0.178336E+10 | 0.449465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 510451.06 | 0.524247E+09 |
June | 0.209978E+10 | 0.175416E+10 | 0.439471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13365598.45 | 0.321581E+09 |
July | 0.208610E+10 | 0.174372E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33842943.37 | 0.149197E+09 |
August | 0.217552E+10 | 0.181792E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21684267.98 | 0.194683E+09 |
September | 0.205665E+10 | 0.171453E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1762581.90 | 0.333298E+09 |
October | 0.208295E+10 | 0.174880E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758403E+09 |
November | 0.200405E+10 | 0.169012E+10 | 0.429732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103241E+10 |
December | 0.208610E+10 | 0.174372E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184054E+10 |
Annual Sum or Average | 0.249375E+11 | 0.208697E+11 | 0.526893E+11 | 71655127.23 | 0.108355E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.159209E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149197E+09 |
Maximum of Months | 0.217552E+10 | 0.181792E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33842943.37 | 0.185686E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.169457E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172940E+10 |
February | 0.190200E+10 | 0.154270E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183243E+10 |
March | 0.217552E+10 | 0.176147E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 489097.27 | 0.112050E+10 |
April | 0.205665E+10 | 0.166132E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864289E+09 |
May | 0.212923E+10 | 0.172802E+10 | 0.674616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 498939.98 | 0.483129E+09 |
June | 0.209978E+10 | 0.169970E+10 | 0.659615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13311027.77 | 0.313297E+09 |
July | 0.208610E+10 | 0.168964E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33778904.34 | 0.152919E+09 |
August | 0.217552E+10 | 0.176147E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21669492.42 | 0.197910E+09 |
September | 0.205665E+10 | 0.166132E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1729351.75 | 0.324223E+09 |
October | 0.208295E+10 | 0.169457E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712378E+09 |
November | 0.200405E+10 | 0.163772E+10 | 0.644998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986317E+09 |
December | 0.208610E+10 | 0.168964E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180563E+10 |
Annual Sum or Average | 0.249375E+11 | 0.202221E+11 | 0.790830E+10 | 71476813.54 | 0.105224E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.154270E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152919E+09 |
Maximum of Months | 0.217552E+10 | 0.176147E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33778904.34 | 0.183243E+10 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166490E+11 |
February | 0.00 | 6249612.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157581E+11 |
March | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166945.64 | 0.100750E+11 |
April | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394488E+10 |
May | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1984561.42 | 0.100922E+10 |
June | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17394491.35 | 0.581770E+09 |
July | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39107546.98 | 0.284112E+09 |
August | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20947495.24 | 0.435090E+09 |
September | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959414E+09 |
October | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301815E+10 |
November | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641825E+10 |
December | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160024E+11 |
Annual Sum or Average | 0.00 | 81468162.94 | 79601040.63 | 0.751353E+11 | |||||
Minimum of Months | 0.00 | 6249612.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284112E+09 |
Maximum of Months | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39107546.98 | 0.166490E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 1249.73 | 02-JAN-09:09 | 2751.42 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 8970.14 | 12-JAN-06:00 |
February | 5888.82 | 01-FEB-15:09 | 1249.73 | 01-FEB-09:09 | 2751.42 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 9295.49 | 13-FEB-06:00 |
March | 5888.82 | 01-MAR-15:09 | 1249.73 | 01-MAR-09:09 | 2751.42 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 72.30 | 15-MAR-14:00 | 5211.97 | 02-MAR-05:10 |
April | 5888.82 | 01-APR-10:09 | 1249.73 | 01-APR-09:09 | 2751.42 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 5051.40 | 16-APR-07:00 |
May | 5888.82 | 01-MAY-14:09 | 1249.73 | 01-MAY-08:09 | 2751.42 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.96 | 14-MAY-15:00 | 2006.65 | 05-MAY-21:00 |
June | 5888.82 | 01-JUN-14:09 | 1249.73 | 01-JUN-08:09 | 2751.42 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 314.14 | 12-JUN-13:00 | 2316.04 | 13-JUN-03:00 |
July | 5888.82 | 01-JUL-10:09 | 1249.73 | 01-JUL-09:09 | 2751.42 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 907.09 | 21-JUL-02:25 | 1623.12 | 06-JUL-02:00 |
August | 5888.82 | 01-AUG-14:09 | 1249.73 | 01-AUG-08:09 | 2751.42 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 393.49 | 13-AUG-18:03 | 1233.08 | 30-AUG-20:10 |
September | 5888.82 | 01-SEP-14:09 | 1249.73 | 01-SEP-08:09 | 2751.42 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 142.20 | 16-SEP-13:00 | 1957.79 | 29-SEP-04:00 |
October | 5888.82 | 02-OCT-14:09 | 1249.73 | 02-OCT-08:09 | 2751.42 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2398.41 | 30-OCT-05:00 |
November | 5888.82 | 01-NOV-14:09 | 1249.73 | 01-NOV-08:09 | 2751.42 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4558.09 | 17-NOV-05:47 |
December | 5888.82 | 01-DEC-15:09 | 1249.73 | 01-DEC-09:09 | 2751.42 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6901.20 | 26-DEC-05:46 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 1249.73 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1233.08 | |||||
Maximum of Months | 5888.82 | 1249.73 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 907.09 | 9295.49 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 16279.94 | 02-JAN-16:49 | 4639.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6620.90 | 12-JAN-01:55 |
February | 24809.68 | 01-FEB-15:09 | 16279.94 | 01-FEB-17:30 | 4639.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6724.28 | 13-FEB-05:51 |
March | 24809.68 | 01-MAR-15:09 | 16279.94 | 01-MAR-17:00 | 4639.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.18 | 15-MAR-14:00 | 4109.81 | 02-MAR-01:00 |
April | 24809.68 | 01-APR-10:09 | 15094.55 | 25-APR-16:00 | 4639.58 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3943.89 | 16-APR-01:53 |
May | 24809.68 | 01-MAY-14:09 | 14962.09 | 11-MAY-16:00 | 4639.58 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 90.02 | 14-MAY-15:00 | 1845.08 | 05-MAY-21:00 |
June | 24809.68 | 01-JUN-14:09 | 14610.42 | 14-JUN-16:00 | 4639.58 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 257.14 | 12-JUN-13:00 | 2094.72 | 13-JUN-03:00 |
July | 24809.68 | 01-JUL-10:09 | 14669.51 | 08-JUL-16:00 | 4639.58 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 451.53 | 21-JUL-02:55 | 1495.64 | 06-JUL-02:00 |
August | 24809.68 | 01-AUG-14:09 | 15157.35 | 28-AUG-16:00 | 4639.58 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.35 | 13-AUG-18:03 | 1041.71 | 30-AUG-20:40 |
September | 24809.68 | 01-SEP-14:09 | 15710.62 | 29-SEP-16:00 | 4639.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.39 | 16-SEP-13:00 | 1822.74 | 29-SEP-04:00 |
October | 24809.68 | 02-OCT-14:09 | 16279.94 | 28-OCT-16:00 | 4639.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2028.53 | 07-OCT-02:00 |
November | 24809.68 | 01-NOV-14:09 | 16279.94 | 01-NOV-16:00 | 4639.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3801.71 | 17-NOV-02:00 |
December | 24809.68 | 01-DEC-15:09 | 16279.94 | 01-DEC-16:40 | 4639.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5389.98 | 28-DEC-21:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 14610.42 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1041.71 | |||||
Maximum of Months | 24809.68 | 16279.94 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 451.53 | 6724.28 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1534.02 | 02-JAN-09:09 | 2912.71 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3887.03 | 12-JAN-06:00 |
February | 2337.76 | 01-FEB-15:09 | 1534.02 | 01-FEB-09:09 | 2912.71 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4028.01 | 13-FEB-05:59 |
March | 2337.76 | 01-MAR-15:09 | 1534.02 | 01-MAR-09:09 | 2912.71 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 15-MAR-14:00 | 2294.69 | 02-MAR-05:04 |
April | 2337.76 | 01-APR-10:09 | 1534.02 | 01-APR-09:09 | 2912.71 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2189.08 | 16-APR-06:53 |
May | 2337.76 | 01-MAY-14:09 | 1534.02 | 01-MAY-08:09 | 2912.71 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.66 | 14-MAY-15:00 | 960.49 | 05-MAY-21:00 |
June | 2337.76 | 01-JUN-14:09 | 1534.02 | 01-JUN-08:09 | 2912.71 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.13 | 12-JUN-13:00 | 1036.92 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 1534.02 | 01-JUL-09:09 | 2912.71 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 397.47 | 21-JUL-02:50 | 735.47 | 06-JUL-02:00 |
August | 2337.76 | 01-AUG-14:09 | 1534.02 | 01-AUG-08:09 | 2912.71 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 174.87 | 13-AUG-18:10 | 547.75 | 30-AUG-20:30 |
September | 2337.76 | 01-SEP-14:09 | 1534.02 | 01-SEP-08:09 | 2912.71 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.64 | 16-SEP-13:00 | 886.11 | 29-SEP-04:00 |
October | 2337.76 | 02-OCT-14:09 | 1534.02 | 02-OCT-08:09 | 2912.71 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1039.30 | 30-OCT-05:00 |
November | 2337.76 | 01-NOV-14:09 | 1534.02 | 01-NOV-08:09 | 2912.71 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1967.67 | 17-NOV-06:00 |
December | 2337.76 | 01-DEC-15:09 | 1534.02 | 01-DEC-09:09 | 2912.71 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3015.83 | 26-DEC-05:24 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1534.02 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.75 | |||||
Maximum of Months | 2337.76 | 1534.02 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 397.47 | 4028.01 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1485.24 | 02-JAN-09:09 | 437.18 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3887.03 | 12-JAN-06:00 |
February | 2337.76 | 01-FEB-15:09 | 1485.24 | 01-FEB-09:09 | 437.18 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3969.71 | 13-FEB-05:51 |
March | 2337.76 | 01-MAR-15:09 | 1485.24 | 01-MAR-09:09 | 437.18 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 15-MAR-14:00 | 2265.80 | 02-MAR-05:05 |
April | 2337.76 | 01-APR-10:09 | 1485.24 | 01-APR-09:09 | 437.18 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2188.92 | 16-APR-07:00 |
May | 2337.76 | 01-MAY-14:09 | 1485.24 | 01-MAY-08:09 | 437.18 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.65 | 14-MAY-15:00 | 886.31 | 05-MAY-21:00 |
June | 2337.76 | 01-JUN-14:09 | 1485.24 | 01-JUN-08:09 | 437.18 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.13 | 12-JUN-13:00 | 1000.41 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 1485.24 | 01-JUL-09:09 | 437.18 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 395.93 | 21-JUL-02:50 | 694.69 | 06-JUL-02:00 |
August | 2337.76 | 01-AUG-14:09 | 1485.24 | 01-AUG-08:09 | 437.18 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.18 | 13-AUG-18:10 | 525.10 | 30-AUG-20:10 |
September | 2337.76 | 01-SEP-14:09 | 1485.24 | 01-SEP-08:09 | 437.18 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.63 | 16-SEP-13:00 | 820.20 | 29-SEP-04:00 |
October | 2337.76 | 02-OCT-14:09 | 1485.24 | 02-OCT-08:09 | 437.18 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1039.30 | 30-OCT-05:00 |
November | 2337.76 | 01-NOV-14:09 | 1485.24 | 01-NOV-08:09 | 437.18 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1973.37 | 17-NOV-05:47 |
December | 2337.76 | 01-DEC-15:09 | 1485.24 | 01-DEC-09:09 | 437.18 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2997.67 | 26-DEC-05:54 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1485.24 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.10 | |||||
Maximum of Months | 2337.76 | 1485.24 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 395.93 | 3969.71 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 35429.18 | 31-JAN-18:00 |
February | 0.00 | 01-FEB-00:10 | 2.58 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 38701.27 | 06-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 2.58 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.88 | 12-MAR-12:53 | 30620.64 | 06-MAR-18:00 |
April | 0.00 | 01-APR-00:10 | 2.58 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 23115.31 | 16-APR-11:10 |
May | 0.00 | 01-MAY-00:10 | 2.58 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.64 | 10-MAY-14:00 | 4802.06 | 24-MAY-11:01 |
June | 0.00 | 01-JUN-00:10 | 2.58 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 872.18 | 12-JUN-11:02 | 6528.76 | 13-JUN-11:01 |
July | 0.00 | 01-JUL-00:10 | 2.58 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 770.94 | 15-JUL-13:55 | 2693.79 | 02-JUL-11:01 |
August | 0.00 | 01-AUG-00:10 | 2.58 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.23 | 13-AUG-11:03 | 3783.62 | 31-AUG-11:01 |
September | 0.00 | 01-SEP-00:10 | 2.58 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 4436.56 | 10-SEP-11:01 |
October | 0.00 | 01-OCT-00:10 | 2.58 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 14664.20 | 24-OCT-11:02 |
November | 0.00 | 01-NOV-00:10 | 2.58 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 18517.22 | 22-NOV-18:00 |
December | 0.00 | 01-DEC-00:10 | 2.58 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 36492.55 | 10-DEC-18:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.79 | ||||
Maximum of Months | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 872.18 | 38701.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3873.78 | 14-JAN-15:25 | 11777.63 | 2499.45 | 5502.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.91 |
February | 689.79 | 18-FEB-15:00 | 5888.82 | 1249.73 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.08 |
March | 4316.32 | 25-MAR-13:05 | 11777.63 | 2499.45 | 5502.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1102.00 |
April | 3934.48 | 10-APR-14:50 | 5888.82 | 1249.73 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.43 |
May | 5100.70 | 27-MAY-16:00 | 5888.82 | 1249.73 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 |
June | 24204.40 | 11-JUN-19:42 | 0.00 | 490.69 | 2722.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.20 |
July | 26543.83 | 03-JUL-20:37 | 0.00 | 490.69 | 3630.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.42 |
August | 26849.98 | 16-AUG-21:35 | 0.00 | 490.69 | 3630.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.52 |
September | 21364.65 | 17-SEP-01:58 | 0.00 | 408.91 | 2269.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.60 |
October | 4049.53 | 23-OCT-17:05 | 7361.02 | 1388.59 | 5502.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.25 |
November | 3876.38 | 11-NOV-16:15 | 5888.82 | 1666.30 | 4891.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.73 |
December | 4637.36 | 21-DEC-12:55 | 10305.43 | 2499.45 | 5502.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.75 |
Annual Sum or Average | |||||||||||
Minimum of Months | 689.79 | 0.00 | 408.91 | 2269.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.60 | |
Maximum of Months | 26849.98 | 11777.63 | 2499.45 | 5502.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1102.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 62055.63 | 12-JAN-07:05 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1498.35 |
February | 62701.69 | 25-FEB-07:05 | 12404.84 | 1378.20 | 6186.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 854.76 |
March | 66129.29 | 04-MAR-07:05 | 12404.84 | 1378.20 | 6186.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.52 |
April | 53034.60 | 17-APR-06:05 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.82 |
May | 93430.32 | 24-MAY-06:03 | 9303.63 | 1033.65 | 6186.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.17 |
June | 165286.18 | 13-JUN-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.15 |
July | 146934.98 | 06-JUL-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.19 |
August | 158950.28 | 03-AUG-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.35 |
September | 148022.85 | 23-SEP-06:03 | 12404.84 | 1378.20 | 6186.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.25 |
October | 38700.50 | 24-OCT-06:03 | 9303.63 | 1033.65 | 6186.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.95 |
November | 50887.25 | 24-NOV-07:05 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.32 |
December | 61593.83 | 07-DEC-07:05 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 852.68 |
Annual Sum or Average | |||||||||||
Minimum of Months | 38700.50 | 9303.63 | 1033.65 | 6186.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.25 | |
Maximum of Months | 165286.18 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1498.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5945.55 | 24-JAN-09:43 | 5844.40 | 6136.09 | 11650.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.04 |
February | 6023.03 | 21-FEB-10:23 | 5844.40 | 6136.09 | 11650.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.24 |
March | 11917.82 | 15-MAR-20:21 | 0.00 | 227.26 | 4483.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 |
April | 4207.37 | 08-APR-13:50 | 2337.76 | 1534.02 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.14 |
May | 18646.45 | 23-MAY-21:11 | 0.00 | 292.19 | 5765.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.60 |
June | 16015.02 | 16-JUN-21:11 | 0.00 | 259.73 | 5124.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.77 |
July | 14702.63 | 08-JUL-00:11 | 0.00 | 227.26 | 3362.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.08 |
August | 13864.44 | 30-AUG-00:11 | 0.00 | 227.26 | 4483.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.21 |
September | 15152.21 | 09-SEP-00:11 | 0.00 | 227.26 | 3362.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.74 |
October | 14074.13 | 11-OCT-21:23 | 0.00 | 97.40 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.76 |
November | 4549.21 | 01-NOV-12:00 | 2045.54 | 1534.02 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.74 |
December | 4873.82 | 25-DEC-15:13 | 4675.52 | 4090.73 | 10356.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.56 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4207.37 | 0.00 | 97.40 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | |
Maximum of Months | 18646.45 | 5844.40 | 6136.09 | 11650.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3971.13 | 27-JAN-12:23 | 6136.63 | 4455.72 | 1311.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.28 |
February | 4370.53 | 04-FEB-14:03 | 7013.29 | 4455.72 | 1311.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.57 |
March | 4401.99 | 04-MAR-16:42 | 9351.05 | 5940.97 | 1748.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.66 |
April | 2673.09 | 04-APR-16:35 | 2922.20 | 2970.48 | 874.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.25 |
May | 3022.79 | 23-MAY-14:50 | 2337.76 | 1485.24 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 0.00 |
June | 13654.45 | 30-JUN-20:19 | 0.00 | 259.73 | 769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.75 |
July | 12076.00 | 04-JUL-20:18 | 0.00 | 194.80 | 432.65 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 | 0.00 |
August | 12524.92 | 02-AUG-21:00 | 0.00 | 227.26 | 673.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.18 |
September | 11989.93 | 22-SEP-22:50 | 0.00 | 227.26 | 673.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.96 |
October | 7327.37 | 11-OCT-20:33 | 0.00 | 129.86 | 384.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.34 |
November | 3107.98 | 22-NOV-11:23 | 6136.63 | 4455.72 | 1311.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.68 |
December | 2933.72 | 02-DEC-11:43 | 7013.29 | 4455.72 | 1311.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2673.09 | 0.00 | 129.86 | 384.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13654.45 | 9351.05 | 5940.97 | 1748.71 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 | 491.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.84 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.78 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.99 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.35 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.21 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.21 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.63 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.11 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.31 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.35 | |
Maximum of Months | 0.00 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.78 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.586441E+11 | 45448.69 | 31-JAN-17:00 | 0.162292E+12 | 206688.33 | 24-JAN-07:10 |
February | 0.520087E+11 | 45793.99 | 06-FEB-17:00 | 0.152808E+12 | 235333.45 | 07-FEB-07:10 |
March | 0.559208E+11 | 47264.96 | 15-MAR-14:00 | 0.928182E+11 | 200649.26 | 07-MAR-07:10 |
April | 0.490497E+11 | 39045.11 | 03-APR-08:09 | 0.401956E+11 | 155981.74 | 17-APR-06:10 |
May | 0.507718E+11 | 49731.92 | 10-MAY-14:00 | 0.997593E+10 | 68805.64 | 01-MAY-06:10 |
June | 0.621981E+11 | 64772.01 | 27-JUN-12:00 | 0.781301E+10 | 5034.23 | 01-JUN-11:30 |
July | 0.760175E+11 | 71905.99 | 15-JUL-13:00 | 0.786846E+10 | 4989.68 | 03-JUL-11:39 |
August | 0.720495E+11 | 64320.58 | 18-AUG-14:00 | 0.789854E+10 | 4966.97 | 31-AUG-11:50 |
September | 0.578639E+11 | 60700.43 | 16-SEP-15:00 | 0.770102E+10 | 18852.42 | 30-SEP-06:49 |
October | 0.526394E+11 | 45400.31 | 11-OCT-14:00 | 0.225976E+11 | 111611.30 | 30-OCT-06:10 |
November | 0.529251E+11 | 44047.71 | 24-NOV-17:00 | 0.563619E+11 | 148053.19 | 24-NOV-07:10 |
December | 0.584457E+11 | 45449.59 | 11-DEC-17:00 | 0.148273E+12 | 227601.45 | 11-DEC-07:10 |
Annual Sum or Average | 0.698534E+12 | 0.716603E+12 | ||||
Minimum of Months | 0.490497E+11 | 39045.11 | 0.770102E+10 | 4966.97 | ||
Maximum of Months | 0.760175E+11 | 71905.99 | 0.162292E+12 | 235333.45 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.218352E+11 | 0.432588E+10 | 0.163682E+11 | 0.00 | 0.161149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188017E+11 | 0.352502E+10 | 0.148500E+11 | 0.00 | 0.148320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211677E+11 | 0.337520E+10 | 0.167807E+11 | 0.00 | 0.141038E+11 | 0.00 | 0.00 | 0.493386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186253E+11 | 0.273337E+10 | 0.159462E+11 | 0.00 | 0.117009E+11 | 0.00 | 0.00 | 43961062.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192349E+11 | 0.238562E+10 | 0.165744E+11 | 0.00 | 0.105579E+11 | 0.00 | 0.00 | 0.201903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186447E+11 | 0.212011E+10 | 0.162059E+11 | 0.00 | 0.103661E+11 | 0.00 | 0.00 | 0.148613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185234E+11 | 0.224533E+10 | 0.163148E+11 | 0.00 | 0.108620E+11 | 0.00 | 0.00 | 0.280721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.192870E+11 | 0.261466E+10 | 0.167807E+11 | 0.00 | 0.109009E+11 | 0.00 | 0.00 | 0.224663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194434E+11 | 0.303678E+10 | 0.159462E+11 | 0.00 | 0.102849E+11 | 0.00 | 0.00 | 0.915262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208686E+11 | 0.368468E+10 | 0.163682E+11 | 0.00 | 0.112666E+11 | 0.00 | 0.00 | 0.451280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206508E+11 | 0.404005E+10 | 0.158468E+11 | 0.00 | 0.123850E+11 | 0.00 | 0.00 | 2423193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218745E+11 | 0.445331E+10 | 0.163148E+11 | 0.00 | 0.158032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238957E+12 | 0.385400E+11 | 0.194297E+12 | 0.149178E+12 | 0.00 | 0.775624E+11 | |||||||
Minimum of Months | 0.185234E+11 | 0.212011E+10 | 0.148500E+11 | 0.00 | 0.102849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.218745E+11 | 0.445331E+10 | 0.167807E+11 | 0.00 | 0.161149E+11 | 0.00 | 0.00 | 0.280721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.153796E+12 | 0.00 | 0.849605E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.145073E+12 | 0.00 | 0.773489E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.842288E+11 | 0.00 | 0.858937E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.320585E+11 | 0.00 | 0.813713E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.175250E+10 | 0.00 | 0.822344E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 640804.23 | 0.00 | 0.781236E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.786846E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.789854E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 50682937.29 | 0.00 | 0.765034E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.145810E+11 | 0.00 | 0.801660E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.484413E+11 | 0.00 | 0.792053E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.139899E+12 | 0.00 | 0.837365E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.619881E+12 | 0.967214E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.765034E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.153796E+12 | 0.00 | 0.858937E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 20551.52 | 02-JAN-16:49 | 3371.20 | 01-JAN-06:10 | 10740.89 | 02-JAN-09:09 | 0.00 | 12021.72 | 29-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 20551.52 | 01-FEB-17:30 | 3371.20 | 01-FEB-06:10 | 10740.89 | 01-FEB-09:09 | 0.00 | 12338.60 | 05-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 20551.52 | 01-MAR-17:00 | 3371.20 | 01-MAR-06:10 | 10740.89 | 01-MAR-09:09 | 0.00 | 11869.25 | 05-MAR-09:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 19366.13 | 25-APR-16:00 | 3371.20 | 01-APR-05:10 | 10740.89 | 01-APR-09:09 | 0.00 | 11082.48 | 16-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 19233.66 | 11-MAY-16:00 | 3371.20 | 01-MAY-05:10 | 10740.89 | 01-MAY-08:09 | 0.00 | 9213.41 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 18882.00 | 14-JUN-16:00 | 3371.20 | 01-JUN-19:49 | 10740.89 | 01-JUN-08:09 | 0.00 | 10418.34 | 18-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 18941.09 | 08-JUL-16:00 | 3371.20 | 01-JUL-19:00 | 10740.89 | 01-JUL-09:09 | 0.00 | 10593.84 | 16-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 19428.92 | 28-AUG-16:00 | 3371.20 | 01-AUG-19:40 | 10740.89 | 01-AUG-08:09 | 0.00 | 10292.63 | 14-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 19982.20 | 29-SEP-16:00 | 3371.20 | 01-SEP-05:10 | 10740.89 | 01-SEP-08:09 | 0.00 | 9230.25 | 14-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 20551.52 | 28-OCT-16:00 | 3371.20 | 01-OCT-05:10 | 10740.89 | 02-OCT-08:09 | 0.00 | 10061.53 | 17-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 20551.52 | 01-NOV-16:00 | 3371.20 | 01-NOV-05:10 | 10740.89 | 01-NOV-08:09 | 0.00 | 10625.16 | 23-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 20551.52 | 01-DEC-16:40 | 3371.20 | 01-DEC-06:10 | 10740.89 | 01-DEC-09:09 | 0.00 | 12349.22 | 10-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 18882.00 | 3371.20 | 10740.89 | 0.00 | 9213.41 | 0.00 | 0.00 | |||||
Maximum of Months | 20551.52 | 3371.20 | 10740.89 | 0.00 | 12349.22 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13593.63 | 15-MAR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3544.63 | 08-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16645.63 | 10-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33819.05 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36012.95 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30633.26 | 10-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26239.93 | 16-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9142.70 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 369.03 | 16-NOV-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36012.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 45448.69 | 31-JAN-17:00 | 20551.52 | 10740.89 | 3371.20 | 0.00 | 10785.08 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 45793.99 | 06-FEB-17:00 | 20551.52 | 10740.89 | 3371.20 | 0.00 | 11130.38 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 47264.96 | 15-MAR-14:00 | 16841.55 | 10740.89 | 0.00 | 0.00 | 6503.07 | 0.00 | 0.00 | 13179.46 | 0.00 |
April | 39045.11 | 03-APR-08:09 | 18743.23 | 10740.89 | 0.00 | 0.00 | 9561.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49731.92 | 10-MAY-14:00 | 15842.34 | 10740.89 | 0.00 | 0.00 | 6503.07 | 0.00 | 0.00 | 16645.63 | 0.00 |
June | 64772.01 | 27-JUN-12:00 | 12411.55 | 10740.89 | 0.00 | 0.00 | 7800.52 | 0.00 | 0.00 | 33819.05 | 0.00 |
July | 71905.99 | 15-JUL-13:00 | 16658.36 | 10740.89 | 0.00 | 0.00 | 8493.80 | 0.00 | 0.00 | 36012.95 | 0.00 |
August | 64320.58 | 18-AUG-14:00 | 16117.40 | 10740.89 | 0.00 | 0.00 | 6956.49 | 0.00 | 0.00 | 30505.80 | 0.00 |
September | 60700.43 | 16-SEP-15:00 | 18500.11 | 10740.89 | 0.00 | 0.00 | 6558.01 | 0.00 | 0.00 | 24901.42 | 0.00 |
October | 45400.31 | 11-OCT-14:00 | 19013.66 | 10740.89 | 0.00 | 0.00 | 6503.07 | 0.00 | 0.00 | 9142.70 | 0.00 |
November | 44047.71 | 24-NOV-17:00 | 20551.52 | 10740.89 | 3371.20 | 0.00 | 9384.10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 45449.59 | 11-DEC-17:00 | 20551.52 | 10740.89 | 3371.20 | 0.00 | 10785.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 39045.11 | 12411.55 | 10740.89 | 0.00 | 0.00 | 6503.07 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71905.99 | 20551.52 | 10740.89 | 3371.20 | 0.00 | 11130.38 | 0.00 | 0.00 | 36012.95 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 202115.17 | 24-JAN-07:10 | 0.00 | 5185.16 | 23-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 233473.45 | 07-FEB-07:10 | 0.00 | 5264.95 | 07-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 198789.26 | 07-MAR-07:10 | 0.00 | 5232.01 | 03-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 151415.82 | 17-APR-06:10 | 0.00 | 5131.17 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 66945.64 | 01-MAY-06:10 | 0.00 | 5088.32 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 356.54 | 14-JUN-06:19 | 0.00 | 5034.23 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4989.68 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4966.97 | 31-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 16398.78 | 30-SEP-06:00 | 0.00 | 4989.64 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 109751.30 | 30-OCT-06:10 | 0.00 | 5035.53 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 146193.19 | 24-NOV-07:10 | 0.00 | 5086.75 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 225741.45 | 11-DEC-07:10 | 0.00 | 5130.08 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4966.97 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 233473.45 | 0.00 | 5264.95 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.33 | 19.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11.33 | 19.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7.50 | 19.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3.50 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.50 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.51 | 0.00 | 0.00 |
October | 0.50 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.67 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10.00 | 19.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.83 | 19.77 | 0.00 | 1.33 | 24.48 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.33 | 20.48 | 0.00 | 0.00 | 0.50 | 24.51 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.67 | 19.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9.50 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4.50 | 20.20 | 0.00 | 0.00 | 0.17 | 24.49 | 0.00 | 0.00 |
April | 2.00 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.50 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 24.51 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 24.49 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 24.50 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 24.50 | 0.00 | 0.00 |
October | 0.33 | 20.48 | 0.00 | 0.00 | 0.83 | 24.51 | 0.00 | 0.00 |
November | 2.17 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.17 | 19.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.33 | 19.81 | 0.00 | 36.67 | 24.50 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.50 | 20.48 | 0.00 | 0.00 | 9.83 | 24.51 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.50 | 19.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13.33 | 18.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6.83 | 20.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3.17 | 20.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.67 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.48 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.47 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.47 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.47 | 0.00 | 0.00 |
October | 0.83 | 20.42 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 0.00 |
November | 3.67 | 20.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11.17 | 19.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.17 | 19.44 | 0.00 | 4.83 | 24.47 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.33 | 20.49 | 0.00 | 0.00 | 1.67 | 24.48 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.50 | 12.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7.67 | 12.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 49.00 | 12.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 122.00 | 13.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 61.00 | 14.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6.83 | 13.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9.67 | 14.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 114.33 | 12.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 80.83 | 12.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.83 | 12.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 469.67 | 12.83 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.00 | 14.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 406.83 | 21.11 | 406.83 | 21.11 |
February | 376.00 | 21.11 | 376.00 | 21.11 | 376.00 | 21.11 |
March | 422.00 | 21.34 | 295.67 | 21.14 | 295.67 | 21.14 |
April | 405.00 | 21.50 | 129.50 | 21.11 | 129.50 | 21.11 |
May | 413.50 | 23.01 | 14.83 | 22.08 | 14.83 | 22.08 |
June | 182.00 | 23.71 | 146.17 | 23.89 | 48.50 | 23.88 |
July | 99.17 | 23.88 | 328.33 | 23.89 | 89.67 | 23.89 |
August | 80.67 | 23.83 | 231.83 | 23.89 | 56.83 | 23.89 |
September | 221.50 | 23.56 | 103.83 | 23.89 | 40.00 | 23.88 |
October | 410.67 | 22.12 | 38.67 | 21.11 | 38.67 | 21.11 |
November | 399.00 | 21.24 | 197.17 | 21.11 | 197.17 | 21.11 |
December | 415.00 | 21.11 | 396.00 | 21.11 | 396.00 | 21.11 |
Annual Sum or Average | 3838.50 | 21.89 | 2664.83 | 21.96 | 2089.67 | 21.43 |
Minimum of Months | 80.67 | 21.11 | 14.83 | 21.11 | 14.83 | 21.11 |
Maximum of Months | 422.00 | 23.88 | 406.83 | 23.89 | 406.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 371.83 | 21.11 | 371.83 | 21.11 |
February | 376.00 | 21.11 | 345.50 | 21.11 | 345.50 | 21.11 |
March | 415.33 | 21.31 | 179.17 | 21.11 | 179.17 | 21.11 |
April | 405.00 | 21.60 | 27.50 | 21.11 | 27.50 | 21.11 |
May | 280.00 | 22.77 | 18.67 | 23.87 | 3.67 | 23.89 |
June | 80.67 | 23.47 | 228.00 | 23.89 | 32.83 | 23.89 |
July | 80.33 | 23.89 | 387.00 | 23.89 | 78.17 | 23.89 |
August | 52.00 | 23.79 | 329.17 | 23.89 | 42.67 | 23.89 |
September | 114.50 | 23.15 | 163.33 | 23.88 | 26.17 | 23.88 |
October | 391.17 | 21.90 | 10.83 | 21.84 | 8.00 | 21.11 |
November | 399.00 | 21.26 | 71.83 | 21.11 | 71.83 | 21.11 |
December | 415.00 | 21.11 | 306.17 | 21.11 | 306.17 | 21.11 |
Annual Sum or Average | 3423.00 | 21.67 | 2439.00 | 22.40 | 1493.50 | 21.45 |
Minimum of Months | 52.00 | 21.11 | 10.83 | 21.11 | 3.67 | 21.11 |
Maximum of Months | 415.33 | 23.89 | 387.00 | 23.89 | 371.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.12 | 355.17 | 21.11 | 355.17 | 21.11 |
February | 376.00 | 21.13 | 315.83 | 21.11 | 315.83 | 21.11 |
March | 394.33 | 21.46 | 156.33 | 21.28 | 146.67 | 21.11 |
April | 390.17 | 22.14 | 54.83 | 21.11 | 54.83 | 21.11 |
May | 259.67 | 23.17 | 27.83 | 23.72 | 3.50 | 22.57 |
June | 80.50 | 23.56 | 219.33 | 23.89 | 24.83 | 23.89 |
July | 53.00 | 23.86 | 381.33 | 23.89 | 47.17 | 23.89 |
August | 37.17 | 23.79 | 357.67 | 23.89 | 27.00 | 23.89 |
September | 70.83 | 23.31 | 241.00 | 23.89 | 13.33 | 23.89 |
October | 285.50 | 22.47 | 51.00 | 23.32 | 10.50 | 21.11 |
November | 386.17 | 21.77 | 70.00 | 21.11 | 70.00 | 21.11 |
December | 415.00 | 21.14 | 327.33 | 21.11 | 327.33 | 21.11 |
Annual Sum or Average | 3162.33 | 21.85 | 2557.67 | 22.50 | 1396.17 | 21.34 |
Minimum of Months | 37.17 | 21.12 | 27.83 | 21.11 | 3.50 | 21.11 |
Maximum of Months | 415.00 | 23.86 | 381.33 | 23.89 | 355.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 390.17 | 21.11 | 390.17 | 21.11 |
February | 376.00 | 21.11 | 356.00 | 21.11 | 356.00 | 21.11 |
March | 404.33 | 21.27 | 207.33 | 21.13 | 206.00 | 21.11 |
April | 402.83 | 21.68 | 89.17 | 21.11 | 89.17 | 21.11 |
May | 337.67 | 22.70 | 14.67 | 21.90 | 10.50 | 21.11 |
June | 105.50 | 23.33 | 181.83 | 23.89 | 17.00 | 23.86 |
July | 21.83 | 23.65 | 354.50 | 23.89 | 9.67 | 23.89 |
August | 29.00 | 23.47 | 311.67 | 23.89 | 4.67 | 23.89 |
September | 90.83 | 22.88 | 196.00 | 23.89 | 0.00 | 0.00 |
October | 335.67 | 21.94 | 37.83 | 22.29 | 21.83 | 21.11 |
November | 399.00 | 21.48 | 139.50 | 21.11 | 139.50 | 21.11 |
December | 415.00 | 21.11 | 376.00 | 21.11 | 376.00 | 21.11 |
Annual Sum or Average | 3331.67 | 21.64 | 2654.67 | 22.23 | 1620.50 | 21.16 |
Minimum of Months | 21.83 | 21.11 | 14.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 415.00 | 23.65 | 390.17 | 23.89 | 390.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10985 | 21.93170 | -0.7193 | 16.03249 |
February | 376.00000 | 21.10991 | 21.86819 | -0.7224 | 16.11346 |
March | 422.00000 | 21.33618 | 31.13842 | -0.5514 | 12.78776 |
April | 405.00000 | 21.50294 | 36.74629 | -0.4274 | 9.54410 |
May | 418.00000 | 23.00434 | 41.06807 | -1.0383 | 29.47128 |
June | 408.00000 | 23.80527 | 48.27384 | -0.5864 | 12.78421 |
July | 415.00000 | 23.88607 | 56.21287 | -0.4480 | 9.29642 |
August | 422.00000 | 23.87835 | 52.08891 | -0.4912 | 10.18682 |
September | 405.00000 | 23.70477 | 49.17584 | -0.6451 | 14.57010 |
October | 414.00000 | 22.12607 | 41.91134 | -0.2028 | 7.53993 |
November | 399.00000 | 21.23889 | 35.06573 | -0.5047 | 10.73278 |
December | 415.00000 | 21.11066 | 25.66338 | -0.6757 | 14.79542 |
Annual Sum or Average | 4913.00000 | 22.32912 | 38.55198 | -0.5839 | 13.65655 |
Minimum of Months | 376.00000 | 21.10985 | 21.86819 | -1.0383 | 7.53993 |
Maximum of Months | 422.00000 | 23.88607 | 56.21287 | -0.2028 | 29.47128 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09615 | 19.37334 | -0.6363 | 13.64674 |
February | 376.00000 | 21.09614 | 19.29018 | -0.6352 | 13.60282 |
March | 422.00000 | 21.34067 | 28.21895 | -0.4489 | 10.48137 |
April | 405.00000 | 21.59795 | 33.95843 | -0.3054 | 7.78886 |
May | 418.00000 | 23.13690 | 38.22991 | -0.8543 | 22.27826 |
June | 408.00000 | 23.81361 | 46.78356 | -0.4768 | 10.25206 |
July | 415.00000 | 23.90331 | 54.81108 | -0.3600 | 7.82422 |
August | 422.00000 | 23.88539 | 50.81027 | -0.4111 | 8.69026 |
September | 405.00000 | 23.67831 | 47.97173 | -0.5559 | 12.27454 |
October | 414.00000 | 22.01250 | 39.37785 | -0.1503 | 7.01310 |
November | 399.00000 | 21.25522 | 32.65819 | -0.4248 | 9.23815 |
December | 415.00000 | 21.09949 | 23.11121 | -0.5964 | 12.65350 |
Annual Sum or Average | 4913.00000 | 22.33779 | 36.34120 | -0.4873 | 11.30946 |
Minimum of Months | 376.00000 | 21.09614 | 19.29018 | -0.8543 | 7.01310 |
Maximum of Months | 422.00000 | 23.90331 | 54.81108 | -0.1503 | 22.27826 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.11508 | 18.69530 | -0.6462 | 14.01565 |
February | 376.00000 | 21.13491 | 18.63186 | -0.6417 | 13.95988 |
March | 422.00000 | 21.61842 | 26.99096 | -0.3810 | 9.97882 |
April | 405.00000 | 22.19635 | 31.89118 | -0.2035 | 7.75124 |
May | 418.00000 | 23.43145 | 36.26455 | -0.7981 | 20.28538 |
June | 408.00000 | 23.82370 | 45.03548 | -0.4804 | 10.44166 |
July | 415.00000 | 23.88496 | 52.83156 | -0.3515 | 7.72952 |
August | 422.00000 | 23.87882 | 48.75692 | -0.3764 | 8.16917 |
September | 405.00000 | 23.78575 | 45.13739 | -0.4727 | 10.46321 |
October | 414.00000 | 22.90407 | 36.16976 | 0.05950 | 7.14185 |
November | 399.00000 | 21.84230 | 30.82429 | -0.2922 | 8.54364 |
December | 415.00000 | 21.14394 | 22.46125 | -0.6079 | 13.09745 |
Annual Sum or Average | 4913.00000 | 22.57475 | 34.59401 | -0.4319 | 10.95767 |
Minimum of Months | 376.00000 | 21.11508 | 18.63186 | -0.7981 | 7.14185 |
Maximum of Months | 422.00000 | 23.88496 | 52.83156 | 0.05950 | 20.28538 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10960 | 18.69058 | -0.6900 | 15.21597 |
February | 376.00000 | 21.10982 | 18.64374 | -0.6882 | 15.18677 |
March | 422.00000 | 21.37627 | 27.52631 | -0.4740 | 11.21496 |
April | 405.00000 | 21.69497 | 33.17014 | -0.3432 | 8.90699 |
May | 418.00000 | 22.91811 | 38.82879 | -0.9963 | 28.28844 |
June | 408.00000 | 23.74236 | 46.72006 | -0.5492 | 12.26708 |
July | 415.00000 | 23.87601 | 53.33830 | -0.3962 | 8.47911 |
August | 422.00000 | 23.85949 | 49.21144 | -0.4255 | 9.07112 |
September | 405.00000 | 23.66027 | 46.25143 | -0.5547 | 12.70080 |
October | 414.00000 | 22.30884 | 37.93871 | -0.0958 | 7.47891 |
November | 399.00000 | 21.47637 | 31.59354 | -0.4105 | 9.68678 |
December | 415.00000 | 21.11366 | 22.49644 | -0.6572 | 14.30839 |
Annual Sum or Average | 4913.00000 | 22.36461 | 35.49218 | -0.5229 | 12.73543 |
Minimum of Months | 376.00000 | 21.10960 | 18.64374 | -0.9963 | 7.47891 |
Maximum of Months | 422.00000 | 23.87601 | 53.33830 | -0.0958 | 28.28844 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 96257828.42 | 26946009.57 | 11.33 | 76048243.85 | 20209584.58 | 0.00 | 0.36 | 15-MAR-14:50 | 0.00 | 01-MAR-00:10 | 4831.31 | 15-MAR-15:00 | 3879.81 | 15-MAR-14:30 | 966.07 | 15-MAR-15:00 | 1332.04 | 15-MAR-14:40 | 0.00 | 01-MAR-00:10 |
April | 90.31 | 25.67 | 0.33 | 74.17 | 16.14 | 0.00 | 0.00 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 0.13 | 08-APR-13:30 | 0.11 | 08-APR-13:30 | 0.02 | 08-APR-13:30 | 0.04 | 08-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 0.486183E+09 | 0.131930E+09 | 96.39 | 0.427207E+09 | 58975862.98 | 0.00 | 0.46 | 10-MAY-15:00 | 0.00 | 01-MAY-00:10 | 6476.13 | 10-MAY-15:00 | 5090.91 | 23-MAY-15:00 | 1782.98 | 10-MAY-15:00 | 1731.63 | 10-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.674338E+10 | 0.166744E+10 | 317.71 | 0.476885E+10 | 0.197453E+10 | 0.00 | 1.00 | 02-JUN-23:23 | 0.00 | 01-JUN-00:10 | 35348.73 | 18-JUN-06:00 | 29030.28 | 30-JUN-21:00 | 18916.76 | 27-JUN-20:43 | 7466.48 | 17-JUN-23:23 | 0.00 | 01-JUN-00:10 |
July | 0.155331E+11 | 0.371904E+10 | 424.64 | 0.101672E+11 | 0.536583E+10 | 0.00 | 1.00 | 01-JUL-22:01 | 0.00 | 01-JUL-00:05 | 35562.97 | 16-JUL-02:10 | 25476.74 | 06-JUL-21:00 | 20102.19 | 16-JUL-06:17 | 7482.51 | 17-JUL-03:02 | 0.00 | 01-JUL-00:05 |
August | 0.117852E+11 | 0.288618E+10 | 398.92 | 0.850581E+10 | 0.327936E+10 | 0.00 | 1.00 | 01-AUG-00:05 | 0.00 | 01-AUG-00:10 | 35761.97 | 14-AUG-02:53 | 27016.29 | 03-AUG-20:44 | 19958.62 | 14-AUG-04:40 | 7500.12 | 13-AUG-23:30 | 0.00 | 01-AUG-00:05 |
September | 0.379435E+10 | 0.939104E+09 | 245.08 | 0.254677E+10 | 0.124758E+10 | 0.00 | 1.00 | 13-SEP-21:32 | 0.00 | 01-SEP-00:10 | 34953.02 | 15-SEP-20:53 | 23218.74 | 17-SEP-01:58 | 19381.87 | 15-SEP-20:53 | 7354.48 | 16-SEP-23:42 | 0.00 | 01-SEP-00:10 |
October | 18469963.01 | 5178755.18 | 21.27 | 15918575.53 | 2551387.48 | 0.00 | 0.16 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2009.47 | 11-OCT-15:00 | 1719.16 | 11-OCT-15:00 | 290.31 | 11-OCT-15:00 | 557.10 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.384569E+11 | 0.937583E+10 | 1515.68 | 0.265078E+11 | 0.119490E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.155331E+11 | 0.371904E+10 | 424.64 | 0.101672E+11 | 0.536583E+10 | 0.00 | 1.00 | 0.00 | 35761.97 | 29030.28 | 20102.19 | 7500.12 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.107901E+10 | 0.328447E+09 | 18.44 | 0.851491E+09 | 0.227518E+09 | 0.00 | 0.48 | 15-MAR-14:10 | 0.00 | 01-MAR-00:10 | 30632.86 | 15-MAR-14:10 | 26076.55 | 15-MAR-14:10 | 6688.84 | 14-MAR-14:10 | 9219.21 | 15-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 46475384.91 | 14377073.01 | 6.58 | 38309149.18 | 8166235.73 | 0.00 | 0.13 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 7043.76 | 08-APR-13:30 | 5846.54 | 08-APR-13:30 | 1242.98 | 08-APR-14:00 | 2166.21 | 08-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 0.492052E+10 | 0.143836E+10 | 115.54 | 0.421349E+10 | 0.707028E+09 | 0.00 | 0.62 | 10-MAY-15:00 | 0.00 | 01-MAY-00:10 | 113447.51 | 24-MAY-06:03 | 74052.30 | 24-MAY-06:03 | 39395.21 | 24-MAY-06:03 | 27002.81 | 24-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.386428E+11 | 0.105388E+11 | 330.81 | 0.268858E+11 | 0.117570E+11 | 0.00 | 1.00 | 02-JUN-06:02 | 0.00 | 01-JUN-00:10 | 166276.75 | 18-JUN-08:62 | 126345.01 | 11-JUN-08:62 | 84369.65 | 08-JUN-06:03 | 39174.94 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.730255E+11 | 0.193342E+11 | 394.10 | 0.469522E+11 | 0.260733E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 167308.45 | 16-JUL-08:62 | 104705.82 | 15-JUL-06:02 | 90592.32 | 29-JUL-06:04 | 39605.93 | 21-JUL-06:02 | 0.00 | 01-JUL-00:05 |
August | 0.558815E+11 | 0.152297E+11 | 374.82 | 0.398913E+11 | 0.159902E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:05 | 166089.85 | 14-AUG-06:02 | 112819.15 | 06-AUG-08:62 | 89123.58 | 14-AUG-06:04 | 38590.69 | 14-AUG-06:02 | 0.00 | 01-AUG-00:05 |
September | 0.213771E+11 | 0.589421E+10 | 254.86 | 0.143045E+11 | 0.707265E+10 | 0.00 | 1.00 | 09-SEP-06:03 | 0.00 | 01-SEP-00:10 | 161298.94 | 16-SEP-06:02 | 95070.85 | 23-SEP-06:03 | 81041.33 | 14-SEP-06:04 | 37813.79 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.397023E+09 | 0.121223E+09 | 26.87 | 0.325464E+09 | 71558086.87 | 0.00 | 0.31 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 18260.59 | 11-OCT-15:00 | 15090.33 | 11-OCT-15:00 | 3170.26 | 11-OCT-15:00 | 5446.13 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.195370E+12 | 0.528992E+11 | 1522.03 | 0.133463E+12 | 0.619075E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.730255E+11 | 0.193342E+11 | 394.10 | 0.469522E+11 | 0.260733E+11 | 0.00 | 1.00 | 0.00 | 167308.45 | 126345.01 | 90592.32 | 39605.93 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.347378E+09 | 87053909.47 | 30.01 | 0.285975E+09 | 61403194.50 | 0.00 | 1.00 | 15-MAR-20:21 | 0.00 | 01-MAR-00:10 | 19239.46 | 15-MAR-20:21 | 15390.06 | 15-MAR-20:21 | 3849.40 | 15-MAR-20:21 | 4096.02 | 15-MAR-20:21 | 0.00 | 01-MAR-00:10 |
April | 51287509.09 | 13546916.98 | 39.93 | 45688882.94 | 5598626.15 | 0.00 | 0.41 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 3247.48 | 08-APR-13:30 | 2831.97 | 08-APR-13:30 | 475.52 | 08-APR-14:00 | 827.81 | 08-APR-13:40 | 0.00 | 01-APR-00:10 |
May | 0.100096E+10 | 0.254233E+09 | 195.28 | 0.886684E+09 | 0.114274E+09 | 0.00 | 1.00 | 16-MAY-20:25 | 0.00 | 01-MAY-00:10 | 19127.99 | 23-MAY-24:00 | 18010.75 | 23-MAY-23:31 | 2068.47 | 24-MAY-01:01 | 4217.20 | 23-MAY-24:00 | 0.00 | 01-MAY-00:10 |
June | 0.662991E+10 | 0.157210E+10 | 362.97 | 0.479543E+10 | 0.183449E+10 | 0.00 | 1.00 | 01-JUN-20:12 | 0.00 | 01-JUN-00:10 | 21557.60 | 27-JUN-20:13 | 18485.60 | 30-JUN-20:11 | 11428.66 | 27-JUN-21:00 | 4561.25 | 17-JUN-22:10 | 0.00 | 01-JUN-00:10 |
July | 0.131078E+11 | 0.302986E+10 | 453.13 | 0.881706E+10 | 0.429072E+10 | 0.00 | 1.00 | 01-JUL-21:20 | 0.00 | 01-JUL-00:05 | 21759.74 | 16-JUL-07:00 | 16367.10 | 06-JUL-20:11 | 12119.64 | 16-JUL-06:13 | 4589.47 | 16-JUL-01:12 | 0.00 | 01-JUL-00:05 |
August | 0.109901E+11 | 0.256499E+10 | 429.19 | 0.810865E+10 | 0.288146E+10 | 0.00 | 1.00 | 01-AUG-00:40 | 0.00 | 01-AUG-00:05 | 21760.20 | 14-AUG-03:30 | 17747.48 | 03-AUG-20:10 | 11998.17 | 14-AUG-04:17 | 4588.82 | 14-AUG-20:43 | 0.00 | 01-AUG-00:05 |
September | 0.564191E+10 | 0.131096E+10 | 326.42 | 0.404184E+10 | 0.160007E+10 | 0.00 | 1.00 | 03-SEP-18:15 | 0.00 | 01-SEP-00:10 | 21347.88 | 15-SEP-20:17 | 16230.52 | 07-SEP-20:12 | 11573.60 | 15-SEP-23:20 | 4504.83 | 16-SEP-23:12 | 0.00 | 01-SEP-00:10 |
October | 0.663436E+09 | 0.164209E+09 | 107.79 | 0.539305E+09 | 0.124131E+09 | 0.00 | 1.00 | 11-OCT-20:15 | 0.00 | 01-OCT-00:10 | 18485.60 | 11-OCT-20:15 | 15473.42 | 11-OCT-21:23 | 4101.63 | 12-OCT-21:00 | 3913.67 | 11-OCT-20:15 | 0.00 | 01-OCT-00:10 |
November | 2014078.98 | 560921.52 | 19.27 | 1665826.59 | 348252.39 | 0.00 | 0.09 | 16-NOV-12:40 | 0.00 | 01-NOV-00:10 | 643.85 | 16-NOV-12:40 | 539.31 | 16-NOV-12:40 | 104.54 | 16-NOV-12:40 | 178.37 | 16-NOV-12:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.384348E+11 | 0.899751E+10 | 1963.99 | 0.275223E+11 | 0.109125E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.131078E+11 | 0.302986E+10 | 453.13 | 0.881706E+10 | 0.429072E+10 | 0.00 | 1.00 | 0.00 | 21760.20 | 18485.60 | 12119.64 | 4589.47 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.224531E+09 | 50939095.11 | 21.83 | 0.184566E+09 | 39965111.68 | 0.00 | 0.73 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 | 5532.35 | 15-MAR-13:50 | 4968.49 | 15-MAR-13:50 | 1131.48 | 14-MAR-13:00 | 1208.58 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 68242476.75 | 16037047.27 | 23.67 | 63649222.76 | 4593253.99 | 0.00 | 0.36 | 08-APR-13:40 | 0.00 | 01-APR-00:10 | 2457.91 | 08-APR-13:50 | 2158.10 | 08-APR-13:40 | 310.85 | 08-APR-14:00 | 554.71 | 08-APR-13:50 | 0.00 | 01-APR-00:10 |
May | 0.849044E+09 | 0.194498E+09 | 138.60 | 0.751990E+09 | 97053569.65 | 0.00 | 0.64 | 10-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4865.47 | 10-MAY-15:00 | 3836.95 | 23-MAY-14:50 | 1065.86 | 10-MAY-15:00 | 1082.41 | 10-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.505194E+10 | 0.108304E+10 | 374.89 | 0.385632E+10 | 0.119562E+10 | 0.00 | 1.00 | 18-JUN-20:12 | 0.00 | 01-JUN-00:10 | 15983.39 | 18-JUN-20:12 | 14874.24 | 30-JUN-20:19 | 6313.27 | 18-JUN-06:03 | 3120.45 | 18-JUN-20:12 | 0.00 | 01-JUN-00:10 |
July | 0.945506E+10 | 0.198896E+10 | 502.44 | 0.684222E+10 | 0.261284E+10 | 0.00 | 1.00 | 04-JUL-20:18 | 0.00 | 01-JUL-00:05 | 16335.78 | 22-JUL-23:02 | 13330.03 | 04-JUL-20:18 | 5654.88 | 22-JUL-23:02 | 3166.17 | 22-JUL-23:02 | 0.00 | 01-JUL-00:05 |
August | 0.841045E+10 | 0.178543E+10 | 497.02 | 0.663738E+10 | 0.177308E+10 | 0.00 | 1.00 | 01-AUG-02:11 | 0.00 | 01-AUG-00:25 | 16328.43 | 27-AUG-00:58 | 13742.21 | 02-AUG-21:00 | 5598.74 | 27-AUG-00:58 | 3165.32 | 27-AUG-00:58 | 0.00 | 01-AUG-00:05 |
September | 0.478915E+10 | 0.100835E+10 | 351.97 | 0.381836E+10 | 0.970792E+09 | 0.00 | 1.00 | 08-SEP-20:18 | 0.00 | 01-SEP-00:10 | 16166.15 | 16-SEP-04:22 | 13220.76 | 22-SEP-22:50 | 4929.03 | 16-SEP-04:22 | 3212.65 | 16-SEP-23:18 | 0.00 | 01-SEP-00:10 |
October | 0.731009E+09 | 0.160669E+09 | 91.15 | 0.630646E+09 | 0.100363E+09 | 0.00 | 0.84 | 11-OCT-14:30 | 0.00 | 01-OCT-00:10 | 9108.63 | 11-OCT-20:33 | 8611.75 | 11-OCT-20:33 | 1251.78 | 12-OCT-14:10 | 1711.81 | 11-OCT-20:33 | 0.00 | 01-OCT-00:10 |
November | 7684810.83 | 1862271.66 | 6.07 | 6348063.17 | 1336747.66 | 0.00 | 0.14 | 16-NOV-12:30 | 0.00 | 01-NOV-00:10 | 882.19 | 16-NOV-12:30 | 817.87 | 16-NOV-12:30 | 167.15 | 04-NOV-14:50 | 210.95 | 16-NOV-12:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.295871E+11 | 0.628979E+10 | 2007.62 | 0.227915E+11 | 0.679564E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.945506E+10 | 0.198896E+10 | 502.44 | 0.684222E+10 | 0.261284E+10 | 0.00 | 1.00 | 0.00 | 16335.78 | 14874.24 | 6313.27 | 3212.65 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.55 | 5.87 | 15.68 | 1.81 | 71.83 | 0.00 | 0.00 | 744.00 |
February | 34.81 | 9.77 | 25.03 | 11.76 | 66.77 | 0.00 | 0.00 | 672.00 |
March | 54.27 | 27.70 | 26.57 | 38.88 | 49.98 | 0.00 | 0.00 | 744.00 |
April | 73.53 | 39.51 | 34.02 | 65.86 | 36.71 | 0.00 | 0.00 | 720.00 |
May | 94.32 | 58.60 | 35.72 | 97.18 | 27.54 | 0.00 | 0.00 | 744.00 |
June | 109.36 | 69.20 | 40.16 | 121.50 | 20.54 | 0.00 | 0.00 | 720.00 |
July | 101.31 | 62.08 | 39.23 | 117.55 | 15.16 | 0.00 | 0.00 | 744.00 |
August | 85.56 | 47.76 | 37.80 | 95.57 | 18.58 | 0.00 | 0.00 | 744.00 |
September | 63.58 | 34.76 | 28.82 | 62.97 | 27.82 | 0.00 | 0.00 | 720.00 |
October | 38.86 | 16.50 | 22.36 | 27.51 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 22.19 | 6.50 | 15.69 | 8.13 | 47.38 | 0.00 | 0.00 | 720.00 |
December | 19.13 | 3.69 | 15.44 | 1.48 | 68.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.00 | 31.95 | 28.05 | 54.42 | 40.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.13 | 3.69 | 15.44 | 1.48 | 15.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 109.36 | 69.20 | 40.16 | 121.50 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 905.16 | 528.30 | 376.86 | 703.79 | 1059.20 | 0.00 | 0.00 | 744.00 |
February | 1033.90 | 498.66 | 535.24 | 745.78 | 1030.99 | 0.00 | 0.00 | 672.00 |
March | 1262.16 | 709.42 | 552.74 | 1060.23 | 770.91 | 0.00 | 0.00 | 744.00 |
April | 1044.75 | 417.43 | 627.32 | 775.74 | 584.34 | 0.00 | 0.00 | 720.00 |
May | 914.18 | 265.41 | 648.77 | 655.80 | 406.75 | 0.00 | 0.00 | 744.00 |
June | 888.26 | 188.09 | 700.17 | 743.63 | 268.35 | 0.00 | 0.00 | 720.00 |
July | 906.79 | 219.90 | 686.89 | 872.77 | 175.09 | 0.00 | 0.00 | 744.00 |
August | 1018.03 | 329.96 | 688.07 | 992.45 | 236.56 | 0.00 | 0.00 | 744.00 |
September | 1184.03 | 576.80 | 607.23 | 1172.12 | 393.81 | 0.00 | 0.00 | 720.00 |
October | 1133.19 | 647.48 | 485.71 | 1088.46 | 592.64 | 0.00 | 0.00 | 744.00 |
November | 811.29 | 458.00 | 353.28 | 723.88 | 727.21 | 0.00 | 0.00 | 720.00 |
December | 756.82 | 391.59 | 365.23 | 556.69 | 1035.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 987.91 | 435.69 | 552.22 | 841.59 | 604.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 756.82 | 188.09 | 353.28 | 556.69 | 175.09 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1262.16 | 709.42 | 700.17 | 1172.12 | 1059.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 905.16 | 528.30 | 376.86 | 701.86 | 1050.92 | 0.00 | 0.00 | 744.00 |
February | 1033.90 | 498.66 | 535.24 | 743.41 | 1023.01 | 0.00 | 0.00 | 672.00 |
March | 1262.16 | 709.42 | 552.74 | 1061.98 | 754.57 | 0.00 | 0.00 | 744.00 |
April | 1044.75 | 417.43 | 627.32 | 781.65 | 562.11 | 0.00 | 0.00 | 720.00 |
May | 914.18 | 265.41 | 648.77 | 663.26 | 382.70 | 0.00 | 0.00 | 744.00 |
June | 888.26 | 188.09 | 700.17 | 740.55 | 262.32 | 0.00 | 0.00 | 720.00 |
July | 906.79 | 219.90 | 686.89 | 865.69 | 175.34 | 0.00 | 0.00 | 744.00 |
August | 1018.03 | 329.96 | 688.07 | 985.58 | 237.03 | 0.00 | 0.00 | 744.00 |
September | 1184.03 | 576.80 | 607.23 | 1168.87 | 387.45 | 0.00 | 0.00 | 720.00 |
October | 1133.19 | 647.48 | 485.71 | 1094.68 | 568.14 | 0.00 | 0.00 | 744.00 |
November | 811.29 | 458.00 | 353.28 | 727.28 | 706.33 | 0.00 | 0.00 | 720.00 |
December | 756.82 | 391.59 | 365.23 | 555.46 | 1026.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 987.91 | 435.69 | 552.22 | 841.51 | 592.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 756.82 | 188.09 | 353.28 | 555.46 | 175.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1262.16 | 709.42 | 700.17 | 1168.87 | 1050.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 186.25 | 108.70 | 77.54 | 149.85 | 195.00 | 0.00 | 0.00 | 744.00 |
February | 212.74 | 102.61 | 110.13 | 159.98 | 192.13 | 0.00 | 0.00 | 672.00 |
March | 259.71 | 145.97 | 113.73 | 228.40 | 137.45 | 0.00 | 0.00 | 744.00 |
April | 214.97 | 85.89 | 129.08 | 176.79 | 98.67 | 0.00 | 0.00 | 720.00 |
May | 188.11 | 54.61 | 133.49 | 150.33 | 67.76 | 0.00 | 0.00 | 744.00 |
June | 182.77 | 38.70 | 144.07 | 156.06 | 50.16 | 0.00 | 0.00 | 720.00 |
July | 186.59 | 45.25 | 141.34 | 171.70 | 37.30 | 0.00 | 0.00 | 744.00 |
August | 209.47 | 67.89 | 141.58 | 198.05 | 49.52 | 0.00 | 0.00 | 744.00 |
September | 243.63 | 118.68 | 124.95 | 245.78 | 72.40 | 0.00 | 0.00 | 720.00 |
October | 233.17 | 133.23 | 99.94 | 238.66 | 98.91 | 0.00 | 0.00 | 744.00 |
November | 166.93 | 94.24 | 72.69 | 158.41 | 122.48 | 0.00 | 0.00 | 720.00 |
December | 155.73 | 80.57 | 75.15 | 118.93 | 189.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 203.28 | 89.65 | 113.63 | 179.52 | 108.83 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 155.73 | 38.70 | 72.69 | 118.93 | 37.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 259.71 | 145.97 | 144.07 | 245.78 | 195.00 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57718597.03 | 15732063.67 | 41986533.37 | 4856119.62 | 0.192399E+09 |
February | 84201090.29 | 23646496.98 | 60554593.32 | 28446321.97 | 0.161531E+09 |
March | 0.145350E+09 | 74184683.90 | 71165257.52 | 0.104128E+09 | 0.133877E+09 |
April | 0.190593E+09 | 0.102401E+09 | 88192287.96 | 0.170701E+09 | 95163395.01 |
May | 0.252633E+09 | 0.156967E+09 | 95665906.81 | 0.260292E+09 | 73751266.22 |
June | 0.283461E+09 | 0.179367E+09 | 0.104094E+09 | 0.314918E+09 | 53232908.43 |
July | 0.271340E+09 | 0.166269E+09 | 0.105070E+09 | 0.314848E+09 | 40594308.02 |
August | 0.229163E+09 | 0.127912E+09 | 0.101252E+09 | 0.255966E+09 | 49768631.24 |
September | 0.164800E+09 | 90089774.48 | 74709791.07 | 0.163221E+09 | 72112928.48 |
October | 0.104085E+09 | 44198182.05 | 59886372.11 | 73682200.72 | 0.103188E+09 |
November | 57512027.49 | 16845545.58 | 40666481.91 | 21076325.16 | 0.122806E+09 |
December | 51226613.87 | 9877890.32 | 41348723.55 | 3970704.29 | 0.184417E+09 |
Annual Sum or Average | 0.189208E+10 | 0.100749E+10 | 0.884592E+09 | 0.171610E+10 | 0.128284E+10 |
Minimum of Months | 51226613.87 | 9877890.32 | 40666481.91 | 3970704.29 | 40594308.02 |
Maximum of Months | 0.283461E+09 | 0.179367E+09 | 0.105070E+09 | 0.314918E+09 | 0.192399E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242438E+10 | 0.141499E+10 | 0.100938E+10 | 0.188503E+10 | 0.283696E+10 |
February | 0.250121E+10 | 0.120637E+10 | 0.129484E+10 | 0.180420E+10 | 0.249416E+10 |
March | 0.338056E+10 | 0.190011E+10 | 0.148045E+10 | 0.283971E+10 | 0.206480E+10 |
April | 0.270798E+10 | 0.108197E+10 | 0.162601E+10 | 0.201073E+10 | 0.151460E+10 |
May | 0.244853E+10 | 0.710869E+09 | 0.173767E+10 | 0.175650E+10 | 0.108943E+10 |
June | 0.230238E+10 | 0.487537E+09 | 0.181484E+10 | 0.192748E+10 | 0.695574E+09 |
July | 0.242876E+10 | 0.588989E+09 | 0.183977E+10 | 0.233762E+10 | 0.468966E+09 |
August | 0.272670E+10 | 0.883766E+09 | 0.184293E+10 | 0.265818E+10 | 0.633607E+09 |
September | 0.306901E+10 | 0.149506E+10 | 0.157395E+10 | 0.303813E+10 | 0.102076E+10 |
October | 0.303514E+10 | 0.173420E+10 | 0.130094E+10 | 0.291532E+10 | 0.158732E+10 |
November | 0.210285E+10 | 0.118714E+10 | 0.915707E+09 | 0.187631E+10 | 0.188494E+10 |
December | 0.202707E+10 | 0.104883E+10 | 0.978244E+09 | 0.149104E+10 | 0.277476E+10 |
Annual Sum or Average | 0.311546E+11 | 0.137398E+11 | 0.174147E+11 | 0.265403E+11 | 0.190659E+11 |
Minimum of Months | 0.202707E+10 | 0.487537E+09 | 0.915707E+09 | 0.149104E+10 | 0.468966E+09 |
Maximum of Months | 0.338056E+10 | 0.190011E+10 | 0.184293E+10 | 0.303813E+10 | 0.283696E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242438E+10 | 0.141499E+10 | 0.100938E+10 | 0.187986E+10 | 0.281479E+10 |
February | 0.250121E+10 | 0.120637E+10 | 0.129484E+10 | 0.179845E+10 | 0.247485E+10 |
March | 0.338056E+10 | 0.190011E+10 | 0.148045E+10 | 0.284440E+10 | 0.202103E+10 |
April | 0.270798E+10 | 0.108197E+10 | 0.162601E+10 | 0.202604E+10 | 0.145699E+10 |
May | 0.244853E+10 | 0.710869E+09 | 0.173767E+10 | 0.177649E+10 | 0.102501E+10 |
June | 0.230238E+10 | 0.487537E+09 | 0.181484E+10 | 0.191950E+10 | 0.679925E+09 |
July | 0.242876E+10 | 0.588989E+09 | 0.183977E+10 | 0.231867E+10 | 0.469622E+09 |
August | 0.272670E+10 | 0.883766E+09 | 0.184293E+10 | 0.263977E+10 | 0.634873E+09 |
September | 0.306901E+10 | 0.149506E+10 | 0.157395E+10 | 0.302971E+10 | 0.100428E+10 |
October | 0.303514E+10 | 0.173420E+10 | 0.130094E+10 | 0.293199E+10 | 0.152171E+10 |
November | 0.210285E+10 | 0.118714E+10 | 0.915707E+09 | 0.188512E+10 | 0.183081E+10 |
December | 0.202707E+10 | 0.104883E+10 | 0.978244E+09 | 0.148773E+10 | 0.275028E+10 |
Annual Sum or Average | 0.311546E+11 | 0.137398E+11 | 0.174147E+11 | 0.265377E+11 | 0.186842E+11 |
Minimum of Months | 0.202707E+10 | 0.487537E+09 | 0.915707E+09 | 0.148773E+10 | 0.469622E+09 |
Maximum of Months | 0.338056E+10 | 0.190011E+10 | 0.184293E+10 | 0.302971E+10 | 0.281479E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.498851E+09 | 0.291155E+09 | 0.207696E+09 | 0.401345E+09 | 0.522280E+09 |
February | 0.514661E+09 | 0.248228E+09 | 0.266433E+09 | 0.387020E+09 | 0.464805E+09 |
March | 0.695600E+09 | 0.390976E+09 | 0.304623E+09 | 0.611737E+09 | 0.368153E+09 |
April | 0.557207E+09 | 0.222631E+09 | 0.334576E+09 | 0.458236E+09 | 0.255744E+09 |
May | 0.503822E+09 | 0.146272E+09 | 0.357550E+09 | 0.402640E+09 | 0.181485E+09 |
June | 0.473748E+09 | 0.100318E+09 | 0.373430E+09 | 0.404516E+09 | 0.130005E+09 |
July | 0.499753E+09 | 0.121193E+09 | 0.378560E+09 | 0.459882E+09 | 99907794.50 |
August | 0.561058E+09 | 0.181848E+09 | 0.379210E+09 | 0.530465E+09 | 0.132642E+09 |
September | 0.631493E+09 | 0.307630E+09 | 0.323862E+09 | 0.637058E+09 | 0.187663E+09 |
October | 0.624524E+09 | 0.356837E+09 | 0.267686E+09 | 0.639222E+09 | 0.264921E+09 |
November | 0.432692E+09 | 0.244272E+09 | 0.188420E+09 | 0.410595E+09 | 0.317478E+09 |
December | 0.417099E+09 | 0.215812E+09 | 0.201288E+09 | 0.318548E+09 | 0.507074E+09 |
Annual Sum or Average | 0.641051E+10 | 0.282717E+10 | 0.358333E+10 | 0.566126E+10 | 0.343216E+10 |
Minimum of Months | 0.417099E+09 | 0.100318E+09 | 0.188420E+09 | 0.318548E+09 | 99907794.50 |
Maximum of Months | 0.695600E+09 | 0.390976E+09 | 0.379210E+09 | 0.639222E+09 | 0.522280E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 29.01 | 1149.34 | 344.79 | 93.98 | 250.82 | 0.00 | 0.00 |
February | 188.14 | 1068.33 | 556.89 | 156.39 | 400.49 | 0.00 | 0.00 |
March | 622.03 | 799.74 | 868.28 | 443.16 | 425.12 | 0.00 | 0.00 |
April | 1053.71 | 587.43 | 1176.50 | 632.11 | 544.40 | 0.00 | 0.00 |
May | 1554.91 | 440.57 | 1509.16 | 937.68 | 571.48 | 0.00 | 0.00 |
June | 1943.94 | 328.60 | 1749.76 | 1107.21 | 642.55 | 0.00 | 0.00 |
July | 1880.81 | 242.50 | 1620.91 | 993.24 | 627.66 | 0.00 | 0.00 |
August | 1529.07 | 297.30 | 1368.96 | 764.11 | 604.85 | 0.00 | 0.00 |
September | 1007.53 | 445.14 | 1017.28 | 556.11 | 461.17 | 0.00 | 0.00 |
October | 440.16 | 616.42 | 621.77 | 264.03 | 357.74 | 0.00 | 0.00 |
November | 130.10 | 758.06 | 355.01 | 103.98 | 251.03 | 0.00 | 0.00 |
December | 23.72 | 1101.65 | 306.01 | 59.01 | 247.01 | 0.00 | 0.00 |
Annual Sum or Average | 870.68 | 650.86 | 959.96 | 511.16 | 448.80 | 0.00 | 0.00 |
Minimum of Months | 23.72 | 242.50 | 306.01 | 59.01 | 247.01 | 0.00 | 0.00 |
Maximum of Months | 1943.94 | 1149.34 | 1749.76 | 1107.21 | 642.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 703.79 | 1059.20 | 905.16 | 528.30 | 376.86 | 0.00 | 0.00 |
February | 745.78 | 1030.99 | 1033.90 | 498.66 | 535.24 | 0.00 | 0.00 |
March | 1060.23 | 770.91 | 1262.16 | 709.42 | 552.74 | 0.00 | 0.00 |
April | 775.74 | 584.34 | 1044.75 | 417.43 | 627.32 | 0.00 | 0.00 |
May | 655.80 | 406.75 | 914.18 | 265.41 | 648.77 | 0.00 | 0.00 |
June | 743.63 | 268.35 | 888.26 | 188.09 | 700.17 | 0.00 | 0.00 |
July | 872.77 | 175.09 | 906.79 | 219.90 | 686.89 | 0.00 | 0.00 |
August | 992.45 | 236.56 | 1018.03 | 329.96 | 688.07 | 0.00 | 0.00 |
September | 1172.12 | 393.81 | 1184.03 | 576.80 | 607.23 | 0.00 | 0.00 |
October | 1088.46 | 592.64 | 1133.19 | 647.48 | 485.71 | 0.00 | 0.00 |
November | 723.88 | 727.21 | 811.29 | 458.00 | 353.28 | 0.00 | 0.00 |
December | 556.69 | 1035.98 | 756.82 | 391.59 | 365.23 | 0.00 | 0.00 |
Annual Sum or Average | 841.59 | 604.58 | 987.91 | 435.69 | 552.22 | 0.00 | 0.00 |
Minimum of Months | 556.69 | 175.09 | 756.82 | 188.09 | 353.28 | 0.00 | 0.00 |
Maximum of Months | 1172.12 | 1059.20 | 1262.16 | 709.42 | 700.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 701.86 | 1050.92 | 905.16 | 528.30 | 376.86 | 0.00 | 0.00 |
February | 743.41 | 1023.01 | 1033.90 | 498.66 | 535.24 | 0.00 | 0.00 |
March | 1061.98 | 754.57 | 1262.16 | 709.42 | 552.74 | 0.00 | 0.00 |
April | 781.65 | 562.11 | 1044.75 | 417.43 | 627.32 | 0.00 | 0.00 |
May | 663.26 | 382.70 | 914.18 | 265.41 | 648.77 | 0.00 | 0.00 |
June | 740.55 | 262.32 | 888.26 | 188.09 | 700.17 | 0.00 | 0.00 |
July | 865.69 | 175.34 | 906.79 | 219.90 | 686.89 | 0.00 | 0.00 |
August | 985.58 | 237.03 | 1018.03 | 329.96 | 688.07 | 0.00 | 0.00 |
September | 1168.87 | 387.45 | 1184.03 | 576.80 | 607.23 | 0.00 | 0.00 |
October | 1094.68 | 568.14 | 1133.19 | 647.48 | 485.71 | 0.00 | 0.00 |
November | 727.28 | 706.33 | 811.29 | 458.00 | 353.28 | 0.00 | 0.00 |
December | 555.46 | 1026.84 | 756.82 | 391.59 | 365.23 | 0.00 | 0.00 |
Annual Sum or Average | 841.51 | 592.47 | 987.91 | 435.69 | 552.22 | 0.00 | 0.00 |
Minimum of Months | 555.46 | 175.34 | 756.82 | 188.09 | 353.28 | 0.00 | 0.00 |
Maximum of Months | 1168.87 | 1050.92 | 1262.16 | 709.42 | 700.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 149.85 | 195.00 | 186.25 | 108.70 | 77.54 | 0.00 | 0.00 |
February | 159.98 | 192.13 | 212.74 | 102.61 | 110.13 | 0.00 | 0.00 |
March | 228.40 | 137.45 | 259.71 | 145.97 | 113.73 | 0.00 | 0.00 |
April | 176.79 | 98.67 | 214.97 | 85.89 | 129.08 | 0.00 | 0.00 |
May | 150.33 | 67.76 | 188.11 | 54.61 | 133.49 | 0.00 | 0.00 |
June | 156.06 | 50.16 | 182.77 | 38.70 | 144.07 | 0.00 | 0.00 |
July | 171.70 | 37.30 | 186.59 | 45.25 | 141.34 | 0.00 | 0.00 |
August | 198.05 | 49.52 | 209.47 | 67.89 | 141.58 | 0.00 | 0.00 |
September | 245.78 | 72.40 | 243.63 | 118.68 | 124.95 | 0.00 | 0.00 |
October | 238.66 | 98.91 | 233.17 | 133.23 | 99.94 | 0.00 | 0.00 |
November | 158.41 | 122.48 | 166.93 | 94.24 | 72.69 | 0.00 | 0.00 |
December | 118.93 | 189.32 | 155.73 | 80.57 | 75.15 | 0.00 | 0.00 |
Annual Sum or Average | 179.52 | 108.83 | 203.28 | 89.65 | 113.63 | 0.00 | 0.00 |
Minimum of Months | 118.93 | 37.30 | 155.73 | 38.70 | 72.69 | 0.00 | 0.00 |
Maximum of Months | 245.78 | 195.00 | 259.71 | 145.97 | 144.07 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 77697913.85 | 0.307839E+10 | 0.923498E+09 | 0.251713E+09 | 0.671785E+09 | 0.00 | 0.00 |
February | 0.455141E+09 | 0.258450E+10 | 0.134722E+10 | 0.378344E+09 | 0.968873E+09 | 0.00 | 0.00 |
March | 0.166606E+10 | 0.214203E+10 | 0.232560E+10 | 0.118695E+10 | 0.113864E+10 | 0.00 | 0.00 |
April | 0.273121E+10 | 0.152261E+10 | 0.304950E+10 | 0.163842E+10 | 0.141108E+10 | 0.00 | 0.00 |
May | 0.416467E+10 | 0.118002E+10 | 0.404212E+10 | 0.251147E+10 | 0.153065E+10 | 0.00 | 0.00 |
June | 0.503869E+10 | 0.851727E+09 | 0.453537E+10 | 0.286988E+10 | 0.166550E+10 | 0.00 | 0.00 |
July | 0.503756E+10 | 0.649509E+09 | 0.434143E+10 | 0.266031E+10 | 0.168113E+10 | 0.00 | 0.00 |
August | 0.409545E+10 | 0.796298E+09 | 0.366661E+10 | 0.204659E+10 | 0.162002E+10 | 0.00 | 0.00 |
September | 0.261153E+10 | 0.115381E+10 | 0.263679E+10 | 0.144144E+10 | 0.119536E+10 | 0.00 | 0.00 |
October | 0.117892E+10 | 0.165101E+10 | 0.166535E+10 | 0.707171E+09 | 0.958182E+09 | 0.00 | 0.00 |
November | 0.337221E+09 | 0.196489E+10 | 0.920192E+09 | 0.269529E+09 | 0.650664E+09 | 0.00 | 0.00 |
December | 63531268.68 | 0.295066E+10 | 0.819626E+09 | 0.158046E+09 | 0.661580E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.274577E+11 | 0.205255E+11 | 0.302733E+11 | 0.161199E+11 | 0.141535E+11 | 0.00 | 0.00 |
Minimum of Months | 63531268.68 | 0.649509E+09 | 0.819626E+09 | 0.158046E+09 | 0.650664E+09 | 0.00 | 0.00 |
Maximum of Months | 0.503869E+10 | 0.307839E+10 | 0.453537E+10 | 0.286988E+10 | 0.168113E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.188503E+10 | 0.283696E+10 | 0.242438E+10 | 0.141499E+10 | 0.100938E+10 | 0.00 | 0.00 |
February | 0.180420E+10 | 0.249416E+10 | 0.250121E+10 | 0.120637E+10 | 0.129484E+10 | 0.00 | 0.00 |
March | 0.283971E+10 | 0.206480E+10 | 0.338056E+10 | 0.190011E+10 | 0.148045E+10 | 0.00 | 0.00 |
April | 0.201073E+10 | 0.151460E+10 | 0.270798E+10 | 0.108197E+10 | 0.162601E+10 | 0.00 | 0.00 |
May | 0.175650E+10 | 0.108943E+10 | 0.244853E+10 | 0.710869E+09 | 0.173767E+10 | 0.00 | 0.00 |
June | 0.192748E+10 | 0.695574E+09 | 0.230238E+10 | 0.487537E+09 | 0.181484E+10 | 0.00 | 0.00 |
July | 0.233762E+10 | 0.468966E+09 | 0.242876E+10 | 0.588989E+09 | 0.183977E+10 | 0.00 | 0.00 |
August | 0.265818E+10 | 0.633607E+09 | 0.272670E+10 | 0.883766E+09 | 0.184293E+10 | 0.00 | 0.00 |
September | 0.303813E+10 | 0.102076E+10 | 0.306901E+10 | 0.149506E+10 | 0.157395E+10 | 0.00 | 0.00 |
October | 0.291532E+10 | 0.158732E+10 | 0.303514E+10 | 0.173420E+10 | 0.130094E+10 | 0.00 | 0.00 |
November | 0.187631E+10 | 0.188494E+10 | 0.210285E+10 | 0.118714E+10 | 0.915707E+09 | 0.00 | 0.00 |
December | 0.149104E+10 | 0.277476E+10 | 0.202707E+10 | 0.104883E+10 | 0.978244E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.265403E+11 | 0.190659E+11 | 0.311546E+11 | 0.137398E+11 | 0.174147E+11 | 0.00 | 0.00 |
Minimum of Months | 0.149104E+10 | 0.468966E+09 | 0.202707E+10 | 0.487537E+09 | 0.915707E+09 | 0.00 | 0.00 |
Maximum of Months | 0.303813E+10 | 0.283696E+10 | 0.338056E+10 | 0.190011E+10 | 0.184293E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.187986E+10 | 0.281479E+10 | 0.242438E+10 | 0.141499E+10 | 0.100938E+10 | 0.00 | 0.00 |
February | 0.179845E+10 | 0.247485E+10 | 0.250121E+10 | 0.120637E+10 | 0.129484E+10 | 0.00 | 0.00 |
March | 0.284440E+10 | 0.202103E+10 | 0.338056E+10 | 0.190011E+10 | 0.148045E+10 | 0.00 | 0.00 |
April | 0.202604E+10 | 0.145699E+10 | 0.270798E+10 | 0.108197E+10 | 0.162601E+10 | 0.00 | 0.00 |
May | 0.177649E+10 | 0.102501E+10 | 0.244853E+10 | 0.710869E+09 | 0.173767E+10 | 0.00 | 0.00 |
June | 0.191950E+10 | 0.679925E+09 | 0.230238E+10 | 0.487537E+09 | 0.181484E+10 | 0.00 | 0.00 |
July | 0.231867E+10 | 0.469622E+09 | 0.242876E+10 | 0.588989E+09 | 0.183977E+10 | 0.00 | 0.00 |
August | 0.263977E+10 | 0.634873E+09 | 0.272670E+10 | 0.883766E+09 | 0.184293E+10 | 0.00 | 0.00 |
September | 0.302971E+10 | 0.100428E+10 | 0.306901E+10 | 0.149506E+10 | 0.157395E+10 | 0.00 | 0.00 |
October | 0.293199E+10 | 0.152171E+10 | 0.303514E+10 | 0.173420E+10 | 0.130094E+10 | 0.00 | 0.00 |
November | 0.188512E+10 | 0.183081E+10 | 0.210285E+10 | 0.118714E+10 | 0.915707E+09 | 0.00 | 0.00 |
December | 0.148773E+10 | 0.275028E+10 | 0.202707E+10 | 0.104883E+10 | 0.978244E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.265377E+11 | 0.186842E+11 | 0.311546E+11 | 0.137398E+11 | 0.174147E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148773E+10 | 0.469622E+09 | 0.202707E+10 | 0.487537E+09 | 0.915707E+09 | 0.00 | 0.00 |
Maximum of Months | 0.302971E+10 | 0.281479E+10 | 0.338056E+10 | 0.190011E+10 | 0.184293E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.401345E+09 | 0.522280E+09 | 0.498851E+09 | 0.291155E+09 | 0.207696E+09 | 0.00 | 0.00 |
February | 0.387020E+09 | 0.464805E+09 | 0.514661E+09 | 0.248228E+09 | 0.266433E+09 | 0.00 | 0.00 |
March | 0.611737E+09 | 0.368153E+09 | 0.695600E+09 | 0.390976E+09 | 0.304623E+09 | 0.00 | 0.00 |
April | 0.458236E+09 | 0.255744E+09 | 0.557207E+09 | 0.222631E+09 | 0.334576E+09 | 0.00 | 0.00 |
May | 0.402640E+09 | 0.181485E+09 | 0.503822E+09 | 0.146272E+09 | 0.357550E+09 | 0.00 | 0.00 |
June | 0.404516E+09 | 0.130005E+09 | 0.473748E+09 | 0.100318E+09 | 0.373430E+09 | 0.00 | 0.00 |
July | 0.459882E+09 | 99907794.50 | 0.499753E+09 | 0.121193E+09 | 0.378560E+09 | 0.00 | 0.00 |
August | 0.530465E+09 | 0.132642E+09 | 0.561058E+09 | 0.181848E+09 | 0.379210E+09 | 0.00 | 0.00 |
September | 0.637058E+09 | 0.187663E+09 | 0.631493E+09 | 0.307630E+09 | 0.323862E+09 | 0.00 | 0.00 |
October | 0.639222E+09 | 0.264921E+09 | 0.624524E+09 | 0.356837E+09 | 0.267686E+09 | 0.00 | 0.00 |
November | 0.410595E+09 | 0.317478E+09 | 0.432692E+09 | 0.244272E+09 | 0.188420E+09 | 0.00 | 0.00 |
December | 0.318548E+09 | 0.507074E+09 | 0.417099E+09 | 0.215812E+09 | 0.201288E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.566126E+10 | 0.343216E+10 | 0.641051E+10 | 0.282717E+10 | 0.358333E+10 | 0.00 | 0.00 |
Minimum of Months | 0.318548E+09 | 99907794.50 | 0.417099E+09 | 0.100318E+09 | 0.188420E+09 | 0.00 | 0.00 |
Maximum of Months | 0.639222E+09 | 0.522280E+09 | 0.695600E+09 | 0.390976E+09 | 0.379210E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.3 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.73 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.65 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.46 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.38 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.38 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.41 | 11.22 | 4.10 | 7.07 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.35 | 4.97 | 4.79 | 0.12 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.71 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.35 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.3 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.38 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.13 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.16 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.04 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.42 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.82 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.22 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.71 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.23 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.51 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.12 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.84 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.40 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.16 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.71 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.2 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.3 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.4 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.82 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.76 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.17 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.74 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.41 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.22 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.95 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.40 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.96 | 4.80 | 10.49 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.96 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.288160E+10 | -.244828E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -433316010.5 | 58.99 | 0.00 | 0.00 |
February | 0.265351E+10 | -.226166E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -391851695.9 | 59.00 | 0.00 | 0.00 |
March | 0.295724E+10 | -.253119E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -426043310.4 | 58.99 | 0.00 | 0.00 |
April | 0.271915E+10 | -.231154E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -407612389.6 | 59.00 | 0.00 | 0.00 |
May | 0.265768E+10 | -.225595E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -401725534.1 | 58.99 | 0.00 | 0.00 |
June | 0.245179E+10 | -.207663E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -375164889.7 | 58.99 | 0.00 | 0.00 |
July | 0.236735E+10 | -.198182E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385527975.5 | 58.99 | 0.00 | 0.00 |
August | 0.239176E+10 | -.200619E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385568150.1 | 58.99 | 0.00 | 0.00 |
September | 0.231959E+10 | -.194286E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -376721030.1 | 58.99 | 0.00 | 0.00 |
October | 0.248799E+10 | -.207664E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -411359813.5 | 58.99 | 0.00 | 0.00 |
November | 0.254065E+10 | -.213045E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -410198938.1 | 59.00 | 0.00 | 0.00 |
December | 0.278079E+10 | -.234892E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -431875339.2 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.312091E+11 | -.263721E+11 | 8760.00 | -.483697E+10 | 58.99 | |||||
Minimum of Months | 0.231959E+10 | -.253119E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -433316010.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.295724E+10 | -.194286E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -375164889.7 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.88 | 0.65 | 31-JAN-10:50 | 151.15 | 3.97 | 0.00 | 1.50 | 116.58 | 2.64 | 0.00 | 0.00 |
February | 262.50 | 0.81 | 0.60 | 11-FEB-10:50 | 459.75 | 5.66 | 0.00 | 28.17 | 162.78 | 4.20 | 0.00 | 0.00 |
March | 339.33 | 0.82 | 0.50 | 15-MAR-11:30 | 239.31 | 5.44 | 0.00 | 1.83 | 170.77 | 3.97 | 0.00 | 0.00 |
April | 371.17 | 0.77 | 0.50 | 01-APR-11:50 | 605.32 | 6.41 | 0.00 | 40.83 | 202.85 | 4.87 | 0.00 | 3.50 |
May | 332.17 | 0.76 | 0.50 | 01-MAY-11:09 | 1675.92 | 6.94 | 0.00 | 47.67 | 1765.79 | 5.23 | 0.00 | 46.00 |
June | 430.67 | 0.77 | 0.50 | 02-JUN-10:09 | 263.45 | 7.79 | 0.00 | 14.50 | 220.82 | 5.98 | 0.00 | 13.33 |
July | 439.00 | 0.77 | 0.50 | 01-JUL-10:50 | 320.37 | 7.62 | 0.00 | 19.83 | 301.27 | 5.89 | 0.00 | 19.67 |
August | 406.00 | 0.76 | 0.50 | 01-AUG-10:09 | 1232.34 | 7.18 | 0.00 | 54.67 | 1239.05 | 5.52 | 0.00 | 49.00 |
September | 289.17 | 0.79 | 0.50 | 02-SEP-10:39 | 238.86 | 5.71 | 0.00 | 2.17 | 199.01 | 4.20 | 0.00 | 1.00 |
October | 314.33 | 0.84 | 0.50 | 29-OCT-11:20 | 268.04 | 4.92 | 0.00 | 4.67 | 245.76 | 3.51 | 0.00 | 5.17 |
November | 258.33 | 0.84 | 0.50 | 01-NOV-11:09 | 405.29 | 3.94 | 0.00 | 25.83 | 409.48 | 2.62 | 0.00 | 25.83 |
December | 230.67 | 0.88 | 0.74 | 09-DEC-12:39 | 145.05 | 4.17 | 0.00 | 0.00 | 117.88 | 2.82 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | 0.80 | 526.34 | 6.06 | 0.00 | 241.67 | 455.76 | 4.51 | 0.00 | 163.50 | ||
Minimum of Months | 230.67 | 0.76 | 0.50 | 145.05 | 3.94 | 0.00 | 0.00 | 116.58 | 2.62 | 0.00 | 0.00 | |
Maximum of Months | 439.00 | 0.88 | 0.74 | 1675.92 | 7.79 | 0.00 | 54.67 | 1765.79 | 5.98 | 0.00 | 49.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.190895E+11 | 45896.27 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182823E+11 | 45896.27 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112543E+11 | 45896.27 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.447429E+10 | 45896.27 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.306196E+09 | 45896.27 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4052568.69 | 2142.85 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156399E+10 | 45896.27 | 09-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.562689E+10 | 45896.27 | 01-NOV-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169091E+11 | 45896.27 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.775107E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.190895E+11 | 45896.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.725893E+11 | 228847.98 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.678588E+11 | 228847.98 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.402720E+11 | 228847.98 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153072E+11 | 216371.45 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.767078E+09 | 40785.12 | 08-MAY-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20489038.84 | 9094.98 | 30-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.771790E+10 | 127154.78 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.243642E+11 | 213741.55 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.657469E+11 | 228847.98 | 07-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294644E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.725893E+11 | 228847.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.793837E+10 | 30333.28 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.764246E+10 | 30333.28 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350452E+10 | 30333.28 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142082E+10 | 30333.28 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81222316.78 | 20909.17 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2307768.99 | 1247.86 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.407503E+09 | 30333.28 | 09-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171965E+10 | 30333.28 | 03-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.721702E+10 | 30333.28 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299339E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.793837E+10 | 30333.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104174E+11 | 24020.69 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.990287E+10 | 24020.69 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.537403E+10 | 24020.69 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260540E+10 | 24020.69 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.255438E+09 | 24020.69 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 519051.43 | 866.40 | 14-JUN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13947689.70 | 3429.37 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.984999E+09 | 24020.69 | 09-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324641E+10 | 24020.69 | 03-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.965328E+10 | 24020.69 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.424543E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104174E+11 | 24020.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136329E+11 | 33504.43 | 31-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129745E+11 | 36850.90 | 06-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.731703E+10 | 28603.29 | 11-MAR-15:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196832E+10 | 28131.00 | 02-APR-16:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103975E+10 | 28306.80 | 29-OCT-16:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.397581E+10 | 28362.55 | 19-NOV-15:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129699E+11 | 34462.42 | 10-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.538782E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136329E+11 | 36850.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 96257828.42 | 76048243.85 | 4831.31 | 15-MAR-15:00 | 3865.24 | 0.00 |
April | 0.00 | 0.00 | 90.31 | 74.17 | 0.13 | 08-APR-13:30 | 0.11 | 0.00 |
May | 0.00 | 0.00 | 0.486183E+09 | 0.427207E+09 | 6476.13 | 10-MAY-15:00 | 4693.15 | 0.00 |
June | 0.00 | 0.00 | 0.674338E+10 | 0.476885E+10 | 35348.73 | 18-JUN-06:00 | 17106.12 | 0.00 |
July | 0.00 | 0.00 | 0.155331E+11 | 0.101672E+11 | 35562.97 | 16-JUL-02:10 | 16117.16 | 0.00 |
August | 0.00 | 0.00 | 0.117852E+11 | 0.850581E+10 | 35761.97 | 14-AUG-02:53 | 16519.42 | 0.00 |
September | 0.00 | 0.00 | 0.379435E+10 | 0.254677E+10 | 34953.02 | 15-SEP-20:53 | 15571.15 | 0.00 |
October | 0.00 | 0.00 | 18469963.01 | 15918575.53 | 2009.47 | 11-OCT-15:00 | 1719.16 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.384569E+11 | 0.265078E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.155331E+11 | 0.101672E+11 | 35761.97 | 17106.12 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.107901E+10 | 0.851491E+09 | 30632.86 | 15-MAR-14:10 | 26076.55 | 0.00 |
April | 0.00 | 0.00 | 46475384.91 | 38309149.18 | 7043.76 | 08-APR-13:30 | 5846.54 | 0.00 |
May | 0.00 | 0.00 | 0.492052E+10 | 0.421349E+10 | 113447.51 | 24-MAY-06:03 | 74052.30 | 0.00 |
June | 0.00 | 0.00 | 0.386428E+11 | 0.268858E+11 | 166276.75 | 18-JUN-08:62 | 84742.46 | 0.00 |
July | 0.00 | 0.00 | 0.730255E+11 | 0.469522E+11 | 167308.45 | 16-JUL-08:62 | 82507.38 | 0.00 |
August | 0.00 | 0.00 | 0.558815E+11 | 0.398913E+11 | 166089.85 | 14-AUG-06:02 | 77179.21 | 0.00 |
September | 0.00 | 0.00 | 0.213771E+11 | 0.143045E+11 | 161298.94 | 16-SEP-06:02 | 85000.22 | 0.00 |
October | 0.00 | 0.00 | 0.397023E+09 | 0.325464E+09 | 18260.59 | 11-OCT-15:00 | 15090.33 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.195370E+12 | 0.133463E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.730255E+11 | 0.469522E+11 | 167308.45 | 85000.22 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.347378E+09 | 0.285975E+09 | 19239.46 | 15-MAR-20:21 | 15390.06 | 0.00 |
April | 0.00 | 0.00 | 51287509.09 | 45688882.94 | 3247.48 | 08-APR-13:30 | 2831.97 | 0.00 |
May | 0.00 | 0.00 | 0.100096E+10 | 0.886684E+09 | 19127.99 | 23-MAY-24:00 | 17691.01 | 0.00 |
June | 0.00 | 0.00 | 0.662991E+10 | 0.479543E+10 | 21557.60 | 27-JUN-20:13 | 10385.76 | 0.00 |
July | 0.00 | 0.00 | 0.131078E+11 | 0.881706E+10 | 21759.74 | 16-JUL-07:00 | 9733.48 | 0.00 |
August | 0.00 | 0.00 | 0.109901E+11 | 0.810865E+10 | 21760.20 | 14-AUG-03:30 | 9976.90 | 0.00 |
September | 0.00 | 0.00 | 0.564191E+10 | 0.404184E+10 | 21347.88 | 15-SEP-20:17 | 9963.18 | 0.00 |
October | 0.00 | 0.00 | 0.663436E+09 | 0.539305E+09 | 18485.60 | 11-OCT-20:15 | 15425.49 | 0.00 |
November | 0.00 | 0.00 | 2014078.98 | 1665826.59 | 643.85 | 16-NOV-12:40 | 539.31 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.384348E+11 | 0.275223E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.131078E+11 | 0.881706E+10 | 21760.20 | 17691.01 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.224531E+09 | 0.184566E+09 | 5532.35 | 15-MAR-13:50 | 4968.49 | 0.00 |
April | 0.00 | 0.00 | 68242476.75 | 63649222.76 | 2457.91 | 08-APR-13:50 | 2150.26 | 0.00 |
May | 0.00 | 0.00 | 0.849044E+09 | 0.751990E+09 | 4865.47 | 10-MAY-15:00 | 3799.61 | 0.00 |
June | 0.00 | 0.00 | 0.505194E+10 | 0.385632E+10 | 15983.39 | 18-JUN-20:12 | 11874.23 | 0.00 |
July | 0.00 | 0.00 | 0.945506E+10 | 0.684222E+10 | 16335.78 | 22-JUL-23:02 | 10680.91 | 0.00 |
August | 0.00 | 0.00 | 0.841045E+10 | 0.663738E+10 | 16328.43 | 27-AUG-00:58 | 10729.69 | 0.00 |
September | 0.00 | 0.00 | 0.478915E+10 | 0.381836E+10 | 16166.15 | 16-SEP-04:22 | 11237.12 | 0.00 |
October | 0.00 | 0.00 | 0.731009E+09 | 0.630646E+09 | 9108.63 | 11-OCT-20:33 | 8611.75 | 0.00 |
November | 0.00 | 0.00 | 7684810.83 | 6348063.17 | 882.19 | 16-NOV-12:30 | 817.87 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.295871E+11 | 0.227915E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.945506E+10 | 0.684222E+10 | 16335.78 | 11874.23 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.284164E+10 | 0.52 | 1832.35 | 01-JAN-00:15 | 0.90 |
February | 0.267737E+10 | 0.55 | 1832.35 | 01-FEB-00:15 | 0.91 |
March | 0.191612E+10 | 0.35 | 1832.35 | 01-MAR-03:47 | 0.90 |
April | 0.901112E+09 | 0.17 | 1832.35 | 01-APR-07:10 | 0.90 |
May | 9894673.90 | 0.00 | 1832.35 | 01-MAY-07:10 | 0.90 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.562135E+09 | 0.10 | 1832.35 | 03-OCT-07:10 | 0.90 |
November | 0.142125E+10 | 0.27 | 1832.35 | 01-NOV-07:05 | 0.90 |
December | 0.278434E+10 | 0.51 | 1832.35 | 01-DEC-14:51 | 0.90 |
Annual Sum or Average | 0.131139E+11 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.284164E+10 | 0.55 | 1832.35 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159315E+10 | 0.43 | 1751.44 | 01-JAN-07:01 | 0.90 |
February | 0.147320E+10 | 0.45 | 1751.44 | 01-FEB-05:01 | 0.90 |
March | 0.142205E+10 | 0.40 | 1751.44 | 01-MAR-05:01 | 0.90 |
April | 0.121155E+10 | 0.37 | 1751.44 | 01-APR-04:01 | 0.90 |
May | 0.114046E+10 | 0.33 | 1751.44 | 01-MAY-04:01 | 0.89 |
June | 0.112006E+10 | 0.33 | 1751.44 | 17-JUN-23:23 | 0.88 |
July | 0.121013E+10 | 0.35 | 1751.44 | 01-JUL-22:01 | 0.89 |
August | 0.119601E+10 | 0.35 | 1751.44 | 04-AUG-21:33 | 0.89 |
September | 0.110561E+10 | 0.33 | 1751.44 | 16-SEP-21:42 | 0.89 |
October | 0.116247E+10 | 0.34 | 1751.44 | 09-OCT-06:01 | 0.90 |
November | 0.122354E+10 | 0.37 | 1751.44 | 01-NOV-04:02 | 0.90 |
December | 0.154220E+10 | 0.42 | 1751.44 | 01-DEC-05:01 | 0.90 |
Annual Sum or Average | 0.154004E+11 | 0.37 | |||
Minimum of Months | 0.110561E+10 | 0.33 | 1751.44 | 0.88 | |
Maximum of Months | 0.159315E+10 | 0.45 | 1751.44 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.944419E+10 | 0.60 | 11363.26 | 01-JAN-08:61 | 1.42 |
February | 0.863366E+10 | 0.61 | 11363.26 | 01-FEB-06:02 | 1.42 |
March | 0.861228E+10 | 0.57 | 11363.26 | 01-MAR-06:02 | 1.42 |
April | 0.757399E+10 | 0.54 | 10991.55 | 17-APR-06:03 | 1.40 |
May | 0.737084E+10 | 0.52 | 8081.51 | 24-MAY-06:03 | 1.19 |
June | 0.720485E+10 | 0.52 | 11363.26 | 02-JUN-06:02 | 1.40 |
July | 0.742184E+10 | 0.51 | 11363.26 | 01-JUL-06:02 | 1.41 |
August | 0.745392E+10 | 0.52 | 11363.26 | 01-AUG-06:02 | 1.41 |
September | 0.713279E+10 | 0.52 | 11363.26 | 09-SEP-06:03 | 1.40 |
October | 0.751151E+10 | 0.52 | 8333.56 | 30-OCT-06:03 | 1.22 |
November | 0.774564E+10 | 0.54 | 10913.20 | 24-NOV-07:03 | 1.40 |
December | 0.925710E+10 | 0.60 | 11363.26 | 07-DEC-06:02 | 1.42 |
Annual Sum or Average | 0.953626E+11 | 0.55 | |||
Minimum of Months | 0.713279E+10 | 0.51 | 8081.51 | 1.19 | |
Maximum of Months | 0.944419E+10 | 0.61 | 11363.26 | 1.42 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.898146E+09 | 0.41 | 1109.63 | 01-JAN-07:01 | 0.93 |
February | 0.826811E+09 | 0.43 | 1109.63 | 01-FEB-05:01 | 0.93 |
March | 0.807584E+09 | 0.39 | 1109.63 | 01-MAR-05:01 | 0.93 |
April | 0.729257E+09 | 0.36 | 1109.63 | 01-APR-04:01 | 0.93 |
May | 0.720627E+09 | 0.34 | 1096.50 | 23-MAY-23:31 | 0.92 |
June | 0.740999E+09 | 0.37 | 1109.63 | 01-JUN-22:31 | 0.92 |
July | 0.831467E+09 | 0.40 | 1109.63 | 21-JUL-20:10 | 0.91 |
August | 0.839424E+09 | 0.41 | 1109.63 | 08-AUG-04:22 | 0.92 |
September | 0.744381E+09 | 0.37 | 1109.63 | 09-SEP-00:11 | 0.92 |
October | 0.723203E+09 | 0.34 | 1109.63 | 09-OCT-06:01 | 0.93 |
November | 0.726702E+09 | 0.36 | 1109.63 | 03-NOV-04:01 | 0.93 |
December | 0.882416E+09 | 0.41 | 1109.63 | 01-DEC-05:01 | 0.93 |
Annual Sum or Average | 0.947102E+10 | 0.38 | |||
Minimum of Months | 0.720627E+09 | 0.34 | 1096.50 | 0.91 | |
Maximum of Months | 0.898146E+09 | 0.43 | 1109.63 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133773E+10 | 0.60 | 813.34 | 01-JAN-09:50 | 0.93 |
February | 0.122095E+10 | 0.62 | 813.34 | 01-FEB-08:20 | 0.93 |
March | 0.134578E+10 | 0.59 | 813.34 | 02-MAR-12:05 | 0.93 |
April | 0.128495E+10 | 0.58 | 813.34 | 03-APR-06:10 | 0.93 |
May | 0.131604E+10 | 0.56 | 813.34 | 04-MAY-05:03 | 0.93 |
June | 0.130018E+10 | 0.59 | 813.34 | 03-JUN-11:04 | 0.93 |
July | 0.139853E+10 | 0.66 | 813.34 | 03-JUL-12:00 | 0.92 |
August | 0.141149E+10 | 0.67 | 813.34 | 01-AUG-19:40 | 0.93 |
September | 0.130215E+10 | 0.60 | 813.34 | 01-SEP-10:50 | 0.92 |
October | 0.130728E+10 | 0.56 | 813.34 | 07-OCT-19:45 | 0.93 |
November | 0.126791E+10 | 0.58 | 813.34 | 04-NOV-07:17 | 0.93 |
December | 0.133713E+10 | 0.60 | 813.34 | 01-DEC-07:50 | 0.93 |
Annual Sum or Average | 0.158301E+11 | 0.60 | |||
Minimum of Months | 0.122095E+10 | 0.56 | 813.34 | 0.92 | |
Maximum of Months | 0.141149E+10 | 0.67 | 813.34 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.42 | 0.00 |
February | 2.84 | 0.00 |
March | 1.21 | 0.00 |
April | 0.29 | 0.00 |
May | 0.17 | 0.00 |
June | 0.14 | 0.00 |
July | 0.62 | 0.00 |
August | 0.11 | 0.00 |
September | 0.08 | 0.00 |
October | 0.25 | 0.00 |
November | 0.17 | 0.00 |
December | 2.94 | 0.00 |
Annual Sum or Average | 11.24 | 0.00 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 2.94 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.22 | 25.84 |
April | 0.17 | 25.84 |
May | 1.83 | 25.84 |
June | 0.93 | 25.84 |
July | 0.67 | 25.84 |
August | 0.83 | 25.84 |
September | 0.90 | 25.84 |
October | 0.94 | 25.84 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 6.50 | 25.84 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.83 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.99 | 0.00 |
February | 2.09 | 0.00 |
March | 0.33 | 0.00 |
April | 0.21 | 0.97 |
May | 0.75 | 0.00 |
June | 6.32 | 0.02 |
July | 9.97 | 0.00 |
August | 11.95 | 0.00 |
September | 5.46 | 0.11 |
October | 0.53 | 0.00 |
November | 0.00 | 0.00 |
December | 1.96 | 0.00 |
Annual Sum or Average | 41.55 | 0.02 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 11.95 | 0.97 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.72 | 0.00 |
February | 2.69 | 0.00 |
March | 0.90 | 0.00 |
April | 0.37 | 0.00 |
May | 0.47 | 0.00 |
June | 0.18 | 2.44 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.29 | 2.44 |
October | 0.58 | 0.00 |
November | 0.47 | 0.00 |
December | 3.09 | 0.00 |
Annual Sum or Average | 11.78 | 0.10 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.09 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 34.14 | 0.00 |
February | 50.37 | 0.00 |
March | 6.99 | 0.00 |
April | 4.82 | 0.00 |
May | 3.36 | 0.00 |
June | 2.51 | 0.00 |
July | 2.46 | 0.00 |
August | 3.26 | 0.00 |
September | 4.45 | 0.00 |
October | 7.21 | 0.00 |
November | 4.93 | 0.00 |
December | 26.17 | 0.00 |
Annual Sum or Average | 150.66 | 0.00 |
Minimum of Months | 2.46 | 0.00 |
Maximum of Months | 50.37 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.159315E+10 | 0.235672E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.147320E+10 | 0.225708E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.144900E+10 | 0.138942E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.121155E+10 | 0.552382E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.127239E+10 | 0.378019E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.278750E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.492917E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.408220E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.204471E+10 | 5003171.23 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.116765E+10 | 0.193085E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.122354E+10 | 0.694678E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.154220E+10 | 0.208755E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.247763E+11 | 0.956922E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.116765E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.492917E+10 | 0.235672E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.944419E+10 | 0.907366E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.863366E+10 | 0.848235E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.894073E+10 | 0.503400E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.758836E+10 | 0.191340E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.880920E+10 | 0.958848E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.177436E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.267561E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.226836E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.130270E+11 | 25611298.55 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.763273E+10 | 0.964738E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.774564E+10 | 0.304552E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.925710E+10 | 0.821836E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.148262E+12 | 0.368305E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.758836E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.267561E+11 | 0.907366E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.898146E+09 | 0.980046E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.826811E+09 | 0.943513E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.894638E+09 | 0.432657E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.742804E+09 | 0.175409E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.974861E+09 | 0.100274E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.231310E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.386132E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.340441E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.205534E+10 | 2849097.52 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.887412E+09 | 0.503090E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.727263E+09 | 0.212302E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.882416E+09 | 0.890991E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.184685E+11 | 0.369554E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.727263E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.386132E+10 | 0.980046E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.133773E+10 | 0.128610E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.122095E+10 | 0.122258E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.139672E+10 | 0.663460E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.130099E+10 | 0.321654E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.151053E+10 | 0.315356E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.238322E+10 | 640804.23 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.338749E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.319692E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.231050E+10 | 17219370.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.146795E+10 | 0.121605E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.126978E+10 | 0.400791E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.133713E+10 | 0.119176E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.221199E+11 | 0.524128E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.122095E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.338749E+10 | 0.128610E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.159315E+10 | 0.00 | 0.190895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147320E+10 | 0.00 | 0.182823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142205E+10 | 96257828.42 | 0.112543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121155E+10 | 90.31 | 0.447429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114046E+10 | 0.486183E+09 | 0.306196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112006E+10 | 0.668525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121013E+10 | 0.152055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119601E+10 | 0.115922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110561E+10 | 0.375526E+10 | 4052568.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116247E+10 | 18469963.01 | 0.156399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122354E+10 | 0.00 | 0.562689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154220E+10 | 0.00 | 0.169091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154004E+11 | 0.378392E+11 | 0.775107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159315E+10 | 0.152055E+11 | 0.190895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.944419E+10 | 0.00 | 0.725893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.863366E+10 | 0.00 | 0.678588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.861228E+10 | 0.107901E+10 | 0.402720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.757399E+10 | 46475384.91 | 0.153072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.737084E+10 | 0.492052E+10 | 0.767078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.720485E+10 | 0.386428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.742184E+10 | 0.730255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.745392E+10 | 0.558815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.713279E+10 | 0.213771E+11 | 20489038.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.751151E+10 | 0.397023E+09 | 0.771790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.774564E+10 | 0.00 | 0.243642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.925710E+10 | 0.00 | 0.657469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.953626E+11 | 0.195370E+12 | 0.294644E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.713279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.944419E+10 | 0.730255E+11 | 0.725893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.898146E+09 | 0.00 | 0.793837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.826811E+09 | 0.00 | 0.764246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.807584E+09 | 0.346818E+09 | 0.350452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.729257E+09 | 51287509.09 | 0.142082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.720627E+09 | 0.993275E+09 | 81222316.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.740999E+09 | 0.645153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.831467E+09 | 0.125606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.839424E+09 | 0.105698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.744381E+09 | 0.549479E+10 | 2307768.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.723203E+09 | 0.660293E+09 | 0.407503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.726702E+09 | 2014078.98 | 0.171965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.882416E+09 | 0.00 | 0.721702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.947102E+10 | 0.371305E+11 | 0.299339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.720627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.898146E+09 | 0.125606E+11 | 0.793837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.133773E+10 | 0.00 | 0.104174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122095E+10 | 0.00 | 0.990287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134578E+10 | 0.224531E+09 | 0.537403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128495E+10 | 68242476.75 | 0.260540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131604E+10 | 0.849044E+09 | 0.255438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130018E+10 | 0.505194E+10 | 519051.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139853E+10 | 0.945506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141149E+10 | 0.841045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130215E+10 | 0.478915E+10 | 13947689.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130728E+10 | 0.731009E+09 | 0.984999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126791E+10 | 7684810.83 | 0.324641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133713E+10 | 0.00 | 0.965328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158301E+11 | 0.295871E+11 | 0.424543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141149E+10 | 0.945506E+10 | 0.104174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.159315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142205E+10 | 0.00 | 0.00 | 0.00 | 26946009.57 | 0.00 | 0.138942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121155E+10 | 0.00 | 0.00 | 0.00 | 25.67 | 0.00 | 0.552382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114046E+10 | 0.00 | 0.00 | 0.00 | 0.131930E+09 | 0.00 | 0.378019E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112006E+10 | 0.00 | 0.00 | 0.00 | 0.166744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121013E+10 | 0.00 | 0.00 | 0.00 | 0.371904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119601E+10 | 0.00 | 0.00 | 0.00 | 0.288618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110561E+10 | 0.00 | 0.00 | 0.00 | 0.939104E+09 | 0.00 | 5003171.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116247E+10 | 0.00 | 0.00 | 0.00 | 5178755.18 | 0.00 | 0.193085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154004E+11 | 0.00 | 0.00 | 0.00 | 0.937583E+10 | 0.00 | 0.956922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.110561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159315E+10 | 0.00 | 0.00 | 0.00 | 0.371904E+10 | 0.00 | 0.235672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.944419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.863366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.848235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.861228E+10 | 0.00 | 0.00 | 0.00 | 0.328447E+09 | 0.00 | 0.503400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.757399E+10 | 0.00 | 0.00 | 0.00 | 14377073.01 | 0.00 | 0.191340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.737084E+10 | 0.00 | 0.00 | 0.00 | 0.143836E+10 | 0.00 | 0.958848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.720485E+10 | 0.00 | 0.00 | 0.00 | 0.105388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.742184E+10 | 0.00 | 0.00 | 0.00 | 0.193342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.745392E+10 | 0.00 | 0.00 | 0.00 | 0.152297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.713279E+10 | 0.00 | 0.00 | 0.00 | 0.589421E+10 | 0.00 | 25611298.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.751151E+10 | 0.00 | 0.00 | 0.00 | 0.121223E+09 | 0.00 | 0.964738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.774564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.925710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.953626E+11 | 0.00 | 0.00 | 0.00 | 0.528992E+11 | 0.00 | 0.368305E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.713279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.944419E+10 | 0.00 | 0.00 | 0.00 | 0.193342E+11 | 0.00 | 0.907366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.898146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.826811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.807584E+09 | 0.00 | 0.00 | 0.00 | 87053909.47 | 0.00 | 0.432657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.729257E+09 | 0.00 | 0.00 | 0.00 | 13546916.98 | 0.00 | 0.175409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.720627E+09 | 0.00 | 0.00 | 0.00 | 0.254233E+09 | 0.00 | 0.100274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.740999E+09 | 0.00 | 0.00 | 0.00 | 0.157210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.831467E+09 | 0.00 | 0.00 | 0.00 | 0.302986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.839424E+09 | 0.00 | 0.00 | 0.00 | 0.256499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.744381E+09 | 0.00 | 0.00 | 0.00 | 0.131096E+10 | 0.00 | 2849097.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.723203E+09 | 0.00 | 0.00 | 0.00 | 0.164209E+09 | 0.00 | 0.503090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.726702E+09 | 0.00 | 0.00 | 0.00 | 560921.52 | 0.00 | 0.212302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.882416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.947102E+10 | 0.00 | 0.00 | 0.00 | 0.899751E+10 | 0.00 | 0.369554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.720627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.898146E+09 | 0.00 | 0.00 | 0.00 | 0.302986E+10 | 0.00 | 0.980046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.133773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134578E+10 | 0.00 | 0.00 | 0.00 | 50939095.11 | 0.00 | 0.663460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128495E+10 | 0.00 | 0.00 | 0.00 | 16037047.27 | 0.00 | 0.321654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131604E+10 | 0.00 | 0.00 | 0.00 | 0.194498E+09 | 0.00 | 0.315356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130018E+10 | 0.00 | 0.00 | 0.00 | 0.108304E+10 | 0.00 | 640804.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139853E+10 | 0.00 | 0.00 | 0.00 | 0.198896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141149E+10 | 0.00 | 0.00 | 0.00 | 0.178543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130215E+10 | 0.00 | 0.00 | 0.00 | 0.100835E+10 | 0.00 | 17219370.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130728E+10 | 0.00 | 0.00 | 0.00 | 0.160669E+09 | 0.00 | 0.121605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126791E+10 | 0.00 | 0.00 | 0.00 | 1862271.66 | 0.00 | 0.400791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158301E+11 | 0.00 | 0.00 | 0.00 | 0.628979E+10 | 0.00 | 0.524128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.122095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141149E+10 | 0.00 | 0.00 | 0.00 | 0.198896E+10 | 0.00 | 0.128610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 64905001.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110336E+11 | 0.00 | 0.00 | 0.20 |
February | 0.103182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101948E+11 | 0.00 | 0.00 | 0.20 |
March | 0.208480E+10 | 0.00 | 0.00 | 154606.12 | 0.00 | 0.650067E+10 | 95427902.68 | 0.00 | 0.21 |
April | 0.415616E+10 | 0.00 | 0.00 | 15468.23 | 0.00 | 0.212521E+10 | 36079676.50 | 0.00 | 0.21 |
May | 0.305652E+10 | 6521631.24 | 0.00 | 2534578.77 | 326472.79 | 0.129857E+09 | 0.230871E+10 | 0.00 | 0.29 |
June | 0.460717E+09 | 0.878209E+09 | 0.00 | 8115289.26 | 182800.91 | 0.00 | 0.397637E+10 | 0.00 | 0.48 |
July | 55564095.59 | 0.274127E+10 | 0.00 | 5522826.08 | 0.00 | 0.00 | 0.121051E+10 | 0.00 | 0.49 |
August | 0.156438E+09 | 0.143865E+10 | 0.00 | 9788037.31 | 0.00 | 0.00 | 0.269418E+10 | 0.00 | 0.50 |
September | 0.948521E+09 | 0.313685E+09 | 0.00 | 7932248.08 | 0.00 | 0.00 | 0.437508E+10 | 0.00 | 0.48 |
October | 0.473590E+10 | 0.00 | 0.00 | 829676.75 | 0.00 | 0.621012E+09 | 0.926294E+09 | 0.00 | 0.22 |
November | 0.430107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257547E+10 | 0.00 | 0.00 | 0.20 |
December | 0.755656E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987410E+10 | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.208794E+11 | 0.537834E+10 | 0.00 | 34892730.60 | 509273.70 | 0.430547E+11 | 0.156227E+11 | 0.00 | 0.31 |
Minimum of Months | 55564095.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.473590E+10 | 0.274127E+10 | 0.00 | 9788037.31 | 326472.79 | 0.110336E+11 | 0.437508E+10 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.504012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367429E+11 | 0.00 | 0.00 | 0.39 |
February | 0.470138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338895E+11 | 0.00 | 0.00 | 0.39 |
March | 0.545457E+11 | 2080139.49 | 0.00 | 1288111.72 | 0.00 | 0.116334E+11 | 0.612282E+09 | 0.00 | 0.40 |
April | 0.435941E+11 | 0.00 | 0.00 | 909862.66 | 0.00 | 0.347747E+10 | 0.136694E+10 | 0.00 | 0.40 |
May | 0.203644E+11 | 0.140751E+09 | 0.00 | 21124562.20 | 9516824.66 | 0.157482E+09 | 0.167046E+11 | 0.00 | 0.48 |
June | 0.369671E+10 | 0.714600E+10 | 0.00 | 42244285.12 | 52140072.24 | 0.00 | 0.175270E+11 | 0.00 | 0.58 |
July | 0.450494E+09 | 0.190552E+11 | 0.00 | 20133009.55 | 0.227579E+09 | 0.00 | 0.387682E+10 | 0.00 | 0.54 |
August | 0.124936E+10 | 0.100308E+11 | 0.00 | 42048351.24 | 55220969.12 | 0.00 | 0.101783E+11 | 0.00 | 0.56 |
September | 0.769180E+10 | 0.233523E+10 | 0.00 | 40488670.43 | 10047032.25 | 0.00 | 0.199134E+11 | 0.00 | 0.57 |
October | 0.396065E+11 | 0.00 | 0.00 | 4499667.22 | 2498805.63 | 0.112823E+10 | 0.459765E+10 | 0.00 | 0.41 |
November | 0.480802E+11 | 0.00 | 0.00 | 8484.28 | 0.00 | 0.496859E+10 | 69981393.52 | 0.00 | 0.39 |
December | 0.544348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288736E+11 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.371129E+12 | 0.387100E+11 | 0.00 | 0.172745E+09 | 0.357003E+09 | 0.120871E+12 | 0.748471E+11 | 0.00 | 0.46 |
Minimum of Months | 0.450494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.545457E+11 | 0.190552E+11 | 0.00 | 42244285.12 | 0.227579E+09 | 0.367429E+11 | 0.199134E+11 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.491984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321303E+10 | 0.00 | 0.00 | 0.39 |
February | 0.420216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336093E+10 | 0.00 | 0.00 | 0.39 |
March | 0.491511E+10 | 8622332.13 | 0.00 | 753944.34 | 0.00 | 0.113850E+10 | 0.331399E+09 | 0.00 | 0.42 |
April | 0.333583E+10 | 0.00 | 0.00 | 1660223.93 | 0.00 | 0.512247E+09 | 0.121698E+10 | 0.00 | 0.46 |
May | 0.104930E+10 | 26066747.97 | 0.00 | 5982452.16 | 0.00 | 23448601.96 | 0.344010E+10 | 0.00 | 0.68 |
June | 0.244815E+09 | 0.966882E+09 | 0.00 | 7299608.00 | 21415.82 | 0.00 | 0.248264E+10 | 0.00 | 0.89 |
July | 35241760.30 | 0.276496E+10 | 0.00 | 4016516.76 | 115440.43 | 0.00 | 0.664552E+09 | 0.00 | 0.88 |
August | 63794682.74 | 0.154094E+10 | 0.00 | 7941943.05 | 2583581.71 | 0.00 | 0.164191E+10 | 0.00 | 0.93 |
September | 0.385792E+09 | 0.582781E+09 | 0.00 | 10310882.86 | 395104.57 | 0.00 | 0.333748E+10 | 0.00 | 0.96 |
October | 0.248544E+10 | 0.00 | 0.00 | 5228249.09 | 0.00 | 0.113723E+09 | 0.275977E+10 | 0.00 | 0.57 |
November | 0.409663E+10 | 0.00 | 0.00 | 1007263.10 | 0.00 | 0.433007E+09 | 0.805489E+09 | 0.00 | 0.43 |
December | 0.502158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276820E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.307555E+11 | 0.589025E+10 | 0.00 | 44201083.27 | 3115542.53 | 0.115631E+11 | 0.166803E+11 | 0.00 | 0.62 |
Minimum of Months | 35241760.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.502158E+10 | 0.276496E+10 | 0.00 | 10310882.86 | 2583581.71 | 0.336093E+10 | 0.344010E+10 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695647E+10 | 0.00 | 0.00 | 0.39 |
February | 0.117681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637606E+10 | 0.00 | 0.00 | 0.39 |
March | 0.320460E+10 | 1452185.74 | 0.00 | 193542.33 | 0.00 | 0.294846E+10 | 51729115.17 | 0.00 | 0.40 |
April | 0.276072E+10 | 0.00 | 0.00 | 230801.41 | 0.00 | 0.146174E+10 | 0.275891E+09 | 0.00 | 0.40 |
May | 0.200827E+10 | 13463551.29 | 0.00 | 1457522.69 | 0.00 | 0.146175E+09 | 0.896630E+09 | 0.00 | 0.40 |
June | 0.446286E+09 | 0.654873E+09 | 0.00 | 3105125.00 | 0.00 | 0.00 | 0.962092E+09 | 0.00 | 0.40 |
July | 76791596.39 | 0.179416E+10 | 0.00 | 1213119.41 | 0.00 | 0.00 | 0.151052E+09 | 0.00 | 0.40 |
August | 0.157230E+09 | 0.997468E+09 | 0.00 | 3552841.51 | 0.00 | 0.00 | 0.466237E+09 | 0.00 | 0.40 |
September | 0.686773E+09 | 0.296118E+09 | 0.00 | 5043727.06 | 0.00 | 1510102.51 | 0.115319E+10 | 0.00 | 0.40 |
October | 0.305131E+10 | 0.00 | 0.00 | 1718187.64 | 0.00 | 0.440348E+09 | 0.665184E+09 | 0.00 | 0.39 |
November | 0.309801E+10 | 0.00 | 0.00 | 72786.29 | 0.00 | 0.178564E+10 | 0.116318E+09 | 0.00 | 0.39 |
December | 0.998511E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677739E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.188380E+11 | 0.375754E+10 | 0.00 | 16587653.33 | 0.00 | 0.268938E+11 | 0.473832E+10 | 0.00 | 0.40 |
Minimum of Months | 76791596.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.320460E+10 | 0.179416E+10 | 0.00 | 5043727.06 | 0.00 | 0.695647E+10 | 0.115319E+10 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |