Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2020-06-03 19:13:38
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1367.12 | 595.96 | 595.96 |
Net Site Energy | 1367.12 | 595.96 | 595.96 |
Total Source Energy | 3799.68 | 1656.36 | 1656.36 |
Net Source Energy | 3799.68 | 1656.36 | 1656.36 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 163.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 247.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 420.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 190.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 91.28 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1112.68 | 254.44 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 163.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 247.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 420.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 194.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 190.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 91.28 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 209.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 190.65 | 110.91 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 485.04 | 110.91 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 209.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 190.65 | 110.91 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 485.04 | 110.91 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1112.682 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1112.682 | 100.00 |
Total On-Site and Utility Electric Sources | 1112.682 | 100.00 |
Total Electricity End Uses | 1112.682 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1009.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 28.69 |
Skylight-Roof Ratio [%] | 1.25 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.5670 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 18.0834 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 18.0834 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 18.0834 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 9.6875 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.2979 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.2979 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-JUL-14:30 | 12-FEB-09:09 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 189840.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 51085.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26875.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10752.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11311.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4545.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 100025.34 | 194386.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 189840.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 51085.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26875.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10752.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11311.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4545.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 176.86 | 0.00 | 0.00 | 0.00 |
Cooling | 783.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1331.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 616.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 601.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 98.95 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3523.86 | 275.81 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 77.10 | 0.00 | 0.00 | 0.00 |
Cooling | 341.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 580.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 83.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 262.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 43.13 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1536.13 | 120.23 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 77.10 | 0.00 | 0.00 | 0.00 |
Cooling | 341.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 580.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 83.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 262.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 43.13 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1536.13 | 120.23 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.97 |
CORE_RETAIL DIRECT AIR | 8.00 |
POINT_OF_SALE DIRECT AIR | 1.17 |
FRONT_RETAIL DIRECT AIR | 0.909930 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 1.82 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 1.82 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 40901.15 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 51326.47 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 238806.69 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 31594.26 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 25871.04 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.97 | 1.97 | 1.97 | 1.97 | 1.99 | 1.99 | 1.00 | 0.991574 | 1.99 |
PSZ-AC:2 | 8.00 | 8.00 | 8.00 | 8.00 | 8.14 | 8.14 | 1.00 | 0.982786 | 8.14 |
PSZ-AC:3 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.00 | 1.000000 | 1.17 |
PSZ-AC:4 | 0.909930 | 0.909930 | 0.909930 | 0.909930 | 0.911720 | 0.911720 | 1.00 | 0.998036 | 0.911720 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.99 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 8.14 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.17 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 0.911720 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.99 | 1.99 | 1.99 | 1.31 | 37848.79 | 51326.47 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 8.14 | 8.14 | 8.14 | 5.38 | 187847.59 | 238806.69 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.17 | 1.17 | 1.17 | 1.17 | 23909.29 | 31594.26 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.911720 | 0.911720 | 0.911720 | 0.911720 | 19689.46 | 25871.04 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.99 | 0.995570 | 1.33 | 35331.57 | 37848.79 | 18924.40 | 18924.40 | 0.751171 | 0.751170 | 0.751170 | 0.751170 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 8.14 | 4.07 | 5.43 | 177800.38 | 187847.59 | 93923.79 | 93923.79 | 0.694865 | 0.694860 | 0.694860 | 0.694860 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.17 | 0.583835 | 0.778447 | 22415.35 | 23909.29 | 11954.65 | 11954.65 | 0.728225 | 0.728220 | 0.728220 | 0.728220 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 0.911720 | 0.455860 | 0.607813 | 18541.40 | 19689.46 | 9844.73 | 9844.73 | 0.712812 | 0.712810 | 0.712810 | 0.712810 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.99 | 2130.61 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 8.14 | 13720.87 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.17 | 1292.79 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.911720 | 1009.42 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.567 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.637 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 18.083 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 21.313 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 18.083 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 39.603 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 18.083 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 21.313 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 9.688 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.688 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2874.639 | 7.567 | 46.863 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2874.639 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 28942.124 | 18.083 | 111.990 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28942.124 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2727.153 | 18.083 | 111.990 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2727.153 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2727.153 | 18.083 | 111.990 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2727.153 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 116.250 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 116.250 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.7800 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9750000 | 3.9750000 | 3.9750000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 9 | -0.41768822E-14 | 0.27520919E-16 | -0.15672466E-09 | 0.83927561E-16 |
25 | 8 | 0.22856702E-07 | 0.10578700E-12 | 0.38803401E-03 | -0.25988854E-09 |
26 | 7 | -0.12546900E-01 | 0.54357740E-08 | -0.23525379E-01 | 0.14266284E-03 |
27 | 6 | 0.41364683 | 0.18861797E-05 | 0.47915075 | -0.48455579E-02 |
28 | 5 | -5.2715232 | 0.70271773E-04 | -4.4954566 | 0.64187715E-01 |
29 | 4 | 33.360936 | 0.57369956E-03 | 21.652120 | -0.42687724 |
30 | 3 | -111.98802 | 0.12481219E-02 | -56.042688 | 1.5262008 |
31 | 2 | 197.88617 | 0.70096321E-03 | 78.258916 | -2.9127067 |
32 | 1 | -171.44340 | 0.74721452E-04 | -55.366563 | 2.7504751 |
33 | 0 | 57.057407 | 0.42462867E-06 | 15.540328 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.61_SHGC_0.25 | 30 | 1 | VerySmooth | 3.468 | 0.253 | 0.159 | 0.251 |
2 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 31 | 1 | VerySmooth | 5.779 | 0.390 | 0.223 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.15839 | 0.59143 | 0.59143 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.67629E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.22227 | 0.21773 | 0.21773 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1915 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2289.08 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 22435.49382 | 26922.59259 | 1.64530 | 1.97436 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 22996.18574 | 27595.42288 | 1.00399 | 1.20478 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 91077.74395 | 109293.29274 | 6.67012 | 8.00414 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 58277.70179 | 69933.24215 | 2.51115 | 3.01338 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 13126.89312 | 15752.27174 | 0.97306 | 1.16767 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 11433.94517 | 13720.73421 | 0.50133 | 0.60159 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 10292.30269 | 12350.76323 | 0.75827 | 0.90993 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 11437.01367 | 13724.41641 | 0.50147 | 0.60176 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40000 | 1.44457E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 34053.37106 | 40864.04527 | 1.51763 | 1.82115 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 26853.75 | 1.99114 | 1.99114 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 34185.06 | 1.20478 | 1.20478 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 120622.89 | 8.14433 | 8.14433 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 127212.71 | 3.01338 | 3.01338 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 16830.98 | 1.16767 | 1.16767 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 19024.24 | 0.60159 | 0.60159 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 13977.71 | 0.91172 | 0.91172 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 19027.90 | 0.60176 | 0.60176 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.97436 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 8.00414 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16767 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.90993 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.82115 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.82115 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 40901.15203 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.97436 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.97436 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.97436 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.97436 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.99114 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.99114 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.99157 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.00414 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 8.00414 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.00414 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 8.00414 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.14433 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 8.14433 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.98279 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16767 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16767 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16767 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16767 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16767 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.16767 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.90993 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.90993 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.90993 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.90993 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.91172 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.91172 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 0.99804 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.99114 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 8.14433 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.16767 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.91172 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.99114 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.99114 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.99114 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.99114 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.31415 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.99114 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.99557 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.32743 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 35331.57234 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 37848.79000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 18924.39500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 18924.39500 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75117 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75117 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75117 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75117 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37848.79000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 51326.46505 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.99114 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2130.61433 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 51326.46505 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.14433 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.14433 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.14433 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.14433 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.37526 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 8.14433 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.07217 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.42955 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 177800.38438 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 187847.59000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 93923.79500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 93923.79500 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69486 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69486 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69486 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69486 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 187847.59000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 238806.68591 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 8.14433 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 13720.87449 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 238806.68591 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16767 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16767 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16767 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16767 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.16767 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16767 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58384 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77845 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22415.35250 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23909.29000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11954.64500 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11954.64500 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72823 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72822 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72822 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72822 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23909.29000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31594.26278 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16767 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1292.79281 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31594.26278 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.91172 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.91172 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.91172 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.91172 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.91172 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.91172 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45586 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.60781 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18541.40345 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19689.46000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9844.73000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9844.73000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71281 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71281 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71281 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71281 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19689.46000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25871.04109 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.91172 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1009.41880 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25871.04109 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 36285.2 | 11.42 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 181431.5 | 12.89 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 22991.3 | 121.22 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 18972.0 | 159.95 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1571.79 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.61_SHGC_0.25 | N/A | 3.468 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.61_SHGC_0.25 | N/A | 3.468 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.61_SHGC_0.25 | N/A | 3.468 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | |
1 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R4C1 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A | |||
2 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R4C2 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A | |||
3 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R4C3 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A | |||
4 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R4C4 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A | |||
5 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C1 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A | |||
6 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C2 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A | |||
7 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C4 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A | |||
8 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C3 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A | |||
9 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C2 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A | |||
10 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C1 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A | |||
11 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C3 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A | |||
12 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C4 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A | |||
13 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R3C2 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A | |||
14 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R3C1 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A | |||
15 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R3C3 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A | |||
16 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R3C4 | Window5 Detailed Fenestration | N/A | N/A | 0.31 | 0.31 | * | N/A | N/A | 6.00E-002 | N/A |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 12 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 5.4167439099E-002 | 0.2313928619 | Pass | Pass | 0.1730729273 | 0.4524322386 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 2.5731345937E-002 | 9.3658167729E-002 | Pass | Pass | 0.1405141618 | 0.4496925760 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 6.8684308711E-002 | 0.2358180279 | Pass | Pass | 0.1339811865 | 0.3805765384 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 6.5978970298E-002 | 0.2817211411 | Pass | Pass | 0.1182293622 | 0.2926387039 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1254212023 | 0.4854330842 | Pass | Pass | 8.5819012596E-002 | 0.5158920326 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1600.48 | 1571.79 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.39 | 1.49 | 0.31 | 0.00 | 1.79 | 1.79 | 5.779 | 0.390 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.61_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 3.468 | 0.253 | 0.251 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.61_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 3.468 | 0.253 | 0.251 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.61_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 3.468 | 0.253 | 0.251 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 112.63 | 4.057 | 0.288 | 0.289 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 112.63 | 4.057 | 0.288 | 0.289 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.5670 | 379.89 | 2874.64 | LightsWired | BLDG_LIGHT_BACK_SCH | 63.14 | 168.00 | 62.27 | 0.0000 | Y | 33.60 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 18.0834 | 1600.48 | 28942.12 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 58.10 | 0.0000 | Y | 315.67 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 18.0834 | 150.81 | 2727.15 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.94 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 18.0834 | 150.81 | 2727.15 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.94 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 9.6875 | 12.00 | 116.25 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 57.54 | 168.00 | 56.76 | 0.0000 | Y | 1.24 |
Interior Lighting Total | 16.2979 | 2293.99 | 37387.32 | 420.40 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 28942.12 | 7235.53 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 28942.12 | 7235.53 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 316.30 | AstronomicalClock | - | 41.77 | 41.77 | 2.48 | |
EXTERIOR_LIGHTS_B | 4328.00 | AstronomicalClock | - | 83.77 | 71.17 | 57.82 | |
Exterior Lighting Total | 4644.30 | 60.30 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 37848.79 | 28430.88 | 9417.91 | 0.75 | 3.80 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 187847.59 | 130527.78 | 57319.81 | 0.69 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 23909.29 | 17411.22 | 6498.07 | 0.73 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 19689.46 | 14034.84 | 5654.62 | 0.71 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 36285.2 | 11.42 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 181431.5 | 12.89 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 22991.3 | 121.22 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 18972.0 | 159.95 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 40901.15 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 51326.47 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 238806.69 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31594.26 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25871.04 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.58 | 622.50 | 1.82 | 1948.72 | 1070.05 | 1.00 | 1.32 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.99 | 2130.61 | 1070.05 | 1.00 | 1.32 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 8.14 | 13720.87 | 1684.71 | 1.00 | 1.15 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.17 | 1292.79 | 1107.16 | 1.00 | 1.37 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.91 | 1009.42 | 1107.16 | 1.00 | 1.43 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 22435.49 | 26922.59 | 70.87 | 1.645 | 1.974 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00966 | 27.37 | 0.01445 | 0.232 | 0.00 |
CORE_RETAIL | 91077.74 | 109293.29 | 68.29 | 6.670 | 8.004 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00959 | 27.37 | 0.01445 | 1.890 | 0.00 |
POINT_OF_SALE | 13126.89 | 15752.27 | 104.45 | 0.973 | 1.168 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00901 | 27.37 | 0.01445 | 0.178 | 0.00 |
FRONT_RETAIL | 10292.30 | 12350.76 | 81.90 | 0.758 | 0.910 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00937 | 27.37 | 0.01445 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 33.79 | 100.00 | 0.00001 | 34.40 | 0.01445 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 22996.19 | 27595.42 | 72.64 | 1.004 | 1.205 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00753 | -6.30 | 0.00230 | 0.232 | 0.00 |
CORE_RETAIL | 58277.70 | 69933.24 | 43.70 | 2.511 | 3.013 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00751 | -6.30 | 0.00230 | 1.890 | 0.00 |
POINT_OF_SALE | 11433.95 | 13720.73 | 90.98 | 0.501 | 0.602 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00771 | -6.30 | 0.00230 | 0.178 | 0.00 |
FRONT_RETAIL | 11437.01 | 13724.42 | 91.00 | 0.501 | 0.602 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00771 | -6.30 | 0.00230 | 0.178 | 0.00 |
FRONT_ENTRY | 34053.37 | 40864.05 | 3405.34 | 1.518 | 1.821 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.03 | 0.00570 | -6.30 | 0.00230 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.99 | 1.99 | 1.20 | 1.20 | 1.9911 | 1.9744 | 1.9911 | 0.9916 | 1.0000 |
PSZ-AC:2 | 8.14 | 8.14 | 3.01 | 3.01 | 8.1443 | 8.0041 | 8.1443 | 0.9828 | 1.0000 |
PSZ-AC:3 | 1.17 | 1.17 | 0.60 | 0.60 | 1.1677 | 1.1677 | 1.1677 | 1.0000 | 1.0000 |
PSZ-AC:4 | 0.91 | 0.91 | 0.60 | 0.60 | 0.9117 | 0.9099 | 0.9117 | 0.9980 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 40901.152 | 40901.152 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 40901.15 | 40901.15 | 1.821154 | 20.82 | 12.21 | 0.00567140 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.03 | 0.00569786 | 35.5802 | 40864.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 18924.395 | 0.000 | 1.991140 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 18924.40 | 14676.66 | 1.991140 | 24.36 | 17.41 | 0.01004447 | 12.80 | 11.77 | 0.00850000 | 27.97 | 0.01444568 | 21.76 | 11.6298 | 23.89 | 0.00965944 | 50.3865 | 22435.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 51326.465 | 51326.465 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 51326.47 | 51326.47 | 1.991140 | 15.68 | 10.96 | 0.00652081 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 11.6298 | 21.11 | 0.00752563 | 46.6296 | 22996.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 93923.795 | 0.000 | 8.144330 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 93923.79 | 70817.70 | 8.144330 | 26.53 | 18.49 | 0.01052112 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01444567 | 23.51 | 23.2089 | 23.89 | 0.00958844 | 50.0209 | 82477.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 238806.686 | 238806.686 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 238806.69 | 238806.69 | 8.144331 | 3.81 | 2.61 | 0.00424208 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 23.2089 | 21.11 | 0.00751418 | 46.5577 | 58277.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 11954.645 | 0.000 | 1.167670 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 11954.65 | 9717.84 | 1.167670 | 25.54 | 17.63 | 0.00983613 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01444567 | 23.51 | 15.2535 | 23.89 | 0.00901064 | 47.0444 | 12397.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 31594.263 | 31594.263 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31594.26 | 31594.26 | 1.167667 | 12.89 | 9.32 | 0.00610548 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 15.2535 | 21.11 | 0.00770694 | 47.7381 | 11433.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 9844.730 | 0.000 | 0.911720 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 9844.73 | 7725.14 | 0.911720 | 25.94 | 18.00 | 0.01013619 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01444567 | 23.51 | 19.5357 | 23.89 | 0.00937022 | 48.8978 | 9982.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 25871.041 | 25871.041 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25871.04 | 25871.04 | 0.911720 | 12.90 | 9.32 | 0.00610608 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 19.5357 | 21.11 | 0.00770716 | 47.7394 | 11437.01 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 40901.152 | 40901.152 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 1.821154 | 2.11431718 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 40901.15 | 40901.15 | 1.0000 | 2.11431718 | 1.821154 | 20.82 | 12.21 | 0.00567140 | 35320.5 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40901.15 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.05 | 0.00569786 | 21.03 | 0.00569786 | 35.5802 | 40864.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18924.395 | 0.000 | 1.991140 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5122 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 18924.40 | 14676.66 | 1.0000 | 2.31166683 | 1.991140 | 24.36 | 17.41 | 0.01004447 | 50053.8 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18924.40 | 27.97 | 0.01444568 | 21.76 | 0.23156651 | 11.6298 | 23.89 | 0.00946526 | 23.89 | 0.00965944 | 50.3865 | 22435.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51326.465 | 51326.465 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.991140 | 2.31166727 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 51326.47 | 51326.47 | 1.0000 | 2.31166727 | 1.991140 | 15.68 | 10.96 | 0.00652081 | 32252.1 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51326.47 | -6.30 | 0.00229779 | -6.30 | 0.23156651 | 11.6298 | 20.91 | 0.00752563 | 21.11 | 0.00752563 | 46.6296 | 22996.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 93923.795 | 0.000 | 8.144330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3982 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 93923.79 | 70817.70 | 1.0000 | 9.45537607 | 8.144330 | 26.53 | 18.49 | 0.01052112 | 53485.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 93923.79 | 34.40 | 0.01444567 | 23.51 | 1.89021192 | 23.2089 | 23.89 | 0.00920649 | 23.89 | 0.00958844 | 50.0209 | 82477.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 238806.686 | 238806.686 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.144331 | 9.45537779 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 238806.69 | 238806.69 | 1.0000 | 9.45537779 | 8.144331 | 3.81 | 2.61 | 0.00424208 | 14471.0 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 238806.69 | -6.30 | 0.00229779 | -6.30 | 1.89021192 | 23.2089 | 20.83 | 0.00751418 | 21.11 | 0.00751418 | 46.5577 | 58277.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11954.645 | 0.000 | 1.167670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.1249 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 11954.65 | 9717.84 | 1.0000 | 1.35563748 | 1.167670 | 25.54 | 17.63 | 0.00983613 | 50731.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11954.65 | 34.40 | 0.01444567 | 23.51 | 0.17811053 | 15.2535 | 23.89 | 0.00897570 | 23.89 | 0.00901064 | 47.0444 | 12397.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31594.263 | 31594.263 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.167667 | 1.35563409 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31594.26 | 31594.26 | 1.0000 | 1.35563409 | 1.167667 | 12.89 | 9.32 | 0.00610548 | 28371.5 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31594.26 | -6.30 | 0.00229779 | -6.30 | 0.17811053 | 15.2535 | 20.97 | 0.00770694 | 21.11 | 0.00770694 | 47.7381 | 11433.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9844.730 | 0.000 | 0.911720 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6827 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 9844.73 | 7725.14 | 1.0000 | 1.05848553 | 0.911720 | 25.94 | 18.00 | 0.01013619 | 51905.9 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9844.73 | 34.40 | 0.01444567 | 23.51 | 0.17811053 | 19.5357 | 23.89 | 0.00908990 | 23.89 | 0.00937022 | 48.8978 | 9982.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25871.041 | 25871.041 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.911720 | 1.05848557 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25871.04 | 25871.04 | 1.0000 | 1.05848557 | 0.911720 | 12.90 | 9.32 | 0.00610608 | 28375.3 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25871.04 | -6.30 | 0.00229779 | -6.30 | 0.17811053 | 19.5357 | 20.97 | 0.00770716 | 21.11 | 0.00770716 | 47.7394 | 11437.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialEnthalpy | 0.23 | 1.99 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialEnthalpy | 1.89 | 8.14 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialEnthalpy | 0.18 | 1.17 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialEnthalpy | 0.18 | 0.91 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 2655.17 | 2594.83 | 896.00 |
CORE_RETAIL | 2554.00 | 2154.17 | 464.67 |
POINT_OF_SALE | 2704.17 | 1777.83 | 335.67 |
FRONT_RETAIL | 2681.83 | 2234.67 | 615.83 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3223.67 | 2714.50 | 1009.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 16.67 | 7.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 21.50 | 0.00 | 0.00 |
POINT_OF_SALE | 8.83 | 91.00 | 0.00 | 0.00 |
FRONT_RETAIL | 14.33 | 29.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 18.83 | 120.67 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.34 | 61.34 | 2317.33 | 0.524 | 0.029 | 0.000 | 0.000 |
CORE_RETAIL | 127.83 | 258.43 | 9762.95 | 0.829 | 0.006 | 0.000 | 0.000 |
POINT_OF_SALE | 12.05 | 24.35 | 919.94 | 1.253 | 0.032 | 0.000 | 0.000 |
FRONT_RETAIL | 12.05 | 24.35 | 919.94 | 1.013 | 0.032 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.34 | 61.34 | 2317.33 | 0.352 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 127.83 | 258.43 | 9762.95 | 0.681 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.05 | 24.35 | 919.94 | 0.681 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.05 | 24.35 | 919.94 | 0.681 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1112.68 | 3650.00 | 19-FEB-08:00 | 100025.34 | 08-JUL-14:30 |
Electricity:Building | 615.03 | 3288.22 | 11-NOV-08:20 | 44140.05 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 83.46 | 599.86 | 01-JAN-00:10 | 5099.20 | 02-JAN-09:10 |
InteriorLights:Electricity | 420.40 | 1507.59 | 11-NOV-08:20 | 33387.34 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 33.60 | 143.73 | 01-JAN-00:10 | 2344.76 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 420.40 | 1507.59 | 11-NOV-08:20 | 33387.34 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 399.75 | 1854.48 | 11-NOV-08:20 | 30692.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 315.68 | 1085.33 | 11-NOV-08:20 | 26047.91 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 87.72 | 619.23 | 01-JAN-00:10 | 5370.36 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 34.94 | 136.36 | 01-JAN-00:10 | 2454.44 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 42.86 | 208.83 | 01-JAN-00:10 | 2892.10 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 34.94 | 136.36 | 01-JAN-00:10 | 2454.44 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.24 | 5.81 | 01-JAN-00:10 | 85.79 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.24 | 5.81 | 01-JAN-00:10 | 85.79 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 194.63 | 1780.63 | 01-JAN-00:10 | 10752.72 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.86 | 456.13 | 01-JAN-00:10 | 2754.45 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 194.63 | 1780.63 | 01-JAN-00:10 | 10752.72 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.07 | 769.15 | 01-JAN-00:10 | 4644.69 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.78 | 482.87 | 01-JAN-00:10 | 2915.92 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.92 | 72.48 | 01-JAN-00:10 | 437.66 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1112.68 | 3650.00 | 19-FEB-08:00 | 100025.34 | 08-JUL-14:30 |
ElectricityPurchased:Plant | 1112.68 | 3650.00 | 19-FEB-08:00 | 100025.34 | 08-JUL-14:30 |
Cogeneration:ElectricityPurchased | 1112.68 | 3650.00 | 19-FEB-08:00 | 100025.34 | 08-JUL-14:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1112.68 | 3650.00 | 19-FEB-08:00 | 100025.34 | 08-JUL-14:30 |
ElectricityNet:Plant | 1112.68 | 3650.00 | 19-FEB-08:00 | 100025.34 | 08-JUL-14:30 |
Cogeneration:ElectricityNet | 1112.68 | 3650.00 | 19-FEB-08:00 | 100025.34 | 08-JUL-14:30 |
Electricity:HVAC | 437.35 | 0.00 | 01-JAN-00:10 | 62397.27 | 08-JUL-14:30 |
Fans:Electricity | 190.01 | 0.00 | 01-JAN-00:10 | 14738.25 | 12-FEB-09:10 |
General:Fans:Electricity | 190.01 | 0.00 | 01-JAN-00:10 | 14738.25 | 12-FEB-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 247.35 | 0.00 | 01-JAN-00:10 | 51094.15 | 08-JUL-14:40 |
ExteriorLights:Electricity | 60.30 | 0.00 | 01-JAN-07:50 | 4644.30 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.30 | 0.00 | 01-JAN-07:50 | 4644.30 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 254.44 | 1860.00 | 07-JAN-22:10 | 194386.13 | 12-FEB-09:10 |
Gas:Plant | 91.28 | 1860.00 | 07-JAN-22:10 | 5043.86 | 03-FEB-13:00 |
WaterSystems:Gas | 91.28 | 1860.00 | 07-JAN-22:10 | 5043.86 | 03-FEB-13:00 |
Water Heater:WaterSystems:Gas | 91.28 | 1860.00 | 07-JAN-22:10 | 5043.86 | 03-FEB-13:00 |
Gas:HVAC | 163.16 | 0.00 | 01-JAN-00:10 | 189840.43 | 12-FEB-09:10 |
Heating:Gas | 163.16 | 0.00 | 01-JAN-00:10 | 189840.43 | 12-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1825.81 | 0.00 | 01-JAN-00:10 | 259349.13 | 08-JUL-14:20 |
EnergyTransfer:Building | 764.06 | 0.00 | 01-JAN-00:10 | 105991.83 | 12-FEB-09:10 |
EnergyTransfer:Zone:BACK_SPACE | 101.69 | 0.00 | 01-JAN-00:10 | 42750.98 | 12-FEB-07:10 |
Heating:EnergyTransfer | 71.42 | 0.00 | 01-JAN-00:10 | 104654.39 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 13.71 | 0.00 | 01-JAN-00:10 | 42750.98 | 12-FEB-07:10 |
Cooling:EnergyTransfer | 692.63 | 0.00 | 01-JAN-00:10 | 87176.63 | 10-JUN-21:40 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 87.98 | 0.00 | 01-JAN-00:10 | 13757.66 | 08-JUL-16:00 |
EnergyTransfer:Zone:CORE_RETAIL | 475.95 | 0.00 | 01-JAN-00:10 | 75843.11 | 13-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 8.88 | 0.00 | 01-JAN-00:10 | 67818.33 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 467.07 | 0.00 | 01-JAN-00:10 | 71311.96 | 09-MAY-20:30 |
EnergyTransfer:Zone:POINT_OF_SALE | 86.58 | 0.00 | 01-JAN-00:10 | 18754.94 | 12-FEB-07:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 2.93 | 0.00 | 01-JAN-00:10 | 18754.94 | 12-FEB-07:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 83.65 | 0.00 | 01-JAN-00:10 | 12314.60 | 11-OCT-21:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 58.92 | 0.00 | 01-JAN-00:10 | 19724.36 | 12-FEB-07:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 4.99 | 0.00 | 01-JAN-00:10 | 19724.36 | 12-FEB-07:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 53.93 | 0.00 | 01-JAN-00:10 | 10051.63 | 11-OCT-21:30 |
EnergyTransfer:Zone:FRONT_ENTRY | 40.92 | 0.00 | 01-JAN-00:10 | 32050.27 | 07-JAN-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 40.91 | 0.00 | 01-JAN-00:10 | 32050.27 | 07-JAN-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 93.18 | 16-JAN-07:10 |
EnergyTransfer:HVAC | 1061.75 | 0.00 | 01-JAN-00:10 | 177766.27 | 08-JUL-14:10 |
HeatingCoils:EnergyTransfer | 130.52 | 0.00 | 01-JAN-00:10 | 151872.35 | 12-FEB-09:10 |
CoolingCoils:EnergyTransfer | 931.23 | 0.00 | 01-JAN-00:10 | 177766.27 | 08-JUL-14:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 13.709 | -87.978 | 0.000 | 0.000 | 38.309 | 33.603 | 49.857 | 0.000 | 0.000 | 0.645 | 0.000 | 0.000 | 0.000 | 0.000 | -11.340 | -36.804 |
CORE_RETAIL | 0.000 | 0.000 | 8.881 | -467.068 | 0.000 | 0.000 | 160.644 | 315.675 | 84.072 | 47.002 | 0.000 | 0.528 | 0.000 | 0.000 | -26.577 | 0.000 | -10.022 | -113.136 |
POINT_OF_SALE | 0.000 | 0.000 | 2.926 | -83.650 | 0.000 | 0.000 | 14.845 | 34.941 | 52.780 | 26.966 | 0.000 | 0.278 | 0.000 | 0.000 | -19.487 | 0.000 | -5.262 | -24.337 |
FRONT_RETAIL | 0.000 | 0.000 | 4.994 | -53.928 | 0.000 | 0.000 | 15.084 | 34.941 | 7.922 | 27.139 | 0.000 | 0.279 | 0.001 | 0.000 | -18.751 | 0.000 | -5.025 | -12.657 |
FRONT_ENTRY | 40.913 | -0.002 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.239 | 0.000 | 5.253 | 0.000 | 0.936 | 0.000 | 0.000 | -3.840 | 0.000 | -43.604 | -0.896 |
Total Facility | 40.913 | -0.002 | 30.511 | -692.624 | 0.000 | 0.000 | 228.882 | 420.398 | 194.630 | 106.361 | 0.000 | 2.666 | 0.001 | 0.000 | -68.656 | 0.000 | -75.252 | -187.828 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 10-JUN-22:48 | 0.00 | 0.00 | 0.00 | -37974.45 | 0.00 | 0.00 | 0.00 | 143.73 | 456.13 | 0.00 | 0.00 | 0.00 | 37432.11 | 0.00 | -0.00 | 0.00 | -57.52 | 0.00 |
CORE_RETAIL | 10-JUN-22:41 | 0.00 | 0.00 | 0.00 | -178154.51 | 0.00 | 0.00 | 0.00 | 1447.11 | 769.15 | 0.00 | 0.00 | 0.00 | 177285.06 | 0.00 | -1300.47 | 0.00 | -46.34 | 0.00 |
POINT_OF_SALE | 11-OCT-21:25 | 0.00 | 0.00 | 0.00 | -24625.08 | 0.00 | 0.00 | 0.00 | 136.36 | 643.83 | 0.00 | 0.00 | 0.00 | 25284.22 | 0.00 | -1234.86 | 0.00 | -204.47 | 0.00 |
FRONT_RETAIL | 26-FEB-19:31 | 0.00 | 0.00 | 0.00 | -20195.86 | 0.00 | 0.00 | 0.00 | 136.36 | 72.48 | 0.00 | 0.00 | 0.00 | 20818.01 | 0.00 | -756.18 | 0.00 | -74.80 | 0.00 |
FRONT_ENTRY | 16-JAN-07:02 | 0.00 | -931.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.23 | 0.00 | -425.15 | 0.00 | -107.06 | 0.00 |
Total Facility | 09-JUN-20:11 | 0.00 | 0.00 | 0.00 | -202431.09 | 0.00 | 0.00 | 0.00 | 7477.46 | 2374.18 | 0.00 | 0.00 | 91.48 | 194273.27 | 0.00 | -1776.28 | 0.00 | -9.02 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 05-FEB-07:42 | 0.00 | 0.00 | 53487.56 | 0.00 | 0.00 | 0.00 | 0.00 | 143.73 | 456.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1991.36 | -52096.06 |
CORE_RETAIL | 13-FEB-06:01 | 0.00 | 0.00 | 243591.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1447.11 | 1025.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3255.87 | 0.00 | -801.59 | -242006.28 |
POINT_OF_SALE | 12-FEB-07:31 | 0.00 | 0.00 | 33398.77 | 0.00 | 0.00 | 0.00 | 0.00 | 136.36 | 482.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2748.25 | 0.00 | -1883.69 | -29386.06 |
FRONT_RETAIL | 05-FEB-07:42 | 0.00 | 0.00 | 26575.21 | 0.00 | 0.00 | 0.00 | 0.00 | 136.36 | 72.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2037.22 | 0.00 | -872.72 | -23874.11 |
FRONT_ENTRY | 07-JAN-18:00 | 32049.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -543.06 | 0.00 | -31545.92 | -46.02 |
Total Facility | 12-FEB-08:61 | 6221.80 | 0.00 | 311881.03 | 0.00 | 0.00 | 0.00 | 0.00 | 1869.37 | 1780.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7744.56 | 0.00 | -8277.58 | -305730.69 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.9744 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.9911 | 0.1163 | 1.0000 | 0.2316 | 0.1163 | ||
PSZ-AC:2 | 8.0041 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.1443 | 0.2321 | 1.0000 | 1.8902 | 0.2321 | ||
PSZ-AC:3 | 1.1677 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1677 | 0.1525 | 1.0000 | 0.1781 | 0.1525 | ||
PSZ-AC:4 | 0.9099 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.9117 | 0.1954 | 1.0000 | 0.1781 | 0.1954 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.9744 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.9744 | 1.0000 | 1.0000 | 0.2316 | 0.1173 | ||
PSZ-AC:2 | 8.0041 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.0041 | 1.0000 | 1.0000 | 1.8902 | 0.2362 | ||
PSZ-AC:3 | 1.1677 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1677 | 1.0000 | 1.0000 | 0.1781 | 0.1525 | ||
PSZ-AC:4 | 0.9099 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.9099 | 1.0000 | 1.0000 | 0.1781 | 0.1957 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.9744 | 1.9744 | 1.9744 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.0041 | 8.0041 | 8.0041 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1677 | 1.1677 | 1.1677 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.9099 | 0.9099 | 0.9099 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.9744 | 1.9911 | 1.9744 | 1.9744 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.0041 | 8.1443 | 8.0041 | 8.0041 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1677 | 1.1677 | 1.1677 | 1.1677 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.9099 | 0.9117 | 0.9099 | 0.9099 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.9744 | 1.9744 | 1.9744 | 0.2316 | 0.1922 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.0041 | 8.0041 | 8.0041 | 1.8902 | 0.6273 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1677 | 1.1677 | 1.1677 | 0.1781 | 0.2961 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.9099 | 0.9099 | 0.9099 | 0.1781 | 0.2960 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.9744 | 1.9744 | 1.9744 | 1.9744 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.0041 | 8.0041 | 8.0041 | 8.0041 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1677 | 1.1677 | 1.1677 | 1.1677 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.9099 | 0.9099 | 0.9099 | 0.9099 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:38
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 163.16 | 189840.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 247.35 | 51094.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 420.40 | 33387.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.30 | 4644.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 194.63 | 10752.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 190.01 | 14738.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 91.28 | 5043.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 194.63 | 1112.68 |
Natural Gas | 0.00 | 254.44 |
Additional | 0.00 | 0.00 |
Total | 194.63 | 1367.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 183.26 |
Space Heating | 0.00 |
Space Cooling | 107.82 |
Fans (All) | 82.83 |
Service Water Heating | 0.00 |
Receptacle Equipment | 84.84 |
Miscellaneous (All) | 485.04 |
Subtotal | 485.04 |
Natural Gas [MJ/m2] | |
Space Heating | 71.12 |
Service Water Heating | 39.79 |
Miscellaneous (All) | 110.91 |
Subtotal | 110.91 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 30.75 |
Space Heating | 11.93 |
Space Cooling | 18.09 |
Fans (All) | 13.90 |
Service Water Heating | 6.68 |
Receptacle Equipment | 14.24 |
Miscellaneous | 4.41 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3292. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3001. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4559. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_SETBACK | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_SCH_PSZ_AC_2 | CORE_RETAIL DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.740483E+11 |
February | 0.000 | 0.404114E+11 |
March | 0.000 | 0.573920E+10 |
April | 0.000 | 0.132837E+10 |
May | 0.000 | 0.152660E+08 |
June | 0.000 | 539981.400 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.380022E+08 |
October | 0.000 | 0.142773E+10 |
November | 0.000 | 0.759239E+10 |
December | 0.000 | 0.325541E+11 |
Annual Sum or Average | 0.163155E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.740483E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.740483E+11 |
February | 0.000 | 0.404114E+11 |
March | 0.000 | 0.573920E+10 |
April | 0.000 | 0.132837E+10 |
May | 0.000 | 0.152660E+08 |
June | 0.000 | 539981.400 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.380022E+08 |
October | 0.000 | 0.142773E+10 |
November | 0.000 | 0.759239E+10 |
December | 0.000 | 0.325541E+11 |
Annual Sum or Average | 0.163155E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.740483E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.740483E+11 |
February | 0.000 | 0.404114E+11 |
March | 0.000 | 0.573920E+10 |
April | 0.000 | 0.132837E+10 |
May | 0.000 | 0.152660E+08 |
June | 0.000 | 539981.400 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.380022E+08 |
October | 0.000 | 0.142773E+10 |
November | 0.000 | 0.759239E+10 |
December | 0.000 | 0.325541E+11 |
Annual Sum or Average | 0.163155E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.740483E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.740483E+11 |
February | 0.000 | 0.404114E+11 |
March | 0.000 | 0.573920E+10 |
April | 0.000 | 0.132837E+10 |
May | 0.000 | 0.152660E+08 |
June | 0.000 | 539981.400 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.380022E+08 |
October | 0.000 | 0.142773E+10 |
November | 0.000 | 0.759239E+10 |
December | 0.000 | 0.325541E+11 |
Annual Sum or Average | 0.163155E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.740483E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.740483E+11 |
February | 0.000 | 0.404114E+11 |
March | 0.000 | 0.573920E+10 |
April | 0.000 | 0.132837E+10 |
May | 0.000 | 0.152660E+08 |
June | 0.000 | 539981.400 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.380022E+08 |
October | 0.000 | 0.142773E+10 |
November | 0.000 | 0.759239E+10 |
December | 0.000 | 0.325541E+11 |
Annual Sum or Average | 0.163155E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.740483E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.740483E+11 |
February | 0.000 | 0.404114E+11 |
March | 0.000 | 0.573920E+10 |
April | 0.000 | 0.132837E+10 |
May | 0.000 | 0.152660E+08 |
June | 0.000 | 539981.400 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.380022E+08 |
October | 0.000 | 0.142773E+10 |
November | 0.000 | 0.759239E+10 |
December | 0.000 | 0.325541E+11 |
Annual Sum or Average | 0.163155E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.740483E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.740483E+11 |
February | 0.000 | 0.404114E+11 |
March | 0.000 | 0.573920E+10 |
April | 0.000 | 0.132837E+10 |
May | 0.000 | 0.152660E+08 |
June | 0.000 | 539981.400 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.380022E+08 |
October | 0.000 | 0.142773E+10 |
November | 0.000 | 0.759239E+10 |
December | 0.000 | 0.325541E+11 |
Annual Sum or Average | 0.163155E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.740483E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.740483E+11 |
February | 0.000 | 0.404114E+11 |
March | 0.000 | 0.573920E+10 |
April | 0.000 | 0.132837E+10 |
May | 0.000 | 0.152660E+08 |
June | 0.000 | 539981.400 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.380022E+08 |
October | 0.000 | 0.142773E+10 |
November | 0.000 | 0.759239E+10 |
December | 0.000 | 0.325541E+11 |
Annual Sum or Average | 0.163155E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.740483E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.740483E+11 |
February | 0.000 | 0.404114E+11 |
March | 0.000 | 0.573920E+10 |
April | 0.000 | 0.132837E+10 |
May | 0.000 | 0.152660E+08 |
June | 0.000 | 539981.400 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.380022E+08 |
October | 0.000 | 0.142773E+10 |
November | 0.000 | 0.759239E+10 |
December | 0.000 | 0.325541E+11 |
Annual Sum or Average | 0.163155E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.740483E+11 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.533188E+09 | 4508.57 | 26-JAN-13:15 | 0.00 | -3.7 | 0.169418E+10 | 2450.89 | 20-JAN-15:00 | 17.20 | 12.76 |
February | 0.109873E+10 | 4653.56 | 02-FEB-10:25 | -0.6 | -2.3 | 0.166425E+10 | 2451.26 | 22-FEB-15:00 | 14.40 | 13.41 |
March | 0.325740E+10 | 20246.97 | 30-MAR-22:43 | 21.88 | 15.92 | 0.212364E+10 | 2451.29 | 11-MAR-13:39 | 24.43 | 15.65 |
April | 0.504123E+10 | 28094.12 | 17-APR-20:51 | 20.00 | 14.11 | 0.211776E+10 | 2451.30 | 28-APR-14:00 | 25.60 | 15.82 |
May | 0.896999E+10 | 34054.44 | 14-MAY-18:35 | 23.73 | 14.24 | 0.222848E+10 | 2451.23 | 12-MAY-14:09 | 23.90 | 15.17 |
June | 0.140472E+11 | 37974.54 | 10-JUN-22:48 | 21.10 | 11.81 | 0.220145E+10 | 2451.22 | 09-JUN-14:09 | 29.90 | 18.88 |
July | 0.159811E+11 | 27245.54 | 16-JUL-18:10 | 32.52 | 22.44 | 0.218725E+10 | 2451.23 | 22-JUL-11:20 | 32.40 | 24.10 |
August | 0.169152E+11 | 26713.17 | 01-AUG-20:10 | 25.97 | 22.54 | 0.228101E+10 | 2451.24 | 26-AUG-10:20 | 27.77 | 20.59 |
September | 0.112694E+11 | 34986.59 | 13-SEP-20:18 | 18.13 | 14.00 | 0.215588E+10 | 2451.32 | 28-SEP-14:09 | 19.40 | 18.21 |
October | 0.603043E+10 | 24076.37 | 16-OCT-20:52 | 21.10 | 17.79 | 0.213844E+10 | 2451.25 | 21-OCT-10:09 | 16.57 | 11.72 |
November | 0.312911E+10 | 6365.23 | 04-NOV-16:00 | 21.10 | 18.17 | 0.193453E+10 | 2451.25 | 04-NOV-10:09 | 16.70 | 16.44 |
December | 0.170671E+10 | 4321.61 | 13-DEC-16:00 | 17.20 | 16.88 | 0.178202E+10 | 2451.21 | 14-DEC-15:09 | 15.00 | 10.57 |
Annual Sum or Average | 0.879796E+11 | 0.245089E+11 | ||||||||
Minimum of Months | 0.533188E+09 | 4321.61 | -0.6 | -3.7 | 0.166425E+10 | 2450.89 | 14.40 | 10.57 | ||
Maximum of Months | 0.169152E+11 | 37974.54 | 32.52 | 22.54 | 0.228101E+10 | 2451.32 | 32.40 | 24.10 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159957E+11 | 56831.64 | 27-JAN-07:05 | -6.7 | -7.8 | 0.722885E+10 | 10327.19 | 31-JAN-15:00 | 20.00 | 13.57 |
February | 0.185333E+11 | 166302.58 | 28-FEB-21:41 | 19.18 | 11.08 | 0.716128E+10 | 10328.03 | 22-FEB-15:30 | 17.20 | 13.31 |
March | 0.310648E+11 | 153329.19 | 13-MAR-20:23 | 21.95 | 14.52 | 0.913788E+10 | 10327.56 | 11-MAR-11:20 | 19.43 | 13.14 |
April | 0.362689E+11 | 161357.62 | 14-APR-20:16 | 20.73 | 13.65 | 0.897206E+10 | 10327.46 | 07-APR-14:09 | 22.57 | 13.55 |
May | 0.478176E+11 | 166430.21 | 13-MAY-21:31 | 16.13 | 11.09 | 0.938924E+10 | 10327.17 | 20-MAY-15:00 | 26.70 | 19.02 |
June | 0.579164E+11 | 178155.43 | 10-JUN-22:41 | 21.10 | 11.81 | 0.927299E+10 | 10327.32 | 09-JUN-14:09 | 29.90 | 18.88 |
July | 0.610494E+11 | 124480.49 | 28-JUL-21:52 | 17.80 | 17.48 | 0.921488E+10 | 10327.11 | 15-JUL-11:20 | 31.67 | 24.59 |
August | 0.634379E+11 | 119537.70 | 18-AUG-20:10 | 31.60 | 22.39 | 0.960992E+10 | 10327.12 | 26-AUG-11:20 | 29.47 | 21.46 |
September | 0.482283E+11 | 161319.07 | 14-SEP-20:55 | 20.00 | 13.68 | 0.907850E+10 | 10327.32 | 15-SEP-14:09 | 28.48 | 18.73 |
October | 0.378853E+11 | 152879.09 | 22-OCT-18:41 | 19.18 | 13.80 | 0.900937E+10 | 10327.30 | 04-OCT-14:09 | 19.68 | 12.49 |
November | 0.271472E+11 | 108319.38 | 03-NOV-23:52 | 18.30 | 16.17 | 0.823210E+10 | 10327.20 | 04-NOV-10:09 | 16.70 | 16.44 |
December | 0.217281E+11 | 53337.93 | 18-DEC-07:05 | -5.1 | -6.8 | 0.769969E+10 | 10327.35 | 13-DEC-15:00 | 17.20 | 16.88 |
Annual Sum or Average | 0.467073E+12 | 0.104007E+12 | ||||||||
Minimum of Months | 0.159957E+11 | 53337.93 | -6.7 | -7.8 | 0.716128E+10 | 10327.11 | 16.70 | 12.49 | ||
Maximum of Months | 0.634379E+11 | 178155.43 | 31.60 | 22.39 | 0.960992E+10 | 10328.03 | 31.67 | 24.59 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250352E+10 | 4169.19 | 28-JAN-15:00 | 12.20 | 4.53 | 0.752228E+09 | 973.14 | 31-JAN-15:00 | 20.00 | 13.57 |
February | 0.312505E+10 | 24210.12 | 28-FEB-21:11 | 20.03 | 11.49 | 0.715828E+09 | 973.23 | 22-FEB-15:30 | 17.20 | 13.31 |
March | 0.514178E+10 | 21992.01 | 26-MAR-18:35 | 19.27 | 9.12 | 0.886094E+09 | 973.14 | 04-MAR-14:50 | 23.03 | 16.31 |
April | 0.569602E+10 | 22457.31 | 12-APR-22:41 | 18.22 | 12.93 | 0.850469E+09 | 973.14 | 21-APR-14:50 | 22.80 | 18.72 |
May | 0.752371E+10 | 24392.18 | 13-MAY-21:31 | 16.13 | 11.09 | 0.885707E+09 | 973.17 | 24-MAY-14:00 | 18.30 | 17.53 |
June | 0.992790E+10 | 24052.56 | 11-JUN-00:31 | 19.80 | 11.48 | 0.873972E+09 | 973.11 | 17-JUN-10:09 | 27.38 | 22.18 |
July | 0.111045E+11 | 16434.27 | 07-JUL-20:08 | 31.02 | 23.13 | 0.868315E+09 | 973.14 | 29-JUL-10:30 | 18.85 | 18.85 |
August | 0.124521E+11 | 16600.46 | 18-AUG-20:08 | 31.60 | 22.39 | 0.905531E+09 | 973.12 | 26-AUG-10:09 | 27.48 | 20.44 |
September | 0.974269E+10 | 21224.22 | 14-SEP-20:55 | 20.00 | 13.68 | 0.856031E+09 | 973.16 | 21-SEP-14:00 | 22.80 | 20.14 |
October | 0.760541E+10 | 24629.20 | 11-OCT-21:25 | 15.25 | 9.29 | 0.861692E+09 | 973.16 | 05-OCT-14:00 | 20.60 | 15.45 |
November | 0.531221E+10 | 19591.81 | 02-NOV-21:53 | 16.10 | 14.10 | 0.819226E+09 | 973.15 | 01-NOV-14:00 | 20.60 | 15.19 |
December | 0.351698E+10 | 18149.62 | 12-DEC-22:00 | 18.30 | 14.61 | 0.817500E+09 | 973.23 | 11-DEC-15:00 | 21.10 | 15.90 |
Annual Sum or Average | 0.836519E+11 | 0.100926E+11 | ||||||||
Minimum of Months | 0.250352E+10 | 4169.19 | 12.20 | 4.53 | 0.715828E+09 | 973.11 | 17.20 | 13.31 | ||
Maximum of Months | 0.124521E+11 | 24629.20 | 31.60 | 23.13 | 0.905531E+09 | 973.23 | 27.48 | 22.18 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120192E+10 | 3473.33 | 05-JAN-10:03 | -2.0 | -5.4 | 0.697654E+09 | 973.11 | 31-JAN-15:00 | 20.00 | 13.57 |
February | 0.156482E+10 | 20195.85 | 26-FEB-19:31 | 20.00 | 10.70 | 0.678177E+09 | 973.11 | 22-FEB-15:50 | 15.33 | 13.46 |
March | 0.278737E+10 | 16961.89 | 13-MAR-21:11 | 20.93 | 14.31 | 0.857382E+09 | 973.13 | 08-MAR-15:09 | 24.32 | 16.06 |
April | 0.319284E+10 | 17511.60 | 14-APR-20:17 | 20.73 | 13.65 | 0.838321E+09 | 973.13 | 20-APR-14:09 | 23.90 | 16.58 |
May | 0.457150E+10 | 16466.72 | 14-MAY-18:20 | 24.67 | 14.57 | 0.883195E+09 | 973.12 | 12-MAY-14:09 | 23.90 | 15.17 |
June | 0.683905E+10 | 18998.33 | 10-JUN-21:21 | 21.65 | 12.05 | 0.873689E+09 | 973.12 | 17-JUN-15:00 | 25.60 | 22.49 |
July | 0.792609E+10 | 13349.80 | 16-JUL-18:08 | 32.52 | 22.44 | 0.868306E+09 | 973.13 | 29-JUL-10:00 | 19.40 | 19.40 |
August | 0.911922E+10 | 13293.83 | 18-AUG-20:08 | 31.60 | 22.39 | 0.905527E+09 | 973.12 | 31-AUG-14:09 | 23.90 | 20.77 |
September | 0.669072E+10 | 17476.62 | 14-SEP-20:48 | 20.28 | 13.79 | 0.855488E+09 | 973.20 | 28-SEP-14:09 | 19.40 | 18.21 |
October | 0.495204E+10 | 20103.26 | 11-OCT-21:25 | 15.25 | 9.29 | 0.846734E+09 | 973.15 | 05-OCT-14:00 | 20.60 | 15.45 |
November | 0.314356E+10 | 16031.81 | 02-NOV-20:22 | 17.50 | 14.61 | 0.790790E+09 | 973.14 | 01-NOV-14:30 | 20.60 | 15.05 |
December | 0.193977E+10 | 14734.88 | 12-DEC-21:45 | 18.30 | 14.61 | 0.757822E+09 | 973.13 | 11-DEC-15:30 | 21.10 | 15.19 |
Annual Sum or Average | 0.539289E+11 | 0.985308E+10 | ||||||||
Minimum of Months | 0.120192E+10 | 3473.33 | -2.0 | -5.4 | 0.678177E+09 | 973.11 | 15.33 | 13.46 | ||
Maximum of Months | 0.911922E+10 | 20195.85 | 32.52 | 22.44 | 0.905527E+09 | 973.20 | 25.60 | 22.49 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 877320.48 | 931.82 | 16-JAN-07:02 | -2.8 | -4.7 | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 |
February | 450201.45 | 907.26 | 04-FEB-05:02 | -5.7 | -7.6 | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 | 18.59 | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.28 | 21.38 | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 | 21.87 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 | 18.45 | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.45 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 16.85 | 15.92 | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 |
November | 18260.03 | 165.22 | 21-NOV-05:02 | -2.3 | -3.5 | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.59 |
December | 275620.38 | 705.39 | 26-DEC-05:02 | 3.80 | 2.84 | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 |
Annual Sum or Average | 1621402.34 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -5.7 | -7.6 | 0.00 | 0.00 | 1.80 | 1.51 | ||
Maximum of Months | 877320.48 | 931.82 | 25.13 | 21.87 | 0.00 | 0.00 | 25.13 | 21.87 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.616542E+10 | 52641.10 | 08-JAN-07:12 | -4.8 |
February | 0.354912E+10 | 53487.37 | 05-FEB-07:42 | -6.7 |
March | 0.435426E+09 | 51698.10 | 23-MAR-04:01 | 5.18 |
April | 0.118059E+09 | 28715.14 | 07-APR-04:03 | 3.80 |
May | 38245248.92 | 1128.98 | 20-MAY-05:05 | 17.38 |
June | 11853237.77 | 1132.59 | 15-JUN-05:10 | 22.20 |
July | 7609083.93 | 1378.47 | 24-JUL-05:05 | 20.60 |
August | 3964477.81 | 1384.69 | 25-AUG-05:05 | 19.22 |
September | 14972517.48 | 1138.25 | 27-SEP-05:10 | 22.80 |
October | 78881374.66 | 15403.73 | 26-OCT-05:02 | 2.20 |
November | 0.554922E+09 | 51916.59 | 22-NOV-05:01 | -2.9 |
December | 0.273025E+10 | 52347.00 | 18-DEC-05:42 | -5.0 |
Annual Sum or Average | 0.137087E+11 | |||
Minimum of Months | 3964477.81 | 1128.98 | -6.7 | |
Maximum of Months | 0.616542E+10 | 53487.37 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.378525E+10 | 243401.18 | 09-JAN-06:01 | -2.4 |
February | 0.208805E+10 | 243591.08 | 13-FEB-06:01 | -5.6 |
March | 0.467361E+09 | 8409.39 | 19-MAR-08:10 | 4.27 |
April | 0.243437E+09 | 6853.53 | 18-APR-05:03 | 14.22 |
May | 98256019.03 | 7091.75 | 21-MAY-07:03 | 16.97 |
June | 53931833.24 | 7520.69 | 15-JUN-05:05 | 22.20 |
July | 40671471.18 | 6607.81 | 29-JUL-05:07 | 17.80 |
August | 15930721.30 | 7810.40 | 25-AUG-05:05 | 19.22 |
September | 93404948.14 | 6945.73 | 24-SEP-07:03 | 17.85 |
October | 0.200254E+09 | 6449.53 | 17-OCT-05:07 | 16.60 |
November | 0.526072E+09 | 44928.09 | 22-NOV-07:03 | -3.2 |
December | 0.126884E+10 | 163755.55 | 04-DEC-07:03 | -3.3 |
Annual Sum or Average | 0.888145E+10 | |||
Minimum of Months | 15930721.30 | 6449.53 | -5.6 | |
Maximum of Months | 0.378525E+10 | 243591.08 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125705E+10 | 31941.71 | 08-JAN-07:12 | -4.8 |
February | 0.760228E+09 | 33398.72 | 12-FEB-07:31 | -12.4 |
March | 0.129879E+09 | 31316.85 | 23-MAR-04:01 | 5.18 |
April | 77822103.43 | 5886.66 | 06-APR-04:37 | 0.37 |
May | 26539919.44 | 1484.60 | 20-MAY-05:05 | 17.38 |
June | 4729716.52 | 1555.17 | 04-JUN-07:00 | 20.00 |
July | 770122.92 | 1419.43 | 02-JUL-07:05 | 20.37 |
August | 461222.05 | 500.35 | 20-AUG-07:10 | 23.98 |
September | 6120267.83 | 1539.39 | 24-SEP-07:03 | 17.85 |
October | 43924873.38 | 1423.90 | 05-OCT-05:03 | 12.52 |
November | 0.138693E+09 | 31502.06 | 22-NOV-05:01 | -2.9 |
December | 0.479984E+09 | 31652.28 | 03-DEC-07:01 | -3.4 |
Annual Sum or Average | 0.292620E+10 | |||
Minimum of Months | 461222.05 | 500.35 | -12.4 | |
Maximum of Months | 0.125705E+10 | 33398.72 | 23.98 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210862E+10 | 26399.80 | 08-JAN-07:12 | -4.8 |
February | 0.124143E+10 | 26575.15 | 05-FEB-07:42 | -6.7 |
March | 0.228020E+09 | 25872.77 | 23-MAR-04:01 | 5.18 |
April | 0.129342E+09 | 22425.60 | 06-APR-04:02 | 0.92 |
May | 51128771.38 | 1150.32 | 19-MAY-05:05 | 16.60 |
June | 13435239.77 | 1101.15 | 18-JUN-07:05 | 20.10 |
July | 2761989.90 | 984.89 | 23-JUL-07:07 | 22.48 |
August | 1326774.64 | 1046.88 | 27-AUG-07:05 | 21.38 |
September | 10774027.18 | 1218.62 | 05-SEP-05:05 | 21.70 |
October | 78675117.19 | 8897.78 | 31-OCT-04:03 | 8.80 |
November | 0.221390E+09 | 25992.75 | 22-NOV-05:01 | -2.9 |
December | 0.907538E+09 | 26089.46 | 03-DEC-07:01 | -3.4 |
Annual Sum or Average | 0.499444E+10 | |||
Minimum of Months | 1326774.64 | 984.89 | -6.7 | |
Maximum of Months | 0.210862E+10 | 26575.15 | 22.48 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130072E+11 | 32050.27 | 07-JAN-18:00 | -5.0 |
February | 0.803879E+10 | 32023.71 | 11-FEB-18:00 | -5.0 |
March | 0.381406E+10 | 19428.46 | 22-MAR-11:10 | 4.40 |
April | 0.129789E+10 | 14980.45 | 05-APR-11:05 | 8.17 |
May | 0.185746E+09 | 4171.00 | 10-MAY-11:10 | 17.30 |
June | 8617008.67 | 1612.97 | 10-JUN-07:36 | 15.37 |
July | 60613522.82 | 2443.68 | 28-JUL-11:10 | 19.40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.160212E+09 | 3759.43 | 28-SEP-17:00 | 17.20 |
October | 0.192606E+10 | 13572.68 | 25-OCT-11:05 | 9.18 |
November | 0.390693E+10 | 19634.95 | 20-NOV-12:10 | 3.98 |
December | 0.850742E+10 | 23744.62 | 17-DEC-18:00 | 1.10 |
Annual Sum or Average | 0.409135E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.130072E+11 | 32050.27 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.281822E+10 | 2344.76 | 02-JAN-09:09 | 0.420015E+10 | 2754.45 | 02-JAN-09:09 |
February | 0.256399E+10 | 2344.76 | 01-FEB-09:09 | 0.381055E+10 | 2754.45 | 01-FEB-09:09 |
March | 0.292411E+10 | 2344.76 | 01-MAR-09:09 | 0.430594E+10 | 2754.45 | 01-MAR-09:09 |
April | 0.275920E+10 | 2344.76 | 01-APR-09:09 | 0.409182E+10 | 2754.45 | 01-APR-09:09 |
May | 0.287117E+10 | 2344.76 | 01-MAY-08:09 | 0.425304E+10 | 2754.45 | 01-MAY-08:09 |
June | 0.282172E+10 | 2344.76 | 01-JUN-08:09 | 0.415844E+10 | 2754.45 | 01-JUN-08:09 |
July | 0.280865E+10 | 2344.76 | 01-JUL-09:09 | 0.418643E+10 | 2754.45 | 01-JUL-09:09 |
August | 0.292411E+10 | 2344.76 | 01-AUG-08:09 | 0.430594E+10 | 2754.45 | 01-AUG-08:09 |
September | 0.275920E+10 | 2344.76 | 01-SEP-08:09 | 0.409182E+10 | 2754.45 | 01-SEP-08:09 |
October | 0.281822E+10 | 2344.76 | 02-OCT-08:09 | 0.420015E+10 | 2754.45 | 02-OCT-08:09 |
November | 0.272540E+10 | 2344.76 | 01-NOV-08:09 | 0.406638E+10 | 2754.45 | 01-NOV-08:09 |
December | 0.280865E+10 | 2344.76 | 01-DEC-09:09 | 0.418643E+10 | 2754.45 | 01-DEC-09:09 |
Annual Sum or Average | 0.336027E+11 | 0.498571E+11 | ||||
Minimum of Months | 0.256399E+10 | 2344.76 | 0.381055E+10 | 2754.45 | ||
Maximum of Months | 0.292411E+10 | 2344.76 | 0.430594E+10 | 2754.45 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.293831E+11 | 26047.91 | 02-JAN-09:09 | 0.708251E+10 | 4644.69 | 02-JAN-09:09 |
February | 0.262758E+11 | 26047.91 | 01-FEB-09:09 | 0.642555E+10 | 4644.69 | 01-FEB-09:09 |
March | 0.278436E+11 | 26047.91 | 01-MAR-16:49 | 0.726089E+10 | 4644.69 | 01-MAR-09:09 |
April | 0.242585E+11 | 26047.91 | 03-APR-08:09 | 0.689984E+10 | 4644.69 | 01-APR-09:09 |
May | 0.251011E+11 | 26047.91 | 10-MAY-16:00 | 0.717170E+10 | 4644.69 | 01-MAY-08:09 |
June | 0.243615E+11 | 26047.91 | 07-JUN-08:09 | 0.701217E+10 | 4644.69 | 01-JUN-08:09 |
July | 0.241654E+11 | 26047.91 | 01-JUL-16:00 | 0.705936E+10 | 4644.69 | 01-JUL-09:09 |
August | 0.248769E+11 | 26047.91 | 07-AUG-08:09 | 0.726089E+10 | 4644.69 | 01-AUG-08:09 |
September | 0.244913E+11 | 26047.91 | 01-SEP-16:30 | 0.689984E+10 | 4644.69 | 01-SEP-08:09 |
October | 0.285575E+11 | 26047.91 | 02-OCT-08:09 | 0.708251E+10 | 4644.69 | 02-OCT-08:09 |
November | 0.275488E+11 | 26047.91 | 01-NOV-08:09 | 0.685694E+10 | 4644.69 | 01-NOV-08:09 |
December | 0.288119E+11 | 26047.91 | 01-DEC-09:09 | 0.705936E+10 | 4644.69 | 01-DEC-09:09 |
Annual Sum or Average | 0.315675E+12 | 0.840716E+11 | ||||
Minimum of Months | 0.241654E+11 | 26047.91 | 0.642555E+10 | 4644.69 | ||
Maximum of Months | 0.293831E+11 | 26047.91 | 0.726089E+10 | 4644.69 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.293011E+10 | 2454.44 | 02-JAN-09:09 | 0.444637E+10 | 2915.92 | 02-JAN-09:09 |
February | 0.266601E+10 | 2454.44 | 01-FEB-09:09 | 0.403394E+10 | 2915.92 | 01-FEB-09:09 |
March | 0.304105E+10 | 2454.44 | 01-MAR-09:09 | 0.455836E+10 | 2915.92 | 01-MAR-09:09 |
April | 0.286924E+10 | 2454.44 | 01-APR-09:09 | 0.433169E+10 | 2915.92 | 01-APR-09:09 |
May | 0.298558E+10 | 2454.44 | 01-MAY-08:09 | 0.450237E+10 | 2915.92 | 01-MAY-08:09 |
June | 0.293453E+10 | 2454.44 | 01-JUN-08:09 | 0.440222E+10 | 2915.92 | 01-JUN-08:09 |
July | 0.292029E+10 | 2454.44 | 01-JUL-09:09 | 0.443184E+10 | 2915.92 | 01-JUL-09:09 |
August | 0.304105E+10 | 2454.44 | 01-AUG-08:09 | 0.455836E+10 | 2915.92 | 01-AUG-08:09 |
September | 0.286924E+10 | 2454.44 | 01-SEP-08:09 | 0.433169E+10 | 2915.92 | 01-SEP-08:09 |
October | 0.293011E+10 | 2454.44 | 02-OCT-08:09 | 0.444637E+10 | 2915.92 | 02-OCT-08:09 |
November | 0.283340E+10 | 2454.44 | 01-NOV-08:09 | 0.430476E+10 | 2915.92 | 01-NOV-08:09 |
December | 0.292029E+10 | 2454.44 | 01-DEC-09:09 | 0.443184E+10 | 2915.92 | 01-DEC-09:09 |
Annual Sum or Average | 0.349409E+11 | 0.527798E+11 | ||||
Minimum of Months | 0.266601E+10 | 2454.44 | 0.403394E+10 | 2915.92 | ||
Maximum of Months | 0.304105E+10 | 2454.44 | 0.455836E+10 | 2915.92 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.293011E+10 | 2454.44 | 02-JAN-09:09 | 0.667369E+09 | 437.66 | 02-JAN-09:09 |
February | 0.266601E+10 | 2454.44 | 01-FEB-09:09 | 0.605465E+09 | 437.66 | 01-FEB-09:09 |
March | 0.304105E+10 | 2454.44 | 01-MAR-09:09 | 0.684178E+09 | 437.66 | 01-MAR-09:09 |
April | 0.286924E+10 | 2454.44 | 01-APR-09:09 | 0.650156E+09 | 437.66 | 01-APR-09:09 |
May | 0.298558E+10 | 2454.44 | 01-MAY-08:09 | 0.675774E+09 | 437.66 | 01-MAY-08:09 |
June | 0.293453E+10 | 2454.44 | 01-JUN-08:09 | 0.660742E+09 | 437.66 | 01-JUN-08:09 |
July | 0.292029E+10 | 2454.44 | 01-JUL-09:09 | 0.665188E+09 | 437.66 | 01-JUL-09:09 |
August | 0.304105E+10 | 2454.44 | 01-AUG-08:09 | 0.684178E+09 | 437.66 | 01-AUG-08:09 |
September | 0.286924E+10 | 2454.44 | 01-SEP-08:09 | 0.650156E+09 | 437.66 | 01-SEP-08:09 |
October | 0.293011E+10 | 2454.44 | 02-OCT-08:09 | 0.667369E+09 | 437.66 | 02-OCT-08:09 |
November | 0.283340E+10 | 2454.44 | 01-NOV-08:09 | 0.646114E+09 | 437.66 | 01-NOV-08:09 |
December | 0.292029E+10 | 2454.44 | 01-DEC-09:09 | 0.665188E+09 | 437.66 | 01-DEC-09:09 |
Annual Sum or Average | 0.349409E+11 | 0.792188E+10 | ||||
Minimum of Months | 0.266601E+10 | 2454.44 | 0.605465E+09 | 437.66 | ||
Maximum of Months | 0.304105E+10 | 2454.44 | 0.684178E+09 | 437.66 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.103900E+09 | 85.79 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 94517577.03 | 85.79 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.107770E+09 | 85.79 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.101704E+09 | 85.79 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.105835E+09 | 85.79 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.103997E+09 | 85.79 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.103541E+09 | 85.79 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.107770E+09 | 85.79 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.101704E+09 | 85.79 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.103900E+09 | 85.79 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.100485E+09 | 85.79 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.103541E+09 | 85.79 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.123866E+10 | ||||
Minimum of Months | 94517577.03 | 85.79 | 0.00 | 0.00 | |
Maximum of Months | 0.107770E+09 | 85.79 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.281822E+10 | 0.420015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220003E+10 |
February | 0.479114E+10 | 0.256399E+10 | 0.381055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 517721.26 | 0.188371E+10 |
March | 0.548013E+10 | 0.292411E+10 | 0.430594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4834240.46 | 0.123100E+10 |
April | 0.518069E+10 | 0.275920E+10 | 0.409182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12450198.36 | 0.770171E+09 |
May | 0.536353E+10 | 0.287117E+10 | 0.425304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38519903.24 | 0.485604E+09 |
June | 0.528933E+10 | 0.282172E+10 | 0.415844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158358E+09 | 0.191824E+09 |
July | 0.525489E+10 | 0.280865E+10 | 0.418643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181376E+09 | 0.109063E+09 |
August | 0.548013E+10 | 0.292411E+10 | 0.430594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190735E+09 | 43619643.93 |
September | 0.518069E+10 | 0.275920E+10 | 0.409182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49543293.07 | 0.238073E+09 |
October | 0.524694E+10 | 0.281822E+10 | 0.420015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8494224.28 | 0.921933E+09 |
November | 0.504819E+10 | 0.272540E+10 | 0.406638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53825.55 | 0.130115E+10 |
December | 0.525489E+10 | 0.280865E+10 | 0.418643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196380E+10 |
Annual Sum or Average | 0.628175E+11 | 0.336027E+11 | 0.498571E+11 | 0.644882E+09 | 0.113400E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.256399E+10 | 0.381055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43619643.93 |
Maximum of Months | 0.548013E+10 | 0.292411E+10 | 0.430594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190735E+09 | 0.220003E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.293831E+11 | 0.708251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192866E+10 |
February | 0.201852E+11 | 0.262758E+11 | 0.642555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 398222.74 | 0.168880E+10 |
March | 0.230879E+11 | 0.278436E+11 | 0.726089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3969615.96 | 0.114012E+10 |
April | 0.218263E+11 | 0.242585E+11 | 0.689984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10180501.50 | 0.687415E+09 |
May | 0.225967E+11 | 0.251011E+11 | 0.717170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31543927.97 | 0.406094E+09 |
June | 0.222841E+11 | 0.243615E+11 | 0.701217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129544E+09 | 0.155503E+09 |
July | 0.221389E+11 | 0.241654E+11 | 0.705936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148416E+09 | 88010971.93 |
August | 0.230879E+11 | 0.248769E+11 | 0.726089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156171E+09 | 35510088.65 |
September | 0.218263E+11 | 0.244913E+11 | 0.689984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40568218.57 | 0.194265E+09 |
October | 0.221054E+11 | 0.285575E+11 | 0.708251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6952331.94 | 0.798162E+09 |
November | 0.212681E+11 | 0.275488E+11 | 0.685694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44095.95 | 0.115752E+10 |
December | 0.221389E+11 | 0.288119E+11 | 0.705936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174146E+10 |
Annual Sum or Average | 0.264651E+12 | 0.315675E+12 | 0.840716E+11 | 0.527788E+09 | 0.100215E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.241654E+11 | 0.642555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35510088.65 |
Maximum of Months | 0.230879E+11 | 0.293831E+11 | 0.726089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156171E+09 | 0.192866E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.293011E+10 | 0.444637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101355E+10 |
February | 0.190200E+10 | 0.266601E+10 | 0.403394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 210835.28 | 0.876041E+09 |
March | 0.217552E+10 | 0.304105E+10 | 0.455836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2098706.87 | 0.591349E+09 |
April | 0.205665E+10 | 0.286924E+10 | 0.433169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5386693.99 | 0.351434E+09 |
May | 0.212923E+10 | 0.298558E+10 | 0.450237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16719586.08 | 0.213293E+09 |
June | 0.209978E+10 | 0.293453E+10 | 0.440222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68458431.87 | 81754372.02 |
July | 0.208610E+10 | 0.292029E+10 | 0.443184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78150938.95 | 46776524.87 |
August | 0.217552E+10 | 0.304105E+10 | 0.455836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82001353.53 | 18704264.04 |
September | 0.205665E+10 | 0.286924E+10 | 0.433169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21390793.21 | 0.102662E+09 |
October | 0.208295E+10 | 0.293011E+10 | 0.444637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3679749.28 | 0.418730E+09 |
November | 0.200405E+10 | 0.283340E+10 | 0.430476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23350.58 | 0.622598E+09 |
December | 0.208610E+10 | 0.292029E+10 | 0.443184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925264E+09 |
Annual Sum or Average | 0.249375E+11 | 0.349409E+11 | 0.527798E+11 | 0.278120E+09 | 0.526216E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.266601E+10 | 0.403394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18704264.04 |
Maximum of Months | 0.217552E+10 | 0.304105E+10 | 0.455836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82001353.53 | 0.101355E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.293011E+10 | 0.667369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972351E+09 |
February | 0.190200E+10 | 0.266601E+10 | 0.605465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 210824.29 | 0.837007E+09 |
March | 0.217552E+10 | 0.304105E+10 | 0.684178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2100789.20 | 0.556363E+09 |
April | 0.205665E+10 | 0.286924E+10 | 0.650156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5393517.34 | 0.331233E+09 |
May | 0.212923E+10 | 0.298558E+10 | 0.675774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16707758.75 | 0.205581E+09 |
June | 0.209978E+10 | 0.293453E+10 | 0.660742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68612391.94 | 82687754.68 |
July | 0.208610E+10 | 0.292029E+10 | 0.665188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78457201.79 | 46990612.10 |
August | 0.217552E+10 | 0.304105E+10 | 0.684178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82399809.05 | 18866375.28 |
September | 0.205665E+10 | 0.286924E+10 | 0.650156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21442722.44 | 0.101631E+09 |
October | 0.208295E+10 | 0.293011E+10 | 0.667369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3679955.36 | 0.403918E+09 |
November | 0.200405E+10 | 0.283340E+10 | 0.646114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23344.04 | 0.591176E+09 |
December | 0.208610E+10 | 0.292029E+10 | 0.665188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876718E+09 |
Annual Sum or Average | 0.249375E+11 | 0.349409E+11 | 0.792188E+10 | 0.279028E+09 | 0.502452E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.266601E+10 | 0.605465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18866375.28 |
Maximum of Months | 0.217552E+10 | 0.304105E+10 | 0.684178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82399809.05 | 0.972351E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.103900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128489E+11 |
February | 0.00 | 94517577.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808284E+10 |
March | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28275.97 | 0.421929E+10 |
April | 0.00 | 0.101704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8260563.90 | 0.155719E+10 |
May | 0.00 | 0.105835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64108656.32 | 0.419149E+09 |
June | 0.00 | 0.103997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270765E+09 | 95096174.36 |
July | 0.00 | 0.103541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327387E+09 | 0.154184E+09 |
August | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237059E+09 | 74169765.34 |
September | 0.00 | 0.101704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28350848.62 | 0.422279E+09 |
October | 0.00 | 0.103900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42254.03 | 0.253493E+10 |
November | 0.00 | 0.100485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447594E+10 |
December | 0.00 | 0.103541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871987E+10 |
Annual Sum or Average | 0.00 | 0.123866E+10 | 0.936002E+09 | 0.436038E+11 | |||||
Minimum of Months | 0.00 | 94517577.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74169765.34 |
Maximum of Months | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327387E+09 | 0.128489E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2344.76 | 02-JAN-09:09 | 2754.45 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4714.42 | 07-JAN-05:10 |
February | 5888.82 | 01-FEB-15:09 | 2344.76 | 01-FEB-09:09 | 2754.45 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.82 | 28-FEB-15:00 | 5488.76 | 12-FEB-00:53 |
March | 5888.82 | 01-MAR-15:09 | 2344.76 | 01-MAR-09:09 | 2754.45 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 135.18 | 30-MAR-16:00 | 3497.84 | 22-MAR-05:00 |
April | 5888.82 | 01-APR-10:09 | 2344.76 | 01-APR-09:09 | 2754.45 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.08 | 04-APR-15:00 | 1752.58 | 05-APR-05:00 |
May | 5888.82 | 01-MAY-14:09 | 2344.76 | 01-MAY-08:09 | 2754.45 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 334.49 | 29-MAY-18:03 | 1465.94 | 10-MAY-04:00 |
June | 5888.82 | 01-JUN-14:09 | 2344.76 | 01-JUN-08:09 | 2754.45 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 516.84 | 25-JUN-18:10 | 1009.93 | 07-JUN-03:00 |
July | 5888.82 | 01-JUL-10:09 | 2344.76 | 01-JUL-09:09 | 2754.45 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 581.96 | 09-JUL-19:30 | 750.22 | 28-JUL-21:53 |
August | 5888.82 | 01-AUG-14:09 | 2344.76 | 01-AUG-08:09 | 2754.45 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 739.17 | 18-AUG-20:10 | 456.50 | 25-AUG-04:55 |
September | 5888.82 | 01-SEP-14:09 | 2344.76 | 01-SEP-08:09 | 2754.45 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 284.37 | 03-SEP-18:03 | 1033.63 | 29-SEP-05:00 |
October | 5888.82 | 02-OCT-14:09 | 2344.76 | 02-OCT-08:09 | 2754.45 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.92 | 11-OCT-14:00 | 2028.66 | 28-OCT-04:00 |
November | 5888.82 | 01-NOV-14:09 | 2344.76 | 01-NOV-08:09 | 2754.45 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.93 | 19-NOV-14:55 | 3146.12 | 30-NOV-21:03 |
December | 5888.82 | 01-DEC-15:09 | 2344.76 | 01-DEC-09:09 | 2754.45 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5006.22 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2344.76 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.50 | |||||
Maximum of Months | 5888.82 | 2344.76 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 739.17 | 5488.76 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 26047.91 | 02-JAN-09:09 | 4644.69 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3537.97 | 26-JAN-02:00 |
February | 24809.68 | 01-FEB-15:09 | 26047.91 | 01-FEB-09:09 | 4644.69 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.33 | 28-FEB-15:00 | 4994.63 | 12-FEB-00:53 |
March | 24809.68 | 01-MAR-15:09 | 26047.91 | 01-MAR-16:49 | 4644.69 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.67 | 30-MAR-16:00 | 3127.16 | 22-MAR-03:00 |
April | 24809.68 | 01-APR-10:09 | 26047.91 | 03-APR-08:09 | 4644.69 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.02 | 04-APR-15:00 | 1641.62 | 05-APR-05:00 |
May | 24809.68 | 01-MAY-14:09 | 26047.91 | 10-MAY-16:00 | 4644.69 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 273.84 | 29-MAY-18:03 | 1313.51 | 10-MAY-04:00 |
June | 24809.68 | 01-JUN-14:09 | 26047.91 | 07-JUN-08:09 | 4644.69 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 423.87 | 11-JUN-18:03 | 816.41 | 07-JUN-03:20 |
July | 24809.68 | 01-JUL-10:09 | 26047.91 | 01-JUL-16:00 | 4644.69 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 476.37 | 09-JUL-19:30 | 626.60 | 28-JUL-24:00 |
August | 24809.68 | 01-AUG-14:09 | 26047.91 | 07-AUG-08:09 | 4644.69 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 593.66 | 18-AUG-20:10 | 375.74 | 25-AUG-04:55 |
September | 24809.68 | 01-SEP-14:09 | 26047.91 | 01-SEP-16:30 | 4644.69 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 234.45 | 03-SEP-18:03 | 906.70 | 29-SEP-05:00 |
October | 24809.68 | 02-OCT-14:09 | 26047.91 | 02-OCT-08:09 | 4644.69 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.54 | 11-OCT-14:00 | 1932.36 | 28-OCT-04:00 |
November | 24809.68 | 01-NOV-14:09 | 26047.91 | 01-NOV-08:09 | 4644.69 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | 19-NOV-15:00 | 2783.72 | 07-NOV-02:00 |
December | 24809.68 | 01-DEC-15:09 | 26047.91 | 01-DEC-09:09 | 4644.69 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4746.02 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 26047.91 | 4644.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.74 | |||||
Maximum of Months | 24809.68 | 26047.91 | 4644.69 | 0.00 | 0.00 | 0.00 | 0.00 | 593.66 | 4994.63 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2454.44 | 02-JAN-09:09 | 2915.92 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2055.29 | 07-JAN-05:05 |
February | 2337.76 | 01-FEB-15:09 | 2454.44 | 01-FEB-09:09 | 2915.92 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 | 28-FEB-15:00 | 2386.31 | 12-FEB-00:53 |
March | 2337.76 | 01-MAR-15:09 | 2454.44 | 01-MAR-09:09 | 2915.92 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.58 | 30-MAR-16:00 | 1515.72 | 22-MAR-05:00 |
April | 2337.76 | 01-APR-10:09 | 2454.44 | 01-APR-09:09 | 2915.92 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.53 | 04-APR-15:00 | 784.13 | 05-APR-05:00 |
May | 2337.76 | 01-MAY-14:09 | 2454.44 | 01-MAY-08:09 | 2915.92 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 146.95 | 29-MAY-18:10 | 642.43 | 10-MAY-04:00 |
June | 2337.76 | 01-JUN-14:09 | 2454.44 | 01-JUN-08:09 | 2915.92 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 227.05 | 11-JUN-18:10 | 419.82 | 07-JUN-02:55 |
July | 2337.76 | 01-JUL-10:09 | 2454.44 | 01-JUL-09:09 | 2915.92 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 252.03 | 09-JUL-19:30 | 321.15 | 28-JUL-20:10 |
August | 2337.76 | 01-AUG-14:09 | 2454.44 | 01-AUG-08:09 | 2915.92 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 318.51 | 18-AUG-20:10 | 187.03 | 25-AUG-04:45 |
September | 2337.76 | 01-SEP-14:09 | 2454.44 | 01-SEP-08:09 | 2915.92 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 126.25 | 03-SEP-18:10 | 449.97 | 29-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 2454.44 | 02-OCT-08:09 | 2915.92 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.34 | 11-OCT-14:00 | 974.81 | 28-OCT-04:00 |
November | 2337.76 | 01-NOV-14:09 | 2454.44 | 01-NOV-08:09 | 2915.92 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.65 | 19-NOV-15:00 | 1431.04 | 07-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 2454.44 | 01-DEC-09:09 | 2915.92 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2252.78 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2454.44 | 2915.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.03 | |||||
Maximum of Months | 2337.76 | 2454.44 | 2915.92 | 0.00 | 0.00 | 0.00 | 0.00 | 318.51 | 2386.31 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2454.44 | 02-JAN-09:09 | 437.66 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2054.79 | 07-JAN-05:06 |
February | 2337.76 | 01-FEB-15:09 | 2454.44 | 01-FEB-09:09 | 437.66 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.06 | 28-FEB-15:00 | 2330.63 | 12-FEB-00:53 |
March | 2337.76 | 01-MAR-15:09 | 2454.44 | 01-MAR-09:09 | 437.66 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.58 | 30-MAR-16:00 | 1515.72 | 22-MAR-05:00 |
April | 2337.76 | 01-APR-10:09 | 2454.44 | 01-APR-09:09 | 437.66 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.53 | 04-APR-15:00 | 733.22 | 05-APR-05:00 |
May | 2337.76 | 01-MAY-14:09 | 2454.44 | 01-MAY-08:09 | 437.66 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 143.08 | 29-MAY-18:03 | 612.31 | 10-MAY-04:00 |
June | 2337.76 | 01-JUN-14:09 | 2454.44 | 01-JUN-08:09 | 437.66 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 227.80 | 11-JUN-18:10 | 428.02 | 07-JUN-02:55 |
July | 2337.76 | 01-JUL-10:09 | 2454.44 | 01-JUL-09:09 | 437.66 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 252.10 | 09-JUL-19:30 | 318.62 | 28-JUL-21:52 |
August | 2337.76 | 01-AUG-14:09 | 2454.44 | 01-AUG-08:09 | 437.66 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 318.47 | 18-AUG-20:10 | 196.39 | 25-AUG-05:00 |
September | 2337.76 | 01-SEP-14:09 | 2454.44 | 01-SEP-08:09 | 437.66 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 127.21 | 03-SEP-18:10 | 425.34 | 29-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 2454.44 | 02-OCT-08:09 | 437.66 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.34 | 11-OCT-14:00 | 926.03 | 28-OCT-04:00 |
November | 2337.76 | 01-NOV-14:09 | 2454.44 | 01-NOV-08:09 | 437.66 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 | 19-NOV-15:00 | 1375.96 | 07-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 2454.44 | 01-DEC-09:09 | 437.66 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2153.56 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2454.44 | 437.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.39 | |||||
Maximum of Months | 2337.76 | 2454.44 | 437.66 | 0.00 | 0.00 | 0.00 | 0.00 | 318.47 | 2330.63 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 85.79 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 31574.78 | 07-JAN-17:00 |
February | 0.00 | 01-FEB-00:10 | 85.79 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 31804.20 | 11-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 85.79 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 | 28-MAR-17:00 | 19317.96 | 22-MAR-11:10 |
April | 0.00 | 01-APR-00:10 | 85.79 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.28 | 16-APR-11:05 | 15529.21 | 05-APR-11:05 |
May | 0.00 | 01-MAY-00:10 | 85.79 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 755.22 | 30-MAY-11:03 | 4606.54 | 10-MAY-11:10 |
June | 0.00 | 01-JUN-00:10 | 85.79 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1817.12 | 06-JUN-11:02 | 1392.67 | 30-JUN-15:52 |
July | 0.00 | 01-JUL-00:10 | 85.79 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2397.55 | 08-JUL-11:01 | 2984.32 | 28-JUL-11:10 |
August | 0.00 | 01-AUG-00:10 | 85.79 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1881.00 | 01-AUG-11:02 | 1212.86 | 08-AUG-16:53 |
September | 0.00 | 01-SEP-00:10 | 85.79 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.42 | 09-SEP-11:03 | 4357.77 | 28-SEP-17:00 |
October | 0.00 | 01-OCT-00:10 | 85.79 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.69 | 10-OCT-16:00 | 14139.72 | 25-OCT-11:05 |
November | 0.00 | 01-NOV-00:10 | 85.79 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19904.15 | 20-NOV-12:10 |
December | 0.00 | 01-DEC-00:10 | 85.79 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 23756.92 | 17-DEC-18:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 85.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1212.86 | ||||
Maximum of Months | 0.00 | 85.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2397.55 | 31804.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4508.57 | 26-JAN-13:15 | 10305.43 | 4689.51 | 5508.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.95 |
February | 4653.56 | 02-FEB-10:25 | 7361.02 | 4689.51 | 5508.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 792.70 |
March | 20246.97 | 30-MAR-22:43 | 0.00 | 1437.32 | 6081.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.22 |
April | 28094.12 | 17-APR-20:51 | 0.00 | 4024.49 | 4257.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.74 |
May | 34054.44 | 14-MAY-18:35 | 0.00 | 1437.32 | 4561.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 |
June | 37974.54 | 10-JUN-22:48 | 0.00 | 1437.32 | 4561.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.52 |
July | 27245.54 | 16-JUL-18:10 | 0.00 | 574.93 | 1824.53 | 0.00 | 0.00 | 0.00 | 0.00 | 467.19 | 0.00 |
August | 26713.17 | 01-AUG-20:10 | 0.00 | 2299.71 | 2432.70 | 0.00 | 0.00 | 0.00 | 0.00 | 19.35 | 0.00 |
September | 34986.59 | 13-SEP-20:18 | 0.00 | 5749.28 | 6081.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.10 |
October | 24076.37 | 16-OCT-20:52 | 0.00 | 3449.57 | 3649.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.24 |
November | 6365.23 | 04-NOV-16:00 | 5888.82 | 2344.76 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.02 |
December | 4321.61 | 13-DEC-16:00 | 5888.82 | 2344.76 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.52 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4321.61 | 0.00 | 574.93 | 1824.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37974.54 | 10305.43 | 5749.28 | 6081.76 | 0.00 | 0.00 | 0.00 | 0.00 | 467.19 | 792.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 56831.64 | 27-JAN-07:05 | 12404.84 | 23153.70 | 8257.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.27 |
February | 166302.58 | 28-FEB-21:41 | 0.00 | 52095.82 | 9229.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.39 |
March | 153329.19 | 13-MAR-20:23 | 0.00 | 57884.25 | 10255.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.74 |
April | 161357.62 | 14-APR-20:16 | 0.00 | 57884.25 | 10255.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.54 |
May | 166430.21 | 13-MAY-21:31 | 0.00 | 10129.74 | 5384.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.73 |
June | 178155.43 | 10-JUN-22:41 | 0.00 | 14471.06 | 7691.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.34 |
July | 124480.49 | 28-JUL-21:52 | 0.00 | 8682.64 | 6153.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.18 |
August | 119537.70 | 18-AUG-20:10 | 0.00 | 23153.70 | 4102.15 | 0.00 | 0.00 | 0.00 | 0.00 | 593.66 | 0.00 |
September | 161319.07 | 14-SEP-20:55 | 0.00 | 57884.25 | 10255.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.92 |
October | 152879.09 | 22-OCT-18:41 | 0.00 | 11576.85 | 6153.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.01 |
November | 108319.38 | 03-NOV-23:52 | 0.00 | 8682.64 | 6153.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.95 |
December | 53337.93 | 18-DEC-07:05 | 12404.84 | 23153.70 | 8257.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 53337.93 | 0.00 | 8682.64 | 4102.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 178155.43 | 12404.84 | 57884.25 | 10255.37 | 0.00 | 0.00 | 0.00 | 0.00 | 593.66 | 580.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4169.19 | 28-JAN-15:00 | 2337.76 | 2454.44 | 2915.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.02 |
February | 24210.12 | 28-FEB-21:11 | 0.00 | 5454.31 | 6438.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.01 |
March | 21992.01 | 26-MAR-18:35 | 0.00 | 272.72 | 965.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.74 |
April | 22457.31 | 12-APR-22:41 | 0.00 | 1090.86 | 5150.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.76 |
May | 24392.18 | 13-MAY-21:31 | 0.00 | 954.50 | 3380.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.51 |
June | 24052.56 | 11-JUN-00:31 | 0.00 | 954.50 | 3380.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.37 |
July | 16434.27 | 07-JUL-20:08 | 0.00 | 2181.72 | 2575.31 | 0.00 | 0.00 | 0.00 | 0.00 | 130.76 | 0.00 |
August | 16600.46 | 18-AUG-20:08 | 0.00 | 2181.72 | 2575.31 | 0.00 | 0.00 | 0.00 | 0.00 | 309.44 | 0.00 |
September | 21224.22 | 14-SEP-20:55 | 0.00 | 5454.31 | 6438.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.28 |
October | 24629.20 | 11-OCT-21:25 | 0.00 | 272.72 | 1287.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.47 |
November | 19591.81 | 02-NOV-21:53 | 0.00 | 409.07 | 1931.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.99 |
December | 18149.62 | 12-DEC-22:00 | 0.00 | 1090.86 | 1287.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.28 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4169.19 | 0.00 | 272.72 | 965.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24629.20 | 2337.76 | 5454.31 | 6438.29 | 0.00 | 0.00 | 0.00 | 0.00 | 309.44 | 216.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3473.33 | 05-JAN-10:03 | 4383.30 | 7363.31 | 1312.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.00 |
February | 20195.85 | 26-FEB-19:31 | 0.00 | 1363.58 | 724.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.80 |
March | 16961.89 | 13-MAR-21:11 | 0.00 | 1363.58 | 966.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.21 |
April | 17511.60 | 14-APR-20:17 | 0.00 | 5454.31 | 966.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.41 |
May | 16466.72 | 14-MAY-18:20 | 0.00 | 1363.58 | 724.76 | 0.00 | 0.00 | 0.00 | 0.00 | 30.07 | 0.00 |
June | 18998.33 | 10-JUN-21:21 | 0.00 | 1363.58 | 724.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.48 |
July | 13349.80 | 16-JUL-18:08 | 0.00 | 545.43 | 289.90 | 0.00 | 0.00 | 0.00 | 0.00 | 206.55 | 0.00 |
August | 13293.83 | 18-AUG-20:08 | 0.00 | 2181.72 | 386.54 | 0.00 | 0.00 | 0.00 | 0.00 | 309.62 | 0.00 |
September | 17476.62 | 14-SEP-20:48 | 0.00 | 5454.31 | 966.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.14 |
October | 20103.26 | 11-OCT-21:25 | 0.00 | 272.72 | 193.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.10 |
November | 16031.81 | 02-NOV-20:22 | 0.00 | 3272.58 | 579.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.00 |
December | 14734.88 | 12-DEC-21:45 | 0.00 | 1090.86 | 193.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.29 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3473.33 | 0.00 | 272.72 | 193.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20195.85 | 4383.30 | 7363.31 | 1312.98 | 0.00 | 0.00 | 0.00 | 0.00 | 309.62 | 351.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 931.82 | 16-JAN-07:02 | 0.00 | 58.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.06 |
February | 907.26 | 04-FEB-05:02 | 0.00 | 58.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.23 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.29 |
April | 0.00 | 01-APR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.39 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.26 |
June | 0.00 | 01-JUN-00:05 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.59 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.66 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 |
November | 165.22 | 21-NOV-05:02 | 0.00 | 52.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.40 |
December | 705.39 | 26-DEC-05:02 | 0.00 | 58.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.40 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | |
Maximum of Months | 931.82 | 0.00 | 58.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.40 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.790440E+11 | 61041.59 | 07-JAN-17:00 | 0.821655E+11 | 170259.63 | 08-JAN-09:09 |
February | 0.710288E+11 | 67338.93 | 28-FEB-16:00 | 0.477576E+11 | 194386.13 | 12-FEB-09:09 |
March | 0.798993E+11 | 77040.17 | 30-MAR-15:00 | 0.138286E+11 | 59174.35 | 19-MAR-08:20 |
April | 0.812984E+11 | 77578.53 | 17-APR-16:19 | 0.894166E+10 | 46171.85 | 06-APR-06:00 |
May | 0.970172E+11 | 83458.68 | 06-MAY-15:00 | 0.768327E+10 | 7046.05 | 10-MAY-11:09 |
June | 0.112448E+12 | 89613.59 | 22-JUN-16:00 | 0.727798E+10 | 4887.51 | 01-JUN-11:09 |
July | 0.121151E+12 | 100025.34 | 08-JUL-14:30 | 0.735716E+10 | 4849.65 | 03-JUL-11:50 |
August | 0.127185E+12 | 98235.69 | 18-AUG-15:00 | 0.740956E+10 | 4847.06 | 31-AUG-11:50 |
September | 0.102675E+12 | 93188.71 | 07-SEP-15:00 | 0.726773E+10 | 6467.16 | 28-SEP-16:40 |
October | 0.872170E+11 | 85592.20 | 10-OCT-15:00 | 0.903813E+10 | 40056.73 | 26-OCT-06:00 |
November | 0.759036E+11 | 70253.06 | 04-NOV-15:00 | 0.151472E+11 | 107647.59 | 22-NOV-07:10 |
December | 0.778149E+11 | 65694.10 | 12-DEC-15:09 | 0.405631E+11 | 147111.20 | 04-DEC-07:10 |
Annual Sum or Average | 0.111268E+13 | 0.254438E+12 | ||||
Minimum of Months | 0.710288E+11 | 61041.59 | 0.726773E+10 | 4847.06 | ||
Maximum of Months | 0.127185E+12 | 100025.34 | 0.821655E+11 | 194386.13 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.381654E+11 | 0.614719E+10 | 0.163964E+11 | 0.00 | 0.183129E+11 | 0.00 | 0.00 | 22141453.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342664E+11 | 0.519292E+10 | 0.148755E+11 | 0.00 | 0.156755E+11 | 0.00 | 0.00 | 0.101849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369575E+11 | 0.522761E+10 | 0.168094E+11 | 0.00 | 0.161274E+11 | 0.00 | 0.00 | 0.477739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.328579E+11 | 0.453798E+10 | 0.159735E+11 | 0.00 | 0.146687E+11 | 0.00 | 0.00 | 0.132603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.340492E+11 | 0.423559E+10 | 0.166029E+11 | 0.00 | 0.148542E+11 | 0.00 | 0.00 | 0.272753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.331562E+11 | 0.389985E+10 | 0.162336E+11 | 0.00 | 0.150978E+11 | 0.00 | 0.00 | 0.440602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.329181E+11 | 0.410462E+10 | 0.163428E+11 | 0.00 | 0.160042E+11 | 0.00 | 0.00 | 0.517813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.339909E+11 | 0.448360E+10 | 0.168094E+11 | 0.00 | 0.164011E+11 | 0.00 | 0.00 | 0.555002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.330906E+11 | 0.483336E+10 | 0.159735E+11 | 0.00 | 0.148952E+11 | 0.00 | 0.00 | 0.338827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.373398E+11 | 0.553414E+10 | 0.163964E+11 | 0.00 | 0.153455E+11 | 0.00 | 0.00 | 0.126011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.360415E+11 | 0.582817E+10 | 0.158742E+11 | 0.00 | 0.153917E+11 | 0.00 | 0.00 | 0.276800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.375647E+11 | 0.627537E+10 | 0.163428E+11 | 0.00 | 0.172323E+11 | 0.00 | 0.00 | 0.399672E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.420398E+12 | 0.603004E+11 | 0.194630E+12 | 0.190006E+12 | 0.00 | 0.247347E+12 | |||||||
Minimum of Months | 0.328579E+11 | 0.389985E+10 | 0.148755E+11 | 0.00 | 0.146687E+11 | 0.00 | 0.00 | 22141453.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.381654E+11 | 0.627537E+10 | 0.168094E+11 | 0.00 | 0.183129E+11 | 0.00 | 0.00 | 0.555002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.740483E+11 | 0.00 | 0.811727E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.404114E+11 | 0.00 | 0.734628E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.573920E+10 | 0.00 | 0.808943E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.132837E+10 | 0.00 | 0.761329E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 15265998.64 | 0.00 | 0.766801E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 539981.40 | 0.00 | 0.727744E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.735716E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.740956E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 38002199.65 | 0.00 | 0.722973E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.142773E+10 | 0.00 | 0.761040E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.759239E+10 | 0.00 | 0.755485E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.325541E+11 | 0.00 | 0.800894E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.163155E+12 | 0.912824E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.722973E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.740483E+11 | 0.00 | 0.811727E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 33387.34 | 02-JAN-09:09 | 4644.30 | 01-JAN-06:10 | 10752.72 | 02-JAN-09:09 | 0.00 | 14212.24 | 08-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 33387.34 | 01-FEB-09:09 | 4644.30 | 01-FEB-06:10 | 10752.72 | 01-FEB-09:09 | 0.00 | 14738.25 | 12-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 33387.34 | 01-MAR-16:49 | 4644.30 | 01-MAR-06:10 | 10752.72 | 01-MAR-09:09 | 0.00 | 11780.62 | 19-MAR-08:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 33387.34 | 03-APR-08:09 | 4644.30 | 01-APR-05:10 | 10752.72 | 01-APR-09:09 | 0.00 | 11276.88 | 06-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 33387.34 | 10-MAY-16:00 | 4644.30 | 01-MAY-05:10 | 10752.72 | 01-MAY-08:09 | 0.00 | 10591.53 | 11-MAY-11:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 33387.34 | 07-JUN-08:09 | 4644.30 | 01-JUN-05:10 | 10752.72 | 01-JUN-08:09 | 0.00 | 10591.53 | 07-JUN-07:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 33387.34 | 01-JUL-16:00 | 4644.30 | 01-JUL-05:10 | 10752.72 | 01-JUL-09:09 | 0.00 | 11316.20 | 08-JUL-14:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 33387.34 | 07-AUG-08:09 | 4644.30 | 01-AUG-05:10 | 10752.72 | 01-AUG-08:09 | 0.00 | 10402.23 | 01-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 33387.34 | 01-SEP-16:30 | 4644.30 | 01-SEP-05:10 | 10752.72 | 01-SEP-08:09 | 0.00 | 10591.53 | 29-SEP-11:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 33387.34 | 02-OCT-08:09 | 4644.30 | 01-OCT-05:10 | 10752.72 | 02-OCT-08:09 | 0.00 | 11239.27 | 26-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 33387.34 | 01-NOV-08:09 | 4644.30 | 01-NOV-05:10 | 10752.72 | 01-NOV-08:09 | 0.00 | 12686.94 | 22-NOV-07:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 33387.34 | 01-DEC-09:09 | 4644.30 | 01-DEC-06:10 | 10752.72 | 01-DEC-09:09 | 0.00 | 13337.91 | 03-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 33387.34 | 4644.30 | 10752.72 | 0.00 | 10402.23 | 0.00 | 0.00 | |||||
Maximum of Months | 33387.34 | 4644.30 | 10752.72 | 0.00 | 14738.25 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 3226.55 | 31-JAN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16337.67 | 28-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27460.79 | 30-MAR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27162.72 | 18-APR-20:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34348.67 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42221.79 | 06-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 51094.15 | 08-JUL-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 46795.37 | 01-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41676.80 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33441.26 | 10-OCT-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22889.81 | 04-NOV-21:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13214.07 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 3226.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51094.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 61041.59 | 07-JAN-17:00 | 33387.34 | 10752.72 | 4644.30 | 0.00 | 12257.24 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67338.93 | 28-FEB-16:00 | 33387.34 | 10752.72 | 0.00 | 0.00 | 8642.81 | 0.00 | 0.00 | 14556.07 | 0.00 |
March | 77040.17 | 30-MAR-15:00 | 31216.68 | 10752.72 | 0.00 | 0.00 | 8642.81 | 0.00 | 0.00 | 26427.97 | 0.00 |
April | 77578.53 | 17-APR-16:19 | 33387.34 | 10752.72 | 0.00 | 0.00 | 8642.81 | 0.00 | 0.00 | 24795.67 | 0.00 |
May | 83458.68 | 06-MAY-15:00 | 31216.68 | 10752.72 | 0.00 | 0.00 | 8642.81 | 0.00 | 0.00 | 32846.48 | 0.00 |
June | 89613.59 | 22-JUN-16:00 | 31216.68 | 10752.72 | 0.00 | 0.00 | 8915.88 | 0.00 | 0.00 | 38728.32 | 0.00 |
July | 100025.34 | 08-JUL-14:30 | 26875.36 | 10752.72 | 0.00 | 0.00 | 11311.90 | 0.00 | 0.00 | 51085.37 | 0.00 |
August | 98235.69 | 18-AUG-15:00 | 31216.68 | 10752.72 | 0.00 | 0.00 | 10274.09 | 0.00 | 0.00 | 45992.21 | 0.00 |
September | 93188.71 | 07-SEP-15:00 | 31216.68 | 10752.72 | 0.00 | 0.00 | 9542.52 | 0.00 | 0.00 | 41676.80 | 0.00 |
October | 85592.20 | 10-OCT-15:00 | 33387.34 | 10752.72 | 0.00 | 0.00 | 8642.81 | 0.00 | 0.00 | 32809.34 | 0.00 |
November | 70253.06 | 04-NOV-15:00 | 33387.34 | 10752.72 | 0.00 | 0.00 | 8642.81 | 0.00 | 0.00 | 17470.20 | 0.00 |
December | 65694.10 | 12-DEC-15:09 | 33387.34 | 10752.72 | 0.00 | 0.00 | 8642.81 | 0.00 | 0.00 | 12911.24 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 61041.59 | 26875.36 | 10752.72 | 0.00 | 0.00 | 8642.81 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 100025.34 | 33387.34 | 10752.72 | 4644.30 | 0.00 | 12257.24 | 0.00 | 0.00 | 51085.37 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 167065.87 | 09-JAN-07:10 | 0.00 | 5043.49 | 27-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 189840.43 | 12-FEB-09:09 | 0.00 | 5043.86 | 03-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 54633.56 | 19-MAR-08:20 | 0.00 | 5028.69 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 41832.83 | 06-APR-06:49 | 0.00 | 4986.34 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 2122.81 | 10-MAY-11:09 | 0.00 | 4939.01 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 899.97 | 04-JUN-06:00 | 0.00 | 4887.51 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4849.65 | 03-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4847.06 | 31-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 2259.21 | 28-SEP-16:00 | 0.00 | 4879.83 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 35522.97 | 26-OCT-06:00 | 0.00 | 4932.66 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 103105.85 | 22-NOV-07:10 | 0.00 | 4984.89 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 145251.20 | 04-DEC-07:10 | 0.00 | 5024.80 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4847.06 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 189840.43 | 0.00 | 5043.86 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.67 | 20.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.83 | 19.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.50 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.48 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.49 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.52 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.48 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.00 | 0.00 |
November | 0.67 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.50 | 20.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16.67 | 20.03 | 0.00 | 7.00 | 24.49 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.67 | 20.43 | 0.00 | 0.00 | 2.17 | 24.52 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.49 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.47 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 24.51 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.48 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.48 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.47 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.49 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.47 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 21.50 | 24.49 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 24.51 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 20.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.50 | 20.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.49 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.49 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.50 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 24.51 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 24.55 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 24.57 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 24.54 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 24.49 | 0.00 | 0.00 |
November | 0.17 | 20.54 | 0.00 | 0.00 | 1.33 | 24.51 | 0.00 | 0.00 |
December | 1.83 | 20.35 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 0.00 |
Annual Sum or Average | 8.83 | 20.13 | 0.00 | 91.00 | 24.54 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.33 | 20.54 | 0.00 | 0.00 | 29.67 | 24.57 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.00 | 19.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.00 | 19.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.50 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.47 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.48 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 24.51 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 24.52 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.49 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.46 | 0.00 | 0.00 |
November | 0.33 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.67 | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.33 | 19.95 | 0.00 | 29.00 | 24.51 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.00 | 20.50 | 0.00 | 0.00 | 11.83 | 24.52 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.29 | 321.00 | 21.15 | 321.00 | 21.15 |
February | 376.00 | 21.91 | 182.00 | 21.26 | 182.00 | 21.26 |
March | 364.17 | 22.78 | 47.00 | 22.34 | 26.33 | 21.12 |
April | 239.67 | 23.34 | 59.67 | 23.68 | 21.83 | 23.33 |
May | 108.00 | 23.71 | 265.67 | 23.88 | 58.00 | 23.87 |
June | 11.83 | 23.79 | 324.33 | 23.89 | 0.00 | 0.00 |
July | 21.83 | 23.89 | 393.83 | 23.89 | 21.83 | 23.89 |
August | 0.33 | 23.89 | 406.17 | 23.89 | 0.33 | 23.89 |
September | 26.33 | 23.79 | 315.00 | 23.89 | 13.83 | 23.89 |
October | 255.00 | 23.34 | 106.83 | 23.88 | 33.00 | 23.86 |
November | 363.00 | 22.69 | 59.67 | 22.51 | 43.83 | 22.01 |
December | 414.67 | 21.64 | 174.00 | 21.28 | 174.00 | 21.28 |
Annual Sum or Average | 2594.83 | 22.39 | 2655.17 | 23.14 | 896.00 | 21.68 |
Minimum of Months | 0.33 | 21.29 | 47.00 | 21.15 | 0.00 | 0.00 |
Maximum of Months | 414.67 | 23.89 | 406.17 | 23.89 | 321.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 411.17 | 21.36 | 162.33 | 21.22 | 162.33 | 21.22 |
February | 350.50 | 21.99 | 80.33 | 21.32 | 76.83 | 21.21 |
March | 267.83 | 22.78 | 67.33 | 23.89 | 0.00 | 0.00 |
April | 117.17 | 23.08 | 165.50 | 23.89 | 5.67 | 23.89 |
May | 41.00 | 23.48 | 319.33 | 23.89 | 18.33 | 23.89 |
June | 12.50 | 23.59 | 350.17 | 23.89 | 4.50 | 23.89 |
July | 36.67 | 23.89 | 392.50 | 23.89 | 36.67 | 23.89 |
August | 36.00 | 23.89 | 401.83 | 23.89 | 36.00 | 23.89 |
September | 41.67 | 23.73 | 355.33 | 23.89 | 30.00 | 23.89 |
October | 146.17 | 22.94 | 145.50 | 23.89 | 29.67 | 23.87 |
November | 299.17 | 22.59 | 57.00 | 23.72 | 12.33 | 23.13 |
December | 394.33 | 21.73 | 56.83 | 21.74 | 52.33 | 21.55 |
Annual Sum or Average | 2154.17 | 22.26 | 2554.00 | 23.59 | 464.67 | 22.23 |
Minimum of Months | 12.50 | 21.36 | 56.83 | 21.22 | 0.00 | 0.00 |
Maximum of Months | 411.17 | 23.89 | 401.83 | 23.89 | 162.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 396.17 | 22.08 | 125.00 | 21.11 | 125.00 | 21.11 |
February | 289.50 | 22.26 | 76.17 | 21.32 | 70.50 | 21.11 |
March | 219.83 | 23.15 | 90.83 | 23.67 | 7.17 | 21.11 |
April | 128.67 | 23.43 | 181.33 | 23.85 | 8.50 | 23.12 |
May | 66.00 | 23.77 | 316.67 | 23.89 | 40.50 | 23.89 |
June | 8.00 | 23.79 | 350.67 | 23.89 | 0.00 | 0.00 |
July | 11.67 | 23.89 | 401.67 | 23.89 | 11.67 | 23.89 |
August | 0.00 | 0.00 | 412.83 | 23.89 | 0.00 | 0.00 |
September | 6.17 | 23.79 | 368.17 | 23.89 | 1.67 | 23.89 |
October | 98.50 | 23.34 | 223.67 | 23.89 | 19.33 | 23.89 |
November | 199.17 | 23.22 | 90.67 | 23.74 | 11.00 | 22.67 |
December | 354.17 | 22.73 | 66.50 | 22.41 | 40.33 | 21.44 |
Annual Sum or Average | 1777.83 | 22.75 | 2704.17 | 23.64 | 335.67 | 21.86 |
Minimum of Months | 0.00 | 0.00 | 66.50 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 396.17 | 23.89 | 412.83 | 23.89 | 125.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 412.50 | 21.55 | 187.33 | 21.19 | 187.33 | 21.19 |
February | 332.67 | 21.92 | 116.83 | 21.19 | 116.83 | 21.19 |
March | 284.33 | 22.74 | 79.00 | 23.36 | 15.00 | 21.11 |
April | 184.00 | 23.07 | 143.50 | 23.79 | 17.50 | 23.09 |
May | 105.67 | 23.57 | 289.00 | 23.89 | 57.83 | 23.87 |
June | 21.33 | 23.66 | 340.00 | 23.89 | 8.50 | 23.89 |
July | 42.33 | 23.89 | 400.33 | 23.89 | 42.33 | 23.89 |
August | 23.00 | 23.89 | 411.00 | 23.89 | 23.00 | 23.89 |
September | 37.83 | 23.70 | 356.17 | 23.89 | 22.83 | 23.89 |
October | 152.50 | 22.89 | 191.67 | 23.89 | 31.17 | 23.87 |
November | 251.83 | 22.66 | 75.17 | 23.61 | 17.33 | 22.69 |
December | 386.67 | 22.05 | 91.83 | 21.85 | 76.17 | 21.43 |
Annual Sum or Average | 2234.67 | 22.40 | 2681.83 | 23.48 | 615.83 | 22.12 |
Minimum of Months | 21.33 | 21.55 | 75.17 | 21.19 | 8.50 | 21.11 |
Maximum of Months | 412.50 | 23.89 | 411.00 | 23.89 | 187.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.28656 | 30.56204 | -0.5719 | 12.87673 |
February | 376.00000 | 21.90269 | 32.47233 | -0.3784 | 10.32627 |
March | 422.00000 | 22.91922 | 38.06577 | -0.0263 | 6.94349 |
April | 405.00000 | 23.55243 | 43.98788 | 0.21381 | 7.01482 |
May | 418.00000 | 23.84049 | 51.49035 | -0.5162 | 11.00689 |
June | 408.00000 | 23.88663 | 51.08495 | -0.4202 | 8.87093 |
July | 415.00000 | 23.88958 | 55.45857 | -0.3686 | 7.91617 |
August | 422.00000 | 23.88958 | 55.52233 | -0.3614 | 7.79974 |
September | 405.00000 | 23.88157 | 53.74199 | -0.4484 | 9.34233 |
October | 414.00000 | 23.54493 | 47.29609 | 0.25195 | 7.21429 |
November | 399.00000 | 22.78759 | 38.00629 | -0.0543 | 7.16289 |
December | 415.00000 | 21.64269 | 35.08383 | -0.4014 | 9.96086 |
Annual Sum or Average | 4913.00000 | 23.09362 | 44.49885 | -0.2568 | 8.86298 |
Minimum of Months | 376.00000 | 21.28656 | 30.56204 | -0.5719 | 6.94349 |
Maximum of Months | 422.00000 | 23.88958 | 55.52233 | 0.25195 | 12.87673 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.37035 | 27.60365 | -0.4412 | 10.22396 |
February | 376.00000 | 22.11067 | 29.71252 | -0.2138 | 8.50392 |
March | 422.00000 | 23.18139 | 34.96709 | 0.14429 | 6.92172 |
April | 405.00000 | 23.64812 | 41.47454 | 0.33252 | 8.01216 |
May | 418.00000 | 23.84203 | 48.94258 | -0.4212 | 9.07839 |
June | 408.00000 | 23.88014 | 50.82769 | -0.3522 | 7.84612 |
July | 415.00000 | 23.88937 | 56.57666 | -0.3034 | 7.06488 |
August | 422.00000 | 23.88961 | 57.04337 | -0.2983 | 6.99365 |
September | 405.00000 | 23.86781 | 53.71733 | -0.3842 | 8.29813 |
October | 414.00000 | 23.54839 | 45.44980 | 0.33395 | 8.09982 |
November | 399.00000 | 22.91511 | 35.67906 | 0.07091 | 6.96247 |
December | 415.00000 | 21.83192 | 32.31343 | -0.2543 | 8.01532 |
Annual Sum or Average | 4913.00000 | 23.17208 | 42.97134 | -0.1493 | 7.99792 |
Minimum of Months | 376.00000 | 21.37035 | 27.60365 | -0.4412 | 6.92172 |
Maximum of Months | 422.00000 | 23.88961 | 57.04337 | 0.33395 | 10.22396 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.15026 | 25.63176 | -0.2887 | 9.12807 |
February | 376.00000 | 22.62888 | 27.46749 | -0.1185 | 8.39914 |
March | 422.00000 | 23.49787 | 32.73544 | 0.19901 | 7.38809 |
April | 405.00000 | 23.73856 | 40.51208 | 0.33418 | 8.20894 |
May | 418.00000 | 23.87026 | 48.80413 | -0.4140 | 9.01304 |
June | 408.00000 | 23.88775 | 49.39651 | -0.3292 | 7.57566 |
July | 415.00000 | 23.88973 | 54.04308 | -0.2715 | 6.72631 |
August | 422.00000 | 23.88970 | 53.61324 | -0.2433 | 6.43066 |
September | 405.00000 | 23.88829 | 50.95742 | -0.3256 | 7.49301 |
October | 414.00000 | 23.75759 | 43.13958 | 0.40407 | 9.12350 |
November | 399.00000 | 23.54929 | 32.61407 | 0.22822 | 7.39885 |
December | 415.00000 | 22.88961 | 29.04259 | -0.0343 | 7.30122 |
Annual Sum or Average | 4913.00000 | 23.47533 | 40.77567 | -0.0723 | 7.84387 |
Minimum of Months | 376.00000 | 22.15026 | 25.63176 | -0.4140 | 6.43066 |
Maximum of Months | 422.00000 | 23.88973 | 54.04308 | 0.40407 | 9.12807 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.55311 | 26.74439 | -0.4381 | 10.67074 |
February | 376.00000 | 22.13686 | 28.76483 | -0.2485 | 9.24388 |
March | 422.00000 | 23.10533 | 34.41307 | 0.08840 | 7.30880 |
April | 405.00000 | 23.51086 | 42.12488 | 0.25802 | 7.72660 |
May | 418.00000 | 23.80479 | 50.69066 | -0.4711 | 10.39405 |
June | 408.00000 | 23.87734 | 51.33941 | -0.3609 | 8.07852 |
July | 415.00000 | 23.88939 | 56.55391 | -0.2960 | 6.99009 |
August | 422.00000 | 23.88964 | 55.89708 | -0.2706 | 6.69966 |
September | 405.00000 | 23.87031 | 52.94236 | -0.3612 | 8.07231 |
October | 414.00000 | 23.51877 | 44.78313 | 0.33064 | 8.55029 |
November | 399.00000 | 23.11001 | 34.35957 | 0.11180 | 7.32738 |
December | 415.00000 | 22.16791 | 30.92068 | -0.2052 | 8.18516 |
Annual Sum or Average | 4913.00000 | 23.21016 | 42.57840 | -0.1555 | 8.26490 |
Minimum of Months | 376.00000 | 21.55311 | 26.74439 | -0.4711 | 6.69966 |
Maximum of Months | 422.00000 | 23.88964 | 56.55391 | 0.33064 | 10.67074 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 216.83 | 61.43 | 0.33 | 149.71 | 67.11 | 0.00 | 0.00 | 20-JAN-15:50 | 0.00 | 01-JAN-00:10 | 0.26 | 20-JAN-15:50 | 0.18 | 20-JAN-15:50 | 0.08 | 20-JAN-15:50 | 0.07 | 20-JAN-15:50 | 0.00 | 01-JAN-00:10 |
February | 0.165178E+09 | 45871976.57 | 25.58 | 0.165178E+09 | 1.61 | 0.00 | 0.40 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 6074.85 | 28-FEB-15:10 | 6074.85 | 28-FEB-15:10 | 0.00 | 22-FEB-14:35 | 1651.86 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.134921E+10 | 0.357339E+09 | 123.28 | 0.106049E+10 | 0.288718E+09 | 0.00 | 1.00 | 30-MAR-22:40 | 0.00 | 01-MAR-00:10 | 38158.86 | 30-MAR-22:40 | 29366.39 | 30-MAR-22:40 | 8971.45 | 30-MAR-22:43 | 8223.97 | 30-MAR-22:40 | 0.00 | 01-MAR-00:10 |
April | 0.474672E+10 | 0.125132E+10 | 246.55 | 0.392577E+10 | 0.820952E+09 | 0.00 | 0.74 | 15-APR-14:00 | 0.00 | 01-APR-00:10 | 29873.72 | 17-APR-20:51 | 24252.62 | 17-APR-20:51 | 5621.09 | 17-APR-20:51 | 6363.19 | 17-APR-20:51 | 0.00 | 01-APR-00:10 |
May | 0.120570E+11 | 0.305516E+10 | 371.12 | 0.908305E+10 | 0.297392E+10 | 0.00 | 1.00 | 04-MAY-20:28 | 0.00 | 01-MAY-00:10 | 39589.79 | 26-MAY-20:30 | 36010.24 | 14-MAY-18:35 | 20231.43 | 26-MAY-20:30 | 8416.92 | 19-MAY-21:00 | 0.00 | 01-MAY-00:10 |
June | 0.226078E+11 | 0.567144E+10 | 524.49 | 0.169844E+11 | 0.562342E+10 | 0.00 | 1.00 | 02-JUN-01:30 | 0.00 | 01-JUN-00:05 | 38290.13 | 07-JUN-01:52 | 35906.30 | 08-JUN-20:18 | 15419.28 | 07-JUN-01:52 | 8405.43 | 09-JUN-20:15 | 0.00 | 01-JUN-00:05 |
July | 0.272437E+11 | 0.682245E+10 | 591.91 | 0.195838E+11 | 0.765988E+10 | 0.00 | 1.00 | 07-JUL-20:08 | 0.00 | 01-JUL-00:05 | 38113.94 | 21-JUL-20:10 | 30520.44 | 16-JUL-18:10 | 17063.32 | 28-JUL-20:32 | 9564.16 | 09-JUL-18:10 | 0.00 | 01-JUL-00:05 |
August | 0.294402E+11 | 0.729790E+10 | 618.31 | 0.207859E+11 | 0.865428E+10 | 0.00 | 1.00 | 01-AUG-20:10 | 0.00 | 01-AUG-00:05 | 39104.45 | 04-AUG-20:10 | 30011.11 | 01-AUG-20:10 | 10250.11 | 29-AUG-20:10 | 9506.54 | 06-AUG-18:10 | 0.00 | 01-AUG-00:05 |
September | 0.170569E+11 | 0.422519E+10 | 472.71 | 0.122625E+11 | 0.479436E+10 | 0.00 | 1.00 | 07-SEP-20:10 | 0.00 | 01-SEP-00:15 | 39097.05 | 17-SEP-20:01 | 32441.16 | 14-SEP-20:19 | 15467.14 | 24-SEP-01:05 | 8953.70 | 08-SEP-20:10 | 0.00 | 01-SEP-00:05 |
October | 0.502158E+10 | 0.125678E+10 | 234.81 | 0.358534E+10 | 0.143625E+10 | 0.00 | 1.00 | 02-OCT-22:22 | 0.00 | 01-OCT-00:05 | 38478.61 | 19-OCT-21:20 | 23775.01 | 02-OCT-22:22 | 17258.78 | 19-OCT-21:20 | 8179.72 | 19-OCT-21:20 | 0.00 | 01-OCT-00:05 |
November | 0.564065E+09 | 0.149294E+09 | 94.06 | 0.396514E+09 | 0.167550E+09 | 0.00 | 0.50 | 05-NOV-15:20 | 0.00 | 01-NOV-00:10 | 8394.80 | 05-NOV-15:00 | 5915.50 | 05-NOV-16:00 | 3464.58 | 04-NOV-16:00 | 2147.64 | 05-NOV-15:20 | 0.00 | 01-NOV-00:10 |
December | 38179279.66 | 10554508.44 | 11.22 | 27078705.14 | 11100574.52 | 0.00 | 0.21 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 | 3171.70 | 12-DEC-15:10 | 2398.70 | 12-DEC-15:10 | 828.61 | 12-DEC-14:00 | 871.51 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.120290E+12 | 0.301433E+11 | 3314.36 | 0.878601E+11 | 0.324304E+11 | 0.00 | ||||||||||||||
Minimum of Months | 216.83 | 61.43 | 0.33 | 149.71 | 1.61 | 0.00 | 0.00 | 0.00 | 0.26 | 0.18 | 0.00 | 0.07 | 0.00 | |||||||
Maximum of Months | 0.294402E+11 | 0.729790E+10 | 618.31 | 0.207859E+11 | 0.865428E+10 | 0.00 | 1.00 | 0.00 | 39589.79 | 36010.24 | 20231.43 | 9564.16 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 45260486.87 | 14094270.20 | 9.17 | 37394061.16 | 7866425.71 | 0.00 | 0.11 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 | 7760.19 | 31-JAN-15:10 | 6574.27 | 31-JAN-15:10 | 1185.92 | 31-JAN-15:10 | 2393.88 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.229230E+10 | 0.690809E+09 | 58.88 | 0.226592E+10 | 26375868.73 | 0.00 | 0.84 | 28-FEB-21:41 | 0.00 | 01-FEB-00:10 | 159298.32 | 28-FEB-21:41 | 149966.82 | 28-FEB-21:41 | 9331.50 | 28-FEB-21:41 | 37695.31 | 28-FEB-21:41 | 0.00 | 01-FEB-00:10 |
March | 0.123244E+11 | 0.354615E+10 | 180.22 | 0.949349E+10 | 0.283088E+10 | 0.00 | 1.00 | 08-MAR-21:55 | 0.00 | 01-MAR-00:10 | 190372.45 | 29-MAR-23:51 | 176780.19 | 10-MAR-21:45 | 66659.20 | 31-MAR-03:45 | 45243.74 | 29-MAR-23:51 | 0.00 | 01-MAR-00:10 |
April | 0.346518E+11 | 0.987182E+10 | 290.13 | 0.273962E+11 | 0.725563E+10 | 0.00 | 1.00 | 09-APR-18:40 | 0.00 | 01-APR-00:10 | 195965.04 | 30-APR-20:05 | 169620.36 | 09-APR-18:40 | 100962.18 | 30-APR-20:05 | 46306.48 | 30-APR-20:05 | 0.00 | 01-APR-00:10 |
May | 0.721847E+11 | 0.201085E+11 | 424.23 | 0.521092E+11 | 0.200755E+11 | 0.00 | 1.00 | 01-MAY-20:20 | 0.00 | 01-MAY-00:10 | 197750.55 | 25-MAY-20:20 | 173325.23 | 09-MAY-20:25 | 103332.92 | 26-MAY-20:20 | 46597.86 | 25-MAY-20:20 | 0.00 | 01-MAY-00:10 |
June | 0.112752E+12 | 0.312931E+11 | 531.85 | 0.795723E+11 | 0.331801E+11 | 0.00 | 1.00 | 02-JUN-02:00 | 0.00 | 01-JUN-00:05 | 188500.76 | 03-JUN-22:41 | 176503.83 | 10-JUN-21:18 | 65098.80 | 02-JUN-02:55 | 46820.07 | 09-JUN-20:11 | 0.00 | 01-JUN-00:05 |
July | 0.131953E+12 | 0.363826E+11 | 576.45 | 0.868209E+11 | 0.451319E+11 | 0.00 | 1.00 | 07-JUL-20:10 | 0.00 | 01-JUL-00:05 | 198542.38 | 28-JUL-20:20 | 139373.37 | 21-JUL-20:10 | 107068.47 | 28-JUL-20:20 | 53215.55 | 09-JUL-18:10 | 0.00 | 01-JUL-00:05 |
August | 0.141430E+12 | 0.386258E+11 | 604.03 | 0.909051E+11 | 0.505250E+11 | 0.00 | 1.00 | 01-AUG-20:10 | 0.00 | 01-AUG-00:05 | 196113.98 | 04-AUG-20:10 | 138322.13 | 18-AUG-20:10 | 62796.18 | 10-AUG-20:10 | 52521.91 | 18-AUG-20:10 | 0.00 | 01-AUG-00:05 |
September | 0.861541E+11 | 0.236597E+11 | 475.17 | 0.569711E+11 | 0.291830E+11 | 0.00 | 1.00 | 13-SEP-20:16 | 0.00 | 01-SEP-00:05 | 198645.50 | 21-SEP-20:20 | 149148.46 | 14-SEP-20:16 | 101353.09 | 21-SEP-20:22 | 47658.47 | 07-SEP-20:10 | 0.00 | 01-SEP-00:05 |
October | 0.319847E+11 | 0.887090E+10 | 268.98 | 0.221775E+11 | 0.980725E+10 | 0.00 | 1.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:10 | 192156.84 | 15-OCT-18:31 | 160374.11 | 11-OCT-20:12 | 88358.47 | 01-OCT-00:05 | 45619.00 | 15-OCT-18:31 | 0.00 | 01-OCT-00:05 |
November | 0.662618E+10 | 0.192243E+10 | 126.61 | 0.477300E+10 | 0.185318E+10 | 0.00 | 1.00 | 02-NOV-20:22 | 0.00 | 01-NOV-00:10 | 193047.17 | 04-NOV-21:45 | 117489.40 | 02-NOV-20:22 | 92154.28 | 04-NOV-21:45 | 45779.62 | 04-NOV-21:45 | 0.00 | 01-NOV-00:10 |
December | 0.886726E+09 | 0.264822E+09 | 21.61 | 0.570311E+09 | 0.316415E+09 | 0.00 | 0.39 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 | 30386.78 | 12-DEC-15:10 | 21942.99 | 12-DEC-15:10 | 10613.61 | 13-DEC-13:00 | 8897.96 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.633285E+12 | 0.175251E+12 | 3567.32 | 0.433092E+12 | 0.200193E+12 | 0.00 | ||||||||||||||
Minimum of Months | 45260486.87 | 14094270.20 | 9.17 | 37394061.16 | 7866425.71 | 0.00 | 0.11 | 0.00 | 7760.19 | 6574.27 | 1185.92 | 2393.88 | 0.00 | |||||||
Maximum of Months | 0.141430E+12 | 0.386258E+11 | 604.03 | 0.909051E+11 | 0.505250E+11 | 0.00 | 1.00 | 0.00 | 198645.50 | 176780.19 | 107068.47 | 53215.55 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 28144341.11 | 7183319.15 | 40.05 | 25017649.06 | 3126692.05 | 0.00 | 0.26 | 31-JAN-15:00 | 0.00 | 01-JAN-00:10 | 2649.05 | 31-JAN-15:00 | 2509.38 | 31-JAN-15:00 | 234.75 | 31-JAN-13:50 | 663.57 | 31-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.737007E+09 | 0.175566E+09 | 93.44 | 0.735901E+09 | 1106029.81 | 0.00 | 1.00 | 26-FEB-19:20 | 0.00 | 01-FEB-00:10 | 22500.62 | 26-FEB-19:20 | 22500.62 | 26-FEB-19:20 | 161.25 | 16-FEB-17:00 | 4763.71 | 26-FEB-19:20 | 0.00 | 01-FEB-00:10 |
March | 0.231423E+10 | 0.545868E+09 | 233.46 | 0.195418E+10 | 0.360046E+09 | 0.00 | 1.00 | 08-MAR-21:20 | 0.00 | 01-MAR-00:10 | 24479.45 | 28-MAR-22:01 | 22500.62 | 26-MAR-18:35 | 7793.25 | 28-MAR-22:01 | 5198.13 | 28-MAR-22:01 | 0.00 | 01-MAR-00:10 |
April | 0.548766E+10 | 0.130038E+10 | 294.54 | 0.472886E+10 | 0.758804E+09 | 0.00 | 1.00 | 04-APR-21:02 | 0.00 | 01-APR-00:10 | 24887.45 | 30-APR-18:32 | 22500.62 | 09-APR-18:30 | 11738.35 | 22-APR-21:32 | 5265.57 | 30-APR-18:32 | 0.00 | 01-APR-00:10 |
May | 0.103595E+11 | 0.243676E+10 | 419.85 | 0.827387E+10 | 0.208562E+10 | 0.00 | 1.00 | 04-MAY-21:40 | 0.00 | 01-MAY-00:10 | 25078.80 | 24-MAY-20:20 | 22521.22 | 14-MAY-18:11 | 11868.34 | 26-MAY-22:52 | 5294.25 | 24-MAY-20:20 | 0.00 | 01-MAY-00:10 |
June | 0.168362E+11 | 0.400806E+10 | 553.07 | 0.132063E+11 | 0.362998E+10 | 0.00 | 1.00 | 02-JUN-00:48 | 0.00 | 01-JUN-00:05 | 24460.24 | 07-JUN-01:30 | 22543.28 | 10-JUN-21:11 | 10075.79 | 07-JUN-01:30 | 5316.74 | 09-JUN-20:11 | 0.00 | 01-JUN-00:05 |
July | 0.200619E+11 | 0.479721E+10 | 619.32 | 0.150359E+11 | 0.502599E+10 | 0.00 | 1.00 | 07-JUL-20:08 | 0.00 | 01-JUL-00:10 | 23823.57 | 21-JUL-20:08 | 18614.70 | 14-JUL-20:08 | 6545.07 | 26-JUL-20:10 | 5957.96 | 16-JUL-18:08 | 0.00 | 01-JUL-00:05 |
August | 0.224214E+11 | 0.531133E+10 | 645.86 | 0.166768E+11 | 0.574454E+10 | 0.00 | 1.00 | 02-AUG-20:08 | 0.00 | 01-AUG-00:10 | 24642.00 | 04-AUG-20:08 | 18740.37 | 18-AUG-20:08 | 6743.10 | 08-AUG-20:10 | 5997.28 | 06-AUG-18:08 | 0.00 | 01-AUG-00:05 |
September | 0.147177E+11 | 0.340750E+10 | 524.57 | 0.113558E+11 | 0.336196E+10 | 0.00 | 1.00 | 07-SEP-20:08 | 0.00 | 01-SEP-00:05 | 24757.84 | 29-SEP-20:20 | 20165.34 | 14-SEP-20:10 | 11282.55 | 22-SEP-01:40 | 5621.74 | 07-SEP-20:08 | 0.00 | 01-SEP-00:05 |
October | 0.629050E+10 | 0.143217E+10 | 312.65 | 0.505215E+10 | 0.123835E+10 | 0.00 | 1.00 | 02-OCT-21:21 | 0.00 | 01-OCT-00:05 | 24627.51 | 02-OCT-21:21 | 21827.52 | 11-OCT-20:10 | 10585.51 | 11-OCT-03:30 | 5223.57 | 02-OCT-21:21 | 0.00 | 01-OCT-00:05 |
November | 0.191157E+10 | 0.448387E+09 | 190.33 | 0.157416E+10 | 0.337404E+09 | 0.00 | 1.00 | 01-NOV-20:15 | 0.00 | 01-NOV-00:10 | 24533.82 | 03-NOV-20:22 | 15596.58 | 02-NOV-21:00 | 10263.94 | 03-NOV-23:55 | 5207.60 | 03-NOV-20:22 | 0.00 | 01-NOV-00:10 |
December | 0.355728E+09 | 83171113.22 | 97.77 | 0.257219E+09 | 98508156.29 | 0.00 | 1.00 | 12-DEC-22:00 | 0.00 | 01-DEC-00:10 | 23881.32 | 12-DEC-22:45 | 16397.04 | 12-DEC-22:00 | 7673.42 | 12-DEC-22:45 | 5084.65 | 12-DEC-22:45 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.101522E+12 | 0.239536E+11 | 4024.90 | 0.788761E+11 | 0.226454E+11 | 0.00 | ||||||||||||||
Minimum of Months | 28144341.11 | 7183319.15 | 40.05 | 25017649.06 | 1106029.81 | 0.00 | 0.26 | 0.00 | 2649.05 | 2509.38 | 161.25 | 663.57 | 0.00 | |||||||
Maximum of Months | 0.224214E+11 | 0.531133E+10 | 645.86 | 0.166768E+11 | 0.574454E+10 | 0.00 | 1.00 | 0.00 | 25078.80 | 22543.28 | 11868.34 | 5997.28 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 3277923.46 | 863802.35 | 14.72 | 2943613.86 | 334309.59 | 0.00 | 0.09 | 31-JAN-15:00 | 0.00 | 01-JAN-00:10 | 732.33 | 31-JAN-15:00 | 674.47 | 31-JAN-15:00 | 64.12 | 31-JAN-14:40 | 191.87 | 31-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.437445E+09 | 0.106241E+09 | 64.13 | 0.437298E+09 | 146304.36 | 0.00 | 1.00 | 26-FEB-19:31 | 0.00 | 01-FEB-00:10 | 18529.42 | 26-FEB-19:31 | 18529.42 | 26-FEB-19:31 | 744.17 | 28-FEB-21:41 | 3922.94 | 26-FEB-19:31 | 0.00 | 01-FEB-00:10 |
March | 0.136208E+10 | 0.328035E+09 | 178.75 | 0.111947E+10 | 0.242605E+09 | 0.00 | 1.00 | 13-MAR-20:19 | 0.00 | 01-MAR-00:10 | 19801.61 | 30-MAR-23:01 | 16370.61 | 13-MAR-20:19 | 5671.68 | 31-MAR-00:40 | 4231.50 | 30-MAR-23:01 | 0.00 | 01-MAR-00:10 |
April | 0.344832E+10 | 0.836750E+09 | 253.04 | 0.291401E+10 | 0.534312E+09 | 0.00 | 1.00 | 11-APR-20:30 | 0.00 | 01-APR-00:10 | 20495.69 | 21-APR-20:45 | 16811.61 | 16-APR-19:55 | 9009.89 | 21-APR-20:45 | 4336.34 | 21-APR-20:45 | 0.00 | 01-APR-00:10 |
May | 0.703085E+10 | 0.167495E+10 | 363.78 | 0.539627E+10 | 0.163458E+10 | 0.00 | 1.00 | 02-MAY-20:21 | 0.00 | 01-MAY-00:10 | 20859.11 | 25-MAY-20:32 | 18147.87 | 14-MAY-18:20 | 10895.20 | 26-MAY-20:25 | 4388.37 | 25-MAY-20:32 | 0.00 | 01-MAY-00:10 |
June | 0.129777E+11 | 0.308765E+10 | 521.95 | 0.967225E+10 | 0.330544E+10 | 0.00 | 1.00 | 02-JUN-01:06 | 0.00 | 01-JUN-00:10 | 20048.10 | 07-JUN-01:50 | 18501.72 | 10-JUN-21:40 | 8351.11 | 07-JUN-01:50 | 4466.00 | 25-JUN-18:10 | 0.00 | 01-JUN-00:05 |
July | 0.158631E+11 | 0.377905E+10 | 594.03 | 0.112650E+11 | 0.459807E+10 | 0.00 | 1.00 | 07-JUL-20:08 | 0.00 | 01-JUL-00:05 | 20857.66 | 28-JUL-20:32 | 14905.83 | 16-JUL-18:08 | 11300.68 | 28-JUL-20:32 | 4976.78 | 09-JUL-18:08 | 0.00 | 01-JUL-00:05 |
August | 0.180852E+11 | 0.426522E+10 | 632.35 | 0.127201E+11 | 0.536512E+10 | 0.00 | 1.00 | 01-AUG-20:08 | 0.00 | 01-AUG-00:10 | 20423.28 | 04-AUG-20:08 | 14800.75 | 18-AUG-20:08 | 6763.34 | 08-AUG-20:10 | 4943.79 | 06-AUG-18:08 | 0.00 | 01-AUG-00:05 |
September | 0.111701E+11 | 0.259032E+10 | 488.13 | 0.817587E+10 | 0.299426E+10 | 0.00 | 1.00 | 07-SEP-20:08 | 0.00 | 01-SEP-00:05 | 20740.42 | 21-SEP-20:20 | 16221.71 | 14-SEP-20:10 | 10262.38 | 21-SEP-23:00 | 4658.28 | 08-SEP-20:08 | 0.00 | 01-SEP-00:05 |
October | 0.454900E+10 | 0.104130E+10 | 266.94 | 0.349284E+10 | 0.105617E+10 | 0.00 | 1.00 | 02-OCT-21:21 | 0.00 | 01-OCT-00:05 | 20313.72 | 02-OCT-21:21 | 17542.76 | 11-OCT-20:10 | 8798.01 | 19-OCT-20:20 | 4307.13 | 02-OCT-21:21 | 0.00 | 01-OCT-00:05 |
November | 0.103340E+10 | 0.247888E+09 | 142.22 | 0.843510E+09 | 0.189885E+09 | 0.00 | 1.00 | 02-NOV-20:22 | 0.00 | 01-NOV-00:10 | 20233.07 | 03-NOV-20:30 | 12577.34 | 02-NOV-20:22 | 8587.35 | 03-NOV-20:30 | 4293.53 | 03-NOV-20:30 | 0.00 | 01-NOV-00:10 |
December | 0.171951E+09 | 41124802.81 | 42.47 | 0.122844E+09 | 49106162.01 | 0.00 | 1.00 | 12-DEC-21:45 | 0.00 | 01-DEC-00:10 | 19645.69 | 12-DEC-21:45 | 13209.36 | 12-DEC-21:45 | 6436.33 | 12-DEC-21:45 | 4183.01 | 12-DEC-21:45 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.761324E+11 | 0.179994E+11 | 3562.52 | 0.561624E+11 | 0.199700E+11 | 0.00 | ||||||||||||||
Minimum of Months | 3277923.46 | 863802.35 | 14.72 | 2943613.86 | 146304.36 | 0.00 | 0.09 | 0.00 | 732.33 | 674.47 | 64.12 | 191.87 | 0.00 | |||||||
Maximum of Months | 0.180852E+11 | 0.426522E+10 | 632.35 | 0.127201E+11 | 0.536512E+10 | 0.00 | 1.00 | 0.00 | 20859.11 | 18529.42 | 11300.68 | 4976.78 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.29 | 17.31 | 13.98 | 28.04 | 99.21 | 2.50 | 0.00 | 744.00 |
February | 39.09 | 24.21 | 14.87 | 46.45 | 85.83 | 6.17 | 0.00 | 672.00 |
March | 56.69 | 34.62 | 22.07 | 82.45 | 60.83 | 0.00 | 0.00 | 744.00 |
April | 71.28 | 43.92 | 27.36 | 118.58 | 49.28 | 0.00 | 0.00 | 720.00 |
May | 78.92 | 45.26 | 33.66 | 140.83 | 33.01 | 0.00 | 0.00 | 744.00 |
June | 84.20 | 49.25 | 34.95 | 161.52 | 23.38 | 0.00 | 0.00 | 720.00 |
July | 78.41 | 44.00 | 34.41 | 154.80 | 17.05 | 0.00 | 0.00 | 744.00 |
August | 72.18 | 39.15 | 33.03 | 143.88 | 15.95 | 0.00 | 0.00 | 744.00 |
September | 54.05 | 30.02 | 24.02 | 96.41 | 30.52 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 31.16 | 15.21 | 71.22 | 57.11 | 0.00 | 0.00 | 744.00 |
November | 34.55 | 19.57 | 14.98 | 43.23 | 74.58 | 9.50 | 0.00 | 720.00 |
December | 28.29 | 15.43 | 12.86 | 27.41 | 87.46 | 17.50 | 0.00 | 744.00 |
Annual Sum or Average | 56.36 | 32.86 | 23.50 | 93.15 | 52.67 | 35.67 | 0.00 | 8760.00 |
Minimum of Months | 28.29 | 15.43 | 12.86 | 27.41 | 15.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.20 | 49.25 | 34.95 | 161.52 | 99.21 | 17.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 851.70 | 593.59 | 258.11 | 914.38 | 1206.09 | 0.00 | 0.00 | 744.00 |
February | 795.52 | 533.24 | 262.28 | 921.74 | 1047.21 | 0.00 | 0.00 | 672.00 |
March | 716.39 | 373.77 | 342.62 | 848.02 | 742.51 | 0.00 | 0.00 | 744.00 |
April | 537.33 | 175.91 | 361.42 | 665.85 | 595.55 | 0.00 | 0.00 | 720.00 |
May | 433.84 | 51.21 | 382.63 | 583.29 | 380.83 | 0.00 | 0.00 | 744.00 |
June | 400.81 | 22.78 | 378.03 | 710.88 | 225.49 | 0.00 | 0.00 | 720.00 |
July | 405.30 | 30.78 | 374.53 | 769.37 | 148.21 | 0.00 | 0.00 | 744.00 |
August | 484.30 | 91.38 | 392.92 | 914.33 | 120.67 | 0.00 | 0.00 | 744.00 |
September | 532.42 | 198.68 | 333.74 | 833.21 | 316.14 | 0.00 | 0.00 | 720.00 |
October | 770.73 | 499.41 | 271.32 | 1074.15 | 696.00 | 0.00 | 0.00 | 744.00 |
November | 828.33 | 549.52 | 278.81 | 1053.39 | 899.81 | 0.00 | 0.00 | 720.00 |
December | 839.39 | 590.27 | 249.12 | 973.94 | 1064.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 632.31 | 308.16 | 324.14 | 855.10 | 617.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 400.81 | 22.78 | 249.12 | 583.29 | 120.67 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 851.70 | 593.59 | 392.92 | 1074.15 | 1206.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 851.70 | 593.59 | 258.11 | 929.56 | 1164.86 | 0.00 | 0.00 | 744.00 |
February | 795.52 | 533.24 | 262.28 | 932.67 | 1006.93 | 0.00 | 0.00 | 672.00 |
March | 716.39 | 373.77 | 342.62 | 859.14 | 707.25 | 0.00 | 0.00 | 744.00 |
April | 537.33 | 175.91 | 361.42 | 672.26 | 569.47 | 0.00 | 0.00 | 720.00 |
May | 433.84 | 51.21 | 382.63 | 584.73 | 368.60 | 0.00 | 0.00 | 744.00 |
June | 400.81 | 22.78 | 378.03 | 708.82 | 222.00 | 0.00 | 0.00 | 720.00 |
July | 405.30 | 30.78 | 374.53 | 767.69 | 144.60 | 0.00 | 0.00 | 744.00 |
August | 484.30 | 91.38 | 392.92 | 912.41 | 116.55 | 0.00 | 0.00 | 744.00 |
September | 532.42 | 198.68 | 333.74 | 832.10 | 310.71 | 0.00 | 0.00 | 720.00 |
October | 770.73 | 499.41 | 271.32 | 1077.40 | 674.47 | 0.00 | 0.00 | 744.00 |
November | 828.33 | 549.52 | 278.81 | 1063.35 | 863.39 | 0.00 | 0.00 | 720.00 |
December | 839.39 | 590.27 | 249.12 | 988.54 | 1012.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 632.31 | 308.16 | 324.14 | 860.59 | 594.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 400.81 | 22.78 | 249.12 | 584.73 | 116.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 851.70 | 593.59 | 392.92 | 1077.40 | 1164.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 175.25 | 122.14 | 53.11 | 185.89 | 236.92 | 0.00 | 0.00 | 744.00 |
February | 163.69 | 109.72 | 53.97 | 187.99 | 203.30 | 0.00 | 0.00 | 672.00 |
March | 147.41 | 76.91 | 70.50 | 176.79 | 138.61 | 0.00 | 0.00 | 744.00 |
April | 110.56 | 36.20 | 74.37 | 136.24 | 112.45 | 0.00 | 0.00 | 720.00 |
May | 89.27 | 10.54 | 78.73 | 113.62 | 74.27 | 0.00 | 0.00 | 744.00 |
June | 82.47 | 4.69 | 77.79 | 121.19 | 52.34 | 0.00 | 0.00 | 720.00 |
July | 83.40 | 6.33 | 77.06 | 127.75 | 38.63 | 0.00 | 0.00 | 744.00 |
August | 99.65 | 18.80 | 80.85 | 155.46 | 35.88 | 0.00 | 0.00 | 744.00 |
September | 109.55 | 40.88 | 68.67 | 157.67 | 68.79 | 0.00 | 0.00 | 720.00 |
October | 158.59 | 102.76 | 55.83 | 219.02 | 133.81 | 0.00 | 0.00 | 744.00 |
November | 170.44 | 113.07 | 57.37 | 218.46 | 168.42 | 0.00 | 0.00 | 720.00 |
December | 172.72 | 121.46 | 51.26 | 199.86 | 202.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 130.11 | 63.41 | 66.70 | 166.58 | 121.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 82.47 | 4.69 | 51.26 | 113.62 | 35.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 175.25 | 122.14 | 80.85 | 219.02 | 236.92 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83799660.47 | 46352794.17 | 37446866.30 | 75104850.45 | 0.265719E+09 |
February | 94558202.94 | 58580166.60 | 35978036.34 | 0.112373E+09 | 0.207646E+09 |
March | 0.151834E+09 | 92713488.18 | 59120667.73 | 0.220836E+09 | 0.162918E+09 |
April | 0.184746E+09 | 0.113831E+09 | 70914830.84 | 0.307348E+09 | 0.127732E+09 |
May | 0.211380E+09 | 0.121217E+09 | 90163510.88 | 0.377194E+09 | 88422722.18 |
June | 0.218238E+09 | 0.127649E+09 | 90589287.94 | 0.418673E+09 | 60606742.08 |
July | 0.210012E+09 | 0.117862E+09 | 92150516.67 | 0.414613E+09 | 45675047.60 |
August | 0.193326E+09 | 0.104868E+09 | 88458360.80 | 0.385362E+09 | 42731313.08 |
September | 0.140092E+09 | 77820695.27 | 62270949.54 | 0.249884E+09 | 79099102.13 |
October | 0.124200E+09 | 83466326.61 | 40733254.73 | 0.190751E+09 | 0.152973E+09 |
November | 89556384.07 | 50734915.20 | 38821468.87 | 0.112058E+09 | 0.193301E+09 |
December | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 0.234253E+09 |
Annual Sum or Average | 0.177751E+10 | 0.103643E+10 | 0.741084E+09 | 0.293762E+10 | 0.166108E+10 |
Minimum of Months | 75769170.54 | 41333115.29 | 34436055.25 | 73425820.55 | 42731313.08 |
Maximum of Months | 0.218238E+09 | 0.127649E+09 | 92150516.67 | 0.418673E+09 | 0.265719E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228118E+10 | 0.158986E+10 | 0.691321E+09 | 0.244908E+10 | 0.323040E+10 |
February | 0.192451E+10 | 0.129000E+10 | 0.634506E+09 | 0.222988E+10 | 0.253342E+10 |
March | 0.191877E+10 | 0.100110E+10 | 0.917671E+09 | 0.227135E+10 | 0.198873E+10 |
April | 0.139276E+10 | 0.455954E+09 | 0.936807E+09 | 0.172588E+10 | 0.154366E+10 |
May | 0.116199E+10 | 0.137163E+09 | 0.102483E+10 | 0.156229E+10 | 0.102003E+10 |
June | 0.103889E+10 | 59033491.93 | 0.979857E+09 | 0.184259E+10 | 0.584467E+09 |
July | 0.108556E+10 | 82430668.75 | 0.100313E+10 | 0.206067E+10 | 0.396956E+09 |
August | 0.129716E+10 | 0.244748E+09 | 0.105241E+10 | 0.244895E+10 | 0.323214E+09 |
September | 0.138003E+10 | 0.514978E+09 | 0.865048E+09 | 0.215968E+10 | 0.819437E+09 |
October | 0.206433E+10 | 0.133762E+10 | 0.726701E+09 | 0.287701E+10 | 0.186416E+10 |
November | 0.214703E+10 | 0.142435E+10 | 0.722677E+09 | 0.273039E+10 | 0.233230E+10 |
December | 0.224823E+10 | 0.158098E+10 | 0.667249E+09 | 0.260861E+10 | 0.285038E+10 |
Annual Sum or Average | 0.199404E+11 | 0.971822E+10 | 0.102222E+11 | 0.269664E+11 | 0.194871E+11 |
Minimum of Months | 0.103889E+10 | 59033491.93 | 0.634506E+09 | 0.156229E+10 | 0.323214E+09 |
Maximum of Months | 0.228118E+10 | 0.158986E+10 | 0.105241E+10 | 0.287701E+10 | 0.323040E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228118E+10 | 0.158986E+10 | 0.691321E+09 | 0.248972E+10 | 0.311995E+10 |
February | 0.192451E+10 | 0.129000E+10 | 0.634506E+09 | 0.225632E+10 | 0.243595E+10 |
March | 0.191877E+10 | 0.100110E+10 | 0.917671E+09 | 0.230113E+10 | 0.189430E+10 |
April | 0.139276E+10 | 0.455954E+09 | 0.936807E+09 | 0.174249E+10 | 0.147607E+10 |
May | 0.116199E+10 | 0.137163E+09 | 0.102483E+10 | 0.156615E+10 | 0.987271E+09 |
June | 0.103889E+10 | 59033491.93 | 0.979857E+09 | 0.183725E+10 | 0.575426E+09 |
July | 0.108556E+10 | 82430668.75 | 0.100313E+10 | 0.205617E+10 | 0.387298E+09 |
August | 0.129716E+10 | 0.244748E+09 | 0.105241E+10 | 0.244381E+10 | 0.312173E+09 |
September | 0.138003E+10 | 0.514978E+09 | 0.865048E+09 | 0.215680E+10 | 0.805353E+09 |
October | 0.206433E+10 | 0.133762E+10 | 0.726701E+09 | 0.288571E+10 | 0.180650E+10 |
November | 0.214703E+10 | 0.142435E+10 | 0.722677E+09 | 0.275620E+10 | 0.223789E+10 |
December | 0.224823E+10 | 0.158098E+10 | 0.667249E+09 | 0.264770E+10 | 0.271312E+10 |
Annual Sum or Average | 0.199404E+11 | 0.971822E+10 | 0.102222E+11 | 0.271395E+11 | 0.187513E+11 |
Minimum of Months | 0.103889E+10 | 59033491.93 | 0.634506E+09 | 0.156615E+10 | 0.312173E+09 |
Maximum of Months | 0.228118E+10 | 0.158986E+10 | 0.105241E+10 | 0.288571E+10 | 0.311995E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.469386E+09 | 0.327137E+09 | 0.142249E+09 | 0.497878E+09 | 0.634561E+09 |
February | 0.395996E+09 | 0.265437E+09 | 0.130559E+09 | 0.454783E+09 | 0.491818E+09 |
March | 0.394814E+09 | 0.205990E+09 | 0.188824E+09 | 0.473501E+09 | 0.371247E+09 |
April | 0.286581E+09 | 93819260.29 | 0.192762E+09 | 0.353125E+09 | 0.291470E+09 |
May | 0.239097E+09 | 28223201.27 | 0.210874E+09 | 0.304328E+09 | 0.198916E+09 |
June | 0.213767E+09 | 12147000.56 | 0.201620E+09 | 0.314118E+09 | 0.135661E+09 |
July | 0.223370E+09 | 16961310.38 | 0.206408E+09 | 0.342173E+09 | 0.103464E+09 |
August | 0.266909E+09 | 50360534.73 | 0.216549E+09 | 0.416379E+09 | 96092654.08 |
September | 0.283960E+09 | 0.105964E+09 | 0.177996E+09 | 0.408681E+09 | 0.178300E+09 |
October | 0.424765E+09 | 0.275236E+09 | 0.149529E+09 | 0.586616E+09 | 0.358409E+09 |
November | 0.441782E+09 | 0.293080E+09 | 0.148701E+09 | 0.566257E+09 | 0.436541E+09 |
December | 0.462606E+09 | 0.325310E+09 | 0.137296E+09 | 0.535303E+09 | 0.543470E+09 |
Annual Sum or Average | 0.410303E+10 | 0.199967E+10 | 0.210337E+10 | 0.525314E+10 | 0.383995E+10 |
Minimum of Months | 0.213767E+09 | 12147000.56 | 0.130559E+09 | 0.304328E+09 | 96092654.08 |
Maximum of Months | 0.469386E+09 | 0.327137E+09 | 0.216549E+09 | 0.586616E+09 | 0.634561E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 448.66 | 1587.33 | 500.60 | 276.90 | 223.70 | 0.00 | 0.00 |
February | 743.21 | 1373.32 | 625.38 | 387.43 | 237.95 | 0.00 | 0.00 |
March | 1319.21 | 973.23 | 907.01 | 553.84 | 353.17 | 0.00 | 0.00 |
April | 1897.21 | 788.47 | 1140.40 | 702.66 | 437.75 | 0.00 | 0.00 |
May | 2253.25 | 528.21 | 1262.72 | 724.11 | 538.61 | 0.00 | 0.00 |
June | 2584.40 | 374.12 | 1347.15 | 787.96 | 559.19 | 0.00 | 0.00 |
July | 2476.78 | 272.85 | 1254.55 | 704.07 | 550.48 | 0.00 | 0.00 |
August | 2302.04 | 255.26 | 1154.88 | 626.45 | 528.43 | 0.00 | 0.00 |
September | 1542.50 | 488.27 | 864.76 | 480.37 | 384.39 | 0.00 | 0.00 |
October | 1139.49 | 913.81 | 741.93 | 498.60 | 243.33 | 0.00 | 0.00 |
November | 691.72 | 1193.22 | 552.82 | 313.18 | 239.64 | 0.00 | 0.00 |
December | 438.62 | 1399.36 | 452.62 | 246.91 | 205.71 | 0.00 | 0.00 |
Annual Sum or Average | 1490.42 | 842.76 | 901.83 | 525.84 | 375.99 | 0.00 | 0.00 |
Minimum of Months | 438.62 | 255.26 | 452.62 | 246.91 | 205.71 | 0.00 | 0.00 |
Maximum of Months | 2584.40 | 1587.33 | 1347.15 | 787.96 | 559.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 914.38 | 1206.09 | 851.70 | 593.59 | 258.11 | 0.00 | 0.00 |
February | 921.74 | 1047.21 | 795.52 | 533.24 | 262.28 | 0.00 | 0.00 |
March | 848.02 | 742.51 | 716.39 | 373.77 | 342.62 | 0.00 | 0.00 |
April | 665.85 | 595.55 | 537.33 | 175.91 | 361.42 | 0.00 | 0.00 |
May | 583.29 | 380.83 | 433.84 | 51.21 | 382.63 | 0.00 | 0.00 |
June | 710.88 | 225.49 | 400.81 | 22.78 | 378.03 | 0.00 | 0.00 |
July | 769.37 | 148.21 | 405.30 | 30.78 | 374.53 | 0.00 | 0.00 |
August | 914.33 | 120.67 | 484.30 | 91.38 | 392.92 | 0.00 | 0.00 |
September | 833.21 | 316.14 | 532.42 | 198.68 | 333.74 | 0.00 | 0.00 |
October | 1074.15 | 696.00 | 770.73 | 499.41 | 271.32 | 0.00 | 0.00 |
November | 1053.39 | 899.81 | 828.33 | 549.52 | 278.81 | 0.00 | 0.00 |
December | 973.94 | 1064.21 | 839.39 | 590.27 | 249.12 | 0.00 | 0.00 |
Annual Sum or Average | 855.10 | 617.93 | 632.31 | 308.16 | 324.14 | 0.00 | 0.00 |
Minimum of Months | 583.29 | 120.67 | 400.81 | 22.78 | 249.12 | 0.00 | 0.00 |
Maximum of Months | 1074.15 | 1206.09 | 851.70 | 593.59 | 392.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 929.56 | 1164.86 | 851.70 | 593.59 | 258.11 | 0.00 | 0.00 |
February | 932.67 | 1006.93 | 795.52 | 533.24 | 262.28 | 0.00 | 0.00 |
March | 859.14 | 707.25 | 716.39 | 373.77 | 342.62 | 0.00 | 0.00 |
April | 672.26 | 569.47 | 537.33 | 175.91 | 361.42 | 0.00 | 0.00 |
May | 584.73 | 368.60 | 433.84 | 51.21 | 382.63 | 0.00 | 0.00 |
June | 708.82 | 222.00 | 400.81 | 22.78 | 378.03 | 0.00 | 0.00 |
July | 767.69 | 144.60 | 405.30 | 30.78 | 374.53 | 0.00 | 0.00 |
August | 912.41 | 116.55 | 484.30 | 91.38 | 392.92 | 0.00 | 0.00 |
September | 832.10 | 310.71 | 532.42 | 198.68 | 333.74 | 0.00 | 0.00 |
October | 1077.40 | 674.47 | 770.73 | 499.41 | 271.32 | 0.00 | 0.00 |
November | 1063.35 | 863.39 | 828.33 | 549.52 | 278.81 | 0.00 | 0.00 |
December | 988.54 | 1012.96 | 839.39 | 590.27 | 249.12 | 0.00 | 0.00 |
Annual Sum or Average | 860.59 | 594.60 | 632.31 | 308.16 | 324.14 | 0.00 | 0.00 |
Minimum of Months | 584.73 | 116.55 | 400.81 | 22.78 | 249.12 | 0.00 | 0.00 |
Maximum of Months | 1077.40 | 1164.86 | 851.70 | 593.59 | 392.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 185.89 | 236.92 | 175.25 | 122.14 | 53.11 | 0.00 | 0.00 |
February | 187.99 | 203.30 | 163.69 | 109.72 | 53.97 | 0.00 | 0.00 |
March | 176.79 | 138.61 | 147.41 | 76.91 | 70.50 | 0.00 | 0.00 |
April | 136.24 | 112.45 | 110.56 | 36.20 | 74.37 | 0.00 | 0.00 |
May | 113.62 | 74.27 | 89.27 | 10.54 | 78.73 | 0.00 | 0.00 |
June | 121.19 | 52.34 | 82.47 | 4.69 | 77.79 | 0.00 | 0.00 |
July | 127.75 | 38.63 | 83.40 | 6.33 | 77.06 | 0.00 | 0.00 |
August | 155.46 | 35.88 | 99.65 | 18.80 | 80.85 | 0.00 | 0.00 |
September | 157.67 | 68.79 | 109.55 | 40.88 | 68.67 | 0.00 | 0.00 |
October | 219.02 | 133.81 | 158.59 | 102.76 | 55.83 | 0.00 | 0.00 |
November | 218.46 | 168.42 | 170.44 | 113.07 | 57.37 | 0.00 | 0.00 |
December | 199.86 | 202.91 | 172.72 | 121.46 | 51.26 | 0.00 | 0.00 |
Annual Sum or Average | 166.58 | 121.76 | 130.11 | 63.41 | 66.70 | 0.00 | 0.00 |
Minimum of Months | 113.62 | 35.88 | 82.47 | 4.69 | 51.26 | 0.00 | 0.00 |
Maximum of Months | 219.02 | 236.92 | 175.25 | 122.14 | 80.85 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.120168E+10 | 0.425150E+10 | 0.134079E+10 | 0.741645E+09 | 0.599150E+09 | 0.00 | 0.00 |
February | 0.179797E+10 | 0.332234E+10 | 0.151293E+10 | 0.937283E+09 | 0.575649E+09 | 0.00 | 0.00 |
March | 0.353337E+10 | 0.260669E+10 | 0.242935E+10 | 0.148342E+10 | 0.945931E+09 | 0.00 | 0.00 |
April | 0.491757E+10 | 0.204372E+10 | 0.295593E+10 | 0.182129E+10 | 0.113464E+10 | 0.00 | 0.00 |
May | 0.603511E+10 | 0.141476E+10 | 0.338208E+10 | 0.193946E+10 | 0.144262E+10 | 0.00 | 0.00 |
June | 0.669876E+10 | 0.969708E+09 | 0.349182E+10 | 0.204239E+10 | 0.144943E+10 | 0.00 | 0.00 |
July | 0.663381E+10 | 0.730801E+09 | 0.336020E+10 | 0.188579E+10 | 0.147441E+10 | 0.00 | 0.00 |
August | 0.616579E+10 | 0.683701E+09 | 0.309322E+10 | 0.167788E+10 | 0.141533E+10 | 0.00 | 0.00 |
September | 0.399815E+10 | 0.126559E+10 | 0.224147E+10 | 0.124513E+10 | 0.996335E+09 | 0.00 | 0.00 |
October | 0.305202E+10 | 0.244756E+10 | 0.198719E+10 | 0.133546E+10 | 0.651732E+09 | 0.00 | 0.00 |
November | 0.179293E+10 | 0.309282E+10 | 0.143290E+10 | 0.811759E+09 | 0.621144E+09 | 0.00 | 0.00 |
December | 0.117481E+10 | 0.374805E+10 | 0.121231E+10 | 0.661330E+09 | 0.550977E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.470020E+11 | 0.265772E+11 | 0.284402E+11 | 0.165828E+11 | 0.118573E+11 | 0.00 | 0.00 |
Minimum of Months | 0.117481E+10 | 0.683701E+09 | 0.121231E+10 | 0.661330E+09 | 0.550977E+09 | 0.00 | 0.00 |
Maximum of Months | 0.669876E+10 | 0.425150E+10 | 0.349182E+10 | 0.204239E+10 | 0.147441E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244908E+10 | 0.323040E+10 | 0.228118E+10 | 0.158986E+10 | 0.691321E+09 | 0.00 | 0.00 |
February | 0.222988E+10 | 0.253342E+10 | 0.192451E+10 | 0.129000E+10 | 0.634506E+09 | 0.00 | 0.00 |
March | 0.227135E+10 | 0.198873E+10 | 0.191877E+10 | 0.100110E+10 | 0.917671E+09 | 0.00 | 0.00 |
April | 0.172588E+10 | 0.154366E+10 | 0.139276E+10 | 0.455954E+09 | 0.936807E+09 | 0.00 | 0.00 |
May | 0.156229E+10 | 0.102003E+10 | 0.116199E+10 | 0.137163E+09 | 0.102483E+10 | 0.00 | 0.00 |
June | 0.184259E+10 | 0.584467E+09 | 0.103889E+10 | 59033491.93 | 0.979857E+09 | 0.00 | 0.00 |
July | 0.206067E+10 | 0.396956E+09 | 0.108556E+10 | 82430668.75 | 0.100313E+10 | 0.00 | 0.00 |
August | 0.244895E+10 | 0.323214E+09 | 0.129716E+10 | 0.244748E+09 | 0.105241E+10 | 0.00 | 0.00 |
September | 0.215968E+10 | 0.819437E+09 | 0.138003E+10 | 0.514978E+09 | 0.865048E+09 | 0.00 | 0.00 |
October | 0.287701E+10 | 0.186416E+10 | 0.206433E+10 | 0.133762E+10 | 0.726701E+09 | 0.00 | 0.00 |
November | 0.273039E+10 | 0.233230E+10 | 0.214703E+10 | 0.142435E+10 | 0.722677E+09 | 0.00 | 0.00 |
December | 0.260861E+10 | 0.285038E+10 | 0.224823E+10 | 0.158098E+10 | 0.667249E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.269664E+11 | 0.194871E+11 | 0.199404E+11 | 0.971822E+10 | 0.102222E+11 | 0.00 | 0.00 |
Minimum of Months | 0.156229E+10 | 0.323214E+09 | 0.103889E+10 | 59033491.93 | 0.634506E+09 | 0.00 | 0.00 |
Maximum of Months | 0.287701E+10 | 0.323040E+10 | 0.228118E+10 | 0.158986E+10 | 0.105241E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.248972E+10 | 0.311995E+10 | 0.228118E+10 | 0.158986E+10 | 0.691321E+09 | 0.00 | 0.00 |
February | 0.225632E+10 | 0.243595E+10 | 0.192451E+10 | 0.129000E+10 | 0.634506E+09 | 0.00 | 0.00 |
March | 0.230113E+10 | 0.189430E+10 | 0.191877E+10 | 0.100110E+10 | 0.917671E+09 | 0.00 | 0.00 |
April | 0.174249E+10 | 0.147607E+10 | 0.139276E+10 | 0.455954E+09 | 0.936807E+09 | 0.00 | 0.00 |
May | 0.156615E+10 | 0.987271E+09 | 0.116199E+10 | 0.137163E+09 | 0.102483E+10 | 0.00 | 0.00 |
June | 0.183725E+10 | 0.575426E+09 | 0.103889E+10 | 59033491.93 | 0.979857E+09 | 0.00 | 0.00 |
July | 0.205617E+10 | 0.387298E+09 | 0.108556E+10 | 82430668.75 | 0.100313E+10 | 0.00 | 0.00 |
August | 0.244381E+10 | 0.312173E+09 | 0.129716E+10 | 0.244748E+09 | 0.105241E+10 | 0.00 | 0.00 |
September | 0.215680E+10 | 0.805353E+09 | 0.138003E+10 | 0.514978E+09 | 0.865048E+09 | 0.00 | 0.00 |
October | 0.288571E+10 | 0.180650E+10 | 0.206433E+10 | 0.133762E+10 | 0.726701E+09 | 0.00 | 0.00 |
November | 0.275620E+10 | 0.223789E+10 | 0.214703E+10 | 0.142435E+10 | 0.722677E+09 | 0.00 | 0.00 |
December | 0.264770E+10 | 0.271312E+10 | 0.224823E+10 | 0.158098E+10 | 0.667249E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.271395E+11 | 0.187513E+11 | 0.199404E+11 | 0.971822E+10 | 0.102222E+11 | 0.00 | 0.00 |
Minimum of Months | 0.156615E+10 | 0.312173E+09 | 0.103889E+10 | 59033491.93 | 0.634506E+09 | 0.00 | 0.00 |
Maximum of Months | 0.288571E+10 | 0.311995E+10 | 0.228118E+10 | 0.158986E+10 | 0.105241E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.497878E+09 | 0.634561E+09 | 0.469386E+09 | 0.327137E+09 | 0.142249E+09 | 0.00 | 0.00 |
February | 0.454783E+09 | 0.491818E+09 | 0.395996E+09 | 0.265437E+09 | 0.130559E+09 | 0.00 | 0.00 |
March | 0.473501E+09 | 0.371247E+09 | 0.394814E+09 | 0.205990E+09 | 0.188824E+09 | 0.00 | 0.00 |
April | 0.353125E+09 | 0.291470E+09 | 0.286581E+09 | 93819260.29 | 0.192762E+09 | 0.00 | 0.00 |
May | 0.304328E+09 | 0.198916E+09 | 0.239097E+09 | 28223201.27 | 0.210874E+09 | 0.00 | 0.00 |
June | 0.314118E+09 | 0.135661E+09 | 0.213767E+09 | 12147000.56 | 0.201620E+09 | 0.00 | 0.00 |
July | 0.342173E+09 | 0.103464E+09 | 0.223370E+09 | 16961310.38 | 0.206408E+09 | 0.00 | 0.00 |
August | 0.416379E+09 | 96092654.08 | 0.266909E+09 | 50360534.73 | 0.216549E+09 | 0.00 | 0.00 |
September | 0.408681E+09 | 0.178300E+09 | 0.283960E+09 | 0.105964E+09 | 0.177996E+09 | 0.00 | 0.00 |
October | 0.586616E+09 | 0.358409E+09 | 0.424765E+09 | 0.275236E+09 | 0.149529E+09 | 0.00 | 0.00 |
November | 0.566257E+09 | 0.436541E+09 | 0.441782E+09 | 0.293080E+09 | 0.148701E+09 | 0.00 | 0.00 |
December | 0.535303E+09 | 0.543470E+09 | 0.462606E+09 | 0.325310E+09 | 0.137296E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.525314E+10 | 0.383995E+10 | 0.410303E+10 | 0.199967E+10 | 0.210337E+10 | 0.00 | 0.00 |
Minimum of Months | 0.304328E+09 | 96092654.08 | 0.213767E+09 | 12147000.56 | 0.130559E+09 | 0.00 | 0.00 |
Maximum of Months | 0.586616E+09 | 0.634561E+09 | 0.469386E+09 | 0.327137E+09 | 0.216549E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.45 | -3.0 | 4.56 | -7.9 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.23 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.96 | 3.80 | 4.89 | 2.24 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.53 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.43 | 13.69 | 3.50 | 11.45 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.34 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.67 | 19.85 | 3.24 | 17.63 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.41 | 20.72 | 3.39 | 18.20 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.43 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.01 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.21 | 4.17 | 4.16 | 0.29 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.67 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.28 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.45 | -3.0 | 3.06 | -7.9 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.41 | 20.72 | 5.19 | 18.20 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.95 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.72 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.85 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.53 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.47 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.37 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.89 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.82 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.04 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.54 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.94 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.76 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.72 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.89 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.7 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.7 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.4 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.0 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.44 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.1 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.7 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.80 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.15 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.00 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.33 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.31 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.05 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.12 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.09 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.19 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.87 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.80 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.12 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.80 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.78 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.09 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.88 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.80 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.257125E+10 | -.214399E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -427256695.0 | 58.99 | 0.00 | 0.00 |
February | 0.233408E+10 | -.195631E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -377771569.0 | 58.99 | 0.00 | 0.00 |
March | 0.254752E+10 | -.214513E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -402386793.4 | 58.99 | 0.00 | 0.00 |
April | 0.228918E+10 | -.190920E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -379980657.0 | 58.99 | 0.00 | 0.00 |
May | 0.220289E+10 | -.181627E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -386619793.0 | 58.99 | 0.00 | 0.00 |
June | 0.201400E+10 | -.164084E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373166041.1 | 58.99 | 0.00 | 0.00 |
July | 0.194651E+10 | -.156099E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385517418.9 | 58.99 | 0.00 | 0.00 |
August | 0.199089E+10 | -.160534E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385554422.2 | 58.99 | 0.00 | 0.00 |
September | 0.197390E+10 | -.160075E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373144336.2 | 58.99 | 0.00 | 0.00 |
October | 0.215555E+10 | -.176384E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -391708563.6 | 59.00 | 0.00 | 0.00 |
November | 0.224145E+10 | -.185072E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -390730715.1 | 58.99 | 0.00 | 0.00 |
December | 0.248140E+10 | -.206167E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -419728220.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.267486E+11 | -.220550E+11 | 8760.00 | -.469357E+10 | 58.99 | |||||
Minimum of Months | 0.194651E+10 | -.214513E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -427256695.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.257125E+10 | -.156099E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -373144336.2 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.93 | 0.67 | 08-JAN-11:20 | 177.14 | 4.65 | 0.00 | 0.00 | 146.55 | 3.39 | 0.00 | 0.00 |
February | 263.00 | 0.92 | 0.58 | 22-FEB-11:30 | 191.18 | 4.62 | 0.00 | 1.00 | 156.36 | 3.29 | 0.00 | 0.00 |
March | 351.67 | 0.86 | 0.50 | 17-MAR-12:30 | 256.46 | 6.47 | 0.00 | 6.83 | 212.19 | 4.95 | 0.00 | 3.67 |
April | 369.33 | 0.81 | 0.50 | 01-APR-11:30 | 1746.88 | 7.71 | 0.00 | 75.67 | 1824.11 | 6.09 | 0.00 | 58.33 |
May | 407.00 | 0.81 | 0.50 | 01-MAY-11:09 | 317.54 | 9.53 | 0.00 | 51.67 | 266.95 | 7.81 | 0.00 | 32.67 |
June | 411.67 | 0.81 | 0.50 | 01-JUN-10:00 | 315.57 | 10.00 | 0.00 | 49.33 | 264.62 | 8.27 | 0.00 | 32.67 |
July | 411.00 | 0.80 | 0.50 | 01-JUL-11:00 | 323.45 | 9.92 | 0.00 | 57.00 | 271.42 | 8.26 | 0.00 | 34.17 |
August | 390.50 | 0.78 | 0.50 | 05-AUG-11:39 | 421.40 | 9.51 | 0.00 | 77.83 | 314.05 | 7.79 | 0.00 | 43.50 |
September | 298.50 | 0.79 | 0.50 | 01-SEP-11:09 | 2104.77 | 7.39 | 0.00 | 92.83 | 1471.84 | 5.78 | 0.00 | 46.17 |
October | 293.50 | 0.91 | 0.50 | 02-OCT-11:39 | 204.61 | 4.59 | 0.00 | 4.83 | 179.71 | 3.34 | 0.00 | 3.33 |
November | 299.00 | 0.89 | 0.67 | 01-NOV-09:39 | 208.96 | 4.99 | 0.00 | 2.17 | 420.72 | 3.61 | 0.00 | 28.83 |
December | 285.17 | 0.91 | 0.67 | 01-DEC-13:09 | 901.34 | 4.53 | 0.00 | 38.00 | 137.37 | 3.21 | 0.00 | 0.00 |
Annual Sum or Average | 4071.00 | 0.84 | 589.93 | 7.32 | 0.00 | 457.17 | 476.76 | 5.79 | 0.00 | 283.33 | ||
Minimum of Months | 263.00 | 0.78 | 0.50 | 177.14 | 4.53 | 0.00 | 0.00 | 137.37 | 3.21 | 0.00 | 0.00 | |
Maximum of Months | 411.67 | 0.93 | 0.67 | 2104.77 | 10.00 | 0.00 | 92.83 | 1824.11 | 8.27 | 0.00 | 58.33 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105112E+11 | 51326.47 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.591783E+10 | 51326.47 | 01-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.735532E+09 | 51326.47 | 18-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119290E+09 | 28559.18 | 07-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37900234.33 | 14832.06 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.914299E+09 | 51326.47 | 21-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.466964E+10 | 51326.47 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229057E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105112E+11 | 51326.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.316122E+11 | 238806.69 | 08-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164919E+11 | 238806.69 | 05-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122751E+10 | 38496.90 | 19-MAR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215156E+09 | 25825.65 | 07-APR-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124776E+09 | 30694.29 | 26-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.248188E+10 | 92146.00 | 22-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127973E+11 | 212116.02 | 04-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.649508E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.316122E+11 | 238806.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.246084E+10 | 31594.26 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136802E+10 | 31594.26 | 02-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 98483036.27 | 31594.26 | 23-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32933623.75 | 6434.36 | 06-APR-06:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 431985.12 | 1439.95 | 04-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4131544.75 | 1999.05 | 26-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110636E+09 | 31594.26 | 21-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.786183E+09 | 31594.26 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.486166E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246084E+10 | 31594.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.444544E+10 | 25871.04 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262038E+10 | 25871.04 | 01-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.413339E+09 | 25871.04 | 18-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118719E+09 | 22717.76 | 06-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 60352583.13 | 8847.93 | 31-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348444E+09 | 25871.04 | 21-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183749E+10 | 25871.04 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.984417E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.444544E+10 | 25871.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102089E+11 | 30101.55 | 07-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.593092E+10 | 30074.98 | 11-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211649E+10 | 17477.07 | 22-MAR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.576597E+09 | 12280.18 | 05-APR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12212798.92 | 1698.25 | 10-MAY-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30401759.72 | 1807.37 | 28-SEP-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.915025E+09 | 11110.92 | 25-OCT-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.221865E+10 | 17685.79 | 20-NOV-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.595268E+10 | 21795.90 | 17-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279619E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102089E+11 | 30101.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 216.83 | 149.71 | 0.26 | 20-JAN-15:50 | 0.18 | 0.00 |
February | 0.00 | 0.00 | 0.165178E+09 | 0.165178E+09 | 6074.85 | 28-FEB-15:10 | 6074.85 | 0.00 |
March | 0.00 | 0.00 | 0.134921E+10 | 0.106049E+10 | 38158.86 | 30-MAR-22:40 | 29366.39 | 0.00 |
April | 0.00 | 0.00 | 0.474672E+10 | 0.392577E+10 | 29873.72 | 17-APR-20:51 | 24252.62 | 0.00 |
May | 0.00 | 0.00 | 0.120570E+11 | 0.908305E+10 | 39589.79 | 26-MAY-20:30 | 19358.35 | 0.00 |
June | 0.00 | 0.00 | 0.226078E+11 | 0.169844E+11 | 38290.13 | 07-JUN-01:52 | 22870.85 | 0.00 |
July | 0.00 | 0.00 | 0.272437E+11 | 0.195838E+11 | 38113.94 | 21-JUL-20:10 | 30305.81 | 0.00 |
August | 0.00 | 0.00 | 0.294402E+11 | 0.207859E+11 | 39104.45 | 04-AUG-20:10 | 29130.00 | 0.00 |
September | 0.00 | 0.00 | 0.170569E+11 | 0.122625E+11 | 39097.05 | 17-SEP-20:01 | 25659.47 | 0.00 |
October | 0.00 | 0.00 | 0.502158E+10 | 0.358534E+10 | 38478.61 | 19-OCT-21:20 | 21219.83 | 0.00 |
November | 0.00 | 0.00 | 0.564065E+09 | 0.396514E+09 | 8394.80 | 05-NOV-15:00 | 5741.22 | 0.00 |
December | 0.00 | 0.00 | 38179279.66 | 27078705.14 | 3171.70 | 12-DEC-15:10 | 2398.70 | 0.00 |
Annual Sum or Average | 0.120290E+12 | 0.878601E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 216.83 | 149.71 | 0.26 | 0.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.294402E+11 | 0.207859E+11 | 39589.79 | 30305.81 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 45260486.87 | 37394061.16 | 7760.19 | 31-JAN-15:10 | 6574.27 | 0.00 |
February | 0.00 | 0.00 | 0.229230E+10 | 0.226592E+10 | 159298.32 | 28-FEB-21:41 | 149966.82 | 0.00 |
March | 0.00 | 0.00 | 0.123244E+11 | 0.949349E+10 | 190372.45 | 29-MAR-23:51 | 133653.29 | 0.00 |
April | 0.00 | 0.00 | 0.346518E+11 | 0.273962E+11 | 195965.04 | 30-APR-20:05 | 95002.85 | 0.00 |
May | 0.00 | 0.00 | 0.721847E+11 | 0.521092E+11 | 197750.55 | 25-MAY-20:20 | 101521.44 | 0.00 |
June | 0.00 | 0.00 | 0.112752E+12 | 0.795723E+11 | 188500.76 | 03-JUN-22:41 | 146078.71 | 0.00 |
July | 0.00 | 0.00 | 0.131953E+12 | 0.868209E+11 | 198542.38 | 28-JUL-20:20 | 91473.90 | 0.00 |
August | 0.00 | 0.00 | 0.141430E+12 | 0.909051E+11 | 196113.98 | 04-AUG-20:10 | 133531.37 | 0.00 |
September | 0.00 | 0.00 | 0.861541E+11 | 0.569711E+11 | 198645.50 | 21-SEP-20:20 | 97359.58 | 0.00 |
October | 0.00 | 0.00 | 0.319847E+11 | 0.221775E+11 | 192156.84 | 15-OCT-18:31 | 132370.19 | 0.00 |
November | 0.00 | 0.00 | 0.662618E+10 | 0.477300E+10 | 193047.17 | 04-NOV-21:45 | 100892.89 | 0.00 |
December | 0.00 | 0.00 | 0.886726E+09 | 0.570311E+09 | 30386.78 | 12-DEC-15:10 | 21942.99 | 0.00 |
Annual Sum or Average | 0.633285E+12 | 0.433092E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 45260486.87 | 37394061.16 | 7760.19 | 6574.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.141430E+12 | 0.909051E+11 | 198645.50 | 149966.82 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 28144341.11 | 25017649.06 | 2649.05 | 31-JAN-15:00 | 2509.38 | 0.00 |
February | 0.00 | 0.00 | 0.737007E+09 | 0.735901E+09 | 22500.62 | 26-FEB-19:20 | 22500.62 | 0.00 |
March | 0.00 | 0.00 | 0.231423E+10 | 0.195418E+10 | 24479.45 | 28-MAR-22:01 | 16686.20 | 0.00 |
April | 0.00 | 0.00 | 0.548766E+10 | 0.472886E+10 | 24887.45 | 30-APR-18:32 | 13922.49 | 0.00 |
May | 0.00 | 0.00 | 0.103595E+11 | 0.827387E+10 | 25078.80 | 24-MAY-20:20 | 13283.75 | 0.00 |
June | 0.00 | 0.00 | 0.168362E+11 | 0.132063E+11 | 24460.24 | 07-JUN-01:30 | 14384.45 | 0.00 |
July | 0.00 | 0.00 | 0.200619E+11 | 0.150359E+11 | 23823.57 | 21-JUL-20:08 | 18589.08 | 0.00 |
August | 0.00 | 0.00 | 0.224214E+11 | 0.166768E+11 | 24642.00 | 04-AUG-20:08 | 18163.67 | 0.00 |
September | 0.00 | 0.00 | 0.147177E+11 | 0.113558E+11 | 24757.84 | 29-SEP-20:20 | 14471.21 | 0.00 |
October | 0.00 | 0.00 | 0.629050E+10 | 0.505215E+10 | 24627.51 | 02-OCT-21:21 | 14598.37 | 0.00 |
November | 0.00 | 0.00 | 0.191157E+10 | 0.157416E+10 | 24533.82 | 03-NOV-20:22 | 14270.70 | 0.00 |
December | 0.00 | 0.00 | 0.355728E+09 | 0.257219E+09 | 23881.32 | 12-DEC-22:45 | 16207.90 | 0.00 |
Annual Sum or Average | 0.101522E+12 | 0.788761E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 28144341.11 | 25017649.06 | 2649.05 | 2509.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.224214E+11 | 0.166768E+11 | 25078.80 | 22500.62 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3277923.46 | 2943613.86 | 732.33 | 31-JAN-15:00 | 674.47 | 0.00 |
February | 0.00 | 0.00 | 0.437445E+09 | 0.437298E+09 | 18529.42 | 26-FEB-19:31 | 18529.42 | 0.00 |
March | 0.00 | 0.00 | 0.136208E+10 | 0.111947E+10 | 19801.61 | 30-MAR-23:01 | 14792.27 | 0.00 |
April | 0.00 | 0.00 | 0.344832E+10 | 0.291401E+10 | 20495.69 | 21-APR-20:45 | 11485.80 | 0.00 |
May | 0.00 | 0.00 | 0.703085E+10 | 0.539627E+10 | 20859.11 | 25-MAY-20:32 | 10177.61 | 0.00 |
June | 0.00 | 0.00 | 0.129777E+11 | 0.967225E+10 | 20048.10 | 07-JUN-01:50 | 11696.99 | 0.00 |
July | 0.00 | 0.00 | 0.158631E+11 | 0.112650E+11 | 20857.66 | 28-JUL-20:32 | 9556.98 | 0.00 |
August | 0.00 | 0.00 | 0.180852E+11 | 0.127201E+11 | 20423.28 | 04-AUG-20:08 | 14167.46 | 0.00 |
September | 0.00 | 0.00 | 0.111701E+11 | 0.817587E+10 | 20740.42 | 21-SEP-20:20 | 10609.97 | 0.00 |
October | 0.00 | 0.00 | 0.454900E+10 | 0.349284E+10 | 20313.72 | 02-OCT-21:21 | 11725.95 | 0.00 |
November | 0.00 | 0.00 | 0.103340E+10 | 0.843510E+09 | 20233.07 | 03-NOV-20:30 | 11645.72 | 0.00 |
December | 0.00 | 0.00 | 0.171951E+09 | 0.122844E+09 | 19645.69 | 12-DEC-21:45 | 13209.36 | 0.00 |
Annual Sum or Average | 0.761324E+11 | 0.561624E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 3277923.46 | 2943613.86 | 732.33 | 674.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.180852E+11 | 0.127201E+11 | 20859.11 | 18529.42 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.304593E+10 | 0.53 | 1948.72 | 01-JAN-07:01 | 0.91 |
February | 0.233874E+10 | 0.45 | 1948.72 | 01-FEB-05:02 | 0.91 |
March | 0.189547E+10 | 0.33 | 1948.72 | 01-MAR-08:70 | 0.91 |
April | 0.889538E+09 | 0.16 | 1948.72 | 01-APR-07:10 | 0.91 |
May | 0.228536E+09 | 0.04 | 1948.72 | 01-MAY-07:05 | 0.90 |
June | 15109083.26 | 0.00 | 1948.72 | 07-JUN-07:06 | 0.90 |
July | 62553943.16 | 0.01 | 1948.72 | 28-JUL-11:10 | 0.89 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.157345E+09 | 0.03 | 1948.72 | 14-SEP-07:10 | 0.90 |
October | 0.113775E+10 | 0.20 | 1948.72 | 01-OCT-07:08 | 0.90 |
November | 0.188880E+10 | 0.34 | 1948.72 | 01-NOV-04:03 | 0.91 |
December | 0.275460E+10 | 0.48 | 1948.72 | 01-DEC-05:01 | 0.91 |
Annual Sum or Average | 0.144144E+11 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.304593E+10 | 0.53 | 1948.72 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165286E+10 | 0.39 | 2130.61 | 01-JAN-07:01 | 0.91 |
February | 0.140230E+10 | 0.37 | 2130.61 | 01-FEB-05:02 | 0.91 |
March | 0.141187E+10 | 0.34 | 2130.61 | 18-MAR-04:02 | 0.91 |
April | 0.133914E+10 | 0.33 | 1626.84 | 17-APR-20:51 | 0.80 |
May | 0.141045E+10 | 0.35 | 2130.61 | 04-MAY-20:28 | 0.90 |
June | 0.150444E+10 | 0.43 | 2130.61 | 02-JUN-21:51 | 0.90 |
July | 0.161733E+10 | 0.46 | 2130.61 | 07-JUL-20:08 | 0.90 |
August | 0.167156E+10 | 0.48 | 2130.61 | 01-AUG-20:10 | 0.90 |
September | 0.144286E+10 | 0.40 | 2130.61 | 07-SEP-20:10 | 0.90 |
October | 0.137884E+10 | 0.34 | 1831.89 | 16-OCT-20:52 | 0.84 |
November | 0.134240E+10 | 0.34 | 2130.61 | 21-NOV-05:01 | 0.91 |
December | 0.150032E+10 | 0.37 | 2130.61 | 01-DEC-05:01 | 0.91 |
Annual Sum or Average | 0.176744E+11 | 0.38 | |||
Minimum of Months | 0.133914E+10 | 0.33 | 1626.84 | 0.80 | |
Maximum of Months | 0.167156E+10 | 0.48 | 2130.61 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.988212E+10 | 0.56 | 13720.87 | 08-JAN-08:62 | 1.44 |
February | 0.855160E+10 | 0.54 | 13720.87 | 05-FEB-08:62 | 1.44 |
March | 0.903883E+10 | 0.53 | 13720.87 | 13-MAR-20:23 | 1.42 |
April | 0.879132E+10 | 0.54 | 13720.87 | 11-APR-20:18 | 1.43 |
May | 0.934349E+10 | 0.58 | 13720.87 | 04-MAY-20:16 | 1.42 |
June | 0.952840E+10 | 0.66 | 13720.87 | 02-JUN-23:10 | 1.42 |
July | 0.100372E+11 | 0.68 | 13720.87 | 07-JUL-20:10 | 1.42 |
August | 0.102644E+11 | 0.71 | 13720.87 | 01-AUG-20:10 | 1.42 |
September | 0.926853E+10 | 0.62 | 13720.87 | 14-SEP-20:55 | 1.42 |
October | 0.898162E+10 | 0.54 | 13720.87 | 15-OCT-18:31 | 1.42 |
November | 0.858138E+10 | 0.52 | 9854.63 | 03-NOV-20:22 | 1.21 |
December | 0.925465E+10 | 0.54 | 12800.75 | 04-DEC-07:03 | 1.40 |
Annual Sum or Average | 0.111524E+12 | 0.58 | |||
Minimum of Months | 0.855160E+10 | 0.52 | 9854.63 | 1.21 | |
Maximum of Months | 0.102644E+11 | 0.71 | 13720.87 | 1.44 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.209055E+10 | 0.59 | 1292.79 | 04-JAN-20:15 | 0.94 |
February | 0.189863E+10 | 0.59 | 1292.79 | 09-FEB-06:20 | 0.95 |
March | 0.212710E+10 | 0.59 | 1292.79 | 31-MAR-18:47 | 0.94 |
April | 0.205964E+10 | 0.59 | 1292.79 | 01-APR-10:10 | 0.94 |
May | 0.220145E+10 | 0.66 | 1292.79 | 01-MAY-09:05 | 0.93 |
June | 0.229736E+10 | 0.78 | 1292.79 | 28-JUN-14:20 | 0.93 |
July | 0.243137E+10 | 0.82 | 1292.79 | 01-JUL-05:40 | 0.93 |
August | 0.252399E+10 | 0.85 | 1292.79 | 01-AUG-06:20 | 0.93 |
September | 0.228732E+10 | 0.77 | 1292.79 | 01-SEP-06:20 | 0.93 |
October | 0.218000E+10 | 0.64 | 1292.79 | 01-OCT-11:27 | 0.93 |
November | 0.201516E+10 | 0.58 | 1292.79 | 01-NOV-11:40 | 0.94 |
December | 0.208827E+10 | 0.58 | 1292.79 | 01-DEC-06:05 | 0.94 |
Annual Sum or Average | 0.262008E+11 | 0.67 | |||
Minimum of Months | 0.189863E+10 | 0.58 | 1292.79 | 0.93 | |
Maximum of Months | 0.252399E+10 | 0.85 | 1292.79 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164140E+10 | 0.59 | 1009.42 | 01-JAN-14:10 | 0.93 |
February | 0.148424E+10 | 0.59 | 1009.42 | 06-FEB-16:00 | 0.94 |
March | 0.165410E+10 | 0.58 | 1009.42 | 26-MAR-12:00 | 0.94 |
April | 0.158910E+10 | 0.57 | 1009.42 | 01-APR-17:20 | 0.94 |
May | 0.167025E+10 | 0.60 | 1009.42 | 24-MAY-12:30 | 0.93 |
June | 0.175247E+10 | 0.73 | 1009.42 | 05-JUN-16:20 | 0.93 |
July | 0.185570E+10 | 0.79 | 1009.42 | 05-JUL-05:50 | 0.93 |
August | 0.194108E+10 | 0.83 | 1009.42 | 01-AUG-11:00 | 0.93 |
September | 0.173914E+10 | 0.72 | 1009.42 | 01-SEP-07:40 | 0.93 |
October | 0.166726E+10 | 0.61 | 1009.42 | 01-OCT-13:10 | 0.93 |
November | 0.156397E+10 | 0.57 | 1009.42 | 03-NOV-19:50 | 0.93 |
December | 0.163450E+10 | 0.59 | 1009.42 | 01-DEC-09:10 | 0.94 |
Annual Sum or Average | 0.201932E+11 | 0.65 | |||
Minimum of Months | 0.148424E+10 | 0.57 | 1009.42 | 0.93 | |
Maximum of Months | 0.194108E+10 | 0.83 | 1009.42 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.26 | 0.00 |
February | 0.74 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.17 | 0.00 |
June | 0.14 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.11 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.17 | 0.00 |
Annual Sum or Average | 2.59 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.26 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.31 | 25.84 |
March | 1.42 | 22.80 |
April | 1.35 | 13.32 |
May | 2.31 | 1.56 |
June | 0.41 | 0.00 |
July | 0.17 | 0.00 |
August | 0.00 | 0.00 |
September | 0.59 | 0.00 |
October | 1.26 | 18.46 |
November | 1.32 | 25.84 |
December | 0.12 | 25.84 |
Annual Sum or Average | 9.25 | 13.23 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.31 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.22 | 0.00 |
February | 0.35 | 0.00 |
March | 0.58 | 0.00 |
April | 2.13 | 0.16 |
May | 2.33 | 0.00 |
June | 2.13 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 2.11 | 0.00 |
October | 1.81 | 0.13 |
November | 0.83 | 0.85 |
December | 0.21 | 0.49 |
Annual Sum or Average | 12.70 | 0.11 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.33 | 0.85 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.64 | 0.00 |
February | 0.30 | 0.00 |
March | 0.08 | 0.00 |
April | 0.90 | 0.00 |
May | 0.58 | 0.00 |
June | 0.05 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 1.06 | 0.00 |
October | 1.61 | 0.50 |
November | 0.21 | 2.44 |
December | 0.21 | 0.00 |
Annual Sum or Average | 5.64 | 0.23 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.61 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 40.88 | 0.00 |
February | 37.55 | 0.00 |
March | 28.81 | 0.00 |
April | 30.49 | 0.00 |
May | 12.63 | 0.00 |
June | 4.86 | 0.00 |
July | 4.61 | 0.00 |
August | 1.89 | 0.00 |
September | 8.19 | 0.00 |
October | 21.06 | 0.00 |
November | 32.92 | 0.00 |
December | 37.18 | 0.00 |
Annual Sum or Average | 261.07 | 0.00 |
Minimum of Months | 1.89 | 0.00 |
Maximum of Months | 40.88 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.165286E+10 | 0.131390E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.144817E+10 | 0.739728E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.176921E+10 | 0.919415E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.259046E+10 | 0.149113E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.446561E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.717588E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.843978E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.896946E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.566805E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.263562E+10 | 47375292.91 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.149169E+10 | 0.114287E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.151087E+10 | 0.583706E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.478177E+11 | 0.286321E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.144817E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.896946E+10 | 0.131390E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.989622E+10 | 0.395153E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.924241E+10 | 0.206149E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.125850E+11 | 0.153439E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.186631E+11 | 0.268945E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.294519E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.408215E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.464198E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.488902E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.329282E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.178525E+11 | 0.155970E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.105038E+11 | 0.310235E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.951948E+10 | 0.159966E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.286774E+12 | 0.811884E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.924241E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.488902E+11 | 0.395153E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.209774E+10 | 0.307605E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.207420E+10 | 0.171002E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.267296E+10 | 0.123104E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.336002E+10 | 41167029.68 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.463821E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.630542E+10 | 539981.40 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.722858E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.783532E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.569482E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.361217E+10 | 5164430.93 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.246355E+10 | 0.138295E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.217144E+10 | 0.982728E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.501544E+11 | 0.607707E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.207420E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.783532E+10 | 0.307605E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.164226E+10 | 0.555680E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.159048E+10 | 0.327548E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.198213E+10 | 0.516673E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.242585E+10 | 0.148398E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.334520E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.484012E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.563475E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.620630E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.432945E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.270857E+10 | 75440728.92 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.181186E+10 | 0.435555E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.167563E+10 | 0.229687E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.381926E+11 | 0.123052E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.159048E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.620630E+10 | 0.555680E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.165286E+10 | 216.83 | 0.105112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140230E+10 | 0.165178E+09 | 0.591783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141187E+10 | 0.134454E+10 | 0.735532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133914E+10 | 0.474672E+10 | 0.119290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141045E+10 | 0.119944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150444E+10 | 0.225418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161733E+10 | 0.272437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167156E+10 | 0.294402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144286E+10 | 0.170067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137884E+10 | 0.501611E+10 | 37900234.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134240E+10 | 0.564065E+09 | 0.914299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150032E+10 | 38179279.66 | 0.466964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176744E+11 | 0.120102E+12 | 0.229057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133914E+10 | 216.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167156E+10 | 0.294402E+11 | 0.105112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.988212E+10 | 45260486.87 | 0.316122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.855160E+10 | 0.229230E+10 | 0.164919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.903883E+10 | 0.121922E+11 | 0.122751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.879132E+10 | 0.339868E+11 | 0.215156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.934349E+10 | 0.711959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.952840E+10 | 0.112339E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100372E+11 | 0.131892E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102644E+11 | 0.141430E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.926853E+10 | 0.856240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.898162E+10 | 0.317345E+11 | 0.124776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.858138E+10 | 0.656793E+10 | 0.248188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.925465E+10 | 0.886726E+09 | 0.127973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111524E+12 | 0.630187E+12 | 0.649508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.855160E+10 | 45260486.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.102644E+11 | 0.141430E+12 | 0.316122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.209055E+10 | 28144341.11 | 0.246084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189863E+10 | 0.737007E+09 | 0.136802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.212710E+10 | 0.231423E+10 | 98483036.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205964E+10 | 0.548766E+10 | 32933623.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220145E+10 | 0.103595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.229736E+10 | 0.168362E+11 | 431985.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.243137E+10 | 0.200619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.252399E+10 | 0.224214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.228732E+10 | 0.147177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218000E+10 | 0.629050E+10 | 4131544.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201516E+10 | 0.191157E+10 | 0.110636E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208827E+10 | 0.355728E+09 | 0.786183E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262008E+11 | 0.101522E+12 | 0.486166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.189863E+10 | 28144341.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.252399E+10 | 0.224214E+11 | 0.246084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.164140E+10 | 3277923.46 | 0.444544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148424E+10 | 0.437445E+09 | 0.262038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165410E+10 | 0.136208E+10 | 0.413339E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158910E+10 | 0.344832E+10 | 0.118719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167025E+10 | 0.703085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.175247E+10 | 0.129777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185570E+10 | 0.158631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.194108E+10 | 0.180852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173914E+10 | 0.111701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166726E+10 | 0.454900E+10 | 60352583.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156397E+10 | 0.103340E+10 | 0.348444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163450E+10 | 0.171951E+09 | 0.183749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201932E+11 | 0.761324E+11 | 0.984417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148424E+10 | 3277923.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.194108E+10 | 0.180852E+11 | 0.444544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.165286E+10 | 0.00 | 0.00 | 0.00 | 61.43 | 0.00 | 0.131390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140230E+10 | 0.00 | 0.00 | 0.00 | 45871976.57 | 0.00 | 0.739728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141187E+10 | 0.00 | 0.00 | 0.00 | 0.357339E+09 | 0.00 | 0.919415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133914E+10 | 0.00 | 0.00 | 0.00 | 0.125132E+10 | 0.00 | 0.149113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141045E+10 | 0.00 | 0.00 | 0.00 | 0.305516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150444E+10 | 0.00 | 0.00 | 0.00 | 0.567144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161733E+10 | 0.00 | 0.00 | 0.00 | 0.682245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167156E+10 | 0.00 | 0.00 | 0.00 | 0.729790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144286E+10 | 0.00 | 0.00 | 0.00 | 0.422519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137884E+10 | 0.00 | 0.00 | 0.00 | 0.125678E+10 | 0.00 | 47375292.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134240E+10 | 0.00 | 0.00 | 0.00 | 0.149294E+09 | 0.00 | 0.114287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150032E+10 | 0.00 | 0.00 | 0.00 | 10554508.44 | 0.00 | 0.583706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176744E+11 | 0.00 | 0.00 | 0.00 | 0.301433E+11 | 0.00 | 0.286321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.133914E+10 | 0.00 | 0.00 | 0.00 | 61.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167156E+10 | 0.00 | 0.00 | 0.00 | 0.729790E+10 | 0.00 | 0.131390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.988212E+10 | 0.00 | 0.00 | 0.00 | 14094270.20 | 0.00 | 0.395153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.855160E+10 | 0.00 | 0.00 | 0.00 | 0.690809E+09 | 0.00 | 0.206149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.903883E+10 | 0.00 | 0.00 | 0.00 | 0.354615E+10 | 0.00 | 0.153439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.879132E+10 | 0.00 | 0.00 | 0.00 | 0.987182E+10 | 0.00 | 0.268945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.934349E+10 | 0.00 | 0.00 | 0.00 | 0.201085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.952840E+10 | 0.00 | 0.00 | 0.00 | 0.312931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100372E+11 | 0.00 | 0.00 | 0.00 | 0.363826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102644E+11 | 0.00 | 0.00 | 0.00 | 0.386258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.926853E+10 | 0.00 | 0.00 | 0.00 | 0.236597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.898162E+10 | 0.00 | 0.00 | 0.00 | 0.887090E+10 | 0.00 | 0.155970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.858138E+10 | 0.00 | 0.00 | 0.00 | 0.192243E+10 | 0.00 | 0.310235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.925465E+10 | 0.00 | 0.00 | 0.00 | 0.264822E+09 | 0.00 | 0.159966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111524E+12 | 0.00 | 0.00 | 0.00 | 0.175251E+12 | 0.00 | 0.811884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.855160E+10 | 0.00 | 0.00 | 0.00 | 14094270.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.102644E+11 | 0.00 | 0.00 | 0.00 | 0.386258E+11 | 0.00 | 0.395153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.209055E+10 | 0.00 | 0.00 | 0.00 | 7183319.15 | 0.00 | 0.307605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189863E+10 | 0.00 | 0.00 | 0.00 | 0.175566E+09 | 0.00 | 0.171002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.212710E+10 | 0.00 | 0.00 | 0.00 | 0.545868E+09 | 0.00 | 0.123104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205964E+10 | 0.00 | 0.00 | 0.00 | 0.130038E+10 | 0.00 | 41167029.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220145E+10 | 0.00 | 0.00 | 0.00 | 0.243676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.229736E+10 | 0.00 | 0.00 | 0.00 | 0.400806E+10 | 0.00 | 539981.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.243137E+10 | 0.00 | 0.00 | 0.00 | 0.479721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.252399E+10 | 0.00 | 0.00 | 0.00 | 0.531133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.228732E+10 | 0.00 | 0.00 | 0.00 | 0.340750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218000E+10 | 0.00 | 0.00 | 0.00 | 0.143217E+10 | 0.00 | 5164430.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201516E+10 | 0.00 | 0.00 | 0.00 | 0.448387E+09 | 0.00 | 0.138295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208827E+10 | 0.00 | 0.00 | 0.00 | 83171113.22 | 0.00 | 0.982728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262008E+11 | 0.00 | 0.00 | 0.00 | 0.239536E+11 | 0.00 | 0.607707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.189863E+10 | 0.00 | 0.00 | 0.00 | 7183319.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.252399E+10 | 0.00 | 0.00 | 0.00 | 0.531133E+10 | 0.00 | 0.307605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.164140E+10 | 0.00 | 0.00 | 0.00 | 863802.35 | 0.00 | 0.555680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148424E+10 | 0.00 | 0.00 | 0.00 | 0.106241E+09 | 0.00 | 0.327548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165410E+10 | 0.00 | 0.00 | 0.00 | 0.328035E+09 | 0.00 | 0.516673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158910E+10 | 0.00 | 0.00 | 0.00 | 0.836750E+09 | 0.00 | 0.148398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167025E+10 | 0.00 | 0.00 | 0.00 | 0.167495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.175247E+10 | 0.00 | 0.00 | 0.00 | 0.308765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185570E+10 | 0.00 | 0.00 | 0.00 | 0.377905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.194108E+10 | 0.00 | 0.00 | 0.00 | 0.426522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173914E+10 | 0.00 | 0.00 | 0.00 | 0.259032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166726E+10 | 0.00 | 0.00 | 0.00 | 0.104130E+10 | 0.00 | 75440728.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156397E+10 | 0.00 | 0.00 | 0.00 | 0.247888E+09 | 0.00 | 0.435555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163450E+10 | 0.00 | 0.00 | 0.00 | 41124802.81 | 0.00 | 0.229687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201932E+11 | 0.00 | 0.00 | 0.00 | 0.179994E+11 | 0.00 | 0.123052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.148424E+10 | 0.00 | 0.00 | 0.00 | 863802.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.194108E+10 | 0.00 | 0.00 | 0.00 | 0.426522E+10 | 0.00 | 0.555680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.213831E+10 | 0.00 | 0.00 | 9286.51 | 0.00 | 0.562398E+10 | 29159295.85 | 0.00 | 0.20 |
February | 0.247631E+10 | 0.00 | 0.00 | 542912.61 | 197385.99 | 0.293648E+10 | 0.537627E+09 | 0.00 | 0.25 |
March | 0.290446E+10 | 37937669.63 | 0.00 | 2730974.79 | 0.00 | 0.304373E+09 | 0.221400E+10 | 0.00 | 0.33 |
April | 0.108353E+10 | 0.127721E+09 | 0.00 | 5166614.65 | 2872502.89 | 50642784.31 | 0.253947E+10 | 0.00 | 0.43 |
May | 0.245011E+09 | 0.127227E+10 | 0.00 | 5558087.62 | 0.00 | 0.00 | 0.179976E+10 | 0.00 | 0.39 |
June | 44127381.37 | 0.456070E+10 | 0.00 | 2975120.26 | 0.00 | 0.00 | 0.502216E+09 | 0.00 | 0.28 |
July | 205327.38 | 0.653561E+10 | 0.00 | 289760.92 | 0.00 | 0.00 | 85913076.58 | 0.00 | 0.21 |
August | 0.00 | 0.730485E+10 | 0.00 | 67451.83 | 0.00 | 0.00 | 6553379.81 | 0.00 | 0.21 |
September | 91882821.45 | 0.312117E+10 | 0.00 | 4450983.64 | 0.00 | 0.00 | 0.130575E+10 | 0.00 | 0.33 |
October | 0.159601E+10 | 0.603967E+09 | 0.00 | 5995218.97 | 947969.98 | 10585275.10 | 0.351612E+10 | 0.00 | 0.39 |
November | 0.301292E+10 | 8180620.73 | 0.00 | 3037322.32 | 19336700.99 | 0.330120E+09 | 0.254887E+10 | 0.00 | 0.33 |
December | 0.381020E+10 | 0.00 | 0.00 | 457099.44 | 0.00 | 0.218776E+10 | 0.442384E+09 | 0.00 | 0.22 |
Annual Sum or Average | 0.174030E+11 | 0.235724E+11 | 0.00 | 31280833.57 | 23354559.85 | 0.114439E+11 | 0.155278E+11 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 9286.51 | 0.00 | 0.00 | 6553379.81 | 0.00 | 0.20 |
Maximum of Months | 0.381020E+10 | 0.730485E+10 | 0.00 | 5995218.97 | 19336700.99 | 0.562398E+10 | 0.351612E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.478656E+11 | 0.00 | 0.00 | 1085831.66 | 0.00 | 0.112357E+11 | 0.142787E+10 | 0.00 | 0.39 |
February | 0.333482E+11 | 0.00 | 0.00 | 9830842.87 | 0.00 | 0.556749E+10 | 0.721227E+10 | 0.00 | 0.45 |
March | 0.190760E+11 | 0.665916E+09 | 0.00 | 29759920.67 | 0.00 | 24855620.66 | 0.190289E+11 | 0.00 | 0.53 |
April | 0.700725E+10 | 0.237133E+10 | 0.00 | 40002577.46 | 143654.32 | 0.00 | 0.149678E+11 | 0.00 | 0.57 |
May | 0.152731E+10 | 0.129016E+11 | 0.00 | 31074225.06 | 267782.10 | 0.00 | 0.673242E+10 | 0.00 | 0.52 |
June | 0.432142E+09 | 0.373460E+11 | 0.00 | 11978700.24 | 0.00 | 0.00 | 0.174558E+10 | 0.00 | 0.45 |
July | 1045111.54 | 0.514969E+11 | 0.00 | 2311333.22 | 0.00 | 0.00 | 0.442669E+09 | 0.00 | 0.41 |
August | 0.00 | 0.570879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.871687E+09 | 0.248694E+11 | 0.00 | 20686811.07 | 0.00 | 0.00 | 0.503794E+10 | 0.00 | 0.48 |
October | 0.111890E+11 | 0.546788E+10 | 0.00 | 38536929.68 | 285580.04 | 0.00 | 0.185509E+11 | 0.00 | 0.54 |
November | 0.230623E+11 | 0.104069E+09 | 0.00 | 24880525.00 | 58928493.93 | 0.436738E+09 | 0.156342E+11 | 0.00 | 0.51 |
December | 0.420219E+11 | 0.00 | 0.00 | 4345737.54 | 0.00 | 0.373708E+10 | 0.327766E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.186402E+12 | 0.192311E+12 | 0.00 | 0.214493E+09 | 59625510.39 | 0.210019E+11 | 0.940582E+11 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.478656E+11 | 0.570879E+11 | 0.00 | 40002577.46 | 58928493.93 | 0.112357E+11 | 0.190289E+11 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.354990E+10 | 0.00 | 0.00 | 1629214.75 | 0.00 | 0.117703E+10 | 0.165911E+10 | 0.00 | 0.47 |
February | 0.242114E+10 | 197424.50 | 0.00 | 4021640.96 | 0.00 | 0.615493E+09 | 0.244339E+10 | 0.00 | 0.72 |
March | 0.976578E+09 | 81802798.59 | 0.00 | 8169948.89 | 0.00 | 30837045.35 | 0.481873E+10 | 0.00 | 1.01 |
April | 0.454990E+09 | 0.269977E+09 | 0.00 | 6326372.72 | 0.00 | 8262707.42 | 0.288762E+10 | 0.00 | 0.96 |
May | 97889910.97 | 0.130226E+10 | 0.00 | 4624341.70 | 0.00 | 0.00 | 0.162590E+10 | 0.00 | 0.84 |
June | 28312498.76 | 0.373927E+10 | 0.00 | 1626949.24 | 0.00 | 0.00 | 0.384811E+09 | 0.00 | 0.55 |
July | 449390.57 | 0.524295E+10 | 0.00 | 217640.82 | 0.00 | 0.00 | 81019703.16 | 0.00 | 0.42 |
August | 0.00 | 0.591385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 17899836.96 | 0.275332E+10 | 0.00 | 3360374.20 | 0.00 | 0.00 | 0.116592E+10 | 0.00 | 0.66 |
October | 0.551325E+09 | 0.674286E+09 | 0.00 | 10306009.19 | 0.00 | 0.00 | 0.456933E+10 | 0.00 | 1.05 |
November | 0.106045E+10 | 42033095.47 | 0.00 | 9352345.35 | 2066030.77 | 50319982.20 | 0.506897E+10 | 0.00 | 1.00 |
December | 0.233931E+10 | 383690.93 | 0.00 | 4380989.10 | 0.00 | 0.342813E+09 | 0.354254E+10 | 0.00 | 0.63 |
Annual Sum or Average | 0.114982E+11 | 0.200203E+11 | 0.00 | 54015826.92 | 2066030.77 | 0.222476E+10 | 0.282473E+11 | 0.00 | 0.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.354990E+10 | 0.591385E+10 | 0.00 | 10306009.19 | 2066030.77 | 0.117703E+10 | 0.506897E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.288425E+10 | 0.00 | 0.00 | 244254.19 | 0.00 | 0.254645E+10 | 0.322748E+09 | 0.00 | 0.41 |
February | 0.213267E+10 | 109701.99 | 0.00 | 1641202.13 | 0.00 | 0.145851E+10 | 0.955776E+09 | 0.00 | 0.55 |
March | 0.153393E+10 | 64830994.05 | 0.00 | 3283173.35 | 0.00 | 0.227163E+09 | 0.233643E+10 | 0.00 | 0.70 |
April | 0.729242E+09 | 0.197335E+09 | 0.00 | 2730047.49 | 403734.41 | 76327829.15 | 0.150122E+10 | 0.00 | 0.72 |
May | 0.252105E+09 | 0.108848E+10 | 0.00 | 2304839.40 | 0.00 | 0.00 | 0.989751E+09 | 0.00 | 0.68 |
June | 60722037.20 | 0.345973E+10 | 0.00 | 987183.11 | 0.00 | 0.00 | 0.226833E+09 | 0.00 | 0.50 |
July | 7000268.84 | 0.487473E+10 | 0.00 | 175792.40 | 0.00 | 0.00 | 89146032.27 | 0.00 | 0.42 |
August | 0.00 | 0.556069E+10 | 0.00 | 28026.61 | 0.00 | 0.00 | 7529162.27 | 0.00 | 0.41 |
September | 0.111953E+09 | 0.249388E+10 | 0.00 | 1841944.76 | 0.00 | 0.00 | 0.696839E+09 | 0.00 | 0.56 |
October | 0.996165E+09 | 0.579280E+09 | 0.00 | 5517653.56 | 0.00 | 40000054.25 | 0.253541E+10 | 0.00 | 0.76 |
November | 0.171216E+10 | 20600517.57 | 0.00 | 4355063.25 | 3279797.18 | 0.130602E+09 | 0.268302E+10 | 0.00 | 0.73 |
December | 0.287355E+10 | 1231.93 | 0.00 | 1315002.83 | 0.00 | 0.962269E+09 | 0.112534E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.132938E+11 | 0.183397E+11 | 0.00 | 24424183.09 | 3683531.58 | 0.544132E+10 | 0.134700E+11 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 28026.61 | 0.00 | 0.00 | 7529162.27 | 0.00 | 0.41 |
Maximum of Months | 0.288425E+10 | 0.556069E+10 | 0.00 | 5517653.56 | 3279797.18 | 0.254645E+10 | 0.268302E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |