Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2020-06-03 19:11:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1620.15 | 706.26 | 706.26 |
Net Site Energy | 1620.15 | 706.26 | 706.26 |
Total Source Energy | 4908.86 | 2139.88 | 2139.88 |
Net Source Energy | 4908.86 | 2139.88 | 2139.88 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 21.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 650.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 415.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 193.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 85.36 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1513.50 | 106.65 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 21.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 650.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 415.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 194.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 193.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 85.36 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 207.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 367.71 | 46.49 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 659.77 | 46.49 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 207.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 367.71 | 46.49 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 659.77 | 46.49 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1513.500 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1513.500 | 100.00 |
Total On-Site and Utility Electric Sources | 1513.500 | 100.00 |
Total Electricity End Uses | 1513.500 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 303.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 55.45 |
Skylight-Roof Ratio [%] | 2.42 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.5670 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 18.0834 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 18.0834 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 18.0834 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 9.6875 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.2979 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.2979 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-JUN-15:00 | 01-JAN-08:09 | - | - | - | 04-MAY-11:09 |
Heating | 0.00 | 129439.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 94561.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 31216.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10752.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 17701.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 154232.37 | 131299.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 129439.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 94561.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 31216.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10752.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 17701.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 23.08 | 0.00 | 0.00 | 0.00 |
Cooling | 2059.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1314.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 616.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 611.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 92.53 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4793.25 | 115.61 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 10.06 | 0.00 | 0.00 | 0.00 |
Cooling | 897.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 573.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 83.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 266.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 40.33 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2089.48 | 50.39 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 10.06 | 0.00 | 0.00 | 0.00 |
Cooling | 897.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 573.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 83.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 266.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 40.33 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2089.48 | 50.39 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 3.07 |
CORE_RETAIL DIRECT AIR | 9.22 |
POINT_OF_SALE DIRECT AIR | 1.68 |
FRONT_RETAIL DIRECT AIR | 1.50 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 1.44 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 1.44 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 32632.14 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 73076.75 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 240697.25 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 40875.08 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 36687.48 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 3.07 | 3.07 | 3.07 | 3.07 | 3.07 | 3.07 | 1.00 | 1.00 | 3.07 |
PSZ-AC:2 | 9.22 | 9.22 | 9.22 | 9.22 | 9.34 | 9.34 | 1.00 | 0.986393 | 9.34 |
PSZ-AC:3 | 1.68 | 1.68 | 1.68 | 1.68 | 1.68 | 1.68 | 1.00 | 1.00 | 1.68 |
PSZ-AC:4 | 1.50 | 1.50 | 1.50 | 1.50 | 1.50 | 1.50 | 1.00 | 1.00 | 1.50 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 3.07 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 9.34 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.68 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 1.50 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 3.07 | 3.07 | 3.07 | 2.02 | 63349.74 | 73076.75 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 9.34 | 9.34 | 9.34 | 6.17 | 226516.43 | 240697.25 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.68 | 1.68 | 1.68 | 1.11 | 35707.96 | 40875.08 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.50 | 1.50 | 1.50 | 0.988025 | 32489.92 | 36687.48 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 3.07 | 1.53 | 2.05 | 58988.39 | 63349.74 | 31674.87 | 31674.87 | 0.725733 | 0.725730 | 0.725730 | 0.725730 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 9.34 | 4.67 | 6.23 | 213992.25 | 226516.43 | 113258.21 | 113258.21 | 0.682061 | 0.682060 | 0.682060 | 0.682060 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.68 | 0.841775 | 1.12 | 33329.61 | 35707.96 | 17853.98 | 17853.98 | 0.717941 | 0.717940 | 0.717940 | 0.717940 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.50 | 0.748505 | 0.998007 | 30388.20 | 32489.92 | 16244.96 | 16244.96 | 0.711419 | 0.711420 | 0.711420 | 0.711420 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 3.07 | 3282.80 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 9.34 | 15641.57 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.68 | 1801.47 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.50 | 1601.87 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.567 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.637 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 18.083 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 21.313 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 18.083 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 39.603 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 18.083 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 21.313 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 9.688 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.688 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2874.639 | 7.567 | 46.863 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2874.639 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 28942.124 | 18.083 | 111.990 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28942.124 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2727.153 | 18.083 | 111.990 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2727.153 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2727.153 | 18.083 | 111.990 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2727.153 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 116.250 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 116.250 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.3762 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9750000 | 3.9750000 | 3.9750000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
21 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
22 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
23 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
24 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
25 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
26 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
27 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
28 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
29 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
30 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
31 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
32 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
33 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 30 | 1 | VerySmooth | 5.832 | 0.251 | 0.110 | 0.250 |
2 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 31 | 1 | VerySmooth | 5.779 | 0.360 | 0.195 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1915 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 33868.08224 | 40641.69869 | 2.55659 | 3.06790 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | 41.28867 | 9.11023E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 24800.67924 | 29760.81508 | 1.07250 | 1.28699 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 105309.58448 | 126371.50137 | 7.68097 | 9.21716 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 57606.99042 | 69128.38851 | 2.45382 | 2.94458 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 18585.65155 | 22302.78186 | 1.40295 | 1.68355 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 41.51500 | 9.11022E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 11505.27158 | 13806.32590 | 0.49892 | 0.59870 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 16526.32987 | 19831.59585 | 1.24751 | 1.49701 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 41.80600 | 9.11023E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 11498.03236 | 13797.63883 | 0.49860 | 0.59832 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00000 | 9.11023E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 27188.35561 | 32626.02673 | 1.20127 | 1.44152 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 44912.91 | 3.06790 | 3.06790 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 32971.96 | 1.28699 | 1.28699 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 159904.35 | 9.34431 | 9.34431 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 98958.76 | 2.94458 | 2.94458 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 25753.10 | 1.68355 | 1.68355 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 16521.56 | 0.59870 | 0.59870 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 23369.61 | 1.49701 | 1.49701 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 16512.93 | 0.59832 | 0.59832 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.06790 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.21716 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.68355 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.49701 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.44152 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.44152 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 32632.14482 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.06790 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.06790 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.06790 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.06790 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.06790 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.06790 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 9.21716 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 9.21716 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.21716 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 9.21716 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.34431 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 9.34431 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.98639 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.68355 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.68355 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.68355 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.68355 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.68355 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.68355 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.49701 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.49701 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.49701 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.49701 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.49701 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.49701 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 3.06790 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 9.34431 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.68355 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.49701 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.06790 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.06790 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.06790 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.06790 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.02482 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.06790 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.53395 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.04527 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 58988.38905 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 63349.74000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 31674.87000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 31674.87000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72573 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72573 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72573 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72573 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 63349.74000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 73076.74935 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.06790 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3282.80109 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 73076.74935 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.34431 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 9.34431 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 9.34431 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 9.34431 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 6.16724 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 9.34431 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.67216 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 6.22954 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 213992.25044 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 226516.43000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 113258.21500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 113258.21500 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68206 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68206 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68206 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68206 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 226516.43000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 240697.25162 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 9.34431 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 15641.57462 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 240697.25162 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.68355 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.68355 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.68355 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.68355 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.11114 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.68355 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.84178 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.12237 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 33329.61287 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 35707.96000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 17853.98000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 17853.98000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71794 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71794 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71794 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71794 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35707.96000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 40875.08455 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.68355 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1801.47363 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 40875.08455 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.49701 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.49701 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.49701 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.49701 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98802 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.49701 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74851 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.99801 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 30388.19569 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 32489.92000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16244.96000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 16244.96000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71142 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71142 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71142 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71142 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32489.92000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36687.47928 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.49701 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1601.86875 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 36687.47928 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 60937.5 | 11.43 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 219148.1 | 13.48 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 34383.6 | 106.55 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 31311.9 | 129.16 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1545.03 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | |
1 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R4C1 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
2 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R4C2 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
3 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R4C3 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
4 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R4C4 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
5 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C1 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
6 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C2 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
7 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C4 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
8 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C3 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
9 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C2 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
10 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C1 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
11 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C3 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
12 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C4 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
13 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R3C2 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
14 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R3C1 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
15 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R3C3 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
16 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R3C4 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 8 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 8.3269487316E-002 | 0.3658317676 | Pass | Pass | 4.9143796209E-002 | 0.1641933766 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 4.5472749583E-002 | 0.1759797501 | Pass | Pass | 0.1970901115 | 0.7549756224 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 9.3284827385E-002 | 0.2674471868 | Pass | Pass | 0.3093183278 | 2.7978768166 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 8.6874926889E-002 | 0.3082850832 | Pass | Pass | 0.1796770428 | 0.5775741781 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1219739487 | 0.5169854904 | Pass | Pass | 8.5643834999E-002 | 0.4794805973 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.358 | 0.376 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.358 | 0.376 | 1600.48 | 1545.03 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.358 | 0.376 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.358 | 0.376 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.358 | 0.376 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_1.2_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 5.832 | 0.251 | 0.250 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_1.2_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 5.832 | 0.251 | 0.250 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_1.2_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 5.832 | 0.251 | 0.250 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 139.39 | 5.811 | 0.295 | 0.310 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 139.39 | 5.811 | 0.295 | 0.310 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.5670 | 379.89 | 2874.64 | LightsWired | BLDG_LIGHT_BACK_SCH | 63.14 | 168.00 | 62.27 | 0.0000 | Y | 33.60 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 18.0834 | 1600.48 | 28942.12 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 57.12 | 0.0000 | Y | 310.34 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 18.0834 | 150.81 | 2727.15 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.94 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 18.0834 | 150.81 | 2727.15 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.94 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 9.6875 | 12.00 | 116.25 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 57.54 | 168.00 | 56.76 | 0.0000 | Y | 1.24 |
Interior Lighting Total | 16.2979 | 2293.99 | 37387.32 | 415.06 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 28942.12 | 7235.53 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 28942.12 | 7235.53 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 316.30 | AstronomicalClock | - | 41.75 | 41.75 | 2.48 | |
EXTERIOR_LIGHTS_B | 4328.00 | AstronomicalClock | - | 83.75 | 71.15 | 57.81 | |
Exterior Lighting Total | 4644.30 | 60.29 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 63349.74 | 45974.81 | 17374.93 | 0.73 | 3.73 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 226516.43 | 154497.80 | 72018.63 | 0.68 | 3.30 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 35707.96 | 25636.17 | 10071.79 | 0.72 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 32489.92 | 23113.98 | 9375.94 | 0.71 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 60937.5 | 11.43 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 219148.1 | 13.48 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 34383.6 | 106.55 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 31311.9 | 129.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 32632.14 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 73076.75 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 240697.25 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 40875.08 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 36687.48 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.58 | 622.50 | 1.44 | 1542.50 | 1070.05 | 1.00 | 1.36 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 3.07 | 3282.80 | 1070.05 | 1.00 | 1.26 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.61 | 1018.41 | 9.34 | 15641.57 | 1673.92 | 1.00 | 1.16 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.68 | 1801.47 | 1070.05 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.50 | 1601.87 | 1070.05 | 1.00 | 1.36 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 33868.08 | 40641.70 | 106.98 | 2.557 | 3.068 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | 23.89 | 23.89 | 0.00741 | 41.29 | 0.00911 | 0.232 | 0.00 |
CORE_RETAIL | 105309.58 | 126371.50 | 78.96 | 7.681 | 9.217 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 23.89 | 23.89 | 0.00771 | 34.82 | 0.00911 | 1.890 | 0.00 |
POINT_OF_SALE | 18585.65 | 22302.78 | 147.89 | 1.403 | 1.684 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 23.89 | 23.89 | 0.00730 | 41.52 | 0.00911 | 0.178 | 0.00 |
FRONT_RETAIL | 16526.33 | 19831.60 | 131.50 | 1.248 | 1.497 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 23.89 | 23.89 | 0.00733 | 41.81 | 0.00911 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 41.07 | 100.00 | 0.00001 | 42.00 | 0.00911 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 24800.68 | 29760.82 | 78.34 | 1.072 | 1.287 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00798 | 6.30 | 0.00607 | 0.232 | 0.00 |
CORE_RETAIL | 57606.99 | 69128.39 | 43.19 | 2.454 | 2.945 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00798 | 6.30 | 0.00607 | 1.890 | 0.00 |
POINT_OF_SALE | 11505.27 | 13806.33 | 91.55 | 0.499 | 0.599 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00798 | 6.30 | 0.00607 | 0.178 | 0.00 |
FRONT_RETAIL | 11498.03 | 13797.64 | 91.49 | 0.499 | 0.598 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00798 | 6.30 | 0.00607 | 0.178 | 0.00 |
FRONT_ENTRY | 27188.36 | 32626.03 | 2718.84 | 1.201 | 1.442 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.09 | 0.00694 | 6.30 | 0.00607 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 3.07 | 3.07 | 1.29 | 1.29 | 3.0679 | 3.0679 | 3.0679 | 1.0000 | 1.0000 |
PSZ-AC:2 | 9.34 | 9.34 | 2.94 | 2.94 | 9.3443 | 9.2172 | 9.3443 | 0.9864 | 1.0000 |
PSZ-AC:3 | 1.68 | 1.68 | 0.60 | 0.60 | 1.6835 | 1.6835 | 1.6835 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.50 | 1.50 | 0.60 | 0.60 | 1.4970 | 1.4970 | 1.4970 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 32632.145 | 32632.145 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32632.14 | 32632.14 | 1.441522 | 20.94 | 13.57 | 0.00692922 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.09 | 0.00693773 | 43.5586 | 32626.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 31674.870 | 0.000 | 3.067900 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | 31674.87 | 29332.61 | 3.067900 | 25.22 | 15.71 | 0.00753797 | 12.80 | 10.33 | 0.00700000 | 41.52 | 0.00911022 | 22.06 | 7.5480 | 23.89 | 0.00740928 | 39.2087 | 33847.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 73076.749 | 73076.749 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 73076.75 | 73076.75 | 3.067903 | 18.28 | 13.21 | 0.00763472 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 7.5480 | 21.11 | 0.00797752 | 49.9343 | 24800.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 113258.215 | 0.000 | 9.344310 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 | 113258.21 | 101531.66 | 9.344310 | 27.63 | 16.85 | 0.00788796 | 12.80 | 10.33 | 0.00700000 | 42.00 | 0.00911023 | 22.20 | 20.2285 | 23.89 | 0.00770957 | 40.7810 | 100891.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 240697.252 | 240697.252 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 240697.25 | 240697.25 | 9.344305 | 11.51 | 9.51 | 0.00675637 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 20.2285 | 21.11 | 0.00798266 | 49.9659 | 57606.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 17853.980 | 0.000 | 1.683550 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 17853.98 | 16681.32 | 1.683550 | 25.79 | 15.87 | 0.00748932 | 12.80 | 10.33 | 0.00700000 | 41.81 | 0.00911023 | 22.15 | 10.5795 | 23.89 | 0.00729704 | 38.6214 | 18561.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 40875.085 | 40875.085 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40875.08 | 40875.08 | 1.683546 | 16.60 | 12.34 | 0.00741571 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 10.5795 | 21.11 | 0.00798459 | 49.9779 | 11505.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 16244.960 | 0.000 | 1.497010 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 16244.96 | 15079.95 | 1.497010 | 26.04 | 16.01 | 0.00754562 | 12.80 | 10.33 | 0.00700000 | 42.00 | 0.00911023 | 22.20 | 11.8978 | 23.89 | 0.00733381 | 38.8138 | 16514.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 36687.479 | 36687.479 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36687.48 | 36687.48 | 1.497007 | 16.60 | 12.34 | 0.00741531 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 11.8978 | 21.11 | 0.00798455 | 49.9777 | 11498.03 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 32632.145 | 32632.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 1.441522 | 1.69203745 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32632.14 | 32632.14 | 1.0000 | 1.69203745 | 1.441522 | 20.94 | 13.57 | 0.00692922 | 38642.4 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32632.14 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.09 | 0.00693773 | 21.09 | 0.00693773 | 43.5586 | 32626.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31674.870 | 0.000 | 3.067900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.8527 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | 31674.87 | 29332.61 | 1.0000 | 3.60105641 | 3.067900 | 25.22 | 15.71 | 0.00753797 | 44546.8 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31674.87 | 41.52 | 0.00911022 | 22.06 | 0.23156651 | 7.5480 | 23.89 | 0.00740952 | 23.89 | 0.00740928 | 39.2087 | 33847.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 73076.749 | 73076.749 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.067903 | 3.60105978 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 73076.75 | 73076.75 | 1.0000 | 3.60105978 | 3.067903 | 18.28 | 13.21 | 0.00763472 | 37721.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 73076.75 | 6.30 | 0.00607234 | 6.30 | 0.23156651 | 7.5480 | 20.91 | 0.00797752 | 21.11 | 0.00797752 | 49.9343 | 24800.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 113258.215 | 0.000 | 9.344310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5033 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 | 113258.21 | 101531.66 | 1.0000 | 10.96821521 | 9.344310 | 27.63 | 16.85 | 0.00788796 | 47900.2 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 113258.21 | 42.00 | 0.00911023 | 22.20 | 1.89021192 | 20.2285 | 23.89 | 0.00756925 | 23.89 | 0.00770957 | 40.7810 | 100891.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 240697.252 | 240697.252 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 9.344305 | 10.96820974 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 240697.25 | 240697.25 | 1.0000 | 10.96820974 | 9.344305 | 11.51 | 9.51 | 0.00675637 | 28604.6 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 240697.25 | 6.30 | 0.00607234 | 6.30 | 1.89021192 | 20.2285 | 20.84 | 0.00798266 | 21.11 | 0.00798266 | 49.9659 | 57606.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17853.980 | 0.000 | 1.683550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.7623 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 17853.98 | 16681.32 | 1.0000 | 1.97612651 | 1.683550 | 25.79 | 15.87 | 0.00748932 | 45000.5 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17853.98 | 41.81 | 0.00911023 | 22.15 | 0.17811053 | 10.5795 | 23.89 | 0.00729727 | 23.89 | 0.00729704 | 38.6214 | 18561.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 40875.085 | 40875.085 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.683546 | 1.97612163 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40875.08 | 40875.08 | 1.0000 | 1.97612163 | 1.683546 | 16.60 | 12.34 | 0.00741571 | 35459.3 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40875.08 | 6.30 | 0.00607234 | 6.30 | 0.17811053 | 10.5795 | 20.97 | 0.00798459 | 21.11 | 0.00798459 | 49.9779 | 11505.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16244.960 | 0.000 | 1.497010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.8669 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 16244.96 | 15079.95 | 1.0000 | 1.75716857 | 1.497010 | 26.04 | 16.01 | 0.00754562 | 45407.1 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16244.96 | 42.00 | 0.00911023 | 22.20 | 0.17811053 | 11.8978 | 23.89 | 0.00733416 | 23.89 | 0.00733381 | 38.8138 | 16514.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36687.479 | 36687.479 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.497007 | 1.75716559 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36687.48 | 36687.48 | 1.0000 | 1.75716559 | 1.497007 | 16.60 | 12.34 | 0.00741531 | 35455.5 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36687.48 | 6.30 | 0.00607234 | 6.30 | 0.17811053 | 11.8978 | 20.97 | 0.00798455 | 21.11 | 0.00798455 | 49.9777 | 11498.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 3086.83 | 1398.33 | 90.67 |
CORE_RETAIL | 3464.33 | 1016.33 | 229.17 |
POINT_OF_SALE | 4054.83 | 393.50 | 19.50 |
FRONT_RETAIL | 3921.67 | 551.50 | 67.67 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 4146.50 | 1611.33 | 303.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 4.33 | 59.67 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 0.33 | 96.83 | 0.00 | 0.00 |
FRONT_RETAIL | 0.67 | 67.33 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 4.50 | 112.17 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.44 | 61.34 | 2317.33 | 0.371 | 0.013 | 0.000 | 0.000 |
CORE_RETAIL | 128.26 | 258.43 | 9762.95 | 0.719 | 0.002 | 0.000 | 0.000 |
POINT_OF_SALE | 12.09 | 24.35 | 919.94 | 0.719 | 0.014 | 0.000 | 0.000 |
FRONT_RETAIL | 12.09 | 24.35 | 919.94 | 0.719 | 0.014 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.44 | 61.34 | 2317.33 | 0.339 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.26 | 258.43 | 9762.95 | 0.658 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.09 | 24.35 | 919.94 | 0.660 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.09 | 24.35 | 919.94 | 0.659 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1513.50 | 3650.00 | 15-JAN-07:20 | 154232.37 | 10-JUN-16:00 |
Electricity:Building | 609.69 | 3408.81 | 12-FEB-08:50 | 44140.05 | 02-JAN-16:00 |
Electricity:Zone:BACK_SPACE | 83.46 | 599.86 | 01-JAN-00:10 | 5099.20 | 02-JAN-09:10 |
InteriorLights:Electricity | 415.06 | 1628.18 | 12-FEB-08:50 | 33387.34 | 02-JAN-16:00 |
InteriorLights:Electricity:Zone:BACK_SPACE | 33.60 | 143.73 | 01-JAN-00:10 | 2344.76 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 415.06 | 1628.18 | 12-FEB-08:50 | 33387.34 | 02-JAN-16:00 |
Electricity:Zone:CORE_RETAIL | 394.41 | 1975.07 | 12-FEB-08:50 | 30692.60 | 02-JAN-16:00 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 310.34 | 1205.92 | 12-FEB-08:50 | 26047.91 | 02-JAN-16:00 |
Electricity:Zone:POINT_OF_SALE | 87.72 | 619.23 | 01-JAN-00:10 | 5370.36 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 34.94 | 136.36 | 01-JAN-00:10 | 2454.44 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 42.86 | 208.83 | 01-JAN-00:10 | 2892.10 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 34.94 | 136.36 | 01-JAN-00:10 | 2454.44 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.24 | 5.81 | 01-JAN-00:10 | 85.79 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.24 | 5.81 | 01-JAN-00:10 | 85.79 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 194.63 | 1780.63 | 01-JAN-00:10 | 10752.72 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.86 | 456.13 | 01-JAN-00:10 | 2754.45 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 194.63 | 1780.63 | 01-JAN-00:10 | 10752.72 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.07 | 769.15 | 01-JAN-00:10 | 4644.69 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.78 | 482.87 | 01-JAN-00:10 | 2915.92 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.92 | 72.48 | 01-JAN-00:10 | 437.66 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1513.50 | 3650.00 | 11-JUN-18:20 | 154232.37 | 10-JUN-16:00 |
ElectricityPurchased:Plant | 1513.50 | 3650.00 | 11-JUN-18:20 | 154232.37 | 10-JUN-16:00 |
Cogeneration:ElectricityPurchased | 1513.50 | 3650.00 | 11-JUN-18:20 | 154232.37 | 10-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1513.50 | 3650.00 | 11-JUN-18:20 | 154232.37 | 10-JUN-16:00 |
ElectricityNet:Plant | 1513.50 | 3650.00 | 11-JUN-18:20 | 154232.37 | 10-JUN-16:00 |
Cogeneration:ElectricityNet | 1513.50 | 3650.00 | 11-JUN-18:20 | 154232.37 | 10-JUN-16:00 |
Electricity:HVAC | 843.52 | 0.00 | 01-JAN-00:10 | 112262.98 | 10-JUN-16:00 |
Fans:Electricity | 193.19 | 0.00 | 01-JAN-00:10 | 17701.60 | 10-JUN-16:00 |
General:Fans:Electricity | 193.19 | 0.00 | 01-JAN-00:10 | 17701.60 | 10-JUN-16:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 650.33 | 0.00 | 01-JAN-00:10 | 94561.38 | 10-JUN-16:00 |
ExteriorLights:Electricity | 60.29 | 0.00 | 01-JAN-07:20 | 4644.30 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.29 | 0.00 | 01-JAN-07:20 | 4644.30 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 106.65 | 1860.00 | 08-JAN-19:10 | 131299.59 | 01-JAN-08:10 |
Gas:Plant | 85.36 | 1860.00 | 04-JAN-05:10 | 4923.56 | 23-JAN-12:30 |
WaterSystems:Gas | 85.36 | 1860.00 | 04-JAN-05:10 | 4923.56 | 23-JAN-12:30 |
Water Heater:WaterSystems:Gas | 85.36 | 1860.00 | 04-JAN-05:10 | 4923.56 | 23-JAN-12:30 |
Gas:HVAC | 21.29 | 0.00 | 01-JAN-00:10 | 129439.59 | 01-JAN-08:10 |
Heating:Gas | 21.29 | 0.00 | 01-JAN-00:10 | 129439.59 | 01-JAN-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 04-MAY-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 04-MAY-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 04-MAY-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 04-MAY-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 04-MAY-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 04-MAY-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 04-MAY-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 04-MAY-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 3602.82 | 0.00 | 01-JAN-00:10 | 430535.71 | 01-JUL-15:50 |
EnergyTransfer:Building | 1305.54 | 0.00 | 01-JAN-00:10 | 157494.25 | 12-JUN-14:40 |
EnergyTransfer:Zone:BACK_SPACE | 230.16 | 0.00 | 01-JAN-00:10 | 37825.40 | 08-MAY-04:10 |
Heating:EnergyTransfer | 15.01 | 0.00 | 01-JAN-00:10 | 84503.71 | 01-JAN-08:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 4.70 | 0.00 | 01-JAN-00:10 | 33569.91 | 01-JAN-07:10 |
Cooling:EnergyTransfer | 1290.53 | 0.00 | 01-JAN-00:10 | 157494.25 | 12-JUN-14:40 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 225.45 | 0.00 | 01-JAN-00:10 | 37825.40 | 08-MAY-04:10 |
EnergyTransfer:Zone:CORE_RETAIL | 747.69 | 0.00 | 01-JAN-00:10 | 92453.43 | 12-JUN-14:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 2.76 | 0.00 | 01-JAN-00:10 | 56668.78 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 744.93 | 0.00 | 01-JAN-00:10 | 92453.43 | 12-JUN-14:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 175.85 | 0.00 | 01-JAN-00:10 | 18374.42 | 02-OCT-14:30 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.18 | 0.00 | 01-JAN-00:10 | 9516.03 | 01-JAN-07:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 175.68 | 0.00 | 01-JAN-00:10 | 18374.42 | 02-OCT-14:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 144.90 | 0.00 | 01-JAN-00:10 | 16814.93 | 02-OCT-14:30 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.44 | 0.00 | 01-JAN-00:10 | 11409.18 | 01-JAN-07:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 144.47 | 0.00 | 01-JAN-00:10 | 16814.93 | 02-OCT-14:30 |
EnergyTransfer:Zone:FRONT_ENTRY | 6.93 | 0.00 | 01-JAN-00:10 | 15072.95 | 31-DEC-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 6.93 | 0.00 | 01-JAN-00:10 | 15072.95 | 31-DEC-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 63.87 | 01-JAN-07:10 |
EnergyTransfer:HVAC | 2297.28 | 0.00 | 01-JAN-00:10 | 298689.81 | 01-JUL-16:00 |
HeatingCoils:EnergyTransfer | 17.03 | 0.00 | 01-JAN-00:10 | 103551.68 | 01-JAN-08:10 |
CoolingCoils:EnergyTransfer | 2280.25 | 0.00 | 01-JAN-00:10 | 298689.81 | 01-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 4.704 | -225.451 | 0.000 | 0.000 | 37.219 | 33.603 | 49.857 | 0.000 | 0.000 | 1.257 | 99.626 | 0.000 | 0.000 | 0.000 | -0.815 | -0.011 |
CORE_RETAIL | 0.000 | 0.000 | 2.759 | -744.919 | 0.000 | 0.000 | 155.538 | 310.341 | 84.072 | 54.240 | 0.000 | 1.058 | 161.487 | 0.000 | -23.828 | 0.000 | -0.749 | -0.021 |
POINT_OF_SALE | 0.000 | 0.000 | 0.175 | -175.676 | 0.000 | 0.000 | 14.596 | 34.941 | 52.780 | 47.675 | 0.000 | 0.531 | 41.330 | 0.000 | -15.902 | 0.000 | -0.450 | -0.001 |
FRONT_RETAIL | 0.000 | 0.000 | 0.438 | -144.464 | 0.000 | 0.000 | 14.633 | 34.941 | 7.922 | 47.922 | 0.000 | 0.538 | 53.651 | 0.000 | -15.167 | 0.000 | -0.414 | -0.001 |
FRONT_ENTRY | 6.933 | -0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.239 | 0.000 | 8.099 | 0.000 | 2.876 | 0.000 | 0.000 | -3.400 | 0.000 | -11.286 | -4.460 |
Total Facility | 6.933 | -0.000 | 8.077 | -1290.511 | 0.000 | 0.000 | 221.986 | 415.064 | 194.630 | 157.936 | 0.000 | 6.261 | 356.094 | 0.000 | -58.296 | 0.000 | -13.714 | -4.495 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 09-MAY-04:01 | 0.00 | 0.00 | 0.00 | -59267.61 | 0.00 | 0.00 | 0.00 | 143.73 | 608.18 | 0.00 | 0.00 | 0.00 | 58515.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 28-APR-05:01 | 0.00 | 0.00 | 0.00 | -198044.83 | 0.00 | 0.00 | 0.00 | 1447.11 | 1025.54 | 0.00 | 0.00 | 0.00 | 196978.65 | 0.00 | -1406.35 | 0.00 | -0.11 | 0.00 |
POINT_OF_SALE | 23-OCT-04:01 | 0.00 | 0.00 | 0.00 | -33487.35 | 0.00 | 0.00 | 0.00 | 136.36 | 643.83 | 0.00 | 0.00 | 0.00 | 34365.68 | 0.00 | -1635.58 | 0.00 | -22.94 | 0.00 |
FRONT_RETAIL | 29-APR-04:01 | 0.00 | 0.00 | 0.00 | -30115.52 | 0.00 | 0.00 | 0.00 | 136.36 | 72.48 | 0.00 | 0.00 | 0.00 | 30636.63 | 0.00 | -729.94 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 01-JAN-07:02 | 0.00 | -638.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 947.18 | 0.00 | -314.32 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-MAY-04:01 | 0.00 | 0.00 | 0.00 | -313248.02 | 0.00 | 0.00 | 0.00 | 1869.37 | 1780.63 | 0.00 | 0.00 | 125.35 | 311503.55 | 0.00 | -2028.23 | 0.00 | -2.65 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 01-JAN-07:01 | 0.00 | 0.00 | 70895.75 | 0.00 | 0.00 | 0.00 | 0.00 | 143.73 | 456.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -71495.62 |
CORE_RETAIL | 01-JAN-08:62 | 0.00 | 0.00 | 222886.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1447.11 | 769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1552.70 | 0.00 | -1.57 | -223548.19 |
POINT_OF_SALE | 01-JAN-07:01 | 0.00 | 0.00 | 38210.19 | 0.00 | 0.00 | 0.00 | 0.00 | 136.36 | 482.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1702.25 | 0.00 | 0.00 | -37127.17 |
FRONT_RETAIL | 01-JAN-07:01 | 0.00 | 0.00 | 34409.65 | 0.00 | 0.00 | 0.00 | 0.00 | 136.36 | 72.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1624.58 | 0.00 | 0.00 | -32993.90 |
FRONT_ENTRY | 31-DEC-18:00 | 15074.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.13 | 0.00 | 0.00 | 0.00 | 0.00 | 799.66 | 0.00 | -357.77 | 0.00 | -15554.56 | 0.00 |
Total Facility | 01-JAN-08:62 | 3505.99 | 0.00 | 246669.09 | 0.00 | 0.00 | 0.00 | 0.00 | 1869.37 | 1780.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2311.41 | 0.00 | -3382.58 | -248131.09 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 3.0679 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 3.0679 | 0.0755 | 1.0000 | 0.2316 | 0.0755 | ||
PSZ-AC:2 | 9.2172 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 9.3443 | 0.2023 | 1.0000 | 1.8902 | 0.2023 | ||
PSZ-AC:3 | 1.6835 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.6835 | 0.1058 | 1.0000 | 0.1781 | 0.1058 | ||
PSZ-AC:4 | 1.4970 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.4970 | 0.1190 | 1.0000 | 0.1781 | 0.1190 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 3.0679 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 3.0679 | 1.0000 | 1.0000 | 0.2316 | 0.0755 | ||
PSZ-AC:2 | 9.2172 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 9.2172 | 1.0000 | 1.0000 | 1.8902 | 0.2051 | ||
PSZ-AC:3 | 1.6835 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.6835 | 1.0000 | 1.0000 | 0.1781 | 0.1058 | ||
PSZ-AC:4 | 1.4970 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.4970 | 1.0000 | 1.0000 | 0.1781 | 0.1190 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 3.0679 | 3.0679 | 3.0679 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 9.2172 | 9.2172 | 9.2172 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.6835 | 1.6835 | 1.6835 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.4970 | 1.4970 | 1.4970 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 3.0679 | 3.0679 | 3.0679 | 3.0679 | 0.2316 | 1.0000 |
PSZ-AC:2 | 9.2172 | 9.3443 | 9.2172 | 9.2172 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.6835 | 1.6835 | 1.6835 | 1.6835 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.4970 | 1.4970 | 1.4970 | 1.4970 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 3.0679 | 3.0679 | 3.0679 | 0.2316 | 0.1799 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 9.2172 | 9.2172 | 9.2172 | 1.8902 | 0.6419 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.6835 | 1.6835 | 1.6835 | 0.1781 | 0.2975 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.4970 | 1.4970 | 1.4970 | 0.1781 | 0.2977 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 3.0679 | 3.0679 | 3.0679 | 3.0679 | 0.2316 | 1.0000 |
PSZ-AC:2 | 9.2172 | 9.2172 | 9.2172 | 9.2172 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.6835 | 1.6835 | 1.6835 | 1.6835 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.4970 | 1.4970 | 1.4970 | 1.4970 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 21.29 | 129439.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 650.33 | 94561.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 415.06 | 33387.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.29 | 4644.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 194.63 | 10752.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 193.19 | 17701.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 85.36 | 4923.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 194.63 | 1513.50 |
Natural Gas | 0.00 | 106.65 |
Additional | 0.00 | 0.00 |
Total | 194.63 | 1620.15 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 180.94 |
Space Heating | 0.00 |
Space Cooling | 283.49 |
Fans (All) | 84.21 |
Service Water Heating | 0.00 |
Receptacle Equipment | 84.84 |
Miscellaneous (All) | 659.77 |
Subtotal | 659.77 |
Natural Gas [MJ/m2] | |
Space Heating | 9.28 |
Service Water Heating | 37.21 |
Miscellaneous (All) | 46.49 |
Subtotal | 46.49 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 25.62 |
Space Heating | 1.31 |
Space Cooling | 40.14 |
Fans (All) | 11.92 |
Service Water Heating | 5.27 |
Receptacle Equipment | 12.01 |
Miscellaneous | 3.72 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3292. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3001. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4559. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_PSZ_AC_2 | CORE_RETAIL DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_PSZ_AC_2 | CORE_RETAIL DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139368E+11 |
February | 0.000 | 0.224712E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.203094E+08 |
December | 0.000 | 0.508594E+10 |
Annual Sum or Average | 0.212902E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.139368E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139368E+11 |
February | 0.000 | 0.224712E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.203094E+08 |
December | 0.000 | 0.508594E+10 |
Annual Sum or Average | 0.212902E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.139368E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139368E+11 |
February | 0.000 | 0.224712E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.203094E+08 |
December | 0.000 | 0.508594E+10 |
Annual Sum or Average | 0.212902E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.139368E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139368E+11 |
February | 0.000 | 0.224712E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.203094E+08 |
December | 0.000 | 0.508594E+10 |
Annual Sum or Average | 0.212902E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.139368E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139368E+11 |
February | 0.000 | 0.224712E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.203094E+08 |
December | 0.000 | 0.508594E+10 |
Annual Sum or Average | 0.212902E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.139368E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139368E+11 |
February | 0.000 | 0.224712E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.203094E+08 |
December | 0.000 | 0.508594E+10 |
Annual Sum or Average | 0.212902E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.139368E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139368E+11 |
February | 0.000 | 0.224712E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.203094E+08 |
December | 0.000 | 0.508594E+10 |
Annual Sum or Average | 0.212902E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.139368E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139368E+11 |
February | 0.000 | 0.224712E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.203094E+08 |
December | 0.000 | 0.508594E+10 |
Annual Sum or Average | 0.212902E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.139368E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.139368E+11 |
February | 0.000 | 0.224712E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.203094E+08 |
December | 0.000 | 0.508594E+10 |
Annual Sum or Average | 0.212902E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.139368E+11 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.506437E+09 | 3720.80 | 14-JAN-17:00 | 20.70 | 14.70 | 0.190695E+10 | 2451.25 | 25-JAN-15:39 | 22.53 | 13.49 |
February | 0.255881E+10 | 8031.15 | 24-FEB-16:00 | 26.30 | 17.46 | 0.191055E+10 | 2451.30 | 23-FEB-15:00 | 24.80 | 14.33 |
March | 0.110118E+11 | 54477.15 | 29-MAR-04:01 | 21.45 | 17.79 | 0.227653E+10 | 2451.35 | 30-MAR-14:39 | 30.80 | 19.42 |
April | 0.241403E+11 | 59018.33 | 29-APR-04:01 | 26.47 | 17.99 | 0.215642E+10 | 2451.47 | 28-APR-14:20 | 38.80 | 21.14 |
May | 0.352814E+11 | 59266.57 | 09-MAY-04:01 | 27.65 | 19.15 | 0.223250E+10 | 2451.45 | 06-MAY-11:09 | 38.85 | 19.66 |
June | 0.355700E+11 | 57151.47 | 05-JUN-04:01 | 30.32 | 20.24 | 0.220158E+10 | 2451.42 | 03-JUN-10:20 | 37.03 | 23.34 |
July | 0.344796E+11 | 51694.86 | 07-JUL-04:01 | 31.73 | 26.03 | 0.218723E+10 | 2451.36 | 15-JUL-10:09 | 32.62 | 27.30 |
August | 0.316098E+11 | 52409.73 | 09-AUG-04:01 | 30.32 | 25.71 | 0.228101E+10 | 2451.33 | 05-AUG-11:39 | 34.57 | 26.25 |
September | 0.249125E+11 | 53729.28 | 27-SEP-04:01 | 23.75 | 21.10 | 0.215640E+10 | 2451.36 | 01-SEP-14:20 | 32.93 | 26.43 |
October | 0.179182E+11 | 56151.78 | 02-OCT-04:01 | 21.82 | 17.77 | 0.218401E+10 | 2451.34 | 27-OCT-14:09 | 30.78 | 19.08 |
November | 0.652054E+10 | 36381.96 | 01-NOV-04:01 | 15.75 | 12.60 | 0.208680E+10 | 2451.29 | 02-NOV-14:39 | 28.20 | 16.00 |
December | 0.945023E+09 | 4256.45 | 01-DEC-16:00 | 22.30 | 13.70 | 0.201853E+10 | 2451.25 | 02-DEC-12:20 | 22.77 | 12.89 |
Annual Sum or Average | 0.225455E+12 | 0.255985E+11 | ||||||||
Minimum of Months | 0.506437E+09 | 3720.80 | 15.75 | 12.60 | 0.190695E+10 | 2451.25 | 22.53 | 12.89 | ||
Maximum of Months | 0.355700E+11 | 59266.57 | 31.73 | 26.03 | 0.228101E+10 | 2451.47 | 38.85 | 27.30 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190698E+11 | 32829.13 | 05-JAN-07:05 | 4.93 | 4.82 | 0.864017E+10 | 10327.13 | 23-JAN-15:39 | 17.93 | 10.80 |
February | 0.274491E+11 | 41078.03 | 23-FEB-16:00 | 24.80 | 14.33 | 0.824650E+10 | 10327.20 | 04-FEB-16:30 | 23.05 | 13.00 |
March | 0.525271E+11 | 163498.37 | 30-MAR-06:02 | 21.25 | 16.71 | 0.960240E+10 | 10327.40 | 30-MAR-14:39 | 30.80 | 19.42 |
April | 0.795155E+11 | 198041.55 | 28-APR-05:01 | 27.22 | 17.14 | 0.908830E+10 | 10327.39 | 15-APR-11:50 | 37.68 | 19.15 |
May | 0.984950E+11 | 194934.38 | 06-MAY-04:01 | 30.18 | 17.70 | 0.940931E+10 | 10327.84 | 06-MAY-10:09 | 36.52 | 19.41 |
June | 0.951732E+11 | 179339.69 | 07-JUN-04:01 | 33.27 | 20.22 | 0.927902E+10 | 10327.09 | 24-JUN-13:00 | 25.00 | 24.49 |
July | 0.880048E+11 | 162364.87 | 05-JUL-04:01 | 32.58 | 25.32 | 0.921877E+10 | 10327.05 | 18-JUL-14:00 | 26.30 | 25.64 |
August | 0.833668E+11 | 148705.31 | 07-AUG-04:01 | 30.00 | 25.70 | 0.961376E+10 | 10326.83 | 05-AUG-11:20 | 34.23 | 26.11 |
September | 0.720161E+11 | 157310.58 | 27-SEP-05:02 | 23.08 | 20.68 | 0.908857E+10 | 10326.93 | 11-SEP-14:09 | 30.67 | 26.81 |
October | 0.644936E+11 | 166957.94 | 16-OCT-06:03 | 21.32 | 15.11 | 0.920353E+10 | 10327.24 | 27-OCT-14:09 | 30.78 | 19.08 |
November | 0.411529E+11 | 49161.43 | 09-NOV-15:10 | 29.07 | 17.66 | 0.882202E+10 | 10327.47 | 08-NOV-15:30 | 29.55 | 18.27 |
December | 0.236650E+11 | 33160.24 | 01-DEC-15:40 | 22.67 | 13.59 | 0.890079E+10 | 10327.28 | 01-DEC-15:20 | 23.03 | 13.47 |
Annual Sum or Average | 0.744929E+12 | 0.109113E+12 | ||||||||
Minimum of Months | 0.190698E+11 | 32829.13 | 4.93 | 4.82 | 0.824650E+10 | 10326.83 | 17.93 | 10.80 | ||
Maximum of Months | 0.984950E+11 | 198041.55 | 33.27 | 25.70 | 0.961376E+10 | 10327.84 | 37.68 | 26.81 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.567241E+10 | 9371.60 | 12-JAN-15:20 | 23.50 | 14.28 | 0.846319E+09 | 973.17 | 13-JAN-15:00 | 21.10 | 15.04 |
February | 0.748786E+10 | 25799.85 | 23-FEB-05:02 | 15.08 | 13.21 | 0.784034E+09 | 973.17 | 15-FEB-15:09 | 22.98 | 16.79 |
March | 0.126368E+11 | 32961.60 | 29-MAR-04:01 | 21.45 | 17.79 | 0.905369E+09 | 973.24 | 28-MAR-14:00 | 35.60 | 18.47 |
April | 0.172873E+11 | 33457.42 | 07-APR-04:01 | 21.75 | 15.07 | 0.856058E+09 | 973.26 | 15-APR-12:20 | 38.47 | 19.45 |
May | 0.202739E+11 | 32453.48 | 28-MAY-06:01 | 26.58 | 17.54 | 0.886270E+09 | 973.26 | 06-MAY-11:09 | 38.85 | 19.66 |
June | 0.195994E+11 | 30876.61 | 05-JUN-04:11 | 30.23 | 20.24 | 0.873993E+09 | 973.22 | 02-JUN-14:09 | 38.28 | 20.72 |
July | 0.190846E+11 | 27683.87 | 07-JUL-04:11 | 31.67 | 26.03 | 0.868295E+09 | 973.18 | 22-JUL-11:09 | 31.90 | 26.92 |
August | 0.184723E+11 | 27240.94 | 04-AUG-04:01 | 28.05 | 24.13 | 0.905516E+09 | 973.19 | 21-AUG-14:09 | 28.90 | 27.62 |
September | 0.169745E+11 | 31033.50 | 27-SEP-04:01 | 23.75 | 21.10 | 0.856040E+09 | 973.19 | 08-SEP-14:09 | 28.40 | 25.90 |
October | 0.177582E+11 | 33487.06 | 23-OCT-04:01 | 18.78 | 14.94 | 0.867022E+09 | 973.25 | 16-OCT-14:09 | 33.27 | 18.88 |
November | 0.131247E+11 | 31839.00 | 02-NOV-04:01 | 16.58 | 13.43 | 0.833752E+09 | 973.13 | 18-NOV-11:09 | 24.53 | 17.41 |
December | 0.730574E+10 | 10859.96 | 01-DEC-15:10 | 23.22 | 13.40 | 0.859016E+09 | 973.17 | 16-DEC-16:00 | 20.70 | 15.14 |
Annual Sum or Average | 0.175678E+12 | 0.103417E+11 | ||||||||
Minimum of Months | 0.567241E+10 | 9371.60 | 15.08 | 13.21 | 0.784034E+09 | 973.13 | 20.70 | 15.04 | ||
Maximum of Months | 0.202739E+11 | 33487.06 | 31.67 | 26.03 | 0.905516E+09 | 973.26 | 38.85 | 27.62 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366709E+10 | 7457.55 | 12-JAN-15:10 | 23.55 | 14.23 | 0.828750E+09 | 973.16 | 05-JAN-15:50 | 19.92 | 13.20 |
February | 0.543805E+10 | 16628.81 | 23-FEB-05:02 | 15.08 | 13.21 | 0.774866E+09 | 973.15 | 08-FEB-15:00 | 24.00 | 16.17 |
March | 0.100193E+11 | 29008.58 | 29-MAR-04:01 | 21.45 | 17.79 | 0.904498E+09 | 973.22 | 28-MAR-14:00 | 35.60 | 18.47 |
April | 0.146261E+11 | 30115.02 | 29-APR-04:01 | 26.47 | 17.99 | 0.856052E+09 | 973.20 | 21-APR-14:09 | 34.82 | 19.60 |
May | 0.174296E+11 | 29410.32 | 29-MAY-06:01 | 29.10 | 17.75 | 0.886262E+09 | 973.24 | 06-MAY-11:09 | 38.85 | 19.66 |
June | 0.166334E+11 | 27919.30 | 05-JUN-04:01 | 30.32 | 20.24 | 0.873990E+09 | 973.19 | 02-JUN-14:20 | 38.37 | 20.77 |
July | 0.162135E+11 | 24445.39 | 07-JUL-04:01 | 31.73 | 26.03 | 0.868290E+09 | 973.16 | 22-JUL-10:39 | 31.87 | 26.92 |
August | 0.155528E+11 | 24263.66 | 09-AUG-04:11 | 30.23 | 25.61 | 0.905514E+09 | 973.16 | 19-AUG-11:30 | 30.50 | 27.38 |
September | 0.142112E+11 | 27367.02 | 27-SEP-04:01 | 23.75 | 21.10 | 0.856033E+09 | 973.15 | 30-SEP-10:30 | 31.50 | 23.64 |
October | 0.150527E+11 | 29730.79 | 23-OCT-04:01 | 18.78 | 14.94 | 0.867011E+09 | 973.22 | 16-OCT-14:09 | 33.27 | 18.88 |
November | 0.105858E+11 | 28249.54 | 02-NOV-04:01 | 16.58 | 13.43 | 0.832951E+09 | 973.14 | 18-NOV-16:00 | 24.80 | 17.32 |
December | 0.503674E+10 | 9051.24 | 01-DEC-15:10 | 23.22 | 13.40 | 0.850230E+09 | 973.16 | 05-DEC-15:00 | 19.80 | 14.25 |
Annual Sum or Average | 0.144466E+12 | 0.103044E+11 | ||||||||
Minimum of Months | 0.366709E+10 | 7457.55 | 15.08 | 13.21 | 0.774866E+09 | 973.14 | 19.80 | 13.20 | ||
Maximum of Months | 0.174296E+11 | 30115.02 | 31.73 | 26.03 | 0.905514E+09 | 973.24 | 38.85 | 27.38 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 74161.07 | 638.67 | 01-JAN-07:02 | 7.25 | 7.08 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 | 24.63 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 |
Annual Sum or Average | 74161.07 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.25 | 7.08 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 74161.07 | 638.67 | 32.95 | 26.26 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285096E+10 | 70896.83 | 01-JAN-07:01 | 7.25 |
February | 0.568708E+09 | 69388.61 | 11-FEB-05:01 | 9.03 |
March | 2372218.44 | 781.96 | 26-MAR-08:35 | 22.13 |
April | 243633.68 | 812.11 | 23-APR-07:05 | 22.45 |
May | 263745.34 | 3077.03 | 06-MAY-05:04 | 29.55 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 162244.96 | 1056.69 | 22-OCT-07:02 | 20.77 |
November | 21563578.38 | 1580.41 | 26-NOV-12:02 | 24.98 |
December | 0.125994E+10 | 70844.48 | 22-DEC-05:01 | 11.18 |
Annual Sum or Average | 0.470421E+10 | |||
Minimum of Months | 0.00 | 0.00 | 7.25 | |
Maximum of Months | 0.285096E+10 | 70896.83 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110506E+10 | 222893.92 | 01-JAN-08:62 | 8.17 |
February | 0.119456E+09 | 140112.45 | 02-FEB-07:03 | 7.12 |
March | 12983935.38 | 7868.23 | 11-MAR-07:06 | 23.87 |
April | 0.134754E+09 | 22425.97 | 16-APR-08:06 | 30.70 |
May | 0.237654E+09 | 24810.54 | 28-MAY-08:06 | 31.93 |
June | 0.227842E+09 | 25217.90 | 04-JUN-08:06 | 31.72 |
July | 0.219453E+09 | 26049.55 | 02-JUL-07:06 | 33.57 |
August | 0.223360E+09 | 18535.67 | 08-AUG-05:06 | 30.10 |
September | 0.202516E+09 | 12629.37 | 25-SEP-06:06 | 26.22 |
October | 50137253.70 | 11749.80 | 04-OCT-06:06 | 25.52 |
November | 1263251.05 | 1352.56 | 26-NOV-10:05 | 22.08 |
December | 0.224719E+09 | 149390.29 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 0.275920E+10 | |||
Minimum of Months | 1263251.05 | 1352.56 | 6.25 | |
Maximum of Months | 0.110506E+10 | 222893.92 | 33.57 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140237E+09 | 38211.16 | 01-JAN-07:01 | 7.25 |
February | 23596246.62 | 31462.30 | 11-FEB-05:01 | 9.03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 145790.07 | 461.59 | 23-APR-07:10 | 22.45 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 120562.81 | 1406.57 | 24-JUN-05:04 | 26.80 |
July | 215454.53 | 1919.10 | 22-JUL-05:04 | 28.97 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 10952788.10 | 18269.23 | 31-DEC-07:01 | 5.53 |
Annual Sum or Average | 0.175267E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.53 | |
Maximum of Months | 0.140237E+09 | 38211.16 | 30.53 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.327421E+09 | 34410.50 | 01-JAN-07:01 | 7.25 |
February | 58775662.16 | 33744.51 | 11-FEB-05:01 | 9.03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 70268.43 | 234.23 | 23-APR-07:05 | 22.45 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 280507.20 | 2370.24 | 07-JUN-05:04 | 33.20 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 179976.30 | 2099.72 | 08-AUG-05:06 | 30.10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 51358860.06 | 31889.98 | 31-DEC-07:01 | 5.53 |
Annual Sum or Average | 0.438086E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.53 | |
Maximum of Months | 0.327421E+09 | 34410.50 | 33.20 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342659E+10 | 13879.16 | 01-JAN-18:00 | 13.10 |
February | 0.882067E+09 | 11326.89 | 10-FEB-18:00 | 14.50 |
March | 71382662.10 | 1890.96 | 16-MAR-07:10 | 15.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 794943.37 | 1297.63 | 31-OCT-07:07 | 16.90 |
November | 91917744.35 | 2338.45 | 27-NOV-08:10 | 11.60 |
December | 0.246031E+10 | 15072.95 | 31-DEC-18:00 | 12.10 |
Annual Sum or Average | 0.693307E+10 | |||
Minimum of Months | 0.00 | 0.00 | 11.60 | |
Maximum of Months | 0.342659E+10 | 15072.95 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.281822E+10 | 2344.76 | 02-JAN-09:09 | 0.420015E+10 | 2754.45 | 02-JAN-09:09 |
February | 0.256399E+10 | 2344.76 | 01-FEB-09:09 | 0.381055E+10 | 2754.45 | 01-FEB-09:09 |
March | 0.292411E+10 | 2344.76 | 01-MAR-09:09 | 0.430594E+10 | 2754.45 | 01-MAR-09:09 |
April | 0.275920E+10 | 2344.76 | 01-APR-09:09 | 0.409182E+10 | 2754.45 | 01-APR-09:09 |
May | 0.287117E+10 | 2344.76 | 01-MAY-08:09 | 0.425304E+10 | 2754.45 | 01-MAY-08:09 |
June | 0.282172E+10 | 2344.76 | 01-JUN-08:09 | 0.415844E+10 | 2754.45 | 01-JUN-08:09 |
July | 0.280865E+10 | 2344.76 | 01-JUL-09:09 | 0.418643E+10 | 2754.45 | 01-JUL-09:09 |
August | 0.292411E+10 | 2344.76 | 01-AUG-08:09 | 0.430594E+10 | 2754.45 | 01-AUG-08:09 |
September | 0.275920E+10 | 2344.76 | 01-SEP-08:09 | 0.409182E+10 | 2754.45 | 01-SEP-08:09 |
October | 0.281822E+10 | 2344.76 | 02-OCT-08:09 | 0.420015E+10 | 2754.45 | 02-OCT-08:09 |
November | 0.272540E+10 | 2344.76 | 01-NOV-08:09 | 0.406638E+10 | 2754.45 | 01-NOV-08:09 |
December | 0.280865E+10 | 2344.76 | 01-DEC-09:09 | 0.418643E+10 | 2754.45 | 01-DEC-09:09 |
Annual Sum or Average | 0.336027E+11 | 0.498571E+11 | ||||
Minimum of Months | 0.256399E+10 | 2344.76 | 0.381055E+10 | 2754.45 | ||
Maximum of Months | 0.292411E+10 | 2344.76 | 0.430594E+10 | 2754.45 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.282436E+11 | 26047.91 | 02-JAN-15:00 | 0.708251E+10 | 4644.69 | 02-JAN-09:09 |
February | 0.246941E+11 | 26047.91 | 01-FEB-16:10 | 0.642555E+10 | 4644.69 | 01-FEB-09:09 |
March | 0.257486E+11 | 26047.91 | 01-MAR-16:40 | 0.726089E+10 | 4644.69 | 01-MAR-09:09 |
April | 0.252876E+11 | 26047.91 | 01-APR-16:00 | 0.689984E+10 | 4644.69 | 01-APR-09:09 |
May | 0.262260E+11 | 26047.91 | 03-MAY-08:09 | 0.717170E+10 | 4644.69 | 01-MAY-08:09 |
June | 0.251820E+11 | 26047.91 | 15-JUN-16:00 | 0.701217E+10 | 4644.69 | 01-JUN-08:09 |
July | 0.237579E+11 | 26047.91 | 10-JUL-16:49 | 0.705936E+10 | 4644.69 | 01-JUL-09:09 |
August | 0.248194E+11 | 26047.91 | 10-AUG-16:49 | 0.726089E+10 | 4644.69 | 01-AUG-08:09 |
September | 0.238928E+11 | 26047.91 | 02-SEP-16:00 | 0.689984E+10 | 4644.69 | 01-SEP-08:09 |
October | 0.266138E+11 | 26047.91 | 02-OCT-16:30 | 0.708251E+10 | 4644.69 | 02-OCT-08:09 |
November | 0.274834E+11 | 26047.91 | 01-NOV-08:09 | 0.685694E+10 | 4644.69 | 01-NOV-08:09 |
December | 0.283919E+11 | 26047.91 | 01-DEC-15:30 | 0.705936E+10 | 4644.69 | 01-DEC-09:09 |
Annual Sum or Average | 0.310341E+12 | 0.840716E+11 | ||||
Minimum of Months | 0.237579E+11 | 26047.91 | 0.642555E+10 | 4644.69 | ||
Maximum of Months | 0.283919E+11 | 26047.91 | 0.726089E+10 | 4644.69 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.293011E+10 | 2454.44 | 02-JAN-09:09 | 0.444637E+10 | 2915.92 | 02-JAN-09:09 |
February | 0.266601E+10 | 2454.44 | 01-FEB-09:09 | 0.403394E+10 | 2915.92 | 01-FEB-09:09 |
March | 0.304105E+10 | 2454.44 | 01-MAR-09:09 | 0.455836E+10 | 2915.92 | 01-MAR-09:09 |
April | 0.286924E+10 | 2454.44 | 01-APR-09:09 | 0.433169E+10 | 2915.92 | 01-APR-09:09 |
May | 0.298558E+10 | 2454.44 | 01-MAY-08:09 | 0.450237E+10 | 2915.92 | 01-MAY-08:09 |
June | 0.293453E+10 | 2454.44 | 01-JUN-08:09 | 0.440222E+10 | 2915.92 | 01-JUN-08:09 |
July | 0.292029E+10 | 2454.44 | 01-JUL-09:09 | 0.443184E+10 | 2915.92 | 01-JUL-09:09 |
August | 0.304105E+10 | 2454.44 | 01-AUG-08:09 | 0.455836E+10 | 2915.92 | 01-AUG-08:09 |
September | 0.286924E+10 | 2454.44 | 01-SEP-08:09 | 0.433169E+10 | 2915.92 | 01-SEP-08:09 |
October | 0.293011E+10 | 2454.44 | 02-OCT-08:09 | 0.444637E+10 | 2915.92 | 02-OCT-08:09 |
November | 0.283340E+10 | 2454.44 | 01-NOV-08:09 | 0.430476E+10 | 2915.92 | 01-NOV-08:09 |
December | 0.292029E+10 | 2454.44 | 01-DEC-09:09 | 0.443184E+10 | 2915.92 | 01-DEC-09:09 |
Annual Sum or Average | 0.349409E+11 | 0.527798E+11 | ||||
Minimum of Months | 0.266601E+10 | 2454.44 | 0.403394E+10 | 2915.92 | ||
Maximum of Months | 0.304105E+10 | 2454.44 | 0.455836E+10 | 2915.92 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.293011E+10 | 2454.44 | 02-JAN-09:09 | 0.667369E+09 | 437.66 | 02-JAN-09:09 |
February | 0.266601E+10 | 2454.44 | 01-FEB-09:09 | 0.605465E+09 | 437.66 | 01-FEB-09:09 |
March | 0.304105E+10 | 2454.44 | 01-MAR-09:09 | 0.684178E+09 | 437.66 | 01-MAR-09:09 |
April | 0.286924E+10 | 2454.44 | 01-APR-09:09 | 0.650156E+09 | 437.66 | 01-APR-09:09 |
May | 0.298558E+10 | 2454.44 | 01-MAY-08:09 | 0.675774E+09 | 437.66 | 01-MAY-08:09 |
June | 0.293453E+10 | 2454.44 | 01-JUN-08:09 | 0.660742E+09 | 437.66 | 01-JUN-08:09 |
July | 0.292029E+10 | 2454.44 | 01-JUL-09:09 | 0.665188E+09 | 437.66 | 01-JUL-09:09 |
August | 0.304105E+10 | 2454.44 | 01-AUG-08:09 | 0.684178E+09 | 437.66 | 01-AUG-08:09 |
September | 0.286924E+10 | 2454.44 | 01-SEP-08:09 | 0.650156E+09 | 437.66 | 01-SEP-08:09 |
October | 0.293011E+10 | 2454.44 | 02-OCT-08:09 | 0.667369E+09 | 437.66 | 02-OCT-08:09 |
November | 0.283340E+10 | 2454.44 | 01-NOV-08:09 | 0.646114E+09 | 437.66 | 01-NOV-08:09 |
December | 0.292029E+10 | 2454.44 | 01-DEC-09:09 | 0.665188E+09 | 437.66 | 01-DEC-09:09 |
Annual Sum or Average | 0.349409E+11 | 0.792188E+10 | ||||
Minimum of Months | 0.266601E+10 | 2454.44 | 0.605465E+09 | 437.66 | ||
Maximum of Months | 0.304105E+10 | 2454.44 | 0.684178E+09 | 437.66 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.103900E+09 | 85.79 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 94517577.03 | 85.79 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.107770E+09 | 85.79 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.101704E+09 | 85.79 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.105835E+09 | 85.79 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.103997E+09 | 85.79 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.103541E+09 | 85.79 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.107770E+09 | 85.79 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.101704E+09 | 85.79 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.103900E+09 | 85.79 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.100485E+09 | 85.79 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.103541E+09 | 85.79 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.123866E+10 | ||||
Minimum of Months | 94517577.03 | 85.79 | 0.00 | 0.00 | |
Maximum of Months | 0.107770E+09 | 85.79 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.281822E+10 | 0.420015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9099.92 | 0.164073E+09 |
February | 0.479114E+10 | 0.256399E+10 | 0.381055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3262016.53 | 0.201206E+09 |
March | 0.548013E+10 | 0.292411E+10 | 0.430594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41030605.76 | 0.158597E+09 |
April | 0.518069E+10 | 0.275920E+10 | 0.409182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155770E+09 | 17760796.35 |
May | 0.536353E+10 | 0.287117E+10 | 0.425304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287642E+09 | 17403928.36 |
June | 0.528933E+10 | 0.282172E+10 | 0.415844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219020E+09 | 5089204.28 |
July | 0.525489E+10 | 0.280865E+10 | 0.418643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248210E+09 | 5989824.15 |
August | 0.548013E+10 | 0.292411E+10 | 0.430594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146448E+09 | 9490573.92 |
September | 0.518069E+10 | 0.275920E+10 | 0.409182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96005886.34 | 10776960.11 |
October | 0.524694E+10 | 0.281822E+10 | 0.420015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47984262.05 | 15414364.52 |
November | 0.504819E+10 | 0.272540E+10 | 0.406638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11504398.12 | 47025431.42 |
December | 0.525489E+10 | 0.280865E+10 | 0.418643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 319464.70 | 0.161721E+09 |
Annual Sum or Average | 0.628175E+11 | 0.336027E+11 | 0.498571E+11 | 0.125721E+10 | 0.814548E+09 | ||||
Minimum of Months | 0.479114E+10 | 0.256399E+10 | 0.381055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9099.92 | 5089204.28 |
Maximum of Months | 0.548013E+10 | 0.292411E+10 | 0.430594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287642E+09 | 0.201206E+09 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.282436E+11 | 0.708251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159331E+09 |
February | 0.201852E+11 | 0.246941E+11 | 0.642555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2656642.91 | 0.189934E+09 |
March | 0.230879E+11 | 0.257486E+11 | 0.726089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33670981.98 | 0.145323E+09 |
April | 0.218263E+11 | 0.252876E+11 | 0.689984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127498E+09 | 15477050.86 |
May | 0.225967E+11 | 0.262260E+11 | 0.717170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239927E+09 | 9885477.60 |
June | 0.222841E+11 | 0.251820E+11 | 0.701217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185217E+09 | 3712177.81 |
July | 0.221389E+11 | 0.237579E+11 | 0.705936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216422E+09 | 2736859.07 |
August | 0.230879E+11 | 0.248194E+11 | 0.726089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125403E+09 | 4213777.50 |
September | 0.218263E+11 | 0.238928E+11 | 0.689984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78363674.37 | 6717330.15 |
October | 0.221054E+11 | 0.266138E+11 | 0.708251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39398436.30 | 13130760.24 |
November | 0.212681E+11 | 0.274834E+11 | 0.685694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9400489.35 | 43264868.30 |
December | 0.221389E+11 | 0.283919E+11 | 0.705936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89634.56 | 0.155348E+09 |
Annual Sum or Average | 0.264651E+12 | 0.310341E+12 | 0.840716E+11 | 0.105805E+10 | 0.749074E+09 | ||||
Minimum of Months | 0.201852E+11 | 0.237579E+11 | 0.642555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2736859.07 |
Maximum of Months | 0.230879E+11 | 0.283919E+11 | 0.726089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239927E+09 | 0.189934E+09 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.293011E+10 | 0.444637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88788791.19 |
February | 0.190200E+10 | 0.266601E+10 | 0.403394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1406130.91 | 0.104566E+09 |
March | 0.217552E+10 | 0.304105E+10 | 0.455836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17268775.15 | 90786259.30 |
April | 0.205665E+10 | 0.286924E+10 | 0.433169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65873592.85 | 12515645.57 |
May | 0.212923E+10 | 0.298558E+10 | 0.450237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122694E+09 | 10531953.08 |
June | 0.209978E+10 | 0.293453E+10 | 0.440222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92846441.12 | 2546273.95 |
July | 0.208610E+10 | 0.292029E+10 | 0.443184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103834E+09 | 4313998.68 |
August | 0.217552E+10 | 0.304105E+10 | 0.455836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61387130.18 | 6820236.24 |
September | 0.205665E+10 | 0.286924E+10 | 0.433169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40666300.57 | 8055310.83 |
October | 0.208295E+10 | 0.293011E+10 | 0.444637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20352164.08 | 9054160.65 |
November | 0.200405E+10 | 0.283340E+10 | 0.430476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4976911.60 | 25323644.49 |
December | 0.208610E+10 | 0.292029E+10 | 0.443184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47425.76 | 86624633.62 |
Annual Sum or Average | 0.249375E+11 | 0.349409E+11 | 0.527798E+11 | 0.531353E+09 | 0.449927E+09 | ||||
Minimum of Months | 0.190200E+10 | 0.266601E+10 | 0.403394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2546273.95 |
Maximum of Months | 0.217552E+10 | 0.304105E+10 | 0.455836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122694E+09 | 0.104566E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.293011E+10 | 0.667369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84036306.04 |
February | 0.190200E+10 | 0.266601E+10 | 0.605465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1406041.28 | 98920954.18 |
March | 0.217552E+10 | 0.304105E+10 | 0.684178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17315502.13 | 83377598.70 |
April | 0.205665E+10 | 0.286924E+10 | 0.650156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66188357.28 | 10382125.93 |
May | 0.212923E+10 | 0.298558E+10 | 0.675774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123716E+09 | 7839159.13 |
June | 0.209978E+10 | 0.293453E+10 | 0.660742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94537380.19 | 1832174.95 |
July | 0.208610E+10 | 0.292029E+10 | 0.665188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106363E+09 | 2424601.59 |
August | 0.217552E+10 | 0.304105E+10 | 0.684178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62222424.75 | 4624044.45 |
September | 0.205665E+10 | 0.286924E+10 | 0.650156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40954381.99 | 5857168.29 |
October | 0.208295E+10 | 0.293011E+10 | 0.667369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20402713.67 | 8222466.31 |
November | 0.200405E+10 | 0.283340E+10 | 0.646114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4976805.90 | 24304550.01 |
December | 0.208610E+10 | 0.292029E+10 | 0.665188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47408.47 | 82587975.12 |
Annual Sum or Average | 0.249375E+11 | 0.349409E+11 | 0.792188E+10 | 0.538130E+09 | 0.414409E+09 | ||||
Minimum of Months | 0.190200E+10 | 0.266601E+10 | 0.605465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1832174.95 |
Maximum of Months | 0.217552E+10 | 0.304105E+10 | 0.684178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123716E+09 | 98920954.18 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.103900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412862E+10 |
February | 0.00 | 94517577.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157515E+10 |
March | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12621509.29 | 0.531308E+09 |
April | 0.00 | 0.101704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378160E+09 | 59896964.84 |
May | 0.00 | 0.105835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913036E+09 | 14735153.31 |
June | 0.00 | 0.103997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841265E+09 | 16658044.19 |
July | 0.00 | 0.103541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409558E+09 | 23150460.56 |
August | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216159E+09 | 52775795.00 |
September | 0.00 | 0.101704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99506892.39 | 63273656.91 |
October | 0.00 | 0.103900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5653565.18 | 0.409898E+09 |
November | 0.00 | 0.100485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994316E+09 |
December | 0.00 | 0.103541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341618E+10 |
Annual Sum or Average | 0.00 | 0.123866E+10 | 0.287596E+10 | 0.112860E+11 | |||||
Minimum of Months | 0.00 | 94517577.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14735153.31 |
Maximum of Months | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913036E+09 | 0.412862E+10 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2344.76 | 02-JAN-09:09 | 2754.45 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 | 08-JAN-15:00 | 480.17 | 15-JAN-19:01 |
February | 5888.82 | 01-FEB-15:09 | 2344.76 | 01-FEB-09:09 | 2754.45 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.09 | 19-FEB-15:00 | 929.39 | 09-FEB-21:10 |
March | 5888.82 | 01-MAR-15:09 | 2344.76 | 01-MAR-09:09 | 2754.45 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 339.21 | 26-MAR-18:02 | 1708.77 | 24-MAR-24:00 |
April | 5888.82 | 01-APR-10:09 | 2344.76 | 01-APR-09:09 | 2754.45 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 646.48 | 02-APR-18:02 | 203.00 | 04-APR-24:00 |
May | 5888.82 | 01-MAY-14:09 | 2344.76 | 01-MAY-08:09 | 2754.45 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1113.63 | 28-MAY-18:01 | 273.88 | 15-MAY-03:00 |
June | 5888.82 | 01-JUN-14:09 | 2344.76 | 01-JUN-08:09 | 2754.45 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 918.66 | 17-JUN-21:02 | 213.38 | 18-JUN-02:00 |
July | 5888.82 | 01-JUL-10:09 | 2344.76 | 01-JUL-09:09 | 2754.45 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 695.86 | 03-JUL-04:15 | 151.58 | 19-JUL-03:00 |
August | 5888.82 | 01-AUG-14:09 | 2344.76 | 01-AUG-08:09 | 2754.45 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 430.56 | 31-AUG-04:10 | 243.82 | 15-AUG-23:30 |
September | 5888.82 | 01-SEP-14:09 | 2344.76 | 01-SEP-08:09 | 2754.45 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 265.24 | 02-SEP-21:02 | 83.71 | 08-SEP-21:30 |
October | 5888.82 | 02-OCT-14:09 | 2344.76 | 02-OCT-08:09 | 2754.45 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 255.58 | 03-OCT-15:00 | 267.96 | 12-OCT-03:00 |
November | 5888.82 | 01-NOV-14:09 | 2344.76 | 01-NOV-08:09 | 2754.45 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.04 | 13-NOV-14:00 | 354.62 | 29-NOV-24:00 |
December | 5888.82 | 01-DEC-15:09 | 2344.76 | 01-DEC-09:09 | 2754.45 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 | 24-DEC-14:00 | 740.17 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2344.76 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 | 83.71 | |||||
Maximum of Months | 5888.82 | 2344.76 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 1113.63 | 1708.77 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 26047.91 | 02-JAN-15:00 | 4644.69 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 432.08 | 15-JAN-19:10 |
February | 24809.68 | 01-FEB-15:09 | 26047.91 | 01-FEB-16:10 | 4644.69 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.45 | 19-FEB-15:00 | 851.13 | 09-FEB-21:10 |
March | 24809.68 | 01-MAR-15:09 | 26047.91 | 01-MAR-16:40 | 4644.69 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 277.70 | 26-MAR-18:02 | 1713.09 | 24-MAR-24:00 |
April | 24809.68 | 01-APR-10:09 | 26047.91 | 01-APR-16:00 | 4644.69 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 533.68 | 02-APR-18:02 | 159.86 | 04-APR-24:00 |
May | 24809.68 | 01-MAY-14:09 | 26047.91 | 03-MAY-08:09 | 4644.69 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 919.24 | 28-MAY-18:01 | 180.38 | 15-MAY-03:00 |
June | 24809.68 | 01-JUN-14:09 | 26047.91 | 15-JUN-16:00 | 4644.69 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 763.24 | 17-JUN-21:02 | 155.20 | 18-JUN-04:00 |
July | 24809.68 | 01-JUL-10:09 | 26047.91 | 10-JUL-16:49 | 4644.69 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 513.64 | 20-JUL-20:02 | 117.31 | 19-JUL-03:00 |
August | 24809.68 | 01-AUG-14:09 | 26047.91 | 10-AUG-16:49 | 4644.69 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 336.82 | 15-AUG-20:02 | 159.05 | 15-AUG-24:00 |
September | 24809.68 | 01-SEP-14:09 | 26047.91 | 02-SEP-16:00 | 4644.69 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 222.58 | 02-SEP-21:02 | 88.19 | 19-SEP-05:00 |
October | 24809.68 | 02-OCT-14:09 | 26047.91 | 02-OCT-16:30 | 4644.69 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 209.20 | 03-OCT-15:00 | 227.87 | 12-OCT-03:00 |
November | 24809.68 | 01-NOV-14:09 | 26047.91 | 01-NOV-08:09 | 4644.69 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.97 | 13-NOV-14:00 | 345.02 | 29-NOV-24:00 |
December | 24809.68 | 01-DEC-15:09 | 26047.91 | 01-DEC-15:30 | 4644.69 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 | 28-DEC-14:00 | 784.11 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 26047.91 | 4644.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.19 | |||||
Maximum of Months | 24809.68 | 26047.91 | 4644.69 | 0.00 | 0.00 | 0.00 | 0.00 | 919.24 | 1713.09 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2454.44 | 02-JAN-09:09 | 2915.92 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 229.00 | 26-JAN-21:10 |
February | 2337.76 | 01-FEB-15:09 | 2454.44 | 01-FEB-09:09 | 2915.92 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 19-FEB-15:00 | 434.01 | 09-FEB-21:10 |
March | 2337.76 | 01-MAR-15:09 | 2454.44 | 01-MAR-09:09 | 2915.92 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 135.58 | 26-MAR-18:02 | 1022.40 | 24-MAR-23:00 |
April | 2337.76 | 01-APR-10:09 | 2454.44 | 01-APR-09:09 | 2915.92 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 274.16 | 30-APR-18:01 | 132.27 | 04-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 2454.44 | 01-MAY-08:09 | 2915.92 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 479.14 | 28-MAY-18:01 | 138.58 | 15-MAY-03:00 |
June | 2337.76 | 01-JUN-14:09 | 2454.44 | 01-JUN-08:09 | 2915.92 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 395.32 | 17-JUN-21:02 | 91.44 | 18-JUN-01:40 |
July | 2337.76 | 01-JUL-10:09 | 2454.44 | 01-JUL-09:09 | 2915.92 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 301.51 | 03-JUL-04:19 | 72.00 | 19-JUL-03:00 |
August | 2337.76 | 01-AUG-14:09 | 2454.44 | 01-AUG-08:09 | 2915.92 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 186.57 | 31-AUG-04:09 | 120.82 | 15-AUG-23:00 |
September | 2337.76 | 01-SEP-14:09 | 2454.44 | 01-SEP-08:09 | 2915.92 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.35 | 02-SEP-21:02 | 48.68 | 08-SEP-21:20 |
October | 2337.76 | 02-OCT-14:09 | 2454.44 | 02-OCT-08:09 | 2915.92 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.75 | 03-OCT-15:00 | 133.73 | 12-OCT-03:00 |
November | 2337.76 | 01-NOV-14:09 | 2454.44 | 01-NOV-08:09 | 2915.92 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.75 | 13-NOV-14:00 | 223.24 | 29-NOV-24:00 |
December | 2337.76 | 01-DEC-15:09 | 2454.44 | 01-DEC-09:09 | 2915.92 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 | 28-DEC-14:00 | 382.39 | 29-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2454.44 | 2915.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.68 | |||||
Maximum of Months | 2337.76 | 2454.44 | 2915.92 | 0.00 | 0.00 | 0.00 | 0.00 | 479.14 | 1022.40 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2454.44 | 02-JAN-09:09 | 437.66 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 223.07 | 26-JAN-21:10 |
February | 2337.76 | 01-FEB-15:09 | 2454.44 | 01-FEB-09:09 | 437.66 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 19-FEB-15:00 | 382.06 | 09-FEB-21:10 |
March | 2337.76 | 01-MAR-15:09 | 2454.44 | 01-MAR-09:09 | 437.66 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 137.16 | 26-MAR-18:02 | 928.27 | 24-MAR-23:00 |
April | 2337.76 | 01-APR-10:09 | 2454.44 | 01-APR-09:09 | 437.66 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 275.24 | 02-APR-18:02 | 111.59 | 04-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 2454.44 | 01-MAY-08:09 | 437.66 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 480.03 | 28-MAY-18:01 | 114.85 | 15-MAY-03:00 |
June | 2337.76 | 01-JUN-14:09 | 2454.44 | 01-JUN-08:09 | 437.66 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 397.02 | 17-JUN-21:02 | 76.12 | 18-JUN-02:00 |
July | 2337.76 | 01-JUL-10:09 | 2454.44 | 01-JUL-09:09 | 437.66 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 301.33 | 03-JUL-04:28 | 59.85 | 19-JUL-03:00 |
August | 2337.76 | 01-AUG-14:09 | 2454.44 | 01-AUG-08:09 | 437.66 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 186.57 | 31-AUG-04:09 | 108.78 | 15-AUG-23:00 |
September | 2337.76 | 01-SEP-14:09 | 2454.44 | 01-SEP-08:09 | 437.66 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.34 | 02-SEP-21:02 | 36.73 | 19-SEP-04:00 |
October | 2337.76 | 02-OCT-14:09 | 2454.44 | 02-OCT-08:09 | 437.66 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.75 | 03-OCT-15:00 | 119.13 | 12-OCT-03:00 |
November | 2337.76 | 01-NOV-14:09 | 2454.44 | 01-NOV-08:09 | 437.66 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.75 | 13-NOV-14:00 | 208.25 | 29-NOV-24:00 |
December | 2337.76 | 01-DEC-15:09 | 2454.44 | 01-DEC-09:09 | 437.66 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 | 28-DEC-14:00 | 350.63 | 29-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2454.44 | 437.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.73 | |||||
Maximum of Months | 2337.76 | 2454.44 | 437.66 | 0.00 | 0.00 | 0.00 | 0.00 | 480.03 | 928.27 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 85.79 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13888.78 | 01-JAN-18:00 |
February | 0.00 | 01-FEB-00:10 | 85.79 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 11356.27 | 10-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 85.79 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.49 | 30-MAR-14:00 | 2174.69 | 01-MAR-12:02 |
April | 0.00 | 01-APR-00:10 | 85.79 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2194.44 | 16-APR-11:02 | 1248.85 | 05-APR-07:01 |
May | 0.00 | 01-MAY-00:10 | 85.79 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4190.41 | 03-MAY-11:01 | 755.11 | 31-MAY-16:53 |
June | 0.00 | 01-JUN-00:10 | 85.79 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4335.51 | 04-JUN-11:01 | 1266.97 | 27-JUN-11:02 |
July | 0.00 | 01-JUL-00:10 | 85.79 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2437.36 | 01-JUL-11:02 | 909.34 | 18-JUL-11:03 |
August | 0.00 | 01-AUG-00:10 | 85.79 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.97 | 05-AUG-11:02 | 742.58 | 16-AUG-07:02 |
September | 0.00 | 01-SEP-00:10 | 85.79 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1291.58 | 11-SEP-11:02 | 1055.01 | 29-SEP-15:55 |
October | 0.00 | 01-OCT-00:10 | 85.79 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.83 | 02-OCT-11:05 | 1932.65 | 30-OCT-07:01 |
November | 0.00 | 01-NOV-00:10 | 85.79 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3422.35 | 30-NOV-18:00 |
December | 0.00 | 01-DEC-00:10 | 85.79 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 15577.35 | 21-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 85.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 742.58 | ||||
Maximum of Months | 0.00 | 85.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4335.51 | 15577.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3720.80 | 14-JAN-17:00 | 5888.82 | 2344.76 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.72 |
February | 8031.15 | 24-FEB-16:00 | 5888.82 | 2344.76 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 0.00 |
March | 54477.15 | 29-MAR-04:01 | 0.00 | 1437.32 | 6081.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 59018.33 | 29-APR-04:01 | 0.00 | 1437.32 | 4561.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 59266.57 | 09-MAY-04:01 | 0.00 | 1437.32 | 6081.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 57151.47 | 05-JUN-04:01 | 0.00 | 1437.32 | 6081.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 51694.86 | 07-JUL-04:01 | 0.00 | 1437.32 | 6081.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 52409.73 | 09-AUG-04:01 | 0.00 | 1437.32 | 6081.76 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 0.00 |
September | 53729.28 | 27-SEP-04:01 | 0.00 | 1437.32 | 6081.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 56151.78 | 02-OCT-04:01 | 0.00 | 1437.32 | 6081.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36381.96 | 01-NOV-04:01 | 0.00 | 1149.86 | 4865.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.43 |
December | 4256.45 | 01-DEC-16:00 | 5888.82 | 2344.76 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3720.80 | 0.00 | 1149.86 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 59266.57 | 5888.82 | 2344.76 | 6081.76 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 52.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32829.13 | 05-JAN-07:05 | 12404.84 | 23153.70 | 8257.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41078.03 | 23-FEB-16:00 | 24809.68 | 23877.25 | 4644.69 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 | 0.00 |
March | 163498.37 | 30-MAR-06:02 | 15506.05 | 28942.12 | 10321.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 |
April | 198041.55 | 28-APR-05:01 | 0.00 | 11576.85 | 8204.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 |
May | 194934.38 | 06-MAY-04:01 | 0.00 | 14471.06 | 7691.53 | 0.00 | 0.00 | 0.00 | 0.00 | 44.38 | 0.00 |
June | 179339.69 | 07-JUN-04:01 | 0.00 | 14471.06 | 10255.37 | 0.00 | 0.00 | 0.00 | 0.00 | 130.57 | 0.00 |
July | 162364.87 | 05-JUL-04:01 | 0.00 | 14471.06 | 10255.37 | 0.00 | 0.00 | 0.00 | 0.00 | 102.86 | 0.00 |
August | 148705.31 | 07-AUG-04:01 | 0.00 | 14471.06 | 10255.37 | 0.00 | 0.00 | 0.00 | 0.00 | 26.65 | 0.00 |
September | 157310.58 | 27-SEP-05:02 | 0.00 | 7235.53 | 5127.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 |
October | 166957.94 | 16-OCT-06:03 | 12404.84 | 23153.70 | 8257.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 |
November | 49161.43 | 09-NOV-15:10 | 24809.68 | 23877.25 | 4644.69 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 | 0.00 |
December | 33160.24 | 01-DEC-15:40 | 24809.68 | 26047.91 | 4644.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 |
Annual Sum or Average | |||||||||||
Minimum of Months | 32829.13 | 0.00 | 7235.53 | 4644.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 198041.55 | 24809.68 | 28942.12 | 10321.53 | 0.00 | 0.00 | 0.00 | 0.00 | 130.57 | 12.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9371.60 | 12-JAN-15:20 | 2337.76 | 2454.44 | 2915.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 |
February | 25799.85 | 23-FEB-05:02 | 0.00 | 681.79 | 3219.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.63 |
March | 32961.60 | 29-MAR-04:01 | 0.00 | 1363.58 | 6438.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33457.42 | 07-APR-04:01 | 0.00 | 1363.58 | 6438.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.64 |
May | 32453.48 | 28-MAY-06:01 | 0.00 | 1363.58 | 4828.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 |
June | 30876.61 | 05-JUN-04:11 | 0.00 | 1363.58 | 6438.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 27683.87 | 07-JUL-04:11 | 0.00 | 1363.58 | 6438.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27240.94 | 04-AUG-04:01 | 0.00 | 1363.58 | 6438.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 |
September | 31033.50 | 27-SEP-04:01 | 0.00 | 1363.58 | 6438.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33487.06 | 23-OCT-04:01 | 0.00 | 1363.58 | 6438.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.94 |
November | 31839.00 | 02-NOV-04:01 | 0.00 | 1090.86 | 5150.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.15 |
December | 10859.96 | 01-DEC-15:10 | 2337.76 | 2454.44 | 2915.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9371.60 | 0.00 | 681.79 | 2915.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33487.06 | 2337.76 | 2454.44 | 6438.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7457.55 | 12-JAN-15:10 | 2337.76 | 2454.44 | 437.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
February | 16628.81 | 23-FEB-05:02 | 0.00 | 681.79 | 483.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 |
March | 29008.58 | 29-MAR-04:01 | 0.00 | 1363.58 | 966.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30115.02 | 29-APR-04:01 | 0.00 | 1363.58 | 724.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29410.32 | 29-MAY-06:01 | 0.00 | 1363.58 | 724.76 | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 0.00 |
June | 27919.30 | 05-JUN-04:01 | 0.00 | 1363.58 | 966.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24445.39 | 07-JUL-04:01 | 0.00 | 1363.58 | 966.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24263.66 | 09-AUG-04:11 | 0.00 | 1363.58 | 966.34 | 0.00 | 0.00 | 0.00 | 0.00 | 10.01 | 0.00 |
September | 27367.02 | 27-SEP-04:01 | 0.00 | 1363.58 | 966.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29730.79 | 23-OCT-04:01 | 0.00 | 1363.58 | 966.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.47 |
November | 28249.54 | 02-NOV-04:01 | 0.00 | 1090.86 | 773.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.93 |
December | 9051.24 | 01-DEC-15:10 | 2337.76 | 2454.44 | 437.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7457.55 | 0.00 | 681.79 | 437.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30115.02 | 2337.76 | 2454.44 | 966.34 | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 39.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 638.67 | 01-JAN-07:02 | 0.00 | 58.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 0.00 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 638.67 | 0.00 | 58.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 5.52 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.803593E+11 | 71852.11 | 14-JAN-17:49 | 0.216227E+11 | 131299.59 | 01-JAN-08:09 |
February | 0.794935E+11 | 80892.85 | 24-FEB-16:40 | 0.914654E+10 | 69491.44 | 02-FEB-07:10 |
March | 0.107117E+12 | 100131.03 | 28-MAR-15:39 | 0.752669E+10 | 4891.93 | 01-MAR-12:30 |
April | 0.131909E+12 | 122991.66 | 28-APR-15:30 | 0.703134E+10 | 4839.69 | 03-APR-11:50 |
May | 0.165346E+12 | 140260.28 | 30-MAY-15:00 | 0.704863E+10 | 4788.57 | 01-MAY-11:30 |
June | 0.169890E+12 | 154232.37 | 10-JUN-15:00 | 0.668018E+10 | 4741.42 | 01-JUN-11:09 |
July | 0.167616E+12 | 144894.77 | 01-JUL-16:49 | 0.679237E+10 | 4713.11 | 03-JUL-11:20 |
August | 0.163738E+12 | 133368.31 | 07-AUG-14:00 | 0.688864E+10 | 4735.53 | 31-AUG-11:30 |
September | 0.142551E+12 | 123472.47 | 14-SEP-16:00 | 0.679196E+10 | 4777.85 | 29-SEP-11:09 |
October | 0.124298E+12 | 113053.64 | 02-OCT-14:00 | 0.720917E+10 | 4834.75 | 31-OCT-11:50 |
November | 0.981569E+11 | 89512.81 | 08-NOV-15:50 | 0.720581E+10 | 6033.11 | 27-NOV-07:19 |
December | 0.830243E+11 | 73751.04 | 01-DEC-17:30 | 0.127030E+11 | 85870.36 | 23-DEC-07:10 |
Annual Sum or Average | 0.151350E+13 | 0.106647E+12 | ||||
Minimum of Months | 0.794935E+11 | 71852.11 | 0.668018E+10 | 4713.11 | ||
Maximum of Months | 0.169890E+12 | 154232.37 | 0.216227E+11 | 131299.59 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.370259E+11 | 0.593541E+10 | 0.163964E+11 | 0.00 | 0.163784E+11 | 0.00 | 0.00 | 0.462312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326846E+11 | 0.509539E+10 | 0.148755E+11 | 0.00 | 0.136388E+11 | 0.00 | 0.00 | 0.131992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348626E+11 | 0.521089E+10 | 0.168094E+11 | 0.00 | 0.147041E+11 | 0.00 | 0.00 | 0.355302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.338870E+11 | 0.462158E+10 | 0.159735E+11 | 0.00 | 0.147867E+11 | 0.00 | 0.00 | 0.626402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.351741E+11 | 0.440557E+10 | 0.166029E+11 | 0.00 | 0.178732E+11 | 0.00 | 0.00 | 0.912906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.339767E+11 | 0.406426E+10 | 0.162336E+11 | 0.00 | 0.188651E+11 | 0.00 | 0.00 | 0.967504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.325107E+11 | 0.430804E+10 | 0.163428E+11 | 0.00 | 0.188751E+11 | 0.00 | 0.00 | 0.955791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.339334E+11 | 0.460621E+10 | 0.168094E+11 | 0.00 | 0.181971E+11 | 0.00 | 0.00 | 0.901920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.324922E+11 | 0.486122E+10 | 0.159735E+11 | 0.00 | 0.155808E+11 | 0.00 | 0.00 | 0.736432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.353961E+11 | 0.546169E+10 | 0.163964E+11 | 0.00 | 0.146509E+11 | 0.00 | 0.00 | 0.523931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.359761E+11 | 0.564983E+10 | 0.158742E+11 | 0.00 | 0.139118E+11 | 0.00 | 0.00 | 0.267449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.371447E+11 | 0.606637E+10 | 0.163428E+11 | 0.00 | 0.157252E+11 | 0.00 | 0.00 | 0.774526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.415064E+12 | 0.602865E+11 | 0.194630E+12 | 0.193187E+12 | 0.00 | 0.650331E+12 | |||||||
Minimum of Months | 0.324922E+11 | 0.406426E+10 | 0.148755E+11 | 0.00 | 0.136388E+11 | 0.00 | 0.00 | 0.462312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.371447E+11 | 0.606637E+10 | 0.168094E+11 | 0.00 | 0.188751E+11 | 0.00 | 0.00 | 0.967504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.139368E+11 | 0.00 | 0.768591E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.224712E+10 | 0.00 | 0.689942E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.752669E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.703134E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.704863E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.668018E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.679237E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.688864E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.679196E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.720917E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 20309371.86 | 0.00 | 0.718550E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.508594E+10 | 0.00 | 0.761704E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.212902E+11 | 0.853568E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.668018E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.139368E+11 | 0.00 | 0.768591E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 33387.34 | 02-JAN-15:00 | 4644.30 | 01-JAN-06:10 | 10752.72 | 02-JAN-09:09 | 0.00 | 14064.52 | 01-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 33387.34 | 01-FEB-16:10 | 4644.30 | 01-FEB-06:10 | 10752.72 | 01-FEB-09:09 | 0.00 | 11711.01 | 11-FEB-07:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 33387.34 | 01-MAR-16:40 | 4644.30 | 01-MAR-06:10 | 10752.72 | 01-MAR-09:09 | 0.00 | 11277.32 | 13-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 33387.34 | 01-APR-16:00 | 4644.30 | 01-APR-05:10 | 10752.72 | 01-APR-09:09 | 0.00 | 12850.57 | 28-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 33387.34 | 03-MAY-08:09 | 4644.30 | 01-MAY-05:10 | 10752.72 | 01-MAY-08:09 | 0.00 | 15880.23 | 30-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 33387.34 | 15-JUN-16:00 | 4644.30 | 01-JUN-05:10 | 10752.72 | 01-JUN-08:09 | 0.00 | 17701.60 | 10-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 33387.34 | 10-JUL-16:49 | 4644.30 | 01-JUL-05:10 | 10752.72 | 01-JUL-09:09 | 0.00 | 17634.17 | 01-JUL-15:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 33387.34 | 10-AUG-16:49 | 4644.30 | 01-AUG-05:10 | 10752.72 | 01-AUG-08:09 | 0.00 | 15617.05 | 07-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 33387.34 | 02-SEP-16:00 | 4644.30 | 01-SEP-05:10 | 10752.72 | 01-SEP-08:09 | 0.00 | 13582.30 | 14-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 33387.34 | 02-OCT-16:30 | 4644.30 | 01-OCT-05:10 | 10752.72 | 02-OCT-08:09 | 0.00 | 12533.98 | 04-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 33387.34 | 01-NOV-08:09 | 4644.30 | 01-NOV-05:10 | 10752.72 | 01-NOV-08:09 | 0.00 | 10517.57 | 26-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 33387.34 | 01-DEC-15:30 | 4644.30 | 01-DEC-06:10 | 10752.72 | 01-DEC-09:09 | 0.00 | 12373.84 | 31-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 33387.34 | 4644.30 | 10752.72 | 0.00 | 10517.57 | 0.00 | 0.00 | |||||
Maximum of Months | 33387.34 | 4644.30 | 10752.72 | 0.00 | 17701.60 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 16576.73 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28961.42 | 24-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 48855.47 | 28-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 69463.47 | 28-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84031.98 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 94561.38 | 10-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88484.69 | 01-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80123.18 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 69005.63 | 14-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 60789.68 | 03-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37033.11 | 09-NOV-13:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19585.30 | 28-DEC-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 16576.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94561.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 71852.11 | 14-JAN-17:49 | 33387.34 | 10752.72 | 4644.30 | 0.00 | 10473.58 | 0.00 | 0.00 | 12594.18 | 0.00 |
February | 80892.85 | 24-FEB-16:40 | 33387.34 | 10752.72 | 0.00 | 0.00 | 8931.09 | 0.00 | 0.00 | 27821.72 | 0.00 |
March | 100131.03 | 28-MAR-15:39 | 31216.68 | 10752.72 | 0.00 | 0.00 | 9306.48 | 0.00 | 0.00 | 48855.16 | 0.00 |
April | 122991.66 | 28-APR-15:30 | 31216.68 | 10752.72 | 0.00 | 0.00 | 12587.66 | 0.00 | 0.00 | 68434.60 | 0.00 |
May | 140260.28 | 30-MAY-15:00 | 31216.68 | 10752.72 | 0.00 | 0.00 | 15544.79 | 0.00 | 0.00 | 82746.10 | 0.00 |
June | 154232.37 | 10-JUN-15:00 | 31216.68 | 10752.72 | 0.00 | 0.00 | 17701.60 | 0.00 | 0.00 | 94561.38 | 0.00 |
July | 144894.77 | 01-JUL-16:49 | 31216.68 | 10752.72 | 0.00 | 0.00 | 17040.42 | 0.00 | 0.00 | 85884.96 | 0.00 |
August | 133368.31 | 07-AUG-14:00 | 26875.36 | 10752.72 | 0.00 | 0.00 | 15617.05 | 0.00 | 0.00 | 80123.18 | 0.00 |
September | 123472.47 | 14-SEP-16:00 | 33387.34 | 10752.72 | 0.00 | 0.00 | 12948.09 | 0.00 | 0.00 | 66384.32 | 0.00 |
October | 113053.64 | 02-OCT-14:00 | 31216.68 | 10752.72 | 0.00 | 0.00 | 10999.04 | 0.00 | 0.00 | 60085.20 | 0.00 |
November | 89512.81 | 08-NOV-15:50 | 33387.34 | 10752.72 | 0.00 | 0.00 | 8971.78 | 0.00 | 0.00 | 36400.98 | 0.00 |
December | 73751.04 | 01-DEC-17:30 | 33387.34 | 10752.72 | 4644.30 | 0.00 | 10473.58 | 0.00 | 0.00 | 14493.10 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 71852.11 | 26875.36 | 10752.72 | 0.00 | 0.00 | 8931.09 | 0.00 | 0.00 | 12594.18 | 0.00 | |
Maximum of Months | 154232.37 | 33387.34 | 10752.72 | 4644.30 | 0.00 | 17701.60 | 0.00 | 0.00 | 94561.38 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 129439.59 | 01-JAN-08:09 | 0.00 | 4923.56 | 23-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 67631.44 | 02-FEB-07:10 | 0.00 | 4918.64 | 01-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 4891.93 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 4839.69 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4788.57 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4741.42 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4713.11 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4735.53 | 31-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4777.85 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 4834.75 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 2501.90 | 27-NOV-06:00 | 0.00 | 4884.10 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 84010.36 | 23-DEC-07:10 | 0.00 | 4914.70 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4713.11 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 129439.59 | 0.00 | 4923.56 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 24.82 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 25.56 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 25.68 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 25.71 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 25.18 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 24.86 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.67 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.33 | 20.40 | 0.00 | 59.67 | 25.35 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 20.44 | 0.00 | 0.00 | 11.50 | 25.71 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.51 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.72 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 26.36 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 26.85 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.59 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.32 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.31 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 25.74 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 25.42 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.56 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.26 | 0.00 | 96.83 | 26.64 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.26 | 0.00 | 0.00 | 19.17 | 27.59 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.75 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 25.36 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 25.77 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 25.76 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 25.92 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 25.53 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 25.13 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.82 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.46 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.23 | 0.00 | 67.33 | 25.53 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.45 | 0.00 | 0.00 | 12.67 | 25.92 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 22.23 | 59.00 | 21.25 | 59.00 | 21.25 |
February | 310.17 | 23.08 | 7.67 | 23.22 | 1.83 | 21.11 |
March | 83.33 | 23.61 | 163.50 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 367.83 | 23.89 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 418.00 | 23.89 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 408.00 | 23.89 | 0.00 | 0.00 |
July | 0.50 | 23.89 | 415.00 | 23.89 | 0.50 | 23.89 |
August | 0.00 | 0.00 | 422.00 | 23.89 | 0.00 | 0.00 |
September | 8.17 | 23.89 | 405.00 | 23.89 | 8.17 | 23.89 |
October | 4.00 | 23.88 | 358.67 | 23.89 | 0.00 | 0.00 |
November | 163.17 | 23.48 | 41.00 | 23.89 | 0.00 | 0.00 |
December | 415.00 | 22.74 | 21.17 | 21.11 | 21.17 | 21.11 |
Annual Sum or Average | 1398.33 | 22.81 | 3086.83 | 23.82 | 90.67 | 21.47 |
Minimum of Months | 0.00 | 0.00 | 7.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 415.00 | 23.89 | 422.00 | 23.89 | 59.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 349.00 | 22.70 | 7.00 | 21.16 | 7.00 | 21.16 |
February | 128.33 | 22.78 | 72.17 | 23.89 | 0.00 | 0.00 |
March | 18.83 | 23.30 | 298.83 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 397.00 | 23.89 | 0.00 | 0.00 |
May | 1.83 | 23.96 | 418.00 | 23.89 | 1.83 | 23.96 |
June | 18.33 | 23.92 | 408.00 | 23.89 | 18.33 | 23.92 |
July | 43.17 | 23.92 | 415.00 | 23.89 | 43.17 | 23.92 |
August | 65.67 | 23.91 | 422.00 | 23.89 | 65.67 | 23.91 |
September | 87.67 | 23.90 | 405.00 | 23.89 | 87.67 | 23.90 |
October | 4.83 | 23.89 | 402.00 | 23.89 | 4.83 | 23.89 |
November | 44.50 | 23.01 | 217.83 | 23.89 | 0.00 | 0.00 |
December | 254.17 | 22.81 | 1.50 | 22.73 | 0.67 | 21.32 |
Annual Sum or Average | 1016.33 | 23.03 | 3464.33 | 23.89 | 229.17 | 23.82 |
Minimum of Months | 0.00 | 0.00 | 1.50 | 21.16 | 0.00 | 0.00 |
Maximum of Months | 349.00 | 23.96 | 422.00 | 23.89 | 87.67 | 23.96 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 164.67 | 22.60 | 96.83 | 23.79 | 3.50 | 21.11 |
February | 76.83 | 22.78 | 209.83 | 23.89 | 0.00 | 0.00 |
March | 16.00 | 23.69 | 361.00 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 397.33 | 23.89 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 418.00 | 23.89 | 0.00 | 0.00 |
June | 1.67 | 23.89 | 408.00 | 23.89 | 1.67 | 23.89 |
July | 1.50 | 23.89 | 415.00 | 23.89 | 1.50 | 23.89 |
August | 1.17 | 23.89 | 422.00 | 23.89 | 1.17 | 23.89 |
September | 11.67 | 23.89 | 405.00 | 23.89 | 11.67 | 23.89 |
October | 0.00 | 0.00 | 408.50 | 23.89 | 0.00 | 0.00 |
November | 12.50 | 23.32 | 347.67 | 23.89 | 0.00 | 0.00 |
December | 107.50 | 22.80 | 165.67 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 393.50 | 22.81 | 4054.83 | 23.89 | 19.50 | 23.39 |
Minimum of Months | 0.00 | 0.00 | 96.83 | 23.79 | 0.00 | 0.00 |
Maximum of Months | 164.67 | 23.89 | 422.00 | 23.89 | 11.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 205.67 | 22.30 | 61.00 | 23.65 | 5.33 | 21.11 |
February | 96.83 | 22.38 | 186.50 | 23.89 | 0.17 | 21.11 |
March | 29.00 | 23.35 | 344.67 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 391.33 | 23.89 | 0.00 | 0.00 |
May | 0.67 | 23.89 | 418.00 | 23.89 | 0.67 | 23.89 |
June | 7.17 | 23.89 | 408.00 | 23.89 | 7.17 | 23.89 |
July | 6.17 | 23.89 | 415.00 | 23.89 | 6.17 | 23.89 |
August | 3.00 | 23.89 | 422.00 | 23.89 | 3.00 | 23.89 |
September | 45.17 | 23.89 | 405.00 | 23.89 | 45.17 | 23.89 |
October | 0.00 | 0.00 | 405.33 | 23.89 | 0.00 | 0.00 |
November | 21.67 | 23.03 | 337.83 | 23.89 | 0.00 | 0.00 |
December | 136.17 | 22.50 | 127.00 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 551.50 | 22.63 | 3921.67 | 23.89 | 67.67 | 23.66 |
Minimum of Months | 0.00 | 0.00 | 61.00 | 23.65 | 0.00 | 0.00 |
Maximum of Months | 205.67 | 23.89 | 422.00 | 23.89 | 45.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.22054 | 49.52381 | -0.2004 | 7.25624 |
February | 376.00000 | 23.20307 | 48.13999 | 0.10036 | 6.56770 |
March | 422.00000 | 23.82898 | 43.64691 | 0.37316 | 8.21275 |
April | 405.00000 | 23.88977 | 41.47619 | 0.54568 | 11.39457 |
May | 418.00000 | 23.88967 | 45.22611 | -0.1195 | 5.48409 |
June | 408.00000 | 23.88953 | 48.00718 | -0.0902 | 5.43082 |
July | 415.00000 | 23.88949 | 50.56024 | -0.0971 | 5.35856 |
August | 422.00000 | 23.88959 | 51.33857 | -0.1300 | 5.43929 |
September | 405.00000 | 23.88968 | 51.62318 | -0.2076 | 6.00118 |
October | 414.00000 | 23.88971 | 45.28742 | 0.49634 | 10.25857 |
November | 399.00000 | 23.70731 | 45.26637 | 0.29134 | 7.27160 |
December | 415.00000 | 22.72168 | 47.66889 | -0.0635 | 6.62699 |
Annual Sum or Average | 4913.00000 | 23.57777 | 47.31517 | 0.07380 | 7.10574 |
Minimum of Months | 376.00000 | 22.22054 | 41.47619 | -0.2076 | 5.35856 |
Maximum of Months | 422.00000 | 23.88977 | 51.62318 | 0.54568 | 11.39457 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.85905 | 43.31512 | 0.04422 | 6.57864 |
February | 376.00000 | 23.48514 | 43.23044 | 0.27162 | 7.43157 |
March | 422.00000 | 23.86290 | 41.71360 | 0.45617 | 9.52980 |
April | 405.00000 | 23.91081 | 41.32152 | 0.58009 | 12.18020 |
May | 418.00000 | 23.91333 | 47.92604 | -0.1146 | 5.42280 |
June | 408.00000 | 23.91397 | 52.68695 | -0.0890 | 5.32835 |
July | 415.00000 | 23.91529 | 57.74688 | -0.0980 | 5.31803 |
August | 422.00000 | 23.91466 | 59.11642 | -0.1174 | 5.36278 |
September | 405.00000 | 23.91418 | 57.73799 | -0.1660 | 5.65880 |
October | 414.00000 | 23.90385 | 46.51385 | 0.55219 | 11.47032 |
November | 399.00000 | 23.77911 | 42.20215 | 0.39897 | 8.61635 |
December | 415.00000 | 23.20306 | 41.39169 | 0.15109 | 6.67113 |
Annual Sum or Average | 4913.00000 | 23.71589 | 47.95924 | 0.15401 | 7.45576 |
Minimum of Months | 376.00000 | 22.85905 | 41.32152 | -0.1660 | 5.31803 |
Maximum of Months | 422.00000 | 23.91529 | 59.11642 | 0.58009 | 12.18020 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.35007 | 39.72214 | 0.21982 | 7.74248 |
February | 376.00000 | 23.64402 | 40.00881 | 0.38002 | 9.13074 |
March | 422.00000 | 23.88043 | 39.18747 | 0.55082 | 11.71393 |
April | 405.00000 | 23.88975 | 39.77309 | 0.67575 | 14.88259 |
May | 418.00000 | 23.88974 | 45.19227 | 0.00231 | 5.31631 |
June | 408.00000 | 23.88956 | 48.73546 | 0.01750 | 5.35677 |
July | 415.00000 | 23.88951 | 51.70711 | 0.01392 | 5.22914 |
August | 422.00000 | 23.88954 | 52.18394 | -0.0025 | 5.18553 |
September | 405.00000 | 23.88957 | 50.85662 | -0.0340 | 5.40516 |
October | 414.00000 | 23.88991 | 41.57652 | 0.69423 | 15.40236 |
November | 399.00000 | 23.86829 | 37.88142 | 0.57028 | 12.20537 |
December | 415.00000 | 23.58133 | 37.24000 | 0.31814 | 8.30990 |
Annual Sum or Average | 4913.00000 | 23.79682 | 43.71400 | 0.28212 | 8.80514 |
Minimum of Months | 376.00000 | 23.35007 | 37.24000 | -0.0340 | 5.18553 |
Maximum of Months | 422.00000 | 23.88991 | 52.18394 | 0.69423 | 15.40236 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.07780 | 41.54923 | 0.14653 | 7.50689 |
February | 376.00000 | 23.47772 | 41.67047 | 0.32973 | 8.76215 |
March | 422.00000 | 23.84781 | 40.18111 | 0.52491 | 11.21607 |
April | 405.00000 | 23.88969 | 40.14304 | 0.65578 | 14.33140 |
May | 418.00000 | 23.88965 | 45.87326 | -0.0235 | 5.34228 |
June | 408.00000 | 23.88952 | 49.84621 | -0.0111 | 5.34725 |
July | 415.00000 | 23.88946 | 53.19854 | -0.0113 | 5.22812 |
August | 422.00000 | 23.88950 | 53.85929 | -0.0277 | 5.19506 |
September | 405.00000 | 23.88951 | 52.70463 | -0.0588 | 5.43315 |
October | 414.00000 | 23.88981 | 42.40479 | 0.67540 | 14.85666 |
November | 399.00000 | 23.83548 | 38.73771 | 0.54215 | 11.63902 |
December | 415.00000 | 23.40783 | 38.79853 | 0.26383 | 7.99364 |
Annual Sum or Average | 4913.00000 | 23.74099 | 44.95437 | 0.24885 | 8.55464 |
Minimum of Months | 376.00000 | 23.07780 | 38.73771 | -0.0588 | 5.19506 |
Maximum of Months | 422.00000 | 23.88981 | 53.85929 | 0.67540 | 14.85666 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.291113E+09 | 81695480.82 | 33.33 | 0.221832E+09 | 69280922.95 | 0.00 | 0.23 | 14-JAN-16:00 | 0.00 | 01-JAN-00:10 | 5855.35 | 14-JAN-16:00 | 4280.30 | 14-JAN-16:10 | 1576.66 | 14-JAN-16:00 | 1596.82 | 14-JAN-16:00 | 0.00 | 01-JAN-00:10 |
February | 0.364045E+10 | 0.101742E+10 | 203.75 | 0.293677E+10 | 0.703684E+09 | 0.00 | 0.47 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 | 12577.30 | 24-FEB-16:00 | 10101.22 | 24-FEB-16:00 | 3544.46 | 25-FEB-17:00 | 3471.97 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.159060E+11 | 0.444692E+10 | 404.79 | 0.134685E+11 | 0.243758E+10 | 0.00 | 1.00 | 11-MAR-05:01 | 0.00 | 01-MAR-00:10 | 66083.22 | 11-MAR-05:01 | 58745.89 | 29-MAR-04:01 | 15036.02 | 11-MAR-05:02 | 14709.23 | 11-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.327546E+11 | 0.936795E+10 | 455.15 | 0.295579E+11 | 0.319666E+10 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 66288.82 | 17-APR-04:01 | 64229.13 | 29-APR-04:01 | 12405.06 | 17-APR-04:05 | 15587.30 | 27-APR-04:01 | 0.00 | 01-APR-00:10 |
May | 0.502208E+11 | 0.145232E+11 | 493.67 | 0.431625E+11 | 0.705831E+10 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 69801.36 | 24-MAY-04:01 | 64630.91 | 09-MAY-04:01 | 25989.61 | 24-MAY-04:05 | 16433.82 | 04-MAY-04:01 | 0.00 | 01-MAY-00:10 |
June | 0.539815E+11 | 0.154177E+11 | 495.02 | 0.436582E+11 | 0.103233E+11 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 71785.24 | 26-JUN-04:01 | 63202.81 | 05-JUN-04:01 | 33420.41 | 26-JUN-04:07 | 16739.74 | 12-JUN-04:01 | 0.00 | 01-JUN-00:10 |
July | 0.570695E+11 | 0.151392E+11 | 496.95 | 0.416655E+11 | 0.154040E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:05 | 72041.76 | 20-JUL-04:01 | 57855.30 | 07-JUL-04:01 | 33849.84 | 20-JUL-04:07 | 16746.88 | 02-JUL-06:01 | 0.00 | 01-JUL-00:05 |
August | 0.538344E+11 | 0.138132E+11 | 478.93 | 0.379399E+11 | 0.158945E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 70333.36 | 19-AUG-04:01 | 58138.74 | 09-AUG-04:01 | 27888.35 | 11-AUG-04:05 | 16107.72 | 08-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.420519E+11 | 0.109356E+11 | 457.44 | 0.301767E+11 | 0.118752E+11 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 71016.65 | 03-SEP-06:01 | 58249.56 | 27-SEP-04:01 | 32392.77 | 10-SEP-06:03 | 15463.28 | 02-SEP-04:01 | 0.00 | 01-SEP-00:10 |
October | 0.264973E+11 | 0.726892E+10 | 459.28 | 0.217434E+11 | 0.475383E+10 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 67705.92 | 12-OCT-04:01 | 60377.87 | 02-OCT-04:01 | 22101.69 | 12-OCT-04:03 | 14857.52 | 04-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.969207E+10 | 0.272379E+10 | 337.72 | 0.801231E+10 | 0.167976E+10 | 0.00 | 0.60 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 | 47066.55 | 01-NOV-04:01 | 37935.77 | 01-NOV-04:01 | 9130.78 | 01-NOV-04:01 | 10193.84 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 |
December | 0.916842E+09 | 0.259134E+09 | 103.33 | 0.719138E+09 | 0.197704E+09 | 0.00 | 0.24 | 28-DEC-16:00 | 0.00 | 01-DEC-00:10 | 6153.99 | 28-DEC-16:00 | 5310.14 | 01-DEC-15:10 | 1534.88 | 16-DEC-16:00 | 1736.65 | 28-DEC-15:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.346856E+12 | 0.949946E+11 | 4419.38 | 0.273263E+12 | 0.735938E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.291113E+09 | 81695480.82 | 33.33 | 0.221832E+09 | 69280922.95 | 0.00 | 0.23 | 0.00 | 5855.35 | 4280.30 | 1534.88 | 1596.82 | 0.00 | |||||||
Maximum of Months | 0.570695E+11 | 0.154177E+11 | 496.95 | 0.436582E+11 | 0.158945E+11 | 0.00 | 1.00 | 0.00 | 72041.76 | 64630.91 | 33849.84 | 16746.88 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.804027E+10 | 0.249921E+10 | 158.92 | 0.657848E+10 | 0.146179E+10 | 0.00 | 0.39 | 14-JAN-15:20 | 0.00 | 01-JAN-00:10 | 37044.58 | 14-JAN-15:20 | 29499.17 | 12-JAN-15:10 | 9299.32 | 14-JAN-15:20 | 10998.66 | 14-JAN-15:20 | 0.00 | 01-JAN-00:10 |
February | 0.283356E+11 | 0.862461E+10 | 269.52 | 0.230104E+11 | 0.532523E+10 | 0.00 | 0.66 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 | 66608.38 | 24-FEB-16:00 | 53416.09 | 22-FEB-15:40 | 21390.22 | 25-FEB-17:00 | 19688.42 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.785119E+11 | 0.237217E+11 | 400.72 | 0.648462E+11 | 0.136657E+11 | 0.00 | 1.00 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 | 234616.90 | 11-MAR-07:02 | 180562.68 | 13-MAR-06:03 | 57575.75 | 11-MAR-07:02 | 59177.60 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.132222E+12 | 0.414481E+11 | 420.77 | 0.115517E+12 | 0.167048E+11 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 239055.54 | 24-APR-06:02 | 219819.89 | 28-APR-05:01 | 74456.03 | 24-APR-06:02 | 64529.59 | 27-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.190491E+12 | 0.605192E+11 | 449.44 | 0.152298E+12 | 0.381924E+11 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 245908.18 | 24-MAY-06:02 | 219923.30 | 29-MAY-07:01 | 99461.65 | 24-MAY-06:04 | 66691.91 | 04-MAY-04:01 | 0.00 | 01-MAY-00:10 |
June | 0.208918E+12 | 0.644804E+11 | 440.13 | 0.149815E+12 | 0.591024E+11 | 0.00 | 1.00 | 01-JUN-05:03 | 0.00 | 01-JUN-00:10 | 254326.49 | 25-JUN-08:62 | 210003.29 | 07-JUN-04:01 | 127241.24 | 25-JUN-08:04 | 67727.16 | 14-JUN-04:01 | 0.00 | 01-JUN-00:10 |
July | 0.223985E+12 | 0.636363E+11 | 447.15 | 0.135504E+12 | 0.884809E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:05 | 254304.77 | 19-JUL-06:02 | 190310.03 | 05-JUL-04:01 | 127510.83 | 19-JUL-06:04 | 68347.06 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.220238E+12 | 0.604373E+11 | 449.31 | 0.125471E+12 | 0.947667E+11 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 255982.40 | 20-AUG-08:62 | 172359.93 | 07-AUG-04:01 | 132969.22 | 20-AUG-08:04 | 65251.80 | 08-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.177064E+12 | 0.490189E+11 | 428.48 | 0.106314E+12 | 0.707501E+11 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 257742.12 | 10-SEP-08:62 | 176321.25 | 26-SEP-05:02 | 140012.15 | 10-SEP-08:62 | 63761.96 | 24-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.114346E+12 | 0.338714E+11 | 415.29 | 0.875917E+11 | 0.267542E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 246602.06 | 12-OCT-06:02 | 188229.50 | 15-OCT-08:62 | 106304.09 | 12-OCT-06:02 | 61220.00 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.564757E+11 | 0.171035E+11 | 353.42 | 0.462181E+11 | 0.102577E+11 | 0.00 | 0.78 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 | 79929.15 | 09-NOV-13:10 | 68360.55 | 04-NOV-14:40 | 17523.26 | 08-NOV-18:00 | 24093.58 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 0.146670E+11 | 0.453024E+10 | 221.09 | 0.118659E+11 | 0.280108E+10 | 0.00 | 0.45 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 | 41577.82 | 01-DEC-15:30 | 37532.86 | 01-DEC-15:10 | 9578.15 | 16-DEC-16:00 | 12578.23 | 28-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.145329E+13 | 0.429891E+12 | 4454.23 | 0.102503E+13 | 0.428263E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.804027E+10 | 0.249921E+10 | 158.92 | 0.657848E+10 | 0.146179E+10 | 0.00 | 0.39 | 0.00 | 37044.58 | 29499.17 | 9299.32 | 10998.66 | 0.00 | |||||||
Maximum of Months | 0.223985E+12 | 0.644804E+11 | 449.44 | 0.152298E+12 | 0.947667E+11 | 0.00 | 1.00 | 0.00 | 257742.12 | 219923.30 | 140012.15 | 68347.06 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.499676E+10 | 0.127615E+10 | 290.31 | 0.447368E+10 | 0.523079E+09 | 0.00 | 0.69 | 12-JAN-15:30 | 0.00 | 01-JAN-00:10 | 10825.49 | 12-JAN-15:30 | 10035.30 | 12-JAN-15:10 | 1510.34 | 13-JAN-14:00 | 2643.25 | 12-JAN-15:30 | 0.00 | 01-JAN-00:10 |
February | 0.815531E+10 | 0.204800E+10 | 319.23 | 0.722617E+10 | 0.929136E+09 | 0.00 | 0.99 | 22-FEB-05:03 | 0.00 | 01-FEB-00:10 | 30662.02 | 23-FEB-05:02 | 27952.57 | 23-FEB-05:02 | 3502.77 | 25-FEB-05:03 | 6530.87 | 23-FEB-05:02 | 0.00 | 01-FEB-00:10 |
March | 0.158039E+11 | 0.403150E+10 | 445.15 | 0.140426E+11 | 0.176124E+10 | 0.00 | 1.00 | 07-MAR-05:01 | 0.00 | 01-MAR-00:10 | 37411.14 | 11-MAR-05:01 | 35247.14 | 29-MAR-04:01 | 8054.82 | 11-MAR-05:03 | 8164.84 | 11-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.230023E+11 | 0.629457E+10 | 477.49 | 0.210611E+11 | 0.194115E+10 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 37727.69 | 17-APR-04:01 | 36261.67 | 21-APR-04:01 | 7700.01 | 17-APR-04:12 | 8690.53 | 27-APR-04:01 | 0.00 | 01-APR-00:10 |
May | 0.302739E+11 | 0.857780E+10 | 533.15 | 0.258285E+11 | 0.444534E+10 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 39628.99 | 24-MAY-04:01 | 36075.72 | 29-MAY-06:01 | 15483.54 | 24-MAY-04:12 | 9100.46 | 04-MAY-04:11 | 0.00 | 01-MAY-00:10 |
June | 0.320066E+11 | 0.891348E+10 | 524.15 | 0.252355E+11 | 0.677104E+10 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 40857.08 | 26-JUN-04:01 | 34467.35 | 03-JUN-04:01 | 19644.25 | 26-JUN-04:05 | 9303.14 | 12-JUN-04:11 | 0.00 | 01-JUN-00:10 |
July | 0.343596E+11 | 0.885915E+10 | 523.04 | 0.240472E+11 | 0.103124E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:05 | 40994.40 | 20-JUL-04:01 | 30961.75 | 07-JUL-04:11 | 19955.23 | 20-JUL-04:06 | 9281.64 | 02-JUL-06:01 | 0.00 | 01-JUL-00:05 |
August | 0.337687E+11 | 0.841975E+10 | 500.53 | 0.228870E+11 | 0.108817E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 40102.68 | 19-AUG-04:01 | 30442.48 | 06-AUG-06:01 | 17021.29 | 11-AUG-04:12 | 8934.21 | 08-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.289758E+11 | 0.725638E+10 | 471.53 | 0.206780E+11 | 0.829776E+10 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 40465.74 | 03-SEP-06:01 | 33554.63 | 27-SEP-04:01 | 18977.69 | 10-SEP-06:02 | 8606.48 | 18-SEP-04:01 | 0.00 | 01-SEP-00:10 |
October | 0.237742E+11 | 0.599205E+10 | 473.05 | 0.203064E+11 | 0.346778E+10 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 38349.50 | 12-OCT-04:01 | 35322.65 | 23-OCT-04:01 | 12222.04 | 12-OCT-04:03 | 8286.46 | 04-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.154110E+11 | 0.378271E+10 | 415.26 | 0.137905E+11 | 0.162056E+10 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 | 36340.00 | 09-NOV-05:01 | 33881.19 | 02-NOV-04:01 | 5056.97 | 19-NOV-08:61 | 7723.98 | 09-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.704196E+10 | 0.177662E+10 | 337.19 | 0.626237E+10 | 0.779594E+09 | 0.00 | 0.75 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 | 11939.71 | 01-DEC-15:10 | 11449.28 | 01-DEC-15:10 | 1517.81 | 16-DEC-15:30 | 2890.84 | 28-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.257570E+12 | 0.672282E+11 | 5310.07 | 0.205839E+12 | 0.517307E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.499676E+10 | 0.127615E+10 | 290.31 | 0.447368E+10 | 0.523079E+09 | 0.00 | 0.69 | 0.00 | 10825.49 | 10035.30 | 1510.34 | 2643.25 | 0.00 | |||||||
Maximum of Months | 0.343596E+11 | 0.891348E+10 | 533.15 | 0.258285E+11 | 0.108817E+11 | 0.00 | 1.00 | 0.00 | 40994.40 | 36261.67 | 19955.23 | 9303.14 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.294807E+10 | 0.766069E+09 | 229.24 | 0.261203E+10 | 0.336036E+09 | 0.00 | 0.63 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 8786.97 | 12-JAN-15:20 | 8047.59 | 12-JAN-15:10 | 1361.50 | 13-JAN-14:10 | 2189.51 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.591558E+10 | 0.150919E+10 | 284.70 | 0.517711E+10 | 0.738463E+09 | 0.00 | 0.85 | 22-FEB-15:10 | 0.00 | 01-FEB-00:10 | 19652.24 | 23-FEB-05:02 | 17138.72 | 23-FEB-05:02 | 2513.52 | 23-FEB-05:02 | 4188.58 | 23-FEB-05:02 | 0.00 | 01-FEB-00:10 |
March | 0.128996E+11 | 0.332999E+10 | 418.33 | 0.112974E+11 | 0.160224E+10 | 0.00 | 1.00 | 07-MAR-05:01 | 0.00 | 01-MAR-00:10 | 33993.73 | 11-MAR-05:01 | 30799.34 | 29-MAR-04:01 | 7420.09 | 11-MAR-05:02 | 7423.70 | 11-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.201106E+11 | 0.552955E+10 | 463.69 | 0.182393E+11 | 0.187134E+10 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 34241.29 | 17-APR-04:01 | 32695.82 | 29-APR-04:01 | 7332.93 | 17-APR-04:12 | 7877.08 | 27-APR-04:01 | 0.00 | 01-APR-00:10 |
May | 0.270898E+11 | 0.767051E+10 | 509.44 | 0.227863E+11 | 0.430353E+10 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 36029.79 | 24-MAY-04:01 | 32595.50 | 29-MAY-06:01 | 14642.04 | 24-MAY-04:12 | 8297.02 | 04-MAY-04:01 | 0.00 | 01-MAY-00:10 |
June | 0.285954E+11 | 0.793894E+10 | 502.45 | 0.220510E+11 | 0.654446E+10 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 37145.55 | 26-JUN-04:01 | 31220.88 | 05-JUN-04:01 | 18552.58 | 26-JUN-04:05 | 8460.79 | 12-JUN-04:11 | 0.00 | 01-JUN-00:10 |
July | 0.309733E+11 | 0.794454E+10 | 499.71 | 0.209692E+11 | 0.100041E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:15 | 37299.95 | 20-JUL-04:01 | 27813.93 | 07-JUL-04:01 | 18765.77 | 20-JUL-04:06 | 8444.84 | 02-JUL-06:01 | 0.00 | 01-JUL-00:05 |
August | 0.303126E+11 | 0.752177E+10 | 486.63 | 0.197615E+11 | 0.105511E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 36541.19 | 19-AUG-04:01 | 27072.78 | 09-AUG-04:11 | 16432.70 | 11-AUG-04:12 | 8128.33 | 08-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.256966E+11 | 0.643231E+10 | 461.07 | 0.177346E+11 | 0.796199E+10 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 36804.73 | 03-SEP-06:01 | 29415.07 | 27-SEP-04:01 | 18783.00 | 10-SEP-06:02 | 7828.52 | 18-SEP-04:01 | 0.00 | 01-SEP-00:10 |
October | 0.207659E+11 | 0.526072E+10 | 468.54 | 0.174446E+11 | 0.332122E+10 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 34939.80 | 12-OCT-04:01 | 31208.74 | 03-OCT-04:01 | 12470.65 | 12-OCT-04:01 | 7513.76 | 04-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.126268E+11 | 0.313487E+10 | 392.18 | 0.111345E+11 | 0.149230E+10 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 | 33074.81 | 09-NOV-05:01 | 29708.60 | 03-NOV-04:01 | 5237.87 | 09-NOV-05:01 | 7029.68 | 09-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.459331E+10 | 0.117927E+10 | 296.70 | 0.401021E+10 | 0.583093E+09 | 0.00 | 0.71 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 | 10056.78 | 01-DEC-15:10 | 9567.27 | 01-DEC-14:30 | 1402.40 | 16-DEC-14:30 | 2444.69 | 02-DEC-14:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.222528E+12 | 0.582177E+11 | 5012.68 | 0.173218E+12 | 0.493099E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.294807E+10 | 0.766069E+09 | 229.24 | 0.261203E+10 | 0.336036E+09 | 0.00 | 0.63 | 0.00 | 8786.97 | 8047.59 | 1361.50 | 2189.51 | 0.00 | |||||||
Maximum of Months | 0.309733E+11 | 0.794454E+10 | 509.44 | 0.227863E+11 | 0.105511E+11 | 0.00 | 1.00 | 0.00 | 37299.95 | 32695.82 | 18783.00 | 8460.79 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.16 | 18.18 | 15.98 | 46.92 | 97.00 | 33.17 | 0.00 | 744.00 |
February | 43.53 | 24.37 | 19.16 | 69.82 | 80.09 | 2.33 | 0.00 | 672.00 |
March | 57.56 | 34.18 | 23.39 | 107.25 | 56.60 | 0.00 | 0.00 | 744.00 |
April | 74.77 | 52.27 | 22.50 | 159.40 | 35.49 | 0.00 | 0.00 | 720.00 |
May | 78.85 | 54.30 | 24.55 | 178.35 | 19.53 | 0.00 | 0.00 | 744.00 |
June | 73.89 | 46.83 | 27.05 | 171.99 | 12.47 | 0.00 | 0.00 | 720.00 |
July | 51.84 | 18.45 | 33.39 | 123.98 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 44.72 | 12.57 | 32.15 | 106.03 | 10.95 | 0.00 | 0.00 | 744.00 |
September | 46.45 | 19.80 | 26.65 | 99.15 | 20.93 | 0.00 | 0.00 | 720.00 |
October | 51.51 | 32.57 | 18.94 | 103.85 | 50.75 | 0.00 | 0.00 | 744.00 |
November | 43.29 | 28.52 | 14.77 | 75.03 | 78.32 | 0.00 | 0.00 | 720.00 |
December | 33.26 | 17.90 | 15.37 | 46.99 | 98.56 | 9.33 | 0.00 | 744.00 |
Annual Sum or Average | 52.82 | 29.97 | 22.86 | 107.50 | 47.22 | 44.83 | 0.00 | 8760.00 |
Minimum of Months | 33.26 | 12.57 | 14.77 | 46.92 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.85 | 54.30 | 33.39 | 178.35 | 98.56 | 33.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 642.40 | 386.99 | 255.41 | 1422.08 | 1101.32 | 4.17 | 0.00 | 744.00 |
February | 619.79 | 344.62 | 275.17 | 1504.28 | 928.92 | 0.67 | 0.00 | 672.00 |
March | 548.13 | 252.66 | 295.47 | 1554.25 | 630.90 | 0.00 | 0.00 | 744.00 |
April | 400.60 | 133.79 | 266.81 | 1507.13 | 310.99 | 0.00 | 0.00 | 720.00 |
May | 278.87 | 31.34 | 247.53 | 1375.43 | 115.80 | 0.00 | 0.00 | 744.00 |
June | 247.94 | 7.59 | 240.36 | 1351.28 | 70.42 | 0.00 | 0.00 | 720.00 |
July | 257.39 | 5.83 | 251.56 | 1232.19 | 39.67 | 0.00 | 0.00 | 744.00 |
August | 275.63 | 19.51 | 256.12 | 1178.01 | 89.36 | 0.00 | 0.00 | 744.00 |
September | 374.52 | 105.94 | 268.58 | 1323.41 | 196.91 | 0.00 | 0.00 | 720.00 |
October | 631.46 | 355.89 | 275.57 | 2000.46 | 563.31 | 0.00 | 0.00 | 744.00 |
November | 769.60 | 505.35 | 264.25 | 2106.37 | 906.66 | 0.00 | 0.00 | 720.00 |
December | 683.61 | 423.88 | 259.73 | 1593.28 | 1120.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 476.65 | 213.67 | 262.98 | 1511.76 | 504.25 | 4.83 | 0.00 | 8760.00 |
Minimum of Months | 247.94 | 5.83 | 240.36 | 1178.01 | 39.67 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 769.60 | 505.35 | 295.47 | 2106.37 | 1120.65 | 4.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 642.40 | 386.99 | 255.41 | 1437.18 | 1057.76 | 6.33 | 0.00 | 744.00 |
February | 619.79 | 344.62 | 275.17 | 1514.50 | 892.50 | 2.17 | 0.00 | 672.00 |
March | 548.13 | 252.66 | 295.47 | 1558.13 | 602.20 | 0.00 | 0.00 | 744.00 |
April | 400.60 | 133.79 | 266.81 | 1509.88 | 290.74 | 0.00 | 0.00 | 720.00 |
May | 278.87 | 31.34 | 247.53 | 1382.07 | 103.29 | 0.00 | 0.00 | 744.00 |
June | 247.94 | 7.59 | 240.36 | 1363.48 | 59.48 | 0.00 | 0.00 | 720.00 |
July | 257.39 | 5.83 | 251.56 | 1243.17 | 31.54 | 0.00 | 0.00 | 744.00 |
August | 275.63 | 19.51 | 256.12 | 1184.03 | 76.37 | 0.00 | 0.00 | 744.00 |
September | 374.52 | 105.94 | 268.58 | 1330.03 | 177.41 | 0.00 | 0.00 | 720.00 |
October | 631.46 | 355.89 | 275.57 | 2002.56 | 540.65 | 0.00 | 0.00 | 744.00 |
November | 769.60 | 505.35 | 264.25 | 2111.01 | 878.50 | 0.00 | 0.00 | 720.00 |
December | 683.61 | 423.88 | 259.73 | 1606.33 | 1083.83 | 1.00 | 0.00 | 744.00 |
Annual Sum or Average | 476.65 | 213.67 | 262.98 | 1519.60 | 480.93 | 9.50 | 0.00 | 8760.00 |
Minimum of Months | 247.94 | 5.83 | 240.36 | 1184.03 | 31.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 769.60 | 505.35 | 295.47 | 2111.01 | 1083.83 | 6.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.18 | 79.63 | 52.56 | 294.50 | 203.40 | 0.00 | 0.00 | 744.00 |
February | 127.53 | 70.91 | 56.62 | 303.26 | 174.08 | 0.50 | 0.00 | 672.00 |
March | 112.78 | 51.99 | 60.80 | 290.43 | 130.87 | 0.00 | 0.00 | 744.00 |
April | 82.43 | 27.53 | 54.90 | 232.25 | 80.41 | 0.00 | 0.00 | 720.00 |
May | 57.38 | 6.45 | 50.93 | 174.27 | 45.83 | 0.00 | 0.00 | 744.00 |
June | 51.02 | 1.56 | 49.46 | 164.86 | 29.77 | 5.33 | 0.00 | 720.00 |
July | 52.96 | 1.20 | 51.76 | 161.26 | 19.86 | 7.17 | 0.00 | 744.00 |
August | 56.71 | 4.01 | 52.70 | 168.18 | 32.60 | 7.33 | 0.00 | 744.00 |
September | 77.06 | 21.80 | 55.26 | 207.18 | 57.80 | 21.17 | 0.00 | 720.00 |
October | 129.93 | 73.23 | 56.70 | 355.51 | 133.54 | 0.00 | 0.00 | 744.00 |
November | 158.36 | 103.98 | 54.37 | 405.56 | 183.20 | 0.00 | 0.00 | 720.00 |
December | 140.66 | 87.22 | 53.44 | 328.44 | 206.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 98.08 | 43.96 | 54.11 | 256.81 | 107.82 | 41.50 | 0.00 | 8760.00 |
Minimum of Months | 51.02 | 1.20 | 49.46 | 161.26 | 19.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 158.36 | 103.98 | 60.80 | 405.56 | 206.35 | 21.17 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91481406.08 | 48686246.94 | 42795159.14 | 0.125683E+09 | 0.259809E+09 |
February | 0.105305E+09 | 58964677.20 | 46340466.68 | 0.168916E+09 | 0.193745E+09 |
March | 0.154176E+09 | 91539521.53 | 62636089.27 | 0.287254E+09 | 0.151602E+09 |
April | 0.193799E+09 | 0.135477E+09 | 58321768.02 | 0.413173E+09 | 92001228.01 |
May | 0.211194E+09 | 0.145436E+09 | 65758256.71 | 0.477701E+09 | 52309517.39 |
June | 0.191515E+09 | 0.121394E+09 | 70120974.13 | 0.445785E+09 | 32312352.05 |
July | 0.138851E+09 | 49414326.72 | 89436663.43 | 0.332060E+09 | 20949730.64 |
August | 0.119780E+09 | 33665273.57 | 86114776.42 | 0.283982E+09 | 29337196.08 |
September | 0.120394E+09 | 51323934.01 | 69070349.51 | 0.256985E+09 | 54245902.12 |
October | 0.137976E+09 | 87233753.56 | 50742126.76 | 0.278147E+09 | 0.135922E+09 |
November | 0.112203E+09 | 73922252.56 | 38280938.57 | 0.194470E+09 | 0.203013E+09 |
December | 89089288.52 | 47931002.93 | 41158285.58 | 0.125871E+09 | 0.263972E+09 |
Annual Sum or Average | 0.166576E+10 | 0.944988E+09 | 0.720776E+09 | 0.339003E+10 | 0.148922E+10 |
Minimum of Months | 89089288.52 | 33665273.57 | 38280938.57 | 0.125683E+09 | 20949730.64 |
Maximum of Months | 0.211194E+09 | 0.145436E+09 | 89436663.43 | 0.477701E+09 | 0.263972E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172061E+10 | 0.103651E+10 | 0.684103E+09 | 0.380891E+10 | 0.294978E+10 |
February | 0.149939E+10 | 0.833694E+09 | 0.665692E+09 | 0.363915E+10 | 0.224724E+10 |
March | 0.146810E+10 | 0.676714E+09 | 0.791385E+09 | 0.416289E+10 | 0.168981E+10 |
April | 0.103836E+10 | 0.346781E+09 | 0.691583E+09 | 0.390647E+10 | 0.806095E+09 |
May | 0.746931E+09 | 83940889.16 | 0.662990E+09 | 0.368395E+10 | 0.310169E+09 |
June | 0.642673E+09 | 19667135.94 | 0.623006E+09 | 0.350251E+10 | 0.182538E+09 |
July | 0.689396E+09 | 15618333.91 | 0.673778E+09 | 0.330029E+10 | 0.106252E+09 |
August | 0.738243E+09 | 52244298.55 | 0.685999E+09 | 0.315518E+10 | 0.239333E+09 |
September | 0.970749E+09 | 0.274592E+09 | 0.696157E+09 | 0.343027E+10 | 0.510384E+09 |
October | 0.169131E+10 | 0.953206E+09 | 0.738099E+09 | 0.535804E+10 | 0.150877E+10 |
November | 0.199479E+10 | 0.130986E+10 | 0.684934E+09 | 0.545971E+10 | 0.235006E+10 |
December | 0.183098E+10 | 0.113531E+10 | 0.695666E+09 | 0.426745E+10 | 0.300155E+10 |
Annual Sum or Average | 0.150315E+11 | 0.673814E+10 | 0.829339E+10 | 0.476748E+11 | 0.159020E+11 |
Minimum of Months | 0.642673E+09 | 15618333.91 | 0.623006E+09 | 0.315518E+10 | 0.106252E+09 |
Maximum of Months | 0.199479E+10 | 0.130986E+10 | 0.791385E+09 | 0.545971E+10 | 0.300155E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172061E+10 | 0.103651E+10 | 0.684103E+09 | 0.384935E+10 | 0.283309E+10 |
February | 0.149939E+10 | 0.833694E+09 | 0.665692E+09 | 0.366387E+10 | 0.215915E+10 |
March | 0.146810E+10 | 0.676714E+09 | 0.791385E+09 | 0.417329E+10 | 0.161293E+10 |
April | 0.103836E+10 | 0.346781E+09 | 0.691583E+09 | 0.391362E+10 | 0.753606E+09 |
May | 0.746931E+09 | 83940889.16 | 0.662990E+09 | 0.370173E+10 | 0.276651E+09 |
June | 0.642673E+09 | 19667135.94 | 0.623006E+09 | 0.353414E+10 | 0.154176E+09 |
July | 0.689396E+09 | 15618333.91 | 0.673778E+09 | 0.332970E+10 | 84464420.88 |
August | 0.738243E+09 | 52244298.55 | 0.685999E+09 | 0.317131E+10 | 0.204538E+09 |
September | 0.970749E+09 | 0.274592E+09 | 0.696157E+09 | 0.344744E+10 | 0.459849E+09 |
October | 0.169131E+10 | 0.953206E+09 | 0.738099E+09 | 0.536367E+10 | 0.144808E+10 |
November | 0.199479E+10 | 0.130986E+10 | 0.684934E+09 | 0.547174E+10 | 0.227706E+10 |
December | 0.183098E+10 | 0.113531E+10 | 0.695666E+09 | 0.430239E+10 | 0.290292E+10 |
Annual Sum or Average | 0.150315E+11 | 0.673814E+10 | 0.829339E+10 | 0.479222E+11 | 0.151665E+11 |
Minimum of Months | 0.642673E+09 | 15618333.91 | 0.623006E+09 | 0.317131E+10 | 84464420.88 |
Maximum of Months | 0.199479E+10 | 0.130986E+10 | 0.791385E+09 | 0.547174E+10 | 0.290292E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.354041E+09 | 0.213277E+09 | 0.140764E+09 | 0.788790E+09 | 0.544791E+09 |
February | 0.308520E+09 | 0.171545E+09 | 0.136976E+09 | 0.733637E+09 | 0.421134E+09 |
March | 0.302083E+09 | 0.139244E+09 | 0.162839E+09 | 0.777888E+09 | 0.350514E+09 |
April | 0.213659E+09 | 71355297.63 | 0.142303E+09 | 0.601993E+09 | 0.208414E+09 |
May | 0.153692E+09 | 17272060.22 | 0.136420E+09 | 0.466755E+09 | 0.122752E+09 |
June | 0.132239E+09 | 4046799.60 | 0.128192E+09 | 0.427307E+09 | 77162489.54 |
July | 0.141853E+09 | 3213699.62 | 0.138640E+09 | 0.431915E+09 | 53196735.79 |
August | 0.151904E+09 | 10750025.17 | 0.141154E+09 | 0.450441E+09 | 87322599.46 |
September | 0.199746E+09 | 56501347.98 | 0.143244E+09 | 0.537002E+09 | 0.149817E+09 |
October | 0.348011E+09 | 0.196136E+09 | 0.151875E+09 | 0.952204E+09 | 0.357680E+09 |
November | 0.410457E+09 | 0.269522E+09 | 0.140935E+09 | 0.105121E+10 | 0.474853E+09 |
December | 0.376751E+09 | 0.233607E+09 | 0.143143E+09 | 0.879696E+09 | 0.552687E+09 |
Annual Sum or Average | 0.309296E+10 | 0.138647E+10 | 0.170649E+10 | 0.809884E+10 | 0.340032E+10 |
Minimum of Months | 0.132239E+09 | 3213699.62 | 0.128192E+09 | 0.427307E+09 | 53196735.79 |
Maximum of Months | 0.410457E+09 | 0.269522E+09 | 0.162839E+09 | 0.105121E+10 | 0.552687E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 750.79 | 1552.03 | 546.48 | 290.84 | 255.65 | 0.00 | 0.00 |
February | 1117.17 | 1281.39 | 696.46 | 389.98 | 306.48 | 0.00 | 0.00 |
March | 1715.98 | 905.63 | 921.00 | 546.83 | 374.17 | 0.00 | 0.00 |
April | 2550.45 | 567.91 | 1196.29 | 836.28 | 360.01 | 0.00 | 0.00 |
May | 2853.65 | 312.48 | 1261.61 | 868.79 | 392.82 | 0.00 | 0.00 |
June | 2751.76 | 199.46 | 1182.19 | 749.34 | 432.85 | 0.00 | 0.00 |
July | 1983.63 | 125.15 | 829.46 | 295.19 | 534.27 | 0.00 | 0.00 |
August | 1696.43 | 175.25 | 715.53 | 201.11 | 514.43 | 0.00 | 0.00 |
September | 1586.33 | 334.85 | 743.17 | 316.81 | 426.36 | 0.00 | 0.00 |
October | 1661.57 | 811.96 | 824.23 | 521.11 | 303.12 | 0.00 | 0.00 |
November | 1200.43 | 1253.17 | 692.61 | 456.31 | 236.30 | 0.00 | 0.00 |
December | 751.92 | 1576.90 | 532.19 | 286.33 | 245.87 | 0.00 | 0.00 |
Annual Sum or Average | 1719.95 | 755.57 | 845.14 | 479.45 | 365.69 | 0.00 | 0.00 |
Minimum of Months | 750.79 | 125.15 | 532.19 | 201.11 | 236.30 | 0.00 | 0.00 |
Maximum of Months | 2853.65 | 1576.90 | 1261.61 | 868.79 | 534.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1422.08 | 1101.32 | 642.40 | 386.99 | 255.41 | 0.00 | 0.00 |
February | 1504.28 | 928.92 | 619.79 | 344.62 | 275.17 | 0.00 | 0.00 |
March | 1554.25 | 630.90 | 548.13 | 252.66 | 295.47 | 0.00 | 0.00 |
April | 1507.13 | 310.99 | 400.60 | 133.79 | 266.81 | 0.00 | 0.00 |
May | 1375.43 | 115.80 | 278.87 | 31.34 | 247.53 | 0.00 | 0.00 |
June | 1351.28 | 70.42 | 247.94 | 7.59 | 240.36 | 0.00 | 0.00 |
July | 1232.19 | 39.67 | 257.39 | 5.83 | 251.56 | 0.00 | 0.00 |
August | 1178.01 | 89.36 | 275.63 | 19.51 | 256.12 | 0.00 | 0.00 |
September | 1323.41 | 196.91 | 374.52 | 105.94 | 268.58 | 0.00 | 0.00 |
October | 2000.46 | 563.31 | 631.46 | 355.89 | 275.57 | 0.00 | 0.00 |
November | 2106.37 | 906.66 | 769.60 | 505.35 | 264.25 | 0.00 | 0.00 |
December | 1593.28 | 1120.65 | 683.61 | 423.88 | 259.73 | 0.00 | 0.00 |
Annual Sum or Average | 1511.76 | 504.25 | 476.65 | 213.67 | 262.98 | 0.00 | 0.00 |
Minimum of Months | 1178.01 | 39.67 | 247.94 | 5.83 | 240.36 | 0.00 | 0.00 |
Maximum of Months | 2106.37 | 1120.65 | 769.60 | 505.35 | 295.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1437.18 | 1057.76 | 642.40 | 386.99 | 255.41 | 0.00 | 0.00 |
February | 1514.50 | 892.50 | 619.79 | 344.62 | 275.17 | 0.00 | 0.00 |
March | 1558.13 | 602.20 | 548.13 | 252.66 | 295.47 | 0.00 | 0.00 |
April | 1509.88 | 290.74 | 400.60 | 133.79 | 266.81 | 0.00 | 0.00 |
May | 1382.07 | 103.29 | 278.87 | 31.34 | 247.53 | 0.00 | 0.00 |
June | 1363.48 | 59.48 | 247.94 | 7.59 | 240.36 | 0.00 | 0.00 |
July | 1243.17 | 31.54 | 257.39 | 5.83 | 251.56 | 0.00 | 0.00 |
August | 1184.03 | 76.37 | 275.63 | 19.51 | 256.12 | 0.00 | 0.00 |
September | 1330.03 | 177.41 | 374.52 | 105.94 | 268.58 | 0.00 | 0.00 |
October | 2002.56 | 540.65 | 631.46 | 355.89 | 275.57 | 0.00 | 0.00 |
November | 2111.01 | 878.50 | 769.60 | 505.35 | 264.25 | 0.00 | 0.00 |
December | 1606.33 | 1083.83 | 683.61 | 423.88 | 259.73 | 0.00 | 0.00 |
Annual Sum or Average | 1519.60 | 480.93 | 476.65 | 213.67 | 262.98 | 0.00 | 0.00 |
Minimum of Months | 1184.03 | 31.54 | 247.94 | 5.83 | 240.36 | 0.00 | 0.00 |
Maximum of Months | 2111.01 | 1083.83 | 769.60 | 505.35 | 295.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 294.50 | 203.40 | 132.18 | 79.63 | 52.56 | 0.00 | 0.00 |
February | 303.26 | 174.08 | 127.53 | 70.91 | 56.62 | 0.00 | 0.00 |
March | 290.43 | 130.87 | 112.78 | 51.99 | 60.80 | 0.00 | 0.00 |
April | 232.25 | 80.41 | 82.43 | 27.53 | 54.90 | 0.00 | 0.00 |
May | 174.27 | 45.83 | 57.38 | 6.45 | 50.93 | 0.00 | 0.00 |
June | 164.86 | 29.77 | 51.02 | 1.56 | 49.46 | 0.00 | 0.00 |
July | 161.26 | 19.86 | 52.96 | 1.20 | 51.76 | 0.00 | 0.00 |
August | 168.18 | 32.60 | 56.71 | 4.01 | 52.70 | 0.00 | 0.00 |
September | 207.18 | 57.80 | 77.06 | 21.80 | 55.26 | 0.00 | 0.00 |
October | 355.51 | 133.54 | 129.93 | 73.23 | 56.70 | 0.00 | 0.00 |
November | 405.56 | 183.20 | 158.36 | 103.98 | 54.37 | 0.00 | 0.00 |
December | 328.44 | 206.35 | 140.66 | 87.22 | 53.44 | 0.00 | 0.00 |
Annual Sum or Average | 256.81 | 107.82 | 98.08 | 43.96 | 54.11 | 0.00 | 0.00 |
Minimum of Months | 161.26 | 19.86 | 51.02 | 1.20 | 49.46 | 0.00 | 0.00 |
Maximum of Months | 405.56 | 206.35 | 158.36 | 103.98 | 60.80 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.201092E+10 | 0.415695E+10 | 0.146370E+10 | 0.778980E+09 | 0.684723E+09 | 0.00 | 0.00 |
February | 0.270266E+10 | 0.309993E+10 | 0.168488E+10 | 0.943435E+09 | 0.741447E+09 | 0.00 | 0.00 |
March | 0.459607E+10 | 0.242564E+10 | 0.246681E+10 | 0.146463E+10 | 0.100218E+10 | 0.00 | 0.00 |
April | 0.661076E+10 | 0.147202E+10 | 0.310078E+10 | 0.216763E+10 | 0.933148E+09 | 0.00 | 0.00 |
May | 0.764322E+10 | 0.836952E+09 | 0.337911E+10 | 0.232698E+10 | 0.105213E+10 | 0.00 | 0.00 |
June | 0.713257E+10 | 0.516998E+09 | 0.306424E+10 | 0.194230E+10 | 0.112194E+10 | 0.00 | 0.00 |
July | 0.531296E+10 | 0.335196E+09 | 0.222162E+10 | 0.790629E+09 | 0.143099E+10 | 0.00 | 0.00 |
August | 0.454372E+10 | 0.469395E+09 | 0.191648E+10 | 0.538644E+09 | 0.137784E+10 | 0.00 | 0.00 |
September | 0.411176E+10 | 0.867934E+09 | 0.192631E+10 | 0.821183E+09 | 0.110513E+10 | 0.00 | 0.00 |
October | 0.445035E+10 | 0.217475E+10 | 0.220761E+10 | 0.139574E+10 | 0.811874E+09 | 0.00 | 0.00 |
November | 0.311153E+10 | 0.324820E+10 | 0.179525E+10 | 0.118276E+10 | 0.612495E+09 | 0.00 | 0.00 |
December | 0.201394E+10 | 0.422356E+10 | 0.142543E+10 | 0.766896E+09 | 0.658533E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.542404E+11 | 0.238275E+11 | 0.266522E+11 | 0.151198E+11 | 0.115324E+11 | 0.00 | 0.00 |
Minimum of Months | 0.201092E+10 | 0.335196E+09 | 0.142543E+10 | 0.538644E+09 | 0.612495E+09 | 0.00 | 0.00 |
Maximum of Months | 0.764322E+10 | 0.422356E+10 | 0.337911E+10 | 0.232698E+10 | 0.143099E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.380891E+10 | 0.294978E+10 | 0.172061E+10 | 0.103651E+10 | 0.684103E+09 | 0.00 | 0.00 |
February | 0.363915E+10 | 0.224724E+10 | 0.149939E+10 | 0.833694E+09 | 0.665692E+09 | 0.00 | 0.00 |
March | 0.416289E+10 | 0.168981E+10 | 0.146810E+10 | 0.676714E+09 | 0.791385E+09 | 0.00 | 0.00 |
April | 0.390647E+10 | 0.806095E+09 | 0.103836E+10 | 0.346781E+09 | 0.691583E+09 | 0.00 | 0.00 |
May | 0.368395E+10 | 0.310169E+09 | 0.746931E+09 | 83940889.16 | 0.662990E+09 | 0.00 | 0.00 |
June | 0.350251E+10 | 0.182538E+09 | 0.642673E+09 | 19667135.94 | 0.623006E+09 | 0.00 | 0.00 |
July | 0.330029E+10 | 0.106252E+09 | 0.689396E+09 | 15618333.91 | 0.673778E+09 | 0.00 | 0.00 |
August | 0.315518E+10 | 0.239333E+09 | 0.738243E+09 | 52244298.55 | 0.685999E+09 | 0.00 | 0.00 |
September | 0.343027E+10 | 0.510384E+09 | 0.970749E+09 | 0.274592E+09 | 0.696157E+09 | 0.00 | 0.00 |
October | 0.535804E+10 | 0.150877E+10 | 0.169131E+10 | 0.953206E+09 | 0.738099E+09 | 0.00 | 0.00 |
November | 0.545971E+10 | 0.235006E+10 | 0.199479E+10 | 0.130986E+10 | 0.684934E+09 | 0.00 | 0.00 |
December | 0.426745E+10 | 0.300155E+10 | 0.183098E+10 | 0.113531E+10 | 0.695666E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.476748E+11 | 0.159020E+11 | 0.150315E+11 | 0.673814E+10 | 0.829339E+10 | 0.00 | 0.00 |
Minimum of Months | 0.315518E+10 | 0.106252E+09 | 0.642673E+09 | 15618333.91 | 0.623006E+09 | 0.00 | 0.00 |
Maximum of Months | 0.545971E+10 | 0.300155E+10 | 0.199479E+10 | 0.130986E+10 | 0.791385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.384935E+10 | 0.283309E+10 | 0.172061E+10 | 0.103651E+10 | 0.684103E+09 | 0.00 | 0.00 |
February | 0.366387E+10 | 0.215915E+10 | 0.149939E+10 | 0.833694E+09 | 0.665692E+09 | 0.00 | 0.00 |
March | 0.417329E+10 | 0.161293E+10 | 0.146810E+10 | 0.676714E+09 | 0.791385E+09 | 0.00 | 0.00 |
April | 0.391362E+10 | 0.753606E+09 | 0.103836E+10 | 0.346781E+09 | 0.691583E+09 | 0.00 | 0.00 |
May | 0.370173E+10 | 0.276651E+09 | 0.746931E+09 | 83940889.16 | 0.662990E+09 | 0.00 | 0.00 |
June | 0.353414E+10 | 0.154176E+09 | 0.642673E+09 | 19667135.94 | 0.623006E+09 | 0.00 | 0.00 |
July | 0.332970E+10 | 84464420.88 | 0.689396E+09 | 15618333.91 | 0.673778E+09 | 0.00 | 0.00 |
August | 0.317131E+10 | 0.204538E+09 | 0.738243E+09 | 52244298.55 | 0.685999E+09 | 0.00 | 0.00 |
September | 0.344744E+10 | 0.459849E+09 | 0.970749E+09 | 0.274592E+09 | 0.696157E+09 | 0.00 | 0.00 |
October | 0.536367E+10 | 0.144808E+10 | 0.169131E+10 | 0.953206E+09 | 0.738099E+09 | 0.00 | 0.00 |
November | 0.547174E+10 | 0.227706E+10 | 0.199479E+10 | 0.130986E+10 | 0.684934E+09 | 0.00 | 0.00 |
December | 0.430239E+10 | 0.290292E+10 | 0.183098E+10 | 0.113531E+10 | 0.695666E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.479222E+11 | 0.151665E+11 | 0.150315E+11 | 0.673814E+10 | 0.829339E+10 | 0.00 | 0.00 |
Minimum of Months | 0.317131E+10 | 84464420.88 | 0.642673E+09 | 15618333.91 | 0.623006E+09 | 0.00 | 0.00 |
Maximum of Months | 0.547174E+10 | 0.290292E+10 | 0.199479E+10 | 0.130986E+10 | 0.791385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.788790E+09 | 0.544791E+09 | 0.354041E+09 | 0.213277E+09 | 0.140764E+09 | 0.00 | 0.00 |
February | 0.733637E+09 | 0.421134E+09 | 0.308520E+09 | 0.171545E+09 | 0.136976E+09 | 0.00 | 0.00 |
March | 0.777888E+09 | 0.350514E+09 | 0.302083E+09 | 0.139244E+09 | 0.162839E+09 | 0.00 | 0.00 |
April | 0.601993E+09 | 0.208414E+09 | 0.213659E+09 | 71355297.63 | 0.142303E+09 | 0.00 | 0.00 |
May | 0.466755E+09 | 0.122752E+09 | 0.153692E+09 | 17272060.22 | 0.136420E+09 | 0.00 | 0.00 |
June | 0.427307E+09 | 77162489.54 | 0.132239E+09 | 4046799.60 | 0.128192E+09 | 0.00 | 0.00 |
July | 0.431915E+09 | 53196735.79 | 0.141853E+09 | 3213699.62 | 0.138640E+09 | 0.00 | 0.00 |
August | 0.450441E+09 | 87322599.46 | 0.151904E+09 | 10750025.17 | 0.141154E+09 | 0.00 | 0.00 |
September | 0.537002E+09 | 0.149817E+09 | 0.199746E+09 | 56501347.98 | 0.143244E+09 | 0.00 | 0.00 |
October | 0.952204E+09 | 0.357680E+09 | 0.348011E+09 | 0.196136E+09 | 0.151875E+09 | 0.00 | 0.00 |
November | 0.105121E+10 | 0.474853E+09 | 0.410457E+09 | 0.269522E+09 | 0.140935E+09 | 0.00 | 0.00 |
December | 0.879696E+09 | 0.552687E+09 | 0.376751E+09 | 0.233607E+09 | 0.143143E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.809884E+10 | 0.340032E+10 | 0.309296E+10 | 0.138647E+10 | 0.170649E+10 | 0.00 | 0.00 |
Minimum of Months | 0.427307E+09 | 53196735.79 | 0.132239E+09 | 3213699.62 | 0.128192E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105121E+10 | 0.552687E+09 | 0.410457E+09 | 0.269522E+09 | 0.162839E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.37 | 7.87 | 1.20 | 0.37 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.77 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.59 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.31 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.95 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.37 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.28 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.69 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.73 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.45 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.87 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.75 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.37 | 7.87 | 0.66 | 0.37 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.18 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.17 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.47 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.63 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.60 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.49 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.34 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.56 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.67 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.02 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.14 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.28 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.18 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.67 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.55 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.57 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.73 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.61 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.36 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.40 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.17 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.16 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.05 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.91 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.61 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.17 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.47 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.24 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.03 | 0.00 | 15.60 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.69 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.40 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.58 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.47 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.221738E+10 | -.180387E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -413511814.3 | 58.99 | 0.00 | 0.00 |
February | 0.196782E+10 | -.160753E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -360288883.0 | 58.99 | 0.00 | 0.00 |
March | 0.208583E+10 | -.170246E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -383367337.0 | 58.99 | 0.00 | 0.00 |
April | 0.181293E+10 | -.145243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -360501950.1 | 58.99 | 0.00 | 0.00 |
May | 0.169390E+10 | -.132692E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -366986789.1 | 58.99 | 0.00 | 0.00 |
June | 0.152407E+10 | -.116832E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -355751218.6 | 58.99 | 0.00 | 0.00 |
July | 0.148459E+10 | -.111749E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -367093960.0 | 58.99 | 0.00 | 0.00 |
August | 0.156281E+10 | -.119404E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -368772411.2 | 58.99 | 0.00 | 0.00 |
September | 0.161591E+10 | -.125599E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -359924857.7 | 58.99 | 0.00 | 0.00 |
October | 0.182559E+10 | -.144869E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -376906268.3 | 58.99 | 0.00 | 0.00 |
November | 0.193825E+10 | -.156202E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -376231184.9 | 58.99 | 0.00 | 0.00 |
December | 0.216023E+10 | -.175321E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -407018732.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.218893E+11 | -.173930E+11 | 8760.00 | -.449636E+10 | 58.99 | |||||
Minimum of Months | 0.148459E+10 | -.180387E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -413511814.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.221738E+10 | -.111749E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -355751218.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.90 | 0.67 | 14-JAN-11:30 | 217.12 | 5.79 | 0.00 | 0.00 | 178.83 | 4.41 | 0.00 | 0.00 |
February | 303.83 | 0.86 | 0.67 | 01-FEB-10:00 | 258.74 | 6.63 | 0.00 | 0.00 | 214.09 | 5.14 | 0.00 | 0.00 |
March | 364.50 | 0.79 | 0.50 | 02-MAR-11:09 | 1676.25 | 7.71 | 0.00 | 63.33 | 1799.79 | 6.16 | 0.00 | 55.17 |
April | 379.83 | 0.84 | 0.50 | 02-APR-11:30 | 282.74 | 8.03 | 0.00 | 8.00 | 234.79 | 6.42 | 0.00 | 5.67 |
May | 406.00 | 0.84 | 0.50 | 12-MAY-11:30 | 284.23 | 9.25 | 0.00 | 15.00 | 236.33 | 7.56 | 0.00 | 8.50 |
June | 386.67 | 0.82 | 0.50 | 01-JUN-10:50 | 304.88 | 10.06 | 0.00 | 26.83 | 252.66 | 8.30 | 0.00 | 15.00 |
July | 379.83 | 0.77 | 0.50 | 05-JUL-11:20 | 355.82 | 10.88 | 0.00 | 75.67 | 299.90 | 9.26 | 0.00 | 41.17 |
August | 372.50 | 0.77 | 0.50 | 01-AUG-10:30 | 400.02 | 10.25 | 0.00 | 96.33 | 348.60 | 8.69 | 0.00 | 55.83 |
September | 344.33 | 0.78 | 0.50 | 01-SEP-10:39 | 928.68 | 9.09 | 0.00 | 75.83 | 921.05 | 7.51 | 0.00 | 49.67 |
October | 347.33 | 0.85 | 0.50 | 06-OCT-11:20 | 271.52 | 6.80 | 0.00 | 5.17 | 225.43 | 5.35 | 0.00 | 2.33 |
November | 317.83 | 0.90 | 0.75 | 28-NOV-10:39 | 216.82 | 5.52 | 0.00 | 0.00 | 179.43 | 4.10 | 0.00 | 0.00 |
December | 315.50 | 0.90 | 0.75 | 08-DEC-11:39 | 211.75 | 5.63 | 0.00 | 0.00 | 174.03 | 4.22 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | 0.83 | 456.30 | 8.11 | 0.00 | 366.17 | 427.65 | 6.55 | 0.00 | 233.33 | ||
Minimum of Months | 303.83 | 0.77 | 0.50 | 211.75 | 5.52 | 0.00 | 0.00 | 174.03 | 4.10 | 0.00 | 0.00 | |
Maximum of Months | 406.00 | 0.90 | 0.75 | 1676.25 | 10.88 | 0.00 | 96.33 | 1799.79 | 9.26 | 0.00 | 55.83 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.340256E+10 | 73076.75 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.661270E+09 | 73076.75 | 11-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14667751.52 | 2001.52 | 27-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151542E+10 | 73076.75 | 21-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.559392E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.340256E+10 | 73076.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.469251E+10 | 240697.25 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.529685E+09 | 166790.11 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 425604.22 | 709.34 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.989722E+09 | 177675.38 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.621235E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.469251E+10 | 240697.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.447487E+09 | 40875.08 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 79364652.56 | 33980.40 | 11-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 83447035.77 | 19624.97 | 31-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.610299E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.447487E+09 | 40875.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.807918E+09 | 36687.48 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180746E+09 | 36687.48 | 11-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207826E+09 | 35477.45 | 31-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119649E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.807918E+09 | 36687.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.179897E+10 | 12336.67 | 01-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.346631E+09 | 9784.39 | 10-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1154141.75 | 719.35 | 30-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127234E+10 | 13530.46 | 31-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.341909E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.179897E+10 | 13530.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.291113E+09 | 0.221832E+09 | 5855.35 | 14-JAN-16:00 | 4278.69 | 0.00 |
February | 0.00 | 0.00 | 0.364045E+10 | 0.293677E+10 | 12577.30 | 24-FEB-16:00 | 10101.22 | 0.00 |
March | 0.00 | 0.00 | 0.159060E+11 | 0.134685E+11 | 66083.22 | 11-MAR-05:01 | 51673.77 | 0.00 |
April | 0.00 | 0.00 | 0.327546E+11 | 0.295579E+11 | 66288.82 | 17-APR-04:01 | 58859.89 | 0.00 |
May | 0.00 | 0.00 | 0.502208E+11 | 0.431625E+11 | 69801.36 | 24-MAY-04:01 | 46789.13 | 0.00 |
June | 0.00 | 0.00 | 0.539815E+11 | 0.436582E+11 | 71785.24 | 26-JUN-04:01 | 40669.56 | 0.00 |
July | 0.00 | 0.00 | 0.570695E+11 | 0.416655E+11 | 72041.76 | 20-JUL-04:01 | 40493.24 | 0.00 |
August | 0.00 | 0.00 | 0.538344E+11 | 0.379399E+11 | 70333.36 | 19-AUG-04:01 | 45989.51 | 0.00 |
September | 0.00 | 0.00 | 0.420519E+11 | 0.301767E+11 | 71016.65 | 03-SEP-06:01 | 43218.34 | 0.00 |
October | 0.00 | 0.00 | 0.264973E+11 | 0.217434E+11 | 67705.92 | 12-OCT-04:01 | 46338.55 | 0.00 |
November | 0.00 | 0.00 | 0.969207E+10 | 0.801231E+10 | 47066.55 | 01-NOV-04:01 | 37935.77 | 0.00 |
December | 0.00 | 0.00 | 0.916842E+09 | 0.719138E+09 | 6153.99 | 28-DEC-16:00 | 4897.31 | 0.00 |
Annual Sum or Average | 0.346856E+12 | 0.273263E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.291113E+09 | 0.221832E+09 | 5855.35 | 4278.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.570695E+11 | 0.436582E+11 | 72041.76 | 58859.89 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.804027E+10 | 0.657848E+10 | 37044.58 | 14-JAN-15:20 | 27745.26 | 0.00 |
February | 0.00 | 0.00 | 0.283356E+11 | 0.230104E+11 | 66608.38 | 24-FEB-16:00 | 52582.40 | 0.00 |
March | 0.00 | 0.00 | 0.785119E+11 | 0.648462E+11 | 234616.90 | 11-MAR-07:02 | 177041.15 | 0.00 |
April | 0.00 | 0.00 | 0.132222E+12 | 0.115517E+12 | 239055.54 | 24-APR-06:02 | 164599.51 | 0.00 |
May | 0.00 | 0.00 | 0.190491E+12 | 0.152298E+12 | 245908.18 | 24-MAY-06:02 | 147269.68 | 0.00 |
June | 0.00 | 0.00 | 0.208918E+12 | 0.149815E+12 | 254326.49 | 25-JUN-08:62 | 127257.60 | 0.00 |
July | 0.00 | 0.00 | 0.223985E+12 | 0.135504E+12 | 254304.77 | 19-JUL-06:02 | 126927.78 | 0.00 |
August | 0.00 | 0.00 | 0.220238E+12 | 0.125471E+12 | 255982.40 | 20-AUG-08:62 | 123043.67 | 0.00 |
September | 0.00 | 0.00 | 0.177064E+12 | 0.106314E+12 | 257742.12 | 10-SEP-08:62 | 117729.97 | 0.00 |
October | 0.00 | 0.00 | 0.114346E+12 | 0.875917E+11 | 246602.06 | 12-OCT-06:02 | 140297.97 | 0.00 |
November | 0.00 | 0.00 | 0.564757E+11 | 0.462181E+11 | 79929.15 | 09-NOV-13:10 | 65699.01 | 0.00 |
December | 0.00 | 0.00 | 0.146670E+11 | 0.118659E+11 | 41577.82 | 01-DEC-15:30 | 37135.02 | 0.00 |
Annual Sum or Average | 0.145329E+13 | 0.102503E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.804027E+10 | 0.657848E+10 | 37044.58 | 27745.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.223985E+12 | 0.152298E+12 | 257742.12 | 177041.15 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.499676E+10 | 0.447368E+10 | 10825.49 | 12-JAN-15:30 | 10019.67 | 0.00 |
February | 0.00 | 0.00 | 0.815531E+10 | 0.722617E+10 | 30662.02 | 23-FEB-05:02 | 27952.57 | 0.00 |
March | 0.00 | 0.00 | 0.158039E+11 | 0.140426E+11 | 37411.14 | 11-MAR-05:01 | 30697.91 | 0.00 |
April | 0.00 | 0.00 | 0.230023E+11 | 0.210611E+11 | 37727.69 | 17-APR-04:01 | 33231.52 | 0.00 |
May | 0.00 | 0.00 | 0.302739E+11 | 0.258285E+11 | 39628.99 | 24-MAY-04:01 | 25901.45 | 0.00 |
June | 0.00 | 0.00 | 0.320066E+11 | 0.252355E+11 | 40857.08 | 26-JUN-04:01 | 22459.39 | 0.00 |
July | 0.00 | 0.00 | 0.343596E+11 | 0.240472E+11 | 40994.40 | 20-JUL-04:01 | 22438.13 | 0.00 |
August | 0.00 | 0.00 | 0.337687E+11 | 0.228870E+11 | 40102.68 | 19-AUG-04:01 | 25350.92 | 0.00 |
September | 0.00 | 0.00 | 0.289758E+11 | 0.206780E+11 | 40465.74 | 03-SEP-06:01 | 23891.43 | 0.00 |
October | 0.00 | 0.00 | 0.237742E+11 | 0.203064E+11 | 38349.50 | 12-OCT-04:01 | 26172.83 | 0.00 |
November | 0.00 | 0.00 | 0.154110E+11 | 0.137905E+11 | 36340.00 | 09-NOV-05:01 | 32155.48 | 0.00 |
December | 0.00 | 0.00 | 0.704196E+10 | 0.626237E+10 | 11939.71 | 01-DEC-15:10 | 11449.28 | 0.00 |
Annual Sum or Average | 0.257570E+12 | 0.205839E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.499676E+10 | 0.447368E+10 | 10825.49 | 10019.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.343596E+11 | 0.258285E+11 | 40994.40 | 33231.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.294807E+10 | 0.261203E+10 | 8786.97 | 12-JAN-15:20 | 8033.98 | 0.00 |
February | 0.00 | 0.00 | 0.591558E+10 | 0.517711E+10 | 19652.24 | 23-FEB-05:02 | 17138.72 | 0.00 |
March | 0.00 | 0.00 | 0.128996E+11 | 0.112974E+11 | 33993.73 | 11-MAR-05:01 | 26965.18 | 0.00 |
April | 0.00 | 0.00 | 0.201106E+11 | 0.182393E+11 | 34241.29 | 17-APR-04:01 | 29437.32 | 0.00 |
May | 0.00 | 0.00 | 0.270898E+11 | 0.227863E+11 | 36029.79 | 24-MAY-04:01 | 22663.26 | 0.00 |
June | 0.00 | 0.00 | 0.285954E+11 | 0.220510E+11 | 37145.55 | 26-JUN-04:01 | 19385.67 | 0.00 |
July | 0.00 | 0.00 | 0.309733E+11 | 0.209692E+11 | 37299.95 | 20-JUL-04:01 | 19446.19 | 0.00 |
August | 0.00 | 0.00 | 0.303126E+11 | 0.197615E+11 | 36541.19 | 19-AUG-04:01 | 21909.19 | 0.00 |
September | 0.00 | 0.00 | 0.256966E+11 | 0.177346E+11 | 36804.73 | 03-SEP-06:01 | 20756.75 | 0.00 |
October | 0.00 | 0.00 | 0.207659E+11 | 0.174446E+11 | 34939.80 | 12-OCT-04:01 | 22469.15 | 0.00 |
November | 0.00 | 0.00 | 0.126268E+11 | 0.111345E+11 | 33074.81 | 09-NOV-05:01 | 27836.94 | 0.00 |
December | 0.00 | 0.00 | 0.459331E+10 | 0.401021E+10 | 10056.78 | 01-DEC-15:10 | 9561.38 | 0.00 |
Annual Sum or Average | 0.222528E+12 | 0.173218E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.294807E+10 | 0.261203E+10 | 8786.97 | 8033.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.309733E+11 | 0.227863E+11 | 37299.95 | 29437.32 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.174687E+10 | 0.38 | 1542.50 | 01-JAN-07:01 | 0.89 |
February | 0.599962E+09 | 0.14 | 1542.50 | 01-FEB-05:02 | 0.90 |
March | 86139252.37 | 0.02 | 1542.50 | 01-MAR-08:70 | 0.89 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 1388246.92 | 0.00 | 1542.50 | 28-OCT-07:09 | 0.89 |
November | 0.101785E+09 | 0.02 | 1542.50 | 01-NOV-07:08 | 0.89 |
December | 0.129210E+10 | 0.28 | 1542.50 | 01-DEC-08:70 | 0.90 |
Annual Sum or Average | 0.382824E+10 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.174687E+10 | 0.38 | 1542.50 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.220883E+10 | 0.35 | 3282.80 | 01-JAN-07:01 | 0.89 |
February | 0.193021E+10 | 0.33 | 3282.80 | 11-FEB-05:01 | 0.89 |
March | 0.215188E+10 | 0.33 | 3282.80 | 11-MAR-05:01 | 0.89 |
April | 0.214259E+10 | 0.35 | 3282.80 | 01-APR-04:01 | 0.89 |
May | 0.256412E+10 | 0.39 | 3282.80 | 01-MAY-04:01 | 0.90 |
June | 0.270828E+10 | 0.42 | 3282.80 | 01-JUN-04:01 | 0.89 |
July | 0.267096E+10 | 0.40 | 3282.80 | 01-JUL-04:01 | 0.89 |
August | 0.248414E+10 | 0.37 | 3282.80 | 01-AUG-04:01 | 0.89 |
September | 0.218304E+10 | 0.35 | 3282.80 | 01-SEP-04:01 | 0.89 |
October | 0.214506E+10 | 0.34 | 3282.80 | 01-OCT-06:01 | 0.89 |
November | 0.202870E+10 | 0.32 | 2235.95 | 01-NOV-04:01 | 0.74 |
December | 0.215490E+10 | 0.34 | 3282.80 | 21-DEC-05:02 | 0.90 |
Annual Sum or Average | 0.273727E+11 | 0.36 | |||
Minimum of Months | 0.193021E+10 | 0.32 | 2235.95 | 0.74 | |
Maximum of Months | 0.270828E+10 | 0.42 | 3282.80 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.102061E+11 | 0.51 | 15641.57 | 01-JAN-08:62 | 1.40 |
February | 0.912030E+10 | 0.51 | 12759.89 | 02-FEB-07:03 | 1.28 |
March | 0.102114E+11 | 0.52 | 15641.57 | 11-MAR-07:02 | 1.39 |
April | 0.102616E+11 | 0.53 | 15641.57 | 01-APR-06:02 | 1.40 |
May | 0.125017E+11 | 0.58 | 15641.57 | 01-MAY-05:01 | 1.40 |
June | 0.132725E+11 | 0.62 | 15641.57 | 01-JUN-05:03 | 1.39 |
July | 0.133125E+11 | 0.60 | 15641.57 | 01-JUL-04:01 | 1.39 |
August | 0.129045E+11 | 0.59 | 15641.57 | 01-AUG-05:02 | 1.38 |
September | 0.108359E+11 | 0.54 | 15641.57 | 01-SEP-05:02 | 1.39 |
October | 0.101060E+11 | 0.51 | 15641.57 | 01-OCT-07:01 | 1.39 |
November | 0.966276E+10 | 0.51 | 6284.29 | 27-NOV-07:10 | 0.85 |
December | 0.100842E+11 | 0.51 | 13184.31 | 23-DEC-07:03 | 1.30 |
Annual Sum or Average | 0.132479E+12 | 0.54 | |||
Minimum of Months | 0.912030E+10 | 0.51 | 6284.29 | 0.85 | |
Maximum of Months | 0.133125E+11 | 0.62 | 15641.57 | 1.40 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116714E+10 | 0.33 | 1801.47 | 01-JAN-07:01 | 0.89 |
February | 0.105120E+10 | 0.33 | 1510.30 | 23-FEB-05:02 | 0.83 |
March | 0.119544E+10 | 0.34 | 1801.47 | 07-MAR-05:01 | 0.89 |
April | 0.126600E+10 | 0.38 | 1801.47 | 01-APR-04:01 | 0.90 |
May | 0.149335E+10 | 0.44 | 1801.47 | 01-MAY-04:01 | 0.90 |
June | 0.153907E+10 | 0.45 | 1801.47 | 01-JUN-04:01 | 0.89 |
July | 0.153910E+10 | 0.43 | 1801.47 | 01-JUL-04:01 | 0.89 |
August | 0.149840E+10 | 0.41 | 1801.47 | 01-AUG-04:01 | 0.88 |
September | 0.136303E+10 | 0.39 | 1801.47 | 01-SEP-04:01 | 0.89 |
October | 0.127352E+10 | 0.36 | 1801.47 | 01-OCT-06:01 | 0.89 |
November | 0.112323E+10 | 0.33 | 1801.47 | 01-NOV-04:01 | 0.89 |
December | 0.115931E+10 | 0.33 | 898.56 | 23-DEC-06:03 | 0.62 |
Annual Sum or Average | 0.156688E+11 | 0.38 | |||
Minimum of Months | 0.105120E+10 | 0.33 | 898.56 | 0.62 | |
Maximum of Months | 0.153910E+10 | 0.45 | 1801.47 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.104951E+10 | 0.34 | 1601.87 | 01-JAN-07:01 | 0.89 |
February | 0.937138E+09 | 0.33 | 1601.87 | 11-FEB-05:01 | 0.89 |
March | 0.105921E+10 | 0.34 | 1601.87 | 07-MAR-05:01 | 0.89 |
April | 0.111649E+10 | 0.37 | 1601.87 | 01-APR-04:01 | 0.90 |
May | 0.131404E+10 | 0.42 | 1601.87 | 01-MAY-04:01 | 0.90 |
June | 0.134525E+10 | 0.43 | 1601.87 | 01-JUN-04:01 | 0.89 |
July | 0.135254E+10 | 0.41 | 1601.87 | 01-JUL-04:01 | 0.89 |
August | 0.131012E+10 | 0.39 | 1601.87 | 01-AUG-04:01 | 0.88 |
September | 0.119886E+10 | 0.38 | 1601.87 | 01-SEP-04:01 | 0.89 |
October | 0.112489E+10 | 0.36 | 1601.87 | 01-OCT-06:01 | 0.89 |
November | 0.995364E+09 | 0.33 | 1601.87 | 01-NOV-04:01 | 0.89 |
December | 0.103463E+10 | 0.33 | 1549.04 | 31-DEC-07:01 | 0.90 |
Annual Sum or Average | 0.138381E+11 | 0.37 | |||
Minimum of Months | 0.937138E+09 | 0.33 | 1549.04 | 0.88 | |
Maximum of Months | 0.135254E+10 | 0.43 | 1601.87 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 0.00 |
February | 0.22 | 0.00 |
March | 0.14 | 0.00 |
April | 0.74 | 0.00 |
May | 2.89 | 0.00 |
June | 2.81 | 0.00 |
July | 2.40 | 0.00 |
August | 1.74 | 0.00 |
September | 0.82 | 0.00 |
October | 0.40 | 0.00 |
November | 0.00 | 0.00 |
December | 0.33 | 0.00 |
Annual Sum or Average | 12.54 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.89 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.42 | 20.67 |
February | 0.08 | 0.00 |
March | 0.22 | 19.38 |
April | 0.34 | 0.00 |
May | 0.57 | 0.00 |
June | 0.64 | 0.00 |
July | 0.61 | 0.00 |
August | 0.86 | 0.00 |
September | 1.33 | 0.00 |
October | 0.83 | 18.18 |
November | 0.00 | 0.00 |
December | 0.36 | 5.96 |
Annual Sum or Average | 6.27 | 4.81 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.67 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.88 | 0.00 |
March | 2.73 | 0.00 |
April | 2.10 | 0.00 |
May | 2.55 | 0.00 |
June | 2.37 | 0.00 |
July | 2.00 | 0.00 |
August | 2.03 | 0.00 |
September | 2.32 | 0.00 |
October | 1.85 | 0.00 |
November | 2.06 | 0.00 |
December | 0.44 | 0.00 |
Annual Sum or Average | 21.33 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.73 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.18 | 0.00 |
March | 2.06 | 0.00 |
April | 1.89 | 0.00 |
May | 2.94 | 0.00 |
June | 2.75 | 0.00 |
July | 2.33 | 0.00 |
August | 1.90 | 0.00 |
September | 1.60 | 0.00 |
October | 1.81 | 0.00 |
November | 2.06 | 0.00 |
December | 0.14 | 0.00 |
Annual Sum or Average | 19.66 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.94 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 32.19 | 0.00 |
February | 19.60 | 0.00 |
March | 5.38 | 0.00 |
April | 2.94 | 0.00 |
May | 2.87 | 0.00 |
June | 2.42 | 0.00 |
July | 1.71 | 0.00 |
August | 0.67 | 0.00 |
September | 1.58 | 0.00 |
October | 1.78 | 0.00 |
November | 8.07 | 0.00 |
December | 28.38 | 0.00 |
Annual Sum or Average | 107.59 | 0.00 |
Minimum of Months | 0.67 | 0.00 |
Maximum of Months | 32.19 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.229052E+10 | 0.425320E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.294763E+10 | 0.826588E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.659881E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.115105E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.170873E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.181260E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.178101E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.162974E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.131186E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.941399E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.475250E+10 | 18334689.39 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.241403E+10 | 0.189428E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.122367E+12 | 0.699240E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.229052E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.181260E+11 | 0.425320E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.127053E+11 | 0.586564E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.177449E+11 | 0.662106E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.339332E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.517097E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.730209E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.777528E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.769488E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.733417E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.598548E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.439774E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.267663E+11 | 532005.27 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.146145E+11 | 0.123715E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.562370E+12 | 0.776543E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.127053E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.777528E+11 | 0.586564E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.244329E+10 | 0.559359E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.309919E+10 | 99205815.69 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.522694E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.756058E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.100711E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.104525E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.103982E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.991815E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.861941E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.726557E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.490594E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.293594E+10 | 0.104309E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.828969E+11 | 0.762874E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.244329E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.104525E+11 | 0.559359E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.181558E+10 | 0.100990E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.244633E+10 | 0.225932E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.438921E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.664604E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.898455E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.928419E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.929708E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.883189E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.763118E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.638561E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.413024E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.221390E+10 | 0.259782E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.720558E+11 | 0.149561E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.181558E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.929708E+10 | 0.100990E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.220883E+10 | 0.291113E+09 | 0.340256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193021E+10 | 0.364045E+10 | 0.661270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215188E+10 | 0.159060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214259E+10 | 0.327546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.256412E+10 | 0.502208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.270828E+10 | 0.539815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.267096E+10 | 0.570695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.248414E+10 | 0.538344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.218304E+10 | 0.420519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.214506E+10 | 0.264973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202870E+10 | 0.969207E+10 | 14667751.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.215490E+10 | 0.916842E+09 | 0.151542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273727E+11 | 0.346856E+12 | 0.559392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.193021E+10 | 0.291113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270828E+10 | 0.570695E+11 | 0.340256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.102061E+11 | 0.804027E+10 | 0.469251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.912030E+10 | 0.283356E+11 | 0.529685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102114E+11 | 0.785119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102616E+11 | 0.132222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125017E+11 | 0.190491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132725E+11 | 0.208918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133125E+11 | 0.223985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129045E+11 | 0.220238E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108359E+11 | 0.177064E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101060E+11 | 0.114346E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.966276E+10 | 0.564757E+11 | 425604.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100842E+11 | 0.146670E+11 | 0.989722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132479E+12 | 0.145329E+13 | 0.621235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.912030E+10 | 0.804027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133125E+11 | 0.223985E+12 | 0.469251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.116714E+10 | 0.499676E+10 | 0.447487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105120E+10 | 0.815531E+10 | 79364652.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119544E+10 | 0.158039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126600E+10 | 0.230023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149335E+10 | 0.302739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153907E+10 | 0.320066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153910E+10 | 0.343596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149840E+10 | 0.337687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136303E+10 | 0.289758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127352E+10 | 0.237742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112323E+10 | 0.154110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115931E+10 | 0.704196E+10 | 83447035.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156688E+11 | 0.257570E+12 | 0.610299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105120E+10 | 0.499676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153910E+10 | 0.343596E+11 | 0.447487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.104951E+10 | 0.294807E+10 | 0.807918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.937138E+09 | 0.591558E+10 | 0.180746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105921E+10 | 0.128996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111649E+10 | 0.201106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131404E+10 | 0.270898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134525E+10 | 0.285954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135254E+10 | 0.309733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131012E+10 | 0.303126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119886E+10 | 0.256966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112489E+10 | 0.207659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.995364E+09 | 0.126268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103463E+10 | 0.459331E+10 | 0.207826E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138381E+11 | 0.222528E+12 | 0.119649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.937138E+09 | 0.294807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135254E+10 | 0.309733E+11 | 0.807918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.220883E+10 | 0.00 | 0.00 | 0.00 | 81695480.82 | 0.00 | 0.425320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193021E+10 | 0.00 | 0.00 | 0.00 | 0.101742E+10 | 0.00 | 0.826588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215188E+10 | 0.00 | 0.00 | 0.00 | 0.444692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214259E+10 | 0.00 | 0.00 | 0.00 | 0.936795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.256412E+10 | 0.00 | 0.00 | 0.00 | 0.145232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.270828E+10 | 0.00 | 0.00 | 0.00 | 0.154177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.267096E+10 | 0.00 | 0.00 | 0.00 | 0.151392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.248414E+10 | 0.00 | 0.00 | 0.00 | 0.138132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.218304E+10 | 0.00 | 0.00 | 0.00 | 0.109356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.214506E+10 | 0.00 | 0.00 | 0.00 | 0.726892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202870E+10 | 0.00 | 0.00 | 0.00 | 0.272379E+10 | 0.00 | 18334689.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.215490E+10 | 0.00 | 0.00 | 0.00 | 0.259134E+09 | 0.00 | 0.189428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273727E+11 | 0.00 | 0.00 | 0.00 | 0.949946E+11 | 0.00 | 0.699240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.193021E+10 | 0.00 | 0.00 | 0.00 | 81695480.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270828E+10 | 0.00 | 0.00 | 0.00 | 0.154177E+11 | 0.00 | 0.425320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.102061E+11 | 0.00 | 0.00 | 0.00 | 0.249921E+10 | 0.00 | 0.586564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.912030E+10 | 0.00 | 0.00 | 0.00 | 0.862461E+10 | 0.00 | 0.662106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102114E+11 | 0.00 | 0.00 | 0.00 | 0.237217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102616E+11 | 0.00 | 0.00 | 0.00 | 0.414481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125017E+11 | 0.00 | 0.00 | 0.00 | 0.605192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132725E+11 | 0.00 | 0.00 | 0.00 | 0.644804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133125E+11 | 0.00 | 0.00 | 0.00 | 0.636363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129045E+11 | 0.00 | 0.00 | 0.00 | 0.604373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108359E+11 | 0.00 | 0.00 | 0.00 | 0.490189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101060E+11 | 0.00 | 0.00 | 0.00 | 0.338714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.966276E+10 | 0.00 | 0.00 | 0.00 | 0.171035E+11 | 0.00 | 532005.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100842E+11 | 0.00 | 0.00 | 0.00 | 0.453024E+10 | 0.00 | 0.123715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132479E+12 | 0.00 | 0.00 | 0.00 | 0.429891E+12 | 0.00 | 0.776543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.912030E+10 | 0.00 | 0.00 | 0.00 | 0.249921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133125E+11 | 0.00 | 0.00 | 0.00 | 0.644804E+11 | 0.00 | 0.586564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.116714E+10 | 0.00 | 0.00 | 0.00 | 0.127615E+10 | 0.00 | 0.559359E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105120E+10 | 0.00 | 0.00 | 0.00 | 0.204800E+10 | 0.00 | 99205815.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119544E+10 | 0.00 | 0.00 | 0.00 | 0.403150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126600E+10 | 0.00 | 0.00 | 0.00 | 0.629457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149335E+10 | 0.00 | 0.00 | 0.00 | 0.857780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153907E+10 | 0.00 | 0.00 | 0.00 | 0.891348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153910E+10 | 0.00 | 0.00 | 0.00 | 0.885915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149840E+10 | 0.00 | 0.00 | 0.00 | 0.841975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136303E+10 | 0.00 | 0.00 | 0.00 | 0.725638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127352E+10 | 0.00 | 0.00 | 0.00 | 0.599205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112323E+10 | 0.00 | 0.00 | 0.00 | 0.378271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115931E+10 | 0.00 | 0.00 | 0.00 | 0.177662E+10 | 0.00 | 0.104309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156688E+11 | 0.00 | 0.00 | 0.00 | 0.672282E+11 | 0.00 | 0.762874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.105120E+10 | 0.00 | 0.00 | 0.00 | 0.127615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153910E+10 | 0.00 | 0.00 | 0.00 | 0.891348E+10 | 0.00 | 0.559359E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.104951E+10 | 0.00 | 0.00 | 0.00 | 0.766069E+09 | 0.00 | 0.100990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.937138E+09 | 0.00 | 0.00 | 0.00 | 0.150919E+10 | 0.00 | 0.225932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105921E+10 | 0.00 | 0.00 | 0.00 | 0.332999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111649E+10 | 0.00 | 0.00 | 0.00 | 0.552955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131404E+10 | 0.00 | 0.00 | 0.00 | 0.767051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134525E+10 | 0.00 | 0.00 | 0.00 | 0.793894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135254E+10 | 0.00 | 0.00 | 0.00 | 0.794454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131012E+10 | 0.00 | 0.00 | 0.00 | 0.752177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119886E+10 | 0.00 | 0.00 | 0.00 | 0.643231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112489E+10 | 0.00 | 0.00 | 0.00 | 0.526072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.995364E+09 | 0.00 | 0.00 | 0.00 | 0.313487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103463E+10 | 0.00 | 0.00 | 0.00 | 0.117927E+10 | 0.00 | 0.259782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138381E+11 | 0.00 | 0.00 | 0.00 | 0.582177E+11 | 0.00 | 0.149561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.937138E+09 | 0.00 | 0.00 | 0.00 | 0.766069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135254E+10 | 0.00 | 0.00 | 0.00 | 0.794454E+10 | 0.00 | 0.100990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.267991E+10 | 0.00 | 0.00 | 312007.73 | 0.00 | 0.183263E+10 | 0.266235E+09 | 0.00 | 0.22 |
February | 0.139745E+10 | 23428557.98 | 0.00 | 3841811.46 | 0.00 | 0.455663E+09 | 0.848983E+09 | 0.00 | 0.22 |
March | 0.312693E+09 | 0.125465E+10 | 0.00 | 7237556.74 | 80605.26 | 0.00 | 0.519361E+09 | 0.00 | 0.23 |
April | 0.00 | 0.423582E+10 | 0.00 | 2157981.01 | 196733.25 | 0.00 | 19212470.98 | 0.00 | 0.23 |
May | 0.00 | 0.950414E+10 | 0.00 | 0.00 | 158521.60 | 0.00 | 0.00 | 0.00 | 0.23 |
June | 0.00 | 0.126745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
July | 0.00 | 0.160557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.162262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
September | 0.00 | 0.121245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
October | 4781502.02 | 0.423657E+10 | 0.00 | 2009862.59 | 375240.34 | 0.00 | 64292617.81 | 0.00 | 0.22 |
November | 0.654809E+09 | 0.444869E+09 | 0.00 | 5292912.65 | 0.00 | 7231241.99 | 0.665773E+09 | 0.00 | 0.22 |
December | 0.236733E+10 | 0.00 | 0.00 | 989373.51 | 0.00 | 0.119315E+10 | 0.772716E+09 | 0.00 | 0.22 |
Annual Sum or Average | 0.741697E+10 | 0.767803E+11 | 0.00 | 21841505.69 | 811100.45 | 0.348868E+10 | 0.315657E+10 | 0.00 | 0.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 0.267991E+10 | 0.162262E+11 | 0.00 | 7237556.74 | 375240.34 | 0.183263E+10 | 0.848983E+09 | 0.00 | 0.24 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.206204E+11 | 0.00 | 0.00 | 16462143.04 | 0.00 | 0.233163E+10 | 0.105633E+11 | 0.00 | 0.42 |
February | 0.913825E+10 | 0.571973E+09 | 0.00 | 34391924.35 | 0.00 | 69979352.04 | 0.802944E+10 | 0.00 | 0.43 |
March | 0.208310E+10 | 0.113350E+11 | 0.00 | 34095472.16 | 28292976.22 | 0.00 | 0.307783E+10 | 0.00 | 0.44 |
April | 79729168.61 | 0.335080E+11 | 0.00 | 5388180.01 | 0.324778E+09 | 0.00 | 0.127390E+09 | 0.00 | 0.43 |
May | 0.00 | 0.698294E+11 | 0.00 | 63960.41 | 0.589873E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.904247E+11 | 0.00 | 0.00 | 0.809591E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.111958E+12 | 0.00 | 0.00 | 0.104802E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.113037E+12 | 0.00 | 0.00 | 0.115553E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.841375E+11 | 0.00 | 0.00 | 0.124953E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.447687E+09 | 0.314018E+11 | 0.00 | 7692458.51 | 0.460535E+09 | 0.00 | 0.588925E+09 | 0.00 | 0.43 |
November | 0.447599E+10 | 0.565837E+10 | 0.00 | 31694704.57 | 0.00 | 0.00 | 0.427108E+10 | 0.00 | 0.43 |
December | 0.171189E+11 | 5326.79 | 0.00 | 27511764.84 | 0.00 | 0.287743E+09 | 0.113540E+11 | 0.00 | 0.42 |
Annual Sum or Average | 0.539641E+11 | 0.551862E+12 | 0.00 | 0.157301E+09 | 0.566615E+10 | 0.268935E+10 | 0.380120E+11 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.206204E+11 | 0.113037E+12 | 0.00 | 34391924.35 | 0.124953E+10 | 0.233163E+10 | 0.113540E+11 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104016E+10 | 0.00 | 0.00 | 9917021.02 | 0.00 | 0.269090E+09 | 0.165207E+10 | 0.00 | 0.42 |
February | 0.542991E+09 | 0.150566E+09 | 0.00 | 10172546.14 | 0.00 | 48305318.63 | 0.765482E+09 | 0.00 | 0.43 |
March | 80793932.08 | 0.137483E+10 | 0.00 | 6849967.54 | 314658.85 | 0.00 | 0.289612E+09 | 0.00 | 0.44 |
April | 0.00 | 0.352904E+10 | 0.00 | 1257107.44 | 478536.31 | 0.00 | 10304498.98 | 0.00 | 0.44 |
May | 0.00 | 0.732824E+10 | 0.00 | 29354.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.00 | 0.962193E+10 | 0.00 | 0.00 | 466328.18 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.121364E+11 | 0.00 | 0.00 | 1141226.25 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.123497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.946030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.383496E+10 | 0.00 | 1967895.82 | 0.00 | 0.00 | 20992924.76 | 0.00 | 0.44 |
November | 0.118877E+09 | 0.893354E+09 | 0.00 | 8788683.73 | 0.00 | 0.00 | 0.442863E+09 | 0.00 | 0.43 |
December | 0.827818E+09 | 8594840.56 | 0.00 | 12724660.83 | 0.00 | 55742824.50 | 0.142957E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.261064E+10 | 0.606879E+11 | 0.00 | 51707237.30 | 2400749.59 | 0.373138E+09 | 0.461089E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.104016E+10 | 0.123497E+11 | 0.00 | 12724660.83 | 1141226.25 | 0.269090E+09 | 0.165207E+10 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109969E+10 | 0.00 | 0.00 | 5793904.24 | 0.00 | 0.621062E+09 | 0.132588E+10 | 0.00 | 0.43 |
February | 0.673139E+09 | 0.118935E+09 | 0.00 | 7001000.65 | 0.00 | 0.108202E+09 | 0.662834E+09 | 0.00 | 0.43 |
March | 0.181390E+09 | 0.128615E+10 | 0.00 | 5183657.89 | 312680.41 | 0.00 | 0.237531E+09 | 0.00 | 0.44 |
April | 0.00 | 0.346730E+10 | 0.00 | 960074.91 | 94100.80 | 0.00 | 11999160.96 | 0.00 | 0.44 |
May | 0.00 | 0.719671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.940932E+10 | 0.00 | 0.00 | 771640.87 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.118588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.120332E+11 | 0.00 | 0.00 | 526775.49 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.914342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.370698E+10 | 0.00 | 1687024.54 | 0.00 | 0.00 | 30631483.97 | 0.00 | 0.44 |
November | 0.212504E+09 | 0.837306E+09 | 0.00 | 6702015.43 | 0.00 | 0.00 | 0.402234E+09 | 0.00 | 0.43 |
December | 0.993575E+09 | 4125086.96 | 0.00 | 8413327.28 | 0.00 | 0.152749E+09 | 0.129064E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.316029E+10 | 0.590623E+11 | 0.00 | 35741004.95 | 1705197.58 | 0.882013E+09 | 0.396175E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.109969E+10 | 0.120332E+11 | 0.00 | 8413327.28 | 771640.87 | 0.621062E+09 | 0.132588E+10 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |