Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2020-06-03 19:11:31
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1546.13 | 673.99 | 673.99 |
Net Site Energy | 1546.13 | 673.99 | 673.99 |
Total Source Energy | 4257.03 | 1855.73 | 1855.73 |
Net Source Energy | 4257.03 | 1855.73 | 1855.73 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 209.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 65.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 492.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 114.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 371.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 97.12 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1239.09 | 307.04 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 209.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 65.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 492.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 114.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 371.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 97.12 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 264.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 190.53 | 133.85 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 540.15 | 133.85 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 264.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 190.53 | 133.85 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 540.15 | 133.85 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1239.090 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1239.090 | 100.00 |
Total On-Site and Utility Electric Sources | 1239.090 | 100.00 |
Total Electricity End Uses | 1239.090 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 979.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 8.56 |
Skylight-Roof Ratio [%] | 0.37 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 9.0309 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 18.2986 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 18.2986 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 18.2986 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 13.9931 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.7414 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.7414 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-14:00 | 16-JAN-09:09 | - | - | - | 13-SEP-11:09 |
Heating | 0.00 | 143881.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 40300.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 34564.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18078.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1862.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 103714.45 | 145743.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 143881.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 40300.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 34564.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 18078.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1862.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 227.55 | 0.00 | 0.00 | 0.00 |
Cooling | 207.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1558.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 363.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1177.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 105.28 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3924.20 | 332.83 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 99.19 | 0.00 | 0.00 | 0.00 |
Cooling | 90.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 679.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 513.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 45.89 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1710.64 | 145.09 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 99.19 | 0.00 | 0.00 | 0.00 |
Cooling | 90.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 679.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 513.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 45.89 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1710.64 | 145.09 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.66 |
CORE_RETAIL DIRECT AIR | 7.61 |
POINT_OF_SALE DIRECT AIR | 1.30 |
FRONT_RETAIL DIRECT AIR | 1.08 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 1.67 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 1.67 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 38256.89 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 44726.37 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 230385.12 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 34978.51 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 29854.20 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.66 | 1.66 | 1.66 | 1.66 | 1.71 | 1.71 | 1.00 | 0.969030 | 1.71 |
PSZ-AC:2 | 7.61 | 7.61 | 7.61 | 7.61 | 7.84 | 7.84 | 1.00 | 0.971418 | 7.84 |
PSZ-AC:3 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.00 | 1.30 |
PSZ-AC:4 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.00 | 1.08 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.71 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 7.84 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.30 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 1.08 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.71 | 1.71 | 1.71 | 1.71 | 30092.59 | 44726.37 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.84 | 7.84 | 7.84 | 7.84 | 140390.02 | 230385.12 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 1.30 | 21614.65 | 34978.51 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 1.08 | 18242.96 | 29854.20 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.71 | 0.856365 | 1.71 | 28351.76 | 30092.59 | 15046.30 | 30092.59 | 0.777387 | 0.777390 | 0.777390 | 0.777390 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 7.84 | 3.92 | 7.84 | 130313.23 | 140390.02 | 70195.01 | 140390.02 | 0.770719 | 0.770720 | 0.770720 | 0.770720 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.30 | 0.650795 | 1.30 | 21545.94 | 21614.65 | 10807.33 | 21614.65 | 0.797486 | 0.797490 | 0.797490 | 0.797490 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.08 | 0.538300 | 1.08 | 17821.55 | 18242.96 | 9121.48 | 18242.96 | 0.790163 | 0.790160 | 0.790160 | 0.790160 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.71 | 1874.59 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.84 | 13492.50 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.30 | 1483.95 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.08 | 1227.45 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 65 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 6.69 | 10 | 14 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 9.031 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.101 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 18.299 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 21.529 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 18.299 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 39.819 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 18.299 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 21.529 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 13.993 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.993 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 3430.757 | 9.031 | 55.928 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3430.757 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 29286.673 | 18.299 | 113.324 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29286.673 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2759.619 | 18.299 | 113.324 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2759.619 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2759.619 | 18.299 | 113.324 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2759.619 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 167.917 | 13.993 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 167.917 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.6478 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.376 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8390000 | 2.8390000 | 2.8390000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 9 | 0.49119318E-15 | -0.33550344E-15 | -0.16284357E-09 | -0.12303907E-16 |
25 | 8 | 0.23714982E-07 | 0.88106564E-13 | 0.39686193E-03 | -0.26964751E-09 |
26 | 7 | -0.12809687E-01 | 0.44996568E-08 | -0.23903550E-01 | 0.14565082E-03 |
27 | 6 | 0.42078637 | 0.15559313E-05 | 0.48521577 | -0.49297162E-02 |
28 | 5 | -5.3411857 | 0.57794581E-04 | -4.5419698 | 0.65051509E-01 |
29 | 4 | 33.669005 | 0.47055528E-03 | 21.833772 | -0.43096765 |
30 | 3 | -112.64328 | 0.10212385E-02 | -56.401742 | 1.5356680 |
31 | 2 | 198.53538 | 0.57229644E-03 | 78.588493 | -2.9230166 |
32 | 1 | -171.68312 | 0.60883279E-04 | -55.462911 | 2.7546764 |
33 | 0 | 57.057407 | 0.34515708E-06 | 15.524833 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.51_SHGC_0.4 | 30 | 1 | VerySmooth | 2.899 | 0.395 | 0.315 | 0.401 |
2 | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | 31 | 1 | VerySmooth | 5.779 | 0.490 | 0.326 | 0.491 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.82741E-002 | 0.31435 | 0.46434 | 0.46434 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10459 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.32532 | 0.12431 | 0.12431 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.727 | 0.1878 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
31 | SKYLIGHTS_R2C4 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
32 | SKYLIGHTS_R2C1 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
33 | SKYLIGHTS_R2C2 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
34 | SKYLIGHTS_R2C3 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C3 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C1 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C2 | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
39 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
40 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
42 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
43 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
44 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
45 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
46 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
47 | POINT_OF_SALE_ROOF | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
48 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
49 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
50 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
52 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
54 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | FRONT_RETAIL_ROOF | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
58 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
59 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
60 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
62 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
63 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
64 | FRONT_ENTRY_ROOF | 0 | 2292.12 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
65 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.448 | 1.180E-003 | 5.356E-004 | 0.697 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.367 | 2.293E-004 | 1.864E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 2.497E-002 | 2.080E-003 | 6.862E-004 | 1.228 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 19400.55562 | 23280.66674 | 1.38307 | 1.65968 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 20861.76375 | 25034.11650 | 0.88829 | 1.06594 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 88706.92812 | 106448.31375 | 6.34380 | 7.61256 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 51075.21652 | 61290.25982 | 2.13672 | 2.56406 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 14570.52046 | 17484.62455 | 1.08466 | 1.30159 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.79438E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 10232.73072 | 12279.27686 | 0.43771 | 0.52525 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 12051.87792 | 14462.25350 | 0.89717 | 1.07660 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.79438E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 10228.23938 | 12273.88726 | 0.43751 | 0.52501 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40000 | 8.79438E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 31855.26819 | 38226.32183 | 1.38894 | 1.66673 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 22617.04 | 1.71273 | 1.71273 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 31206.94 | 1.06594 | 1.06594 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 110565.29 | 7.83654 | 7.83654 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 115046.57 | 2.56406 | 2.56406 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 18326.19 | 1.30159 | 1.30159 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 17296.42 | 0.52525 | 0.52525 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 15354.88 | 1.07660 | 1.07660 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 17291.07 | 0.52501 | 0.52501 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.65968 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.61256 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.30159 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07660 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.66673 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.66673 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 38256.89372 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.65968 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.65968 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.65968 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.65968 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.71273 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.71273 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.96903 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.61256 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.61256 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.61256 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.61256 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.83654 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.83654 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97142 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.30159 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.30159 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.30159 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.30159 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.30159 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.30159 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07660 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07660 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07660 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07660 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07660 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07660 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.71273 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.83654 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.30159 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.07660 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.71273 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.71273 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.71273 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.71273 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.71273 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.71273 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.85637 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.71273 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 28351.76295 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 30092.59000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 15046.29500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 30092.59000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.77739 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.77739 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.77739 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.77739 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30092.59000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 44726.37461 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.71273 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1874.58892 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 44726.37461 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.83654 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.83654 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.83654 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.83654 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.83654 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.83654 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.91827 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 7.83654 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 130313.22933 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 140390.02000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 70195.01000 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 140390.02000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.77072 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.77072 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.77072 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.77072 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 140390.02000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 230385.11556 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.83654 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 13492.50292 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 230385.11556 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.30159 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.30159 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.30159 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.30159 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.30159 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.30159 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65080 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.30159 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21545.93610 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21614.65000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10807.32500 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 21614.65000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79749 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79749 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79749 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79749 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21614.65000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34978.51264 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.30159 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1483.95385 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 34978.51264 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07660 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07660 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07660 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07660 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.07660 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07660 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53830 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.07660 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17821.55272 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18242.96000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9121.48000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 18242.96000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79016 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79016 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79016 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79016 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18242.96000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29854.19554 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07660 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1227.44604 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29854.19554 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 28749.2 | 10.12 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 134241.8 | 11.52 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 20594.5 | 89.41 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 17399.0 | 127.62 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 25 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1591.92 | 1600.48 | 1593.79 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
32 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
33 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
34 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | N/A | 5.779 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
40 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
56 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
57 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
58 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | |
1 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C4 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
2 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C1 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
3 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C2 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
4 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C3 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
5 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C3 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
6 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C1 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
7 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C4 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A | |||
8 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C2 | Window5 Detailed Fenestration | N/A | N/A | 0.23 | 0.23 | * | N/A | N/A | 6.00E-002 | N/A |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 11 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 8.6507849343E-002 | 0.3463987801 | Pass | Pass | 4.4505794482E-002 | 0.1675893799 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 4.3264534579E-002 | 0.1908970962 | Pass | Pass | 0.2170248484 | 1.0334321047 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 9.1067450104E-002 | 0.4016384150 | Pass | Pass | 8.0543231625E-002 | 0.2193964276 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 9.9058980921E-002 | 0.4245355733 | Pass | Pass | 4.3848367679E-002 | 0.1737827349 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1637243346 | 0.5441646446 | Pass | Pass | 0.1267793894 | 0.5354697093 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 1600.48 | 1591.92 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.490 | 0.491 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.490 | 0.491 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.490 | 0.491 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.490 | 0.491 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.490 | 0.491 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.490 | 0.491 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.490 | 0.491 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.49 | 0.84 | 0.23 | 0.00 | 1.07 | 1.07 | 5.779 | 0.490 | 0.491 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.51_SHGC_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.899 | 0.395 | 0.401 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.51_SHGC_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.899 | 0.395 | 0.401 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.51_SHGC_0.4 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.899 | 0.395 | 0.401 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 92.49 | 3.166 | 0.403 | 0.409 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 92.49 | 3.166 | 0.403 | 0.409 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 9.0309 | 379.89 | 3430.76 | LightsWired | BLDG_LIGHT_BACK_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 43.96 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 18.2986 | 1600.48 | 29286.67 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 375.23 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 18.2986 | 150.81 | 2759.62 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 35.36 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 18.2986 | 150.81 | 2759.62 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 35.36 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 13.9931 | 12.00 | 167.92 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 2.15 |
Interior Lighting Total | 16.7414 | 2293.99 | 38404.58 | 492.05 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7321.52 | AstronomicalClock | - | 83.55 | 83.55 | 114.82 | |
Exterior Lighting Total | 7321.52 | 114.82 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 30092.59 | 23393.68 | 6698.91 | 0.78 | 3.50 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 140390.02 | 108201.40 | 32188.62 | 0.77 | 3.23 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 21614.65 | 17237.47 | 4377.18 | 0.80 | 3.50 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18242.96 | 14414.86 | 3828.10 | 0.79 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 28749.2 | 10.12 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 134241.8 | 11.52 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 20594.5 | 89.41 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 17399.0 | 127.62 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 38256.89 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 44726.37 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 230385.12 | 0.79 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 34978.51 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29854.20 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.57 | 622.50 | 1.67 | 1824.24 | 1094.51 | 1.00 | 1.30 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.71 | 1874.59 | 1094.51 | 1.00 | 1.31 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.59 | 1018.41 | 7.84 | 13492.50 | 1721.74 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.30 | 1483.95 | 1140.11 | 1.00 | 1.30 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.08 | 1227.45 | 1140.11 | 1.00 | 1.34 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 19400.56 | 23280.67 | 61.28 | 1.383 | 1.660 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00989 | 21.70 | 0.00879 | 0.232 | 0.00 |
CORE_RETAIL | 88706.93 | 106448.31 | 66.51 | 6.344 | 7.613 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00968 | 21.70 | 0.00879 | 1.890 | 0.00 |
POINT_OF_SALE | 14570.52 | 17484.62 | 115.94 | 1.085 | 1.302 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 23.89 | 23.89 | 0.00887 | 29.05 | 0.00879 | 0.178 | 0.00 |
FRONT_RETAIL | 12051.88 | 14462.25 | 95.90 | 0.897 | 1.077 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 23.89 | 23.89 | 0.00895 | 29.14 | 0.00879 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.64 | 100.00 | 0.00001 | 29.40 | 0.00879 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 20861.76 | 25034.12 | 65.90 | 0.888 | 1.066 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00734 | -4.20 | 0.00269 | 0.232 | 0.00 |
CORE_RETAIL | 51075.22 | 61290.26 | 38.29 | 2.137 | 2.564 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00729 | -4.20 | 0.00269 | 1.890 | 0.00 |
POINT_OF_SALE | 10232.73 | 12279.28 | 81.42 | 0.438 | 0.525 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00755 | -4.20 | 0.00269 | 0.178 | 0.00 |
FRONT_RETAIL | 10228.24 | 12273.89 | 81.39 | 0.438 | 0.525 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00755 | -4.20 | 0.00269 | 0.178 | 0.00 |
FRONT_ENTRY | 31855.27 | 38226.32 | 3185.53 | 1.389 | 1.667 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.04 | 0.00575 | -4.20 | 0.00269 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.71 | 1.71 | 1.07 | 1.07 | 1.7127 | 1.6597 | 1.7127 | 0.9690 | 1.0000 |
PSZ-AC:2 | 7.84 | 7.84 | 2.56 | 2.56 | 7.8365 | 7.6126 | 7.8365 | 0.9714 | 1.0000 |
PSZ-AC:3 | 1.30 | 1.30 | 0.53 | 0.53 | 1.3016 | 1.3016 | 1.3016 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.08 | 1.08 | 0.53 | 0.53 | 1.0766 | 1.0766 | 1.0766 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 38256.894 | 38256.894 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 38256.89 | 38256.89 | 1.666728 | 20.82 | 12.47 | 0.00572567 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.04 | 0.00575170 | 36.7015 | 38226.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 30092.590 | 0.000 | 1.712730 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 30092.59 | 26662.20 | 1.712730 | 24.69 | 17.04 | 0.00918611 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 13.5203 | 23.89 | 0.00988720 | 52.7115 | 19400.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 44726.375 | 44726.375 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 44726.37 | 44726.37 | 1.712727 | 15.45 | 10.86 | 0.00632684 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 13.5203 | 21.11 | 0.00733609 | 46.4890 | 20861.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 140390.020 | 0.000 | 7.836540 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 140390.02 | 126990.72 | 7.836540 | 25.29 | 17.17 | 0.00908794 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 24.1205 | 23.89 | 0.00967649 | 51.6049 | 83066.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 230385.116 | 230385.116 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 230385.12 | 230385.12 | 7.836545 | 2.38 | 1.48 | 0.00389848 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 24.1205 | 21.11 | 0.00728751 | 46.1823 | 51075.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 21614.650 | 0.000 | 1.301590 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 21614.65 | 20241.01 | 1.301590 | 24.61 | 16.74 | 0.00885971 | 12.80 | 11.97 | 0.00850000 | 29.14 | 0.00879438 | 18.22 | 13.6841 | 23.89 | 0.00886992 | 47.3560 | 14567.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 34978.513 | 34978.513 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 34978.51 | 34978.51 | 1.301588 | 12.39 | 9.06 | 0.00590109 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 13.6841 | 21.11 | 0.00754848 | 47.8176 | 10232.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 18242.960 | 0.000 | 1.076600 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 18242.96 | 16914.18 | 1.076600 | 24.77 | 16.85 | 0.00892156 | 12.80 | 11.97 | 0.00850000 | 29.23 | 0.00879438 | 18.24 | 16.5438 | 23.89 | 0.00894637 | 47.7584 | 12051.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 29854.196 | 29854.196 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29854.20 | 29854.20 | 1.076603 | 12.39 | 9.05 | 0.00590003 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 16.5437 | 21.11 | 0.00754800 | 47.8146 | 10228.24 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 38256.894 | 38256.894 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 1.666728 | 1.97839073 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 38256.89 | 38256.89 | 1.0000 | 1.97839073 | 1.666728 | 20.82 | 12.47 | 0.00572567 | 35463.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38256.89 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.05 | 0.00575170 | 21.04 | 0.00575170 | 36.7015 | 38226.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30092.590 | 0.000 | 1.712730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9165 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 30092.59 | 26662.20 | 1.0000 | 2.03299472 | 1.712730 | 24.69 | 17.04 | 0.00918611 | 48203.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30092.59 | 29.40 | 0.00879438 | 18.30 | 0.23156651 | 13.5203 | 23.89 | 0.00925264 | 23.89 | 0.00988720 | 52.7115 | 19400.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 44726.375 | 44726.375 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.712727 | 2.03299096 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 44726.37 | 44726.37 | 1.0000 | 2.03299096 | 1.712727 | 15.45 | 10.86 | 0.00632684 | 31534.5 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44726.37 | -4.20 | 0.00269032 | -4.20 | 0.23156651 | 13.5203 | 20.91 | 0.00733609 | 21.11 | 0.00733609 | 46.4890 | 20861.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 140390.020 | 0.000 | 7.836540 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7340 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 140390.02 | 126990.72 | 1.0000 | 9.30190075 | 7.836540 | 25.29 | 17.17 | 0.00908794 | 48570.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 140390.02 | 29.40 | 0.00879438 | 18.30 | 1.89021192 | 24.1205 | 23.89 | 0.00918828 | 23.89 | 0.00967649 | 51.6049 | 83066.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 230385.116 | 230385.116 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.836545 | 9.30190632 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 230385.12 | 230385.12 | 1.0000 | 9.30190632 | 7.836545 | 2.38 | 1.48 | 0.00389848 | 12160.9 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 230385.12 | -4.20 | 0.00269032 | -4.20 | 1.89021192 | 24.1205 | 20.85 | 0.00728751 | 21.11 | 0.00728751 | 46.1823 | 51075.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21614.650 | 0.000 | 1.301590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3098 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 21614.65 | 20241.01 | 1.0000 | 1.54497533 | 1.301590 | 24.61 | 16.74 | 0.00885971 | 47289.0 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21614.65 | 29.14 | 0.00879438 | 18.22 | 0.17811053 | 13.6841 | 23.89 | 0.00887007 | 23.89 | 0.00886992 | 47.3560 | 14567.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34978.513 | 34978.513 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.301588 | 1.54497348 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 34978.51 | 34978.51 | 1.0000 | 1.54497348 | 1.301588 | 12.39 | 9.06 | 0.00590109 | 27345.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34978.51 | -4.20 | 0.00269032 | -4.20 | 0.17811053 | 13.6841 | 20.90 | 0.00754848 | 21.11 | 0.00754848 | 47.8176 | 10232.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18242.960 | 0.000 | 1.076600 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4247 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 18242.96 | 16914.18 | 1.0000 | 1.27791428 | 1.076600 | 24.77 | 16.85 | 0.00892156 | 47615.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18242.96 | 29.23 | 0.00879438 | 18.24 | 0.17811053 | 16.5438 | 23.89 | 0.00894681 | 23.89 | 0.00894637 | 47.7584 | 12051.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29854.196 | 29854.196 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.076603 | 1.27791816 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29854.20 | 29854.20 | 1.0000 | 1.27791816 | 1.076603 | 12.39 | 9.05 | 0.00590003 | 27339.3 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29854.20 | -4.20 | 0.00269032 | -4.20 | 0.17811053 | 16.5437 | 20.90 | 0.00754800 | 21.11 | 0.00754800 | 47.8146 | 10228.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.71 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 1.89 | 7.84 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.30 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 1304.17 | 3714.50 | 948.50 |
CORE_RETAIL | 1333.33 | 2624.50 | 209.17 |
POINT_OF_SALE | 1551.50 | 2610.83 | 383.00 |
FRONT_RETAIL | 1599.50 | 3119.00 | 685.67 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 2245.17 | 3724.00 | 979.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 31.33 | 0.17 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 21.33 | 0.00 | 0.00 |
POINT_OF_SALE | 15.67 | 11.33 | 0.00 | 0.00 |
FRONT_RETAIL | 27.83 | 2.17 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 33.00 | 33.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.37 | 61.34 | 2317.33 | 0.688 | 0.049 | 0.000 | 0.000 |
CORE_RETAIL | 127.94 | 258.43 | 9762.95 | 1.082 | 0.009 | 0.000 | 0.000 |
POINT_OF_SALE | 12.06 | 24.35 | 919.94 | 1.563 | 0.053 | 0.000 | 0.000 |
FRONT_RETAIL | 12.06 | 24.35 | 919.94 | 0.709 | 0.053 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.37 | 61.34 | 2317.33 | 0.355 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 127.94 | 258.43 | 9762.95 | 0.687 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.06 | 24.35 | 919.94 | 0.687 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.06 | 24.35 | 919.94 | 0.687 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 11 | 11 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1239.09 | 3715.40 | 05-MAR-06:50 | 103714.45 | 29-AUG-15:00 |
Electricity:Building | 687.20 | 3715.40 | 01-JAN-00:10 | 45335.16 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 93.95 | 631.39 | 01-JAN-00:10 | 5846.82 | 02-JAN-09:10 |
InteriorLights:Electricity | 492.05 | 1920.23 | 01-JAN-00:10 | 34564.13 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 43.96 | 171.54 | 01-JAN-00:10 | 3087.68 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 492.05 | 1920.23 | 01-JAN-00:10 | 34564.13 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 459.53 | 2239.77 | 01-JAN-00:10 | 31010.61 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 375.23 | 1464.33 | 01-JAN-00:10 | 26358.01 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 88.28 | 624.80 | 01-JAN-00:10 | 5404.55 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 35.36 | 137.98 | 01-JAN-00:10 | 2483.66 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 43.30 | 211.05 | 01-JAN-00:10 | 2922.06 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 35.36 | 137.98 | 01-JAN-00:10 | 2483.66 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 2.15 | 8.40 | 01-JAN-00:10 | 151.13 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 2.15 | 8.40 | 01-JAN-00:10 | 151.13 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1239.09 | 3715.40 | 19-MAR-18:10 | 103714.45 | 29-AUG-15:00 |
ElectricityPurchased:Plant | 1239.09 | 3715.40 | 19-MAR-18:10 | 103714.45 | 29-AUG-15:00 |
Cogeneration:ElectricityPurchased | 1239.09 | 3715.40 | 19-MAR-18:10 | 103714.45 | 29-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1239.09 | 3715.40 | 19-MAR-18:10 | 103714.45 | 29-AUG-15:00 |
ElectricityNet:Plant | 1239.09 | 3715.40 | 19-MAR-18:10 | 103714.45 | 29-AUG-15:00 |
Cogeneration:ElectricityNet | 1239.09 | 3715.40 | 19-MAR-18:10 | 103714.45 | 29-AUG-15:00 |
Electricity:HVAC | 437.06 | 0.00 | 01-JAN-00:10 | 58379.29 | 29-AUG-15:00 |
Fans:Electricity | 371.66 | 0.00 | 01-JAN-00:10 | 19902.73 | 01-JAN-13:40 |
General:Fans:Electricity | 371.66 | 0.00 | 01-JAN-00:10 | 19902.73 | 01-JAN-13:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 65.40 | 0.00 | 01-JAN-00:10 | 40300.80 | 29-AUG-15:00 |
ExteriorLights:Electricity | 114.82 | 0.00 | 01-JAN-08:10 | 7321.52 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 114.82 | 0.00 | 01-JAN-08:10 | 7321.52 | 01-JAN-00:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 307.04 | 1862.00 | 02-APR-10:10 | 145743.09 | 16-JAN-09:10 |
Gas:Plant | 97.12 | 1862.00 | 11-JAN-05:10 | 5102.55 | 14-FEB-12:10 |
WaterSystems:Gas | 97.12 | 1862.00 | 11-JAN-05:10 | 5102.55 | 14-FEB-12:10 |
Water Heater:WaterSystems:Gas | 97.12 | 1862.00 | 11-JAN-05:10 | 5102.55 | 14-FEB-12:10 |
Gas:HVAC | 209.92 | 0.00 | 01-JAN-00:10 | 143881.09 | 16-JAN-09:10 |
Heating:Gas | 209.92 | 0.00 | 01-JAN-00:10 | 143881.09 | 16-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1024.76 | 0.00 | 01-JAN-00:10 | 210174.54 | 10-AUG-14:30 |
EnergyTransfer:Building | 635.61 | 0.00 | 01-JAN-00:10 | 91799.81 | 16-JAN-09:10 |
EnergyTransfer:Zone:BACK_SPACE | 64.42 | 0.00 | 01-JAN-00:10 | 40022.93 | 19-FEB-07:10 |
Heating:EnergyTransfer | 127.38 | 0.00 | 01-JAN-00:10 | 89588.30 | 19-FEB-08:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 20.31 | 0.00 | 01-JAN-00:10 | 40022.93 | 19-FEB-07:10 |
Cooling:EnergyTransfer | 508.22 | 0.00 | 01-JAN-00:10 | 82978.03 | 06-JUL-20:20 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 44.11 | 0.00 | 01-JAN-00:10 | 14435.90 | 21-JUN-20:50 |
EnergyTransfer:Zone:CORE_RETAIL | 387.47 | 0.00 | 01-JAN-00:10 | 78246.63 | 03-JUN-21:40 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 13.65 | 0.00 | 01-JAN-00:10 | 58497.84 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 373.83 | 0.00 | 01-JAN-00:10 | 78246.63 | 03-JUN-21:40 |
EnergyTransfer:Zone:POINT_OF_SALE | 62.08 | 0.00 | 01-JAN-00:10 | 17732.24 | 19-FEB-07:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 4.88 | 0.00 | 01-JAN-00:10 | 17732.24 | 19-FEB-07:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 57.21 | 0.00 | 01-JAN-00:10 | 11067.33 | 26-APR-20:20 |
EnergyTransfer:Zone:FRONT_RETAIL | 41.43 | 0.00 | 01-JAN-00:10 | 17737.10 | 19-FEB-07:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 8.35 | 0.00 | 01-JAN-00:10 | 17737.10 | 19-FEB-07:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 33.08 | 0.00 | 01-JAN-00:10 | 8658.29 | 04-OCT-14:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 80.20 | 0.00 | 01-JAN-00:10 | 26223.35 | 18-FEB-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 80.20 | 0.00 | 01-JAN-00:10 | 26223.35 | 18-FEB-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 99.79 | 25-DEC-07:10 |
EnergyTransfer:HVAC | 389.16 | 0.00 | 01-JAN-00:10 | 130928.77 | 10-AUG-14:30 |
HeatingCoils:EnergyTransfer | 167.41 | 0.00 | 01-JAN-00:10 | 114365.01 | 16-JAN-09:10 |
CoolingCoils:EnergyTransfer | 221.74 | 0.00 | 01-JAN-00:10 | 130928.77 | 10-AUG-14:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 20.314 | -44.108 | 0.000 | 0.000 | 39.181 | 43.956 | 49.992 | 0.000 | 0.000 | 0.074 | 0.004 | 0.000 | 0.000 | 0.000 | -25.928 | -83.480 |
CORE_RETAIL | 0.000 | 0.000 | 13.645 | -373.823 | 0.000 | 0.000 | 162.971 | 375.227 | 84.299 | 10.008 | 0.000 | 0.061 | 0.006 | 0.000 | -9.940 | 0.000 | -23.584 | -238.864 |
POINT_OF_SALE | 0.000 | 0.000 | 4.876 | -57.206 | 0.000 | 0.000 | 15.108 | 35.357 | 52.922 | 28.730 | 0.000 | 0.033 | 0.001 | 0.000 | -22.973 | 0.000 | -11.931 | -44.916 |
FRONT_RETAIL | 0.000 | 0.000 | 8.349 | -33.081 | 0.000 | 0.000 | 15.554 | 35.357 | 7.943 | 28.980 | 0.000 | 0.032 | 0.002 | 0.000 | -21.941 | 0.000 | -11.294 | -29.900 |
FRONT_ENTRY | 80.198 | -0.003 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.151 | 0.000 | 5.938 | 0.000 | 0.008 | 0.708 | 0.000 | -4.413 | 0.000 | -84.588 | -0.000 |
Total Facility | 80.198 | -0.003 | 47.185 | -508.218 | 0.000 | 0.000 | 232.814 | 492.048 | 195.156 | 73.656 | 0.000 | 0.208 | 0.721 | 0.000 | -59.266 | 0.000 | -157.326 | -397.161 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 07-JUL-20:36 | 0.00 | 0.00 | 0.00 | -30782.45 | 0.00 | 0.00 | 0.00 | 686.15 | 613.14 | 0.00 | 0.00 | 0.00 | 29988.23 | 0.00 | -0.00 | 0.00 | -505.07 | 0.00 |
CORE_RETAIL | 04-OCT-20:33 | 0.00 | 0.00 | 0.00 | -162396.72 | 0.00 | 0.00 | 0.00 | 5857.33 | 1033.91 | 0.00 | 0.00 | 0.00 | 156842.13 | 0.00 | -511.51 | 0.00 | -825.13 | 0.00 |
POINT_OF_SALE | 04-OCT-20:10 | 0.00 | 0.00 | 0.00 | -24679.69 | 0.00 | 0.00 | 0.00 | 551.92 | 649.09 | 0.00 | 0.00 | 0.00 | 24830.17 | 0.00 | -971.93 | 0.00 | -379.56 | 0.00 |
FRONT_RETAIL | 25-JUN-18:20 | 0.00 | 0.00 | 0.00 | -16861.58 | 0.00 | 0.00 | 0.00 | 137.98 | 73.07 | 162.33 | 0.00 | 0.00 | 16724.14 | 0.00 | -0.00 | 0.00 | -235.94 | 0.00 |
FRONT_ENTRY | 25-DEC-07:02 | 0.00 | -997.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 1285.26 | 0.00 | -295.80 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-JUL-20:11 | 0.00 | 0.00 | 0.00 | -172722.55 | 0.00 | 0.00 | 0.00 | 7680.92 | 2393.56 | 0.00 | 0.00 | 0.00 | 166020.23 | 0.00 | -1938.58 | 0.00 | -1433.57 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 19-FEB-07:11 | 0.00 | 0.00 | 46192.63 | 0.00 | 0.00 | 0.00 | 0.00 | 171.54 | 459.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4963.91 | -41860.11 |
CORE_RETAIL | 16-JAN-08:62 | 0.00 | 0.00 | 232371.04 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.33 | 775.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -610.49 | 0.00 | -560.65 | -233439.66 |
POINT_OF_SALE | 19-FEB-07:11 | 0.00 | 0.00 | 35492.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.98 | 486.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1986.80 | 0.00 | -2295.69 | -31834.31 |
FRONT_RETAIL | 27-NOV-05:01 | 0.00 | 0.00 | 28777.59 | 0.00 | 0.00 | 0.00 | 0.00 | 137.98 | 97.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -582.39 | 0.00 | -817.89 | -27612.71 |
FRONT_ENTRY | 18-FEB-18:00 | 26222.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.13 | 0.00 | 0.00 | 0.00 | 0.00 | 39.08 | 0.00 | -382.45 | 0.00 | -26029.95 | 0.00 |
Total Facility | 19-FEB-08:62 | 4798.78 | 0.00 | 278204.69 | 0.00 | 0.00 | 0.00 | 0.00 | 1920.23 | 1795.17 | 843.91 | 0.00 | 0.00 | 0.00 | 0.00 | -699.80 | 0.00 | -7720.40 | -279142.58 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.6597 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.7127 | 0.1352 | 1.0000 | 0.2316 | 0.1352 | ||
PSZ-AC:2 | 7.6126 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.8365 | 0.2412 | 1.0000 | 1.8902 | 0.2412 | ||
PSZ-AC:3 | 1.3016 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.3016 | 0.1368 | 1.0000 | 0.1781 | 0.1368 | ||
PSZ-AC:4 | 1.0766 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0766 | 0.1654 | 1.0000 | 0.1781 | 0.1654 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.6597 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.6597 | 1.0000 | 1.0000 | 0.2316 | 0.1395 | ||
PSZ-AC:2 | 7.6126 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.6126 | 1.0000 | 1.0000 | 1.8902 | 0.2483 | ||
PSZ-AC:3 | 1.3016 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.3016 | 1.0000 | 1.0000 | 0.1781 | 0.1368 | ||
PSZ-AC:4 | 1.0766 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0766 | 1.0000 | 1.0000 | 0.1781 | 0.1654 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.6597 | 1.6597 | 1.6597 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.6126 | 7.6126 | 7.6126 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.3016 | 1.3016 | 1.3016 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0766 | 1.0766 | 1.0766 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.6597 | 1.7127 | 1.6597 | 1.6597 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.6126 | 7.8365 | 7.6126 | 7.6126 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.3016 | 1.3016 | 1.3016 | 1.3016 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0766 | 1.0766 | 1.0766 | 1.0766 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.6597 | 1.6597 | 1.6597 | 0.2316 | 0.2172 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.6126 | 7.6126 | 7.6126 | 1.8902 | 0.7372 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.3016 | 1.3016 | 1.3016 | 0.1781 | 0.3391 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0766 | 1.0766 | 1.0766 | 0.1781 | 0.3393 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.6597 | 1.6597 | 1.6597 | 1.6597 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.6126 | 7.6126 | 7.6126 | 7.6126 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.3016 | 1.3016 | 1.3016 | 1.3016 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0766 | 1.0766 | 1.0766 | 1.0766 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 209.92 | 143881.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 65.40 | 40300.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 492.05 | 34564.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 114.82 | 7321.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 371.66 | 19902.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 97.12 | 5102.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1239.09 |
Natural Gas | 0.00 | 307.04 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1546.13 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 214.49 |
Space Heating | 0.00 |
Space Cooling | 28.51 |
Fans (All) | 162.02 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 540.15 |
Subtotal | 540.15 |
Natural Gas [MJ/m2] | |
Space Heating | 91.51 |
Service Water Heating | 42.34 |
Miscellaneous (All) | 133.85 |
Subtotal | 133.85 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 31.82 |
Space Heating | 13.58 |
Space Cooling | 4.23 |
Fans (All) | 24.04 |
Service Water Heating | 6.28 |
Receptacle Equipment | 12.62 |
Miscellaneous | 7.43 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3609. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_SETBACK | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_SCH_PSZ_AC_2 | CORE_RETAIL DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.609370E+11 |
February | 0.000 | 0.398838E+11 |
March | 0.000 | 0.166300E+11 |
April | 0.000 | 0.757780E+10 |
May | 0.000 | 0.350600E+10 |
June | 0.000 | 0.123319E+10 |
July | 0.000 | 0.299115E+09 |
August | 0.000 | 0.150333E+09 |
September | 0.000 | 0.174988E+10 |
October | 0.000 | 0.570578E+10 |
November | 0.000 | 0.244288E+11 |
December | 0.000 | 0.478154E+11 |
Annual Sum or Average | 0.209917E+12 | |
Minimum of Months | 0.000 | 0.150333E+09 |
Maximum of Months | 0.000 | 0.609370E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.609370E+11 |
February | 0.000 | 0.398838E+11 |
March | 0.000 | 0.166300E+11 |
April | 0.000 | 0.757780E+10 |
May | 0.000 | 0.350600E+10 |
June | 0.000 | 0.123319E+10 |
July | 0.000 | 0.299115E+09 |
August | 0.000 | 0.150333E+09 |
September | 0.000 | 0.174988E+10 |
October | 0.000 | 0.570578E+10 |
November | 0.000 | 0.244288E+11 |
December | 0.000 | 0.478154E+11 |
Annual Sum or Average | 0.209917E+12 | |
Minimum of Months | 0.000 | 0.150333E+09 |
Maximum of Months | 0.000 | 0.609370E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2007
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.609370E+11 |
February | 0.000 | 0.398838E+11 |
March | 0.000 | 0.166300E+11 |
April | 0.000 | 0.757780E+10 |
May | 0.000 | 0.350600E+10 |
June | 0.000 | 0.123319E+10 |
July | 0.000 | 0.299115E+09 |
August | 0.000 | 0.150333E+09 |
September | 0.000 | 0.174988E+10 |
October | 0.000 | 0.570578E+10 |
November | 0.000 | 0.244288E+11 |
December | 0.000 | 0.478154E+11 |
Annual Sum or Average | 0.209917E+12 | |
Minimum of Months | 0.000 | 0.150333E+09 |
Maximum of Months | 0.000 | 0.609370E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.609370E+11 |
February | 0.000 | 0.398838E+11 |
March | 0.000 | 0.166300E+11 |
April | 0.000 | 0.757780E+10 |
May | 0.000 | 0.350600E+10 |
June | 0.000 | 0.123319E+10 |
July | 0.000 | 0.299115E+09 |
August | 0.000 | 0.150333E+09 |
September | 0.000 | 0.174988E+10 |
October | 0.000 | 0.570578E+10 |
November | 0.000 | 0.244288E+11 |
December | 0.000 | 0.478154E+11 |
Annual Sum or Average | 0.209917E+12 | |
Minimum of Months | 0.000 | 0.150333E+09 |
Maximum of Months | 0.000 | 0.609370E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.609370E+11 |
February | 0.000 | 0.398838E+11 |
March | 0.000 | 0.166300E+11 |
April | 0.000 | 0.757780E+10 |
May | 0.000 | 0.350600E+10 |
June | 0.000 | 0.123319E+10 |
July | 0.000 | 0.299115E+09 |
August | 0.000 | 0.150333E+09 |
September | 0.000 | 0.174988E+10 |
October | 0.000 | 0.570578E+10 |
November | 0.000 | 0.244288E+11 |
December | 0.000 | 0.478154E+11 |
Annual Sum or Average | 0.209917E+12 | |
Minimum of Months | 0.000 | 0.150333E+09 |
Maximum of Months | 0.000 | 0.609370E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.609370E+11 |
February | 0.000 | 0.398838E+11 |
March | 0.000 | 0.166300E+11 |
April | 0.000 | 0.757780E+10 |
May | 0.000 | 0.350600E+10 |
June | 0.000 | 0.123319E+10 |
July | 0.000 | 0.299115E+09 |
August | 0.000 | 0.150333E+09 |
September | 0.000 | 0.174988E+10 |
October | 0.000 | 0.570578E+10 |
November | 0.000 | 0.244288E+11 |
December | 0.000 | 0.478154E+11 |
Annual Sum or Average | 0.209917E+12 | |
Minimum of Months | 0.000 | 0.150333E+09 |
Maximum of Months | 0.000 | 0.609370E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.609370E+11 |
February | 0.000 | 0.398838E+11 |
March | 0.000 | 0.166300E+11 |
April | 0.000 | 0.757780E+10 |
May | 0.000 | 0.350600E+10 |
June | 0.000 | 0.123319E+10 |
July | 0.000 | 0.299115E+09 |
August | 0.000 | 0.150333E+09 |
September | 0.000 | 0.174988E+10 |
October | 0.000 | 0.570578E+10 |
November | 0.000 | 0.244288E+11 |
December | 0.000 | 0.478154E+11 |
Annual Sum or Average | 0.209917E+12 | |
Minimum of Months | 0.000 | 0.150333E+09 |
Maximum of Months | 0.000 | 0.609370E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.609370E+11 |
February | 0.000 | 0.398838E+11 |
March | 0.000 | 0.166300E+11 |
April | 0.000 | 0.757780E+10 |
May | 0.000 | 0.350600E+10 |
June | 0.000 | 0.123319E+10 |
July | 0.000 | 0.299115E+09 |
August | 0.000 | 0.150333E+09 |
September | 0.000 | 0.174988E+10 |
October | 0.000 | 0.570578E+10 |
November | 0.000 | 0.244288E+11 |
December | 0.000 | 0.478154E+11 |
Annual Sum or Average | 0.209917E+12 | |
Minimum of Months | 0.000 | 0.150333E+09 |
Maximum of Months | 0.000 | 0.609370E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.609370E+11 |
February | 0.000 | 0.398838E+11 |
March | 0.000 | 0.166300E+11 |
April | 0.000 | 0.757780E+10 |
May | 0.000 | 0.350600E+10 |
June | 0.000 | 0.123319E+10 |
July | 0.000 | 0.299115E+09 |
August | 0.000 | 0.150333E+09 |
September | 0.000 | 0.174988E+10 |
October | 0.000 | 0.570578E+10 |
November | 0.000 | 0.244288E+11 |
December | 0.000 | 0.478154E+11 |
Annual Sum or Average | 0.209917E+12 | |
Minimum of Months | 0.000 | 0.150333E+09 |
Maximum of Months | 0.000 | 0.609370E+11 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.530320E+09 | 3247.45 | 07-JAN-13:00 | 0.60 | 0.14 | 0.165888E+10 | 2112.92 | 11-JAN-15:00 | 14.40 | 10.48 |
February | 0.738715E+09 | 2921.87 | 17-FEB-12:30 | 1.95 | 0.91 | 0.157876E+10 | 2451.25 | 27-FEB-15:09 | 19.90 | 12.20 |
March | 0.169653E+10 | 2727.01 | 22-MAR-10:40 | 4.63 | 3.96 | 0.193530E+10 | 2451.22 | 18-MAR-13:50 | 19.53 | 10.60 |
April | 0.241321E+10 | 7042.54 | 27-APR-15:00 | 27.20 | 17.27 | 0.199935E+10 | 2451.25 | 29-APR-13:09 | 20.18 | 14.71 |
May | 0.447794E+10 | 8025.55 | 15-MAY-15:00 | 23.30 | 12.59 | 0.218608E+10 | 2451.31 | 04-MAY-14:20 | 24.07 | 15.16 |
June | 0.641701E+10 | 28871.79 | 21-JUN-20:45 | 18.07 | 12.84 | 0.219170E+10 | 2451.32 | 26-JUN-14:00 | 20.60 | 14.39 |
July | 0.838883E+10 | 30784.73 | 07-JUL-20:36 | 20.20 | 12.89 | 0.218569E+10 | 2451.32 | 22-JUL-14:09 | 24.60 | 16.62 |
August | 0.882690E+10 | 28897.36 | 08-AUG-22:31 | 21.07 | 14.03 | 0.227893E+10 | 2451.34 | 09-AUG-14:09 | 28.42 | 18.30 |
September | 0.559430E+10 | 27481.05 | 13-SEP-20:49 | 18.40 | 14.97 | 0.214265E+10 | 2451.31 | 09-SEP-13:09 | 20.68 | 14.49 |
October | 0.263413E+10 | 5691.45 | 04-OCT-15:00 | 21.70 | 11.47 | 0.205830E+10 | 2451.23 | 16-OCT-14:00 | 13.90 | 10.27 |
November | 0.158789E+10 | 4644.42 | 04-NOV-14:30 | 21.10 | 15.93 | 0.175063E+10 | 2451.28 | 04-NOV-15:00 | 20.00 | 15.90 |
December | 0.802696E+09 | 2523.51 | 30-DEC-17:00 | 5.60 | 4.80 | 0.167012E+10 | 2056.89 | 30-DEC-16:10 | 8.35 | 6.85 |
Annual Sum or Average | 0.441085E+11 | 0.236364E+11 | ||||||||
Minimum of Months | 0.530320E+09 | 2523.51 | 0.60 | 0.14 | 0.157876E+10 | 2056.89 | 8.35 | 6.85 | ||
Maximum of Months | 0.882690E+10 | 30784.73 | 27.20 | 17.27 | 0.227893E+10 | 2451.34 | 28.42 | 18.30 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162667E+11 | 36286.30 | 16-JAN-09:07 | -0.5 | -2.1 | 0.707949E+10 | 10172.28 | 11-JAN-15:00 | 14.40 | 10.48 |
February | 0.167426E+11 | 31982.97 | 20-FEB-09:07 | 1.47 | -0.2 | 0.690287E+10 | 10327.14 | 25-FEB-11:00 | 15.00 | 12.12 |
March | 0.248594E+11 | 36557.99 | 01-MAR-07:03 | -0.1 | -1.6 | 0.873154E+10 | 10326.95 | 08-MAR-15:09 | 15.18 | 11.29 |
April | 0.288904E+11 | 144025.07 | 27-APR-21:13 | 16.27 | 11.35 | 0.876870E+10 | 10327.52 | 27-APR-14:09 | 26.28 | 16.89 |
May | 0.379235E+11 | 153347.15 | 14-MAY-20:05 | 16.28 | 10.33 | 0.931836E+10 | 10327.16 | 08-MAY-14:00 | 17.80 | 14.19 |
June | 0.438662E+11 | 156493.26 | 03-JUN-21:35 | 15.77 | 9.34 | 0.925930E+10 | 10327.57 | 26-JUN-14:50 | 20.60 | 14.29 |
July | 0.494995E+11 | 149464.10 | 05-JUL-20:20 | 15.40 | 10.60 | 0.921202E+10 | 10327.74 | 22-JUL-14:30 | 25.00 | 16.77 |
August | 0.508169E+11 | 147138.92 | 14-AUG-23:41 | 17.58 | 12.13 | 0.960547E+10 | 10327.61 | 09-AUG-14:39 | 28.17 | 18.40 |
September | 0.383205E+11 | 142364.34 | 04-SEP-19:10 | 15.82 | 12.07 | 0.905236E+10 | 10327.70 | 29-SEP-14:00 | 20.00 | 14.17 |
October | 0.274590E+11 | 162399.93 | 04-OCT-20:33 | 15.00 | 9.61 | 0.893793E+10 | 10327.13 | 14-OCT-11:09 | 11.88 | 9.04 |
November | 0.213594E+11 | 32590.34 | 11-NOV-09:03 | 0.78 | 0.55 | 0.760966E+10 | 10327.18 | 04-NOV-11:00 | 18.90 | 15.18 |
December | 0.178209E+11 | 34455.00 | 26-DEC-07:07 | -1.6 | -1.6 | 0.720278E+10 | 9772.50 | 02-DEC-14:50 | 11.78 | 5.55 |
Annual Sum or Average | 0.373825E+12 | 0.101680E+12 | ||||||||
Minimum of Months | 0.162667E+11 | 31982.97 | -1.6 | -2.1 | 0.690287E+10 | 9772.50 | 11.78 | 5.55 | ||
Maximum of Months | 0.508169E+11 | 162399.93 | 17.58 | 12.13 | 0.960547E+10 | 10327.74 | 28.17 | 18.40 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187207E+10 | 3844.76 | 20-JAN-13:30 | 6.70 | 4.71 | 0.707809E+09 | 973.09 | 11-JAN-15:09 | 14.40 | 10.48 |
February | 0.228260E+10 | 6489.67 | 27-FEB-15:10 | 19.90 | 12.20 | 0.698467E+09 | 973.10 | 25-FEB-11:00 | 15.00 | 12.12 |
March | 0.341717E+10 | 7004.87 | 18-MAR-13:50 | 19.53 | 10.60 | 0.859046E+09 | 973.10 | 11-MAR-12:20 | 11.30 | 9.96 |
April | 0.432062E+10 | 22134.66 | 26-APR-20:15 | 17.40 | 11.43 | 0.833689E+09 | 973.16 | 29-APR-15:20 | 21.47 | 14.97 |
May | 0.539445E+10 | 21283.82 | 14-MAY-18:11 | 21.47 | 11.71 | 0.877962E+09 | 973.17 | 05-MAY-14:30 | 24.40 | 16.78 |
June | 0.615746E+10 | 23278.28 | 27-JUN-22:11 | 17.43 | 12.73 | 0.872402E+09 | 973.17 | 26-JUN-14:00 | 20.60 | 14.39 |
July | 0.767887E+10 | 22788.20 | 19-JUL-20:11 | 17.93 | 12.64 | 0.868208E+09 | 973.20 | 01-JUL-14:09 | 20.00 | 14.38 |
August | 0.886121E+10 | 22870.77 | 14-AUG-22:51 | 18.00 | 12.37 | 0.905314E+09 | 973.19 | 25-AUG-14:30 | 26.90 | 18.77 |
September | 0.736986E+10 | 21928.59 | 10-SEP-18:41 | 19.60 | 13.46 | 0.854365E+09 | 973.22 | 09-SEP-14:09 | 21.20 | 15.01 |
October | 0.505028E+10 | 24678.66 | 04-OCT-20:10 | 16.65 | 10.40 | 0.853611E+09 | 973.12 | 07-OCT-15:50 | 16.97 | 12.09 |
November | 0.267913E+10 | 9002.57 | 04-NOV-14:00 | 21.10 | 15.93 | 0.762320E+09 | 973.14 | 04-NOV-11:09 | 17.98 | 14.86 |
December | 0.212236E+10 | 5116.36 | 05-DEC-12:40 | 10.40 | 6.14 | 0.736248E+09 | 973.10 | 02-DEC-11:39 | 11.83 | 6.01 |
Annual Sum or Average | 0.572061E+11 | 0.982944E+10 | ||||||||
Minimum of Months | 0.187207E+10 | 3844.76 | 6.70 | 4.71 | 0.698467E+09 | 973.09 | 11.30 | 6.01 | ||
Maximum of Months | 0.886121E+10 | 24678.66 | 21.47 | 15.93 | 0.905314E+09 | 973.22 | 26.90 | 18.77 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.631638E+09 | 3095.61 | 07-JAN-13:10 | 0.97 | 0.44 | 0.662182E+09 | 884.12 | 11-JAN-15:09 | 14.40 | 10.48 |
February | 0.109379E+10 | 4148.63 | 27-FEB-15:10 | 19.90 | 12.20 | 0.642103E+09 | 973.12 | 28-FEB-15:30 | 13.90 | 10.69 |
March | 0.186386E+10 | 4547.42 | 01-MAR-15:10 | 13.12 | 7.27 | 0.787346E+09 | 973.12 | 10-MAR-15:30 | 15.85 | 11.52 |
April | 0.239725E+10 | 7073.01 | 27-APR-13:30 | 26.10 | 16.53 | 0.790745E+09 | 973.13 | 27-APR-14:00 | 27.20 | 17.27 |
May | 0.299124E+10 | 16515.40 | 14-MAY-18:18 | 21.47 | 11.71 | 0.853542E+09 | 973.14 | 02-MAY-14:20 | 17.07 | 12.42 |
June | 0.357237E+10 | 16861.72 | 25-JUN-18:20 | 21.13 | 13.22 | 0.862283E+09 | 973.15 | 26-JUN-14:00 | 20.60 | 14.39 |
July | 0.476191E+10 | 15893.21 | 23-JUL-18:41 | 24.68 | 15.73 | 0.864448E+09 | 973.17 | 31-JUL-14:00 | 28.30 | 18.89 |
August | 0.580971E+10 | 16839.37 | 14-AUG-23:41 | 17.58 | 12.13 | 0.901901E+09 | 973.16 | 29-AUG-14:09 | 29.90 | 19.92 |
September | 0.472058E+10 | 16037.47 | 10-SEP-18:41 | 19.60 | 13.46 | 0.843072E+09 | 973.17 | 15-SEP-14:50 | 22.62 | 16.74 |
October | 0.298489E+10 | 14284.73 | 04-OCT-20:11 | 16.10 | 10.14 | 0.810702E+09 | 973.13 | 07-OCT-10:20 | 14.27 | 10.89 |
November | 0.137991E+10 | 6427.71 | 04-NOV-14:00 | 21.10 | 15.93 | 0.684233E+09 | 973.13 | 02-NOV-14:00 | 13.30 | 11.18 |
December | 0.873378E+09 | 2934.53 | 06-DEC-12:00 | 3.30 | 3.23 | 0.680684E+09 | 973.10 | 05-DEC-15:09 | 9.35 | 6.61 |
Annual Sum or Average | 0.330805E+11 | 0.938324E+10 | ||||||||
Minimum of Months | 0.631638E+09 | 2934.53 | 0.97 | 0.44 | 0.642103E+09 | 884.12 | 9.35 | 6.61 | ||
Maximum of Months | 0.580971E+10 | 16861.72 | 26.10 | 16.53 | 0.901901E+09 | 973.17 | 29.90 | 19.92 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1119815.12 | 930.23 | 14-JAN-05:02 | 2.20 | 1.44 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 620526.68 | 990.00 | 21-FEB-05:02 | 1.70 | 0.78 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 132528.36 | 677.72 | 06-MAR-05:02 | 6.70 | 6.18 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 30344.35 | 332.06 | 11-APR-04:02 | 5.10 | 4.28 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 | 13.74 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 | 13.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 226311.91 | 578.03 | 24-NOV-05:02 | 2.70 | 2.03 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 816521.04 | 997.85 | 25-DEC-07:02 | -0.7 | -0.7 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 2946047.46 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -0.7 | -0.7 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 1119815.12 | 997.85 | 17.17 | 13.74 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.582389E+10 | 46054.12 | 21-JAN-05:42 | 0.60 |
February | 0.419534E+10 | 46192.70 | 19-FEB-07:11 | -5.0 |
March | 0.190180E+10 | 45768.88 | 06-MAR-05:42 | 6.70 |
April | 0.796543E+09 | 45533.08 | 11-APR-04:01 | 5.10 |
May | 0.229102E+09 | 44009.08 | 18-MAY-04:02 | 6.52 |
June | 0.163847E+09 | 2155.65 | 14-JUN-05:02 | 10.00 |
July | 0.115882E+09 | 1820.21 | 19-JUL-05:01 | 11.57 |
August | 96727329.64 | 1849.53 | 20-AUG-07:25 | 14.20 |
September | 0.171269E+09 | 1897.81 | 28-SEP-05:45 | 8.30 |
October | 0.380356E+09 | 45113.86 | 30-OCT-04:01 | 7.20 |
November | 0.201981E+10 | 45696.07 | 24-NOV-05:42 | 2.30 |
December | 0.441962E+10 | 45825.56 | 22-DEC-05:42 | 0.60 |
Annual Sum or Average | 0.203142E+11 | |||
Minimum of Months | 96727329.64 | 1820.21 | -5.0 | |
Maximum of Months | 0.582389E+10 | 46192.70 | 14.20 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340941E+10 | 232371.02 | 16-JAN-08:62 | -1.0 |
February | 0.219052E+10 | 232194.05 | 21-FEB-06:02 | 1.70 |
March | 0.139180E+10 | 20836.42 | 07-MAR-07:20 | 7.03 |
April | 0.105942E+10 | 14029.84 | 28-APR-05:04 | 11.10 |
May | 0.448095E+09 | 15059.71 | 05-MAY-05:03 | 12.98 |
June | 0.110475E+09 | 15063.87 | 21-JUN-05:03 | 12.88 |
July | 0.143414E+09 | 15619.46 | 20-JUL-05:03 | 13.40 |
August | 0.148623E+09 | 15471.13 | 01-AUG-05:03 | 11.30 |
September | 0.152643E+09 | 15527.60 | 13-SEP-05:03 | 12.80 |
October | 0.897205E+09 | 13535.64 | 16-OCT-05:53 | 6.70 |
November | 0.140987E+10 | 36400.89 | 28-NOV-07:13 | 3.90 |
December | 0.228400E+10 | 196761.75 | 26-DEC-06:03 | -0.8 |
Annual Sum or Average | 0.136455E+11 | |||
Minimum of Months | 0.110475E+09 | 13535.64 | -1.0 | |
Maximum of Months | 0.340941E+10 | 232371.02 | 13.40 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144779E+10 | 34950.77 | 15-JAN-07:01 | -3.4 |
February | 0.837309E+09 | 35492.05 | 19-FEB-07:11 | -5.0 |
March | 0.375891E+09 | 34910.57 | 06-MAR-05:01 | 6.70 |
April | 0.210310E+09 | 34903.24 | 11-APR-04:01 | 5.10 |
May | 0.125879E+09 | 13588.43 | 18-MAY-04:02 | 6.52 |
June | 74596108.50 | 1470.31 | 14-JUN-05:53 | 10.00 |
July | 27756363.39 | 1724.37 | 24-JUL-05:04 | 15.87 |
August | 29248279.64 | 1748.47 | 15-AUG-05:03 | 13.05 |
September | 46923239.61 | 1683.96 | 10-SEP-07:03 | 12.57 |
October | 0.137915E+09 | 18372.74 | 28-OCT-04:02 | 7.88 |
November | 0.477635E+09 | 34931.49 | 24-NOV-05:01 | 2.70 |
December | 0.108431E+10 | 34931.61 | 27-DEC-05:01 | 4.50 |
Annual Sum or Average | 0.487556E+10 | |||
Minimum of Months | 27756363.39 | 1470.31 | -5.0 | |
Maximum of Months | 0.144779E+10 | 35492.05 | 15.87 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255394E+10 | 28106.15 | 11-JAN-05:01 | 10.00 |
February | 0.150853E+10 | 28489.79 | 24-FEB-05:01 | 13.90 |
March | 0.749715E+09 | 27967.40 | 08-MAR-05:01 | 10.00 |
April | 0.344824E+09 | 27329.05 | 11-APR-04:01 | 5.10 |
May | 55434837.87 | 26692.65 | 18-MAY-04:02 | 6.52 |
June | 4304340.02 | 6595.57 | 14-JUN-05:02 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 86816.67 | 110.76 | 29-AUG-07:13 | 18.83 |
September | 79095.67 | 470.50 | 27-SEP-05:03 | 7.38 |
October | 0.132000E+09 | 27020.67 | 28-OCT-04:02 | 7.88 |
November | 0.938610E+09 | 28777.27 | 27-NOV-05:01 | 12.12 |
December | 0.206179E+10 | 28432.48 | 16-DEC-05:01 | 10.10 |
Annual Sum or Average | 0.834931E+10 | |||
Minimum of Months | 0.00 | 0.00 | 5.10 | |
Maximum of Months | 0.255394E+10 | 28777.27 | 18.83 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141799E+11 | 25787.75 | 07-JAN-12:10 | -0.4 |
February | 0.108035E+11 | 26223.35 | 18-FEB-18:00 | -0.6 |
March | 0.899820E+10 | 19036.45 | 05-MAR-12:10 | 5.10 |
April | 0.599741E+10 | 16150.16 | 18-APR-17:00 | 7.20 |
May | 0.423653E+10 | 14522.40 | 23-MAY-17:00 | 8.30 |
June | 0.212847E+10 | 11565.40 | 13-JUN-11:07 | 11.28 |
July | 0.907658E+09 | 8462.44 | 12-JUL-11:05 | 13.98 |
August | 0.666906E+09 | 8250.58 | 01-AUG-11:05 | 13.62 |
September | 0.266536E+10 | 11308.68 | 16-SEP-11:05 | 11.78 |
October | 0.597319E+10 | 13456.82 | 31-OCT-17:00 | 9.40 |
November | 0.104516E+11 | 21510.64 | 12-NOV-18:00 | 3.30 |
December | 0.131897E+11 | 25758.71 | 26-DEC-12:10 | 0.27 |
Annual Sum or Average | 0.801984E+11 | |||
Minimum of Months | 0.666906E+09 | 8250.58 | -0.6 | |
Maximum of Months | 0.141799E+11 | 26223.35 | 13.98 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.368607E+10 | 3087.68 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.335384E+10 | 3087.68 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.382564E+10 | 3087.68 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.360950E+10 | 3087.68 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.375586E+10 | 3087.68 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.369163E+10 | 3087.68 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.367372E+10 | 3087.68 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.382564E+10 | 3087.68 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.360950E+10 | 3087.68 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.368607E+10 | 3087.68 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.356442E+10 | 3087.68 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.367372E+10 | 3087.68 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.439556E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.335384E+10 | 3087.68 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.382564E+10 | 3087.68 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.314662E+11 | 26358.01 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.286301E+11 | 26358.01 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.326576E+11 | 26358.01 | 01-MAR-09:09 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.308125E+11 | 26358.01 | 01-APR-09:09 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.320619E+11 | 26358.01 | 01-MAY-08:09 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.315136E+11 | 26358.01 | 01-JUN-08:09 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.313608E+11 | 26358.01 | 01-JUL-09:09 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.326576E+11 | 26358.01 | 01-AUG-08:09 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.308125E+11 | 26358.01 | 01-SEP-08:09 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.314662E+11 | 26358.01 | 02-OCT-08:09 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.304277E+11 | 26358.01 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.313608E+11 | 26358.01 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.375227E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.286301E+11 | 26358.01 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.326576E+11 | 26358.01 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.296499E+10 | 2483.66 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.269775E+10 | 2483.66 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.307725E+10 | 2483.66 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.290340E+10 | 2483.66 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.302112E+10 | 2483.66 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.296946E+10 | 2483.66 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.295506E+10 | 2483.66 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.307725E+10 | 2483.66 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.290340E+10 | 2483.66 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.296499E+10 | 2483.66 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.286713E+10 | 2483.66 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.295506E+10 | 2483.66 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.353568E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.269775E+10 | 2483.66 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.307725E+10 | 2483.66 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.296499E+10 | 2483.66 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.269775E+10 | 2483.66 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.307725E+10 | 2483.66 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.290340E+10 | 2483.66 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.302112E+10 | 2483.66 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.296946E+10 | 2483.66 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.295506E+10 | 2483.66 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.307725E+10 | 2483.66 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.290340E+10 | 2483.66 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.296499E+10 | 2483.66 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.286713E+10 | 2483.66 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.295506E+10 | 2483.66 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.353568E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.269775E+10 | 2483.66 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.307725E+10 | 2483.66 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.180413E+09 | 151.13 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.164152E+09 | 151.13 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.187244E+09 | 151.13 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.176665E+09 | 151.13 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.183829E+09 | 151.13 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.180685E+09 | 151.13 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.179809E+09 | 151.13 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.187244E+09 | 151.13 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.176665E+09 | 151.13 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.180413E+09 | 151.13 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.174459E+09 | 151.13 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.179809E+09 | 151.13 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.215139E+10 | ||||
Minimum of Months | 0.164152E+09 | 151.13 | 0.00 | 0.00 | |
Maximum of Months | 0.187244E+09 | 151.13 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.368607E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312000E+10 |
February | 0.479114E+10 | 0.335384E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265488E+10 |
March | 0.548013E+10 | 0.382564E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268990E+10 |
April | 0.518069E+10 | 0.360950E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3954660.78 | 0.256068E+10 |
May | 0.536353E+10 | 0.375586E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 256690.99 | 0.211492E+10 |
June | 0.528933E+10 | 0.369163E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2205697.70 | 0.174296E+10 |
July | 0.525489E+10 | 0.367372E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23552570.68 | 0.138875E+10 |
August | 0.548013E+10 | 0.382564E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44028994.39 | 0.121883E+10 |
September | 0.518069E+10 | 0.360950E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 243812.82 | 0.999653E+09 |
October | 0.524694E+10 | 0.368607E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226635E+10 |
November | 0.504819E+10 | 0.356442E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255970E+10 |
December | 0.525489E+10 | 0.367372E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261157E+10 |
Annual Sum or Average | 0.628175E+11 | 0.439556E+11 | 0.499918E+11 | 74242427.36 | 0.259282E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.335384E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999653E+09 |
Maximum of Months | 0.548013E+10 | 0.382564E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44028994.39 | 0.312000E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.314662E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279714E+10 |
February | 0.201852E+11 | 0.286301E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240135E+10 |
March | 0.230879E+11 | 0.326576E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253047E+10 |
April | 0.218263E+11 | 0.308125E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3237268.10 | 0.241911E+10 |
May | 0.225967E+11 | 0.320619E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 210287.01 | 0.194397E+10 |
June | 0.222841E+11 | 0.315136E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1805892.51 | 0.155823E+10 |
July | 0.221389E+11 | 0.313608E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19312309.28 | 0.119451E+10 |
August | 0.230879E+11 | 0.326576E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36109903.76 | 0.103584E+10 |
September | 0.218263E+11 | 0.308125E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 199623.01 | 0.888249E+09 |
October | 0.221054E+11 | 0.314662E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210976E+10 |
November | 0.212681E+11 | 0.304277E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235456E+10 |
December | 0.221389E+11 | 0.313608E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235043E+10 |
Annual Sum or Average | 0.264651E+12 | 0.375227E+12 | 0.842987E+11 | 60875283.68 | 0.235836E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.286301E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.888249E+09 |
Maximum of Months | 0.230879E+11 | 0.326576E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36109903.76 | 0.279714E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.296499E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140268E+10 |
February | 0.190200E+10 | 0.269775E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122955E+10 |
March | 0.217552E+10 | 0.307725E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128149E+10 |
April | 0.205665E+10 | 0.290340E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1713770.34 | 0.119671E+10 |
May | 0.212923E+10 | 0.302112E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111263.38 | 0.963813E+09 |
June | 0.209978E+10 | 0.296946E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 955915.38 | 0.786203E+09 |
July | 0.208610E+10 | 0.295506E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10321167.08 | 0.621385E+09 |
August | 0.217552E+10 | 0.307725E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19343232.52 | 0.540845E+09 |
September | 0.205665E+10 | 0.290340E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105402.29 | 0.459273E+09 |
October | 0.208295E+10 | 0.296499E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107261E+10 |
November | 0.200405E+10 | 0.286713E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118602E+10 |
December | 0.208610E+10 | 0.295506E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119039E+10 |
Annual Sum or Average | 0.249375E+11 | 0.353568E+11 | 0.529224E+11 | 32550750.99 | 0.119310E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.269775E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459273E+09 |
Maximum of Months | 0.217552E+10 | 0.307725E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19343232.52 | 0.140268E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.296499E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134405E+10 |
February | 0.190200E+10 | 0.269775E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116678E+10 |
March | 0.217552E+10 | 0.307725E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120022E+10 |
April | 0.205665E+10 | 0.290340E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1713759.93 | 0.112476E+10 |
May | 0.212923E+10 | 0.302112E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 111271.39 | 0.909500E+09 |
June | 0.209978E+10 | 0.296946E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 955808.57 | 0.744566E+09 |
July | 0.208610E+10 | 0.295506E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10185502.15 | 0.598216E+09 |
August | 0.217552E+10 | 0.307725E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18985306.72 | 0.527758E+09 |
September | 0.205665E+10 | 0.290340E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 105418.70 | 0.439265E+09 |
October | 0.208295E+10 | 0.296499E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100316E+10 |
November | 0.200405E+10 | 0.286713E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110216E+10 |
December | 0.208610E+10 | 0.295506E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113405E+10 |
Annual Sum or Average | 0.249375E+11 | 0.353568E+11 | 0.794328E+10 | 32057067.46 | 0.112945E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.269775E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439265E+09 |
Maximum of Months | 0.217552E+10 | 0.307725E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18985306.72 | 0.134405E+10 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.180413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138756E+11 |
February | 0.00 | 0.164152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108180E+11 |
March | 0.00 | 0.187244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931655E+10 |
April | 0.00 | 0.176665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529050.82 | 0.646356E+10 |
May | 0.00 | 0.183829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482386E+10 |
June | 0.00 | 0.180685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275859E+10 |
July | 0.00 | 0.179809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1884138.62 | 0.155700E+10 |
August | 0.00 | 0.187244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5812507.32 | 0.127509E+10 |
September | 0.00 | 0.176665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348080E+10 |
October | 0.00 | 0.180413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665279E+10 |
November | 0.00 | 0.174459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105529E+11 |
December | 0.00 | 0.179809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130137E+11 |
Annual Sum or Average | 0.00 | 0.215139E+10 | 8225696.76 | 0.845884E+11 | |||||
Minimum of Months | 0.00 | 0.164152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127509E+10 |
Maximum of Months | 0.00 | 0.187244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5812507.32 | 0.138756E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 3087.68 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5689.08 | 28-JAN-05:10 |
February | 5888.82 | 01-FEB-15:09 | 3087.68 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5367.01 | 19-FEB-08:00 |
March | 5888.82 | 01-MAR-15:09 | 3087.68 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5232.17 | 29-MAR-04:55 |
April | 5888.82 | 01-APR-10:09 | 3087.68 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 210.32 | 01-APR-16:00 | 4879.30 | 08-APR-04:05 |
May | 5888.82 | 01-MAY-14:09 | 3087.68 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 05-MAY-16:00 | 4810.59 | 17-MAY-20:05 |
June | 5888.82 | 01-JUN-14:09 | 3087.68 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 90.41 | 28-JUN-16:00 | 4662.50 | 13-JUN-03:00 |
July | 5888.82 | 01-JUL-10:09 | 3087.68 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 426.10 | 30-JUL-18:03 | 2523.19 | 02-JUL-04:00 |
August | 5888.82 | 01-AUG-14:09 | 3087.68 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 390.87 | 13-AUG-18:03 | 3462.94 | 11-AUG-04:00 |
September | 5888.82 | 01-SEP-14:09 | 3087.68 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.60 | 14-SEP-17:00 | 2443.98 | 18-SEP-23:00 |
October | 5888.82 | 02-OCT-14:09 | 3087.68 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5068.37 | 31-OCT-20:03 |
November | 5888.82 | 01-NOV-14:09 | 3087.68 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6268.87 | 29-NOV-21:02 |
December | 5888.82 | 01-DEC-15:09 | 3087.68 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5285.49 | 22-DEC-21:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 3087.68 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2443.98 | |||||
Maximum of Months | 5888.82 | 3087.68 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 426.10 | 6268.87 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 26358.01 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5063.09 | 12-JAN-24:00 |
February | 24809.68 | 01-FEB-15:09 | 26358.01 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4562.92 | 16-FEB-04:00 |
March | 24809.68 | 01-MAR-15:09 | 26358.01 | 01-MAR-09:09 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4450.99 | 28-MAR-24:00 |
April | 24809.68 | 01-APR-10:09 | 26358.01 | 01-APR-09:09 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 172.19 | 01-APR-16:00 | 4905.94 | 07-APR-24:00 |
May | 24809.68 | 01-MAY-14:09 | 26358.01 | 01-MAY-08:09 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 05-MAY-16:00 | 4203.28 | 17-MAY-20:10 |
June | 24809.68 | 01-JUN-14:09 | 26358.01 | 01-JUN-08:09 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.02 | 28-JUN-15:00 | 4711.18 | 13-JUN-03:00 |
July | 24809.68 | 01-JUL-10:09 | 26358.01 | 01-JUL-09:09 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 345.84 | 30-JUL-18:03 | 2433.43 | 02-JUL-04:00 |
August | 24809.68 | 01-AUG-14:09 | 26358.01 | 01-AUG-08:09 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 317.61 | 13-AUG-18:03 | 3098.29 | 04-AUG-24:00 |
September | 24809.68 | 01-SEP-14:09 | 26358.01 | 01-SEP-08:09 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 | 14-SEP-17:00 | 2333.70 | 18-SEP-23:00 |
October | 24809.68 | 02-OCT-14:09 | 26358.01 | 02-OCT-08:09 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4509.14 | 31-OCT-20:10 |
November | 24809.68 | 01-NOV-14:09 | 26358.01 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5181.32 | 29-NOV-21:02 |
December | 24809.68 | 01-DEC-15:09 | 26358.01 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4372.96 | 22-DEC-21:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 26358.01 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2333.70 | |||||
Maximum of Months | 24809.68 | 26358.01 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 345.84 | 5181.32 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2483.66 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2500.25 | 28-JAN-05:04 |
February | 2337.76 | 01-FEB-15:09 | 2483.66 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2357.15 | 19-FEB-07:44 |
March | 2337.76 | 01-MAR-15:09 | 2483.66 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2267.25 | 29-MAR-05:00 |
April | 2337.76 | 01-APR-10:09 | 2483.66 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.15 | 01-APR-16:00 | 2256.00 | 07-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 2483.66 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 | 05-MAY-16:00 | 2151.17 | 17-MAY-20:05 |
June | 2337.76 | 01-JUN-14:09 | 2483.66 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 | 28-JUN-16:00 | 2080.04 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 2483.66 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.63 | 30-JUL-18:10 | 1133.88 | 02-JUL-04:00 |
August | 2337.76 | 01-AUG-14:09 | 2483.66 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 173.93 | 13-AUG-18:10 | 1592.16 | 11-AUG-04:00 |
September | 2337.76 | 01-SEP-14:09 | 2483.66 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 14-SEP-17:00 | 1114.83 | 18-SEP-23:00 |
October | 2337.76 | 02-OCT-14:09 | 2483.66 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2359.25 | 31-OCT-20:03 |
November | 2337.76 | 01-NOV-14:09 | 2483.66 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2719.94 | 29-NOV-21:02 |
December | 2337.76 | 01-DEC-15:09 | 2483.66 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2295.05 | 22-DEC-21:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2483.66 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1114.83 | |||||
Maximum of Months | 2337.76 | 2483.66 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 189.63 | 2719.94 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2483.66 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2499.94 | 28-JAN-05:05 |
February | 2337.76 | 01-FEB-15:09 | 2483.66 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2325.30 | 19-FEB-07:50 |
March | 2337.76 | 01-MAR-15:09 | 2483.66 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2267.25 | 29-MAR-05:00 |
April | 2337.76 | 01-APR-10:09 | 2483.66 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.15 | 01-APR-16:00 | 2133.82 | 11-APR-04:04 |
May | 2337.76 | 01-MAY-14:09 | 2483.66 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 | 05-MAY-16:00 | 1935.68 | 17-MAY-20:05 |
June | 2337.76 | 01-JUN-14:09 | 2483.66 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 | 28-JUN-16:00 | 1963.83 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 2483.66 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.29 | 30-JUL-18:10 | 1069.78 | 02-JUL-04:00 |
August | 2337.76 | 01-AUG-14:09 | 2483.66 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 175.62 | 13-AUG-18:10 | 1540.65 | 11-AUG-04:00 |
September | 2337.76 | 01-SEP-14:09 | 2483.66 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 14-SEP-17:00 | 1023.21 | 30-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 2483.66 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2184.46 | 31-OCT-20:03 |
November | 2337.76 | 01-NOV-14:09 | 2483.66 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2711.94 | 29-NOV-21:02 |
December | 2337.76 | 01-DEC-15:09 | 2483.66 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2287.75 | 22-DEC-21:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2483.66 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1023.21 | |||||
Maximum of Months | 2337.76 | 2483.66 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 191.29 | 2711.94 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 151.13 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 26190.68 | 07-JAN-12:10 |
February | 0.00 | 01-FEB-00:10 | 151.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 26029.95 | 18-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 151.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 18852.45 | 22-MAR-11:10 |
April | 0.00 | 01-APR-00:10 | 151.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.52 | 01-APR-16:00 | 16400.39 | 18-APR-17:00 |
May | 0.00 | 01-MAY-00:10 | 151.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 14923.11 | 23-MAY-17:00 |
June | 0.00 | 01-JUN-00:10 | 151.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 12316.09 | 13-JUN-11:03 |
July | 0.00 | 01-JUL-00:10 | 151.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.14 | 24-JUL-15:00 | 8592.89 | 12-JUL-11:05 |
August | 0.00 | 01-AUG-00:10 | 151.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.81 | 10-AUG-17:00 | 9038.37 | 01-AUG-11:05 |
September | 0.00 | 01-SEP-00:10 | 151.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 12250.77 | 16-SEP-11:02 |
October | 0.00 | 01-OCT-00:10 | 151.13 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 13750.03 | 29-OCT-11:03 |
November | 0.00 | 01-NOV-00:10 | 151.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 21413.79 | 12-NOV-17:00 |
December | 0.00 | 01-DEC-00:10 | 151.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 25343.84 | 26-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 151.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8592.89 | ||||
Maximum of Months | 0.00 | 151.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.81 | 26190.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3247.45 | 07-JAN-13:00 | 5888.82 | 3087.68 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.04 |
February | 2921.87 | 17-FEB-12:30 | 5152.71 | 3087.68 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.65 |
March | 2727.01 | 22-MAR-10:40 | 5152.71 | 3087.68 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 975.33 |
April | 7042.54 | 27-APR-15:00 | 5888.82 | 3087.68 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 119.88 | 0.00 |
May | 8025.55 | 15-MAY-15:00 | 5888.82 | 3087.68 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.98 |
June | 28871.79 | 21-JUN-20:45 | 0.00 | 1372.30 | 1226.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.78 |
July | 30784.73 | 07-JUL-20:36 | 0.00 | 6861.51 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.07 |
August | 28897.36 | 08-AUG-22:31 | 0.00 | 1372.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.67 |
September | 27481.05 | 13-SEP-20:49 | 0.00 | 6861.51 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5691.45 | 04-OCT-15:00 | 5888.82 | 3087.68 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.92 |
November | 4644.42 | 04-NOV-14:30 | 5888.82 | 3087.68 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.74 |
December | 2523.51 | 30-DEC-17:00 | 5888.82 | 3087.68 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2523.51 | 0.00 | 1372.30 | 1226.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30784.73 | 5888.82 | 6861.51 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 119.88 | 975.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36286.30 | 16-JAN-09:07 | 9303.63 | 8786.00 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 736.23 |
February | 31982.97 | 20-FEB-09:07 | 9303.63 | 8786.00 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.49 |
March | 36557.99 | 01-MAR-07:03 | 12404.84 | 23429.34 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.63 |
April | 144025.07 | 27-APR-21:13 | 0.00 | 4393.00 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.46 |
May | 153347.15 | 14-MAY-20:05 | 0.00 | 2928.67 | 1550.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 918.63 |
June | 156493.26 | 03-JUN-21:35 | 0.00 | 2928.67 | 1550.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 975.10 |
July | 149464.10 | 05-JUL-20:20 | 0.00 | 11714.67 | 2067.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.38 |
August | 147138.92 | 14-AUG-23:41 | 0.00 | 13179.00 | 9305.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.01 |
September | 142364.34 | 04-SEP-19:10 | 0.00 | 5857.33 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 774.46 |
October | 162399.93 | 04-OCT-20:33 | 0.00 | 17572.00 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.13 |
November | 32590.34 | 11-NOV-09:03 | 9303.63 | 8786.00 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.22 |
December | 34455.00 | 26-DEC-07:07 | 9303.63 | 17572.00 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.37 |
Annual Sum or Average | |||||||||||
Minimum of Months | 31982.97 | 0.00 | 2928.67 | 1550.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.63 | |
Maximum of Months | 162399.93 | 12404.84 | 23429.34 | 9305.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 975.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3844.76 | 20-JAN-13:30 | 2045.54 | 2483.66 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.87 |
February | 6489.67 | 27-FEB-15:10 | 4675.52 | 4967.31 | 5841.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.06 |
March | 7004.87 | 18-MAR-13:50 | 2337.76 | 2483.66 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.51 |
April | 22134.66 | 26-APR-20:15 | 0.00 | 1103.85 | 1298.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.70 |
May | 21283.82 | 14-MAY-18:11 | 0.00 | 1379.81 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.22 |
June | 23278.28 | 27-JUN-22:11 | 0.00 | 1379.81 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.67 |
July | 22788.20 | 19-JUL-20:11 | 0.00 | 4415.39 | 5192.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.06 |
August | 22870.77 | 14-AUG-22:51 | 0.00 | 1241.83 | 5841.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.13 |
September | 21928.59 | 10-SEP-18:41 | 0.00 | 1379.81 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.76 |
October | 24678.66 | 04-OCT-20:10 | 0.00 | 1655.77 | 1947.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.56 |
November | 9002.57 | 04-NOV-14:00 | 2337.76 | 2483.66 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5116.36 | 05-DEC-12:40 | 2045.54 | 2483.66 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.09 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3844.76 | 0.00 | 1103.85 | 1298.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24678.66 | 4675.52 | 4967.31 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3095.61 | 07-JAN-13:10 | 2337.76 | 2483.66 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.79 |
February | 4148.63 | 27-FEB-15:10 | 4675.52 | 4967.31 | 876.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.06 |
March | 4547.42 | 01-MAR-15:10 | 2337.76 | 2483.66 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.38 |
April | 7073.01 | 27-APR-13:30 | 2045.54 | 2483.66 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 26.30 | 0.00 |
May | 16515.40 | 14-MAY-18:18 | 0.00 | 1379.81 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.10 |
June | 16861.72 | 25-JUN-18:20 | 0.00 | 1379.81 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.94 |
July | 15893.21 | 23-JUL-18:41 | 0.00 | 1379.81 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 65.67 | 0.00 |
August | 16839.37 | 14-AUG-23:41 | 0.00 | 1241.83 | 876.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.67 |
September | 16037.47 | 10-SEP-18:41 | 0.00 | 1379.81 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.78 |
October | 14284.73 | 04-OCT-20:11 | 0.00 | 5519.24 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.06 |
November | 6427.71 | 04-NOV-14:00 | 2337.76 | 2483.66 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2934.53 | 06-DEC-12:00 | 2045.54 | 2483.66 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.01 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2934.53 | 0.00 | 1241.83 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16861.72 | 4675.52 | 5519.24 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 65.67 | 467.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 930.23 | 14-JAN-05:02 | 0.00 | 83.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.64 |
February | 990.00 | 21-FEB-05:02 | 0.00 | 83.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.04 |
March | 677.72 | 06-MAR-05:02 | 0.00 | 83.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.39 |
April | 332.06 | 11-APR-04:02 | 0.00 | 83.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.86 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.42 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.14 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.44 |
August | 0.00 | 01-AUG-00:03 | 0.00 | 25.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.09 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 16.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.86 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.22 |
November | 578.03 | 24-NOV-05:02 | 0.00 | 83.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.57 |
December | 997.85 | 25-DEC-07:02 | 0.00 | 83.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 997.85 | 0.00 | 83.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.86 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.102209E+12 | 72559.44 | 11-JAN-17:30 | 0.693685E+11 | 145743.09 | 16-JAN-09:09 |
February | 0.917340E+11 | 72987.23 | 27-FEB-17:49 | 0.475305E+11 | 136425.75 | 19-FEB-09:09 |
March | 0.102081E+12 | 72672.67 | 02-MAR-17:49 | 0.251209E+11 | 63743.36 | 06-MAR-05:10 |
April | 0.976788E+11 | 94320.38 | 27-APR-14:00 | 0.156553E+11 | 52103.04 | 11-APR-04:10 |
May | 0.102171E+12 | 91790.70 | 06-MAY-13:39 | 0.117421E+11 | 21817.57 | 18-MAY-04:10 |
June | 0.103353E+12 | 93566.49 | 28-JUN-14:00 | 0.913072E+10 | 16346.54 | 13-JUN-13:00 |
July | 0.113106E+12 | 101908.47 | 24-JUL-14:00 | 0.831292E+10 | 12142.19 | 12-JUL-11:09 |
August | 0.121676E+12 | 103714.45 | 29-AUG-14:00 | 0.821880E+10 | 12343.81 | 01-AUG-11:09 |
September | 0.103701E+12 | 94751.64 | 14-SEP-14:09 | 0.955346E+10 | 15836.60 | 26-SEP-13:00 |
October | 0.100704E+12 | 80430.27 | 04-OCT-14:00 | 0.138308E+11 | 29108.25 | 28-OCT-04:10 |
November | 0.983512E+11 | 79304.74 | 04-NOV-14:09 | 0.323994E+11 | 90101.78 | 24-NOV-07:10 |
December | 0.102326E+12 | 72559.45 | 04-DEC-16:30 | 0.561780E+11 | 142388.76 | 26-DEC-07:10 |
Annual Sum or Average | 0.123909E+13 | 0.307041E+12 | ||||
Minimum of Months | 0.917340E+11 | 72559.44 | 0.821880E+10 | 12142.19 | ||
Maximum of Months | 0.121676E+12 | 103714.45 | 0.693685E+11 | 145743.09 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.412627E+11 | 0.124847E+11 | 0.164409E+11 | 0.00 | 0.320207E+11 | 0.00 | 0.00 | 74.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.375436E+11 | 0.102926E+11 | 0.149157E+11 | 0.00 | 0.289395E+11 | 0.00 | 0.00 | 42701616.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.428250E+11 | 0.100466E+11 | 0.168545E+11 | 0.00 | 0.321996E+11 | 0.00 | 0.00 | 0.155684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.404055E+11 | 0.836850E+10 | 0.160165E+11 | 0.00 | 0.306263E+11 | 0.00 | 0.00 | 0.226197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.420438E+11 | 0.743281E+10 | 0.166477E+11 | 0.00 | 0.313069E+11 | 0.00 | 0.00 | 0.473976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.413249E+11 | 0.654105E+10 | 0.162772E+11 | 0.00 | 0.303453E+11 | 0.00 | 0.00 | 0.886413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.411244E+11 | 0.705941E+10 | 0.163871E+11 | 0.00 | 0.307541E+11 | 0.00 | 0.00 | 0.177806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.428250E+11 | 0.810492E+10 | 0.168545E+11 | 0.00 | 0.312860E+11 | 0.00 | 0.00 | 0.226052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.404055E+11 | 0.913287E+10 | 0.160165E+11 | 0.00 | 0.303138E+11 | 0.00 | 0.00 | 0.783197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.412627E+11 | 0.108373E+11 | 0.164409E+11 | 0.00 | 0.313156E+11 | 0.00 | 0.00 | 0.847926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.399008E+11 | 0.117159E+11 | 0.159174E+11 | 0.00 | 0.305539E+11 | 0.00 | 0.00 | 0.263119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.411244E+11 | 0.128053E+11 | 0.163871E+11 | 0.00 | 0.320030E+11 | 0.00 | 0.00 | 5966985.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.492048E+12 | 0.114822E+12 | 0.195156E+12 | 0.371665E+12 | 0.00 | 0.653990E+11 | |||||||
Minimum of Months | 0.375436E+11 | 0.654105E+10 | 0.149157E+11 | 0.00 | 0.289395E+11 | 0.00 | 0.00 | 74.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.428250E+11 | 0.128053E+11 | 0.168545E+11 | 0.00 | 0.321996E+11 | 0.00 | 0.00 | 0.226052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.609370E+11 | 0.00 | 0.843141E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.398838E+11 | 0.00 | 0.764666E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.166300E+11 | 0.00 | 0.849080E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.757780E+10 | 0.00 | 0.807746E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.350600E+10 | 0.00 | 0.823613E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.123319E+10 | 0.00 | 0.789753E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.299115E+09 | 0.00 | 0.801380E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.150333E+09 | 0.00 | 0.806847E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.174988E+10 | 0.00 | 0.780358E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.570578E+10 | 0.00 | 0.812499E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.244288E+11 | 0.00 | 0.797062E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.478154E+11 | 0.00 | 0.836262E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.209917E+12 | 0.971241E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.150333E+09 | 0.00 | 0.764666E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.609370E+11 | 0.00 | 0.849080E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 34564.13 | 02-JAN-09:09 | 7321.52 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 19902.73 | 01-JAN-13:39 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 34564.13 | 01-FEB-09:09 | 7321.52 | 01-FEB-00:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 19902.73 | 03-FEB-09:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 34564.13 | 01-MAR-09:09 | 7321.52 | 01-MAR-00:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 19902.73 | 05-MAR-11:39 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 34564.13 | 01-APR-09:09 | 7321.52 | 01-APR-00:10 | 10771.04 | 01-APR-09:09 | 0.00 | 19902.73 | 04-APR-15:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 34564.13 | 01-MAY-08:09 | 7321.52 | 01-MAY-00:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 19902.73 | 01-MAY-14:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 34564.13 | 01-JUN-08:09 | 7321.52 | 01-JUN-00:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 19902.73 | 01-JUN-11:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 34564.13 | 01-JUL-09:09 | 7321.52 | 01-JUL-00:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 19902.73 | 02-JUL-14:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 34564.13 | 01-AUG-08:09 | 7321.52 | 01-AUG-00:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 19902.73 | 01-AUG-12:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 34564.13 | 01-SEP-08:09 | 7321.52 | 01-SEP-00:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 19902.73 | 01-SEP-12:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 34564.13 | 02-OCT-08:09 | 7321.52 | 01-OCT-00:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 19902.73 | 02-OCT-13:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 34564.13 | 01-NOV-08:09 | 7321.52 | 01-NOV-00:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 19902.73 | 05-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 34564.13 | 01-DEC-09:09 | 7321.52 | 01-DEC-00:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 19902.73 | 02-DEC-08:39 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 34564.13 | 7321.52 | 10771.04 | 0.00 | 19902.73 | 0.00 | 0.00 | |||||
Maximum of Months | 34564.13 | 7321.52 | 10771.04 | 0.00 | 19902.73 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.04 | 11-JAN-18:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4309.49 | 27-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7251.01 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30906.73 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28377.04 | 06-MAY-13:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30152.83 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 38494.82 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40300.80 | 29-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31337.98 | 14-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17016.61 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15891.09 | 04-NOV-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 350.97 | 02-DEC-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40300.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 72559.44 | 11-JAN-17:30 | 34564.13 | 10771.04 | 7321.52 | 0.00 | 19902.73 | 0.00 | 0.00 | 0.02 | 0.00 |
February | 72987.23 | 27-FEB-17:49 | 34564.13 | 10771.04 | 7321.52 | 0.00 | 19902.73 | 0.00 | 0.00 | 427.81 | 0.00 |
March | 72672.67 | 02-MAR-17:49 | 34564.13 | 10771.04 | 7321.52 | 0.00 | 19902.73 | 0.00 | 0.00 | 113.25 | 0.00 |
April | 94320.38 | 27-APR-14:00 | 34564.13 | 10771.04 | 0.00 | 0.00 | 18078.49 | 0.00 | 0.00 | 30906.73 | 0.00 |
May | 91790.70 | 06-MAY-13:39 | 34564.13 | 10771.04 | 0.00 | 0.00 | 18078.49 | 0.00 | 0.00 | 28377.04 | 0.00 |
June | 93566.49 | 28-JUN-14:00 | 34564.13 | 10771.04 | 0.00 | 0.00 | 18078.49 | 0.00 | 0.00 | 30152.83 | 0.00 |
July | 101908.47 | 24-JUL-14:00 | 34564.13 | 10771.04 | 0.00 | 0.00 | 18078.49 | 0.00 | 0.00 | 38494.82 | 0.00 |
August | 103714.45 | 29-AUG-14:00 | 34564.13 | 10771.04 | 0.00 | 0.00 | 18078.49 | 0.00 | 0.00 | 40300.80 | 0.00 |
September | 94751.64 | 14-SEP-14:09 | 34564.13 | 10771.04 | 0.00 | 0.00 | 18078.49 | 0.00 | 0.00 | 31337.98 | 0.00 |
October | 80430.27 | 04-OCT-14:00 | 34564.13 | 10771.04 | 0.00 | 0.00 | 18078.49 | 0.00 | 0.00 | 17016.61 | 0.00 |
November | 79304.74 | 04-NOV-14:09 | 34564.13 | 10771.04 | 0.00 | 0.00 | 18078.49 | 0.00 | 0.00 | 15891.09 | 0.00 |
December | 72559.45 | 04-DEC-16:30 | 34564.13 | 10771.04 | 7321.52 | 0.00 | 19902.73 | 0.00 | 0.00 | 0.03 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 72559.44 | 34564.13 | 10771.04 | 0.00 | 0.00 | 18078.49 | 0.00 | 0.00 | 0.02 | 0.00 | |
Maximum of Months | 103714.45 | 34564.13 | 10771.04 | 7321.52 | 0.00 | 19902.73 | 0.00 | 0.00 | 40300.80 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 143881.09 | 16-JAN-09:09 | 0.00 | 5102.33 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 134247.87 | 19-FEB-09:09 | 0.00 | 5102.55 | 14-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 61881.36 | 06-MAR-05:10 | 0.00 | 5099.06 | 03-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 50241.04 | 11-APR-04:10 | 0.00 | 5078.18 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 19955.57 | 18-MAY-04:10 | 0.00 | 5050.89 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 11466.08 | 13-JUN-13:00 | 0.00 | 5021.26 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 7185.82 | 09-JUL-12:00 | 0.00 | 4995.98 | 03-JUL-11:00 | 0.00 |
August | 0.00 | 0.00 | 7359.86 | 01-AUG-11:09 | 0.00 | 4985.72 | 31-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 10984.20 | 26-SEP-14:30 | 0.00 | 5000.69 | 29-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 25738.09 | 31-OCT-04:10 | 0.00 | 5030.92 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 88239.78 | 24-NOV-07:10 | 0.00 | 5062.56 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 137815.73 | 26-DEC-07:10 | 0.00 | 5086.13 | 28-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 7185.82 | 0.00 | 4985.72 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 143881.09 | 0.00 | 5102.55 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.50 | 20.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6.50 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.83 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.67 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.17 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.33 | 20.20 | 0.00 | 0.17 | 24.46 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.50 | 20.48 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.49 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 24.49 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 24.49 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.49 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.48 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 21.33 | 24.49 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 24.49 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 20.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.83 | 20.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.00 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.33 | 20.52 | 0.00 | 0.00 | 0.33 | 24.46 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.46 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.46 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.49 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.51 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.47 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.47 | 0.00 | 0.00 |
November | 1.67 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.33 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.67 | 20.23 | 0.00 | 11.33 | 24.49 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.50 | 20.52 | 0.00 | 0.00 | 4.00 | 24.51 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.67 | 20.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6.00 | 20.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.33 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.83 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.48 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.00 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.83 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27.83 | 20.16 | 0.00 | 2.17 | 24.48 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.67 | 20.54 | 0.00 | 0.00 | 2.00 | 24.49 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.14 | 295.50 | 21.11 | 295.50 | 21.11 |
February | 376.00 | 21.43 | 217.33 | 21.11 | 217.33 | 21.11 |
March | 422.00 | 21.98 | 82.50 | 21.12 | 82.50 | 21.12 |
April | 385.33 | 22.79 | 15.67 | 21.11 | 15.67 | 21.11 |
May | 340.67 | 23.38 | 6.33 | 23.89 | 0.00 | 0.00 |
June | 207.83 | 23.66 | 12.50 | 23.89 | 0.00 | 0.00 |
July | 100.17 | 23.79 | 127.33 | 23.89 | 0.00 | 0.00 |
August | 61.67 | 23.70 | 167.33 | 23.89 | 0.00 | 0.00 |
September | 186.33 | 23.57 | 42.17 | 23.89 | 0.00 | 0.00 |
October | 410.83 | 23.00 | 1.67 | 21.11 | 1.67 | 21.11 |
November | 394.67 | 21.84 | 92.50 | 21.11 | 92.50 | 21.11 |
December | 415.00 | 21.16 | 243.33 | 21.11 | 243.33 | 21.11 |
Annual Sum or Average | 3714.50 | 22.30 | 1304.17 | 21.87 | 948.50 | 21.11 |
Minimum of Months | 61.67 | 21.14 | 1.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 422.00 | 23.79 | 295.50 | 23.89 | 295.50 | 21.12 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.22 | 92.17 | 21.11 | 92.17 | 21.11 |
February | 365.33 | 21.66 | 59.33 | 21.11 | 59.33 | 21.11 |
March | 395.17 | 22.52 | 1.33 | 21.11 | 1.33 | 21.11 |
April | 250.17 | 22.98 | 36.17 | 23.89 | 0.00 | 0.00 |
May | 102.17 | 23.08 | 93.50 | 23.89 | 0.00 | 0.00 |
June | 42.50 | 23.42 | 171.33 | 23.89 | 0.00 | 0.00 |
July | 18.83 | 23.67 | 280.67 | 23.89 | 0.00 | 0.00 |
August | 16.17 | 23.54 | 324.67 | 23.89 | 0.00 | 0.00 |
September | 56.33 | 23.28 | 204.67 | 23.89 | 0.00 | 0.00 |
October | 215.50 | 22.95 | 4.67 | 23.89 | 0.00 | 0.00 |
November | 333.33 | 21.81 | 16.00 | 22.59 | 7.50 | 21.11 |
December | 415.00 | 21.32 | 48.83 | 21.11 | 48.83 | 21.11 |
Annual Sum or Average | 2624.50 | 22.06 | 1333.33 | 23.45 | 209.17 | 21.11 |
Minimum of Months | 16.17 | 21.22 | 1.33 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 415.00 | 23.67 | 324.67 | 23.89 | 92.17 | 21.11 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.62 | 145.67 | 21.11 | 145.67 | 21.11 |
February | 347.00 | 22.17 | 80.00 | 21.11 | 80.00 | 21.11 |
March | 356.50 | 22.86 | 24.00 | 21.46 | 21.00 | 21.11 |
April | 240.17 | 23.05 | 43.00 | 23.65 | 3.67 | 21.11 |
May | 135.67 | 23.21 | 81.83 | 23.89 | 0.00 | 0.00 |
June | 67.33 | 23.55 | 140.50 | 23.89 | 0.00 | 0.00 |
July | 34.33 | 23.81 | 273.83 | 23.89 | 0.00 | 0.00 |
August | 21.83 | 23.69 | 321.67 | 23.89 | 0.00 | 0.00 |
September | 55.67 | 23.50 | 223.83 | 23.89 | 0.00 | 0.00 |
October | 196.17 | 23.19 | 70.17 | 23.89 | 0.00 | 0.00 |
November | 336.67 | 22.44 | 41.67 | 22.07 | 27.33 | 21.11 |
December | 405.50 | 21.87 | 105.33 | 21.11 | 105.33 | 21.11 |
Annual Sum or Average | 2610.83 | 22.47 | 1551.50 | 23.20 | 383.00 | 21.11 |
Minimum of Months | 21.83 | 21.62 | 24.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 414.00 | 23.81 | 321.67 | 23.89 | 145.67 | 21.11 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.17 | 221.50 | 21.11 | 221.50 | 21.11 |
February | 365.50 | 21.52 | 140.67 | 21.11 | 140.67 | 21.11 |
March | 390.33 | 22.03 | 56.00 | 21.13 | 55.50 | 21.11 |
April | 309.17 | 22.44 | 43.33 | 22.95 | 14.67 | 21.11 |
May | 214.00 | 22.62 | 56.67 | 23.89 | 0.00 | 0.00 |
June | 118.83 | 22.87 | 92.17 | 23.89 | 0.00 | 0.00 |
July | 74.50 | 23.19 | 227.17 | 23.89 | 0.00 | 0.00 |
August | 52.00 | 23.05 | 272.33 | 23.89 | 0.00 | 0.00 |
September | 118.50 | 22.86 | 175.17 | 23.89 | 0.00 | 0.00 |
October | 271.50 | 22.40 | 52.00 | 23.89 | 0.00 | 0.00 |
November | 376.67 | 21.60 | 74.33 | 21.45 | 65.17 | 21.11 |
December | 414.00 | 21.33 | 188.17 | 21.11 | 188.17 | 21.11 |
Annual Sum or Average | 3119.00 | 21.93 | 1599.50 | 22.70 | 685.67 | 21.11 |
Minimum of Months | 52.00 | 21.17 | 43.33 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 414.00 | 23.19 | 272.33 | 23.89 | 221.50 | 21.11 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.13653 | 35.33745 | -0.5776 | 12.19572 |
February | 376.00000 | 21.43321 | 36.56792 | -0.4802 | 10.93320 |
March | 422.00000 | 21.97776 | 37.11970 | -0.3041 | 8.03787 |
April | 405.00000 | 22.83229 | 39.18653 | -0.0540 | 6.51214 |
May | 418.00000 | 23.46379 | 41.12582 | -0.8276 | 20.89861 |
June | 408.00000 | 23.76946 | 41.47239 | -0.6591 | 14.65451 |
July | 415.00000 | 23.86403 | 45.30219 | -0.5526 | 11.69168 |
August | 422.00000 | 23.86064 | 48.68278 | -0.5291 | 11.12549 |
September | 405.00000 | 23.73870 | 47.79003 | -0.6548 | 14.64015 |
October | 414.00000 | 22.99271 | 42.60968 | 0.01435 | 6.10107 |
November | 399.00000 | 21.85572 | 42.58335 | -0.2992 | 8.58355 |
December | 415.00000 | 21.16498 | 37.53541 | -0.5393 | 11.26307 |
Annual Sum or Average | 4913.00000 | 22.68405 | 41.30541 | -0.4559 | 11.39937 |
Minimum of Months | 376.00000 | 21.13653 | 35.33745 | -0.8276 | 6.10107 |
Maximum of Months | 422.00000 | 23.86403 | 48.68278 | 0.01435 | 20.89861 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.21964 | 33.05977 | -0.4451 | 9.48428 |
February | 376.00000 | 21.72599 | 33.68007 | -0.2974 | 8.30958 |
March | 422.00000 | 22.61863 | 33.35619 | -0.0431 | 6.26148 |
April | 405.00000 | 23.33020 | 35.84936 | 0.18099 | 6.62608 |
May | 418.00000 | 23.69097 | 39.19172 | -0.5800 | 12.82410 |
June | 408.00000 | 23.83898 | 40.51253 | -0.4850 | 10.19786 |
July | 415.00000 | 23.87742 | 44.66286 | -0.4232 | 8.99423 |
August | 422.00000 | 23.87364 | 48.07671 | -0.4080 | 8.70071 |
September | 405.00000 | 23.80161 | 46.30357 | -0.4947 | 10.54049 |
October | 414.00000 | 23.40343 | 39.46927 | 0.21142 | 6.59881 |
November | 399.00000 | 22.15656 | 39.82708 | -0.1258 | 7.28687 |
December | 415.00000 | 21.31746 | 35.00227 | -0.3952 | 8.60436 |
Annual Sum or Average | 4913.00000 | 22.91401 | 39.11879 | -0.2760 | 8.70779 |
Minimum of Months | 376.00000 | 21.21964 | 33.05977 | -0.5800 | 6.26148 |
Maximum of Months | 422.00000 | 23.87742 | 48.07671 | 0.21142 | 12.82410 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.61921 | 31.72312 | -0.4107 | 9.54401 |
February | 376.00000 | 22.30148 | 31.73822 | -0.2023 | 8.28209 |
March | 422.00000 | 23.00478 | 31.27636 | 0.00735 | 6.83427 |
April | 405.00000 | 23.38291 | 34.37709 | 0.16777 | 7.11342 |
May | 418.00000 | 23.66242 | 38.21795 | -0.6278 | 14.68777 |
June | 408.00000 | 23.83296 | 39.81752 | -0.5171 | 11.11070 |
July | 415.00000 | 23.88365 | 44.07795 | -0.4178 | 9.04700 |
August | 422.00000 | 23.87976 | 47.25530 | -0.3724 | 8.35725 |
September | 405.00000 | 23.83494 | 45.15855 | -0.4437 | 9.99194 |
October | 414.00000 | 23.55255 | 37.62543 | 0.24959 | 7.31601 |
November | 399.00000 | 22.66028 | 37.79406 | -0.0616 | 7.25970 |
December | 415.00000 | 21.91348 | 33.21305 | -0.3146 | 8.64228 |
Annual Sum or Average | 4913.00000 | 23.13392 | 37.73100 | -0.2464 | 9.02563 |
Minimum of Months | 376.00000 | 21.61921 | 31.27636 | -0.6278 | 6.83427 |
Maximum of Months | 422.00000 | 23.88365 | 47.25530 | 0.24959 | 14.68777 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.16851 | 32.44079 | -0.5371 | 11.39315 |
February | 376.00000 | 21.58859 | 33.49092 | -0.3758 | 9.58659 |
March | 422.00000 | 22.16119 | 33.83892 | -0.1868 | 7.60410 |
April | 405.00000 | 22.76484 | 37.23851 | 0.01906 | 7.12007 |
May | 418.00000 | 23.21576 | 41.13021 | -0.7980 | 21.09566 |
June | 408.00000 | 23.57208 | 42.53681 | -0.6330 | 14.86785 |
July | 415.00000 | 23.74926 | 45.11410 | -0.5047 | 11.22041 |
August | 422.00000 | 23.77388 | 47.80120 | -0.4491 | 10.13190 |
September | 405.00000 | 23.57060 | 46.39480 | -0.5683 | 13.67256 |
October | 414.00000 | 22.89699 | 40.77560 | 0.09408 | 7.04172 |
November | 399.00000 | 21.71992 | 39.92862 | -0.2802 | 8.40576 |
December | 415.00000 | 21.33777 | 34.25833 | -0.4640 | 10.33315 |
Annual Sum or Average | 4913.00000 | 22.63583 | 39.61863 | -0.3910 | 11.05738 |
Minimum of Months | 376.00000 | 21.16851 | 32.44079 | -0.7980 | 7.04172 |
Maximum of Months | 422.00000 | 23.77388 | 47.80120 | 0.09408 | 21.09566 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 41660.90 | 12814.00 | 3.83 | 33362.77 | 8298.13 | 0.00 | 0.00 | 28-FEB-14:10 | 0.00 | 01-FEB-00:10 | 66.26 | 28-FEB-14:10 | 52.90 | 28-FEB-14:10 | 13.36 | 28-FEB-14:10 | 20.38 | 28-FEB-14:10 | 0.00 | 01-FEB-00:10 |
March | 72214.64 | 22215.42 | 8.25 | 60307.16 | 11907.48 | 0.00 | 0.00 | 10-MAR-17:00 | 0.00 | 01-MAR-00:10 | 101.18 | 10-MAR-17:00 | 82.59 | 10-MAR-17:00 | 18.59 | 10-MAR-17:00 | 31.13 | 10-MAR-17:00 | 0.00 | 01-MAR-00:10 |
April | 0.527651E+09 | 0.159891E+09 | 75.08 | 0.489565E+09 | 38085865.00 | 0.00 | 0.44 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 11167.61 | 27-APR-15:00 | 9889.55 | 27-APR-15:00 | 1278.05 | 27-APR-15:00 | 3355.91 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.127733E+10 | 0.372212E+09 | 170.63 | 0.111891E+10 | 0.158418E+09 | 0.00 | 0.47 | 06-MAY-13:50 | 0.00 | 01-MAY-00:10 | 12302.02 | 06-MAY-13:50 | 9924.89 | 06-MAY-14:00 | 2476.63 | 06-MAY-12:50 | 3458.14 | 06-MAY-13:50 | 0.00 | 01-MAY-00:10 |
June | 0.267326E+10 | 0.777382E+09 | 238.56 | 0.246545E+10 | 0.207811E+09 | 0.00 | 1.00 | 21-JUN-20:45 | 0.00 | 01-JUN-00:10 | 29635.78 | 28-JUN-20:45 | 24717.30 | 21-JUN-20:45 | 7482.19 | 28-JUN-20:45 | 6851.09 | 28-JUN-20:45 | 0.00 | 01-JUN-00:10 |
July | 0.655076E+10 | 0.188590E+10 | 297.28 | 0.552774E+10 | 0.102302E+10 | 0.00 | 1.00 | 07-JUL-20:36 | 0.00 | 01-JUL-00:10 | 31097.47 | 26-JUL-20:30 | 28298.67 | 23-JUL-19:11 | 9895.42 | 27-JUL-20:37 | 7299.86 | 30-JUL-19:01 | 0.00 | 01-JUL-00:10 |
August | 0.843626E+10 | 0.244336E+10 | 314.86 | 0.706897E+10 | 0.136729E+10 | 0.00 | 1.00 | 07-AUG-20:23 | 0.00 | 01-AUG-00:03 | 31026.02 | 24-AUG-21:21 | 28507.97 | 08-AUG-21:36 | 9532.98 | 10-AUG-23:43 | 7367.34 | 24-AUG-20:37 | 0.00 | 01-AUG-00:03 |
September | 0.215448E+10 | 0.617428E+09 | 202.57 | 0.173410E+10 | 0.420376E+09 | 0.00 | 1.00 | 13-SEP-20:49 | 0.00 | 01-SEP-00:05 | 30213.37 | 13-SEP-20:49 | 21203.60 | 13-SEP-20:49 | 10712.85 | 15-SEP-20:33 | 6981.65 | 13-SEP-20:49 | 0.00 | 01-SEP-00:05 |
October | 52948974.93 | 15727253.78 | 76.24 | 52889206.07 | 59768.85 | 0.00 | 0.20 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4404.15 | 04-OCT-15:00 | 4404.15 | 04-OCT-15:00 | 18.41 | 26-OCT-15:00 | 1297.06 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 31901468.52 | 9534489.56 | 12.14 | 23672809.94 | 8228658.57 | 0.00 | 0.14 | 04-NOV-14:20 | 0.00 | 01-NOV-00:10 | 3305.25 | 04-NOV-14:20 | 2488.18 | 04-NOV-14:30 | 824.01 | 04-NOV-14:00 | 981.68 | 04-NOV-14:20 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.217047E+11 | 0.628147E+10 | 1399.45 | 0.184814E+11 | 0.322331E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.843626E+10 | 0.244336E+10 | 314.86 | 0.706897E+10 | 0.136729E+10 | 0.00 | 1.00 | 0.00 | 31097.47 | 28507.97 | 10712.85 | 7367.34 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 28339746.87 | 9323744.20 | 16.05 | 27714121.32 | 625625.55 | 0.00 | 0.06 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 6478.10 | 27-FEB-15:10 | 6478.10 | 27-FEB-15:10 | 150.01 | 25-FEB-17:30 | 2120.07 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.150821E+09 | 48616248.37 | 48.09 | 0.150459E+09 | 361628.85 | 0.00 | 0.16 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 16122.14 | 18-MAR-16:00 | 16122.14 | 18-MAR-16:00 | 128.34 | 10-MAR-18:30 | 5138.95 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.478733E+10 | 0.151184E+10 | 133.91 | 0.452011E+10 | 0.267219E+09 | 0.00 | 1.00 | 26-APR-20:25 | 0.00 | 01-APR-00:10 | 135745.77 | 27-APR-20:21 | 124211.33 | 26-APR-20:25 | 17223.17 | 27-APR-21:13 | 33924.80 | 27-APR-20:21 | 0.00 | 01-APR-00:10 |
May | 0.109866E+11 | 0.335850E+10 | 215.35 | 0.970657E+10 | 0.128001E+10 | 0.00 | 1.00 | 03-MAY-20:20 | 0.00 | 01-MAY-00:10 | 141882.77 | 07-MAY-18:18 | 133866.67 | 14-MAY-18:17 | 50633.87 | 06-MAY-22:55 | 35467.09 | 07-MAY-18:18 | 0.00 | 01-MAY-00:10 |
June | 0.210676E+11 | 0.644315E+10 | 289.22 | 0.194639E+11 | 0.160367E+10 | 0.00 | 1.00 | 01-JUN-20:25 | 0.00 | 01-JUN-00:10 | 141128.83 | 11-JUN-18:19 | 135838.90 | 25-JUN-18:17 | 37779.57 | 29-JUN-21:55 | 35295.56 | 11-JUN-18:19 | 0.00 | 01-JUN-00:10 |
July | 0.419862E+11 | 0.127567E+11 | 337.76 | 0.357549E+11 | 0.623135E+10 | 0.00 | 1.00 | 02-JUL-18:25 | 0.00 | 01-JUL-00:10 | 145500.26 | 26-JUL-20:16 | 133911.34 | 23-JUL-19:11 | 52160.86 | 15-JUL-22:15 | 36828.57 | 24-JUL-20:11 | 0.00 | 01-JUL-00:10 |
August | 0.523584E+11 | 0.159584E+11 | 350.69 | 0.442254E+11 | 0.813300E+10 | 0.00 | 1.00 | 01-AUG-00:55 | 0.00 | 01-AUG-00:03 | 145219.91 | 24-AUG-21:02 | 135414.00 | 08-AUG-21:54 | 57682.58 | 26-AUG-21:35 | 37276.73 | 24-AUG-20:37 | 0.00 | 01-AUG-00:03 |
September | 0.168787E+11 | 0.508888E+10 | 246.49 | 0.136652E+11 | 0.321344E+10 | 0.00 | 1.00 | 01-SEP-00:05 | 0.00 | 01-SEP-00:10 | 141785.73 | 13-SEP-20:11 | 125971.21 | 10-SEP-18:19 | 51016.34 | 15-SEP-21:53 | 35445.31 | 13-SEP-20:11 | 0.00 | 01-SEP-00:05 |
October | 0.945509E+09 | 0.297029E+09 | 127.61 | 0.926226E+09 | 19282656.98 | 0.00 | 1.00 | 04-OCT-20:33 | 0.00 | 01-OCT-00:10 | 132118.68 | 04-OCT-20:33 | 127229.50 | 04-OCT-20:33 | 4889.19 | 04-OCT-20:33 | 32868.81 | 04-OCT-20:33 | 0.00 | 01-OCT-00:10 |
November | 0.482516E+09 | 0.151152E+09 | 27.55 | 0.362122E+09 | 0.120394E+09 | 0.00 | 0.29 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 33601.32 | 04-NOV-14:20 | 25902.54 | 04-NOV-14:30 | 7785.67 | 04-NOV-13:40 | 10375.61 | 04-NOV-14:20 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.149672E+12 | 0.456236E+11 | 1792.71 | 0.128803E+12 | 0.208693E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.523584E+11 | 0.159584E+11 | 350.69 | 0.442254E+11 | 0.813300E+10 | 0.00 | 1.00 | 0.00 | 145500.26 | 135838.90 | 57682.58 | 37276.73 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 241.57 | 74.44 | 1.17 | 232.83 | 8.74 | 0.00 | 0.00 | 11-JAN-18:20 | 0.00 | 01-JAN-00:10 | 0.12 | 11-JAN-18:20 | 0.12 | 11-JAN-18:20 | 0.00 | 11-JAN-18:20 | 0.04 | 11-JAN-18:20 | 0.00 | 01-JAN-00:10 |
February | 29155603.40 | 8598875.74 | 43.69 | 29065031.42 | 90571.98 | 0.00 | 0.22 | 27-FEB-14:57 | 0.00 | 01-FEB-00:10 | 3604.11 | 27-FEB-14:57 | 3604.11 | 27-FEB-14:57 | 23.69 | 27-FEB-16:10 | 1044.92 | 27-FEB-14:57 | 0.00 | 01-FEB-00:10 |
March | 47272056.72 | 13725802.14 | 100.34 | 47246832.35 | 25224.37 | 0.00 | 0.26 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 4202.39 | 18-MAR-14:00 | 4202.39 | 18-MAR-14:00 | 15.20 | 18-MAR-13:00 | 1204.89 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.866249E+09 | 0.249362E+09 | 160.75 | 0.829682E+09 | 36566368.77 | 0.00 | 1.00 | 26-APR-20:15 | 0.00 | 01-APR-00:10 | 21018.00 | 27-APR-20:10 | 19726.88 | 26-APR-20:15 | 2323.61 | 27-APR-20:10 | 4855.50 | 27-APR-20:10 | 0.00 | 01-APR-00:10 |
May | 0.147099E+10 | 0.417512E+09 | 204.71 | 0.132581E+10 | 0.145180E+09 | 0.00 | 1.00 | 03-MAY-20:20 | 0.00 | 01-MAY-00:10 | 21774.39 | 07-MAY-18:11 | 20571.01 | 14-MAY-18:11 | 4627.94 | 07-MAY-18:18 | 5030.26 | 07-MAY-18:11 | 0.00 | 01-MAY-00:10 |
June | 0.253082E+10 | 0.725077E+09 | 262.69 | 0.240097E+10 | 0.129847E+09 | 0.00 | 1.00 | 09-JUN-20:15 | 0.00 | 01-JUN-00:10 | 21662.52 | 11-JUN-18:11 | 20863.39 | 25-JUN-18:11 | 4946.13 | 22-JUN-20:55 | 5006.32 | 11-JUN-18:11 | 0.00 | 01-JUN-00:10 |
July | 0.571543E+10 | 0.161986E+10 | 329.45 | 0.499835E+10 | 0.717082E+09 | 0.00 | 1.00 | 06-JUL-20:15 | 0.00 | 01-JUL-00:10 | 22343.88 | 26-JUL-20:11 | 21365.92 | 23-JUL-18:41 | 7854.45 | 15-JUL-21:20 | 5298.60 | 30-JUL-18:41 | 0.00 | 01-JUL-00:10 |
August | 0.794596E+10 | 0.223951E+10 | 340.24 | 0.694605E+10 | 0.999916E+09 | 0.00 | 1.00 | 06-AUG-18:10 | 0.00 | 01-AUG-00:03 | 22286.48 | 24-AUG-20:41 | 21223.93 | 08-AUG-21:50 | 6871.86 | 30-AUG-20:15 | 5303.01 | 13-AUG-18:41 | 0.00 | 01-AUG-00:03 |
September | 0.341128E+10 | 0.933018E+09 | 253.82 | 0.283182E+10 | 0.579456E+09 | 0.00 | 1.00 | 08-SEP-20:10 | 0.00 | 01-SEP-00:05 | 21843.23 | 15-SEP-20:10 | 19842.59 | 10-SEP-18:10 | 7448.53 | 22-SEP-20:15 | 5044.64 | 15-SEP-20:10 | 0.00 | 01-SEP-00:05 |
October | 0.427132E+09 | 0.120571E+09 | 170.69 | 0.412223E+09 | 14909816.02 | 0.00 | 1.00 | 04-OCT-20:10 | 0.00 | 01-OCT-00:10 | 20742.71 | 04-OCT-20:11 | 20742.71 | 04-OCT-20:11 | 671.43 | 08-OCT-13:30 | 4772.80 | 04-OCT-20:11 | 0.00 | 01-OCT-00:10 |
November | 0.152182E+09 | 42022018.52 | 44.34 | 0.115946E+09 | 36235601.68 | 0.00 | 0.50 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 9465.84 | 04-NOV-14:00 | 7468.39 | 04-NOV-14:00 | 2125.87 | 04-NOV-13:10 | 2547.01 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 6251.97 | 1916.61 | 14.58 | 6247.27 | 4.70 | 0.00 | 0.00 | 02-DEC-13:00 | 0.00 | 01-DEC-00:10 | 0.43 | 02-DEC-13:00 | 0.43 | 02-DEC-13:00 | 0.00 | 30-DEC-14:00 | 0.13 | 02-DEC-13:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.225965E+11 | 0.636926E+10 | 1926.47 | 0.199372E+11 | 0.265931E+10 | 0.00 | ||||||||||||||
Minimum of Months | 241.57 | 74.44 | 1.17 | 232.83 | 4.70 | 0.00 | 0.00 | 0.00 | 0.12 | 0.12 | 0.00 | 0.04 | 0.00 | |||||||
Maximum of Months | 0.794596E+10 | 0.223951E+10 | 340.24 | 0.694605E+10 | 0.999916E+09 | 0.00 | 1.00 | 0.00 | 22343.88 | 21365.92 | 7854.45 | 5303.01 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 94560321.99 | 24766182.28 | 14.67 | 91226095.28 | 3334226.71 | 0.00 | 0.31 | 27-FEB-15:05 | 0.00 | 01-FEB-00:10 | 4517.80 | 27-FEB-15:10 | 4517.80 | 27-FEB-15:10 | 219.11 | 28-FEB-14:10 | 1148.99 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.355474E+09 | 93319697.42 | 58.97 | 0.352190E+09 | 3283607.77 | 0.00 | 0.34 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 4921.68 | 18-MAR-14:00 | 4921.68 | 18-MAR-14:00 | 271.78 | 10-MAR-13:00 | 1241.97 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.130650E+10 | 0.340881E+09 | 140.20 | 0.124671E+10 | 59793978.28 | 0.00 | 0.59 | 27-APR-14:10 | 0.00 | 01-APR-00:10 | 9403.39 | 27-APR-14:10 | 8814.47 | 27-APR-14:10 | 1079.87 | 28-APR-13:00 | 2397.40 | 27-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.227977E+10 | 0.591536E+09 | 233.90 | 0.209623E+10 | 0.183539E+09 | 0.00 | 1.00 | 14-MAY-18:18 | 0.00 | 01-MAY-00:10 | 17702.55 | 14-MAY-18:18 | 17702.55 | 14-MAY-18:18 | 1350.64 | 07-MAY-18:21 | 3670.30 | 14-MAY-18:18 | 0.00 | 01-MAY-00:10 |
June | 0.354284E+10 | 0.918528E+09 | 308.14 | 0.329841E+10 | 0.244425E+09 | 0.00 | 1.00 | 11-JUN-18:19 | 0.00 | 01-JUN-00:10 | 18415.11 | 22-JUN-20:20 | 17992.79 | 25-JUN-18:20 | 1883.17 | 22-JUN-20:20 | 3804.97 | 22-JUN-20:20 | 0.00 | 01-JUN-00:10 |
July | 0.590206E+10 | 0.151811E+10 | 366.62 | 0.523494E+10 | 0.667117E+09 | 0.00 | 1.00 | 14-JUL-20:17 | 0.00 | 01-JUL-00:10 | 18821.06 | 27-JUL-20:16 | 17759.80 | 23-JUL-18:41 | 3698.99 | 27-JUL-20:16 | 4004.42 | 30-JUL-18:41 | 0.00 | 01-JUL-00:10 |
August | 0.763084E+10 | 0.196396E+10 | 414.38 | 0.667718E+10 | 0.953654E+09 | 0.00 | 1.00 | 08-AUG-20:41 | 0.00 | 01-AUG-00:03 | 18628.44 | 29-AUG-20:41 | 17611.93 | 08-AUG-20:41 | 2605.87 | 23-AUG-22:48 | 4009.92 | 13-AUG-18:41 | 0.00 | 01-AUG-00:03 |
September | 0.476808E+10 | 0.119264E+10 | 311.17 | 0.418335E+10 | 0.584730E+09 | 0.00 | 1.00 | 13-SEP-20:41 | 0.00 | 01-SEP-00:05 | 18516.54 | 13-SEP-20:41 | 16804.04 | 10-SEP-18:41 | 2506.70 | 13-SEP-20:41 | 3823.58 | 13-SEP-20:41 | 0.00 | 01-SEP-00:05 |
October | 0.162576E+10 | 0.414598E+09 | 161.86 | 0.155533E+10 | 70432261.24 | 0.00 | 0.87 | 04-OCT-20:11 | 0.00 | 01-OCT-00:10 | 14323.02 | 04-OCT-20:11 | 14323.02 | 04-OCT-20:11 | 870.04 | 01-OCT-13:30 | 3147.50 | 04-OCT-20:11 | 0.00 | 01-OCT-00:10 |
November | 0.240129E+09 | 60410417.38 | 23.56 | 0.200596E+09 | 39532804.09 | 0.00 | 0.52 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 8392.83 | 04-NOV-14:00 | 7094.91 | 04-NOV-14:00 | 1346.90 | 04-NOV-13:20 | 2007.39 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 22159331.99 | 5965068.77 | 7.10 | 22159331.99 | 0.00 | 0.00 | 0.10 | 02-DEC-13:30 | 0.00 | 01-DEC-00:10 | 1312.27 | 02-DEC-13:30 | 1312.27 | 02-DEC-13:30 | 0.00 | 02-DEC-13:50 | 350.87 | 02-DEC-13:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.277682E+11 | 0.712472E+10 | 2040.55 | 0.249583E+11 | 0.280984E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.763084E+10 | 0.196396E+10 | 414.38 | 0.667718E+10 | 0.953654E+09 | 0.00 | 1.00 | 0.00 | 18821.06 | 17992.79 | 3698.99 | 4009.92 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.08 | 2.15 | 6.94 | 1.77 | 57.54 | 0.00 | 0.00 | 744.00 |
February | 16.65 | 6.35 | 10.30 | 10.65 | 51.12 | 0.00 | 0.00 | 672.00 |
March | 26.79 | 11.38 | 15.41 | 25.01 | 44.82 | 5.67 | 0.00 | 744.00 |
April | 42.88 | 21.78 | 21.10 | 50.35 | 36.32 | 0.00 | 0.00 | 720.00 |
May | 55.39 | 28.35 | 27.04 | 71.52 | 30.66 | 0.00 | 0.00 | 744.00 |
June | 60.33 | 35.04 | 25.29 | 80.94 | 24.83 | 1.00 | 0.00 | 720.00 |
July | 63.03 | 41.34 | 21.69 | 90.11 | 22.31 | 0.00 | 0.00 | 744.00 |
August | 50.47 | 31.85 | 18.62 | 72.15 | 22.74 | 0.00 | 0.00 | 744.00 |
September | 35.89 | 19.89 | 16.00 | 45.36 | 31.39 | 4.67 | 0.00 | 720.00 |
October | 20.99 | 9.66 | 11.33 | 19.75 | 43.23 | 10.50 | 0.00 | 744.00 |
November | 10.64 | 2.82 | 7.82 | 4.60 | 48.22 | 0.00 | 0.00 | 720.00 |
December | 7.69 | 2.03 | 5.65 | 1.71 | 60.19 | 9.00 | 0.00 | 744.00 |
Annual Sum or Average | 33.41 | 17.79 | 15.62 | 39.67 | 39.40 | 30.83 | 0.00 | 8760.00 |
Minimum of Months | 7.69 | 2.03 | 5.65 | 1.71 | 22.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.03 | 41.34 | 27.04 | 90.11 | 60.19 | 10.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.08 | 2.15 | 6.94 | 1.77 | 57.54 | 0.00 | 0.00 | 744.00 |
February | 16.65 | 6.35 | 10.30 | 10.65 | 51.12 | 0.00 | 0.00 | 672.00 |
March | 26.79 | 11.38 | 15.41 | 25.01 | 44.82 | 5.67 | 0.00 | 744.00 |
April | 42.88 | 21.78 | 21.10 | 50.35 | 36.32 | 0.00 | 0.00 | 720.00 |
May | 55.39 | 28.35 | 27.04 | 71.52 | 30.66 | 0.00 | 0.00 | 744.00 |
June | 60.33 | 35.04 | 25.29 | 80.94 | 24.83 | 1.00 | 0.00 | 720.00 |
July | 63.03 | 41.34 | 21.69 | 90.11 | 22.31 | 0.00 | 0.00 | 744.00 |
August | 50.47 | 31.85 | 18.62 | 72.15 | 22.74 | 0.00 | 0.00 | 744.00 |
September | 35.89 | 19.89 | 16.00 | 45.36 | 31.39 | 4.67 | 0.00 | 720.00 |
October | 20.99 | 9.66 | 11.33 | 19.75 | 43.23 | 10.50 | 0.00 | 744.00 |
November | 10.64 | 2.82 | 7.82 | 4.60 | 48.22 | 0.00 | 0.00 | 720.00 |
December | 7.69 | 2.03 | 5.65 | 1.71 | 60.19 | 9.00 | 0.00 | 744.00 |
Annual Sum or Average | 33.41 | 17.79 | 15.62 | 39.67 | 39.40 | 30.83 | 0.00 | 8760.00 |
Minimum of Months | 7.69 | 2.03 | 5.65 | 1.71 | 22.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.03 | 41.34 | 27.04 | 90.11 | 60.19 | 10.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.08 | 2.15 | 6.94 | 1.77 | 57.54 | 0.00 | 0.00 | 744.00 |
February | 16.65 | 6.35 | 10.30 | 10.65 | 51.12 | 0.00 | 0.00 | 672.00 |
March | 26.79 | 11.38 | 15.41 | 25.01 | 44.82 | 5.67 | 0.00 | 744.00 |
April | 42.88 | 21.78 | 21.10 | 50.35 | 36.32 | 0.00 | 0.00 | 720.00 |
May | 55.39 | 28.35 | 27.04 | 71.52 | 30.66 | 0.00 | 0.00 | 744.00 |
June | 60.33 | 35.04 | 25.29 | 80.94 | 24.83 | 1.00 | 0.00 | 720.00 |
July | 63.03 | 41.34 | 21.69 | 90.11 | 22.31 | 0.00 | 0.00 | 744.00 |
August | 50.47 | 31.85 | 18.62 | 72.15 | 22.74 | 0.00 | 0.00 | 744.00 |
September | 35.89 | 19.89 | 16.00 | 45.36 | 31.39 | 4.67 | 0.00 | 720.00 |
October | 20.99 | 9.66 | 11.33 | 19.75 | 43.23 | 10.50 | 0.00 | 744.00 |
November | 10.64 | 2.82 | 7.82 | 4.60 | 48.22 | 0.00 | 0.00 | 720.00 |
December | 7.69 | 2.03 | 5.65 | 1.71 | 60.19 | 9.00 | 0.00 | 744.00 |
Annual Sum or Average | 33.41 | 17.79 | 15.62 | 39.67 | 39.40 | 30.83 | 0.00 | 8760.00 |
Minimum of Months | 7.69 | 2.03 | 5.65 | 1.71 | 22.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.03 | 41.34 | 27.04 | 90.11 | 60.19 | 10.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.08 | 2.15 | 6.94 | 1.77 | 57.54 | 0.00 | 0.00 | 744.00 |
February | 16.65 | 6.35 | 10.30 | 10.65 | 51.12 | 0.00 | 0.00 | 672.00 |
March | 26.79 | 11.38 | 15.41 | 25.01 | 44.82 | 5.67 | 0.00 | 744.00 |
April | 42.88 | 21.78 | 21.10 | 50.35 | 36.32 | 0.00 | 0.00 | 720.00 |
May | 55.39 | 28.35 | 27.04 | 71.52 | 30.66 | 0.00 | 0.00 | 744.00 |
June | 60.33 | 35.04 | 25.29 | 80.94 | 24.83 | 1.00 | 0.00 | 720.00 |
July | 63.03 | 41.34 | 21.69 | 90.11 | 22.31 | 0.00 | 0.00 | 744.00 |
August | 50.47 | 31.85 | 18.62 | 72.15 | 22.74 | 0.00 | 0.00 | 744.00 |
September | 35.89 | 19.89 | 16.00 | 45.36 | 31.39 | 4.67 | 0.00 | 720.00 |
October | 20.99 | 9.66 | 11.33 | 19.75 | 43.23 | 10.50 | 0.00 | 744.00 |
November | 10.64 | 2.82 | 7.82 | 4.60 | 48.22 | 0.00 | 0.00 | 720.00 |
December | 7.69 | 2.03 | 5.65 | 1.71 | 60.19 | 9.00 | 0.00 | 744.00 |
Annual Sum or Average | 33.41 | 17.79 | 15.62 | 39.67 | 39.40 | 30.83 | 0.00 | 8760.00 |
Minimum of Months | 7.69 | 2.03 | 5.65 | 1.71 | 22.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.03 | 41.34 | 27.04 | 90.11 | 60.19 | 10.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.08 | 2.15 | 6.94 | 1.77 | 57.54 | 0.00 | 0.00 | 744.00 |
February | 16.65 | 6.35 | 10.30 | 10.65 | 51.12 | 0.00 | 0.00 | 672.00 |
March | 26.79 | 11.38 | 15.41 | 25.01 | 44.82 | 5.67 | 0.00 | 744.00 |
April | 42.88 | 21.78 | 21.10 | 50.35 | 36.32 | 0.00 | 0.00 | 720.00 |
May | 55.39 | 28.35 | 27.04 | 71.52 | 30.66 | 0.00 | 0.00 | 744.00 |
June | 60.33 | 35.04 | 25.29 | 80.94 | 24.83 | 1.00 | 0.00 | 720.00 |
July | 63.03 | 41.34 | 21.69 | 90.11 | 22.31 | 0.00 | 0.00 | 744.00 |
August | 50.47 | 31.85 | 18.62 | 72.15 | 22.74 | 0.00 | 0.00 | 744.00 |
September | 35.89 | 19.89 | 16.00 | 45.36 | 31.39 | 4.67 | 0.00 | 720.00 |
October | 20.99 | 9.66 | 11.33 | 19.75 | 43.23 | 10.50 | 0.00 | 744.00 |
November | 10.64 | 2.82 | 7.82 | 4.60 | 48.22 | 0.00 | 0.00 | 720.00 |
December | 7.69 | 2.03 | 5.65 | 1.71 | 60.19 | 9.00 | 0.00 | 744.00 |
Annual Sum or Average | 33.41 | 17.79 | 15.62 | 39.67 | 39.40 | 30.83 | 0.00 | 8760.00 |
Minimum of Months | 7.69 | 2.03 | 5.65 | 1.71 | 22.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.03 | 41.34 | 27.04 | 90.11 | 60.19 | 10.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.08 | 2.15 | 6.94 | 1.77 | 57.54 | 0.00 | 0.00 | 744.00 |
February | 16.65 | 6.35 | 10.30 | 10.65 | 51.12 | 0.00 | 0.00 | 672.00 |
March | 26.79 | 11.38 | 15.41 | 25.01 | 44.82 | 5.67 | 0.00 | 744.00 |
April | 42.88 | 21.78 | 21.10 | 50.35 | 36.32 | 0.00 | 0.00 | 720.00 |
May | 55.39 | 28.35 | 27.04 | 71.52 | 30.66 | 0.00 | 0.00 | 744.00 |
June | 60.33 | 35.04 | 25.29 | 80.94 | 24.83 | 1.00 | 0.00 | 720.00 |
July | 63.03 | 41.34 | 21.69 | 90.11 | 22.31 | 0.00 | 0.00 | 744.00 |
August | 50.47 | 31.85 | 18.62 | 72.15 | 22.74 | 0.00 | 0.00 | 744.00 |
September | 35.89 | 19.89 | 16.00 | 45.36 | 31.39 | 4.67 | 0.00 | 720.00 |
October | 20.99 | 9.66 | 11.33 | 19.75 | 43.23 | 10.50 | 0.00 | 744.00 |
November | 10.64 | 2.82 | 7.82 | 4.60 | 48.22 | 0.00 | 0.00 | 720.00 |
December | 7.69 | 2.03 | 5.65 | 1.71 | 60.19 | 9.00 | 0.00 | 744.00 |
Annual Sum or Average | 33.41 | 17.79 | 15.62 | 39.67 | 39.40 | 30.83 | 0.00 | 8760.00 |
Minimum of Months | 7.69 | 2.03 | 5.65 | 1.71 | 22.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.03 | 41.34 | 27.04 | 90.11 | 60.19 | 10.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.08 | 2.15 | 6.94 | 1.77 | 57.54 | 0.00 | 0.00 | 744.00 |
February | 16.65 | 6.35 | 10.30 | 10.65 | 51.12 | 0.00 | 0.00 | 672.00 |
March | 26.79 | 11.38 | 15.41 | 25.01 | 44.82 | 5.67 | 0.00 | 744.00 |
April | 42.88 | 21.78 | 21.10 | 50.35 | 36.32 | 0.00 | 0.00 | 720.00 |
May | 55.39 | 28.35 | 27.04 | 71.52 | 30.66 | 0.00 | 0.00 | 744.00 |
June | 60.33 | 35.04 | 25.29 | 80.94 | 24.83 | 1.00 | 0.00 | 720.00 |
July | 63.03 | 41.34 | 21.69 | 90.11 | 22.31 | 0.00 | 0.00 | 744.00 |
August | 50.47 | 31.85 | 18.62 | 72.15 | 22.74 | 0.00 | 0.00 | 744.00 |
September | 35.89 | 19.89 | 16.00 | 45.36 | 31.39 | 4.67 | 0.00 | 720.00 |
October | 20.99 | 9.66 | 11.33 | 19.75 | 43.23 | 10.50 | 0.00 | 744.00 |
November | 10.64 | 2.82 | 7.82 | 4.60 | 48.22 | 0.00 | 0.00 | 720.00 |
December | 7.69 | 2.03 | 5.65 | 1.71 | 60.19 | 9.00 | 0.00 | 744.00 |
Annual Sum or Average | 33.41 | 17.79 | 15.62 | 39.67 | 39.40 | 30.83 | 0.00 | 8760.00 |
Minimum of Months | 7.69 | 2.03 | 5.65 | 1.71 | 22.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.03 | 41.34 | 27.04 | 90.11 | 60.19 | 10.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.08 | 2.15 | 6.94 | 1.77 | 57.54 | 0.00 | 0.00 | 744.00 |
February | 16.65 | 6.35 | 10.30 | 10.65 | 51.12 | 0.00 | 0.00 | 672.00 |
March | 26.79 | 11.38 | 15.41 | 25.01 | 44.82 | 5.67 | 0.00 | 744.00 |
April | 42.88 | 21.78 | 21.10 | 50.35 | 36.32 | 0.00 | 0.00 | 720.00 |
May | 55.39 | 28.35 | 27.04 | 71.52 | 30.66 | 0.00 | 0.00 | 744.00 |
June | 60.33 | 35.04 | 25.29 | 80.94 | 24.83 | 1.00 | 0.00 | 720.00 |
July | 63.03 | 41.34 | 21.69 | 90.11 | 22.31 | 0.00 | 0.00 | 744.00 |
August | 50.47 | 31.85 | 18.62 | 72.15 | 22.74 | 0.00 | 0.00 | 744.00 |
September | 35.89 | 19.89 | 16.00 | 45.36 | 31.39 | 4.67 | 0.00 | 720.00 |
October | 20.99 | 9.66 | 11.33 | 19.75 | 43.23 | 10.50 | 0.00 | 744.00 |
November | 10.64 | 2.82 | 7.82 | 4.60 | 48.22 | 0.00 | 0.00 | 720.00 |
December | 7.69 | 2.03 | 5.65 | 1.71 | 60.19 | 9.00 | 0.00 | 744.00 |
Annual Sum or Average | 33.41 | 17.79 | 15.62 | 39.67 | 39.40 | 30.83 | 0.00 | 8760.00 |
Minimum of Months | 7.69 | 2.03 | 5.65 | 1.71 | 22.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.03 | 41.34 | 27.04 | 90.11 | 60.19 | 10.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 710.63 | 421.88 | 288.74 | 550.69 | 1031.12 | 0.00 | 0.00 | 744.00 |
February | 1093.22 | 676.73 | 416.49 | 955.85 | 939.61 | 0.00 | 0.00 | 672.00 |
March | 1176.41 | 627.59 | 548.83 | 1023.23 | 852.69 | 0.00 | 0.00 | 744.00 |
April | 1241.68 | 539.19 | 702.49 | 1024.66 | 705.25 | 0.00 | 0.00 | 720.00 |
May | 1135.10 | 338.05 | 797.06 | 841.84 | 592.64 | 0.00 | 0.00 | 744.00 |
June | 1038.50 | 278.71 | 759.79 | 733.39 | 470.89 | 0.00 | 0.00 | 720.00 |
July | 1132.50 | 414.66 | 717.84 | 917.54 | 420.10 | 0.00 | 0.00 | 744.00 |
August | 1216.85 | 567.39 | 649.46 | 1153.27 | 406.92 | 0.00 | 0.00 | 744.00 |
September | 1348.75 | 745.01 | 603.73 | 1311.05 | 581.70 | 0.00 | 0.00 | 720.00 |
October | 1221.68 | 754.42 | 467.26 | 1173.31 | 786.80 | 0.00 | 0.00 | 744.00 |
November | 721.96 | 413.68 | 308.28 | 590.27 | 901.56 | 0.00 | 0.00 | 720.00 |
December | 755.27 | 488.68 | 266.60 | 662.09 | 1064.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1065.58 | 521.20 | 544.38 | 911.03 | 728.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 710.63 | 278.71 | 266.60 | 550.69 | 406.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1348.75 | 754.42 | 797.06 | 1311.05 | 1064.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 710.63 | 421.88 | 288.74 | 556.73 | 999.47 | 0.00 | 0.00 | 744.00 |
February | 1093.22 | 676.73 | 416.49 | 966.88 | 897.89 | 0.00 | 0.00 | 672.00 |
March | 1176.41 | 627.59 | 548.83 | 1036.30 | 804.09 | 0.00 | 0.00 | 744.00 |
April | 1241.68 | 539.19 | 702.49 | 1037.83 | 668.05 | 0.00 | 0.00 | 720.00 |
May | 1135.10 | 338.05 | 797.06 | 853.29 | 561.39 | 0.00 | 0.00 | 744.00 |
June | 1038.50 | 278.71 | 759.79 | 740.45 | 448.56 | 0.00 | 0.00 | 720.00 |
July | 1132.50 | 414.66 | 717.84 | 919.92 | 405.07 | 0.00 | 0.00 | 744.00 |
August | 1216.85 | 567.39 | 649.46 | 1153.31 | 396.81 | 0.00 | 0.00 | 744.00 |
September | 1348.75 | 745.01 | 603.73 | 1314.20 | 560.47 | 0.00 | 0.00 | 720.00 |
October | 1221.68 | 754.42 | 467.26 | 1182.60 | 743.37 | 0.00 | 0.00 | 744.00 |
November | 721.96 | 413.68 | 308.28 | 602.01 | 848.49 | 0.00 | 0.00 | 720.00 |
December | 755.27 | 488.68 | 266.60 | 669.15 | 1026.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1065.58 | 521.20 | 544.38 | 918.95 | 695.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 710.63 | 278.71 | 266.60 | 556.73 | 396.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1348.75 | 754.42 | 797.06 | 1314.20 | 1026.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 146.22 | 86.81 | 59.41 | 111.25 | 206.12 | 0.00 | 0.00 | 744.00 |
February | 224.95 | 139.25 | 85.70 | 194.83 | 183.22 | 0.00 | 0.00 | 672.00 |
March | 242.06 | 129.14 | 112.93 | 211.47 | 162.07 | 0.00 | 0.00 | 744.00 |
April | 255.49 | 110.95 | 144.55 | 213.15 | 133.34 | 0.00 | 0.00 | 720.00 |
May | 233.56 | 69.56 | 164.01 | 177.82 | 110.04 | 0.00 | 0.00 | 744.00 |
June | 213.69 | 57.35 | 156.34 | 156.51 | 86.81 | 0.00 | 0.00 | 720.00 |
July | 233.03 | 85.32 | 147.71 | 190.91 | 79.64 | 0.00 | 0.00 | 744.00 |
August | 250.38 | 116.75 | 133.64 | 233.74 | 80.95 | 0.00 | 0.00 | 744.00 |
September | 277.52 | 153.30 | 124.23 | 271.73 | 109.94 | 0.00 | 0.00 | 720.00 |
October | 251.38 | 155.23 | 96.14 | 242.91 | 146.24 | 0.00 | 0.00 | 744.00 |
November | 148.55 | 85.12 | 63.43 | 121.37 | 172.68 | 0.00 | 0.00 | 720.00 |
December | 155.41 | 100.55 | 54.86 | 134.84 | 210.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 219.26 | 107.24 | 112.01 | 188.30 | 139.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 146.22 | 57.35 | 54.86 | 111.25 | 79.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 277.52 | 155.23 | 164.01 | 271.73 | 210.48 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24325062.71 | 5746397.96 | 18578664.75 | 4746249.35 | 0.154113E+09 |
February | 40276083.47 | 15363597.78 | 24912485.68 | 25771775.22 | 0.123663E+09 |
March | 71745120.16 | 30467775.52 | 41277344.64 | 66975050.07 | 0.120037E+09 |
April | 0.111149E+09 | 56458449.79 | 54690898.53 | 0.130510E+09 | 94147014.28 |
May | 0.148364E+09 | 75940845.75 | 72423324.86 | 0.191569E+09 | 82126145.37 |
June | 0.156369E+09 | 90827105.62 | 65541954.37 | 0.209797E+09 | 64367446.03 |
July | 0.168828E+09 | 0.110728E+09 | 58099872.43 | 0.241363E+09 | 59758258.22 |
August | 0.135186E+09 | 85307496.47 | 49878534.39 | 0.193252E+09 | 60901880.85 |
September | 93027962.97 | 51545727.24 | 41482235.73 | 0.117579E+09 | 81356247.17 |
October | 56208228.55 | 25868818.65 | 30339409.90 | 52899855.16 | 0.115790E+09 |
November | 27586461.92 | 7316762.27 | 20269699.65 | 11930715.23 | 0.124989E+09 |
December | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 0.161216E+09 |
Annual Sum or Average | 0.105365E+10 | 0.561019E+09 | 0.492631E+09 | 0.125097E+10 | 0.124247E+10 |
Minimum of Months | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 59758258.22 |
Maximum of Months | 0.168828E+09 | 0.110728E+09 | 72423324.86 | 0.241363E+09 | 0.161216E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24325062.71 | 5746397.96 | 18578664.75 | 4746249.35 | 0.154113E+09 |
February | 40276083.47 | 15363597.78 | 24912485.68 | 25771775.22 | 0.123663E+09 |
March | 71745120.16 | 30467775.52 | 41277344.64 | 66975050.07 | 0.120037E+09 |
April | 0.111149E+09 | 56458449.79 | 54690898.53 | 0.130510E+09 | 94147014.28 |
May | 0.148364E+09 | 75940845.75 | 72423324.86 | 0.191569E+09 | 82126145.37 |
June | 0.156369E+09 | 90827105.62 | 65541954.37 | 0.209797E+09 | 64367446.03 |
July | 0.168828E+09 | 0.110728E+09 | 58099872.43 | 0.241363E+09 | 59758258.22 |
August | 0.135186E+09 | 85307496.47 | 49878534.39 | 0.193252E+09 | 60901880.85 |
September | 93027962.97 | 51545727.24 | 41482235.73 | 0.117579E+09 | 81356247.17 |
October | 56208228.55 | 25868818.65 | 30339409.90 | 52899855.16 | 0.115790E+09 |
November | 27586461.92 | 7316762.27 | 20269699.65 | 11930715.23 | 0.124989E+09 |
December | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 0.161216E+09 |
Annual Sum or Average | 0.105365E+10 | 0.561019E+09 | 0.492631E+09 | 0.125097E+10 | 0.124247E+10 |
Minimum of Months | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 59758258.22 |
Maximum of Months | 0.168828E+09 | 0.110728E+09 | 72423324.86 | 0.241363E+09 | 0.161216E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24325062.71 | 5746397.96 | 18578664.75 | 4746249.35 | 0.154113E+09 |
February | 40276083.47 | 15363597.78 | 24912485.68 | 25771775.22 | 0.123663E+09 |
March | 71745120.16 | 30467775.52 | 41277344.64 | 66975050.07 | 0.120037E+09 |
April | 0.111149E+09 | 56458449.79 | 54690898.53 | 0.130510E+09 | 94147014.28 |
May | 0.148364E+09 | 75940845.75 | 72423324.86 | 0.191569E+09 | 82126145.37 |
June | 0.156369E+09 | 90827105.62 | 65541954.37 | 0.209797E+09 | 64367446.03 |
July | 0.168828E+09 | 0.110728E+09 | 58099872.43 | 0.241363E+09 | 59758258.22 |
August | 0.135186E+09 | 85307496.47 | 49878534.39 | 0.193252E+09 | 60901880.85 |
September | 93027962.97 | 51545727.24 | 41482235.73 | 0.117579E+09 | 81356247.17 |
October | 56208228.55 | 25868818.65 | 30339409.90 | 52899855.16 | 0.115790E+09 |
November | 27586461.92 | 7316762.27 | 20269699.65 | 11930715.23 | 0.124989E+09 |
December | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 0.161216E+09 |
Annual Sum or Average | 0.105365E+10 | 0.561019E+09 | 0.492631E+09 | 0.125097E+10 | 0.124247E+10 |
Minimum of Months | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 59758258.22 |
Maximum of Months | 0.168828E+09 | 0.110728E+09 | 72423324.86 | 0.241363E+09 | 0.161216E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24325062.71 | 5746397.96 | 18578664.75 | 4746249.35 | 0.154113E+09 |
February | 40276083.47 | 15363597.78 | 24912485.68 | 25771775.22 | 0.123663E+09 |
March | 71745120.16 | 30467775.52 | 41277344.64 | 66975050.07 | 0.120037E+09 |
April | 0.111149E+09 | 56458449.79 | 54690898.53 | 0.130510E+09 | 94147014.28 |
May | 0.148364E+09 | 75940845.75 | 72423324.86 | 0.191569E+09 | 82126145.37 |
June | 0.156369E+09 | 90827105.62 | 65541954.37 | 0.209797E+09 | 64367446.03 |
July | 0.168828E+09 | 0.110728E+09 | 58099872.43 | 0.241363E+09 | 59758258.22 |
August | 0.135186E+09 | 85307496.47 | 49878534.39 | 0.193252E+09 | 60901880.85 |
September | 93027962.97 | 51545727.24 | 41482235.73 | 0.117579E+09 | 81356247.17 |
October | 56208228.55 | 25868818.65 | 30339409.90 | 52899855.16 | 0.115790E+09 |
November | 27586461.92 | 7316762.27 | 20269699.65 | 11930715.23 | 0.124989E+09 |
December | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 0.161216E+09 |
Annual Sum or Average | 0.105365E+10 | 0.561019E+09 | 0.492631E+09 | 0.125097E+10 | 0.124247E+10 |
Minimum of Months | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 59758258.22 |
Maximum of Months | 0.168828E+09 | 0.110728E+09 | 72423324.86 | 0.241363E+09 | 0.161216E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24325062.71 | 5746397.96 | 18578664.75 | 4746249.35 | 0.154113E+09 |
February | 40276083.47 | 15363597.78 | 24912485.68 | 25771775.22 | 0.123663E+09 |
March | 71745120.16 | 30467775.52 | 41277344.64 | 66975050.07 | 0.120037E+09 |
April | 0.111149E+09 | 56458449.79 | 54690898.53 | 0.130510E+09 | 94147014.28 |
May | 0.148364E+09 | 75940845.75 | 72423324.86 | 0.191569E+09 | 82126145.37 |
June | 0.156369E+09 | 90827105.62 | 65541954.37 | 0.209797E+09 | 64367446.03 |
July | 0.168828E+09 | 0.110728E+09 | 58099872.43 | 0.241363E+09 | 59758258.22 |
August | 0.135186E+09 | 85307496.47 | 49878534.39 | 0.193252E+09 | 60901880.85 |
September | 93027962.97 | 51545727.24 | 41482235.73 | 0.117579E+09 | 81356247.17 |
October | 56208228.55 | 25868818.65 | 30339409.90 | 52899855.16 | 0.115790E+09 |
November | 27586461.92 | 7316762.27 | 20269699.65 | 11930715.23 | 0.124989E+09 |
December | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 0.161216E+09 |
Annual Sum or Average | 0.105365E+10 | 0.561019E+09 | 0.492631E+09 | 0.125097E+10 | 0.124247E+10 |
Minimum of Months | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 59758258.22 |
Maximum of Months | 0.168828E+09 | 0.110728E+09 | 72423324.86 | 0.241363E+09 | 0.161216E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24325062.71 | 5746397.96 | 18578664.75 | 4746249.35 | 0.154113E+09 |
February | 40276083.47 | 15363597.78 | 24912485.68 | 25771775.22 | 0.123663E+09 |
March | 71745120.16 | 30467775.52 | 41277344.64 | 66975050.07 | 0.120037E+09 |
April | 0.111149E+09 | 56458449.79 | 54690898.53 | 0.130510E+09 | 94147014.28 |
May | 0.148364E+09 | 75940845.75 | 72423324.86 | 0.191569E+09 | 82126145.37 |
June | 0.156369E+09 | 90827105.62 | 65541954.37 | 0.209797E+09 | 64367446.03 |
July | 0.168828E+09 | 0.110728E+09 | 58099872.43 | 0.241363E+09 | 59758258.22 |
August | 0.135186E+09 | 85307496.47 | 49878534.39 | 0.193252E+09 | 60901880.85 |
September | 93027962.97 | 51545727.24 | 41482235.73 | 0.117579E+09 | 81356247.17 |
October | 56208228.55 | 25868818.65 | 30339409.90 | 52899855.16 | 0.115790E+09 |
November | 27586461.92 | 7316762.27 | 20269699.65 | 11930715.23 | 0.124989E+09 |
December | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 0.161216E+09 |
Annual Sum or Average | 0.105365E+10 | 0.561019E+09 | 0.492631E+09 | 0.125097E+10 | 0.124247E+10 |
Minimum of Months | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 59758258.22 |
Maximum of Months | 0.168828E+09 | 0.110728E+09 | 72423324.86 | 0.241363E+09 | 0.161216E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24325062.71 | 5746397.96 | 18578664.75 | 4746249.35 | 0.154113E+09 |
February | 40276083.47 | 15363597.78 | 24912485.68 | 25771775.22 | 0.123663E+09 |
March | 71745120.16 | 30467775.52 | 41277344.64 | 66975050.07 | 0.120037E+09 |
April | 0.111149E+09 | 56458449.79 | 54690898.53 | 0.130510E+09 | 94147014.28 |
May | 0.148364E+09 | 75940845.75 | 72423324.86 | 0.191569E+09 | 82126145.37 |
June | 0.156369E+09 | 90827105.62 | 65541954.37 | 0.209797E+09 | 64367446.03 |
July | 0.168828E+09 | 0.110728E+09 | 58099872.43 | 0.241363E+09 | 59758258.22 |
August | 0.135186E+09 | 85307496.47 | 49878534.39 | 0.193252E+09 | 60901880.85 |
September | 93027962.97 | 51545727.24 | 41482235.73 | 0.117579E+09 | 81356247.17 |
October | 56208228.55 | 25868818.65 | 30339409.90 | 52899855.16 | 0.115790E+09 |
November | 27586461.92 | 7316762.27 | 20269699.65 | 11930715.23 | 0.124989E+09 |
December | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 0.161216E+09 |
Annual Sum or Average | 0.105365E+10 | 0.561019E+09 | 0.492631E+09 | 0.125097E+10 | 0.124247E+10 |
Minimum of Months | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 59758258.22 |
Maximum of Months | 0.168828E+09 | 0.110728E+09 | 72423324.86 | 0.241363E+09 | 0.161216E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24325062.71 | 5746397.96 | 18578664.75 | 4746249.35 | 0.154113E+09 |
February | 40276083.47 | 15363597.78 | 24912485.68 | 25771775.22 | 0.123663E+09 |
March | 71745120.16 | 30467775.52 | 41277344.64 | 66975050.07 | 0.120037E+09 |
April | 0.111149E+09 | 56458449.79 | 54690898.53 | 0.130510E+09 | 94147014.28 |
May | 0.148364E+09 | 75940845.75 | 72423324.86 | 0.191569E+09 | 82126145.37 |
June | 0.156369E+09 | 90827105.62 | 65541954.37 | 0.209797E+09 | 64367446.03 |
July | 0.168828E+09 | 0.110728E+09 | 58099872.43 | 0.241363E+09 | 59758258.22 |
August | 0.135186E+09 | 85307496.47 | 49878534.39 | 0.193252E+09 | 60901880.85 |
September | 93027962.97 | 51545727.24 | 41482235.73 | 0.117579E+09 | 81356247.17 |
October | 56208228.55 | 25868818.65 | 30339409.90 | 52899855.16 | 0.115790E+09 |
November | 27586461.92 | 7316762.27 | 20269699.65 | 11930715.23 | 0.124989E+09 |
December | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 0.161216E+09 |
Annual Sum or Average | 0.105365E+10 | 0.561019E+09 | 0.492631E+09 | 0.125097E+10 | 0.124247E+10 |
Minimum of Months | 20584662.34 | 5447844.05 | 15136818.29 | 4573829.83 | 59758258.22 |
Maximum of Months | 0.168828E+09 | 0.110728E+09 | 72423324.86 | 0.241363E+09 | 0.161216E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.147497E+10 | 0.276176E+10 |
February | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.231239E+10 | 0.227310E+10 |
March | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.274061E+10 | 0.228386E+10 |
April | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.265592E+10 | 0.182800E+10 |
May | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.225478E+10 | 0.158734E+10 |
June | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.190095E+10 | 0.122055E+10 |
July | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.245753E+10 | 0.112520E+10 |
August | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.308893E+10 | 0.108988E+10 |
September | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.339825E+10 | 0.150777E+10 |
October | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.314259E+10 | 0.210736E+10 |
November | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.152999E+10 | 0.233685E+10 |
December | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.177335E+10 | 0.285149E+10 |
Annual Sum or Average | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.287303E+11 | 0.229732E+11 |
Minimum of Months | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.147497E+10 | 0.108988E+10 |
Maximum of Months | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.339825E+10 | 0.285149E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.149115E+10 | 0.267699E+10 |
February | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.233908E+10 | 0.217218E+10 |
March | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.277563E+10 | 0.215367E+10 |
April | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.269006E+10 | 0.173158E+10 |
May | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.228547E+10 | 0.150364E+10 |
June | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.191924E+10 | 0.116265E+10 |
July | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.246392E+10 | 0.108494E+10 |
August | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.308903E+10 | 0.106283E+10 |
September | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.340641E+10 | 0.145275E+10 |
October | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.316749E+10 | 0.199104E+10 |
November | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.156040E+10 | 0.219928E+10 |
December | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.179226E+10 | 0.274917E+10 |
Annual Sum or Average | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.289801E+11 | 0.219407E+11 |
Minimum of Months | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.149115E+10 | 0.106283E+10 |
Maximum of Months | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.340641E+10 | 0.274917E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.391640E+09 | 0.232507E+09 | 0.159133E+09 | 0.297972E+09 | 0.552084E+09 |
February | 0.544188E+09 | 0.336867E+09 | 0.207321E+09 | 0.471336E+09 | 0.443250E+09 |
March | 0.648345E+09 | 0.345876E+09 | 0.302469E+09 | 0.566397E+09 | 0.434086E+09 |
April | 0.662239E+09 | 0.287571E+09 | 0.374668E+09 | 0.552474E+09 | 0.345620E+09 |
May | 0.625578E+09 | 0.186305E+09 | 0.439273E+09 | 0.476282E+09 | 0.294738E+09 |
June | 0.553877E+09 | 0.148650E+09 | 0.405227E+09 | 0.405680E+09 | 0.225004E+09 |
July | 0.624144E+09 | 0.228526E+09 | 0.395618E+09 | 0.511338E+09 | 0.213311E+09 |
August | 0.670629E+09 | 0.312698E+09 | 0.357931E+09 | 0.626047E+09 | 0.216811E+09 |
September | 0.719344E+09 | 0.397348E+09 | 0.321996E+09 | 0.704332E+09 | 0.284977E+09 |
October | 0.673289E+09 | 0.415775E+09 | 0.257514E+09 | 0.650615E+09 | 0.391695E+09 |
November | 0.385050E+09 | 0.220633E+09 | 0.164417E+09 | 0.314602E+09 | 0.447585E+09 |
December | 0.416246E+09 | 0.269321E+09 | 0.146926E+09 | 0.361166E+09 | 0.563737E+09 |
Annual Sum or Average | 0.691457E+10 | 0.338208E+10 | 0.353249E+10 | 0.593824E+10 | 0.441290E+10 |
Minimum of Months | 0.385050E+09 | 0.148650E+09 | 0.146926E+09 | 0.297972E+09 | 0.213311E+09 |
Maximum of Months | 0.719344E+09 | 0.415775E+09 | 0.439273E+09 | 0.704332E+09 | 0.563737E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.18 | 460.31 | 72.66 | 17.16 | 55.49 | 0.00 | 0.00 |
February | 85.22 | 408.94 | 133.19 | 50.81 | 82.38 | 0.00 | 0.00 |
March | 200.04 | 358.53 | 214.29 | 91.00 | 123.29 | 0.00 | 0.00 |
April | 402.81 | 290.58 | 343.05 | 174.25 | 168.80 | 0.00 | 0.00 |
May | 572.19 | 245.30 | 443.14 | 226.82 | 216.32 | 0.00 | 0.00 |
June | 647.52 | 198.66 | 482.62 | 280.33 | 202.29 | 0.00 | 0.00 |
July | 720.92 | 178.49 | 504.27 | 330.73 | 173.54 | 0.00 | 0.00 |
August | 577.22 | 181.91 | 403.78 | 254.80 | 148.98 | 0.00 | 0.00 |
September | 362.90 | 251.10 | 287.12 | 159.09 | 128.03 | 0.00 | 0.00 |
October | 158.00 | 345.85 | 167.89 | 77.27 | 90.62 | 0.00 | 0.00 |
November | 36.82 | 385.77 | 85.14 | 22.58 | 62.56 | 0.00 | 0.00 |
December | 13.66 | 481.53 | 61.48 | 16.27 | 45.21 | 0.00 | 0.00 |
Annual Sum or Average | 317.34 | 315.19 | 267.29 | 142.32 | 124.97 | 0.00 | 0.00 |
Minimum of Months | 13.66 | 178.49 | 61.48 | 16.27 | 45.21 | 0.00 | 0.00 |
Maximum of Months | 720.92 | 481.53 | 504.27 | 330.73 | 216.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 550.69 | 1031.12 | 710.63 | 421.88 | 288.74 | 0.00 | 0.00 |
February | 955.85 | 939.61 | 1093.22 | 676.73 | 416.49 | 0.00 | 0.00 |
March | 1023.23 | 852.69 | 1176.41 | 627.59 | 548.83 | 0.00 | 0.00 |
April | 1024.66 | 705.25 | 1241.68 | 539.19 | 702.49 | 0.00 | 0.00 |
May | 841.84 | 592.64 | 1135.10 | 338.05 | 797.06 | 0.00 | 0.00 |
June | 733.39 | 470.89 | 1038.50 | 278.71 | 759.79 | 0.00 | 0.00 |
July | 917.54 | 420.10 | 1132.50 | 414.66 | 717.84 | 0.00 | 0.00 |
August | 1153.27 | 406.92 | 1216.85 | 567.39 | 649.46 | 0.00 | 0.00 |
September | 1311.05 | 581.70 | 1348.75 | 745.01 | 603.73 | 0.00 | 0.00 |
October | 1173.31 | 786.80 | 1221.68 | 754.42 | 467.26 | 0.00 | 0.00 |
November | 590.27 | 901.56 | 721.96 | 413.68 | 308.28 | 0.00 | 0.00 |
December | 662.09 | 1064.62 | 755.27 | 488.68 | 266.60 | 0.00 | 0.00 |
Annual Sum or Average | 911.03 | 728.47 | 1065.58 | 521.20 | 544.38 | 0.00 | 0.00 |
Minimum of Months | 550.69 | 406.92 | 710.63 | 278.71 | 266.60 | 0.00 | 0.00 |
Maximum of Months | 1311.05 | 1064.62 | 1348.75 | 754.42 | 797.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 556.73 | 999.47 | 710.63 | 421.88 | 288.74 | 0.00 | 0.00 |
February | 966.88 | 897.89 | 1093.22 | 676.73 | 416.49 | 0.00 | 0.00 |
March | 1036.30 | 804.09 | 1176.41 | 627.59 | 548.83 | 0.00 | 0.00 |
April | 1037.83 | 668.05 | 1241.68 | 539.19 | 702.49 | 0.00 | 0.00 |
May | 853.29 | 561.39 | 1135.10 | 338.05 | 797.06 | 0.00 | 0.00 |
June | 740.45 | 448.56 | 1038.50 | 278.71 | 759.79 | 0.00 | 0.00 |
July | 919.92 | 405.07 | 1132.50 | 414.66 | 717.84 | 0.00 | 0.00 |
August | 1153.31 | 396.81 | 1216.85 | 567.39 | 649.46 | 0.00 | 0.00 |
September | 1314.20 | 560.47 | 1348.75 | 745.01 | 603.73 | 0.00 | 0.00 |
October | 1182.60 | 743.37 | 1221.68 | 754.42 | 467.26 | 0.00 | 0.00 |
November | 602.01 | 848.49 | 721.96 | 413.68 | 308.28 | 0.00 | 0.00 |
December | 669.15 | 1026.42 | 755.27 | 488.68 | 266.60 | 0.00 | 0.00 |
Annual Sum or Average | 918.95 | 695.74 | 1065.58 | 521.20 | 544.38 | 0.00 | 0.00 |
Minimum of Months | 556.73 | 396.81 | 710.63 | 278.71 | 266.60 | 0.00 | 0.00 |
Maximum of Months | 1314.20 | 1026.42 | 1348.75 | 754.42 | 797.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 111.25 | 206.12 | 146.22 | 86.81 | 59.41 | 0.00 | 0.00 |
February | 194.83 | 183.22 | 224.95 | 139.25 | 85.70 | 0.00 | 0.00 |
March | 211.47 | 162.07 | 242.06 | 129.14 | 112.93 | 0.00 | 0.00 |
April | 213.15 | 133.34 | 255.49 | 110.95 | 144.55 | 0.00 | 0.00 |
May | 177.82 | 110.04 | 233.56 | 69.56 | 164.01 | 0.00 | 0.00 |
June | 156.51 | 86.81 | 213.69 | 57.35 | 156.34 | 0.00 | 0.00 |
July | 190.91 | 79.64 | 233.03 | 85.32 | 147.71 | 0.00 | 0.00 |
August | 233.74 | 80.95 | 250.38 | 116.75 | 133.64 | 0.00 | 0.00 |
September | 271.73 | 109.94 | 277.52 | 153.30 | 124.23 | 0.00 | 0.00 |
October | 242.91 | 146.24 | 251.38 | 155.23 | 96.14 | 0.00 | 0.00 |
November | 121.37 | 172.68 | 148.55 | 85.12 | 63.43 | 0.00 | 0.00 |
December | 134.84 | 210.48 | 155.41 | 100.55 | 54.86 | 0.00 | 0.00 |
Annual Sum or Average | 188.30 | 139.93 | 219.26 | 107.24 | 112.01 | 0.00 | 0.00 |
Minimum of Months | 111.25 | 79.64 | 146.22 | 57.35 | 54.86 | 0.00 | 0.00 |
Maximum of Months | 271.73 | 210.48 | 277.52 | 155.23 | 164.01 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 37969994.77 | 0.123291E+10 | 0.194601E+09 | 45971183.69 | 0.148629E+09 | 0.00 | 0.00 |
February | 0.206174E+09 | 0.989307E+09 | 0.322209E+09 | 0.122909E+09 | 0.199300E+09 | 0.00 | 0.00 |
March | 0.535800E+09 | 0.960297E+09 | 0.573961E+09 | 0.243742E+09 | 0.330219E+09 | 0.00 | 0.00 |
April | 0.104408E+10 | 0.753176E+09 | 0.889195E+09 | 0.451668E+09 | 0.437527E+09 | 0.00 | 0.00 |
May | 0.153255E+10 | 0.657009E+09 | 0.118691E+10 | 0.607527E+09 | 0.579387E+09 | 0.00 | 0.00 |
June | 0.167838E+10 | 0.514940E+09 | 0.125095E+10 | 0.726617E+09 | 0.524336E+09 | 0.00 | 0.00 |
July | 0.193091E+10 | 0.478066E+09 | 0.135062E+10 | 0.885825E+09 | 0.464799E+09 | 0.00 | 0.00 |
August | 0.154601E+10 | 0.487215E+09 | 0.108149E+10 | 0.682460E+09 | 0.399028E+09 | 0.00 | 0.00 |
September | 0.940634E+09 | 0.650850E+09 | 0.744224E+09 | 0.412366E+09 | 0.331858E+09 | 0.00 | 0.00 |
October | 0.423199E+09 | 0.926322E+09 | 0.449666E+09 | 0.206951E+09 | 0.242715E+09 | 0.00 | 0.00 |
November | 95445721.88 | 0.999911E+09 | 0.220692E+09 | 58534098.17 | 0.162158E+09 | 0.00 | 0.00 |
December | 36590638.66 | 0.128973E+10 | 0.164677E+09 | 43582752.43 | 0.121095E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100077E+11 | 0.993973E+10 | 0.842920E+10 | 0.448815E+10 | 0.394105E+10 | 0.00 | 0.00 |
Minimum of Months | 36590638.66 | 0.478066E+09 | 0.164677E+09 | 43582752.43 | 0.121095E+09 | 0.00 | 0.00 |
Maximum of Months | 0.193091E+10 | 0.128973E+10 | 0.135062E+10 | 0.885825E+09 | 0.579387E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.147497E+10 | 0.276176E+10 | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.00 | 0.00 |
February | 0.231239E+10 | 0.227310E+10 | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.00 | 0.00 |
March | 0.274061E+10 | 0.228386E+10 | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.00 | 0.00 |
April | 0.265592E+10 | 0.182800E+10 | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.00 | 0.00 |
May | 0.225478E+10 | 0.158734E+10 | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.00 | 0.00 |
June | 0.190095E+10 | 0.122055E+10 | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.00 | 0.00 |
July | 0.245753E+10 | 0.112520E+10 | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.00 | 0.00 |
August | 0.308893E+10 | 0.108988E+10 | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.00 | 0.00 |
September | 0.339825E+10 | 0.150777E+10 | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.00 | 0.00 |
October | 0.314259E+10 | 0.210736E+10 | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.00 | 0.00 |
November | 0.152999E+10 | 0.233685E+10 | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.00 | 0.00 |
December | 0.177335E+10 | 0.285149E+10 | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.287303E+11 | 0.229732E+11 | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147497E+10 | 0.108988E+10 | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.339825E+10 | 0.285149E+10 | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.149115E+10 | 0.267699E+10 | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.00 | 0.00 |
February | 0.233908E+10 | 0.217218E+10 | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.00 | 0.00 |
March | 0.277563E+10 | 0.215367E+10 | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.00 | 0.00 |
April | 0.269006E+10 | 0.173158E+10 | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.00 | 0.00 |
May | 0.228547E+10 | 0.150364E+10 | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.00 | 0.00 |
June | 0.191924E+10 | 0.116265E+10 | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.00 | 0.00 |
July | 0.246392E+10 | 0.108494E+10 | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.00 | 0.00 |
August | 0.308903E+10 | 0.106283E+10 | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.00 | 0.00 |
September | 0.340641E+10 | 0.145275E+10 | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.00 | 0.00 |
October | 0.316749E+10 | 0.199104E+10 | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.00 | 0.00 |
November | 0.156040E+10 | 0.219928E+10 | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.00 | 0.00 |
December | 0.179226E+10 | 0.274917E+10 | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.289801E+11 | 0.219407E+11 | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.00 | 0.00 |
Minimum of Months | 0.149115E+10 | 0.106283E+10 | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.340641E+10 | 0.274917E+10 | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.297972E+09 | 0.552084E+09 | 0.391640E+09 | 0.232507E+09 | 0.159133E+09 | 0.00 | 0.00 |
February | 0.471336E+09 | 0.443250E+09 | 0.544188E+09 | 0.336867E+09 | 0.207321E+09 | 0.00 | 0.00 |
March | 0.566397E+09 | 0.434086E+09 | 0.648345E+09 | 0.345876E+09 | 0.302469E+09 | 0.00 | 0.00 |
April | 0.552474E+09 | 0.345620E+09 | 0.662239E+09 | 0.287571E+09 | 0.374668E+09 | 0.00 | 0.00 |
May | 0.476282E+09 | 0.294738E+09 | 0.625578E+09 | 0.186305E+09 | 0.439273E+09 | 0.00 | 0.00 |
June | 0.405680E+09 | 0.225004E+09 | 0.553877E+09 | 0.148650E+09 | 0.405227E+09 | 0.00 | 0.00 |
July | 0.511338E+09 | 0.213311E+09 | 0.624144E+09 | 0.228526E+09 | 0.395618E+09 | 0.00 | 0.00 |
August | 0.626047E+09 | 0.216811E+09 | 0.670629E+09 | 0.312698E+09 | 0.357931E+09 | 0.00 | 0.00 |
September | 0.704332E+09 | 0.284977E+09 | 0.719344E+09 | 0.397348E+09 | 0.321996E+09 | 0.00 | 0.00 |
October | 0.650615E+09 | 0.391695E+09 | 0.673289E+09 | 0.415775E+09 | 0.257514E+09 | 0.00 | 0.00 |
November | 0.314602E+09 | 0.447585E+09 | 0.385050E+09 | 0.220633E+09 | 0.164417E+09 | 0.00 | 0.00 |
December | 0.361166E+09 | 0.563737E+09 | 0.416246E+09 | 0.269321E+09 | 0.146926E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.593824E+10 | 0.441290E+10 | 0.691457E+10 | 0.338208E+10 | 0.353249E+10 | 0.00 | 0.00 |
Minimum of Months | 0.297972E+09 | 0.213311E+09 | 0.385050E+09 | 0.148650E+09 | 0.146926E+09 | 0.00 | 0.00 |
Maximum of Months | 0.704332E+09 | 0.563737E+09 | 0.719344E+09 | 0.415775E+09 | 0.439273E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.11 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.09 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.03 | 5.25 | 4.23 | 1.21 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.01 | 7.49 | 3.85 | 3.74 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.79 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.40 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.56 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.54 | 10.74 | 2.23 | 5.46 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.18 | 7.19 | 4.02 | 2.09 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.12 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.11 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.56 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.48 | 7.20 | 8.40 | 3.88 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.15 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.40 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.20 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.35 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.72 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.76 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.67 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.67 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.47 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.93 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.42 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.42 | 0.00 | 0.00 | 3.88 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.76 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -1.9 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.18 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.56 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.56 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.48 | 11-JAN-21:00 | 11.10 | 10.00 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 12.41 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.44 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.27 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.57 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.72 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.16 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.12 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.96 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.04 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.70 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.48 | 11.10 | 6.70 | 0.00 | 6.35 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 28.90 | 15.70 | 6.70 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.48 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.34 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.09 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.76 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.92 | 2.10 | 6.88 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.00 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.09 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.282409E+10 | -.225146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -572624011.7 | 58.99 | 0.00 | 0.00 |
February | 0.257688E+10 | -.206443E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -512446807.7 | 59.00 | 0.00 | 0.00 |
March | 0.287183E+10 | -.231594E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -555894305.6 | 58.99 | 0.00 | 0.00 |
April | 0.266623E+10 | -.214137E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -524866000.4 | 58.99 | 0.00 | 0.00 |
May | 0.266316E+10 | -.213334E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -529816338.7 | 58.99 | 0.00 | 0.00 |
June | 0.251838E+10 | -.201361E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -504770441.2 | 58.99 | 0.00 | 0.00 |
July | 0.248137E+10 | -.196382E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -517555296.1 | 58.99 | 0.00 | 0.00 |
August | 0.252621E+10 | -.200938E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -516829553.1 | 58.99 | 0.00 | 0.00 |
September | 0.244144E+10 | -.193717E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -504274412.8 | 58.99 | 0.00 | 0.00 |
October | 0.257250E+10 | -.203473E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -537770550.9 | 58.99 | 0.00 | 0.00 |
November | 0.257815E+10 | -.203904E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -539109063.7 | 58.99 | 0.00 | 0.00 |
December | 0.276723E+10 | -.219755E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -569675604.7 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314875E+11 | -.251018E+11 | 8760.00 | -.638563E+10 | 58.99 | |||||
Minimum of Months | 0.244144E+10 | -.231594E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -572624011.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.287183E+10 | -.193717E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -504274412.8 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | ||||||||||
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.889119E+10 | 44726.37 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.620784E+10 | 44726.37 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246029E+10 | 44726.37 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.823324E+09 | 44726.37 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 52685405.88 | 43825.84 | 18-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 56208.95 | 468.41 | 14-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.276179E+09 | 44726.37 | 16-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.298145E+10 | 44726.37 | 01-NOV-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.681516E+10 | 44726.37 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285082E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.889119E+10 | 44726.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.201544E+11 | 230385.12 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123518E+11 | 230385.12 | 19-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209691E+10 | 43756.12 | 25-MAR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.309271E+09 | 25610.22 | 18-APR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 56468324.18 | 11301.39 | 16-OCT-06:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.556561E+10 | 62353.82 | 28-NOV-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143987E+11 | 195358.27 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.549331E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201544E+11 | 230385.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.248162E+10 | 34978.51 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140168E+10 | 34978.51 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.469999E+09 | 34978.51 | 05-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154490E+09 | 34978.51 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8824399.37 | 13400.16 | 18-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26729479.74 | 18299.64 | 28-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.644608E+09 | 34978.51 | 11-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182763E+10 | 34978.51 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.701559E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.248162E+10 | 34978.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.558323E+10 | 29854.20 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.340722E+10 | 29854.20 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175687E+10 | 29854.20 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.837147E+09 | 29854.20 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223795E+09 | 29854.20 | 18-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19483348.54 | 8204.14 | 14-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21085957.06 | 2188.47 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.389974E+09 | 29854.20 | 28-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225510E+10 | 29854.20 | 10-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.456022E+10 | 29854.20 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190541E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.558323E+10 | 29854.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114485E+11 | 23962.96 | 07-JAN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.842164E+10 | 24399.11 | 18-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.650012E+10 | 17211.81 | 05-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.393508E+10 | 14325.92 | 18-APR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.251949E+10 | 12698.16 | 23-MAY-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.967013E+09 | 9172.87 | 13-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.239292E+09 | 5973.36 | 12-JUL-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120266E+09 | 6019.92 | 01-AUG-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137881E+10 | 8787.36 | 26-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.381474E+10 | 11632.58 | 31-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.804357E+10 | 19686.40 | 12-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105143E+11 | 23932.88 | 26-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.579028E+11 | |||||||
Minimum of Months | 0.120266E+09 | 5973.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114485E+11 | 24399.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 41660.90 | 33362.77 | 66.26 | 28-FEB-14:10 | 52.90 | 0.00 |
March | 0.00 | 0.00 | 72214.64 | 60307.16 | 101.18 | 10-MAR-17:00 | 82.59 | 0.00 |
April | 0.00 | 0.00 | 0.527651E+09 | 0.489565E+09 | 11167.61 | 27-APR-15:00 | 9889.55 | 0.00 |
May | 0.00 | 0.00 | 0.127733E+10 | 0.111891E+10 | 12302.02 | 06-MAY-13:50 | 9921.57 | 0.00 |
June | 0.00 | 0.00 | 0.267326E+10 | 0.246545E+10 | 29635.78 | 28-JUN-20:45 | 22153.59 | 0.00 |
July | 0.00 | 0.00 | 0.655076E+10 | 0.552774E+10 | 31097.47 | 26-JUL-20:30 | 22448.37 | 0.00 |
August | 0.00 | 0.00 | 0.843626E+10 | 0.706897E+10 | 31026.02 | 24-AUG-21:21 | 23454.66 | 0.00 |
September | 0.00 | 0.00 | 0.215448E+10 | 0.173410E+10 | 30213.37 | 13-SEP-20:49 | 21203.60 | 0.00 |
October | 0.00 | 0.00 | 52948974.93 | 52889206.07 | 4404.15 | 04-OCT-15:00 | 4404.15 | 0.00 |
November | 0.00 | 0.00 | 31901468.52 | 23672809.94 | 3305.25 | 04-NOV-14:20 | 2487.32 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.217047E+11 | 0.184814E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.843626E+10 | 0.706897E+10 | 31097.47 | 23454.66 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 28339746.87 | 27714121.32 | 6478.10 | 27-FEB-15:10 | 6478.10 | 0.00 |
March | 0.00 | 0.00 | 0.150821E+09 | 0.150459E+09 | 16122.14 | 18-MAR-16:00 | 16122.14 | 0.00 |
April | 0.00 | 0.00 | 0.478733E+10 | 0.452011E+10 | 135745.77 | 27-APR-20:21 | 119760.95 | 0.00 |
May | 0.00 | 0.00 | 0.109866E+11 | 0.970657E+10 | 141882.77 | 07-MAY-18:18 | 111127.66 | 0.00 |
June | 0.00 | 0.00 | 0.210676E+11 | 0.194639E+11 | 141128.83 | 11-JUN-18:19 | 116898.41 | 0.00 |
July | 0.00 | 0.00 | 0.419862E+11 | 0.357549E+11 | 145500.26 | 26-JUL-20:16 | 107365.22 | 0.00 |
August | 0.00 | 0.00 | 0.523584E+11 | 0.442254E+11 | 145219.91 | 24-AUG-21:02 | 113791.75 | 0.00 |
September | 0.00 | 0.00 | 0.168787E+11 | 0.136652E+11 | 141785.73 | 13-SEP-20:11 | 101092.60 | 0.00 |
October | 0.00 | 0.00 | 0.945509E+09 | 0.926226E+09 | 132118.68 | 04-OCT-20:33 | 127229.50 | 0.00 |
November | 0.00 | 0.00 | 0.482516E+09 | 0.362122E+09 | 33601.32 | 04-NOV-14:20 | 25883.58 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.149672E+12 | 0.128803E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.523584E+11 | 0.442254E+11 | 145500.26 | 127229.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 241.57 | 232.83 | 0.12 | 11-JAN-18:20 | 0.12 | 0.00 |
February | 0.00 | 0.00 | 29155603.40 | 29065031.42 | 3604.11 | 27-FEB-14:57 | 3604.11 | 0.00 |
March | 0.00 | 0.00 | 47272056.72 | 47246832.35 | 4202.39 | 18-MAR-14:00 | 4202.39 | 0.00 |
April | 0.00 | 0.00 | 0.866249E+09 | 0.829682E+09 | 21018.00 | 27-APR-20:10 | 18694.39 | 0.00 |
May | 0.00 | 0.00 | 0.147099E+10 | 0.132581E+10 | 21774.39 | 07-MAY-18:11 | 17175.35 | 0.00 |
June | 0.00 | 0.00 | 0.253082E+10 | 0.240097E+10 | 21662.52 | 11-JUN-18:11 | 18104.63 | 0.00 |
July | 0.00 | 0.00 | 0.571543E+10 | 0.499835E+10 | 22343.88 | 26-JUL-20:11 | 16559.14 | 0.00 |
August | 0.00 | 0.00 | 0.794596E+10 | 0.694605E+10 | 22286.48 | 24-AUG-20:41 | 17961.78 | 0.00 |
September | 0.00 | 0.00 | 0.341128E+10 | 0.283182E+10 | 21843.23 | 15-SEP-20:10 | 14665.23 | 0.00 |
October | 0.00 | 0.00 | 0.427132E+09 | 0.412223E+09 | 20742.71 | 04-OCT-20:11 | 20742.71 | 0.00 |
November | 0.00 | 0.00 | 0.152182E+09 | 0.115946E+09 | 9465.84 | 04-NOV-14:00 | 7468.39 | 0.00 |
December | 0.00 | 0.00 | 6251.97 | 6247.27 | 0.43 | 02-DEC-13:00 | 0.43 | 0.00 |
Annual Sum or Average | 0.225965E+11 | 0.199372E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 241.57 | 232.83 | 0.12 | 0.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.794596E+10 | 0.694605E+10 | 22343.88 | 20742.71 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 94560321.99 | 91226095.28 | 4517.80 | 27-FEB-15:10 | 4517.80 | 0.00 |
March | 0.00 | 0.00 | 0.355474E+09 | 0.352190E+09 | 4921.68 | 18-MAR-14:00 | 4921.68 | 0.00 |
April | 0.00 | 0.00 | 0.130650E+10 | 0.124671E+10 | 9403.39 | 27-APR-14:10 | 8814.47 | 0.00 |
May | 0.00 | 0.00 | 0.227977E+10 | 0.209623E+10 | 17702.55 | 14-MAY-18:18 | 17702.55 | 0.00 |
June | 0.00 | 0.00 | 0.354284E+10 | 0.329841E+10 | 18415.11 | 22-JUN-20:20 | 16531.94 | 0.00 |
July | 0.00 | 0.00 | 0.590206E+10 | 0.523494E+10 | 18821.06 | 27-JUL-20:16 | 15122.07 | 0.00 |
August | 0.00 | 0.00 | 0.763084E+10 | 0.667718E+10 | 18628.44 | 29-AUG-20:41 | 16167.62 | 0.00 |
September | 0.00 | 0.00 | 0.476808E+10 | 0.418335E+10 | 18516.54 | 13-SEP-20:41 | 16009.84 | 0.00 |
October | 0.00 | 0.00 | 0.162576E+10 | 0.155533E+10 | 14323.02 | 04-OCT-20:11 | 14323.02 | 0.00 |
November | 0.00 | 0.00 | 0.240129E+09 | 0.200596E+09 | 8392.83 | 04-NOV-14:00 | 7094.91 | 0.00 |
December | 0.00 | 0.00 | 22159331.99 | 22159331.99 | 1312.27 | 02-DEC-13:30 | 1312.27 | 0.00 |
Annual Sum or Average | 0.277682E+11 | 0.249583E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.763084E+10 | 0.667718E+10 | 18821.06 | 17702.55 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.293530E+10 | 0.55 | 1824.24 | 01-JAN-00:17 | 0.91 |
February | 0.255595E+10 | 0.53 | 1824.24 | 01-FEB-05:01 | 0.91 |
March | 0.266218E+10 | 0.50 | 1824.24 | 01-MAR-05:02 | 0.91 |
April | 0.222966E+10 | 0.43 | 1824.24 | 01-APR-04:01 | 0.91 |
May | 0.189604E+10 | 0.35 | 1824.24 | 01-MAY-04:03 | 0.91 |
June | 0.132049E+10 | 0.25 | 1824.24 | 01-JUN-07:10 | 0.91 |
July | 0.799626E+09 | 0.15 | 1824.24 | 01-JUL-07:10 | 0.91 |
August | 0.644623E+09 | 0.12 | 1824.24 | 01-AUG-07:10 | 0.90 |
September | 0.142675E+10 | 0.27 | 1824.24 | 01-SEP-07:10 | 0.90 |
October | 0.231818E+10 | 0.43 | 1824.24 | 01-OCT-07:05 | 0.90 |
November | 0.257560E+10 | 0.49 | 1824.24 | 01-NOV-04:02 | 0.91 |
December | 0.287332E+10 | 0.53 | 1824.24 | 01-DEC-05:01 | 0.91 |
Annual Sum or Average | 0.242377E+11 | 0.38 | |||
Minimum of Months | 0.644623E+09 | 0.12 | 1824.24 | 0.90 | |
Maximum of Months | 0.293530E+10 | 0.55 | 1824.24 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.306911E+10 | 0.57 | 1874.59 | 03-JAN-14:00 | 0.91 |
February | 0.277774E+10 | 0.57 | 1874.59 | 01-FEB-06:40 | 0.91 |
March | 0.309113E+10 | 0.58 | 1874.59 | 04-MAR-07:43 | 0.91 |
April | 0.295169E+10 | 0.56 | 1874.59 | 04-APR-06:13 | 0.91 |
May | 0.303133E+10 | 0.55 | 1874.59 | 02-MAY-16:30 | 0.91 |
June | 0.295698E+10 | 0.55 | 1874.59 | 01-JUN-11:30 | 0.91 |
July | 0.302368E+10 | 0.55 | 1874.59 | 01-JUL-09:53 | 0.90 |
August | 0.307799E+10 | 0.56 | 1874.59 | 01-AUG-12:20 | 0.90 |
September | 0.293762E+10 | 0.55 | 1874.59 | 01-SEP-13:00 | 0.90 |
October | 0.300793E+10 | 0.55 | 1874.59 | 03-OCT-13:50 | 0.91 |
November | 0.292714E+10 | 0.56 | 1874.59 | 04-NOV-10:00 | 0.90 |
December | 0.306578E+10 | 0.57 | 1874.59 | 04-DEC-20:55 | 0.91 |
Annual Sum or Average | 0.359181E+11 | 0.56 | |||
Minimum of Months | 0.277774E+10 | 0.55 | 1874.59 | 0.90 | |
Maximum of Months | 0.309113E+10 | 0.58 | 1874.59 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.216150E+11 | 0.86 | 13492.50 | 01-JAN-13:40 | 1.43 |
February | 0.196235E+11 | 0.86 | 13492.50 | 02-FEB-07:50 | 1.43 |
March | 0.220036E+11 | 0.87 | 13492.50 | 01-MAR-07:50 | 1.43 |
April | 0.211820E+11 | 0.87 | 13492.50 | 01-APR-07:20 | 1.43 |
May | 0.219847E+11 | 0.87 | 13492.50 | 01-MAY-11:15 | 1.42 |
June | 0.217647E+11 | 0.90 | 13492.50 | 01-JUN-05:40 | 1.42 |
July | 0.224939E+11 | 0.91 | 13492.50 | 01-JUL-18:07 | 1.43 |
August | 0.229708E+11 | 0.92 | 13492.50 | 01-AUG-12:30 | 1.42 |
September | 0.216034E+11 | 0.89 | 13492.50 | 01-SEP-05:02 | 1.42 |
October | 0.216327E+11 | 0.85 | 13492.50 | 02-OCT-10:33 | 1.42 |
November | 0.208378E+11 | 0.85 | 13492.50 | 01-NOV-10:40 | 1.42 |
December | 0.216636E+11 | 0.86 | 13492.50 | 02-DEC-08:00 | 1.43 |
Annual Sum or Average | 0.259376E+12 | 0.87 | |||
Minimum of Months | 0.196235E+11 | 0.85 | 13492.50 | 1.42 | |
Maximum of Months | 0.229708E+11 | 0.92 | 13492.50 | 1.43 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.240156E+10 | 0.59 | 1483.95 | 28-JAN-09:20 | 0.95 |
February | 0.217370E+10 | 0.59 | 1483.95 | 01-FEB-07:50 | 0.95 |
March | 0.242682E+10 | 0.59 | 1483.95 | 01-MAR-07:08 | 0.95 |
April | 0.233206E+10 | 0.58 | 1483.95 | 01-APR-06:13 | 0.95 |
May | 0.240837E+10 | 0.58 | 1483.95 | 12-MAY-11:20 | 0.94 |
June | 0.236467E+10 | 0.59 | 1483.95 | 17-JUN-10:05 | 0.94 |
July | 0.245249E+10 | 0.60 | 1483.95 | 06-JUL-09:43 | 0.94 |
August | 0.255521E+10 | 0.63 | 1483.95 | 30-AUG-05:20 | 0.94 |
September | 0.240609E+10 | 0.62 | 1483.95 | 01-SEP-05:15 | 0.94 |
October | 0.238654E+10 | 0.57 | 1483.95 | 14-OCT-16:00 | 0.94 |
November | 0.230120E+10 | 0.58 | 1483.95 | 23-NOV-08:20 | 0.95 |
December | 0.240177E+10 | 0.59 | 1483.95 | 01-DEC-07:00 | 0.95 |
Annual Sum or Average | 0.286105E+11 | 0.59 | |||
Minimum of Months | 0.217370E+10 | 0.57 | 1483.95 | 0.94 | |
Maximum of Months | 0.255521E+10 | 0.63 | 1483.95 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.199973E+10 | 0.60 | 1227.45 | 06-JAN-20:00 | 0.95 |
February | 0.180857E+10 | 0.60 | 1227.45 | 01-FEB-09:10 | 0.95 |
March | 0.201593E+10 | 0.60 | 1227.45 | 01-MAR-06:20 | 0.95 |
April | 0.193096E+10 | 0.59 | 1227.45 | 07-APR-06:50 | 0.95 |
May | 0.198637E+10 | 0.57 | 1227.45 | 01-MAY-05:17 | 0.94 |
June | 0.193848E+10 | 0.58 | 1227.45 | 14-JUN-05:30 | 0.94 |
July | 0.198447E+10 | 0.59 | 1227.45 | 06-JUL-09:17 | 0.94 |
August | 0.203737E+10 | 0.64 | 1227.45 | 03-AUG-19:15 | 0.94 |
September | 0.194000E+10 | 0.61 | 1227.45 | 02-SEP-19:00 | 0.94 |
October | 0.197025E+10 | 0.57 | 1227.45 | 19-OCT-06:20 | 0.94 |
November | 0.191218E+10 | 0.58 | 1227.45 | 01-NOV-06:15 | 0.94 |
December | 0.199857E+10 | 0.59 | 1227.45 | 03-DEC-10:20 | 0.95 |
Annual Sum or Average | 0.235229E+11 | 0.59 | |||
Minimum of Months | 0.180857E+10 | 0.57 | 1227.45 | 0.94 | |
Maximum of Months | 0.203737E+10 | 0.64 | 1227.45 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.34 | 0.00 |
February | 0.85 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.06 | 0.00 |
July | 0.11 | 0.00 |
August | 0.08 | 0.00 |
September | 0.00 | 0.00 |
October | 0.06 | 0.00 |
November | 0.12 | 0.00 |
December | 0.65 | 0.00 |
Annual Sum or Average | 3.26 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.34 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.62 | 1.72 |
February | 0.00 | 0.00 |
March | 1.49 | 25.84 |
April | 1.12 | 22.65 |
May | 1.49 | 1.44 |
June | 3.49 | 0.62 |
July | 5.15 | 0.00 |
August | 4.51 | 0.00 |
September | 1.86 | 0.00 |
October | 0.94 | 23.56 |
November | 0.17 | 25.84 |
December | 0.33 | 0.00 |
Annual Sum or Average | 21.19 | 4.52 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 5.15 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.59 | 0.00 |
February | 0.46 | 0.00 |
March | 0.17 | 2.44 |
April | 0.44 | 0.00 |
May | 0.69 | 0.00 |
June | 1.15 | 0.00 |
July | 3.33 | 0.00 |
August | 4.89 | 0.00 |
September | 2.46 | 0.00 |
October | 0.34 | 0.00 |
November | 0.12 | 0.00 |
December | 0.36 | 0.00 |
Annual Sum or Average | 14.99 | 0.03 |
Minimum of Months | 0.12 | 0.00 |
Maximum of Months | 4.89 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.20 | 0.00 |
February | 0.60 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.08 | 0.00 |
September | 0.00 | 0.00 |
October | 0.06 | 0.00 |
November | 0.15 | 0.00 |
December | 0.57 | 0.00 |
Annual Sum or Average | 2.65 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.20 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 43.81 | 0.00 |
February | 41.57 | 0.00 |
March | 36.58 | 0.00 |
April | 24.09 | 0.00 |
May | 23.07 | 0.00 |
June | 24.63 | 0.00 |
July | 28.31 | 0.00 |
August | 20.79 | 0.00 |
September | 22.66 | 0.00 |
October | 20.62 | 0.00 |
November | 39.18 | 0.00 |
December | 49.03 | 0.00 |
Annual Sum or Average | 374.33 | 0.00 |
Minimum of Months | 20.62 | 0.00 |
Maximum of Months | 49.03 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.306911E+10 | 0.111140E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.277775E+10 | 0.775979E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.309115E+10 | 0.307537E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.311158E+10 | 0.102915E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.340354E+10 | 65856757.34 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.373436E+10 | 70261.19 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.490958E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.552135E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.355504E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.302365E+10 | 0.345224E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.293667E+10 | 0.372681E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.306578E+10 | 0.851896E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.421996E+11 | 0.356352E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.277775E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.552135E+10 | 0.111140E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.216150E+11 | 0.254314E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.196328E+11 | 0.155858E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.220522E+11 | 0.264595E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.226938E+11 | 0.390248E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.253432E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.282078E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.352506E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.389292E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.266922E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.219297E+11 | 71253405.90 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.209890E+11 | 0.702285E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.216636E+11 | 0.181687E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.304999E+12 | 0.693163E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.196328E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.389292E+11 | 0.254314E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.240156E+10 | 0.310203E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.218230E+10 | 0.175210E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.244054E+10 | 0.587499E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.258142E+10 | 0.193112E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.282589E+10 | 11030499.22 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.308975E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.407235E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.479472E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.333911E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.250711E+10 | 33411849.68 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.234322E+10 | 0.805760E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.240178E+10 | 0.228454E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.349798E+11 | 0.876949E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.218230E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.479472E+10 | 0.310203E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.199973E+10 | 0.697904E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.183333E+10 | 0.425903E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.210925E+10 | 0.219608E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.227184E+10 | 0.104643E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.257790E+10 | 0.279744E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.285701E+10 | 24354185.67 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.350258E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.400133E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.313264E+10 | 26357446.33 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.238485E+10 | 0.487468E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.197259E+10 | 0.281887E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.200454E+10 | 0.570028E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.306476E+11 | 0.238177E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.183333E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.400133E+10 | 0.697904E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.306911E+10 | 0.00 | 0.889119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277774E+10 | 41660.90 | 0.620784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.309113E+10 | 72214.64 | 0.246029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.295169E+10 | 0.527651E+09 | 0.823324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.303133E+10 | 0.127733E+10 | 52685405.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.295698E+10 | 0.267326E+10 | 56208.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.302368E+10 | 0.655076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.307799E+10 | 0.843626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.293762E+10 | 0.215448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.300793E+10 | 52948974.93 | 0.276179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.292714E+10 | 31901468.52 | 0.298145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.306578E+10 | 0.00 | 0.681516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.359181E+11 | 0.217047E+11 | 0.285082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.277774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.309113E+10 | 0.843626E+10 | 0.889119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.216150E+11 | 0.00 | 0.201544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196235E+11 | 28339746.87 | 0.123518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.220036E+11 | 0.150821E+09 | 0.209691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.211820E+11 | 0.478733E+10 | 0.309271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.219847E+11 | 0.109866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.217647E+11 | 0.210676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.224939E+11 | 0.419862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.229708E+11 | 0.523584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216034E+11 | 0.168787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.216327E+11 | 0.945509E+09 | 56468324.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.208378E+11 | 0.482516E+09 | 0.556561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216636E+11 | 0.00 | 0.143987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259376E+12 | 0.149672E+12 | 0.549331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.196235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.229708E+11 | 0.523584E+11 | 0.201544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.240156E+10 | 241.57 | 0.248162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217370E+10 | 29155603.40 | 0.140168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242682E+10 | 47272056.72 | 0.469999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.233206E+10 | 0.866249E+09 | 0.154490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240837E+10 | 0.147099E+10 | 8824399.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.236467E+10 | 0.253082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.245249E+10 | 0.571543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.255521E+10 | 0.794596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.240609E+10 | 0.341128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.238654E+10 | 0.427132E+09 | 26729479.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.230120E+10 | 0.152182E+09 | 0.644608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240177E+10 | 6251.97 | 0.182763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286105E+11 | 0.225965E+11 | 0.701559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.217370E+10 | 241.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.255521E+10 | 0.794596E+10 | 0.248162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.199973E+10 | 0.00 | 0.558323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180857E+10 | 94560321.99 | 0.340722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.201593E+10 | 0.355474E+09 | 0.175687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.193096E+10 | 0.130650E+10 | 0.837147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198637E+10 | 0.227977E+10 | 0.223795E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193848E+10 | 0.354284E+10 | 19483348.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.198447E+10 | 0.590206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.203737E+10 | 0.763084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194000E+10 | 0.476808E+10 | 21085957.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197025E+10 | 0.162576E+10 | 0.389974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191218E+10 | 0.240129E+09 | 0.225510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199857E+10 | 22159331.99 | 0.456022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235229E+11 | 0.277682E+11 | 0.190541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.180857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.203737E+10 | 0.763084E+10 | 0.558323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.306911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277774E+10 | 0.00 | 0.00 | 0.00 | 12814.00 | 0.00 | 0.775979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.309113E+10 | 0.00 | 0.00 | 0.00 | 22215.42 | 0.00 | 0.307537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.295169E+10 | 0.00 | 0.00 | 0.00 | 0.159891E+09 | 0.00 | 0.102915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.303133E+10 | 0.00 | 0.00 | 0.00 | 0.372212E+09 | 0.00 | 65856757.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.295698E+10 | 0.00 | 0.00 | 0.00 | 0.777382E+09 | 0.00 | 70261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.302368E+10 | 0.00 | 0.00 | 0.00 | 0.188590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.307799E+10 | 0.00 | 0.00 | 0.00 | 0.244336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.293762E+10 | 0.00 | 0.00 | 0.00 | 0.617428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.300793E+10 | 0.00 | 0.00 | 0.00 | 15727253.78 | 0.00 | 0.345224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.292714E+10 | 0.00 | 0.00 | 0.00 | 9534489.56 | 0.00 | 0.372681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.306578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.359181E+11 | 0.00 | 0.00 | 0.00 | 0.628147E+10 | 0.00 | 0.356352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.277774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.309113E+10 | 0.00 | 0.00 | 0.00 | 0.244336E+10 | 0.00 | 0.111140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.216150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196235E+11 | 0.00 | 0.00 | 0.00 | 9323744.20 | 0.00 | 0.155858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.220036E+11 | 0.00 | 0.00 | 0.00 | 48616248.37 | 0.00 | 0.264595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.211820E+11 | 0.00 | 0.00 | 0.00 | 0.151184E+10 | 0.00 | 0.390248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.219847E+11 | 0.00 | 0.00 | 0.00 | 0.335850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.217647E+11 | 0.00 | 0.00 | 0.00 | 0.644315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.224939E+11 | 0.00 | 0.00 | 0.00 | 0.127567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.229708E+11 | 0.00 | 0.00 | 0.00 | 0.159584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216034E+11 | 0.00 | 0.00 | 0.00 | 0.508888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.216327E+11 | 0.00 | 0.00 | 0.00 | 0.297029E+09 | 0.00 | 71253405.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.208378E+11 | 0.00 | 0.00 | 0.00 | 0.151152E+09 | 0.00 | 0.702285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259376E+12 | 0.00 | 0.00 | 0.00 | 0.456236E+11 | 0.00 | 0.693163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.196235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.229708E+11 | 0.00 | 0.00 | 0.00 | 0.159584E+11 | 0.00 | 0.254314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.240156E+10 | 0.00 | 0.00 | 0.00 | 74.44 | 0.00 | 0.310203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217370E+10 | 0.00 | 0.00 | 0.00 | 8598875.74 | 0.00 | 0.175210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242682E+10 | 0.00 | 0.00 | 0.00 | 13725802.14 | 0.00 | 0.587499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.233206E+10 | 0.00 | 0.00 | 0.00 | 0.249362E+09 | 0.00 | 0.193112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240837E+10 | 0.00 | 0.00 | 0.00 | 0.417512E+09 | 0.00 | 11030499.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.236467E+10 | 0.00 | 0.00 | 0.00 | 0.725077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.245249E+10 | 0.00 | 0.00 | 0.00 | 0.161986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.255521E+10 | 0.00 | 0.00 | 0.00 | 0.223951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.240609E+10 | 0.00 | 0.00 | 0.00 | 0.933018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.238654E+10 | 0.00 | 0.00 | 0.00 | 0.120571E+09 | 0.00 | 33411849.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.230120E+10 | 0.00 | 0.00 | 0.00 | 42022018.52 | 0.00 | 0.805760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240177E+10 | 0.00 | 0.00 | 0.00 | 1916.61 | 0.00 | 0.228454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286105E+11 | 0.00 | 0.00 | 0.00 | 0.636926E+10 | 0.00 | 0.876949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.217370E+10 | 0.00 | 0.00 | 0.00 | 74.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.255521E+10 | 0.00 | 0.00 | 0.00 | 0.223951E+10 | 0.00 | 0.310203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.199973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180857E+10 | 0.00 | 0.00 | 0.00 | 24766182.28 | 0.00 | 0.425903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.201593E+10 | 0.00 | 0.00 | 0.00 | 93319697.42 | 0.00 | 0.219608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.193096E+10 | 0.00 | 0.00 | 0.00 | 0.340881E+09 | 0.00 | 0.104643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198637E+10 | 0.00 | 0.00 | 0.00 | 0.591536E+09 | 0.00 | 0.279744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193848E+10 | 0.00 | 0.00 | 0.00 | 0.918528E+09 | 0.00 | 24354185.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.198447E+10 | 0.00 | 0.00 | 0.00 | 0.151811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.203737E+10 | 0.00 | 0.00 | 0.00 | 0.196396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194000E+10 | 0.00 | 0.00 | 0.00 | 0.119264E+10 | 0.00 | 26357446.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197025E+10 | 0.00 | 0.00 | 0.00 | 0.414598E+09 | 0.00 | 0.487468E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191218E+10 | 0.00 | 0.00 | 0.00 | 60410417.38 | 0.00 | 0.281887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199857E+10 | 0.00 | 0.00 | 0.00 | 5965068.77 | 0.00 | 0.570028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235229E+11 | 0.00 | 0.00 | 0.00 | 0.712472E+10 | 0.00 | 0.238177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.180857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.203737E+10 | 0.00 | 0.00 | 0.00 | 0.196396E+10 | 0.00 | 0.697904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.258690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520941E+10 | 0.00 | 0.00 | 0.20 |
February | 0.304603E+10 | 0.00 | 0.00 | 48076.13 | 0.00 | 0.344750E+10 | 0.127400E+09 | 0.00 | 0.21 |
March | 0.531307E+10 | 0.00 | 0.00 | 95127.51 | 0.00 | 0.120514E+10 | 0.245246E+09 | 0.00 | 0.21 |
April | 0.372033E+10 | 6094113.46 | 0.00 | 2055101.97 | 0.00 | 0.356284E+09 | 0.225266E+10 | 0.00 | 0.27 |
May | 0.173118E+10 | 3742851.49 | 0.00 | 7444424.14 | 0.00 | 869439.60 | 0.606582E+10 | 0.00 | 0.45 |
June | 0.665141E+09 | 5920669.25 | 0.00 | 12389141.79 | 0.00 | 0.00 | 0.781043E+10 | 0.00 | 0.65 |
July | 0.340489E+09 | 0.175897E+09 | 0.00 | 14105489.57 | 0.00 | 0.00 | 0.657290E+10 | 0.00 | 0.71 |
August | 0.274029E+09 | 0.384016E+09 | 0.00 | 11966421.94 | 0.00 | 0.00 | 0.570182E+10 | 0.00 | 0.65 |
September | 0.928908E+09 | 5425369.78 | 0.00 | 10834239.91 | 0.00 | 0.00 | 0.719007E+10 | 0.00 | 0.58 |
October | 0.362956E+10 | 0.00 | 0.00 | 2599070.01 | 0.00 | 0.114178E+09 | 0.329615E+10 | 0.00 | 0.28 |
November | 0.442889E+10 | 0.00 | 0.00 | 408648.98 | 0.00 | 0.162673E+10 | 0.590003E+09 | 0.00 | 0.22 |
December | 0.344471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399621E+10 | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.301092E+11 | 0.581096E+09 | 0.00 | 61945741.95 | 0.00 | 0.159563E+11 | 0.398525E+11 | 0.00 | 0.39 |
Minimum of Months | 0.274029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.531307E+10 | 0.384016E+09 | 0.00 | 14105489.57 | 0.00 | 0.520941E+10 | 0.781043E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.510723E+11 | 0.00 | 0.00 | 4188.80 | 0.00 | 0.999706E+10 | 68346084.91 | 0.00 | 0.39 |
February | 0.436882E+11 | 0.00 | 0.00 | 2812418.12 | 0.00 | 0.529310E+10 | 0.388876E+10 | 0.00 | 0.41 |
March | 0.400512E+11 | 0.00 | 0.00 | 10624367.05 | 0.00 | 0.181080E+09 | 0.154705E+11 | 0.00 | 0.43 |
April | 0.195769E+11 | 71953846.86 | 0.00 | 34700375.06 | 0.00 | 0.00 | 0.332507E+11 | 0.00 | 0.55 |
May | 0.927828E+10 | 60406473.51 | 0.00 | 67209233.39 | 0.00 | 0.00 | 0.482606E+11 | 0.00 | 0.75 |
June | 0.332788E+10 | 63202394.86 | 0.00 | 90103333.88 | 0.00 | 0.00 | 0.503701E+11 | 0.00 | 0.93 |
July | 0.967779E+09 | 0.144537E+10 | 0.00 | 92345836.03 | 0.00 | 0.00 | 0.396113E+11 | 0.00 | 0.95 |
August | 0.129595E+10 | 0.315532E+10 | 0.00 | 79703196.63 | 0.00 | 0.00 | 0.331071E+11 | 0.00 | 0.91 |
September | 0.524743E+10 | 81820390.85 | 0.00 | 76174778.22 | 0.00 | 0.00 | 0.466539E+11 | 0.00 | 0.85 |
October | 0.191940E+11 | 0.00 | 0.00 | 34246809.77 | 0.00 | 0.00 | 0.366991E+11 | 0.00 | 0.55 |
November | 0.409485E+11 | 0.00 | 0.00 | 8695908.44 | 0.00 | 0.184360E+10 | 0.102732E+11 | 0.00 | 0.42 |
December | 0.513142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698281E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.285963E+12 | 0.487807E+10 | 0.00 | 0.496620E+09 | 0.00 | 0.242976E+11 | 0.317654E+12 | 0.00 | 0.63 |
Minimum of Months | 0.967779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.513142E+11 | 0.315532E+10 | 0.00 | 92345836.03 | 0.00 | 0.999706E+10 | 0.503701E+11 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.430466E+10 | 0.00 | 0.00 | 181616.19 | 0.00 | 0.127470E+10 | 0.279346E+09 | 0.00 | 0.40 |
February | 0.309396E+10 | 0.00 | 0.00 | 1763992.44 | 0.00 | 0.622844E+09 | 0.181869E+10 | 0.00 | 0.47 |
March | 0.217247E+10 | 0.00 | 0.00 | 4265223.68 | 0.00 | 0.230845E+09 | 0.418728E+10 | 0.00 | 0.58 |
April | 0.119331E+10 | 9274019.59 | 0.00 | 7024211.74 | 0.00 | 57973873.16 | 0.517906E+10 | 0.00 | 0.79 |
May | 0.708512E+09 | 13440886.37 | 0.00 | 10014156.10 | 0.00 | 0.00 | 0.628180E+10 | 0.00 | 1.09 |
June | 0.314240E+09 | 9759320.80 | 0.00 | 12430272.98 | 0.00 | 0.00 | 0.642457E+10 | 0.00 | 1.40 |
July | 94445676.28 | 0.184736E+09 | 0.00 | 13159043.94 | 0.00 | 0.00 | 0.534869E+10 | 0.00 | 1.49 |
August | 0.113214E+09 | 0.410073E+09 | 0.00 | 11972272.82 | 0.00 | 0.00 | 0.472735E+10 | 0.00 | 1.44 |
September | 0.296859E+09 | 52969808.62 | 0.00 | 14509330.69 | 0.00 | 0.00 | 0.690017E+10 | 0.00 | 1.41 |
October | 0.103496E+10 | 0.00 | 0.00 | 8985870.28 | 0.00 | 0.00 | 0.659332E+10 | 0.00 | 0.88 |
November | 0.297238E+10 | 0.00 | 0.00 | 2442963.45 | 0.00 | 0.306712E+09 | 0.230423E+10 | 0.00 | 0.49 |
December | 0.392899E+10 | 0.00 | 0.00 | 945060.06 | 0.00 | 0.958168E+09 | 0.964416E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.202280E+11 | 0.680253E+09 | 0.00 | 87694014.37 | 0.00 | 0.345124E+10 | 0.510089E+11 | 0.00 | 0.91 |
Minimum of Months | 94445676.28 | 0.00 | 0.00 | 181616.19 | 0.00 | 0.00 | 0.279346E+09 | 0.00 | 0.40 |
Maximum of Months | 0.430466E+10 | 0.410073E+09 | 0.00 | 14509330.69 | 0.00 | 0.127470E+10 | 0.690017E+10 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.240559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377562E+10 | 0.00 | 0.00 | 0.43 |
February | 0.279574E+10 | 0.00 | 0.00 | 299080.57 | 0.00 | 0.217937E+10 | 0.241597E+09 | 0.00 | 0.43 |
March | 0.310029E+10 | 0.00 | 0.00 | 1093028.12 | 0.00 | 0.124839E+10 | 0.836154E+09 | 0.00 | 0.43 |
April | 0.224139E+10 | 7967676.91 | 0.00 | 2615047.35 | 0.00 | 0.590480E+09 | 0.131817E+10 | 0.00 | 0.43 |
May | 0.165715E+10 | 6179032.63 | 0.00 | 4333000.80 | 0.00 | 0.130510E+09 | 0.176301E+10 | 0.00 | 0.43 |
June | 0.959463E+09 | 4739527.54 | 0.00 | 6196142.13 | 0.00 | 5753942.48 | 0.175464E+10 | 0.00 | 0.43 |
July | 0.614664E+09 | 0.150339E+09 | 0.00 | 7071388.98 | 0.00 | 0.00 | 0.116689E+10 | 0.00 | 0.43 |
August | 0.498560E+09 | 0.352181E+09 | 0.00 | 7171425.52 | 0.00 | 0.00 | 0.975021E+09 | 0.00 | 0.44 |
September | 0.111365E+10 | 33530624.59 | 0.00 | 7676420.51 | 0.00 | 675280.31 | 0.160412E+10 | 0.00 | 0.43 |
October | 0.230622E+10 | 0.00 | 0.00 | 3921803.22 | 0.00 | 0.297565E+09 | 0.164725E+10 | 0.00 | 0.43 |
November | 0.310150E+10 | 0.00 | 0.00 | 500960.65 | 0.00 | 0.155350E+10 | 0.254077E+09 | 0.00 | 0.42 |
December | 0.253934E+10 | 0.00 | 0.00 | 134618.33 | 0.00 | 0.322430E+10 | 0.129832E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.233336E+11 | 0.554937E+09 | 0.00 | 41012916.18 | 0.00 | 0.130062E+11 | 0.116908E+11 | 0.00 | 0.43 |
Minimum of Months | 0.498560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.310150E+10 | 0.352181E+09 | 0.00 | 7676420.51 | 0.00 | 0.377562E+10 | 0.176301E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |