Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2020-06-03 19:12:37
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1897.41 | 827.12 | 827.12 |
Net Site Energy | 1897.41 | 827.12 | 827.12 |
Total Source Energy | 5835.13 | 2543.66 | 2543.66 |
Net Source Energy | 5835.13 | 2543.66 | 2543.66 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 931.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 390.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 236.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 83.52 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1813.89 | 83.52 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 931.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 390.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 194.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 236.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 83.52 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 196.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 509.11 | 36.41 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 790.71 | 36.41 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 196.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 509.11 | 36.41 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 790.71 | 36.41 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1813.890 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1813.890 | 100.00 |
Total On-Site and Utility Electric Sources | 1813.890 | 100.00 |
Total Electricity End Uses | 1813.890 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1153.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 55.45 |
Skylight-Roof Ratio [%] | 2.42 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.5670 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 18.0834 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 18.0834 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 18.0834 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 9.6875 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.2979 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.2979 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 06-MAY-15:30 | 09-JAN-12:30 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 72529.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 31216.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10752.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15384.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4789.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 129883.81 | 4789.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 72529.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 31216.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10752.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 15384.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4789.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2950.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1238.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 191.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 616.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 747.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 90.54 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5744.59 | 90.54 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1286.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 539.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 83.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 325.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 39.47 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2504.19 | 39.47 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1286.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 539.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 83.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 325.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 39.47 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2504.19 | 39.47 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 2.48 |
CORE_RETAIL DIRECT AIR | 8.35 |
POINT_OF_SALE DIRECT AIR | 1.30 |
FRONT_RETAIL DIRECT AIR | 1.12 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 0.101644 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 0.101644 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 2355.20 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 57564.65 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 192987.47 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 29857.90 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 25855.03 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 2.48 | 2.48 | 2.48 | 2.48 | 2.48 | 2.48 | 1.00 | 1.00 | 2.48 |
PSZ-AC:2 | 8.35 | 8.35 | 8.35 | 8.35 | 8.61 | 8.61 | 1.00 | 0.969294 | 8.61 |
PSZ-AC:3 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.00 | 1.30 |
PSZ-AC:4 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.00 | 1.00 | 1.12 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 2.48 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 8.61 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.30 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 1.12 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 2.48 | 2.48 | 2.48 | 1.64 | 50661.05 | 57564.65 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 8.61 | 8.61 | 8.61 | 5.68 | 210258.24 | 192987.47 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 1.30 | 27977.00 | 29857.90 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 1.12 | 25118.51 | 25855.03 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 2.48 | 1.24 | 1.65 | 47474.88 | 50661.05 | 25330.53 | 25330.53 | 0.729073 | 0.729070 | 0.729070 | 0.729070 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 8.61 | 4.31 | 5.74 | 199808.29 | 210258.24 | 105129.12 | 105129.12 | 0.680235 | 0.680230 | 0.680230 | 0.680230 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.30 | 0.648695 | 0.864927 | 26337.15 | 27977.00 | 13988.50 | 13988.50 | 0.713229 | 0.713230 | 0.713230 | 0.713230 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.12 | 0.561090 | 0.748120 | 23716.32 | 25118.51 | 12559.25 | 12559.25 | 0.702895 | 0.702890 | 0.702890 | 0.702890 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.48 | 2655.03 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 8.61 | 14506.28 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.30 | 1436.41 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.12 | 1242.43 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.567 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.637 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 18.083 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 21.313 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 18.083 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 39.603 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 18.083 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 21.313 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 9.688 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.688 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2874.639 | 7.567 | 46.863 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2874.639 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 28942.124 | 18.083 | 111.990 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28942.124 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2727.153 | 18.083 | 111.990 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2727.153 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2727.153 | 18.083 | 111.990 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2727.153 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 116.250 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 116.250 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.3762 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9750000 | 3.9750000 | 3.9750000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
21 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
22 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
23 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
24 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
25 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
26 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
27 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
28 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
29 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
30 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
31 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
32 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
33 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 30 | 1 | VerySmooth | 5.832 | 0.251 | 0.110 | 0.250 |
2 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 31 | 1 | VerySmooth | 5.779 | 0.360 | 0.195 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19502 | 0.25365 | 0.25365 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1915 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2262.32 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 28163.48752 | 33796.18503 | 2.06769 | 2.48122 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 34.86000 | 1.71339E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 6621.48068 | 7945.77682 | 0.27764 | 0.33317 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 98340.68339 | 118008.82006 | 6.95511 | 8.34614 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71339E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 23624.23003 | 28349.07604 | 0.98442 | 1.89021 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 14726.28745 | 17671.54493 | 1.08116 | 1.29739 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 35.03000 | 1.71339E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 3192.30678 | 3830.76814 | 0.13363 | 0.17811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 12737.51142 | 15285.01371 | 0.93515 | 1.12218 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 35.20000 | 1.71339E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 3192.30678 | 3830.76814 | 0.13363 | 0.17811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20000 | 1.71339E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 1962.73184 | 2355.27821 | 8.47033E-002 | 0.10164 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 20.10000 | 1.47983E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 36381.16 | 2.48122 | 2.48122 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 7921.38 | 0.33317 | 0.33317 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 140588.10 | 8.61053 | 8.61053 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 45493.45 | 1.89021 | 1.89021 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 19828.89 | 1.29739 | 1.29739 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 4286.75 | 0.17811 | 0.17811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 17485.44 | 1.12218 | 1.12218 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 4286.75 | 0.17811 | 0.17811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.48122 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 8.34614 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.29739 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12218 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.10164 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 0.10164 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 2355.20382 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.48122 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.48122 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.48122 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.48122 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.48122 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.48122 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.34614 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 8.34614 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.34614 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 8.34614 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.61053 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 8.61053 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.96929 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.29739 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.29739 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.29739 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.29739 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.29739 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.29739 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12218 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12218 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12218 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12218 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.12218 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.12218 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 2.48122 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 8.61053 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.29739 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.12218 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.48122 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.48122 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.48122 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.48122 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.63761 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.48122 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.24061 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.65415 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 47474.87762 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 50661.05000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 25330.52500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 25330.52500 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72907 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72907 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72907 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72907 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 50661.05000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 57564.64708 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.48122 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2655.02646 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 57564.64708 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.61053 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.61053 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.61053 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.61053 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.68295 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 8.61053 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.30527 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.74035 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 199808.28773 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 210258.24000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 105129.12000 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 105129.12000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68023 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68023 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68023 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68023 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 210258.24000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 192987.47173 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 8.61053 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 14506.28252 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 192987.47173 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.29739 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.29739 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.29739 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.29739 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.29739 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.29739 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64870 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86493 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26337.14765 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27977.00000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13988.50000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 13988.50000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71323 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71323 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71323 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71323 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27977.00000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29857.90124 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.29739 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1436.41414 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29857.90124 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.12218 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.12218 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.12218 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.12218 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.12218 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.12218 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56109 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74812 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 23716.31857 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 25118.51000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12559.25500 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12559.25500 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70289 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70289 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70289 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70289 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25118.51000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25855.03420 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.12218 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1242.42903 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25855.03420 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 48710.5 | 11.40 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 203467.5 | 13.42 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 26956.1 | 120.98 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 24234.9 | 147.16 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1545.03 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | N/A | 5.779 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 5.832 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | |
1 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R4C1 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
2 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R4C2 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
3 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R4C3 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
4 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R4C4 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
5 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C1 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
6 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C2 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
7 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C4 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
8 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R1C3 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
9 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C2 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
10 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C1 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
11 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C3 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
12 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R2C4 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
13 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R3C2 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
14 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R3C1 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
15 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R3C3 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A | |||
16 | SKYLIGHT_FRAME | Frame | SKYLIGHTS_R3C4 | Window5 Detailed Fenestration | N/A | N/A | 1.98 | 1.98 | * | N/A | N/A | 0.32 | N/A |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 6 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 0.1269090538 | 0.1953383565 | Pass | Pass | 0.6658378254 | 1.8265177688 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 0.1063118577 | 0.1606092244 | Pass | Pass | 2.0396579207 | 14.7556261991 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 0.1625568334 | 0.2530690515 | Pass | Pass | 0.3532687505 | 0.7016858810 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 0.1391426599 | 0.2177090705 | Pass | Pass | 0.3618841204 | 0.7267622854 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 7.4375299370E-002 | 9.4794913652E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.358 | 0.376 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.358 | 0.376 | 1600.48 | 1545.03 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.358 | 0.376 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.358 | 0.376 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.358 | 0.376 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.36 | 1.49 | 1.98 | 0.00 | 3.47 | 3.47 | 5.779 | 0.360 | 0.401 | 283.913 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_1.2_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 5.832 | 0.251 | 0.250 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_1.2_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 5.832 | 0.251 | 0.250 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_1.2_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 5.832 | 0.251 | 0.250 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 139.39 | 5.811 | 0.295 | 0.310 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 139.39 | 5.811 | 0.295 | 0.310 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.5670 | 379.89 | 2874.64 | LightsWired | BLDG_LIGHT_BACK_SCH | 63.14 | 168.00 | 62.27 | 0.0000 | Y | 33.60 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 18.0834 | 1600.48 | 28942.12 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 52.69 | 0.0000 | Y | 286.25 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 18.0834 | 150.81 | 2727.15 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.94 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 18.0834 | 150.81 | 2727.15 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.94 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 9.6875 | 12.00 | 116.25 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 57.54 | 168.00 | 56.76 | 0.0000 | Y | 1.24 |
Interior Lighting Total | 16.2979 | 2293.99 | 37387.32 | 390.97 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 28942.12 | 7235.53 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 28942.12 | 7235.53 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 316.30 | AstronomicalClock | - | 41.93 | 41.93 | 2.49 | |
EXTERIOR_LIGHTS_B | 4328.00 | AstronomicalClock | - | 83.83 | 71.26 | 57.89 | |
Exterior Lighting Total | 4644.30 | 60.38 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 50661.05 | 36935.45 | 13725.60 | 0.73 | 3.73 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 210258.24 | 143023.96 | 67234.28 | 0.68 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 27977.00 | 19954.04 | 8022.96 | 0.71 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 25118.51 | 17655.55 | 7462.96 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 48710.5 | 11.40 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 203467.5 | 13.42 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 26956.1 | 120.98 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 24234.9 | 147.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 2355.20 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 57564.65 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 192987.47 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29857.90 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25855.03 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.10 | 113.85 | 1120.11 | 1.00 | 3.24 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.48 | 2655.03 | 1070.05 | 1.00 | 1.29 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 8.61 | 14506.28 | 1684.71 | 1.00 | 1.15 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:50:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.30 | 1436.41 | 1107.16 | 1.00 | 1.34 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.12 | 1242.43 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 28163.49 | 33796.19 | 88.96 | 2.068 | 2.481 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 23.89 | 23.89 | 0.00905 | 34.86 | 0.01713 | 0.232 | 0.00 |
CORE_RETAIL | 98340.68 | 118008.82 | 73.73 | 6.955 | 8.346 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 23.89 | 23.89 | 0.00945 | 28.91 | 0.01713 | 1.890 | 0.00 |
POINT_OF_SALE | 14726.29 | 17671.54 | 117.18 | 1.081 | 1.297 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 23.89 | 23.89 | 0.00892 | 35.03 | 0.01713 | 0.178 | 0.00 |
FRONT_RETAIL | 12737.51 | 15285.01 | 101.35 | 0.935 | 1.122 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 23.89 | 23.89 | 0.00899 | 35.20 | 0.01713 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 34.75 | 100.00 | 0.00001 | 35.20 | 0.01713 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 6621.48 | 7945.78 | 20.92 | 0.278 | 0.333 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00995 | 20.10 | 0.01480 | 0.232 | 0.00 |
CORE_RETAIL | 23624.23 | 28349.08 | 17.71 | 0.984 | 1.890 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00852 | 20.10 | 0.01480 | 1.890 | 0.00 |
POINT_OF_SALE | 3192.31 | 3830.77 | 25.40 | 0.134 | 0.178 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00991 | 20.10 | 0.01480 | 0.178 | 0.00 |
FRONT_RETAIL | 3192.31 | 3830.77 | 25.40 | 0.134 | 0.178 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00991 | 20.10 | 0.01480 | 0.178 | 0.00 |
FRONT_ENTRY | 1962.73 | 2355.28 | 196.27 | 0.085 | 0.102 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.12 | 0.01441 | 20.10 | 0.01480 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 2.48 | 2.48 | 0.33 | 0.33 | 2.4812 | 2.4812 | 2.4812 | 1.0000 | 1.0000 |
PSZ-AC:2 | 8.61 | 8.61 | 1.89 | 1.89 | 8.6105 | 8.3461 | 8.6105 | 0.9693 | 1.0000 |
PSZ-AC:3 | 1.30 | 1.30 | 0.18 | 0.18 | 1.2974 | 1.2974 | 1.2974 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.12 | 1.12 | 0.18 | 0.18 | 1.1222 | 1.1222 | 1.1222 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 2355.204 | 2355.204 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 2355.20 | 2355.20 | 0.101644 | 20.98 | 20.12 | 0.01446131 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.12 | 0.01440671 | 91.4731 | 2355.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 25330.525 | 0.000 | 2.481220 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 25330.53 | 20368.56 | 2.481220 | 24.94 | 17.78 | 0.00980264 | 12.80 | 12.09 | 0.00850000 | 35.12 | 0.01713393 | 25.78 | 9.3328 | 23.89 | 0.00904636 | 48.9608 | 28132.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 57564.647 | 57564.647 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 57564.65 | 57564.65 | 2.481224 | 20.34 | 19.06 | 0.01331922 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 9.3328 | 21.11 | 0.00994811 | 63.6457 | 6621.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 105129.120 | 0.000 | 8.610530 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:50:00 | 105129.12 | 75000.79 | 8.610530 | 26.33 | 19.09 | 0.01086984 | 12.80 | 12.09 | 0.00850000 | 34.99 | 0.01713393 | 25.75 | 21.9523 | 23.89 | 0.00945375 | 51.1384 | 97519.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 192987.472 | 192987.472 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 192987.47 | 192987.47 | 8.610528 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 21.9523 | 21.11 | 0.00851953 | 54.6330 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 13988.500 | 0.000 | 1.297390 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 13988.50 | 10936.50 | 1.297390 | 25.44 | 18.15 | 0.01004809 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01713393 | 25.80 | 13.7284 | 23.89 | 0.00891988 | 48.2858 | 14721.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 29857.901 | 29857.901 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 29857.90 | 29857.90 | 1.297388 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 13.7284 | 21.11 | 0.00990922 | 63.3996 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 12559.255 | 0.000 | 1.122180 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 12559.25 | 9549.74 | 1.122180 | 25.68 | 18.41 | 0.01027843 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01713393 | 25.80 | 15.8718 | 23.89 | 0.00898506 | 48.6336 | 12737.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 25855.034 | 25855.034 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | 25855.03 | 25855.03 | 1.122178 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 15.8719 | 21.11 | 0.00990922 | 63.3996 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 2355.204 | 2355.204 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.101644 | 0.12233823 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 2355.20 | 2355.20 | 1.0000 | 0.12233823 | 0.101644 | 20.98 | 20.12 | 0.01446131 | 57810.6 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2355.20 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.12 | 0.01440671 | 21.12 | 0.01440671 | 91.4731 | 2355.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25330.525 | 0.000 | 2.481220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0626 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 25330.53 | 20368.56 | 1.0000 | 2.98638394 | 2.481220 | 24.94 | 17.78 | 0.00980264 | 50027.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25330.53 | 35.12 | 0.01713393 | 25.78 | 0.23156651 | 9.3328 | 23.89 | 0.00904708 | 23.89 | 0.00904636 | 48.9608 | 28132.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 57564.647 | 57564.647 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.481224 | 2.98638818 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 57564.65 | 57564.65 | 1.0000 | 2.98638818 | 2.481224 | 20.34 | 19.06 | 0.01331922 | 54254.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57564.65 | 20.10 | 0.01479830 | 20.10 | 0.23156651 | 9.3328 | 20.89 | 0.00994811 | 21.11 | 0.00994811 | 63.6457 | 6621.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 105129.120 | 0.000 | 8.610530 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0465 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 12:50:00 | 105129.12 | 75000.79 | 1.0000 | 10.36359070 | 8.610530 | 26.33 | 19.09 | 0.01086984 | 54174.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 105129.12 | 34.99 | 0.01713393 | 25.75 | 1.89021192 | 21.9523 | 23.89 | 0.00910294 | 23.89 | 0.00945375 | 51.1384 | 97519.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 192987.472 | 192987.472 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.610528 | 10.36358824 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 192987.47 | 192987.47 | 1.0000 | 10.36358824 | 8.610528 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 192987.47 | 20.10 | 0.01479830 | 20.10 | 1.89021192 | 21.9523 | 21.11 | 0.00000000 | 21.11 | 0.00851953 | 54.6330 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13988.500 | 0.000 | 1.297390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5189 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 13988.50 | 10936.50 | 1.0000 | 1.56153209 | 1.297390 | 25.44 | 18.15 | 0.01004809 | 51169.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13988.50 | 35.20 | 0.01713393 | 25.80 | 0.17811053 | 13.7284 | 23.89 | 0.00892005 | 23.89 | 0.00891988 | 48.2858 | 14721.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29857.901 | 29857.901 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.297388 | 1.56152934 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 29857.90 | 29857.90 | 1.0000 | 1.56152934 | 1.297388 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29857.90 | 20.10 | 0.01479830 | 20.10 | 0.17811053 | 13.7284 | 21.11 | 0.00000000 | 21.11 | 0.00990922 | 63.3996 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12559.255 | 0.000 | 1.122180 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9471 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 12559.25 | 9549.74 | 1.0000 | 1.35065022 | 1.122180 | 25.68 | 18.41 | 0.01027843 | 52004.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12559.25 | 35.20 | 0.01713393 | 25.80 | 0.17811053 | 15.8718 | 23.89 | 0.00898506 | 23.89 | 0.00898506 | 48.6336 | 12737.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25855.034 | 25855.034 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.122178 | 1.35064765 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | 25855.03 | 25855.03 | 1.0000 | 1.35064765 | 1.122178 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25855.03 | 20.10 | 0.01479830 | 20.10 | 0.17811053 | 15.8719 | 21.11 | 0.00000000 | 21.11 | 0.00990922 | 63.3996 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 4904.67 | 48.50 | 48.50 |
CORE_RETAIL | 4912.00 | 1153.50 | 1153.50 |
POINT_OF_SALE | 4913.00 | 202.67 | 202.67 |
FRONT_RETAIL | 4913.00 | 480.17 | 480.17 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 4913.00 | 1153.67 | 1153.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 0.00 | 563.33 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 69.50 | 0.00 | 0.00 |
POINT_OF_SALE | 0.00 | 774.17 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 696.50 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 779.83 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.50 | 61.34 | 2317.33 | 0.372 | 0.020 | 0.000 | 0.000 |
CORE_RETAIL | 128.48 | 258.43 | 9762.95 | 0.721 | 0.004 | 0.000 | 0.000 |
POINT_OF_SALE | 12.11 | 24.35 | 919.94 | 0.720 | 0.021 | 0.000 | 0.000 |
FRONT_RETAIL | 12.11 | 24.35 | 919.94 | 0.720 | 0.021 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.50 | 61.34 | 2317.33 | 0.364 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.48 | 258.43 | 9762.95 | 0.706 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.11 | 24.35 | 919.94 | 0.705 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.11 | 24.35 | 919.94 | 0.705 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1813.89 | 3408.81 | 12-FEB-08:00 | 129883.81 | 06-MAY-15:30 |
Electricity:Building | 585.61 | 3047.04 | 05-FEB-08:50 | 44140.05 | 02-JAN-16:10 |
Electricity:Zone:BACK_SPACE | 83.46 | 599.86 | 01-JAN-00:10 | 5099.20 | 02-JAN-09:10 |
InteriorLights:Electricity | 390.98 | 1266.41 | 05-FEB-08:50 | 33387.34 | 02-JAN-16:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 33.60 | 143.73 | 01-JAN-00:10 | 2344.76 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 390.98 | 1266.41 | 05-FEB-08:50 | 33387.34 | 02-JAN-16:10 |
Electricity:Zone:CORE_RETAIL | 370.32 | 1613.30 | 05-FEB-08:50 | 30692.60 | 02-JAN-16:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 286.25 | 844.15 | 05-FEB-08:50 | 26047.91 | 02-JAN-16:10 |
Electricity:Zone:POINT_OF_SALE | 87.72 | 619.23 | 01-JAN-00:10 | 5370.36 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 34.94 | 136.36 | 01-JAN-00:10 | 2454.44 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 42.86 | 208.83 | 01-JAN-00:10 | 2892.10 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 34.94 | 136.36 | 01-JAN-00:10 | 2454.44 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.24 | 5.81 | 01-JAN-00:10 | 85.79 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.24 | 5.81 | 01-JAN-00:10 | 85.79 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 194.63 | 1780.63 | 01-JAN-00:10 | 10752.72 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.86 | 456.13 | 01-JAN-00:10 | 2754.45 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 194.63 | 1780.63 | 01-JAN-00:10 | 10752.72 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.07 | 769.15 | 01-JAN-00:10 | 4644.69 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.78 | 482.87 | 01-JAN-00:10 | 2915.92 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.92 | 72.48 | 01-JAN-00:10 | 437.66 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1813.89 | 3408.81 | 12-FEB-08:00 | 129883.81 | 06-MAY-15:30 |
ElectricityPurchased:Plant | 1813.89 | 3408.81 | 12-FEB-08:00 | 129883.81 | 06-MAY-15:30 |
Cogeneration:ElectricityPurchased | 1813.89 | 3408.81 | 12-FEB-08:00 | 129883.81 | 06-MAY-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1813.89 | 3408.81 | 12-FEB-08:00 | 129883.81 | 06-MAY-15:30 |
ElectricityNet:Plant | 1813.89 | 3408.81 | 12-FEB-08:00 | 129883.81 | 06-MAY-15:30 |
Cogeneration:ElectricityNet | 1813.89 | 3408.81 | 12-FEB-08:00 | 129883.81 | 06-MAY-15:30 |
Electricity:HVAC | 1167.90 | 0.00 | 02-JAN-04:20 | 89810.57 | 13-JUN-15:00 |
Fans:Electricity | 236.11 | 0.00 | 02-JAN-04:20 | 15736.73 | 13-JUN-15:00 |
General:Fans:Electricity | 236.11 | 0.00 | 02-JAN-04:20 | 15736.73 | 13-JUN-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 931.79 | 0.00 | 02-JAN-04:20 | 74073.84 | 13-JUN-15:00 |
ExteriorLights:Electricity | 60.38 | 0.00 | 01-JAN-06:20 | 4644.30 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.38 | 0.00 | 01-JAN-06:20 | 4644.30 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 83.52 | 1860.00 | 17-JAN-08:10 | 4789.90 | 09-JAN-12:30 |
Gas:Plant | 83.52 | 1860.00 | 17-JAN-08:10 | 4789.90 | 09-JAN-12:30 |
WaterSystems:Gas | 83.52 | 1860.00 | 17-JAN-08:10 | 4789.90 | 09-JAN-12:30 |
Water Heater:WaterSystems:Gas | 83.52 | 1860.00 | 17-JAN-08:10 | 4789.90 | 09-JAN-12:30 |
Gas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Gas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 5208.52 | 0.00 | 02-JAN-04:20 | 378786.46 | 13-JUN-15:00 |
EnergyTransfer:Building | 1605.34 | 0.00 | 02-JAN-04:20 | 117654.56 | 06-MAY-15:30 |
EnergyTransfer:Zone:BACK_SPACE | 328.42 | 0.00 | 01-JAN-00:10 | 26784.90 | 13-JUN-16:00 |
Heating:EnergyTransfer | 0.25 | 0.00 | 01-JAN-00:10 | 6624.64 | 20-AUG-07:20 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 0.01 | 0.00 | 01-JAN-00:10 | 978.90 | 20-OCT-05:10 |
Cooling:EnergyTransfer | 1605.10 | 0.00 | 02-JAN-04:20 | 117654.56 | 06-MAY-15:30 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 328.41 | 0.00 | 01-JAN-00:10 | 26784.90 | 13-JUN-16:00 |
EnergyTransfer:Zone:CORE_RETAIL | 901.69 | 0.00 | 01-JAN-00:40 | 66730.61 | 06-MAY-15:40 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 0.23 | 0.00 | 01-JAN-00:10 | 6624.64 | 20-AUG-07:20 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 901.46 | 0.00 | 01-JAN-00:40 | 66730.61 | 06-MAY-15:40 |
EnergyTransfer:Zone:POINT_OF_SALE | 205.10 | 0.00 | 01-JAN-00:40 | 15710.46 | 07-DEC-15:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.00 | 0.00 | 01-JAN-00:10 | 724.05 | 19-NOV-08:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 205.09 | 0.00 | 01-JAN-00:40 | 15710.46 | 07-DEC-15:10 |
EnergyTransfer:Zone:FRONT_RETAIL | 170.14 | 0.00 | 01-JAN-00:40 | 13949.55 | 07-DEC-15:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.00 | 0.00 | 01-JAN-00:10 | 625.50 | 19-NOV-08:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 170.13 | 0.00 | 01-JAN-00:40 | 13949.55 | 07-DEC-15:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 3603.18 | 0.00 | 02-JAN-04:20 | 265502.80 | 13-JUN-15:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 3603.18 | 0.00 | 02-JAN-04:20 | 265502.80 | 13-JUN-15:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 0.007 | -328.407 | 0.000 | 0.000 | 36.671 | 33.603 | 49.857 | 0.000 | 0.000 | 2.644 | 205.724 | 0.000 | 0.000 | 0.000 | -0.100 | -0.000 |
CORE_RETAIL | 0.000 | 0.000 | 0.229 | -901.448 | 0.000 | 0.000 | 154.496 | 286.253 | 84.072 | 60.577 | 0.000 | 2.192 | 320.174 | 0.000 | -6.464 | 0.000 | -0.080 | -0.001 |
POINT_OF_SALE | 0.000 | 0.000 | 0.005 | -205.091 | 0.000 | 0.000 | 14.558 | 34.941 | 52.780 | 39.485 | 0.000 | 1.136 | 65.788 | 0.000 | -3.554 | 0.000 | -0.047 | -0.000 |
FRONT_RETAIL | 0.000 | 0.000 | 0.005 | -170.128 | 0.000 | 0.000 | 14.558 | 34.941 | 7.922 | 39.610 | 0.000 | 1.142 | 75.312 | 0.000 | -3.316 | 0.000 | -0.045 | -0.000 |
FRONT_ENTRY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.239 | 0.000 | 6.262 | 0.000 | 1.971 | 0.000 | 0.000 | -1.475 | 0.000 | -1.632 | -6.365 |
Total Facility | 0.000 | 0.000 | 0.246 | -1605.074 | 0.000 | 0.000 | 220.282 | 390.976 | 194.630 | 145.934 | 0.000 | 9.085 | 666.998 | 0.000 | -14.809 | 0.000 | -1.904 | -6.366 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 24-FEB-21:07 | 0.00 | 0.00 | 0.00 | -37825.68 | 0.00 | 0.00 | 0.00 | 574.93 | 608.18 | 0.00 | 0.00 | 62.57 | 36580.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 20-DEC-21:10 | 0.00 | 0.00 | 0.00 | -140787.82 | 0.00 | 0.00 | 0.00 | 5788.42 | 1025.54 | 0.00 | 0.00 | 0.00 | 135054.85 | 0.00 | -1008.27 | 0.00 | -72.72 | 0.00 |
POINT_OF_SALE | 20-DEC-21:06 | 0.00 | 0.00 | 0.00 | -21094.19 | 0.00 | 0.00 | 0.00 | 545.43 | 643.83 | 0.00 | 0.00 | 0.00 | 20672.50 | 0.00 | -724.63 | 0.00 | -42.94 | 0.00 |
FRONT_RETAIL | 20-DEC-21:06 | 0.00 | 0.00 | 0.00 | -18450.72 | 0.00 | 0.00 | 0.00 | 545.43 | 96.63 | 0.00 | 0.00 | 0.00 | 18546.98 | 0.00 | -696.95 | 0.00 | -41.38 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-FEB-21:07 | 0.00 | 0.00 | 0.00 | -196540.77 | 0.00 | 0.00 | 0.00 | 7477.46 | 2374.18 | 0.00 | 0.00 | 176.47 | 187524.52 | 0.00 | -1008.60 | 0.00 | -3.26 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 01-OCT-07:07 | 0.00 | 0.00 | 2029.30 | 0.00 | 0.00 | 0.00 | 0.00 | 143.73 | 456.13 | 0.00 | 0.00 | 12.85 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2642.02 |
CORE_RETAIL | 28-MAY-07:03 | 0.00 | 0.00 | 24914.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.92 | 769.15 | 2448.11 | 0.00 | 44.84 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29382.12 |
POINT_OF_SALE | 19-NOV-08:07 | 0.00 | 0.00 | 2172.24 | 0.00 | 0.00 | 0.00 | 0.00 | 136.36 | 482.87 | 1872.73 | 0.00 | 4.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4668.27 |
FRONT_RETAIL | 19-NOV-08:07 | 0.00 | 0.00 | 1876.58 | 0.00 | 0.00 | 0.00 | 0.00 | 136.36 | 72.48 | 1892.37 | 0.00 | 4.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3981.78 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-MAY-07:03 | -14328.87 | 14328.87 | 24914.10 | -14328.87 | 0.00 | 0.00 | 0.00 | 1628.18 | 1780.63 | 6015.43 | 0.00 | 937.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20946.48 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.4812 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.4812 | 0.0933 | 1.0000 | 0.2316 | 0.0933 | ||
PSZ-AC:2 | 8.3461 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.6105 | 0.2195 | 1.0000 | 1.8902 | 0.2195 | ||
PSZ-AC:3 | 1.2974 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.2974 | 0.1373 | 1.0000 | 0.1781 | 0.1373 | ||
PSZ-AC:4 | 1.1222 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1222 | 0.1587 | 1.0000 | 0.1781 | 0.1587 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.4812 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.4812 | 1.0000 | 1.0000 | 0.2316 | 0.0933 | ||
PSZ-AC:2 | 8.3461 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.3461 | 1.0000 | 1.0000 | 1.8902 | 0.2265 | ||
PSZ-AC:3 | 1.2974 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.2974 | 1.0000 | 1.0000 | 0.1781 | 0.1373 | ||
PSZ-AC:4 | 1.1222 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1222 | 1.0000 | 1.0000 | 0.1781 | 0.1587 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.4812 | 2.4812 | 2.4812 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.3461 | 8.3461 | 8.3461 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.2974 | 1.2974 | 1.2974 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.1222 | 1.1222 | 1.1222 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.4812 | 2.4812 | 2.4812 | 2.4812 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.3461 | 8.6105 | 8.3461 | 8.3461 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.2974 | 1.2974 | 1.2974 | 1.2974 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.1222 | 1.1222 | 1.1222 | 1.1222 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.4812 | 2.4812 | 2.4812 | 0.2316 | 0.6950 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.3461 | 8.3461 | 8.3461 | 1.8902 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.2974 | 1.2974 | 1.2974 | 0.1781 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.1222 | 1.1222 | 1.1222 | 0.1781 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.4812 | 2.4812 | 2.4812 | 2.4812 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.3461 | 8.3461 | 8.3461 | 8.3461 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.2974 | 1.2974 | 1.2974 | 1.2974 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.1222 | 1.1222 | 1.1222 | 1.1222 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:37
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 2293.99 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 931.79 | 74073.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 390.98 | 33387.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.38 | 4644.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 194.63 | 10752.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 236.11 | 15736.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 83.52 | 4789.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 194.63 | 1813.89 |
Natural Gas | 0.00 | 83.52 |
Additional | 0.00 | 0.00 |
Total | 194.63 | 1897.41 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 170.43 |
Space Heating | 0.00 |
Space Cooling | 406.19 |
Fans (All) | 102.92 |
Service Water Heating | 0.00 |
Receptacle Equipment | 84.84 |
Miscellaneous (All) | 790.71 |
Subtotal | 790.71 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 36.41 |
Miscellaneous (All) | 36.41 |
Subtotal | 36.41 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 20.61 |
Space Heating | 0.00 |
Space Cooling | 49.11 |
Fans (All) | 12.44 |
Service Water Heating | 4.40 |
Receptacle Equipment | 10.26 |
Miscellaneous | 3.18 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3292. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3001. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4559. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_SETBACK | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_SCH_PSZ_AC_2 | CORE_RETAIL DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2010
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230622E+11 | 36966.25 | 15-JAN-19:08 | 26.75 | 20.92 | 0.218396E+10 | 2451.32 | 04-JAN-15:30 | 32.35 | 24.42 |
February | 0.235719E+11 | 37828.11 | 24-FEB-21:07 | 27.38 | 21.31 | 0.199426E+10 | 2451.29 | 21-FEB-15:00 | 31.90 | 23.95 |
March | 0.286415E+11 | 36593.87 | 21-MAR-20:05 | 27.00 | 22.86 | 0.228100E+10 | 2451.29 | 16-MAR-14:09 | 31.83 | 24.83 |
April | 0.301303E+11 | 35923.18 | 26-APR-20:06 | 28.92 | 23.58 | 0.215632E+10 | 2451.28 | 20-APR-14:39 | 31.90 | 26.23 |
May | 0.331748E+11 | 36788.00 | 31-MAY-20:06 | 24.07 | 23.94 | 0.223240E+10 | 2451.32 | 06-MAY-14:39 | 37.00 | 27.33 |
June | 0.361328E+11 | 36827.08 | 27-JUN-01:23 | 24.25 | 24.19 | 0.220150E+10 | 2451.36 | 15-JUN-14:00 | 35.00 | 28.15 |
July | 0.308918E+11 | 37602.64 | 20-JUL-00:43 | 23.78 | 22.66 | 0.218722E+10 | 2451.22 | 18-JUL-14:30 | 28.85 | 25.08 |
August | 0.282757E+11 | 36183.17 | 24-AUG-00:03 | 24.00 | 23.26 | 0.228096E+10 | 2451.24 | 19-AUG-15:09 | 24.15 | 24.01 |
September | 0.263310E+11 | 34931.64 | 12-SEP-20:06 | 25.17 | 24.30 | 0.215634E+10 | 2451.24 | 16-SEP-12:30 | 26.70 | 25.17 |
October | 0.233439E+11 | 34178.40 | 09-OCT-18:08 | 24.35 | 23.32 | 0.218394E+10 | 2451.27 | 10-OCT-14:09 | 31.17 | 26.18 |
November | 0.227510E+11 | 34070.03 | 22-NOV-21:06 | 25.10 | 23.60 | 0.210124E+10 | 2451.30 | 21-NOV-15:00 | 30.30 | 25.43 |
December | 0.221044E+11 | 37504.34 | 20-DEC-21:08 | 22.83 | 18.42 | 0.218728E+10 | 2451.28 | 30-DEC-15:00 | 30.30 | 25.77 |
Annual Sum or Average | 0.328411E+12 | 0.261464E+11 | ||||||||
Minimum of Months | 0.221044E+11 | 34070.03 | 22.83 | 18.42 | 0.199426E+10 | 2451.22 | 24.15 | 23.95 | ||
Maximum of Months | 0.361328E+11 | 37828.11 | 28.92 | 24.30 | 0.228100E+10 | 2451.36 | 37.00 | 28.15 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.713119E+11 | 130722.34 | 15-JAN-19:10 | 26.75 | 20.92 | 0.920098E+10 | 10327.29 | 18-JAN-15:30 | 31.50 | 23.80 |
February | 0.692315E+11 | 133187.59 | 24-FEB-21:07 | 27.38 | 21.31 | 0.840169E+10 | 10327.23 | 23-FEB-15:39 | 33.20 | 22.59 |
March | 0.837785E+11 | 126866.56 | 02-MAR-21:08 | 26.83 | 21.45 | 0.960981E+10 | 10327.04 | 04-MAR-16:10 | 32.83 | 22.26 |
April | 0.828504E+11 | 119488.33 | 26-APR-20:08 | 28.92 | 23.58 | 0.908467E+10 | 10326.87 | 15-APR-11:20 | 32.67 | 26.00 |
May | 0.813486E+11 | 119294.33 | 10-MAY-20:08 | 22.17 | 22.17 | 0.940534E+10 | 10326.99 | 01-MAY-14:09 | 34.83 | 27.34 |
June | 0.822986E+11 | 112012.08 | 07-JUN-20:08 | 28.00 | 25.05 | 0.927520E+10 | 10327.16 | 30-JUN-14:50 | 28.67 | 27.14 |
July | 0.750658E+11 | 120695.96 | 19-JUL-20:10 | 23.13 | 22.36 | 0.921485E+10 | 10327.27 | 12-JUL-14:00 | 27.00 | 25.53 |
August | 0.755186E+11 | 119321.18 | 23-AUG-20:10 | 23.00 | 22.39 | 0.960984E+10 | 10327.29 | 21-AUG-14:09 | 28.83 | 26.58 |
September | 0.736748E+11 | 113768.22 | 12-SEP-20:08 | 25.17 | 24.30 | 0.908472E+10 | 10326.94 | 21-SEP-14:09 | 27.83 | 25.74 |
October | 0.686116E+11 | 111223.83 | 09-OCT-18:10 | 24.35 | 23.32 | 0.920093E+10 | 10327.07 | 13-OCT-14:39 | 28.33 | 25.56 |
November | 0.679874E+11 | 122271.18 | 24-NOV-21:10 | 23.38 | 21.12 | 0.885246E+10 | 10327.04 | 28-NOV-15:39 | 28.97 | 24.66 |
December | 0.697840E+11 | 140813.98 | 20-DEC-21:10 | 22.83 | 18.42 | 0.921495E+10 | 10327.15 | 07-DEC-15:50 | 31.17 | 22.81 |
Annual Sum or Average | 0.901462E+12 | 0.110155E+12 | ||||||||
Minimum of Months | 0.679874E+11 | 111223.83 | 22.17 | 18.42 | 0.840169E+10 | 10326.87 | 27.00 | 22.26 | ||
Maximum of Months | 0.837785E+11 | 140813.98 | 28.92 | 25.05 | 0.960984E+10 | 10327.29 | 34.83 | 27.34 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195196E+11 | 20339.71 | 16-JAN-19:05 | 26.33 | 21.45 | 0.866980E+09 | 973.08 | 28-JAN-16:30 | 30.05 | 23.13 |
February | 0.180224E+11 | 20646.23 | 24-FEB-21:05 | 27.38 | 21.31 | 0.791668E+09 | 973.07 | 15-FEB-15:09 | 29.18 | 24.64 |
March | 0.186110E+11 | 19403.94 | 02-MAR-21:06 | 26.83 | 21.45 | 0.905515E+09 | 973.10 | 03-MAR-15:09 | 32.97 | 23.33 |
April | 0.165603E+11 | 18343.39 | 26-APR-20:06 | 28.92 | 23.58 | 0.856038E+09 | 973.08 | 15-APR-11:20 | 32.67 | 26.00 |
May | 0.167884E+11 | 18389.71 | 10-MAY-20:06 | 22.17 | 22.17 | 0.886252E+09 | 973.09 | 01-MAY-14:09 | 34.83 | 27.34 |
June | 0.167076E+11 | 17613.55 | 07-JUN-20:06 | 28.00 | 25.05 | 0.873989E+09 | 973.12 | 30-JUN-14:09 | 27.33 | 25.85 |
July | 0.154269E+11 | 18230.43 | 13-JUL-20:06 | 28.92 | 23.25 | 0.868306E+09 | 973.07 | 01-JUL-11:20 | 31.57 | 25.04 |
August | 0.151536E+11 | 18061.21 | 23-AUG-20:08 | 23.00 | 22.39 | 0.905521E+09 | 973.17 | 04-AUG-14:39 | 24.67 | 24.67 |
September | 0.157051E+11 | 17894.73 | 12-SEP-20:06 | 25.17 | 24.30 | 0.856043E+09 | 973.14 | 16-SEP-14:39 | 26.50 | 25.13 |
October | 0.159991E+11 | 17921.86 | 04-OCT-20:05 | 27.92 | 25.10 | 0.866989E+09 | 973.16 | 11-OCT-14:09 | 24.08 | 24.08 |
November | 0.174682E+11 | 19222.65 | 24-NOV-21:08 | 23.38 | 21.12 | 0.834147E+09 | 973.07 | 08-NOV-15:09 | 28.17 | 25.21 |
December | 0.191313E+11 | 21096.93 | 20-DEC-21:06 | 22.83 | 18.42 | 0.868297E+09 | 973.07 | 09-DEC-15:09 | 26.82 | 24.70 |
Annual Sum or Average | 0.205093E+12 | 0.103797E+11 | ||||||||
Minimum of Months | 0.151536E+11 | 17613.55 | 22.17 | 18.42 | 0.791668E+09 | 973.07 | 24.08 | 23.13 | ||
Maximum of Months | 0.195196E+11 | 21096.93 | 28.92 | 25.10 | 0.905521E+09 | 973.17 | 34.83 | 27.34 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165195E+11 | 17802.18 | 16-JAN-19:05 | 26.33 | 21.45 | 0.866980E+09 | 973.09 | 28-JAN-16:30 | 30.05 | 23.13 |
February | 0.153249E+11 | 17956.43 | 24-FEB-21:05 | 27.38 | 21.31 | 0.791668E+09 | 973.07 | 15-FEB-15:09 | 29.18 | 24.64 |
March | 0.154899E+11 | 16778.25 | 02-MAR-21:06 | 26.83 | 21.45 | 0.905516E+09 | 973.11 | 03-MAR-15:09 | 32.97 | 23.33 |
April | 0.136619E+11 | 15727.02 | 26-APR-20:06 | 28.92 | 23.58 | 0.856039E+09 | 973.08 | 22-APR-15:30 | 30.65 | 25.91 |
May | 0.138677E+11 | 15691.25 | 10-MAY-20:06 | 22.17 | 22.17 | 0.886254E+09 | 973.11 | 17-MAY-14:09 | 29.00 | 26.74 |
June | 0.138884E+11 | 15068.25 | 02-JUN-23:23 | 24.50 | 24.50 | 0.873991E+09 | 973.14 | 30-JUN-14:09 | 27.33 | 25.85 |
July | 0.125300E+11 | 15759.35 | 09-JUL-18:06 | 29.42 | 23.46 | 0.868308E+09 | 973.11 | 11-JUL-14:09 | 25.08 | 23.60 |
August | 0.122077E+11 | 15457.36 | 23-AUG-20:08 | 23.00 | 22.39 | 0.905525E+09 | 973.12 | 19-AUG-14:00 | 24.00 | 24.00 |
September | 0.128866E+11 | 15281.49 | 03-SEP-18:08 | 24.97 | 23.62 | 0.856042E+09 | 973.12 | 16-SEP-12:39 | 25.93 | 24.85 |
October | 0.130123E+11 | 15585.45 | 09-OCT-18:08 | 24.35 | 23.32 | 0.866991E+09 | 973.16 | 30-OCT-14:00 | 23.50 | 23.13 |
November | 0.146012E+11 | 16655.91 | 24-NOV-21:08 | 23.38 | 21.12 | 0.834148E+09 | 973.10 | 08-NOV-15:00 | 26.50 | 25.04 |
December | 0.161404E+11 | 18453.39 | 20-DEC-21:06 | 22.83 | 18.42 | 0.868298E+09 | 973.08 | 09-DEC-15:09 | 26.82 | 24.70 |
Annual Sum or Average | 0.170131E+12 | 0.103798E+11 | ||||||||
Minimum of Months | 0.122077E+11 | 15068.25 | 22.17 | 18.42 | 0.791668E+09 | 973.07 | 23.50 | 23.13 | ||
Maximum of Months | 0.165195E+11 | 18453.39 | 29.42 | 24.50 | 0.905525E+09 | 973.16 | 32.97 | 26.74 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 | 23.60 | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 | 23.60 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 | 22.46 | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 | 22.46 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 | 25.10 | 0.00 | 0.00 | 01-APR-00:10 | 27.53 | 25.10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 | 26.40 | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 | 26.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 | 23.91 | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 | 23.91 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.40 | 24.33 | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 | 24.33 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.63 | 24.75 | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 | 24.75 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 | 25.66 | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 | 25.66 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 | 25.35 | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 | 25.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 | 24.37 | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 | 24.37 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 23.80 | 22.46 | 0.00 | 0.00 | 23.80 | 22.46 | ||
Maximum of Months | 0.00 | 0.00 | 28.62 | 26.40 | 0.00 | 0.00 | 28.62 | 26.40 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 164926.98 | 1059.75 | 08-JAN-08:05 | 23.68 |
February | 902036.18 | 1886.70 | 26-FEB-08:07 | 25.33 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 539518.53 | 1798.40 | 18-MAY-05:05 | 24.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 379644.00 | 1898.22 | 16-JUL-07:07 | 24.92 |
August | 522342.55 | 1741.14 | 06-AUG-07:10 | 25.83 |
September | 311780.29 | 1039.27 | 16-SEP-05:05 | 24.00 |
October | 2010192.41 | 2029.09 | 01-OCT-07:07 | 25.50 |
November | 1355141.71 | 1911.59 | 19-NOV-08:07 | 25.50 |
December | 1300627.64 | 1793.38 | 31-DEC-08:05 | 24.67 |
Annual Sum or Average | 7486210.29 | |||
Minimum of Months | 0.00 | 0.00 | 23.68 | |
Maximum of Months | 2010192.41 | 2029.09 | 27.53 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28586372.04 | 9620.35 | 11-JAN-06:05 | 24.70 |
February | 34369969.73 | 13167.10 | 20-FEB-08:65 | 26.33 |
March | 11898325.19 | 12028.07 | 12-MAR-07:05 | 25.83 |
April | 4520464.62 | 9077.05 | 10-APR-05:10 | 25.08 |
May | 5817327.06 | 24909.35 | 28-MAY-07:03 | 32.25 |
June | 3683072.45 | 12276.91 | 29-JUN-05:05 | 26.00 |
July | 14552492.42 | 12131.22 | 04-JUL-07:05 | 25.83 |
August | 16988518.75 | 11788.59 | 18-AUG-05:05 | 25.83 |
September | 27327744.87 | 12288.01 | 25-SEP-05:05 | 26.00 |
October | 40229006.83 | 12439.34 | 16-OCT-05:05 | 26.00 |
November | 29016619.49 | 12334.04 | 14-NOV-06:05 | 26.03 |
December | 12399978.83 | 5749.94 | 04-DEC-06:05 | 23.00 |
Annual Sum or Average | 0.229390E+09 | |||
Minimum of Months | 3683072.45 | 5749.94 | 23.00 | |
Maximum of Months | 40229006.83 | 24909.35 | 32.25 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 605774.12 | 1656.21 | 29-JAN-08:04 | 24.17 |
February | 991338.04 | 2151.63 | 05-FEB-08:07 | 25.33 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 386483.23 | 1932.42 | 16-JUL-07:07 | 24.92 |
August | 185236.56 | 553.72 | 06-AUG-07:10 | 25.83 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 1117899.56 | 2112.03 | 01-OCT-07:07 | 25.50 |
November | 683984.46 | 2172.15 | 19-NOV-08:07 | 25.50 |
December | 542378.37 | 1759.74 | 03-DEC-08:04 | 24.50 |
Annual Sum or Average | 4513094.34 | |||
Minimum of Months | 0.00 | 0.00 | 24.05 | |
Maximum of Months | 1117899.56 | 2172.15 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 534687.10 | 1426.85 | 29-JAN-08:04 | 24.17 |
February | 851944.14 | 1847.16 | 05-FEB-08:07 | 25.33 |
March | 205601.11 | 342.67 | 04-MAR-06:10 | 24.10 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 334102.10 | 1670.51 | 16-JUL-07:07 | 24.92 |
August | 156375.17 | 521.25 | 06-AUG-07:10 | 25.83 |
September | 307441.57 | 961.32 | 16-SEP-05:10 | 24.00 |
October | 1013924.56 | 1831.98 | 01-OCT-07:07 | 25.50 |
November | 818329.46 | 1876.50 | 19-NOV-08:07 | 25.50 |
December | 462661.64 | 1530.61 | 03-DEC-08:04 | 24.50 |
Annual Sum or Average | 4685066.86 | |||
Minimum of Months | 0.00 | 0.00 | 24.00 | |
Maximum of Months | 1013924.56 | 1876.50 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.281822E+10 | 2344.76 | 02-JAN-09:09 | 0.420015E+10 | 2754.45 | 02-JAN-09:09 |
February | 0.256399E+10 | 2344.76 | 01-FEB-09:09 | 0.381055E+10 | 2754.45 | 01-FEB-09:09 |
March | 0.292411E+10 | 2344.76 | 01-MAR-09:09 | 0.430594E+10 | 2754.45 | 01-MAR-09:09 |
April | 0.275920E+10 | 2344.76 | 01-APR-09:09 | 0.409182E+10 | 2754.45 | 01-APR-09:09 |
May | 0.287117E+10 | 2344.76 | 01-MAY-08:09 | 0.425304E+10 | 2754.45 | 01-MAY-08:09 |
June | 0.282172E+10 | 2344.76 | 01-JUN-08:09 | 0.415844E+10 | 2754.45 | 01-JUN-08:09 |
July | 0.280865E+10 | 2344.76 | 01-JUL-09:09 | 0.418643E+10 | 2754.45 | 01-JUL-09:09 |
August | 0.292411E+10 | 2344.76 | 01-AUG-08:09 | 0.430594E+10 | 2754.45 | 01-AUG-08:09 |
September | 0.275920E+10 | 2344.76 | 01-SEP-08:09 | 0.409182E+10 | 2754.45 | 01-SEP-08:09 |
October | 0.281822E+10 | 2344.76 | 02-OCT-08:09 | 0.420015E+10 | 2754.45 | 02-OCT-08:09 |
November | 0.272540E+10 | 2344.76 | 01-NOV-08:09 | 0.406638E+10 | 2754.45 | 01-NOV-08:09 |
December | 0.280865E+10 | 2344.76 | 01-DEC-09:09 | 0.418643E+10 | 2754.45 | 01-DEC-09:09 |
Annual Sum or Average | 0.336027E+11 | 0.498571E+11 | ||||
Minimum of Months | 0.256399E+10 | 2344.76 | 0.381055E+10 | 2754.45 | ||
Maximum of Months | 0.292411E+10 | 2344.76 | 0.430594E+10 | 2754.45 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.245861E+11 | 26047.91 | 02-JAN-16:10 | 0.708251E+10 | 4644.69 | 02-JAN-09:09 |
February | 0.213887E+11 | 26047.91 | 01-FEB-16:40 | 0.642555E+10 | 4644.69 | 01-FEB-09:09 |
March | 0.253330E+11 | 26047.91 | 01-MAR-16:30 | 0.726089E+10 | 4644.69 | 01-MAR-09:09 |
April | 0.238158E+11 | 26047.91 | 01-APR-16:49 | 0.689984E+10 | 4644.69 | 01-APR-09:09 |
May | 0.245372E+11 | 26047.91 | 01-MAY-16:49 | 0.717170E+10 | 4644.69 | 01-MAY-08:09 |
June | 0.232944E+11 | 26047.91 | 01-JUN-16:00 | 0.701217E+10 | 4644.69 | 01-JUN-08:09 |
July | 0.236688E+11 | 26047.91 | 01-JUL-16:49 | 0.705936E+10 | 4644.69 | 01-JUL-09:09 |
August | 0.247134E+11 | 26047.91 | 01-AUG-16:00 | 0.726089E+10 | 4644.69 | 01-AUG-08:09 |
September | 0.231364E+11 | 26047.91 | 01-SEP-16:40 | 0.689984E+10 | 4644.69 | 01-SEP-08:09 |
October | 0.231878E+11 | 26047.91 | 02-OCT-16:30 | 0.708251E+10 | 4644.69 | 02-OCT-08:09 |
November | 0.234758E+11 | 26047.91 | 01-NOV-15:00 | 0.685694E+10 | 4644.69 | 01-NOV-08:09 |
December | 0.251151E+11 | 26047.91 | 01-DEC-16:10 | 0.705936E+10 | 4644.69 | 01-DEC-09:09 |
Annual Sum or Average | 0.286253E+12 | 0.840716E+11 | ||||
Minimum of Months | 0.213887E+11 | 26047.91 | 0.642555E+10 | 4644.69 | ||
Maximum of Months | 0.253330E+11 | 26047.91 | 0.726089E+10 | 4644.69 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.293011E+10 | 2454.44 | 02-JAN-09:09 | 0.444637E+10 | 2915.92 | 02-JAN-09:09 |
February | 0.266601E+10 | 2454.44 | 01-FEB-09:09 | 0.403394E+10 | 2915.92 | 01-FEB-09:09 |
March | 0.304105E+10 | 2454.44 | 01-MAR-09:09 | 0.455836E+10 | 2915.92 | 01-MAR-09:09 |
April | 0.286924E+10 | 2454.44 | 01-APR-09:09 | 0.433169E+10 | 2915.92 | 01-APR-09:09 |
May | 0.298558E+10 | 2454.44 | 01-MAY-08:09 | 0.450237E+10 | 2915.92 | 01-MAY-08:09 |
June | 0.293453E+10 | 2454.44 | 01-JUN-08:09 | 0.440222E+10 | 2915.92 | 01-JUN-08:09 |
July | 0.292029E+10 | 2454.44 | 01-JUL-09:09 | 0.443184E+10 | 2915.92 | 01-JUL-09:09 |
August | 0.304105E+10 | 2454.44 | 01-AUG-08:09 | 0.455836E+10 | 2915.92 | 01-AUG-08:09 |
September | 0.286924E+10 | 2454.44 | 01-SEP-08:09 | 0.433169E+10 | 2915.92 | 01-SEP-08:09 |
October | 0.293011E+10 | 2454.44 | 02-OCT-08:09 | 0.444637E+10 | 2915.92 | 02-OCT-08:09 |
November | 0.283340E+10 | 2454.44 | 01-NOV-08:09 | 0.430476E+10 | 2915.92 | 01-NOV-08:09 |
December | 0.292029E+10 | 2454.44 | 01-DEC-09:09 | 0.443184E+10 | 2915.92 | 01-DEC-09:09 |
Annual Sum or Average | 0.349409E+11 | 0.527798E+11 | ||||
Minimum of Months | 0.266601E+10 | 2454.44 | 0.403394E+10 | 2915.92 | ||
Maximum of Months | 0.304105E+10 | 2454.44 | 0.455836E+10 | 2915.92 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.293011E+10 | 2454.44 | 02-JAN-09:09 | 0.667369E+09 | 437.66 | 02-JAN-09:09 |
February | 0.266601E+10 | 2454.44 | 01-FEB-09:09 | 0.605465E+09 | 437.66 | 01-FEB-09:09 |
March | 0.304105E+10 | 2454.44 | 01-MAR-09:09 | 0.684178E+09 | 437.66 | 01-MAR-09:09 |
April | 0.286924E+10 | 2454.44 | 01-APR-09:09 | 0.650156E+09 | 437.66 | 01-APR-09:09 |
May | 0.298558E+10 | 2454.44 | 01-MAY-08:09 | 0.675774E+09 | 437.66 | 01-MAY-08:09 |
June | 0.293453E+10 | 2454.44 | 01-JUN-08:09 | 0.660742E+09 | 437.66 | 01-JUN-08:09 |
July | 0.292029E+10 | 2454.44 | 01-JUL-09:09 | 0.665188E+09 | 437.66 | 01-JUL-09:09 |
August | 0.304105E+10 | 2454.44 | 01-AUG-08:09 | 0.684178E+09 | 437.66 | 01-AUG-08:09 |
September | 0.286924E+10 | 2454.44 | 01-SEP-08:09 | 0.650156E+09 | 437.66 | 01-SEP-08:09 |
October | 0.293011E+10 | 2454.44 | 02-OCT-08:09 | 0.667369E+09 | 437.66 | 02-OCT-08:09 |
November | 0.283340E+10 | 2454.44 | 01-NOV-08:09 | 0.646114E+09 | 437.66 | 01-NOV-08:09 |
December | 0.292029E+10 | 2454.44 | 01-DEC-09:09 | 0.665188E+09 | 437.66 | 01-DEC-09:09 |
Annual Sum or Average | 0.349409E+11 | 0.792188E+10 | ||||
Minimum of Months | 0.266601E+10 | 2454.44 | 0.605465E+09 | 437.66 | ||
Maximum of Months | 0.304105E+10 | 2454.44 | 0.684178E+09 | 437.66 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.103900E+09 | 85.79 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 94517577.03 | 85.79 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.107770E+09 | 85.79 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.101704E+09 | 85.79 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.105835E+09 | 85.79 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.103997E+09 | 85.79 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.103541E+09 | 85.79 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.107770E+09 | 85.79 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.101704E+09 | 85.79 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.103900E+09 | 85.79 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.100485E+09 | 85.79 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.103541E+09 | 85.79 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.123866E+10 | ||||
Minimum of Months | 94517577.03 | 85.79 | 0.00 | 0.00 | |
Maximum of Months | 0.107770E+09 | 85.79 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.281822E+10 | 0.420015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129191E+09 | 30987076.91 |
February | 0.479114E+10 | 0.256399E+10 | 0.381055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174994E+09 | 1629213.21 |
March | 0.548013E+10 | 0.292411E+10 | 0.430594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341036E+09 | 3240070.73 |
April | 0.518069E+10 | 0.275920E+10 | 0.409182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344337E+09 | 125085.45 |
May | 0.536353E+10 | 0.287117E+10 | 0.425304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371320E+09 | 1205676.58 |
June | 0.528933E+10 | 0.282172E+10 | 0.415844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338847E+09 | 2674479.77 |
July | 0.525489E+10 | 0.280865E+10 | 0.418643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185400E+09 | 1417462.57 |
August | 0.548013E+10 | 0.292411E+10 | 0.430594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248683E+09 | 2665822.49 |
September | 0.518069E+10 | 0.275920E+10 | 0.409182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175251E+09 | 1425567.97 |
October | 0.524694E+10 | 0.281822E+10 | 0.420015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137412E+09 | 2170110.65 |
November | 0.504819E+10 | 0.272540E+10 | 0.406638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108172E+09 | 8868408.04 |
December | 0.525489E+10 | 0.280865E+10 | 0.418643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89153099.08 | 43413044.60 |
Annual Sum or Average | 0.628175E+11 | 0.336027E+11 | 0.498571E+11 | 0.264380E+10 | 99822018.98 | ||||
Minimum of Months | 0.479114E+10 | 0.256399E+10 | 0.381055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89153099.08 | 125085.45 |
Maximum of Months | 0.548013E+10 | 0.292411E+10 | 0.430594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371320E+09 | 43413044.60 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.245861E+11 | 0.708251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106561E+09 | 25303623.37 |
February | 0.201852E+11 | 0.213887E+11 | 0.642555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144602E+09 | 1241039.03 |
March | 0.230879E+11 | 0.253330E+11 | 0.726089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282532E+09 | 2430834.66 |
April | 0.218263E+11 | 0.238158E+11 | 0.689984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285347E+09 | 58744.81 |
May | 0.225967E+11 | 0.245372E+11 | 0.717170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308500E+09 | 670991.32 |
June | 0.222841E+11 | 0.232944E+11 | 0.701217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283278E+09 | 1715760.14 |
July | 0.221389E+11 | 0.236688E+11 | 0.705936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154107E+09 | 788293.36 |
August | 0.230879E+11 | 0.247134E+11 | 0.726089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206315E+09 | 2035763.52 |
September | 0.218263E+11 | 0.231364E+11 | 0.689984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145000E+09 | 1111963.44 |
October | 0.221054E+11 | 0.231878E+11 | 0.708251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113452E+09 | 1672576.19 |
November | 0.212681E+11 | 0.234758E+11 | 0.685694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89162519.60 | 7193588.95 |
December | 0.221389E+11 | 0.251151E+11 | 0.705936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73349910.52 | 35375256.79 |
Annual Sum or Average | 0.264651E+12 | 0.286253E+12 | 0.840716E+11 | 0.219221E+10 | 79598435.58 | ||||
Minimum of Months | 0.201852E+11 | 0.213887E+11 | 0.642555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73349910.52 | 58744.81 |
Maximum of Months | 0.230879E+11 | 0.253330E+11 | 0.726089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308500E+09 | 35375256.79 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.293011E+10 | 0.444637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54906801.22 | 14507636.11 |
February | 0.190200E+10 | 0.266601E+10 | 0.403394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74478628.45 | 1043590.98 |
March | 0.217552E+10 | 0.304105E+10 | 0.455836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145374E+09 | 1719535.25 |
April | 0.205665E+10 | 0.286924E+10 | 0.433169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148057E+09 | 67348.94 |
May | 0.212923E+10 | 0.298558E+10 | 0.450237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160424E+09 | 564398.09 |
June | 0.209978E+10 | 0.293453E+10 | 0.440222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147023E+09 | 1136140.83 |
July | 0.208610E+10 | 0.292029E+10 | 0.443184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80272920.50 | 635957.33 |
August | 0.217552E+10 | 0.304105E+10 | 0.455836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107205E+09 | 1195743.28 |
September | 0.205665E+10 | 0.286924E+10 | 0.433169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75207031.11 | 707524.69 |
October | 0.208295E+10 | 0.293011E+10 | 0.444637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58708867.42 | 1157628.50 |
November | 0.200405E+10 | 0.283340E+10 | 0.430476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46111244.42 | 4320192.15 |
December | 0.208610E+10 | 0.292029E+10 | 0.443184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38131822.55 | 19974710.20 |
Annual Sum or Average | 0.249375E+11 | 0.349409E+11 | 0.527798E+11 | 0.113590E+10 | 47030406.36 | ||||
Minimum of Months | 0.190200E+10 | 0.266601E+10 | 0.403394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38131822.55 | 67348.94 |
Maximum of Months | 0.217552E+10 | 0.304105E+10 | 0.455836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160424E+09 | 19974710.20 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.293011E+10 | 0.667369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55185654.86 | 14121216.15 |
February | 0.190200E+10 | 0.266601E+10 | 0.605465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74853814.99 | 897373.51 |
March | 0.217552E+10 | 0.304105E+10 | 0.684178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146459E+09 | 1547825.31 |
April | 0.205665E+10 | 0.286924E+10 | 0.650156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148962E+09 | 51736.40 |
May | 0.212923E+10 | 0.298558E+10 | 0.675774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161201E+09 | 486029.50 |
June | 0.209978E+10 | 0.293453E+10 | 0.660742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147778E+09 | 1057235.55 |
July | 0.208610E+10 | 0.292029E+10 | 0.665188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80622155.75 | 553129.06 |
August | 0.217552E+10 | 0.304105E+10 | 0.684178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107840E+09 | 1141268.82 |
September | 0.205665E+10 | 0.286924E+10 | 0.650156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75611247.92 | 648233.69 |
October | 0.208295E+10 | 0.293011E+10 | 0.667369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59026471.65 | 1057637.68 |
November | 0.200405E+10 | 0.283340E+10 | 0.646114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46351953.59 | 4126410.05 |
December | 0.208610E+10 | 0.292029E+10 | 0.665188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38234328.04 | 19574293.42 |
Annual Sum or Average | 0.249375E+11 | 0.349409E+11 | 0.792188E+10 | 0.114212E+10 | 45262389.15 | ||||
Minimum of Months | 0.190200E+10 | 0.266601E+10 | 0.605465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38234328.04 | 51736.40 |
Maximum of Months | 0.217552E+10 | 0.304105E+10 | 0.684178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161201E+09 | 19574293.42 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.103900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10092545.24 | 0.302247E+09 |
February | 0.00 | 94517577.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44291537.87 | 0.149751E+09 |
March | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231048E+09 | 71313478.22 |
April | 0.00 | 0.101704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343537E+09 | 19177788.83 |
May | 0.00 | 0.105835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390335E+09 | 49329712.36 |
June | 0.00 | 0.103997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353742E+09 | 42730143.76 |
July | 0.00 | 0.103541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160599E+09 | 92100387.09 |
August | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223799E+09 | 80821573.65 |
September | 0.00 | 0.101704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149461E+09 | 92490893.55 |
October | 0.00 | 0.103900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51130139.35 | 0.138480E+09 |
November | 0.00 | 0.100485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10132254.26 | 0.253050E+09 |
December | 0.00 | 0.103541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2703896.26 | 0.340305E+09 |
Annual Sum or Average | 0.00 | 0.123866E+10 | 0.197087E+10 | 0.163180E+10 | |||||
Minimum of Months | 0.00 | 94517577.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2703896.26 | 19177788.83 |
Maximum of Months | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390335E+09 | 0.340305E+09 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2344.76 | 02-JAN-09:09 | 2754.45 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 365.89 | 08-JAN-19:08 | 849.36 | 07-JAN-05:00 |
February | 5888.82 | 01-FEB-15:09 | 2344.76 | 01-FEB-09:09 | 2754.45 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 465.66 | 20-FEB-19:45 | 57.18 | 26-FEB-06:40 |
March | 5888.82 | 01-MAR-15:09 | 2344.76 | 01-MAR-09:09 | 2754.45 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.09 | 19-MAR-18:10 | 155.11 | 14-MAR-22:00 |
April | 5888.82 | 01-APR-10:09 | 2344.76 | 01-APR-09:09 | 2754.45 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 629.18 | 02-APR-19:00 | 38.48 | 22-APR-02:40 |
May | 5888.82 | 01-MAY-14:09 | 2344.76 | 01-MAY-08:09 | 2754.45 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 807.21 | 07-MAY-18:10 | 304.75 | 08-MAY-22:00 |
June | 5888.82 | 01-JUN-14:09 | 2344.76 | 01-JUN-08:09 | 2754.45 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 755.32 | 11-JUN-19:00 | 264.96 | 20-JUN-23:20 |
July | 5888.82 | 01-JUL-10:09 | 2344.76 | 01-JUL-09:09 | 2754.45 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 415.25 | 25-JUL-20:50 | 175.60 | 19-JUL-20:40 |
August | 5888.82 | 01-AUG-14:09 | 2344.76 | 01-AUG-08:09 | 2754.45 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 606.27 | 01-AUG-21:00 | 211.31 | 23-AUG-20:05 |
September | 5888.82 | 01-SEP-14:09 | 2344.76 | 01-SEP-08:09 | 2754.45 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 358.06 | 10-SEP-14:55 | 150.57 | 15-SEP-22:00 |
October | 5888.82 | 02-OCT-14:09 | 2344.76 | 02-OCT-08:09 | 2754.45 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 515.99 | 08-OCT-18:10 | 101.97 | 23-OCT-04:50 |
November | 5888.82 | 01-NOV-14:09 | 2344.76 | 01-NOV-08:09 | 2754.45 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 216.51 | 02-NOV-21:52 | 183.83 | 25-NOV-05:05 |
December | 5888.82 | 01-DEC-15:09 | 2344.76 | 01-DEC-09:09 | 2754.45 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 245.37 | 10-DEC-19:10 | 398.17 | 21-DEC-05:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2344.76 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 216.51 | 38.48 | |||||
Maximum of Months | 5888.82 | 2344.76 | 2754.45 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.09 | 849.36 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 26047.91 | 02-JAN-16:10 | 4644.69 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 301.56 | 08-JAN-19:10 | 577.39 | 07-JAN-05:10 |
February | 24809.68 | 01-FEB-15:09 | 26047.91 | 01-FEB-16:40 | 4644.69 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 380.62 | 20-FEB-19:10 | 50.40 | 26-FEB-06:55 |
March | 24809.68 | 01-MAR-15:09 | 26047.91 | 01-MAR-16:30 | 4644.69 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 833.35 | 19-MAR-18:10 | 125.67 | 03-MAR-05:55 |
April | 24809.68 | 01-APR-10:09 | 26047.91 | 01-APR-16:49 | 4644.69 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 515.03 | 02-APR-19:00 | 17.83 | 22-APR-02:40 |
May | 24809.68 | 01-MAY-14:09 | 26047.91 | 01-MAY-16:49 | 4644.69 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 659.68 | 07-MAY-18:10 | 175.22 | 08-MAY-22:00 |
June | 24809.68 | 01-JUN-14:09 | 26047.91 | 01-JUN-16:00 | 4644.69 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 618.26 | 11-JUN-19:00 | 127.05 | 20-JUN-23:20 |
July | 24809.68 | 01-JUL-10:09 | 26047.91 | 01-JUL-16:49 | 4644.69 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 339.91 | 25-JUL-20:30 | 102.79 | 19-JUL-20:08 |
August | 24809.68 | 01-AUG-14:09 | 26047.91 | 01-AUG-16:00 | 4644.69 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.65 | 01-AUG-21:00 | 169.17 | 23-AUG-20:08 |
September | 24809.68 | 01-SEP-14:09 | 26047.91 | 01-SEP-16:40 | 4644.69 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.07 | 10-SEP-14:55 | 118.27 | 15-SEP-21:35 |
October | 24809.68 | 02-OCT-14:09 | 26047.91 | 02-OCT-16:30 | 4644.69 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 422.04 | 08-OCT-18:10 | 80.12 | 23-OCT-04:40 |
November | 24809.68 | 01-NOV-14:09 | 26047.91 | 01-NOV-15:00 | 4644.69 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 181.99 | 02-NOV-21:52 | 141.84 | 25-NOV-05:15 |
December | 24809.68 | 01-DEC-15:09 | 26047.91 | 01-DEC-16:10 | 4644.69 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 200.77 | 10-DEC-19:10 | 327.33 | 21-DEC-05:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 26047.91 | 4644.69 | 0.00 | 0.00 | 0.00 | 0.00 | 181.99 | 17.83 | |||||
Maximum of Months | 24809.68 | 26047.91 | 4644.69 | 0.00 | 0.00 | 0.00 | 0.00 | 833.35 | 577.39 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2454.44 | 02-JAN-09:09 | 2915.92 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 157.95 | 08-JAN-19:10 | 442.51 | 07-JAN-05:00 |
February | 2337.76 | 01-FEB-15:09 | 2454.44 | 01-FEB-09:09 | 2915.92 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 201.64 | 20-FEB-19:10 | 36.68 | 24-FEB-01:00 |
March | 2337.76 | 01-MAR-15:09 | 2454.44 | 01-MAR-09:09 | 2915.92 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 441.15 | 19-MAR-18:10 | 85.91 | 14-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 2454.44 | 01-APR-09:09 | 2915.92 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 272.61 | 02-APR-19:00 | 20.27 | 22-APR-02:40 |
May | 2337.76 | 01-MAY-14:09 | 2454.44 | 01-MAY-08:09 | 2915.92 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 350.15 | 07-MAY-18:10 | 141.31 | 08-MAY-22:00 |
June | 2337.76 | 01-JUN-14:09 | 2454.44 | 01-JUN-08:09 | 2915.92 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 327.29 | 11-JUN-19:00 | 118.00 | 20-JUN-23:20 |
July | 2337.76 | 01-JUL-10:09 | 2454.44 | 01-JUL-09:09 | 2915.92 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.93 | 25-JUL-21:00 | 75.86 | 19-JUL-20:40 |
August | 2337.76 | 01-AUG-14:09 | 2454.44 | 01-AUG-08:09 | 2915.92 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 262.69 | 01-AUG-21:00 | 98.84 | 23-AUG-20:05 |
September | 2337.76 | 01-SEP-14:09 | 2454.44 | 01-SEP-08:09 | 2915.92 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 155.15 | 10-SEP-14:55 | 76.49 | 15-SEP-22:00 |
October | 2337.76 | 02-OCT-14:09 | 2454.44 | 02-OCT-08:09 | 2915.92 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 223.50 | 08-OCT-18:10 | 47.65 | 23-OCT-04:55 |
November | 2337.76 | 01-NOV-14:09 | 2454.44 | 01-NOV-08:09 | 2915.92 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 93.78 | 02-NOV-20:10 | 82.87 | 25-NOV-05:00 |
December | 2337.76 | 01-DEC-15:09 | 2454.44 | 01-DEC-09:09 | 2915.92 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.28 | 10-DEC-19:10 | 175.25 | 21-DEC-05:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2454.44 | 2915.92 | 0.00 | 0.00 | 0.00 | 0.00 | 93.78 | 20.27 | |||||
Maximum of Months | 2337.76 | 2454.44 | 2915.92 | 0.00 | 0.00 | 0.00 | 0.00 | 441.15 | 442.51 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2454.44 | 02-JAN-09:09 | 437.66 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 157.97 | 08-JAN-19:10 | 418.22 | 07-JAN-05:00 |
February | 2337.76 | 01-FEB-15:09 | 2454.44 | 01-FEB-09:09 | 437.66 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 201.64 | 20-FEB-19:10 | 32.18 | 24-FEB-01:00 |
March | 2337.76 | 01-MAR-15:09 | 2454.44 | 01-MAR-09:09 | 437.66 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 441.15 | 19-MAR-18:10 | 77.71 | 14-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 2454.44 | 01-APR-09:09 | 437.66 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 272.64 | 02-APR-19:00 | 15.68 | 22-APR-02:40 |
May | 2337.76 | 01-MAY-14:09 | 2454.44 | 01-MAY-08:09 | 437.66 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 350.14 | 07-MAY-18:10 | 127.50 | 08-MAY-22:00 |
June | 2337.76 | 01-JUN-14:09 | 2454.44 | 01-JUN-08:09 | 437.66 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 327.29 | 11-JUN-19:00 | 104.75 | 20-JUN-23:20 |
July | 2337.76 | 01-JUL-10:09 | 2454.44 | 01-JUL-09:09 | 437.66 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.94 | 25-JUL-20:50 | 65.27 | 19-JUL-20:40 |
August | 2337.76 | 01-AUG-14:09 | 2454.44 | 01-AUG-08:09 | 437.66 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 262.69 | 01-AUG-21:00 | 90.56 | 23-AUG-20:05 |
September | 2337.76 | 01-SEP-14:09 | 2454.44 | 01-SEP-08:09 | 437.66 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 155.15 | 10-SEP-15:00 | 67.88 | 15-SEP-22:00 |
October | 2337.76 | 02-OCT-14:09 | 2454.44 | 02-OCT-08:09 | 437.66 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 223.53 | 08-OCT-18:10 | 46.90 | 23-OCT-05:00 |
November | 2337.76 | 01-NOV-14:09 | 2454.44 | 01-NOV-08:09 | 437.66 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 93.78 | 02-NOV-20:10 | 80.56 | 25-NOV-05:00 |
December | 2337.76 | 01-DEC-15:09 | 2454.44 | 01-DEC-09:09 | 437.66 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.30 | 10-DEC-19:10 | 170.71 | 21-DEC-05:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2454.44 | 437.66 | 0.00 | 0.00 | 0.00 | 0.00 | 93.78 | 15.68 | |||||
Maximum of Months | 2337.76 | 2454.44 | 437.66 | 0.00 | 0.00 | 0.00 | 0.00 | 441.15 | 418.22 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 85.79 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.79 | 11-JAN-08:63 | 1504.46 | 24-JAN-08:61 |
February | 0.00 | 01-FEB-00:10 | 85.79 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641.71 | 26-FEB-12:55 | 1150.32 | 21-FEB-09:53 |
March | 0.00 | 01-MAR-00:10 | 85.79 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2347.38 | 03-MAR-12:02 | 1370.62 | 14-MAR-11:02 |
April | 0.00 | 01-APR-00:10 | 85.79 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1667.60 | 09-APR-11:02 | 1162.46 | 14-APR-15:53 |
May | 0.00 | 01-MAY-00:10 | 85.79 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2725.53 | 05-MAY-11:01 | 1770.24 | 21-MAY-12:52 |
June | 0.00 | 01-JUN-00:10 | 85.79 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1666.81 | 16-JUN-11:02 | 1501.92 | 30-JUN-12:53 |
July | 0.00 | 01-JUL-00:10 | 85.79 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1165.31 | 01-JUL-11:02 | 1443.68 | 03-JUL-12:53 |
August | 0.00 | 01-AUG-00:10 | 85.79 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2011.24 | 16-AUG-11:02 | 1701.78 | 25-AUG-11:02 |
September | 0.00 | 01-SEP-00:10 | 85.79 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 919.74 | 09-SEP-11:03 | 1618.91 | 15-SEP-16:53 |
October | 0.00 | 01-OCT-00:10 | 85.79 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.34 | 26-OCT-11:03 | 1053.61 | 29-OCT-16:55 |
November | 0.00 | 01-NOV-00:10 | 85.79 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.38 | 18-NOV-12:55 | 1107.66 | 09-NOV-15:55 |
December | 0.00 | 01-DEC-00:10 | 85.79 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.28 | 11-DEC-12:05 | 1190.49 | 21-DEC-08:61 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 85.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.28 | 1053.61 | ||||
Maximum of Months | 0.00 | 85.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2725.53 | 1770.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36966.25 | 15-JAN-19:08 | 0.00 | 718.66 | 2280.66 | 0.00 | 0.00 | 0.00 | 0.00 | 159.75 | 0.00 |
February | 37828.11 | 24-FEB-21:07 | 0.00 | 3449.57 | 3649.06 | 0.00 | 0.00 | 0.00 | 0.00 | 62.57 | 0.00 |
March | 36593.87 | 21-MAR-20:05 | 0.00 | 3449.57 | 3649.06 | 0.00 | 0.00 | 0.00 | 0.00 | 279.11 | 0.00 |
April | 35923.18 | 26-APR-20:06 | 0.00 | 2874.64 | 3040.88 | 0.00 | 0.00 | 0.00 | 0.00 | 371.31 | 0.00 |
May | 36788.00 | 31-MAY-20:06 | 0.00 | 2874.64 | 3040.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.98 |
June | 36827.08 | 27-JUN-01:23 | 0.00 | 431.20 | 1824.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37602.64 | 20-JUL-00:43 | 0.00 | 431.20 | 1824.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 |
August | 36183.17 | 24-AUG-00:03 | 0.00 | 431.20 | 1824.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 |
September | 34931.64 | 12-SEP-20:06 | 0.00 | 2874.64 | 3040.88 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 | 0.00 |
October | 34178.40 | 09-OCT-18:08 | 0.00 | 574.93 | 1824.53 | 0.00 | 0.00 | 0.00 | 0.00 | 16.14 | 0.00 |
November | 34070.03 | 22-NOV-21:06 | 0.00 | 2874.64 | 3040.88 | 0.00 | 0.00 | 0.00 | 0.00 | 31.41 | 0.00 |
December | 37504.34 | 20-DEC-21:08 | 0.00 | 2874.64 | 3040.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.09 |
Annual Sum or Average | |||||||||||
Minimum of Months | 34070.03 | 0.00 | 431.20 | 1824.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37828.11 | 0.00 | 3449.57 | 3649.06 | 0.00 | 0.00 | 0.00 | 0.00 | 371.31 | 86.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 130722.34 | 15-JAN-19:10 | 0.00 | 7235.53 | 3845.76 | 0.00 | 0.00 | 0.00 | 0.00 | 133.91 | 0.00 |
February | 133187.59 | 24-FEB-21:07 | 0.00 | 34730.55 | 6153.22 | 0.00 | 0.00 | 0.00 | 0.00 | 54.05 | 0.00 |
March | 126866.56 | 02-MAR-21:08 | 0.00 | 28942.12 | 5127.69 | 0.00 | 0.00 | 0.00 | 0.00 | 181.97 | 0.00 |
April | 119488.33 | 26-APR-20:08 | 0.00 | 28942.12 | 5127.69 | 0.00 | 0.00 | 0.00 | 0.00 | 308.09 | 0.00 |
May | 119294.33 | 10-MAY-20:08 | 0.00 | 28942.12 | 5127.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.63 |
June | 112012.08 | 07-JUN-20:08 | 0.00 | 28942.12 | 5127.69 | 0.00 | 0.00 | 0.00 | 0.00 | 129.85 | 0.00 |
July | 120695.96 | 19-JUL-20:10 | 0.00 | 23153.70 | 4102.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.10 |
August | 119321.18 | 23-AUG-20:10 | 0.00 | 23153.70 | 4102.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.31 |
September | 113768.22 | 12-SEP-20:08 | 0.00 | 28942.12 | 5127.69 | 0.00 | 0.00 | 0.00 | 0.00 | 12.97 | 0.00 |
October | 111223.83 | 09-OCT-18:10 | 0.00 | 5788.42 | 3076.61 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 0.00 |
November | 122271.18 | 24-NOV-21:10 | 0.00 | 23153.70 | 4102.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 |
December | 140813.98 | 20-DEC-21:10 | 0.00 | 28942.12 | 5127.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.72 |
Annual Sum or Average | |||||||||||
Minimum of Months | 111223.83 | 0.00 | 5788.42 | 3076.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 140813.98 | 0.00 | 34730.55 | 6153.22 | 0.00 | 0.00 | 0.00 | 0.00 | 308.09 | 118.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20339.71 | 16-JAN-19:05 | 0.00 | 818.15 | 2897.23 | 0.00 | 0.00 | 0.00 | 0.00 | 65.23 | 0.00 |
February | 20646.23 | 24-FEB-21:05 | 0.00 | 3272.58 | 3862.97 | 0.00 | 0.00 | 0.00 | 0.00 | 24.84 | 0.00 |
March | 19403.94 | 02-MAR-21:06 | 0.00 | 2727.15 | 3219.14 | 0.00 | 0.00 | 0.00 | 0.00 | 89.17 | 0.00 |
April | 18343.39 | 26-APR-20:06 | 0.00 | 2727.15 | 3219.14 | 0.00 | 0.00 | 0.00 | 0.00 | 157.71 | 0.00 |
May | 18389.71 | 10-MAY-20:06 | 0.00 | 2727.15 | 3219.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.02 |
June | 17613.55 | 07-JUN-20:06 | 0.00 | 2727.15 | 3219.14 | 0.00 | 0.00 | 0.00 | 0.00 | 65.81 | 0.00 |
July | 18230.43 | 13-JUL-20:06 | 0.00 | 2727.15 | 3219.14 | 0.00 | 0.00 | 0.00 | 0.00 | 116.56 | 0.00 |
August | 18061.21 | 23-AUG-20:08 | 0.00 | 2181.72 | 2575.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.80 |
September | 17894.73 | 12-SEP-20:06 | 0.00 | 2727.15 | 3219.14 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 0.00 |
October | 17921.86 | 04-OCT-20:05 | 0.00 | 3272.58 | 3862.97 | 0.00 | 0.00 | 0.00 | 0.00 | 97.93 | 0.00 |
November | 19222.65 | 24-NOV-21:08 | 0.00 | 2181.72 | 2575.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.87 |
December | 21096.93 | 20-DEC-21:06 | 0.00 | 2727.15 | 3219.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.94 |
Annual Sum or Average | |||||||||||
Minimum of Months | 17613.55 | 0.00 | 818.15 | 2575.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21096.93 | 0.00 | 3272.58 | 3862.97 | 0.00 | 0.00 | 0.00 | 0.00 | 157.71 | 64.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17802.18 | 16-JAN-19:05 | 0.00 | 818.15 | 434.85 | 0.00 | 0.00 | 0.00 | 0.00 | 66.81 | 0.00 |
February | 17956.43 | 24-FEB-21:05 | 0.00 | 3272.58 | 579.80 | 0.00 | 0.00 | 0.00 | 0.00 | 25.54 | 0.00 |
March | 16778.25 | 02-MAR-21:06 | 0.00 | 2727.15 | 483.17 | 0.00 | 0.00 | 0.00 | 0.00 | 91.47 | 0.00 |
April | 15727.02 | 26-APR-20:06 | 0.00 | 2727.15 | 483.17 | 0.00 | 0.00 | 0.00 | 0.00 | 160.85 | 0.00 |
May | 15691.25 | 10-MAY-20:06 | 0.00 | 2727.15 | 483.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 |
June | 15068.25 | 02-JUN-23:23 | 0.00 | 409.07 | 289.90 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 0.00 |
July | 15759.35 | 09-JUL-18:06 | 0.00 | 681.79 | 362.38 | 0.00 | 0.00 | 0.00 | 0.00 | 129.23 | 0.00 |
August | 15457.36 | 23-AUG-20:08 | 0.00 | 2181.72 | 386.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.95 |
September | 15281.49 | 03-SEP-18:08 | 0.00 | 545.43 | 289.90 | 0.00 | 0.00 | 0.00 | 0.00 | 22.93 | 0.00 |
October | 15585.45 | 09-OCT-18:08 | 0.00 | 545.43 | 289.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 | 0.00 |
November | 16655.91 | 24-NOV-21:08 | 0.00 | 2181.72 | 386.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.10 |
December | 18453.39 | 20-DEC-21:06 | 0.00 | 2727.15 | 483.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.38 |
Annual Sum or Average | |||||||||||
Minimum of Months | 15068.25 | 0.00 | 409.07 | 289.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18453.39 | 0.00 | 3272.58 | 579.80 | 0.00 | 0.00 | 0.00 | 0.00 | 160.85 | 60.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.96 |
April | 0.00 | 01-APR-00:03 | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.90 |
May | 0.00 | 01-MAY-00:03 | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 0.00 |
June | 0.00 | 01-JUN-00:03 | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.69 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.10 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.89 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 9.96 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.140874E+12 | 106855.77 | 04-JAN-15:30 | 0.714367E+10 | 4789.90 | 09-JAN-12:30 |
February | 0.132659E+12 | 111359.83 | 13-FEB-15:00 | 0.645561E+10 | 4788.72 | 03-FEB-12:30 |
March | 0.156787E+12 | 113728.77 | 28-MAR-15:50 | 0.716238E+10 | 4784.00 | 02-MAR-12:30 |
April | 0.159466E+12 | 119888.56 | 01-APR-15:50 | 0.686707E+10 | 4775.46 | 03-APR-11:30 |
May | 0.169426E+12 | 129883.81 | 06-MAY-15:30 | 0.706091E+10 | 4766.99 | 02-MAY-11:39 |
June | 0.167990E+12 | 127438.64 | 13-JUN-14:00 | 0.683181E+10 | 4759.52 | 01-JUN-11:09 |
July | 0.148315E+12 | 111624.42 | 15-JUL-16:00 | 0.700400E+10 | 4755.63 | 28-JUL-11:39 |
August | 0.158909E+12 | 118168.95 | 14-AUG-16:00 | 0.706634E+10 | 4760.68 | 31-AUG-11:09 |
September | 0.151129E+12 | 115048.59 | 09-SEP-15:30 | 0.683730E+10 | 4768.13 | 29-SEP-11:20 |
October | 0.146326E+12 | 110756.88 | 04-OCT-15:20 | 0.707712E+10 | 4777.62 | 31-OCT-11:39 |
November | 0.140777E+12 | 108299.79 | 14-NOV-15:00 | 0.687576E+10 | 4785.17 | 30-NOV-12:39 |
December | 0.141232E+12 | 106896.82 | 30-DEC-16:19 | 0.713907E+10 | 4789.12 | 27-DEC-12:09 |
Annual Sum or Average | 0.181389E+13 | 0.835210E+11 | ||||
Minimum of Months | 0.132659E+12 | 106855.77 | 0.645561E+10 | 4755.63 | ||
Maximum of Months | 0.169426E+12 | 129883.81 | 0.716238E+10 | 4789.90 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.333685E+11 | 0.542825E+10 | 0.163964E+11 | 0.00 | 0.184248E+11 | 0.00 | 0.00 | 0.672561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293792E+11 | 0.481116E+10 | 0.148755E+11 | 0.00 | 0.172039E+11 | 0.00 | 0.00 | 0.663891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344470E+11 | 0.513008E+10 | 0.168094E+11 | 0.00 | 0.200738E+11 | 0.00 | 0.00 | 0.803265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324152E+11 | 0.482221E+10 | 0.159735E+11 | 0.00 | 0.206110E+11 | 0.00 | 0.00 | 0.856441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.334854E+11 | 0.487929E+10 | 0.166029E+11 | 0.00 | 0.220136E+11 | 0.00 | 0.00 | 0.924445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.320892E+11 | 0.465502E+10 | 0.162336E+11 | 0.00 | 0.220708E+11 | 0.00 | 0.00 | 0.929415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.324216E+11 | 0.485700E+10 | 0.163428E+11 | 0.00 | 0.194446E+11 | 0.00 | 0.00 | 0.752488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.338274E+11 | 0.493224E+10 | 0.168094E+11 | 0.00 | 0.207507E+11 | 0.00 | 0.00 | 0.825898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.317358E+11 | 0.492253E+10 | 0.159735E+11 | 0.00 | 0.197458E+11 | 0.00 | 0.00 | 0.787514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.319701E+11 | 0.524712E+10 | 0.163964E+11 | 0.00 | 0.191655E+11 | 0.00 | 0.00 | 0.735473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.319685E+11 | 0.522831E+10 | 0.158742E+11 | 0.00 | 0.182253E+11 | 0.00 | 0.00 | 0.694810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.338679E+11 | 0.547102E+10 | 0.163428E+11 | 0.00 | 0.183754E+11 | 0.00 | 0.00 | 0.671749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.390976E+12 | 0.603842E+11 | 0.194630E+12 | 0.236105E+12 | 0.00 | 0.931795E+12 | |||||||
Minimum of Months | 0.293792E+11 | 0.465502E+10 | 0.148755E+11 | 0.00 | 0.172039E+11 | 0.00 | 0.00 | 0.663891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.344470E+11 | 0.547102E+10 | 0.168094E+11 | 0.00 | 0.220708E+11 | 0.00 | 0.00 | 0.929415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.714367E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.645561E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.716238E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.686707E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.706091E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.683181E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.700400E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.706634E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.683730E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.707712E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.687576E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.713907E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.835210E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.645561E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.716238E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 33387.34 | 02-JAN-16:10 | 4644.30 | 01-JAN-06:10 | 10752.72 | 02-JAN-09:09 | 0.00 | 11224.20 | 04-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 33387.34 | 01-FEB-16:40 | 4644.30 | 01-FEB-06:10 | 10752.72 | 01-FEB-09:09 | 0.00 | 12011.06 | 13-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 33387.34 | 01-MAR-16:30 | 4644.30 | 01-MAR-06:10 | 10752.72 | 01-MAR-09:09 | 0.00 | 12909.19 | 28-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 33387.34 | 01-APR-16:49 | 4644.30 | 01-APR-05:10 | 10752.72 | 01-APR-09:09 | 0.00 | 13956.31 | 01-APR-14:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 33387.34 | 01-MAY-16:49 | 4644.30 | 01-MAY-05:10 | 10752.72 | 01-MAY-08:09 | 0.00 | 15384.60 | 06-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 33387.34 | 01-JUN-16:00 | 4644.30 | 01-JUN-05:10 | 10752.72 | 01-JUN-08:09 | 0.00 | 15736.73 | 13-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 33387.34 | 01-JUL-16:49 | 4644.30 | 01-JUL-05:10 | 10752.72 | 01-JUL-09:09 | 0.00 | 12561.40 | 15-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 33387.34 | 01-AUG-16:00 | 4644.30 | 01-AUG-05:10 | 10752.72 | 01-AUG-08:09 | 0.00 | 14327.62 | 09-AUG-14:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 33387.34 | 01-SEP-16:40 | 4644.30 | 01-SEP-05:10 | 10752.72 | 01-SEP-08:09 | 0.00 | 13647.77 | 30-SEP-10:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 33387.34 | 02-OCT-16:30 | 4644.30 | 01-OCT-05:10 | 10752.72 | 02-OCT-08:09 | 0.00 | 12644.19 | 16-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 33387.34 | 01-NOV-15:00 | 4644.30 | 01-NOV-05:10 | 10752.72 | 01-NOV-08:09 | 0.00 | 11735.28 | 14-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 33387.34 | 01-DEC-16:10 | 4644.30 | 01-DEC-17:30 | 10752.72 | 01-DEC-09:09 | 0.00 | 11289.75 | 30-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 33387.34 | 4644.30 | 10752.72 | 0.00 | 11224.20 | 0.00 | 0.00 | |||||
Maximum of Months | 33387.34 | 4644.30 | 10752.72 | 0.00 | 15736.73 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 53724.86 | 04-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 57881.28 | 28-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 61474.61 | 28-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65644.85 | 01-APR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73637.29 | 06-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74073.84 | 13-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 57641.66 | 15-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 64858.33 | 09-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 62393.98 | 30-SEP-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57867.64 | 04-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 55373.75 | 18-NOV-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 53289.48 | 30-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 53289.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74073.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 106855.77 | 04-JAN-15:30 | 31216.68 | 10752.72 | 0.00 | 0.00 | 11161.52 | 0.00 | 0.00 | 53724.86 | 0.00 |
February | 111359.83 | 13-FEB-15:00 | 31216.68 | 10752.72 | 0.00 | 0.00 | 12011.06 | 0.00 | 0.00 | 57379.38 | 0.00 |
March | 113728.77 | 28-MAR-15:50 | 31216.68 | 10752.72 | 0.00 | 0.00 | 12655.38 | 0.00 | 0.00 | 59103.99 | 0.00 |
April | 119888.56 | 01-APR-15:50 | 31216.68 | 10752.72 | 0.00 | 0.00 | 13823.80 | 0.00 | 0.00 | 64095.37 | 0.00 |
May | 129883.81 | 06-MAY-15:30 | 31216.68 | 10752.72 | 0.00 | 0.00 | 15384.60 | 0.00 | 0.00 | 72529.82 | 0.00 |
June | 127438.64 | 13-JUN-14:00 | 26875.36 | 10752.72 | 0.00 | 0.00 | 15736.73 | 0.00 | 0.00 | 74073.84 | 0.00 |
July | 111624.42 | 15-JUL-16:00 | 33387.34 | 10752.72 | 0.00 | 0.00 | 12089.71 | 0.00 | 0.00 | 55394.66 | 0.00 |
August | 118168.95 | 14-AUG-16:00 | 33387.34 | 10752.72 | 0.00 | 0.00 | 13522.13 | 0.00 | 0.00 | 60506.77 | 0.00 |
September | 115048.59 | 09-SEP-15:30 | 31216.68 | 10752.72 | 0.00 | 0.00 | 13297.87 | 0.00 | 0.00 | 59781.32 | 0.00 |
October | 110756.88 | 04-OCT-15:20 | 31216.68 | 10752.72 | 0.00 | 0.00 | 12220.13 | 0.00 | 0.00 | 56567.36 | 0.00 |
November | 108299.79 | 14-NOV-15:00 | 33387.34 | 10752.72 | 0.00 | 0.00 | 11735.28 | 0.00 | 0.00 | 52424.45 | 0.00 |
December | 106896.82 | 30-DEC-16:19 | 33387.34 | 10752.72 | 0.00 | 0.00 | 11202.88 | 0.00 | 0.00 | 51553.89 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 106855.77 | 26875.36 | 10752.72 | 0.00 | 0.00 | 11161.52 | 0.00 | 0.00 | 51553.89 | 0.00 | |
Maximum of Months | 129883.81 | 33387.34 | 10752.72 | 0.00 | 0.00 | 15736.73 | 0.00 | 0.00 | 74073.84 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 4789.90 | 09-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 4788.72 | 03-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 4784.00 | 02-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 4775.46 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4766.99 | 02-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4759.52 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4755.63 | 28-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4760.68 | 31-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4768.13 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 4777.62 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 4785.17 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 4789.12 | 27-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4755.63 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4789.90 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 24.55 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 39.50 | 24.58 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 57.17 | 24.64 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 59.83 | 24.73 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 59.00 | 24.81 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 63.17 | 24.89 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 | 24.70 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 51.50 | 24.69 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 24.63 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 24.57 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 24.55 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 24.53 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 563.33 | 24.69 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 24.53 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 | 24.89 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.47 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.47 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 24.49 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 24.50 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 24.50 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 24.51 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.48 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.49 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.49 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.48 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.45 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.46 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 69.50 | 24.49 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.45 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 24.51 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 67.83 | 24.88 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 24.91 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 69.00 | 24.91 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 63.50 | 24.88 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 64.83 | 24.84 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 65.17 | 24.86 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 69.33 | 24.73 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 56.83 | 24.77 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 62.17 | 24.80 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 60.50 | 24.80 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 62.50 | 24.82 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 67.50 | 24.83 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 774.17 | 24.84 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 56.83 | 24.73 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 69.33 | 24.91 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 61.50 | 24.78 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 62.67 | 24.79 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 64.83 | 24.78 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 59.83 | 24.75 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 58.17 | 24.75 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 60.00 | 24.76 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 57.83 | 24.65 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 | 24.67 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 55.17 | 24.70 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 53.17 | 24.70 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 56.00 | 24.73 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 58.00 | 24.75 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 696.50 | 24.74 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 | 24.65 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 64.83 | 24.79 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 408.50 | 23.89 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 375.83 | 23.89 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 421.83 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 405.00 | 23.89 | 0.00 | 0.00 |
May | 11.17 | 23.89 | 418.00 | 23.89 | 11.17 | 23.89 |
June | 0.00 | 0.00 | 408.00 | 23.89 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 415.00 | 23.89 | 0.00 | 0.00 |
August | 20.17 | 23.89 | 422.00 | 23.89 | 20.17 | 23.89 |
September | 3.67 | 23.89 | 405.00 | 23.89 | 3.67 | 23.89 |
October | 13.50 | 23.89 | 414.00 | 23.89 | 13.50 | 23.89 |
November | 0.00 | 0.00 | 398.83 | 23.89 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 412.67 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 48.50 | 23.89 | 4904.67 | 23.89 | 48.50 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 375.83 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 20.17 | 23.89 | 422.00 | 23.89 | 20.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.67 | 23.89 | 413.17 | 23.89 | 23.67 | 23.89 |
February | 10.50 | 23.89 | 376.00 | 23.89 | 10.50 | 23.89 |
March | 20.83 | 23.89 | 422.00 | 23.89 | 20.83 | 23.89 |
April | 72.00 | 23.89 | 405.00 | 23.89 | 72.00 | 23.89 |
May | 159.00 | 23.89 | 418.00 | 23.89 | 159.00 | 23.89 |
June | 143.50 | 23.89 | 408.00 | 23.89 | 143.50 | 23.89 |
July | 81.67 | 23.89 | 415.00 | 23.89 | 81.67 | 23.89 |
August | 192.17 | 23.89 | 422.00 | 23.89 | 192.17 | 23.89 |
September | 150.33 | 23.89 | 405.00 | 23.89 | 150.33 | 23.89 |
October | 179.50 | 23.89 | 414.00 | 23.89 | 179.50 | 23.89 |
November | 78.67 | 23.89 | 399.00 | 23.89 | 78.67 | 23.89 |
December | 41.67 | 23.89 | 414.83 | 23.89 | 41.67 | 23.89 |
Annual Sum or Average | 1153.50 | 23.89 | 4912.00 | 23.89 | 1153.50 | 23.89 |
Minimum of Months | 10.50 | 23.89 | 376.00 | 23.89 | 10.50 | 23.89 |
Maximum of Months | 192.17 | 23.89 | 422.00 | 23.89 | 192.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 414.00 | 23.89 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 422.00 | 23.89 | 0.00 | 0.00 |
April | 4.83 | 23.89 | 405.00 | 23.89 | 4.83 | 23.89 |
May | 51.17 | 23.89 | 418.00 | 23.89 | 51.17 | 23.89 |
June | 31.33 | 23.89 | 408.00 | 23.89 | 31.33 | 23.89 |
July | 2.33 | 23.89 | 415.00 | 23.89 | 2.33 | 23.89 |
August | 63.50 | 23.89 | 422.00 | 23.89 | 63.50 | 23.89 |
September | 27.83 | 23.89 | 405.00 | 23.89 | 27.83 | 23.89 |
October | 21.67 | 23.89 | 414.00 | 23.89 | 21.67 | 23.89 |
November | 0.00 | 0.00 | 399.00 | 23.89 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 415.00 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 202.67 | 23.89 | 4913.00 | 23.89 | 202.67 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 63.50 | 23.89 | 422.00 | 23.89 | 63.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 23.89 | 414.00 | 23.89 | 2.00 | 23.89 |
February | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 0.00 |
March | 2.50 | 23.89 | 422.00 | 23.89 | 2.50 | 23.89 |
April | 20.67 | 23.89 | 405.00 | 23.89 | 20.67 | 23.89 |
May | 94.17 | 23.89 | 418.00 | 23.89 | 94.17 | 23.89 |
June | 75.50 | 23.89 | 408.00 | 23.89 | 75.50 | 23.89 |
July | 20.33 | 23.89 | 415.00 | 23.89 | 20.33 | 23.89 |
August | 127.67 | 23.89 | 422.00 | 23.89 | 127.67 | 23.89 |
September | 64.67 | 23.89 | 405.00 | 23.89 | 64.67 | 23.89 |
October | 65.33 | 23.89 | 414.00 | 23.89 | 65.33 | 23.89 |
November | 5.00 | 23.89 | 399.00 | 23.89 | 5.00 | 23.89 |
December | 2.33 | 23.89 | 415.00 | 23.89 | 2.33 | 23.89 |
Annual Sum or Average | 480.17 | 23.89 | 4913.00 | 23.89 | 480.17 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 127.67 | 23.89 | 422.00 | 23.89 | 127.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.88964 | 52.09702 | 0.55971 | 11.60646 |
February | 376.00000 | 23.88968 | 51.37348 | 0.58107 | 12.12281 |
March | 422.00000 | 23.88950 | 51.93516 | 0.60210 | 12.65372 |
April | 405.00000 | 23.88935 | 53.37420 | 0.63324 | 13.46146 |
May | 418.00000 | 23.88926 | 54.93237 | -0.1665 | 5.72829 |
June | 408.00000 | 23.88920 | 53.52073 | -0.1312 | 5.52958 |
July | 415.00000 | 23.88946 | 52.28979 | -0.2096 | 6.02727 |
August | 422.00000 | 23.88938 | 56.63168 | -0.2141 | 6.09435 |
September | 405.00000 | 23.88946 | 55.94331 | -0.2251 | 6.15067 |
October | 414.00000 | 23.88956 | 57.14263 | 0.59267 | 12.40089 |
November | 399.00000 | 23.88964 | 54.82876 | 0.58269 | 12.15042 |
December | 415.00000 | 23.88964 | 53.46948 | 0.56112 | 11.63178 |
Annual Sum or Average | 4913.00000 | 23.88948 | 53.97830 | 0.26050 | 9.60286 |
Minimum of Months | 376.00000 | 23.88920 | 51.37348 | -0.2251 | 5.52958 |
Maximum of Months | 422.00000 | 23.88968 | 57.14263 | 0.63324 | 13.46146 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.88955 | 56.75544 | 0.59547 | 12.46786 |
February | 376.00000 | 23.88955 | 56.53188 | 0.61017 | 12.84629 |
March | 422.00000 | 23.88946 | 56.87983 | 0.62860 | 13.33430 |
April | 405.00000 | 23.88945 | 60.19023 | 0.65661 | 14.08753 |
May | 418.00000 | 23.88946 | 63.62634 | -0.1784 | 5.72523 |
June | 408.00000 | 23.88943 | 63.33670 | -0.1670 | 5.64905 |
July | 415.00000 | 23.88950 | 60.76523 | -0.2205 | 6.06516 |
August | 422.00000 | 23.88949 | 64.63641 | -0.1977 | 5.89007 |
September | 405.00000 | 23.88950 | 63.69476 | -0.1977 | 5.87317 |
October | 414.00000 | 23.88952 | 64.21971 | 0.63475 | 13.47988 |
November | 399.00000 | 23.88957 | 61.24208 | 0.62166 | 13.13293 |
December | 415.00000 | 23.88958 | 58.47506 | 0.60207 | 12.62920 |
Annual Sum or Average | 4913.00000 | 23.88950 | 60.88957 | 0.27888 | 10.06829 |
Minimum of Months | 376.00000 | 23.88943 | 56.53188 | -0.2205 | 5.64905 |
Maximum of Months | 422.00000 | 23.88958 | 64.63641 | 0.65661 | 14.08753 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.88947 | 49.70740 | 0.72213 | 16.09363 |
February | 376.00000 | 23.88948 | 50.01775 | 0.73025 | 16.33114 |
March | 422.00000 | 23.88946 | 51.98224 | 0.70907 | 15.67253 |
April | 405.00000 | 23.88950 | 55.61098 | 0.70614 | 15.54656 |
May | 418.00000 | 23.88951 | 58.06528 | -0.0916 | 5.32535 |
June | 408.00000 | 23.88949 | 57.88259 | -0.0816 | 5.28043 |
July | 415.00000 | 23.88963 | 55.65026 | -0.1410 | 5.53451 |
August | 422.00000 | 23.88953 | 59.23640 | -0.1313 | 5.53058 |
September | 405.00000 | 23.88957 | 57.52898 | -0.1071 | 5.40452 |
October | 414.00000 | 23.88955 | 56.95423 | 0.69693 | 15.30443 |
November | 399.00000 | 23.88955 | 53.32357 | 0.71804 | 15.94094 |
December | 415.00000 | 23.88952 | 50.81710 | 0.72250 | 16.09574 |
Annual Sum or Average | 4913.00000 | 23.88952 | 54.76653 | 0.36734 | 11.45728 |
Minimum of Months | 376.00000 | 23.88946 | 49.70740 | -0.1410 | 5.28043 |
Maximum of Months | 422.00000 | 23.88963 | 59.23640 | 0.73025 | 16.33114 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.88949 | 50.67721 | 0.70664 | 15.61622 |
February | 376.00000 | 23.88949 | 50.91759 | 0.71488 | 15.85579 |
March | 422.00000 | 23.88949 | 53.25346 | 0.69475 | 15.24296 |
April | 405.00000 | 23.88952 | 57.24353 | 0.69583 | 15.23581 |
May | 418.00000 | 23.88953 | 60.00444 | -0.1089 | 5.38592 |
June | 408.00000 | 23.88952 | 59.68076 | -0.0984 | 5.33594 |
July | 415.00000 | 23.88964 | 57.59016 | -0.1594 | 5.64072 |
August | 422.00000 | 23.88957 | 61.60815 | -0.1460 | 5.60209 |
September | 405.00000 | 23.88956 | 59.54794 | -0.1242 | 5.47411 |
October | 414.00000 | 23.88958 | 59.07622 | 0.68834 | 15.04073 |
November | 399.00000 | 23.88955 | 54.77341 | 0.70552 | 15.55400 |
December | 415.00000 | 23.88953 | 51.93114 | 0.70787 | 15.64437 |
Annual Sum or Average | 4913.00000 | 23.88954 | 56.39988 | 0.35271 | 11.25700 |
Minimum of Months | 376.00000 | 23.88949 | 50.67721 | -0.1594 | 5.33594 |
Maximum of Months | 422.00000 | 23.88964 | 61.60815 | 0.71488 | 15.85579 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.375093E+11 | 0.966039E+10 | 655.66 | 0.274441E+11 | 0.100652E+11 | 0.00 | 1.00 | 03-JAN-21:07 | 0.00 | 01-JAN-00:03 | 52876.01 | 09-JAN-21:06 | 41874.32 | 15-JAN-19:08 | 15601.02 | 09-JAN-21:06 | 12450.89 | 08-JAN-19:06 | 0.00 | 01-JAN-00:03 |
February | 0.379126E+11 | 0.978830E+10 | 603.57 | 0.281197E+11 | 0.979292E+10 | 0.00 | 1.00 | 01-FEB-21:06 | 0.00 | 01-FEB-00:12 | 52605.59 | 15-FEB-21:06 | 42506.00 | 24-FEB-21:07 | 14847.92 | 14-FEB-21:06 | 12551.51 | 26-FEB-19:05 | 0.00 | 01-FEB-00:10 |
March | 0.469046E+11 | 0.120969E+11 | 669.20 | 0.343855E+11 | 0.125191E+11 | 0.00 | 1.00 | 01-MAR-21:06 | 0.00 | 01-MAR-00:12 | 52704.42 | 14-MAR-20:06 | 40855.55 | 13-MAR-20:05 | 14098.49 | 14-MAR-20:06 | 12634.97 | 26-MAR-18:05 | 0.00 | 01-MAR-00:10 |
April | 0.515702E+11 | 0.131733E+11 | 644.26 | 0.363743E+11 | 0.151959E+11 | 0.00 | 1.00 | 01-APR-21:06 | 0.00 | 01-APR-00:33 | 52623.73 | 10-APR-20:08 | 40765.69 | 26-APR-20:06 | 17332.16 | 20-APR-20:10 | 13253.87 | 30-APR-18:43 | 0.00 | 01-APR-00:03 |
May | 0.587193E+11 | 0.148516E+11 | 664.54 | 0.399569E+11 | 0.187624E+11 | 0.00 | 1.00 | 01-MAY-20:06 | 0.00 | 01-MAY-00:33 | 53434.27 | 20-MAY-03:23 | 40556.78 | 11-MAY-01:23 | 18469.44 | 21-MAY-18:10 | 13135.91 | 29-MAY-18:06 | 0.00 | 01-MAY-00:03 |
June | 0.620502E+11 | 0.156074E+11 | 646.68 | 0.429767E+11 | 0.190735E+11 | 0.00 | 1.00 | 01-JUN-01:23 | 0.00 | 01-JUN-00:33 | 53505.97 | 28-JUN-20:08 | 41486.08 | 07-JUN-20:42 | 18795.97 | 28-JUN-20:08 | 12987.12 | 11-JUN-18:42 | 0.00 | 01-JUN-00:03 |
July | 0.502477E+11 | 0.125413E+11 | 664.14 | 0.360718E+11 | 0.141759E+11 | 0.00 | 1.00 | 01-JUL-21:08 | 0.00 | 01-JUL-00:10 | 53135.81 | 07-JUL-20:08 | 41709.64 | 16-JUL-03:43 | 15815.14 | 07-JUL-20:08 | 12648.91 | 30-JUL-18:06 | 0.00 | 01-JUL-00:05 |
August | 0.513924E+11 | 0.127482E+11 | 656.10 | 0.338046E+11 | 0.175878E+11 | 0.00 | 1.00 | 01-AUG-20:06 | 0.00 | 01-AUG-00:33 | 53418.63 | 11-AUG-02:43 | 40108.00 | 24-AUG-00:03 | 17316.36 | 06-AUG-18:08 | 12674.37 | 27-AUG-18:06 | 0.00 | 01-AUG-00:05 |
September | 0.471329E+11 | 0.117742E+11 | 640.85 | 0.315031E+11 | 0.156299E+11 | 0.00 | 1.00 | 01-SEP-20:06 | 0.00 | 01-SEP-00:33 | 53324.01 | 19-SEP-20:08 | 38969.26 | 03-SEP-18:08 | 17071.05 | 18-SEP-20:08 | 12704.12 | 04-SEP-18:06 | 0.00 | 01-SEP-00:05 |
October | 0.426760E+11 | 0.106643E+11 | 652.87 | 0.280286E+11 | 0.146474E+11 | 0.00 | 1.00 | 01-OCT-18:08 | 0.00 | 01-OCT-00:12 | 53488.88 | 27-OCT-20:08 | 38548.14 | 08-OCT-18:06 | 17419.93 | 27-OCT-20:08 | 12409.84 | 12-OCT-20:06 | 0.00 | 01-OCT-00:10 |
November | 0.396719E+11 | 0.999344E+10 | 635.86 | 0.271161E+11 | 0.125558E+11 | 0.00 | 1.00 | 01-NOV-20:08 | 0.00 | 01-NOV-00:33 | 53521.60 | 11-NOV-19:10 | 38522.09 | 05-NOV-18:06 | 17407.66 | 11-NOV-19:10 | 12517.43 | 19-NOV-19:07 | 0.00 | 01-NOV-00:05 |
December | 0.371062E+11 | 0.947425E+10 | 652.80 | 0.263243E+11 | 0.107819E+11 | 0.00 | 1.00 | 01-DEC-21:08 | 0.00 | 01-DEC-00:13 | 53286.55 | 23-DEC-22:10 | 41361.10 | 20-DEC-21:08 | 16428.61 | 10-DEC-19:06 | 12421.06 | 10-DEC-19:06 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.562893E+12 | 0.142374E+12 | 7786.53 | 0.392106E+12 | 0.170788E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.371062E+11 | 0.947425E+10 | 603.57 | 0.263243E+11 | 0.979292E+10 | 0.00 | 1.00 | 0.00 | 52605.59 | 38522.09 | 14098.49 | 12409.84 | 0.00 | |||||||
Maximum of Months | 0.620502E+11 | 0.156074E+11 | 669.20 | 0.429767E+11 | 0.190735E+11 | 0.00 | 1.00 | 0.00 | 53521.60 | 42506.00 | 18795.97 | 13253.87 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.158356E+12 | 0.434212E+11 | 617.46 | 0.100095E+12 | 0.582604E+11 | 0.00 | 1.00 | 02-JAN-21:10 | 0.00 | 01-JAN-00:03 | 228514.00 | 09-JAN-21:08 | 155633.23 | 15-JAN-19:10 | 97903.06 | 09-JAN-21:08 | 57411.85 | 08-JAN-19:08 | 0.00 | 01-JAN-00:03 |
February | 0.156294E+12 | 0.430456E+11 | 572.48 | 0.994900E+11 | 0.568038E+11 | 0.00 | 1.00 | 01-FEB-21:08 | 0.00 | 01-FEB-00:12 | 227387.16 | 15-FEB-21:08 | 158197.91 | 24-FEB-21:07 | 93798.30 | 15-FEB-21:08 | 57957.82 | 26-FEB-19:08 | 0.00 | 01-FEB-00:10 |
March | 0.193172E+12 | 0.532970E+11 | 652.40 | 0.122168E+12 | 0.710037E+11 | 0.00 | 1.00 | 01-MAR-21:08 | 0.00 | 01-MAR-00:12 | 226905.77 | 14-MAR-20:08 | 151588.73 | 13-MAR-20:07 | 92485.27 | 14-MAR-20:08 | 58313.60 | 26-MAR-18:07 | 0.00 | 01-MAR-00:10 |
April | 0.212961E+12 | 0.576874E+11 | 637.11 | 0.124362E+12 | 0.885995E+11 | 0.00 | 1.00 | 01-APR-21:08 | 0.00 | 01-APR-00:07 | 229415.81 | 10-APR-20:10 | 147651.84 | 26-APR-20:08 | 101390.13 | 20-APR-20:10 | 59283.57 | 30-APR-18:08 | 0.00 | 01-APR-00:03 |
May | 0.231854E+12 | 0.616614E+11 | 650.88 | 0.124917E+12 | 0.106937E+12 | 0.00 | 1.00 | 01-MAY-20:08 | 0.00 | 01-MAY-00:33 | 232856.68 | 16-MAY-20:08 | 136360.67 | 05-MAY-20:07 | 113016.35 | 16-MAY-20:08 | 60516.56 | 29-MAY-18:08 | 0.00 | 01-MAY-00:03 |
June | 0.232288E+12 | 0.616098E+11 | 630.91 | 0.125033E+12 | 0.107255E+12 | 0.00 | 1.00 | 01-JUN-20:10 | 0.00 | 01-JUN-00:07 | 233830.25 | 03-JUN-21:10 | 137521.59 | 07-JUN-20:08 | 116573.58 | 03-JUN-21:10 | 59709.63 | 11-JUN-18:42 | 0.00 | 01-JUN-00:03 |
July | 0.186221E+12 | 0.497523E+11 | 641.55 | 0.107018E+12 | 0.792029E+11 | 0.00 | 1.00 | 01-JUL-21:10 | 0.00 | 01-JUL-00:05 | 229515.29 | 07-JUL-20:10 | 148309.68 | 13-JUL-20:08 | 102126.78 | 07-JUL-20:10 | 58458.03 | 30-JUL-18:08 | 0.00 | 01-JUL-00:05 |
August | 0.213789E+12 | 0.557789E+11 | 640.29 | 0.111228E+12 | 0.102561E+12 | 0.00 | 1.00 | 01-AUG-20:08 | 0.00 | 01-AUG-00:33 | 231957.99 | 14-AUG-20:08 | 134709.54 | 23-AUG-20:10 | 109124.35 | 14-AUG-20:08 | 58421.73 | 27-AUG-18:08 | 0.00 | 01-AUG-00:05 |
September | 0.201667E+12 | 0.529991E+11 | 626.65 | 0.107671E+12 | 0.939958E+11 | 0.00 | 1.00 | 01-SEP-20:08 | 0.00 | 01-SEP-00:33 | 231474.76 | 18-SEP-20:10 | 133691.32 | 29-SEP-20:08 | 109358.14 | 18-SEP-20:10 | 58464.31 | 13-SEP-20:08 | 0.00 | 01-SEP-00:05 |
October | 0.187631E+12 | 0.491637E+11 | 628.49 | 0.993483E+11 | 0.882827E+11 | 0.00 | 1.00 | 01-OCT-18:10 | 0.00 | 01-OCT-00:12 | 231571.41 | 14-OCT-21:10 | 136544.13 | 08-OCT-18:08 | 109055.07 | 14-OCT-21:10 | 57183.69 | 08-OCT-18:08 | 0.00 | 01-OCT-00:10 |
November | 0.172027E+12 | 0.456379E+11 | 602.60 | 0.966577E+11 | 0.753694E+11 | 0.00 | 1.00 | 01-NOV-20:10 | 0.00 | 01-NOV-00:33 | 230263.29 | 12-NOV-19:10 | 139580.44 | 24-NOV-21:10 | 107384.17 | 11-NOV-19:10 | 57620.81 | 19-NOV-19:08 | 0.00 | 01-NOV-00:05 |
December | 0.161561E+12 | 0.436036E+11 | 611.99 | 0.974861E+11 | 0.640746E+11 | 0.00 | 1.00 | 01-DEC-21:08 | 0.00 | 01-DEC-00:13 | 231486.72 | 09-DEC-22:10 | 157034.87 | 20-DEC-21:10 | 109407.16 | 09-DEC-22:10 | 57161.48 | 10-DEC-19:08 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.230782E+13 | 0.617658E+12 | 7512.81 | 0.131547E+13 | 0.992346E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.156294E+12 | 0.430456E+11 | 572.48 | 0.966577E+11 | 0.568038E+11 | 0.00 | 1.00 | 0.00 | 226905.77 | 133691.32 | 92485.27 | 57161.48 | 0.00 | |||||||
Maximum of Months | 0.232288E+12 | 0.616614E+11 | 652.40 | 0.125033E+12 | 0.107255E+12 | 0.00 | 1.00 | 0.00 | 233830.25 | 158197.91 | 116573.58 | 60516.56 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.319372E+11 | 0.752129E+10 | 665.29 | 0.242972E+11 | 0.764000E+10 | 0.00 | 1.00 | 02-JAN-21:08 | 0.00 | 01-JAN-00:03 | 29528.89 | 09-JAN-21:06 | 22905.29 | 15-JAN-19:06 | 9644.81 | 09-JAN-21:06 | 6776.47 | 08-JAN-19:06 | 0.00 | 01-JAN-00:03 |
February | 0.300403E+11 | 0.717437E+10 | 604.88 | 0.227991E+11 | 0.724119E+10 | 0.00 | 1.00 | 01-FEB-21:06 | 0.00 | 01-FEB-00:12 | 29369.65 | 11-FEB-22:08 | 23174.95 | 24-FEB-21:05 | 9019.28 | 14-FEB-21:06 | 6835.34 | 26-FEB-19:05 | 0.00 | 01-FEB-00:10 |
March | 0.330909E+11 | 0.793811E+10 | 670.25 | 0.243553E+11 | 0.873556E+10 | 0.00 | 1.00 | 01-MAR-21:06 | 0.00 | 01-MAR-00:12 | 29479.99 | 14-MAR-20:06 | 22092.11 | 02-MAR-21:06 | 9269.30 | 14-MAR-20:06 | 6894.13 | 26-MAR-18:05 | 0.00 | 01-MAR-00:10 |
April | 0.328989E+11 | 0.785137E+10 | 645.34 | 0.225045E+11 | 0.103944E+11 | 0.00 | 1.00 | 01-APR-21:06 | 0.00 | 01-APR-00:33 | 29960.12 | 20-APR-20:10 | 21343.24 | 26-APR-20:06 | 11501.56 | 20-APR-20:10 | 7140.01 | 30-APR-18:43 | 0.00 | 01-APR-00:03 |
May | 0.356434E+11 | 0.843585E+10 | 664.32 | 0.229537E+11 | 0.126897E+11 | 0.00 | 1.00 | 01-MAY-20:06 | 0.00 | 01-MAY-00:33 | 30380.33 | 30-MAY-03:23 | 20084.62 | 05-MAY-20:05 | 12861.97 | 30-MAY-03:23 | 7177.55 | 29-MAY-18:06 | 0.00 | 01-MAY-00:03 |
June | 0.351558E+11 | 0.831226E+10 | 644.09 | 0.226502E+11 | 0.125057E+11 | 0.00 | 1.00 | 01-JUN-01:23 | 0.00 | 01-JUN-00:33 | 30258.78 | 06-JUN-03:23 | 20516.84 | 07-JUN-20:42 | 12420.68 | 06-JUN-03:23 | 7095.78 | 11-JUN-18:42 | 0.00 | 01-JUN-00:03 |
July | 0.296800E+11 | 0.691723E+10 | 660.28 | 0.204400E+11 | 0.923999E+10 | 0.00 | 1.00 | 01-JUL-21:08 | 0.00 | 01-JUL-00:10 | 29834.31 | 07-JUL-20:08 | 21332.23 | 13-JUL-20:06 | 10769.90 | 07-JUL-20:08 | 6916.51 | 30-JUL-18:06 | 0.00 | 01-JUL-00:05 |
August | 0.324456E+11 | 0.750017E+10 | 660.07 | 0.205006E+11 | 0.119451E+11 | 0.00 | 1.00 | 01-AUG-20:06 | 0.00 | 01-AUG-00:33 | 30346.93 | 11-AUG-02:43 | 20060.36 | 23-AUG-20:08 | 12732.06 | 11-AUG-02:43 | 6928.13 | 27-AUG-18:06 | 0.00 | 01-AUG-00:05 |
September | 0.319975E+11 | 0.742953E+10 | 643.31 | 0.209004E+11 | 0.110971E+11 | 0.00 | 1.00 | 01-SEP-20:06 | 0.00 | 01-SEP-00:33 | 29982.99 | 18-SEP-20:08 | 20339.32 | 29-SEP-20:06 | 11355.63 | 18-SEP-20:08 | 6933.22 | 04-SEP-18:06 | 0.00 | 01-SEP-00:05 |
October | 0.317692E+11 | 0.732212E+10 | 660.14 | 0.209706E+11 | 0.107986E+11 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:12 | 29912.53 | 01-OCT-07:03 | 20610.34 | 08-OCT-18:06 | 11079.01 | 01-OCT-07:03 | 6766.60 | 15-OCT-18:06 | 0.00 | 01-OCT-00:10 |
November | 0.317067E+11 | 0.735195E+10 | 641.87 | 0.221956E+11 | 0.951118E+10 | 0.00 | 1.00 | 01-NOV-20:08 | 0.00 | 01-NOV-00:33 | 29787.73 | 11-NOV-19:08 | 21422.86 | 24-NOV-21:08 | 10637.53 | 11-NOV-19:08 | 6808.53 | 19-NOV-19:05 | 0.00 | 01-NOV-00:05 |
December | 0.321121E+11 | 0.748144E+10 | 665.14 | 0.237662E+11 | 0.834592E+10 | 0.00 | 1.00 | 01-DEC-21:06 | 0.00 | 01-DEC-00:13 | 29895.93 | 09-DEC-22:08 | 23095.50 | 20-DEC-21:06 | 10948.33 | 09-DEC-22:08 | 6759.43 | 10-DEC-19:06 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.388478E+12 | 0.912357E+11 | 7824.97 | 0.268333E+12 | 0.120144E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.296800E+11 | 0.691723E+10 | 604.88 | 0.204400E+11 | 0.724119E+10 | 0.00 | 1.00 | 0.00 | 29369.65 | 20060.36 | 9019.28 | 6759.43 | 0.00 | |||||||
Maximum of Months | 0.356434E+11 | 0.843585E+10 | 670.25 | 0.243553E+11 | 0.126897E+11 | 0.00 | 1.00 | 0.00 | 30380.33 | 23174.95 | 12861.97 | 7177.55 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.282781E+11 | 0.665324E+10 | 665.08 | 0.208542E+11 | 0.742392E+10 | 0.00 | 1.00 | 02-JAN-21:08 | 0.00 | 01-JAN-00:03 | 26719.51 | 09-JAN-21:06 | 20021.10 | 15-JAN-19:06 | 9722.23 | 09-JAN-21:06 | 6094.24 | 08-JAN-19:06 | 0.00 | 01-JAN-00:03 |
February | 0.267616E+11 | 0.638085E+10 | 604.88 | 0.196972E+11 | 0.706442E+10 | 0.00 | 1.00 | 01-FEB-21:06 | 0.00 | 01-FEB-00:12 | 26542.26 | 14-FEB-21:06 | 20202.69 | 20-FEB-19:42 | 9086.27 | 14-FEB-21:06 | 6145.93 | 26-FEB-19:05 | 0.00 | 01-FEB-00:10 |
March | 0.291969E+11 | 0.699453E+10 | 669.83 | 0.207673E+11 | 0.842957E+10 | 0.00 | 1.00 | 01-MAR-21:06 | 0.00 | 01-MAR-00:12 | 26632.53 | 14-MAR-20:06 | 19143.78 | 13-MAR-20:05 | 9283.44 | 14-MAR-20:06 | 6198.45 | 26-MAR-18:05 | 0.00 | 01-MAR-00:10 |
April | 0.291757E+11 | 0.693202E+10 | 644.26 | 0.191526E+11 | 0.100232E+11 | 0.00 | 1.00 | 01-APR-21:06 | 0.00 | 01-APR-00:33 | 27161.44 | 20-APR-20:10 | 18389.36 | 26-APR-20:06 | 11494.91 | 20-APR-20:10 | 6502.75 | 30-APR-18:43 | 0.00 | 01-APR-00:03 |
May | 0.318636E+11 | 0.749567E+10 | 663.55 | 0.195834E+11 | 0.122802E+11 | 0.00 | 1.00 | 01-MAY-20:06 | 0.00 | 01-MAY-00:33 | 27427.63 | 30-MAY-03:23 | 17490.11 | 29-MAY-18:06 | 12391.21 | 28-MAY-18:10 | 6451.31 | 29-MAY-18:06 | 0.00 | 01-MAY-00:03 |
June | 0.315446E+11 | 0.741211E+10 | 643.59 | 0.193999E+11 | 0.121447E+11 | 0.00 | 1.00 | 01-JUN-20:08 | 0.00 | 01-JUN-00:33 | 27356.59 | 28-JUN-20:08 | 17553.65 | 07-JUN-20:42 | 12331.03 | 28-JUN-20:08 | 6375.47 | 11-JUN-18:42 | 0.00 | 01-JUN-00:03 |
July | 0.259505E+11 | 0.603798E+10 | 659.82 | 0.171013E+11 | 0.884921E+10 | 0.00 | 1.00 | 01-JUL-21:08 | 0.00 | 01-JUL-00:10 | 27026.56 | 07-JUL-20:08 | 18588.47 | 09-JUL-18:06 | 10926.01 | 07-JUL-20:08 | 6218.73 | 30-JUL-18:06 | 0.00 | 01-JUL-00:05 |
August | 0.285100E+11 | 0.656249E+10 | 655.92 | 0.170943E+11 | 0.114157E+11 | 0.00 | 1.00 | 01-AUG-20:06 | 0.00 | 01-AUG-00:33 | 27386.46 | 11-AUG-02:43 | 17039.56 | 23-AUG-20:08 | 12229.81 | 11-AUG-02:43 | 6228.09 | 27-AUG-18:06 | 0.00 | 01-AUG-00:05 |
September | 0.283270E+11 | 0.654860E+10 | 641.10 | 0.176410E+11 | 0.106860E+11 | 0.00 | 1.00 | 01-SEP-20:06 | 0.00 | 01-SEP-00:33 | 27181.06 | 18-SEP-20:08 | 17430.02 | 29-SEP-20:06 | 11513.17 | 18-SEP-20:08 | 6232.60 | 13-SEP-20:06 | 0.00 | 01-SEP-00:05 |
October | 0.278434E+11 | 0.639726E+10 | 655.61 | 0.175216E+11 | 0.103218E+11 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:12 | 27093.88 | 25-OCT-20:08 | 17946.42 | 08-OCT-18:06 | 11165.96 | 25-OCT-20:08 | 6085.74 | 15-OCT-18:06 | 0.00 | 01-OCT-00:10 |
November | 0.281043E+11 | 0.649771E+10 | 640.62 | 0.188962E+11 | 0.920808E+10 | 0.00 | 1.00 | 01-NOV-20:08 | 0.00 | 01-NOV-00:33 | 26937.58 | 30-NOV-21:08 | 18400.97 | 24-NOV-21:08 | 10509.85 | 30-NOV-21:08 | 6124.28 | 19-NOV-19:05 | 0.00 | 01-NOV-00:05 |
December | 0.284321E+11 | 0.661558E+10 | 664.35 | 0.203342E+11 | 0.809789E+10 | 0.00 | 1.00 | 01-DEC-21:06 | 0.00 | 01-DEC-00:13 | 27008.91 | 09-DEC-22:08 | 20043.17 | 20-DEC-21:06 | 10760.07 | 09-DEC-22:08 | 6078.19 | 10-DEC-19:06 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.343988E+12 | 0.805280E+11 | 7808.61 | 0.228043E+12 | 0.115945E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.259505E+11 | 0.603798E+10 | 604.88 | 0.170943E+11 | 0.706442E+10 | 0.00 | 1.00 | 0.00 | 26542.26 | 17039.56 | 9086.27 | 6078.19 | 0.00 | |||||||
Maximum of Months | 0.318636E+11 | 0.749567E+10 | 669.83 | 0.208542E+11 | 0.122802E+11 | 0.00 | 1.00 | 0.00 | 27427.63 | 20202.69 | 12391.21 | 6502.75 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.09 | 23.89 | 26.20 | 107.47 | 20.33 | 0.00 | 0.00 | 744.00 |
February | 57.88 | 29.98 | 27.90 | 125.88 | 20.47 | 0.00 | 0.00 | 672.00 |
March | 66.97 | 39.14 | 27.83 | 145.70 | 15.30 | 0.00 | 0.00 | 744.00 |
April | 67.82 | 37.88 | 29.95 | 148.76 | 9.06 | 0.00 | 0.00 | 720.00 |
May | 56.80 | 24.58 | 32.22 | 127.71 | 6.95 | 0.00 | 0.00 | 744.00 |
June | 61.37 | 30.24 | 31.13 | 137.26 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 51.71 | 17.04 | 34.66 | 114.48 | 10.58 | 0.00 | 0.00 | 744.00 |
August | 57.05 | 24.37 | 32.68 | 118.54 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 52.72 | 20.35 | 32.37 | 116.24 | 9.04 | 0.00 | 0.00 | 720.00 |
October | 48.22 | 16.99 | 31.23 | 100.69 | 10.13 | 0.00 | 0.00 | 744.00 |
November | 46.14 | 17.45 | 28.68 | 99.27 | 14.14 | 0.00 | 0.00 | 720.00 |
December | 46.53 | 20.84 | 25.69 | 99.90 | 21.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.23 | 25.18 | 30.06 | 120.05 | 12.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.14 | 16.99 | 25.69 | 99.27 | 6.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.82 | 39.14 | 34.66 | 148.76 | 21.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 558.99 | 239.90 | 319.10 | 1846.78 | 208.80 | 0.00 | 0.00 | 744.00 |
February | 487.97 | 174.62 | 313.35 | 1693.40 | 164.93 | 0.00 | 0.00 | 672.00 |
March | 336.53 | 61.84 | 274.68 | 1233.84 | 111.58 | 0.00 | 0.00 | 744.00 |
April | 236.68 | 0.23 | 236.45 | 992.13 | 33.77 | 0.00 | 0.00 | 720.00 |
May | 236.72 | 0.00 | 236.72 | 1029.42 | 46.36 | 0.00 | 0.00 | 744.00 |
June | 235.87 | 0.00 | 235.87 | 1016.93 | 48.68 | 0.00 | 0.00 | 720.00 |
July | 242.98 | 0.00 | 242.98 | 919.63 | 96.52 | 0.00 | 0.00 | 744.00 |
August | 236.83 | 0.65 | 236.18 | 841.10 | 74.81 | 0.00 | 0.00 | 744.00 |
September | 266.00 | 12.68 | 253.32 | 990.13 | 79.50 | 0.00 | 0.00 | 720.00 |
October | 355.12 | 67.14 | 287.98 | 1152.24 | 108.52 | 0.00 | 0.00 | 744.00 |
November | 456.48 | 146.90 | 309.58 | 1516.95 | 143.09 | 0.00 | 0.00 | 720.00 |
December | 554.24 | 239.82 | 314.42 | 1818.98 | 236.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 349.80 | 78.28 | 271.52 | 1252.06 | 112.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 235.87 | 0.00 | 235.87 | 841.10 | 33.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 558.99 | 239.90 | 319.10 | 1846.78 | 236.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 558.99 | 239.90 | 319.10 | 1848.63 | 199.68 | 0.00 | 0.00 | 744.00 |
February | 487.97 | 174.62 | 313.35 | 1695.06 | 155.75 | 0.00 | 0.00 | 672.00 |
March | 336.53 | 61.84 | 274.68 | 1236.84 | 100.90 | 0.00 | 0.00 | 744.00 |
April | 236.68 | 0.23 | 236.45 | 998.48 | 27.76 | 0.00 | 0.00 | 720.00 |
May | 236.72 | 0.00 | 236.72 | 1037.09 | 41.87 | 0.00 | 0.00 | 744.00 |
June | 235.87 | 0.00 | 235.87 | 1022.68 | 43.92 | 0.00 | 0.00 | 720.00 |
July | 242.98 | 0.00 | 242.98 | 922.92 | 89.67 | 0.00 | 0.00 | 744.00 |
August | 236.83 | 0.65 | 236.18 | 846.02 | 67.19 | 0.00 | 0.00 | 744.00 |
September | 266.00 | 12.68 | 253.32 | 993.65 | 72.74 | 0.00 | 0.00 | 720.00 |
October | 355.12 | 67.14 | 287.98 | 1157.36 | 99.64 | 0.00 | 0.00 | 744.00 |
November | 456.48 | 146.90 | 309.58 | 1519.69 | 135.49 | 0.00 | 0.00 | 720.00 |
December | 554.24 | 239.82 | 314.42 | 1820.56 | 227.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 349.80 | 78.28 | 271.52 | 1256.02 | 105.15 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 235.87 | 0.00 | 235.87 | 846.02 | 27.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 558.99 | 239.90 | 319.10 | 1848.63 | 227.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.02 | 49.36 | 65.66 | 318.07 | 72.32 | 0.00 | 0.00 | 744.00 |
February | 100.41 | 35.93 | 64.48 | 281.49 | 65.11 | 0.00 | 0.00 | 672.00 |
March | 69.25 | 12.73 | 56.52 | 189.31 | 51.85 | 0.00 | 0.00 | 744.00 |
April | 48.70 | 0.05 | 48.65 | 138.85 | 29.51 | 8.67 | 0.00 | 720.00 |
May | 48.71 | 0.00 | 48.71 | 141.86 | 29.49 | 158.17 | 0.00 | 744.00 |
June | 48.53 | 0.00 | 48.53 | 140.87 | 31.86 | 66.00 | 0.00 | 720.00 |
July | 50.00 | 0.00 | 50.00 | 140.56 | 38.00 | 9.17 | 0.00 | 744.00 |
August | 48.73 | 0.13 | 48.60 | 124.03 | 33.76 | 36.83 | 0.00 | 744.00 |
September | 54.73 | 2.61 | 52.12 | 151.52 | 36.40 | 45.17 | 0.00 | 720.00 |
October | 73.07 | 13.82 | 59.26 | 188.15 | 43.45 | 50.67 | 0.00 | 744.00 |
November | 93.93 | 30.23 | 63.70 | 257.48 | 53.97 | 14.33 | 0.00 | 720.00 |
December | 114.04 | 49.35 | 64.70 | 315.17 | 76.16 | 25.17 | 0.00 | 744.00 |
Annual Sum or Average | 71.98 | 16.11 | 55.87 | 198.56 | 46.77 | 414.17 | 0.00 | 8760.00 |
Minimum of Months | 48.53 | 0.00 | 48.53 | 124.03 | 29.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 115.02 | 49.36 | 65.66 | 318.07 | 76.16 | 158.17 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134170E+09 | 63992210.97 | 70177398.51 | 0.287850E+09 | 54456894.45 |
February | 0.140028E+09 | 72526669.00 | 67501367.59 | 0.304531E+09 | 49521806.72 |
March | 0.179373E+09 | 0.104826E+09 | 74546376.60 | 0.390233E+09 | 40968654.78 |
April | 0.175796E+09 | 98174311.87 | 77621681.95 | 0.385592E+09 | 23492546.70 |
May | 0.152130E+09 | 65828454.99 | 86301765.05 | 0.342065E+09 | 18608856.58 |
June | 0.159062E+09 | 78373658.71 | 80688764.65 | 0.355782E+09 | 17361095.35 |
July | 0.138488E+09 | 45648800.86 | 92839132.30 | 0.306631E+09 | 28337033.69 |
August | 0.152815E+09 | 65276098.40 | 87539292.89 | 0.317500E+09 | 26261235.15 |
September | 0.136659E+09 | 52753441.14 | 83906005.98 | 0.301301E+09 | 23422143.85 |
October | 0.129140E+09 | 45493208.79 | 83647222.77 | 0.269688E+09 | 27129562.12 |
November | 0.119586E+09 | 45236056.09 | 74349480.16 | 0.257313E+09 | 36643538.66 |
December | 0.124631E+09 | 55823941.69 | 68807422.31 | 0.267563E+09 | 57807974.14 |
Annual Sum or Average | 0.174188E+10 | 0.793953E+09 | 0.947926E+09 | 0.378605E+10 | 0.404011E+09 |
Minimum of Months | 0.119586E+09 | 45236056.09 | 67501367.59 | 0.257313E+09 | 17361095.35 |
Maximum of Months | 0.179373E+09 | 0.104826E+09 | 92839132.30 | 0.390233E+09 | 57807974.14 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149720E+10 | 0.642535E+09 | 0.854670E+09 | 0.494642E+10 | 0.559262E+09 |
February | 0.118050E+10 | 0.422442E+09 | 0.758061E+09 | 0.409667E+10 | 0.398994E+09 |
March | 0.901354E+09 | 0.165646E+09 | 0.735708E+09 | 0.330472E+10 | 0.298856E+09 |
April | 0.613479E+09 | 594534.63 | 0.612885E+09 | 0.257161E+10 | 87519081.77 |
May | 0.634031E+09 | 0.00 | 0.634031E+09 | 0.275719E+10 | 0.124169E+09 |
June | 0.611370E+09 | 0.00 | 0.611370E+09 | 0.263589E+10 | 0.126183E+09 |
July | 0.650796E+09 | 0.00 | 0.650796E+09 | 0.246314E+10 | 0.258532E+09 |
August | 0.634315E+09 | 1739083.47 | 0.632576E+09 | 0.225279E+10 | 0.200358E+09 |
September | 0.689465E+09 | 32868673.60 | 0.656596E+09 | 0.256642E+10 | 0.206074E+09 |
October | 0.951150E+09 | 0.179834E+09 | 0.771316E+09 | 0.308616E+10 | 0.290651E+09 |
November | 0.118320E+10 | 0.380765E+09 | 0.802432E+09 | 0.393194E+10 | 0.370890E+09 |
December | 0.148449E+10 | 0.642346E+09 | 0.842143E+09 | 0.487195E+10 | 0.632514E+09 |
Annual Sum or Average | 0.110314E+11 | 0.246877E+10 | 0.856258E+10 | 0.394849E+11 | 0.355400E+10 |
Minimum of Months | 0.611370E+09 | 0.00 | 0.611370E+09 | 0.225279E+10 | 87519081.77 |
Maximum of Months | 0.149720E+10 | 0.642535E+09 | 0.854670E+09 | 0.494642E+10 | 0.632514E+09 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149720E+10 | 0.642535E+09 | 0.854670E+09 | 0.495137E+10 | 0.534821E+09 |
February | 0.118050E+10 | 0.422442E+09 | 0.758061E+09 | 0.410069E+10 | 0.376778E+09 |
March | 0.901354E+09 | 0.165646E+09 | 0.735708E+09 | 0.331276E+10 | 0.270254E+09 |
April | 0.613479E+09 | 594534.63 | 0.612885E+09 | 0.258806E+10 | 71958933.78 |
May | 0.634031E+09 | 0.00 | 0.634031E+09 | 0.277774E+10 | 0.112136E+09 |
June | 0.611370E+09 | 0.00 | 0.611370E+09 | 0.265078E+10 | 0.113838E+09 |
July | 0.650796E+09 | 0.00 | 0.650796E+09 | 0.247194E+10 | 0.240168E+09 |
August | 0.634315E+09 | 1739083.47 | 0.632576E+09 | 0.226598E+10 | 0.179953E+09 |
September | 0.689465E+09 | 32868673.60 | 0.656596E+09 | 0.257555E+10 | 0.188552E+09 |
October | 0.951150E+09 | 0.179834E+09 | 0.771316E+09 | 0.309986E+10 | 0.266884E+09 |
November | 0.118320E+10 | 0.380765E+09 | 0.802432E+09 | 0.393903E+10 | 0.351202E+09 |
December | 0.148449E+10 | 0.642346E+09 | 0.842143E+09 | 0.487619E+10 | 0.609417E+09 |
Annual Sum or Average | 0.110314E+11 | 0.246877E+10 | 0.856258E+10 | 0.396100E+11 | 0.331596E+10 |
Minimum of Months | 0.611370E+09 | 0.00 | 0.611370E+09 | 0.226598E+10 | 71958933.78 |
Maximum of Months | 0.149720E+10 | 0.642535E+09 | 0.854670E+09 | 0.495137E+10 | 0.609417E+09 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308072E+09 | 0.132211E+09 | 0.175861E+09 | 0.851925E+09 | 0.193715E+09 |
February | 0.242906E+09 | 86923523.14 | 0.155982E+09 | 0.680988E+09 | 0.157513E+09 |
March | 0.185467E+09 | 34084002.41 | 0.151383E+09 | 0.507059E+09 | 0.138884E+09 |
April | 0.126232E+09 | 122334.16 | 0.126110E+09 | 0.359901E+09 | 76478927.34 |
May | 0.130461E+09 | 0.00 | 0.130461E+09 | 0.379952E+09 | 78992354.22 |
June | 0.125798E+09 | 0.00 | 0.125798E+09 | 0.365146E+09 | 82593318.28 |
July | 0.133911E+09 | 0.00 | 0.133911E+09 | 0.376464E+09 | 0.101787E+09 |
August | 0.130520E+09 | 357841.75 | 0.130162E+09 | 0.332215E+09 | 90418640.48 |
September | 0.141867E+09 | 6763208.20 | 0.135104E+09 | 0.392736E+09 | 94355774.61 |
October | 0.195713E+09 | 37003512.75 | 0.158710E+09 | 0.503954E+09 | 0.116365E+09 |
November | 0.243460E+09 | 78347983.52 | 0.165112E+09 | 0.667399E+09 | 0.139888E+09 |
December | 0.305455E+09 | 0.132172E+09 | 0.173283E+09 | 0.844147E+09 | 0.203978E+09 |
Annual Sum or Average | 0.226986E+10 | 0.507985E+09 | 0.176188E+10 | 0.626189E+10 | 0.147497E+10 |
Minimum of Months | 0.125798E+09 | 0.00 | 0.125798E+09 | 0.332215E+09 | 76478927.34 |
Maximum of Months | 0.308072E+09 | 0.132211E+09 | 0.175861E+09 | 0.851925E+09 | 0.203978E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1719.53 | 325.31 | 801.49 | 382.27 | 419.22 | 0.00 | 0.00 |
February | 2014.09 | 327.53 | 926.11 | 479.67 | 446.44 | 0.00 | 0.00 |
March | 2331.14 | 244.74 | 1071.52 | 626.20 | 445.32 | 0.00 | 0.00 |
April | 2380.20 | 145.02 | 1085.16 | 606.01 | 479.15 | 0.00 | 0.00 |
May | 2043.40 | 111.16 | 908.78 | 393.24 | 515.54 | 0.00 | 0.00 |
June | 2196.19 | 107.17 | 981.87 | 483.79 | 498.08 | 0.00 | 0.00 |
July | 1831.73 | 169.28 | 827.29 | 272.69 | 554.59 | 0.00 | 0.00 |
August | 1896.65 | 156.88 | 912.88 | 389.94 | 522.93 | 0.00 | 0.00 |
September | 1859.88 | 144.58 | 843.58 | 325.64 | 517.94 | 0.00 | 0.00 |
October | 1611.04 | 162.06 | 771.45 | 271.76 | 499.68 | 0.00 | 0.00 |
November | 1588.35 | 226.19 | 738.18 | 279.23 | 458.95 | 0.00 | 0.00 |
December | 1598.35 | 345.33 | 744.51 | 333.48 | 411.04 | 0.00 | 0.00 |
Annual Sum or Average | 1920.88 | 204.98 | 883.75 | 402.82 | 480.94 | 0.00 | 0.00 |
Minimum of Months | 1588.35 | 107.17 | 738.18 | 271.76 | 411.04 | 0.00 | 0.00 |
Maximum of Months | 2380.20 | 345.33 | 1085.16 | 626.20 | 554.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1846.78 | 208.80 | 558.99 | 239.90 | 319.10 | 0.00 | 0.00 |
February | 1693.40 | 164.93 | 487.97 | 174.62 | 313.35 | 0.00 | 0.00 |
March | 1233.84 | 111.58 | 336.53 | 61.84 | 274.68 | 0.00 | 0.00 |
April | 992.13 | 33.77 | 236.68 | 0.23 | 236.45 | 0.00 | 0.00 |
May | 1029.42 | 46.36 | 236.72 | 0.00 | 236.72 | 0.00 | 0.00 |
June | 1016.93 | 48.68 | 235.87 | 0.00 | 235.87 | 0.00 | 0.00 |
July | 919.63 | 96.52 | 242.98 | 0.00 | 242.98 | 0.00 | 0.00 |
August | 841.10 | 74.81 | 236.83 | 0.65 | 236.18 | 0.00 | 0.00 |
September | 990.13 | 79.50 | 266.00 | 12.68 | 253.32 | 0.00 | 0.00 |
October | 1152.24 | 108.52 | 355.12 | 67.14 | 287.98 | 0.00 | 0.00 |
November | 1516.95 | 143.09 | 456.48 | 146.90 | 309.58 | 0.00 | 0.00 |
December | 1818.98 | 236.15 | 554.24 | 239.82 | 314.42 | 0.00 | 0.00 |
Annual Sum or Average | 1252.06 | 112.70 | 349.80 | 78.28 | 271.52 | 0.00 | 0.00 |
Minimum of Months | 841.10 | 33.77 | 235.87 | 0.00 | 235.87 | 0.00 | 0.00 |
Maximum of Months | 1846.78 | 236.15 | 558.99 | 239.90 | 319.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1848.63 | 199.68 | 558.99 | 239.90 | 319.10 | 0.00 | 0.00 |
February | 1695.06 | 155.75 | 487.97 | 174.62 | 313.35 | 0.00 | 0.00 |
March | 1236.84 | 100.90 | 336.53 | 61.84 | 274.68 | 0.00 | 0.00 |
April | 998.48 | 27.76 | 236.68 | 0.23 | 236.45 | 0.00 | 0.00 |
May | 1037.09 | 41.87 | 236.72 | 0.00 | 236.72 | 0.00 | 0.00 |
June | 1022.68 | 43.92 | 235.87 | 0.00 | 235.87 | 0.00 | 0.00 |
July | 922.92 | 89.67 | 242.98 | 0.00 | 242.98 | 0.00 | 0.00 |
August | 846.02 | 67.19 | 236.83 | 0.65 | 236.18 | 0.00 | 0.00 |
September | 993.65 | 72.74 | 266.00 | 12.68 | 253.32 | 0.00 | 0.00 |
October | 1157.36 | 99.64 | 355.12 | 67.14 | 287.98 | 0.00 | 0.00 |
November | 1519.69 | 135.49 | 456.48 | 146.90 | 309.58 | 0.00 | 0.00 |
December | 1820.56 | 227.53 | 554.24 | 239.82 | 314.42 | 0.00 | 0.00 |
Annual Sum or Average | 1256.02 | 105.15 | 349.80 | 78.28 | 271.52 | 0.00 | 0.00 |
Minimum of Months | 846.02 | 27.76 | 235.87 | 0.00 | 235.87 | 0.00 | 0.00 |
Maximum of Months | 1848.63 | 227.53 | 558.99 | 239.90 | 319.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 318.07 | 72.32 | 115.02 | 49.36 | 65.66 | 0.00 | 0.00 |
February | 281.49 | 65.11 | 100.41 | 35.93 | 64.48 | 0.00 | 0.00 |
March | 189.31 | 51.85 | 69.25 | 12.73 | 56.52 | 0.00 | 0.00 |
April | 138.85 | 29.51 | 48.70 | 0.05 | 48.65 | 0.00 | 0.00 |
May | 141.86 | 29.49 | 48.71 | 0.00 | 48.71 | 0.00 | 0.00 |
June | 140.87 | 31.86 | 48.53 | 0.00 | 48.53 | 0.00 | 0.00 |
July | 140.56 | 38.00 | 50.00 | 0.00 | 50.00 | 0.00 | 0.00 |
August | 124.03 | 33.76 | 48.73 | 0.13 | 48.60 | 0.00 | 0.00 |
September | 151.52 | 36.40 | 54.73 | 2.61 | 52.12 | 0.00 | 0.00 |
October | 188.15 | 43.45 | 73.07 | 13.82 | 59.26 | 0.00 | 0.00 |
November | 257.48 | 53.97 | 93.93 | 30.23 | 63.70 | 0.00 | 0.00 |
December | 315.17 | 76.16 | 114.04 | 49.35 | 64.70 | 0.00 | 0.00 |
Annual Sum or Average | 198.56 | 46.77 | 71.98 | 16.11 | 55.87 | 0.00 | 0.00 |
Minimum of Months | 124.03 | 29.49 | 48.53 | 0.00 | 48.53 | 0.00 | 0.00 |
Maximum of Months | 318.07 | 76.16 | 115.02 | 49.36 | 65.66 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.460559E+10 | 0.871310E+09 | 0.214671E+10 | 0.102388E+10 | 0.112284E+10 | 0.00 | 0.00 |
February | 0.487249E+10 | 0.792349E+09 | 0.224045E+10 | 0.116043E+10 | 0.108002E+10 | 0.00 | 0.00 |
March | 0.624373E+10 | 0.655498E+09 | 0.286996E+10 | 0.167722E+10 | 0.119274E+10 | 0.00 | 0.00 |
April | 0.616947E+10 | 0.375881E+09 | 0.281274E+10 | 0.157079E+10 | 0.124195E+10 | 0.00 | 0.00 |
May | 0.547304E+10 | 0.297742E+09 | 0.243408E+10 | 0.105326E+10 | 0.138083E+10 | 0.00 | 0.00 |
June | 0.569252E+10 | 0.277778E+09 | 0.254500E+10 | 0.125398E+10 | 0.129102E+10 | 0.00 | 0.00 |
July | 0.490609E+10 | 0.453393E+09 | 0.221581E+10 | 0.730381E+09 | 0.148543E+10 | 0.00 | 0.00 |
August | 0.508000E+10 | 0.420180E+09 | 0.244505E+10 | 0.104442E+10 | 0.140063E+10 | 0.00 | 0.00 |
September | 0.482082E+10 | 0.374754E+09 | 0.218655E+10 | 0.844055E+09 | 0.134250E+10 | 0.00 | 0.00 |
October | 0.431501E+10 | 0.434073E+09 | 0.206625E+10 | 0.727891E+09 | 0.133836E+10 | 0.00 | 0.00 |
November | 0.411701E+10 | 0.586297E+09 | 0.191337E+10 | 0.723777E+09 | 0.118959E+10 | 0.00 | 0.00 |
December | 0.428101E+10 | 0.924928E+09 | 0.199410E+10 | 0.893183E+09 | 0.110092E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.605768E+11 | 0.646418E+10 | 0.278701E+11 | 0.127032E+11 | 0.151668E+11 | 0.00 | 0.00 |
Minimum of Months | 0.411701E+10 | 0.277778E+09 | 0.191337E+10 | 0.723777E+09 | 0.108002E+10 | 0.00 | 0.00 |
Maximum of Months | 0.624373E+10 | 0.924928E+09 | 0.286996E+10 | 0.167722E+10 | 0.148543E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.494642E+10 | 0.559262E+09 | 0.149720E+10 | 0.642535E+09 | 0.854670E+09 | 0.00 | 0.00 |
February | 0.409667E+10 | 0.398994E+09 | 0.118050E+10 | 0.422442E+09 | 0.758061E+09 | 0.00 | 0.00 |
March | 0.330472E+10 | 0.298856E+09 | 0.901354E+09 | 0.165646E+09 | 0.735708E+09 | 0.00 | 0.00 |
April | 0.257161E+10 | 87519081.77 | 0.613479E+09 | 594534.63 | 0.612885E+09 | 0.00 | 0.00 |
May | 0.275719E+10 | 0.124169E+09 | 0.634031E+09 | 0.00 | 0.634031E+09 | 0.00 | 0.00 |
June | 0.263589E+10 | 0.126183E+09 | 0.611370E+09 | 0.00 | 0.611370E+09 | 0.00 | 0.00 |
July | 0.246314E+10 | 0.258532E+09 | 0.650796E+09 | 0.00 | 0.650796E+09 | 0.00 | 0.00 |
August | 0.225279E+10 | 0.200358E+09 | 0.634315E+09 | 1739083.47 | 0.632576E+09 | 0.00 | 0.00 |
September | 0.256642E+10 | 0.206074E+09 | 0.689465E+09 | 32868673.60 | 0.656596E+09 | 0.00 | 0.00 |
October | 0.308616E+10 | 0.290651E+09 | 0.951150E+09 | 0.179834E+09 | 0.771316E+09 | 0.00 | 0.00 |
November | 0.393194E+10 | 0.370890E+09 | 0.118320E+10 | 0.380765E+09 | 0.802432E+09 | 0.00 | 0.00 |
December | 0.487195E+10 | 0.632514E+09 | 0.148449E+10 | 0.642346E+09 | 0.842143E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.394849E+11 | 0.355400E+10 | 0.110314E+11 | 0.246877E+10 | 0.856258E+10 | 0.00 | 0.00 |
Minimum of Months | 0.225279E+10 | 87519081.77 | 0.611370E+09 | 0.00 | 0.611370E+09 | 0.00 | 0.00 |
Maximum of Months | 0.494642E+10 | 0.632514E+09 | 0.149720E+10 | 0.642535E+09 | 0.854670E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.495137E+10 | 0.534821E+09 | 0.149720E+10 | 0.642535E+09 | 0.854670E+09 | 0.00 | 0.00 |
February | 0.410069E+10 | 0.376778E+09 | 0.118050E+10 | 0.422442E+09 | 0.758061E+09 | 0.00 | 0.00 |
March | 0.331276E+10 | 0.270254E+09 | 0.901354E+09 | 0.165646E+09 | 0.735708E+09 | 0.00 | 0.00 |
April | 0.258806E+10 | 71958933.78 | 0.613479E+09 | 594534.63 | 0.612885E+09 | 0.00 | 0.00 |
May | 0.277774E+10 | 0.112136E+09 | 0.634031E+09 | 0.00 | 0.634031E+09 | 0.00 | 0.00 |
June | 0.265078E+10 | 0.113838E+09 | 0.611370E+09 | 0.00 | 0.611370E+09 | 0.00 | 0.00 |
July | 0.247194E+10 | 0.240168E+09 | 0.650796E+09 | 0.00 | 0.650796E+09 | 0.00 | 0.00 |
August | 0.226598E+10 | 0.179953E+09 | 0.634315E+09 | 1739083.47 | 0.632576E+09 | 0.00 | 0.00 |
September | 0.257555E+10 | 0.188552E+09 | 0.689465E+09 | 32868673.60 | 0.656596E+09 | 0.00 | 0.00 |
October | 0.309986E+10 | 0.266884E+09 | 0.951150E+09 | 0.179834E+09 | 0.771316E+09 | 0.00 | 0.00 |
November | 0.393903E+10 | 0.351202E+09 | 0.118320E+10 | 0.380765E+09 | 0.802432E+09 | 0.00 | 0.00 |
December | 0.487619E+10 | 0.609417E+09 | 0.148449E+10 | 0.642346E+09 | 0.842143E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.396100E+11 | 0.331596E+10 | 0.110314E+11 | 0.246877E+10 | 0.856258E+10 | 0.00 | 0.00 |
Minimum of Months | 0.226598E+10 | 71958933.78 | 0.611370E+09 | 0.00 | 0.611370E+09 | 0.00 | 0.00 |
Maximum of Months | 0.495137E+10 | 0.609417E+09 | 0.149720E+10 | 0.642535E+09 | 0.854670E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.851925E+09 | 0.193715E+09 | 0.308072E+09 | 0.132211E+09 | 0.175861E+09 | 0.00 | 0.00 |
February | 0.680988E+09 | 0.157513E+09 | 0.242906E+09 | 86923523.14 | 0.155982E+09 | 0.00 | 0.00 |
March | 0.507059E+09 | 0.138884E+09 | 0.185467E+09 | 34084002.41 | 0.151383E+09 | 0.00 | 0.00 |
April | 0.359901E+09 | 76478927.34 | 0.126232E+09 | 122334.16 | 0.126110E+09 | 0.00 | 0.00 |
May | 0.379952E+09 | 78992354.22 | 0.130461E+09 | 0.00 | 0.130461E+09 | 0.00 | 0.00 |
June | 0.365146E+09 | 82593318.28 | 0.125798E+09 | 0.00 | 0.125798E+09 | 0.00 | 0.00 |
July | 0.376464E+09 | 0.101787E+09 | 0.133911E+09 | 0.00 | 0.133911E+09 | 0.00 | 0.00 |
August | 0.332215E+09 | 90418640.48 | 0.130520E+09 | 357841.75 | 0.130162E+09 | 0.00 | 0.00 |
September | 0.392736E+09 | 94355774.61 | 0.141867E+09 | 6763208.20 | 0.135104E+09 | 0.00 | 0.00 |
October | 0.503954E+09 | 0.116365E+09 | 0.195713E+09 | 37003512.75 | 0.158710E+09 | 0.00 | 0.00 |
November | 0.667399E+09 | 0.139888E+09 | 0.243460E+09 | 78347983.52 | 0.165112E+09 | 0.00 | 0.00 |
December | 0.844147E+09 | 0.203978E+09 | 0.305455E+09 | 0.132172E+09 | 0.173283E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.626189E+10 | 0.147497E+10 | 0.226986E+10 | 0.507985E+09 | 0.176188E+10 | 0.00 | 0.00 |
Minimum of Months | 0.332215E+09 | 76478927.34 | 0.125798E+09 | 0.00 | 0.125798E+09 | 0.00 | 0.00 |
Maximum of Months | 0.851925E+09 | 0.203978E+09 | 0.308072E+09 | 0.132211E+09 | 0.175861E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.65 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.90 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.36 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 22.99 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.54 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.00 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.13 | 23.20 | 1.94 | 20.28 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.59 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 22.99 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.66 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.00 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 22.99 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.95 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.41 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.58 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.62 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.85 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.50 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.22 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.33 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.21 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.00 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.85 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.93 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.52 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.16 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.27 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.92 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.69 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.10 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.42 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.05 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.55 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.52 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.86 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.10 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.05 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.03 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.55 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.10 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.177297E+10 | -.138733E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385633226.4 | 58.99 | 0.00 | 0.00 |
February | 0.160350E+10 | -.125525E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -348244755.2 | 58.99 | 0.00 | 0.00 |
March | 0.178734E+10 | -.140191E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385437261.6 | 58.99 | 0.00 | 0.00 |
April | 0.167700E+10 | -.130410E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -372901578.7 | 58.99 | 0.00 | 0.00 |
May | 0.170564E+10 | -.132032E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385319590.7 | 58.99 | 0.00 | 0.00 |
June | 0.164794E+10 | -.127514E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -372801887.7 | 58.99 | 0.00 | 0.00 |
July | 0.165791E+10 | -.127253E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385381570.3 | 58.99 | 0.00 | 0.00 |
August | 0.170828E+10 | -.132282E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385456984.1 | 58.99 | 0.00 | 0.00 |
September | 0.165302E+10 | -.128000E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373017278.9 | 58.99 | 0.00 | 0.00 |
October | 0.171783E+10 | -.133233E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385497102.1 | 58.99 | 0.00 | 0.00 |
November | 0.168432E+10 | -.131117E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373147034.5 | 58.99 | 0.00 | 0.00 |
December | 0.176820E+10 | -.138260E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385608930.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.203839E+11 | -.158455E+11 | 8760.00 | -.453845E+10 | 58.99 | |||||
Minimum of Months | 0.160350E+10 | -.140191E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -385633226.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.178734E+10 | -.125525E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -348244755.2 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.77 | 0.50 | 02-JAN-11:30 | 455.04 | 8.39 | 0.00 | 92.00 | 382.74 | 6.90 | 0.00 | 56.83 |
February | 321.17 | 0.72 | 0.50 | 01-FEB-10:50 | 2577.24 | 8.97 | 0.00 | 127.17 | 2238.66 | 7.43 | 0.00 | 117.17 |
March | 361.17 | 0.77 | 0.50 | 01-MAR-09:50 | 382.69 | 9.87 | 0.00 | 51.00 | 316.18 | 8.20 | 0.00 | 35.17 |
April | 358.33 | 0.78 | 0.50 | 03-APR-09:00 | 359.24 | 11.42 | 0.00 | 45.17 | 297.48 | 9.66 | 0.00 | 17.50 |
May | 376.33 | 0.77 | 0.50 | 03-MAY-10:09 | 375.32 | 12.42 | 1.83 | 62.33 | 300.80 | 10.63 | 0.00 | 23.33 |
June | 370.50 | 0.75 | 0.50 | 02-JUN-09:00 | 660.50 | 15.88 | 53.17 | 119.17 | 305.44 | 11.23 | 0.00 | 23.33 |
July | 383.17 | 0.77 | 0.50 | 01-JUL-10:39 | 364.23 | 12.41 | 0.00 | 82.67 | 304.36 | 10.74 | 0.00 | 35.50 |
August | 369.33 | 0.76 | 0.50 | 02-AUG-10:30 | 377.17 | 12.08 | 0.00 | 83.17 | 314.50 | 10.39 | 0.00 | 29.33 |
September | 357.83 | 0.75 | 0.50 | 01-SEP-09:50 | 389.08 | 10.66 | 0.00 | 108.17 | 315.06 | 9.09 | 0.00 | 53.83 |
October | 356.83 | 0.73 | 0.50 | 01-OCT-09:00 | 673.42 | 9.93 | 0.00 | 169.33 | 418.51 | 8.34 | 0.00 | 78.33 |
November | 337.67 | 0.75 | 0.50 | 01-NOV-10:09 | 909.55 | 9.10 | 0.00 | 124.67 | 921.96 | 7.51 | 0.00 | 67.17 |
December | 349.33 | 0.78 | 0.50 | 01-DEC-10:20 | 346.33 | 8.26 | 0.00 | 61.67 | 291.21 | 6.76 | 0.00 | 39.83 |
Annual Sum or Average | 4292.33 | 0.76 | 635.25 | 10.85 | 55.00 | 1126.50 | 514.46 | 8.96 | 0.00 | 577.33 | ||
Minimum of Months | 321.17 | 0.72 | 0.50 | 346.33 | 8.26 | 0.00 | 45.17 | 291.21 | 6.76 | 0.00 | 17.50 | |
Maximum of Months | 383.17 | 0.78 | 0.50 | 2577.24 | 15.88 | 53.17 | 169.33 | 2238.66 | 11.23 | 0.00 | 117.17 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.375093E+11 | 0.274441E+11 | 52876.01 | 09-JAN-21:06 | 37275.00 | 0.00 |
February | 0.00 | 0.00 | 0.379126E+11 | 0.281197E+11 | 52605.59 | 15-FEB-21:06 | 37853.62 | 0.00 |
March | 0.00 | 0.00 | 0.469046E+11 | 0.343855E+11 | 52704.42 | 14-MAR-20:06 | 38605.93 | 0.00 |
April | 0.00 | 0.00 | 0.515702E+11 | 0.363743E+11 | 52623.73 | 10-APR-20:08 | 36741.84 | 0.00 |
May | 0.00 | 0.00 | 0.587193E+11 | 0.399569E+11 | 53434.27 | 20-MAY-03:23 | 36312.24 | 0.00 |
June | 0.00 | 0.00 | 0.620502E+11 | 0.429767E+11 | 53505.97 | 28-JUN-20:08 | 34710.00 | 0.00 |
July | 0.00 | 0.00 | 0.502477E+11 | 0.360718E+11 | 53135.81 | 07-JUL-20:08 | 37320.67 | 0.00 |
August | 0.00 | 0.00 | 0.513924E+11 | 0.338046E+11 | 53418.63 | 11-AUG-02:43 | 36471.72 | 0.00 |
September | 0.00 | 0.00 | 0.471329E+11 | 0.315031E+11 | 53324.01 | 19-SEP-20:08 | 36667.21 | 0.00 |
October | 0.00 | 0.00 | 0.426760E+11 | 0.280286E+11 | 53488.88 | 27-OCT-20:08 | 36068.95 | 0.00 |
November | 0.00 | 0.00 | 0.396719E+11 | 0.271161E+11 | 53521.60 | 11-NOV-19:10 | 36113.94 | 0.00 |
December | 0.00 | 0.00 | 0.371062E+11 | 0.263243E+11 | 53286.55 | 23-DEC-22:10 | 37370.04 | 0.00 |
Annual Sum or Average | 0.562893E+12 | 0.392106E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.371062E+11 | 0.263243E+11 | 52605.59 | 34710.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.620502E+11 | 0.429767E+11 | 53521.60 | 38605.93 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.158356E+12 | 0.100095E+12 | 228514.00 | 09-JAN-21:08 | 130610.94 | 0.00 |
February | 0.00 | 0.00 | 0.156294E+12 | 0.994900E+11 | 227387.16 | 15-FEB-21:08 | 133588.85 | 0.00 |
March | 0.00 | 0.00 | 0.193172E+12 | 0.122168E+12 | 226905.77 | 14-MAR-20:08 | 134420.50 | 0.00 |
April | 0.00 | 0.00 | 0.212961E+12 | 0.124362E+12 | 229415.81 | 10-APR-20:10 | 128992.70 | 0.00 |
May | 0.00 | 0.00 | 0.231854E+12 | 0.124917E+12 | 232856.68 | 16-MAY-20:08 | 119840.33 | 0.00 |
June | 0.00 | 0.00 | 0.232288E+12 | 0.125033E+12 | 233830.25 | 03-JUN-21:10 | 117256.67 | 0.00 |
July | 0.00 | 0.00 | 0.186221E+12 | 0.107018E+12 | 229515.29 | 07-JUL-20:10 | 127388.51 | 0.00 |
August | 0.00 | 0.00 | 0.213789E+12 | 0.111228E+12 | 231957.99 | 14-AUG-20:08 | 122833.63 | 0.00 |
September | 0.00 | 0.00 | 0.201667E+12 | 0.107671E+12 | 231474.76 | 18-SEP-20:10 | 122116.62 | 0.00 |
October | 0.00 | 0.00 | 0.187631E+12 | 0.993483E+11 | 231571.41 | 14-OCT-21:10 | 122516.34 | 0.00 |
November | 0.00 | 0.00 | 0.172027E+12 | 0.966577E+11 | 230263.29 | 12-NOV-19:10 | 124434.35 | 0.00 |
December | 0.00 | 0.00 | 0.161561E+12 | 0.974861E+11 | 231486.72 | 09-DEC-22:10 | 122079.56 | 0.00 |
Annual Sum or Average | 0.230782E+13 | 0.131547E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.156294E+12 | 0.966577E+11 | 226905.77 | 117256.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.232288E+12 | 0.125033E+12 | 233830.25 | 134420.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.319372E+11 | 0.242972E+11 | 29528.89 | 09-JAN-21:06 | 19884.08 | 0.00 |
February | 0.00 | 0.00 | 0.300403E+11 | 0.227991E+11 | 29369.65 | 11-FEB-22:08 | 20583.93 | 0.00 |
March | 0.00 | 0.00 | 0.330909E+11 | 0.243553E+11 | 29479.99 | 14-MAR-20:06 | 20210.70 | 0.00 |
April | 0.00 | 0.00 | 0.328989E+11 | 0.225045E+11 | 29960.12 | 20-APR-20:10 | 18458.56 | 0.00 |
May | 0.00 | 0.00 | 0.356434E+11 | 0.229537E+11 | 30380.33 | 30-MAY-03:23 | 17518.37 | 0.00 |
June | 0.00 | 0.00 | 0.351558E+11 | 0.226502E+11 | 30258.78 | 06-JUN-03:23 | 17838.10 | 0.00 |
July | 0.00 | 0.00 | 0.296800E+11 | 0.204400E+11 | 29834.31 | 07-JUL-20:08 | 19064.41 | 0.00 |
August | 0.00 | 0.00 | 0.324456E+11 | 0.205006E+11 | 30346.93 | 11-AUG-02:43 | 17614.88 | 0.00 |
September | 0.00 | 0.00 | 0.319975E+11 | 0.209004E+11 | 29982.99 | 18-SEP-20:08 | 18627.36 | 0.00 |
October | 0.00 | 0.00 | 0.317692E+11 | 0.209706E+11 | 29912.53 | 01-OCT-07:03 | 18833.51 | 0.00 |
November | 0.00 | 0.00 | 0.317067E+11 | 0.221956E+11 | 29787.73 | 11-NOV-19:08 | 19150.20 | 0.00 |
December | 0.00 | 0.00 | 0.321121E+11 | 0.237662E+11 | 29895.93 | 09-DEC-22:08 | 18947.61 | 0.00 |
Annual Sum or Average | 0.388478E+12 | 0.268333E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.296800E+11 | 0.204400E+11 | 29369.65 | 17518.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.356434E+11 | 0.243553E+11 | 30380.33 | 20583.93 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.282781E+11 | 0.208542E+11 | 26719.51 | 09-JAN-21:06 | 16997.28 | 0.00 |
February | 0.00 | 0.00 | 0.267616E+11 | 0.196972E+11 | 26542.26 | 14-FEB-21:06 | 17455.99 | 0.00 |
March | 0.00 | 0.00 | 0.291969E+11 | 0.207673E+11 | 26632.53 | 14-MAR-20:06 | 17349.09 | 0.00 |
April | 0.00 | 0.00 | 0.291757E+11 | 0.191526E+11 | 27161.44 | 20-APR-20:10 | 15666.53 | 0.00 |
May | 0.00 | 0.00 | 0.318636E+11 | 0.195834E+11 | 27427.63 | 30-MAY-03:23 | 15077.47 | 0.00 |
June | 0.00 | 0.00 | 0.315446E+11 | 0.193999E+11 | 27356.59 | 28-JUN-20:08 | 15025.55 | 0.00 |
July | 0.00 | 0.00 | 0.259505E+11 | 0.171013E+11 | 27026.56 | 07-JUL-20:08 | 16100.56 | 0.00 |
August | 0.00 | 0.00 | 0.285100E+11 | 0.170943E+11 | 27386.46 | 11-AUG-02:43 | 15156.65 | 0.00 |
September | 0.00 | 0.00 | 0.283270E+11 | 0.176410E+11 | 27181.06 | 18-SEP-20:08 | 15667.89 | 0.00 |
October | 0.00 | 0.00 | 0.278434E+11 | 0.175216E+11 | 27093.88 | 25-OCT-20:08 | 15927.91 | 0.00 |
November | 0.00 | 0.00 | 0.281043E+11 | 0.188962E+11 | 26937.58 | 30-NOV-21:08 | 16427.73 | 0.00 |
December | 0.00 | 0.00 | 0.284321E+11 | 0.203342E+11 | 27008.91 | 09-DEC-22:08 | 16248.84 | 0.00 |
Annual Sum or Average | 0.343988E+12 | 0.228043E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.259505E+11 | 0.170943E+11 | 26542.26 | 15025.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.318636E+11 | 0.208542E+11 | 27427.63 | 17455.99 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205641E+10 | 0.49 | 2655.03 | 03-JAN-21:07 | 0.87 |
February | 0.194917E+10 | 0.50 | 2655.03 | 01-FEB-21:06 | 0.87 |
March | 0.232004E+10 | 0.51 | 2655.03 | 01-MAR-21:06 | 0.87 |
April | 0.244447E+10 | 0.52 | 2655.03 | 01-APR-21:06 | 0.87 |
May | 0.277779E+10 | 0.54 | 2655.03 | 01-MAY-20:06 | 0.87 |
June | 0.293863E+10 | 0.56 | 2655.03 | 01-JUN-01:23 | 0.87 |
July | 0.242387E+10 | 0.51 | 2655.03 | 01-JUL-21:08 | 0.87 |
August | 0.246367E+10 | 0.51 | 2655.03 | 01-AUG-20:06 | 0.87 |
September | 0.226631E+10 | 0.51 | 2655.03 | 01-SEP-20:06 | 0.87 |
October | 0.214691E+10 | 0.49 | 2655.03 | 01-OCT-18:08 | 0.87 |
November | 0.203094E+10 | 0.49 | 2655.03 | 01-NOV-20:08 | 0.87 |
December | 0.203638E+10 | 0.49 | 2655.03 | 01-DEC-21:08 | 0.87 |
Annual Sum or Average | 0.278546E+11 | 0.51 | |||
Minimum of Months | 0.194917E+10 | 0.49 | 2655.03 | 0.87 | |
Maximum of Months | 0.293863E+10 | 0.56 | 2655.03 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109031E+11 | 0.73 | 14506.28 | 02-JAN-21:10 | 1.36 |
February | 0.102513E+11 | 0.76 | 14506.28 | 01-FEB-21:08 | 1.36 |
March | 0.121547E+11 | 0.79 | 14506.28 | 01-MAR-21:08 | 1.36 |
April | 0.127298E+11 | 0.82 | 14506.28 | 01-APR-21:08 | 1.36 |
May | 0.135958E+11 | 0.82 | 14506.28 | 01-MAY-20:08 | 1.36 |
June | 0.136680E+11 | 0.83 | 14506.28 | 01-JUN-20:10 | 1.36 |
July | 0.116315E+11 | 0.77 | 14506.28 | 01-JUL-21:10 | 1.36 |
August | 0.127853E+11 | 0.79 | 14506.28 | 01-AUG-20:08 | 1.36 |
September | 0.121116E+11 | 0.79 | 14506.28 | 01-SEP-20:08 | 1.36 |
October | 0.115596E+11 | 0.75 | 14506.28 | 01-OCT-18:10 | 1.36 |
November | 0.108868E+11 | 0.74 | 14506.28 | 01-NOV-20:10 | 1.36 |
December | 0.108803E+11 | 0.72 | 14506.28 | 01-DEC-21:08 | 1.36 |
Annual Sum or Average | 0.143158E+12 | 0.78 | |||
Minimum of Months | 0.102513E+11 | 0.72 | 14506.28 | 1.36 | |
Maximum of Months | 0.136680E+11 | 0.83 | 14506.28 | 1.36 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.293706E+10 | 0.84 | 1436.41 | 01-JAN-12:30 | 0.90 |
February | 0.268703E+10 | 0.85 | 1436.41 | 01-FEB-04:23 | 0.90 |
March | 0.301023E+10 | 0.84 | 1436.41 | 01-MAR-09:40 | 0.90 |
April | 0.292255E+10 | 0.84 | 1436.41 | 01-APR-18:10 | 0.90 |
May | 0.302646E+10 | 0.83 | 1436.41 | 24-MAY-14:37 | 0.90 |
June | 0.293112E+10 | 0.83 | 1436.41 | 01-JUN-07:50 | 0.89 |
July | 0.289597E+10 | 0.84 | 1436.41 | 01-JUL-09:50 | 0.90 |
August | 0.295914E+10 | 0.83 | 1436.41 | 01-AUG-07:20 | 0.89 |
September | 0.288395E+10 | 0.84 | 1436.41 | 01-SEP-14:10 | 0.90 |
October | 0.293870E+10 | 0.83 | 1436.41 | 23-OCT-05:50 | 0.89 |
November | 0.285162E+10 | 0.84 | 1436.41 | 28-NOV-16:30 | 0.90 |
December | 0.293423E+10 | 0.84 | 1436.41 | 01-DEC-11:00 | 0.90 |
Annual Sum or Average | 0.349781E+11 | 0.84 | |||
Minimum of Months | 0.268703E+10 | 0.83 | 1436.41 | 0.89 | |
Maximum of Months | 0.302646E+10 | 0.85 | 1436.41 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.252820E+10 | 0.84 | 1242.43 | 02-JAN-07:50 | 0.89 |
February | 0.231632E+10 | 0.85 | 1242.43 | 01-FEB-01:03 | 0.90 |
March | 0.258877E+10 | 0.84 | 1242.43 | 01-MAR-01:43 | 0.90 |
April | 0.251417E+10 | 0.84 | 1242.43 | 01-APR-09:30 | 0.90 |
May | 0.261362E+10 | 0.83 | 1242.43 | 01-MAY-04:05 | 0.89 |
June | 0.253313E+10 | 0.83 | 1242.43 | 01-JUN-09:50 | 0.89 |
July | 0.249327E+10 | 0.84 | 1242.43 | 01-JUL-15:20 | 0.90 |
August | 0.254258E+10 | 0.82 | 1242.43 | 02-AUG-14:20 | 0.89 |
September | 0.248389E+10 | 0.83 | 1242.43 | 01-SEP-09:10 | 0.89 |
October | 0.252029E+10 | 0.83 | 1242.43 | 02-OCT-06:10 | 0.89 |
November | 0.245588E+10 | 0.84 | 1242.43 | 01-NOV-09:30 | 0.89 |
December | 0.252445E+10 | 0.84 | 1242.43 | 01-DEC-06:10 | 0.90 |
Annual Sum or Average | 0.301146E+11 | 0.84 | |||
Minimum of Months | 0.231632E+10 | 0.82 | 1242.43 | 0.89 | |
Maximum of Months | 0.261362E+10 | 0.85 | 1242.43 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.06 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.06 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.21 | 0.00 |
February | 2.46 | 0.00 |
March | 0.24 | 0.00 |
April | 0.03 | 0.00 |
May | 0.89 | 0.00 |
June | 0.62 | 0.00 |
July | 0.50 | 0.00 |
August | 0.33 | 0.00 |
September | 0.46 | 0.00 |
October | 0.96 | 0.00 |
November | 1.96 | 0.00 |
December | 4.13 | 0.00 |
Annual Sum or Average | 15.79 | 0.00 |
Minimum of Months | 0.03 | 0.00 |
Maximum of Months | 4.13 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.117168E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.117375E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.144169E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.156178E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.176294E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.185460E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.149652E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.152119E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.140405E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.128112E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.120244E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.115106E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.170228E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.115106E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.185460E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.543243E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.532969E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.654517E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.704172E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.752571E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.752777E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.613838E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.685642E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.651107E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.607232E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.565248E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.544839E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.760816E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.532969E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.752777E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.104584E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.986140E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.109483E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.107739E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.114623E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.112434E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.981320E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.104593E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.103135E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.102608E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.102036E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.104157E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.126214E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.981320E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.114623E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.918144E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.869717E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.958330E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.944619E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.101093E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.994524E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.853126E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.910507E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.903248E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.891755E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.895360E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.914003E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.110643E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.853126E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.101093E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.205641E+10 | 0.375093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.194917E+10 | 0.379126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232004E+10 | 0.469046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.244447E+10 | 0.515702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.277779E+10 | 0.587193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.293863E+10 | 0.620502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.242387E+10 | 0.502477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.246367E+10 | 0.513924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.226631E+10 | 0.471329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.214691E+10 | 0.426760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203094E+10 | 0.396719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203638E+10 | 0.371062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278546E+11 | 0.562893E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.194917E+10 | 0.371062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.293863E+10 | 0.620502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109031E+11 | 0.158356E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102513E+11 | 0.156294E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121547E+11 | 0.193172E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127298E+11 | 0.212961E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135958E+11 | 0.231854E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136680E+11 | 0.232288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116315E+11 | 0.186221E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127853E+11 | 0.213789E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121116E+11 | 0.201667E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115596E+11 | 0.187631E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108868E+11 | 0.172027E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108803E+11 | 0.161561E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143158E+12 | 0.230782E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102513E+11 | 0.156294E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136680E+11 | 0.232288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.293706E+10 | 0.319372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268703E+10 | 0.300403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301023E+10 | 0.330909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.292255E+10 | 0.328989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.302646E+10 | 0.356434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.293112E+10 | 0.351558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.289597E+10 | 0.296800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.295914E+10 | 0.324456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.288395E+10 | 0.319975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.293870E+10 | 0.317692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285162E+10 | 0.317067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.293423E+10 | 0.321121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349781E+11 | 0.388478E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.268703E+10 | 0.296800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.302646E+10 | 0.356434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.252820E+10 | 0.282781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231632E+10 | 0.267616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.258877E+10 | 0.291969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.251417E+10 | 0.291757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261362E+10 | 0.318636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.253313E+10 | 0.315446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.249327E+10 | 0.259505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.254258E+10 | 0.285100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.248389E+10 | 0.283270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252029E+10 | 0.278434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.245588E+10 | 0.281043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.252445E+10 | 0.284321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301146E+11 | 0.343988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.231632E+10 | 0.259505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261362E+10 | 0.318636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.205641E+10 | 0.00 | 0.00 | 0.00 | 0.966039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.194917E+10 | 0.00 | 0.00 | 0.00 | 0.978830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232004E+10 | 0.00 | 0.00 | 0.00 | 0.120969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.244447E+10 | 0.00 | 0.00 | 0.00 | 0.131733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.277779E+10 | 0.00 | 0.00 | 0.00 | 0.148516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.293863E+10 | 0.00 | 0.00 | 0.00 | 0.156074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.242387E+10 | 0.00 | 0.00 | 0.00 | 0.125413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.246367E+10 | 0.00 | 0.00 | 0.00 | 0.127482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.226631E+10 | 0.00 | 0.00 | 0.00 | 0.117742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.214691E+10 | 0.00 | 0.00 | 0.00 | 0.106643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203094E+10 | 0.00 | 0.00 | 0.00 | 0.999344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203638E+10 | 0.00 | 0.00 | 0.00 | 0.947425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278546E+11 | 0.00 | 0.00 | 0.00 | 0.142374E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.194917E+10 | 0.00 | 0.00 | 0.00 | 0.947425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.293863E+10 | 0.00 | 0.00 | 0.00 | 0.156074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.109031E+11 | 0.00 | 0.00 | 0.00 | 0.434212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102513E+11 | 0.00 | 0.00 | 0.00 | 0.430456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121547E+11 | 0.00 | 0.00 | 0.00 | 0.532970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127298E+11 | 0.00 | 0.00 | 0.00 | 0.576874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135958E+11 | 0.00 | 0.00 | 0.00 | 0.616614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136680E+11 | 0.00 | 0.00 | 0.00 | 0.616098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116315E+11 | 0.00 | 0.00 | 0.00 | 0.497523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127853E+11 | 0.00 | 0.00 | 0.00 | 0.557789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121116E+11 | 0.00 | 0.00 | 0.00 | 0.529991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115596E+11 | 0.00 | 0.00 | 0.00 | 0.491637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108868E+11 | 0.00 | 0.00 | 0.00 | 0.456379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108803E+11 | 0.00 | 0.00 | 0.00 | 0.436036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143158E+12 | 0.00 | 0.00 | 0.00 | 0.617658E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.102513E+11 | 0.00 | 0.00 | 0.00 | 0.430456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136680E+11 | 0.00 | 0.00 | 0.00 | 0.616614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.293706E+10 | 0.00 | 0.00 | 0.00 | 0.752129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268703E+10 | 0.00 | 0.00 | 0.00 | 0.717437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301023E+10 | 0.00 | 0.00 | 0.00 | 0.793811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.292255E+10 | 0.00 | 0.00 | 0.00 | 0.785137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.302646E+10 | 0.00 | 0.00 | 0.00 | 0.843585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.293112E+10 | 0.00 | 0.00 | 0.00 | 0.831226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.289597E+10 | 0.00 | 0.00 | 0.00 | 0.691723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.295914E+10 | 0.00 | 0.00 | 0.00 | 0.750017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.288395E+10 | 0.00 | 0.00 | 0.00 | 0.742953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.293870E+10 | 0.00 | 0.00 | 0.00 | 0.732212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285162E+10 | 0.00 | 0.00 | 0.00 | 0.735195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.293423E+10 | 0.00 | 0.00 | 0.00 | 0.748144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349781E+11 | 0.00 | 0.00 | 0.00 | 0.912357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.268703E+10 | 0.00 | 0.00 | 0.00 | 0.691723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.302646E+10 | 0.00 | 0.00 | 0.00 | 0.843585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.252820E+10 | 0.00 | 0.00 | 0.00 | 0.665324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231632E+10 | 0.00 | 0.00 | 0.00 | 0.638085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.258877E+10 | 0.00 | 0.00 | 0.00 | 0.699453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.251417E+10 | 0.00 | 0.00 | 0.00 | 0.693202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261362E+10 | 0.00 | 0.00 | 0.00 | 0.749567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.253313E+10 | 0.00 | 0.00 | 0.00 | 0.741211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.249327E+10 | 0.00 | 0.00 | 0.00 | 0.603798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.254258E+10 | 0.00 | 0.00 | 0.00 | 0.656249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.248389E+10 | 0.00 | 0.00 | 0.00 | 0.654860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252029E+10 | 0.00 | 0.00 | 0.00 | 0.639726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.245588E+10 | 0.00 | 0.00 | 0.00 | 0.649771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.252445E+10 | 0.00 | 0.00 | 0.00 | 0.661558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301146E+11 | 0.00 | 0.00 | 0.00 | 0.805280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.231632E+10 | 0.00 | 0.00 | 0.00 | 0.603798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261362E+10 | 0.00 | 0.00 | 0.00 | 0.749567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.933021E+10 | 0.00 | 0.00 | 6031881.34 | 0.00 | 0.00 | 0.00 | 0.25 |
February | 0.00 | 0.962516E+10 | 0.00 | 0.00 | 3212408.96 | 0.00 | 0.00 | 0.00 | 0.25 |
March | 0.00 | 0.120426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
April | 0.00 | 0.151757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
May | 0.00 | 0.183800E+11 | 0.00 | 0.00 | 1755484.20 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.187144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.136266E+11 | 0.00 | 0.00 | 2951114.33 | 0.00 | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.164602E+11 | 0.00 | 0.00 | 1999982.47 | 0.00 | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.151618E+11 | 0.00 | 0.00 | 1663235.93 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.00 | 0.138419E+11 | 0.00 | 0.00 | 12157580.67 | 0.00 | 0.00 | 0.00 | 0.25 |
November | 0.00 | 0.118743E+11 | 0.00 | 0.00 | 5846131.09 | 0.00 | 0.00 | 0.00 | 0.25 |
December | 0.00 | 0.998042E+10 | 0.00 | 0.00 | 10992066.30 | 0.00 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.00 | 0.164213E+12 | 0.00 | 0.00 | 46609885.30 | 0.00 | 0.00 | 0.00 | 0.26 |
Minimum of Months | 0.00 | 0.933021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.00 | 0.187144E+11 | 0.00 | 0.00 | 12157580.67 | 0.00 | 0.00 | 0.00 | 0.27 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.659324E+11 | 0.00 | 305922.39 | 0.296340E+09 | 0.00 | 18454293.05 | 0.00 | 0.47 |
February | 0.00 | 0.676884E+11 | 0.00 | 0.00 | 0.215620E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
March | 0.00 | 0.863798E+11 | 0.00 | 0.00 | 85045339.01 | 0.00 | 0.00 | 0.00 | 0.49 |
April | 0.00 | 0.107084E+12 | 0.00 | 0.00 | 44402093.37 | 0.00 | 0.00 | 0.00 | 0.49 |
May | 0.00 | 0.126025E+12 | 0.00 | 0.00 | 72080561.42 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.125865E+12 | 0.00 | 0.00 | 19542454.74 | 0.00 | 0.00 | 0.00 | 0.50 |
July | 0.00 | 0.894993E+11 | 0.00 | 0.00 | 0.169260E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.114349E+12 | 0.00 | 0.00 | 0.236378E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.105704E+12 | 0.00 | 0.00 | 0.204632E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.971022E+11 | 0.00 | 0.00 | 0.344722E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
November | 0.00 | 0.833456E+11 | 0.00 | 0.00 | 0.212426E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
December | 0.00 | 0.707109E+11 | 0.00 | 21328.63 | 0.262573E+09 | 0.00 | 1575316.07 | 0.00 | 0.47 |
Annual Sum or Average | 0.00 | 0.113969E+13 | 0.00 | 327251.02 | 0.216302E+10 | 0.00 | 20029609.12 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.659324E+11 | 0.00 | 0.00 | 19542454.74 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.00 | 0.126025E+12 | 0.00 | 305922.39 | 0.344722E+09 | 0.00 | 18454293.05 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.816908E+10 | 0.00 | 0.00 | 1714111.52 | 0.00 | 0.00 | 0.00 | 0.54 |
February | 0.00 | 0.815877E+10 | 0.00 | 6319.84 | 1792508.23 | 0.00 | 0.00 | 0.00 | 0.54 |
March | 0.00 | 0.985452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
April | 0.00 | 0.118928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
May | 0.00 | 0.141477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.139346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.100770E+11 | 0.00 | 0.00 | 942127.42 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.126595E+11 | 0.00 | 0.00 | 1330476.99 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.120244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.114249E+11 | 0.00 | 0.00 | 2858440.83 | 0.00 | 0.00 | 0.00 | 0.54 |
November | 0.00 | 0.101171E+11 | 0.00 | 0.00 | 1793629.62 | 0.00 | 0.00 | 0.00 | 0.54 |
December | 0.00 | 0.877283E+10 | 0.00 | 0.00 | 1229659.71 | 0.00 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.00 | 0.131233E+12 | 0.00 | 6319.84 | 11660954.32 | 0.00 | 0.00 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.815877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.00 | 0.141477E+11 | 0.00 | 6319.84 | 2858440.83 | 0.00 | 0.00 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.796981E+10 | 0.00 | 0.00 | 1694883.18 | 0.00 | 0.00 | 0.00 | 0.53 |
February | 0.00 | 0.799456E+10 | 0.00 | 10475.06 | 1770216.77 | 0.00 | 880.80 | 0.00 | 0.54 |
March | 0.00 | 0.956949E+10 | 0.00 | 0.00 | 980700.98 | 0.00 | 0.00 | 0.00 | 0.55 |
April | 0.00 | 0.115418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
May | 0.00 | 0.137706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.135994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.969455E+10 | 0.00 | 0.00 | 934254.59 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.121576E+11 | 0.00 | 0.00 | 1276673.18 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.116286E+11 | 0.00 | 0.00 | 3087419.85 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.109664E+11 | 0.00 | 0.00 | 5789311.69 | 0.00 | 0.00 | 0.00 | 0.53 |
November | 0.00 | 0.982970E+10 | 0.00 | 0.00 | 2984127.66 | 0.00 | 0.00 | 0.00 | 0.54 |
December | 0.00 | 0.854330E+10 | 0.00 | 0.00 | 1202024.26 | 0.00 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.00 | 0.127266E+12 | 0.00 | 10475.06 | 19719612.16 | 0.00 | 880.80 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.796981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.00 | 0.137706E+11 | 0.00 | 10475.06 | 5789311.69 | 0.00 | 880.80 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |