Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2020-06-03 19:13:12
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1386.63 | 604.46 | 604.46 |
Net Site Energy | 1386.63 | 604.46 | 604.46 |
Total Source Energy | 4181.61 | 1822.85 | 1822.85 |
Net Source Energy | 4181.61 | 1822.85 | 1822.85 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 15.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 590.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 289.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 38.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 174.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 85.35 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1285.89 | 100.74 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 15.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 590.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 289.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 38.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 174.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 85.35 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 333.09 | 43.92 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 560.55 | 43.92 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 333.09 | 43.92 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 560.55 | 43.92 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1285.889 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1285.889 | 100.00 |
Total On-Site and Utility Electric Sources | 1285.889 | 100.00 |
Total Electricity End Uses | 1285.889 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 410.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.5670 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 13.1320 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 13.1320 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 13.1320 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 10.7639 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 12.1980 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 12.1980 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-JUN-15:00 | 02-JAN-07:10 | - | - | - | 01-MAY-11:09 |
Heating | 0.00 | 118061.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 85564.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 22873.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16051.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 135229.96 | 119921.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 118061.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 85564.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 22873.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 16051.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 16.68 | 0.00 | 0.00 | 0.00 |
Cooling | 1868.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 915.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 121.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 615.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 551.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 92.52 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4072.41 | 109.20 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 7.27 | 0.00 | 0.00 | 0.00 |
Cooling | 814.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 399.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 240.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 40.33 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1775.25 | 47.60 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 7.27 | 0.00 | 0.00 | 0.00 |
Cooling | 814.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 399.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 240.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 40.33 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1775.25 | 47.60 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 2.79 |
CORE_RETAIL DIRECT AIR | 8.38 |
POINT_OF_SALE DIRECT AIR | 1.52 |
FRONT_RETAIL DIRECT AIR | 1.33 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 0.722669 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 0.722669 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 20776.57 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 66728.44 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 222165.35 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 37257.06 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 32911.40 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 2.79 | 2.79 | 2.79 | 2.79 | 2.85 | 2.85 | 1.00 | 0.977566 | 2.85 |
PSZ-AC:2 | 8.38 | 8.38 | 8.38 | 8.38 | 8.52 | 8.52 | 1.00 | 0.983280 | 8.52 |
PSZ-AC:3 | 1.52 | 1.52 | 1.52 | 1.52 | 1.52 | 1.52 | 1.00 | 1.00 | 1.52 |
PSZ-AC:4 | 1.33 | 1.33 | 1.33 | 1.33 | 1.33 | 1.33 | 1.00 | 1.00 | 1.33 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 2.85 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 8.52 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.52 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 1.33 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 2.85 | 2.85 | 2.85 | 1.88 | 59370.10 | 66728.44 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 8.52 | 8.52 | 8.52 | 5.63 | 211655.47 | 222165.35 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.52 | 1.52 | 1.52 | 1.00 | 32536.87 | 37257.06 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.33 | 1.33 | 1.33 | 0.874543 | 29326.70 | 32911.40 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 2.85 | 1.43 | 1.90 | 55337.66 | 59370.10 | 29685.05 | 29685.05 | 0.723170 | 0.723170 | 0.723170 | 0.723170 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 8.52 | 4.26 | 5.68 | 200972.56 | 211655.47 | 105827.74 | 105827.74 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.52 | 0.759010 | 1.01 | 30410.50 | 32536.87 | 16268.43 | 16268.43 | 0.714945 | 0.714940 | 0.714940 | 0.714940 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.33 | 0.662535 | 0.883380 | 27483.82 | 29326.70 | 14663.35 | 14663.35 | 0.705984 | 0.705980 | 0.705980 | 0.705980 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.85 | 3049.82 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 8.52 | 14359.44 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.52 | 1624.35 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.33 | 1467.06 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.567 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.637 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 13.132 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 16.362 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 13.132 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 34.652 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 13.132 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 16.362 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 10.764 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.764 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2874.639 | 7.567 | 46.863 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2874.639 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 21017.495 | 13.132 | 81.326 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21017.495 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 1980.433 | 13.132 | 81.326 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1980.433 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 1980.433 | 13.132 | 81.326 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1980.433 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 129.167 | 10.764 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 129.167 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
25 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
26 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
27 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
28 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
29 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
30 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
31 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
32 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
33 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 30 | 1 | VerySmooth | 3.241 | 0.252 | 0.162 | 0.276 |
2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 31 | 1 | VerySmooth | 4.262 | 0.355 | 0.203 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1915 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 31620.57165 | 37944.68598 | 2.32186 | 2.78623 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 22815.62770 | 27378.75324 | 0.98491 | 1.18189 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 96044.46927 | 115253.36312 | 6.98405 | 8.38085 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 50223.41621 | 60268.09945 | 2.12462 | 2.54955 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 16758.23218 | 20109.87861 | 1.26501 | 1.51802 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.11023E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 10534.66839 | 12641.60207 | 0.45609 | 0.54731 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 14628.13021 | 17553.75625 | 1.10422 | 1.32507 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 41.61200 | 9.11023E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 10526.72810 | 12632.07372 | 0.45574 | 0.54689 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00000 | 9.11023E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 17312.15169 | 20774.58202 | 0.60222 | 0.72267 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 41994.91 | 2.85017 | 2.85017 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 30603.17 | 1.18189 | 1.18189 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 147309.38 | 8.52337 | 8.52337 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 90069.37 | 2.54955 | 2.54955 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 23535.68 | 1.51802 | 1.51802 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 15394.72 | 0.54731 | 0.54731 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 21080.39 | 1.32507 | 1.32507 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 15385.26 | 0.54689 | 0.54689 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.78623 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 8.38085 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.51802 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.32507 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.72267 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 0.72267 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 20776.57317 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.78623 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.78623 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.78623 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.78623 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.85017 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.85017 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.97757 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.38085 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 8.38085 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.38085 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 8.38085 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.52337 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 8.52337 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.98328 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.51802 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.51802 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.51802 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.51802 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.51802 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.51802 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.32507 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.32507 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.32507 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.32507 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.32507 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.32507 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 2.85017 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 8.52337 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.51802 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.32507 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.85017 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.85017 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.85017 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.85017 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.88111 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.85017 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.42509 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.90011 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 55337.65912 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 59370.10000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 29685.05000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 29685.05000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72317 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72317 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72317 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72317 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 59370.10000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 66728.43535 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.85017 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3049.81869 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 66728.43535 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.52337 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.52337 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.52337 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.52337 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.62542 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 8.52337 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.26169 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.68225 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 200972.56344 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 211655.47000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 105827.73500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 105827.73500 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 211655.47000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 222165.34864 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 8.52337 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 14359.43888 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 222165.34864 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.51802 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.51802 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.51802 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.51802 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00189 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.51802 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.75901 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.01201 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 30410.50226 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 32536.87000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16268.43500 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 16268.43500 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71494 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71494 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71494 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71494 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32536.87000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37257.06231 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.51802 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1624.34810 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 37257.06231 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.32507 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.32507 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.32507 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.32507 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.87454 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.32507 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.66254 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.88338 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27483.81957 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29326.70000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14663.35000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 14663.35000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70598 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70598 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70598 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70598 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29326.70000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32911.40393 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.32507 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1467.05755 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32911.40393 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 57128.7 | 11.44 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 204931.3 | 13.88 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 31342.5 | 109.26 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 28283.6 | 133.46 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 7.6127204740E-002 | 0.3357288879 | Pass | Pass | 6.0014804315E-002 | 0.2430242516 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 3.8640000465E-002 | 0.1603060587 | Pass | Pass | 0.2095697863 | 0.6984833671 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 8.1517721291E-002 | 0.2347439992 | Pass | Pass | 0.1458461787 | 0.5618198071 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 7.1644285157E-002 | 0.2714602538 | Pass | Pass | 0.1796944809 | 0.8302686903 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1608248198 | 0.3832779547 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.57_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 3.241 | 0.252 | 0.276 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.57_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 3.241 | 0.252 | 0.276 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 3.241 | 0.252 | 0.276 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 3.466 | 0.275 | 0.303 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 3.466 | 0.275 | 0.303 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.5670 | 379.89 | 2874.64 | LightsWired | BLDG_LIGHT_BACK_SCH | 55.08 | 168.00 | 52.05 | 0.0000 | Y | 28.09 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 13.1320 | 1600.48 | 21017.49 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 54.05 | 0.0000 | Y | 213.26 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 13.1320 | 150.81 | 1980.43 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 65.03 | 0.0000 | Y | 24.18 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 13.1320 | 150.81 | 1980.43 | LightsWired | BLDG_LIGHT_FRONT_SCH | 67.15 | 168.00 | 63.01 | 0.0000 | Y | 23.42 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 10.7639 | 12.00 | 129.17 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 57.54 | 168.00 | 3.36 | 0.0000 | Y | 0.08 |
Interior Lighting Total | 12.1980 | 2293.99 | 27982.17 | 289.03 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 21017.49 | 5254.37 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 21017.49 | 5254.37 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 316.30 | AstronomicalClock | - | 41.75 | 41.75 | 2.48 | |
EXTERIOR_LIGHTS_B | 3054.90 | AstronomicalClock | - | 83.75 | 62.75 | 35.99 | |
Exterior Lighting Total | 3371.20 | 38.47 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 59370.10 | 42934.68 | 16435.42 | 0.72 | 3.73 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 211655.47 | 143096.03 | 68559.44 | 0.68 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 32536.87 | 23261.91 | 9274.96 | 0.71 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 29326.70 | 20704.06 | 8622.64 | 0.71 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 57128.7 | 11.44 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 204931.3 | 13.88 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 31342.5 | 109.26 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 28283.6 | 133.46 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 20776.57 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 66728.44 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 222165.35 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 37257.06 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32911.40 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.72 | 800.11 | 1107.16 | 1.00 | 1.48 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.85 | 3049.82 | 1070.05 | 1.00 | 1.27 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 8.52 | 14359.44 | 1684.71 | 1.00 | 1.15 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.52 | 1624.35 | 1070.05 | 1.00 | 1.36 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.33 | 1467.06 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 31620.57 | 37944.69 | 99.88 | 2.322 | 2.786 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 23.89 | 23.89 | 0.00751 | 34.82 | 0.00911 | 0.232 | 0.00 |
CORE_RETAIL | 96044.47 | 115253.36 | 72.01 | 6.984 | 8.381 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 23.89 | 23.89 | 0.00793 | 34.82 | 0.00911 | 1.890 | 0.00 |
POINT_OF_SALE | 16758.23 | 20109.88 | 133.35 | 1.265 | 1.518 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 23.89 | 23.89 | 0.00733 | 41.16 | 0.00911 | 0.178 | 0.00 |
FRONT_RETAIL | 14628.13 | 17553.76 | 116.40 | 1.104 | 1.325 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 23.89 | 23.89 | 0.00738 | 41.61 | 0.00911 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 40.93 | 100.00 | 0.00001 | 42.00 | 0.00911 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 22815.63 | 27378.75 | 72.07 | 0.985 | 1.182 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00797 | 6.30 | 0.00607 | 0.232 | 0.00 |
CORE_RETAIL | 50223.42 | 60268.10 | 37.66 | 2.125 | 2.550 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00798 | 6.30 | 0.00607 | 1.890 | 0.00 |
POINT_OF_SALE | 10534.67 | 12641.60 | 83.82 | 0.456 | 0.547 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00798 | 6.30 | 0.00607 | 0.178 | 0.00 |
FRONT_RETAIL | 10526.73 | 12632.07 | 83.76 | 0.456 | 0.547 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00798 | 6.30 | 0.00607 | 0.178 | 0.00 |
FRONT_ENTRY | 17312.15 | 20774.58 | 1731.22 | 0.602 | 0.723 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 16.00 | 15.98 | 0.00663 | 6.30 | 0.00607 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 2.85 | 2.85 | 1.18 | 1.18 | 2.8502 | 2.7862 | 2.8502 | 0.9776 | 1.0000 |
PSZ-AC:2 | 8.52 | 8.52 | 2.55 | 2.55 | 8.5234 | 8.3809 | 8.5234 | 0.9833 | 1.0000 |
PSZ-AC:3 | 1.52 | 1.52 | 0.55 | 0.55 | 1.5180 | 1.5180 | 1.5180 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.33 | 1.33 | 0.55 | 0.55 | 1.3251 | 1.3251 | 1.3251 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 20776.573 | 20776.573 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 20776.57 | 20776.57 | 0.722669 | 15.79 | 11.21 | 0.00662044 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 15.98 | 0.00663141 | 57.3640 | 20774.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 29685.050 | 0.000 | 2.850170 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 29685.05 | 27354.87 | 2.850170 | 25.31 | 15.78 | 0.00757710 | 12.80 | 10.33 | 0.00700000 | 41.42 | 0.00911023 | 22.04 | 8.1247 | 23.89 | 0.00750882 | 39.7304 | 31406.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 66728.435 | 66728.435 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 66728.44 | 66728.44 | 2.850172 | 18.05 | 13.09 | 0.00759974 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 8.1247 | 21.11 | 0.00797192 | 49.8997 | 22815.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 105827.735 | 0.000 | 8.523370 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 | 105827.74 | 94130.59 | 8.523370 | 28.08 | 17.08 | 0.00797693 | 12.80 | 10.33 | 0.00700000 | 42.00 | 0.00911023 | 22.20 | 22.1768 | 23.89 | 0.00792548 | 41.9107 | 90259.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 222165.349 | 222165.349 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 222165.35 | 222165.35 | 8.523366 | 10.05 | 8.64 | 0.00656583 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 22.1768 | 21.11 | 0.00798060 | 49.9531 | 50223.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 16268.435 | 0.000 | 1.518020 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 16268.43 | 15110.34 | 1.518020 | 25.96 | 15.97 | 0.00753869 | 12.80 | 10.33 | 0.00700000 | 41.52 | 0.00911022 | 22.06 | 11.7331 | 23.89 | 0.00732930 | 38.7902 | 16740.92 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 37257.062 | 37257.062 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37257.06 | 37257.06 | 1.518015 | 16.15 | 12.10 | 0.00735908 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 11.7331 | 21.11 | 0.00797984 | 49.9487 | 10534.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 14663.350 | 0.000 | 1.325070 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 14663.35 | 13511.68 | 1.325070 | 26.31 | 16.16 | 0.00761104 | 12.80 | 10.33 | 0.00700000 | 41.90 | 0.00911022 | 22.17 | 13.4416 | 23.89 | 0.00737696 | 39.0395 | 14599.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 32911.404 | 32911.404 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32911.40 | 32911.40 | 1.325065 | 16.15 | 12.10 | 0.00735856 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 13.4416 | 21.11 | 0.00797978 | 49.9482 | 10526.73 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 20776.573 | 20776.573 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.722669 | 0.84825884 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 20776.57 | 20776.57 | 1.0000 | 0.84825884 | 0.722669 | 15.79 | 11.21 | 0.00662044 | 32618.5 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20776.57 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 15.98 | 0.00663141 | 15.98 | 0.00663141 | 57.3640 | 20774.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29685.050 | 0.000 | 2.850170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.9255 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 29685.05 | 27354.87 | 1.0000 | 3.34548811 | 2.850170 | 25.31 | 15.78 | 0.00757710 | 44743.9 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29685.05 | 41.42 | 0.00911023 | 22.04 | 0.23156651 | 8.1247 | 23.89 | 0.00744126 | 23.89 | 0.00750882 | 39.7304 | 31406.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 66728.435 | 66728.435 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.850172 | 3.34549036 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 66728.44 | 66728.44 | 1.0000 | 3.34549036 | 2.850172 | 18.05 | 13.09 | 0.00759974 | 37395.7 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 66728.44 | 6.30 | 0.00607234 | 6.30 | 0.23156651 | 8.1247 | 20.91 | 0.00797192 | 21.11 | 0.00797192 | 49.8997 | 22815.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 105827.735 | 0.000 | 8.523370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6687 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 | 105827.74 | 94130.59 | 1.0000 | 10.00460778 | 8.523370 | 28.08 | 17.08 | 0.00797693 | 48577.2 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 105827.74 | 42.00 | 0.00911023 | 22.20 | 1.89021192 | 22.1768 | 23.89 | 0.00763614 | 23.89 | 0.00792548 | 41.9107 | 90259.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 222165.349 | 222165.349 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.523366 | 10.00460266 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 222165.35 | 222165.35 | 1.0000 | 10.00460266 | 8.523366 | 10.05 | 8.64 | 0.00656583 | 26640.4 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 222165.35 | 6.30 | 0.00607234 | 6.30 | 1.89021192 | 22.1768 | 20.79 | 0.00798060 | 21.11 | 0.00798060 | 49.9531 | 50223.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16268.435 | 0.000 | 1.518020 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.8541 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 16268.43 | 15110.34 | 1.0000 | 1.78182980 | 1.518020 | 25.96 | 15.97 | 0.00753869 | 45301.7 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16268.43 | 41.52 | 0.00911022 | 22.06 | 0.17811053 | 11.7331 | 23.89 | 0.00732955 | 23.89 | 0.00732930 | 38.7902 | 16740.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37257.062 | 37257.062 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.518015 | 1.78182425 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37257.06 | 37257.06 | 1.0000 | 1.78182425 | 1.518015 | 16.15 | 12.10 | 0.00735908 | 34856.0 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37257.06 | 6.30 | 0.00607234 | 6.30 | 0.17811053 | 11.7331 | 20.91 | 0.00797984 | 21.11 | 0.00797984 | 49.9487 | 10534.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14663.350 | 0.000 | 1.325070 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.9885 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 14663.35 | 13511.68 | 1.0000 | 1.55534790 | 1.325070 | 26.31 | 16.16 | 0.00761104 | 45848.8 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14663.35 | 41.90 | 0.00911022 | 22.17 | 0.17811053 | 13.4416 | 23.89 | 0.00737770 | 23.89 | 0.00737696 | 39.0395 | 14599.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32911.404 | 32911.404 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.325065 | 1.55534230 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32911.40 | 32911.40 | 1.0000 | 1.55534230 | 1.325065 | 16.15 | 12.10 | 0.00735856 | 34851.0 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32911.40 | 6.30 | 0.00607234 | 6.30 | 0.17811053 | 13.4416 | 20.91 | 0.00797978 | 21.11 | 0.00797978 | 49.9482 | 10526.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 3031.50 | 1422.17 | 89.50 |
CORE_RETAIL | 3332.83 | 1247.00 | 339.50 |
POINT_OF_SALE | 3941.83 | 424.67 | 21.33 |
FRONT_RETAIL | 3806.83 | 622.67 | 90.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 4027.50 | 1743.50 | 410.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 3.17 | 61.17 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 0.33 | 85.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.67 | 66.17 | 0.00 | 0.00 |
FRONT_ENTRY | 60.50 | 0.00 | 0.00 | 0.00 |
Facility | 63.83 | 97.17 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.42 | 61.34 | 2317.33 | 0.371 | 0.013 | 0.000 | 0.000 |
CORE_RETAIL | 128.15 | 258.43 | 9762.95 | 0.720 | 0.002 | 0.000 | 0.000 |
POINT_OF_SALE | 12.08 | 24.35 | 919.94 | 0.719 | 0.014 | 0.000 | 0.000 |
FRONT_RETAIL | 12.08 | 24.35 | 919.94 | 0.719 | 0.014 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.42 | 61.34 | 2317.33 | 0.339 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.15 | 258.43 | 9762.95 | 0.657 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.08 | 24.35 | 919.94 | 0.658 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.08 | 24.35 | 919.94 | 0.657 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1285.89 | 2265.44 | 01-JAN-07:40 | 135229.96 | 10-JUN-16:00 |
Electricity:Building | 483.32 | 2265.44 | 01-JAN-00:10 | 35190.60 | 02-JAN-15:50 |
Electricity:Zone:BACK_SPACE | 77.86 | 535.60 | 01-JAN-00:10 | 4774.71 | 02-JAN-09:10 |
InteriorLights:Electricity | 289.03 | 493.85 | 01-JAN-00:10 | 24449.72 | 02-JAN-15:50 |
InteriorLights:Electricity:Zone:BACK_SPACE | 28.09 | 81.78 | 01-JAN-00:10 | 2023.29 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 289.03 | 493.85 | 01-JAN-00:10 | 24449.72 | 02-JAN-15:50 |
Electricity:Zone:CORE_RETAIL | 297.19 | 1109.80 | 01-JAN-00:10 | 23555.33 | 02-JAN-15:50 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 213.26 | 344.55 | 01-JAN-00:10 | 18915.75 | 02-JAN-15:50 |
Electricity:Zone:POINT_OF_SALE | 76.87 | 512.89 | 01-JAN-00:10 | 4695.10 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 24.18 | 32.47 | 01-JAN-00:10 | 1782.39 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 31.33 | 104.57 | 01-JAN-00:10 | 2162.89 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 23.42 | 32.47 | 01-JAN-00:10 | 1725.71 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 0.08 | 2.58 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 0.08 | 2.58 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 |
InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.77 | 453.82 | 01-JAN-00:10 | 2751.42 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 83.93 | 765.25 | 01-JAN-00:10 | 4639.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.69 | 480.42 | 01-JAN-00:10 | 2912.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.91 | 72.11 | 01-JAN-00:10 | 437.18 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1285.89 | 2265.44 | 01-JAN-07:40 | 135229.96 | 10-JUN-16:00 |
ElectricityPurchased:Plant | 1285.89 | 2265.44 | 01-JAN-07:40 | 135229.96 | 10-JUN-16:00 |
Cogeneration:ElectricityPurchased | 1285.89 | 2265.44 | 01-JAN-07:40 | 135229.96 | 10-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1285.89 | 2265.44 | 01-JAN-07:40 | 135229.96 | 10-JUN-16:00 |
ElectricityNet:Plant | 1285.89 | 2265.44 | 01-JAN-07:40 | 135229.96 | 10-JUN-16:00 |
Cogeneration:ElectricityNet | 1285.89 | 2265.44 | 01-JAN-07:40 | 135229.96 | 10-JUN-16:00 |
Electricity:HVAC | 764.10 | 0.00 | 01-JAN-00:10 | 101615.67 | 10-JUN-16:00 |
Fans:Electricity | 174.02 | 0.00 | 01-JAN-00:10 | 16361.39 | 01-JUL-16:00 |
General:Fans:Electricity | 174.02 | 0.00 | 01-JAN-00:10 | 16361.39 | 01-JUL-16:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 590.08 | 0.00 | 01-JAN-00:10 | 85564.27 | 10-JUN-16:00 |
ExteriorLights:Electricity | 38.47 | 0.00 | 01-JAN-07:20 | 3371.20 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 38.47 | 0.00 | 01-JAN-07:20 | 3371.20 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 100.74 | 1860.00 | 04-JAN-20:20 | 119921.28 | 02-JAN-07:10 |
Gas:Plant | 85.35 | 1860.00 | 02-JAN-20:10 | 4923.53 | 23-JAN-12:50 |
WaterSystems:Gas | 85.35 | 1860.00 | 02-JAN-20:10 | 4923.53 | 23-JAN-12:50 |
Water Heater:WaterSystems:Gas | 85.35 | 1860.00 | 02-JAN-20:10 | 4923.53 | 23-JAN-12:50 |
Gas:HVAC | 15.39 | 0.00 | 01-JAN-00:10 | 118061.28 | 02-JAN-07:10 |
Heating:Gas | 15.39 | 0.00 | 01-JAN-00:10 | 118061.28 | 02-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 3298.52 | 0.00 | 01-JAN-00:10 | 401044.21 | 01-JUL-16:00 |
EnergyTransfer:Building | 1166.38 | 0.00 | 01-JAN-00:10 | 140635.48 | 12-JUN-14:40 |
EnergyTransfer:Zone:BACK_SPACE | 212.82 | 0.00 | 01-JAN-00:10 | 37926.62 | 06-JUN-04:10 |
Heating:EnergyTransfer | 7.06 | 0.00 | 01-JAN-00:10 | 71756.53 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 3.87 | 0.00 | 01-JAN-00:10 | 30336.37 | 01-JAN-07:10 |
Cooling:EnergyTransfer | 1159.32 | 0.00 | 01-JAN-00:10 | 140635.48 | 12-JUN-14:40 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 208.95 | 0.00 | 01-JAN-00:10 | 37926.62 | 06-JUN-04:10 |
EnergyTransfer:Zone:CORE_RETAIL | 666.94 | 0.00 | 01-JAN-00:10 | 86123.21 | 29-MAY-08:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 2.76 | 0.00 | 01-JAN-00:10 | 53849.64 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 664.18 | 0.00 | 01-JAN-00:10 | 82222.57 | 12-JUN-14:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 159.15 | 0.00 | 01-JAN-00:10 | 16276.44 | 12-JUN-04:30 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.12 | 0.00 | 01-JAN-00:10 | 7870.78 | 01-JAN-07:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 159.03 | 0.00 | 01-JAN-00:10 | 16276.44 | 12-JUN-04:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 127.46 | 0.00 | 01-JAN-00:10 | 15608.58 | 13-JUN-04:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.29 | 0.00 | 01-JAN-00:10 | 9887.87 | 01-JAN-07:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 127.16 | 0.00 | 01-JAN-00:10 | 15608.58 | 13-JUN-04:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 0.02 | 0.00 | 01-JAN-00:10 | 2049.21 | 03-JAN-08:10 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.02 | 0.00 | 01-JAN-00:10 | 2049.21 | 03-JAN-08:10 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 2132.13 | 0.00 | 01-JAN-00:10 | 282678.86 | 01-JUL-16:00 |
HeatingCoils:EnergyTransfer | 12.31 | 0.00 | 01-JAN-00:10 | 94449.02 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 2119.82 | 0.00 | 01-JAN-00:10 | 282678.86 | 01-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 3.869 | -208.943 | 0.000 | 0.000 | 37.250 | 28.087 | 49.772 | 0.000 | 0.000 | 1.265 | 89.520 | 0.000 | 0.000 | 0.000 | -0.819 | -0.001 |
CORE_RETAIL | 0.000 | 0.000 | 2.760 | -664.172 | 0.000 | 0.000 | 155.697 | 213.259 | 83.927 | 49.052 | 0.000 | 1.079 | 172.009 | 0.000 | -12.872 | 0.000 | -0.740 | -0.000 |
POINT_OF_SALE | 0.000 | 0.000 | 0.117 | -159.031 | 0.000 | 0.000 | 14.600 | 24.176 | 52.689 | 36.092 | 0.000 | 0.534 | 41.977 | 0.000 | -10.699 | 0.000 | -0.454 | -0.001 |
FRONT_RETAIL | 0.000 | 0.000 | 0.292 | -127.162 | 0.000 | 0.000 | 14.646 | 23.423 | 7.908 | 36.066 | 0.000 | 0.543 | 54.955 | 0.000 | -10.255 | 0.000 | -0.417 | -0.001 |
FRONT_ENTRY | 0.021 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.081 | 0.000 | 6.446 | 0.000 | 3.681 | 0.000 | 0.000 | -2.259 | 0.000 | -4.975 | -2.995 |
Total Facility | 0.021 | 0.000 | 7.038 | -1159.308 | 0.000 | 0.000 | 222.193 | 289.026 | 194.297 | 127.656 | 0.000 | 7.101 | 358.462 | 0.000 | -36.086 | 0.000 | -7.406 | -2.998 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 09-MAY-04:01 | 0.00 | 0.00 | 0.00 | -55720.26 | 0.00 | 0.00 | 0.00 | 81.78 | 605.09 | 0.00 | 0.00 | 0.00 | 55033.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 28-APR-05:01 | 0.00 | 0.00 | 0.00 | -181141.20 | 0.00 | 0.00 | 0.00 | 344.55 | 1020.33 | 0.00 | 0.00 | 0.02 | 180536.44 | 0.00 | -760.13 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 23-OCT-04:01 | 0.00 | 0.00 | 0.00 | -30878.89 | 0.00 | 0.00 | 0.00 | 32.47 | 640.56 | 0.00 | 0.00 | 0.00 | 31343.97 | 0.00 | -1114.15 | 0.00 | -23.94 | 0.00 |
FRONT_RETAIL | 08-APR-04:01 | 0.00 | 0.00 | 0.00 | -27106.08 | 0.00 | 0.00 | 0.00 | 32.47 | 72.11 | 0.00 | 0.00 | 0.00 | 27666.67 | 0.00 | -612.60 | 0.00 | -52.56 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-MAY-04:01 | 0.00 | 0.00 | 0.00 | -283387.20 | 0.00 | 0.00 | 0.00 | 493.85 | 2362.12 | 0.00 | 0.00 | 0.00 | 282134.91 | 0.00 | -1603.67 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 01-JAN-07:01 | 0.00 | 0.00 | 64647.89 | 0.00 | 0.00 | 0.00 | 0.00 | 81.78 | 453.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -65183.49 |
CORE_RETAIL | 01-JAN-08:61 | 0.00 | 0.00 | 207751.99 | 0.00 | 0.00 | 0.00 | 0.00 | 344.55 | 765.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -689.96 | 0.00 | -1.55 | -208170.28 |
POINT_OF_SALE | 01-JAN-07:01 | 0.00 | 0.00 | 34696.76 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 480.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1210.37 | 0.00 | 0.00 | -33999.27 |
FRONT_RETAIL | 01-JAN-07:01 | 0.00 | 0.00 | 30762.49 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 72.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1159.08 | 0.00 | 0.00 | -29707.98 |
FRONT_ENTRY | 06-JAN-08:05 | 3325.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 | 27.58 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2387.47 | -968.21 |
Total Facility | 01-JAN-08:61 | 0.00 | 0.00 | 229192.95 | 0.00 | 0.00 | 0.00 | 0.00 | 493.85 | 1771.59 | 12.81 | 0.00 | 0.00 | 0.00 | 0.00 | -1008.20 | 0.00 | -2053.34 | -228409.65 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.7862 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.8502 | 0.0812 | 1.0000 | 0.2316 | 0.0812 | ||
PSZ-AC:2 | 8.3809 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.5234 | 0.2218 | 1.0000 | 1.8902 | 0.2218 | ||
PSZ-AC:3 | 1.5180 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.5180 | 0.1173 | 1.0000 | 0.1781 | 0.1173 | ||
PSZ-AC:4 | 1.3251 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.3251 | 0.1344 | 1.0000 | 0.1781 | 0.1344 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.7862 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.7862 | 1.0000 | 1.0000 | 0.2316 | 0.0831 | ||
PSZ-AC:2 | 8.3809 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.3809 | 1.0000 | 1.0000 | 1.8902 | 0.2255 | ||
PSZ-AC:3 | 1.5180 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.5180 | 1.0000 | 1.0000 | 0.1781 | 0.1173 | ||
PSZ-AC:4 | 1.3251 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.3251 | 1.0000 | 1.0000 | 0.1781 | 0.1344 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.7862 | 2.7862 | 2.7862 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.3809 | 8.3809 | 8.3809 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.5180 | 1.5180 | 1.5180 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.3251 | 1.3251 | 1.3251 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.7862 | 2.8502 | 2.7862 | 2.7862 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.3809 | 8.5234 | 8.3809 | 8.3809 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.5180 | 1.5180 | 1.5180 | 1.5180 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.3251 | 1.3251 | 1.3251 | 1.3251 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.7862 | 2.7862 | 2.7862 | 0.2316 | 0.1959 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.3809 | 8.3809 | 8.3809 | 1.8902 | 0.7414 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.5180 | 1.5180 | 1.5180 | 0.1781 | 0.3254 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.3251 | 1.3251 | 1.3251 | 0.1781 | 0.3257 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.7862 | 2.7862 | 2.7862 | 2.7862 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.3809 | 8.3809 | 8.3809 | 8.3809 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.5180 | 1.5180 | 1.5180 | 1.5180 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.3251 | 1.3251 | 1.3251 | 1.3251 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:12
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 15.39 | 118061.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 590.08 | 85564.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 289.03 | 24449.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 38.47 | 3371.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 194.30 | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 174.02 | 16361.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 85.35 | 4923.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 194.30 | 1285.89 |
Natural Gas | 0.00 | 100.74 |
Additional | 0.00 | 0.00 |
Total | 194.30 | 1386.63 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 125.99 |
Space Heating | 0.00 |
Space Cooling | 257.23 |
Fans (All) | 75.86 |
Service Water Heating | 0.00 |
Receptacle Equipment | 84.70 |
Miscellaneous (All) | 560.55 |
Subtotal | 560.55 |
Natural Gas [MJ/m2] | |
Space Heating | 6.71 |
Service Water Heating | 37.21 |
Miscellaneous (All) | 43.92 |
Subtotal | 43.92 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 20.84 |
Space Heating | 1.11 |
Space Cooling | 42.56 |
Fans (All) | 12.55 |
Service Water Heating | 6.16 |
Receptacle Equipment | 14.01 |
Miscellaneous | 2.77 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 2872. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3001. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3501. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4552. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_FRONTENTRY_STD2013 | FRONT_ENTRY DUALSPSCHED | January | 16.00 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.108416E+11 |
February | 0.000 | 0.158116E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2766515.947 |
December | 0.000 | 0.296185E+10 |
Annual Sum or Average | 0.153873E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108416E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.108416E+11 |
February | 0.000 | 0.158116E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2766515.947 |
December | 0.000 | 0.296185E+10 |
Annual Sum or Average | 0.153873E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108416E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.108416E+11 |
February | 0.000 | 0.158116E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2766515.947 |
December | 0.000 | 0.296185E+10 |
Annual Sum or Average | 0.153873E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108416E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.108416E+11 |
February | 0.000 | 0.158116E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2766515.947 |
December | 0.000 | 0.296185E+10 |
Annual Sum or Average | 0.153873E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108416E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.108416E+11 |
February | 0.000 | 0.158116E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2766515.947 |
December | 0.000 | 0.296185E+10 |
Annual Sum or Average | 0.153873E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108416E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.108416E+11 |
February | 0.000 | 0.158116E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2766515.947 |
December | 0.000 | 0.296185E+10 |
Annual Sum or Average | 0.153873E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108416E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.108416E+11 |
February | 0.000 | 0.158116E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2766515.947 |
December | 0.000 | 0.296185E+10 |
Annual Sum or Average | 0.153873E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108416E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.108416E+11 |
February | 0.000 | 0.158116E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2766515.947 |
December | 0.000 | 0.296185E+10 |
Annual Sum or Average | 0.153873E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108416E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.108416E+11 |
February | 0.000 | 0.158116E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2766515.947 |
December | 0.000 | 0.296185E+10 |
Annual Sum or Average | 0.153873E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108416E+11 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.534476E+09 | 3422.59 | 14-JAN-17:00 | 20.70 | 14.70 | 0.188975E+10 | 2451.34 | 12-JAN-15:09 | 23.55 | 14.23 |
February | 0.231835E+10 | 7223.01 | 24-FEB-16:00 | 26.30 | 17.46 | 0.190462E+10 | 2451.29 | 23-FEB-15:30 | 25.30 | 14.21 |
March | 0.100432E+11 | 51009.80 | 29-MAR-04:01 | 21.45 | 17.79 | 0.227671E+10 | 2451.33 | 30-MAR-14:39 | 30.80 | 19.42 |
April | 0.221123E+11 | 55454.63 | 29-APR-04:01 | 26.47 | 17.99 | 0.215642E+10 | 2451.39 | 28-APR-14:30 | 38.90 | 21.10 |
May | 0.324860E+11 | 55719.27 | 09-MAY-04:01 | 27.65 | 19.15 | 0.223250E+10 | 2451.45 | 06-MAY-11:50 | 39.85 | 19.78 |
June | 0.327531E+11 | 53015.16 | 05-JUN-04:01 | 30.32 | 20.24 | 0.220158E+10 | 2451.40 | 03-JUN-10:30 | 37.25 | 23.36 |
July | 0.320326E+11 | 49154.20 | 07-JUL-04:01 | 31.73 | 26.03 | 0.218723E+10 | 2451.36 | 15-JUL-10:09 | 32.62 | 27.30 |
August | 0.295370E+11 | 48524.44 | 09-AUG-04:01 | 30.32 | 25.71 | 0.228101E+10 | 2451.31 | 05-AUG-11:39 | 34.57 | 26.25 |
September | 0.233064E+11 | 50250.27 | 27-SEP-04:01 | 23.75 | 21.10 | 0.215639E+10 | 2451.31 | 14-SEP-14:30 | 33.80 | 27.53 |
October | 0.167853E+11 | 52732.99 | 02-OCT-04:01 | 21.82 | 17.77 | 0.218400E+10 | 2451.30 | 25-OCT-14:00 | 29.10 | 18.46 |
November | 0.612185E+10 | 46368.67 | 01-NOV-04:01 | 15.75 | 12.60 | 0.208776E+10 | 2451.28 | 01-NOV-14:09 | 28.50 | 15.92 |
December | 0.915907E+09 | 3884.86 | 01-DEC-16:00 | 22.30 | 13.70 | 0.200975E+10 | 2451.25 | 02-DEC-12:20 | 22.77 | 12.89 |
Annual Sum or Average | 0.208946E+12 | 0.255677E+11 | ||||||||
Minimum of Months | 0.534476E+09 | 3422.59 | 15.75 | 12.60 | 0.188975E+10 | 2451.25 | 22.77 | 12.89 | ||
Maximum of Months | 0.327531E+11 | 55719.27 | 31.73 | 26.03 | 0.228101E+10 | 2451.45 | 39.85 | 27.53 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174010E+11 | 33156.08 | 05-JAN-07:05 | 4.93 | 4.82 | 0.855619E+10 | 10327.19 | 27-JAN-15:09 | 16.32 | 12.15 |
February | 0.242081E+11 | 35780.50 | 23-FEB-16:00 | 24.80 | 14.33 | 0.822154E+10 | 10327.20 | 23-FEB-15:00 | 24.80 | 14.33 |
March | 0.464510E+11 | 151672.72 | 30-MAR-06:02 | 21.25 | 16.71 | 0.960078E+10 | 10327.33 | 30-MAR-14:39 | 30.80 | 19.42 |
April | 0.706750E+11 | 181139.50 | 28-APR-05:01 | 27.22 | 17.14 | 0.908823E+10 | 10327.29 | 15-APR-11:00 | 38.00 | 19.29 |
May | 0.878779E+11 | 178942.16 | 06-MAY-04:01 | 30.18 | 17.70 | 0.940931E+10 | 10327.55 | 06-MAY-10:09 | 36.52 | 19.41 |
June | 0.846364E+11 | 163608.73 | 07-JUN-04:01 | 33.27 | 20.22 | 0.927903E+10 | 10327.01 | 24-JUN-13:00 | 25.00 | 24.49 |
July | 0.785326E+11 | 146426.99 | 05-JUL-04:01 | 32.58 | 25.32 | 0.921877E+10 | 10327.06 | 18-JUL-14:00 | 26.30 | 25.64 |
August | 0.742473E+11 | 133405.12 | 07-AUG-05:01 | 29.53 | 24.78 | 0.961377E+10 | 10326.89 | 05-AUG-11:20 | 34.23 | 26.11 |
September | 0.644118E+11 | 144993.36 | 27-SEP-05:02 | 23.08 | 20.68 | 0.908856E+10 | 10326.79 | 08-SEP-14:09 | 28.40 | 25.90 |
October | 0.576279E+11 | 160809.91 | 02-OCT-05:03 | 21.60 | 17.46 | 0.920339E+10 | 10327.31 | 27-OCT-14:09 | 30.78 | 19.08 |
November | 0.366522E+11 | 42836.71 | 09-NOV-15:10 | 29.07 | 17.66 | 0.882047E+10 | 10327.25 | 21-NOV-15:39 | 26.10 | 15.01 |
December | 0.214606E+11 | 31920.56 | 21-DEC-07:05 | 5.68 | 4.75 | 0.885364E+10 | 10327.17 | 09-DEC-12:20 | 17.37 | 12.40 |
Annual Sum or Average | 0.664182E+12 | 0.108954E+12 | ||||||||
Minimum of Months | 0.174010E+11 | 31920.56 | 4.93 | 4.75 | 0.822154E+10 | 10326.79 | 16.32 | 12.15 | ||
Maximum of Months | 0.878779E+11 | 181139.50 | 33.27 | 25.32 | 0.961377E+10 | 10327.55 | 38.00 | 26.11 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.509080E+10 | 8245.83 | 12-JAN-15:50 | 23.35 | 14.42 | 0.843450E+09 | 973.15 | 07-JAN-16:00 | 18.40 | 12.94 |
February | 0.672141E+10 | 27808.33 | 23-FEB-05:02 | 15.08 | 13.21 | 0.783354E+09 | 973.16 | 15-FEB-15:50 | 22.92 | 16.84 |
March | 0.112928E+11 | 30139.02 | 29-MAR-04:01 | 21.45 | 17.79 | 0.905419E+09 | 973.17 | 28-MAR-14:00 | 35.60 | 18.47 |
April | 0.154046E+11 | 30793.86 | 07-APR-04:01 | 21.75 | 15.07 | 0.856055E+09 | 973.23 | 20-APR-14:20 | 36.93 | 19.66 |
May | 0.183090E+11 | 29653.97 | 29-MAY-06:01 | 29.10 | 17.75 | 0.886265E+09 | 973.23 | 06-MAY-11:09 | 38.85 | 19.66 |
June | 0.177518E+11 | 28214.39 | 05-JUN-04:01 | 30.32 | 20.24 | 0.873989E+09 | 973.19 | 02-JUN-14:20 | 38.37 | 20.77 |
July | 0.173868E+11 | 24983.24 | 07-JUL-04:11 | 31.67 | 26.03 | 0.868288E+09 | 973.16 | 22-JUL-13:50 | 29.75 | 26.98 |
August | 0.168089E+11 | 24657.11 | 06-AUG-06:01 | 28.77 | 23.60 | 0.905510E+09 | 973.17 | 26-AUG-10:09 | 30.40 | 28.09 |
September | 0.154492E+11 | 28397.18 | 27-SEP-04:01 | 23.75 | 21.10 | 0.856035E+09 | 973.17 | 30-SEP-10:30 | 31.50 | 23.64 |
October | 0.161357E+11 | 30878.63 | 23-OCT-04:01 | 18.78 | 14.94 | 0.867016E+09 | 973.23 | 16-OCT-14:00 | 33.60 | 19.10 |
November | 0.120322E+11 | 29747.68 | 02-NOV-04:01 | 16.58 | 13.43 | 0.833870E+09 | 973.13 | 04-NOV-10:09 | 24.08 | 16.24 |
December | 0.664957E+10 | 9709.27 | 01-DEC-15:30 | 22.85 | 13.53 | 0.858563E+09 | 973.16 | 16-DEC-16:00 | 20.70 | 15.14 |
Annual Sum or Average | 0.159033E+12 | 0.103378E+11 | ||||||||
Minimum of Months | 0.509080E+10 | 8245.83 | 15.08 | 13.21 | 0.783354E+09 | 973.13 | 18.40 | 12.94 | ||
Maximum of Months | 0.183090E+11 | 30878.63 | 31.67 | 26.03 | 0.905510E+09 | 973.23 | 38.85 | 28.09 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.302849E+10 | 6235.63 | 12-JAN-15:40 | 23.40 | 14.37 | 0.821109E+09 | 973.13 | 25-JAN-15:00 | 22.30 | 13.54 |
February | 0.463059E+10 | 24362.06 | 23-FEB-05:02 | 15.08 | 13.21 | 0.772336E+09 | 973.15 | 24-FEB-15:09 | 26.38 | 17.38 |
March | 0.859499E+10 | 26154.81 | 29-MAR-04:01 | 21.45 | 17.79 | 0.904493E+09 | 973.15 | 28-MAR-14:00 | 35.60 | 18.47 |
April | 0.126933E+11 | 27105.98 | 08-APR-04:01 | 23.47 | 13.96 | 0.856050E+09 | 973.21 | 15-APR-12:30 | 38.70 | 19.53 |
May | 0.154240E+11 | 26575.68 | 29-MAY-06:01 | 29.10 | 17.75 | 0.886258E+09 | 973.19 | 06-MAY-11:09 | 38.85 | 19.66 |
June | 0.147189E+11 | 24847.07 | 05-JUN-04:01 | 30.32 | 20.24 | 0.873987E+09 | 973.16 | 03-JUN-10:09 | 36.82 | 23.31 |
July | 0.144673E+11 | 22073.34 | 07-JUL-04:01 | 31.73 | 26.03 | 0.868290E+09 | 973.15 | 22-JUL-12:00 | 30.50 | 26.90 |
August | 0.138485E+11 | 21937.79 | 09-AUG-04:01 | 30.32 | 25.71 | 0.905510E+09 | 973.14 | 19-AUG-10:39 | 30.50 | 27.27 |
September | 0.126384E+11 | 24576.56 | 27-SEP-04:01 | 23.75 | 21.10 | 0.856032E+09 | 973.12 | 12-SEP-14:09 | 31.00 | 27.45 |
October | 0.133623E+11 | 27022.94 | 23-OCT-04:01 | 18.78 | 14.94 | 0.867001E+09 | 973.20 | 16-OCT-14:39 | 33.47 | 19.01 |
November | 0.941646E+10 | 26032.40 | 02-NOV-04:01 | 16.58 | 13.43 | 0.833081E+09 | 973.13 | 28-NOV-15:00 | 22.70 | 15.30 |
December | 0.434048E+10 | 7813.48 | 01-DEC-15:20 | 23.03 | 13.47 | 0.847122E+09 | 973.14 | 07-DEC-15:00 | 19.20 | 12.65 |
Annual Sum or Average | 0.127164E+12 | 0.102913E+11 | ||||||||
Minimum of Months | 0.302849E+10 | 6235.63 | 15.08 | 13.21 | 0.772336E+09 | 973.12 | 19.20 | 12.65 | ||
Maximum of Months | 0.154240E+11 | 27105.98 | 31.73 | 26.03 | 0.905510E+09 | 973.21 | 38.85 | 27.45 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241079E+10 | 64648.88 | 01-JAN-07:01 | 7.25 |
February | 0.473763E+09 | 62837.31 | 11-FEB-05:02 | 9.03 |
March | 2652245.34 | 582.29 | 27-MAR-05:10 | 20.63 |
April | 226863.39 | 741.39 | 23-APR-07:05 | 22.45 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 21256428.60 | 1510.73 | 26-NOV-12:03 | 24.98 |
December | 0.960903E+09 | 64332.34 | 22-DEC-05:01 | 11.18 |
Annual Sum or Average | 0.386959E+10 | |||
Minimum of Months | 0.00 | 0.00 | 7.25 | |
Maximum of Months | 0.241079E+10 | 64648.88 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105987E+10 | 207756.53 | 01-JAN-08:61 | 8.17 |
February | 0.116509E+09 | 140771.40 | 02-FEB-07:03 | 7.12 |
March | 12335767.81 | 7587.10 | 11-MAR-07:06 | 23.87 |
April | 0.137622E+09 | 22207.92 | 16-APR-08:06 | 30.70 |
May | 0.247981E+09 | 26370.78 | 01-MAY-06:06 | 32.80 |
June | 0.242161E+09 | 25233.33 | 12-JUN-05:06 | 34.12 |
July | 0.245058E+09 | 23118.25 | 02-JUL-07:20 | 33.63 |
August | 0.249309E+09 | 17381.39 | 08-AUG-05:06 | 30.10 |
September | 0.183692E+09 | 13146.00 | 12-SEP-06:08 | 27.02 |
October | 48284924.48 | 10976.90 | 04-OCT-06:06 | 25.52 |
November | 1243680.32 | 1204.23 | 26-NOV-10:05 | 22.08 |
December | 0.215405E+09 | 148449.05 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 0.275948E+10 | |||
Minimum of Months | 1243680.32 | 1204.23 | 6.25 | |
Maximum of Months | 0.105987E+10 | 207756.53 | 34.12 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 99584492.64 | 34697.66 | 01-JAN-07:01 | 7.25 |
February | 15942001.75 | 21585.37 | 11-FEB-05:02 | 9.03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 211541.29 | 417.47 | 23-APR-07:10 | 22.45 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 165132.13 | 1926.54 | 17-JUN-05:04 | 29.32 |
July | 81808.38 | 954.43 | 02-JUL-07:06 | 33.57 |
August | 28927.84 | 337.49 | 08-AUG-05:06 | 30.10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 1114537.46 | 2402.24 | 31-DEC-08:62 | 6.52 |
Annual Sum or Average | 0.117128E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.52 | |
Maximum of Months | 99584492.64 | 34697.66 | 33.57 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229416E+09 | 30763.26 | 01-JAN-07:01 | 7.25 |
February | 42844804.58 | 29998.53 | 11-FEB-05:02 | 9.03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 62081.65 | 206.94 | 23-APR-07:05 | 22.45 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 159303.52 | 1858.54 | 12-JUN-05:06 | 34.12 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 19296273.97 | 17486.62 | 31-DEC-07:02 | 5.53 |
Annual Sum or Average | 0.291779E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.53 | |
Maximum of Months | 0.229416E+09 | 30763.26 | 34.12 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13188443.03 | 3326.50 | 06-JAN-08:05 | 6.67 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 7990793.15 | 3320.79 | 21-DEC-08:05 | 6.25 |
Annual Sum or Average | 21179236.18 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 13188443.03 | 3326.50 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.235462E+10 | 2023.29 | 02-JAN-09:09 | 0.419292E+10 | 2751.42 | 02-JAN-09:09 |
February | 0.214299E+10 | 2023.29 | 01-FEB-09:09 | 0.380401E+10 | 2751.42 | 01-FEB-09:09 |
March | 0.244478E+10 | 2023.29 | 01-MAR-09:09 | 0.429860E+10 | 2751.42 | 01-MAR-09:09 |
April | 0.230724E+10 | 2023.29 | 01-APR-09:09 | 0.408483E+10 | 2751.42 | 01-APR-09:09 |
May | 0.239970E+10 | 2023.29 | 01-MAY-08:09 | 0.424576E+10 | 2751.42 | 01-MAY-08:09 |
June | 0.235921E+10 | 2023.29 | 01-JUN-08:09 | 0.415135E+10 | 2751.42 | 01-JUN-08:09 |
July | 0.234773E+10 | 2023.29 | 01-JUL-09:09 | 0.417924E+10 | 2751.42 | 01-JUL-09:09 |
August | 0.244478E+10 | 2023.29 | 01-AUG-08:09 | 0.429860E+10 | 2751.42 | 01-AUG-08:09 |
September | 0.230724E+10 | 2023.29 | 01-SEP-08:09 | 0.408483E+10 | 2751.42 | 01-SEP-08:09 |
October | 0.235462E+10 | 2023.29 | 02-OCT-08:09 | 0.419292E+10 | 2751.42 | 02-OCT-08:09 |
November | 0.227595E+10 | 2023.29 | 01-NOV-08:09 | 0.405935E+10 | 2751.42 | 01-NOV-08:09 |
December | 0.234773E+10 | 2023.29 | 01-DEC-09:09 | 0.417924E+10 | 2751.42 | 01-DEC-09:09 |
Annual Sum or Average | 0.280866E+11 | 0.497716E+11 | ||||
Minimum of Months | 0.214299E+10 | 2023.29 | 0.380401E+10 | 2751.42 | ||
Maximum of Months | 0.244478E+10 | 2023.29 | 0.429860E+10 | 2751.42 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.194774E+11 | 18915.75 | 02-JAN-15:50 | 0.707031E+10 | 4639.58 | 02-JAN-09:09 |
February | 0.170017E+11 | 18915.75 | 01-FEB-16:10 | 0.641452E+10 | 4639.58 | 01-FEB-09:09 |
March | 0.176566E+11 | 18915.75 | 01-MAR-16:40 | 0.724851E+10 | 4639.58 | 01-MAR-09:09 |
April | 0.173879E+11 | 18915.75 | 01-APR-16:00 | 0.688804E+10 | 4639.58 | 01-APR-09:09 |
May | 0.180112E+11 | 18915.75 | 03-MAY-08:09 | 0.715941E+10 | 4639.58 | 01-MAY-08:09 |
June | 0.172932E+11 | 18915.75 | 15-JUN-16:00 | 0.700021E+10 | 4639.58 | 01-JUN-08:09 |
July | 0.162552E+11 | 18915.75 | 10-JUL-16:49 | 0.704724E+10 | 4639.58 | 01-JUL-09:09 |
August | 0.170058E+11 | 18915.75 | 10-AUG-16:40 | 0.724851E+10 | 4639.58 | 01-AUG-08:09 |
September | 0.163624E+11 | 18915.75 | 02-SEP-16:00 | 0.688804E+10 | 4639.58 | 01-SEP-08:09 |
October | 0.183085E+11 | 18915.75 | 02-OCT-16:30 | 0.707031E+10 | 4639.58 | 02-OCT-08:09 |
November | 0.189173E+11 | 18915.75 | 01-NOV-08:09 | 0.684509E+10 | 4639.58 | 01-NOV-08:09 |
December | 0.195819E+11 | 18915.75 | 01-DEC-15:30 | 0.704724E+10 | 4639.58 | 01-DEC-09:09 |
Annual Sum or Average | 0.213259E+12 | 0.839274E+11 | ||||
Minimum of Months | 0.162552E+11 | 18915.75 | 0.641452E+10 | 4639.58 | ||
Maximum of Months | 0.195819E+11 | 18915.75 | 0.724851E+10 | 4639.58 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.202570E+10 | 1782.39 | 02-JAN-09:09 | 0.443872E+10 | 2912.71 | 02-JAN-09:09 |
February | 0.184426E+10 | 1782.39 | 01-FEB-09:09 | 0.402701E+10 | 2912.71 | 01-FEB-09:09 |
March | 0.210616E+10 | 1782.39 | 01-MAR-09:09 | 0.455059E+10 | 2912.71 | 01-MAR-09:09 |
April | 0.198616E+10 | 1782.39 | 01-APR-09:09 | 0.432429E+10 | 2912.71 | 01-APR-09:09 |
May | 0.206593E+10 | 1782.39 | 01-MAY-08:09 | 0.449465E+10 | 2912.71 | 01-MAY-08:09 |
June | 0.203227E+10 | 1782.39 | 01-JUN-08:09 | 0.439471E+10 | 2912.71 | 01-JUN-08:09 |
July | 0.201982E+10 | 1782.39 | 01-JUL-09:09 | 0.442423E+10 | 2912.71 | 01-JUL-09:09 |
August | 0.210616E+10 | 1782.39 | 01-AUG-08:09 | 0.455059E+10 | 2912.71 | 01-AUG-08:09 |
September | 0.198616E+10 | 1782.39 | 01-SEP-08:09 | 0.432429E+10 | 2912.71 | 01-SEP-08:09 |
October | 0.202570E+10 | 1782.39 | 02-OCT-08:09 | 0.443872E+10 | 2912.71 | 02-OCT-08:09 |
November | 0.195769E+10 | 1782.39 | 01-NOV-08:09 | 0.429732E+10 | 2912.71 | 01-NOV-08:09 |
December | 0.201982E+10 | 1782.39 | 01-DEC-09:09 | 0.442423E+10 | 2912.71 | 01-DEC-09:09 |
Annual Sum or Average | 0.241758E+11 | 0.526893E+11 | ||||
Minimum of Months | 0.184426E+10 | 1782.39 | 0.402701E+10 | 2912.71 | ||
Maximum of Months | 0.210616E+10 | 1782.39 | 0.455059E+10 | 2912.71 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.196268E+10 | 1725.71 | 02-JAN-09:09 | 0.666220E+09 | 437.18 | 02-JAN-09:09 |
February | 0.178687E+10 | 1725.71 | 01-FEB-09:09 | 0.604426E+09 | 437.18 | 01-FEB-09:09 |
March | 0.204057E+10 | 1725.71 | 01-MAR-09:09 | 0.683011E+09 | 437.18 | 01-MAR-09:09 |
April | 0.192434E+10 | 1725.71 | 01-APR-09:09 | 0.649045E+09 | 437.18 | 01-APR-09:09 |
May | 0.200162E+10 | 1725.71 | 01-MAY-08:09 | 0.674616E+09 | 437.18 | 01-MAY-08:09 |
June | 0.196898E+10 | 1725.71 | 01-JUN-08:09 | 0.659615E+09 | 437.18 | 01-JUN-08:09 |
July | 0.195698E+10 | 1725.71 | 01-JUL-09:09 | 0.664046E+09 | 437.18 | 01-JUL-09:09 |
August | 0.204057E+10 | 1725.71 | 01-AUG-08:09 | 0.683011E+09 | 437.18 | 01-AUG-08:09 |
September | 0.192434E+10 | 1725.71 | 01-SEP-08:09 | 0.649045E+09 | 437.18 | 01-SEP-08:09 |
October | 0.196268E+10 | 1725.71 | 02-OCT-08:09 | 0.666220E+09 | 437.18 | 02-OCT-08:09 |
November | 0.189680E+10 | 1725.71 | 01-NOV-08:09 | 0.644998E+09 | 437.18 | 01-NOV-08:09 |
December | 0.195698E+10 | 1725.71 | 01-DEC-09:09 | 0.664046E+09 | 437.18 | 01-DEC-09:09 |
Annual Sum or Average | 0.234234E+11 | 0.790830E+10 | ||||
Minimum of Months | 0.178687E+10 | 1725.71 | 0.604426E+09 | 437.18 | ||
Maximum of Months | 0.204057E+10 | 1725.71 | 0.683011E+09 | 437.18 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 6919213.84 | 2.58 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 6249612.50 | 2.58 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 6919213.84 | 2.58 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 6696013.39 | 2.58 | 01-APR-00:10 | 0.00 | 0.00 |
May | 6919213.84 | 2.58 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 6696013.39 | 2.58 | 01-JUN-00:10 | 0.00 | 0.00 |
July | 6919213.84 | 2.58 | 01-JUL-00:10 | 0.00 | 0.00 |
August | 6919213.84 | 2.58 | 01-AUG-00:10 | 0.00 | 0.00 |
September | 6696013.39 | 2.58 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 6919213.84 | 2.58 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 6696013.39 | 2.58 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 6919213.84 | 2.58 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 81468162.94 | ||||
Minimum of Months | 6249612.50 | 2.58 | 0.00 | 0.00 | |
Maximum of Months | 6919213.84 | 2.58 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.235462E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17428.56 | 0.164555E+09 |
February | 0.479114E+10 | 0.214299E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3304690.98 | 0.203555E+09 |
March | 0.548013E+10 | 0.244478E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41062511.12 | 0.160579E+09 |
April | 0.518069E+10 | 0.230724E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156488E+09 | 17431557.80 |
May | 0.536353E+10 | 0.239970E+10 | 0.424576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288474E+09 | 16570472.79 |
June | 0.528933E+10 | 0.235921E+10 | 0.415135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220844E+09 | 4928224.39 |
July | 0.525489E+10 | 0.234773E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250513E+09 | 5498184.09 |
August | 0.548013E+10 | 0.244478E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147890E+09 | 8719838.39 |
September | 0.518069E+10 | 0.230724E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96236270.47 | 10133468.59 |
October | 0.524694E+10 | 0.235462E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48050032.75 | 15502993.40 |
November | 0.504819E+10 | 0.227595E+10 | 0.405935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11510118.74 | 47965210.28 |
December | 0.525489E+10 | 0.234773E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 368732.42 | 0.163537E+09 |
Annual Sum or Average | 0.628175E+11 | 0.280866E+11 | 0.497716E+11 | 0.126476E+10 | 0.818976E+09 | ||||
Minimum of Months | 0.479114E+10 | 0.214299E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17428.56 | 4928224.39 |
Maximum of Months | 0.548013E+10 | 0.244478E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288474E+09 | 0.203555E+09 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.194774E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157756E+09 |
February | 0.201852E+11 | 0.170017E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2656648.93 | 0.189330E+09 |
March | 0.230879E+11 | 0.176566E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33763564.87 | 0.144150E+09 |
April | 0.218263E+11 | 0.173879E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128562E+09 | 14621001.64 |
May | 0.225967E+11 | 0.180112E+11 | 0.715941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244194E+09 | 8622645.49 |
June | 0.222841E+11 | 0.172932E+11 | 0.700021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189240E+09 | 3452582.09 |
July | 0.221389E+11 | 0.162552E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223222E+09 | 2277223.73 |
August | 0.230879E+11 | 0.170058E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129284E+09 | 3409278.52 |
September | 0.218263E+11 | 0.163624E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79285282.43 | 5334675.40 |
October | 0.221054E+11 | 0.183085E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39488373.14 | 12748445.88 |
November | 0.212681E+11 | 0.189173E+11 | 0.684509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9400809.47 | 43434799.14 |
December | 0.221389E+11 | 0.195819E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89628.16 | 0.154924E+09 |
Annual Sum or Average | 0.264651E+12 | 0.213259E+12 | 0.839274E+11 | 0.107919E+10 | 0.740060E+09 | ||||
Minimum of Months | 0.201852E+11 | 0.162552E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2277223.73 |
Maximum of Months | 0.230879E+11 | 0.195819E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244194E+09 | 0.189330E+09 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.202570E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90151492.78 |
February | 0.190200E+10 | 0.184426E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1406108.66 | 0.106612E+09 |
March | 0.217552E+10 | 0.210616E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17265531.11 | 91846590.60 |
April | 0.205665E+10 | 0.198616E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66045948.03 | 12265235.03 |
May | 0.212923E+10 | 0.206593E+10 | 0.449465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122925E+09 | 9951222.94 |
June | 0.209978E+10 | 0.203227E+10 | 0.439471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93646826.18 | 2549577.99 |
July | 0.208610E+10 | 0.201982E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104662E+09 | 3707228.37 |
August | 0.217552E+10 | 0.210616E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61592300.91 | 6180700.93 |
September | 0.205665E+10 | 0.198616E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40744628.37 | 7601870.68 |
October | 0.208295E+10 | 0.202570E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20380129.45 | 9082125.56 |
November | 0.200405E+10 | 0.195769E+10 | 0.429732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4976885.67 | 25843947.57 |
December | 0.208610E+10 | 0.201982E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47420.34 | 88570684.35 |
Annual Sum or Average | 0.249375E+11 | 0.241758E+11 | 0.526893E+11 | 0.533693E+09 | 0.454363E+09 | ||||
Minimum of Months | 0.190200E+10 | 0.184426E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2549577.99 |
Maximum of Months | 0.217552E+10 | 0.210616E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122925E+09 | 0.106612E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.196268E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84797669.31 |
February | 0.190200E+10 | 0.178687E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1406183.36 | 0.100481E+09 |
March | 0.217552E+10 | 0.204057E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17315428.01 | 84167535.91 |
April | 0.205665E+10 | 0.192434E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66408586.15 | 10047848.79 |
May | 0.212923E+10 | 0.200162E+10 | 0.674616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124252E+09 | 7244009.38 |
June | 0.209978E+10 | 0.196898E+10 | 0.659615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95693143.97 | 1843639.62 |
July | 0.208610E+10 | 0.195698E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108435E+09 | 2051124.42 |
August | 0.217552E+10 | 0.204057E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63173777.75 | 3956784.61 |
September | 0.205665E+10 | 0.192434E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41089836.83 | 5302614.59 |
October | 0.208295E+10 | 0.196268E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20436930.81 | 8216033.72 |
November | 0.200405E+10 | 0.189680E+10 | 0.644998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4976769.69 | 24785053.59 |
December | 0.208610E+10 | 0.195698E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47399.49 | 84121422.81 |
Annual Sum or Average | 0.249375E+11 | 0.234234E+11 | 0.790830E+10 | 0.543235E+09 | 0.417015E+09 | ||||
Minimum of Months | 0.190200E+10 | 0.178687E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1843639.62 |
Maximum of Months | 0.217552E+10 | 0.204057E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124252E+09 | 0.100481E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126387E+10 |
February | 0.00 | 6249612.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786765E+09 |
March | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45290121.74 | 0.368057E+09 |
April | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536500E+09 | 48428384.69 |
May | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105189E+10 | 12432799.17 |
June | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.966520E+09 | 16092973.04 |
July | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519618E+09 | 16211951.07 |
August | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323495E+09 | 36304414.75 |
September | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199172E+09 | 39700988.43 |
October | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38024060.94 | 0.279805E+09 |
November | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.798868E+09 |
December | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130855E+10 |
Annual Sum or Average | 0.00 | 81468162.94 | 0.368051E+10 | 0.497509E+10 | |||||
Minimum of Months | 0.00 | 6249612.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12432799.17 |
Maximum of Months | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105189E+10 | 0.130855E+10 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2023.29 | 02-JAN-09:09 | 2751.42 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 | 08-JAN-15:00 | 481.27 | 15-JAN-19:10 |
February | 5888.82 | 01-FEB-15:09 | 2023.29 | 01-FEB-09:09 | 2751.42 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.09 | 19-FEB-15:00 | 945.76 | 09-FEB-21:10 |
March | 5888.82 | 01-MAR-15:09 | 2023.29 | 01-MAR-09:09 | 2751.42 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 340.31 | 26-MAR-18:02 | 1721.44 | 24-MAR-24:00 |
April | 5888.82 | 01-APR-10:09 | 2023.29 | 01-APR-09:09 | 2751.42 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 647.77 | 02-APR-18:02 | 201.93 | 04-APR-24:00 |
May | 5888.82 | 01-MAY-14:09 | 2023.29 | 01-MAY-08:09 | 2751.42 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.52 | 28-MAY-18:01 | 273.08 | 15-MAY-03:00 |
June | 5888.82 | 01-JUN-14:09 | 2023.29 | 01-JUN-08:09 | 2751.42 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 919.75 | 17-JUN-21:02 | 213.28 | 18-JUN-02:00 |
July | 5888.82 | 01-JUL-10:09 | 2023.29 | 01-JUL-09:09 | 2751.42 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 694.61 | 03-JUL-04:20 | 151.70 | 19-JUL-03:00 |
August | 5888.82 | 01-AUG-14:09 | 2023.29 | 01-AUG-08:09 | 2751.42 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 432.55 | 31-AUG-04:09 | 239.69 | 15-AUG-23:40 |
September | 5888.82 | 01-SEP-14:09 | 2023.29 | 01-SEP-08:09 | 2751.42 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 265.76 | 02-SEP-21:02 | 79.68 | 08-SEP-21:30 |
October | 5888.82 | 02-OCT-14:09 | 2023.29 | 02-OCT-08:09 | 2751.42 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 255.57 | 03-OCT-15:00 | 269.74 | 12-OCT-03:00 |
November | 5888.82 | 01-NOV-14:09 | 2023.29 | 01-NOV-08:09 | 2751.42 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.04 | 13-NOV-14:00 | 361.61 | 29-NOV-24:00 |
December | 5888.82 | 01-DEC-15:09 | 2023.29 | 01-DEC-09:09 | 2751.42 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.39 | 24-DEC-14:00 | 751.56 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 | 79.68 | |||||
Maximum of Months | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.52 | 1721.44 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 18915.75 | 02-JAN-15:50 | 4639.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 426.78 | 15-JAN-19:30 |
February | 24809.68 | 01-FEB-15:09 | 18915.75 | 01-FEB-16:10 | 4639.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.45 | 19-FEB-15:00 | 837.30 | 09-FEB-21:10 |
March | 24809.68 | 01-MAR-15:09 | 18915.75 | 01-MAR-16:40 | 4639.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 278.71 | 26-MAR-18:02 | 1700.14 | 24-MAR-24:00 |
April | 24809.68 | 01-APR-10:09 | 18915.75 | 01-APR-16:00 | 4639.58 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 534.68 | 02-APR-18:02 | 159.14 | 10-APR-05:00 |
May | 24809.68 | 01-MAY-14:09 | 18915.75 | 03-MAY-08:09 | 4639.58 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 918.91 | 28-MAY-18:01 | 174.33 | 15-MAY-03:00 |
June | 24809.68 | 01-JUN-14:09 | 18915.75 | 15-JUN-16:00 | 4639.58 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 764.42 | 17-JUN-21:02 | 150.80 | 18-JUN-04:00 |
July | 24809.68 | 01-JUL-10:09 | 18915.75 | 10-JUL-16:49 | 4639.58 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 515.00 | 20-JUL-20:02 | 111.56 | 19-JUL-03:00 |
August | 24809.68 | 01-AUG-14:09 | 18915.75 | 10-AUG-16:40 | 4639.58 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.97 | 15-AUG-20:02 | 149.30 | 15-AUG-24:00 |
September | 24809.68 | 01-SEP-14:09 | 18915.75 | 02-SEP-16:00 | 4639.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 223.20 | 02-SEP-21:02 | 84.91 | 19-SEP-05:00 |
October | 24809.68 | 02-OCT-14:09 | 18915.75 | 02-OCT-16:30 | 4639.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 209.20 | 03-OCT-15:00 | 220.97 | 12-OCT-03:00 |
November | 24809.68 | 01-NOV-14:09 | 18915.75 | 01-NOV-08:09 | 4639.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.96 | 13-NOV-14:00 | 347.15 | 28-NOV-05:02 |
December | 24809.68 | 01-DEC-15:09 | 18915.75 | 01-DEC-15:30 | 4639.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 | 28-DEC-14:00 | 775.32 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 18915.75 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.91 | |||||
Maximum of Months | 24809.68 | 18915.75 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 918.91 | 1700.14 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1782.39 | 02-JAN-09:09 | 2912.71 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 230.42 | 12-JAN-04:00 |
February | 2337.76 | 01-FEB-15:09 | 1782.39 | 01-FEB-09:09 | 2912.71 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 19-FEB-15:00 | 448.44 | 09-FEB-21:10 |
March | 2337.76 | 01-MAR-15:09 | 1782.39 | 01-MAR-09:09 | 2912.71 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.36 | 26-MAR-18:02 | 1037.85 | 24-MAR-23:00 |
April | 2337.76 | 01-APR-10:09 | 1782.39 | 01-APR-09:09 | 2912.71 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 274.93 | 30-APR-18:01 | 131.28 | 04-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 1782.39 | 01-MAY-08:09 | 2912.71 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 478.56 | 28-MAY-18:01 | 138.74 | 15-MAY-03:00 |
June | 2337.76 | 01-JUN-14:09 | 1782.39 | 01-JUN-08:09 | 2912.71 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 395.99 | 17-JUN-21:02 | 97.45 | 18-JUN-01:50 |
July | 2337.76 | 01-JUL-10:09 | 1782.39 | 01-JUL-09:09 | 2912.71 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 301.55 | 03-JUL-04:14 | 71.67 | 19-JUL-03:00 |
August | 2337.76 | 01-AUG-14:09 | 1782.39 | 01-AUG-08:09 | 2912.71 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 187.26 | 31-AUG-04:08 | 117.28 | 15-AUG-23:00 |
September | 2337.76 | 01-SEP-14:09 | 1782.39 | 01-SEP-08:09 | 2912.71 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.78 | 02-SEP-21:02 | 45.43 | 08-SEP-21:30 |
October | 2337.76 | 02-OCT-14:09 | 1782.39 | 02-OCT-08:09 | 2912.71 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.75 | 03-OCT-15:00 | 134.33 | 12-OCT-03:00 |
November | 2337.76 | 01-NOV-14:09 | 1782.39 | 01-NOV-08:09 | 2912.71 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.75 | 13-NOV-14:00 | 229.09 | 29-NOV-24:00 |
December | 2337.76 | 01-DEC-15:09 | 1782.39 | 01-DEC-09:09 | 2912.71 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 | 28-DEC-14:00 | 389.74 | 29-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1782.39 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.43 | |||||
Maximum of Months | 2337.76 | 1782.39 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 478.56 | 1037.85 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1725.71 | 02-JAN-09:09 | 437.18 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 223.67 | 26-JAN-21:10 |
February | 2337.76 | 01-FEB-15:09 | 1725.71 | 01-FEB-09:09 | 437.18 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 19-FEB-15:00 | 394.59 | 09-FEB-21:10 |
March | 2337.76 | 01-MAR-15:09 | 1725.71 | 01-MAR-09:09 | 437.18 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 137.98 | 26-MAR-18:02 | 937.66 | 24-MAR-23:00 |
April | 2337.76 | 01-APR-10:09 | 1725.71 | 01-APR-09:09 | 437.18 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 276.17 | 02-APR-18:02 | 110.03 | 04-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 1725.71 | 01-MAY-08:09 | 437.18 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 479.61 | 28-MAY-18:01 | 114.47 | 15-MAY-03:00 |
June | 2337.76 | 01-JUN-14:09 | 1725.71 | 01-JUN-08:09 | 437.18 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 397.76 | 17-JUN-21:02 | 80.22 | 18-JUN-02:00 |
July | 2337.76 | 01-JUL-10:09 | 1725.71 | 01-JUL-09:09 | 437.18 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 301.31 | 03-JUL-04:28 | 58.71 | 19-JUL-03:00 |
August | 2337.76 | 01-AUG-14:09 | 1725.71 | 01-AUG-08:09 | 437.18 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 188.68 | 31-AUG-04:08 | 105.09 | 15-AUG-23:20 |
September | 2337.76 | 01-SEP-14:09 | 1725.71 | 01-SEP-08:09 | 437.18 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.79 | 02-SEP-21:02 | 36.49 | 19-SEP-04:00 |
October | 2337.76 | 02-OCT-14:09 | 1725.71 | 02-OCT-08:09 | 437.18 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.75 | 03-OCT-15:00 | 118.99 | 12-OCT-03:00 |
November | 2337.76 | 01-NOV-14:09 | 1725.71 | 01-NOV-08:09 | 437.18 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.75 | 13-NOV-14:00 | 213.19 | 29-NOV-24:00 |
December | 2337.76 | 01-DEC-15:09 | 1725.71 | 01-DEC-09:09 | 437.18 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 | 28-DEC-14:00 | 362.74 | 29-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1725.71 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.49 | |||||
Maximum of Months | 2337.76 | 1725.71 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 479.61 | 937.66 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3744.23 | 27-JAN-12:01 |
February | 0.00 | 01-FEB-00:10 | 2.58 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2704.38 | 09-FEB-12:02 |
March | 0.00 | 01-MAR-00:10 | 2.58 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1019.96 | 28-MAR-11:02 | 1954.99 | 16-MAR-07:01 |
April | 0.00 | 01-APR-00:10 | 2.58 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.44 | 16-APR-11:01 | 1284.55 | 05-APR-07:01 |
May | 0.00 | 01-MAY-00:10 | 2.58 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4837.82 | 03-MAY-11:01 | 721.87 | 31-MAY-16:53 |
June | 0.00 | 01-JUN-00:10 | 2.58 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4698.74 | 05-JUN-11:01 | 1262.27 | 27-JUN-11:02 |
July | 0.00 | 01-JUL-00:10 | 2.58 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2949.10 | 01-JUL-11:01 | 887.01 | 18-JUL-11:03 |
August | 0.00 | 01-AUG-00:10 | 2.58 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1645.55 | 05-AUG-11:02 | 730.77 | 16-AUG-07:02 |
September | 0.00 | 01-SEP-00:10 | 2.58 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1341.55 | 11-SEP-11:02 | 896.94 | 29-SEP-15:55 |
October | 0.00 | 01-OCT-00:10 | 2.58 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1121.47 | 02-OCT-11:02 | 2033.52 | 30-OCT-07:01 |
November | 0.00 | 01-NOV-00:10 | 2.58 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2671.79 | 30-NOV-12:02 |
December | 0.00 | 01-DEC-00:10 | 2.58 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5325.89 | 21-DEC-12:01 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.87 | ||||
Maximum of Months | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4837.82 | 5325.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3422.59 | 14-JAN-17:00 | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.72 |
February | 7223.01 | 24-FEB-16:00 | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 0.00 |
March | 51009.80 | 29-MAR-04:01 | 0.00 | 817.82 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 55454.63 | 29-APR-04:01 | 0.00 | 817.82 | 4538.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55719.27 | 09-MAY-04:01 | 0.00 | 817.82 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 53015.16 | 05-JUN-04:01 | 0.00 | 817.82 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 49154.20 | 07-JUL-04:01 | 0.00 | 817.82 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 48524.44 | 09-AUG-04:01 | 0.00 | 817.82 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 19.56 | 0.00 |
September | 50250.27 | 27-SEP-04:01 | 0.00 | 817.82 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 52732.99 | 02-OCT-04:01 | 0.00 | 817.82 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 46368.67 | 01-NOV-04:01 | 0.00 | 736.04 | 5445.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.40 |
December | 3884.86 | 01-DEC-16:00 | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3422.59 | 0.00 | 736.04 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55719.27 | 5888.82 | 2023.29 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 53.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33156.08 | 05-JAN-07:05 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35780.50 | 23-FEB-16:00 | 24809.68 | 17339.43 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 | 0.00 |
March | 151672.72 | 30-MAR-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 |
April | 181139.50 | 28-APR-05:01 | 0.00 | 2411.84 | 7142.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 0.00 |
May | 178942.16 | 06-MAY-04:01 | 0.00 | 3445.49 | 7652.47 | 0.00 | 0.00 | 0.00 | 0.00 | 48.88 | 0.00 |
June | 163608.73 | 07-JUN-04:01 | 0.00 | 3445.49 | 10203.29 | 0.00 | 0.00 | 0.00 | 0.00 | 137.85 | 0.00 |
July | 146426.99 | 05-JUL-04:01 | 0.00 | 3445.49 | 10203.29 | 0.00 | 0.00 | 0.00 | 0.00 | 110.54 | 0.00 |
August | 133405.12 | 07-AUG-05:01 | 0.00 | 2756.39 | 8162.63 | 0.00 | 0.00 | 0.00 | 0.00 | 9.55 | 0.00 |
September | 144993.36 | 27-SEP-05:02 | 0.00 | 1722.75 | 5101.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
October | 160809.91 | 02-OCT-05:03 | 0.00 | 1378.20 | 4081.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
November | 42836.71 | 09-NOV-15:10 | 24809.68 | 17339.43 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 0.00 |
December | 31920.56 | 21-DEC-07:05 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 |
Annual Sum or Average | |||||||||||
Minimum of Months | 31920.56 | 0.00 | 1378.20 | 4081.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 181139.50 | 24809.68 | 17339.43 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 137.85 | 29.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8245.83 | 12-JAN-15:50 | 2337.76 | 1782.39 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 |
February | 27808.33 | 23-FEB-05:02 | 0.00 | 194.80 | 3843.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
March | 30139.02 | 29-MAR-04:01 | 0.00 | 324.66 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30793.86 | 07-APR-04:01 | 0.00 | 324.66 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 |
May | 29653.97 | 29-MAY-06:01 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 0.00 |
June | 28214.39 | 05-JUN-04:01 | 0.00 | 324.66 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24983.24 | 07-JUL-04:11 | 0.00 | 324.66 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24657.11 | 06-AUG-06:01 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
September | 28397.18 | 27-SEP-04:01 | 0.00 | 324.66 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30878.63 | 23-OCT-04:01 | 0.00 | 324.66 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.94 |
November | 29747.68 | 02-NOV-04:01 | 0.00 | 292.19 | 5765.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.78 |
December | 9709.27 | 01-DEC-15:30 | 2337.76 | 1782.39 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.25 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8245.83 | 0.00 | 194.80 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30878.63 | 2337.76 | 1782.39 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 44.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6235.63 | 12-JAN-15:40 | 2337.76 | 1725.71 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 |
February | 24362.06 | 23-FEB-05:02 | 0.00 | 194.80 | 576.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 |
March | 26154.81 | 29-MAR-04:01 | 0.00 | 324.66 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27105.98 | 08-APR-04:01 | 0.00 | 324.66 | 721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.56 |
May | 26575.68 | 29-MAY-06:01 | 0.00 | 324.66 | 721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 | 0.00 |
June | 24847.07 | 05-JUN-04:01 | 0.00 | 324.66 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22073.34 | 07-JUL-04:01 | 0.00 | 324.66 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21937.79 | 09-AUG-04:01 | 0.00 | 324.66 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 0.00 |
September | 24576.56 | 27-SEP-04:01 | 0.00 | 324.66 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27022.94 | 23-OCT-04:01 | 0.00 | 324.66 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 |
November | 26032.40 | 02-NOV-04:01 | 0.00 | 292.19 | 865.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.34 |
December | 7813.48 | 01-DEC-15:20 | 2337.76 | 1725.71 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6235.63 | 0.00 | 194.80 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27105.98 | 2337.76 | 1725.71 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 | 52.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 | 0.00 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.24 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 | 5.72 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.628579E+11 | 57322.61 | 12-JAN-15:00 | 0.185268E+11 | 119921.28 | 02-JAN-07:10 |
February | 0.639514E+11 | 68197.43 | 24-FEB-16:40 | 0.848073E+10 | 68183.93 | 11-FEB-07:10 |
March | 0.893821E+11 | 85601.27 | 28-MAR-15:00 | 0.752501E+10 | 4891.86 | 01-MAR-12:09 |
April | 0.112512E+12 | 105911.90 | 28-APR-15:30 | 0.703336E+10 | 4839.60 | 03-APR-11:09 |
May | 0.143171E+12 | 123005.92 | 30-MAY-15:50 | 0.704845E+10 | 4789.01 | 01-MAY-11:30 |
June | 0.148007E+12 | 135229.96 | 10-JUN-15:00 | 0.668031E+10 | 4741.24 | 01-JUN-11:50 |
July | 0.147007E+12 | 128408.92 | 01-JUL-16:49 | 0.679215E+10 | 4713.07 | 03-JUL-11:30 |
August | 0.143145E+12 | 118114.34 | 07-AUG-14:00 | 0.688993E+10 | 4735.46 | 31-AUG-11:20 |
September | 0.123639E+12 | 108039.35 | 14-SEP-16:00 | 0.679221E+10 | 4777.72 | 29-SEP-11:20 |
October | 0.105596E+12 | 97754.16 | 03-OCT-15:09 | 0.720783E+10 | 4834.62 | 31-OCT-11:00 |
November | 0.810451E+11 | 76144.40 | 08-NOV-15:50 | 0.718688E+10 | 5407.92 | 27-NOV-06:49 |
December | 0.655747E+11 | 60086.52 | 01-DEC-15:30 | 0.105774E+11 | 80993.51 | 23-DEC-07:10 |
Annual Sum or Average | 0.128589E+13 | 0.100741E+12 | ||||
Minimum of Months | 0.628579E+11 | 57322.61 | 0.668031E+10 | 4713.07 | ||
Maximum of Months | 0.148007E+12 | 135229.96 | 0.185268E+11 | 119921.28 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.258274E+11 | 0.385863E+10 | 0.163682E+11 | 0.00 | 0.134434E+11 | 0.00 | 0.00 | 0.336035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227820E+11 | 0.329241E+10 | 0.148500E+11 | 0.00 | 0.119711E+11 | 0.00 | 0.00 | 0.110559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242550E+11 | 0.333273E+10 | 0.167807E+11 | 0.00 | 0.134278E+11 | 0.00 | 0.00 | 0.315859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.236123E+11 | 0.291946E+10 | 0.159462E+11 | 0.00 | 0.135067E+11 | 0.00 | 0.00 | 0.565273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.244854E+11 | 0.274816E+10 | 0.165744E+11 | 0.00 | 0.163031E+11 | 0.00 | 0.00 | 0.830603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.236603E+11 | 0.251492E+10 | 0.162059E+11 | 0.00 | 0.173025E+11 | 0.00 | 0.00 | 0.883237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.225866E+11 | 0.267737E+10 | 0.163148E+11 | 0.00 | 0.174856E+11 | 0.00 | 0.00 | 0.879426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.236043E+11 | 0.289380E+10 | 0.167807E+11 | 0.00 | 0.168513E+11 | 0.00 | 0.00 | 0.830146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.225869E+11 | 0.309342E+10 | 0.159462E+11 | 0.00 | 0.143411E+11 | 0.00 | 0.00 | 0.676717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.246584E+11 | 0.351477E+10 | 0.163682E+11 | 0.00 | 0.134482E+11 | 0.00 | 0.00 | 0.476069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250544E+11 | 0.366585E+10 | 0.158468E+11 | 0.00 | 0.126867E+11 | 0.00 | 0.00 | 0.237913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.259134E+11 | 0.395370E+10 | 0.163148E+11 | 0.00 | 0.132498E+11 | 0.00 | 0.00 | 0.614305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289026E+12 | 0.384652E+11 | 0.194297E+12 | 0.174017E+12 | 0.00 | 0.590083E+12 | |||||||
Minimum of Months | 0.225866E+11 | 0.251492E+10 | 0.148500E+11 | 0.00 | 0.119711E+11 | 0.00 | 0.00 | 0.336035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.259134E+11 | 0.395370E+10 | 0.167807E+11 | 0.00 | 0.174856E+11 | 0.00 | 0.00 | 0.883237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.108416E+11 | 0.00 | 0.768526E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.158116E+10 | 0.00 | 0.689957E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.752501E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.703336E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.704845E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.668031E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.679215E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.688993E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.679221E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.720783E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2766515.95 | 0.00 | 0.718412E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.296185E+10 | 0.00 | 0.761558E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.153873E+11 | 0.853538E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.668031E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.108416E+11 | 0.00 | 0.768526E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 24449.72 | 02-JAN-15:50 | 3371.20 | 01-JAN-06:10 | 10740.89 | 02-JAN-09:09 | 0.00 | 11570.81 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 24449.72 | 01-FEB-16:10 | 3371.20 | 01-FEB-06:10 | 10740.89 | 01-FEB-09:09 | 0.00 | 10110.17 | 02-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 24449.72 | 01-MAR-16:40 | 3371.20 | 01-MAR-06:10 | 10740.89 | 01-MAR-09:09 | 0.00 | 10354.18 | 12-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 24449.72 | 01-APR-16:00 | 3371.20 | 01-APR-05:10 | 10740.89 | 01-APR-09:09 | 0.00 | 11646.53 | 16-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 24449.72 | 03-MAY-08:09 | 3371.20 | 01-MAY-05:10 | 10740.89 | 01-MAY-08:09 | 0.00 | 14446.82 | 30-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 24449.72 | 15-JUN-16:00 | 3371.20 | 01-JUN-05:10 | 10740.89 | 01-JUN-08:09 | 0.00 | 16051.40 | 10-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 24449.72 | 10-JUL-16:49 | 3371.20 | 01-JUL-05:10 | 10740.89 | 01-JUL-09:09 | 0.00 | 16361.39 | 01-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 24449.72 | 10-AUG-16:40 | 3371.20 | 01-AUG-05:10 | 10740.89 | 01-AUG-08:09 | 0.00 | 14372.28 | 07-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 24449.72 | 02-SEP-16:00 | 3371.20 | 01-SEP-05:10 | 10740.89 | 01-SEP-08:09 | 0.00 | 12576.79 | 01-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 24449.72 | 02-OCT-16:30 | 3371.20 | 01-OCT-05:10 | 10740.89 | 02-OCT-08:09 | 0.00 | 11646.53 | 04-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 24449.72 | 01-NOV-08:09 | 3371.20 | 01-NOV-05:10 | 10740.89 | 01-NOV-08:09 | 0.00 | 8267.43 | 09-NOV-15:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 24449.72 | 01-DEC-15:30 | 3371.20 | 01-DEC-06:10 | 10740.89 | 01-DEC-09:09 | 0.00 | 10480.90 | 23-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 24449.72 | 3371.20 | 10740.89 | 0.00 | 8267.43 | 0.00 | 0.00 | |||||
Maximum of Months | 24449.72 | 3371.20 | 10740.89 | 0.00 | 16361.39 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 13931.74 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25811.25 | 24-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43529.70 | 28-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 62001.30 | 28-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76223.21 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85564.27 | 10-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81381.48 | 01-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 73280.39 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 62914.40 | 14-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 54930.13 | 03-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33039.69 | 09-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16775.91 | 01-DEC-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 13931.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85564.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 57322.61 | 12-JAN-15:00 | 24449.72 | 10740.89 | 0.00 | 0.00 | 8200.27 | 0.00 | 0.00 | 13931.74 | 0.00 |
February | 68197.43 | 24-FEB-16:40 | 24449.72 | 10740.89 | 0.00 | 0.00 | 8200.27 | 0.00 | 0.00 | 24806.56 | 0.00 |
March | 85601.27 | 28-MAR-15:00 | 22873.41 | 10740.89 | 0.00 | 0.00 | 8457.28 | 0.00 | 0.00 | 43529.70 | 0.00 |
April | 105911.90 | 28-APR-15:30 | 22873.41 | 10740.89 | 0.00 | 0.00 | 11201.09 | 0.00 | 0.00 | 61096.52 | 0.00 |
May | 123005.92 | 30-MAY-15:50 | 22873.41 | 10740.89 | 0.00 | 0.00 | 14178.78 | 0.00 | 0.00 | 75212.84 | 0.00 |
June | 135229.96 | 10-JUN-15:00 | 22873.41 | 10740.89 | 0.00 | 0.00 | 16051.40 | 0.00 | 0.00 | 85564.27 | 0.00 |
July | 128408.92 | 01-JUL-16:49 | 22873.41 | 10740.89 | 0.00 | 0.00 | 15802.88 | 0.00 | 0.00 | 78991.75 | 0.00 |
August | 118114.34 | 07-AUG-14:00 | 19720.78 | 10740.89 | 0.00 | 0.00 | 14372.28 | 0.00 | 0.00 | 73280.39 | 0.00 |
September | 108039.35 | 14-SEP-16:00 | 24449.72 | 10740.89 | 0.00 | 0.00 | 11966.08 | 0.00 | 0.00 | 60882.67 | 0.00 |
October | 97754.16 | 03-OCT-15:09 | 22873.41 | 10740.89 | 0.00 | 0.00 | 10057.85 | 0.00 | 0.00 | 54082.02 | 0.00 |
November | 76144.40 | 08-NOV-15:50 | 24449.72 | 10740.89 | 0.00 | 0.00 | 8250.45 | 0.00 | 0.00 | 32703.35 | 0.00 |
December | 60086.52 | 01-DEC-15:30 | 24449.72 | 10740.89 | 0.00 | 0.00 | 8200.27 | 0.00 | 0.00 | 16695.65 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 57322.61 | 19720.78 | 10740.89 | 0.00 | 0.00 | 8200.27 | 0.00 | 0.00 | 13931.74 | 0.00 | |
Maximum of Months | 135229.96 | 24449.72 | 10740.89 | 0.00 | 0.00 | 16051.40 | 0.00 | 0.00 | 85564.27 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 118061.28 | 02-JAN-07:10 | 0.00 | 4923.53 | 23-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 66323.93 | 11-FEB-07:10 | 0.00 | 4919.14 | 01-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 4891.86 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 4839.60 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4789.01 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4741.24 | 01-JUN-11:50 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4713.07 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4735.46 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4777.72 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 4834.62 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 1027.16 | 27-NOV-06:00 | 0.00 | 4883.84 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 79133.51 | 23-DEC-07:10 | 0.00 | 4914.71 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4713.07 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 118061.28 | 0.00 | 4923.53 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 24.81 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 25.47 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 25.51 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 25.68 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 25.18 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 24.86 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.63 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.17 | 20.41 | 0.00 | 61.17 | 25.29 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 20.51 | 0.00 | 0.00 | 13.00 | 25.68 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.70 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.21 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.26 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.62 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 26.54 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 25.62 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 25.62 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 25.33 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.59 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.41 | 0.00 | 85.00 | 26.01 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.41 | 0.00 | 0.00 | 14.33 | 26.62 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.67 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 25.30 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 25.84 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 25.48 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 25.44 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 25.35 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 25.07 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 24.99 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.53 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.35 | 0.00 | 66.17 | 25.37 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.35 | 0.00 | 0.00 | 11.33 | 25.84 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.67 | 14.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.83 | 15.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17.00 | 14.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.50 | 14.60 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.67 | 15.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 22.17 | 56.50 | 21.25 | 56.50 | 21.25 |
February | 317.00 | 23.08 | 7.00 | 23.36 | 1.33 | 21.11 |
March | 95.67 | 23.67 | 142.33 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 359.00 | 23.89 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 418.00 | 23.89 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 408.00 | 23.89 | 0.00 | 0.00 |
July | 0.67 | 23.89 | 415.00 | 23.89 | 0.67 | 23.89 |
August | 0.00 | 0.00 | 422.00 | 23.89 | 0.00 | 0.00 |
September | 10.33 | 23.89 | 405.00 | 23.89 | 10.33 | 23.89 |
October | 1.33 | 23.89 | 349.83 | 23.89 | 0.00 | 0.00 |
November | 168.17 | 23.53 | 28.17 | 23.89 | 0.00 | 0.00 |
December | 415.00 | 22.71 | 20.67 | 21.11 | 20.67 | 21.11 |
Annual Sum or Average | 1422.17 | 22.81 | 3031.50 | 23.82 | 89.50 | 21.54 |
Minimum of Months | 0.00 | 0.00 | 7.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 415.00 | 23.89 | 422.00 | 23.89 | 56.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 378.50 | 22.68 | 6.50 | 21.16 | 6.50 | 21.16 |
February | 169.67 | 22.97 | 38.67 | 23.89 | 0.00 | 0.00 |
March | 22.67 | 23.33 | 257.33 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 389.50 | 23.89 | 0.00 | 0.00 |
May | 3.00 | 23.94 | 418.00 | 23.89 | 3.00 | 23.94 |
June | 25.83 | 23.91 | 408.00 | 23.89 | 25.83 | 23.91 |
July | 60.17 | 23.92 | 415.00 | 23.89 | 60.17 | 23.92 |
August | 120.33 | 23.90 | 422.00 | 23.89 | 120.33 | 23.90 |
September | 117.00 | 23.90 | 405.00 | 23.89 | 117.00 | 23.90 |
October | 6.00 | 23.89 | 400.50 | 23.89 | 6.00 | 23.89 |
November | 47.50 | 23.05 | 171.67 | 23.89 | 0.00 | 0.00 |
December | 296.33 | 22.88 | 0.67 | 21.32 | 0.67 | 21.32 |
Annual Sum or Average | 1247.00 | 23.12 | 3332.83 | 23.89 | 339.50 | 23.85 |
Minimum of Months | 0.00 | 0.00 | 0.67 | 21.16 | 0.00 | 0.00 |
Maximum of Months | 378.50 | 23.94 | 422.00 | 23.89 | 120.33 | 23.94 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 178.33 | 22.62 | 50.00 | 23.75 | 2.50 | 21.11 |
February | 81.50 | 22.83 | 187.17 | 23.89 | 0.00 | 0.00 |
March | 15.50 | 23.74 | 349.00 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 396.00 | 23.89 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 418.00 | 23.89 | 0.00 | 0.00 |
June | 2.17 | 23.89 | 408.00 | 23.89 | 2.17 | 23.89 |
July | 2.00 | 23.89 | 415.00 | 23.89 | 2.00 | 23.89 |
August | 1.50 | 23.89 | 422.00 | 23.89 | 1.50 | 23.89 |
September | 13.17 | 23.89 | 405.00 | 23.89 | 13.17 | 23.89 |
October | 0.00 | 0.00 | 411.83 | 23.89 | 0.00 | 0.00 |
November | 11.50 | 23.45 | 341.83 | 23.89 | 0.00 | 0.00 |
December | 119.00 | 22.92 | 138.00 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 424.67 | 22.86 | 3941.83 | 23.89 | 21.33 | 23.56 |
Minimum of Months | 0.00 | 0.00 | 50.00 | 23.75 | 0.00 | 0.00 |
Maximum of Months | 178.33 | 23.89 | 422.00 | 23.89 | 13.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 225.50 | 22.29 | 30.00 | 23.36 | 5.67 | 21.11 |
February | 106.50 | 22.41 | 160.50 | 23.89 | 0.00 | 0.00 |
March | 31.33 | 23.42 | 327.83 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 387.17 | 23.89 | 0.00 | 0.00 |
May | 1.00 | 23.89 | 418.00 | 23.89 | 1.00 | 23.89 |
June | 9.83 | 23.89 | 408.00 | 23.89 | 9.83 | 23.89 |
July | 10.67 | 23.89 | 415.00 | 23.89 | 10.67 | 23.89 |
August | 7.67 | 23.89 | 422.00 | 23.89 | 7.67 | 23.89 |
September | 55.17 | 23.89 | 405.00 | 23.89 | 55.17 | 23.89 |
October | 0.00 | 0.00 | 405.67 | 23.89 | 0.00 | 0.00 |
November | 21.33 | 23.14 | 329.00 | 23.89 | 0.00 | 0.00 |
December | 153.67 | 22.57 | 98.67 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 622.67 | 22.68 | 3806.83 | 23.89 | 90.00 | 23.71 |
Minimum of Months | 0.00 | 0.00 | 30.00 | 23.36 | 0.00 | 0.00 |
Maximum of Months | 225.50 | 23.89 | 422.00 | 23.89 | 55.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.16062 | 49.75814 | -0.2120 | 7.25643 |
February | 376.00000 | 23.18285 | 48.50191 | 0.09257 | 6.49615 |
March | 422.00000 | 23.83436 | 44.00928 | 0.36274 | 8.00723 |
April | 405.00000 | 23.88975 | 41.74121 | 0.52289 | 10.85395 |
May | 418.00000 | 23.88966 | 45.58689 | -0.1582 | 5.66446 |
June | 408.00000 | 23.88953 | 48.49771 | -0.1283 | 5.55376 |
July | 415.00000 | 23.88947 | 51.12963 | -0.1284 | 5.47162 |
August | 422.00000 | 23.88957 | 51.91457 | -0.1579 | 5.58471 |
September | 405.00000 | 23.88965 | 52.16495 | -0.2310 | 6.18832 |
October | 414.00000 | 23.88979 | 45.59452 | 0.48318 | 9.96812 |
November | 399.00000 | 23.72359 | 45.47466 | 0.29003 | 7.18840 |
December | 415.00000 | 22.69447 | 47.90405 | -0.0683 | 6.59484 |
Annual Sum or Average | 4913.00000 | 23.57065 | 47.69191 | 0.05442 | 7.06714 |
Minimum of Months | 376.00000 | 22.16062 | 41.74121 | -0.2310 | 5.47162 |
Maximum of Months | 422.00000 | 23.88979 | 52.16495 | 0.52289 | 10.85395 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.75731 | 43.81661 | 0.00695 | 6.43719 |
February | 376.00000 | 23.44828 | 43.74149 | 0.24547 | 7.13185 |
March | 422.00000 | 23.85818 | 42.09924 | 0.43236 | 9.06480 |
April | 405.00000 | 23.91035 | 41.55059 | 0.54814 | 11.39702 |
May | 418.00000 | 23.91358 | 48.39685 | -0.1633 | 5.66835 |
June | 408.00000 | 23.91430 | 53.41030 | -0.1365 | 5.51655 |
July | 415.00000 | 23.91563 | 58.72934 | -0.1381 | 5.49626 |
August | 422.00000 | 23.91499 | 60.19927 | -0.1550 | 5.56513 |
September | 405.00000 | 23.91450 | 58.72110 | -0.2004 | 5.90568 |
October | 414.00000 | 23.90336 | 47.02057 | 0.52859 | 10.91741 |
November | 399.00000 | 23.77698 | 42.56174 | 0.37988 | 8.26563 |
December | 415.00000 | 23.14126 | 41.81536 | 0.12270 | 6.48294 |
Annual Sum or Average | 4913.00000 | 23.69875 | 48.55748 | 0.12073 | 7.31473 |
Minimum of Months | 376.00000 | 22.75731 | 41.55059 | -0.2004 | 5.49626 |
Maximum of Months | 422.00000 | 23.91563 | 60.19927 | 0.54814 | 11.39702 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.31596 | 40.08728 | 0.19874 | 7.46796 |
February | 376.00000 | 23.64191 | 40.32324 | 0.35954 | 8.69666 |
March | 422.00000 | 23.88280 | 39.51996 | 0.51905 | 10.90745 |
April | 405.00000 | 23.88971 | 40.07465 | 0.63196 | 13.59352 |
May | 418.00000 | 23.88968 | 45.65693 | -0.0561 | 5.28709 |
June | 408.00000 | 23.88953 | 49.34396 | -0.0373 | 5.28902 |
July | 415.00000 | 23.88942 | 52.45615 | -0.0348 | 5.18964 |
August | 422.00000 | 23.88947 | 52.98190 | -0.0502 | 5.18155 |
September | 405.00000 | 23.88953 | 51.52684 | -0.0811 | 5.39629 |
October | 414.00000 | 23.88985 | 41.93076 | 0.65752 | 14.27039 |
November | 399.00000 | 23.87462 | 38.02271 | 0.54495 | 11.50382 |
December | 415.00000 | 23.58741 | 37.36533 | 0.30436 | 7.99531 |
Annual Sum or Average | 4913.00000 | 23.79498 | 44.15129 | 0.24451 | 8.38179 |
Minimum of Months | 376.00000 | 23.31596 | 37.36533 | -0.0811 | 5.18155 |
Maximum of Months | 422.00000 | 23.88985 | 52.98190 | 0.65752 | 14.27039 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.99407 | 42.11574 | 0.11369 | 7.25126 |
February | 376.00000 | 23.44909 | 42.19543 | 0.30239 | 8.32320 |
March | 422.00000 | 23.85080 | 40.63922 | 0.49179 | 10.39925 |
April | 405.00000 | 23.88966 | 40.45017 | 0.60967 | 13.01368 |
May | 418.00000 | 23.88961 | 46.36867 | -0.0848 | 5.37862 |
June | 408.00000 | 23.88950 | 50.54555 | -0.0684 | 5.34873 |
July | 415.00000 | 23.88944 | 54.09427 | -0.0622 | 5.24359 |
August | 422.00000 | 23.88945 | 54.82816 | -0.0778 | 5.24697 |
September | 405.00000 | 23.88949 | 53.56069 | -0.1080 | 5.48033 |
October | 414.00000 | 23.88971 | 42.80226 | 0.63697 | 13.70494 |
November | 399.00000 | 23.84398 | 38.92896 | 0.51568 | 10.92127 |
December | 415.00000 | 23.37566 | 39.15711 | 0.24103 | 7.67125 |
Annual Sum or Average | 4913.00000 | 23.72995 | 45.51594 | 0.20740 | 8.15102 |
Minimum of Months | 376.00000 | 22.99407 | 38.92896 | -0.1080 | 5.24359 |
Maximum of Months | 422.00000 | 23.88971 | 54.82816 | 0.63697 | 13.70494 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.214765E+09 | 60293824.35 | 25.67 | 0.160834E+09 | 53930585.67 | 0.00 | 0.22 | 14-JAN-16:50 | 0.00 | 01-JAN-00:10 | 5279.59 | 14-JAN-16:40 | 3815.36 | 14-JAN-16:50 | 1468.93 | 14-JAN-16:20 | 1439.44 | 14-JAN-16:40 | 0.00 | 01-JAN-00:10 |
February | 0.320834E+10 | 0.897155E+09 | 191.33 | 0.256069E+10 | 0.647650E+09 | 0.00 | 0.46 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 | 11596.19 | 24-FEB-16:00 | 9197.38 | 24-FEB-16:00 | 3489.92 | 25-FEB-17:00 | 3205.24 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.147111E+11 | 0.411672E+10 | 408.90 | 0.123445E+11 | 0.236654E+10 | 0.00 | 1.00 | 10-MAR-05:01 | 0.00 | 01-MAR-00:10 | 61945.80 | 11-MAR-05:01 | 54713.01 | 29-MAR-04:01 | 14359.06 | 11-MAR-05:02 | 13786.90 | 11-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.305226E+11 | 0.872700E+10 | 455.51 | 0.273732E+11 | 0.314936E+10 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 62215.74 | 17-APR-04:01 | 60125.15 | 29-APR-04:01 | 11948.66 | 17-APR-04:12 | 14612.57 | 27-APR-04:01 | 0.00 | 01-APR-00:10 |
May | 0.471395E+11 | 0.135764E+11 | 487.98 | 0.401568E+11 | 0.698273E+10 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 65448.50 | 24-MAY-04:01 | 60528.09 | 09-MAY-04:01 | 25130.86 | 24-MAY-04:06 | 15415.77 | 04-MAY-04:01 | 0.00 | 01-MAY-00:10 |
June | 0.508606E+11 | 0.144603E+11 | 487.36 | 0.406347E+11 | 0.102259E+11 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 67267.94 | 26-JUN-04:01 | 58545.06 | 06-JUN-04:01 | 31519.28 | 26-JUN-04:07 | 15709.94 | 12-JUN-04:01 | 0.00 | 01-JUN-00:10 |
July | 0.543441E+11 | 0.143378E+11 | 491.64 | 0.390384E+11 | 0.153057E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 67501.14 | 20-JUL-04:01 | 54745.66 | 07-JUL-04:01 | 31970.94 | 20-JUL-04:08 | 15699.79 | 02-JUL-06:01 | 0.00 | 01-JUL-00:10 |
August | 0.515029E+11 | 0.131441E+11 | 478.24 | 0.357052E+11 | 0.157977E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 65943.33 | 19-AUG-04:01 | 53725.63 | 09-AUG-04:01 | 26750.05 | 19-AUG-04:07 | 15097.27 | 08-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.401921E+11 | 0.103973E+11 | 457.56 | 0.284152E+11 | 0.117770E+11 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 66574.99 | 03-SEP-06:01 | 54210.13 | 27-SEP-04:01 | 30830.99 | 10-SEP-06:03 | 14497.24 | 02-SEP-04:01 | 0.00 | 01-SEP-00:10 |
October | 0.251623E+11 | 0.688607E+10 | 462.59 | 0.204594E+11 | 0.470294E+10 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 63482.63 | 12-OCT-04:01 | 56369.35 | 02-OCT-04:01 | 20919.25 | 12-OCT-04:03 | 13932.07 | 04-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.908952E+10 | 0.255277E+10 | 339.78 | 0.745218E+10 | 0.163734E+10 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 | 60889.71 | 09-NOV-05:01 | 48901.06 | 01-NOV-04:01 | 13990.21 | 09-NOV-05:01 | 13156.41 | 09-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.720508E+09 | 0.203814E+09 | 90.94 | 0.559779E+09 | 0.160729E+09 | 0.00 | 0.23 | 01-DEC-15:50 | 0.00 | 01-DEC-00:10 | 5458.55 | 01-DEC-16:00 | 4729.57 | 01-DEC-15:30 | 1431.07 | 16-DEC-16:20 | 1529.97 | 28-DEC-16:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.327668E+12 | 0.893598E+11 | 4377.50 | 0.254861E+12 | 0.728074E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.214765E+09 | 60293824.35 | 25.67 | 0.160834E+09 | 53930585.67 | 0.00 | 0.22 | 0.00 | 5279.59 | 3815.36 | 1431.07 | 1439.44 | 0.00 | |||||||
Maximum of Months | 0.543441E+11 | 0.144603E+11 | 491.64 | 0.406347E+11 | 0.157977E+11 | 0.00 | 1.00 | 0.00 | 67501.14 | 60528.09 | 31970.94 | 15709.94 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.539670E+10 | 0.163865E+10 | 132.55 | 0.437450E+10 | 0.102220E+10 | 0.00 | 0.35 | 14-JAN-15:20 | 0.00 | 01-JAN-00:10 | 30704.96 | 14-JAN-15:20 | 24434.16 | 12-JAN-15:20 | 8138.47 | 14-JAN-15:20 | 8950.89 | 14-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.237694E+11 | 0.706805E+10 | 257.00 | 0.190938E+11 | 0.467561E+10 | 0.00 | 0.64 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 | 60031.26 | 24-FEB-16:00 | 47542.54 | 22-FEB-15:10 | 19861.63 | 25-FEB-17:00 | 17314.77 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.709623E+11 | 0.208864E+11 | 396.85 | 0.579265E+11 | 0.130358E+11 | 0.00 | 1.00 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 | 219488.41 | 11-MAR-07:02 | 166217.13 | 13-MAR-06:03 | 56472.83 | 11-MAR-07:02 | 53708.54 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.122103E+12 | 0.371384E+11 | 420.08 | 0.105768E+12 | 0.163347E+11 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 223598.54 | 24-APR-06:02 | 201747.13 | 28-APR-05:01 | 72614.48 | 24-APR-06:02 | 58535.63 | 27-APR-05:02 | 0.00 | 01-APR-00:10 |
May | 0.177913E+12 | 0.545917E+11 | 447.32 | 0.140510E+12 | 0.374032E+11 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 231243.15 | 24-MAY-06:02 | 203969.43 | 29-MAY-07:01 | 98988.30 | 24-MAY-06:04 | 60477.26 | 04-MAY-04:01 | 0.00 | 01-MAY-00:10 |
June | 0.195950E+12 | 0.583154E+11 | 438.02 | 0.138071E+12 | 0.578789E+11 | 0.00 | 1.00 | 01-JUN-05:03 | 0.00 | 01-JUN-00:10 | 238764.83 | 25-JUN-08:62 | 192660.66 | 07-JUN-04:01 | 122858.32 | 25-JUN-08:04 | 61428.38 | 14-JUN-04:01 | 0.00 | 01-JUN-00:10 |
July | 0.211639E+12 | 0.579420E+11 | 445.18 | 0.124917E+12 | 0.867218E+11 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 238680.63 | 19-JUL-06:02 | 172818.24 | 05-JUL-04:01 | 123059.06 | 19-JUL-06:04 | 62007.18 | 02-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.208085E+12 | 0.550172E+11 | 448.26 | 0.115269E+12 | 0.928154E+11 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 240327.24 | 20-AUG-08:62 | 157899.18 | 07-AUG-05:01 | 128489.01 | 20-AUG-08:62 | 59186.19 | 08-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.166959E+12 | 0.445817E+11 | 428.78 | 0.977935E+11 | 0.691653E+11 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 241937.16 | 10-SEP-08:62 | 161292.70 | 26-SEP-05:02 | 135187.96 | 10-SEP-08:62 | 57840.61 | 24-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.105788E+12 | 0.304257E+11 | 414.37 | 0.798697E+11 | 0.259186E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 230789.52 | 12-OCT-06:03 | 175700.08 | 02-OCT-05:03 | 103381.57 | 12-OCT-06:03 | 55567.20 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.505898E+11 | 0.149352E+11 | 351.72 | 0.409002E+11 | 0.968964E+10 | 0.00 | 0.76 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 | 72595.73 | 09-NOV-15:10 | 61517.72 | 04-NOV-14:50 | 16772.86 | 08-NOV-18:00 | 21321.42 | 09-NOV-13:20 | 0.00 | 01-NOV-00:10 |
December | 0.112542E+11 | 0.339770E+10 | 204.03 | 0.899386E+10 | 0.226039E+10 | 0.00 | 0.42 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 | 35956.60 | 01-DEC-15:10 | 32197.15 | 01-DEC-15:10 | 8399.14 | 16-DEC-16:00 | 10573.13 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.135041E+13 | 0.385938E+12 | 4384.15 | 0.933487E+12 | 0.416922E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.539670E+10 | 0.163865E+10 | 132.55 | 0.437450E+10 | 0.102220E+10 | 0.00 | 0.35 | 0.00 | 30704.96 | 24434.16 | 8138.47 | 8950.89 | 0.00 | |||||||
Maximum of Months | 0.211639E+12 | 0.583154E+11 | 448.26 | 0.140510E+12 | 0.928154E+11 | 0.00 | 1.00 | 0.00 | 241937.16 | 203969.43 | 135187.96 | 62007.18 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.422049E+10 | 0.108275E+10 | 279.50 | 0.374286E+10 | 0.477631E+09 | 0.00 | 0.68 | 12-JAN-15:50 | 0.00 | 01-JAN-00:10 | 9650.06 | 12-JAN-16:00 | 8814.42 | 12-JAN-15:40 | 1422.12 | 13-JAN-14:20 | 2360.51 | 12-JAN-15:50 | 0.00 | 01-JAN-00:10 |
February | 0.722718E+10 | 0.181939E+10 | 316.54 | 0.634272E+10 | 0.884460E+09 | 0.00 | 1.00 | 23-FEB-05:02 | 0.00 | 01-FEB-00:10 | 32354.63 | 23-FEB-05:02 | 29576.31 | 23-FEB-05:02 | 4124.82 | 25-FEB-05:03 | 6889.73 | 23-FEB-05:02 | 0.00 | 01-FEB-00:10 |
March | 0.142927E+11 | 0.365122E+10 | 450.70 | 0.125767E+11 | 0.171607E+10 | 0.00 | 1.00 | 07-MAR-05:01 | 0.00 | 01-MAR-00:10 | 34081.48 | 11-MAR-05:01 | 31871.92 | 29-MAR-04:01 | 7375.53 | 11-MAR-05:03 | 7438.91 | 11-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.209385E+11 | 0.571389E+10 | 472.72 | 0.190405E+11 | 0.189803E+10 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 34395.62 | 17-APR-04:01 | 32808.05 | 21-APR-04:01 | 7317.41 | 17-APR-04:05 | 7916.94 | 27-APR-04:01 | 0.00 | 01-APR-00:10 |
May | 0.280813E+11 | 0.790051E+10 | 525.02 | 0.237133E+11 | 0.436806E+10 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 36128.32 | 24-MAY-04:01 | 32804.92 | 29-MAY-06:01 | 14534.12 | 24-MAY-04:05 | 8294.96 | 04-MAY-04:11 | 0.00 | 01-MAY-00:10 |
June | 0.299191E+11 | 0.826848E+10 | 514.04 | 0.232483E+11 | 0.667076E+10 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 37222.75 | 26-JUN-04:01 | 31488.53 | 05-JUN-04:01 | 18135.76 | 26-JUN-04:06 | 8480.08 | 12-JUN-04:11 | 0.00 | 01-JUN-00:10 |
July | 0.324292E+11 | 0.829062E+10 | 508.98 | 0.222261E+11 | 0.102030E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 37353.84 | 20-JUL-04:01 | 27909.97 | 07-JUL-04:11 | 18384.41 | 20-JUL-04:07 | 8457.32 | 02-JUL-06:01 | 0.00 | 01-JUL-00:10 |
August | 0.318590E+11 | 0.787956E+10 | 494.03 | 0.211003E+11 | 0.107587E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 36573.71 | 19-AUG-04:01 | 27440.03 | 06-AUG-06:01 | 15816.87 | 19-AUG-04:06 | 8141.09 | 08-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.272209E+11 | 0.676137E+10 | 467.34 | 0.190235E+11 | 0.819737E+10 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 36886.70 | 03-SEP-06:01 | 30396.95 | 27-SEP-04:01 | 17884.84 | 10-SEP-06:03 | 7841.52 | 18-SEP-04:01 | 0.00 | 01-SEP-00:10 |
October | 0.219792E+11 | 0.551728E+10 | 472.98 | 0.185509E+11 | 0.342837E+10 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 34964.14 | 12-OCT-04:01 | 32145.23 | 23-OCT-04:01 | 11783.04 | 12-OCT-04:03 | 7554.97 | 04-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.141883E+11 | 0.348164E+10 | 422.16 | 0.125809E+11 | 0.160740E+10 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 | 33140.13 | 09-NOV-05:01 | 30959.22 | 02-NOV-04:01 | 4889.49 | 18-NOV-05:02 | 7043.03 | 09-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.622988E+10 | 0.157515E+10 | 334.06 | 0.547509E+10 | 0.754795E+09 | 0.00 | 0.75 | 01-DEC-15:30 | 0.00 | 01-DEC-00:10 | 10744.00 | 01-DEC-15:30 | 10195.39 | 01-DEC-15:10 | 1498.99 | 16-DEC-16:20 | 2598.65 | 28-DEC-15:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.238586E+12 | 0.619419E+11 | 5258.06 | 0.187621E+12 | 0.509647E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.422049E+10 | 0.108275E+10 | 279.50 | 0.374286E+10 | 0.477631E+09 | 0.00 | 0.68 | 0.00 | 9650.06 | 8814.42 | 1422.12 | 2360.51 | 0.00 | |||||||
Maximum of Months | 0.324292E+11 | 0.829062E+10 | 525.02 | 0.237133E+11 | 0.107587E+11 | 0.00 | 1.00 | 0.00 | 37353.84 | 32808.05 | 18384.41 | 8480.08 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.220775E+10 | 0.578656E+09 | 209.07 | 0.192954E+10 | 0.278209E+09 | 0.00 | 0.60 | 12-JAN-15:40 | 0.00 | 01-JAN-00:10 | 7513.37 | 12-JAN-15:40 | 6750.38 | 12-JAN-15:30 | 1237.26 | 13-JAN-15:10 | 1883.93 | 12-JAN-15:40 | 0.00 | 01-JAN-00:10 |
February | 0.495768E+10 | 0.127128E+10 | 276.11 | 0.428370E+10 | 0.673984E+09 | 0.00 | 1.00 | 23-FEB-05:02 | 0.00 | 01-FEB-00:10 | 29075.57 | 23-FEB-05:02 | 25515.62 | 23-FEB-05:02 | 3559.94 | 23-FEB-05:02 | 6191.75 | 23-FEB-05:02 | 0.00 | 01-FEB-00:10 |
March | 0.113146E+11 | 0.293150E+10 | 420.11 | 0.977732E+10 | 0.153732E+10 | 0.00 | 1.00 | 07-MAR-05:01 | 0.00 | 01-MAR-00:10 | 30677.61 | 11-MAR-05:01 | 27481.08 | 29-MAR-04:01 | 7315.89 | 11-MAR-05:03 | 6700.17 | 11-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.180307E+11 | 0.494802E+10 | 461.23 | 0.161998E+11 | 0.183091E+10 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 30922.91 | 17-APR-04:01 | 29289.19 | 28-APR-04:01 | 6852.33 | 17-APR-04:05 | 7112.62 | 27-APR-04:01 | 0.00 | 01-APR-00:10 |
May | 0.248887E+11 | 0.699168E+10 | 499.39 | 0.206633E+11 | 0.422542E+10 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 32546.87 | 24-MAY-04:01 | 29313.51 | 29-MAY-06:01 | 13606.81 | 24-MAY-04:05 | 7492.48 | 04-MAY-04:01 | 0.00 | 01-MAY-00:10 |
June | 0.264603E+11 | 0.727943E+10 | 488.83 | 0.200286E+11 | 0.643172E+10 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 33539.44 | 26-JUN-04:01 | 27776.97 | 07-JUN-04:01 | 16979.28 | 26-JUN-04:06 | 7633.54 | 12-JUN-04:01 | 0.00 | 01-JUN-00:10 |
July | 0.290074E+11 | 0.737220E+10 | 494.65 | 0.191329E+11 | 0.987449E+10 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 33668.41 | 20-JUL-04:01 | 25016.84 | 07-JUL-04:01 | 17146.81 | 20-JUL-04:07 | 7623.01 | 02-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.283752E+11 | 0.697366E+10 | 482.81 | 0.179651E+11 | 0.104101E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 33028.58 | 19-AUG-04:01 | 24538.51 | 09-AUG-04:01 | 15108.81 | 11-AUG-04:12 | 7338.11 | 08-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.239036E+11 | 0.593133E+10 | 461.20 | 0.160624E+11 | 0.784119E+10 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 33242.40 | 03-SEP-06:01 | 26175.27 | 27-SEP-04:01 | 17358.97 | 10-SEP-06:02 | 7069.53 | 02-SEP-04:01 | 0.00 | 01-SEP-00:10 |
October | 0.189261E+11 | 0.477785E+10 | 468.00 | 0.156498E+11 | 0.327623E+10 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 31566.67 | 12-OCT-04:01 | 27949.37 | 03-OCT-04:01 | 11559.06 | 12-OCT-04:01 | 6787.39 | 04-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.113464E+11 | 0.282167E+10 | 401.24 | 0.987466E+10 | 0.147170E+10 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 | 29872.06 | 09-NOV-05:01 | 26850.10 | 13-NOV-05:01 | 5752.76 | 18-NOV-05:02 | 6348.44 | 09-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.374323E+10 | 0.966389E+09 | 283.66 | 0.321009E+10 | 0.533144E+09 | 0.00 | 0.69 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 | 8779.97 | 01-DEC-15:30 | 8262.81 | 01-DEC-15:10 | 1337.77 | 16-DEC-15:30 | 2134.52 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.203162E+12 | 0.528437E+11 | 4946.30 | 0.154777E+12 | 0.483844E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.220775E+10 | 0.578656E+09 | 209.07 | 0.192954E+10 | 0.278209E+09 | 0.00 | 0.60 | 0.00 | 7513.37 | 6750.38 | 1237.26 | 1883.93 | 0.00 | |||||||
Maximum of Months | 0.290074E+11 | 0.737220E+10 | 499.39 | 0.206633E+11 | 0.104101E+11 | 0.00 | 1.00 | 0.00 | 33668.41 | 29313.51 | 17358.97 | 7633.54 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.53 | 50.47 | 9.00 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 67.05 | 42.59 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.87 | 31.19 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 144.14 | 19.75 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.99 | 10.82 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 152.15 | 6.70 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.52 | 4.27 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.54 | 6.18 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.70 | 11.93 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.99 | 28.56 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.69 | 42.86 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.61 | 51.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.22 | 25.51 | 9.00 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.61 | 4.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.99 | 51.80 | 9.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 904.59 | 549.75 | 354.85 | 1217.56 | 747.63 | 0.00 | 0.00 | 744.00 |
February | 860.00 | 477.70 | 382.29 | 1222.03 | 628.01 | 0.00 | 0.00 | 672.00 |
March | 735.08 | 324.58 | 410.49 | 1137.67 | 426.81 | 0.00 | 0.00 | 744.00 |
April | 516.20 | 145.52 | 370.68 | 978.69 | 205.68 | 0.00 | 0.00 | 720.00 |
May | 371.16 | 27.27 | 343.90 | 952.18 | 72.38 | 0.00 | 0.00 | 744.00 |
June | 339.62 | 5.69 | 333.93 | 972.12 | 37.44 | 0.00 | 0.00 | 720.00 |
July | 354.31 | 4.82 | 349.49 | 902.05 | 23.37 | 0.00 | 0.00 | 744.00 |
August | 375.85 | 20.02 | 355.83 | 844.64 | 55.24 | 0.00 | 0.00 | 744.00 |
September | 503.84 | 130.71 | 373.14 | 962.88 | 126.42 | 0.00 | 0.00 | 720.00 |
October | 866.93 | 484.08 | 382.86 | 1495.86 | 384.46 | 0.00 | 0.00 | 744.00 |
November | 1083.19 | 716.07 | 367.12 | 1701.69 | 619.93 | 0.00 | 0.00 | 720.00 |
December | 966.72 | 605.87 | 360.84 | 1354.99 | 760.02 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 655.29 | 289.93 | 365.36 | 1144.47 | 339.28 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 339.62 | 4.82 | 333.93 | 844.64 | 23.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1083.19 | 716.07 | 410.49 | 1701.69 | 760.02 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 904.59 | 549.75 | 354.85 | 1223.64 | 720.97 | 0.00 | 0.00 | 744.00 |
February | 860.00 | 477.70 | 382.29 | 1224.10 | 606.60 | 0.00 | 0.00 | 672.00 |
March | 735.08 | 324.58 | 410.49 | 1134.09 | 410.22 | 0.00 | 0.00 | 744.00 |
April | 516.20 | 145.52 | 370.68 | 973.90 | 192.18 | 0.00 | 0.00 | 720.00 |
May | 371.16 | 27.27 | 343.90 | 949.74 | 64.27 | 0.00 | 0.00 | 744.00 |
June | 339.62 | 5.69 | 333.93 | 973.48 | 31.13 | 0.00 | 0.00 | 720.00 |
July | 354.31 | 4.82 | 349.49 | 902.65 | 18.05 | 0.00 | 0.00 | 744.00 |
August | 375.85 | 20.02 | 355.83 | 841.86 | 46.49 | 0.00 | 0.00 | 744.00 |
September | 503.84 | 130.71 | 373.14 | 959.95 | 113.89 | 0.00 | 0.00 | 720.00 |
October | 866.93 | 484.08 | 382.86 | 1490.93 | 371.50 | 0.00 | 0.00 | 744.00 |
November | 1083.19 | 716.07 | 367.12 | 1698.88 | 604.37 | 0.00 | 0.00 | 720.00 |
December | 966.72 | 605.87 | 360.84 | 1359.23 | 738.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 655.29 | 289.93 | 365.36 | 1143.64 | 325.19 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 339.62 | 4.82 | 333.93 | 841.86 | 18.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1083.19 | 716.07 | 410.49 | 1698.88 | 738.23 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 186.13 | 113.12 | 73.01 | 263.86 | 131.38 | 0.00 | 0.00 | 744.00 |
February | 176.96 | 98.29 | 78.66 | 253.47 | 117.60 | 0.00 | 0.00 | 672.00 |
March | 151.25 | 66.79 | 84.47 | 218.35 | 89.54 | 0.00 | 0.00 | 744.00 |
April | 106.22 | 29.94 | 76.27 | 155.35 | 53.32 | 0.00 | 0.00 | 720.00 |
May | 76.37 | 5.61 | 70.76 | 125.22 | 26.77 | 0.00 | 0.00 | 744.00 |
June | 69.88 | 1.17 | 68.71 | 126.86 | 16.35 | 0.00 | 0.00 | 720.00 |
July | 72.90 | 0.99 | 71.91 | 126.81 | 11.27 | 4.50 | 0.00 | 744.00 |
August | 77.34 | 4.12 | 73.22 | 127.48 | 20.58 | 0.00 | 0.00 | 744.00 |
September | 103.67 | 26.89 | 76.78 | 158.67 | 37.80 | 11.67 | 0.00 | 720.00 |
October | 178.38 | 99.61 | 78.78 | 276.24 | 92.63 | 0.00 | 0.00 | 744.00 |
November | 222.88 | 147.34 | 75.54 | 336.17 | 128.26 | 0.00 | 0.00 | 720.00 |
December | 198.92 | 124.67 | 74.25 | 287.80 | 137.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 134.83 | 59.66 | 75.18 | 204.40 | 71.64 | 16.17 | 0.00 | 8760.00 |
Minimum of Months | 69.88 | 0.99 | 68.71 | 125.22 | 11.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 222.88 | 147.34 | 84.47 | 336.17 | 137.04 | 11.67 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.124620E+09 | 0.135170E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.162219E+09 | 0.103034E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267498E+09 | 83545030.55 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373599E+09 | 51181245.32 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425850E+09 | 28982370.18 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.394368E+09 | 17370102.07 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287977E+09 | 11429265.88 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.245180E+09 | 16546313.95 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229912E+09 | 30920474.88 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251740E+09 | 76504581.97 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180645E+09 | 0.111088E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.122164E+09 | 0.138735E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.306577E+10 | 0.804507E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.122164E+09 | 11429265.88 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425850E+09 | 0.138735E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.326112E+10 | 0.200245E+10 |
February | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.295634E+10 | 0.151928E+10 |
March | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.304715E+10 | 0.114317E+10 |
April | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.253676E+10 | 0.533129E+09 |
May | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.255031E+10 | 0.193867E+09 |
June | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.251973E+10 | 97040760.72 |
July | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.241604E+10 | 62584927.46 |
August | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.226229E+10 | 0.147943E+09 |
September | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.249578E+10 | 0.327677E+09 |
October | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.400652E+10 | 0.102975E+10 |
November | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.441078E+10 | 0.160687E+10 |
December | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.362920E+10 | 0.203563E+10 |
Annual Sum or Average | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.360920E+11 | 0.106994E+11 |
Minimum of Months | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.226229E+10 | 62584927.46 |
Maximum of Months | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.441078E+10 | 0.203563E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.327741E+10 | 0.193105E+10 |
February | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.296135E+10 | 0.146748E+10 |
March | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.303754E+10 | 0.109874E+10 |
April | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.252436E+10 | 0.498125E+09 |
May | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.254379E+10 | 0.172136E+09 |
June | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.252326E+10 | 80701026.55 |
July | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.241767E+10 | 48337125.80 |
August | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.225485E+10 | 0.124523E+09 |
September | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.248818E+10 | 0.295196E+09 |
October | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.399331E+10 | 0.995030E+09 |
November | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.440351E+10 | 0.156654E+10 |
December | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.364055E+10 | 0.197726E+10 |
Annual Sum or Average | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.360658E+11 | 0.102551E+11 |
Minimum of Months | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.225485E+10 | 48337125.80 |
Maximum of Months | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.440351E+10 | 0.197726E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.498540E+09 | 0.302977E+09 | 0.195563E+09 | 0.706727E+09 | 0.351891E+09 |
February | 0.428095E+09 | 0.237795E+09 | 0.190300E+09 | 0.613197E+09 | 0.284498E+09 |
March | 0.405114E+09 | 0.178883E+09 | 0.226232E+09 | 0.584832E+09 | 0.239836E+09 |
April | 0.275312E+09 | 77610020.26 | 0.197702E+09 | 0.402660E+09 | 0.138214E+09 |
May | 0.204555E+09 | 15027040.58 | 0.189528E+09 | 0.335388E+09 | 71703235.00 |
June | 0.181132E+09 | 3034933.40 | 0.178097E+09 | 0.328823E+09 | 42368360.16 |
July | 0.195266E+09 | 2654389.84 | 0.192612E+09 | 0.339650E+09 | 30192872.31 |
August | 0.207136E+09 | 11031363.02 | 0.196105E+09 | 0.341438E+09 | 55112932.45 |
September | 0.268720E+09 | 69711043.12 | 0.199009E+09 | 0.411261E+09 | 97980669.86 |
October | 0.477784E+09 | 0.266784E+09 | 0.210999E+09 | 0.739893E+09 | 0.248094E+09 |
November | 0.577710E+09 | 0.381909E+09 | 0.195801E+09 | 0.871342E+09 | 0.332462E+09 |
December | 0.532776E+09 | 0.333908E+09 | 0.198869E+09 | 0.770841E+09 | 0.367044E+09 |
Annual Sum or Average | 0.425214E+10 | 0.188132E+10 | 0.237082E+10 | 0.644605E+10 | 0.225940E+10 |
Minimum of Months | 0.181132E+09 | 2654389.84 | 0.178097E+09 | 0.328823E+09 | 30192872.31 |
Maximum of Months | 0.577710E+09 | 0.381909E+09 | 0.226232E+09 | 0.871342E+09 | 0.367044E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 744.44 | 807.47 | 559.04 | 296.83 | 262.21 | 0.00 | 0.00 |
February | 1072.88 | 681.44 | 714.82 | 400.46 | 314.35 | 0.00 | 0.00 |
March | 1597.96 | 499.07 | 947.64 | 563.86 | 383.78 | 0.00 | 0.00 |
April | 2306.17 | 315.93 | 1233.68 | 864.43 | 369.25 | 0.00 | 0.00 |
May | 2543.91 | 173.13 | 1302.44 | 899.54 | 402.91 | 0.00 | 0.00 |
June | 2434.37 | 107.22 | 1220.66 | 776.71 | 443.96 | 0.00 | 0.00 |
July | 1720.29 | 68.28 | 853.75 | 305.76 | 547.99 | 0.00 | 0.00 |
August | 1464.63 | 98.84 | 735.66 | 208.03 | 527.63 | 0.00 | 0.00 |
September | 1419.21 | 190.87 | 764.32 | 327.01 | 437.31 | 0.00 | 0.00 |
October | 1503.82 | 457.02 | 847.67 | 536.77 | 310.90 | 0.00 | 0.00 |
November | 1115.09 | 685.73 | 709.84 | 467.47 | 242.37 | 0.00 | 0.00 |
December | 729.77 | 828.76 | 543.73 | 291.55 | 252.18 | 0.00 | 0.00 |
Annual Sum or Average | 1555.44 | 408.17 | 869.47 | 494.39 | 375.08 | 0.00 | 0.00 |
Minimum of Months | 729.77 | 68.28 | 543.73 | 208.03 | 242.37 | 0.00 | 0.00 |
Maximum of Months | 2543.91 | 828.76 | 1302.44 | 899.54 | 547.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1217.56 | 747.63 | 904.59 | 549.75 | 354.85 | 0.00 | 0.00 |
February | 1222.03 | 628.01 | 860.00 | 477.70 | 382.29 | 0.00 | 0.00 |
March | 1137.67 | 426.81 | 735.08 | 324.58 | 410.49 | 0.00 | 0.00 |
April | 978.69 | 205.68 | 516.20 | 145.52 | 370.68 | 0.00 | 0.00 |
May | 952.18 | 72.38 | 371.16 | 27.27 | 343.90 | 0.00 | 0.00 |
June | 972.12 | 37.44 | 339.62 | 5.69 | 333.93 | 0.00 | 0.00 |
July | 902.05 | 23.37 | 354.31 | 4.82 | 349.49 | 0.00 | 0.00 |
August | 844.64 | 55.24 | 375.85 | 20.02 | 355.83 | 0.00 | 0.00 |
September | 962.88 | 126.42 | 503.84 | 130.71 | 373.14 | 0.00 | 0.00 |
October | 1495.86 | 384.46 | 866.93 | 484.08 | 382.86 | 0.00 | 0.00 |
November | 1701.69 | 619.93 | 1083.19 | 716.07 | 367.12 | 0.00 | 0.00 |
December | 1354.99 | 760.02 | 966.72 | 605.87 | 360.84 | 0.00 | 0.00 |
Annual Sum or Average | 1144.47 | 339.28 | 655.29 | 289.93 | 365.36 | 0.00 | 0.00 |
Minimum of Months | 844.64 | 23.37 | 339.62 | 4.82 | 333.93 | 0.00 | 0.00 |
Maximum of Months | 1701.69 | 760.02 | 1083.19 | 716.07 | 410.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1223.64 | 720.97 | 904.59 | 549.75 | 354.85 | 0.00 | 0.00 |
February | 1224.10 | 606.60 | 860.00 | 477.70 | 382.29 | 0.00 | 0.00 |
March | 1134.09 | 410.22 | 735.08 | 324.58 | 410.49 | 0.00 | 0.00 |
April | 973.90 | 192.18 | 516.20 | 145.52 | 370.68 | 0.00 | 0.00 |
May | 949.74 | 64.27 | 371.16 | 27.27 | 343.90 | 0.00 | 0.00 |
June | 973.48 | 31.13 | 339.62 | 5.69 | 333.93 | 0.00 | 0.00 |
July | 902.65 | 18.05 | 354.31 | 4.82 | 349.49 | 0.00 | 0.00 |
August | 841.86 | 46.49 | 375.85 | 20.02 | 355.83 | 0.00 | 0.00 |
September | 959.95 | 113.89 | 503.84 | 130.71 | 373.14 | 0.00 | 0.00 |
October | 1490.93 | 371.50 | 866.93 | 484.08 | 382.86 | 0.00 | 0.00 |
November | 1698.88 | 604.37 | 1083.19 | 716.07 | 367.12 | 0.00 | 0.00 |
December | 1359.23 | 738.23 | 966.72 | 605.87 | 360.84 | 0.00 | 0.00 |
Annual Sum or Average | 1143.64 | 325.19 | 655.29 | 289.93 | 365.36 | 0.00 | 0.00 |
Minimum of Months | 841.86 | 18.05 | 339.62 | 4.82 | 333.93 | 0.00 | 0.00 |
Maximum of Months | 1698.88 | 738.23 | 1083.19 | 716.07 | 410.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 263.86 | 131.38 | 186.13 | 113.12 | 73.01 | 0.00 | 0.00 |
February | 253.47 | 117.60 | 176.96 | 98.29 | 78.66 | 0.00 | 0.00 |
March | 218.35 | 89.54 | 151.25 | 66.79 | 84.47 | 0.00 | 0.00 |
April | 155.35 | 53.32 | 106.22 | 29.94 | 76.27 | 0.00 | 0.00 |
May | 125.22 | 26.77 | 76.37 | 5.61 | 70.76 | 0.00 | 0.00 |
June | 126.86 | 16.35 | 69.88 | 1.17 | 68.71 | 0.00 | 0.00 |
July | 126.81 | 11.27 | 72.90 | 0.99 | 71.91 | 0.00 | 0.00 |
August | 127.48 | 20.58 | 77.34 | 4.12 | 73.22 | 0.00 | 0.00 |
September | 158.67 | 37.80 | 103.67 | 26.89 | 76.78 | 0.00 | 0.00 |
October | 276.24 | 92.63 | 178.38 | 99.61 | 78.78 | 0.00 | 0.00 |
November | 336.17 | 128.26 | 222.88 | 147.34 | 75.54 | 0.00 | 0.00 |
December | 287.80 | 137.04 | 198.92 | 124.67 | 74.25 | 0.00 | 0.00 |
Annual Sum or Average | 204.40 | 71.64 | 134.83 | 59.66 | 75.18 | 0.00 | 0.00 |
Minimum of Months | 125.22 | 11.27 | 69.88 | 0.99 | 68.71 | 0.00 | 0.00 |
Maximum of Months | 336.17 | 137.04 | 222.88 | 147.34 | 84.47 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.199392E+10 | 0.216272E+10 | 0.149733E+10 | 0.795025E+09 | 0.702302E+09 | 0.00 | 0.00 |
February | 0.259551E+10 | 0.164855E+10 | 0.172928E+10 | 0.968801E+09 | 0.760484E+09 | 0.00 | 0.00 |
March | 0.427997E+10 | 0.133672E+10 | 0.253816E+10 | 0.151025E+10 | 0.102791E+10 | 0.00 | 0.00 |
April | 0.597758E+10 | 0.818900E+09 | 0.319771E+10 | 0.224060E+10 | 0.957106E+09 | 0.00 | 0.00 |
May | 0.681360E+10 | 0.463718E+09 | 0.348846E+10 | 0.240932E+10 | 0.107914E+10 | 0.00 | 0.00 |
June | 0.630988E+10 | 0.277922E+09 | 0.316396E+10 | 0.201322E+10 | 0.115074E+10 | 0.00 | 0.00 |
July | 0.460764E+10 | 0.182868E+09 | 0.228668E+10 | 0.818957E+09 | 0.146773E+10 | 0.00 | 0.00 |
August | 0.392288E+10 | 0.264741E+09 | 0.197039E+10 | 0.557183E+09 | 0.141321E+10 | 0.00 | 0.00 |
September | 0.367860E+10 | 0.494728E+09 | 0.198111E+10 | 0.847610E+09 | 0.113350E+10 | 0.00 | 0.00 |
October | 0.402784E+10 | 0.122407E+10 | 0.227041E+10 | 0.143769E+10 | 0.832718E+09 | 0.00 | 0.00 |
November | 0.289031E+10 | 0.177741E+10 | 0.183990E+10 | 0.121168E+10 | 0.628220E+09 | 0.00 | 0.00 |
December | 0.195462E+10 | 0.221976E+10 | 0.145632E+10 | 0.780876E+09 | 0.675440E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.490524E+11 | 0.128721E+11 | 0.274197E+11 | 0.155912E+11 | 0.118285E+11 | 0.00 | 0.00 |
Minimum of Months | 0.195462E+10 | 0.182868E+09 | 0.145632E+10 | 0.557183E+09 | 0.628220E+09 | 0.00 | 0.00 |
Maximum of Months | 0.681360E+10 | 0.221976E+10 | 0.348846E+10 | 0.240932E+10 | 0.146773E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.326112E+10 | 0.200245E+10 | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.00 | 0.00 |
February | 0.295634E+10 | 0.151928E+10 | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.00 | 0.00 |
March | 0.304715E+10 | 0.114317E+10 | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.00 | 0.00 |
April | 0.253676E+10 | 0.533129E+09 | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.00 | 0.00 |
May | 0.255031E+10 | 0.193867E+09 | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.00 | 0.00 |
June | 0.251973E+10 | 97040760.72 | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.00 | 0.00 |
July | 0.241604E+10 | 62584927.46 | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.00 | 0.00 |
August | 0.226229E+10 | 0.147943E+09 | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.00 | 0.00 |
September | 0.249578E+10 | 0.327677E+09 | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.00 | 0.00 |
October | 0.400652E+10 | 0.102975E+10 | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.00 | 0.00 |
November | 0.441078E+10 | 0.160687E+10 | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.00 | 0.00 |
December | 0.362920E+10 | 0.203563E+10 | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.360920E+11 | 0.106994E+11 | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.00 | 0.00 |
Minimum of Months | 0.226229E+10 | 62584927.46 | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.00 | 0.00 |
Maximum of Months | 0.441078E+10 | 0.203563E+10 | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.327741E+10 | 0.193105E+10 | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.00 | 0.00 |
February | 0.296135E+10 | 0.146748E+10 | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.00 | 0.00 |
March | 0.303754E+10 | 0.109874E+10 | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.00 | 0.00 |
April | 0.252436E+10 | 0.498125E+09 | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.00 | 0.00 |
May | 0.254379E+10 | 0.172136E+09 | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.00 | 0.00 |
June | 0.252326E+10 | 80701026.55 | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.00 | 0.00 |
July | 0.241767E+10 | 48337125.80 | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.00 | 0.00 |
August | 0.225485E+10 | 0.124523E+09 | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.00 | 0.00 |
September | 0.248818E+10 | 0.295196E+09 | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.00 | 0.00 |
October | 0.399331E+10 | 0.995030E+09 | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.00 | 0.00 |
November | 0.440351E+10 | 0.156654E+10 | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.00 | 0.00 |
December | 0.364055E+10 | 0.197726E+10 | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.360658E+11 | 0.102551E+11 | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.00 | 0.00 |
Minimum of Months | 0.225485E+10 | 48337125.80 | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.00 | 0.00 |
Maximum of Months | 0.440351E+10 | 0.197726E+10 | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.706727E+09 | 0.351891E+09 | 0.498540E+09 | 0.302977E+09 | 0.195563E+09 | 0.00 | 0.00 |
February | 0.613197E+09 | 0.284498E+09 | 0.428095E+09 | 0.237795E+09 | 0.190300E+09 | 0.00 | 0.00 |
March | 0.584832E+09 | 0.239836E+09 | 0.405114E+09 | 0.178883E+09 | 0.226232E+09 | 0.00 | 0.00 |
April | 0.402660E+09 | 0.138214E+09 | 0.275312E+09 | 77610020.26 | 0.197702E+09 | 0.00 | 0.00 |
May | 0.335388E+09 | 71703235.00 | 0.204555E+09 | 15027040.58 | 0.189528E+09 | 0.00 | 0.00 |
June | 0.328823E+09 | 42368360.16 | 0.181132E+09 | 3034933.40 | 0.178097E+09 | 0.00 | 0.00 |
July | 0.339650E+09 | 30192872.31 | 0.195266E+09 | 2654389.84 | 0.192612E+09 | 0.00 | 0.00 |
August | 0.341438E+09 | 55112932.45 | 0.207136E+09 | 11031363.02 | 0.196105E+09 | 0.00 | 0.00 |
September | 0.411261E+09 | 97980669.86 | 0.268720E+09 | 69711043.12 | 0.199009E+09 | 0.00 | 0.00 |
October | 0.739893E+09 | 0.248094E+09 | 0.477784E+09 | 0.266784E+09 | 0.210999E+09 | 0.00 | 0.00 |
November | 0.871342E+09 | 0.332462E+09 | 0.577710E+09 | 0.381909E+09 | 0.195801E+09 | 0.00 | 0.00 |
December | 0.770841E+09 | 0.367044E+09 | 0.532776E+09 | 0.333908E+09 | 0.198869E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.644605E+10 | 0.225940E+10 | 0.425214E+10 | 0.188132E+10 | 0.237082E+10 | 0.00 | 0.00 |
Minimum of Months | 0.328823E+09 | 30192872.31 | 0.181132E+09 | 2654389.84 | 0.178097E+09 | 0.00 | 0.00 |
Maximum of Months | 0.871342E+09 | 0.367044E+09 | 0.577710E+09 | 0.381909E+09 | 0.226232E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.37 | 7.87 | 1.20 | 0.37 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.77 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.59 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.31 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.95 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.37 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.28 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.69 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.73 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.45 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.87 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.75 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.37 | 7.87 | 0.66 | 0.37 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.18 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.17 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.47 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.63 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.60 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.49 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.34 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.56 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.67 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.02 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.14 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.28 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.18 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.67 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.55 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.57 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.73 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.61 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.36 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.40 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.17 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.16 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.05 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.91 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.61 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.17 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.47 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.24 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.03 | 0.00 | 15.60 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.69 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.40 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.58 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.47 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.221697E+10 | -.180384E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -413127308.9 | 58.99 | 0.00 | 0.00 |
February | 0.196725E+10 | -.160751E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -359738781.5 | 59.00 | 0.00 | 0.00 |
March | 0.208540E+10 | -.170247E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -382929919.6 | 58.99 | 0.00 | 0.00 |
April | 0.181318E+10 | -.145244E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -360740537.5 | 58.99 | 0.00 | 0.00 |
May | 0.169414E+10 | -.132690E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -367240075.0 | 58.99 | 0.00 | 0.00 |
June | 0.152445E+10 | -.116832E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -356125226.9 | 58.99 | 0.00 | 0.00 |
July | 0.148495E+10 | -.111749E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -367457493.0 | 58.99 | 0.00 | 0.00 |
August | 0.156319E+10 | -.119400E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -369184370.8 | 58.99 | 0.00 | 0.00 |
September | 0.161616E+10 | -.125599E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -360164361.4 | 58.99 | 0.00 | 0.00 |
October | 0.182531E+10 | -.144865E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -376659684.2 | 58.99 | 0.00 | 0.00 |
November | 0.193724E+10 | -.156205E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -375199506.6 | 58.99 | 0.00 | 0.00 |
December | 0.215953E+10 | -.175317E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -406363088.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.218878E+11 | -.173928E+11 | 8760.00 | -.449493E+10 | 58.99 | |||||
Minimum of Months | 0.148495E+10 | -.180384E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -413127308.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.221697E+10 | -.111749E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -356125226.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.90 | 0.67 | 14-JAN-11:39 | 214.19 | 5.63 | 0.00 | 0.00 | 176.46 | 4.24 | 0.00 | 0.00 |
February | 303.83 | 0.86 | 0.67 | 01-FEB-10:00 | 255.59 | 6.46 | 0.00 | 0.00 | 211.55 | 4.98 | 0.00 | 0.00 |
March | 364.50 | 0.80 | 0.50 | 02-MAR-11:09 | 1665.61 | 7.54 | 0.00 | 62.33 | 1790.31 | 5.98 | 0.00 | 55.17 |
April | 379.83 | 0.84 | 0.50 | 02-APR-11:30 | 279.74 | 7.87 | 0.00 | 7.50 | 232.34 | 6.25 | 0.00 | 5.00 |
May | 406.00 | 0.84 | 0.50 | 12-MAY-11:30 | 281.29 | 9.09 | 0.00 | 13.17 | 233.95 | 7.39 | 0.00 | 8.50 |
June | 386.67 | 0.82 | 0.50 | 01-JUN-10:00 | 301.78 | 9.90 | 0.00 | 24.33 | 250.20 | 8.14 | 0.00 | 14.00 |
July | 379.83 | 0.78 | 0.50 | 05-JUL-11:30 | 352.27 | 10.72 | 0.00 | 70.67 | 297.11 | 9.10 | 0.00 | 39.00 |
August | 372.50 | 0.77 | 0.50 | 01-AUG-10:39 | 396.24 | 10.10 | 0.00 | 91.33 | 345.62 | 8.53 | 0.00 | 53.33 |
September | 344.33 | 0.78 | 0.50 | 01-SEP-10:39 | 922.57 | 8.93 | 0.00 | 72.50 | 916.05 | 7.34 | 0.00 | 48.83 |
October | 347.33 | 0.85 | 0.50 | 06-OCT-11:20 | 268.37 | 6.63 | 0.00 | 4.33 | 222.88 | 5.17 | 0.00 | 2.00 |
November | 317.83 | 0.90 | 0.75 | 28-NOV-10:50 | 213.90 | 5.34 | 0.00 | 0.00 | 177.04 | 3.93 | 0.00 | 0.00 |
December | 315.50 | 0.90 | 0.75 | 08-DEC-11:39 | 208.78 | 5.46 | 0.00 | 0.00 | 171.63 | 4.05 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | 0.83 | 452.26 | 7.94 | 0.00 | 346.17 | 424.31 | 6.38 | 0.00 | 225.83 | ||
Minimum of Months | 303.83 | 0.77 | 0.50 | 208.78 | 5.34 | 0.00 | 0.00 | 171.63 | 3.93 | 0.00 | 0.00 | |
Maximum of Months | 406.00 | 0.90 | 0.75 | 1665.61 | 10.72 | 0.00 | 91.33 | 1790.31 | 9.10 | 0.00 | 55.17 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.300294E+10 | 66728.44 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.558379E+09 | 66728.44 | 11-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2213212.76 | 923.75 | 27-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122886E+10 | 66728.44 | 22-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.479239E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.300294E+10 | 66728.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.458815E+10 | 222165.35 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.500433E+09 | 167313.47 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.936581E+09 | 176640.83 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.602517E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.458815E+10 | 222165.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.354862E+09 | 37257.06 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 56505966.32 | 23167.08 | 11-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 53865065.79 | 4865.22 | 31-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.465233E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.354862E+09 | 37257.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.721598E+09 | 32911.40 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149610E+09 | 32911.40 | 11-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147152E+09 | 19208.53 | 31-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101836E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.721598E+09 | 32911.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5704662.48 | 2450.41 | 06-JAN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3022064.01 | 2359.22 | 21-DEC-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8726726.49 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5704662.48 | 2450.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.214765E+09 | 0.160834E+09 | 5279.59 | 14-JAN-16:40 | 3812.07 | 0.00 |
February | 0.00 | 0.00 | 0.320834E+10 | 0.256069E+10 | 11596.19 | 24-FEB-16:00 | 9197.38 | 0.00 |
March | 0.00 | 0.00 | 0.147111E+11 | 0.123445E+11 | 61945.80 | 11-MAR-05:01 | 48117.69 | 0.00 |
April | 0.00 | 0.00 | 0.305226E+11 | 0.273732E+11 | 62215.74 | 17-APR-04:01 | 54497.63 | 0.00 |
May | 0.00 | 0.00 | 0.471395E+11 | 0.401568E+11 | 65448.50 | 24-MAY-04:01 | 43260.45 | 0.00 |
June | 0.00 | 0.00 | 0.508606E+11 | 0.406347E+11 | 67267.94 | 26-JUN-04:01 | 37690.24 | 0.00 |
July | 0.00 | 0.00 | 0.543441E+11 | 0.390384E+11 | 67501.14 | 20-JUL-04:01 | 37522.31 | 0.00 |
August | 0.00 | 0.00 | 0.515029E+11 | 0.357052E+11 | 65943.33 | 19-AUG-04:01 | 42550.21 | 0.00 |
September | 0.00 | 0.00 | 0.401921E+11 | 0.284152E+11 | 66574.99 | 03-SEP-06:01 | 40106.64 | 0.00 |
October | 0.00 | 0.00 | 0.251623E+11 | 0.204594E+11 | 63482.63 | 12-OCT-04:01 | 43193.12 | 0.00 |
November | 0.00 | 0.00 | 0.908952E+10 | 0.745218E+10 | 60889.71 | 09-NOV-05:01 | 46899.50 | 0.00 |
December | 0.00 | 0.00 | 0.720508E+09 | 0.559779E+09 | 5458.55 | 01-DEC-16:00 | 4693.12 | 0.00 |
Annual Sum or Average | 0.327668E+12 | 0.254861E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.214765E+09 | 0.160834E+09 | 5279.59 | 3812.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.543441E+11 | 0.406347E+11 | 67501.14 | 54497.63 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.539670E+10 | 0.437450E+10 | 30704.96 | 14-JAN-15:20 | 22566.48 | 0.00 |
February | 0.00 | 0.00 | 0.237694E+11 | 0.190938E+11 | 60031.26 | 24-FEB-16:00 | 46688.26 | 0.00 |
March | 0.00 | 0.00 | 0.709623E+11 | 0.579265E+11 | 219488.41 | 11-MAR-07:02 | 163015.59 | 0.00 |
April | 0.00 | 0.00 | 0.122103E+12 | 0.105768E+12 | 223598.54 | 24-APR-06:02 | 150984.05 | 0.00 |
May | 0.00 | 0.00 | 0.177913E+12 | 0.140510E+12 | 231243.15 | 24-MAY-06:02 | 132789.42 | 0.00 |
June | 0.00 | 0.00 | 0.195950E+12 | 0.138071E+12 | 238764.83 | 25-JUN-08:62 | 115942.47 | 0.00 |
July | 0.00 | 0.00 | 0.211639E+12 | 0.124917E+12 | 238680.63 | 19-JUL-06:02 | 115632.12 | 0.00 |
August | 0.00 | 0.00 | 0.208085E+12 | 0.115269E+12 | 240327.24 | 20-AUG-08:62 | 111838.24 | 0.00 |
September | 0.00 | 0.00 | 0.166959E+12 | 0.977935E+11 | 241937.16 | 10-SEP-08:62 | 106749.20 | 0.00 |
October | 0.00 | 0.00 | 0.105788E+12 | 0.798697E+11 | 230789.52 | 12-OCT-06:03 | 127407.94 | 0.00 |
November | 0.00 | 0.00 | 0.505898E+11 | 0.409002E+11 | 72595.73 | 09-NOV-15:10 | 60665.48 | 0.00 |
December | 0.00 | 0.00 | 0.112542E+11 | 0.899386E+10 | 35956.60 | 01-DEC-15:10 | 32197.15 | 0.00 |
Annual Sum or Average | 0.135041E+13 | 0.933487E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.539670E+10 | 0.437450E+10 | 30704.96 | 22566.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.211639E+12 | 0.140510E+12 | 241937.16 | 163015.59 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.422049E+10 | 0.374286E+10 | 9650.06 | 12-JAN-16:00 | 8788.23 | 0.00 |
February | 0.00 | 0.00 | 0.722718E+10 | 0.634272E+10 | 32354.63 | 23-FEB-05:02 | 29576.31 | 0.00 |
March | 0.00 | 0.00 | 0.142927E+11 | 0.125767E+11 | 34081.48 | 11-MAR-05:01 | 27782.46 | 0.00 |
April | 0.00 | 0.00 | 0.209385E+11 | 0.190405E+11 | 34395.62 | 17-APR-04:01 | 29997.09 | 0.00 |
May | 0.00 | 0.00 | 0.280813E+11 | 0.237133E+11 | 36128.32 | 24-MAY-04:01 | 23192.09 | 0.00 |
June | 0.00 | 0.00 | 0.299191E+11 | 0.232483E+11 | 37222.75 | 26-JUN-04:01 | 20179.88 | 0.00 |
July | 0.00 | 0.00 | 0.324292E+11 | 0.222261E+11 | 37353.84 | 20-JUL-04:01 | 20102.85 | 0.00 |
August | 0.00 | 0.00 | 0.318590E+11 | 0.211003E+11 | 36573.71 | 19-AUG-04:01 | 22664.27 | 0.00 |
September | 0.00 | 0.00 | 0.272209E+11 | 0.190235E+11 | 36886.70 | 03-SEP-06:01 | 21478.17 | 0.00 |
October | 0.00 | 0.00 | 0.219792E+11 | 0.185509E+11 | 34964.14 | 12-OCT-04:01 | 23638.64 | 0.00 |
November | 0.00 | 0.00 | 0.141883E+11 | 0.125809E+11 | 33140.13 | 09-NOV-05:01 | 29321.66 | 0.00 |
December | 0.00 | 0.00 | 0.622988E+10 | 0.547509E+10 | 10744.00 | 01-DEC-15:30 | 10153.19 | 0.00 |
Annual Sum or Average | 0.238586E+12 | 0.187621E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.422049E+10 | 0.374286E+10 | 9650.06 | 8788.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.324292E+11 | 0.237133E+11 | 37353.84 | 29997.09 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.220775E+10 | 0.192954E+10 | 7513.37 | 12-JAN-15:40 | 6741.47 | 0.00 |
February | 0.00 | 0.00 | 0.495768E+10 | 0.428370E+10 | 29075.57 | 23-FEB-05:02 | 25515.62 | 0.00 |
March | 0.00 | 0.00 | 0.113146E+11 | 0.977732E+10 | 30677.61 | 11-MAR-05:01 | 24099.60 | 0.00 |
April | 0.00 | 0.00 | 0.180307E+11 | 0.161998E+11 | 30922.91 | 17-APR-04:01 | 26231.47 | 0.00 |
May | 0.00 | 0.00 | 0.248887E+11 | 0.206633E+11 | 32546.87 | 24-MAY-04:01 | 20032.89 | 0.00 |
June | 0.00 | 0.00 | 0.264603E+11 | 0.200286E+11 | 33539.44 | 26-JUN-04:01 | 17197.12 | 0.00 |
July | 0.00 | 0.00 | 0.290074E+11 | 0.191329E+11 | 33668.41 | 20-JUL-04:01 | 17202.98 | 0.00 |
August | 0.00 | 0.00 | 0.283752E+11 | 0.179651E+11 | 33028.58 | 19-AUG-04:01 | 19321.61 | 0.00 |
September | 0.00 | 0.00 | 0.239036E+11 | 0.160624E+11 | 33242.40 | 03-SEP-06:01 | 18427.71 | 0.00 |
October | 0.00 | 0.00 | 0.189261E+11 | 0.156498E+11 | 31566.67 | 12-OCT-04:01 | 20007.61 | 0.00 |
November | 0.00 | 0.00 | 0.113464E+11 | 0.987466E+10 | 29872.06 | 09-NOV-05:01 | 25036.66 | 0.00 |
December | 0.00 | 0.00 | 0.374323E+10 | 0.321009E+10 | 8779.97 | 01-DEC-15:30 | 8192.23 | 0.00 |
Annual Sum or Average | 0.203162E+12 | 0.154777E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.220775E+10 | 0.192954E+10 | 7513.37 | 6741.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.290074E+11 | 0.206633E+11 | 33668.41 | 26231.47 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 6224853.81 | 0.00 | 800.11 | 03-JAN-08:63 | 0.93 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 4544623.35 | 0.00 | 800.11 | 21-DEC-08:05 | 0.93 |
Annual Sum or Average | 10769477.16 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6224853.81 | 0.00 | 800.11 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.204637E+10 | 0.35 | 3049.82 | 01-JAN-07:01 | 0.89 |
February | 0.179136E+10 | 0.33 | 3049.82 | 11-FEB-05:02 | 0.89 |
March | 0.200201E+10 | 0.34 | 3049.82 | 10-MAR-05:01 | 0.89 |
April | 0.198922E+10 | 0.35 | 3049.82 | 01-APR-04:01 | 0.89 |
May | 0.236550E+10 | 0.39 | 3049.82 | 01-MAY-04:01 | 0.90 |
June | 0.251239E+10 | 0.42 | 3049.82 | 01-JUN-04:01 | 0.89 |
July | 0.249894E+10 | 0.40 | 3049.82 | 01-JUL-04:01 | 0.89 |
August | 0.232752E+10 | 0.37 | 3049.82 | 01-AUG-04:01 | 0.89 |
September | 0.203388E+10 | 0.35 | 3049.82 | 01-SEP-04:01 | 0.89 |
October | 0.199935E+10 | 0.34 | 3049.82 | 01-OCT-06:01 | 0.89 |
November | 0.188551E+10 | 0.32 | 3049.82 | 01-NOV-04:01 | 0.89 |
December | 0.199584E+10 | 0.33 | 3049.82 | 22-DEC-05:01 | 0.90 |
Annual Sum or Average | 0.254479E+11 | 0.36 | |||
Minimum of Months | 0.179136E+10 | 0.32 | 3049.82 | 0.89 | |
Maximum of Months | 0.251239E+10 | 0.42 | 3049.82 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.937946E+10 | 0.52 | 14359.44 | 01-JAN-08:61 | 1.41 |
February | 0.837315E+10 | 0.51 | 12232.26 | 02-FEB-07:03 | 1.31 |
March | 0.937549E+10 | 0.52 | 14359.44 | 11-MAR-07:02 | 1.40 |
April | 0.936916E+10 | 0.53 | 14359.44 | 01-APR-06:02 | 1.41 |
May | 0.113806E+11 | 0.58 | 14359.44 | 01-MAY-05:01 | 1.41 |
June | 0.121351E+11 | 0.62 | 14359.44 | 01-JUN-05:03 | 1.40 |
July | 0.122926E+11 | 0.60 | 14359.44 | 01-JUL-05:01 | 1.40 |
August | 0.119173E+11 | 0.59 | 14359.44 | 01-AUG-05:02 | 1.39 |
September | 0.996020E+10 | 0.54 | 14359.44 | 01-SEP-05:02 | 1.39 |
October | 0.927466E+10 | 0.51 | 14359.44 | 01-OCT-07:01 | 1.40 |
November | 0.887069E+10 | 0.51 | 5743.78 | 10-NOV-21:00 | 0.85 |
December | 0.925853E+10 | 0.51 | 12593.98 | 23-DEC-07:03 | 1.33 |
Annual Sum or Average | 0.121587E+12 | 0.55 | |||
Minimum of Months | 0.837315E+10 | 0.51 | 5743.78 | 0.85 | |
Maximum of Months | 0.122926E+11 | 0.62 | 14359.44 | 1.41 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.105081E+10 | 0.33 | 1624.35 | 01-JAN-07:01 | 0.89 |
February | 0.948356E+09 | 0.33 | 1624.35 | 23-FEB-05:02 | 0.90 |
March | 0.107963E+10 | 0.34 | 1624.35 | 07-MAR-05:01 | 0.89 |
April | 0.113391E+10 | 0.37 | 1624.35 | 01-APR-04:01 | 0.90 |
May | 0.135164E+10 | 0.43 | 1624.35 | 01-MAY-04:01 | 0.90 |
June | 0.140830E+10 | 0.45 | 1624.35 | 01-JUN-04:01 | 0.89 |
July | 0.142354E+10 | 0.43 | 1624.35 | 01-JUL-04:01 | 0.89 |
August | 0.138204E+10 | 0.41 | 1624.35 | 01-AUG-04:01 | 0.88 |
September | 0.124064E+10 | 0.39 | 1624.35 | 01-SEP-04:01 | 0.89 |
October | 0.114704E+10 | 0.36 | 1624.35 | 01-OCT-06:01 | 0.89 |
November | 0.101627E+10 | 0.34 | 1624.35 | 01-NOV-04:01 | 0.89 |
December | 0.104475E+10 | 0.33 | 777.01 | 31-DEC-08:62 | 0.61 |
Annual Sum or Average | 0.142269E+11 | 0.38 | |||
Minimum of Months | 0.948356E+09 | 0.33 | 777.01 | 0.61 | |
Maximum of Months | 0.142354E+10 | 0.45 | 1624.35 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.960518E+09 | 0.34 | 1467.06 | 01-JAN-07:01 | 0.92 |
February | 0.858238E+09 | 0.34 | 1467.06 | 11-FEB-05:02 | 0.92 |
March | 0.970673E+09 | 0.35 | 1467.06 | 07-MAR-05:01 | 0.92 |
April | 0.101438E+10 | 0.38 | 1467.06 | 01-APR-04:01 | 0.93 |
May | 0.120537E+10 | 0.42 | 1467.06 | 01-MAY-04:01 | 0.93 |
June | 0.124676E+10 | 0.44 | 1467.06 | 01-JUN-04:01 | 0.92 |
July | 0.127047E+10 | 0.43 | 1467.06 | 01-JUL-04:01 | 0.92 |
August | 0.122442E+10 | 0.41 | 1467.06 | 01-AUG-04:01 | 0.91 |
September | 0.110640E+10 | 0.39 | 1467.06 | 01-SEP-04:01 | 0.92 |
October | 0.102714E+10 | 0.37 | 1467.06 | 01-OCT-06:01 | 0.92 |
November | 0.914261E+09 | 0.34 | 1467.06 | 01-NOV-04:01 | 0.93 |
December | 0.946185E+09 | 0.34 | 885.29 | 24-DEC-08:61 | 0.72 |
Annual Sum or Average | 0.127448E+11 | 0.38 | |||
Minimum of Months | 0.858238E+09 | 0.34 | 885.29 | 0.72 | |
Maximum of Months | 0.127047E+10 | 0.44 | 1467.06 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.22 | 0.00 |
February | 0.42 | 0.00 |
March | 0.11 | 0.00 |
April | 1.12 | 0.00 |
May | 2.35 | 0.00 |
June | 2.24 | 0.00 |
July | 1.87 | 0.00 |
August | 1.76 | 0.00 |
September | 0.91 | 0.00 |
October | 0.26 | 0.00 |
November | 0.00 | 0.00 |
December | 0.17 | 0.00 |
Annual Sum or Average | 11.43 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.35 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.94 | 19.94 |
February | 0.69 | 12.40 |
March | 0.17 | 25.84 |
April | 0.48 | 0.00 |
May | 0.25 | 0.00 |
June | 0.72 | 0.00 |
July | 0.23 | 0.00 |
August | 0.32 | 0.00 |
September | 0.78 | 0.00 |
October | 0.25 | 25.84 |
November | 0.00 | 0.00 |
December | 1.03 | 10.48 |
Annual Sum or Average | 6.87 | 10.03 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.94 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 1.16 | 0.00 |
March | 1.98 | 0.00 |
April | 2.64 | 0.00 |
May | 2.48 | 0.00 |
June | 2.07 | 0.00 |
July | 1.72 | 0.00 |
August | 1.74 | 0.00 |
September | 1.75 | 0.00 |
October | 1.26 | 0.00 |
November | 1.84 | 0.00 |
December | 0.36 | 0.00 |
Annual Sum or Average | 18.99 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.64 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.00 |
February | 0.35 | 0.00 |
March | 1.55 | 0.00 |
April | 2.23 | 0.00 |
May | 2.35 | 0.00 |
June | 2.22 | 0.00 |
July | 1.72 | 0.00 |
August | 1.74 | 0.00 |
September | 1.63 | 0.00 |
October | 1.15 | 0.00 |
November | 0.68 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 15.69 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.35 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 6.91 | 0.00 |
February | 3.30 | 0.00 |
March | 0.69 | 0.00 |
April | 2.61 | 0.00 |
May | 2.49 | 0.00 |
June | 3.57 | 0.00 |
July | 2.33 | 0.00 |
August | 0.92 | 0.00 |
September | 1.17 | 0.00 |
October | 1.08 | 0.00 |
November | 4.63 | 0.00 |
December | 7.18 | 0.00 |
Annual Sum or Average | 36.88 | 0.00 |
Minimum of Months | 0.69 | 0.00 |
Maximum of Months | 7.18 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.210666E+10 | 0.375368E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.268852E+10 | 0.697973E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.611873E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.107162E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.159419E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.169727E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.168368E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.154717E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.124311E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.888543E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.443827E+10 | 2766515.95 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.219965E+10 | 0.153607E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.114808E+12 | 0.599049E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.210666E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.169727E+11 | 0.375368E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.110181E+11 | 0.573519E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.154412E+11 | 0.625542E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.302619E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.465075E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.659723E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.704505E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.702346E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.669345E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.545419E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.397003E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.238059E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.126562E+11 | 0.117073E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.507525E+12 | 0.753146E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.110181E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.704505E+11 | 0.573519E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.213356E+10 | 0.443577E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.276775E+10 | 70632457.90 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.473085E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.684780E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.925215E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.967678E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.971416E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.926160E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.800200E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.666432E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.449792E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.261990E+10 | 67331332.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.761688E+11 | 0.581541E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.213356E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.971416E+10 | 0.443577E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.153917E+10 | 0.901998E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.212951E+10 | 0.187012E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.390217E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.596239E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.819705E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.852619E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.864267E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.819807E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.703772E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.580500E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.373593E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.191257E+10 | 0.183940E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.655885E+11 | 0.127295E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.153917E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.864267E+10 | 0.901998E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.204637E+10 | 0.214765E+09 | 0.300294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179136E+10 | 0.320834E+10 | 0.558379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200201E+10 | 0.147111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198922E+10 | 0.305226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.236550E+10 | 0.471395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.251239E+10 | 0.508606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.249894E+10 | 0.543441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.232752E+10 | 0.515029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.203388E+10 | 0.401921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.199935E+10 | 0.251623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188551E+10 | 0.908952E+10 | 2213212.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199584E+10 | 0.720508E+09 | 0.122886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254479E+11 | 0.327668E+12 | 0.479239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.179136E+10 | 0.214765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251239E+10 | 0.543441E+11 | 0.300294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.937946E+10 | 0.539670E+10 | 0.458815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.837315E+10 | 0.237694E+11 | 0.500433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.937549E+10 | 0.709623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.936916E+10 | 0.122103E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113806E+11 | 0.177913E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121351E+11 | 0.195950E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122926E+11 | 0.211639E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119173E+11 | 0.208085E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.996020E+10 | 0.166959E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.927466E+10 | 0.105788E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.887069E+10 | 0.505898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.925853E+10 | 0.112542E+11 | 0.936581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121587E+12 | 0.135041E+13 | 0.602517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.837315E+10 | 0.539670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122926E+11 | 0.211639E+12 | 0.458815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.105081E+10 | 0.422049E+10 | 0.354862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.948356E+09 | 0.722718E+10 | 56505966.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107963E+10 | 0.142927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113391E+10 | 0.209385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135164E+10 | 0.280813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140830E+10 | 0.299191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142354E+10 | 0.324292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138204E+10 | 0.318590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124064E+10 | 0.272209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114704E+10 | 0.219792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101627E+10 | 0.141883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104475E+10 | 0.622988E+10 | 53865065.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142269E+11 | 0.238586E+12 | 0.465233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.948356E+09 | 0.422049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142354E+10 | 0.324292E+11 | 0.354862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.960518E+09 | 0.220775E+10 | 0.721598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.858238E+09 | 0.495768E+10 | 0.149610E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.970673E+09 | 0.113146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101438E+10 | 0.180307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120537E+10 | 0.248887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124676E+10 | 0.264603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127047E+10 | 0.290074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122442E+10 | 0.283752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110640E+10 | 0.239036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102714E+10 | 0.189261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.914261E+09 | 0.113464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.946185E+09 | 0.374323E+10 | 0.147152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127448E+11 | 0.203162E+12 | 0.101836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.858238E+09 | 0.220775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127047E+10 | 0.290074E+11 | 0.721598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.204637E+10 | 0.00 | 0.00 | 0.00 | 60293824.35 | 0.00 | 0.375368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179136E+10 | 0.00 | 0.00 | 0.00 | 0.897155E+09 | 0.00 | 0.697973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200201E+10 | 0.00 | 0.00 | 0.00 | 0.411672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198922E+10 | 0.00 | 0.00 | 0.00 | 0.872700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.236550E+10 | 0.00 | 0.00 | 0.00 | 0.135764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.251239E+10 | 0.00 | 0.00 | 0.00 | 0.144603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.249894E+10 | 0.00 | 0.00 | 0.00 | 0.143378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.232752E+10 | 0.00 | 0.00 | 0.00 | 0.131441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.203388E+10 | 0.00 | 0.00 | 0.00 | 0.103973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.199935E+10 | 0.00 | 0.00 | 0.00 | 0.688607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188551E+10 | 0.00 | 0.00 | 0.00 | 0.255277E+10 | 0.00 | 2766515.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199584E+10 | 0.00 | 0.00 | 0.00 | 0.203814E+09 | 0.00 | 0.153607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254479E+11 | 0.00 | 0.00 | 0.00 | 0.893598E+11 | 0.00 | 0.599049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.179136E+10 | 0.00 | 0.00 | 0.00 | 60293824.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251239E+10 | 0.00 | 0.00 | 0.00 | 0.144603E+11 | 0.00 | 0.375368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.937946E+10 | 0.00 | 0.00 | 0.00 | 0.163865E+10 | 0.00 | 0.573519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.837315E+10 | 0.00 | 0.00 | 0.00 | 0.706805E+10 | 0.00 | 0.625542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.937549E+10 | 0.00 | 0.00 | 0.00 | 0.208864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.936916E+10 | 0.00 | 0.00 | 0.00 | 0.371384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113806E+11 | 0.00 | 0.00 | 0.00 | 0.545917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121351E+11 | 0.00 | 0.00 | 0.00 | 0.583154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122926E+11 | 0.00 | 0.00 | 0.00 | 0.579420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119173E+11 | 0.00 | 0.00 | 0.00 | 0.550172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.996020E+10 | 0.00 | 0.00 | 0.00 | 0.445817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.927466E+10 | 0.00 | 0.00 | 0.00 | 0.304257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.887069E+10 | 0.00 | 0.00 | 0.00 | 0.149352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.925853E+10 | 0.00 | 0.00 | 0.00 | 0.339770E+10 | 0.00 | 0.117073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121587E+12 | 0.00 | 0.00 | 0.00 | 0.385938E+12 | 0.00 | 0.753146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.837315E+10 | 0.00 | 0.00 | 0.00 | 0.163865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122926E+11 | 0.00 | 0.00 | 0.00 | 0.583154E+11 | 0.00 | 0.573519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.105081E+10 | 0.00 | 0.00 | 0.00 | 0.108275E+10 | 0.00 | 0.443577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.948356E+09 | 0.00 | 0.00 | 0.00 | 0.181939E+10 | 0.00 | 70632457.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107963E+10 | 0.00 | 0.00 | 0.00 | 0.365122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113391E+10 | 0.00 | 0.00 | 0.00 | 0.571389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135164E+10 | 0.00 | 0.00 | 0.00 | 0.790051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140830E+10 | 0.00 | 0.00 | 0.00 | 0.826848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142354E+10 | 0.00 | 0.00 | 0.00 | 0.829062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138204E+10 | 0.00 | 0.00 | 0.00 | 0.787956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124064E+10 | 0.00 | 0.00 | 0.00 | 0.676137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114704E+10 | 0.00 | 0.00 | 0.00 | 0.551728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101627E+10 | 0.00 | 0.00 | 0.00 | 0.348164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104475E+10 | 0.00 | 0.00 | 0.00 | 0.157515E+10 | 0.00 | 67331332.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142269E+11 | 0.00 | 0.00 | 0.00 | 0.619419E+11 | 0.00 | 0.581541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.948356E+09 | 0.00 | 0.00 | 0.00 | 0.108275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142354E+10 | 0.00 | 0.00 | 0.00 | 0.829062E+10 | 0.00 | 0.443577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.960518E+09 | 0.00 | 0.00 | 0.00 | 0.578656E+09 | 0.00 | 0.901998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.858238E+09 | 0.00 | 0.00 | 0.00 | 0.127128E+10 | 0.00 | 0.187012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.970673E+09 | 0.00 | 0.00 | 0.00 | 0.293150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101438E+10 | 0.00 | 0.00 | 0.00 | 0.494802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120537E+10 | 0.00 | 0.00 | 0.00 | 0.699168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124676E+10 | 0.00 | 0.00 | 0.00 | 0.727943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127047E+10 | 0.00 | 0.00 | 0.00 | 0.737220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122442E+10 | 0.00 | 0.00 | 0.00 | 0.697366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110640E+10 | 0.00 | 0.00 | 0.00 | 0.593133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102714E+10 | 0.00 | 0.00 | 0.00 | 0.477785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.914261E+09 | 0.00 | 0.00 | 0.00 | 0.282167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.946185E+09 | 0.00 | 0.00 | 0.00 | 0.966389E+09 | 0.00 | 0.183940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127448E+11 | 0.00 | 0.00 | 0.00 | 0.528437E+11 | 0.00 | 0.127295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.858238E+09 | 0.00 | 0.00 | 0.00 | 0.578656E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127047E+10 | 0.00 | 0.00 | 0.00 | 0.737220E+10 | 0.00 | 0.901998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.276567E+10 | 0.00 | 0.00 | 234685.92 | 0.00 | 0.178206E+10 | 0.209302E+09 | 0.00 | 0.22 |
February | 0.147219E+10 | 19176764.23 | 0.00 | 3389642.95 | 0.00 | 0.452282E+09 | 0.823178E+09 | 0.00 | 0.22 |
March | 0.313059E+09 | 0.120646E+10 | 0.00 | 6932733.41 | 143794.97 | 0.00 | 0.553066E+09 | 0.00 | 0.23 |
April | 0.00 | 0.418627E+10 | 0.00 | 2189901.42 | 385174.69 | 0.00 | 19379687.14 | 0.00 | 0.23 |
May | 0.00 | 0.943389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
June | 0.00 | 0.125660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
July | 0.00 | 0.159172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.161122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
September | 0.00 | 0.120274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
October | 1751789.43 | 0.417717E+10 | 0.00 | 2307548.30 | 0.00 | 0.00 | 65038992.35 | 0.00 | 0.22 |
November | 0.659397E+09 | 0.414218E+09 | 0.00 | 5194547.99 | 0.00 | 0.00 | 0.698952E+09 | 0.00 | 0.22 |
December | 0.254873E+10 | 0.00 | 0.00 | 824501.19 | 55413.62 | 0.108553E+10 | 0.715520E+09 | 0.00 | 0.22 |
Annual Sum or Average | 0.776080E+10 | 0.760600E+11 | 0.00 | 21073561.19 | 584383.28 | 0.331988E+10 | 0.308444E+10 | 0.00 | 0.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 0.276567E+10 | 0.161122E+11 | 0.00 | 6932733.41 | 385174.69 | 0.178206E+10 | 0.823178E+09 | 0.00 | 0.24 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.225283E+11 | 0.00 | 0.00 | 11963117.06 | 0.00 | 0.202955E+10 | 0.901476E+10 | 0.00 | 0.42 |
February | 0.972773E+10 | 0.473227E+09 | 0.00 | 28685158.12 | 0.00 | 89686639.58 | 0.784876E+10 | 0.00 | 0.43 |
March | 0.229468E+10 | 0.109304E+11 | 0.00 | 29494590.90 | 28587742.64 | 0.00 | 0.309652E+10 | 0.00 | 0.44 |
April | 81789589.62 | 0.330696E+11 | 0.00 | 5083299.00 | 0.394154E+09 | 0.00 | 0.130477E+09 | 0.00 | 0.44 |
May | 0.00 | 0.689518E+11 | 0.00 | 81293.81 | 0.605654E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.890303E+11 | 0.00 | 0.00 | 0.884527E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.109931E+12 | 0.00 | 0.00 | 0.126767E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.110750E+12 | 0.00 | 0.00 | 0.145928E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.823802E+11 | 0.00 | 0.00 | 0.132602E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.454860E+09 | 0.305785E+11 | 0.00 | 7124410.48 | 0.454129E+09 | 0.00 | 0.629169E+09 | 0.00 | 0.43 |
November | 0.470257E+10 | 0.534507E+10 | 0.00 | 27806895.61 | 0.00 | 0.00 | 0.433997E+10 | 0.00 | 0.43 |
December | 0.183177E+11 | 0.00 | 0.00 | 22433548.75 | 0.00 | 0.197337E+09 | 0.105154E+11 | 0.00 | 0.42 |
Annual Sum or Average | 0.581077E+11 | 0.541440E+12 | 0.00 | 0.132672E+09 | 0.642003E+10 | 0.231657E+10 | 0.355751E+11 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.225283E+11 | 0.110750E+12 | 0.00 | 29494590.90 | 0.145928E+10 | 0.202955E+10 | 0.105154E+11 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123477E+10 | 0.00 | 0.00 | 9973017.08 | 0.00 | 0.160665E+09 | 0.160079E+10 | 0.00 | 0.42 |
February | 0.580843E+09 | 0.137292E+09 | 0.00 | 9150968.70 | 0.00 | 28364200.15 | 0.782285E+09 | 0.00 | 0.43 |
March | 72025153.17 | 0.132847E+10 | 0.00 | 6835488.79 | 194119.19 | 0.00 | 0.306587E+09 | 0.00 | 0.44 |
April | 0.00 | 0.348573E+10 | 0.00 | 1327639.87 | 483681.16 | 0.00 | 10298457.64 | 0.00 | 0.45 |
May | 0.00 | 0.725012E+10 | 0.00 | 27567.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.00 | 0.952808E+10 | 0.00 | 0.00 | 522738.25 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.120171E+11 | 0.00 | 0.00 | 484798.48 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.122131E+11 | 0.00 | 0.00 | 519989.88 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.936518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.378403E+10 | 0.00 | 2222448.99 | 0.00 | 0.00 | 17935356.37 | 0.00 | 0.44 |
November | 95138794.63 | 0.867344E+09 | 0.00 | 9098416.88 | 0.00 | 0.00 | 0.467210E+09 | 0.00 | 0.43 |
December | 0.909710E+09 | 5288418.64 | 0.00 | 13057484.82 | 0.00 | 12578830.13 | 0.141630E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.289249E+10 | 0.599817E+11 | 0.00 | 51693032.72 | 2205326.96 | 0.201608E+09 | 0.460141E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.123477E+10 | 0.122131E+11 | 0.00 | 13057484.82 | 522738.25 | 0.160665E+09 | 0.160079E+10 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135469E+10 | 0.00 | 0.00 | 4926746.55 | 0.00 | 0.501107E+09 | 0.121628E+10 | 0.00 | 0.42 |
February | 0.735274E+09 | 0.103549E+09 | 0.00 | 5827954.39 | 0.00 | 83255170.94 | 0.667717E+09 | 0.00 | 0.43 |
March | 0.173274E+09 | 0.123121E+10 | 0.00 | 4901692.61 | 75917.47 | 0.00 | 0.265377E+09 | 0.00 | 0.44 |
April | 0.00 | 0.342501E+10 | 0.00 | 966114.86 | 91733.16 | 0.00 | 12007226.16 | 0.00 | 0.44 |
May | 0.00 | 0.711798E+10 | 0.00 | 2896.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.929100E+10 | 0.00 | 0.00 | 177653.57 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.117169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.118861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.902482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.364958E+10 | 0.00 | 1935385.22 | 0.00 | 0.00 | 26389689.01 | 0.00 | 0.44 |
November | 0.198736E+09 | 0.808032E+09 | 0.00 | 6649460.27 | 0.00 | 0.00 | 0.422629E+09 | 0.00 | 0.43 |
December | 0.114404E+10 | 2807027.02 | 0.00 | 7806201.01 | 0.00 | 89584077.79 | 0.123892E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.360602E+10 | 0.582570E+11 | 0.00 | 33016451.19 | 345304.20 | 0.673946E+09 | 0.384932E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.135469E+10 | 0.118861E+11 | 0.00 | 7806201.01 | 177653.57 | 0.501107E+09 | 0.123892E+10 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |