Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2020-06-03 19:13:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1135.80 | 495.12 | 495.12 |
Net Site Energy | 1135.80 | 495.12 | 495.12 |
Total Source Energy | 3084.32 | 1344.52 | 1344.52 |
Net Source Energy | 3084.32 | 1344.52 | 1344.52 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 154.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 216.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 294.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 38.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 91.28 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 889.64 | 246.16 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 154.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 216.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 294.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 38.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 145.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 91.28 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 145.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 157.93 | 107.31 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 387.81 | 107.31 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 145.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 157.93 | 107.31 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 387.81 | 107.31 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 889.639 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 889.639 | 100.00 |
Total On-Site and Utility Electric Sources | 889.639 | 100.00 |
Total Electricity End Uses | 889.639 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1068.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.5670 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 13.1320 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 13.1320 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 13.1320 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 10.7639 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 12.1980 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 12.1980 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-JUL-14:20 | 12-FEB-09:09 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 186475.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48868.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19720.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10174.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 89504.82 | 188335.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 186475.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 48868.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19720.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 10174.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 167.88 | 0.00 | 0.00 | 0.00 |
Cooling | 686.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 932.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 121.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 615.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 460.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 98.95 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2817.49 | 266.83 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 73.18 | 0.00 | 0.00 | 0.00 |
Cooling | 299.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 406.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 200.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 43.13 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1228.20 | 116.32 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 73.18 | 0.00 | 0.00 | 0.00 |
Cooling | 299.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 406.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 200.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 43.13 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1228.20 | 116.32 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.93 |
CORE_RETAIL DIRECT AIR | 7.09 |
POINT_OF_SALE DIRECT AIR | 1.09 |
FRONT_RETAIL DIRECT AIR | 0.826495 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 1.14 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 1.14 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 32546.71 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 50308.85 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 218316.02 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 29879.99 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 24065.59 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.93 | 1.93 | 1.93 | 1.93 | 1.94 | 1.94 | 1.00 | 0.992946 | 1.94 |
PSZ-AC:2 | 7.09 | 7.09 | 7.09 | 7.09 | 7.29 | 7.29 | 1.00 | 0.973273 | 7.29 |
PSZ-AC:3 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.00 | 1.00 | 1.09 |
PSZ-AC:4 | 0.826495 | 0.826495 | 0.826495 | 0.826495 | 0.827577 | 0.827577 | 1.00 | 0.998692 | 0.827577 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.94 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 7.29 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.09 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 0.827577 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.94 | 1.94 | 1.94 | 1.28 | 37212.35 | 50308.85 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.29 | 7.29 | 7.29 | 4.81 | 175054.19 | 218316.02 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.09 | 1.09 | 1.09 | 0.717738 | 22761.83 | 29879.99 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.827577 | 0.827577 | 0.827577 | 0.827577 | 18450.03 | 24065.59 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.94 | 0.971255 | 1.30 | 34761.11 | 37212.35 | 18606.17 | 18606.17 | 0.748693 | 0.748690 | 0.748690 | 0.748690 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 7.29 | 3.64 | 4.86 | 166179.33 | 175054.19 | 87527.10 | 87527.10 | 0.684400 | 0.684400 | 0.684400 | 0.684400 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.09 | 0.543740 | 0.724987 | 21379.41 | 22761.83 | 11380.92 | 11380.92 | 0.721768 | 0.721770 | 0.721770 | 0.721770 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 0.827580 | 0.413790 | 0.551720 | 17418.15 | 18450.03 | 9225.01 | 9225.01 | 0.703989 | 0.703990 | 0.703990 | 0.703990 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.94 | 2078.58 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.29 | 12279.27 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.09 | 1204.02 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.827577 | 916.26 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.567 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.637 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 13.132 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 16.362 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 13.132 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 34.652 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 13.132 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 16.362 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 10.764 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.764 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2874.639 | 7.567 | 46.863 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2874.639 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 21017.495 | 13.132 | 81.326 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21017.495 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 1980.433 | 13.132 | 81.326 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1980.433 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 1980.433 | 13.132 | 81.326 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1980.433 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 129.167 | 10.764 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 129.167 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.7800 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 9 | -0.41768822E-14 | 0.27520919E-16 | -0.15672466E-09 | 0.83927561E-16 |
25 | 8 | 0.22856702E-07 | 0.10578700E-12 | 0.38803401E-03 | -0.25988854E-09 |
26 | 7 | -0.12546900E-01 | 0.54357740E-08 | -0.23525379E-01 | 0.14266284E-03 |
27 | 6 | 0.41364683 | 0.18861797E-05 | 0.47915075 | -0.48455579E-02 |
28 | 5 | -5.2715232 | 0.70271773E-04 | -4.4954566 | 0.64187715E-01 |
29 | 4 | 33.360936 | 0.57369956E-03 | 21.652120 | -0.42687724 |
30 | 3 | -111.98802 | 0.12481219E-02 | -56.042688 | 1.5262008 |
31 | 2 | 197.88617 | 0.70096321E-03 | 78.258916 | -2.9127067 |
32 | 1 | -171.44340 | 0.74721452E-04 | -55.366563 | 2.7504751 |
33 | 0 | 57.057407 | 0.42462867E-06 | 15.540328 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.45_SHGC_0.25 | 30 | 1 | VerySmooth | 2.557 | 0.252 | 0.162 | 0.276 |
2 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 31 | 1 | VerySmooth | 3.127 | 0.346 | 0.263 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.15759E-002 | 0.26293 | 0.50711 | 0.50711 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 7.71143E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1915 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 21933.82559 | 26320.59071 | 1.60734 | 1.92881 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 21577.19118 | 25892.62942 | 0.94068 | 1.12882 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 81055.68102 | 97266.81722 | 5.91152 | 7.09383 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 52742.61580 | 63291.13897 | 2.26452 | 2.71742 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 12243.85865 | 14692.63038 | 0.90624 | 1.08748 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 10643.23874 | 12771.88649 | 0.46599 | 0.55918 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 9377.84568 | 11253.41482 | 0.68875 | 0.82650 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 10646.33877 | 12775.60653 | 0.46612 | 0.55935 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40000 | 1.44457E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 27114.88595 | 32537.86313 | 0.95104 | 1.14125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | -6.30000 | 2.29779E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 26224.86 | 1.94251 | 1.94251 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 32491.57 | 1.12882 | 1.12882 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 108455.01 | 7.28864 | 7.28864 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 120573.54 | 2.71742 | 2.71742 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 15535.05 | 1.08748 | 1.08748 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 18110.29 | 0.55918 | 0.55918 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 12663.68 | 0.82758 | 0.82758 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 18113.98 | 0.55935 | 0.55935 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.92881 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.09383 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08748 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.82650 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.14125 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.14125 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 32546.71308 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.92881 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.92881 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.92881 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.92881 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.94251 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.94251 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.99295 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.09383 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.09383 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.09383 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.09383 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.28864 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.28864 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97327 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08748 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08748 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08748 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08748 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.08748 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.08748 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.82650 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.82650 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.82650 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.82650 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.82758 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.82758 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 0.99869 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.94251 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.28864 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.08748 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.82758 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.94251 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.94251 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.94251 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.94251 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.28206 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.94251 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.97126 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.29501 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 34761.10727 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 37212.35000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 18606.17500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 18606.17500 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74869 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74869 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74869 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74869 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37212.35000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 50308.85399 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.94251 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2078.57716 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 50308.85399 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.28864 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.28864 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.28864 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.28864 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.81050 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.28864 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.64432 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.85909 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 166179.32591 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 175054.19000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 87527.09500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 87527.09500 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68440 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68440 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68440 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68440 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 175054.19000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 218316.02238 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.28864 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 12279.27022 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 218316.02238 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.08748 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.08748 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.08748 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.08748 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71774 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.08748 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54374 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.72499 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21379.41242 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22761.83000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11380.91500 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11380.91500 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72177 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72177 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72177 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72177 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22761.83000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29879.99031 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.08748 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1204.01566 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29879.99031 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.82758 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.82758 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.82758 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.82758 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.82758 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.82758 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.41379 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.55172 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17418.14667 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18450.03000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9225.01500 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9225.01500 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70399 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70399 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70399 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70399 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18450.03000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24065.58803 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.82758 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 916.25947 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 24065.58803 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 35686.8 | 11.44 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 169307.8 | 13.08 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 21906.6 | 120.39 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 17798.5 | 172.76 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | N/A | 3.127 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 13 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 5.2997938905E-002 | 0.2245670350 | Pass | Pass | 0.2496768949 | 0.9880720984 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 3.1360558041E-002 | 0.1259838773 | Pass | Pass | 0.1105461396 | 0.3165469040 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 5.6709381596E-002 | 0.2350946299 | Pass | Pass | 0.2137368478 | 0.6706703944 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 6.4813724042E-002 | 0.2746523034 | Pass | Pass | 6.6879282152E-002 | 0.2256967825 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1380352226 | 0.5879186750 | Pass | Pass | 6.1294512002E-002 | 0.6110736830 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.55_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.346 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.45_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.557 | 0.252 | 0.276 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.45_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.557 | 0.252 | 0.276 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.45_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.557 | 0.252 | 0.276 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 2.683 | 0.273 | 0.303 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 2.683 | 0.273 | 0.303 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.5670 | 379.89 | 2874.64 | LightsWired | BLDG_LIGHT_BACK_SCH | 55.08 | 168.00 | 52.05 | 0.0000 | Y | 28.09 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 13.1320 | 1600.48 | 21017.49 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 55.46 | 0.0000 | Y | 218.81 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 13.1320 | 150.81 | 1980.43 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 65.03 | 0.0000 | Y | 24.18 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 13.1320 | 150.81 | 1980.43 | LightsWired | BLDG_LIGHT_FRONT_SCH | 67.15 | 168.00 | 63.01 | 0.0000 | Y | 23.42 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 10.7639 | 12.00 | 129.17 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 57.54 | 168.00 | 3.36 | 0.0000 | Y | 0.08 |
Interior Lighting Total | 12.1980 | 2293.99 | 27982.17 | 294.58 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 21017.49 | 5254.37 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 21017.49 | 5254.37 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 316.30 | AstronomicalClock | - | 41.77 | 41.77 | 2.48 | |
EXTERIOR_LIGHTS_B | 3054.90 | AstronomicalClock | - | 83.77 | 62.77 | 36.00 | |
Exterior Lighting Total | 3371.20 | 38.48 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 37212.35 | 27860.51 | 9351.84 | 0.75 | 3.80 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 175054.19 | 119807.09 | 55247.10 | 0.68 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22761.83 | 16428.81 | 6333.02 | 0.72 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18450.03 | 12988.64 | 5461.39 | 0.70 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 35686.8 | 11.44 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 169307.8 | 13.08 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 21906.6 | 120.39 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 17798.5 | 172.76 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 32546.71 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 50308.85 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 218316.02 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29879.99 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 24065.59 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.56 | 622.50 | 1.14 | 1263.55 | 1107.16 | 1.00 | 1.36 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.94 | 2078.58 | 1070.05 | 1.00 | 1.32 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 7.29 | 12279.27 | 1684.71 | 1.00 | 1.16 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.09 | 1204.02 | 1107.16 | 1.00 | 1.38 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.83 | 916.26 | 1107.16 | 1.00 | 1.45 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 21933.83 | 26320.59 | 69.28 | 1.607 | 1.929 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00970 | 27.37 | 0.01445 | 0.232 | 0.00 |
CORE_RETAIL | 81055.68 | 97266.82 | 60.77 | 5.912 | 7.094 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.00996 | 27.37 | 0.01445 | 1.890 | 0.00 |
POINT_OF_SALE | 12243.86 | 14692.63 | 97.42 | 0.906 | 1.087 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00906 | 27.37 | 0.01445 | 0.178 | 0.00 |
FRONT_RETAIL | 9377.85 | 11253.41 | 74.62 | 0.689 | 0.826 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00961 | 27.37 | 0.01445 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 33.67 | 100.00 | 0.00001 | 34.40 | 0.01445 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 21577.19 | 25892.63 | 68.16 | 0.941 | 1.129 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00743 | -6.30 | 0.00230 | 0.232 | 0.00 |
CORE_RETAIL | 52742.62 | 63291.14 | 39.55 | 2.265 | 2.717 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00744 | -6.30 | 0.00230 | 1.890 | 0.00 |
POINT_OF_SALE | 10643.24 | 12771.89 | 84.69 | 0.466 | 0.559 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00764 | -6.30 | 0.00230 | 0.178 | 0.00 |
FRONT_RETAIL | 10646.34 | 12775.61 | 84.71 | 0.466 | 0.559 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00764 | -6.30 | 0.00230 | 0.178 | 0.00 |
FRONT_ENTRY | 27114.89 | 32537.86 | 2711.49 | 0.951 | 1.141 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 16.00 | 15.91 | 0.00504 | -6.30 | 0.00230 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.94 | 1.94 | 1.13 | 1.13 | 1.9425 | 1.9288 | 1.9425 | 0.9929 | 1.0000 |
PSZ-AC:2 | 7.29 | 7.29 | 2.72 | 2.72 | 7.2886 | 7.0938 | 7.2886 | 0.9733 | 1.0000 |
PSZ-AC:3 | 1.09 | 1.09 | 0.56 | 0.56 | 1.0875 | 1.0875 | 1.0875 | 1.0000 | 1.0000 |
PSZ-AC:4 | 0.83 | 0.83 | 0.56 | 0.56 | 0.8276 | 0.8265 | 0.8276 | 0.9987 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 32546.713 | 32546.713 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 32546.71 | 32546.71 | 1.141251 | 15.63 | 9.34 | 0.00500539 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 15.91 | 0.00503943 | 43.4195 | 32537.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 18606.175 | 0.000 | 1.942510 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 18606.17 | 14318.12 | 1.942510 | 24.37 | 17.45 | 0.01009959 | 12.80 | 11.77 | 0.00850000 | 27.97 | 0.01444568 | 21.76 | 11.9210 | 23.89 | 0.00970353 | 50.6130 | 21933.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 50308.854 | 50308.854 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 50308.85 | 50308.85 | 1.942510 | 15.33 | 10.66 | 0.00637770 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 11.9210 | 21.11 | 0.00743065 | 46.0487 | 21577.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 87527.095 | 0.000 | 7.288640 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 87527.10 | 64384.26 | 7.288640 | 26.90 | 18.81 | 0.01078013 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01444567 | 23.51 | 25.9337 | 23.88 | 0.00996358 | 51.9502 | 79781.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 218316.022 | 218316.022 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 218316.02 | 218316.02 | 7.288635 | 1.97 | 1.06 | 0.00386252 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 25.9337 | 21.11 | 0.00743798 | 46.0911 | 52742.62 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 11380.915 | 0.000 | 1.087480 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 11380.92 | 9116.55 | 1.087480 | 25.70 | 17.78 | 0.00995760 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01444567 | 23.51 | 16.3783 | 23.89 | 0.00906269 | 47.3125 | 11300.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 29879.990 | 29879.990 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29879.99 | 29879.99 | 1.087482 | 12.24 | 8.85 | 0.00593782 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 16.3782 | 21.11 | 0.00763913 | 47.3237 | 10643.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 9225.015 | 0.000 | 0.827580 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 9225.01 | 7091.54 | 0.827580 | 26.20 | 18.23 | 0.01032472 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01444567 | 23.51 | 21.5219 | 23.89 | 0.00961443 | 50.1552 | 8870.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 24065.588 | 24065.588 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24065.59 | 24065.59 | 0.827577 | 12.24 | 8.85 | 0.00593853 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 21.5219 | 21.11 | 0.00763943 | 47.3255 | 10646.34 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 32546.713 | 32546.713 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 1.141251 | 1.32496524 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 32546.71 | 32546.71 | 1.0000 | 1.32496524 | 1.141251 | 15.63 | 9.34 | 0.00500539 | 28374.1 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32546.71 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 15.92 | 0.00503943 | 15.91 | 0.00503943 | 43.4195 | 32537.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18606.175 | 0.000 | 1.942510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6146 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 18606.17 | 14318.12 | 1.0000 | 2.25520854 | 1.942510 | 24.37 | 17.45 | 0.01009959 | 50206.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18606.17 | 27.97 | 0.01444568 | 21.76 | 0.23156651 | 11.9210 | 23.89 | 0.00951137 | 23.89 | 0.00970353 | 50.6130 | 21933.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 50308.854 | 50308.854 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.942510 | 2.25520815 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 50308.85 | 50308.85 | 1.0000 | 2.25520815 | 1.942510 | 15.33 | 10.66 | 0.00637770 | 31533.4 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50308.85 | -6.30 | 0.00229779 | -6.30 | 0.23156651 | 11.9210 | 20.91 | 0.00743065 | 21.11 | 0.00743065 | 46.0487 | 21577.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 87527.095 | 0.000 | 7.288640 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8797 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 87527.10 | 64384.26 | 1.0000 | 8.46194005 | 7.288640 | 26.90 | 18.81 | 0.01078013 | 54531.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87527.10 | 34.40 | 0.01444567 | 23.51 | 1.89021192 | 25.9337 | 23.89 | 0.00930662 | 23.88 | 0.00996358 | 51.9502 | 79781.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 218316.022 | 218316.022 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.288635 | 8.46193434 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 218316.02 | 218316.02 | 1.0000 | 8.46193434 | 7.288635 | 1.97 | 1.06 | 0.00386252 | 11650.1 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 218316.02 | -6.30 | 0.00229779 | -6.30 | 1.89021192 | 25.9337 | 20.86 | 0.00743798 | 21.11 | 0.00743798 | 46.0911 | 52742.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11380.915 | 0.000 | 1.087480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3507 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 11380.92 | 9116.55 | 1.0000 | 1.26253877 | 1.087480 | 25.70 | 17.78 | 0.00995760 | 51205.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11380.92 | 34.40 | 0.01444567 | 23.51 | 0.17811053 | 16.3783 | 23.89 | 0.00902157 | 23.89 | 0.00906269 | 47.3125 | 11300.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29879.990 | 29879.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.087482 | 1.26254158 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29879.99 | 29879.99 | 1.0000 | 1.26254158 | 1.087482 | 12.24 | 8.85 | 0.00593782 | 27283.0 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29879.99 | -6.30 | 0.00229779 | -6.30 | 0.17811053 | 16.3782 | 20.90 | 0.00763913 | 21.11 | 0.00763913 | 47.3237 | 10643.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9225.015 | 0.000 | 0.827580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0331 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 9225.01 | 7091.54 | 1.0000 | 0.96080097 | 0.827580 | 26.20 | 18.23 | 0.01032472 | 52650.2 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9225.01 | 34.40 | 0.01444567 | 23.51 | 0.17811053 | 21.5219 | 23.89 | 0.00916340 | 23.89 | 0.00961443 | 50.1552 | 8870.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24065.588 | 24065.588 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.827577 | 0.96079786 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24065.59 | 24065.59 | 1.0000 | 0.96079786 | 0.827577 | 12.24 | 8.85 | 0.00593853 | 27287.4 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24065.59 | -6.30 | 0.00229779 | -6.30 | 0.17811053 | 21.5219 | 20.90 | 0.00763943 | 21.11 | 0.00763943 | 47.3255 | 10646.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialEnthalpy | 0.23 | 1.94 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialEnthalpy | 1.89 | 7.29 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialEnthalpy | 0.18 | 1.09 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialEnthalpy | 0.18 | 0.83 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 2639.33 | 2629.67 | 921.17 |
CORE_RETAIL | 2628.67 | 2332.00 | 583.00 |
POINT_OF_SALE | 2620.67 | 1891.67 | 332.50 |
FRONT_RETAIL | 2623.50 | 2362.00 | 672.33 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3211.33 | 2778.17 | 1068.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 15.83 | 9.83 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 8.67 | 91.50 | 0.00 | 0.00 |
FRONT_RETAIL | 15.00 | 20.50 | 0.00 | 0.00 |
FRONT_ENTRY | 391.83 | 0.00 | 0.00 | 0.00 |
Facility | 410.50 | 105.83 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.32 | 61.34 | 2317.33 | 0.517 | 0.029 | 0.000 | 0.000 |
CORE_RETAIL | 127.72 | 258.43 | 9762.95 | 0.800 | 0.006 | 0.000 | 0.000 |
POINT_OF_SALE | 12.04 | 24.35 | 919.94 | 0.971 | 0.032 | 0.000 | 0.000 |
FRONT_RETAIL | 12.04 | 24.35 | 919.94 | 0.958 | 0.032 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.32 | 61.34 | 2317.33 | 0.352 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 127.72 | 258.43 | 9762.95 | 0.681 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.04 | 24.35 | 919.94 | 0.681 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.04 | 24.35 | 919.94 | 0.681 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 889.64 | 2265.44 | 19-FEB-07:40 | 89504.82 | 08-JUL-14:20 |
Electricity:Building | 488.88 | 2265.44 | 01-JAN-00:10 | 35190.60 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 77.86 | 535.60 | 01-JAN-00:10 | 4774.71 | 02-JAN-09:10 |
InteriorLights:Electricity | 294.58 | 493.85 | 01-JAN-00:10 | 24449.72 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 28.09 | 81.78 | 01-JAN-00:10 | 2023.29 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 294.58 | 493.85 | 01-JAN-00:10 | 24449.72 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 302.74 | 1109.80 | 01-JAN-00:10 | 23555.33 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 218.81 | 344.55 | 01-JAN-00:10 | 18915.75 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 76.87 | 512.89 | 01-JAN-00:10 | 4695.10 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 24.18 | 32.47 | 01-JAN-00:10 | 1782.39 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 31.33 | 104.57 | 01-JAN-00:10 | 2162.89 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 23.42 | 32.47 | 01-JAN-00:10 | 1725.71 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 0.08 | 2.58 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 0.08 | 2.58 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 |
InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.77 | 453.82 | 01-JAN-00:10 | 2751.42 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 83.93 | 765.25 | 01-JAN-00:10 | 4639.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.69 | 480.42 | 01-JAN-00:10 | 2912.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.91 | 72.11 | 01-JAN-00:10 | 437.18 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 889.64 | 2265.44 | 19-FEB-07:40 | 89504.82 | 08-JUL-14:20 |
ElectricityPurchased:Plant | 889.64 | 2265.44 | 19-FEB-07:40 | 89504.82 | 08-JUL-14:20 |
Cogeneration:ElectricityPurchased | 889.64 | 2265.44 | 19-FEB-07:40 | 89504.82 | 08-JUL-14:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 889.64 | 2265.44 | 19-FEB-07:40 | 89504.82 | 08-JUL-14:20 |
ElectricityNet:Plant | 889.64 | 2265.44 | 19-FEB-07:40 | 89504.82 | 08-JUL-14:20 |
Cogeneration:ElectricityNet | 889.64 | 2265.44 | 19-FEB-07:40 | 89504.82 | 08-JUL-14:20 |
Electricity:HVAC | 362.29 | 0.00 | 01-JAN-00:10 | 59043.15 | 08-JUL-14:20 |
Fans:Electricity | 145.53 | 0.00 | 01-JAN-00:10 | 12676.40 | 12-FEB-09:10 |
General:Fans:Electricity | 145.53 | 0.00 | 01-JAN-00:10 | 12676.40 | 12-FEB-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 216.76 | 0.00 | 01-JAN-00:10 | 48868.44 | 08-JUL-14:20 |
ExteriorLights:Electricity | 38.48 | 0.00 | 01-JAN-07:50 | 3371.20 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 38.48 | 0.00 | 01-JAN-07:50 | 3371.20 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 246.16 | 1860.00 | 09-JAN-05:40 | 188335.55 | 12-FEB-09:10 |
Gas:Plant | 91.28 | 1860.00 | 09-JAN-05:40 | 5043.91 | 01-FEB-13:00 |
WaterSystems:Gas | 91.28 | 1860.00 | 09-JAN-05:40 | 5043.91 | 01-FEB-13:00 |
Water Heater:WaterSystems:Gas | 91.28 | 1860.00 | 09-JAN-05:40 | 5043.91 | 01-FEB-13:00 |
Gas:HVAC | 154.87 | 0.00 | 01-JAN-00:10 | 186475.55 | 12-FEB-09:10 |
Heating:Gas | 154.87 | 0.00 | 01-JAN-00:10 | 186475.55 | 12-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1592.17 | 0.00 | 01-JAN-00:10 | 248069.14 | 08-JUL-14:00 |
EnergyTransfer:Building | 641.62 | 0.00 | 01-JAN-00:10 | 96260.62 | 13-FEB-07:10 |
EnergyTransfer:Zone:BACK_SPACE | 96.64 | 0.00 | 01-JAN-00:10 | 41688.02 | 12-FEB-07:10 |
Heating:EnergyTransfer | 43.69 | 0.00 | 01-JAN-00:10 | 91990.18 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 12.58 | 0.00 | 01-JAN-00:10 | 41688.02 | 12-FEB-07:10 |
Cooling:EnergyTransfer | 597.93 | 0.00 | 01-JAN-00:10 | 77324.66 | 07-JUL-15:00 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 84.07 | 0.00 | 01-JAN-00:10 | 12721.24 | 08-JUL-16:00 |
EnergyTransfer:Zone:CORE_RETAIL | 396.74 | 0.00 | 01-JAN-00:10 | 70753.01 | 09-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 10.46 | 0.00 | 01-JAN-00:10 | 61062.59 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 386.29 | 0.00 | 01-JAN-00:10 | 56778.21 | 10-JUN-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 81.69 | 0.00 | 01-JAN-00:10 | 18691.04 | 12-FEB-07:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 2.50 | 0.00 | 01-JAN-00:10 | 18691.04 | 12-FEB-07:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 79.18 | 0.00 | 01-JAN-00:10 | 9258.70 | 11-OCT-14:10 |
EnergyTransfer:Zone:FRONT_RETAIL | 53.15 | 0.00 | 01-JAN-00:10 | 18841.21 | 12-FEB-07:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 4.76 | 0.00 | 01-JAN-00:10 | 18841.21 | 12-FEB-07:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 48.39 | 0.00 | 01-JAN-00:10 | 9380.95 | 11-OCT-21:30 |
EnergyTransfer:Zone:FRONT_ENTRY | 13.39 | 0.00 | 01-JAN-00:10 | 25275.11 | 07-JAN-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 13.39 | 0.00 | 01-JAN-00:10 | 25275.11 | 07-JAN-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 950.56 | 0.00 | 01-JAN-00:10 | 171783.57 | 08-JUL-14:00 |
HeatingCoils:EnergyTransfer | 123.90 | 0.00 | 01-JAN-00:10 | 149180.44 | 12-FEB-09:10 |
CoolingCoils:EnergyTransfer | 826.66 | 0.00 | 01-JAN-00:10 | 171783.57 | 08-JUL-14:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 12.576 | -84.068 | 0.000 | 0.000 | 38.362 | 28.087 | 49.772 | 0.000 | 0.000 | 0.645 | 0.000 | 0.000 | 0.000 | 0.000 | -11.346 | -34.027 |
CORE_RETAIL | 0.000 | 0.000 | 10.455 | -386.284 | 0.000 | 0.000 | 161.414 | 218.814 | 83.927 | 34.545 | 0.000 | 0.459 | 0.000 | 0.000 | -16.111 | 0.000 | -10.199 | -97.021 |
POINT_OF_SALE | 0.000 | 0.000 | 2.501 | -79.183 | 0.000 | 0.000 | 14.956 | 24.176 | 52.689 | 27.134 | 0.000 | 0.279 | 0.001 | 0.000 | -15.028 | 0.000 | -5.219 | -22.305 |
FRONT_RETAIL | 0.000 | 0.000 | 4.763 | -48.385 | 0.000 | 0.000 | 15.145 | 23.423 | 7.908 | 27.148 | 0.000 | 0.279 | 0.001 | 0.000 | -14.572 | 0.000 | -4.999 | -10.709 |
FRONT_ENTRY | 13.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.081 | 0.000 | 5.536 | 0.000 | 1.114 | 3.792 | 0.000 | -2.750 | 0.000 | -21.167 | 0.000 |
Total Facility | 13.394 | 0.000 | 30.295 | -597.920 | 0.000 | 0.000 | 229.877 | 294.582 | 194.297 | 94.363 | 0.000 | 2.776 | 3.794 | 0.000 | -48.462 | 0.000 | -52.930 | -164.063 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 08-JUN-20:19 | 0.00 | 0.00 | 0.00 | -37071.21 | 0.00 | 0.00 | 0.00 | 81.78 | 605.09 | 0.00 | 0.00 | 0.00 | 36509.20 | 0.00 | -0.00 | 0.00 | -124.86 | 0.00 |
CORE_RETAIL | 08-JUN-06:02 | 0.00 | 0.00 | 0.00 | -188291.38 | 0.00 | 0.00 | 1634.59 | 344.55 | 2062.04 | 0.00 | 0.00 | 0.00 | 185380.34 | 0.00 | -965.12 | 0.00 | -165.02 | 0.00 |
POINT_OF_SALE | 11-JUN-00:21 | 0.00 | 0.00 | 0.00 | -20387.77 | 0.00 | 0.00 | 0.00 | 32.47 | 480.42 | 0.00 | 0.00 | 0.00 | 20560.28 | 0.00 | -606.19 | 0.00 | -79.21 | 0.00 |
FRONT_RETAIL | 08-NOV-21:33 | 0.00 | 0.00 | 0.00 | -21539.00 | 0.00 | 0.00 | 0.00 | 32.47 | 96.14 | 0.00 | 0.00 | 0.00 | 22672.00 | 0.00 | -1027.17 | 0.00 | -234.44 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-JUN-06:02 | 0.00 | 0.00 | 0.00 | -194033.86 | 0.00 | 0.00 | 2405.45 | 493.85 | 4773.73 | 0.00 | 0.00 | 0.00 | 189772.36 | 0.00 | -2872.50 | 0.00 | -539.02 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 10-JAN-05:42 | 0.00 | 0.00 | 52094.27 | 0.00 | 0.00 | 0.00 | 0.00 | 81.78 | 605.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1674.14 | -51107.00 |
CORE_RETAIL | 13-FEB-06:01 | 0.00 | 0.00 | 223242.71 | 0.00 | 0.00 | 0.00 | 0.00 | 344.55 | 1020.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1852.46 | 0.00 | -806.28 | -221948.85 |
POINT_OF_SALE | 12-FEB-07:12 | 0.00 | 0.00 | 30368.68 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 480.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2479.63 | 0.00 | -2179.43 | -26222.50 |
FRONT_RETAIL | 10-JAN-05:42 | 0.00 | 0.00 | 24782.25 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 96.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1772.38 | 0.00 | -721.11 | -22417.37 |
FRONT_ENTRY | 07-JAN-18:00 | 25274.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 465.44 | 0.00 | -367.91 | 0.00 | -25374.43 | 0.00 |
Total Facility | 12-FEB-08:62 | 4857.27 | 0.00 | 254384.07 | 0.00 | 0.00 | 0.00 | 0.00 | 493.85 | 1771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4946.61 | 0.00 | -7427.89 | -249132.27 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.9288 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.9425 | 0.1192 | 1.0000 | 0.2316 | 0.1192 | ||
PSZ-AC:2 | 7.0938 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.2886 | 0.2593 | 1.0000 | 1.8902 | 0.2593 | ||
PSZ-AC:3 | 1.0875 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0875 | 0.1638 | 1.0000 | 0.1781 | 0.1638 | ||
PSZ-AC:4 | 0.8265 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.8276 | 0.2152 | 1.0000 | 0.1781 | 0.2152 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.9288 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.9288 | 1.0000 | 1.0000 | 0.2316 | 0.1201 | ||
PSZ-AC:2 | 7.0938 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.0938 | 1.0000 | 1.0000 | 1.8902 | 0.2665 | ||
PSZ-AC:3 | 1.0875 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0875 | 1.0000 | 1.0000 | 0.1781 | 0.1638 | ||
PSZ-AC:4 | 0.8265 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.8265 | 1.0000 | 1.0000 | 0.1781 | 0.2155 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.9288 | 1.9288 | 1.9288 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.0938 | 7.0938 | 7.0938 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.0875 | 1.0875 | 1.0875 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.8265 | 0.8265 | 0.8265 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.9288 | 1.9425 | 1.9288 | 1.9288 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.0938 | 7.2886 | 7.0938 | 7.0938 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.0875 | 1.0875 | 1.0875 | 1.0875 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.8265 | 0.8276 | 0.8265 | 0.8265 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.9288 | 1.9288 | 1.9288 | 0.2316 | 0.2051 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.0938 | 7.0938 | 7.0938 | 1.8902 | 0.6956 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.0875 | 1.0875 | 1.0875 | 0.1781 | 0.3185 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.8265 | 0.8265 | 0.8265 | 0.1781 | 0.3184 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.9288 | 1.9288 | 1.9288 | 1.9288 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.0938 | 7.0938 | 7.0938 | 7.0938 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.0875 | 1.0875 | 1.0875 | 1.0875 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.8265 | 0.8265 | 0.8265 | 0.8265 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:39
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 154.87 | 186475.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 216.76 | 48868.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 294.58 | 24449.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 38.48 | 3371.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 194.30 | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 145.53 | 12676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 91.28 | 5043.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 194.30 | 889.64 |
Natural Gas | 0.00 | 246.16 |
Additional | 0.00 | 0.00 |
Total | 194.30 | 1135.80 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.41 |
Space Heating | 0.00 |
Space Cooling | 94.49 |
Fans (All) | 63.44 |
Service Water Heating | 0.00 |
Receptacle Equipment | 84.70 |
Miscellaneous (All) | 387.81 |
Subtotal | 387.81 |
Natural Gas [MJ/m2] | |
Space Heating | 67.51 |
Service Water Heating | 39.79 |
Miscellaneous (All) | 107.31 |
Subtotal | 107.31 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 25.94 |
Space Heating | 13.64 |
Space Cooling | 19.08 |
Fans (All) | 12.81 |
Service Water Heating | 8.04 |
Receptacle Equipment | 17.11 |
Miscellaneous | 3.39 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 2872. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3001. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3501. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4552. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_SETBACK | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_FRONTENTRY_STD2013 | FRONT_ENTRY DUALSPSCHED | January | 16.00 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.721904E+11 |
February | 0.000 | 0.397355E+11 |
March | 0.000 | 0.456484E+10 |
April | 0.000 | 0.696021E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.450239E+09 |
November | 0.000 | 0.659028E+10 |
December | 0.000 | 0.306475E+11 |
Annual Sum or Average | 0.154875E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.721904E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.721904E+11 |
February | 0.000 | 0.397355E+11 |
March | 0.000 | 0.456484E+10 |
April | 0.000 | 0.696021E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.450239E+09 |
November | 0.000 | 0.659028E+10 |
December | 0.000 | 0.306475E+11 |
Annual Sum or Average | 0.154875E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.721904E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.721904E+11 |
February | 0.000 | 0.397355E+11 |
March | 0.000 | 0.456484E+10 |
April | 0.000 | 0.696021E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.450239E+09 |
November | 0.000 | 0.659028E+10 |
December | 0.000 | 0.306475E+11 |
Annual Sum or Average | 0.154875E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.721904E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.721904E+11 |
February | 0.000 | 0.397355E+11 |
March | 0.000 | 0.456484E+10 |
April | 0.000 | 0.696021E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.450239E+09 |
November | 0.000 | 0.659028E+10 |
December | 0.000 | 0.306475E+11 |
Annual Sum or Average | 0.154875E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.721904E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.721904E+11 |
February | 0.000 | 0.397355E+11 |
March | 0.000 | 0.456484E+10 |
April | 0.000 | 0.696021E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.450239E+09 |
November | 0.000 | 0.659028E+10 |
December | 0.000 | 0.306475E+11 |
Annual Sum or Average | 0.154875E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.721904E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.721904E+11 |
February | 0.000 | 0.397355E+11 |
March | 0.000 | 0.456484E+10 |
April | 0.000 | 0.696021E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.450239E+09 |
November | 0.000 | 0.659028E+10 |
December | 0.000 | 0.306475E+11 |
Annual Sum or Average | 0.154875E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.721904E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.721904E+11 |
February | 0.000 | 0.397355E+11 |
March | 0.000 | 0.456484E+10 |
April | 0.000 | 0.696021E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.450239E+09 |
November | 0.000 | 0.659028E+10 |
December | 0.000 | 0.306475E+11 |
Annual Sum or Average | 0.154875E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.721904E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.721904E+11 |
February | 0.000 | 0.397355E+11 |
March | 0.000 | 0.456484E+10 |
April | 0.000 | 0.696021E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.450239E+09 |
November | 0.000 | 0.659028E+10 |
December | 0.000 | 0.306475E+11 |
Annual Sum or Average | 0.154875E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.721904E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.721904E+11 |
February | 0.000 | 0.397355E+11 |
March | 0.000 | 0.456484E+10 |
April | 0.000 | 0.696021E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.450239E+09 |
November | 0.000 | 0.659028E+10 |
December | 0.000 | 0.306475E+11 |
Annual Sum or Average | 0.154875E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.721904E+11 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.503879E+09 | 3423.11 | 22-JAN-16:25 | 4.45 | 0.89 | 0.168921E+10 | 2395.42 | 20-JAN-15:00 | 17.20 | 12.76 |
February | 0.972652E+09 | 3947.36 | 28-FEB-16:00 | 23.30 | 12.51 | 0.165314E+10 | 2451.26 | 22-FEB-15:50 | 15.33 | 13.46 |
March | 0.294725E+10 | 18463.55 | 30-MAR-21:50 | 22.98 | 16.51 | 0.210681E+10 | 2451.27 | 11-MAR-12:30 | 22.50 | 14.49 |
April | 0.463430E+10 | 30541.32 | 18-APR-20:41 | 20.28 | 15.59 | 0.211523E+10 | 2451.30 | 28-APR-14:00 | 25.60 | 15.82 |
May | 0.839335E+10 | 32135.04 | 18-MAY-00:07 | 20.22 | 15.27 | 0.222876E+10 | 2451.24 | 12-MAY-14:09 | 23.90 | 15.17 |
June | 0.134962E+11 | 37071.18 | 08-JUN-20:19 | 21.33 | 12.39 | 0.220152E+10 | 2451.23 | 09-JUN-14:09 | 29.90 | 18.88 |
July | 0.153856E+11 | 27104.46 | 07-JUL-22:03 | 29.13 | 22.70 | 0.218726E+10 | 2451.23 | 15-JUL-10:09 | 30.18 | 23.74 |
August | 0.163312E+11 | 26681.03 | 18-AUG-22:03 | 29.32 | 23.09 | 0.228102E+10 | 2451.26 | 26-AUG-10:20 | 27.77 | 20.59 |
September | 0.109932E+11 | 34371.99 | 14-SEP-21:27 | 19.45 | 13.85 | 0.215607E+10 | 2451.30 | 28-SEP-14:09 | 19.40 | 18.21 |
October | 0.579999E+10 | 24945.29 | 19-OCT-20:42 | 17.38 | 15.86 | 0.213767E+10 | 2451.25 | 28-OCT-11:20 | 14.60 | 14.60 |
November | 0.297321E+10 | 5939.95 | 04-NOV-15:55 | 21.10 | 18.17 | 0.192795E+10 | 2451.24 | 04-NOV-11:20 | 16.87 | 16.52 |
December | 0.163842E+10 | 3955.10 | 13-DEC-16:00 | 17.20 | 16.88 | 0.177112E+10 | 2451.21 | 14-DEC-15:09 | 15.00 | 10.57 |
Annual Sum or Average | 0.840692E+11 | 0.244558E+11 | ||||||||
Minimum of Months | 0.503879E+09 | 3423.11 | 4.45 | 0.89 | 0.165314E+10 | 2395.42 | 14.60 | 10.57 | ||
Maximum of Months | 0.163312E+11 | 37071.18 | 29.32 | 23.09 | 0.228102E+10 | 2451.30 | 30.18 | 23.74 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132132E+11 | 57336.66 | 27-JAN-07:05 | -6.7 | -7.8 | 0.715535E+10 | 10327.01 | 31-JAN-15:00 | 20.00 | 13.57 |
February | 0.153083E+11 | 55019.35 | 09-FEB-07:05 | -5.6 | -7.4 | 0.704821E+10 | 10327.31 | 22-FEB-15:39 | 16.27 | 13.43 |
March | 0.258903E+11 | 129445.49 | 31-MAR-06:03 | 17.30 | 16.12 | 0.897674E+10 | 10327.37 | 11-MAR-11:30 | 20.00 | 13.41 |
April | 0.302425E+11 | 159601.74 | 18-APR-06:03 | 13.30 | 12.05 | 0.893989E+10 | 10327.12 | 01-APR-11:20 | 14.07 | 9.35 |
May | 0.395421E+11 | 154559.49 | 17-MAY-06:02 | 16.78 | 13.16 | 0.939119E+10 | 10327.14 | 20-MAY-15:00 | 26.70 | 19.02 |
June | 0.470760E+11 | 188327.17 | 08-JUN-06:02 | 12.07 | 8.46 | 0.927733E+10 | 10327.27 | 09-JUN-14:09 | 29.90 | 18.88 |
July | 0.495345E+11 | 127808.60 | 03-JUL-06:02 | 18.68 | 16.73 | 0.921832E+10 | 10327.01 | 11-JUL-14:09 | 32.02 | 22.40 |
August | 0.511283E+11 | 125842.57 | 26-AUG-06:02 | 21.78 | 17.45 | 0.961355E+10 | 10326.98 | 26-AUG-11:20 | 29.47 | 21.46 |
September | 0.399977E+11 | 164240.82 | 14-SEP-06:03 | 12.30 | 10.99 | 0.908360E+10 | 10327.15 | 15-SEP-14:30 | 28.85 | 18.95 |
October | 0.324382E+11 | 150252.44 | 03-OCT-06:03 | 11.10 | 11.10 | 0.894749E+10 | 10327.28 | 04-OCT-14:09 | 19.68 | 12.49 |
November | 0.233817E+11 | 93574.90 | 04-NOV-06:03 | 16.10 | 15.06 | 0.808623E+10 | 10327.12 | 04-NOV-13:39 | 17.43 | 17.12 |
December | 0.185358E+11 | 50086.20 | 04-DEC-07:05 | -3.3 | -4.9 | 0.749885E+10 | 10327.01 | 11-DEC-15:00 | 21.10 | 15.90 |
Annual Sum or Average | 0.386289E+12 | 0.103237E+12 | ||||||||
Minimum of Months | 0.132132E+11 | 50086.20 | -6.7 | -7.8 | 0.704821E+10 | 10326.98 | 14.07 | 9.35 | ||
Maximum of Months | 0.511283E+11 | 188327.17 | 21.78 | 17.45 | 0.961355E+10 | 10327.37 | 32.02 | 22.40 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262811E+10 | 4156.40 | 26-JAN-12:20 | -0.7 | -4.2 | 0.722146E+09 | 973.15 | 31-JAN-15:00 | 20.00 | 13.57 |
February | 0.301175E+10 | 16372.11 | 28-FEB-22:01 | 18.63 | 10.78 | 0.696116E+09 | 973.16 | 22-FEB-15:30 | 17.20 | 13.31 |
March | 0.468888E+10 | 19945.35 | 13-MAR-22:11 | 20.03 | 14.42 | 0.874250E+09 | 973.14 | 11-MAR-11:20 | 19.43 | 13.14 |
April | 0.520904E+10 | 18085.10 | 11-APR-21:21 | 19.15 | 13.43 | 0.846060E+09 | 973.13 | 07-APR-14:09 | 22.57 | 13.55 |
May | 0.695169E+10 | 18512.69 | 18-MAY-01:11 | 18.30 | 14.24 | 0.884933E+09 | 973.12 | 23-MAY-14:20 | 24.27 | 20.59 |
June | 0.935223E+10 | 20387.75 | 11-JUN-00:21 | 20.00 | 11.55 | 0.873884E+09 | 973.13 | 14-JUN-14:20 | 30.20 | 22.59 |
July | 0.105093E+11 | 16175.06 | 07-JUL-21:23 | 30.00 | 22.75 | 0.868298E+09 | 973.13 | 01-JUL-15:09 | 28.95 | 23.37 |
August | 0.117885E+11 | 16546.43 | 18-AUG-22:03 | 29.32 | 23.09 | 0.905509E+09 | 973.12 | 26-AUG-12:20 | 30.97 | 21.91 |
September | 0.926264E+10 | 16399.04 | 18-SEP-20:11 | 18.70 | 14.42 | 0.855869E+09 | 973.15 | 21-SEP-14:00 | 22.80 | 20.14 |
October | 0.721549E+10 | 16806.21 | 11-OCT-20:41 | 16.47 | 9.75 | 0.856455E+09 | 973.14 | 05-OCT-14:00 | 20.60 | 15.45 |
November | 0.505916E+10 | 14639.08 | 08-NOV-21:15 | 14.63 | 7.27 | 0.807418E+09 | 973.14 | 04-NOV-13:20 | 17.07 | 16.75 |
December | 0.350756E+10 | 15677.14 | 12-DEC-22:11 | 18.30 | 14.70 | 0.790373E+09 | 973.11 | 12-DEC-15:30 | 22.50 | 16.06 |
Annual Sum or Average | 0.791844E+11 | 0.998131E+10 | ||||||||
Minimum of Months | 0.262811E+10 | 4156.40 | -0.7 | -4.2 | 0.696116E+09 | 973.11 | 17.07 | 13.14 | ||
Maximum of Months | 0.117885E+11 | 20387.75 | 30.00 | 23.09 | 0.905509E+09 | 973.16 | 30.97 | 23.37 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104893E+10 | 3380.22 | 26-JAN-19:33 | -0.9 | -4.2 | 0.688719E+09 | 973.10 | 30-JAN-15:09 | 16.70 | 10.50 |
February | 0.130741E+10 | 17142.22 | 26-FEB-19:45 | 20.00 | 10.70 | 0.668721E+09 | 973.11 | 22-FEB-15:30 | 17.20 | 13.31 |
March | 0.231698E+10 | 15537.64 | 13-MAR-20:41 | 21.38 | 14.27 | 0.846373E+09 | 973.13 | 11-MAR-14:09 | 25.18 | 16.16 |
April | 0.269227E+10 | 16131.84 | 14-APR-20:21 | 20.55 | 13.63 | 0.834230E+09 | 973.13 | 20-APR-14:00 | 23.90 | 16.58 |
May | 0.398605E+10 | 15390.06 | 14-MAY-18:21 | 24.20 | 14.41 | 0.882864E+09 | 973.13 | 12-MAY-14:09 | 23.90 | 15.17 |
June | 0.622048E+10 | 17716.19 | 10-JUN-21:34 | 21.47 | 11.97 | 0.873717E+09 | 973.13 | 17-JUN-15:00 | 25.60 | 22.49 |
July | 0.729443E+10 | 12819.63 | 09-JUL-19:23 | 30.80 | 22.67 | 0.868307E+09 | 973.13 | 29-JUL-10:00 | 19.40 | 19.40 |
August | 0.841233E+10 | 12941.02 | 18-AUG-22:43 | 28.98 | 23.26 | 0.905527E+09 | 973.12 | 26-AUG-10:20 | 27.77 | 20.59 |
September | 0.614917E+10 | 16649.35 | 15-SEP-00:29 | 16.65 | 13.30 | 0.855465E+09 | 973.13 | 16-SEP-14:50 | 25.28 | 23.05 |
October | 0.448491E+10 | 20098.46 | 11-OCT-23:17 | 14.03 | 8.66 | 0.842513E+09 | 973.14 | 05-OCT-14:39 | 20.40 | 15.28 |
November | 0.277237E+10 | 21539.88 | 08-NOV-21:33 | 14.27 | 7.16 | 0.782949E+09 | 973.10 | 04-NOV-11:20 | 16.87 | 16.52 |
December | 0.170107E+10 | 3915.43 | 12-DEC-14:00 | 22.80 | 17.06 | 0.743526E+09 | 973.11 | 11-DEC-15:00 | 21.10 | 15.90 |
Annual Sum or Average | 0.483864E+11 | 0.979291E+10 | ||||||||
Minimum of Months | 0.104893E+10 | 3380.22 | -0.9 | -4.2 | 0.668721E+09 | 973.10 | 16.70 | 10.50 | ||
Maximum of Months | 0.841233E+10 | 21539.88 | 30.80 | 23.26 | 0.905527E+09 | 973.14 | 27.77 | 23.05 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 | 18.59 | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.28 | 21.38 | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 | 21.87 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 | 18.45 | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.59 | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.59 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.80 | 1.51 | 0.00 | 0.00 | 1.80 | 1.51 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 21.87 | 0.00 | 0.00 | 25.13 | 21.87 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.566711E+10 | 52094.03 | 10-JAN-05:42 | -4.2 |
February | 0.332648E+10 | 51793.44 | 13-FEB-05:11 | -5.2 |
March | 0.407317E+09 | 50701.92 | 23-MAR-04:01 | 5.18 |
April | 0.104514E+09 | 26325.16 | 07-APR-04:03 | 3.80 |
May | 32080449.60 | 1133.25 | 19-MAY-05:07 | 16.60 |
June | 7051552.78 | 1162.13 | 02-JUN-05:05 | 15.18 |
July | 3590654.11 | 1444.63 | 14-JUL-05:05 | 23.30 |
August | 3125253.60 | 1420.66 | 09-AUG-05:05 | 24.40 |
September | 13730668.43 | 1088.89 | 20-SEP-05:05 | 15.60 |
October | 69491895.66 | 10625.83 | 26-OCT-05:02 | 2.20 |
November | 0.489578E+09 | 50911.05 | 22-NOV-05:01 | -2.9 |
December | 0.245172E+10 | 51374.61 | 04-DEC-05:42 | -2.8 |
Annual Sum or Average | 0.125758E+11 | |||
Minimum of Months | 3125253.60 | 1088.89 | -5.2 | |
Maximum of Months | 0.566711E+10 | 52094.03 | 24.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.365531E+10 | 221933.50 | 09-JAN-06:02 | -2.4 |
February | 0.200451E+10 | 223242.69 | 13-FEB-06:01 | -5.6 |
March | 0.517321E+09 | 6179.44 | 19-MAR-08:10 | 4.27 |
April | 0.490227E+09 | 4840.86 | 09-APR-07:12 | 9.63 |
May | 0.489842E+09 | 4798.81 | 14-MAY-07:13 | 14.07 |
June | 0.286852E+09 | 6683.84 | 25-JUN-08:06 | 23.87 |
July | 0.179755E+09 | 10660.04 | 16-JUL-08:06 | 25.97 |
August | 0.152014E+09 | 8191.96 | 06-AUG-08:20 | 25.17 |
September | 0.400389E+09 | 5893.60 | 17-SEP-08:20 | 23.87 |
October | 0.503097E+09 | 4857.01 | 08-OCT-07:12 | 11.83 |
November | 0.537461E+09 | 18305.95 | 23-NOV-09:05 | 5.73 |
December | 0.123860E+10 | 163050.86 | 04-DEC-07:03 | -3.3 |
Annual Sum or Average | 0.104554E+11 | |||
Minimum of Months | 0.152014E+09 | 4798.81 | -5.6 | |
Maximum of Months | 0.365531E+10 | 223242.69 | 25.97 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116112E+10 | 30244.08 | 09-JAN-05:12 | -2.2 |
February | 0.684200E+09 | 30368.70 | 12-FEB-07:12 | -12.6 |
March | 75472553.12 | 29695.30 | 23-MAR-04:01 | 5.18 |
April | 34113977.49 | 8553.36 | 06-APR-05:02 | 0.18 |
May | 14775365.37 | 628.94 | 17-MAY-05:07 | 16.70 |
June | 2268425.00 | 778.70 | 16-JUN-05:05 | 20.68 |
July | 888167.40 | 595.82 | 29-JUL-05:07 | 17.80 |
August | 231312.63 | 538.32 | 20-AUG-07:10 | 23.98 |
September | 4612957.53 | 792.83 | 05-SEP-05:05 | 21.70 |
October | 19491584.89 | 795.75 | 19-OCT-05:05 | 20.92 |
November | 83870899.96 | 29860.10 | 22-NOV-05:01 | -2.9 |
December | 0.419893E+09 | 29992.90 | 03-DEC-07:01 | -3.4 |
Annual Sum or Average | 0.250094E+10 | |||
Minimum of Months | 231312.63 | 538.32 | -12.6 | |
Maximum of Months | 0.116112E+10 | 30368.70 | 23.98 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202782E+10 | 24782.18 | 10-JAN-05:42 | -4.2 |
February | 0.120347E+10 | 24648.85 | 12-FEB-07:12 | -12.6 |
March | 0.225599E+09 | 24127.98 | 23-MAR-04:01 | 5.18 |
April | 0.112608E+09 | 21930.46 | 06-APR-04:02 | 0.92 |
May | 41504529.65 | 1049.04 | 19-MAY-05:07 | 16.60 |
June | 8896782.76 | 1025.93 | 18-JUN-07:04 | 20.10 |
July | 1914121.39 | 968.87 | 04-JUL-07:07 | 21.88 |
August | 165844.52 | 552.82 | 20-AUG-07:10 | 23.98 |
September | 8178781.40 | 1043.24 | 03-SEP-07:07 | 21.78 |
October | 65738106.69 | 14573.89 | 31-OCT-04:03 | 8.80 |
November | 0.200455E+09 | 24227.83 | 22-NOV-05:01 | -2.9 |
December | 0.866534E+09 | 24310.08 | 03-DEC-07:01 | -3.4 |
Annual Sum or Average | 0.476289E+10 | |||
Minimum of Months | 165844.52 | 552.82 | -12.6 | |
Maximum of Months | 0.202782E+10 | 24782.18 | 23.98 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.650556E+10 | 25275.11 | 07-JAN-18:00 | -5.0 |
February | 0.377003E+10 | 25207.25 | 11-FEB-18:00 | -5.0 |
March | 0.371443E+09 | 12936.15 | 22-MAR-11:10 | 4.40 |
April | 18239035.94 | 2022.01 | 26-APR-07:10 | 4.97 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 7771730.52 | 2612.30 | 26-OCT-07:07 | 2.57 |
November | 0.696145E+09 | 20590.54 | 21-NOV-16:51 | 7.20 |
December | 0.202436E+10 | 17021.52 | 17-DEC-18:00 | 1.10 |
Annual Sum or Average | 0.133936E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.650556E+10 | 25275.11 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.235462E+10 | 2023.29 | 02-JAN-09:09 | 0.419292E+10 | 2751.42 | 02-JAN-09:09 |
February | 0.214299E+10 | 2023.29 | 01-FEB-09:09 | 0.380401E+10 | 2751.42 | 01-FEB-09:09 |
March | 0.244478E+10 | 2023.29 | 01-MAR-09:09 | 0.429860E+10 | 2751.42 | 01-MAR-09:09 |
April | 0.230724E+10 | 2023.29 | 01-APR-09:09 | 0.408483E+10 | 2751.42 | 01-APR-09:09 |
May | 0.239970E+10 | 2023.29 | 01-MAY-08:09 | 0.424576E+10 | 2751.42 | 01-MAY-08:09 |
June | 0.235921E+10 | 2023.29 | 01-JUN-08:09 | 0.415135E+10 | 2751.42 | 01-JUN-08:09 |
July | 0.234773E+10 | 2023.29 | 01-JUL-09:09 | 0.417924E+10 | 2751.42 | 01-JUL-09:09 |
August | 0.244478E+10 | 2023.29 | 01-AUG-08:09 | 0.429860E+10 | 2751.42 | 01-AUG-08:09 |
September | 0.230724E+10 | 2023.29 | 01-SEP-08:09 | 0.408483E+10 | 2751.42 | 01-SEP-08:09 |
October | 0.235462E+10 | 2023.29 | 02-OCT-08:09 | 0.419292E+10 | 2751.42 | 02-OCT-08:09 |
November | 0.227595E+10 | 2023.29 | 01-NOV-08:09 | 0.405935E+10 | 2751.42 | 01-NOV-08:09 |
December | 0.234773E+10 | 2023.29 | 01-DEC-09:09 | 0.417924E+10 | 2751.42 | 01-DEC-09:09 |
Annual Sum or Average | 0.280866E+11 | 0.497716E+11 | ||||
Minimum of Months | 0.214299E+10 | 2023.29 | 0.380401E+10 | 2751.42 | ||
Maximum of Months | 0.244478E+10 | 2023.29 | 0.429860E+10 | 2751.42 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.203961E+11 | 18915.75 | 02-JAN-09:09 | 0.707031E+10 | 4639.58 | 02-JAN-09:09 |
February | 0.182356E+11 | 18915.75 | 01-FEB-09:09 | 0.641452E+10 | 4639.58 | 01-FEB-09:09 |
March | 0.193314E+11 | 18915.75 | 01-MAR-10:30 | 0.724851E+10 | 4639.58 | 01-MAR-09:09 |
April | 0.167409E+11 | 18915.75 | 03-APR-08:09 | 0.688804E+10 | 4639.58 | 01-APR-09:09 |
May | 0.173885E+11 | 18915.75 | 05-MAY-16:00 | 0.715941E+10 | 4639.58 | 01-MAY-08:09 |
June | 0.168999E+11 | 18915.75 | 07-JUN-08:09 | 0.700021E+10 | 4639.58 | 01-JUN-08:09 |
July | 0.167777E+11 | 18915.75 | 01-JUL-16:49 | 0.704724E+10 | 4639.58 | 01-JUL-09:09 |
August | 0.172398E+11 | 18915.75 | 01-AUG-08:09 | 0.724851E+10 | 4639.58 | 01-AUG-08:09 |
September | 0.169063E+11 | 18915.75 | 01-SEP-16:30 | 0.688804E+10 | 4639.58 | 01-SEP-08:09 |
October | 0.198147E+11 | 18915.75 | 02-OCT-08:09 | 0.707031E+10 | 4639.58 | 02-OCT-08:09 |
November | 0.191055E+11 | 18915.75 | 01-NOV-08:09 | 0.684509E+10 | 4639.58 | 01-NOV-08:09 |
December | 0.199780E+11 | 18915.75 | 01-DEC-09:09 | 0.704724E+10 | 4639.58 | 01-DEC-09:09 |
Annual Sum or Average | 0.218814E+12 | 0.839274E+11 | ||||
Minimum of Months | 0.167409E+11 | 18915.75 | 0.641452E+10 | 4639.58 | ||
Maximum of Months | 0.203961E+11 | 18915.75 | 0.724851E+10 | 4639.58 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.202570E+10 | 1782.39 | 02-JAN-09:09 | 0.443872E+10 | 2912.71 | 02-JAN-09:09 |
February | 0.184426E+10 | 1782.39 | 01-FEB-09:09 | 0.402701E+10 | 2912.71 | 01-FEB-09:09 |
March | 0.210616E+10 | 1782.39 | 01-MAR-09:09 | 0.455059E+10 | 2912.71 | 01-MAR-09:09 |
April | 0.198616E+10 | 1782.39 | 01-APR-09:09 | 0.432429E+10 | 2912.71 | 01-APR-09:09 |
May | 0.206593E+10 | 1782.39 | 01-MAY-08:09 | 0.449465E+10 | 2912.71 | 01-MAY-08:09 |
June | 0.203227E+10 | 1782.39 | 01-JUN-08:09 | 0.439471E+10 | 2912.71 | 01-JUN-08:09 |
July | 0.201982E+10 | 1782.39 | 01-JUL-09:09 | 0.442423E+10 | 2912.71 | 01-JUL-09:09 |
August | 0.210616E+10 | 1782.39 | 01-AUG-08:09 | 0.455059E+10 | 2912.71 | 01-AUG-08:09 |
September | 0.198616E+10 | 1782.39 | 01-SEP-08:09 | 0.432429E+10 | 2912.71 | 01-SEP-08:09 |
October | 0.202570E+10 | 1782.39 | 02-OCT-08:09 | 0.443872E+10 | 2912.71 | 02-OCT-08:09 |
November | 0.195769E+10 | 1782.39 | 01-NOV-08:09 | 0.429732E+10 | 2912.71 | 01-NOV-08:09 |
December | 0.201982E+10 | 1782.39 | 01-DEC-09:09 | 0.442423E+10 | 2912.71 | 01-DEC-09:09 |
Annual Sum or Average | 0.241758E+11 | 0.526893E+11 | ||||
Minimum of Months | 0.184426E+10 | 1782.39 | 0.402701E+10 | 2912.71 | ||
Maximum of Months | 0.210616E+10 | 1782.39 | 0.455059E+10 | 2912.71 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.196268E+10 | 1725.71 | 02-JAN-09:09 | 0.666220E+09 | 437.18 | 02-JAN-09:09 |
February | 0.178687E+10 | 1725.71 | 01-FEB-09:09 | 0.604426E+09 | 437.18 | 01-FEB-09:09 |
March | 0.204057E+10 | 1725.71 | 01-MAR-09:09 | 0.683011E+09 | 437.18 | 01-MAR-09:09 |
April | 0.192434E+10 | 1725.71 | 01-APR-09:09 | 0.649045E+09 | 437.18 | 01-APR-09:09 |
May | 0.200162E+10 | 1725.71 | 01-MAY-08:09 | 0.674616E+09 | 437.18 | 01-MAY-08:09 |
June | 0.196898E+10 | 1725.71 | 01-JUN-08:09 | 0.659615E+09 | 437.18 | 01-JUN-08:09 |
July | 0.195698E+10 | 1725.71 | 01-JUL-09:09 | 0.664046E+09 | 437.18 | 01-JUL-09:09 |
August | 0.204057E+10 | 1725.71 | 01-AUG-08:09 | 0.683011E+09 | 437.18 | 01-AUG-08:09 |
September | 0.192434E+10 | 1725.71 | 01-SEP-08:09 | 0.649045E+09 | 437.18 | 01-SEP-08:09 |
October | 0.196268E+10 | 1725.71 | 02-OCT-08:09 | 0.666220E+09 | 437.18 | 02-OCT-08:09 |
November | 0.189680E+10 | 1725.71 | 01-NOV-08:09 | 0.644998E+09 | 437.18 | 01-NOV-08:09 |
December | 0.195698E+10 | 1725.71 | 01-DEC-09:09 | 0.664046E+09 | 437.18 | 01-DEC-09:09 |
Annual Sum or Average | 0.234234E+11 | 0.790830E+10 | ||||
Minimum of Months | 0.178687E+10 | 1725.71 | 0.604426E+09 | 437.18 | ||
Maximum of Months | 0.204057E+10 | 1725.71 | 0.683011E+09 | 437.18 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 6919213.84 | 2.58 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 6249612.50 | 2.58 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 6919213.84 | 2.58 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 6696013.39 | 2.58 | 01-APR-00:10 | 0.00 | 0.00 |
May | 6919213.84 | 2.58 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 6696013.39 | 2.58 | 01-JUN-00:10 | 0.00 | 0.00 |
July | 6919213.84 | 2.58 | 01-JUL-00:10 | 0.00 | 0.00 |
August | 6919213.84 | 2.58 | 01-AUG-00:10 | 0.00 | 0.00 |
September | 6696013.39 | 2.58 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 6919213.84 | 2.58 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 6696013.39 | 2.58 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 6919213.84 | 2.58 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 81468162.94 | ||||
Minimum of Months | 6249612.50 | 2.58 | 0.00 | 0.00 | |
Maximum of Months | 6919213.84 | 2.58 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.235462E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220813E+10 |
February | 0.479114E+10 | 0.214299E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 565431.25 | 0.188171E+10 |
March | 0.548013E+10 | 0.244478E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4829966.79 | 0.122147E+10 |
April | 0.518069E+10 | 0.230724E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12458300.07 | 0.771076E+09 |
May | 0.536353E+10 | 0.239970E+10 | 0.424576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38514310.22 | 0.488191E+09 |
June | 0.528933E+10 | 0.235921E+10 | 0.415135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158387E+09 | 0.192037E+09 |
July | 0.525489E+10 | 0.234773E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181505E+09 | 0.108486E+09 |
August | 0.548013E+10 | 0.244478E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190949E+09 | 43649768.84 |
September | 0.518069E+10 | 0.230724E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49519742.32 | 0.238266E+09 |
October | 0.524694E+10 | 0.235462E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8494510.83 | 0.926196E+09 |
November | 0.504819E+10 | 0.227595E+10 | 0.405935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53823.19 | 0.130151E+10 |
December | 0.525489E+10 | 0.234773E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196485E+10 |
Annual Sum or Average | 0.628175E+11 | 0.280866E+11 | 0.497716E+11 | 0.645277E+09 | 0.113456E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.214299E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43649768.84 |
Maximum of Months | 0.548013E+10 | 0.244478E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190949E+09 | 0.220813E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.203961E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191871E+10 |
February | 0.201852E+11 | 0.182356E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 398159.96 | 0.166584E+10 |
March | 0.230879E+11 | 0.193314E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3937999.84 | 0.111722E+10 |
April | 0.218263E+11 | 0.167409E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10172488.47 | 0.698385E+09 |
May | 0.225967E+11 | 0.173885E+11 | 0.715941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30678350.48 | 0.450995E+09 |
June | 0.222841E+11 | 0.168999E+11 | 0.700021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117563E+09 | 0.218956E+09 |
July | 0.221389E+11 | 0.167777E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123756E+09 | 0.137880E+09 |
August | 0.230879E+11 | 0.172398E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128540E+09 | 89019691.09 |
September | 0.218263E+11 | 0.169063E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36760022.86 | 0.233579E+09 |
October | 0.221054E+11 | 0.198147E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6952640.11 | 0.812257E+09 |
November | 0.212681E+11 | 0.191055E+11 | 0.684509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44083.83 | 0.113899E+10 |
December | 0.221389E+11 | 0.199780E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171741E+10 |
Annual Sum or Average | 0.264651E+12 | 0.218814E+12 | 0.839274E+11 | 0.458803E+09 | 0.101992E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.167409E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89019691.09 |
Maximum of Months | 0.230879E+11 | 0.203961E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128540E+09 | 0.191871E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.202570E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100697E+10 |
February | 0.190200E+10 | 0.184426E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 210901.70 | 0.867556E+09 |
March | 0.217552E+10 | 0.210616E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2101483.99 | 0.584201E+09 |
April | 0.205665E+10 | 0.198616E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5389318.00 | 0.349661E+09 |
May | 0.212923E+10 | 0.206593E+10 | 0.449465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16708698.56 | 0.213094E+09 |
June | 0.209978E+10 | 0.203227E+10 | 0.439471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68537466.35 | 82223225.14 |
July | 0.208610E+10 | 0.201982E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78271607.60 | 46508121.85 |
August | 0.217552E+10 | 0.210616E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82164333.64 | 18625829.56 |
September | 0.205665E+10 | 0.198616E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21421126.50 | 0.102229E+09 |
October | 0.208295E+10 | 0.202570E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3680392.52 | 0.416399E+09 |
November | 0.200405E+10 | 0.195769E+10 | 0.429732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23377.82 | 0.617906E+09 |
December | 0.208610E+10 | 0.201982E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913482E+09 |
Annual Sum or Average | 0.249375E+11 | 0.241758E+11 | 0.526893E+11 | 0.278509E+09 | 0.521886E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.184426E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18625829.56 |
Maximum of Months | 0.217552E+10 | 0.210616E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82164333.64 | 0.100697E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.196268E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.971792E+09 |
February | 0.190200E+10 | 0.178687E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 210819.23 | 0.831505E+09 |
March | 0.217552E+10 | 0.204057E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2100011.28 | 0.548319E+09 |
April | 0.205665E+10 | 0.192434E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5397685.56 | 0.329760E+09 |
May | 0.212923E+10 | 0.200162E+10 | 0.674616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16712901.87 | 0.206497E+09 |
June | 0.209978E+10 | 0.196898E+10 | 0.659615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68666273.65 | 82432848.97 |
July | 0.208610E+10 | 0.195698E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78530248.89 | 47029700.99 |
August | 0.217552E+10 | 0.204057E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82495115.54 | 18702341.02 |
September | 0.205665E+10 | 0.192434E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21460157.45 | 0.101520E+09 |
October | 0.208295E+10 | 0.196268E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3680028.40 | 0.402671E+09 |
November | 0.200405E+10 | 0.189680E+10 | 0.644998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23345.62 | 0.587797E+09 |
December | 0.208610E+10 | 0.195698E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871337E+09 |
Annual Sum or Average | 0.249375E+11 | 0.234234E+11 | 0.790830E+10 | 0.279277E+09 | 0.499936E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.178687E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18702341.02 |
Maximum of Months | 0.217552E+10 | 0.204057E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82495115.54 | 0.971792E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756148E+10 |
February | 0.00 | 6249612.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1680.29 | 0.462468E+10 |
March | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554843.15 | 0.139058E+10 |
April | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22924942.99 | 0.526072E+09 |
May | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86678072.46 | 0.260606E+09 |
June | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310459E+09 | 86806222.50 |
July | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369093E+09 | 98674275.78 |
August | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280508E+09 | 68976055.62 |
September | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43629033.15 | 0.270332E+09 |
October | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281282.36 | 0.973274E+09 |
November | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34448.95 | 0.188275E+10 |
December | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342296E+10 |
Annual Sum or Average | 0.00 | 81468162.94 | 0.111416E+10 | 0.211672E+11 | |||||
Minimum of Months | 0.00 | 6249612.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68976055.62 |
Maximum of Months | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369093E+09 | 0.756148E+10 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2023.29 | 02-JAN-09:09 | 2751.42 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4729.76 | 07-JAN-05:07 |
February | 5888.82 | 01-FEB-15:09 | 2023.29 | 01-FEB-09:09 | 2751.42 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.82 | 28-FEB-15:00 | 5517.12 | 12-FEB-00:55 |
March | 5888.82 | 01-MAR-15:09 | 2023.29 | 01-MAR-09:09 | 2751.42 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 135.20 | 30-MAR-16:00 | 3497.84 | 22-MAR-05:00 |
April | 5888.82 | 01-APR-10:09 | 2023.29 | 01-APR-09:09 | 2751.42 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.08 | 04-APR-15:00 | 1754.69 | 05-APR-05:00 |
May | 5888.82 | 01-MAY-14:09 | 2023.29 | 01-MAY-08:09 | 2751.42 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 332.05 | 29-MAY-18:05 | 1484.31 | 10-MAY-04:00 |
June | 5888.82 | 01-JUN-14:09 | 2023.29 | 01-JUN-08:09 | 2751.42 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 518.08 | 11-JUN-18:03 | 1016.09 | 07-JUN-03:00 |
July | 5888.82 | 01-JUL-10:09 | 2023.29 | 01-JUL-09:09 | 2751.42 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 602.85 | 09-JUL-19:27 | 752.75 | 28-JUL-22:00 |
August | 5888.82 | 01-AUG-14:09 | 2023.29 | 01-AUG-08:09 | 2751.42 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 716.87 | 18-AUG-20:03 | 422.46 | 25-AUG-04:50 |
September | 5888.82 | 01-SEP-14:09 | 2023.29 | 01-SEP-08:09 | 2751.42 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 285.17 | 03-SEP-18:03 | 1050.51 | 29-SEP-05:00 |
October | 5888.82 | 02-OCT-14:09 | 2023.29 | 02-OCT-08:09 | 2751.42 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.94 | 11-OCT-14:00 | 2022.67 | 28-OCT-04:00 |
November | 5888.82 | 01-NOV-14:09 | 2023.29 | 01-NOV-08:09 | 2751.42 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.93 | 19-NOV-14:55 | 3134.43 | 30-NOV-21:05 |
December | 5888.82 | 01-DEC-15:09 | 2023.29 | 01-DEC-09:09 | 2751.42 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5020.94 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.46 | |||||
Maximum of Months | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 716.87 | 5517.12 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 18915.75 | 02-JAN-09:09 | 4639.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3522.30 | 07-JAN-04:53 |
February | 24809.68 | 01-FEB-15:09 | 18915.75 | 01-FEB-09:09 | 4639.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.33 | 28-FEB-15:00 | 4994.80 | 12-FEB-00:55 |
March | 24809.68 | 01-MAR-15:09 | 18915.75 | 01-MAR-10:30 | 4639.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.67 | 30-MAR-16:00 | 3032.09 | 22-MAR-03:00 |
April | 24809.68 | 01-APR-10:09 | 18915.75 | 03-APR-08:09 | 4639.58 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.02 | 04-APR-15:00 | 1634.38 | 05-APR-05:00 |
May | 24809.68 | 01-MAY-14:09 | 18915.75 | 05-MAY-16:00 | 4639.58 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 271.68 | 29-MAY-18:05 | 1334.38 | 10-MAY-04:00 |
June | 24809.68 | 01-JUN-14:09 | 18915.75 | 07-JUN-08:09 | 4639.58 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 424.49 | 11-JUN-18:03 | 943.07 | 07-JUN-02:53 |
July | 24809.68 | 01-JUL-10:09 | 18915.75 | 01-JUL-16:49 | 4639.58 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 426.18 | 09-JUL-18:03 | 681.23 | 28-JUL-22:00 |
August | 24809.68 | 01-AUG-14:09 | 18915.75 | 01-AUG-08:09 | 4639.58 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 589.25 | 18-AUG-20:03 | 439.19 | 25-AUG-04:55 |
September | 24809.68 | 01-SEP-14:09 | 18915.75 | 01-SEP-16:30 | 4639.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 234.59 | 03-SEP-18:03 | 926.56 | 29-SEP-05:00 |
October | 24809.68 | 02-OCT-14:09 | 18915.75 | 02-OCT-08:09 | 4639.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.54 | 11-OCT-14:00 | 1890.11 | 28-OCT-04:00 |
November | 24809.68 | 01-NOV-14:09 | 18915.75 | 01-NOV-08:09 | 4639.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | 19-NOV-15:00 | 2775.14 | 07-NOV-02:00 |
December | 24809.68 | 01-DEC-15:09 | 18915.75 | 01-DEC-09:09 | 4639.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4698.14 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 18915.75 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.19 | |||||
Maximum of Months | 24809.68 | 18915.75 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 589.25 | 4994.80 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1782.39 | 02-JAN-09:09 | 2912.71 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2062.41 | 07-JAN-05:05 |
February | 2337.76 | 01-FEB-15:09 | 1782.39 | 01-FEB-09:09 | 2912.71 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 | 28-FEB-15:00 | 2396.29 | 12-FEB-00:55 |
March | 2337.76 | 01-MAR-15:09 | 1782.39 | 01-MAR-09:09 | 2912.71 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.59 | 30-MAR-16:00 | 1521.95 | 22-MAR-04:04 |
April | 2337.76 | 01-APR-10:09 | 1782.39 | 01-APR-09:09 | 2912.71 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 | 04-APR-15:00 | 783.08 | 05-APR-05:00 |
May | 2337.76 | 01-MAY-14:09 | 1782.39 | 01-MAY-08:09 | 2912.71 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 139.31 | 29-MAY-18:05 | 651.65 | 10-MAY-04:00 |
June | 2337.76 | 01-JUN-14:09 | 1782.39 | 01-JUN-08:09 | 2912.71 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 227.76 | 11-JUN-18:10 | 417.33 | 07-JUN-05:00 |
July | 2337.76 | 01-JUL-10:09 | 1782.39 | 01-JUL-09:09 | 2912.71 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 265.43 | 09-JUL-19:27 | 328.22 | 28-JUL-24:00 |
August | 2337.76 | 01-AUG-14:09 | 1782.39 | 01-AUG-08:09 | 2912.71 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 318.63 | 18-AUG-20:10 | 189.45 | 25-AUG-04:45 |
September | 2337.76 | 01-SEP-14:09 | 1782.39 | 01-SEP-08:09 | 2912.71 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 127.08 | 03-SEP-18:10 | 457.38 | 29-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 1782.39 | 02-OCT-08:09 | 2912.71 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.35 | 11-OCT-14:00 | 973.32 | 28-OCT-04:00 |
November | 2337.76 | 01-NOV-14:09 | 1782.39 | 01-NOV-08:09 | 2912.71 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.65 | 19-NOV-15:00 | 1440.55 | 07-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 1782.39 | 01-DEC-09:09 | 2912.71 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2241.79 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1782.39 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.45 | |||||
Maximum of Months | 2337.76 | 1782.39 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 318.63 | 2396.29 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1725.71 | 02-JAN-09:09 | 437.18 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2042.90 | 07-JAN-05:10 |
February | 2337.76 | 01-FEB-15:09 | 1725.71 | 01-FEB-09:09 | 437.18 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.06 | 28-FEB-15:00 | 2342.28 | 12-FEB-00:55 |
March | 2337.76 | 01-MAR-15:09 | 1725.71 | 01-MAR-09:09 | 437.18 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.58 | 30-MAR-16:00 | 1515.72 | 22-MAR-05:00 |
April | 2337.76 | 01-APR-10:09 | 1725.71 | 01-APR-09:09 | 437.18 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.53 | 04-APR-15:00 | 729.69 | 05-APR-05:00 |
May | 2337.76 | 01-MAY-14:09 | 1725.71 | 01-MAY-08:09 | 437.18 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 141.60 | 29-MAY-18:05 | 620.73 | 10-MAY-04:00 |
June | 2337.76 | 01-JUN-14:09 | 1725.71 | 01-JUN-08:09 | 437.18 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 228.06 | 11-JUN-18:10 | 435.85 | 07-JUN-02:53 |
July | 2337.76 | 01-JUL-10:09 | 1725.71 | 01-JUL-09:09 | 437.18 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 260.32 | 09-JUL-19:27 | 319.57 | 28-JUL-22:00 |
August | 2337.76 | 01-AUG-14:09 | 1725.71 | 01-AUG-08:09 | 437.18 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 318.55 | 18-AUG-20:10 | 177.49 | 25-AUG-05:00 |
September | 2337.76 | 01-SEP-14:09 | 1725.71 | 01-SEP-08:09 | 437.18 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 122.62 | 03-SEP-18:20 | 431.73 | 29-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 1725.71 | 02-OCT-08:09 | 437.18 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.34 | 11-OCT-14:00 | 919.40 | 28-OCT-04:00 |
November | 2337.76 | 01-NOV-14:09 | 1725.71 | 01-NOV-08:09 | 437.18 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 | 19-NOV-15:00 | 1384.49 | 07-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 1725.71 | 01-DEC-09:09 | 437.18 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2146.68 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1725.71 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.49 | |||||
Maximum of Months | 2337.76 | 1725.71 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 318.55 | 2342.28 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 25397.65 | 07-JAN-17:00 |
February | 0.00 | 01-FEB-00:10 | 2.58 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 01-FEB-18:53 | 25582.19 | 11-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 2.58 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.91 | 28-MAR-17:00 | 13413.02 | 22-MAR-11:10 |
April | 0.00 | 01-APR-00:10 | 2.58 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.80 | 16-APR-11:03 | 6631.01 | 05-APR-11:01 |
May | 0.00 | 01-MAY-00:10 | 2.58 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 959.32 | 30-MAY-11:02 | 2314.79 | 24-MAY-11:01 |
June | 0.00 | 01-JUN-00:10 | 2.58 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1951.54 | 06-JUN-11:02 | 1340.81 | 07-JUN-07:01 |
July | 0.00 | 01-JUL-00:10 | 2.58 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2627.10 | 08-JUL-11:01 | 2067.41 | 28-JUL-11:02 |
August | 0.00 | 01-AUG-00:10 | 2.58 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2142.01 | 01-AUG-11:01 | 1150.90 | 08-AUG-16:53 |
September | 0.00 | 01-SEP-00:10 | 2.58 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 703.58 | 09-SEP-11:03 | 2126.25 | 30-SEP-11:02 |
October | 0.00 | 01-OCT-00:10 | 2.58 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.18 | 10-OCT-16:00 | 5890.60 | 25-OCT-11:01 |
November | 0.00 | 01-NOV-00:10 | 2.58 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.87 | 19-NOV-14:55 | 14645.21 | 20-NOV-12:03 |
December | 0.00 | 01-DEC-00:10 | 2.58 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 17693.11 | 17-DEC-18:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1150.90 | ||||
Maximum of Months | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2627.10 | 25582.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3423.11 | 22-JAN-16:25 | 5888.82 | 2697.72 | 4891.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 600.35 |
February | 3947.36 | 28-FEB-16:00 | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.10 |
March | 18463.55 | 30-MAR-21:50 | 0.00 | 163.56 | 1210.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.68 |
April | 30541.32 | 18-APR-20:41 | 0.00 | 572.47 | 4235.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.88 |
May | 32135.04 | 18-MAY-00:07 | 0.00 | 817.82 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.51 |
June | 37071.18 | 08-JUN-20:19 | 0.00 | 736.04 | 5445.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.86 |
July | 27104.46 | 07-JUL-22:03 | 0.00 | 245.35 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 240.74 | 0.00 |
August | 26681.03 | 18-AUG-22:03 | 0.00 | 245.35 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 414.42 | 0.00 |
September | 34371.99 | 14-SEP-21:27 | 0.00 | 654.26 | 4840.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.90 |
October | 24945.29 | 19-OCT-20:42 | 0.00 | 408.91 | 3025.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.98 |
November | 5939.95 | 04-NOV-15:55 | 11777.63 | 4046.58 | 5502.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.03 |
December | 3955.10 | 13-DEC-16:00 | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.52 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3423.11 | 0.00 | 163.56 | 1210.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37071.18 | 11777.63 | 4046.58 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 414.42 | 600.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 57336.66 | 27-JAN-07:05 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.42 |
February | 55019.35 | 09-FEB-07:05 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.43 |
March | 129445.49 | 31-MAR-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.03 |
April | 159601.74 | 18-APR-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.48 |
May | 154559.49 | 17-MAY-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.55 |
June | 188327.17 | 08-JUN-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.02 |
July | 127808.60 | 03-JUL-06:02 | 18607.26 | 2067.29 | 12372.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.32 |
August | 125842.57 | 26-AUG-06:02 | 15506.05 | 1722.75 | 7732.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.97 |
September | 164240.82 | 14-SEP-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.79 |
October | 150252.44 | 03-OCT-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.27 |
November | 93574.90 | 04-NOV-06:03 | 9303.63 | 1033.65 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.00 |
December | 50086.20 | 04-DEC-07:05 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.80 |
Annual Sum or Average | |||||||||||
Minimum of Months | 50086.20 | 9303.63 | 1033.65 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.97 | |
Maximum of Months | 188327.17 | 18607.26 | 2067.29 | 12372.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4156.40 | 26-JAN-12:20 | 2045.54 | 1782.39 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.98 |
February | 16372.11 | 28-FEB-22:01 | 0.00 | 292.19 | 5765.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.67 |
March | 19945.35 | 13-MAR-22:11 | 0.00 | 324.66 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.47 |
April | 18085.10 | 11-APR-21:21 | 0.00 | 259.73 | 5124.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.56 |
May | 18512.69 | 18-MAY-01:11 | 0.00 | 259.73 | 5124.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.00 |
June | 20387.75 | 11-JUN-00:21 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.21 |
July | 16175.06 | 07-JUL-21:23 | 0.00 | 97.40 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 142.39 | 0.00 |
August | 16546.43 | 18-AUG-22:03 | 0.00 | 97.40 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 177.96 | 0.00 |
September | 16399.04 | 18-SEP-20:11 | 0.00 | 292.19 | 5765.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.20 |
October | 16806.21 | 11-OCT-20:41 | 0.00 | 259.73 | 5124.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.31 |
November | 14639.08 | 08-NOV-21:15 | 0.00 | 64.93 | 1281.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.27 |
December | 15677.14 | 12-DEC-22:11 | 0.00 | 227.26 | 4483.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.14 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4156.40 | 0.00 | 64.93 | 1281.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20387.75 | 2045.54 | 1782.39 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 177.96 | 300.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3380.22 | 26-JAN-19:33 | 2629.98 | 2876.18 | 1020.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.07 |
February | 17142.22 | 26-FEB-19:45 | 0.00 | 64.93 | 144.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.35 |
March | 15537.64 | 13-MAR-20:41 | 0.00 | 324.66 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.13 |
April | 16131.84 | 14-APR-20:21 | 0.00 | 324.66 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.02 |
May | 15390.06 | 14-MAY-18:21 | 0.00 | 324.66 | 721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 | 0.00 |
June | 17716.19 | 10-JUN-21:34 | 0.00 | 259.73 | 576.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.29 |
July | 12819.63 | 09-JUL-19:23 | 0.00 | 97.40 | 216.32 | 0.00 | 0.00 | 0.00 | 0.00 | 247.50 | 0.00 |
August | 12941.02 | 18-AUG-22:43 | 0.00 | 97.40 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 153.48 | 0.00 |
September | 16649.35 | 15-SEP-00:29 | 0.00 | 259.73 | 769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20098.46 | 11-OCT-23:17 | 0.00 | 129.86 | 384.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.11 |
November | 21539.88 | 08-NOV-21:33 | 0.00 | 129.86 | 384.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.44 |
December | 3915.43 | 12-DEC-14:00 | 2045.54 | 1725.71 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3380.22 | 0.00 | 64.93 | 144.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21539.88 | 2629.98 | 2876.18 | 1020.08 | 0.00 | 0.00 | 0.00 | 0.00 | 247.50 | 380.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.09 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.44 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.66 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.41 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.90 |
June | 0.00 | 01-JUN-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.96 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.82 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.75 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.38 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.46 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.52 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.82 | |
Maximum of Months | 0.00 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.52 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.613082E+11 | 48768.78 | 07-JAN-17:00 | 0.803067E+11 | 168839.89 | 09-JAN-07:10 |
February | 0.549265E+11 | 54481.48 | 28-FEB-16:00 | 0.470828E+11 | 188335.55 | 12-FEB-09:09 |
March | 0.617002E+11 | 64389.66 | 30-MAR-15:00 | 0.126545E+11 | 62938.84 | 19-MAR-08:20 |
April | 0.641990E+11 | 64810.28 | 17-APR-16:19 | 0.830995E+10 | 55990.01 | 07-APR-06:30 |
May | 0.782757E+11 | 71219.74 | 06-MAY-15:00 | 0.766780E+10 | 4938.67 | 01-MAY-11:20 |
June | 0.927070E+11 | 79765.72 | 06-JUN-14:30 | 0.727749E+10 | 4887.52 | 01-JUN-11:30 |
July | 0.100509E+12 | 89504.82 | 08-JUL-14:20 | 0.735691E+10 | 4849.64 | 03-JUL-11:30 |
August | 0.105558E+12 | 86211.33 | 18-AUG-15:00 | 0.740966E+10 | 4847.78 | 31-AUG-11:39 |
September | 0.837710E+11 | 81306.82 | 07-SEP-15:00 | 0.722973E+10 | 4879.82 | 29-SEP-11:50 |
October | 0.685243E+11 | 72617.73 | 10-OCT-15:00 | 0.806040E+10 | 54885.98 | 26-OCT-06:30 |
November | 0.584347E+11 | 57519.74 | 04-NOV-15:00 | 0.141452E+11 | 108947.78 | 22-NOV-07:10 |
December | 0.597253E+11 | 52661.19 | 12-DEC-15:09 | 0.386563E+11 | 145000.37 | 04-DEC-07:10 |
Annual Sum or Average | 0.889639E+12 | 0.246158E+12 | ||||
Minimum of Months | 0.549265E+11 | 48768.78 | 0.722973E+10 | 4847.78 | ||
Maximum of Months | 0.105558E+12 | 89504.82 | 0.803067E+11 | 188335.55 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.267460E+11 | 0.401236E+10 | 0.163682E+11 | 0.00 | 0.141707E+11 | 0.00 | 0.00 | 10920013.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.240160E+11 | 0.336320E+10 | 0.148500E+11 | 0.00 | 0.119102E+11 | 0.00 | 0.00 | 0.787117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.259299E+11 | 0.334486E+10 | 0.167807E+11 | 0.00 | 0.118718E+11 | 0.00 | 0.00 | 0.377298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.229653E+11 | 0.285878E+10 | 0.159462E+11 | 0.00 | 0.112425E+11 | 0.00 | 0.00 | 0.111862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.238627E+11 | 0.262477E+10 | 0.165744E+11 | 0.00 | 0.116751E+11 | 0.00 | 0.00 | 0.235388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.232671E+11 | 0.239558E+10 | 0.162059E+11 | 0.00 | 0.118804E+11 | 0.00 | 0.00 | 0.389581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.231091E+11 | 0.252971E+10 | 0.163148E+11 | 0.00 | 0.125595E+11 | 0.00 | 0.00 | 0.459962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.238382E+11 | 0.280480E+10 | 0.167807E+11 | 0.00 | 0.129067E+11 | 0.00 | 0.00 | 0.492276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231307E+11 | 0.307319E+10 | 0.159462E+11 | 0.00 | 0.116432E+11 | 0.00 | 0.00 | 0.299777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261646E+11 | 0.356736E+10 | 0.163682E+11 | 0.00 | 0.115680E+11 | 0.00 | 0.00 | 0.108561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252426E+11 | 0.379530E+10 | 0.158468E+11 | 0.00 | 0.113870E+11 | 0.00 | 0.00 | 0.216308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.263094E+11 | 0.410541E+10 | 0.163148E+11 | 0.00 | 0.127108E+11 | 0.00 | 0.00 | 0.284843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294582E+12 | 0.384753E+11 | 0.194297E+12 | 0.145526E+12 | 0.00 | 0.216760E+12 | |||||||
Minimum of Months | 0.229653E+11 | 0.239558E+10 | 0.148500E+11 | 0.00 | 0.112425E+11 | 0.00 | 0.00 | 10920013.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.267460E+11 | 0.410541E+10 | 0.167807E+11 | 0.00 | 0.141707E+11 | 0.00 | 0.00 | 0.492276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.721904E+11 | 0.00 | 0.811621E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.397355E+11 | 0.00 | 0.734733E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.456484E+10 | 0.00 | 0.808971E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.696021E+09 | 0.00 | 0.761393E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.766780E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.727749E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.735691E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.740966E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.722973E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.450239E+09 | 0.00 | 0.761016E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.659028E+10 | 0.00 | 0.755497E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.306475E+11 | 0.00 | 0.800885E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.154875E+12 | 0.912827E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.722973E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.721904E+11 | 0.00 | 0.811621E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 24449.72 | 02-JAN-09:09 | 3371.20 | 01-JAN-06:10 | 10740.89 | 02-JAN-09:09 | 0.00 | 12153.43 | 08-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 24449.72 | 01-FEB-09:09 | 3371.20 | 01-FEB-06:10 | 10740.89 | 01-FEB-09:09 | 0.00 | 12676.40 | 12-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 24449.72 | 01-MAR-10:30 | 3371.20 | 01-MAR-06:10 | 10740.89 | 01-MAR-09:09 | 0.00 | 9827.62 | 19-MAR-08:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 24449.72 | 03-APR-08:09 | 3371.20 | 01-APR-05:10 | 10740.89 | 01-APR-09:09 | 0.00 | 9211.64 | 06-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 24449.72 | 05-MAY-16:00 | 3371.20 | 01-MAY-05:10 | 10740.89 | 01-MAY-08:09 | 0.00 | 10088.03 | 31-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 24449.72 | 07-JUN-08:09 | 3371.20 | 01-JUN-05:10 | 10740.89 | 01-JUN-08:09 | 0.00 | 10088.03 | 12-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 24449.72 | 01-JUL-16:49 | 3371.20 | 01-JUL-05:10 | 10740.89 | 01-JUL-09:09 | 0.00 | 10185.83 | 08-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 24449.72 | 01-AUG-08:09 | 3371.20 | 01-AUG-05:10 | 10740.89 | 01-AUG-08:09 | 0.00 | 10088.03 | 23-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 24449.72 | 01-SEP-16:30 | 3371.20 | 01-SEP-05:10 | 10740.89 | 01-SEP-08:09 | 0.00 | 10088.03 | 07-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 24449.72 | 02-OCT-08:09 | 3371.20 | 01-OCT-05:10 | 10740.89 | 02-OCT-08:09 | 0.00 | 10088.03 | 18-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 24449.72 | 01-NOV-08:09 | 3371.20 | 01-NOV-05:10 | 10740.89 | 01-NOV-08:09 | 0.00 | 10269.16 | 22-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 24449.72 | 01-DEC-09:09 | 3371.20 | 01-DEC-06:10 | 10740.89 | 01-DEC-09:09 | 0.00 | 11226.82 | 03-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 24449.72 | 3371.20 | 10740.89 | 0.00 | 9211.64 | 0.00 | 0.00 | |||||
Maximum of Months | 24449.72 | 3371.20 | 10740.89 | 0.00 | 12676.40 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 1617.32 | 31-JAN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13818.21 | 28-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24704.68 | 30-MAR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24441.46 | 17-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32110.18 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39930.40 | 06-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 48868.44 | 08-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 44250.38 | 01-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39379.51 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30865.07 | 10-OCT-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16378.86 | 05-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10329.58 | 12-DEC-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 1617.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48868.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 48768.78 | 07-JAN-17:00 | 24449.72 | 10740.89 | 3371.20 | 0.00 | 10206.97 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 54481.48 | 28-FEB-16:00 | 24449.72 | 10740.89 | 0.00 | 0.00 | 7141.00 | 0.00 | 0.00 | 12149.87 | 0.00 |
March | 64389.66 | 30-MAR-15:00 | 22873.41 | 10740.89 | 0.00 | 0.00 | 7141.00 | 0.00 | 0.00 | 23634.36 | 0.00 |
April | 64810.28 | 17-APR-16:19 | 24449.72 | 10740.89 | 0.00 | 0.00 | 7141.00 | 0.00 | 0.00 | 22478.67 | 0.00 |
May | 71219.74 | 06-MAY-15:00 | 22873.41 | 10740.89 | 0.00 | 0.00 | 7141.00 | 0.00 | 0.00 | 30464.44 | 0.00 |
June | 79765.72 | 06-JUN-14:30 | 21297.09 | 10740.89 | 0.00 | 0.00 | 8185.85 | 0.00 | 0.00 | 39541.89 | 0.00 |
July | 89504.82 | 08-JUL-14:20 | 19720.78 | 10740.89 | 0.00 | 0.00 | 10174.71 | 0.00 | 0.00 | 48868.44 | 0.00 |
August | 86211.33 | 18-AUG-15:00 | 22873.41 | 10740.89 | 0.00 | 0.00 | 9022.29 | 0.00 | 0.00 | 43574.74 | 0.00 |
September | 81306.82 | 07-SEP-15:00 | 22873.41 | 10740.89 | 0.00 | 0.00 | 8313.01 | 0.00 | 0.00 | 39379.51 | 0.00 |
October | 72617.73 | 10-OCT-15:00 | 24449.72 | 10740.89 | 0.00 | 0.00 | 7251.30 | 0.00 | 0.00 | 30175.82 | 0.00 |
November | 57519.74 | 04-NOV-15:00 | 24449.72 | 10740.89 | 0.00 | 0.00 | 7141.00 | 0.00 | 0.00 | 15188.13 | 0.00 |
December | 52661.19 | 12-DEC-15:09 | 24449.72 | 10740.89 | 0.00 | 0.00 | 7141.00 | 0.00 | 0.00 | 10329.58 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 48768.78 | 19720.78 | 10740.89 | 0.00 | 0.00 | 7141.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89504.82 | 24449.72 | 10740.89 | 3371.20 | 0.00 | 10206.97 | 0.00 | 0.00 | 48868.44 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 164287.16 | 09-JAN-07:10 | 0.00 | 5042.99 | 30-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 186475.55 | 12-FEB-09:09 | 0.00 | 5043.91 | 01-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 60874.68 | 19-MAR-08:20 | 0.00 | 5028.87 | 01-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 54130.01 | 07-APR-06:30 | 0.00 | 4986.19 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4938.67 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4887.52 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4849.64 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4847.78 | 31-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4879.82 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 50352.56 | 26-OCT-06:30 | 0.00 | 4932.43 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 106803.11 | 22-NOV-07:10 | 0.00 | 4985.35 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 143140.37 | 04-DEC-07:10 | 0.00 | 5024.62 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4847.78 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 186475.55 | 0.00 | 5043.91 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.50 | 20.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.33 | 20.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.49 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.47 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.46 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.49 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.48 | 0.00 | 0.00 |
November | 0.50 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.17 | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.83 | 20.12 | 0.00 | 9.83 | 24.48 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.50 | 20.47 | 0.00 | 0.00 | 3.83 | 24.49 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 20.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.50 | 20.08 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 0.00 |
March | 0.17 | 20.51 | 0.00 | 0.00 | 1.17 | 24.52 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.49 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.49 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 24.50 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 24.53 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 24.55 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 24.52 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 24.49 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.48 | 0.00 | 0.00 |
December | 1.67 | 20.36 | 0.00 | 0.00 | 0.33 | 24.53 | 0.00 | 0.00 |
Annual Sum or Average | 8.67 | 20.17 | 0.00 | 91.50 | 24.52 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.33 | 20.51 | 0.00 | 0.00 | 30.50 | 24.55 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.00 | 20.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.00 | 20.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.50 | 0.00 | 0.00 | 0.50 | 24.48 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.46 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.47 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.50 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 24.50 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.48 | 0.00 | 0.00 |
October | 0.17 | 20.55 | 0.00 | 0.00 | 0.83 | 24.47 | 0.00 | 0.00 |
November | 0.33 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.67 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.00 | 20.14 | 0.00 | 20.50 | 24.49 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.00 | 20.55 | 0.00 | 0.00 | 9.17 | 24.50 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 67.83 | 12.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 42.17 | 13.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 53.33 | 13.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14.17 | 13.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35.33 | 14.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 41.17 | 13.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 137.83 | 13.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 391.83 | 13.32 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.83 | 14.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.27 | 323.50 | 21.14 | 323.50 | 21.14 |
February | 376.00 | 21.85 | 184.00 | 21.24 | 184.00 | 21.24 |
March | 372.50 | 22.72 | 42.33 | 22.02 | 29.00 | 21.15 |
April | 252.67 | 23.36 | 59.33 | 23.68 | 27.50 | 23.43 |
May | 114.33 | 23.74 | 259.67 | 23.88 | 60.83 | 23.85 |
June | 12.33 | 23.83 | 316.83 | 23.89 | 0.00 | 0.00 |
July | 25.33 | 23.89 | 393.33 | 23.89 | 25.33 | 23.89 |
August | 0.00 | 0.00 | 406.50 | 23.89 | 0.00 | 0.00 |
September | 22.50 | 23.82 | 308.33 | 23.89 | 13.00 | 23.89 |
October | 260.67 | 23.36 | 105.50 | 23.88 | 32.17 | 23.86 |
November | 364.33 | 22.66 | 61.50 | 22.48 | 47.33 | 22.06 |
December | 415.00 | 21.60 | 178.50 | 21.28 | 178.50 | 21.28 |
Annual Sum or Average | 2629.67 | 22.38 | 2639.33 | 23.12 | 921.17 | 21.69 |
Minimum of Months | 0.00 | 0.00 | 42.33 | 21.14 | 0.00 | 0.00 |
Maximum of Months | 415.00 | 23.89 | 406.50 | 23.89 | 323.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.31 | 196.67 | 21.19 | 196.67 | 21.19 |
February | 371.17 | 21.94 | 91.83 | 21.23 | 91.83 | 21.23 |
March | 311.67 | 22.68 | 51.17 | 23.76 | 2.33 | 21.11 |
April | 142.00 | 23.12 | 145.00 | 23.88 | 7.67 | 23.88 |
May | 46.50 | 23.56 | 315.33 | 23.89 | 27.00 | 23.89 |
June | 13.50 | 23.81 | 362.33 | 23.89 | 9.00 | 23.90 |
July | 43.17 | 23.89 | 415.00 | 23.89 | 43.17 | 23.89 |
August | 44.00 | 23.90 | 421.33 | 23.89 | 44.00 | 23.90 |
September | 36.50 | 23.82 | 375.67 | 23.89 | 31.83 | 23.89 |
October | 181.33 | 22.96 | 137.50 | 23.87 | 41.67 | 23.84 |
November | 325.00 | 22.47 | 47.00 | 23.46 | 19.00 | 22.83 |
December | 403.17 | 21.57 | 69.83 | 21.54 | 68.83 | 21.51 |
Annual Sum or Average | 2332.00 | 22.23 | 2628.67 | 23.52 | 583.00 | 22.23 |
Minimum of Months | 13.50 | 21.31 | 47.00 | 21.19 | 2.33 | 21.11 |
Maximum of Months | 414.00 | 23.90 | 421.33 | 23.89 | 196.67 | 23.90 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 403.83 | 21.76 | 139.50 | 21.23 | 139.50 | 21.23 |
February | 316.00 | 22.08 | 83.17 | 21.18 | 81.00 | 21.11 |
March | 258.33 | 22.97 | 78.67 | 23.59 | 8.33 | 21.11 |
April | 148.33 | 23.23 | 156.33 | 23.84 | 8.83 | 22.97 |
May | 45.50 | 23.53 | 296.83 | 23.89 | 15.33 | 23.89 |
June | 8.17 | 23.66 | 340.83 | 23.89 | 0.00 | 0.00 |
July | 9.50 | 23.89 | 398.33 | 23.89 | 9.50 | 23.89 |
August | 0.00 | 0.00 | 409.00 | 23.89 | 0.00 | 0.00 |
September | 7.33 | 23.59 | 361.00 | 23.89 | 1.50 | 23.89 |
October | 109.83 | 23.04 | 209.67 | 23.89 | 16.00 | 23.88 |
November | 214.33 | 22.90 | 80.50 | 23.72 | 8.50 | 22.25 |
December | 370.50 | 22.38 | 66.83 | 22.23 | 44.00 | 21.36 |
Annual Sum or Average | 1891.67 | 22.49 | 2620.67 | 23.60 | 332.50 | 21.63 |
Minimum of Months | 0.00 | 0.00 | 66.83 | 21.18 | 0.00 | 0.00 |
Maximum of Months | 403.83 | 23.89 | 409.00 | 23.89 | 139.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.46 | 199.50 | 21.17 | 199.50 | 21.17 |
February | 351.83 | 21.89 | 128.33 | 21.16 | 128.33 | 21.16 |
March | 311.83 | 22.67 | 66.67 | 23.17 | 17.17 | 21.11 |
April | 201.67 | 23.05 | 117.83 | 23.76 | 19.50 | 23.09 |
May | 111.83 | 23.58 | 282.33 | 23.88 | 61.17 | 23.86 |
June | 23.67 | 23.71 | 333.67 | 23.89 | 9.67 | 23.89 |
July | 47.33 | 23.89 | 400.33 | 23.89 | 47.33 | 23.89 |
August | 24.33 | 23.89 | 410.50 | 23.89 | 24.33 | 23.89 |
September | 42.33 | 23.74 | 348.67 | 23.89 | 27.50 | 23.89 |
October | 168.33 | 22.86 | 176.83 | 23.88 | 35.50 | 23.84 |
November | 272.67 | 22.61 | 65.67 | 23.54 | 18.83 | 22.68 |
December | 392.17 | 21.91 | 93.17 | 21.68 | 83.50 | 21.42 |
Annual Sum or Average | 2362.00 | 22.36 | 2623.50 | 23.44 | 672.33 | 22.12 |
Minimum of Months | 23.67 | 21.46 | 65.67 | 21.16 | 9.67 | 21.11 |
Maximum of Months | 414.00 | 23.89 | 410.50 | 23.89 | 199.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.26647 | 30.60957 | -0.5740 | 12.80069 |
February | 376.00000 | 21.84350 | 32.67703 | -0.3934 | 10.32209 |
March | 422.00000 | 22.84478 | 38.45638 | -0.0493 | 6.96502 |
April | 405.00000 | 23.54951 | 44.29599 | 0.20589 | 6.93176 |
May | 418.00000 | 23.84599 | 51.85286 | -0.5252 | 11.15323 |
June | 408.00000 | 23.88789 | 51.22911 | -0.4331 | 9.07787 |
July | 415.00000 | 23.88960 | 55.72417 | -0.3806 | 8.08489 |
August | 422.00000 | 23.88960 | 55.68812 | -0.3732 | 7.96554 |
September | 405.00000 | 23.88487 | 53.80499 | -0.4548 | 9.43638 |
October | 414.00000 | 23.55176 | 47.50070 | 0.25081 | 7.16542 |
November | 399.00000 | 22.76174 | 38.24510 | -0.0629 | 7.15222 |
December | 415.00000 | 21.59842 | 35.14765 | -0.4126 | 10.05141 |
Annual Sum or Average | 4913.00000 | 23.07635 | 44.70418 | -0.2669 | 8.91980 |
Minimum of Months | 376.00000 | 21.26647 | 30.60957 | -0.5740 | 6.93176 |
Maximum of Months | 422.00000 | 23.88960 | 55.72417 | 0.25081 | 12.80069 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.29552 | 27.78591 | -0.4773 | 10.67296 |
February | 376.00000 | 21.95580 | 30.19609 | -0.2717 | 8.70868 |
March | 422.00000 | 22.99688 | 35.83406 | 0.08048 | 6.73744 |
April | 405.00000 | 23.61852 | 42.13539 | 0.30843 | 7.74423 |
May | 418.00000 | 23.86141 | 49.76192 | -0.4299 | 9.17287 |
June | 408.00000 | 23.90614 | 51.47087 | -0.3484 | 7.69426 |
July | 415.00000 | 23.91193 | 57.37754 | -0.2934 | 6.85002 |
August | 422.00000 | 23.91281 | 57.81468 | -0.2872 | 6.77370 |
September | 405.00000 | 23.89613 | 54.49760 | -0.3773 | 8.10696 |
October | 414.00000 | 23.48678 | 46.41985 | 0.30790 | 7.86060 |
November | 399.00000 | 22.73869 | 36.43257 | 0.01282 | 6.95304 |
December | 415.00000 | 21.63160 | 32.67385 | -0.3188 | 8.55712 |
Annual Sum or Average | 4913.00000 | 23.10923 | 43.64738 | -0.1747 | 7.98097 |
Minimum of Months | 376.00000 | 21.29552 | 27.78591 | -0.4773 | 6.73744 |
Maximum of Months | 422.00000 | 23.91281 | 57.81468 | 0.30843 | 10.67296 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.81077 | 26.36234 | -0.3574 | 9.58812 |
February | 376.00000 | 22.36022 | 28.31263 | -0.1799 | 8.65107 |
March | 422.00000 | 23.31718 | 33.35088 | 0.14685 | 7.24193 |
April | 405.00000 | 23.64311 | 40.55484 | 0.29779 | 7.83274 |
May | 418.00000 | 23.84743 | 47.76818 | -0.4501 | 9.67826 |
June | 408.00000 | 23.88458 | 48.42658 | -0.3601 | 7.96650 |
July | 415.00000 | 23.88958 | 52.84243 | -0.3035 | 7.06072 |
August | 422.00000 | 23.88950 | 52.32410 | -0.2769 | 6.74463 |
September | 405.00000 | 23.88267 | 49.53580 | -0.3568 | 7.89606 |
October | 414.00000 | 23.66331 | 42.92701 | 0.36925 | 8.68795 |
November | 399.00000 | 23.35420 | 33.06732 | 0.17857 | 7.22355 |
December | 415.00000 | 22.53666 | 30.01264 | -0.1108 | 7.51018 |
Annual Sum or Average | 4913.00000 | 23.34647 | 40.56111 | -0.1175 | 8.00255 |
Minimum of Months | 376.00000 | 21.81077 | 26.36234 | -0.4501 | 6.74463 |
Maximum of Months | 422.00000 | 23.88958 | 52.84243 | 0.36925 | 9.67826 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.45949 | 26.98808 | -0.4663 | 10.90597 |
February | 376.00000 | 22.01515 | 29.14531 | -0.2881 | 9.37384 |
March | 422.00000 | 22.97865 | 34.99551 | 0.04295 | 7.20048 |
April | 405.00000 | 23.46418 | 42.59134 | 0.23121 | 7.47441 |
May | 418.00000 | 23.80250 | 51.12678 | -0.4946 | 10.80531 |
June | 408.00000 | 23.87925 | 51.55757 | -0.3857 | 8.40794 |
July | 415.00000 | 23.88942 | 56.92366 | -0.3196 | 7.25100 |
August | 422.00000 | 23.88964 | 56.24325 | -0.2955 | 6.95073 |
September | 405.00000 | 23.87122 | 53.14831 | -0.3818 | 8.33331 |
October | 414.00000 | 23.47011 | 45.13156 | 0.30687 | 8.29052 |
November | 399.00000 | 23.01358 | 34.76843 | 0.07777 | 7.22188 |
December | 415.00000 | 22.01522 | 31.29573 | -0.2501 | 8.43510 |
Annual Sum or Average | 4913.00000 | 23.15344 | 42.94395 | -0.1855 | 8.38269 |
Minimum of Months | 376.00000 | 21.45949 | 26.98808 | -0.4946 | 6.95073 |
Maximum of Months | 422.00000 | 23.88964 | 56.92366 | 0.30687 | 10.90597 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.126593E+09 | 35332652.06 | 21.22 | 0.126593E+09 | 70.94 | 0.00 | 0.37 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 5458.04 | 28-FEB-15:10 | 5458.04 | 28-FEB-15:10 | 0.10 | 22-FEB-15:53 | 1497.10 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.116085E+10 | 0.309899E+09 | 108.02 | 0.906503E+09 | 0.254343E+09 | 0.00 | 1.00 | 30-MAR-21:50 | 0.00 | 01-MAR-00:10 | 37690.09 | 30-MAR-21:50 | 29225.79 | 30-MAR-21:50 | 8464.30 | 30-MAR-21:50 | 8218.69 | 30-MAR-21:50 | 0.00 | 01-MAR-00:10 |
April | 0.433427E+10 | 0.114931E+10 | 240.60 | 0.356594E+10 | 0.768326E+09 | 0.00 | 1.00 | 17-APR-21:40 | 0.00 | 01-APR-00:10 | 37045.21 | 18-APR-20:41 | 29668.13 | 17-APR-21:40 | 9988.27 | 18-APR-20:41 | 7882.81 | 18-APR-20:41 | 0.00 | 01-APR-00:10 |
May | 0.113228E+11 | 0.288307E+10 | 369.91 | 0.845018E+10 | 0.287262E+10 | 0.00 | 1.00 | 03-MAY-20:21 | 0.00 | 01-MAY-00:10 | 38626.98 | 03-MAY-20:21 | 32086.06 | 15-MAY-20:50 | 16245.56 | 22-MAY-23:15 | 8275.96 | 19-MAY-21:00 | 0.00 | 01-MAY-00:10 |
June | 0.219516E+11 | 0.551790E+10 | 532.73 | 0.163762E+11 | 0.557547E+10 | 0.00 | 1.00 | 02-JUN-01:30 | 0.00 | 01-JUN-00:10 | 37676.54 | 06-JUN-00:20 | 35291.60 | 08-JUN-20:19 | 14969.60 | 07-JUN-02:00 | 8291.26 | 09-JUN-20:16 | 0.00 | 01-JUN-00:05 |
July | 0.264721E+11 | 0.663333E+10 | 597.35 | 0.189039E+11 | 0.756829E+10 | 0.00 | 1.00 | 07-JUL-20:10 | 0.00 | 01-JUL-00:05 | 39317.22 | 28-JUL-20:30 | 30208.75 | 07-JUL-22:03 | 21511.62 | 28-JUL-20:30 | 9343.02 | 09-JUL-18:43 | 0.00 | 01-JUL-00:05 |
August | 0.287555E+11 | 0.712727E+10 | 623.35 | 0.201695E+11 | 0.858598E+10 | 0.00 | 1.00 | 02-AUG-20:10 | 0.00 | 01-AUG-00:05 | 38277.17 | 03-AUG-20:43 | 29766.67 | 18-AUG-22:03 | 9654.82 | 10-AUG-20:43 | 9286.57 | 18-AUG-20:10 | 0.00 | 01-AUG-00:05 |
September | 0.167095E+11 | 0.414106E+10 | 474.57 | 0.119380E+11 | 0.477155E+10 | 0.00 | 1.00 | 13-SEP-20:19 | 0.00 | 01-SEP-00:05 | 39156.03 | 21-SEP-20:27 | 31799.13 | 14-SEP-20:20 | 19362.10 | 21-SEP-23:00 | 8257.57 | 21-SEP-20:27 | 0.00 | 01-SEP-00:05 |
October | 0.478787E+10 | 0.120166E+10 | 232.26 | 0.338247E+10 | 0.140540E+10 | 0.00 | 0.99 | 19-OCT-02:15 | 0.00 | 01-OCT-00:10 | 30758.49 | 19-OCT-20:42 | 17292.17 | 19-OCT-20:42 | 13466.33 | 19-OCT-20:42 | 6536.49 | 19-OCT-20:42 | 0.00 | 01-OCT-00:10 |
November | 0.467105E+09 | 0.124057E+09 | 88.41 | 0.325108E+09 | 0.141997E+09 | 0.00 | 0.48 | 05-NOV-15:20 | 0.00 | 01-NOV-00:10 | 7823.66 | 05-NOV-15:00 | 5476.11 | 05-NOV-16:00 | 3188.29 | 04-NOV-15:55 | 2015.33 | 05-NOV-15:30 | 0.00 | 01-NOV-00:10 |
December | 24275496.44 | 6782689.02 | 9.66 | 17420356.39 | 6855140.05 | 0.00 | 0.17 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 | 2443.89 | 12-DEC-15:10 | 1836.62 | 12-DEC-15:10 | 607.26 | 12-DEC-15:10 | 679.13 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.116113E+12 | 0.291297E+11 | 3298.09 | 0.841617E+11 | 0.319508E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.287555E+11 | 0.712727E+10 | 623.35 | 0.201695E+11 | 0.858598E+10 | 0.00 | 1.00 | 0.00 | 39317.22 | 35291.60 | 21511.62 | 9343.02 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 6688339.33 | 2106334.20 | 2.67 | 5507927.08 | 1180412.26 | 0.00 | 0.05 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 | 2913.85 | 31-JAN-15:10 | 2418.34 | 31-JAN-15:10 | 495.51 | 31-JAN-15:10 | 914.18 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.161480E+10 | 0.493567E+09 | 42.15 | 0.158561E+10 | 29193847.73 | 0.00 | 0.44 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 30788.33 | 28-FEB-15:10 | 29828.71 | 28-FEB-15:10 | 959.62 | 28-FEB-15:10 | 9258.42 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.911670E+10 | 0.266695E+10 | 148.31 | 0.683956E+10 | 0.227714E+10 | 0.00 | 1.00 | 31-MAR-06:03 | 0.00 | 01-MAR-00:10 | 178212.01 | 31-MAR-06:03 | 103825.49 | 31-MAR-06:03 | 74386.52 | 31-MAR-06:03 | 42328.68 | 31-MAR-06:03 | 0.00 | 01-MAR-00:10 |
April | 0.281703E+11 | 0.816691E+10 | 267.22 | 0.220203E+11 | 0.614999E+10 | 0.00 | 1.00 | 18-APR-06:03 | 0.00 | 01-APR-00:10 | 182566.68 | 23-APR-08:62 | 110051.20 | 18-APR-06:03 | 90946.68 | 23-APR-08:62 | 43143.91 | 23-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.606874E+11 | 0.169722E+11 | 368.10 | 0.427110E+11 | 0.179765E+11 | 0.00 | 1.00 | 03-MAY-06:03 | 0.00 | 01-MAY-00:10 | 186393.05 | 31-MAY-06:02 | 126572.93 | 07-MAY-08:62 | 94324.99 | 26-MAY-06:02 | 43735.85 | 31-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.987132E+11 | 0.269974E+11 | 413.34 | 0.668251E+11 | 0.318881E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:05 | 189091.57 | 18-JUN-08:62 | 158537.10 | 11-JUN-08:62 | 90838.10 | 21-JUN-06:02 | 45014.73 | 25-JUN-08:62 | 0.00 | 01-JUN-00:05 |
July | 0.116974E+12 | 0.315420E+11 | 432.75 | 0.732562E+11 | 0.437180E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 193956.78 | 30-JUL-08:62 | 129703.74 | 25-JUL-06:02 | 101296.90 | 28-JUL-06:02 | 46283.29 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.125334E+12 | 0.333487E+11 | 444.41 | 0.763611E+11 | 0.489725E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:05 | 192783.66 | 20-AUG-08:62 | 136590.94 | 26-AUG-06:02 | 101173.76 | 23-AUG-06:02 | 45848.54 | 06-AUG-08:62 | 0.00 | 01-AUG-00:05 |
September | 0.749777E+11 | 0.203198E+11 | 382.64 | 0.474468E+11 | 0.275309E+11 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 194067.97 | 17-SEP-08:62 | 128809.84 | 16-SEP-06:02 | 93128.02 | 17-SEP-08:04 | 45472.59 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.263027E+11 | 0.731098E+10 | 228.27 | 0.176120E+11 | 0.869070E+10 | 0.00 | 1.00 | 02-OCT-06:03 | 0.00 | 01-OCT-00:10 | 190637.35 | 19-OCT-06:02 | 109967.73 | 18-OCT-06:02 | 106464.65 | 19-OCT-06:04 | 44245.77 | 19-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.456217E+10 | 0.134625E+10 | 107.75 | 0.323341E+10 | 0.132877E+10 | 0.00 | 0.51 | 04-NOV-15:55 | 0.00 | 01-NOV-00:10 | 122210.71 | 04-NOV-06:03 | 66449.18 | 04-NOV-06:03 | 55761.52 | 04-NOV-06:03 | 29059.80 | 04-NOV-06:03 | 0.00 | 01-NOV-00:10 |
December | 0.502009E+09 | 0.151917E+09 | 16.97 | 0.324253E+09 | 0.177756E+09 | 0.00 | 0.32 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 | 22982.09 | 12-DEC-15:10 | 16278.10 | 12-DEC-15:10 | 7304.31 | 12-DEC-14:00 | 6852.87 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.546962E+12 | 0.149319E+12 | 2854.59 | 0.358221E+12 | 0.188741E+12 | 0.00 | ||||||||||||||
Minimum of Months | 6688339.33 | 2106334.20 | 2.67 | 5507927.08 | 1180412.26 | 0.00 | 0.05 | 0.00 | 2913.85 | 2418.34 | 495.51 | 914.18 | 0.00 | |||||||
Maximum of Months | 0.125334E+12 | 0.333487E+11 | 444.41 | 0.763611E+11 | 0.489725E+11 | 0.00 | 1.00 | 0.00 | 194067.97 | 158537.10 | 106464.65 | 46283.29 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 32029493.02 | 8621715.10 | 23.43 | 26659572.41 | 5369920.61 | 0.00 | 0.28 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 | 2416.59 | 31-JAN-15:10 | 2145.59 | 31-JAN-15:00 | 335.44 | 31-JAN-16:00 | 638.50 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.696968E+09 | 0.176410E+09 | 83.83 | 0.693284E+09 | 3683445.08 | 0.00 | 1.00 | 26-FEB-19:20 | 0.00 | 01-FEB-00:10 | 21420.78 | 26-FEB-19:20 | 21420.78 | 26-FEB-19:20 | 592.87 | 28-FEB-22:01 | 4535.09 | 26-FEB-19:20 | 0.00 | 01-FEB-00:10 |
March | 0.218032E+10 | 0.546002E+09 | 214.55 | 0.177180E+10 | 0.408521E+09 | 0.00 | 1.00 | 13-MAR-20:11 | 0.00 | 01-MAR-00:10 | 22608.29 | 31-MAR-00:10 | 19000.73 | 13-MAR-20:11 | 6471.17 | 30-MAR-00:01 | 4835.50 | 13-MAR-20:11 | 0.00 | 01-MAR-00:10 |
April | 0.479633E+10 | 0.120424E+10 | 289.21 | 0.395827E+10 | 0.838064E+09 | 0.00 | 1.00 | 11-APR-20:11 | 0.00 | 01-APR-00:10 | 23650.16 | 30-APR-18:45 | 19514.53 | 16-APR-19:54 | 10917.89 | 30-APR-18:45 | 5006.17 | 30-APR-18:45 | 0.00 | 01-APR-00:10 |
May | 0.924712E+10 | 0.229593E+10 | 427.78 | 0.703524E+10 | 0.221188E+10 | 0.00 | 1.00 | 04-MAY-21:32 | 0.00 | 01-MAY-00:10 | 23524.14 | 27-MAY-23:35 | 21081.72 | 14-MAY-18:20 | 10810.55 | 27-MAY-23:35 | 4985.92 | 27-MAY-23:35 | 0.00 | 01-MAY-00:10 |
June | 0.151669E+11 | 0.377401E+10 | 558.98 | 0.113494E+11 | 0.381753E+10 | 0.00 | 1.00 | 02-JUN-01:30 | 0.00 | 01-JUN-00:05 | 22795.89 | 06-JUN-01:30 | 21420.78 | 10-JUN-22:08 | 8094.58 | 06-JUN-01:30 | 4986.32 | 09-JUN-20:21 | 0.00 | 01-JUN-00:05 |
July | 0.182224E+11 | 0.453374E+10 | 619.84 | 0.130001E+11 | 0.522225E+10 | 0.00 | 1.00 | 07-JUL-20:08 | 0.00 | 01-JUL-00:10 | 22543.01 | 07-JUL-20:08 | 18236.69 | 07-JUL-21:23 | 6034.78 | 29-JUL-01:15 | 5698.87 | 09-JUL-18:43 | 0.00 | 01-JUL-00:05 |
August | 0.204837E+11 | 0.503622E+10 | 644.17 | 0.144948E+11 | 0.598890E+10 | 0.00 | 1.00 | 02-AUG-20:08 | 0.00 | 01-AUG-00:10 | 23326.33 | 03-AUG-20:43 | 18651.59 | 18-AUG-22:03 | 6109.32 | 19-AUG-21:10 | 5656.48 | 18-AUG-20:08 | 0.00 | 01-AUG-00:05 |
September | 0.135315E+11 | 0.327550E+10 | 532.32 | 0.991586E+10 | 0.361563E+10 | 0.00 | 1.00 | 07-SEP-20:43 | 0.00 | 01-SEP-00:05 | 23439.89 | 29-SEP-20:25 | 18839.01 | 14-SEP-20:10 | 9840.85 | 29-SEP-20:25 | 5254.94 | 07-SEP-20:43 | 0.00 | 01-SEP-00:05 |
October | 0.611712E+10 | 0.146090E+10 | 315.45 | 0.470703E+10 | 0.141009E+10 | 0.00 | 1.00 | 02-OCT-21:40 | 0.00 | 01-OCT-00:10 | 23123.27 | 19-OCT-20:12 | 20347.89 | 11-OCT-20:10 | 9801.58 | 19-OCT-20:12 | 4915.99 | 19-OCT-20:12 | 0.00 | 01-OCT-00:10 |
November | 0.203402E+10 | 0.502764E+09 | 190.39 | 0.166084E+10 | 0.373178E+09 | 0.00 | 1.00 | 01-NOV-20:20 | 0.00 | 01-NOV-00:10 | 23263.56 | 03-NOV-20:20 | 14560.71 | 02-NOV-20:53 | 9602.42 | 03-NOV-20:20 | 4941.41 | 03-NOV-20:20 | 0.00 | 01-NOV-00:10 |
December | 0.392998E+09 | 97166850.52 | 72.66 | 0.274428E+09 | 0.118571E+09 | 0.00 | 1.00 | 12-DEC-21:20 | 0.00 | 01-DEC-00:10 | 22631.83 | 12-DEC-21:20 | 15265.39 | 12-DEC-21:20 | 7366.44 | 12-DEC-21:20 | 4819.33 | 12-DEC-21:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.929014E+11 | 0.229115E+11 | 3972.60 | 0.688877E+11 | 0.240137E+11 | 0.00 | ||||||||||||||
Minimum of Months | 32029493.02 | 8621715.10 | 23.43 | 26659572.41 | 3683445.08 | 0.00 | 0.28 | 0.00 | 2416.59 | 2145.59 | 335.44 | 638.50 | 0.00 | |||||||
Maximum of Months | 0.204837E+11 | 0.503622E+10 | 644.17 | 0.144948E+11 | 0.598890E+10 | 0.00 | 1.00 | 0.00 | 23650.16 | 21420.78 | 10917.89 | 5698.87 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 781527.40 | 191964.13 | 8.64 | 698864.53 | 82662.86 | 0.00 | 0.04 | 31-JAN-15:00 | 0.00 | 01-JAN-00:10 | 287.14 | 31-JAN-15:00 | 260.59 | 31-JAN-15:00 | 27.10 | 31-JAN-15:10 | 70.36 | 31-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.361848E+09 | 81806815.50 | 57.50 | 0.361744E+09 | 103672.97 | 0.00 | 1.00 | 26-FEB-19:45 | 0.00 | 01-FEB-00:10 | 17363.00 | 26-FEB-19:45 | 17363.00 | 26-FEB-19:45 | 16.77 | 22-FEB-14:20 | 3391.80 | 26-FEB-19:45 | 0.00 | 01-FEB-00:10 |
March | 0.111540E+10 | 0.250128E+09 | 157.83 | 0.902498E+09 | 0.212905E+09 | 0.00 | 1.00 | 13-MAR-20:40 | 0.00 | 01-MAR-00:10 | 18559.28 | 30-MAR-23:01 | 14976.05 | 13-MAR-20:40 | 5455.84 | 31-MAR-00:35 | 3659.32 | 30-MAR-23:01 | 0.00 | 01-MAR-00:10 |
April | 0.294550E+10 | 0.665753E+09 | 240.87 | 0.245950E+10 | 0.486005E+09 | 0.00 | 1.00 | 12-APR-20:36 | 0.00 | 01-APR-00:10 | 18667.84 | 18-APR-20:20 | 15556.90 | 16-APR-19:57 | 5397.49 | 18-APR-20:20 | 3664.76 | 18-APR-20:20 | 0.00 | 01-APR-00:10 |
May | 0.628877E+10 | 0.138754E+10 | 358.91 | 0.474176E+10 | 0.154701E+10 | 0.00 | 1.00 | 03-MAY-20:21 | 0.00 | 01-MAY-00:10 | 19470.60 | 26-MAY-20:32 | 16598.83 | 14-MAY-18:21 | 10398.89 | 26-MAY-20:32 | 3784.89 | 26-MAY-20:32 | 0.00 | 01-MAY-00:10 |
June | 0.121744E+11 | 0.266877E+10 | 528.06 | 0.891727E+10 | 0.325711E+10 | 0.00 | 1.00 | 02-JUN-00:35 | 0.00 | 01-JUN-00:10 | 19036.07 | 07-JUN-01:05 | 17255.00 | 10-JUN-21:34 | 8431.91 | 07-JUN-01:05 | 3834.00 | 25-JUN-18:10 | 0.00 | 01-JUN-00:05 |
July | 0.150045E+11 | 0.328711E+10 | 596.76 | 0.104769E+11 | 0.452761E+10 | 0.00 | 1.00 | 07-JUL-20:08 | 0.00 | 01-JUL-00:05 | 18612.28 | 21-JUL-20:43 | 14248.28 | 07-JUL-22:03 | 6158.02 | 26-JUL-20:10 | 4305.91 | 09-JUL-18:10 | 0.00 | 01-JUL-00:05 |
August | 0.171454E+11 | 0.371540E+10 | 634.56 | 0.118382E+11 | 0.530724E+10 | 0.00 | 1.00 | 01-AUG-20:43 | 0.00 | 01-AUG-00:10 | 19127.35 | 03-AUG-20:10 | 14367.26 | 18-AUG-22:43 | 6541.47 | 08-AUG-20:10 | 4277.77 | 06-AUG-18:10 | 0.00 | 01-AUG-00:05 |
September | 0.104877E+11 | 0.224131E+10 | 489.69 | 0.754358E+10 | 0.294410E+10 | 0.00 | 1.00 | 07-SEP-20:10 | 0.00 | 01-SEP-00:05 | 19528.57 | 21-SEP-20:21 | 14910.84 | 14-SEP-20:11 | 10042.16 | 21-SEP-21:25 | 4016.50 | 07-SEP-20:10 | 0.00 | 01-SEP-00:05 |
October | 0.417613E+10 | 0.882581E+09 | 260.42 | 0.314660E+10 | 0.102953E+10 | 0.00 | 1.00 | 02-OCT-21:40 | 0.00 | 01-OCT-00:10 | 18938.79 | 16-OCT-23:45 | 16218.61 | 11-OCT-20:10 | 8501.09 | 19-OCT-20:42 | 3708.95 | 16-OCT-23:45 | 0.00 | 01-OCT-00:10 |
November | 0.852719E+09 | 0.190000E+09 | 130.88 | 0.693174E+09 | 0.159545E+09 | 0.00 | 1.00 | 02-NOV-20:33 | 0.00 | 01-NOV-00:10 | 18426.12 | 02-NOV-20:33 | 17054.23 | 08-NOV-21:33 | 6769.39 | 02-NOV-20:33 | 3619.88 | 02-NOV-20:33 | 0.00 | 01-NOV-00:10 |
December | 0.129389E+09 | 28976275.21 | 34.99 | 91935328.91 | 37453185.03 | 0.00 | 0.63 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5835.88 | 12-DEC-14:00 | 4140.75 | 12-DEC-14:00 | 1695.13 | 12-DEC-14:00 | 1239.12 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.706825E+11 | 0.153996E+11 | 3499.12 | 0.511738E+11 | 0.195087E+11 | 0.00 | ||||||||||||||
Minimum of Months | 781527.40 | 191964.13 | 8.64 | 698864.53 | 82662.86 | 0.00 | 0.04 | 0.00 | 287.14 | 260.59 | 16.77 | 70.36 | 0.00 | |||||||
Maximum of Months | 0.171454E+11 | 0.371540E+10 | 634.56 | 0.118382E+11 | 0.530724E+10 | 0.00 | 1.00 | 0.00 | 19528.57 | 17363.00 | 10398.89 | 4305.91 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.76 | 18.23 | 15.53 | 17.98 | 57.53 | 0.00 | 0.00 | 744.00 |
February | 42.98 | 26.46 | 16.52 | 33.81 | 49.89 | 0.00 | 0.00 | 672.00 |
March | 63.41 | 38.90 | 24.52 | 62.72 | 36.04 | 0.00 | 0.00 | 744.00 |
April | 80.38 | 49.99 | 30.39 | 90.88 | 30.16 | 0.00 | 0.00 | 720.00 |
May | 89.28 | 51.89 | 37.39 | 106.81 | 21.17 | 0.00 | 0.00 | 744.00 |
June | 95.40 | 56.58 | 38.82 | 120.67 | 15.89 | 0.00 | 0.00 | 720.00 |
July | 88.67 | 50.46 | 38.21 | 113.93 | 12.11 | 0.00 | 0.00 | 744.00 |
August | 81.42 | 44.74 | 36.68 | 105.13 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 60.60 | 33.92 | 26.68 | 70.63 | 19.97 | 0.00 | 0.00 | 720.00 |
October | 51.55 | 34.66 | 16.89 | 51.60 | 34.73 | 0.00 | 0.00 | 744.00 |
November | 37.65 | 21.01 | 16.63 | 28.91 | 44.12 | 0.00 | 0.00 | 720.00 |
December | 30.32 | 16.04 | 14.28 | 16.34 | 51.26 | 2.83 | 0.00 | 744.00 |
Annual Sum or Average | 63.05 | 36.95 | 26.10 | 68.46 | 31.93 | 2.83 | 0.00 | 8760.00 |
Minimum of Months | 30.32 | 16.04 | 14.28 | 16.34 | 11.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.40 | 56.58 | 38.82 | 120.67 | 57.53 | 2.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 866.15 | 603.94 | 262.21 | 980.76 | 925.61 | 0.00 | 0.00 | 744.00 |
February | 808.40 | 541.95 | 266.45 | 965.56 | 801.80 | 0.00 | 0.00 | 672.00 |
March | 726.74 | 378.67 | 348.06 | 872.62 | 567.01 | 0.00 | 0.00 | 744.00 |
April | 544.19 | 177.02 | 367.17 | 665.13 | 459.62 | 0.00 | 0.00 | 720.00 |
May | 439.66 | 50.95 | 388.71 | 581.59 | 297.44 | 0.00 | 0.00 | 744.00 |
June | 406.50 | 22.47 | 384.04 | 681.35 | 178.48 | 0.00 | 0.00 | 720.00 |
July | 410.98 | 30.50 | 380.48 | 728.01 | 117.15 | 0.00 | 0.00 | 744.00 |
August | 490.71 | 91.54 | 399.17 | 857.58 | 96.09 | 0.00 | 0.00 | 744.00 |
September | 539.68 | 200.64 | 339.04 | 804.67 | 248.42 | 0.00 | 0.00 | 720.00 |
October | 782.65 | 507.02 | 275.63 | 1074.64 | 540.06 | 0.00 | 0.00 | 744.00 |
November | 842.16 | 558.92 | 283.24 | 1086.29 | 694.96 | 0.00 | 0.00 | 720.00 |
December | 853.76 | 600.68 | 253.08 | 1030.42 | 812.66 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 641.92 | 312.63 | 329.30 | 860.42 | 476.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 406.50 | 22.47 | 253.08 | 581.59 | 96.09 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 866.15 | 603.94 | 399.17 | 1086.29 | 925.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 866.15 | 603.94 | 262.21 | 986.99 | 902.69 | 0.00 | 0.00 | 744.00 |
February | 808.40 | 541.95 | 266.45 | 969.97 | 776.49 | 0.00 | 0.00 | 672.00 |
March | 726.74 | 378.67 | 348.06 | 878.50 | 542.67 | 0.00 | 0.00 | 744.00 |
April | 544.19 | 177.02 | 367.17 | 667.09 | 442.54 | 0.00 | 0.00 | 720.00 |
May | 439.66 | 50.95 | 388.71 | 579.04 | 290.07 | 0.00 | 0.00 | 744.00 |
June | 406.50 | 22.47 | 384.04 | 675.67 | 175.92 | 0.00 | 0.00 | 720.00 |
July | 410.98 | 30.50 | 380.48 | 722.49 | 115.03 | 0.00 | 0.00 | 744.00 |
August | 490.71 | 91.54 | 399.17 | 851.72 | 93.46 | 0.00 | 0.00 | 744.00 |
September | 539.68 | 200.64 | 339.04 | 800.06 | 245.63 | 0.00 | 0.00 | 720.00 |
October | 782.65 | 507.02 | 275.63 | 1073.94 | 527.25 | 0.00 | 0.00 | 744.00 |
November | 842.16 | 558.92 | 283.24 | 1090.86 | 671.38 | 0.00 | 0.00 | 720.00 |
December | 853.76 | 600.68 | 253.08 | 1037.68 | 782.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 641.92 | 312.63 | 329.30 | 860.85 | 462.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 406.50 | 22.47 | 253.08 | 579.04 | 93.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 866.15 | 603.94 | 399.17 | 1090.86 | 902.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 178.22 | 124.27 | 53.95 | 215.68 | 159.86 | 0.00 | 0.00 | 744.00 |
February | 166.34 | 111.51 | 54.83 | 208.92 | 138.70 | 0.00 | 0.00 | 672.00 |
March | 149.54 | 77.92 | 71.62 | 193.18 | 97.60 | 0.00 | 0.00 | 744.00 |
April | 111.97 | 36.42 | 75.55 | 140.88 | 84.00 | 0.00 | 0.00 | 720.00 |
May | 90.47 | 10.48 | 79.98 | 114.49 | 58.56 | 0.00 | 0.00 | 744.00 |
June | 83.64 | 4.62 | 79.02 | 118.97 | 42.01 | 0.00 | 0.00 | 720.00 |
July | 84.56 | 6.28 | 78.29 | 124.41 | 31.17 | 0.00 | 0.00 | 744.00 |
August | 100.97 | 18.84 | 82.13 | 149.35 | 29.12 | 0.00 | 0.00 | 744.00 |
September | 111.05 | 41.28 | 69.76 | 154.09 | 54.73 | 0.00 | 0.00 | 720.00 |
October | 161.04 | 104.33 | 56.72 | 224.76 | 98.81 | 0.00 | 0.00 | 744.00 |
November | 173.29 | 115.01 | 58.28 | 234.91 | 120.60 | 0.00 | 0.00 | 720.00 |
December | 175.67 | 123.60 | 52.08 | 228.41 | 134.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 132.08 | 64.33 | 67.76 | 175.55 | 87.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 83.64 | 4.62 | 52.08 | 114.49 | 29.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 178.22 | 124.27 | 82.13 | 234.91 | 159.86 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90428333.37 | 48837535.16 | 41590798.21 | 48164977.93 | 0.154081E+09 |
February | 0.103982E+09 | 64022430.99 | 39959425.10 | 81793906.34 | 0.120689E+09 |
March | 0.169840E+09 | 0.104177E+09 | 65663058.20 | 0.167977E+09 | 96532041.75 |
April | 0.208339E+09 | 0.129576E+09 | 78762382.82 | 0.235564E+09 | 78164006.87 |
May | 0.239116E+09 | 0.138974E+09 | 0.100141E+09 | 0.286076E+09 | 56691908.65 |
June | 0.247266E+09 | 0.146652E+09 | 0.100614E+09 | 0.312765E+09 | 41198417.04 |
July | 0.237489E+09 | 0.135141E+09 | 0.102348E+09 | 0.305163E+09 | 32435592.18 |
August | 0.218086E+09 | 0.119838E+09 | 98247308.71 | 0.281585E+09 | 30757871.68 |
September | 0.157071E+09 | 87909236.62 | 69161955.38 | 0.183069E+09 | 51749470.83 |
October | 0.138069E+09 | 92828517.92 | 45240863.80 | 0.138210E+09 | 93017976.15 |
November | 97583683.81 | 54466167.25 | 43117516.56 | 74937841.99 | 0.114350E+09 |
December | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 0.137292E+09 |
Annual Sum or Average | 0.198847E+10 | 0.116537E+10 | 0.823093E+09 | 0.215907E+10 | 0.100696E+10 |
Minimum of Months | 81197549.75 | 42950743.90 | 38246805.85 | 43763847.92 | 30757871.68 |
Maximum of Months | 0.247266E+09 | 0.146652E+09 | 0.102348E+09 | 0.312765E+09 | 0.154081E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.262686E+10 | 0.247916E+10 |
February | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.233587E+10 | 0.193971E+10 |
March | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.233721E+10 | 0.151868E+10 |
April | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.172402E+10 | 0.119134E+10 |
May | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.155772E+10 | 0.796657E+09 |
June | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.176606E+10 | 0.462612E+09 |
July | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.194989E+10 | 0.313765E+09 |
August | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.229694E+10 | 0.257378E+09 |
September | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.208570E+10 | 0.643897E+09 |
October | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.287832E+10 | 0.144649E+10 |
November | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.281566E+10 | 0.180134E+10 |
December | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.275989E+10 | 0.217664E+10 |
Annual Sum or Average | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.271342E+11 | 0.150277E+11 |
Minimum of Months | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.155772E+10 | 0.257378E+09 |
Maximum of Months | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.287832E+10 | 0.247916E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.264355E+10 | 0.241777E+10 |
February | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.234654E+10 | 0.187848E+10 |
March | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.235296E+10 | 0.145349E+10 |
April | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.172910E+10 | 0.114707E+10 |
May | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.155091E+10 | 0.776927E+09 |
June | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.175134E+10 | 0.455984E+09 |
July | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.193512E+10 | 0.308096E+09 |
August | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.228126E+10 | 0.250323E+09 |
September | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.207376E+10 | 0.636662E+09 |
October | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.287645E+10 | 0.141219E+10 |
November | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.282751E+10 | 0.174021E+10 |
December | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.277933E+10 | 0.209505E+10 |
Annual Sum or Average | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.271478E+11 | 0.145722E+11 |
Minimum of Months | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.155091E+10 | 0.250323E+09 |
Maximum of Months | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.287645E+10 | 0.241777E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.477354E+09 | 0.332844E+09 | 0.144510E+09 | 0.577682E+09 | 0.428181E+09 |
February | 0.402408E+09 | 0.269774E+09 | 0.132634E+09 | 0.505423E+09 | 0.335533E+09 |
March | 0.400520E+09 | 0.208695E+09 | 0.191825E+09 | 0.517422E+09 | 0.261417E+09 |
April | 0.290238E+09 | 94412838.34 | 0.195825E+09 | 0.365159E+09 | 0.217731E+09 |
May | 0.242305E+09 | 28079908.65 | 0.214225E+09 | 0.306662E+09 | 0.156851E+09 |
June | 0.216806E+09 | 11981890.80 | 0.204824E+09 | 0.308370E+09 | 0.108893E+09 |
July | 0.226499E+09 | 16810004.70 | 0.209689E+09 | 0.333224E+09 | 83472863.89 |
August | 0.270442E+09 | 50451868.80 | 0.219990E+09 | 0.400022E+09 | 77996183.31 |
September | 0.287834E+09 | 0.107009E+09 | 0.180825E+09 | 0.399398E+09 | 0.141869E+09 |
October | 0.431332E+09 | 0.279427E+09 | 0.151906E+09 | 0.601995E+09 | 0.264651E+09 |
November | 0.449158E+09 | 0.298093E+09 | 0.151064E+09 | 0.608880E+09 | 0.312606E+09 |
December | 0.470522E+09 | 0.331044E+09 | 0.139478E+09 | 0.611777E+09 | 0.361118E+09 |
Annual Sum or Average | 0.416542E+10 | 0.202862E+10 | 0.213680E+10 | 0.553601E+10 | 0.275032E+10 |
Minimum of Months | 0.216806E+09 | 11981890.80 | 0.132634E+09 | 0.306662E+09 | 77996183.31 |
Maximum of Months | 0.477354E+09 | 0.332844E+09 | 0.219990E+09 | 0.611777E+09 | 0.428181E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 287.72 | 920.44 | 540.19 | 291.74 | 248.45 | 0.00 | 0.00 |
February | 540.96 | 798.21 | 687.71 | 423.43 | 264.28 | 0.00 | 0.00 |
March | 1003.45 | 576.65 | 1014.57 | 622.32 | 392.25 | 0.00 | 0.00 |
April | 1454.10 | 482.49 | 1286.04 | 799.85 | 486.19 | 0.00 | 0.00 |
May | 1708.94 | 338.66 | 1428.41 | 830.19 | 598.21 | 0.00 | 0.00 |
June | 1930.65 | 254.31 | 1526.33 | 905.26 | 621.07 | 0.00 | 0.00 |
July | 1822.96 | 193.76 | 1418.69 | 807.29 | 611.40 | 0.00 | 0.00 |
August | 1682.11 | 183.74 | 1302.78 | 715.88 | 586.90 | 0.00 | 0.00 |
September | 1130.06 | 319.44 | 969.58 | 542.65 | 426.93 | 0.00 | 0.00 |
October | 825.63 | 555.66 | 824.79 | 554.53 | 270.26 | 0.00 | 0.00 |
November | 462.58 | 705.86 | 602.37 | 336.21 | 266.16 | 0.00 | 0.00 |
December | 261.43 | 820.14 | 485.05 | 256.58 | 228.48 | 0.00 | 0.00 |
Annual Sum or Average | 1095.42 | 510.89 | 1008.86 | 591.26 | 417.60 | 0.00 | 0.00 |
Minimum of Months | 261.43 | 183.74 | 485.05 | 256.58 | 228.48 | 0.00 | 0.00 |
Maximum of Months | 1930.65 | 920.44 | 1526.33 | 905.26 | 621.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 980.76 | 925.61 | 866.15 | 603.94 | 262.21 | 0.00 | 0.00 |
February | 965.56 | 801.80 | 808.40 | 541.95 | 266.45 | 0.00 | 0.00 |
March | 872.62 | 567.01 | 726.74 | 378.67 | 348.06 | 0.00 | 0.00 |
April | 665.13 | 459.62 | 544.19 | 177.02 | 367.17 | 0.00 | 0.00 |
May | 581.59 | 297.44 | 439.66 | 50.95 | 388.71 | 0.00 | 0.00 |
June | 681.35 | 178.48 | 406.50 | 22.47 | 384.04 | 0.00 | 0.00 |
July | 728.01 | 117.15 | 410.98 | 30.50 | 380.48 | 0.00 | 0.00 |
August | 857.58 | 96.09 | 490.71 | 91.54 | 399.17 | 0.00 | 0.00 |
September | 804.67 | 248.42 | 539.68 | 200.64 | 339.04 | 0.00 | 0.00 |
October | 1074.64 | 540.06 | 782.65 | 507.02 | 275.63 | 0.00 | 0.00 |
November | 1086.29 | 694.96 | 842.16 | 558.92 | 283.24 | 0.00 | 0.00 |
December | 1030.42 | 812.66 | 853.76 | 600.68 | 253.08 | 0.00 | 0.00 |
Annual Sum or Average | 860.42 | 476.52 | 641.92 | 312.63 | 329.30 | 0.00 | 0.00 |
Minimum of Months | 581.59 | 96.09 | 406.50 | 22.47 | 253.08 | 0.00 | 0.00 |
Maximum of Months | 1086.29 | 925.61 | 866.15 | 603.94 | 399.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 986.99 | 902.69 | 866.15 | 603.94 | 262.21 | 0.00 | 0.00 |
February | 969.97 | 776.49 | 808.40 | 541.95 | 266.45 | 0.00 | 0.00 |
March | 878.50 | 542.67 | 726.74 | 378.67 | 348.06 | 0.00 | 0.00 |
April | 667.09 | 442.54 | 544.19 | 177.02 | 367.17 | 0.00 | 0.00 |
May | 579.04 | 290.07 | 439.66 | 50.95 | 388.71 | 0.00 | 0.00 |
June | 675.67 | 175.92 | 406.50 | 22.47 | 384.04 | 0.00 | 0.00 |
July | 722.49 | 115.03 | 410.98 | 30.50 | 380.48 | 0.00 | 0.00 |
August | 851.72 | 93.46 | 490.71 | 91.54 | 399.17 | 0.00 | 0.00 |
September | 800.06 | 245.63 | 539.68 | 200.64 | 339.04 | 0.00 | 0.00 |
October | 1073.94 | 527.25 | 782.65 | 507.02 | 275.63 | 0.00 | 0.00 |
November | 1090.86 | 671.38 | 842.16 | 558.92 | 283.24 | 0.00 | 0.00 |
December | 1037.68 | 782.20 | 853.76 | 600.68 | 253.08 | 0.00 | 0.00 |
Annual Sum or Average | 860.85 | 462.08 | 641.92 | 312.63 | 329.30 | 0.00 | 0.00 |
Minimum of Months | 579.04 | 93.46 | 406.50 | 22.47 | 253.08 | 0.00 | 0.00 |
Maximum of Months | 1090.86 | 902.69 | 866.15 | 603.94 | 399.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 215.68 | 159.86 | 178.22 | 124.27 | 53.95 | 0.00 | 0.00 |
February | 208.92 | 138.70 | 166.34 | 111.51 | 54.83 | 0.00 | 0.00 |
March | 193.18 | 97.60 | 149.54 | 77.92 | 71.62 | 0.00 | 0.00 |
April | 140.88 | 84.00 | 111.97 | 36.42 | 75.55 | 0.00 | 0.00 |
May | 114.49 | 58.56 | 90.47 | 10.48 | 79.98 | 0.00 | 0.00 |
June | 118.97 | 42.01 | 83.64 | 4.62 | 79.02 | 0.00 | 0.00 |
July | 124.41 | 31.17 | 84.56 | 6.28 | 78.29 | 0.00 | 0.00 |
August | 149.35 | 29.12 | 100.97 | 18.84 | 82.13 | 0.00 | 0.00 |
September | 154.09 | 54.73 | 111.05 | 41.28 | 69.76 | 0.00 | 0.00 |
October | 224.76 | 98.81 | 161.04 | 104.33 | 56.72 | 0.00 | 0.00 |
November | 234.91 | 120.60 | 173.29 | 115.01 | 58.28 | 0.00 | 0.00 |
December | 228.41 | 134.83 | 175.67 | 123.60 | 52.08 | 0.00 | 0.00 |
Annual Sum or Average | 175.55 | 87.21 | 132.08 | 64.33 | 67.76 | 0.00 | 0.00 |
Minimum of Months | 114.49 | 29.12 | 83.64 | 4.62 | 52.08 | 0.00 | 0.00 |
Maximum of Months | 234.91 | 159.86 | 178.22 | 124.27 | 82.13 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.770640E+09 | 0.246529E+10 | 0.144685E+10 | 0.781401E+09 | 0.665453E+09 | 0.00 | 0.00 |
February | 0.130870E+10 | 0.193102E+10 | 0.166371E+10 | 0.102436E+10 | 0.639351E+09 | 0.00 | 0.00 |
March | 0.268763E+10 | 0.154451E+10 | 0.271743E+10 | 0.166683E+10 | 0.105061E+10 | 0.00 | 0.00 |
April | 0.376902E+10 | 0.125062E+10 | 0.333342E+10 | 0.207322E+10 | 0.126020E+10 | 0.00 | 0.00 |
May | 0.457722E+10 | 0.907071E+09 | 0.382585E+10 | 0.222359E+10 | 0.160226E+10 | 0.00 | 0.00 |
June | 0.500424E+10 | 0.659175E+09 | 0.395626E+10 | 0.234643E+10 | 0.160982E+10 | 0.00 | 0.00 |
July | 0.488261E+10 | 0.518969E+09 | 0.379982E+10 | 0.216225E+10 | 0.163757E+10 | 0.00 | 0.00 |
August | 0.450535E+10 | 0.492126E+09 | 0.348937E+10 | 0.191741E+10 | 0.157196E+10 | 0.00 | 0.00 |
September | 0.292911E+10 | 0.827992E+09 | 0.251314E+10 | 0.140655E+10 | 0.110659E+10 | 0.00 | 0.00 |
October | 0.221136E+10 | 0.148829E+10 | 0.220911E+10 | 0.148526E+10 | 0.723854E+09 | 0.00 | 0.00 |
November | 0.119901E+10 | 0.182960E+10 | 0.156134E+10 | 0.871459E+09 | 0.689880E+09 | 0.00 | 0.00 |
December | 0.700222E+09 | 0.219667E+10 | 0.129916E+10 | 0.687212E+09 | 0.611949E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.345451E+11 | 0.161113E+11 | 0.318155E+11 | 0.186460E+11 | 0.131695E+11 | 0.00 | 0.00 |
Minimum of Months | 0.700222E+09 | 0.492126E+09 | 0.129916E+10 | 0.687212E+09 | 0.611949E+09 | 0.00 | 0.00 |
Maximum of Months | 0.500424E+10 | 0.246529E+10 | 0.395626E+10 | 0.234643E+10 | 0.163757E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.262686E+10 | 0.247916E+10 | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.00 | 0.00 |
February | 0.233587E+10 | 0.193971E+10 | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.00 | 0.00 |
March | 0.233721E+10 | 0.151868E+10 | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.00 | 0.00 |
April | 0.172402E+10 | 0.119134E+10 | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.00 | 0.00 |
May | 0.155772E+10 | 0.796657E+09 | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.00 | 0.00 |
June | 0.176606E+10 | 0.462612E+09 | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.00 | 0.00 |
July | 0.194989E+10 | 0.313765E+09 | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.00 | 0.00 |
August | 0.229694E+10 | 0.257378E+09 | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.00 | 0.00 |
September | 0.208570E+10 | 0.643897E+09 | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.00 | 0.00 |
October | 0.287832E+10 | 0.144649E+10 | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.00 | 0.00 |
November | 0.281566E+10 | 0.180134E+10 | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.00 | 0.00 |
December | 0.275989E+10 | 0.217664E+10 | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.271342E+11 | 0.150277E+11 | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.00 | 0.00 |
Minimum of Months | 0.155772E+10 | 0.257378E+09 | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.287832E+10 | 0.247916E+10 | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.264355E+10 | 0.241777E+10 | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.00 | 0.00 |
February | 0.234654E+10 | 0.187848E+10 | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.00 | 0.00 |
March | 0.235296E+10 | 0.145349E+10 | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.00 | 0.00 |
April | 0.172910E+10 | 0.114707E+10 | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.00 | 0.00 |
May | 0.155091E+10 | 0.776927E+09 | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.00 | 0.00 |
June | 0.175134E+10 | 0.455984E+09 | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.00 | 0.00 |
July | 0.193512E+10 | 0.308096E+09 | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.00 | 0.00 |
August | 0.228126E+10 | 0.250323E+09 | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.00 | 0.00 |
September | 0.207376E+10 | 0.636662E+09 | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.00 | 0.00 |
October | 0.287645E+10 | 0.141219E+10 | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.00 | 0.00 |
November | 0.282751E+10 | 0.174021E+10 | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.00 | 0.00 |
December | 0.277933E+10 | 0.209505E+10 | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.271478E+11 | 0.145722E+11 | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.00 | 0.00 |
Minimum of Months | 0.155091E+10 | 0.250323E+09 | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.287645E+10 | 0.241777E+10 | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.577682E+09 | 0.428181E+09 | 0.477354E+09 | 0.332844E+09 | 0.144510E+09 | 0.00 | 0.00 |
February | 0.505423E+09 | 0.335533E+09 | 0.402408E+09 | 0.269774E+09 | 0.132634E+09 | 0.00 | 0.00 |
March | 0.517422E+09 | 0.261417E+09 | 0.400520E+09 | 0.208695E+09 | 0.191825E+09 | 0.00 | 0.00 |
April | 0.365159E+09 | 0.217731E+09 | 0.290238E+09 | 94412838.34 | 0.195825E+09 | 0.00 | 0.00 |
May | 0.306662E+09 | 0.156851E+09 | 0.242305E+09 | 28079908.65 | 0.214225E+09 | 0.00 | 0.00 |
June | 0.308370E+09 | 0.108893E+09 | 0.216806E+09 | 11981890.80 | 0.204824E+09 | 0.00 | 0.00 |
July | 0.333224E+09 | 83472863.89 | 0.226499E+09 | 16810004.70 | 0.209689E+09 | 0.00 | 0.00 |
August | 0.400022E+09 | 77996183.31 | 0.270442E+09 | 50451868.80 | 0.219990E+09 | 0.00 | 0.00 |
September | 0.399398E+09 | 0.141869E+09 | 0.287834E+09 | 0.107009E+09 | 0.180825E+09 | 0.00 | 0.00 |
October | 0.601995E+09 | 0.264651E+09 | 0.431332E+09 | 0.279427E+09 | 0.151906E+09 | 0.00 | 0.00 |
November | 0.608880E+09 | 0.312606E+09 | 0.449158E+09 | 0.298093E+09 | 0.151064E+09 | 0.00 | 0.00 |
December | 0.611777E+09 | 0.361118E+09 | 0.470522E+09 | 0.331044E+09 | 0.139478E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.553601E+10 | 0.275032E+10 | 0.416542E+10 | 0.202862E+10 | 0.213680E+10 | 0.00 | 0.00 |
Minimum of Months | 0.306662E+09 | 77996183.31 | 0.216806E+09 | 11981890.80 | 0.132634E+09 | 0.00 | 0.00 |
Maximum of Months | 0.611777E+09 | 0.428181E+09 | 0.477354E+09 | 0.332844E+09 | 0.219990E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.45 | -3.0 | 4.56 | -7.9 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.23 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.96 | 3.80 | 4.89 | 2.24 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.53 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.43 | 13.69 | 3.50 | 11.45 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.34 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.67 | 19.85 | 3.24 | 17.63 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.41 | 20.72 | 3.39 | 18.20 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.43 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.01 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.21 | 4.17 | 4.16 | 0.29 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.67 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.28 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.45 | -3.0 | 3.06 | -7.9 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.41 | 20.72 | 5.19 | 18.20 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.95 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.72 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.85 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.53 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.47 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.37 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.89 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.82 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.04 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.54 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.94 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.76 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.72 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.89 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.7 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.7 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.4 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.0 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.44 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.1 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.7 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.80 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.15 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.00 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.33 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.31 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.05 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.12 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.09 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.19 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.87 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.80 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.12 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.80 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.78 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.09 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.88 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.80 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.257093E+10 | -.214399E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -426938715.0 | 58.99 | 0.00 | 0.00 |
February | 0.233441E+10 | -.195627E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -378139298.8 | 59.00 | 0.00 | 0.00 |
March | 0.254822E+10 | -.214514E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -403081809.3 | 58.99 | 0.00 | 0.00 |
April | 0.228907E+10 | -.190920E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -379866280.9 | 58.99 | 0.00 | 0.00 |
May | 0.220272E+10 | -.181625E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -386467162.8 | 58.99 | 0.00 | 0.00 |
June | 0.201399E+10 | -.164085E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373136957.1 | 58.99 | 0.00 | 0.00 |
July | 0.194657E+10 | -.156098E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385591828.6 | 58.99 | 0.00 | 0.00 |
August | 0.199094E+10 | -.160534E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385606680.5 | 58.99 | 0.00 | 0.00 |
September | 0.197389E+10 | -.160075E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373142684.2 | 58.99 | 0.00 | 0.00 |
October | 0.215520E+10 | -.176387E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -391330920.2 | 58.99 | 0.00 | 0.00 |
November | 0.224147E+10 | -.185070E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -390763132.8 | 58.99 | 0.00 | 0.00 |
December | 0.248154E+10 | -.206167E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -419875192.0 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.267490E+11 | -.220550E+11 | 8760.00 | -.469394E+10 | 58.99 | |||||
Minimum of Months | 0.194657E+10 | -.214514E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -426938715.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.257093E+10 | -.156098E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -373136957.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.94 | 0.67 | 08-JAN-11:39 | 167.14 | 4.01 | 0.00 | 0.00 | 138.36 | 2.83 | 0.00 | 0.00 |
February | 263.00 | 0.92 | 0.67 | 09-FEB-13:30 | 181.14 | 3.99 | 0.00 | 0.00 | 148.39 | 2.74 | 0.00 | 0.00 |
March | 351.67 | 0.87 | 0.50 | 22-MAR-12:30 | 244.69 | 5.76 | 0.00 | 4.33 | 202.79 | 4.24 | 0.00 | 2.33 |
April | 369.33 | 0.81 | 0.50 | 01-APR-11:39 | 1707.62 | 7.00 | 0.00 | 69.17 | 1791.68 | 5.37 | 0.00 | 56.83 |
May | 407.00 | 0.82 | 0.50 | 01-MAY-11:20 | 304.34 | 8.82 | 0.00 | 40.67 | 256.37 | 7.08 | 0.00 | 28.17 |
June | 411.67 | 0.82 | 0.50 | 01-JUN-11:09 | 302.46 | 9.31 | 0.00 | 38.33 | 254.12 | 7.54 | 0.00 | 26.17 |
July | 411.00 | 0.82 | 0.50 | 01-JUL-12:09 | 309.98 | 9.23 | 0.00 | 40.50 | 260.59 | 7.53 | 0.00 | 27.17 |
August | 390.50 | 0.80 | 0.50 | 05-AUG-13:30 | 403.21 | 8.81 | 0.00 | 62.33 | 302.09 | 7.07 | 0.00 | 36.83 |
September | 298.50 | 0.79 | 0.50 | 01-SEP-11:09 | 2014.71 | 6.69 | 0.00 | 87.50 | 1440.64 | 5.06 | 0.00 | 45.50 |
October | 293.50 | 0.91 | 0.50 | 02-OCT-11:50 | 194.44 | 3.96 | 0.00 | 2.33 | 169.41 | 2.79 | 0.00 | 2.33 |
November | 299.00 | 0.90 | 0.67 | 01-NOV-09:39 | 196.41 | 4.30 | 0.00 | 2.00 | 355.47 | 2.97 | 0.00 | 28.33 |
December | 285.17 | 0.92 | 0.67 | 03-DEC-13:09 | 817.40 | 3.85 | 0.00 | 37.33 | 129.43 | 2.63 | 0.00 | 0.00 |
Annual Sum or Average | 4071.00 | 0.85 | 564.11 | 6.64 | 0.00 | 384.50 | 459.16 | 5.12 | 0.00 | 253.67 | ||
Minimum of Months | 263.00 | 0.79 | 0.50 | 167.14 | 3.85 | 0.00 | 0.00 | 129.43 | 2.63 | 0.00 | 0.00 | |
Maximum of Months | 411.67 | 0.94 | 0.67 | 2014.71 | 9.31 | 0.00 | 87.50 | 1791.68 | 7.54 | 0.00 | 56.83 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100787E+11 | 50308.85 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.574835E+10 | 50308.85 | 01-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728241E+09 | 50308.85 | 18-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103692E+09 | 26108.19 | 07-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33770441.11 | 9976.80 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.846482E+09 | 50308.85 | 21-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.444322E+10 | 50308.85 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219824E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100787E+11 | 50308.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.346624E+11 | 218316.02 | 08-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184198E+11 | 218316.02 | 12-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200360E+10 | 36798.44 | 19-MAR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.278247E+09 | 31224.16 | 07-APR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231537E+09 | 31513.70 | 26-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.337925E+10 | 61925.91 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155225E+11 | 211438.68 | 04-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.744973E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.346624E+11 | 218316.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.306427E+10 | 29879.99 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177081E+10 | 29879.99 | 02-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197258E+09 | 29879.99 | 23-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53792211.12 | 8356.71 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21353531.89 | 2967.45 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162717E+09 | 29879.99 | 21-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111669E+10 | 29879.99 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.638689E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.306427E+10 | 29879.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.459169E+10 | 24065.59 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.273915E+10 | 24065.59 | 01-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.469720E+09 | 24065.59 | 18-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120845E+09 | 22190.53 | 06-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73138326.46 | 14620.30 | 31-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.386873E+09 | 24065.59 | 21-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195940E+10 | 24065.59 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103408E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.459169E+10 | 24065.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.535528E+10 | 29061.37 | 02-JAN-17:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311031E+10 | 26699.60 | 08-FEB-17:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.253052E+09 | 11672.01 | 22-MAR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 240661.32 | 230.52 | 26-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 392204.76 | 935.06 | 26-OCT-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.496905E+09 | 25750.71 | 21-NOV-16:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147617E+10 | 15757.98 | 17-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106923E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.535528E+10 | 29061.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.126593E+09 | 0.126593E+09 | 5458.04 | 28-FEB-15:10 | 5458.04 | 0.00 |
March | 0.00 | 0.00 | 0.116085E+10 | 0.906503E+09 | 37690.09 | 30-MAR-21:50 | 29225.79 | 0.00 |
April | 0.00 | 0.00 | 0.433427E+10 | 0.356594E+10 | 37045.21 | 18-APR-20:41 | 27056.94 | 0.00 |
May | 0.00 | 0.00 | 0.113228E+11 | 0.845018E+10 | 38626.98 | 03-MAY-20:21 | 23677.71 | 0.00 |
June | 0.00 | 0.00 | 0.219516E+11 | 0.163762E+11 | 37676.54 | 06-JUN-00:20 | 24962.30 | 0.00 |
July | 0.00 | 0.00 | 0.264721E+11 | 0.189039E+11 | 39317.22 | 28-JUL-20:30 | 17805.60 | 0.00 |
August | 0.00 | 0.00 | 0.287555E+11 | 0.201695E+11 | 38277.17 | 03-AUG-20:43 | 28847.74 | 0.00 |
September | 0.00 | 0.00 | 0.167095E+11 | 0.119380E+11 | 39156.03 | 21-SEP-20:27 | 27808.88 | 0.00 |
October | 0.00 | 0.00 | 0.478787E+10 | 0.338247E+10 | 30758.49 | 19-OCT-20:42 | 17292.17 | 0.00 |
November | 0.00 | 0.00 | 0.467105E+09 | 0.325108E+09 | 7823.66 | 05-NOV-15:00 | 5285.08 | 0.00 |
December | 0.00 | 0.00 | 24275496.44 | 17420356.39 | 2443.89 | 12-DEC-15:10 | 1836.62 | 0.00 |
Annual Sum or Average | 0.116113E+12 | 0.841617E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.287555E+11 | 0.201695E+11 | 39317.22 | 29225.79 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6688339.33 | 5507927.08 | 2913.85 | 31-JAN-15:10 | 2418.34 | 0.00 |
February | 0.00 | 0.00 | 0.161480E+10 | 0.158561E+10 | 30788.33 | 28-FEB-15:10 | 29828.71 | 0.00 |
March | 0.00 | 0.00 | 0.911670E+10 | 0.683956E+10 | 178212.01 | 31-MAR-06:03 | 103825.49 | 0.00 |
April | 0.00 | 0.00 | 0.281703E+11 | 0.220203E+11 | 182566.68 | 23-APR-08:62 | 91620.00 | 0.00 |
May | 0.00 | 0.00 | 0.606874E+11 | 0.427110E+11 | 186393.05 | 31-MAY-06:02 | 93936.67 | 0.00 |
June | 0.00 | 0.00 | 0.987132E+11 | 0.668251E+11 | 189091.57 | 18-JUN-08:62 | 110950.13 | 0.00 |
July | 0.00 | 0.00 | 0.116974E+12 | 0.732562E+11 | 193956.78 | 30-JUL-08:62 | 99701.61 | 0.00 |
August | 0.00 | 0.00 | 0.125334E+12 | 0.763611E+11 | 192783.66 | 20-AUG-08:62 | 106094.95 | 0.00 |
September | 0.00 | 0.00 | 0.749777E+11 | 0.474468E+11 | 194067.97 | 17-SEP-08:62 | 101403.42 | 0.00 |
October | 0.00 | 0.00 | 0.263027E+11 | 0.176120E+11 | 190637.35 | 19-OCT-06:02 | 84333.68 | 0.00 |
November | 0.00 | 0.00 | 0.456217E+10 | 0.323341E+10 | 122210.71 | 04-NOV-06:03 | 66449.18 | 0.00 |
December | 0.00 | 0.00 | 0.502009E+09 | 0.324253E+09 | 22982.09 | 12-DEC-15:10 | 16278.10 | 0.00 |
Annual Sum or Average | 0.546962E+12 | 0.358221E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 6688339.33 | 5507927.08 | 2913.85 | 2418.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125334E+12 | 0.763611E+11 | 194067.97 | 110950.13 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 32029493.02 | 26659572.41 | 2416.59 | 31-JAN-15:10 | 2137.17 | 0.00 |
February | 0.00 | 0.00 | 0.696968E+09 | 0.693284E+09 | 21420.78 | 26-FEB-19:20 | 21420.78 | 0.00 |
March | 0.00 | 0.00 | 0.218032E+10 | 0.177180E+10 | 22608.29 | 31-MAR-00:10 | 16515.43 | 0.00 |
April | 0.00 | 0.00 | 0.479633E+10 | 0.395827E+10 | 23650.16 | 30-APR-18:45 | 12732.27 | 0.00 |
May | 0.00 | 0.00 | 0.924712E+10 | 0.703524E+10 | 23524.14 | 27-MAY-23:35 | 12713.59 | 0.00 |
June | 0.00 | 0.00 | 0.151669E+11 | 0.113494E+11 | 22795.89 | 06-JUN-01:30 | 14701.31 | 0.00 |
July | 0.00 | 0.00 | 0.182224E+11 | 0.130001E+11 | 22543.01 | 07-JUL-20:08 | 17753.10 | 0.00 |
August | 0.00 | 0.00 | 0.204837E+11 | 0.144948E+11 | 23326.33 | 03-AUG-20:43 | 18059.94 | 0.00 |
September | 0.00 | 0.00 | 0.135315E+11 | 0.991586E+10 | 23439.89 | 29-SEP-20:25 | 13599.04 | 0.00 |
October | 0.00 | 0.00 | 0.611712E+10 | 0.470703E+10 | 23123.27 | 19-OCT-20:12 | 13321.69 | 0.00 |
November | 0.00 | 0.00 | 0.203402E+10 | 0.166084E+10 | 23263.56 | 03-NOV-20:20 | 13661.13 | 0.00 |
December | 0.00 | 0.00 | 0.392998E+09 | 0.274428E+09 | 22631.83 | 12-DEC-21:20 | 15265.39 | 0.00 |
Annual Sum or Average | 0.929014E+11 | 0.688877E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 32029493.02 | 26659572.41 | 2416.59 | 2137.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.204837E+11 | 0.144948E+11 | 23650.16 | 21420.78 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 781527.40 | 698864.53 | 287.14 | 31-JAN-15:00 | 260.59 | 0.00 |
February | 0.00 | 0.00 | 0.361848E+09 | 0.361744E+09 | 17363.00 | 26-FEB-19:45 | 17363.00 | 0.00 |
March | 0.00 | 0.00 | 0.111540E+10 | 0.902498E+09 | 18559.28 | 30-MAR-23:01 | 13688.55 | 0.00 |
April | 0.00 | 0.00 | 0.294550E+10 | 0.245950E+10 | 18667.84 | 18-APR-20:20 | 13270.35 | 0.00 |
May | 0.00 | 0.00 | 0.628877E+10 | 0.474176E+10 | 19470.60 | 26-MAY-20:32 | 9071.71 | 0.00 |
June | 0.00 | 0.00 | 0.121744E+11 | 0.891727E+10 | 19036.07 | 07-JUN-01:05 | 10604.16 | 0.00 |
July | 0.00 | 0.00 | 0.150045E+11 | 0.104769E+11 | 18612.28 | 21-JUL-20:43 | 13783.16 | 0.00 |
August | 0.00 | 0.00 | 0.171454E+11 | 0.118382E+11 | 19127.35 | 03-AUG-20:10 | 13314.28 | 0.00 |
September | 0.00 | 0.00 | 0.104877E+11 | 0.754358E+10 | 19528.57 | 21-SEP-20:21 | 9596.95 | 0.00 |
October | 0.00 | 0.00 | 0.417613E+10 | 0.314660E+10 | 18938.79 | 16-OCT-23:45 | 11193.19 | 0.00 |
November | 0.00 | 0.00 | 0.852719E+09 | 0.693174E+09 | 18426.12 | 02-NOV-20:33 | 11656.73 | 0.00 |
December | 0.00 | 0.00 | 0.129389E+09 | 91935328.91 | 5835.88 | 12-DEC-14:00 | 4140.75 | 0.00 |
Annual Sum or Average | 0.706825E+11 | 0.511738E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 781527.40 | 698864.53 | 287.14 | 260.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.171454E+11 | 0.118382E+11 | 19528.57 | 17363.00 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.118478E+10 | 0.33 | 1263.55 | 01-JAN-16:51 | 0.94 |
February | 0.682872E+09 | 0.21 | 1263.55 | 01-FEB-08:63 | 0.94 |
March | 0.119456E+09 | 0.03 | 1263.55 | 06-MAR-08:07 | 0.94 |
April | 16678802.35 | 0.00 | 1263.55 | 06-APR-07:05 | 0.94 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 8162504.79 | 0.00 | 1263.55 | 13-OCT-07:08 | 0.94 |
November | 0.206388E+09 | 0.06 | 1263.55 | 07-NOV-08:08 | 0.94 |
December | 0.555252E+09 | 0.15 | 1263.55 | 01-DEC-08:65 | 0.94 |
Annual Sum or Average | 0.277359E+10 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118478E+10 | 0.33 | 1263.55 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.160516E+10 | 0.39 | 2078.58 | 01-JAN-07:01 | 0.91 |
February | 0.136625E+10 | 0.37 | 2078.58 | 01-FEB-05:02 | 0.91 |
March | 0.137680E+10 | 0.34 | 2078.58 | 18-MAR-04:02 | 0.91 |
April | 0.130614E+10 | 0.33 | 2048.04 | 18-APR-20:41 | 0.90 |
May | 0.137678E+10 | 0.35 | 2078.58 | 03-MAY-20:21 | 0.90 |
June | 0.147685E+10 | 0.44 | 2078.58 | 02-JUN-20:16 | 0.90 |
July | 0.157902E+10 | 0.47 | 2078.58 | 07-JUL-20:10 | 0.90 |
August | 0.162787E+10 | 0.49 | 2078.58 | 02-AUG-20:10 | 0.90 |
September | 0.141629E+10 | 0.41 | 2078.58 | 13-SEP-20:19 | 0.90 |
October | 0.134451E+10 | 0.34 | 1604.46 | 19-OCT-20:42 | 0.80 |
November | 0.130779E+10 | 0.33 | 2078.58 | 21-NOV-05:01 | 0.91 |
December | 0.145838E+10 | 0.36 | 2078.58 | 01-DEC-05:01 | 0.91 |
Annual Sum or Average | 0.172418E+11 | 0.38 | |||
Minimum of Months | 0.130614E+10 | 0.33 | 1604.46 | 0.80 | |
Maximum of Months | 0.162787E+10 | 0.49 | 2078.58 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.903832E+10 | 0.57 | 12279.27 | 08-JAN-08:62 | 1.44 |
February | 0.776520E+10 | 0.55 | 12279.27 | 12-FEB-08:62 | 1.44 |
March | 0.807954E+10 | 0.53 | 12279.27 | 31-MAR-06:03 | 1.42 |
April | 0.770804E+10 | 0.52 | 12279.27 | 18-APR-06:03 | 1.42 |
May | 0.796625E+10 | 0.52 | 12279.27 | 03-MAY-06:03 | 1.41 |
June | 0.791537E+10 | 0.53 | 12279.27 | 01-JUN-06:02 | 1.42 |
July | 0.831304E+10 | 0.53 | 12279.27 | 01-JUL-06:02 | 1.41 |
August | 0.846774E+10 | 0.54 | 12279.27 | 01-AUG-06:02 | 1.41 |
September | 0.775962E+10 | 0.52 | 12279.27 | 01-SEP-06:02 | 1.41 |
October | 0.788597E+10 | 0.52 | 12279.27 | 02-OCT-06:03 | 1.41 |
November | 0.770024E+10 | 0.52 | 7697.52 | 04-NOV-06:03 | 1.13 |
December | 0.841008E+10 | 0.54 | 12047.18 | 04-DEC-07:03 | 1.43 |
Annual Sum or Average | 0.970094E+11 | 0.53 | |||
Minimum of Months | 0.770024E+10 | 0.52 | 7697.52 | 1.13 | |
Maximum of Months | 0.903832E+10 | 0.57 | 12279.27 | 1.44 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.852833E+09 | 0.38 | 1204.02 | 01-JAN-07:01 | 0.94 |
February | 0.749137E+09 | 0.37 | 1204.02 | 02-FEB-05:01 | 0.94 |
March | 0.796259E+09 | 0.36 | 1204.02 | 13-MAR-22:11 | 0.94 |
April | 0.770054E+09 | 0.35 | 991.41 | 11-APR-21:21 | 0.86 |
May | 0.817449E+09 | 0.40 | 1078.00 | 18-MAY-01:11 | 0.89 |
June | 0.888352E+09 | 0.48 | 1204.02 | 04-JUN-04:01 | 0.93 |
July | 0.970585E+09 | 0.51 | 1204.02 | 07-JUL-20:08 | 0.93 |
August | 0.103920E+10 | 0.54 | 1204.02 | 02-AUG-20:08 | 0.93 |
September | 0.883887E+09 | 0.48 | 1204.02 | 07-SEP-20:43 | 0.93 |
October | 0.819808E+09 | 0.39 | 883.79 | 10-OCT-20:10 | 0.81 |
November | 0.754658E+09 | 0.35 | 1204.02 | 21-NOV-05:01 | 0.94 |
December | 0.804465E+09 | 0.36 | 1204.02 | 01-DEC-05:01 | 0.94 |
Annual Sum or Average | 0.101467E+11 | 0.41 | |||
Minimum of Months | 0.749137E+09 | 0.35 | 883.79 | 0.81 | |
Maximum of Months | 0.103920E+10 | 0.54 | 1204.02 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148962E+10 | 0.59 | 916.26 | 03-JAN-14:00 | 0.94 |
February | 0.134676E+10 | 0.59 | 916.26 | 01-FEB-18:06 | 0.94 |
March | 0.149977E+10 | 0.58 | 916.26 | 09-MAR-18:20 | 0.93 |
April | 0.144162E+10 | 0.57 | 916.26 | 01-APR-17:20 | 0.94 |
May | 0.151461E+10 | 0.60 | 916.26 | 10-MAY-13:10 | 0.94 |
June | 0.159980E+10 | 0.74 | 916.26 | 03-JUN-06:15 | 0.93 |
July | 0.169684E+10 | 0.79 | 916.26 | 07-JUL-10:00 | 0.93 |
August | 0.177185E+10 | 0.83 | 916.26 | 04-AUG-10:20 | 0.93 |
September | 0.158344E+10 | 0.72 | 916.26 | 01-SEP-05:05 | 0.93 |
October | 0.150958E+10 | 0.60 | 916.26 | 04-OCT-09:50 | 0.94 |
November | 0.141789E+10 | 0.56 | 916.26 | 02-NOV-17:30 | 0.93 |
December | 0.148265E+10 | 0.58 | 916.26 | 08-DEC-07:20 | 0.94 |
Annual Sum or Average | 0.183544E+11 | 0.65 | |||
Minimum of Months | 0.134676E+10 | 0.56 | 916.26 | 0.93 | |
Maximum of Months | 0.177185E+10 | 0.83 | 916.26 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.89 | 0.00 |
February | 0.46 | 0.00 |
March | 0.25 | 0.00 |
April | 0.00 | 0.00 |
May | 0.50 | 0.00 |
June | 0.17 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.11 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.25 | 0.00 |
Annual Sum or Average | 2.63 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.89 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.51 | 25.84 |
March | 1.29 | 25.84 |
April | 1.17 | 25.84 |
May | 1.08 | 21.87 |
June | 2.42 | 10.69 |
July | 2.39 | 5.41 |
August | 2.14 | 2.01 |
September | 0.92 | 18.80 |
October | 2.08 | 25.84 |
November | 1.38 | 25.84 |
December | 0.12 | 25.84 |
Annual Sum or Average | 15.50 | 16.35 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.42 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.31 | 0.00 |
February | 0.53 | 0.19 |
March | 0.58 | 0.52 |
April | 2.08 | 0.05 |
May | 1.34 | 0.00 |
June | 1.75 | 0.00 |
July | 0.08 | 0.00 |
August | 0.00 | 0.00 |
September | 2.40 | 0.00 |
October | 2.22 | 0.27 |
November | 0.76 | 0.66 |
December | 0.54 | 0.56 |
Annual Sum or Average | 12.61 | 0.15 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.40 | 0.66 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.62 | 0.00 |
February | 0.76 | 1.33 |
March | 0.42 | 0.73 |
April | 1.05 | 0.00 |
May | 0.60 | 0.00 |
June | 1.07 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 1.08 | 0.00 |
October | 2.12 | 0.77 |
November | 0.38 | 2.44 |
December | 0.37 | 0.81 |
Annual Sum or Average | 8.46 | 0.49 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.12 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 8.05 | 0.00 |
February | 9.77 | 0.00 |
March | 4.96 | 0.00 |
April | 2.34 | 0.00 |
May | 2.73 | 0.00 |
June | 4.50 | 0.00 |
July | 4.44 | 0.00 |
August | 2.53 | 0.00 |
September | 3.08 | 0.00 |
October | 5.71 | 0.00 |
November | 6.18 | 0.00 |
December | 7.97 | 0.00 |
Annual Sum or Average | 62.27 | 0.00 |
Minimum of Months | 2.34 | 0.00 |
Maximum of Months | 9.77 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.160516E+10 | 0.125984E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.140158E+10 | 0.718544E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.168670E+10 | 0.910302E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.245545E+10 | 0.129615E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.425985E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.699475E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.821235E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.875515E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.555735E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.254617E+10 | 42213051.39 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.143184E+10 | 0.105810E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.146516E+10 | 0.555402E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.463715E+11 | 0.274781E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.140158E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.875515E+10 | 0.125984E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.904042E+10 | 0.433280E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.825877E+10 | 0.230247E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.107465E+11 | 0.250450E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.158750E+11 | 0.347808E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.249385E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.349128E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.398551E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.418165E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.280794E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.151970E+11 | 0.289421E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.904649E+10 | 0.422406E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.856200E+10 | 0.194031E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.246328E+12 | 0.931217E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.825877E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.418165E+11 | 0.433280E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.861455E+09 | 0.383034E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.925548E+09 | 0.221351E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.134226E+10 | 0.246572E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.197430E+10 | 67240263.90 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.311338E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.466237E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.550433E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.607541E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.415939E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.228071E+10 | 26691914.86 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.125742E+10 | 0.203396E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.901632E+09 | 0.139587E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.330582E+11 | 0.798362E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.861455E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.607541E+10 | 0.383034E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.148981E+10 | 0.573961E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.142856E+10 | 0.342393E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.174990E+10 | 0.587150E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.210737E+10 | 0.151057E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.290215E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.426857E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.498395E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.548726E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.382475E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.239216E+10 | 91422908.07 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.160789E+10 | 0.483591E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.151162E+10 | 0.244925E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.337540E+11 | 0.129260E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.142856E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.548726E+10 | 0.573961E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.160516E+10 | 0.00 | 0.100787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136625E+10 | 0.126593E+09 | 0.574835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137680E+10 | 0.115700E+10 | 0.728241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130614E+10 | 0.433055E+10 | 0.103692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137678E+10 | 0.112667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147685E+10 | 0.218886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157902E+10 | 0.264681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162787E+10 | 0.287555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141629E+10 | 0.166494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134451E+10 | 0.478787E+10 | 33770441.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130779E+10 | 0.467105E+09 | 0.846482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145838E+10 | 24275496.44 | 0.444322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172418E+11 | 0.115922E+12 | 0.219824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162787E+10 | 0.287555E+11 | 0.100787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.903832E+10 | 6688339.33 | 0.346624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.776520E+10 | 0.161480E+10 | 0.184198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.807954E+10 | 0.911670E+10 | 0.200360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.770804E+10 | 0.281703E+11 | 0.278247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.796625E+10 | 0.606874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.791537E+10 | 0.987132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.831304E+10 | 0.116974E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.846774E+10 | 0.125334E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.775962E+10 | 0.749777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.788597E+10 | 0.263027E+11 | 0.231537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.770024E+10 | 0.456217E+10 | 0.337925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.841008E+10 | 0.502009E+09 | 0.155225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.970094E+11 | 0.546962E+12 | 0.744973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.770024E+10 | 6688339.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.903832E+10 | 0.125334E+12 | 0.346624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.852833E+09 | 32029493.02 | 0.306427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.749137E+09 | 0.691020E+09 | 0.177081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.796259E+09 | 0.217342E+10 | 0.197258E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.770054E+09 | 0.473249E+10 | 53792211.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.817449E+09 | 0.921283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.888352E+09 | 0.151134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.970585E+09 | 0.182224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103920E+10 | 0.204837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.883887E+09 | 0.134821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.819808E+09 | 0.608778E+10 | 21353531.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.754658E+09 | 0.202548E+10 | 0.162717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.804465E+09 | 0.390690E+09 | 0.111669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101467E+11 | 0.926473E+11 | 0.638689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.749137E+09 | 32029493.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103920E+10 | 0.204837E+11 | 0.306427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148962E+10 | 781527.40 | 0.459169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134676E+10 | 0.361848E+09 | 0.273915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149977E+10 | 0.111540E+10 | 0.469720E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144162E+10 | 0.294550E+10 | 0.120845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151461E+10 | 0.628877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159980E+10 | 0.121744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169684E+10 | 0.150045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.177185E+10 | 0.171454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158344E+10 | 0.104877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150958E+10 | 0.417613E+10 | 73138326.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141789E+10 | 0.852719E+09 | 0.386873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148265E+10 | 0.129389E+09 | 0.195940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183544E+11 | 0.706825E+11 | 0.103408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134676E+10 | 781527.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.177185E+10 | 0.171454E+11 | 0.459169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.160516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136625E+10 | 0.00 | 0.00 | 0.00 | 35332652.06 | 0.00 | 0.718544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137680E+10 | 0.00 | 0.00 | 0.00 | 0.309899E+09 | 0.00 | 0.910302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130614E+10 | 0.00 | 0.00 | 0.00 | 0.114931E+10 | 0.00 | 0.129615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137678E+10 | 0.00 | 0.00 | 0.00 | 0.288307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147685E+10 | 0.00 | 0.00 | 0.00 | 0.551790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157902E+10 | 0.00 | 0.00 | 0.00 | 0.663333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162787E+10 | 0.00 | 0.00 | 0.00 | 0.712727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141629E+10 | 0.00 | 0.00 | 0.00 | 0.414106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134451E+10 | 0.00 | 0.00 | 0.00 | 0.120166E+10 | 0.00 | 42213051.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130779E+10 | 0.00 | 0.00 | 0.00 | 0.124057E+09 | 0.00 | 0.105810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145838E+10 | 0.00 | 0.00 | 0.00 | 6782689.02 | 0.00 | 0.555402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172418E+11 | 0.00 | 0.00 | 0.00 | 0.291297E+11 | 0.00 | 0.274781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.130614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162787E+10 | 0.00 | 0.00 | 0.00 | 0.712727E+10 | 0.00 | 0.125984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.903832E+10 | 0.00 | 0.00 | 0.00 | 2106334.20 | 0.00 | 0.433280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.776520E+10 | 0.00 | 0.00 | 0.00 | 0.493567E+09 | 0.00 | 0.230247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.807954E+10 | 0.00 | 0.00 | 0.00 | 0.266695E+10 | 0.00 | 0.250450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.770804E+10 | 0.00 | 0.00 | 0.00 | 0.816691E+10 | 0.00 | 0.347808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.796625E+10 | 0.00 | 0.00 | 0.00 | 0.169722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.791537E+10 | 0.00 | 0.00 | 0.00 | 0.269974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.831304E+10 | 0.00 | 0.00 | 0.00 | 0.315420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.846774E+10 | 0.00 | 0.00 | 0.00 | 0.333487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.775962E+10 | 0.00 | 0.00 | 0.00 | 0.203198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.788597E+10 | 0.00 | 0.00 | 0.00 | 0.731098E+10 | 0.00 | 0.289421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.770024E+10 | 0.00 | 0.00 | 0.00 | 0.134625E+10 | 0.00 | 0.422406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.841008E+10 | 0.00 | 0.00 | 0.00 | 0.151917E+09 | 0.00 | 0.194031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.970094E+11 | 0.00 | 0.00 | 0.00 | 0.149319E+12 | 0.00 | 0.931217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.770024E+10 | 0.00 | 0.00 | 0.00 | 2106334.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.903832E+10 | 0.00 | 0.00 | 0.00 | 0.333487E+11 | 0.00 | 0.433280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.852833E+09 | 0.00 | 0.00 | 0.00 | 8621715.10 | 0.00 | 0.383034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.749137E+09 | 0.00 | 0.00 | 0.00 | 0.176410E+09 | 0.00 | 0.221351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.796259E+09 | 0.00 | 0.00 | 0.00 | 0.546002E+09 | 0.00 | 0.246572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.770054E+09 | 0.00 | 0.00 | 0.00 | 0.120424E+10 | 0.00 | 67240263.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.817449E+09 | 0.00 | 0.00 | 0.00 | 0.229593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.888352E+09 | 0.00 | 0.00 | 0.00 | 0.377401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.970585E+09 | 0.00 | 0.00 | 0.00 | 0.453374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103920E+10 | 0.00 | 0.00 | 0.00 | 0.503622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.883887E+09 | 0.00 | 0.00 | 0.00 | 0.327550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.819808E+09 | 0.00 | 0.00 | 0.00 | 0.146090E+10 | 0.00 | 26691914.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.754658E+09 | 0.00 | 0.00 | 0.00 | 0.502764E+09 | 0.00 | 0.203396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.804465E+09 | 0.00 | 0.00 | 0.00 | 97166850.52 | 0.00 | 0.139587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101467E+11 | 0.00 | 0.00 | 0.00 | 0.229115E+11 | 0.00 | 0.798362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.749137E+09 | 0.00 | 0.00 | 0.00 | 8621715.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103920E+10 | 0.00 | 0.00 | 0.00 | 0.503622E+10 | 0.00 | 0.383034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.148962E+10 | 0.00 | 0.00 | 0.00 | 191964.13 | 0.00 | 0.573961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134676E+10 | 0.00 | 0.00 | 0.00 | 81806815.50 | 0.00 | 0.342393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149977E+10 | 0.00 | 0.00 | 0.00 | 0.250128E+09 | 0.00 | 0.587150E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144162E+10 | 0.00 | 0.00 | 0.00 | 0.665753E+09 | 0.00 | 0.151057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151461E+10 | 0.00 | 0.00 | 0.00 | 0.138754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159980E+10 | 0.00 | 0.00 | 0.00 | 0.266877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169684E+10 | 0.00 | 0.00 | 0.00 | 0.328711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.177185E+10 | 0.00 | 0.00 | 0.00 | 0.371540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158344E+10 | 0.00 | 0.00 | 0.00 | 0.224131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150958E+10 | 0.00 | 0.00 | 0.00 | 0.882581E+09 | 0.00 | 91422908.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141789E+10 | 0.00 | 0.00 | 0.00 | 0.190000E+09 | 0.00 | 0.483591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148265E+10 | 0.00 | 0.00 | 0.00 | 28976275.21 | 0.00 | 0.244925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183544E+11 | 0.00 | 0.00 | 0.00 | 0.153996E+11 | 0.00 | 0.129260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.134676E+10 | 0.00 | 0.00 | 0.00 | 191964.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.177185E+10 | 0.00 | 0.00 | 0.00 | 0.371540E+10 | 0.00 | 0.573961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.215987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562100E+10 | 0.00 | 0.00 | 0.20 |
February | 0.251781E+10 | 0.00 | 0.00 | 364732.40 | 306125.84 | 0.298474E+10 | 0.370650E+09 | 0.00 | 0.24 |
March | 0.310560E+10 | 32122057.45 | 0.00 | 2267614.99 | 0.00 | 0.301868E+09 | 0.185161E+10 | 0.00 | 0.31 |
April | 0.115518E+10 | 0.109426E+09 | 0.00 | 4575614.01 | 1849189.79 | 50131884.55 | 0.242384E+10 | 0.00 | 0.42 |
May | 0.226965E+09 | 0.121862E+10 | 0.00 | 5571080.97 | 0.00 | 0.00 | 0.187191E+10 | 0.00 | 0.40 |
June | 32388389.80 | 0.452687E+10 | 0.00 | 3284629.30 | 0.00 | 0.00 | 0.536903E+09 | 0.00 | 0.28 |
July | 0.00 | 0.649386E+10 | 0.00 | 436775.78 | 0.00 | 0.00 | 0.141494E+09 | 0.00 | 0.22 |
August | 0.00 | 0.726692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
September | 55287281.40 | 0.310537E+10 | 0.00 | 4428474.86 | 0.00 | 0.00 | 0.136383E+10 | 0.00 | 0.33 |
October | 0.161487E+10 | 0.586596E+09 | 0.00 | 5810847.55 | 479184.32 | 1153379.44 | 0.345608E+10 | 0.00 | 0.38 |
November | 0.314570E+10 | 5103381.89 | 0.00 | 2716161.63 | 19313555.51 | 0.288343E+09 | 0.234816E+10 | 0.00 | 0.32 |
December | 0.384724E+10 | 0.00 | 0.00 | 371972.04 | 0.00 | 0.214698E+10 | 0.388044E+09 | 0.00 | 0.22 |
Annual Sum or Average | 0.178609E+11 | 0.233449E+11 | 0.00 | 29827903.52 | 21948055.45 | 0.113942E+11 | 0.147525E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.384724E+10 | 0.726692E+10 | 0.00 | 5810847.55 | 19313555.51 | 0.562100E+10 | 0.345608E+10 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.475228E+11 | 0.00 | 0.00 | 353002.17 | 0.00 | 0.118683E+11 | 0.663437E+09 | 0.00 | 0.39 |
February | 0.343989E+11 | 0.00 | 0.00 | 5618095.25 | 0.00 | 0.593818E+10 | 0.435974E+10 | 0.00 | 0.43 |
March | 0.225206E+11 | 0.551745E+09 | 0.00 | 19476226.65 | 529056.42 | 99097287.29 | 0.129470E+11 | 0.00 | 0.48 |
April | 0.783575E+10 | 0.216141E+10 | 0.00 | 25684754.61 | 101043.95 | 0.00 | 0.125015E+11 | 0.00 | 0.51 |
May | 0.149568E+10 | 0.121331E+11 | 0.00 | 27372609.99 | 22112098.27 | 0.00 | 0.650013E+10 | 0.00 | 0.49 |
June | 0.275943E+09 | 0.361453E+11 | 0.00 | 9926924.92 | 0.242376E+09 | 0.00 | 0.166412E+10 | 0.00 | 0.43 |
July | 11611115.64 | 0.497500E+11 | 0.00 | 2936517.37 | 0.415447E+09 | 0.00 | 0.461211E+09 | 0.00 | 0.41 |
August | 8818278.64 | 0.552388E+11 | 0.00 | 1254051.64 | 0.501882E+09 | 0.00 | 96273327.36 | 0.00 | 0.41 |
September | 0.655986E+09 | 0.236769E+11 | 0.00 | 17059656.02 | 0.154959E+09 | 0.00 | 0.476829E+10 | 0.00 | 0.46 |
October | 0.124727E+11 | 0.496085E+10 | 0.00 | 31761445.32 | 9808443.34 | 0.00 | 0.153933E+11 | 0.00 | 0.50 |
November | 0.251338E+11 | 70282043.08 | 0.00 | 16861969.30 | 65072543.49 | 0.581756E+09 | 0.115440E+11 | 0.00 | 0.47 |
December | 0.410359E+11 | 0.00 | 0.00 | 2573322.59 | 0.00 | 0.465478E+10 | 0.224565E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.193368E+12 | 0.184688E+12 | 0.00 | 0.160879E+09 | 0.141229E+10 | 0.231422E+11 | 0.731447E+11 | 0.00 | 0.45 |
Minimum of Months | 8818278.64 | 0.00 | 0.00 | 353002.17 | 0.00 | 0.00 | 96273327.36 | 0.00 | 0.39 |
Maximum of Months | 0.475228E+11 | 0.552388E+11 | 0.00 | 31761445.32 | 0.501882E+09 | 0.118683E+11 | 0.153933E+11 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.401582E+10 | 0.00 | 0.00 | 815674.27 | 0.00 | 0.117497E+10 | 0.771284E+09 | 0.00 | 0.42 |
February | 0.271309E+10 | 58802.68 | 0.00 | 3223206.41 | 0.00 | 0.614003E+09 | 0.141458E+10 | 0.00 | 0.55 |
March | 0.121744E+10 | 93613869.81 | 0.00 | 6371343.30 | 0.00 | 56338451.70 | 0.306825E+10 | 0.00 | 0.69 |
April | 0.577802E+09 | 0.318141E+09 | 0.00 | 4702748.48 | 0.00 | 3573392.39 | 0.184729E+10 | 0.00 | 0.68 |
May | 0.131437E+09 | 0.142957E+10 | 0.00 | 3372216.21 | 0.00 | 0.00 | 0.905035E+09 | 0.00 | 0.60 |
June | 28478303.21 | 0.387987E+10 | 0.00 | 1537513.09 | 0.00 | 0.00 | 0.249001E+09 | 0.00 | 0.49 |
July | 0.00 | 0.541726E+10 | 0.00 | 133411.97 | 0.00 | 0.00 | 42050917.74 | 0.00 | 0.41 |
August | 0.00 | 0.611001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 34541624.44 | 0.292507E+10 | 0.00 | 2566758.19 | 0.00 | 0.00 | 0.659857E+09 | 0.00 | 0.53 |
October | 0.714827E+09 | 0.733161E+09 | 0.00 | 8888307.23 | 0.00 | 0.00 | 0.294983E+10 | 0.00 | 0.73 |
November | 0.138923E+10 | 61919255.37 | 0.00 | 7981194.80 | 2551307.27 | 54604916.42 | 0.323309E+10 | 0.00 | 0.69 |
December | 0.282072E+10 | 2996991.61 | 0.00 | 3356124.65 | 0.00 | 0.397900E+09 | 0.207016E+10 | 0.00 | 0.50 |
Annual Sum or Average | 0.136434E+11 | 0.209717E+11 | 0.00 | 42948498.62 | 2551307.27 | 0.230139E+10 | 0.172104E+11 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.401582E+10 | 0.611001E+10 | 0.00 | 8888307.23 | 2551307.27 | 0.117497E+10 | 0.323309E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.276180E+10 | 0.00 | 0.00 | 127007.02 | 0.00 | 0.269836E+10 | 0.215693E+09 | 0.00 | 0.40 |
February | 0.205048E+10 | 90719.93 | 0.00 | 1287070.46 | 0.00 | 0.159218E+10 | 0.739299E+09 | 0.00 | 0.52 |
March | 0.170802E+10 | 58770740.60 | 0.00 | 2434402.49 | 0.00 | 0.266411E+09 | 0.178698E+10 | 0.00 | 0.63 |
April | 0.858988E+09 | 0.178133E+09 | 0.00 | 1981409.61 | 304348.82 | 67618537.83 | 0.122397E+10 | 0.00 | 0.66 |
May | 0.248375E+09 | 0.104197E+10 | 0.00 | 2025341.60 | 0.00 | 0.00 | 0.943381E+09 | 0.00 | 0.65 |
June | 57010289.33 | 0.342000E+10 | 0.00 | 888510.43 | 0.00 | 0.00 | 0.210903E+09 | 0.00 | 0.49 |
July | 5702321.85 | 0.481752E+10 | 0.00 | 156249.24 | 0.00 | 0.00 | 89094710.94 | 0.00 | 0.41 |
August | 0.00 | 0.550165E+10 | 0.00 | 28456.30 | 0.00 | 0.00 | 4740554.09 | 0.00 | 0.41 |
September | 0.104522E+09 | 0.246074E+10 | 0.00 | 1642385.21 | 0.00 | 0.00 | 0.644667E+09 | 0.00 | 0.54 |
October | 0.111370E+10 | 0.557799E+09 | 0.00 | 4846057.87 | 0.00 | 35402364.56 | 0.216369E+10 | 0.00 | 0.71 |
November | 0.190682E+10 | 15560759.52 | 0.00 | 3731795.28 | 3508661.06 | 0.124655E+09 | 0.220292E+10 | 0.00 | 0.66 |
December | 0.284595E+10 | 0.00 | 0.00 | 938007.68 | 0.00 | 0.107490E+10 | 0.843252E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.136614E+11 | 0.180522E+11 | 0.00 | 20086693.19 | 3813009.88 | 0.585953E+10 | 0.110686E+11 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 28456.30 | 0.00 | 0.00 | 4740554.09 | 0.00 | 0.40 |
Maximum of Months | 0.284595E+10 | 0.550165E+10 | 0.00 | 4846057.87 | 3508661.06 | 0.269836E+10 | 0.220292E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |