Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2020-06-03 19:13:22
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1508.87 | 657.75 | 657.75 |
Net Site Energy | 1508.87 | 657.75 | 657.75 |
Total Source Energy | 4605.17 | 2007.49 | 2007.49 |
Net Source Energy | 4605.17 | 2007.49 | 2007.49 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 730.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 277.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 38.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 183.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 83.25 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1425.62 | 83.25 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 730.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 277.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 38.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 183.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 83.25 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 137.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 398.81 | 36.29 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 621.46 | 36.29 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 137.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 398.81 | 36.29 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 621.46 | 36.29 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1425.617 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1425.617 | 100.00 |
Total On-Site and Utility Electric Sources | 1425.617 | 100.00 |
Total Electricity End Uses | 1425.617 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 76.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.5670 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 13.1320 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 13.1320 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 13.1320 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 10.7639 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 12.1980 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 12.1980 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | 13-JAN-12:09 | - | - | - | 26-APR-11:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 95729.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19720.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18292.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4860.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 144484.53 | 4860.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 95729.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19720.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 18292.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4860.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2315.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 880.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 122.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 615.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 582.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 90.24 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4514.93 | 90.24 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1009.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 253.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 39.34 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1968.15 | 39.34 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1009.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 253.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 39.34 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1968.15 | 39.34 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 2.84 |
CORE_RETAIL DIRECT AIR | 8.45 |
POINT_OF_SALE DIRECT AIR | 1.61 |
FRONT_RETAIL DIRECT AIR | 1.41 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 0.234536 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 0.234536 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 6907.04 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 68033.90 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 215515.01 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 38890.21 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 34486.11 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 2.84 | 2.84 | 2.84 | 2.84 | 2.88 | 2.88 | 1.00 | 0.986149 | 2.88 |
PSZ-AC:2 | 8.45 | 8.45 | 8.45 | 8.45 | 8.57 | 8.57 | 1.00 | 0.985974 | 8.57 |
PSZ-AC:3 | 1.61 | 1.61 | 1.61 | 1.61 | 1.61 | 1.61 | 1.00 | 1.00 | 1.61 |
PSZ-AC:4 | 1.41 | 1.41 | 1.41 | 1.41 | 1.41 | 1.41 | 1.00 | 1.00 | 1.41 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 2.88 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 8.57 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.61 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 1.41 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 2.88 | 2.88 | 2.88 | 1.90 | 62906.77 | 68033.90 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 8.57 | 8.57 | 8.57 | 5.65 | 212720.11 | 215515.01 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.61 | 1.61 | 1.61 | 1.06 | 35960.59 | 38890.21 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.41 | 1.41 | 1.41 | 0.933795 | 32719.84 | 34486.11 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 2.88 | 1.44 | 1.92 | 58870.31 | 62906.77 | 31453.38 | 31453.38 | 0.709172 | 0.709170 | 0.709170 | 0.709170 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 8.57 | 4.28 | 5.71 | 212720.14 | 212720.11 | 106360.05 | 106360.05 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.61 | 0.802625 | 1.07 | 33732.21 | 35960.59 | 17980.29 | 17980.29 | 0.702674 | 0.702670 | 0.702670 | 0.702670 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.41 | 0.707420 | 0.943227 | 30770.20 | 32719.84 | 16359.92 | 16359.92 | 0.694165 | 0.694170 | 0.694170 | 0.694170 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.88 | 3076.67 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 8.57 | 14431.67 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.61 | 1717.69 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.41 | 1566.45 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.567 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.637 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 13.132 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 16.362 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 13.132 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 34.652 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 13.132 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 16.362 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 10.764 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.764 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2874.639 | 7.567 | 46.863 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2874.639 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 21017.495 | 13.132 | 81.326 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21017.495 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 1980.433 | 13.132 | 81.326 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1980.433 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 1980.433 | 13.132 | 81.326 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1980.433 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 129.167 | 10.764 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 129.167 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
25 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
26 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
27 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
28 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
29 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
30 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
31 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
32 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
33 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.22 | 30 | 1 | VerySmooth | 2.843 | 0.222 | 0.132 | 0.242 |
2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 31 | 1 | VerySmooth | 4.262 | 0.355 | 0.203 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.13126 | 0.64095 | 0.64095 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1915 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 32984.58064 | 39581.49677 | 2.36287 | 2.83544 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07356E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 18383.51578 | 22060.21894 | 0.77062 | 0.92474 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 99231.99423 | 119078.39307 | 7.03841 | 8.44609 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07356E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 49423.11578 | 59307.73894 | 2.03833 | 2.44600 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 18171.24655 | 21805.49585 | 1.33771 | 1.60525 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 41.83000 | 1.07356E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 8252.19673 | 9902.63608 | 0.34701 | 0.41641 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 16015.82883 | 19218.99460 | 1.17903 | 1.41484 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 42.31500 | 1.07356E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 8252.19673 | 9902.63608 | 0.34701 | 0.41641 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80000 | 1.07356E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 5755.98349 | 6907.18019 | 0.19545 | 0.23454 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 43673.23 | 2.87527 | 2.87527 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 23721.73 | 0.92474 | 0.92474 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 154112.08 | 8.56624 | 8.56624 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 75390.27 | 2.44600 | 2.44600 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 25448.10 | 1.60525 | 1.60525 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 11392.71 | 0.41641 | 0.41641 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 22980.65 | 1.41484 | 1.41484 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 11392.71 | 0.41641 | 0.41641 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.83544 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 8.44609 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.60525 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.41484 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.23454 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 0.23454 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 6907.03551 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.83544 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.83544 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.83544 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.83544 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.87527 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.87527 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.98615 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.44609 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 8.44609 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.44609 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 8.44609 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.56624 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 8.56624 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.98597 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.60525 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.60525 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.60525 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.60525 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.60525 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.60525 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.41484 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41484 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.41484 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.41484 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.41484 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.41484 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 2.87527 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 8.56624 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.60525 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.41484 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.87527 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.87527 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.87527 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.87527 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.89768 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.87527 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.43764 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.91685 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 58870.30703 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 62906.77000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 31453.38500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 31453.38500 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70917 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70917 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70917 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70917 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 62906.77000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 68033.89688 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.87527 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3076.67258 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 68033.89688 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.56624 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.56624 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.56624 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.56624 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.65372 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 8.56624 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.28312 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.71083 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 212720.13906 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 212720.11000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 106360.05500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 106360.05500 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 212720.11000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 215515.01485 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 8.56624 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 14431.66817 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 215515.01485 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.60525 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.60525 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.60525 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.60525 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05946 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.60525 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.80263 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.07017 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 33732.21489 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 35960.59000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 17980.29500 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 17980.29500 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70267 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70267 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70267 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70267 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35960.59000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 38890.21011 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.60525 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1717.69300 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 38890.21011 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.41484 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.41484 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.41484 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.41484 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.93380 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.41484 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.70742 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.94323 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 30770.19656 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 32719.84000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16359.92000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 16359.92000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69416 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69417 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69417 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69417 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32719.84000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34486.10659 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.41484 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1566.45376 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 34486.10659 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 60643.8 | 11.54 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 205962.1 | 14.05 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 34696.6 | 102.10 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 31605.2 | 124.48 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.22 | N/A | 2.843 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.22 | N/A | 2.843 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.22 | N/A | 2.843 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 7 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 3.9999924113E-002 | 3.7170054346E-002 | Pass | Pass | 0.6121751896 | 3.8614496433 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 3.5520075893E-002 | 5.2285705452E-002 | Pass | Pass | 7.6399327086E-002 | 0.2082937065 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 4.0350033015E-002 | 5.3598742618E-002 | Pass | Pass | 3.6738760114E-002 | 0.1090233322 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 3.9905492350E-002 | 4.4496043666E-002 | Pass | Pass | 5.6203754074E-002 | 0.1345120949 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1230468063 | 0.3011489845 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5_SHGC_0.22 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.843 | 0.222 | 0.242 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5_SHGC_0.22 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.843 | 0.222 | 0.242 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5_SHGC_0.22 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.843 | 0.222 | 0.242 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 3.156 | 0.251 | 0.277 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 3.156 | 0.251 | 0.277 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.5670 | 379.89 | 2874.64 | LightsWired | BLDG_LIGHT_BACK_SCH | 55.08 | 168.00 | 52.05 | 0.0000 | Y | 28.09 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 13.1320 | 1600.48 | 21017.49 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 51.24 | 0.0000 | Y | 202.17 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 13.1320 | 150.81 | 1980.43 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 65.03 | 0.0000 | Y | 24.18 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 13.1320 | 150.81 | 1980.43 | LightsWired | BLDG_LIGHT_FRONT_SCH | 67.15 | 168.00 | 63.01 | 0.0000 | Y | 23.42 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 10.7639 | 12.00 | 129.17 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 57.54 | 168.00 | 3.36 | 0.0000 | Y | 0.08 |
Interior Lighting Total | 12.1980 | 2293.99 | 27982.17 | 277.94 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 21017.49 | 5254.37 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 21017.49 | 5254.37 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 316.30 | AstronomicalClock | - | 41.85 | 41.85 | 2.48 | |
EXTERIOR_LIGHTS_B | 3054.90 | AstronomicalClock | - | 83.85 | 62.85 | 36.04 | |
Exterior Lighting Total | 3371.20 | 38.53 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 62906.77 | 44611.59 | 18295.18 | 0.71 | 3.73 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 212720.11 | 143815.81 | 68904.30 | 0.68 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 35960.59 | 25268.43 | 10692.16 | 0.70 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 32719.84 | 22713.13 | 10006.71 | 0.69 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 60643.8 | 11.54 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 205962.1 | 14.05 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 34696.6 | 102.10 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 31605.2 | 124.48 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 6907.04 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 68033.90 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 215515.01 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 38890.21 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 34486.11 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.23 | 262.71 | 1120.11 | 1.00 | 2.09 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.88 | 3076.67 | 1070.05 | 1.00 | 1.27 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 8.57 | 14431.67 | 1684.71 | 1.00 | 1.15 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.61 | 1717.69 | 1070.05 | 1.00 | 1.35 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.41 | 1566.45 | 1107.16 | 1.00 | 1.33 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 32984.58 | 39581.50 | 104.19 | 2.363 | 2.835 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00750 | 35.62 | 0.01074 | 0.232 | 0.00 |
CORE_RETAIL | 99231.99 | 119078.39 | 74.40 | 7.038 | 8.446 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00787 | 35.62 | 0.01074 | 1.890 | 0.00 |
POINT_OF_SALE | 18171.25 | 21805.50 | 144.59 | 1.338 | 1.605 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 23.89 | 23.89 | 0.00732 | 41.83 | 0.01074 | 0.178 | 0.00 |
FRONT_RETAIL | 16015.83 | 19218.99 | 127.44 | 1.179 | 1.415 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 23.89 | 23.89 | 0.00736 | 42.31 | 0.01074 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 41.75 | 100.00 | 0.00001 | 42.80 | 0.01074 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 18383.52 | 22060.22 | 58.07 | 0.771 | 0.925 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00816 | 12.70 | 0.00915 | 0.232 | 0.00 |
CORE_RETAIL | 49423.12 | 59307.74 | 37.06 | 2.038 | 2.446 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00806 | 12.70 | 0.00915 | 1.890 | 0.00 |
POINT_OF_SALE | 8252.20 | 9902.64 | 65.66 | 0.347 | 0.416 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00815 | 12.70 | 0.00915 | 0.178 | 0.00 |
FRONT_RETAIL | 8252.20 | 9902.64 | 65.66 | 0.347 | 0.416 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00815 | 12.70 | 0.00915 | 0.178 | 0.00 |
FRONT_ENTRY | 5755.98 | 6907.18 | 575.60 | 0.195 | 0.235 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 16.00 | 16.00 | 0.00902 | 12.70 | 0.00915 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 2.88 | 2.88 | 0.92 | 0.92 | 2.8753 | 2.8354 | 2.8753 | 0.9861 | 1.0000 |
PSZ-AC:2 | 8.57 | 8.57 | 2.45 | 2.45 | 8.5662 | 8.4461 | 8.5662 | 0.9860 | 1.0000 |
PSZ-AC:3 | 1.61 | 1.61 | 0.42 | 0.42 | 1.6052 | 1.6052 | 1.6052 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.41 | 1.41 | 0.42 | 0.42 | 1.4148 | 1.4148 | 1.4148 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 6907.036 | 6907.036 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6907.04 | 6907.04 | 0.234536 | 15.81 | 13.80 | 0.00902350 | 40.00 | 21.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 16.00 | 0.00901515 | 79.5377 | 6907.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 31453.385 | 0.000 | 2.875270 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 31453.38 | 28420.23 | 2.875270 | 25.37 | 16.17 | 0.00770975 | 12.80 | 10.55 | 0.00700000 | 42.31 | 0.01073557 | 23.67 | 8.0537 | 23.89 | 0.00750075 | 40.6961 | 32508.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 68033.897 | 68033.897 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 68033.90 | 68033.90 | 2.875268 | 18.79 | 14.37 | 0.00840922 | 40.00 | 21.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 8.0537 | 21.11 | 0.00816059 | 52.3608 | 18383.52 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 106360.055 | 0.000 | 8.566240 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 106360.05 | 90796.85 | 8.566240 | 28.21 | 17.68 | 0.00833144 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01073558 | 23.80 | 22.0658 | 23.89 | 0.00787449 | 42.7015 | 93592.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 215515.015 | 215515.015 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 215515.01 | 215515.01 | 8.566239 | 14.52 | 13.19 | 0.00890580 | 40.00 | 21.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 22.0658 | 21.11 | 0.00806358 | 51.7472 | 49423.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 17980.295 | 0.000 | 1.605250 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 17980.29 | 16321.42 | 1.605250 | 25.92 | 16.36 | 0.00769800 | 12.80 | 10.55 | 0.00700000 | 42.22 | 0.01073558 | 23.64 | 11.0955 | 23.89 | 0.00731807 | 39.7152 | 18147.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 38890.210 | 38890.210 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38890.21 | 38890.21 | 1.605250 | 17.38 | 13.99 | 0.00857643 | 40.00 | 21.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 11.0955 | 21.11 | 0.00814516 | 52.2630 | 8252.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 16359.920 | 0.000 | 1.414840 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 16359.92 | 14706.75 | 1.414840 | 26.25 | 16.55 | 0.00778628 | 12.80 | 10.55 | 0.00700000 | 42.61 | 0.01073558 | 23.75 | 12.5887 | 23.89 | 0.00736056 | 39.9431 | 15994.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 34486.107 | 34486.107 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 34486.11 | 34486.11 | 1.414841 | 17.38 | 13.99 | 0.00857643 | 40.00 | 21.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.5887 | 21.11 | 0.00814516 | 52.2630 | 8252.20 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 6907.036 | 6907.036 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.234536 | 0.28228684 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6907.04 | 6907.04 | 1.0000 | 0.28228684 | 0.234536 | 15.81 | 13.80 | 0.00902350 | 38714.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6907.04 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 16.00 | 0.00901515 | 16.00 | 0.00901515 | 79.5377 | 6907.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31453.385 | 0.000 | 2.875270 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1720 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 31453.38 | 28420.23 | 1.0000 | 3.46066054 | 2.875270 | 25.37 | 16.17 | 0.00770975 | 45142.0 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31453.38 | 42.31 | 0.01073557 | 23.67 | 0.23156651 | 8.0537 | 23.89 | 0.00744437 | 23.89 | 0.00750075 | 40.6961 | 32508.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 68033.897 | 68033.897 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.875268 | 3.46065803 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 68033.90 | 68033.90 | 1.0000 | 3.46065803 | 2.875268 | 18.79 | 14.37 | 0.00840922 | 40205.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 68033.90 | 12.70 | 0.00915345 | 12.70 | 0.23156651 | 8.0537 | 20.82 | 0.00816059 | 21.11 | 0.00816059 | 52.3608 | 18383.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 106360.055 | 0.000 | 8.566240 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3277 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 106360.05 | 90796.85 | 1.0000 | 10.31028348 | 8.566240 | 28.21 | 17.68 | 0.00833144 | 49621.4 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 106360.05 | 42.80 | 0.01073558 | 23.80 | 1.89021192 | 22.0658 | 23.89 | 0.00761893 | 23.89 | 0.00787449 | 42.7015 | 93592.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 215515.015 | 215515.015 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.566239 | 10.31028221 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 215515.01 | 215515.01 | 1.0000 | 10.31028221 | 8.566239 | 14.52 | 13.19 | 0.00890580 | 37099.1 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 215515.01 | 12.70 | 0.00915345 | 12.70 | 1.89021192 | 22.0658 | 20.69 | 0.00806358 | 21.11 | 0.00806358 | 51.7472 | 49423.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17980.295 | 0.000 | 1.605250 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1502 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 17980.29 | 16321.42 | 1.0000 | 1.93207084 | 1.605250 | 25.92 | 16.36 | 0.00769800 | 45673.2 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17980.29 | 42.22 | 0.01073558 | 23.64 | 0.17811053 | 11.0955 | 23.89 | 0.00731835 | 23.89 | 0.00731807 | 39.7152 | 18147.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38890.210 | 38890.210 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.605250 | 1.93207041 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38890.21 | 38890.21 | 1.0000 | 1.93207041 | 1.605250 | 17.38 | 13.99 | 0.00857643 | 39189.1 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38890.21 | 12.70 | 0.00915345 | 12.70 | 0.17811053 | 11.0955 | 20.88 | 0.00814516 | 21.11 | 0.00814516 | 52.2630 | 8252.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16359.920 | 0.000 | 1.414840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3143 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 16359.92 | 14706.75 | 1.0000 | 1.70289432 | 1.414840 | 26.25 | 16.55 | 0.00778628 | 46227.5 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16359.92 | 42.61 | 0.01073558 | 23.75 | 0.17811053 | 12.5887 | 23.89 | 0.00736089 | 23.89 | 0.00736056 | 39.9431 | 15994.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34486.107 | 34486.107 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.414841 | 1.70289573 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 34486.11 | 34486.11 | 1.0000 | 1.70289573 | 1.414841 | 17.38 | 13.99 | 0.00857643 | 39189.1 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34486.11 | 12.70 | 0.00915345 | 12.70 | 0.17811053 | 12.5887 | 20.88 | 0.00814516 | 21.11 | 0.00814516 | 52.2630 | 8252.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 3639.33 | 404.17 | 4.67 |
CORE_RETAIL | 4203.67 | 237.17 | 76.50 |
POINT_OF_SALE | 4515.83 | 83.00 | 0.00 |
FRONT_RETAIL | 4417.67 | 143.17 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 4529.33 | 475.67 | 76.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 0.00 | 80.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 2.17 | 0.00 | 0.17 |
POINT_OF_SALE | 0.00 | 112.50 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 80.33 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 138.00 | 0.00 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.47 | 61.34 | 2317.33 | 0.371 | 0.027 | 0.000 | 0.000 |
CORE_RETAIL | 128.37 | 258.43 | 9762.95 | 0.720 | 0.005 | 0.000 | 0.000 |
POINT_OF_SALE | 12.10 | 24.35 | 919.94 | 0.718 | 0.029 | 0.000 | 0.000 |
FRONT_RETAIL | 12.10 | 24.35 | 919.94 | 0.719 | 0.029 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.47 | 61.34 | 2317.33 | 0.359 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.37 | 258.43 | 9762.95 | 0.696 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.10 | 24.35 | 919.94 | 0.698 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.10 | 24.35 | 919.94 | 0.696 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1425.62 | 2265.44 | 01-JAN-07:10 | 144484.53 | 10-AUG-16:00 |
Electricity:Building | 472.23 | 2265.44 | 01-JAN-00:10 | 35190.60 | 02-JAN-16:00 |
Electricity:Zone:BACK_SPACE | 77.86 | 535.60 | 01-JAN-00:10 | 4774.71 | 02-JAN-09:10 |
InteriorLights:Electricity | 277.94 | 493.85 | 01-JAN-00:10 | 24449.72 | 02-JAN-16:00 |
InteriorLights:Electricity:Zone:BACK_SPACE | 28.09 | 81.78 | 01-JAN-00:10 | 2023.29 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 277.94 | 493.85 | 01-JAN-00:10 | 24449.72 | 02-JAN-16:00 |
Electricity:Zone:CORE_RETAIL | 286.10 | 1109.80 | 01-JAN-00:10 | 23555.33 | 02-JAN-16:00 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 202.17 | 344.55 | 01-JAN-00:10 | 18915.75 | 02-JAN-16:00 |
Electricity:Zone:POINT_OF_SALE | 76.87 | 512.89 | 01-JAN-00:10 | 4695.10 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 24.18 | 32.47 | 01-JAN-00:10 | 1782.39 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 31.33 | 104.57 | 01-JAN-00:10 | 2162.89 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 23.42 | 32.47 | 01-JAN-00:10 | 1725.71 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 0.08 | 2.58 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 0.08 | 2.58 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 |
InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.77 | 453.82 | 01-JAN-00:10 | 2751.42 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 83.93 | 765.25 | 01-JAN-00:10 | 4639.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.69 | 480.42 | 01-JAN-00:10 | 2912.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.91 | 72.11 | 01-JAN-00:10 | 437.18 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1425.62 | 2265.44 | 01-JAN-07:10 | 144484.53 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 1425.62 | 2265.44 | 01-JAN-07:10 | 144484.53 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 1425.62 | 2265.44 | 01-JAN-07:10 | 144484.53 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1425.62 | 2265.44 | 01-JAN-07:10 | 144484.53 | 10-AUG-16:00 |
ElectricityNet:Plant | 1425.62 | 2265.44 | 01-JAN-07:10 | 144484.53 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 1425.62 | 2265.44 | 01-JAN-07:10 | 144484.53 | 10-AUG-16:00 |
Electricity:HVAC | 914.86 | 0.00 | 01-JAN-00:10 | 114022.86 | 10-AUG-16:00 |
Fans:Electricity | 183.88 | 0.00 | 01-JAN-00:10 | 18292.93 | 10-AUG-16:00 |
General:Fans:Electricity | 183.88 | 0.00 | 01-JAN-00:10 | 18292.93 | 10-AUG-16:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 730.98 | 0.00 | 01-JAN-00:10 | 95729.93 | 10-AUG-16:00 |
ExteriorLights:Electricity | 38.53 | 0.00 | 01-JAN-07:10 | 3371.20 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 38.53 | 0.00 | 01-JAN-07:10 | 3371.20 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 83.25 | 1860.00 | 05-JAN-08:10 | 4860.62 | 13-JAN-12:10 |
Gas:Plant | 83.25 | 1860.00 | 05-JAN-08:10 | 4860.62 | 13-JAN-12:10 |
WaterSystems:Gas | 83.25 | 1860.00 | 05-JAN-08:10 | 4860.62 | 13-JAN-12:10 |
Water Heater:WaterSystems:Gas | 83.25 | 1860.00 | 05-JAN-08:10 | 4860.62 | 13-JAN-12:10 |
Gas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 788.71 | 01-JAN-08:10 |
Heating:Gas | 0.00 | 0.00 | 01-JAN-00:10 | 788.71 | 01-JAN-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 3926.72 | 0.00 | 01-JAN-00:10 | 434709.99 | 03-AUG-14:10 |
EnergyTransfer:Building | 1342.17 | 0.00 | 01-JAN-00:10 | 131517.90 | 05-AUG-13:20 |
EnergyTransfer:Zone:BACK_SPACE | 267.83 | 0.00 | 01-JAN-00:10 | 37919.74 | 10-JUN-04:10 |
Heating:EnergyTransfer | 1.45 | 0.00 | 01-JAN-00:10 | 14476.05 | 21-MAY-07:20 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 0.03 | 0.00 | 01-JAN-00:10 | 1210.46 | 16-JAN-11:20 |
Cooling:EnergyTransfer | 1340.72 | 0.00 | 01-JAN-00:10 | 131517.90 | 05-AUG-13:20 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 267.80 | 0.00 | 01-JAN-00:10 | 37919.74 | 10-JUN-04:10 |
EnergyTransfer:Zone:CORE_RETAIL | 754.61 | 0.00 | 01-JAN-00:10 | 85881.22 | 04-JUL-08:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 1.42 | 0.00 | 01-JAN-00:10 | 14476.05 | 21-MAY-07:20 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 753.19 | 0.00 | 01-JAN-00:10 | 80479.93 | 04-JUL-08:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 176.52 | 0.00 | 01-JAN-00:10 | 16571.50 | 07-AUG-04:30 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.00 | 0.00 | 01-JAN-00:10 | 385.13 | 16-AUG-05:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 176.51 | 0.00 | 01-JAN-00:10 | 16571.50 | 07-AUG-04:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 143.22 | 0.00 | 01-JAN-00:10 | 15782.14 | 13-SEP-04:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.00 | 0.00 | 01-JAN-00:10 | 408.48 | 15-FEB-08:00 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 143.22 | 0.00 | 01-JAN-00:10 | 15782.14 | 13-SEP-04:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 2584.55 | 0.00 | 01-JAN-00:10 | 310052.13 | 03-AUG-14:10 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 630.97 | 01-JAN-08:10 |
CoolingCoils:EnergyTransfer | 2584.55 | 0.00 | 01-JAN-00:10 | 310052.13 | 03-AUG-14:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 0.031 | -267.789 | 0.000 | 0.000 | 36.700 | 28.087 | 49.772 | 0.000 | 0.000 | 3.580 | 151.090 | 0.000 | 0.000 | 0.000 | -1.470 | -0.003 |
CORE_RETAIL | 0.000 | 0.000 | 1.420 | -753.184 | 0.000 | 0.000 | 154.564 | 202.170 | 83.927 | 49.749 | 0.000 | 3.112 | 269.252 | 0.000 | -9.757 | 0.000 | -1.253 | -0.000 |
POINT_OF_SALE | 0.000 | 0.000 | 0.001 | -176.511 | 0.000 | 0.000 | 14.560 | 24.176 | 52.689 | 29.422 | 0.000 | 1.519 | 61.246 | 0.000 | -6.285 | 0.000 | -0.819 | -0.001 |
FRONT_RETAIL | 0.000 | 0.000 | 0.001 | -143.215 | 0.000 | 0.000 | 14.566 | 23.423 | 7.908 | 29.297 | 0.000 | 1.535 | 73.212 | 0.000 | -5.990 | 0.000 | -0.737 | -0.001 |
FRONT_ENTRY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.081 | 0.000 | 4.837 | 0.000 | 5.201 | 0.000 | 0.000 | -1.461 | 0.000 | -2.785 | -5.873 |
Total Facility | 0.000 | 0.000 | 1.453 | -1340.700 | 0.000 | 0.000 | 220.390 | 277.937 | 194.297 | 113.306 | 0.000 | 14.948 | 554.800 | 0.000 | -23.493 | 0.000 | -7.064 | -5.878 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 04-JUL-06:01 | 0.00 | 0.00 | 0.00 | -57523.06 | 0.00 | 0.00 | 0.00 | 81.78 | 453.82 | 0.00 | 0.00 | 23.08 | 56964.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 23-MAR-06:02 | 0.00 | 0.00 | 0.00 | -185293.94 | 0.00 | 0.00 | 1603.68 | 344.55 | 2062.04 | 0.00 | 0.00 | 0.00 | 182248.03 | 0.00 | -943.03 | 0.00 | -21.32 | 0.00 |
POINT_OF_SALE | 23-MAR-04:01 | 0.00 | 0.00 | 0.00 | -33046.66 | 0.00 | 0.00 | 0.00 | 32.47 | 640.56 | 0.00 | 0.00 | 0.00 | 33166.83 | 0.00 | -723.03 | 0.00 | -70.16 | 0.00 |
FRONT_RETAIL | 23-MAR-04:01 | 0.00 | 0.00 | 0.00 | -29985.16 | 0.00 | 0.00 | 0.00 | 32.47 | 96.14 | 0.00 | 0.00 | 0.00 | 30600.13 | 0.00 | -682.56 | 0.00 | -61.01 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-AUG-06:01 | 0.00 | 0.00 | 0.00 | -254421.37 | 0.00 | 0.00 | 0.00 | 493.85 | 1771.59 | 859.60 | 0.00 | 456.87 | 250839.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 10-DEC-08:04 | 0.00 | 0.00 | 1304.48 | 0.00 | 0.00 | 0.00 | 0.00 | 81.78 | 453.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -15.44 | -1824.64 |
CORE_RETAIL | 06-AUG-07:06 | 0.00 | 0.00 | 29122.70 | 0.00 | 0.00 | 0.00 | 0.00 | 344.55 | 765.25 | 997.60 | 0.00 | 40.62 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31270.71 |
POINT_OF_SALE | 16-AUG-05:06 | 0.00 | 0.00 | 2695.91 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 640.56 | 342.35 | 0.00 | 88.34 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3799.62 |
FRONT_RETAIL | 21-JUL-05:06 | 0.00 | 0.00 | 2538.14 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 96.14 | 167.89 | 0.00 | 59.03 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2893.67 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-AUG-05:06 | -23506.85 | 23506.85 | 29930.69 | -23506.85 | 0.00 | 0.00 | 0.00 | 493.85 | 2362.12 | 708.90 | 0.00 | 523.10 | 0.00 | 0.00 | -44.43 | 0.00 | 0.00 | -10467.38 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.8354 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.8753 | 0.0805 | 1.0000 | 0.2316 | 0.0805 | ||
PSZ-AC:2 | 8.4461 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.5662 | 0.2207 | 1.0000 | 1.8902 | 0.2207 | ||
PSZ-AC:3 | 1.6052 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.6052 | 0.1110 | 1.0000 | 0.1781 | 0.1110 | ||
PSZ-AC:4 | 1.4148 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.4148 | 0.1259 | 1.0000 | 0.1781 | 0.1259 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.8354 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.8354 | 1.0000 | 1.0000 | 0.2316 | 0.0817 | ||
PSZ-AC:2 | 8.4461 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.4461 | 1.0000 | 1.0000 | 1.8902 | 0.2238 | ||
PSZ-AC:3 | 1.6052 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.6052 | 1.0000 | 1.0000 | 0.1781 | 0.1110 | ||
PSZ-AC:4 | 1.4148 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.4148 | 1.0000 | 1.0000 | 0.1781 | 0.1259 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.8354 | 2.8354 | 2.8354 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.4461 | 8.4461 | 8.4461 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.6052 | 1.6052 | 1.6052 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.4148 | 1.4148 | 1.4148 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.8354 | 2.8753 | 2.8354 | 2.8354 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.4461 | 8.5662 | 8.4461 | 8.4461 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.6052 | 1.6052 | 1.6052 | 1.6052 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.4148 | 1.4148 | 1.4148 | 1.4148 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.8354 | 2.8354 | 2.8354 | 0.2316 | 0.2504 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.4461 | 8.4461 | 8.4461 | 1.8902 | 0.7728 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.6052 | 1.6052 | 1.6052 | 0.1781 | 0.4277 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.4148 | 1.4148 | 1.4148 | 0.1781 | 0.4277 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.8354 | 2.8354 | 2.8354 | 2.8354 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.4461 | 8.4461 | 8.4461 | 8.4461 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.6052 | 1.6052 | 1.6052 | 1.6052 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.4148 | 1.4148 | 1.4148 | 1.4148 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:22
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 0.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 0.00 | 788.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 730.98 | 95729.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 277.94 | 24449.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 38.53 | 3371.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 194.30 | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 183.88 | 18292.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 83.25 | 4860.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 194.30 | 1425.62 |
Natural Gas | 0.00 | 83.25 |
Additional | 0.00 | 0.00 |
Total | 194.30 | 1508.87 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 121.16 |
Space Heating | 0.00 |
Space Cooling | 318.65 |
Fans (All) | 80.16 |
Service Water Heating | 0.00 |
Receptacle Equipment | 84.70 |
Miscellaneous (All) | 621.46 |
Subtotal | 621.46 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 36.29 |
Miscellaneous (All) | 36.29 |
Subtotal | 36.29 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.42 |
Space Heating | 0.00 |
Space Cooling | 48.45 |
Fans (All) | 12.19 |
Service Water Heating | 5.52 |
Receptacle Equipment | 12.88 |
Miscellaneous | 2.55 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 2872. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3001. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3501. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4552. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_FRONTENTRY_STD2013 | FRONT_ENTRY DUALSPSCHED | January | 16.00 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 1910566.147 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 1910566.147 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 1910566.147 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 1910566.147 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 1910566.147 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 1910566.147 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 1910566.147 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 1910566.147 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 1910566.147 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 1910566.147 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 1910566.147 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 1910566.147 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 1910566.147 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 1910566.147 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 1910566.147 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 1910566.147 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 1910566.147 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 1910566.147 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 1910566.147 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 1910566.147 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 1910566.147 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 1910566.147 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 1910566.147 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 1910566.147 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 1910566.147 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 1910566.147 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 1910566.147 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.495477E+10 | 42147.55 | 30-JAN-05:01 | 20.00 | 17.43 | 0.216474E+10 | 2451.26 | 28-JAN-15:09 | 25.75 | 18.21 |
February | 0.692663E+10 | 42690.36 | 08-FEB-05:01 | 22.00 | 18.64 | 0.198846E+10 | 2451.24 | 18-FEB-11:09 | 20.17 | 18.20 |
March | 0.120080E+11 | 57495.99 | 23-MAR-04:01 | 21.33 | 13.56 | 0.228011E+10 | 2451.29 | 28-MAR-14:00 | 29.10 | 20.87 |
April | 0.180300E+11 | 57376.55 | 29-APR-04:01 | 25.83 | 16.39 | 0.215641E+10 | 2451.39 | 07-APR-14:09 | 30.83 | 20.54 |
May | 0.303005E+11 | 57377.57 | 11-MAY-04:01 | 29.58 | 16.44 | 0.223252E+10 | 2451.35 | 18-MAY-14:20 | 36.67 | 24.05 |
June | 0.343509E+11 | 54212.73 | 01-JUN-04:01 | 28.75 | 21.74 | 0.220158E+10 | 2451.46 | 16-JUN-14:00 | 38.00 | 21.57 |
July | 0.392558E+11 | 57524.08 | 04-JUL-06:01 | 30.18 | 16.65 | 0.218718E+10 | 2451.47 | 29-JUL-10:50 | 39.92 | 24.51 |
August | 0.406566E+11 | 51080.48 | 06-AUG-06:01 | 34.98 | 22.46 | 0.228093E+10 | 2451.41 | 12-AUG-10:09 | 34.90 | 25.71 |
September | 0.317844E+11 | 49394.59 | 02-SEP-04:01 | 30.48 | 22.93 | 0.215638E+10 | 2451.42 | 26-SEP-14:50 | 39.00 | 24.94 |
October | 0.253679E+11 | 53222.84 | 20-OCT-04:01 | 22.50 | 16.20 | 0.218398E+10 | 2451.34 | 30-OCT-14:09 | 31.00 | 23.29 |
November | 0.160189E+11 | 52796.67 | 05-NOV-06:01 | 20.10 | 15.20 | 0.210125E+10 | 2451.35 | 08-NOV-15:00 | 30.20 | 21.97 |
December | 0.814115E+10 | 48876.77 | 01-DEC-05:01 | 17.83 | 12.83 | 0.218374E+10 | 2451.23 | 16-DEC-12:20 | 22.03 | 14.23 |
Annual Sum or Average | 0.267796E+12 | 0.261173E+11 | ||||||||
Minimum of Months | 0.495477E+10 | 42147.55 | 17.83 | 12.83 | 0.198846E+10 | 2451.23 | 20.17 | 14.23 | ||
Maximum of Months | 0.406566E+11 | 57524.08 | 34.98 | 22.93 | 0.228093E+10 | 2451.47 | 39.92 | 25.71 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298369E+11 | 87820.34 | 29-JAN-09:03 | 23.22 | 19.02 | 0.914011E+10 | 10327.87 | 28-JAN-15:09 | 25.75 | 18.21 |
February | 0.332211E+11 | 133558.68 | 06-FEB-07:03 | 21.25 | 17.85 | 0.838229E+10 | 10327.53 | 09-FEB-15:09 | 22.85 | 20.18 |
March | 0.455011E+11 | 185295.53 | 23-MAR-06:02 | 22.83 | 12.03 | 0.960591E+10 | 10327.39 | 28-MAR-14:00 | 29.10 | 20.87 |
April | 0.562858E+11 | 179842.96 | 26-APR-06:02 | 23.97 | 12.26 | 0.908755E+10 | 10327.86 | 27-APR-14:00 | 36.40 | 21.94 |
May | 0.788844E+11 | 175614.85 | 11-MAY-05:01 | 28.00 | 16.04 | 0.940945E+10 | 10327.95 | 06-MAY-14:50 | 37.00 | 21.57 |
June | 0.841526E+11 | 159774.70 | 01-JUN-05:01 | 28.67 | 21.40 | 0.927908E+10 | 10327.59 | 17-JUN-10:09 | 34.33 | 24.91 |
July | 0.922288E+11 | 170396.17 | 04-JUL-07:01 | 31.33 | 17.53 | 0.921878E+10 | 10327.41 | 13-JUL-14:09 | 38.00 | 27.89 |
August | 0.955474E+11 | 150537.24 | 06-AUG-06:01 | 34.98 | 22.46 | 0.961379E+10 | 10327.04 | 16-AUG-14:50 | 40.67 | 29.29 |
September | 0.800650E+11 | 143688.71 | 05-SEP-04:01 | 30.58 | 25.34 | 0.908860E+10 | 10327.30 | 09-SEP-14:09 | 35.83 | 30.24 |
October | 0.691308E+11 | 165152.12 | 20-OCT-05:03 | 23.17 | 16.22 | 0.920494E+10 | 10327.72 | 11-OCT-14:20 | 34.67 | 21.99 |
November | 0.513436E+11 | 159798.20 | 19-NOV-09:02 | 25.40 | 16.07 | 0.885490E+10 | 10327.67 | 13-NOV-15:00 | 30.20 | 20.80 |
December | 0.369919E+11 | 139950.33 | 12-DEC-07:02 | 23.17 | 17.80 | 0.920152E+10 | 10327.22 | 09-DEC-14:09 | 28.83 | 21.36 |
Annual Sum or Average | 0.753189E+12 | 0.110087E+12 | ||||||||
Minimum of Months | 0.298369E+11 | 87820.34 | 21.25 | 12.03 | 0.838229E+10 | 10327.04 | 22.85 | 18.21 | ||
Maximum of Months | 0.955474E+11 | 185295.53 | 34.98 | 25.34 | 0.961379E+10 | 10327.95 | 40.67 | 30.24 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.790516E+10 | 26217.80 | 30-JAN-05:01 | 20.00 | 17.43 | 0.865592E+09 | 973.26 | 28-JAN-15:09 | 25.75 | 18.21 |
February | 0.812992E+10 | 26657.77 | 28-FEB-05:02 | 18.67 | 16.28 | 0.791133E+09 | 973.19 | 16-FEB-15:20 | 24.57 | 18.26 |
March | 0.102900E+11 | 33046.32 | 23-MAR-04:01 | 21.33 | 13.56 | 0.905422E+09 | 973.18 | 24-MAR-14:09 | 27.00 | 20.20 |
April | 0.117601E+11 | 32988.30 | 29-APR-04:01 | 25.83 | 16.39 | 0.856074E+09 | 973.22 | 15-APR-12:20 | 29.63 | 20.23 |
May | 0.163517E+11 | 32547.30 | 05-MAY-04:01 | 25.75 | 15.81 | 0.886287E+09 | 973.24 | 09-MAY-14:09 | 38.83 | 22.15 |
June | 0.174505E+11 | 29814.15 | 02-JUN-04:01 | 28.33 | 18.19 | 0.874003E+09 | 973.25 | 21-JUN-14:30 | 39.50 | 22.55 |
July | 0.203902E+11 | 32020.69 | 04-JUL-06:01 | 30.18 | 16.65 | 0.868281E+09 | 973.22 | 29-JUL-10:39 | 39.83 | 24.00 |
August | 0.224070E+11 | 27857.32 | 06-AUG-06:01 | 34.98 | 22.46 | 0.905490E+09 | 973.09 | 05-AUG-11:20 | 43.33 | 25.10 |
September | 0.195968E+11 | 28490.58 | 26-SEP-04:01 | 26.97 | 19.71 | 0.856028E+09 | 973.20 | 02-SEP-10:09 | 36.58 | 24.14 |
October | 0.181478E+11 | 31452.03 | 21-OCT-04:01 | 22.25 | 15.09 | 0.867008E+09 | 973.28 | 02-OCT-14:00 | 34.90 | 21.66 |
November | 0.141788E+11 | 31244.94 | 05-NOV-06:01 | 20.10 | 15.20 | 0.834173E+09 | 973.18 | 03-NOV-14:30 | 31.00 | 23.76 |
December | 0.990612E+10 | 29632.48 | 01-DEC-05:01 | 17.83 | 12.83 | 0.868227E+09 | 973.23 | 29-DEC-15:09 | 23.00 | 17.05 |
Annual Sum or Average | 0.176514E+12 | 0.103777E+11 | ||||||||
Minimum of Months | 0.790516E+10 | 26217.80 | 17.83 | 12.83 | 0.791133E+09 | 973.09 | 23.00 | 17.05 | ||
Maximum of Months | 0.224070E+11 | 33046.32 | 34.98 | 22.46 | 0.905490E+09 | 973.28 | 43.33 | 25.10 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.535322E+10 | 22998.09 | 23-JAN-05:02 | 18.83 | 16.93 | 0.862082E+09 | 973.27 | 28-JAN-15:09 | 25.75 | 18.21 |
February | 0.571737E+10 | 22312.27 | 24-FEB-05:01 | 20.00 | 18.04 | 0.789605E+09 | 973.19 | 23-FEB-15:50 | 26.55 | 17.95 |
March | 0.744794E+10 | 29984.86 | 23-MAR-04:01 | 21.33 | 13.56 | 0.904777E+09 | 973.16 | 21-MAR-14:09 | 29.67 | 18.82 |
April | 0.911327E+10 | 29217.12 | 29-APR-04:01 | 25.83 | 16.39 | 0.856057E+09 | 973.19 | 07-APR-14:09 | 30.83 | 20.54 |
May | 0.135760E+11 | 29237.83 | 11-MAY-04:01 | 29.58 | 16.44 | 0.886282E+09 | 973.22 | 09-MAY-14:09 | 38.83 | 22.15 |
June | 0.146599E+11 | 26867.57 | 01-JUN-04:01 | 28.75 | 21.74 | 0.873998E+09 | 973.22 | 21-JUN-14:30 | 39.50 | 22.55 |
July | 0.174010E+11 | 28605.26 | 04-JUL-06:01 | 30.18 | 16.65 | 0.868282E+09 | 973.22 | 29-JUL-10:50 | 39.92 | 24.51 |
August | 0.192843E+11 | 24959.32 | 06-AUG-06:01 | 34.98 | 22.46 | 0.905492E+09 | 973.12 | 26-AUG-10:09 | 36.42 | 25.58 |
September | 0.167265E+11 | 24929.67 | 26-SEP-04:01 | 26.97 | 19.71 | 0.856027E+09 | 973.17 | 02-SEP-10:20 | 36.87 | 24.10 |
October | 0.153079E+11 | 27783.92 | 21-OCT-04:01 | 22.25 | 15.09 | 0.866998E+09 | 973.24 | 02-OCT-14:00 | 34.90 | 21.66 |
November | 0.114693E+11 | 27722.98 | 05-NOV-06:01 | 20.10 | 15.20 | 0.834166E+09 | 973.16 | 28-NOV-15:09 | 27.88 | 22.35 |
December | 0.716093E+10 | 26034.46 | 01-DEC-05:01 | 17.83 | 12.83 | 0.867577E+09 | 973.19 | 02-DEC-13:09 | 27.67 | 18.82 |
Annual Sum or Average | 0.143218E+12 | 0.103713E+11 | ||||||||
Minimum of Months | 0.535322E+10 | 22312.27 | 17.83 | 12.83 | 0.789605E+09 | 973.12 | 25.75 | 17.95 | ||
Maximum of Months | 0.192843E+11 | 29984.86 | 34.98 | 22.46 | 0.905492E+09 | 973.27 | 39.92 | 25.58 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.83 | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.58 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.58 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.45 | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.45 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.55 | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.55 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 | 23.23 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.23 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.01 | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.01 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 | 28.28 | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.03 | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.16 | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.16 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.62 | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.62 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.83 | 0.00 | 0.00 | 15.70 | 12.83 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.00 | 0.00 | 33.23 | 28.28 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21925289.43 | 1213.08 | 16-JAN-11:00 | 24.00 |
February | 4197900.10 | 1201.50 | 15-FEB-07:55 | 23.20 |
March | 1343699.72 | 821.77 | 05-MAR-08:07 | 22.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 49319.79 | 286.93 | 26-NOV-08:02 | 19.33 |
December | 3322633.62 | 1304.53 | 10-DEC-08:04 | 22.17 |
Annual Sum or Average | 30838842.66 | |||
Minimum of Months | 0.00 | 0.00 | 19.33 | |
Maximum of Months | 21925289.43 | 1304.53 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8963355.84 | 6618.95 | 29-JAN-09:07 | 23.22 |
February | 10829225.86 | 6245.40 | 05-FEB-09:10 | 23.55 |
March | 64585630.17 | 15721.79 | 02-MAR-07:06 | 27.67 |
April | 92924536.38 | 12195.53 | 02-APR-08:06 | 26.00 |
May | 0.190385E+09 | 24672.86 | 21-MAY-08:06 | 31.67 |
June | 0.183985E+09 | 22091.58 | 29-JUN-05:20 | 32.33 |
July | 0.222954E+09 | 27006.42 | 04-JUL-08:06 | 32.82 |
August | 0.196830E+09 | 29123.44 | 06-AUG-07:06 | 35.08 |
September | 0.184998E+09 | 20934.11 | 04-SEP-07:20 | 31.90 |
October | 0.182327E+09 | 16332.83 | 15-OCT-08:06 | 27.67 |
November | 67634019.51 | 11542.61 | 11-NOV-09:06 | 25.52 |
December | 13376216.17 | 7778.31 | 10-DEC-09:05 | 23.60 |
Annual Sum or Average | 0.141979E+10 | |||
Minimum of Months | 8963355.84 | 6245.40 | 23.22 | |
Maximum of Months | 0.222954E+09 | 29123.44 | 35.08 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 41466.52 | 138.22 | 09-MAR-06:10 | 20.83 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 182209.80 | 2125.78 | 10-JUN-05:06 | 30.00 |
July | 246027.73 | 1984.96 | 21-JUL-05:06 | 32.08 |
August | 716430.93 | 2695.89 | 16-AUG-05:06 | 34.00 |
September | 69259.50 | 808.03 | 08-SEP-05:06 | 29.58 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 1255394.48 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 716430.93 | 2695.89 | 34.00 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 377920.43 | 485.89 | 15-FEB-07:55 | 23.20 |
March | 66451.26 | 300.36 | 05-MAR-08:07 | 22.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 217559.08 | 2538.19 | 21-JUL-05:06 | 32.08 |
August | 32878.01 | 285.76 | 16-AUG-05:06 | 34.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 694808.78 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 377920.43 | 2538.19 | 34.00 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.235462E+10 | 2023.29 | 02-JAN-09:09 | 0.419292E+10 | 2751.42 | 02-JAN-09:09 |
February | 0.214299E+10 | 2023.29 | 01-FEB-09:09 | 0.380401E+10 | 2751.42 | 01-FEB-09:09 |
March | 0.244478E+10 | 2023.29 | 01-MAR-09:09 | 0.429860E+10 | 2751.42 | 01-MAR-09:09 |
April | 0.230724E+10 | 2023.29 | 01-APR-09:09 | 0.408483E+10 | 2751.42 | 01-APR-09:09 |
May | 0.239970E+10 | 2023.29 | 01-MAY-08:09 | 0.424576E+10 | 2751.42 | 01-MAY-08:09 |
June | 0.235921E+10 | 2023.29 | 01-JUN-08:09 | 0.415135E+10 | 2751.42 | 01-JUN-08:09 |
July | 0.234773E+10 | 2023.29 | 01-JUL-09:09 | 0.417924E+10 | 2751.42 | 01-JUL-09:09 |
August | 0.244478E+10 | 2023.29 | 01-AUG-08:09 | 0.429860E+10 | 2751.42 | 01-AUG-08:09 |
September | 0.230724E+10 | 2023.29 | 01-SEP-08:09 | 0.408483E+10 | 2751.42 | 01-SEP-08:09 |
October | 0.235462E+10 | 2023.29 | 02-OCT-08:09 | 0.419292E+10 | 2751.42 | 02-OCT-08:09 |
November | 0.227595E+10 | 2023.29 | 01-NOV-08:09 | 0.405935E+10 | 2751.42 | 01-NOV-08:09 |
December | 0.234773E+10 | 2023.29 | 01-DEC-09:09 | 0.417924E+10 | 2751.42 | 01-DEC-09:09 |
Annual Sum or Average | 0.280866E+11 | 0.497716E+11 | ||||
Minimum of Months | 0.214299E+10 | 2023.29 | 0.380401E+10 | 2751.42 | ||
Maximum of Months | 0.244478E+10 | 2023.29 | 0.429860E+10 | 2751.42 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.185158E+11 | 18915.75 | 02-JAN-15:00 | 0.707031E+10 | 4639.58 | 02-JAN-09:09 |
February | 0.162141E+11 | 18915.75 | 01-FEB-16:30 | 0.641452E+10 | 4639.58 | 01-FEB-09:09 |
March | 0.168263E+11 | 18915.75 | 01-MAR-16:49 | 0.724851E+10 | 4639.58 | 01-MAR-09:09 |
April | 0.158688E+11 | 18915.75 | 01-APR-16:00 | 0.688804E+10 | 4639.58 | 01-APR-09:09 |
May | 0.167708E+11 | 17339.43 | 01-MAY-16:30 | 0.715941E+10 | 4639.58 | 01-MAY-08:09 |
June | 0.164419E+11 | 17339.43 | 01-JUN-16:30 | 0.700021E+10 | 4639.58 | 01-JUN-08:09 |
July | 0.161523E+11 | 18915.75 | 14-JUL-16:00 | 0.704724E+10 | 4639.58 | 01-JUL-09:09 |
August | 0.164674E+11 | 17339.43 | 01-AUG-16:40 | 0.724851E+10 | 4639.58 | 01-AUG-08:09 |
September | 0.155238E+11 | 18915.75 | 12-SEP-16:00 | 0.688804E+10 | 4639.58 | 01-SEP-08:09 |
October | 0.169335E+11 | 18915.75 | 02-OCT-16:40 | 0.707031E+10 | 4639.58 | 02-OCT-08:09 |
November | 0.176387E+11 | 18915.75 | 01-NOV-16:19 | 0.684509E+10 | 4639.58 | 01-NOV-08:09 |
December | 0.188162E+11 | 18915.75 | 01-DEC-15:50 | 0.704724E+10 | 4639.58 | 01-DEC-09:09 |
Annual Sum or Average | 0.202170E+12 | 0.839274E+11 | ||||
Minimum of Months | 0.155238E+11 | 17339.43 | 0.641452E+10 | 4639.58 | ||
Maximum of Months | 0.188162E+11 | 18915.75 | 0.724851E+10 | 4639.58 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.202570E+10 | 1782.39 | 02-JAN-09:09 | 0.443872E+10 | 2912.71 | 02-JAN-09:09 |
February | 0.184426E+10 | 1782.39 | 01-FEB-09:09 | 0.402701E+10 | 2912.71 | 01-FEB-09:09 |
March | 0.210616E+10 | 1782.39 | 01-MAR-09:09 | 0.455059E+10 | 2912.71 | 01-MAR-09:09 |
April | 0.198616E+10 | 1782.39 | 01-APR-09:09 | 0.432429E+10 | 2912.71 | 01-APR-09:09 |
May | 0.206593E+10 | 1782.39 | 01-MAY-08:09 | 0.449465E+10 | 2912.71 | 01-MAY-08:09 |
June | 0.203227E+10 | 1782.39 | 01-JUN-08:09 | 0.439471E+10 | 2912.71 | 01-JUN-08:09 |
July | 0.201982E+10 | 1782.39 | 01-JUL-09:09 | 0.442423E+10 | 2912.71 | 01-JUL-09:09 |
August | 0.210616E+10 | 1782.39 | 01-AUG-08:09 | 0.455059E+10 | 2912.71 | 01-AUG-08:09 |
September | 0.198616E+10 | 1782.39 | 01-SEP-08:09 | 0.432429E+10 | 2912.71 | 01-SEP-08:09 |
October | 0.202570E+10 | 1782.39 | 02-OCT-08:09 | 0.443872E+10 | 2912.71 | 02-OCT-08:09 |
November | 0.195769E+10 | 1782.39 | 01-NOV-08:09 | 0.429732E+10 | 2912.71 | 01-NOV-08:09 |
December | 0.201982E+10 | 1782.39 | 01-DEC-09:09 | 0.442423E+10 | 2912.71 | 01-DEC-09:09 |
Annual Sum or Average | 0.241758E+11 | 0.526893E+11 | ||||
Minimum of Months | 0.184426E+10 | 1782.39 | 0.402701E+10 | 2912.71 | ||
Maximum of Months | 0.210616E+10 | 1782.39 | 0.455059E+10 | 2912.71 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.196268E+10 | 1725.71 | 02-JAN-09:09 | 0.666220E+09 | 437.18 | 02-JAN-09:09 |
February | 0.178687E+10 | 1725.71 | 01-FEB-09:09 | 0.604426E+09 | 437.18 | 01-FEB-09:09 |
March | 0.204057E+10 | 1725.71 | 01-MAR-09:09 | 0.683011E+09 | 437.18 | 01-MAR-09:09 |
April | 0.192434E+10 | 1725.71 | 01-APR-09:09 | 0.649045E+09 | 437.18 | 01-APR-09:09 |
May | 0.200162E+10 | 1725.71 | 01-MAY-08:09 | 0.674616E+09 | 437.18 | 01-MAY-08:09 |
June | 0.196898E+10 | 1725.71 | 01-JUN-08:09 | 0.659615E+09 | 437.18 | 01-JUN-08:09 |
July | 0.195698E+10 | 1725.71 | 01-JUL-09:09 | 0.664046E+09 | 437.18 | 01-JUL-09:09 |
August | 0.204057E+10 | 1725.71 | 01-AUG-08:09 | 0.683011E+09 | 437.18 | 01-AUG-08:09 |
September | 0.192434E+10 | 1725.71 | 01-SEP-08:09 | 0.649045E+09 | 437.18 | 01-SEP-08:09 |
October | 0.196268E+10 | 1725.71 | 02-OCT-08:09 | 0.666220E+09 | 437.18 | 02-OCT-08:09 |
November | 0.189680E+10 | 1725.71 | 01-NOV-08:09 | 0.644998E+09 | 437.18 | 01-NOV-08:09 |
December | 0.195698E+10 | 1725.71 | 01-DEC-09:09 | 0.664046E+09 | 437.18 | 01-DEC-09:09 |
Annual Sum or Average | 0.234234E+11 | 0.790830E+10 | ||||
Minimum of Months | 0.178687E+10 | 1725.71 | 0.604426E+09 | 437.18 | ||
Maximum of Months | 0.204057E+10 | 1725.71 | 0.683011E+09 | 437.18 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 6919213.84 | 2.58 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 6249612.50 | 2.58 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 6919213.84 | 2.58 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 6696013.39 | 2.58 | 01-APR-00:10 | 0.00 | 0.00 |
May | 6919213.84 | 2.58 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 6696013.39 | 2.58 | 01-JUN-00:10 | 0.00 | 0.00 |
July | 6919213.84 | 2.58 | 01-JUL-00:10 | 0.00 | 0.00 |
August | 6919213.84 | 2.58 | 01-AUG-00:10 | 0.00 | 0.00 |
September | 6696013.39 | 2.58 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 6919213.84 | 2.58 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 6696013.39 | 2.58 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 6919213.84 | 2.58 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 81468162.94 | ||||
Minimum of Months | 6249612.50 | 2.58 | 0.00 | 0.00 | |
Maximum of Months | 6919213.84 | 2.58 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.235462E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3869042.46 | 0.336738E+09 |
February | 0.479114E+10 | 0.214299E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26305217.29 | 0.343202E+09 |
March | 0.548013E+10 | 0.244478E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87963928.14 | 0.199526E+09 |
April | 0.518069E+10 | 0.230724E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185064E+09 | 0.120603E+09 |
May | 0.536353E+10 | 0.239970E+10 | 0.424576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404804E+09 | 27472232.10 |
June | 0.528933E+10 | 0.235921E+10 | 0.415135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523902E+09 | 14399533.20 |
July | 0.525489E+10 | 0.234773E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704681E+09 | 166471.34 |
August | 0.548013E+10 | 0.244478E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729853E+09 | 106335.27 |
September | 0.518069E+10 | 0.230724E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477735E+09 | 8723651.85 |
October | 0.524694E+10 | 0.235462E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287727E+09 | 36037064.46 |
November | 0.504819E+10 | 0.227595E+10 | 0.405935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127604E+09 | 0.117774E+09 |
December | 0.525489E+10 | 0.234773E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20717758.01 | 0.265123E+09 |
Annual Sum or Average | 0.628175E+11 | 0.280866E+11 | 0.497716E+11 | 0.358023E+10 | 0.146987E+10 | ||||
Minimum of Months | 0.479114E+10 | 0.214299E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3869042.46 | 106335.27 |
Maximum of Months | 0.548013E+10 | 0.244478E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729853E+09 | 0.343202E+09 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.185158E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3162977.35 | 0.302657E+09 |
February | 0.201852E+11 | 0.162141E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21690125.74 | 0.304925E+09 |
March | 0.230879E+11 | 0.168263E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72172523.25 | 0.172152E+09 |
April | 0.218263E+11 | 0.158688E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154953E+09 | 95904787.32 |
May | 0.225967E+11 | 0.167708E+11 | 0.715941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352673E+09 | 16386276.04 |
June | 0.222841E+11 | 0.164419E+11 | 0.700021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464043E+09 | 4575860.14 |
July | 0.221389E+11 | 0.161523E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621556E+09 | 0.00 |
August | 0.230879E+11 | 0.164674E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632976E+09 | 0.00 |
September | 0.218263E+11 | 0.155238E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417353E+09 | 3582902.01 |
October | 0.221054E+11 | 0.169335E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248051E+09 | 23826900.42 |
November | 0.212681E+11 | 0.176387E+11 | 0.684509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106665E+09 | 96865497.47 |
December | 0.221389E+11 | 0.188162E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17037802.89 | 0.232450E+09 |
Annual Sum or Average | 0.264651E+12 | 0.202170E+12 | 0.839274E+11 | 0.311233E+10 | 0.125333E+10 | ||||
Minimum of Months | 0.201852E+11 | 0.155238E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3162977.35 | 0.00 |
Maximum of Months | 0.230879E+11 | 0.188162E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632976E+09 | 0.304925E+09 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.202570E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1674368.60 | 0.178180E+09 |
February | 0.190200E+10 | 0.184426E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11161673.59 | 0.182425E+09 |
March | 0.217552E+10 | 0.210616E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36503362.92 | 0.108776E+09 |
April | 0.205665E+10 | 0.198616E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78430325.54 | 64179138.35 |
May | 0.212923E+10 | 0.206593E+10 | 0.449465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172005E+09 | 14967855.24 |
June | 0.209978E+10 | 0.203227E+10 | 0.439471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224741E+09 | 7304934.83 |
July | 0.208610E+10 | 0.201982E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303927E+09 | 134734.70 |
August | 0.217552E+10 | 0.210616E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314682E+09 | 71014.50 |
September | 0.205665E+10 | 0.198616E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199913E+09 | 8450782.07 |
October | 0.208295E+10 | 0.202570E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115705E+09 | 33120921.44 |
November | 0.200405E+10 | 0.195769E+10 | 0.429732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51783690.72 | 77956112.29 |
December | 0.208610E+10 | 0.201982E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8924752.90 | 0.143143E+09 |
Annual Sum or Average | 0.249375E+11 | 0.241758E+11 | 0.526893E+11 | 0.151945E+10 | 0.818710E+09 | ||||
Minimum of Months | 0.190200E+10 | 0.184426E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1674368.60 | 71014.50 |
Maximum of Months | 0.217552E+10 | 0.210616E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314682E+09 | 0.182425E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.196268E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1674569.45 | 0.166663E+09 |
February | 0.190200E+10 | 0.178687E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11185324.95 | 0.168555E+09 |
March | 0.217552E+10 | 0.204057E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36999129.72 | 96855087.94 |
April | 0.205665E+10 | 0.192434E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79118000.82 | 55135265.96 |
May | 0.212923E+10 | 0.200162E+10 | 0.674616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175220E+09 | 10929410.61 |
June | 0.209978E+10 | 0.196898E+10 | 0.659615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230587E+09 | 4180028.52 |
July | 0.208610E+10 | 0.195698E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305403E+09 | 28576.48 |
August | 0.217552E+10 | 0.204057E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315316E+09 | 56481.54 |
September | 0.205665E+10 | 0.192434E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201146E+09 | 6585898.91 |
October | 0.208295E+10 | 0.196268E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116840E+09 | 27345144.01 |
November | 0.200405E+10 | 0.189680E+10 | 0.644998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52308421.00 | 68650266.62 |
December | 0.208610E+10 | 0.195698E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8931213.52 | 0.132296E+09 |
Annual Sum or Average | 0.249375E+11 | 0.234234E+11 | 0.790830E+10 | 0.153473E+10 | 0.737281E+09 | ||||
Minimum of Months | 0.190200E+10 | 0.178687E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1674569.45 | 28576.48 |
Maximum of Months | 0.217552E+10 | 0.204057E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315316E+09 | 0.168555E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345679.45 | 0.775246E+09 |
February | 0.00 | 6249612.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23067227.70 | 0.571505E+09 |
March | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111580E+09 | 0.365886E+09 |
April | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328414E+09 | 91702337.18 |
May | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796528E+09 | 12557439.14 |
June | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924746E+09 | 9817622.00 |
July | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108788E+10 | 478887.19 |
August | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998684E+09 | 757039.36 |
September | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631769E+09 | 13162191.94 |
October | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262588E+09 | 59789894.14 |
November | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29339445.40 | 0.251613E+09 |
December | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5941768.38 | 0.632615E+09 |
Annual Sum or Average | 0.00 | 81468162.94 | 0.520088E+10 | 0.278513E+10 | |||||
Minimum of Months | 0.00 | 6249612.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345679.45 | 478887.19 |
Maximum of Months | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108788E+10 | 0.775246E+09 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2023.29 | 02-JAN-09:09 | 2751.42 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 111.74 | 29-JAN-12:00 | 895.98 | 18-JAN-04:00 |
February | 5888.82 | 01-FEB-15:09 | 2023.29 | 01-FEB-09:09 | 2751.42 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 414.25 | 05-FEB-19:02 | 846.80 | 10-FEB-23:00 |
March | 5888.82 | 01-MAR-15:09 | 2023.29 | 01-MAR-09:09 | 2751.42 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 725.37 | 02-MAR-06:00 | 706.27 | 17-MAR-21:30 |
April | 5888.82 | 01-APR-10:09 | 2023.29 | 01-APR-09:09 | 2751.42 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 668.66 | 28-APR-13:20 | 632.92 | 05-APR-01:00 |
May | 5888.82 | 01-MAY-14:09 | 2023.29 | 01-MAY-08:09 | 2751.42 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1841.63 | 21-MAY-13:00 | 260.35 | 15-MAY-03:00 |
June | 5888.82 | 01-JUN-14:09 | 2023.29 | 01-JUN-08:09 | 2751.42 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1188.34 | 09-JUN-04:16 | 320.15 | 06-JUN-04:00 |
July | 5888.82 | 01-JUL-10:09 | 2023.29 | 01-JUL-09:09 | 2751.42 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1411.92 | 30-JUL-18:01 | 33.97 | 03-JUL-04:00 |
August | 5888.82 | 01-AUG-14:09 | 2023.29 | 01-AUG-08:09 | 2751.42 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2208.05 | 16-AUG-20:01 | 24.97 | 31-AUG-03:55 |
September | 5888.82 | 01-SEP-14:09 | 2023.29 | 01-SEP-08:09 | 2751.42 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1445.51 | 04-SEP-18:01 | 159.73 | 27-SEP-03:00 |
October | 5888.82 | 02-OCT-14:09 | 2023.29 | 02-OCT-08:09 | 2751.42 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 973.07 | 09-OCT-18:01 | 395.59 | 20-OCT-04:00 |
November | 5888.82 | 01-NOV-14:09 | 2023.29 | 01-NOV-08:09 | 2751.42 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 594.07 | 19-NOV-19:02 | 461.68 | 22-NOV-04:00 |
December | 5888.82 | 01-DEC-15:09 | 2023.29 | 01-DEC-09:09 | 2751.42 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 128.88 | 10-DEC-13:00 | 645.20 | 16-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 111.74 | 24.97 | |||||
Maximum of Months | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2208.05 | 895.98 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 18915.75 | 02-JAN-15:00 | 4639.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.47 | 29-JAN-12:00 | 874.96 | 18-JAN-04:00 |
February | 24809.68 | 01-FEB-15:09 | 18915.75 | 01-FEB-16:30 | 4639.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 342.34 | 05-FEB-19:02 | 782.48 | 10-FEB-23:00 |
March | 24809.68 | 01-MAR-15:09 | 18915.75 | 01-MAR-16:49 | 4639.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 440.85 | 02-MAR-04:00 | 633.64 | 17-MAR-22:00 |
April | 24809.68 | 01-APR-10:09 | 18915.75 | 01-APR-16:00 | 4639.58 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 547.28 | 28-APR-13:20 | 529.41 | 05-APR-01:00 |
May | 24809.68 | 01-MAY-14:09 | 17339.43 | 01-MAY-16:30 | 4639.58 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1507.48 | 21-MAY-13:00 | 171.16 | 01-MAY-05:00 |
June | 24809.68 | 01-JUN-14:09 | 17339.43 | 01-JUN-16:30 | 4639.58 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 935.91 | 09-JUN-20:01 | 197.74 | 07-JUN-05:00 |
July | 24809.68 | 01-JUL-10:09 | 18915.75 | 14-JUL-16:00 | 4639.58 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.18 | 30-JUL-18:01 | 0.00 | 01-JUL-00:10 |
August | 24809.68 | 01-AUG-14:09 | 17339.43 | 01-AUG-16:40 | 4639.58 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1830.33 | 16-AUG-20:01 | 0.00 | 01-AUG-00:05 |
September | 24809.68 | 01-SEP-14:09 | 18915.75 | 12-SEP-16:00 | 4639.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.16 | 04-SEP-18:01 | 144.81 | 25-SEP-05:00 |
October | 24809.68 | 02-OCT-14:09 | 18915.75 | 02-OCT-16:40 | 4639.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 806.05 | 09-OCT-18:01 | 324.44 | 20-OCT-05:00 |
November | 24809.68 | 01-NOV-14:09 | 18915.75 | 01-NOV-16:19 | 4639.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 491.82 | 19-NOV-19:02 | 429.49 | 22-NOV-05:55 |
December | 24809.68 | 01-DEC-15:09 | 18915.75 | 01-DEC-15:50 | 4639.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.49 | 10-DEC-13:00 | 588.43 | 16-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 17339.43 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 91.47 | 0.00 | |||||
Maximum of Months | 24809.68 | 18915.75 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1830.33 | 874.96 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1782.39 | 02-JAN-09:09 | 2912.71 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.43 | 29-JAN-12:00 | 519.17 | 18-JAN-04:00 |
February | 2337.76 | 01-FEB-15:09 | 1782.39 | 01-FEB-09:09 | 2912.71 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 169.02 | 05-FEB-19:02 | 464.63 | 10-FEB-23:00 |
March | 2337.76 | 01-MAR-15:09 | 1782.39 | 01-MAR-09:09 | 2912.71 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 314.33 | 02-MAR-06:00 | 417.72 | 17-MAR-21:30 |
April | 2337.76 | 01-APR-10:09 | 1782.39 | 01-APR-09:09 | 2912.71 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 289.73 | 28-APR-13:20 | 302.23 | 05-APR-01:00 |
May | 2337.76 | 01-MAY-14:09 | 1782.39 | 01-MAY-08:09 | 2912.71 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 798.02 | 21-MAY-13:00 | 120.49 | 15-MAY-03:00 |
June | 2337.76 | 01-JUN-14:09 | 1782.39 | 01-JUN-08:09 | 2912.71 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 514.91 | 09-JUN-04:20 | 144.58 | 06-JUN-04:00 |
July | 2337.76 | 01-JUL-10:09 | 1782.39 | 01-JUL-09:09 | 2912.71 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 607.34 | 30-JUL-18:01 | 16.07 | 02-JUL-05:00 |
August | 2337.76 | 01-AUG-14:09 | 1782.39 | 01-AUG-08:09 | 2912.71 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 949.81 | 16-AUG-20:01 | 18.98 | 27-AUG-06:00 |
September | 2337.76 | 01-SEP-14:09 | 1782.39 | 01-SEP-08:09 | 2912.71 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.79 | 04-SEP-18:01 | 111.95 | 27-SEP-03:00 |
October | 2337.76 | 02-OCT-14:09 | 1782.39 | 02-OCT-08:09 | 2912.71 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 414.17 | 09-OCT-18:01 | 218.67 | 20-OCT-04:00 |
November | 2337.76 | 01-NOV-14:09 | 1782.39 | 01-NOV-08:09 | 2912.71 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 246.38 | 19-NOV-19:02 | 233.89 | 22-NOV-04:00 |
December | 2337.76 | 01-DEC-15:09 | 1782.39 | 01-DEC-09:09 | 2912.71 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.85 | 10-DEC-13:00 | 295.44 | 16-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1782.39 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 48.43 | 16.07 | |||||
Maximum of Months | 2337.76 | 1782.39 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 949.81 | 519.17 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1725.71 | 02-JAN-09:09 | 437.18 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.43 | 29-JAN-12:00 | 473.60 | 18-JAN-04:00 |
February | 2337.76 | 01-FEB-15:09 | 1725.71 | 01-FEB-09:09 | 437.18 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 170.86 | 05-FEB-19:02 | 423.98 | 10-FEB-23:00 |
March | 2337.76 | 01-MAR-15:09 | 1725.71 | 01-MAR-09:09 | 437.18 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 314.33 | 02-MAR-06:00 | 370.76 | 17-MAR-21:30 |
April | 2337.76 | 01-APR-10:09 | 1725.71 | 01-APR-09:09 | 437.18 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 289.73 | 28-APR-13:20 | 274.11 | 05-APR-01:00 |
May | 2337.76 | 01-MAY-14:09 | 1725.71 | 01-MAY-08:09 | 437.18 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 798.02 | 21-MAY-13:00 | 103.36 | 15-MAY-03:00 |
June | 2337.76 | 01-JUN-14:09 | 1725.71 | 01-JUN-08:09 | 437.18 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 520.73 | 09-JUN-04:10 | 118.00 | 06-JUN-04:00 |
July | 2337.76 | 01-JUL-10:09 | 1725.71 | 01-JUL-09:09 | 437.18 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 608.49 | 30-JUL-18:01 | 10.89 | 03-JUL-04:00 |
August | 2337.76 | 01-AUG-14:09 | 1725.71 | 01-AUG-08:09 | 437.18 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 952.37 | 16-AUG-20:01 | 14.12 | 31-AUG-03:55 |
September | 2337.76 | 01-SEP-14:09 | 1725.71 | 01-SEP-08:09 | 437.18 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 621.93 | 04-SEP-18:01 | 94.21 | 27-SEP-03:00 |
October | 2337.76 | 02-OCT-14:09 | 1725.71 | 02-OCT-08:09 | 437.18 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 415.40 | 09-OCT-18:01 | 195.52 | 20-OCT-04:00 |
November | 2337.76 | 01-NOV-14:09 | 1725.71 | 01-NOV-08:09 | 437.18 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 248.48 | 19-NOV-19:02 | 215.72 | 22-NOV-04:00 |
December | 2337.76 | 01-DEC-15:09 | 1725.71 | 01-DEC-09:09 | 437.18 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.85 | 10-DEC-13:00 | 276.45 | 16-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1725.71 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 48.43 | 10.89 | |||||
Maximum of Months | 2337.76 | 1725.71 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 952.37 | 473.60 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.79 | 23-JAN-12:53 | 2499.83 | 09-JAN-08:61 |
February | 0.00 | 01-FEB-00:10 | 2.58 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 929.63 | 05-FEB-12:03 | 2599.26 | 20-FEB-12:02 |
March | 0.00 | 01-MAR-00:10 | 2.58 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4373.75 | 27-MAR-11:01 | 2072.00 | 31-MAR-07:01 |
April | 0.00 | 01-APR-00:10 | 2.58 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5471.81 | 28-APR-11:01 | 1624.39 | 01-APR-07:01 |
May | 0.00 | 01-MAY-00:10 | 2.58 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5330.80 | 09-MAY-11:01 | 1317.55 | 01-MAY-07:01 |
June | 0.00 | 01-JUN-00:10 | 2.58 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5899.57 | 12-JUN-11:01 | 1008.80 | 22-JUN-07:55 |
July | 0.00 | 01-JUL-00:10 | 2.58 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6919.71 | 21-JUL-11:01 | 227.39 | 20-JUL-10:53 |
August | 0.00 | 01-AUG-00:10 | 2.58 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6649.01 | 16-AUG-11:01 | 940.21 | 04-AUG-13:52 |
September | 0.00 | 01-SEP-00:10 | 2.58 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4517.35 | 26-SEP-11:01 | 810.82 | 25-SEP-07:02 |
October | 0.00 | 01-OCT-00:10 | 2.58 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2677.68 | 09-OCT-11:01 | 1529.03 | 29-OCT-07:01 |
November | 0.00 | 01-NOV-00:10 | 2.58 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.49 | 05-NOV-11:02 | 1617.03 | 22-NOV-08:61 |
December | 0.00 | 01-DEC-00:10 | 2.58 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 869.57 | 09-DEC-12:03 | 2991.88 | 15-DEC-12:01 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.79 | 227.39 | ||||
Maximum of Months | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6919.71 | 2991.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 42147.55 | 30-JAN-05:01 | 0.00 | 572.47 | 4235.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.55 |
February | 42690.36 | 08-FEB-05:01 | 0.00 | 654.26 | 4840.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.05 |
March | 57495.99 | 23-MAR-04:01 | 0.00 | 736.04 | 5445.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.37 |
April | 57376.55 | 29-APR-04:01 | 0.00 | 817.82 | 4538.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.03 |
May | 57377.57 | 11-MAY-04:01 | 0.00 | 817.82 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 39.55 | 0.00 |
June | 54212.73 | 01-JUN-04:01 | 0.00 | 817.82 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 |
July | 57524.08 | 04-JUL-06:01 | 0.00 | 817.82 | 4538.16 | 0.00 | 0.00 | 0.00 | 0.00 | 23.08 | 0.00 |
August | 51080.48 | 06-AUG-06:01 | 0.00 | 817.82 | 4538.16 | 0.00 | 0.00 | 0.00 | 0.00 | 157.62 | 0.00 |
September | 49394.59 | 02-SEP-04:01 | 0.00 | 817.82 | 4538.16 | 0.00 | 0.00 | 0.00 | 0.00 | 63.37 | 0.00 |
October | 53222.84 | 20-OCT-04:01 | 0.00 | 817.82 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.01 |
November | 52796.67 | 05-NOV-06:01 | 0.00 | 817.82 | 4538.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.45 |
December | 48876.77 | 01-DEC-05:01 | 0.00 | 572.47 | 4235.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.44 |
Annual Sum or Average | |||||||||||
Minimum of Months | 42147.55 | 0.00 | 572.47 | 4235.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57524.08 | 0.00 | 817.82 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 157.62 | 359.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 87820.34 | 29-JAN-09:03 | 9303.63 | 1033.65 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.09 |
February | 133558.68 | 06-FEB-07:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.30 |
March | 185295.53 | 23-MAR-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.32 |
April | 179842.96 | 26-APR-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 |
May | 175614.85 | 11-MAY-05:01 | 0.00 | 2411.84 | 7142.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2.19 | 0.00 |
June | 159774.70 | 01-JUN-05:01 | 0.00 | 2756.39 | 8162.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4.07 | 0.00 |
July | 170396.17 | 04-JUL-07:01 | 0.00 | 2756.39 | 6121.98 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 | 0.00 |
August | 150537.24 | 06-AUG-06:01 | 0.00 | 3445.49 | 7652.47 | 0.00 | 0.00 | 0.00 | 0.00 | 147.34 | 0.00 |
September | 143688.71 | 05-SEP-04:01 | 0.00 | 3445.49 | 10203.29 | 0.00 | 0.00 | 0.00 | 0.00 | 28.24 | 0.00 |
October | 165152.12 | 20-OCT-05:03 | 0.00 | 1378.20 | 4081.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.22 |
November | 159798.20 | 19-NOV-09:02 | 15506.05 | 1722.75 | 7732.63 | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 0.00 |
December | 139950.33 | 12-DEC-07:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.90 |
Annual Sum or Average | |||||||||||
Minimum of Months | 87820.34 | 0.00 | 1033.65 | 4081.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 185295.53 | 15506.05 | 3445.49 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 147.34 | 50.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26217.80 | 30-JAN-05:01 | 0.00 | 227.26 | 4483.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.32 |
February | 26657.77 | 28-FEB-05:02 | 0.00 | 194.80 | 3843.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.21 |
March | 33046.32 | 23-MAR-04:01 | 0.00 | 292.19 | 5765.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.16 |
April | 32988.30 | 29-APR-04:01 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 |
May | 32547.30 | 05-MAY-04:01 | 0.00 | 324.66 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 |
June | 29814.15 | 02-JUN-04:01 | 0.00 | 324.66 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 |
July | 32020.69 | 04-JUL-06:01 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 0.00 |
August | 27857.32 | 06-AUG-06:01 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 74.30 | 0.00 |
September | 28490.58 | 26-SEP-04:01 | 0.00 | 324.66 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.82 |
October | 31452.03 | 21-OCT-04:01 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.80 |
November | 31244.94 | 05-NOV-06:01 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.35 |
December | 29632.48 | 01-DEC-05:01 | 0.00 | 227.26 | 4483.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 26217.80 | 0.00 | 194.80 | 3843.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33046.32 | 0.00 | 324.66 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 74.30 | 159.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22998.09 | 23-JAN-05:02 | 0.00 | 194.80 | 576.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.71 |
February | 22312.27 | 24-FEB-05:01 | 0.00 | 227.26 | 673.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.60 |
March | 29984.86 | 23-MAR-04:01 | 0.00 | 292.19 | 865.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.01 |
April | 29217.12 | 29-APR-04:01 | 0.00 | 324.66 | 721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 |
May | 29237.83 | 11-MAY-04:01 | 0.00 | 324.66 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 21.37 | 0.00 |
June | 26867.57 | 01-JUN-04:01 | 0.00 | 324.66 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 28605.26 | 04-JUL-06:01 | 0.00 | 324.66 | 721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 13.78 | 0.00 |
August | 24959.32 | 06-AUG-06:01 | 0.00 | 324.66 | 721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 74.01 | 0.00 |
September | 24929.67 | 26-SEP-04:01 | 0.00 | 324.66 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 |
October | 27783.92 | 21-OCT-04:01 | 0.00 | 324.66 | 721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.38 |
November | 27722.98 | 05-NOV-06:01 | 0.00 | 324.66 | 721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 |
December | 26034.46 | 01-DEC-05:01 | 0.00 | 227.26 | 673.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.97 |
Annual Sum or Average | |||||||||||
Minimum of Months | 22312.27 | 0.00 | 194.80 | 576.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29984.86 | 0.00 | 324.66 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 74.01 | 148.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.30 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.19 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.77 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 |
June | 0.00 | 01-JUN-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 | 0.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 | 0.00 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 | 0.00 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.57 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 | 20.14 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.757029E+11 | 68615.93 | 30-JAN-15:50 | 0.742904E+10 | 4860.62 | 13-JAN-12:09 |
February | 0.743748E+11 | 80554.27 | 07-FEB-15:00 | 0.666782E+10 | 4855.17 | 01-FEB-12:39 |
March | 0.903331E+11 | 85202.22 | 27-MAR-15:00 | 0.728630E+10 | 4830.77 | 01-MAR-12:00 |
April | 0.101367E+12 | 95075.69 | 29-APR-15:00 | 0.683582E+10 | 4785.63 | 03-APR-11:09 |
May | 0.130943E+12 | 116016.02 | 31-MAY-14:20 | 0.687740E+10 | 4744.16 | 01-MAY-11:00 |
June | 0.146726E+12 | 125879.10 | 09-JUN-14:09 | 0.654522E+10 | 4706.40 | 01-JUN-11:39 |
July | 0.168423E+12 | 138385.01 | 20-JUL-13:30 | 0.668227E+10 | 4688.07 | 31-JUL-11:50 |
August | 0.177685E+12 | 144484.53 | 10-AUG-15:00 | 0.678185E+10 | 4712.41 | 31-AUG-11:20 |
September | 0.146932E+12 | 127495.78 | 07-SEP-14:00 | 0.668159E+10 | 4749.60 | 29-SEP-11:39 |
October | 0.125554E+12 | 115161.84 | 07-OCT-15:00 | 0.706664E+10 | 4797.04 | 31-OCT-11:00 |
November | 0.102075E+12 | 97406.81 | 01-NOV-15:30 | 0.700948E+10 | 4836.15 | 30-NOV-12:30 |
December | 0.855014E+11 | 79602.15 | 05-DEC-15:00 | 0.738471E+10 | 4857.56 | 28-DEC-12:20 |
Annual Sum or Average | 0.142562E+13 | 0.832481E+11 | ||||
Minimum of Months | 0.743748E+11 | 68615.93 | 0.654522E+10 | 4688.07 | ||
Maximum of Months | 0.177685E+12 | 144484.53 | 0.742904E+10 | 4860.62 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.248657E+11 | 0.379188E+10 | 0.163682E+11 | 0.00 | 0.133309E+11 | 0.00 | 0.00 | 0.173462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.219945E+11 | 0.324588E+10 | 0.148500E+11 | 0.00 | 0.121210E+11 | 0.00 | 0.00 | 0.221634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234247E+11 | 0.333273E+10 | 0.167807E+11 | 0.00 | 0.136274E+11 | 0.00 | 0.00 | 0.331676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.220933E+11 | 0.294778E+10 | 0.159462E+11 | 0.00 | 0.132031E+11 | 0.00 | 0.00 | 0.471764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232450E+11 | 0.282300E+10 | 0.165744E+11 | 0.00 | 0.148380E+11 | 0.00 | 0.00 | 0.734629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.228091E+11 | 0.262819E+10 | 0.162059E+11 | 0.00 | 0.169139E+11 | 0.00 | 0.00 | 0.881689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.224837E+11 | 0.275423E+10 | 0.163148E+11 | 0.00 | 0.202388E+11 | 0.00 | 0.00 | 0.106632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.230658E+11 | 0.294639E+10 | 0.167807E+11 | 0.00 | 0.215709E+11 | 0.00 | 0.00 | 0.113321E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.217483E+11 | 0.310353E+10 | 0.159462E+11 | 0.00 | 0.172120E+11 | 0.00 | 0.00 | 0.889224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.232834E+11 | 0.348241E+10 | 0.163682E+11 | 0.00 | 0.143867E+11 | 0.00 | 0.00 | 0.680329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.237758E+11 | 0.360719E+10 | 0.158468E+11 | 0.00 | 0.130485E+11 | 0.00 | 0.00 | 0.457965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251476E+11 | 0.386268E+10 | 0.163148E+11 | 0.00 | 0.133879E+11 | 0.00 | 0.00 | 0.267884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277937E+12 | 0.385259E+11 | 0.194297E+12 | 0.183879E+12 | 0.00 | 0.730979E+12 | |||||||
Minimum of Months | 0.217483E+11 | 0.262819E+10 | 0.148500E+11 | 0.00 | 0.121210E+11 | 0.00 | 0.00 | 0.173462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251476E+11 | 0.386268E+10 | 0.167807E+11 | 0.00 | 0.215709E+11 | 0.00 | 0.00 | 0.113321E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 1910566.15 | 0.00 | 0.742713E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.666782E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.728630E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.683582E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.687740E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.654522E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.668227E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.678185E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.668159E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.706664E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.700948E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.738471E+10 | 0.00 | 0.00 |
Annual Sum or Average | 1910566.15 | 0.832462E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.654522E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 1910566.15 | 0.00 | 0.742713E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 24449.72 | 02-JAN-15:00 | 3371.20 | 01-JAN-06:10 | 10740.89 | 02-JAN-09:09 | 0.00 | 9329.66 | 29-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 24449.72 | 01-FEB-16:30 | 3371.20 | 01-FEB-06:10 | 10740.89 | 01-FEB-09:09 | 0.00 | 10733.84 | 09-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 24449.72 | 01-MAR-16:49 | 3371.20 | 01-MAR-06:10 | 10740.89 | 01-MAR-09:09 | 0.00 | 10481.75 | 15-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 24449.72 | 01-APR-16:00 | 3371.20 | 01-APR-05:10 | 10740.89 | 01-APR-09:09 | 0.00 | 11780.60 | 30-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 22873.41 | 01-MAY-16:30 | 3371.20 | 01-MAY-05:10 | 10740.89 | 01-MAY-08:09 | 0.00 | 13667.30 | 31-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 22873.41 | 01-JUN-16:30 | 3371.20 | 01-JUN-05:10 | 10740.89 | 01-JUN-08:09 | 0.00 | 15237.07 | 10-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 24449.72 | 14-JUL-16:00 | 3371.20 | 01-JUL-05:10 | 10740.89 | 01-JUL-09:09 | 0.00 | 17684.72 | 20-JUL-14:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 22873.41 | 01-AUG-16:40 | 3371.20 | 01-AUG-05:10 | 10740.89 | 01-AUG-08:09 | 0.00 | 18292.93 | 10-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 24449.72 | 12-SEP-16:00 | 3371.20 | 01-SEP-05:10 | 10740.89 | 01-SEP-08:09 | 0.00 | 16332.75 | 07-SEP-14:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 24449.72 | 02-OCT-16:40 | 3371.20 | 01-OCT-05:10 | 10740.89 | 02-OCT-08:09 | 0.00 | 13788.51 | 08-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 24449.72 | 01-NOV-16:19 | 3371.20 | 01-NOV-05:10 | 10740.89 | 01-NOV-08:09 | 0.00 | 11780.60 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 24449.72 | 01-DEC-15:50 | 3371.20 | 01-DEC-06:10 | 10740.89 | 01-DEC-09:09 | 0.00 | 10566.22 | 11-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 22873.41 | 3371.20 | 10740.89 | 0.00 | 9329.66 | 0.00 | 0.00 | |||||
Maximum of Months | 24449.72 | 3371.20 | 10740.89 | 0.00 | 18292.93 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 25108.33 | 30-JAN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38622.98 | 07-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43674.96 | 27-MAR-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 57035.20 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71961.60 | 31-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80511.78 | 09-JUN-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88752.43 | 20-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 95729.93 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81923.25 | 07-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 68433.29 | 07-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 55447.22 | 01-NOV-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36094.55 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 25108.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95729.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 68615.93 | 30-JAN-15:50 | 24449.72 | 10740.89 | 0.00 | 0.00 | 8317.00 | 0.00 | 0.00 | 25108.33 | 0.00 |
February | 80554.27 | 07-FEB-15:00 | 22873.41 | 10740.89 | 0.00 | 0.00 | 8317.00 | 0.00 | 0.00 | 38622.98 | 0.00 |
March | 85202.22 | 27-MAR-15:00 | 22873.41 | 10740.89 | 0.00 | 0.00 | 8317.00 | 0.00 | 0.00 | 43270.93 | 0.00 |
April | 95075.69 | 29-APR-15:00 | 21297.09 | 10740.89 | 0.00 | 0.00 | 9553.96 | 0.00 | 0.00 | 53483.74 | 0.00 |
May | 116016.02 | 31-MAY-14:20 | 19720.78 | 10740.89 | 0.00 | 0.00 | 13592.75 | 0.00 | 0.00 | 71961.60 | 0.00 |
June | 125879.10 | 09-JUN-14:09 | 19720.78 | 10740.89 | 0.00 | 0.00 | 14905.66 | 0.00 | 0.00 | 80511.78 | 0.00 |
July | 138385.01 | 20-JUL-13:30 | 21297.09 | 10740.89 | 0.00 | 0.00 | 17594.60 | 0.00 | 0.00 | 88752.43 | 0.00 |
August | 144484.53 | 10-AUG-15:00 | 19720.78 | 10740.89 | 0.00 | 0.00 | 18292.93 | 0.00 | 0.00 | 95729.93 | 0.00 |
September | 127495.78 | 07-SEP-14:00 | 19720.78 | 10740.89 | 0.00 | 0.00 | 16245.83 | 0.00 | 0.00 | 80788.29 | 0.00 |
October | 115161.84 | 07-OCT-15:00 | 22873.41 | 10740.89 | 0.00 | 0.00 | 13371.99 | 0.00 | 0.00 | 68175.55 | 0.00 |
November | 97406.81 | 01-NOV-15:30 | 22873.41 | 10740.89 | 0.00 | 0.00 | 10199.45 | 0.00 | 0.00 | 53593.07 | 0.00 |
December | 79602.15 | 05-DEC-15:00 | 24449.72 | 10740.89 | 0.00 | 0.00 | 8317.00 | 0.00 | 0.00 | 36094.55 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 68615.93 | 19720.78 | 10740.89 | 0.00 | 0.00 | 8317.00 | 0.00 | 0.00 | 25108.33 | 0.00 | |
Maximum of Months | 144484.53 | 24449.72 | 10740.89 | 0.00 | 0.00 | 18292.93 | 0.00 | 0.00 | 95729.93 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 788.71 | 01-JAN-08:09 | 0.00 | 4860.62 | 13-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 4855.17 | 01-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 4830.77 | 01-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 4785.63 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4744.16 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4706.40 | 01-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4688.07 | 31-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4712.41 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4749.60 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 4797.04 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 4836.15 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 4857.56 | 28-DEC-12:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4688.07 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 788.71 | 0.00 | 4860.62 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.59 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.67 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 25.10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 25.58 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 26.11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 26.17 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 25.37 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 24.87 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.57 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 80.00 | 25.59 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 26.17 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.18 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.00 | 0.17 | 24.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.17 | 26.05 | 0.17 | 24.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.18 | 0.17 | 24.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.52 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.58 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.68 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.75 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 25.70 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 26.23 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.29 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 27.17 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 24.84 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.51 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 112.50 | 26.41 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.51 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 27.29 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.51 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.66 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.66 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 24.96 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 25.27 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.07 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 26.32 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 25.92 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 25.24 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.77 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 80.33 | 25.59 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 26.32 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 208.50 | 23.49 | 23.67 | 23.89 | 0.00 | 0.00 |
February | 82.33 | 23.53 | 76.67 | 23.89 | 0.00 | 0.00 |
March | 40.17 | 23.75 | 190.17 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 347.67 | 23.89 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 418.00 | 23.89 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 408.00 | 23.89 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 415.00 | 23.89 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 422.00 | 23.89 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 405.00 | 23.89 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 411.17 | 23.89 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 359.00 | 23.89 | 0.00 | 0.00 |
December | 73.17 | 23.62 | 163.00 | 23.89 | 4.67 | 23.89 |
Annual Sum or Average | 404.17 | 23.55 | 3639.33 | 23.89 | 4.67 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 23.67 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 208.50 | 23.75 | 422.00 | 23.89 | 4.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 91.00 | 23.13 | 158.50 | 23.89 | 0.00 | 0.00 |
February | 30.67 | 23.06 | 230.50 | 23.89 | 0.00 | 0.00 |
March | 12.67 | 23.36 | 290.33 | 23.89 | 0.00 | 0.00 |
April | 0.33 | 24.03 | 381.67 | 23.89 | 0.33 | 24.03 |
May | 0.83 | 24.10 | 418.00 | 23.89 | 0.83 | 24.10 |
June | 9.00 | 23.98 | 408.00 | 23.89 | 9.00 | 23.98 |
July | 15.00 | 24.01 | 415.00 | 23.89 | 15.00 | 24.01 |
August | 17.00 | 23.99 | 422.00 | 23.90 | 17.00 | 23.99 |
September | 13.17 | 23.97 | 405.00 | 23.89 | 13.17 | 23.97 |
October | 14.67 | 23.94 | 411.33 | 23.89 | 14.67 | 23.94 |
November | 1.00 | 23.96 | 387.50 | 23.89 | 1.00 | 23.96 |
December | 31.83 | 23.32 | 275.83 | 23.89 | 5.50 | 23.88 |
Annual Sum or Average | 237.17 | 23.41 | 4203.67 | 23.89 | 76.50 | 23.97 |
Minimum of Months | 0.33 | 23.06 | 158.50 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 91.00 | 24.10 | 422.00 | 23.90 | 17.00 | 24.10 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 45.33 | 23.41 | 253.17 | 23.89 | 0.00 | 0.00 |
February | 19.50 | 23.44 | 298.17 | 23.89 | 0.00 | 0.00 |
March | 9.00 | 23.64 | 339.17 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 387.17 | 23.89 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 418.00 | 23.89 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 408.00 | 23.89 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 415.00 | 23.89 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 422.00 | 23.89 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 405.00 | 23.89 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 414.00 | 23.89 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 397.67 | 23.89 | 0.00 | 0.00 |
December | 9.17 | 23.69 | 358.50 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 83.00 | 23.47 | 4515.83 | 23.89 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 253.17 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 45.33 | 23.69 | 422.00 | 23.89 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 65.17 | 22.98 | 222.67 | 23.89 | 0.00 | 0.00 |
February | 35.50 | 23.12 | 284.33 | 23.89 | 0.00 | 0.00 |
March | 21.33 | 23.38 | 313.33 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 375.83 | 23.89 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 418.00 | 23.89 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 408.00 | 23.89 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 415.00 | 23.89 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 422.00 | 23.89 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 405.00 | 23.89 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 414.00 | 23.89 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 396.33 | 23.89 | 0.00 | 0.00 |
December | 21.17 | 23.36 | 343.17 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 143.17 | 23.13 | 4417.67 | 23.89 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 222.67 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 65.17 | 23.38 | 422.00 | 23.89 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.67204 | 49.07402 | 0.27652 | 7.09834 |
February | 376.00000 | 23.80192 | 49.66914 | 0.36201 | 7.96453 |
March | 422.00000 | 23.87380 | 45.40450 | 0.41154 | 8.67795 |
April | 405.00000 | 23.88968 | 45.30484 | 0.50090 | 10.32456 |
May | 418.00000 | 23.88970 | 44.22717 | -0.1947 | 5.90342 |
June | 408.00000 | 23.88952 | 47.28879 | -0.1098 | 5.31463 |
July | 415.00000 | 23.88925 | 48.57719 | -0.0543 | 5.11506 |
August | 422.00000 | 23.88918 | 49.20626 | -0.0442 | 5.09132 |
September | 405.00000 | 23.88957 | 48.89920 | -0.1330 | 5.44702 |
October | 414.00000 | 23.88967 | 47.10176 | 0.58687 | 12.27634 |
November | 399.00000 | 23.88965 | 47.77293 | 0.49587 | 10.20120 |
December | 415.00000 | 23.83586 | 50.46031 | 0.38437 | 8.26639 |
Annual Sum or Average | 4913.00000 | 23.85861 | 47.73326 | 0.20481 | 7.62741 |
Minimum of Months | 376.00000 | 23.67204 | 44.22717 | -0.1947 | 5.09132 |
Maximum of Months | 422.00000 | 23.88970 | 50.46031 | 0.58687 | 12.27634 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.70623 | 46.99306 | 0.35432 | 8.01729 |
February | 376.00000 | 23.81292 | 48.75647 | 0.42680 | 8.98030 |
March | 422.00000 | 23.87377 | 45.64576 | 0.45686 | 9.48831 |
April | 405.00000 | 23.90532 | 47.33717 | 0.53220 | 11.00262 |
May | 418.00000 | 23.91340 | 48.23172 | -0.2076 | 6.00627 |
June | 408.00000 | 23.91432 | 53.63832 | -0.1374 | 5.47946 |
July | 415.00000 | 23.91612 | 56.04274 | -0.0905 | 5.25695 |
August | 422.00000 | 23.91599 | 57.14354 | -0.0777 | 5.19752 |
September | 405.00000 | 23.91502 | 56.10665 | -0.1387 | 5.48264 |
October | 414.00000 | 23.91402 | 52.00804 | 0.60760 | 12.83246 |
November | 399.00000 | 23.90420 | 50.64145 | 0.53568 | 11.07516 |
December | 415.00000 | 23.83826 | 50.30544 | 0.44444 | 9.28986 |
Annual Sum or Average | 4913.00000 | 23.87780 | 51.08415 | 0.22307 | 8.15886 |
Minimum of Months | 376.00000 | 23.70623 | 45.64576 | -0.2076 | 5.19752 |
Maximum of Months | 422.00000 | 23.91612 | 57.14354 | 0.60760 | 12.83246 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.82848 | 41.79262 | 0.43679 | 9.29299 |
February | 376.00000 | 23.86133 | 43.68325 | 0.48709 | 10.17168 |
March | 422.00000 | 23.88310 | 41.90538 | 0.50804 | 10.59341 |
April | 405.00000 | 23.88984 | 43.67662 | 0.57230 | 11.98483 |
May | 418.00000 | 23.88985 | 44.38657 | -0.1156 | 5.44106 |
June | 408.00000 | 23.88965 | 48.65005 | -0.0431 | 5.13834 |
July | 415.00000 | 23.88936 | 50.16430 | 0.02981 | 5.11079 |
August | 422.00000 | 23.88923 | 50.43488 | 0.06889 | 5.19637 |
September | 405.00000 | 23.88942 | 48.87828 | 0.01809 | 5.15964 |
October | 414.00000 | 23.88976 | 45.23975 | 0.71843 | 15.95508 |
November | 399.00000 | 23.88984 | 43.85251 | 0.63845 | 13.66986 |
December | 415.00000 | 23.88390 | 43.89204 | 0.51923 | 10.80118 |
Annual Sum or Average | 4913.00000 | 23.88126 | 45.56116 | 0.31766 | 9.01946 |
Minimum of Months | 376.00000 | 23.82848 | 41.79262 | -0.1156 | 5.11079 |
Maximum of Months | 422.00000 | 23.88985 | 50.43488 | 0.71843 | 15.95508 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.73187 | 44.03895 | 0.39999 | 8.85684 |
February | 376.00000 | 23.80837 | 46.08033 | 0.46015 | 9.73706 |
March | 422.00000 | 23.85980 | 43.70345 | 0.48260 | 10.11354 |
April | 405.00000 | 23.88964 | 45.14233 | 0.55425 | 11.55637 |
May | 418.00000 | 23.88979 | 45.17383 | -0.1460 | 5.61159 |
June | 408.00000 | 23.88958 | 49.65156 | -0.0726 | 5.21349 |
July | 415.00000 | 23.88937 | 50.96744 | 0.00247 | 5.09444 |
August | 422.00000 | 23.88924 | 51.19008 | 0.04133 | 5.13572 |
September | 405.00000 | 23.88940 | 49.76599 | -0.0100 | 5.15470 |
October | 414.00000 | 23.88966 | 46.13433 | 0.69892 | 15.36936 |
November | 399.00000 | 23.88973 | 45.15983 | 0.61877 | 13.14261 |
December | 415.00000 | 23.85689 | 46.19520 | 0.49694 | 10.37428 |
Annual Sum or Average | 4913.00000 | 23.86474 | 46.94131 | 0.29167 | 8.75842 |
Minimum of Months | 376.00000 | 23.73187 | 43.70345 | -0.1460 | 5.09444 |
Maximum of Months | 422.00000 | 23.88979 | 51.19008 | 0.69892 | 15.36936 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.743949E+10 | 0.203253E+10 | 337.38 | 0.554744E+10 | 0.189205E+10 | 0.00 | 1.00 | 30-JAN-05:01 | 0.00 | 01-JAN-00:10 | 66036.42 | 30-JAN-05:01 | 46164.19 | 30-JAN-05:01 | 19872.23 | 30-JAN-05:01 | 14185.73 | 30-JAN-05:01 | 0.00 | 01-JAN-00:10 |
February | 0.107671E+11 | 0.293319E+10 | 346.10 | 0.811115E+10 | 0.265596E+10 | 0.00 | 1.00 | 06-FEB-05:01 | 0.00 | 01-FEB-00:10 | 67961.10 | 09-FEB-05:01 | 46744.32 | 08-FEB-05:01 | 25287.44 | 09-FEB-05:02 | 14689.08 | 09-FEB-05:01 | 0.00 | 01-FEB-00:10 |
March | 0.179112E+11 | 0.491726E+10 | 437.16 | 0.144128E+11 | 0.349849E+10 | 0.00 | 1.00 | 01-MAR-05:01 | 0.00 | 01-MAR-00:10 | 67453.62 | 29-MAR-04:01 | 62146.05 | 28-MAR-04:01 | 21747.18 | 29-MAR-04:03 | 15499.98 | 02-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.272474E+11 | 0.751861E+10 | 453.56 | 0.221017E+11 | 0.514564E+10 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 67855.77 | 12-APR-04:01 | 62138.49 | 29-APR-04:01 | 23655.83 | 12-APR-04:03 | 14970.18 | 18-APR-04:01 | 0.00 | 01-APR-00:10 |
May | 0.447105E+11 | 0.124385E+11 | 474.28 | 0.370388E+11 | 0.767170E+10 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 70407.43 | 24-MAY-04:01 | 62949.40 | 11-MAY-04:01 | 28997.98 | 24-MAY-04:07 | 16168.64 | 23-MAY-04:01 | 0.00 | 01-MAY-00:10 |
June | 0.541070E+11 | 0.149330E+11 | 466.52 | 0.420854E+11 | 0.120216E+11 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:05 | 72277.72 | 19-JUN-04:01 | 59203.17 | 01-JUN-04:01 | 35929.64 | 19-JUN-04:07 | 16499.46 | 29-JUN-04:01 | 0.00 | 01-JUN-00:05 |
July | 0.637381E+11 | 0.180332E+11 | 514.93 | 0.486489E+11 | 0.150892E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 71737.62 | 05-JUL-04:01 | 63109.09 | 04-JUL-06:01 | 31758.17 | 05-JUL-04:10 | 16607.21 | 15-JUL-04:09 | 0.00 | 01-JUL-00:10 |
August | 0.667520E+11 | 0.188850E+11 | 528.46 | 0.503898E+11 | 0.163621E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:15 | 71867.93 | 08-AUG-04:11 | 57664.51 | 06-AUG-06:01 | 34282.38 | 23-AUG-04:08 | 17061.82 | 05-AUG-04:11 | 0.00 | 01-AUG-00:05 |
September | 0.526524E+11 | 0.142918E+11 | 463.26 | 0.391574E+11 | 0.134950E+11 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 71778.70 | 11-SEP-04:01 | 54701.25 | 02-SEP-04:01 | 32254.30 | 11-SEP-04:10 | 16549.21 | 13-SEP-04:01 | 0.00 | 01-SEP-00:10 |
October | 0.403341E+11 | 0.108669E+11 | 468.75 | 0.310483E+11 | 0.928587E+10 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 71395.64 | 02-OCT-04:01 | 56976.37 | 20-OCT-04:01 | 32967.52 | 08-OCT-06:06 | 15517.12 | 05-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.255821E+11 | 0.691121E+10 | 445.34 | 0.196014E+11 | 0.598068E+10 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 | 68832.17 | 03-NOV-04:01 | 56201.94 | 05-NOV-06:01 | 25500.10 | 03-NOV-04:12 | 15042.17 | 20-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.131253E+11 | 0.355296E+10 | 400.43 | 0.965614E+10 | 0.346919E+10 | 0.00 | 1.00 | 01-DEC-05:01 | 0.00 | 01-DEC-00:10 | 67105.60 | 11-DEC-05:01 | 52600.38 | 01-DEC-05:01 | 22456.86 | 06-DEC-05:01 | 14600.60 | 12-DEC-05:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.424367E+12 | 0.117314E+12 | 5336.15 | 0.327799E+12 | 0.965674E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.743949E+10 | 0.203253E+10 | 337.38 | 0.554744E+10 | 0.189205E+10 | 0.00 | 1.00 | 0.00 | 66036.42 | 46164.19 | 19872.23 | 14185.73 | 0.00 | |||||||
Maximum of Months | 0.667520E+11 | 0.188850E+11 | 528.46 | 0.503898E+11 | 0.163621E+11 | 0.00 | 1.00 | 0.00 | 72277.72 | 63109.09 | 35929.64 | 17061.82 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.381618E+11 | 0.111028E+11 | 346.73 | 0.278291E+11 | 0.103327E+11 | 0.00 | 0.63 | 30-JAN-15:40 | 0.00 | 01-JAN-00:10 | 150497.55 | 29-JAN-09:03 | 100785.55 | 29-JAN-09:03 | 49712.00 | 29-JAN-09:03 | 36384.00 | 29-JAN-09:03 | 0.00 | 01-JAN-00:10 |
February | 0.500125E+11 | 0.144372E+11 | 341.22 | 0.363525E+11 | 0.136600E+11 | 0.00 | 1.00 | 06-FEB-07:03 | 0.00 | 01-FEB-00:10 | 228724.81 | 09-FEB-07:02 | 149907.58 | 06-FEB-07:03 | 85710.93 | 09-FEB-07:02 | 54107.69 | 09-FEB-07:02 | 0.00 | 01-FEB-00:10 |
March | 0.748141E+11 | 0.217275E+11 | 402.65 | 0.574251E+11 | 0.173890E+11 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:10 | 228203.42 | 29-MAR-06:03 | 203951.59 | 23-MAR-06:02 | 91210.90 | 29-MAR-06:03 | 55465.13 | 02-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.106980E+12 | 0.310132E+11 | 408.39 | 0.815359E+11 | 0.254446E+11 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:10 | 233115.02 | 30-APR-08:62 | 200328.82 | 26-APR-06:02 | 101573.01 | 30-APR-08:04 | 55167.22 | 03-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.162113E+12 | 0.478400E+11 | 442.10 | 0.124749E+12 | 0.373637E+11 | 0.00 | 1.00 | 01-MAY-05:03 | 0.00 | 01-MAY-00:10 | 234045.72 | 24-MAY-05:02 | 198134.12 | 11-MAY-05:01 | 103068.15 | 01-MAY-06:04 | 61374.47 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.198114E+12 | 0.577508E+11 | 434.74 | 0.137358E+12 | 0.607559E+11 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:05 | 238991.30 | 25-JUN-08:62 | 182523.58 | 01-JUN-05:01 | 119058.41 | 25-JUN-08:06 | 62551.35 | 11-JUN-08:62 | 0.00 | 01-JUN-00:05 |
July | 0.234713E+12 | 0.693848E+11 | 449.46 | 0.156461E+12 | 0.782522E+11 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 239604.04 | 05-JUL-04:01 | 198642.12 | 04-JUL-07:01 | 120495.61 | 20-JUL-06:08 | 63500.12 | 23-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.248953E+12 | 0.733437E+11 | 458.67 | 0.162147E+12 | 0.868061E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:05 | 240484.93 | 08-AUG-06:03 | 183667.23 | 06-AUG-06:01 | 123489.17 | 08-AUG-06:08 | 64001.19 | 10-AUG-16:00 | 0.00 | 01-AUG-00:05 |
September | 0.202598E+12 | 0.575296E+11 | 431.89 | 0.131061E+12 | 0.715367E+11 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 241358.89 | 11-SEP-06:02 | 170742.69 | 04-SEP-07:01 | 125895.51 | 11-SEP-06:06 | 61641.46 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.154396E+12 | 0.433497E+11 | 436.49 | 0.106717E+12 | 0.476795E+11 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 239895.89 | 08-OCT-08:62 | 183538.70 | 20-OCT-05:03 | 120927.81 | 08-OCT-08:06 | 58158.34 | 08-OCT-08:06 | 0.00 | 01-OCT-00:10 |
November | 0.103502E+12 | 0.291534E+11 | 401.70 | 0.727727E+11 | 0.307296E+11 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 233176.40 | 03-NOV-06:02 | 183302.85 | 19-NOV-09:02 | 100960.95 | 03-NOV-06:04 | 55447.67 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.603584E+11 | 0.172389E+11 | 382.93 | 0.420663E+11 | 0.182921E+11 | 0.00 | 1.00 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 | 223576.95 | 10-DEC-09:02 | 158289.47 | 12-DEC-07:02 | 77451.94 | 11-DEC-07:03 | 54205.63 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.163472E+13 | 0.473872E+12 | 4936.96 | 0.113648E+13 | 0.498242E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.381618E+11 | 0.111028E+11 | 341.22 | 0.278291E+11 | 0.103327E+11 | 0.00 | 0.63 | 0.00 | 150497.55 | 100785.55 | 49712.00 | 36384.00 | 0.00 | |||||||
Maximum of Months | 0.248953E+12 | 0.733437E+11 | 458.67 | 0.162147E+12 | 0.868061E+11 | 0.00 | 1.00 | 0.00 | 241358.89 | 203951.59 | 125895.51 | 64001.19 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.974140E+10 | 0.246142E+10 | 392.41 | 0.792988E+10 | 0.181151E+10 | 0.00 | 1.00 | 23-JAN-05:02 | 0.00 | 01-JAN-00:10 | 37724.31 | 30-JAN-05:01 | 29015.32 | 25-JAN-05:02 | 9117.80 | 30-JAN-05:01 | 7963.46 | 30-JAN-05:01 | 0.00 | 01-JAN-00:10 |
February | 0.107925E+11 | 0.273738E+10 | 379.62 | 0.865354E+10 | 0.213900E+10 | 0.00 | 1.00 | 06-FEB-05:01 | 0.00 | 01-FEB-00:10 | 39042.82 | 09-FEB-05:01 | 29295.29 | 28-FEB-05:02 | 13786.34 | 09-FEB-05:02 | 8265.17 | 09-FEB-05:01 | 0.00 | 01-FEB-00:10 |
March | 0.140934E+11 | 0.365794E+10 | 454.03 | 0.117000E+11 | 0.239339E+10 | 0.00 | 1.00 | 01-MAR-05:01 | 0.00 | 01-MAR-00:10 | 38740.08 | 29-MAR-04:01 | 35843.57 | 28-MAR-04:01 | 12278.42 | 29-MAR-04:02 | 8724.20 | 02-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.176988E+11 | 0.469900E+10 | 454.56 | 0.144512E+11 | 0.324756E+10 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 39150.19 | 30-APR-06:01 | 35946.56 | 29-APR-04:01 | 14046.27 | 30-APR-06:03 | 8426.93 | 18-APR-04:01 | 0.00 | 01-APR-00:10 |
May | 0.257014E+11 | 0.700493E+10 | 480.64 | 0.210337E+11 | 0.466763E+10 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 40641.79 | 30-MAY-04:01 | 36114.82 | 11-MAY-04:01 | 17692.90 | 24-MAY-04:05 | 9086.55 | 23-MAY-04:01 | 0.00 | 01-MAY-00:10 |
June | 0.302744E+11 | 0.818666E+10 | 477.32 | 0.228051E+11 | 0.746930E+10 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:05 | 41332.57 | 20-JUN-04:01 | 32968.25 | 15-JUN-04:01 | 21595.32 | 19-JUN-04:06 | 9266.66 | 29-JUN-04:02 | 0.00 | 01-JUN-00:05 |
July | 0.366199E+11 | 0.101197E+11 | 556.42 | 0.269439E+11 | 0.967602E+10 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 41219.64 | 02-JUL-06:01 | 35661.83 | 04-JUL-06:01 | 19244.34 | 06-JUL-04:07 | 9328.37 | 16-JUL-06:53 | 0.00 | 01-JUL-00:10 |
August | 0.400533E+11 | 0.110798E+11 | 592.82 | 0.292997E+11 | 0.107536E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:25 | 41132.52 | 27-AUG-06:01 | 32291.15 | 06-AUG-06:01 | 20006.49 | 08-AUG-04:07 | 9592.61 | 05-AUG-04:01 | 0.00 | 01-AUG-00:05 |
September | 0.339423E+11 | 0.900834E+10 | 518.38 | 0.249286E+11 | 0.901373E+10 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:15 | 40836.11 | 28-SEP-04:01 | 31219.37 | 26-SEP-04:01 | 18070.60 | 23-SEP-04:06 | 9223.28 | 13-SEP-04:11 | 0.00 | 01-SEP-00:10 |
October | 0.284613E+11 | 0.731836E+10 | 485.55 | 0.221539E+11 | 0.630741E+10 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 41170.38 | 08-OCT-06:01 | 33598.26 | 21-OCT-04:01 | 19497.35 | 08-OCT-06:06 | 8729.11 | 05-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.208271E+11 | 0.522935E+10 | 449.93 | 0.165264E+11 | 0.430066E+10 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 | 39670.69 | 03-NOV-04:01 | 33085.15 | 05-NOV-06:01 | 14310.37 | 03-NOV-04:12 | 8478.65 | 20-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.134926E+11 | 0.337959E+10 | 441.36 | 0.106426E+11 | 0.284997E+10 | 0.00 | 1.00 | 01-DEC-05:01 | 0.00 | 01-DEC-00:10 | 38531.37 | 11-DEC-05:01 | 31823.60 | 01-DEC-05:01 | 12194.20 | 11-DEC-05:01 | 8217.75 | 12-DEC-05:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.281698E+12 | 0.748825E+11 | 5683.06 | 0.217069E+12 | 0.646298E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.974140E+10 | 0.246142E+10 | 379.62 | 0.792988E+10 | 0.181151E+10 | 0.00 | 1.00 | 0.00 | 37724.31 | 29015.32 | 9117.80 | 7963.46 | 0.00 | |||||||
Maximum of Months | 0.400533E+11 | 0.110798E+11 | 592.82 | 0.292997E+11 | 0.107536E+11 | 0.00 | 1.00 | 0.00 | 41332.57 | 36114.82 | 21595.32 | 9592.61 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.677789E+10 | 0.174949E+10 | 361.95 | 0.530264E+10 | 0.147525E+10 | 0.00 | 1.00 | 23-JAN-05:02 | 0.00 | 01-JAN-00:10 | 34294.56 | 30-JAN-05:01 | 25007.73 | 23-JAN-05:02 | 9469.94 | 30-JAN-05:01 | 7241.43 | 30-JAN-05:01 | 0.00 | 01-JAN-00:10 |
February | 0.794432E+10 | 0.205564E+10 | 357.49 | 0.615710E+10 | 0.178722E+10 | 0.00 | 1.00 | 06-FEB-05:01 | 0.00 | 01-FEB-00:10 | 35465.25 | 09-FEB-05:01 | 24195.48 | 24-FEB-05:01 | 13423.53 | 09-FEB-05:02 | 7515.76 | 09-FEB-05:01 | 0.00 | 01-FEB-00:10 |
March | 0.108357E+11 | 0.286495E+10 | 433.71 | 0.875371E+10 | 0.208194E+10 | 0.00 | 1.00 | 01-MAR-05:01 | 0.00 | 01-MAR-00:10 | 35248.67 | 29-MAR-04:01 | 32328.87 | 28-MAR-04:01 | 12354.56 | 29-MAR-04:02 | 7924.84 | 02-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.146836E+11 | 0.394561E+10 | 451.68 | 0.116938E+11 | 0.298981E+10 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 35621.48 | 30-APR-06:01 | 31709.70 | 29-APR-04:01 | 13662.36 | 30-APR-06:03 | 7665.51 | 18-APR-04:01 | 0.00 | 01-APR-00:10 |
May | 0.226341E+11 | 0.617951E+10 | 472.36 | 0.181254E+11 | 0.450870E+10 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 36953.86 | 24-MAY-04:01 | 32407.76 | 11-MAY-04:01 | 16864.16 | 24-MAY-04:05 | 8269.07 | 23-MAY-04:01 | 0.00 | 01-MAY-00:10 |
June | 0.271123E+11 | 0.729842E+10 | 463.90 | 0.198598E+11 | 0.725249E+10 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:05 | 37604.04 | 20-JUN-04:01 | 29622.39 | 01-JUN-04:01 | 20220.61 | 19-JUN-04:05 | 8431.41 | 29-JUN-04:03 | 0.00 | 01-JUN-00:05 |
July | 0.332133E+11 | 0.909404E+10 | 511.33 | 0.237617E+11 | 0.945165E+10 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 37498.49 | 06-JUL-04:01 | 31771.24 | 04-JUL-06:01 | 18601.31 | 05-JUL-04:08 | 8494.40 | 16-JUL-07:01 | 0.00 | 01-JUL-00:10 |
August | 0.365271E+11 | 0.100128E+11 | 557.39 | 0.259833E+11 | 0.105438E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:05 | 37497.02 | 27-AUG-06:01 | 28896.91 | 06-AUG-06:01 | 19261.86 | 08-AUG-04:19 | 8730.91 | 05-AUG-04:01 | 0.00 | 01-AUG-00:05 |
September | 0.306922E+11 | 0.809265E+10 | 489.63 | 0.218884E+11 | 0.880377E+10 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 37425.74 | 11-SEP-04:01 | 27556.22 | 02-SEP-04:01 | 17205.59 | 11-SEP-04:08 | 8458.30 | 13-SEP-04:01 | 0.00 | 01-SEP-00:10 |
October | 0.252949E+11 | 0.649787E+10 | 472.53 | 0.191715E+11 | 0.612336E+10 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 37466.26 | 08-OCT-06:01 | 29482.70 | 21-OCT-04:01 | 18328.92 | 08-OCT-06:06 | 7943.14 | 05-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.177776E+11 | 0.450261E+10 | 449.83 | 0.137050E+11 | 0.407259E+10 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 | 36069.66 | 03-NOV-04:01 | 29120.02 | 05-NOV-06:01 | 13750.14 | 03-NOV-04:12 | 7705.47 | 20-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.102705E+11 | 0.261698E+10 | 416.64 | 0.779671E+10 | 0.247377E+10 | 0.00 | 1.00 | 01-DEC-05:01 | 0.00 | 01-DEC-00:10 | 34995.88 | 11-DEC-05:01 | 27661.90 | 01-DEC-05:01 | 11977.65 | 11-DEC-05:01 | 7470.70 | 12-DEC-05:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.243763E+12 | 0.649106E+11 | 5438.43 | 0.182199E+12 | 0.615644E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.677789E+10 | 0.174949E+10 | 357.49 | 0.530264E+10 | 0.147525E+10 | 0.00 | 1.00 | 0.00 | 34294.56 | 24195.48 | 9469.94 | 7241.43 | 0.00 | |||||||
Maximum of Months | 0.365271E+11 | 0.100128E+11 | 557.39 | 0.259833E+11 | 0.105438E+11 | 0.00 | 1.00 | 0.00 | 37604.04 | 32407.76 | 20220.61 | 8730.91 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.83 | 13.35 | 21.47 | 50.52 | 35.82 | 0.00 | 0.00 | 744.00 |
February | 42.45 | 17.48 | 24.97 | 66.11 | 31.12 | 0.00 | 0.00 | 672.00 |
March | 50.92 | 21.29 | 29.63 | 84.92 | 27.23 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 27.07 | 33.51 | 108.61 | 21.96 | 0.00 | 0.00 | 720.00 |
May | 68.52 | 33.43 | 35.10 | 131.49 | 12.61 | 0.00 | 0.00 | 744.00 |
June | 71.49 | 36.49 | 34.99 | 139.33 | 9.87 | 0.00 | 0.00 | 720.00 |
July | 69.35 | 35.32 | 34.03 | 141.90 | 4.72 | 0.00 | 0.00 | 744.00 |
August | 65.95 | 32.48 | 33.46 | 135.52 | 4.21 | 0.00 | 0.00 | 744.00 |
September | 59.33 | 28.61 | 30.72 | 116.22 | 10.33 | 0.00 | 0.00 | 720.00 |
October | 49.72 | 23.37 | 26.35 | 91.61 | 17.13 | 0.00 | 0.00 | 744.00 |
November | 39.62 | 17.41 | 22.21 | 66.47 | 25.63 | 0.00 | 0.00 | 720.00 |
December | 32.28 | 12.49 | 19.79 | 48.48 | 32.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.80 | 24.93 | 28.87 | 98.60 | 19.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.28 | 12.49 | 19.79 | 48.48 | 4.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 71.49 | 36.49 | 35.10 | 141.90 | 35.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 597.30 | 280.87 | 316.42 | 893.33 | 443.30 | 0.00 | 0.00 | 744.00 |
February | 560.78 | 229.38 | 331.40 | 864.48 | 390.68 | 0.00 | 0.00 | 672.00 |
March | 461.47 | 125.22 | 336.24 | 739.41 | 319.21 | 0.00 | 0.00 | 744.00 |
April | 362.71 | 38.36 | 324.35 | 683.10 | 224.71 | 0.00 | 0.00 | 720.00 |
May | 307.26 | 4.63 | 302.63 | 809.27 | 92.54 | 0.00 | 0.00 | 744.00 |
June | 289.43 | 0.35 | 289.08 | 855.41 | 48.47 | 0.00 | 0.00 | 720.00 |
July | 289.39 | 2.42 | 286.97 | 986.31 | 8.89 | 0.00 | 0.00 | 744.00 |
August | 335.60 | 23.67 | 311.93 | 1053.38 | 6.00 | 0.00 | 0.00 | 744.00 |
September | 442.54 | 101.34 | 341.20 | 1041.54 | 63.05 | 0.00 | 0.00 | 720.00 |
October | 579.45 | 230.32 | 349.12 | 1165.07 | 152.33 | 0.00 | 0.00 | 744.00 |
November | 639.40 | 308.28 | 331.12 | 1146.84 | 266.06 | 0.00 | 0.00 | 720.00 |
December | 593.62 | 293.29 | 300.32 | 950.80 | 388.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 454.28 | 136.02 | 318.26 | 932.98 | 199.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 289.39 | 0.35 | 286.97 | 683.10 | 6.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 639.40 | 308.28 | 349.12 | 1165.07 | 443.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 597.30 | 280.87 | 316.42 | 892.51 | 428.64 | 0.00 | 0.00 | 744.00 |
February | 560.78 | 229.38 | 331.40 | 862.03 | 376.67 | 0.00 | 0.00 | 672.00 |
March | 461.47 | 125.22 | 336.24 | 735.80 | 304.85 | 0.00 | 0.00 | 744.00 |
April | 362.71 | 38.36 | 324.35 | 677.53 | 212.25 | 0.00 | 0.00 | 720.00 |
May | 307.26 | 4.63 | 302.63 | 804.34 | 83.12 | 0.00 | 0.00 | 744.00 |
June | 289.43 | 0.35 | 289.08 | 852.21 | 41.31 | 0.00 | 0.00 | 720.00 |
July | 289.39 | 2.42 | 286.97 | 982.90 | 7.78 | 0.00 | 0.00 | 744.00 |
August | 335.60 | 23.67 | 311.93 | 1049.63 | 5.31 | 0.00 | 0.00 | 744.00 |
September | 442.54 | 101.34 | 341.20 | 1035.98 | 58.53 | 0.00 | 0.00 | 720.00 |
October | 579.45 | 230.32 | 349.12 | 1158.62 | 142.97 | 0.00 | 0.00 | 744.00 |
November | 639.40 | 308.28 | 331.12 | 1141.79 | 254.27 | 0.00 | 0.00 | 720.00 |
December | 593.62 | 293.29 | 300.32 | 947.98 | 375.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 454.28 | 136.02 | 318.26 | 929.01 | 189.94 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 289.39 | 0.35 | 286.97 | 677.53 | 5.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 639.40 | 308.28 | 349.12 | 1158.62 | 428.64 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 122.90 | 57.79 | 65.11 | 183.67 | 84.22 | 0.00 | 0.00 | 744.00 |
February | 115.39 | 47.20 | 68.19 | 172.51 | 76.13 | 0.00 | 0.00 | 672.00 |
March | 94.95 | 25.77 | 69.19 | 139.49 | 65.63 | 0.00 | 0.00 | 744.00 |
April | 74.63 | 7.89 | 66.74 | 114.02 | 51.69 | 0.00 | 0.00 | 720.00 |
May | 63.22 | 0.95 | 62.27 | 113.48 | 27.44 | 0.00 | 0.00 | 744.00 |
June | 59.55 | 0.07 | 59.48 | 113.21 | 19.12 | 0.00 | 0.00 | 720.00 |
July | 59.55 | 0.50 | 59.05 | 123.55 | 8.03 | 0.00 | 0.00 | 744.00 |
August | 69.05 | 4.87 | 64.18 | 133.69 | 8.82 | 0.00 | 0.00 | 744.00 |
September | 91.06 | 20.85 | 70.21 | 153.63 | 27.40 | 0.00 | 0.00 | 720.00 |
October | 119.23 | 47.39 | 71.84 | 195.88 | 46.64 | 0.00 | 0.00 | 744.00 |
November | 131.57 | 63.43 | 68.13 | 210.47 | 64.71 | 0.00 | 0.00 | 720.00 |
December | 122.15 | 60.35 | 61.80 | 188.25 | 78.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 93.47 | 27.99 | 65.49 | 153.39 | 46.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 59.55 | 0.07 | 59.05 | 113.21 | 8.03 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 131.57 | 63.43 | 71.84 | 210.47 | 84.22 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93279755.56 | 35761971.05 | 57517784.51 | 0.135300E+09 | 95951889.65 |
February | 0.102697E+09 | 42291137.78 | 60405455.26 | 0.159928E+09 | 75276780.68 |
March | 0.136387E+09 | 57025172.00 | 79361874.20 | 0.227451E+09 | 72924032.16 |
April | 0.157018E+09 | 70154447.15 | 86863837.25 | 0.281509E+09 | 56916370.50 |
May | 0.183536E+09 | 89536496.76 | 93999770.91 | 0.352184E+09 | 33781363.55 |
June | 0.185297E+09 | 94590848.46 | 90705966.16 | 0.361131E+09 | 25589698.01 |
July | 0.185739E+09 | 94601269.81 | 91137977.66 | 0.380056E+09 | 12653012.15 |
August | 0.176637E+09 | 87007369.11 | 89630079.99 | 0.362977E+09 | 11285583.44 |
September | 0.153779E+09 | 74160953.59 | 79618502.72 | 0.301249E+09 | 26773764.06 |
October | 0.133174E+09 | 62605361.68 | 70568487.67 | 0.245377E+09 | 45893808.50 |
November | 0.102685E+09 | 45124080.80 | 57560889.91 | 0.172301E+09 | 66433071.72 |
December | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 86348903.76 |
Annual Sum or Average | 0.169668E+10 | 0.786312E+09 | 0.910364E+09 | 0.310931E+10 | 0.609828E+09 |
Minimum of Months | 86446335.26 | 33453148.13 | 52993187.14 | 0.129843E+09 | 11285583.44 |
Maximum of Months | 0.185739E+09 | 94601269.81 | 93999770.91 | 0.380056E+09 | 95951889.65 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.159980E+10 | 0.752291E+09 | 0.847511E+09 | 0.239269E+10 | 0.118733E+10 |
February | 0.135665E+10 | 0.554924E+09 | 0.801725E+09 | 0.209134E+10 | 0.945130E+09 |
March | 0.123599E+10 | 0.335398E+09 | 0.900597E+09 | 0.198044E+10 | 0.854969E+09 |
April | 0.940147E+09 | 99430939.41 | 0.840716E+09 | 0.177060E+10 | 0.582449E+09 |
May | 0.822974E+09 | 12410512.59 | 0.810563E+09 | 0.216756E+10 | 0.247859E+09 |
June | 0.750198E+09 | 897411.60 | 0.749300E+09 | 0.221722E+10 | 0.125633E+09 |
July | 0.775107E+09 | 6479161.69 | 0.768628E+09 | 0.264174E+10 | 23802676.44 |
August | 0.898867E+09 | 63390603.70 | 0.835477E+09 | 0.282138E+10 | 16083703.58 |
September | 0.114707E+10 | 0.262674E+09 | 0.884398E+09 | 0.269967E+10 | 0.163437E+09 |
October | 0.155199E+10 | 0.616892E+09 | 0.935095E+09 | 0.312053E+10 | 0.407987E+09 |
November | 0.165733E+10 | 0.799063E+09 | 0.858265E+09 | 0.297260E+10 | 0.689626E+09 |
December | 0.158994E+10 | 0.785560E+09 | 0.804379E+09 | 0.254663E+10 | 0.104038E+10 |
Annual Sum or Average | 0.143261E+11 | 0.428941E+10 | 0.100367E+11 | 0.294224E+11 | 0.628469E+10 |
Minimum of Months | 0.750198E+09 | 897411.60 | 0.749300E+09 | 0.177060E+10 | 16083703.58 |
Maximum of Months | 0.165733E+10 | 0.799063E+09 | 0.935095E+09 | 0.312053E+10 | 0.118733E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.159980E+10 | 0.752291E+09 | 0.847511E+09 | 0.239050E+10 | 0.114808E+10 |
February | 0.135665E+10 | 0.554924E+09 | 0.801725E+09 | 0.208543E+10 | 0.911230E+09 |
March | 0.123599E+10 | 0.335398E+09 | 0.900597E+09 | 0.197076E+10 | 0.816508E+09 |
April | 0.940147E+09 | 99430939.41 | 0.840716E+09 | 0.175617E+10 | 0.550159E+09 |
May | 0.822974E+09 | 12410512.59 | 0.810563E+09 | 0.215434E+10 | 0.222631E+09 |
June | 0.750198E+09 | 897411.60 | 0.749300E+09 | 0.220893E+10 | 0.107068E+09 |
July | 0.775107E+09 | 6479161.69 | 0.768628E+09 | 0.263261E+10 | 20836895.20 |
August | 0.898867E+09 | 63390603.70 | 0.835477E+09 | 0.281133E+10 | 14229478.44 |
September | 0.114707E+10 | 0.262674E+09 | 0.884398E+09 | 0.268527E+10 | 0.151720E+09 |
October | 0.155199E+10 | 0.616892E+09 | 0.935095E+09 | 0.310324E+10 | 0.382930E+09 |
November | 0.165733E+10 | 0.799063E+09 | 0.858265E+09 | 0.295951E+10 | 0.659078E+09 |
December | 0.158994E+10 | 0.785560E+09 | 0.804379E+09 | 0.253907E+10 | 0.100561E+10 |
Annual Sum or Average | 0.143261E+11 | 0.428941E+10 | 0.100367E+11 | 0.292972E+11 | 0.599007E+10 |
Minimum of Months | 0.750198E+09 | 897411.60 | 0.749300E+09 | 0.175617E+10 | 14229478.44 |
Maximum of Months | 0.165733E+10 | 0.799063E+09 | 0.935095E+09 | 0.310324E+10 | 0.114808E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.329183E+09 | 0.154795E+09 | 0.174388E+09 | 0.491931E+09 | 0.225574E+09 |
February | 0.279150E+09 | 0.114184E+09 | 0.164967E+09 | 0.417339E+09 | 0.184172E+09 |
March | 0.254324E+09 | 69012944.52 | 0.185311E+09 | 0.373609E+09 | 0.175780E+09 |
April | 0.193449E+09 | 20459363.62 | 0.172990E+09 | 0.295549E+09 | 0.133974E+09 |
May | 0.169339E+09 | 2553643.68 | 0.166785E+09 | 0.303933E+09 | 73507748.11 |
June | 0.154364E+09 | 184655.50 | 0.154179E+09 | 0.293442E+09 | 49558606.53 |
July | 0.159490E+09 | 1333181.86 | 0.158156E+09 | 0.330924E+09 | 21508758.95 |
August | 0.184955E+09 | 13043539.75 | 0.171912E+09 | 0.358062E+09 | 23632737.09 |
September | 0.236027E+09 | 54048898.60 | 0.181978E+09 | 0.398202E+09 | 71019561.39 |
October | 0.319344E+09 | 0.126935E+09 | 0.192409E+09 | 0.524641E+09 | 0.124927E+09 |
November | 0.341019E+09 | 0.164419E+09 | 0.176601E+09 | 0.545536E+09 | 0.167720E+09 |
December | 0.327153E+09 | 0.161640E+09 | 0.165513E+09 | 0.504212E+09 | 0.209930E+09 |
Annual Sum or Average | 0.294780E+10 | 0.882609E+09 | 0.206519E+10 | 0.483738E+10 | 0.146130E+10 |
Minimum of Months | 0.154364E+09 | 184655.50 | 0.154179E+09 | 0.293442E+09 | 21508758.95 |
Maximum of Months | 0.341019E+09 | 0.164419E+09 | 0.192409E+09 | 0.545536E+09 | 0.225574E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 808.24 | 573.19 | 557.23 | 213.63 | 343.59 | 0.00 | 0.00 |
February | 1057.73 | 497.86 | 679.21 | 279.70 | 399.51 | 0.00 | 0.00 |
March | 1358.73 | 435.63 | 814.74 | 340.65 | 474.09 | 0.00 | 0.00 |
April | 1737.71 | 351.34 | 969.25 | 433.05 | 536.20 | 0.00 | 0.00 |
May | 2103.85 | 201.80 | 1096.39 | 534.87 | 561.53 | 0.00 | 0.00 |
June | 2229.20 | 157.96 | 1143.81 | 583.89 | 559.91 | 0.00 | 0.00 |
July | 2270.34 | 75.59 | 1109.55 | 565.12 | 544.43 | 0.00 | 0.00 |
August | 2168.32 | 67.42 | 1055.18 | 519.76 | 535.42 | 0.00 | 0.00 |
September | 1859.56 | 165.27 | 949.26 | 457.78 | 491.47 | 0.00 | 0.00 |
October | 1465.81 | 274.16 | 795.54 | 373.99 | 421.56 | 0.00 | 0.00 |
November | 1063.59 | 410.08 | 633.86 | 278.54 | 355.31 | 0.00 | 0.00 |
December | 775.64 | 515.82 | 516.41 | 199.84 | 316.57 | 0.00 | 0.00 |
Annual Sum or Average | 1577.53 | 309.40 | 860.82 | 398.94 | 461.88 | 0.00 | 0.00 |
Minimum of Months | 775.64 | 67.42 | 516.41 | 199.84 | 316.57 | 0.00 | 0.00 |
Maximum of Months | 2270.34 | 573.19 | 1143.81 | 583.89 | 561.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 893.33 | 443.30 | 597.30 | 280.87 | 316.42 | 0.00 | 0.00 |
February | 864.48 | 390.68 | 560.78 | 229.38 | 331.40 | 0.00 | 0.00 |
March | 739.41 | 319.21 | 461.47 | 125.22 | 336.24 | 0.00 | 0.00 |
April | 683.10 | 224.71 | 362.71 | 38.36 | 324.35 | 0.00 | 0.00 |
May | 809.27 | 92.54 | 307.26 | 4.63 | 302.63 | 0.00 | 0.00 |
June | 855.41 | 48.47 | 289.43 | 0.35 | 289.08 | 0.00 | 0.00 |
July | 986.31 | 8.89 | 289.39 | 2.42 | 286.97 | 0.00 | 0.00 |
August | 1053.38 | 6.00 | 335.60 | 23.67 | 311.93 | 0.00 | 0.00 |
September | 1041.54 | 63.05 | 442.54 | 101.34 | 341.20 | 0.00 | 0.00 |
October | 1165.07 | 152.33 | 579.45 | 230.32 | 349.12 | 0.00 | 0.00 |
November | 1146.84 | 266.06 | 639.40 | 308.28 | 331.12 | 0.00 | 0.00 |
December | 950.80 | 388.43 | 593.62 | 293.29 | 300.32 | 0.00 | 0.00 |
Annual Sum or Average | 932.98 | 199.29 | 454.28 | 136.02 | 318.26 | 0.00 | 0.00 |
Minimum of Months | 683.10 | 6.00 | 289.39 | 0.35 | 286.97 | 0.00 | 0.00 |
Maximum of Months | 1165.07 | 443.30 | 639.40 | 308.28 | 349.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 892.51 | 428.64 | 597.30 | 280.87 | 316.42 | 0.00 | 0.00 |
February | 862.03 | 376.67 | 560.78 | 229.38 | 331.40 | 0.00 | 0.00 |
March | 735.80 | 304.85 | 461.47 | 125.22 | 336.24 | 0.00 | 0.00 |
April | 677.53 | 212.25 | 362.71 | 38.36 | 324.35 | 0.00 | 0.00 |
May | 804.34 | 83.12 | 307.26 | 4.63 | 302.63 | 0.00 | 0.00 |
June | 852.21 | 41.31 | 289.43 | 0.35 | 289.08 | 0.00 | 0.00 |
July | 982.90 | 7.78 | 289.39 | 2.42 | 286.97 | 0.00 | 0.00 |
August | 1049.63 | 5.31 | 335.60 | 23.67 | 311.93 | 0.00 | 0.00 |
September | 1035.98 | 58.53 | 442.54 | 101.34 | 341.20 | 0.00 | 0.00 |
October | 1158.62 | 142.97 | 579.45 | 230.32 | 349.12 | 0.00 | 0.00 |
November | 1141.79 | 254.27 | 639.40 | 308.28 | 331.12 | 0.00 | 0.00 |
December | 947.98 | 375.45 | 593.62 | 293.29 | 300.32 | 0.00 | 0.00 |
Annual Sum or Average | 929.01 | 189.94 | 454.28 | 136.02 | 318.26 | 0.00 | 0.00 |
Minimum of Months | 677.53 | 5.31 | 289.39 | 0.35 | 286.97 | 0.00 | 0.00 |
Maximum of Months | 1158.62 | 428.64 | 639.40 | 308.28 | 349.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 183.67 | 84.22 | 122.90 | 57.79 | 65.11 | 0.00 | 0.00 |
February | 172.51 | 76.13 | 115.39 | 47.20 | 68.19 | 0.00 | 0.00 |
March | 139.49 | 65.63 | 94.95 | 25.77 | 69.19 | 0.00 | 0.00 |
April | 114.02 | 51.69 | 74.63 | 7.89 | 66.74 | 0.00 | 0.00 |
May | 113.48 | 27.44 | 63.22 | 0.95 | 62.27 | 0.00 | 0.00 |
June | 113.21 | 19.12 | 59.55 | 0.07 | 59.48 | 0.00 | 0.00 |
July | 123.55 | 8.03 | 59.55 | 0.50 | 59.05 | 0.00 | 0.00 |
August | 133.69 | 8.82 | 69.05 | 4.87 | 64.18 | 0.00 | 0.00 |
September | 153.63 | 27.40 | 91.06 | 20.85 | 70.21 | 0.00 | 0.00 |
October | 195.88 | 46.64 | 119.23 | 47.39 | 71.84 | 0.00 | 0.00 |
November | 210.47 | 64.71 | 131.57 | 63.43 | 68.13 | 0.00 | 0.00 |
December | 188.25 | 78.38 | 122.15 | 60.35 | 61.80 | 0.00 | 0.00 |
Annual Sum or Average | 153.39 | 46.34 | 93.47 | 27.99 | 65.49 | 0.00 | 0.00 |
Minimum of Months | 113.21 | 8.03 | 59.55 | 0.07 | 59.05 | 0.00 | 0.00 |
Maximum of Months | 210.47 | 84.22 | 131.57 | 63.43 | 71.84 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.216480E+10 | 0.153523E+10 | 0.149248E+10 | 0.572192E+09 | 0.920285E+09 | 0.00 | 0.00 |
February | 0.255885E+10 | 0.120443E+10 | 0.164315E+10 | 0.676658E+09 | 0.966487E+09 | 0.00 | 0.00 |
March | 0.363922E+10 | 0.116678E+10 | 0.218219E+10 | 0.912403E+09 | 0.126979E+10 | 0.00 | 0.00 |
April | 0.450415E+10 | 0.910662E+09 | 0.251229E+10 | 0.112247E+10 | 0.138982E+10 | 0.00 | 0.00 |
May | 0.563494E+10 | 0.540502E+09 | 0.293658E+10 | 0.143258E+10 | 0.150400E+10 | 0.00 | 0.00 |
June | 0.577810E+10 | 0.409435E+09 | 0.296475E+10 | 0.151345E+10 | 0.145130E+10 | 0.00 | 0.00 |
July | 0.608089E+10 | 0.202448E+09 | 0.297183E+10 | 0.151362E+10 | 0.145821E+10 | 0.00 | 0.00 |
August | 0.580764E+10 | 0.180569E+09 | 0.282620E+10 | 0.139212E+10 | 0.143408E+10 | 0.00 | 0.00 |
September | 0.481998E+10 | 0.428380E+09 | 0.246047E+10 | 0.118658E+10 | 0.127390E+10 | 0.00 | 0.00 |
October | 0.392604E+10 | 0.734301E+09 | 0.213078E+10 | 0.100169E+10 | 0.112910E+10 | 0.00 | 0.00 |
November | 0.275682E+10 | 0.106293E+10 | 0.164296E+10 | 0.721985E+09 | 0.920974E+09 | 0.00 | 0.00 |
December | 0.207749E+10 | 0.138158E+10 | 0.138314E+10 | 0.535250E+09 | 0.847891E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.497489E+11 | 0.975725E+10 | 0.271468E+11 | 0.125810E+11 | 0.145658E+11 | 0.00 | 0.00 |
Minimum of Months | 0.207749E+10 | 0.180569E+09 | 0.138314E+10 | 0.535250E+09 | 0.847891E+09 | 0.00 | 0.00 |
Maximum of Months | 0.608089E+10 | 0.153523E+10 | 0.297183E+10 | 0.151362E+10 | 0.150400E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.239269E+10 | 0.118733E+10 | 0.159980E+10 | 0.752291E+09 | 0.847511E+09 | 0.00 | 0.00 |
February | 0.209134E+10 | 0.945130E+09 | 0.135665E+10 | 0.554924E+09 | 0.801725E+09 | 0.00 | 0.00 |
March | 0.198044E+10 | 0.854969E+09 | 0.123599E+10 | 0.335398E+09 | 0.900597E+09 | 0.00 | 0.00 |
April | 0.177060E+10 | 0.582449E+09 | 0.940147E+09 | 99430939.41 | 0.840716E+09 | 0.00 | 0.00 |
May | 0.216756E+10 | 0.247859E+09 | 0.822974E+09 | 12410512.59 | 0.810563E+09 | 0.00 | 0.00 |
June | 0.221722E+10 | 0.125633E+09 | 0.750198E+09 | 897411.60 | 0.749300E+09 | 0.00 | 0.00 |
July | 0.264174E+10 | 23802676.44 | 0.775107E+09 | 6479161.69 | 0.768628E+09 | 0.00 | 0.00 |
August | 0.282138E+10 | 16083703.58 | 0.898867E+09 | 63390603.70 | 0.835477E+09 | 0.00 | 0.00 |
September | 0.269967E+10 | 0.163437E+09 | 0.114707E+10 | 0.262674E+09 | 0.884398E+09 | 0.00 | 0.00 |
October | 0.312053E+10 | 0.407987E+09 | 0.155199E+10 | 0.616892E+09 | 0.935095E+09 | 0.00 | 0.00 |
November | 0.297260E+10 | 0.689626E+09 | 0.165733E+10 | 0.799063E+09 | 0.858265E+09 | 0.00 | 0.00 |
December | 0.254663E+10 | 0.104038E+10 | 0.158994E+10 | 0.785560E+09 | 0.804379E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.294224E+11 | 0.628469E+10 | 0.143261E+11 | 0.428941E+10 | 0.100367E+11 | 0.00 | 0.00 |
Minimum of Months | 0.177060E+10 | 16083703.58 | 0.750198E+09 | 897411.60 | 0.749300E+09 | 0.00 | 0.00 |
Maximum of Months | 0.312053E+10 | 0.118733E+10 | 0.165733E+10 | 0.799063E+09 | 0.935095E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.239050E+10 | 0.114808E+10 | 0.159980E+10 | 0.752291E+09 | 0.847511E+09 | 0.00 | 0.00 |
February | 0.208543E+10 | 0.911230E+09 | 0.135665E+10 | 0.554924E+09 | 0.801725E+09 | 0.00 | 0.00 |
March | 0.197076E+10 | 0.816508E+09 | 0.123599E+10 | 0.335398E+09 | 0.900597E+09 | 0.00 | 0.00 |
April | 0.175617E+10 | 0.550159E+09 | 0.940147E+09 | 99430939.41 | 0.840716E+09 | 0.00 | 0.00 |
May | 0.215434E+10 | 0.222631E+09 | 0.822974E+09 | 12410512.59 | 0.810563E+09 | 0.00 | 0.00 |
June | 0.220893E+10 | 0.107068E+09 | 0.750198E+09 | 897411.60 | 0.749300E+09 | 0.00 | 0.00 |
July | 0.263261E+10 | 20836895.20 | 0.775107E+09 | 6479161.69 | 0.768628E+09 | 0.00 | 0.00 |
August | 0.281133E+10 | 14229478.44 | 0.898867E+09 | 63390603.70 | 0.835477E+09 | 0.00 | 0.00 |
September | 0.268527E+10 | 0.151720E+09 | 0.114707E+10 | 0.262674E+09 | 0.884398E+09 | 0.00 | 0.00 |
October | 0.310324E+10 | 0.382930E+09 | 0.155199E+10 | 0.616892E+09 | 0.935095E+09 | 0.00 | 0.00 |
November | 0.295951E+10 | 0.659078E+09 | 0.165733E+10 | 0.799063E+09 | 0.858265E+09 | 0.00 | 0.00 |
December | 0.253907E+10 | 0.100561E+10 | 0.158994E+10 | 0.785560E+09 | 0.804379E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.292972E+11 | 0.599007E+10 | 0.143261E+11 | 0.428941E+10 | 0.100367E+11 | 0.00 | 0.00 |
Minimum of Months | 0.175617E+10 | 14229478.44 | 0.750198E+09 | 897411.60 | 0.749300E+09 | 0.00 | 0.00 |
Maximum of Months | 0.310324E+10 | 0.114808E+10 | 0.165733E+10 | 0.799063E+09 | 0.935095E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.491931E+09 | 0.225574E+09 | 0.329183E+09 | 0.154795E+09 | 0.174388E+09 | 0.00 | 0.00 |
February | 0.417339E+09 | 0.184172E+09 | 0.279150E+09 | 0.114184E+09 | 0.164967E+09 | 0.00 | 0.00 |
March | 0.373609E+09 | 0.175780E+09 | 0.254324E+09 | 69012944.52 | 0.185311E+09 | 0.00 | 0.00 |
April | 0.295549E+09 | 0.133974E+09 | 0.193449E+09 | 20459363.62 | 0.172990E+09 | 0.00 | 0.00 |
May | 0.303933E+09 | 73507748.11 | 0.169339E+09 | 2553643.68 | 0.166785E+09 | 0.00 | 0.00 |
June | 0.293442E+09 | 49558606.53 | 0.154364E+09 | 184655.50 | 0.154179E+09 | 0.00 | 0.00 |
July | 0.330924E+09 | 21508758.95 | 0.159490E+09 | 1333181.86 | 0.158156E+09 | 0.00 | 0.00 |
August | 0.358062E+09 | 23632737.09 | 0.184955E+09 | 13043539.75 | 0.171912E+09 | 0.00 | 0.00 |
September | 0.398202E+09 | 71019561.39 | 0.236027E+09 | 54048898.60 | 0.181978E+09 | 0.00 | 0.00 |
October | 0.524641E+09 | 0.124927E+09 | 0.319344E+09 | 0.126935E+09 | 0.192409E+09 | 0.00 | 0.00 |
November | 0.545536E+09 | 0.167720E+09 | 0.341019E+09 | 0.164419E+09 | 0.176601E+09 | 0.00 | 0.00 |
December | 0.504212E+09 | 0.209930E+09 | 0.327153E+09 | 0.161640E+09 | 0.165513E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.483738E+10 | 0.146130E+10 | 0.294780E+10 | 0.882609E+09 | 0.206519E+10 | 0.00 | 0.00 |
Minimum of Months | 0.293442E+09 | 21508758.95 | 0.154364E+09 | 184655.50 | 0.154179E+09 | 0.00 | 0.00 |
Maximum of Months | 0.545536E+09 | 0.225574E+09 | 0.341019E+09 | 0.164419E+09 | 0.192409E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.73 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.25 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.73 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.16 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.89 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.77 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.47 | 23.16 | 3.85 | 24.13 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.01 | 24.10 | 3.89 | 24.32 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.67 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.65 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.61 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.83 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.01 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.73 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.01 | 24.10 | 3.95 | 24.32 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.53 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.25 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.80 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.14 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.72 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.53 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 21.97 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.35 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.39 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.78 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.12 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.02 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.53 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.35 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.44 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.73 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.73 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.04 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.94 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.23 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.43 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.81 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.81 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.94 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.20 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.04 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.10 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.85 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.13 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.23 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.13 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.20 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.10 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.85 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.09 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.85 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.200502E+10 | -.161533E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -389685801.7 | 58.99 | 0.00 | 0.00 |
February | 0.177772E+10 | -.142943E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -348292466.0 | 58.99 | 0.00 | 0.00 |
March | 0.188923E+10 | -.150826E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -380975924.6 | 58.99 | 0.00 | 0.00 |
April | 0.165183E+10 | -.128835E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -363483405.5 | 58.99 | 0.00 | 0.00 |
May | 0.155437E+10 | -.118622E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -368147244.8 | 58.99 | 0.00 | 0.00 |
June | 0.141338E+10 | -.105954E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -353844698.9 | 58.98 | 0.00 | 0.00 |
July | 0.139375E+10 | -.102958E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -364169217.3 | 58.99 | 0.00 | 0.00 |
August | 0.147597E+10 | -.111122E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -364748693.6 | 58.99 | 0.00 | 0.00 |
September | 0.152433E+10 | -.116926E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -355062744.8 | 58.99 | 0.00 | 0.00 |
October | 0.170987E+10 | -.133892E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -370948350.0 | 58.99 | 0.00 | 0.00 |
November | 0.179368E+10 | -.142861E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -365066589.9 | 58.99 | 0.00 | 0.00 |
December | 0.197032E+10 | -.158583E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -384482931.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.201595E+11 | -.157506E+11 | 8760.00 | -.440891E+10 | 58.99 | |||||
Minimum of Months | 0.139375E+10 | -.161533E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -389685801.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.200502E+10 | -.102958E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -348292466.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.85 | 0.67 | 01-JAN-11:50 | 263.89 | 6.94 | 0.00 | 0.00 | 216.89 | 5.46 | 0.00 | 0.00 |
February | 308.33 | 0.82 | 0.50 | 24-FEB-11:00 | 306.27 | 7.72 | 0.00 | 5.17 | 253.63 | 6.18 | 0.00 | 2.00 |
March | 357.50 | 0.75 | 0.50 | 01-MAR-11:00 | 1383.90 | 8.83 | 0.00 | 136.17 | 1224.65 | 7.20 | 0.00 | 56.17 |
April | 375.00 | 0.78 | 0.50 | 02-APR-11:30 | 352.09 | 9.69 | 0.00 | 75.50 | 295.02 | 8.06 | 0.00 | 44.33 |
May | 405.33 | 0.79 | 0.50 | 10-MAY-10:39 | 342.63 | 10.68 | 0.00 | 26.50 | 286.27 | 9.04 | 0.00 | 16.50 |
June | 403.50 | 0.79 | 0.50 | 04-JUN-11:20 | 345.04 | 11.22 | 0.00 | 21.33 | 285.88 | 9.53 | 0.00 | 5.67 |
July | 405.00 | 0.78 | 0.50 | 05-JUL-10:50 | 352.24 | 11.02 | 0.00 | 38.83 | 291.59 | 9.37 | 0.00 | 14.83 |
August | 395.83 | 0.76 | 0.50 | 01-AUG-11:39 | 369.91 | 10.47 | 0.00 | 93.33 | 307.55 | 8.83 | 0.00 | 47.17 |
September | 358.83 | 0.75 | 0.50 | 01-SEP-10:39 | 384.49 | 9.59 | 0.00 | 119.83 | 320.63 | 7.95 | 0.00 | 65.33 |
October | 351.17 | 0.79 | 0.50 | 01-OCT-10:39 | 341.74 | 8.24 | 0.00 | 47.83 | 284.68 | 6.70 | 0.00 | 35.33 |
November | 318.83 | 0.83 | 0.67 | 01-NOV-09:50 | 286.59 | 7.33 | 0.00 | 0.00 | 236.19 | 5.79 | 0.00 | 0.00 |
December | 319.00 | 0.86 | 0.67 | 01-DEC-11:09 | 251.43 | 6.71 | 0.00 | 0.00 | 205.91 | 5.24 | 0.00 | 0.00 |
Annual Sum or Average | 4323.33 | 0.79 | 417.20 | 9.18 | 0.00 | 564.50 | 352.59 | 7.59 | 0.00 | 287.33 | ||
Minimum of Months | 308.33 | 0.75 | 0.50 | 251.43 | 6.71 | 0.00 | 0.00 | 205.91 | 5.24 | 0.00 | 0.00 | |
Maximum of Months | 405.33 | 0.86 | 0.67 | 1383.90 | 11.22 | 0.00 | 136.17 | 1224.65 | 9.53 | 0.00 | 65.33 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1528452.92 | 810.58 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1528452.92 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1528452.92 | 810.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.743949E+10 | 0.554744E+10 | 66036.42 | 30-JAN-05:01 | 46164.19 | 0.00 |
February | 0.00 | 0.00 | 0.107671E+11 | 0.811115E+10 | 67961.10 | 09-FEB-05:01 | 43067.54 | 0.00 |
March | 0.00 | 0.00 | 0.179112E+11 | 0.144128E+11 | 67453.62 | 29-MAR-04:01 | 47062.32 | 0.00 |
April | 0.00 | 0.00 | 0.272474E+11 | 0.221017E+11 | 67855.77 | 12-APR-04:01 | 45413.41 | 0.00 |
May | 0.00 | 0.00 | 0.447105E+11 | 0.370388E+11 | 70407.43 | 24-MAY-04:01 | 44551.65 | 0.00 |
June | 0.00 | 0.00 | 0.541070E+11 | 0.420854E+11 | 72277.72 | 19-JUN-04:01 | 38663.80 | 0.00 |
July | 0.00 | 0.00 | 0.637381E+11 | 0.486489E+11 | 71737.62 | 05-JUL-04:01 | 43695.92 | 0.00 |
August | 0.00 | 0.00 | 0.667520E+11 | 0.503898E+11 | 71867.93 | 08-AUG-04:11 | 42085.52 | 0.00 |
September | 0.00 | 0.00 | 0.526524E+11 | 0.391574E+11 | 71778.70 | 11-SEP-04:01 | 42718.76 | 0.00 |
October | 0.00 | 0.00 | 0.403341E+11 | 0.310483E+11 | 71395.64 | 02-OCT-04:01 | 41326.44 | 0.00 |
November | 0.00 | 0.00 | 0.255821E+11 | 0.196014E+11 | 68832.17 | 03-NOV-04:01 | 45442.19 | 0.00 |
December | 0.00 | 0.00 | 0.131253E+11 | 0.965614E+10 | 67105.60 | 11-DEC-05:01 | 44878.88 | 0.00 |
Annual Sum or Average | 0.424367E+12 | 0.327799E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.743949E+10 | 0.554744E+10 | 66036.42 | 38663.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.667520E+11 | 0.503898E+11 | 72277.72 | 47062.32 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.381618E+11 | 0.278291E+11 | 150497.55 | 29-JAN-09:03 | 100785.55 | 0.00 |
February | 0.00 | 0.00 | 0.500125E+11 | 0.363525E+11 | 228724.81 | 09-FEB-07:02 | 143013.88 | 0.00 |
March | 0.00 | 0.00 | 0.748141E+11 | 0.574251E+11 | 228203.42 | 29-MAR-06:03 | 136992.52 | 0.00 |
April | 0.00 | 0.00 | 0.106980E+12 | 0.815359E+11 | 233115.02 | 30-APR-08:62 | 131960.21 | 0.00 |
May | 0.00 | 0.00 | 0.162113E+12 | 0.124749E+12 | 234045.72 | 24-MAY-05:02 | 145923.89 | 0.00 |
June | 0.00 | 0.00 | 0.198114E+12 | 0.137358E+12 | 238991.30 | 25-JUN-08:62 | 120075.53 | 0.00 |
July | 0.00 | 0.00 | 0.234713E+12 | 0.156461E+12 | 239604.04 | 05-JUL-04:01 | 141990.51 | 0.00 |
August | 0.00 | 0.00 | 0.248953E+12 | 0.162147E+12 | 240484.93 | 08-AUG-06:03 | 117725.84 | 0.00 |
September | 0.00 | 0.00 | 0.202598E+12 | 0.131061E+12 | 241358.89 | 11-SEP-06:02 | 115778.75 | 0.00 |
October | 0.00 | 0.00 | 0.154396E+12 | 0.106717E+12 | 239895.89 | 08-OCT-08:62 | 119252.48 | 0.00 |
November | 0.00 | 0.00 | 0.103502E+12 | 0.727727E+11 | 233176.40 | 03-NOV-06:02 | 132681.59 | 0.00 |
December | 0.00 | 0.00 | 0.603584E+11 | 0.420663E+11 | 223576.95 | 10-DEC-09:02 | 155054.05 | 0.00 |
Annual Sum or Average | 0.163472E+13 | 0.113648E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.381618E+11 | 0.278291E+11 | 150497.55 | 100785.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.248953E+12 | 0.162147E+12 | 241358.89 | 155054.05 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.974140E+10 | 0.792988E+10 | 37724.31 | 30-JAN-05:01 | 28606.52 | 0.00 |
February | 0.00 | 0.00 | 0.107925E+11 | 0.865354E+10 | 39042.82 | 09-FEB-05:01 | 25618.73 | 0.00 |
March | 0.00 | 0.00 | 0.140934E+11 | 0.117000E+11 | 38740.08 | 29-MAR-04:01 | 26892.94 | 0.00 |
April | 0.00 | 0.00 | 0.176988E+11 | 0.144512E+11 | 39150.19 | 30-APR-06:01 | 26171.04 | 0.00 |
May | 0.00 | 0.00 | 0.257014E+11 | 0.210337E+11 | 40641.79 | 30-MAY-04:01 | 25528.50 | 0.00 |
June | 0.00 | 0.00 | 0.302744E+11 | 0.228051E+11 | 41332.57 | 20-JUN-04:01 | 22998.56 | 0.00 |
July | 0.00 | 0.00 | 0.366199E+11 | 0.269439E+11 | 41219.64 | 02-JUL-06:01 | 23725.14 | 0.00 |
August | 0.00 | 0.00 | 0.400533E+11 | 0.292997E+11 | 41132.52 | 27-AUG-06:01 | 24259.63 | 0.00 |
September | 0.00 | 0.00 | 0.339423E+11 | 0.249286E+11 | 40836.11 | 28-SEP-04:01 | 25047.63 | 0.00 |
October | 0.00 | 0.00 | 0.284613E+11 | 0.221539E+11 | 41170.38 | 08-OCT-06:01 | 23401.60 | 0.00 |
November | 0.00 | 0.00 | 0.208271E+11 | 0.165264E+11 | 39670.69 | 03-NOV-04:01 | 27255.92 | 0.00 |
December | 0.00 | 0.00 | 0.134926E+11 | 0.106426E+11 | 38531.37 | 11-DEC-05:01 | 26337.16 | 0.00 |
Annual Sum or Average | 0.281698E+12 | 0.217069E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.974140E+10 | 0.792988E+10 | 37724.31 | 22998.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.400533E+11 | 0.292997E+11 | 41332.57 | 28606.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.677789E+10 | 0.530264E+10 | 34294.56 | 30-JAN-05:01 | 24824.62 | 0.00 |
February | 0.00 | 0.00 | 0.794432E+10 | 0.615710E+10 | 35465.25 | 09-FEB-05:01 | 22263.28 | 0.00 |
March | 0.00 | 0.00 | 0.108357E+11 | 0.875371E+10 | 35248.67 | 29-MAR-04:01 | 23171.30 | 0.00 |
April | 0.00 | 0.00 | 0.146836E+11 | 0.116938E+11 | 35621.48 | 30-APR-06:01 | 22679.98 | 0.00 |
May | 0.00 | 0.00 | 0.226341E+11 | 0.181254E+11 | 36953.86 | 24-MAY-04:01 | 21107.91 | 0.00 |
June | 0.00 | 0.00 | 0.271123E+11 | 0.198598E+11 | 37604.04 | 20-JUN-04:01 | 19798.90 | 0.00 |
July | 0.00 | 0.00 | 0.332133E+11 | 0.237617E+11 | 37498.49 | 06-JUL-04:01 | 20548.19 | 0.00 |
August | 0.00 | 0.00 | 0.365271E+11 | 0.259833E+11 | 37497.02 | 27-AUG-06:01 | 21006.54 | 0.00 |
September | 0.00 | 0.00 | 0.306922E+11 | 0.218884E+11 | 37425.74 | 11-SEP-04:01 | 22075.23 | 0.00 |
October | 0.00 | 0.00 | 0.252949E+11 | 0.191715E+11 | 37466.26 | 08-OCT-06:01 | 20335.64 | 0.00 |
November | 0.00 | 0.00 | 0.177776E+11 | 0.137050E+11 | 36069.66 | 03-NOV-04:01 | 23618.90 | 0.00 |
December | 0.00 | 0.00 | 0.102705E+11 | 0.779671E+10 | 34995.88 | 11-DEC-05:01 | 23018.23 | 0.00 |
Annual Sum or Average | 0.243763E+12 | 0.182199E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.677789E+10 | 0.530264E+10 | 34294.56 | 19798.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.365271E+11 | 0.259833E+11 | 37604.04 | 24824.62 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.197208E+10 | 0.32 | 3076.67 | 30-JAN-05:01 | 0.87 |
February | 0.179562E+10 | 0.32 | 3076.67 | 06-FEB-05:01 | 0.87 |
March | 0.202725E+10 | 0.33 | 3076.67 | 01-MAR-05:01 | 0.87 |
April | 0.197736E+10 | 0.34 | 3076.67 | 01-APR-04:01 | 0.87 |
May | 0.217393E+10 | 0.35 | 3076.67 | 01-MAY-04:01 | 0.86 |
June | 0.240740E+10 | 0.38 | 3076.67 | 01-JUN-04:01 | 0.87 |
July | 0.286589E+10 | 0.44 | 3076.67 | 01-JUL-04:01 | 0.86 |
August | 0.300331E+10 | 0.45 | 3076.67 | 01-AUG-04:01 | 0.86 |
September | 0.232485E+10 | 0.37 | 3076.67 | 01-SEP-04:01 | 0.86 |
October | 0.208466E+10 | 0.34 | 3076.67 | 01-OCT-06:01 | 0.86 |
November | 0.194544E+10 | 0.33 | 3076.67 | 01-NOV-04:01 | 0.87 |
December | 0.198361E+10 | 0.32 | 3076.67 | 01-DEC-05:01 | 0.87 |
Annual Sum or Average | 0.265614E+11 | 0.36 | |||
Minimum of Months | 0.179562E+10 | 0.32 | 3076.67 | 0.86 | |
Maximum of Months | 0.300331E+10 | 0.45 | 3076.67 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.924842E+10 | 0.50 | 8810.66 | 29-JAN-09:03 | 1.07 |
February | 0.840122E+10 | 0.50 | 14431.67 | 06-FEB-07:03 | 1.37 |
March | 0.942729E+10 | 0.51 | 14431.67 | 01-MAR-07:02 | 1.36 |
April | 0.911447E+10 | 0.50 | 14431.67 | 02-APR-08:62 | 1.37 |
May | 0.103606E+11 | 0.53 | 14431.67 | 01-MAY-05:03 | 1.36 |
June | 0.120193E+11 | 0.59 | 14431.67 | 01-JUN-05:01 | 1.37 |
July | 0.143515E+11 | 0.64 | 14431.67 | 01-JUL-05:02 | 1.36 |
August | 0.152201E+11 | 0.67 | 14431.67 | 01-AUG-04:01 | 1.36 |
September | 0.120910E+11 | 0.59 | 14431.67 | 01-SEP-05:01 | 1.36 |
October | 0.989956E+10 | 0.51 | 14431.67 | 01-OCT-07:02 | 1.36 |
November | 0.899169E+10 | 0.50 | 14431.67 | 01-NOV-06:02 | 1.36 |
December | 0.927228E+10 | 0.50 | 14431.67 | 10-DEC-09:02 | 1.37 |
Annual Sum or Average | 0.128397E+12 | 0.55 | |||
Minimum of Months | 0.840122E+10 | 0.50 | 8810.66 | 1.07 | |
Maximum of Months | 0.152201E+11 | 0.67 | 14431.67 | 1.37 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110495E+10 | 0.32 | 1717.69 | 23-JAN-05:02 | 0.87 |
February | 0.100782E+10 | 0.32 | 1717.69 | 06-FEB-05:01 | 0.87 |
March | 0.113841E+10 | 0.33 | 1717.69 | 01-MAR-05:01 | 0.87 |
April | 0.110623E+10 | 0.34 | 1717.69 | 01-APR-04:01 | 0.87 |
May | 0.121162E+10 | 0.35 | 1717.69 | 01-MAY-04:01 | 0.86 |
June | 0.131315E+10 | 0.38 | 1717.69 | 01-JUN-04:01 | 0.87 |
July | 0.159167E+10 | 0.47 | 1717.69 | 01-JUL-04:01 | 0.86 |
August | 0.175733E+10 | 0.52 | 1717.69 | 01-AUG-04:01 | 0.86 |
September | 0.147220E+10 | 0.44 | 1717.69 | 01-SEP-04:01 | 0.86 |
October | 0.126570E+10 | 0.37 | 1717.69 | 01-OCT-06:01 | 0.86 |
November | 0.110716E+10 | 0.34 | 1717.69 | 01-NOV-04:01 | 0.87 |
December | 0.111698E+10 | 0.33 | 1717.69 | 01-DEC-05:01 | 0.87 |
Annual Sum or Average | 0.151932E+11 | 0.38 | |||
Minimum of Months | 0.100782E+10 | 0.32 | 1717.69 | 0.86 | |
Maximum of Months | 0.175733E+10 | 0.52 | 1717.69 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100549E+10 | 0.33 | 1566.45 | 23-JAN-05:02 | 0.90 |
February | 0.916340E+09 | 0.33 | 1566.45 | 06-FEB-05:01 | 0.90 |
March | 0.103446E+10 | 0.34 | 1566.45 | 01-MAR-05:01 | 0.90 |
April | 0.100501E+10 | 0.35 | 1566.45 | 01-APR-04:01 | 0.90 |
May | 0.109179E+10 | 0.36 | 1566.45 | 01-MAY-04:01 | 0.89 |
June | 0.117405E+10 | 0.38 | 1566.45 | 01-JUN-04:01 | 0.90 |
July | 0.142976E+10 | 0.44 | 1566.45 | 01-JUL-04:01 | 0.89 |
August | 0.159009E+10 | 0.50 | 1566.45 | 01-AUG-04:01 | 0.89 |
September | 0.132401E+10 | 0.43 | 1566.45 | 01-SEP-04:01 | 0.89 |
October | 0.113677E+10 | 0.37 | 1566.45 | 01-OCT-06:01 | 0.89 |
November | 0.100424E+10 | 0.35 | 1566.45 | 01-NOV-04:01 | 0.90 |
December | 0.101502E+10 | 0.34 | 1566.45 | 01-DEC-05:01 | 0.90 |
Annual Sum or Average | 0.137271E+11 | 0.38 | |||
Minimum of Months | 0.916340E+09 | 0.33 | 1566.45 | 0.89 | |
Maximum of Months | 0.159009E+10 | 0.50 | 1566.45 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.03 | 0.00 |
March | 0.12 | 0.00 |
April | 0.52 | 0.00 |
May | 1.86 | 0.00 |
June | 2.75 | 0.00 |
July | 3.69 | 0.00 |
August | 3.77 | 0.00 |
September | 2.61 | 0.00 |
October | 0.79 | 0.00 |
November | 0.09 | 0.00 |
December | 0.04 | 0.00 |
Annual Sum or Average | 16.27 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.77 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.17 | 25.84 |
April | 0.35 | 12.21 |
May | 0.46 | 0.00 |
June | 0.56 | 0.00 |
July | 0.60 | 3.58 |
August | 0.71 | 6.08 |
September | 0.84 | 0.00 |
October | 0.61 | 0.00 |
November | 0.08 | 25.84 |
December | 0.17 | 25.84 |
Annual Sum or Average | 4.55 | 4.74 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.84 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.86 | 0.00 |
February | 1.57 | 0.00 |
March | 1.64 | 0.00 |
April | 1.27 | 0.00 |
May | 1.95 | 0.00 |
June | 2.74 | 0.00 |
July | 3.34 | 0.00 |
August | 3.31 | 0.00 |
September | 2.98 | 0.00 |
October | 1.96 | 0.00 |
November | 1.34 | 0.00 |
December | 2.08 | 0.00 |
Annual Sum or Average | 25.04 | 0.00 |
Minimum of Months | 0.86 | 0.00 |
Maximum of Months | 3.34 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.30 | 0.00 |
March | 0.73 | 0.00 |
April | 0.52 | 0.00 |
May | 1.86 | 0.00 |
June | 2.62 | 0.00 |
July | 3.27 | 0.00 |
August | 3.57 | 0.00 |
September | 2.98 | 0.00 |
October | 1.87 | 0.00 |
November | 0.93 | 0.00 |
December | 0.47 | 0.00 |
Annual Sum or Average | 19.12 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.57 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.06 | 0.00 |
February | 2.53 | 0.00 |
March | 1.29 | 0.00 |
April | 2.11 | 0.00 |
May | 2.94 | 0.00 |
June | 2.39 | 0.00 |
July | 2.86 | 0.00 |
August | 2.73 | 0.00 |
September | 2.06 | 0.00 |
October | 3.00 | 0.00 |
November | 1.92 | 0.00 |
December | 2.03 | 0.00 |
Annual Sum or Average | 27.91 | 0.00 |
Minimum of Months | 1.29 | 0.00 |
Maximum of Months | 3.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.400461E+10 | 1910566.15 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.472881E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.694451E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.949598E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.146125E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.173404E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.208990E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.218883E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.166166E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.129516E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.885665E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.553657E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.143876E+12 | 1910566.15 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.400461E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.218883E+11 | 1910566.15 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.203512E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.228384E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.311548E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.401277E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.582006E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.697701E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.837363E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.885638E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.696206E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.532493E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.381451E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.265112E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.602269E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.203512E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.885638E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.356637E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.374519E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.479635E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.580523E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.821655E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.949980E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.117114E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.128371E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.104805E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.858406E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.633651E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.449657E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.900757E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.356637E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.128371E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.275499E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.297198E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.389941E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.495062E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.727130E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.847248E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.105238E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.116029E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.941666E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.763465E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.550686E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.363201E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.786377E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.275499E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.116029E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.197208E+10 | 0.743949E+10 | 1528452.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179562E+10 | 0.107671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202725E+10 | 0.179112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197736E+10 | 0.272474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.217393E+10 | 0.447105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.240740E+10 | 0.541070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.286589E+10 | 0.637381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.300331E+10 | 0.667520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.232485E+10 | 0.526524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208466E+10 | 0.403341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194544E+10 | 0.255821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.198361E+10 | 0.131253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265614E+11 | 0.424367E+12 | 1528452.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.179562E+10 | 0.743949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.300331E+10 | 0.667520E+11 | 1528452.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.924842E+10 | 0.381618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.840122E+10 | 0.500125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.942729E+10 | 0.748141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.911447E+10 | 0.106980E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103606E+11 | 0.162113E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120193E+11 | 0.198114E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143515E+11 | 0.234713E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152201E+11 | 0.248953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120910E+11 | 0.202598E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.989956E+10 | 0.154396E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.899169E+10 | 0.103502E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.927228E+10 | 0.603584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128397E+12 | 0.163472E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.840122E+10 | 0.381618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152201E+11 | 0.248953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.110495E+10 | 0.974140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100782E+10 | 0.107925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113841E+10 | 0.140934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110623E+10 | 0.176988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121162E+10 | 0.257014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131315E+10 | 0.302744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159167E+10 | 0.366199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.175733E+10 | 0.400533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147220E+10 | 0.339423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126570E+10 | 0.284613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110716E+10 | 0.208271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111698E+10 | 0.134926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151932E+11 | 0.281698E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100782E+10 | 0.974140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175733E+10 | 0.400533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.100549E+10 | 0.677789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.916340E+09 | 0.794432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103446E+10 | 0.108357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100501E+10 | 0.146836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109179E+10 | 0.226341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117405E+10 | 0.271123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142976E+10 | 0.332133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159009E+10 | 0.365271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132401E+10 | 0.306922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113677E+10 | 0.252949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100424E+10 | 0.177776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101502E+10 | 0.102705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137271E+11 | 0.243763E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.916340E+09 | 0.677789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159009E+10 | 0.365271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.197208E+10 | 0.00 | 0.00 | 0.00 | 0.203253E+10 | 0.00 | 1910566.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179562E+10 | 0.00 | 0.00 | 0.00 | 0.293319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202725E+10 | 0.00 | 0.00 | 0.00 | 0.491726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197736E+10 | 0.00 | 0.00 | 0.00 | 0.751861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.217393E+10 | 0.00 | 0.00 | 0.00 | 0.124385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.240740E+10 | 0.00 | 0.00 | 0.00 | 0.149330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.286589E+10 | 0.00 | 0.00 | 0.00 | 0.180332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.300331E+10 | 0.00 | 0.00 | 0.00 | 0.188850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.232485E+10 | 0.00 | 0.00 | 0.00 | 0.142918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208466E+10 | 0.00 | 0.00 | 0.00 | 0.108669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194544E+10 | 0.00 | 0.00 | 0.00 | 0.691121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.198361E+10 | 0.00 | 0.00 | 0.00 | 0.355296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265614E+11 | 0.00 | 0.00 | 0.00 | 0.117314E+12 | 0.00 | 1910566.15 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.179562E+10 | 0.00 | 0.00 | 0.00 | 0.203253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.300331E+10 | 0.00 | 0.00 | 0.00 | 0.188850E+11 | 0.00 | 1910566.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.924842E+10 | 0.00 | 0.00 | 0.00 | 0.111028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.840122E+10 | 0.00 | 0.00 | 0.00 | 0.144372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.942729E+10 | 0.00 | 0.00 | 0.00 | 0.217275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.911447E+10 | 0.00 | 0.00 | 0.00 | 0.310132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103606E+11 | 0.00 | 0.00 | 0.00 | 0.478400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120193E+11 | 0.00 | 0.00 | 0.00 | 0.577508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143515E+11 | 0.00 | 0.00 | 0.00 | 0.693848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152201E+11 | 0.00 | 0.00 | 0.00 | 0.733437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120910E+11 | 0.00 | 0.00 | 0.00 | 0.575296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.989956E+10 | 0.00 | 0.00 | 0.00 | 0.433497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.899169E+10 | 0.00 | 0.00 | 0.00 | 0.291534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.927228E+10 | 0.00 | 0.00 | 0.00 | 0.172389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128397E+12 | 0.00 | 0.00 | 0.00 | 0.473872E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.840122E+10 | 0.00 | 0.00 | 0.00 | 0.111028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152201E+11 | 0.00 | 0.00 | 0.00 | 0.733437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.110495E+10 | 0.00 | 0.00 | 0.00 | 0.246142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100782E+10 | 0.00 | 0.00 | 0.00 | 0.273738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113841E+10 | 0.00 | 0.00 | 0.00 | 0.365794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110623E+10 | 0.00 | 0.00 | 0.00 | 0.469900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121162E+10 | 0.00 | 0.00 | 0.00 | 0.700493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131315E+10 | 0.00 | 0.00 | 0.00 | 0.818666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159167E+10 | 0.00 | 0.00 | 0.00 | 0.101197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.175733E+10 | 0.00 | 0.00 | 0.00 | 0.110798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147220E+10 | 0.00 | 0.00 | 0.00 | 0.900834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126570E+10 | 0.00 | 0.00 | 0.00 | 0.731836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110716E+10 | 0.00 | 0.00 | 0.00 | 0.522935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111698E+10 | 0.00 | 0.00 | 0.00 | 0.337959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151932E+11 | 0.00 | 0.00 | 0.00 | 0.748825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.100782E+10 | 0.00 | 0.00 | 0.00 | 0.246142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175733E+10 | 0.00 | 0.00 | 0.00 | 0.110798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.100549E+10 | 0.00 | 0.00 | 0.00 | 0.174949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.916340E+09 | 0.00 | 0.00 | 0.00 | 0.205564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103446E+10 | 0.00 | 0.00 | 0.00 | 0.286495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100501E+10 | 0.00 | 0.00 | 0.00 | 0.394561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109179E+10 | 0.00 | 0.00 | 0.00 | 0.617951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117405E+10 | 0.00 | 0.00 | 0.00 | 0.729842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142976E+10 | 0.00 | 0.00 | 0.00 | 0.909404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159009E+10 | 0.00 | 0.00 | 0.00 | 0.100128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132401E+10 | 0.00 | 0.00 | 0.00 | 0.809265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113677E+10 | 0.00 | 0.00 | 0.00 | 0.649787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100424E+10 | 0.00 | 0.00 | 0.00 | 0.450261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101502E+10 | 0.00 | 0.00 | 0.00 | 0.261698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137271E+11 | 0.00 | 0.00 | 0.00 | 0.649106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.916340E+09 | 0.00 | 0.00 | 0.00 | 0.174949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159009E+10 | 0.00 | 0.00 | 0.00 | 0.100128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.836969E+09 | 0.268379E+09 | 0.00 | 5969081.51 | 5383150.67 | 0.00 | 0.102254E+10 | 0.00 | 0.22 |
February | 0.439333E+09 | 0.824400E+09 | 0.00 | 5302840.03 | 519907.11 | 0.00 | 0.522342E+09 | 0.00 | 0.22 |
March | 0.157228E+09 | 0.191131E+10 | 0.00 | 6258637.66 | 0.00 | 0.00 | 0.407296E+09 | 0.00 | 0.23 |
April | 369429.90 | 0.460967E+10 | 0.00 | 6710744.72 | 0.00 | 0.00 | 0.127992E+09 | 0.00 | 0.23 |
May | 0.00 | 0.883100E+10 | 0.00 | 1201029.61 | 0.00 | 0.00 | 1164909.68 | 0.00 | 0.23 |
June | 0.00 | 0.130087E+11 | 0.00 | 301296.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
July | 0.00 | 0.168220E+11 | 0.00 | 780520.24 | 0.00 | 0.00 | 217451.00 | 0.00 | 0.24 |
August | 0.00 | 0.182252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
September | 0.00 | 0.142855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
October | 0.00 | 0.939318E+10 | 0.00 | 1319627.52 | 0.00 | 0.00 | 2954287.37 | 0.00 | 0.23 |
November | 1839912.29 | 0.489976E+10 | 0.00 | 1752445.11 | 939531.59 | 0.00 | 25141775.25 | 0.00 | 0.22 |
December | 0.321338E+09 | 0.140905E+10 | 0.00 | 5747287.83 | 2714291.27 | 0.00 | 0.497317E+09 | 0.00 | 0.22 |
Annual Sum or Average | 0.175708E+10 | 0.944881E+11 | 0.00 | 35343510.53 | 9556880.65 | 0.00 | 0.260696E+10 | 0.00 | 0.23 |
Minimum of Months | 0.00 | 0.268379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 0.836969E+09 | 0.182252E+11 | 0.00 | 6710744.72 | 5383150.67 | 0.00 | 0.102254E+10 | 0.00 | 0.24 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.605642E+10 | 0.252327E+10 | 0.00 | 32864155.86 | 55464453.11 | 0.00 | 0.647312E+10 | 0.00 | 0.43 |
February | 0.339826E+10 | 0.677541E+10 | 0.00 | 24577393.66 | 45364640.57 | 0.00 | 0.342980E+10 | 0.00 | 0.43 |
March | 0.225552E+10 | 0.146392E+11 | 0.00 | 19199743.95 | 61098286.97 | 0.00 | 0.218447E+10 | 0.00 | 0.44 |
April | 0.709898E+09 | 0.337058E+11 | 0.00 | 11493276.26 | 0.293460E+09 | 0.00 | 0.950186E+09 | 0.00 | 0.43 |
May | 15078253.27 | 0.627652E+11 | 0.00 | 6370681.80 | 0.403684E+09 | 0.00 | 0.101468E+09 | 0.00 | 0.43 |
June | 540399.26 | 0.913077E+11 | 0.00 | 2148141.11 | 0.586030E+09 | 0.00 | 5697830.79 | 0.00 | 0.44 |
July | 1962908.19 | 0.116899E+12 | 0.00 | 1739987.87 | 0.730894E+09 | 0.00 | 11591489.60 | 0.00 | 0.44 |
August | 0.00 | 0.126566E+12 | 0.00 | 0.00 | 0.728362E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 1468973.75 | 0.997758E+11 | 0.00 | 681459.12 | 0.695487E+09 | 0.00 | 9059245.13 | 0.00 | 0.44 |
October | 26120440.29 | 0.650247E+11 | 0.00 | 3773804.98 | 0.927821E+09 | 0.00 | 0.118208E+09 | 0.00 | 0.43 |
November | 0.276573E+09 | 0.343920E+11 | 0.00 | 3962603.70 | 0.384917E+09 | 0.00 | 0.232795E+09 | 0.00 | 0.43 |
December | 0.308131E+10 | 0.107415E+11 | 0.00 | 24085476.52 | 62990764.68 | 0.00 | 0.289088E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.158232E+11 | 0.665115E+12 | 0.00 | 0.130897E+09 | 0.497557E+10 | 0.00 | 0.164073E+11 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.252327E+10 | 0.00 | 0.00 | 45364640.57 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.605642E+10 | 0.126566E+12 | 0.00 | 32864155.86 | 0.927821E+09 | 0.00 | 0.647312E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.337791E+09 | 0.650779E+09 | 0.00 | 6563490.78 | 0.00 | 0.00 | 0.517749E+09 | 0.00 | 0.43 |
February | 0.154858E+09 | 0.112819E+10 | 0.00 | 4114924.19 | 0.00 | 0.00 | 0.265606E+09 | 0.00 | 0.43 |
March | 48260109.44 | 0.187712E+10 | 0.00 | 4701074.13 | 0.00 | 0.00 | 0.230865E+09 | 0.00 | 0.44 |
April | 0.00 | 0.377400E+10 | 0.00 | 3681606.27 | 0.00 | 0.00 | 75009061.26 | 0.00 | 0.44 |
May | 0.00 | 0.675365E+10 | 0.00 | 959380.70 | 0.00 | 0.00 | 616468.93 | 0.00 | 0.45 |
June | 0.00 | 0.975753E+10 | 0.00 | 375833.29 | 555853.59 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.126890E+11 | 0.00 | 531973.51 | 629525.36 | 0.00 | 543122.80 | 0.00 | 0.46 |
August | 0.00 | 0.139114E+11 | 0.00 | 0.00 | 1563369.90 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.110994E+11 | 0.00 | 7616.61 | 625366.97 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.755769E+10 | 0.00 | 847961.20 | 0.00 | 0.00 | 342661.87 | 0.00 | 0.44 |
November | 0.00 | 0.437488E+10 | 0.00 | 1527548.40 | 0.00 | 0.00 | 9836853.47 | 0.00 | 0.43 |
December | 60599558.88 | 0.177619E+10 | 0.00 | 4549189.99 | 0.00 | 0.00 | 0.255095E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.601509E+09 | 0.753498E+11 | 0.00 | 27860599.08 | 3374115.82 | 0.00 | 0.135566E+10 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.650779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.337791E+09 | 0.139114E+11 | 0.00 | 6563490.78 | 1563369.90 | 0.00 | 0.517749E+09 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.487123E+09 | 0.487922E+09 | 0.00 | 4399964.20 | 406048.33 | 0.00 | 0.483449E+09 | 0.00 | 0.43 |
February | 0.259105E+09 | 0.926728E+09 | 0.00 | 3187606.57 | 0.00 | 0.00 | 0.266439E+09 | 0.00 | 0.43 |
March | 0.129873E+09 | 0.167069E+10 | 0.00 | 3283725.71 | 0.00 | 0.00 | 0.218925E+09 | 0.00 | 0.44 |
April | 305091.43 | 0.356446E+10 | 0.00 | 2905225.19 | 0.00 | 0.00 | 0.102843E+09 | 0.00 | 0.44 |
May | 0.00 | 0.661027E+10 | 0.00 | 827941.87 | 0.00 | 0.00 | 730685.90 | 0.00 | 0.44 |
June | 0.00 | 0.957477E+10 | 0.00 | 338806.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.124655E+11 | 0.00 | 538346.00 | 451355.84 | 0.00 | 51204.47 | 0.00 | 0.46 |
August | 0.00 | 0.136906E+11 | 0.00 | 0.00 | 493011.84 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.109019E+11 | 0.00 | 4854.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.739453E+10 | 0.00 | 779255.60 | 0.00 | 0.00 | 471120.05 | 0.00 | 0.44 |
November | 0.00 | 0.417351E+10 | 0.00 | 1331242.53 | 0.00 | 0.00 | 14760072.96 | 0.00 | 0.43 |
December | 0.176964E+09 | 0.151743E+10 | 0.00 | 3353601.70 | 145963.96 | 0.00 | 0.227782E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.105337E+10 | 0.729783E+11 | 0.00 | 20950570.58 | 1496379.97 | 0.00 | 0.131545E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.487922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.487123E+09 | 0.136906E+11 | 0.00 | 4399964.20 | 493011.84 | 0.00 | 0.483449E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |