Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2020-06-03 19:12:11
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1148.04 | 500.46 | 500.46 |
Net Site Energy | 1148.04 | 500.46 | 500.46 |
Total Source Energy | 3432.14 | 1496.14 | 1496.14 |
Net Source Energy | 3432.14 | 1496.14 | 1496.14 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 10.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 390.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 293.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 38.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 133.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 87.54 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1050.24 | 97.80 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 10.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 390.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 293.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 38.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 133.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 87.54 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 144.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 228.54 | 42.63 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 457.82 | 42.63 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 144.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 228.54 | 42.63 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 457.82 | 42.63 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1050.245 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1050.245 | 100.00 |
Total On-Site and Utility Electric Sources | 1050.245 | 100.00 |
Total Electricity End Uses | 1050.245 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 501.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.5670 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 13.1320 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 13.1320 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 13.1320 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 10.7639 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 12.1980 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 12.1980 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-15:00 | 05-FEB-09:20 | - | - | - | 03-JAN-12:09 |
Heating | 0.00 | 86834.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 54708.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19720.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10782.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 95952.32 | 88694.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 86834.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 54708.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19720.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 10782.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 11.13 | 0.00 | 0.00 | 0.00 |
Cooling | 1236.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 928.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 121.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 615.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 423.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 94.89 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3326.13 | 106.01 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 4.85 | 0.00 | 0.00 | 0.00 |
Cooling | 538.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 404.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 184.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 41.36 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1449.93 | 46.21 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 4.85 | 0.00 | 0.00 | 0.00 |
Cooling | 538.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 404.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 53.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 184.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 41.36 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1449.93 | 46.21 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.96 |
CORE_RETAIL DIRECT AIR | 7.04 |
POINT_OF_SALE DIRECT AIR | 1.10 |
FRONT_RETAIL DIRECT AIR | 0.854280 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 0.843638 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 0.843638 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 24873.38 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 49868.47 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 200960.63 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 28953.05 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 23209.51 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.96 | 1.96 | 1.96 | 1.96 | 1.97 | 1.97 | 1.00 | 0.995234 | 1.97 |
PSZ-AC:2 | 7.04 | 7.04 | 7.04 | 7.04 | 7.25 | 7.25 | 1.00 | 0.970476 | 7.25 |
PSZ-AC:3 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.00 | 1.00 | 1.10 |
PSZ-AC:4 | 0.854280 | 0.854280 | 0.854280 | 0.854280 | 0.854280 | 0.854280 | 1.00 | 1.00 | 0.854280 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.97 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 7.25 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.10 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 0.854280 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.97 | 1.97 | 1.97 | 1.30 | 39789.16 | 49868.47 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.25 | 7.25 | 7.25 | 4.79 | 180064.15 | 200960.63 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.10 | 1.10 | 1.10 | 0.728273 | 24232.52 | 28953.05 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.854280 | 0.854280 | 0.854280 | 0.563825 | 19954.77 | 23209.51 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.97 | 0.985155 | 1.31 | 37335.14 | 39789.16 | 19894.58 | 19894.58 | 0.732371 | 0.732370 | 0.732370 | 0.732370 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 7.25 | 3.63 | 4.83 | 177366.63 | 180064.15 | 90032.07 | 90032.07 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.10 | 0.551720 | 0.735627 | 22857.03 | 24232.52 | 12116.26 | 12116.26 | 0.708129 | 0.708130 | 0.708130 | 0.708130 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 0.854280 | 0.427140 | 0.569520 | 18909.70 | 19954.77 | 9977.39 | 9977.39 | 0.691547 | 0.691550 | 0.691550 | 0.691550 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.97 | 2108.33 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.25 | 12216.17 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.10 | 1221.69 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.854280 | 945.82 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.567 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.637 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 13.132 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 16.362 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 13.132 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 34.652 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 13.132 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 16.362 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 10.764 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.764 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2874.639 | 7.567 | 46.863 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2874.639 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 21017.495 | 13.132 | 81.326 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21017.495 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 1980.433 | 13.132 | 81.326 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1980.433 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 1980.433 | 13.132 | 81.326 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1980.433 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 129.167 | 10.764 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 129.167 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.9837 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8493 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 9 | 0.31844121E-15 | 0.33891907E-16 | -0.14717764E-09 | -0.34085343E-17 |
25 | 8 | 0.21517510E-07 | 0.13210865E-12 | 0.37403321E-03 | -0.24466149E-09 |
26 | 7 | -0.12129356E-01 | 0.68855956E-08 | -0.22924263E-01 | 0.13791520E-03 |
27 | 6 | 0.40230169 | 0.24029480E-05 | 0.46949424 | -0.47118258E-02 |
28 | 5 | -5.1608121 | 0.89965799E-04 | -4.4213154 | 0.62814943E-01 |
29 | 4 | 32.871256 | 0.73775273E-03 | 21.362378 | -0.42037561 |
30 | 3 | -110.94624 | 0.16114037E-02 | -55.469893 | 1.5111496 |
31 | 2 | 196.85374 | 0.90819125E-03 | 77.733479 | -2.8963115 |
32 | 1 | -171.06207 | 0.97128343E-04 | -55.213590 | 2.7437919 |
33 | 0 | 57.057407 | 0.55402955E-06 | 15.565444 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.54_SHGC_0.25 | 30 | 1 | VerySmooth | 3.070 | 0.252 | 0.162 | 0.276 |
2 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 31 | 1 | VerySmooth | 3.695 | 0.347 | 0.243 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.33471E-002 | 0.16139 | 0.60602 | 0.60602 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.56025E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.24267 | 0.45800 | 0.45800 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.96142E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1915 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 23100.86652 | 27721.03982 | 1.63410 | 1.96092 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 18116.28351 | 21739.54022 | 0.75955 | 0.91147 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 83361.49264 | 100033.79117 | 5.86425 | 7.03710 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 49224.23344 | 59069.08013 | 2.03264 | 2.43917 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 12871.48563 | 15445.78276 | 0.91954 | 1.10344 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 9030.35315 | 10836.42378 | 0.38060 | 0.45672 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 10035.11037 | 12042.13244 | 0.71190 | 0.85428 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 9030.35315 | 10836.42378 | 0.38060 | 0.45672 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90000 | 1.65138E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 20724.51804 | 24869.42165 | 0.70303 | 0.84364 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 27714.39 | 1.97031 | 1.97031 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 25620.25 | 0.91147 | 0.91147 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 112403.39 | 7.25118 | 7.25118 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 93704.70 | 2.43917 | 2.43917 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 16416.50 | 1.10344 | 1.10344 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 14045.28 | 0.45672 | 0.45672 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 13606.10 | 0.85428 | 0.85428 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 14045.28 | 0.45672 | 0.45672 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.96092 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.03710 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10344 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.85428 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.84364 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 0.84364 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 24873.38254 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.96092 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.96092 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.96092 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.96092 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.97031 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.97031 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.99523 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.03710 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.03710 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.03710 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.03710 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.25118 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.25118 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97048 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.10344 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.10344 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.10344 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.10344 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10344 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.10344 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.85428 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.85428 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.85428 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.85428 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.85428 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.85428 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.97031 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.25118 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.10344 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.85428 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.97031 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.97031 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.97031 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.97031 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.30041 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.97031 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.98516 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.31354 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 37335.14461 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 39789.16000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 19894.58000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 19894.58000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73237 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73237 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73237 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73237 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39789.16000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 49868.46581 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.97031 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2108.32619 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 49868.46581 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.25118 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.25118 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.25118 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.25118 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.78578 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.25118 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.62559 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.83412 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 177366.62665 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 180064.15000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 90032.07500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 90032.07500 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 180064.15000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 200960.63457 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.25118 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 12216.17492 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 200960.63457 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10344 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10344 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10344 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10344 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.72827 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10344 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55172 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.73563 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22857.02910 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 24232.52000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12116.26000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12116.26000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70813 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70813 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70813 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70813 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24232.52000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28953.04699 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10344 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1221.68748 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28953.04699 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.85428 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.85428 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.85428 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.85428 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.56382 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.85428 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.42714 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.56952 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18909.70482 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19954.77000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9977.38500 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9977.38500 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69155 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69155 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69155 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69155 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19954.77000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23209.50962 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.85428 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 945.82355 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 23209.50962 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 38240.5 | 11.38 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 174343.6 | 13.24 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 23364.0 | 118.35 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 19281.6 | 156.68 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | N/A | 3.695 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.54_SHGC_0.25 | N/A | 3.070 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.54_SHGC_0.25 | N/A | 3.070 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.54_SHGC_0.25 | N/A | 3.070 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 8 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 1.7230645298E-002 | 6.1795099572E-002 | Pass | Pass | 0.2583442520 | 2.6526084351 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 2.4752411127E-002 | 0.1154147869 | Pass | Pass | 3.6260325259E-002 | 0.1476697095 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 0.1896422299 | 0.3100297822 | Pass | Pass | 0.4391873423 | 1.6396828466 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 0.1352774294 | 0.2456199434 | Pass | Pass | 0.3913444526 | 1.6103471055 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1608406424 | 0.3554118217 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.54_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 3.070 | 0.252 | 0.276 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.54_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 3.070 | 0.252 | 0.276 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.54_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 3.070 | 0.252 | 0.276 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 3.208 | 0.273 | 0.303 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 3.208 | 0.273 | 0.303 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.5670 | 379.89 | 2874.64 | LightsWired | BLDG_LIGHT_BACK_SCH | 55.08 | 168.00 | 52.05 | 0.0000 | Y | 28.09 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 13.1320 | 1600.48 | 21017.49 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 55.12 | 0.0000 | Y | 217.47 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 13.1320 | 150.81 | 1980.43 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 65.03 | 0.0000 | Y | 24.18 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 13.1320 | 150.81 | 1980.43 | LightsWired | BLDG_LIGHT_FRONT_SCH | 67.15 | 168.00 | 63.01 | 0.0000 | Y | 23.42 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 10.7639 | 12.00 | 129.17 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 57.54 | 168.00 | 3.36 | 0.0000 | Y | 0.08 |
Interior Lighting Total | 12.1980 | 2293.99 | 27982.17 | 293.24 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 21017.49 | 5254.37 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 21017.49 | 5254.37 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 316.30 | AstronomicalClock | - | 41.73 | 41.73 | 2.48 | |
EXTERIOR_LIGHTS_B | 3054.90 | AstronomicalClock | - | 83.73 | 62.73 | 35.97 | |
Exterior Lighting Total | 3371.20 | 38.45 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 39789.16 | 29140.39 | 10648.77 | 0.73 | 3.73 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 180064.15 | 121737.77 | 58326.38 | 0.68 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 24232.52 | 17159.77 | 7072.75 | 0.71 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 19954.77 | 13799.72 | 6155.05 | 0.69 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 38240.5 | 11.38 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 174343.6 | 13.24 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 23364.0 | 118.35 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 19281.6 | 156.68 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 24873.38 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 49868.47 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 200960.63 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28953.05 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 23209.51 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.84 | 934.04 | 1107.16 | 1.00 | 1.43 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.97 | 2108.33 | 1070.05 | 1.00 | 1.32 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 7.25 | 12216.17 | 1684.71 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.10 | 1221.69 | 1107.16 | 1.00 | 1.38 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.85 | 945.82 | 1107.16 | 1.00 | 1.44 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 23100.87 | 27721.04 | 72.97 | 1.634 | 1.961 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00960 | 28.05 | 0.01651 | 0.232 | 0.00 |
CORE_RETAIL | 83361.49 | 100033.79 | 62.50 | 5.864 | 7.037 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.88 | 0.00991 | 28.05 | 0.01651 | 1.890 | 0.00 |
POINT_OF_SALE | 12871.49 | 15445.78 | 102.42 | 0.920 | 1.103 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00903 | 28.05 | 0.01651 | 0.178 | 0.00 |
FRONT_RETAIL | 10035.11 | 12042.13 | 79.85 | 0.712 | 0.854 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00947 | 28.05 | 0.01651 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.50 | 100.00 | 0.00001 | 33.90 | 0.01651 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 18116.28 | 21739.54 | 57.23 | 0.760 | 0.911 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00756 | 4.60 | 0.00526 | 0.232 | 0.00 |
CORE_RETAIL | 49224.23 | 59069.08 | 36.91 | 2.033 | 2.439 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00782 | 4.60 | 0.00526 | 1.890 | 0.00 |
POINT_OF_SALE | 9030.35 | 10836.42 | 71.85 | 0.381 | 0.457 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00768 | 4.60 | 0.00526 | 0.178 | 0.00 |
FRONT_RETAIL | 9030.35 | 10836.42 | 71.85 | 0.381 | 0.457 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00768 | 4.60 | 0.00526 | 0.178 | 0.00 |
FRONT_ENTRY | 20724.52 | 24869.42 | 2072.45 | 0.703 | 0.844 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 16.00 | 15.97 | 0.00614 | 4.60 | 0.00526 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.97 | 1.97 | 0.91 | 0.91 | 1.9703 | 1.9609 | 1.9703 | 0.9952 | 1.0000 |
PSZ-AC:2 | 7.25 | 7.25 | 2.44 | 2.44 | 7.2512 | 7.0371 | 7.2512 | 0.9705 | 1.0000 |
PSZ-AC:3 | 1.10 | 1.10 | 0.46 | 0.46 | 1.1034 | 1.1034 | 1.1034 | 1.0000 | 1.0000 |
PSZ-AC:4 | 0.85 | 0.85 | 0.46 | 0.46 | 0.8543 | 0.8543 | 0.8543 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 24873.383 | 24873.383 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 24873.38 | 24873.38 | 0.843638 | 15.78 | 10.90 | 0.00612335 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 15.97 | 0.00613815 | 54.5090 | 24869.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 19894.580 | 0.000 | 1.970310 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 19894.58 | 14805.87 | 1.970310 | 24.43 | 17.99 | 0.01027001 | 12.80 | 12.09 | 0.00850000 | 28.55 | 0.01651377 | 23.71 | 11.7528 | 23.89 | 0.00960276 | 51.9148 | 23100.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 49868.466 | 49868.466 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 49868.47 | 49868.47 | 1.970311 | 16.75 | 12.18 | 0.00697527 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 11.7528 | 21.11 | 0.00756044 | 48.5431 | 18116.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 90032.075 | 0.000 | 7.251180 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 90032.07 | 61432.14 | 7.251180 | 26.72 | 19.55 | 0.01131972 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01651378 | 25.10 | 26.0676 | 23.88 | 0.00991402 | 53.5738 | 82257.92 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 200960.635 | 200960.635 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 200960.63 | 200960.63 | 7.251183 | 8.22 | 7.14 | 0.00583392 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 26.0676 | 21.11 | 0.00781991 | 50.1860 | 49224.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 12116.260 | 0.000 | 1.103440 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 12116.26 | 9228.21 | 1.103440 | 25.56 | 18.35 | 0.01025202 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01651378 | 25.10 | 16.1414 | 23.89 | 0.00903471 | 48.8825 | 12070.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 28953.047 | 28953.047 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28953.05 | 28953.05 | 1.103444 | 14.56 | 11.02 | 0.00673286 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 16.1413 | 21.11 | 0.00767626 | 49.2776 | 9030.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 9977.385 | 0.000 | 0.854280 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 9977.39 | 7260.03 | 0.854280 | 25.98 | 18.80 | 0.01065639 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01651378 | 25.10 | 20.8492 | 23.89 | 0.00946805 | 51.1967 | 9691.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 23209.510 | 23209.510 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23209.51 | 23209.51 | 0.854280 | 14.56 | 11.02 | 0.00673286 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 20.8492 | 21.11 | 0.00767626 | 49.2776 | 9030.35 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 24873.383 | 24873.383 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.843638 | 1.01503711 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 24873.38 | 24873.38 | 1.0000 | 1.01503711 | 0.843638 | 15.78 | 10.90 | 0.00612335 | 31347.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24873.38 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 15.97 | 0.00613815 | 15.97 | 0.00613815 | 54.5090 | 24869.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19894.580 | 0.000 | 1.970310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9314 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 19894.58 | 14805.87 | 1.0000 | 2.37061177 | 1.970310 | 24.43 | 17.99 | 0.01027001 | 50703.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19894.58 | 28.55 | 0.01651377 | 23.71 | 0.23156651 | 11.7528 | 23.89 | 0.00943846 | 23.89 | 0.00960276 | 51.9148 | 23100.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 49868.466 | 49868.466 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.970311 | 2.37061328 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 49868.47 | 49868.47 | 1.0000 | 2.37061328 | 1.970311 | 16.75 | 12.18 | 0.00697527 | 34493.6 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49868.47 | 4.60 | 0.00525715 | 4.60 | 0.23156651 | 11.7528 | 20.89 | 0.00756044 | 21.11 | 0.00756044 | 48.5431 | 18116.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 90032.075 | 0.000 | 7.251180 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.8828 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 90032.07 | 61432.14 | 1.0000 | 8.72437974 | 7.251180 | 26.72 | 19.55 | 0.01131972 | 55723.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90032.07 | 33.90 | 0.01651378 | 25.10 | 1.89021192 | 26.0676 | 23.89 | 0.00926916 | 23.88 | 0.00991402 | 53.5738 | 82257.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 200960.635 | 200960.635 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.251183 | 8.72438389 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 200960.63 | 200960.63 | 1.0000 | 8.72438389 | 7.251183 | 8.22 | 7.14 | 0.00583392 | 22944.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 200960.63 | 4.60 | 0.00525715 | 4.60 | 1.89021192 | 26.0676 | 20.71 | 0.00781991 | 21.11 | 0.00781991 | 50.1860 | 49224.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12116.260 | 0.000 | 1.103440 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8980 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 12116.26 | 9228.21 | 1.0000 | 1.32762248 | 1.103440 | 25.56 | 18.35 | 0.01025202 | 51814.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12116.26 | 33.90 | 0.01651378 | 25.10 | 0.17811053 | 16.1414 | 23.89 | 0.00899277 | 23.89 | 0.00903471 | 48.8825 | 12070.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28953.047 | 28953.047 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.103444 | 1.32762709 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28953.05 | 28953.05 | 1.0000 | 1.32762709 | 1.103444 | 14.56 | 11.02 | 0.00673286 | 31655.3 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28953.05 | 4.60 | 0.00525715 | 4.60 | 0.17811053 | 16.1413 | 20.93 | 0.00767626 | 21.11 | 0.00767626 | 49.2776 | 9030.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9977.385 | 0.000 | 0.854280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6497 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 9977.39 | 7260.03 | 1.0000 | 1.02784142 | 0.854280 | 25.98 | 18.80 | 0.01065639 | 53267.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9977.39 | 33.90 | 0.01651378 | 25.10 | 0.17811053 | 20.8492 | 23.89 | 0.00911317 | 23.89 | 0.00946805 | 51.1967 | 9691.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23209.510 | 23209.510 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.854280 | 1.02784139 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23209.51 | 23209.51 | 1.0000 | 1.02784139 | 0.854280 | 14.56 | 11.02 | 0.00673286 | 31655.3 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23209.51 | 4.60 | 0.00525715 | 4.60 | 0.17811053 | 20.8492 | 20.93 | 0.00767626 | 21.11 | 0.00767626 | 49.2776 | 9030.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialEnthalpy | 0.23 | 1.97 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialEnthalpy | 1.89 | 7.25 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialEnthalpy | 0.18 | 1.10 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialEnthalpy | 0.18 | 0.85 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 3196.67 | 1345.67 | 173.33 |
CORE_RETAIL | 3583.33 | 1284.00 | 402.17 |
POINT_OF_SALE | 3697.83 | 566.33 | 37.83 |
FRONT_RETAIL | 3560.50 | 964.50 | 207.33 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3893.67 | 1692.17 | 501.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 1.33 | 11.33 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 0.17 | 216.33 | 0.00 | 0.00 |
FRONT_RETAIL | 0.50 | 68.83 | 0.00 | 0.00 |
FRONT_ENTRY | 240.83 | 0.00 | 0.00 | 0.00 |
Facility | 242.50 | 233.50 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.44 | 61.34 | 2317.33 | 0.490 | 0.022 | 0.000 | 0.000 |
CORE_RETAIL | 128.26 | 258.43 | 9762.95 | 0.788 | 0.004 | 0.000 | 0.000 |
POINT_OF_SALE | 12.09 | 24.35 | 919.94 | 0.929 | 0.024 | 0.000 | 0.000 |
FRONT_RETAIL | 12.09 | 24.35 | 919.94 | 0.827 | 0.024 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.44 | 61.34 | 2317.33 | 0.353 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.26 | 258.43 | 9762.95 | 0.684 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.09 | 24.35 | 919.94 | 0.684 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.09 | 24.35 | 919.94 | 0.684 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1050.24 | 2265.44 | 01-JAN-07:30 | 95952.32 | 22-JUL-16:00 |
Electricity:Building | 487.53 | 2265.44 | 01-JAN-00:10 | 35190.60 | 02-JAN-15:20 |
Electricity:Zone:BACK_SPACE | 77.86 | 535.60 | 01-JAN-00:10 | 4774.71 | 02-JAN-09:10 |
InteriorLights:Electricity | 293.24 | 493.85 | 01-JAN-00:10 | 24449.72 | 02-JAN-15:20 |
InteriorLights:Electricity:Zone:BACK_SPACE | 28.09 | 81.78 | 01-JAN-00:10 | 2023.29 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 293.24 | 493.85 | 01-JAN-00:10 | 24449.72 | 02-JAN-15:20 |
Electricity:Zone:CORE_RETAIL | 301.40 | 1109.80 | 01-JAN-00:10 | 23555.33 | 02-JAN-15:20 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 217.47 | 344.55 | 01-JAN-00:10 | 18915.75 | 02-JAN-15:20 |
Electricity:Zone:POINT_OF_SALE | 76.87 | 512.89 | 01-JAN-00:10 | 4695.10 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 24.18 | 32.47 | 01-JAN-00:10 | 1782.39 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 31.33 | 104.57 | 01-JAN-00:10 | 2162.89 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 23.42 | 32.47 | 01-JAN-00:10 | 1725.71 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 0.08 | 2.58 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 0.08 | 2.58 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 |
InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.77 | 453.82 | 01-JAN-00:10 | 2751.42 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 83.93 | 765.25 | 01-JAN-00:10 | 4639.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.69 | 480.42 | 01-JAN-00:10 | 2912.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.91 | 72.11 | 01-JAN-00:10 | 437.18 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1050.24 | 2265.44 | 01-JAN-07:30 | 95952.32 | 22-JUL-16:00 |
ElectricityPurchased:Plant | 1050.24 | 2265.44 | 01-JAN-07:30 | 95952.32 | 22-JUL-16:00 |
Cogeneration:ElectricityPurchased | 1050.24 | 2265.44 | 01-JAN-07:30 | 95952.32 | 22-JUL-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1050.24 | 2265.44 | 01-JAN-07:30 | 95952.32 | 22-JUL-16:00 |
ElectricityNet:Plant | 1050.24 | 2265.44 | 01-JAN-07:30 | 95952.32 | 22-JUL-16:00 |
Cogeneration:ElectricityNet | 1050.24 | 2265.44 | 01-JAN-07:30 | 95952.32 | 22-JUL-16:00 |
Electricity:HVAC | 524.26 | 0.00 | 01-JAN-00:10 | 65490.65 | 22-JUL-16:00 |
Fans:Electricity | 133.87 | 0.00 | 01-JAN-00:10 | 11173.15 | 10-SEP-08:10 |
General:Fans:Electricity | 133.87 | 0.00 | 01-JAN-00:10 | 11173.15 | 10-SEP-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 390.40 | 0.00 | 01-JAN-00:10 | 54708.22 | 22-JUL-16:00 |
ExteriorLights:Electricity | 38.45 | 0.00 | 01-JAN-07:30 | 3371.20 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 38.45 | 0.00 | 01-JAN-07:30 | 3371.20 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 97.80 | 1860.00 | 03-JAN-18:10 | 88694.31 | 05-FEB-09:20 |
Gas:Plant | 87.54 | 1860.00 | 03-JAN-18:10 | 4929.90 | 23-JAN-13:00 |
WaterSystems:Gas | 87.54 | 1860.00 | 03-JAN-18:10 | 4929.90 | 23-JAN-13:00 |
Water Heater:WaterSystems:Gas | 87.54 | 1860.00 | 03-JAN-18:10 | 4929.90 | 23-JAN-13:00 |
Gas:HVAC | 10.26 | 0.00 | 01-JAN-00:10 | 86834.31 | 05-FEB-09:20 |
Heating:Gas | 10.26 | 0.00 | 01-JAN-00:10 | 86834.31 | 05-FEB-09:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2346.88 | 0.00 | 01-JAN-00:10 | 276675.36 | 07-OCT-13:00 |
EnergyTransfer:Building | 826.72 | 0.00 | 01-JAN-00:10 | 79767.50 | 07-JUL-14:50 |
EnergyTransfer:Zone:BACK_SPACE | 133.91 | 0.00 | 01-JAN-00:10 | 17207.62 | 06-FEB-05:10 |
Heating:EnergyTransfer | 6.72 | 0.00 | 01-JAN-00:10 | 33777.18 | 05-FEB-07:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 1.06 | 0.00 | 01-JAN-00:10 | 17207.62 | 06-FEB-05:10 |
Cooling:EnergyTransfer | 820.00 | 0.00 | 01-JAN-00:10 | 79767.50 | 07-JUL-14:50 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 132.85 | 0.00 | 01-JAN-00:10 | 13449.96 | 07-JUL-15:00 |
EnergyTransfer:Zone:CORE_RETAIL | 499.14 | 0.00 | 01-JAN-00:10 | 57187.26 | 10-SEP-08:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 4.13 | 0.00 | 01-JAN-00:10 | 8361.55 | 01-MAY-06:20 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 495.01 | 0.00 | 01-JAN-00:10 | 54729.26 | 08-MAR-07:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 113.94 | 0.00 | 01-JAN-00:10 | 10635.56 | 07-OCT-14:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.20 | 0.00 | 01-JAN-00:10 | 7375.30 | 05-FEB-07:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 113.75 | 0.00 | 01-JAN-00:10 | 10635.56 | 07-OCT-14:10 |
EnergyTransfer:Zone:FRONT_RETAIL | 78.78 | 0.00 | 01-JAN-00:10 | 9427.07 | 05-FEB-07:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.38 | 0.00 | 01-JAN-00:10 | 9427.07 | 05-FEB-07:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 78.39 | 0.00 | 01-JAN-00:10 | 8688.46 | 07-OCT-14:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 0.95 | 0.00 | 01-JAN-00:10 | 21439.09 | 20-DEC-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.95 | 0.00 | 01-JAN-00:10 | 21439.09 | 20-DEC-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1520.16 | 0.00 | 01-JAN-00:10 | 198769.70 | 07-OCT-13:00 |
HeatingCoils:EnergyTransfer | 8.21 | 0.00 | 01-JAN-00:10 | 69467.45 | 05-FEB-09:20 |
CoolingCoils:EnergyTransfer | 1511.95 | 0.00 | 01-JAN-00:10 | 198769.70 | 07-OCT-13:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 1.060 | -132.845 | 0.000 | 0.000 | 37.082 | 28.087 | 49.772 | 0.000 | 0.000 | 1.197 | 19.742 | 0.000 | 0.000 | 0.000 | -4.094 | -0.001 |
CORE_RETAIL | 0.000 | 0.000 | 4.127 | -495.005 | 0.000 | 0.000 | 156.077 | 217.471 | 83.927 | 42.111 | 0.000 | 0.731 | 6.477 | 0.000 | -12.040 | 0.000 | -3.877 | -0.001 |
POINT_OF_SALE | 0.000 | 0.000 | 0.197 | -113.745 | 0.000 | 0.000 | 14.611 | 24.176 | 52.689 | 32.036 | 0.000 | 0.516 | 1.576 | 0.000 | -10.167 | 0.000 | -1.889 | -0.000 |
FRONT_RETAIL | 0.000 | 0.000 | 0.385 | -78.390 | 0.000 | 0.000 | 14.700 | 23.423 | 7.908 | 32.040 | 0.000 | 0.518 | 11.064 | 0.000 | -9.835 | 0.000 | -1.814 | -0.000 |
FRONT_ENTRY | 0.951 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.081 | 0.000 | 6.194 | 0.000 | 1.794 | 0.505 | 0.000 | -2.008 | 0.000 | -7.517 | -0.000 |
Total Facility | 0.951 | 0.000 | 5.769 | -819.984 | 0.000 | 0.000 | 222.469 | 293.238 | 194.297 | 112.382 | 0.000 | 4.756 | 39.364 | 0.000 | -34.050 | 0.000 | -19.192 | -0.002 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 17-APR-20:47 | 0.00 | 0.00 | 0.00 | -36542.56 | 0.00 | 0.00 | 0.00 | 81.78 | 605.09 | 0.00 | 0.00 | 0.00 | 35855.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 27-OCT-06:02 | 0.00 | 0.00 | 0.00 | -204169.50 | 0.00 | 0.00 | 1607.85 | 344.55 | 2062.04 | 0.00 | 0.00 | 0.00 | 201448.57 | 0.00 | -1079.15 | 0.00 | -214.36 | 0.00 |
POINT_OF_SALE | 23-NOV-20:01 | 0.00 | 0.00 | 0.00 | -19630.91 | 0.00 | 0.00 | 0.00 | 32.47 | 480.42 | 0.00 | 0.00 | 0.00 | 20643.87 | 0.00 | -1418.91 | 0.00 | -106.94 | 0.00 |
FRONT_RETAIL | 17-APR-20:41 | 0.00 | 0.00 | 0.00 | -17239.07 | 0.00 | 0.00 | 0.00 | 32.47 | 96.14 | 0.00 | 0.00 | 0.00 | 17471.66 | 0.00 | -361.20 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-OCT-06:02 | 0.00 | 0.00 | 0.00 | -208954.93 | 0.00 | 0.00 | 2378.71 | 493.85 | 4773.73 | 0.00 | 0.00 | 0.00 | 205291.73 | 0.00 | -3292.00 | 0.00 | -691.08 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 22-JAN-08:61 | 0.00 | 0.00 | 50575.31 | 0.00 | 0.00 | 0.00 | 0.00 | 81.78 | 453.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -413.55 | -50697.35 |
CORE_RETAIL | 10-SEP-08:08 | 0.00 | 0.00 | 23619.25 | 0.00 | 0.00 | 0.00 | 1595.71 | 344.55 | 1546.53 | 1639.21 | 0.00 | 120.36 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28865.60 |
POINT_OF_SALE | 05-FEB-07:01 | 0.00 | 0.00 | 28996.37 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 480.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2214.07 | 0.00 | -1072.74 | -26222.45 |
FRONT_RETAIL | 05-FEB-07:01 | 0.00 | 0.00 | 23420.52 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 72.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2153.09 | 0.00 | -1030.05 | -20341.95 |
FRONT_ENTRY | 04-JAN-17:21 | 21531.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 | 5.86 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -11145.64 | -10394.27 |
Total Facility | 05-FEB-07:01 | 0.00 | 0.00 | 102933.80 | 0.00 | 0.00 | 0.00 | 0.00 | 493.85 | 1771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6946.64 | 0.00 | -6813.36 | -91439.24 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.9609 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.9703 | 0.1175 | 1.0000 | 0.2316 | 0.1175 | ||
PSZ-AC:2 | 7.0371 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.2512 | 0.2607 | 1.0000 | 1.8902 | 0.2607 | ||
PSZ-AC:3 | 1.1034 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1034 | 0.1614 | 1.0000 | 0.1781 | 0.1614 | ||
PSZ-AC:4 | 0.8543 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.8543 | 0.2085 | 1.0000 | 0.1781 | 0.2085 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.9609 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.9609 | 1.0000 | 1.0000 | 0.2316 | 0.1181 | ||
PSZ-AC:2 | 7.0371 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.0371 | 1.0000 | 1.0000 | 1.8902 | 0.2686 | ||
PSZ-AC:3 | 1.1034 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1034 | 1.0000 | 1.0000 | 0.1781 | 0.1614 | ||
PSZ-AC:4 | 0.8543 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.8543 | 1.0000 | 1.0000 | 0.1781 | 0.2085 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.9609 | 1.9609 | 1.9609 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.0371 | 7.0371 | 7.0371 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1034 | 1.1034 | 1.1034 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.8543 | 0.8543 | 0.8543 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.9609 | 1.9703 | 1.9609 | 1.9609 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.0371 | 7.2512 | 7.0371 | 7.0371 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1034 | 1.1034 | 1.1034 | 1.1034 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.8543 | 0.8543 | 0.8543 | 0.8543 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.9609 | 1.9609 | 1.9609 | 0.2316 | 0.2541 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.0371 | 7.0371 | 7.0371 | 1.8902 | 0.7749 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1034 | 1.1034 | 1.1034 | 0.1781 | 0.3900 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.8543 | 0.8543 | 0.8543 | 0.1781 | 0.3900 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.9609 | 1.9609 | 1.9609 | 1.9609 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.0371 | 7.0371 | 7.0371 | 7.0371 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1034 | 1.1034 | 1.1034 | 1.1034 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.8543 | 0.8543 | 0.8543 | 0.8543 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:11
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 10.26 | 86834.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 390.40 | 54708.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 293.24 | 24449.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 38.45 | 3371.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 194.30 | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 133.87 | 11173.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 87.54 | 4929.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 194.30 | 1050.24 |
Natural Gas | 0.00 | 97.80 |
Additional | 0.00 | 0.00 |
Total | 194.30 | 1148.04 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 127.83 |
Space Heating | 0.00 |
Space Cooling | 170.18 |
Fans (All) | 58.36 |
Service Water Heating | 0.00 |
Receptacle Equipment | 84.70 |
Miscellaneous (All) | 457.82 |
Subtotal | 457.82 |
Natural Gas [MJ/m2] | |
Space Heating | 4.47 |
Service Water Heating | 38.16 |
Miscellaneous (All) | 42.63 |
Subtotal | 42.63 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 25.54 |
Space Heating | 0.89 |
Space Cooling | 34.01 |
Fans (All) | 11.66 |
Service Water Heating | 7.62 |
Receptacle Equipment | 16.92 |
Miscellaneous | 3.35 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 2872. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3001. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3501. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4552. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_SETBACK | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_FRONTENTRY_STD2013 | FRONT_ENTRY DUALSPSCHED | January | 16.00 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.327883E+10 |
February | 0.000 | 0.292100E+10 |
March | 0.000 | 0.182706E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.223645E+10 |
Annual Sum or Average | 0.102633E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.327883E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.327883E+10 |
February | 0.000 | 0.292100E+10 |
March | 0.000 | 0.182706E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.223645E+10 |
Annual Sum or Average | 0.102633E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.327883E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.327883E+10 |
February | 0.000 | 0.292100E+10 |
March | 0.000 | 0.182706E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.223645E+10 |
Annual Sum or Average | 0.102633E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.327883E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.327883E+10 |
February | 0.000 | 0.292100E+10 |
March | 0.000 | 0.182706E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.223645E+10 |
Annual Sum or Average | 0.102633E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.327883E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.327883E+10 |
February | 0.000 | 0.292100E+10 |
March | 0.000 | 0.182706E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.223645E+10 |
Annual Sum or Average | 0.102633E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.327883E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.327883E+10 |
February | 0.000 | 0.292100E+10 |
March | 0.000 | 0.182706E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.223645E+10 |
Annual Sum or Average | 0.102633E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.327883E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.327883E+10 |
February | 0.000 | 0.292100E+10 |
March | 0.000 | 0.182706E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.223645E+10 |
Annual Sum or Average | 0.102633E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.327883E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.327883E+10 |
February | 0.000 | 0.292100E+10 |
March | 0.000 | 0.182706E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.223645E+10 |
Annual Sum or Average | 0.102633E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.327883E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.327883E+10 |
February | 0.000 | 0.292100E+10 |
March | 0.000 | 0.182706E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.223645E+10 |
Annual Sum or Average | 0.102633E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.327883E+10 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371868E+10 | 21944.41 | 01-JAN-20:12 | 19.00 | 17.29 | 0.203713E+10 | 2451.27 | 28-JAN-16:00 | 22.00 | 14.38 |
February | 0.407776E+10 | 21997.61 | 27-FEB-22:02 | 18.90 | 18.13 | 0.190921E+10 | 2451.29 | 09-FEB-15:09 | 22.02 | 14.61 |
March | 0.549572E+10 | 21644.93 | 27-MAR-23:12 | 19.00 | 18.78 | 0.221068E+10 | 2451.30 | 04-MAR-11:09 | 23.48 | 14.90 |
April | 0.880350E+10 | 36542.48 | 17-APR-20:47 | 21.37 | 14.47 | 0.215343E+10 | 2451.27 | 10-APR-14:09 | 20.42 | 10.76 |
May | 0.154018E+11 | 26406.13 | 07-MAY-18:13 | 30.57 | 23.65 | 0.223250E+10 | 2451.25 | 27-MAY-13:39 | 30.03 | 24.98 |
June | 0.168067E+11 | 26015.22 | 28-JUN-20:10 | 29.22 | 24.16 | 0.220161E+10 | 2451.24 | 20-JUN-14:50 | 32.38 | 25.45 |
July | 0.178262E+11 | 28951.83 | 07-JUL-22:43 | 28.30 | 24.40 | 0.218727E+10 | 2451.23 | 08-JUL-13:00 | 29.40 | 23.80 |
August | 0.182035E+11 | 29255.76 | 02-AUG-22:03 | 27.35 | 22.07 | 0.228103E+10 | 2451.27 | 28-AUG-14:09 | 33.00 | 25.44 |
September | 0.156996E+11 | 29073.89 | 10-SEP-22:03 | 27.97 | 24.30 | 0.215639E+10 | 2451.24 | 01-SEP-14:00 | 32.20 | 24.98 |
October | 0.141162E+11 | 32061.20 | 01-OCT-22:41 | 20.15 | 15.76 | 0.218307E+10 | 2451.33 | 28-OCT-14:09 | 21.00 | 14.40 |
November | 0.735020E+10 | 26296.08 | 04-NOV-23:22 | 19.20 | 17.80 | 0.209168E+10 | 2451.28 | 25-NOV-15:09 | 19.80 | 14.71 |
December | 0.534625E+10 | 26105.55 | 17-DEC-07:12 | 20.67 | 18.06 | 0.209198E+10 | 2451.29 | 02-DEC-16:00 | 20.00 | 16.82 |
Annual Sum or Average | 0.132846E+12 | 0.257360E+11 | ||||||||
Minimum of Months | 0.371868E+10 | 21644.93 | 18.90 | 14.47 | 0.190921E+10 | 2451.23 | 19.80 | 10.76 | ||
Maximum of Months | 0.182035E+11 | 36542.48 | 30.57 | 24.40 | 0.228103E+10 | 2451.33 | 33.00 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276540E+11 | 137958.47 | 02-JAN-07:03 | 15.83 | 15.23 | 0.864166E+10 | 10327.25 | 14-JAN-16:10 | 19.32 | 12.61 |
February | 0.268024E+11 | 140998.05 | 25-FEB-07:02 | 14.77 | 14.77 | 0.809550E+10 | 10327.25 | 25-FEB-11:09 | 18.08 | 17.53 |
March | 0.326582E+11 | 151931.54 | 08-MAR-07:03 | 10.50 | 8.44 | 0.933676E+10 | 10326.96 | 23-MAR-14:00 | 21.10 | 12.59 |
April | 0.396103E+11 | 147259.44 | 18-APR-06:03 | 16.78 | 15.04 | 0.907494E+10 | 10327.19 | 10-APR-14:09 | 20.42 | 10.76 |
May | 0.501581E+11 | 115935.78 | 12-MAY-06:02 | 23.40 | 20.68 | 0.940926E+10 | 10327.30 | 12-MAY-14:00 | 32.20 | 23.22 |
June | 0.520834E+11 | 116292.56 | 12-JUN-06:02 | 23.58 | 21.07 | 0.927900E+10 | 10327.07 | 01-JUN-14:09 | 29.60 | 22.93 |
July | 0.528618E+11 | 102700.87 | 18-JUL-06:02 | 24.27 | 22.84 | 0.921877E+10 | 10327.01 | 13-JUL-14:00 | 25.60 | 23.63 |
August | 0.534460E+11 | 109547.64 | 04-AUG-06:02 | 25.68 | 23.49 | 0.961371E+10 | 10327.09 | 05-AUG-13:00 | 27.70 | 25.21 |
September | 0.475832E+11 | 114829.63 | 23-SEP-06:02 | 22.28 | 20.35 | 0.908842E+10 | 10327.05 | 30-SEP-15:00 | 23.80 | 22.68 |
October | 0.467235E+11 | 204204.65 | 27-OCT-06:02 | 14.83 | 7.55 | 0.919732E+10 | 10327.40 | 28-OCT-11:00 | 19.00 | 12.85 |
November | 0.342509E+11 | 138690.52 | 30-NOV-07:03 | 15.50 | 14.44 | 0.880743E+10 | 10327.13 | 09-NOV-15:00 | 21.10 | 12.44 |
December | 0.311801E+11 | 143347.68 | 17-DEC-09:02 | 19.00 | 14.28 | 0.881108E+10 | 10327.37 | 05-DEC-15:50 | 18.33 | 12.42 |
Annual Sum or Average | 0.495012E+12 | 0.108574E+12 | ||||||||
Minimum of Months | 0.268024E+11 | 102700.87 | 10.50 | 7.55 | 0.809550E+10 | 10326.96 | 18.08 | 10.76 | ||
Maximum of Months | 0.534460E+11 | 204204.65 | 25.68 | 23.49 | 0.961371E+10 | 10327.40 | 32.20 | 25.21 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.670570E+10 | 18185.80 | 01-JAN-08:61 | 16.50 | 14.99 | 0.854071E+09 | 973.22 | 07-JAN-12:00 | 19.00 | 13.75 |
February | 0.633684E+10 | 17762.74 | 01-FEB-23:01 | 17.75 | 17.13 | 0.780462E+09 | 973.15 | 09-FEB-15:09 | 22.02 | 14.61 |
March | 0.634648E+10 | 16149.86 | 25-MAR-23:31 | 19.70 | 16.46 | 0.888584E+09 | 973.14 | 04-MAR-11:09 | 23.48 | 14.90 |
April | 0.739512E+10 | 15454.28 | 30-APR-22:51 | 21.30 | 17.74 | 0.855104E+09 | 973.13 | 10-APR-14:09 | 20.42 | 10.76 |
May | 0.105455E+11 | 14192.81 | 07-MAY-18:43 | 27.22 | 24.15 | 0.886264E+09 | 973.16 | 01-MAY-14:50 | 32.02 | 25.22 |
June | 0.108820E+11 | 14685.03 | 28-JUN-20:10 | 29.22 | 24.16 | 0.873998E+09 | 973.14 | 03-JUN-14:50 | 31.10 | 24.12 |
July | 0.114792E+11 | 16956.89 | 07-JUL-21:23 | 28.85 | 25.01 | 0.868299E+09 | 973.11 | 01-JUL-15:50 | 25.68 | 24.34 |
August | 0.123521E+11 | 18244.01 | 30-AUG-21:23 | 28.90 | 22.60 | 0.905509E+09 | 973.11 | 07-AUG-14:00 | 25.00 | 24.24 |
September | 0.116640E+11 | 18068.18 | 10-SEP-21:23 | 28.10 | 24.32 | 0.856038E+09 | 973.15 | 29-SEP-14:09 | 28.75 | 24.28 |
October | 0.125483E+11 | 18931.92 | 26-OCT-20:41 | 19.17 | 12.01 | 0.866727E+09 | 973.20 | 02-OCT-14:50 | 28.83 | 21.64 |
November | 0.946796E+10 | 19631.86 | 23-NOV-20:01 | 11.12 | 7.92 | 0.833489E+09 | 973.21 | 21-NOV-15:50 | 21.28 | 15.12 |
December | 0.802274E+10 | 15527.74 | 03-DEC-08:61 | 13.00 | 13.00 | 0.858275E+09 | 973.17 | 04-DEC-15:00 | 19.00 | 13.76 |
Annual Sum or Average | 0.113746E+12 | 0.103268E+11 | ||||||||
Minimum of Months | 0.633684E+10 | 14192.81 | 11.12 | 7.92 | 0.780462E+09 | 973.11 | 19.00 | 10.76 | ||
Maximum of Months | 0.125483E+11 | 19631.86 | 29.22 | 25.01 | 0.905509E+09 | 973.22 | 32.02 | 25.22 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.425518E+10 | 13870.85 | 29-JAN-19:19 | 19.00 | 15.29 | 0.832002E+09 | 973.16 | 07-JAN-12:00 | 19.00 | 13.75 |
February | 0.396064E+10 | 12117.03 | 01-FEB-23:04 | 17.75 | 17.13 | 0.764312E+09 | 973.16 | 09-FEB-15:09 | 22.02 | 14.61 |
March | 0.374569E+10 | 16546.30 | 24-MAR-21:21 | 19.10 | 14.88 | 0.866226E+09 | 973.10 | 25-MAR-15:00 | 23.80 | 18.73 |
April | 0.447634E+10 | 17239.44 | 17-APR-20:41 | 21.37 | 14.47 | 0.851926E+09 | 973.12 | 10-APR-14:09 | 20.42 | 10.76 |
May | 0.726236E+10 | 12269.81 | 07-MAY-18:43 | 27.22 | 24.15 | 0.886256E+09 | 973.13 | 01-MAY-14:50 | 32.02 | 25.22 |
June | 0.765595E+10 | 11795.20 | 28-JUN-20:10 | 29.22 | 24.16 | 0.873995E+09 | 973.12 | 03-JUN-14:50 | 31.10 | 24.12 |
July | 0.831957E+10 | 13633.07 | 07-JUL-22:03 | 28.30 | 24.91 | 0.868299E+09 | 973.09 | 01-JUL-15:39 | 25.77 | 24.38 |
August | 0.905291E+10 | 14692.63 | 30-AUG-22:03 | 28.42 | 22.68 | 0.905508E+09 | 973.10 | 12-AUG-14:00 | 25.00 | 22.92 |
September | 0.847865E+10 | 14960.32 | 10-SEP-22:43 | 27.83 | 24.27 | 0.856031E+09 | 973.12 | 29-SEP-14:09 | 28.75 | 24.28 |
October | 0.929549E+10 | 16269.06 | 26-OCT-21:29 | 19.00 | 11.81 | 0.865997E+09 | 973.15 | 28-OCT-14:09 | 21.00 | 14.40 |
November | 0.652436E+10 | 15459.35 | 24-NOV-21:19 | 18.50 | 14.80 | 0.831247E+09 | 973.16 | 14-NOV-15:50 | 18.38 | 13.09 |
December | 0.536429E+10 | 15888.86 | 17-DEC-20:01 | 10.00 | 6.98 | 0.835816E+09 | 973.15 | 05-DEC-15:50 | 18.33 | 12.42 |
Annual Sum or Average | 0.783914E+11 | 0.102376E+11 | ||||||||
Minimum of Months | 0.374569E+10 | 11795.20 | 10.00 | 6.98 | 0.764312E+09 | 973.09 | 18.33 | 10.76 | ||
Maximum of Months | 0.929549E+10 | 17239.44 | 29.22 | 24.91 | 0.905508E+09 | 973.16 | 32.02 | 25.22 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 | 16.69 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 18.20 | 18.20 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 17.62 | 17.16 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.00 | 0.00 | 01-APR-00:05 | 20.72 | 19.79 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 22.93 | 21.40 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 | 23.10 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 | 23.54 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 | 24.22 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 22.17 | 20.64 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 21.63 | 21.01 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14.12 | 12.36 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 14.12 | 12.36 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 24.22 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294556E+09 | 50575.22 | 22-JAN-08:61 | 9.17 |
February | 0.286240E+09 | 50516.92 | 05-FEB-07:01 | -3.4 |
March | 0.177875E+09 | 50475.54 | 12-MAR-06:01 | 7.10 |
April | 35129640.63 | 1113.56 | 21-APR-05:10 | 18.30 |
May | 7770179.57 | 1507.87 | 19-MAY-05:05 | 25.00 |
June | 3573595.62 | 1545.94 | 28-JUN-05:05 | 26.70 |
July | 3484718.36 | 1462.91 | 31-JUL-05:05 | 24.40 |
August | 1975045.66 | 1572.16 | 07-AUG-05:05 | 24.17 |
September | 4899145.12 | 1539.82 | 02-SEP-05:05 | 24.23 |
October | 11901774.97 | 1594.22 | 25-OCT-05:05 | 26.50 |
November | 50338636.95 | 1881.62 | 08-NOV-06:05 | 19.40 |
December | 0.182677E+09 | 49812.73 | 21-DEC-05:02 | 0.17 |
Annual Sum or Average | 0.106042E+10 | |||
Minimum of Months | 1975045.66 | 1113.56 | -3.4 | |
Maximum of Months | 0.294556E+09 | 50575.22 | 26.70 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.519005E+09 | 11613.26 | 10-JAN-07:10 | 3.17 |
February | 0.467558E+09 | 16590.53 | 05-FEB-09:10 | -0.3 |
March | 0.508414E+09 | 8795.95 | 13-MAR-06:10 | 5.92 |
April | 0.425785E+09 | 4905.80 | 28-APR-06:06 | 23.22 |
May | 0.214405E+09 | 14122.09 | 28-MAY-08:20 | 27.77 |
June | 0.180839E+09 | 14032.82 | 04-JUN-08:08 | 27.80 |
July | 0.221556E+09 | 15835.13 | 04-JUL-08:08 | 28.48 |
August | 0.176755E+09 | 15466.14 | 06-AUG-08:08 | 28.17 |
September | 0.187672E+09 | 23617.89 | 10-SEP-08:08 | 32.40 |
October | 0.259689E+09 | 11821.16 | 07-OCT-06:08 | 26.67 |
November | 0.458641E+09 | 7737.74 | 11-NOV-09:06 | 24.40 |
December | 0.506730E+09 | 14604.44 | 21-DEC-07:10 | 0.50 |
Annual Sum or Average | 0.412705E+10 | |||
Minimum of Months | 0.176755E+09 | 4905.80 | -0.3 | |
Maximum of Months | 0.519005E+09 | 23617.89 | 32.40 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35410400.36 | 1366.11 | 05-JAN-07:08 | 0.83 |
February | 53380519.70 | 28996.37 | 05-FEB-07:01 | -3.4 |
March | 51485812.38 | 28965.28 | 12-MAR-06:01 | 7.10 |
April | 12389403.34 | 827.71 | 27-APR-05:05 | 20.92 |
May | 502135.06 | 839.74 | 27-MAY-05:05 | 25.00 |
June | 580274.62 | 861.55 | 19-JUN-05:05 | 25.00 |
July | 822206.19 | 840.08 | 12-JUL-05:05 | 23.90 |
August | 329135.80 | 550.07 | 06-AUG-07:10 | 26.33 |
September | 910893.20 | 853.12 | 28-SEP-05:05 | 22.28 |
October | 1977151.12 | 768.93 | 01-OCT-07:02 | 19.17 |
November | 8617511.24 | 855.86 | 29-NOV-06:05 | 21.60 |
December | 30534625.40 | 10937.31 | 21-DEC-05:08 | 0.17 |
Annual Sum or Average | 0.196940E+09 | |||
Minimum of Months | 329135.80 | 550.07 | -3.4 | |
Maximum of Months | 53380519.70 | 28996.37 | 26.33 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61006738.10 | 23062.91 | 10-JAN-05:02 | 1.33 |
February | 93090449.83 | 23420.52 | 05-FEB-07:01 | -3.4 |
March | 0.117677E+09 | 23401.40 | 12-MAR-06:01 | 7.10 |
April | 18230613.72 | 476.37 | 24-APR-05:10 | 20.08 |
May | 1398167.56 | 657.36 | 22-MAY-05:05 | 26.10 |
June | 771852.93 | 471.02 | 02-JUN-05:10 | 24.50 |
July | 690924.13 | 646.43 | 13-JUL-05:05 | 26.93 |
August | 317614.73 | 615.13 | 09-AUG-05:05 | 22.60 |
September | 981285.96 | 488.59 | 16-SEP-05:10 | 23.80 |
October | 2942026.47 | 496.99 | 01-OCT-07:02 | 19.17 |
November | 14751172.89 | 493.34 | 05-NOV-07:02 | 16.78 |
December | 72816315.08 | 23064.47 | 21-DEC-05:02 | 0.17 |
Annual Sum or Average | 0.384674E+09 | |||
Minimum of Months | 317614.73 | 471.02 | -3.4 | |
Maximum of Months | 0.117677E+09 | 23420.52 | 26.93 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183606E+09 | 21531.38 | 04-JAN-17:21 | 7.00 |
February | 0.400236E+09 | 21505.75 | 04-FEB-14:51 | 7.20 |
March | 0.112070E+09 | 17238.15 | 11-MAR-12:10 | 6.28 |
April | 0.00 | 0.00 | 01-APR-00:05 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 21.63 |
December | 0.254652E+09 | 21507.88 | 30-DEC-17:51 | 7.00 |
Annual Sum or Average | 0.950563E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.28 | |
Maximum of Months | 0.400236E+09 | 21531.38 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.235462E+10 | 2023.29 | 02-JAN-09:09 | 0.419292E+10 | 2751.42 | 02-JAN-09:09 |
February | 0.214299E+10 | 2023.29 | 01-FEB-09:09 | 0.380401E+10 | 2751.42 | 01-FEB-09:09 |
March | 0.244478E+10 | 2023.29 | 01-MAR-09:09 | 0.429860E+10 | 2751.42 | 01-MAR-09:09 |
April | 0.230724E+10 | 2023.29 | 01-APR-09:09 | 0.408483E+10 | 2751.42 | 01-APR-09:09 |
May | 0.239970E+10 | 2023.29 | 01-MAY-08:09 | 0.424576E+10 | 2751.42 | 01-MAY-08:09 |
June | 0.235921E+10 | 2023.29 | 01-JUN-08:09 | 0.415135E+10 | 2751.42 | 01-JUN-08:09 |
July | 0.234773E+10 | 2023.29 | 01-JUL-09:09 | 0.417924E+10 | 2751.42 | 01-JUL-09:09 |
August | 0.244478E+10 | 2023.29 | 01-AUG-08:09 | 0.429860E+10 | 2751.42 | 01-AUG-08:09 |
September | 0.230724E+10 | 2023.29 | 01-SEP-08:09 | 0.408483E+10 | 2751.42 | 01-SEP-08:09 |
October | 0.235462E+10 | 2023.29 | 02-OCT-08:09 | 0.419292E+10 | 2751.42 | 02-OCT-08:09 |
November | 0.227595E+10 | 2023.29 | 01-NOV-08:09 | 0.405935E+10 | 2751.42 | 01-NOV-08:09 |
December | 0.234773E+10 | 2023.29 | 01-DEC-09:09 | 0.417924E+10 | 2751.42 | 01-DEC-09:09 |
Annual Sum or Average | 0.280866E+11 | 0.497716E+11 | ||||
Minimum of Months | 0.214299E+10 | 2023.29 | 0.380401E+10 | 2751.42 | ||
Maximum of Months | 0.244478E+10 | 2023.29 | 0.429860E+10 | 2751.42 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.201420E+11 | 18915.75 | 02-JAN-15:20 | 0.707031E+10 | 4639.58 | 02-JAN-09:09 |
February | 0.176105E+11 | 18915.75 | 01-FEB-09:09 | 0.641452E+10 | 4639.58 | 01-FEB-09:09 |
March | 0.191372E+11 | 18915.75 | 01-MAR-09:09 | 0.724851E+10 | 4639.58 | 01-MAR-09:09 |
April | 0.174944E+11 | 18915.75 | 01-APR-16:00 | 0.688804E+10 | 4639.58 | 01-APR-09:09 |
May | 0.178719E+11 | 18915.75 | 01-MAY-16:30 | 0.715941E+10 | 4639.58 | 01-MAY-08:09 |
June | 0.172519E+11 | 18915.75 | 08-JUN-08:09 | 0.700021E+10 | 4639.58 | 01-JUN-08:09 |
July | 0.167290E+11 | 18915.75 | 25-JUL-08:20 | 0.704724E+10 | 4639.58 | 01-JUL-09:09 |
August | 0.173024E+11 | 18915.75 | 02-AUG-08:09 | 0.724851E+10 | 4639.58 | 01-AUG-08:09 |
September | 0.164381E+11 | 18915.75 | 05-SEP-08:09 | 0.688804E+10 | 4639.58 | 01-SEP-08:09 |
October | 0.182071E+11 | 18915.75 | 02-OCT-08:09 | 0.707031E+10 | 4639.58 | 02-OCT-08:09 |
November | 0.191200E+11 | 18915.75 | 01-NOV-08:09 | 0.684509E+10 | 4639.58 | 01-NOV-08:09 |
December | 0.201659E+11 | 18915.75 | 01-DEC-09:09 | 0.704724E+10 | 4639.58 | 01-DEC-09:09 |
Annual Sum or Average | 0.217471E+12 | 0.839274E+11 | ||||
Minimum of Months | 0.164381E+11 | 18915.75 | 0.641452E+10 | 4639.58 | ||
Maximum of Months | 0.201659E+11 | 18915.75 | 0.724851E+10 | 4639.58 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.202570E+10 | 1782.39 | 02-JAN-09:09 | 0.443872E+10 | 2912.71 | 02-JAN-09:09 |
February | 0.184426E+10 | 1782.39 | 01-FEB-09:09 | 0.402701E+10 | 2912.71 | 01-FEB-09:09 |
March | 0.210616E+10 | 1782.39 | 01-MAR-09:09 | 0.455059E+10 | 2912.71 | 01-MAR-09:09 |
April | 0.198616E+10 | 1782.39 | 01-APR-09:09 | 0.432429E+10 | 2912.71 | 01-APR-09:09 |
May | 0.206593E+10 | 1782.39 | 01-MAY-08:09 | 0.449465E+10 | 2912.71 | 01-MAY-08:09 |
June | 0.203227E+10 | 1782.39 | 01-JUN-08:09 | 0.439471E+10 | 2912.71 | 01-JUN-08:09 |
July | 0.201982E+10 | 1782.39 | 01-JUL-09:09 | 0.442423E+10 | 2912.71 | 01-JUL-09:09 |
August | 0.210616E+10 | 1782.39 | 01-AUG-08:09 | 0.455059E+10 | 2912.71 | 01-AUG-08:09 |
September | 0.198616E+10 | 1782.39 | 01-SEP-08:09 | 0.432429E+10 | 2912.71 | 01-SEP-08:09 |
October | 0.202570E+10 | 1782.39 | 02-OCT-08:09 | 0.443872E+10 | 2912.71 | 02-OCT-08:09 |
November | 0.195769E+10 | 1782.39 | 01-NOV-08:09 | 0.429732E+10 | 2912.71 | 01-NOV-08:09 |
December | 0.201982E+10 | 1782.39 | 01-DEC-09:09 | 0.442423E+10 | 2912.71 | 01-DEC-09:09 |
Annual Sum or Average | 0.241758E+11 | 0.526893E+11 | ||||
Minimum of Months | 0.184426E+10 | 1782.39 | 0.402701E+10 | 2912.71 | ||
Maximum of Months | 0.210616E+10 | 1782.39 | 0.455059E+10 | 2912.71 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.196268E+10 | 1725.71 | 02-JAN-09:09 | 0.666220E+09 | 437.18 | 02-JAN-09:09 |
February | 0.178687E+10 | 1725.71 | 01-FEB-09:09 | 0.604426E+09 | 437.18 | 01-FEB-09:09 |
March | 0.204057E+10 | 1725.71 | 01-MAR-09:09 | 0.683011E+09 | 437.18 | 01-MAR-09:09 |
April | 0.192434E+10 | 1725.71 | 01-APR-09:09 | 0.649045E+09 | 437.18 | 01-APR-09:09 |
May | 0.200162E+10 | 1725.71 | 01-MAY-08:09 | 0.674616E+09 | 437.18 | 01-MAY-08:09 |
June | 0.196898E+10 | 1725.71 | 01-JUN-08:09 | 0.659615E+09 | 437.18 | 01-JUN-08:09 |
July | 0.195698E+10 | 1725.71 | 01-JUL-09:09 | 0.664046E+09 | 437.18 | 01-JUL-09:09 |
August | 0.204057E+10 | 1725.71 | 01-AUG-08:09 | 0.683011E+09 | 437.18 | 01-AUG-08:09 |
September | 0.192434E+10 | 1725.71 | 01-SEP-08:09 | 0.649045E+09 | 437.18 | 01-SEP-08:09 |
October | 0.196268E+10 | 1725.71 | 02-OCT-08:09 | 0.666220E+09 | 437.18 | 02-OCT-08:09 |
November | 0.189680E+10 | 1725.71 | 01-NOV-08:09 | 0.644998E+09 | 437.18 | 01-NOV-08:09 |
December | 0.195698E+10 | 1725.71 | 01-DEC-09:09 | 0.664046E+09 | 437.18 | 01-DEC-09:09 |
Annual Sum or Average | 0.234234E+11 | 0.790830E+10 | ||||
Minimum of Months | 0.178687E+10 | 1725.71 | 0.604426E+09 | 437.18 | ||
Maximum of Months | 0.204057E+10 | 1725.71 | 0.683011E+09 | 437.18 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 6919213.84 | 2.58 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 6249612.50 | 2.58 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 6919213.84 | 2.58 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 6696013.39 | 2.58 | 01-APR-00:10 | 0.00 | 0.00 |
May | 6919213.84 | 2.58 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 6696013.39 | 2.58 | 01-JUN-00:10 | 0.00 | 0.00 |
July | 6919213.84 | 2.58 | 01-JUL-00:10 | 0.00 | 0.00 |
August | 6919213.84 | 2.58 | 01-AUG-00:10 | 0.00 | 0.00 |
September | 6696013.39 | 2.58 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 6919213.84 | 2.58 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 6696013.39 | 2.58 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 6919213.84 | 2.58 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 81468162.94 | ||||
Minimum of Months | 6249612.50 | 2.58 | 0.00 | 0.00 | |
Maximum of Months | 6919213.84 | 2.58 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.235462E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2592093.71 | 0.896225E+09 |
February | 0.479114E+10 | 0.214299E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5232434.26 | 0.647338E+09 |
March | 0.548013E+10 | 0.244478E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14643981.68 | 0.732876E+09 |
April | 0.518069E+10 | 0.230724E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34360548.21 | 0.270227E+09 |
May | 0.536353E+10 | 0.239970E+10 | 0.424576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178150E+09 | 7016224.16 |
June | 0.528933E+10 | 0.235921E+10 | 0.415135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163251E+09 | 12290303.99 |
July | 0.525489E+10 | 0.234773E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227872E+09 | 763841.02 |
August | 0.548013E+10 | 0.244478E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228496E+09 | 14694014.56 |
September | 0.518069E+10 | 0.230724E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176940E+09 | 26168673.61 |
October | 0.524694E+10 | 0.235462E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142164E+09 | 0.227710E+09 |
November | 0.504819E+10 | 0.227595E+10 | 0.405935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14781290.43 | 0.467613E+09 |
December | 0.525489E+10 | 0.234773E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8561862.94 | 0.791379E+09 |
Annual Sum or Average | 0.628175E+11 | 0.280866E+11 | 0.497716E+11 | 0.119705E+10 | 0.409430E+10 | ||||
Minimum of Months | 0.479114E+10 | 0.214299E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2592093.71 | 763841.02 |
Maximum of Months | 0.548013E+10 | 0.244478E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228496E+09 | 0.896225E+09 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.201420E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2121924.15 | 0.792023E+09 |
February | 0.201852E+11 | 0.176105E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4283317.68 | 0.578077E+09 |
March | 0.230879E+11 | 0.191372E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11987200.16 | 0.656160E+09 |
April | 0.218263E+11 | 0.174944E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26362652.20 | 0.256029E+09 |
May | 0.225967E+11 | 0.178719E+11 | 0.715941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106529E+09 | 41006334.81 |
June | 0.222841E+11 | 0.172519E+11 | 0.700021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101486E+09 | 36804039.07 |
July | 0.221389E+11 | 0.167290E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128603E+09 | 12958832.97 |
August | 0.230879E+11 | 0.173024E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134578E+09 | 49928630.59 |
September | 0.218263E+11 | 0.164381E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107560E+09 | 73702341.66 |
October | 0.221054E+11 | 0.182071E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89343199.02 | 0.254640E+09 |
November | 0.212681E+11 | 0.191200E+11 | 0.684509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11323388.45 | 0.419116E+09 |
December | 0.221389E+11 | 0.201659E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7002549.57 | 0.706501E+09 |
Annual Sum or Average | 0.264651E+12 | 0.217471E+12 | 0.839274E+11 | 0.731180E+09 | 0.387695E+10 | ||||
Minimum of Months | 0.201852E+11 | 0.164381E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2121924.15 | 12958832.97 |
Maximum of Months | 0.230879E+11 | 0.201659E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134578E+09 | 0.792023E+09 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.202570E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1123247.41 | 0.429759E+09 |
February | 0.190200E+10 | 0.184426E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2267503.48 | 0.303777E+09 |
March | 0.217552E+10 | 0.210616E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6345620.77 | 0.328095E+09 |
April | 0.205665E+10 | 0.198616E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14910558.32 | 0.118468E+09 |
May | 0.212923E+10 | 0.206593E+10 | 0.449465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77374330.54 | 2856480.28 |
June | 0.209978E+10 | 0.203227E+10 | 0.439471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70599446.31 | 5188339.81 |
July | 0.208610E+10 | 0.201982E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98375513.40 | 295973.61 |
August | 0.217552E+10 | 0.210616E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98211895.16 | 6352840.22 |
September | 0.205665E+10 | 0.198616E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76122367.49 | 11201797.67 |
October | 0.208295E+10 | 0.202570E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60835975.73 | 99906599.77 |
November | 0.200405E+10 | 0.195769E+10 | 0.429732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6403210.45 | 0.210859E+09 |
December | 0.208610E+10 | 0.201982E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3707315.21 | 0.372649E+09 |
Annual Sum or Average | 0.249375E+11 | 0.241758E+11 | 0.526893E+11 | 0.516277E+09 | 0.188941E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.184426E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1123247.41 | 295973.61 |
Maximum of Months | 0.217552E+10 | 0.210616E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98375513.40 | 0.429759E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.196268E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1123614.17 | 0.409903E+09 |
February | 0.190200E+10 | 0.178687E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2267544.60 | 0.288378E+09 |
March | 0.217552E+10 | 0.204057E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6346005.78 | 0.311713E+09 |
April | 0.205665E+10 | 0.192434E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14930371.46 | 0.114552E+09 |
May | 0.212923E+10 | 0.200162E+10 | 0.674616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77256618.59 | 3024928.79 |
June | 0.209978E+10 | 0.196898E+10 | 0.659615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70730125.65 | 5344679.47 |
July | 0.208610E+10 | 0.195698E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98657321.75 | 312412.51 |
August | 0.217552E+10 | 0.204057E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98753587.53 | 6325027.80 |
September | 0.205665E+10 | 0.192434E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76417583.61 | 11127716.15 |
October | 0.208295E+10 | 0.196268E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61093513.29 | 99088358.60 |
November | 0.200405E+10 | 0.189680E+10 | 0.644998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6415207.56 | 0.208352E+09 |
December | 0.208610E+10 | 0.195698E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3707519.01 | 0.355471E+09 |
Annual Sum or Average | 0.249375E+11 | 0.234234E+11 | 0.790830E+10 | 0.517699E+09 | 0.181359E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.178687E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1123614.17 | 312412.51 |
Maximum of Months | 0.217552E+10 | 0.204057E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98753587.53 | 0.409903E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98897.84 | 0.167853E+10 |
February | 0.00 | 6249612.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88465.50 | 0.144644E+10 |
March | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8822079.52 | 0.908977E+09 |
April | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71018507.78 | 0.341518E+09 |
May | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370966E+09 | 41316601.94 |
June | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411202E+09 | 21362397.58 |
July | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390448E+09 | 47239876.69 |
August | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334888E+09 | 61607151.79 |
September | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154643E+09 | 0.132363E+09 |
October | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45843070.89 | 0.328397E+09 |
November | 0.00 | 6696013.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4687054.60 | 0.948231E+09 |
December | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1340865.61 | 0.156137E+10 |
Annual Sum or Average | 0.00 | 81468162.94 | 0.179405E+10 | 0.751735E+10 | |||||
Minimum of Months | 0.00 | 6249612.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88465.50 | 21362397.58 |
Maximum of Months | 0.00 | 6919213.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411202E+09 | 0.167853E+10 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2023.29 | 02-JAN-09:09 | 2751.42 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.80 | 19-JAN-12:03 | 1883.51 | 21-JAN-06:00 |
February | 5888.82 | 01-FEB-15:09 | 2023.29 | 01-FEB-09:09 | 2751.42 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 144.86 | 02-FEB-13:00 | 2846.75 | 05-FEB-08:00 |
March | 5888.82 | 01-MAR-15:09 | 2023.29 | 01-MAR-09:09 | 2751.42 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 144.37 | 28-MAR-14:00 | 2244.88 | 20-MAR-22:00 |
April | 5888.82 | 01-APR-10:09 | 2023.29 | 01-APR-09:09 | 2751.42 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 233.42 | 29-APR-16:00 | 1283.77 | 01-APR-21:10 |
May | 5888.82 | 01-MAY-14:09 | 2023.29 | 01-MAY-08:09 | 2751.42 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 491.87 | 07-MAY-18:03 | 119.43 | 13-MAY-04:55 |
June | 5888.82 | 01-JUN-14:09 | 2023.29 | 01-JUN-08:09 | 2751.42 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 505.73 | 09-JUN-20:10 | 305.10 | 06-JUN-20:55 |
July | 5888.82 | 01-JUL-10:09 | 2023.29 | 01-JUL-09:09 | 2751.42 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 545.64 | 02-JUL-21:10 | 83.32 | 11-JUL-20:10 |
August | 5888.82 | 01-AUG-14:09 | 2023.29 | 01-AUG-08:09 | 2751.42 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 804.61 | 22-AUG-20:10 | 404.19 | 25-AUG-24:00 |
September | 5888.82 | 01-SEP-14:09 | 2023.29 | 01-SEP-08:09 | 2751.42 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1063.04 | 09-SEP-22:53 | 279.59 | 05-SEP-03:25 |
October | 5888.82 | 02-OCT-14:09 | 2023.29 | 02-OCT-08:09 | 2751.42 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 479.57 | 08-OCT-18:20 | 1118.92 | 29-OCT-02:00 |
November | 5888.82 | 01-NOV-14:09 | 2023.29 | 01-NOV-08:09 | 2751.42 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 118.14 | 07-NOV-22:10 | 1585.10 | 12-NOV-07:00 |
December | 5888.82 | 01-DEC-15:09 | 2023.29 | 01-DEC-09:09 | 2751.42 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.02 | 13-DEC-14:00 | 2292.06 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 54.80 | 83.32 | |||||
Maximum of Months | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1063.04 | 2846.75 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 18915.75 | 02-JAN-15:20 | 4639.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.85 | 19-JAN-12:03 | 1654.22 | 21-JAN-06:00 |
February | 24809.68 | 01-FEB-15:09 | 18915.75 | 01-FEB-09:09 | 4639.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 118.58 | 02-FEB-13:00 | 2322.54 | 05-FEB-08:00 |
March | 24809.68 | 01-MAR-15:09 | 18915.75 | 01-MAR-09:09 | 4639.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 118.17 | 28-MAR-14:00 | 2029.25 | 20-MAR-22:00 |
April | 24809.68 | 01-APR-10:09 | 18915.75 | 01-APR-16:00 | 4639.58 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.06 | 29-APR-16:00 | 1073.37 | 02-APR-06:00 |
May | 24809.68 | 01-MAY-14:09 | 18915.75 | 01-MAY-16:30 | 4639.58 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 403.90 | 07-MAY-18:03 | 188.46 | 09-MAY-01:55 |
June | 24809.68 | 01-JUN-14:09 | 18915.75 | 08-JUN-08:09 | 4639.58 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 398.50 | 09-JUN-20:03 | 352.32 | 06-JUN-21:20 |
July | 24809.68 | 01-JUL-10:09 | 18915.75 | 25-JUL-08:20 | 4639.58 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 421.02 | 04-JUL-18:03 | 139.61 | 31-JUL-02:55 |
August | 24809.68 | 01-AUG-14:09 | 18915.75 | 02-AUG-08:09 | 4639.58 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 642.25 | 22-AUG-20:03 | 494.74 | 25-AUG-23:55 |
September | 24809.68 | 01-SEP-14:09 | 18915.75 | 05-SEP-08:09 | 4639.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 715.73 | 09-SEP-22:53 | 387.65 | 05-SEP-02:55 |
October | 24809.68 | 02-OCT-14:09 | 18915.75 | 02-OCT-08:09 | 4639.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 388.67 | 08-OCT-18:03 | 1003.92 | 29-OCT-02:00 |
November | 24809.68 | 01-NOV-14:09 | 18915.75 | 01-NOV-08:09 | 4639.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 92.00 | 07-NOV-13:00 | 1378.27 | 12-NOV-07:00 |
December | 24809.68 | 01-DEC-15:09 | 18915.75 | 01-DEC-09:09 | 4639.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.97 | 13-DEC-14:00 | 2136.15 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 18915.75 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 44.85 | 139.61 | |||||
Maximum of Months | 24809.68 | 18915.75 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 715.73 | 2322.54 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1782.39 | 02-JAN-09:09 | 2912.71 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.74 | 19-JAN-12:03 | 864.03 | 26-JAN-03:00 |
February | 2337.76 | 01-FEB-15:09 | 1782.39 | 01-FEB-09:09 | 2912.71 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.78 | 02-FEB-13:00 | 1233.58 | 05-FEB-08:00 |
March | 2337.76 | 01-MAR-15:09 | 1782.39 | 01-MAR-09:09 | 2912.71 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.55 | 28-MAR-14:00 | 995.02 | 20-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 1782.39 | 01-APR-09:09 | 2912.71 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 101.15 | 29-APR-16:00 | 563.95 | 01-APR-21:10 |
May | 2337.76 | 01-MAY-14:09 | 1782.39 | 01-MAY-08:09 | 2912.71 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 216.86 | 07-MAY-18:10 | 43.54 | 13-MAY-04:40 |
June | 2337.76 | 01-JUN-14:09 | 1782.39 | 01-JUN-08:09 | 2912.71 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 217.37 | 09-JUN-20:10 | 131.91 | 06-JUN-20:40 |
July | 2337.76 | 01-JUL-10:09 | 1782.39 | 01-JUL-09:09 | 2912.71 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 236.44 | 02-JUL-21:10 | 40.89 | 11-JUL-20:10 |
August | 2337.76 | 01-AUG-14:09 | 1782.39 | 01-AUG-08:09 | 2912.71 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 345.97 | 22-AUG-20:10 | 205.26 | 25-AUG-24:00 |
September | 2337.76 | 01-SEP-14:09 | 1782.39 | 01-SEP-08:09 | 2912.71 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 455.28 | 09-SEP-22:53 | 123.21 | 12-SEP-24:00 |
October | 2337.76 | 02-OCT-14:09 | 1782.39 | 02-OCT-08:09 | 2912.71 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 215.45 | 08-OCT-18:10 | 528.86 | 29-OCT-02:00 |
November | 2337.76 | 01-NOV-14:09 | 1782.39 | 01-NOV-08:09 | 2912.71 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.90 | 07-NOV-21:47 | 720.72 | 12-NOV-08:00 |
December | 2337.76 | 01-DEC-15:09 | 1782.39 | 01-DEC-09:09 | 2912.71 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 | 13-DEC-14:00 | 1054.67 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1782.39 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 23.74 | 40.89 | |||||
Maximum of Months | 2337.76 | 1782.39 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 455.28 | 1233.58 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1725.71 | 02-JAN-09:09 | 437.18 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 | 19-JAN-12:07 | 814.40 | 26-JAN-03:00 |
February | 2337.76 | 01-FEB-15:09 | 1725.71 | 01-FEB-09:09 | 437.18 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.78 | 02-FEB-13:00 | 1233.58 | 05-FEB-08:00 |
March | 2337.76 | 01-MAR-15:09 | 1725.71 | 01-MAR-09:09 | 437.18 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.55 | 28-MAR-14:00 | 939.26 | 20-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 1725.71 | 01-APR-09:09 | 437.18 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 101.15 | 29-APR-16:00 | 522.87 | 01-APR-21:10 |
May | 2337.76 | 01-MAY-14:09 | 1725.71 | 01-MAY-08:09 | 437.18 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 217.43 | 07-MAY-18:10 | 47.72 | 13-MAY-04:45 |
June | 2337.76 | 01-JUN-14:09 | 1725.71 | 01-JUN-08:09 | 437.18 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 218.80 | 09-JUN-20:10 | 122.74 | 07-JUN-02:15 |
July | 2337.76 | 01-JUL-10:09 | 1725.71 | 01-JUL-09:09 | 437.18 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 236.51 | 02-JUL-21:10 | 36.91 | 11-JUL-20:10 |
August | 2337.76 | 01-AUG-14:09 | 1725.71 | 01-AUG-08:09 | 437.18 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 346.38 | 22-AUG-20:10 | 196.08 | 25-AUG-24:00 |
September | 2337.76 | 01-SEP-14:09 | 1725.71 | 01-SEP-08:09 | 437.18 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 457.33 | 09-SEP-22:53 | 123.85 | 05-SEP-03:25 |
October | 2337.76 | 02-OCT-14:09 | 1725.71 | 02-OCT-08:09 | 437.18 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 215.30 | 08-OCT-18:10 | 507.49 | 29-OCT-02:00 |
November | 2337.76 | 01-NOV-14:09 | 1725.71 | 01-NOV-08:09 | 437.18 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.62 | 07-NOV-21:47 | 704.48 | 12-NOV-08:00 |
December | 2337.76 | 01-DEC-15:09 | 1725.71 | 01-DEC-09:09 | 437.18 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.51 | 13-DEC-14:00 | 971.86 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1725.71 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 | 36.91 | |||||
Maximum of Months | 2337.76 | 1725.71 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 457.33 | 1233.58 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 2.58 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.85 | 02-JAN-15:00 | 18219.67 | 04-JAN-18:00 |
February | 0.00 | 01-FEB-00:10 | 2.58 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.55 | 24-FEB-12:55 | 20305.56 | 04-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 2.58 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.63 | 30-MAR-13:00 | 17685.64 | 11-MAR-12:10 |
April | 0.00 | 01-APR-00:10 | 2.58 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.05 | 28-APR-11:02 | 2180.06 | 11-APR-07:01 |
May | 0.00 | 01-MAY-00:10 | 2.58 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1907.71 | 27-MAY-11:02 | 1168.88 | 13-MAY-11:53 |
June | 0.00 | 01-JUN-00:10 | 2.58 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1927.03 | 14-JUN-11:02 | 1409.34 | 18-JUN-13:53 |
July | 0.00 | 01-JUL-00:10 | 2.58 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2724.49 | 18-JUL-11:01 | 1274.26 | 31-JUL-11:02 |
August | 0.00 | 01-AUG-00:10 | 2.58 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1906.11 | 01-AUG-11:02 | 1573.76 | 06-AUG-15:53 |
September | 0.00 | 01-SEP-00:10 | 2.58 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1920.52 | 10-SEP-11:02 | 2484.64 | 02-SEP-15:52 |
October | 0.00 | 01-OCT-00:10 | 2.58 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 771.54 | 06-OCT-11:03 | 3757.37 | 27-OCT-11:01 |
November | 0.00 | 01-NOV-00:10 | 2.58 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.39 | 01-NOV-14:00 | 6682.30 | 12-NOV-12:01 |
December | 0.00 | 01-DEC-00:10 | 2.58 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.23 | 13-DEC-12:05 | 22022.20 | 20-DEC-18:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.85 | 1168.88 | ||||
Maximum of Months | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2724.49 | 22022.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21944.41 | 01-JAN-20:12 | 0.00 | 408.91 | 2269.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.03 |
February | 21997.61 | 27-FEB-22:02 | 0.00 | 408.91 | 3025.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.70 |
March | 21644.93 | 27-MAR-23:12 | 0.00 | 408.91 | 3025.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.52 |
April | 36542.48 | 17-APR-20:47 | 0.00 | 736.04 | 5445.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26406.13 | 07-MAY-18:13 | 0.00 | 245.35 | 1361.45 | 0.00 | 0.00 | 0.00 | 0.00 | 453.83 | 0.00 |
June | 26015.22 | 28-JUN-20:10 | 0.00 | 1724.78 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 397.12 | 0.00 |
July | 28951.83 | 07-JUL-22:43 | 0.00 | 245.35 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 280.52 | 0.00 |
August | 29255.76 | 02-AUG-22:03 | 0.00 | 245.35 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 265.54 | 0.00 |
September | 29073.89 | 10-SEP-22:03 | 0.00 | 245.35 | 1361.45 | 0.00 | 0.00 | 0.00 | 0.00 | 164.09 | 0.00 |
October | 32061.20 | 01-OCT-22:41 | 0.00 | 572.47 | 3176.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.88 |
November | 26296.08 | 04-NOV-23:22 | 0.00 | 490.69 | 2722.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.98 |
December | 26105.55 | 17-DEC-07:12 | 0.00 | 490.69 | 2722.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.69 |
Annual Sum or Average | |||||||||||
Minimum of Months | 21644.93 | 0.00 | 245.35 | 1361.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36542.48 | 0.00 | 1724.78 | 5445.79 | 0.00 | 0.00 | 0.00 | 0.00 | 453.83 | 564.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 137958.47 | 02-JAN-07:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.45 |
February | 140998.05 | 25-FEB-07:02 | 15506.05 | 1722.75 | 7732.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 151931.54 | 08-MAR-07:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.66 |
April | 147259.44 | 18-APR-06:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.44 |
May | 115935.78 | 12-MAY-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.96 |
June | 116292.56 | 12-JUN-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 |
July | 102700.87 | 18-JUL-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.95 |
August | 109547.64 | 04-AUG-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 10.46 | 0.00 |
September | 114829.63 | 23-SEP-06:02 | 15506.05 | 1722.75 | 7732.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 |
October | 204204.65 | 27-OCT-06:02 | 15506.05 | 1722.75 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.36 |
November | 138690.52 | 30-NOV-07:03 | 12404.84 | 1378.20 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.20 |
December | 143347.68 | 17-DEC-09:02 | 18607.26 | 2067.29 | 9279.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.39 |
Annual Sum or Average | |||||||||||
Minimum of Months | 102700.87 | 12404.84 | 1378.20 | 7732.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 204204.65 | 18607.26 | 2067.29 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 10.46 | 332.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18185.80 | 01-JAN-08:61 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.25 |
February | 17762.74 | 01-FEB-23:01 | 0.00 | 227.26 | 4483.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.79 |
March | 16149.86 | 25-MAR-23:31 | 0.00 | 259.73 | 3843.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.59 |
April | 15454.28 | 30-APR-22:51 | 0.00 | 259.73 | 3843.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.22 |
May | 14192.81 | 07-MAY-18:43 | 0.00 | 97.40 | 1441.26 | 0.00 | 0.00 | 0.00 | 0.00 | 111.91 | 0.00 |
June | 14685.03 | 28-JUN-20:10 | 0.00 | 1188.26 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 170.85 | 0.00 |
July | 16956.89 | 07-JUL-21:23 | 0.00 | 97.40 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 97.20 | 0.00 |
August | 18244.01 | 30-AUG-21:23 | 0.00 | 97.40 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18068.18 | 10-SEP-21:23 | 0.00 | 97.40 | 1441.26 | 0.00 | 0.00 | 0.00 | 0.00 | 69.14 | 0.00 |
October | 18931.92 | 26-OCT-20:41 | 0.00 | 292.19 | 5765.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.26 |
November | 19631.86 | 23-NOV-20:01 | 0.00 | 259.73 | 3843.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.94 |
December | 15527.74 | 03-DEC-08:61 | 0.00 | 324.66 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.07 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14192.81 | 0.00 | 97.40 | 1441.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19631.86 | 0.00 | 1188.26 | 5765.03 | 0.00 | 0.00 | 0.00 | 0.00 | 170.85 | 106.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13870.85 | 29-JAN-19:19 | 0.00 | 227.26 | 504.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.22 |
February | 12117.03 | 01-FEB-23:04 | 0.00 | 227.26 | 673.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.44 |
March | 16546.30 | 24-MAR-21:21 | 0.00 | 259.73 | 769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.31 |
April | 17239.44 | 17-APR-20:41 | 0.00 | 292.19 | 865.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12269.81 | 07-MAY-18:43 | 0.00 | 97.40 | 216.32 | 0.00 | 0.00 | 0.00 | 0.00 | 112.56 | 0.00 |
June | 11795.20 | 28-JUN-20:10 | 0.00 | 1188.26 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 171.85 | 0.00 |
July | 13633.07 | 07-JUL-22:03 | 0.00 | 97.40 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 70.17 | 0.00 |
August | 14692.63 | 30-AUG-22:03 | 0.00 | 97.40 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14960.32 | 10-SEP-22:43 | 0.00 | 97.40 | 216.32 | 0.00 | 0.00 | 0.00 | 0.00 | 45.73 | 0.00 |
October | 16269.06 | 26-OCT-21:29 | 0.00 | 259.73 | 769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.56 |
November | 15459.35 | 24-NOV-21:19 | 0.00 | 259.73 | 769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.94 |
December | 15888.86 | 17-DEC-20:01 | 0.00 | 292.19 | 648.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.66 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11795.20 | 0.00 | 97.40 | 216.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17239.44 | 0.00 | 1188.26 | 865.29 | 0.00 | 0.00 | 0.00 | 0.00 | 171.85 | 383.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.57 |
April | 0.00 | 01-APR-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.51 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 |
June | 0.00 | 01-JUN-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.03 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.70 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.55 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | |
Maximum of Months | 0.00 | 0.00 | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.640520E+11 | 71638.69 | 19-JAN-15:09 | 0.109763E+11 | 73606.08 | 10-JAN-07:19 |
February | 0.607287E+11 | 68922.97 | 27-FEB-16:10 | 0.986944E+10 | 88694.31 | 05-FEB-09:20 |
March | 0.704619E+11 | 70741.71 | 06-MAR-15:00 | 0.948300E+10 | 61342.02 | 13-MAR-06:19 |
April | 0.783153E+11 | 84712.77 | 28-APR-15:00 | 0.723699E+10 | 4880.31 | 03-APR-11:50 |
May | 0.104029E+12 | 85725.36 | 27-MAY-15:20 | 0.733574E+10 | 4846.45 | 01-MAY-11:09 |
June | 0.106078E+12 | 91253.99 | 28-JUN-14:00 | 0.701018E+10 | 4812.38 | 01-JUN-11:00 |
July | 0.111088E+12 | 95952.32 | 22-JUL-15:00 | 0.713534E+10 | 4789.73 | 03-JUL-11:39 |
August | 0.111848E+12 | 90145.51 | 03-AUG-15:00 | 0.720948E+10 | 4799.52 | 31-AUG-11:09 |
September | 0.101827E+12 | 95766.34 | 09-SEP-16:00 | 0.703144E+10 | 4826.15 | 29-SEP-11:50 |
October | 0.978466E+11 | 92480.48 | 07-OCT-13:30 | 0.737284E+10 | 4864.30 | 31-OCT-11:39 |
November | 0.741841E+11 | 81295.24 | 02-NOV-14:09 | 0.726308E+10 | 4898.44 | 30-NOV-12:39 |
December | 0.697869E+11 | 75703.84 | 15-DEC-14:30 | 0.987567E+10 | 84393.49 | 21-DEC-07:19 |
Annual Sum or Average | 0.105024E+13 | 0.977995E+11 | ||||
Minimum of Months | 0.607287E+11 | 68922.97 | 0.701018E+10 | 4789.73 | ||
Maximum of Months | 0.111848E+12 | 95952.32 | 0.109763E+11 | 88694.31 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.264919E+11 | 0.385459E+10 | 0.163682E+11 | 0.00 | 0.107704E+11 | 0.00 | 0.00 | 0.656693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233909E+11 | 0.328027E+10 | 0.148500E+11 | 0.00 | 0.979661E+10 | 0.00 | 0.00 | 0.941090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.257357E+11 | 0.332868E+10 | 0.167807E+11 | 0.00 | 0.108982E+11 | 0.00 | 0.00 | 0.137186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237189E+11 | 0.292755E+10 | 0.159462E+11 | 0.00 | 0.105276E+11 | 0.00 | 0.00 | 0.251951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.243461E+11 | 0.276030E+10 | 0.165744E+11 | 0.00 | 0.114058E+11 | 0.00 | 0.00 | 0.489425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.236190E+11 | 0.252705E+10 | 0.162059E+11 | 0.00 | 0.115823E+11 | 0.00 | 0.00 | 0.521436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.230605E+11 | 0.268748E+10 | 0.163148E+11 | 0.00 | 0.123374E+11 | 0.00 | 0.00 | 0.566874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.239008E+11 | 0.290189E+10 | 0.167807E+11 | 0.00 | 0.122969E+11 | 0.00 | 0.00 | 0.559679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.226625E+11 | 0.309746E+10 | 0.159462E+11 | 0.00 | 0.113960E+11 | 0.00 | 0.00 | 0.487243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.245571E+11 | 0.350870E+10 | 0.163682E+11 | 0.00 | 0.115932E+11 | 0.00 | 0.00 | 0.418195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252571E+11 | 0.365169E+10 | 0.158468E+11 | 0.00 | 0.104288E+11 | 0.00 | 0.00 | 0.189997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.264973E+11 | 0.392134E+10 | 0.163148E+11 | 0.00 | 0.108336E+11 | 0.00 | 0.00 | 0.122198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293238E+12 | 0.384470E+11 | 0.194297E+12 | 0.133867E+12 | 0.00 | 0.390396E+12 | |||||||
Minimum of Months | 0.226625E+11 | 0.252705E+10 | 0.148500E+11 | 0.00 | 0.979661E+10 | 0.00 | 0.00 | 0.656693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.264973E+11 | 0.392134E+10 | 0.167807E+11 | 0.00 | 0.123374E+11 | 0.00 | 0.00 | 0.566874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.327883E+10 | 0.00 | 0.769744E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.292100E+10 | 0.00 | 0.694844E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.182706E+10 | 0.00 | 0.765594E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.723699E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.733574E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.701018E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.713534E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.720948E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.703144E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.737284E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.726308E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.223645E+10 | 0.00 | 0.763922E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.102633E+11 | 0.875361E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.694844E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.327883E+10 | 0.00 | 0.769744E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 24449.72 | 02-JAN-15:20 | 3371.20 | 01-JAN-06:10 | 10740.89 | 02-JAN-09:09 | 0.00 | 8875.55 | 05-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 24449.72 | 01-FEB-09:09 | 3371.20 | 01-FEB-06:10 | 10740.89 | 01-FEB-09:09 | 0.00 | 9753.11 | 05-FEB-09:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 24449.72 | 01-MAR-09:09 | 3371.20 | 01-MAR-06:10 | 10740.89 | 01-MAR-09:09 | 0.00 | 9528.69 | 07-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 24449.72 | 01-APR-16:00 | 3371.20 | 01-APR-05:10 | 10740.89 | 01-APR-09:09 | 0.00 | 9528.69 | 15-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 24449.72 | 01-MAY-16:30 | 3371.20 | 01-MAY-05:10 | 10740.89 | 01-MAY-08:09 | 0.00 | 9528.69 | 06-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 24449.72 | 08-JUN-08:09 | 3371.20 | 01-JUN-05:10 | 10740.89 | 01-JUN-08:09 | 0.00 | 10062.51 | 28-JUN-14:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 24449.72 | 25-JUL-08:20 | 3371.20 | 01-JUL-05:10 | 10740.89 | 01-JUL-09:09 | 0.00 | 10782.43 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 24449.72 | 02-AUG-08:09 | 3371.20 | 01-AUG-05:10 | 10740.89 | 01-AUG-08:09 | 0.00 | 10382.97 | 06-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 24449.72 | 05-SEP-08:09 | 3371.20 | 01-SEP-05:10 | 10740.89 | 01-SEP-08:09 | 0.00 | 11173.15 | 10-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 24449.72 | 02-OCT-08:09 | 3371.20 | 01-OCT-05:10 | 10740.89 | 02-OCT-08:09 | 0.00 | 10560.62 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 24449.72 | 01-NOV-08:09 | 3371.20 | 01-NOV-05:10 | 10740.89 | 01-NOV-08:09 | 0.00 | 9528.69 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 24449.72 | 01-DEC-09:09 | 3371.20 | 01-DEC-06:10 | 10740.89 | 01-DEC-09:09 | 0.00 | 9528.69 | 11-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 24449.72 | 3371.20 | 10740.89 | 0.00 | 8875.55 | 0.00 | 0.00 | |||||
Maximum of Months | 24449.72 | 3371.20 | 10740.89 | 0.00 | 11173.15 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 29564.51 | 19-JAN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29793.58 | 24-FEB-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31220.56 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42784.34 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43761.05 | 24-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 50309.37 | 28-JUN-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 54708.22 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 49573.01 | 03-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 51630.00 | 09-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 51910.70 | 07-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39821.60 | 02-NOV-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34147.01 | 16-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 29564.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54708.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 71638.69 | 19-JAN-15:09 | 24449.72 | 10740.89 | 0.00 | 0.00 | 6883.58 | 0.00 | 0.00 | 29564.51 | 0.00 |
February | 68922.97 | 27-FEB-16:10 | 24449.72 | 10740.89 | 0.00 | 0.00 | 6666.61 | 0.00 | 0.00 | 27065.75 | 0.00 |
March | 70741.71 | 06-MAR-15:00 | 24449.72 | 10740.89 | 0.00 | 0.00 | 6596.80 | 0.00 | 0.00 | 28954.30 | 0.00 |
April | 84712.77 | 28-APR-15:00 | 22873.41 | 10740.89 | 0.00 | 0.00 | 8314.14 | 0.00 | 0.00 | 42784.34 | 0.00 |
May | 85725.36 | 27-MAY-15:20 | 22873.41 | 10740.89 | 0.00 | 0.00 | 8510.49 | 0.00 | 0.00 | 43600.58 | 0.00 |
June | 91253.99 | 28-JUN-14:00 | 21297.09 | 10740.89 | 0.00 | 0.00 | 9883.08 | 0.00 | 0.00 | 49332.93 | 0.00 |
July | 95952.32 | 22-JUL-15:00 | 19720.78 | 10740.89 | 0.00 | 0.00 | 10782.43 | 0.00 | 0.00 | 54708.22 | 0.00 |
August | 90145.51 | 03-AUG-15:00 | 21297.09 | 10740.89 | 0.00 | 0.00 | 9348.62 | 0.00 | 0.00 | 48758.90 | 0.00 |
September | 95766.34 | 09-SEP-16:00 | 24449.72 | 10740.89 | 0.00 | 0.00 | 9716.00 | 0.00 | 0.00 | 50859.74 | 0.00 |
October | 92480.48 | 07-OCT-13:30 | 19720.78 | 10740.89 | 0.00 | 0.00 | 10464.51 | 0.00 | 0.00 | 51554.31 | 0.00 |
November | 81295.24 | 02-NOV-14:09 | 22873.41 | 10740.89 | 0.00 | 0.00 | 7859.34 | 0.00 | 0.00 | 39821.60 | 0.00 |
December | 75703.84 | 15-DEC-14:30 | 24449.72 | 10740.89 | 0.00 | 0.00 | 6937.74 | 0.00 | 0.00 | 33575.50 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 68922.97 | 19720.78 | 10740.89 | 0.00 | 0.00 | 6596.80 | 0.00 | 0.00 | 27065.75 | 0.00 | |
Maximum of Months | 95952.32 | 24449.72 | 10740.89 | 0.00 | 0.00 | 10782.43 | 0.00 | 0.00 | 54708.22 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 69071.98 | 10-JAN-07:19 | 0.00 | 4929.90 | 23-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 86834.31 | 05-FEB-09:20 | 0.00 | 4928.74 | 06-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 59482.02 | 13-MAR-06:19 | 0.00 | 4912.92 | 01-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 4880.31 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4846.45 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4812.38 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4789.73 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4799.52 | 31-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4826.15 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 4864.30 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 4898.44 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 79861.07 | 21-DEC-07:19 | 0.00 | 4922.01 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4789.73 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 86834.31 | 0.00 | 4929.90 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.47 | 0.00 | 0.00 | 0.33 | 24.45 | 0.00 | 0.00 |
February | 0.50 | 20.53 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.46 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.48 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.49 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.46 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.46 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.47 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.48 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.47 | 0.00 | 0.00 |
December | 0.17 | 20.53 | 0.00 | 0.00 | 1.50 | 24.48 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 20.50 | 0.00 | 11.33 | 24.47 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.53 | 0.00 | 0.00 | 2.33 | 24.49 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.49 | 0.00 | 0.00 |
February | 0.17 | 20.44 | 0.00 | 0.00 | 4.33 | 24.49 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.49 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.48 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 24.51 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 24.51 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 24.54 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 24.55 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 24.57 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 | 24.59 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 24.53 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 24.50 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.44 | 0.00 | 216.33 | 24.55 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.48 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.44 | 0.00 | 0.00 | 43.33 | 24.59 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.49 | 0.00 | 0.00 | 1.17 | 24.49 | 0.00 | 0.00 |
February | 0.17 | 20.24 | 0.00 | 0.00 | 0.67 | 24.46 | 0.00 | 0.00 |
March | 0.17 | 20.36 | 0.00 | 0.00 | 1.33 | 24.48 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.49 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.48 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.47 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 24.49 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 24.50 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 24.54 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 24.54 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.48 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.48 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.36 | 0.00 | 68.83 | 24.51 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.46 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.49 | 0.00 | 0.00 | 20.50 | 24.54 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 89.00 | 13.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50.83 | 13.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45.33 | 13.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.17 | 14.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49.50 | 12.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 240.83 | 13.52 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.00 | 14.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 329.00 | 22.70 | 93.50 | 23.55 | 38.83 | 23.08 |
February | 244.00 | 22.90 | 164.17 | 23.52 | 72.67 | 23.06 |
March | 241.67 | 23.10 | 131.67 | 23.73 | 21.50 | 22.94 |
April | 86.17 | 23.72 | 239.83 | 23.89 | 14.00 | 23.89 |
May | 4.83 | 23.89 | 398.83 | 23.89 | 4.83 | 23.89 |
June | 0.00 | 0.00 | 384.67 | 23.89 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 402.17 | 23.89 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 411.17 | 23.89 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 391.17 | 23.89 | 0.00 | 0.00 |
October | 34.67 | 23.78 | 320.50 | 23.89 | 1.33 | 23.89 |
November | 145.00 | 23.59 | 142.67 | 23.89 | 2.83 | 23.89 |
December | 260.33 | 22.92 | 116.33 | 23.79 | 17.33 | 23.20 |
Annual Sum or Average | 1345.67 | 23.04 | 3196.67 | 23.85 | 173.33 | 23.17 |
Minimum of Months | 0.00 | 0.00 | 93.50 | 23.52 | 0.00 | 0.00 |
Maximum of Months | 329.00 | 23.89 | 411.17 | 23.89 | 72.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 297.67 | 22.65 | 108.50 | 23.84 | 29.83 | 23.70 |
February | 199.67 | 22.84 | 186.67 | 23.84 | 41.00 | 23.71 |
March | 164.83 | 22.81 | 185.33 | 23.88 | 9.83 | 23.88 |
April | 37.50 | 23.54 | 310.00 | 23.89 | 16.67 | 23.89 |
May | 30.17 | 23.90 | 418.00 | 23.89 | 30.17 | 23.90 |
June | 17.67 | 23.90 | 408.00 | 23.89 | 17.67 | 23.90 |
July | 54.33 | 23.90 | 415.00 | 23.89 | 54.33 | 23.90 |
August | 46.67 | 23.90 | 422.00 | 23.89 | 46.67 | 23.90 |
September | 53.67 | 23.90 | 405.00 | 23.89 | 53.67 | 23.90 |
October | 59.33 | 23.80 | 351.67 | 23.89 | 49.83 | 23.90 |
November | 94.33 | 23.40 | 216.67 | 23.89 | 22.50 | 23.89 |
December | 228.17 | 22.79 | 156.50 | 23.89 | 30.00 | 23.89 |
Annual Sum or Average | 1284.00 | 23.06 | 3583.33 | 23.89 | 402.17 | 23.86 |
Minimum of Months | 17.67 | 22.65 | 108.50 | 23.84 | 9.83 | 23.70 |
Maximum of Months | 297.67 | 23.90 | 422.00 | 23.89 | 54.33 | 23.90 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 134.67 | 22.91 | 153.00 | 23.87 | 10.50 | 23.60 |
February | 117.17 | 22.97 | 199.00 | 23.84 | 14.33 | 23.21 |
March | 138.33 | 22.94 | 191.83 | 23.86 | 3.17 | 22.28 |
April | 33.00 | 23.50 | 282.50 | 23.89 | 0.67 | 23.89 |
May | 1.33 | 23.89 | 404.00 | 23.89 | 1.33 | 23.89 |
June | 0.00 | 0.00 | 391.17 | 23.89 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 404.83 | 23.89 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 413.83 | 23.89 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 394.00 | 23.89 | 0.00 | 0.00 |
October | 7.33 | 23.50 | 364.17 | 23.89 | 0.00 | 0.00 |
November | 25.00 | 23.46 | 283.00 | 23.89 | 0.00 | 0.00 |
December | 109.50 | 23.02 | 216.50 | 23.87 | 7.83 | 23.30 |
Annual Sum or Average | 566.33 | 23.02 | 3697.83 | 23.88 | 37.83 | 23.29 |
Minimum of Months | 0.00 | 0.00 | 153.00 | 23.84 | 0.00 | 0.00 |
Maximum of Months | 138.33 | 23.89 | 413.83 | 23.89 | 14.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 204.17 | 22.54 | 133.00 | 23.78 | 19.67 | 23.13 |
February | 164.67 | 22.64 | 181.83 | 23.77 | 27.83 | 23.13 |
March | 191.17 | 22.54 | 174.50 | 23.74 | 19.67 | 22.59 |
April | 95.17 | 23.44 | 261.67 | 23.89 | 31.50 | 23.88 |
May | 26.67 | 23.89 | 404.50 | 23.89 | 26.67 | 23.89 |
June | 7.17 | 23.89 | 390.67 | 23.89 | 7.17 | 23.89 |
July | 20.50 | 23.89 | 403.33 | 23.89 | 20.50 | 23.89 |
August | 11.00 | 23.89 | 411.33 | 23.89 | 11.00 | 23.89 |
September | 14.83 | 23.89 | 393.33 | 23.89 | 14.83 | 23.89 |
October | 25.50 | 23.50 | 356.33 | 23.89 | 7.33 | 23.89 |
November | 46.00 | 23.14 | 255.00 | 23.89 | 1.50 | 23.89 |
December | 157.67 | 22.50 | 195.00 | 23.82 | 19.67 | 23.21 |
Annual Sum or Average | 964.50 | 22.80 | 3560.50 | 23.87 | 207.33 | 23.53 |
Minimum of Months | 7.17 | 22.50 | 133.00 | 23.74 | 1.50 | 22.59 |
Maximum of Months | 204.17 | 23.89 | 411.33 | 23.89 | 31.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.93640 | 47.14236 | 0.05104 | 7.15974 |
February | 376.00000 | 23.24245 | 50.44071 | 0.16598 | 7.93019 |
March | 422.00000 | 23.42956 | 47.40945 | 0.20865 | 7.64539 |
April | 405.00000 | 23.85228 | 52.13271 | 0.40657 | 8.73889 |
May | 418.00000 | 23.88963 | 56.63540 | -0.3765 | 8.00301 |
June | 408.00000 | 23.88966 | 55.55917 | -0.3572 | 7.73002 |
July | 415.00000 | 23.88965 | 57.73055 | -0.3355 | 7.40641 |
August | 422.00000 | 23.88964 | 57.05968 | -0.3397 | 7.45937 |
September | 405.00000 | 23.88963 | 57.91233 | -0.3600 | 7.75842 |
October | 414.00000 | 23.88017 | 53.35627 | 0.47393 | 9.91048 |
November | 399.00000 | 23.77928 | 48.46994 | 0.34032 | 7.94416 |
December | 415.00000 | 23.27366 | 48.29417 | 0.17128 | 7.50766 |
Annual Sum or Average | 4913.00000 | 23.65539 | 52.69852 | 0.00159 | 7.93051 |
Minimum of Months | 376.00000 | 22.93640 | 47.14236 | -0.3765 | 7.15974 |
Maximum of Months | 422.00000 | 23.88966 | 57.91233 | 0.47393 | 9.91048 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.00882 | 44.56509 | 0.15008 | 7.30222 |
February | 376.00000 | 23.33594 | 48.09790 | 0.26726 | 8.45044 |
March | 422.00000 | 23.47316 | 45.93422 | 0.30020 | 8.35191 |
April | 405.00000 | 23.87065 | 51.67864 | 0.48073 | 10.08271 |
May | 418.00000 | 23.91355 | 58.70934 | -0.2836 | 6.72031 |
June | 408.00000 | 23.91358 | 58.59136 | -0.2660 | 6.52852 |
July | 415.00000 | 23.91483 | 61.62643 | -0.2457 | 6.30551 |
August | 422.00000 | 23.91407 | 60.73092 | -0.2551 | 6.40119 |
September | 405.00000 | 23.91384 | 61.47810 | -0.2730 | 6.60282 |
October | 414.00000 | 23.89550 | 55.00248 | 0.53649 | 11.26349 |
November | 399.00000 | 23.78237 | 48.37438 | 0.41120 | 9.02532 |
December | 415.00000 | 23.29199 | 46.98289 | 0.25520 | 8.07127 |
Annual Sum or Average | 4913.00000 | 23.68724 | 53.52472 | 0.08729 | 7.91517 |
Minimum of Months | 376.00000 | 23.00882 | 44.56509 | -0.2836 | 6.30551 |
Maximum of Months | 422.00000 | 23.91483 | 61.62643 | 0.53649 | 11.26349 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.56410 | 39.15156 | 0.31135 | 8.35741 |
February | 376.00000 | 23.60059 | 42.30131 | 0.34610 | 9.10870 |
March | 422.00000 | 23.57362 | 42.26268 | 0.31185 | 8.59821 |
April | 405.00000 | 23.85696 | 47.94491 | 0.45720 | 9.66772 |
May | 418.00000 | 23.88967 | 53.92286 | -0.3009 | 6.98548 |
June | 408.00000 | 23.88966 | 53.55361 | -0.2820 | 6.77822 |
July | 415.00000 | 23.88963 | 55.76264 | -0.2563 | 6.48277 |
August | 422.00000 | 23.88952 | 54.39574 | -0.2469 | 6.39272 |
September | 405.00000 | 23.88959 | 54.15981 | -0.2581 | 6.53746 |
October | 414.00000 | 23.88262 | 48.32852 | 0.56731 | 12.02077 |
November | 399.00000 | 23.86223 | 42.27763 | 0.47809 | 10.11595 |
December | 415.00000 | 23.65684 | 41.24258 | 0.37558 | 9.20662 |
Annual Sum or Average | 4913.00000 | 23.78775 | 47.99102 | 0.12239 | 8.34185 |
Minimum of Months | 376.00000 | 23.56410 | 39.15156 | -0.3009 | 6.39272 |
Maximum of Months | 422.00000 | 23.88967 | 55.76264 | 0.56731 | 12.02077 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.21395 | 41.69417 | 0.21788 | 7.96786 |
February | 376.00000 | 23.32768 | 44.99094 | 0.27072 | 8.81545 |
March | 422.00000 | 23.26981 | 45.17228 | 0.23156 | 8.44175 |
April | 405.00000 | 23.77732 | 51.76007 | 0.43141 | 9.41478 |
May | 418.00000 | 23.88959 | 57.23410 | -0.3221 | 7.24420 |
June | 408.00000 | 23.88961 | 56.46342 | -0.3059 | 7.05783 |
July | 415.00000 | 23.88960 | 58.80713 | -0.2777 | 6.70612 |
August | 422.00000 | 23.88951 | 57.23621 | -0.2718 | 6.64634 |
September | 405.00000 | 23.88952 | 57.25797 | -0.2813 | 6.77994 |
October | 414.00000 | 23.86550 | 50.24742 | 0.54549 | 11.56850 |
November | 399.00000 | 23.80027 | 44.28084 | 0.44591 | 9.64746 |
December | 415.00000 | 23.35376 | 43.65568 | 0.29253 | 8.82064 |
Annual Sum or Average | 4913.00000 | 23.67261 | 50.78367 | 0.07862 | 8.24940 |
Minimum of Months | 376.00000 | 23.21395 | 41.69417 | -0.3221 | 6.64634 |
Maximum of Months | 422.00000 | 23.88961 | 58.80713 | 0.54549 | 11.56850 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.265094E+10 | 0.678140E+09 | 127.96 | 0.170965E+10 | 0.941291E+09 | 0.00 | 0.88 | 31-JAN-21:30 | 0.00 | 01-JAN-00:05 | 28849.84 | 01-JAN-20:12 | 16523.34 | 01-JAN-20:12 | 12326.50 | 01-JAN-20:12 | 6223.85 | 01-JAN-20:12 | 0.00 | 01-JAN-00:05 |
February | 0.390467E+10 | 0.993078E+09 | 159.58 | 0.252171E+10 | 0.138296E+10 | 0.00 | 1.00 | 01-FEB-00:25 | 0.00 | 01-FEB-00:05 | 41928.85 | 28-FEB-22:45 | 20676.53 | 24-FEB-21:45 | 22081.91 | 28-FEB-22:45 | 8995.63 | 28-FEB-22:45 | 0.00 | 01-FEB-00:05 |
March | 0.614434E+10 | 0.157801E+10 | 252.95 | 0.420142E+10 | 0.194291E+10 | 0.00 | 1.00 | 27-MAR-21:00 | 0.00 | 01-MAR-00:05 | 41707.15 | 27-MAR-21:00 | 20637.37 | 28-MAR-21:00 | 21113.15 | 27-MAR-21:00 | 8963.55 | 27-MAR-21:00 | 0.00 | 01-MAR-00:05 |
April | 0.126572E+11 | 0.324452E+10 | 405.44 | 0.897359E+10 | 0.368364E+10 | 0.00 | 1.00 | 04-APR-21:00 | 0.00 | 01-APR-00:05 | 41573.77 | 04-APR-21:00 | 34644.03 | 17-APR-20:47 | 18952.99 | 04-APR-21:00 | 8943.47 | 04-APR-21:00 | 0.00 | 01-APR-00:05 |
May | 0.278975E+11 | 0.708194E+10 | 599.92 | 0.193306E+11 | 0.856689E+10 | 0.00 | 1.00 | 06-MAY-15:40 | 0.00 | 01-MAY-00:10 | 37453.36 | 07-MAY-18:13 | 29268.20 | 07-MAY-18:13 | 9996.45 | 23-MAY-20:20 | 9376.50 | 07-MAY-18:13 | 0.00 | 01-MAY-00:10 |
June | 0.300147E+11 | 0.762646E+10 | 602.44 | 0.210679E+11 | 0.894678E+10 | 0.00 | 1.00 | 15-JUN-10:10 | 0.00 | 01-JUN-00:05 | 38977.20 | 28-JUN-20:10 | 29208.34 | 28-JUN-20:10 | 11486.80 | 29-JUN-20:10 | 9452.59 | 28-JUN-20:10 | 0.00 | 01-JUN-00:05 |
July | 0.331249E+11 | 0.835624E+10 | 633.06 | 0.222577E+11 | 0.108672E+11 | 0.00 | 1.00 | 07-JUL-20:10 | 0.00 | 01-JUL-00:10 | 40587.19 | 07-JUL-20:10 | 32083.15 | 07-JUL-22:43 | 11711.20 | 04-JUL-18:10 | 10176.42 | 23-JUL-18:10 | 0.00 | 01-JUL-00:05 |
August | 0.331177E+11 | 0.832812E+10 | 639.46 | 0.225122E+11 | 0.106055E+11 | 0.00 | 1.00 | 02-AUG-20:10 | 0.00 | 01-AUG-00:05 | 41792.11 | 10-AUG-20:10 | 32478.82 | 02-AUG-22:03 | 13669.25 | 10-AUG-20:10 | 10152.33 | 24-AUG-20:10 | 0.00 | 01-AUG-00:05 |
September | 0.288794E+11 | 0.717702E+10 | 595.61 | 0.191082E+11 | 0.977116E+10 | 0.00 | 1.00 | 03-SEP-18:10 | 0.00 | 01-SEP-00:33 | 40646.27 | 03-SEP-18:43 | 32292.98 | 10-SEP-22:03 | 11797.07 | 09-SEP-21:10 | 10598.43 | 09-SEP-21:10 | 0.00 | 01-SEP-00:05 |
October | 0.235695E+11 | 0.590775E+10 | 541.44 | 0.161622E+11 | 0.740723E+10 | 0.00 | 1.00 | 01-OCT-01:20 | 0.00 | 01-OCT-00:05 | 41663.55 | 06-OCT-20:10 | 35961.17 | 26-OCT-20:11 | 15831.56 | 30-OCT-22:02 | 9673.16 | 13-OCT-20:10 | 0.00 | 01-OCT-00:05 |
November | 0.885856E+10 | 0.225176E+10 | 331.73 | 0.608501E+10 | 0.277355E+10 | 0.00 | 1.00 | 05-NOV-01:35 | 0.00 | 01-NOV-00:05 | 42134.93 | 08-NOV-06:00 | 22605.59 | 05-NOV-01:35 | 21481.62 | 08-NOV-06:00 | 9024.00 | 08-NOV-06:00 | 0.00 | 01-NOV-00:05 |
December | 0.553657E+10 | 0.139999E+10 | 212.37 | 0.368131E+10 | 0.185527E+10 | 0.00 | 1.00 | 09-DEC-23:25 | 0.00 | 01-DEC-00:05 | 41605.72 | 13-DEC-00:40 | 22854.06 | 17-DEC-07:12 | 21067.54 | 13-DEC-00:40 | 8948.34 | 13-DEC-00:40 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.216356E+12 | 0.546230E+11 | 5101.95 | 0.147612E+12 | 0.687444E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.265094E+10 | 0.678140E+09 | 127.96 | 0.170965E+10 | 0.941291E+09 | 0.00 | 0.88 | 0.00 | 28849.84 | 16523.34 | 9996.45 | 6223.85 | 0.00 | |||||||
Maximum of Months | 0.331249E+11 | 0.835624E+10 | 639.46 | 0.225122E+11 | 0.108672E+11 | 0.00 | 1.00 | 0.00 | 42134.93 | 35961.17 | 22081.91 | 10598.43 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.147663E+11 | 0.409587E+10 | 146.83 | 0.903373E+10 | 0.573259E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 193450.09 | 31-JAN-07:03 | 115436.41 | 01-JAN-09:02 | 103873.93 | 31-JAN-07:03 | 45214.07 | 31-JAN-07:03 | 0.00 | 01-JAN-00:05 |
February | 0.224591E+11 | 0.615180E+10 | 180.94 | 0.137993E+11 | 0.865987E+10 | 0.00 | 1.00 | 01-FEB-07:03 | 0.00 | 01-FEB-00:05 | 191486.62 | 26-FEB-09:02 | 99136.69 | 28-FEB-07:02 | 97776.10 | 26-FEB-09:02 | 44953.89 | 26-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.346777E+11 | 0.952436E+10 | 256.81 | 0.223075E+11 | 0.123703E+11 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:05 | 195240.50 | 07-MAR-07:02 | 125065.84 | 06-MAR-07:03 | 92787.59 | 28-MAR-06:02 | 45422.61 | 07-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.649391E+11 | 0.176971E+11 | 366.07 | 0.423960E+11 | 0.225431E+11 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:05 | 195833.90 | 29-APR-06:02 | 149547.19 | 18-APR-06:03 | 99821.08 | 14-APR-06:02 | 46225.54 | 29-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.125989E+12 | 0.334255E+11 | 441.65 | 0.762778E+11 | 0.497114E+11 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 199837.09 | 23-MAY-06:02 | 129986.35 | 12-MAY-06:02 | 94404.81 | 23-MAY-06:04 | 48679.28 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.134789E+12 | 0.356226E+11 | 431.89 | 0.810738E+11 | 0.537147E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:05 | 199395.60 | 19-JUN-06:02 | 131419.51 | 11-JUN-08:62 | 90927.10 | 19-JUN-06:04 | 49085.55 | 18-JUN-08:62 | 0.00 | 01-JUN-00:05 |
July | 0.148130E+12 | 0.384965E+11 | 440.14 | 0.829227E+11 | 0.652070E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 200978.86 | 02-JUL-08:62 | 122785.05 | 19-JUL-06:02 | 94313.61 | 02-JUL-08:04 | 49886.81 | 09-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.144012E+12 | 0.375357E+11 | 447.35 | 0.823709E+11 | 0.616410E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:05 | 201021.97 | 06-AUG-08:62 | 128830.83 | 04-AUG-06:02 | 93724.94 | 06-AUG-08:04 | 49058.97 | 06-AUG-08:04 | 0.00 | 01-AUG-00:05 |
September | 0.125277E+12 | 0.323953E+11 | 428.87 | 0.693576E+11 | 0.559195E+11 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 199831.07 | 17-SEP-08:62 | 126399.37 | 23-SEP-06:02 | 94300.40 | 05-SEP-06:04 | 51656.35 | 10-SEP-08:06 | 0.00 | 01-SEP-00:05 |
October | 0.104033E+12 | 0.273560E+11 | 407.36 | 0.618468E+11 | 0.421858E+11 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:05 | 200420.45 | 22-OCT-08:62 | 159745.70 | 27-OCT-06:02 | 96986.40 | 22-OCT-08:04 | 48260.65 | 07-OCT-06:02 | 0.00 | 01-OCT-00:05 |
November | 0.455842E+11 | 0.123298E+11 | 305.39 | 0.284125E+11 | 0.171717E+11 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:05 | 196992.50 | 02-NOV-06:02 | 127971.35 | 06-NOV-07:02 | 100915.75 | 04-NOV-06:04 | 46753.70 | 11-NOV-09:02 | 0.00 | 01-NOV-00:05 |
December | 0.287949E+11 | 0.779377E+10 | 209.28 | 0.174961E+11 | 0.112988E+11 | 0.00 | 1.00 | 09-DEC-07:03 | 0.00 | 01-DEC-00:05 | 196078.60 | 12-DEC-07:02 | 120349.49 | 17-DEC-09:02 | 92717.54 | 09-DEC-07:03 | 45520.87 | 15-DEC-07:02 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.993450E+12 | 0.262424E+12 | 4062.58 | 0.587295E+12 | 0.406156E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.147663E+11 | 0.409587E+10 | 146.83 | 0.903373E+10 | 0.573259E+10 | 0.00 | 1.00 | 0.00 | 191486.62 | 99136.69 | 90927.10 | 44953.89 | 0.00 | |||||||
Maximum of Months | 0.148130E+12 | 0.384965E+11 | 447.35 | 0.829227E+11 | 0.652070E+11 | 0.00 | 1.00 | 0.00 | 201021.97 | 159745.70 | 103873.93 | 51656.35 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.452468E+10 | 0.108146E+10 | 277.45 | 0.331946E+10 | 0.120522E+10 | 0.00 | 1.00 | 01-JAN-00:55 | 0.00 | 01-JAN-00:05 | 24712.47 | 16-JAN-19:12 | 17269.63 | 02-JAN-21:15 | 11024.01 | 02-JAN-03:50 | 5250.99 | 16-JAN-19:12 | 0.00 | 01-JAN-00:05 |
February | 0.575784E+10 | 0.136102E+10 | 282.50 | 0.416721E+10 | 0.159064E+10 | 0.00 | 1.00 | 01-FEB-21:12 | 0.00 | 01-FEB-00:25 | 25116.46 | 01-FEB-23:01 | 13783.92 | 20-FEB-19:25 | 12307.14 | 01-FEB-21:12 | 5319.81 | 01-FEB-23:01 | 0.00 | 01-FEB-00:05 |
March | 0.654538E+10 | 0.157710E+10 | 328.84 | 0.479013E+10 | 0.175525E+10 | 0.00 | 1.00 | 01-MAR-01:50 | 0.00 | 01-MAR-00:15 | 25546.48 | 28-MAR-22:45 | 17645.54 | 04-MAR-22:20 | 13212.93 | 28-MAR-22:45 | 5384.01 | 28-MAR-22:45 | 0.00 | 01-MAR-00:05 |
April | 0.103678E+11 | 0.254914E+10 | 473.31 | 0.754986E+10 | 0.281797E+10 | 0.00 | 1.00 | 03-APR-20:20 | 0.00 | 01-APR-00:10 | 25326.85 | 15-APR-21:25 | 21129.65 | 17-APR-20:11 | 12729.46 | 15-APR-21:25 | 5352.42 | 15-APR-21:25 | 0.00 | 01-APR-00:05 |
May | 0.191733E+11 | 0.473857E+10 | 629.42 | 0.132595E+11 | 0.591374E+10 | 0.00 | 1.00 | 04-MAY-11:35 | 0.00 | 01-MAY-00:10 | 21163.58 | 25-MAY-20:10 | 15853.97 | 25-MAY-20:10 | 6038.61 | 24-MAY-20:10 | 5097.29 | 25-MAY-20:10 | 0.00 | 01-MAY-00:10 |
June | 0.200168E+11 | 0.495727E+10 | 617.72 | 0.138571E+11 | 0.615971E+10 | 0.00 | 1.00 | 05-JUN-10:30 | 0.00 | 01-JUN-00:05 | 22306.71 | 28-JUN-20:10 | 16641.73 | 28-JUN-20:10 | 6721.04 | 29-JUN-20:10 | 5322.74 | 28-JUN-20:10 | 0.00 | 01-JUN-00:05 |
July | 0.221085E+11 | 0.542492E+10 | 642.50 | 0.145861E+11 | 0.752240E+10 | 0.00 | 1.00 | 07-JUL-21:23 | 0.00 | 01-JUL-00:10 | 24588.84 | 19-JUL-20:43 | 19096.98 | 07-JUL-21:23 | 7067.02 | 04-JUL-18:10 | 5825.20 | 07-JUL-21:23 | 0.00 | 01-JUL-00:05 |
August | 0.227595E+11 | 0.556853E+10 | 648.28 | 0.154011E+11 | 0.735841E+10 | 0.00 | 1.00 | 02-AUG-20:43 | 0.00 | 01-AUG-00:10 | 25262.05 | 10-AUG-20:10 | 20480.77 | 30-AUG-21:23 | 8071.73 | 10-AUG-20:10 | 6057.41 | 24-AUG-20:08 | 0.00 | 01-AUG-00:05 |
September | 0.209915E+11 | 0.506733E+10 | 622.42 | 0.140453E+11 | 0.694617E+10 | 0.00 | 1.00 | 03-SEP-18:08 | 0.00 | 01-SEP-00:33 | 24564.64 | 10-SEP-18:08 | 20269.16 | 10-SEP-21:23 | 7266.72 | 09-SEP-21:08 | 6333.46 | 09-SEP-21:08 | 0.00 | 01-SEP-00:05 |
October | 0.195861E+11 | 0.472609E+10 | 589.29 | 0.140163E+11 | 0.556989E+10 | 0.00 | 1.00 | 01-OCT-01:51 | 0.00 | 01-OCT-00:25 | 25208.60 | 07-OCT-21:43 | 21541.53 | 26-OCT-20:10 | 9031.79 | 01-OCT-05:00 | 5753.10 | 13-OCT-20:08 | 0.00 | 01-OCT-00:05 |
November | 0.106685E+11 | 0.253825E+10 | 440.76 | 0.797228E+10 | 0.269619E+10 | 0.00 | 1.00 | 02-NOV-20:08 | 0.00 | 01-NOV-00:10 | 25074.47 | 07-NOV-21:43 | 21868.32 | 22-NOV-23:13 | 10890.63 | 20-NOV-21:12 | 5578.35 | 07-NOV-21:43 | 0.00 | 01-NOV-00:05 |
December | 0.746547E+10 | 0.177040E+10 | 351.64 | 0.551390E+10 | 0.195157E+10 | 0.00 | 1.00 | 01-DEC-21:15 | 0.00 | 01-DEC-00:05 | 24541.93 | 27-DEC-24:00 | 18002.62 | 07-DEC-21:55 | 10580.92 | 27-DEC-24:00 | 5219.57 | 27-DEC-24:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.169965E+12 | 0.413601E+11 | 5904.13 | 0.118478E+12 | 0.514871E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.452468E+10 | 0.108146E+10 | 277.45 | 0.331946E+10 | 0.120522E+10 | 0.00 | 1.00 | 0.00 | 21163.58 | 13783.92 | 6038.61 | 5097.29 | 0.00 | |||||||
Maximum of Months | 0.227595E+11 | 0.556853E+10 | 648.28 | 0.154011E+11 | 0.752240E+10 | 0.00 | 1.00 | 0.00 | 25546.48 | 21868.32 | 13212.93 | 6333.46 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.297064E+10 | 0.711454E+09 | 204.75 | 0.202552E+10 | 0.945117E+09 | 0.00 | 1.00 | 01-JAN-01:00 | 0.00 | 01-JAN-00:05 | 20924.96 | 17-JAN-21:20 | 13922.73 | 02-JAN-21:20 | 11024.91 | 18-JAN-21:12 | 4417.74 | 17-JAN-21:20 | 0.00 | 01-JAN-00:05 |
February | 0.382910E+10 | 0.905006E+09 | 217.21 | 0.258599E+10 | 0.124311E+10 | 0.00 | 1.00 | 01-FEB-00:45 | 0.00 | 01-FEB-00:05 | 20918.21 | 21-FEB-21:20 | 10589.73 | 25-FEB-23:02 | 11004.50 | 21-FEB-21:20 | 4416.76 | 21-FEB-21:20 | 0.00 | 01-FEB-00:05 |
March | 0.427365E+10 | 0.103913E+10 | 261.70 | 0.289670E+10 | 0.137695E+10 | 0.00 | 1.00 | 24-MAR-20:22 | 0.00 | 01-MAR-00:10 | 21181.52 | 31-MAR-20:30 | 14080.00 | 24-MAR-21:21 | 11011.80 | 30-MAR-20:20 | 4452.87 | 31-MAR-20:30 | 0.00 | 01-MAR-00:05 |
April | 0.689195E+10 | 0.170439E+10 | 391.40 | 0.466870E+10 | 0.222325E+10 | 0.00 | 1.00 | 04-APR-21:50 | 0.00 | 01-APR-00:05 | 20709.22 | 19-APR-20:20 | 16475.10 | 17-APR-20:41 | 9900.90 | 04-APR-21:50 | 4384.95 | 19-APR-20:20 | 0.00 | 01-APR-00:05 |
May | 0.150647E+11 | 0.369656E+10 | 606.89 | 0.971585E+10 | 0.534883E+10 | 0.00 | 1.00 | 08-MAY-13:00 | 0.00 | 01-MAY-00:10 | 17772.54 | 07-MAY-18:43 | 13479.81 | 07-MAY-18:43 | 5561.63 | 19-MAY-20:10 | 4240.34 | 07-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 0.160620E+11 | 0.393732E+10 | 602.47 | 0.103709E+11 | 0.569113E+10 | 0.00 | 1.00 | 19-JUN-16:25 | 0.00 | 01-JUN-00:05 | 18876.70 | 28-JUN-20:10 | 13174.06 | 28-JUN-20:10 | 6734.25 | 29-JUN-20:10 | 4483.85 | 28-JUN-20:10 | 0.00 | 01-JUN-00:05 |
July | 0.181818E+11 | 0.440977E+10 | 635.03 | 0.111561E+11 | 0.702569E+10 | 0.00 | 1.00 | 07-JUL-20:10 | 0.00 | 01-JUL-00:10 | 20474.41 | 07-JUL-20:10 | 15116.30 | 07-JUL-22:03 | 7043.85 | 04-JUL-18:10 | 5021.24 | 23-JUL-18:10 | 0.00 | 01-JUL-00:05 |
August | 0.187078E+11 | 0.453559E+10 | 643.61 | 0.118214E+11 | 0.688635E+10 | 0.00 | 1.00 | 02-AUG-20:08 | 0.00 | 01-AUG-00:05 | 21183.88 | 10-AUG-20:10 | 16229.00 | 30-AUG-22:03 | 7854.33 | 10-AUG-20:10 | 5000.17 | 24-AUG-20:08 | 0.00 | 01-AUG-00:05 |
September | 0.170346E+11 | 0.408468E+10 | 613.24 | 0.105948E+11 | 0.643981E+10 | 0.00 | 1.00 | 01-SEP-20:43 | 0.00 | 01-SEP-00:33 | 20696.28 | 01-SEP-20:43 | 16528.04 | 10-SEP-22:43 | 6678.38 | 09-SEP-21:08 | 5221.60 | 09-SEP-21:08 | 0.00 | 01-SEP-00:05 |
October | 0.159557E+11 | 0.382960E+10 | 573.95 | 0.107319E+11 | 0.522381E+10 | 0.00 | 1.00 | 01-OCT-01:20 | 0.00 | 01-OCT-00:05 | 21108.66 | 24-OCT-20:10 | 17261.79 | 26-OCT-20:10 | 8885.24 | 31-OCT-04:50 | 4749.98 | 13-OCT-20:08 | 0.00 | 01-OCT-00:05 |
November | 0.790522E+10 | 0.187987E+10 | 399.69 | 0.554303E+10 | 0.236219E+10 | 0.00 | 1.00 | 02-NOV-20:08 | 0.00 | 01-NOV-00:05 | 20817.42 | 07-NOV-21:43 | 17265.24 | 22-NOV-21:20 | 9694.17 | 30-NOV-00:40 | 4612.98 | 07-NOV-21:43 | 0.00 | 01-NOV-00:05 |
December | 0.530273E+10 | 0.125565E+10 | 291.79 | 0.368463E+10 | 0.161810E+10 | 0.00 | 1.00 | 07-DEC-23:03 | 0.00 | 01-DEC-00:05 | 20772.88 | 08-DEC-22:00 | 14716.18 | 17-DEC-20:01 | 9644.64 | 08-DEC-22:00 | 4394.93 | 08-DEC-22:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.132180E+12 | 0.319890E+11 | 5441.73 | 0.857955E+11 | 0.463843E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.297064E+10 | 0.711454E+09 | 204.75 | 0.202552E+10 | 0.945117E+09 | 0.00 | 1.00 | 0.00 | 17772.54 | 10589.73 | 5561.63 | 4240.34 | 0.00 | |||||||
Maximum of Months | 0.187078E+11 | 0.453559E+10 | 643.61 | 0.118214E+11 | 0.702569E+10 | 0.00 | 1.00 | 0.00 | 21183.88 | 17265.24 | 11024.91 | 5221.60 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.95 | 28.50 | 14.45 | 44.21 | 45.23 | 8.00 | 0.00 | 744.00 |
February | 55.94 | 38.57 | 17.37 | 63.78 | 40.32 | 1.50 | 0.00 | 672.00 |
March | 60.95 | 38.04 | 22.91 | 73.69 | 34.18 | 0.00 | 0.00 | 744.00 |
April | 78.41 | 51.41 | 27.00 | 104.88 | 25.03 | 0.00 | 0.00 | 720.00 |
May | 74.98 | 43.24 | 31.74 | 109.57 | 10.42 | 0.00 | 0.00 | 744.00 |
June | 82.88 | 48.36 | 34.52 | 122.61 | 10.23 | 0.00 | 0.00 | 720.00 |
July | 77.06 | 40.12 | 36.94 | 113.81 | 8.21 | 0.00 | 0.00 | 744.00 |
August | 71.68 | 36.23 | 35.44 | 106.20 | 9.72 | 0.00 | 0.00 | 744.00 |
September | 61.43 | 31.00 | 30.43 | 88.01 | 11.73 | 0.00 | 0.00 | 720.00 |
October | 57.49 | 34.09 | 23.40 | 79.22 | 17.50 | 0.00 | 0.00 | 744.00 |
November | 46.90 | 32.08 | 14.82 | 54.12 | 34.70 | 3.17 | 0.00 | 720.00 |
December | 39.21 | 25.73 | 13.48 | 40.67 | 40.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 62.49 | 37.23 | 25.26 | 83.46 | 23.86 | 12.67 | 0.00 | 8760.00 |
Minimum of Months | 39.21 | 25.73 | 13.48 | 40.67 | 8.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.88 | 51.41 | 36.94 | 122.61 | 45.23 | 8.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1051.47 | 749.97 | 301.50 | 1450.62 | 722.82 | 0.00 | 0.00 | 744.00 |
February | 953.42 | 617.16 | 336.26 | 1298.52 | 616.24 | 0.00 | 0.00 | 672.00 |
March | 608.45 | 274.50 | 333.96 | 780.44 | 542.92 | 0.00 | 0.00 | 744.00 |
April | 450.91 | 105.51 | 345.41 | 591.79 | 340.47 | 0.00 | 0.00 | 720.00 |
May | 344.55 | 14.51 | 330.03 | 662.88 | 74.24 | 0.00 | 0.00 | 744.00 |
June | 340.42 | 3.11 | 337.31 | 704.97 | 62.88 | 0.00 | 0.00 | 720.00 |
July | 356.35 | 6.46 | 349.88 | 733.06 | 35.98 | 0.00 | 0.00 | 744.00 |
August | 419.18 | 50.19 | 368.99 | 807.37 | 64.88 | 0.00 | 0.00 | 744.00 |
September | 503.00 | 132.47 | 370.53 | 884.60 | 101.88 | 0.00 | 0.00 | 720.00 |
October | 780.53 | 406.55 | 373.98 | 1314.41 | 209.07 | 0.00 | 0.00 | 744.00 |
November | 993.60 | 684.18 | 309.42 | 1482.18 | 478.18 | 0.00 | 0.00 | 720.00 |
December | 1027.44 | 737.94 | 289.49 | 1493.99 | 637.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 650.85 | 313.65 | 337.20 | 1015.87 | 322.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 340.42 | 3.11 | 289.49 | 591.79 | 35.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1051.47 | 749.97 | 373.98 | 1493.99 | 722.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1051.47 | 749.97 | 301.50 | 1457.56 | 695.49 | 0.00 | 0.00 | 744.00 |
February | 953.42 | 617.16 | 336.26 | 1304.16 | 595.56 | 0.00 | 0.00 | 672.00 |
March | 608.45 | 274.50 | 333.96 | 785.18 | 521.44 | 0.00 | 0.00 | 744.00 |
April | 450.91 | 105.51 | 345.41 | 591.48 | 331.22 | 0.00 | 0.00 | 720.00 |
May | 344.55 | 14.51 | 330.03 | 659.76 | 70.88 | 0.00 | 0.00 | 744.00 |
June | 340.42 | 3.11 | 337.31 | 701.32 | 59.59 | 0.00 | 0.00 | 720.00 |
July | 356.35 | 6.46 | 349.88 | 730.39 | 33.54 | 0.00 | 0.00 | 744.00 |
August | 419.18 | 50.19 | 368.99 | 804.16 | 61.65 | 0.00 | 0.00 | 744.00 |
September | 503.00 | 132.47 | 370.53 | 881.29 | 97.83 | 0.00 | 0.00 | 720.00 |
October | 780.53 | 406.55 | 373.98 | 1311.20 | 204.87 | 0.00 | 0.00 | 744.00 |
November | 993.60 | 684.18 | 309.42 | 1481.29 | 472.25 | 0.00 | 0.00 | 720.00 |
December | 1027.44 | 737.94 | 289.49 | 1498.90 | 616.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 650.85 | 313.65 | 337.20 | 1016.00 | 311.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 340.42 | 3.11 | 289.49 | 591.48 | 33.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1051.47 | 749.97 | 373.98 | 1498.90 | 695.49 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.35 | 154.32 | 62.04 | 312.86 | 123.05 | 0.00 | 0.00 | 744.00 |
February | 196.18 | 126.99 | 69.19 | 276.51 | 108.28 | 0.00 | 0.00 | 672.00 |
March | 125.20 | 56.48 | 68.72 | 165.85 | 94.35 | 0.00 | 0.00 | 744.00 |
April | 92.78 | 21.71 | 71.07 | 116.94 | 66.08 | 0.00 | 0.00 | 720.00 |
May | 70.90 | 2.99 | 67.91 | 108.41 | 23.68 | 0.00 | 0.00 | 744.00 |
June | 70.05 | 0.64 | 69.41 | 112.92 | 22.69 | 0.00 | 0.00 | 720.00 |
July | 73.32 | 1.33 | 71.99 | 116.33 | 16.39 | 4.67 | 0.00 | 744.00 |
August | 86.25 | 10.33 | 75.93 | 132.72 | 24.48 | 10.00 | 0.00 | 744.00 |
September | 103.50 | 27.26 | 76.24 | 156.19 | 31.40 | 0.00 | 0.00 | 720.00 |
October | 160.60 | 83.65 | 76.95 | 247.90 | 53.18 | 3.33 | 0.00 | 744.00 |
November | 204.45 | 140.78 | 63.67 | 301.70 | 92.02 | 0.00 | 0.00 | 720.00 |
December | 211.41 | 151.84 | 59.57 | 313.20 | 111.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 133.92 | 64.54 | 69.38 | 196.41 | 63.66 | 18.00 | 0.00 | 8760.00 |
Minimum of Months | 70.05 | 0.64 | 59.57 | 108.41 | 16.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 216.35 | 154.32 | 76.95 | 313.20 | 123.05 | 10.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115032E+09 | 76327710.81 | 38704260.47 | 0.118401E+09 | 0.121150E+09 |
February | 0.135331E+09 | 93317970.10 | 42013021.49 | 0.154287E+09 | 97545315.59 |
March | 0.163248E+09 | 0.101879E+09 | 61369057.46 | 0.197377E+09 | 91558061.21 |
April | 0.203237E+09 | 0.133248E+09 | 69989533.89 | 0.271844E+09 | 64885135.42 |
May | 0.200823E+09 | 0.115819E+09 | 85003856.96 | 0.293471E+09 | 27909233.36 |
June | 0.214819E+09 | 0.125342E+09 | 89477319.46 | 0.317809E+09 | 26511029.34 |
July | 0.206409E+09 | 0.107471E+09 | 98938754.41 | 0.304834E+09 | 22000423.35 |
August | 0.191982E+09 | 97047862.68 | 94933726.78 | 0.284433E+09 | 26034482.48 |
September | 0.159214E+09 | 80342029.27 | 78872262.60 | 0.228128E+09 | 30391527.38 |
October | 0.153983E+09 | 91302559.87 | 62680269.82 | 0.212174E+09 | 46875696.81 |
November | 0.121576E+09 | 83153545.30 | 38422051.83 | 0.140272E+09 | 89939943.57 |
December | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 0.107695E+09 |
Annual Sum or Average | 0.197067E+10 | 0.117415E+10 | 0.796521E+09 | 0.263196E+10 | 0.752495E+09 |
Minimum of Months | 0.105019E+09 | 68902090.30 | 36117040.60 | 0.108925E+09 | 22000423.35 |
Maximum of Months | 0.214819E+09 | 0.133248E+09 | 98938754.41 | 0.317809E+09 | 0.121150E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.281625E+10 | 0.200871E+10 | 0.807538E+09 | 0.388534E+10 | 0.193601E+10 |
February | 0.230652E+10 | 0.149304E+10 | 0.813480E+09 | 0.314139E+10 | 0.149081E+10 |
March | 0.162968E+10 | 0.735209E+09 | 0.894470E+09 | 0.209032E+10 | 0.145416E+10 |
April | 0.116877E+10 | 0.273478E+09 | 0.895291E+09 | 0.153392E+10 | 0.882491E+09 |
May | 0.922829E+09 | 38867334.72 | 0.883962E+09 | 0.177547E+10 | 0.198841E+09 |
June | 0.882370E+09 | 8053470.89 | 0.874316E+09 | 0.182729E+10 | 0.162977E+09 |
July | 0.954442E+09 | 17313771.82 | 0.937128E+09 | 0.196344E+10 | 96375308.26 |
August | 0.112274E+10 | 0.134426E+09 | 0.988316E+09 | 0.216246E+10 | 0.173781E+09 |
September | 0.130377E+10 | 0.343358E+09 | 0.960408E+09 | 0.229288E+10 | 0.264074E+09 |
October | 0.209056E+10 | 0.108889E+10 | 0.100167E+10 | 0.352052E+10 | 0.559980E+09 |
November | 0.257541E+10 | 0.177339E+10 | 0.802020E+09 | 0.384182E+10 | 0.123944E+10 |
December | 0.275189E+10 | 0.197651E+10 | 0.775382E+09 | 0.400150E+10 | 0.170854E+10 |
Annual Sum or Average | 0.205252E+11 | 0.989124E+10 | 0.106340E+11 | 0.320364E+11 | 0.101675E+11 |
Minimum of Months | 0.882370E+09 | 8053470.89 | 0.775382E+09 | 0.153392E+10 | 96375308.26 |
Maximum of Months | 0.281625E+10 | 0.200871E+10 | 0.100167E+10 | 0.400150E+10 | 0.193601E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.281625E+10 | 0.200871E+10 | 0.807538E+09 | 0.390394E+10 | 0.186279E+10 |
February | 0.230652E+10 | 0.149304E+10 | 0.813480E+09 | 0.315502E+10 | 0.144077E+10 |
March | 0.162968E+10 | 0.735209E+09 | 0.894470E+09 | 0.210301E+10 | 0.139664E+10 |
April | 0.116877E+10 | 0.273478E+09 | 0.895291E+09 | 0.153312E+10 | 0.858528E+09 |
May | 0.922829E+09 | 38867334.72 | 0.883962E+09 | 0.176709E+10 | 0.189836E+09 |
June | 0.882370E+09 | 8053470.89 | 0.874316E+09 | 0.181782E+10 | 0.154455E+09 |
July | 0.954442E+09 | 17313771.82 | 0.937128E+09 | 0.195626E+10 | 89821738.23 |
August | 0.112274E+10 | 0.134426E+09 | 0.988316E+09 | 0.215385E+10 | 0.165115E+09 |
September | 0.130377E+10 | 0.343358E+09 | 0.960408E+09 | 0.228431E+10 | 0.253586E+09 |
October | 0.209056E+10 | 0.108889E+10 | 0.100167E+10 | 0.351192E+10 | 0.548731E+09 |
November | 0.257541E+10 | 0.177339E+10 | 0.802020E+09 | 0.383950E+10 | 0.122407E+10 |
December | 0.275189E+10 | 0.197651E+10 | 0.775382E+09 | 0.401465E+10 | 0.165031E+10 |
Annual Sum or Average | 0.205252E+11 | 0.989124E+10 | 0.106340E+11 | 0.320405E+11 | 0.983465E+10 |
Minimum of Months | 0.882370E+09 | 8053470.89 | 0.775382E+09 | 0.153312E+10 | 89821738.23 |
Maximum of Months | 0.281625E+10 | 0.200871E+10 | 0.100167E+10 | 0.401465E+10 | 0.186279E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.579484E+09 | 0.413321E+09 | 0.166163E+09 | 0.837977E+09 | 0.329582E+09 |
February | 0.474600E+09 | 0.307214E+09 | 0.167385E+09 | 0.668926E+09 | 0.261960E+09 |
March | 0.335330E+09 | 0.151280E+09 | 0.184050E+09 | 0.444220E+09 | 0.252706E+09 |
April | 0.240491E+09 | 56272016.91 | 0.184219E+09 | 0.303097E+09 | 0.171270E+09 |
May | 0.189886E+09 | 7997520.07 | 0.181888E+09 | 0.290378E+09 | 63421937.46 |
June | 0.181560E+09 | 1657118.90 | 0.179903E+09 | 0.292677E+09 | 58809164.61 |
July | 0.196390E+09 | 3562560.66 | 0.192828E+09 | 0.311591E+09 | 43886187.00 |
August | 0.231020E+09 | 27660052.61 | 0.203360E+09 | 0.355467E+09 | 65562636.91 |
September | 0.268269E+09 | 70650884.68 | 0.197618E+09 | 0.404839E+09 | 81384710.21 |
October | 0.430164E+09 | 0.224056E+09 | 0.206108E+09 | 0.663981E+09 | 0.142433E+09 |
November | 0.529928E+09 | 0.364900E+09 | 0.165027E+09 | 0.782012E+09 | 0.238528E+09 |
December | 0.566242E+09 | 0.406696E+09 | 0.159546E+09 | 0.838880E+09 | 0.298158E+09 |
Annual Sum or Average | 0.422336E+10 | 0.203527E+10 | 0.218810E+10 | 0.619405E+10 | 0.200770E+10 |
Minimum of Months | 0.181560E+09 | 1657118.90 | 0.159546E+09 | 0.290378E+09 | 43886187.00 |
Maximum of Months | 0.579484E+09 | 0.413321E+09 | 0.206108E+09 | 0.838880E+09 | 0.329582E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 707.29 | 723.71 | 687.17 | 455.96 | 231.21 | 0.00 | 0.00 |
February | 1020.42 | 645.14 | 895.05 | 617.18 | 277.86 | 0.00 | 0.00 |
March | 1179.08 | 546.94 | 975.20 | 608.59 | 366.60 | 0.00 | 0.00 |
April | 1678.05 | 400.53 | 1254.55 | 822.52 | 432.03 | 0.00 | 0.00 |
May | 1753.11 | 166.72 | 1199.66 | 691.87 | 507.79 | 0.00 | 0.00 |
June | 1961.78 | 163.65 | 1326.04 | 773.72 | 552.33 | 0.00 | 0.00 |
July | 1820.99 | 131.42 | 1233.03 | 642.00 | 591.03 | 0.00 | 0.00 |
August | 1699.12 | 155.52 | 1146.84 | 579.74 | 567.11 | 0.00 | 0.00 |
September | 1408.20 | 187.60 | 982.80 | 495.94 | 486.87 | 0.00 | 0.00 |
October | 1267.47 | 280.02 | 919.85 | 545.42 | 374.43 | 0.00 | 0.00 |
November | 865.88 | 555.18 | 750.47 | 513.29 | 237.17 | 0.00 | 0.00 |
December | 650.68 | 643.34 | 627.35 | 411.60 | 215.75 | 0.00 | 0.00 |
Annual Sum or Average | 1335.34 | 381.78 | 999.83 | 595.71 | 404.12 | 0.00 | 0.00 |
Minimum of Months | 650.68 | 131.42 | 627.35 | 411.60 | 215.75 | 0.00 | 0.00 |
Maximum of Months | 1961.78 | 723.71 | 1326.04 | 822.52 | 591.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1450.62 | 722.82 | 1051.47 | 749.97 | 301.50 | 0.00 | 0.00 |
February | 1298.52 | 616.24 | 953.42 | 617.16 | 336.26 | 0.00 | 0.00 |
March | 780.44 | 542.92 | 608.45 | 274.50 | 333.96 | 0.00 | 0.00 |
April | 591.79 | 340.47 | 450.91 | 105.51 | 345.41 | 0.00 | 0.00 |
May | 662.88 | 74.24 | 344.55 | 14.51 | 330.03 | 0.00 | 0.00 |
June | 704.97 | 62.88 | 340.42 | 3.11 | 337.31 | 0.00 | 0.00 |
July | 733.06 | 35.98 | 356.35 | 6.46 | 349.88 | 0.00 | 0.00 |
August | 807.37 | 64.88 | 419.18 | 50.19 | 368.99 | 0.00 | 0.00 |
September | 884.60 | 101.88 | 503.00 | 132.47 | 370.53 | 0.00 | 0.00 |
October | 1314.41 | 209.07 | 780.53 | 406.55 | 373.98 | 0.00 | 0.00 |
November | 1482.18 | 478.18 | 993.60 | 684.18 | 309.42 | 0.00 | 0.00 |
December | 1493.99 | 637.90 | 1027.44 | 737.94 | 289.49 | 0.00 | 0.00 |
Annual Sum or Average | 1015.87 | 322.41 | 650.85 | 313.65 | 337.20 | 0.00 | 0.00 |
Minimum of Months | 591.79 | 35.98 | 340.42 | 3.11 | 289.49 | 0.00 | 0.00 |
Maximum of Months | 1493.99 | 722.82 | 1051.47 | 749.97 | 373.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1457.56 | 695.49 | 1051.47 | 749.97 | 301.50 | 0.00 | 0.00 |
February | 1304.16 | 595.56 | 953.42 | 617.16 | 336.26 | 0.00 | 0.00 |
March | 785.18 | 521.44 | 608.45 | 274.50 | 333.96 | 0.00 | 0.00 |
April | 591.48 | 331.22 | 450.91 | 105.51 | 345.41 | 0.00 | 0.00 |
May | 659.76 | 70.88 | 344.55 | 14.51 | 330.03 | 0.00 | 0.00 |
June | 701.32 | 59.59 | 340.42 | 3.11 | 337.31 | 0.00 | 0.00 |
July | 730.39 | 33.54 | 356.35 | 6.46 | 349.88 | 0.00 | 0.00 |
August | 804.16 | 61.65 | 419.18 | 50.19 | 368.99 | 0.00 | 0.00 |
September | 881.29 | 97.83 | 503.00 | 132.47 | 370.53 | 0.00 | 0.00 |
October | 1311.20 | 204.87 | 780.53 | 406.55 | 373.98 | 0.00 | 0.00 |
November | 1481.29 | 472.25 | 993.60 | 684.18 | 309.42 | 0.00 | 0.00 |
December | 1498.90 | 616.16 | 1027.44 | 737.94 | 289.49 | 0.00 | 0.00 |
Annual Sum or Average | 1016.00 | 311.85 | 650.85 | 313.65 | 337.20 | 0.00 | 0.00 |
Minimum of Months | 591.48 | 33.54 | 340.42 | 3.11 | 289.49 | 0.00 | 0.00 |
Maximum of Months | 1498.90 | 695.49 | 1051.47 | 749.97 | 373.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 312.86 | 123.05 | 216.35 | 154.32 | 62.04 | 0.00 | 0.00 |
February | 276.51 | 108.28 | 196.18 | 126.99 | 69.19 | 0.00 | 0.00 |
March | 165.85 | 94.35 | 125.20 | 56.48 | 68.72 | 0.00 | 0.00 |
April | 116.94 | 66.08 | 92.78 | 21.71 | 71.07 | 0.00 | 0.00 |
May | 108.41 | 23.68 | 70.90 | 2.99 | 67.91 | 0.00 | 0.00 |
June | 112.92 | 22.69 | 70.05 | 0.64 | 69.41 | 0.00 | 0.00 |
July | 116.33 | 16.39 | 73.32 | 1.33 | 71.99 | 0.00 | 0.00 |
August | 132.72 | 24.48 | 86.25 | 10.33 | 75.93 | 0.00 | 0.00 |
September | 156.19 | 31.40 | 103.50 | 27.26 | 76.24 | 0.00 | 0.00 |
October | 247.90 | 53.18 | 160.60 | 83.65 | 76.95 | 0.00 | 0.00 |
November | 301.70 | 92.02 | 204.45 | 140.78 | 63.67 | 0.00 | 0.00 |
December | 313.20 | 111.32 | 211.41 | 151.84 | 59.57 | 0.00 | 0.00 |
Annual Sum or Average | 196.41 | 63.66 | 133.92 | 64.54 | 69.38 | 0.00 | 0.00 |
Minimum of Months | 108.41 | 16.39 | 70.05 | 0.64 | 59.57 | 0.00 | 0.00 |
Maximum of Months | 313.20 | 123.05 | 216.35 | 154.32 | 76.95 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.189441E+10 | 0.193840E+10 | 0.184051E+10 | 0.122124E+10 | 0.619268E+09 | 0.00 | 0.00 |
February | 0.246859E+10 | 0.156073E+10 | 0.216530E+10 | 0.149309E+10 | 0.672208E+09 | 0.00 | 0.00 |
March | 0.315804E+10 | 0.146493E+10 | 0.261196E+10 | 0.163006E+10 | 0.981905E+09 | 0.00 | 0.00 |
April | 0.434950E+10 | 0.103816E+10 | 0.325180E+10 | 0.213197E+10 | 0.111983E+10 | 0.00 | 0.00 |
May | 0.469554E+10 | 0.446548E+09 | 0.321317E+10 | 0.185311E+10 | 0.136006E+10 | 0.00 | 0.00 |
June | 0.508494E+10 | 0.424176E+09 | 0.343711E+10 | 0.200547E+10 | 0.143164E+10 | 0.00 | 0.00 |
July | 0.487735E+10 | 0.352007E+09 | 0.330255E+10 | 0.171953E+10 | 0.158302E+10 | 0.00 | 0.00 |
August | 0.455093E+10 | 0.416552E+09 | 0.307171E+10 | 0.155277E+10 | 0.151894E+10 | 0.00 | 0.00 |
September | 0.365005E+10 | 0.486264E+09 | 0.254743E+10 | 0.128547E+10 | 0.126196E+10 | 0.00 | 0.00 |
October | 0.339479E+10 | 0.750011E+09 | 0.246373E+10 | 0.146084E+10 | 0.100288E+10 | 0.00 | 0.00 |
November | 0.224436E+10 | 0.143904E+10 | 0.194521E+10 | 0.133046E+10 | 0.614753E+09 | 0.00 | 0.00 |
December | 0.174279E+10 | 0.172311E+10 | 0.168031E+10 | 0.110243E+10 | 0.577873E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.421113E+11 | 0.120399E+11 | 0.315308E+11 | 0.187864E+11 | 0.127443E+11 | 0.00 | 0.00 |
Minimum of Months | 0.174279E+10 | 0.352007E+09 | 0.168031E+10 | 0.110243E+10 | 0.577873E+09 | 0.00 | 0.00 |
Maximum of Months | 0.508494E+10 | 0.193840E+10 | 0.343711E+10 | 0.213197E+10 | 0.158302E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.388534E+10 | 0.193601E+10 | 0.281625E+10 | 0.200871E+10 | 0.807538E+09 | 0.00 | 0.00 |
February | 0.314139E+10 | 0.149081E+10 | 0.230652E+10 | 0.149304E+10 | 0.813480E+09 | 0.00 | 0.00 |
March | 0.209032E+10 | 0.145416E+10 | 0.162968E+10 | 0.735209E+09 | 0.894470E+09 | 0.00 | 0.00 |
April | 0.153392E+10 | 0.882491E+09 | 0.116877E+10 | 0.273478E+09 | 0.895291E+09 | 0.00 | 0.00 |
May | 0.177547E+10 | 0.198841E+09 | 0.922829E+09 | 38867334.72 | 0.883962E+09 | 0.00 | 0.00 |
June | 0.182729E+10 | 0.162977E+09 | 0.882370E+09 | 8053470.89 | 0.874316E+09 | 0.00 | 0.00 |
July | 0.196344E+10 | 96375308.26 | 0.954442E+09 | 17313771.82 | 0.937128E+09 | 0.00 | 0.00 |
August | 0.216246E+10 | 0.173781E+09 | 0.112274E+10 | 0.134426E+09 | 0.988316E+09 | 0.00 | 0.00 |
September | 0.229288E+10 | 0.264074E+09 | 0.130377E+10 | 0.343358E+09 | 0.960408E+09 | 0.00 | 0.00 |
October | 0.352052E+10 | 0.559980E+09 | 0.209056E+10 | 0.108889E+10 | 0.100167E+10 | 0.00 | 0.00 |
November | 0.384182E+10 | 0.123944E+10 | 0.257541E+10 | 0.177339E+10 | 0.802020E+09 | 0.00 | 0.00 |
December | 0.400150E+10 | 0.170854E+10 | 0.275189E+10 | 0.197651E+10 | 0.775382E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.320364E+11 | 0.101675E+11 | 0.205252E+11 | 0.989124E+10 | 0.106340E+11 | 0.00 | 0.00 |
Minimum of Months | 0.153392E+10 | 96375308.26 | 0.882370E+09 | 8053470.89 | 0.775382E+09 | 0.00 | 0.00 |
Maximum of Months | 0.400150E+10 | 0.193601E+10 | 0.281625E+10 | 0.200871E+10 | 0.100167E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.390394E+10 | 0.186279E+10 | 0.281625E+10 | 0.200871E+10 | 0.807538E+09 | 0.00 | 0.00 |
February | 0.315502E+10 | 0.144077E+10 | 0.230652E+10 | 0.149304E+10 | 0.813480E+09 | 0.00 | 0.00 |
March | 0.210301E+10 | 0.139664E+10 | 0.162968E+10 | 0.735209E+09 | 0.894470E+09 | 0.00 | 0.00 |
April | 0.153312E+10 | 0.858528E+09 | 0.116877E+10 | 0.273478E+09 | 0.895291E+09 | 0.00 | 0.00 |
May | 0.176709E+10 | 0.189836E+09 | 0.922829E+09 | 38867334.72 | 0.883962E+09 | 0.00 | 0.00 |
June | 0.181782E+10 | 0.154455E+09 | 0.882370E+09 | 8053470.89 | 0.874316E+09 | 0.00 | 0.00 |
July | 0.195626E+10 | 89821738.23 | 0.954442E+09 | 17313771.82 | 0.937128E+09 | 0.00 | 0.00 |
August | 0.215385E+10 | 0.165115E+09 | 0.112274E+10 | 0.134426E+09 | 0.988316E+09 | 0.00 | 0.00 |
September | 0.228431E+10 | 0.253586E+09 | 0.130377E+10 | 0.343358E+09 | 0.960408E+09 | 0.00 | 0.00 |
October | 0.351192E+10 | 0.548731E+09 | 0.209056E+10 | 0.108889E+10 | 0.100167E+10 | 0.00 | 0.00 |
November | 0.383950E+10 | 0.122407E+10 | 0.257541E+10 | 0.177339E+10 | 0.802020E+09 | 0.00 | 0.00 |
December | 0.401465E+10 | 0.165031E+10 | 0.275189E+10 | 0.197651E+10 | 0.775382E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.320405E+11 | 0.983465E+10 | 0.205252E+11 | 0.989124E+10 | 0.106340E+11 | 0.00 | 0.00 |
Minimum of Months | 0.153312E+10 | 89821738.23 | 0.882370E+09 | 8053470.89 | 0.775382E+09 | 0.00 | 0.00 |
Maximum of Months | 0.401465E+10 | 0.186279E+10 | 0.281625E+10 | 0.200871E+10 | 0.100167E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.837977E+09 | 0.329582E+09 | 0.579484E+09 | 0.413321E+09 | 0.166163E+09 | 0.00 | 0.00 |
February | 0.668926E+09 | 0.261960E+09 | 0.474600E+09 | 0.307214E+09 | 0.167385E+09 | 0.00 | 0.00 |
March | 0.444220E+09 | 0.252706E+09 | 0.335330E+09 | 0.151280E+09 | 0.184050E+09 | 0.00 | 0.00 |
April | 0.303097E+09 | 0.171270E+09 | 0.240491E+09 | 56272016.91 | 0.184219E+09 | 0.00 | 0.00 |
May | 0.290378E+09 | 63421937.46 | 0.189886E+09 | 7997520.07 | 0.181888E+09 | 0.00 | 0.00 |
June | 0.292677E+09 | 58809164.61 | 0.181560E+09 | 1657118.90 | 0.179903E+09 | 0.00 | 0.00 |
July | 0.311591E+09 | 43886187.00 | 0.196390E+09 | 3562560.66 | 0.192828E+09 | 0.00 | 0.00 |
August | 0.355467E+09 | 65562636.91 | 0.231020E+09 | 27660052.61 | 0.203360E+09 | 0.00 | 0.00 |
September | 0.404839E+09 | 81384710.21 | 0.268269E+09 | 70650884.68 | 0.197618E+09 | 0.00 | 0.00 |
October | 0.663981E+09 | 0.142433E+09 | 0.430164E+09 | 0.224056E+09 | 0.206108E+09 | 0.00 | 0.00 |
November | 0.782012E+09 | 0.238528E+09 | 0.529928E+09 | 0.364900E+09 | 0.165027E+09 | 0.00 | 0.00 |
December | 0.838880E+09 | 0.298158E+09 | 0.566242E+09 | 0.406696E+09 | 0.159546E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.619405E+10 | 0.200770E+10 | 0.422336E+10 | 0.203527E+10 | 0.218810E+10 | 0.00 | 0.00 |
Minimum of Months | 0.290378E+09 | 43886187.00 | 0.181560E+09 | 1657118.90 | 0.159546E+09 | 0.00 | 0.00 |
Maximum of Months | 0.838880E+09 | 0.329582E+09 | 0.579484E+09 | 0.413321E+09 | 0.206108E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.01 | 8.64 | 3.24 | 3.12 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.57 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.53 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.81 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.36 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.89 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.01 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.46 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.87 | 10.53 | 3.17 | 6.00 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.01 | 8.64 | 2.44 | 3.12 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.65 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.77 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.86 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.04 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.75 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.93 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.95 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.72 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.63 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.03 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.82 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.65 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.63 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.2 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -1.8 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.94 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.57 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 17.99 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.55 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.11 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.8 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.2 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.10 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.48 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.76 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.54 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.83 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.16 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.78 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.48 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.10 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.54 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.08 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.78 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.222679E+10 | -.182577E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -401020416.6 | 58.99 | 0.00 | 0.00 |
February | 0.200747E+10 | -.164893E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -358540512.9 | 58.99 | 0.00 | 0.00 |
March | 0.219300E+10 | -.179970E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -393293154.6 | 58.99 | 0.00 | 0.00 |
April | 0.197981E+10 | -.160596E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373859546.0 | 58.99 | 0.00 | 0.00 |
May | 0.193021E+10 | -.154466E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385553096.1 | 58.99 | 0.00 | 0.00 |
June | 0.179464E+10 | -.142136E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373274274.0 | 58.99 | 0.00 | 0.00 |
July | 0.176573E+10 | -.137994E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385784265.5 | 58.99 | 0.00 | 0.00 |
August | 0.182554E+10 | -.143981E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385733046.9 | 58.99 | 0.00 | 0.00 |
September | 0.181297E+10 | -.143981E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373160243.4 | 58.99 | 0.00 | 0.00 |
October | 0.195943E+10 | -.157351E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385924688.0 | 58.99 | 0.00 | 0.00 |
November | 0.200253E+10 | -.162694E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -375596193.0 | 58.99 | 0.00 | 0.00 |
December | 0.217858E+10 | -.178274E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -395837231.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.236767E+11 | -.190891E+11 | 8760.00 | -.458758E+10 | 58.99 | |||||
Minimum of Months | 0.176573E+10 | -.182577E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -401020416.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.222679E+10 | -.137994E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -358540512.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.93 | 0.67 | 18-JAN-11:20 | 173.95 | 3.97 | 0.00 | 0.00 | 145.07 | 2.68 | 0.00 | 0.00 |
February | 295.50 | 0.90 | 0.58 | 03-FEB-12:30 | 212.09 | 4.80 | 0.00 | 0.83 | 176.37 | 3.36 | 0.00 | 0.00 |
March | 296.00 | 0.85 | 0.50 | 09-MAR-10:30 | 262.45 | 6.00 | 0.00 | 11.33 | 220.67 | 4.50 | 0.00 | 10.67 |
April | 347.33 | 0.85 | 0.50 | 04-APR-11:30 | 275.86 | 7.45 | 0.00 | 11.67 | 230.06 | 5.77 | 0.00 | 10.00 |
May | 353.67 | 0.84 | 0.50 | 04-MAY-11:50 | 290.63 | 9.25 | 0.00 | 11.83 | 241.85 | 7.58 | 0.00 | 8.17 |
June | 394.00 | 0.82 | 0.50 | 01-JUN-10:00 | 298.04 | 9.85 | 0.00 | 24.17 | 250.94 | 8.18 | 0.00 | 14.83 |
July | 390.00 | 0.81 | 0.50 | 01-JUL-10:00 | 324.06 | 10.21 | 0.00 | 43.33 | 272.02 | 8.57 | 0.00 | 22.83 |
August | 380.83 | 0.79 | 0.50 | 02-AUG-10:09 | 505.38 | 9.42 | 0.00 | 54.33 | 473.26 | 7.75 | 0.00 | 39.67 |
September | 342.17 | 0.79 | 0.50 | 01-SEP-11:09 | 1198.77 | 8.07 | 0.00 | 72.33 | 1275.08 | 6.49 | 0.00 | 58.33 |
October | 330.00 | 0.84 | 0.50 | 06-OCT-10:39 | 281.29 | 6.67 | 0.00 | 11.67 | 234.53 | 5.13 | 0.00 | 10.00 |
November | 308.00 | 0.92 | 0.67 | 01-NOV-11:50 | 184.60 | 4.06 | 0.00 | 0.00 | 154.42 | 2.73 | 0.00 | 0.00 |
December | 282.83 | 0.93 | 0.67 | 11-DEC-11:50 | 171.58 | 4.01 | 0.00 | 0.00 | 142.37 | 2.70 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | 0.85 | 356.80 | 7.22 | 0.00 | 241.50 | 326.28 | 5.68 | 0.00 | 174.50 | ||
Minimum of Months | 282.83 | 0.79 | 0.50 | 171.58 | 3.97 | 0.00 | 0.00 | 142.37 | 2.68 | 0.00 | 0.00 | |
Maximum of Months | 394.00 | 0.93 | 0.67 | 1198.77 | 10.21 | 0.00 | 72.33 | 1275.08 | 8.57 | 0.00 | 58.33 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.516972E+09 | 49868.47 | 10-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.442621E+09 | 49868.47 | 05-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.244059E+09 | 49868.47 | 12-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.279140E+09 | 49868.47 | 21-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148279E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.516972E+09 | 49868.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167092E+10 | 49967.06 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119471E+10 | 58550.05 | 05-FEB-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.698540E+09 | 37231.09 | 13-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103499E+10 | 54979.82 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.459916E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167092E+10 | 58550.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 69650674.79 | 5129.97 | 05-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102948E+09 | 28953.05 | 05-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101205E+09 | 28953.05 | 12-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 61255336.35 | 10729.95 | 21-DEC-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335059E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102948E+09 | 28953.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.247492E+09 | 23209.51 | 10-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268057E+09 | 23209.51 | 05-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.331054E+09 | 23209.51 | 11-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213625E+09 | 23209.51 | 21-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106023E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.331054E+09 | 23209.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118026E+09 | 24873.38 | 04-JAN-17:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328471E+09 | 24873.38 | 04-FEB-14:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 86793535.88 | 16304.11 | 11-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200146E+09 | 24873.38 | 20-DEC-16:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.733436E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.328471E+09 | 24873.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.265094E+10 | 0.170965E+10 | 28849.84 | 01-JAN-20:12 | 16523.34 | 0.00 |
February | 0.00 | 0.00 | 0.390467E+10 | 0.252171E+10 | 41928.85 | 28-FEB-22:45 | 19846.94 | 0.00 |
March | 0.00 | 0.00 | 0.614434E+10 | 0.420142E+10 | 41707.15 | 27-MAR-21:00 | 20594.00 | 0.00 |
April | 0.00 | 0.00 | 0.126572E+11 | 0.897359E+10 | 41573.77 | 04-APR-21:00 | 22620.78 | 0.00 |
May | 0.00 | 0.00 | 0.278975E+11 | 0.193306E+11 | 37453.36 | 07-MAY-18:13 | 29268.20 | 0.00 |
June | 0.00 | 0.00 | 0.300147E+11 | 0.210679E+11 | 38977.20 | 28-JUN-20:10 | 29208.34 | 0.00 |
July | 0.00 | 0.00 | 0.331249E+11 | 0.222577E+11 | 40587.19 | 07-JUL-20:10 | 30377.26 | 0.00 |
August | 0.00 | 0.00 | 0.331177E+11 | 0.225122E+11 | 41792.11 | 10-AUG-20:10 | 28122.87 | 0.00 |
September | 0.00 | 0.00 | 0.288794E+11 | 0.191082E+11 | 40646.27 | 03-SEP-18:43 | 30089.25 | 0.00 |
October | 0.00 | 0.00 | 0.235695E+11 | 0.161622E+11 | 41663.55 | 06-OCT-20:10 | 28921.72 | 0.00 |
November | 0.00 | 0.00 | 0.885856E+10 | 0.608501E+10 | 42134.93 | 08-NOV-06:00 | 20653.31 | 0.00 |
December | 0.00 | 0.00 | 0.553657E+10 | 0.368131E+10 | 41605.72 | 13-DEC-00:40 | 20538.18 | 0.00 |
Annual Sum or Average | 0.216356E+12 | 0.147612E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.265094E+10 | 0.170965E+10 | 28849.84 | 16523.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.331249E+11 | 0.225122E+11 | 42134.93 | 30377.26 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.147663E+11 | 0.903373E+10 | 193450.09 | 31-JAN-07:03 | 89576.15 | 0.00 |
February | 0.00 | 0.00 | 0.224591E+11 | 0.137993E+11 | 191486.62 | 26-FEB-09:02 | 93710.52 | 0.00 |
March | 0.00 | 0.00 | 0.346777E+11 | 0.223075E+11 | 195240.50 | 07-MAR-07:02 | 113521.54 | 0.00 |
April | 0.00 | 0.00 | 0.649391E+11 | 0.423960E+11 | 195833.90 | 29-APR-06:02 | 115890.50 | 0.00 |
May | 0.00 | 0.00 | 0.125989E+12 | 0.762778E+11 | 199837.09 | 23-MAY-06:02 | 106050.08 | 0.00 |
June | 0.00 | 0.00 | 0.134789E+12 | 0.810738E+11 | 199395.60 | 19-JUN-06:02 | 109252.62 | 0.00 |
July | 0.00 | 0.00 | 0.148130E+12 | 0.829227E+11 | 200978.86 | 02-JUL-08:62 | 107390.27 | 0.00 |
August | 0.00 | 0.00 | 0.144012E+12 | 0.823709E+11 | 201021.97 | 06-AUG-08:62 | 107986.48 | 0.00 |
September | 0.00 | 0.00 | 0.125277E+12 | 0.693576E+11 | 199831.07 | 17-SEP-08:62 | 108480.60 | 0.00 |
October | 0.00 | 0.00 | 0.104033E+12 | 0.618468E+11 | 200420.45 | 22-OCT-08:62 | 103975.62 | 0.00 |
November | 0.00 | 0.00 | 0.455842E+11 | 0.284125E+11 | 196992.50 | 02-NOV-06:02 | 113297.30 | 0.00 |
December | 0.00 | 0.00 | 0.287949E+11 | 0.174961E+11 | 196078.60 | 12-DEC-07:02 | 111700.18 | 0.00 |
Annual Sum or Average | 0.993450E+12 | 0.587295E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.147663E+11 | 0.903373E+10 | 191486.62 | 89576.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.148130E+12 | 0.829227E+11 | 201021.97 | 115890.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.452468E+10 | 0.331946E+10 | 24712.47 | 16-JAN-19:12 | 13977.04 | 0.00 |
February | 0.00 | 0.00 | 0.575784E+10 | 0.416721E+10 | 25116.46 | 01-FEB-23:01 | 13329.95 | 0.00 |
March | 0.00 | 0.00 | 0.654538E+10 | 0.479013E+10 | 25546.48 | 28-MAR-22:45 | 12333.55 | 0.00 |
April | 0.00 | 0.00 | 0.103678E+11 | 0.754986E+10 | 25326.85 | 15-APR-21:25 | 12597.39 | 0.00 |
May | 0.00 | 0.00 | 0.191733E+11 | 0.132595E+11 | 21163.58 | 25-MAY-20:10 | 15853.97 | 0.00 |
June | 0.00 | 0.00 | 0.200168E+11 | 0.138571E+11 | 22306.71 | 28-JUN-20:10 | 16641.73 | 0.00 |
July | 0.00 | 0.00 | 0.221085E+11 | 0.145861E+11 | 24588.84 | 19-JUL-20:43 | 18876.20 | 0.00 |
August | 0.00 | 0.00 | 0.227595E+11 | 0.154011E+11 | 25262.05 | 10-AUG-20:10 | 17190.33 | 0.00 |
September | 0.00 | 0.00 | 0.209915E+11 | 0.140453E+11 | 24564.64 | 10-SEP-18:08 | 18044.30 | 0.00 |
October | 0.00 | 0.00 | 0.195861E+11 | 0.140163E+11 | 25208.60 | 07-OCT-21:43 | 18360.12 | 0.00 |
November | 0.00 | 0.00 | 0.106685E+11 | 0.797228E+10 | 25074.47 | 07-NOV-21:43 | 18628.38 | 0.00 |
December | 0.00 | 0.00 | 0.746547E+10 | 0.551390E+10 | 24541.93 | 27-DEC-24:00 | 13961.01 | 0.00 |
Annual Sum or Average | 0.169965E+12 | 0.118478E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.452468E+10 | 0.331946E+10 | 21163.58 | 12333.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.227595E+11 | 0.154011E+11 | 25546.48 | 18876.20 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.297064E+10 | 0.202552E+10 | 20924.96 | 17-JAN-21:20 | 10396.82 | 0.00 |
February | 0.00 | 0.00 | 0.382910E+10 | 0.258599E+10 | 20918.21 | 21-FEB-21:20 | 9913.71 | 0.00 |
March | 0.00 | 0.00 | 0.427365E+10 | 0.289670E+10 | 21181.52 | 31-MAR-20:30 | 10571.48 | 0.00 |
April | 0.00 | 0.00 | 0.689195E+10 | 0.466870E+10 | 20709.22 | 19-APR-20:20 | 12199.43 | 0.00 |
May | 0.00 | 0.00 | 0.150647E+11 | 0.971585E+10 | 17772.54 | 07-MAY-18:43 | 13479.81 | 0.00 |
June | 0.00 | 0.00 | 0.160620E+11 | 0.103709E+11 | 18876.70 | 28-JUN-20:10 | 13174.06 | 0.00 |
July | 0.00 | 0.00 | 0.181818E+11 | 0.111561E+11 | 20474.41 | 07-JUL-20:10 | 14271.61 | 0.00 |
August | 0.00 | 0.00 | 0.187078E+11 | 0.118214E+11 | 21183.88 | 10-AUG-20:10 | 13329.55 | 0.00 |
September | 0.00 | 0.00 | 0.170346E+11 | 0.105948E+11 | 20696.28 | 01-SEP-20:43 | 14769.11 | 0.00 |
October | 0.00 | 0.00 | 0.159557E+11 | 0.107319E+11 | 21108.66 | 24-OCT-20:10 | 13628.31 | 0.00 |
November | 0.00 | 0.00 | 0.790522E+10 | 0.554303E+10 | 20817.42 | 07-NOV-21:43 | 14393.63 | 0.00 |
December | 0.00 | 0.00 | 0.530273E+10 | 0.368463E+10 | 20772.88 | 08-DEC-22:00 | 11128.24 | 0.00 |
Annual Sum or Average | 0.132180E+12 | 0.857955E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.297064E+10 | 0.202552E+10 | 17772.54 | 9913.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.187078E+11 | 0.118214E+11 | 21183.88 | 14769.11 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 64822445.23 | 0.02 | 934.04 | 03-JAN-08:04 | 0.91 |
February | 71972529.07 | 0.03 | 934.04 | 04-FEB-08:05 | 0.91 |
March | 25527340.46 | 0.01 | 934.04 | 09-MAR-08:04 | 0.91 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 53900837.28 | 0.02 | 934.04 | 04-DEC-08:05 | 0.91 |
Annual Sum or Average | 0.216223E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71972529.07 | 0.03 | 934.04 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136884E+10 | 0.32 | 2108.33 | 10-JAN-05:02 | 0.88 |
February | 0.124389E+10 | 0.32 | 2108.33 | 05-FEB-07:01 | 0.88 |
March | 0.139191E+10 | 0.33 | 2108.33 | 12-MAR-06:01 | 0.88 |
April | 0.137340E+10 | 0.36 | 2108.33 | 17-APR-20:47 | 0.87 |
May | 0.157079E+10 | 0.45 | 1958.31 | 07-MAY-18:13 | 0.84 |
June | 0.158370E+10 | 0.47 | 2009.59 | 28-JUN-20:10 | 0.85 |
July | 0.168127E+10 | 0.48 | 2108.33 | 07-JUL-20:10 | 0.87 |
August | 0.168814E+10 | 0.48 | 2108.33 | 02-AUG-20:10 | 0.87 |
September | 0.157004E+10 | 0.46 | 2108.33 | 03-SEP-18:10 | 0.87 |
October | 0.155403E+10 | 0.43 | 2108.33 | 04-OCT-20:10 | 0.87 |
November | 0.134425E+10 | 0.34 | 1851.29 | 04-NOV-23:22 | 0.82 |
December | 0.138523E+10 | 0.34 | 2108.33 | 21-DEC-05:02 | 0.88 |
Annual Sum or Average | 0.177555E+11 | 0.40 | |||
Minimum of Months | 0.124389E+10 | 0.32 | 1851.29 | 0.82 | |
Maximum of Months | 0.168814E+10 | 0.48 | 2108.33 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.789549E+10 | 0.50 | 12216.17 | 01-JAN-09:02 | 1.37 |
February | 0.716117E+10 | 0.50 | 12216.17 | 01-FEB-07:03 | 1.36 |
March | 0.800952E+10 | 0.51 | 12216.17 | 01-MAR-07:02 | 1.37 |
April | 0.771430E+10 | 0.50 | 12216.17 | 01-APR-06:02 | 1.36 |
May | 0.818151E+10 | 0.51 | 12216.17 | 01-MAY-06:02 | 1.36 |
June | 0.832473E+10 | 0.53 | 12216.17 | 01-JUN-06:02 | 1.36 |
July | 0.885007E+10 | 0.53 | 12216.17 | 01-JUL-06:02 | 1.36 |
August | 0.873926E+10 | 0.53 | 12216.17 | 01-AUG-06:02 | 1.36 |
September | 0.806100E+10 | 0.51 | 12216.17 | 01-SEP-06:02 | 1.36 |
October | 0.819420E+10 | 0.51 | 12216.17 | 01-OCT-08:62 | 1.37 |
November | 0.757933E+10 | 0.50 | 12216.17 | 01-NOV-06:02 | 1.36 |
December | 0.789780E+10 | 0.50 | 12216.17 | 09-DEC-07:03 | 1.36 |
Annual Sum or Average | 0.966084E+11 | 0.51 | |||
Minimum of Months | 0.716117E+10 | 0.50 | 12216.17 | 1.36 | |
Maximum of Months | 0.885007E+10 | 0.53 | 12216.17 | 1.37 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.814444E+09 | 0.36 | 1042.62 | 01-JAN-08:61 | 0.84 |
February | 0.747551E+09 | 0.37 | 1221.69 | 01-FEB-23:01 | 0.90 |
March | 0.834279E+09 | 0.37 | 1221.69 | 12-MAR-06:01 | 0.91 |
April | 0.822894E+09 | 0.41 | 1081.22 | 30-APR-22:51 | 0.85 |
May | 0.944978E+09 | 0.48 | 1021.15 | 25-MAY-20:10 | 0.83 |
June | 0.955238E+09 | 0.50 | 1082.79 | 28-JUN-20:10 | 0.85 |
July | 0.102418E+10 | 0.51 | 1221.69 | 07-JUL-21:23 | 0.90 |
August | 0.105940E+10 | 0.52 | 1221.69 | 02-AUG-20:43 | 0.90 |
September | 0.100058E+10 | 0.51 | 1221.69 | 03-SEP-18:08 | 0.90 |
October | 0.104439E+10 | 0.50 | 1221.69 | 04-OCT-20:08 | 0.90 |
November | 0.857295E+09 | 0.41 | 1221.69 | 02-NOV-20:08 | 0.90 |
December | 0.848287E+09 | 0.39 | 1003.29 | 15-DEC-21:10 | 0.82 |
Annual Sum or Average | 0.109535E+11 | 0.45 | |||
Minimum of Months | 0.747551E+09 | 0.36 | 1003.29 | 0.82 | |
Maximum of Months | 0.105940E+10 | 0.52 | 1221.69 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.626788E+09 | 0.35 | 945.82 | 10-JAN-05:02 | 0.91 |
February | 0.572027E+09 | 0.35 | 945.82 | 05-FEB-07:01 | 0.91 |
March | 0.637014E+09 | 0.35 | 945.82 | 11-MAR-05:02 | 0.91 |
April | 0.617021E+09 | 0.37 | 945.82 | 17-APR-20:41 | 0.90 |
May | 0.708467E+09 | 0.45 | 809.32 | 07-MAY-18:43 | 0.84 |
June | 0.718674E+09 | 0.47 | 858.82 | 28-JUN-20:10 | 0.86 |
July | 0.781912E+09 | 0.49 | 945.82 | 07-JUL-20:10 | 0.90 |
August | 0.810101E+09 | 0.50 | 945.82 | 02-AUG-20:08 | 0.90 |
September | 0.764429E+09 | 0.49 | 945.82 | 01-SEP-20:43 | 0.90 |
October | 0.800631E+09 | 0.48 | 945.82 | 04-OCT-20:08 | 0.90 |
November | 0.647884E+09 | 0.39 | 945.82 | 02-NOV-20:08 | 0.90 |
December | 0.648405E+09 | 0.37 | 945.82 | 21-DEC-05:02 | 0.91 |
Annual Sum or Average | 0.833335E+10 | 0.42 | |||
Minimum of Months | 0.572027E+09 | 0.35 | 809.32 | 0.84 | |
Maximum of Months | 0.810101E+09 | 0.50 | 945.82 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 0.00 |
February | 0.08 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.33 | 0.00 |
November | 0.00 | 0.00 |
December | 0.08 | 0.00 |
Annual Sum or Average | 0.66 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.33 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.78 | 25.84 |
February | 1.10 | 25.84 |
March | 1.25 | 25.84 |
April | 1.61 | 21.83 |
May | 1.58 | 0.00 |
June | 1.92 | 0.00 |
July | 1.58 | 0.00 |
August | 2.00 | 0.00 |
September | 1.08 | 0.00 |
October | 1.37 | 3.92 |
November | 1.35 | 24.24 |
December | 1.90 | 25.84 |
Annual Sum or Average | 17.53 | 11.59 |
Minimum of Months | 0.78 | 0.00 |
Maximum of Months | 2.00 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.63 | 0.25 |
February | 1.12 | 0.09 |
March | 2.35 | 0.00 |
April | 0.32 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 1.68 | 0.06 |
November | 3.11 | 0.00 |
December | 1.03 | 0.59 |
Annual Sum or Average | 11.24 | 0.11 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.11 | 0.59 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.17 | 0.12 |
February | 0.92 | 0.00 |
March | 0.08 | 0.00 |
April | 0.22 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.82 | 0.12 |
November | 3.10 | 0.04 |
December | 0.83 | 0.57 |
Annual Sum or Average | 7.14 | 0.12 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.10 | 0.57 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 6.08 | 0.00 |
February | 3.87 | 0.00 |
March | 3.96 | 0.00 |
April | 2.55 | 0.00 |
May | 0.58 | 0.00 |
June | 1.08 | 0.00 |
July | 0.72 | 0.00 |
August | 1.39 | 0.00 |
September | 1.47 | 0.00 |
October | 3.90 | 0.00 |
November | 3.56 | 0.00 |
December | 4.22 | 0.00 |
Annual Sum or Average | 33.39 | 0.00 |
Minimum of Months | 0.58 | 0.00 |
Maximum of Months | 6.08 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.204698E+10 | 0.646215E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.223697E+10 | 0.553276E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.296992E+10 | 0.305074E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.461792E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.865274E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.921016E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.100375E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.100163E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.874706E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.746177E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.359601E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.278522E+10 | 0.348926E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.723785E+11 | 0.185349E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.204698E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.100375E+11 | 0.646215E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.119914E+11 | 0.208865E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.133130E+11 | 0.149338E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.175339E+11 | 0.873175E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.254114E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.416070E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.439473E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.473466E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.462749E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.404563E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.355502E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.199091E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156916E+11 | 0.129374E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.359033E+12 | 0.574895E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.119914E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.473466E+11 | 0.208865E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.189591E+10 | 87063343.49 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.210857E+10 | 0.128685E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.241138E+10 | 0.126506E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.337203E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.568354E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.591251E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.644910E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.662793E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.606791E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.577048E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.339555E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.261868E+10 | 76569170.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.523136E+11 | 0.418824E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.189591E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.662793E+10 | 0.128685E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.133824E+10 | 0.309365E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.147703E+10 | 0.335071E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.167614E+10 | 0.413818E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.232141E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.440503E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.465599E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.519168E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.534569E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.484910E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.463023E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.252775E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.190405E+10 | 0.267031E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.403224E+11 | 0.132528E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.133824E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.534569E+10 | 0.413818E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136884E+10 | 0.265094E+10 | 0.516972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124389E+10 | 0.388339E+10 | 0.442621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139191E+10 | 0.613583E+10 | 0.244059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137340E+10 | 0.126392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157079E+10 | 0.278975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158370E+10 | 0.300147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168127E+10 | 0.331249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168814E+10 | 0.331177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157004E+10 | 0.288794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155403E+10 | 0.235116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134425E+10 | 0.884164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138523E+10 | 0.552811E+10 | 0.279140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177555E+11 | 0.216225E+12 | 0.148279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124389E+10 | 0.265094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168814E+10 | 0.331249E+11 | 0.516972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.789549E+10 | 0.147663E+11 | 0.167092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.716117E+10 | 0.224591E+11 | 0.119471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.800952E+10 | 0.346777E+11 | 0.698540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.771430E+10 | 0.649391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.818151E+10 | 0.125989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.832473E+10 | 0.134789E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.885007E+10 | 0.148130E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.873926E+10 | 0.144012E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.806100E+10 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.819420E+10 | 0.104033E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.757933E+10 | 0.455842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.789780E+10 | 0.287949E+11 | 0.103499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.966084E+11 | 0.993450E+12 | 0.459916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.716117E+10 | 0.147663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.885007E+10 | 0.148130E+12 | 0.167092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.814444E+09 | 0.449656E+10 | 69650674.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.747551E+09 | 0.574076E+10 | 0.102948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.834279E+09 | 0.650004E+10 | 0.101205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.822894E+09 | 0.103526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.944978E+09 | 0.191733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.955238E+09 | 0.200168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102418E+10 | 0.221085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105940E+10 | 0.227595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100058E+10 | 0.209915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104439E+10 | 0.195326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.857295E+09 | 0.106169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.848287E+09 | 0.744678E+10 | 61255336.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109535E+11 | 0.169736E+12 | 0.335059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.747551E+09 | 0.449656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.105940E+10 | 0.227595E+11 | 0.102948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.626788E+09 | 0.293600E+10 | 0.247492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.572027E+09 | 0.380730E+10 | 0.268057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.637014E+09 | 0.425751E+10 | 0.331054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.617021E+09 | 0.688494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.708467E+09 | 0.150647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.718674E+09 | 0.160620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.781912E+09 | 0.181818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.810101E+09 | 0.187078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.764429E+09 | 0.170346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.800631E+09 | 0.159219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.647884E+09 | 0.784993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.648405E+09 | 0.529051E+10 | 0.213625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.833335E+10 | 0.131999E+12 | 0.106023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.572027E+09 | 0.293600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.810101E+09 | 0.187078E+11 | 0.331054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.136884E+10 | 0.00 | 0.00 | 0.00 | 0.678140E+09 | 0.00 | 0.646215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124389E+10 | 0.00 | 0.00 | 0.00 | 0.993078E+09 | 0.00 | 0.553276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139191E+10 | 0.00 | 0.00 | 0.00 | 0.157801E+10 | 0.00 | 0.305074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137340E+10 | 0.00 | 0.00 | 0.00 | 0.324452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157079E+10 | 0.00 | 0.00 | 0.00 | 0.708194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158370E+10 | 0.00 | 0.00 | 0.00 | 0.762646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168127E+10 | 0.00 | 0.00 | 0.00 | 0.835624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168814E+10 | 0.00 | 0.00 | 0.00 | 0.832812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157004E+10 | 0.00 | 0.00 | 0.00 | 0.717702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155403E+10 | 0.00 | 0.00 | 0.00 | 0.590775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134425E+10 | 0.00 | 0.00 | 0.00 | 0.225176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138523E+10 | 0.00 | 0.00 | 0.00 | 0.139999E+10 | 0.00 | 0.348926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177555E+11 | 0.00 | 0.00 | 0.00 | 0.546230E+11 | 0.00 | 0.185349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.124389E+10 | 0.00 | 0.00 | 0.00 | 0.678140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168814E+10 | 0.00 | 0.00 | 0.00 | 0.835624E+10 | 0.00 | 0.646215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.789549E+10 | 0.00 | 0.00 | 0.00 | 0.409587E+10 | 0.00 | 0.208865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.716117E+10 | 0.00 | 0.00 | 0.00 | 0.615180E+10 | 0.00 | 0.149338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.800952E+10 | 0.00 | 0.00 | 0.00 | 0.952436E+10 | 0.00 | 0.873175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.771430E+10 | 0.00 | 0.00 | 0.00 | 0.176971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.818151E+10 | 0.00 | 0.00 | 0.00 | 0.334255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.832473E+10 | 0.00 | 0.00 | 0.00 | 0.356226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.885007E+10 | 0.00 | 0.00 | 0.00 | 0.384965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.873926E+10 | 0.00 | 0.00 | 0.00 | 0.375357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.806100E+10 | 0.00 | 0.00 | 0.00 | 0.323953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.819420E+10 | 0.00 | 0.00 | 0.00 | 0.273560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.757933E+10 | 0.00 | 0.00 | 0.00 | 0.123298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.789780E+10 | 0.00 | 0.00 | 0.00 | 0.779377E+10 | 0.00 | 0.129374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.966084E+11 | 0.00 | 0.00 | 0.00 | 0.262424E+12 | 0.00 | 0.574895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.716117E+10 | 0.00 | 0.00 | 0.00 | 0.409587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.885007E+10 | 0.00 | 0.00 | 0.00 | 0.384965E+11 | 0.00 | 0.208865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.814444E+09 | 0.00 | 0.00 | 0.00 | 0.108146E+10 | 0.00 | 87063343.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.747551E+09 | 0.00 | 0.00 | 0.00 | 0.136102E+10 | 0.00 | 0.128685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.834279E+09 | 0.00 | 0.00 | 0.00 | 0.157710E+10 | 0.00 | 0.126506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.822894E+09 | 0.00 | 0.00 | 0.00 | 0.254914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.944978E+09 | 0.00 | 0.00 | 0.00 | 0.473857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.955238E+09 | 0.00 | 0.00 | 0.00 | 0.495727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102418E+10 | 0.00 | 0.00 | 0.00 | 0.542492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105940E+10 | 0.00 | 0.00 | 0.00 | 0.556853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100058E+10 | 0.00 | 0.00 | 0.00 | 0.506733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104439E+10 | 0.00 | 0.00 | 0.00 | 0.472609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.857295E+09 | 0.00 | 0.00 | 0.00 | 0.253825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.848287E+09 | 0.00 | 0.00 | 0.00 | 0.177040E+10 | 0.00 | 76569170.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109535E+11 | 0.00 | 0.00 | 0.00 | 0.413601E+11 | 0.00 | 0.418824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.747551E+09 | 0.00 | 0.00 | 0.00 | 0.108146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.105940E+10 | 0.00 | 0.00 | 0.00 | 0.556853E+10 | 0.00 | 0.128685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.626788E+09 | 0.00 | 0.00 | 0.00 | 0.711454E+09 | 0.00 | 0.309365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.572027E+09 | 0.00 | 0.00 | 0.00 | 0.905006E+09 | 0.00 | 0.335071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.637014E+09 | 0.00 | 0.00 | 0.00 | 0.103913E+10 | 0.00 | 0.413818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.617021E+09 | 0.00 | 0.00 | 0.00 | 0.170439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.708467E+09 | 0.00 | 0.00 | 0.00 | 0.369656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.718674E+09 | 0.00 | 0.00 | 0.00 | 0.393732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.781912E+09 | 0.00 | 0.00 | 0.00 | 0.440977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.810101E+09 | 0.00 | 0.00 | 0.00 | 0.453559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.764429E+09 | 0.00 | 0.00 | 0.00 | 0.408468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.800631E+09 | 0.00 | 0.00 | 0.00 | 0.382960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.647884E+09 | 0.00 | 0.00 | 0.00 | 0.187987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.648405E+09 | 0.00 | 0.00 | 0.00 | 0.125565E+10 | 0.00 | 0.267031E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.833335E+10 | 0.00 | 0.00 | 0.00 | 0.319890E+11 | 0.00 | 0.132528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.572027E+09 | 0.00 | 0.00 | 0.00 | 0.711454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.810101E+09 | 0.00 | 0.00 | 0.00 | 0.453559E+10 | 0.00 | 0.413818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.309202E+10 | 0.301942E+09 | 0.00 | 1990176.44 | 12896239.06 | 0.273425E+09 | 0.144201E+10 | 0.00 | 0.26 |
February | 0.184835E+10 | 0.428519E+09 | 0.00 | 3116878.84 | 8317020.43 | 0.171043E+09 | 0.173110E+10 | 0.00 | 0.31 |
March | 0.141681E+10 | 0.972302E+09 | 0.00 | 3767530.11 | 107036.12 | 0.122941E+09 | 0.241325E+10 | 0.00 | 0.34 |
April | 0.180158E+09 | 0.220500E+10 | 0.00 | 4425600.73 | 406369.58 | 0.00 | 0.190295E+10 | 0.00 | 0.37 |
May | 0.00 | 0.751326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
June | 0.00 | 0.856098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
July | 0.00 | 0.102062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
August | 0.00 | 0.953010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.806282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
October | 65051322.24 | 0.583503E+10 | 0.00 | 4085502.23 | 0.00 | 0.00 | 0.120004E+10 | 0.00 | 0.30 |
November | 0.575188E+09 | 0.170578E+10 | 0.00 | 6461316.01 | 2185001.38 | 0.00 | 0.309836E+10 | 0.00 | 0.42 |
December | 0.231979E+10 | 0.106295E+10 | 1155324.69 | 3096580.75 | 11041470.28 | 93653448.95 | 0.199030E+10 | 1891.85 | 0.30 |
Annual Sum or Average | 0.949737E+10 | 0.563849E+11 | 1155324.69 | 26943585.10 | 34953136.85 | 0.661063E+09 | 0.137780E+11 | 1891.85 | 0.28 |
Minimum of Months | 0.00 | 0.301942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Maximum of Months | 0.309202E+10 | 0.102062E+11 | 1155324.69 | 6461316.01 | 12896239.06 | 0.273425E+09 | 0.309836E+10 | 1891.85 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.233042E+11 | 0.281655E+10 | 0.00 | 15511378.75 | 36565530.00 | 84789620.92 | 0.991925E+10 | 0.00 | 0.44 |
February | 0.130418E+11 | 0.420245E+10 | 0.00 | 20519012.77 | 4473504.82 | 0.206061E+09 | 0.110846E+11 | 0.00 | 0.47 |
March | 0.111799E+11 | 0.842284E+10 | 0.00 | 24494419.81 | 37379712.84 | 51574848.41 | 0.126436E+11 | 0.00 | 0.49 |
April | 0.128441E+10 | 0.179976E+11 | 0.00 | 25450422.56 | 0.105948E+09 | 0.00 | 0.782605E+10 | 0.00 | 0.49 |
May | 0.00 | 0.572214E+11 | 0.00 | 0.00 | 0.587226E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
June | 881357.36 | 0.643885E+11 | 0.00 | 309233.65 | 0.530701E+09 | 0.00 | 602733.71 | 0.00 | 0.41 |
July | 0.00 | 0.762550E+11 | 0.00 | 0.00 | 0.596095E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.711026E+11 | 0.00 | 0.00 | 0.499331E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.595594E+11 | 0.00 | 0.00 | 0.469328E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
October | 0.752743E+09 | 0.445322E+11 | 0.00 | 16476538.11 | 0.356731E+09 | 0.00 | 0.456842E+10 | 0.00 | 0.44 |
November | 0.479238E+10 | 0.130397E+11 | 0.00 | 33443993.78 | 91913269.79 | 0.00 | 0.129649E+11 | 0.00 | 0.51 |
December | 0.177643E+11 | 0.823102E+10 | 0.00 | 19458952.02 | 0.102294E+09 | 56815949.33 | 0.100418E+11 | 0.00 | 0.46 |
Annual Sum or Average | 0.721206E+11 | 0.427769E+12 | 0.00 | 0.155664E+09 | 0.341798E+10 | 0.399241E+09 | 0.690493E+11 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.281655E+10 | 0.00 | 0.00 | 4473504.82 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.233042E+11 | 0.762550E+11 | 0.00 | 33443993.78 | 0.596095E+09 | 0.206061E+09 | 0.129649E+11 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.895630E+09 | 0.567109E+09 | 0.00 | 9026870.10 | 537900.61 | 8078507.01 | 0.357678E+10 | 0.00 | 0.67 |
February | 0.666692E+09 | 0.818446E+09 | 0.00 | 5682059.60 | 0.00 | 27906114.03 | 0.228679E+10 | 0.00 | 0.65 |
March | 0.682151E+09 | 0.115127E+10 | 0.00 | 5190428.58 | 105954.91 | 28975980.54 | 0.210934E+10 | 0.00 | 0.63 |
April | 0.103757E+09 | 0.215793E+10 | 0.00 | 2845326.92 | 128554.58 | 0.00 | 0.916702E+09 | 0.00 | 0.57 |
May | 0.00 | 0.619376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.688337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
July | 0.00 | 0.814823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.774098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.675879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
October | 28044190.36 | 0.518465E+10 | 0.00 | 3287961.16 | 0.00 | 0.00 | 0.728979E+09 | 0.00 | 0.52 |
November | 0.128817E+09 | 0.183378E+10 | 0.00 | 8906600.87 | 0.00 | 0.00 | 0.236404E+10 | 0.00 | 0.73 |
December | 0.665568E+09 | 0.123314E+10 | 0.00 | 8422162.75 | 1295359.70 | 15486918.20 | 0.294563E+10 | 0.00 | 0.65 |
Annual Sum or Average | 0.317066E+10 | 0.486715E+11 | 0.00 | 43361409.97 | 2067769.81 | 80447519.79 | 0.149283E+11 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.567109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.895630E+09 | 0.814823E+10 | 0.00 | 9026870.10 | 1295359.70 | 28975980.54 | 0.357678E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.157584E+10 | 0.438847E+09 | 0.00 | 3782479.00 | 1431125.41 | 70110971.32 | 0.174504E+10 | 0.00 | 0.52 |
February | 0.107034E+10 | 0.661732E+09 | 0.00 | 2506633.35 | 1466166.40 | 85705974.78 | 0.113897E+10 | 0.00 | 0.50 |
March | 0.107319E+10 | 0.921049E+09 | 0.00 | 2256187.16 | 975607.15 | 0.142889E+09 | 0.919170E+09 | 0.00 | 0.51 |
April | 0.229548E+09 | 0.175635E+10 | 0.00 | 1726108.09 | 2499277.23 | 0.00 | 0.667929E+09 | 0.00 | 0.52 |
May | 0.00 | 0.568370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.644563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.768261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.729979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.629595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
October | 85033603.62 | 0.491241E+10 | 0.00 | 2078512.52 | 0.00 | 0.00 | 0.444546E+09 | 0.00 | 0.47 |
November | 0.283443E+09 | 0.164619E+10 | 0.00 | 5661456.12 | 0.00 | 0.00 | 0.159192E+10 | 0.00 | 0.60 |
December | 0.125796E+10 | 0.108094E+10 | 0.00 | 4228067.31 | 2498641.71 | 90095128.25 | 0.147834E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.557536E+10 | 0.448252E+11 | 0.00 | 22239443.57 | 8870817.89 | 0.388801E+09 | 0.798592E+10 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.438847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.157584E+10 | 0.768261E+10 | 0.00 | 5661456.12 | 2499277.23 | 0.142889E+09 | 0.174504E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |